Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.8 LAccepted-AOC | L1 | Accepted-AOC THE LOWEST TENDERER | |
| 2 | L2₹30.2 L+₹4.4 L (17.0%)Rejected-Finance 3RD FLOOR BHAKTAMAR RESIDENCY SOMNATHNAGAR ROAD PUNE 411014 | PUNE | PUNE | MAHARASHTRA | 411014 | L2 | Rejected-Finance NOT THE LOWEST TENDERER | |
| 3 | L3₹32.3 L+₹6.5 L (25.1%)Rejected-Finance | L3 | Rejected-Finance NOT THE LOWEST TENDERER | |
| 4 | L4₹32.7 L+₹6.8 L (26.4%)Rejected-Finance | L4 | Rejected-Finance NOT THE LOWEST TENDERER |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
29 Feb 2024, 6:15 pmClosed
GE MH AND RH KHADKI
Military Engineer Services Garrison Engineer MH and Range Hills Range Hills Road Khadki, Pune 411003
REP MAINT TO LT UG CABLES LT APFC PANEL SWITCH GEAR CONVERSON OF OH LINE TO UG AND VARIOUS MOTORS SLUDGE PUMPS ETC INCL CLEANING OF SLUDGE TANKS RAW SEWAGE TANKS ETC AND CONNECTED PIPE LINE NETWORK OF 0.6 MLD STP AT RH UNDER GE MH AND RH KHADKI
2024_MES_640488_1
8526/E8
Open Tender
Civil Works
Item Rate
180 days
GE MH AND RH KHADKI
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
KHADKI
₹90,000
3 Apr 2024
2 Feb 2024
2 Mar 2024
2 Feb 2024
29 Feb 2024
17 Feb 2024
2 Feb 2024 - 22 Feb 2024
Amount
Supplying, laying, jointing, commissioning and testing XLPE insulated screened PVC bedded, armoured, heavy duty underground electric cable in replacement with stranded aluminium conductor 1100 volts grade confirming to IS-7098 (Part-I-1988) laid in trenches/ducts/wall / floor / pipes/ poles including cable glands and aluminium lugs of appropriate size, pvc sleeve etc complete all as directed by Enginner in -Charge for following sizes . Make :- Havells / Gloster / Finolex / Polycab
300 sq mm 3.5 core
240 sq mm 3.5 core
185 Sqmm 3.5 core
150 sq mm 3.5 core
95 sq mm 3.5 core
70 sq mm 3.5 core
50 sq mm 3.5 core
35 sq mm 3.5 core
25 sq mm 3.5 core
16 sq mm 4 core
NOTE :- Earth work, bricks, riddled earth, GI pipe for protection of cable will be measured & paid under under relevant items of schdule.
Supply and errect in vertical position steel tubular swaged poles, type 410 SP- 31 (09 mtr long) in replacement with 300mm x 300mmx6mm mild steel plate continiusly welded to pole, final taper plug, bolts,nuts and screws and making holes as per requirement all as specified including factory painted with two coats of black bituminous paint internally through out and externally for embeded portion and applying one coat of red oxide primer, making 05 Nos strip each 30 cm high with super enamel paint ( Black and yellow) from ground level / coping upto 1.5 m, painting with two coats of aluminium paint for the remaning height complete all as specified and directed. Note :- PCC in foundation, copping, excavation and earth work shall be measured and paid separately under relevent items of sch.
Aluminium bus bar strips with proper colour code -04 No, 300 A cap, insulator, nuts bolts etc complete.
Indicator Lamp-01 Set (Set of three)
Incommer MCCB 4P 250 Amp, 415V, 36 KA Ics = 100 Icu Adjustable type - 01 No
Outgoing, MCCB 4P 125 amp, 415V, 25 KA Ics = 100 Icu Adjustable type - 05 No
MCB TPN 32A, 10KA B CURVE - 01 Nos for Street light panel
Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
Note : (i) Electrical connection from switchgear to bus bar would be through aluminium strips of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminum lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 50x50x6mm with bottam of panel having minimum 60cm height from existing ground/floor level.
M & L in replacement earthing complete with galvanized steel earth plate electrode 60 cm x 60cmx6 mm thick, buried directly in ground vertically (earth pit not less than 2.25 m deep below ground level) with top edge of the earth plate not less than 1.5m below ground level , connected to 32x6 mm GI strip as earthling lead by means blots and nuts check nuts and washers of galvanized iron and connected to main switch board including watering arrangement with PCC chamber, MS funnel, wire gauge. CI cover with frame, 50 MM dia GI pipe light grade for protection of wire/strip etc including necessary excavation in any type of strata, returning, filling removal of soil outside MD land, filling of charcoal and salt complete all as shown in electrical plate No. 3 of MES Sch Part I, connected to earthing test point all as specified and directed on testing on completion.
Supply, fixing and testing in replacement Inverter LED Street light fitting of 90 Watt with PDC housing complete with battery back up of upto minimum 2 hrs with body robust,corrosion resistant,superior finish and without any cracks or through holes,made in a single piece by high pressure die cast aluminium alloy.The luminaries shall be monolithic construction totally enclosed dust and water proof with minimum IP - 66 protection as per IS - 10322-1982(Part -I) with latest amendments and input voltage range 140 - 300 V, AC, frequency 50 - 60 Hz ,P.F should be more than 0.95 with Total Harmonic Distoration THD(I) less than 10% ,cool white colour and lamp starting time should not be more than 10 second fitting should be provided with 10 KV surge protection.Driver should be constant current constant voltage driver .Driver should have high voltage withstanding capacity upto 300 V, AC. Driver should also have double phase protection,no load , open circuit and short circuit protection .LED light fitting should be suitable for ambient temperature from -10 degreeCentrigrade to 60 degree Centrigrade and humidity level 10% to 90 % RH. Covers should be polycarbonate/toughened glass to ensure minimum IP 66 degree protection.Cover should not degrade due to heating and ageing.The efficiency of LED luminaries system shall be more than 100 lumens per watt and must be certified by the LM-79 test report and including provision of connection for street light from pole box with 2.5 Sqmm PVC insulated stranded copper conductor FRLSH cable, 1100 Volts grade ISI marked complete all as specified and directed by Engineer-in- charge. Make : HALONIX /JAQUAR/BENLO/HAVELLS
S&F in repairs Bracket for fixing of street light fittings bend to shape, made out of 40 mm dia GI pipe medium grade upto 1.5 mtr long fixed with two sets of MS clamps made out of flat iron of size 50x6 mm fabricated to shape and fixed with nuts bolts and washers & two coats of aluminium paints over a coat of red oxide primer complete all as specified and directed by Engr-in-Charge Note : MS clamps, nuts, bolt and washer shall be measured seperately under relevant item
S&F in repairs Junction box of size not less then 325x220x150mm, made of high quality thermo plastic polystyrene, weather proof, dust, jet water proof, chemical, acid corrosion, impact, insulated & shock proof IP 66 / 67 for outdoor Installation with internallly embedded gasket (PUR) including the box fitted with connector 8 way 40 Amps 01 No including Emlex stud type TB 4 Nos incoming / outcoming cable at controlled with MCB SP 6 Amps 01 No & enclosed along pole including fixing with steel tubular poles with two Nos FI clamps 25mmx3mm with nuts, bolts and washers complete and making connection with 1.5 sqmm copper conductor unsheathed FRLS PVC insulated 3 core from junction box to security lights fittings duly laid inside the streel tubular pole and bracket. complete all as specified and directed by Engineer-in-Charge. Note : 40 mm bore GI pipe light grade, 3 core 1.5 sqmm cable and GI brackets will be measured separately . Make :- Sintex Cat Part No. GSJB-3726 or equivalent in Indokop / Hensel Note :- Cost of flat iron clamp is deemed to include in unit rate of this items.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation of poles stays laying of electric cables, pipes etc and getting out in soft/loose soil complete all as specified and directed.
All as per item No 8 but in hard/dense soil.
Removing excavated material soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed
Returning, filling in, including spreading, levelling watering and well ramming in layers not exceeding 25cm in soft/loose soil complete all as specified and directed.
M & L for riddled earth for cushioning to under ground electric cable including spreading , levelling and hand punning complete all as directed. Note - Punned thickness shall only be measured & paid.
M& L for road cuttung / foot path and making good with PCC 1:3:6 TYPE C-2 (using 40 mm graded stone aggregate) of 150 mm
Supply and laying un-reinforced precast concrete cable cover LV, Type I, flat, size 250mm x 150mm x 40mm for under ground cable all as specified and directed.
Supply and laying GI tubes light grade, galvanized, 40 mm bore in repair, laid in trenches or under floor or fixed with poles/walls for protection of electric cable all as directed
All as per item No -15 but 80 mmm bore.
Plain cement concrete (PCC) type C2 1:3:6 using 40mm graded aggregate stone for making foundation of Pole/stay assembly
Plain cement concrete (PCC) type C1 1:3:6 using 20mm graded aggregate stone for making copings of Poles etc.
Supply only straight through joint kit, heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size 25 to 50Sqmm 3.5/4 core cable complete all as directed.
Supply only straight through joint kit, heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size from 70 up to 120 sq mm3.5/4 core cable complete all as directed.
Supply only straight through joint kit, heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size from 150 to 185 sq mm 3.5/4 core cable complete all as directed.
Supply only straight through joint kit, heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size from 240 to 300 sq mm 3.5/4 core cable complete all as directed.
Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint.
Supply and fixing MCCB, 63 amps, 3 pole, 415 V, 16 KA breaking capacity, with Thermal magnetic release, incl dismentling taking down unserviceable one, making cutting of existing panel for fixing MCCB on suitable fitting and make panel good and all as directed by Engr-in-charge. Make- Indoasian (Optium 1.1)/Legrand/L & T
All as per item No 24 but, 100 amps, 3 pole, 415 V, 16 KA breaking capacity
All as per item No 24 but, 125 amps, 3 pole, 415 V, 16 KA breaking capacity
All as per item No 24 but, 160 amps, 3 pole, 415 V, 36 KA breaking capacity
All as per item No 24 but ,250 amps, 3 pole, 415 V, 36 KA breaking capacity
Supply and fixing MCCB, 4 pole, 36 KA breaking capacity, with Adjustable type, optium 2.0, 315 amps, incl dismentling taking down unserviceable one, making cutting of existing panel for fixing MCCB on suitable fitting, Iincluding use required sheet metal and make panel good and all as directed by Engr-in-charge.
Supply and fixing MCCB, 4 pole, 415 V, 16 KA breaking capacity, with Thermal magnetic release, optium 1.1, 63 amps, incl dismentling taking down unserviceable one, making cutting of existing panel for fixing MCCB on suitable fitting and make panel good and all as directed by Engr-in-charge
All as per item No -30 but of capacity 100 Amps
All as per item No - 30 but of capacity 125 Amps
All as per item No - 30 but of capacity 160 Amps
M&L for cleaning of MES electric supply installations/campus by surface dressing or trimming of natural ground to remove small unequalities not exc 15 cm deep (including removing vegetation/ shrubs/brush wood/under growth) and carrying away the rubbish to a distance of not exc 50 mtr away complete at an interval of every 30 days for the various sub stations. Note: Spray of herbsite deemed included in quoted rate.
Decarbonizing of LT indoor/outdoor Panel/feeder pillar box any type removing unserviceable MCCBs, burnt busbars, unserviceable indicator lamps, unserviceable Ammeter, unserviceable Volt meter, replacing burnt, damaged bus bar of any size and fixing proper hanging front and rear openings, welding of hinges including welding of brokieng MS sheet using extra sheets replace burnt thimbles with new existing size thimbles replacing with new MCCB, incluidng dismantling the existing connected cables and re-connecting the same cables complete all as specified and directed by Engr -in- charge. Note : MCCBs, Bus bars, indicator lamps, Ammeter, Volt meter, will be measured & paid separately as supply only .
Servicing of APFC panel cleaning, tightning of connections, setting programme, testing of CT'S including caliberation of APFC panel and replacing unserviceable capacitors, capacitor contactor, breakers, power factor controller after servicing testing panel and achive power factor of 1.00 all as directed and specified by Engr-in-Charge. Note: Capacitors, capacitor contactor, power factor controller measered and paid separately.
Note for item Nos 35 & 36 :- (i) Quoted rate includes replacement of damaged panel locks as per existing as per site requirement. (ii) Painting of panels with mounting stand (with two coat of paint as specified by Engr-in-charge) included in quoted rate . (iii) suitable size of lugs and cable gland for panel deemed included in quoted rate. (iv) Necessary MS sheet,Hinges and welding including coated rate. (v) Rate includes cleaning of panel by using high speed air blower to remove dust.
Supply and fix in replacement Power factor controllers (96x96), 5 steps, with timer, 415 volt, AC, 50 HZ power supply including suitable wiring all as directed and specified by Engr-in-Charge. Make: L &T Cat No ETACONM005R or equivalent make of Scheider/ EPCOS
Supply and fix in replacement Power factor controllers (144x144), 8 steps, with timer, 415 volt, AC, 50 HZ power supply including suitable wiring all as directed and specified by Engr-in-Charge. Make: L &T Cat No ETACONM008R or equivalent make of Scheider/ EPCOS
Supply replace and test, commissioning of LT capacitor upto 5 to 15 KVAR, 440Volt of Heavy duty for non-linear loads up to 440 V cylinderical type on existing APFC panel and necessary panel wiring, all as directed and satisfied by Engr-in-Charege Make: For capacitor L & T Cat No: LTCCU or equivalent make of Legrand/Schneider
All as per item No - 40 but 20 to 25 KVAR, 440 volt Make: For capacitor L & T Cat No: LTCCN or equivalent make of Legrand/Schneider
Supply replace and test, commissioning of capacitor duty contactor of capacity of 15 KVAr on existing APFC panel and necessary panel wiring all as directed and satisfied by Engr-in-Charege. Make L & T cat No: CS96127 or equivaltnt make of Legrand /Schneider
All as per item No -42 but of 25 KVAR contactor Make L & T / Legrand /Schneider
Supply & laying pipe galvanised medium class including all fitting ( such as bends, elbows, tees required for reduce size as per site requirment, short pieces, connectors, back-nuts, diminishing pieces, caps, plugs and unions, etc) and fixing complete with clips, wall hooks, wooden plug, or laying in trenches or fixed to wall /floor/roof including cutting screwing etc, all as specified and as directed.
50 mm bore pipe
40 mm bore pipe
25 mm bore pipe
20 mm bore pipe
Supply and lay in repairs M S Pipes B class Heavy grade with all fittings,flange and nut bolts etc laid in floors or fixed to walls and ceilings etc of 65 mm dia.
All as per item No 45 above but of size 80 mm dia
All as per item No 45 above but of size 100 mm dia
All as per item No 45 above but of size 150 mm dia
Supply and fixing of gun metal globe or gate valve ISI marked with iron wheel head screwed both ends for iron pipes or unions conforming to IS-778 complete with jointing materials like rubber sheet, nuts and bolts for the following sizes complete all as specified and directed.
All as per item No 46 above but of size 50 mm bore pipe
All as per item No 46 above but of size 40 mm bore pipe
All as per item No 46 above but of size 25 mm bore pipe
All as per item No 46 above but of size 20 mm bore pipe
Taking out of existing non clog submersible pump set 3 HP,415 volt 50HZ AC supply from raw water sewage sump and Equalization tank after disconecting the electric connection complete . Dismantling the pump & electric motor , cleaning of blockage sludge and servicing of pump , motor including necessary oiling , greasing etc complete checking of other parts of pump, motor including replacement of minor spare parts like bush bearing, pin nut bolts etc checking of insulation resistance of motor winding, and reassembled the same and reinstalled to its original position complete all as specified and directed by Engr-in-charge . Note: (i) Winding will be measured & paid seprately under relevent item of schedule. (ii) The rates for necessary T&P required to taking up and down of submersible pump is deemed to be included in quoted rate.
All as per item no 47 above but of capacity 7.5 HP (Raw sewage tank)
All as per item no 47 above but of capacity 12.5 HP (Raw sewage tank)
Dismantling the coupling and taking out 7.5 HP pump from pump motor set fixed in foundation and transport to work shop opening the pump, replacement unserviceable bearing and bushes and worn out nut and bolts gaskets, machining of shafts, over hauling & greasing of pump and reassembling packing gland with suitable size after fixing with motor, testing of motor and pump with full load at site complete all as specified and directed by Engineer-in- charge. (Filter pump)
Disconnectioning of electric connection and dismantling and taking out burnt electric motor from foundation /centifuge for repair in local workshop ,opening of motor for rewinding with super enamelled copper winding wire of suitable gauge as existing and varnishing, heating and testing after repair upto the entire satisfaction of Engr-in-Charge, after necessary repair reassembling and fixing it in its original location of capacity 3 HP, 3 Phase, 440 Volt capacity complete all as specified and directed by Engineer-in- charge. (centifuge Pump).
All as per item no 49 above but 7.5 HP feed pump motor, (Equalisation tank pump moter) .
All as per item no 49 above but 15 HP ( Air blower motor).
All as per item no 49 above but 1 HP (Screw pump and slow moving agitator motor).
All as per item no 49 above but 0.5 HP (Poly dose pump motor).
Disconnectioning of electric connection and dismantling and taking out burnt electric motor non clog subersible pump from sewage sump for repair in local workshop ,opening of motor for rewinding with super enamelled copper winding wire of suitable gauge as existing and varnishing, heating and testing after repair upto the entire satisfaction of Engr-in-Charge reassembling the motor and fixing back to its original location of capacity 5 HP, 3 Phase, 440 Volt complete all as specified and directed by Engineer-in- charge. (Motor of Raw sewage sump and equalization tank)
All as per above item no 50 but of capacity 7.5 to 12.5 HP.
M & L for servicing of compressor with air blower of 600 Cum/hr capacity unit replacement of compressor oil,air filter, oil filter, etc complete all as specified and directed by Engineer-in- charge. Note :- The rates are inclusive of replacement of compressor oil, Oil filter and any other minor parts required for smooth functioning of the Air blower.
Carring out Testing of treated water and Raw sewage water (befor and after) as per norms / standard raw sewage characteristics from Govt approved laboratory complete all as directed by Engr-in- charge. Note - Contractor shall collect water sample from raw sewage tank and from treated water tank of STP twice in a month for testing from Govt approved agency and report shall be submitted to Engr-in-charge.
Supply and fixing in repairs fan belt for compressor of SPA 1360LP Make Ecodriver or equivalent complete all as specified and directed by Engr- in -charge.
Supply and fixing in repairs fan belt for centifuge Make Ecodriver or equivalent complete all as specified and directed by Engr- in -charge.
Supply and fixing in repairs compressor filter Make Ecodriver or equivalent complete all as specified and directed by Engr- in -charge.
Supply and fixing in replacement fine bubble air diffuser type 63-1000 membrane OD 63 mm length 1000 mm air flow rate 7.0 – 10.0 m3/hr including taking down complete all as specified and directed by Engineer-in- charge.
M&L for cleaning of various types of RCC tanks as per under mentioned descriptions by Dewatering the water /sludge from tank with the help of sewage suction pump and clean the interior portion of tank (bottom and all side walls of tank) by means of coir/wire brush etc and wash the interior portions of tanks by using water and clear away of all sludge, vegetation, muds to a distance not exc 50 m all as specified and directed by Engr-in-charge for the Bar screen chamber tank.
All as per item No 57 above but Raw sewage collection tank no-1 of size (Dia 4.5mtr and depth 10.5 mtr)
All as per item No 57 above but stilling chamber of size (1m x1m x2m,) Fine screen chamber (1m X 0.5 X 0.45m), grid chamber (1.8m X 1m X 1m) , channel upto equalization tank of capacity 5 cum.
All as per item No 57 above but Equalization tank of size (8m x 6m x 4m) of capacity 192 cum (approx).
All as per item No 57 above but MBBR tank ( Aerartion) of size (8m x 4m x 3.9m) of capacity 125 cum (approx) .
All as per item No 57 above but tube settler tank of size (8m x 2.4m x 3.7m) of capacity 72 cum(approx).
All as per item No 57 above but chlorine contact tank (CCT) of size (8m x 2.2m x 3.5m) of capacity 62 cum (approx).
All as per item No 57 above but Sludge sump of size 2.6m x 2.4m x 2m) of capacity 13 cum (approx).
All as per item No 57 above but treated water tank of size (16.23m x 3.4m x 4.5m) of capacity 250 cum (approx).
M & L for Bar screen chamber (Square Net) as per existing size/sample at site with suitable fixing arrangements complete all as specified and directed by Engineer in Charge. Note:- (i) The rates are inclusive of all civil works involved for fixing the Bar screen chamber. (ii) The rates are inclusive of MS channel work required for fixing the Bar screen chamber.
Supply and laying in replacement UPVC Pipe grade (SCH-80) IS specification 4985/1988 sustainable pressure not less then 10 Kg/Cm2 of size 100 mm outer dia, including necessary fittings such as tees, bends elbows & reducer etc complete as specified directed. Make : Supreme/SFMC or equivalent make.
All as per item No 59 above but of size 50 mm outer dia.
M&L pebbles 25-40mm for change of filter media pressure type in the sand filter and activated carbon filter including opening and reassembling carefully up to entire satisfaction of Engr-in-charge
All as per item No 60 above but Pebbles 12-25mm
All as per item No 60 above but Pebbles 6-12mm
All as per item No 60 above but Pebbles 2-6mm
All as per item No 60 above but Activated carbon
All as per item No 60 above but Quartz sand 0.3 mm to 0.5 mm
Supply and fixing in repairs cast iron butterfly valves with CI disc ‘ISI ’ marked lever operated PN-1.6 of 200 mm size including taking down complete all as specified and directed by Engineer-in- charge. Make : GM/Normax or equivalent make
All as per item No 61 above but 150mm Make : GM/Normax or equivalent make
All as per item No 61 above but 100mm Make : GM/Normax or equivalent make
All as per item No 61 above but 80mm Make : GM/Normax or equivalent make
All as per item No 61 above but 50 mm Make : GM/Normak or equivalent make
M & L for Surface dressing n exc 15 cm deep in soft/loose soil at STP MH area including cutting of Bushing and grass complete all as specified and directed by Engineer in Charge.
Supply only Liquid Sodium hypochloride for STP in required quantity for dosing in dosing tank all as specified and directed
Supply only bactacult for culture development in STP used in controlled manner as per specified and directed
Supply and fix Centifuge Screen bag JM centifuge model 60-5 in cenrtifuge as per specified and directed
Dismanling the unserviceable pressure guage and S&F new pressure gause with pressure range 0-10 Kg/sq cm complete all as specified and directed by Engr- in -charge
M&L for replacement of PVC insulated, PVC round sheathed multistranded copper, unarmoured copper cable round in shape of size 2.5 Sqmm 3 core with multistanded copper conductor inluding taking down complete all as specified and directed by Engineer-in- charge.
M&L for replacement of submersible cable round/flat of 4 core 6 Sqmm with multistanded copper conductor including taking down complete all as specified and directed by Engineer-in- charge.
Servicing and ovehauling of mobile lifting chain pully (1 ton capacity) fixed at existing submersible pump by disconnicting the hook and taking out the chain from the pully block , greasing/oiling the movable parts and fixing it back to its original position complete all as specified and directed by Engr-in-charge.
Servicing and ovehauling of mobile lifting chain pully (2 ton capacity) fixed at existing submersible pump by disconnicting the hook and taking out the chain from the pully block, greasing/oiling the movable parts and fixing it back to its original position complete all as specified and directed by Engr-in-charge.
Aluminium bus bar strips with proper colour code -04 No, 500 A cap, insulator, nuts bolts etc complete.
Indicator Lamp-01 Set (Set of three)
Incomer :- MCCB of rating 400 Amps, 04 Pole 36 kA, Ics=Icu=100% DN Series Make L & T (01 nos)
Out going :-
32 Amps, 03 Pole MCB 10 kA, C curve Make L & T (03 Nos)
20 Amps, 03 Pole MCB 10 kA, C curve Make L & T (09 Nos)
06 Amps, 03 Pole MCB 10 kA, C curve Make L & T (03 Nos)
06 Amps, 01 Pole MCB 10 kA, C curve Make L & T (for control) (01 Nos)
Timer for Star Delta connection (09 Nos)
Relay of capacity 09 - 14 Amps for motor (04 Nos)
Relay of capacity 06 - 10 Amps for motor (07 Nos)
Relay of capacity 04 - 06 Amps for motor (01 Nos)
Relay of capacity 02.5 - 04 Amps for motor (03 Nos)
Power contactor of 50 Amps capacity 03 pole, 240 Volts with 02 NO and 02 NC (06 Nos)
Power contactor 03 Pole 240 Volt with 02 NO and 02 NC of 32 Amps capacity (06 Nos)
Power contactor 03 Pole 240 Volt with 02 NO and 02 NC of 20 Amps capacity (27 Nos)
Din rail connector of 32 Amps (72 Nos)
Digital Smart Panel Meter for showing voltage and Amp meter suitable for 400 / 5 CT (01 Nos)
CT of capacity 400/5 (03 Nos)
06 Sq mm PVC insulated multistranded copper wire for power wiring of 7.5 to 15 HP Motor
4 Sq mm PVC insulated multistranded copper wire for power wiring of 0.5 to 5 HP Motor
1.5 Sq mm PVC insulated multistranded copper wire for power wiring for control, other panel wiring and CT wiring
Hardware like lugs, nut bolts, insulator for bus bar, cable tie, cable tray,
Motor on / off indicator
ON and Off push button along with NO and NC element. Qty as per OEM recommendations.
Change Over Switch of rating 400 amps (01 Nos)
Note : (i) Electrical connection from switchgear to bus bar would be through copper strips of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminum lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron frame of size 50x50x6mm with bottam of panel having minimum 60cm height from existing ground/ floor level. (vii) The rates are inclusive of all spares required as per OEM recommendations to make the starter panel fully functional. (viii) The control wires from motor / pump to starter panel fully functional. (ix) Contractor has to visit the site and get a brief on scope of work before quoting the tender.
Preparation of painted surfaces of all exposed metallic surface such as various sizes valves/ wheels, raillings, stair case and open pipes inlet/ out let etc. by means of wire brush /emery etc and cleaning and painting with one coat of red oxide and two coat epoxy paint of existing colour shades all as specified and directed.
All as per item No 72 above but activated carbon filter tank (01 nos ) with connected pipe lines and accessories.
All as per item No 72 above but Activated sand filter tank (01 nos ) with connected pipe lines and accessories.
All as per item No 72above but Air Blowers (02 nos) with accessories and open pipes etc
M&L for Digital Backlit glow sign board star flex made out of 0.75 x 0.75 mm MS frame box type with back side having galvanized tin sheet of thickness not less than 22 gauge, and side cover s with powder coated tin sheet ISI marked including 10 watts -02 nos LED tube rods. The frame box is to be fitted / welded on MS round pipes -02 nos of lenght 3 to 4 mtrs each of thickness not less than 16 gauage. The size of the board should be 8 feets x 3 feets . Note:- (i) The rates of pcc work for coping and foundation of these boards are included in the quoted rates. (ii) The MS frames and MS round pipes are to be painted black in colour after one coat of red oxide. (iii) The rates are inclusive of dismantling the old glow sign board from any height.
Supply and fix 15 ft x 3 ft size, 3 MM ACP sheet Recto reflective Sign board of size on frame of MS tubing 40mmx40mm, with 4 nos support of 40mm tubing for board including Side pillar of height 8 ft mounted on RCC coloum on entrance door of STP MH made out of 40x40 mm Angle of 6mm thick of 4 nos angle on each columb with support at interval of 2 ft all as specified and directed by Engr- in- charge. Note:- (i) The content on the board will be finalised with concerned JE/Engr-in-charge. (ii) The rates are inclusive of dismantling the old glow sign board from any height. (iii) The cost is inclusive of MS work including fabrication wherever required to fix the boards at their respective locations.
Supply and fix 6 Ft x 4 Ft sign board made out of 3MM ACP Sheet LG mark vineyal pasting on 0.75 x 0.75 inch MS frame with vertical side pole of ms angle of size 40x40 mm , 6 mm thickness with necessary excavtion, PCC and copping all included all as per specified and directed by Engr-in-charge. Note : (i) Content of board to be frinalize with concern of JE/ Engr-in-charge. (ii) The rates are inclusive of dismantling the old glow sign board from any height. (iii) The cost is inclusive of MS work including fabrication wherever required to fix the boards at their respective locations.
Supply and fix Sign board of Size 2ftx 1 ft on 3mm ACP sheet LG mark vineyal pasting board with mirror screw including fitting all included all as per specified and directed by Engr-in-charge. Note : (i) Content of board to be finalize with concern of JE/ Engr-in-charge. (ii) The rates are inclusive of dismantling the old glow sign board from any height. (iii) The cost is inclusive of MS work including fabrication wherever required to fix the boards at their respective locations.
Supply and fix Sign board of size 2ftx 1 ft on 3mm ACP sheet LG mark vineyal pasting board mounted on angle of 25 x 25 of 3 ft long srewed fixed on wall/parapit including fitting all included all as per specified and directed by Engr-in-charge. Note : (i) Content of board to be Finalize with concern of JE/ Engr-in-charge. (ii) The rates are inclusive of dismantling the old glow sign board from any height. (iii) The cost is inclusive of MS work including fabrication wherever required to fix the boards at their respective locations.
M&L for RCC cement concrete rectangular type Route indicator for Treated water Pipe line made out of RCC M-20 grade of size 750mm x 300mm x 80mm, having embrosed on both sides with "TREATED WATER OF STP NOT FOR DRINKING" including painting with two coats of synthetic enamel red colour paint to exposed surfaces complete all as specified and directed by the Engineer-in-charge. Note : The foundation work (PCC foundation) for fixing the route indicator is included in the quoted rates
Adinath Technical Services
PAMS ENTERPRISES
SHREE VAIBHAV ELECTRICALS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .