Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.6 LAdmitted-Finance 14 BEPIN BEHARI GANGUALY STREET KOLKATA 700 012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | L1 | Admitted-Finance | |
| 2 | L2₹28.0 L+₹44,370 (1.61%)Admitted-Finance MOSAT HARIPUR RD VILL P O HARIPUR DIST HOOGHLY PIN 712701 | HARIPUR | HOOGHLY | WEST BENGAL | 712701 | L2 | Admitted-Finance | |
| 3 | L3₹28.7 L+₹1.1 L (3.99%)Admitted-Finance 90 E BECHARAM CHATTERJEE ROAD KOLKATA 700034 | KOLKATA | KOLKATA | WEST BENGAL | 700034 | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | ASSOCIATED ELECTRICAL CONST CO. 1963 PVT.LTD L1 | SIMPSON AND FERRIS PVT LTD L3 | GHANASHYAM ELECTRIC STORES L2 |
|---|---|---|---|---|---|---|
| 1.00 | Charges for dismantling of damaged Detectors and Panel, HMI,Damaged Battery, MCP,Hooter etc by the CO's own manpower and Tools & tackles and submit the materials at sectional store | 1 | Job | 5,500 ₹5,500 | 5,000 ₹5,000 Lowest | 10,000 ₹10,000 |
| 2.00 | Charges for dismantling of damaged Detectors andSupply installation Testing & Commisioning of EN -54 standard VDS Approved Addressable Multi sensor Detector (optical smoke as well as heat ) with inbulit / additional isolator and integral LED status indicator with 360 degree viewing angle Detector shall commumcate 3 danger levels for differentiated alarm activation and high tolerance to dust dirt temperature fluctuation and air currents Detector should have unquie address for communication and assigned through panel along with Mounting Base as required with the protection category of IP40 (Approved Make: Siemens-cerberous pro) At existing System | 400 | Nos. | 4,375 ₹17,50,000 Lowest | 4,620 ₹18,48,000 | 4,450 ₹17,80,000 |
| 3.00 | Charges for dismantling of damaged Detectors andSupply installation Testing & Commisioning of EN -54 standard VDS Approved Addressable Multi sensor Detector (optical smoke as well as heat ) with inbulit / additional isolator and integral LED status indicator with 360 degree viewing angle Detector shall commumcate 3 danger levels for differentiated alarm activation and high tolerance to dust dirt temperature fluctuation and air currents Detector should have unquie address for communication and assigned through panel along with Mounting Base as required with the protection category of IP40 (Approved Make:Honeywell- Essar IQ8/Honeywell- Morley ) At existing System | 80 | Nos | 3,650 ₹2,92,000 | 3,590 ₹2,87,200 | 3,525 ₹2,82,000 Lowest |
| 4.00 | Supply, Installation, Testing & Commissioning of Intelligent Addressable EN Standards & VDS Approved Manual Call Point with base and Necessary accessories for fitting, J.B etc. (Approved Make: Siemens Cerberus Pro) At existing System
. | 10 | Nos | 7,010 ₹70,100 | 7,100 ₹71,000 | 7,000 ₹70,000 Lowest |
| 5.00 | Supply, Installation, Testing & Commissioning of Intelligent Addressable EN Standards & VDS Approved Manual Call Point with base and Necessary accessories for fitting, J.B etc. (Approved Make: Honeywell- Essar IQ8/Honeywell- Morley ) At existing System | 6 | Nos. | 4,620 ₹27,720 | 4,460 ₹26,760 Lowest | 4,750 ₹28,500 |
| 6.00 | Supply, Installation, Testing & Commissioning of EN Standards & VDS Approved Loop Powered Sounder cum Strobe with base and necessary accessories for fitting, J.B etc. (Approved Make: Honeywell- Essar IQ8/Honeywell- Morley) At existing System | 5 | Nos. | 7,600 ₹38,000 | 6,800 ₹34,000 Lowest | 6,810 ₹34,050 |
| 7.00 | Supply, Installation, Testing & Commissioning of EN Standards & VDS Approved Loop Powered Sounder cum Strobe with base and necessary accessories for fitting, J.B etc. (Approved Make: Siemens Cerberus Pro) At existing System | 10 | Nos. | 14,400 ₹1,44,000 | 15,000 ₹1,50,000 | 14,200 ₹1,42,000 Lowest |
| 8.00 | Supply & Laying of 1.1KV grade 2 core 1.5 sq.mm cu cable including S & laying 19 mm PVC Rigid conduit Make: Precission (MMS) PVC insulated flexible FRLS Shielded copper Cable (Make. Finolex/ POLYCAB/ KEI) for replacement of damaged cable. | 200 | Mtrs. | 128 ₹25,600 | 110 ₹22,000 Lowest | 140 ₹28,000 |
| 9.00Supply, Installation,Testing & Commisioning of Microprocessor based addressable fully networkable fire alarm control panel ( VDS / LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel should have extra loop card slot for expansion of capcity twice. .(Approved Make : Cerberus Pro / Honeywell-Morley/Johnson Controls / Securiton) | ||||||
| 9.10 | The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software. | 1 | Nos. | 1,12,000 ₹1,12,000 | 1,10,000 ₹1,10,000 Lowest | 1,12,000 ₹1,12,000 |
Tender Value
₹27.6 L
EMD Value
₹55,286
Closing Date
23 Jun 2026, 1:00 pmClosed
EEI,KNHED, PW Dte
THE EXECUTIVE ENGINEER, P.W.D /KOLKATA NORTH HEALTH ELECTRICAL DIVISION
Rectification job of different make addressable type Fire Detection systems installed at different buildings of R.G. Kar Medical College and Hospital, Kolkata
2026_WBPWD_5014932_1
WBPWD/EE/KNHED/e-NIQ-11/26-27
Open Tender
FIRE FIGHTING ORG
Item Rate
90 days
Kolkata
Please refer Tender documents.
6 documents required · 6 mandatory
₹55,286
Office of the EE, KNHED,PW Dte
17 Jul 2026
3 Jun 2026
25 Jun 2026
3 Jun 2026
23 Jun 2026
10 Jun 2026
9 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Charges for dismantling of damaged Detectors and Panel, HMI,Damaged Battery, MCP,Hooter etc by the CO's own manpower and Tools & tackles and submit the materials at sectional store | 1 | Job | - | - |
| 2 | Charges for dismantling of damaged Detectors andSupply installation Testing & Commisioning of EN -54 standard VDS Approved Addressable Multi sensor Detector (optical smoke as well as heat ) with inbulit / additional isolator and integral LED status indicator with 360 degree viewing angle Detector shall commumcate 3 danger levels for differentiated alarm activation and high tolerance to dust dirt temperature fluctuation and air currents Detector should have unquie address for communication and assigned through panel along with Mounting Base as required with the protection category of IP40 (Approved Make: Siemens-cerberous pro) At existing System | 400 | Nos. | - | - |
| 3 | Charges for dismantling of damaged Detectors andSupply installation Testing & Commisioning of EN -54 standard VDS Approved Addressable Multi sensor Detector (optical smoke as well as heat ) with inbulit / additional isolator and integral LED status indicator with 360 degree viewing angle Detector shall commumcate 3 danger levels for differentiated alarm activation and high tolerance to dust dirt temperature fluctuation and air currents Detector should have unquie address for communication and assigned through panel along with Mounting Base as required with the protection category of IP40 (Approved Make:Honeywell- Essar IQ8/Honeywell- Morley ) At existing System | 80 | Nos | - | - |
| 4 | Supply, Installation, Testing & Commissioning of Intelligent Addressable EN Standards & VDS Approved Manual Call Point with base and Necessary accessories for fitting, J.B etc. (Approved Make: Siemens Cerberus Pro) At existing System
. | 10 | Nos | - | - |
| 5 | Supply, Installation, Testing & Commissioning of Intelligent Addressable EN Standards & VDS Approved Manual Call Point with base and Necessary accessories for fitting, J.B etc. (Approved Make: Honeywell- Essar IQ8/Honeywell- Morley ) At existing System | 6 | Nos. | - | - |
| 6 | Supply, Installation, Testing & Commissioning of EN Standards & VDS Approved Loop Powered Sounder cum Strobe with base and necessary accessories for fitting, J.B etc. (Approved Make: Honeywell- Essar IQ8/Honeywell- Morley) At existing System | 5 | Nos. | - | - |
| 7 | Supply, Installation, Testing & Commissioning of EN Standards & VDS Approved Loop Powered Sounder cum Strobe with base and necessary accessories for fitting, J.B etc. (Approved Make: Siemens Cerberus Pro) At existing System | 10 | Nos. | - | - |
| 8 | Supply & Laying of 1.1KV grade 2 core 1.5 sq.mm cu cable including S & laying 19 mm PVC Rigid conduit Make: Precission (MMS) PVC insulated flexible FRLS Shielded copper Cable (Make. Finolex/ POLYCAB/ KEI) for replacement of damaged cable. | 200 | Mtrs. | - | - |
| 9Supply, Installation,Testing & Commisioning of Microprocessor based addressable fully networkable fire alarm control panel ( VDS / LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel should have extra loop card slot for expansion of capcity twice. .(Approved Make : Cerberus Pro / Honeywell-Morley/Johnson Controls / Securiton) | |||||
| 9.1 | The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software. | 1 | Nos. | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
cancelled_1.pdf
pdf • 0.47 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.55 MB
2911.pdf
Tender Documents • 1.46 MB
suspension.pdf
Additional Documents • 2.91 MB
BOQ_5083369.xls
BOQ • 0.42 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .