Tender Value
₹53.4 L
EMD Value
₹1.1 L
Closing Date
4 Feb 2020, 5:00 pmClosed
Raja Nagender Singh
Executive Engineer, Elect. Division PWD B and R Br., Karnal.
Construction of National Law University in Rajiv Gandhi Education City, Rai Distt. Sonipat (Providing Fire Alarm and PA system Hostel Block)
2019_HRY_112406_1
PWD/Elect-KNL/Elect-KNL/16731
Open Tender
Construction Works
Works
150 days
Karnal
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,000
Executive Engineer, Elect. Division PWD B and R Br
₹1.1 L
17 Mar 2020
12 Dec 2019
5 Feb 2020
12 Dec 2019
4 Feb 2020
12 Dec 2019
Amount
FIRE ALARM SYSTEM SITC of Micro processor based 2 wire fault tolerant, networkable type Fire Alarm / Detection Control Panel (having nos. of loops to suit minimum 20% extra over the nos. of fire detectors. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, loop cards, minimum 160 characters LCD unit/ 5.7’’TFT to indicate Fire / Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel Shall be sheet Steel power coated, sealed to IP30. The Panel shall have 20 Zones with individual LED Indicators, expandable to 80 LED Indicators. The Panel shall have 2 Serial Ports. The pane\l shall have a built in power supply, battery charger maintenance free battery capable of running for a minimum 24 hours operation complete as required. And conforming to BS5839 standards and Duly Approved by EN 54/UL/VDS as per specifications complete in all respect up to the entire satisfaction of Engineer-in – charge of work. MAKE BOSCH / SIEMENS / EDWARDS EST3X / MORLEY IAS ZXE SERIES 6 Loops (Hostel Block)
SITC of Analog Addressable type Active Repeater Fire Alarm Panel with Backlit LCD display, having controlls for reset, mute, accept, silence alarms and self test conforming to BS5839 standards with all labour and materials required to complete the job in all respect up to the entire satisfaction fo engineer-in-charge of work. Make BOSCH / SIEMENS / EDWARDS / MORLEY
Supply, Installation,Testing & Commisioning of Analog Addressable Intelligent optical smoke detector with decentralise intelligence,automatic function self test, soft addressable Photo type with inbuilt fault isolator as per NFPA style 7 wiring complete with base as required
SITC of Intelligent Analog Addressable type Smoke Detector that combine Photo Electronic and fixed temp thermal with dual LED, hard addressable having rotary decade address switches, with mounting base complete as requried conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of engineer-in-charge of work. Make BOSCH / SIEMENS / EDWARDS / MORLEY
SITC of intelligent Analog Addressable type Manual Call Point having Surface or flush mounting option fully compliant to EN 54 having Rotary Decade switches for addressing with Back Box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Make BOSCH / SIEMENS / EDWARDS / MORLEY
Supply, installation, testing and commissioning of addressable control module complete as per specification. Make BOSCH / SIEMENS / EDWARDS / MORLEY
Supply, installation, testing and commissioning of addressable monitor module complete as per specification. Make BOSCH / SIEMENS / EDWARDS / MORLEY
Supply Installation, Testing & Commissioning of wall mounting addressable type sounder including power supply and accessories.
SITC of Intelligent Analog Addressable type Response Indicator with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work Make BOSCH / SIEMENS / EDWARDS / MORLEY HONEYWEL.
Supply Installation, Testing & Commissioning of Glow Type Exit Sign Board photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink Sulphate as bare chemical class - I material PSPA fixed on 3 mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener including cost of labour and material required to complete the job in all respect up to entire satisfaction of Engineer-in-Charge of work. Make PES/Giolite/OMEX.
PUBLIC ADDRESS SYSTEM. Supply, Installation, Testing & Commissioning of a 12/ 16 speaker circuit digital voice alarm controller that supports 12/16 zones without additional equipment. Direct connection to 12/16 speaker lines from controller. Monitored emergency Push to Talk paging microphone part of controller. Includes Digital Signal Processor, Audio storage for pre-recorded messages, audio matrix, amplifier monitoring and control, loudspeaker output connection terminals and audio source connection ports for auxiliary inputs.
Supply, Installation, Testing & Commissioning of amplifier to be connected directly to controller with standard 100V line. Equipped with Toroidal Transformer, protective circuits, LED Status indicators and speaker output short circuit protection, extensive heat sinking, fan cooling and soft start. With balanced XLR input. 480- 500 watt. Make Honeywell / BOSCH / Heinrich.
Supply, Installation, Testing & Commissioning of 6W ceiling speaker 5inch in metal with metal enclosure with Line Matching Transformer and tapping of 3W and 6W. Make Honeywell / BOSCH / Heinrich
Supply, Installation, Testing & Commissioning of 19" Mounting Rack with required power points suitable for above equipments. Make Comrack / Valrack/ Hive Network.
Supply, Installation, Testing & Commissioning of 6 watt volume controller with box & modular plate etc complete as required. Make Honeywell / BOSCH / Heinrich.
Wiring for PA system with the following sizes of FRLS insulated copper conductor single core cables in existing surface/recessed M.S. conduit etc. as complete as required. Make Polycab / Finolex / Havells. 2 x 1.5 sq.mm (30/0.25mm)
Hytek Turnkey Projects Pvt. Ltd.
Protection Engineers
Insat Techno Services
JBR ELECTRONICS
TNS NETWORKING SOLUTIONS PVT LTD
Electrocare Systems and Services
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .