Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹70,000
Closing Date
3 Oct 2025, 10:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE
LAL DIGGI ALIGARH
EUDCA-02/2025-26
2025_DVVNL_1077038_1
EUDCA-02/2025-26
Open Tender
Electrical Works
Turn-key
90 days
EUDC ALIGARH
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
DVVNL
₹70,000
25 Oct 2025
24 Sept 2025
3 Oct 2025
24 Sept 2025
3 Oct 2025
24 Sept 2025
Amount
Safe carriage of following materials from Store centre or any other place to the respective site of work through the Kachha/Pacca road including loading, unloading at the respective ends and erection/laying of same including the work of dragging as per site requirement, jumpering of Transformer with 11 KV line through LT ABC cable, Weasal conductor etc. Cost of labour, T&P carrier etc. required for proper completion of work as per RESPO Norms is included in the work.
11 Mtrs. ST Pole
13 Mtrs. ST Pole
Earthing complete
Stay complete(GI Stay Rod 16x1800mm, 5 Kgs. Stay wire 7/8, Stay clamps, Insulator, Bolts, Nuts & Washers)
11 KV D.O. Fuse Set
11 KV TPMO
11 KV XLPE Cable 3x185sq.mm.
I/D & O/D cable Jointing kit suitable for 3x185mm2 XLPE cable
11 KV XLPE Cable 3x300sq.mm. (Double Curcuit)
I/D & O/D cable Jointing kit suitable for 3x300mm2 XLPE cable
ACSR DogConductor
LT XLPE CABLE AL.1*1000 SQMM (80 MTR*4)DOUBLE CKT
11 KV Disc Insulator with fitting
11 KV Pin Insulator with pin & nut
11 KV Pilfer proof metering cubicle 100/5 A
11 KV VCB I/C CTR 600/300/5A,350 MVA,24 VOLT(1250A)
11 KV VCB O/G CTR 200/100/5A, 350 MVA(1250A)
11 KV O/G VCB 200/5/1A
11KV CT/PT Metering Pole Mounting Unit 10/5A
Supply, fixing, installation and erection of following materials as per site requirement as per RESPO Norms:-
G.I. Pipe 6" dia
Top channel M.S. 100x50x2240mm
Droper Channel M.S. 100x50x2000 mm
Number plate
Danger Board with clamp N&B
Barbed wire
Aluminium tape
Stone pad
Clamp with bolt & nut
Nut Bolt with washer
Tee-off Channel MS size 125x65x1300mm.
Cross Bracing Angle
M.S. Angle (T/F Base)
1000 KVA, 11/0.433 KV, Copper Wound, 03 Phase, 50 Hz, Oil Cooled, Outdoor Type Distribution Transformer along with all Standard Fittings And Accessories
A-TYPE L.T. PANNEL 2000 AMP
FRAME STRUCTURE MADE OF GALVANISED MS ANGLE SUITABLE FOR FEEDER PILLER TYPE A
AL.LUGS 1000 SQMM
COPPER L PIECE
Concreting of Stay
Concreting of Support
CONSTRUCTION OF TRENCH WITH TRENCH COVER FOR LAYING OF HT & LT CABLE (30 MTR HT & 80 MTR LT )
PLINTH (2x2x1.5 MTR) FOR LT Pennal
Neutral & Body earthing for 11 KV VCB by drilling/boring a hole of size 200 mm dia and 3000mm long in depth and then inserting the Gel earthing electrodes of size 50mm dia and 3000 mm long inside the pit then mix the back fill compound nicely with the soil and re-filling the empty space around the earthing electrode including making of chamber at the top of the earthing as per direction of supervising engineer. It includes the cost of all material labour, T&P, carrier etc. required for proper completion of work. The aforesaid work shall be carried out as per RESSPO norms. Max neutral to earth voltage should be less than 3 volts and earth resistance should be less than 1 ohm.
Neutral & Body earthing for 11 KV L.T. Panel by drilling/boring a hole of size 200 mm dia and 3000mm long in depth and then inserting the Gel earthing electrodes of size 50mm dia and 3000 mm long inside the pit then mix the back fill compound nicely with the soil and re-filling the empty space around the earthing electrode including making of chamber at the top of the earthing as per direction of supervising engineer. It includes the cost of all material labour, T&P, carrier etc. required for proper completion of work. The aforesaid work shall be carried out as per RESSPO norms. Max neutral to earth voltage should be less than 3 volts and earth resistance should be less than 1 ohm.
Providing and fixing of welded wire mesh fencing around transformer plinth with M.S. Angle of size 35X35X6 mm. length and 1.20 Meters height, such panels shall be supported on M.S. Angle from of size 40X40X6 mm. having 04 Nos. corner supports of height 1.65 Meters including extended legs for grouting which will be used as a door for entry of the personnel or removal/shifting of transformer with welded hinges, sliding belt etc. for locking the arrangement as per drawing and specifications the fencing will be painted one coat of red oxide primer and then two coats of bus green synthetic enamel paint. The rates should be inclusive of all materials required for proper completion of above work (length of each fencing approx. 11 Meters)
Construction of plinth at various 11/0.4 KV Sub-station suitable for 1000KVA Distribution Transformer having size 5’x 5’ x 5’ out which 2’ below the ground. Work will include digging of foundation 2’ deep & brick work with Ist class bricks having cement and sand mortar of ratio 1:6 on all the walls, each of 9” thickness. The area inside the wall shall be duly filled by mud up to the height of appropriate level from ground level and shall be duly watered & rammed. Above the filling C.C. of ration 1:6:12 (Cement sand and brick ballast) giving 4” layer shall be provided. Above C.C. layer RCC layer having 4” thickness and with ratio 1:2:4 of cement sand and stone ballast shall be provided Re-enforcement shall be provided by providing net of (8 Nos. + 8 Nos.) M.S. rods of size 10 mm dia and each of 5’ length in the middle of the top of C.C. layer. The plinth shall be plastered with 12mm thick plaster in ratio 1:4 at all sides. This work will include cost of labour, T&P and all material required for construction of plinth which shall be provided by the contractor as per RESSPO Norms.
Neutral & body earthing of 1000KVA Distribution Transformer installed at various 33/11 kV Sub-stations by digging of pit upto water level depth and then inserting 1-¼” dia GI pipe of ‘A’ grade, conforming to the requirement of IS specification and then connecting the top of the inserted pipe and transformer body through GI strip of size 40x6 mm with the help of nut and bolt or through gas welding, as per direction of supervising engineer. It includes the cost of all material labour, T&P, carrier etc. required for proper completion of work. The aforesaid work shall be carried out as per RESSPO norms.
M/s Lucky Enterprises (BID ID -5576530)
stage.html
html • 0.01 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .