Loading…
Loading…
Tender Value
₹25.7 L
EMD Value
₹52,000
Closing Date
15 Jun 2026, 5:00 pmDue tomorrow
Manoj Singhal
Executive Engineer (E), Gurugram
S/I/T/C of 60 Kwp ( 15 Kwp x 4 Nos ) Roof Top Grid Connected Solar Power Plant for Common Area Electric load of Newly Constructed 144 Nos T-III Houses and 24 Nos T-IV Houses in RTC Bhondsi District Gurugram
2026_HBC_526783_1
2026D818AFAE 4DAA 43A1 9487 30A0F7B9964057HHC
Open Tender
Civil Works
120 days
Bhondasi
S/I/T/C of 60 Kwp ( 15 Kwp x 4 Nos ) Roof Top Grid Connected Solar Power Plant for Common Area Electric load of Newly Constructed 144 Nos T-III Houses and 24 Nos T-IV Houses in RTC Bhondsi District Gurugram
2 documents required · 2 mandatory
₹5,900
₹52,000
Yes
8 Jun 2026
8 Jun 2026
16 Jun 2026
8 Jun 2026
15 Jun 2026
8 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 2 | [32.70.2]Supply Installation testing commissioning of Solar Photovoltaic grid connected roof top Plant conforming to MNRE specifications as amended, consisting of Mono/Poly Crystalline silicon solar cells, net metering facility, necessary protections, earthing, mounted on Aluminium/GI structure of suitable strength with following components complete as required:-
(a) Solar Photovoltaic Module manufactured in India, conforming to IS 14286/IEC 61215, IS/IEC 61730-Part-1, IS/IEC 61730-Part-2. Solar Photovoltaic Module conversion efficiency shall not be less than 16.5%. PV modules used in solar power plants/ systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years.
(b) Power Conditioning Unit (PCU) of 350-800 V DC Input voltage range and 400 V AC, three phase, 4 wire, 50Hz plus /- 2.5 Hz, output voltage suitable to generate AC
(c) Power with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degrees C. The PCU shall adjust the voltage and frequency level to suit grid frequency
(d) Data Monitoring System complete with accessories.
(e) Fixing of Array junction box and Main junction box with IP 65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required.
(f) Lightning and surge voltage protection.
(g) Connections and Interconnections by supplying and fixing required size XLPE insulated copper conductor 1.1 kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying and fixing of necessary channel/conduit lugs and other accessories etc. as required. 2. Above 10 kWp and up to 100 Kwp [Through Rate] | 60 | KWp | 42,902 | ₹25,74,120 | BI01010001010000000000000515BI0100001113 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.90 MB
BOQ_605759.xls
BOQ • 0.43 MB
777951Z157763.pdf
Additional Documents • 3.63 MB
OT0157763.pdf
Other Document • 1.00 MB
Download all tender documents and submit your bid