XEN Jal Shakti PHE Mechanical Division Udhampur
MH MORH
Repair to 250 KVA electric transformer at pumping station Mansar.
2020_PHE_109265_1
ENIT NO. 80 OF 2020-21
Open Tender
Repair and Maintenance Works
Item Rate
12 days
XEN Jal Shakti PHE Mechanical division Udhampur
Repair to 250 KVA electric transformer at pumping station Mansar.
8 documents required · 8 mandatory
₹200
Yes
xen Jal Shakti PHE Mechanical Division Udhampur
₹1,480
Yes
5 Jan 2021
16 Nov 2020
28 Nov 2020
16 Nov 2020
27 Nov 2020
17 Nov 2020
Amount
The job includes repairs to 250 KVA electric transformer of pumping station Mansar by way of disconnecting the cable connections, drop out fuse set from HT side, demounting from platform with the help of crane and its carriage to road. Loading, transportation on departmental vehicle to the workshop. Extracting out transformer assembly out of oil tank with the help of chain pulley block and dismantling the same. Opening of transformer top cover, draining of transformer oil and opening of side channels and lamination by using skilled labour and special tools and tackles. Draining the transformer oil followed by cleaning the oil tank from inside to remove sludge with the help of scrubbers and chemicals. Taking out all the damaged coils. Replacement of damaged aluminum LT and HT coils. Refitting of new coils to the cores after replacement of damaged coils. Assembling of transformer cores into the transformer tank. Refitting of side channel laminations after repair to oil tank to make it leak proof. Refilling of transformer oil after dehydration and topping up of new transformer oil with 100 liters. Heating of transformer core in oven. Replacement of LT bush with rods and HT bush with rods. Providing and fitting of gasket, nuts, bolts and terminal set. Shifting back repaired transformer to the pumping station and mounting it on the platform with the help of crane and manual labour. Connecting the cable connections and drop out connections, testing and commissioning of transformer on full load at site. The job also includes the cost of skill labour, hire charges, charges for special tools and tackles as well as material charges, charges of crane and manual labour for shifting to and fro and loading / unloading charges. Complete job.
M/S RAGHUNATH MECHANICAL AND ELECTRICAL ENGINEERING WORKS
NATIONAL ELECTRO-MECH COMPANY
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .