| 3 | L3₹5.4 L+₹41,230.32 (8.30%)Rejected-AOC 334 SCHOOL DANGA BANKURA BANKURA WEST BENGAL 722101 | BANKURA | BANKURA | WEST BENGAL | 722101 | L3 | Rejected-AOC REJECTED DUE TO NOT SELECTED AS L1 |
Tender Value
Refer Docs
EMD Value
₹10,000
Closing Date
25 Aug 2025, 12:00 pmClosed
Assistant Engineer,(Electrical Sub-Division-III)
O/O Assistant Engineer, Electrical Sub Division No. III (H.D), Milanpally RHE Campus, Siliguri
Replacement and renovation work of compound illumination system at Maheshmati RHE, Malda attached to Electrical Subdivision No-III, Housing Directorate.
2025_HSD_890904_1
WBHD/AE/ESD-III/eNIQ-55/25-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
7 days
Maheshmati, Malda
Please refer Tender documents.
3 documents required · 3 mandatory
₹10,000
18 Sept 2025
13 Aug 2025
27 Aug 2025
13 Aug 2025
25 Aug 2025
14 Aug 2025
Amount
Dismantling steel tubular/Rail/Strut embedded in CC foundation incl. excavation, filling of holes, restoring surface, loading at site and delivering, unloading, sorting, stacking properly at any place as per direction upto a lead of 1.6 km
Supplying and fixing 2 Way MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment. along with Supplying and fixing 240V 32A DP MCB (Make: Legrand/Schneider/Siemens/ABB/L&T) of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection
Supply & Delivery of 9 Mtr Steel Tubular Pole (Calcutta Poles/Jindal /Bansal/Transrail) as per specification Type 410 SP - 33 as overall length 9 mtr weight 164 KG with fixing the base plate as per direction of EIC incl Supply of base plate,CI cap with Pole having with 40 mm. dia 1.5 mtr. long detachable type G.I. Single arm bracket, suitable for pole head. The arm bracket shall be properly welded with 15 mm. thick stifner plate of pole sleeve for strengthening incl. properly fixing arrangement with the pole by bolts.
Fixing only outdoor / street light type fluorescent light fitting or MV light fitting complete with all accessories to be fixed /projected from the wall of the building incl. making holes/providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe (ISI-Medium) quality 1.5 mts. average length having suitable bend S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall incl. painting etc.
Erection of Single Steel tubular pole of length as given below with/without sole plate & Cap etc. in CC foundation (Proportion and dimension indicated below), having 600x600x150 mm thick CC (4:2:1) base block below sole plate/pole with hard jhama metal including CC (6:3:1) muffing 0.30 mts. dia and 0.30 mts. above ground level including 3 mm thick neat cemented finish and GI earth bolt after making drilled holes etc. on pole & carriage of pole upto 1.6 Km from Store to work-site including filling up the excavated earth pit with shifted soil and ramming properly Upto 9.0 mtr.
providing CC (6:3:1) base block (around the pole) dimension 0.60x0.60x0.76 mt. above ground level, neatly cemented finish (3 mm thick), at the base pole (in lieu of CC muffing) incl. drilled hole in pole suitable for alkathene/polythene pipe entry, for street light wiring, without Loop Box( 10 for exiting damage)
Painting of Steel Tubular Pole of lengths and no. of coats of paint, as given below with ready mixed paint/primer of approved make, and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint Upto 9.0 mtr. long pole One coat of red lead/Zinc chromate priming. 1st coat of synthetic enamel paint over the primer. 2nd coat of synthetic enamel paint over the 1st coat.
Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint.
Supply and Delivery of 45 Watt (Efficacy not less than 110 LPW with IP 66 protection, 10 KV SPD included) street light fitting in place of the existing fitting including taking down the defunt street light. (Make: Crompton CRP-409-45-57-SL_GL-NSG or its equivalent of Philips/Wipro/Jaquar) with NABL accredited lab with valid test certificate.
Supply and Delivery of 70 Watt (Efficacy not less than 110 LPW with IP 66 protection, 10 KV SPD included) street light fitting in place of the existing fitting including taking down the defunt street light. (Make: Crompton CRP-409-70-57-SL_GL-NSG or its equivalent of Philips/Wipro/Jaquar/Magik) with NABL accredited lab with valid test certificate. (42 for exiting pole)
Supply and Delivery of 120 Watt (Efficacy not less than 110 LPW with IP 66 protection, 10 KV SPD included) street light fitting in place of the existing fitting including taking down the defunt street light. (Make: Crompton CRP-411-120-57-SL_GL-NSG or its equivalent of Philips/Wipro/Jaquar/Magik) with NABL accredited lab with valid test certificate. ( from building)
Fixing only outdoor light Fitting by providing labour of different rated LED street light fitting as per the direction EIC.
Supply of 2 core 10 sqmm of 1.1 KV grade alluminium XLPE, PVC/ armoured LT cable ( Make : Havells/ Polycab/ KEI/ Finolex/RR )
Laying of 2 core 10 sqmm cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish at an average depth of 75 mm in floor/pavement/wall etc.
Laying of one No. 2 core 10 sqmm cable in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables of 2 core 10 sqmm cable.
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials :2 core 10 sqmm cable.
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required 3 x 22/0.3 (1.5 sqmm).( Loop Box to Fitting)
Supplying and Laying 19mm heavy gauge Polythene Pipe. ( Loop Box to Fitting)
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:By ISI-Medium GI pipe
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required 32 mm dia
Hiring charges for mobile folding ladder at different sites for the above compound light work including transporation charges and providing 2 nos of unskilled labour for proper handing of the ladder and carring it
Supply & Fixing of 240V, 40 W LED decorative post-top luminarie complete with all accessories and equipped with IP65 Protection (Make- Crompton, LPTO - 40 - CDL - M or equivalent model of Philipsj/wipro) on existing MS Pipe/Mini Pole as per direction of E.I.C
Supply & Fixing of 240V, 150 W Flood LED out door type light fittings complete with all accessories and equipped with IP66 Protection (Make:- Crompton TFS- 504 - 150 - 57 - 60 D - HL2 - GL NBK or equivalent model of Philips/Wipro) on existing MS Pipe/Mini Pole as per direction of E.I.C (For existing Ground Light)
Add. G.S.T.@ 18% (on Total from item no 1 to 25) to be calculated by bidder
Add. LWC.@ 1% to be calculated (on total from item no 1 to 25 + GST@18%) by bidder
SARKAR ENTERPRISE (BID ID -6857638)
Swarnendu Sarkar (BID ID -6854895)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .