Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹6.8 LAccepted-AOC | 1 | Accepted-AOC L1 | |
| 2 | 2₹7.0 L+₹13,960 (2.04%)Rejected-Finance | 2 | Rejected-Finance L2 | |
| 3 | 3₹7.3 L+₹48,686 (7.13%)Rejected-Finance UC I USHA PARK HARI NAGAR NEW DELHI 64 | NEW DELHI | DELHI | 110001 | 3 | Rejected-Finance L3 | |
| 4 | 4₹7.5 L+₹67,290 (9.85%)Rejected-Finance 5A 24 ANSARI ROAD DARYA GANJ NEW DELHI 110002 | CENTRAL | DELHI | 110002 | 4 | Rejected-Finance L4 |
Tender Value
₹8.1 L
EMD Value
₹16,500
Closing Date
30 Sept 2021, 11:00 amClosed
EEE/RZ/NZ
EEE/RZ/NZ
Provision of Semi High Mast pole in Bhagya Laxmi Apartment Sector-9,Delhi Citizen Apartment Sector-13 and Hans Vihar Apartment in Sector-13 Extension Rohini in AC-13 under Rohini Zone
2021_NDMC_89250_1
EEE-III/RZ/NZ/TC/2021-22/5.1
Open Tender
Electrical Works
Item Rate
120 days
EEE/RZ/NZ
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
₹16,500
Yes
14 Jun 2022
23 Sept 2021
1 Oct 2021
23 Sept 2021
30 Sept 2021
23 Sept 2021
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.a) Upto 35 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. A) Upto 35 sq. mm
Laying & fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall/surface as required. A) Upto 35 sq. mm ( clamped with 1 mm thick saddle)
Supplying and fixing of light class G.I. pipe of 50 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required.
Supplying & laying of following size DWC HDPE pipe ISI marked alongwith all accessories like socket,bend,couplers etc.conforming to IS 14930 Part-II complete with fitting & cutting,jointing etc.direct in ground (75 cm.below ground level) i/c excavation & refilling the trench but excluding sand cushioning & protactive covering etc.complete as reqd. a) 63 mm dia.(OD 63 mm & ID 51 mm.minimum)
Supply of XLPE insulated and PVC Sheathed Al conductor armoured cable 1.1 KV grade conforming to IS-7098 as required. A) 2x16 sq.mm
SITC of 150W LED flood Light luminiare fitted with lense, made of pressure die cast aluminium housing & toughned glass cover i/c mounting bracket complete with the following specification as reqd. (a) Total system wattage <=170 watt (b) Total Lumens output >=12500 lumens (c) Luminaire Efficacy>=80 Lm/w (d) Power Factor>=0.90 (e) Colour Temperature 5500K-6500K (f) CRI>=70
Fabrication , Supplying,Installation,testing,Commissioning of 12 mts.high mast System with its accessories ,Mast shaft shall be in one section , hot dip galvanized (Single dip ) inside & out sides &suitable for wind velocity as per IS 875 part3 .There shall be in longitudinal seam weld per section and No circumfrential weld. It should also included accessories For High Mast head frame ,2 point suspension system with steel wire rope 5mm dia. (7/19construction) single drum winch ,galvanized lantern carriage arrangement suitable for 4 Nos. (1x400watt.) luminaries symmitrically And its control gears boxes and lighting finial ,the mast shall have manual raising and lowering operation with foundation bolts and Anchor plate and control panel housing suitable RCC shallow foundation withM20 grade concrete for the high mast considering The safe soil bearing capacity at site as 10T/sqm at 2mts. Depth with all material i/c 4Nos S.P MCB,63Amp.DPIsolator etc as reqd.
Supply and fabrication of pole protection system made up of 8SWG steel wire mesh of size25mmx75mm rectangular with 50mmx50mmx6mm MS angle iron for supporting the mesh and grounding the protection system in suitable quality of CC etc as reqd.
Kamal Electricals
SRI BALAJI ELECTRICALS
ACE ENGINEERS BUREAU
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .