Online continuous fixed type Hydrogen gas leak detector | Sensor type- Catalytic Bead sensor, Measuring Range- 0 to 100 percent LEL of Hydrogen Gas. Response Time - T90 less than 30sec or T50/T60 less than 15secAccuracy- plus/minus 3 percent LEL(or better) from 0 to 50 percent LEL plus/minus 5 percent LEL(or better) from 51 to 100 percent LEL. Operating Temperature- 0 to 55 degC. Relative Humidity- 0 to 95percent, non-condensing. Sensor Housing- Stainless Steel SS 316. Instrument Housing- Aluminium or Stainless Steel SS316. Transmitter- Explosion proof Transmitter. Transmitter should be properly configuredand must be fully compatible with detector sensor. Display- Integral LED/LCD display showing Gas concentration value Power Supply- 24V DC Output- 4-20 mA with local display and relay o/p for fault/alarm detection(minimum 2 relay o/p). Separate local indication for alarm, faulty and healthy conditions. Protection Class- IP66/NEMA 4X or equivalent or better Communication- RS485/HART Setting- Facility for local Calibration and Configuration should be there directly in the supplied Hydrogen Gas Leak Detector system without using any other external device. Calibration and Configuration of the Device should be Non-Intrusive. Certification- ATEX, IECEx Approval for Hazardous area Mounting- Mounting bracket to be provided Calibration - Calibration facility should be provided. Also as per attached document Annexure-II, and QR. |