Loading…
Loading…
Updated dates
Tender Value
₹6.0 Cr
EMD Value
₹12.0 L
Closing Date
19 Feb 2026, 4:30 pmClosed
Deputy General Manager, Contract and Procurement
Contracts and Procurement Division, Admin Building, Indira Sagar Power Station, NHDC Ltd, Narmada Nagar
Construction of 2nd floor of new admin building along with centralized air conditioning, lift and electrification work of new admin building at Indira Sagar Power Station, Narmada Nagar, Distt. Khandwa (M.P.).
2026_NHDC_894540_1
NIT NO. 35/3232/2025-26 Dated 16/01/2026
Open Tender
Civil Works - Buildings
330 days
Indira Sagar Power Station, Narmada Nagar
As per tender document
3 documents required · 3 mandatory
₹1,770
NHDC Limited
₹12.0 L
Yes
16 Mar 2026
19 Jan 2026
23 Feb 2026
19 Jan 2026
19 Feb 2026
19 Jan 2026
19 Jan 2026 - 2 Feb 2026
Civil works
Centering and shuttering including strutting, propping etc. and removal of form for: Columns, Pillars, Piers, Abutments, Posts and Struts.
Centering and shuttering including strutting, propping etc. and removal of form for: Lintels, beams, girders, bressumers and cantilevers
Centering and shuttering including strutting, propping etc. and removal of form for: Stairs, (excluding landings) except spiral-Staircases.
Centering and shuttering including strutting, propping etc. and removal of form for: Suspended floors, roofs, landings, balconies and access platform.
Centering and shuttering including strutting, propping etc. and removal of form for: Shelves (Cast in situ)
Centering and shuttering including strutting, propping etc. and removal of form for: Weather shade, Chajjas, corbels etc., including Edges.
Centering and shuttering in cluding strutting, propping etc. and removal of form for: Small surfaces such as cantilever ends, brackets and ends of steps, caps and bases to pilasters and columns and the like.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding including cost of binding wire all wastages and overlaps, couplers (overlaps shall be provided as per requirement of IS 13920 for ductile detalingIS 456 RCC Design & SP 34 Reinforcement detailing ) etc. complete . (Note:- 1. Spacer bars (chairs) shall be paid separately as shown in the drawing and as per direction of engineer in charge. 2. No extra payment shall be done for overlaps and/or couplers. 3.Couplers shall be conforming to IS code on “Reinforcement Couplers for Mechanical Splices of Bars for Concrete Reinforcement - Specification”) Thermo-Mechanically Treated bars.FE 500 D or more conforming to IS 1786
Add extra for providing reinforcement above Floor two level for every additional floor or part thereof.
Extra for providing and mixing water proofing material as per IS standard in cement concrete work quantity as prescribed by the manufacturer.
Providing and fixing M.S. fan clamp type I or II of 16 mm dia M.S. bar bent to shape with hooked ends in R.C.C. slabs, beams during laying including painting the exposed portion of loop, all as per standard design complete.
Reinforced cement concrete work (with 20 mm nominal size graded stone aggregate) in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, posts and struts etc. above plinth level and upto floor two level excluding cost of centering, shuttering, finishing and reinforcement:M-20 Grade Concrete.
Reinforced cement concrete work (with 20 mm nominal size graded stone aggregate) in beams, suspended floors, roofs having slope of any degree landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral staircases above plinth level and upto floor two level excluding the cost of centering, shuttering, finishing and reinforcement in concrete grade. M-20 Grade Concrete
Extra for R.C.C. work above floor two level for each floors or part thereof for item 12. (For 2nd floor)
Extra for R.C.C. work above floor two level for each floors or part thereof for item 13. (For 2nd floor)
Brick work with fly ash lime bricks (FALG Bricks) conforming to IS:12894-2002, in super structure above plinth level up to floor two level in : Having 75 kg / cm2 average compressive strength. Cement mortar 1:6 (1 cement : 6 sand)
Extra for brick work in superstructure above floor two levels for each additional floor or part thereof respective item. (Full Brick)
Half brick masonry with fly ash lime Gypsum bricks (FALG bricks) conforming to IS: 12894, in super structure above plinth and upto floor two level. Having 75 kg/cm2 average compressive strength. . Cement mortar 1 : 4 (1 cement : 4 sand)
Extra for half brick masonry in superstructure, above floor two level for every floor or part thereof respective item.
Providing and fixing panelled or panelled and glazed shutters for doors, windows and clerestory windows including ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws excluding, panelling/glazing which will be paid for separately, all complete as per direction of Engineer-in-charge. Second class teak wood 30 mm thick shutters
Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured). Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick: Second class teak wood
Float glass panes 5 mm thick glass pane (weight not less than 12.5 kg/sqm)
Extra for providing frosted glass panes 4 mm thick instead of ordinary float glass panes 4 mm thick in doors, windows and clerestory window shutters. (Area of opening for glass panes excluding portion inside rebate shall be measured).
Providing and fixing factory made integral PVC flush door shutter made from rigid PVC foam sheet (Single Extruded) with density not less than 600 kg/cum, conforming to IS: 2380 part 14 for screw holding strength with Celluka finish surfaces on both sides at the manufacturing process itself, manufactured by an ISO : 9001 - 2000 certified company. 28 to 30 mm thick plain solid PVC flush door shutter
Providing and fixing bright finished brass handles with necessary screws etc. complete. : 125 mm
Providing and fixing bright finished brass sliding door bolts with nuts and screws etc complete.: 300x16mm
Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete : : 250x10 mm
Providing and fixing bright finished brass hanging type floor door stopper with necessary screws, etc. complete.
Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm) with double speed adjustment with necessary accessories and screws etc. complete.
Providing and fixing stainless steel (Grade 304) railing made of Hollowtubes, channels, plates etc. including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete i/c fixing the railing with necessary accessories and stainless steel dash fasteners, stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer in-charge. (For payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.)
6 mm cement plaster of mix : 1:3 (1 cement : 3 fine sand)
12 mm cement plaster of mix :1:4 (1 cement: 4 fine sand)
15 mm cement plaster on the rough side of single or half brick wall of mix 1:4 (1 cement : 4 sand)
Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. Fixed to openings /wooden frames with rawl plugs screws etc.
Providing and fixing Ceramic glazed wall tiles 300x450 mm or more (having thickness 6 to 7 mm) of 1st quality conforming to IS: 15622 of approved make in all Colours& shades, except burgundy, bottle green, black laid on 12mm thick bed of Cement Mortar 1:3 (1 Cement: 3 sand)preprad same day when mortar is still green jointed with grey cement slurry @3.3 kg per sqm including pointing the joints with white cement and matching pigments etc., complete.
Providing and laying Ceramic glazed floor tiles 300x300 mm or more (having thickness 6 to 7mm) of 1st quality conforming to IS : 15622 of approved make in any colours and shade laid on20 mm thick Cement Mortar 1:4 (1 Cement : 4 sand) including pointing the joints with white cement and matching pigment etc., complete.
Providing and laying digital print random design(PGVT)/(GVT) vitrified tiles in different sizes with water absorption less than 0.05% and conforming to IS:15622 of approved make in all colours& shades, 1st quality/ premium quality including grouting the joints with white cement and matching pigments etc. complete For floor glossy/ rustic /stain/matt finished laid on 20mm thick cement mortar 1:4 (1 cement:4sand) Size 1200X2400 mm thickness 9-10 mm
Providing and laying digital print random design(PGVT)/(GVT) vitrified tiles in different sizes with water absorption less than 0.05% and conforming to IS:15622 of approved make in all colours& shades, 1st quality / premium in skirting, riser laid our 12mm thick cement mortar 113 including grouting the joints with white cement and matching pigments etc. complete For skirting, risers etc. glossy/ rustic /stain/matt finished in all colours and shades Size 600X600 mm thickness 9-10 mm
Providing and laying Granite stone flooring in required design and patterns in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry admixed with pigment of matching shade including rubbing, curing and polishing and as directed by the Engineer-in-Charge Granite stone slab Dark Black. Dark Red, White or equivalent, Flamed Finish Granite
Granite stone work 18mm thick of any colour in riser of steps, skirting, dado and pillars laid on 12 mm average thick cement mortar 1:3 (1 cement:3 sand) and jointed with white cement slurry mixed with pigment to match the shade of slab.
Providing edge moulding to 18mm thick marble stone counters, Vanities, window sills etc. including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. Granite work.
Providing and fixing in wall lining flat pressed three layer (medium density) particle board or graded wood Pre laminated one side decorative lamination on other side balancing lamination Grade I, Type II, IS : 12823 marked including priming coat on unexposed surface, with necessary fixing arrangement and screws etc. complete : 18 mm thick
Providing and fixing false ceiling at all height including providing andfixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed tothe ceiling with dash fastener 12.5 mmdia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in adirection perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with 12.5 mm thick tapered edge gypsum boardFire resistant Glass Reinforced Gypsum (GRG) board conforming to IS: 2095- (Part 3) : 1996 (Board with BIS certification marks)
Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound) content. With water thinnable cement primer on wall surface having VOC content less than 50 grams/litre.
Finishing walls by any mechanical or manual means with Premium Acrylic Smooth exterior paint (Premium exterior) of required shade including all scaffolding. New work (Two or more coat applied @1.67ltr/10sqm over and including one coat undiluted exterior waterproofing coating @ 2.39 litre/10sqm with crack bridging ability of upto 0.5 mm on horizontal surfaces with an elongation of 150% and water proofing of upto 3 bars on vertical surface)
Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade: Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture.
Providing and applying white cement based putty of average thickness 1 mm, of approved brand over the plastered wall surface to prepare the surface even and smooth i/c all cost of material, labour and scaffold etc in all position complete. Note : Putty shall be applied only on the internal walls, for application on the exterior walls prior permission of APD/Chief Engineer will be required.
Wall painting by any mechanical or manual means with plastic emulsion paint of approved brand and manufacture to give an even shade: Two or more coats on new work
Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound) content. With ready mixed pink or grey primer on wood work (hard and soft wood) having VOC content less than 50 grams/litre.
Mealamine polishing on door windows by preparing the surface applying putty base course. Prepare the surface smooth by sand papering and then applying mealamine polish with air compressor. Two or more coats on new works including a coat of wood filler.
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For Fixed Portion Powder coated aluminium (minimum thickness of powder coating 50 micron)
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For shutters of doors, windows and ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately). Powder coated aluminium (minimum thickness of powder coating 50 micron)
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber/ neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item) : With float glass panes of 5.50 mm thickness
Providing and fixing white vitreous china Anti germ Fluoro-Polymer Coated Water closet squatting pan with 100 mm sand cast Iron P and S- trap, and 7.2 liter Low level, dual flush, PP (Poly Propylene) made open slim wall hung cistern capacity 3 liter/6 liter flushing, with allfittings and fixtures complete including cutting and making good the wall and floors wherever required. White Vitreous china Anti germ Fluoro-Polymer coated Orissa Pattern W. C. Pan of Size 440 x 575 x 250mm With integral foot rests. (Premium Range)
Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350mm with white PVC automatic flushing cistern, with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS : 2556, C.I. trap with outlet grating and other couplings in C.P. brass including painting of fittings and cutting and making good the walls and floors wherever required Range of three half stall urinals with 10 litre P.V.C. automatic flushing cistern.
Providing & Fixing 8mm thick froasted Urinal glass partition size 900x450mm brass made bracket with chrome plating.
Providing and fixing white vitreous china pedestal type Anti germ Fluoro-Polymer Coated Water Closet with soft closing seat cover, and 7.2 litre Low level slim dual flushing, PP (Poly Propeline) made 80 mm thick concealed flushing cistern, flushing capacity 3 litre/6 litre, with all fittings and fixtures complete including cutting and making good the wall and floors wherever required. Anti-germ Fluoro-Polymer Coated (nano coating) European W. C. Pan of Size 360X545X395mm With integral foot rests. (Premium Range)
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps,32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require : White Vitreous China Wash basin size 630x450 mm with a pair of 15 mm C.P. brass pillar taps.
Providing and fixing UPVC trap of self cleaning design complete. Including cost of cutting and making good the wall and floors. 100 mm inlet and 75 mm outlet
Providing and fixing uplasticised PVC connection pipe with brass unions : 45 cm length 15 mm nominal bore
Providing and fixing CP jet assembly to including connection etc complete.
Providing and fixing C.P. brass grating of approved quality and make conforming to IS: specification 100 mm dia.
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I. brackets and stainless steel plug 40 mm including painting of fittings and brackets, cutting and making good the walls wherever required : Kitchen sink without drain board 610x510 mm bowl depth 200 mm.
Providing and fixing CP brass towel rail of approved quality and make 600x20mm.
Providing and fixing PTMT towel ring trapezoidal shape 215mm long, 200mm wide with a minimum distances of 37mm from wall face with concealed fittings arrangement of approved quality and colour. Weighing not less than 88 gms.
Providing and fixing toilet paper holder : C.P.BRASS
Providing and fixing CP brass soap dish of approved quality and make
Providing and fixing bevelled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes and fittings with one step CPVC solvent cement and testing of jointscomplete as per direction of Engineer- in- Charge.Concealed work including cutting chases and making good the walls etc 20 mm nominal outer dia .Pipes.
Providing and fixing G.I. pipes complete with G.I. fittings and clamps, including cutting and making good the walls etc. Internal work - Exposed on wall 25 mm dia. nominal bore
Providing and fixing G.I. pipes complete with G.I. fittings and clamps, including cutting and making good the walls etc. Internal work - Exposed on wall 32 mm dia. nominal bore
Providing and fixing C.P. brass bib cock of approved quality conforming to IS: 8931and weighing not less than 400gm, 15 mm nominal bore.
Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS: 8931. 15 mm nominal bore.
Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) 25 mm nominal bore
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : 15mm nominal bore
Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflowpipes but without fittings and the base support for tank
Providing and fixing on wall face Unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion. (i) 110 mm diameter (minimum wall thickness 2.2mm)
Providing and fixing on wall face Unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion. (i) Single socketed pipes 75 mm diameter (minimum wall thickness 1.8mm)
Providing and fixing on wall face Unplasticised - PVC moulded fittings/ accessories for Unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.Bend 87.5° 75 mm bend (minimum wall thickness 1.8mm)
Providing and fixing on wall face Unplasticised - PVC moulded fittings/ accessories for Unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion. Bend 87.5° 110 mm bend (minimum wall thickness 2.2mm)
Providing and fixing on wall face Unplasticised - UPVC moulded fittings/ accessories for Unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion. Single tee with door 75x75x75 mm (minimum wall thickness 1.8mm)
Providing and fixing on wall face Unplasticised - UPVC moulded fittings/ accessories for Unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion. Single tee with door 110x110x110 mm (minimum wall thickness 2.2mm)
Providing and fixing on wall face Unplasticised - UPVC moulded fittings/ accessories for Unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion. Single tee without door 75x75x75 mm (minimum wall thickness 1.8mm)
Providing and fixing on wall face Unplasticised - UPVC moulded fittings/ accessories for Unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion. Single tee without door 110x110x110 mm (minimum wall thickness 2.2mm)
Providing and fixing unplasticised - PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 75 mm (minimum wall thickness 1.8mm)
Providing and fixing unplasticised - PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 110 mm (minimum wall thickness 2.2mm)
Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931. 15mm nominal bore
Providing and fixing C.P. brass wall mixer of approved quality and make conforming to IS:specification. 15 mm nominal bore. .
Providing and fixing PTMT Bottle Trap for Wash basin and sink. Bottle trap 38mm single piece moulded with height of 270mm, effective length of tail pipe 260mm from the centre of the waste coupling 77mm breadth with 25mm minimum water seal, weighting not less than 263gms.
Water proofing treatment over Roof, Wall, Chajjas,, Balcony with fibre glass mesh and Sealer coat at leakage/ seepage area consisting of (i) Surface preparation roughening of surface, opening cracks in ‘V’ groove in size of 5mmX10mm (WXD), filling of cracks with putty with laying fiber glass mesh, Cleaning of surface by scrubbing with steel wire/Nylon brush. Removing all dust particles and washing with adequate water to clean completely. (ii) Providing and applying 1st coat of fibre glass mesh (minimum thicknes 70-80 micron) and two component flexible waterproof and protective modified mortar, dry powder 80% chemical 20% acrylic resin having 30% solid contents) with mix proportion of part 1 and 2 with proper mixing with laying of fiber glass mesh (of weaving size of 10X10 yarn/inch duly coated with alkaline resistant polymer). Allow the coating to air cure for minimum 2 Hrs. After two hours of 1st coat applying 2nd coat (minimum thickness 100 micron) of fibre glass mesh of with mix proporation of part 1 and 2 with proper mixing. Allow the coating to air cure for minimum 2 hrs. Consumption of two component should be acrylic resin @17.90 kg for 10 sqm area or as per manufacture instructions. (After two coats of diamond shield, surface is to be cured properly minimum for 4 hrs. before application of third coat). (iii) Providing and applying 1st coat of sealer coat 50-60 micron (single component Hight build elastomeric, fixable pure acrylic waterproofing membrane having solid content of 65%) and allow it to air cure for 4Hrs. minimum. After two hours minimum of 1st coat applying 2nd and finals coat 120-140 micron of sealer coat and allow it to air cure for 4 Hrs mimimum. Consumption of Sealer coat should be @ 5.40 kg per 10 sqm area. (iv) The treated area should be cure with water for 48 hrs. by flooding the surface. (v) The final appearance of the coating will be milky white. All above operations to be done in order.(five years guarantee)
Designing, fabricating, testing, installing and fixing in position Curtain Wall with Aluminum Composite Panel (ACP) Cladding, with open grooves for linear as well as curvilinear portions of the building, for all heights and all levels etc. including: a) Structural analysis and design and preparation of shopdrawings for pressure equalisation or rain screen principle as required, proper drainage of water to make it watertight including checking of all the structural and functional design. b) Providing, fabricating and supplying and fixing panels of aluminum composite panel cladding in pan shape in metalic colour of approved shades. The aluminum composite panel cladding sheet shall be coil coated, with kynar 500 based PVDF / fluoropolymer resin coating of approved colour and shade on face # 1 and polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc. c) The fastening brackets of Aluminum alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated washers to arrest the wind load movement, fasteners, SS 316Pins and anchor bolts of approved make in SS 316, Nylonseparators to prevent bi-metallic contacts all complete required to perform as per specification and drawing The item includes cost of all material and labour component, the cost of all mock ups at site, cost of all samples of the individual componentsfor testing in an approved laboratory, field tests on the assembled working curtain wall with aluminum composite panel cladding, cleaning and protection of the curtain wall with aluminum composite panel cladding till the handing over of the building for occupation. Base frame work for ACP cladding is payable under the relevant aluminum items. The Contractor shall provide curtain wall with aluminum composite panel cladding, having all the performance characteristics all complete, as per theArchitectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer- in-Charge. However, for the purpose of payment, only the actual area on the external faceof the curtain wall with Aluminum Composite Panel Cladding (including width ofgroove) shall be measured in sqm. upto two decimal places. 4 mm thick aluminum composite pannel material consisting of 3 mm thick FR grade mineral core sandwiched between two aluminum sheets (each 0.5mm thick)
"Design, supply and installation of suspended Spider Glazing system designed to withstand the wind pressure as pr IS 875 (Part III). The Suspended System held with Spider Fittings of SS-316 Grade Steel of approved manufacturer with glass panel having 12 mm thick clear toughened glass held together with SS- 316 Grade Stainless steel Spider and bolt assembly with laminated glass fins 21 mm thick. The Glass fins and glass panel assembly shall beconnected to Slab/beams by means of SS 316 Grade stainless steel brackets and Anchor bolts and at the bottom using SS channel of 50x25x2mm using fastener and anchor bolts, non staining weather sealants of approved make, Teflon/ nylon bushes and separators to prevent bi-metallic contacts, all completeto perform as per specificationand approved drawings. The complete system to be designed to accommodate thermal expansion and seismic movements etc. The joints between glass panels (6 to 8 mm) and gaps at the perimeter and in U channel of the assembly to be filled with none staining weather sealant, so as to make the entire system fully air tight, water proof and dust proof. The rate shall include all design, Engineering and shop drawing including approval fromstructural designer, labour,TandP, scaffolding, other incidental charges including wastage, enabling temporary services all fitting fixers nutbolts, washer, Buffer plates, fastener, anchors, SS channel laminated glass etc. all complete. For the purpose of payment, actual elevation area of Glazing including thickness of joints and the portion of Glass panel inside the SS channel shall bemeasured.
GENERAL ELECTRIFICATION WORK
Concealed PVC conduit HMS: Supply and fixing PVC conduits required confirming to IS 9537 (Part-3), ISI marked along with the accessories in concealed system etc. as required PVC. conduit 25 mm (HMS)
Concealed PVC conduit HMS: Supply and fixing PVC conduits required confirming to IS 9537 (Part-3), ISI marked along with the accessories in concealed system etc. as required PVC. conduit 32 mm (HMS)
Supplying and fixing of approved make modular type G.I. metal box 1.2mm minimum thick and depth 50mm for single row boxes and 60mm depth for two/three row boxes earth terminal stud with nut and washer with modular base and cover plate including fixing in concealed etc. as required for:- 1or 2 Module metal box
Supplying and fixing of approved make modular type G.I. metal box 1.2mm minimum thick and depth 50mm for single row boxes and 60mm depth for two/three row boxes earth terminal stud with nut and washer with modular base and cover plate including fixing in concealed etc. as required for:- 4 Module metal box
Supplying and fixing of approved make modular type G.I. metal box 1.2mm minimum thick and depth 50mm for single row boxes and 60mm depth for two/three row boxes earth terminal stud with nut and washer with modular base and cover plate including fixing in concealed etc. as required for:- 6 Module metal box
Supplying and fixing of approved make modular type G.I. metal box 1.2mm minimum thick and depth 50mm for single row boxes and 60mm depth for two/three row boxes earth terminal stud with nut and washer with modular base and cover plate including fixing in concealed etc. as required for:- 8/9 Module metal box
Supplying and fixing of approved make modular type G.I. metal box 1.2mm minimum thick and depth 50mm for single row boxes and 60mm depth for two/three row boxes earth terminal stud with nut and washer with modular base and cover plate including fixing in concealed etc. as required for:- 12 Module metal box
Supplying and fixing of approved make modular type G.I. metal box 1.2mm minimum thick and depth 50mm for single row boxes and 60mm depth for two/three row boxes earth terminal stud with nut and washer with modular base and cover plate including fixing in concealed etc. as required for:- 18 Module metal box
Point wiring (excluding metallic switch box & sheet but including switches, sockets, lamp holders/ceiling roses etc) with 1.5sq. mm. PVC insulated cable FR-LSH with copper multi strand conductor ISI marked in concealed rigid P.V.C. conduit (HMS) ISI marked of suitable size and 1.5sq. mm. PVC insulated FRLS copper earth continuity conductor of green colour inside conduit, screwless connector for joints etc. as required as per specification for :- Light point/fan points. Using modular accessories Primary short point
Point wiring (excluding metallic switch box & sheet but including switches, sockets, lamp holders/ceiling roses etc) with 1.5sq. mm. PVC insulated cable FR-LSH with copper multi strand conductor ISI marked in concealed rigid P.V.C. conduit (HMS) ISI marked of suitable size and 1.5sq. mm. PVC insulated FRLS copper earth continuity conductor of green colour inside conduit, screwless connector for joints etc. as required as per specification for :- Light point/fan points. Using modular accessories Primary medium point
Point wiring (excluding metallic switch box & sheet but including switches, sockets, lamp holders/ceiling roses etc) with 1.5sq. mm. PVC insulated cable FR-LSH with copper multi strand conductor ISI marked in concealed rigid P.V.C. conduit (HMS) ISI marked of suitable size and 1.5sq. mm. PVC insulated FRLS copper earth continuity conductor of green colour inside conduit, screwless connector for joints etc. as required as per specification for :- Light point/fan points. Using modular accessories Primary long point
Point wiring (excluding metallic switch box & sheet but including switches, sockets, lamp holders/ceiling roses etc) with 1.5sq. mm. PVC insulated cable FR-LSH with copper multi strand conductor ISI marked in concealed rigid P.V.C. conduit (HMS) ISI marked of suitable size and 1.5sq. mm. PVC insulated FRLS copper earth continuity conductor of green colour inside conduit, screwless connector for joints etc. as required as per specification for :- Call bell/buzzer points. Using modular accessories Medium point
Point wiring (excluding metallic switch box & sheet but including switches, sockets, lamp holders/ceiling roses etc) with 1.5sq. mm. PVC insulated cable FR-LSH with copper multi strand conductor ISI marked in concealed rigid P.V.C. conduit (HMS) ISI marked of suitable size and 1.5sq. mm. PVC insulated FRLS copper earth continuity conductor of green colour inside conduit, screwless connector for joints etc. as required as per specification for :- Call bell/buzzer points. Using modular accessories Long point
Point wiring (excluding metallic switch box & sheet but including switches, sockets, lamp holders/ceiling roses etc) with 1.5sq. mm. PVC insulated cable FR-LSH with copper multi strand conductor ISI marked in concealed rigid P.V.C. conduit (HMS) ISI marked of suitable size and 1.5sq. mm. PVC insulated FRLS copper earth continuity conductor of green colour inside conduit, screwless connector for joints etc. as required as per specification for :- Twin control light points. Using modular accessories Medium point
Supplying and drawing single core PVC insulated cable FR-LSH with copper multi strand conductor ISI marked in existing rigid PVC casing and capping/conduit in surface or concealed as per specification. 2.5 sq. mm. wire 3 X 2.5 sq. mm.
Supplying and drawing single core PVC insulated cable FR-LSH with copper multi strand conductor ISI marked in existing rigid PVC casing and capping/conduit in surface or concealed as per specification. 2.5 sq. mm. wire 6 X 2.5 sq. mm.
Supplying and drawing single core PVC insulated cable FR-LSH with copper multi strand conductor ISI marked in existing rigid PVC casing and capping/conduit in surface or concealed as per specification. 4.00 sq. mm. wire 3 X 4.00 sq. mm.
Supplying and drawing single core PVC insulated cable FR-LSH with copper multi strand conductor ISI marked in existing rigid PVC casing and capping/conduit in surface or concealed as per specification. 4.00 sq. mm. wire 6 X 4.00 sq. mm.
Supplying and drawing single core PVC insulated cable FR-LSH with copper multi strand conductor ISI marked in existing rigid PVC casing and capping/conduit in surface or concealed as per specification. 6.00 sq. mm. wire 3 X 6.00 sq. mm.
Supplying and drawing single core PVC insulated cable FR-LSH with copper multi strand conductor ISI marked in existing rigid PVC casing and capping/conduit in surface or concealed as per specification. 6.00 sq. mm. wire 5 X 6.00 sq. mm.
Supplying of approved make, powder coated metal double door vertical TPN MCB DB IP 43 protection with provision for MCCB upto 160A TP/FP 36kA as incomer and space for SP/TP MCBs as outgoing (without MCCB/MCBs) inclusive of busbar & connections etc 8 Way without MCCB
Supplying of approved make, powder coated metal double door vertical TPN MCB DB IP 43 protection with provision for MCCB upto 160A TP/FP 36kA as incomer and space for SP/TP MCBs as outgoing (without MCCB/MCBs) inclusive of busbar & connections etc 4 Way without MCCB
Supplying of approved make TPN MCB DB metal double door IP 43 protection with provision for FP MCB/ Isolator/ RCCB/RCBO as incomer and SP MCBs as outgoing inclusive of busbar, neutral bar, earth bar, connection copper wire not less than 16 sq.mm & two earth terminals etc. complete as per IS:13032(exclusive of MCB & isolator): 6 Way (8+18)
Supply of approved make powder coated sheet steel encloser SPN MCB DB inclusive of busbar, neutral bar, earth bar, connection copper wire not less than 16 sq.mm & two earth terminals etc. complete as per IS:13032(exclusive of MCB & isolator)- 12 Way double door IP 43 protection
Supply of ISI marked and accepted standard of miniature circuit breaker (MCB) of 'C' series with short circuit indication, suitable for 240/415 Volts,50 Cycle, 10 kA/15 kA Value AC supply conforming to IS : 8828 : 1996, IEC : 60898 :2002 & 60947-2 but without enclosures :- Triple pole - MCB TP For 40Amp 10kA rating
Supply of ISI marked and accepted standard of miniature circuit breaker (MCB) of 'C' series with short circuit indication, suitable for 240/415 Volts,50 Cycle, 10 kA/15 kA Value AC supply conforming to IS : 8828 : 1996, IEC : 60898 :2002 & 60947-2 but without enclosures :- Tripole pole - MCB TP 50Amp to 63Amp 10kA rating
Supplying and installing of RCBOs (Residual current circuit breaker with overload and short circuit protection) ISI marked complete as per I.S. standard conforming to IEC:61009-1 & IS:12640-2, 240/415V 50 Hz with 10 kA short circuit withstand capacity for earth leakage, overload & short circuit protection including connection in existing enclosure in approved manner as per specification. 2 pole 32Amp, 30mA sensitivity
Supplying and installing of RCBOs (Residual current circuit breaker with overload and short circuit protection) ISI marked complete as per I.S. standard conforming to IEC:61009-1 & IS:12640-2, 240/415V 50 Hz with 10 kA short circuit withstand capacity for earth leakage, overload & short circuit protection including connection in existing enclosure in approved manner as per specification. 4 pole 40Amp, 30mA sensitivity
Supply of ISI marked and accepted standard of miniature circuit breaker (MCB) of 'C' series with short circuit indication, suitable for 240/415 Volts,50 Cycle, 10 kA/15 kA Value AC supply conforming to IS : 8828 : 1996, IEC : 60898 :2002 & 60947-2 but without enclosures :- Single pole - MCB SP 6Amp to 32Amp 10kA rating
Labour charges for fixing sheet steel enclosures, MCB/MCCBDB flush mounting type, as per accepted practice, duly embedded and end plate completely flushed in wall, cable connection etc. complete :- for item no. 115 & 116
Labour charges for fixing sheet steel enclosures, MCB/MCCBDB flush mounting type, as per accepted practice, duly embedded and end plate completely flushed in wall, cable connection etc. complete :- for item no. 117 & 118
Fixing of MCB/MCCB/Isolator in sheet steel enclosure as required as per accepted practice, including mounting on busbar and cable connection etc. complete (labour only) MCB/Isolator SP/DP
Fixing of MCB/MCCB/Isolator in sheet steel enclosure as required as per accepted practice, including mounting on busbar and cable connection etc. complete (labour only) MCB/MCCB/ Isolator TP/TPN/FP
Supply and fixing as per specification call bell/buzzer of approved make with necessary materials complete. Multi sound bell
Supply and fixing as per specification Switch of approved make ISI marked with necessary material complete. 6/10Amp SP 250 Volt modular switch
Supply and fixing as per specification Switch of approved make ISI marked with necessary material complete. 16/20Amp SP 250 Volt modular switch
Supply and fixing as per specification Switch of approved make ISI marked with necessary material complete. Blank plate 1 module
Supply and fixing as per specification socket outlet of approved make & ISI marked with necessary material complete 10Amp 250 Volt 3 Pin modular type
Supply and fixing as per specification socket outlet of approved make & ISI marked with necessary material complete 10/16/20Amp 250 Volt 3 Pin modular type
Supply and fixing Led tube rod comprising of LED tube with non-integral/integral driver, upto 6500K color temp having 40000 burning hrs life with minimum @ L 70, system lumen output should be minimum with system efficacy> 100 lm/Watt. LED driver PF> 0.95 & THD < 20%. The colour rendering index of LED light should be more than 70. Submission LM 79-08/IS16106 (2012), IEC60598, IEC61347i/c connection wire, testing etc. to complete the job. Tube light LED 1 X 20/22Watt, Integral i/c batten aluminium body, PC diffuser.
Supply and fixing surface mounting LED down lighter, LED of 1 to 3Watt each assembled on single MCPCB, having color temp upto 6500K & having 50000 burning hrs. life with minimum @ L 70, system lumen output should be minimum with efficacy>100 lm/Watt. LED driver PF > 0.95, THD < 20% & surge protection 4KV. The colour rendering index of LED light should be more than 70. Housing made of pressure die cast aluminium/CRCA powder coated frame with glare free diffused polycarbonate cover. Submission LM 79- 08/IS16106 (2012), IEC60598, IEC61347i/c connection wire, testing etc. to complete the job. 7/8/10 watt LED down lighter (surface mounting)
Supply and fixing recessed mounting LED down lighter, LED of 1 to 3 Watt each assembled on single MCPCB, having color temp upto 6500K & having 50000 burning hrs. life with minimum @ L 70, system lumen output should be minimum with efficacy>100 lm/Watt. LED driver PF > 0.95, THD < 20% & surge protection 4KV. The colour rendering index of LED light should be more than 70. Housing made of pressure die cast aluminium/CRCA powder coated frame with glare free diffused polycarbonate cover. Submission LM 79-08/IS16106 (2012), IEC60598, IEC61347i/c connection wire, testing etc. to complete the job.. 12 Watt, color temp 3000-6500k as required
Supplying, erection and testing of approved make electric Ceiling fan of double ball bearing complete with standard down rod, canopy, hanging shackle, Aluminium blades, without regulator, A.C. 230-250 volts including connections with all necessary material complete of approved as required confirming to IS : 374/2019 with upto date amendments. Ceiling Fan Ornamental 1200 mm Sweep, with minimum air delivery 210 m³/min and service value ≥ 4.00 as per BEE.
Supply and fixing of approved make step type modular electronic fan regulator including connection etc. as required on existing board. 100 Watt (2 module)
Linear profile recessed LED light : Supply and fixing of Linear profile suspended LED lumanaire, having color temp upto 6500K & having 20000 burning hrs life with minimum @ L 70, system lumen output should be minimum with efficacy>80lm/W. LED driver PF > 0.9, THD < 20% & surge protection 5KV. The colour rendering index of LED light should be more than 80. Housing made of pressure die cast aluminium / CRCA powder coated frame with high transmission diffuser. Submission LM 80-08 Form LED Source Manufacturer & LM79-08 / IS16106 from NABL approved lab. Manufacturer manadatory. i/c mounting arrangment, connection wire, testing etc. to complete the job. Guarantee as per tender agreement condition. 32/40W
LED Panel (recessed mounting) : Supply and fixing of recessed mounting type Led light fixture, LED of 1 to 3 Watt each assembled on single MCPCB, having color temp upto 6500K & having 50000 burning hrs life with minimum @ L 70, system lumen output should be minimum with efficacy>100 lm/Watt. LED driver PF> 0.95, THD < 20% & surge protection 4KV. The colour rendering index of LED light should be more than 70. Housing made of CRCA powder coated frame with glare free diffused polycarbonate cover. Submission LM 79-08/IS16106 (2012), IEC60598, IEC61347i/c connection wire, testing etc. to complete the job. LED luminiare 2' X 2', 36Watt, color temp 3000-6500k as required.
Supplying, erection and testing of approved make wall mounting fan oscillating type with base, blades, guard, speed regulator etc. AC 230-250 volts with connections and including raw bolt/anchor hole fastener etc. complete finished and as required. 400 mm sweep
Supplying and fixing of deluxe fresh air fan with louvers (ventilating fan) with self-closing louvers of decorative PVC blades mounting square frame of approved make complete with all necessary material as required 250mm RPM1300/1400
Supplying, erecting and testing of approved make exhaust fan heavy duty with mounting frame, blades AC 230-250 complete connection and including, frame bolt/anchor hole fasteners etc. complete finished and as required. 300mm sweep RPM 900 /1400
Earthing with G.I. earth plate 600mm X 600mm X 6mm thick including accessories and providing masonry encloser in cement mortar, cover plate having locking arrangement on the top and G.I. watering pipe 20mm dia 2.7 metre long etc. (but without charcoal or coke and salt) complete as required
Add extra for using salt and charcoal/coke for G.I. plate or copper plate earth electrode as required including excavation in hard rock and refilling the pit with black soil.
Providing and fixing 25mm X 5mm G.I. strip in 40 mm dia G.I. pipe from earth electrode as required
Supply and laying 25mm X 5mm G.I. strip at 0.5 metre below ground level as strip earth electrode including jointing etc. as required.
Providing and fixing 25mm X 5mm G.I. strip on surface or in recessed for connection etc. as required
Supply and erection of hot dip G.I. cable tray perforation not more than 17.5% for specific dimensions along with tees, bends. The cable tray shall be hang from ceiling/ fixed to wall with necessary angle/flat iron/hanging rod, for ceiling suspensions, clamp, anchor fastener, nuts, bolts, washers, not more than 1.0 mtr. apart complete as per specification to complete the Cable tray- 150x50x1.6mm thick
Supply and erection of hot dip G.I. cable tray perforation not more than 17.5% for specific dimensions along with tees, bends. The cable tray shall be hang from ceiling/ fixed to wall with necessary angle/flat iron/hanging rod, for ceiling suspensions, clamp, anchor fastener, nuts, bolts, washers, not more than 1.0 mtr. apart complete as per specification to complete the Cable tray- 300x50x1.6mm thick
Busbar chamber, 415 V 4 way : Supplying of metal clad ISI marked busbar chamber made of heavy gauge iron sheet complete with copper strip and busbar supports as per specification conforming to IS -4064 500 Amp : 500/630 Amp 415 VOLTS, 4 way
Supply and fixing of LT panel accessories of approved make in existing LT panel including connections etc. as required as per specification. Copper bus bar strips with PVC sleeves
Supply and fixing of LT panel accessories of approved make in existing LT panel including connections etc. as required as per specification. Multifunction Meter
Supply and fixing of LT panel accessories of approved make in existing LT panel including connections etc. as required as per specification. LED lamp indicator
(MCCB) suitable for 3 phase & N, 4 pole, AC supply with micro-processor release- Supplying of ISI marked and approved make of moulded case circuit breaker (MCCB) suitable for 3 phase & N, 4 pole,50 Hz, 415 Volts, (Ics=100%Icu) AC supply with microprocessor release with inbuilt instantaneous protection & variable trip class 7.2 Ir & 6 Ir having respective breaking capacity (KA) at 415 Volts cited against their range standard conforming to IS/IEC 60947- 2 MCCB, 36kA, 400 Amps, 4P - MCCB 36kA current rating - 400 Amps 4 Pole µprocessor release, over load 40% -100% x In. & short circuit 1.5 - 8 x Ir. Adjustable
(MCCB) suitable for 3 phase & N, 4 pole, AC supply with micro-processor release- Supplying of ISI marked and approved make of moulded case circuit breaker (MCCB) suitable for 3 phase & N, 4 pole,50 Hz, 415 Volts, (Ics=100%Icu) AC supply with microprocessor release with inbuilt instantaneous protection & variable trip class 7.2 Ir & 6 Ir having respective breaking capacity (KA) at 415 Volts cited against their range standard conforming to IS/IEC 60947- 2 MCCB 36kA current rating - 250 Amps 4 Pole µ-processor release, over load 40% -100% x In. & short circuit 1.5 - 8 x Ir. Adjustable
(MCCB) suitable for 3 phase & N, 4 pole, AC supply with micro-processor release- Supplying of ISI marked and approved make of moulded case circuit breaker (MCCB) suitable for 3 phase & N, 4 pole,50 Hz, 415 Volts, (Ics=100%Icu) AC supply with microprocessor release with inbuilt instantaneous protection & variable trip class 7.2 Ir & 6 Ir having respective breaking capacity (KA) at 415 Volts cited against their range standard conforming to IS/IEC 60947- 2 MCCB 36kA current rating - 40 & 100 Amps 4 Pole & Micro-Processor Release, over load 40% -100% x In. & short circuit 1.5 - 8 x Ir. adjustable
Supply of XLPE insulated power cable (conforming IS-7098 Part-I) 1100 Volt grade, 1 core/2 core/3½ core/4 core ISI marked with alu. stranded /solid conductor 3½ core armoured - 120 sq. mm.
Supply of XLPE insulated power cable (conforming IS-7098 Part-I) 1100 Volt grade, 1 core/2 core/3½ core/4 core ISI marked with alu. stranded /solid conductor 3½ core armoured - 50 sq. mm
Supply of XLPE insulated power cable (conforming IS-7098 Part-I) 1100 Volt grade, 1 core/2 core/3½ core/4 core ISI marked with alu. stranded /solid conductor 3½ core armoured - 35 sq. mm
Laying, 1.1KV grade of size exceeding 25sq. mm but not xceeding 120 sq. mm : Laying of one number armoured/unarmoured power cable 1.1KV grade of size exceeding 25sq. mm but not exceeding 120 sq. mm in the existing masonry open duct as required.
Crimping type alum. Lugs : Supplying and fixing crimping type alum. lugs as per I.S.S. specification suitable for following size of cable with alu./copper solid/stranded conductor evenly crimped with high/pressure tool and connected to switch gear / bus / M.C.C.B. /M.C.B. etc. as required complete. For conductor size : 35 Sq mm
Crimping type alum. Lugs : Supplying and fixing crimping type alum. lugs as per I.S.S. specification suitable for following size of cable with alu./copper solid/stranded conductor evenly crimped with high/pressure tool and connected to switch gear / bus / M.C.C.B. /M.C.B. etc. as required complete. For conductor size : 50 Sq mm
Crimping type alum. Lugs : Supplying and fixing crimping type alum. lugs as per I.S.S. specification suitable for following size of cable with alu./copper solid/stranded conductor evenly crimped with high/pressure tool and connected to switch gear / bus / M.C.C.B. /M.C.B. etc. as required complete. For conductor size : 120 Sq mm
COB LIGHT : Supply and fixing of recessed mounting LED swivel type COB downlighter, having color temp upto 6500K & having 20000 burning hrs life with minimum @ L 70, system lumen output should be minimum with efficacy>80lm/W. LED driver PF > 0.9, THD < 20% & surge protection 5KV. The colour rendering index of LED light should be more than 70. Housing made of pressure die cast aluminium / CRCA powder coated frame with glare free diffused polycorbonate cover. Submission LM 80-08 Form LED Source Manufacturer & LM79-08 / IS16106 from NABL approved lab. Manufacturer manadatory. i/c connection wire, testing etc. to complete the job. Guarantee as per tender agreement condition. COB LIGHT : 6/7W
T.V. outlet modular : Supply, fixing and testing of T.V. outlet modular (1Module)
Co-axial T.V. cable : Supplying and drawing co-axial T.V. cable RG-6 Grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tined copper braid and protected with PVC sheathed in existing surface/concealed, steel/PVC conduit as required.
LIFT AND ELEVATORS
Add extra to item no. 1.1 for every additional floor beyond initial G+ 1 floor (additional stops beyond two stops) provides all necessary additional parts/equipments as per manufacturer's requirement. upto 9 stops: Cost for each additional floor : upto 9 stops (For 13-26 Passengers)
Gong System: Add extra to item no. 1.1 for hall lantern and arrival gong system. Extra cost for per floor per lift
Toughened glass, on front door of car and each landing door : Add extra to item no.1.1 for transparent observation, toughened glass fixed to the structural steel frame of required size as per manufactures design on front door of car and each landing door in place of S.S. (stainless steel) panels including cost of hold fastening of guide rails to a separately erected civil structure (steel or RCC columns) but excluding cost of civil structure. For 13-26 passenger (for passenger car)
Toughened glass, on front door of car and each landing door : Add extra to item no.1.1 for transparent observation, toughened glass fixed to the structural steel frame of required size as per manufactures design on front door of car and each landing door in place of S.S. (stainless steel) panels including cost of hold fastening of guide rails to a separately erected civil structure (steel or RCC columns) but excluding cost of civil structure. For 13-26 passenger (for each landing door)
VRV/VRF outdoor AC unit:- Supply installation testing and commissioning of VRV /VRF /MRV outdoor units with following multiple inverter based scroll type compressors, electronic expansion valve, R 410A/ecofriendly green refrigerant, cooling & heating mode both options, special pre-coated fin type heat exchanger, low noise direct driven propeller condenser fans in each module with top discharge including internal wiring, microprocessor controls, safety. The condensing unit should be capable of providing cooling between +/- 5deg. C. to 48 deg. C & heating within 0 deg. C to 15 deg. C, COP not less than 3.3. Each system should have the provision to combine maximum 3 nos compressor in each outdoor unit, every single outdoor unit should not have more than maximum Capacity 20 HP (3 phase) each compressor complete as per specification. Outdoor/indoor units should be of same make (brand). (Single phase/three phase)28 HP
VRV/VRF outdoor AC unit:- Supply installation testing and commissioning of VRV /VRF /MRV outdoor units with following multiple inverter based scroll type compressors, electronic expansion valve, R 410A/ecofriendly green refrigerant, cooling & heating mode both options, special pre-coated fin type heat exchanger, low noise direct driven propeller condenser fans in each module with top discharge including internal wiring, microprocessor controls, safety. The condensing unit should be capable of providing cooling between +/- 5deg. C. to 48 deg. C & heating within 0 deg. C to 15 deg. C, COP not less than 3.3. Each system should have the provision to combine maximum 3 nos compressor in each outdoor unit, every single outdoor unit should not have more than maximum Capacity 20 HP (3 phase) each compressor complete as per specification. Outdoor/indoor units should be of same make (brand). (Single phase/three phase) 56 HP
VRF/VRV indoor AC unit (wall mounted):- Supply installation testing and commissioning of wall mounted indoor split unit comprising of copper evaporator, electronic expansion valve, blower, motor, filter pad, auto air swing louvers, and temperature & on/off display with provision of discharge angle setting by wireless remote controller including internal wiring, controls complete as per specification. (Single phase/three phase)1.05TR
VRF/VRV indoor AC unit (wall mounted):- Supply installation testing and commissioning of wall mounted indoor split unit comprising of copper evaporator, electronic expansion valve, blower, motor, filter pad, auto air swing louvers, and temperature & on/off display with provision of discharge angle setting by wireless remote controller including internal wiring, controls complete as per specification. (Single phase/three phase) 1.33TR
VRF/VRV indoor AC unit (wall mounted):- Supply installation testing and commissioning of wall mounted indoor split unit comprising of copper evaporator, electronic expansion valve, blower, motor, filter pad, auto air swing louvers, and temperature & on/off display with provision of discharge angle setting by wireless remote controller including internal wiring, controls complete as per specification. (Single phase/three phase) 1.65TR
VRF/VRV indoor AC unit (wall mounted):- Supply installation testing and commissioning of wall mounted indoor split unit comprising of copper evaporator, electronic expansion valve, blower, motor, filter pad, auto air swing louvers, and temperature & on/off display with provision of discharge angle setting by wireless remote controller including internal wiring, controls complete as per specification. (Single phase/three phase) 2.08TR
VRF/VRV indoor AC unit (ceiling mounted 4 way):- Supply installation testing and commissioning of 4 way round flow ceiling suspended/mounted cassette type unit comprising of copper evaporator, electronic expansion valve, blower, motor, filter pad, auto air swing louvers, temperature &on/off display with inbuilt drain pump & decorative panels including internal wiring, controls. Dimension in terms of length & width should not be more than 950mmX 950mm with wireless remote controller. (Single phase/three phase) 2.08 TR
VRF/VRV indoor AC unit (ceiling mounted 4 way):- Supply installation testing and commissioning of 4 way round flow ceiling suspended/mounted cassette type unit comprising of copper evaporator, electronic expansion valve, blower, motor, filter pad, auto air swing louvers, temperature &on/off display with inbuilt drain pump & decorative panels including internal wiring, controls. Dimension in terms of length & width should not be more than 950mmX 950mm with wireless remote controller. (Single phase/three phase) 2.64 TR
VRF/VRV indoor AC unit (ceiling mounted 4 way):- Supply installation testing and commissioning of 4 way round flow ceiling suspended/mounted cassette type unit comprising of copper evaporator, electronic expansion valve, blower, motor, filter pad, auto air swing louvers, temperature &on/off display with inbuilt drain pump & decorative panels including internal wiring, controls. Dimension in terms of length & width should not be more than 950mmX 950mm with wireless remote controller. (Single phase/three phase) 3.30 TR
VRF/VRV indoor AC unit (ceiling mounted 4 way):- Supply installation testing and commissioning of 4 way round flow ceiling suspended/mounted cassette type unit comprising of copper evaporator, electronic expansion valve, blower, motor, filter pad, auto air swing louvers, temperature &on/off display with inbuilt drain pump & decorative panels including internal wiring, controls. Dimension in terms of length & width should not be more than 950mmX 950mm with wireless remote controller. (Single phase/three phase) 4.13 TR
VRF/VRV indoor AC unit (mid - static ductable) :- Supply installation testing and commissioning of mid static ductable type comprising of copper evaporator, electronic expansion valve, blower, motor, filter pad, with inbuilt drain pump including internal wiring, controls with cordless remotes. (Single phase/three phase) 1.33 TR
VRF/VRV indoor AC unit (mid - static ductable) :- Supply installation testing and commissioning of mid static ductable type comprising of copper evaporator, electronic expansion valve, blower, motor, filter pad, with inbuilt drain pump including internal wiring, controls with cordless remotes. (Single phase/three phase) 1.65 TR
VRF/VRV indoor AC unit (mid - static ductable) :- Supply installation testing and commissioning of mid static ductable type comprising of copper evaporator, electronic expansion valve, blower, motor, filter pad, with inbuilt drain pump including internal wiring, controls with cordless remotes. (Single phase/three phase) 2.08TR
VRF/VRV indoor AC unit (mid - static ductable) :- Supply installation testing and commissioning of mid static ductable type comprising of copper evaporator, electronic expansion valve, blower, motor, filter pad, with inbuilt drain pump including internal wiring, controls with cordless remotes. (Single phase/three phase) 2.64TR
VRF/VRV indoor AC unit (high static ductable) :-Supply, installation, testing and commissioning of high static ductable type comprising of copper evaporator, electronic expansion valve, blower, motor, filter pad, with inbuilt drain pump including internal wiring, controls with cordless remote. (Single phase/three phase) 4.75 TR
VRF/VRV indoor AC unit (high static ductable) :-Supply, installation, testing and commissioning of high static ductable type comprising of copper evaporator, electronic expansion valve, blower, motor, filter pad, with inbuilt drain pump including internal wiring, controls with cordless remote. (Single phase/three phase) 5.4 TR
Copper piping: - Supply, installation, testing and commissioning of interconnecting copper refrigerant pipe work (19mm/13mm thick) duly insulated with elastomeric nitrile rubber type tubular insulation between indoor & outdoor units as per specifications. And exposed piping should be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as per specification. 44 mm O.D. wall thickness ≥ 1.4mm (insulation – 19 mm thick)
Copper piping: - Supply, installation, testing and commissioning of interconnecting copper refrigerant pipe work (19mm/13mm thick) duly insulated with elastomeric nitrile rubber type tubular insulation between indoor & outdoor units as per specifications. And exposed piping should be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as per specification. 41.1 mm O.D. wall thickness ≥ 1.4mm (insulation – 19 mm thick)
Copper piping: - Supply, installation, testing and commissioning of interconnecting copper refrigerant pipe work (19mm/13mm thick) duly insulated with elastomeric nitrile rubber type tubular insulation between indoor & outdoor units as per specifications. And exposed piping should be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as per specification.38 mm O.D. wall thickness ≥ 1.4mm (insulation – 19 mm thick)
Copper piping: - Supply, installation, testing and commissioning of interconnecting copper refrigerant pipe work (19mm/13mm thick) duly insulated with elastomeric nitrile rubber type tubular insulation between indoor & outdoor units as per specifications. And exposed piping should be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as per specification.34.9 mm O.D. wall thickness ≥ 1.4mm (insulation – 19 mm thick)
Copper piping: - Supply, installation, testing and commissioning of interconnecting copper refrigerant pipe work (19mm/13mm thick) duly insulated with elastomeric nitrile rubber type tubular insulation between indoor & outdoor units as per specifications. And exposed piping should be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as per specification.28.6 mm O.D. wall thickness ≥ 1.2mm (insulation – 19 mm thick)
Copper piping: - Supply, installation, testing and commissioning of interconnecting copper refrigerant pipe work (19mm/13mm thick) duly insulated with elastomeric nitrile rubber type tubular insulation between indoor & outdoor units as per specifications. And exposed piping should be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as per specification.25 mm O.D. wall thickness ≥ 1.2mm (insulation – 19 mm thick)
Copper piping: - Supply, installation, testing and commissioning of interconnecting copper refrigerant pipe work (19mm/13mm thick) duly insulated with elastomeric nitrile rubber type tubular insulation between indoor & outdoor units as per specifications. And exposed piping should be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as per specification.22.2 mm O.D. wall thickness ≥ 1.0mm (insulation – 19 mm thick)
Copper piping: - Supply, installation, testing and commissioning of interconnecting copper refrigerant pipe work (19mm/13mm thick) duly insulated with elastomeric nitrile rubber type tubular insulation between indoor & outdoor units as per specifications. And exposed piping should be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as per specification.19.1 mm O.D. wall thickness ≥ 1.0mm (insulation – 13 mm thick)
Copper piping: - Supply, installation, testing and commissioning of interconnecting copper refrigerant pipe work (19mm/13mm thick) duly insulated with elastomeric nitrile rubber type tubular insulation between indoor & outdoor units as per specifications. And exposed piping should be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as per specification.15.9 mm O.D. wall thickness ≥ 0.8mm (insulation – 13 mm thick)
Copper piping: - Supply, installation, testing and commissioning of interconnecting copper refrigerant pipe work (19mm/13mm thick) duly insulated with elastomeric nitrile rubber type tubular insulation between indoor & outdoor units as per specifications. And exposed piping should be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as per specification.12.7 mm O.D. wall thickness ≥ 0.8mm (insulation – 13 mm thick)
Copper piping: - Supply, installation, testing and commissioning of interconnecting copper refrigerant pipe work (19mm/13mm thick) duly insulated with elastomeric nitrile rubber type tubular insulation between indoor & outdoor units as per specifications. And exposed piping should be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as per specification.9.5 mm O.D. wall thickness ≥ 0.8mm (insulation – 13 mm thick)
Copper piping: - Supply, installation, testing and commissioning of interconnecting copper refrigerant pipe work (19mm/13mm thick) duly insulated with elastomeric nitrile rubber type tubular insulation between indoor & outdoor units as per specifications. And exposed piping should be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as per specification.6.4 mm O.D. wall thickness ≥ 0.8mm (insulation – 13 mm thick)
Drain piping :- Providing and fixing of CPVC, 6Kg/cm2 drain water piping with fittings, support and insulated with 6 mm thick closed cell elastomeric nitrile rubber insulation complete as per specification. 25 mm dia ID
Drain piping :- Providing and fixing of CPVC, 6Kg/cm2 drain water piping with fittings, support and insulated with 6 mm thick closed cell elastomeric nitrile rubber insulation complete as per specification. 32 mm dia ID
Drain piping :- Providing and fixing of CPVC, 6Kg/cm2 drain water piping with fittings, support and insulated with 6 mm thick closed cell elastomeric nitrile rubber insulation complete as per specification. 40 mm dia ID
Flexible pre insulated duct: - Supply and fixing of aluminum foil flexible pre-insulated duct in accordance with the approved specifications.100 mm dia
PVC fresh air pipe fan: -Supply and fixing of PVC fresh air pipe fan complete as per specification. 100 mm dia
PVC fresh air pipe fan: -Supply and fixing of PVC fresh air pipe fan complete as per specification. 150 mm dia
PVC fresh air pipe fan: -Supply and fixing of PVC fresh air pipe fan complete as per specification. 200 mm dia
VRF/VRV indoor AC unit installation charges: - Installation of wall mounted indoor split unit including labor for internal wiring, controls complete as per specification. (Single phase/three phase)
VRF/VRV indoor AC unit installation charges: - Installation of cassette unit 4/2/1 way flow ceiling suspended/mounted cassette type unit & decorative panels including labor for internal wiring, controls with wireless remote controller. (Single phase/three phase)
VRF/VRV indoor AC unit installation charges:- Installation of mid static ductable ceiling mounted type including labor for internal wiring, controls with cordless remote. (Single phase/three phase)
VRF/VRV indoor AC unit installation charges:-Installation of high static ductable ceiling mounted type including labor for internal wiring, controls with cordless remote. (Single phase/three phase)
VRF/VRV outdoor AC unit installation charges: - Installation of VRF/VRV/ MRV outdoor unit is including labor for internal wiring, controls complete as per specification. (single phase/three phase)
Refrigerant:- Supply and additional refrigerant charge of refrigerant R410/410A & equivalent Eco friendly green gas to compensate the additional piping done at site for all systems including testing commissioning as required,
Y joints:- Supply, installation, testing & commissioning of ref nut/Y-joints brass for indoor and outdoor units of suitable size as per requirement,
Ducting:- Supply and fixing of site fabricated GI sheet metal ducts in accordance with the approved shop drawings and as required as per specifications. GI sheet will be as per IS-277. All necessary GI /MS supports using thread rods (as directed). Angle, flat, and anchor bolts, food grade neoprene gaskets, food grade adhesive included in the scope.24G
Ducting:- Supply and fixing of site fabricated GI sheet metal ducts in accordance with the approved shop drawings and as required as per specifications. GI sheet will be as per IS-277. All necessary GI /MS supports using thread rods (as directed). Angle, flat, and anchor bolts, food grade neoprene gaskets, food grade adhesive included in the scope.22G
Thermal insulation :- Supplying and fixing of following thickness of mat finish closed cell nitrile rubber (class “1”) insulation on existing duct after applying two coats of cold setting adhesive complete as per specifications and as required. 12/13 mm thick
Internal duct acoustic insulation: - Supply, installation, testing and commissioning of internal duct acoustic insulation with open cell structured class "O" fire retardant nitrile rubber with density 140 - 180 kg/m³ and specs as per RISAC chart specification sheet inside of the AHU supply air ducting up to 4 mtr. length from AHU mouth as per the specifications, it should have antimicrobial properties.10 mm thick
Grills and diffusers Supplying & fixing of powder coated extruded aluminum air grills without volume control damper complete as required.
Grills and diffusers Supplying & fixing of coller damper complete as required.
Grills and diffusers Supplying & fixing of powder coated extruded aluminum square diffuser without volume control damper complete as required.
Grills and diffusers Supplying & fixing of powder coated extruded aluminum square diffuser with volume control damper complete as required.
Grills and diffusers Supplying & fixing of G.I duct volume control damper
Grills and diffusers Flexible connections :- Providing & fixing of flexible canvas connection between indoor unit and duct to avoid the vibration transfer
Controlcable: - Supply and laying, testing & commissioning of following sizes of shielded copper conductor Communication cables on existing tray including fixing clamps & proper connections to equipment etc. complete as required.2Cx1.5 sq.mm
Outdoor stand fabrication :- Supply, fabrication and erection of angle/channel/flat iron stand, hanging arrangement for air conditioning machines & ducts etc, back /support clamps or other similar work etc. including nut bolts of required size, making holes, fabrication, welding, cutting, etc. and painting with one coat of red oxide paint & two coat of enamel paint as required as per specification.
Fresh air in line fan: - Supply, installation, testing and commissioning of fresh air inline fan.900 CFM (static pressure upto 20 mm)
Installation fresh air in line fan: - Installation of fresh air inline fan including internal wiring, controls complete as per specification as mentioned below :-Above 300 CFM to 900 CFM
Please Enable Macros to View BoQ information
stage.html
html • 0.02 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.70 MB
35Tender3232.pdf
Tender Documents • 19.91 MB
BOQ_940250.xls
BOQ • 0.48 MB
Download all tender documents and submit your bid