| 1 | L1₹51.8 LAdmitted-Finance | -1.25% | ₹51.8 L | L1 | Admitted-Finance |
Tender Value
₹52.5 L
EMD Value
₹1.0 L
Closing Date
20 Jan 2026, 6:00 pmClosed
Executive Engineer
PWD Electrical Division Medical College Jaipur
Air Conditioning work in ICU (Room-202,203) at Trauma Centre SMS Hospital,Jaipur
2026_CEPWD_526345_3
EE_PWD_Medical_NIT_46_2025_26
Open Tender
Electrical Works
60 days
Trauma Centre SMS Hospital
Please refer tender documents
2 documents required · 2 mandatory
₹1,500
Through Egras Challan in Office ID 28560
₹1.0 L
Yes
In the Chamber of Executive Engineer
29 Jan 2026
9 Jan 2026
21 Jan 2026
9 Jan 2026
20 Jan 2026
9 Jan 2026
15 Jan 2026
Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
Single pole MCB (With B/C curve tripping Characteristics)
6 A to 32 A rating
Supply , Installation, Testing and Comissioning of site fabricated ducting made from GI sheet metal conforming to IS:277 with a zinc coating grade not less than 120 GSM (both side inclusive) & fabricated as per IS:655 and as per approved drawings & designs including the cost of hangers, supports, angle, expansion fasteners , closed cell neoprene gasket T&P etc. as required of following thickness. Test Certificate for Galavanizing with lot no. to be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supply , Installation, Testing and Comissioning of site fabricated ducting made from aluminium sheet conforming to IS:737, Grade 31000 fabricated as per IS:655 and as per approved drawings & designs including the cost of hangers, supports , angle , expansion fasteners , closed cell neoprene gasket T&P etc. as required of following thickness. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying, installing, testing and balancing of extruded Aluminium powder coated Air Diffuser and complete with Flush, 20mm flanges with PVC/neoprene gasket, anti – smudge frame and removable inner core to facilitate the adjustable of air control damper, square/round/ rectangular as required.including fixing with steel screws etc. complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supply Air Diffuser with Volume Control damper
Return Air Diffuser without Volume Control damper
Supply & fixing of external thermal closed-cell Nitrile rubber Insulation material FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified 'Class O' in Fire Propagation as per BS 476 Part 6 in form of sheet on duct including cost of adhesive (CPRX Compound) complete as required. All as per pre approved by Engineer in charge.
19mm thick for Outdoor Application with 26 SWG Aluminium Cladding
Supply, installation, testing and commissioning of following minimum capacity and external static pressure VRF/VRV ceiling mounted ductable type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain pan, drain pump, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± 10%, 50 Hz complete as required. The unit shall have automatic force shut down valve in case of fire on receiveing signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Low static ductable units (19 to 30 pascal external static pressure)
Supplying and installation of high-pressure grade required size OEM make copper connection Y or T Joints / refnet for liquid and suction line complete erected on wall/ceiling with supports/raceways, Nitrile rubber insulation, painting etc. with brazing and testing for leakages confirming the normal operation of the VRV / VRF air conditioning system. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Gas charging of VRF/VRV system with R410A refrigerant gas. Before gas charging system shall be flushed with high purity Nitrogen Gas to remove carbon content, dirt particles to make sure that there is no chance of mixing any impurity with Refrigerant Gas. Thereafter System shall be tested with Nitrogen Gas at 1.5 Times of working pressure of R410 Refrigerant Gas to ensure leakproof system. Whole system shall be Vacuumed up to 500-micron level which ensures the zero-moisture content level in piping to ensure better cooling efficiency and long life of the system. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Un Armoured
2 core x 1.5 Sq.mm
Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia
50 mm dia per running inch length
Dismentling of split air conditioner of any capacity/any type including existing indoor unit & outdoor unit , refrigerant piping , connecting cables , drain pipe etc. including shifting of dismentaled material to store complete as required
SITC of Interconnecting refrigerant copper pipe for split/Ductable/ Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. Piping between each set of indoor & outdoor units of different sizes as per OEM requirement & specifications including class 'O' Nitrile rubber sleeves, chase cutting, supports, making good the same with sand cement plaster etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Providing and making wall openings in existing stone / Brick masonary partition wall complete with all requited T & P , Scafolding and providing lintel of required size and strength, repairing ,plastering and cleaning the site debrises as required.
Providing and fixing double scaffolding system on the exterior side, upto five story made with 4" wooden member 1.5 m c/c horizontal and vertical direction joining with rassi, clamps, challies. The scaffolding system shall be stiffened with bracing, runner, connection of building if necessary with all essential safty features for the workmen etc complete as per direction of EI.The lavation area of the scaffolding shall be measured for payment. The payment will be made once irrespective of duration of scaffolding. Note : This item to be used for maintence work judicially
SITC of UL 10th edition / EN54 / VDS certified Addressable control (input/output) modules/ Relay Module for shutting down lifts, Hooters, AHU's, Acknoledgement of Sprinkler system with potential free contact monitoring Etc. as Required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Automatic Floating Sensitivity type Analog addressable Multi criteria (two optical/Smoke sensor to reduce false alarm) detector with mounting base & LED etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Addressable type fault isolator with base for isolating shorted, dewired and loose circuits between two successive fault, isolators with automatic resetting arrangement etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Addessable Manual Call point (MCP) with LED / FIRE Indication Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Addressable sounder with strobe light, Loop Powered / Direct powered from FACP with sound level 90 dB and programmable from the panel etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of Response Indicator for indicating the activation of the Remotely located Detector for Addressable type Detectors Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and drawing Fire Resistant flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
2 x 1.5 Sq.mm Armoured With Outer Sheath in Red Color
Providing and fixing of Aluminium housing body self contained Rechargeable LED Emergency Light with required content and Size Approx. 300 mm x 180 mm, confirming to IS:9583 :1981with Ni-Mh / Ni - Cd Battery, 3 Hrs Back Up, Constant Current Charger, Input Voltage 230 V , 50 Hz including fixing on wall, door, ceiling etc. with proper clamps, hangers, cleats, anchor fasteners etc. complete in all respects required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Single sided signage
Double sided signage
P & F of Fire retardent flexible canvass connection made of fibreglass weave having silver grey silicon rubber coating, of height 200 mm with sufficient fold to avoid transmission of vibration with GI frame ,Gasket Nut Bolts for air cooling Plants/AHU/FCU etc as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying, installing and balancing of extruded Aluminium powder coated fresh air inlet louvers with bird screen & volume control damper fixing with steel screws etc. complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level
1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
Plaster on new surface on wall in cement sand mortar 1:4 including racking of joints etc. complete fine finish :
20mm thick
Finishing wall with water proofing cement paint of approved brand and manufacture and or required shade to give an even shade including all scaffolding:
New work (Two or more coats applied @ 3.84 kg/10 sqm).
SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:-
(a)Thickness of CRCA sheet shall be 2.0 mm, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided
(b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.
[c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra )
(d)Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.
(e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.
(f)Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra )
(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.
(h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator with standard short circuit withstand capacity , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Electrolytic grade Aluminium bus bar 6010 grade
Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy as per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Three phase AMP + HZ + PF + KW + KVA + KVAR + KVARH+KWH+DUAL ENERGY+ ENERGY+THD-I, THD-V & RUN HRS
Providing & Fixing of BIS approved Current Transformer as per PWD specification for electrical Works ,ISI marked as per IS 2705-1992/ conforming to IEC 60044-1, with secondary terminal of CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Ring type tape wound CT
C T Class 1, Ratio upto 150/5, Burden 5 VA
Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 29 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Red/yellow/Green colour
Blue / white Colour
Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor as per PWD specification for electrical Works, ISI marked IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
4 pole Power contactors with following AC 1 Rating
Providing & Fixing of thermal over load relay with built in single phase protection and having at least 1NO & 1NC contacts, manual /auto reset facility including making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
14 to 23 Amp
Providing & Fixing of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
One day reserve (Analog type )
Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
1 x 4.0 sq.mm
Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, round / flat strip armouring, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
Supplying, installation, testing and commissioning of fire dampers, the blades and frame shall be min. 1.6 mm thick GI and factory fitted in a sleeve made out of 1.6 mm thick GI of min. 400 mm long, as & where required, of required sizes including control wiring. The damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal. CBRI tested and certified for 90 minute fire rating etc. complete as required and as per specifications. (Total assembly should be UL listed).
Fire Damper
Actuator
SITC of Digital thermostat with cooling & heating mode including necessary control wiring to maintain the inside design condition as required.
Supply, Installation, Testing & Commissioning of 40 KVA Online UPS (3/3ph) pure sinewave (40kw) with 60 Minutes Battery Backup: 40 KVA floor mounted with IP 20 PROTECTION INDEX,phase sequence correction, inbuilt isolation transformer Online Double conversion VFI SS 111 (voltage frequency independent) TECHNOLOGY UPS pure sinewave (40kw), Should work with 3Ph-3Ph ,operating temp. 0 to 40 degree without derating. NOISE 1M (<65 dBA at 100 %load ),switching technology with IGBT (rectifier & inverter both), manual & automatic bypass both inbuilt, New 5 inch touch screen LCD Display. Double Conversion Efficiency upto 95% without transformer loss. UPS eco mode efficiency 98%.i/p voltage range 415 +/-10% and output voltage 415 V during mains voltage variation not more than +/- 1% specified value,over loading 125-150% for 60 sec & 101-125% for 10 min. i/p frequency 46-54 HZ ,THDi <=3%,Input Power Factor Correction 0.99. Unity Output Power Factor. with battery 12V/130AH- (Qty:38 nos) with Battery racks & interconnecting cables,etc.
SITC of DOL starter panel suitable for various capacity Axial flow fan having/ AHU suitable rating MCCB/MCB, AC 3 duty Contactor, Realy with NO /NC aux contact, overload, short circuit, earth fault, single phase protection, Phase indication lamp with protection MCB, ON/OFF/ Trip indication lamp, Digital multifunction meter with suitable rating current transformer. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. Wiring for micro switch for start/stopping the fan when signal from fire alarm panel (in case of Fire condition only). starters shall be provided with suitable potential free contract for connections to the Building Automation System. The starter panel shall be placed near Axial flow fan, with all connection from fan terminal box to stareter panel complete in all respect making connection etc as per list of approved makes.
Providing and fixing the Magnehelic Gauge for checking the pressure having range between 0 to 20 pascles with SS boxes Breathing pipe.
Supply, installation, testing & commissioning of Non return dampers of heavy gauge GIG sheet Construction complete with frame & suitable for fixing on duct as per specifications. The NRD(Non return dampers) frame shall be of 18G GI sheet, GIC - Channel frame of 120mm width with 30mm flange and 20G GI sheet blades, all blades shall be connected through linkage for simultaneous opening & closing of blades.
SITC of factory assembled Ceiling suspended double skin Air Handling Unit having specifications as per A, B, C, D, E, F & G
(a) Mixing Box: Mixing box with manually operated fresh air and return air dampers in aluminium construction
(b) Pre filter section: Pre-Filter (EU-4) section complete with 50mm thick washable synthetic fibre filters. Velocity across the filters shall not exceed 500 FPM. Filters shall have efficiency not less than 90% down to 10 Microns (EU-4/MERV-8). Filter material shall be non combustible type.
(c) Fine Filter section: Fine filter section with 305 mm thick fine filetrs complete with fine filters. Velocity across fine filters shall not exceed 500FPM. Filters shall have efficiency not less than 99% down to 3 Microns (EU-7/MERV-13). Filter material shall be non-combustible type.
(d)Coil Section: Coil section with 6 row (3+3) deep chilled water cooling coil/ DX cooling coil of copper tube & copper header and aluminium fins construction having wall thickness of tubes not less than 0.5mm. Drain pan shall be made out of 18 gauge SS-304 duly insulated with 13mm thick closed cell elastomeric insulation with class 'O' fire retardant properties. Face velocity across cooling coil shall not exceed 500FPM. - Space Provision for coil to be provided. Drain Pan with drain arrangement to be provided for coil at this stage.
(e) Fan Section: Fan Section comprising of belt driven, DIDW Backward curved AMCA certified centrifugal fan with maximum air outlet velocity of 10m/s suitable for required cfm at 70 mm static pressure (Total static of the unit shall be verified by the OEM before the design & supply of the units). Fan & Motor should be mounted over Aluminium channel of suitable thickness and should be isolated from the unit's bottom panel.
(f) Motor: TEFC High efficiency IE-3 class motors suitably designed for VFD with pulley, belt, Guard
(g) The unit shall be fabricated with frame work hollow extruded aluminium profile with 0.80 mm preplasticised GSS on outside and 0.80mm 275gsm plain GSS on inside complete with 48 mm thick CFC free PUF insulation of minimum 40 kg/cum density sandwiched in between inner and outer skins., The AHU shall be with thermal break profile with internal coving section complete with inspection doors, marine light, limit switch and control wiring as required. AHUs shall have access for all parts. noise level shall not exceed 70 dB, necessary vibration Isolation arrangement like spring hanger etc. as required.
more than 2000 cfm to 4000 cfm
SITC of factory assembled Floor mounted double skin Air Handling Unit having specifications as per A, B, C, D, E, F & G
(a) Mixing Box: Mixing box with manually operated fresh air and return air dampers in aluminium construction
(b)Pre filter section: Pre-Filter (EU-4) section complete with 50mm thick washable synthetic fibre filters. Velocity across the filters shall not exceed 500 FPM. Filters shall have efficiency not less than 90% down to 10 Microns (EU-4/MERV-8). Filter material shall be non combustible type.
(c) Fine Filter section: Fine filter section with 305 mm thick fine filetrs complete with fine filters. Velocity across fine filters shall not exceed 500FPM. Filters shall have efficiency not less than 99% down to 3 Microns (EU-7/MERV-13). Filter material shall be non combustible type.
(d) Coil Section: Coil section with 6 row (3+3) deep chilled water cooling coil/ DX cooling coil of copper tube & copper header and aluminium fins construction having wall thickness of tubes not less than 0.5mm. Drain pan shall be made out of 18 gauge SS-304 duly insulated with 13mm thick closed cell elastomeric insulation with class 'O' fire retardant properties. Face velocity across cooling coil shall not exceed 500FPM. - Space Provision for coil to be provided. Drain Pan with drain arrangement to be provided for coil at this stage.
(e) Fan Section: Fan Section comprising of belt driven, DIDW Backward curved AMCA certified centrifugal fan with maximum air outlet velocity of 10m/s suitable for required cfm at 70 mm static pressure (Total static of the unit shall be verified by the OEM before the design & supply of the units). Fan & Motor should be mounted over Aluminium channel of suitable thickness and should be isolated from the unit's bottom panel by means of Spring isolators.
(f) Motor: TEFC High efficiency IE-3 class motors suitably designed for VFD with pulley, belt, Guard
(g)The unit shall be fabricated with frame work hollow extruded aluminium profile with 0.80 mm preplasticised GSS on outside and 0.80mm 275gsm plain GSS on inside complete with 48 mm thick CFC free PUF insulation of minimum 40 kg/cum density sandwiched in between inner and outer skins., The AHU shall be with thermal break profile with internal coving section complete with inspection doors, marine light, limit switch and control wiring as required. AHUs shall have access for all parts. Necessary vibration Isolation arrangement, noise level shall not exceed 70 dB
3000 cfm to 8000 cfm
SITC of circular type Inline fans for ventilation including motor, with forward curved Direct driven SISW fan, motor and drive suitable for 220 ± 10% volts, 1 phase, 50 Hz A.C supply, thermal overload protection, including making connections, ancillary structure to suspend it from beam/slab, vibration isolator etc. as required of following sizes. (Cost of canvass connection to be paid extra)
200 cfm to 500 cfm at 15 mm static
SITC of AMCA Certified (For Air and Sound Performance) tube axial flow fan in standard M.S. construction. Entire fan model & AMCA Seal shall appear in technical submittal of fan. All the fans are synthetic enameled painted/hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at inlet. The electric motor coupler shall be squirrel cage induction motor (IE-2 type) confirming to IS - 325 IP55 with class `H' insulation. Motor shall be of high temperature resistance "Class H Smoke Spill" 250° C for 2 hrs. Fan shall be EN 12101-3 Certified & CE/UL Listed for high temperature. Fan efficiency should not be less than 70 %, noise level should not be more than 80 db @ 3 m distance when measured in hemispherical reverberant room conditions for Normal mode Fans and noise level should not be more than 90 db @ 3 m distance when measured in hemispherical reverberant room conditions for Emergency mode Fans. Fan shall have all provision for start on emergency signal from fire alarm panel including ancillary structure to suspend it from beam/slab, vibration isolator etc. as required of following sizes. (cost of canvass connection to be paid extra)
5000 cfm to 15000 cfm with static 30 mm
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.68 MB
Tendernotice_2.pdf
PDF • 1.90 MB
BOQ_939045.xls
BOQ • 0.48 MB
Cover3.pdf
Tender Documents • 0.30 MB
Download all tender documents and submit your bid