Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
Closing Date
30 Oct 2021, 2:30 pmClosed
EXECUTIVE ENGINEER STD 2ND RAJBAGH
OFFICE OF THE EXECUTIVE ENGINEER STD 2ND RAJBAGH
CONSTRUCTION OF 33/0.433KV 2x1.6MVA SUB STATION AT CHILDREN HOSPITAL AT BEMINA SRINAGAR
2021_PDD_143572_1
eNIT No STD-II / 85 of 2021-22 Dated 11-10-2021
Open Tender
Electrical Works
Turn-key
45 days
SRINAGAR
Please refer Tender documents.
4 documents required · 4 mandatory
₹7,500
Yes
OFFICE OF THE EXECUTIVE ENGINEER STD 2ND RAJBAGH
Exempted
3 Nov 2021
12 Oct 2021
1 Nov 2021
12 Oct 2021
30 Oct 2021
12 Oct 2021
Amount
Electrical Works
Laying of 33KV Power cable/Overhead conductor
Supply and Erection of 16mtr Long ST Pole with base plate and top cap (ST-410 SP80 ) including excavation of pit and back filling by boulders upto 1ft as per REC construction Standard
Providing and fixing of fabricated GI Channel/Angle duly fabricated of sorts as per site requirement
Proviidng,Laying,stringing ,tensioning and binding of 0.1 ACSR Conductor (DOG) as per REC construction standards
Providing and fixing of PG clamps suitable for 0.1 ACSR Conductor heavy duty as per REC construction standards
Supply,installation,Testing and commissioning of 33kV Polymeric composite Pin Insulator with Pin (36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm) suitable for 0.1ACSR of reputed make
Supply,installation,Testing and commissioning of 33kV Polymeric composite Disc Insulator with fitting (36KV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm) suitable for 0.1ACSR of reputed make
Providing and fixing of danger plates with clamps as per REC standards
Providing and fixing of anti climbing devices with clamps as per REC standards
Providing and fixing of Earthing of ST poles Complete by GI Pipe 40 mm or GI Rod 20mm using 2.5 mtr long through GI Strip as REC construction Standard
Providing and Painting of ST Poles with one coat of red oxide and two coats of aluminum paint to give even shade.
Providing and laying of Cement bottoming of 16 mtr long ST Poles in mix 1:2:4 using 20mm crush stone aggregate including shuttering ,form work etc. as per REC standards 1cum /pole
Providing and fixing of Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete
Providing and fixing of Galvanised Nuts & Bolts
Supply, Installation, Testing & Commissioning of 33kV Isolator with Earthing Blade (36kV,1250A, Outdoor, 3 poles, 25 kA)
Providing and fixing of Straight Through Joints for cables
Providing and fixing of Cable Markers
Supply,Laying,Testing, and commissioning of 33KV, Single core 120 sqmm Aluminium, round wire Armoured XLPE Cable , FRLS One spare cable
Providing and fixing of 33kV outdoor Heat Shrinkable Cable Termination Kits suitable for 120 sqmm single core cable
Supply,Installation, Testing, and commissioning of 30 kV Lightening Arrestors (30 kV, 10kA, Station class, ZnO, Polymer) gap less
Electrical Equipment and Equipment structure
Supply and Erection of 9 Mtr. Long ST Pole(ST-410 SP33) with base plate and top cap including excavation of pit and back filling by boulders as per REC construction Standard
Providing and fixing of fabricated GI Channel/Angle duly fabricated of sorts as per site requirement
Supply, Installation, Testing and commissioning of 33/.433KV ,1.6MVA 3 Phase, 50Hz Outdoor type,Dyn-11, oil immersed ONAN cooled , Copper Wound Step Down Transformer ISI marked as per Energy Efficiency Level Losses given in detailed specification. The Transformer shall be manufactured using CRGO Core and fitted with ON Load Tap Changer suitable for primary voltage variation of 18150 to 33990 volts(-45% to +3%) and secondary voltage of 433+/-3%. The OLTC shall be fitted with AVR, Tap Normalizer, RTCC Panel UPS and Tap Position Indicator. Transformer shall confirm to IS 1180(Part -1) 2014 ammeded upto date with first filling of oil confirming to IS 335 of 1983 (with latest amendment)
Supply, Installation, Testing & Commissioning of 33kV Isolator without Earthing Blade (36kV,1250A, Outdoor, 3 poles, 25 kA)
Supply, Installation, Testing & Commissioning of 33kV Isolator with Earthing Blade (36kV,800A, Outdoor, 3 poles, 25 kA)
Supply, Installation, Testing & Commissioning of 33KV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type)
Supply, Installation, Testing & Commissioning of 33 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port
Supply, Installation, Testing & Commissioning of 33 kV Current Transformer (33 kV, 1Φ, Multi Ratio Multi Core, Outdoor) (1 No. per Φ)
Supply, Installation, Testing & Commissioning of 33 kV Voltage Transformer (33 kV/110 V, 1Φ, Multi-Core,Outdoor), (1No. per Φ)
Supply, Installation, Testing & Commissioning of 33 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m
Supply, Installation, Testing & Commissioning of 30 kV Lightening Arrestors (30 kV, 10kA, Station class, ZnO, Polymer) gap less
P/F of GI Pipe structure of nonimal bore 200, 5.9 mm thick as per REC standards
Providing and fixing of Galvanised Nuts & Bolts
Supply,Laying,Testing, and commissioning of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS.
Supply,Laying,Testing, and commissioning of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS.
Supply,Laying,Testing, and commissioning of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS
Providing and fixing of Lugs, Ferrules of sorts etc.
Proviidng,Laying,stringing ,tensioning and binding of 0.1 ACSR Conductor as per REC construction standards
P/F of T- Clamps of sorts of standard make
Supply,installation,Testing and commissioning of 33kV Polymeric composite Disc Insulator with fitting (36KV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm) suitable for 0.1ACSR of reputed make
Common Misc Items
Supply, Installation, Testing & Commissioning of A) Battery Bank 30 Volt, 100AH, of 15 no cells of 2Volt each, sealed maintanance free VRLA type, high impact polyprophelene copolymer container, flame retardant B) 30 Volt, 100AH, float cum bost charger with full wave rectification for 220Volt, 1 phase, 50 Hz, AC input supply
Supply, Installation, Testing & Commissioning of Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories
Supply, Installation, Testing & Commissioning of Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A), rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories
Supply, Installation, Testing & Commissioning of 7.5kVA Servo-Stabizer of reputed make
P/F of Rubber Mat 1mx2m 19mm thick
P/F of Fire fighting equipment consisting of A) Dry chemical powder type (6kg) for control room (3No) B) Carbon dioxide type of 4.5kg Capacity for control room (4No) C) Carbon dioxide type trolly mounted of 22.5 kg capacity for switch yard (2No)
P/F of 3 Sand Bucket Fire Extingiusher
P/F of Safety Helmet
P/F of Rubber Gloves for 33 kV level
P/F of Safety Belt
P/F of Safety Shoes
P/F of Earthing rod (set of 3 rods)
P/F of HV Detectors all voltages
P/F of Yard Lighting by way of using 2no 9m long GI high mast pole continuously tappered of optogonal cross section incl suitable shall raft foundation using 4 no 250w each LED Flood light confirming to IP-66 complete with all accessories and suitable control feeder panel
CIVIL WORKS (NOTE: Bidders shall quote the rates i/c of carriage of materials
Yard Concreting/Metalling
Earthwork in surface excavation not exceeding 30cm in depth
Providing and laying of Dry Stone soling including spreading /levelling /ramming by manual means
Providing and laying in position cement concrete in 1:4:8 mix with 40 mm (1 cement:2 coarse sand:4 graded stone aggregate 40mm nominal size).
Providing and laying in position cement concrete in 1:2:4 mix with 20 mm (1 cement:2 coarse sand:4 graded stone aggregate 20mm nominal size).
Supply/stacking/Laying/spreading including levelling of graded stone agg. 40mm nominal sizeby manual means
Fencing
Earth work in excavation by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 min width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth asdirected:1 meter from cutting edge All kinds of soils
Providing , laying , compacting & ramming of stone boulders of size for back filling of the excavated soil upto plinth level
Providing and laying in position mud mat in 1:4:8 mix with 20 mm stone agg excluding the cost of centring and shuttering.(1 cement:4 coarse sand:8 stone aggregate of 20mm nominal size)
Providing and laying in position 1:3:6 mix with 40 mm stone agg excluding the cost of centring and shuttering.(1 cement:4 coarse sand:8 stone aggregate of 40mm nominal size)
Centering and shuttering including strutting, propping etc. and removal of form work for Foundations, footings, bases for columns etc
Providing and fixing of structural steel of specified section for chainlink fencing,including cutting etc. and applying priming coat of approved steel promer (Complete job)
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 25x25 mm made of G.I. wire of dia 3 mm including strengthening with 2 mm dia wire or nuts, bolts and washers & applying a priming coat of an approved steel primer.
Providing and laying of 12mm thick cement plaster in (1:4) mix ( 1 Cement:- 4 couse sand) 12mm thick
Yard Earthing
Earth work in excavation by manual means in trenches in all types of soils including disposal of executed earth upto /water from cutting edges, disposal earth to be leveled and neatly dressed back in the trenches.
Providing and fixing of earthing electrodes (3meter long 40mm dia GI pipes) through GI Strip.
Providing and laying of earthing mat in flat Iron(50x8mm)
Filling back excavated earth in trench incl. ramming etc.
EQUIPMENT FOUNDATION:
Earthwork in excavation by manual means in trenchs for foundations , drains , pipes , cables etc ( exceeding 1.5 m in width ) and for shafts , wells ,cesspits and the like not exceeding 10 sqm on plan , depth upto 1m from cutting edge ,disposed earth to be levelled and neatly dressed in all kinds of soil
Providing and laying of stone soling in the excavated trenches, duly hand packed on level including ramming with iron hand rammers, including unloading etc
Providing and laying in position of mud mat in 1:4:8 mix with 20 mm stone agg excluding the cost of centring and shuttering.(1 cement:4 coarse sand:8 stone aggregate of 20mm nominal size)
Providing and laying in position 1:3:6 mix with 40 mm stone agg excluding the cost of centring and shuttering.(1 cement:4 coarse sand:8 stone aggregate of 20mm nominal size)
Providing and laying in position cement concrete in 1:2:4 mix with 20 mm (1 cement:2 coarse sand:4 graded stone aggregate 20mm nominal size).
Reinforcement for RCC works including straightening, cutting , bending, placing in position and binding all complete. Thermo-mechanically treated bars including carriage
Centering and shuttering including strutting, propping etc. and removal of form work for: Foundations, footings, bases for columns etc
Providing and laying of 12mm thick cement plaster in (1:4) mix ( 1 Cement:- 4 course sand)
Providing and fixing of ( 1''x1.5') Grouting Bolts with angle iron frame (Complete structure)
Providing and fixing of GI channel Iron (100x50x50x 6mm) at the top surface of transformer bed
Construction of cable trench
Earthwork in excavation by manual means in trenchs for foundations , drains , pipes , cables etc ( exceeding 1.5 m in width ) and for shafts , wells ,cesspits and the like not exceeding 10 sqm on plan , depth upto 1m from cutting edge ,disposed earth to be levelled and neatly dressed in all kinds of soil
Providing and laying of stone soling in the excavated trenches, duly hand packed on level including ramming with iron hand rammers, including unloading etc
Providing and laying in position mud mat in 1:4:8 mix with 20 mm stone agg excluding the cost of centring and shuttering.(1 cement:4 coarse sand:8 stone aggregate of 20mm nominal size)
Centering and shuttering including strutting, propping etc. and removal of form work for: Foundations, footings, bases for columns etc
Providing ,fixing of Angle Iron duly fabricated for cable support structure , including transportation.
Providing and laying in position cement concrete in 1:2:4 mix with 20 mm (1 cement:2 coarse sand:4 graded stone aggregate 20mm nominal size).
Providing and fixing of chequered plate 8 mm thick @47.2kg/sqm
Ali Mohammad Baba and Sons
stage.html
html • 0.03 MB
tech_bid_open.pdf
PDF • 0.11 MB
tech_eval.pdf
PDF • 0.12 MB
fin_bid_open.pdf
PDF • 0.11 MB
boq_comp_chart.xlsx
xlsx • 0.02 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .