Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹29.7 LAccepted-AOC G 58 KIRAN GARDEN UTTAM NAGAR NEW DELHI 110059 | NEW DELHI | WEST DELHI | DELHI | 110059 | L1 | Accepted-AOC Accepted | |
| 2 | L2₹34.6 L+₹2.5 L (7.70%)Rejected-AOC 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NORTH | DELHI | 110006 | L2 | Rejected-AOC Rejected | |
| 3 | L3₹34.8 L+₹2.7 L (8.27%)Rejected-AOC A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | L3 | Rejected-AOC Rejected | |
| 4 | L4₹37.1 L+₹4.9 L (15.3%)Rejected-AOC D 35 1ST FLOOR CLOCK TOWER HARI NAGAR NEW DELHI 110064 | WEST | DELHI | 110064 | L4 | Rejected-AOC Rejected | |
| 5 | L5₹43.4 L+₹11.2 L (34.8%)Rejected-AOC | L5 | Rejected-AOC Rejected |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
19 May 2022, 6:00 pmClosed
GE (P) AF Gurgaon
GE (P) AF Gurgaon NEar Atul Kataria Chowk Gurgaon
CA NO. GE(P)AF/GUR-08/2022-23 REPAIR MAINTENANCE OF STARTER PANEL, CENTRIFUGAL PUMPS SUBMERSIBLE PUMPS, DEVELOPMENT OF LOW YIELD BORE WELL AND OTHER ALLIED AND MISC MAINT WORKS OF BOREWELL, RISING MAIN OF PIPE LINE WITH OTHER ALLIED MAINT WORKS
2022_MES_519238_1
GE(P) AF/Gur-08/2022-23
Open Tender
Miscellaneous Works
Item Rate
270 days
GE (P) AF GUrgaon
All as per NIT
10 documents required · 10 mandatory
₹500
Yes
GE (P) AF Gurgaon
₹96,000
Yes
18 Jun 2022
21 Apr 2022
21 May 2022
21 Apr 2022
19 May 2022
5 May 2022
Amount
Schedule-A
Taking out centrifugal pump set, from squirrel cage induction motor capacity upto 25 HP , AC, 3 phase, 415 volts from site after disconnecting of suction and delivery line, taking out to work shop, dismantling pump set for overhauling, replacing u/s shaft sleeve, gland packing, bush, water seal, applying grease etc reassembling the pump set and refixing back at site on the base plate and conneting existing pipe line with nuts, bolts and new gasket, connecting the existing cable etc. checking the pump set for satisfactory working all as directed by EIC including dismantling from foundation with the help of special tools, opening the pump comletely including disconnection of pump from suction pipe and motor and remetaling/grinding/polishing pump shaft, replacement of all defective parts if any (except bearings, impeller, bush & shaft) of existing size, gasket packing etc, complete overhauling and re-assembling, testing and commissioning complete all as specified and directed. Note : repairing shall be done with gurantee during the contract period and any defects after rewinding and servicing of motor shall be rectified by the contractor at his own cost.
Taking out centrifugal pump set, from squirrel cage induction motor capacity 50 HP , AC, 3 phase, 415 volts from site after disconnecting of suction and delivery line, taking out to work shop, dismantling pump set for overhauling, replacing u/s shaft sleeve, gland packing, bush, water seal, applying grease etc reassembling the pump set and refixing back at site on the base plate and conneting existing pipe line with nuts, bolts and new gasket, connecting the existing cable etc. checking the pump set for satisfactory working all as directed by EIC including dismantling from foundation with the help of special tools, opening the pump comletely including disconnection of pump from suction pipe and motor and remetaling/grinding/polishing pump shaft, replacement of all defective parts if any (except bearings, impeller, bush & shaft) of existing size, gasket packing etc, complete overhauling and re-assembling, testing and commissioning complete all as specified and directed. Note : repairing shall be done with gurantee during the contract period and any defects after rewinding and servicing of motor shall be rectified by the contractor at his own cost.
Supply & Fix in replacement of bearing for centrifugal pump sets of any size complete as per matching to existing. Make: SKF/NBC/TATA
Supply & Fix in replacement of bearing for squirrel cage induction motor upto 50 HP of any size complete as per matching to existing. Make: SKF/NBC/TATA
Supply & Fix in replacement of shaft for centrifugal pump set of capacity 50 HP of any size complete as per matching to existing complete all as directed.
Supply & Fix in replacement of shaft for centrifugal pump set of capacity 25 HP of any size complete as per matching to existing complete all as directed..
Supply & Fix in replacement of long & short bush for centrifugal pump set of capacity 50 HP of any size complete as per matching to existing complete all as directed.
Supply & Fix in replacement of long & short bush for centrifugal pump set of capacity 25 HP of any size complete as per matching to existing complete all as directed.
Supply & Fix in replacement of impeller for centrifugal pump set of capacity 50 HP of any size complete as per matching to existing complete all as directed.
Supply & Fix in replacement of impeller for centrifugal pump set of capacity 25 HP of any size complete as per matching to existing complete all as directed.
Supply and fi in repair casing of centrifugal pump set of capcity 50 HP of size as per sample and any size complete as per matching to existing
Dismantling monoblock pump set centrifugal type 5 HP, AC, 3 phase, 415 volts from site after disconnecting of electric connection, suction and delivery line, taking out to work shop, opening of motor, taking out old worn-out / burnt-out winding complete, cleaning the slots properly and rewinding with supper enamelled copper wire as per existing gauge and varnishing complete, dismantling pump set for overhauling, replacing u/s shaft sleeve, gland packing, bush, water seal, applying grease etc and reassembling the complete pump after repairs and replacement of parts as required, refixing the same at site incl. electric and piping connections cpte, checking for satisfatory working all as directed by EIC. Note : rewinding shall be done with gurantee during the contract period and any defects after rewinding and servicing of motor shall be rectified by the contractor at his own cost.
Dismantling / taking down of electric motor 25 HP, AC, 3 phase, 415 volts from site after disconnecting from pump & electric connection for rewinding, taking out to work shop, opening of motor, taking out old worn-out / burnt-out winding complete, cleaning the slots properly and rewinding with supper enamelled copper wire as per existing gauge and varnishing complete, and reassembling after repairs and replacement of parts as required, refixing the same at site incl. electric connections , checking for satisfatory working all as directed by EIC. Note : rewinding shall be done with gurantee during the contract period and any defects after rewinding and servicing of motor shall be rectified by the contractor at his own cost.
Dismantling / taking down of electric motor 50 HP, AC, 3 phase, 415 volts from site after disconnecting from pump & electric connection for rewinding, taking out to work shop, opening of motor, taking out old worn-out / burnt-out winding complete, cleaning the slots properly and rewinding with supper enamelled copper wire as per existing gauge and varnishing complete, and reassembling after repairs and replacement of parts as required, refixing the same at site incl. electric connections , checking for satisfatory working all as directed by EIC. Note : rewinding shall be done with gurantee during the contract period and any defects after rewinding and servicing of motor shall be rectified by the contractor at his own cost.
Supply and Fix ball bearing for pumps and motors of following Nos:-Make:- SKF, NBC
(a) Bearing No 6305.
(b) Bearing No 6307.
(c) Bearing No 6309.
(d) Bearing No 6310.
Labour only for taking out submersible pump/motor from existing location by disconnecting electric connection of submersible cable from outdoor panel,and taking out submersible pump/motor by using Tripod stand & chain pulley set complete all as directed alongwith taking out of entire column pipe length of any dia alongwith submersible cable, SWR rope from bore well upto a depth of 90mtr complete and redeploying of pump/motor alongwith column pipe,SWR rope, submersible cable etc by taking all necessary precautions including replacement of nuts,bolts and washers complete with rubber gasket of column pipe joints , joining of column pipes and rendering the entire setup functional after reconnecting to outdoor panel and testing thereof including lowering the submersible pump after repair with adopting the above procedure .(Note:- 1. The taking up and redeployment of pump/motor is meant for enhancement of bore wells, replacement of submersible cable,replacement of column pipe,or repair/replacement to pump/motor and all as jobs as mentioned will be measured and paid seperately in respective items. 2. Proper care should be taken while taking up or redeploying of pump/motor with colum pipe from bore wells. All T&P and clamps, nuts/bolts required is inclusive of rates and any damage to borewell while execution of work shall be the responsibility of contractor and he shall be liable for rectification or provision of new bore well if existing one gets damaged due to negligence while execution of job.
M&L for Re-development of borewells by means of air compressor of capacity (not less than 600 cu.feet/minute) followed by high capacity pump to its optimum yield till clear water of portable quality free from sand and silt is obtained including draw down performance and yield test of tube well complete all as specified and directed by Engineer-in-charge. (Note-compressor shall not be less than 75 BHP or above capacity pumping set equipment for testing yield shall be used)
M&L for Testing (Conducting yield test with" V" notch) by means of pumping set of suitable capacity for continously pumping for 16 hours running to determine safe pumping yield complete all as specified (All equipments,fuel etc shall be arranged by contractor at his own cost)
Supply, fixing and testing of submersible electric driven pump only with outer dia of pump not exceeding 150 mm having discharge capacity 5 lps at 90 Meter head (operating head range -113-74 mtr) complete all as specified and directed by Engr-in-charge. (Taking out and lowering of pump motor set will be measured and paid separately).
Supply, fixing, connecting electric connections and testing submersible motor only capacity 10 HP 3 phase 415 volts, 50 HZ with outer dia of pump set not exceeding 150 mm suitable to be coupled with pump as mentioned in item no. 18 hereinbefore complete all specified and directed.
M&L for complete rewinding of electric submersibe motor with super enameled copper wire of superior quality as per existing gauge including vanishing, insulating material complete all as directed and greasing, oiling etc and including reassembling fixing in position making connection testing, commissioning & transporting complete. Note :- rewinding shall be done with gurantee during the contract period. Any defects after rewinding shall be rectified by the contractor at his own expanses.
M & L for carrying out following repairing works to submersible motor 3 phase , 415 volts 50 Hz of 10/12.5 HP capacity complete all as specified by Engineer-in-charge.
(a) Stripping of motor complete, taking out warn-out / burnout winding wire complete and rewinding the motor with PVC insulated copper winding wire of appropriate gauge as per manufactures specifications and direction and replacement of following parts and reassembling the complete motor after repairs and replacement of following parts (Note : rewinding of submersible motor will be mesaured and paid seperately).
(i) Thrust plate - 01 No.
(ii) Gun metal bush set with brazing the motor and coupling-01set
(iii) Rubber water seal as per manufactures specification- 01 No
(iv) Replacement of submersible copper cable - 2 x 5 RM
(b) Reassembling of motor including commissioning complete submersible motor at site.
M & L for carrying out following repairing works to submersible pump set with motor 3 phase , 415 volts 50 Hz of 12.5/15 HP capacity.E53 )Disconnection of pump from motor for repair including replacement of following warn out parts and reassembling complete after repair and replacement of following u/s parts :-
(i) Bronze impellers - 07 Nos
(ii) Gun metal impellers- 07 Nos
(iii) Gun Metal Guide bush - 07 Nos
(iv) Gun Metal Diffuser -07 Nos
(v) Gun Metal Neck-ring -07 Nos
(vi)Gun Metal Coupling bush with MS key - 01 set.
(vii) Strainer - 01 Nos
(viii)Sand protection ring - 01 No
Supply, lay , connecting PVC insulated submersible copper cable 3 core, 4 sqmm, woking voltage 1100 volts complete all as specified and directed.
Supply and fix in repairs coloum pipe in tubewells, 50mm borex 6 Mtr long galvanized tubing Heavy grade with both ends screwed and fixed with flanges and holed drilled, groves cut for cables flanges 10mm thick, welded to pipe MS flats 20mm x 6mm thick 150mm long to flange and pipe (3 Nos) in each flanged side, replacements of nut bolts and 2 Nos of rubber gaskets. Each coloum pipe 6 mtrs long and ISI marked etc all complete all as specified and directed by Engineer-in-Charge
Supply and fix in repairs MS pipe in existing pipelines, 150mm bore x 6 mtr long galvanized tubing Heavy grade, ISI marked with both ends screwed and fixed with flanges and holed drilled, replacements of nut bolts and 2 Nos of rubber gaskets. etc all complete all as specified and directed by Engineer-in-Charge
M & L for disconnecting pipelines(delivery, suction,priming, etc.) , electrical connections, accessories/removing the centrifugal pump(motor)set upto 50 hp with proper tools and material including "C"channel from the foundation, keeping aside. Breaking the existing PCC foundation. Contructing new PCC (type C1,1:3:6) foundation of size not less than 2mx.7mx.45 to existing (width and length)diamensions including fixing of new "C' channel of suitable size not less than 85 kg with proper nuts and bolts complete, depth of PCC minimum 45 cms, re-installing and recommissioning the pump(motor)set including refixing of electrical parts as directed and specified by EIC, replacement of rubber coupling (star bush) between coupling, replacement of gaskets/packings at delivery, suction lines, fixing of new antivibration pads (make-dunlop)- 06 nos below channel frame with suitable size fasteners/bolts, nuts,washers, resetting of suction and delivery pipeline as per pump's suction and delivery position. Replacement of bolts, nuts,washers between channel frame and pump. Re-aligning the axis of pump & motor as specified and recommended by pump manufacturer to avoid any parallel or angular misalignment. Reconnecting all electrical connectons, checking the pump set for satisfactory working all as directed by Engr-in-Charge.
Disconnecting / taking down carefully existing unserviceable LT panel board / feeder pillar box any type and capacity including all control switches, fitting and fixtures from different location including disconnection of existing electric incomming and outgoing cable and dismantling of PCC platform and make good with existing surface complete all as directed by the Engr-in-Charge.
Supply, install commissioning and testing cubical out door feeder LT panel board of size not less than 1200x1200x450mm, platform mounted, factory made totally enclosed dust and vermin proof (protection class IP-54, CPRI Approved) double shutter front and back opening with locking arrangement complete supported on angle iron 50 mm x 50 mm x 6 mm thick frame work and 3.15 mm thick CRCA sheet duly painted with powder coated paint to all steel surfaces over outside and inside complete including necessary PCC foundation and necessary electrical connection of incomming and outgoing cable with necessary lugs complete all as specified and directed. The panel board shall be suitable for 415 volt, 50 Hz, 3 phase, 4 wire system with epoxy type copper bus bar of appropriate size and internal control wiring shall be of insulated multi stranded copper conductor cables (make of Panel : Advance Switch gear / Hensel / Universal / Adhunik or equivalent as approved by GE :-
INCOMING:
(a) MCCB, four pole, 100 Amp, 25 KA at 415 Volts, adjustable thermal and magnetic setting- 01 No.
(b) Changeover switch of 100 Amps, 4 pole, 415 volts -01 Nos
(c) 200 Amps rated copper bus bar suitable for 04 pole system - 01 set.
(d) Phase indicating lamp RYB LED type (Set of three ) -01 Set
OUTGOING:
(a) MCCB triple pole 32 Amps, 36 KA at 415 Volts, adjustable thermal and magnetic setting- 02 Nos .
(b) Isolator DP 32 Amps, 10 ka-01 ( security lighting )
(c) Fully automatic star delta starter panel mounted of cap 15 HP- (02 Nos)
(d) Digital hour meter-02 Nos
Supply, install commissioning and testing cubical out door feeder LT panel board of size not less than 1200x1200x450mm, platform mounted, factory made totally enclosed dust and vermin proof (protection class IP-54, CPRI Approved) double shutter front and back opening with locking arrangement complete supported on angle iron 50 mm x 50 mm x 6 mm thick frame work and 3.15 mm thick CRCA sheet duly painted with powder coated paint to all steel surfaces over outside and inside complete including necessary PCC foundation and necessary electrical connection of incomming and outgoing cable with necessary lugs complete all as specified and directed. The panel board shall be suitable for 415 volt, 50 Hz, 3 phase, 4 wire system with epoxy type copper bus bar of appropriate size and internal control wiring shall be of insulated multi stranded copper conductor cables (make of Panel : Advance Switch gear / Hensel / Universal / Adhunik or equivalent as approved by GE :-
INCOMING
(a) MCCB, four pole, 125 Amp, 30KA at 415 Volts, adjustable thermal and magnetic setting- 01 No.
(b) Changeover switch of 125 Amps, 4 pole, 415 volts -01 Nos
(c) 250 Amps rated copper bus bar suitable for 04 pole system - 01 set.
(d) Phase indicating lamp RYB LED type (Set of three ) -01 Set
OUT GOING
(a) MCCB triple pole 63 Amps, 18 KA at 415 Volts, adjustable thermal and magnetic setting- 02 Nos .
(b) Isolator DP 32 Amps, 10 ka-01 ( security lighting )
(c) Fully automatic star delta starter panel mounted of cap 25/30 HP- (02 Nos)
(d) Digital hour meter-02 Nos
Supply, install commissioning and testing cubical out door feeder LT panel board of size not less than 1200x1200x450mm, platform mounted, factory made totally enclosed dust and vermin proof (protection class IP-54, CPRI Approved) double shutter front and back opening with locking arrangement complete supported on angle iron 50 mm x 50 mm x 6 mm thick frame work and 3.15 mm thick CRCA sheet duly painted with powder coated paint to all steel surfaces over outside and inside complete including necessary PCC foundation and necessary electrical connection of incomming and outgoing cable with necessary lugs complete all as specified and directed. The panel board shall be suitable for 415 volt, 50 Hz, 3 phase, 4 wire system with epoxy type copper bus bar of appropriate size and internal control wiring shall be of insulated multi stranded copper conductor cables (make of Panel : Advance Switch gear / Hensel / Universal / Adhunik or equivalent as approved by GE :-
INCOMING
(a) MCCB, four pole, 150 Amp, 36 KA at 415 Volts, adjustable thermal and magnetic setting- 01 No.
(b) Changeover switch of 150 Amps, 4 pole, 415 volts -01 Nos
(c) 300 Amps rated copper bus bar suitable for 04 pole system - 01 set.
(d) Phase indicating lamp RYB LED type (Set of three ) -01 Set
OUT GOING
(a) MCCB triple pole 100 Amps, 36 KA at 415 Volts, adjustable thermal and magnetic setting- 02 Nos .
(b) Isolator DP 32 Amps, 10 ka-01 ( security lighting )
(c) Fully automatic star delta starter panel mounted of cap 50 HP- (02 Nos)
(d) Digital hour meter-02 Nos
M & L for cutting extg CI Pipe 200 mm dia inserting tee of size 200x200x300 mm incl all lead joints Tee and excavation complete (01 No each for fresh water and raw water existing source of OHT)
S&F CI specials and fittings such as bends, tees, collar, branch pieces, cap & plug etc, one end flange and other end spigot or socket any type any radius complete all as specified.
Supply, installation, fixing, jointing and testing in replacement ISI Marked, of approved quality, cast iron sluice valve of class PN-1.6 conforming to IS-14846 of 2000 both ends flanged with iron wheel head and stainless steel spindle, long body type, jointed and tested complete all as specified and directed for following bores :-
(a) 150mm bore.
(b) 100mm bore.
Repairs to leakage run lead joint in position of size 150mm CI/DI pipes by burning out existing joints,recovering lead, cleaning internal surfaces of socket and providing new joints with using recovered lead and additional new lead, making joint leak proof.(Excavation of Earth work shall be measured and paid seperately)
All as per item No 35 above but Size of CI/DI pipe 100mm -- ditto --
All as per item No 35 above but Size of CI/DI pipe 80mm -- ditto --
Excavation in trenches n. exc 1.5 metre wide for taking out/ laying pipe line etc. and not exceeding 1.5 metre deep and getting out in soft/ loose soil complete all as specified & directed by Engineer-in-charge.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified & directed by Engineer-in-charge.
Removal of excavated surplus spoil to a distance n.exc 50 metre and depositing where directed at level not exceeding 1.5 metre above the starting point complete all as specified & directed by Engineer-in-charge.
Supply and spreading dry sand in trenches for cable cushioning complete all as specified & as directed by Engineer-in-charge.
Supply and laying burnt sub class protection of size 23 cm x 11.5 cm x 3.5 cm complete all as specified & directed by Engineer-in-charge.
Supply and lay and testing cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric cable (heavy duty) with stranded aluminium conductor 1100 volts grade of following size 70 Sqmm 3.5 core complete all as specified & directed by Engineer-in-charge.
Supply and lay and testing cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric cable (heavy duty) with stranded aluminium conductor 1100 volts grade of following size 95 Sqmm 3.5 core.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine including laying pipe of 80 mm dia suitable for 0.4 mpa working pressure. Note : pipe will be measured and paid seperately.
M&L for boring in any type of soil under road 1.5 mtr below the top surface of road complete for passing through 40 mm to 100 mm dia GI pipe and filling earth after laying of pipe including disposal of surplus soil complete all as specified and directed.
Supply and fixing of Heat resistent flame retardant HRFR PVC insulated copper cable, single core of size 10 Sqmm, 1100 volts grade complete all as specified & directed by Engineer-in-charge.
Taking out existing GI tubing 80mm with all fittings complete all as specified & directed by Engineer-in-charge.
Taking out existing GI tubing 50mm bore with all fittings complete all as specified & directed by Engineer-in-charge.
Taking out existing GI tubing 40mm bore with all fittings complete all as specified & directed by Engineer-in-charge.
Taking out existing GI tubing 25mm bore with all fittings complete all as specified & directed by Engineer-in-charge.
Taking out existing GI tubing 20mm bore with all fittings complete all as specified & directed by Engineer-in-charge.
Supply & fixing galvanised iron tubes of size 80mm bore (medium grade) with all fittings and laid in trenches, under floor or road including fittings such as socket, bend, elbow, union etc. complete all as specified & directed by Engineer-in-charge.
Supply & fixing galvanised iron tubes of size 50mm bore (medium grade) with all fittings and laid in trenches, under floor or road including fittings such as socket, bend, elbow, union etc. complete all as specified & directed by Engineer-in-charge.
Supply & fixing galvanised iron tubes of size 40mm bore (medium grade) with all fittings and laid in trenches, under floor or road including fittings such as socket, bend, elbow, union etc. complete all as specified & directed by Engineer-in-charge.
Supply & fixing galvanised iron tubes of size 25mm bore (medium grade) with all fittings and laid in trenches, under floor or road including fittings such as socket, bend, elbow, union etc. complete all as specified & directed by Engineer-in-charge.
Supply & fixing galvanised iron tubes of size 20mm bore (medium grade) with all fittings and laid in trenches, under floor or road including fittings such as socket, bend, elbow, union etc. complete all as specified & directed by Engineer-in-charge.
Machine pressed precast concrete interlocking paver block any shape and size confirming to IS 15658- 2006 of 80 mm thickness, M-35 grade, with grey cement and no pigment complete all as specified & directed by Engineer-in-charge. .
Supply and fix in repairs 4 Inch size 50mm bore GI Nipple medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 4 Inch size 40mm bore GI Nipple medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 4 Inch size 25mm bore GI Nipple medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 4 Inch size 20mm bore GI Nipple medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 8 Inch 50mm bore GI Nipple medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 8 Inch 40mm bore GI Nipple medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 8 Inch 25mm bore GI Nipple medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fixi n repairs 8 Inch 20mm bore GI Nipple medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 80mm bore GI elbow medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 50mm bore GI elbow medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 40mm bore GI elbow medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 25mm bore GI elbow medium grade ISI marked.
Supply and fix in repairs 20mm bore GI elbow medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 50x40mm bore GI reducer socket medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 40x25mm bore reducer socket complete all as directed by Engineer-in-charge.
Supply and fix in repairs 25x20mm bore reducer socket complete all as directed by Engineer-in-charge.
Supply and fix in repairs 40x20mm bore reducer socket complete all as directed by Engineer-in-charge.
Supply and fix in repairs 50x40mm bore GI elbow reducer medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 40x25mm bore elbow reducer complete all as directed by Engineer-in-charge.
Supply and fix in repairs 25x20mm bore elbow reducer complete all as directed by Engineer-in-charge.
Supply and fix in repairs 40x20mm bore elbow reducer complete all as directed by Engineer-in-charge.
Supply and fix in repairs 50mm bore union medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 40mm bore union medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 25mm bore union medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 20mm bore union medium grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 40mm bore gate valve grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 25mm bore gate valve grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 50mm bore gate valve grade ISI marked complete all as directed by Engineer-in-charge.
Supply and fix in repairs 20mm bore gate valve grade ISI marked complete all as directed by Engineer-in-charge.
Earthing complete with galvanised steel earth plate electrode size 60 cm x 60 cm, 6.3 mm thick burried directly in ground vertically to a depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less than 1.5 metre below ground level, connected to galvanised iron or steel, earth strip 32 x 6 mm size by means of nuts, bolts check nuts and washers made of galvanised iron or steel, earth wire protected by galvanised iron pipe 15mm bore, medium grade and connected to main switch board or main control board as directed and including concrete pit in PCC 1:3:6 type C-1(using 20 mm graded stone aggregate), pre-cast RCC cover slab 30 cm x 30 cm x 10 cm with one lifting handle made of 8 mm dia MS bar funnel wire mesh, 20 mm bore galvanised iron or steel pipe medium grade for watering charcoal or coke and salt in alternate layers, necessary excavation and earth work in any type of soil complete all as shown in electrical Plate No 5 of MES Schedule Part- I and testing on completion , completed all as specified and as directed.
Supply and fix in repairs MS pipe fitting as bends, tees, collar, branch pieces, cap & plug etc, both ends flange welded complete with replacement of nuts and bolts all as specified and directed by Engineer-in-Charge
M&L in replacement of 10000 Ltr capacityTriple layer ISI marked PVC Tank including tank neeples of 40 to 50mm size and taking down existing unserviceable tank complete all as specified and as directed by Engineer-in-Charge. Make : Sintex / Rotex or as specified in list of makes.
M&L in replacement of 5000 Ltr capacityTriple layer ISI marked PVC Tank including tank neeples of 40 to 50mm size and taking down existing unserviceable tank complete all as specified and as directed by Engineer-in-Charge. Make : Sintex or Rotex as specified in list of makes.
M&L in replacement of 1000 Ltr capacityTriple layer ISI marked PVC Tank including tank neeples of 40 to 50mm size and taking down existing unserviceable tank complete all as specified and as directed by Engineer-in-Charge. Make : Sintex or Rotex or as specified in list of makes.
Note The amount of Rs 248606/- against Schedule of Credit on Page No 116 shall be deducted from the total amount quoted against Sch 'A' while deriving the Contract Sum for Acceptance
M/S Anand Enterprises
M/s Adhikari construction co.
M/s Navansh Engineers & Consultants
M.B. ENTERPRISES
Ridhi engineers and builders
SM CONSTRUCTION COMPANY
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .