400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS
CC/NT/W-GIS/DOM/A10/25/06459
Open
Power/Energy Projects/Products
Works
All over India
₹25,000
27 Nov 2025
20 May 2025
10 Sept 2025
20 May 2025
10 Sept 2025
20 May 2025
27 May 2025
Sl. BAY NUM. BAY NAME DEVICE ID SIGNAL DESCRIPTION DATA TYPE SCADA ID REMARK
1 BUS BUS BUS VOLTAGE R-Y PHASE AI KVRY
2 BUS BUS VOLTAGE Y-B PHASE AI KVYB
3 BUS BUS VOLTAGE B-R PHASE AI KVBR
4 BUS BUS FREQUENCY AI HZ
1 ABC LINE FEEDER LINE I (R-PHASE) AI IR
2 ABC LINE I (Y-PHASE) AI IY
3 ABC LINE I (B-PHASE) AI IB
4 ABC LINE MW AI MW
5 ABC LINE MVAR AI MX
6 ABC LINE V (R-Y PHASE) AI KVRY
7 ABC LINE V (Y-B PHASE) AI KVYB
8 ABC LINE V (B-R PHASE) AI KVBR
9 ABC LINE FREQUENCY AI HZ
10 ABC LINE MAIN-1 FAULT IMPEDANCE AI FLZ1
11 ABC LINE MAIN-1 FAULT DISTANCE AI FLD1
12 ABC LINE MAIN-1 FAULT PERCENTAGE AI FLP1
13 ABC LINE MAIN-2 FAULT IMPEDANCE AI FLZ2
14 ABC LINE MAIN-2 FAULT DISTANCE AI FLD2
15 ABC LINE MAIN-2 FAULT PERCENTAGE AI FLP2
1 ABC BUS REACTOR/ LINE REACTOR RE REACTOR I (R-PHASE) AI IR
2 ABC RE REACTOR I (Y-PHASE) AI IY
3 ABC RE REACTOR I (B-PHASE) AI IB
4 ABC RE REACTOR MVAR AI MX
5 ABC RE REACTOR V (R-Y PHASE) AI KVRY
6 ABC RE REACTOR V (Y-B PHASE) AI KVYB
7 ABC RE REACTOR V (B-R PHASE) AI KVBR
8 ABC RE FREQUENCY AI HZ
9 ABC RE WTI TEMP R PHASE AI WTI ONLY ONE SIGNAL IN PLACE OF THREE SIGNALS APPLICABLE INDIVIDUALLY FOR R/Y/B PHASES TO BE CONSIDERED FOR 3 PHASE LINE REACTOR/ BUS REACTOR
12 ABC RE OTI TEMP R PHASE AI OTI
15 ABC RE DGA MOISTURE VALUE - R PHASE AI MOIS
16 ABC RE DGA H2 VALUE - R PHASE AI DGH2
17 ABC RE DGA C2H2 VALUE - R PHASE AI C2H2
18 ABC RE DGA CO VALUE - R PHASE AI DGCO
19 ABC RE DGA CO2 VALUE - R PHASE AI DCO2
20 ABC RE DGA CH4 VALUE - R PHASE AI DCH4
21 ABC RE DGA C2H6 VALUE - R PHASE AI C2H6
22 ABC RE DGA C2H4 VALUE - R PHASE AI C2H4
23 ABC RE DGA N2 VALUE - R PHASE AI DGO2
1 ABC TIE/ BUS COUPLER / BUS SECTION/TBC TIE/ BC/ BS I (R-PHASE) AI IR
2 ABC TIE/ BC/ BS I (Y-PHASE) AI IY
3 ABC TIE/ BC/ BS I (B-PHASE) AI IB
1 ABC ICT XFMR_P I (R-PHASE) AI IR
2 ABC XFMR_P I (Y-PHASE) AI IY
3 ABC XFMR_P I (B-PHASE) AI IB
4 ABC XFMR_P MW AI MW
5 ABC XFMR_P MVAR AI MX
6 ABC XFMR_P V (R-Y PHASE) AI KVRY
7 ABC XFMR_P V (Y-B PHASE) AI KVYB
8 ABC XFMR_P V (B-R PHASE) AI KVBR
9 ABC XFMR_P FREQUENCY AI HZ
10 ABC XFMR_P HVWTI TEMP - R PHASE AI HVWT ONLY ONE SIGNAL IN PLACE OF THREE SIGNALS APPLICABLE INDIVIDUALLY FOR R/Y/B PHASES TO BE CONSIDERED IN CASE OF 3-PHASE ICT
11 ABC XFMR_S IVWTI TEMP - R PHASE AI IVWT
12 ABC XFMR_T LVWTI TEMP - R PHASE AI LVWT
19 ABC XFMR_P OTI TEMP R PHASE AI OTI
22 ABC XFMR_P TAP POSITION INDICATOR - R PHASE AI TPI
25 ABC XFMR_P DGA MOISTURE VALUE - R PHASE AI MOIS
26 ABC XFMR_P DGA H2 VALUE - R PHASE AI DGH2
27 ABC XFMR_P DGA C2H2 VALUE - R PHASE AI C2H2
28 ABC XFMR_P DGA CO VALUE - R PHASE AI DGCO
29 ABC XFMR_P DGA CO2 VALUE - R PHASE AI DCO2
30 ABC XFMR_P DGA CH4 VALUE - R PHASE AI DCH4
31 ABC XFMR_P DGA C2H6 VALUE - R PHASE AI C2H6
32 ABC XFMR_P DGA C2H4 VALUE - R PHASE AI C2H4
33 ABC XFMR_P DGA N2 VALUE AI DGO2
1 220VDC DCDB 220V_DCDB-1 220V DCDB -1 VOLTAGE AI
2 220VDC 220V_DCDB-1 220V BATTERY SET-1 CURRENT AI
3 220VDC 220V_DCDB-2 220V DCDB -2 VOLTAGE AI
4 220VDC 220V_DCDB-2 220V BATTERY SET-2 CURRENT AI
5 48 VDC 48V_DCDB-1 48V DCDB -1 VOLTAGE AI
6 48 VDC 48V_DCDB-1 48V BATTERY SET-1 CURRENT AI
7 48 VDC 48V_DCDB-2 48V DCDB -2 VOLTAGE AI
8 48 VDC 48V_DCDB-2 48V BATTERY SET-2 CURRENT AI
9 220VDC BCHRG BATCHRG220V-1 220V BATTERY CHARGER-1 CURRENT AI
10 220VDC BATCHRG220V-2 220V BATTERY CHARGER-2 CURRENT AI
11 48 VDC BATCHRG48V-1 48V BATTERY CHARGER-1 CURRENT AI
12 48 VDC BATCHRG48V-2 48V BATTERY CHARGER-2 CURRENT AI
13 415 V FP FIREPROTN FIRE FIGHTING PRESSURE MONITORING AI
14 415 V DPUMP DIESEL ENGINE BATTERY-1 VOLTAGE AI
15 415 V DPUMP DIESEL ENGINE BATTERY-2 VOLTAGE AI
19 415 V AIRCON G_KIOSK_1 765KV KIOSK-1 TEMP AI
20 415 V F_KIOSK_1 400KV KIOSK-1 TEMP AI
21 415 V TEMP_MON CONTROL ROOM TEMPRATURE AI
22 415 V TEMP_MON BATTERY ROOM TEMPRATURE AI
23 415 V TEMP_MON AMBIENT TEMPERATURE OUTDOOR AI
24 415 V TEMP_MON AMBIENT RELATIVE HUMIDITY OUTDOOR AI
25 415 V DG Set DGSET-1 VOLTAGE (R-Y PHASE) AI
26 415 V DGSET-1 VOLTAGE (Y-B PHASE) AI
27 415 V DGSET-1 VOLTAGE (B-R PHASE) AI
28 415 V DGSET-1 CURRENT (R-PHASE) AI
29 415 V DGSET-1 CURRENT (Y-PHASE) AI
30 415 V DGSET-1 CURRENT (B-PHASE) AI
31 415 V DGSET-1 DG SET BATTERY-1 VOLTAGE AI
32 415 V DGSET-1 DG SET BATTERY-2 VOLTAGE AI
33 415 V LTSUP MSB-1 VOLTAGE (R-Y PHASE) AI
34 415 V MSB-1 VOLTAGE (Y-B PHASE) AI
35 415 V MSB-1 VOLTAGE (B-R PHASE) AI
36 415 V MSB-1 CURRENT (R-PHASE) AI
37 415 V MSB-1 CURRENT (Y-PHASE) AI
38 415 V MSB-1 CURRENT (B-PHASE) AI
39 415 V MSB-2 VOLTAGE (R-Y PHASE) AI
40 415 V MSB-2 VOLTAGE (Y-B PHASE) AI
41 415 V MSB-2 VOLTAGE (B-R PHASE) AI
42 415 V MSB-2 CURRENT (R-PHASE) AI
43 415 V MSB-2 CURRENT (Y-PHASE) AI
44 415 V MSB-2 CURRENT (B-PHASE) AI
Sl.NO Device DEVICE ID SIGNAL DESCRIPTION DATA TYPE REMARKS SCADA ID
1 CB CB CB OPEN / CLOSE DPS STTS
2 CB CB R-PH OPEN / CLOSE DPS STTR
3 CB CB Y-PH OPEN / CLOSE DPS STTY
4 CB CB B-PH OPEN / CLOSE DPS STTB
5 CB CB OPEN / CLOSE COMMAND DPC DPC
6 CB CB CHECK SYNC BYPASS COMMAND SPC DLCC
7 CB CB MANUAL OPEN SPS MNOP
8 CB CB MANUAL CLOSE SPS MNCL
9 CB CB POLE DISCREPANCY OPERATED SPS PDIS
10 CB CB POLE DISCREPANCY WITH IN POLE OPERATED SPS PDIB
11 CB CB DC SUPPLY 1/2 FAIL SPS DC
12 CB CB AC SUPPLY FAIL SPS ACSP
13 CB CB SPRING DISCHARGE SPS SPRG
14 CB CB SF6 LOW ALARM SPS SF6L
15 CB CB TC1 Faulty SPS TC1F
16 CB CB TC2 Faulty SPS TC2F
17 CB CB IN LOCAL/REMOTE SPS CBLM
18 CB CB MCB TRIPPED ( Motor/Heating/Lighting) SPS MCBT
19 CB INTERLOCK ENABLED SPS INTL
20 CB LBB PROTECTION OPERATED SPS LBBO
21 CB OPERATION LOCKOUT SPS OPL
22 ISOLATOR Isolator ISOLATOR OPEN / CLOSE DPS STTS
23 Isolator ISOLATOR OPEN / CLOSE DPS STTS
24 Isolator INTERLOCK ENABLED SPS INTL
25 Isolator ISOLATOR OPEN / CLOSE COMMAND DPC STTS
26 Earth Switch Earth Switch EARTH SWITCH OPEN / CLOSE DPS STTS
27 Earth Switch INTERLOCK ENABLED SPS INTL
28 BCU BCU BCU IN LOCAL / REMOTE DPS BCUR
29 BCU BCU UNHEALTHY SPS BCUH
30 BCU BCU TIME SYNC ERROR SPS BCUC
31 Line A/R AUTO RECLOSE IN AUTO / NONAUTO DPS ARNA
32 A/R AUTO RECLOSE IN AUTO / NONAUTO COMMAND DPC ARNA
33 A/R Autoreclosure Block SPS
34 A/R AUTORECLOSE LOCKOUT SPS ARLO
35 A/R AUTORECLOSE OPERATED SPS AROP
36 A/R AUTORECLOSE UNSUCCESFUL SPS ARFM
37 A/R A/R LOCK OUT RELAY RESET SPC ARLO
38 Main-1 Distance MAIN-1 PROTECTION OPERATED SPS M1OP
39 Main-1 Distance MAIN-1 DISTANCE PROTECTION ZONE1 TRIP SPS M1Z1
40 Main-1 Distance MAIN-1 DISTANCE PROTECTION ZONE2 TRIP SPS M1Z2
41 Main-1 Distance MAIN-1 DISTANCE PROTECTION ZONE3 TRIP SPS M1Z3
42 Main-1 Distance MAIN-1 DISTANCE PROTECTION REVERSE ZONE TRIP SPS M1RP
43 Main-1 Distance MAIN-1 A/R BLOCK SPS M1AR
44 Main-1 Distance MAIN-1 CVT FUSE FAILURE SPS M1FU
45 Main-1 Distance MAIN-1 RELAY FAULTY SPS M1UH
46 Main-1 Distance MAIN-1 DEF OPERATED SPS M1DE
47 Main-1 Distance MAIN-1 SOTF OPERATED SPS M1SO
48 Main-1 Distance MAIN-1 CARRIER SEND CH-1 SPS CAR7
49 Main-1 Distance MAIN-1 CARRIER SEND CH-2 SPS CAR8
50 Main-1 Distance MAIN-1 CARRIED RECD CH-1 SPS CAR3
51 Main-1 Distance MAIN-1 CARRIED RECD CH-2 SPS CAR5
52 Main-1 Distance MAIN-1 CARRIER AIDED TRIP SPS CAT1
53 Main-1 Distance MAIN-1 CARRIER SWITCH IN OUT OF SERVICE SPS CAS1
54 Main-1 Distance DIRECT TRIP SEND CHANNEL 1 SPS TRS1
55 Main-1 Distance DIRECT RECEIVED CHANNEL 1 SPS TRP1
56 Main-1 Distance MAIN-1 PSB DETECTED SPS PSB1
57 Main-1 Distance MAIN-1 STUB PROTN OPERATED SPS STUB
58 Main-1 Distance MAIN-1 O/V STAGE-1 TRIP SPS OV-1
59 Main-1 Distance 89L OPERATED FOR STUB M1 SPS
60 Main-1 Distance MAIN-1 O/V STAGE-2 TRIP SPS OV-2
61 Main-1 Distance DIRECT TRIP SEND CHANNEL 2 SPS TRS2
62 Main-1 Distance DIRECT RECEIVED CHANNEL 2 SPS TRP2
63 Main-1 Distance CARRIER FAIL CH-1 SPS CAF1
64 Main-1 Distance DC SOURCE-1 FAIL SPS DC-1
65 Main-1 Distance DC SOURCE-2 FAIL SPS DC-2
66 Main-1 Distance CARRIER FAIL CH-2 SPS CAF2
67 Busbar Relay MAIN-1 BB PROTECTION OPTD SPS BB1P
68 Busbar Relay MAIN-2 BB PROTECTION OPTD SPS BB2P
69 Busbar Relay MAIN-1 BB PU UNIT FAULTY SPS B1UH
70 Busbar Relay MAIN-2 BB PU UNIT FAULTY SPS B2UH
71 Master Trip 86A TRIP RELAY OPERATED SPS 86AO
72 Master Trip 86B TRIP RELAY OPERATED SPS 86BO
73 Master Trip 86A TRIP RELAY FAULTY SPS 86AU
74 Master Trip 86B TRIP RELAY FAULTY SPS 86BU
75 Master Trip 86A TRIP RELAY RESET SPC 86AO
76 Master Trip 86B TRIP RELAY RESET SPC 86BO
77 Line Differential Relay MAIN-1 LINE DIFFERENTIAL PROTECTION OPERATED SPS
78 Line Differential Relay MAIN-2 LINE DIFFERENTIAL PROTECTION OPERATED SPS
79 Line Differential Relay MAIN-1 DIFFERENTIAL PROTN TRIP R PH SPS
80 Line Differential Relay MAIN-1 DIFFERENTIAL PROTN TRIP Y PH SPS
81 Line Differential Relay MAIN-1 DIFFERENTIAL PROTN TRIP B PH SPS
82 Line Differential Relay MAIN-2 DIFFERENTIAL PROTN TRIP R PH SPS
83 Line Differential Relay MAIN-2 DIFFERENTIAL PROTN TRIP Y PH SPS
84 Line Differential Relay MAIN-2 DIFFERENTIAL PROTN TRIP B PH SPS
85 Line Differential Relay MAIN-1 DIFFERENTIATED WAVE BLOCK SPS
86 Line Differential Relay MAIN-1 DIFFERENTIATED HORMONICS BLOCK SPS
87 Line Differential Relay MAIN-2 DIFFERENTIATED WAVE BLOCK SPS
88 Line Differential Relay MAIN-2 DIFFERENTIATED HORMONICS BLOCK SPS
89 Line Differential Relay MAIN-1 DIFFERENTIATED RESTRAIN TRIP SPS
90 Line Differential Relay MAIN-2 DIFFERENTIATED RESTRAIN TRIP SPS
91 Line Differential Relay MAIN-1 DIFFERENTIATED UNRESTRAIN TRIP SPS
92 Line Differential Relay MAIN-2 DIFFERENTIATED UNRESTRAIN TRIP SPS
93 Line Differential Relay MAIN-1 BROKEN CONDUCTOR ALARM SPS
94 Line Differential Relay MAIN-2 BROKEN CONDUCTOR ALARM SPS
95 Reactor Reactor Differential DIFFERENTIAL RELAY OPTD. SPS REDI
96 Reactor Differential DIFFERENTIAL RELAY FAULTY SPS DIRU
97 Backup Impedance B/U IMPEDANCE OPTD SPS BUIO
98 Backup Impedance B/U RELAY FAULTY SPS BURF
99 Backup Impedance SELECTED VT FUSE FAIL ALARM SPS VTFU
100 REF REF OPTD SPS RERE
101 REF REF RELAY FAULTY SPS RERE
102 ? DC SOURCE-1 FAIL SPS DC-1
103 ? DC SOURCE-2 FAIL SPS DC-2
104 ? Oil level low alarm R phase SPS 3 PHASE STATUS IS REQUIRED IF LINE REACTOR/ BUS REACTOR IS 3 PHASE REOL
105 Buchholz BUCHOLTZ ALARM_R PHASE SPS BUCA
106 Buchholz BUCHOLTZ TRIP_R PHASE SPS BUCT
107 ?? SHUT_OFF_VALVE TRIP R PHASE SPS VLVT
108 WTI WTI ALARM_R PHASE SPS WTIA
109 WTI WTI_TRIP_R PHASE SPS WTIT
110 OTI OTI_ALARM_R_PHASE SPS OTIA
111 OTI OTI_TRIP_R_PHASE SPS OTIT
112 PRV PRV_TRIP_1_R_PHASE SPS REPR
113 PRV PRV_TRIP_2_R_PHASE SPS PRV2
114 Fire Protection FIRE PROTN OPTD R PHASE SPS FRRR
115 Fire Protection DELUGE VALVE ON - R PHASE SPS DVRR
116 Fire Protection COMMAND FOR DELUGE VALVE SPC DVTR
117 Spare selection SPARE REACTOR SELECT FOR R PHASE SPS SPRE
118 TEED Protection TEED PROTECTION OPTD SPS
119 TEED Protection TEED RELAY FAULTY SPS
120 CSD CONTROL SWITCH DEVICE BYPASSED SPS BYSW
121 CSD CONTROL SWITCH DEVICE TROUBLE SPS
122 CSD BYPASS CMD FOR CNTRL SWITCH DEVICE SPC BYSW
123 Busbar Relay MAIN-1 BB PROTECTION OPTD SPS BB1P
124 Busbar Relay MAIN-2 BB PROTECTION OPTD SPS BB2P
125 Busbar Relay MAIN-1 BB PU UNIT FAULTY SPS B1UH
126 Busbar Relay MAIN-2 BB PU UNIT FAULTY SPS B2UH
127 Master Trip 86A TRIP RELAY OPERATED SPS 86AO
128 Master Trip 86B TRIP RELAY OPERATED SPS 86BO
129 Master Trip 86A TRIP RELAY FAULTY SPS 86AU
130 Master Trip 86B TRIP RELAY FAULTY SPS 86BU
131 Master Trip 86A TRIP RELAY RESET SPC 86AO
132 Master Trip 86B TRIP RELAY RESET SPC 86BO
133 NGR NGR BUCHHOLZ TRIP(NGR) SPS
134 NGR REACTOR PRV TRIP(NGR) SPS
135 NGR OTI TRIP(NGR) SPS
136 NGR OTI ALARM(NGR) SPS
137 NGR BUCHHOLZ ALARM(NGR) SPS
138 NGR LOW OIL LEVEL ALARM(NGR) SPS
139 ICT (Primary) Differential DIFFERENTIAL RELAY OPTD. SPS TFDI
140 Differential DIFF RELAY UNHEALTHY SPS DIRU
141 Overflux OVERFLUX ALARM SPS OFLA
142 Overflux OVERFLUX TRIP OPTD SPS OFLP
143 Backup O/C and E/F BACKUP O/C, E/F OPTD (HV) SPS BUOC
144 Backup O/C and E/F BACKUP O/C E/F RELAY UNHEALTHY SPS CFRL
145 Backup O/C and E/F SELECTED VT FUSE FAIL ALARM SPS VTFU
146 Backup O/C and E/F INTERTRIP OPTD. SPS TRPO
147 ? DC SOURCE-1 FAIL SPS DC-1
148 ? DC SOURCE-2 FAIL SPS DC-2
149 Busbar Relay MAIN-1 BB PROTECTION OPTD SPS BB1P
150 Busbar Relay MAIN-2 BB PROTECTION OPTD SPS BB2P
151 Busbar Relay MAIN-1 BB PU UNIT FAULTY SPS B1UH
152 Busbar Relay MAIN-2 BB PU UNIT FAULTY SPS B2UH
153 REF REF OPTD R PHASE SPS 3 PHASE STATUS IS REQUIRED IF LINE REACTOR/ BUS REACTOR IS 3 PHASE TFRF
154 REF REF RELAY FAULTY SPS
155 Buchholz BUCHHOLZ ALARM R PHASE SPS BUCA
156 Buchholz BUCHHOLZ TRIP R PHASE SPS BUCT
157 OTI OTI ALARM R PHASE SPS OTIA
158 OTI OTI TRIP R PHASE SPS OTIT
159 WTI WTI ALARM (HV/IV/LV) R PHASE SPS WTIA
160 WTI WTI TRIP (HV/IV/LV) R PHASE SPS WTIT
161 PRV PRV-1 TRIP R-PHASE SPS TFPR
162 PRV PRV-2 TRIP R-PHASE SPS PRV2
163 OLTC OLTC OIL SURGE RELAY OPTD- R PHASE SPS OLTR
164 OLTC OLTC PRV TRIP OPTD- R PHASE SPS OLTP
165 OLTC OLTC OIL LEVEL ALARM R PHASE SPS
166 OLTC OIL FLOW VALVE TRIP- R PHASE SPS
167 OLTC OLTC DRIVE MOTOR FAULTY SPS
168 Cooling System FANS FAIL TO START BANK A - R PHASE SPS FANF
169 Cooling System FANS FAIL TO START BANK B - R PHASE SPS FANB
170 Cooling System PUMPS FAIL TO START BANK A - R PHASE SPS PMPF
171 Cooling System PUMPS FAIL TO START BANK B - R PHASE SPS PMPB
172 Cooling System OIL FLOW LOW ALARM BANK R PHASE SPS TFOL
173 ? COMMON THERMAL O/L ALARM R PHASE SPS OLAL
174 ? COMMON THERMAL O/L TRIP R PHASE SPS CTTP
175 ? STANDBY SUPLY FAIL R PHASE SPS SBSF
176 Fire Protection FIRE IN TRANSFORMER R PHASE SPS FRTR
177 Fire Protection DELUGE VALVE OPTD - R PHASE SPS DVTR
178 Fire Protection DELGUE VALVE COMMAND ICT SPC
179 Spare selection SPARE ICT SELECTED FOR R PHASE SPS
180 ? AVR OPERATION FAIL SPS
181 Neutral O/C NEUTRAL O/C PROTECTION OPTD SPS
182 Neutral O/C NEUTRAL O/C RELAY UNHEALTHY SPS
183 ? DIRECT WDG TEMP MONITORING TRIP R PHASE SPS
184 Backup Impedance BACKUP IMPEDANCE TRIP Z1 SPS BUZ1
185 Backup Impedance BACKUP IMPEDANCE TRIP Z2 SPS BUZ2
186 Backup Impedance BACKUP IMPEDANCE TRIP Z3 SPS BUZ3
187 Backup Impedance BACKUP IMPEDANCE TRIP Z4 SPS BUZ4
188 Backup Impedance BU IMPEDANCE RELAY FAULTY SPS
189 Backup Impedance VT FUSE FAIL ALARM SPS VTFU
190 Backup Impedance POWER SWING BLOCKING SPS
191 Busbar Relay MAIN-1 BB PROTECTION OPTD SPS BB1P
192 Busbar Relay MAIN-2 BB PROTECTION OPTD SPS BB2P
193 Busbar Relay MAIN-1 BB PU UNIT FAULTY SPS B1UH
194 Busbar Relay MAIN-2 BB PU UNIT FAULTY SPS B2UH
195 Master Trip 86A TRIP RELAY OPERATED SPS 86AO
196 Master Trip 86B TRIP RELAY OPERATED SPS 86BO
197 Master Trip 86A TRIP RELAY FAULTY SPS 86AU
198 Master Trip 86B TRIP RELAY FAULTY SPS 86BU
199 Master Trip 86A TRIP RELAY RESET SPC 86AO
200 Master Trip 86B TRIP RELAY RESET SPC 86BO
201 ICT (Secondary) Overflux LV - OVERFLUX ALARM SPS OFLA
202 Overflux LV - OVERFLUX OPTD SPS OFLP
203 Backup O/C and E/F LV - BACKUP O/C OPTD SPS BUOC
204 Backup O/C and E/F LV - BACKUP E/F OPTD SPS BUEF
205 Backup O/C and E/F SELECTED VT FUSE FAIL ALARM SPS VTFU
206 Master Trip 86A TRIP RELAY OPERATED SPS 86AO
207 Master Trip 86B TRIP RELAY OPERATED SPS 86BO
208 Master Trip 86A TRIP REALY UNHEALTHY SPS 86AU
209 Master Trip 86B TRIP REALY UNHEALTHY SPS 86BU
210 Busbar Relay MAIN-1 BB PROTECTION OPTD SPS BB1P
211 Busbar Relay MAIN-2 BB PROTECTION OPTD SPS BB2P
212 Busbar Relay MAIN-1 BB PU UNIT FAULTY SPS B1UH
213 Busbar Relay MAIN-2 BB PU UNIT FAULTY SPS B2UH
214 ? DC SOURCE-1 FAIL SPS DC-1
215 ? DC SOURCE-2 FAIL SPS DC-2
216 Bus Bar G_B1 M1 BB Z1 operated SPS BB17
217 G_B1 M2 BB Z1 operated SPS BB18
218 G_B1 M1 BB Z1 out of service SPS BB9
219 G_B1 M2 BB Z1 out of service SPS BB30
220 G_B1 M1 BB Z1 CT Trouble SPS M1TB
221 G_B1 M2 BB Z1 CT Trouble SPS M2TB
222 G_B1 Main-1 BB relay Healthy SPS BBH
223 G_B2 M1 BB Z2 operated SPS BBH
224 G_B2 M2 BB Z2 operated SPS
225 G_B2 M1 BB Z2 out of service SPS
226 G_B2 M2 BB Z2 out of service SPS
227 G_B2 M1 BB Z2 CT Trouble SPS
228 G_B2 M2 BB Z2 CT Trouble SPS
229 G_B2 Main-2 BB relay Healthy SPS
230 G_B1 MAIN-1 BB BLOCK/FIBERCOM ERROR SPS
231 G_B2 MAIN-2 BB BLOCK/FIBERCOM ERROR SPS
232 GIS Bay additional Signals GIS Bay additional Signals CB PUMP RUNTIME EXCEEDED SPS
233 GIS Bay additional Signals DE DRIVE STATUS ALARM SPS
234 GIS Bay additional Signals CRANK HANDLE INSERTED SPS
235 GIS Bay additional Signals PARTIAL DISCHARGE HIGH ALARM SPS
236 GIS Bay additional Signals LCC IN LOCAL MODE SPS
237 GIS Bay additional Signals LCC IN REMOTE MODE SPS
238 GIS Bay additional Signals BAY INTERLOCK BYPASS SELECTED SPS
239 GIS Bay additional Signals GAS LKG R/Y/B STG1 REFILL SPS SF61
240 GIS Bay additional Signals GAS LKG R/Y/B STG2 LOW SPS SF62
241 GIS Bay additional Signals GAS LKG R/Y/B ZONE TRIP SPS SF6T
242 GIS Bay additional Signals GAS LKG R/Y/B CB LOCKOUT/CB OPERATION LOCKOUT SPS SF6T
243 BCHRG & DCDB BATCHRG220V-1 220V BATTERY CHARGER -1 ON FLOAT MODE DPS
244 BATCHRG220V-1 220V BATTERY CHARGER -1 ON BOOST MODE DPS
245 BATCHRG220V-2 220V BATTERY CHARGER -2 ON FLOAT MODE DPS
246 BATCHRG220V-2 220V BATTERY CHARGER -2 ON BOOST MODE DPS
247 BATCHRG48V-1 48V BATTERY CHARGER -1 ON FLOAT MODE DPS
248 BATCHRG48V-1 48V BATTERY CHARGER -1 ON BOOST MODE DPS
249 BATCHRG48V-2 48V BATTERY CHARGER -2 ON FLOAT MODE DPS
250 BATCHRG48V-2 48V BATTERY CHARGER -2 ON BOOST MODE DPS
251 220V_DCDB-1 220V DCDB -1 EARTH FAULT SPS
252 220V_DCDB-2 220V DCDB -2 EARTH FAULT SPS
253 BATCHRG220V-1 220V BATTERY CHARGER-1 TROUBLE SPS
254 BATCHRG220V-2 220V BATTERY CHARGER-2 TROUBLE SPS
255 BATCHRG48V-1 48V BATTERY CHARGER-1 TROUBLE SPS
256 BATCHRG48V-2 48V BATTERY CHARGER-2 TROUBLE SPS
257 DGSET DGSET-1 DG SET BREAKER OPEN DPS
258 DGSET-1 DG SET BREAKER CLOSE DPS
259 DGSET-1 DG SET START COMMAND SPC
260 DGSET-1 DG SET STOP COMMAND SPC
261 DGSET-1 ALTERNATOR ON SPS
262 DGSET-1 CHARGER 1 ON SPS
263 DGSET-1 CHARGER 2 ON SPS
264 DGSET-1 ENGINE OVERHEATING SPS
265 DGSET-1 HIGH COOLING WATER TEMP. SPS
266 DGSET-1 LOW OIL PRESSURE TRIP SPS
267 DGSET-1 DG SET FAILED TO START IN 30 SEC SPS
268 DGSET-1 LACK OF FUEL SPS
269 DGSET-1 LOW LEVEL IN DAILY SERVICE FUEL TANK SPS
270 DGSET-1 HIGH SPEED DIESEL TANK LEVEL LOW SPS
271 DGSET-1 OVERSPEED TRIP SPS
272 DGSET-1 DG I/C PROTN OPTD(ALT FAULT,DIFF ETC) SPS
273 DGSET-1 CONTROL SUPPLY FAIL SPS
274 DGSET-1 DG PROTECTION OPERATED (O/C, E/F, DIFF.) SPS
275 DGSET-1 DG PROTECTION U/V OPERATED SPS
276 DGSET-1 AMF PANEL REMOTE SWITCH INDICATION SPS
277 DGSET-1 DG OVERLOAD SPS
278 DGSET-1 PHASE SEQUENCE NEGATIVE ALARM SPS
279 LTSUP ACDB-1 ACDB INCOMER-1 OPEN DPS
280 ACDB-1 ACDB INCOMER-1 CLOSE DPS
281 ACDB-1 ACDB INCOMER-1 O/C PROTN. RLY OPTD SPS
282 ACDB-1 ACDB INCOMER-1 E/F PROTN. RLY OPTD SPS
283 ACDB-1 ACDB INCOMER-1 U/V PROTN. RLY OPTD SPS
284 ACDB-BC ACDB BUS COUPLER OPEN DPS
285 ACDB-BC ACDB BUS COUPLER CLOSE DPS
286 ACDB-BC SUPERVISION OF CONTROL SUPPLY SPS
287 ACDB-2 ACDB INCOMER-2 OPEN DPS
288 ACDB-2 ACDB INCOMER-2 CLOSE DPS
289 ACDB-2 ACDB INCOMER-2 O/C PROTN. RLY OPTD SPS
290 ACDB-2 ACDB INCOMER-2 E/F PROTN. RLY OPTD SPS
291 ACDB-2 ACDB INCOMER-2 U/V PROTN. RLY OPTD SPS
292 MSB-1 MSB-1 CB OPEN DPS
293 MSB-1 MSB-1 CB CLOSE DPS
294 MSB-1 AUX. TRAFO-1 BUCHHOLZ ALARM SPS
295 MSB-1 AUX. TRAFO-1 WTI ALARM SPS
296 MSB-1 AUX. TRAFO-1 OTI ALARM SPS
297 MSB-1 AUX. TRAFO-1 BUCHHOLZ TRIP SPS
298 MSB-1 AUX. TRAFO-1 WTI TRIP SPS
299 MSB-1 AUX. TRAFO-1 OTI TRIP SPS
300 MSB-1 I/C-1 O/C PROTECTION RELAY TRIP SPS
301 MSB-1 I/C-1 E/F PROTECTION RELAY TRIP SPS
302 MSB-1 MSB BUS-1 U/V OPTD SPS
303 MSB-1 PHASE SEQUENCE NEGATIVE ALARM SPS
304 MSB_BC MSB BUS COUPLER BREAKER OPEN DPS
305 MSB_BC MSB BUS COUPLER BREAKER CLOSE DPS
306 MSB_BC SUPERVISION OF CONTROL SUPPLY SPS
307 MSB-2 MSB-2 CB OPEN DPS
308 MSB-2 MSB- 2 CB CLOSE DPS
309 MSB-2 AUX. TRAFO-2 BUCHHOLZ ALARM SPS
310 MSB-2 AUX. TRAFO- 2 WTI ALARM SPS
311 MSB-2 AUX. TRAFO-2 OTI ALARM SPS
312 MSB-2 AUX. TRAFO-2 BUCHHOLZ TRIP SPS
313 MSB-2 AUX. TRAFO-2 WTI TRIP SPS
314 MSB-2 AUX. TRAFO-2 OTI TRIP SPS
315 MSB-2 I/C-2 O/C PROTECTION RELAY TRIP SPS
316 MSB-2 I/C-2 E/F PROTECTION RELAY TRIP SPS
317 MSB-2 MSB BUS-2 U/V OPTD SPS
318 MSB-2 PHASE SEQUENCE NEGATIVE ALARM SPS
319 TERTIARY EARTH SWITCH OPEN DPS
320 TERTIARY EARTH SWITCH CLOSE DPS
321 TERTIARY CB OPEN DPS
322 TERTIARY CB CLOSE DPS
323 TERTIARY ISO OPEN DPS
324 TERTIARY ISO CLOSE DPS
325 TERTIARY CB INTERLOCK ENABLED SPS
326 TERTIARY ISO INTERLOCK ENABLED SPS
327 TERTIARY CB TRIPPED ON PROTN SPS
328 FP EPUMP ELECTRIC MOTOR FIRE WATER PUMP RUNNING SPS
329 EPUMP ELECTRIC MOTOR FIRE WATER PUMP FAILS TO START SPS
330 EPUMP ELECTRIC PUMP IN AUTO MODE SPS
331 EPUMP CONTROL SUPPLY FAIL SPS
332 EPUMP HVW ELECTRIC PUMP ACB ON DPS
333 EPUMP HVW ELECTRIC PUMP ACB OFF DPS
334 EPUMP EMER. START OF ELECTRIC MOTOR DRIVEN PUMP SPC
335 EPUMP EMER. STOP OF ELECTRIC MOTOR DRIVEN PUMP SPC
336 DPUMP DIESEL ENGINE FIRE WATER PUMP FAILS TO START SPS
337 DPUMP DIESEL ENGINE FIRE WATER PUMP RUNNING SPS
338 DPUMP DIESEL ENGINE PUMP IN AUTO MODE SPS
339 DPUMP DIESEL ENGINE BATTERY CHARGER-1 ON SPS
340 DPUMP DIESEL ENGINE BATTERY CHARGER-2 ON SPS
341 DPUMP DIESEL ENGINE FUEL LEVEL LOW SPS
342 DPUMP CONTROL SUPPLY FAIL SPS
343 DPUMP DIESEL PUMP OVER SPEED TRIP SPS
344 DPUMP DIESEL PUMP LOW OIL PRESSURE TRIP SPS
345 DPUMP DIESEL ENGINE HIGH TEMPERATURE ALARM SPS
346 DPUMP EMER. START OF DIESEL MOTOR DRIVEN PUMP SPC
347 DPUMP EMER. STOP OF DIESEL MOTOR DRIVEN PUMP SPC
348 SMOKE ALARM CONTROL ROOM ZONE-1 FIRE DETECTED SPS
349 SMOKE ALARM CONTROL ROOM ZONE-2 FIRE DETECTED SPS
350 SMOKE ALARM CONTROL ROOM ZONE-3 FIRE DETECTED SPS
351 SMOKE ALARM CONTROL ROOM ZONE-4 FIRE DETECTED SPS
352 SMOKE ALARM 765KV KIOSK-1 FIRE DETECTED SPS
353 SMOKE ALARM 400kV KIOSK-1 FIRE DETECTED SPS
354 FIREPROTN WATER STORAGE TANK-1 WATER LEVEL LOW SPS
355 FIREPROTN WATER STORAGE TANK-2 WATER LEVEL LOW SPS
356 FIREPROTN FIRE FIGHTING TANK HEADER PRESSURE LEVEL LOW SPS
357 FIREPROTN FIRE ANNAUNCIATION PANEL FAULTY SPS
358 FIREPROTN COMMON FIRE ALARM SPS
359 FIREPROTN CONTROL SUPPLY FAIL SPS
360 JPUMP-1 JOCKEY PUMP-1 RUNNING SPS
361 JPUMP-1 JOCKEY PUMP-1 FAILS TO START SPS
362 JPUMP-1 SUPERVISION OF CONTROL SUPPLY SPS
363 JPUMP-2 JOCKEY PUMP-2 RUNNING SPS
364 JPUMP-2 JOCKEY PUMP-2 FAILS TO START SPS
365 JPUMP-2 SUPERVISION OF CONTROL SUPPLY SPS
366 G_703_ICT-1 FIRE IN ICT/ REACTOR SPS
367 G_703_ICT-1 DELUGE SYSTEM OPERATING FOR ICT/REACTOR SPS
368 G_703_ICT-1 DELGUE VALVE ICT/REACTOR ON COMMAND SPC
369 SYSTEM AUX_SYSTEM SUBSTATION MAIN CONTROL ON NTAMC SPS
370 AUX_SYSTEM SUBSTATION MAIN CONTROL ON RTAMC SPS
371 AUX_SYSTEM SUBSTATION MAIN CONTROL ON BACK UP NTAMC SPS
372 AUX_SYSTEM SUBSTATION AUX CONTROL ON NTAMC SPS
373 AUX_SYSTEM SUBSTATION AUXCONTROL ON RTAMC SPS
374 AUX_SYSTEM SUBSTATION AUX CONTROL ON BACK UP NTAMC SPS
375 AUX_SYSTEM SUBSTATION COMMAND FOR MAIN CONTROL ON NTAMC SPC
376 AUX_SYSTEM SUBSTATION COMMAND FOR MAIN CONTROL ON RTAMC SPC
377 AUX_SYSTEM SUBSTATION COMMAND FOR MAIN CONTROL ON BACK UP NTAMC SPC
378 AUX_SYSTEM SUBSTATION COMMAND FOR AUX CONTROL ON NTAMC SPC
379 AUX_SYSTEM SUBSTATION COMMAND FOR AUXCONTROL ON RTAMC SPC
380 AUX_SYSTEM SUBSTATION COMMAND FOR AUX CONTROL ON BACK UP NTAMC SPC
381 COMMON PLCC PLCC EXCHANGE FAIL SPS
382 GPS TIME SYNCH. SIGNAL ABSENT SPS
383 AIRCON G_KIOSK_1 765KV KIOSK-1 HIGH TEMP ALARM SPS
384 F_KIOSK_1 400KV KIOSK-1 HIGH TEMP ALARM SPS
385 SAS GATEWAY GATEWAY-1 FAIL SPS
386 GATEWAY GATEWAY-2 FAIL SPS
387 LOCAL_HMI LOCAL HMI-1 FAIL SPS
388 LOCAL_HMI LOCAL HMI-2 FAIL SPS
400KV LINE with Non-Switched Reactor
S.No BAY NO RTU INPUT TYPE DATA S.No BAY NO BCU INPUTS TYPE DATA S.No BAY NO BCU OUTPUTS TYPE DATA
1 40X-52 CB COMPRESSOR / PUMP ON SPS HARD 1 40X-52 CB OPEN DPS HARD 1 40X-52 CB OPEN COMMAND DPC HARD
2 40X-52 CB AC SUPPLY FAIL SPS HARD 2 40X-52 CB CLOSE DPS HARD 2 40X-52 CB CLOSE COMMAND DPC HARD
3 40X-52 CB LOSS OF SF6 SPS HARD 3 40X-52 CB MANUAL OPEN SPS HARD 3 40X-89A ISOLATOR OPEN COMMAND DPC HARD
4 40X-52 CB TROUBLE ALARM SPS HARD 4 40X-52 CB MANUAL CLOSE SPS HARD 4 40X-89A ISOLATOR CLOSE COMMAND DPC HARD
5 40X MAIN-1/2 -POWERSWING BLCK DETECTED SPS HARD 5 40X-89A ISOLATOR OPEN DPS HARD 5 40X-89B ISOLATOR OPEN COMMAND DPC HARD
6 40X MAIN-1/2 STUB PROTECTION OPTD. SPS HARD 6 40X-89A ISOLATOR CLOSE DPS HARD 6 40X-89B ISOLATOR CLOSE COMMAND DPC HARD
7 40X DIRECT TRIP RECEIVED- CH.-1/2 SPS HARD 7 40X-89AE EARTH SWITCH OPEN DPS HARD 7 40X-89L ISOLATOR OPEN COMMAND DPC HARD
8 40X DIRECT TRIP SEND-CH-1/2 SPS HARD 8 40X-89AE EARTH SWITCH CLOSE DPS HARD 8 40X-89L ISOLATOR CLOSE COMMAND DPC HARD
9 40X MAIN-1 INTER TRIP RECEIVED SPS HARD 9 40X-89B ISOLATOR OPEN DPS HARD 9 40X-89R ISOLATOR OPEN COMMAND DPC HARD
10 40X MAIN-1 INTER TRIP SEND SPS HARD 10 40X-89B ISOLATOR CLOSE DPS HARD 10 40X-89R ISOLATOR CLOSE COMMAND DPC HARD
11 40X MAIN-2 INTER TRIP RECEIVED SPS HARD 11 40X-89BE EARTH SWITCH OPEN DPS HARD 11 40X-89NGR ISOLATOR OPEN COMMAND DPC HARD *
12 40X MAIN-2 INTER TRIP SEND SPS HARD 12 40X-89BE EARTH SWITCH CLOSE DPS HARD 12 40X-89NGR ISOLATOR CLOSE COMMAND DPC HARD *
13 40X OVERVOLTAGE STAGE-1 OPTD. SPS HARD 13 40X-89L ISOLATOR OPEN DPS HARD 13 40X A/R AUTO COMMAND DPC HARD
14 40X OVERVOLTAGE STAGE-2 OPTD. SPS HARD 14 40X-89L ISOLATOR CLOSE DPS HARD 14 40X A/R NON AUTO COMMAND DPC HARD
15 40X A/R UNSUCCESSFUL SPS HARD 15 40X-89LE EARTH SWITCH OPEN DPS HARD 15 40X CB CHECK SYNC. BYPASS COMMAND SPC SOFT
16 40X CARRIER FAIL CH-1/2 SPS HARD 16 40X-89LE EARTH SWITCH CLOSE DPS HARD
17 40X SPEECH CHANNEL FAIL SPS HARD 17 40X-89R ISOLATOR OPEN DPS HARD S.No BAY NO BCU ANALOGUE INPUTS TYPE DATA
18 40X DIFFERENTIAL PROTN OPTD. SPS HARD 18 40X-89R ISOLATOR CLOSE DPS HARD 1 40X REACTOR OTI-TEMP AI HARD
19 40X REF PROTECTION OPTD. SPS HARD 19 40X-89RE EARTH SWITCH OPEN DPS HARD 2 40X REACTOR WTI-TEMP AI HARD
20 40X BACK-UP IMPEDANCE PROTN OPTD SPS HARD 20 40X-89RE EARTH SWITCH CLOSE DPS HARD 3 40X I (R-PHASE) AI SOFT
21 40X BUCHHOLZ TRIP SPS HARD 21 40X-89NGR ISOLATOR OPEN DPS HARD ** 4 40X I (Y-PHASE) AI SOFT
22 40X REACTOR PRV TRIP SPS HARD 22 40X-89NGR ISOLATOR CLOSE DPS HARD ** 5 40X I B-PHASE) AI SOFT
23 40X OTI TRIP SPS HARD 23 40X A/R IN AUTO MODE DPS HARD 6 40X MVAR AI SOFT
24 40X WTI TRIP SPS HARD 24 40X A/R IN NON AUTO MODE DPS HARD 7 40X MW AI SOFT
25 40X OTI ALARM SPS HARD 25 40X-52 CB OPERATION LOCKOUT SPS HARD 8 40X V (B-R PHASE) AI SOFT
26 40X WTI ALARM SPS HARD 26 40X-52 CB POLE DISCREPANCY OPTD. SPS HARD 9 40X V (R-Y PHASE) AI SOFT
27 40X BUCHHOLZ ALARM SPS HARD 27 40X DC SOURCE-1 FAIL SPS HARD 10 40X V (Y-B PHASE) AI SOFT
28 40X LOW OIL LEVEL ALARM SPS HARD 28 40X DC SOURCE-2 FAIL SPS HARD 11 40X FREQUENCY AI SOFT
29 40X BUCHHOLZ TRIP(NGR) SPS HARD * 29 40X MAIN CB TC-1 FAULTY SPS HARD 12 40X Reactor I (R-PHASE) AI SOFT
30 40X REACTOR PRV TRIP(NGR) SPS HARD * 30 40X MAIN CB TC-2 FAULTY SPS HARD 13 40X Reactor I (Y-PHASE) AI SOFT
31 40X OTI TRIP(NGR) SPS HARD * 31 40X 86A TRIP RELAY OPTD. SPS HARD 14 40X Reactor I B-PHASE) AI SOFT
32 40X WTI TRIP(NGR) SPS HARD * 32 40X 86B TRIP RELAY OPTD. SPS HARD 15 40X Reactor MVAR AI SOFT
33 40X OTI ALARM(NGR) SPS HARD * 33 40X 86LO A/R LOCKOUT RELAY OPTD. SPS HARD 16 40X Reactor V (B-R PHASE) AI SOFT
34 40X WTI ALARM(NGR) SPS HARD * 34 40X Main-1 BB PROTN. OPTD. SPS HARD 17 40X Reactor V (R-Y PHASE) AI SOFT
35 40X BUCHHOLZ ALARM(NGR) SPS HARD * 35 40X Main-2 BB PROTN. OPTD. SPS HARD 18 40X Reactor V (Y-B PHASE) AI SOFT
36 40X LOW OIL LEVEL ALARM(NGR) SPS HARD * 36 40X MAIN CB LBB OPTD. SPS HARD
37 40X 86A TRIP RELAY UNHEALTHY SPS HARD 37 40X MAIN CB A/R OPTD. SPS HARD S.No BAY NO RTU OUTPUT TYPE DATA
38 40X 86B TRIP RELAY UNHEALTHY SPS HARD 38 40X CB A/R LOCKOUT SPS HARD 1 40X 86A TRIP RELAY RESET SPC HARD
39 40X MAIN-1/2 WEAK END INFEED OPTD. SPS HARD 39 40X L/R SWITCH IN REMOTE SPS HARD 2 40X 86B TRIP RELAY RESET SPC HARD
40 40X CB SPRING CHARGED/air/oil pr low SPS HARD 40 40X MAIN-1 DISTANCE PROTECTION OPTD. SPS HARD 3 40X 86LO A/R LOCKOUT RELAY RESET SPC HARD
41 40X CB DC SUPPLY 1/2 FAIL SPS HARD 41 40X MAIN-1 ZONE-1 TRIP SPS HARD 4 40X REACTOR GR-A TRIP RESET SPC HARD
42 40X BYPASS CMD FOR CNTRL SWITCH DEVICE SPS HARD 42 40X MAIN-1 CVT FUSE FAILURE SPS HARD 5 40X REACTOR GR-B TRIP RESET SPC HARD
43 40X MAIN-1 CARRIER SWITCH OUT SPS HARD 43 40X MAIN-1 UNHEALTHY SPS HARD
44 40X MAIN-2 CARRIER SWITCH OUT SPS HARD 44 40X MAIN-2 DISTANCE PROTECTION OPTD. SPS HARD
45 40X Reactor Gr-A Trip Relay Unhealthy SPS HARD 45 40X MAIN-2 ZONE-1 TRIP SPS HARD * Applicable for NGR Only
46 40X Reactor Gr-B Trip Relay Unhealthy SPS HARD 46 40X MAIN-2 CVT FUSE FAILURE SPS HARD
47 40XLA R-PH LA LEAKAGE CURRENT HIGH SPS HARD 47 40X MAIN-2 UNHEALTHY SPS HARD
48 40XLA Y-PH LA LEAKAGE CURRENT HIGH SPS HARD 48 40X MAIN-1/2 SOTF OPTD. SPS HARD
49 40XLA B-PH LA LEAKAGE CURRENT HIGH SPS HARD 49 40X-52 INTERLOCK ENABLED SPS SOFT
50 40XRLA R-PH REACTOR LA LEAKAGE CURRENT HIGH SPS HARD 50 40X-89A INTERLOCK ENABLED SPS SOFT
51 40XRLA Y-PH REACTOR LA LEAKAGE CURRENT HIGH SPS HARD 51 40X-89AE INTERLOCK ENABLED SPS SOFT
52 40XRLA B-PH REACTOR LA LEAKAGE CURRENT HIGH SPS HARD 52 40X-89 INTERLOCK ENABLED SPS SOFT
53 40X REACTOR COOLING SYSTEM TROUBLE ALARM SPS HARD 53 40X-89E INTERLOCK ENABLED SPS SOFT
54 40X CB R-Phase Close/Open SPS HARD 54 40X-89L INTERLOCK ENABLED SPS SOFT
55 40X CB Y-Phase Close/Open SPS HARD 55 40X-89LE INTERLOCK ENABLED SPS SOFT
56 40X CB B-Phase Close/Open SPS HARD 56 40X-89R INTERLOCK ENABLED SPS SOFT
57 40X-89RE INTERLOCK ENABLED SPS SOFT
58 40X-89NGR INTERLOCK ENABLED SPS SOFT
59 40X MFT Healthy SPS SOFT
60 40X MFT Healthy (Reactor) SPS SOFT
61 40X BAY IN MAINTENANCE MODE SPS SOFT
TYPICAL DATA LIST
IEC 60870-5-104 interoperability Profile for NTAMC Control centers
PROTOCOL SUMMARY
SL.No. Description Value Remark
1 ASDU Common Address 1
2 Common Address Size of ASDU 2 Byte
3 Information object Address Structure 3 Byte
4 Frame Max Length 255
5 MV Periodic Cycle Periodic cycle 15Sec and Spontaneous transmission on 1% change of Current value. For Frequency 0.02% (i.e.0.01 Hz)
6 Binary Time Stamp Size 7 Byte CP56 Time 2a
7 T0: Connection Time Out 30 Sec.
8 T1: APDU Time Out 15 Sec.
9 T2: Acknowledge Time Out 10 Sec.
10 T3: Test Frame Time Out 20 Sec.
11 K: Send Acknowledgement Frames (APDU) 12
12 W: Acknowledgement Received Frame (APDU) 8
13 Time Synchronisation NA Locally through IRIG-B or SNTP
14 Cause of Transmission 2 Byte
DIGTAL STATUS SETTINGS PROFILE
SL.No. Discription Duration
1 Debouncing Time 4ms
2 Filtering Delay 5ms
IEC 60870-5-104 Digital Signal type
SL.No. Discription Status Signal type CONTROL TYPE TIME OUT DURATION
1(a) Circuit Breaker (ON/OFF) DPS DPC SBO 3 Sec
1(b) Circuit breaker (Check synch bypass) SPS SPC SBO 3 Sec
2 Isolator DPS DPC SBO 20 Sec
3 Trip Relay & L/O Relays reset SPS SPC DIRECT OPERATE 10 Sec
4 Mode Selection (e.g. AR Auto/Non-auto, Protection Transfer etc.), Auxiliaries Motor, DG set & Diesel Engine, etc DPS DPC SBO 10 Sec
5 Control Switching Device (CSD) BYPASS COMMAND & Status SPS SPC SBO 10 Sec
6 Fire fighting tank Water level, Manual Open/Close status (One SPS for each level) SPS NA
7 Auto/Manual, Local/Remote DPS NA
The abnormal state for SPS signals shall be the HIGH state for alarms like ALARM/NORMAL, UNHEALTHY/HEALTHY, LOW/NORMAL, FAIL/NORMAL, SET/RESET.
IEC 60870-5-104 ASDU TYPE
SL.No. Description ASDU TYPE ID Remark
1 Analog Measured Valuse, Short Floating Point Value 13
2 SPS Single Point Information with Time Tag 30
3 DPS Double Point Information with Time Tag 31
5 SPC Single Command 45 SET/RESET
6 DPC Double Command 46 OPEN/CLOSE
IEC 60870-5-104 IOA ADDRESS STRUCTURE
SL.No. Description Starting Address Remark
1 Single Point Status (SPS) 1
2 Double Point Status (DPS) 5000
3 Measurement Value (MV) or Analog Value (AI) 10000
4 Double Point Control (DPC) 15000
5 Single Point Control (SPC) 17000
NTAMC TYPICAL SIGNALS FOR SWITCHGEAR (CB,ISOLATOR & EARTH SWITCH)
CIRCUIT BREAKER SIGNALS ISOLATOR SIGNALS
S.No SIGNAL NAME TYPE S.No SIGNAL NAME TYPE
1 CB OPENED / CLOSED DPS 1 ISOLATOR OPENED / CLOSED DPS
2 CB R-PH OPENED / CLOSED DPS 2 ISO INTERLOCK ENABLED SPS
3 CB Y-PH OPENED / CLOSED DPS 3 ISOLATOR OPEN / CLOSE COMMAND DPC
4 CB B-PH OPENED / CLOSED DPS NOTE- 1. S.No. 1-3 Signals to be mapped for each isolator
5 CB MANUAL OPEN SPS
6 CB MANUAL CLOSE SPS
7 POLE DISCREPANCY ALARM WITHIN PHASE. SPS
8 POLE DISCREPANCY ALARM ACROSS PHASE. SPS
9 CB DC SUPPLY 1/2 FAIL SPS
10 CB AC SUPPLY FAIL SPS EARTH SWITCH SIGNALS
11 CB SPRING DISCHARGE SPS S.No SIGNAL NAME TYPE
12 CB LOW AIR PRESSURE SPS 1 EARTH SWITCH OPENED / CLOSED DPS
13 CB LOW HYDRAULIC PRESSURE SPS 2 ES INTERLOCK ENABLED SPS
14 CB SF6 GAS PRESSURE FIRST STAGE LOW ALARM SPS NOTE- Signals to be mapped for each Earth Switch
15 CB SF6 LOCK OUT ALARM ( SECOND STAGE ) SPS
16 CB TC1 Faulty SPS
17 CB TC2 Faulty SPS
18 CB TROUBLE ALARM
19 CB MCB TRIPPED (Motor/Heating/Lighting) SPS
20 CB INTERLOCK ENABLED SPS
21 LBB PROTECTION OPERATED SPS
22 CB OPERATION LOCKOUT SPS
23 CB COMPRESSOR / PUMP ON SPS
24 CONTROL SWITCH DEVICE BYPASSED SPS
25 CONTROL SWITCH DEVICE TROUBLE SPS
26 BYPASS CMD FOR CNTRL SWITCH DEVICE SPC
27 CB OPEN / CLOSE COMMAND DPC
28 CB CHECK SYNC BYPASS COMMAND SPC
NOTE-S.No. 11,12,13-One no. signal to be taken as per CB Operating Mechanism Type as applicable
NOTE- If any other signal is required for remote operation as per site condition, it needs to be incorporated in final signal list.
NTAMC TYPICAL SIGNALS FOR LINE BAY AND COMMON SIGNALS FOR OTHER BAYS
LINE DISTANCE PROTECTION SIGNALS LINE DIFFERENTIAL PROTECTION SIGNALS MASTER TRIP SIGNALS
S.No SIGNAL NAME TYPE S.No SIGNAL NAME TYPE S.No SIGNAL NAME TYPE
1 MAIN-1 OPERATED SPS 1 LINE DIFF PROT OPERATED SPS 1 86A TRIP RELAY OPERATED SPS
2 MAIN-1 ZONE1 TRIP SPS 2 LINE DIFF PROT OPERATED R-PH SPS 2 86B TRIP RELAY OPERATED SPS
3 MAIN-1 ZONE2 TRIP SPS 3 LINE DIFF PROT OPERATED Y-PH SPS 3 86A TRIP RELAY FAULTY SPS
4 MAIN-1 ZONE3 TRIP SPS 4 LINE DIFF PROT OPERATED B-PH SPS 4 86B TRIP RELAY FAULTY SPS
5 MAIN-1 REVERSE ZONE TRIP SPS 5 LINE DIFF COMM FAIL LOCAL SPS 5 RESET 86A TRIP RELAY SPC
6 MAIN-1 PSB DETECTED SPS 6 LINE DIFF COMM FAIL REMOTE SPS 6 RESET 86B TRIP RELAY SPC
7 MAIN-1 CVT FUSE FAILURE SPS 7 LINE DIFF PROT BLOCKED SPS NOTE- Applicable for master trip relays (86A/86B) of any element ( Main, Tie, Switchable reactor bays,ICT etc)
8 MAIN-1 RELAY FAULTY SPS 8 DIFFERENTIATED RESTRAIN TRIP SPS
9 MAIN-1 DEF OPERATED SPS 9 DIFFERENTIATED UNRESTRAIN TRIP SPS
10 MAIN-1 SOTF OPERATED SPS 9 DIFFERENTIAL RELAY UNHEALTHY SPS
11 MAIN-1 CARRIER SEND CH-1 SPS NOTE- Signal are to be taken as per Relay availability(Main-1/2) BCU SIGNALS
12 MAIN-1 CARRIER SEND CH-2 SPS S.No SIGNAL NAME TYPE
13 MAIN-1 CARRIED RECD CH-1 SPS LINE ANALOG SIGNALS 1 BCU IN LOCAL / REMOTE DPS
14 MAIN-1 CARRIED RECD CH-2 SPS S.No SIGNAL NAME TYPE 2 BCU UNHEALTHY SPS
15 MAIN-1 O/V STAGE-1 TRIP SPS 1 I (R-PHASE) AI 3 BCU TIME SYNC ERROR SPS
16 MAIN-1 O/V STAGE-2 TRIP SPS 2 I (Y-PHASE) AI NOTE-Applicable for all BCUs in each bay
17 MAIN-1 STUB PROTN OPERATED SPS 3 I (B-PHASE) AI
18 MAIN-1 STUB_ENABLED SPS 4 MW AI PROCESS BUS SCHEME
19 MAIN-1 CARRIER AIDED TRIP SPS 5 MVAR AI S.No SIGNAL NAME TYPE
20 MAIN-1 BROKEN CONDUCTOR ALARM SPS 6 V (R-Y PHASE) AI 1 Switchgear Control Unit Unhealthy(SU) SPS
21 MAIN-1 A/R BLOCK SPS 7 V (Y-B PHASE) AI 2 Merging Unit Unhealthy(MU) SPS
22 MAIN-1 CARRIER SWITCH IN OUT SPS 8 V (B-R PHASE) AI 3 Switchgear Control Unit Communication Fail SPS
23 MAIN-1 WEAK END INFEED OPTD. SPS 9 FREQUENCY AI 4 Merging Unit Communication Fail SPS
24 MAIN-1 OVERVOLTAGE START SPS NOTE-Applicable for each line feeder 5 Transformer Control Unit Communication Fail SPS
25 DIRECT TRIP SEND CHANNEL 1 SPS NOTE- 1)S. No. 1-4 are Applicable for each elelment 2) S.No. 5 is applicable for each ICT.
26 DIRECT RECEIVED CHANNEL 1 SPS TRAVELLING WAVE FAULT LOCATOR SIGNALS
27 DIRECT TRIP SEND CHANNEL 2 SPS S.No SIGNAL NAME TYPE
28 DIRECT RECEIVED CHANNEL 2 SPS 1 TWFL Trouble Alarm SPS
29 CARRIER FAIL CH-1 SPS 2 TWFL Fault Distance AI
30 CARRIER FAIL CH-2 SPS NOTE- Signals Applicable as per availability of TWFL in line feeder TIE BAY, TBC & BUS COUPLER CURRENTS
31 DC SOURCE-1 FAIL SPS S.No SIGNAL NAME TYPE
32 DC SOURCE-2 FAIL SPS CT- SF6 GAS 1 I (R-PHASE) AI
NOTE- 1) S.No. 1 to 24 signal are to be taken for Main-2 Relay also 2) Sr No. 17 & 18 applicable as per bus bar scheme S.No SIGNAL NAME TYPE 2 I (Y-PHASE) AI
1 CT LOSS SF6 R PH SPS 3 I (B-PHASE) AI
2 CT LOSS SF6 Y PH SPS NOTE-Applicable for each tie bay, TBC and Bus Coupler
3 CT LOSS SF6 B PH SPS
AUTORECLOSURE SIGNALS 4 CT SF6 PR LOCKOUT SPS
S.No SIGNAL NAME TYPE NOTE-Applicable in case of SF6 CT GIS BAYS SIGNALS
1 A/R IN AUTO / NONAUTO MODE DPS S.No SIGNAL NAME TYPE
2 A/R IN BLOCK MODE SPS SPECIAL PROTECTION 1 PARTIAL DISCHARGE HIGH ALARM SPS
3 AUTORECLOSE LOCKOUT SPS S.No SIGNAL NAME TYPE 2 LCC IN LOCAL MODE SPS
4 AUTORECLOSE OPERATED SPS 1 df/dt OPERATION SPS 3 LCC IN REMOTE MODE SPS
5 AUTORECLOSE UNSUCCESFUL SPS 2 SPS Operated SPS 4 GAS LEAKAGE R/Y/B STG1 REFILL SPS
6 CB NOT READY FOR A/R SPS 5 GAS LEAKAGE R/Y/B STG2 LOW SPS
7 A/R/IN AUTO/NONAUTO COMMAND DPC PTS Signals 6 GAS LEAKAGE R/Y/B ZONE TRIP SPS
8 RESET A/R LOCKOUT RELAY SPC S.No SIGNAL NAME TYPE 7 GAS LEAKAGE R/Y/B CB LOCKOUT SPS
NOTE-Applicable in case of Line and Respective Tie Bay 1 PTS Switch in Normal/Transfer Mode DPS NOTE- Sr. No. 4 to 7 signals are applicable for all gas compartment pertaining to each bay into one group. ( NTAMC IOM DTD. 05.10.2018 )
2 PTS Switch in Normal/Transfer Mode Command DPC
NOTE-Applicable for each element in case of Double Main Transfer Bus scheme
NOTE- If any other signal is required for remote operation as per site condition, it needs to be incorporated in final signal list.
NTAMC TYPICAL SIGNALS FOR ICT AND REACTOR BAYS
ICT/REACTOR SIGNALS ICT/REACTOR PROTECTION SIGNALS NGR BODY PROTECTION SIGNALS
S.No SIGNAL NAME TYPE S.No SIGNAL NAME TYPE S.No SIGNAL NAME TYPE
1 LOW OIL LEVEL ALARM SPS 1 BACKUP IMPEDANCE TRIP Z1 SPS 1 BUCHHOLZ TRIP SPS
2 BUCHHOLZ ALARM SPS 2 BACKUP IMPEDANCE TRIP Z2 SPS 2 PRV TRIP SPS
3 BUCHHOLZ TRIP SPS 3 BACKUP IMPEDANCE TRIP Z3 SPS 3 OTI TRIP SPS
4 OTI ALARM SPS 4 BACKUP IMPEDANCE TRIP Z4 SPS 4 OTI ALARM SPS
5 OTI TRIP SPS 5 POWER SWING BLOCKING SPS 5 BUCHHOLZ ALARM SPS
6 WTI ALARM SPS 6 HV - BACKUP O/C OPTD SPS 6 LOW OIL LEVEL ALARM SPS
7 WTI TRIP SPS 7 HV - BACKUP E/F OPTD SPS NOTE- 1) Applicable Only for oil filled NGR.
8 PRV-1 TRIP SPS 8 LV - BACKUP O/C OPTD SPS
9 PRV-2 TRIP SPS 9 LV - BACKUP E/F OPTD SPS
10 SPARE REACTOR/TRANSFORMER SELECTED SPS 10 LV - OVERFLUX ALARM SPS
11 SUDDEN PRESSURE RELAY TRIP SPS 11 LV - OVERFLUX OPTD SPS ICT/REACTOR ANALOG SIGNALS
12 OSR-1 Trip SPS 12 HV-OVERFLUX ALARM SPS S.No SIGNAL NAME TYPE
13 OSR-2 Trip SPS 13 HV OVERFLUX TRIP SPS 1 I (R-PHASE) AI
14 FIRE IN REACTOR/ICT SPS 14 NEUTRAL O/C PROTECTION OPTD SPS 2 I (Y-PHASE) AI
15 DELUGE VALVE OPTD SPS 15 NEUTRAL O/C RELAY UNHEALTHY SPS 3 I (B-PHASE) AI
16 DC SOURCE-1 FAIL SPS 16 COMMON THERMAL O/L ALARM SPS 4 MW AI
17 DC SOURCE-2 FAIL SPS 17 COMMON THERMAL O/L TRIP SPS 5 MVAR AI
18 SHUT OFF VALVE OPERATED SPS 18 INTERTRIP OPTD. SPS 6 V (R-Y PHASE) AI
19 OLTC PRV TRIP OPTD SPS 19 BACKUP O/C E/F RELAY UNHEALTHY HV SPS 7 V (Y-B PHASE) AI
20 OLTC OIL LEVEL ALARM SPS 20 BACKUP O/C E/F RELAY UNHEALTHY LV SPS 8 V (B-R PHASE) AI
21 OLTC DRIVE MOTOR FAULTY SPS 21 REF OPERATED SPS 9 FREQUENCY AI
22 DIRECT WDG TEMP MONITORING TRIP SPS 22 REF BLOCK SPS 10 HVWTI TEMP AI
23 FANS FAIL TO START BANK A SPS 23 DIFFERENTIAL RELAY OPTD. SPS 11 IVWTI TEMP AI
24 FANS FAIL TO START BANK B SPS 24 BACKUP IMPEDANCE OPTD SPS 12 LVWTI TEMP AI
25 PUMPS FAIL TO START BANK A SPS 25 SELECTED VT FUSE FAIL ALARM (Combined signal for all selected VT Fuse fail) SPS 13 OTI TEMP AI
26 PUMPS FAIL TO START BANK B SPS 26 DIFF RELAY UNHEALTHY SPS 14 TAP POSITION AI
27 OIL FLOW LOW ALARM BANK SPS 27 REF RELAY UNHEALTHY SPS 15 DGA MOISTURE VALUE AI
28 REACTOR COOLING SYSTEM TROUBLE SPS 28 BACKUP IMPEDANCE RELAY UNHEALTHY SPS 16 DGA H2 VALUE AI
29 TEED PROTECTION OPTD SPS 17 DGA C2H2 VALUE AI
NOTE- 1) Sr. no 1 to 18 - As applicable for ICT & Reactor. 2) Sr.no 19 to 27 - For ICTs. 3) Sr.no 28- for Reactor 4) As Applicable, above signal shall be required unit wise if individual phase units are existing. 30 TEED RELAY FAULTY SPS 18 DGA CO VALUE AI
NOTE- 1) Sr. no 1 to 20 - As applicable for ICT. 2) Sr.no 21 to 28 - For ICTs & Reactor. 3) Sr.no 29 & 30 for Reactor if applicable as per scheme. 4) As Applicable, above signal shall be required unit wise if individual phase units are existing. 19 DGA CO2 VALUE AI
20 DGA CH4 VALUE AI
21 DGA C2H6 VALUE AI
22 DGA C2H4 VALUE AI
23 DGA N2 VALUE AI
NOTE- 1) As Applicable, above signal(10-23) shall be required unit wise if individual phase units are existing. 2) ICT parameters needed at primary & secondary side(1-9) 3) Sr.No 14- TAP Position is applicable for ICT only. 4) 10,11,12 to be merged and single WTI to be taken for Reactor
NOTE- If any other signal is required for remote operation as per site condition, it needs to be incorporated in final signal list.
NTAMC TYPICAL SIGNALS FOR BUSBAR AND CONTROL AUTHORITY
BUS BAR SIGNALS (BUS-I,II,TBC AS APPLICABLE) BUS BAR PERIPHERAL UNITS- BAY WISE
S.No SIGNAL NAME TYPE S.No SIGNAL NAME TYPE
1 M1 BB Z1 OPERATED SPS 1 MAIN-1 BB PU UNIT FAULTY SPS
2 M2 BB Z1 OPERATED SPS 2 MAIN-2 BB PU UNIT FAULTY SPS
3 M1 BB Z2 OPERATED SPS 3 MAIN-1 BB PROTECTION OPTD SPS
4 M2 BB Z2 OPERATED SPS 4 MAIN-2 BB PROTECTION OPTD SPS
5 M1 BB Z1 OUT OF SERVICE SPS NOTE- 1) Signals to be taken for each bayas per availability of Bus Scheme .
6 M2 BB Z1 OUT OF SERVICE SPS
7 M1 BB Z2 OUT OF SERVICE SPS
8 M2 BB Z2 OUT OF SERVICE SPS
9 Main-1 BB RELAY UNHEALTHY SPS CONTROL AUTHORITY SIGNALS
10 Main-2 BB RELAY UNHEALTHY SPS S.No SIGNAL NAME TYPE
11 M1 BB Z1 BLOCK (Circuitry fault, out of service, fibrecom and any other conditions etc to be grouped) SPS 1 SUBSTATION MAIN CONTROL ON NTAMC SPS
12 M2 BB Z1 BLOCK(Circuitry fault, out of service, fibrecom and any other conditions etc to be grouped) SPS 2 SUBSTATION MAIN CONTROL ON RTAMC SPS
13 M1 BB Z2 BLOCK(Circuitry fault, out of service, fibrecom and any other conditions etc to be grouped) SPS 3 SUBSTATION MAIN CONTROL ON BACK UP SPS
14 M2 BB Z2 BLOCK(Circuitry fault, out of service, fibrecom and any other conditions etc to be grouped) SPS 4 SUBSTATION AUX CONTROL ON NTAMC SPS
15 M1 BB Z1 CT TROUBLE SPS 5 SUBSTATION AUX CONTROL ON RTAMC SPS
16 M2 BB Z1 CT TROUBLE SPS 6 SUBSTATION AUX CONTROL ON BACKUP SPS
17 M1 BB Z2 CT TROUBLE SPS
18 M2 BB Z2 CT TROUBLE SPS 7 COMMAND-MAIN CONTROL ON NTAMC SPC
19 MAIN-1 ZONE X AND ZONE Y MERGED/INTERCONNECTED SPS 8 COMMAND-MAIN CONTROL ON RTAMC SPC
20 MAIN-2 ZONE X AND ZONE Y MERGED/INTERCONNECTED SPS 9 COMMAND-MAIN CONTROL ON BACKUP SPC
21 CT SELECTION INCOMPLETE SPS 10 COMMAND-AUX CONTROL ON NTAMC SPC
22 VOLTAGE R-Y PHASE AI 11 COMMAND-AUX CONTROL ON RTAMC SPC
23 VOLTAGE Y-B PHASE AI 12 COMMAND-AUX CONTROL ON BACKUP SPC
24 VOLTAGE B-R PHASE AI NOTE- 1) Applicable for each Substation.
25 FREQUENCY AI
26 BUS BAR CHECK ZONE OPERATED SPS
27 BUS BAR CHECK ZONE CT SUPV ALARM SPS
28 BUS BAR CHECK ZONE OUT OF SERVICE SPS
29 BUS BAR CHECK ZONE RELAY UNHEALTHY SPS
NOTE- 1) Signals to be taken as per availability of Bus Scheme(One and Half,Double Main, Double Main Transfer etc.) 2) S. No. 22 to 25- to be taken for each bus 3) Signal at S. No. 19 and 20 to be taken as per availability of Bus Interconnection combinations for DMT/DM/Bus Sectionalizer scheme 4) S. No. 21 Signal to be added for DMT and DM Scheme 5) S.No. 26 to 29 - to be taken for each Main-1, Main-2 relay separately as per scheme
NOTE- If any other signal is required for remote operation as per site condition, it needs to be incorporated in final signal list.
NTAMC TYPICAL SIGNALS FOR AUXILIARY SYSTEM
LT SUPPLY SIGNALS-ACDB,MSB,TERTIARY DG SET SIGNALS FIRE FIGHTING
S.No SIGNAL NAME TYPE S.No SIGNAL NAME TYPE S.No SIGNAL NAME TYPE
1 ACDB INCOMER-1 OPEN/CLOSE DPS 1 DG SET BREAKER OPEN/CLOSE DPS 1 ELECTRIC MOTOR FIRE WATER PUMP RUNNING SPS
2 ACDB INCOMER-1 U/V PROTN. RLY OPTD SPS 2 ALTERNATOR ON SPS 2 ELECTRIC MOTOR FIRE WATER PUMP FAILS TO START SPS
3 ACDB INCOMER-1 OPEN/CLOSE COMMAND DPC 3 CHARGER 1 ON SPS 3 ELECTRIC PUMP IN AUTO MODE SPS
4 ACDB BUS COUPLER OPEN/CLOSE DPS 4 CHARGER 2 ON SPS 4 EPUMP CONTROL SUPPLY FAIL SPS
5 ACDB BC SUPERVISION OF CONTROL SUPPLY SPS 5 ENGINE OVERHEATING SPS 5 HVW ELECTRIC PUMP ACB ON /OFF DPS
6 ACDB BC OPEN/CLOSE COMMAND DPC 6 HIGH COOLING WATER TEMP. SPS 6 DIESEL ENGINE FIRE WATER PUMP FAILS TO START SPS
7 MSB-1 CB OPEN/CLOSE DPS 7 LOW OIL PRESSURE TRIP SPS 7 DIESEL ENGINE FIRE WATER PUMP RUNNING SPS
8 AUX. TRAFO-1 BUCHHOLZ ALARM SPS 8 DG SET FAILED TO START IN 30 SEC SPS 8 DIESEL ENGINE PUMP IN AUTO MODE SPS
9 AUX. TRAFO-1 WTI ALARM SPS 9 LACK OF FUEL SPS 9 DIESEL ENGINE BATTERY CHARGER-1 ON SPS
10 AUX. TRAFO-1 OTI ALARM SPS 10 LOW LEVEL IN DAILY SERVICE FUEL TANK SPS 10 DIESEL ENGINE BATTERY CHARGER-2 ON SPS
11 AUX. TRAFO-1 BUCHHOLZ TRIP SPS 11 HIGH SPEED DIESEL TANK LEVEL LOW SPS 11 DIESEL ENGINE FUEL LEVEL LOW SPS
12 AUX. TRAFO-1 WTI TRIP SPS 12 OVERSPEED TRIP SPS 12 DPUMP CONTROL SUPPLY FAIL SPS
13 AUX. TRAFO-1 OTI TRIP SPS 13 DG I/C PROTN OPTD(ALT FAULT,DIFF ETC) SPS 13 DIESEL PUMP OVER SPEED TRIP SPS
14 I/C-1 O/C PROTECTION RELAY TRIP SPS 14 CONTROL SUPPLY FAIL SPS 14 DIESEL PUMP LOW OIL PRESSURE TRIP SPS
15 I/C-1 E/F PROTECTION RELAY TRIP SPS 15 DG PROTECTION OPERATED (O/C, E/F, DIFF.) SPS 15 DIESEL ENGINE HIGH TEMPERATURE ALARM SPS
16 MSB BUS-1 U/V OPTD SPS 16 DG PROTECTION U/V OPERATED SPS 16 CONTROL ROOM ZONE-1 FIRE DETECTED SPS
17 MSB-1 PHASE SEQUENCE NEGATIVE ALARM SPS 17 AMF PANEL REMOTE SWITCH INDICATION SPS 17 CONTROL ROOM ZONE-2 FIRE DETECTED SPS
18 MSB INCOMER-1 OPEN/CLOSE COMMAND DPC 18 DG OVERLOAD SPS 18 CONTROL ROOM ZONE-3 FIRE DETECTED SPS
19 MSB-1 VOLTAGE (R-Y PHASE) AI 19 PHASE SEQUENCE NEGATIVE ALARM SPS 19 CONTROL ROOM ZONE-4 FIRE DETECTED SPS
20 MSB-1 VOLTAGE (Y-B PHASE) AI 20 ALTERNATOR FAULT SPS 20 765KV KIOSK-1 FIRE DETECTED SPS
21 MSB-1 VOLTAGE (B-R PHASE) AI 21 ACTIVE POWER(KW) AI 21 400kV KIOSK-1 FIRE DETECTED SPS
22 MSB-1 CURRENT (R-PHASE) AI 22 REACTIVE POWER(KVAR) AI 22 WATER STORAGE TANK-1 WATER LEVEL LOW SPS
23 MSB-1 CURRENT (Y-PHASE) AI 23 VOLTAGE (R-Y PHASE) AI 23 WATER STORAGE TANK-2 WATER LEVEL LOW SPS
24 MSB-1 CURRENT (B-PHASE) AI 24 VOLTAGE (Y-B PHASE) AI 24 FIRE FIGHTING TANK HEADER PRESSURE LEVEL LOW SPS
25 MSB-1 ACTIVE POWER(KW) AI 25 VOLTAGE (B-R PHASE) AI 25 FIRE ANNAUNCIATION PANEL FAULTY SPS
26 MSB-1 REACTIVE POWER(KVAR) AI 26 CURRENT (R-PHASE) AI 26 COMMON FIRE ALARM SPS
27 MSB BUS COUPLER BREAKER OPEN/CLOSE DPS 27 CURRENT (Y-PHASE) AI 27 JOCKEY PUMP-1 RUNNING SPS
28 MSB_BC SUPERVISION OF CONTROL SUPPLY SPS 28 CURRENT (B-PHASE) AI 28 JOCKEY PUMP-1 FAILS TO START SPS
29 MSB BC OPEN/CLOSE COMMAND DPC 29 DG SET BREAKER OPEN/CLOSE COMMAND DPC 29 JPUMP-1 SUPERVISION OF CONTROL SUPPLY SPS
30 TERTIARY-EARTH SWITCH OPEN/CLOSE DPS 30 DG SET START COMMAND SPC 30 JOCKEY PUMP-2 RUNNING SPS
31 TERTIARY-CB OPEN /CLOSE DPS 31 DG SET STOP COMMAND SPC 31 JOCKEY PUMP-2 FAILS TO START SPS
32 TERTIARY-ISO OPEN /CLOSE DPS 32 JPUMP-2 SUPERVISION OF CONTROL SUPPLY SPS
33 TERTIARY-CB INTERLOCK ENABLED SPS 33 FIRE FIGHTING PRESSURE MONITORING AI
34 TERTIARY-ISO INTERLOCK ENABLED SPS DCDB & BATTERY CHARGER NOTE- FIRE DETECTED Alarms to be taken as per applicability.
35 TERTIARY-CB TRIPPED ON PROTN SPS S.No SIGNAL NAME TYPE
36 TERTIARY-CB OPEN /CLOSE COMMAND DPC 1 220V BATTERY CHARGER -1 ON FLOAT/BOOST MODE DPS
37 TERTIARY-ISO OPEN /CLOSE COMMAND DPC 2 220V BATTERY CHARGER -2 ON FLOAT/BOOST MODE DPS
NOTE- 1) S.No. 1 to 3 same signals to be taken for ACDB-2 also 2) S.No. 7 to 26 same signals to be taken for MSB-2 also 3 48V BATTERY CHARGER -1 ON FLOAT/BOOST MODE DPS OTHER SIGNALS
4 48V BATTERY CHARGER -2 ON FLOAT/BOOST MODE DPS S.No SIGNAL NAME TYPE
5 220V DCDB -1 EARTH FAULT SPS 1 TIME SYNCH. SIGNAL ABSENT SPS
6 220V DCDB -2 EARTH FAULT SPS 2 765KV KIOSK-1 TEMP AI
7 220V BATTERY CHARGER-1 TROUBLE SPS 3 400KV KIOSK-1 TEMP AI
8 220V BATTERY CHARGER-2 TROUBLE SPS 4 CONTROL ROOM TEMPRATURE AI
9 48V BATTERY CHARGER-1 TROUBLE SPS 5 BATTERY ROOM TEMPRATURE AI
10 48V BATTERY CHARGER-2 TROUBLE SPS 6 AMBIENT TEMPERATURE OUTDOOR AI
11 220V DCDB -1 VOLTAGE AI 7 AMBIENT RELATIVE HUMIDITY OUTDOOR AI
12 220V BATTERY SET-1 CURRENT AI 8 WIND SPEED AI
13 220V DCDB -2 VOLTAGE AI 9 SUBSTATION IN LOCAL/REMOTE DPS
14 220V BATTERY SET-2 CURRENT AI NOTE- 1) S.No. 2,3 to be taken as per availability of no. of Kiosks
15 48V DCDB -1 VOLTAGE AI
16 48V BATTERY SET-1 CURRENT AI
17 48V DCDB -2 VOLTAGE AI
18 48V BATTERY SET-2 CURRENT AI
19 220V BATTERY CHARGER-1 CURRENT AI
20 220V BATTERY CHARGER-2 CURRENT AI
21 48V BATTERY CHARGER-1 CURRENT AI
22 48V BATTERY CHARGER-2 CURRENT AI
NOTE- 1) 110V DCDB Signals to be taken as per availability of DC source 2) Instantaneous alaram may be used for DC Earth Fault
NOTE- If any other signal is required for remote operation as per site condition, it needs to be incorporated in final signal list.
Distance Relay Differential Relay Master Trip Relay
S.No BAY NO Signal name TYPE S.No BAY NO Signal name TYPE S.No BAY NO Signal name TYPE
1 52BBR BPCB OPEN/CLOSE STATUS DPS 1 ABC MAIN-1 LINE DIFFERENTIAL PROTECTION OPERATED SPS 1 ABC 86A TRIP RELAY OPERATED SPS
2 52BBR-RPh BPCB R PHASE OPEN/CLOSE STATUS DPS 2 ABC MAIN-2 LINE DIFFERENTIAL PROTECTION OPERATED SPS 2 ABC 86B TRIP RELAY OPERATED SPS
3 52BBR-YPh BPCB Y PHASE OPEN/CLOSE STATUS DPS 3 ABC MAIN-2 DIFFERENTIAL PROTN TRIP R PH SPS 3 ABC 86A TRIP RELAY FAULTY SPS
4 52BBR-Bph BPCB B PHASE OPEN/CLOSE STATUS DPS 4 ABC MAIN-2 DIFFERENTIAL PROTN TRIP Y PH SPS 4 ABC 86B TRIP RELAY FAULTY SPS
5 89MBS BYPASS MBS ISOLATOR OPEN/CLOSE STATUS DPS 5 ABC MAIN-2 DIFFERENTIAL PROTN TRIP B PH SPS 5 ABC 86A TRIP RELAY RESET SPC
6 89DS1 ISOLATOR 1 OPEN/CLOSE STATUS DPS 6 ABC MAIN-1 DIFFERENTIATED WAVE BLOCK SPS 6 ABC 86B TRIP RELAY RESET SPC
7 89DS2 ISOLATOR 2 OPEN/CLOSE STATUS DPS 7 ABC MAIN-1 DIFFERENTIATED HORMONICS BLOCK SPS
8 89ES1 EARTH SWITCH 1 OPEN/CLOSE STATUS DPS 8 ABC MAIN-2 DIFFERENTIATED WAVE BLOCK SPS * Master Trip relay signals are required in All Bays and Switchable Reactors
9 89ES2 EARTH SWITCH 2 OPEN/CLOSE STATUS DPS 9 ABC MAIN-2 DIFFERENTIATED HORMONICS BLOCK SPS
10 52BBR BPCB OPEN/CLOSE CMD DPC 10 ABC MAIN-1 DIFFERENTIATED RESTRAIN TRIP SPS
11 89MBS BYPASS MBS OPEN/CLOSE CMD DPC 11 ABC MAIN-2 DIFFERENTIATED RESTRAIN TRIP SPS
12 89DS1 BYPASS CAP ISO 1 OPEN/CLOSE CMD DPC 12 ABC MAIN-1 DIFFERENTIATED UNRESTRAIN TRIP SPS Auto Reclosure Signals
13 89DS2 BYPASS CAP ISO 2 OPEN/CLOSE CMD DPC 13 ABC MAIN-2 DIFFERENTIATED UNRESTRAIN TRIP SPS S.No BAY NO Signal name TYPE
14 MASTER TRIP RST SPC 14 ABC MAIN-1 BROKEN CONDUCTOR ALARM SPS 1 ABC A/R IN AUTO / NONAUTO DPS
MOV TEMPERATURE R PHASE AI 15 ABC MAIN-2 BROKEN CONDUCTOR ALARM SPS 2 ABC A/R/IN AUTO/NONAUTO COMMAND DPC
MOV TEMPERATURE Y PHASE AI 16 ABC MAIN-1 BROKEN CONDUCTOR ALARM SPS 3 ABC A/R BLOCK SPS
MOV TEMPERATURE B PHASE AI 17 ABC MAIN-2 BROKEN CONDUCTOR ALARM SPS 4 ABC AUTORECLOSE LOCKOUT SPS
CAPACITOR R PHASE CURRENT AI 5 ABC AUTORECLOSE OPERATED SPS
CAPACITOR Y PHASE CURRENT AI 6 ABC AUTORECLOSE UNSUCCESFUL SPS
CAPACITOR B PHASE CURRENT AI 7 ABC A/R LOCK OUT RELAY RESET SPC
CAPACITOR R PHASE UNBALANCED CURRENT AI Busbar PU
CAPACITOR Y PHASE UNBALANCED CURRENT AI S.No BAY NO Signal name TYPE
CAPACITOR B PHASE UNBALANCED CURRENT AI 1 ABC MAIN-1 BB PROTECTION OPTD SPS
LINE CT CURRENT R-PH AI 2 ABC MAIN-2 BB PROTECTION OPTD SPS
LINE CT CURRENT Y-PH AI 3 ABC MAIN-1 BB PU UNIT FAULTY SPS Analog Signals
LINE CT CURRENT B-PH AI 4 ABC MAIN-2 BB PU UNIT FAULTY SPS S.No BAY NO Signal name TYPE
KIOSK TEMP AI 1 ABC I (R-PHASE) AI
2 ABC I (Y-PHASE) AI
3 ABC I (B-PHASE) AI
BCU 5 ABC MVAR AI
S.No BAY NO Signal name TYPE 6 ABC V (R-Y PHASE) AI
1 ABC BCU IN LOCAL / REMOTE DPS 7 ABC V (Y-B PHASE) AI
2 ABC BCU UNHEALTHY SPS 8 ABC V (B-R PHASE) AI
3 ABC BCU TIME SYNC ERROR SPS 9 ABC FREQUENCY AI
10 ABC MAIN-1 FAULT IMPEDANCE AI
11 ABC MAIN-1 FAULT DISTANCE AI
12 ABC MAIN-1 FAULT PERCENTAGE AI
13 ABC MAIN-2 FAULT IMPEDANCE AI
14 ABC MAIN-2 FAULT DISTANCE AI
15 ABC MAIN-2 FAULT PERCENTAGE AI
Sl.NO BAY NUM. BAY NAME DEVICE ID SIGNAL DESCRIPTION DATA TYPE SCADA ID REMARK
LINE FEEDER (ONE AND HALF BREAKER SCHEME)
1 ABC LINE FEEDER CB CB OPEN / CLOSE DPS STTS
2 ABC LINE FEEDER CB CB R-PH OPEN / CLOSE DPS STTR
3 ABC LINE FEEDER CB CB Y-PH OPEN / CLOSE DPS STTY
4 ABC LINE FEEDER CB CB B-PH OPEN / CLOSE DPS STTB
5 ABC LINE FEEDER 89A ISOLATOR OPEN / CLOSE DPS STTS
6 ABC LINE FEEDER 89B ISOLATOR OPEN / CLOSE DPS STTS
7 ABC LINE FEEDER 89L ISOLATOR OPEN / CLOSE DPS STTS
8 ABC LINE FEEDER 89AE1 EARTH SWITCH OPEN / CLOSE DPS STTS Bus Side Earth Switch
9 ABC LINE FEEDER 89AE2 EARTH SWITCH OPEN / CLOSE DPS STTS
10 ABC LINE FEEDER 89BE EARTH SWITCH OPEN / CLOSE DPS STTS
11 ABC LINE FEEDER 89LE EARTH SWITCH OPEN / CLOSE DPS STTS
12 ABC LINE FEEDER BCU BCU IN LOCAL / REMOTE DPS BCUR
13 ABC LINE FEEDER CB AUTO RECLOSE IN AUTO / NONAUTO DPS ARNA
SWITCHEABLE LINE REACTOR
1 ABC LINE REACTOR 52R REACTOR CB OPEN/CLOSE DPS STTS
2 ABC LINE REACTOR 52R REACTOR CB R-PH OPEN / CLOSE DPS STTR
3 ABC LINE REACTOR 52R REACTOR CB Y-PH OPEN / CLOSE DPS STTY
4 ABC LINE REACTOR 52R REACTOR CB B-PH OPEN / CLOSE DPS STTB
5 ABC LINE REACTOR 89RR ISOLATOR OPEN / CLOSE DPS STTS 3 PHASE STATUS IS REQUIRED IF REACTOR IS 3 PHASE
6 ABC LINE REACTOR 89RY ISOLATOR OPEN / CLOSE DPS STTS
7 ABC LINE REACTOR 89RB ISOLATOR OPEN / CLOSE DPS STTS
8 ABC LINE REACTOR 89RS1R ISOLATOR OPEN / CLOSE DPS STTS NOT APPLICABLE IF REACTOR IS 3 PHASE
9 ABC LINE REACTOR 89RS1Y ISOLATOR OPEN / CLOSE DPS STTS
10 ABC LINE REACTOR 89RS1B ISOLATOR OPEN / CLOSE DPS STTS
11 ABC LINE REACTOR 89RER EARTH SWITCH OPEN / CLOSE DPS STTS
12 ABC LINE REACTOR 89REY EARTH SWITCH OPEN / CLOSE DPS STTS
13 ABC LINE REACTOR 89REB EARTH SWITCH OPEN / CLOSE DPS STTS
14 ABC LINE REACTOR RE-BCU BCU IN LOCAL / REMOTE DPS BCUR
1 ABC LINE FEEDER WITH SW REACTOR NGR BYPASS CB OPEN / CLOSE DPS STTS ISOLATOR STATUS REQUIRED IF BYPASS ISOLATOR IS AVAILABLE
TIE BAY/ BUS SECTION
1 ABC TIE/ BS CB CB OPEN / CLOSE DPS STTS
2 ABC TIE/ BS CB CB R-PH OPEN / CLOSE DPS STTR
3 ABC TIE/ BS CB CB Y-PH OPEN / CLOSE DPS STTY
4 ABC TIE/ BS CB CB B-PH OPEN / CLOSE DPS STTB
5 ABC TIE/ BS 89A ISOLATOR OPEN/CLOSE DPS STTS
6 ABC TIE/ BS 89B ISOLATOR OPEN/CLOSE DPS STTS
7 ABC TIE/ BS 89AE EARTH SWITCH OPEN / CLOSE DPS STTS
8 ABC TIE/ BS 89BE EARTH SWITCH OPEN / CLOSE DPS STTS
9 ABC TIE/ BS BCU BCU IN LOCAL / REMOTE DPS BCUR
10 ABC TIE/ BS CB AUTO RECLOSE IN AUTO / NONAUTO DPS ARNA
LINE SERIES REACTOR/ BUS SERIES REACTOR
1 ABC LSR / BSR CB CB OPEN / CLOSE DPS STTS
2 ABC LSR / BSR CB CB R-PH OPEN / CLOSE DPS STTR
3 ABC LSR / BSR CB CB Y-PH OPEN / CLOSE DPS STTY
4 ABC LSR / BSR CB CB B-PH OPEN / CLOSE DPS STTB
5 ABC LSR / BSR 89A ISOLATOR OPEN/CLOSE DPS STTS
6 ABC LSR / BSR 89B ISOLATOR OPEN/CLOSE DPS STTS
7 ABC LSR / BSR 89AE EARTH SWITCH OPEN / CLOSE DPS STTS
8 ABC LSR / BSR 89BE EARTH SWITCH OPEN / CLOSE DPS STTS
9 ABC LSR / BSR 89L/ 89BSR ISOLATOR OPEN / CLOSE DPS STTS
10 ABC LSR / BSR 89LE/ 89BSRE EARTH SWITCH OPEN / CLOSE DPS STTS
11 ABC LSR 89LSR ISOLATOR OPEN/CLOSE DPS STTS In case of Line Series Reactor
13 ABC LSR 89LSR1 ISOLATOR OPEN/CLOSE DPS STTS
15 ABC LSR 89LSR2 ISOLATOR OPEN/CLOSE DPS STTS
17 ABC LSR 89LSR2- ES EARTH SWITCH OPEN / CLOSE DPS STTS
1 BUS-X VT 89 ISOLATOR OPEN/CLOSE STTS
2 BUS-X VT 89E EARTH SWITCH OPEN / CLOSE STTS
1 ABC FUTURE LINE 89A ISOLATOR OPEN / CLOSE DPS STTS
2 ABC FUTURE LINE 89AE EARTH SWITCH OPEN / CLOSE DPS STTS
3 ABC FUTURE LINE BCU BCU IN LOCAL / REMOTE DPS BCUR
765 KV BUS REACTOR (ONE AND HALF BREAKER SCHEME)
1 ABC BUS REACTOR CB CB OPEN / CLOSE DPS STTS
2 ABC BUS REACTOR CB CB R-PH OPEN / CLOSE DPS STTR
3 ABC BUS REACTOR CB CB Y-PH OPEN / CLOSE DPS STTY
4 ABC BUS REACTOR CB CB B-PH OPEN / CLOSE DPS STTB
5 ABC BUS REACTOR 89A ISOLATOR OPEN/CLOSE DPS STTS
6 ABC BUS REACTOR 89B ISOLATOR OPEN/CLOSE DPS STTS
7 ABC BUS REACTOR 89AE EARTH SWITCH OPEN / CLOSE DPS STTS
8 ABC BUS REACTOR 89BE EARTH SWITCH OPEN / CLOSE DPS STTS
9 ABC BUS REACTOR 89RR ISOLATOR OPEN / CLOSE DPS STTS 3 PHASE STATUS IS REQUIRED IF REACTOR IS 3 PHASE
10 ABC BUS REACTOR 89RY ISOLATOR OPEN / CLOSE DPS STTS
11 ABC BUS REACTOR 89RB ISOLATOR OPEN / CLOSE DPS STTS
12 ABC BUS REACTOR 89RS1R ISOLATOR OPEN / CLOSE DPS STTS NOT APPLICABLE IF REACTOR IS 3 PHASE
13 ABC BUS REACTOR 89RS1Y ISOLATOR OPEN / CLOSE DPS STTS
14 ABC BUS REACTOR 89RS1B ISOLATOR OPEN / CLOSE DPS STTS
15 ABC BUS REACTOR 89RER EARTH SWITCH OPEN / CLOSE DPS STTS
16 ABC BUS REACTOR 89REY EARTH SWITCH OPEN / CLOSE DPS STTS
17 ABC BUS REACTOR 89REB EARTH SWITCH OPEN / CLOSE DPS STTS
18 ABC BUS REACTOR RE-BCU BCU IN LOCAL / REMOTE DPS BCUR
1 ABC ICT CB CB OPEN / CLOSE DPS STTS
2 ABC ICT CB CB R-PH OPEN / CLOSE DPS STTR
3 ABC ICT CB CB Y-PH OPEN / CLOSE DPS STTY
4 ABC ICT CB CB B-PH OPEN / CLOSE DPS STTB
5 ABC ICT 89A ISOLATOR OPEN/CLOSE DPS STTS
6 ABC ICT 89B ISOLATOR OPEN/CLOSE DPS STTS
7 ABC ICT 89AE EARTH SWITCH OPEN / CLOSE DPS STTS
8 ABC ICT 89BE EARTH SWITCH OPEN / CLOSE DPS STTS
9 ABC ICT 89TR ISOLATOR OPEN / CLOSE DPS STTS 3 PHASE STATUS IS REQUIRED INSTEAD OF SINGLE PHASE ISOLATOR IN CASE OF 3 PHASE ICT
10 ABC ICT 89TY ISOLATOR OPEN / CLOSE DPS STTS
11 ABC ICT 89TB ISOLATOR OPEN / CLOSE DPS STTS
12 ABC ICT 89TS1R ISOLATOR OPEN / CLOSE DPS STTS NOT APPLICABLE FOR 3 PHASE ISOLATOR
13 ABC ICT 89TS1Y ISOLATOR OPEN / CLOSE DPS STTS
14 ABC ICT 89TS1B ISOLATOR OPEN / CLOSE DPS STTS
15 ABC ICT 89TER EARTH SWITCH OPEN / CLOSE DPS STTS
16 ABC ICT 89TEY EARTH SWITCH OPEN / CLOSE DPS STTS
17 ABC ICT 89TEB EARTH SWITCH OPEN / CLOSE DPS STTS
18 ABC ICT 89TS2EB EARTH SWITCH OPEN / CLOSE DPS STTS
19 ABC ICT BCU BCU IN LOCAL / REMOTE DPS BCUR
LINE FEEDER (DOUBLE MAIN )
1 ABC LINE FEEDER CB CB OPEN / CLOSE DPS STTS
2 ABC LINE FEEDER CB CB R-PH OPEN / CLOSE DPS STTR
3 ABC LINE FEEDER CB CB Y-PH OPEN / CLOSE DPS STTY
4 ABC LINE FEEDER CB CB B-PH OPEN / CLOSE DPS STTB
5 ABC LINE FEEDER 89A ISOLATOR OPEN/CLOSE DPS STTS
6 ABC LINE FEEDER 89B ISOLATOR OPEN/CLOSE DPS STTS
7 ABC LINE FEEDER 89AE EARTH SWITCH OPEN / CLOSE DPS STTS
8 ABC LINE FEEDER 89L ISOLATOR OPEN / CLOSE DPS STTS
9 ABC LINE FEEDER 89LE1 EARTH SWITCH OPEN / CLOSE DPS STTS
10 ABC LINE FEEDER 89LE2 EARTH SWITCH OPEN / CLOSE DPS STTS
11 ABC LINE FEEDER BCU BCU IN LOCAL / REMOTE DPS BCUR
ICT (DOUBLE MAIN )
1 ABC ICT CB CB OPEN / CLOSE DPS STTS
2 ABC ICT CB CB R-PH OPEN / CLOSE DPS STTR
3 ABC ICT CB CB Y-PH OPEN / CLOSE DPS STTY
4 ABC ICT CB CB B-PH OPEN / CLOSE DPS STTB
5 ABC ICT 89A ISOLATOR OPEN/CLOSE DPS STTS
6 ABC ICT 89B ISOLATOR OPEN/CLOSE DPS STTS
7 ABC ICT 89AE EARTH SWITCH OPEN / CLOSE DPS STTS
8 ABC ICT 89T ISOLATOR OPEN / CLOSE DPS STTS
9 ABC ICT 89TE1 EARTH SWITCH OPEN / CLOSE DPS STTS
10 ABC ICT 89TE2 EARTH SWITCH OPEN / CLOSE DPS STTS
11 ABC ICT BCU BCU IN LOCAL / REMOTE DPS BCUR
220 KV ICT (DMT SCHEME)
1 ABC ICT CB CB OPEN / CLOSE DPS STTS
2 ABC ICT 89A ISOLATOR OPEN/CLOSE DPS STTS
3 ABC ICT 89B ISOLATOR OPEN/CLOSE DPS STTS
4 ABC ICT 89T ISOLATOR OPEN / CLOSE DPS STTS
5 ABC ICT 89L EARTH SWITCH OPEN / CLOSE DPS STTS
6 ABC ICT 89AE EARTH SWITCH OPEN / CLOSE DPS STTS
7 ABC ICT 89LE1 EARTH SWITCH OPEN / CLOSE DPS STTS
8 ABC ICT 89LE2 EARTH SWITCH OPEN / CLOSE DPS STTS
9 ABC ICT BCU BCU IN LOCAL / REMOTE DPS BCUR
220 KV LINE FEEDER (DMT SCHEME)
1 ABC LINE FEEDER CB CB OPEN / CLOSE DPS STTS
2 ABC LINE FEEDER CB CB R-PH OPEN / CLOSE DPS STTR
3 ABC LINE FEEDER CB CB Y-PH OPEN / CLOSE DPS STTY
4 ABC LINE FEEDER CB CB B-PH OPEN / CLOSE DPS STTB
5 ABC LINE FEEDER 89A ISOLATOR OPEN / CLOSE DPS STTS
6 ABC LINE FEEDER 89B ISOLATOR OPEN / CLOSE DPS STTS
7 ABC LINE FEEDER 89T ISOLATOR OPEN / CLOSE DPS STTS
8 ABC LINE FEEDER 89L ISOLATOR OPEN / CLOSE DPS STTS
9 ABC LINE FEEDER 89AE EARTH SWITCH OPEN / CLOSE DPS STTS
10 ABC LINE FEEDER 89LE1 EARTH SWITCH OPEN / CLOSE DPS STTS
11 ABC LINE FEEDER 89LE2 EARTH SWITCH OPEN / CLOSE DPS STTS
12 ABC LINE FEEDER BCU BCU IN LOCAL / REMOTE DPS BCUR
13 ABC LINE FEEDER CB AUTO RECLOSE IN AUTO / NONAUTO DPS ARNA
14 ABC LINE FEEDER CB TRANSFER SWITCH NORMAL/TRANSFER DPS TSWN
220 KV BUS COUPLER (DMT SCHEME)
1 ABC BUS COUPLER CB CB OPEN / CLOSE DPS STTS
2 ABC BUS COUPLER 89A ISOLATOR OPEN / CLOSE DPS STTS
3 ABC BUS COUPLER 89B ISOLATOR OPEN / CLOSE DPS STTS
4 ABC BUS COUPLER 89AE1 EARTH SWITCH OPEN / CLOSE DPS STTS
5 ABC BUS COUPLER 89AE2 EARTH SWITCH OPEN / CLOSE DPS STTS
6 ABC BUS COUPLER 89BE1 EARTH SWITCH OPEN / CLOSE DPS STTS
7 ABC BUS COUPLER 89BE2 EARTH SWITCH OPEN / CLOSE DPS STTS
8 ABC BUS COUPLER BCU BCU IN LOCAL / REMOTE DPS BCUR
220 KV TRANSFER BUS COUPLER (DMT SCHEME)
1 ABC TRANSFER BUS COUPLER CB CB OPEN / CLOSE DPS STTS
2 ABC TRANSFER BUS COUPLER CB CB R-PH OPEN / CLOSE DPS STTR
3 ABC TRANSFER BUS COUPLER CB CB Y-PH OPEN / CLOSE DPS STTY
4 ABC TRANSFER BUS COUPLER CB CB B-PH OPEN / CLOSE DPS STTB
5 ABC TRANSFER BUS COUPLER 89A ISOLATOR OPEN / CLOSE DPS STTS
6 ABC TRANSFER BUS COUPLER 89B ISOLATOR OPEN / CLOSE DPS STTS
7 ABC TRANSFER BUS COUPLER 89T ISOLATOR OPEN / CLOSE DPS STTS
8 ABC TRANSFER BUS COUPLER 89AE EARTH SWITCH OPEN / CLOSE DPS STTS
9 ABC TRANSFER BUS COUPLER 89TE1 EARTH SWITCH OPEN / CLOSE DPS STTS
10 ABC TRANSFER BUS COUPLER 89TE2 EARTH SWITCH OPEN / CLOSE DPS STTS
11 ABC TRANSFER BUS COUPLER BCU BCU IN LOCAL / REMOTE DPS BCUR
12 ABC TRANSFER BUS COUPLER CB AUTO RECLOSE IN AUTO / NONAUTO DPS ARNA
132 KV ICT (SINGLE MAIN AND TRANSFER)
1 ABC ICT CB CB OPEN / CLOSE DPS STTS
2 ABC ICT 89A ISOLATOR OPEN/CLOSE DPS STTS
3 ABC ICT 89L ISOLATOR OPEN/CLOSE DPS STTS
4 ABC ICT 89T ISOLATOR OPEN / CLOSE DPS STTS
5 ABC ICT BCU BCU IN LOCAL / REMOTE DPS BCUR
132 KV BUS COUPLER (SINGLE MAIN AND TRANSFER)
1 ABC BUS COUPLER CB CB OPEN / CLOSE DPS STTS
2 ABC BUS COUPLER 89A ISOLATOR OPEN/CLOSE DPS STTS
3 ABC BUS COUPLER 89L ISOLATOR OPEN/CLOSE DPS STTS
4 ABC BUS COUPLER 89T ISOLATOR OPEN / CLOSE DPS STTS
5 ABC BUS COUPLER BCU BCU IN LOCAL / REMOTE DPS BCUR
132 KV LINE FEEDER (SINGLE MAIN AND TRANSFER)
1 ABC LINE FEEDER CB CB OPEN / CLOSE DPS STTS
2 ABC LINE FEEDER 89A ISOLATOR OPEN/CLOSE DPS STTS
3 ABC LINE FEEDER 89T ISOLATOR OPEN/CLOSE DPS STTS
4 ABC LINE FEEDER 89L EARTH SWITCH OPEN / CLOSE DPS STTS
5 ABC LINE FEEDER 89LE EARTH SWITCH OPEN / CLOSE DPS STTS
6 ABC LINE FEEDER BCU BCU IN LOCAL / REMOTE DPS BCUR
FIXED SERIES CAPACITOR (FSC)
1 ABC FSC 52BBR BPCB OPEN/CLOSE STATUS DPS
2 ABC FSC 52BBR-RPh BPCB R PHASE OPEN/CLOSE STATUS DPS
3 ABC FSC 52BBR-YPh BPCB Y PHASE OPEN/CLOSE STATUS DPS
4 ABC FSC 52BBR-Bph BPCB B PHASE OPEN/CLOSE STATUS DPS
5 ABC FSC 89MBS BYPASS MBS ISOLATOR OPEN/CLOSE STATUS DPS
6 ABC FSC 89DS1 ISOLATOR 1 OPEN/CLOSE STATUS DPS
7 ABC FSC 89DS2 ISOLATOR 2 OPEN/CLOSE STATUS DPS
8 ABC FSC 89ES1 EARTH SWITCH 1 OPEN/CLOSE STATUS DPS
9 ABC FSC 89ES2 EARTH SWITCH 2 OPEN/CLOSE STATUS DPS
AUXILLIARY SYSTEM
1 220VDC BCHRG BATCHRG220V-1 220V BATTERY CHARGER -1 ON FLOAT MODE DPS
2 220VDC BCHRG BATCHRG220V-1 220V BATTERY CHARGER -1 ON BOOST MODE DPS
3 220VDC BCHRG BATCHRG220V-2 220V BATTERY CHARGER -2 ON FLOAT MODE DPS
4 220VDC BCHRG BATCHRG220V-2 220V BATTERY CHARGER -2 ON BOOST MODE DPS
5 48 VDC BCHRG BATCHRG48V-1 48V BATTERY CHARGER -1 ON FLOAT MODE DPS
6 48 VDC BCHRG BATCHRG48V-1 48V BATTERY CHARGER -1 ON BOOST MODE DPS
7 48 VDC BCHRG BATCHRG48V-2 48V BATTERY CHARGER -2 ON FLOAT MODE DPS
8 48 VDC BCHRG BATCHRG48V-2 48V BATTERY CHARGER -2 ON BOOST MODE DPS
9 415 V FP EPUMP HVW ELECTRIC PUMP ACB ON DPS
10 415 V FP EPUMP HVW ELECTRIC PUMP ACB OFF DPS
11 415 V DG Set DGSET-1 DG SET BREAKER OPEN DPS
12 415 V DG Set DGSET-1 DG SET BREAKER CLOSE DPS
13 415 V LTSUP ACDB-1 ACDB INCOMER-1 OPEN DPS
14 415 V LTSUP ACDB-1 ACDB INCOMER-1 CLOSE DPS
15 415 V LTSUP ACDB-BC ACDB BUS COUPLER OPEN DPS
16 415 V LTSUP ACDB-BC ACDB BUS COUPLER CLOSE DPS
17 415 V LTSUP ACDB-2 ACDB INCOMER-2 OPEN DPS
18 415 V LTSUP ACDB-2 ACDB INCOMER-2 CLOSE DPS
19 415 V LTSUP MSB-1 MSB-1 CB OPEN DPS
20 415 V LTSUP MSB-1 MSB-1 CB CLOSE DPS
21 415 V LTSUP MSB_BC MSB BUS COUPLER BREAKER OPEN DPS
22 415 V LTSUP MSB_BC MSB BUS COUPLER BREAKER CLOSE DPS
23 415 V LTSUP MSB-2 MSB-2 CB OPEN DPS
24 415 V LTSUP MSB-2 MSB- 2 CB CLOSE DPS
25 33 KV LTSUP TERTIARY EARTH SWITCH OPEN DPS
26 33 KV LTSUP TERTIARY EARTH SWITCH CLOSE DPS
27 33 KV LTSUP TERTIARY CB OPEN DPS
28 33 KV LTSUP TERTIARY CB CLOSE DPS
29 33 KV LTSUP TERTIARY ISO OPEN DPS
30 33 KV LTSUP TERTIARY ISO CLOSE DPS
STATCOM (SIEMENS)
1 ABC STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89A HV Main Bay 89A Isolator Open DPS
2 ABC STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89A HV Main Bay 89A Isolator Close DPS
3 ABC STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89B HV Main Bay 89B Isolator Open DPS
4 ABC STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89B HV Main Bay 89B Isolator Close DPS
5 ABC STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89AE HV Main Bay 89AE Earth Switch Open DPS
6 ABC STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89AE HV Main Bay 89AE Earth Switch Close DPS
7 ABC STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89BE HV Main Bay 89BE Earth Switch Open DPS
8 ABC STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89BE HV Main Bay 89BE Earth Switch Close DPS
9 ABC STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-52 HV Main Bay CB Open DPS
10 ABC STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-52 HV Main Bay CB Close DPS
11 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q2 R PH ISOLATOR OPEN DPS
12 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q2 R PH ISOLATOR CLOSED DPS
13 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q2 Y PH ISOLATOR OPEN DPS
14 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q2 Y PH ISOLATOR CLOSED DPS
15 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q2 B PH ISOLATOR OPEN DPS
16 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q2 B PH ISOLATOR CLOSED DPS
17 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q3 R PH ISOLATOR OPEN DPS
18 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q3 R PH ISOLATOR CLOSED DPS
19 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q3 Y PH ISOLATOR OPEN DPS
20 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q3 Y PH ISOLATOR CLOSED DPS
21 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q3 B PH ISOLATOR OPEN DPS
22 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q3 B PH ISOLATOR CLOSED DPS
23 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q51 R PH EARTH SWITCH OPEN DPS
24 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q51 R PH EARTH SWITCH CLOSED DPS
25 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q51 Y PH EARTH SWITCH OPEN DPS
26 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q51 Y PH EARTH SWITCH CLOSED DPS
27 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q51 B PH EARTH SWITCH OPEN DPS
28 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q51 B PH EARTH SWITCH CLOSED DPS
29 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q52 EARTH SWITCH OPEN DPS
30 ABC STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q52 EARTH SWITCH CLOSED DPS
31 ABC STATCOM HV SIDE TIE BAY TIE BAY 4YY-89A ISOLATOR OPEN DPS
32 ABC STATCOM HV SIDE TIE BAY TIE BAY 4YY-89A ISOLATOR CLOSE DPS
33 ABC STATCOM HV SIDE TIE BAY TIE BAY 4YY-89B ISOLATOR OPEN DPS
34 ABC STATCOM HV SIDE TIE BAY TIE BAY 4YY-89B ISOLATOR CLOSE DPS
35 ABC STATCOM HV SIDE TIE BAY TIE BAY 4YY-89AE EARTH SWITCH OPEN DPS
36 ABC STATCOM HV SIDE TIE BAY TIE BAY 4YY-89AE EARTH SWITCH CLOSE DPS
37 ABC STATCOM HV SIDE TIE BAY TIE BAY 4YY-89BE EARTH SWITCH OPEN DPS
38 ABC STATCOM HV SIDE TIE BAY TIE BAY 4YY-89BE EARTH SWITCH CLOSE DPS
39 ABC STATCOM HV SIDE TIE BAY TIE BAY 4YY-52 CB OPEN DPS
40 ABC STATCOM HV SIDE TIE BAY TIE BAY 4YY-52 CB CLOSE DPS
41 ABC FUTURE HV Future Bay 89A Isolator Open DPS
42 ABC FUTURE HV Future Bay 89A Isolator Close DPS
43 ABC FUTURE HV Future Bay 89AE Earth Switcr Open DPS
44 ABC FUTURE HV Future Bay 89AE Earth Switcr Close DPS
45 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q1 R PH MV ISOLATOR OPEN DPS
46 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q1 R PH MV ISOLATOR CLOSED DPS
47 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q1 Y PH MV ISOLATOR OPEN DPS
48 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q1 Y PH MV ISOLATOR CLOSED DPS
49 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q1 B PH MV ISOLATOR OPEN DPS
50 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q1 B PH MV ISOLATOR CLOSED DPS
51 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q2 R PH MV ISOLATOR OPEN DPS
52 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q2 R PH MV ISOLATOR CLOSED DPS
53 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q2 Y PH MV ISOLATOR OPEN DPS
54 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q2 Y PH MV ISOLATOR CLOSED DPS
55 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q2 B PH MV ISOLATOR OPEN DPS
56 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q2 B PH MV ISOLATOR CLOSED DPS
57 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q12 R PH MV ISOLATOR OPEN DPS
58 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q12 R PH MV ISOLATOR CLOSED DPS
59 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q12 Y PH MV ISOLATOR OPEN DPS
60 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q12 Y PH MV ISOLATOR CLOSED DPS
61 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q12 B PH MV ISOLATOR OPEN DPS
62 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q12 B PH MV ISOLATOR CLOSED DPS
63 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q13 R PH MV ISOLATOR OPEN DPS
64 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q13 R PH MV ISOLATOR CLOSED DPS
65 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q13 Y PH MV ISOLATOR OPEN DPS
66 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q13 Y PH MV ISOLATOR CLOSED DPS
67 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q13 B PH MV ISOLATOR OPEN DPS
68 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q13 B PH MV ISOLATOR CLOSED DPS
69 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER J01-Q52 BUSBAR EARTHING SWITCH OPEN DPS
70 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER J01-Q52 BUSBAR EARTHING SWITCH CLOSED DPS
71 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER J01-Q0 AUXILIARY SUPPLY CIRCUIT BREAKER OPEN DPS
72 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER J01-Q0 AUXILIARY SUPPLY CIRCUIT BREAKER CLOSED DPS
73 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER J01-Q1 AUXILIARY SUPPLY ISOLATOR OPEN DPS
74 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER J01-Q1 AUXILIARY SUPPLY ISOLATOR CLOSED DPS
75 J11 STATCOM VSC-1 BAY MSC-2 MV-J32 CIRCUIT BREAKER OPEN DPS
76 J11 STATCOM VSC-1 BAY VSC-1 J11 Q0 CIRCUIT BREAKER CLOSED DPS
77 J11 STATCOM VSC-1 BAY VSC-1 J11 Q5 EARTHING SWITCH OPEN DPS
78 J11 STATCOM VSC-1 BAY VSC-1 J11 Q5 EARTHING SWITCH CLOSED DPS
79 J11 STATCOM VSC-1 BAY VSC-1 J11 Q1 ISOLATOR SWITCH OPEN DPS
80 J11 STATCOM VSC-1 BAY VSC-1 J11 Q1 ISOLATOR SWITCH CLOSED DPS
81 J12 STATCOM VSC-2 BAY VSC-2 J12 Q0 CIRCUIT BREAKER OPEN DPS
82 J12 STATCOM VSC-2 BAY VSC-2 J12 Q0 CIRCUIT BREAKER CLOSED DPS
83 J12 STATCOM VSC-2 BAY VSC-2 J12 Q5 EARTHING SWITCH OPEN DPS
84 J12 STATCOM VSC-2 BAY VSC-2 J12 Q5 EARTHING SWITCH CLOSED DPS
85 J12 STATCOM VSC-2 BAY VSC-2 J12 Q1 ISOLATOR SWITCH OPEN DPS
86 J12 STATCOM VSC-2 BAY VSC-2 J12 Q1 ISOLATOR SWITCH CLOSED DPS
87 J21 STATCOM MSR-1 BAY MSR-1 J21 Q0 CIRCUIT BREAKER OPEN DPS
88 J21 STATCOM MSR-1 BAY MSR-1 J21 Q0 CIRCUIT BREAKER CLOSED DPS
89 J21 STATCOM MSR-1 BAY MSR-1 J21 Q1 ISOLATOR SWITCH OPEN DPS
90 J21 STATCOM MSR-1 BAY MSR-1 J21 Q1 ISOLATOR SWITCH CLOSED DPS
91 J21 STATCOM MSR-1 BAY MSR-1 J21 Q5 EARTHING SWITCH OPEN DPS
92 J21 STATCOM MSR-1 BAY MSR-1 J21 Q5 EARTHING SWITCH CLOSED DPS
93 J22 STATCOM MSR-2 BAY MSR-2 J22 Q0 CIRCUIT BREAKER OPEN DPS
94 J22 STATCOM MSR-2 BAY MSR-2 J22 Q0 CIRCUIT BREAKER CLOSED DPS
95 J22 STATCOM MSR-2 BAY MSR-2 J22 Q1 ISOLATOR SWITCH OPEN DPS
96 J22 STATCOM MSR-2 BAY MSR-2 J22 Q1 ISOLATOR SWITCH CLOSED DPS
97 J22 STATCOM MSR-2 BAY MSR-2 J22 Q5 EARTHING SWITCH OPEN DPS
98 J22 STATCOM MSR-2 BAY MSR-2 J22 Q5 EARTHING SWITCH CLOSED DPS
99 J31 STATCOM MSC-1 BAY MSC-1 J31 Q0 CIRCUIT BREAKER OPEN DPS
100 J31 STATCOM MSC-1 BAY MSC-1 J31 Q0 CIRCUIT BREAKER CLOSED DPS
101 J31 STATCOM MSC-1 BAY MSC-1 J31 Q1 ISOLATOR SWITCH OPEN DPS
102 J31 STATCOM MSC-1 BAY MSC-1 J31 Q1 ISOLATOR SWITCH CLOSED DPS
103 J31 STATCOM MSC-1 BAY MSC-1 J31 Q5 EARTHING SWITCH OPEN DPS
104 J31 STATCOM MSC-1 BAY MSC-1 J31 Q5 EARTHING SWITCH CLOSED DPS
105 J32 STATCOM MSC-2 BAY MSC-2 J32 Q0 CIRCUIT BREAKER OPEN DPS
106 J32 STATCOM MSC-2 BAY MSC-2 J32 Q0 CIRCUIT BREAKER CLOSED DPS
107 J32 STATCOM MSC-2 BAY MSC-2 J32 Q1 ISOLATOR SWITCH OPEN DPS
108 J32 STATCOM MSC-2 BAY MSC-2 J32 Q1 ISOLATOR SWITCH CLOSED DPS
109 J32 STATCOM MSC-2 BAY MSC-2 J32 Q5 EARTHING SWITCH OPEN DPS
110 J32 STATCOM MSC-2 BAY MSC-2 J32 Q5 EARTHING SWITCH CLOSED DPS
111 STATCOM STATCOM STATCOM OPERATION STATCOM AUTOMATIC CONTROL STATUS DPS
112 STATCOM STATCOM STATCOM OPERATION STATCOM MANUAL CONTROL STATUS DPS
113 STATCOM STATCOM STATCOM OPERATION REACTIVE POWER CONTROL MODE ENABLE DPS
114 STATCOM STATCOM STATCOM OPERATION REACTIVE POWER CONTROL MODE DISABLE DPS
115 STATCOM STATCOM STATCOM OPERATION GAIN ADJUSTMENT AUTOMATIC DPS
116 STATCOM STATCOM STATCOM OPERATION GAIN ADJUSTMENT MANUAL DPS
117 STATCOM STATCOM STATCOM OPERATION NPS ON DPS
118 STATCOM STATCOM STATCOM OPERATION NPS OFF DPS
119 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICES HV AUTOMATIC DPS
120 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICES HV OFF DPS
121 STATCOM STATCOM STATCOM OPERATION AUTO-RESTART ON SELECTED DPS
122 STATCOM STATCOM STATCOM OPERATION AUTO-RESTART OFF SELECTED DPS
123 STATCOM STATCOM STATCOM OPERATION SELECT SYSTEM 1 ACTIVE DPS
124 STATCOM STATCOM STATCOM OPERATION SELECT SYSTEM 2 ACTIVE DPS
125 STATCOM STATCOM STATCOM OPERATION UNEQUAL LOAD SHARING MODE ON DPS
126 STATCOM STATCOM STATCOM OPERATION UNEQUAL LOAD SHARING MODE OFF DPS
127 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV1 PSD BYPASS DPS
128 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV1 PSD ON DPS
129 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV2 PSD BYPASS DPS
130 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV2 PSD ON DPS
131 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV3 PSD BYPASS DPS
132 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV3 PSD ON DPS
133 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV4 PSD BYPASS DPS
134 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV4 PSD ON DPS
135 STATCOM AUX STATCOM AUX MSB-1 A-AC SUPPLY -CB1 OPEN POSITION DPS
136 STATCOM AUX STATCOM AUX MSB-1 A-AC SUPPLY -CB1 CLOSED POSITION DPS
137 STATCOM AUX STATCOM AUX MSB-2 B-AC SUPPLY -CB2 OPEN POSITION DPS
138 STATCOM AUX STATCOM AUX MSB-2 B-AC SUPPLY -CB2 CLOSED POSITION DPS
139 STATCOM AUX STATCOM AUX MSB-BC AC TIE-BREAKER -CB3 OPEN POSITION DPS
140 STATCOM AUX STATCOM AUX MSB-BC AC TIE-BREAKER -CB3 CLOSED POSITION DPS
141 STATCOM AUX STATCOM AUX ACDB-2A ACDB- 2A AC SUPPLY - INCOMER -1 CB OPEN POSITION DPS
142 STATCOM AUX STATCOM AUX ACDB-2A ACDB- 2A AC SUPPLY -- INCOMER -1 CB CLOSED POSITION DPS
143 STATCOM AUX STATCOM AUX ACDB-2A ACDB- 2A AC SUPPLY - INCOMER -2 CB OPEN POSITION DPS
144 STATCOM AUX STATCOM AUX ACDB-2A ACDB- 2A AC SUPPLY -- INCOMER -2 CB CLOSED POSITION DPS
145 STATCOM AUX STATCOM AUX ACDB-2A ACDB- 2A AC SUPPLY - DG INCOMER CB OPEN POSITION DPS
146 STATCOM AUX STATCOM AUX ACDB-2A ACDB- 2A AC SUPPLY -- DG INCOMER CB CLOSED POSITION DPS
147 STATCOM AUX STATCOM AUX ACDB-2A ACDB- 2A AC TIE-BREAKER -CB OPEN POSITION DPS
148 STATCOM AUX STATCOM AUX ACDB-2A ACDB- 2A AC TIE-BREAKER -CB CLOSED POSITION DPS
1 ABC FUTURE BAY 89A HV Future Bay 89A Isolator Open DPS
2 ABC FUTURE BAY 89A HV Future Bay 89A Isolator Close DPS
3 ABC FUTURE BAY 89AE HV Future Bay 89AE Earth Switch Open DPS
4 ABC FUTURE BAY 89AE HV Future Bay 89AE Earth Switch Close DPS
5 ABC FUTURE& COUPLING T/F-1 TIE 52 CB R-PHASE OPEN DPS
6 ABC FUTURE& COUPLING T/F-1 TIE 52 CB R-PHASE CLOSE DPS
7 ABC FUTURE& COUPLING T/F-1 TIE 52 CB Y-PHASE OPEN DPS
8 ABC FUTURE& COUPLING T/F-1 TIE 52 CB Y-PHASE CLOSE DPS
9 ABC FUTURE& COUPLING T/F-1 TIE 52 CB B-PHASE OPEN DPS
10 ABC FUTURE& COUPLING T/F-1 TIE 52 CB B-PHASE CLOSE DPS
11 ABC FUTURE& COUPLING T/F-1 TIE 52 CB OPEN DPS
12 ABC FUTURE& COUPLING T/F-1 TIE 52 CB CLOSE DPS
13 ABC FUTURE& COUPLING T/F-1 TIE 89A ISOLATOR OPEN DPS
14 ABC FUTURE& COUPLING T/F-1 TIE 89A ISOLATOR CLOSE DPS
15 ABC FUTURE& COUPLING T/F-1 TIE 89AE EARTH SWITCH OPEN DPS
16 ABC FUTURE& COUPLING T/F-1 TIE 89AE EARTH SWITCH CLOSE DPS
17 ABC FUTURE& COUPLING T/F-1 TIE 89B ISOLATOR OPEN DPS
18 ABC FUTURE& COUPLING T/F-1 TIE 89B ISOLATOR CLOSE DPS
19 ABC FUTURE& COUPLING T/F-1 TIE BCU BCU IN LOCAL DPS
20 ABC FUTURE& COUPLING T/F-1 TIE BCU BCU IN REMOTE DPS
21 ABC COUPLING TRANSFORMER (HV) 52 CB OPEN DPS
22 ABC COUPLING TRANSFORMER (HV) 52 CB CLOSE DPS
23 ABC COUPLING TRANSFORMER (HV) 89A ISOLATOR OPEN DPS
24 ABC COUPLING TRANSFORMER (HV) 89A ISOLATOR CLOSE DPS
25 ABC COUPLING TRANSFORMER (HV) 89AE EARTH SWITCH OPEN DPS
26 ABC COUPLING TRANSFORMER (HV) 89AE EARTH SWITCH CLOSE DPS
27 ABC COUPLING TRANSFORMER (HV) 89B ISOLATOR OPEN DPS
28 ABC COUPLING TRANSFORMER (HV) 89B ISOLATOR CLOSE DPS
29 ABC COUPLING TRANSFORMER (HV) 89BE EARTH SWITCH OPEN DPS
30 ABC COUPLING TRANSFORMER (HV) 89BE EARTH SWITCH CLOSE DPS
31 ABC COUPLING TRANSFORMER (HV) 89TR ISOLATOR OPEN DPS
32 ABC COUPLING TRANSFORMER (HV) 89TR ISOLATOR CLOSE DPS
33 ABC COUPLING TRANSFORMER (HV) 89TRE EARTH SWITCH OPEN DPS
34 ABC COUPLING TRANSFORMER (HV) 89TRE EARTH SWITCH CLOSE DPS
35 ABC COUPLING TRANSFORMER (HV) 89TSR ISOLATOR OPEN DPS
36 ABC COUPLING TRANSFORMER (HV) 89TSR ISOLATOR CLOSE DPS
37 ABC COUPLING TRANSFORMER (HV) 89TY ISOLATOR OPEN DPS
38 ABC COUPLING TRANSFORMER (HV) 89TY ISOLATOR CLOSE DPS
39 ABC COUPLING TRANSFORMER (HV) 89TYE EARTH SWITCH OPEN DPS
40 ABC COUPLING TRANSFORMER (HV) 89TYE EARTH SWITCH CLOSE DPS
41 ABC COUPLING TRANSFORMER (HV) 89TSY ISOLATOR OPEN DPS
42 ABC COUPLING TRANSFORMER (HV) 89TSY ISOLATOR CLOSE DPS
43 ABC COUPLING TRANSFORMER (HV) 89TB ISOLATOR OPEN DPS
44 ABC COUPLING TRANSFORMER (HV) 89TB ISOLATOR CLOSE DPS
45 ABC COUPLING TRANSFORMER (HV) 89TBE EARTH SWITCH OPEN DPS
46 ABC COUPLING TRANSFORMER (HV) 89TBE EARTH SWITCH CLOSE DPS
47 ABC COUPLING TRANSFORMER (HV) 89TSB ISOLATOR OPEN DPS
48 ABC COUPLING TRANSFORMER (HV) 89TSB ISOLATOR CLOSE DPS
49 38.5KV COUPLING T/F (S) ICT (MV) 60089TR1 ISOLATOR OPEN/CLOSE DPS
50 38.5KV COUPLING T/F (S) ICT (MV) 60089TR2 ISOLATOR OPEN/CLOSE DPS
51 38.5KV COUPLING T/F (S) ICT (MV) 60089TY1 ISOLATOR OPEN/CLOSE DPS
52 38.5KV COUPLING T/F (S) ICT (MV) 60089TY2 ISOLATOR OPEN/CLOSE DPS
53 38.5KV COUPLING T/F (S) ICT (MV) 60089TB1 ISOLATOR OPEN/CLOSE DPS
54 38.5KV COUPLING T/F (S) ICT (MV) 60089TB2 ISOLATOR OPEN/CLOSE DPS
55 38.5KV COUPLING T/F (S) ICT (MV) 60089TSR1 ISOLATOR OPEN/CLOSE DPS
56 38.5KV COUPLING T/F (S) ICT (MV) 60089TSR2 ISOLATOR OPEN/CLOSE DPS
57 38.5KV COUPLING T/F (S) ICT (MV) 60089TSY1 ISOLATOR OPEN/CLOSE DPS
58 38.5KV COUPLING T/F (S) ICT (MV) 60089TSY2 ISOLATOR OPEN/CLOSE DPS
59 38.5KV COUPLING T/F (S) ICT (MV) 60089TSB1 ISOLATOR OPEN/CLOSE DPS
60 38.5KV COUPLING T/F (S) ICT (MV) 60089TSB2 ISOLATOR OPEN/CLOSE DPS
61 38.5KV COUPLING T/F (S) ICT (MV) 60089TR1E EARTH SWITCH OPEN/CLOSE DPS
62 38.5KV COUPLING T/F (S) ICT (MV) 60089TR2E EARTH SWITCH OPEN/CLOSE DPS
63 38.5KV COUPLING T/F (S) ICT (MV) 60089TY1E EARTH SWITCH OPEN/CLOSE DPS
64 38.5KV COUPLING T/F (S) ICT (MV) 60089TY2E EARTH SWITCH OPEN/CLOSE DPS
65 38.5KV COUPLING T/F (S) ICT (MV) 60089TB1E EARTH SWITCH OPEN/CLOSE DPS
66 38.5KV COUPLING T/F (S) ICT (MV) 60089TB2E EARTH SWITCH OPEN/CLOSE DPS
67 38.5KV COUPLING T/F (S) ICT (MV) 60089TSR1E EARTH SWITCH OPEN/CLOSE DPS
68 38.5KV COUPLING T/F (S) ICT (MV) 60089TSR2E EARTH SWITCH OPEN/CLOSE DPS
69 38.5KV MV BUS BAR 60089E EARTH SWITCH OPEN/CLOSE DPS
70 38.5KV STATCOM- 1 STATCOM VSC 60152 CB OPEN/CLOSE DPS
71 38.5KV STATCOM- 1 STATCOM VSC 60152BP BYPASS CB OPEN/CLOSE DPS
72 38.5KV STATCOM- 1 STATCOM VSC 60189A ISOLATOR OPEN/CLOSE DPS
73 38.5KV STATCOM- 1 STATCOM VSC 60189AE EARTH SWITCH OPEN/CLOSE DPS
74 38.5KV STATCOM- 2 STATCOM VSC 60252 CB OPEN/CLOSE DPS
75 38.5KV STATCOM- 2 STATCOM VSC 60252BP BYPASS CB OPEN/CLOSE DPS
76 38.5KV STATCOM- 2 STATCOM VSC 60289A ISOLATOR OPEN/CLOSE DPS
77 38.5KV STATCOM- 2 STATCOM VSC 60289AE EARTH SWITCH OPEN/CLOSE DPS
78 38.5KV MSC 60352 CB OPEN/CLOSE DPS
79 38.5KV MSC 60389A ISOLATOR OPEN/CLOSE DPS
80 38.5KV MSC 60389AE EARTH SWITCH OPEN/CLOSE DPS
81 38.5KV MSR- 1 60452 CB OPEN/CLOSE DPS
82 38.5KV MSR- 1 60489A ISOLATOR OPEN/CLOSE DPS
83 38.5KV MSR- 1 60489AE EARTH SWITCH OPEN/CLOSE DPS
84 38.5KV MSR- 2 60552 CB OPEN/CLOSE DPS
85 38.5KV MSR- 2 60589A ISOLATOR OPEN/CLOSE DPS
86 38.5KV MSR- 2 60589AE EARTH SWITCH OPEN/CLOSE DPS
87 38.5KV AUX T/F 60652 CB OPEN/CLOSE DPS
88 38.5KV AUX T/F 60689A ISOLATOR OPEN/CLOSE DPS
89 38.5KV AUX T/F 60689AE EARTH SWITCH OPEN/CLOSE DPS
90 33KV AUX TERTIARY 33KV ISOLATOR ISOLATOR OPEN/CLOSE DPS
91 33KV AUX TERTIARY 33KV CB CB OPEN/CLOSE DPS
92 415 V AUX MSB INCOMER-1 INCOMER-1 ON/OFF DPS
93 415 V AUX MSB BUS COUPLER BUS COUPLER ON/OFF DPS
94 415 V AUX MSB INCOMER-2 INCOMER-2 ON/OFF DPS
95 415 V AUX ACDB INCOMER-1 INCOMER-1 ON/OFF DPS
96 415 V AUX ACDB BUS COUPLER BUS COUPLER ON/OFF DPS
97 415 V AUX ACDB INCOMER-2 INCOMER-2 ON/OFF DPS
98 415 V AUX DG SET DG INCOMER CB ON/OFF DPS
STATCOM (HYOSUNG)
1 ABC COUPLING TRANSFORMER (HV) 52 CB OPEN/CLOSE DPS
2 ABC COUPLING TRANSFORMER (HV) 89A ISOLATOR OPEN/CLOSE DPS
3 ABC COUPLING TRANSFORMER (HV) 89AE EARTH SWITCH OPEN/CLOSE DPS
4 ABC COUPLING TRANSFORMER (HV) 89B ISOLATOR OPEN/CLOSE DPS
5 ABC COUPLING TRANSFORMER (HV) 89BE EARTH SWITCH OPEN/CLOSE DPS
6 ABC COUPLING TRANSFORMER (HV) 89TR ISOLATOR OPEN/CLOSE DPS
7 ABC COUPLING TRANSFORMER (HV) 89TRE EARTH SWITCH OPEN/CLOSE DPS
8 ABC COUPLING TRANSFORMER (HV) 89TSR ISOLATOR OPEN/CLOSE DPS
9 ABC COUPLING TRANSFORMER (HV) 89TY ISOLATOR OPEN/CLOSE DPS
10 ABC COUPLING TRANSFORMER (HV) 89TYE EARTH SWITCH OPEN/CLOSE DPS
11 ABC COUPLING TRANSFORMER (HV) 89TSY ISOLATOR OPEN/CLOSE DPS
12 ABC COUPLING TRANSFORMER (HV) 89TB ISOLATOR OPEN/CLOSE DPS
13 ABC COUPLING TRANSFORMER (HV) 89TBE EARTH SWITCH OPEN/CLOSE DPS
14 ABC COUPLING TRANSFORMER (HV) 89TSB ISOLATOR OPEN/CLOSE DPS
15 ABC COUPLING TRANSFORMER (HV) 89TSBE EARTH SWITCH OPEN/CLOSE DPS
16 20KV COUPLING TRANSFORMER (MV) 89TR ISOLATOR OPEN/CLOSE DPS
17 20KV COUPLING TRANSFORMER (MV) 89TY ISOLATOR OPEN/CLOSE DPS
18 20KV COUPLING TRANSFORMER (MV) 89TB ISOLATOR OPEN/CLOSE DPS
19 20KV COUPLING TRANSFORMER (MV) 89TSR ISOLATOR OPEN/CLOSE DPS
20 20KV COUPLING TRANSFORMER (MV) 89TSY ISOLATOR OPEN/CLOSE DPS
21 20KV COUPLING TRANSFORMER (MV) 89TSB ISOLATOR OPEN/CLOSE DPS
22 20KV COUPLING TRANSFORMER (MV) 89TER EARTH SWITCH OPEN/CLOSE DPS
23 20KV COUPLING TRANSFORMER (MV) 89TEY EARTH SWITCH OPEN/CLOSE DPS
24 20KV COUPLING TRANSFORMER (MV) 89TEB EARTH SWITCH OPEN/CLOSE DPS
25 20KV COUPLING TRANSFORMER (MV) TSER EARTH SWITCH OPEN/CLOSE DPS
26 20KV STATCOM-1 VSC-1 52 CB OPEN/CLOSE DPS
27 20KV STATCOM-1 VSC-1 89A ISOLATOR OPEN/CLOSE DPS
28 20KV STATCOM-1 VSC-1 89AE EARTH SWITCH OPEN/CLOSE DPS
29 20KV STATCOM-1 VSC-1 89B ISOLATOR OPEN/CLOSE DPS
30 20KV STATCOM-1 VSC-1 89BE1 EARTH SWITCH OPEN/CLOSE DPS
31 20KV STATCOM-1 VSC-1 89BE2 EARTH SWITCH OPEN/CLOSE DPS
32 20KV STATCOM-2 VSC-2 52 CB OPEN/CLOSE DPS
33 20KV STATCOM-2 VSC-2 89A ISOLATOR OPEN/CLOSE DPS
34 20KV STATCOM-2 VSC-2 89AE EARTH SWITCH OPEN/CLOSE DPS
35 20KV STATCOM-2 VSC-2 89B ISOLATOR OPEN/CLOSE DPS
36 20KV STATCOM-2 VSC-2 89BE1 EARTH SWITCH OPEN/CLOSE DPS
37 20KV STATCOM-2 VSC-2 89BE2 EARTH SWITCH OPEN/CLOSE DPS
38 20KV GND T/F 89 ISOLATOR OPEN/CLOSE DPS
39 20KV GND T/F 89E EARTH SWITCH OPEN/CLOSE DPS
40 20KV BUS PT 89E1 EARTH SWITCH OPEN/CLOSE DPS
41 20KV BUS PT 89 ISOLATOR OPEN/CLOSE DPS
42 20KV BUS PT 89E2 EARTH SWITCH OPEN/CLOSE DPS
43 20KV AUX.T/F 89 ISOLATOR OPEN/CLOSE DPS
44 20KV AUX.T/F 89E EARTH SWITCH OPEN/CLOSE DPS
45 20KV AUX.T/F 52 CB OPEN/CLOSE DPS
46 33KV AUX.T/F TERTIARY 52 CB OPEN / CLOSE DPS
47 33KV AUX.T/F TERTIARY 89 89 OPEN / CLOSE DPS
48 415 V LTSUP MSB-1 INCOMER-1 OPEN/CLOSE DPS
49 415 V LTSUP MSB-2 INCOMER-2 OPEN/CLOSE DPS
50 415 V LTSUP MSB-BC BUS COUPLER OPEN/CLOSE DPS
51 415 V LTSUP ACDB-1 INCOMER-1 OPEN/CLOSE DPS
52 415 V LTSUP ACDB-2 INCOMER-2 OPEN/CLOSE DPS
53 415 V LTSUP DGSET DG SET CB OPEN DPS
54 415 V LTSUP ACDB-BC BUS COUPLER OPEN/CLOSE DPS
55 20KV MSR-1 89A ISOLATOR OPEN/CLOSE DPS
56 20KV MSR-1 89AE EARTH SWITCH OPEN/CLOSE DPS
57 20KV MSR-1 52 CB OPEN/CLOSE DPS
58 20KV MSR-1 89B ISOLATOR OPEN/CLOSE DPS
59 20KV MSR-1 89BE1 EARTH SWITCH OPEN/CLOSE DPS
60 20KV MSR-1 89BE2 EARTH SWITCH OPEN/CLOSE DPS
61 20KV MSR-2 89A ISOLATOR OPEN/CLOSE DPS
62 20KV MSR-2 89AE EARTH SWITCH OPEN/CLOSE DPS
63 20KV MSR-2 52 CB OPEN/CLOSE DPS
64 20KV MSR-2 89B ISOLATOR OPEN/CLOSE DPS
65 20KV MSR-2 89BE1 EARTH SWITCH OPEN/CLOSE DPS
66 20KV MSR-2 89BE2 EARTH SWITCH OPEN/CLOSE DPS
67 20KV MSC 89A ISOLATOR OPEN/CLOSE DPS
68 20KV MSC 89AE EARTH SWITCH OPEN/CLOSE DPS
69 20KV MSC 52 CB OPEN/CLOSE DPS
70 20KV MSC 89B ISOLATOR OPEN/CLOSE DPS
71 20KV MSC 89BE1 EARTH SWITCH OPEN/CLOSE DPS
72 20KV MSC 89BE2 EARTH SWITCH OPEN/CLOSE DPS
73 ABC FUTURE 89A ISOLATOR OPEN/CLOSE DPS
74 ABC FUTURE 89AE EARTH SWITCH OPEN/CLOSE DPS
75 ABC FUTURE & STATCOM TIE 52 CB OPEN/CLOSE DPS
76 ABC FUTURE & STATCOM TIE 89A ISOLATOR OPEN/CLOSE DPS
77 ABC FUTURE & STATCOM TIE 89AE EARTH SWITCH OPEN/CLOSE DPS
78 ABC FUTURE & STATCOM TIE 89B ISOLATOR OPEN/CLOSE DPS
79 ABC FUTURE & STATCOM TIE 89BE EARTH SWITCH OPEN/CLOSE DPS
Sl.NO BAY NUM. BAY NAME DEVICE ID SIGNAL DESCRIPTION SCADA ID DATA TYPE REMARK
LINE FEEDER (ONE AND HALF BREAKER SCHEME)
1 ABC LINE FEEDER CB CB OPEN / CLOSE COMMAND STTS DPC
2 ABC LINE FEEDER CB AUTO RECLOSE TO AUTO / NON-AUTO MODE ARNA DPC
3 ABC LINE FEEDER 89A ISOLATOR OPEN / CLOSE COMMAND STTS DPC
4 ABC LINE FEEDER 89B ISOLATOR OPEN / CLOSE COMMAND STTS DPC
5 ABC LINE FEEDER 89L ISOLATOR OPEN / CLOSE COMMAND STTS DPC
SWITCHEABLE LINE REACTOR
1 ABC LINE FEEDER WITH SW REACTOR 52R CB OPEN/CLOSE COMMAND STTS DPC
2 ABC LINE FEEDER WITH SW REACTOR 89RR ISOLATOR OPEN / CLOSE COMMAND STTS DPC
3 ABC LINE FEEDER WITH SW REACTOR 89RY ISOLATOR OPEN / CLOSE COMMAND STTS DPC
4 ABC LINE FEEDER WITH SW REACTOR 89RB ISOLATOR OPEN / CLOSE COMMAND STTS DPC
5 ABC LINE FEEDER WITH SW REACTOR 89RS1R ISOLATOR OPEN / CLOSE COMMAND STTS DPC
6 ABC LINE FEEDER WITH SW REACTOR 89RS1Y ISOLATOR OPEN / CLOSE COMMAND STTS DPC
7 ABC LINE FEEDER WITH SW REACTOR 89RS1B ISOLATOR OPEN / CLOSE COMMAND STTS DPC
1 ABC LINE FEEDER WITH SW REACTOR NGR BYPASS CB OPEN / CLOSE COMMAND STTS DPC
TIE/ BUS SECTION
1 ABC TIE/ BS CB CB OPEN / CLOSE / CLOSE COMMAND STTS DPC
2 ABC TIE/ BS CB AUTO RECLOSE TO AUTO / NON-AUTO MODE ARNA DPC
3 ABC TIE/ BS 89A ISOLATOR OPEN / CLOSE COMMAND STTS DPC
4 ABC TIE/ BS 89B ISOLATOR OPEN / CLOSE COMMAND STTS DPC
1 ABC FUTURE LINE 89A ISOLATOR OPEN/CLOSE COMMAND STTS DPC
765 KV BUS REACTOR (ONE AND HALF BREAKER SCHEME)
1 ABC BUS REACTOR 89A ISOLATOR OPEN/CLOSE COMMAND STTS DPC
2 ABC BUS REACTOR 89B ISOLATOR OPEN/CLOSE COMMAND STTS DPC
3 ABC BUS REACTOR 89RR ISOLATOR OPEN / CLOSE COMMAND STTS DPC
4 ABC BUS REACTOR 89RY ISOLATOR OPEN / CLOSE COMMAND STTS DPC
5 ABC BUS REACTOR 89RB ISOLATOR OPEN / CLOSE COMMAND STTS DPC
6 ABC BUS REACTOR 89RS1R ISOLATOR OPEN / CLOSE COMMAND STTS DPC
7 ABC BUS REACTOR 89RS1Y ISOLATOR OPEN / CLOSE COMMAND STTS DPC
8 ABC BUS REACTOR 89RS1B ISOLATOR OPEN / CLOSE COMMAND STTS DPC
ICT (ONE & HALF BREAKER SCHEME)
1 ABC ICT CB CB OPEN / CLOSE COMMAND STTS DPC
2 ABC ICT 89A ISOLATOR OPEN/CLOSE COMMAND STTS DPC
3 ABC ICT 89B ISOLATOR OPEN/CLOSE COMMAND STTS DPC
4 ABC ICT 89TR ISOLATOR OPEN / CLOSE COMMAND STTS DPC
5 ABC ICT 89TY ISOLATOR OPEN / CLOSE COMMAND STTS DPC
6 ABC ICT 89TB ISOLATOR OPEN / CLOSE COMMAND STTS DPC
7 ABC ICT 89TS1R ISOLATOR OPEN / CLOSE COMMAND STTS DPC
8 ABC ICT 89TS1Y ISOLATOR OPEN / CLOSE COMMAND STTS DPC
9 ABC ICT 89TS1B ISOLATOR OPEN / CLOSE COMMAND STTS DPC
LINE SERIES REACTOR/ BUS SERIES REACTOR
1 ABC LSR/BSR CB CB OPEN / CLOSE / CLOSE COMMAND STTS DPC
2 ABC LSR/BSR 89A ISOLATOR OPEN / CLOSE COMMAND STTS DPC
3 ABC LSR/BSR 89B ISOLATOR OPEN / CLOSE COMMAND STTS DPC
4 ABC LSR/BSR 89L/ 89BSR ISOLATOR OPEN / CLOSE COMMAND STTS DPC
5 ABC LSR 89LSR ISOLATOR OPEN/CLOSE COMMAND STTS DPC
6 ABC LSR 89LSR1 ISOLATOR OPEN / CLOSE COMMAND STTS DPC
7 ABC LSR 89LSR2 ISOLATOR OPEN / CLOSE COMMAND STTS DPC
FIXED SERIES CAPACITOR (FSC)
1 ABC FSC 52BBR BPCB OPEN/CLOSE CMD DPC
2 ABC FSC 89MBS BYPASS MBS OPEN/CLOSE CMD DPC
3 ABC FSC 89DS1 BYPASS CAP ISO 1 OPEN/CLOSE CMD DPC
4 ABC FSC 89DS2 BYPASS CAP ISO 2 OPEN/CLOSE CMD DPC
ICT (DOUBLE MAIN SCHEME)
1 ABC ICT CB CB OPEN / CLOSE COMMAND STTS DPC
2 ABC ICT 89A ISOLATOR OPEN/CLOSE COMMAND STTS DPC
3 ABC ICT 89B ISOLATOR OPEN/CLOSE COMMAND STTS DPC
4 ABC ICT 89T ISOLATOR OPEN / CLOSE COMMAND STTS DPC
5 ABC ICT CB CB OPEN / CLOSE COMMAND STTS DPC
6 ABC ICT 89A ISOLATOR OPEN/CLOSE COMMAND STTS DPC
7 ABC ICT 89B ISOLATOR OPEN/CLOSE COMMAND STTS DPC
8 ABC ICT 89T ISOLATOR OPEN / CLOSE COMMAND STTS DPC
LINE FEEDER (DOUBLE MAIN SCHEME)
1 ABC LINE FEEDER CB CB OPEN / CLOSE COMMAND STTS DPC
2 ABC LINE FEEDER 89A ISOLATOR OPEN/CLOSE COMMAND STTS DPC
3 ABC LINE FEEDER 89B ISOLATOR OPEN/CLOSE COMMAND STTS DPC
4 ABC LINE FEEDER 89L ISOLATOR OPEN / CLOSE COMMAND STTS DPC
5 ABC LINE FEEDER CB CB OPEN / CLOSE COMMAND STTS DPC
6 ABC LINE FEEDER 89A ISOLATOR OPEN/CLOSE COMMAND STTS DPC
7 ABC LINE FEEDER 89B ISOLATOR OPEN/CLOSE COMMAND STTS DPC
8 ABC LINE FEEDER 89L ISOLATOR OPEN / CLOSE COMMAND STTS DPC
ICT (DOUBLE MAIN & TRANSFER SCHEME)
1 ABC ICT CB CB OPEN / CLOSE / CLOSE COMMAND STTS DPC
2 ABC ICT 89A ISOLATOR OPEN / CLOSE COMMAND STTS DPC
3 ABC ICT 89B ISOLATOR OPEN / CLOSE COMMAND STTS DPC
4 ABC ICT 89T ISOLATOR OPEN / CLOSE COMMAND STTS DPC
5 ABC ICT 89L ISOLATOR OPEN / CLOSE COMMAND STTS DPC
LINE FEEDER (DOUBLE MAIN & TRANSFER SCHEME)
1 ABC LINE FEEDER CB CB OPEN / CLOSE / CLOSE COMMAND STTS DPC
2 ABC LINE FEEDER CB AUTO RECLOSE TO AUTO / NON-AUTO MODE DPC
3 ABC LINE FEEDER 89A ISOLATOR OPEN / CLOSE COMMAND STTS DPC
4 ABC LINE FEEDER 89B ISOLATOR OPEN / CLOSE COMMAND STTS DPC
5 ABC LINE FEEDER 89T ISOLATOR OPEN / CLOSE COMMAND STTS DPC
6 ABC LINE FEEDER 89L ISOLATOR OPEN / CLOSE COMMAND STTS DPC
BUS COUPLER ( DMT SCHEME)
1 ABC BUS COUPLER CB CB OPEN / CLOSE / CLOSE COMMAND STTS DPC
2 ABC BUS COUPLER 89A ISOLATOR OPEN / CLOSE COMMAND STTS DPC
3 ABC BUS COUPLER 89B ISOLATOR OPEN / CLOSE COMMAND STTS DPC
TRANSFER BUS COUPLER
1 ABC TRANSFER BUS COUPLER CB CB OPEN / CLOSE / CLOSE COMMAND DPC
2 ABC TRANSFER BUS COUPLER 89A ISOLATOR OPEN / CLOSE COMMAND STTS DPC
3 ABC TRANSFER BUS COUPLER 89B ISOLATOR OPEN / CLOSE COMMAND STTS DPC
4 ABC TRANSFER BUS COUPLER 89T ISOLATOR OPEN / CLOSE COMMAND STTS DPC
ICT (SINGLE MAIN & TRANSFER SCHEME)
1 ABC ICT CB CB OPEN / CLOSE / CLOSE COMMAND STTS DPC
2 ABC ICT 89A ISOLATOR OPEN / CLOSE COMMAND STTS DPC
3 ABC ICT 89B ISOLATOR OPEN / CLOSE COMMAND STTS DPC
4 ABC ICT 89T ISOLATOR OPEN / CLOSE COMMAND STTS DPC
5 ABC ICT 89L ISOLATOR OPEN / CLOSE COMMAND STTS DPC
BUS COUPLER ( SINGLE MAIN & TRANSFER SCHEME)
1 ABC BUS COUPLER CB CB OPEN / CLOSE / CLOSE COMMAND STTS DPC
2 ABC BUS COUPLER 89A ISOLATOR OPEN / CLOSE COMMAND STTS DPC
3 ABC BUS COUPLER 89B ISOLATOR OPEN / CLOSE COMMAND STTS DPC
4 ABC BUS COUPLER 89T ISOLATOR OPEN / CLOSE COMMAND STTS DPC
5 ABC BUS COUPLER 89L ISOLATOR OPEN / CLOSE COMMAND STTS DPC
LINE FEEDER ( SINGLE MAIN & TRANSFER SCHEME)
1 ABC LINE FEEDER CB CB OPEN / CLOSE / CLOSE COMMAND STTS DPC
2 ABC LINE FEEDER 89A ISOLATOR OPEN / CLOSE COMMAND STTS DPC
3 ABC LINE FEEDER 89B ISOLATOR OPEN / CLOSE COMMAND STTS DPC
4 ABC LINE FEEDER 89T ISOLATOR OPEN / CLOSE COMMAND STTS DPC
5 ABC LINE FEEDER 89L ISOLATOR OPEN / CLOSE COMMAND STTS DPC
AUXILIARY SYSTEM
1 415 V RTU I/O_RACK-1 DUMMY BREAKER OPEN COMMAND DPC
2 415 V RTU I/O_RACK-1 DUMMY BREAKER CLOSE COMMAND DPC
3 415 V DG Set DGSET-1 DG SET CB OPEN COMMAND DPC
4 415 V DG Set DGSET-1 DG SET CB CLOSE COMMAND DPC
5 33 KV LTSUP TERTIARY CB OPEN COMMAND DPC
6 33 KV LTSUP TERTIARY CB CLOSE COMMAND DPC
7 33 KV LTSUP TERTIARY ISO OPEN COMMAND DPC
8 33 KV LTSUP TERTIARY ISO CLOSE COMMAND DPC
STATCOM (SIEMENS)
1 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89A HV Main Bay 89A Isolator Open DPC
2 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89A HV Main Bay 89A Isolator Close DPC
3 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89B HV Main Bay 89B Isolator Open DPC
4 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89B HV Main Bay 89B Isolator Close DPC
5 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-52 HV Main Bay CB Open DPC
6 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-52 HV Main Bay CB Close DPC
7 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q2 R PH ISOLATOR OPEN DPC
8 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q2 R PH ISOLATOR CLOSED DPC
9 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q2 Y PH ISOLATOR OPEN DPC
10 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q2 Y PH ISOLATOR CLOSED DPC
11 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q2 B PH ISOLATOR OPEN DPC
12 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q2 B PH ISOLATOR CLOSED DPC
13 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q3-R-PH ISOLATOR OPEN DPC
14 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q3-R-PH ISOLATOR CLOSED DPC
15 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q3-Y-PH ISOLATOR OPEN DPC
16 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q3-Y-PH ISOLATOR CLOSED DPC
17 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q3-B-PH ISOLATOR OPEN DPC
18 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q3-B-PH ISOLATOR CLOSED DPC
19 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-89A ISOLATOR OPEN DPC
20 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-89A ISOLATOR CLOSE DPC
21 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-89B ISOLATOR OPEN DPC
22 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-89B ISOLATOR CLOSE DPC
23 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-52 CB OPEN DPC
24 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-52 CB CLOSE DPC
25 4ZZ FUTURE HV Future Bay 89A Isolator Open DPC
26 4ZZ FUTURE HV Future Bay 89A Isolator Close DPC
27 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q1 R PH MV ISOLATOR OPEN DPC
28 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q1 R PH MV ISOLATOR CLOSED DPC
29 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q1 Y PH MV ISOLATOR OPEN DPC
30 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q1 Y PH MV ISOLATOR CLOSED DPC
31 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q1 B PH MV ISOLATOR OPEN DPC
32 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q1 B PH MV ISOLATOR CLOSED DPC
33 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q2 R PH MV ISOLATOR OPEN DPC
34 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q2 R PH MV ISOLATOR CLOSED DPC
35 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q2 Y PH MV ISOLATOR OPEN DPC
36 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q2 Y PH MV ISOLATOR CLOSED DPC
37 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q2 B PH MV ISOLATOR OPEN DPC
38 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q2 B PH MV ISOLATOR CLOSED DPC
39 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q12 R PH MV ISOLATOR OPEN DPC
40 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q12 R PH MV ISOLATOR CLOSED DPC
41 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q12 Y PH MV ISOLATOR OPEN DPC
42 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q12 Y PH MV ISOLATOR CLOSED DPC
43 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q12 B PH MV ISOLATOR OPEN DPC
44 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q12 B PH MV ISOLATOR CLOSED DPC
45 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q13 R PH MV ISOLATOR OPEN DPC
46 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q13 R PH MV ISOLATOR CLOSED DPC
47 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q13 Y PH MV ISOLATOR OPEN DPC
48 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q13 Y PH MV ISOLATOR CLOSED DPC
49 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q13 B PH MV ISOLATOR OPEN DPC
50 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q13 B PH MV ISOLATOR CLOSED DPC
51 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER J01-Q0 AUXILIARY SUPPLY CIRCUIT BREAKER OPEN DPC
52 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER J01-Q0 AUXILIARY SUPPLY CIRCUIT BREAKER CLOSED DPC
53 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER J01-Q1 AUXILIARY SUPPLY ISOLATOR OPEN DPC
54 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER J01-Q1 AUXILIARY SUPPLY ISOLATOR CLOSED DPC
55 J11 STATCOM VSC-1 BAY VSC-2 MV-J12 CIRCUIT BREAKER OPEN DPC
56 J11 STATCOM VSC-1 BAY MSR-1 MV-J21 CIRCUIT BREAKER CLOSED DPC
57 J11 STATCOM VSC-1 BAY MSR-2 MV-J22 ISOLATOR SWITCH OPEN DPC
58 J11 STATCOM VSC-1 BAY MSC-1 MV-J31 ISOLATOR SWITCH CLOSED DPC
59 J12 STATCOM VSC-2 BAY MSR-1 MV-J21 CIRCUIT BREAKER OPEN DPC
60 J12 STATCOM VSC-2 BAY MSR-2 MV-J22 CIRCUIT BREAKER CLOSED DPC
61 J12 STATCOM VSC-2 BAY MSC-1 MV-J31 ISOLATOR SWITCH OPEN DPC
62 J12 STATCOM VSC-2 BAY MSC-2 MV-J32 ISOLATOR SWITCH CLOSED DPC
63 J21 STATCOM MSR-1 BAY MSR-2 MV-J22 CIRCUIT BREAKER OPEN DPC
64 J21 STATCOM MSR-1 BAY MSC-1 MV-J31 CIRCUIT BREAKER CLOSED DPC
65 J21 STATCOM MSR-1 BAY MSC-2 MV-J32 ISOLATOR SWITCH OPEN DPC
66 J21 STATCOM MSR-1 BAY MSR-1 J21 Q1 ISOLATOR SWITCH CLOSED DPC
67 J22 STATCOM MSR-2 BAY MSR-2 J22 Q0 CIRCUIT BREAKER OPEN DPC
68 J22 STATCOM MSR-2 BAY MSR-2 J22 Q0 CIRCUIT BREAKER CLOSED DPC
69 J22 STATCOM MSR-2 BAY MSR-2 J22 Q1 ISOLATOR SWITCH OPEN DPC
70 J22 STATCOM MSR-2 BAY MSR-2 J22 Q1 ISOLATOR SWITCH CLOSED DPC
71 J31 STATCOM MSC-1 BAY MSC-1 J31 Q0 CIRCUIT BREAKER OPEN DPC
72 J31 STATCOM MSC-1 BAY MSC-1 J31 Q0 CIRCUIT BREAKER CLOSED DPC
73 J31 STATCOM MSC-1 BAY MSC-1 J31 Q1 ISOLATOR SWITCH OPEN DPC
74 J31 STATCOM MSC-1 BAY MSC-1 J31 Q1 ISOLATOR SWITCH CLOSED DPC
75 J32 STATCOM MSC-2 BAY MSC-2 J32 Q0 CIRCUIT BREAKER OPEN DPC
76 J32 STATCOM MSC-2 BAY MSC-2 J32 Q0 CIRCUIT BREAKER CLOSED DPC
77 J32 STATCOM MSC-2 BAY MSC-2 J32 Q1 ISOLATOR SWITCH OPEN DPC
78 J32 STATCOM MSC-2 BAY MSC-2 J32 Q1 ISOLATOR SWITCH CLOSED DPC
79 STATCOM STATCOM STATCOM OPERATION STATCOM AUTOMATIC CONTROL CMD DPC
80 STATCOM STATCOM STATCOM OPERATION STATCOM MANUAL CONTROL CMD DPC
81 STATCOM STATCOM STATCOM OPERATION REACTIVE POWER CONTROL MODE ENABLE CMD DPC
82 STATCOM STATCOM STATCOM OPERATION REACTIVE POWER CONTROL MODE DISABLE CMD DPC
83 STATCOM STATCOM STATCOM OPERATION GAIN ADJUSTMENT AUTOMATIC CMD DPC
84 STATCOM STATCOM STATCOM OPERATION GAIN ADJUSTMENT MANUAL CMD DPC
85 STATCOM STATCOM STATCOM OPERATION NPS ON CMD DPC
86 STATCOM STATCOM STATCOM OPERATION NPS OFF CMD DPC
87 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICES HV AUTOMATIC DPC
88 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICES HV OFF DPC
89 STATCOM STATCOM STATCOM OPERATION AUTO-RESTART ON SELECTED DPC
90 STATCOM STATCOM STATCOM OPERATION AUTO-RESTART OFF SELECTED DPC
91 STATCOM STATCOM STATCOM OPERATION SELECT SYSTEM 1 ACTIVE DPC
92 STATCOM STATCOM STATCOM OPERATION SELECT SYSTEM 2 ACTIVE DPC
93 STATCOM STATCOM STATCOM OPERATION UNEQUAL LOAD SHARING MODE ON CMD DPC
94 STATCOM STATCOM STATCOM OPERATION UNEQUAL LOAD SHARING MODE OFF CMD DPC
95 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV1 PSD BYPASS COMMAND DPC
96 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV1 PSD ON COMMAND DPC
97 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV2 PSD BYPASS COMMAND DPC
98 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV2 PSD ON COMMAND DPC
99 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV3 PSD BYPASS COMMAND DPC
100 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV3 PSD ON COMMAND DPC
101 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV4 PSD BYPASS COMMAND DPC
102 STATCOM STATCOM STATCOM OPERATION EXTERNAL DEVICE LV4 PSD ON COMMAND DPC
1 XX KV FUTURE BAY 89A ISOLATOR OPEN COMMAND DPC
2 XX KV FUTURE BAY 89A ISOLATOR CLOSE COMMAND DPC
3 XX KV FUTURE& COUPLING T/F-1 TIE 52 CB OPEN COMMAND DPC
4 XX KV FUTURE& COUPLING T/F-1 TIE 52 CB CLOSE COMMAND DPC
5 XX KV FUTURE& COUPLING T/F-1 TIE 89A 89A OPEN COMMAND DPC
6 XX KV FUTURE& COUPLING T/F-1 TIE 89A 89A CLOSE COMMAND DPC
7 XX KV FUTURE& COUPLING T/F-1 TIE 89B 89B OPEN COMMAND DPC
8 XX KV FUTURE& COUPLING T/F-1 TIE 89B 89B CLOSE COMMAND DPC
9 XX KV COUPLING TRANSFORMER (HV) 52 CB OPEN COMMAND DPC
10 XX KV COUPLING TRANSFORMER (HV) 52 CB CLOSE COMMAND DPC
11 XX KV COUPLING TRANSFORMER (HV) 89A ISOLATOR OPEN COMMAND DPC
12 XX KV COUPLING TRANSFORMER (HV) 89A ISOLATOR CLOSE COMMAND DPC
13 XX KV COUPLING TRANSFORMER (HV) 89 ISOLATOR OPEN COMMAND DPC
14 XX KV COUPLING TRANSFORMER (HV) 89 ISOLATOR CLOSE COMMAND DPC
15 XX KV COUPLING TRANSFORMER (HV) 89TR ISOLATOR OPEN COMMAND DPC
16 XX KV COUPLING TRANSFORMER (HV) 89TR ISOLATOR CLOSE COMMAND DPC
17 XX KV COUPLING TRANSFORMER (HV) 89TSR ISOLATOR OPEN COMMAND DPC
18 XX KV COUPLING TRANSFORMER (HV) 89TSR ISOLATOR CLOSE COMMAND DPC
19 XX KV COUPLING TRANSFORMER (HV) 89TY ISOLATOR OPEN COMMAND DPC
20 XX KV COUPLING TRANSFORMER (HV) 89TY ISOLATOR CLOSE COMMAND DPC
21 XX KV COUPLING TRANSFORMER (HV) 89TSY ISOLATOR OPEN COMMAND DPC
22 XX KV COUPLING TRANSFORMER (HV) 89TSY ISOLATOR CLOSE COMMAND DPC
23 XX KV COUPLING TRANSFORMER (HV) 89TB ISOLATOR OPEN COMMAND DPC
24 XX KV COUPLING TRANSFORMER (HV) 89TB ISOLATOR CLOSE COMMAND DPC
25 XX KV COUPLING TRANSFORMER (HV) 89TSB ISOLATOR OPEN COMMAND DPC
26 XX KV COUPLING TRANSFORMER (HV) 89TSB ISOLATOR CLOSE COMMAND DPC
27 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) TAP CHANGER LOWER COMMAND DPC
28 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) TAP CHANGER RAISE COMMAND DPC
29 38.5KV COUPLING T/F (S) ICT (MV) 60089TR1 ISOLATOR OPEN/CLOSE DPC
30 38.5KV COUPLING T/F (S) ICT (MV) 60089TR2 ISOLATOR OPEN/CLOSE DPC
31 38.5KV COUPLING T/F (S) ICT (MV) 60089TY1 ISOLATOR OPEN/CLOSE DPC
32 38.5KV COUPLING T/F (S) ICT (MV) 60089TY2 ISOLATOR OPEN/CLOSE DPC
33 38.5KV COUPLING T/F (S) ICT (MV) 60089TB1 ISOLATOR OPEN/CLOSE DPC
34 38.5KV COUPLING T/F (S) ICT (MV) 60089TB2 ISOLATOR OPEN/CLOSE DPC
35 38.5KV COUPLING T/F (S) ICT (MV) 60089TSR1 ISOLATOR OPEN/CLOSE DPC
36 38.5KV COUPLING T/F (S) ICT (MV) 60089TSR2 ISOLATOR OPEN/CLOSE DPC
37 38.5KV COUPLING T/F (S) ICT (MV) 60089TSY1 ISOLATOR OPEN/CLOSE DPC
38 38.5KV COUPLING T/F (S) ICT (MV) 60089TSY2 ISOLATOR OPEN/CLOSE DPC
39 38.5KV COUPLING T/F (S) ICT (MV) 60089TSB1 ISOLATOR OPEN/CLOSE DPC
40 38.5KV COUPLING T/F (S) ICT (MV) 60089TSB2 ISOLATOR OPEN/CLOSE DPC
41 38.5KV STATCOM- 1 STATCOM VSC 60189A ISOLATOR OPEN/CLOSE DPC
42 38.5KV STATCOM- 1 60152 CB OPEN/CLOSE DPC
43 38.5KV STATCOM- 1 VSC-1 STATCOM-1 COOLING SYSTEM COMMAND DPC
44 38.5KV STATCOM- 2 STATCOM VSC 60289A ISOLATOR OPEN/CLOSE DPC
45 38.5KV STATCOM- 2 60252 CB OPEN / CLOSE DPC
46 38.5KV STATCOM- 2 VSC-2 STATCOM-2 COOLING SYSTEM COMMAND DPC
47 38.5KV MSC 60352 CB OPEN/CLOSE DPC
48 38.5KV MSC 60389A ISOLATOR OPEN/CLOSE DPC
49 38.5KV MSR- 1 60452 CB OPEN/CLOSE DPC
50 38.5KV MSR- 1 60489A ISOLATOR OPEN/CLOSE DPC
51 38.5KV MSR- 2 60552 CB OPEN/CLOSE DPC
52 38.5KV MSR- 2 60589A ISOLATOR OPEN/CLOSE DPC
53 38.5KV AUX T/F 60652 CB OPEN/CLOSE DPC
54 38.5KV AUX T/F 60689A ISOLATOR OPEN/CLOSE DPC
55 33KV AUX TERTIARY 33KV ISOLATOR ISOLATOR OPEN/CLOSE DPC
56 33KV AUX TERTIARY 33KV CB CB OPEN/CLOSE DPC
57 415 V AUX MSB INCOMER-1 INCOMER-1 ON/OFF DPC
58 415 V AUX MSB BUS COUPLER BUSCOUPLER ON/OFF DPC
59 415 V AUX MSB INCOMER-2 INCOMER-2 ON/OFF DPC
60 415 V AUX ACDB INCOMER-1 INCOMER-1 ON/OFF DPC
61 415 V AUX ACDB BUS COUPLER BUSCOUPLER ON/OFF DPC
62 415 V AUX ACDB INCOMER-2 INCOMER-2 ON/OFF DPC
63 415 V AUX DG SET DG START/STOP DPC
64 415 V AUX DG SET DG INCOMER CB ON/OFF DPC
STATCOM (HYOSUNG)
1 400KV COUPLING TRANSFORMER (HV) 52 CB OPEN/CLOSE DPC
2 400KV COUPLING TRANSFORMER (HV) 89A ISOLATOR OPEN/CLOSE DPC
3 400KV COUPLING TRANSFORMER (HV) 89B ISOLATOR OPEN/CLOSE DPC
4 400KV COUPLING TRANSFORMER (HV) 89TR ISOLATOR OPEN/CLOSE DPC
5 400KV COUPLING TRANSFORMER (HV) 89TSR ISOLATOR OPEN/CLOSE DPC
6 400KV COUPLING TRANSFORMER (HV) 89TY ISOLATOR OPEN/CLOSE DPC
7 400KV COUPLING TRANSFORMER (HV) 89TSY ISOLATOR OPEN/CLOSE DPC
8 400KV COUPLING TRANSFORMER (HV) 89TB ISOLATOR OPEN/CLOSE DPC
9 400KV COUPLING TRANSFORMER (HV) 89TSB ISOLATOR OPEN/CLOSE DPC
10 20KV COUPLING TRANSFORMER (MV) 89TR ISOLATOR OPEN/CLOSE DPC
11 20KV COUPLING TRANSFORMER (MV) 89TY ISOLATOR OPEN/CLOSE DPC
12 20KV COUPLING TRANSFORMER (MV) 89TB ISOLATOR OPEN/CLOSE DPC
13 20KV COUPLING TRANSFORMER (MV) 89TSR ISOLATOR OPEN/CLOSE DPC
14 20KV COUPLING TRANSFORMER (MV) 89TSY ISOLATOR OPEN/CLOSE DPC
15 20KV COUPLING TRANSFORMER (MV) 89TSB ISOLATOR OPEN/CLOSE DPC
16 20KV STATCOM-1 VSC-1 -52 CB OPEN/CLOSE DPC
17 20KV STATCOM-1 VSC-1 -89A ISOLATOR OPEN/CLOSE DPC
18 20KV STATCOM-1 VSC-1 -89B ISOLATOR OPEN/CLOSE DPC
19 20KV STATCOM-2 VSC-2 -52 CB OPEN/CLOSE DPC
20 20KV STATCOM-2 VSC-2 -89A ISOLATOR OPEN/CLOSE DPC
21 20KV STATCOM-2 VSC-2 -89B ISOLATOR OPEN/CLOSE DPC
22 20KV GND T/F 89 ISOLATOR OPEN/CLOSE DPC
23 20KV BUS PT 89 ISOLATOR OPEN/CLOSE DPC
24 20KV AUX.T/F 89 ISOLATOR OPEN/CLOSE DPC
25 20KV AUX.T/F 52 CB OPEN/CLOSE DPC
26 33KV AUX.T/F TERTIARY 52 CB OPEN / CLOSE DPC
27 33KV AUX.T/F TERTIARY 89 89 OPEN / CLOSE DPC
28 20KV MSR-1 89A ISOLATOR OPEN/CLOSE DPC
29 20KV MSR-1 52 CB OPEN/CLOSE DPC
30 20KV MSR-1 89B ISOLATOR OPEN/CLOSE DPC
31 20KV MSR-2 89A ISOLATOR OPEN/CLOSE DPC
32 20KV MSR-2 52 CB OPEN/CLOSE DPC
33 20KV MSR-2 89B ISOLATOR OPEN/CLOSE DPC
34 20KV MSC 89A ISOLATOR OPEN/CLOSE DPC
35 20KV MSC 52 CB OPEN/CLOSE DPC
36 20KV MSC 89B ISOLATOR OPEN/CLOSE DPC
37 400KV FUTURE 89A ISOLATOR OPEN/CLOSE DPC
38 400KV FUTURE & STATCOM TIE 52 CB OPEN/CLOSE DPC
39 400KV FUTURE & STATCOM TIE 89A ISOLATOR OPEN/CLOSE DPC
40 400KV FUTURE & STATCOM TIE 89B ISOLATOR OPEN/CLOSE DPC
Sl.NO BAY NUM. BAY NAME DEVICE ID SIGNAL DESCRIPTION DATA TYPE SCADA ID REMARK
765 KV/ 400 KV/ 220 KV LINE FEEDER
1 ABC LINE FEEDER LINE 86A TRIP RELAY RESET SPC 86AO
2 ABC LINE FEEDER LINE 86B TRIP RELAY RESET SPC 86BO
3 ABC LINE FEEDER CB CB CHECK SYNC BYPASS COMMAND SPC DLCC
4 ABC LINE FEEDER CB A/R LOCK OUT RELAY RESET SPC ARLO
765 KV/ 400 KV SWITCHABLE LINE REACTOR/ BUS REACTOR
1 ABC LINE FEEDER WITH SW REACTOR RE REACTOR TRIP RELAY 86A RESET SPC GRAO
2 ABC LINE FEEDER WITH SW REACTOR RE REACTOR TRIP RELAY 86B RESET SPC GRBO
3 ABC LINE FEEDER WITH SW REACTOR ZBR BYPASS CMD FOR CNTRL SWITCH DEVICE SPC BYSW
4 ABC LINE FEEDER WITH SW REACTOR RE COMMAND FOR DELUGE VALVE - R PH SPC To be combined in case of 3 phase Line Reactor/Bus Reactor
5 ABC LINE FEEDER WITH SW REACTOR RE COMMAND FOR DELUGE VALVE - Y PH SPC
6 ABC LINE FEEDER WITH SW REACTOR RE COMMAND FOR DELUGE VALVE - B PH SPC
7 ABC LINE FEEDER WITH SW REACTOR RE COMMAND FOR DELUGE VALVE - SPARE SPC
FIXED SERIES CAPACITOR (FSC)
1 ABC FSC MASTER TRIP RST SPC
765 KV/ 400 KV/220 KV TIE/ BUS SECTION BAY
1 ABC TIE / BS CB 86A TRIP RELAY RESET SPC 86AO
2 ABC TIE / BS CB 86B TRIP RELAY RESET SPC 86BO
3 ABC TIE / BS CB CB CHECK SYNC BYPASS COMMAND SPC DLCC
4 ABC TIE CB BYPASS CMD FOR CNTRL SWITCH DEVICE SPC BYSW In case of ICT, Line Reactor or Bus Reactor in Main Bays
5 ABC TIE / BS CB A/R LOCK OUT RELAY RESET SPC ARLO
1 ABC ICT XFMR_P 86A TRIP RELAY RESET SPC 89AO
2 ABC ICT XFMR_P 86B TRIP RELAY RESET SPC 86AO
3 ABC ICT XFMR_P CB CHECK SYNC BYPASS COMMAND SPC DLCC
4 ABC ICT XFMR_P BYPASS CMD FOR CNTRL SWITCH DEVICE SPC BYSW
5 ABC ICT XFMR_P COMMAND FOR DELUGE VALVE - R PH SPC DVTR To be combined in case of 3 phase ICT
6 ABC ICT XFMR_P COMMAND FOR DELUGE VALVE - Y PH SPC DVTY
7 ABC ICT XFMR_P COMMAND FOR DELUGE VALVE - B PH SPC DVTB
8 ABC ICT XFMR_P TAP CHANGER RAISE COMMAND SPC
9 ABC ICT XFMR_P TAP CHANGER LOWER COMMAND SPC
10 ABC SPARE ICT XFMR_P COMMAND FOR DELUGE VALVE - SPARE SPC
1 ABC BUS COUPLER CB CB CHECK SYNC BYPASS COMMAND SPC DLCC
TRANSFER BUS COUPLER
1 ABC TRANSFER BUS COUPLER LINE 86A TRIP RELAY RESET SPC 86AO
2 ABC TRANSFER BUS COUPLER LINE 86B TRIP RELAY RESET SPC 86BO
3 ABC TRANSFER BUS COUPLER CB CB CHECK SYNC BYPASS COMMAND SPC DLCC
4 ABC TRANSFER BUS COUPLER CB A/R LOCK OUT RELAY RESET SPC ARLO
AUXILIARY SYSTEM
1 415 V FP EPUMP EMER. START OF ELECTRIC MOTOR DRIVEN PUMP SPC
2 415 V FP EPUMP EMER. STOP OF ELECTRIC MOTOR DRIVEN PUMP SPC
3 415 V FP DPUMP EMER. START OF DIESEL MOTOR DRIVEN PUMP SPC
4 415 V FP DPUMP EMER. STOP OF DIESEL MOTOR DRIVEN PUMP SPC
5 415 V FP G_703_ICT-1 DELGUE VALVE ICT ON COMMAND SPC
6 415 V FP G_701_BR-1 DELUGE VALVE ON COMMAND FOR BUS REACTOR SPC
7 415 V SYSTEM AUX_SYSTEM SUBSTATION COMMAND FOR MAIN CONTROL ON NTAMC SPC
8 415 V SYSTEM AUX_SYSTEM SUBSTATION COMMAND FOR MAIN CONTROL ON RTAMC SPC
9 415 V SYSTEM AUX_SYSTEM SUBSTATION COMMAND FOR MAIN CONTROL ON BACK UP NTAMC SPC
10 415 V SYSTEM AUX_SYSTEM SUBSTATION COMMAND FOR AUX CONTROL ON NTAMC SPC
11 415 V SYSTEM AUX_SYSTEM SUBSTATION COMMAND FOR AUXCONTROL ON RTAMC SPC
12 415 V SYSTEM AUX_SYSTEM SUBSTATION COMMAND FOR AUX CONTROL ON BACK UP NTAMC SPC
13 415 V DG Set DGSET-1 DG SET START COMMAND SPC
14 415 V DG Set DGSET-1 DG SET STOP COMMAND SPC
STATCOM (SIEMENS)
1 STATCOM STATCOM STATCOM OPERATION ACKNOWLEDGE CMD VSC 1 SPC
2 STATCOM STATCOM STATCOM OPERATION ACKNOWLEDGE CMD VSC 2 SPC
3 STATCOM STATCOM STATCOM OPERATION CONTROL VIA HMI REMOTE COMMAND SPC
4 STATCOM STATCOM STATCOM OPERATION CONTROL VIA RCI COMMAND SPC
5 STATCOM STATCOM STATCOM OPERATION EMERGENCY T+E20RIP CMD SPC
1 XX KV FUTURE& COUPLING T/F-1 TIE 86A TRIP RELAY RESET COMMAND SPC
2 XX KV FUTURE& COUPLING T/F-1 TIE 86B TRIP RELAY RESET COMMAND SPC
3 XX KV FUTURE& COUPLING T/F-1 TIE BYPASS CMD FOR CNTRL SWITCH DEVICE SPC
4 XX KV FUTURE& COUPLING T/F-1 TIE CB CHECK SYNC. BYPASS COMMAND SPC
5 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) 86A TRIP RELAY RESET SPC
6 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) 86B TRIP RELAY RESET SPC
7 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) CB CHECK SYNC. BYPASS COMMAND SPC
8 38.5KV STATCOM CONTROL STATCOM ONE KEY START SPC
9 38.5KV STATCOM CONTROL STATCOM ONE KEY STOP SPC
10 38.5KV STATCOM CONTROL STATCOM ONE KEY EXIT SPC
11 38.5KV STATCOM CONTROL STATCOM ONE KEY FAULT CLEAR (RESET) SPC
12 38.5KV STATCOM CONTROL STATCOM STATCOM 1 EMG. STOP SPC
13 38.5KV STATCOM CONTROL STATCOM STATCOM 2 EMG. STOP SPC
14 38.5KV STATCOM CONTROL STATCOM SUBSTATION EMG. STOP SPC
15 38.5KV STATCOM CONTROL STATCOM EXTERNAL CONTROL AUTO (MSR & MSC, HV B/R) SPC
16 38.5KV STATCOM CONTROL STATCOM EXTERNAL CONTROL MANUAL (MSR & MSC, HV B/R) SPC
17 38.5KV STATCOM CONTROL STATCOM UP-SET U-REF(PU) SPC
18 38.5KV STATCOM CONTROL STATCOM DN-SET U-REF(PU) SPC
19 38.5KV STATCOM CONTROL STATCOM Q-SET REF(PU)/FS REF(PU) UP SPC
20 38.5KV STATCOM CONTROL STATCOM Q-SET REF(PU)/FS REF(PU) DN SPC
21 38.5KV STATCOM CONTROL STATCOM VOLTAGE MODE CONTROL SPC
22 38.5KV STATCOM CONTROL STATCOM REACTIVE MODE CONTROL SPC
23 415 V AUX FP CUPLING TRAFO DELUGE VALVE R-PH CONTROL CMD SPC
24 415 V AUX FP CUPLING TRAFO DELUGE VALVE Y-PH CONTROL CMD SPC
25 415 V AUX FP CUPLING TRAFO DELUGE VALVE B-PH CONTROL CMD SPC
26 415 V AUX FP CUPLING TRAFO DELUGE VALVE S-PH CONTROL CMD SPC
STATCOM (HYOSUNG)
1 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY 86.1 TRIP RELAY RESET SPC
2 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY 86.2 TRIP RELAY RESET SPC
3 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY CSD BYPASS-ON SPC
4 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY CSD BYPASS-OFF (IN SERVICE) SPC
5 20KV STATCOM-1 VSC-1 STATCOM UNIT-1 TRIP RELAY-A(86A) RESET SPC
6 20KV STATCOM-1 VSC-1 STATCOM UNIT-1 TRIP RELAY-B(86B) RESET SPC
7 20KV STATCOM-2 VSC-2 STATCOM UNIT-2 TRIP RELAY-A(86A) RESET SPC
8 20KV STATCOM-2 VSC-2 STATCOM UNIT-2 TRIP RELAY-B(86B) RESET SPC
9 20KV AUX.T/F AUX T/F TRIP RELAY-A(86A) RESET SPC
10 20KV AUX.T/F AUX T/F TRIP RELAY-B(86B) RESET SPC
11 20KV MSR-1 MSR MSR-1 TRIP RELAY-A(86A) RESET SPC
12 20KV MSR-1 MSR MSR-1 TRIP RELAY-B(86B) RESET SPC
13 20KV MSR-2 MSR MSR-2 TRIP RELAY-A(86A) RESET SPC
14 20KV MSR-2 MSR MSR-2 TRIP RELAY-B(86B) RESET SPC
15 20KV MSC MSC MSC TRIP RELAY-A(86A) RESET SPC
16 20KV MSC MSC MSC TRIP RELAY-B(86B) RESET SPC
17 400KV FUTURE & STATCOM TIE 86.1 TRIP RELAY RESET SPC
18 400KV FUTURE & STATCOM TIE 86.2 TRIP RELAY RESET SPC
19 400KV FUTURE & STATCOM TIE CSD BYPASS-ON SPC
20 400KV FUTURE & STATCOM TIE CSD BYPASS-OFF (IN SERVICE) SPC
Annexure B : HYSONG
Annexure C: RXPE
IEC 60870-5-104 interoperability Profile for NTAMC Control centers
PROTOCOL SUMMARY
SL.No. Description Value Remark
1 ASDU Common Address 237 Integer Number to be provided by NTAMC
2 Common Address Size of ASDU 2 Byte
3 Information object Address Structure 3 Byte
4 Frame Max Length 255
5 MV Periodic Cycle Periodic cycle 15Sec and Spontaneous transmission on 1% change of Current value. For Frequency 0.02% (i.e.0.01 Hz)
6 Binary Time Stamp Size 7 Byte CP56 Time 2a
7 T0: Connection Time Out 30 Sec.
8 T1: APDU Time Out 15 Sec.
9 T2: Acknowledge Time Out 10 Sec.
10 T3: Test Frame Time Out 20 Sec.
11 K: Send Acknowledgement Frames (APDU) 12
12 W: Acknowledgement Received Frame (APDU) 8
13 Time Synchronisation NA Locally through IRIG-B or SNTP
14 Cause of Transmission 2 Byte
DIGTAL STATUS SETTINGS PROFILE
SL.No. Discription Duration Remark
1 Debouncing Time 4ms
2 Filtering Delay 5ms
IEC 60870-5-104 Digital Signal type
SL.No. Discription Status Signal type CONTROL TYPE PULSE WIDTH DURATION TIME OUT DURATION
1(a) Circuit Breaker (ON/OFF) DPS DPC SBO 500 ms 3 Sec
1(b) Circuit breaker (Check synch bypass) SPS SPC DIRECT OPERATE 500 ms 3 Sec
2 Isolator DPS DPC SBO 500 ms 20 Sec
3 Tap Changer status & RAISE/LOWER control command DPS DPC SBO 500 ms 10 Sec
4 Trip Relay & L/O Relays reset SPS SPC DIRECT OPERATE 500 ms 10 Sec
5 Mode Selection (e.g. AR Auto/Non-auto, Protection Transfer etc.), Auxiliaries Motor, DG set & Diesel Engine, etc DPS DPC SBO 500 ms 10 Sec
6 Control Switching Device (CSD) BYPASS COMMAND & Status SPS SPC DIRECT OPERATE 500 ms 10 Sec
7 Fire fighting tank Water level, Manual Open/Close status (One SPS for each level) SPS NA
8 Control Authority Transfer signals (NTAMC/BNTAMC/RTAMC) SPS SPC DIRECT OPERATE 500 ms 3 Sec
9 Auto/Manual, Local/Remote DPS NA
10 Other signals SPS SPC (If applicable) DIRECT OPERATE 500 ms 3 Sec
The abnormal state for SPS signals shall be the HIGH state for alarms like ALARM/NORMAL, UNHEALTHY/HEALTHY, LOW/NORMAL, ON/OFF, FAIL/NORMAL, SET/RESET.
IEC 60870-5-104 ASDU ANALOG Data TYPE
SL.No. Description Remark
1 Tap Position (1- 25) Analog
2 MW, MVAR, Current, Freq, Volatge Analog
3 Temperature, Humidity Analog
4 Fire fighting System Water pressure Analog
5 DC Supply Volatge /Current Analog
6 DG set & FF engine Battery volatge Analog
IEC 60870-5-104 ASDU TYPE
SL.No. Description ASDU TYPE ID Remark
1 Analog Measured Valuse, Short Floating Point Value 13
2 SPS Single Point Information with Time Tag 30
3 DPS Double Point Information with Time Tag 31
4 Analog spontaneous transmission Measured Value, Short Floating Point Value with Time Tag 36
5 SPC Single Command 45 OPEN/CLOSE, SET/RESET
6 DPC Double Command 46 OPEN/CLOSE, RAISE/LOWER, AUTO/MANUAL
IEC 60870-5-104 IOA ADDRESS STRUCTURE
SL.No. Description Starting Address Remark
1 Single Point Status (SPS) 1
2 Double Point Status (DPS) 5000
3 Measurement Value (MV) or Analog Value (AI) 10000
4 Double Point Control (DPC) 15000
5 Single Point Control (SPC) 17000
A. Control Authority Transfer Scheme for NTAMC/RTAMC/Backup NTAMC
Both the SAS Gateways shall be configured to report independently to three control centers of NTAMC system (Main NTAMC, Backup NTAMC & RTAMC) simultaneously. There shall be a Control Center Authority Transfer scheme implemented such that at a time, only one Control Center shall be able to Control the Substation. Any Control center shall be able to takeover supervisory control authority from the substation gateway for either / both main system / auxiliary system after substation is manually put in remote mode from local station. The information regarding which control center is having the control authority shall be known to all the other control centers. The total points in the substation will be categorised in two Groups either as "POWER" or "AUXILLIARY". The Control Authority transfer to a Control Center shall be possible for any of the groups i.e. POWER or AUXILIARY or both. This takeover control logic shall be implemented in the SAS Gateway.
B. Substation Level Local/Remote Switch
A Substation Level Local/Remote switch shall be provided prefarably in SUX BCU Panel in control room. The function is to transfer the supervisory control from SUBSTATION level to the CONTROL CENTER level. The controls shall be from SUBSTATION if the switch is in LOCAL position. It will be from the CONTROL CENTERs (Main NTAMC /Backup NTAMC / RTAMC) if the switch is in REMOTE MODE. The Control Authority Transfer shall be applicable when in REMOTE MODE.
C. Station ID shall be a unique number for each substation to be provided by NTAMC Control Center
D. A Dummy Circuit Breaker to be provided in the Aux BCU Panel in Substation Control Room to test healthiness of the communication link including Substation Gateway / RTU from NTAMC control center. The associated control & monitoring indication to be hard wired to Aux BCU for the same.
Sl.NO BAY NUM. BAY NAME DEVICE ID SIGNAL DESCRIPTION DATA TYPE SCADA ID Remarks
765 KV/ 400 KV/ 220 KV LINE FEEDER
1 ABC LINE FEEDER BCU BAY IN MAINTENANCE MODE SPS BAYM
2 ABC LINE FEEDER BCU BCU DC SUPPLY FAIL-1/2 SPS BCUD
3 ABC LINE FEEDER BCU BCU UNHEALTHY SPS BCUH
4 ABC LINE FEEDER BCU BCU TIME SYNC ERROR SPS BCUC
5 ABC LINE FEEDER CB CB MANUAL OPEN SPS MNOP
6 ABC LINE FEEDER CB CB MANUAL CLOSE SPS MNCL
7 ABC LINE FEEDER CB LBB PROTECTION OPERATED SPS LBBO
8 ABC LINE FEEDER CB OPERATION LOCKOUT SPS OPLO
9 ABC LINE FEEDER CB CB POLE DISCREPANCY OPERATED SPS PDIS
10 ABC LINE FEEDER CB CB POLE DISCREPANCY WITH IN POLE OPERATED SPS PDIB
11 ABC LINE FEEDER CB CB DC SUPPLY 1/2 FAIL SPS DC
12 ABC LINE FEEDER CB CB AC SUPPLY FAIL SPS ACSP
13 ABC LINE FEEDER CB CB SPRING DISCHARGE SPS SPRG
14 ABC LINE FEEDER CB CB SF6 LOW ALARM SPS SF6L
15 ABC LINE FEEDER CB CB TC1 Faulty SPS TC1F
16 ABC LINE FEEDER CB CB TC2 Faulty SPS TC2F
17 ABC LINE FEEDER CB AUTORECLOSE LOCKOUT SPS ARLO
18 ABC LINE FEEDER CB AUTORECLOSE OPERATED SPS AROP
17 ABC LINE FEEDER CB CB IN LOCAL/REMOTE SPS CBLM
19 ABC LINE FEEDER LINE AUTORECLOSE UNSUCCESFUL SPS ARFM
20 ABC LINE FEEDER LINE MAIN-1 PROTECTION OPERATED SPS M1OP
21 ABC LINE FEEDER LINE MAIN-1 DISTANCE PROTECTION ZONE1 TRIP SPS M1Z1
22 ABC LINE FEEDER LINE MAIN-1 DISTANCE PROTECTION ZONE2 TRIP SPS M1Z2
23 ABC LINE FEEDER LINE MAIN-1 DISTANCE PROTECTION ZONE3 TRIP SPS M1Z3
24 ABC LINE FEEDER LINE MAIN-1 DISTANCE PROTECTION REVERSE ZONE TRIP SPS M1RP
25 ABC LINE FEEDER LINE MAIN-1 A/R BLOCK SPS M1AR
26 ABC LINE FEEDER LINE MAIN-1 CVT FUSE FAILURE SPS M1FU
27 ABC LINE FEEDER LINE MAIN-1 RELAY FAULTY SPS M1UH
28 ABC LINE FEEDER LINE MAIN-1 DEF OPERATED SPS M1DE
29 ABC LINE FEEDER LINE MAIN-1 SOTF OPERATED SPS M1SO
30 ABC LINE FEEDER LINE MAIN-1 CARRIER SEND CH-1 SPS CAR7
31 ABC LINE FEEDER LINE MAIN-1 CARRIER SEND CH-2 SPS CAR8
32 ABC LINE FEEDER LINE MAIN-1 CARRIED RECD CH-1 SPS CAR3
33 ABC LINE FEEDER LINE MAIN-1 CARRIED RECD CH-2 SPS CAR5
34 ABC LINE FEEDER LINE MAIN-1 CARRIER AIDED TRIP SPS CAT1
35 ABC LINE FEEDER LINE MAIN-1 CARRIER SWITCH IN OUT OF SERVICE SPS CAS1
36 ABC LINE FEEDER LINE MAIN-2 PROTECTION OPERATED SPS M2OP
37 ABC LINE FEEDER LINE MAIN-2 DISTANCE PROTECTION ZONE1 TRIP SPS M2Z1
38 ABC LINE FEEDER LINE MAIN-2 DISTANCE PROTECTION ZONE2 TRIP SPS M2Z2
39 ABC LINE FEEDER LINE MAIN-2 DISTANCE PROTECTION ZONE3 TRIP SPS M2Z3
40 ABC LINE FEEDER LINE MAIN-2 DISTANCE PROTECTION REVERSE ZONE TRIP SPS M2RP
41 ABC LINE FEEDER LINE MAIN-2 A/R BLOCK SPS M2AR
42 ABC LINE FEEDER LINE MAIN-2 CVT FUSE FAILURE SPS M2FU
43 ABC LINE FEEDER LINE MAIN-2 RELAY FAULTY SPS M2UH
44 ABC LINE FEEDER LINE MAIN-2 DEF OPERATED SPS M2DE
45 ABC LINE FEEDER LINE MAIN-2 SOTF OPERATED SPS M2SO
46 ABC LINE FEEDER LINE MAIN-2 CARRIER SEND CH-1 SPS CAR9
47 ABC LINE FEEDER LINE MAIN-2 CARRIER SEND CH-2 SPS CARS
48 ABC LINE FEEDER LINE MAIN-2 CARRIED RECD CH-1 SPS CAR4
49 ABC LINE FEEDER LINE MAIN-2 CARRIED RECD CH-2 SPS CAR6
50 ABC LINE FEEDER LINE MAIN-2 CARRIER AIDED TRIP SPS CAT2
51 ABC LINE FEEDER LINE MAIN-2 CARRIER SWITCH IN OUT OF SERVICE SPS CAS2
52 ABC LINE FEEDER LINE MAIN-1 BB PROTECTION OPTD SPS BB1P
53 ABC LINE FEEDER LINE MAIN-2 BB PROTECTION OPTD SPS BB2P
54 ABC LINE FEEDER LINE MAIN-1 BB PU UNIT FAULTY SPS B1UH
55 ABC LINE FEEDER LINE MAIN-2 BB PU UNIT FAULTY SPS B2UH
56 ABC LINE FEEDER LINE DIRECT TRIP SEND CHANNEL 1 SPS TRS1
57 ABC LINE FEEDER LINE DIRECT RECEIVED CHANNEL 1 SPS TRP1
58 ABC LINE FEEDER LINE DIRECT TRIP SEND CHANNEL 2 SPS TRS2
59 ABC LINE FEEDER LINE DIRECT RECEIVED CHANNEL 2 SPS TRP2
60 ABC LINE FEEDER LINE 86A TRIP RELAY OPERATED SPS 86AO
61 ABC LINE FEEDER LINE 86B TRIP RELAY OPERATED SPS 86BO
62 ABC LINE FEEDER LINE 86A TRIP RELAY FAULTY SPS 86AU
63 ABC LINE FEEDER LINE 86B TRIP RELAY FAULTY SPS 86BU
64 ABC LINE FEEDER LINE CARRIER FAIL CH-1 SPS CAF1
65 ABC LINE FEEDER LINE CARRIER FAIL CH-2 SPS CAF2
66 ABC LINE FEEDER LINE DC SOURCE-1 FAIL SPS DC-1
67 ABC LINE FEEDER LINE DC SOURCE-2 FAIL SPS DC-2
68 ABC LINE FEEDER LINE MAIN-1 PSB DETECTED SPS PSB1
69 ABC LINE FEEDER LINE MAIN-1 STUB PROTN OPERATED SPS STUB
70 ABC LINE FEEDER LINE MAIN-1 O/V STAGE-1 TRIP SPS OV-1
71 ABC LINE FEEDER LINE MAIN-1 O/V STAGE-2 TRIP SPS OV-12
72 ABC LINE FEEDER LINE MAIN-2 PSB DETECTED SPS PSB2
73 ABC LINE FEEDER LINE MAIN-2 STUB PROTECTION OPERATED SPS STUP
74 ABC LINE FEEDER LINE MAIN-2 O/V STAGE-1 TRIP SPS OV-3
75 ABC LINE FEEDER LINE MAIN-2 O/V STAGE-2 TRIP SPS OV-4
76 ABC LINE FEEDER LINE MAIN-1 LINE DIFFERENTIAL PROTECTION OPERATED SPS
77 ABC LINE FEEDER LINE MAIN-2 LINE DIFFERENTIAL PROTECTION OPERATED SPS
78 ABC LINE FEEDER LINE 89L OPERATED FOR STUB M1 SPS
79 ABC LINE FEEDER LINE 89L OPERATED FOR STUB M2 SPS
80 ABC LINE FEEDER LINE SPEECH CHANNEL FAIL SPS
81 ABC LINE FEEDER LINE CB MCB TRIPPED ( Motor/Heating/Lighting) SPS
82 ABC LINE FEEDER LINE MAIN-1 DIFFERENTIAL PROTN TRIP R PH SPS
83 ABC LINE FEEDER LINE MAIN-1 DIFFERENTIAL PROTN TRIP Y PH SPS
84 ABC LINE FEEDER LINE MAIN-1 DIFFERENTIAL PROTN TRIP B PH SPS
85 ABC LINE FEEDER LINE MAIN-2 DIFFERENTIAL PROTN TRIP R PH SPS
86 ABC LINE FEEDER LINE MAIN-2 DIFFERENTIAL PROTN TRIP Y PH SPS
87 ABC LINE FEEDER LINE MAIN-2 DIFFERENTIAL PROTN TRIP B PH SPS
88 ABC LINE FEEDER LINE MAIN-1 DIFFERENTIATED WAVE BLOCK SPS
89 ABC LINE FEEDER LINE MAIN-1 DIFFERENTIATED HORMONICS BLOCK SPS
90 ABC LINE FEEDER LINE MAIN-2 DIFFERENTIATED WAVE BLOCK SPS
91 ABC LINE FEEDER LINE MAIN-2 DIFFERENTIATED HORMONICS BLOCK SPS
92 ABC LINE FEEDER LINE MAIN-1 DIFFERENTIATED RESTRAIN TRIP SPS
93 ABC LINE FEEDER LINE MAIN-2 DIFFERENTIATED RESTRAIN TRIP SPS
94 ABC LINE FEEDER LINE MAIN-1 DIFFERENTIATED UNRESTRAIN TRIP SPS
95 ABC LINE FEEDER LINE MAIN-2 DIFFERENTIATED UNRESTRAIN TRIP SPS
96 ABC LINE FEEDER LINE MAIN-1 BROKEN CONDUCTOR ALARM SPS
97 ABC LINE FEEDER LINE MAIN-2 BROKEN CONDUCTOR ALARM SPS
98 ABC LINE FEEDER LINE Autoreclosure Block SPS
99 ABC LINE FEEDER CB INTERLOCK ENABLED SPS INTL
100 ABC LINE FEEDER 89A INTERLOCK ENABLED SPS INTL
101 ABC LINE FEEDER 89B INTERLOCK ENABLED SPS INTL
102 ABC LINE FEEDER 89L INTERLOCK ENABLED SPS INTL
103 ABC LINE FEEDER 89AE1 INTERLOCK ENABLED SPS INTL Bus Earth Switch
104 ABC LINE FEEDER 89AE2 INTERLOCK ENABLED SPS INTL
105 ABC LINE FEEDER 89BE INTERLOCK ENABLED SPS INTL
106 ABC LINE FEEDER 89LE INTERLOCK ENABLED SPS INTL
107 ABC LINE FEEDER CB CB PUMP RUNTIME EXCEEDED SPS For GIS Line Feeder Bays
108 ABC LINE FEEDER CB DE DRIVE STATUS ALARM SPS
109 ABC LINE FEEDER CB CRANK HANDLE INSERTED SPS
110 ABC LINE FEEDER PARTIAL DISCHARGE HIGH ALARM SPS
111 ABC LINE FEEDER LCC IN LOCAL MODE SPS
112 ABC LINE FEEDER LCC IN REMOTE MODE SPS
113 ABC LINE FEEDER BAY INTERLOCK BYPASS SELECTED SPS
114 ABC LINE FEEDER GAS LKG R/Y/B STG1 REFILL SPS SF61
115 ABC LINE FEEDER GAS LKG R/Y/B STG2 LOW SPS SF62
116 ABC LINE FEEDER GAS LKG R/Y/B ZONE TRIP SPS SF6T
117 ABC LINE FEEDER GAS LKG R/Y/B CB LOCKOUT/CB OPERATION LOCKOUT SPS SF6T
765 KV/ 400 KV LINE REACTOR/ BUS REACTOR
1 ABC LINE REACTOR/ BUS REACTOR BCU BAY IN MAINTENANCE MODE SPS BAYM
2 ABC LINE REACTOR/ BUS REACTOR BCU BCU DC SUPPLY FAIL-1/2 SPS BCUD
3 ABC LINE REACTOR/ BUS REACTOR BCU BCU UNHEALTHY SPS BCUH
4 ABC LINE REACTOR/ BUS REACTOR BCU BCU TIME SYNC ERROR SPS BCUC
5 ABC LINE REACTOR/ BUS REACTOR 52R CB MANUAL OPEN SPS MNOP Required if reactor is switchable
6 ABC LINE REACTOR/ BUS REACTOR 52R CB MANUAL CLOSE SPS MNCL
7 ABC LINE REACTOR/ BUS REACTOR 52R LBB PROTECTION OPERATED SPS LBBO
8 ABC LINE REACTOR/ BUS REACTOR 52R OPERATION LOCKOUT SPS OPLO
9 ABC LINE REACTOR/ BUS REACTOR 52R CB POLE DISCREPANCY OPERATED SPS PDIS
10 ABC LINE REACTOR/ BUS REACTOR 52R CB POLE DISCREPANCY WITH IN POLE OPERATED SPS PDIB
11 ABC LINE REACTOR/ BUS REACTOR 52R CB DC SUPPLY 1/2 FAIL SPS DC
12 ABC LINE REACTOR/ BUS REACTOR 52R CB AC SUPPLY FAIL SPS ACSP
13 ABC LINE REACTOR/ BUS REACTOR 52R CB SPRING DISCHARGE SPS SPRG
14 ABC LINE REACTOR/ BUS REACTOR 52R CB SF6 LOW ALARM SPS SF6L
15 ABC LINE REACTOR/ BUS REACTOR 52R CB TC1 Faulty SPS TC1F
16 ABC LINE REACTOR/ BUS REACTOR 52R CB TC2 Faulty SPS TC2F
17 ABC LINE REACTOR/ BUS REACTOR RE DIFFERENTIAL RELAY OPTD. SPS REDI
18 ABC LINE REACTOR/ BUS REACTOR RE B/U IMPEDANCE OPTD SPS BUIO
19 ABC LINE REACTOR/ BUS REACTOR RE REF OPTD SPS RERE
20 ABC LINE REACTOR/ BUS REACTOR RE B/U RELAY FAULTY SPS BURF
21 ABC LINE REACTOR/ BUS REACTOR RE DIFFERENTIAL RELAY FAULTY SPS DIRU
22 ABC LINE REACTOR/ BUS REACTOR RE SELECTED VT FUSE FAIL ALARM SPS VTFU
23 ABC LINE REACTOR/ BUS REACTOR RE REACTOR 86A TRIP RELAY OPERATED SPS GRAO
24 ABC LINE REACTOR/ BUS REACTOR RE REACTOR 86B TRIP RELAY OPERATED SPS GRBO
25 ABC LINE REACTOR/ BUS REACTOR RE REACTOR 86A TRIP RELAY FAULTY SPS GRAU
26 ABC LINE REACTOR/ BUS REACTOR RE REACTOR 86B TRIP RELAY FAULTY SPS GRBU
27 ABC LINE REACTOR/ BUS REACTOR RE MAIN-1 BB PROTECTION OPTD SPS BB1P
28 ABC LINE REACTOR/ BUS REACTOR RE MAIN-2 BB PROTECTION OPTD SPS BB2P
29 ABC LINE REACTOR/ BUS REACTOR RE MAIN-1 BB PU UNIT FAULTY SPS B1UH
30 ABC LINE REACTOR/ BUS REACTOR RE MAIN-2 BB PU UNIT FAULTY SPS B2UH
31 ABC LINE REACTOR/ BUS REACTOR RE DC SOURCE-1 FAIL SPS DC-1
32 ABC LINE REACTOR/ BUS REACTOR RE DC SOURCE-2 FAIL SPS DC-2
33 ABC LINE REACTOR/ BUS REACTOR RE Oil level low alarm R phase SPS REOL 3 PHASE STATUS IS REQUIRED IF LINE REACTOR/ BUS REACTOR IS 3 PHASE
34 ABC LINE REACTOR/ BUS REACTOR RE MOISTURE ALARM in R phase SPS MOSA
35 ABC LINE REACTOR/ BUS REACTOR RE BUCHOLTZ ALARM_R PHASE SPS BUCA
36 ABC LINE REACTOR/ BUS REACTOR RE BUCHOLTZ TRIP_R PHASE SPS BUCT
37 ABC LINE REACTOR/ BUS REACTOR RE SHUT_OFF_VALVE TRIP R PHASE SPS VLVT
38 ABC LINE REACTOR/ BUS REACTOR RE WTI ALARM_R PHASE SPS WTIA
39 ABC LINE REACTOR/ BUS REACTOR RE WTI_TRIP_R PHASE SPS WTIT
40 ABC LINE REACTOR/ BUS REACTOR RE OTI_ALARM_R_PHASE SPS OTIA
41 ABC LINE REACTOR/ BUS REACTOR RE OTI_TRIP_R_PHASE SPS OTIT
42 ABC LINE REACTOR/ BUS REACTOR RE PRV_TRIP_1_R_PHASE SPS REPR
43 ABC LINE REACTOR/ BUS REACTOR RE PRV_TRIP_2_R_PHASE SPS PRV2
44 ABC LINE REACTOR/ BUS REACTOR RE FIRE PROTN OPTD R PHASE SPS FRRR
45 ABC LINE REACTOR/ BUS REACTOR RE DELUGE VALVE ON - R PHASE SPS DVRR
46 ABC LINE REACTOR/ BUS REACTOR RE DGA MONITORING DEVICE UNHEALTHY SPS DGAM
47 ABC LINE REACTOR/ BUS REACTOR RE SPARE REACTOR SELECT FOR R PHASE SPS SPRE
48 ABC LINE REACTOR/ BUS REACTOR RE Oil level Low Alarm Y PHASE SPS REOL
49 ABC LINE REACTOR/ BUS REACTOR RE MOISTURE ALARM in Y PHASE SPS MOSA
50 ABC LINE REACTOR/ BUS REACTOR RE BUCHOLTZ ALARM_Y PHASE SPS BUCA
51 ABC LINE REACTOR/ BUS REACTOR RE BUCHOLTZ TRIP_Y PHASE SPS BUCT
52 ABC LINE REACTOR/ BUS REACTOR RE SHUT_OFF_VALVE TRIP Y PHASE SPS VLVT
53 ABC LINE REACTOR/ BUS REACTOR RE WTI ALARM_Y PHASE SPS WTIA
54 ABC LINE REACTOR/ BUS REACTOR RE WTI_TRIP_Y PHASE SPS WTIT
55 ABC LINE REACTOR/ BUS REACTOR RE OTI_ALARM_Y PHASE SPS OTIA
56 ABC LINE REACTOR/ BUS REACTOR RE OTI_TRIP_Y PHASE SPS OTIT
57 ABC LINE REACTOR/ BUS REACTOR RE PRV_TRIP_1_Y PHASE SPS REPR
58 ABC LINE REACTOR/ BUS REACTOR RE PRV_TRIP_2_Y PHASE SPS PRV2
59 ABC LINE REACTOR/ BUS REACTOR RE FIRE PROTN OPTD Y PHASE SPS FRRY
60 ABC LINE REACTOR/ BUS REACTOR RE DELUGE VALVE ON - Y PHASE SPS DVRY
61 ABC LINE REACTOR/ BUS REACTOR RE DGA MONITORING DEVICE UNHEALTHY SPS
62 ABC LINE REACTOR/ BUS REACTOR RE SPARE REACTOR SELECT FOR Y PHASE SPS SPRE
63 ABC LINE REACTOR/ BUS REACTOR RE Oil level low alarm B PHASE SPS REOL
64 ABC LINE REACTOR/ BUS REACTOR RE MOISTURE ALARM in B PHASE SPS MOSA
65 ABC LINE REACTOR/ BUS REACTOR RE BUCHOLTZ ALARM_B PHASE SPS BUCA
66 ABC LINE REACTOR/ BUS REACTOR RE BUCHOLTZ TRIP_B PHASE SPS BUCT
67 ABC LINE REACTOR/ BUS REACTOR RE SHUT_OFF_VALVE TRIP B PHASE SPS VLVT
68 ABC LINE REACTOR/ BUS REACTOR RE WTI ALARM_B PHASE SPS WTIA
69 ABC LINE REACTOR/ BUS REACTOR RE WTI_TRIP_B PHASE SPS WTIT
70 ABC LINE REACTOR/ BUS REACTOR RE OTI_ALARM_B PHASE SPS OTIA
71 ABC LINE REACTOR/ BUS REACTOR RE OTI_TRIP_B PHASE SPS OTIT
72 ABC LINE REACTOR/ BUS REACTOR RE PRV_TRIP_1_B PHASE SPS REPR
73 ABC LINE REACTOR/ BUS REACTOR RE PRV_TRIP_2_B PHASE SPS PRV2
74 ABC LINE REACTOR/ BUS REACTOR RE FIRE PROTN OPTD B PHASE SPS FRRR
75 ABC LINE REACTOR/ BUS REACTOR RE DELUGE VALVE ON - B PHASE SPS DVRB
76 ABC LINE REACTOR/ BUS REACTOR RE DGA MONITORING DEVICE UNHEALTHY SPS
77 ABC LINE REACTOR/ BUS REACTOR RE SPARE REACTOR SELECT FOR B PHASE SPS SPRE
78 ABC LINE REACTOR/ BUS REACTOR RE TEED PROTECTION OPTD SPS
79 ABC LINE REACTOR/ BUS REACTOR RE TEED RELAY FAULTY SPS
80 ABC LINE REACTOR/ BUS REACTOR CB INTERLOCK ENABLED SPS INTL Applicable in case of Bus Reactor
81 ABC LINE REACTOR/ BUS REACTOR 89A INTERLOCK ENABLED SPS INTL
82 ABC LINE REACTOR/ BUS REACTOR 89B INTERLOCK ENABLED SPS INTL
83 ABC LINE REACTOR/ BUS REACTOR 89AE INTERLOCK ENABLED SPS INTL
84 ABC LINE REACTOR/ BUS REACTOR 89BE INTERLOCK ENABLED SPS INTL
85 ABC LINE REACTOR/ BUS REACTOR 52R INTERLOCK ENABLED SPS INTL
86 ABC LINE REACTOR/ BUS REACTOR 89RR INTERLOCK ENABLED SPS INTL
87 ABC LINE REACTOR/ BUS REACTOR 89RY INTERLOCK ENABLED SPS INTL
88 ABC LINE REACTOR/ BUS REACTOR 89RB INTERLOCK ENABLED SPS INTL
89 ABC LINE REACTOR/ BUS REACTOR 89RS1R INTERLOCK ENABLED SPS INTL
90 ABC LINE REACTOR/ BUS REACTOR 89RS1Y INTERLOCK ENABLED SPS INTL
91 ABC LINE REACTOR/ BUS REACTOR 89RS1B INTERLOCK ENABLED SPS INTL
92 ABC LINE REACTOR/ BUS REACTOR 89RER INTERLOCK ENABLED SPS INTL
93 ABC LINE REACTOR/ BUS REACTOR 89REY INTERLOCK ENABLED SPS INTL
94 ABC LINE REACTOR/ BUS REACTOR 89REB INTERLOCK ENABLED SPS INTL
95 ABC LINE REACTOR/ BUS REACTOR 52R CONTROL SWITCH DEVICE BYPASSED SPS BYSW
96 ABC LINE REACTOR/ BUS REACTOR 52R CONTROL SWITCH DEVICE TROUBLE SPS
97 ABC LINE REACTOR/ BUS REACTOR CB CB PUMP RUNTIME EXCEEDED SPS FOR GIS BAYS
98 ABC LINE REACTOR/ BUS REACTOR CB DE DRIVE STATUS ALARM SPS
99 ABC LINE REACTOR/ BUS REACTOR CB CRANK HANDLE INSERTED SPS
100 ABC LINE REACTOR/ BUS REACTOR GAS LKG R/Y/B STG1 REFILL SPS SF61
101 ABC LINE REACTOR/ BUS REACTOR GAS LKG R/Y/B STG2 LOW SPS SF62
102 ABC LINE REACTOR/ BUS REACTOR GAS LKG R/Y/B ZONE TRIP SPS SF6T
103 ABC LINE REACTOR/ BUS REACTOR GAS LKG R/Y/B CB LOCKOUT/CB OPERATION LOCKOUT SPS SF6T
1 ABC LINE FEEDER WITH REACTOR NGR BUCHHOLZ TRIP(NGR) SPS BUCT
2 ABC LINE FEEDER WITH REACTOR NGR REACTOR PRV TRIP(NGR) SPS REPR
3 ABC LINE FEEDER WITH REACTOR NGR OTI TRIP(NGR) SPS OTIT
4 ABC LINE FEEDER WITH REACTOR NGR OTI ALARM(NGR) SPS OTIA
5 ABC LINE FEEDER WITH REACTOR NGR BUCHHOLZ ALARM(NGR) SPS BUCA
6 ABC LINE FEEDER WITH REACTOR NGR LOW OIL LEVEL ALARM(NGR) SPS REOL
7 ABC LINE FEEDER WITH REACTOR NGR OPERATION LOCKOUT SPS OPLO
8 ABC LINE FEEDER WITH REACTOR 52NGR CB AC SUPPLY FAIL SPS ACSP
9 ABC LINE FEEDER WITH REACTOR 52NGR CB SPRING DISCHARGE SPS SPRG
10 ABC LINE FEEDER WITH REACTOR 52NGR CB SF6 LOW ALARM SPS SF6L
11 ABC LINE FEEDER WITH REACTOR 52NGR CB TC1 Faulty SPS TC1F
12 ABC LINE FEEDER WITH REACTOR 52NGR CB TC2 Faulty SPS TC2F
SPARE LINE REACTOR
1 ABC SPARE LINE REACTOR RE Oil level low alarm SPARE SPS REOL
2 ABC SPARE LINE REACTOR RE MOISTURE ALARM in SPARE SPS MOSA
3 ABC SPARE LINE REACTOR RE BUCH1/2_ALARM_SPARE SPS BUCA
4 ABC SPARE LINE REACTOR RE BUCH1/2 TRIP_SPARE SPS BUCT
5 ABC SPARE LINE REACTOR RE SHUT_OFF_VALVE TRIP SPARE SPS VLVT
6 ABC SPARE LINE REACTOR RE WTI ALARM_SPARE SPS WTIA
7 ABC SPARE LINE REACTOR RE WTI_TRIP_SPARE SPS WTIT
8 ABC SPARE LINE REACTOR RE OTI_ALARM_SPARE SPS OTIA
9 ABC SPARE LINE REACTOR RE OTI_TRIP_SPARE SPS OTIT
10 ABC SPARE LINE REACTOR RE PRV_TRIP_1_SPARE SPS REPR
11 ABC SPARE LINE REACTOR RE PRV_TRIP_2_SPARE SPS PRV2
12 ABC SPARE LINE REACTOR RE FIRE PROTN OPTD SPARE PHASE SPS FRRS
13 ABC SPARE LINE REACTOR RE DELUGE VALVE ON SPARE SPS DVRS
84 ABC SPARE LINE REACTOR GAS LKG R/Y/B STG1 REFILL SPS SF61 For GIS Bays
86 ABC SPARE LINE REACTOR GAS LKG R/Y/B ZONE TRIP SPS SF6T
765 KV/ 400KV TIE/ BUS SECTION BAY
1 ABC TIE/ BS BCU BAY IN MAINTENANCE MODE SPS BAYM
2 ABC TIE/ BS BCU BCU DC SUPPLY FAIL-1/2 SPS BCUD
3 ABC TIE/ BS BCU BCU UNHEALTHY SPS BCUH
4 ABC TIE/ BS BCU BCU TIME SYNC ERROR SPS BCUC
5 ABC TIE/ BS CB CB MANUAL OPEN SPS MNOP
6 ABC TIE/ BS CB CB MANUAL CLOSE SPS MNCL
7 ABC TIE/ BS CB LBB PROTECTION OPERATED SPS LBBO
8 ABC TIE/ BS CB OPERATION LOCKOUT SPS OPLO
9 ABC TIE/ BS CB CB POLE DISCREPANCY OPERATED SPS PDIS
10 ABC TIE/ BS CB CB POLE DISCREPANCY WITH IN POLE OPERATED SPS PDIB
11 ABC TIE/ BS CB CB DC SUPPLY 1/2 FAIL SPS DC
12 ABC TIE/ BS CB CB AC SUPPLY FAIL SPS ACSP
13 ABC TIE/ BS CB CB SPRING DISCHARGE SPS SPRG
14 ABC TIE/ BS CB CB SF6 LOW ALARM SPS SF6L
15 ABC TIE/ BS CB CB TC1 Faulty SPS TC1F
16 ABC TIE/ BS CB CB TC2 Faulty SPS TC2F
17 ABC TIE/ BS CB AUTORECLOSE LOCKOUT SPS ARLO
18 ABC TIE/ BS CB AUTORECLOSE OPERATED SPS AROP
19 ABC TIE/ BS LINE AUTORECLOSE UNSUCCESFUL SPS ARFT
20 ABC TIE/ BS CB 86A TRIP RELAY OPERATED SPS 86AO
21 ABC TIE/ BS CB 86B TRIP RELAY OPERATED SPS 86BO
22 ABC TIE/ BS CB 86A TRIP RELAY FAULTY SPS 86AU
23 ABC TIE/ BS CB 86B TRIP RELAY FAULTY SPS 86BU
24 ABC TIE CB CONTROL SWITCH DEVICE BYPASSED SPS BYSW In case of Line Reactor/ Bus Reactor/ ICT in main bays
25 ABC TIE CB CONTROL SWITCH DEVICE TROUBLE SPS
26 ABC TIE/ BS CB INTERLOCK ENABLED SPS INTL
27 ABC TIE/ BS 89A INTERLOCK ENABLED SPS INTL
28 ABC TIE/ BS 89B INTERLOCK ENABLED SPS INTL
29 ABC TIE/ BS 89AE1 INTERLOCK ENABLED SPS INTL
30 ABC TIE/ BS 89AE2 INTERLOCK ENABLED SPS INTL
31 ABC TIE/ BS 89BE1 INTERLOCK ENABLED SPS INTL
32 ABC TIE/ BS 89BE2 INTERLOCK ENABLED SPS INTL
33 ABC TIE/ BS GAS LKG R/Y/B STG1 REFILL SPS SF61 For GIS Bays
34 ABC TIE/ BS GAS LKG R/Y/B STG2 LOW SPS SF62
35 ABC TIE/ BS GAS LKG R/Y/B ZONE TRIP SPS SF6T
36 ABC TIE/ BS GAS LKG R/Y/B CB LOCKOUT/CB OPERATION LOCKOUT SPS SF6T
765 KV / 400 KV/ 220 KV FUTURE BAY
1 ABC FUTURE LINE BCU BAY IN MAINTENANCE MODE SPS BAYM
2 ABC FUTURE LINE BCU BCU DC SUPPLY FAIL-1/2 SPS BCUD
3 ABC FUTURE LINE BCU BCU UNHEALTHY SPS BCUH
4 ABC FUTURE LINE BCU BCU TIME SYNC ERROR SPS BCUC
5 ABC FUTURE LINE 89A INTERLOCK ENABLED SPS INTL
6 ABC FUTURE LINE 89AE INTERLOCK ENABLED SPS INTL
ICT (PRIMARY SIDE)
1 ABC ICT BCU BAY IN MAINTENANCE MODE SPS BAYM
2 ABC ICT BCU BCU DC SUPPLY FAIL-1/2 SPS BCUD
3 ABC ICT BCU BCU UNHEALTHY SPS BCUH
4 ABC ICT BCU BCU TIME SYNC ERROR SPS BCUC
5 ABC ICT CB CB MANUAL OPEN SPS MNOP
6 ABC ICT CB CB MANUAL CLOSE SPS MNCL
7 ABC ICT CB LBB PROTECTION OPERATED SPS LBBO
8 ABC ICT CB OPERATION LOCKOUT SPS OPLO
9 ABC ICT CB CB POLE DISCREPANCY OPERATED SPS PDIS
10 ABC ICT CB CB POLE DISCREPANCY WITH IN POLE OPERATED SPS PDIB
11 ABC ICT CB CB DC SUPPLY 1/2 FAIL SPS DC
12 ABC ICT CB CB AC SUPPLY FAIL SPS ACSP
13 ABC ICT CB CB SPRING DISCHARGE SPS SPRG
14 ABC ICT CB CB SF6 LOW ALARM SPS SF6L
15 ABC ICT CB CB TC1 Faulty SPS TC1F
16 ABC ICT CB CB TC2 Faulty SPS TC2F
17 ABC ICT CB CONTROL SWITCH DEVICE BYPASSED SPS BYSW
18 ABC ICT CB CONTROL SWITCH DEVICE TROUBLE SPS
19 ABC ICT XFMR_P DIFFERENTIAL RELAY OPTD. SPS TFDI
20 ABC ICT XFMR_P DIFF RELAY UNHEALTHY SPS DIRU
21 ABC ICT XFMR_P OVERFLUX ALARM SPS OFLA
22 ABC ICT XFMR_P OVERFLUX TRIP OPTD SPS OFLP
23 ABC ICT XFMR_P BACKUP O/C, E/F OPTD (HV) SPS BUOC
24 ABC ICT XFMR_P BACKUP O/C E/F RELAY UNHEALTHY SPS CFRL
25 ABC ICT XFMR_P 86A TRIP RELAY OPERATED SPS 86AO
26 ABC ICT XFMR_P 86B TRIP RELAY OPERATED SPS 86BO
27 ABC ICT XFMR_P 86A TRIP REALY UNHEALTHY SPS 86AU
28 ABC ICT XFMR_P 86B TRIP REALY UNHEALTHY SPS 86BU
29 ABC ICT XFMR_P SELECTED VT FUSE FAIL ALARM SPS VTFU
30 ABC ICT XFMR_P INTERTRIP OPTD. SPS TRPO
31 ABC ICT XFMR_P MAIN-1 BB PROTECTION OPTD SPS BB1P
32 ABC ICT XFMR_P MAIN-2 BB PROTECTION OPTD SPS BB2P
33 ABC ICT XFMR_P MAIN-1 BB PU UNIT FAULTY SPS B1UH
34 ABC ICT XFMR_P MAIN-2 BB PU UNIT FAULTY SPS B2UH
35 ABC ICT XFMR_P DC SOURCE-1 FAIL SPS DC-1
36 ABC ICT XFMR_P DC SOURCE-2 FAIL SPS DC-2
37 ABC ICT XFMR_P TAP CHANGER IN PROGRESS SPS TCIP
38 ABC ICT XFMR_P TAP CHANGER IN REMOTE SPS TCIR
39 ABC ICT XFMR_P TAP CHANGER OUT OF STEP SPS TCOS
40 ABC ICT XFMR_P TAP CHANGER PHASE DISCREPANCY SPS TCPD
41 ABC ICT XFMR_P TAP CHANGER IN FOLLOWER MODE SPS TCIF
42 ABC ICT XFMR_P TAP CHANGER IN INDEPENDENT MODE SPS TCII
43 ABC ICT XFMR_P TAP CHANGER IN MASTER MODE+E362 SPS TCIM
44 ABC ICT XFMR_P REF OPTD R PHASE SPS TFRF TO BE COMBINED IN CASE OF 3 PHASE ICT
45 ABC ICT XFMR_P BUCHHOLZ ALARM R PHASE SPS BUCA
46 ABC ICT XFMR_P BUCHHOLZ TRIP R PHASE SPS BUCT
47 ABC ICT XFMR_P OTI ALARM R PHASE SPS OTIA
48 ABC ICT XFMR_P OTI TRIP R PHASE SPS OTIT
49 ABC ICT XFMR_P WTI ALARM (HV/IV/LV) R PHASE SPS WTIA
50 ABC ICT XFMR_P WTI TRIP (HV/IV/LV) R PHASE SPS WTIT
51 ABC ICT XFMR_P PRV-1 TRIP R-PHASE SPS TFPR
52 ABC ICT XFMR_P PRV-2 TRIP R-PHASE SPS PRV2
53 ABC ICT XFMR_P OLTC OIL SURGE RELAY OPTD- R PHASE SPS OLTR
54 ABC ICT XFMR_P OLTC PRV TRIP OPTD- R PHASE SPS OLTP
55 ABC ICT XFMR_P OIL FLOW VALVE TRIP- R PHASE SPS
56 ABC ICT XFMR_P FANS FAIL TO START BANK A - R PHASE SPS FANF
57 ABC ICT XFMR_P FANS FAIL TO START BANK B - R PHASE SPS FANB
58 ABC ICT XFMR_P PUMPS FAIL TO START BANK A - R PHASE SPS PMPF
59 ABC ICT XFMR_P PUMPS FAIL TO START BANK B - R PHASE SPS PMPB
60 ABC ICT XFMR_P OIL FLOW LOW ALARM BANK R PHASE SPS TFOL
61 ABC ICT XFMR_P COMMON THERMAL O/L ALARM R PHASE SPS OLAL
62 ABC ICT XFMR_P COMMON THERMAL O/L TRIP R PHASE SPS CTTP
63 ABC ICT XFMR_P STANDBY SUPLY FAIL R PHASE SPS SBSF
64 ABC ICT XFMR_P MOISTURE ALARM R PHASE SPS MOSA
65 ABC ICT XFMR_P DGA ALARM R PHASE SPS DGAA
66 ABC ICT XFMR_P FIRE IN TRANSFORMER R PHASE SPS FRTR
67 ABC ICT XFMR_P DELUGE VALVE OPTD - R PHASE SPS DVTR
68 ABC ICT XFMR_P OLTC OIL LEVEL ALARM R PHASE SPS
69 ABC ICT XFMR_P DGA MONITORING DEVICE UNHEALTHY R PHASE SPS
70 ABC ICT XFMR_P SPARE ICT SELECTED FOR R PHASE SPS
71 ABC ICT XFMR_P REF OPTD Y PHASE SPS
72 ABC ICT XFMR_P REF PROTN Y PHASE BLOCKED SPS
73 ABC ICT XFMR_P BACKUP O/C OPTD (HV) Y PHASE SPS BUOC
74 ABC ICT XFMR_P BUCHHOLZ ALARM Y PHASE SPS BUCA
75 ABC ICT XFMR_P BUCHHOLZ TRIP Y PHASE SPS BUCT
76 ABC ICT XFMR_P OTI ALARM Y PHASE SPS OTIA
77 ABC ICT XFMR_P OTI TRIP Y PHASE SPS OTIT
78 ABC ICT XFMR_P WTI ALARM (HV/IV/LV) Y PHASE SPS WTIA
79 ABC ICT XFMR_P WTI TRIP (HV/IV/LV) Y PHASE SPS WTIT
80 ABC ICT XFMR_P PRV-1 TRIP Y PHASE SPS TFPR
81 ABC ICT XFMR_P PRV-2 TRIP Y PHASE SPS PRV2
82 ABC ICT XFMR_P OLTC OIL SURGE RELAY OPTD- Y PHASE SPS OLTR
83 ABC ICT XFMR_P OLTC PRV TRIP OPTD- Y PHASE SPS OLTP
84 ABC ICT XFMR_P OIL FLOW VALVE TRIP- Y PHASE SPS
85 ABC ICT XFMR_P FANS FAIL TO START BANK A - Y PHASE SPS FANF
86 ABC ICT XFMR_P FANS FAIL TO START BANK B - Y PHASE SPS FANB
87 ABC ICT XFMR_P PUMPS FAIL TO START BANK A - Y PHASE SPS PMPF
88 ABC ICT XFMR_P PUMPS FAIL TO START BANK B - Y PHASE SPS PMPB
89 ABC ICT XFMR_P OIL FLOW LOW ALARM BANK Y PHASE SPS TFOL
90 ABC ICT XFMR_P COMMON THERMAL O/L ALARM Y PHASE SPS OLAL
91 ABC ICT XFMR_P COMMON THERMAL O/L TRIP Y PHASE SPS CTTP
92 ABC ICT XFMR_P STANDBY SUPLY FAIL Y PHASE SPS SBSF
93 ABC ICT XFMR_P MOISTURE ALARM Y PHASE SPS MOSA
94 ABC ICT XFMR_P DGA ALARM Y PHASE SPS DGAA
95 ABC ICT XFMR_P FIRE IN TRANSFORMER Y PHASE SPS FRTY
96 ABC ICT XFMR_P DELUGE VALVE OPTD - Y PHASE SPS DVTY
97 ABC ICT XFMR_P OLTC OIL LEVEL ALARM Y PHASE SPS
98 ABC ICT XFMR_P DGA MONITORING DEVICE UNHEALTHY Y PHASE SPS
99 ABC ICT XFMR_P SPARE ICT SELECTED FOR Y PHASE SPS
100 ABC ICT XFMR_P REF OPTD B PHASE SPS
101 ABC ICT XFMR_P REF PROTN B PHASE BLOCKED SPS
102 ABC ICT XFMR_P BACKUP O/C OPTD (HV) B PHASE SPS BUOC
103 ABC ICT XFMR_P BUCHHOLZ ALARM B PHASE SPS BUCA
104 ABC ICT XFMR_P BUCHHOLZ TRIP B PHASE SPS BUCT
105 ABC ICT XFMR_P OTI ALARM B PHASE SPS OTIA
106 ABC ICT XFMR_P OTI TRIP B PHASE SPS OTIT
107 ABC ICT XFMR_P WTI ALARM (HV/IV/LV) B PHASE SPS WTIA
108 ABC ICT XFMR_P WTI TRIP (HV/IV/LV) B PHASE SPS WTIT
109 ABC ICT XFMR_P PRV-1 TRIP B PHASE SPS TFPR
110 ABC ICT XFMR_P PRV-2 TRIP B PHASE SPS PRV2
111 ABC ICT XFMR_P OLTC OIL SURGE RELAY OPTD- B PHASE SPS OLTR
112 ABC ICT XFMR_P OLTC PRV TRIP OPTD- B PHASE SPS OLTP
113 ABC ICT XFMR_P OIL FLOW VALVE TRIP- B PHASE SPS
114 ABC ICT XFMR_P FANS FAIL TO START BANK A - B PHASE SPS FANF
115 ABC ICT XFMR_P FANS FAIL TO START BANK B - B PHASE SPS FANB
116 ABC ICT XFMR_P PUMPS FAIL TO START BANK A - B PHASE SPS PMPF
117 ABC ICT XFMR_P PUMPS FAIL TO START BANK B - B PHASE SPS PMPB
118 ABC ICT XFMR_P OIL FLOW LOW ALARM BANK B PHASE SPS TFOL
119 ABC ICT XFMR_P COMMON THERMAL O/L ALARM B PHASE SPS OLAL
120 ABC ICT XFMR_P COMMON THERMAL O/L TRIP B PHASE SPS CTTP
121 ABC ICT XFMR_P STANDBY SUPLY FAIL B PHASE SPS SBSF
122 ABC ICT XFMR_P MOISTURE ALARM B PHASE SPS MOSA
123 ABC ICT XFMR_P DGA ALARM B PHASE SPS DGAA
124 ABC ICT XFMR_P FIRE IN TRANSFOMER B PHASE SPS FRTB
125 ABC ICT XFMR_P DELUGE VALVE ON - B PHASE SPS DVTB
126 ABC ICT XFMR_P OLTC OIL LEVEL ALARM B PHASE SPS
127 ABC ICT XFMR_P DGA MONITORING DEVICE UNHEALTHY B PHASE SPS
128 ABC ICT XFMR_P SPARE ICT SELECTED FOR B PHASE SPS
129 ABC ICT XFMR_P FANS FAIL TO START BANK A - B PHASE SPS FANF
130 ABC ICT XFMR_P FANS FAIL TO START BANK B - B PHASE SPS FANB
131 ABC ICT XFMR_P PUMPS FAIL TO START BANK A - B PHASE SPS PMPF
132 ABC ICT XFMR_P PUMPS FAIL TO START BANK B - B PHASE SPS PMPB
133 ABC ICT XFMR_P AVR OPERATION FAIL SPS
134 ABC ICT XFMR_P OLTC DRIVE MOTOR FAULTY SPS
135 ABC ICT XFMR_P OLTC ON LOWER LIMIT SPS
136 ABC ICT XFMR_P OLTC ON UPPER LIMIT SPS
137 ABC ICT XFMR_P NEUTRAL O/C PROTECTION OPTD SPS
138 ABC ICT XFMR_P NEUTRAL O/C RELAY UNHEALTHY SPS
139 ABC ICT XFMR_P DIRECT WDG TEMP MONITORING TRIP R PHASE SPS
140 ABC ICT XFMR_P BACKUP IMPEDANCE TRIP Z1 SPS BUZ1
141 ABC ICT XFMR_P BACKUP IMPEDANCE TRIP Z2 SPS BUZ2
142 ABC ICT XFMR_P BACKUP IMPEDANCE TRIP Z3 SPS BUZ3
143 ABC ICT XFMR_P BACKUP IMPEDANCE TRIP Z4 SPS BUZ4
144 ABC ICT XFMR_P BU IMPEDANCE RELAY FAULTY SPS
145 ABC ICT XFMR_P VT FUSE FAIL ALARM SPS VTFU
146 ABC ICT XFMR_P POWER SWING BLOCKING SPS
140 ABC ICT XFMR_P CABLE BOX BCUZ ALARM OK SPS
141 ABC ICT XFMR_P CABLEBOX BCUZTRIP RESET SPS
142 ABC ICT XFMR_P H2 GAS ALARM-1 SPS
143 ABC ICT XFMR_P H2 GAS ALARM-2 SPS
144 ABC ICT XFMR_P ICT CABLBOX RPH PRD OPT SPS
145 ABC ICT XFMR_P ICT CABLBOX YPH PRD OPT SPS
146 ABC ICT XFMR_P ICT CABLBOX BPH PRD OPT SPS
147 ABC ICT CB INTERLOCK ENABLED SPS INTL
148 ABC ICT 89A INTERLOCK ENABLED SPS INTL
149 ABC ICT 89B INTERLOCK ENABLED SPS INTL
150 ABC ICT 89AE INTERLOCK ENABLED SPS INTL
151 ABC ICT 89BE INTERLOCK ENABLED SPS INTL
152 ABC ICT 89TR INTERLOCK ENABLED SPS INTL
153 ABC ICT 89TY INTERLOCK ENABLED SPS INTL
154 ABC ICT 89TB INTERLOCK ENABLED SPS INTL
155 ABC ICT 89TS1R INTERLOCK ENABLED SPS INTL
156 ABC ICT 89TS1Y INTERLOCK ENABLED SPS INTL
157 ABC ICT 89TS1B INTERLOCK ENABLED SPS INTL
158 ABC ICT 89TER INTERLOCK ENABLED SPS INTL
159 ABC ICT 89TEY INTERLOCK ENABLED SPS INTL
160 ABC ICT 89TEB INTERLOCK ENABLED SPS INTL
161 ABC ICT 89TS2EB INTERLOCK ENABLED SPS INTL
162 ABC ICT GAS LKG R/Y/B STG1 REFILL SPS SF61 For GIS Bays
163 ABC ICT GAS LKG R/Y/B STG2 LOW SPS SF62
164 ABC ICT GAS LKG R/Y/B ZONE TRIP SPS SF6T
165 ABC ICT GAS LKG R/Y/B CB LOCKOUT/CB OPERATION LOCKOUT SPS SF6T
1 ABC SPARE ICT XFMR_P REF OPTD SPARE SPS
2 ABC SPARE ICT XFMR_P REF PROTN SPARE BLOCKED SPS
3 ABC SPARE ICT XFMR_P BACKUP O/C OPTD (HV) SPARE SPS BUOC
4 ABC SPARE ICT XFMR_P BUCHHOLZ ALARM SPARE SPS BUCA
5 ABC SPARE ICT XFMR_P BUCHHOLZ TRIP SPARE SPS BUCT
6 ABC SPARE ICT XFMR_P OTI ALARM SPARE SPS OTIA
7 ABC SPARE ICT XFMR_P OTI TRIP SPARE SPS OTIT
8 ABC SPARE ICT XFMR_P WTI ALARM (HV/IV/LV) SPARE SPS WTIA
9 ABC SPARE ICT XFMR_P WTI TRIP (HV/IV/LV) SPARE SPS WTIT
10 ABC SPARE ICT XFMR_P PRV-1 TRIP SPARE SPS TFPR
11 ABC SPARE ICT XFMR_P PRV-2 TRIP SPARE SPS PRV2
12 ABC SPARE ICT XFMR_P OLTC OIL SURGE RELAY OPTD- SPARE SPS OLTR
13 ABC SPARE ICT XFMR_P OIL FLOW LOW ALARM BANK SPARE SPS TFOL
14 ABC SPARE ICT XFMR_P OLTC PRV TRIP OPTD- SPARE SPS OLTP
15 ABC SPARE ICT XFMR_P OIL FLOW VALVE TRIP- B PHASE SPS
16 ABC SPARE ICT XFMR_P COMMON THERMAL O/L ALARM SPARE SPS OLAL
17 ABC SPARE ICT XFMR_P COMMON THERMAL O/L TRIP SPARE SPS CTTP
18 ABC SPARE ICT XFMR_P STANDBY SUPLY FAIL SPARE SPS SBSF
19 ABC SPARE ICT XFMR_P FANS FAIL TO START BANK A - SPARE SPS FANF
20 ABC SPARE ICT XFMR_P FANS FAIL TO START BANK B - SPARE SPS FANB
21 ABC SPARE ICT XFMR_P PUMPS FAIL TO START BANK A - SPARE SPS PMPF
22 ABC SPARE ICT XFMR_P PUMPS FAIL TO START BANK B - SPARE SPS PMPB
23 ABC SPARE ICT XFMR_P MOISTURE ALARM SPARE SPS MOSA
24 ABC SPARE ICT XFMR_P DGA ALARM SPARE SPS DGAA
25 ABC SPARE ICT XFMR_P FIRE IN TREASFORMER - SPARE SPS FRTS
26 ABC SPARE ICT XFMR_P DELUGE VALVE ON - SPARE SPS DVTS
27 ABC SPARE ICT XFMR_P OLTC OIL LEVEL ALARM SPARE SPS
28 ABC SPARE ICT XFMR_P DGA MONITORING DEVICE UNHEALTHY SPARE SPS
29 ABC SPARE ICT GAS LKG R/Y/B STG1 REFILL SPS SF61 For GIS Bays
30 ABC SPARE ICT GAS LKG R/Y/B ZONE TRIP SPS SF6T
ICT (SECONDARY SIDE)
1 ABC ICT BCU BAY IN MAINTENANCE MODE SPS BAYM
2 ABC ICT BCU BCU DC SUPPLY FAIL-1/2 SPS BCUD
3 ABC ICT BCU BCU UNHEALTHY SPS BCUH
4 ABC ICT BCU BCU TIME SYNC ERROR SPS BCUC
5 ABC ICT CB CB MANUAL OPEN SPS MNOP
6 ABC ICT CB CB MANUAL CLOSE SPS MNCL
7 ABC ICT CB LBB PROTECTION OPERATED SPS LBBO
8 ABC ICT CB OPERATION LOCKOUT SPS OPLO
9 ABC ICT CB CB POLE DISCREPANCY OPERATED SPS PDIS
10 ABC ICT CB CB DC SUPPLY 1/2 FAIL SPS DC
11 ABC ICT CB CB AC SUPPLY FAIL SPS ACSP
12 ABC ICT CB CB SPRING/AIR/OIL LOW SPS SPRG
13 ABC ICT CB CB SF6 LOW ALARM SPS SF6L
14 ABC ICT CB CB TC1 Faulty SPS TC1F
15 ABC ICT CB CB TC2 Faulty SPS TC2F
16 ABC ICT XFMR_S LV - OVERFLUX ALARM SPS OFLA
17 ABC ICT XFMR_S LV - OVERFLUX OPTD SPS OFLP
18 ABC ICT XFMR_S LV - BACKUP O/C OPTD SPS BUOC
19 ABC ICT XFMR_S LV - BACKUP E/F OPTD SPS BUEF
20 ABC ICT XFMR_S SELECTED VT FUSE FAIL ALARM SPS VTFU
21 ABC ICT XFMR_S 86A TRIP RELAY OPERATED SPS 86AO
22 ABC ICT XFMR_S 86B TRIP RELAY OPERATED SPS 86BO
23 ABC ICT XFMR_S 86A TRIP REALY UNHEALTHY SPS 86AU
24 ABC ICT XFMR_S 86B TRIP REALY UNHEALTHY SPS 86BU
25 ABC ICT XFMR_S MAIN-1 BB PROTECTION OPTD SPS BB1P
26 ABC ICT XFMR_S MAIN-2 BB PROTECTION OPTD SPS BB2P
27 ABC ICT XFMR_S MAIN-1 BB PU UNIT FAULTY SPS B1UH
28 ABC ICT XFMR_S MAIN-2 BB PU UNIT FAULTY SPS B2UH
29 ABC ICT XFMR_S DC SOURCE-1 FAIL SPS DC-1
30 ABC ICT XFMR_S DC SOURCE-2 FAIL SPS DC-2
31 ABC ICT CB INTERLOCK ENABLED SPS INTL
32 ABC ICT 89A INTERLOCK ENABLED SPS INTL
33 ABC ICT 89B INTERLOCK ENABLED SPS INTL
34 ABC ICT 89L INTERLOCK ENABLED SPS INTL
35 ABC ICT 89T INTERLOCK ENABLED SPS INTL
36 ABC ICT 89AE INTERLOCK ENABLED SPS INTL
37 ABC ICT 89LE1 INTERLOCK ENABLED SPS INTL
38 ABC ICT 89LE2 INTERLOCK ENABLED SPS INTL
LINE SERIES REACTOR/ BUS SERIES REACTOR
1 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR CB INTERLOCK ENABLED SPS INTL
2 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR 89A INTERLOCK ENABLED SPS INTL
3 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR 89AE INTERLOCK ENABLED SPS INTL
4 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR 89B INTERLOCK ENABLED SPS INTL
5 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR 89BE INTERLOCK ENABLED SPS INTL
6 ABC LSR / BSR 89L/ 89BSR INTERLOCK ENABLED SPS INTL
7 ABC LSR / BSR 89LE/ 89BSRE INTERLOCK ENABLED SPS INTL
8 ABC LSR 89LSR INTERLOCK ENABLED SPS INTL In case of Line Series Reactor
9 ABC LSR 89LSR1 INTERLOCK ENABLED SPS INTL
10 ABC LSR 89LSR2 INTERLOCK ENABLED SPS INTL
11 ABC LSR 89LSR2- ES INTERLOCK ENABLED SPS INTL
12 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR BCU BAY IN MAINTENANCE MODE SPS BAYM
13 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR BCU BCU DC SUPPLY FAIL-1/2 SPS BCUD
14 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR BCU BCU UNHEALTHY SPS BCUH
15 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR BCU BCU TIME SYNC ERROR SPS BCUC
16 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR CB CB MANUAL OPEN SPS MNOP CB corresponding to main bay
17 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR CB CB MANUAL CLOSE SPS MNCL
18 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR CB LBB PROTECTION OPERATED SPS LBBO
19 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR CB OPERATION LOCKOUT SPS OPLO
20 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR CB CB POLE DISCREPANCY OPERATED SPS PDIS
21 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR CB CB POLE DISCREPANCY WITH IN POLE OPERATED SPS PDIB
22 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR CB CB DC SUPPLY 1/2 FAIL SPS DC
23 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR CB CB AC SUPPLY FAIL SPS ACSP
24 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR CB CB SPRING DISCHARGE SPS SPRG
25 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR CB CB SF6 LOW ALARM SPS SF6L
26 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR CB CB TC1 Faulty SPS TC1F
27 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR CB CB TC2 Faulty SPS TC2F
28 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE 86A TRIP RELAY OPTD. SPS
29 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE 86B TRIP RELAY OPTD. SPS
30 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE 86A TRIP RELAY UNHEALTHY SPS
31 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE 86B TRIP RELAY UNHEALTHY SPS
32 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE DIFFERENTIAL PROTN OPTD. 87 R2 SPS
33 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE BACK-UP IMPEDANCE PROTN OPTD SPS
34 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE BACK-UP IMPEDANCE PROTN OPTD - R PHASE SPS
35 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE BACK-UP IMPEDANCE PROTN OPTD - Y PHASE SPS
36 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE BACK-UP IMPEDANCE PROTN OPTD - B PHASE SPS
37 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE BACKUP E/F OPTD. (HV) SPS
38 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE BACKUP O/C OPTD. (HV) SPS
39 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE CVT FUSE FAIL (B/U IMP) SPS
40 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE DIFF. PROTECTION OPTD 87R1 SPS
41 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE DIFF. PROTECTION OPTD 87R1 - R PHASE SPS
42 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE DIFF. PROTECTION OPTD 87R1 - Y PHASE SPS
43 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE DIFF. PROTECTION OPTD 87R1 - B PHASE SPS
44 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE DC SOURCE-1 FAIL SPS
45 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE DC SOURCE-2 FAIL SPS
46 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE DIFFERENTIAL RELAY UNHEALTHY 87R2 SPS
47 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE BACKUP IMPEDANCE RELAY UNHEALTHY SPS
48 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE DIFFERENTIAL RELAY UNHEALTHY 87R1 SPS
49 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE BAY IN MAINTENANCE MODE SPS
50 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE 87 R2 TIME SYNCHRONISATION ERROR SPS
51 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE 21 R TIME SYNCHRONISATION ERROR SPS
52 ABC LINE SERIES REACTOR/ BUS SERIES REACTOR RE 87 R1 TIME SYNCHRONISATION ERROR SPS
FIXED SERIES CAPACITOR (FSC)
1 ABC FSC 89ES2 EARTH SWITCH 2 OPERATION INTERLOCK SPS
2 ABC FSC LINE DE-ENRGIZED SPS
3 ABC FSC FAULT TO PLATFORM TRIP-1/2 SPS
4 ABC FSC PERMANENT BYPASS SPS
5 ABC FSC 52BBR BPCB STATUS DISCREPANCY SPS
6 ABC FSC 52BBR BPCB AUX CONTACT DISCORDANCE SPS
7 ABC FSC 52BBR GENRAL LOCKOUT/MIN OIL PRESSURE LOCKOUT SPS
8 ABC FSC 52BBR BPCB POLE DISCREPANCY SPS
9 ABC FSC 52BBR BPCB DC 1/2 FAIL SPS
10 ABC FSC 52BBR BPCB LOSS OF SF6 SPS
11 ABC FSC 52BBR 1POLE REINSERTION DURING AR SPS
12 ABC FSC 52BBR BYPASS BREAKER FAIL TO OPEN SPS
13 ABC FSC 52BBR BYPASS BREAKER SWITCHWED WITHOUT COMMAND SPS
14 ABC FSC 52BBR BYPASS BREAKER FAIL TO CLOSE SPS
15 ABC FSC 52BBR BYPASS CB SPRING DISCHARGE/FAILURE SPS
16 ABC FSC 52BBR BPCB OPERATION INTERLOCK SPS
17 ABC FSC 89MBS BYPASS MBS OPERATION INTERLOCK SPS
18 ABC FSC 89DS1 BYPASS CAP ISO 1 OPERATION INTERLOCK SPS
19 ABC FSC 89DS1 DISCONNECTOR 1 PHASE DISAGREEMENT SPS
20 ABC FSC 89DS1 GENERAL ALARM SPS
21 ABC FSC 89MBS BYPASS DISCONNECTOR ALARM SPS
22 ABC FSC 89DS2 DISCONNECTOR 2 PHASE DISAGREEMENT SPS
23 ABC FSC 89DS2 GENERAL ALARM SPS
24 ABC FSC CAP CAPACITOR UNBALANCE ALARM SPS
25 ABC FSC CAP CAPACITOR UNBALANCED TRIP SPS
26 ABC FSC CAP CAPACITOR OVERLOAD ALARM SPS
27 ABC FSC CAP CAPACITOR OVERLOAD TRIP SPS
28 ABC FSC MOV MOV TRIP SPS
29 ABC FSC PROT PROTECTION SYSTEM FAIL-1 SPS
30 ABC FSC PROT PROTECTION SYSTEM FAIL-2 SPS
31 ABC FSC PROT SIGNAL TRANSMISSION POWER FAIL SPS
32 ABC FSC PROT MASTER TRIP SPS
33 ABC FSC PROT GPS TIME SYNC FAIL SPS
34 ABC FSC PROT DIRECT TRIP RECEIVE SPS
35 ABC FSC PROT COMMUNICATION CHANNEL FAIL SPS
36 ABC FSC PROT BYPASS CAP ISO 2 OPERATION INTERLOCK SPS
37 ABC FSC PROT MOV FAIL SPS
38 ABC FSC PROT CONTROL SYSTEM 1 HARDWARE ALARM SPS
39 ABC FSC PROT PROTECTION SYSTEM 1 HARDWARE ALARM SPS
40 ABC FSC PROT CONTROL & PROTECTION SYSTEM 1 COMMUNICATION FAULT SPS
41 ABC FSC PROT PROTECTION SYSTEM 1 MEASURING SYSTEM WARNING SPS
42 ABC FSC PROT CONTROL SYSTEM 2 HARDWARE ALARM SPS
43 ABC FSC PROT PROTECTION SYSTEM 2 HARDWARE ALARM SPS
44 ABC FSC PROT CONTROL & PROTECTION SYSTEM 2 COMMUNICATION FAULT SPS
45 ABC FSC PROT PROTECTION SYSTEM 2 MEASURING SYSTEM WARNING SPS
46 ABC FSC PROT CONTROL & PROTECTION SYSTEM POWER SUPPLY ALARM SPS
47 ABC FSC PROT CONTROL & PROTECTION SYSTEM REDUNDANCY DISTURBED SPS
48 ABC FSC PROT EARTH SWITCH 1 ALARM SPS
49 ABC FSC PROT EARTH SWITCH 2 ALARM SPS
50 ABC FSC PROT DISCONNECTOR SWITCH 1 ALARM SPS
51 ABC FSC PROT DISCONNECTOR SWITCH 2 ALARM SPS
52 ABC FSC PROT LINE EARTH SWITCH ALARM SPS
53 ABC FSC PROT BYPASS BREAKER ALARM SPS
54 ABC FSC PROT MAIN BYPASS SWITCH ALARM SPS
55 ABC FSC PROT LINE SIDE 1: DE-ENERGIZED SPS
56 ABC FSC PROT LINE SIDE 2: DE-ENERGIZED SPS
57 ABC FSC 52BBR BYPASS BREAKER LOCAL/REMOTE CONTROL SPS
58 ABC FSC 52BBR BYPASS BREAKER MAIN CLOSING COIL UNHEALTHY SPS
59 ABC FSC 52BBR BYPASS BREAKER BACKUP CLOSING COIL UNHEALTHY SPS
60 ABC FSC PROT FIRE FIGHTING SYSTEM: ALARM SPS
61 ABC FSC PROT-1 SYSTEM 1: MOV OVERLOAD SPS
62 ABC FSC PROT-1 SYSTEM 1: MOV TEMPERATURE TRIP SPS
63 ABC FSC PROT-1 SYSTEM 1: MOV TEMPERATURE GRADIENT LOW SET SPS
64 ABC FSC PROT-1 SYSTEM 1: MOV TEMPERATURE GRADIENT HIGH SET SPS
65 ABC FSC PROT-1 SYSTEM 1: MOV UNBALANCE SPS
66 ABC FSC PROT-1 SYSTEM 1: MOV HIGH CURRENT SPS
67 ABC FSC PROT-1 SYSTEM 1: SPARK GAP FAILED TO TRIGGER SPS
68 ABC FSC PROT-1 SYSTEM 1: SPARK GAP DELAYED TRIGGER SPS
69 ABC FSC PROT-1 SYSTEM 1: SPARK GAP PROLONGED CONDUCTION SPS
70 ABC FSC PROT-1 SYSTEM 1: SPARK GAP SELF TRIGGER SPS
71 ABC FSC PROT-1 SYSTEM 1: SPARK GAP TRIGGER (R,Y,B) SPS
72 ABC FSC PROT-1 SYSTEM 1: BYPASS BREAKER FAIL SPS
73 ABC FSC PROT-1 SYSTEM 1: PREVENT REINSERTION ACTIVE SPS
74 ABC FSC PROT-1 SYSTEM 1: PERMANENT BYPASS SPS
75 ABC FSC PROT-1 SYSTEM 1: TEMPORARY BYPASS PHASE(R,Y,B) SPS
76 ABC FSC PROT-1 SYSTEM 1: REINSERTION SPS
77 ABC FSC PROT-1 SYSTEM 1: LINE TRIP SPS
78 ABC FSC PROT-2 SYSTEM 2: MOV OVERLOAD SPS
79 ABC FSC PROT-2 SYSTEM 2: MOV TEMPERATURE TRIP SPS
80 ABC FSC PROT-2 SYSTEM 2: MOV TEMPERATURE GRADIENT LOW SET SPS
81 ABC FSC PROT-2 SYSTEM 2: MOV TEMPERATURE GRADIENT HIGH SET SPS
82 ABC FSC PROT-2 SYSTEM 2: MOV UNBALANCE SPS
83 ABC FSC PROT-2 SYSTEM 2: MOV HIGH CURRENT SPS
84 ABC FSC PROT-2 SYSTEM 2: SPARK GAP FAILED TO TRIGGER SPS
85 ABC FSC PROT-2 SYSTEM 2: SPARK GAP DELAYED TRIGGER SPS
86 ABC FSC PROT-2 SYSTEM 2: SPARK GAP PROLONGED CONDUCTION SPS
87 ABC FSC PROT-2 SYSTEM 2: SPARK GAP SELF TRIGGER SPS
88 ABC FSC PROT-2 SYSTEM 2: SPARK GAP TRIGGER (R,Y,B) SPS
89 ABC FSC PROT-2 SYSTEM 2: BYPASS BREAKER FAIL SPS
90 ABC FSC PROT-2 SYSTEM 2: PREVENT REINSERTION ACTIVE SPS
91 ABC FSC PROT-2 SYSTEM 2: PERMANENT BYPASS SPS
92 ABC FSC PROT-2 SYSTEM 2: TEMPORARY BYPASS PHASE(R,Y,B) SPS
93 ABC FSC PROT-2 SYSTEM 2: REINSERTION SPS
94 ABC FSC PROT-2 SYSTEM 2: LINE TRIP SPS
765 KV / 400 KV/ 220 KV BUS BAR
1 765kV BUS-X BUS M1 BB Z1 operated SPS BB17
2 765kV BUS-X BUS M2 BB Z1 operated SPS BB18
3 765kV BUS-X BUS M1 BB Z1 out of service SPS BB9
4 765kV BUS-X BUS M2 BB Z1 out of service SPS BB30
5 765kV BUS-X BUS M1 BB Z1 CT Trouble SPS M1TB
6 765kV BUS-X BUS M2 BB Z1 CT Trouble SPS M2TB
7 765kV BUS-X BUS Main-1 BB relay Healthy SPS BBH
8 765kV BUS-X BUS Main- 2 BB relay Healthy SPS BBH
9 765kV BUS-X BUS MAIN-1 BB ZONE-1 CT SUPVN. ALARM SPS
10 765kV BUS-X BUS MAIN-2 BB ZONE-1 CT SUPVN. ALARM SPS
11 765kV BUS-X BUS BUSBAR-1 IN/OUT SWITCH IN OUT POSITION SPS
12 765kV BUS-X BUS BUSBAR-2 IN/OUT SWITCH IN OUT POSITION SPS
13 765kV BUS-X BUS MAIN-1 CZ CT SUPV ALARM SPS
14 765kV BUS-X BUS MAIN-2 CZ CT SUPV ALARM SPS
1 ABC BUS COUPLER BCU BAY IN MAINTENANCE MODE SPS BAYM
2 ABC BUS COUPLER BCU BCU DC SUPPLY FAIL-1/2 SPS BCUD
3 ABC BUS COUPLER BCU BCU UNHEALTHY SPS BCUH
4 ABC BUS COUPLER BCU BCU TIME SYNC ERROR SPS BCUC
5 ABC BUS COUPLER CB CB MANUAL OPEN SPS MNOP
6 ABC BUS COUPLER CB CB MANUAL CLOSE SPS MNCL
7 ABC BUS COUPLER CB LBB PROTECTION OPERATED SPS LBBO
8 ABC BUS COUPLER CB OPERATION LOCKOUT SPS OPLO
9 ABC BUS COUPLER CB CB POLE DISCREPANCY OPERATED SPS PDIS
10 ABC BUS COUPLER CB CB DC SUPPLY 1/2 FAIL SPS DC
11 ABC BUS COUPLER CB CB AC SUPPLY FAIL SPS ACSP
12 ABC BUS COUPLER CB CB SPRING/AIR/OIL LOW SPS SPRG
13 ABC BUS COUPLER CB CB SF6 LOW ALARM SPS SF6L
14 ABC BUS COUPLER CB CB TC1 Faulty SPS TC1F
15 ABC BUS COUPLER CB CB TC2 Faulty SPS TC2F
16 ABC BUS COUPLER CB INTERLOCK ENABLED SPS INTL
17 ABC BUS COUPLER 89A INTERLOCK ENABLED SPS INTL
18 ABC BUS COUPLER 89B INTERLOCK ENABLED SPS INTL
19 ABC BUS COUPLER 89AE1 INTERLOCK ENABLED SPS INTL
20 ABC BUS COUPLER 89AE2 INTERLOCK ENABLED SPS INTL
21 ABC BUS COUPLER 89BE1 INTERLOCK ENABLED SPS INTL
22 ABC BUS COUPLER 89BE2 INTERLOCK ENABLED SPS INTL
TRANSFER BUS COUPLER
1 ABC TRANSFER BUS COUPLER BCU BAY IN MAINTENANCE MODE SPS BAYM
2 ABC TRANSFER BUS COUPLER BCU BCU DC SUPPLY FAIL-1/2 SPS BCUD
3 ABC TRANSFER BUS COUPLER BCU BCU UNHEALTHY SPS BCUH
4 ABC TRANSFER BUS COUPLER BCU BCU TIME SYNC ERROR SPS BCUC
5 ABC TRANSFER BUS COUPLER CB CB MANUAL OPEN SPS MNOP
6 ABC TRANSFER BUS COUPLER CB CB MANUAL CLOSE SPS MNCL
7 ABC TRANSFER BUS COUPLER CB LBB PROTECTION OPERATED SPS LBBO
8 ABC TRANSFER BUS COUPLER CB OPERATION LOCKOUT SPS OPLO
9 ABC TRANSFER BUS COUPLER CB CB POLE DISCREPANCY OPERATED SPS PDIS
10 ABC TRANSFER BUS COUPLER CB CB DC SUPPLY 1/2 FAIL SPS DC
11 ABC TRANSFER BUS COUPLER CB CB AC SUPPLY FAIL SPS ACSP
12 ABC TRANSFER BUS COUPLER CB CB SPRING/AIR/OIL LOW SPS SPRG
13 ABC TRANSFER BUS COUPLER CB CB SF6 LOW ALARM SPS SF6L
14 ABC TRANSFER BUS COUPLER CB CB TC1 Faulty SPS TC1F
15 ABC TRANSFER BUS COUPLER CB CB TC2 Faulty SPS TC2F
16 ABC TRANSFER BUS COUPLER CB AUTORECLOSE LOCKOUT SPS ARLO
17 ABC TRANSFER BUS COUPLER CB AUTORECLOSE OPERATED SPS AROP
18 ABC TRANSFER BUS COUPLER LINE AUTORECLOSE UNSUCCESFUL SPS ARFM
19 ABC TRANSFER BUS COUPLER LINE 86A TRIP RELAY OPERATED SPS 86AO
20 ABC TRANSFER BUS COUPLER LINE 86B TRIP RELAY OPERATED SPS 86BO
21 ABC TRANSFER BUS COUPLER LINE 86A TRIP RELAY FAULTY SPS 86AU
22 ABC TRANSFER BUS COUPLER LINE 86B TRIP RELAY FAULTY SPS 86BU
23 ABC TRANSFER BUS COUPLER CB INTERLOCK ENABLED SPS INTL
24 ABC TRANSFER BUS COUPLER 89A INTERLOCK ENABLED SPS INTL
25 ABC TRANSFER BUS COUPLER 89B INTERLOCK ENABLED SPS INTL
26 ABC TRANSFER BUS COUPLER 89T INTERLOCK ENABLED SPS INTL
27 ABC TRANSFER BUS COUPLER 89AE INTERLOCK ENABLED SPS INTL
28 ABC TRANSFER BUS COUPLER 89TE1 INTERLOCK ENABLED SPS INTL
29 ABC TRANSFER BUS COUPLER 89TE2 INTERLOCK ENABLED SPS INTL
AUXILLIARY SYSTEM
1 220VDC DCDB 220V_DCDB-1 220V DCDB -1 EARTH FAULT SPS
2 220VDC DCDB 220V_DCDB-2 220V DCDB -2 EARTH FAULT SPS
3 220VDC BCHRG BATCHRG220V-1 220V BATTERY CHARGER-1 TROUBLE SPS
4 220VDC BCHRG BATCHRG220V-2 220V BATTERY CHARGER-2 TROUBLE SPS
5 48 VDC BCHRG BATCHRG48V-1 48V BATTERY CHARGER-1 TROUBLE SPS
6 48 VDC BCHRG BATCHRG48V-2 48V BATTERY CHARGER-2 TROUBLE SPS
7 415 V FP EPUMP ELECTRIC MOTOR FIRE WATER PUMP RUNNING SPS
8 415 V FP EPUMP ELECTRIC MOTOR FIRE WATER PUMP FAILS TO START SPS
9 415 V FP EPUMP ELECTRIC PUMP IN AUTO MODE SPS
10 415 V FP EPUMP CONTROL SUPPLY FAIL SPS
11 415 V FP DPUMP DIESEL ENGINE FIRE WATER PUMP FAILS TO START SPS
12 415 V FP DPUMP DIESEL ENGINE FIRE WATER PUMP RUNNING SPS
13 415 V FP DPUMP DIESEL ENGINE PUMP IN AUTO MODE SPS
14 415 V FP DPUMP DIESEL ENGINE BATTERY CHARGER-1 ON SPS
15 415 V FP DPUMP DIESEL ENGINE BATTERY CHARGER-2 ON SPS
16 415 V FP DPUMP DIESEL ENGINE FUEL LEVEL LOW SPS
17 415 V FP DPUMP CONTROL SUPPLY FAIL SPS
18 415 V FP DPUMP DIESEL PUMP OVER SPEED TRIP SPS
19 415 V FP DPUMP DIESEL PUMP LOW OIL PRESSURE TRIP SPS
20 415 V FP DPUMP DIESEL ENGINE HIGH TEMPERATURE ALARM SPS
21 415 V FP SMOKE ALARM CONTROL ROOM ZONE-1 FIRE DETECTED SPS
22 415 V FP SMOKE ALARM CONTROL ROOM ZONE-2 FIRE DETECTED SPS
23 415 V FP SMOKE ALARM CONTROL ROOM ZONE-3 FIRE DETECTED SPS
24 415 V FP SMOKE ALARM CONTROL ROOM ZONE-4 FIRE DETECTED SPS
25 415 V FP SMOKE ALARM 765KV KIOSK-1 FIRE DETECTED SPS
26 415 V FP SMOKE ALARM 400kV KIOSK-1 FIRE DETECTED SPS
27 415 V FP FIREPROTN WATER STORAGE TANK-1 WATER LEVEL LOW SPS
28 415 V FP FIREPROTN WATER STORAGE TANK-2 WATER LEVEL LOW SPS
29 415 V FP FIREPROTN FIRE FIGHTING TANK HEADER PRESSURE LEVEL LOW SPS
30 415 V FP FIREPROTN FIRE ANNAUNCIATION PANEL FAULTY SPS
31 415 V FP FIREPROTN COMMON FIRE ALARM SPS
32 415 V FP FIREPROTN CONTROL SUPPLY FAIL SPS
33 415 V FP JPUMP-1 JOCKEY PUMP-1 RUNNING SPS
34 415 V FP JPUMP-1 JOCKEY PUMP-1 FAILS TO START SPS
35 415 V FP JPUMP-1 JOCKEY PUMP-1 IN AUTO MODE SPS
36 415 V FP JPUMP-1 SUPERVISION OF CONTROL SUPPLY SPS
37 415 V FP JPUMP-1 JOCKEY PUMP-1 TRIP SPS
38 415 V FP JPUMP-2 JOCKEY PUMP-2 RUNNING SPS
39 415 V FP JPUMP-2 JOCKEY PUMP-2 FAILS TO START SPS
40 415 V FP JPUMP-2 JOCKEY PUMP-2 IN AUTO MODE SPS
41 415 V FP JPUMP-2 SUPERVISION OF CONTROL SUPPLY SPS
42 415 V FP JPUMP-2 JOCKEY PUMP-2 TRIP SPS
43 415 V FP G_703_ICT-1 FIRE IN ICT-1 SPS
44 415 V FP G_703_ICT-1 DELUGE SYSTEM OPERATING FOR ICT-1 SPS
45 415 V FP G_701_BR-1 FIRE IN BUS REACTOR SPS
46 415 V FP G_701_BR-1 DELUGE SYSTEM OPERATING FOR BUS REACTOR SPS
47 415 V FP G_703_ICT-1 FF NIS Out of service SPS
48 415 V FP G_703_ICT-1 FF NIS System ON SPS
49 415 V FP G_703_ICT-1 FF NISPNRV Closed SPS
50 415 V FP G_703_ICT-1 FF NIS Fire Detector Trip SPS
51 415 V FP G_703_ICT-1 FF NIS Buchholz Relay Trip SPS
52 415 V FP G_703_ICT-1 FF NIS Oil Drain Valve open SPS
53 415 V FP G_703_ICT-1 FF NIS Extinction in Progress SPS
54 415 V FP G_703_ICT-1 FF NIS Oil Drain Valve closed SPS
55 415 V FP G_703_ICT-1 FF NIS Gas inlet valve closed SPS
56 415 V FP G_703_ICT-1 FF NIS Cylinder pressure low SPS
57 415 V FP G_703_ICT-1 FF NIS Diff. Relay trip SPS
58 415 V FP G_703_ICT-1 FF NIS PRV Trip SPS
59 415 V FP G_703_ICT-1 FF NIS Transformer Trip SPS
60 415 V FP G_703_ICT-1 FF NIS Line Fault Fire Detector SPS
61 415 V FP G_703_ICT-1 FF NIS Line Fault Diff. Relay SPS
62 415 V FP G_703_ICT-1 FF NIS Line Fault Buchholz Relay SPS
63 415 V FP G_703_ICT-1 FF NIS Line fault PRV SPS
64 415 V FP G_703_ICT-1 FF NIS Line fault Transformer Trip SPS
65 415 V FP G_703_ICT-1 FF NIS Line Fault PNRV SPS
66 415 V FP G_703_ICT-1 FF NIS Hooter for DC supply fail SPS
67 415 V FP G_703_ICT-1 FF NIS Contactor for DC Supply Fail SPS
69 415 V FP G_703_ICT-1 Hydrant System in Service SPS
70 415 V FP G_703_ICT-1 Hydrant System Faulty SPS
71 415 V FP G_703_ICT-1 Hydrant Syestem On SPS
72 415 V COMMON PLCC PLCC EXCHANGE FAIL SPS
73 415 V COMMON GPS TIME SYNCH. SIGNAL ABSENT SPS
74 415 V AIRCON G_KIOSK_1 765KV KIOSK-1 HIGH TEMP ALARM SPS
75 415 V AIRCON F_KIOSK_1 400KV KIOSK-1 HIGH TEMP ALARM SPS
76 415 V SYSTEM AUX_SYSTEM SUBSTATION MAIN CONTROL ON NTAMC SPS
77 415 V SYSTEM AUX_SYSTEM SUBSTATION MAIN CONTROL ON RTAMC SPS
78 415 V SYSTEM AUX_SYSTEM SUBSTATION MAIN CONTROL ON BACK UP NTAMC SPS
79 415 V SYSTEM AUX_SYSTEM SUBSTATION AUX CONTROL ON NTAMC SPS
80 415 V SYSTEM AUX_SYSTEM SUBSTATION AUXCONTROL ON RTAMC SPS
81 415 V SYSTEM AUX_SYSTEM SUBSTATION AUX CONTROL ON BACK UP NTAMC SPS
82 415 V DG Set DGSET-1 ALTERNATOR ON SPS
83 415 V DG Set DGSET-1 CHARGER 1 ON SPS
84 415 V DG Set DGSET-1 CHARGER 2 ON SPS
85 415 V DG Set DGSET-1 ENGINE OVERHEATING SPS
86 415 V DG Set DGSET-1 HIGH COOLING WATER TEMP. SPS
87 415 V DG Set DGSET-1 LOW OIL PRESSURE TRIP SPS
88 415 V DG Set DGSET-1 DG SET FAILED TO START IN 30 SEC SPS
89 415 V DG Set DGSET-1 LACK OF FUEL SPS
90 415 V DG Set DGSET-1 LOW LEVEL IN DAILY SERVICE FUEL TANK SPS
91 415 V DG Set DGSET-1 HIGH SPEED DIESEL TANK LEVEL LOW SPS
92 415 V DG Set DGSET-1 OVERSPEED TRIP SPS
93 415 V DG Set DGSET-1 DG I/C PROTN OPTD(ALT FAULT,DIFF ETC) SPS
94 415 V DG Set DGSET-1 CONTROL SUPPLY FAIL SPS
95 415 V DG Set DGSET-1 DG PROTECTION OPERATED (O/C, E/F, DIFF.) SPS
96 415 V DG Set DGSET-1 DG PROTECTION U/V OPERATED SPS
97 415 V DG Set DGSET-1 AMF PANEL REMOTE SWITCH INDICATION SPS
98 415 V DG Set DGSET-1 DG OVERLOAD SPS
99 415 V DG Set DGSET-1 PHASE SEQUENCE NEGATIVE ALARM SPS
100 415 V LTSUP ACDB-1 ACDB INCOMER-1 O/C PROTN. RLY OPTD SPS
101 415 V LTSUP ACDB-1 ACDB INCOMER-1 E/F PROTN. RLY OPTD SPS
102 415 V LTSUP ACDB-1 ACDB INCOMER-1 U/V PROTN. RLY OPTD SPS
103 415 V LTSUP ACDB-BC SUPERVISION OF CONTROL SUPPLY SPS
104 415 V LTSUP ACDB-2 ACDB INCOMER-2 O/C PROTN. RLY OPTD SPS
105 415 V LTSUP ACDB-2 ACDB INCOMER-2 E/F PROTN. RLY OPTD SPS
106 415 V LTSUP ACDB-2 ACDB INCOMER-2 U/V PROTN. RLY OPTD SPS
107 415 V LTSUP MSB-1 AUX. TRAFO-1 BUCHHOLZ ALARM SPS
108 415 V LTSUP MSB-1 AUX. TRAFO-1 WTI ALARM SPS
109 415 V LTSUP MSB-1 AUX. TRAFO-1 OTI ALARM SPS
110 415 V LTSUP MSB-1 AUX. TRAFO-1 BUCHHOLZ TRIP SPS
111 415 V LTSUP MSB-1 AUX. TRAFO-1 WTI TRIP SPS
112 415 V LTSUP MSB-1 AUX. TRAFO-1 OTI TRIP SPS
113 415 V LTSUP MSB-1 I/C-1 O/C PROTECTION RELAY TRIP SPS
114 415 V LTSUP MSB-1 I/C-1 E/F PROTECTION RELAY TRIP SPS
115 415 V LTSUP MSB-1 MSB BUS-1 U/V OPTD SPS
116 415 V LTSUP MSB-1 PHASE SEQUENCE NEGATIVE ALARM SPS
117 415 V LTSUP MSB_BC SUPERVISION OF CONTROL SUPPLY SPS
118 415 V LTSUP MSB-2 AUX. TRAFO-2 BUCHHOLZ ALARM SPS
119 415 V LTSUP MSB-2 AUX. TRAFO- 2 WTI ALARM SPS
120 415 V LTSUP MSB-2 AUX. TRAFO-2 OTI ALARM SPS
121 415 V LTSUP MSB-2 AUX. TRAFO-2 BUCHHOLZ TRIP SPS
122 415 V LTSUP MSB-2 AUX. TRAFO-2 WTI TRIP SPS
123 415 V LTSUP MSB-2 AUX. TRAFO-2 OTI TRIP SPS
124 415 V LTSUP MSB-2 I/C-2 O/C PROTECTION RELAY TRIP SPS
125 415 V LTSUP MSB-2 I/C-2 E/F PROTECTION RELAY TRIP SPS
126 415 V LTSUP MSB-2 MSB BUS-2 U/V OPTD SPS
127 415 V LTSUP MSB-2 PHASE SEQUENCE NEGATIVE ALARM SPS
128 33 KV LTSUP TERTIARY CB INTERLOCK ENABLED SPS
129 33 KV LTSUP TERTIARY ISO INTERLOCK ENABLED SPS
130 33 KV LTSUP TERTIARY CB TRIPPED ON PROTN SPS
131 SAS GATEWAY GATEWAY-1 FAIL SPS
132 SAS GATEWAY GATEWAY-2 FAIL SPS
133 SAS LOCAL_HMI LOCAL HMI-1 FAIL SPS
134 SAS LOCAL_HMI LOCAL HMI-2 FAIL SPS
135 AUXBCU AUX BCU UNHEALTHY SPS
136 AUXBCU AUX BCU TIME SYNC ERROR SPS
STATCOM (SIEMENS)
1 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-52 INTERLOCK ENABLED SPS
2 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89A INTERLOCK ENABLED SPS
3 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89B INTERLOCK ENABLED SPS
4 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89AE INTERLOCK ENABLED SPS
5 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-89BE INTERLOCK ENABLED SPS
6 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX HV Main Bay Transformer Connected SPS
7 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX HV Main Bay PSD Error SPS
8 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX HV Main Bay CT SF6 Loss Alarm SPS
9 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX HV Main Bay CT SF6 Lockout Alarm SPS
10 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-52 HV Main Bay CB SF6 Loss Alarm SPS
11 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-52 HV Main Bay CB SF6 Lockout Alarm SPS
12 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-52 HV Main Bay CB DC-1/2 Fail SPS
13 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-52 HV Main Bay CB Pole Descripency Operated SPS
14 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-52 HV Main Bay CB TC-1 Faulty SPS
15 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX-52 HV Main Bay CB TC-2 Faulty SPS
16 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX HV Main Bay 86.1 Relay Operated SPS
17 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX HV Main Bay 86.2 Relay Operated SPS
18 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX HV Main Bay CB Spring Discharge SPS
19 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX HV Main Bay LBB Operated SPS
20 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX HV Main Bay LBB Unhealthy SPS
21 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX HV Main Bay PSD Unhealthy SPS
22 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY 4XX HV Main Bay BCU Unhealthy SPS
23 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY PROTN LOCKOUT RELAYS ACTIVATED HV MAIN BAY SPS
24 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q2 R PH INTERLOCK ENABLED SPS
25 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q2 Y PH INTERLOCK ENABLED SPS
26 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q2 B PH INTERLOCK ENABLED SPS
27 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q3-R-PH INTERLOCK ENABLED SPS
28 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q3 Y PH INTERLOCK ENABLED SPS
29 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q3 B PH INTERLOCK ENABLED SPS
30 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q51 R PH INTERLOCK ENABLED SPS
31 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q51 Y PH INTERLOCK ENABLED SPS
32 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q51 B PH INTERLOCK ENABLED SPS
33 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) 4XX-Q52 INTERLOCK ENABLED SPS
34 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R BUCHHOLZ RELAY 1 ALARM SPS
35 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R BUCHHOLZ RELAY 2 ALARM SPS
36 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y BUCHHOLZ RELAY 1 ALARM SPS
37 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y BUCHHOLZ RELAY 2 ALARM SPS
38 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B BUCHHOLZ RELAY 1 ALARM SPS
39 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B BUCHHOLZ RELAY 2 ALARM SPS
40 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S BUCHHOLZ RELAY 1 ALARM SPS
41 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S BUCHHOLZ RELAY 2 ALARM SPS
42 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R FAN FAILURE SPS
43 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y FAN FAILURE SPS
44 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B FAN FAILURE SPS
45 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S FAN FAILURE SPS
46 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01 PROTECTION RELAY - 1 TRIP SPS
47 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01 PROTECTION RELAY - 2 TRIP SPS
48 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01 PROTECTION RELAY - 1 FAILURE SPS
49 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01 PROTECTION RELAY - 2 FAILURE SPS
50 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY HV Tie Bay Transformer Connected SPS
51 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY HV Tie Bay PSD Error SPS
52 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-CT HV Tie Bay CT SF6 Loss Alarm SPS
53 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-CT HV Tie Bay CT SF6 Lockout Alarm SPS
54 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-52 HV Tie Bay CB SF6 Loss Alarm SPS
55 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-52 HV Tie Bay CB SF6 Lockout Alarm SPS
56 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-52 HV Tie Bay CB DC-1/2 Fail SPS
57 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-52 HV Tie Bay CB Pole Descripency Operated SPS
58 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-52 HV Tie Bay CB TC-1 Faulty SPS
59 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-52 HV Tie Bay CB TC-2 Faulty SPS
60 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-52 HV Tie Bay CB Spring Discharge SPS
61 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY HV Tie Bay 86.1 Relay Operated SPS
62 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY HV Tie Bay 86.2 Relay Operated SPS
63 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY HV Tie Bay LBB Operated SPS
64 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY HV Tie Bay LBB Unhealthy SPS
65 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY HV Tie Bay PSD Unhealthy SPS
66 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY HV Tie Bay BCU Unhealthy SPS
67 4YY STATCOM HV SIDE TIE BAY TIE BAY PROTN LOCKOUT RELAYS ACTIVATED HV TIE BAY SPS
68 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-52 INTERLOCK ENABLED SPS
69 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-89A INTERLOCK ENABLED SPS
70 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-89B INTERLOCK ENABLED SPS
71 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-89AE INTERLOCK ENABLED SPS
72 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY-89BE INTERLOCK ENABLED SPS
73 4ZZ FUTURE 89A INTERLOCK ENABLED SPS
74 4ZZ FUTURE 89AE INTERLOCK ENABLED SPS
75 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q1 R PH INTERLOCK ENABLED SPS
76 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q1 Y PH INTERLOCK ENABLED SPS
77 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q1 B PH INTERLOCK ENABLED SPS
78 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q2 R PH INTERLOCK ENABLED SPS
79 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q2 Y PH INTERLOCK ENABLED SPS
80 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q2 B PH INTERLOCK ENABLED SPS
81 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q12 R PH INTERLOCK ENABLED SPS
82 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q12 Y PH INTERLOCK ENABLED SPS
83 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q12 B PH INTERLOCK ENABLED SPS
84 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q13 R PH INTERLOCK ENABLED SPS
85 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q13 Y PH INTERLOCK ENABLED SPS
86 J0 STATCOM MV SIDE BAY COUPLING TRANSFORMER (MV) J0-Q13 B PH INTERLOCK ENABLED SPS
87 STATCOM STATCOM MV BUS BAR PROTECTION RELAY - 1 TRIP SPS
88 STATCOM STATCOM MV BUS BAR PROTECTION RELAY - 2 TRIP SPS
89 STATCOM STATCOM MV BUS BAR PROTECTION RELAY - 1 FAILURE SPS
90 STATCOM STATCOM MV BUS BAR PROTECTION RELAY - 2 FAILURE SPS
91 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER MV-H01 PROTECTION RELAY - 1 TRIP SPS
92 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER MV-H01 PROTECTION RELAY - 2 TRIP SPS
93 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER MV-H01 PROTECTION RELAY - 1 FAILURE SPS
94 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER MV-H01 PROTECTION RELAY - 2 FAILURE SPS
95 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER J01-Q0 INTERLOCK ENABLED SPS
96 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER J01-Q1 INTERLOCK ENABLED SPS
97 J01 STATCOM AUX. TRANF. BAY AUX TRANSFORMER J01-Q52 INTERLOCK ENABLED SPS
98 J02 STATCOM NGT BAY GND TRANSFORMER MV-H02 PROTECTION RELAY - 1 TRIP SPS
99 J02 STATCOM NGT BAY GND TRANSFORMER MV-H02 PROTECTION RELAY - 2 TRIP SPS
100 J02 STATCOM NGT BAY GND TRANSFORMER MV-H02 PROTECTION RELAY - 1 FAILURE SPS
101 J02 STATCOM NGT BAY GND TRANSFORMER MV-H02 PROTECTION RELAY - 2 FAILURE SPS
102 J11 STATCOM VSC-1 BAY VSC-1 MV-J11 PROTECTION RELAY - 1 TRIP SPS
103 J11 STATCOM VSC-1 BAY VSC-1 MV-J11 PROTECTION RELAY - 2 TRIP SPS
104 J11 STATCOM VSC-1 BAY VSC-1 MV-J11 PROTECTION RELAY - 3 TRIP SPS
105 J11 STATCOM VSC-1 BAY VSC-1 MV-J11 PROTECTION RELAY - 1 FAILURE SPS
106 J11 STATCOM VSC-1 BAY VSC-1 MV-J11 PROTECTION RELAY - 2 FAILURE SPS
107 J11 STATCOM VSC-1 BAY VSC-1 MV-J11 PROTECTION RELAY - 3 FAILURE SPS
108 J11 STATCOM VSC-1 BAY VSC-1 MV-J11 LOCKOUT RELAYS ACTIVATED SPS
109 J11 STATCOM VSC-1 BAY VSC-1 MV-J11 STATCOM READY FOR OPERATION SPS
110 J11 STATCOM VSC-1 BAY VSC-1 MV-J11 SEQUENCE FAILURE SPS
111 J11 STATCOM VSC-1 BAY VSC-1 MV-J11 SEQUENCE RUNNING SPS
112 J11 STATCOM VSC-1 BAY VSC-1 J11 Q0 INTERLOCK ENABLED SPS
113 J11 STATCOM VSC-1 BAY VSC-1 J11 Q1 INTERLOCK ENABLED SPS
114 J11 STATCOM VSC-1 BAY VSC-1 J11 Q5 INTERLOCK ENABLED SPS
115 J12 STATCOM VSC-2 BAY VSC-2 MV-J12 PROTECTION RELAY - 1 TRIP SPS
116 J12 STATCOM VSC-2 BAY VSC-2 MV-J12 PROTECTION RELAY - 2 TRIP SPS
117 J12 STATCOM VSC-2 BAY VSC-2 MV-J12 PROTECTION RELAY - 3 TRIP SPS
118 J12 STATCOM VSC-2 BAY VSC-2 MV-J12 PROTECTION RELAY - 1 FAILURE SPS
119 J12 STATCOM VSC-2 BAY VSC-2 MV-J12 PROTECTION RELAY - 2 FAILURE SPS
120 J12 STATCOM VSC-2 BAY VSC-2 MV-J12 PROTECTION RELAY - 3 FAILURE SPS
121 J12 STATCOM VSC-2 BAY VSC-2 MV-J12 STATCOM READY FOR OPERATION SPS
122 J12 STATCOM VSC-2 BAY VSC-2 MV-J12 SEQUENCE FAILURE SPS
123 J12 STATCOM VSC-2 BAY VSC-2 MV-J12 SEQUENCE RUNNING SPS
124 J12 STATCOM VSC-2 BAY VSC-2 MV-J12 LOCKOUT RELAYS ACTIVATED SPS
125 J12 STATCOM VSC-2 BAY VSC-2 J12 Q0 INTERLOCK ENABLED SPS
126 J12 STATCOM VSC-2 BAY VSC-2 J12 Q1 INTERLOCK ENABLED SPS
127 J12 STATCOM VSC-2 BAY VSC-2 J12 Q5 INTERLOCK ENABLED SPS
128 J21 STATCOM MSR-1 BAY MSR-1 MV-J21 PROTECTION RELAY - 1 TRIP SPS
129 J21 STATCOM MSR-1 BAY MSR-1 MV-J21 PROTECTION RELAY - 2 TRIP SPS
130 J21 STATCOM MSR-1 BAY MSR-1 MV-J21 LOCKOUT RELAYS ACTIVATED SPS
131 J21 STATCOM MSR-1 BAY MSR-1 MV-J21 PROTECTION RELAY - 1 FAILURE SPS
132 J21 STATCOM MSR-1 BAY MSR-1 MV-J21 PROTECTION RELAY - 2 FAILURE SPS
133 J21 STATCOM MSR-1 BAY MSR-1 J21 Q0 INTERLOCK ENABLED SPS
134 J21 STATCOM MSR-1 BAY MSR-1 J21 Q1 INTERLOCK ENABLED SPS
135 J21 STATCOM MSR-1 BAY MSR-1 J21 Q5 INTERLOCK ENABLED SPS
136 J22 STATCOM MSR-2 BAY MSR-2 MV-J22 PROTECTION RELAY - 1 TRIP SPS
137 J22 STATCOM MSR-2 BAY MSR-2 MV-J22 PROTECTION RELAY - 2 TRIP SPS
138 J22 STATCOM MSR-2 BAY MSR-2 MV-J22 PROTECTION RELAY - 1 FAILURE SPS
139 J22 STATCOM MSR-2 BAY MSR-2 MV-J22 PROTECTION RELAY - 2 FAILURE SPS
140 J22 STATCOM MSR-2 BAY MSR-2 MV-J22 LOCKOUT RELAYS ACTIVATED SPS
141 J22 STATCOM MSR-2 BAY MSR-2 J22 Q0 INTERLOCK ENABLED SPS
142 J22 STATCOM MSR-2 BAY MSR-2 J22 Q1 INTERLOCK ENABLED SPS
143 J22 STATCOM MSR-2 BAY MSR-2 J22 Q5 INTERLOCK ENABLED SPS
144 J31 STATCOM MSC-1 BAY MSC-1 MV-J31 PROTECTION RELAY - 1 TRIP SPS
145 J31 STATCOM MSC-1 BAY MSC-1 MV-J31 PROTECTION RELAY - 2 TRIP SPS
146 J31 STATCOM MSC-1 BAY MSC-1 MV-J31 PROTECTION RELAY - 1 FAILURE SPS
147 J31 STATCOM MSC-1 BAY MSC-1 MV-J31 PROTECTION RELAY - 2 FAILURE SPS
148 J31 STATCOM MSC-1 BAY MSC-1 MV-J31 LOCKOUT RELAYS ACTIVATED SPS
149 J31 STATCOM MSC-1 BAY MSC-1 J31 Q0 INTERLOCK ENABLED SPS
150 J31 STATCOM MSC-1 BAY MSC-1 J31 Q1 INTERLOCK ENABLED SPS
151 J31 STATCOM MSC-1 BAY MSC-1 J31 Q5 INTERLOCK ENABLED SPS
152 J32 STATCOM MSC-2 BAY MSC-2 MV-J32 PROTECTION RELAY - 1 TRIP SPS
153 J32 STATCOM MSC-2 BAY MSC-2 MV-J32 PROTECTION RELAY - 2 TRIP SPS
154 J32 STATCOM MSC-2 BAY MSC-2 MV-J32 PROTECTION RELAY - 1 FAILURE SPS
155 J32 STATCOM MSC-2 BAY MSC-2 MV-J32 PROTECTION RELAY - 2 FAILURE SPS
156 J32 STATCOM MSC-2 BAY MSC-2 MV-J32 LOCKOUT RELAYS ACTIVATED SPS
157 J32 STATCOM MSC-2 BAY MSC-2 J32 Q0 INTERLOCK ENABLED SPS
158 J32 STATCOM MSC-2 BAY MSC-2 J32 Q1 INTERLOCK ENABLED SPS
159 J32 STATCOM MSC-2 BAY MSC-2 J32 Q5 INTERLOCK ENABLED SPS
160 STATCOM STATCOM STATCOM OPERATION ACKNOWLEDGE VSC 1 SPS
161 STATCOM STATCOM STATCOM OPERATION ACKNOWLEDGE VSC 2 SPS
162 STATCOM STATCOM STATCOM OPERATION EMERGENCY TRIP SPS
163 STATCOM STATCOM STATCOM OPERATION LOCAL HMI SELECTED SPS
164 STATCOM STATCOM STATCOM OPERATION REMOTE HMI SELECTED SPS
165 STATCOM STATCOM STATCOM OPERATION RCI SELECTED SPS
166 STATCOM STATCOM STATCOM PROTECTION SYSTEM-1 System 1: TRIP - OVERVOLTAGE HV DETECTED SPS
167 STATCOM STATCOM STATCOM PROTECTION SYSTEM-1 System 1: TRIP - LOCKOUT RELAY ACTIVATED (VSC 1) SPS
168 STATCOM STATCOM STATCOM PROTECTION SYSTEM-1 System 1: ESOF FROM CCS OR MMS (VSC 1) SPS
169 STATCOM STATCOM STATCOM PROTECTION SYSTEM-1 System 1: ESOF DUE TO CONVERTER FAILURE (VSC 1) SPS
170 STATCOM STATCOM STATCOM PROTECTION SYSTEM-1 System 1: ESOF AFTER EXTENDED CONVERTER BLOCKING T > 5 SEC (VSC 1) SPS
171 STATCOM STATCOM STATCOM PROTECTION SYSTEM-1 System 1: ESOF BY SEQUENCE FAULT - CP1 (VSC 1) SPS
172 STATCOM STATCOM STATCOM PROTECTION SYSTEM-1 System 1: ESOF BY FIREFIGHTING - IR SENSOR (VSC 1) SPS
173 STATCOM STATCOM STATCOM PROTECTION SYSTEM-1 System 1: TRIP - LOCKOUT RELAY ACTIVATED (VSC 2) SPS
174 STATCOM STATCOM STATCOM PROTECTION SYSTEM-1 System 1: ESOF FROM CCS OR MMS (VSC 2) SPS
175 STATCOM STATCOM STATCOM PROTECTION SYSTEM-1 System 1: ESOF DUE TO CONVERTER FAILURE (VSC 2) SPS
176 STATCOM STATCOM STATCOM PROTECTION SYSTEM-1 System 1: ESOF AFTER EXTENDED CONVERTER BLOCKING T > 5 SEC (VSC 2) SPS
177 STATCOM STATCOM STATCOM PROTECTION SYSTEM-1 System 1: ESOF BY SEQUENCE FAULT - CP1 (VSC 2) SPS
178 STATCOM STATCOM STATCOM PROTECTION SYSTEM-1 System 1: ESOF BY FIREFIGHTING - IR SENSOR (VSC 2) SPS
179 STATCOM STATCOM STATCOM PROTECTION SYSTEM 1 TDC 1 FAULT SPS
180 STATCOM STATCOM STATCOM PROTECTION SYSTEM-1 SYSTEM 1: NO EXTERNAL TIME SYNCHRONISATION SPS
181 STATCOM STATCOM STATCOM PROTECTION SYSTEM-2 System 2: TRIP - OVERVOLTAGE HV DETECTED SPS
182 STATCOM STATCOM STATCOM PROTECTION SYSTEM-2 System 2: TRIP - LOCKOUT RELAY ACTIVATED (VSC 1) SPS
183 STATCOM STATCOM STATCOM PROTECTION SYSTEM-2 System 2: ESOF FROM CCS OR MMS (VSC 1) SPS
184 STATCOM STATCOM STATCOM PROTECTION SYSTEM-2 System 2: ESOF DUE TO CONVERTER FAILURE (VSC 1) SPS
185 STATCOM STATCOM STATCOM PROTECTION SYSTEM-2 System 2: ESOF AFTER EXTENDED CONVERTER BLOCKING T > 5 SEC (VSC 1) SPS
186 STATCOM STATCOM STATCOM PROTECTION SYSTEM-2 System 2: ESOF BY SEQUENCE FAULT - CP1 (VSC 1) SPS
187 STATCOM STATCOM STATCOM PROTECTION SYSTEM-2 System 2: ESOF BY FIREFIGHTING - IR SENSOR (VSC 1) SPS
188 STATCOM STATCOM STATCOM PROTECTION SYSTEM-2 System 2: TRIP - LOCKOUT RELAY ACTIVATED (VSC 2) SPS
189 STATCOM STATCOM STATCOM PROTECTION SYSTEM-2 System 2: ESOF FROM CCS OR MMS (VSC 2) SPS
190 STATCOM STATCOM STATCOM PROTECTION SYSTEM-2 System 2: ESOF DUE TO CONVERTER FAILURE (VSC 2) SPS
191 STATCOM STATCOM STATCOM PROTECTION SYSTEM-2 System 2: ESOF AFTER EXTENDED CONVERTER BLOCKING T > 5 SEC (VSC 2) SPS
192 STATCOM STATCOM STATCOM PROTECTION SYSTEM-2 System 2: ESOF BY SEQUENCE FAULT - CP1 (VSC 2) SPS
193 STATCOM STATCOM STATCOM PROTECTION SYSTEM-2 System 2: ESOF BY FIREFIGHTING - IR SENSOR (VSC 2) SPS
194 STATCOM STATCOM STATCOM PROTECTION SYSTEM 2 TDC 2 FAULT SPS
195 STATCOM STATCOM STATCOM PROTECTION SYSTEM-2 SYSTEM 2: NO EXTERNAL TIME SYNCHRONISATION SPS
196 STATCOM STATCOM STATCOM PROTECTION EMERGENCY TRIP TRIP FROM EMERGENCY BUTTON SPS
197 STATCOM STATCOM STATCOM PROTECTION TFR TRIGGER TFR TRIGGER CMD SPS
198 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: STATCOM CONTROL WARNING SPS
199 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: STATCOM CONTROL FAULT SPS
200 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: STATCOM CONTROL TRIP SPS
201 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: COMMUNICATION SUMMARY WARNING SPS
202 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: COMMUNICATION SUMMARY FAULT SPS
203 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: STATCOM BUILDING ALARM (AIR CONDITION) SPS
204 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: AC AUXILIARY SUPPLY WARNING SPS
205 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: AC AUXILIARY SUPPLY FAULT SPS
206 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: STATCOM PLUS PROTECTION SYSTEM WARNING SPS
207 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: STATCOM PLUS PROTECTION SYSTEM FAULT SPS
208 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: STATCOM PLUS PROTECTION SYSTEM TRIP SPS
209 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: DFR FAULT SPS
210 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: DC AUXILIARY SUPPLY WARNING SPS
211 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: DC AUXILIARY SUPPLY FAULT SPS
212 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: STATCOM NOT READY SPS
213 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: HV BUSBAR FAULT SPS
214 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: HV BUSBAR TRIP SPS
215 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: TRANSFORMER WARNING SPS
216 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: TRANSFORMER FAULT SPS
217 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: TRANSFORMER TRIP SPS
218 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MV BUSBAR FAULT SPS
219 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: VSC 1 WARNING SPS
220 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: VSC 1 FAULT SPS
221 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: VSC 1 TRIP SPS
222 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: VSC 2 WARNING SPS
223 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: VSC 2 FAULT SPS
224 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: VSC 2 TRIP SPS
225 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSR 1 WARNING SPS
226 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSR 1 FAULT SPS
227 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSR 1 TRIP SPS
228 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSR 2 WARNING SPS
229 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSR 2 FAULT SPS
230 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSR 2 TRIP SPS
231 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSC 1 WARNING SPS
232 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSC 1 FAULT SPS
233 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSC 1 TRIP SPS
234 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSC 2 WARNING SPS
235 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSC 2 FAULT SPS
236 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSC 2 TRIP SPS
237 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: COOLING SYSTEM VSC 1 WARNING SPS
238 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: COOLING SYSTEM VSC 1 FAULT SPS
239 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: COOLING SYSTEM VSC 1 TRIP SPS
240 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: COOLING SYSTEM VSC 2 WARNING SPS
241 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: COOLING SYSTEM VSC 2 FAULT SPS
242 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: COOLING SYSTEM VSC 2 TRIP SPS
243 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: VSC 1 PROTECTION WARNING SPS
244 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: VSC 1 PROTECTION FAULT SPS
245 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: VSC 1 PROTECTION TRIP SPS
246 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: VSC 2 PROTECTION WARNING SPS
247 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: VSC 2 PROTECTION FAULT SPS
248 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: VSC 2 PROTECTION TRIP SPS
249 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSR 1 PROTECTION WARNING SPS
250 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSR 1 PROTECTION FAULT SPS
251 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSR 1 PROTECTION TRIP SPS
252 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSR 2 PROTECTION WARNING SPS
253 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSR 2 PROTECTION FAULT SPS
254 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSC 1 PROTECTION WARNING SPS
255 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSC 1 PROTECTION FAULT SPS
256 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSC 1 PROTECTION TRIP SPS
257 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSC 2 PROTECTION WARNING SPS
258 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSC 2 PROTECTION FAULT SPS
259 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSC 2 PROTECTION TRIP SPS
260 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: HV LINK PROTECTION WARNING SPS
261 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: HV LINK PROTECTION TRIP SPS
262 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: TRANSFORMER T0 PROTECTION WARNING SPS
263 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: TRANSFORMER T0 PROTECTION FAULT SPS
264 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: TRANSFORMER T0 PROTECTION TRIP SPS
265 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: STATCOM MV BUSBAR PROTECTION WARNING SPS
266 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: STATCOM MV BUSBAR PROTECTION FAULT SPS
267 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: STATCOM MV BUSBAR PROTECTION TRIP SPS
268 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: LV GROUNDING TRANSFORMER PROTECTION WARNING SPS
269 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: LV GROUNDING TRANSFORMER PROTECTION FAULT SPS
270 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: LV GROUNDING TRANSFORMER PROTECTION TRIP SPS
271 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: AUX TRANSFORMER PROTECTION WARNING SPS
272 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: AUX TRANSFORMER PROTECTION FAULT SPS
273 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: AUX TRANSFORMER PROTECTION TRIP SPS
274 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: UPS WARNING SPS
275 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: FIRE PROTECTION SYSTEM ALARM SPS
276 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: AUX VOLTAGE STABILIZER ALARM SPS
277 STATCOM STATCOM STATCOM GROUP ALARM GROUP MESSAGE: MSR 2 PROTECTION TRIP SPS
278 STATCOM AUX STATCOM AUX DG SET DG SET - ALTERNATOR ON SPS
279 STATCOM AUX STATCOM AUX DG SET DG SET - DG INCOMING BREAKER ON SPS
280 STATCOM AUX STATCOM AUX DG SET DG SET - ENGINE FAULT SPS
281 STATCOM AUX STATCOM AUX BUILDING FIRE ALARM FIRE ALARM SYSTEM - BUILDING FIRE DETECTED SPS
282 STATCOM AUX STATCOM AUX TRANSFORMER FIRE ALARM FIRE ALARM SYSTEM TRANSFORMER FIRE DETECTED SPS
283 STATCOM AUX STATCOM AUX COOLING SYSTEM UPS UPS FOR VALVE COOLING - SWITCH ON MAINTENANCE BYPASS POSITION SPS
284 STATCOM AUX STATCOM AUX COOLING SYSTEM UPS UPS FOR VALVE COOLING - AC SUPPLY FAULT SPS
285 STATCOM AUX STATCOM AUX COOLING SYSTEM UPS UPS FOR VALVE COOLING - LOW DC VOLTAGE SPS
286 STATCOM AUX STATCOM AUX COOLING SYSTEM UPS UPS FOR VALVE COOLING - LOAD ON STATIC BYPASS POSITION SPS
287 STATCOM AUX STATCOM AUX COOLING SYSTEM UPS UPS FOR VALVE COOLING - COMMON ALARM SPS
288 STATCOM AUX STATCOM AUX COOLING SYSTEM UPS UPS FOR VALVE COOLING - LOAD ON BATTERY SPS
289 STATCOM AUX STATCOM AUX COOLING SYSTEM UPS UPS FOR VALVE COOLING - FAN FAILURE SPS
290 STATCOM AUX STATCOM AUX AIRCON CONVERTER ROOM-1 AIR CONDITIONER TROUBLE SPS
291 STATCOM AUX STATCOM AUX AIRCON CONVERTER ROOM-2 AIR CONDITIONER TROUBLE SPS
292 STATCOM AUX STATCOM AUX BCHARG220-1 220V DCDB 1 BATTERY CHARGER - AC SUPPLY FAULT SPS
293 STATCOM AUX STATCOM AUX BCHARG220-1 220V DCDB 1 BATTERY CHARGER - CHARGER TROUBLE SPS
294 STATCOM AUX STATCOM AUX BCHARG220-2 220V DCDB 2 BATTERY CHARGER - AC SUPPLY FAULT SPS
295 STATCOM AUX STATCOM AUX BCHARG220-2 220V DCDB 2 BATTERY CHARGER - CHARGER TROUBLE SPS
1 XX KV FUTURE BAY 89A INTERLOCK ENABLED SPS
2 XX KV FUTURE BAY 89AE INTERLOCK ENABLED SPS
3 XX KV FUTURE& COUPLING T/F-1 TIE 52 CB MANUAL OPEN SPS
4 XX KV FUTURE& COUPLING T/F-1 TIE 52 CB MANUAL CLOSE SPS
5 XX KV FUTURE& COUPLING T/F-1 TIE 89BE EARTH SWITCH OPEN SPS
6 XX KV FUTURE& COUPLING T/F-1 TIE 89BE EARTH SWITCH CLOSE SPS
7 XX KV FUTURE& COUPLING T/F-1 TIE BCU BCU DC SUPPLY -1/2 FAIL SPS
8 XX KV FUTURE& COUPLING T/F-1 TIE BCU BCU UNHEALTHY SPS
9 XX KV FUTURE& COUPLING T/F-1 TIE BCU BCU TIME SYNC ERROR SPS
10 XX KV FUTURE& COUPLING T/F-1 TIE 52 CB OPERATION LOCKOUT SPS
11 XX KV FUTURE& COUPLING T/F-1 TIE 52 CB POLE DISCREPANCY OPTD. SPS
12 XX KV FUTURE& COUPLING T/F-1 TIE 52 CB TC-1 FAULTY SPS
13 XX KV FUTURE& COUPLING T/F-1 TIE 52 CB TC-2 FAULTY SPS
14 XX KV FUTURE& COUPLING T/F-1 TIE 52 CB LBB OPTD. SPS
15 XX KV FUTURE& COUPLING T/F-1 TIE 52 LBB Unhealthy SPS
16 XX KV FUTURE& COUPLING T/F-1 TIE BAY IN MAINTENANCE MODE SPS
17 XX KV FUTURE& COUPLING T/F-1 TIE 86A TRIP RELAY OPTD. SPS
18 XX KV FUTURE& COUPLING T/F-1 TIE 86B TRIP RELAY OPTD. SPS
19 XX KV FUTURE& COUPLING T/F-1 TIE 52 INTERLOCK ENABLED SPS
20 XX KV FUTURE& COUPLING T/F-1 TIE 89A INTERLOCK ENABLED SPS
21 XX KV FUTURE& COUPLING T/F-1 TIE 89AE INTERLOCK ENABLED SPS
22 XX KV FUTURE& COUPLING T/F-1 TIE 89B INTERLOCK ENABLED SPS
23 XX KV FUTURE& COUPLING T/F-1 TIE 89BE INTERLOCK ENABLED SPS
24 XX KV FUTURE& COUPLING T/F-1 TIE 52 CB COMPRESSOR / PUMP ON SPS
25 XX KV FUTURE& COUPLING T/F-1 TIE 52 CB AC SUPPLY FAIL SPS
26 XX KV FUTURE& COUPLING T/F-1 TIE 52 CB LOSS OF SF6 STG1 SPS
27 XX KV FUTURE& COUPLING T/F-1 TIE 52 CB LOSS OF SF6 STG2 SPS
28 XX KV FUTURE& COUPLING T/F-1 TIE 52 CB TROUBLE ALARM SPS
29 XX KV FUTURE& COUPLING T/F-1 TIE 86A TRIP RELAY UNHEALTHY SPS
30 XX KV FUTURE& COUPLING T/F-1 TIE 86B TRIP RELAY UNHEALTHY SPS
31 XX KV FUTURE& COUPLING T/F-1 TIE CB SPRING DISCHARGED / AIR /OIL PR LOW SPS
32 XX KV FUTURE& COUPLING T/F-1 TIE CB DC SUPPLY 1/2 FAIL SPS
33 XX KV FUTURE& COUPLING T/F-1 TIE CTRL SWITCH DEVICE TROUBLE/BYPASSED SPS
34 XX KV FUTURE& COUPLING T/F-1 TIE 52 CB COMPRESSOR/PUMP RUN TIME EXCEEDED SPS
35 XX KV COUPLING TRANSFORMER (HV) 52 CB OPERATION LOCKOUT SPS
36 XX KV COUPLING TRANSFORMER (HV) 52 CB POLE DISCREPANCY OPTD. SPS
37 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) DC SOURCE-1 FAIL SPS
38 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) DC SOURCE-2 FAIL SPS
39 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) CB TC-1 FAULTY SPS
40 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) CB TC-2 FAULTY SPS
41 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) 86A TRIP RELAY OPTD. SPS
42 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) 86B TRIP RELAY OPTD. SPS
43 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) Main-1 BB PROTN. OPTD. SPS
44 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) Main-2 BB PROTN. OPTD. SPS
45 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) MAIN CB LBB OPTD. SPS
46 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) LBB Unhealthy SPS
47 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OVERFLUX PROTECTION OPTD.(HV) SPS
48 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) BACKUP E/F OPTD. (HV) SPS
49 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OVERLOAD ALARM SPS
50 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) REF PROTECTION OPTD. SPS
51 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) TRANSFORMER DIFF. PROTECTION OPTD(R-PH) SPS
52 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) BACKUP O/C OPTD. (HV)(R-PH) SPS
53 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) BUCHHOLZ TRIP(R-PH) SPS
54 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OLTC PRV TRIP(R-PH) SPS
55 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OTI TRIP(R-PH) SPS
56 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) TRANSFORMER PRV TRIP(R-PH) SPS
57 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) WTI TRIP (HV/IV/LV)(R-PH) SPS
58 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OVERFLUX ALARM (HV)(R-PH) SPS
59 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) BUCHHOLZ ALARM(R-PH) SPS
60 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) LOW OIL LEVEL ALARM(R-PH) SPS
61 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OTI ALARM(R-PH) SPS
62 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) WTI ALARM (HV/IV/LV)(R-PH) SPS
63 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) TAP CHANGER IN PROGRESS SPS
64 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) TAP CHANGER IN REMOTE SPS
65 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) TAP CHANGER OUT OF STEP SPS
66 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OLTC DRIVE MOTOR FAULY ALARM SPS
67 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) CB COMPRESSOR / PUMP ON SPS
68 XX KV COUPLING TRANSFORMER (HV) 52 CB AC SUPPLY FAIL SPS
69 XX KV COUPLING TRANSFORMER (HV) 52 CB LOSS OF SF6 STG1 SPS
70 XX KV COUPLING TRANSFORMER (HV) 52 CB LOSS OF SF6 STG2 SPS
71 XX KV COUPLING TRANSFORMER (HV) 52 CB TROUBLE ALARM SPS
72 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) TAP CHANGER IN FOLLOWER MODE SPS
73 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) TAP CHANGER IN INDEPENDENT MODE SPS
74 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) TAP CHANGER IN MASTER MODE SPS
75 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) COOLING SYSTEM TROUBLE ALARM(R-PH) SPS
76 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) FANS FAIL TO START BANK-A/B(R-PH) SPS
77 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) FANS RUNNING BANK-A/B(R-PH) SPS
78 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) PUMPS FAIL TO START BANK-A/B(R-PH) SPS
79 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) PUMPS RUNNING BANK-A/B(R-PH) SPS
80 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OIL FLOW LOW ALARM BANK-A/B(R-PH) SPS
81 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) FAN/PUMP THERMALO/L TRIP ALARM(R-PH) SPS
82 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) 86A TRIP RELAY UNHEALTHY SPS
83 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) 86B TRIP RELAY UNHEALTHY SPS
84 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) CB SPRING DISCHARGED/AIR/OIL PR LOW SPS
85 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) CB DC SUPPLY 1/2 FAIL SPS
86 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) CONDITIONING MONITORING DEVICE FOR DGA-UNHEALTHY SPS
87 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) TRANSFORMER DIFF. PROTECTION OPTD(Y-PH) SPS
88 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) BACKUP O/C OPTD. (HV)(Y-PH) SPS
89 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) BUCHHOLZ TRIP(Y-PH) SPS
90 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OLTC PRV TRIP(Y-PH) SPS
91 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OTI TRIP(Y-PH) SPS
92 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) TRANSFORMER PRV TRIP(Y-PH) SPS
93 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) WTI TRIP (HV/IV/LV)(Y-PH) SPS
94 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OVERFLUX ALARM (HV)(Y-PH) SPS
95 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) BUCHHOLZ ALARM(Y-PH) SPS
96 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) LOW OIL LEVEL ALARM(Y-PH) SPS
97 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OTI ALARM(Y-PH) SPS
98 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) WTI ALARM (HV/IV/LV)(Y-PH) SPS
99 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) COOLING SYSTEM TROUBLE ALARM(Y-PH) SPS
100 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) FANS FAIL TO START BANK-A/B(Y-PH) SPS
101 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) FANS RUNNING BANK-A/B(Y-PH) SPS
102 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) PUMPS FAIL TO START BANK-A/B(Y-PH) SPS
103 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) PUMPS RUNNING BANK-A/B(Y-PH) SPS
104 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OIL FLOW LOW ALARM BANK-A/B(Y-PH) SPS
105 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) FAN/PUMP THERMALO/L TRIP ALARM(Y-PH) SPS
106 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) TRANSFORMER DIFF. PROTECTION OPTD(B-PH) SPS
107 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) BACKUP O/C OPTD. (HV)(B-PH) SPS
108 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) BUCHHOLZ TRIP(B-PH) SPS
109 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OLTC PRV TRIP(B-PH) SPS
110 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OTI TRIP(B-PH) SPS
111 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) TRANSFORMER PRV TRIP(B-PH) SPS
112 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) WTI TRIP (HV/IV/LV)(B-PH) SPS
113 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OVERFLUX ALARM (HV)(B-PH) SPS
114 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) BUCHHOLZ ALARM(B-PH) SPS
115 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) LOW OIL LEVEL ALARM(B-PH) SPS
116 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OTI ALARM(B-PH) SPS
117 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) WTI ALARM (HV/IV/LV)(B-PH) SPS
118 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) COOLING SYSTEM TROUBLE ALARM(B-PH) SPS
119 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) FANS FAIL TO START BANK-A/B(B-PH) SPS
120 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) FANS RUNNING BANK-A/B(B-PH) SPS
121 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) PUMPS FAIL TO START BANK-A/B(B-PH) SPS
122 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) PUMPS RUNNING BANK-A/B(B-PH) SPS
123 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) OIL FLOW LOW ALARM BANK-A/B(B-PH) SPS
124 XX KV COUPLING TRANSFORMER (HV) TRAFO (HV) FAN/PUMP THERMALO/L TRIP ALARM(B-PH) SPS
125 XX KV COUPLING TRANSFORMER STATCOM HV BAY - 52 INTERLOCK ENABLED SPS
126 XX KV COUPLING TRANSFORMER STATCOM HV BAY - 89A INTERLOCK ENABLED SPS
127 XX KV COUPLING TRANSFORMER STATCOM HV BAY- 89 INTERLOCK ENABLED SPS
128 XX KV COUPLING TRANSFORMER STATCOM HV BAY- 89TR INTERLOCK ENABLED SPS
129 XX KV COUPLING TRANSFORMER STATCOM HV BAY- 89TSR INTERLOCK ENABLED SPS
130 XX KV COUPLING TRANSFORMER STATCOM HV BAY- 89TY INTERLOCK ENABLED SPS
131 XX KV COUPLING TRANSFORMER STATCOM HV BAY- 89TSY INTERLOCK ENABLED SPS
132 XX KV COUPLING TRANSFORMER STATCOM HV BAY- 89TB INTERLOCK ENABLED SPS
133 XX KV COUPLING TRANSFORMER STATCOM HV BAY- 89TSB INTERLOCK ENABLED SPS
134 XX KV SPARE COUPLING T/F SPARE TRAFO TRANSFORMER DIFF. PROTECTION OPTD(SP) SPS
135 XX KV SPARE COUPLING T/F SPARE TRAFO BACKUP O/C OPTD. (HV)(SP) SPS
136 XX KV SPARE COUPLING T/F SPARE TRAFO BUCHHOLZ TRIP(SP) SPS
137 XX KV SPARE COUPLING T/F SPARE TRAFO OLTC PRV TRIP(SP) SPS
138 XX KV SPARE COUPLING T/F SPARE TRAFO OTI TRIP (SP) SPS
139 XX KV SPARE COUPLING T/F SPARE TRAFO TRANSFORMER PRV TRIP (SP) SPS
140 XX KV SPARE COUPLING T/F SPARE TRAFO WTI TRIP (HV/IV/LV) (SP) SPS
141 XX KV SPARE COUPLING T/F SPARE TRAFO OVERFLUX ALARM (HV) (SP) SPS
142 XX KV SPARE COUPLING T/F SPARE TRAFO BUCHHOLZ ALARM (SP) SPS
143 XX KV SPARE COUPLING T/F SPARE TRAFO LOW OIL LEVEL ALARM (SP) SPS
144 XX KV SPARE COUPLING T/F SPARE TRAFO OTI ALARM (SP) SPS
145 XX KV SPARE COUPLING T/F SPARE TRAFO WTI ALARM (HV/IV/LV) (SP) SPS
146 XX KV SPARE COUPLING T/F SPARE TRAFO COOLING SYSTEM TROUBLE ALARM (SP) SPS
147 XX KV SPARE COUPLING T/F SPARE TRAFO FANS FAIL TO START BANK-A (SP) SPS
148 XX KV SPARE COUPLING T/F SPARE TRAFO FANS FAIL TO START BANK-B (SP) SPS
149 XX KV SPARE COUPLING T/F SPARE TRAFO FANS RUNNING BANK-A/B (SP) SPS
150 XX KV SPARE COUPLING T/F SPARE TRAFO PUMPS FAIL TO START BANK-A (SP) SPS
151 XX KV SPARE COUPLING T/F SPARE TRAFO PUMPS FAIL TO START BANK-B (SP) SPS
152 XX KV SPARE COUPLING T/F SPARE TRAFO PUMPS RUNNING BANK-A/B (SP) SPS
153 XX KV SPARE COUPLING T/F SPARE TRAFO OIL FLOW LOW ALARM BANK-A (SP) SPS
154 XX KV SPARE COUPLING T/F SPARE TRAFO OIL FLOW LOW ALARM BANK-B (SP) SPS
155 XX KV SPARE COUPLING T/F SPARE TRAFO OLTC DRIVE MOTOR FAULY ALARM (SP) SPS
156 XX KV SPARE COUPLING T/F SPARE TRAFO FAN/PUMP THERMALO/L TRIP ALARM (SP) SPS
157 38.5KV COUPLING T/F (S) ICT (MV) 60089TR1 INTERLOCK ENABLED SPS
158 38.5KV COUPLING T/F (S) ICT (MV) 60089TR2 INTERLOCK ENABLED SPS
159 38.5KV COUPLING T/F (S) ICT (MV) 60089TY1 INTERLOCK ENABLED SPS
160 38.5KV COUPLING T/F (S) ICT (MV) 60089TY2 INTERLOCK ENABLED SPS
161 38.5KV COUPLING T/F (S) ICT (MV) 60089TB1 INTERLOCK ENABLED SPS
162 38.5KV COUPLING T/F (S) ICT (MV) 60089TB2 INTERLOCK ENABLED SPS
163 38.5KV COUPLING T/F (S) ICT (MV) 60089TSR1 INTERLOCK ENABLED SPS
164 38.5KV COUPLING T/F (S) ICT (MV) 60089TSR2 INTERLOCK ENABLED SPS
165 38.5KV COUPLING T/F (S) ICT (MV) 60089TSY1 INTERLOCK ENABLED SPS
166 38.5KV COUPLING T/F (S) ICT (MV) 60089TSY2 INTERLOCK ENABLED SPS
167 38.5KV COUPLING T/F (S) ICT (MV) 60089TSB1 INTERLOCK ENABLED SPS
168 38.5KV COUPLING T/F (S) ICT (MV) 60089TSB2 INTERLOCK ENABLED SPS
169 38.5KV COUPLING T/F (S) ICT (MV) 60089TR1E INTERLOCK ENABLED SPS
170 38.5KV COUPLING T/F (S) ICT (MV) 60089TR2E INTERLOCK ENABLED SPS
171 38.5KV COUPLING T/F (S) ICT (MV) 60089TY1E INTERLOCK ENABLED SPS
172 38.5KV COUPLING T/F (S) ICT (MV) 60089TY2E INTERLOCK ENABLED SPS
173 38.5KV COUPLING T/F (S) ICT (MV) 60089TB1E INTERLOCK ENABLED SPS
174 38.5KV COUPLING T/F (S) ICT (MV) 60089TB2E INTERLOCK ENABLED SPS
175 38.5KV COUPLING T/F (S) ICT (MV) 60089TSR1E INTERLOCK ENABLED SPS
176 38.5KV COUPLING T/F (S) ICT (MV) 60089TSR2E INTERLOCK ENABLED SPS
177 38.5KV MV BUS BAR 60089E INTERLOCK ENABLED SPS
178 38.5 KV MV BUS BAR MV BUS BAR MV BUS PROTECTION TRIP SPS
179 38.5 KV MV BUS BAR MV BUS BAR MV BUS PROTECTION RELAY FAILURE SPS
180 38.5KV STATCOM- 1 STATCOM VSC 60189A INTERLOCK ENABLED SPS
181 38.5KV STATCOM- 1 STATCOM VSC 60189AE INTERLOCK ENABLED SPS
182 38.5KV STATCOM- 1 VSC-1 STATCOM-1 COMMON ALARM SPS
183 38.5KV STATCOM- 1 VSC-1 STATCOM 1 PROTECTION TRIP SPS
184 38.5KV STATCOM- 1 VSC-1 PROTECTION RELAY FAILURE SPS
185 38.5KV STATCOM- 1 VSC-1 MASTER TRIP A SPS
186 38.5KV STATCOM- 1 VSC-1 MASTER TRIP B SPS
187 38.5KV STATCOM- 1 VSC-1 COOLING SYSTEM ALARM SPS
188 38.5KV STATCOM- 1 VSC-1 COOLING SYSTEM TRIP SPS
189 38.5KV STATCOM- 1 VSC-1 CB TROUBLE ALARM SPS
190 38.5KV STATCOM- 1 VSC-1 STATCOM-1 READY FOR OPERATION SPS
191 38.5KV STATCOM- 1 VSC-1 STATCOM-1 ORDER RUNNING SPS
192 38.5KV STATCOM- 1 VSC-1 STATCOM-1 COOLING SYSTEM STATUS SPS
193 38.5KV STATCOM- 2 STATCOM VSC 60289A INTERLOCK ENABLED SPS
194 38.5KV STATCOM- 2 STATCOM VSC 60289AE INTERLOCK ENABLED SPS
195 38.5KV STATCOM- 2 VSC-2 STATCOM-2 COMMON ALARM SPS
196 38.5KV STATCOM- 2 VSC-2 STATCOM 2 PROTECTION TRIP SPS
197 38.5KV STATCOM- 2 VSC-2 PROTECTION RELAY FAILURE SPS
198 38.5KV STATCOM- 2 VSC-2 MASTER TRIP A SPS
199 38.5KV STATCOM- 2 VSC-2 MASTER TRIP B SPS
200 38.5KV STATCOM- 2 VSC-2 COOLING SYSTEM ALARM SPS
201 38.5KV STATCOM- 2 VSC-2 COOLING SYSTEM TRIP SPS
202 38.5KV STATCOM- 2 VSC-2 CB TROUBLE ALARM SPS
203 38.5KV STATCOM- 2 VSC-2 STATCOM-2 READY FOR OPERATION SPS
204 38.5KV STATCOM- 2 VSC-2 STATCOM-2 CB ORDER RUNNNING SPS
205 38.5KV STATCOM- 2 VSC-2 STATCOM-2 COOLING SYSTEM STATUS SPS
206 38.5KV MSC 60352 INTERLOCK ENABLED SPS
207 38.5KV MSC 60389A INTERLOCK ENABLED SPS
208 38.5KV MSC 60389AE INTERLOCK ENABLED SPS
209 38.5KV MSC MSC PROTECTION TRIP SPS
210 38.5KV MSC MSC PROTECTION RELAY FAILURE SPS
211 38.5KV MSC MSC MASTER TRIP A SPS
212 38.5KV MSC MSC MASTER TRIP B SPS
213 38.5KV MSC MSC CB TROUBLE ALARM SPS
214 38.5KV MSR- 1 60452 INTERLOCK ENABLED SPS
215 38.5KV MSR- 1 60489A INTERLOCK ENABLED SPS
216 38.5KV MSR- 1 60489AE INTERLOCK ENABLED SPS
217 38.5KV MSR- 1 MSR-1 PROTECTION TRIP SPS
218 38.5KV MSR- 1 MSR-1 PROTECTION RELAY FAILURE SPS
219 38.5KV MSR- 1 MSR-1 MASTER TRIP A SPS
220 38.5KV MSR- 1 MSR-1 MASTER TRIP B SPS
221 38.5KV MSR- 1 MSR-1 CB TROUBLE ALARM SPS
222 38.5KV MSR- 2 60552 INTERLOCK ENABLED SPS
223 38.5KV MSR- 2 60589A INTERLOCK ENABLED SPS
224 38.5KV MSR- 2 60589AE INTERLOCK ENABLED SPS
225 38.5KV MSR- 2 MSR-2 PROTECTION TRIP SPS
226 38.5KV MSR- 2 MSR-2 PROTECTION RELAY FAILURE SPS
227 38.5KV MSR- 2 MSR-2 MASTER TRIP A SPS
228 38.5KV MSR- 2 MSR-2 MASTER TRIP B SPS
229 38.5KV MSR- 2 MSR-2 CB TROUBLE ALARM SPS
230 38.5KV AUX T/F 60652 INTERLOCK ENABLED SPS
231 38.5KV AUX T/F 60689A INTERLOCK ENABLED SPS
232 38.5KV AUX T/F 60689AE INTERLOCK ENABLED SPS
233 38.5KV AUX T/F 60652 CB TROUBLE ALARM SPS
234 38.5KV AUX T/F PROTN PROTECTION TRIP SPS
235 38.5KV AUX T/F PROTN PROTECTION RELAY FAILURE SPS
236 38.5KV AUX T/F PROTN MASTER TRIP A SPS
237 38.5KV AUX T/F PROTN MASTER TRIP B SPS
238 38.5KV AUX T/F AVR AVR FAIL ALARM SPS
239 38.5KV STATCOM NGT BAY GND TRANSFORMER PROTECTION TRIP SPS
240 38.5KV STATCOM CONTROL STATCOM ONE KEY START STATUS SPS
241 38.5KV STATCOM CONTROL STATCOM ONE KEY STOP STATUS SPS
242 38.5KV STATCOM CONTROL STATCOM ONE KEY EXIT STATUS SPS
243 38.5KV STATCOM CONTROL STATCOM STATCOM 1 EMG. STOP STATUS SPS
244 38.5KV STATCOM CONTROL STATCOM STATCOM 2 EMG. STOP STATUS SPS
245 38.5KV STATCOM CONTROL STATCOM SUBSTATION EMG. STOP STATUS SPS
246 38.5KV STATCOM CONTROL STATCOM EXTERNAL CONTROL AUTO (MSR & MSC, HV B/R) SPS
247 38.5KV STATCOM CONTROL STATCOM EXTERNAL CONTROL MANUAL (MSR & MSC, HV B/R) SPS
248 38.5KV STATCOM CONTROL STATCOM VOLTAGE MODE CONTROL SPS
249 38.5KV STATCOM CONTROL STATCOM REACTIVE MODE CONTROL SPS
250 38.5KV STATCOM CONTROL CONTROLLER CONTROLLER 1 FAULT SPS
251 38.5KV STATCOM CONTROL CONTROLLER CONTROLLER 2 FAULT SPS
252 38.5KV SAS COMMON RXPE LOCAL HMI LOCAL HMI SELECTED SPS
253 38.5KV SAS COMMON RXPE REMOTE HMI REMOTE HMI SELECTED SPS
254 38.5KV SAS COMMON GPS TIME SYNCHRONIZATION ERROR(GPS ERROR) SPS
255 38.5KV SAS COMMON STATCOM GATEWAY COMMUNICATION ALARM/WARNING SPS
256 38.5KV SAS COMMON STATCOM GATEWAY COMMUNICATION FAULT SPS
257 38.5KV AUX COMMON NWP PANEL 220V DC-1 FAIL SPS
258 38.5KV AUX COMMON NWP PANEL 220V DC-2 FAIL SPS
259 415 V AUX FP CUPLING TRAFO DELUGE SYSTEM OPERATING FOR CT R-PH SPS
260 415 V AUX FP CUPLING TRAFO FIRE IN COUPLING TRAFO R-PH SPS
261 415 V AUX FP CUPLING TRAFO DELUGE SYSTEM OPERATING FOR CT Y-PH SPS
262 415 V AUX FP CUPLING TRAFO FIRE IN COUPLING TRAFO Y-PH SPS
263 415 V AUX FP CUPLING TRAFO DELUGE SYSTEM OPERATING FOR CT B-PH SPS
264 415 V AUX FP CUPLING TRAFO FIRE IN COUPLING TRAFO B-PH SPS
265 415 V AUX FP CUPLING TRAFO DELUGE SYSTEM OPERATING FOR CT S-PH SPS
266 415 V AUX FP CUPLING TRAFO FIRE IN COUPLING TRAFO S-PH SPS
267 415 V AUX FP SMOKE ALARM CONTROL ROOM ZONE-1 FIRE DETECTED SPS
268 415 V AUX FP SMOKE ALARM CONTROL ROOM ZONE-2 FIRE DETECTED SPS
269 415 V AUX FP SMOKE ALARM CONTROL ROOM ZONE-3 FIRE DETECTED SPS
270 415 V AUX FP SMOKE ALARM CONTROL ROOM ZONE-4 FIRE DETECTED SPS
271 415 V AUX FP SMOKE ALARM CONTROL ROOM ZONE-5 FIRE DETECTED SPS
272 415 V AUX FP SMOKE ALARM CONTROL ROOM ZONE-6 FIRE DETECTED SPS
273 415 V AUX FP SMOKE ALARM CONTROL ROOM ZONE-7 FIRE DETECTED SPS
274 415 V AUX FP SMOKE ALARM CONTROL ROOM ZONE-8 FIRE DETECTED SPS
275 415 V AUX FP SMOKE ALARM CONTROL ROOM ZONE-9 FIRE DETECTED SPS
276 415 V AUX FP SMOKE ALARM CONTROL ROOM ZONE-10 FIRE DETECTED SPS
277 415 V AUX FP SMOKE ALARM CONTROL ROOM ZONE-11 FIRE DETECTED SPS
278 415 V AUX FP SMOKE ALARM CONTROL ROOM ZONE-12 FIRE DETECTED SPS
279 415 V AUX FP SMOKE ALARM CONTROL ROOM ZONE-13 FIRE DETECTED SPS
280 415 V AUX FP SMOKE ALARM CONTROL ROOM ZONE-14 FIRE DETECTED SPS
281 415 V AUX CHARGER-1 AC POWER FAIL SPS
282 415 V AUX CHARGER-1 RECTIFIER/CHARGER FUSE FAIL SPS
283 415 V AUX CHARGER-1 OVER VOLTAGE ALARM SPS
284 415 V AUX CHARGER-1 UNDER VOLTAGE ALARM SPS
285 415 V AUX DCDB-1 DC-1 EARTH FAULT ALARM SPS
286 415 V AUX CHARGER-2 AC POWER FAIL SPS
287 415 V AUX CHARGER-2 RECTIFIER/CHARGER FUSE FAIL SPS
288 415 V AUX CHARGER-2 OVER VOLTAGE ALARM SPS
289 415 V AUX CHARGER-2 UNDER VOLTAGE ALARM SPS
290 415 V AUX DCDB-2 DC-2 EARTH FAULT ALARM SPS
291 415 V AUX UPS-1 UPS-1 BATTERY LOW ALARM SPS
292 415 V AUX UPS-2 UPS-2 BATTERY LOW ALARM SPS
293 33KV AUX TERTIARY 33KV PROTN TERTIARY TRANSF PROTN OPTD SPS
294 33KV AUX TERTIARY 33KV CB CB INTERLOCK ENABLED SPS
295 33KV AUX TERTIARY 33KV ISOLATOR ISOLATOR INTERLOCK ENABLED SPS
296 415 V AUX DG SET AMF PANEL MAINS-1 ON SPS
297 415 V AUX DG SET AMF PANEL ALTERNATOR FAIL SPS
298 415 V AUX DG SET AMF PANEL ALTERNATOR ON SPS
299 415 V AUX DG SET AMF PANEL CHARGER-1 OFF SPS
300 415 V AUX DG SET AMF PANEL CHARGER-2 OFF SPS
301 415 V AUX DG SET AMF PANEL OVERSPEED SPS
302 415 V AUX DG SET AMF PANEL MAIN-2 LT SUPPLY ON/OFF SPS
303 415 V AUX DG SET AMF PANEL ENGINE OVER HEATING SPS
304 415 V AUX DG SET AMF PANEL LOW FUEL SPS
305 415 V AUX DG SET AMF PANEL LOW OIL PRESSURE SPS
306 415 V AUX DG SET AMF PANEL SET TO START 30S AFTER RX 1ST TIMER SPS
307 415 V AUX DG SET AMF PANEL HIGH COOLING WATER TEMPERATURE SPS
308 415 V AUX DG SET AMF PANEL LACK OF FUEL SPS
309 415 V AUX DG SET AMF PANEL DG SET RUNNING SPS
310 415 V AUX AIRCON STATCOM-1 STATCOM-1 AIR CONDITIONER TROUBLE ALARM SPS
311 415 V AUX AIRCON STATCOM-2 STATCOM-2 AIR CONDITIONER TROUBLE ALARM SPS
STATCOM (HYOSUNG)
1 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) MAIN-A PROTECTION TRIP SPS
2 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) MAIN-B PROTECTION TRIP SPS
3 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) MAIN-A PROTECTION RELAY FAILURE SPS
4 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) MAIN-B PROTECTION RELAY FAILURE SPS
5 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) WTI-HV ALARM SPS
6 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) WTI-LV ALARM SPS
7 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) OTI ALARM SPS
8 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) BUCHHOLZ RELAY-1 ALARM SPS
9 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) BUCHHOLZ RELAY-2 ALARM SPS
10 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) BUCHHOLZ RELAY-1 TRIP SPS
11 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) BUCHHOLZ RELAY-2 TRIP SPS
12 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) PRD-1 TRIP SPS
13 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) PRD-2 TRIP SPS
14 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) WTI-HV TRIP SPS
15 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) WTI-LV TRIP SPS
16 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) OTI TRIP SPS
17 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) SPR TRIP SPS
18 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) WTI-HV ALARM SPS
19 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) WTI-LV ALARM SPS
20 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) OTI ALARM SPS
21 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) BUCHHOLZ RELAY-1 ALARM SPS
22 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) BUCHHOLZ RELAY-2 ALARM SPS
23 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) BUCHHOLZ RELAY-1 TRIP SPS
24 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) BUCHHOLZ RELAY-2 TRIP SPS
25 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) PRD-1 TRIP SPS
26 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) PRD-2 TRIP SPS
27 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) WTI-HV TRIP SPS
28 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) WTI-LV TRIP SPS
29 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) OTI TRIP SPS
30 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) SPR TRIP SPS
31 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) WTI-HV ALARM SPS
32 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) WTI-LV ALARM SPS
33 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) OTI ALARM SPS
34 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) BUCHHOLZ RELAY-1 ALARM SPS
35 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) BUCHHOLZ RELAY-2 ALARM SPS
36 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) BUCHHOLZ RELAY-1 TRIP SPS
37 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) BUCHHOLZ RELAY-2 TRIP SPS
38 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) PRD-1 TRIP SPS
39 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) PRD-2 TRIP SPS
40 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) WTI-HV TRIP SPS
41 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) WTI-LV TRIP SPS
42 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) OTI TRIP SPS
43 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) SPR TRIP SPS
44 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) WTI-HV ALARM SPS
45 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) WTI-LV ALARM SPS
46 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) OTI ALARM SPS
47 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) BUCHHOLZ RELAY-1 ALARM SPS
48 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) BUCHHOLZ RELAY-2 ALARM SPS
49 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) BUCHHOLZ RELAY-1 TRIP SPS
50 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) BUCHHOLZ RELAY-2 TRIP SPS
51 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) PRD-1 TRIP SPS
52 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) PRD-2 TRIP SPS
53 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) WTI-HV TRIP SPS
54 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) WTI-LV TRIP SPS
55 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) OTI TRIP SPS
56 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) SPR TRIP SPS
57 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) GROUP MESSAGE : (C. TRAFO R-PH) FAN FAIL SPS
58 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) GROUP MESSAGE : (C. TRAFO Y-PH) FAN FAIL SPS
59 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) GROUP MESSAGE : (C. TRAFO B-PH) FAN FAIL SPS
60 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) GROUP MESSAGE : (C. TRAFO SP-PH) FAN FAIL SPS
61 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) SP TR. R-PH SELECTED SPS
62 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) SP TR. Y-PH SELECTED SPS
63 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) SP TR. B-PH SELECTED SPS
64 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) SP TR. DE-SELECTED SPS
65 400KV COUPLING TRANSFORMER (HV) 52 INTERLOCK ENABLED SPS
66 400KV COUPLING TRANSFORMER (HV) 89A INTERLOCK ENABLED SPS
67 400KV COUPLING TRANSFORMER (HV) 89AE INTERLOCK ENABLED SPS
68 400KV COUPLING TRANSFORMER (HV) 89B INTERLOCK ENABLED SPS
69 400KV COUPLING TRANSFORMER (HV) 89BE INTERLOCK ENABLED SPS
70 400KV COUPLING TRANSFORMER (HV) 89TR INTERLOCK ENABLED SPS
71 400KV COUPLING TRANSFORMER (HV) 89TRE INTERLOCK ENABLED SPS
72 400KV COUPLING TRANSFORMER (HV) 89TSR INTERLOCK ENABLED SPS
73 400KV COUPLING TRANSFORMER (HV) 89TY INTERLOCK ENABLED SPS
74 400KV COUPLING TRANSFORMER (HV) 89TYE INTERLOCK ENABLED SPS
75 400KV COUPLING TRANSFORMER (HV) 89TSY INTERLOCK ENABLED SPS
76 400KV COUPLING TRANSFORMER (HV) 89TB INTERLOCK ENABLED SPS
77 400KV COUPLING TRANSFORMER (HV) 89TBE INTERLOCK ENABLED SPS
78 400KV COUPLING TRANSFORMER (HV) 89TSB INTERLOCK ENABLED SPS
79 400KV COUPLING TRANSFORMER (HV) 89TSBE INTERLOCK ENABLED SPS
80 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) 400KV MAIN BAY LBB PROTECTION TRIP SPS
81 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY LBB RELAY FAILURE SPS
82 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY BCU FAILURE SPS
83 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY 86.1 TRIP RELAY OPERATED SPS
84 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY 86.2 TRIP RELAY OPERATED SPS
85 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY CT SF6 Loss Alarm SPS
86 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY CT SF6 Lockout Alarm SPS
87 400KV COUPLING TRANSFORMER (HV) 52 400kV MAIN BAY CB SF6 Loss Alarm SPS
88 400KV COUPLING TRANSFORMER (HV) 52 400kV MAIN BAY CB SF6 Lockout Alarm 1/2 SPS
89 400KV COUPLING TRANSFORMER (HV) 52 400kV MAIN BAY CB DC-1/2 Fail SPS
90 400KV COUPLING TRANSFORMER (HV) 52 400kV MAIN BAY CB Pole Descripency Alarm SPS
91 400KV COUPLING TRANSFORMER (HV) 52 400kV MAIN BAY CB TC-1 Faulty SPS
92 400KV COUPLING TRANSFORMER (HV) 52 400kV MAIN BAY CB TC-2 Faulty SPS
93 400KV COUPLING TRANSFORMER (HV) 52 400kV MAIN BAY CB Spring Charged SPS
94 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY CSD Alarm SPS
95 400KV COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY CSD out of service SPS
96 20KV COUPLING TRANSFORMER (MV) 89TR INTERLOCK ENABLED SPS
97 20KV COUPLING TRANSFORMER (MV) 89TY INTERLOCK ENABLED SPS
98 20KV COUPLING TRANSFORMER (MV) 89TB INTERLOCK ENABLED SPS
99 20KV COUPLING TRANSFORMER (MV) 89TSR INTERLOCK ENABLED SPS
100 20KV COUPLING TRANSFORMER (MV) 89TSY INTERLOCK ENABLED SPS
101 20KV COUPLING TRANSFORMER (MV) 89TSB INTERLOCK ENABLED SPS
102 20KV COUPLING TRANSFORMER (MV) 89TER INTERLOCK ENABLED SPS
103 20KV COUPLING TRANSFORMER (MV) 89TEY INTERLOCK ENABLED SPS
104 20KV COUPLING TRANSFORMER (MV) 89TEB INTERLOCK ENABLED SPS
105 20KV COUPLING TRANSFORMER (MV) TSER INTERLOCK ENABLED SPS
106 20KV STATCOM-1 VSC-1 MAIN PROTECTION TRIP SPS
107 20KV STATCOM-1 VSC-1 MAIN LBB PROTECTION TRIP SPS
108 20KV STATCOM-1 VSC-1 CONTROLLER FAILURE TRIP SPS
109 20KV STATCOM-1 VSC-1 BACKUP PROTECTION TRIP SPS
110 20KV STATCOM-1 VSC-1 BACKUP LBB PROTECTION TRIP SPS
111 20KV STATCOM-1 VSC-1 MAIN PROTECTION RELAY FAILURE SPS
112 20KV STATCOM-1 VSC-1 BACKUP PROTECTION RELAY FAILURE SPS
113 20KV STATCOM-1 VSC-1 TRIP RELAY-A(86A) OPERATED SPS
114 20KV STATCOM-1 VSC-1 TRIP RELAY-B(86B) OPERATED SPS
115 20KV STATCOM-1 VSC-1 GROUP MESSAGE : STATCOM UNIT-1 CONTROLLER A FAILURE (COMM. FAIL / HW FAIL) SPS
116 20KV STATCOM-1 VSC-1 GROUP MESSAGE : STATCOM UNIT-1 CONTROLLER B FAILURE (COMM. FAIL / HW FAIL) SPS
117 20KV STATCOM-1 VSC-1 GROUP MESSAGE : (COOLING-1) COOLING SYSTME ALARM SPS
118 20KV STATCOM-1 VSC-1 (COOLING-1) COOLING SYSTME CONTROLLER-A ACTIVE SPS
119 20KV STATCOM-1 VSC-1 (COOLING-1) COOLING SYSTME CONTROLLER-B ACTIVE SPS
120 20KV STATCOM-1 VSC-1 (COOLING-1) COOLING SYSTME CONTROLLER-A FAILURE SPS
121 20KV STATCOM-1 VSC-1 (COOLING-1) COOLING SYSTME CONTROLLER-B FAILURE SPS
122 20KV STATCOM-1 VSC-1 52 TRIP CIRCUIT-1 FAULTY SPS
123 20KV STATCOM-1 VSC-1 52 TRIP CIRCUIT-2 FAULTY SPS
124 20KV STATCOM-1 VSC-1 52 PRESSURE BLOCKING ALARM SPS
125 20KV STATCOM-1 VSC-1 52 SF6 GAS LOW ALARM SPS
126 20KV STATCOM-1 VSC-1 52 POLE DISCREPANCY ALARM SPS
127 20KV STATCOM-1 VSC-1 52 AC FAILURE ALARM SPS
128 20KV STATCOM-1 VSC-1 52 INTERLOCK ENABLED SPS
129 20KV STATCOM-1 VSC-1 -89A INTERLOCK ENABLED SPS
130 20KV STATCOM-1 VSC-1 -89AE INTERLOCK ENABLED SPS
131 20KV STATCOM-1 VSC-1 -89B INTERLOCK ENABLED SPS
132 20KV STATCOM-1 VSC-1 -89BE1 INTERLOCK ENABLED SPS
133 20KV STATCOM-1 VSC-1 -89BE2 INTERLOCK ENABLED SPS
134 20KV STATCOM-1 VSC-1 (UNIT-1) VALVE OVERCURRENT TRIP SPS
135 20KV STATCOM-1 VSC-1 (UNIT-1) COOLING SYSTEM TRIP SPS
136 20KV STATCOM-1 VSC-1 GROUP MESSAGE : (UNIT-1) DC CT POWER FAIL SPS
137 20KV STATCOM-1 VSC-1 (UNIT-1) PHASE CONTROLLER FAILURE TRIP SPS
138 20KV STATCOM-1 VSC-1 GROUP MESSAGE : (UNIT-1) VALVE ERROR TRIP SPS
139 20KV STATCOM-1 VSC-1 (UNIT-1) SUB-MODULE FAILURE OR BYPASSED SPS
140 20KV STATCOM-1 VSC-1 (UNIT-1) VALVE HALL-1 TEMPERATURE HIGH TRIP SPS
141 20KV STATCOM-2 VSC-2 MAIN PROTECTION TRIP SPS
142 20KV STATCOM-2 VSC-2 MAIN LBB PROTECTION TRIP SPS
143 20KV STATCOM-2 VSC-2 CONTROLLER FAILURE TRIP SPS
144 20KV STATCOM-2 VSC-2 BACKUP PROTECTION TRIP SPS
145 20KV STATCOM-2 VSC-2 BACKUP LBB PROTECTION TRIP SPS
146 20KV STATCOM-2 VSC-2 MAIN PROTECTION RELAY FAILURE SPS
147 20KV STATCOM-2 VSC-2 BACKUP PROTECTION RELAY FAILURE SPS
148 20KV STATCOM-2 VSC-2 TRIP RELAY-A(86A) OPERATED SPS
149 20KV STATCOM-2 VSC-2 TRIP RELAY-B(86B) OPERATED SPS
150 20KV STATCOM-2 VSC-2 GROUP MESSAGE : STATCOM UNIT-2 CONTROLLER A FAILURE (COMM. FAIL / HW FAIL) SPS
151 20KV STATCOM-2 VSC-2 GROUP MESSAGE : STATCOM UNIT-2 CONTROLLER B FAILURE (COMM. FAIL / HW FAIL) SPS
152 20KV STATCOM-2 VSC-2 GROUP MESSAGE : (COOLING-2) COOLING SYSTME ALARM SPS
153 20KV STATCOM-2 VSC-2 (COOLING-2) COOLING SYSTME CONTROLLER-A ACTIVE SPS
154 20KV STATCOM-2 VSC-2 (COOLING-2) COOLING SYSTME CONTROLLER-B ACTIVE SPS
155 20KV STATCOM-2 VSC-2 (COOLING-2) COOLING SYSTME CONTROLLER-A FAILURE SPS
156 20KV STATCOM-2 VSC-2 (COOLING-2) COOLING SYSTME CONTROLLER-B FAILURE SPS
157 20KV STATCOM-2 VSC-2 52 TRIP CIRCUIT-1 FAULTY SPS
158 20KV STATCOM-2 VSC-2 52 TRIP CIRCUIT-2 FAULTY SPS
159 20KV STATCOM-2 VSC-2 52 PRESSURE BLOCKING ALARM SPS
160 20KV STATCOM-2 VSC-2 52 SF6 GAS LOW ALARM SPS
161 20KV STATCOM-2 VSC-2 52 POLE DISCREPANCY ALARM SPS
162 20KV STATCOM-2 VSC-2 52 AC FAILURE ALARM SPS
163 20KV STATCOM-2 VSC-2 52 INTERLOCK ENABLED SPS
164 20KV STATCOM-2 VSC-2 -89A INTERLOCK ENABLED SPS
165 20KV STATCOM-2 VSC-2 -89AE INTERLOCK ENABLED SPS
166 20KV STATCOM-2 VSC-2 -89B INTERLOCK ENABLED SPS
167 20KV STATCOM-2 VSC-2 -89BE1 INTERLOCK ENABLED SPS
168 20KV STATCOM-2 VSC-2 -89BE2 INTERLOCK ENABLED SPS
169 20KV STATCOM-2 VSC-2 (UNIT-2) VALVE OVERCURRENT TRIP SPS
170 20KV STATCOM-2 VSC-2 (UNIT-2) COOLING SYSTEM TRIP SPS
171 20KV STATCOM-2 VSC-2 GROUP MESSAGE : (UNIT-2) DC CT POWER FAIL SPS
172 20KV STATCOM-2 VSC-2 (UNIT-2) PHASE CONTROLLER FAILURE TRIP SPS
173 20KV STATCOM-2 VSC-2 GROUP MESSAGE : (UNIT-2) VALVE ERROR TRIP SPS
174 20KV STATCOM-2 VSC-2 (UNIT-2) SUB-MODULE FAILURE OR BYPASSED SPS
175 20KV STATCOM-2 VSC-2 (UNIT-2) VALVE HALL-2 TEMPERATURE HIGH TRIP SPS
176 20KV STATCOM CONTROL STATCOM COOLING-1 SYSTME TRIP SPS
177 20KV STATCOM CONTROL STATCOM COOLING-2 SYSTME TRIP SPS
178 20KV STATCOM CONTROL STATCOM STATCOM STATION CONTROLLER FAILURE TRIP SPS
179 20KV STATCOM CONTROL STATCOM STATION CONTROLLER START SPS
180 20KV STATCOM CONTROL STATCOM STATION CONTROLLER STOP SPS
181 20KV STATCOM CONTROL STATCOM STATCOM STATION RUNNING SPS
182 20KV STATCOM CONTROL STATCOM STATCOM STATION SEQUENCE FAIULRE SPS
183 20KV STATCOM CONTROL STATCOM UNIT-1 CONTROLLER START SPS
184 20KV STATCOM CONTROL STATCOM UNIT-1 CONTROLLER STOP SPS
185 20KV STATCOM CONTROL STATCOM STATCOM UNIT-1 STOPPED SPS
186 20KV STATCOM CONTROL STATCOM STATCOM UNIT-1 RUNNING SPS
187 20KV STATCOM CONTROL STATCOM STATCOM UNIT-1 SEQUENCE FAIULRE SPS
188 20KV STATCOM CONTROL STATCOM UNIT-2 CONTROLLER START SPS
189 20KV STATCOM CONTROL STATCOM UNIT-2 CONTROLLER STOP SPS
190 20KV STATCOM CONTROL STATCOM STATCOM UNIT-2 STOPPED SPS
191 20KV STATCOM CONTROL STATCOM STATCOM UNIT-2 RUNNING SPS
192 20KV STATCOM CONTROL STATCOM STATCOM UNIT-2 SEQUENCE FAIULRE SPS
193 20KV STATCOM CONTROL STATCOM AUTOMATIC START SPS
194 20KV STATCOM CONTROL STATCOM AUTOMATIC STOP SPS
195 20KV STATCOM CONTROL STATCOM AUTOMATIC START/STOP SEQUENCE RUNNING SPS
196 20KV STATCOM CONTROL STATCOM AUTOMATIC START/STOP SEQUENCE FAIL SPS
197 20KV STATCOM CONTROL STATCOM (STATION) HV SIDE OVERVOLTAGE TRIP SPS
198 20KV STATCOM CONTROL STATCOM (STATION) HV SIDE UNDERVOLTAGE TRIP SPS
199 20KV STATCOM CONTROL STATCOM (STATION) HV SIDE OVERCURRENT TRIP SPS
200 20KV STATCOM CONTROL STATCOM (STATION) HV PT FAIL TRIP SPS
201 20KV STATCOM CONTROL STATCOM EMERGENCY STOP SPS
202 20KV STATCOM CONTROL STATCOM GROUP MESSAGE : STATION CONTROLLER A FAILURE (COMM. FAIL / HW FAIL) SPS
203 20KV STATCOM CONTROL STATCOM GROUP MESSAGE : STATION CONTROLLER B FAILURE (COMM. FAIL / HW FAIL) SPS
204 20KV STATCOM CONTROL STATCOM MANUAL Q CONTROL MODE SELECTED SPS
205 20KV STATCOM CONTROL STATCOM AUTOMATIC VOLTAGE CONTROL MODE SELECTED SPS
206 20KV STATCOM CONTROL STATCOM POD CONTROL ENABLED SPS
207 20KV STATCOM CONTROL STATCOM SSOD CONTROL ENABLED SPS
208 20KV STATCOM CONTROL STATCOM ADAPTIVE GAIN REDUCTION ENABLED SPS
209 20KV STATCOM CONTROL STATCOM ADAPTIVE GAIN CLACULATION ENABLED SPS
210 20KV STATCOM CONTROL STATCOM NEGATIVE SEQ. VOLTAGE CONTROL ENABLED SPS
211 20KV STATCOM CONTROL STATCOM MSC CONTROL MODE - AUTO. CONTROL SELLECTED SPS
212 20KV STATCOM CONTROL STATCOM MSR-1 CONTROL MODE - AUTO. CONTROL SELLECTED SPS
213 20KV STATCOM CONTROL STATCOM MSR-2 CONTROL MODE - AUTO. CONTROL SELLECTED SPS
214 20KV STATCOM CONTROL STATCOM HV BR MAIN BAY CONTROL MODE - AUTO. CONTROL SELLECTED (HYD ONLY) SPS
215 20KV STATCOM CONTROL STATCOM HV BR TIE BAY CONTROL MODE - AUTO. CONTROL SELLECTED (HYD ONLY) SPS
216 20KV STATCOM CONTROL AHU AHU 1-1 RUNNING SPS
217 20KV STATCOM CONTROL AHU AHU 1-2 RUNNING SPS
218 20KV STATCOM CONTROL AHU AHU 2-1 RUNNING SPS
219 20KV STATCOM CONTROL AHU AHU 2-2 RUNNING SPS
220 20KV GND T/F GND T/F MV BUSBAR BACKUP PROTECTION TRIP (GND TRAFO TRIP) SPS
221 20KV GND T/F GND T/F BACKUP PROTECTION RELAY FAILURE (GND TRAFO) SPS
222 20KV GND T/F GND T/F BUCHHOLZ RELAY TRIP SPS
223 20KV GND T/F GND T/F PRD TRIP SPS
224 20KV GND T/F GND T/F WTI TRIP SPS
225 20KV GND T/F GND T/F OTI TRIP SPS
226 20KV GND T/F GND T/F BUCHHOLZ RELAY ALARM SPS
227 20KV GND T/F GND T/F WTI ALARM SPS
228 20KV GND T/F GND T/F OTI ALARM SPS
229 20KV GND T/F 89 INTERLOCK ENABLED SPS
230 20KV GND T/F 89E INTERLOCK ENABLED SPS
231 20KV MV BUS BAR MV BUS BAR MAIN PROTECTION TRIP SPS
232 20KV MV BUS BAR MV BUS BAR MAIN PROTECTION RELAY FAILURE SPS
233 20KV BUS PT 89E1 INTERLOCK ENABLED SPS
234 20KV BUS PT 89 INTERLOCK ENABLED SPS
235 20KV BUS PT 89E2 INTERLOCK ENABLED SPS
236 20KV AUX.T/F MV AUX T/F MAIN PROTECTION TRIP SPS
237 20KV AUX.T/F MV AUX T/F BACKUP PROTECTION TRIP SPS
238 20KV AUX.T/F MV AUX T/F MAIN PROTECTION RELAY FAILURE SPS
239 20KV AUX.T/F MV AUX T/F BACKUP PROTECTION RELAY FAILURE SPS
240 20KV AUX.T/F MV AUX T/F TRIP RELAY-A(86A) OPERATED SPS
241 20KV AUX.T/F MV AUX T/F TRIP RELAY-B(86B) OPERATED SPS
242 20KV AUX.T/F MV AUX T/F BUCHHOLZ RELAY TRIP SPS
243 20KV AUX.T/F MV AUX T/F WTI TRIP SPS
244 20KV AUX.T/F MV AUX T/F OTI TRIP SPS
245 20KV AUX.T/F MV AUX T/F BUCHHOLZ RELAY ALARM SPS
246 20KV AUX.T/F MV AUX T/F WTI ALARM SPS
247 20KV AUX.T/F MV AUX T/F OTI ALARM SPS
248 20KV AUX.T/F 52 TRIP CIRCUIT-1 FAULTY SPS
249 20KV AUX.T/F 52 TRIP CIRCUIT-2 FAULTY SPS
250 20KV AUX.T/F 52 PRESSURE BLOCKING ALARM SPS
251 20KV AUX.T/F 52 SF6 GAS LOW ALARM SPS
252 20KV AUX.T/F 52 POLE DISCREPANCY ALARM SPS
253 20KV AUX.T/F 52 AC FAILURE ALARM SPS
254 20KV AUX.T/F 89 INTERLOCK ENABLED SPS
255 20KV AUX.T/F 89E INTERLOCK ENABLED SPS
256 20KV AUX.T/F 52 INTERLOCK ENABLED SPS
257 33KV AUX.T/F TERTIARY 33kV AUX. TR PROTECTION TRIP SPS
258 33KV AUX.T/F TERTIARY 33kV AUX. TR TRIP RELAY OPERATED SPS
259 33KV AUX.T/F TERTIARY 33kV AUX. TR CB SF6 Loss Alarm SPS
260 33KV AUX.T/F TERTIARY 33kV AUX. TR CB SF6 Lockout Alarm SPS
261 33KV AUX.T/F TERTIARY 33kV AUX. TR CB Spring Charged SPS
262 33KV AUX.T/F TERTIARY 33kV AUX. TR CB DC 1/2 Fail Alarm SPS
263 33KV AUX.T/F TERTIARY 33kV AUX. TR Bucholz Alarm SPS
264 33KV AUX.T/F TERTIARY 33kV AUX. TR WTI Alarm SPS
265 33KV AUX.T/F TERTIARY 33kV AUX. TR OTI Alarm SPS
266 33KV AUX.T/F TERTIARY 52 INTERLOCK ENABLED SPS
267 33KV AUX.T/F TERTIARY 89 INTERLOCK ENABLED SPS
268 415 V FP CONTROL ROOM CONTROL ROOM FIRE DETECTED SPS
269 415 V FP VALVE HALL VALVE HALL-1 FIRE DETECTED SPS
270 415 V FP VALVE HALL VALVE HALL-2 FIRE DETECTED SPS
271 415 V FP CONTROL ROOM GROUP MESSAGE : CONTROL BUILDING FIRE DETECTED SPS
272 415 V FP COUPLING T/F GROUP MESSAGE : COUPLING TRANSFORMER FIRE DETECTED SPS
273 415 V DCDB DCDB-1 GROUP MESSAGE : 220V DC SOURCE-1 FAILURE SPS
274 415 V DCDB DCDB-2 GROUP MESSAGE : 220V DC SOURCE-2 FAILURE SPS
275 415 V DCDB DCDB-1 EARTH FAULT SPS
276 415 V DCDB DCDB-1 BATTERY CHARGER TROUBLE SPS
277 415 V DCDB DCDB-2 EARTH FAULT SPS
278 415 V DCDB DCDB-2 BATTERY CHARGER TROUBLE SPS
279 415 V GPS GPS GROUP MESSAGE : TIME SYNC. FAIL SPS
280 415 V DG SET AMF PANEL DG SET ON SPS
281 415 V DG SET AMF PANEL DG SET OFF SPS
282 415 V DG SET AMF PANEL DG SET LOW OIL PRESSURE SPS
283 415 V DG SET AMF PANEL DG SET LOW FUEL SPS
284 415 V DG SET AMF PANEL DG SET FAILED TO START IN 30 SEC SPS
285 415 V DG SET AMF PANEL DG SET HIGH COOLING WATER TEMPERATURE SPS
286 415 V DG SET AMF PANEL DG SET LOW LEVEL IN DAILY SERVICE FUEL TANK SPS
287 415 V DG SET AMF PANEL OVER SPEED TRIP SPS
288 415 V DG SET AMF PANEL ALTERNATOR FAULT SPS
289 415 V DG SET AMF PANEL ALTERNATOR ON SPS
290 415 V COOLING UPS UPS-1 BYPASS FAILURE / AC SUPPLY FAILURE SPS
291 415 V COOLING UPS UPS-1 LOW BATTERY SPS
292 415 V COOLING UPS UPS-1 LOAD ON MAINS SPS
293 415 V COOLING UPS UPS-1 LOAD ON MAINTENANCE/BYPASS-MODE SPS
294 415 V COOLING UPS UPS-1 LOAD ON INVERTER SPS
295 415 V COOLING UPS UPS-2 BYPASS FAILURE / AC SUPPLY FAILURE SPS
296 415 V COOLING UPS UPS-2 LOW BATTERY SPS
297 415 V COOLING UPS UPS-2 LOAD ON MAINS SPS
298 415 V COOLING UPS UPS-2 LOAD ON MAINTENANCE/BYPASS-MODE SPS
299 415 V COOLING UPS UPS-2 LOAD ON INVERTER SPS
300 415 V AUX AIRCON VALVE HALL-1 TEMPERATURE HIGH ALARM SPS
301 415 V AUX AIRCON VALVE HALL-2 TEMPERATURE HIGH ALARM SPS
302 415 V AUX AIRCON CONTROL ROOM TEMPERATURE HIGH ALARM SPS
303 415 V SAS STATION LOCAL/REMOTE LOCAL HMI CONTROL SELECTED (HYDERBAD S/S) SPS
304 415 V SAS STATION LOCAL/REMOTE REMOTE CENTER CONTROL SELECTED (NTAMC/RTAMC/B-NTAMC) SPS
305 20KV MSR-1 MSR MSR-1 MAIN PROTECTION TRIP SPS
306 20KV MSR-1 MSR MSR-1 MAIN LBB PROTECTION TRIP SPS
307 20KV MSR-1 MSR MSR-1 BACKUP PROTECTION TRIP SPS
308 20KV MSR-1 MSR MSR-1 BACKUP LBB PROTECTION TRIP SPS
309 20KV MSR-1 MSR MSR-1 MAIN PROTECTION RELAY FAILURE SPS
310 20KV MSR-1 MSR MSR-1 BACKUP PROTECTION RELAY FAILURE SPS
311 20KV MSR-1 MSR MSR-1 TRIP RELAY-A(86A) OPERATED SPS
312 20KV MSR-1 MSR MSR-1 TRIP RELAY-B(86B) OPERATED SPS
313 20KV MSR-1 89A INTERLOCK ENABLED SPS
314 20KV MSR-1 89AE INTERLOCK ENABLED SPS
315 20KV MSR-1 52 INTERLOCK ENABLED SPS
316 20KV MSR-1 89B INTERLOCK ENABLED SPS
317 20KV MSR-1 89BE1 INTERLOCK ENABLED SPS
318 20KV MSR-1 89BE2 INTERLOCK ENABLED SPS
319 20KV MSR-1 52 TRIP CIRCUIT-1 FAULTY SPS
320 20KV MSR-1 52 TRIP CIRCUIT-2 FAULTY SPS
321 20KV MSR-1 52 PRESSURE BLOCKING ALARM SPS
322 20KV MSR-1 52 SF6 GAS LOW ALARM SPS
323 20KV MSR-1 52 POLE DISCREPANCY ALARM SPS
324 20KV MSR-1 52 AC FAILURE ALARM SPS
325 20KV MSR-2 MSR MSR-2 MAIN PROTECTION TRIP SPS
326 20KV MSR-2 MSR MSR-2 MAIN LBB PROTECTION TRIP SPS
327 20KV MSR-2 MSR MSR-2 BACKUP PROTECTION TRIP SPS
328 20KV MSR-2 MSR MSR-2 BACKUP LBB PROTECTION TRIP SPS
329 20KV MSR-2 MSR MSR-2 MAIN PROTECTION RELAY FAILURE SPS
330 20KV MSR-2 MSR MSR-2 BACKUP PROTECTION RELAY FAILURE SPS
331 20KV MSR-2 MSR MSR-2 TRIP RELAY-A(86A) OPERATED SPS
332 20KV MSR-2 MSR MSR-2 TRIP RELAY-B(86B) OPERATED SPS
333 20KV MSR-2 89A INTERLOCK ENABLED SPS
334 20KV MSR-2 89AE INTERLOCK ENABLED SPS
335 20KV MSR-2 52 INTERLOCK ENABLED SPS
336 20KV MSR-2 89B INTERLOCK ENABLED SPS
337 20KV MSR-2 89BE1 INTERLOCK ENABLED SPS
338 20KV MSR-2 89BE2 INTERLOCK ENABLED SPS
339 20KV MSR-2 52 TRIP CIRCUIT-1 FAULTY SPS
340 20KV MSR-2 52 TRIP CIRCUIT-2 FAULTY SPS
341 20KV MSR-2 52 PRESSURE BLOCKING ALARM SPS
342 20KV MSR-2 52 SF6 GAS LOW ALARM SPS
343 20KV MSR-2 52 POLE DISCREPANCY ALARM SPS
344 20KV MSR-2 52 AC FAILURE ALARM SPS
345 20KV MSC MSC MSC MAIN PROTECTION TRIP SPS
346 20KV MSC MSC MSC MAIN LBB PROTECTION TRIP SPS
347 20KV MSC MSC MSC BACKUP PROTECTION TRIP SPS
348 20KV MSC MSC MSC BACKUP LBB PROTECTION TRIP SPS
349 20KV MSC MSC MSC MAIN PROTECTION RELAY FAILURE SPS
350 20KV MSC MSC MSC BACKUP PROTECTION RELAY FAILURE SPS
351 20KV MSC MSC MSC TRIP RELAY-A(86A) OPERATED SPS
352 20KV MSC MSC MSC TRIP RELAY-B(86B) OPERATED SPS
353 20KV MSC 89A INTERLOCK ENABLED SPS
354 20KV MSC 89AE INTERLOCK ENABLED SPS
355 20KV MSC 52 INTERLOCK ENABLED SPS
356 20KV MSC 89B INTERLOCK ENABLED SPS
357 20KV MSC 89BE1 INTERLOCK ENABLED SPS
358 20KV MSC 89BE2 INTERLOCK ENABLED SPS
359 20KV MSC 52 TRIP CIRCUIT-1 FAULTY SPS
360 20KV MSC 52 TRIP CIRCUIT-2 FAULTY SPS
361 20KV MSC 52 PRESSURE BLOCKING ALARM SPS
362 20KV MSC 52 SF6 GAS LOW ALARM SPS
363 20KV MSC 52 POLE DISCREPANCY ALARM SPS
364 20KV MSC 52 AC FAILURE ALARM SPS
365 400KV FUTURE 89A INTERLOCK ENABLED SPS
366 400KV FUTURE 89AE INTERLOCK ENABLED SPS
367 400KV FUTURE & STATCOM TIE 400KV TIE BAY LBB PROTECTION TRIP SPS
368 400KV FUTURE & STATCOM TIE 400kV TIE BAY LBB RELAY FAILURE SPS
369 400KV FUTURE & STATCOM TIE 400kV TIE BAY BCU FAILURE SPS
370 400KV FUTURE & STATCOM TIE 400kV TIE BAY 86.1 TRIP RELAY OPERATED SPS
371 400KV FUTURE & STATCOM TIE 400kV TIE BAY 86.2 TRIP RELAY OPERATED SPS
372 400KV FUTURE & STATCOM TIE CT SF6 Loss Alarm SPS
373 400KV FUTURE & STATCOM TIE CT SF6 Lockout Alarm SPS
374 400KV FUTURE & STATCOM TIE 52 CB SF6 Loss Alarm SPS
375 400KV FUTURE & STATCOM TIE 52 CB SF6 Lockout Alarm 1/2 SPS
376 400KV FUTURE & STATCOM TIE 52 CB DC-1/2 Fail SPS
377 400KV FUTURE & STATCOM TIE 52 CB Pole Descripency Alarm SPS
378 400KV FUTURE & STATCOM TIE 52 CB TC-1 Faulty SPS
379 400KV FUTURE & STATCOM TIE 52 CB TC-2 Faulty SPS
380 400KV FUTURE & STATCOM TIE 52 CB Spring Charged SPS
381 400KV FUTURE & STATCOM TIE 52 CSD Alarm SPS
382 400KV FUTURE & STATCOM TIE 52 CSD out of service SPS
Sl. BAY NUM. BAY NAME DEVICE ID SIGNAL DESCRIPTION DATA TYPE SCADA ID REMARK
765 KV/ 400 KV/ 220 KV/ 132 KV BUS BAR ( MAIN BUS & TRANSFER BUS)
1 BUS BUS-X BUS VOLTAGE R-Y PHASE AI KVRY
2 BUS BUS-X BUS VOLTAGE Y-B PHASE AI KVYB
3 BUS BUS-X BUS VOLTAGE B-R PHASE AI KVBR
4 BUS BUS-X BUS FREQUENCY AI HZ
765 KV/ 400 KV/ 220 KV /132 KV LINE FEEDER / LINE SERIES REACTOR/ BUS SERIES REACTOR (LSR/BSR)
1 ABC LINE FEEDER LINE / LSR / BSR I (R-PHASE) AI IR
2 ABC LINE FEEDER LINE / LSR / BSR I (Y-PHASE) AI IY
3 ABC LINE FEEDER LINE / LSR / BSR I (B-PHASE) AI IB
4 ABC LINE FEEDER LINE / LSR / BSR MW AI MW
5 ABC LINE FEEDER LINE / LSR / BSR MVAR AI MX
6 ABC LINE FEEDER LINE / LSR / BSR V (R-Y PHASE) AI KVRY
7 ABC LINE FEEDER LINE / LSR / BSR V (Y-B PHASE) AI KVYB
8 ABC LINE FEEDER LINE / LSR / BSR V (B-R PHASE) AI KVBR
9 ABC LINE FEEDER LINE / LSR / BSR FREQUENCY AI HZ
10 ABC LINE FEEDER LINE MAIN-1 FAULT IMPEDANCE AI FLZ1
11 ABC LINE FEEDER LINE MAIN-1 FAULT DISTANCE AI FLD1
12 ABC LINE FEEDER LINE MAIN-1 FAULT PERCENTAGE AI FLP1
13 ABC LINE FEEDER LINE MAIN-2 FAULT IMPEDANCE AI FLZ2
14 ABC LINE FEEDER LINE MAIN-2 FAULT DISTANCE AI FLD2
15 ABC LINE FEEDER LINE MAIN-2 FAULT PERCENTAGE AI FLP2
765 KV/ 400 KV LINE REACTOR/ BUS REACTOR
1 ABC BUS REACTOR/ LINE REACTOR RE REACTOR I (R-PHASE) AI IR
2 ABC BUS REACTOR/ LINE REACTOR RE REACTOR I (Y-PHASE) AI IY
3 ABC BUS REACTOR/ LINE REACTOR RE REACTOR I (B-PHASE) AI IB
4 ABC BUS REACTOR/ LINE REACTOR RE REACTOR MVAR AI MX
5 ABC BUS REACTOR/ LINE REACTOR RE REACTOR V (R-Y PHASE) AI KVRY
6 ABC BUS REACTOR/ LINE REACTOR RE REACTOR V (Y-B PHASE) AI KVYB
7 ABC BUS REACTOR/ LINE REACTOR RE REACTOR V (B-R PHASE) AI KVBR
8 ABC BUS REACTOR/ LINE REACTOR RE FREQUENCY AI HZ
9 ABC BUS REACTOR/ LINE REACTOR RE WTI TEMP R PHASE AI WTI ONLY ONE SIGNAL IN PLACE OF THREE SIGNALS APPLICABLE INDIVIDUALLY FOR R/Y/B PHASES TO BE CONSIDERED FOR 3 PHASE LINE REACTOR/ BUS REACTOR
10 ABC BUS REACTOR/ LINE REACTOR RE WTI TEMP Y PHASE AI WTI
11 ABC BUS REACTOR/ LINE REACTOR RE WTI TEMP B PHASE AI WTI
12 ABC BUS REACTOR/ LINE REACTOR RE OTI TEMP R PHASE AI OTI
13 ABC BUS REACTOR/ LINE REACTOR RE OTI TEMP Y PHASE AI OTI
14 ABC BUS REACTOR/ LINE REACTOR RE OTI TEMP B PHASE AI OTI
15 ABC BUS REACTOR/ LINE REACTOR RE DGA MOISTURE VALUE - R PHASE AI MOIS
16 ABC BUS REACTOR/ LINE REACTOR RE DGA H2 VALUE - R PHASE AI DGH2
17 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H2 VALUE - R PHASE AI C2H2
18 ABC BUS REACTOR/ LINE REACTOR RE DGA CO VALUE - R PHASE AI DGCO
19 ABC BUS REACTOR/ LINE REACTOR RE DGA CO2 VALUE - R PHASE AI DCO2
20 ABC BUS REACTOR/ LINE REACTOR RE DGA CH4 VALUE - R PHASE AI DCH4
21 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H6 VALUE - R PHASE AI C2H6
22 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H4 VALUE - R PHASE AI C2H4
23 ABC BUS REACTOR/ LINE REACTOR RE DGA O2 VALUE - R PHASE AI DGO2
24 ABC BUS REACTOR/ LINE REACTOR RE DGA MOISTURE VALUE - Y PHASE AI MOIS
25 ABC BUS REACTOR/ LINE REACTOR RE DGA H2 VALUE - Y PHASE AI DGH2
26 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H2 VALUE - Y PHASE AI C2H2
27 ABC BUS REACTOR/ LINE REACTOR RE DGA CO VALUE - Y PHASE AI DGCO
28 ABC BUS REACTOR/ LINE REACTOR RE DGA CO2 VALUE - Y PHASE AI DCO2
29 ABC BUS REACTOR/ LINE REACTOR RE DGA CH4 VALUE - Y PHASE AI DCH4
30 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H6 VALUE - Y PHASE AI C2H6
31 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H4 VALUE - Y PHASE AI C2H4
32 ABC BUS REACTOR/ LINE REACTOR RE DGA O2 VALUE - Y PHASE AI DGO2
33 ABC BUS REACTOR/ LINE REACTOR RE DGA MOISTURE VALUE - B PHASE AI MOIS
34 ABC BUS REACTOR/ LINE REACTOR RE DGA H2 VALUE - B PHASE AI DGH2
35 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H2 VALUE - B PHASE AI C2H2
36 ABC BUS REACTOR/ LINE REACTOR RE DGA CO VALUE - B PHASE AI DGCO
37 ABC BUS REACTOR/ LINE REACTOR RE DGA CO2 VALUE - B PHASE AI DCO2
38 ABC BUS REACTOR/ LINE REACTOR RE DGA CH4 VALUE - B PHASE AI DCH4
39 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H6 VALUE - B PHASE AI C2H6
40 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H4 VALUE - B PHASE AI C2H4
41 ABC BUS REACTOR/ LINE REACTOR RE DGA O2 VALUE - B PHASE AI DGO2
765 KV SPARE LINE REACTOR/ BUS REACTOR
1 ABC SPARE LINE REACTOR / BUS REACTOR RE WTI TEMP SPARE AI WTI
2 ABC SPARE LINE REACTOR / BUS REACTOR RE OTI TEMP SPARE AI OTI
3 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA MOISTURE VALUE AI MOIS
4 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA H2 VALUE AI DGH2
5 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA C2H2 VALUE AI C2H2
6 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA CO VALUE AI DGCO
7 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA CO2 VALUE AI DCO2
8 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA CH4 VALUE AI DCH4
9 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA C2H6 VALUE AI C2H6
10 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA C2H4 VALUE AI C2H4
11 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA O2 VALUE AI DGO2
765 KV/ 400 KV/ 220KV /132 KV TIE BAY / BUS COUPLER / BUS SECTION / TBC
1 ABC TIE/ BUS COUPLER / BUS SECTION TIE/ BC/ BS I (R-PHASE) AI IR
2 ABC TIE/ BUS COUPLER / BUS SECTION TIE/ BC/ BS I (Y-PHASE) AI IY
3 ABC TIE/ BUS COUPLER / BUS SECTION TIE/ BC/ BS I (B-PHASE) AI IB
1 ABC ICT XFMR_P I (R-PHASE) AI IR
2 ABC ICT XFMR_P I (Y-PHASE) AI IY
3 ABC ICT XFMR_P I (B-PHASE) AI IB
4 ABC ICT XFMR_P MW AI MW
5 ABC ICT XFMR_P MVAR AI MX
6 ABC ICT XFMR_P V (R-Y PHASE) AI KVRY
7 ABC ICT XFMR_P V (Y-B PHASE) AI KVYB
8 ABC ICT XFMR_P V (B-R PHASE) AI KVBR
9 ABC ICT XFMR_P FREQUENCY AI HZ
10 ABC ICT XFMR_P HVWTI TEMP - R PHASE AI HVWT ONLY ONE SIGNAL IN PLACE OF THREE SIGNALS APPLICABLE INDIVIDUALLY FOR R/Y/B PHASES TO BE CONSIDERED IN CASE OF 3-PHASE ICT
11 ABC ICT XFMR_S IVWTI TEMP - R PHASE AI IVWT
12 ABC ICT XFMR_T LVWTI TEMP - R PHASE AI LVWT
13 ABC ICT XFMR_P HVWTI TEMP - Y PHASE AI HVWT
14 ABC ICT XFMR_S IVWTI TEMP - Y PHASE AI IVWT
15 ABC ICT XFMR_T LVWTI TEMP - Y PHASE AI LVWT
16 ABC ICT XFMR_P HVWTI TEMP - B PHASE AI HVWT
17 ABC ICT XFMR_S IVWTI TEMP - B PHASE AI IVWT
18 ABC ICT XFMR_T LVWTI TEMP - B PHASE AI LVWT
19 ABC ICT XFMR_P OTI TEMP R PHASE AI OTI
20 ABC ICT XFMR_P OTI TEMP Y PHASE AI OTI
21 ABC ICT XFMR_P OTI TEMP B PHASE AI OTI
22 ABC ICT XFMR_P TAP POSITION INDICATOR - R PHASE AI TPI
23 ABC ICT XFMR_P TAP POSITION INDICATOR - Y PHASE AI TPI
24 ABC ICT XFMR_P TAP POSITION INDICATOR - B PHASE AI TPI
25 ABC ICT XFMR_P DGA MOISTURE VALUE - R PHASE AI MOIS
26 ABC ICT XFMR_P DGA H2 VALUE - R PHASE AI DGH2
27 ABC ICT XFMR_P DGA C2H2 VALUE - R PHASE AI C2H2
28 ABC ICT XFMR_P DGA CO VALUE - R PHASE AI DGCO
29 ABC ICT XFMR_P DGA CO2 VALUE - R PHASE AI DCO2
30 ABC ICT XFMR_P DGA CH4 VALUE - R PHASE AI DCH4
31 ABC ICT XFMR_P DGA C2H6 VALUE - R PHASE AI C2H6
32 ABC ICT XFMR_P DGA C2H4 VALUE - R PHASE AI C2H4
33 ABC ICT XFMR_P DGA O2 VALUE - R PHASE AI DGO2
34 ABC ICT XFMR_P DGA MOISTURE VALUE - Y PHASE AI MOIS
35 ABC ICT XFMR_P DGA H2 VALUE - Y PHASE AI DGH2
36 ABC ICT XFMR_P DGA C2H2 VALUE - Y PHASE AI C2H2
37 ABC ICT XFMR_P DGA CO VALUE - Y PHASE AI DGCO
38 ABC ICT XFMR_P DGA CO2 VALUE - Y PHASE AI DCO2
39 ABC ICT XFMR_P DGA CH4 VALUE - Y PHASE AI DCH4
40 ABC ICT XFMR_P DGA C2H6 VALUE - Y PHASE AI C2H6
41 ABC ICT XFMR_P DGA C2H4 VALUE - Y PHASE AI C2H4
42 ABC ICT XFMR_P DGA O2 VALUE - Y PHASE AI DGO2
43 ABC ICT XFMR_P DGA MOISTURE VALUE - B PHASE AI MOIS
44 ABC ICT XFMR_P DGA H2 VALUE - B PHASE AI DGH2
45 ABC ICT XFMR_P DGA C2H2 VALUE - B PHASE AI C2H2
46 ABC ICT XFMR_P DGA CO VALUE - B PHASE AI DGCO
47 ABC ICT XFMR_P DGA CO2 VALUE - B PHASE AI DCO2
48 ABC ICT XFMR_P DGA CH4 VALUE - B PHASE AI DCH4
49 ABC ICT XFMR_P DGA C2H6 VALUE - B PHASE AI C2H6
50 ABC ICT XFMR_P DGA C2H4 VALUE - B PHASE AI C2H4
51 ABC ICT XFMR_P DGA O2 VALUE - B PHASE AI DGO2
765 KV SPARE ICT
1 SPARE SPARE ICT XFMR_P HVWTI - TEMP SPARE AI HVWT
2 SPARE SPARE ICT XFMR_S IVWTI - TEMP SPARE AI IVWT
3 SPARE SPARE ICT XFMR_T LVWTI - TEMP SPARE AI LVWT
4 SPARE SPARE ICT XFMR_P OTI TEMP SPARE AI OTI
5 SPARE SPARE ICT XFMR_P TAP POSITION INDICATOR AI TPI
6 SPARE SPARE ICT XFMR_P DGA MOISTURE VALUE AI MOIS
7 SPARE SPARE ICT XFMR_P DGA H2 VALUE AI DGH2
8 SPARE SPARE ICT XFMR_P DGA C2H2 VALUE AI C2H2
9 SPARE SPARE ICT XFMR_P DGA CO VALUE AI DGCO
10 SPARE SPARE ICT XFMR_P DGA CO2 VALUE AI DCO2
11 SPARE SPARE ICT XFMR_P DGA CH4 VALUE AI DCH4
12 SPARE SPARE ICT XFMR_P DGA C2H6 VALUE AI C2H6
13 SPARE SPARE ICT XFMR_P DGA C2H4 VALUE AI C2H4
14 SPARE SPARE ICT XFMR_P DGA O2 VALUE AI DGO2
FIXED SERIES CAPACITOR (FSC)
1 ABC FSC FSC-X MOV TEMPERATURE R PHASE AI
2 ABC FSC FSC-X MOV TEMPERATURE Y PHASE AI
3 ABC FSC FSC-X MOV TEMPERATURE B PHASE AI
4 ABC FSC FSC-X CAPACITOR R PHASE CURRENT AI
5 ABC FSC FSC-X CAPACITOR Y PHASE CURRENT AI
6 ABC FSC FSC-X CAPACITOR B PHASE CURRENT AI
7 ABC FSC FSC-X CAPACITOR R PHASE UNBALANCED CURRENT AI
8 ABC FSC FSC-X CAPACITOR Y PHASE UNBALANCED CURRENT AI
9 ABC FSC FSC-X CAPACITOR B PHASE UNBALANCED CURRENT AI
10 ABC FSC FSC-X LINE CT CURRENT R-PH AI
11 ABC FSC FSC-X LINE CT CURRENT Y-PH AI
12 ABC FSC FSC-X LINE CT CURRENT B-PH AI
13 ABC FSC FSC-X KIOSK TEMP AI
AUXILLIARY SYSTEM
1 220VDC DCDB 220V_DCDB-1 220V DCDB -1 VOLTAGE AI
2 220VDC DCDB 220V_DCDB-1 220V BATTERY SET-1 CURRENT AI
3 220VDC DCDB 220V_DCDB-2 220V DCDB -2 VOLTAGE AI
4 220VDC DCDB 220V_DCDB-2 220V BATTERY SET-2 CURRENT AI
5 48 VDC DCDB 48V_DCDB-1 48V DCDB -1 VOLTAGE AI
6 48 VDC DCDB 48V_DCDB-1 48V BATTERY SET-1 CURRENT AI
7 48 VDC DCDB 48V_DCDB-2 48V DCDB -2 VOLTAGE AI
8 48 VDC DCDB 48V_DCDB-2 48V BATTERY SET-2 CURRENT AI
9 220VDC BCHRG BATCHRG220V-1 220V BATTERY CHARGER-1 CURRENT AI
10 220VDC BCHRG BATCHRG220V-2 220V BATTERY CHARGER-2 CURRENT AI
11 48 VDC BCHRG BATCHRG48V-1 48V BATTERY CHARGER-1 CURRENT AI
12 48 VDC BCHRG BATCHRG48V-2 48V BATTERY CHARGER-2 CURRENT AI
13 415 V FP FIREPROTN FIRE FIGHTING PRESSURE MONITORING AI
14 415 V FP DPUMP DIESEL ENGINE BATTERY-1 VOLTAGE AI
15 415 V FP DPUMP DIESEL ENGINE BATTERY-2 VOLTAGE AI
16 415 V FP ICT FF NIS Nitrogen Cylinder Pressure AI
17 WIND SPEED AI
18 WIND DIRECTION AI
19 415 V AIRCON G_KIOSK_1 765KV KIOSK-1 TEMP AI
20 415 V AIRCON F_KIOSK_1 400KV KIOSK-1 TEMP AI
21 415 V AIRCON TEMP_MON CONTROL ROOM TEMPRATURE AI
22 415 V AIRCON TEMP_MON BATTERY ROOM TEMPRATURE AI
23 415 V AIRCON TEMP_MON AMBIENT TEMPERATURE OUTDOOR AI
24 415 V AIRCON TEMP_MON AMBIENT RELATIVE HUMIDITY OUTDOOR AI
25 415 V DG Set DGSET-1 VOLTAGE (R-Y PHASE) AI
26 415 V DG Set DGSET-1 VOLTAGE (Y-B PHASE) AI
27 415 V DG Set DGSET-1 VOLTAGE (B-R PHASE) AI
28 415 V DG Set DGSET-1 CURRENT (R-PHASE) AI
29 415 V DG Set DGSET-1 CURRENT (Y-PHASE) AI
30 415 V DG Set DGSET-1 CURRENT (B-PHASE) AI
31 415 V DG Set DGSET-1 DG SET BATTERY-1 VOLTAGE AI
32 415 V DG Set DGSET-1 DG SET BATTERY-2 VOLTAGE AI
33 415 V LTSUP MSB-1 VOLTAGE (R-Y PHASE) AI
34 415 V LTSUP MSB-1 VOLTAGE (Y-B PHASE) AI
35 415 V LTSUP MSB-1 VOLTAGE (B-R PHASE) AI
36 415 V LTSUP MSB-1 CURRENT (R-PHASE) AI
37 415 V LTSUP MSB-1 CURRENT (Y-PHASE) AI
38 415 V LTSUP MSB-1 CURRENT (B-PHASE) AI
39 415 V LTSUP MSB-2 VOLTAGE (R-Y PHASE) AI
40 415 V LTSUP MSB-2 VOLTAGE (Y-B PHASE) AI
41 415 V LTSUP MSB-2 VOLTAGE (B-R PHASE) AI
42 415 V LTSUP MSB-2 CURRENT (R-PHASE) AI
43 415 V LTSUP MSB-2 CURRENT (Y-PHASE) AI
44 415 V LTSUP MSB-2 CURRENT (B-PHASE) AI
STATCOM (SIEMENS)
1 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY HV Main Bay Voltage R-Y AI
2 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY HV Main Bay Voltage Y-B AI
3 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY HV Main Bay Voltage B-R AI
4 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY HV Main Bay Current_Phase R AI
5 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY HV Main Bay Current_Phase Y AI
6 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY HV Main Bay Current_Phase B AI
7 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER COUPLING TRANSFORMER MVAR HV SIDE AI
8 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA CARBON DIOXIDE AI
9 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA ETHYLENE AI
10 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA ACETYLENE AI
11 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA ETHANE AI
12 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA HYDROGEN AI
13 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA OXYGEN AI
14 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA METHANE AI
15 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA CARBON MONOXIDE AI
16 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA NITROGEN AI
17 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA WATER AI
18 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA COMBUSTIBLE GASSES AI
19 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA CARBON DIOXIDE AI
20 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA ETHYLENE AI
21 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA ACETYLENE AI
22 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA ETHANE AI
23 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA HYDROGEN AI
24 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA OXYGEN AI
25 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA METHANE AI
26 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA CARBON MONOXIDE AI
27 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA NITROGEN AI
28 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA WATER AI
29 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA COMBUSTIBLE GASSES AI
30 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA CARBON DIOXIDE AI
31 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA ETHYLENE AI
32 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA ACETYLENE AI
33 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA ETHANE AI
34 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA HYDROGEN AI
35 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA OXYGEN AI
36 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA METHANE AI
37 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA CARBON MONOXIDE AI
38 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA NITROGEN AI
39 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA WATER AI
40 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA COMBUSTIBLE GASSES AI
41 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA CARBON DIOXIDE AI
42 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA ETHYLENE AI
43 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA ACETYLENE AI
44 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA ETHANE AI
45 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA HYDROGEN AI
46 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA OXYGEN AI
47 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA METHANE AI
48 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA CARBON MONOXIDE AI
49 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA NITROGEN AI
50 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA WATER AI
51 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA COMBUSTIBLE GASSES AI
52 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY HV Tie Bay Current_Phase R AI
53 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY HV Tie Bay Current_Phase Y AI
54 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY HV Tie Bay Current_Phase B AI
55 STATCOM STATCOM MV BUS BAR MV BUS VOLTAGE AI
56 J11 STATCOM VSC-1 BAY VSC-1 MV-J11 STATCOM 1 MVAR AI
57 J12 STATCOM VSC-2 BAY VSC-2 MV-J12 STATCOM 2 MVAR AI
58 J21 STATCOM MSR-1 BAY MSR-1 MV-J21 MSR 1 MVAR AI
59 J22 STATCOM MSR-2 BAY MSR-2 MV-J22 MSR 2 MVAR AI
60 J31 STATCOM MSC-1 BAY MSC-1 MV-J31 MSC 1 MVAR AI
61 J32 STATCOM MSC-2 BAY MSC-2 MV-J32 MSC 2 MVAR AI
62 STATCOM STATCOM STATCOM OPERATION SLOPE AI
63 STATCOM STATCOM STATCOM OPERATION UP-SET U-REF(PU) AI
64 STATCOM STATCOM STATCOM OPERATION DN-SET U-REF(PU) AI
65 STATCOM STATCOM STATCOM OPERATION Q-SET REF(PU) AI
66 STATCOM STATCOM STATCOM OPERATION LOAD FACTOR SETPOINT AI
67 STATCOM STATCOM STATCOM OPERATION FIXED REACTIVE POWER SETPOINT(FS REF) AI
68 STATCOM STATCOM STATCOM OPERATION NPS DEADBAND SETPOINT AI
69 STATCOM STATCOM STATCOM OPERATION VQ MIN SETPOINT AI
70 STATCOM STATCOM STATCOM OPERATION VQ MAX SETPOINT AI
71 STATCOM STATCOM STATCOM OPERATION GAIN FACTOR SETPOINT AI
72 STATCOM STATCOM STATCOM OPERATION INDUCTIVE VOLTAGE SETPOINT AI
73 STATCOM STATCOM STATCOM OPERATION CAPACITIVE VOLTAGE SETPOINT AI
74 STATCOM STATCOM STATCOM OPERATION LOAD FACTOR SETPOINT AI
75 STATCOM STATCOM STATCOM OPERATION FIXED REACTIVE POWER SETPOINT(FS REF) AI
76 STATCOM STATCOM STATCOM OPERATION REACTIVE POWER SETPOINT (QREF) AI
77 STATCOM STATCOM STATCOM OPERATION NPS DEADBAND SETPOINT AI
78 STATCOM STATCOM STATCOM OPERATION VQ MIN SETPOINT AI
79 STATCOM STATCOM STATCOM OPERATION VQ MAX SETPOINT AI
80 STATCOM STATCOM STATCOM OPERATION SLOPE SETPOINT AI
81 STATCOM STATCOM STATCOM OPERATION GAIN FACTOR SETPOINT AI
478 STATCOM STATCOM STATCOM OPERATION INDUCTIVE VOLTAGE SETPOINT APC
479 STATCOM STATCOM STATCOM OPERATION CAPACITIVE VOLTAGE SETPOINT APC
480 STATCOM STATCOM STATCOM OPERATION LOAD FACTOR SETPOINT APC
481 STATCOM STATCOM STATCOM OPERATION FIXED REACTIVE POWER SETPOINT(FS REF) APC
482 STATCOM STATCOM STATCOM OPERATION REACTIVE POWER SETPOINT (QREF) APC
483 STATCOM STATCOM STATCOM OPERATION NPS DEADBAND SETPOINT APC
484 STATCOM STATCOM STATCOM OPERATION VQ MIN SETPOINT APC
485 STATCOM STATCOM STATCOM OPERATION VQ MAX SETPOINT APC
486 STATCOM STATCOM STATCOM OPERATION SLOPE SETPOINT APC
487 STATCOM STATCOM STATCOM OPERATION GAIN FACTOR SETPOINT APC
1 ABC FUTURE& COUPLING T/F-1 TIE TIE BAY CURRENT PHASE_R AI
2 ABC FUTURE& COUPLING T/F-1 TIE TIE BAY CURRENT PHASE_Y AI
3 ABC FUTURE& COUPLING T/F-1 TIE TIE BAY CURRENT PHASE_B AI
4 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI-R-PH TEMP (HV SIDE) AI
5 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -R-PHTEMP (IV SIDE) AI
6 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -R-PH TEMP (LV SIDE) AI
7 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) OTI R-PH TEMP AI
8 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) TAP POSITION INDICATION R-PH AI
9 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI-Y-PH TEMP (HV SIDE) AI
10 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -Y-PH TEMP (IV SIDE) AI
11 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -Y-PH TEMP (LV SIDE) AI
12 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) OTI Y-PH TEMP AI
13 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) TAP POSITION INDICATION Y-PH AI
14 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI-B-PH TEMP (HV SIDE) AI
15 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -B-PH TEMP (IV SIDE) AI
16 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -B-PH TEMP (LV SIDE) AI
17 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) OTI B-PH TEMP AI
18 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) TAP POSITION INDICATION B-PH AI
19 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI- SP-PH TEMP (HV SIDE) AI
20 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -SP-PH TEMP (IV SIDE) AI
21 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -SP-PH TEMP (LV SIDE) AI
22 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) OTI SP-PH TEMP AI
23 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) TAP POSITION SP-PH INDICATION AI
24 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) I (R-PHASE) AI
25 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) I (Y-PHASE) AI
26 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) I B-PHASE) AI
27 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) MVAR AI
28 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) MW AI
29 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) V (B-R PHASE) AI
30 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) V (R-Y PHASE) AI
31 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) V (Y-B PHASE) AI
32 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) FREQUENCY AI
33 ABC COUPLING TRANSFORMER STATCOM HV BAY - RPH DGA H2O INDICATION R phase AI
34 ABC COUPLING TRANSFORMER STATCOM HV BAY - RPH DGA H2 LEVEL INDICATION R phase AI
35 ABC COUPLING TRANSFORMER STATCOM HV BAY - YPH DGA H2O INDICATION Y phase AI
36 ABC COUPLING TRANSFORMER STATCOM HV BAY - YPH DGA H2 LEVEL INDICATION Y phase AI
37 ABC COUPLING TRANSFORMER STATCOM HV BAY - BPH DGA H2O INDICATION B phase AI
38 ABC COUPLING TRANSFORMER STATCOM HV BAY - BPH DGA H2 LEVEL INDICATION B phase AI
39 ABC COUPLING TRANSFORMER STATCOM HV BAY - SPARE PH DGA H2O INDICATION Spare phase AI
40 ABC COUPLING TRANSFORMER STATCOM HV BAY - SPARE PH DGA H2 LEVEL INDICATION Spare phase AI
41 38.5KV MV BUS BAR MV BUS BAR MV BUS VOLTAGE AI
42 38.5KV STATCOM- 1 VSC-1 STATCOM- 1 MVAR AI
43 38.5KV STATCOM- 2 VSC-2 STATCOM- 2 MVAR AI
44 38.5KV MSC MSC MSC MVAR AI
45 38.5KV MSR- 1 MSR-1 MSR- 1 MVAR AI
46 38.5KV MSR- 2 MSR-2 MSR- 2 MVAR AI
47 38.5KV STATCOM CONTROL STATCOM SLOPE OF INDUCTIVE POWER AI
48 38.5KV STATCOM CONTROL STATCOM SLOPE OF CAPACITIVE POWER AI
49 38.5KV STATCOM CONTROL STATCOM UP-SET U-REF(PU) AI
50 38.5KV STATCOM CONTROL STATCOM DN-SET U-REF(PU) AI
51 38.5KV STATCOM CONTROL STATCOM Q-SET REF(PU)/FS REF(PU) AI
52 415 V AUX DCDB-1 DCDB-1 VOLTAGE AI
53 415 V AUX DCDB-1 BATTERY SET-1 CURRENT AI
54 415 V AUX CHARGER-1 BATTERY CHARGER-1 CURRENT AI
55 415 V AUX DCDB-2 DCDB-2 VOLTAGE AI
56 415 V AUX DCDB-2 BATTERY SET-2 CURRENT AI
57 415 V AUX CHARGER-2 BATTERY CHARGER-2 CURRENT AI
58 415 V AUX MSB INCOMER-1 VOLTAGE R-Y AI
59 415 V AUX MSB INCOMER-1 VOLTAGE Y-B AI
60 415 V AUX MSB INCOMER-1 VOLTAGE B-R AI
61 415 V AUX MSB INCOMER-1 CURRENT R AI
62 415 V AUX MSB INCOMER-1 CURRENT Y AI
63 415 V AUX MSB INCOMER-1 CURRENT B AI
64 415 V AUX MSB INCOMER-2 VOLTAGE R-Y AI
65 415 V AUX MSB INCOMER-2 VOLTAGE Y-B AI
66 415 V AUX MSB INCOMER-2 VOLTAGE B-R AI
67 415 V AUX MSB INCOMER-2 CURRENT R AI
68 415 V AUX MSB INCOMER-2 CURRENT Y AI
69 415 V AUX MSB INCOMER-2 CURRENT B AI
70 415 V AUX AIRCON AMBIENT AMBIENT TEMPERATURE SWITCHYARD AI
71 415 V AUX AIRCON CONTROL ROOM CONTROL ROOM TEMPERATURE AI
72 415 V AUX AIRCON BATTERY ROOM BATTERY ROOM TEMPERATURE AI
73 415 V AUX AIRCON UPS ROOM UPS ROOM TEMPERATURE AI
STATCOM (HYOSUNG)
1 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY Voltage R-Y AI
2 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY Voltage Y-B AI
3 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY Voltage B-R AI
4 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN + TIE Current_Phase R AI
5 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN + TIE Current_Phase Y AI
6 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN + TIE Current_Phase B AI
7 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) MVAR OF COUPLING TRANSFORMER HV SIDE AI
8 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) C2H2 AI
9 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) C2H4 AI
10 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) C2H6 AI
11 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) CH4 AI
12 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) CO2 AI
13 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) CO AI
14 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) H2O AI
15 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) H2 AI
16 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) C2H2 AI
17 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) C2H4 AI
18 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) C2H6 AI
19 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) CH4 AI
20 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) CO2 AI
21 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) CO AI
22 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) H2O AI
23 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) H2 AI
24 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) C2H2 AI
25 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) C2H4 AI
26 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) C2H6 AI
27 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) CH4 AI
28 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) CO2 AI
29 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) CO AI
30 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) H2O AI
31 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) H2 AI
32 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) C2H2 AI
33 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) C2H4 AI
34 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) C2H6 AI
35 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) CH4 AI
36 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) CO2 AI
37 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) CO AI
38 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) H2O AI
39 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) H2 AI
40 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) WTI-HV AI
41 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) WTI-LV AI
42 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) OTI AI
43 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) WTI-HV AI
44 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) WTI-LV AI
45 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) OTI AI
46 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) WTI-HV AI
47 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) WTI-LV AI
48 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) OTI AI
49 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) WTI-HV AI
50 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) WTI-LV AI
51 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) OTI AI
52 20KV STATCOM-1 VSC-1 STATCOM UNIT-1 MVAR AI
53 20KV STATCOM-2 VSC-2 STATCOM UNIT-2 MVAR AI
54 20KV STATCOM CONTROL STATCOM V-REF SETTING AI
55 20KV STATCOM CONTROL STATCOM DROOP SETTING AI
56 20KV STATCOM CONTROL STATCOM DEAD-BAND UP SETTING AI
57 20KV STATCOM CONTROL STATCOM DEAD-BAND DN SETTING AI
58 20KV STATCOM CONTROL STATCOM Q-REF SETTING AI
59 20KV MV BUS BAR MV BUS BAR MV BUS VOLTAGE AI
60 20KV AUX.T/F MV AUX T/F KW AI
61 20KV AUX.T/F MV AUX T/F KVAR AI
62 33KV AUX.T/F TERTIARY KW AI
63 33KV AUX.T/F TERTIARY KVAR AI
64 415 V DCDB DCDB-1 220V DCDB-1 VOLTAGE AI
65 415 V DCDB DCDB-1 220V BATTERY SET-1 CURRENT AI
66 415 V DCDB DCDB-1 220V BATTERY CHARGER-1 CURRENT AI
67 415 V DCDB DCDB-2 220V DCDB-2 VOLTAGE AI
68 415 V DCDB DCDB-2 220V BATTERY SET-2 CURRENT AI
69 415 V DCDB DCDB-2 220V BATTERY CHARGER-2 CURRENT AI
70 415 V LTSUP MSB-1 (R-PH) INCOMER-1 VOLTAGE AI
71 415 V LTSUP MSB-1 (Y-PH) INCOMER-1 VOLTAGE AI
72 415 V LTSUP MSB-1 (B-PH) INCOMER-1 VOLTAGE AI
73 415 V LTSUP MSB-2 (R-PH) INCOMER-2 VOLTAGE AI
74 415 V LTSUP MSB-2 (Y-PH) INCOMER-2 VOLTAGE AI
75 415 V LTSUP MSB-2 (B-PH) INCOMER-2 VOLTAGE AI
76 415 V LTSUP MSB-1 (R-PH) INCOMER-1 CURRENT AI
77 415 V LTSUP MSB-1 (Y-PH) INCOMER-1 CURRENT AI
78 415 V LTSUP MSB-1 (B-PH) INCOMER-1 CURRENT AI
79 415 V LTSUP MSB-2 (R-PH) INCOMER-2 CURRENT AI
80 415 V LTSUP MSB-2 (Y-PH) INCOMER-2 CURRENT AI
81 415 V LTSUP MSB-2 (B-PH) INCOMER-2 CURRENT AI
82 415 V LTSUP DGSET (R-PH) DG FEEDER VOLTAGE AI
83 415 V LTSUP DGSET (Y-PH) DG FEEDER VOLTAGE AI
84 415 V LTSUP DGSET (B-PH) DG FEEDER VOLTAGE AI
85 415 V LTSUP DGSET (R-PH) DG FEEDER CURRENT AI
86 415 V LTSUP DGSET (Y-PH) DG FEEDER CURRENT AI
87 415 V LTSUP DGSET (B-PH) DG FEEDER CURRENT AI
88 20KV MSR-1 MSR MSR-1 MVAR AI
89 20KV MSR-2 MSR MSR-2 MVAR AI
90 20KV MSC MSC MSC MVAR AI
91 20KV STATCOM-1 STATCOM CONTROLLER A CONTROL MODE : MANUAL Q CONTROL / AUTOMATIC VOLTAGE AI_CMD 1 : Manual Q / 5 : Automatic Voltage
92 20KV STATCOM-1 STATCOM CONTROLLER A V-REF SETTING AI_CMD
93 20KV STATCOM-1 STATCOM CONTROLLER A DEAD-BAND UP SETTING AI_CMD
94 20KV STATCOM-1 STATCOM CONTROLLER A DEAD-BAND DN SETTING AI_CMD
95 20KV STATCOM-1 STATCOM CONTROLLER A DROOP SETTING AI_CMD
96 20KV STATCOM-1 STATCOM CONTROLLER A Q-REF SETTING AI_CMD
97 20KV STATCOM-1 STATCOM CONTROLLER A POD CONTROL ENABLE AI_CMD 1 : Manual Q / 5 : Automatic Voltage
98 20KV STATCOM-1 STATCOM CONTROLLER A SSOD CONTROL ENABLE AI_CMD 1 : Manual Q / 5 : Automatic Voltage
99 20KV STATCOM-1 STATCOM CONTROLLER A ADACTIVE GAIN REDUCTION ENABLE AI_CMD 1 : Manual Q / 5 : Automatic Voltage
100 20KV STATCOM-1 STATCOM CONTROLLER A ADACTIVE GAIN CLACULATION ENABLE AI_CMD 1 : Manual Q / 5 : Automatic Voltage
101 20KV STATCOM-1 STATCOM CONTROLLER A NEGATIVE SEQ. VOLTAGE CONTROL ENABLE AI_CMD 1 : Manual Q / 5 : Automatic Voltage
102 20KV STATCOM-1 STATCOM CONTROLLER A MSC CONTROL MODE - AUTOMATIC / MANUAL AI_CMD 1 : Manual Q / 5 : Automatic Voltage
103 20KV STATCOM-1 STATCOM CONTROLLER A MSR-1 CONTROL MODE - AUTOMATIC / MANUAL AI_CMD 1 : Manual Q / 5 : Automatic Voltage
104 20KV STATCOM-1 STATCOM CONTROLLER A MSR-2 CONTROL MODE - AUTOMATIC / MANUAL AI_CMD 1 : Manual Q / 5 : Automatic Voltage
105 20KV STATCOM-1 STATCOM CONTROLLER A HV BR MAIN BAY CONTROL MODE - AUTOMATIC (HYD ONLY) AI_CMD 1 : Manual Q / 5 : Automatic Voltage
106 20KV STATCOM-1 STATCOM CONTROLLER A HV BR TIE BAY CONTROL MODE - AUTOMATIC (HYD ONLY) AI_CMD 1 : Manual Q / 5 : Automatic Voltage
107 20KV STATCOM-2 STATCOM CONTROLLER B CONTROL MODE : MANUAL Q CONTROL / AUTOMATIC VOLTAGE AI_CMD 1 : Manual Q / 5 : Automatic Voltage
108 20KV STATCOM-2 STATCOM CONTROLLER B V-REF SETTING AI_CMD
109 20KV STATCOM-2 STATCOM CONTROLLER B DEAD-BAND UP SETTING AI_CMD
110 20KV STATCOM-2 STATCOM CONTROLLER B DEAD-BAND DN SETTING AI_CMD
111 20KV STATCOM-2 STATCOM CONTROLLER B DROOP SETTING AI_CMD
112 20KV STATCOM-2 STATCOM CONTROLLER B Q-REF SETTING AI_CMD
113 20KV STATCOM-2 STATCOM CONTROLLER B POD CONTROL ENABLE AI_CMD 1 : Manual Q / 5 : Automatic Voltage
114 20KV STATCOM-2 STATCOM CONTROLLER B SSOD CONTROL ENABLE AI_CMD 1 : Manual Q / 5 : Automatic Voltage
115 20KV STATCOM-2 STATCOM CONTROLLER B ADACTIVE GAIN REDUCTION ENABLE AI_CMD 1 : Manual Q / 5 : Automatic Voltage
116 20KV STATCOM-2 STATCOM CONTROLLER B ADACTIVE GAIN CLACULATION ENABLE AI_CMD 1 : Manual Q / 5 : Automatic Voltage
117 20KV STATCOM-2 STATCOM CONTROLLER B NEGATIVE SEQ. VOLTAGE CONTROL ENABLE AI_CMD 1 : Manual Q / 5 : Automatic Voltage
118 20KV STATCOM-2 STATCOM CONTROLLER B MSC CONTROL MODE - AUTOMATIC / MANUAL AI_CMD 1 : Manual Q / 5 : Automatic Voltage
119 20KV STATCOM-2 STATCOM CONTROLLER B MSR-1 CONTROL MODE - AUTOMATIC / MANUAL AI_CMD 1 : Manual Q / 5 : Automatic Voltage
120 20KV STATCOM-2 STATCOM CONTROLLER B MSR-2 CONTROL MODE - AUTOMATIC / MANUAL AI_CMD 1 : Manual Q / 5 : Automatic Voltage
121 20KV STATCOM-2 STATCOM CONTROLLER B HV BR MAIN BAY CONTROL MODE - AUTOMATIC / MANUAL (HYD ONLY) AI_CMD 1 : Manual Q / 5 : Automatic Voltage
122 20KV STATCOM-2 STATCOM CONTROLLER B HV BR TIE BAY CONTROL MODE - AUTOMATIC / MANUAL (HYD ONLY) AI_CMD 1 : Manual Q / 5 : Automatic Voltage
Sl. BAY NUM. BAY NAME DEVICE ID SIGNAL DESCRIPTION DATA TYPE SCADA ID REMARK
1 BUS BUS BUS VOLTAGE R-Y PHASE AI KVRY
2 BUS BUS BUS VOLTAGE Y-B PHASE AI KVYB
3 BUS BUS BUS VOLTAGE B-R PHASE AI KVBR
4 BUS BUS BUS FREQUENCY AI HZ
1 ABC LINE FEEDER LINE / LSR / BSR I (R-PHASE) AI IR
2 ABC LINE FEEDER LINE / LSR / BSR I (Y-PHASE) AI IY
3 ABC LINE FEEDER LINE / LSR / BSR I (B-PHASE) AI IB
4 ABC LINE FEEDER LINE / LSR / BSR MW AI MW
5 ABC LINE FEEDER LINE / LSR / BSR MVAR AI MX
6 ABC LINE FEEDER LINE / LSR / BSR V (R-Y PHASE) AI KVRY
7 ABC LINE FEEDER LINE / LSR / BSR V (Y-B PHASE) AI KVYB
8 ABC LINE FEEDER LINE / LSR / BSR V (B-R PHASE) AI KVBR
9 ABC LINE FEEDER LINE / LSR / BSR FREQUENCY AI HZ
10 ABC LINE FEEDER LINE MAIN-1 FAULT IMPEDANCE AI FLZ1
11 ABC LINE FEEDER LINE MAIN-1 FAULT DISTANCE AI FLD1
12 ABC LINE FEEDER LINE MAIN-1 FAULT PERCENTAGE AI FLP1
13 ABC LINE FEEDER LINE MAIN-2 FAULT IMPEDANCE AI FLZ2
14 ABC LINE FEEDER LINE MAIN-2 FAULT DISTANCE AI FLD2
15 ABC LINE FEEDER LINE MAIN-2 FAULT PERCENTAGE AI FLP2
1 ABC BUS REACTOR/ LINE REACTOR RE REACTOR I (R-PHASE) AI IR
2 ABC BUS REACTOR/ LINE REACTOR RE REACTOR I (Y-PHASE) AI IY
3 ABC BUS REACTOR/ LINE REACTOR RE REACTOR I (B-PHASE) AI IB
4 ABC BUS REACTOR/ LINE REACTOR RE REACTOR MVAR AI MX
5 ABC BUS REACTOR/ LINE REACTOR RE REACTOR V (R-Y PHASE) AI KVRY
6 ABC BUS REACTOR/ LINE REACTOR RE REACTOR V (Y-B PHASE) AI KVYB
7 ABC BUS REACTOR/ LINE REACTOR RE REACTOR V (B-R PHASE) AI KVBR
8 ABC BUS REACTOR/ LINE REACTOR RE FREQUENCY AI HZ
9 ABC BUS REACTOR/ LINE REACTOR RE WTI TEMP R PHASE AI WTI ONLY ONE SIGNAL IN PLACE OF THREE SIGNALS APPLICABLE INDIVIDUALLY FOR R/Y/B PHASES TO BE CONSIDERED FOR 3 PHASE LINE REACTOR/ BUS REACTOR
10 ABC BUS REACTOR/ LINE REACTOR RE WTI TEMP Y PHASE AI WTI
11 ABC BUS REACTOR/ LINE REACTOR RE WTI TEMP B PHASE AI WTI
12 ABC BUS REACTOR/ LINE REACTOR RE OTI TEMP R PHASE AI OTI
13 ABC BUS REACTOR/ LINE REACTOR RE OTI TEMP Y PHASE AI OTI
14 ABC BUS REACTOR/ LINE REACTOR RE OTI TEMP B PHASE AI OTI
15 ABC BUS REACTOR/ LINE REACTOR RE DGA MOISTURE VALUE - R PHASE AI MOIS
16 ABC BUS REACTOR/ LINE REACTOR RE DGA H2 VALUE - R PHASE AI DGH2
17 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H2 VALUE - R PHASE AI C2H2
18 ABC BUS REACTOR/ LINE REACTOR RE DGA CO VALUE - R PHASE AI DGCO
19 ABC BUS REACTOR/ LINE REACTOR RE DGA CO2 VALUE - R PHASE AI DCO2
20 ABC BUS REACTOR/ LINE REACTOR RE DGA CH4 VALUE - R PHASE AI DCH4
21 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H6 VALUE - R PHASE AI C2H6
22 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H4 VALUE - R PHASE AI C2H4
23 ABC BUS REACTOR/ LINE REACTOR RE DGA O2 VALUE - R PHASE AI DGO2
24 ABC BUS REACTOR/ LINE REACTOR RE DGA MOISTURE VALUE - Y PHASE AI MOIS
25 ABC BUS REACTOR/ LINE REACTOR RE DGA H2 VALUE - Y PHASE AI DGH2
26 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H2 VALUE - Y PHASE AI C2H2
27 ABC BUS REACTOR/ LINE REACTOR RE DGA CO VALUE - Y PHASE AI DGCO
28 ABC BUS REACTOR/ LINE REACTOR RE DGA CO2 VALUE - Y PHASE AI DCO2
29 ABC BUS REACTOR/ LINE REACTOR RE DGA CH4 VALUE - Y PHASE AI DCH4
30 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H6 VALUE - Y PHASE AI C2H6
31 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H4 VALUE - Y PHASE AI C2H4
32 ABC BUS REACTOR/ LINE REACTOR RE DGA O2 VALUE - Y PHASE AI DGO2
33 ABC BUS REACTOR/ LINE REACTOR RE DGA MOISTURE VALUE - B PHASE AI MOIS
34 ABC BUS REACTOR/ LINE REACTOR RE DGA H2 VALUE - B PHASE AI DGH2
35 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H2 VALUE - B PHASE AI C2H2
36 ABC BUS REACTOR/ LINE REACTOR RE DGA CO VALUE - B PHASE AI DGCO
37 ABC BUS REACTOR/ LINE REACTOR RE DGA CO2 VALUE - B PHASE AI DCO2
38 ABC BUS REACTOR/ LINE REACTOR RE DGA CH4 VALUE - B PHASE AI DCH4
39 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H6 VALUE - B PHASE AI C2H6
40 ABC BUS REACTOR/ LINE REACTOR RE DGA C2H4 VALUE - B PHASE AI C2H4
41 ABC BUS REACTOR/ LINE REACTOR RE DGA O2 VALUE - B PHASE AI DGO2
1 ABC SPARE LINE REACTOR / BUS REACTOR RE WTI TEMP SPARE AI WTI
2 ABC SPARE LINE REACTOR / BUS REACTOR RE OTI TEMP SPARE AI OTI
3 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA MOISTURE VALUE AI MOIS
4 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA H2 VALUE AI DGH2
5 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA C2H2 VALUE AI C2H2
6 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA CO VALUE AI DGCO
7 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA CO2 VALUE AI DCO2
8 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA CH4 VALUE AI DCH4
9 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA C2H6 VALUE AI C2H6
10 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA C2H4 VALUE AI C2H4
11 ABC SPARE LINE REACTOR / BUS REACTOR RE DGA O2 VALUE AI DGO2
1 ABC TIE/ BUS COUPLER / BUS SECTION TIE/ BC/ BS I (R-PHASE) AI IR
2 ABC TIE/ BUS COUPLER / BUS SECTION TIE/ BC/ BS I (Y-PHASE) AI IY
3 ABC TIE/ BUS COUPLER / BUS SECTION TIE/ BC/ BS I (B-PHASE) AI IB
1 ABC ICT XFMR_P I (R-PHASE) AI IR
2 ABC ICT XFMR_P I (Y-PHASE) AI IY
3 ABC ICT XFMR_P I (B-PHASE) AI IB
4 ABC ICT XFMR_P MW AI MW
5 ABC ICT XFMR_P MVAR AI MX
6 ABC ICT XFMR_P V (R-Y PHASE) AI KVRY
7 ABC ICT XFMR_P V (Y-B PHASE) AI KVYB
8 ABC ICT XFMR_P V (B-R PHASE) AI KVBR
9 ABC ICT XFMR_P FREQUENCY AI HZ
10 ABC ICT XFMR_P HVWTI TEMP - R PHASE AI HVWT ONLY ONE SIGNAL IN PLACE OF THREE SIGNALS APPLICABLE INDIVIDUALLY FOR R/Y/B PHASES TO BE CONSIDERED IN CASE OF 3-PHASE ICT
11 ABC ICT XFMR_S IVWTI TEMP - R PHASE AI IVWT
12 ABC ICT XFMR_T LVWTI TEMP - R PHASE AI LVWT
13 ABC ICT XFMR_P HVWTI TEMP - Y PHASE AI HVWT
14 ABC ICT XFMR_S IVWTI TEMP - Y PHASE AI IVWT
15 ABC ICT XFMR_T LVWTI TEMP - Y PHASE AI LVWT
16 ABC ICT XFMR_P HVWTI TEMP - B PHASE AI HVWT
17 ABC ICT XFMR_S IVWTI TEMP - B PHASE AI IVWT
18 ABC ICT XFMR_T LVWTI TEMP - B PHASE AI LVWT
19 ABC ICT XFMR_P OTI TEMP R PHASE AI OTI
20 ABC ICT XFMR_P OTI TEMP Y PHASE AI OTI
21 ABC ICT XFMR_P OTI TEMP B PHASE AI OTI
22 ABC ICT XFMR_P TAP POSITION INDICATOR - R PHASE AI TPI
23 ABC ICT XFMR_P TAP POSITION INDICATOR - Y PHASE AI TPI
24 ABC ICT XFMR_P TAP POSITION INDICATOR - B PHASE AI TPI
25 ABC ICT XFMR_P DGA MOISTURE VALUE - R PHASE AI MOIS
26 ABC ICT XFMR_P DGA H2 VALUE - R PHASE AI DGH2
27 ABC ICT XFMR_P DGA C2H2 VALUE - R PHASE AI C2H2
28 ABC ICT XFMR_P DGA CO VALUE - R PHASE AI DGCO
29 ABC ICT XFMR_P DGA CO2 VALUE - R PHASE AI DCO2
30 ABC ICT XFMR_P DGA CH4 VALUE - R PHASE AI DCH4
31 ABC ICT XFMR_P DGA C2H6 VALUE - R PHASE AI C2H6
32 ABC ICT XFMR_P DGA C2H4 VALUE - R PHASE AI C2H4
33 ABC ICT XFMR_P DGA O2 VALUE - R PHASE AI DGO2
34 ABC ICT XFMR_P DGA MOISTURE VALUE - Y PHASE AI MOIS
35 ABC ICT XFMR_P DGA H2 VALUE - Y PHASE AI DGH2
36 ABC ICT XFMR_P DGA C2H2 VALUE - Y PHASE AI C2H2
37 ABC ICT XFMR_P DGA CO VALUE - Y PHASE AI DGCO
38 ABC ICT XFMR_P DGA CO2 VALUE - Y PHASE AI DCO2
39 ABC ICT XFMR_P DGA CH4 VALUE - Y PHASE AI DCH4
40 ABC ICT XFMR_P DGA C2H6 VALUE - Y PHASE AI C2H6
41 ABC ICT XFMR_P DGA C2H4 VALUE - Y PHASE AI C2H4
42 ABC ICT XFMR_P DGA O2 VALUE - Y PHASE AI DGO2
43 ABC ICT XFMR_P DGA MOISTURE VALUE - B PHASE AI MOIS
44 ABC ICT XFMR_P DGA H2 VALUE - B PHASE AI DGH2
45 ABC ICT XFMR_P DGA C2H2 VALUE - B PHASE AI C2H2
46 ABC ICT XFMR_P DGA CO VALUE - B PHASE AI DGCO
47 ABC ICT XFMR_P DGA CO2 VALUE - B PHASE AI DCO2
48 ABC ICT XFMR_P DGA CH4 VALUE - B PHASE AI DCH4
49 ABC ICT XFMR_P DGA C2H6 VALUE - B PHASE AI C2H6
50 ABC ICT XFMR_P DGA C2H4 VALUE - B PHASE AI C2H4
51 ABC ICT XFMR_P DGA O2 VALUE - B PHASE AI DGO2
1 SPARE SPARE ICT XFMR_P HVWTI - TEMP SPARE AI HVWT
2 SPARE SPARE ICT XFMR_S IVWTI - TEMP SPARE AI IVWT
3 SPARE SPARE ICT XFMR_T LVWTI - TEMP SPARE AI LVWT
4 SPARE SPARE ICT XFMR_P OTI TEMP SPARE AI OTI
5 SPARE SPARE ICT XFMR_P TAP POSITION INDICATOR AI TPI
6 SPARE SPARE ICT XFMR_P DGA MOISTURE VALUE AI MOIS
7 SPARE SPARE ICT XFMR_P DGA H2 VALUE AI DGH2
8 SPARE SPARE ICT XFMR_P DGA C2H2 VALUE AI C2H2
9 SPARE SPARE ICT XFMR_P DGA CO VALUE AI DGCO
10 SPARE SPARE ICT XFMR_P DGA CO2 VALUE AI DCO2
11 SPARE SPARE ICT XFMR_P DGA CH4 VALUE AI DCH4
12 SPARE SPARE ICT XFMR_P DGA C2H6 VALUE AI C2H6
13 SPARE SPARE ICT XFMR_P DGA C2H4 VALUE AI C2H4
14 SPARE SPARE ICT XFMR_P DGA O2 VALUE AI DGO2
1 ABC FSC FSC-X MOV TEMPERATURE R PHASE AI
2 ABC FSC FSC-X MOV TEMPERATURE Y PHASE AI
3 ABC FSC FSC-X MOV TEMPERATURE B PHASE AI
4 ABC FSC FSC-X CAPACITOR R PHASE CURRENT AI
5 ABC FSC FSC-X CAPACITOR Y PHASE CURRENT AI
6 ABC FSC FSC-X CAPACITOR B PHASE CURRENT AI
7 ABC FSC FSC-X CAPACITOR R PHASE UNBALANCED CURRENT AI
8 ABC FSC FSC-X CAPACITOR Y PHASE UNBALANCED CURRENT AI
9 ABC FSC FSC-X CAPACITOR B PHASE UNBALANCED CURRENT AI
10 ABC FSC FSC-X LINE CT CURRENT R-PH AI
11 ABC FSC FSC-X LINE CT CURRENT Y-PH AI
12 ABC FSC FSC-X LINE CT CURRENT B-PH AI
13 ABC FSC FSC-X KIOSK TEMP AI
1 220VDC DCDB 220V_DCDB-1 220V DCDB -1 VOLTAGE AI
2 220VDC DCDB 220V_DCDB-1 220V BATTERY SET-1 CURRENT AI
3 220VDC DCDB 220V_DCDB-2 220V DCDB -2 VOLTAGE AI
4 220VDC DCDB 220V_DCDB-2 220V BATTERY SET-2 CURRENT AI
5 48 VDC DCDB 48V_DCDB-1 48V DCDB -1 VOLTAGE AI
6 48 VDC DCDB 48V_DCDB-1 48V BATTERY SET-1 CURRENT AI
7 48 VDC DCDB 48V_DCDB-2 48V DCDB -2 VOLTAGE AI
8 48 VDC DCDB 48V_DCDB-2 48V BATTERY SET-2 CURRENT AI
9 220VDC BCHRG BATCHRG220V-1 220V BATTERY CHARGER-1 CURRENT AI
10 220VDC BCHRG BATCHRG220V-2 220V BATTERY CHARGER-2 CURRENT AI
11 48 VDC BCHRG BATCHRG48V-1 48V BATTERY CHARGER-1 CURRENT AI
12 48 VDC BCHRG BATCHRG48V-2 48V BATTERY CHARGER-2 CURRENT AI
13 415 V FP FIREPROTN FIRE FIGHTING PRESSURE MONITORING AI
14 415 V FP DPUMP DIESEL ENGINE BATTERY-1 VOLTAGE AI
15 415 V FP DPUMP DIESEL ENGINE BATTERY-2 VOLTAGE AI
16 415 V FP ICT FF NIS Nitrogen Cylinder Pressure AI
17 WIND SPEED AI
18 WIND DIRECTION AI
19 415 V AIRCON G_KIOSK_1 765KV KIOSK-1 TEMP AI
20 415 V AIRCON F_KIOSK_1 400KV KIOSK-1 TEMP AI
21 415 V AIRCON TEMP_MON CONTROL ROOM TEMPRATURE AI
22 415 V AIRCON TEMP_MON BATTERY ROOM TEMPRATURE AI
23 415 V AIRCON TEMP_MON AMBIENT TEMPERATURE OUTDOOR AI
24 415 V AIRCON TEMP_MON AMBIENT RELATIVE HUMIDITY OUTDOOR AI
25 415 V DG Set DGSET-1 VOLTAGE (R-Y PHASE) AI
26 415 V DG Set DGSET-1 VOLTAGE (Y-B PHASE) AI
27 415 V DG Set DGSET-1 VOLTAGE (B-R PHASE) AI
28 415 V DG Set DGSET-1 CURRENT (R-PHASE) AI
29 415 V DG Set DGSET-1 CURRENT (Y-PHASE) AI
30 415 V DG Set DGSET-1 CURRENT (B-PHASE) AI
31 415 V DG Set DGSET-1 DG SET BATTERY-1 VOLTAGE AI
32 415 V DG Set DGSET-1 DG SET BATTERY-2 VOLTAGE AI
33 415 V LTSUP MSB-1 VOLTAGE (R-Y PHASE) AI
34 415 V LTSUP MSB-1 VOLTAGE (Y-B PHASE) AI
35 415 V LTSUP MSB-1 VOLTAGE (B-R PHASE) AI
36 415 V LTSUP MSB-1 CURRENT (R-PHASE) AI
37 415 V LTSUP MSB-1 CURRENT (Y-PHASE) AI
38 415 V LTSUP MSB-1 CURRENT (B-PHASE) AI
39 415 V LTSUP MSB-2 VOLTAGE (R-Y PHASE) AI
40 415 V LTSUP MSB-2 VOLTAGE (Y-B PHASE) AI
41 415 V LTSUP MSB-2 VOLTAGE (B-R PHASE) AI
42 415 V LTSUP MSB-2 CURRENT (R-PHASE) AI
43 415 V LTSUP MSB-2 CURRENT (Y-PHASE) AI
44 415 V LTSUP MSB-2 CURRENT (B-PHASE) AI
STATCOM (SIEMENS)
1 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY HV Main Bay Voltage R-Y AI
2 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY HV Main Bay Voltage Y-B AI
3 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY HV Main Bay Voltage B-R AI
4 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY HV Main Bay Current_Phase R AI
5 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY HV Main Bay Current_Phase Y AI
6 4XX STATCOM HV SIDE MAIN BAY STATCOM HV BAY HV Main Bay Current_Phase B AI
7 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER COUPLING TRANSFORMER MVAR HV SIDE AI
8 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA CARBON DIOXIDE AI
9 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA ETHYLENE AI
10 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA ACETYLENE AI
11 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA ETHANE AI
12 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA HYDROGEN AI
13 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA OXYGEN AI
14 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA METHANE AI
15 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA CARBON MONOXIDE AI
16 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA NITROGEN AI
17 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA WATER AI
18 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-R TRANSFORMER T01_L1 DGA COMBUSTIBLE GASSES AI
19 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA CARBON DIOXIDE AI
20 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA ETHYLENE AI
21 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA ACETYLENE AI
22 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA ETHANE AI
23 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA HYDROGEN AI
24 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA OXYGEN AI
25 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA METHANE AI
26 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA CARBON MONOXIDE AI
27 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA NITROGEN AI
28 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA WATER AI
29 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-Y TRANSFORMER T01_L2 DGA COMBUSTIBLE GASSES AI
30 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA CARBON DIOXIDE AI
31 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA ETHYLENE AI
32 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA ACETYLENE AI
33 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA ETHANE AI
34 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA HYDROGEN AI
35 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA OXYGEN AI
36 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA METHANE AI
37 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA CARBON MONOXIDE AI
38 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA NITROGEN AI
39 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA WATER AI
40 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-B TRANSFORMER T01_L3 DGA COMBUSTIBLE GASSES AI
41 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA CARBON DIOXIDE AI
42 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA ETHYLENE AI
43 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA ACETYLENE AI
44 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA ETHANE AI
45 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA HYDROGEN AI
46 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA OXYGEN AI
47 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA METHANE AI
48 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA CARBON MONOXIDE AI
49 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA NITROGEN AI
50 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA WATER AI
51 4XX STATCOM HV SIDE MAIN BAY COUPLING TRANSFORMER (HV) T01-S TRANSFORMER T01_LX DGA COMBUSTIBLE GASSES AI
52 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY HV Tie Bay Current_Phase R AI
53 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY HV Tie Bay Current_Phase Y AI
54 4YY STATCOM HV SIDE TIE BAY TIE BAY 4YY HV Tie Bay Current_Phase B AI
55 STATCOM STATCOM MV BUS BAR MV BUS VOLTAGE AI
56 J11 STATCOM VSC-1 BAY VSC-1 MV-J11 STATCOM 1 MVAR AI
57 J12 STATCOM VSC-2 BAY VSC-2 MV-J12 STATCOM 2 MVAR AI
58 J21 STATCOM MSR-1 BAY MSR-1 MV-J21 MSR 1 MVAR AI
59 J22 STATCOM MSR-2 BAY MSR-2 MV-J22 MSR 2 MVAR AI
60 J31 STATCOM MSC-1 BAY MSC-1 MV-J31 MSC 1 MVAR AI
61 J32 STATCOM MSC-2 BAY MSC-2 MV-J32 MSC 2 MVAR AI
62 STATCOM STATCOM STATCOM OPERATION SLOPE AI
63 STATCOM STATCOM STATCOM OPERATION UP-SET U-REF(PU) AI
64 STATCOM STATCOM STATCOM OPERATION DN-SET U-REF(PU) AI
65 STATCOM STATCOM STATCOM OPERATION Q-SET REF(PU) AI
66 STATCOM STATCOM STATCOM OPERATION LOAD FACTOR SETPOINT AI
67 STATCOM STATCOM STATCOM OPERATION FIXED REACTIVE POWER SETPOINT(FS REF) AI
68 STATCOM STATCOM STATCOM OPERATION NPS DEADBAND SETPOINT AI
69 STATCOM STATCOM STATCOM OPERATION VQ MIN SETPOINT AI
70 STATCOM STATCOM STATCOM OPERATION VQ MAX SETPOINT AI
71 STATCOM STATCOM STATCOM OPERATION GAIN FACTOR SETPOINT AI
72 STATCOM STATCOM STATCOM OPERATION INDUCTIVE VOLTAGE SETPOINT AI
73 STATCOM STATCOM STATCOM OPERATION CAPACITIVE VOLTAGE SETPOINT AI
74 STATCOM STATCOM STATCOM OPERATION LOAD FACTOR SETPOINT AI
75 STATCOM STATCOM STATCOM OPERATION FIXED REACTIVE POWER SETPOINT(FS REF) AI
76 STATCOM STATCOM STATCOM OPERATION REACTIVE POWER SETPOINT (QREF) AI
77 STATCOM STATCOM STATCOM OPERATION NPS DEADBAND SETPOINT AI
78 STATCOM STATCOM STATCOM OPERATION VQ MIN SETPOINT AI
79 STATCOM STATCOM STATCOM OPERATION VQ MAX SETPOINT AI
80 STATCOM STATCOM STATCOM OPERATION SLOPE SETPOINT AI
81 STATCOM STATCOM STATCOM OPERATION GAIN FACTOR SETPOINT AI
478 STATCOM STATCOM STATCOM OPERATION INDUCTIVE VOLTAGE SETPOINT APC
479 STATCOM STATCOM STATCOM OPERATION CAPACITIVE VOLTAGE SETPOINT APC
480 STATCOM STATCOM STATCOM OPERATION LOAD FACTOR SETPOINT APC
481 STATCOM STATCOM STATCOM OPERATION FIXED REACTIVE POWER SETPOINT(FS REF) APC
482 STATCOM STATCOM STATCOM OPERATION REACTIVE POWER SETPOINT (QREF) APC
483 STATCOM STATCOM STATCOM OPERATION NPS DEADBAND SETPOINT APC
484 STATCOM STATCOM STATCOM OPERATION VQ MIN SETPOINT APC
485 STATCOM STATCOM STATCOM OPERATION VQ MAX SETPOINT APC
486 STATCOM STATCOM STATCOM OPERATION SLOPE SETPOINT APC
487 STATCOM STATCOM STATCOM OPERATION GAIN FACTOR SETPOINT APC
1 ABC FUTURE& COUPLING T/F-1 TIE TIE BAY CURRENT PHASE_R AI
2 ABC FUTURE& COUPLING T/F-1 TIE TIE BAY CURRENT PHASE_Y AI
3 ABC FUTURE& COUPLING T/F-1 TIE TIE BAY CURRENT PHASE_B AI
4 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI-R-PH TEMP (HV SIDE) AI
5 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -R-PHTEMP (IV SIDE) AI
6 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -R-PH TEMP (LV SIDE) AI
7 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) OTI R-PH TEMP AI
8 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) TAP POSITION INDICATION R-PH AI
9 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI-Y-PH TEMP (HV SIDE) AI
10 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -Y-PH TEMP (IV SIDE) AI
11 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -Y-PH TEMP (LV SIDE) AI
12 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) OTI Y-PH TEMP AI
13 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) TAP POSITION INDICATION Y-PH AI
14 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI-B-PH TEMP (HV SIDE) AI
15 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -B-PH TEMP (IV SIDE) AI
16 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -B-PH TEMP (LV SIDE) AI
17 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) OTI B-PH TEMP AI
18 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) TAP POSITION INDICATION B-PH AI
19 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI- SP-PH TEMP (HV SIDE) AI
20 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -SP-PH TEMP (IV SIDE) AI
21 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) WTI -SP-PH TEMP (LV SIDE) AI
22 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) OTI SP-PH TEMP AI
23 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) TAP POSITION SP-PH INDICATION AI
24 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) I (R-PHASE) AI
25 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) I (Y-PHASE) AI
26 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) I B-PHASE) AI
27 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) MVAR AI
28 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) MW AI
29 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) V (B-R PHASE) AI
30 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) V (R-Y PHASE) AI
31 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) V (Y-B PHASE) AI
32 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) FREQUENCY AI
33 ABC COUPLING TRANSFORMER STATCOM HV BAY - RPH DGA H2O INDICATION R phase AI
34 ABC COUPLING TRANSFORMER STATCOM HV BAY - RPH DGA H2 LEVEL INDICATION R phase AI
35 ABC COUPLING TRANSFORMER STATCOM HV BAY - YPH DGA H2O INDICATION Y phase AI
36 ABC COUPLING TRANSFORMER STATCOM HV BAY - YPH DGA H2 LEVEL INDICATION Y phase AI
37 ABC COUPLING TRANSFORMER STATCOM HV BAY - BPH DGA H2O INDICATION B phase AI
38 ABC COUPLING TRANSFORMER STATCOM HV BAY - BPH DGA H2 LEVEL INDICATION B phase AI
39 ABC COUPLING TRANSFORMER STATCOM HV BAY - SPARE PH DGA H2O INDICATION Spare phase AI
40 ABC COUPLING TRANSFORMER STATCOM HV BAY - SPARE PH DGA H2 LEVEL INDICATION Spare phase AI
41 38.5KV MV BUS BAR MV BUS BAR MV BUS VOLTAGE AI
42 38.5KV STATCOM- 1 VSC-1 STATCOM- 1 MVAR AI
43 38.5KV STATCOM- 2 VSC-2 STATCOM- 2 MVAR AI
44 38.5KV MSC MSC MSC MVAR AI
45 38.5KV MSR- 1 MSR-1 MSR- 1 MVAR AI
46 38.5KV MSR- 2 MSR-2 MSR- 2 MVAR AI
47 38.5KV STATCOM CONTROL STATCOM SLOPE OF INDUCTIVE POWER AI
48 38.5KV STATCOM CONTROL STATCOM SLOPE OF CAPACITIVE POWER AI
49 38.5KV STATCOM CONTROL STATCOM UP-SET U-REF(PU) AI
50 38.5KV STATCOM CONTROL STATCOM DN-SET U-REF(PU) AI
51 38.5KV STATCOM CONTROL STATCOM Q-SET REF(PU)/FS REF(PU) AI
52 415 V AUX DCDB-1 DCDB-1 VOLTAGE AI
53 415 V AUX DCDB-1 BATTERY SET-1 CURRENT AI
54 415 V AUX CHARGER-1 BATTERY CHARGER-1 CURRENT AI
55 415 V AUX DCDB-2 DCDB-2 VOLTAGE AI
56 415 V AUX DCDB-2 BATTERY SET-2 CURRENT AI
57 415 V AUX CHARGER-2 BATTERY CHARGER-2 CURRENT AI
58 415 V AUX MSB INCOMER-1 VOLTAGE R-Y AI
59 415 V AUX MSB INCOMER-1 VOLTAGE Y-B AI
60 415 V AUX MSB INCOMER-1 VOLTAGE B-R AI
61 415 V AUX MSB INCOMER-1 CURRENT R AI
62 415 V AUX MSB INCOMER-1 CURRENT Y AI
63 415 V AUX MSB INCOMER-1 CURRENT B AI
64 415 V AUX MSB INCOMER-2 VOLTAGE R-Y AI
65 415 V AUX MSB INCOMER-2 VOLTAGE Y-B AI
66 415 V AUX MSB INCOMER-2 VOLTAGE B-R AI
67 415 V AUX MSB INCOMER-2 CURRENT R AI
68 415 V AUX MSB INCOMER-2 CURRENT Y AI
69 415 V AUX MSB INCOMER-2 CURRENT B AI
70 415 V AUX AIRCON AMBIENT AMBIENT TEMPERATURE SWITCHYARD AI
71 415 V AUX AIRCON CONTROL ROOM CONTROL ROOM TEMPERATURE AI
72 415 V AUX AIRCON BATTERY ROOM BATTERY ROOM TEMPERATURE AI
73 415 V AUX AIRCON UPS ROOM UPS ROOM TEMPERATURE AI
STATCOM (HYOSUNG)
1 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY Voltage R-Y AI
2 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY Voltage Y-B AI
3 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN BAY Voltage B-R AI
4 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN + TIE Current_Phase R AI
5 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN + TIE Current_Phase Y AI
6 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) 400kV MAIN + TIE Current_Phase B AI
7 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) MVAR OF COUPLING TRANSFORMER HV SIDE AI
8 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) C2H2 AI
9 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) C2H4 AI
10 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) C2H6 AI
11 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) CH4 AI
12 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) CO2 AI
13 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) CO AI
14 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) H2O AI
15 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA R-PH) H2 AI
16 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) C2H2 AI
17 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) C2H4 AI
18 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) C2H6 AI
19 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) CH4 AI
20 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) CO2 AI
21 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) CO AI
22 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) H2O AI
23 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA Y-PH) H2 AI
24 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) C2H2 AI
25 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) C2H4 AI
26 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) C2H6 AI
27 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) CH4 AI
28 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) CO2 AI
29 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) CO AI
30 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) H2O AI
31 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA B-PH) H2 AI
32 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) C2H2 AI
33 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) C2H4 AI
34 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) C2H6 AI
35 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) CH4 AI
36 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) CO2 AI
37 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) CO AI
38 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) H2O AI
39 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (ODGA SP-PH) H2 AI
40 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) WTI-HV AI
41 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) WTI-LV AI
42 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO R-PH) OTI AI
43 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) WTI-HV AI
44 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) WTI-LV AI
45 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO Y-PH) OTI AI
46 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) WTI-HV AI
47 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) WTI-LV AI
48 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO B-PH) OTI AI
49 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) WTI-HV AI
50 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) WTI-LV AI
51 ABC COUPLING TRANSFORMER (HV) TRAFO (HV) (C. TRAFO SP-PH) OTI AI
52 20KV STATCOM-1 VSC-1 STATCOM UNIT-1 MVAR AI
53 20KV STATCOM-2 VSC-2 STATCOM UNIT-2 MVAR AI
54 20KV STATCOM CONTROL STATCOM V-REF SETTING AI
55 20KV STATCOM CONTROL STATCOM DROOP SETTING AI
56 20KV STATCOM CONTROL STATCOM DEAD-BAND UP SETTING AI
57 20KV STATCOM CONTROL STATCOM DEAD-BAND DN SETTING AI
58 20KV STATCOM CONTROL STATCOM Q-REF SETTING AI
59 20KV MV BUS BAR MV BUS BAR MV BUS VOLTAGE AI
60 20KV AUX.T/F MV AUX T/F KW AI
61 20KV AUX.T/F MV AUX T/F KVAR AI
62 33KV AUX.T/F TERTIARY KW AI
63 33KV AUX.T/F TERTIARY KVAR AI
64 415 V DCDB DCDB-1 220V DCDB-1 VOLTAGE AI
65 415 V DCDB DCDB-1 220V BATTERY SET-1 CURRENT AI
66 415 V DCDB DCDB-1 220V BATTERY CHARGER-1 CURRENT AI
67 415 V DCDB DCDB-2 220V DCDB-2 VOLTAGE AI
68 415 V DCDB DCDB-2 220V BATTERY SET-2 CURRENT AI
69 415 V DCDB DCDB-2 220V BATTERY CHARGER-2 CURRENT AI
70 415 V LTSUP MSB-1 (R-PH) INCOMER-1 VOLTAGE AI
71 415 V LTSUP MSB-1 (Y-PH) INCOMER-1 VOLTAGE AI
72 415 V LTSUP MSB-1 (B-PH) INCOMER-1 VOLTAGE AI
73 415 V LTSUP MSB-2 (R-PH) INCOMER-2 VOLTAGE AI
74 415 V LTSUP MSB-2 (Y-PH) INCOMER-2 VOLTAGE AI
75 415 V LTSUP MSB-2 (B-PH) INCOMER-2 VOLTAGE AI
76 415 V LTSUP MSB-1 (R-PH) INCOMER-1 CURRENT AI
77 415 V LTSUP MSB-1 (Y-PH) INCOMER-1 CURRENT AI
78 415 V LTSUP MSB-1 (B-PH) INCOMER-1 CURRENT AI
79 415 V LTSUP MSB-2 (R-PH) INCOMER-2 CURRENT AI
80 415 V LTSUP MSB-2 (Y-PH) INCOMER-2 CURRENT AI
81 415 V LTSUP MSB-2 (B-PH) INCOMER-2 CURRENT AI
82 415 V LTSUP DGSET (R-PH) DG FEEDER VOLTAGE AI
83 415 V LTSUP DGSET (Y-PH) DG FEEDER VOLTAGE AI
84 415 V LTSUP DGSET (B-PH) DG FEEDER VOLTAGE AI
85 415 V LTSUP DGSET (R-PH) DG FEEDER CURRENT AI
86 415 V LTSUP DGSET (Y-PH) DG FEEDER CURRENT AI
87 415 V LTSUP DGSET (B-PH) DG FEEDER CURRENT AI
88 20KV MSR-1 MSR MSR-1 MVAR AI
89 20KV MSR-2 MSR MSR-2 MVAR AI
90 20KV MSC MSC MSC MVAR AI
91 20KV STATCOM-1 STATCOM CONTROLLER A CONTROL MODE : MANUAL Q CONTROL / AUTOMATIC VOLTAGE APC 1 : Manual Q / 5 : Automatic Voltage
92 20KV STATCOM-1 STATCOM CONTROLLER A V-REF SETTING APC
93 20KV STATCOM-1 STATCOM CONTROLLER A DEAD-BAND UP SETTING APC
94 20KV STATCOM-1 STATCOM CONTROLLER A DEAD-BAND DN SETTING APC
95 20KV STATCOM-1 STATCOM CONTROLLER A DROOP SETTING APC
96 20KV STATCOM-1 STATCOM CONTROLLER A Q-REF SETTING APC
97 20KV STATCOM-1 STATCOM CONTROLLER A POD CONTROL ENABLE APC 1 : Manual Q / 5 : Automatic Voltage
98 20KV STATCOM-1 STATCOM CONTROLLER A SSOD CONTROL ENABLE APC 1 : Manual Q / 5 : Automatic Voltage
99 20KV STATCOM-1 STATCOM CONTROLLER A ADACTIVE GAIN REDUCTION ENABLE APC 1 : Manual Q / 5 : Automatic Voltage
100 20KV STATCOM-1 STATCOM CONTROLLER A ADACTIVE GAIN CLACULATION ENABLE APC 1 : Manual Q / 5 : Automatic Voltage
101 20KV STATCOM-1 STATCOM CONTROLLER A NEGATIVE SEQ. VOLTAGE CONTROL ENABLE APC 1 : Manual Q / 5 : Automatic Voltage
102 20KV STATCOM-1 STATCOM CONTROLLER A MSC CONTROL MODE - AUTOMATIC / MANUAL APC 1 : Manual Q / 5 : Automatic Voltage
103 20KV STATCOM-1 STATCOM CONTROLLER A MSR-1 CONTROL MODE - AUTOMATIC / MANUAL APC 1 : Manual Q / 5 : Automatic Voltage
104 20KV STATCOM-1 STATCOM CONTROLLER A MSR-2 CONTROL MODE - AUTOMATIC / MANUAL APC 1 : Manual Q / 5 : Automatic Voltage
105 20KV STATCOM-1 STATCOM CONTROLLER A HV BR MAIN BAY CONTROL MODE - AUTOMATIC (HYD ONLY) APC 1 : Manual Q / 5 : Automatic Voltage
106 20KV STATCOM-1 STATCOM CONTROLLER A HV BR TIE BAY CONTROL MODE - AUTOMATIC (HYD ONLY) APC 1 : Manual Q / 5 : Automatic Voltage
107 20KV STATCOM-2 STATCOM CONTROLLER B CONTROL MODE : MANUAL Q CONTROL / AUTOMATIC VOLTAGE APC 1 : Manual Q / 5 : Automatic Voltage
108 20KV STATCOM-2 STATCOM CONTROLLER B V-REF SETTING APC
109 20KV STATCOM-2 STATCOM CONTROLLER B DEAD-BAND UP SETTING APC
110 20KV STATCOM-2 STATCOM CONTROLLER B DEAD-BAND DN SETTING APC
111 20KV STATCOM-2 STATCOM CONTROLLER B DROOP SETTING APC
112 20KV STATCOM-2 STATCOM CONTROLLER B Q-REF SETTING APC
113 20KV STATCOM-2 STATCOM CONTROLLER B POD CONTROL ENABLE APC 1 : Manual Q / 5 : Automatic Voltage
114 20KV STATCOM-2 STATCOM CONTROLLER B SSOD CONTROL ENABLE APC 1 : Manual Q / 5 : Automatic Voltage
115 20KV STATCOM-2 STATCOM CONTROLLER B ADACTIVE GAIN REDUCTION ENABLE APC 1 : Manual Q / 5 : Automatic Voltage
116 20KV STATCOM-2 STATCOM CONTROLLER B ADACTIVE GAIN CLACULATION ENABLE APC 1 : Manual Q / 5 : Automatic Voltage
117 20KV STATCOM-2 STATCOM CONTROLLER B NEGATIVE SEQ. VOLTAGE CONTROL ENABLE APC 1 : Manual Q / 5 : Automatic Voltage
118 20KV STATCOM-2 STATCOM CONTROLLER B MSC CONTROL MODE - AUTOMATIC / MANUAL APC 1 : Manual Q / 5 : Automatic Voltage
119 20KV STATCOM-2 STATCOM CONTROLLER B MSR-1 CONTROL MODE - AUTOMATIC / MANUAL APC 1 : Manual Q / 5 : Automatic Voltage
120 20KV STATCOM-2 STATCOM CONTROLLER B MSR-2 CONTROL MODE - AUTOMATIC / MANUAL APC 1 : Manual Q / 5 : Automatic Voltage
121 20KV STATCOM-2 STATCOM CONTROLLER B HV BR MAIN BAY CONTROL MODE - AUTOMATIC / MANUAL (HYD ONLY) APC 1 : Manual Q / 5 : Automatic Voltage
122 20KV STATCOM-2 STATCOM CONTROLLER B HV BR TIE BAY CONTROL MODE - AUTOMATIC / MANUAL (HYD ONLY) APC 1 : Manual Q / 5 : Automatic Voltage
S. No. VOLT. LEVEL BAY NAME BAY NUM. FEEDER TYPE DEVICE IDENTIFICATION POINT DESCRIPTION DATA TYPE IEC 104 ADDRESS REMARK
1 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB OPEN/CLOSE STATUS DPS
3 …KV XXXXXX BAY NO FSC BAY NO-52BBR-RPh BPCB R PHASE OPEN/CLOSE STATUS DPS
5 …KV XXXXXX BAY NO FSC BAY NO-52BBR-YPh BPCB Y PHASE OPEN/CLOSE STATUS DPS
7 …KV XXXXXX BAY NO FSC BAY NO-52BBR-Bph BPCB B PHASE OPEN/CLOSE STATUS DPS
9 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS ISOLATOR OPEN/CLOSE STATUS DPS
10 …KV XXXXXX BAY NO FSC BAY NO-89DS1 ISOLATOR 1 OPEN/CLOSE STATUS DPS
11 …KV XXXXXX BAY NO FSC BAY NO-89DS2 ISOLATOR 2 OPEN/CLOSE STATUS DPS
12 …KV XXXXXX BAY NO FSC BAY NO-89ES1 EARTH SWITCH 1 OPERATION INTERLOCK SPS
13 …KV XXXXXX BAY NO FSC BAY NO-89ES2 EARTH SWITCH 2 OPERATION INTERLOCK SPS
14 …KV XXXXXX BAY NO FSC BAY NO-89ES1 EARTH SWITCH 1 OPEN/CLOSE STATUS DPS
15 …KV XXXXXX BAY NO FSC BAY NO-89ES2 EARTH SWITCH 2 OPEN/CLOSE STATUS DPS
16 …KV XXXXXX BAY NO FSC BAY NO LINE DE-ENRGIZED SPS
17 …KV XXXXXX BAY NO FSC BAY NO FAULT TO PLATFORM TRIP-1/2 SPS
18 …KV XXXXXX BAY NO FSC BAY NO PERMANENT BYPASS SPS
19 …KV XXXXXX BAY NO FSC BAY NO MOV TEMPERATURE R PHASE AI
20 …KV XXXXXX BAY NO FSC BAY NO MOV TEMPERATURE Y PHASE AI
21 …KV XXXXXX BAY NO FSC BAY NO MOV TEMPERATURE B PHASE AI
22 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR R PHASE CURRENT AI
23 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR Y PHASE CURRENT AI
24 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR B PHASE CURRENT AI
25 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR R PHASE UNBALANCED CURRENT AI
26 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR Y PHASE UNBALANCED CURRENT AI
27 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR B PHASE UNBALANCED CURRENT AI
28 …KV XXXXXX BAY NO FSC BAY NO LINE CT CURRENT R-PH AI
29 …KV XXXXXX BAY NO FSC BAY NO LINE CT CURRENT Y-PH AI
30 …KV XXXXXX BAY NO FSC BAY NO LINE CT CURRENT B-PH AI
31 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB STATUS DISCREPANCY SPS
32 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB AUX CONTACT DISCORDANCE SPS
33 …KV XXXXXX BAY NO FSC BAY NO-52BBR GENRAL LOCKOUT/MIN OIL PRESSURE LOCKOUT SPS
34 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB POLE DISCREPANCY SPS
35 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB DC 1/2 FAIL SPS
36 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB LOSS OF SF6 SPS
37 …KV XXXXXX BAY NO FSC BAY NO-52BBR 1POLE REINSERTION DURING AR SPS
38 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER FAIL TO OPEN SPS COMMON- R-PH,Y-PH,B-PH FAIL TO OPEN
39 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER SWITCHWED WITHOUT COMMAND SPS
40 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER FAIL TO CLOSE SPS COMMON- R-PH,Y-PH,B-PH FAIL TO CLOSE
41 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS CB SPRING DISCHARGE/FAILURE SPS
42 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB OPEN CMD DPC
43 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB CLOSE CMD DPC
44 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB OPERATION INTERLOCK SPS
45 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS OPEN CMD DPC
46 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS CLOSE CMD DPC
47 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS OPERATION INTERLOCK SPS
48 …KV XXXXXX BAY NO FSC BAY NO-89DS1 BYPASS CAP ISO 1 OPEN CMD DPC
49 …KV XXXXXX BAY NO FSC BAY NO-89DS1 BYPASS CAP ISO 1 CLOSE CMD DPC
50 …KV XXXXXX BAY NO FSC BAY NO-89DS1 BYPASS CAP ISO 1 OPERATION INTERLOCK SPS
51 …KV XXXXXX BAY NO FSC BAY NO-89DS2 BYPASS CAP ISO 2 OPEN CMD DPC
52 …KV XXXXXX BAY NO FSC BAY NO-89DS2 BYPASS CAP ISO 2 CLOSE CMD DPC
53 …KV XXXXXX BAY NO FSC BAY NO-89DS1 DISCONNECTOR 1 PHASE DISAGREEMENT SPS
54 …KV XXXXXX BAY NO FSC BAY NO-89DS1 GENERAL ALARM SPS
55 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS DISCONNECTOR ALARM SPS
56 …KV XXXXXX BAY NO FSC BAY NO-89DS2 DISCONNECTOR 2 PHASE DISAGREEMENT SPS
57 …KV XXXXXX BAY NO FSC BAY NO-89DS2 GENERAL ALARM SPS
58 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR UNBALANCE ALARM SPS
59 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR UNBALANCED TRIP SPS FOR BOTH HIGH SET AND LOW SET (IF AVAILABLE)
60 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR OVERLOAD ALARM SPS
61 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR OVERLOAD TRIP SPS
62 …KV XXXXXX BAY NO FSC BAY NO-MOV MOV TRIP SPS
63 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM FAIL-1 SPS
64 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM FAIL-2 SPS
65 …KV XXXXXX BAY NO FSC BAY NO-PROT SIGNAL TRANSMISSION POWER FAIL SPS
66 …KV XXXXXX BAY NO FSC BAY NO-PROT MASTER TRIP SPS
67 …KV XXXXXX BAY NO FSC BAY NO-PROT GPS TIME SYNC FAIL SPS
68 …KV XXXXXX BAY NO FSC BAY NO-PROT DIRECT TRIP RECEIVE SPS
69 …KV XXXXXX BAY NO FSC BAY NO-PROT COMMUNICATION CHANNEL FAIL SPS
70 …KV XXXXXX BAY NO FSC BAY NO-89DS2 BYPASS CAP ISO 2 OPERATION INTERLOCK SPS
71 …KV XXXXXX BAY NO FSC BAY NO-PROT MASTER TRIP RST SPC
72 …KV XXXXXX BAY NO FSC BAY NO-PROT MOV FAIL SPS COMMON- R-PH,Y-PH,B-PH
73 …KV XXXXXX BAY NO FSC BAY NO-PROT KIOSK TEMP AI
74 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL SYSTEM 1 HARDWARE ALARM SPS Group Alarm
75 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 1 HARDWARE ALARM SPS Group Alarm
76 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM 1 COMMUNICATION FAULT SPS Group Alarm
77 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 1 MEASURING SYSTEM WARNING SPS Group Alarm
78 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL SYSTEM 2 HARDWARE ALARM SPS Group Alarm
79 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 2 HARDWARE ALARM SPS Group Alarm
80 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM 2 COMMUNICATION FAULT SPS Group Alarm
81 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 2 MEASURING SYSTEM WARNING SPS Group Alarm
82 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM POWER SUPPLY ALARM SPS Group Alarm
83 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM REDUNDANCY DISTURBED SPS Group Alarm
84 …KV XXXXXX BAY NO FSC BAY NO-PROT EARTH SWITCH 1 ALARM SPS Group Alarm
85 …KV XXXXXX BAY NO FSC BAY NO-PROT EARTH SWITCH 2 ALARM SPS Group Alarm
86 …KV XXXXXX BAY NO FSC BAY NO-PROT DISCONNECTOR SWITCH 1 ALARM SPS Group Alarm
87 …KV XXXXXX BAY NO FSC BAY NO-PROT DISCONNECTOR SWITCH 2 ALARM SPS Group Alarm
88 …KV XXXXXX BAY NO FSC BAY NO-PROT LINE EARTH SWITCH ALARM SPS Group Alarm
89 …KV XXXXXX BAY NO FSC BAY NO-PROT BYPASS BREAKER ALARM SPS Group Alarm
90 …KV XXXXXX BAY NO FSC BAY NO-PROT MAIN BYPASS SWITCH ALARM SPS Group Alarm
91 …KV XXXXXX BAY NO FSC BAY NO-PROT LINE SIDE 1: DE-ENERGIZED SPS
92 …KV XXXXXX BAY NO FSC BAY NO-PROT LINE SIDE 2: DE-ENERGIZED SPS
93 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER LOCAL/REMOTE CONTROL SPS
94 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER MAIN CLOSING COIL UNHEALTHY SPS
95 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER BACKUP CLOSING COIL UNHEALTHY SPS
96 …KV XXXXXX BAY NO FSC BAY NO-PROT FIRE FIGHTING SYSTEM: ALARM SPS
97 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV OVERLOAD SPS
98 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV TEMPERATURE TRIP SPS
99 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV TEMPERATURE GRADIENT LOW SET SPS
100 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV TEMPERATURE GRADIENT HIGH SET SPS
101 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV UNBALANCE SPS
102 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV HIGH CURRENT SPS
103 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP FAILED TO TRIGGER SPS
104 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP DELAYED TRIGGER SPS
105 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP PROLONGED CONDUCTION SPS
106 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP SELF TRIGGER SPS
107 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP TRIGGER (R,Y,B) SPS R,Y,B Phase to be combined
108 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: BYPASS BREAKER FAIL SPS
109 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: PREVENT REINSERTION ACTIVE SPS
110 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: PERMANENT BYPASS SPS
111 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: TEMPORARY BYPASS PHASE(R,Y,B) SPS R,Y,B Phase to be combined
112 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: REINSERTION SPS
113 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: LINE TRIP SPS
114 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV OVERLOAD SPS
115 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV TEMPERATURE TRIP SPS
116 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV TEMPERATURE GRADIENT LOW SET SPS
117 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV TEMPERATURE GRADIENT HIGH SET SPS
118 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV UNBALANCE SPS
119 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV HIGH CURRENT SPS
120 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP FAILED TO TRIGGER SPS
121 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP DELAYED TRIGGER SPS
122 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP PROLONGED CONDUCTION SPS
123 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP SELF TRIGGER SPS
124 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP TRIGGER (R,Y,B) SPS R,Y,B Phase to be combined
125 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: BYPASS BREAKER FAIL SPS
126 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: PREVENT REINSERTION ACTIVE SPS
127 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: PERMANENT BYPASS SPS
128 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: TEMPORARY BYPASS PHASE(R,Y,B) SPS R,Y,B Phase to be combined
129 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: REINSERTION SPS
130 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: LINE TRIP SPS
S. No. VOLT. LEVEL BAY NAME BAY NUM. FEEDER TYPE DEVICE IDENTIFICATION POINT DESCRIPTION DATA TYPE IEC 104 ADDRESS REMARK
1 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB OPEN/CLOSE STATUS DPS
3 …KV XXXXXX BAY NO FSC BAY NO-52BBR-RPh BPCB R PHASE OPEN/CLOSE STATUS DPS
5 …KV XXXXXX BAY NO FSC BAY NO-52BBR-YPh BPCB Y PHASE OPEN/CLOSE STATUS DPS
7 …KV XXXXXX BAY NO FSC BAY NO-52BBR-Bph BPCB B PHASE OPEN/CLOSE STATUS DPS
9 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS ISOLATOR OPEN/CLOSE STATUS DPS
10 …KV XXXXXX BAY NO FSC BAY NO-89DS1 ISOLATOR 1 OPEN/CLOSE STATUS DPS
11 …KV XXXXXX BAY NO FSC BAY NO-89DS2 ISOLATOR 2 OPEN/CLOSE STATUS DPS
12 …KV XXXXXX BAY NO FSC BAY NO-89ES1 EARTH SWITCH 1 OPERATION INTERLOCK SPS
13 …KV XXXXXX BAY NO FSC BAY NO-89ES2 EARTH SWITCH 2 OPERATION INTERLOCK SPS
14 …KV XXXXXX BAY NO FSC BAY NO-89ES1 EARTH SWITCH 1 OPEN/CLOSE STATUS DPS
15 …KV XXXXXX BAY NO FSC BAY NO-89ES2 EARTH SWITCH 2 OPEN/CLOSE STATUS DPS
16 …KV XXXXXX BAY NO FSC BAY NO LINE DE-ENRGIZED SPS
17 …KV XXXXXX BAY NO FSC BAY NO FAULT TO PLATFORM TRIP-1/2 SPS
18 …KV XXXXXX BAY NO FSC BAY NO PERMANENT BYPASS SPS
19 …KV XXXXXX BAY NO FSC BAY NO MOV TEMPERATURE R PHASE AI
20 …KV XXXXXX BAY NO FSC BAY NO MOV TEMPERATURE Y PHASE AI
21 …KV XXXXXX BAY NO FSC BAY NO MOV TEMPERATURE B PHASE AI
22 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR R PHASE CURRENT AI
23 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR Y PHASE CURRENT AI
24 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR B PHASE CURRENT AI
25 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR R PHASE UNBALANCED CURRENT AI
26 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR Y PHASE UNBALANCED CURRENT AI
27 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR B PHASE UNBALANCED CURRENT AI
28 …KV XXXXXX BAY NO FSC BAY NO LINE CT CURRENT R-PH AI
29 …KV XXXXXX BAY NO FSC BAY NO LINE CT CURRENT Y-PH AI
30 …KV XXXXXX BAY NO FSC BAY NO LINE CT CURRENT B-PH AI
31 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB STATUS DISCREPANCY SPS
32 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB AUX CONTACT DISCORDANCE SPS
33 …KV XXXXXX BAY NO FSC BAY NO-52BBR GENRAL LOCKOUT/MIN OIL PRESSURE LOCKOUT SPS
34 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB POLE DISCREPANCY SPS
35 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB DC 1/2 FAIL SPS
36 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB LOSS OF SF6 SPS
37 …KV XXXXXX BAY NO FSC BAY NO-52BBR 1POLE REINSERTION DURING AR SPS
38 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER FAIL TO OPEN SPS COMMON- R-PH,Y-PH,B-PH FAIL TO OPEN
39 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER SWITCHWED WITHOUT COMMAND SPS
40 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER FAIL TO CLOSE SPS COMMON- R-PH,Y-PH,B-PH FAIL TO CLOSE
41 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS CB SPRING DISCHARGE/FAILURE SPS
42 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB OPEN CMD DPC
43 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB CLOSE CMD DPC
44 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB OPERATION INTERLOCK SPS
45 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS OPEN CMD DPC
46 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS CLOSE CMD DPC
47 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS OPERATION INTERLOCK SPS
48 …KV XXXXXX BAY NO FSC BAY NO-89DS1 BYPASS CAP ISO 1 OPEN CMD DPC
49 …KV XXXXXX BAY NO FSC BAY NO-89DS1 BYPASS CAP ISO 1 CLOSE CMD DPC
50 …KV XXXXXX BAY NO FSC BAY NO-89DS1 BYPASS CAP ISO 1 OPERATION INTERLOCK SPS
51 …KV XXXXXX BAY NO FSC BAY NO-89DS2 BYPASS CAP ISO 2 OPEN CMD DPC
52 …KV XXXXXX BAY NO FSC BAY NO-89DS2 BYPASS CAP ISO 2 CLOSE CMD DPC
53 …KV XXXXXX BAY NO FSC BAY NO-89DS1 DISCONNECTOR 1 PHASE DISAGREEMENT SPS
54 …KV XXXXXX BAY NO FSC BAY NO-89DS1 GENERAL ALARM SPS
55 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS DISCONNECTOR ALARM SPS
56 …KV XXXXXX BAY NO FSC BAY NO-89DS2 DISCONNECTOR 2 PHASE DISAGREEMENT SPS
57 …KV XXXXXX BAY NO FSC BAY NO-89DS2 GENERAL ALARM SPS
58 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR UNBALANCE ALARM SPS
59 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR UNBALANCED TRIP SPS FOR BOTH HIGH SET AND LOW SET (IF AVAILABLE)
60 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR OVERLOAD ALARM SPS
61 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR OVERLOAD TRIP SPS
62 …KV XXXXXX BAY NO FSC BAY NO-MOV MOV TRIP SPS
63 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM FAIL-1 SPS
64 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM FAIL-2 SPS
65 …KV XXXXXX BAY NO FSC BAY NO-PROT SIGNAL TRANSMISSION POWER FAIL SPS
66 …KV XXXXXX BAY NO FSC BAY NO-PROT MASTER TRIP SPS
67 …KV XXXXXX BAY NO FSC BAY NO-PROT GPS TIME SYNC FAIL SPS
68 …KV XXXXXX BAY NO FSC BAY NO-PROT DIRECT TRIP RECEIVE SPS
69 …KV XXXXXX BAY NO FSC BAY NO-PROT COMMUNICATION CHANNEL FAIL SPS
70 …KV XXXXXX BAY NO FSC BAY NO-89DS2 BYPASS CAP ISO 2 OPERATION INTERLOCK SPS
71 …KV XXXXXX BAY NO FSC BAY NO-PROT MASTER TRIP RST SPC
72 …KV XXXXXX BAY NO FSC BAY NO-PROT MOV FAIL SPS COMMON- R-PH,Y-PH,B-PH
73 …KV XXXXXX BAY NO FSC BAY NO-PROT KIOSK TEMP AI
74 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL SYSTEM 1 HARDWARE ALARM SPS Group Alarm
75 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 1 HARDWARE ALARM SPS Group Alarm
76 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM 1 COMMUNICATION FAULT SPS Group Alarm
77 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 1 MEASURING SYSTEM WARNING SPS Group Alarm
78 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL SYSTEM 2 HARDWARE ALARM SPS Group Alarm
79 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 2 HARDWARE ALARM SPS Group Alarm
80 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM 2 COMMUNICATION FAULT SPS Group Alarm
81 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 2 MEASURING SYSTEM WARNING SPS Group Alarm
82 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM POWER SUPPLY ALARM SPS Group Alarm
83 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM REDUNDANCY DISTURBED SPS Group Alarm
84 …KV XXXXXX BAY NO FSC BAY NO-PROT EARTH SWITCH 1 ALARM SPS Group Alarm
85 …KV XXXXXX BAY NO FSC BAY NO-PROT EARTH SWITCH 2 ALARM SPS Group Alarm
86 …KV XXXXXX BAY NO FSC BAY NO-PROT DISCONNECTOR SWITCH 1 ALARM SPS Group Alarm
87 …KV XXXXXX BAY NO FSC BAY NO-PROT DISCONNECTOR SWITCH 2 ALARM SPS Group Alarm
88 …KV XXXXXX BAY NO FSC BAY NO-PROT LINE EARTH SWITCH ALARM SPS Group Alarm
89 …KV XXXXXX BAY NO FSC BAY NO-PROT BYPASS BREAKER ALARM SPS Group Alarm
90 …KV XXXXXX BAY NO FSC BAY NO-PROT MAIN BYPASS SWITCH ALARM SPS Group Alarm
91 …KV XXXXXX BAY NO FSC BAY NO-PROT LINE SIDE 1: DE-ENERGIZED SPS
92 …KV XXXXXX BAY NO FSC BAY NO-PROT LINE SIDE 2: DE-ENERGIZED SPS
93 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER LOCAL/REMOTE CONTROL SPS
94 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER MAIN CLOSING COIL UNHEALTHY SPS
95 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER BACKUP CLOSING COIL UNHEALTHY SPS
96 …KV XXXXXX BAY NO FSC BAY NO-PROT FIRE FIGHTING SYSTEM: ALARM SPS
97 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV OVERLOAD SPS
98 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV TEMPERATURE TRIP SPS
99 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV TEMPERATURE GRADIENT LOW SET SPS
100 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV TEMPERATURE GRADIENT HIGH SET SPS
101 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV UNBALANCE SPS
102 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV HIGH CURRENT SPS
103 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP FAILED TO TRIGGER SPS
104 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP DELAYED TRIGGER SPS
105 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP PROLONGED CONDUCTION SPS
106 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP SELF TRIGGER SPS
107 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP TRIGGER (R,Y,B) SPS R,Y,B Phase to be combined
108 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: BYPASS BREAKER FAIL SPS
109 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: PREVENT REINSERTION ACTIVE SPS
110 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: PERMANENT BYPASS SPS
111 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: TEMPORARY BYPASS PHASE(R,Y,B) SPS R,Y,B Phase to be combined
112 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: REINSERTION SPS
113 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: LINE TRIP SPS
114 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV OVERLOAD SPS
115 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV TEMPERATURE TRIP SPS
116 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV TEMPERATURE GRADIENT LOW SET SPS
117 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV TEMPERATURE GRADIENT HIGH SET SPS
118 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV UNBALANCE SPS
119 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV HIGH CURRENT SPS
120 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP FAILED TO TRIGGER SPS
121 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP DELAYED TRIGGER SPS
122 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP PROLONGED CONDUCTION SPS
123 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP SELF TRIGGER SPS
124 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP TRIGGER (R,Y,B) SPS R,Y,B Phase to be combined
125 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: BYPASS BREAKER FAIL SPS
126 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: PREVENT REINSERTION ACTIVE SPS
127 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: PERMANENT BYPASS SPS
128 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: TEMPORARY BYPASS PHASE(R,Y,B) SPS R,Y,B Phase to be combined
129 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: REINSERTION SPS
130 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: LINE TRIP SPS
NTAMC TYPICAL SIGNALS FOR FSC
FSC PROTECTION SIGNALS BYPASS CB SIGNALS
S.No SIGNAL NAME TYPE S.No SIGNAL NAME TYPE
1 SYSTEM 1: MOV OVERLOAD SPS 1 BPCB STATUS DISCREPANCY SPS
2 SYSTEM 1: MOV TEMPERATURE TRIP SPS 2 BPCB AUX CONTACT DISCORDANCE SPS
3 SYSTEM 1: MOV TEMPERATURE GRADIENT LOW SET SPS 3 GENRAL LOCKOUT/MIN OIL PRESSURE LOCKOUT SPS
4 SYSTEM 1: MOV TEMPERATURE GRADIENT HIGH SET SPS 4 BPCB POLE DISCREPANCY SPS
5 SYSTEM 1: MOV UNBALANCE SPS 5 BPCB DC 1/2 FAIL SPS
6 SYSTEM 1: MOV HIGH CURRENT SPS 6 BPCB LOSS OF SF6 SPS
7 SYSTEM 1: SPARK GAP FAILED TO TRIGGER SPS 7 1 POLE REINSERTION DURING AR SPS
8 SYSTEM 1: SPARK GAP DELAYED TRIGGER SPS 8 BYPASS BREAKER FAIL TO OPEN SPS
9 SYSTEM 1: SPARK GAP PROLONGED CONDUCTION SPS 9 BYPASS BREAKER SWITCHWED WITHOUT COMMAND SPS
10 SYSTEM 1: SPARK GAP SELF TRIGGER SPS 10 BYPASS BREAKER FAIL TO CLOSE SPS
11 SYSTEM 1: SPARK GAP TRIGGER (R,Y,B) SPS 11 BYPASS CB SPRING DISCHARGE/FAILURE SPS
12 SYSTEM 1: BYPASS BREAKER FAIL SPS 12 BYPASS BREAKER LOCAL/REMOTE CONTROL SPS
13 SYSTEM 1: PREVENT REINSERTION ACTIVE SPS 13 BYPASS BREAKER MAIN CLOSING COIL UNHEALTHY SPS
14 SYSTEM 1: PERMANENT BYPASS SPS 14 BYPASS BREAKER BACKUP CLOSING COIL UNHEALTHY SPS
15 SYSTEM 1: TEMPORARY BYPASS PHASE(R,Y,B) SPS NOTE- 1)CB Status, Command and Interlock are also required
16 SYSTEM 1: REINSERTION SPS
17 SYSTEM 1: LINE TRIP SPS
18 SYSTEM 1: BYPASS PLATFORM PROTECTION SPS ISOLATOR SIGNALS
19 SYSTEM 1: BYPASS GAP PROTECTION SPS S.No SIGNAL NAME TYPE
20 SYSTEM 1: CAPACITOR UNBALANCE ALARM SPS 1 DS-DISCONNECTOR 1 PHASE DISAGREEMENT SPS
21 SYSTEM 1: CAPACITOR UNBALANCED TRIP SPS 2 DS-GENERAL ALARM SPS
22 SYSTEM 1: CAPACITOR OVERLOAD ALARM SPS 3 MBS-BYPASS DISCONNECTOR ALARM SPS
23 SYSTEM 1: CAPACITOR OVERLOAD TRIP SPS NOTE- 1)Isolator Status, Command and Interlock are also required
24 SYSTEM 1: MOV TRIP SPS
25 SYSTEM 1: FAULT TO PLATFORM TRIP-1/2 SPS
26 SYSTEM 1: DC SUPPLY FAIL SPS
27 SYSTEM1: EXTERNAL BYPASS SPS EARTH SWITCH SIGNALS
28 LINE DE-ENRGIZED SPS S.No SIGNAL NAME TYPE
29 PROTECTION SYSTEM FAIL/BLOCKED-1 SPS 1 EARTH SWITCH 1 ALARM SPS
30 PROTECTION SYSTEM FAIL/BLOCKED-2 SPS NOTE- 1)Earth Switch Status and Interlock are also required
31 SIGNAL TRANSMISSION POWER FAIL SPS
32 MASTER TRIP SPS
33 DIRECT TRIP RECEIVE SPS ANALOG SIGNALS
34 COMMUNICATION CHANNEL FAIL SPS S.No SIGNAL NAME TYPE
35 MOV FAIL SPS 1 MOV TEMPERATURE R PHASE AI
36 GPS TIME SYNC FAIL SPS 2 MOV TEMPERATURE Y PHASE AI
37 CONTROL SYSTEM 1 HARDWARE ALARM SPS 3 MOV TEMPERATURE B PHASE AI
38 PROTECTION SYSTEM 1 HARDWARE ALARM SPS 4 CAPACITOR R PHASE CURRENT AI
39 CONTROL & PROTECTION SYSTEM 1 COMMUNICATION FAULT SPS 5 CAPACITOR Y PHASE CURRENT AI
40 PROTECTION SYSTEM 1 MEASURING SYSTEM WARNING SPS 6 CAPACITOR B PHASE CURRENT AI
41 CONTROL & PROTECTION SYSTEM POWER SUPPLY ALARM SPS 7 CAPACITOR R PHASE UNBALANCED CURRENT AI
42 CONTROL & PROTECTION SYSTEM REDUNDANCY DISTURBED SPS 8 CAPACITOR Y PHASE UNBALANCED CURRENT AI
43 LINE SIDE 1: DE-ENERGIZED SPS 9 CAPACITOR B PHASE UNBALANCED CURRENT AI
44 LINE SIDE 2: DE-ENERGIZED SPS 10 LINE CT CURRENT R-PH AI
45 FIRE FIGHTING SYSTEM: ALARM SPS 11 LINE CT CURRENT Y-PH AI
46 PROTECTION SYSTEM 1 MEASURING SYSTEM WARNING SPS 12 LINE CT CURRENT B-PH AI
47 LOCAL CONTROL ROOM TEMPERATURE ALARM SPS 13 KIOSK TEMP AI
48 TFR FAULT SPS 14 MOV CURRENT R PHASE AI
49 PERMANENT /MONITORING LOCKOUT DUE TO C&P SYSTEM SPS 15 MOV CURRENT Y PHASE AI
NOTE- 1)S.No. 1-27 to be taken for SYSTEM-2 also 2) S.No. 37-40 to be taken for Control and Protection System-2 also 16 MOV CURRENT B PHASE AI
17 MOV BRANCH CURRENT R PHASE AI
18 MOV BRANCH CURRENT Y PHASE AI
19 MOV BRANCH CURRENT B PHASE AI
20 SPARK GAP CURRENT R PHASE AI
21 SPARK GAP CURRENT Y PHASE AI
22 SPARK GAP CURRENT B PHASE AI
23 PLATFORM CURRENT R PHASE AI
24 PLATFORM CURRENT Y PHASE AI
25 PLATFORM CURRENT B PHASE AI
NOTE- If any other signal is required for remote operation as per site condition, it needs to be incorporated in final signal list.
NTAMC SIGNALS FOR HVDC SUBSTATION
BIPOLE BACK TO BACK VSC
S.No SIGNAL NAME TYPE S.No SIGNAL NAME TYPE SL. No. SIGNAL NAME TYPE
1 POLE-1 DC POWER AI 1 POLE-1 DC POWER AI 1 SM-1 DC POWER AI
2 POLE-1 DC VOLTAGE AI 2 POLE-1 DC VOLTAGE AI 2 SM-1 DC LINE VOLTAGE AI
3 POLE-1 DC CURRENT AI 3 POLE-1 DC CURRENT AI 3 SM-1 DC CURRENT AI
4 POLE-1 FIRING/EXTINCTION ANGLE AI 4 POLE-1 FIRING/EXTINCTION ANGLE AI 4 SM 1 ACTIVE POWER AI
5 POLE-1 GROUND/METALLIC RETURN SPS 5 POLE-1 BLOCKED/DEBLOCKED SPS 5 SM-1 REACTIVE POWER AI
6 POLE-1 POWER DIRECTION POWER FLOW DIRECTION NORMAL/REVERSE SPS 6 POLE 1 VBE/VCU SUMMARY FAULT SPS 6 SM-1 ACTIVE POWER CAPABILITY AI
7 POLE-1 BLOCKED/DEBLOCKED SPS 7 POLE 1 VALVE HALL SUMMARY TRIP SPS 7 SM-1 RECATIVE POWER CAPABILITY AI
8 POLE-1 OVERLOAD IN USE SPS 8 POLE-1 CONVERTER TRANSFORMER SUMMARY FAULT SPS 8 SM-1 POWER FLOW DIRECTION FORWARD/REVERSE SPS
9 POLE-1 POWER RAMP IN PROGRESS SPS 9 POLE-1 VALVE COOLING SYSTEM FAULT SPS 9 SM-1 COUPLED SPS
10 POLE-1 DC VOLTAGE FULL/REDUCED SPS 10 POLE-1 VALVE COOLING TRIP SPS 10 SM-1 DECOUPLED SPS
11 POLE-1 RUNBACK ACTIVATED INDICATION SPS 11 POLE-1 VESDA TRIP SPS 11 SM-1 DC LINE FAULT RECOVERY SEQUENCE IN PROGRESS SPS
12 POLE-1 POWER SWING MODULATION ON/OFF SPS 12 POLE-1 EMERGENCY SWITCH OFF SPS 12 SM-1 AC BYPASS AREA SUMMARY FAULT SPS
13 POLE-1 FREQUENCY CONTROL ON/OFF SPS 13 POLE-1 POWER DIRECTION SPS 13 SM-1 COUPLING TRANSFORMER SUMMARY FAULT SPS
14 POLE-1 FREQUENCY CONTROL ACTIVATED SPS 14 POLE-1 POWER SWING MODULATION ON/OFF SPS 14 SM-1 STAR POINT AREA SUMMARY FAULT SPS
15 POLE-1 DC LINE TRANSIENT FAULT SPS 15 POLE-1 FREQUENCY CONTROL ON/OFF SPS 15 SM-1 VALVE HALL SUMMARY FAULT SPS
16 POLE-1 IN P/I MODE SPS 16 POLE-1 FREQUENCY CONTROL ACTIVATED SPS 16 SM-1 VALVE COOLING SYSTEM SUMMARY FAULT SPS
17 POLE 1 VBE/VCU SUMMARY FAULT SPS 17 POLE-1 OPERATION AT POWER/CURRENT LIMIT SPS 17 SM-1 VALVE COOLING TRIP SPS
18 POLE 1 VALVE HALL SUMMARY TRIP SPS 18 BIPOLE DC POWER AI 18 SM-1 DC YARD SUMMARY FAULT SPS
19 POLE-1 CONVERTER TRANSFORMER SUMMARY FAULT SPS 19 STABILITY FUNCTION ENABLED SPS 19 SM-1 VESDA/ARC PROTECTION TRIP SPS
20 POLE-1 VALVE COOLING SYSTEM FAULT SPS 20 ABSOLUTE MINIMUM FILTER CRITERIA NOT FULFILLED SPS 20 SM-1 LINE FAULT PROTECTION OPERATED SPS
21 POLE-1 VALVE COOLING TRIP SPS 21 AUTOMATIC BIPOLE POWER CONTROL SPS 21 SM-1 RECONFIGURATION TO DECOUPLED SEQUENCE IN PROGRESS SPS
22 POLE-1 DC YARD SUMMARY FAULT SPS 22 RPC ON/OFF SPS 22 SM-1 RECONFIGURATION TO ISLANDED SEQUENCE IN PROGRESS SPS
23 POLE-1 VESDA TRIP SPS 23 RPC AUTO/MANUAL SPS 23 SM-1 EMERGENCY SWITCH OFF SPS
24 POLE-1 EMERGENCY SWITCH OFF SPS NOTE- Signals from 1-17 are to be repeated for all Pole 24 SM-1 POD ENABLED SPS
25 POLE-1 DC FILTER CONNECTED/DISCONNECTED SPS 25 SM-1 RUN BACK SPS
26 POLE-1 DC LINE FAULT SPS 26 SM-1 FREQUENCY CONTROL SPS
27 POLE-1 OPERATION AT POWER/CURRENT LIMIT SPS 27 MULTI LINK POWER ORDER AI
28 BIPOLE DC POWER AI 28 SPS ACTIVATED SPS
29 NEUTRAL AREA SUMMARY TRIP SPS 29 ACTIVE POWER MULTI LINK OPERATION SELECTED SPS
30 ABSOLUTE MINIMUM FILTER CRITERIA NOT FULFILLED SPS 30 ACTIVE POWER SINGLE LINK OPERATION SELECTED SPS
31 DMR 1/2 CONNECTED SPS 31 REACTIVE POWER MULTI LINK OPERATION SELECTED SPS
32 AUTOMATIC BIPOLE POWER CONTROL SPS 32 REACTIVE POWER SINGLE LINK OPERATION SELECTED SPS
33 MASTER STATION STATION A/ STATION B SPS NOTE- Signals from 1-26 are to be repeated for Symmetric Monopole
34 RPC ON/OFF SPS
35 RPC AUTO/MANUAL SPS
36 STABILITY FUNCTION ENABLED SPS
NOTE- Signals from 1-27 are to be repeated for all Pole
S.No SIGNAL NAME TYPE
1 AC FILTER BANK MVAR AI
2 FILTER PROTECTION TRIP SPS
NOTE- 1) No. of Signals as per availability of AC Filters
NOTE- 1)For AC Side bays and convertor transformer, Typical datalist for AC Substation is to be referrred. 2) If any other signal is required for remote operation as per site condition, it needs to be incorporated in final signal list. 3)DPS for all HVDC Switchgear/Equipment to be added in NTAMC signal list for HVDC Station during detailed Engineering. 4) The list can be a basic guideline which has to be reviewed during detailed engineering and any modifications/new signal are required the same to be incorporated accordingly
NOTE- If any other signal is required for remote operation as per site condition, it needs to be incorporated in final signal list.
NTAMC TYPICAL SIGNALS FOR TS of STATCOM
STATCOM STATION MSR/MSC AUX-TRAFO
S.No SIGNAL NAME TYPE S.No SIGNAL NAME TYPE S.No SIGNAL NAME TYPE
1 COOLING SYSTEM-1 TRIP SPS 1 MSR-1 MAIN PROTECTION TRIP SPS 1 MAIN PROTECTION TRIP SPS
2 COOLING SYSTEM-2 TRIP SPS 2 MSR-1 MAIN LBB PROTECTION TRIP SPS 2 BACKUP PROTECTION TRIP SPS
3 STATCOM BOTH STATION CONTROLLER FAILURE TRIP SPS 3 MSR-1 BACKUP PROTECTION TRIP SPS 3 MAIN PROTECTION RELAY FAILURE SPS
4 STATION CONTROLLER-1 START SPS 4 MSR-1 BACKUP LBB PROTECTION TRIP SPS 4 BACKUP PROTECTION RELAY FAILURE SPS
5 STATION CONTROLLER-1 STOP SPS 5 MSR-1 MAIN PROTECTION RELAY FAILURE SPS 5 TRIP RELAY-A(86A) OPERATED SPS
6 STATION CONTROLLER-2 START SPS 6 MSR-1 BACKUP PROTECTION RELAY FAILURE SPS 6 TRIP RELAY-B(86B) OPERATED SPS
7 STATION CONTROLLER-2 STOP SPS 7 MSR-1 TRIP RELAY-A(86A) OPERATED SPS 7 BUCHHOLZ RELAY TRIP SPS
8 STATCOM STATION RUNNING SPS 8 MSR-1 TRIP RELAY-B(86B) OPERATED SPS 8 WTI TRIP SPS
9 STATCOM STATION SEQUENCE FAIULRE SPS 9 MSR-1 TRIP RELAY-A(86A) RESET SPC 9 OTI TRIP SPS
10 UNIT-1 CONTROLLER START SPS 10 MSR-1 TRIP RELAY-B(86B) RESET SPC 10 BUCHHOLZ RELAY ALARM SPS
11 UNIT-1 CONTROLLER STOP SPS 11 MSR-1 MVAR AI 11 WTI ALARM SPS
12 STATCOM UNIT-1 STOPPED SPS 12 MSR-1 PSD ON DPS 12 OTI ALARM SPS
13 STATCOM UNIT-1 RUNNING SPS 13 MSR-1 PSD BYPASS DPS 13 TRIP CIRCUIT-1 FAULTY SPS
14 STATCOM UNIT-1 SEQUENCE FAIULRE SPS NOTE- Same siganals to be taken for MSR-2, MSC-1 & 2 14 TRIP CIRCUIT-2 FAULTY SPS
15 UNIT-2 CONTROLLER START SPS STATCOM-1 15 PRESSURE BLOCKING ALARM SPS
16 UNIT-2 CONTROLLER STOP SPS S.No SIGNAL NAME TYPE 16 SF6 GAS LOW ALARM SPS
17 STATCOM UNIT-2 STOPPED SPS 1 MAIN PROTECTION TRIP SPS 17 POLE DISCREPANCY ALARM SPS
18 STATCOM UNIT-2 RUNNING SPS 2 MAIN LBB PROTECTION TRIP SPS 18 AC FAILURE ALARM SPS
19 STATCOM UNIT-2 SEQUENCE FAIULRE SPS 3 STATCOM-1 BOTH UNIT CONTROLLER FAILURE TRIP SPS 19 TRIP RELAY-A(86A) RESET SPC
20 ONE KEY START SPS 4 BACKUP PROTECTION TRIP SPS 20 TRIP RELAY-B(86B) RESET SPC
21 ONE KEY STOP SPS 5 BACKUP LBB PROTECTION TRIP SPS 21 KW AI
22 AUTOMATIC START/STOP SEQUENCE RUNNING SPS 6 MAIN PROTECTION RELAY FAILURE SPS 22 KVAR AI
23 AUTOMATIC START/STOP SEQUENCE FAIL SPS 7 BACKUP PROTECTION RELAY FAILURE SPS 23 KVA AI
24 (STATION) HV SIDE OVERVOLTAGE TRIP SPS 8 MASTER TRIP RELAY-A(86A) OPERATED SPS
25 (STATION) HV SIDE UNDERVOLTAGE TRIP SPS 9 MASTER TRIP RELAY-B(86B) OPERATED SPS AUXILIARY
26 (STATION) HV SIDE OVERCURRENT TRIP SPS 10 STATCOM UNIT-1 CONTROLLER A FAILURE (COMM. FAIL / HW FAIL) SPS S.No SIGNAL NAME TYPE
27 (STATION) HV IVT FAIL TRIP SPS 11 STATCOM UNIT-1 CONTROLLER B FAILURE (COMM. FAIL / HW FAIL) SPS 1 UPS-1 BYPASS FAILURE SPS
28 EMERGENCY STOP SPS 12 (UNIT-1) COOLING SYSTEM ALARM SPS 2 UPS-1 AC SUPPLY FAILURE SPS
29 GROUP MESSAGE : STATION CONTROLLER A FAILURE (COMM. FAIL / HW FAIL) SPS 13 (UNIT-1) COOLING SYSTEM CONTROLLER-A ACTIVE SPS 3 UPS-1 LOAD ON MAINS SPS
30 GROUP MESSAGE : STATION CONTROLLER B FAILURE (COMM. FAIL / HW FAIL) SPS 14 (UNIT-1) COOLING SYSTEM CONTROLLER-B ACTIVE SPS 4 UPS-1 LOAD ON MAINTENANCE BYPASS-MODE SPS
31 MANUAL Q CONTROL MODE SELECTED SPS 15 (UNIT-1) COOLING SYSTEM CONTROLLER-A FAILURE SPS 5 UPS-1 LOAD ON STATIC BYPASS-MODE SPS
32 AUTOMATIC VOLTAGE CONTROL MODE SELECTED SPS 16 (UNIT-1) COOLING SYSTEM CONTROLLER-B FAILURE SPS 6 UPS-1 LOAD ON INVERTER SPS
33 NEGATIVE SEQ. VOLTAGE CONTROL ENABLED SPS 17 (UNIT-1) VALVE OVERCURRENT TRIP SPS 7 UPS-1 BATTERY LOW/LOW DC VOLTAGE SPS
34 POD CONTROL ENABLE SPS 18 (UNIT-1) COOLING SYSTEM TRIP SPS 8 UPS-1 BATTERY MCCB OFF/TRIP SPS
35 SSOD CONTROL ENABLED SPS 19 (UNIT-1) DC CT POWER FAIL SPS 9 UPS-1 TROUBLE COMMON ALARM SPS
36 ADAPTIVE GAIN REDUCTION ENABLED SPS 20 (UNIT-1) PHASE CONTROLLER FAILURE TRIP SPS 10 UPS -1 FAN FAILURE SPS
37 ADAPTIVE GAIN CLACULATION ENABLED SPS 21 (UNIT-1) VALVE ERROR TRIP SPS
38 MSC-1 CONTROL MODE - AUTO. CONTROL SELLECTED SPS 22 (UNIT-1) SUB-MODULE FAILURE OR BYPASSED SPS NOTE- 1)NOTE- Same siganals to be taken for UPS-2 2) Other signals are to be taken from Auxiliary typical list.
39 MSC-1 CONTROL MODE - AUTO. CONTROL SELLECTED SPS 23 (UNIT-1) VALVE HALL-1 TEMPERATURE HIGH TRIP SPS
40 MSR-1 CONTROL MODE - AUTO. CONTROL SELLECTED SPS 24 STATCOM UNIT-1 TRIP RELAY-A(86A) RESET SPC
41 MSR-2 CONTROL MODE - AUTO. CONTROL SELLECTED SPS 25 STATCOM UNIT-1 TRIP RELAY-B(86B) RESET SPC
42 HV BR MAIN BAY CONTROL MODE - AUTO. CONTROL SELLECTED SPS 26 STATCOM UNIT-1 MVAR AI
43 HV BR TIE BAY CONTROL MODE - AUTO. CONTROL SELLECTED SPS 27 STATCOM UNIT-1 EMERGENCY STOP SPC
44 AHU STATCOM UNIT 1-A RUNNING SPS 28 STATCOM UNIT-1 EMERGENCY STOP STATUS SPS
45 AHU STATCOM UNIT 1-B RUNNING SPS 29 STATCOM-1 COOLING SYSTEM COMMAND CMD
46 AHU STATCOM UNIT 2-A RUNNING SPS 30 STATCOM-1 COOLING SYSTEM STATUS SPS
47 AHU STATCOM UNIT 2-B RUNNING SPS 31 STATCOM-1 READY FOR OPERATION SPS
48 V-REF SETTING AI 32 STATCOM-1 SEQUENCE FAILURE SPS AVR
49 SLOPE/DROOP SETTING AI 33 STATCOM-1 SEQUENCE RUNNING SPS S.No SIGNAL NAME TYPE
50 DEAD-BAND UP SETTING AI 34 STATCOM-1 PSD ON DPS 1 AVR FAIL ALARM SPS
51 DEAD-BAND DOWN SETTING AI 35 STATCOM-1 PSD BYPASS DPS 2 AVR STOP SPS
52 Q-REF SETTING AI NOTE- Same siganals to be taken for STATCOM-2 3 AVR Warning ALARM SPS
53 CONTROL MODE : MANUAL Q CONTROL / AUTOMATIC VOLTAGE CONTROL AI_CMD 4 AVR Transformer Alarm SPS
54 V-REF SETTING AI_CMD
55 DEAD-BAND UP SETTING AI_CMD
56 DEAD-BAND DOWN SETTING AI_CMD GROUND TRANSFORMER
57 SLOPE/DROOP SETTING AI_CMD S.No SIGNAL NAME TYPE TERTIARY TRAFO
58 Q-REF SETTING AI_CMD 1 MV BUSBAR BACKUP PROTECTION TRIP (GND TRAFO TRIP) SPS S.No SIGNAL NAME TYPE
59 POD CONTROL ENABLE AI_CMD 2 BACKUP PROTECTION RELAY FAILURE (GND TRAFO) SPS 1 33kV AUX. TR PROTECTION TRIP SPS
60 SSOD CONTROL ENABLE AI_CMD 3 BUCHHOLZ RELAY TRIP SPS 2 33kV AUX. TR TRIP RELAY OPERATED SPS
61 NEGATIVE SEQ. VOLTAGE CONTROL ENABLE AI_CMD 4 PRD TRIP SPS 3 33kV AUX. TR CB SF6 Loss Alarm SPS
62 ADACTIVE GAIN REDUCTION ENABLE AI_CMD 5 WTI TRIP SPS 4 33kV AUX. TR CB SF6 Lockout Alarm SPS
63 ADACTIVE GAIN CALCULATION ENABLE AI_CMD 6 OTI TRIP SPS 5 33kV AUX. TR CB Spring Charged SPS
64 MSC-1CONTROL MODE - AUTOMATIC / MANUAL AI_CMD 7 BUCHHOLZ RELAY ALARM SPS 6 33kV AUX. TR CB DC 1/2 Fail Alarm SPS
65 MSC-2 CONTROL MODE - AUTOMATIC / MANUAL AI_CMD 8 WTI ALARM SPS 7 33kV AUX. TR Bucholz Alarm SPS
66 MSR-1 CONTROL MODE - AUTOMATIC / MANUAL AI_CMD 9 OTI ALARM SPS 8 33kV AUX. TR WTI Alarm SPS
67 MSR-2 CONTROL MODE - AUTOMATIC / MANUAL AI_CMD NOTE- Signals other than Switchgear Status, Interlock and command 9 33kV AUX. TR OTI Alarm SPS
68 HV BR MAIN BAY CONTROL MODE - AUTOMATIC AI_CMD 10 KW AI
69 HV BR TIE BAY CONTROL MODE - AUTOMATIC AI_CMD MV BUSBAR 11 KVAR AI
70 ONE KEY START SPC S.No SIGNAL NAME TYPE
71 ONE KEY STOP SPC 1 MV BUS VOLTAGE AI
72 TFR TRIGGER CMD SPS 2 MV BUS PROTECTION TRIP SPS
3 MV BUS PROTECTION RELAY FAILURE SPS
NOTE- 1. For 400KV bays, Typical datalist of respective bay is to be referred. 2. For all CB, ISOLATOR and Earthswitch, Typical list of Switchgears to be referred. 3. Grouping of Signals may be done as per site condition. 4. If any other signal is required for remote operation as per site condition, it needs to be incorporated in final signal list. 5. Indexing of Equipments in signal list may be done as per design and availability.
NOTE- If any other signal is required for remote operation as per site condition, it needs to be incorporated in final signal list.
S. No. VOLT. LEVEL BAY NAME BAY NUM. FEEDER TYPE DEVICE IDENTIFICATION POINT DESCRIPTION DATA TYPE IEC 104 ADDRESS REMARK
1 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB OPEN/CLOSE STATUS DPS
3 …KV XXXXXX BAY NO FSC BAY NO-52BBR-RPh BPCB R PHASE OPEN/CLOSE STATUS DPS
5 …KV XXXXXX BAY NO FSC BAY NO-52BBR-YPh BPCB Y PHASE OPEN/CLOSE STATUS DPS
7 …KV XXXXXX BAY NO FSC BAY NO-52BBR-Bph BPCB B PHASE OPEN/CLOSE STATUS DPS
9 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS ISOLATOR OPEN/CLOSE STATUS DPS
10 …KV XXXXXX BAY NO FSC BAY NO-89DS1 ISOLATOR 1 OPEN/CLOSE STATUS DPS
11 …KV XXXXXX BAY NO FSC BAY NO-89DS2 ISOLATOR 2 OPEN/CLOSE STATUS DPS
12 …KV XXXXXX BAY NO FSC BAY NO-89ES1 EARTH SWITCH 1 OPERATION INTERLOCK SPS
13 …KV XXXXXX BAY NO FSC BAY NO-89ES2 EARTH SWITCH 2 OPERATION INTERLOCK SPS
14 …KV XXXXXX BAY NO FSC BAY NO-89ES1 EARTH SWITCH 1 OPEN/CLOSE STATUS DPS
15 …KV XXXXXX BAY NO FSC BAY NO-89ES2 EARTH SWITCH 2 OPEN/CLOSE STATUS DPS
16 …KV XXXXXX BAY NO FSC BAY NO LINE DE-ENRGIZED SPS
17 …KV XXXXXX BAY NO FSC BAY NO FAULT TO PLATFORM TRIP-1/2 SPS
18 …KV XXXXXX BAY NO FSC BAY NO PERMANENT BYPASS SPS
19 …KV XXXXXX BAY NO FSC BAY NO MOV TEMPERATURE R PHASE AI
20 …KV XXXXXX BAY NO FSC BAY NO MOV TEMPERATURE Y PHASE AI
21 …KV XXXXXX BAY NO FSC BAY NO MOV TEMPERATURE B PHASE AI
22 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR R PHASE CURRENT AI
23 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR Y PHASE CURRENT AI
24 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR B PHASE CURRENT AI
25 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR R PHASE UNBALANCED CURRENT AI
26 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR Y PHASE UNBALANCED CURRENT AI
27 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR B PHASE UNBALANCED CURRENT AI
28 …KV XXXXXX BAY NO FSC BAY NO LINE CT CURRENT R-PH AI
29 …KV XXXXXX BAY NO FSC BAY NO LINE CT CURRENT Y-PH AI
30 …KV XXXXXX BAY NO FSC BAY NO LINE CT CURRENT B-PH AI
31 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB STATUS DISCREPANCY SPS
32 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB AUX CONTACT DISCORDANCE SPS
33 …KV XXXXXX BAY NO FSC BAY NO-52BBR GENRAL LOCKOUT/MIN OIL PRESSURE LOCKOUT SPS
34 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB POLE DISCREPANCY SPS
35 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB DC 1/2 FAIL SPS
36 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB LOSS OF SF6 SPS
37 …KV XXXXXX BAY NO FSC BAY NO-52BBR 1POLE REINSERTION DURING AR SPS
38 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER FAIL TO OPEN SPS COMMON- R-PH,Y-PH,B-PH FAIL TO OPEN
39 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER SWITCHWED WITHOUT COMMAND SPS
40 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER FAIL TO CLOSE SPS COMMON- R-PH,Y-PH,B-PH FAIL TO CLOSE
41 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS CB SPRING DISCHARGE/FAILURE SPS
42 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB OPEN CMD DPC
43 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB CLOSE CMD DPC
44 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB OPERATION INTERLOCK SPS
45 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS OPEN CMD DPC
46 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS CLOSE CMD DPC
47 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS OPERATION INTERLOCK SPS
48 …KV XXXXXX BAY NO FSC BAY NO-89DS1 BYPASS CAP ISO 1 OPEN CMD DPC
49 …KV XXXXXX BAY NO FSC BAY NO-89DS1 BYPASS CAP ISO 1 CLOSE CMD DPC
50 …KV XXXXXX BAY NO FSC BAY NO-89DS1 BYPASS CAP ISO 1 OPERATION INTERLOCK SPS
51 …KV XXXXXX BAY NO FSC BAY NO-89DS2 BYPASS CAP ISO 2 OPEN CMD DPC
52 …KV XXXXXX BAY NO FSC BAY NO-89DS2 BYPASS CAP ISO 2 CLOSE CMD DPC
53 …KV XXXXXX BAY NO FSC BAY NO-89DS1 DISCONNECTOR 1 PHASE DISAGREEMENT SPS
54 …KV XXXXXX BAY NO FSC BAY NO-89DS1 GENERAL ALARM SPS
55 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS DISCONNECTOR ALARM SPS
56 …KV XXXXXX BAY NO FSC BAY NO-89DS2 DISCONNECTOR 2 PHASE DISAGREEMENT SPS
57 …KV XXXXXX BAY NO FSC BAY NO-89DS2 GENERAL ALARM SPS
58 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR UNBALANCE ALARM SPS
59 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR UNBALANCED TRIP SPS FOR BOTH HIGH SET AND LOW SET (IF AVAILABLE)
60 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR OVERLOAD ALARM SPS
61 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR OVERLOAD TRIP SPS
62 …KV XXXXXX BAY NO FSC BAY NO-MOV MOV TRIP SPS
63 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM FAIL-1 SPS
64 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM FAIL-2 SPS
65 …KV XXXXXX BAY NO FSC BAY NO-PROT SIGNAL TRANSMISSION POWER FAIL SPS
66 …KV XXXXXX BAY NO FSC BAY NO-PROT MASTER TRIP SPS
67 …KV XXXXXX BAY NO FSC BAY NO-PROT GPS TIME SYNC FAIL SPS
68 …KV XXXXXX BAY NO FSC BAY NO-PROT DIRECT TRIP RECEIVE SPS
69 …KV XXXXXX BAY NO FSC BAY NO-PROT COMMUNICATION CHANNEL FAIL SPS
70 …KV XXXXXX BAY NO FSC BAY NO-89DS2 BYPASS CAP ISO 2 OPERATION INTERLOCK SPS
71 …KV XXXXXX BAY NO FSC BAY NO-PROT MASTER TRIP RST SPC
72 …KV XXXXXX BAY NO FSC BAY NO-PROT MOV FAIL SPS COMMON- R-PH,Y-PH,B-PH
73 …KV XXXXXX BAY NO FSC BAY NO-PROT KIOSK TEMP AI
74 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL SYSTEM 1 HARDWARE ALARM SPS Group Alarm
75 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 1 HARDWARE ALARM SPS Group Alarm
76 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM 1 COMMUNICATION FAULT SPS Group Alarm
77 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 1 MEASURING SYSTEM WARNING SPS Group Alarm
78 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL SYSTEM 2 HARDWARE ALARM SPS Group Alarm
79 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 2 HARDWARE ALARM SPS Group Alarm
80 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM 2 COMMUNICATION FAULT SPS Group Alarm
81 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 2 MEASURING SYSTEM WARNING SPS Group Alarm
82 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM POWER SUPPLY ALARM SPS Group Alarm
83 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM REDUNDANCY DISTURBED SPS Group Alarm
84 …KV XXXXXX BAY NO FSC BAY NO-PROT EARTH SWITCH 1 ALARM SPS Group Alarm
85 …KV XXXXXX BAY NO FSC BAY NO-PROT EARTH SWITCH 2 ALARM SPS Group Alarm
86 …KV XXXXXX BAY NO FSC BAY NO-PROT DISCONNECTOR SWITCH 1 ALARM SPS Group Alarm
87 …KV XXXXXX BAY NO FSC BAY NO-PROT DISCONNECTOR SWITCH 2 ALARM SPS Group Alarm
88 …KV XXXXXX BAY NO FSC BAY NO-PROT LINE EARTH SWITCH ALARM SPS Group Alarm
89 …KV XXXXXX BAY NO FSC BAY NO-PROT BYPASS BREAKER ALARM SPS Group Alarm
90 …KV XXXXXX BAY NO FSC BAY NO-PROT MAIN BYPASS SWITCH ALARM SPS Group Alarm
91 …KV XXXXXX BAY NO FSC BAY NO-PROT LINE SIDE 1: DE-ENERGIZED SPS
92 …KV XXXXXX BAY NO FSC BAY NO-PROT LINE SIDE 2: DE-ENERGIZED SPS
93 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER LOCAL/REMOTE CONTROL SPS
94 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER MAIN CLOSING COIL UNHEALTHY SPS
95 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER BACKUP CLOSING COIL UNHEALTHY SPS
96 …KV XXXXXX BAY NO FSC BAY NO-PROT FIRE FIGHTING SYSTEM: ALARM SPS
97 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV OVERLOAD SPS
98 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV TEMPERATURE TRIP SPS
99 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV TEMPERATURE GRADIENT LOW SET SPS
100 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV TEMPERATURE GRADIENT HIGH SET SPS
101 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV UNBALANCE SPS
102 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV HIGH CURRENT SPS
103 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP FAILED TO TRIGGER SPS
104 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP DELAYED TRIGGER SPS
105 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP PROLONGED CONDUCTION SPS
106 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP SELF TRIGGER SPS
107 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP TRIGGER (R,Y,B) SPS R,Y,B Phase to be combined
108 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: BYPASS BREAKER FAIL SPS
109 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: PREVENT REINSERTION ACTIVE SPS
110 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: PERMANENT BYPASS SPS
111 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: TEMPORARY BYPASS PHASE(R,Y,B) SPS R,Y,B Phase to be combined
112 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: REINSERTION SPS
113 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: LINE TRIP SPS
114 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV OVERLOAD SPS
115 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV TEMPERATURE TRIP SPS
116 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV TEMPERATURE GRADIENT LOW SET SPS
117 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV TEMPERATURE GRADIENT HIGH SET SPS
118 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV UNBALANCE SPS
119 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV HIGH CURRENT SPS
120 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP FAILED TO TRIGGER SPS
121 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP DELAYED TRIGGER SPS
122 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP PROLONGED CONDUCTION SPS
123 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP SELF TRIGGER SPS
124 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP TRIGGER (R,Y,B) SPS R,Y,B Phase to be combined
125 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: BYPASS BREAKER FAIL SPS
126 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: PREVENT REINSERTION ACTIVE SPS
127 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: PERMANENT BYPASS SPS
128 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: TEMPORARY BYPASS PHASE(R,Y,B) SPS R,Y,B Phase to be combined
129 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: REINSERTION SPS
130 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: LINE TRIP SPS
S. No. VOLT. LEVEL BAY NAME BAY NUM. FEEDER TYPE DEVICE IDENTIFICATION POINT DESCRIPTION DATA TYPE IEC 104 ADDRESS REMARK
1 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB OPEN/CLOSE STATUS DPS
3 …KV XXXXXX BAY NO FSC BAY NO-52BBR-RPh BPCB R PHASE OPEN/CLOSE STATUS DPS
5 …KV XXXXXX BAY NO FSC BAY NO-52BBR-YPh BPCB Y PHASE OPEN/CLOSE STATUS DPS
7 …KV XXXXXX BAY NO FSC BAY NO-52BBR-Bph BPCB B PHASE OPEN/CLOSE STATUS DPS
9 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS ISOLATOR OPEN/CLOSE STATUS DPS
10 …KV XXXXXX BAY NO FSC BAY NO-89DS1 ISOLATOR 1 OPEN/CLOSE STATUS DPS
11 …KV XXXXXX BAY NO FSC BAY NO-89DS2 ISOLATOR 2 OPEN/CLOSE STATUS DPS
12 …KV XXXXXX BAY NO FSC BAY NO-89ES1 EARTH SWITCH 1 OPERATION INTERLOCK SPS
13 …KV XXXXXX BAY NO FSC BAY NO-89ES2 EARTH SWITCH 2 OPERATION INTERLOCK SPS
14 …KV XXXXXX BAY NO FSC BAY NO-89ES1 EARTH SWITCH 1 OPEN/CLOSE STATUS DPS
15 …KV XXXXXX BAY NO FSC BAY NO-89ES2 EARTH SWITCH 2 OPEN/CLOSE STATUS DPS
16 …KV XXXXXX BAY NO FSC BAY NO LINE DE-ENRGIZED SPS
17 …KV XXXXXX BAY NO FSC BAY NO FAULT TO PLATFORM TRIP-1/2 SPS
18 …KV XXXXXX BAY NO FSC BAY NO PERMANENT BYPASS SPS
19 …KV XXXXXX BAY NO FSC BAY NO MOV TEMPERATURE R PHASE AI
20 …KV XXXXXX BAY NO FSC BAY NO MOV TEMPERATURE Y PHASE AI
21 …KV XXXXXX BAY NO FSC BAY NO MOV TEMPERATURE B PHASE AI
22 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR R PHASE CURRENT AI
23 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR Y PHASE CURRENT AI
24 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR B PHASE CURRENT AI
25 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR R PHASE UNBALANCED CURRENT AI
26 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR Y PHASE UNBALANCED CURRENT AI
27 …KV XXXXXX BAY NO FSC BAY NO CAPACITOR B PHASE UNBALANCED CURRENT AI
28 …KV XXXXXX BAY NO FSC BAY NO LINE CT CURRENT R-PH AI
29 …KV XXXXXX BAY NO FSC BAY NO LINE CT CURRENT Y-PH AI
30 …KV XXXXXX BAY NO FSC BAY NO LINE CT CURRENT B-PH AI
31 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB STATUS DISCREPANCY SPS
32 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB AUX CONTACT DISCORDANCE SPS
33 …KV XXXXXX BAY NO FSC BAY NO-52BBR GENRAL LOCKOUT/MIN OIL PRESSURE LOCKOUT SPS
34 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB POLE DISCREPANCY SPS
35 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB DC 1/2 FAIL SPS
36 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB LOSS OF SF6 SPS
37 …KV XXXXXX BAY NO FSC BAY NO-52BBR 1POLE REINSERTION DURING AR SPS
38 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER FAIL TO OPEN SPS COMMON- R-PH,Y-PH,B-PH FAIL TO OPEN
39 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER SWITCHWED WITHOUT COMMAND SPS
40 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER FAIL TO CLOSE SPS COMMON- R-PH,Y-PH,B-PH FAIL TO CLOSE
41 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS CB SPRING DISCHARGE/FAILURE SPS
42 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB OPEN CMD DPC
43 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB CLOSE CMD DPC
44 …KV XXXXXX BAY NO FSC BAY NO-52BBR BPCB OPERATION INTERLOCK SPS
45 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS OPEN CMD DPC
46 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS CLOSE CMD DPC
47 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS MBS OPERATION INTERLOCK SPS
48 …KV XXXXXX BAY NO FSC BAY NO-89DS1 BYPASS CAP ISO 1 OPEN CMD DPC
49 …KV XXXXXX BAY NO FSC BAY NO-89DS1 BYPASS CAP ISO 1 CLOSE CMD DPC
50 …KV XXXXXX BAY NO FSC BAY NO-89DS1 BYPASS CAP ISO 1 OPERATION INTERLOCK SPS
51 …KV XXXXXX BAY NO FSC BAY NO-89DS2 BYPASS CAP ISO 2 OPEN CMD DPC
52 …KV XXXXXX BAY NO FSC BAY NO-89DS2 BYPASS CAP ISO 2 CLOSE CMD DPC
53 …KV XXXXXX BAY NO FSC BAY NO-89DS1 DISCONNECTOR 1 PHASE DISAGREEMENT SPS
54 …KV XXXXXX BAY NO FSC BAY NO-89DS1 GENERAL ALARM SPS
55 …KV XXXXXX BAY NO FSC BAY NO-89MBS BYPASS DISCONNECTOR ALARM SPS
56 …KV XXXXXX BAY NO FSC BAY NO-89DS2 DISCONNECTOR 2 PHASE DISAGREEMENT SPS
57 …KV XXXXXX BAY NO FSC BAY NO-89DS2 GENERAL ALARM SPS
58 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR UNBALANCE ALARM SPS
59 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR UNBALANCED TRIP SPS FOR BOTH HIGH SET AND LOW SET (IF AVAILABLE)
60 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR OVERLOAD ALARM SPS
61 …KV XXXXXX BAY NO FSC BAY NO-CAP CAPACITOR OVERLOAD TRIP SPS
62 …KV XXXXXX BAY NO FSC BAY NO-MOV MOV TRIP SPS
63 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM FAIL-1 SPS
64 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM FAIL-2 SPS
65 …KV XXXXXX BAY NO FSC BAY NO-PROT SIGNAL TRANSMISSION POWER FAIL SPS
66 …KV XXXXXX BAY NO FSC BAY NO-PROT MASTER TRIP SPS
67 …KV XXXXXX BAY NO FSC BAY NO-PROT GPS TIME SYNC FAIL SPS
68 …KV XXXXXX BAY NO FSC BAY NO-PROT DIRECT TRIP RECEIVE SPS
69 …KV XXXXXX BAY NO FSC BAY NO-PROT COMMUNICATION CHANNEL FAIL SPS
70 …KV XXXXXX BAY NO FSC BAY NO-89DS2 BYPASS CAP ISO 2 OPERATION INTERLOCK SPS
71 …KV XXXXXX BAY NO FSC BAY NO-PROT MASTER TRIP RST SPC
72 …KV XXXXXX BAY NO FSC BAY NO-PROT MOV FAIL SPS COMMON- R-PH,Y-PH,B-PH
73 …KV XXXXXX BAY NO FSC BAY NO-PROT KIOSK TEMP AI
74 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL SYSTEM 1 HARDWARE ALARM SPS Group Alarm
75 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 1 HARDWARE ALARM SPS Group Alarm
76 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM 1 COMMUNICATION FAULT SPS Group Alarm
77 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 1 MEASURING SYSTEM WARNING SPS Group Alarm
78 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL SYSTEM 2 HARDWARE ALARM SPS Group Alarm
79 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 2 HARDWARE ALARM SPS Group Alarm
80 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM 2 COMMUNICATION FAULT SPS Group Alarm
81 …KV XXXXXX BAY NO FSC BAY NO-PROT PROTECTION SYSTEM 2 MEASURING SYSTEM WARNING SPS Group Alarm
82 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM POWER SUPPLY ALARM SPS Group Alarm
83 …KV XXXXXX BAY NO FSC BAY NO-PROT CONTROL & PROTECTION SYSTEM REDUNDANCY DISTURBED SPS Group Alarm
84 …KV XXXXXX BAY NO FSC BAY NO-PROT EARTH SWITCH 1 ALARM SPS Group Alarm
85 …KV XXXXXX BAY NO FSC BAY NO-PROT EARTH SWITCH 2 ALARM SPS Group Alarm
86 …KV XXXXXX BAY NO FSC BAY NO-PROT DISCONNECTOR SWITCH 1 ALARM SPS Group Alarm
87 …KV XXXXXX BAY NO FSC BAY NO-PROT DISCONNECTOR SWITCH 2 ALARM SPS Group Alarm
88 …KV XXXXXX BAY NO FSC BAY NO-PROT LINE EARTH SWITCH ALARM SPS Group Alarm
89 …KV XXXXXX BAY NO FSC BAY NO-PROT BYPASS BREAKER ALARM SPS Group Alarm
90 …KV XXXXXX BAY NO FSC BAY NO-PROT MAIN BYPASS SWITCH ALARM SPS Group Alarm
91 …KV XXXXXX BAY NO FSC BAY NO-PROT LINE SIDE 1: DE-ENERGIZED SPS
92 …KV XXXXXX BAY NO FSC BAY NO-PROT LINE SIDE 2: DE-ENERGIZED SPS
93 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER LOCAL/REMOTE CONTROL SPS
94 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER MAIN CLOSING COIL UNHEALTHY SPS
95 …KV XXXXXX BAY NO FSC BAY NO-52BBR BYPASS BREAKER BACKUP CLOSING COIL UNHEALTHY SPS
96 …KV XXXXXX BAY NO FSC BAY NO-PROT FIRE FIGHTING SYSTEM: ALARM SPS
97 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV OVERLOAD SPS
98 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV TEMPERATURE TRIP SPS
99 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV TEMPERATURE GRADIENT LOW SET SPS
100 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV TEMPERATURE GRADIENT HIGH SET SPS
101 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV UNBALANCE SPS
102 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: MOV HIGH CURRENT SPS
103 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP FAILED TO TRIGGER SPS
104 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP DELAYED TRIGGER SPS
105 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP PROLONGED CONDUCTION SPS
106 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP SELF TRIGGER SPS
107 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: SPARK GAP TRIGGER (R,Y,B) SPS R,Y,B Phase to be combined
108 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: BYPASS BREAKER FAIL SPS
109 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: PREVENT REINSERTION ACTIVE SPS
110 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: PERMANENT BYPASS SPS
111 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: TEMPORARY BYPASS PHASE(R,Y,B) SPS R,Y,B Phase to be combined
112 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: REINSERTION SPS
113 …KV XXXXXX BAY NO FSC BAY NO-PROT-1 SYSTEM 1: LINE TRIP SPS
114 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV OVERLOAD SPS
115 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV TEMPERATURE TRIP SPS
116 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV TEMPERATURE GRADIENT LOW SET SPS
117 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV TEMPERATURE GRADIENT HIGH SET SPS
118 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV UNBALANCE SPS
119 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: MOV HIGH CURRENT SPS
120 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP FAILED TO TRIGGER SPS
121 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP DELAYED TRIGGER SPS
122 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP PROLONGED CONDUCTION SPS
123 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP SELF TRIGGER SPS
124 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: SPARK GAP TRIGGER (R,Y,B) SPS R,Y,B Phase to be combined
125 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: BYPASS BREAKER FAIL SPS
126 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: PREVENT REINSERTION ACTIVE SPS
127 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: PERMANENT BYPASS SPS
128 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: TEMPORARY BYPASS PHASE(R,Y,B) SPS R,Y,B Phase to be combined
129 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: REINSERTION SPS
130 …KV XXXXXX BAY NO FSC BAY NO-PROT-2 SYSTEM 2: LINE TRIP SPS
NTAMC TYPICAL SIGNALS FOR SVC
SVC CONTROLLER AND PROTECTION TSC/TCR DTF FILTER
S.No Signal name TYPE S.No Signal name TYPE S.No Signal name TYPE
1 SVC CONTROLLER 1 ALARM SPS 1 TCR ALARM SPS 1 DTF Filter Ararm SPS
2 SVC CONTROLLER 1 TRIP SPS 2 TCR TRIP SPS 2 DTF Filter Trip SPS
3 SVC CONTROLLER 2 ALARM SPS 3 TCR Protn A Fail SPS 3 Double Tunned Filter Protn A Fail SPS
4 SVC CONTROLLER 2 TRIP SPS 4 TCR Protn A Trip SPS 4 Double Tunned Filter Protn A Alarm SPS
5 Q-MODE ENABLED SPS 5 TCR Protn A Alarm SPS 5 Double Tunned Filter Protn A Trip SPS
6 SVC AUTOMATIC MODE (VCM) SPS 6 TCR Protn B Fail SPS 6 Double Tunned Filter Protn B Fail SPS
7 SVC CONTROL FROM LOCAL HMI 1/2 SPS 7 TCR Protn B Trip SPS 7 Double Tunned Filter Protn B Alarm SPS
8 SVC CONTROL FROM RCI 1/2 SPS 8 TCR Protn B Alarm SPS 8 Double Tunned Filter Protn B Trip SPS
9 SVC CONTROL FROM REMOTE HMI 1/2 SPS 9 VALVE BASE ELECTRONIC TCR ALARM SPS 9 DTF Cap Unbalance Protn A Failure/ Alarm Stage 2 SPS
10 SVC MANUAL MODE (FSM) SPS 10 VALVE BASE ELECTRONIC TCR TRIP SPS 10 DTF Cap Unbalance Protn A Unbalance Alarm/ Stage 1 SPS
11 SVC OFF SPS 11 TSC -Cap unbalance protn A Failure SPS 11 DTF Cap Unbalance Protn A TRIP SPS
12 SVC ON SPS 12 TSC -Cap unbalance protn A Alarm SPS 12 DTF Cap Unbalance Protn B Failure/ Alarm Stage 2 SPS
13 SVC READY FOR SWITCHING ON SPS 13 TSC -Cap unbalance protn TRIP SPS 13 DTF Cap Unbalance Protn B Unbalance Alarm Stage 1 SPS
14 SVC READY FOR SWITCHING OFF SPS 14 TCR CURRENT PHASE A-B AI 14 DTF Cap Unbalance Protn B TRIP SPS
15 SVC AUTOMATIC GAIN ADJUSTMENT ENABLED SPS 15 TCR CURRENT PHASE B-C AI 15 FILTER LOCK-OUT RELAY 1 RESET SPC
16 DTF 1/2 FILTER DISCHARGE TIME RUNNING SPS 16 TCR CURRENT PHASE C-A AI 16 FILTER LOCK-OUT RELAY 2 RESET SPC
17 SVC Control DEGRADED MODE SPS 17 TCR LOCK-OUT RELAY 1 RESET SPC 17 Filter Current R-Y AI
18 POWER OSCILLATION DAMPING ENABLED SPS 18 TCR LOCK-OUT RELAY 2 RESET SPC 18 Filter Current Y-B AI
19 POWER OSCILLATION DAMPING DISABLED SPS NOTE- 1)Sr.No. 11,12,13 is specific to TSC 2) Signal to be included for all TCRs & TSCs 19 Filter Current B-R AI
20 SVC AUTOMATIC GAIN ADJUSTMENT DISABLED SPS Note Signal list to be included for all filters
21 SVC Q-MODE DISABLED SPS
22 SVC CONTROL FROM FIELD SPS
23 SVC CONTROLLER-1/2 ALARM SPS
24 SVC CONTROLLER-1/2 TRIP SPS HV BUSBAR STAR COUPLER
25 SVC -PROTN SYSTEM-1/2 ALARM SPS S.No Signal name TYPE S.No Signal name TYPE
26 CONTROL SYSTEM 1 ACTIVE SPS 1 HV BUSBAR ALARM SPS 1 OTI ALARM SPS
27 CONTROL SYSTEM 2 ACTIVE SPS 2 HV BUSBAR TRIP SPS 2 OIL LOW LEVEL ALARM SPS
28 SVC ON SEQUENCE RUNNING SPS 3 HV BUSBAR VOLTAGE R-Y AI 3 BUCHHOLZ RELAY TRIP SPS
29 SVC OFF SEQUENCE RUNNING SPS 4 HV BUSBAR VOLTAGE Y-B AI 4 PRESSURE RELIEF DEVICE TRIP SPS
30 SVC NO SEQUENCE IS RUNNING SPS 5 HV BUSBAR VOLTAGE B-R AI 5 Bunchholz Alarm SPS
31 DIGITAL FAULT RECORDER FAULTY (DFR) SPS 6 WTI ALARM SPS
32 DIGITAL FAULT RECORDER TRIGGERED (DFR) SPS 7 WTI TRIP SPS
33 AC VOLTAGE STABELIZER ALARM SPS MV BUSBAR 8 OTI TRIP SPS
34 SVC -PROTN SYSTEM-1 ALARM SPS S.No Signal name TYPE 9 Neutral Star Coupler TFR Protn A FAIL SPS
35 SVC -PROTN SYSTEM-1 TRIP SPS 1 MV BB Protn 1 FAILURE SPS 10 Neutral Star Coupler TFR Protn A Trip SPS
36 SVC -PROTN SYSTEM-2 ALARM SPS 2 MV BB Protn 1 TRIP SPS 11 Neutral Star Coupler TFR Protn A Alarm SPS
37 SVC -PROTN SYSTEM-2 TRIP SPS 3 MV BB Protn 1 ALARM SPS 12 Neutral Star Coupler TFR Protn B FAIL SPS
38 PROTN 1 - ANY TEST SWITCH IN USE SPS 4 MV BB Protn 2 FAILURE SPS 13 Neutral Star Coupler TFR Protn B Trip SPS
39 PROTN 2 - ANY TEST SWITCH IN USE SPS 5 MV BB Protn 2 TRIP SPS 14 Neutral Star Coupler TFR Protn B Alarm SPS
40 SVC EMERGENCY TRIP 1 SPC 6 MV BB Protn 2 ALARM SPS
41 SVC EMERGENCY TRIP 2 SPC 7 MV BUSBAR ALARM SPS AUXILIARY TRANSFORMER
42 CONTROL VIA RCI 1/2 COMMAND SPC 8 MV BUSBAR TRIP SPS S.No Signal name TYPE
43 POD POWER SELECTION COMMAND SPC 9 MV BUSBAR VOLTAGE R-Y AI 1 OTI ALARM SPS
44 POD FREQUENCY SELECTION COMMAND SPC 10 MV BUSBAR VOLTAGE Y-B AI 2 OTI TRIP SPS
45 AUTOMATIC CONTROL SELECTION (VOLTAGE CONT. MODE) DPC 11 MV BUSBAR VOLTAGE B-R AI 3 WTI ALARM SPS
46 MANUAL CONTROL SELECTION (FIXED SUSCEPT. MODE) DPC 4 WTI TRIP SPS
47 Q CONTROL MODE ENABLE/ DISABLE COMMAND DPC 5 OIL LOW LEVEL ALARM SPS
48 GAIN ADJUSTMENT ENABLE/ DISABLE COMMAND DPC 6 BUCHHOLZ ALARM SPS
49 POWER OSCILLATION DAMPING CONTROL ENABLE/ DISABLE COMMAND DPC 7 BUCHHOLZ RELAY TRIP SPS
50 REFERENCE VOLTAGE RAISE/ LOWER COMMAND DPC AUXILIARY 8 PRESSURE RELIEF DEVICE TRIP SPS
51 REACTIVE POWER MORE CAPACITIVE (RAISE)/ INDUCTIVE (LOWER) COMMAND DPC S.No Signal name TYPE 9 Aux Tfr Protn A FAIL SPS
52 MANUAL MODE REACTIVE OUTPUT MORE CAPACITIVE (RAISE)/ INDUCTIVE (LOWER) COMMAND DPC 1 AHU Motor 1 Thermal overload trip SPS 10 Aux Tfr Protn A Trip SPS
53 CONTROL SYSTEM SLOPE RAISE/ LOWER COMMAND DPC 2 AHU Motor 2 Thermal overload trip SPS 11 Aux Tfr Protn A Alarm SPS
54 VQ MINIMUM RAISE/ LOWER COMMAND DPC 3 AHU Motor 1 Healthy SPS 12 Aux Tfr Protn B FAIL SPS
55 VQ MAXIMUM RAISE/ LOWER COMMAND DPC 4 AHU Motor 2 Healthy SPS 13 Aux Tfr Protn B Trip SPS
56 UNDER VOLTAGE DETECTION RAISE/ LOWER COMMAND DPC 5 AHU Motor 1 in service SPS 14 Aux Tfr Protn B Alarm SPS
57 UNDER VOLTAGE RELEASE RAISE/ LOWER COMMAND DPC 6 AHU Motor 2 in service SPS 15 Auxilliary Tfr supply trip SPS
58 UNDER VOLTAGE DETECTION VALUE AI 7 UPS Overload alarm SPS 16 AUX LOCK-OUT RELAY 1 RESET SPC
59 UNDER VOLTAGE RELEASE VALUE AI 8 UPS Overload trip SPS 17 AUX LOCK-OUT RELAY 2 RESET SPC
60 ACTUAL VOLTAGE VALUE AI 9 UPS Battery Under Voltage SPS
61 SVC REACTIVE POWER AI 10 UPS main supply Off SPS
62 FREQUENCY AI 11 BATTERY ROOM General Alarm SPS
63 CONTROLLER GAIN AI 12 SVC CONTROL ROOM General alarm SPS
64 SVC REACTIVE POWER REFERENCE VALUE AI 13 UPS Fan failure SPS COOLING SYSTEM
65 SVC REACTIVE POWER REFERENCE VALUE AI 14 UPS-1 BATTERY MCCB OFF/TRIP SPS S.No Signal name TYPE
66 SLOPE VALUE AI 15 UPS-1 TROUBLE COMMON ALARM SPS 1 COOLING SYSTEM FLOW AI
67 FIXED SUSCEPTANCE REFERENCE VALUE AI NOTE- 1)Other signals are to be taken from Auxiliary typical list. 2 COOLING SYSTEM PRESSURE VALVE INLET AI
68 MINIMUM VALUE FOR Q-CONTROLLER AI 3 COOLING SYSTEM EXPANSION TANK LEVEL AI
69 MAXIMUM VALUE FOR Q-CONTROLLER AI 4 COOLING SYSTEM CONDUCTIVITY MAIN CIRCUIT AI
70 GAIN REDUCTION FACTOR AI 5 COOLING SYSTEM CONDUCTIVITY ION EXCHANGER AI
71 DEGRADED MODE AI 6 COOLING SYSTEM VALVE INLET TEMPERATURE AI
72 SVC PRIMARY CURRENT R AI 7 THYRISTOR COOLING SYSTEM - ALARM SPS
73 SVC PRIMARY CURRENT Y AI 8 THYRISTOR COOLING SYSTEM - TRIP SPS
74 SVC PRIMARY CURRENT B AI
75 DIGITAL FAULT RECORDER FAULTY (DFR) SPS
76 DIGITAL FAULT RECORDER TRIGGERED (DFR) SPS
NOTE- 1. For 400KV bays, Typical datalist of respective bay is to be referred. 2. For all CB, ISOLATOR and Earthswitch, Typical list of Switchgears to be referred. 3. Grouping of Signals may be done as per site condition. 4. If any other signal is required for remote operation as per site condition, it needs to be incorporated in final signal list. 5. Indexing of Equipments in signal list may be done as per design and availability.
NOTE- If any other signal is required for remote operation as per site condition, it needs to be incorporated in final signal list.
SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (AUX SYSTEM)
REQUIRED SIGNALS FOR AUX SYSTEM
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS
1 415V STNMN1AUXBCU INT BCU IN LOCAL/ REMOTE
2 415V STNMN1AUXBCU SPI DG_CB_OPEN PERMITTED OR ENABLED
3 415V STNMN1AUXBCU SPI DG_CB_CLOSE PERMITTED OR ENABLED
4 415V STNMN1AUXBCU DPI DG_CB POSITION
5 415V STNMN1AUXBCU CMD DG_CB COMMAND CLOSE / OPEN
6 415V STNMN1AUXBCU SPI MSB_INCOMER_1_CB_OPEN PERMITTED OR ENABLED
7 415V STNMN1AUXBCU SPI MSB_INCOMER_1_CB_CLOSE PERMITTED OR ENABLED
8 415V STNMN1AUXBCU DPI MSB_INCOMER_1_CB POSITION
9 415V STNMN1AUXBCU CMD MSB_INCOMER_1_CB COMMAND CLOSE / OPEN
10 415V STNMN1AUXBCU SPI MSB_INCOMER_2_CB_OPEN PERMITTED OR ENABLED
11 415V STNMN1AUXBCU SPI MSB_INCOMER_2_CB_CLOSE PERMITTED OR ENABLED
12 415V STNMN1AUXBCU DPI MSB_INCOMER_2_CB POSITION
13 415V STNMN1AUXBCU CMD MSB_INCOMER_2_CB COMMAND CLOSE / OPEN
14 415V STNMN1AUXBCU SPI MSB_BUSCOUPLER_CB_OPEN PERMITTED OR ENABLED
15 415V STNMN1AUXBCU SPI MSB_BUSCOUPLER_CB_CLOSE PERMITTED OR ENABLED
16 415V STNMN1AUXBCU DPI MSB_BUSCOUPLER_CB POSITION
17 415V STNMN1AUXBCU CMD MSB_BUSCOUPLER_CB COMMAND CLOSE / OPEN
18 415V STNMN1AUXBCU SPI ACDB_INCOMER_1_CB_OPEN PERMITTED OR ENABLED
19 415V STNMN1AUXBCU SPI ACDB_INCOMER_1_CB_CLOSE PERMITTED OR ENABLED
20 415V STNMN1AUXBCU DPI ACDB_INCOMER_1_CB POSITION
21 415V STNMN1AUXBCU CMD ACDB_INCOMER_1_CB COMMAND CLOSE / OPEN
22 415V STNMN1AUXBCU SPI ACDB_INCOMER_2_CB_OPEN PERMITTED OR ENABLED
23 415V STNMN1AUXBCU SPI ACDB_INCOMER_2_CB_CLOSE PERMITTED OR ENABLED
24 415V STNMN1AUXBCU DPI ACDB_INCOMER_2_CB POSITION
25 415V STNMN1AUXBCU CMD ACDB_INCOMER_2_CB COMMAND CLOSE / OPEN
26 415V STNMN1AUXBCU SPI ACDB_BUSCOPULER_CB_OPEN PERMITTED OR ENABLED
27 415V STNMN1AUXBCU SPI ACDB_BUSCOPULER_CB_CLOSE PERMITTED OR ENABLED
28 415V STNMN1AUXBCU DPI ACDB_BUSCOPULER_CB POSITION
29 415V STNMN1AUXBCU CMD ACDB_BUSCOPULER_CB COMMAND CLOSE / OPEN
30 415V STNMN1AUXBCU SPI HVW_MOTOR_CB_OPEN PERMITTED OR ENABLED
31 415V STNMN1AUXBCU SPI HVW_MOTOR_CB_CLOSE PERMITTED OR ENABLED
32 415V STNMN1AUXBCU DPI HVW_MOTOR_CB_ POSITION
33 415V STNMN1AUXBCU CMD HVW_MOTOR_CB_ COMMAND CLOSE / OPEN
34 415V STNMN1AUXBCU SPI SEB_33kV_CB_OPEN PERMITTED OR ENABLED
35 415V STNMN1AUXBCU SPI SEB_33kV_CB_CLOSE PERMITTED OR ENABLED
36 415V STNMN1AUXBCU DPI SEB_33kV_CB_ POSITION
37 415V STNMN1AUXBCU CMD SEB_33kV_CB_ COMMAND CLOSE / OPEN
38 415V STNMN1AUXBCU SPI SEB_33kV_ISOLATOR_OPEN PERMITTED OR ENABLED
39 415V STNMN1AUXBCU SPI SEB_33kV_ISOLATOR_CLOSE PERMITTED OR ENABLED
40 415V STNMN1AUXBCU DPI SEB_33kV_ISOLATOR_ POSITION
41 415V STNMN1AUXBCU CMD SEB_33kV_ISOLATOR_ COMMAND CLOSE / OPEN
42 415V STNMN1AUXBCU SPI TERTIARY TRAFO_33kV_CB_OPEN PERMITTED OR ENABLED If the inputs taken in Respecetive ICT Protection/BCU these signals may be omitted.
43 415V STNMN1AUXBCU SPI TERTIARY TRAFO_33kV_CB_CLOSE PERMITTED OR ENABLED
44 415V STNMN1AUXBCU DPI TERTIARY TRAFO_33kV_CB_ POSITION
45 415V STNMN1AUXBCU CMD TERTIARY TRAFO_33kV_CB_ COMMAND
46 415V STNMN1AUXBCU SPI TERTIARY TRAFO_33kV_ISOLATOR_OPEN PERMITTED OR ENABLED
47 415V STNMN1AUXBCU SPI TERTIARY TRAFO_33kV_ISOLATOR_CLOSE PERMITTED OR ENABLED
48 415V STNMN1AUXBCU DPI TERTIARY TRAFO_33kV_ISOLATOR_ POSITION
49 415V STNMN1AUXBCU CMD TERTIARY TRAFO_33kV_ISOLATOR_ COMMAND
THE LOGICAL NODE INSTANCE NUMBER (SCSWIn/SCILOn) FOR BBREAKERS MAY BE ASSIGNED AS PER AVAILABILITY
50 415V STNMN1AUXBCU AI DG INCOMER CURRENT L1
51 415V STNMN1AUXBCU AI DG INCOMER CURRENT L2
52 415V STNMN1AUXBCU AI DG INCOMER CURRENT L3
53 415V STNMN1AUXBCU AI DG INCOMER VOLTAGE U12
54 415V STNMN1AUXBCU AI DG INCOMER VOLTAGE U23
55 415V STNMN1AUXBCU AI DG INCOMER VOLTAGE U31
56 415V STNMN1AUXBCU AI DG INCOMER ACTIVE POWER (P)
57 415V STNMN1AUXBCU AI DG INCOMER REACTIVE POWER (Q)
58 415V STNMN1AUXBCU AI DG INCOMER POWER FACTOR (PF)
59 415V STNMN1AUXBCU AI DG INCOMER FREQUENCY (HZ)
60 415V STNMN1AUXBCU AI MSB INCOMER-1 CURRENT L1
61 415V STNMN1AUXBCU AI MSB INCOMER-1 CURRENT L2
62 415V STNMN1AUXBCU AI MSB INCOMER-1 CURRENT L3
63 415V STNMN1AUXBCU AI MSB INCOMER-1 VOLTAGE U12
64 415V STNMN1AUXBCU AI MSB INCOMER-1 VOLTAGE U23
65 415V STNMN1AUXBCU AI MSB INCOMER-1 VOLTAGE U31
66 415V STNMN1AUXBCU AI MSB INCOMER-1 ACTIVE POWER (P)
67 415V STNMN1AUXBCU AI MSB INCOMER-1 REACTIVE POWER (Q)
68 415V STNMN1AUXBCU AI MSB INCOMER-1 POWER FACTOR (PF)
69 415V STNMN1AUXBCU AI MSB INCOMER-1 FREQUENCY (HZ)
70 415V STNMN1AUXBCU AI MSB INCOMER-2 CURRENT L1
71 415V STNMN1AUXBCU AI MSB INCOMER-2 CURRENT L2
72 415V STNMN1AUXBCU AI MSB INCOMER-2 CURRENT L3
73 415V STNMN1AUXBCU AI MSB INCOMER-2 VOLTAGE U12
74 415V STNMN1AUXBCU AI MSB INCOMER-2 VOLTAGE U23
75 415V STNMN1AUXBCU AI MSB INCOMER-2 VOLTAGE U31
76 415V STNMN1AUXBCU AI MSB INCOMER-2 ACTIVE POWER (P)
77 415V STNMN1AUXBCU AI MSB INCOMER-2 REACTIVE POWER (Q)
78 415V STNMN1AUXBCU AI MSB INCOMER-2 POWER FACTOR (PF)
79 415V STNMN1AUXBCU AI MSB INCOMER-2 FREQUENCY (HZ)
80 415V STNMN1AUXBCU AI 220V CHARGER 1 CURRENT
81 415V STNMN1AUXBCU AI 220V CHARGER 2 CURRENT
82 415V STNMN1AUXBCU AI 48V CHARGER 1 CURRENT
83 415V STNMN1AUXBCU AI 48V CHARGER 2 CURRENT
84 415V STNMN1AUXBCU AI 220V DCDB 1 VOLTAGE
85 415V STNMN1AUXBCU AI 220V DCDB 1 CURRENT
86 415V STNMN1AUXBCU AI 220V DCDB 2 VOLTAGE
87 415V STNMN1AUXBCU AI 220V DCDB 2 CURRENT
88 415V STNMN1AUXBCU AI 48V DCDB 1 VOLTAGE
89 415V STNMN1AUXBCU AI 48V DCDB 1 CURRENT
90 415V STNMN1AUXBCU AI 48V DCDB 2 VOLTAGE
91 415V STNMN1AUXBCU AI 48V DCDB 2 CURRENT
92 415V STNMN1AUXBCU SPI 220V CHARGER-1 ON FLOAT MODE
93 415V STNMN1AUXBCU SPI 220V CHARGER-1 ON BOAST MODE
94 415V STNMN1AUXBCU SPI 220V CHARGER 1 TROUBLE Y CLOSE / OPEN
95 415V STNMN1AUXBCU SPI 220V DCDB-1 EARTH FAULT OPTD Y
96 415V STNMN1AUXBCU SPI 220V CHARGER-2 ON FLOAT MODE
97 415V STNMN1AUXBCU SPI 220V CHARGER-2 ON BOAST MODE
98 415V STNMN1AUXBCU SPI 220V CHARGER 2 TROUBLE Y
99 415V STNMN1AUXBCU SPI 220V DCDB-2 EARTH FAULT OPTD Y
100 415V STNMN1AUXBCU SPI 48V CHARGER-1 ON FLOAT MODE CLOSE / OPEN
101 415V STNMN1AUXBCU SPI 48V CHARGER-1 ON BOAST MODE
102 415V STNMN1AUXBCU SPI 48V CHARGER 1 TROUBLE Y
103 415V STNMN1AUXBCU SPI 48V CHARGER-2 ON FLOAT MODE
104 415V STNMN1AUXBCU SPI 48V CHARGER-2 ON BOAST MODE CLOSE / OPEN
105 415V STNMN1AUXBCU SPI 48V CHARGER 2 TROUBLE Y
106 415V STNMN1AUXBCU SPI 415V INCOMER-1 UNDERVOLTAGE Y
107 415V STNMN1AUXBCU SPI 415V INCOMER-2 UNDERVOLTAGE Y CLOSE / OPEN
108 415V STNMN1AUXBCU SPI SEB TRAFO - BUCHHOLZ ALARM Y
109 415V STNMN1AUXBCU SPI SEB TRAFO - BUCHHOLZ TRIP Y
110 415V STNMN1AUXBCU SPI SEB TRAFO - WTI ALARM Y
111 415V STNMN1AUXBCU SPI SEB TRAFO - WTI TRIP Y
112 415V STNMN1AUXBCU SPI SEB TRAFO - OTI ALARM Y
113 415V STNMN1AUXBCU SPI SEB TRAFO - OTI TRIP Y
114 415V STNMN1AUXBCU SPI SEB TRAFO - PRD ALARM Y
115 415V STNMN1AUXBCU SPI SEB TRAFO - PRD TRIP Y
116 415V STNMN1AUXBCU SPI SEB 33KV_TC-1 FAULTY Y
117 415V STNMN1AUXBCU SPI SEB 33KV_TC-2 FAULTY Y
118 415V STNMN1AUXBCU SPI SEB 33kV PHASE OVERCURRENT START Y
119 415V STNMN1AUXBCU SPI SEB33kV PHASE OVERCURRENT TRIP Y
120 415V STNMN1AUXBCU SPI SEB 33kV PHASE EARTHFAULT START Y
121 415V STNMN1AUXBCU SPI SEB 33kV PHASE EARTHFAULT TRIP Y
122 415V STNMN1AUXBCU SPI SEB 33kV PHASE RESIDUAL OVERVOLTAGE START Y
123 415V STNMN1AUXBCU SPI SEB 33kV PHASE RESIDUAL OVERVOLTAGE TRIP Y
124 415V STNMN1AUXBCU SPI SEB 33kV 86 OPTD Y
125 415V STNMN1AUXBCU SPI SEB 33kV CB ASSOCIATED ALARMS Y
126 415V STNMN1AUXBCU SPI TERTIARY TRAFO - BUCHHOLZ ALARM Y If the inputs taken in Respecetive ICT Protection/BCU these signals may be omitted.
127 415V STNMN1AUXBCU SPI TERTIARY TRAFO - BUCHHOLZ TRIP Y
128 415V STNMN1AUXBCU SPI TERTIARY TRAFO - WTI ALARM Y
129 415V STNMN1AUXBCU SPI TERTIARY TRAFO - WTI TRIP Y
130 415V STNMN1AUXBCU SPI TERTIARY TRAFO - OTI ALARM Y
131 415V STNMN1AUXBCU SPI TERTIARY TRAFO - OTI TRIP Y
132 415V STNMN1AUXBCU SPI TERTIARY TRAFO - PRD ALARM Y
133 415V STNMN1AUXBCU SPI TERTIARY TRAFO - PRD TRIP Y
134 415V STNMN1AUXBCU SPI TERTIARY 33KV_TC-1 FAULTY Y
135 415V STNMN1AUXBCU SPI TERTIARY 33KV_TC-2 FAULTY Y
136 415V STNMN1AUXBCU SPI TERTIARY 33kV PHASE OVERCURRENT START Y
137 415V STNMN1AUXBCU SPI TERTIARY33kV PHASE OVERCURRENT TRIP Y
138 415V STNMN1AUXBCU SPI TERTIARY 33kV PHASE EARTHFAULT START Y
139 415V STNMN1AUXBCU SPI TERTIARY 33kV PHASE EARTHFAULT TRIP Y
140 415V STNMN1AUXBCU SPI TERTIARY 33kV PHASE RESIDUAL OVERVOLTAGE START Y
141 415V STNMN1AUXBCU SPI TERTIARY 33kV PHASE RESIDUAL OVERVOLTAGE TRIP Y
142 415V STNMN1AUXBCU SPI TERTIARY 33kV 86 OPTD Y
143 415V STNMN1AUXBCU SPI TERTIARY 33kV CB ASSOCIATED ALARMS Y
144 415V STNMN1AUXBCU SPI AUX INCOMER DC-1 FAULTY Y
145 415V STNMN1AUXBCU SPI AUX INCOMER DC-2 FAULTY Y
146 415V STNMN1AUXBCU SPI WATER STORAGE TANK-1 LEVEL LOW Y
147 415V STNMN1AUXBCU SPI WATER STORAGE TANK-2 LEVEL LOW Y
148 415V STNMN1AUXBCU SPI HVW MOTOR DRIVEN PUMP RUNNING
149 415V STNMN1AUXBCU SPI HVW MOTOR DRIVEN PUMP FAILS TO START Y
150 415V STNMN1AUXBCU SPI HVW MOTOR PUMP TRIP FEEDBACK Y
151 415V STNMN1AUXBCU SPI DIESEL ENGINE RUNNING
152 415V STNMN1AUXBCU SPI DIESEL ENGINE FAILS TO START Y
153 415V STNMN1AUXBCU SPI DIESEL ENGINE TANK LEVEL LOW Y
154 415V STNMN1AUXBCU SPI JOCKEY PUMP -1 RUNNING
155 415V STNMN1AUXBCU SPI JOCKEY PUMP -2 RUNNING
156 415V STNMN1AUXBCU SPI JOCKEY PUMP -1 FAILS TO START Y
157 415V STNMN1AUXBCU SPI JOCKEY PUMP -2 FAILS TO START Y
158 415V STNMN1AUXBCU SPI JOCKEY PUMP O/L TRIP Y
159 415V STNMN1AUXBCU SPI JOCKEY PUMP PANEL DC HEALTHY Y
160 415V STNMN1AUXBCU CMD HVW MOTORT START
161 415V STNMN1AUXBCU CMD HVW MOTORT STOP
162 415V STNMN1AUXBCU CMD DIESEL ENGINE START
163 415V STNMN1AUXBCU CMD DIESEL ENGINE STOP
164 415V STNMN1AUXBCU CMD JOCKEY PUMP-1 START
165 415V STNMN1AUXBCU CMD JOCKEY PUMP-1 STOP
166 415V STNMN1AUXBCU CMD JOCKEY PUMP-2 START
167 415V STNMN1AUXBCU CMD JOCKEY PUMP-2 STOP
168 415V STNMN1AUXBCU SPI FIRE IN ZONE -1 Y
169 415V STNMN1AUXBCU SPI FIRE IN ZONE -2 Y
170 415V STNMN1AUXBCU SPI FIRE IN ZONE -3 Y
171 415V STNMN1AUXBCU SPI FIRE IN ZONE -4 Y
172 415V STNMN1AUXBCU SPI FIRE IN ZONE -5 Y
173 415V STNMN1AUXBCU SPI FIRE IN ZONE -N Y
174 415V STNMN1AUXBCU SPI FIRE IN TRANSFORMER-1 Y If the inputs taken in Respecetive ICT Protection/BCU these signals may be omitted.
175 415V STNMN1AUXBCU SPI FIRE IN TRANSFORMER-2 Y
176 415V STNMN1AUXBCU SPI FIRE IN TRANSFORMER-N Y
177 415V STNMN1AUXBCU CMD DELUGE COMMAND TO TRANSFORMER-1
178 415V STNMN1AUXBCU CMD DELUGE COMMAND TO TRANSFORMER-2
179 415V STNMN1AUXBCU CMD DELUGE COMMAND TO TRANSFORMER-N
180 415V STNMN1AUXBCU SPI DG DIFFERENTIAL PROT TRIP Y
181 415V STNMN1AUXBCU SPI DG OC/EF PROT TRIP Y
182 415V STNMN1AUXBCU SPI DG FAIL TO START Y
183 415V STNMN1AUXBCU SPI ALTERNATOR ON
184 415V STNMN1AUXBCU SPI DG LUBE OIL LOW PRESSURE ALARM Y
185 415V STNMN1AUXBCU SPI HIGH WATER TEMP TRIP Y CLOSE / OPEN
186 415V STNMN1AUXBCU SPI ENGG. COM FAULT Y
187 415V STNMN1AUXBCU SPI LACK OF FUEL ALARM Y
188 415V STNMN1AUXBCU SPI DG CHARGER-1 ON
189 415V STNMN1AUXBCU SPI DG CHARGER-1 OFF Y CLOSE / OPEN
190 415V STNMN1AUXBCU SPI DG CHARGER-2 ON
191 415V STNMN1AUXBCU SPI DG CHARGER-2 OFF Y
192 415V STNMN1AUXBCU CMD DG START/STOP COMMAND CLOSE / OPEN
193 415V STNMN1AUXBCU SPI AUX INCOMER DC-1 FAULTY Y
194 415V STNMN1AUXBCU SPI AUX INCOMER DC-2 FAULTY Y
195 415V STNMN1AUXBCU SPI TIME SYNCHRONIZATION ERROR Y
196 415V STNMN1AUXBCU SPI BCU UNHEALTHY Y
197 415V STNMN1AUXBCU SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
198 415V STNMN1AUXBCU SPI RELAY IN TEST MODE Y
199 415V STNMN1AUXBCU SPI SETTINGS CHANGED Y
200 415V STNMN1AUXBCU SPI DR MEMMORY 80% FULL Y
201 415V STNMN1AUXBCU SPI SPARE ALARM-1 ** 20 nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
202 415V STNMN1AUXBCU SPI SPARE ALARM-2
203 415V STNMN1AUXBCU SPI SPARE ALARM-3
204 415V STNMN1AUXBCU SPI SPARE ALARM-4
205 415V STNMN1AUXBCU SPI SPARE ALARM-5
206 415V STNMN1AUXBCU SPI SPARE ALARM-6
207 415V STNMN1AUXBCU SPI SPARE ALARM-7
208 415V STNMN1AUXBCU SPI SPARE ALARM-8
209 415V STNMN1AUXBCU SPI SPARE ALARM-9
210 415V STNMN1AUXBCU SPI SPARE ALARM-10
211 415V STNMN1AUXBCU SPI SPARE ALARM-11
212 415V STNMN1AUXBCU SPI SPARE ALARM-12
213 415V STNMN1AUXBCU SPI SPARE ALARM-13
214 415V STNMN1AUXBCU SPI SPARE ALARM-14
215 415V STNMN1AUXBCU SPI SPARE ALARM-15
216 415V STNMN1AUXBCU SPI SPARE ALARM-16
217 415V STNMN1AUXBCU SPI SPARE ALARM-17
218 415V STNMN1AUXBCU SPI SPARE ALARM-18
219 415V STNMN1AUXBCU SPI SPARE ALARM-19
220 415V STNMN1AUXBCU SPI SPARE ALARM-20
ADDITIONAL SIGNAL FOR CB TROUBLE ETC AS PER SCHEME
** 20 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
GE Standard Signals for 220kV Level
Revision History
Rev.No Description of Remarks Date Remarks
02 Old Signal list --
03 1. Distance relay - Missing internal signals related to functions such as AR, Weak-infeed, SOTF. 2. Addition of Differential Protection signals 3. Addition of Transformer phase wise Mechanical tripping signals 4. Addition of Centralized Busbar protection related signals. 5. Addition of tertiary transformer related protection signals. 6. Addition of Backup impedance protection signals for ICT & Reactor. 7. Addition of Directional OC & EF protection signals for ICT. 8. Addition of Mechanical trippings & alarms associated with REF. 9. Addition of NGR associated protection & CB Alarms 10. Addition of De-centralised - Busbar protection signals 11. Addition of Breaker failure protection initiation & Re-trip signals in standalone & centralized busbar protection 12. Addition of BCU – AR associated internal signals, TC phase wise, CSD related alarms, Bay wise measurements 16.01.2024
REVISION 2- STANDARD SIGNAL LIST FOR GE
BAY NUMBERS ARE SYMBOLIC. FOLLOWING IEDS REPRESENT THE APPLICATIONS AS MENTIONED BELOW.
WORKSHEET NO. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 P741 IEC BB4_P741_87CUA BUSBAR PROTECTION(DISTRIBUTED) MAIN 1 RELAY FOR 400KV BHWD200BBM1 Where same IED protects both Bus 1 & 2
2 P741 IEC BB4_P741_87CUB BUSBAR PROTECTION(DISTRIBUTED) MAIN 2 RELAY FOR 400KV BHWD200BBM2 Where same IED protects both Bus 1 & 2
3 P743 IEC R208_P743_PU_A LINE PU-1 BHWD2XXM1PU Only if standalone reporting directly to HMI. Includes BFR related signals also
4 P743 IEC R208_P743_PU_B LINE PU-2 BHWD2XXM2PU Only if standalone reporting directly to HMI. Includes BFR related signals also
5 P743 IEC R201_P743_PU_A ICT PU-1 BHWD2XXM2PU Only if standalone reporting directly to HMI. Includes BFR related signals also
6 P743 IEC R201_P743_PU_B ICT PU-2 BHWD2XXM2PU Only if standalone reporting directly to HMI. Includes BFR related signals also
7 B90 IEC BB4_B90_87 BUSBAR PROTECTION(CENTRALIZIED) MAIN RELAY FOR 400KV BHWD400BB1M1 Where same IED protects both Bus 1 & 2
8 P444 IEC R203_P444_21M1 LINE DISTANCE RELAY MAIN-1 BHWD2XXM1DIS Bay No. 2XX will be always the main bay number for the Line feeder
9 P546 IEC R201_P546_21M2 LINE DIFFERENTIAL RELAY MAIN-2 BHWD4XXM2DIS Bay No. 4XX will be always the main bay number for the Line feeder
11 P643 IEC R207_P643_87T ICT DIFFERENTIAL RELAY BHWD4XXTDIF Bay No. 4XX will be always the main bay number for the ICT feeder
12 P643 IEC R207_P643_64T ICT REF RELAY BHWD4XXTREF Bay No. 4XX will be always the main bay number for the ICT feeder
13 P442 IEC R207_P442_21R ICT BACKUP IMPEDNACE BHWD4XXTBU Bay No. 4XX will be always the main bay number for the ICT feeder
14 P643 IEC R212_P643_87R REACTOR DIFFERENTIAL RELAY BHWD4XXBRDIF Bay No. 4XX will be always the main bay number for the Bus Reactor feeder. BR for Bus Reactor & LR for Line reactor
15 P141 IEC R212_P141_64R REACTOR REF RELAY BHWD4XXBRREF Bay No. 4XX will be always the main bay number for the Bus Reactor feeder. BR for Bus Reactor & LR for Line reactor
16 P442 IEC R212_P442_21R REACTOR BACKUP IMPEDANCE RELAY BHWD4XXBRBU Bay No. 4XX will be always the main bay number for the Bus Reactor feeder. BR for Bus Reactor & LR for Line reactor
17 BCU BCU_201_LINE/ICT BCU BHWD2XXBCU BCU is for each bay so 2XX refers to Bay
** PLEASE NOTE THAT ALL BCU SHOULD HAVE TIME SYNC SIGNAL. HERE THEY ARE MENTIONED IN SEPARATE SHEET.
** The code BHWD in the IED name will be provided by POWERGRID for each substation that will be unique for database management.2XX refers to the bay.
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name BB4_P741_87CUA GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : BB4_P741_87CUA
DIGITAL INFORMATION FROM IED IED name BB4_P741_87CUA
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 200KV BB4_P741_87CUA PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 200KV BB4_P741_87CUA PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUA PROTECTION ZONE-1 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 1 Transmitted to IEC System;GosGGIO2 ST;Ind5;stVal;SPS None Yes 1 0
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUA PROTECTION ZONE-2 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 2 Transmitted to IEC System;GosGGIO2 ST;Ind6;stVal;SPS None Yes 1 0
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUA PROTECTION ZONE-3 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 3 Transmitted to IEC System;GosGGIO2 ST;Ind6;stVal;SPS None Yes 1 0
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUA PROTECTION ZONE-1 BUSBAR BLOCKED Set Reset RS_ST_BB BLOCK 1 Transmitted to IEC System;GosGGIO2 ST;Indxx;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUA PROTECTION ZONE-2 BUSBAR BLOCKED Set Reset RS_ST_BB BLOCK 2 Transmitted to IEC System;GosGGIO2 ST;Indxx;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUA PROTECTION ZONE-3 BUSBAR BLOCKED Set Reset RS_ST_BB BLOCK 3 Transmitted to IEC System;GosGGIO2 ST;Indxx;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUA PROTECTION Z1 BUSBAR BLOCKED DUE TO COMM. ERR Set Reset RS_ST_BB BLOCKC1 Transmitted to IEC System;GosGGIO2 ST;Ind7;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUA PROTECTION Z2 BUSBAR BLOCKED DUE TO COMM. ERR Set Reset RS_ST_BB BLOCKC2 Transmitted to IEC System;GosGGIO2 ST;Ind8;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUA PROTECTION Z3 BUSBAR BLOCKED DUE TO COMM. ERR Set Reset RS_ST_BB BLOCKC3 Transmitted to IEC System;GosGGIO2 ST;Ind8;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUA PROTECTION ZONE-1 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI1 Transmitted to IEC System;GosGGIO2 ST;Ind9;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUA PROTECTION ZONE-2 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI2 Transmitted to IEC System;GosGGIO2 ST;Ind10;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUA PROTECTION ZONE-3 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI3 Transmitted to IEC System;GosGGIO2 ST;Ind10;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLa_Reset_In SPS 200KV BB4_P741_87CUA SYSTEM MAIN-1 B/B ZONE-1 In Reset RS_IN_M1 BB Z1 Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 200KV BB4_P741_87CUA SYSTEM 87CUB RELAY Healthy Unhealthy UH_HL_87CUB Transmitted to IEC System;OptGGIO1 ST;Ind3;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 200KV BB4_P741_87CUA SYSTEM BBMT2 RELAY Healthy Unhealthy UH_HL_BBMT2 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLa_Reset_In SPS 200KV BB4_P741_87CUA SYSTEM MAIN-1 B/B ZONE-2 In Reset RS_IN_M1 BB Z2 Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A Protection;CftPhsPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV BB4_P741_87CUA PROTECTION ZONE-1 CIRCUITRY FAULT Operated Reset RS_OP_ZONE1 CFT Transmitted to IEC Protection;CftPhsPDIF1 ST;Op;general;general;ACT None 1 #REF!
A Protection;CftPhsPDIF2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV BB4_P741_87CUA PROTECTION ZONE-2 CIRCUITRY FAULT Operated Reset RS_OP_ZONE2 CFT Transmitted to IEC Protection;CftPhsPDIF2 ST;Op;general;general;ACT None 1 #REF!
A Protection;CftPhsPDIF2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV BB4_P741_87CUA PROTECTION ZONE-3 CIRCUITRY FAULT Operated Reset RS_OP_ZONE3 CFT Transmitted to IEC Protection;CftPhsPDIF2 ST;Op;general;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 200KV BB4_P741_87CUA PROTECTION B/B ZONE-1 TRIP Operated Reset RS_OP_ZONE1 Transmitted to IEC Protection;TrpPhsPDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 200KV BB4_P741_87CUA PROTECTION B/B ZONE-2 TRIP Operated Reset RS_OP_ZONE2 Transmitted to IEC Protection;TrpPhsPDIF2 ST;Op;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 200KV BB4_P741_87CUA PROTECTION B/B ZONE-3 TRIP Operated Reset RS_OP_ZONE3 Transmitted to IEC Protection;TrpPhsPDIF2 ST;Op;general;ACT None 1 #REF!
SPS 200KV BB4_P741_87CUA PROTECTION ZONE MERGE Set Reset RS_ST_ZONE_MRG
SPS 200KV BB4_P741_87CUA PROTECTION BUSBAR ZONE 1 R- PHASE TRIP Operated Reset RS_OP_ZONE1_R Protection;TrpPhsPDIF1 ST;Op;phs1
SPS 200KV BB4_P741_87CUA PROTECTION BUSBAR ZONE 1 Y- PHASE TRIP Operated Reset RS_OP_ZONE1_Y Protection;TrpPhsPDIF1 ST;Op;phs2
SPS 200KV BB4_P741_87CUA PROTECTION BUSBAR ZONE 1 B- PHASE TRIP Operated Reset RS_OP_ZONE1_B Protection;TrpPhsPDIF1 ST;Op;phs3
SPS 200KV BB4_P741_87CUA PROTECTION BUSBAR ZONE 2 R- PHASE TRIP Operated Reset RS_OP_ZONE2_R Protection;TrpPhsPDIF2 ST;Op;phs1
SPS 200KV BB4_P741_87CUA PROTECTION BUSBAR ZONE 2 Y- PHASE TRIP Operated Reset RS_OP_ZONE2_Y Protection;TrpPhsPDIF2 ST;Op;phs2
SPS 200KV BB4_P741_87CUA PROTECTION BUSBAR ZONE 2 B- PHASE TRIP Operated Reset RS_OP_ZONE2_B Protection;TrpPhsPDIF2 ST;Op;phs3
SPS 200KV BB4_P741_87CUA PROTECTION BUSBAR ZONE 3 R- PHASE TRIP Operated Reset RS_OP_ZONE3_R Protection;TrpPhsPDIF2 ST;Op;phs1
SPS 200KV BB4_P741_87CUA PROTECTION BUSBAR ZONE 3 Y- PHASE TRIP Operated Reset RS_OP_ZONE3_Y Protection;TrpPhsPDIF2 ST;Op;phs2
SPS 200KV BB4_P741_87CUA PROTECTION BUSBAR ZONE 3 B- PHASE TRIP Operated Reset RS_OP_ZONE3_B Protection;TrpPhsPDIF2 ST;Op;phs3
A SPARE SPS 200KV BB4_P741_87CUA PROTECTION CHECK ZONE Operated Reset RS_OP_CHECKZONE None No 1 #REF!
DIGITAL INFORMATION TO IED 200KV BB4_P741_87CUA
Iss. Customer Ref IED DO Reference Electrical Data 200KV Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) 200KV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 200KV 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 200KV 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 200KV 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 200KV 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 200KV 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 200KV 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 200KV 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 200KV 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 200KV 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 200KV 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
ANALOG INFORMATION FROM IED 200KV BB4_P741_87CUA
Iss. Customer Ref IED AI Reference Electrical Data 200KV Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit 200KV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 200KV Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUA
A SPARE 200KV Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUA
A SPARE 200KV Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUA
A SPARE 200KV Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUA
ANALOG INFORMATION TO IED 200KV BB4_P741_87CUA
Iss. Customer Ref IED AI Reference Electrical Data 200KV Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit 200KV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 200KV 13 ANALOG INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE 200KV 13 ANALOG INFORMATION TO IED IED name BB4_P741_87CUA
COUNTER INFORMATION FROM IED 200KV BB4_P741_87CUA
Iss. Customer Ref IED Counter Reference Electrical Data 200KV Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit 200KV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 200KV Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUA
A SPARE 200KV Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUA
A SPARE 200KV Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUA
A SPARE 200KV Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUA
END OF IED DATA 200KV
DI GROUPS 200KV
Iss. Customer Ref Group DI Reference Electrical Data 200KV Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) 200KV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200KV None No 1 C264 DI GROUPS
A 2 SPARE SPS 200KV None No 1 C264 DI GROUPS
A 3 SPARE SPS 200KV None No 1 C264 DI GROUPS
A 4 SPARE SPS 200KV None No 1 C264 DI GROUPS
A 5 SPARE SPS 200KV None No 1 C264 DI GROUPS
A 6 SPARE SPS 200KV None No 1 C264 DI GROUPS
A 7 SPARE SPS 200KV None No 1 C264 DI GROUPS
A 8 SPARE SPS 200KV None No 1 C264 DI GROUPS
A 9 SPARE SPS 200KV None No 1 C264 DI GROUPS
A 10 SPARE SPS 200KV None No 1 C264 DI GROUPS
A 11 SPARE SPS 200KV None No 1 C264 DI GROUPS
A 12 SPARE SPS 200KV None No 1 C264 DI GROUPS
A 13 SPARE SPS 200KV None No 1 C264 DI GROUPS
A 14 SPARE SPS 200KV None No 1 C264 DI GROUPS
A 15 SPARE SPS 200KV None No 1 C264 DI GROUPS
A 16 SPARE SPS 200KV None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION 200KV
Iss. Customer Ref Self DI Reference Electrical Data 200KV Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) 200KV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS 200KV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION 200KV
Iss. Customer Ref Self DO Reference Electrical Data 200KV Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) 200KV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC 200KV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC 200KV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC 200KV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC 200KV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC 200KV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC 200KV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC 200KV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC 200KV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC 200KV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC 200KV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION 200KV
Iss. Customer Ref Self AI Reference Electrical Data 200KV Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit 200KV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE 200KV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION 200KV
Iss. Customer Ref Self Counter Reference Electrical Data 200KV Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit 200KV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE 200KV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION 200KV
Iss. Customer Ref SetPoint Reference Electrical Data 200KV Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit 200KV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE 200KV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name BB4_P741_87CUB GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : BB4_P741_87CUB
DIGITAL INFORMATION FROM IED IED name BB4_P741_87CUB
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 200KV BB4_P741_87CUB PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name BB4_P741_87CUB
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 200KV BB4_P741_87CUB PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUB PROTECTION ZONE-1 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 1 Transmitted to IEC System;GosGGIO2 ST;Ind5;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUB PROTECTION ZONE-2 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 2 Transmitted to IEC System;GosGGIO2 ST;Ind6;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUB PROTECTION ZONE-3 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 3 Transmitted to IEC System;GosGGIO2 ST;Ind6;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUB PROTECTION ZONE-1 BUSBAR BLOCKED Set Reset RS_ST_BB BLOCK 1 Transmitted to IEC System;GosGGIO2 ST;Indxx;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUB PROTECTION ZONE-2 BUSBAR BLOCKED Set Reset RS_ST_BB BLOCK 2 Transmitted to IEC System;GosGGIO2 ST;Indxx;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUB PROTECTION ZONE-3 BUSBAR BLOCKED Set Reset RS_ST_BB BLOCK 3 Transmitted to IEC System;GosGGIO2 ST;Indxx;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_P741_87CUB PROTECTION Z1 BUSBAR BLOCKED DUE TO COMM. ERR Set Reset RS_ST_BB BLOCKC1 Transmitted to IEC System;GosGGIO2 ST;Ind7;stVal;SPS None Yes 1 #REF!
SPS 200KV BB4_P741_87CUB PROTECTION Z2 BUSBAR BLOCKED DUE TO COMM. ERR Set Reset RS_ST_BB BLOCKC2 Transmitted to IEC System;GosGGIO2 ST;Ind8;stVal;SPS
SPS 200KV BB4_P741_87CUB PROTECTION Z3 BUSBAR BLOCKED DUE TO COMM. ERR Set Reset RS_ST_BB BLOCKC3 Transmitted to IEC System;GosGGIO2 ST;Ind8;stVal;SPS
SPS 200KV BB4_P741_87CUB PROTECTION ZONE-1 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI1 Transmitted to IEC System;GosGGIO2 ST;Ind9;stVal;SPS
SPS 200KV BB4_P741_87CUB PROTECTION ZONE-2 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI2 Transmitted to IEC System;GosGGIO2 ST;Ind10;stVal;SPS
SPS 200KV BB4_P741_87CUB PROTECTION ZONE-3 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI3 Transmitted to IEC System;GosGGIO2 ST;Ind10;stVal;SPS
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLa_Reset_In SPS 200KV BB4_P741_87CUB SYSTEM MAIN-1 B/B ZONE-1 In Reset RS_IN_M2 BB Z1 Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 200KV BB4_P741_87CUB SYSTEM 87CUA RELAY Healthy Unhealthy UH_HL_87CUA Transmitted to IEC System;OptGGIO1 ST;Ind3;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 200KV BB4_P741_87CUB SYSTEM BBMT2 RELAY Healthy Unhealthy UH_HL_BBMT1 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLa_Reset_In SPS 200KV BB4_P741_87CUB SYSTEM MAIN-1 B/B ZONE-2 In Reset RS_IN_M2 BB Z2 Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A Protection;CftPhsPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV BB4_P741_87CUB PROTECTION ZONE-1 CIRCUITRY FAULT Operated Reset RS_OP_ZONE1 CFT Transmitted to IEC Protection;CftPhsPDIF1 ST;Op;general;general;ACT None 1 #REF!
A Protection;CftPhsPDIF2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV BB4_P741_87CUB PROTECTION ZONE-2 CIRCUITRY FAULT Operated Reset RS_OP_ZONE2 CFT Transmitted to IEC Protection;CftPhsPDIF2 ST;Op;general;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 200KV BB4_P741_87CUB PROTECTION B/B ZONE-1 TRIP Operated Reset RS_OP_ZONE1 Transmitted to IEC Protection;TrpPhsPDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 200KV BB4_P741_87CUB PROTECTION B/B ZONE-2 TRIP Operated Reset RS_OP_ZONE2 Transmitted to IEC Protection;TrpPhsPDIF2 ST;Op;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 200KV BB4_P741_87CUB PROTECTION B/B ZONE-3 TRIP Operated Reset RS_OP_ZONE3 Transmitted to IEC Protection;TrpPhsPDIF2 ST;Op;general;ACT None 1 #REF!
SPS 200KV BB4_P741_87CUB PROTECTION ZONE MERGE (IF APPLICABLE ) Set Reset RS_ST_ZONE_MRG
SPS 200KV BB4_P741_87CUB PROTECTION BUSBAR ZONE 1 R- PHASE TRIP Operated Reset RS_OP_ZONE1_R Protection;TrpPhsPDIF1 ST;Op;phs1
SPS 200KV BB4_P741_87CUB PROTECTION BUSBAR ZONE 1 Y- PHASE TRIP Operated Reset RS_OP_ZONE1_Y Protection;TrpPhsPDIF1 ST;Op;phs2
SPS 200KV BB4_P741_87CUB PROTECTION BUSBAR ZONE 1 B- PHASE TRIP Operated Reset RS_OP_ZONE1_B Protection;TrpPhsPDIF1 ST;Op;phs3
SPS 200KV BB4_P741_87CUB PROTECTION BUSBAR ZONE 2 R- PHASE TRIP Operated Reset RS_OP_ZONE2_R Protection;TrpPhsPDIF2 ST;Op;phs1
SPS 200KV BB4_P741_87CUB PROTECTION BUSBAR ZONE 2 Y- PHASE TRIP Operated Reset RS_OP_ZONE2_Y Protection;TrpPhsPDIF2 ST;Op;phs2
SPS 200KV BB4_P741_87CUB PROTECTION BUSBAR ZONE 2 B- PHASE TRIP Operated Reset RS_OP_ZONE2_B Protection;TrpPhsPDIF2 ST;Op;phs3
SPS 200KV BB4_P741_87CUA PROTECTION BUSBAR ZONE 3 R- PHASE TRIP Operated Reset RS_OP_ZONE3_R Protection;TrpPhsPDIF2 ST;Op;phs1
SPS 200KV BB4_P741_87CUA PROTECTION BUSBAR ZONE 3 Y- PHASE TRIP Operated Reset RS_OP_ZONE3_Y Protection;TrpPhsPDIF2 ST;Op;phs2
SPS 200KV BB4_P741_87CUA PROTECTION BUSBAR ZONE 3 B- PHASE TRIP Operated Reset RS_OP_ZONE3_B Protection;TrpPhsPDIF2 ST;Op;phs3
SPS 200KV BB4_P741_87CUB PROTECTION CHECK ZONE Operated Reset RS_OP_CHECKZONE
DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
ANALOG INFORMATION FROM IED IED name BB4_P741_87CUB
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUB
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUB
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUB
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUB
ANALOG INFORMATION TO IED IED name BB4_P741_87CUB
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE 13 ANALOG INFORMATION TO IED IED name BB4_P741_87CUB
COUNTER INFORMATION FROM IED IED name BB4_P741_87CUB
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUB
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUB
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUB
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUB
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R208_P743_PU GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
IED NAME : R208_P743_PU
DIGITAL INFORMATION FROM IED IED name R208_P743_PU
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R209_P743_PU_A PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R208_P743_PU
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R209_P743_PU_A PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R208_P743_PU
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLa_Reset_Close SPS 220kV R209_P743_PU_A PROTECTION CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF1 ST;OpIn;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R208_P743_PU
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 220kV R209_P743_PU_A PROTECTION CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF2 ST;OpEx;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R208_P743_PU
A SPARE SPS 220kV R209_P743_PU_A PROTECTION EXTERNAL CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S3 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT None No 1 #REF!
A SPARE SPS 220kV R209_P743_PU_A PROTECTION EXTERNAL CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S4 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT None No 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 220kV R209_P743_PU_A SYSTEM LBB INITIATION 3-PH Set Reset RS_OP_LBB INI 3P System;OptGGIO1 ST;Ind3;stVal;SPS None 1 #REF!
SPS 220kV R209_P743_PU_A SYSTEM LBB INITIATION R-PH Set Reset RS_OP_LBB INI B System;OptGGIO1 ST;Ind4;stVal;SPS
A SPARE SPS 220kV R209_P743_PU_A SYSTEM LBB INITIATION Y-PH Set Reset RS_OP_LBB INI R System;OptGGIO1 ST;Ind5;stVal;SPS None No 1 0
A SPARE SPS 220kV R209_P743_PU_A SYSTEM LBB INITIATION B-PH Set Reset RS_OP_LBB INI Y System;OptGGIO1 ST;Ind6;stVal;SPS None No 1 0
A SPARE SPS 220kV R209_P743_PU_A SYSTEM B/B PU-B HEALTHY Healthy Unhealthy UN_HL_BB_PU B None No 1 0
A SPARE SPS None No 1 0
A SPARE SPS None No 1 0
A SPARE SPS None No 1 0
DIGITAL INFORMATION TO IED IED name R208_P743_PU
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R208_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R208_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R208_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R208_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R208_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R208_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R208_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R208_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R208_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R208_P743_PU
ANALOG INFORMATION FROM IED IED name R208_P743_PU
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R208_P743_PU
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R208_P743_PU
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R208_P743_PU
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R208_P743_PU
ANALOG INFORMATION TO IED IED name R208_P743_PU
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R208_P743_PU
A SPARE 13 ANALOG INFORMATION TO IED IED name R208_P743_PU
COUNTER INFORMATION FROM IED IED name R208_P743_PU
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R208_P743_PU
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R208_P743_PU
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R208_P743_PU
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R208_P743_PU
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R209_P743_PU GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
IED NAME : R209_P743_PU
DIGITAL INFORMATION FROM IED IED name R209_P743_PU
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R209_P743_PU_B PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R209_P743_PU
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R209_P743_PU_B PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R209_P743_PU
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLa_Reset_Close SPS 220kV R209_P743_PU_B PROTECTION CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF1 ST;OpIn;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R209_P743_PU
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 220kV R209_P743_PU_B PROTECTION CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF2 ST;OpEx;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R209_P743_PU
A SPARE SPS 220kV R209_P743_PU_B PROTECTION EXTERNAL CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S3 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT None No 1 #REF!
A SPARE SPS 220kV R209_P743_PU_B PROTECTION EXTERNAL CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S4 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT None No 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 220kV R209_P743_PU_B SYSTEM LBB INITIATION 3-PH Set Reset RS_OP_LBB INI 3P System;OptGGIO1 ST;Ind3;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLa_Reset_Close SPS 220kV R209_P743_PU_B SYSTEM LBB INITIATION R-PH Set Reset RS_OP_LBB INI B System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 220kV R209_P743_PU_B SYSTEM LBB INITIATION Y-PH Set Reset RS_OP_LBB INI R System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLa_Reset_Close SPS 220kV R209_P743_PU_B SYSTEM LBB INITIATION B-PH Set Reset RS_OP_LBB INI Y System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind14;stVal;SPS SPE_HLA_Reset_Optd SPS 220kV R209_P743_PU_B SYSTEM B/B PU-A HEALTHY Healthy Unhealthy UN_HL_BB_PU A None 1 #REF!
A SPARE SPS None No 1 #REF!
A SPARE SPS None No 1 #REF!
A SPARE SPS None No 1 #REF!
A SPARE SPS None No 1 #REF!
A SPARE SPS None No 1 #REF!
A SPARE SPS None No 1 #REF!
DIGITAL INFORMATION TO IED IED name R209_P743_PU
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R209_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R209_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R209_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R209_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R209_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R209_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R209_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R209_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R209_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R209_P743_PU
ANALOG INFORMATION FROM IED IED name R209_P743_PU
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R209_P743_PU
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R209_P743_PU
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R209_P743_PU
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R209_P743_PU
ANALOG INFORMATION TO IED IED name R209_P743_PU
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R209_P743_PU
A SPARE 13 ANALOG INFORMATION TO IED IED name R209_P743_PU
COUNTER INFORMATION FROM IED IED name R209_P743_PU
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R209_P743_PU
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R209_P743_PU
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R209_P743_PU
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R209_P743_PU
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R201_P743_PU GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
IED NAME : R201_P743_PU
DIGITAL INFORMATION FROM IED IED name R201_P743_PU
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R209_P743_PU_A PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R201_P743_PU
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R209_P743_PU_A PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R201_P743_PU
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 220kV R209_P743_PU_A PROTECTION CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF1 ST;OpIn;general;ACT None 1 #REF!
A SPARE SPS 220kV R209_P743_PU_A PROTECTION CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF2 ST;OpEx;general;ACT None No 1 #REF!
A SPARE SPS 220kV R209_P743_PU_A PROTECTION EXTERNAL CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S3 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT None No 1 #REF!
A SPARE SPS 220kV R209_P743_PU_A PROTECTION EXTERNAL CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S4 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT None No 1 #REF!
A SPARE SPS 220kV R209_P743_PU_A SYSTEM LBB INITIATION 3-PH Set Reset RS_OP_LBB INI 3P System;OptGGIO1 ST;Ind3;stVal;SPS None No 1 #REF!
SPS 220kV R209_P743_PU_A SYSTEM B/B PU-B HEALTHY Healthy Unhealthy UN_HL_BB_PU B
A SPARE None No 1 #REF!
SPS 220kV R203_P743_PU SYSTEM LBB INITIATION B-PH Set Reset RS_OP_LBB INI Y System;OptGGIO1 ST;Ind6;stVal;SPS
DIGITAL INFORMATION TO IED IED name R201_P743_PU
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R201_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R201_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R201_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R201_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R201_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R201_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R201_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R201_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R201_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R201_P743_PU
ANALOG INFORMATION FROM IED IED name R201_P743_PU
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R201_P743_PU
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R201_P743_PU
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R201_P743_PU
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R201_P743_PU
ANALOG INFORMATION TO IED IED name R201_P743_PU
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R201_P743_PU
A SPARE 13 ANALOG INFORMATION TO IED IED name R201_P743_PU
COUNTER INFORMATION FROM IED IED name R201_P743_PU
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R201_P743_PU
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R201_P743_PU
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R201_P743_PU
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R201_P743_PU
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A SPARE None No 1 0
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R203_P743_PU GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
IED NAME : R203_P743_PU
DIGITAL INFORMATION FROM IED IED name R203_P743_PU
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R209_P743_PU_B PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R203_P743_PU
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R209_P743_PU_B PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 220kV R209_P743_PU_B PROTECTION CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF1 ST;OpIn;general;ACT None 1 #REF!
A SPARE SPS 220kV R209_P743_PU_B PROTECTION CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF2 ST;OpEx;general;ACT None No 1 #REF!
A SPARE SPS 220kV R209_P743_PU_B PROTECTION EXTERNAL CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S3 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT None No 1 #REF!
A SPARE SPS 220kV R209_P743_PU_B PROTECTION EXTERNAL CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S4 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT None No 1 #REF!
A SPARE SPS 220kV R209_P743_PU_B SYSTEM LBB INITIATION 3-PH Set Reset RS_OP_LBB INI 3P System;OptGGIO1 ST;Ind3;stVal;SPS None No 1 #REF!
SPS 220kV R209_P743_PU_B SYSTEM B/B PU-A HEALTHY Healthy Unhealthy UN_HL_BB_PU A
DIGITAL INFORMATION TO IED IED name R203_P743_PU
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R203_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R203_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R203_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R203_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R203_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R203_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R203_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R203_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R203_P743_PU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R203_P743_PU
ANALOG INFORMATION FROM IED IED name R203_P743_PU
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R203_P743_PU
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R203_P743_PU
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R203_P743_PU
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R203_P743_PU
ANALOG INFORMATION TO IED IED name R203_P743_PU
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R203_P743_PU
A SPARE 13 ANALOG INFORMATION TO IED IED name R203_P743_PU
COUNTER INFORMATION FROM IED IED name R203_P743_PU
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R203_P743_PU
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R203_P743_PU
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R203_P743_PU
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R203_P743_PU
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 CCCC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : Site Name
IEC Description
Computer Name 7BB1_P747_87_R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
IED NAME : 7BB1_P747_87_R
DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 200KV BB4_B90_87 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_R
SPS 200KV BB4_B90_87 PROTECTION ZONE-1 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind3;stVal;SPS
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_B90_87 PROTECTION ZONE-2 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_R
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_B90_87 PROTECTION ZONE-3 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 0
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLA_Normal_Alarm SPS 200KV BB4_B90_87 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind6;stVal;SPS None Yes 1 #REF!
SPS 200KV BB4_B90_87 PROTECTION ZONE-1 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind7;stVal;SPS
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_B90_87 PROTECTION ZONE-2 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind8;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_B90_87 PROTECTION ZONE-3 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind8;stVal;SPS None Yes 1 0
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV BB4_B90_87 SYSTEM BAY 425 LBB Operated Reset RS_OP 425 LBB System;OptGGIO1 ST;Ind2;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV BB4_B90_87 SYSTEM BAY 428 LBB Operated Reset RS_OP 428 LBB System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV BB4_B90_87 SYSTEM BAY 426 LBB Operated Reset RS_OP 426 LBB System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind25;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_B90_87 SYSTEM ZONE-1 MAIN-1 SWITCH IN Set Reset RS_ST Z-1 IN System;OptGGIO1 ST;Ind25;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind27;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 200KV BB4_B90_87 SYSTEM BB M2 RELAY R-PH Healthy Unhealthy UH_HL BB M2 RLY System;OptGGIO1 ST;Ind27;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind29;stVal;SPS SPE_HLa_Reset_Set SPS 200KV BB4_B90_87 SYSTEM ZONE-2 MAIN-1 SWITCH IN Set Reset RS_ST Z-2 IN System;OptGGIO1 ST;Ind29;stVal;SPS None 1 #REF!
A Protection;CznPDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 200KV BB4_B90_87 PROTECTION CHECK ZONE DIFF PROT Operated Reset RS_OP_CHK ZONE Protection;CznPDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;BbpT01PDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 200KV BB4_B90_87 PROTECTION BUSBAR ZONE1 TRIP Operated Reset RS_OP_BB ZONE1 Protection;BbpT01PDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;BbpT02PDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 200KV BB4_B90_87 PROTECTION BUSBAR ZONE2 TRIP Operated Reset RS_OP_BB ZONE2 Protection;BbpT02PDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;BbpT02PDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 200KV BB4_B90_87 PROTECTION BUSBAR ZONE3 TRIP Operated Reset RS_OP_BB ZONE3 Protection;BbpT02PDIF1 ST;Op;general;ACT None 1 #REF!
SPS 200KV BB4_B90_87 PROTECTION BUSBAR ZONE 1 PROTECTION BLOCKED Set Reset RS_ST_BB BLK Z1
SPS 200KV BB4_B90_87 PROTECTION BUSBAR ZONE 2 PROTECTION BLOCKED Set Reset RS_ST_BB BLK Z2
SPS 200KV BB4_B90_87 PROTECTION BUSBAR ZONE 3 PROTECTION BLOCKED Set Reset RS_ST_BB BLK Z3
A SPARE SPS 200KV BB4_B90_87 PROTECTION CHECK ZONE Operated Reset RS_OP_CHECKZONE None No 1 0
DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
ANALOG INFORMATION TO IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_R
COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R203_P444_21M1 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R203_P444_21M1
DIGITAL INFORMATION FROM IED IED name R203_P444_21M1
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R203_P444_21M1 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R203_P444_21M1
A System;AlmGGIO1 ST;Alm6;stVal;SPS SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION CVT FUSE FAIL Alarm Normal RS_OP_VT-FUSE Transmitted to IEC System;AlmGGIO1 ST;Alm6;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R203_P444_21M1
A System;AlmGGIO1 ST;Alm31;stVal;SPS SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION BROKEN CONDUCTOR Alarm Normal RS_OP_BRKN CND Transmitted to IEC System;AlmGGIO1 ST;Alm31;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R203_P444_21M1
A System;GosGGIO2 ST;Ind15;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R203_P444_21M1 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind15;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Nrml_Optd SPS 220kV R203_P444_21M1 SYSTEM 86A TRIP RELAY Operated Reset NM_OP_86A Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 220kV R203_P444_21M1 SYSTEM CARRIER CHANNEL-1 Healthy Unhealthy UL_HL_CARR_CH1 Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_NotRec_Recvd SPS 220kV R203_P444_21M1 SYSTEM CARRIER CHANNEL-2 Received Not Received NR_RC_CARR_CH2 Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 220kV R203_P444_21M1 SYSTEM MAIN-2 RELAY Healthy Unhealthy UL_HL_MAIN-2 Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_NotRec_Recvd SPS 220kV R203_P444_21M1 SYSTEM CARRIER CHANNEL-1 Received Not Received NR_RC_CARR_CH1 Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 220kV R203_P444_21M1 SYSTEM CARRIER CHANNEL-2 Healthy Unhealthy UL_HL_CARR_CH2 Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_NotRec_Recvd SPS 220kV R203_P444_21M1 SYSTEM DIRECT TRIP CHANNEL-1 Received Not Received NR_RC_DT_REV_CH1 Transmitted to IEC System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLA_NotRec_Recvd SPS 220kV R203_P444_21M1 SYSTEM DIRECT TRIP CHANNEL-2 Received Not Received NR_RC_DT_REV_CH2 Transmitted to IEC System;OptGGIO1 ST;Ind13;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind18;stVal;SPS SPE_HLA_Nrml_Optd SPS 220kV R203_P444_21M1 SYSTEM MAIN/TBC LBB Operated Normal NM_OP_M_T_LBB Transmitted to IEC System;OptGGIO1 ST;Ind18;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind22;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R203_P444_21M1 SYSTEM CB CLOSE FOR SOTF INITATION Set Reset NM_AL_SOTF Transmitted to IEC System;OptGGIO1 ST;Ind22;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind24;stVal;SPS SPE_HLa_Reset_Set SPS 220kV R203_P444_21M1 SYSTEM TRIP RELAY 86A SUPERVISION Healthy Unhealthy RS_ST_86A SUPV Transmitted to IEC System;OptGGIO1 ST;Ind24;stVal;SPS None 1 #REF!
A Control;PsbRPSB3 ST;Str;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION POWER SWING DETECTED Set Reset RS_AL_PSB_STR Transmitted to IEC Control;PsbRPSB3 ST;Str;general;ACD None 1 #REF!
A Control;PsbRPSB3 ST;BlkZn;stVal;SPS SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION POWER SWING BLOCKING Set Reset RS_OP_PWR SW BLK Transmitted to IEC Control;PsbRPSB3 ST;BlkZn;stVal;SPS None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE ZONE-1 R-PH Operated Reset RS_OP_Z1R-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE ZONE-1 Y-PH Operated Reset RS_OP_Z1Y-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE ZONE-1 B-PH Operated Reset RS_OP_Z1B-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE PROTN ZONE-1 Operated Reset RS_OP_ZONE-1 Transmitted to IEC Protection;DisPDIS1 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE ZONE-1 START Set Reset RS_OP_DIS S Z1 Transmitted to IEC Protection;DisPDIS1 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE PROTN ZONE-2 Operated Reset RS_OP_ZONE-2 Transmitted to IEC Protection;DisPDIS2 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsA;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE ZONE-2 START R-PH Set Reset RS_OP_DIS S Z2_R Transmitted to IEC Protection;DisPDIS2 ST;Str;phsA;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsB;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE ZONE-2 START Y-PH Set Reset RS_OP_DIS S Z2_Y Transmitted to IEC Protection;DisPDIS2 ST;Str;phsB;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsC;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE ZONE-2 START B-PH Set Reset RS_OP_DIS S Z2_B Transmitted to IEC Protection;DisPDIS2 ST;Str;phsC;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE ZONE-2 START Set Reset RS_OP_DIS S Z2 Transmitted to IEC Protection;DisPDIS2 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS3 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE PROTN ZONE-3 Operated Reset RS_OP_ZONE-3 Transmitted to IEC Protection;DisPDIS3 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS3 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE ZONE-3 START Set Reset RS_OP_DIS S Z3 Transmitted to IEC Protection;DisPDIS3 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS4 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE PROTN ZONE-4 Operated Reset RS_OP_ZONE-4 Transmitted to IEC Protection;DisPDIS4 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS4 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE ZONE-4 START Set Reset RS_OP_DIS S Z4 Transmitted to IEC Protection;DisPDIS4 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS5 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE PROTN ZONE-5 Operated Reset RS_OP_ZONE-5 Transmitted to IEC Protection;DisPDIS5 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS5 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE ZONE-5 START Set Reset RS_OP_DIS S Z5 Transmitted to IEC Protection;DisPDIS5 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPSCH1 ST;CarRx;general;ACT SPE_HLa_Reset_Set SPS 220kV R203_P444_21M1 PROTECTION CARRIER AIDED SCHEME Operated Reset RS_ST_CARR_AIDED Transmitted to IEC Protection;DisPSCH1 ST;CarRx;general;ACT None 1 #REF!
A Protection;DisPSCH1 ST;ProRx;stVal;SPS SPE_HLa_Reset_Set SPS 220kV R203_P444_21M1 PROTECTION CARRIER RECEIVE Set Reset RS_ST_CARR REC Transmitted to IEC Protection;DisPSCH1 ST;ProRx;stVal;SPS None 1 #REF!
A Protection;DisPSCH1 ST;ProTx;stVal;SPS SPE_HLa_Reset_Set SPS 220kV R203_P444_21M1 PROTECTION CARRIER SEND Set Reset RS_ST_CARR SEND Transmitted to IEC Protection;DisPSCH1 ST;ProTx;stVal;SPS None 1 #REF!
A Protection;EfdPTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DIRECTIONAL E/F START Set Reset RS_OP_DIR E/F S Transmitted to IEC Protection;EfdPTOC1 ST;Str;general;general;ACD None 1 #REF!
A Protection;EfdPTOC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DIRECTIONAL E/F Operated Reset RS_OP_DEF Transmitted to IEC Protection;EfdPTOC1 ST;Op;general;general;ACT None 1 #REF!
A Protection;SofPSOF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION SOTF Operated Reset RS_OP_SOTF Transmitted to IEC Protection;SofPSOF1 ST;Op;general;ACT None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION OVERVOLTAGE STAGE-1 Operated Reset RS_OP_O/V-I Transmitted to IEC Protection;VtpPhsPTOV1 ST;Op;general;ACT None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION OVERVOLTAGE STAGE-1 START Set Reset RS_OP_O/V STG1 S Transmitted to IEC Protection;VtpPhsPTOV1 ST;Str;general;general;ACD None 1 #REF!
A Protection;VtpPhsPTOV2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION OVERVOLTAGE STAGE-2 Operated Reset RS_OP_O/V-II Transmitted to IEC Protection;VtpPhsPTOV2 ST;Op;general;ACT None 1 #REF!
A SPARE SPS None No 1 #REF!
DIGITAL INFORMATION TO IED IED name R203_P444_21M1
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
A Protection;DisPDIS2 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE ZONE-2 R-PH Operated Reset RS_OP_Z1R-PH Transmitted to IEC Protection;DisPDIS2 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE ZONE-2 Y-PH Operated Reset RS_OP_Z1Y-PH Transmitted to IEC Protection;DisPDIS2 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_P444_21M1 PROTECTION DISTANCE ZONE-2 B-PH Operated Reset RS_OP_Z1B-PH Transmitted to IEC Protection;DisPDIS2 ST;Op;phsC;general;ACT None 1 #REF!
A SPARE SPS 220kV R203_P444_21M1 PROTECTION Distance Blocked Set Reset RS_ST_DIS BLK Protection;DisPDIS ST;BLK 2 #REF!
A SPARE SPS 220kV R203_P444_21M1 SYSTEM DT SEND CH 1 Set Reset RS_ST_DT_CH-1_S 2 #REF!
A SPARE SPS 220kV R203_P444_21M1 SYSTEM DT SEND CH 2 Set Reset RS_ST_DT_CH-2_S 2 #REF!
A SPARE SPS 220kV R203_P444_21M1 SYSTEM BCU RELAY Healthy Unhealthy RS_ST_BCU System;OptGGIO1 ST;Indx;stVal;SPS 2 #REF!
A SPARE SPS 220kV R203_P444_21M1 SYSTEM PREPARE 3-PH TRIP FROM TIE BCU Set Reset RS_ST_MAIN_3 PH System;OptGGIO1 ST;Indx;stVal;SPS 2 #REF!
A SPARE SPS 220kV R203_P444_21M1 SYSTEM PREPARE 3-PH TRIP FROM MAIN BCU Set Reset RS_ST_TIE_3 PH System;OptGGIO1 ST;Indx;stVal;SPS 2 #REF!
A SPARE SPS 220kV R203_P444_21M1 SYSTEM MAIN/ TBC CB AR OPTD Operated Reset RS_OP_A/R System;OptGGIO1 ST;Indx;stVal;SPS 2 #REF!
SPS 220kV R203_P444_21M1 SYSTEM MAIN/ TBC LBB PROTECTION OPERATED Operated Reset RS_OP_LBB System;OptGGIO1 ST;Indx;stVal;SPS
ANALOG INFORMATION FROM IED SPC IED name R203_P444_21M1
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Records;PriRFLO1 MX;FltZ;cVal;CMV MV_hla_Fault_Impd Z 220kV R203_P444_21M1 PROTECTION FAULT IMPEDANCE -100.0 100.0 Fltz Transmitted to IEC Records;PriRFLO1 MX;FltZ;cVal;CMV 6 ANALOG INFORMATION FROM IED IED name R203_P444_21M1
A Records;PriRFLO1 MX;FltDiskm;mag;MV MV_Hla_Fault_Dist Km 220kV R203_P444_21M1 PROTECTION FAULT DISTANCE 0.0 1000.0 FltDiskm Transmitted to IEC Records;PriRFLO1 MX;FltDiskm;mag;MV 6 ANALOG INFORMATION FROM IED IED name R203_P444_21M1
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R203_P444_21M1
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R203_P444_21M1
ANALOG INFORMATION TO IED IED name R203_P444_21M1
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R203_P444_21M1
A SPARE 13 ANALOG INFORMATION TO IED IED name R203_P444_21M1
COUNTER INFORMATION FROM IED IED name R203_P444_21M1
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R203_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R203_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R203_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R203_P444_21M1
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R401_P546_21M2 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R401_P546_21M2
DIGITAL INFORMATION FROM IED IED name R401_P546_21M2
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 200KV R401_P546_21M2 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R401_P546_21M2
A System;AlmGGIO1 ST;Alm6;stVal;SPS SPE_HLA_Normal_Fail SPS 200KV R401_P546_21M2 PROTECTION CVT FUSE FAIL Alarm Normal NL_FL_CVT FUSE Transmitted to IEC System;AlmGGIO1 ST;Alm6;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R401_P546_21M2
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 200KV R401_P546_21M2 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind13;stVal;SPS SPE_HLA_Normal_Alarm SPS 200KV R401_P546_21M2 PROTECTION BROKEN CONDUCTOR Alarm Normal NL_AL_BROKEN CON Transmitted to IEC System;AlmGGIO1 ST;Ind31;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 200KV R401_P546_21M2 SYSTEM CARRIER CHANNEL-2 Healthy Unhealthy UN_HL_CARR CH-2 Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 SYSTEM 86B TRIP RLY Operated Reset RS_OP_86B RLY Transmitted to IEC System;OptGGIO1 ST;Ind2;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 SYSTEM MAIN -1 PROTECTION Operated Reset RS_OP_M1 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 200KV R401_P546_21M2 SYSTEM TRIP RELAY 86B SUPERVISION Healthy Unhealthy UN_HL_86B SUPV Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind19;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 200KV R401_P546_21M2 SYSTEM BCU HEALTHY Healthy Unhealthy UN_HL_BCU Transmitted to IEC System;OptGGIO1 ST;Ind19;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind20;stVal;SPS SPE_HLA_NotRec_Recvd SPS 200KV R401_P546_21M2 SYSTEM CARRIER CHANNEL-2 Received Not Received NR_RV_CARR CH-2 Transmitted to IEC System;OptGGIO1 ST;Ind20;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind21;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 200KV R401_P546_21M2 SYSTEM MAIN-1 RELAY Healthy Unhealthy UN_HL_M1 Transmitted to IEC System;OptGGIO1 ST;Ind21;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind23;stVal;SPS SPE_HLA_Normal_Alarm SPS 200KV R401_P546_21M2 SYSTEM SOTF INITIATION Set Reset NL_AL_SOTF Transmitted to IEC System;OptGGIO1 ST;Ind23;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind24;stVal;SPS SPE_HLA_NotRec_Recvd SPS 200KV R401_P546_21M2 SYSTEM CARRIER CHANNEL-1 Received Not Received NR_RV_CARR CH-1 Transmitted to IEC System;OptGGIO1 ST;Ind24;stVal;SPS None 1 #REF!
A Control;PsbRPSB3 ST;Str1;general;ACD SPE_HLA_Normal_Alarm SPS 200KV R401_P546_21M2 PROTECTION POWER SWING DETECTED Set Reset NL_AL_PWR SW DET Transmitted to IEC Control;PsbRPSB3 ST;Str;general;ACD None 1 #REF!
A Control;PsbRPSB3 ST;BlkZn;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION POWER SWING BLOCKING Set Reset RS_OP_PWR SW BLK Transmitted to IEC Control;PsbRPSB3 ST;BlkZn;stVal;SPS None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION LINE DIFFERENTIAL Operated Reset RS_OP_DIF Transmitted to IEC Protection;DifPDIF1 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION DISTANCE ZONE-1 R-PH Operated Reset RS_OP_DIS Z1 R Transmitted to IEC Protection;DisPDIS1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION DISTANCE ZONE-1 Y-PH Operated Reset RS_OP_DIS Z1 Y Transmitted to IEC Protection;DisPDIS1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION DISTANCE ZONE-1 B-PH Operated Reset RS_OP_DIS Z1 B Transmitted to IEC Protection;DisPDIS1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION DISTANCE ZONE-1 Operated Reset RS_OP_DIS Z1 Transmitted to IEC Protection;DisPDIS1 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION DISTANCE ZONE-1 START Set Reset RS_OP_DIS S Z1 Transmitted to IEC Protection;DisPDIS1 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION DISTANCE ZONE-2 Operated Reset RS_OP_DIS Z2 Transmitted to IEC Protection;DisPDIS2 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION DISTANCE ZONE-2 START Set Reset RS_OP_DIS S Z2 Transmitted to IEC Protection;DisPDIS2 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS3 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION DISTANCE ZONE-3 Operated Reset RS_OP_DIS Z3 Transmitted to IEC Protection;DisPDIS3 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS3 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION DISTANCE ZONE-3 START Set Reset RS_OP_DIS S Z3 Transmitted to IEC Protection;DisPDIS3 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS4 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION DISTANCE ZONE-4 Operated Reset RS_OP_DIS Z4 Transmitted to IEC Protection;DisPDIS4 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS4 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION DISTANCE ZONE-4 START Set Reset RS_OP_DIS S Z4 Transmitted to IEC Protection;DisPDIS4 ST;Str;general;general;ACD None 1 #REF!
A Protection;EfdPTOC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION DIRECTIONAL E/F Operated Reset RS_OP_DIR E/F Transmitted to IEC Protection;EfdPTOC1 ST;Op;general;general;ACT None 1 #REF!
A Protection;EfdPTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION DIRECTIONAL E/F START Set Reset RS_OP_DIR E/F S Transmitted to IEC Protection;EfdPTOC1 ST;Str;general;general;ACD None 1 #REF!
A Protection;SofPSOF1 ST;Op1;general;ACT SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION SOTF Operated Reset RS_OP_SOTF Transmitted to IEC Protection;SofPSOF1 ST;Op1;general;ACT None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION OVERVOLTAGE STAGE-1 Operated Reset RS_OP_O/V STG1 Transmitted to IEC Protection;VtpPhsPTOV1 ST;Op;general;general;ACT None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION OVERVOLTAGE STAGE-1 START Set Reset RS_OP_O/V STG1 S Transmitted to IEC Protection;VtpPhsPTOV1 ST;Str;general;general;ACD None 1 #REF!
A Protection;VtpPhsPTOV2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV R401_P546_21M2 PROTECTION OVERVOLTAGE STAGE-2 Operated Reset RS_OP_O/V STG2 Transmitted to IEC Protection;VtpPhsPTOV2 ST;Op;general;general;ACT None 1 #REF!
DIGITAL INFORMATION TO IED IED name R401_P546_21M2
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Protection;DisPDIS5 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 200KV R201_P546_21M2 PROTECTION DISTANCE ZONE-5 START Set Reset RS_OP_DIS S Z5 Transmitted to IEC Protection;DisPDIS5 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPSCH1 ST;ProRx;stVal;SPS SPE_HLa_Reset_Set SPS 200KV R201_P546_21M2 PROTECTION CARRIER RECEIVE Set Reset RS_ST_CARR REC Transmitted to IEC Protection;DisPSCH1 ST;ProRx;stVal;SPS None 1 #REF!
A Protection;DisPSCH1 ST;ProTx;stVal;SPS SPE_HLa_Reset_Set SPS 200KV R201_P546_21M2 PROTECTION CARRIER SEND Set Reset RS_ST_CARR SEND Transmitted to IEC Protection;DisPSCH1 ST;ProTx;stVal;SPS None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 200KV R201_P546_21M2 PROTECTION DISTANCE ZONE-2 R-PH Operated Reset RS_OP_DIS Z2 R Transmitted to IEC Protection;DisPDIS2 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 200KV R201_P546_21M2 PROTECTION DISTANCE ZONE-2 Y-PH Operated Reset RS_OP_DIS Z2 Y Transmitted to IEC Protection;DisPDIS2 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 200KV R201_P546_21M2 PROTECTION DISTANCE ZONE-2 B-PH Operated Reset RS_OP_DIS Z2 B Transmitted to IEC Protection;DisPDIS2 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsA;general;ACD SPE_HLA_Reset_Optd SPS 200KV R201_P546_21M2 PROTECTION DISTANCE ZONE-2 START R-PH Set Reset RS_OP_DIS S Z2 R Transmitted to IEC Protection;DisPDIS2 ST;Str;phsA;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsB;general;ACD SPE_HLA_Reset_Optd SPS 200KV R201_P546_21M2 PROTECTION DISTANCE ZONE-2 START Y-PH Set Reset RS_OP_DIS S Z2 Y Transmitted to IEC Protection;DisPDIS2 ST;Str;phsB;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsC;general;ACD SPE_HLA_Reset_Optd SPS 200KV R201_P546_21M2 PROTECTION DISTANCE ZONE-2 START B-PH Set Reset RS_OP_DIS S Z2 B Transmitted to IEC Protection;DisPDIS2 ST;Str;phsC;general;ACD None 1 #REF!
A Protection;DisPDIS4 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV R201_P546_21M2 PROTECTION DISTANCE ZONE-5 Operated Reset RS_OP_DIS Z5 Transmitted to IEC Protection;DisPDIS5 ST;Op;general;general;ACT None 1 #REF!
A SPARE SPS 200KV R201_P546_21M2 PROTECTION CARRIER AIDED SCHEME Operated Reset RS_ST_CARR_AIDED Transmitted to IEC Protection;DisPSCH1 ST;CarRx;general;ACT 2 #REF!
A Protection;DifPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV R201_P546_21M2 PROTECTION LINE DIFFERENTIAL R PH Operated Reset RS_OP_DIF R Transmitted to IEC Protection;DifPDIF1 ST;Op;phsA;general;ACT None 1 #REF!
A SPARE SPS 200KV R201_P546_21M2 PROTECTION LINE DIFFERENTIAL Y PH Operated Reset RS_OP_DIF Y Transmitted to IEC Protection;DifPDIF1 ST;Op;phsB;general;ACT 2 #REF!
A SPARE SPS 200KV R201_P546_21M2 PROTECTION LINE DIFFERENTIAL B PH Operated Reset RS_OP_DIF B Transmitted to IEC Protection;DifPDIF1 ST;Op;phsC;general;ACT 2 #REF!
A SPARE SPS 200KV R201_P546_21M2 PROTECTION LINE DIFFERENTIAL START Reset RS_ST_DIF Transmitted to IEC Protection;DifPDIF1 ST;Str;general;general;ACT 2 #REF!
SPS 200KV R201_P546_21M2 SYSTEM CARRIER CHANNEL-1 Healthy Unhealthy UN_HL_CARR CH-1 Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS
SPS 200KV R201_P546_21M2 SYSTEM DIRECT TRIP CHANNEL-1 RECEIVED NOT RECEIVED NR_RC_DT-1 Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS
A SPARE SPS 200KV R201_P546_21M2 SYSTEM DIRECT TRIP CHANNEL-2 RECEIVED NOT RECEIVED NR_RC_DT-2 Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS 2 #REF!
SPS 200KV R201_P546_21M2 PROTECTION DISTANCE ENABLED Set Reset RS_ST_DIS_EN
SPS 200KV R201_P546_21M2 PROTECTION DT SEND CH 1 Set Reset RS_ST_DT_CH-1_S
SPS 200KV R201_P546_21M2 PROTECTION DT SEND CH 2 Set Reset RS_ST_DT_CH-2_S
SPS 200KV R201_P546_21M2 SYSTEM MAIN/ TBC CB AR OPTD Operated Reset RS_OP_A/R System;OptGGIO1 ST;Indx;stVal;SPS
SPS 200KV R201_P546_21M2 SYSTEM MAIN/ TBC LBB PROTECTION OPERATED Operated Reset RS_OP_LBB System;OptGGIO1 ST;Indx;stVal;SPS
SPS 200KV R201_P546_21M2 SYSTEM BCU RELAY Healthy Unhealthy RS_ST_BCU System;OptGGIO1 ST;Indx;stVal;SPS
SPS 200KV R201_P546_21M2 PROTECTION DIFFERENTIAL COMMUNICATION FAIL Set Reset RS_ST_DIFF_COM
SPS 200KV R201_P546_21M2 PROTECTION DIFFERENTIAL BLOCKED Set Reset RS_ST_DIFF_BLK
ANALOG INFORMATION FROM IED IED name R401_P546_21M2
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Records;RFLO1 MX;FltZ;cVal;CMV MV_hla_Fault_Impd_2 Z 400kV R201_P546_21M2 RECORDS Fltz -100.0 100.0 Fltz Transmitted to IEC Records;RFLO1 MX;FltZ;cVal;CMV 6 ANALOG INFORMATION FROM IED IED name R401_P546_21M2
A Records;RFLO1 MX;FltDiskm;mag;MV MV_Hla_Fault_Dist_1 Km 400kV R201_P546_21M2 RECORDS FltDiskm 0.0 1000.0 FltDiskm Transmitted to IEC Records;RFLO1 MX;FltDiskm;mag;MV 6 ANALOG INFORMATION FROM IED IED name R401_P546_21M2
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P546_21M2
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P546_21M2
ANALOG INFORMATION TO IED IED name R401_P546_21M2
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R401_P546_21M2
A SPARE 13 ANALOG INFORMATION TO IED IED name R401_P546_21M2
COUNTER INFORMATION FROM IED IED name R401_P546_21M2
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P546_21M2
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P546_21M2
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P546_21M2
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P546_21M2
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R203_REL670_21M2 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R203_REL670_21M2
DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A LD0;ZCPSCH1 ST;CarRx;general;ACT SPE_HLa_Reset_Set SPS 220kV R203_REL670_21M2 PROTECTION CARRIER AIDED SCHEME Operated Reset RS_ST_CARR_AIDED Transmitted to IEC LD0;ZCPSCH1 ST;CarRx;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZCPSCH1 ST;ProRx;stVal;SPS SPE_HLA_NotRec_Recvd SPS 220kV R203_REL670_21M2 PROTECTION CARRIER Received Not Received NR_RV_CARR CH-2 Transmitted to IEC LD0;ZCPSCH1 ST;ProRx;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMRPSB1 ST;Str;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION PSB DETECTED Set Reset RS_OP_PSB Transmitted to IEC LD0;ZMRPSB1 ST;Str;general;ACD None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMRPSB1 ST;BlkZn;stVal;SPS SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION POWER SWING BLOCKING Set Reset RS_OP_PSB_BLK Transmitted to IEC LD0;ZMRPSB1 ST;BlkZn;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;BRCPTOC1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION BROKEN CONDUCTOR Alarm Normal RS_OP_BRK. COND. Transmitted to IEC LD0;BRCPTOC1 ST;Op;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;SMPPTRC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC LD0;SMPPTRC1 ST;Op;general;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;STBPTOC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION STUB PROTN Operated Reset RS_OP_STUB Transmitted to IEC LD0;STBPTOC1 ST;Op;general;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZCVPSOF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION SOTF Operated Reset RS_OP_SOTF Transmitted to IEC LD0;ZCVPSOF1 ST;Op;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCPDIS1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE-1 R-PH Operated Reset RS_OP_ZONE1-RPH Transmitted to IEC LD0;ZMCPDIS1 ST;Op;phsA;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCPDIS1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE-1 Y-PH Operated Reset RS_OP_ZONE1-YPH Transmitted to IEC LD0;ZMCPDIS1 ST;Op;phsB;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCPDIS1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE-1 B-PH Operated Reset RS_OP_ZONE1-BPH Transmitted to IEC LD0;ZMCPDIS1 ST;Op;phsC;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCPDIS1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE1 Operated Reset RS_OP_ZONE1 Transmitted to IEC LD0;ZMCPDIS1 ST;Op;general;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCPDIS1 ST;Str;phsA;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE-1 START R-PH Set Reset RS_OP_ZONE1-RP_S Transmitted to IEC LD0;ZMCPDIS1 ST;Str;phsA;general;ACD None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCPDIS1 ST;Str;phsB;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE-1 START Y-PH Set Reset RS_OP_ZONE1-YP_S Transmitted to IEC LD0;ZMCPDIS1 ST;Str;phsB;general;ACD None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCPDIS1 ST;Str;phsC;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE-1 START B-PH Set Reset RS_OP_ZONE1-BP_S Transmitted to IEC LD0;ZMCPDIS1 ST;Str;phsC;general;ACD None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCPDIS1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE1 START Operated Reset RS_OP_ZONE1_S Transmitted to IEC LD0;ZMCPDIS1 ST;Str;general;general;ACD None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;SP16GGIO1 ST;Ind4;stVal;SPS SPE_HLA_NotRec_Recvd SPS 220kV R203_REL670_21M2 SYSTEM CARRIER CHANNEL-2 Received Not Received NR_RC_CARR_CH2 Transmitted to IEC LD0;SP16GGIO1 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;SP16GGIO1 ST;Ind5;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R203_REL670_21M2 SYSTEM SOTF INITIATION Set Reset NM_AL_SOTF_INI Transmitted to IEC LD0;SP16GGIO1 ST;Ind5;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;SP16GGIO1 ST;Ind7;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 220kV R203_REL670_21M2 SYSTEM BCU Healthy Unhealthy UL_HL_BCU Transmitted to IEC LD0;SP16GGIO1 ST;Ind7;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;SP16GGIO1 ST;Ind8;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 220kV R203_REL670_21M2 SYSTEM CARRIER CHANNEL-2 Healthy Unhealthy UL_HL_CARR_CH2 Transmitted to IEC LD0;SP16GGIO1 ST;Ind8;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;SP16GGIO1 ST;Ind11;stVal;SPS SPE_HLA_Healthy_Flty SPS 220kV R203_REL670_21M2 SYSTEM PU RELAY Faulty Healthy UL_HL_PU_REL Transmitted to IEC LD0;SP16GGIO1 ST;Ind11;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;SP16GGIO1 ST;Ind12;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 220kV R203_REL670_21M2 SYSTEM MAIN-1 RELAY Healthy Unhealthy UL_HL_MAIN1_REL Transmitted to IEC LD0;SP16GGIO1 ST;Ind12;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;SP16GGIO1 ST;Ind13;stVal;SPS SPE_HLA_NotRec_Recvd SPS 220kV R203_REL670_21M2 SYSTEM CARRIER CHANNEL-1 Received Not Received NR_RC_CARR_CH1 Transmitted to IEC LD0;SP16GGIO1 ST;Ind13;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;SP16GGIO1 ST;Ind14;stVal;SPS SPE_HLa_In_Out SPS 220kV R203_REL670_21M2 SYSTEM CARRIER CHANNEL-1 In Out IN_OU_CARR_CH1 Transmitted to IEC LD0;SP16GGIO1 ST;Ind14;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;SP16GGIO1 ST;Ind15;stVal;SPS SPE_HLa_In_Out SPS 220kV R203_REL670_21M2 SYSTEM CARRIER CHANNEL-2 In Out IN_OU_CARR_CH2 Transmitted to IEC LD0;SP16GGIO1 ST;Ind15;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;SP16GGIO1 ST;Ind16;stVal;SPS SPE_HLa_Reset_Set SPS 220kV R203_REL670_21M2 SYSTEM TRIP RELAY 86B SUPERVISION Set Reset RS_ST_86B SPVN Transmitted to IEC LD0;SP16GGIO1 ST;Ind16;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;SP16GGIO2 ST;Ind2;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R203_REL670_21M2 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC LD0;SP16GGIO2 ST;Ind2;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;SP16GGIO2 ST;Ind11;stVal;SPS SPE_HLA_Nrml_Optd SPS 220kV R203_REL670_21M2 SYSTEM 86B TRIP RELAY Operated Normal NM_OP_86B Transmitted to IEC LD0;SP16GGIO2 ST;Ind11;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCAPDIS2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE2 Operated Reset RS_OP_ZONE2 Transmitted to IEC LD0;ZMCAPDIS2 ST;Op;general;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCAPDIS2 ST;Str;phsA;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE-2 START R-PH Set Reset RS_OP_ZONE2-RP_S Transmitted to IEC LD0;ZMCAPDIS2 ST;Str;phsA;general;ACD None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCAPDIS2 ST;Str;phsB;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE-2 START Y-PH Set Reset RS_OP_ZONE2-YP_S Transmitted to IEC LD0;ZMCAPDIS2 ST;Str;phsB;general;ACD None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCAPDIS2 ST;Str;phsC;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE-2 START B-PH Set Reset RS_OP_ZONE2-BP_S Transmitted to IEC LD0;ZMCAPDIS2 ST;Str;phsC;general;ACD None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCAPDIS2 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE2 START Set Reset RS_OP_ZONE2_S Transmitted to IEC LD0;ZMCAPDIS2 ST;Str;general;general;ACD None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCAPDIS3 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE3 Operated Reset RS_OP_ZONE3 Transmitted to IEC LD0;ZMCAPDIS3 ST;Op;general;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCAPDIS3 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE3 START Set Reset RS_OP_ZONE3_S Transmitted to IEC LD0;ZMCAPDIS3 ST;Str;general;general;ACD None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCAPDIS4 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE4 Operated Reset RS_OP_ZONE4 Transmitted to IEC LD0;ZMCAPDIS4 ST;Op;general;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCAPDIS4 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE4 START Set Reset RS_OP_ZONE4_S Transmitted to IEC LD0;ZMCAPDIS4 ST;Str;general;general;ACD None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCAPDIS5 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE5 Operated Reset RS_OP_ZONE5 Transmitted to IEC LD0;ZMCAPDIS5 ST;Op;general;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A EF4_1;EF4PTOC1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DIRECTIONAL E/F Operated Reset RS_OP_DEF Transmitted to IEC EF4_1;EF4PTOC1 ST;Op;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A EF4_1;EF4PTOC1 ST;Str;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DIRECTIONAL E/F START Set Reset RS_OP_DEF_S Transmitted to IEC EF4_1;EF4PTOC1 ST;Str;general;ACD None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A OV2_1;OV2PTOV1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION OVERVOLTAGE STAGE-1 Operated Reset RS_OP_O/V-1 Transmitted to IEC OV2_1;OV2PTOV1 ST;Op;general;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A OV2_1;OV2PTOV1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION OVERVOLTAGE STAGE-1 START Set Reset RS_OP_O/V-1_S Transmitted to IEC OV2_1;OV2PTOV1 ST;Str;general;general;ACD None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A OV2_1;OV2PTOV2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION OVERVOLTAGE STAGE-2 Operated Reset RS_OP_O/V-2 Transmitted to IEC OV2_1;OV2PTOV2 ST;Op;general;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
DIGITAL INFORMATION TO IED IED name R203_REL670_21M2
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A LD0;ZMCAPDIS5 ST;Op;general;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE5 START Set Reset RS_OP_ZONE5 Transmitted to IEC LD0;ZMCAPDIS5 ST;Op;general;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCPDIS2 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE-2 R-PH Operated Reset RS_OP_ZONE1-RPH Transmitted to IEC LD0;ZMCPDIS1 ST;Op;phsA;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCPDIS2 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE-2 Y-PH Operated Reset RS_OP_ZONE1-YPH Transmitted to IEC LD0;ZMCPDIS1 ST;Op;phsB;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCPDIS2 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE-2 B-PH Operated Reset RS_OP_ZONE1-BPH Transmitted to IEC LD0;ZMCPDIS1 ST;Op;phsC;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZMCAPDIS5 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 220kV R203_REL670_21M2 PROTECTION DISTANCE ZONE5 START Set Reset RS_OP_ZONE4_S Transmitted to IEC LD0;ZMCAPDIS4 ST;Str;general;general;ACD None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;ZCPSCH1 ST;ProTx;stVal;SPS SPE_HLa_Reset_Set SPS 220kV R203_REL670_21M2 PROTECTION CARRIER Set reset NR_RV_CARR CH-2 Transmitted to IEC LD0;ZCPSCH1 ST;ProRx;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;SP16GGIO2 ST;Ind3;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R203_REL670_21M2 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_TIME SYNC Transmitted to IEC LD0;SP16GGIO2 ST;Ind2;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A SPARE SPC 220kV R203_REL670_21M2 PROTECTION 2 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A SPARE SPS 220kV R203_REL670_21M2 SYSTEM FEEDER IN NORMAL MODE Set Reset RS_ST_FDR NRML Transmitted to IEC LD0;SP16GGIO2 ST;Ind3;stVal;SPS 2 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A SPARE SPS 220kV R203_REL670_21M2 SYSTEM FEEDER IN TRANSFER MODE Set Reset RS_ST_FDR TRNSFR Transmitted to IEC LD0;SP16GGIO2 ST;Ind4;stVal;SPS 2 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
A SPARE SPS 220kV R203_REL670_21M2 SYSTEM FEEDER IN INVERSE MODE Set Reset RS_ST_FDR INV Transmitted to IEC LD0;SP16GGIO2 ST;Ind5;stVal;SPS 2 DIGITAL INFORMATION FROM IED IED name R203_REL670_21M2
ANALOG INFORMATION FROM IED IED name R203_REL670_21M2
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A LD0;LMBRFLO1 MX;FltZ;cVal;CMV MV_hla_Fault_Impd Z 220kV R203_REL670_21M2 PROTECTION FAULT IMPEDANCE -100.0 100.0 Fltz Transmitted to IEC LD0;LMBRFLO1 MX;FltZ;cVal;CMV 6 ANALOG INFORMATION FROM IED IED name R203_REL670_21M2
A LD0;LMBRFLO1 MX;FltDiskm;mag;MV MV_Hla_Fault_Dist Km 220kV R203_REL670_21M2 PROTECTION FAULT DISTANCE 0.0 1000.0 FltDiskm Transmitted to IEC LD0;LMBRFLO1 MX;FltDiskm;mag;MV 6 ANALOG INFORMATION FROM IED IED name R203_REL670_21M2
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R203_REL670_21M2
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R203_REL670_21M2
ANALOG INFORMATION TO IED IED name R203_REL670_21M2
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R203_REL670_21M2
A SPARE 13 ANALOG INFORMATION TO IED IED name R203_REL670_21M2
COUNTER INFORMATION FROM IED IED name R203_REL670_21M2
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R203_REL670_21M2
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R203_REL670_21M2
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R203_REL670_21M2
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R203_REL670_21M2
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R407_P643_87T GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R407_P643_87T
DIGITAL INFORMATION FROM IED IED name R407_P643_87T
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 200KV R207_P643_87T PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R407_P643_87T
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 200KV R207_P643_87T PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T PROTECTION OVEREXCITATION HV START Set Reset RS_OP_O/E HV S Transmitted to IEC Protection;VhzWg1PVPH1 ST;Str;general;ACD None Yes 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T SYSTEM 86A1 TRIP RELAY Operated Reset RS_OP_86A1 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T SYSTEM 86A2 TRIP RELAY Operated Reset RS_OP_86A2 Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Normal_Fail SPS 200KV R207_P643_87T SYSTEM DC SOURCE-2 Fail Normal NL_FL_DC S2 Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 200KV R207_P643_87T SYSTEM REF RELAY Healthy Unhealthy UL_HL_64 Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ TRIP 1&2 Operated Reset RS_OP_BUCH12 Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Normal_Alarm SPS 200KV R207_P643_87T SYSTEM PRD 1 2 &3 Alarm Normal RS_OP_PRD123 Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T SYSTEM OSR1 Operated Reset RS_OP_OSR-1 Transmitted to IEC System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T SYSTEM OSR2 Operated Reset RS_OP_OSR-2 Transmitted to IEC System;OptGGIO1 ST;Ind13;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind14;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T SYSTEM OSR3 Operated Reset RS_OP_OSR-3 Transmitted to IEC System;OptGGIO1 ST;Ind14;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind15;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T SYSTEM OTI Operated Reset RS_OP_OTI Transmitted to IEC System;OptGGIO1 ST;Ind15;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind16;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T SYSTEM 86A2 SUPERVISION Healthy Unhealthy RS_OP_86A2 S Transmitted to IEC System;OptGGIO1 ST;Ind16;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind17;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T SYSTEM WTI HV Operated Reset RS_OP_WTI HV Transmitted to IEC System;OptGGIO1 ST;Ind17;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind18;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T SYSTEM WTI LV Operated Reset RS_OP_WTI LV Transmitted to IEC System;OptGGIO1 ST;Ind18;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind19;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T SYSTEM WTI IV Operated Reset RS_OP_WTI IV Transmitted to IEC System;OptGGIO1 ST;Ind19;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind20;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T SYSTEM LOW OIL LEVEL MAIN TANK Alarm Normal RS_OP_MOLG Transmitted to IEC System;OptGGIO1 ST;Ind20;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind21;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T SYSTEM LOW OIL LEVEL OLTC Alarm Normal RS_OP_MOLG O Transmitted to IEC System;OptGGIO1 ST;Ind21;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind24;stVal;SPS SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T SYSTEM 86A1 SUPERVISION Healthy Unhealthy RS_OP_86A1 S Transmitted to IEC System;OptGGIO1 ST;Ind24;stVal;SPS None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T PROTECTION DIFFERENTIAL R-PH TRIP Operated Reset RS_OP_DIFF R PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T PROTECTION DIFFERENTIAL Y-PH TRIP Operated Reset RS_OP_DIFF Y-PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T PROTECTION DIFFERENTIAL B-PH TRIP Operated Reset RS_OP_DIFF B-PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T PROTECTION DIFFERENTIAL TRP Operated Reset RS_OP_DIFF Transmitted to IEC Protection;DifPDIF1 ST;Op;general;general;ACT None 1 #REF!
A Protection;EfmEl1PTOC1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T PROTECTION DIFFERENTIAL CURRENT ALARM Set Reset RS_ST_DIFF_CURNT None 1 #REF!
A Protection;EfmEl1PTOC1 ST;Str;general;ACD SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T PROTECTION DIFFERENTIAL PROTECTION START Set Reset RS_ST_DIFF_STRT None 1 #REF!
A Protection;OcpEI1PTOC1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T PROTECTION DIFFERENTIAL PROTECTION RPH START Set Reset RS_ST_DIFF_STR_R None 1 #REF!
A Protection;OcpEI1PTOC1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T PROTECTION DIFFERENTIAL PROTECTION YPH START Set Reset RS_ST_DIFF_STR_Y None 1 #REF!
A Protection;OcpEI1PTOC1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T PROTECTION DIFFERENTIAL PROTECTION BPH START Set Reset RS_ST_DIFF_STR_B None 1 #REF!
A Protection;OcpEI1PTOC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200KV R207_P643_87T PROTECTION DIFFERENTIAL BLOCKED Set Reset RS_ST_DIFF_BLK None 1 #REF!
SPS 200KV R207_P643_87T PROTECTION DIFFERENTIAL PROTECTION TRIP-HS1 Operated Reset RS_OP_DIFF_HS-1
SPS 200KV R207_P643_87T PROTECTION DIFFERENTIAL PROTECTION TRIP-HS2 Operated Reset RS_OP_DIFF_HS-2
SPS 200KV R207_P643_87T PROTECTION DIFFERENTIAL PROTECTION 2nd HARMONIC BLOCK Set Reset RS_ST_DIFF_HBK 2
SPS 200KV R207_P643_87T PROTECTION DIFFERENTIAL PROTECTION 5th HARMONIC BLOCK Set Reset RS_ST_DIFF_HBK 5
A Protection;VhzWg1PVPH1 ST;Op;general;ACT SPE_HLA_Normal_Alarm SPS 200KV R207_P643_87T PROTECTION OVEREXCITATION HV ALARM Set Reset NL_AL_O/E HV Transmitted to IEC Protection;VhzWg1PVPH1 ST;Op;general;ACT None 1 #REF!
A Protection;VhzWg1PVPH2 ST;Op;general;ACT SPE_HLA_Reset_Trip SPS 200KV R207_P643_87T PROTECTION OVEREXCITATION HV TRIP Operated Reset RS_TR_O/E HV Transmitted to IEC Protection;VhzWg1PVPH2 ST;Op;general;ACT None 1 #REF!
SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
DIGITAL INFORMATION TO IED SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref IED DO Reference Electrical Data SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R207_P643_87T
SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
ANALOG INFORMATION FROM IED SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref IED AI Reference Electrical Data SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 ANALOG INFORMATION FROM IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 ANALOG INFORMATION FROM IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 ANALOG INFORMATION FROM IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 ANALOG INFORMATION FROM IED IED name R207_P643_87T
SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
ANALOG INFORMATION TO IED SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref IED AI Reference Electrical Data SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 13 ANALOG INFORMATION TO IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 13 ANALOG INFORMATION TO IED IED name R207_P643_87T
SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
COUNTER INFORMATION FROM IED SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref IED Counter Reference Electrical Data SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 COUNTER INFORMATION FROM IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 COUNTER INFORMATION FROM IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 COUNTER INFORMATION FROM IED IED name R207_P643_87T
A SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 COUNTER INFORMATION FROM IED IED name R207_P643_87T
END OF IED DATA SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
DI GROUPS SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref Group DI Reference Electrical Data SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
SELF GENERATED DIGITAL INFORMATION SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref Self DI Reference Electrical Data SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
SELF GENERATED DIGITAL OUTPUT INFORMATION SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref Self DO Reference Electrical Data SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
SELF GENERATED ANALOG INFORMATION SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref Self AI Reference Electrical Data SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
SELF GENERATED COUNTER INFORMATION SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref Self Counter Reference Electrical Data SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
SELF GENERATED SETPOINT INFORMATION SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref SetPoint Reference Electrical Data SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE SPS 200KV R207_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE SPS 200KV R207_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE SPS 200KV R207_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
SPS 200KV R207_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
END OF DATA SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-1 TRIP Operated Reset RS_TR_BUCH-1 System;OptGGIO1 ST;Ind11;stVal;SPS
SPS 200KV R207_P643_87T SYSTEM WTI-HV TRIP Operated Reset RS_TR_WTI-HV System;OptGGIO1 ST;Ind12;stVal;SPS
SPS 200KV R207_P643_87T SYSTEM WTI - IV & LV TRIP Operated Reset RS_TR_WTI-LVIV System;OptGGIO1 ST;Ind13;stVal;SPS
SPS 200KV R207_P643_87T SYSTEM PRD-2 TRIP Operated Reset RS_TR_PRV2 System;OptGGIO1 ST;Ind14;stVal;SPS
SPS 200KV R207_P643_87T SYSTEM OTI ALARM Alarm Normal NL_AL_OTI System;OptGGIO1 ST;Ind15;stVal;SPS
SPS 200KV R207_P643_87T SYSTEM PRV OLTC ALARM Set Reset NL_AL_OLTC System;OptGGIO1 ST;Ind17;stVal;SPS
SPS 200KV R207_P643_87T SYSTEM OIL LEVEL LOW ALARM Set Reset NL_AL_OLL System;OptGGIO1 ST;Ind18;stVal;SPS
SPS 200KV R207_P643_87T SYSTEM BUCHHOLZ-2 ALARM Set Reset RS_ST_BUCH-2 ALM System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 200KV R207_P643_87T SYSTEM OSR-1 TRIP Operated Reset RS_OP_OSR-1 TR System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 200KV R207_P643_87T SYSTEM FIRE PROTECTION Operated Reset RS_OP_FIRE PRTN System;OptGGIO1 ST;IndXX;stVal;SPS
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R407_P643_64 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R407_P643_64
DIGITAL INFORMATION FROM IED IED name R407_P643_64
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 200kV R207_P643_64 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R407_P643_64
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 200kV R207_P643_64 PROTECTION OVEREXCITATION IV START Set Reset RS_OP_O/E IV S Transmitted to IEC Protection;VhzWg1PVPH1 ST;Str;general;ACD None Yes 1 #REF!
A System;GosGGIO2 ST;Ind8;stVal;SPS SPE_HLA_Normal_Alarm SPS 200kV R207_P643_64 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind8;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 200kV R207_P643_64 SYSTEM 87T RELAY Healthy Unhealthy UL_HL_87T Transmitted to IEC System;OptGGIO1 ST;Ind2;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLA_Reset_Optd SPS 200kV R207_P643_64 SYSTEM 86B1 TRIP RELAY Operated Reset RS_OP_86B1 Transmitted to IEC System;OptGGIO1 ST;Ind3;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 200kV R207_P643_64 SYSTEM 86B2 TRIP RELAY Operated Reset RS_OP_86B2 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Normal_Alarm SPS 200kV R207_P643_64 SYSTEM WTI HV Alarm Normal NL_AL_WTI HV Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Normal_Alarm SPS 200kV R207_P643_64 SYSTEM WTI LV Alarm Normal NL_AL_WTI LV Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Normal_Alarm SPS 200kV R207_P643_64 SYSTEM WTI IV Alarm Normal NL_AL_WTI IV Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Normal_Alarm SPS 200kV R207_P643_64 SYSTEM BUCHHOLZ 1&2 Alarm Normal NL_AL_BUCH12 Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Normal_Alarm SPS 200kV R207_P643_64 SYSTEM OTI Alarm Normal NL_AL_OTI Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Normal_Fail SPS 200kV R207_P643_64 SYSTEM DC SOURCE-1 Fail Normal NL_FL_DC S1 Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind15;stVal;SPS SPE_HLA_Reset_Optd SPS 200kV R207_P643_64 SYSTEM 86A1 SUPERVISION Healthy Unhealthy RS_OP_86B1 S Transmitted to IEC System;OptGGIO1 ST;Ind15;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind16;stVal;SPS SPE_HLA_Reset_Optd SPS 200kV R207_P643_64 SYSTEM 86A2 SUPERVISION Healthy Unhealthy RS_OP_86B2 S Transmitted to IEC System;OptGGIO1 ST;Ind16;stVal;SPS None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 200kV R207_P643_64 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;HzrHvwPTOC1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 200kV R207_P643_64 PROTECTION REF R PH TRIP Operated Reset RS_OP_REF Transmitted to IEC Protection;HzrHvwPTOC1 ST;Op;general;ACT None 1 #REF!
SPS 200kV R207_P643_64 PROTECTION REF Y PH TRIP Operated Reset RS_OP_REF Transmitted to IEC Protection;HzrLvwPTOC1 ST;Op;general;ACT
SPS 200kV R207_P643_64 PROTECTION REF B PH TRIP Operated Reset RS_OP_REF Transmitted to IEC Protection;HzrTvwPTOC1 ST;Op;general;ACT
A Protection;OcpEI1PTOC1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 200kV R207_P643_64 PROTECTION REF ALARM Set Reset RS_ST_REF ALM None 1 #REF!
A Protection;OcpEI1PTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 200kV R207_P643_64 PROTECTION OVEREXCITATION IV START Set Reset RS_ST_O/E IV ST None 1 #REF!
A Protection;VhzWg1PVPH1 ST;Op;general;ACT SPE_HLA_Normal_Alarm SPS 200kV R207_P643_64 PROTECTION OVEREXCITATION IV ALARM Set Reset NL_AL_O/E IV Transmitted to IEC Protection;VhzWg1PVPH1 ST;Op;general;ACT None 1 #REF!
A Protection;VhzWg1PVPH2 ST;Op;general;ACT SPE_HLA_Reset_Trip SPS 200kV R207_P643_64 PROTECTION OVEREXCITATION IV TRIP Operated Reset RS_TR_O/E IV T Transmitted to IEC Protection;VhzWg1PVPH2 ST;Op;general;ACT None 1 #REF!
SPS 200kV R207_P643_64 SYSTEM OIL TEMP TRIP
DIGITAL INFORMATION TO IED SPS 200kV R207_P643_64 SYSTEM BUCHHOLZ-2 TRIP
Iss. Customer Ref IED DO Reference Electrical Data SPS 200kV R207_P643_64 SYSTEM BUCHHOLZ ALARM Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 200kV R207_P643_64 SYSTEM WDG TEMP - HV ALARM Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 200kV R207_P643_64 SYSTEM WDG TEMP - IV & LV ALARM 2 DIGITAL INFORMATION TO IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM OIL FLOW FAIL ALARM 2 DIGITAL INFORMATION TO IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R207_P643_64
SPS 200kV R207_P643_64 SYSTEM
ANALOG INFORMATION FROM IED SPS 200kV R207_P643_64 SYSTEM
Iss. Customer Ref IED AI Reference Electrical Data SPS 200kV R207_P643_64 SYSTEM Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 200kV R207_P643_64 SYSTEM Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 ANALOG INFORMATION FROM IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 ANALOG INFORMATION FROM IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 ANALOG INFORMATION FROM IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 ANALOG INFORMATION FROM IED IED name R207_P643_64
SPS 200kV R207_P643_64 SYSTEM
ANALOG INFORMATION TO IED SPS 200kV R207_P643_64 SYSTEM
Iss. Customer Ref IED AI Reference Electrical Data SPS 200kV R207_P643_64 SYSTEM Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 200kV R207_P643_64 SYSTEM Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 200kV R207_P643_64 SYSTEM 13 ANALOG INFORMATION TO IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM 13 ANALOG INFORMATION TO IED IED name R207_P643_64
SPS 200kV R207_P643_64 SYSTEM
COUNTER INFORMATION FROM IED SPS 200kV R207_P643_64 SYSTEM
Iss. Customer Ref IED Counter Reference Electrical Data SPS 200kV R207_P643_64 SYSTEM Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 200kV R207_P643_64 SYSTEM Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 COUNTER INFORMATION FROM IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 COUNTER INFORMATION FROM IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 COUNTER INFORMATION FROM IED IED name R207_P643_64
A SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 COUNTER INFORMATION FROM IED IED name R207_P643_64
END OF IED DATA SPS 200kV R207_P643_64 SYSTEM
SPS 200kV R207_P643_64 SYSTEM
DI GROUPS SPS 200kV R207_P643_64 SYSTEM
Iss. Customer Ref Group DI Reference Electrical Data SPS 200kV R207_P643_64 SYSTEM Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function SPS 200kV R207_P643_64 SYSTEM Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 2 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 3 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 4 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 5 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 6 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 7 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 8 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 9 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 10 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 11 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 12 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 13 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 14 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 15 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 16 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 DI GROUPS
SPS 200kV R207_P643_64 SYSTEM
SELF GENERATED DIGITAL INFORMATION SPS 200kV R207_P643_64 SYSTEM
Iss. Customer Ref Self DI Reference Electrical Data SPS 200kV R207_P643_64 SYSTEM Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 200kV R207_P643_64 SYSTEM Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS 200kV R207_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SPS 200kV R207_P643_64 SYSTEM
SELF GENERATED DIGITAL OUTPUT INFORMATION SPS 200kV R207_P643_64 SYSTEM
Iss. Customer Ref Self DO Reference Electrical Data SPS 200kV R207_P643_64 SYSTEM Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 200kV R207_P643_64 SYSTEM Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200kV R207_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPS 200kV R207_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPS 200kV R207_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPS 200kV R207_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPS 200kV R207_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPS 200kV R207_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPS 200kV R207_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPS 200kV R207_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPS 200kV R207_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPS 200kV R207_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SPS 200kV R207_P643_64 SYSTEM
SELF GENERATED ANALOG INFORMATION SPS 200kV R207_P643_64 SYSTEM
Iss. Customer Ref Self AI Reference Electrical Data SPS 200kV R207_P643_64 SYSTEM Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 200kV R207_P643_64 SYSTEM Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SPS 200kV R207_P643_64 SYSTEM
SELF GENERATED COUNTER INFORMATION SPS 200kV R207_P643_64 SYSTEM
Iss. Customer Ref Self Counter Reference Electrical Data SPS 200kV R207_P643_64 SYSTEM Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 200kV R207_P643_64 SYSTEM Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SPS 200kV R207_P643_64 SYSTEM
SELF GENERATED SETPOINT INFORMATION SPS 200kV R207_P643_64 SYSTEM
Iss. Customer Ref SetPoint Reference Electrical Data SPS 200kV R207_P643_64 SYSTEM Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 200kV R207_P643_64 SYSTEM Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE SPS 200kV R207_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
SPS 200kV R207_P643_64 SYSTEM
END OF DATA SPS 200kV R207_P643_64 SYSTEM
SPS 200kV R207_P643_64 SYSTEM PRD-1 TRIP Operated Reset RS_TR_PRD-1 System;OptGGIO1 ST;Ind5;stVal;SPS
SPS 200kV R207_P643_64 SYSTEM OTI TRIP Operated Reset RS_TR_OTI System;OptGGIO1 ST;Ind6;stVal;SPS
SPS 200kV R207_P643_64 SYSTEM BUCHHOLZ-2 TRIP Operated Reset RS_TR_BUCH-2 System;OptGGIO1 ST;Ind7;stVal;SPS
SPS 200kV R207_P643_64 SYSTEM BUCHHOLZ-1 ALARM Set Reset NL_AL_BUCH System;OptGGIO1 ST;Ind8;stVal;SPS
SPS 200kV R207_P643_64 SYSTEM WTI - HV ALARM Set Reset NL_AL_WTI-HV System;OptGGIO1 ST;Ind9;stVal;SPS
SPS 200kV R207_P643_64 SYSTEM WTI - IV & LV ALARM Set Reset NL_AL_WTI IVLV System;OptGGIO1 ST;Ind10;stVal;SPS
SPS 200kV R207_P643_64 SYSTEM OSR-2 TRIP Operated Reset RS_OP_OSR-2 TRP System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 200kV R207_P643_64 SYSTEM PRD-3 TRIP Operated Reset RS_OP_PRD-3 TRP System;OptGGIO1 ST;IndXX;stVal;SPS
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R412_P442_21R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R412_P442_21R
DIGITAL INFORMATION FROM IED IED name R412_P442_21R
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 200kV R207_P442_21R PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R412_P442_21R
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 200kV R207_P442_21R PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R412_P442_21R
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 200kV R207_P442_21R PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;CbfRBRF1 ST;OpEx;general;ACT SPE_HLA_Normal_Fail SPS 200kV R207_P442_21R PROTECTION VT FUSE FAIL Alarm Normal NL_FL_VT FUSE Transmitted to IEC System;AlmGGIO1 ST;Alm6;stVal;SPS None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 200kV R207_P442_21R PROTECTION BACKUP IMPEDENCE R-PH TRIP Operated Reset RS_OP_B/U IMP R Transmitted to IEC Protection;DisPDIS1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 200kV R207_P442_21R PROTECTION BACKUP IMPEDENCE Y-PH TRIP Operated Reset RS_OP_B/U IMP Y Transmitted to IEC Protection;DisPDIS1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 200kV R207_P442_21R PROTECTION BACKUP IMPEDENCE B-PH TRIP Operated Reset RS_OP_B/U IMP B Transmitted to IEC Protection;DisPDIS1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200kV R207_P442_21R PROTECTION BACKUP IMPEDENCE Operated Reset RS_OP_B/U IMP Transmitted to IEC Protection;DisPDIS1 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Str;general;general;ACD SPE_HLA_Reset_Start SPS 200kV R207_P442_21R PROTECTION REACTOR BACKUP IMPEDANE PICKUP set Reset RS_ST_Z1 START Transmitted to IEC Protection;DisPDIS1 ST;Str;general;general;ACD None 1 #REF!
A SPARE SPS 200kV R207_P442_21R PROTECTION BACKUP ZONE-1 TRIP Operated Reset RS_OP_Z1_TRP None No 1 #REF!
SPS 200kV R207_P442_21R
DIGITAL INFORMATION TO IED SPS 200kV R207_P442_21R
Iss. Customer Ref IED DO Reference Electrical Data SPS 200kV R207_P442_21R Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 200kV R207_P442_21R Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 200kV R207_P442_21R 2 DIGITAL INFORMATION TO IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R 2 DIGITAL INFORMATION TO IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R 2 DIGITAL INFORMATION TO IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R 2 DIGITAL INFORMATION TO IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R R 2 DIGITAL INFORMATION TO IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R 2 DIGITAL INFORMATION TO IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R 2 DIGITAL INFORMATION TO IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R 2 DIGITAL INFORMATION TO IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R 2 DIGITAL INFORMATION TO IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R 2 DIGITAL INFORMATION TO IED IED name R207_P442_21R
SPS 200kV R207_P442_21R
ANALOG INFORMATION FROM IED SPS 200kV R207_P442_21R
Iss. Customer Ref IED AI Reference Electrical Data SPS 200kV R207_P442_21R Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 200kV R207_P442_21R Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 200kV R207_P442_21R Yes 6 ANALOG INFORMATION FROM IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R Yes 6 ANALOG INFORMATION FROM IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R Yes 6 ANALOG INFORMATION FROM IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R Yes 6 ANALOG INFORMATION FROM IED IED name R207_P442_21R
SPS 200kV R207_P442_21R
ANALOG INFORMATION TO IED SPS 200kV R207_P442_21R
Iss. Customer Ref IED AI Reference Electrical Data SPS 200kV R207_P442_21R Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 200kV R207_P442_21R Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 200kV R207_P442_21R 13 ANALOG INFORMATION TO IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R 13 ANALOG INFORMATION TO IED IED name R207_P442_21R
SPS 200kV R207_P442_21R
COUNTER INFORMATION FROM IED SPS 200kV R207_P442_21R
Iss. Customer Ref IED Counter Reference Electrical Data SPS 200kV R207_P442_21R Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 200kV R207_P442_21R Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 200kV R207_P442_21R Yes 39 COUNTER INFORMATION FROM IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R Yes 39 COUNTER INFORMATION FROM IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R Yes 39 COUNTER INFORMATION FROM IED IED name R207_P442_21R
A SPARE SPS 200kV R207_P442_21R Yes 39 COUNTER INFORMATION FROM IED IED name R207_P442_21R
END OF IED DATA SPS 200kV R207_P442_21R
SPS 200kV R207_P442_21R
DI GROUPS SPS 200kV R207_P442_21R
Iss. Customer Ref Group DI Reference Electrical Data SPS 200kV R207_P442_21R Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function SPS 200kV R207_P442_21R Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
A 2 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
A 3 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
A 4 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
A 5 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
A 6 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
A 7 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
A 8 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
A 9 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
A 10 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
A 11 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
A 12 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
A 13 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
A 14 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
A 15 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
A 16 SPARE SPS 200kV R207_P442_21R None No 1 C264 DI GROUPS
SPS 200kV R207_P442_21R
SELF GENERATED DIGITAL INFORMATION SPS 200kV R207_P442_21R
Iss. Customer Ref Self DI Reference Electrical Data SPS 200kV R207_P442_21R Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 200kV R207_P442_21R Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS 200kV R207_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SPS 200kV R207_P442_21R
SELF GENERATED DIGITAL OUTPUT INFORMATION SPS 200kV R207_P442_21R
Iss. Customer Ref Self DO Reference Electrical Data SPS 200kV R207_P442_21R Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 200kV R207_P442_21R Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200kV R207_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPS 200kV R207_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPS 200kV R207_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPS 200kV R207_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPS 200kV R207_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPS 200kV R207_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPS 200kV R207_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPS 200kV R207_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPS 200kV R207_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPS 200kV R207_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SPS 200kV R207_P442_21R
SELF GENERATED ANALOG INFORMATION SPS 200kV R207_P442_21R
Iss. Customer Ref Self AI Reference Electrical Data SPS 200kV R207_P442_21R Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 200kV R207_P442_21R Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE SPS 200kV R207_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SPS 200kV R207_P442_21R
SELF GENERATED COUNTER INFORMATION SPS 200kV R207_P442_21R
Iss. Customer Ref Self Counter Reference Electrical Data SPS 200kV R207_P442_21R Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 200kV R207_P442_21R Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE SPS 200kV R207_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SPS 200kV R207_P442_21R
SELF GENERATED SETPOINT INFORMATION SPS 200kV R207_P442_21R
Iss. Customer Ref SetPoint Reference Electrical Data SPS 200kV R207_P442_21R Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 200kV R207_P442_21R Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE SPS 200kV R207_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
SPS 200kV R207_P442_21R
END OF DATA SPS 200kV R207_P442_21R
SPS 200kV R207_P442_21R PROTECTION BACKUP OVERCURRENT START set Reset RS_ST_B/U O/C ST
SPS 200kV R207_P442_21R PROTECTION BACKUP OVERCURRENT TRIP Operated Reset RS_ST_B/C O/C TR
SPS 200kV R207_P442_21R PROTECTION BACKUP EARTHFAULT START set Reset RS_ST_B/U E/F_ST
SPS 200kV R207_P442_21R PROTECTION BACKUP EARTHFAULT TRIP Operated Reset RS_ST_B/C E/F TR
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R412_P643_87R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R412_P643_87R
DIGITAL INFORMATION FROM IED IED name R412_P643_87R
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 200kV R212_P643_87R PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R412_P643_87R
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 200kV R212_P643_87R PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 200kV R212_P643_87R SYSTEM 86A TRIP RELAY Operated Reset RS_OP_86A Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Reset_Optd SPS 200kV R212_P643_87R SYSTEM B/U IMPEDENCE Operated Reset RS_OP_B/U IMP Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 200kV R212_P643_87R SYSTEM REF (64R) RELAY Healthy Unhealthy UH_HL_64R(REF) Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 200kV R212_P643_87R PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 200kV R212_P643_87R PROTECTION DIFFERENTIAL R-PH TRIP Operated Reset RS_OP_DIFF R PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 200kV R212_P643_87R PROTECTION DIFFERENTIAL Y-PH TRIP Operated Reset RS_OP_DIFF Y-PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 200kV R212_P643_87R PROTECTION DIFFERENTIAL B-PH TRIP Operated Reset RS_OP_DIFF B-PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200kV R212_P643_87R PROTECTION DIFFERENTIAL TRIP Operated Reset RS_OP_DIFF Transmitted to IEC Protection;DifPDIF1 ST;Op;general;general;ACT None 1 #REF!
A SPARE SPS 200kV R212_P643_87R SYSTEM 86A SUPERVISION HEALTHY UNHEALTHY UL_HL_86A SUP System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 #REF!
SPS 200kV R212_P643_87R PROTECTION DIFFERENTIAL CURRENT ALARM Set Reset RS_ST_DIFF_CURNT
SPS 200kV R212_P643_87R PROTECTION DIFFERENTIAL PROTECTION START Set Reset RS_ST_DIFF_STRT
SPS 200kV R212_P643_87R PROTECTION DIFFERENTIAL PROTECTION RPH START Set Reset RS_ST_DIFF_STR_R
SPS 200kV R212_P643_87R PROTECTION DIFFERENTIAL PROTECTION YPH START Set Reset RS_ST_DIFF_STR_Y
SPS 200kV R212_P643_87R PROTECTION DIFFERENTIAL PROTECTION BPH START Set Reset RS_ST_DIFF_STR_B
SPS 200kV R212_P643_87R PROTECTION DIFFERENTIAL BLOCKED Set Reset RS_ST_DIFF_BLK
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Trip SPS 200kV R212_P643_87R SYSTEM REACTOR BUCHHOLZ Operated Reset RS_TR_BUCHHOLZ1 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Reset_Trip SPS 200kV R212_P643_87R SYSTEM REACTOR WTI TRIP Operated Reset RS_TR_WTI Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Trip SPS 200kV R212_P643_87R SYSTEM REACTOR PNRV Trip Reset RS_TR_PNRV Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
SPS 200kV R212_P643_87R SYSTEM REACTOR PRD Operated Reset RS_OP_PRD-2 System;OptGGIO1 ST;Ind11;stVal;SPS
SPS 200kV R212_P643_87R SYSTEM REACTOR OTI ALARM Set Reset RS_ST_OTI ALM System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 200kV R212_P643_87R SYSTEM REACTOR OSR TRIP Operated Reset RS_OP_OSR_TR System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 200kV R212_P643_87R SYSTEM REACTOR OIL LOW LEVEL ALARM Set Reset RS_ST_OIL LO_ AL System;OptGGIO1 ST;IndXX;stVal;SPS
A SPARE SPS 200kV R212_P643_87R SYSTEM FIRE PROTECTION Operated Reset RS_OP_FIRE_PTR System;OptGGIO1 ST;IndXX;stVal;SPS None No 1 #REF!
DIGITAL INFORMATION TO IED SPS 400kV R412_P643_87R
Iss. Customer Ref IED DO Reference Electrical Data SPS 400kV Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
ANALOG INFORMATION FROM IED SPS 400kV R412_P643_87R
Iss. Customer Ref IED AI Reference Electrical Data SPS 400kV Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 400kV Yes 6 ANALOG INFORMATION FROM IED IED name R412_P643_87R
A SPARE SPS 400kV Yes 6 ANALOG INFORMATION FROM IED IED name R412_P643_87R
A SPARE SPS 400kV Yes 6 ANALOG INFORMATION FROM IED IED name R412_P643_87R
A SPARE SPS 400kV Yes 6 ANALOG INFORMATION FROM IED IED name R412_P643_87R
ANALOG INFORMATION TO IED SPS 400kV R412_P643_87R
Iss. Customer Ref IED AI Reference Electrical Data SPS 400kV Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 400kV 13 ANALOG INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 13 ANALOG INFORMATION TO IED IED name R412_P643_87R
COUNTER INFORMATION FROM IED SPS 400kV R412_P643_87R
Iss. Customer Ref IED Counter Reference Electrical Data SPS 400kV Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 400kV Yes 39 COUNTER INFORMATION FROM IED IED name R412_P643_87R
A SPARE SPS 400kV Yes 39 COUNTER INFORMATION FROM IED IED name R412_P643_87R
A SPARE SPS 400kV Yes 39 COUNTER INFORMATION FROM IED IED name R412_P643_87R
A SPARE SPS 400kV Yes 39 COUNTER INFORMATION FROM IED IED name R412_P643_87R
END OF IED DATA SPS 400kV
DI GROUPS SPS 400kV
Iss. Customer Ref Group DI Reference Electrical Data SPS 400kV Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 2 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 3 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 4 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 5 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 6 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 7 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 8 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 9 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 10 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 11 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 12 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 13 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 14 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 15 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 16 SPARE SPS 400kV None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION SPS 400kV
Iss. Customer Ref Self DI Reference Electrical Data SPS 400kV Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION SPS 400kV
Iss. Customer Ref Self DO Reference Electrical Data SPS 400kV Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION SPS 400kV
Iss. Customer Ref Self AI Reference Electrical Data SPS 400kV Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION SPS 400kV
Iss. Customer Ref Self Counter Reference Electrical Data SPS 400kV Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION SPS 400kV
Iss. Customer Ref SetPoint Reference Electrical Data SPS 400kV Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
END OF DATA SPS 400kV
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R412_P141_64R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R412_P141_64R
DIGITAL INFORMATION FROM IED IED name R412_P141_64R
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 200kV R212_P141_64R PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R412_P141_64R
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 200kV R212_P141_64R PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 200kV R212_P141_64R SYSTEM B/U IMPEDENCE PROT RELAY Healthy Unhealthy UH_HL_B/U IMP Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 200kV R212_P141_64R SYSTEM 87R (REACTOR DIFFERENTIAL) RELAY Healthy Unhealthy UH_HL_87R(R DIF) Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 200kV R212_P141_64R SYSTEM 86B TRIP RELAY SUPERVISION Healthy Unhealthy UH_HL_86B Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 200kV R212_P141_64R PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
SPS 200kV R212_P141_64R PROTECTION REF TRIP Operated Reset RS_OP_REF Transmitted to IEC Protection;SenRefPDIF1 ST;Op;general;general;ACT
SPS 200kV R212_P141_64R PROTECTION REF ALARM Set Reset RS_ST_REF ALM
SPS 200kV R212_P141_64R PROTECTION REF R PH TRIP Operated Reset RS_OP_REF_R
A Protection;SenRefPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 200kV R212_P141_64R PROTECTION REF Y PH TRIP Operated Reset RS_OP_REF_Y None 1 #REF!
A SPARE SPS 200kV R212_P141_64R PROTECTION REF B PH TRIP Operated Reset RS_OP_REF_B None No 1 #REF!
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLA_Reset_Trip SPS 200kV R212_P141_64R SYSTEM REACTOR WTI ALARM Set Reset RS_TR_REC PRV Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Trip SPS 200kV R212_P141_64R SYSTEM REACTOR OTI TRIP Operated Reset RS_TR_REC OTI Transmitted to IEC System;OptGGIO1 ST;Ind2;stVal;SPS None 1 #REF!
SPS 200kV R212_P141_64R SYSTEM BUCHHOLZ ALARM Set Reset RS_TR_BUCH Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS
DIGITAL INFORMATION TO IED IED name R412_P141_64R
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
ANALOG INFORMATION FROM IED IED name R412_P141_64R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P141_64R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P141_64R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P141_64R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P141_64R
ANALOG INFORMATION TO IED IED name R412_P141_64R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R412_P141_64R
A SPARE 13 ANALOG INFORMATION TO IED IED name R412_P141_64R
COUNTER INFORMATION FROM IED IED name R412_P141_64R
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P141_64R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P141_64R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P141_64R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P141_64R
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R412_P442_21R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R412_P442_21R
DIGITAL INFORMATION FROM IED IED name R412_P442_21R
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R412_P442_21R PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R412_P442_21R
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R412_P442_21R PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R412_P442_21R
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P442_21R PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;CbfRBRF1 ST;OpEx;general;ACT SPE_HLA_Normal_Fail SPS 400kV R412_P442_21R PROTECTION VT FUSE FAIL Alarm Normal NL_FL_VT FUSE Transmitted to IEC System;AlmGGIO1 ST;Alm6;stVal;SPS None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P442_21R PROTECTION BACKUP IMPEDENCE R-PH TRIP Operated Reset RS_OP_B/U IMP R Transmitted to IEC Protection;DisPDIS1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P442_21R PROTECTION BACKUP IMPEDENCE Y-PH TRIP Operated Reset RS_OP_B/U IMP Y Transmitted to IEC Protection;DisPDIS1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P442_21R PROTECTION BACKUP IMPEDENCE B-PH TRIP Operated Reset RS_OP_B/U IMP B Transmitted to IEC Protection;DisPDIS1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P442_21R PROTECTION BACKUP IMPEDENCE Operated Reset RS_OP_B/U IMP Transmitted to IEC Protection;DisPDIS1 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Str;general;general;ACD SPE_HLA_Reset_Start SPS 400kV R412_P442_21R PROTECTION REACTOR BACKUP IMPEDANE PICKUP set Reset RS_ST_Z1 START Transmitted to IEC Protection;DisPDIS1 ST;Str;general;general;ACD None 1 #REF!
A SPARE SPS 400kV R412_P442_21R PROTECTION BACKUP IMPEDANCE Z-1 TRIP Operated Reset RS_OP_Z1_TRP None No 1 #REF!
DIGITAL INFORMATION TO IED SPS IED name R412_P442_21R
Iss. Customer Ref IED DO Reference Electrical Data SPS Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
ANALOG INFORMATION FROM IED SPS IED name R412_P442_21R
Iss. Customer Ref IED AI Reference Electrical Data SPS Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS Yes 6 ANALOG INFORMATION FROM IED IED name R412_P442_21R
A SPARE SPS Yes 6 ANALOG INFORMATION FROM IED IED name R412_P442_21R
A SPARE SPS Yes 6 ANALOG INFORMATION FROM IED IED name R412_P442_21R
A SPARE SPS Yes 6 ANALOG INFORMATION FROM IED IED name R412_P442_21R
ANALOG INFORMATION TO IED SPS IED name R412_P442_21R
Iss. Customer Ref IED AI Reference Electrical Data SPS Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 13 ANALOG INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 13 ANALOG INFORMATION TO IED IED name R412_P442_21R
COUNTER INFORMATION FROM IED SPS IED name R412_P442_21R
Iss. Customer Ref IED Counter Reference Electrical Data SPS Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS Yes 39 COUNTER INFORMATION FROM IED IED name R412_P442_21R
A SPARE SPS Yes 39 COUNTER INFORMATION FROM IED IED name R412_P442_21R
A SPARE SPS Yes 39 COUNTER INFORMATION FROM IED IED name R412_P442_21R
A SPARE SPS Yes 39 COUNTER INFORMATION FROM IED IED name R412_P442_21R
END OF IED DATA SPS
Iss. Customer Ref Group DI Reference Electrical Data SPS Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION SPS
Iss. Customer Ref Self DI Reference Electrical Data SPS Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION SPS
Iss. Customer Ref Self DO Reference Electrical Data SPS Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION SPS
Iss. Customer Ref Self AI Reference Electrical Data SPS Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION SPS
Iss. Customer Ref Self Counter Reference Electrical Data SPS Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION SPS
Iss. Customer Ref SetPoint Reference Electrical Data SPS Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
END OF DATA SPS
SPS 400kV R412_P442_21R PROTECTION BACKUP OVERCURRENT START Start Reset RS_ST_O/C Protection;OcpPTOC1 ST;Op;general;general;ACD
SPS 400kV R412_P442_21R PROTECTION BACKUP OVERCURRENT TRIP Operated Reset RS_OP_O/C Protection;OcpPTOC1 ST;Str;general;general;ACT
SPS 400kV R412_P442_21R PROTECTION BACKUP EARTHFAULT START Start Reset RS_ST_O/C Protection;EfdPTOC1 ST;Op;general;ACD
SPS 400kV R412_P442_21R PROTECTION BACKUP EARTHFAULT TRIP Operated Reset RS_OP_O/C Protection;EfdPTOC1 ST;Str;general;ACT
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
MiCOM C264 DESCRIPTION
Computer Name B201_ICT1 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) C264 Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 0
Digital Inputs Board Slot P
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A P 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 7 SPE_HLA_Normal_Alarm SPS 220kV B201_ICT1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL1 Transmitted to IEC CONTROL2;XCBR1 ST;Ind11;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 8 SPE_HLA_Normal_Alarm SPS 220kV B201_ICT1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL2 Transmitted to IEC CONTROL2;XCBR1 ST;Ind7;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 9 SPE_HLA_Normal_Alarm SPS 220kV B201_ICT1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL3 Transmitted to IEC CONTROL2;XCBR1 ST;Ind8;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 10 SPE_HLA_Normal_Alarm SPS 220kV B201_ICT1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL4 Transmitted to IEC CONTROL2;XCBR1 ST;Ind12;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 11 SPE_HLA_Normal_Alarm SPS 220kV B201_ICT1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL5 Transmitted to IEC CONTROL2;XCBR1 ST;Ind5;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 12 SPE_HLA_Normal_Alarm SPS 220kV B201_ICT1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL6 Transmitted to IEC CONTROL2;XCBR1 ST;Ind6;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 13 SPE_HLA_Normal_Alarm SPS 220kV B201_ICT1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL7 Transmitted to IEC CONTROL2;XCBR1 ST;Ind1;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 14 SPE_HLA_Normal_Alarm SPS 220kV B201_ICT1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL8 Transmitted to IEC CONTROL2;XCBR1 ST;Ind14;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 15 SPE_HLA_Normal_Alarm SPS 220kV B201_ICT1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL9 Transmitted to IEC CONTROL2;XCBR1 ST;Ind2;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 16 SPE_HLA_Normal_Alarm SPS 220kV B201_ICT1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL10 Transmitted to IEC CONTROL2;XCBR1 ST;Ind3;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 1
Digital Inputs Board Slot O
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A O 1 SPE_HLA_Normal_Alarm SPS 220kV B201_ICT1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL11 Transmitted to IEC CONTROL2;XCBR1 ST;Ind4;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 2 SPE_HLA_Normal_Alarm SPS 220kV B201_ICT1 52 CB TOUBLE Alarm Normal RS_OP_CB_TRBL12 Transmitted to IEC CONTROL2;XCBR1 ST;Ind10;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 3 SPE_HLA_Normal_Alarm SPS 220kV B201_ICT1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL13 Transmitted to IEC CONTROL2;XCBR1 ST;Ind13;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 4 SPE_HLA_Normal_Alarm SPS 220kV B201_ICT1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL14 Transmitted to IEC CONTROL2;XCBR1 ST;Ind9;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 5 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89A POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 12;192;20;5;6;7;8; None 2 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 6 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89A POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 12;192;20;5;6;7;8; None 2 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 7 DP_HLa_ESOpen_Close DPS 220kV B201_ICT1 89AE POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 10;11;2;3;4;6;7;8;9; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 8 DP_HLa_ESOpen_Close DPS 220kV B201_ICT1 89AE POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 10;11;2;3;4;6;7;8;9; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 9 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89B POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC 12;197;2;20;3;4;5; None 3 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 10 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC 12;197;2;20;3;4;5; None 3 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 11 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89T POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI4 ST;Pos;stVal;DPC 100;101;102;126;127;128;13;14;15;152;153;154;16;177;34;35;36;54;55;56;80;81;82; None 5 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 12 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89T POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI4 ST;Pos;stVal;DPC 100;101;102;126;127;128;13;14;15;152;153;154;16;177;34;35;36;54;55;56;80;81;82; None 5 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 15 SPE_HLA_Normal_Alarm SPS 220kV B201_ICT1 PROTECTION FIRE DETECTED Alarm Normal NM_AL_FIRE_DET Transmitted to IEC CONTROL1;GGIO1 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A O 16 SPE_HLA_Off_On SPS 220kV B201_ICT1 PROTECTION AC COMPRESSOR-1&2 On Off OF_ON_AC_CM1_2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 2
Digital Inputs Board Slot N
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A N 1 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89C POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI3 ST;Pos;stVal;DPC 12;13;5; None 4 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 2 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89C POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI3 ST;Pos;stVal;DPC 12;13;5; None 4 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 3 DP_HLa_ESOpen_Close DPS 220kV B201_ICT1 89CE1 POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 10;11;2;3;4;6;7;8;9; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 4 DP_HLa_ESOpen_Close DPS 220kV B201_ICT1 89CE1 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 10;11;2;3;4;6;7;8;9; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 5 DP_HLa_ESOpen_Close DPS 220kV B201_ICT1 89CE2 POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI3 ST;Pos;stVal;DPC 10;11;14;15;16;9; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 6 DP_HLa_ESOpen_Close DPS 220kV B201_ICT1 89CE2 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI3 ST;Pos;stVal;DPC 10;11;14;15;16;9; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 7 DP_HLA_Trip_Closed DPS 220kV B201_ICT1 PROTECTION EMERGENCY/MANUAL CB POSITION Closed TR_CL_CB_EMER Transmitted to IEC CONTROL1;GGIO1 ST;DPCSO1;stVal;DPC None 1 DIGITAL INPUT BOARD DIU2xx
A N 8 DP_HLA_Trip_Closed DPS 220kV B201_ICT1 PROTECTION EMERGENCY/MANUAL CB POSITION Trip TR_CL_CB_EMER Transmitted to IEC CONTROL1;GGIO1 ST;DPCSO1;stVal;DPC None 1 DIGITAL INPUT BOARD DIU2xx
A N 9 SPE_HLA_Nrml_Optd SPS 220kV B201_ICT1 PROTECTION LBB Operated Normal NM_OP_LBB Transmitted to IEC CONTROL1;GGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 11 SPE_HLA_Normal_Fail SPS 220kV B201_ICT1 PROTECTION DC SUPPLY-1 Fail Normal NM_FL_DC SUP1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 12 SPE_HLA_Normal_Fail SPS 220kV B201_ICT1 PROTECTION DC SUPPLY-2 Fail Normal NM_FL_DC SUP2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind7;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 13 SPE_HLA_Healthy_Flty SPS 220kV B201_ICT1 PROTECTION TRIP COIL-1 Faulty Healthy HL_FT_TC1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 14 SPE_HLA_Healthy_Flty SPS 220kV B201_ICT1 PROTECTION TRIP COIL-2 Faulty Healthy HL_FT_TC2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 15 SPE_HLa_Reset_Transf SPS 220kV B201_ICT1 PROTECTION BAY IN TRANSFER MODE Reset Transferred NM_AL_TRNSFR_MOD Transmitted to IEC CONTROL1;GGIO1 ST;Ind9;stVal;SPS 20; None 1 DIGITAL INPUT BOARD DIU2xx
A N 16 SPE_HLA_Healthy_Flty SPS 220kV B201_ICT1 PROTECTION PUA RELAY Faulty Healthy UL_HL_PU_RLY Transmitted to IEC CONTROL1;GGIO1 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 3
Digital Inputs Board Slot M
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A M 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 4
Digital Inputs Board Slot L
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A L 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 0
Digital Outputs Board Slot E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A E 1 SC_DE_Reset_Set_Int_2 SPC 220kV B201_ICT1 VT SELECTION BUS-1 Set DS_SL_BUS1 Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO4;ctlVal;DPC 20<; 66 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 2 SC_DE_Reset_Set_Int_2 SPC 220kV B201_ICT1 VT SELECTION BUS-1 Set SL_DS_BUS1 Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO2;ctlVal;DPC 20<; 68 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 3 SC_DE_Reset_Set_Int_2 SPC 220kV B201_ICT1 VT SELECTION BUS-2 Set DS_SL_BUS2 Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO3;ctlVal;DPC 67 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 4 SC_DE_Reset_Set_Int_2 SPC 220kV B201_ICT1 VT SELECTION BUS-2 Set SL_DS_BUS2 Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO1;ctlVal;DPC 20<; 69 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A E 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 1
Digital Outputs Board Slot F
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A F 1 DC_SBO_Open_Close DPC 220kV B201_ICT1 52 CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI5 CO;Pos;sboClass;DPC 1 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 2 DC_SBO_Open_Close DPC 220kV B201_ICT1 52 CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI5 CO;Pos;sboClass;DPC 1 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 3 SC_DE_Reset_Set_1 SPC 220kV B201_ICT1 PROTECTION CB TRIP Set XX_XX_CB_TR1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO1;ctlVal;DPC 152 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 4 SC_DE_Reset_Set_1 SPC 220kV B201_ICT1 PROTECTION CB TRIP Set XX_XX_CB_TR2 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO2;ctlVal;DPC 151 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 5 SC_DE_Reset_Set_1 SPC 220kV B201_ICT1 PROTECTION CB TRIP Set XX_XX_CB_TR3 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO3;ctlVal;DPC 154 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 6 SC_DE_Reset_Set_1 SPC 220kV B201_ICT1 PROTECTION CB TRIP Set XX_XX_CB_TR4 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO4;ctlVal;DPC 153 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 7 SC_DE_Reset_Set_1 SPC 220kV B201_ICT1 PROTECTION CB TRIP Set XX_XX_CB_TR5 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO5;ctlVal;DPC 150 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A F 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 2
Digital Outputs Board Slot G
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A G 1 DC_SBO_Open_Close DPC 220kV B201_ICT1 89A CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 2 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 2 DC_SBO_Open_Close DPC 220kV B201_ICT1 89A CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 2 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 3 SC_DE_NotPerm_Perm SPC 220kV B201_ICT1 IL PERMISSIVE 89A I/L PERMISSIVE XX_XX_89A Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO1;ctlVal;DPC 59 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 4 SC_DE_NotPerm_Perm SPC 220kV B201_ICT1 IL PERMISSIVE 89AE I/L PERMISSIVE XX_XX_89AE Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO3;ctlVal;DPC 60 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 5 DC_SBO_Open_Close DPC 220kV B201_ICT1 89B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 3 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 6 DC_SBO_Open_Close DPC 220kV B201_ICT1 89B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 3 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 7 SC_DE_NotPerm_Perm SPC 220kV B201_ICT1 IL PERMISSIVE 89B I/L PERMISSIVE XX_XX_89B Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO2;ctlVal;DPC 61 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A G 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 3
Digital Outputs Board Slot H
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A H 1 DC_SBO_Open_Close DPC 220kV B201_ICT1 89C CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 4 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 2 DC_SBO_Open_Close DPC 220kV B201_ICT1 89C CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 4 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 3 SC_DE_NotPerm_Perm SPC 220kV B201_ICT1 IL PERMISSIVE 89C I/L PERMISSIVE XX_XX_89C Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO7;ctlVal;DPC 62 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 4 SC_DE_NotPerm_Perm SPC 220kV B201_ICT1 IL PERMISSIVE 89CE1 I/L PERMISSIVE XX_XX_89CE1 Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO4;ctlVal;DPC 63 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 5 SC_DE_NotPerm_Perm SPC 220kV B201_ICT1 IL PERMISSIVE 89CE2 I/L PERMISSIVE XX_XX_89CE2 Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO6;ctlVal;DPC 64 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 6 DC_SBO_Open_Close DPC 220kV B201_ICT1 89T CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 5 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 7 DC_SBO_Open_Close DPC 220kV B201_ICT1 89T CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 5 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 8 SC_DE_NotPerm_Perm SPC 220kV B201_ICT1 IL PERMISSIVE 89T I/L PERMISSIVE XX_XX_89T Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO5;ctlVal;DPC 65 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A H 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
ANALOG INPUT BOARD AIU21x
Analog Input Board Number 0
Analog Input Board Slot D
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE 6 ANALOG INPUT BOARD AIU21x
A 2 SPARE 6 ANALOG INPUT BOARD AIU21x
A 3 SPARE 6 ANALOG INPUT BOARD AIU21x
A 4 SPARE 6 ANALOG INPUT BOARD AIU21x
A 5 SPARE 6 ANALOG INPUT BOARD AIU21x
A 6 SPARE 6 ANALOG INPUT BOARD AIU21x
A 7 SPARE 6 ANALOG INPUT BOARD AIU21x
A 8 SPARE 6 ANALOG INPUT BOARD AIU21x
CT/VT ANALOG INPUT BOARD TMU2x0
CT/VT Board Number 0
CT/VT Board Slot Q
CT/VT Board Model TMU220
Nominal Current 1 (1A/5A)
Nominal Voltage 110.00 [1V … 500V]
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A DF MV_HLa_Frequency_1 Hz 220kV B201_ICT1 SYNCH DATA FREQUENCY DIFFERENCE 0.0 2.0 FREQUENCY DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifHzClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DV MV_hla_ AuxVoltage_1 V 220kV B201_ICT1 SYNCH DATA VOLTAGE DIFFERENCE 0.0 152.42494 VOLTAGE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifVClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Dj MV_hla_PhaseDiff ˚ 220kV B201_ICT1 SYNCH DATA PHASE DIFFERENCE 0.0 360.0 PHASE ANGLE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifAngClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ia MV_HLa_AuxCurrent A 220kV B201_ICT1 METERING I-R PHASE CURRENT 0.0 1920.0 IR PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ib MV_HLa_AuxCurrent A 220kV B201_ICT1 METERING I-Y PHASE CURRENT 0.0 1920.0 IY PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ic MV_HLa_AuxCurrent A 220kV B201_ICT1 METERING I-B PHASE CURRENT 0.0 1920.0 IB PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsC;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vb MV_hla_ AuxVoltage_1 V 220kV B201_ICT1 SYNCH DATA INCOMING SUPPLY 0.0 152.42494 INCOMING SUPPLY Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;PhV;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uab MV_hla_ AuxVoltage V 220kV B201_ICT1 METERING R-Y VOLTAGE 0.0 264.0 R-Y VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsAB;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ubc MV_HLa_Voltage kV 220kV B201_ICT1 METERING Y-B VOLTAGE 0.0 264.0 Y-B VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsBC;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uca MV_HLa_Voltage kV 220kV B201_ICT1 METERING B-R VOLTAGE 0.0 264.0 B-R VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsCA;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar MV_hla_ AuxVoltage_1 V 220kV B201_ICT1 SYNCH DATA RUNNING SUPPLY 0.0 152.42494 RUNNING SUPPLY Transmitted to IEC MEASUREMENT1;barMMXU1 MX;PhV;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Freq (Line) MV_HLa_Frequency Hz 220kV B201_ICT1 METERING FREQUENCY 45.0 55.0 FREQUENCY Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;Hz;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A P total (MW) MV_HLa_ActPower_1 MW 220kV B201_ICT1 METERING ACTIVE POWER -731.5968 731.5968 ACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotW;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Q total (Mvar) MV_HLa_ActPower_1 MW 220kV B201_ICT1 METERING REACTIVE POWER -731.5968 731.5968 REACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotVAr;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A cos ft : Power factor MV_HLa_PowerFactor 220kV B201_ICT1 METERING POWER FACTOR -1.2 1.2 POWER FACTOR Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotPF;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 89A IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI1 ST;IndSys1;stVal;SPS 2<; None 59 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 89AE IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI2 ST;IndSys1;stVal;SPS 5<; None 60 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 89B IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI2 ST;IndSys1;stVal;SPS 6<; None 61 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 89C IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI3 ST;IndSys1;stVal;SPS 9<; None 62 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 89CE1 IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI1 ST;IndSys1;stVal;SPS 12<; None 63 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 89CE2 IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI3 ST;IndSys1;stVal;SPS 13<; None 64 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 89T IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI4 ST;IndSys1;stVal;SPS 14<; None 65 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPE_HLa_Reset_Set SPS 220kV B201_ICT1 SYNCH DATA CLOSE PERMISSIVE Set Reset RS_ST_CB CLOSE Transmitted to IEC CONTROL1;GAPC1 ST;IndSys5;stVal;SPS 18<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPE_HLa_Reset_Set SPS 220kV B201_ICT1 SYNCH DATA DEAD INCOMING DEAD RUNNING Set Reset RS_ST_DINC_DRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys4;stVal;SPS 18<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPE_HLa_Reset_Set SPS 220kV B201_ICT1 SYNCH DATA DEAD INCOMING LIVE RUNNING Set Reset RS_ST_DINC_LRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys3;stVal;SPS 18<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPE_HLa_Reset_Set SPS 220kV B201_ICT1 SYNCH DATA LIVE INCOMING DEAD RUNNING Set Reset RS_ST_LINC_DRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys2;stVal;SPS 18<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPE_HLa_Reset_Set SPS 220kV B201_ICT1 SYNCH DATA LIVE INCOMING LIVE RUNNING Set Reset RS_ST_LINC_LRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys1;stVal;SPS 18<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPE_HLa_Dselect_Select SPS 220kV B201_ICT1 VT SELECTION BUS-1 Selected Deselected DS_SL_BUS1 Transmitted to IEC CONTROL1;GAPC3 ST;IndSys1;stVal;SPS 20<; None 66 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPE_HLa_Dselect_Select SPS 220kV B201_ICT1 VT SELECTION BUS-2 Selected Deselected DS_SL_BUS2 Transmitted to IEC CONTROL1;GAPC3 ST;IndSys2;stVal;SPS 20<; None 67 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPE_HLa_Dselect_Select SPS 220kV B201_ICT1 VT SELECTION BUS-1 Selected Deselected SL_DS_BUS1 Transmitted to IEC CONTROL1;GAPC3 ST;IndSys4;stVal;SPS 20<; None 68 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPE_HLa_Dselect_Select SPS 220kV B201_ICT1 VT SELECTION BUS-2 Selected Deselected SL_DS_BUS2 Transmitted to IEC CONTROL1;GAPC3 ST;IndSys3;stVal;SPS 20<; None 69 1 C264 SELF GENERATED DIGITAL INFORMATION
A 17 SPE_HLa_Reset_Set SPS 220kV B201_ICT1 52 | OE_CL_CONTROL OPEN ORDER Set Reset RS_ST_OPN ORD Transmitted to IEC CONTROL1;CSWI5 ST;OpnOrd;general;general;ACT None 150;151;152;153;154 CB OpenOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 18 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 89A | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 19 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 89B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO2 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 20 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 89C | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO3 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 21 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 89T | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO4 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 22 SPS_hla_Set_Reset SPS 220kV B201_ICT1 ORDER RUNNING ON THE BAY Set Reset RS_ST_ORD RUNING Transmitted to IEC CONTROL1;GBAY1 ST;OrdRun;stVal;SPS None OrderInProgress 1 C264 SELF GENERATED DIGITAL INFORMATION
A 23 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 52 | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLOSE ILK Transmitted to IEC CONTROL2;CILO5 ST;EnaCls;stVal;SPS None CB CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 24 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 89A | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 25 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 89B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO2 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 26 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 89C | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO3 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 27 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 89T | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO4 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 28 SPE_HLa_Reset_Set SPS 220kV B201_ICT1 SYNCH FUNCTION CLOSE ORDER Set Reset RS_ST_CLS ODR Transmitted to IEC CONTROL1;RSYN1 ST;ClsOpSt;stVal;SPS None IntManualCSFct CS_CloseOrderState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 29 SPE_HLA_on_off SPS 220kV B201_ICT1 SYNCH FUNCTION ON/OFF SECONDARY SPS Off On RS_ST_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 ST;EnaSec;origin;SPC None 182 IntManualCSFct CS_OnOff_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 30 SPE_HLa_Reset_Set SPS 220kV B201_ICT1 SYNCH FUNCTION POSSIBLE CLOSING Set Reset RS_ST_POS CLS Transmitted to IEC CONTROL1;RSYN1 ST;Rel;stVal;SPS 18; None IntManualCSFct CS_AuthoState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 31 SPE_HLa_Reset_Set SPS 220kV B201_ICT1 SYNCH FUNCTION PRESENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF U PRES Transmitted to IEC CONTROL1;RSYN1 ST;VRefInd;stVal;SPS 18; None IntManualCSFct CS_VoltageRefPresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 32 SPE_HLa_Reset_Set SPS 220kV B201_ICT1 SYNCH FUNCTION ABSENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF. U ABS Transmitted to IEC CONTROL1;RSYN1 ST;VRefAbs;stVal;SPS 18; None IntManualCSFct CS_VoltageRefAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 33 SPE_HLa_Reset_Set SPS 220kV B201_ICT1 SYNCH FUNCTION RS_ST_V CHOICE Set Reset RS_ST_V CHOICE Transmitted to IEC CONTROL1;RSYN1 ST;BusVC;stVal;SPS None IntManualCSFct CS_BusBarVChoice_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 34 SPE_HLa_Reset_Set SPS 220kV B201_ICT1 SYNCH FUNCTION VOLT ABSENCE Set Reset RS_ST_VOLT ABS Transmitted to IEC CONTROL1;RSYN1 ST;VAbs;stVal;SPS 18; None IntManualCSFct CS_VoltageAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 35 SPE_HLa_Reset_Set SPS 220kV B201_ICT1 SYNCH FUNCTION VOLT PRESENCE Set Reset RS_ST_VOLT PRES Transmitted to IEC CONTROL1;RSYN1 ST;VP;stVal;SPS 18; None IntManualCSFct CS_VoltagePresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 36 SPE_HLa_Notper_Perm SPS 220kV B201_ICT1 52 | OE_CL_CONTROL CLOSE ORDER Permissive Not Permissive RS_ST_CLS ORD Transmitted to IEC CONTROL1;CSWI5 ST;ClsOrd;general;general;ACT None CB CloseOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 37 DP_HLA_CBOpen_Close DPS 220kV B201_ICT1 52 POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI5 ST;Pos;stVal;DPC 10;11;2;3;4;6;7;8;9; None 1 17 CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 38 DP_HLA_CBOpen_Close DPS 220kV B201_ICT1 52 POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI5 ST;Pos;stVal;DPC 10;11;2;3;4;6;7;8;9; None 1 17 CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 39 DP_HLA_Trip_Closed DPS 220kV B201_ICT1 52 EMERGENCY/MANUAL Trip TP_CL_EMRG/MAN Transmitted to IEC CONTROL1;CSWI5 ST;DPCSO1;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 40 DP_HLA_Trip_Closed DPS 220kV B201_ICT1 52 EMERGENCY/MANUAL Closed TP_CL_EMRG/MAN Transmitted to IEC CONTROL1;CSWI5 ST;DPCSO1;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 41 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89A COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 42 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89A COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 43 DP_HLa_ESOpen_Close DPS 220kV B201_ICT1 89AE COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 44 DP_HLa_ESOpen_Close DPS 220kV B201_ICT1 89AE COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 45 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89B COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 46 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89B COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 47 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89C COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 48 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89C COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 49 DP_HLa_ESOpen_Close DPS 220kV B201_ICT1 89CE1 COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 50 DP_HLa_ESOpen_Close DPS 220kV B201_ICT1 89CE1 COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 51 DP_HLa_ESOpen_Close DPS 220kV B201_ICT1 89CE2 COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 52 DP_HLa_ESOpen_Close DPS 220kV B201_ICT1 89CE2 COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 53 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89T COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 54 DP_HLA_ ISOOpen_Close DPS 220kV B201_ICT1 89T COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 55 DP_HLa_LocRem_Bay DPS 220kV B201_ICT1 BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 6 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 56 DP_HLa_LocRem_Bay DPS 220kV B201_ICT1 BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 6 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 57 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SC_DE_Off_On SPC 220kV B201_ICT1 SYNCH FUNCTION ON/OFF SECONDARY CONTROL SPC On Off OF_ON_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 CO;EnaSec;ctlVal;DPC 182 IntManualCSFct CS_CtrlOnOff_SPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 DC_DE_LocRem_BayCtrl DPC 220kV B201_ICT1 BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 6 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 DC_DE_LocRem_BayCtrl DPC 220kV B201_ICT1 BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 6 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 MV_hla_Temp ˚ Cel 220kV B201_ICT1 PROTECTION AC KIOSK TEMP 0.0 100.0 AC KIOSK TEMP Transmitted to IEC CONTROL1;GAPC2 MX;AnIn1;mag;MV 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 MV_HLa_Unused 220kV B201_ICT1 CB_COUNTER Count_Close 0.0 10000.0 Count_Close Transmitted to IEC CONTROL2;GAPC1 MX;AnIn2;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 MV_HLa_Unused 220kV B201_ICT1 CB_COUNTER Count_Open 0.0 10000.0 Count_Open Transmitted to IEC CONTROL2;GAPC1 MX;AnIn1;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 17 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 17 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 18 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 18 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 19 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 19 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 20 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 20 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 21 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 21 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 22 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 22 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 23 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 23 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 24 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 24 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 25 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R220_P741_87CU GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R220_P741_87CU
DIGITAL INFORMATION FROM IED IED name R220_P741_87CU
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R220_P741_87CU PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R220_P741_87CU
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 220kV R220_P741_87CU PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 220kV R220_P741_87CU PROTECTION ZONE-1 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 1 Transmitted to IEC System;GosGGIO2 ST;Ind5;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 220kV R220_P741_87CU PROTECTION ZONE-2 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 2 Transmitted to IEC System;GosGGIO2 ST;Ind6;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 220kV R220_P741_87CU PROTECTION ZONE-3 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 3 Transmitted to IEC System;GosGGIO2 ST;Ind7;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 220kV R220_P741_87CU PROTECTION ZONE-1 BUSBAR BLOCKED DUE TO COMM. Set Reset RS_ST_BB BLOCKC1 Transmitted to IEC System;GosGGIO2 ST;Ind8;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 220kV R220_P741_87CU PROTECTION ZONE-2 BUSBAR BLOCKED DUE TO COMM. Set Reset RS_ST_BB BLOCKC2 Transmitted to IEC System;GosGGIO2 ST;Ind9;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 220kV R220_P741_87CU PROTECTION ZONE-3 BUSBAR BLOCKED DUE TO COMM. Set Reset RS_ST_BB BLOCKC3 Transmitted to IEC System;GosGGIO2 ST;Ind10;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 220kV R220_P741_87CU PROTECTION ZONE-1 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI1 Transmitted to IEC System;GosGGIO2 ST;Ind11;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 220kV R220_P741_87CU PROTECTION ZONE-2 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI2 Transmitted to IEC System;GosGGIO2 ST;Ind12;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 220kV R220_P741_87CU PROTECTION ZONE-3 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI3 Transmitted to IEC System;GosGGIO2 ST;Ind13;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLa_Reset_Close SPS 220kV R220_P741_87CU SYSTEM B/B ZONE-1 IN Reset RS_IN_BB_Z1 Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLa_Reset_Close SPS 220kV R220_P741_87CU SYSTEM B/B ZONE-2 IN Reset RS_IN_BB_Z2 Transmitted to IEC System;OptGGIO1 ST;Ind3;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLa_Reset_Close SPS 220kV R220_P741_87CU SYSTEM B/B ZONE-3 IN Reset RS_IN_BB_Z2 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A Protection;CftPhsPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R220_P741_87CU PROTECTION ZONE-1 CIRCUITRY FAULT Operated Reset RS_OP_ZONE1 CFT Transmitted to IEC Protection;CftPhsPDIF1 ST;Op;general;general;ACT None 1 #REF!
A Protection;CftPhsPDIF2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 220kV R220_P741_87CU PROTECTION ZONE-2 CIRCUITRY FAULT Operated Reset RS_OP_ZONE2 CFT Transmitted to IEC Protection;CftPhsPDIF2 ST;Op;general;general;ACT None 1 #REF!
220kV R220_P741_87CU PROTECTION ZONE-3 CIRCUITRY FAULT Operated Reset RS_OP_ZONE3 CFT Transmitted to IEC Protection;CftPhsPDIF3 ST;Op;general;general;ACT
A Protection;TrpPhsPDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 220kV R220_P741_87CU PROTECTION B/B ZONE-1 Operated Reset RS_OP_ZONE1 Transmitted to IEC Protection;TrpPhsPDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 220kV R220_P741_87CU PROTECTION B/B ZONE-2 Operated Reset RS_OP_ZONE2 Transmitted to IEC Protection;TrpPhsPDIF2 ST;Op;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 220kV R220_P741_87CU PROTECTION B/B ZONE-3 Operated Reset RS_OP_ZONE3 CFT Transmitted to IEC Protection;TrpPhsPDIF3 ST;Op;general;ACT None 1 #REF!
A SPARE SPS 220kV R220_P741_87CU PROTECTION ZONE MERGE SET Reset None No 1 #REF!
SPS 220kV R220_P741_87CU PROTECTION BUSBAR ZONE 1 R- PHASE TRIP
SPS 220kV R220_P741_87CU PROTECTION BUSBAR ZONE 1 Y- PHASE TRIP
SPS 220kV R220_P741_87CU PROTECTION BUSBAR ZONE 1 B- PHASE TRIP
SPS 220kV R220_P741_87CU PROTECTION BUSBAR ZONE 2 R- PHASE TRIP
SPS 220kV R220_P741_87CU PROTECTION BUSBAR ZONE 2 Y- PHASE TRIP
SPS 220kV R220_P741_87CU PROTECTION BUSBAR ZONE 2 B- PHASE TRIP
SPS 220kV R220_P741_87CU PROTECTION BUSBAR ZONE 3 R- PHASE TRIP
SPS 220kV R220_P741_87CU PROTECTION BUSBAR ZONE 3 Y- PHASE TRIP
SPS 220kV R220_P741_87CU PROTECTION BUSBAR ZONE 3 B- PHASE TRIP
DIGITAL INFORMATION TO IED IED name R220_P741_87CU
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R220_P741_87CU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R220_P741_87CU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R220_P741_87CU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R220_P741_87CU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R220_P741_87CU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R220_P741_87CU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R220_P741_87CU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R220_P741_87CU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R220_P741_87CU
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R220_P741_87CU
ANALOG INFORMATION FROM IED IED name R220_P741_87CU
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R220_P741_87CU
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R220_P741_87CU
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R220_P741_87CU
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R220_P741_87CU
ANALOG INFORMATION TO IED IED name R220_P741_87CU
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R220_P741_87CU
A SPARE 13 ANALOG INFORMATION TO IED IED name R220_P741_87CU
COUNTER INFORMATION FROM IED IED name R220_P741_87CU
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R220_P741_87CU
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R220_P741_87CU
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R220_P741_87CU
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R220_P741_87CU
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
MiCOM C264 DESCRIPTION
Computer Name B203_LINE1 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) C264 Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 0
Digital Inputs Board Slot P
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A P 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 7 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL1 Transmitted to IEC CONTROL2;XCBR1 ST;Ind11;stVal;SPS 57;58;59; None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 8 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL2 Transmitted to IEC CONTROL2;XCBR1 ST;Ind7;stVal;SPS 58; None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 9 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL3 Transmitted to IEC CONTROL2;XCBR1 ST;Ind8;stVal;SPS 58; None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 10 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL4 Transmitted to IEC CONTROL2;XCBR1 ST;Ind12;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 11 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL5 Transmitted to IEC CONTROL2;XCBR1 ST;Ind5;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 12 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL6 Transmitted to IEC CONTROL2;XCBR1 ST;Ind6;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 13 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL7 Transmitted to IEC CONTROL2;XCBR1 ST;Ind1;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 14 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL8 Transmitted to IEC CONTROL2;XCBR1 ST;Ind14;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 15 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL9 Transmitted to IEC CONTROL2;XCBR1 ST;Ind2;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 16 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL10 Transmitted to IEC CONTROL2;XCBR1 ST;Ind3;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 1
Digital Inputs Board Slot O
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A O 1 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL11 Transmitted to IEC CONTROL2;XCBR1 ST;Ind4;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 2 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 52 CB TOUBLE Alarm Normal RS_OP_CB_TRBL12 Transmitted to IEC CONTROL2;XCBR1 ST;Ind10;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 3 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL13 Transmitted to IEC CONTROL2;XCBR1 ST;Ind13;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 4 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL14 Transmitted to IEC CONTROL2;XCBR1 ST;Ind9;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 5 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89A POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 192;45;46;47;48;52;64;66; None 14 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 6 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89A POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 192;45;46;47;48;52;64;66; None 14 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 7 DP_HLa_ESOpen_Close DPS 220kV B203_LINE1 89AE POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 42;43;44;46;47;48;49;50;51; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 8 DP_HLa_ESOpen_Close DPS 220kV B203_LINE1 89AE POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 42;43;44;46;47;48;49;50;51; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 9 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89B POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC 197;42;43;44;45;52;64;66; None 15 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 10 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC 197;42;43;44;45;52;64;66; None 15 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 11 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89T POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI4 ST;Pos;stVal;DPC 100;101;102;126;127;128;14;15;152;153;154;16;177;34;35;36;53;54;55;56;80;81;82; None 17 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 12 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89T POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI4 ST;Pos;stVal;DPC 100;101;102;126;127;128;14;15;152;153;154;16;177;34;35;36;53;54;55;56;80;81;82; None 17 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 15 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 PROTECTION FIRE DETECTED Alarm Normal NM_AL_FIRE_DET Transmitted to IEC CONTROL1;GGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A O 16 SPE_HLA_Off_On SPS 220kV B203_LINE1 PROTECTION AC COMPRESSOR-1&2 On Off OF_ON_AC_CM1_2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 2
Digital Inputs Board Slot N
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A N 1 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89C POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI3 ST;Pos;stVal;DPC 45;52;53; None 16 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 2 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89C POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI3 ST;Pos;stVal;DPC 45;52;53; None 16 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 3 DP_HLa_ESOpen_Close DPS 220kV B203_LINE1 89CE1 POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 42;43;44;46;47;48;49;50;51; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 4 DP_HLa_ESOpen_Close DPS 220kV B203_LINE1 89CE1 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 42;43;44;46;47;48;49;50;51; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 5 DP_HLa_ESOpen_Close DPS 220kV B203_LINE1 89CE2 POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI3 ST;Pos;stVal;DPC 49;50;51;54;55;56; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 6 DP_HLa_ESOpen_Close DPS 220kV B203_LINE1 89CE2 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI3 ST;Pos;stVal;DPC 49;50;51;54;55;56; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 11 SPE_HLA_Reset_Optd SPS 220kV B203_LINE1 AR FUNCTION R-PH INITIATION Operated Reset RS_OP_PHR INI Transmitted to IEC CONTROL1;RREC1 ST;Ind2;stVal;SPS 58; None ARFct TripPhA_SPS 1 DIGITAL INPUT BOARD DIU2xx
A N 12 SPE_HLA_Reset_Optd SPS 220kV B203_LINE1 AR FUNCTION Y-PH INITIATION Operated Reset RS_OP_PHY INI Transmitted to IEC CONTROL1;RREC1 ST;Ind3;stVal;SPS 58; None ARFct TripPhB_SPS 1 DIGITAL INPUT BOARD DIU2xx
A N 13 SPE_HLA_Reset_Optd SPS 220kV B203_LINE1 AR FUNCTION B-PH INITIATION Operated Reset RS_OP_PHB INI Transmitted to IEC CONTROL1;RREC1 ST;Ind4;stVal;SPS 58; None ARFct TripPhC_SPS 1 DIGITAL INPUT BOARD DIU2xx
A N 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 3
Digital Inputs Board Slot M
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A M 1 DP_HLA_Trip_Closed DPS 220kV B203_LINE1 PROTECTION EMERGENCY/MANUAL CB POSITION Closed TR_CL_CB_EMER Transmitted to IEC CONTROL1;GGIO1 ST;DPCSO1;stVal;DPC None 1 DIGITAL INPUT BOARD DIU2xx
A M 2 DP_HLA_Trip_Closed DPS 220kV B203_LINE1 PROTECTION EMERGENCY/MANUAL CB POSITION Trip TR_CL_CB_EMER Transmitted to IEC CONTROL1;GGIO1 ST;DPCSO1;stVal;DPC None 1 DIGITAL INPUT BOARD DIU2xx
A M 3 SPE_HLA_Normal_Fail SPS 220kV B203_LINE1 PROTECTION DC SUPPLY-1 Fail Normal NM_FL_DC SUP1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind9;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 4 SPE_HLA_Normal_Fail SPS 220kV B203_LINE1 PROTECTION DC SUPPLY-2 Fail Normal NM_FL_DC SUP-2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind10;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 5 SPE_HLA_Nrml_Optd SPS 220kV B203_LINE1 PROTECTION AUTO-RECLOSE LOCKOUT RELAY Operated Normal NM_OP_AR_LO_REL Transmitted to IEC CONTROL1;GGIO1 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 6 SPE_HLA_Healthy_Flty SPS 220kV B203_LINE1 PROTECTION TRIP COIL-1 Faulty Healthy HL_FT_TC1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind7;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 7 SPE_HLA_Healthy_Flty SPS 220kV B203_LINE1 PROTECTION TRIP COIL-2 Faulty Healthy HL_FT_TC2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 8 SPE_HLA_Normal_Fail SPS 220kV B203_LINE1 PROTECTION SPEECH CHANNEL Fail Normal NM_FL_SP_CH Transmitted to IEC CONTROL1;GGIO1 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 9 SPE_HLa_Reset_Transf SPS 220kV B203_LINE1 PROTECTION BAY IN TRANSFER MODE Reset Transferred NM_AL_TRNSFR_MOD Transmitted to IEC CONTROL1;GGIO1 ST;Ind3;stVal;SPS 62; None 1 DIGITAL INPUT BOARD DIU2xx
A M 10 SPE_HLA_Reset_Optd SPS 220kV B203_LINE1 AR FUNCTION AR BLOCK Operated Reset RS_OP_AR BLOCK Transmitted to IEC CONTROL1;RREC1 ST;Ind1;stVal;SPS None ARFct AR_Blocking_SPS 1 DIGITAL INPUT BOARD DIU2xx
A M 11 SPS 220kV B203_LINE1 AR FUNCTION BAY IN NORMAL MODE SET Reset RS_ST_NRML CONTROL1;GGIO1 ST;Ind112;stVal;SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 13 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 PROTECTION DT SEND CHANNEL-1 Alarm Normal NM_AL_DT_SD_CH1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind11;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 15 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 PROTECTION DT SEND CHANNEL-2 Alarm Normal NM_AL_DT_SD_CH2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 4
Digital Inputs Board Slot L
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A L 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 0
Digital Outputs Board Slot E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A E 1 SC_DE_Off_On SPC 220kV B203_LINE1 AR DATA A/R OFF On Off XX_XX_A/R OFF Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO2;ctlVal;DPC 1 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 2 SC_DE_Reset_Set SPC 220kV B203_LINE1 AR DATA MAIN CB A/R OPTD Set XX_XX_MAIN CB AR Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO5;ctlVal;DPC 89 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 3 SC_DE_Reset_Reset_2 SPC 220kV B203_LINE1 AR DATA A/R LOCKOUT TRIP Reset XX_XX_A/R L/O Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO3;ctlVal;DPC 88 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 4 SC_DE_Reset_Reset SPC 220kV B203_LINE1 AR DATA TO A/R CLSG. CKT Reset XX_XX_A/R CLSG C Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO1;ctlVal;DPC 90 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 5 SC_DE_Reset_Set SPC 220kV B203_LINE1 AR DATA TO TIE A/R PROIRITY CKT HOLD Set XX_XX_TI AR CKTH Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO4;ctlVal;DPC 91 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A E 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 1
Digital Outputs Board Slot F
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A F 1 DC_SBO_Open_Close DPC 220kV B203_LINE1 52 CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI5 CO;Pos;sboClass;DPC 13 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 2 DC_SBO_Open_Close DPC 220kV B203_LINE1 52 CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI5 CO;Pos;sboClass;DPC 13 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 3 SC_DE_Reset_Set_1 SPC 220kV B203_LINE1 PROTECTION CB TRIP Set XX_XX_CB_TR1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO1;ctlVal;DPC 161 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 4 SC_DE_Reset_Set_1 SPC 220kV B203_LINE1 PROTECTION CB TRIP Set XX_XX_CB_TR2 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO5;ctlVal;DPC 162 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 5 SC_DE_Reset_Set_1 SPC 220kV B203_LINE1 PROTECTION CB TRIP Set XX_XX_CB_TR3 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO6;ctlVal;DPC 160 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 6 SC_DE_Reset_Set_1 SPC 220kV B203_LINE1 PROTECTION CB TRIP Set XX_XX_CB_TR4 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO7;ctlVal;DPC 163 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 7 SC_DE_Reset_Set_1 SPC 220kV B203_LINE1 PROTECTION CB TRIP Set XX_XX_CB_TR5 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO8;ctlVal;DPC 164 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 9 SC_DE_Reset_Set_Int_2 SPC 220kV B203_LINE1 PROTECTION TRANSFER MODE Set XX_ST_TRNSFER_MO Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO9;ctlVal;DPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A F 10 SC_DE_Reset_Set_1 SPC 220kV B203_LINE1 PROTECTION NORMAL MODE Set XX_ST_NRML_MODE Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO10;ctlVal;DPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 2
Digital Outputs Board Slot G
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A G 1 DC_SBO_Open_Close DPC 220kV B203_LINE1 89A CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 14 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 2 DC_SBO_Open_Close DPC 220kV B203_LINE1 89A CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 14 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 3 SC_DE_NotPerm_Perm SPC 220kV B203_LINE1 IL PERMISSIVE 89A I/L PERMISSIVE XX_XX_89A Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO1;ctlVal;DPC 81 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 4 SC_DE_NotPerm_Perm SPC 220kV B203_LINE1 IL PERMISSIVE 89AE I/L PERMISSIVE XX_XX_89AE Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO3;ctlVal;DPC 82 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 5 DC_SBO_Open_Close DPC 220kV B203_LINE1 89B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 15 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 6 DC_SBO_Open_Close DPC 220kV B203_LINE1 89B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 15 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 7 SC_DE_NotPerm_Perm SPC 220kV B203_LINE1 IL PERMISSIVE 89B I/L PERMISSIVE XX_XX_89B Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO2;ctlVal;DPC 83 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 8 SC_DE_Reset_Set_1 SPC 220kV B203_LINE1 PROTECTION 86A TRIP RELAY Set XX_RS_86A_TR Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO11;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 9 SC_DE_Reset_Set_1 SPC 220kV B203_LINE1 PROTECTION 86B TRIP RELAY Set XX_RS_86B_TR Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO12;ctlVal;DPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A G 10 SC_DE_Reset_Set_Int_2 SPC 220kV B203_LINE1 PROTECTION AUTO-RECLOSE LOCKOUT RELAY Set XX_RS_AR_LO_REL Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO2;ctlVal;DPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 3
Digital Outputs Board Slot H
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A H 1 DC_SBO_Open_Close DPC 220kV B203_LINE1 89C CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 16 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 2 DC_SBO_Open_Close DPC 220kV B203_LINE1 89C CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 16 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 3 SC_DE_NotPerm_Perm SPC 220kV B203_LINE1 IL PERMISSIVE 89C I/L PERMISSIVE XX_XX_89C Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO7;ctlVal;DPC 84 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 4 SC_DE_NotPerm_Perm SPC 220kV B203_LINE1 IL PERMISSIVE 89CE1 I/L PERMISSIVE XX_XX_89CE1 Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO4;ctlVal;DPC 85 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 5 SC_DE_NotPerm_Perm SPC 220kV B203_LINE1 IL PERMISSIVE 89CE2 I/L PERMISSIVE XX_XX_89CE2 Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO6;ctlVal;DPC 86 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 6 DC_SBO_Open_Close DPC 220kV B203_LINE1 89T CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 17 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 7 DC_SBO_Open_Close DPC 220kV B203_LINE1 89T CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 17 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 8 SC_DE_NotPerm_Perm SPC 220kV B203_LINE1 IL PERMISSIVE 89T I/L PERMISSIVE XX_XX_89T Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO5;ctlVal;DPC 87 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 9 SC_DE_Reset_Set_1 SPC 220kV B203_LINE1 PROTECTION DT SEND CHANNEL-1 Set XX_XX_DT_SD_CH1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO3;ctlVal;DPC 93 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A H 10 SC_DE_Reset_Set_1 SPC 220kV B203_LINE1 PROTECTION DT SEND CHANNEL-2 Set XX_XX_DT_SD_CH2 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO4;ctlVal;DPC 92 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
ANALOG INPUT BOARD AIU21x
Analog Input Board Number 0
Analog Input Board Slot D
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE 6 ANALOG INPUT BOARD AIU21x
A 2 SPARE 6 ANALOG INPUT BOARD AIU21x
A 3 SPARE 6 ANALOG INPUT BOARD AIU21x
A 4 SPARE 6 ANALOG INPUT BOARD AIU21x
A 5 SPARE 6 ANALOG INPUT BOARD AIU21x
A 6 SPARE 6 ANALOG INPUT BOARD AIU21x
A 7 SPARE 6 ANALOG INPUT BOARD AIU21x
A 8 SPARE 6 ANALOG INPUT BOARD AIU21x
CT/VT ANALOG INPUT BOARD TMU2x0
CT/VT Board Number 0
CT/VT Board Slot Q
CT/VT Board Model TMU220
Nominal Current 1 (1A/5A)
Nominal Voltage 110.00 [1V … 500V]
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A DF MV_HLa_Frequency_1 Hz 220kV B203_LINE1 SYNCH DATA FREQUENCY DIFFERENCE 0.0 2.0 FREQUENCY DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifHzClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DV MV_hla_ AuxVoltage_1 V 220kV B203_LINE1 SYNCH DATA VOLTAGE DIFFERENCE 0.0 152.42494 VOLTAGE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifVClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Dj MV_hla_PhaseDiff ˚ 220kV B203_LINE1 SYNCH DATA PHASE DIFFERENCE 0.0 360.0 PHASE ANGLE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifAngClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ia MV_HLa_AuxCurrent A 220kV B203_LINE1 METERING I-R PHASE CURRENT 0.0 1920.0 IR PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ib MV_HLa_AuxCurrent A 220kV B203_LINE1 METERING I-Y PHASE CURRENT 0.0 1920.0 IY PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ic MV_HLa_AuxCurrent A 220kV B203_LINE1 METERING I-B PHASE CURRENT 0.0 1920.0 IB PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsC;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vb MV_hla_ AuxVoltage_1 V 220kV B203_LINE1 SYNCH DATA INCOMING SUPPLY 0.0 152.42494 INCOMING SUPPLY Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;PhV;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uab MV_hla_ AuxVoltage V 220kV B203_LINE1 METERING R-Y VOLTAGE 0.0 264.0 R-Y VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsAB;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ubc MV_HLa_Voltage kV 220kV B203_LINE1 METERING Y-B VOLTAGE 0.0 264.0 Y-B VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsBC;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uca MV_HLa_Voltage kV 220kV B203_LINE1 METERING B-R VOLTAGE 0.0 264.0 B-R VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsCA;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar MV_hla_ AuxVoltage_1 V 220kV B203_LINE1 SYNCH DATA RUNNING SUPPLY-1 0.0 152.42494 RUNNING SUPPLY-1 Transmitted to IEC MEASUREMENT1;barMMXU1 MX;PhV;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Freq (Line) MV_HLa_Frequency Hz 220kV B203_LINE1 METERING FREQUENCY 45.0 55.0 FREQUENCY Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;Hz;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A P total (MW) MV_HLa_ActPower_1 MW 220kV B203_LINE1 METERING ACTIVE POWER -731.5968 731.5968 ACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotW;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Q total (Mvar) MV_HLa_ActPower_1 MW 220kV B203_LINE1 METERING REACTIVE POWER -731.5968 731.5968 REACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotVAr;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar RMS 2 value of the busbar voltage phase MV_hla_ AuxVoltage_1 V 220kV B203_LINE1 SYNCH DATA RUNNING SUPPLY-2 0.0 152.42494 RUNNING SUPPLY-2 Transmitted to IEC MEASUREMENT1;GGIO1 MX;AnIn1;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A cos ft : Power factor MV_HLa_PowerFactor 220kV B203_LINE1 METERING POWER FACTOR -1.2 1.2 POWER FACTOR Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotPF;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 89A IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI1 ST;IndSys1;stVal;SPS 42<; None 81 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 89AE IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI2 ST;IndSys1;stVal;SPS 45<; None 82 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 89B IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI2 ST;IndSys1;stVal;SPS 46<; None 83 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 89C IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI3 ST;IndSys1;stVal;SPS 49<; None 84 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 89CE1 IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI1 ST;IndSys1;stVal;SPS 52<; None 85 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 89CE2 IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI3 ST;IndSys1;stVal;SPS 53<; None 86 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 89T IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI4 ST;IndSys1;stVal;SPS 54<; None 87 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPE_HLA_Reset_Optd SPS 220kV B203_LINE1 AR DATA LOCKOUT FROM AR LOGIC Operated Reset RS_OP_AR LO FBD Transmitted to IEC CONTROL1;GAPC3 ST;IndSys5;stVal;SPS 58<; None 88 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 AR DATA A/R OPTD FROM FBD Set Reset RS_ST_AR OPTD FB Transmitted to IEC CONTROL1;GAPC3 ST;IndSys6;stVal;SPS 57<; None 89;90 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 AR DATA PRIORITY CIRCUIT HOLD Set Reset RS_ST_PRI HLD ON Transmitted to IEC CONTROL1;GAPC3 ST;IndSys7;stVal;SPS 59<; None 91 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPE_HLA_Normal_Alarm SPS 220kV B203_LINE1 PROTECTION DT SEND Alarm Normal NM_AL_DT_SD Transmitted to IEC CONTROL1;GAPC2 ST;IndSys1;stVal;SPS 62<; None 92;93 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 SYNCH DATA CLOSE PERMISSIVE Set Reset RS_ST_CB CLOSE Transmitted to IEC CONTROL1;GAPC1 ST;IndSys5;stVal;SPS 63<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 SYNCH DATA DEAD INCOMING DEAD RUNNING Set Reset RS_ST_DINC_DRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys4;stVal;SPS 63<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 SYNCH DATA DEAD INCOMING LIVE RUNNING Set Reset RS_ST_DINC_LRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys3;stVal;SPS 63<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 SYNCH DATA LIVE INCOMING DEAD RUNNING Set Reset RS_ST_LINC_DRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys2;stVal;SPS 63<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 SYNCH DATA LIVE INCOMING LIVE RUNNING Set Reset RS_ST_LINC_LRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys1;stVal;SPS 63<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 17 SPE_HLa_Dselect_Select SPS 220kV B203_LINE1 VT SELECTION BUS-1 Selected Deselected DS_SL_BUS1 Transmitted to IEC CONTROL2;GAPC1 ST;IndSys1;stVal;SPS 66<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 18 SPE_HLa_Dselect_Select SPS 220kV B203_LINE1 VT SELECTION BUS-2 Selected Deselected DS_SL_BUS2 Transmitted to IEC CONTROL2;GAPC1 ST;IndSys2;stVal;SPS 66<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 19 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 52 | OE_CL_CONTROL OPEN ORDER Set Reset RS_ST_OPN ORD Transmitted to IEC CONTROL1;CSWI5 ST;OpnOrd;general;general;ACT 62; None 160;161;162;163;164 CB OpenOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 20 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 89A | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 21 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 89B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO2 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 22 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 89C | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO3 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 23 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 89T | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO4 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 24 SPS_hla_Set_Reset SPS 220kV B203_LINE1 ORDER RUNNING ON THE BAY Set Reset RS_ST_ORD RUNING Transmitted to IEC CONTROL1;GBAY1 ST;OrdRun;stVal;SPS None OrderInProgress 1 C264 SELF GENERATED DIGITAL INFORMATION
A 25 SPE_HLA_Reset_Optd SPS 220kV B203_LINE1 AR FUNCTION TRIP 3-PHASES Operated Reset RS_OP_TRP 3PH Transmitted to IEC CONTROL1;RREC1 ST;Trip3P;stVal;SPS None ARFct Trip_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 26 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 SYNCH FUNCTION CLOSE ORDER Set Reset RS_ST_CLS ODR Transmitted to IEC CONTROL1;RSYN1 ST;ClsOpSt;stVal;SPS None IntManualCSFct CS_CloseOrderState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 27 SPE_HLA_on_off SPS 220kV B203_LINE1 SYNCH FUNCTION ON/OFF SECONDARY SPS Off On RS_ST_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 ST;EnaSec;origin;SPC None 184 IntManualCSFct CS_OnOff_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 28 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 SYNCH FUNCTION POSSIBLE CLOSING Set Reset RS_ST_POS CLS Transmitted to IEC CONTROL1;RSYN1 ST;Rel;stVal;SPS 63; None IntManualCSFct CS_AuthoState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 29 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 SYNCH FUNCTION PRESENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF U PRES Transmitted to IEC CONTROL1;RSYN1 ST;VRefInd;stVal;SPS 63; None IntManualCSFct CS_VoltageRefPresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 30 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 SYNCH FUNCTION ABSENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF. U ABS Transmitted to IEC CONTROL1;RSYN1 ST;VRefAbs;stVal;SPS 63; None IntManualCSFct CS_VoltageRefAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 31 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 SYNCH FUNCTION RS_ST_V CHOICE Set Reset RS_ST_V CHOICE Transmitted to IEC CONTROL1;RSYN1 ST;BusVC;stVal;SPS 64<; None IntManualCSFct CS_BusBarVChoice_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 32 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 SYNCH FUNCTION VOLT ABSENCE Set Reset RS_ST_VOLT ABS Transmitted to IEC CONTROL1;RSYN1 ST;VAbs;stVal;SPS 53;63; None IntManualCSFct CS_VoltageAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 33 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 SYNCH FUNCTION VOLT PRESENCE Set Reset RS_ST_VOLT PRES Transmitted to IEC CONTROL1;RSYN1 ST;VP;stVal;SPS 63; None IntManualCSFct CS_VoltagePresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 34 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 52 | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLOSE ILK Transmitted to IEC CONTROL2;CILO5 ST;EnaCls;stVal;SPS None CB CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 35 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 52 | OE_CL_CONTROL CLOSE ORDER Permissive Not Permissive RS_ST_CLS ORD Transmitted to IEC CONTROL1;CSWI5 ST;ClsOrd;general;general;ACT 57; None CB CloseOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 36 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 89A | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 37 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 89B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO2 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 38 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 89C | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO3 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 39 SPE_HLa_Notper_Perm SPS 220kV B203_LINE1 89T | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO4 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 40 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 AR DATA LOCK Set Reset RS_ST_S10_LOCK Transmitted to IEC CONTROL1;GAPC3 ST;IndSys1;stVal;SPS 58; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 41 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 AR DATA WAIT FOR CB CLOSE Set Reset RS_ST_S7_WT CB C Transmitted to IEC CONTROL1;GAPC3 ST;IndSys4;stVal;SPS 57; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 42 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 AR DATA RECLAIM_TIMER Set Reset RS_ST_S8_RC TIM Transmitted to IEC CONTROL1;GAPC3 ST;IndSys3;stVal;SPS None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 43 SPE_HLa_Reset_Set SPS 220kV B203_LINE1 AR DATA LOCK_SHOTS Set Reset RS_ST_S9_LO SHTS Transmitted to IEC CONTROL1;GAPC3 ST;IndSys2;stVal;SPS 58; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 44 DP_HLA_CBOpen_Close DPS 220kV B203_LINE1 52 POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI5 ST;Pos;stVal;DPC 42;43;44;46;47;48;49;50;51; None 13 61 CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 45 DP_HLA_CBOpen_Close DPS 220kV B203_LINE1 52 POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI5 ST;Pos;stVal;DPC 42;43;44;46;47;48;49;50;51; None 13 61 CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 46 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89A COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 47 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89A COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 48 DP_HLa_ESOpen_Close DPS 220kV B203_LINE1 89AE COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 49 DP_HLa_ESOpen_Close DPS 220kV B203_LINE1 89AE COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 50 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89B COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 51 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89B COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 52 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89C COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 53 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89C COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 54 DP_HLa_ESOpen_Close DPS 220kV B203_LINE1 89CE1 COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 55 DP_HLa_ESOpen_Close DPS 220kV B203_LINE1 89CE1 COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 56 DP_HLa_ESOpen_Close DPS 220kV B203_LINE1 89CE2 COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 57 DP_HLa_ESOpen_Close DPS 220kV B203_LINE1 89CE2 COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 58 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89T COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 59 DP_HLA_ ISOOpen_Close DPS 220kV B203_LINE1 89T COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 60 DP_HLA_On_Off DPS 220kV B203_LINE1 AR FUNCTION ON/OFF STATUS On OF_ON_AR STATUS Transmitted to IEC CONTROL1;RREC1 ST;Ena;origin;DPC 59; None 18 1 ARFct AR_OnOff_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 61 DP_HLA_On_Off DPS 220kV B203_LINE1 AR FUNCTION ON/OFF STATUS Off OF_ON_AR STATUS Transmitted to IEC CONTROL1;RREC1 ST;Ena;origin;DPC 59; None 18 1 ARFct AR_OnOff_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 62 DP_HLa_LocRem_Bay DPS 220kV B203_LINE1 BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 19 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 63 DP_HLa_LocRem_Bay DPS 220kV B203_LINE1 BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 19 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 64 MP_HLA_AR_Fault MPS 220kV B203_LINE1 AR FUNCTION AUTORECLOSER FAULT STATUS AUTORECLOSER FLT Transmitted to IEC CONTROL1;RREC1 ST;ARFlt;stVal;INS None ARFct AR_FaultReason_MPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 65 MP_HLA_AR_Status MPS 220kV B203_LINE1 AR FUNCTION AUTORECLOSER STATUS AUTORECLOSER ST Transmitted to IEC CONTROL1;RREC1 ST;ARSt;stVal;INS 59; None ARFct AR_Status_MPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 66 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SC_DE_Reset_Set_Int SPC 220kV B203_LINE1 AR FUNCTION Force trip 3 Phase Set XX_XX_TRIP 3PH Transmitted to IEC CONTROL1;RREC1 CO;Trip3P;ctlVal;DPC ARFct Ctrl3PhaseTrip_SPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SC_DE_Off_On SPC 220kV B203_LINE1 SYNCH FUNCTION ON/OFF SECONDARY CONTROL SPC On Off OF_ON_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 CO;EnaSec;ctlVal;DPC 184 IntManualCSFct CS_CtrlOnOff_SPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SC_DE_Reset_Set_Int_2 SPC 220kV B203_LINE1 VT SELECTION BUS-2 Set DS_SL_BUS2 Transmitted to IEC CONTROL2;GAPC1 CO;SPCSO3;ctlVal;DPC 66<; 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SC_DE_Reset_Set_Int_2 SPC 220kV B203_LINE1 VT SELECTION BUS-1 Set SL_DS_BUS1 Transmitted to IEC CONTROL2;GAPC1 CO;SPCSO1;ctlVal;DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SC_DE_Reset_Set_Int_2 SPC 220kV B203_LINE1 VT SELECTION BUS-2 Set SL_DS_BUS2 Transmitted to IEC CONTROL2;GAPC1 CO;SPCSO2;ctlVal;DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 DC_DE_AROff_AROn DPC 220kV B203_LINE1 AR FUNCTION OFF Off OF_ON_A/R OFF Transmitted to IEC CONTROL1;RREC1 CO;Ena;ctlVal;DPC 18 ARFct AR_CtrlOnOff_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 DC_DE_AROff_AROn DPC 220kV B203_LINE1 AR FUNCTION OFF On OF_ON_A/R OFF Transmitted to IEC CONTROL1;RREC1 CO;Ena;ctlVal;DPC 18 ARFct AR_CtrlOnOff_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 DC_DE_LocRem_BayCtrl DPC 220kV B203_LINE1 BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 19 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 DC_DE_LocRem_BayCtrl DPC 220kV B203_LINE1 BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 19 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 MV_hla_Temp ˚ Cel 220kV B203_LINE1 PROTECTION AC KIOSK TEMP 0.0 100.0 AC KIOSK TEMP Transmitted to IEC CONTROL1;GAPC2 MX;AnIn1;mag;MV 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 MV_HLa_Unused 220kV B203_LINE1 CB_COUNTER Count_Close 0.0 10000.0 Count_Close Transmitted to IEC CONTROL2;GAPC2 MX;AnIn2;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 MV_HLa_Unused 220kV B203_LINE1 CB_COUNTER Count_Open 0.0 10000.0 Count_Open Transmitted to IEC CONTROL2;GAPC2 MX;AnIn1;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
MiCOM C264 DESCRIPTION
Computer Name B208_TBC GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) C264 Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 0
Digital Inputs Board Slot P
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A P 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 7 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL1 Transmitted to IEC CONTROL2;XCBR1 ST;Ind11;stVal;SPS 178;179;180; None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 8 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL2 Transmitted to IEC CONTROL2;XCBR1 ST;Ind7;stVal;SPS 179; None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 9 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL3 Transmitted to IEC CONTROL2;XCBR1 ST;Ind8;stVal;SPS 179; None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 10 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL4 Transmitted to IEC CONTROL2;XCBR1 ST;Ind12;stVal;SPS 179; None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 11 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL5 Transmitted to IEC CONTROL2;XCBR1 ST;Ind5;stVal;SPS 179; None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 12 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL6 Transmitted to IEC CONTROL2;XCBR1 ST;Ind6;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 13 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL7 Transmitted to IEC CONTROL2;XCBR1 ST;Ind1;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 14 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL8 Transmitted to IEC CONTROL2;XCBR1 ST;Ind14;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 15 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL9 Transmitted to IEC CONTROL2;XCBR1 ST;Ind2;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 16 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL10 Transmitted to IEC CONTROL2;XCBR1 ST;Ind3;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 1
Digital Inputs Board Slot O
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A O 1 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL11 Transmitted to IEC CONTROL2;XCBR1 ST;Ind4;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 2 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC 52 CB TOUBLE Alarm Normal RS_OP_CB_TRBL12 Transmitted to IEC CONTROL2;XCBR1 ST;Ind10;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 3 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL13 Transmitted to IEC CONTROL2;XCBR1 ST;Ind13;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 4 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL14 Transmitted to IEC CONTROL2;XCBR1 ST;Ind9;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 5 DP_HLA_ ISOOpen_Close DPS 220kV B208_TBC 89A POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 169;170;171;172;176;184;186;192;20;40;86; None 48 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 6 DP_HLA_ ISOOpen_Close DPS 220kV B208_TBC 89A POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 169;170;171;172;176;184;186;192;20;40;86; None 48 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 7 DP_HLa_ESOpen_Close DPS 220kV B208_TBC 89AE POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 166;167;168;170;171;172;173;174;175; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 8 DP_HLa_ESOpen_Close DPS 220kV B208_TBC 89AE POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 166;167;168;170;171;172;173;174;175; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 9 DP_HLA_ ISOOpen_Close DPS 220kV B208_TBC 89B POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC 166;167;168;169;176;184;186;197;20;40;86; None 49 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 10 DP_HLA_ ISOOpen_Close DPS 220kV B208_TBC 89B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC 166;167;168;169;176;184;186;197;20;40;86; None 49 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 11 DP_HLA_ ISOOpen_Close DPS 220kV B208_TBC 89T POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI3 ST;Pos;stVal;DPC 100;101;102;126;127;128;14;15;152;153;154;16;169;176;34;35;36;54;55;56;80;81;82; None 50 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 12 DP_HLA_ ISOOpen_Close DPS 220kV B208_TBC 89T POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI3 ST;Pos;stVal;DPC 100;101;102;126;127;128;14;15;152;153;154;16;169;176;34;35;36;54;55;56;80;81;82; None 50 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 13 DP_HLa_ESOpen_Close DPS 220kV B208_TBC 89TE1 POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 166;167;168;170;171;172;173;174;175; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 14 DP_HLa_ESOpen_Close DPS 220kV B208_TBC 89TE1 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 166;167;168;170;171;172;173;174;175; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 15 DP_HLa_ESOpen_Close DPS 220kV B208_TBC 89TE2 POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI3 ST;Pos;stVal;DPC 100;101;102;126;127;128;14;15;152;153;154;16;173;174;175;34;35;36;54;55;56;80;81;82; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 16 DP_HLa_ESOpen_Close DPS 220kV B208_TBC 89TE2 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI3 ST;Pos;stVal;DPC 100;101;102;126;127;128;14;15;152;153;154;16;173;174;175;34;35;36;54;55;56;80;81;82; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 2
Digital Inputs Board Slot N
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A N 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 3 SPE_HLA_Normal_Fail SPS 220kV B208_TBC PROTECTION DC SUPPLY-1 Fail Normal NM_FL_DC SUP1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 4 SPE_HLA_Normal_Fail SPS 220kV B208_TBC PROTECTION DC SUPPLY-2 Fail Normal NM_FL_DC SUP2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind9;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 5 SPE_HLA_Nrml_Optd SPS 220kV B208_TBC PROTECTION LOCKOUT TRIP RELAY Operated Normal NM_OP_LO_TR Transmitted to IEC CONTROL1;GGIO1 ST;Ind11;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 6 SPE_HLA_Healthy_Flty SPS 220kV B208_TBC PROTECTION PUA RELAY Faulty Healthy UL_HL_PU_RLY Transmitted to IEC CONTROL1;GGIO1 ST;Ind10;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 7 SPE_HLA_Healthy_Flty SPS 220kV B208_TBC PROTECTION TRIP COIL-1 Faulty Healthy HL_FT_TC1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind7;stVal;SPS 165; None 1 DIGITAL INPUT BOARD DIU2xx
A N 8 SPE_HLA_Healthy_Flty SPS 220kV B208_TBC PROTECTION TRIP COIL-2 Faulty Healthy HL_FT_TC2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind6;stVal;SPS 165; None 1 DIGITAL INPUT BOARD DIU2xx
A N 9 SPE_HLA_Nrml_Optd SPS 220kV B208_TBC PROTECTION LBB Operated Normal NM_OP_LBB Transmitted to IEC CONTROL1;GGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 3
Digital Inputs Board Slot M
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A M 1 SPE_HLA_Reset_Optd SPS 220kV B208_TBC AR FUNCTION-LINE R-PH INITIATION Operated Reset RS_OP_PHR INI Transmitted to IEC CONTROL1;RREC1 ST;Ind2;stVal;SPS 179; None ARFct TripPhA_SPS 1 DIGITAL INPUT BOARD DIU2xx
A M 2 SPE_HLA_Reset_Optd SPS 220kV B208_TBC AR FUNCTION-LINE Y-PH INITIATION Operated Reset RS_OP_PHY INI Transmitted to IEC CONTROL1;RREC1 ST;Ind3;stVal;SPS 179; None ARFct TripPhB_SPS 1 DIGITAL INPUT BOARD DIU2xx
A M 3 SPE_HLA_Reset_Optd SPS 220kV B208_TBC AR FUNCTION-LINE B-PH INITIATION Operated Reset RS_OP_PHB INI Transmitted to IEC CONTROL1;RREC1 ST;Ind4;stVal;SPS 179; None ARFct TripPhC_SPS 1 DIGITAL INPUT BOARD DIU2xx
A M 4 SPE_HLA_Reset_Optd SPS 220kV B208_TBC AR FUNCTION-LINE BLOCK CONTACTS Operated Reset RS_OP_AR BLOCK Transmitted to IEC CONTROL1;RREC1 ST;Ind1;stVal;SPS None ARFct AR_Blocking_SPS 1 DIGITAL INPUT BOARD DIU2xx
A M 5 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC PROTECTION BUSBAR PANEL DC SUPPLY Alarm Normal NM_FL_BB_DC Transmitted to IEC CONTROL1;GGIO1 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 6 SPE_HLA_Nrml_Optd SPS 220kV B208_TBC PROTECTION BUSBAR PROTECTION Operated Normal NM_OP_BB_PRTN Transmitted to IEC CONTROL1;GGIO1 ST;Ind3;stVal;SPS 165; None 1 DIGITAL INPUT BOARD DIU2xx
A M 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 9 DP_HLA_Trip_Closed DPS 220kV B208_TBC PROTECTION EMERGENCY/MANUAL CB POSITION Closed TR_CL_CB_EMER Transmitted to IEC CONTROL1;GGIO1 ST;DPCSO1;stVal;DPC None 1 DIGITAL INPUT BOARD DIU2xx
A M 10 DP_HLA_Trip_Closed DPS 220kV B208_TBC PROTECTION EMERGENCY/MANUAL CB POSITION Trip TR_CL_CB_EMER Transmitted to IEC CONTROL1;GGIO1 ST;DPCSO1;stVal;DPC None 1 DIGITAL INPUT BOARD DIU2xx
A M 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 15 SPE_HLA_Normal_Alarm SPS 220kV B208_TBC PROTECTION FIRE DETECTED Alarm Normal NM_AL_FIRE_DET Transmitted to IEC CONTROL1;GGIO1 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 16 SPE_HLA_Off_On SPS 220kV B208_TBC PROTECTION AC COMPRESSOR-1&2 On Off OF_ON_AC_CM1_2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 4
Digital Inputs Board Slot L
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A L 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 0
Digital Outputs Board Slot D
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A D 1 SC_DE_Off_On SPC 220kV B208_TBC AR DATA A/R OFF On Off XX_XX_A/R OFF Transmitted to IEC CONTROL1;GGIO4 CO;SPCSO2;ctlVal;DPC 5 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 2 SC_DE_Reset_Set SPC 220kV B208_TBC AR DATA MAIN CB A/R OPTD Set XX_XX_MAIN CB AR Transmitted to IEC CONTROL1;GGIO4 CO;SPCSO5;ctlVal;DPC 197 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 3 SC_DE_Reset_Reset_2 SPC 220kV B208_TBC AR DATA A/R LOCKOUT TRIP Reset XX_XX_A/R L/O Transmitted to IEC CONTROL1;GGIO4 CO;SPCSO3;ctlVal;DPC 196 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 4 SC_DE_Reset_Reset SPC 220kV B208_TBC AR DATA TO A/R CLSG. CKT Reset XX_XX_A/R CLSG C Transmitted to IEC CONTROL1;GGIO4 CO;SPCSO1;ctlVal;DPC 198 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 5 SC_DE_Reset_Set SPC 220kV B208_TBC AR DATA TO TIE A/R PROIRITY CKT HOLD Set XX_XX_TI AR CKTH Transmitted to IEC CONTROL1;GGIO4 CO;SPCSO4;ctlVal;DPC 199 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A D 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 1
Digital Outputs Board Slot E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A E 1 DC_SBO_Open_Close DPC 220kV B208_TBC 52 CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 47 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 2 DC_SBO_Open_Close DPC 220kV B208_TBC 52 CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 47 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 3 SC_DE_Reset_Set_1 SPC 220kV B208_TBC PROTECTION CB TRIP Set XX_XX_CB_TR1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO1;ctlVal;DPC 186 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 4 SC_DE_Reset_Set_1 SPC 220kV B208_TBC PROTECTION CB TRIP Set XX_XX_CB_TR2 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO2;ctlVal;DPC 185 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 5 SC_DE_Reset_Set_1 SPC 220kV B208_TBC PROTECTION CB TRIP Set XX_XX_CB_TR3 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO3;ctlVal;DPC 189 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 6 SC_DE_Reset_Set_1 SPC 220kV B208_TBC PROTECTION CB TRIP Set XX_XX_CB_TR4 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO4;ctlVal;DPC 187 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 7 SC_DE_Reset_Set_1 SPC 220kV B208_TBC PROTECTION CB TRIP Set XX_XX_CB_TR5 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO5;ctlVal;DPC 188 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 8 SC_DE_Reset_Set_Int_2 SPC 220kV B208_TBC VT SELECTION BUS-1 Set DS_SL_BUS1 Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO2;ctlVal;DPC 186<; 200 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 9 SC_DE_Reset_Set_Int_2 SPC 220kV B208_TBC VT SELECTION BUS-2 Set DS_SL_BUS2 Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO1;ctlVal;DPC 201 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A E 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 2
Digital Outputs Board Slot F
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A F 1 DC_SBO_Open_Close DPC 220kV B208_TBC 89A CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 48 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 2 DC_SBO_Open_Close DPC 220kV B208_TBC 89A CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 48 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 3 SC_DE_NotPerm_Perm SPC 220kV B208_TBC IL PERMISSIVE 89A I/L PERMISSIVE XX_XX_89A Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO1;ctlVal;DPC 190 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 4 SC_DE_NotPerm_Perm SPC 220kV B208_TBC IL PERMISSIVE 89AE I/L PERMISSIVE XX_XX_89AE Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO3;ctlVal;DPC 191 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 5 DC_SBO_Open_Close DPC 220kV B208_TBC 89B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 49 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 6 DC_SBO_Open_Close DPC 220kV B208_TBC 89B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 49 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 7 SC_DE_NotPerm_Perm SPC 220kV B208_TBC IL PERMISSIVE 89B I/L PERMISSIVE XX_XX_89B Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO2;ctlVal;DPC 192 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A F 10 SC_DE_Reset_Set_Int_2 SPC 220kV B208_TBC PROTECTION AUTO-RECLOSE LOCKOUT RELAY Set XX_RS_AR_LO_REL Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO6;ctlVal;DPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 3
Digital Outputs Board Slot G
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A G 1 DC_SBO_Open_Close DPC 220kV B208_TBC 89T CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 50 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 2 DC_SBO_Open_Close DPC 220kV B208_TBC 89T CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 50 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 3 SC_DE_NotPerm_Perm SPC 220kV B208_TBC IL PERMISSIVE 89T I/L PERMISSIVE XX_XX_89T Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO6;ctlVal;DPC 193 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 4 SC_DE_NotPerm_Perm SPC 220kV B208_TBC IL PERMISSIVE 89TE1 I/L PERMISSIVE XX_XX_89TE1 Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO4;ctlVal;DPC 194 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 5 SC_DE_NotPerm_Perm SPC 220kV B208_TBC IL PERMISSIVE 89TE2 I/L PERMISSIVE XX_XX_89TE2 Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO5;ctlVal;DPC 195 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A G 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
CT/VT ANALOG INPUT BOARD TMU2x0
CT/VT Board Number 0
CT/VT Board Slot Q
CT/VT Board Model TMU220
Nominal Current 1 (1A/5A)
Nominal Voltage 110.00 [1V … 500V]
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A DF MV_HLa_Frequency_1 Hz 220kV B208_TBC SYNCH DATA FREQUENCY DIFFERENCE 0.0 2.0 FREQUENCY DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifHzClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DV MV_hla_ AuxVoltage_1 V 220kV B208_TBC SYNCH DATA VOLTAGE DIFFERENCE 0.0 152.42494 VOLTAGE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifVClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Dj MV_hla_PhaseDiff ˚ 220kV B208_TBC SYNCH DATA PHASE DIFFERENCE 0.0 360.0 PHASE ANGLE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifAngClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ia MV_hla_ AuxVoltage_3 V 220kV B208_TBC METERING I-R PHASE CURRENT 0.0 1920.0 IR PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ib MV_HLa_AuxCurrent A 220kV B208_TBC METERING I-Y PHASE CURRENT 0.0 1920.0 IY PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ic MV_HLa_AuxCurrent A 220kV B208_TBC METERING I-B PHASE CURRENT 0.0 1920.0 IB PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsC;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vb MV_hla_ AuxVoltage_1 V 220kV B208_TBC SYNCH DATA INCOMING SUPPLY 0.0 152.42494 INCOMING SUPPLY Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;PhV;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uab MV_hla_ AuxVoltage V 220kV B208_TBC METERING R-Y VOLTAGE 0.0 264.0 R-Y VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsAB;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ubc MV_HLa_Voltage kV 220kV B208_TBC METERING Y-B VOLTAGE 0.0 264.0 Y-B VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsBC;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uca MV_HLa_Voltage kV 220kV B208_TBC METERING B-R VOLTAGE 0.0 264.0 B-R VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsCA;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar MV_hla_ AuxVoltage_1 V 220kV B208_TBC SYNCH DATA RUNNING SUPPLY-1 0.0 152.42494 RUNNING SUPPLY-1 Transmitted to IEC MEASUREMENT1;barMMXU1 MX;PhV;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Freq (Line) MV_HLa_Frequency Hz 220kV B208_TBC METERING FREQUENCY 45.0 55.0 FREQUENCY Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;Hz;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A P total (MW) MV_HLa_ActPower_1 MW 220kV B208_TBC METERING ACTIVE POWER -731.5968 731.5968 ACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotW;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Q total (Mvar) MV_HLa_ActPower_1 MW 220kV B208_TBC METERING REACTIVE POWER -731.5968 731.5968 REACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotVAr;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar RMS 2 value of the busbar voltage phase MV_hla_ AuxVoltage_1 V 220kV B208_TBC SYNCH DATA RUNNING SUPPLY-2 0.0 152.42494 RUNNING SUPPLY-2 Transmitted to IEC MEASUREMENT1;GGIO1 MX;AnIn1;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A cos ft : Power factor MV_HLa_PowerFactor 220kV B208_TBC METERING POWER FACTOR -1.2 1.2 POWER FACTOR Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotPF;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPE_HLa_Reset_Set SPS 220kV B208_TBC 52 | OE_CL_CONTROL OPEN ORDER Set Reset RS_ST_OPN ORD Transmitted to IEC CONTROL1;CSWI4 ST;OpnOrd;general;general;ACT 108;134;160;62; None 185;186;187;188;189 CB OpenOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPE_HLa_Notper_Perm SPS 220kV B208_TBC 89A IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI1 ST;IndSys1;stVal;SPS 166<; None 190 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPE_HLa_Notper_Perm SPS 220kV B208_TBC 89A | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPE_HLa_Notper_Perm SPS 220kV B208_TBC 89AE IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI2 ST;IndSys1;stVal;SPS 169<; None 191 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPE_HLa_Notper_Perm SPS 220kV B208_TBC 89B IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI2 ST;IndSys1;stVal;SPS 170<; None 192 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPE_HLa_Notper_Perm SPS 220kV B208_TBC 89B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO2 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPE_HLa_Notper_Perm SPS 220kV B208_TBC 89T IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI3 ST;IndSys1;stVal;SPS 173<; None 193 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPE_HLa_Notper_Perm SPS 220kV B208_TBC 89T | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO3 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPE_HLa_Notper_Perm SPS 220kV B208_TBC 89TE1 IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI1 ST;IndSys1;stVal;SPS 176<; None 194 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPE_HLa_Notper_Perm SPS 220kV B208_TBC 89TE2 IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI3 ST;IndSys1;stVal;SPS 177<; None 195 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPE_HLA_Reset_Optd SPS 220kV B208_TBC AR DATA LOCKOUT FROM AR LOGIC Operated Reset RS_OP_AR LO FBD Transmitted to IEC CONTROL1;GAPC4 ST;IndSys5;stVal;SPS 165;179<; None 196 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPE_HLa_Reset_Set SPS 220kV B208_TBC AR DATA A/R OPTD FROM FBD Set Reset RS_ST_AR OPTD FB Transmitted to IEC CONTROL1;GAPC4 ST;IndSys6;stVal;SPS 178<; None 197;198 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPE_HLa_Reset_Set SPS 220kV B208_TBC AR DATA PRIORITY CIRCUIT HOLD Set Reset RS_ST_PRI HLD ON Transmitted to IEC CONTROL1;GAPC4 ST;IndSys7;stVal;SPS 180<; None 199 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPS_hla_Set_Reset SPS 220kV B208_TBC ORDER RUNNING ON THE BAY Set Reset RS_ST_ORD RUNING Transmitted to IEC CONTROL1;GBAY1 ST;OrdRun;stVal;SPS None OrderInProgress 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPE_HLa_Reset_Set SPS 220kV B208_TBC SYNCH DATA CLOSE PERMISSIVE Set Reset RS_ST_CB CLOSE Transmitted to IEC CONTROL1;GAPC1 ST;IndSys5;stVal;SPS 183<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPE_HLa_Reset_Set SPS 220kV B208_TBC SYNCH DATA DEAD INCOMING DEAD RUNNING Set Reset RS_ST_DINC_DRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys4;stVal;SPS 183<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 17 SPE_HLa_Reset_Set SPS 220kV B208_TBC SYNCH DATA DEAD INCOMING LIVE RUNNING Set Reset RS_ST_DINC_LRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys3;stVal;SPS 183<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 18 SPE_HLa_Reset_Set SPS 220kV B208_TBC SYNCH DATA LIVE INCOMING DEAD RUNNING Set Reset RS_ST_LINC_DRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys2;stVal;SPS 183<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 19 SPE_HLa_Reset_Set SPS 220kV B208_TBC SYNCH DATA LIVE INCOMING LIVE RUNNING Set Reset RS_ST_LINC_LRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys1;stVal;SPS 183<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 20 SPE_HLa_Dselect_Select SPS 220kV B208_TBC VT SELECTION BUS-1 Selected Deselected DS_SL_BUS1 Transmitted to IEC CONTROL1;GAPC3 ST;IndSys1;stVal;SPS 186<; None 200 1 C264 SELF GENERATED DIGITAL INFORMATION
A 21 SPE_HLa_Dselect_Select SPS 220kV B208_TBC VT SELECTION BUS-2 Selected Deselected DS_SL_BUS2 Transmitted to IEC CONTROL1;GAPC3 ST;IndSys2;stVal;SPS 186<; None 201 1 C264 SELF GENERATED DIGITAL INFORMATION
A 22 SPE_HLA_Reset_Optd SPS 220kV B208_TBC AR FUNCTION-LINE TRIP 3-PHASES Operated Reset RS_OP_TRP 3PH Transmitted to IEC CONTROL1;RREC1 ST;Trip3P;stVal;SPS None ARFct Trip_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 23 SPE_HLa_Reset_Set SPS 220kV B208_TBC SYNCH FUNCTION CLOSE ORDER Set Reset RS_ST_CLS ODR Transmitted to IEC CONTROL1;RSYN1 ST;ClsOpSt;stVal;SPS None IntManualCSFct CS_CloseOrderState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 24 SPE_HLA_on_off SPS 220kV B208_TBC SYNCH FUNCTION ON/OFF SECONDARY SPS Off On RS_ST_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 ST;EnaSec;origin;SPC None 189 IntManualCSFct CS_OnOff_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 25 SPE_HLa_Reset_Set SPS 220kV B208_TBC SYNCH FUNCTION POSSIBLE CLOSING Set Reset RS_ST_POS CLS Transmitted to IEC CONTROL1;RSYN1 ST;Rel;stVal;SPS 183; None IntManualCSFct CS_AuthoState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 26 SPE_HLa_Reset_Set SPS 220kV B208_TBC SYNCH FUNCTION PRESENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF U PRES Transmitted to IEC CONTROL1;RSYN1 ST;VRefInd;stVal;SPS 183; None IntManualCSFct CS_VoltageRefPresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 27 SPE_HLa_Reset_Set SPS 220kV B208_TBC SYNCH FUNCTION ABSENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF. U ABS Transmitted to IEC CONTROL1;RSYN1 ST;VRefAbs;stVal;SPS 183; None IntManualCSFct CS_VoltageRefAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 28 SPE_HLa_Reset_Set SPS 220kV B208_TBC SYNCH FUNCTION RS_ST_V CHOICE Set Reset RS_ST_V CHOICE Transmitted to IEC CONTROL1;RSYN1 ST;BusVC;stVal;SPS 184<; None IntManualCSFct CS_BusBarVChoice_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 29 SPE_HLa_Reset_Set SPS 220kV B208_TBC SYNCH FUNCTION VOLT ABSENCE Set Reset RS_ST_VOLT ABS Transmitted to IEC CONTROL1;RSYN1 ST;VAbs;stVal;SPS 183; None IntManualCSFct CS_VoltageAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 30 SPE_HLa_Reset_Set SPS 220kV B208_TBC SYNCH FUNCTION VOLT PRESENCE Set Reset RS_ST_VOLT PRES Transmitted to IEC CONTROL1;RSYN1 ST;VP;stVal;SPS 183; None IntManualCSFct CS_VoltagePresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 31 SPE_HLa_Notper_Perm SPS 220kV B208_TBC 52 | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLOSE ILK Transmitted to IEC CONTROL2;CILO4 ST;EnaCls;stVal;SPS None CB CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 32 SPE_HLa_Notper_Perm SPS 220kV B208_TBC 52 | OE_CL_CONTROL CLOSE ORDER Permissive Not Permissive RS_ST_CLS ORD Transmitted to IEC CONTROL1;CSWI4 ST;ClsOrd;general;general;ACT 178; None CB CloseOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 33 SPE_HLa_Notper_Perm SPS 220kV B208_TBC 89A | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 34 SPE_HLa_Notper_Perm SPS 220kV B208_TBC 89B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO2 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 35 SPE_HLa_Notper_Perm SPS 220kV B208_TBC 89T | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO3 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 36 SPE_HLa_Reset_Set SPS 220kV B208_TBC AR DATA LOCK Set Reset RS_ST_S10_LOCK Transmitted to IEC CONTROL1;GAPC4 ST;IndSys1;stVal;SPS 179; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 37 SPE_HLa_Reset_Set SPS 220kV B208_TBC AR DATA WAIT FOR CB CLOSE Set Reset RS_ST_S7_WT CB C Transmitted to IEC CONTROL1;GAPC4 ST;IndSys4;stVal;SPS 178; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 38 SPE_HLa_Reset_Set SPS 220kV B208_TBC AR DATA RECLAIM_TIMER Set Reset RS_ST_S8_RC TIM Transmitted to IEC CONTROL1;GAPC4 ST;IndSys3;stVal;SPS None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 39 SPE_HLa_Reset_Set SPS 220kV B208_TBC AR DATA LOCK_SHOTS Set Reset RS_ST_S9_LO SHTS Transmitted to IEC CONTROL1;GAPC4 ST;IndSys2;stVal;SPS 179; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 40 DP_HLA_CBOpen_Close DPS 220kV B208_TBC 52 POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;stVal;DPC 100;101;102;126;127;128;14;15;152;153;154;16;166;167;168;170;171;172;173;174;175;34;35;36;54;55;56;80;81;82; None 47 182 Yes CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 41 DP_HLA_CBOpen_Close DPS 220kV B208_TBC 52 POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;stVal;DPC 100;101;102;126;127;128;14;15;152;153;154;16;166;167;168;170;171;172;173;174;175;34;35;36;54;55;56;80;81;82; None 47 182 Yes CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 42 DP_HLA_Trip_Closed DPS 220kV B208_TBC 52 EMERGENCY/MANUAL Trip TP_CL_EMRG/MAN Transmitted to IEC CONTROL1;CSWI4 ST;DPCSO1;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 43 DP_HLA_Trip_Closed DPS 220kV B208_TBC 52 EMERGENCY/MANUAL Closed TP_CL_EMRG/MAN Transmitted to IEC CONTROL1;CSWI4 ST;DPCSO1;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 44 DP_HLA_ ISOOpen_Close DPS 220kV B208_TBC 89A COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 45 DP_HLA_ ISOOpen_Close DPS 220kV B208_TBC 89A COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 46 DP_HLa_ESOpen_Close DPS 220kV B208_TBC 89AE COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 47 DP_HLa_ESOpen_Close DPS 220kV B208_TBC 89AE COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 48 DP_HLA_ ISOOpen_Close DPS 220kV B208_TBC 89B COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 49 DP_HLA_ ISOOpen_Close DPS 220kV B208_TBC 89B COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 50 DP_HLA_ ISOOpen_Close DPS 220kV B208_TBC 89T COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 51 DP_HLA_ ISOOpen_Close DPS 220kV B208_TBC 89T COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 52 DP_HLa_ESOpen_Close DPS 220kV B208_TBC 89TE1 COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 53 DP_HLa_ESOpen_Close DPS 220kV B208_TBC 89TE1 COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 54 DP_HLA_ ISOOpen_Close DPS 220kV B208_TBC 89TE2 COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 55 DP_HLA_ ISOOpen_Close DPS 220kV B208_TBC 89TE2 COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 56 DP_HLA_On_Off DPS 220kV B208_TBC AR FUNCTION-LINE ON/OFF STATUS On OF_ON_AR STATUS Transmitted to IEC CONTROL1;RREC1 ST;Ena;origin;DPC 180; None 51 5 ARFct AR_OnOff_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 57 DP_HLA_On_Off DPS 220kV B208_TBC AR FUNCTION-LINE ON/OFF STATUS Off OF_ON_AR STATUS Transmitted to IEC CONTROL1;RREC1 ST;Ena;origin;DPC 180; None 51 5 ARFct AR_OnOff_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 58 DP_HLa_LocRem_Bay DPS 220kV B208_TBC BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 52 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 59 DP_HLa_LocRem_Bay DPS 220kV B208_TBC BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 52 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 60 MP_HLA_AR_Fault MPS 220kV B208_TBC AR FUNCTION-LINE AUTORECLOSER FAULT STATUS AUTORECLOSER FLT Transmitted to IEC CONTROL1;RREC1 ST;ARFlt;stVal;INS None ARFct AR_FaultReason_MPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 61 MP_HLA_AR_Status MPS 220kV B208_TBC AR FUNCTION-LINE AUTORECLOSER STATUS AUTORECLOSER ST Transmitted to IEC CONTROL1;RREC1 ST;ARSt;stVal;INS 180; None ARFct AR_Status_MPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 62 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SC_DE_Reset_Set_Int SPC 220kV B208_TBC AR FUNCTION-LINE Force trip 3 Phase Set XX_XX_TRIP 3PH Transmitted to IEC CONTROL1;RREC1 CO;Trip3P;ctlVal;DPC ARFct Ctrl3PhaseTrip_SPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SC_DE_Off_On SPC 220kV B208_TBC SYNCH FUNCTION ON/OFF SECONDARY CONTROL SPC On Off OF_ON_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 CO;EnaSec;ctlVal;DPC 189 IntManualCSFct CS_CtrlOnOff_SPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 DC_DE_AROff_AROn DPC 220kV B208_TBC AR FUNCTION-LINE OFF Off OF_ON_A/R OFF Transmitted to IEC CONTROL1;RREC1 CO;Ena;ctlVal;DPC 51 ARFct AR_CtrlOnOff_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 DC_DE_AROff_AROn DPC 220kV B208_TBC AR FUNCTION-LINE OFF On OF_ON_A/R OFF Transmitted to IEC CONTROL1;RREC1 CO;Ena;ctlVal;DPC 51 ARFct AR_CtrlOnOff_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 DC_DE_LocRem_BayCtrl DPC 220kV B208_TBC BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 52 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 DC_DE_LocRem_BayCtrl DPC 220kV B208_TBC BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 52 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 MV_HLa_Unused 220kV B208_TBC CB_COUNTER Count_Close 0.0 10000.0 Count_Close Transmitted to IEC CONTROL2;GAPC1 MX;AnIn2;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 MV_HLa_Unused 220kV B208_TBC CB_COUNTER Count_Open 0.0 10000.0 Count_Open Transmitted to IEC CONTROL2;GAPC1 MX;AnIn1;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 MV_hla_Temp ˚ Cel 220kV B208_TBC PROTECTION AC KIOSK TEMP 0.0 100.0 AC KIOSK TEMP Transmitted to IEC CONTROL1;GAPC2 MX;AnIn1;mag;MV 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
MiCOM C264 DESCRIPTION
Computer Name B209_BC GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) C264 Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 0
Digital Inputs Board Slot P
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A P 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 7 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL1 Transmitted to IEC CONTROL2;XCBR1 ST;Ind12;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 8 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL2 Transmitted to IEC CONTROL2;XCBR1 ST;Ind8;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 9 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL3 Transmitted to IEC CONTROL2;XCBR1 ST;Ind9;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 10 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL4 Transmitted to IEC CONTROL2;XCBR1 ST;Ind13;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 11 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL5 Transmitted to IEC CONTROL2;XCBR1 ST;Ind6;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 12 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL6 Transmitted to IEC CONTROL2;XCBR1 ST;Ind7;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 13 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL7 Transmitted to IEC CONTROL2;XCBR1 ST;Ind1;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 14 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL8 Transmitted to IEC CONTROL2;XCBR1 ST;Ind2;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 15 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL9 Transmitted to IEC CONTROL2;XCBR1 ST;Ind3;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 16 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL10 Transmitted to IEC CONTROL2;XCBR1 ST;Ind4;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 1
Digital Inputs Board Slot O
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A O 1 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL11 Transmitted to IEC CONTROL2;XCBR1 ST;Ind5;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 2 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 CB TOUBLE Alarm Normal RS_OP_CB_TRBL12 Transmitted to IEC CONTROL2;XCBR1 ST;Ind11;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 3 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL13 Transmitted to IEC CONTROL2;XCBR1 ST;Ind14;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 4 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 CB TROUBLE Alarm Normal RS_OP_CB_TRBL14 Transmitted to IEC CONTROL2;XCBR1 ST;Ind10;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 5 DP_HLA_ ISOOpen_Close DPS 220kV B209_BC 89A POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 114;115;116;118;119;120;140;141;142;144;145;146;166;167;168;170;171;172;191;192;196;2;22;23;24;26;27;28;3;4;42;43;44;46;47;48;6;68;69;7;70;72;73;74;8;88;89;90;92;93;94; None 54 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 6 DP_HLA_ ISOOpen_Close DPS 220kV B209_BC 89A POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 114;115;116;118;119;120;140;141;142;144;145;146;166;167;168;170;171;172;191;192;196;2;22;23;24;26;27;28;3;4;42;43;44;46;47;48;6;68;69;7;70;72;73;74;8;88;89;90;92;93;94; None 54 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 7 DP_HLa_ESOpen_Close DPS 220kV B209_BC 89AE1 POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 188;189;190; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 8 DP_HLa_ESOpen_Close DPS 220kV B209_BC 89AE1 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 188;189;190; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 9 DP_HLa_ESOpen_Close DPS 220kV B209_BC 89AE2 POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI4 ST;Pos;stVal;DPC 114;115;116;140;141;142;166;167;168;188;189;190;193;194;195;2;22;23;24;3;4;42;43;44;68;69;70;88;89;90; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 10 DP_HLa_ESOpen_Close DPS 220kV B209_BC 89AE2 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI4 ST;Pos;stVal;DPC 114;115;116;140;141;142;166;167;168;188;189;190;193;194;195;2;22;23;24;3;4;42;43;44;68;69;70;88;89;90; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 11 DP_HLA_ ISOOpen_Close DPS 220kV B209_BC 89B POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC 114;115;116;118;119;120;140;141;142;144;145;146;166;167;168;170;171;172;191;196;197;2;22;23;24;26;27;28;3;4;42;43;44;46;47;48;6;68;69;7;70;72;73;74;8;88;89;90;92;93;94; None 55 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 12 DP_HLA_ ISOOpen_Close DPS 220kV B209_BC 89B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC 114;115;116;118;119;120;140;141;142;144;145;146;166;167;168;170;171;172;191;196;197;2;22;23;24;26;27;28;3;4;42;43;44;46;47;48;6;68;69;7;70;72;73;74;8;88;89;90;92;93;94; None 55 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 13 DP_HLa_ESOpen_Close DPS 220kV B209_BC 89BE1 POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI3 ST;Pos;stVal;DPC 188;193;194;195; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 14 DP_HLa_ESOpen_Close DPS 220kV B209_BC 89BE1 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI3 ST;Pos;stVal;DPC 188;193;194;195; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 15 DP_HLa_ESOpen_Close DPS 220kV B209_BC 89BE2 POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 118;119;120;144;145;146;170;171;172;189;190;193;194;195;26;27;28;46;47;48;6;7;72;73;74;8;92;93;94; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 16 DP_HLa_ESOpen_Close DPS 220kV B209_BC 89BE2 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 118;119;120;144;145;146;170;171;172;189;190;193;194;195;26;27;28;46;47;48;6;7;72;73;74;8;92;93;94; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 2
Digital Inputs Board Slot N
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A N 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 3 SPE_HLA_Normal_Fail SPS 220kV B209_BC PROTECTION DC SUPPLY-1 Fail Normal NM_FL_DC SUP1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind16;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 4 SPE_HLA_Normal_Fail SPS 220kV B209_BC PROTECTION DC SUPPLY-2 Fail Normal NM_FL_DC SUP-2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 5 SPE_HLA_Healthy_Flty SPS 220kV B209_BC PROTECTION TRIP COIL-1 Faulty Healthy HL_FT_TC1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind13;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 6 SPE_HLA_Healthy_Flty SPS 220kV B209_BC PROTECTION TRIP COIL-2 Faulty Healthy HL_FT_TC2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind12;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 7 SPE_HLA_Healthy_Flty SPS 220kV B209_BC PROTECTION PUA RELAY Faulty Healthy HL_FT_PU_RLY Transmitted to IEC CONTROL1;GGIO1 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 9 SPE_HLA_Nrml_Optd SPS 220kV B209_BC PROTECTION LBB Operated Normal NM_OP_LBB Transmitted to IEC CONTROL1;GGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 10 SPE_HLA_Nrml_Optd SPS 220kV B209_BC PROTECTION BUSBAR PROTECTION Operated Normal NM_OP_BB_PRTN Transmitted to IEC CONTROL1;GGIO1 ST;Ind9;stVal;SPS 187; None 1 DIGITAL INPUT BOARD DIU2xx
A N 11 DP_HLA_Trip_Closed DPS 220kV B209_BC PROTECTION EMERGENCY/MANUAL CB POSITION Trip TR_CL_CB_EMER Transmitted to IEC CONTROL1;GGIO1 ST;DPCSO1;stVal;DPC None 1 DIGITAL INPUT BOARD DIU2xx
A N 12 DP_HLA_Trip_Closed DPS 220kV B209_BC PROTECTION EMERGENCY/MANUAL CB POSITION Closed TR_CL_CB_EMER Transmitted to IEC CONTROL1;GGIO1 ST;DPCSO1;stVal;DPC None 1 DIGITAL INPUT BOARD DIU2xx
A N 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 15 SPE_HLA_Normal_Alarm SPS 220kV B209_BC PROTECTION FIRE DETECTED Alarm Normal NM_AL_FIRE_DET Transmitted to IEC CONTROL1;GGIO1 ST;Ind10;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 16 SPE_HLA_Off_On SPS 220kV B209_BC PROTECTION AC COMPRESSOR-1&2 On Off OF_ON_AC_CM1_2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind11;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 3
Digital Inputs Board Slot M
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A M 1 SPE_HLA_Normal_Fail SPS 220kV B209_BC PROTECTION BUSBAR DC-1 Fail Normal NM_FL_BB_DC1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 2 SPE_HLA_Normal_Fail SPS 220kV B209_BC PROTECTION BUSBAR DC-2 Fail Normal NM_FL_BB_DC2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 3 SPE_HLA_Unhlthy_Hlthy SPS 220kV B209_BC PROTECTION 87CU RELAY Healthy Unhealthy UL_HL_87CU_REL Transmitted to IEC CONTROL1;GGIO1 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 4 SPE_HLA_Nrml_Optd SPS 220kV B209_BC PROTECTION ZONE-1 Operated Normal NM_OP_Z1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind14;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 5 SPE_HLA_Nrml_Optd SPS 220kV B209_BC PROTECTION ZONE-2 Operated Normal NM_OP_Z2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind15;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 6 SPE_HLa_In_Out SPS 220kV B209_BC PROTECTION DC-2 SUPPLY In Out OU_IN_DC2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 7 SPE_HLa_In_Out SPS 220kV B209_BC PROTECTION DC-1 SUPPLY In Out OU_IN_DC1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind7;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 4
Digital Inputs Board Slot L
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A L 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 0
Digital Outputs Board Slot E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A E 1 DC_SBO_Open_Close DPC 220kV B209_BC 52 CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 53 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 2 DC_SBO_Open_Close DPC 220kV B209_BC 52 CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 53 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 3 SC_DE_Reset_Set_1 SPC 220kV B209_BC PROTECTION CB TRIP Set XX_XX_CB_TR1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO1;ctlVal;DPC 203 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 4 SC_DE_Reset_Set_1 SPC 220kV B209_BC PROTECTION CB TRIP Set XX_XX_CB_TR2 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO2;ctlVal;DPC 202 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 5 SC_DE_Reset_Set_1 SPC 220kV B209_BC PROTECTION CB TRIP Set XX_XX_CB_TR3 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO3;ctlVal;DPC 204 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 6 SC_DE_Reset_Set_1 SPC 220kV B209_BC PROTECTION CB TRIP Set XX_XX_CB_TR4 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO4;ctlVal;DPC 205 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 7 SC_DE_Reset_Set_1 SPC 220kV B209_BC PROTECTION CB TRIP Set XX_XX_CB_TR5 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO5;ctlVal;DPC 206 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A E 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 1
Digital Outputs Board Slot F
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A F 1 DC_SBO_Open_Close DPC 220kV B209_BC 89A CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 54 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 2 DC_SBO_Open_Close DPC 220kV B209_BC 89A CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 54 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 3 SC_DE_NotPerm_Perm SPC 220kV B209_BC IL PERMISSIVE 89A I/L PERMISSIVE XX_XX_89A Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO1;ctlVal;DPC 144 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 4 SC_DE_NotPerm_Perm SPC 220kV B209_BC IL PERMISSIVE 89AE1 I/L PERMISSIVE XX_XX_89AE1 Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO3;ctlVal;DPC 145 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 5 DC_SBO_Open_Close DPC 220kV B209_BC 89B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 55 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 6 DC_SBO_Open_Close DPC 220kV B209_BC 89B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 55 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 7 SC_DE_NotPerm_Perm SPC 220kV B209_BC IL PERMISSIVE 89B I/L PERMISSIVE XX_XX_89B Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO2;ctlVal;DPC 147 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 8 SC_DE_NotPerm_Perm SPC 220kV B209_BC IL PERMISSIVE 89BE1 I/L PERMISSIVE XX_XX_89BE1 Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO4;ctlVal;DPC 148 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 9 SC_DE_NotPerm_Perm SPC 220kV B209_BC IL PERMISSIVE 89BE2 I/L PERMISSIVE XX_XX_89BE2 Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO6;ctlVal;DPC 149 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A F 10 SC_DE_NotPerm_Perm SPC 220kV B209_BC IL PERMISSIVE 89AE2 I/L PERMISSIVE XX_XX_89AE2 Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO5;ctlVal;DPC 146 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 2
Digital Outputs Board Slot G
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A G 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A G 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 3
Digital Outputs Board Slot H
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A H 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A H 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
ANALOG INPUT BOARD AIU21x
Analog Input Board Number 0
Analog Input Board Slot D
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 4/20 mA MV_hla_Temp ˚ Cel 220kV B209_BC PROTECTION AC KIOSK TEMP 0.0 100.0 AC KIOSK TEMP Transmitted to IEC CONTROL1;GGIO1 MX;AnIn1;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 2 SPARE 6 ANALOG INPUT BOARD AIU21x
A 3 SPARE 6 ANALOG INPUT BOARD AIU21x
A 4 SPARE 6 ANALOG INPUT BOARD AIU21x
A 5 SPARE 6 ANALOG INPUT BOARD AIU21x
A 6 SPARE 6 ANALOG INPUT BOARD AIU21x
A 7 SPARE 6 ANALOG INPUT BOARD AIU21x
A 8 SPARE 6 ANALOG INPUT BOARD AIU21x
CT/VT ANALOG INPUT BOARD TMU2x0
CT/VT Board Number 0
CT/VT Board Slot Q
CT/VT Board Model TMU220
Nominal Current 1 (1A/5A)
Nominal Voltage 110.00 [1V … 500V]
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A DF MV_HLa_Frequency_1 Hz 220kV B209_BC SYNCH DATA FREQUENCY DIFFERENCE 0.0 2.0 FREQUENCY DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifHzClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DV MV_hla_ AuxVoltage_1 V 220kV B209_BC SYNCH DATA VOLTAGE DIFFERENCE 0.0 152.42494 VOLTAGE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifVClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Dj MV_hla_PhaseDiff ˚ 220kV B209_BC SYNCH DATA PHASE DIFFERENCE 0.0 360.0 PHASE ANGLE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifAngClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ia MV_HLa_AuxCurrent A 220kV B209_BC METERING I-R PHASE CURRENT 0.0 1920.0 IR PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ib MV_HLa_AuxCurrent A 220kV B209_BC METERING I-Y PHASE CURRENT 0.0 1920.0 IY PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ic MV_HLa_AuxCurrent A 220kV B209_BC METERING I-B PHASE CURRENT 0.0 1920.0 IB PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsC;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vb MV_hla_ AuxVoltage_1 V 220kV B209_BC SYNCH DATA INCOMING SUPPLY 0.0 152.42494 INCOMING SUPPLY Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;PhV;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uab MV_hla_ AuxVoltage V 220kV B209_BC METERING R-Y VOLTAGE 0.0 264.0 R-Y VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsAB;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ubc MV_HLa_Voltage kV 220kV B209_BC METERING Y-B VOLTAGE 0.0 264.0 Y-B VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsBC;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uca MV_HLa_Voltage kV 220kV B209_BC METERING B-R VOLTAGE 0.0 264.0 B-R VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsCA;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar MV_hla_ AuxVoltage_1 V 220kV B209_BC SYNCH DATA RUNNING SUPPLY 0.0 152.42494 RUNNING SUPPLY Transmitted to IEC MEASUREMENT1;barMMXU1 MX;PhV;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Freq (Line) MV_HLa_Frequency Hz 220kV B209_BC METERING FREQUENCY 45.0 55.0 FREQUENCY Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;Hz;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A P total (MW) MV_HLa_ActPower_1 MW 220kV B209_BC METERING ACTIVE POWER -731.5968 731.5968 ACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotW;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Q total (Mvar) MV_HLa_ActPower_1 MW 220kV B209_BC METERING REACTIVE POWER -731.5968 731.5968 REACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotVAr;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A cos ft : Power factor MV_HLa_PowerFactor 220kV B209_BC METERING POWER FACTOR -1.2 1.2 POWER FACTOR Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotPF;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 SPRING CHARGE STATUS Alarm Normal NL_AL_SPING ST 2 Transmitted to IEC CONTROL1;CSWI3 ST;IndSys1;stVal;SPS None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPE_HLa_Notper_Perm SPS 220kV B209_BC 89A IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI1 ST;IndSys1;stVal;SPS 188<; None 144 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPE_HLa_Notper_Perm SPS 220kV B209_BC 89AE1 IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI1 ST;IndSys1;stVal;SPS 191<; None 145 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPE_HLa_Notper_Perm SPS 220kV B209_BC 89AE2 IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI5 ST;IndSys1;stVal;SPS 192<; None 146 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPE_HLa_Notper_Perm SPS 220kV B209_BC 89B IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI2 ST;IndSys1;stVal;SPS 193<; None 147 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPE_HLa_Notper_Perm SPS 220kV B209_BC 89BE1 IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI4 ST;IndSys1;stVal;SPS 196<; None 148 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPE_HLa_Notper_Perm SPS 220kV B209_BC 89BE2 IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI2 ST;IndSys1;stVal;SPS 197<; None 149 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPE_HLa_Reset_Set SPS 220kV B209_BC SYNCH DATA CLOSE PERMISSIVE Set Reset RS_ST_CB CLOSE Transmitted to IEC CONTROL1;GAPC1 ST;IndSys5;stVal;SPS 199<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPE_HLa_Reset_Set SPS 220kV B209_BC SYNCH DATA DEAD INCOMING DEAD RUNNING Set Reset RS_ST_DINC_DRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys4;stVal;SPS 199<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPE_HLa_Reset_Set SPS 220kV B209_BC SYNCH DATA DEAD INCOMING LIVE RUNNING Set Reset RS_ST_DINC_LRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys3;stVal;SPS 199<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPE_HLa_Reset_Set SPS 220kV B209_BC SYNCH DATA LIVE INCOMING DEAD RUNNING Set Reset RS_ST_LINC_DRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys2;stVal;SPS 199<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPE_HLa_Reset_Set SPS 220kV B209_BC SYNCH DATA LIVE INCOMING LIVE RUNNING Set Reset RS_ST_LINC_LRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys1;stVal;SPS 199<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPE_HLA_Normal_Alarm SPS 220kV B209_BC 52 LOSS OF SF6 GAS POLE A/B/C Alarm Normal NL_AL_LOSS SF6 Transmitted to IEC CONTROL1;CSWI3 ST;IndSys2;stVal;SPS None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPE_HLa_Reset_Set SPS 220kV B209_BC 52 | OE_CL_CONTROL OPEN ORDER Set Reset RS_ST_OPN ORD Transmitted to IEC CONTROL1;CSWI3 ST;OpnOrd;general;general;ACT None 202;203;204;205;206 CB OpenOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPE_HLa_Notper_Perm SPS 220kV B209_BC 89A | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL1;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPE_HLa_Notper_Perm SPS 220kV B209_BC 89B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL1;CILO2 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 17 SPS_hla_Set_Reset SPS 220kV B209_BC ORDER RUNNING ON THE BAY Set Reset RS_ST_ORD RUNING Transmitted to IEC CONTROL1;GBAY1 ST;OrdRun;stVal;SPS None OrderInProgress 1 C264 SELF GENERATED DIGITAL INFORMATION
A 18 SPE_HLa_Reset_Set SPS 220kV B209_BC SYNCH FUNCTION CLOSE ORDER Set Reset RS_ST_CLS ODR Transmitted to IEC CONTROL1;RSYN1 ST;ClsOpSt;stVal;SPS None IntManualCSFct CS_CloseOrderState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 19 SPE_HLA_on_off SPS 220kV B209_BC SYNCH FUNCTION ON/OFF SECONDARY SPS Off On RS_ST_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 ST;EnaSec;origin;SPC None 190 IntManualCSFct CS_OnOff_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 20 SPE_HLa_Reset_Set SPS 220kV B209_BC SYNCH FUNCTION POSSIBLE CLOSING Set Reset RS_ST_POS CLS Transmitted to IEC CONTROL1;RSYN1 ST;Rel;stVal;SPS 199; None IntManualCSFct CS_AuthoState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 21 SPE_HLa_Reset_Set SPS 220kV B209_BC SYNCH FUNCTION PRESENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF U PRES Transmitted to IEC CONTROL1;RSYN1 ST;VRefInd;stVal;SPS 199; None IntManualCSFct CS_VoltageRefPresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 22 SPE_HLa_Reset_Set SPS 220kV B209_BC SYNCH FUNCTION ABSENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF. U ABS Transmitted to IEC CONTROL1;RSYN1 ST;VRefAbs;stVal;SPS 199; None IntManualCSFct CS_VoltageRefAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 23 SPE_HLa_Reset_Set SPS 220kV B209_BC SYNCH FUNCTION VOLT ABSENCE Set Reset RS_ST_VOLT ABS Transmitted to IEC CONTROL1;RSYN1 ST;VAbs;stVal;SPS 199; None IntManualCSFct CS_VoltageAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 24 SPE_HLa_Reset_Set SPS 220kV B209_BC SYNCH FUNCTION VOLT PRESENCE Set Reset RS_ST_VOLT PRES Transmitted to IEC CONTROL1;RSYN1 ST;VP;stVal;SPS 199; None IntManualCSFct CS_VoltagePresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 25 SPE_HLa_Notper_Perm SPS 220kV B209_BC 52 | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLOSE ILK Transmitted to IEC CONTROL2;CILO1 ST;EnaCls;stVal;SPS None CB CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 26 SPE_HLa_Notper_Perm SPS 220kV B209_BC 52 | OE_CL_CONTROL CLOSE ORDER Permissive Not Permissive RS_ST_CLS ORD Transmitted to IEC CONTROL1;CSWI3 ST;ClsOrd;general;general;ACT None CB CloseOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 27 SPE_HLa_Notper_Perm SPS 220kV B209_BC 89A | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL1;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 28 SPE_HLa_Notper_Perm SPS 220kV B209_BC 89B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL1;CILO2 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 29 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Y_52 POS Open 7_Y_52 POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO2;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 30 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Y_52 POS Closed 7_Y_52 POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO2;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 31 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Z_52 POS Open 7_Z_52 POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO3;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 32 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Z_52 POS Closed 7_Z_52 POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO3;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 33 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Z_TB POS Open 7_Z_TB POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO6;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 34 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Z_TB POS Closed 7_Z_TB POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO6;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 35 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Z_TE R POS Open 7_Z_TE R POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO7;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 36 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Z_TE R POS Closed 7_Z_TE R POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO7;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 37 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Z_TE Y POS Open 7_Z_TE Y POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO8;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 38 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Z_TE Y POS Closed 7_Z_TE Y POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO8;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 39 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Z_TR POS Open 7_Z_TR POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO4;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 40 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Z_TR POS Closed 7_Z_TR POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO4;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 41 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Z_TSR POS Open 7_Z_TSR POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO9;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 42 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Z_TSR POS Closed 7_Z_TSR POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO9;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 43 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Z_TY POS Open 7_Z_TY POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO5;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 44 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 7_Z_TY POS Closed 7_Z_TY POS Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO5;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 45 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC 114;115;116;118;119;120;140;141;142;144;145;146;166;167;168;170;171;172;188;189;190;193;194;195;2;22;23;24;26;27;28;3;4;42;43;44;46;47;48;6;68;69;7;70;72;73;74;8;88;89;90;92;93;94; None 53 198 Yes CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 46 DP_HLA_CBOpen_Close DPS 220kV B209_BC 52 POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC 114;115;116;118;119;120;140;141;142;144;145;146;166;167;168;170;171;172;188;189;190;193;194;195;2;22;23;24;26;27;28;3;4;42;43;44;46;47;48;6;68;69;7;70;72;73;74;8;88;89;90;92;93;94; None 53 198 Yes CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 47 DP_HLA_Trip_Closed DPS 220kV B209_BC 52 EMERGENCY/MANUAL Trip TP_CL_EMRG/MAN Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO1;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 48 DP_HLA_Trip_Closed DPS 220kV B209_BC 52 EMERGENCY/MANUAL Closed TP_CL_EMRG/MAN Transmitted to IEC CONTROL1;CSWI3 ST;DPCSO1;stVal;DPC None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 49 DP_HLA_ ISOOpen_Close DPS 220kV B209_BC 89A COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 50 DP_HLA_ ISOOpen_Close DPS 220kV B209_BC 89A COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 51 DP_HLA_ ISOOpen_Close DPS 220kV B209_BC 89AE1 COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 52 DP_HLA_ ISOOpen_Close DPS 220kV B209_BC 89AE1 COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 53 DP_HLa_ESOpen_Close DPS 220kV B209_BC 89AE2 COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI5 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 54 DP_HLa_ESOpen_Close DPS 220kV B209_BC 89AE2 COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI5 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 55 DP_HLA_ ISOOpen_Close DPS 220kV B209_BC 89B COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 56 DP_HLA_ ISOOpen_Close DPS 220kV B209_BC 89B COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 57 DP_HLa_ESOpen_Close DPS 220kV B209_BC 89BE1 COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 58 DP_HLa_ESOpen_Close DPS 220kV B209_BC 89BE1 COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 59 DP_HLA_ ISOOpen_Close DPS 220kV B209_BC 89BE2 COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 60 DP_HLA_ ISOOpen_Close DPS 220kV B209_BC 89BE2 COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 61 DP_HLa_LocRem_Bay DPS 220kV B209_BC BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 56 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 62 DP_HLa_LocRem_Bay DPS 220kV B209_BC BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 56 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 63 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SC_DE_Off_On SPC 220kV B209_BC SYNCH FUNCTION ON/OFF SECONDARY CONTROL SPC On Off OF_ON_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 CO;EnaSec;ctlVal;DPC 190 IntManualCSFct CS_CtrlOnOff_SPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 DC_DE_LocRem_BayCtrl DPC 220kV B209_BC BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 56 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 DC_DE_LocRem_BayCtrl DPC 220kV B209_BC BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 56 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 MV_HLa_Unused 220kV B209_BC CB_COUNTER Count_Close 0.0 10000.0 Count_Close Transmitted to IEC CONTROL2;GAPC1 MX;AnIn2;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 MV_HLa_Unused 220kV B209_BC CB_COUNTER Count_Open 0.0 10000.0 Count_Open Transmitted to IEC CONTROL2;GAPC1 MX;AnIn1;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
PATH SIGNAL IEC ADDRESS
Scs | Ethernet network | System Group | B201_ICT1 TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B201_ICT1 | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Scs | Ethernet network | System Group | B203_LINE1 TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B203_LINE1 | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Scs | Ethernet network | System Group | B208_TBC TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B208_TBC | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Scs | Ethernet network | System Group | B209_BC TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B209_BC | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
PATH PROFILE SIGNAL IEC ADDRESS
PGCIL | BHADLA | 220kV | B201_ICT1 | PROTECTION |NL_AL_GOOSE RECP 46 : SPE_HLA_Normal_Alarm GOOSE RECEIPT FAIL/TROUBLE CONTROL2; GAPC2 ST; IndSys2
PGCIL | BHADLA | 220kV | B203_LINE1| PROTECTION |NL_AL_GOOSE RECP 46 : SPE_HLA_Normal_Alarm GOOSE RECEIPT FAIL/TROUBLE CONTROL2; GAPC2 ST; IndSys2
PGCIL | BHADLA | 220kV | B208_TBC | PROTECTION |NL_AL_GOOSE RECP 46 : SPE_HLA_Normal_Alarm GOOSE RECEIPT FAIL/TROUBLE CONTROL2; GAPC2 ST; IndSys2
PGCIL | BHADLA | 220kV | B209_BC | PROTECTION |NL_AL_GOOSE RECP 46 : SPE_HLA_Normal_Alarm GOOSE RECEIPT FAIL/TROUBLE CONTROL2; GAPC2 ST; IndSys2
Designation : #REF! Symbol : #REF!
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
SYSTEM INFORMATION DATA DESCRIPTION
Gateway Port used (on gateway) Keys :
SCADA 1 GE Reserved
SCADA 2 Auto generated
SCADA 3 Read Only
SYSTEM INFORMATION SERVER OI
SERVER OI Name :
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Sp0000 SPS AGENCY STATUS HEALTHY FAULTY Agency status 40 SYSTEM INFORMATION SERVER OI AgencyStatus
Sp0000 SPS AUTOMATIC ARCHIVING STATUS HEALTHY FAULTY Auto archiving 40 SYSTEM INFORMATION SERVER OI AutomaticArchiving
Mp0000OIHist MPS HISTORIAN DATABASE STATUS Central archive 40 SYSTEM INFORMATION SERVER OI CentralArchiving
Sp0000 SPS OI SBUS LINK HEALTHY FAULTY Device link 40 SYSTEM INFORMATION SERVER OI CommDevice
Sp0H00 SPS SBUS ACQUISITION STATUS HEALTHY FAULTY IEC Coupling 40 SYSTEM INFORMATION SERVER OI CouplingStatus
Sp0H00 SPS LOGGING QUEUE STATUS HEALTHY FAULTY Log Queue 40 SYSTEM INFORMATION SERVER OI LogQueue
Mp0HLAOpMod MPS OPERATING MODE Operating mode 40 SYSTEM INFORMATION SERVER OI OperatingMode
Sp0H00 SPS REDUNDANCY MODE ACTIVE STANDBY Redundancy mode 40 SYSTEM INFORMATION SERVER OI RedDevice
Mp0HLAOpMod MPS REDUNDANCY STATUS Redundancy status No 40 SYSTEM INFORMATION SERVER OI RedundancyStatus
Sp0H00 SPS SYNCHRONIZATION STATUS HEALTHY FAULTY Synchronisation 40 SYSTEM INFORMATION SERVER OI SyncDevice
OI printer Mp0HLAOIPrt MPS PRINTER STATUS Printer status 40 SYSTEM INFORMATION SERVER OI Printing
OI printer Mp0HLAOIPrt MPS BACKUP PRINTER STATUS BackupPrint stat No 40 SYSTEM INFORMATION SERVER OI BackupPrinting
SYSTEM INFORMATION CLIENT OI
CLIENT OI Name :
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Sp0HLARev SPS CONNECTION STATUS HEALTHY FAULTY OI client link 41 SYSTEM INFORMATION CLIENT OI CommS2K_C
SYSTEM INFORMATION MiCOM C264
MiCOM C264 Name :
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Sp0000 SPS DATABASE INCONSISTENCY YES NO DB incoh. SPS 42 SYSTEM INFORMATION MiCOM C264 DBIncoherency
ScD000Pul SPC C264 DATABASE SWITCHING EXECUTE - DB switch ctrl 42 SYSTEM INFORMATION MiCOM C264 DBSwitch_SPC
Sp0000 SPS C264 SBUS LINK HEALTHY FAULTY Device link 42 SYSTEM INFORMATION MiCOM C264 CommDevice
Sp0000 SPS DIGITAL INPUT ACQUISITION FAULTY HEALTHY DI acq stopped 42 SYSTEM INFORMATION MiCOM C264 DIAcquisitionStopped
DcD000Pul DPC C264 BAYS CONTROL MODE CHANGE REMOTE LOCAL Loc/rem ctrl DPC 42 SYSTEM INFORMATION MiCOM C264 LocRemDevice_DPC
Dp0000 DPS C264 MANAGED BAYS IN CONTROL MODE REMOTE LOCAL Local/remote DPS 42 SYSTEM INFORMATION MiCOM C264 LocRemDevice
Sp0HL0 SPS C264 BAYS IN CONTROL MODE REMOTE LOCAL Local/remote SPS 42 SYSTEM INFORMATION MiCOM C264 LocRemDeviceForIEC
Mv0000Mst MV C264 FAULT LEVEL FOR REDUNDANCY Main status MV 42 SYSTEM INFORMATION MiCOM C264 MainInternalStatus
DcD000Pul DPC C264 FORCE OPERATION MODE TO OPERATIONNAL MAINTENANCE Mode control DPC 42 SYSTEM INFORMATION MiCOM C264 ModeDevice_DPC
Mp0HLAOpMod MPS C264 OPERATING MODE Operating mode 42 SYSTEM INFORMATION MiCOM C264 OperatingMode
ScD000Pul SPC C264 BIU REDUNDANCY RELAY CO 2 ACTIVATE DEACTIVATE Red mode ctrl 42 SYSTEM INFORMATION MiCOM C264 RedChangeMode_SPC
ScD000Pul SPC C264 BIU REDUNDANCY RELAY CO 1 ACTIVATE DEACTIVATE Red Status ctrl 42 SYSTEM INFORMATION MiCOM C264 RedChangeStatus_SPC
Sp0HL0 SPS REDUNDANT C264 CHANGE MODE ACTIVE STANDBY Red. change mode 42 SYSTEM INFORMATION MiCOM C264 RedChangeMode
Sp0HL0 SPS REDUNDANT C264 STATUS ACTIVE STANDBY Red. change stat 42 SYSTEM INFORMATION MiCOM C264 RedChangeStatus
Sp0000 SPS SOFTWARE ERROR DETECTED YES NO Soft. error SPS 42 SYSTEM INFORMATION MiCOM C264 SoftError
Sp0H00 SPS C264 SYNCHRONIZATION STATUS HEALTHY FAULTY Synchronisation 42 SYSTEM INFORMATION MiCOM C264 SyncDevice
DcD000Pul DPC C264 CHANGE EXPLOITATION MODE NORMAL TEST Test control DPC 42 SYSTEM INFORMATION MiCOM C264 TestDevice_DPC
Sp0000 SPS C264 WATCHDOG RELAY STATUS HEALTHY FAULTY Watchdog SPS 42 SYSTEM INFORMATION MiCOM C264 WatchdogError
Dp0000OpM DPS C264 OPERATING MODE RUNNING MAINTENANCE Device mode No 42 SYSTEM INFORMATION MiCOM C264 ModeDevice
Sp0H00 SPS DISTURBANCE FILE ON C264 READY NOT READY DREC ready No 42 SYSTEM INFORMATION MiCOM C264 DisturbUCA2
Sp0000 SPS C264 COUNTERS ACQUISITION TOP YES NO Counter Top No 42 SYSTEM INFORMATION MiCOM C264 CounterTop
Sp0HLARev SPS GPS SYNCHRONISATION SOURCE HEALTHY FAULTY Ext clock status No 42 SYSTEM INFORMATION MiCOM C264 ExtClockStatus
Sp0HL0 SPS C264 REDUNDANCY MODE ACTIVE STANDBY Redundancy mode No 42 SYSTEM INFORMATION MiCOM C264 RedDevice
Sp0HL0 SPS REPORT BUFFER OVERFLOW GTW 1 YES NO Buff Ov Gtw 1 42 SYSTEM INFORMATION MiCOM C264
Sp0HL0 SPS REPORT BUFFER OVERFLOW GTW 2 YES NO Buff Ov Gtw 2
Sp0HL0 SPS REPORT BUFFER OVERFLOW OI YES NO Buff Ov OI
Sp0HL0 SPS REPORT BUFFER OVERFLOW OI BACKUP YES NO Buff Ov OI Bck
Sp0HL0 SPS ALL AIU STATUS FAULTY HEALTHY All AIU status 42 SYSTEM INFORMATION MiCOM C264 GlobalAIUStatus
Sp0HL0 SPS ALL AOU STATUS FAULTY HEALTHY All AOU status 42 SYSTEM INFORMATION MiCOM C264 GlobalAOUStatus
Sp0HL0 SPS ALL CCU STATUS FAULTY HEALTHY All CCU status 42 SYSTEM INFORMATION MiCOM C264 GlobalCCUStatus
Sp0HL0 SPS ALL DIU STATUS FAULTY HEALTHY All DIU status 42 SYSTEM INFORMATION MiCOM C264 GlobalDIUStatus
Sp0HL0 SPS ALL DOU STATUS FAULTY HEALTHY All DOU status 42 SYSTEM INFORMATION MiCOM C264 GlobalDOUStatus
Sp0HL0 SPS ALL TMU STATUS FAULTY HEALTHY All TMU status 42 SYSTEM INFORMATION MiCOM C264 GlobalTMUStatus
Sp0HL0 SPS ALL HBU STATUS FAULTY HEALTHY All HBU status
Sp0HL0 SPS ALL IED STATUS FAULTY HEALTHY All IED status 42 SYSTEM INFORMATION MiCOM C264 GlobalIEDStatus
Sp0HL0 SPS ALL Printer STATUS FAULTY HEALTHY All Printer stat 42 SYSTEM INFORMATION MiCOM C264 GlobalPrinterStatus
Sp0HL0 SPS ALL RACK STATUS FAULTY HEALTHY All rack status 42 SYSTEM INFORMATION MiCOM C264 GlobalRackLinkStatus
Sp0HL0 SPS LOCAL ALARM ACKNOWLEDGEMENT YES NO Local alarm ack No 42 SYSTEM INFORMATION MiCOM C264 LocalAlarmAck_SPS
Sp0HL0 SPS SETTING DONE YES NO Setting done 42 SYSTEM INFORMATION MiCOM C264 SettingDone
Sp0HL0 SPS SETTING FILE DISCORDANCE YES NO Setting disc. 42 SYSTEM INFORMATION MiCOM C264 SettingFileDiscordance
Sp0HL0 SPS SETTING IN PROGRESS YES NO Setting in prog. 42 SYSTEM INFORMATION MiCOM C264 SettingInProgress
Sp0HL0 SPS SETTING INCOHERENCY YES NO Setting incoher. 42 SYSTEM INFORMATION MiCOM C264 SettingIncoherency
BoardBIU Mp0HLABoard MPS BIU BOARD STATUS BIU status 42 SYSTEM INFORMATION MiCOM C264 BIUStatus
BoardGHU Mp0HLABoard MPS GHU BOARD STATUS GHU status 42 SYSTEM INFORMATION MiCOM C264 GHUStatus
BoardAIU201 Mp0HLABoard MPS AIU20x BOARD STATUS AIU status 42 SYSTEM INFORMATION MiCOM C264 AIUStatus
BoardAIU210 Mp0HLABoard MPS AIU20x BOARD STATUS AIU status 42 SYSTEM INFORMATION MiCOM C264 AIUStatus
BoardAOU200 Mp0HLABoard MPS AOU200 BOARD STATUS AOU status 42 SYSTEM INFORMATION MiCOM C264 AOUStatus
BoardDIU Mp0HLABoard MPS DIU BOARD STATUS DIU status 42 SYSTEM INFORMATION MiCOM C264 DIUStatus
BoardDOU Mp0HLABoard MPS DOU BOARD STATUS DOU status 42 SYSTEM INFORMATION MiCOM C264 DOUStatus
BoardCCU Mp0HLABoard MPS CCU BOARD STATUS CCU status 42 SYSTEM INFORMATION MiCOM C264 CCUStatus
BoardTMU Mp0HLABoard MPS TMU BOARD STATUS TMU status 42 SYSTEM INFORMATION MiCOM C264 TIUStatus
BoardHBU Mp0HLABoard MPS HBU BOARD STATUS HBU status
IED Sp0HLARev SPS IED CONNECTION STATUS TO C264 HEALTHY FAULTY IED SPS com. 42 SYSTEM INFORMATION MiCOM C264 CommIED
IED Sp0H00 SPS IED SYNCHRONISATION STATUS HEALTHY FAULTY IED SPS Synchro. 42 SYSTEM INFORMATION MiCOM C264 SyncIED
IED Sp0000 SPS IED DISTURBANCE FILE READY NOT READY IED DREC ready No 42 SYSTEM INFORMATION MiCOM C264 DisturbIED
RackLink Dp0000OpM DPS RACK LINK STATUS HEALTHY FAULTY Rack link status 42 SYSTEM INFORMATION MiCOM C264 RackLinkStatus
PLC Isagraph Mp0HLAIsag MPS ISAGRAF STATUS ISAGRAF status 42 SYSTEM INFORMATION MiCOM C264 ISAGRAFStatus
BoardPrinter Dp0000OpM DPS PRINTER STATUS DPS Printer st. DPS No 42 SYSTEM INFORMATION MiCOM C264 PrinterStatus
BoardPrinter Mp0HLAOIPrt MPS LOCAL PRINTER STATUS Printer Status 42 SYSTEM INFORMATION MiCOM C264 Printing
SCADA Sp0H00 SPS C264 SCADA PORT COMMUNICATION ACTIVE STANDBY Redundancy SPS 42 SYSTEM INFORMATION MiCOM C264 RedSCADA
SCADA Sp0HLARev SPS SCADA CONNECTION STATUS TO C264 HEALTHY FAULTY SCADA SPS com. 42 SYSTEM INFORMATION MiCOM C264 CommSCADA
SYSTEM INFORMATION MiCOM C364
MiCOM C364 Name :
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Sp0000 SPS DATABASE INCONSISTENCY YES NO DB incoh. SPS 43 SYSTEM INFORMATION MiCOM C364 DBIncoherency
ScD000Pul SPC C364 DATABASE SWITCHING EXECUTE - DB switch ctrl 43 SYSTEM INFORMATION MiCOM C364 DBSwitch_SPC
Sp0000 SPS C364 SBUS LINK HEALTHY FAULTY Device link 43 SYSTEM INFORMATION MiCOM C364 CommDevice
DcD000Pul DPC C364 BAYS CONTROL MODE CHANGE REMOTE LOCAL Loc/rem ctrl DPC 43 SYSTEM INFORMATION MiCOM C364 LocRemDevice_DPC
Dp0000 DPS C364 MANAGED BAYS IN CONTROL MODE REMOTE LOCAL Local/remote DPS 43 SYSTEM INFORMATION MiCOM C364 LocRemDevice
Sp0HL0 SPS C364 BAYS IN CONTROL MODE REMOTE LOCAL Local/remote SPS 43 SYSTEM INFORMATION MiCOM C364 LocRemDeviceForIEC
Sp0H00 SPS LOGGING QUEUE STATUS HEALTHY FAULTY Log Queue 43 SYSTEM INFORMATION MiCOM C364 LogQueue
DcD000Pul DPC C364 FORCE OPERATION MODE TO OPERATIONNAL MAINTENANCE Mode control DPC 43 SYSTEM INFORMATION MiCOM C364 ModeDevice_DPC
Mp0HLAOpMod MPS C364 OPERATING MODE Operating mode 43 SYSTEM INFORMATION MiCOM C364 OperatingMode
Sp0000 SPS SOFTWARE ERROR DETECTED YES NO Soft. error SPS 43 SYSTEM INFORMATION MiCOM C364 SoftError
Sp0H00 SPS C364 SYNCHRONIZATION STATUS HEALTHY FAULTY Synchronisation 43 SYSTEM INFORMATION MiCOM C364 SyncDevice
DcD000Pul DPC C364 CHANGE EXPLOITATION MODE NORMAL TEST Test control DPC 43 SYSTEM INFORMATION MiCOM C364 TestDevice_DPC
Sp0000 SPS C364 WATCHDOG RELAY STATUS HEALTHY FAULTY Watchdog SPS 43 SYSTEM INFORMATION MiCOM C364 WatchdogError
Dp0000OpM DPS C364 OPERATING MODE RUNNING MAINTENANCE Device mode No 43 SYSTEM INFORMATION MiCOM C364 ModeDevice
Sp0HLARev SPS GPS SYNCHRONISATION SOURCE HEALTHY FAULTY Ext clock status No 43 SYSTEM INFORMATION MiCOM C364 ExtClockStatus
Sp0HL0 SPS C364 REDUNDANCY MODE ACTIVE STANDBY Redundancy mode No 43 SYSTEM INFORMATION MiCOM C364 RedDevice
IED Sp0HLARev SPS IED CONNECTION STATUS TO C364 HEALTHY FAULTY IED SPS com. 43 SYSTEM INFORMATION MiCOM C364 CommIED
IED Sp0H00 SPS IED SYNCHRONISATION STATUS HEALTHY FAULTY IED SPS Synchro. 43 SYSTEM INFORMATION MiCOM C364 SyncIED
IED Sp0000 SPS IED DISTURBANCE FILE READY NOT READY IED DREC ready No 43 SYSTEM INFORMATION MiCOM C364 DisturbIED
PLC Isagraph Mp0HLAIsag MPS ISAGRAF STATUS ISAGRAF status 43 SYSTEM INFORMATION MiCOM C364 ISAGRAFStatus
SCADA Sp0H00 SPS C364 SCADA PORT COMMUNICATION ACTIVE STANDBY Redundancy SPS 43 SYSTEM INFORMATION MiCOM C364 RedSCADA
SCADA Sp0HLARev SPS SCADA CONNECTION STATUS TO C364 HEALTHY FAULTY SCADA SPS com. 43 SYSTEM INFORMATION MiCOM C364 CommSCADA
SYSTEM INFORMATION UCA2 IED
UCA2 IED Name :
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Sp0HLARev SPS IED SBUS LINK HEALTHY FAULTY Device link 44 SYSTEM INFORMATION UCA2 IED CommDevice
SYSTEM INFORMATION GATEWAY
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
ScD000Pul SPC GTW DATABASE SWITCHING EXECUTE - DB switch ctrl 45 SYSTEM INFORMATION GATEWAY DBSwitch_SPC
Sp0000 SPS GTW SBUS LINK HEALTHY FAULTY Device link 45 SYSTEM INFORMATION GATEWAY CommDevice
DcD000Pul DPC GTW FORCE OPERATION MODE TO OPERATIONNAL MAINTENANCE Mode control DPC 45 SYSTEM INFORMATION GATEWAY ModeDevice_DPC
Mp0HLAOpMod MPS GTW OPERATING MODE Operating mode 45 SYSTEM INFORMATION GATEWAY OperatingMode
Sp0H00 SPS GTW SYNCHRONISATION STATUS HEALTHY FAULTY Synchronisation 45 SYSTEM INFORMATION GATEWAY SyncDevice
SCADA Sp0H00 SPS GTW SCADA PORT COMMUNICATION ACTIVE STANDBY Redundancy SPS 45 SYSTEM INFORMATION GATEWAY RedSCADA
SCADA Sp0HLARev SPS SCADA CONNECTION STATUS TO GTW HEALTHY FAULTY SCADA SPS com. 45 SYSTEM INFORMATION GATEWAY CommSCADA
IED Sp0HLARev SPS IED CONNECTION STATUS TO GTW HEALTHY FAULTY IED SPS com. 42 SYSTEM INFORMATION MiCOM C264 CommIED
IED Sp0H00 SPS IED SYNCHRONISATION STATUS HEALTHY FAULTY IED SPS Synchro. 42 SYSTEM INFORMATION MiCOM C264 SyncIED
PLC Isagraph Mp0HLAIsag MPS ISAGRAF STATUS ISAGRAF status 43 SYSTEM INFORMATION MiCOM C364 ISAGRAFStatus_GTW
SYSTEM INFORMATION IEC 61850
IEC 61850 Name :
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Sp0HLARev SPS IED SBUS LINK HEALTHY FAULTY Device link 46 SYSTEM INFORMATION IEC 61850 CommDevice
Mp0HLAOpMod MPS IED OPERATING MODE Operating mode No 46 SYSTEM INFORMATION IEC 61850 OperatingMode
DcD000Pul DPC IED FORCE OPERATION MODE TO OPERATIONNAL MAINTENANCE Mode control DPC No 46 SYSTEM INFORMATION IEC 61850 ModeDevice_DPC
Sp0H00 SPS REDUNDANCY MODE ACTIVE STANDBY Redundancy mode No 46 SYSTEM INFORMATION IEC 61850 RedDevice
Sp0H00 SPS DISTURBANCE FILE ON IED READY NOT READY DREC ready No 46 SYSTEM INFORMATION IEC 61850 DisturbUCA2
Sp0H00 SPS LOGICAL DEVICE DISTURBANCE FILE READY NOT READY LD DREC ready No 46 SYSTEM INFORMATION IEC 61850 DisturbLD
Sp0000 SPS IEC61850 GENERIC SPS HEALTHY FAULTY IEC61850 gen SPS No 46 SYSTEM INFORMATION IEC 61850 UCA2GenSPS
Dp0000 DPS IEC61850 GENERIC DPS HEALTHY FAULTY IEC61850 gen DPS No 46 SYSTEM INFORMATION IEC 61850 UCA2GenDPS
Mp0000OIHist MPS IEC61850 GENERIC MPS IEC61850 gen MPS No 46 SYSTEM INFORMATION IEC 61850 UCA2GenMPS
ScD000Pul SPC IEC61850 GENERIC SPC HEALTHY FAULTY IEC61850 gen SPC No 46 SYSTEM INFORMATION IEC 61850 UCA2GenSPC
DcD000Pul DPC IEC61850 GENERIC DPC HEALTHY FAULTY IEC61850 gen DPC No 46 SYSTEM INFORMATION IEC 61850 UCA2GenDPC
Mv0000Mst MV IEC61850 GENERIC MV IEC61850 gen MV No 46 SYSTEM INFORMATION IEC 61850 UCA2GenMV
SYSTEM INFORMATION BAY OI
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Sp0000 SPS AGENCY STATUS HEALTHY FAULTY Agency status 47 SYSTEM INFORMATION BAY OI AgencyStatus
Sp0000 SPS AUTOMATIC ARCHIVING STATUS HEALTHY FAULTY Auto archiving 47 SYSTEM INFORMATION BAY OI AutomaticArchiving
Mp0000OIHist MPS HISTORIAN DATABASE STATUS Central archive 47 SYSTEM INFORMATION BAY OI CentralArchiving
Sp0000 SPS OI SBUS LINK HEALTHY FAULTY Device link 47 SYSTEM INFORMATION BAY OI CommDevice
Sp0H00 SPS SBUS ACQUISITION STATUS HEALTHY FAULTY IEC Coupling 47 SYSTEM INFORMATION BAY OI CouplingStatus
Sp0H00 SPS LOGGING QUEUE STATUS HEALTHY FAULTY Log Queue 47 SYSTEM INFORMATION BAY OI LogQueue
Sp0HLARev SPS CONNECTION STATUS HEALTHY FAULTY OI client link 47 SYSTEM INFORMATION BAY OI CommS2K_C
Mp0HLAOpMod MPS OPERATING MODE Operating mode 47 SYSTEM INFORMATION BAY OI OperatingMode
Sp0H00 SPS REDUNDANCY MODE ACTIVE STANDBY Redundancy mode 47 SYSTEM INFORMATION BAY OI RedDevice
Sp0H00 SPS SYNCHRONIZATION STATUS HEALTHY FAULTY Synchronisation 47 SYSTEM INFORMATION BAY OI SyncDevice
Français English Spanish Português Brasil Russian German
First column to begin translation is column 5
SYSTEM INFORMATION SERVER OI SYSTEM INFORMATION SERVER OI SYSTEM INFORMATION SERVER OI SYSTEM INFORMATION SERVER OI SYSTEM INFORMATION SERVER OI SYSTEM INFORMATION SERVER OI
1 | AgencyStatus 1 | AgencyStatus 1 | AgencyStatus 1 | AgencyStatus 1 | AgencyStatus 1 | AgencyStatus
ETAT DE L'AGENCE AGENCY STATUS ESTADO AGENCY ESTADO DA AGENCY IEC СТАТУС ДРАЙВЕРА AGENCY STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Etat de l'agence Agency status Estado Agency Estado Agency Статус драйвера Agency status
1 | AutomaticArchiving 1 | AutomaticArchiving 1 | AutomaticArchiving 1 | AutomaticArchiving 1 | AutomaticArchiving 1 | AutomaticArchiving
ETAT DE L'ARCHIVAGE AUTOMATIQUE AUTOMATIC ARCHIVING STATUS ESTADO ARCHIVO AUTOMATICO ESTADO DO ARQUIVO AUTOMATICO СТАТУС АВТОМАТИЧЕСКОЙ АРХИВАЦИИ AUTOMATIC ARCHIVING STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Archivage Auto Auto archiving Archivo Auto Arquivo Auto Авто архивация Auto archiving
1 | CentralArchiving 1 | CentralArchiving 1 | CentralArchiving 1 | CentralArchiving 1 | CentralArchiving 1 | CentralArchiving
ETAT DE LA BD HISTORIAN HISTORIAN DATABASE STATUS ESTADO BASE DE DATOS HISTORIAN ESTADO BASE DE DADOS HISTORIAN Статус БД Историк HISTORIAN DATABASE STATUS
Archive Centrale Central archive Archivo Central Archivo Central Центр. архив Central archive
1 | CommDevice 1 | CommDevice 1 | CommDevice 1 | CommDevice 1 | CommDevice 1 | CommDevice
ETAT DU LIEN SBUS OI SBUS LINK ENLACE OI SBUS ESTADO DA CONEXAO SBUS СОЕДИНЕНИЕ OI и SBUS OI SBUS LINK
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien SBUS Device link Enlace SBUS Conexao SBUS Связь устройств. Device link
1 | LogQueue 1 | LogQueue 1 | LogQueue 1 | LogQueue 1 | LogQueue 1 | LogQueue
ETAT DE LA FILE D'IMPRESSION LOGGING QUEUE STATUS ESTADO COLA DE EVENTOS ESTADO DA FILA DE EVENTOS СНЯТИЕ ПОКАЗАНИЯ СТАТУСА ОЧЕРЕДИ LOGGING QUEUE STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
File impression Log Queue Cola de Eventos Fila de Eventos Лог очереди Log Queue
1 | OperatingMode 1 | OperatingMode 1 | OperatingMode 1 | OperatingMode 1 | OperatingMode 1 | OperatingMode
MODE OPERATIONNEL OPERATING MODE MODO OPERACIONAL MODO DE OPERACAO РЕЖИМ РАБОТЫ OPERATING MODE
Mode d'Operation Operating mode Modo Operacional Modo do operacao Режим работы Operating mode
1 | RedDevice 1 | RedDevice 1 | RedDevice 1 | RedDevice 1 | RedDevice 1 | RedDevice
MODE DE REDONDANCE REDUNDANCY MODE MODO REDUNDANCIA MODO REDUNDANCIA РЕЖИМ РЕЗЕРВА REDUNDANCY MODE
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
Mode Redondance Redundancy mode Modo Redundancia Modo Redundancia Режим резерва Redundanzmodus
1 | RedundancyStatus 1 | RedundancyStatus 1 | RedundancyStatus 1 | RedundancyStatus 1 | RedundancyStatus 1 | RedundancyStatus
ETAT DE REDONDANCE REDUNDANCY STATUS ESTADO REDUNDANCIA ESTADO REDUNDANCIA СТАТУС РЕЗЕРВА REDUNDANCY STATUS
Etat Redondance Redundancy status Estado Redundancia Estado Redundancia СТАТУС резерва Redundanzstatus
1 | SyncDevice 1 | SyncDevice 1 | SyncDevice 1 | SyncDevice 1 | SyncDevice 1 | SyncDevice
ETAT DE SYNCHRONISATION SYNCHRONIZATION STATUS ESTADO SINCRONIZACION ESTADO DA SINCRONIZACAO СТАТУС СИНХРОНИЗАЦИИ SYNCHRONISIERUNG STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchronisation Synchronisation Sincronización Sincronizacao Синхронизация Synchronisation
1 | CouplingStatus 1 | CouplingStatus 1 | CouplingStatus 1 | CouplingStatus 1 | CouplingStatus 1 | CouplingStatus
ETAT DU COUPLAGE AGENCE SBUS ACQUISITION STATUS ESTADO ADQUISICION SBUS ESTADO AQUISICAO SBUS SBUS СТАТУС СБОРА ДАННЫХ SBUS ACQUISITION STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Couplage IEC IEC Coupling Acople IEC Aquisicao IEC Связь с IEC IEC Coupling
1 | Printing 1 | Printing 1 | Printing 1 | Printing 1 | Printing 1 | Printing
ETAT DE L'IMPRIMANTE PRINTER STATUS ESTADO IMPRESORA ESTADO IMPRESSORA СТАТУС ПРИНТЕРА DRUCKER STATUS
Etat Imprimante Printer status Estado Impresora Estado Impresora СТАТУС ПРИНТЕРА Drucker Status
1 | BackupPrinting 1 | BackupPrinting 1 | BackupPrinting 1 | BackupPrinting 1 | BackupPrinting 1 | BackupPrinting
ETAT DE L'IMPRIMANTE DE RESERVE BACKUP PRINTER STATUS ESTADO IMPRESORA DE RESPALDO ESTADO IMPRESSORA RESERVA СТАТУС РЕЗЕРВНОГО ПРИНТЕРА RESERVE DRUCKER STATUS
Etat Imp Reserve BackupPrint stat Estado Impr.Res. Estado Impr.Res. Ст.резе.принтера Res.Druck stat
SYSTEM INFORMATION CLIENT OI SYSTEM INFORMATION CLIENT OI SYSTEM INFORMATION CLIENT OI SYSTEM INFORMATION CLIENT OI SYSTEM INFORMATION CLIENT OI SYSTEM INFORMATION CLIENT OI
2 | CommS2K_C 2 | CommS2K_C 2 | CommS2K_C 2 | CommS2K_C 2 | CommS2K_C 2 | CommS2K_C
ETAT DE LA CONNECTION CONNECTION STATUS ESTADO CONEXIÓN ESTADO DA CONEXAO СТАТУС СОЕДИНЕНИЯ VERBINDUNG STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien OI CLIENT OI client link Enlace CLIENTE Conexao CLIENTE Связь клиента OI client link
SYSTEM INFORMATION MiCOM C264 SYSTEM INFORMATION MiCOM C264 SYSTEM INFORMATION MiCOM C264 SYSTEM INFORMATION MiCOM C264 SYSTEM INFORMATION MiCOM C264 SYSTEM INFORMATION MiCOM C264
3 | DBIncoherency 3 | DBIncoherency 3 | DBIncoherency 3 | DBIncoherency 3 | DBIncoherency 3 | DBIncoherency
BD INCOHERENTE DATABASE INCONSISTENCY INCONSISTENCIA BASE DE DATOS BD INCOERENTE НЕСОВМЕСТИМОСТЬ БД DATABASE INKONSISTENZ
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
DB incoh. SPS DB incoh. SPS DB incoh. SPS DB incoh. SPS БД несовм. SPS DB incoh. SPS
3 | DBSwitch_SPC 3 | DBSwitch_SPC 3 | DBSwitch_SPC 3 | DBSwitch_SPC 3 | DBSwitch_SPC 3 | DBSwitch_SPC
PERMUTATION DE BD C264 DATABASE SWITCHING CAMBIANDO BASE DE DATOS C264 CHAVEAMENTO DE BD ПЕРЕКЛЮЧЕНИЕ БД НА С264 C264 DATABASE UMSCHALTUNG
EXECUTER EXECUTE EJECUTAR EXECUTAR ВЫПОЛНЕНИЕ AUSFÜHREN
Permutation BD DB switch ctrl Ctrl Cambio BD Chaveamento BD БД Ком переключ. DB switch ctrl
3 | CommDevice 3 | CommDevice 3 | CommDevice 3 | CommDevice 3 | CommDevice 3 | CommDevice
ETAT DU LIEN SBUS C264 SBUS LINK ENLACE C264 SBUS ESTADO DA CONEXAO SBUS СВЯЗЬ с сетью SBUS C264 SBUS LINK
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien Equipement Device link Enlace Dispo. Enlace Dispo. Связь устройств. Gerät Link
3 | DIAcquisitionStopped 3 | DIAcquisitionStopped 3 | DIAcquisitionStopped 3 | DIAcquisitionStopped 3 | DIAcquisitionStopped 3 | DIAcquisitionStopped
ACQUISITION CARTES ENTREES DIGITAL INPUT ACQUISITION ADQUISICION ENTRADAS DIGITALES AQUISICAO ENTRADAS DIGITAIS ОПРОС DI DIGITAL EINGANGSERFASSUNG
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
DI acq arrêtée DI acq stopped Adq. ED detenida Adq. ED detenida Остано.опроса DI DI acq stopped
3 | LocRemDevice_DPC 3 | LocRemDevice_DPC 3 | LocRemDevice_DPC 3 | LocRemDevice_DPC 3 | LocRemDevice_DPC 3 | LocRemDevice_DPC
CHANGEMENT MODE DE CONTRÔLE C264 C264 BAYS CONTROL MODE CHANGE CAMBIO MODO CONTROL BAHIAS C264 CHAVEAR MODO DE CONTROLE DA C264 ИЗМЕНЕНИЕ РЕЖИМА УПРАВЛЕНИЯ ЯЧЕЙКАМИ С264 C264 BAYS CONTROL MODE CHANGE
DISTANT REMOTE REMOTO REMOTO ДИСТАНЦИОННЫЙ FERN
LOCAL LOCAL LOCAL LOCAL МЕСТНЫЙ LOKAL
Loc/Dst ctrl DPC Loc/rem ctrl DPC Loc/rem ctrl DPC Loc/rem ctrl DPC Мес/Дист ком DPC Loc/rem ctrl DPC
3 | LocRemDevice 3 | LocRemDevice 3 | LocRemDevice 3 | LocRemDevice 3 | LocRemDevice 3 | LocRemDevice
ETAT DU MODE DE CONTRÔLE C264 C264 MANAGED BAYS IN CONTROL MODE BAHIAS DEL C264 EN MODO CONTROL MODO DE CONTROLE DA C264 С264 ОБСЛУЖИВАЕТ ЯЧЕЙКИ В РЕЖИМЕ УПРАВЛЕНИЯ C264 MANAGED BAYS IN CONTROL MODE
DISTANT REMOTE REMOTO REMOTO ДИСТАНЦИОННЫЙ FERN
LOCAL LOCAL LOCAL LOCAL МЕСТНЫЙ LOKAL
Local/Dist DPS Local/remote DPS Local/remoto DPS Local/remoto DPS Мес/Дист ком DPS Fern/Lokal Sps
3 | LocRemDeviceForIEC 3 | LocRemDeviceForIEC 3 | LocRemDeviceForIEC 3 | LocRemDeviceForIEC 3 | LocRemDeviceForIEC 3 | LocRemDeviceForIEC
ETAT DU MODE DE CONTRÔLE C264 C264 BAYS IN CONTROL MODE BAHIAS C264 EN MODO CONTROL MODO DE CONTROLE DA C264 РЕЖИМ УПРАВЛЕНИЯ ЯЧЕЙКАМИ С264 C264 FELDSTEUERMODUS
DISTANT REMOTE REMOTO REMOTO ДИСТАНЦИОННЫЙ FERN
LOCAL LOCAL LOCAL LOCAL МЕСТНЫЙ LOKAL
Local/Dist SPS Local/remote SPS Local/remoto SPS Local/remoto SPS Мес/Дист ком SPS Fern/Lokal SPS
3 | MainInternalStatus 3 | MainInternalStatus 3 | MainInternalStatus 3 | MainInternalStatus 3 | MainInternalStatus 3 | MainInternalStatus
NIVEAU DU DEFAUT C264 POUR REDONDANCE C264 FAULT LEVEL FOR REDUNDANCY C264 NIVEL DE FALLA PARA REDUNDANCIA NIVEL DE DEFEITO DA C264 P/ REDUNDANCIA C264 Вины уровня избыточности C264 FEHLERLEVEL REDUNDANZ
Etat Princial MV Main status MV Estado Princ MV Estado Princ MV Основной статус Main status MV
3 | ModeDevice_DPC 3 | ModeDevice_DPC 3 | ModeDevice_DPC 3 | ModeDevice_DPC 3 | ModeDevice_DPC 3 | ModeDevice_DPC
CHANGER LE MODE D'EXPLOITATION C264 FORCE OPERATION MODE TO FORZAR C264 MODO DE OPERACIÓN A CHAVEAR MODO DE OPERACAO C264 Силу режиме для C264 SETZE GERÄTEMODUS IN
OPERATIONNEL OPERATIONNAL OPERACIONAL OPERACIONAL В РАБОТЕ BERTIEBSMODUS
MAINTENANCE MAINTENANCE MANTENIMIENTO MANUTENCAO ОБСЛУЖИВАНИЕ WARTUNG
Mode ctrl DPC Mode control DPC Modo control DPC Modo control DPC Команда режима MODUS UMSCHALT
3 | OperatingMode 3 | OperatingMode 3 | OperatingMode 3 | OperatingMode 3 | OperatingMode 3 | OperatingMode
MODE OPERATIONNEL C264 OPERATING MODE C264 MODO OPERACIÓN MODO DE OPERACAO Режим работы C264 C264 BETRIEBSMODUS
Mode d'Operation Operating mode Modo Operacional Modo do operacao Режим работы Operating mode
3 | RedChangeMode_SPC 3 | RedChangeMode_SPC 3 | RedChangeMode_SPC 3 | RedChangeMode_SPC 3 | RedChangeMode_SPC 3 | RedChangeMode_SPC
RELAIS DE REDONDANCE BIU CO2 C264 BIU REDUNDANCY RELAY CO 2 C264 BIU RELE REDUNDANCIA CO 2 C264 BIU RELE REDUNDANCIA CO 2 C264 BIU Pезервирования Pелейной CO 2 C264 BIU REDUNDANZ RELAIS CO 2
ACTIVER ACTIVATE ACTIVAR ATIVAR АКТИВНО AKTIVIERE
DESACTIVER DEACTIVATE DESACTIVAR DESATIVAR НЕАКТИВНО DEAKTIVIERE
Mode Ctrl Red Red mode ctrl Ctrl Modo Red. Ctrl Modo Red. управ.режи.резер Red Mod Befehl
3 | RedChangeStatus_SPC 3 | RedChangeStatus_SPC 3 | RedChangeStatus_SPC 3 | RedChangeStatus_SPC 3 | RedChangeStatus_SPC 3 | RedChangeStatus_SPC
RELAIS DE REDONDANCE BIU CO1 C264 BIU REDUNDANCY RELAY CO 1 C264 BIU RELE REDUNDANCIA CO 1 C264 BIU RELE REDUNDANCIA CO 1 C264 BIU Pезервирования Pелейной CO 1 C264 BIU REDUNDANZ RELAIS CO 1
ACTIVER ACTIVATE ACTIVAR ATIVAR АКТИВНО AKTIVIERE
DESACTIVER DEACTIVATE DESACTIVAR DESATIVAR НЕАКТИВНО DEAKTIVIERE
Etat Ctrl Red Red Status ctrl Ctrl Estado Red. Ctrl Estado Red. Управ.стат.резер Red Mod Befehl
3 | RedChangeMode 3 | RedChangeMode 3 | RedChangeMode 3 | RedChangeMode 3 | RedChangeMode 3 | RedChangeMode
MODE DE REDONDANCE REDUNDANT C264 CHANGE MODE MODO REDUNDANCIA C264 MODO DA REDUNDANCIA Режим РЕЗЕРВНОГО C264 RESERVE C264 MODE
ACTIF ACTIVE ACTIVA ATIVO ОСНОВНОЙ ACTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
Mode Chgt Red Red. change mode Mod. Cambio Red. Mod. Cambio Red. Реж.перек.резер Red. Änderung Md
3 | RedChangeStatus 3 | RedChangeStatus 3 | RedChangeStatus 3 | RedChangeStatus 3 | RedChangeStatus 3 | RedChangeStatus
ETAT DE REDONDANCE REDUNDANT C264 STATUS ESTADO REDUNDANCIA C264 ESTADO DA REDUNDANCIA СТАТУС РЕЗЕРВНОГО C264 RESERVE C264 STATUS
ACTIF ACTIVE ACTIVA ATIVO ОСНОВНОЙ ACTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
Etat Chgt Red Red. change stat Est. Cambio Red. Est. Cambio Red. Стат.перек.резер Red. Änderung St
3 | SoftError 3 | SoftError 3 | SoftError 3 | SoftError 3 | SoftError 3 | SoftError
ERREUR LOGICIELLE DETECTEE SOFTWARE ERROR DETECTED ERROR DETECTADO SOFTWARE ERRO DE SOFTWARE DETECTADO ОБНАРУЖЕНА ОШИБКА ПО SOFTWAREFEHLER
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Err. Logicielle Soft. error SPS Error Soft. SPS Soft. error SPS Ошибка по SPS Softwarefehler
3 | SyncDevice 3 | SyncDevice 3 | SyncDevice 3 | SyncDevice 3 | SyncDevice 3 | SyncDevice
ETAT DE SYNCHRONISATION C264 SYNCHRONIZATION STATUS ESATDO SINCRONIZACION C264 ESTADO DA SINCRONIZACAO СТАТУС СИНХРОНИЗАЦИИ C264 C264 SYNCHRONISIERUNG STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchronisation Synchronisation Sincronización Sincronizacao Синхронизация Synchronisation
3 | TestDevice_DPC 3 | TestDevice_DPC 3 | TestDevice_DPC 3 | TestDevice_DPC 3 | TestDevice_DPC 3 | TestDevice_DPC
CHANGEMENT MODE EXPLOITATION C264 CHANGE EXPLOITATION MODE CAMBIO MODO EXPLOTACION C264 CHAVEAR MODO DE OPERACAO Смена режима работы C264 C264 TESTMODUS UMSCHALT
OPERATIONNEL NORMAL NORMAL OPERACIONAM НОРМАЛЬНЫЙ NORMAL
TEST TEST PRUEBA TESTE ТЕСТОВОЙ TEST
Ctrl Test DPC Test control DPC Ctrl Prueba DPC Ctrl Prueba DPC ком Тестов. DPC Testmodus DPC
3 | WatchdogError 3 | WatchdogError 3 | WatchdogError 3 | WatchdogError 3 | WatchdogError 3 | WatchdogError
ETAT DU CHIEN DE GARDE C264 C264 WATCHDOG RELAY STATUS ESTADO RELE WATCHDOG C264 ESTADO RELE WATCHDOG C264 СТАТУС WATCHDOG C264 C264 WATCHDOG RELAIS STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA ATIVO НЕИСПРАВНЫЙ FEHLER
Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS
3 | ModeDevice 3 | ModeDevice 3 | ModeDevice 3 | ModeDevice 3 | ModeDevice 3 | ModeDevice
V3 MODE OPERATIONNEL C264 OPERATING MODE C264 MODO OPERACIÓN DISPOSITIVO V3 MODO DE OPERACAO РЕЖИМ РАБОТЫ C264 C264 BETRIEBSMODUS
OPERATIONNEL RUNNING EN SERVICIO EM SERVICO Рабочее BETRIEB
MAINTENANCE MAINTENANCE MANTENIMIENTO MANUTENCAO ОБСЛУЖИВАНИЕ WARTUNG
Mode Eqpt Device mode Modo Dispositivo Modo Dispositivo Режим устройства Gerätemodus
3 | DisturbUCA2 3 | DisturbUCA2 3 | DisturbUCA2 3 | DisturbUCA2 3 | DisturbUCA2 3 | DisturbUCA2
FICHIER DE PERTURBOGRAPHIE C264 DISTURBANCE FILE ON C264 ARCHIVO DE DISTURBIO EN C264 ARQUIVO DE OSCILOGRAFIA C264 ФАЙЛ ОСЦИЛОГРАМ НА C264 STÖRFALLDATEI AUF C264
PRÊT READY LISTO PRONTO ГОТОВ BEREIT
ABSENT NOT READY NO LISTO AUSENTE НЕ ГОТОВ NICHT BEREIT
DREC prêt DREC ready DREC Listo DREC Pronto DREC готов DREC ready
3 | CounterTop 3 | CounterTop 3 | CounterTop 3 | CounterTop 3 | CounterTop 3 | CounterTop
DEMARRAGE DU COMPTAGE C264 COUNTERS ACQUISITION TOP ADQ MAX CONTADORES C264 CONTAGEM PARTIDA Счетчик C264 макс C264 ZÄHLERSTAND MAX
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Max Compteur Counter Top Max Contadores Max Contagem Счетчик макс Zähler max
3 | ExtClockStatus 3 | ExtClockStatus 3 | ExtClockStatus 3 | ExtClockStatus 3 | ExtClockStatus 3 | ExtClockStatus
ETAT DE LA SOURCE DE SYNCHRONISATION GPS SYNCHRONISATION SOURCE FUENTE SINCRONIZACION GPS FONTE SINCRONIZACAO GPS GPS ИСТОЧНИК СИНХРОНИЗАЦИИ GPS SYNCHRONISIERUNG QUELLE
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Etat Horloge Ext clock status Estado Reloj GPS Estado Reloj GPS Статус IRIG-B Ext Uhr Status
3 | RedDevice 3 | RedDevice 3 | RedDevice 3 | RedDevice 3 | RedDevice 3 | RedDevice
MODE DE REDONDANCE C264 REDUNDANCY MODE MODO REDUNDANCIA C264 MODO REDUNDANCIA C264 C264 Режим резервирования C264 REDUNDANZ MODUS
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
Mode Redondance Redundancy mode Modo Redundancia Modo Redundancia Режим резерва Redundanzmodus
3 | BuffOvGtw1 3 | BuffOvGtw1 3 | BuffOvGtw1 3 | BuffOvGtw1 3 | BuffOvGtw1 3 | BuffOvGtw1
DEBORDEMENT DE TAMPON GTW 1 REPORT BUFFER OVERFLOW GTW 1 DESBORDAMIENTO DE BUFER GTW 1 DESBORDAMIENTO DE BUFER GTW 1 Переполнение буфера GTW 1 Pufferüberlauf GTW 1
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Débord. Tampon Gtw 1 Buff Ov Gtw 1 Desbord. Búfer Gtw 1 Desbord. Búfer Gtw 1 Переп. Буфера Gtw 1 Pufferüberlauf Gtw 1
3 | BuffOvGtw2 3 | BuffOvGtw2 3 | BuffOvGtw2 3 | BuffOvGtw2 3 | BuffOvGtw2 3 | BuffOvGtw2
DEBORDEMENT DE TAMPON GTW 2 REPORT BUFFER OVERFLOW GTW 2 DESBORDAMIENTO DE BUFER GTW 2 DESBORDAMIENTO DE BUFER GTW 2 Переполнение буфера GTW 2 Pufferüberlauf GTW 2
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Débord. Tampon OI Buff Ov Gtw 2 Desbord. Búfer Gtw 2 Desbord. Búfer Gtw 2 Переп. Буфера Gtw 2 Pufferüberlauf Gtw 2
3 | BuffOvOI 3 | BuffOvOI 3 | BuffOvOI 3 | BuffOvOI 3 | BuffOvOI 3 | BuffOvOI
DEBORDEMENT DE TAMPON OI REPORT BUFFER OVERFLOW OI DESBORDAMIENTO DE BUFER OI DESBORDAMIENTO DE BUFER OI Переполнение буфера OI Pufferüberlauf OI
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Débord. Tampon Oi Buff Ov Oi Desbord. Búfer Oi Desbord. Búfer Oi Переп. Буфера Oi Pufferüberlauf Oi
3 | BuffOvOIBck 3 | BuffOvOIBck 3 | BuffOvOI Bck 3 | BuffOvOIBck 3 | BuffOvOIBck 3 | BuffOvOIBck
DEBORDEMENT DE TAMPON OI BACKUP REPORT BUFFER OVERFLOW OI BACKUP DESBORDAMIENTO DE BUFER OI BACKUP DESBORDAMIENTO DE BUFER OI BACKUP Переполнение буфера OI BACKUP Pufferüberlauf OI BACKUP
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Débord. Tampon Oi Bck Buff Ov Oi Bck Desbord. Búfer Oi Bck Desbord. Búfer Oi Bck Переп. Буфера Oi Bck Pufferüberlauf Oi Bck
3 | BIUStatus 3 | BIUStatus 3 | BIUStatus 3 | BIUStatus 3 | BIUStatus 3 | BIUStatus
ETAT DE LA CARTE BIU BIU BOARD STATUS ESTADO TARJETA BIU ESTADO DO CARTAO BIU СТАТУС ПЛАТЫ BIU BIU KARTEN STATUS
Etat BIU BIU status Estado BIU Estado BIU BIU статус BIU status
3 | GHUStatus 3 | GHUStatus 3 | GHUStatus 3 | GHUStatus 3 | GHUStatus 3 | GHUStatus
ETAT DE LA CARTE GHU GHU BOARD STATUS ESTADO TARJETA GHU ESTADO DO CARTAO GHU GHU СТАТУС ПЛАТЫ GHU KARTEN STATUS
Etat GHU GHU status Estado GHU Estado GHU GHU статус GHU status
3 | AIUStatus 3 | AIUStatus 3 | AIUStatus 3 | AIUStatus 3 | AIUStatus 3 | AIUStatus
ETAT DE LA CARTE AIU20x AIU20x BOARD STATUS ESTADO TARJETA AIU20x ESTADO DO CARTAO AIU20x AIU20x СТАТУС ПЛАТЫ AIU20x KARTEN STATUS
Etat AIU AIU status Estado AIU Estado AIU AIU статус AIU status
3 | AIUStatus 3 | AIUStatus 3 | AIUStatus 3 | AIUStatus 3 | AIUStatus 3 | AIUStatus
ETAT DE LA CARTE AIU21x AIU21x BOARD STATUS ESTADO TARJETA AIU21x ESTADO DO CARTAO AIU21x AIU21x СТАТУС ПЛАТЫ AIU21x KARTEN STATUS
Etat AIU AIU status Estado AIU Estado AIU AIU статус AIU status
3 | AOUStatus 3 | AOUStatus 3 | AOUStatus 3 | AOUStatus 3 | AOUStatus 3 | AOUStatus
ETAT DE LA CARTE AOU200 AOU200 BOARD STATUS ESTADO TARJETA AOU200 ESTADO DO CARTAO AOU200 AOU200 СТАТУС ПЛАТЫ AOU200 KARTEN STATUS
Etat AOU AOU status Estado AOU Estado AOU AOU статус AOU status
3 | DIUStatus 3 | DIUStatus 3 | DIUStatus 3 | DIUStatus 3 | DIUStatus 3 | DIUStatus
ETAT DE LA CARTE DIU DIU BOARD STATUS ESTADO TARJETA DIU ESTADO DO CARTAO DIU DIU СТАТУС ПЛАТЫ DIU KARTEN STATUS
Etat DIU DIU status Estado DIU Estado DIU DIU статус DIU status
3 | DOUStatus 3 | DOUStatus 3 | DOUStatus 3 | DOUStatus 3 | DOUStatus 3 | DOUStatus
ETAT DE LA CARTE DOU DOU BOARD STATUS ESTADO TARJETA DOU ESTADO DO CARTAO DOU DOU СТАТУС ПЛАТЫ DOU KARTEN STATUS
Etat DOU DOU status Estado DOU Estado DOU DOU статус DOU status
3 | CCUStatus 3 | CCUStatus 3 | CCUStatus 3 | CCUStatus 3 | CCUStatus 3 | CCUStatus
ETAT DE LA CARTE CCU CCU BOARD STATUS ESTADO TARJETA CCU ESTADO DO CARTAO CCU CCU СТАТУС ПЛАТЫ CCU KARTEN STATUS
Etat CCU CCU status Estado CCU Estado CCU CCU статус CCU status
3 | TIUStatus 3 | TIUStatus 3 | TIUStatus 3 | TIUStatus 3 | TIUStatus 3 | TIUStatus
ETAT DE LA CARTE TMU TMU BOARD STATUS ESTADO TARJETA TMU ESTADO DO CARTAO TMU TMU СТАТУС ПЛАТЫ TMU KARTEN STATUS
Etat TMU TMU status Estado TMU Estado TMU TMU статус TMU status
3 | HBUStatus 3 | HBUStatus 3 HBUStatus 3 | HBUStatus 3 |HBUStatus 3 |HBUStatus
ETAT DE LA CARTE HBU HBU BOARD STATUS ESTADO TARJETA HBU ESTADO DO CARTAO HBU HBU СТАТУС ПЛАТЫ HBU KARTEN STATUS
Etat HBU HBU status Estado HBU Estado HBU HBU статус HBU status
3 | CommIED 3 | CommIED 3 | CommIED 3 | CommIED 3 | CommIED 3 | CommIED
ETAT DE LA CONNECTION AU C264 IED CONNECTION STATUS TO C264 ESTADO COMUNICACIÓN IED AL C264 ESTADO DA CONEXAO COM A C264 СТАТУС СВЯЗИ IED С С264 IED VERBINDUNGSSTATUS C264
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Com. IED SPS IED SPS com. IED SPS com. IED SPS com. IED SPS связь. IED SPS com.
3 | SyncIED 3 | SyncIED 3 | SyncIED 3 | SyncIED 3 | SyncIED 3 | SyncIED
ETAT DE LA SYNCHRONISATION DE L'IED IED SYNCHRONISATION STATUS ESTADO SINCRONIZACION IED ESTADO DA SINCRONIZACAO DO RELE IED СТАТУС СИНХРОНИЗАЦИИ IED SYNCHRONISIERUNGSSTATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchro. IED SPS IED SPS Synchro. IED SPS Sincro. IED SPS Sincro. IED SPS синхр. IED SPS Synchro.
3 | DisturbIED 3 | DisturbIED 3 | DisturbIED 3 | DisturbIED 3 | DisturbIED 3 | DisturbIED
FICHIER DE PERTURBOGRAPHIE IED IED DISTURBANCE FILE ARCHIVO DE DISTURBIO EN IED ARQUIVO DE OSCILOGRAFIA IED IED ФАЙЛ ОСЦИЛОГРАМ IED DISTURBANCE FILE
PRÊT READY LISTO PRONTO ГОТОВ BEREIT
ABSENT NOT READY NO LISTO AUSENTE НЕ ГОТОВ NICHT BEREIT
IED DREC Prêt IED DREC ready IED DREC Listo IED DREC Pronto IED DRECготов IED DREC ready
3 | ISAGRAFStatus 3 | ISAGRAFStatus 3 | ISAGRAFStatus 3 | ISAGRAFStatus 3 | ISAGRAFStatus 3 | ISAGRAFStatus
ETAT ISAGRAF ISAGRAF STATUS ESTADO ISAGRAF ESTADO ISAGRAF ISAGRAF статус ISAGRAF STATUS
Etat ISAGRAF ISAGRAF status Estado ISAGRAF Estado ISAGRAF ISAGRAF статус ISAGRAF status
3 | PrinterStatus 3 | PrinterStatus 3 | PrinterStatus 3 | PrinterStatus 3 | PrinterStatus 3 | PrinterStatus
PRINTER STATUS DPS PRINTER STATUS DPS DPS ESTADO IMPRESORA DPS ESTADO IMPRESSORA СТАТУС ПРИНТЕРА DPS DRUCKER STATUS DPS
Etat Impr. DPS Printer st. DPS Edo. Impr. DPS Edo. Impr. DPS стат принт DPS Druckerstat. DPS
3 | Printing 3 | Printing 3 | Printing 3 | Printing 3 | Printing 3 | Printing
ETAT DE L'IMPRIMANTE LOCAL LOCAL PRINTER STATUS ESTADO IMPRESORA LOCAL ESTADO IMPRESSORA LOCAL СТАТУС ПРИНТЕРА LOKAL DRUCKER STATUS
Etat Imprimante Printer Status Edo. Impresora Edo. Impressora статус принтера Drucker Status
3 | RedSCADA 3 | RedSCADA 3 | RedSCADA 3 | RedSCADA 3 | RedSCADA 3 | RedSCADA
PORT DE COMMUNICATION AVEC LE SCADA C264 SCADA PORT COMMUNICATION PTO. COM C264 SCADA CANAL DE COMUNICACAO C/ SCADA СТАТУС ПОРТА СВЯЗЬ C264 с SCADA C264 FWL PORT KOMMUNIKATION
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
SPS Redondance Redundancy SPS Redundancia SPS Redundancia SPS резервирование Redundancy SPS
3 | CommSCADA 3 | CommSCADA 3 | CommSCADA 3 | CommSCADA 3 | CommSCADA 3 | CommSCADA
ETAT DE LA COMMUNICATION SCADA SCADA CONNECTION STATUS TO C264 EDO. CONEXIÓN SCADA AL C264 ESTADO DA CONEXAO C/ SCADA СТАТУС СОЕДИНЕНИЯ SCADA С C264 FWL VERBINDUNGSSTATUS C264
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Com. SCADA SPS SCADA SPS com. SCADA SPS com. SCADA SPS com. SCADA SPS связь FWL SPS KOMMU
3 | GlobalAIUStatus 3 | GlobalAIUStatus 3 | GlobalAIUStatus 3 | GlobalAIUStatus 3 | GlobalAIUStatus 3 | GlobalAIUStatus
TOUS LES ETATS AIU ALL AIU STATUS TODOS LOS AIU ESTADO AIU TODO ESTADO ВСЕ AIU СТАТУС ALLE AIU STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états AIU All AIU status Todos AIU estado AIU todo estado Все AIU статус Alle AIU Status
3 | GlobalAOUStatus 3 | GlobalAOUStatus 3 | GlobalAOUStatus 3 | GlobalAOUStatus 3 | GlobalAOUStatus 3 | GlobalAOUStatus
TOUS LES ETATS AOU ALL AOU STATUS TODOS LOS AOU ESTADO AOU TODO ESTADO ВСЕ АOU СТАТУС ALLE AOU STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états AOU All AOU status Todos AOU estado AOU todo estado Все AOU статус Alle AOU Status
3 | GlobalCCUStatus 3 | GlobalCCUStatus 3 | GlobalCCUStatus 3 | GlobalCCUStatus 3 | GlobalCCUStatus 3 | GlobalCCUStatus
TOUS LES ETATS CCU ALL CCU STATUS TODOS LOS CCU ESTADO CCU TODO ESTADO ВСЕ CCU СТАТУС ALLE CCU STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états CCU All CCU status Todos CCU estado CCU todo estado Все CCU статус Alle CCU Status
3 | GlobalDIUStatus 3 | GlobalDIUStatus 3 | GlobalDIUStatus 3 | GlobalDIUStatus 3 | GlobalDIUStatus 3 | GlobalDIUStatus
TOUS LES ETATS DIU ALL DIU STATUS TODOS LOS DIU ESTADO DIU TODO ESTADO ВСЕ DIU СТАТУС ALLE DIU STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états DIU All DIU status Todos DIU estado DIU todo estado Все DIU статус Alle DIU Status
3 | GlobalDOUStatus 3 | GlobalDOUStatus 3 | GlobalDOUStatus 3 | GlobalDOUStatus 3 | GlobalDOUStatus 3 | GlobalDOUStatus
TOUS LES ETATS DOU ALL DOU STATUS TODOS LOS DOU ESTADO DOU TODO ESTADO ВСЕ DOU СТАТУС ALLE DOU STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états DOU All DOU status Todos DOU estado DOU todo estado Все DOU статус Alle DOU Status
3 | GlobalTMUStatus 3 | GlobalTMUStatus 3 | GlobalTMUStatus 3 | GlobalTMUStatus 3 | GlobalTMUStatus 3 | GlobalTMUStatus
TOUS LES ETATS TMU ALL TMU STATUS TODOS LOS TMU ESTADO TMU TODO ESTADO ВСЕ TMU СТАТУС ALLE TMU STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états TMU All TMU status Todos TMU estado TMU todo estado Все TMU статус Alle TMU Status
3 | GlobalHBUStatus 3 | GlobaHBMUStatus 3 | GlobalHBUStatus 3 | GlobalHBUStatus 3 | GlobalHBUStatus 3 | GlobalHBUStatus
TOUS LES ETATS HBU ALL HBU STATUS TODOS LOS HBU ESTADO HBU TODO ESTADO ВСЕ HBU СТАТУС ALLE HBU STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états HBU All HBU status Todos HBU estado HBU todo estado Все HBU статус Alle HBU Status
3 | GlobalIEDStatus 3 | GlobalIEDStatus 3 | GlobalIEDStatus 3 | GlobalIEDStatus 3 | GlobalIEDStatus 3 | GlobalIEDStatus
TOUS LES ETATS IED ALL IED STATUS TODOS LOS IED ESTADO IED TODO ESTADO ВСЕ IED СТАТУС ALLE IED STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états IED All IED status Todos IED estado IED todo estado Все IED статус Alle IED Status
3 | GlobalPrinterStatus 3 | GlobalPrinterStatus 3 | GlobalPrinterStatus 3 | GlobalPrinterStatus 3 | GlobalPrinterStatus 3 | GlobalPrinterStatus
TOUS LES ETATS D'IMPRIMANTES ALL Printer STATUS TODOS LOS IMPRESSORA ESTADO IMPRESSORA TODO ESTADO ВСЕ ПРИНТЕР СТАТУС ALLE DRUCKER-STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états Impr. All Printer stat Todos Imp.estado Todos Imp.estado Все Принтер стат Alle Druck.Status
3 | GlobalRackLinkStatus 3 | GlobalRackLinkStatus 3 | GlobalRackLinkStatus 3 | GlobalRackLinkStatus 3 | GlobalRackLinkStatus 3 | GlobalRackLinkStatus
TOUS LES ETATS RACK ALL RACK STATUS TODOS LOS RACK ESTADO RACK TODO ESTADO ВСЕ RACK СТАТУС ALLE RACK STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états rack All rack status Todos rack estado rack todo estado Все rack статус Alle rack status
3 | RackLinkStatus 3 | RackLinkStatus 3 | RackLinkStatus 3 | RackLinkStatus 3 | RackLinkStatus 3 | RackLinkStatus
ETAT DU LIEN RACK RACK LINK STATUS RACK DE ENLACE DE ESTADO RACK LINK ESTADO RACK СТАТУС RACK LINK STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Etat lien Rack Rack link status Rack estado Rack estado Rack статус Rack link status
3 | LocalAlarmAck_SPS 3 | LocalAlarmAck_SPS 3 | LocalAlarmAck_SPS 3 | LocalAlarmAck_SPS 3 | LocalAlarmAck_SPS 3 | LocalAlarmAck_SPS
ACQUITTEMENT ALARME LOCALE LOCAL ALARM ACKNOWLEDGEMENT RECONOCIMIENTO DE ALARMA LOCAL LOCAIS ALARME AVISO МЕСТНЫЕ СИГНАЛА ПОДТВЕРЖДЕНИЯ LOKALEN ALARM ANERKENNUNG
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Acq. Alarm loc Local alarm ack Recon Alarma loc Loc Alarme aviso Mес Сигнала подт Zähler max
3 | SettingDone 3 | SettingDone 3 | SettingDone 3 | SettingDone 3 | SettingDone 3 | SettingDone
PARAMETRAGE EFFECTUE SETTING DONE AJUSTE DE HECHO DEFINIR FEITO НАСТРОЙКА ДЕЛАЕТСЯ EINSTELLUNG ERFOLGT
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Parametrage fait Setting done Ajuste de hecho Definir feito Настр делается Einst. Erfolgt
3 | SettingFileDiscordance 3 | SettingFileDiscordance 3 | SettingFileDiscordance 3 | SettingFileDiscordance 3 | SettingFileDiscordance 3 | SettingFileDiscordance
DISCORDANCE FICHIER PARAMETRAGE SETTING FILE DISCORDANCE ARCHIVO DE CONFIGURACION DISCORDANCIA DEFINIÇÃO ARQUIVO DISCORDANCIA НАСТРОЙКА ФАЙЛОВ РАЗНОГОЛОСИЦА EINSTELLUNG DATEI DISSONANZ
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Disc.fich.param Setting disc. Arch.Conf.Disc. Def.Arquivo Disc Настр файлов раз Einst.Dat.Diss.
3 | SettingInProgress 3 | SettingInProgress 3 | SettingInProgress 3 | SettingInProgress 3 | SettingInProgress 3 | SettingInProgress
PARAMETRAGE EN COURS SETTING IN PROGRESS AJUSTE EN MARCHA DEFINIR EM ANDAMENTO УСТАНОВЛЕНИЕ В ХОДЕ EINSTELLUNG IN PROGRESS
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Param en cours Setting in prog. Ajuste en marcha Definir em Andam Устан В Ходе Einst. In prog.
3 | SettingIncoherency 3 | SettingIncoherency 3 | SettingIncoherency 3 | SettingIncoherency 3 | SettingIncoherency 3 | SettingIncoherency
PARAMETRAGE INCOHERENT SETTING INCOHERENCY AJUSTE INCOHERENCY DEFINIR INCOHERENCY УСТАНОВЛЕНИЕ НЕПОСЛЕДОВАТЕЛЬНОСТЬ EINSTELLUNG INCOHERENCY
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Param Invalide Setting incoher. Ajuste incoher. Definir incoher. Устан Непосл Einst. Incoher.
SYSTEM INFORMATION MiCOM C364 SYSTEM INFORMATION MiCOM C364 SYSTEM INFORMATION MiCOM C364 SYSTEM INFORMATION MiCOM C364 SYSTEM INFORMATION MiCOM C364 SYSTEM INFORMATION MiCOM C364
4 | DBIncoherency 4 | DBIncoherency 4 | DBIncoherency 4 | DBIncoherency 4 | DBIncoherency 4 | DBIncoherency
BD INCOHERENTE DATABASE INCONSISTENCY INCONSISTENCIA BASE DE DATOS BD INCOERENTE НЕСОВМЕСТИМОСТЬ БД DATENBANK INKONSISTENZ
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
DB incoh. SPS DB incoh. SPS DB incoh. SPS DB incoh. SPS БД несовм. SPS DB Inkonsistenz
4 | DBSwitch_SPC 4 | DBSwitch_SPC 4 | DBSwitch_SPC 4 | DBSwitch_SPC 4 | DBSwitch_SPC 4 | DBSwitch_SPC
PERMUTATION DE BD C364 C364 DATABASE SWITCHING CAMBIANDO BASE DE DATOS C364 CHAVEAMENTO DE BD C364 ПЕРЕКЛЮЧЕНИЕ БД НА С364 C364 DATABASE UMSCHALTUNG
EXECUTER EXECUTE EJECUTAR EXECUTAR ВЫПОЛНЕНИЕ AUSFÜHREN
Permutation BD DB switch ctrl Ctrl Cambio BD Chaveamento BD БД Ком переключ. DB switch ctrl
4 | CommDevice 4 | CommDevice 4 | CommDevice 4 | CommDevice 4 | CommDevice 4 | CommDevice
ETAT DU LIEN SBUS C364 SBUS LINK ENLACE C364 SBUS ESTADO DA CONEXAO SBUS СВЯЗЬ с сетью SBUS C364 SBUS LINK
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien Equipement Device link Enlace Dispo. Enlace Dispo. Связь устройств. Gerät Link
4 | LocRemDevice_DPC 4 | LocRemDevice_DPC 4 | LocRemDevice_DPC 4 | LocRemDevice_DPC 4 | LocRemDevice_DPC 4 | LocRemDevice_DPC
CHANGEMENT MODE DE CONTRÔLE C364 C364 BAYS CONTROL MODE CHANGE CAMBIO MODO CONTROL BAHIAS C364 CHAVEAR MODO DE CONTROLE DA C364 ИЗМЕНЕНИЕ РЕЖИМА УПРАВЛЕНИЯ ЯЧЕЙКАМИ С264 C364 BAYS CONTROL MODE CHANGE
DISTANT REMOTE REMOTO REMOTO ДИСТАНЦИОННЫЙ FERN
LOCAL LOCAL LOCAL LOCAL МЕСТНЫЙ LOKAL
Loc/Dst ctrl DPC Loc/rem ctrl DPC Loc/rem ctrl DPC Loc/rem ctrl DPC Мес/Дист ком DPC Loc/rem ctrl DPC
4 | LocRemDevice 4 | LocRemDevice 4 | LocRemDevice 4 | LocRemDevice 4 | LocRemDevice 4 | LocRemDevice
ETAT DU MODE DE CONTRÔLE C364 C364 MANAGED BAYS IN CONTROL MODE BAHIAS DEL C364 EN MODO CONTROL MODO DE CONTROLE DA C364 С264 ОБСЛУЖИВАЕТ ЯЧЕЙКИ В РЕЖИМЕ УПРАВЛЕНИЯ C364 MANAGED BAYS IN CONTROL MODE
DISTANT REMOTE REMOTO REMOTO ДИСТАНЦИОННЫЙ FERN
LOCAL LOCAL LOCAL LOCAL МЕСТНЫЙ LOKAL
Local/Dist DPS Local/remote DPS Local/remoto DPS Local/remoto DPS Мес/Дист ком DPS Fern/Lokal Sps
4 | LocRemDeviceForIEC 4 | LocRemDeviceForIEC 4 | LocRemDeviceForIEC 4 | LocRemDeviceForIEC 4 | LocRemDeviceForIEC 4 | LocRemDeviceForIEC
ETAT DU MODE DE CONTRÔLE C364 C364 BAYS IN CONTROL MODE BAHIAS C364 EN MODO CONTROL MODO DE CONTROLE DA C364 РЕЖИМ УПРАВЛЕНИЯ ЯЧЕЙКАМИ С264 C364 FELDSTEUERMODUS
DISTANT REMOTE REMOTO REMOTO ДИСТАНЦИОННЫЙ FERN
LOCAL LOCAL LOCAL LOCAL МЕСТНЫЙ LOKAL
Local/Dist SPS Local/remote SPS Local/remoto SPS Local/remoto SPS Мес/Дист ком SPS Fern/Lokal SPS
4 | LogQueue 4 | LogQueue 4 | LogQueue 4 | LogQueue 4 | LogQueue 4 | LogQueue
ETAT DE LA FILE D'IMPRESSION LOGGING QUEUE STATUS ESTADO COLA DE EVENTOS ESTADO DA FILA DE EVENTOS СНЯТИЕ ПОКАЗАНИЯ СТАТУСА ОЧЕРЕДИ LOGGING QUEUE STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
File impression Log Queue Cola de Eventos Fila de Eventos Лог очереди Log Queue
4 | ModeDevice_DPC 4 | ModeDevice_DPC 4 | ModeDevice_DPC 4 | ModeDevice_DPC 4 | ModeDevice_DPC 4 | ModeDevice_DPC
CHANGER LE MODE D'EXPLOITATION C364 C364 FORCE OPERATION MODE TO FORZAR C364 MODO DE OPERACIÓN A CHAVEAR C364 MODO DE OPERACAO C364 Силу режиме для C364 SETZE GERÄTEMODUS IN
OPERATIONNEL OPERATIONNAL OPERACIONAL OPERACIONAL В РАБОТЕ BERTIEBSMODUS
MAINTENANCE MAINTENANCE MANTENIMIENTO MANUTENCAO ОБСЛУЖИВАНИЕ WARTUNG
Mode ctrl DPC Mode control DPC Modo control DPC Modo control DPC Команда режима MODUS UMSCHALT
4 | OperatingMode 4 | OperatingMode 4 | OperatingMode 4 | OperatingMode 4 | OperatingMode 4 | OperatingMode
MODE OPERATIONNEL C364 C364 OPERATING MODE C364 MODO OPERACIÓN C364 MODO DE OPERACAO Режим работы C364 C364 BETRIEBSMODUS
Mode d'Operation Operating mode Modo Operacional Modo do operacao Режим работы Operating mode
4 | SoftError 4 | SoftError 4 | SoftError 4 | SoftError 4 | SoftError 4 | SoftError
ERREUR LOGICIELLE DETECTEE SOFTWARE ERROR DETECTED ERROR DETECTADO SOFTWARE ERRO DE SOFTWARE DETECTADO ОБНАРУЖЕНА ОШИБКА ПО SOFTWAREFEHLER
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Err. Logicielle Soft. error SPS Error Soft. SPS Soft. error SPS Ошибка по SPS Softwarefehler
4 | SyncDevice 4 | SyncDevice 4 | SyncDevice 4 | SyncDevice 4 | SyncDevice 4 | SyncDevice
ETAT DE SYNCHRONISATION C364 C364 SYNCHRONIZATION STATUS ESATDO SINCRONIZACION C364 ESTADO DA SINCRONIZACAO C364 СТАТУС СИНХРОНИЗАЦИИ C364 C364 SYNCHRONISIERUNG STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchronisation Synchronisation Sincronización Sincronizacao Синхронизация Synchronisation
4 | TestDevice_DPC 4 | TestDevice_DPC 4 | TestDevice_DPC 4 | TestDevice_DPC 4 | TestDevice_DPC 4 | TestDevice_DPC
CHANGEMENT MODE EXPLOITATION C364 C364 CHANGE EXPLOITATION MODE CAMBIO MODO EXPLOTACION C364 CHAVEAR MODO DE OPERACAO C364 Смена режима работы C364 C364 TESTMODUS UMSCHALT
OPERATIONNEL NORMAL NORMAL OPERACIONAM НОРМАЛЬНЫЙ NORMAL
TEST TEST PRUEBA TESTE ТЕСТОВОЙ TEST
Ctrl Test DPC Test control DPC Ctrl Prueba DPC Ctrl Prueba DPC ком Тестов. DPC Testmodus DPC
4 | WatchdogError 4 | WatchdogError 4 | WatchdogError 4 | WatchdogError 4 | WatchdogError 4 | WatchdogError
ETAT DU CHIEN DE GARDE C364 C364 WATCHDOG RELAY STATUS ESTADO RELE WATCHDOG C364 ESTADO RELE WATCHDOG C364 СТАТУС WATCHDOG C364 C364 WATCHDOG RELAIS STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA ATIVO НЕИСПРАВНЫЙ FEHLER
Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS
4 | ModeDevice 4 | ModeDevice 4 | ModeDevice 4 | ModeDevice 4 | ModeDevice 4 | ModeDevice
V3 MODE OPERATIONNEL C364 OPERATING MODE C364 MODO OPERACIÓN DISPOSITIVO V3 MODO DE OPERACAO РЕЖИМ РАБОТЫ C364 C364 BETRIEBSMODUS
OPERATIONNEL RUNNING EN SERVICIO EM SERVICO Рабочее BETRIEB
MAINTENANCE MAINTENANCE MANTENIMIENTO MANUTENCAO ОБСЛУЖИВАНИЕ WARTUNG
Mode Eqpt Device mode Modo Dispositivo Modo Dispositivo Режим устройства Gerätemodus
4 | ExtClockStatus 4 | ExtClockStatus 4 | ExtClockStatus 4 | ExtClockStatus 4 | ExtClockStatus 4 | ExtClockStatus
ETAT DE LA SOURCE DE SYNCHRONISATION GPS SYNCHRONISATION SOURCE FUENTE SINCRONIZACION GPS FONTE SINCRONIZACAO GPS GPS ИСТОЧНИК СИНХРОНИЗАЦИИ GPS SYNCHRONISIERUNG QUELLE
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Etat Horloge Ext clock status Estado Reloj GPS Estado Reloj GPS Статус IRIG-B Ext Uhr Status
4 | RedDevice 4 | RedDevice 4 | RedDevice 4 | RedDevice 4 | RedDevice 4 | RedDevice
MODE DE REDONDANCE C364 C364 REDUNDANCY MODE MODO REDUNDANCIA C364 MODO REDUNDANCIA C364 C364 Режим резервирования C364 REDUNDANZ MODUS
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
Mode Redondance Redundancy mode Modo Redundancia Modo Redundancia Режим резерва Redundanzmodus
4 | CommIED 4 | CommIED 4 | CommIED 4 | CommIED 4 | CommIED 4 | CommIED
ETAT DE LA CONNECTION AU C364 IED CONNECTION STATUS TO C364 ESTADO COMUNICACIÓN IED AL C364 ESTADO DA CONEXAO COM A C364 СТАТУС СВЯЗИ IED С С264 IED VERBINDUNGSSTATUS C364
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Com. IED SPS IED SPS com. IED SPS com. IED SPS com. IED SPS связь. IED SPS com.
4 | SyncIED 4 | SyncIED 4 | SyncIED 4 | SyncIED 4 | SyncIED 4 | SyncIED
ETAT DE LA SYNCHRONISATION DE L'IED IED SYNCHRONISATION STATUS ESTADO SINCRONIZACION IED ESTADO DA SINCRONIZACAO DO RELE IED СТАТУС СИНХРОНИЗАЦИИ IED SYNCHRONISIERUNGSSTATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchro. IED SPS IED SPS Synchro. IED SPS Sincro. IED SPS Sincro. IED SPS синхр. IED SPS Synchro.
4 | DisturbIED 4 | DisturbIED 4 | DisturbIED 4 | DisturbIED 4 | DisturbIED 4 | DisturbIED
FICHIER DE PERTURBOGRAPHIE IED IED DISTURBANCE FILE ARCHIVO DE DISTURBIO EN IED ARQUIVO DE OSCILOGRAFIA IED IED ФАЙЛ ОСЦИЛОГРАМ IED DISTURBANCE FILE
PRÊT READY LISTO PRONTO ГОТОВ BEREIT
ABSENT NOT READY NO LISTO AUSENTE НЕ ГОТОВ NICHT BEREIT
IED DREC Prêt IED DREC ready IED DREC Listo IED DREC Pronto IED DRECготов IED DREC ready
4 | ISAGRAFStatus 4 | ISAGRAFStatus 4 | ISAGRAFStatus 4 | ISAGRAFStatus 4 | ISAGRAFStatus 4 | ISAGRAFStatus
ETAT ISAGRAF ISAGRAF STATUS ESTADO ISAGRAF ESTADO ISAGRAF ISAGRAF статус ISAGRAF STATUS
Etat ISAGRAF ISAGRAF status Estado ISAGRAF Estado ISAGRAF ISAGRAF статус ISAGRAF status
4 | RedSCADA 4 | RedSCADA 4 | RedSCADA 4 | RedSCADA 4 | RedSCADA 4 | RedSCADA
PORT DE COMMUNICATION C364 AVEC LE SCADA C364 SCADA PORT COMMUNICATION PTO. COM C364 SCADA CANAL DE COMUNICACAO C364 C/ SCADA СТАТУС ПОРТА СВЯЗЬ C364 с SCADA C364 FWL PORT KOMMUNIKATION
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
SPS Redondance Redundancy SPS Redundancia SPS Redundancia SPS резервирование Redundancy SPS
4 | CommSCADA 4 | CommSCADA 4 | CommSCADA 4 | CommSCADA 4 | CommSCADA 4 | CommSCADA
ETAT DE LA COMMUNICATION SCADA C364 SCADA CONNECTION STATUS TO C364 EDO. CONEXIÓN SCADA AL C364 ESTADO DA CONEXAO C364 C/ SCADA СТАТУС СОЕДИНЕНИЯ SCADA С C364 FWL VERBINDUNGSSTATUS C364
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Com. SCADA SPS SCADA SPS com. SCADA SPS com. SCADA SPS com. SCADA SPS связь FWL SPS KOMMU
SYSTEM INFORMATION UCA2 IED SYSTEM INFORMATION UCA2 IED SYSTEM INFORMATION UCA2 IED SYSTEM INFORMATION UCA2 IED SYSTEM INFORMATION UCA2 IED SYSTEM INFORMATION UCA2 IED
5 | CommDevice 5 | CommDevice 5 | CommDevice 5 | CommDevice 5 | CommDevice 5 | CommDevice
ETAT DU LIEN IED SBUS IED SBUS LINK ENLACE IED SBUS ESTADO DA CONEXAO IED SBUS IED SBUS связь IED SBUS LINK
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien Equipement Device link Enlace Dispo. Enlace Dispo. Связь устройств. Gerät Link
SYSTEM INFORMATION GATEWAY SYSTEM INFORMATION GATEWAY SYSTEM INFORMATION GATEWAY SYSTEM INFORMATION GATEWAY SYSTEM INFORMATION GATEWAY SYSTEM INFORMATION GATEWAY
6 | DBSwitch_SPC 6 | DBSwitch_SPC 6 | DBSwitch_SPC 6 | DBSwitch_SPC 6 | DBSwitch_SPC 6 | DBSwitch_SPC
PERMUTATION DE BD GTW GTW DATABASE SWITCHING CAMBIANDO BASE DE DATOS GTW CHAVEAMENTO DE BD GTW ПЕРЕКЛЮЧЕНИЕ БД GTW GTW DATENBANKUMSCHALTUNG
EXECUTER EXECUTE EJECUTAR EXECUTAR ВЫПОЛНЕНИЕ AUSFÜHREN
Permutation BD DB switch ctrl Ctrl Cambio BD Chaveamento BD БД Ком переключ. DB switch ctrl
6 | CommDevice 6 | CommDevice 6 | CommDevice 6 | CommDevice 6 | CommDevice 6 | CommDevice
ETAT DU LIEN GTW SBUS GTW SBUS LINK ENLACE GTW SBUS ESTADO DA CONEXAO GTW SBUS GTW SBUS СВЯЗЬ GTW SBUS LINK
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien Equipement Device link Enlace Dispo. Enlace Dispo. Связь устройств. Device link
6 | ModeDevice_DPC 6 | ModeDevice_DPC 6 | ModeDevice_DPC 6 | ModeDevice_DPC 6 | ModeDevice_DPC 6 | ModeDevice_DPC
CHANGER LE MODE D'EXPLOITATION GTW GTW FORCE OPERATION MODE TO FORZAR GTW MODO DE OPERACIÓN A CHAVEAR GTW MODO DE OPERACAO GTW ПЕРЕЙТИ В РЕЖИМ GTW UMSCHALTUNG BETRIEBSMODUS
OPERATIONNEL OPERATIONNAL OPERACIONAL OPERACIONAL В РАБОТЕ BERTIEBSMODUS
MAINTENANCE MAINTENANCE MANTENIMIENTO MANUTENCAO ОБСЛУЖИВАНИЕ WARTUNG
Mode ctrl DPC Mode control DPC Modo control DPC Modo control DPC Команда режима MODUS UMSCHALT
6 | OperatingMode 6 | OperatingMode 6 | OperatingMode 6 | OperatingMode 6 | OperatingMode 6 | OperatingMode
MODE OPERATIONNEL GTW GTW OPERATING MODE MODO OPERACIONAL GTW GTW MODO DE OPERACAO GTW Режим работы GTW BETRIEBSMODUS
Mode d'Operation Operating mode Modo Operacional Modo do operacao Режим работы Operating mode
6 | SyncDevice 6 | SyncDevice 6 | SyncDevice 6 | SyncDevice 6 | SyncDevice 6 | SyncDevice
ETAT DE SYNCHRONISATION GTW GTW SYNCHRONISATION STATUS ESTADO SINCRONIZACION GTW ESTADO DA SINCRONIZACAO GTW GTW СТАТУС СИНХРОНИЗАЦИИ GTW SYNCHRONISATION STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchronisation Synchronisation Sincronización Sincronizacao Синхронизация Synchronisation
6 | RedSCADA 6 | RedSCADA 6 | RedSCADA 6 | RedSCADA 6 | RedSCADA 6 | RedSCADA
PORT DE COMMUNICATION GTW AVEC LE SCADA GTW SCADA PORT COMMUNICATION PTO. COM GTW SCADA CANAL DE COMUNICACAO GTW C/ SCADA СТАТУС ПОРТА СВЯЗЬ GTW c SCADA GTW FWL PORT KOMMUNIKATION
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
SPS Redondance Redundancy SPS Redundancia SPS Redundancia SPS резервирование Redundancy SPS
6 | CommSCADA 6 | CommSCADA 6 | CommSCADA 6 | CommSCADA 6 | CommSCADA 6 | CommSCADA
ETAT DE LA COMMUNICATION GTW SCADA SCADA CONNECTION STATUS TO GTW EDO. CONEXIÓN SCADA AL GTW ESTADO DA CONEXAO GTW C/ SCADA СТАТУС СОЕДИНЕНИЯ SCADA С GTW FWL VERBINDUNGSSTATUS GTW
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Com. SCADA SPS SCADA SPS com. SCADA SPS com. SCADA SPS com. SCADA SPS связь FWL SPS KOMMU
6 | CommIED 6 | CommIED 6 | CommIED 6 | CommIED 6 | CommIED 6 | CommIED
ETAT DE LA CONNECTION GTW IED CONNECTION STATUS TO GTW ESTADO COMUNICACIÓN IED AL GTW ESTADO DA CONEXAO COM A GTW СТАТУС СВЯЗИ IED С GTW IED VERBINDUNGSSTATUS GTW
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Com. IED SPS IED SPS com. IED SPS com. IED SPS com. IED SPS связь. IED SPS com.
6 | SyncIED 6| SyncIED 6 | SyncIED 6 | SyncIED 6 | SyncIED 6 | SyncIED
ETAT DE LA SYNCHRONISATION DE L'IED IED SYNCHRONISATION STATUS ESTADO SINCRONIZACION IED ESTADO DA SINCRONIZACAO DO RELE IED СТАТУС СИНХРОНИЗАЦИИ IED SYNCHRONISIERUNGSSTATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchro. IED SPS IED SPS Synchro. IED SPS Sincro. IED SPS Sincro. IED SPS синхр. IED SPS Synchro.
6 | ISAGRAFStatus 6 | ISAGRAFStatus 6 | ISAGRAFStatus 6 | ISAGRAFStatus 6 | ISAGRAFStatus 6 | ISAGRAFStatus
ETAT ISAGRAF ISAGRAF STATUS ESTADO ISAGRAF ESTADO ISAGRAF ISAGRAF статус ISAGRAF STATUS
Etat ISAGRAF ISAGRAF status Estado ISAGRAF Estado ISAGRAF ISAGRAF статус ISAGRAF status
SYSTEM INFORMATION IEC 61850 SYSTEM INFORMATION IEC 61850 SYSTEM INFORMATION IEC 61850 SYSTEM INFORMATION IEC 61850 SYSTEM INFORMATION IEC 61850 SYSTEM INFORMATION IEC 61850
7 | CommDevice 7 | CommDevice 7 | CommDevice 7 | CommDevice 7 | CommDevice 7 | CommDevice
ETAT DU LIEN IED SBUS IED SBUS LINK ENLACE IED SBUS ESTADO DA CONEXAO IED SBUS IED SBUS связь IED SBUS LINK
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien Equipement Device link Enlace Dispo. Enlace Dispo. Связь устройств. Gerät Link
7 | OperatingMode 7 | OperatingMode 7 | OperatingMode 7 | OperatingMode 7 | OperatingMode 7 | OperatingMode
MODE OPERATIONNEL IED OPERATING MODE IED MODO OPERACIÓN MODO DE OPERACAO Режим работы IED IED BETRIEBSMODUS
Mode d'Operation Operating mode Modo Operacional Modo do operacao Режим работы Operating mode
7 | ModeDevice_DPC 7 | ModeDevice_DPC 7 | ModeDevice_DPC 7 | ModeDevice_DPC 7 | ModeDevice_DPC 7 | ModeDevice_DPC
CHANGER LE MODE D'EXPLOITATION IED FORCE OPERATION MODE TO FORZAR IED MODO DE OPERACIÓN A CHAVEAR MODO DE OPERACAO IED Силу режиме для IED SETZE GERÄTEMODUS IN
OPERATIONNEL OPERATIONNAL OPERACIONAL OPERACIONAL В РАБОТЕ BERTIEBSMODUS
MAINTENANCE MAINTENANCE MANTENIMIENTO MANUTENCAO ОБСЛУЖИВАНИЕ WARTUNG
Mode ctrl DPC Mode control DPC Modo control DPC Modo control DPC Команда режима MODUS UMSCHALT
7 | RedDevice 7 | RedDevice 7 | RedDevice 7 | RedDevice 7 | RedDevice 7 | RedDevice
MODE DE REDONDANCE REDUNDANCY MODE MODO REDUNDANCIA MODO REDUNDANCIA РЕЖИМ РЕЗЕРВА REDUNDANCY MODE
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
Mode Redondance Redundancy mode Modo Redundancia Modo Redundancia Режим резерва Redundanzmodus
7 | DisturbUCA2 7 | DisturbUCA2 7 | DisturbUCA2 7 | DisturbUCA2 7 | DisturbUCA2 7 | DisturbUCA2
FICHIER DE PERTURBOGRAPHIE IED DISTURBANCE FILE ON IED ARCHIVO DE DISTURBIO EN IED ARQUIVO DE OSCILOGRAFIA IED ФАЙЛ ОСЦИЛОГРАМ НА IED STÖRFALLDATEI AUF IED
PRÊT READY LISTO PRONTO ГОТОВ BEREIT
ABSENT NOT READY NO LISTO AUSENTE НЕ ГОТОВ NICHT BEREIT
DREC prêt DREC ready DREC Listo DREC Pronto DREC готов DREC ready
7 | DisturbLD 7 | DisturbLD 7 | DisturbLD 7 | DisturbLD 7 | DisturbLD 7 | DisturbLD
FICHIER DE PERTURBOGRAPHIE LD LOGICAL DEVICE DISTURBANCE FILE ARCHIVO DE DISTURBIO LD ARQUIVO DE OSCILOGRAFIA LD ФАЙЛ ОСЦИЛОГРАМ LD STÖRFALLDATEI LD
PRÊT READY LISTO PRONTO ГОТОВ BEREIT
ABSENT NOT READY NO LISTO AUSENTE НЕ ГОТОВ NICHT BEREIT
LD DREC prêt LD DREC ready LD DREC Listo LD DREC Pronto LD DREC готов LD DREC ready
7 | UCA2GenSPS 7 | UCA2GenSPS 7 | UCA2GenSPS 7 | UCA2GenSPS 7 | UCA2GenSPS 7 | UCA2GenSPS
IEC61850 GENERIC SPS IEC61850 GENERIC SPS IEC61850 GENERIC SPS IEC61850 GENERIC SPS IEC61850 GENERIC SPS IEC61850 GENERIC SPS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS
7 | UCA2GenDPS 7 | UCA2GenDPS 7 | UCA2GenDPS 7 | UCA2GenDPS 7 | UCA2GenDPS 7 | UCA2GenDPS
IEC61850 GENERIC DPS IEC61850 GENERIC DPS IEC61850 GENERIC DPS IEC61850 GENERIC DPS IEC61850 GENERIC DPS IEC61850 GENERIC DPS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS
7 | UCA2GenMPS 7 | UCA2GenMPS 7 | UCA2GenMPS 7 | UCA2GenMPS 7 | UCA2GenMPS 7 | UCA2GenMPS
IEC61850 GENERIC MPS IEC61850 GENERIC MPS IEC61850 GENERIC MPS IEC61850 GENERIC MPS IEC61850 GENERIC MPS IEC61850 GENERIC MPS
IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS
7 | UCA2GenSPC 7 | UCA2GenSPC 7 | UCA2GenSPC 7 | UCA2GenSPC 7 | UCA2GenSPC 7 | UCA2GenSPC
IEC61850 GENERIC SPC IEC61850 GENERIC SPC IEC61850 GENERIC SPC IEC61850 GENERIC SPC IEC61850 GENERIC SPC IEC61850 GENERIC SPC
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC
7 | UCA2GenDPC 7 | UCA2GenDPC 7 | UCA2GenDPC 7 | UCA2GenDPC 7 | UCA2GenDPC 7 | UCA2GenDPC
IEC61850 GENERIC DPC IEC61850 GENERIC DPC IEC61850 GENERIC DPC IEC61850 GENERIC DPC IEC61850 GENERIC DPC IEC61850 GENERIC DPC
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC
7 | UCA2GenMV 7 | UCA2GenMV 7 | UCA2GenMV 7 | UCA2GenMV 7 | UCA2GenMV 7 | UCA2GenMV
IEC61850 GENERIC MV IEC61850 GENERIC MV IEC61850 GENERIC MV IEC61850 GENERIC MV IEC61850 GENERIC MV IEC61850 GENERIC MV
IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV
SYSTEM INFORMATION BAY OI SYSTEM INFORMATION BAY OI SYSTEM INFORMATION BAY OI SYSTEM INFORMATION BAY OI SYSTEM INFORMATION BAY OI SYSTEM INFORMATION BAY OI
8 | AgencyStatus 8 | AgencyStatus 8 | AgencyStatus 8 | AgencyStatus 8 | AgencyStatus 8 | AgencyStatus
ETAT DE L'AGENCE AGENCY STATUS ESTADO AGENCY ESTADO DA AGENCY IEC СТАТУС ДРАЙВЕРА AGENCY STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Etat de l'agence Agency status Estado Agency Estado Agency Статус драйвера Agency status
8 | AutomaticArchiving 8 | AutomaticArchiving 8 | AutomaticArchiving 8 | AutomaticArchiving 8 | AutomaticArchiving 8 | AutomaticArchiving
ETAT DE L'ARCHIVAGE AUTOMATIQUE AUTOMATIC ARCHIVING STATUS ESTADO ARCHIVO AUTOMATICO ESTADO DO ARQUIVO AUTOMATICO СТАТУС АВТОМАТИЧЕСКОЙ АРХИВАЦИИ AUTOMATIC ARCHIVING STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Archivage Auto Auto archiving Archivo Auto Arquivo Auto Авто архивация Auto archiving
8 | CentralArchiving 8 | CentralArchiving 8 | CentralArchiving 8 | CentralArchiving 8 | CentralArchiving 8 | CentralArchiving
ETAT DE LA BD HISTORIAN HISTORIAN DATABASE STATUS ESTADO BASE DE DATOS HISTORIAN ESTADO BASE DE DADOS HISTORIAN Статус БД Историк HISTORIAN DATABASE STATUS
Archive Centrale Central archive Archivo Central Archivo Central Центр. архив Central archive
8 | CommDevice 8 | CommDevice 8 | CommDevice 8 | CommDevice 8 | CommDevice 8 | CommDevice
ETAT DU LIEN SBUS OI SBUS LINK ENLACE OI SBUS ESTADO DA CONEXAO SBUS СОЕДИНЕНИЕ OI и SBUS OI SBUS LINK
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien SBUS Device link Enlace SBUS Conexao SBUS Связь устройств. Device link
8 | LogQueue 8 | LogQueue 8 | LogQueue 8 | LogQueue 8 | LogQueue 8 | LogQueue
ETAT DE LA FILE D'IMPRESSION LOGGING QUEUE STATUS ESTADO COLA DE EVENTOS ESTADO DA FILA DE EVENTOS СНЯТИЕ ПОКАЗАНИЯ СТАТУСА ОЧЕРЕДИ LOGGING QUEUE STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
File impression Log Queue Cola de Eventos Fila de Eventos Лог очереди Log Queue
8 | OperatingMode 8 | OperatingMode 8 | OperatingMode 8 | OperatingMode 8 | OperatingMode 8 | OperatingMode
MODE OPERATIONNEL OPERATING MODE MODO OPERACIONAL MODO DE OPERACAO РЕЖИМ РАБОТЫ OPERATING MODE
Mode d'Operation Operating mode Modo Operacional Modo do operacao Режим работы Operating mode
8 | RedDevice 8 | RedDevice 8 | RedDevice 8 | RedDevice 8 | RedDevice 8 | RedDevice
MODE DE REDONDANCE REDUNDANCY MODE MODO REDUNDANCIA MODO REDUNDANCIA РЕЖИМ РЕЗЕРВА REDUNDANCY MODE
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
Mode Redondance Redundancy mode Modo Redundancia Modo Redundancia Режим резерва Redundanzmodus
8 | SyncDevice 8 | SyncDevice 8 | SyncDevice 8 | SyncDevice 8 | SyncDevice 8 | SyncDevice
ETAT DE SYNCHRONISATION SYNCHRONIZATION STATUS ESTADO SINCRONIZACION ESTADO DA SINCRONIZACAO СТАТУС СИНХРОНИЗАЦИИ SYNCHRONISIERUNG STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchronisation Synchronisation Sincronización Sincronizacao Синхронизация Synchronisation
8 | CouplingStatus 8 | CouplingStatus 8 | CouplingStatus 8 | CouplingStatus 8 | CouplingStatus 8 | CouplingStatus
ETAT DU COUPLAGE AGENCE SBUS ACQUISITION STATUS ESTADO ADQUISICION SBUS ESTADO AQUISICAO SBUS SBUS СТАТУС СБОРА ДАННЫХ SBUS ACQUISITION STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Couplage IEC IEC Coupling Acople IEC Aquisicao IEC Связь с IEC IEC Coupling
8 | CommS2K_C 8 | CommS2K_C 8 | CommS2K_C 8 | CommS2K_C 8 | CommS2K_C 8 | CommS2K_C
ETAT DE LA CONNECTION CONNECTION STATUS ESTADO CONEXIÓN ESTADO DA CONEXAO СТАТУС СОЕДИНЕНИЯ VERBINDUNG STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien OI CLIENT OI client link Enlace CLIENTE Conexao CLIENTE Связь клиента OI client link
SPSPrf | SPSNoAlLogArc ;
DPSPrf | DPSNoAlLogArc ;
MPSPrf | MPSNoAlLogArc ;
SPCPrf | SPCNoAlLogArc ;
DPCPrf | DPCNoAlLogArc ;
MVPrf | MVNoAlLogArc ;
SetPointPrf | SPNoAlLogArc ;
CounterPrf | CTNoAlLogArc ;
Designation : #REF! Symbol : #REF!
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
This sheet is used to choose what are the default Menu Options for this Datalist
The goal is to allow only given Menu Options to a customer for example.
GE Menu: Menu Option Display in Datalist Menu
Show Datalist Yes
Hide Sheets Yes
Display Sheets Yes
Check Datalist consistency Yes
Set Default parameter Values Yes
Add or Modify a BCU, UCA2 IED or IEC 61850 IED Yes
Import PES Signal List Yes
Count SPARE Data Yes
Translate this Datalist Yes
About this Datalist Yes
CUSTOMER Menu: Menu Option Display in Datalist Menu
Show Datalist Yes
Display Sheets No
Check Datalist consistency No
Set Default parameter Values No
Add or Modify a BCU, UCA2 IED or IEC 61850 IED Yes
Import PES Signal List Yes
Count SPARE Data Yes
Translate this Datalist No
About this Datalist Yes
Designation : #REF! Symbol : #REF!
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
MiCOM C264 DESCRIPTION
Computer Name GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) Read Only
Gateway Port used (on gateway)
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number
Digital Inputs Board Slot
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number
Digital Outputs Board Slot
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
HIGH BREAK UNIT BOARD HBU20x
HBU Board Number
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL INPUT/OUTPUT BOARD CCU20x
DI/DO Board Number
DI/DO Board Slot
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
A 2 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
A 3 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
A 4 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
A 5 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
A 6 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
A 7 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
A 8 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARDS CCU20x
A 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARDS CCU20x
A 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARDS CCU20x
A 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARDS CCU20x
ANALOG INPUT BOARD AIU20x
Analog Input Board Number
Analog Input Board Slot
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE 6 ANALOG INPUT BOARD AIU20x
A 2 SPARE 6 ANALOG INPUT BOARD AIU20x
A 3 SPARE 6 ANALOG INPUT BOARD AIU20x
A 4 SPARE 6 ANALOG INPUT BOARD AIU20x
ANALOG INPUT BOARD AIU21x
Analog Input Board Number
Analog Input Board Slot
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE 6 ANALOG INPUT BOARD AIU21x
A 2 SPARE 6 ANALOG INPUT BOARD AIU21x
A 3 SPARE 6 ANALOG INPUT BOARD AIU21x
A 4 SPARE 6 ANALOG INPUT BOARD AIU21x
A 5 SPARE 6 ANALOG INPUT BOARD AIU21x
A 6 SPARE 6 ANALOG INPUT BOARD AIU21x
A 7 SPARE 6 ANALOG INPUT BOARD AIU21x
A 8 SPARE 6 ANALOG INPUT BOARD AIU21x
CT/VT ANALOG INPUT BOARD TMU2x0
CT/VT Board Number
CT/VT Board Slot
CT/VT Board Model
Nominal Current (1A/5A)
Nominal Voltage [1V … 500V]
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Va Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vb Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vc Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ia Mv0000Current A 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ib Mv0000Current A 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ic Mv0000Current A 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uab Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ubc Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uca Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Freq (Line) Mv000Freq Hz 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DV Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DF Mv000Freq Hz 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Dj Mv0000Current ° 6 CT/VT ANALOG INPUT BOARD TMU2x0
A P total (MW) Mv0000Power MW 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Q total (Mvar) Mv0000RePower Mvar 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Power Factor Mv000PowerF - 6 CT/VT ANALOG INPUT BOARD TMU2x0
DSP210 Board Number
DSP210 Board Slot
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 DSP210 BOARD
A 5 SPARE SPC NO 2 DSP210 BOARD
ANALOG OUTPUT BOARD AOU20x
Analog Output Board Number
Analog Output Board Slot
Iss. Customer Ref AO Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE 13 ANALOG OUTPUT BOARD AOU20x
A 2 SPARE 13 ANALOG OUTPUT BOARD AOU20x
A 3 SPARE 13 ANALOG OUTPUT BOARD AOU20x
A 4 SPARE 13 ANALOG OUTPUT BOARD AOU20x
DIGITAL INFORMATION FROM IED IED name
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
DIGITAL INFORMATION TO IED IED name
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
ANALOG INFORMATION FROM IED IED name
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
ANALOG INFORMATION TO IED IED name
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name
A SPARE 13 ANALOG INFORMATION TO IED IED name
COUNTER INFORMATION FROM IED IED name
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF!
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
MiCOM C364 DESCRIPTION
Computer Name Auto generated
Redundant Computer Read Only
Gateway Port used (on gateway)
DIGITAL INFORMATION FROM IED IED name
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
DIGITAL INFORMATION TO IED IED name
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
ANALOG INFORMATION FROM IED IED name
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
ANALOG INFORMATION TO IED IED name
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name
A SPARE 13 ANALOG INFORMATION TO IED IED name
COUNTER INFORMATION FROM IED IED name
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED name
A SPARE Yes 39 COUNTER INFORMATION FROM IED name
A SPARE Yes 39 COUNTER INFORMATION FROM IED name
A SPARE Yes 39 COUNTER INFORMATION FROM IED name
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C364 DI GROUPS
A 2 SPARE SPS None No 1 C364 DI GROUPS
A 3 SPARE SPS None No 1 C364 DI GROUPS
A 4 SPARE SPS None No 1 C364 DI GROUPS
A 5 SPARE SPS None No 1 C364 DI GROUPS
A 6 SPARE SPS None No 1 C364 DI GROUPS
A 7 SPARE SPS None No 1 C364 DI GROUPS
A 8 SPARE SPS None No 1 C364 DI GROUPS
A 9 SPARE SPS None No 1 C364 DI GROUPS
A 10 SPARE SPS None No 1 C364 DI GROUPS
A 11 SPARE SPS None No 1 C364 DI GROUPS
A 12 SPARE SPS None No 1 C364 DI GROUPS
A 13 SPARE SPS None No 1 C364 DI GROUPS
A 14 SPARE SPS None No 1 C364 DI GROUPS
A 15 SPARE SPS None No 1 C364 DI GROUPS
A 16 SPARE SPS None No 1 C364 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.0.0
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : Site Name
This sheet is to be used to indicate the cells/columns that are : GE Reserved
- P : present in all corresponding sheets but the contents shall not be used by automatic tools Auto generated
- U : present in all corresponding sheets and shall be used by automatic tools Read Only
- A : not present in corresponding sheets
- PH : hide in all corresponding sheets but the contents shall not be used by automatic tools
- UH : hide in all corresponding sheets and shall be used by automatic tools
MiCOM CXXX DESCRIPTION
DIGITAL INPUT BOARD DIU2xx
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U
DIGITAL OUTPUT BOARD DOU20x
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U A U U U U U
HIGH BREAK UNIT BOARD HBU20x
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U A U U U U U
DIGITAL INPUT/OUTPUT BOARD CCU20x
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U A U U U U U
ANALOG INPUT BOARD AIU20x
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U U U U U U U
ANALOG INPUT BOARD AIU21x
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U U U U U U U
CT/VT ANALOG INPUT BOARD TMU2x0
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U A U U U U U U U U U U U U U U U U U U U A U A U U U U U U U U U U U
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U A U U U U U
ANALOG OUTPUT BOARD AOU20x
Iss. Customer Ref AO Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A A A U U A U U A U U U U U
DIGITAL INFORMATION FROM IED
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U
DIGITAL INFORMATION TO IED
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U A U U U U U
ANALOG INFORMATION FROM IED
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U U U U U U U
ANALOG INFORMATION TO IED
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A A A U U A U U A U U U U U
COUNTER INFORMATION FROM IED
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A A A U U U U U A U U U U U
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U A U U U U U
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U U U U U U U
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A A A U U U U U A U U U U U
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A A A U U A U U A U U U U U
SUBSTATION DATA DESCRIPTION
SUBSTATION DI GROUPS
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Managed by Computer Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U
SYSTEM INFORMATION DATA DESCRIPTION
SYSTEM INFORMATION SERVER OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U A U U U U A U U U A A U U U
SYSTEM INFORMATION CLIENT OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U A U U U U A U U U A A U U U
SYSTEM INFORMATION MiCOM C264
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U U U U U U A U U U A A U U U
SYSTEM INFORMATION MiCOM C364
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U U U U U U A U U U A A U U U
SYSTEM INFORMATION UCA2 IED
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U U U U U U A U U U A A U U U
SYSTEM INFORMATION GATEWAY
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U A U U U U A U U U A A U U U
SYSTEM INFORMATION IEC 61850
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U U U U U U A U U U A A U U U
SYSTEM INFORMATION BAY OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U A U U U U A U U U A A U U U
Designation : #REF! Symbol : #REF! BABA
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
This sheet is used to set default parameter value for each data. GE Reserved
- set the Old parameter value to change in the "Old Value" line Auto generated
- set the New parameter value used to overwrite Old one in the "New Value" line Read Only
- It is possible to use regular expressions as 'Old value' to locate data by using:
? Any single character.
* Zero or more characters.
# Any single digit (0-9).
[charlist] Any single character in charlist.
[!charlist] Any single character not in charlist.
- A group of one or more characters (charlist) enclosed in brackets ([ ]) can be used to
match any single character in string and can include almost any character code,
including digits.
- Note: To match the special characters left bracket ([), question mark (?), number sign (#),
and asterisk (*), enclose them in brackets. The right bracket (]) can't be used within a group
to match itself, but it can be used outside a group as an individual character.
- By using a hyphen (-) to separate the upper and lower bounds of the range, charlist can
specify a range of characters. For example, [A-Z] results in a match if the corresponding
character position in string contains any uppercase letters in the range A-Z. Multiple ranges
'aBBBa' is like 'a*a'
'F' is like '[A-Z]'
'F' is NOT like '[!A-Z]'
'a2a' is like 'a#a'
'aM5b' is like 'a[L-P]#[!c-e]'
'BAT123khg' is like 'B?T*'
'CAT123khg' is NOT like 'B?T*'
MiCOM CXXX DESCRIPTION
DIGITAL INPUT BOARD DIU2xx
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
DIGITAL OUTPUT BOARD DOU20x
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
HIGH BREAK UNIT BOARD HBU20x
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
DIGITAL INPUT/OUTPUT BOARD CCU20x
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
ANALOG INPUT BOARD AIU20x
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
ANALOG INPUT BOARD AIU21x
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
CT/VT ANALOG INPUT BOARD TMU2x0
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
ANALOG OUTPUT BOARD AOU20x
Iss. Customer Ref AO Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
DIGITAL INFORMATION FROM IED
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
DIGITAL INFORMATION TO IED
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
ANALOG INFORMATION FROM IED
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
ANALOG INFORMATION TO IED
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
COUNTER INFORMATION FROM IED
Iss. Customer Ref IED Counter Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
SUBSTATION DATA DESCRIPTION
SUBSTATION DI GROUPS
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Managed by Computer Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
SYSTEM INFORMATION DATA DESCRIPTION
SYSTEM INFORMATION SERVER OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
SYSTEM INFORMATION CLIENT OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
SYSTEM INFORMATION MiCOM C264
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
SYSTEM INFORMATION MiCOM C364
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
SYSTEM INFORMATION UCA2 IED
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
SYSTEM INFORMATION GATEWAY
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
SYSTEM INFORMATION IEC 61850
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
SYSTEM INFORMATION BAY OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Designation : #REF! Symbol : #REF!
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
This sheet is to be used to indicate the cells/columns for which the contents shall be copied to a new DataList release. GE Reserved
The possible values are : Auto generated
- N : do not copy in any case Read Only
- C : copy in any case (when the line is significant)
- E : copy only if the cell within new release is empty
MiCOM CXXX DESCRIPTION
DIGITAL INPUT BOARD DIU2xx
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
DIGITAL OUTPUT BOARD DOU20x
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E N E N E E E E E N E E E E E
HIGH BREAK UNIT BOARD HBU20x
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E N E N E E E E E N E E E E E
DIGITAL INPUT/OUTPUT BOARD CCU20x
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E N E N E E E E E N E E E E E
ANALOG INPUT BOARD AIU20x
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N E N E E E E E E E E E E E
ANALOG INPUT BOARD AIU21x
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N E N E E E E E E E E E E E
CT/VT ANALOG INPUT BOARD TMU2x0
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E N E N E E E E E E E E E E E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E N E N E E E E E N E E E E E
ANALOG OUTPUT BOARD AOU20x
Iss. Customer Ref AO Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E N N N E E N E E N E E E E E
DIGITAL INFORMATION FROM IED
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
DIGITAL INFORMATION TO IED
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N E N E E E E E N E E E E E
ANALOG INFORMATION FROM IED
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N E N E E E E E E E E E E E
ANALOG INFORMATION TO IED
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N N N E E N E E N E E E E E
COUNTER INFORMATION FROM IED
Iss. Customer Ref IED Counter Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N N N E E E E E N E E E E E
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N E N E E E E E N E E E E E
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N E N E E E E E E E E E E E
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N N N E E E E E N E E E E E
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N N N E E N E E N E E E E E
SUBSTATION DATA DESCRIPTION
SUBSTATION DI GROUPS
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Managed by Computer Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
SYSTEM INFORMATION DATA DESCRIPTION
SYSTEM INFORMATION SERVER OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E N E E E E N E E E N N E E E
SYSTEM INFORMATION CLIENT OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E N E E E E N E E E N N E E E
SYSTEM INFORMATION MiCOM C264
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E E E E E E N E E E N N E E E
SYSTEM INFORMATION MiCOM C364
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E E E E E E N E E E N N E E E
SYSTEM INFORMATION UCA2 IED
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E E E E E E N E E E N N E E E
SYSTEM INFORMATION GATEWAY
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E N E E E E N E E E N N E E E
SYSTEM INFORMATION IEC 61850
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E E E E E E N E E E N N E E E
SYSTEM INFORMATION BAY OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E N E E E E N E E E N N E E E
Designation : #REF! Symbol : #REF!
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
This sheet indicates the cells/columns used for building comparison criteria. GE Reserved
The possible values are : Auto generated
- P : present in all corresponding sheets but the contents shall not be used to build comparison criteria Read Only
- U : present in all corresponding sheets and shall be used to build comparison criteria
- A : not present in corresponding sheets
MiCOM CXXX DESCRIPTION
DIGITAL INPUT BOARD DIU2xx
Description Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case Digital Inputs Board Number Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
DIGITAL OUTPUT BOARD DOU20x
Description Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case Digital Outputs Board Number Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
HIGH BREAK UNIT BOARD HBU20x
Description Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case Digital Outputs Board Number Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
DIGITAL INPUT/OUTPUT BOARD CCU20x
Description Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case DI/DO Board Number Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
Description Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case DI/DO Board Number Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
ANALOG INPUT BOARD AIU20x
Description Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Use this Matrix Case Analog Input Board Number Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
ANALOG INPUT BOARD AIU21x
Description Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Use this Matrix Case Analog Input Board Number Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
CT/VT ANALOG INPUT BOARD TMU2x0
Description Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Use this Matrix Case CT/VT Board Number Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P P A U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
P U P P P P A P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
P P P P P P A P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
Description Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case DSP210 Board Number Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
ANALOG OUTPUT BOARD AOU20x
Description Iss. Customer Ref AO Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case Analog Output Board Number Issue Panel Number Tag Number Slot Channel Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P A A A P P A P P A P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P A A A P P A P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A A A P P A P P A P P P P P
DIGITAL INFORMATION FROM IED
Description Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case IED name Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P U U U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
DIGITAL INFORMATION TO IED
Description Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case IED name Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
ANALOG INFORMATION FROM IED
Description Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Use this Matrix Case IED name Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
ANALOG INFORMATION TO IED
Description Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case IED name Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P U U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P P U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P P P U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P P P U U U P U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P P P U U U U P P U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P P P U U U U U U P P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P P P U U U P P P U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P P P U U U U P P P P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P U U P P P U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P U U U U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P P P P P P P P P P P P P P P P P P A A A P P A P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A A A P P A P P A P P P P P
COUNTER INFORMATION FROM IED
Description Iss. Customer Ref IED Counter Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Use this Matrix Case IED name Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P U U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P P U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P P P U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P P P U U U P U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P P P U U U U P P U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P P P U U U U U U P P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P P P U U U P P P U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P P P U U U U P P P P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P U U P P P U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U P P P P U U U U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P P P P P P P P P P P P P P P P P P P A A A P P P P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A A A P P P P P A P P P P P
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U A P P P P U U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
P A P P P U U P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
P A P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U A P P P P P U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
P A P P P U P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
P A P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U A P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
P A P P P U P P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
P A P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Use this Matrix Case Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U A P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
P A P P P U P P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
P A P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Use this Matrix Case Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U A P P P P P U U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P P U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P P P U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P P P U U U P U U U P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P P P U U U U P P U P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P P P U U U U U U P P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P P P U U U P P P U P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P P P U U U U P P P P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P U U P P P U U U U P P P P P P P P P P A A A P P P P P A P P P P P
P A P P P U P P P P P P P P P P P P P P P P P P P P A A A P P P P P A P P P P P
P A P P P P P P P P P P P P P P P P P P P P P P P P A A A P P P P P A P P P P P
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U A P P P P P U U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P P U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P P P U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P P P U U U P U U U P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P P P U U U U P P U P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P P P U U U U U U P P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P P P U U U P P P U P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P P P U U U U P P P P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P U U P P P U U U U P P P P P P P P P P A A A P P A P P A P P P P P
P A P P P U P P P P P P P P P P P P P P P P P P P P A A A P P A P P A P P P P P
P A P P P P P P P P P P P P P P P P P P P P P P P P A A A P P A P P A P P P P P
SUBSTATION DATA DESCRIPTION
SUBSTATION DI GROUPS
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Managed by Computer Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U A P P P P U U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
P A P P P U U P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
P A P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
SYSTEM INFORMATION DATA DESCRIPTION
SYSTEM INFORMATION SERVER OI
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case SERVER OI Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
SYSTEM INFORMATION CLIENT OI
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case CLIENT OI Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
SYSTEM INFORMATION MiCOM C264
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case MiCOM C264 Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
SYSTEM INFORMATION MiCOM C364
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case MiCOM C364 Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
SYSTEM INFORMATION UCA2 IED
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case UCA2 IED Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
SYSTEM INFORMATION GATEWAY
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case GATEWAY Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
SYSTEM INFORMATION IEC 61850
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case IEC 61850 Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
SYSTEM INFORMATION BAY OI
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case BAY OI Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
Mapping Language English Français English Spanish Português Brasil Russian German
SHEET : Customer Front Page SHEET : Page de Garde Client SHEET : Customer Front Page SHEET : Página principal Cliente SHEET : Página Inicial Cliente SHEET : Первая Страница Клиента SHEET : Customer Front Page
SHEET : GE Front Page SHEET : Page de Garde GE SHEET : GE Front Page SHEET : Página principal GE SHEET : Pagina Inicial GE SHEET : Первая Страница GE SHEET : GE Front Page
ISSUE REVISION ISSUE REVISION REVISÃO ВЕРСИЯ VERSION
DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPCION DESCRIÇÃO ОПИСАНИЕ BESCHREIBUNG
DATE DATE DATE FECHA DATA ДАТА DATUM
CUSTOMER CLIENT CUSTOMER CLIENTE Cliente ЗАКАЗЧИК KUNDE
GE GE GE GE GE GE GE
CUSTOMER CLIENT CUSTOMER CLIENTE Cliente ЗАКАЗЧИК KUNDE
CONTRACT No. CONTRAT N° CONTRACT No. NO. de CONTRATO Num. do CONTRATO КОНТРАКТ No. AUFTRAG Nr.
ORDER No. Commande N° ORDER No. No. De ORDEN Num. Da Ordem ЗАКАЗ No. BESTELL Nr.
PROJECT: PROJET: PROJECT: PROYECTO: PROJETO: ПРОЕКТ: PROJEKT:
Project Name Nom du Projet Project Name Nombre del proyecto Nome do projeto Название проекта : Projektname
SITE: SITE: SITE: SITIO: OBRA: ОБЪЕКТ: Anlage:
DOCUMENT NUMBER: Numéro de Document : DOCUMENT NUMBER: DOCUMENTO NUMERO: DOCUMENTO Número: НОМЕР ДОКУМЕНТА: Dokument Nummer:
Site Name Nom du Site Site Name Nombre del sitio Nome da obra Название объекта Anlagen Name
xyz-SC-DTL xyz-SC-DTL xyz-SC-DTL xyz-SC-DTL xez-SC-DTL xyz-SC-DTL xyz-SC-DTL
DATE DATE DATE FECHA DATA ДАТА DATUM
SIGNATURE SIGNATURE SIGNATURE FIRMA Assinatura ПОДПИСЬ UNTERSCHRIFT
DOCUMENT TITLE SUBSTATION CONTROL SYSTEM DATA LIST Titre du document LISTE DE DONNEES DU SYSTEME DE Contrôle DE SOUS-STATION DOCUMENT TITLE SUBSTATION CONTROL SYSTEM DATA LIST TITULO DEL DOCUMENTO LISTADO DE DATOS DEL SISTEMA DE CONTROL DE LA SUBESTACION Título DO DOCUMENTO Lista de DADOS DO Sistema de CONTROLE DA SUBESTAÇÃO Заголовок документа ТАБЛИЦА СИГНАЛОВ АСУ DOKUMENT TITEL LEITTECHNIKSYSTEM DatumNPUNKTLISTE
DRAWN CREE DRAWN DRAWN Desenho МНЕМОСХЕМЫ ERSTELLT
DSAgile SUBSTATION CONTROL SYSTEM Data List DSAgile SYSTEME DE COMMANDE DE SOUS-STATION Liste de données DSAgile SUBSTATION CONTROL SYSTEM Data List DSAgile SISTEMA DE CONTROL DE SUBESTACIONES Data List DSAgile Sistema de CONTROLE de SUBESTAÇÕES Lista de Dados DSAgile АВТОМАТИЗИРОВАННАЯ СИСТЕМА УПРАВЛЕНИЯ Таблица Сигналов DSAgile LEITTECHNIK Data List
CHECKED VERIFIE CHECKED REVISADO REVISADO ПРОВЕРЕНО GEPRÜFT
APPROVED APPROUVE APPROVED APROBADO APROVADO УТВЕРЖДЕНО BESTÄTIGT
ISSUED BY: EDITE PAR: ISSUED BY: EMITIDO POR: EMITIDO POR: Выпущено: ERSTELLT VON:
SIZE TAILLE SIZE TAMAÑO TAMANHO РАЗМЕР Größe
PAGES PAGES PAGES PAGINAS PÁGINAS СТРАНИЦЫ SEITEN
ISSUE REVISION ISSUE REVISION REVISÃO ВЕРСИЯ VERSION
A3 A3 A3 A3 A3 A3 A3
GE Parc Eurêka 81, rue Euclide 34000 MONTPELLIER GE Parc Eurêka 81, rue Euclide 34000 MONTPELLIER GE Parc Eurêka 81, rue Euclide 34000 MONTPELLIER GE Parc Eurêka 81, rue Euclide 34000 MONTPELLIER GE Parc Eurêka 81, rue Euclide 34000 MONTPELLIER GE Parc Eurêka 81, rue Euclide 34000 MONTPELLIER GE Parc Eurêka 81, rue Euclide 34000 MONTPELLIER
ESTABLISHED ETABLI PAR ESTABLISHED ESTABLISHED ESTABLISHED ESTABLISHED ESTABLISHED
SHEET : History SHEET : Journal SHEET : History SHEET : Historia SHEET : Histórico SHEET : История SHEET : History
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
PACIDL-A PACIDL-A PACIDL-A PACIDL-A PACIDL-A PACIDL-A PACIDL-A
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN DATA DEBUT DES DONNEES BEGIN DATA INICIO DE DATOS INICIO DOS DADOS НАЧАЛО ДАННЫХ BEGIN DATA
Issue Révision Issue Revisión Revisão Версия Version
Date Date Date Fecha Data Дата Datum
Author Auteur Author Autor Autor Автор Autor
Company Compagnie Company Compañia Companhia Компания Firma
Modifications Modifications Modifications Modificaciones Modificações Изменения Änderungen
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : Equipments SHEET : Equipements SHEET : Equipments SHEET : Equipos SHEET : Equipamentos SHEET : Оборудование SHEET : Equipments
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
EQUIPMENT LIST LISTE DES EQUIPEMENTS EQUIPMENT LIST LISTA DE EQUIPOS Lista de Equipamentos СПИСОК ОБОРУДОВАНИЯ EQUIPMENT LISTE
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Usual Communication Communication usuelle Usual Communication Habitual Comunicación Comunicação usual Передача данных Ublichen Kommunikation
Legacy T104 Master Legacy T104 Maître Legacy T104 Master Legacy T104 Master Legacy T104 Master Legacy T104 Master Legacy T104 Master
Legacy T101 Master Legacy T101 Maître Legacy T101 Master Legacy T101 Master Legacy T101 Master Legacy T101 Master Legacy T101 Master
Boards Cartes Boards Tarjetas Placa Платы Karten
Issue Révision Issue Revisión Revisão Версия Version
NAME NOM NAME NOMBRE NOME ИМЯ NAME
DESCRIPTION (LONG NAME) DESCRIPTION (NOM LONG) DESCRIPTION (LONG NAME) DESCRIPCION (NOMBRE COMPLETO) Descrição (Nome COMPLETO) ОПИСАНИЕ (ДЛИННОЕ ИМЯ) Beschreibung(Long Name)
LINK COMMUNICATION LINK VINCULO VINCULO СВЯЗЬ LINK
REDUNDANT REDONDANCE REDUNDANT REDUNDANTE REDUNDANTE С РЕЗЕРВИРОВАНИЕМ REDUNDANT
TYPE TYPE TYPE TIPO TIPO МОДЕЛЬ TYPE
Substation Name Nom de la Sous-station Substation Name Nombre de subestación Nome do Substação Имя подстанции Stationsname:
Bay mimic Tranche mimic Bay mimic Mímico de bahía Mímico do Painel Мнемосхема Ячейки Bay mimic
Synchronisation mode MODE DE SYNCHRONISATION Synchronisation mode Modo de sincronización Modo de Sincronização Режим синхронизации Synchronisation mode
Network Name NOM DU RESEAU Network Name Nombre de red Nome da rede Сетевое Имя Netzwerk Name
TCP/IP (IEC) Address Adresse TCP/IP (IEC) TCP/IP (IEC) Address Dirección TCP/IP (IEC) Endereço TCP/IP (IEC) TCP/IP (IEC) Адрес TCP/IP (IEC) Addresse
Port 1 Port 1 Port 1 Puerto 1 Porta 1 Порт 1 Port 1
Protocol Name Nom de protocole Protocol Name Nombre de Protocolo Nome do Protocolo ИМЯ Протокола Protocol Name
Port 2 Port 2 Port 2 Puerto 2 Porta 2 Порт 2 Port 2
Protocol Name Nom de protocole Protocol Name Nombre de Protocolo Nome do Protocolo ИМЯ Протокола Protocol Name
Port 3 Port 3 Port 3 Puerto 3 Porta 3 Порт 3 Port 3
Protocol Name Nom de protocole Protocol Name Nombre de Protocolo Nome do Protocolo ИМЯ Протокола Protocol Name
Port 4 Port 4 Port 4 Puerto 4 Porta 4 Порт 4 Port 4
Protocol Name Nom de protocole Protocol Name Nombre de Protocolo Nome do Protocolo ИМЯ Протокола Protocol Name
Id1 T104M (+ IED Addr) Id1 T104M (+ IED Adr) Id1 T104M (+ IED Addr) Id1 T104M (Direcc + IED) Id1 T104M (Direcc + IED) Id1 T104M (+ адрес IED) Id1 T104M (+ IED Addr)
Id2 T104M (+ IED Addr) Id2 T104M (+ IED Adr) Id2 T104M (+ IED Addr) Id2 T104M (Direcc + IED) Id2 T104M (Direcc + IED) Id2 T104M (+ адрес IED) Id2 T104M (+ IED Addr)
Id3 T104M (+ IED Addr) Id3 T104M (+ IED Adr) Id3 T104M (+ IED Addr) Id3 T104M (Direcc + IED) Id3 T104M (Direcc + IED) Id3 T104M (+ адрес IED) Id3 T104M (+ IED Addr)
Id4 T104M (+ IED Addr) Id4 T104M (+ IED Adr) Id4 T104M (+ IED Addr) Id4 T104M (Direcc + IED) Id4 T104M (Direcc + IED) Id4 T104M (+ адрес IED) Id4 T104M (+ IED Addr)
Id1 T101M (+ IED Addr) Id1 T101M (+ IED Adr) Id1 T101M (+ IED Addr) Id1 T101M (Direcc + IED) Id1 T101M (Direcc + IED) Id1 T101M (+ адрес IED) Id1 T101M (+ IED Addr)
Id2 T101M (+ IED Addr) Id2 T101M (+ IED Adr) Id2 T101M (+ IED Addr) Id2 T101M (Direcc + IED) Id2 T101M (Direcc + IED) Id2 T101M (+ адрес IED) Id2 T101M (+ IED Addr)
Id3 T101M (+ IED Addr) Id3 T101M (+ IED Adr) Id3 T101M (+ IED Addr) Id3 T101M (Direcc + IED) Id3 T101M (Direcc + IED) Id3 T101M (+ адрес IED) Id3 T101M (+ IED Addr)
Id4 T101M (+ IED Addr) Id4 T101M (+ IED Adr) Id4 T101M (+ IED Addr) Id4 T101M (Direcc + IED) Id4 T101M (Direcc + IED) Id4 T101M (+ адрес IED) Id4 T101M (+ IED Addr)
IEC61850 Protocol Id Id Protocole IEC61850 IEC61850 Protocol Id IEC61850 Protocolo Id IEC61850 Protocolo Id IEC61850 Протокола Id IEC61850 Protocol Id
OPC Protocol Id Id Protocole OPC OPC Protocol Id OPC Protocolo Id OPC Protocolo Id OPC Протокола Id OPC Protocol Id
DIU2xx DIU2xx DIU2xx DIU2xx DIU2xx DIU2xx DIU2xx
CCU20x CCU20x CCU20x CCU20x CCU20x CCU20x CCU20x
DOU20x DOU20x DOU20x DOU20x DOU20x DOU20x DOU20x
HBU20x HBU20x HBU20x HBU20x HBU20x HBU20x HBU20x
AIU20x AIU20x AIU20x AIU20x AIU20x AIU20x AIU20x
AIU21x AIU21x AIU21x AIU21x AIU21x AIU21x AIU21x
TMU2x0 TMU2x0 TMU2x0 TMU2x0 TMU2x0 TMU2x0 TMU2x0
DSP210 DSP210 DSP210 DSP210 DSP210 DSP210 DSP210
AOU20x AOU20x AOU20x AOU20x AOU20x AOU20x AOU20x
SWx SWx SWx SWx SWx SWx SWx
Extension Racks Racks d'Extension Extension Racks Extensión bastidores Extensão Racks продление стеллажи Erweiterung Racks
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Template Modèle Template Plantilla Panilha Образец Template
Sheet Name Nom de la Feuille Sheet Name Nombre de hoja Nome da Planilha Имя Страницы Sheet Name
DIU32 DIU32 DIU32 DIU32 DIU32 DIU32 DIU32
SUMMARY RESUME SUMMARY RESUMEN RESUMO КРАТКИЙ ZUSAMMENFASSUNG
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : Computers Arrangement SHEET : Arrangement des Calculateurs SHEET : Computers Arrangement SHEET : Computadors Arrangement SHEET : Arranjo dos Computadores SHEET : Компановка контроллеров SHEET : Computers Arrangement
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
MiCOM COMPUTERS HARDWARE DESCRIPTION DESCRIPTION MATERIELLE DES CALCULATEURS MICOM MiCOM COMPUTERS HARDWARE DESCRIPTION DESCRIPCION DEL HARDWARE COMPUTADOR MiCOM Descrição DO HARDWARE COMPUTADOR MiCOM ОПИСАНИЕ УСТРОЙСТВА КОНТРОЛЛЕРОВ MiCOM MiCOM COMPUTERS HARDWARE BESCHREIBUNG
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Auto generated Génération automatique Auto generated Auto generado Auto Geração Автоматически сгенерировано Auto generated
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
ERROR ERREUR ERROR ERROR ERRO ОШИБКА FEHLER
C264 Ext Rack C264 Rack d'Ext. C264 Ext Rack C264 Ext Rack C264 Ext Rack C264 Ext Rack C264 Ext Rack
C264C Ext Rack C264C Rack d'Ext. C264C Ext Rack C264C Ext Rack C264C Ext Rack C264C Ext Rack C264C Ext Rack
Computer type (C264/C264C): Type de Calculateur (C264/C264C): Computer type (C264/C264C): Typo de computador (C264/C264C): Tipo de computador (C264/C264C): Тип контроллера (C264/C264C): Computer type (C264/C264C):
back face Face arriere back face panel posterior Painel Traseiro Тыльная сторона back face
APPLICABLE PRINCIPAL APPLICABLE APLICABLE Aplicável ПРИМЕНЯЕМЫЙ APPLICABLE
REDUNDANT REDONDANCE REDUNDANT REDUNDANTE REDUNDANTE С РЕЗЕРВИРОВАНИЕМ REDUNDANT
PANEL ECRAN PANEL PANEL PAINEL ПАНЕЛЬ PANEL
COMMENTS COMMENTAIRES COMMENTS COMENTARIOS COMENTÃRIOS КОММЕНТАРИИ KOMMENTAR
Port 1 Port 1 Port 1 Puerto 1 Porta 1 Порт 1 Port 1
Port 2 Port 2 Port 2 Puerto 2 Porta 2 Порт 2 Port 2
Port 3 Port 3 Port 3 Puerto 3 Porta 3 Порт 3 Port 3
Port 4 Port 4 Port 4 Puerto 4 Porta 4 Порт 4 Port 4
front slot number: Numéro de position devant: front slot number: número de slot frontal: Número do Slot Frontal: номер слота на фронтальной стороне: front slot number:
COMPUTER NAME NOM DU CALCULATEUR COMPUTER NAME NOMBRE DEL COMPUTADOR Nome do Computador ИМЯ КОНТРОЛЛЕРА COMPUTER NAME
NUMBER NUMERO NUMBER NUMERO NUMERO НОМЕР ANZAHL
BIU240 Port 1 BIU240 Port 1 BIU240 Port 1 BIU240 Puerto 1 BIU240 Porta 1 BIU240 Порт 1 BIU240 Port 1
BIU240 Port 2 BIU240 Port 2 BIU240 Port 2 BIU240 Puerto 2 BIU240 Porta 2 BIU240 Порт 2 BIU240 Port 2
CPU Port 1 CPU Port 1 CPU Port 1 CPU Puerto 1 CPU Porta 1 CPU Портt 1 CPU Port 1
CPU Port 2 CPU Port 2 CPU Port 2 CPU Puerto 2 CPU Porta 2 CPU Порт 2 CPU Port 2
back slot number: Numéro de position arrière: back slot number: número de slot posterior: número de Slot posterior: номер слота на тыльной стороне: back slot number:
Protocol Type Type de Protocole Protocol Type Tipo de protocolo Tipo de Protocolo Тип протокола Protocol Type
CPU 260 + COMMUNICATION CPU 260 + COMMUNICATION CPU 260 + COMMUNICATION CPU 260 + COMUNICACION CPU 260 + COMUNICAÇÃO CPU 260 + ЛИНИИ СВЯЗИ CPU 260 + COMMUNICATION
BIU 241 BIU 241 BIU 241 BIU 241 BIU 241 BIU 241 BIU 241
Baud Rate Vitesse de la communication (en Baud) Baud Rate Bauidos Baud Rate Скорость в бодах Baud Rate
RS Type RS Type RS Type Tipo de RS Tipo de RS Тип RS RS Type
Parity Parité Parity Paridad Paridade Четность Parity
Number Stop bits Nombre de bits de stop Number Stop bits Número de bits de paro Número de bits de paro Number Stop bits Anzahl Stop bits
Number bits Nombre de bits Number bits Número de bits Número de bits Number bits Anzahl bits
Rx Management Gestion de RX Rx Management Administración de Rx Administração de Rx Управление Rx Rx Management
Tx Management Gestion de TX Tx Management Administración de Tx Administração de Tx Управление Tx Tx Management
CTS wired CTS Câblé CTS wired CTS cableadas CTS Linkados CTS wired CTS wired
DTS wired Câblage de DTS DTS wired DTS cableadas DTS Linkados DTS wired DTS wired
CD wired Câblage de CD CD wired CD cableadas CD Linkados CD wired CD wired
logical number: Numéro logique: logical number: número lógico: número lógico: логический номер: logical number:
DCR wired Câblage de DCR DCR wired DCR cableadas DCR Linkados DCR wired DCR wired
CPU 270 + COMMUNICATION CPU 270 + COMMUNICATION CPU 270 + COMMUNICATION CPU 270 + COMUNICACION CPU 270 + COMUNICAÇÃO CPU 270 + ЛИНИИ СВЯЗИ CPU 270 + COMMUNICATION
Computer type (C264/C264C): Type de Calculateur (C264/C264C): Computer type (C264/C264C): Typo de computador (C264/C264C): Tipo de computador (C264/C264C): Тип контроллера (C264/C264C): Computer type (C264/C264C):
C264C C264C C264C C264C C264C C264C C264C
back face Face arriere back face panel posterior Painel Traseiro Тыльная сторона back face
APPLICABLE PRINCIPAL APPLICABLE APLICABLE Aplicável ПРИМЕНЯЕМЫЙ APPLICABLE
REDUNDANT REDONDANCE REDUNDANT REDUNDANTE REDUNDANTE С РЕЗЕРВИРОВАНИЕМ REDUNDANT
PANEL ECRAN PANEL PANEL PAINEL ПАНЕЛЬ PANEL
COMMENTS COMMENTAIRES COMMENTS COMENTARIOS COMENTÃRIOS КОММЕНТАРИИ KOMMENTAR
Port 1 Port 1 Port 1 Puerto 1 Porta 1 Порт 1 Port 1
Port 2 Port 2 Port 2 Puerto 2 Porta 2 Порт 2 Port 2
Port 3 Port 3 Port 3 Puerto 3 Porta 3 Порт 3 Port 3
Port 4 Port 4 Port 4 Puerto 4 Porta 4 Порт 4 Port 4
front slot number: Numéro de position devant: front slot number: número de slot frontal: Número do Slot Frontal: номер слота на фронтальной стороне: front slot number:
COMPUTER NAME NOM DU CALCULATEUR COMPUTER NAME NOMBRE DEL COMPUTADOR Nome do Computador ИМЯ КОНТРОЛЛЕРА COMPUTER NAME
NUMBER NUMERO NUMBER NUMERO NUMERO НОМЕР ANZAHL
BIU240 Port 1 BIU240 Port 1 BIU240 Port 1 BIU240 Puerto 1 BIU240 Porta 1 BIU240 Порт 1 BIU240 Port 1
BIU240 Port 2 BIU240 Port 2 BIU240 Port 2 BIU240 Puerto 2 BIU240 Porta 2 BIU240 Порт 2 BIU240 Port 2
CPU Port 1 CPU Port 1 CPU Port 1 CPU Puerto 1 CPU Porta 1 CPU Портt 1 CPU Port 1
CPU Port 2 CPU Port 2 CPU Port 2 CPU Puerto 2 CPU Porta 2 CPU Порт 2 CPU Port 2
back slot number: Numéro de position arrière: back slot number: número de slot posterior: número de Slot posterior: номер слота на тыльной стороне: back slot number:
Protocol Type Type de Protocole Protocol Type Tipo de protocolo Tipo de Protocolo Тип протокола Protocol Type
TMU2x0 (slot 2/2) TMU2x0 (slot 2/2) TMU2x0 (slot 2/2) TMU2x0 (slot 2/2) TMU2x0 (Slot 2/2) TMU2x0 (слот 2/2) TMU2x0 (slot 2/2)
TMU2x0 (slot 1/2) TMU2x0 (slot 1/2) TMU2x0 (slot 1/2) TMU2x0 (slot 1/2) TMU2x0 (Slot 1/2) TMU2x0 (слот 1/2) TMU2x0 (slot 1/2)
CPU 260 + COMMUNICATION CPU 260 + COMMUNICATION CPU 260 + COMMUNICATION CPU 260 + COMUNICACION CPU 260 + COMUNICAÇÃO CPU 260 + ЛИНИИ СВЯЗИ CPU 260 + COMMUNICATION
BIU 241 BIU 241 BIU 241 BIU 241 BIU 241 BIU 241 BIU 241
Baud Rate Vitesse de la communication (en Baud) Baud Rate Bauidos Baud Rate Скорость в бодах Baud Rate
RS Type RS Type RS Type Tipo de RS Tipo de RS Тип RS RS Type
Parity Parité Parity Paridad Paridade Четность Parity
Number Stop bits Nombre de bits de stop Number Stop bits Número de bits de paro Número de bits de paro Number Stop bits Anzahl Stop bits
Number bits Nombre de bits Number bits Número de bits Número de bits Number bits Anzahl bits
Rx Management Gestion de RX Rx Management Administración de Rx Administração de Rx Управление Rx Rx Management
Tx Management Gestion de TX Tx Management Administración de Tx Administração de Tx Управление Tx Tx Management
CTS wired CTS Câblé CTS wired CTS cableadas CTS Linkados CTS wired CTS wired
DTS wired Câblage de DTS DTS wired DTS cableadas DTS Linkados DTS wired DTS wired
CD wired Câblage de CD CD wired CD cableadas CD Linkados CD wired CD wired
logical number: Numéro logique: logical number: número lógico: número lógico: логический номер: logical number:
DCR wired Câblage de DCR DCR wired DCR cableadas DCR Linkados DCR wired DCR wired
CPU 270 + COMMUNICATION CPU 270 + COMMUNICATION CPU 270 + COMMUNICATION CPU 270 + COMUNICACION CPU 270 + COMUNICAÇÃO CPU 270 + ЛИНИИ СВЯЗИ CPU 270 + COMMUNICATION
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : C264_Template SHEET : C264_Template SHEET : C264_Template SHEET : C264_Template SHEET : C264_Template SHEET : C264_Template SHEET : C264_Template
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
MiCOM C264 DESCRIPTION DESCRIPTION DU MiCOM C264 MiCOM C264 DESCRIPTION DESCRIPCION MiCOM C264 Descrição MiCOM C264 ОПИСАНИЕ MiCOM C264 MiCOM C264 BESCHREIBUNG
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
Computer Name Nom du Calculateur Computer Name Nombre de computador Nome do computador Имя контроллера Computer Name
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Redundant Computer Calculateur Redondant Redundant Computer Computador Redundante Computador Redundante Резервный компьютер Redundant Computer
Auto generated Génération automatique Auto generated Auto generado Auto Geração Автоматически сгенерировано Auto generated
Computer type (C264/C264C) Type de Calculateur (C264/C264C) Computer type (C264/C264C) Tipo de computador (C264/C264C) Tipo de computador (C264/C264C) Тип контроллера (C264/C264C) Computer type (C264/C264C)
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Gateway Passerelle Gateway UTR UTR Шлюз Gateway
Port used (on gateway) Ports utilisés (sur la passerelle) Port used (on gateway) Puerto utilizado (en UTR) Porta utilizada (em UTR) Используемый порт (на шлюз) benutzter Port (Gateway)
SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1
SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2
SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3
SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4
DIGITAL INPUT BOARD DIU32 Carte d'entrées numériques DIU32 DIGITAL INPUT BOARD DIU32 TARJETAS DE ENTRADAS DIGITALES DIU32 Etiquetas de Entradas Digitais DIU32 ПЛАТЫ DIU32 DIGITALE EINGANGSKARTE DIU32
DIGITAL INPUT BOARD DIU2xx Carte d'entrées numériques DIU2xx DIGITAL INPUT BOARD DIU2xx TARJETAS DE ENTRADAS DIGITALES DIU2xx Etiquetas de Entradas Digitais DIU2xx ПЛАТЫ DIU2xx DIGITALE EINGANGSKARTE DIU2xx
Digital Inputs Board Number Numéro de la carte d'entrées numériques Digital Inputs Board Number Tarjeta de entradas digitales Número Etiqueta de Entradas digitais Número Номер платы DI Digital Inputs Board Number
Digital Inputs Board Slot Position de la carte d'entrées numériques Digital Inputs Board Slot Tarjeta de entradas digitales Slot Etiqueta de Entradas digitais Slot Слот платы DI Digital Inputs Board Slot
Digital Inputs Extension Rack Number Numéro rack d'extension de la carte d'entrées numériques Digital Inputs Extension Rack Number Tarjeta de entradas digitales Extensión Rack Número Etiqueta de Entradas digitais Extensão Rack Número продлению стойки Количество DI Digital Inputs Extension Rack Number
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
DI Reference Référence DI DI Reference DI Referencia DI Referência Ссылка DI DI Referenz
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels / States Libellés/Etats Labels / States Etiquetas/Estados Etiquetas/Estados Метки / Состояния Labels / States
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Groups Groupes Groups Grupos Grupos Группы Gruppen
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Slot Position Slot Slot Slot Слот Slot
Channel Voie Channel Canal Canal Канал Channel
Function Fonction Function Función Função Функция Function
Type (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Simple/DPS=Double/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple) Tipo (SPS=Sencilla/DPS=Dual/MPS=Multiple) Tipo (SPS=Simples/DPS=Duplo/MPS=Múltiplo) Тип (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 Multiple : label d'état (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 Multiple : Texto (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 Múltiplo : Texto (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 Множественный: Обозначение (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique = 01 Multiple : Numéro d'état (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 Multiple : Número de estado (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 Múltiplo : Número de estado (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 Множественный : Состояние Number (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
Computers Groups (separator ";") Groupes de calculateur (séparateur ";") Computers Groups (separator ";") Grupos de Computadoras (separador ";") Grupos de Computadores (separador ";") Группы контроллеров (разделитель ";") Computers Gruppen (separator ";")
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
LED LED LED LED LED индикатор LED
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Is a xPC Feedback Est un retour de position xPC Is a xPC Feedback Es una xPC de retroalimentación É FeedBack de xPC Присутствует xPC обратная связь Is a xPC Feedback
Acts on xPC Acté sur xPC Acts on xPC Actúa en xPC Atua em xPC Действует на с xPC Acts on xPC
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
DIGITAL OUTPUT BOARD DOU20x Carte de sorties numériques DOU20x DIGITAL OUTPUT BOARD DOU20x TARJETAS DIGITALES SALIDAS DOU20x Placas de Saídas Digitais DOU20x ПЛАТЫ DOU20x DIGITALE AUSGANGSKARTE DOU20x
Digital Outputs Board Number Numéro de la carte de sorties numériques Digital Outputs Board Number Número de tarjeta de salidas digitales Número de Etiqueta de saidas digitais Номер платы DO Digitale Ausgangskarte Nummer
Digital Outputs Board Slot Position de la carte de sorties numériques Digital Outputs Board Slot Slot de trajeta de salidas digitales Slot de trajeta de saidas digitais Слот платы DO Digitale Ausgangskarte Steckplatz
Digital Outputs Extension Rack Number Numéro rack d'extension de la carte de sorties numériques Digital Outputs Extension Rack Number Tarjeta de salidas digitales Extensión Rack Número Etiqueta de saidas digitais Extensão Rack Número продлению стойки Количество DO Digitale Ausgangskarte Extension Rack Nummer
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
DO Reference Référence DO DO Reference Referencia DO Referência DO Ссылка DO DO Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Control Contrôle Local Local Control Control Local Controle Local местного контроля Local Control
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Slot Position Slot Slot Slot Слот Slot
Channel Voie Channel Canal Canal Канал Channel
Function Fonction Function Función Função Функция Function
Type (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Simple/DPC=Double/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch) Tipo (SPC=Sencilla/DPC=Dual/DS=Dual Switch) Tipo (SPC=Simples/DPC=Duplo/DS=Dual Switch) Тип (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique =01 (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Control Contrôle LCD LCD Control Control LCD Ordem desde LCD Управление LCD LCD Control
HMI Control Contrôle HMI HMI Control Control IHM Ordem desde IHM Управление HMI HMI Control
Has a xPS Feedback A un retour de position xPS Has a xPS Feedback Contiene retroalimentación xPS Possui FeedBack xPS имеет xPS отзывы Has a xPS Feedback
Is activated by xPS Est activé par xPS Is activated by xPS Es activado por xPS É ativado por xPS Активируется с помощью xPS Is activated by xPS
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Relay Relais Relay Relé Relé Реле Relay
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
HIGH BREAK UNIT BOARD HBU20x Carte de sorties numériques HBU20x HIGH BREAK UNIT BOARD HBU20x TARJETAS HBU SALIDAS HBU20x Placas de Saídas Digitais DOU20x ПЛАТЫ HBU20x HBU AUSGANGSKARTE HBU20x
HBU Board Number Numéro de la carte de sorties numériques HBU HBU Board Number Número de tarjeta de salidas digitales Número de Etiqueta de saidas HBU Номер платы HBU HBU Ausgangskarte Nummer
HBU Board Slot Position de la carte de sorties numériques HBU HBU Board Slot Slot de trajeta de salidas digitales Slot de trajeta de saidas HBU Слот платы HBU HBU Ausgangskarte Steckplatz
HBU Extension Rack Number Numéro rack d'extension de la carte de sorties numériques HBU HBU Extension Rack Number Tarjeta de salidas digitales Extensión Rack Número Etiqueta de saidas HBU Extensão Rack Número продлению стойки Количество HBU HBU Ausgangskarte Extension Rack Nummer
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
DO Reference Référence DO DO Reference Referencia DO Referência DO Ссылка DO DO Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Control Contrôle Local Local Control Control Local Controle Local местного контроля Local Control
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Slot Position Slot Slot Slot Слот Slot
Channel Voie Channel Canal Canal Канал Channel
Function Fonction Function Función Função Функция Function
Type (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Simple/DPC=Double/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch) Tipo (SPC=Sencilla/DPC=Dual/DS=Dual Switch) Tipo (SPC=Simples/DPC=Duplo/DS=Dual Switch) Тип (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique =01 (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Control Contrôle LCD LCD Control Control LCD Ordem desde LCD Управление LCD LCD Control
HMI Control Contrôle HMI HMI Control Control IHM Ordem desde IHM Управление HMI HMI Control
Has a xPS Feedback A un retour de position xPS Has a xPS Feedback Contiene retroalimentación xPS Possui FeedBack xPS имеет xPS отзывы Has a xPS Feedback
Is activated by xPS Est activé par xPS Is activated by xPS Es activado por xPS É ativado por xPS Активируется с помощью xPS Is activated by xPS
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Relay Relais Relay Relé Relé Реле Relay
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
DIGITAL INPUT/OUTPUT BOARD CCU20x Carte entrées/sorties numériques CCU20x DIGITAL INPUT/OUTPUT BOARD CCU20x TARJETAS DIGITALES ENTRADAS/SALIDAS CCU20x Etiquetas digitais Entradas/saidas CCU20x ПЛАТЫ CCU20x DIGITAL EINGANGS-/AUSGANGSKARTE U200
DI/DO Board Number Numéro de la carte DI/DO DI/DO Board Number Número de tarjeta DI/DO Número de Etiqueta DI/DO Номер плат DI/DO DI/DO Karte Nummer
DI/DO Board Slot Position de la carte DI/DO DI/DO Board Slot Slot de Tarjeta DI/DO Slot do Cartão DI/DO Слот платы DI/DO DI/DO Karte Steckplatz
DI/DO Extension Rack Number Numéro rack d'extension de la carte DI/DO DI/DO Extension Rack Number Tarjeta DI/DO Extensión Rack Número Etiqueta DI/DO Extensão Rack Número продлению стойки Количество DI/DO DI/DO Extension Rack Nummer
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
DI Reference Référence DI DI Reference DI Referencia DI Referência Ссылка DI DI Referenz
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels / States Libellés/Etats Labels / States Etiquetas/Estados Etiquetas/Estados Метки / Состояния Labels / States
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Groups Groupes Groups Grupos Grupos Группы Gruppen
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Slot Position Slot Slot Slot Слот Slot
Channel Voie Channel Canal Canal Канал Channel
Function Fonction Function Función Função Функция Function
Type (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Simple/DPS=Double/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple) Tipo (SPS=Sencilla/DPS=Dual/MPS=Multiple) Tipo (SPS=Simples/DPS=Duplo/MPS=Múltiplo) Тип (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 Multiple : label d'état (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 Multiple : Texto (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 Múltiplo : Texto (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 Множественный: Обозначение (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique = 01 Multiple : Numéro d'état (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 Multiple : Número de estado (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 Múltiplo : Número de estado (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 Множественный : Состояние Number (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
Computers Groups (separator ";") Groupes de calculateur (séparateur ";") Computers Groups (separator ";") Grupos de Computadoras (separador ";") Grupos de Computadores (separador ";") Группы контроллеров (разделитель ";") Computers Gruppen (separator ";")
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
LED LED LED LED LED индикатор LED
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Is a xPC Feedback Est un retour de position xPC Is a xPC Feedback Es una xPC de retroalimentación É FeedBack de xPC Присутствует xPC обратная связь Is a xPC Feedback
Acts on xPC Acté sur xPC Acts on xPC Actúa en xPC Atua em xPC Действует на с xPC Acts on xPC
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
DO Reference Référence DO DO Reference Referencia DO Referência DO Ссылка DO DO Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Control Contrôle Local Local Control Control Local Controle Local местного контроля Local Control
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Slot Position Slot Slot Slot Слот Slot
Channel Voie Channel Canal Canal Канал Channel
Function Fonction Function Función Função Функция Function
Type (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Simple/DPC=Double/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch) Tipo (SPC=Sencilla/DPC=Dual/DS=Dual Switch) Tipo (SPC=Simples/DPC=Duplo/DS=Dual Switch) Тип (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique =01 (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Control Contrôle LCD LCD Control Control LCD Ordem desde LCD Управление LCD LCD Control
HMI Control Contrôle HMI HMI Control Control IHM Ordem desde IHM Управление HMI HMI Control
Has a xPS Feedback A un retour de position xPS Has a xPS Feedback Contiene retroalimentación xPS Possui FeedBack xPS имеет xPS отзывы Has a xPS Feedback
Is activated by xPS Est activé par xPS Is activated by xPS Es activado por xPS É ativado por xPS Активируется с помощью xPS Is activated by xPS
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Relay Relais Relay Relé Relé Реле Relay
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
ANALOG INPUT BOARD AIU21x Carte d'entrées analogiques AIU21x ANALOG INPUT BOARD AIU21x TARJETAS DE ENTRADAS ANALOGICAS AIU21x Etiquetas de Entradas Analógicas AIU21x ПЛАТЫ AIU21x ANALOGE EINGANGSKARTE AIU21x
ANALOG INPUT BOARD AIU20x Carte d'entrées analogiques AIU20x ANALOG INPUT BOARD AIU20x TARJETAS DE ENTRADAS ANALOGICAS AIU20x Etiquetas de Entradas Analógicas AIU20x ПЛАТЫ AIU20x ANALOGE EINGANGSKARTE AIU20x
Analog Input Board Number Numéro de la carte d'entrées analogiques Analog Input Board Number Número de tarjeta de entradas analógicas Número de Etiqueta de Entradas Analógicas Номер платы AI Analogeingangskarten Nummer
Analog Input Board Slot Position de la carte d'entrées analogiques Analog Input Board Slot Slot de Tarjeta de entradas analógicas Slot do Cartão de Entradas Analógicas Слот платы AI Analogeingangskarten Steckplatz
Analog Input Extension Rack Number Numéro rack d'extension de la carte d'entrées analogiques Analog Input Extension Rack Number Tarjeta de entradas analógicas Extensión Rack Número Etiqueta de Entradas Analógicas Extensão Rack Número продлению стойки Количество AI Analogeingangskarten Extension Rack Nummer
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
AI Reference Référence AI AI Reference Referencia AI Referência AI Ссылка AI AI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Link Lien Link Vínculo Vínculo Связь Link
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Channel Voie Channel Canal Canal Канал Channel
Transducer Type Type de Transducteur Transducer Type Tipo de transductor Tipo de Transdutor Тип преобразователя Transducer Type
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Corresponding AI Value at Transducer minimum Correspond à la valeur AI minimum du transducteur Corresponding AI Value at Transducer minimum Valor AI correspondiente al mínimo del transductor Valor AI correspondente ao Mínimo do Transdutor Значение AI, соответствующее минимуму преобразователя Corresponding AI Value at Transducer minimum
Corresponding AI Value at Transducer Maximum Correspond à la valeur AI maximum du transducteur Corresponding AI Value at Transducer Maximum Valor AI correspondiente al Máximo del transductor Valor AI correspondente ao Máximo do Transdutor Значение AI, соответствующее максимуму преобразователя Corresponding AI Value at Transducer Maximum
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Integrated by COUNTER Intégré par le Compteur Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
CT/VT ANALOG INPUT BOARD TMU2x0 Module Analogique CT/VT TMU2x0 CT/VT ANALOG INPUT BOARD TMU2x0 CT/VT TARJETAS DE ENTRADAS ANALOGICAS TMU2x0 CT/VT Etiquetas de Entradas Analógicas TMU2x0 ПЛАТЫ АНАЛОГОВЫЙ ВХОД CT/VT TMU2x0 CT/VT ANALOGE EINGANGSKARTE TMU2x0
CT/VT Board Number Numéro du module CT/VT CT/VT Board Number CT/VT Número de tarjeta Número do Cartão CT/VT Номер платы CT/VT CT/VT Karte Nummer
CT/VT Board Slot Position du module CT/VT CT/VT Board Slot CT/VT Slot de Tarjeta CT/VT Slot do Cartão Слот платы CT/VT CT/VT Karte Steckplatz
CT acquisition Acquisition TC CT acquisition CT adquisición CT aquisição Снятие значения тока CT acquisition
VT acquisition Acquisition TT VT acquisition VT adquisición VT aquisição Снятие значения напряжения VT acquisition
Nominal Current Courant Nominal Nominal Current Corriente nominal Corrente Nominal Номинальный ток Nennstrom
Nominal Voltage Tension Nominale Nominal Voltage Voltaje nominal Tensão Nominal Номинальное напряжение Nennspannung
CT/VT Board Model Modèle de carte CT/VT CT/VT Board Model CT/VT Modelo de Tarjeta CT/VT Modo do Cartão CT/VT борту модели CT/VT Board Model
CT/VT Extension Rack Number Numéro rack d'extension de la carte CT/VT CT/VT Extension Rack Number CT/VT Extensión Rack Número CT/VT Extensão Rack Número продлению стойки Количество CT/VT CT/VT Extension Rack Nummer
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
AI Reference Référence AI AI Reference Referencia AI Referência AI Ссылка AI AI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Link Lien Link Vínculo Vínculo Связь Link
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Input type (U/I) Type d'entrée (U/I) Input type (U/I) Tipo de entrada (U/I) Tipo de Entrada (U/I) Тип входа (U/I) Input type (U/I)
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Corresponding AI Value at minimum Correspond à la valeur AI minimum Corresponding AI Value at minimum Valor AI correspondiente al mínimo Valor AI correspondente ao Mínimo Значение AI, соответствующее минимуму Corresponding AI Value at minimum
Corresponding AI Value at Maximum Correspond à la valeur AI maximum Corresponding AI Value at Maximum Valor AI correspondiente al Máximo Valor AI correspondente ao Máximo Значение AI, соответствующее максимуму Corresponding AI Value at Maximum
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Integrated by COUNTER Intégré par le Compteur Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
IED NAME : NOM DE l'IED : IED NAME : NOMBRE DE IED : Nome do IED : ИМЯ IED : IED NAME :
DIGITAL INFORMATION FROM IED ENTREES NUMERIQUES DE l'IED DIGITAL INFORMATION FROM IED INFORMACION DIGITAL DESDE IED Informação Digital deste IED ЦИФРОВАЯ ИНФОРМАЦИЯ С IED DIGITALE INFORMATIONEN VON IED
IED name NOM DE l'IED IED name NOMBRE DE IED Nome do IED Имя IED IED name
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
IED DI Reference Référence de la carte d'entrée numérique de l'IED IED DI Reference DI Referencia IED DI Referência IED IED DI ссылка IED DI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels / States Libellés/Etats Labels / States Etiquetas/Estados Etiquetas/Estados Метки / Состояния Labels / States
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Groups Groupes Groups Grupos Grupos Группы Gruppen
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Information Adresse T103: ASDU nb;Fonction type MODBUS: Mapping Adresse;Bit nb DNP3: Adresse IEC: LD;LN T10X MASTER: Information Address T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Dirección de información T103: ASDU no;Tipo de función MODBUS: Dirección de mapeo;Bit no. DNP3: Dirección IEC: LD;LN T10X MASTER: Information Address T101: Endereço de Informação T103: ASDU no;Tipo de Função MODBUS: Endereço de Mapeamento;Bit no. DNP3: Endereço IEC: LD;LN T10X MASTER: Information Address T101: адрес информации T103: Номер ASDU ;Тип функции MODBUS: Адрес сигнала;Номер бита DNP3: Адрес IEC: LD;LN T10X MASTER: Information Address T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address
T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101:Adresse Commune ASDU;;Mode de détection T103: Information nb;Adresse CommuneASDU;Mode de détection MODBUS: Fonction;;Mode de détection DNP3: ;;Mode de détection IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Dirección común ASDU;;DetectMode T103: No. de información;Dirección común ASDU;DetectMode MODBUS: Función;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Endereço comum ASDU;;DetectMode T103: No. de Informação;Endereço comum ASDU;DetectMode MODBUS: Função;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Общий адрес ASDU;;DetectMode T103: информационный номер;Общий адрес ASDU;DetectMode MODBUS: Функция;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type
Function Fonction Function Función Função Функция Function
Type (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Simple/DPS=Double/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple) Tipo (SPS=Sencilla/DPS=Dual/MPS=Multiple) Tipo (SPS=Simples/DPS=Duplo/MPS=Múltiplo) Тип (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 Multiple : label d'état (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 Multiple : Texto (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 Múltiplo : Texto (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 Множественный: Обозначение (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique = 01 Multiple : Numéro d'état (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 Multiple : Número de estado (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 Múltiplo : Número de estado (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 Множественный : Состояние Number (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
Computers Groups (separator ";") Groupes de calculateur (séparateur ";") Computers Groups (separator ";") Grupos de Computadoras (separador ";") Grupos de Computadores (separador ";") Группы контроллеров (разделитель ";") Computers Gruppen (separator ";")
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
LED LED LED LED LED индикатор LED
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Is a xPC Feedback Est un retour de position xPC Is a xPC Feedback Es una xPC de retroalimentación É FeedBack de xPC Присутствует xPC обратная связь Is a xPC Feedback
Acts on xPC Acté sur xPC Acts on xPC Actúa en xPC Atua em xPC Действует на с xPC Acts on xPC
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
DIGITAL INFORMATION TO IED SORTIES NUMERIQUES DE l'IED DIGITAL INFORMATION TO IED INFORMACION DIGITAL HACIA IED Informação Digital Ajuste do IED ЦИФРОВАЯ ИНФОРМАЦИЯ К IED DIGITALE INFORMATIONEN AN IED
IED name NOM DE l'IED IED name NOMBRE DE IED Nome do IED Имя IED IED name
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
IED DO Reference Référence de la carte de sortie numérique de l'IED IED DO Reference IED Referencia DO IED Referência DO IED DO ссылка IED DO Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Control Contrôle Local Local Control Control Local Controle Local местного контроля Local Control
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Information Adresse T103: ASDU nb;Fonction type MODBUS: Mapping Adresse;Bit nb DNP3: Adresse IEC: LD;LN T10X MASTER: Information Address T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Dirección de información T103: ASDU no;Tipo de función MODBUS: Dirección de mapeo;Bit no. DNP3: Dirección IEC: LD;LN T10X MASTER: Information Address T101: Endereço de Informação T103: ASDU no;Tipo de Função MODBUS: Endereço de Mapeamento;Bit no. DNP3: Endereço IEC: LD;LN T10X MASTER: Information Address T101: адрес информации T103: Номер ASDU ;Тип функции MODBUS: Адрес сигнала;Номер бита DNP3: Адрес IEC: LD;LN T10X MASTER: Information Address T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address
T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101:Adresse Commune ASDU;;Type d'Ordre T103: Information nb;Adresse Commune ASDU;Type d'Ordre MODBUS: Fonction;;Type d'Ordre DNP3: ;;Type d'Ordre IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Dirección común ASDU;;OrderType T103: No. de información;Dirección común ASDU;OrderType MODBUS: Función;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Endereço comum ASDU;;OrderType T103: No. de Informação;Endereço comum ASDU;OrderType MODBUS: Função;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Общий адрес ASDU;;OrderType T103: информационный номер;Общий адрес ASDU;OrderType MODBUS: Функция;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type
Function Fonction Function Función Função Функция Function
Type (SPC=Single/DPC=Dual) Type (SPC=Simple/DPC=Double) Type (SPC=Single/DPC=Dual) Tipo (SPC=Sencilla/DPC=Dual) Tipo (SPC=Simples/DPC=Duplo) Тип (SPC=Single/DPC=Dual) Type (SPC=Single/DPC=Dual)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique =01 (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Control Contrôle LCD LCD Control Control LCD Ordem desde LCD Управление LCD LCD Control
HMI Control Contrôle HMI HMI Control Control IHM Ordem desde IHM Управление HMI HMI Control
Has a xPS Feedback A un retour de position xPS Has a xPS Feedback Contiene retroalimentación xPS Possui FeedBack xPS имеет xPS отзывы Has a xPS Feedback
Is activated by xPS Est activé par xPS Is activated by xPS Es activado por xPS É ativado por xPS Активируется с помощью xPS Is activated by xPS
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
ANALOG INFORMATION FROM IED ENTREES ANALOGIQUES DE l'IED ANALOG INFORMATION FROM IED INFORMACION ANALOGICA DESDE IED Informação Analógica deste IED АНАЛОГОВАЯ ИНФОРМАЦИЯ С IED ANALOGINFORMATIONEN VON IED
IED name NOM DE l'IED IED name NOMBRE DE IED Nome do IED Имя IED IED name
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
IED AI Reference Référence de la carte d'entrée analogique de l'IED IED AI Reference Referencia AI IED Referência AI IED IED AI ссылка IED AI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Link Lien Link Vínculo Vínculo Связь Link
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Information Adresse T103: ASDU nb;Fonction type; Unité de la MV MODBUS: Mapping Adresse;Format de la donnée DNP3: Adresse IEC: LD;LN T10X MASTER: Information Address T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Dirección de información T103: ASDU no;Tipo de función;Unidad de MV MODBUS: Dirección de mapeo;Format de Dado DNP3: Dirección IEC: LD;LN T10X MASTER: Information Address T101: Endereço de Informação T103: ASDU no;Tipo de Função;Unidade do MV MODBUS: Endereço de Mapeamento;Format de Dado DNP3: Endereço IEC: LD;LN T10X MASTER: Information Address T101: адрес информации T103: Номер ASDU ;Тип функции;Unit ofr the MV MODBUS: Адрес сигнала;DataFormat DNP3: Адрес IEC: LD;LN T10X MASTER: Information Address T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address
T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101:Adresse Commune ASDU T103: Information nb;Adresse Commune ASDU; index dans l'ASDU MODBUS: Fonction DNP3: Non utilisé IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Dirección común ASDU T103: No. de información;Dirección común ASDU;Indice in ASDU MODBUS: Función DNP3: No utilizado IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Endereço comum ASDU T103: No. de Informação;Endereço comum ASDU;Indice in ASDU MODBUS: Função DNP3: Não Utilizado IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Общий адрес ASDU T103: информационный номер;Общий адрес ASDU;Index in ASDU MODBUS: Функция DNP3: Не используется IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Corresponding AI Value at minimum Correspond à la valeur AI minimum Corresponding AI Value at minimum Valor AI correspondiente al mínimo Valor AI correspondente ao Mínimo Значение AI, соответствующее минимуму Corresponding AI Value at minimum
Corresponding AI Value at Maximum Correspond à la valeur AI maximum Corresponding AI Value at Maximum Valor AI correspondiente al Máximo Valor AI correspondente ao Máximo Значение AI, соответствующее максимуму Corresponding AI Value at Maximum
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Integrated by COUNTER Intégré par le Compteur Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
ANALOG INFORMATION TO IED SORTIES ANALOGIQUES DE l'IED ANALOG INFORMATION TO IED INFORMACION ANALOGICA HACIA IED Informação Analógica Ajuste do IED АНАЛОГОВАЯ ИНФОРМАЦИЯ К IED ANALOGINFORMATIONEN AN IED
IED name NOM DE l'IED IED name NOMBRE DE IED Nome do IED Имя IED IED name
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
IED AI Reference Référence de la carte d'entrée analogique de l'IED IED AI Reference Referencia AI IED Referência AI IED IED AI ссылка IED AI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Information Adresse;Format de Sortie T103: ASDU nb;Fonction type;Format de Sortie MODBUS: Mapping Adresse DNP3: Adresse IEC: LD;LN T10X MASTER: Information Address T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Dirección de información;Output Format T103: ASDU no;Tipo de función;Output Format MODBUS: Dirección de mapeo DNP3: Dirección IEC: LD;LN T10X MASTER: Information Address T101: Endereço de Informação;Output Format T103: ASDU no;Tipo de Função;Output Format MODBUS: Endereço de Mapeamento DNP3: Endereço IEC: LD;LN T10X MASTER: Information Address T101: адрес информации;Output Format T103: Номер ASDU ;Тип функции;Output Format MODBUS: Адрес сигнала DNP3: Адрес IEC: LD;LN T10X MASTER: Information Address T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address
T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101:Adresse Commune ASDU;;Type d'Ordre T103: Information nb;Adresse Commune ASDU;Type d'Ordre MODBUS: Fonction;;Type d'Ordre DNP3: ;;Type d'Ordre IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Dirección común ASDU;;OrderType T103: No. de información;Dirección común ASDU;OrderType MODBUS: Función;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Endereço comum ASDU;;OrderType T103: No. de Informação;Endereço comum ASDU;OrderType MODBUS: Função;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Общий адрес ASDU;;OrderType T103: информационный номер;Общий адрес ASDU;OrderType MODBUS: Функция;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Corresponding AI Value at minimum Correspond à la valeur AI minimum Corresponding AI Value at minimum Valor AI correspondiente al mínimo Valor AI correspondente ao Mínimo Значение AI, соответствующее минимуму Corresponding AI Value at minimum
Corresponding AI Value at Maximum Correspond à la valeur AI maximum Corresponding AI Value at Maximum Valor AI correspondiente al Máximo Valor AI correspondente ao Máximo Значение AI, соответствующее максимуму Corresponding AI Value at Maximum
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
END OF IED DATA FIN DES DONNEES DE l'IED END OF IED DATA FIN DE DATOS IED FIM DOS DADOS IED КОНЕЦ ДАННЫХ ПО IED END OF IED DATA
DI GROUPS GROUPES ENTREES NUMERIQUES DI GROUPS Grupos DI Grupos DI Группы DI DI GROUPS
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
Group DI Reference Référence du Groupes des DI Group DI Reference Referencia de grupo DI Referência de grupo DI Группа DI ссылку Gruppe DI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Groups Groupes Groups Grupos Grupos Группы Gruppen
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Number Numéro Number Número Número Номер Number
Group Operator Opérateur du Groupe Group Operator Operador de grupo Operador de grupo Группа оператора Gruppe Operator
Function Fonction Function Función Função Функция Function
Type (S=Single) Type (S=Simple) Type (S=Single) Tipo (S=Sencilla) Tipo (S=Simples) Тип (S=Single) Type (S=Single)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 (16 char) Simple : Texte à l'état électrique = 1 (16 car) Single : Text at electrical state = 1 (16 char) Sencilla : Texto en estado eléctrico = 1 (16 caract) Simples: Texto em estado Elétrico = 1 (16 caract) Одиночный : Обозначение электрического состояния = 1 (16 символов) Single : Text at electrical state = 1 (16 char)
Single : Text at electrical state = 0 (16 char) Simple : Texte à l'état électrique = 0 (16 car) Single : Text at electrical state = 0 (16 char) Sencilla : Texto en estado eléctrico = 0 (16 caract) Simples: Texto em estado Elétrico = 0 (16 caract) Одиночный : Обозначение электрического состояния = 0 (16 символов) Single : Text at electrical state = 0 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
Computers Groups (separator ";") Groupes de calculateur (séparateur ";") Computers Groups (separator ";") Grupos de Computadoras (separador ";") Grupos de Computadores (separador ";") Группы контроллеров (разделитель ";") Computers Gruppen (separator ";")
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
LED LED LED LED LED индикатор LED
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Is a xPC Feedback Est un retour de position xPC Is a xPC Feedback Es una xPC de retroalimentación É FeedBack de xPC Присутствует xPC обратная связь Is a xPC Feedback
Acts on xPC Acté sur xPC Acts on xPC Actúa en xPC Atua em xPC Действует на с xPC Acts on xPC
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
SELF GENERATED DIGITAL INFORMATION ENTREES NUMERIQUES AUTOMATIQUES SELF GENERATED DIGITAL INFORMATION INFORMACION DIGITAL AUTO GENERADA Informação Digital Auto Gerada ЦИФРОВАЯ ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ SELBSTGENERIERTE DIGITALE INFORMATIONEN
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
Self DI Reference Référence interne DI Self DI Reference Referencia DI auto Referência DI Auto Собственная ссылка DI Self DI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels / States Libellés/Etats Labels / States Etiquetas/Estados Etiquetas/Estados Метки / Состояния Labels / States
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Groups Groupes Groups Grupos Grupos Группы Gruppen
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Number Numéro Number Número Número Номер Number
Function Fonction Function Función Função Функция Function
Type (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Simple/DPS=Double/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple) Tipo (SPS=Sencilla/DPS=Dual/MPS=Multiple) Tipo (SPS=Simples/DPS=Duplo/MPS=Múltiplo) Тип (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 Multiple : label d'état (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 Multiple : Texto (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 Múltiplo : Texto (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 Множественный: Обозначение (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique = 01 Multiple : Numéro d'état (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 Multiple : Número de estado (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 Múltiplo : Número de estado (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 Множественный : Состояние Number (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
Computers Groups (separator ";") Groupes de calculateur (séparateur ";") Computers Groups (separator ";") Grupos de Computadoras (separador ";") Grupos de Computadores (separador ";") Группы контроллеров (разделитель ";") Computers Gruppen (separator ";")
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
LED LED LED LED LED индикатор LED
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Is a xPC Feedback Est un retour de position xPC Is a xPC Feedback Es una xPC de retroalimentación É FeedBack de xPC Присутствует xPC обратная связь Is a xPC Feedback
Acts on xPC Acté sur xPC Acts on xPC Actúa en xPC Atua em xPC Действует на с xPC Acts on xPC
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Automation Origin (if any) Automatisme d'origine (si existant) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
SELF GENERATED DIGITAL OUTPUT INFORMATION SORTIES NUMERIQUES AUTOMATIQUES SELF GENERATED DIGITAL OUTPUT INFORMATION INFORMACION DE SALIDAS DIGITALES AUTO GENERADAS Informação de saidas Digitais Auto Geradas ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ ЦИФРОВЫМИ ВЫХОДАМИ SELBSTGENERIERTE DIGITALE AUSGANGSINFORMATIONEN
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
Self DO Reference Référence interne DO Self DO Reference Referencia DO Auto Referência DO Auto Собственная DO ссылка Self DO Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Control Contrôle Local Local Control Control Local Controle Local местного контроля Local Control
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Number Numéro Number Número Número Номер Number
Function Fonction Function Función Função Функция Function
Type (SPC=Single/DPC=Dual) Type (SPC=Simple/DPC=Double) Type (SPC=Single/DPC=Dual) Tipo (SPC=Sencilla/DPC=Dual) Tipo (SPC=Simples/DPC=Duplo) Тип (SPC=Single/DPC=Dual) Type (SPC=Single/DPC=Dual)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique =01 (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Control Contrôle LCD LCD Control Control LCD Ordem desde LCD Управление LCD LCD Control
HMI Control Contrôle HMI HMI Control Control IHM Ordem desde IHM Управление HMI HMI Control
Has a xPS Feedback A un retour de position xPS Has a xPS Feedback Contiene retroalimentación xPS Possui FeedBack xPS имеет xPS отзывы Has a xPS Feedback
Is activated by xPS Est activé par xPS Is activated by xPS Es activado por xPS É ativado por xPS Активируется с помощью xPS Is activated by xPS
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Relay Relais Relay Relé Relé Реле Relay
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Automation Origin (if any) Automatisme d'origine (si existant) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
SELF GENERATED ANALOG INFORMATION ENTREES ANALOGIQUES AUTOMATIQUES SELF GENERATED ANALOG INFORMATION INFORMACION ANALOGICA AUTO GENERADA Informação Analógica Auto Gerada АНАЛОГОВАЯ ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ SELBST GENERIERTE ANALOGINFORMATIONEN
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
Self AI Reference Référence interne AI Self AI Reference Referencia AI auto Referência AI Automática Собственная ссылка AI Self AI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Link Lien Link Vínculo Vínculo Связь Link
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Number Numéro Number Número Número Номер Number
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Corresponding AI Value at Transducer minimum Correspond à la valeur AI minimum du transducteur Corresponding AI Value at Transducer minimum Valor AI correspondiente al mínimo del transductor Valor AI correspondente ao Mínimo do Transdutor Значение AI, соответствующее минимуму преобразователя Corresponding AI Value at Transducer minimum
Corresponding AI Value at Transducer Maximum Correspond à la valeur AI maximum du transducteur Corresponding AI Value at Transducer Maximum Valor AI correspondiente al Máximo del transductor Valor AI correspondente ao Máximo do Transdutor Значение AI, соответствующее максимуму преобразователя Corresponding AI Value at Transducer Maximum
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Integrated by COUNTER Intégré par le Compteur Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Automation Origin (if any) Automatisme d'origine (si existant) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : C364_Template SHEET : C364_Template SHEET : C364_Template SHEET : C364_Template SHEET : C364_Template SHEET : C364_Template SHEET : C364_Template
MiCOM C364 DESCRIPTION DESCRIPTION DU MiCOM C364 MiCOM C364 DESCRIPTION Descripción MiCOM C364 Descrição MiCOM C364 ОПИСАНИЕ MiCOM C364 MiCOM C364 BESCHREIBUNG
DI GROUPS GROUPES DES ENTREES NUMERIQUES DI GROUPS Grupos DI Grupos DI DI Группы DI GROUPS
SELF GENERATED DIGITAL INFORMATION ENTREES NUMERIQUES AUTOMATIQUES SELF GENERATED DIGITAL INFORMATION INFORMACION DIGITAL AUTO GENERADA Informação Digital Auto Gerada ЦИФРОВАЯ ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ SELBSTGENERIERTE DIGITALE INFORMATIONEN
SELF GENERATED DIGITAL OUTPUT INFORMATION SORTIES NUMERIQUES AUTOMATIQUES SELF GENERATED DIGITAL OUTPUT INFORMATION INFORMACION DE SALIDAS DIGITALES AUTO GENERADAS Informação de saidas digitais Auto Geradas ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ ЦИФРОВЫМИ ВЫХОДАМИ SELBSTGENERIERTE DIGITALE AUSGANGS INFORMATIONEN
SELF GENERATED ANALOG INFORMATION ENTREES ANALOGIQUES AUTOMATIQUES SELF GENERATED ANALOG INFORMATION INFORMACION ANALOGICA AUTO GENERADA Informação Analógica Auto Gerada АНАЛОГОВАЯ ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ SELBSTGENERIERTE ANALOG INFORMATIONEN
SHEET : Substation data SHEET : Données de la Soustation SHEET : Substation data SHEET : Datos de subestación SHEET : Dados da Substação SHEET : Данные подстанции SHEET : Substation data
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
SUBSTATION DATA DESCRIPTION DESCRIPTION DES DONNEES DE SOUS-STATION SUBSTATION DATA DESCRIPTION DESCRIPCION DE DATOS DE SUBESTACION Descrição de Dados de Substação ДАННЫЕ ОПИСАНИЯ ПОДСТАНЦИИ SUBSTATION DATA DESCRIPTION
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
Substation Name Nom de la Sous-station Substation Name Nombre de subestación Nome do Substação Имя подстанции Stationsname:
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Control Uniqueness Contrôle Uniquement Control Uniqueness Unequidad de control Unicidade de Controle Однозначность управления Control Uniqueness
Substation Sous-station Substation Subestación Substação Подстанция Substation
No / Substation / Bay / Specific Non / Sous-station / Tranche / Spécifique No / Substation / Bay / Specific No / Subestación / Bahía / Specifico Não/ Substação / Painel / Específico No / Substation / Bay / Specific No / Substation / Bay / Specific
Auto generated Génération automatique Auto generated Auto generado Auto Geração Автоматически сгенерировано Auto generated
Site taking control Emplacement prenant le contrôle Site taking control Toma de control de sitio Controle de Sítio Site taking control Site taking control
SCADA & Local SCADA & Local SCADA & Local SCADA & Local SCADA & Local SCADA & Local SCADA & Local
SCADA / Local / SCADA & Local SCADA / Local / SCADA & Local SCADA / Local / SCADA & Local SCADA / Local / SCADA & Local SCADA / Local / SCADA & Local SCADA / Local / SCADA & Local SCADA / Local / SCADA & Local
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Gateway Passerelle Gateway UTR UTR Шлюз Gateway
Port used (on gateway) Ports utilisés (sur la passerelle) Port used (on gateway) Puerto utilizado (en UTR) Porta utilizada (em UTR) Используемый порт (на шлюз) benutzter Port (Gateway)
SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1
SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2
SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3
SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4
Default Computer that manages Substation Calculateur par défaut gérant la Sous-station Default Computer that manages Substation Equipo que gestiona Subestación Computador que gerencia Subestação компьютер, который управляет Подстанция Computer verwaltet Substation
SUBSTATION DI GROUPS GROUPES DES DI DE LA SOUS-STATION SUBSTATION DI GROUPS GRUPOS DI SUBSTATION GRUPOS DE SUBSTAÇÃO Группы DI подстанции SUBSTATION DI GROUPS
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
Group DI Reference Référence du Groupes des DI Group DI Reference Referencia de grupo DI Referência de grupo DI Группа DI ссылку Gruppe DI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Description Description Description Descripción Descrição Описание Beschreibung
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Groups Groupes Groups Grupos Grupos Группы Gruppen
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Number Numéro Number Número Número Номер Number
Group Operator Opérateur du Groupe Group Operator Operador de grupo Operador de grupo Группа оператора Gruppe Operator
Function Fonction Function Función Função Функция Function
Type (S=Single) Type (S=Simple) Type (S=Single) Tipo (S=Sencilla) Tipo (S=Simples) Тип (S=Single) Type (S=Single)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 (16 char) Simple : Texte à l'état électrique = 1 (16 car) Single : Text at electrical state = 1 (16 char) Sencilla : Texto en estado eléctrico = 1 (16 caract) Simples: Texto em estado Elétrico = 1 (16 caract) Одиночный : Обозначение электрического состояния = 1 (16 символов) Single : Text at electrical state = 1 (16 char)
Single : Text at electrical state = 0 (16 char) Simple : Texte à l'état électrique = 0 (16 car) Single : Text at electrical state = 0 (16 char) Sencilla : Texto en estado eléctrico = 0 (16 caract) Simples: Texto em estado Elétrico = 0 (16 caract) Одиночный : Обозначение электрического состояния = 0 (16 символов) Single : Text at electrical state = 0 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
Managed by Computer Géré par le Calcultateur Managed by Computer Manejado por la computadora Controlado por Computador управляет компьютер Managed by Computer
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
LED LED LED LED LED индикатор LED
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Is a xPC Feedback Est un retour de position xPC Is a xPC Feedback Es una xPC de retroalimentación É FeedBack de xPC Присутствует xPC обратная связь Is a xPC Feedback
Acts on xPC Acté sur xPC Acts on xPC Actúa en xPC Atua em xPC Действует на с xPC Acts on xPC
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : Electric Functions SHEET : Fonctions Electriques SHEET : Electric Functions SHEET : Funciones eléctricas SHEET : FUNÇÕES ELÉTRICAS SHEET : Функции электрической части SHEET : Electric Functions
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
ELECTRICAL PROFILES PROFILS ELECTRIQUES ELECTRICAL PROFILES PERFILES ELECTRICOS Perfis Elétricos ПРОФИЛИ ЭЛЕКТРИЧЕСКОЙ ЧАСТИ ELECTRICAL PROFILES
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Single Digital Inputs Profiles Profils des entrées numériques simples (SPS) Single Digital Inputs Profiles Perfiles de entradas digitales sencillas Perfis de Entradas Digitais Únicas Профили одинарных DI Single Digital Inputs Profiles
Single System Digital Inputs Profiles Profils des entrées numériques systèmes simples (SPS) Single System Digital Inputs Profiles Pérfiles de sistema de entradas digitales sencillas Perfis de Sistema de Entradas Digitais Únicas Профили одинарных системных DI Single System Digital Inputs Profiles
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
SPS General Parameters Paramètres généraux de la SPS SPS General Parameters Parámetros generales SPS Parâmetros Geração SPS Основные параметры SPS SPS General Parameters
Generation Condition Condition de la Génération Generation Condition Condición de generación Condição de Geração Основное условие Generation Condition
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
Fugitive Alarm (Spurious) Alarme fugitive Fugitive Alarm (Spurious) Alarma fujitiva (Spurious) Alarme de Fuga(Spurious) Fugitive Alarm (Spurious) Fugitive Alarm (Spurious)
State 1 confirmation delay (x100 ms) Etat 1 confirmation du retard (x100 ms) State 1 confirmation delay (x100 ms) Confirmación de retardo Estado 1 (x100 ms) Confirmação de retardo Estado 1 (x100 ms) Состояние 1 задержка подтверждения (х100 мс) State 1 confirmation delay (x100 ms)
State 1 Gravity level Etat 1 niveau de gravité State 1 Gravity level Nivel de gravedad estado 1 Nivel de gravidade estado 1 Состояние 1 уровень сложности State 1 Gravity level
State 0 confirmation delay (x100 ms) Etat 0 confirmation du retard (x100 ms) State 0 confirmation delay (x100 ms) Confirmación de retardo Estado 0 (x100 ms) Confirmação de retardo Estado 0 (x100 ms) Состояние 0 задержка подтверждения (х100 мс) State 0 confirmation delay (x100 ms)
State 0 Gravity level Etat 0 niveau de gravité State 0 Gravity level Nivel de gravedad estado 0 Nivel de gravidade estado 0 Состояние 0 - уровень сложности State 0 Gravity level
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
SPS Printing Parameters Paramètres d'impression de la SPS SPS Printing Parameters Parámetros de impresión SPS Parâmetros de Impressão SPS Параметры печати SPS SPS Printing Parameters
Printed on Sequence Of Events SOE 1 : Imprimer sur l'imprimante Fil de l'eau 1 : Printed on Sequence Of Events SOE 1 : Impreso en SOE 1 : Impresso em SOE 1 : Вывод на SOE 1 : Printed on Sequence Of Events SOE 1 :
Printed on Sequence Of Events SOE 2 : Imprimer sur l'imprimante Fil de l'eau 2 : Printed on Sequence Of Events SOE 2 : Impreso en SOE 2 : Impresso em SOE 1 : Вывод на SOE 2 : Printed on Sequence Of Events SOE 2 :
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
SPS Interlocking Parameters Paramètres d'Interverrouillage de la SPS SPS Interlocking Parameters Parámetros de enclavamientos SPS Parâmetros de Intertravamento SPS Параметры блокировки SPS SPS Interlocking Parameters
Reset Interlock Value Reset des valeurs de l'interverrouillage Reset Interlock Value Reiniciar valor de enclavamiento Reiniciar Valor de Intertravamento Сбросить значение блокировки Reset Interlock Value
Set Interlock Value Niveau haut des valeurs de l'interverrouillage Set Interlock Value Ajustar valor de enclavamiento Ajustar Valor de Intertravamento Установить значение блокировки Set Interlock Value
SPS Processing Parameters Paramètres de traitement de la SPS SPS Processing Parameters Parámetros de procesamiento SPS Parâmetros de Processamento SPS Пораметры обработки SPS SPS Processing Parameters
Toggling state label Libellé de l'état de basculement Toggling state label Etiqueta de estado en curso Etiqueta de estado em Curso Метка статуса Toggling Toggling state label
SelfCheckFault state label Libellé de l'état d'auto vérification du défaut SelfCheckFault state label Etiqueta de estado FallaAutoChequeo Etiqueta de estado FalhaAutoCheque Метка статуса SelfCheckFault SelfCheckFault state label
Unknown state label Libellé de l'état inconnu Unknown state label Etiqueta de estado desconocido Etiqueta de estado Desconhecido Метка статуса Unknown Unknown state label
Suppressed state label Libellé de l'état supprimé Suppressed state label Etiqueta de estado suprimido Etiqueta de estado Suprimido Метка статуса Suppressed Suppressed state label
Forced state label Libellé de l'état forcé Forced state label Etiqueta de estado forzado Etiqueta de estado Forçado Метка статуса Forced Forced state label
Substituted state label Libellé de l'état substitué Substituted state label Etiqueta de estado sustituido Etiqueta de estado Substituído Метка статуса Substituted Substituted state label
Treatment on Set state Traitement sur l'état Set Treatment on Set state Manipulación en estado de Ajuste Manipulação em estado de Ajuste Обработка статуса Set Treatment on Set state
Treatment on Reset state Traitement sur l'état Reset Treatment on Reset state Manipulación en estado de reajuste Manipulação em estado de Reajuste Обработка статуса Reset Treatment on Reset state
Treatment on Open state Traitement sur l'état Ouvert Treatment on Open state Manipulación en estado Abierto Manipulação em estado Aberto Обработка статуса Open Treatment on Open state
Treatment on Close state Traitement sur l'état Fermé Treatment on Close state Manipulación en estado Cerrado Manipulação em estado Fechado Обрабока статуса Close Treatment on Close state
Treatment on Toggling state Traitement sur l'état de basculement Treatment on Toggling state Manipulación en estado en curso Manipulação em estado em Curso Обработка статуса Toggling Treatment on Toggling state
Treatment on SelfCheckFault state Traitement sur l'état d'auto vérification du défaut Treatment on SelfCheckFault state Manipulación en estado FallaAutoChequeo Manipulação em estado FalhaAutoCheque Обработка статуса SelfCheckFault Treatment on SelfCheckFault state
Treatment on Unknown state Traitement sur l'état inconnu Treatment on Unknown state Manipulación en estado Desconocido Manipulação em estado Desconhecido Обрабока статуса Unknown Treatment on Unknown state
Treatment on Suppressed state Traitement sur l'état supprimé Treatment on Suppressed state Manipulación en estado Suprimido Manipulação em estado Suprimido Обработка статуса Suppressed Treatment on Suppressed state
Treatment on Forced state Traitement sur l'état forcé Treatment on Forced state Manipulación en estado Forzado Manipulação em estado Forçado Обработка статуса Forced Treatment on Forced state
Treatment on Substituted state Traitement sur l'état substitué Treatment on Substituted state Manipulación en estado sustituido Manipulação em estado Substituído Обработка статуса Substituted Treatment on Substituted state
Treatment on Forcing state Traitement sur l'état de forçage Treatment on Forcing state Manipulación en estado Forzando Manipulação em estado Forzando Обработка статуса Forcing Treatment on Forcing state
Treatment on Substitution state Traitement sur l'état de substitution Treatment on Substitution state Manipulación en estado por sustitución Manipulação em estado por Substituição Обработка статуса Substitution Treatment on Substitution state
Treatment on Suppression state Traitement sur l'état de suppression Treatment on Suppression state Manipulación en estado por supresión Manipulação em estado por Supressão Обработка статуса Suppression Treatment on Suppression state
Alarm and Gravity on Toggling state Gravité d'alarme sur l'état de basculement Alarm and Gravity on Toggling state Alarma y gravedad en estado en curso Alarme e gravidade em estado em Curso Тревога и важность статуса Toggling Alarm and Gravity on Toggling state
Alarm and Gravity on SelfCheckFault state Gravité d'alarme sur l'état d'auto vérification du défaut Alarm and Gravity on SelfCheckFault state Alarma y gravedad en estado FallaAutoChequeo Alarme e gravidade em estado FalhaAutoCheque Тревога и важность статуса SelfCheckFault Alarm and Gravity on SelfCheckFault state
Alarm and Gravity on Unknown state Gravité d'alarme sur l'état inconnu Alarm and Gravity on Unknown state Alarma y gravedad en estado desconocido Alarme e gravidade em estado Desconhecido Тревога и важность статуса Unknown Alarm and Gravity on Unknown state
Alarm and Gravity on Suppressed state Gravité d'alarme sur l'état supprimé Alarm and Gravity on Suppressed state Alarma y gravedad en estado Suprimido Alarme e gravidade em estado Suprimido Тревога и важность статуса Suppressed Alarm and Gravity on Suppressed state
Alarm and Gravity on Forced state Gravité d'alarme sur l'état forcé Alarm and Gravity on Forced state Alarma y gravedad en estado forzado Alarme e gravidade em estado Forçado Тревога и важность статуса Forced Alarm and Gravity on Forced state
Alarm and Gravity on Substituted state Gravité d'alarme sur l'état substitué Alarm and Gravity on Substituted state Alarma y gravedad en estado Sustituido Alarme e gravidade em estado Substituído Тревога и важность статуса Substituted Alarm and Gravity on Substituted state
Masking due to control Masqué dû à la commande Masking due to control Enmascarar debido al control Mascarar devido ao controle Masking due to control Masking due to control
SBMC dependant Dépendance SBMC SBMC dependant SBMC dependiente SBMC dependente SBMC иждивенца SBMC unterhaltsberechtigte
Toggling filtering Basculement du filtrage Toggling filtering Curso de la filtración Curso de filtrar Toggling filtering Toggling filtering
Initial status Status initial Initial status Estado inicial Estado inicial Начальный статус Initial status
Forced Reset Interlock Value Reset forcé des valeurs de l'interverrouillage Forced Reset Interlock Value Reiniciar forzado valor de enclavamiento Reiniciar Forçado Valor de Intertravamento Сброс значения блокировки Forced Forced Reset Interlock Value
Forced Set Interlock Value Niveau haut forcé des valeurs de l'interverrouillage Forced Set Interlock Value Ajustar forzado valor de enclavamiento Ajustar Forçado Valor de Intertravamento Установка значения блокировки Forced Forced Set Interlock Value
Substituted Reset Interlock Value Reset substitué des valeurs de l'interverrouillage Substituted Reset Interlock Value Reiniciar Sustituido valor de enclavamiento Reiniciar Substituído Valor de Intertravamento Сброс значения блокировки Substituted Substituted Reset Interlock Value
Substituted Set Interlock Value Niveau haut substitué des valeurs de l'interverrouillage Substituted Set Interlock Value Ajustar Sustituido valor de enclavamiento Ajustar Substituído Valor de Intertravamento Установка значения блокировки Substituted Substituted Set Interlock Value
Suppressed interlock value Valeur de l'interverrouillage supprimé Suppressed interlock value Valor de enclavamiento suprimido Valor de Intertravamento Suprimido Значение блокировки Suppressed Suppressed interlock value
Unknown interlock value Valeur de l'interverrouillage inconnu Unknown interlock value Valor de enclavamiento desconocido Valor de Intertravamento Desconhecido Значение блокировки Unknown Unknown interlock value
Toggling interlock value Valeur de l'interverrouillage de basculement Toggling interlock value Valor de enclavamiento curso Valor de Intertravamento Curso Значение блокировки Toggling Toggling interlock value
SelfCheckFault interlock value Valeur de l'interverrouillage sur l'auto vérification du défaut SelfCheckFault interlock value Valor de enclavamiento FallaAutoChequeo Valor de Intertravamento FalhaAutoCheque Значение блокировки SelfCheckFaul SelfCheckFault interlock value
Default State labels Valeurs par défaut des Etats électriques Default State labels Por defecto las etiquetas de estado Estado padrão rótulos По умолчанию состояние этикетки Default State labels
Default Text at electrical state = 1 (16 char) Texte par défaut à l'état électrique = 1 (16 car) Default Text at electrical state = 1 (16 char) Texto predeterminado en estado eléctrico = 1 (16 caract) Texto padrão em estado Elétrico = 1 (16 caract) умолчанию текст электрического состояния = 1 (16 символов) Default Text at electrical state = 1 (16 char)
Default Text at electrical state = 0 (16 char) Texte par défaut à l'état électrique = 0 (16 car) Default Text at electrical state = 0 (16 char) Texto predeterminado en estado eléctrico = 0 (16 caract) Texto padrão em estado Elétrico = 0 (16 caract) умолчанию текст электрического состояния = 0 (16 символов) Default Text at electrical state = 0 (16 char)
Enable FSS (forcing / substituting / suppressing) Activer le FSS (forçage / substitution / suppression) Enable FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) позволить FSS (forcing / substituting / suppressing) Enable FSS (forcing / substituting / suppressing)
Double Digital Inputs Profiles Profils des entrées numériques doubles (DPS) Double Digital Inputs Profiles Perfiles entradas digitales Dobles Perfis Entradas Digitais Duplas Профили двоичных DI Double Digital Inputs Profiles
Double System Digital Inputs Profiles Profils des entrées numériques systèmes doubles (DPS) Double System Digital Inputs Profiles Pérfiles de sistema de entradas digitales dobles Perfis de Sistema de Entradas Digitais Duplas Профили двоичных системных DI Double System Digital Inputs Profiles
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
DPS General Parameters Paramètres généraux de la DPS DPS General Parameters Parámetros generales DPS Parâmetros Geração DPS Основные параметры DPS DPS General Parameters
Generation Condition Condition de la Génération Generation Condition Condición de generación Condição de Geração Основное условие Generation Condition
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
State 10 Gravity level Etat 10 niveau de gravité State 10 Gravity level Nivel de gravedad 10 Nivel de gravidade 10 Состояние 10 Уровень важности State 10 Gravity level
State 10 confirmation delay (x100 ms) Etat 10 confirmation de retard (x100 ms) State 10 confirmation delay (x100 ms) Confirmación de retardo Estado 10 (x100 ms) Confirmação de retardo Estado 10 (x100 ms) Состояние 10 задержка подтверждения (х100 мс) State 10 confirmation delay (x100 ms)
State 01 Gravity level Etat 01 niveau de gravité State 01 Gravity level Nivel de gravedad Estado 01 Nivel de gravidade Estado 01 Состояние 01 Уровень важности State 01 Gravity level
State 01 confirmation delay (x100 ms) Etat 01 confirmation du retard (x100 ms) State 01 confirmation delay (x100 ms) Confirmación de retardo Estado 01 (x100 ms) Confirmação de retardo Estado 01 (x100 ms) Состояние 01 задержка подтверждения (х100 мс) State 01 confirmation delay (x100 ms)
Complementary [00] delay (x100 ms) Complémentarité [00] retard (x100 ms) Complementary [00] delay (x100 ms) Retardo [00] complementario (x100 ms) Retardo [00] complememtario (x100 ms) Дополнительная [00] задержка (х100 мс) Complementary [00] delay (x100 ms)
Complementary [11] delay (x100 ms) Complémentarité [11] retard (x100 ms) Complementary [11] delay (x100 ms) Retardo [11] complementario (x100 ms) Retardo [11] complememtario (x100 ms) Дополнительная [11] задержка (х100 мс) Complementary [11] delay (x100 ms)
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
DPS Printing Parameters Paramètres d'impression de la DPS DPS Printing Parameters Parámetros de impresión DPS Parâmetros de Impressão DPS Параметры печати DPS DPS Printing Parameters
Printed on Sequence Of Events SOE 1 : Imprimer sur l'imprimante Fil de l'eau 1 : Printed on Sequence Of Events SOE 1 : Impreso en SOE 1 : Impresso em SOE 1 : Вывод на SOE 1 : Printed on Sequence Of Events SOE 1 :
Printed on Sequence Of Events SOE 2 : Imprimer sur l'imprimante Fil de l'eau 2 : Printed on Sequence Of Events SOE 2 : Impreso en SOE 2 : Impresso em SOE 1 : Вывод на SOE 2 : Printed on Sequence Of Events SOE 2 :
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
DPS Interlocking Parameters Paramètres d'Interverrouillage de la DPS DPS Interlocking Parameters Parámetros de enclavamiento DPS Parâmetros de Intertravamento DPS Параметры блокировки DPS DPS Interlocking Parameters
Jammed Interlock Value Valeur "bloqué" de l'interverrouillage Jammed Interlock Value Valor enclavamiento bloqueado Valor Intertravamento bloqueado Значение блокировки Jammed Jammed Interlock Value
Open Interlock Value Valeur "ouvert" de l'interverrouillage Open Interlock Value Valor enclavamiento abierto Valor Intertravamento Aberto Значение блокировки Open Open Interlock Value
Closed Interlock Value Valeur "fermé" de l'interverrouillage Closed Interlock Value Valor enclavamiento cerrado Valor Intertravamento Fechado Значение блокировки Closed Closed Interlock Value
DPS Processing Parameters Paramètres de traitement de la DPS DPS Processing Parameters Parámetros de procesadmiento DPS Parâmetros de Processamento DPS Пораметры обработки DPS DPS Processing Parameters
Jammed (=DBI 00) state label Libellé de l'état bloqué (=DBI 00) Jammed (=DBI 00) state label Etiqueta de estado bloqueado (=DBI 00) Etiqueta de estado bloqueado (=DBI 00) Метка статуса Jammed (=DBI 00) Jammed (=DBI 00) state label
Undefined (=DBI 11) state label Libellé de l'état indéfini (=DBI 11) Undefined (=DBI 11) state label Etiqueta de estado indefinido (=DBI 11) Etiqueta de estado Indefinido (=DBI 11) Метка статуса Undefined (=DBI 11) Undefined (=DBI 11) state label
Toggling state label Libellé de l'état de basculement Toggling state label Etiqueta de estado en curso Etiqueta de estado em Curso Метка статуса Toggling Toggling state label
SelfCheckFault state label Libellé de l'état d'auto vérification du défaut SelfCheckFault state label Etiqueta de estado FallaAutoChequeo Etiqueta de estado FalhaAutoCheque Метка статуса SelfCheckFault SelfCheckFault state label
Unknown state label Libellé de l'état inconnu Unknown state label Etiqueta de estado desconocido Etiqueta de estado Desconhecido Метка статуса Unknown Unknown state label
Suppressed state label Libellé de l'état supprimé Suppressed state label Etiqueta de estado suprimido Etiqueta de estado Suprimido Метка статуса Suppressed Suppressed state label
Forced state label Libellé de l'état forcé Forced state label Etiqueta de estado forzado Etiqueta de estado Forçado Метка статуса Forced Forced state label
Substituted state label Libellé de l'état substitué Substituted state label Etiqueta de estado sustituido Etiqueta de estado Substituído Метка статуса Substituted Substituted state label
Motion interlock value Valeur de l'interverrouillage Motion Motion interlock value Valor de enclavamiento Motion Valor de Intertravamento Motion Значение блокировки Motion Motion interlock value
Treatment on Open state Traitement sur l'état Ouvert Treatment on Open state Manipulación en estado Abierto Manipulação em estado Aberto Обработка статуса Open Treatment on Open state
Treatment on Close state Traitement sur l'état Fermé Treatment on Close state Manipulación en estado Cerrado Manipulação em estado Fechado Обрабока статуса Close Treatment on Close state
Treatment on Jammed state Traitement sur l'état bloqué Treatment on Jammed state Manipulación en estado bloqueado Manipulação em estado bloqueado Обработка статуса Jammed Treatment on Jammed state
Treatment on Undefined state Traitement sur l'état indéfini Treatment on Undefined state Manipulación en estado Indefinido Manipulação em estado Indefinido Обработка статуса Undefined Treatment on Undefined state
Treatment on Toggling state Traitement sur l'état de basculement Treatment on Toggling state Manipulación en estado en curso Manipulação em estado em Curso Обработка статуса Toggling Treatment on Toggling state
Treatment on SelfCheckFault state Traitement sur l'état d'auto vérification du défaut Treatment on SelfCheckFault state Manipulación en estado FallaAutoChequeo Manipulação em estado FalhaAutoCheque Обработка статуса SelfCheckFault Treatment on SelfCheckFault state
Treatment on Unknown state Traitement sur l'état inconnu Treatment on Unknown state Manipulación en estado Desconocido Manipulação em estado Desconhecido Обрабока статуса Unknown Treatment on Unknown state
Treatment on Suppressed state Traitement sur l'état supprimé Treatment on Suppressed state Manipulación en estado Suprimido Manipulação em estado Suprimido Обработка статуса Suppressed Treatment on Suppressed state
Treatment on Forced state Traitement sur l'état forcé Treatment on Forced state Manipulación en estado Forzado Manipulação em estado Forçado Обработка статуса Forced Treatment on Forced state
Treatment on Substituted state Traitement sur l'état substitué Treatment on Substituted state Manipulación en estado sustituido Manipulação em estado Substituído Обработка статуса Substituted Treatment on Substituted state
Treatment on Forcing state Traitement sur l'état de forçage Treatment on Forcing state Manipulación en estado Forzando Manipulação em estado Forzando Обработка статуса Forcing Treatment on Forcing state
Treatment on Substitution state Traitement sur l'état de substitution Treatment on Substitution state Manipulación en estado por sustitución Manipulação em estado por Substituição Обработка статуса Substitution Treatment on Substitution state
Treatment on Suppression state Traitement sur l'état de suppression Treatment on Suppression state Manipulación en estado por supresión Manipulação em estado por Supressão Обработка статуса Suppression Treatment on Suppression state
Alarm and Gravity on Jammed state Gravité d'alarme sur l'état bloqué Alarm and Gravity on Jammed state Alarma y gravedad en estado bloqueado Alarme e gravidade em estado bloqueado Тревога и важность статуса Jammed Alarm and Gravity on Jammed state
Alarm and Gravity on Undefined state Gravité d'alarme sur l'état indéfini Alarm and Gravity on Undefined state Alarma y gravedad en estado Indefinido Alarme e gravidade em estado Indefinido Тревога и важность статуса Undefined Alarm and Gravity on Undefined state
Alarm and Gravity on Toggling state Gravité d'alarme sur l'état de basculement Alarm and Gravity on Toggling state Alarma y gravedad en estado en curso Alarme e gravidade em estado em Curso Тревога и важность статуса Toggling Alarm and Gravity on Toggling state
Alarm and Gravity on SelfCheckFault state Gravité d'alarme sur l'état d'auto vérification du défaut Alarm and Gravity on SelfCheckFault state Alarma y gravedad en estado FallaAutoChequeo Alarme e gravidade em estado FalhaAutoCheque Тревога и важность статуса SelfCheckFault Alarm and Gravity on SelfCheckFault state
Alarm and Gravity on Unknown state Gravité d'alarme sur l'état inconnu Alarm and Gravity on Unknown state Alarma y gravedad en estado desconocido Alarme e gravidade em estado Desconhecido Тревога и важность статуса Unknown Alarm and Gravity on Unknown state
Alarm and Gravity on Suppressed state Gravité d'alarme sur l'état supprimé Alarm and Gravity on Suppressed state Alarma y gravedad en estado Suprimido Alarme e gravidade em estado Suprimido Тревога и важность статуса Suppressed Alarm and Gravity on Suppressed state
Alarm and Gravity on Forced state Gravité d'alarme sur l'état forcé Alarm and Gravity on Forced state Alarma y gravedad en estado forzado Alarme e gravidade em estado Forçado Тревога и важность статуса Forced Alarm and Gravity on Forced state
Alarm and Gravity on Substituted state Gravité d'alarme sur l'état substitué Alarm and Gravity on Substituted state Alarma y gravedad en estado Sustituido Alarme e gravidade em estado Substituído Тревога и важность статуса Substituted Alarm and Gravity on Substituted state
Fugitive Alarm (Spurious) Alarme fugitive Fugitive Alarm (Spurious) Alarma fujitiva (Spurious) Alarme de Fuga(Spurious) Fugitive Alarm (Spurious) Fugitive Alarm (Spurious)
Masking due to control Masqué dû à la commande Masking due to control Enmascarar debido al control Mascarar devido ao controle Masking due to control Masking due to control
SBMC dependant Dépendance SBMC SBMC dependant SBMC dependiente SBMC dependente SBMC иждивенца SBMC unterhaltsberechtigte
Toggling filtering Basculement du filtrage Toggling filtering Curso de la filtración Curso de filtrar Toggling filtering Toggling filtering
Initial status Status initial Initial status Estado inicial Estado inicial Начальный статус Initial status
Forced Jammed Interlock Value Bloquage forcé des valeurs de l'interverrouillage Forced Jammed Interlock Value Bloqueado forzado valor de enclavamiento Bloqueado Forçado Valor de Intertravamento Значение блокировки Forced Jammed Forced Jammed Interlock Value
Forced Open Interlock Value Ouverture forcée des valeurs de l'interverrouillage Forced Open Interlock Value Abierto forzado valor de enclavamiento Aberto Forçado Valor de Intertravamento Значение блокировки Forced Open Forced Open Interlock Value
Forced Closed Interlock Value Fermeture forcée des valeurs de l'interverrouillage Forced Closed Interlock Value Cerrado forzado valor de enclavamiento Fechado Forçado Valor de Intertravamento Значение блокировки Forced Closed Forced Closed Interlock Value
Substituted Jammed Interlock Value Bloquage substitué des valeurs de l'interverrouillage Substituted Jammed Interlock Value Bloqueado Sustituido valor de enclavamiento Bloqueado Substituído Valor de Intertravamento Значение блокировки Substituted Jammed Substituted Jammed Interlock Value
Substituted Open Interlock Value Ouverture substituée des valeurs de l'interverrouillage Substituted Open Interlock Value Abierto Sustituido valor de enclavamiento Aberto Substituído Valor de Intertravamento Значение блокировки Substituted Open Substituted Open Interlock Value
Substituted Closed Interlock Value Fermeture substituée des valeurs de l'interverrouillage Substituted Closed Interlock Value Cerrado Sustituido valor de enclavamiento Fechado Substituído Valor de Intertravamento Значение блокировки Substituted Closed Substituted Closed Interlock Value
Suppressed interlock value Valeur de l'interverrouillage supprimé Suppressed interlock value Valor de enclavamiento suprimido Valor de Intertravamento Suprimido Значение блокировки Suppressed Suppressed interlock value
Unknown interlock value Valeur de l'interverrouillage inconnu Unknown interlock value Valor de enclavamiento desconocido Valor de Intertravamento Desconhecido Значение блокировки Unknown Unknown interlock value
Toggling interlock value Valeur de l'interverrouillage de basculement Toggling interlock value Valor de enclavamiento curso Valor de Intertravamento Curso Значение блокировки Toggling Toggling interlock value
SelfCheckFault interlock value Valeur de l'interverrouillage sur l'auto vérification du défaut SelfCheckFault interlock value Valor de enclavamiento FallaAutoChequeo Valor de Intertravamento FalhaAutoCheque Значение блокировки SelfCheckFaul SelfCheckFault interlock value
Undefined interlock value Valeur de l'interverrouillage indéfini Undefined interlock value Valor de enclavamiento indefinido Valor de Intertravamento Indefinido Значение блокировки Undefined Undefined interlock value
Default State labels Valeurs par défaut des Etats électriques Default State labels Por defecto las etiquetas de estado Estado padrão rótulos По умолчанию состояние этикетки Default State labels
Default Text at electrical state = 10 (16 char) Texte par défaut à l'état électrique = 10 (16 car) Default Text at electrical state = 10 (16 char) Texto predeterminado en estado eléctrico = 10 (16 caract) Texto padrão em estado Elétrico = 10 (16 caract) умолчанию текст электрического состояния = 10 (16 символов) Default Text at electrical state = 10 (16 char)
Default Text at electrical state = 01 (16 char) Texte par défaut à l'état électrique = 01 (16 car) Default Text at electrical state = 01 (16 char) Texto predeterminado en estado eléctrico = 01 (16 caract) Texto padrão em estado Elétrico = 01 (16 caract) умолчанию текст электрического состояния = 01 (16 символов) Default Text at electrical state = 01 (16 char)
Enable FSS (forcing / substituting / suppressing) Activer le FSS (forçage / substitution / suppression) Enable FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) позволить FSS (forcing / substituting / suppressing) Enable FSS (forcing / substituting / suppressing)
Multiple Digital Inputs Profiles Profils des entrées numériques multiples (MPS) Multiple Digital Inputs Profiles Perfiles de entradas digitales Múltiples Perfis de Entradas digitais Múltiplas Профили множественных DI Multiple Digital Inputs Profiles
Multiple System Digital Inputs Profiles Profils des entrées numériques systèmes multiples (MPS) Multiple System Digital Inputs Profiles Perfiles de systema de entradas digitales Múltiples Perfis de Systema de Entradas Digitais Múltiplas Профили множественных системных DI Multiple System Digital Inputs Profiles
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
MPS General Parameters Paramètres généraux de la MPS MPS General Parameters Parámetros generales MPS Parâmetros Geração MPS Основные параметры MPS MPS General Parameters
Generation Condition Condition de la Génération Generation Condition Condición de generación Condição de Geração Основное условие Generation Condition
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
MPS Printing Parameters Paramètres d'impression de la MPS MPS Printing Parameters Parámetros de impresión MPS Parâmetros de Impressão MPS Параметры печати MPS MPS Printing Parameters
Printed on Sequence Of Events SOE 1 : Imprimer sur l'imprimante Fil de l'eau 1 : Printed on Sequence Of Events SOE 1 : Impreso en SOE 1 : Impresso em SOE 1 : Вывод на SOE 1 : Printed on Sequence Of Events SOE 1 :
Printed on Sequence Of Events SOE 2 : Imprimer sur l'imprimante Fil de l'eau 2 : Printed on Sequence Of Events SOE 2 : Impreso en SOE 2 : Impresso em SOE 1 : Вывод на SOE 2 : Printed on Sequence Of Events SOE 2 :
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
MPS Interlocking Parameters Paramètres d'Interverrouillage de la MPS MPS Interlocking Parameters Parámetros de enclavamiento MPS Parâmetros de Intertravamento MPS Параметры блокировки MPS MPS Interlocking Parameters
State 0 Interlock Value Valeur de l'interverrouillage à l'état 0 State 0 Interlock Value Valor de enclavamiento estado 0 Valor de Intertravamento estado 0 Состояние 0 значения блокировки State 0 Interlock Value
State 1 Interlock Value Valeur de l'interverrouillage à l'état 1 State 1 Interlock Value Valor de enclavamiento estado 1 Valor de Intertravamento estado 1 Состояние 1 значения блокировки State 1 Interlock Value
State 2 Interlock Value Valeur de l'interverrouillage à l'état 2 State 2 Interlock Value Valor de enclavamiento estado 2 Valor de Intertravamento estado 2 Состояние 2 значения блокировки State 2 Interlock Value
State 3 Interlock Value Valeur de l'interverrouillage à l'état 3 State 3 Interlock Value Valor de enclavamiento estado 3 Valor de Intertravamento estado 3 Состояние 3 значения блокировки State 3 Interlock Value
State 4 Interlock Value Valeur de l'interverrouillage à l'état 4 State 4 Interlock Value Valor de enclavamiento estado 4 Valor de Intertravamento estado 4 Состояние 4 значения блокировки State 4 Interlock Value
State 5 Interlock Value Valeur de l'interverrouillage à l'état 5 State 5 Interlock Value Valor de enclavamiento estado 5 Valor de Intertravamento estado 5 Состояние 5 значения блокировки State 5 Interlock Value
State 6 Interlock Value Valeur de l'interverrouillage à l'état 6 State 6 Interlock Value Valor de enclavamiento estado 6 Valor de Intertravamento estado 6 Состояние 6 значения блокировки State 6 Interlock Value
State 7 Interlock Value Valeur de l'interverrouillage à l'état 7 State 7 Interlock Value Valor de enclavamiento estado 7 Valor de Intertravamento estado 7 Состояние 7 значения блокировки State 7 Interlock Value
State 8 Interlock Value Valeur de l'interverrouillage à l'état 8 State 8 Interlock Value Valor de enclavamiento estado 8 Valor de Intertravamento estado 8 Состояние 8 значения блокировки State 8 Interlock Value
State 9 Interlock Value Valeur de l'interverrouillage à l'état 9 State 9 Interlock Value Valor de enclavamiento estado 9 Valor de Intertravamento estado 9 Состояние 9 значения блокировки State 9 Interlock Value
State 10 Interlock Value Valeur de l'interverrouillage à l'état 10 State 10 Interlock Value Valor de enclavamiento estado 10 Valor de Intertravamento estado 10 Состояние 10 значения блокировки State 10 Interlock Value
State 11 Interlock Value Valeur de l'interverrouillage à l'état 11 State 11 Interlock Value Valor de enclavamiento estado 11 Valor de Intertravamento estado 11 Состояние 11 значения блокировки State 11 Interlock Value
State 12 Interlock Value Valeur de l'interverrouillage à l'état 12 State 12 Interlock Value Valor de enclavamiento estado 12 Valor de Intertravamento estado 12 Состояние 12 значения блокировки State 12 Interlock Value
State 13 Interlock Value Valeur de l'interverrouillage à l'état 13 State 13 Interlock Value Valor de enclavamiento estado 13 Valor de Intertravamento estado 13 Состояние 13 значения блокировки State 13 Interlock Value
State 14 Interlock Value Valeur de l'interverrouillage à l'état 14 State 14 Interlock Value Valor de enclavamiento estado 14 Valor de Intertravamento estado 14 Состояние 14 значения блокировки State 14 Interlock Value
State 15 Interlock Value Valeur de l'interverrouillage à l'état 15 State 15 Interlock Value Valor de enclavamiento estado 15 Valor de Intertravamento estado 15 Состояние 15 значения блокировки State 15 Interlock Value
MPS Processing Parameters Paramètres de traitement de la MPS MPS Processing Parameters Parámetros de procesamiento MPS Parâmetros de Processamento MPS Пораметры обработки MPS MPS Processing Parameters
State 0 label Libellé de l'état 0 State 0 label Etiqueta de estado 0 Etiqueta de estado 0 Состояние 0 метки State 0 label
State 1 label Libellé de l'état 1 State 1 label Etiqueta de estado 1 Etiqueta de estado 1 Состояние 1 метки State 1 label
State 2 label Libellé de l'état 2 State 2 label Etiqueta de estado 2 Etiqueta de estado 2 Состояние 2 метки State 2 label
State 3 label Libellé de l'état 3 State 3 label Etiqueta de estado 3 Etiqueta de estado 3 Состояние 3 метки State 3 label
State 4 label Libellé de l'état 4 State 4 label Etiqueta de estado 4 Etiqueta de estado 4 Состояние 4 метки State 4 label
State 5 label Libellé de l'état 5 State 5 label Etiqueta de estado 5 Etiqueta de estado 5 Состояние 5 метки State 5 label
State 6 label Libellé de l'état 6 State 6 label Etiqueta de estado 6 Etiqueta de estado 6 Состояние 6 метки State 6 label
State 7 label Libellé de l'état 7 State 7 label Etiqueta de estado 7 Etiqueta de estado 7 Состояние 7 метки State 7 label
State 8 label Libellé de l'état 8 State 8 label Etiqueta de estado 8 Etiqueta de estado 8 Состояние 8 метки State 8 label
State 9 label Libellé de l'état 9 State 9 label Etiqueta de estado 9 Etiqueta de estado 9 Состояние 9 метки State 9 label
State 10 label Libellé de l'état 10 State 10 label Etiqueta de estado 10 Etiqueta de estado 10 Состояние 10 метки State 10 label
State 11 label Libellé de l'état 11 State 11 label Etiqueta de estado 11 Etiqueta de estado 11 Состояние 11 метки State 11 label
State 12 label Libellé de l'état 12 State 12 label Etiqueta de estado 12 Etiqueta de estado 12 Состояние 12 метки State 12 label
State 13 label Libellé de l'état 13 State 13 label Etiqueta de estado 13 Etiqueta de estado 13 Состояние 13 метки State 13 label
State 14 label Libellé de l'état 14 State 14 label Etiqueta de estado 14 Etiqueta de estado 14 Состояние 14 метки State 14 label
State 15 label Libellé de l'état 15 State 15 label Etiqueta de estado 15 Etiqueta de estado 15 Состояние 15 метки State 15 label
Undefined state label Libellé de l'état indéfini Undefined state label Etiqueta de estado Indefinido Etiqueta de estado Indefinido Метка статуса Undefined Undefined state label
Toggling state label Libellé de l'état de basculement Toggling state label Etiqueta de estado en curso Etiqueta de estado em Curso Метка статуса Toggling Toggling state label
SelfCheckFault state label Libellé de l'état d'auto vérification du défaut SelfCheckFault state label Etiqueta de estado FallaAutoChequeo Etiqueta de estado FalhaAutoCheque Метка статуса SelfCheckFault SelfCheckFault state label
Unknown state label Libellé de l'état inconnu Unknown state label Etiqueta de estado desconocido Etiqueta de estado Desconhecido Метка статуса Unknown Unknown state label
Suppressed state label Libellé de l'état supprimé Suppressed state label Etiqueta de estado suprimido Etiqueta de estado Suprimido Метка статуса Suppressed Suppressed state label
Forced state label Libellé de l'état forcé Forced state label Etiqueta de estado forzado Etiqueta de estado Forçado Метка статуса Forced Forced state label
Substituted state label Libellé de l'état substitué Substituted state label Etiqueta de estado sustituido Etiqueta de estado Substituído Метка статуса Substituted Substituted state label
Treatment on state 0 Traitement sur l'état 0 Treatment on state 0 Manipulación en estado 0 Manipulação em estado 0 Обработка статуса 0 Treatment on state 0
Treatment on state 1 Traitement sur l'état 1 Treatment on state 1 Manipulación en estado 1 Manipulação em estado 1 Обработка статуса 1 Treatment on state 1
Treatment on state 2 Traitement sur l'état 2 Treatment on state 2 Manipulación en estado 2 Manipulação em estado 2 Обработка статуса 2 Treatment on state 2
Treatment on state 3 Traitement sur l'état 3 Treatment on state 3 Manipulación en estado 3 Manipulação em estado 3 Обработка статуса 3 Treatment on state 3
Treatment on state 4 Traitement sur l'état 4 Treatment on state 4 Manipulación en estado 4 Manipulação em estado 4 Обработка статуса 4 Treatment on state 4
Treatment on state 5 Traitement sur l'état 5 Treatment on state 5 Manipulación en estado 5 Manipulação em estado 5 Обработка статуса 5 Treatment on state 5
Treatment on state 6 Traitement sur l'état 6 Treatment on state 6 Manipulación en estado 6 Manipulação em estado 6 Обработка статуса 6 Treatment on state 6
Treatment on state 7 Traitement sur l'état 7 Treatment on state 7 Manipulación en estado 7 Manipulação em estado 7 Обработка статуса 7 Treatment on state 7
Treatment on state 8 Traitement sur l'état 8 Treatment on state 8 Manipulación en estado 8 Manipulação em estado 8 Обработка статуса 8 Treatment on state 8
Treatment on state 9 Traitement sur l'état 9 Treatment on state 9 Manipulación en estado 9 Manipulação em estado 9 Обработка статуса 9 Treatment on state 9
Treatment on state 10 Traitement sur l'état 10 Treatment on state 10 Manipulación en estado 10 Manipulação em estado 10 Обработка статуса 10 Treatment on state 10
Treatment on state 11 Traitement sur l'état 11 Treatment on state 11 Manipulación en estado 11 Manipulação em estado 11 Обработка статуса 11 Treatment on state 11
Treatment on state 12 Traitement sur l'état 12 Treatment on state 12 Manipulación en estado 12 Manipulação em estado 12 Обработка статуса 12 Treatment on state 12
Treatment on state 13 Traitement sur l'état 13 Treatment on state 13 Manipulación en estado 13 Manipulação em estado 13 Обработка статуса 13 Treatment on state 13
Treatment on state 14 Traitement sur l'état 14 Treatment on state 14 Manipulación en estado 14 Manipulação em estado 14 Обработка статуса 14 Treatment on state 14
Treatment on state 15 Traitement sur l'état 15 Treatment on state 15 Manipulación en estado 15 Manipulação em estado 15 Обработка статуса 15 Treatment on state 15
Treatment on Undefined state Traitement sur l'état indéfini Treatment on Undefined state Manipulación en estado Indefinido Manipulação em estado Indefinido Обработка статуса Undefined Treatment on Undefined state
Treatment on Toggling state Traitement sur l'état de basculement Treatment on Toggling state Manipulación en estado en curso Manipulação em estado em Curso Обработка статуса Toggling Treatment on Toggling state
Treatment on SelfCheckFault state Traitement sur l'état d'auto vérification du défaut Treatment on SelfCheckFault state Manipulación en estado FallaAutoChequeo Manipulação em estado FalhaAutoCheque Обработка статуса SelfCheckFault Treatment on SelfCheckFault state
Treatment on Unknown state Traitement sur l'état inconnu Treatment on Unknown state Manipulación en estado Desconocido Manipulação em estado Desconhecido Обрабока статуса Unknown Treatment on Unknown state
Treatment on Suppressed state Traitement sur l'état supprimé Treatment on Suppressed state Manipulación en estado Suprimido Manipulação em estado Suprimido Обработка статуса Suppressed Treatment on Suppressed state
Treatment on Forced state Traitement sur l'état forcé Treatment on Forced state Manipulación en estado Forzado Manipulação em estado Forçado Обработка статуса Forced Treatment on Forced state
Treatment on Substituted state Traitement sur l'état substitué Treatment on Substituted state Manipulación en estado sustituido Manipulação em estado Substituído Обработка статуса Substituted Treatment on Substituted state
Treatment on Forcing state Traitement sur l'état de forçage Treatment on Forcing state Manipulación en estado Forzando Manipulação em estado Forzando Обработка статуса Forcing Treatment on Forcing state
Treatment on Substitution state Traitement sur l'état de substitution Treatment on Substitution state Manipulación en estado por sustitución Manipulação em estado por Substituição Обработка статуса Substitution Treatment on Substitution state
Treatment on Suppression state Traitement sur l'état de suppression Treatment on Suppression state Manipulación en estado por supresión Manipulação em estado por Supressão Обработка статуса Suppression Treatment on Suppression state
Alarm and Gravity on state 0 Gravité d'alarme sur l'état 0 Alarm and Gravity on state 0 Alarma y gravedad en estado 0 Alarme e gravidade em estado 0 Тревога и важность статуса 0 Alarm and Gravity on state 0
Alarm and Gravity on state 1 Gravité d'alarme sur l'état 1 Alarm and Gravity on state 1 Alarma y gravedad en estado 1 Alarme e gravidade em estado 1 Тревога и важность статуса 1 Alarm and Gravity on state 1
Alarm and Gravity on state 2 Gravité d'alarme sur l'état 2 Alarm and Gravity on state 2 Alarma y gravedad en estado 2 Alarme e gravidade em estado 2 Тревога и важность статуса 2 Alarm and Gravity on state 2
Alarm and Gravity on state 3 Gravité d'alarme sur l'état 3 Alarm and Gravity on state 3 Alarma y gravedad en estado 3 Alarme e gravidade em estado 3 Тревога и важность статуса 3 Alarm and Gravity on state 3
Alarm and Gravity on state 4 Gravité d'alarme sur l'état 4 Alarm and Gravity on state 4 Alarma y gravedad en estado 4 Alarme e gravidade em estado 4 Тревога и важность статуса 4 Alarm and Gravity on state 4
Alarm and Gravity on state 5 Gravité d'alarme sur l'état 5 Alarm and Gravity on state 5 Alarma y gravedad en estado 5 Alarme e gravidade em estado 5 Тревога и важность статуса 5 Alarm and Gravity on state 5
Alarm and Gravity on state 6 Gravité d'alarme sur l'état 6 Alarm and Gravity on state 6 Alarma y gravedad en estado 6 Alarme e gravidade em estado 6 Тревога и важность статуса 6 Alarm and Gravity on state 6
Alarm and Gravity on state 7 Gravité d'alarme sur l'état 7 Alarm and Gravity on state 7 Alarma y gravedad en estado 7 Alarme e gravidade em estado 7 Тревога и важность статуса 7 Alarm and Gravity on state 7
Alarm and Gravity on state 8 Gravité d'alarme sur l'état 8 Alarm and Gravity on state 8 Alarma y gravedad en estado 8 Alarme e gravidade em estado 8 Тревога и важность статуса 8 Alarm and Gravity on state 8
Alarm and Gravity on state 9 Gravité d'alarme sur l'état 9 Alarm and Gravity on state 9 Alarma y gravedad en estado 9 Alarme e gravidade em estado 9 Тревога и важность статуса 9 Alarm and Gravity on state 9
Alarm and Gravity on state 10 Gravité d'alarme sur l'état 10 Alarm and Gravity on state 10 Alarma y gravedad en estado 10 Alarme e gravidade em estado 10 Тревога и важность статуса 10 Alarm and Gravity on state 10
Alarm and Gravity on state 11 Gravité d'alarme sur l'état 11 Alarm and Gravity on state 11 Alarma y gravedad en estado 11 Alarme e gravidade em estado 11 Тревога и важность статуса 11 Alarm and Gravity on state 11
Alarm and Gravity on state 12 Gravité d'alarme sur l'état 12 Alarm and Gravity on state 12 Alarma y gravedad en estado 12 Alarme e gravidade em estado 12 Тревога и важность статуса 12 Alarm and Gravity on state 12
Alarm and Gravity on state 13 Gravité d'alarme sur l'état 13 Alarm and Gravity on state 13 Alarma y gravedad en estado 13 Alarme e gravidade em estado 13 Тревога и важность статуса 13 Alarm and Gravity on state 13
Alarm and Gravity on state 14 Gravité d'alarme sur l'état 14 Alarm and Gravity on state 14 Alarma y gravedad en estado 14 Alarme e gravidade em estado 14 Тревога и важность статуса 14 Alarm and Gravity on state 14
Alarm and Gravity on state 15 Gravité d'alarme sur l'état 15 Alarm and Gravity on state 15 Alarma y gravedad en estado 15 Alarme e gravidade em estado 15 Тревога и важность статуса 15 Alarm and Gravity on state 15
Alarm and Gravity on Undefined state Gravité d'alarme sur l'état indéfini Alarm and Gravity on Undefined state Alarma y gravedad en estado Indefinido Alarme e gravidade em estado Indefinido Тревога и важность статуса Undefined Alarm and Gravity on Undefined state
Alarm and Gravity on Toggling state Gravité d'alarme sur l'état de basculement Alarm and Gravity on Toggling state Alarma y gravedad en estado en curso Alarme e gravidade em estado em Curso Тревога и важность статуса Toggling Alarm and Gravity on Toggling state
Alarm and Gravity on SelfCheckFault state Gravité d'alarme sur l'état d'auto vérification du défaut Alarm and Gravity on SelfCheckFault state Alarma y gravedad en estado FallaAutoChequeo Alarme e gravidade em estado FalhaAutoCheque Тревога и важность статуса SelfCheckFault Alarm and Gravity on SelfCheckFault state
Alarm and Gravity on Unknown state Gravité d'alarme sur l'état inconnu Alarm and Gravity on Unknown state Alarma y gravedad en estado desconocido Alarme e gravidade em estado Desconhecido Тревога и важность статуса Unknown Alarm and Gravity on Unknown state
Alarm and Gravity on Suppressed state Gravité d'alarme sur l'état supprimé Alarm and Gravity on Suppressed state Alarma y gravedad en estado Suprimido Alarme e gravidade em estado Suprimido Тревога и важность статуса Suppressed Alarm and Gravity on Suppressed state
Alarm and Gravity on Forced state Gravité d'alarme sur l'état forcé Alarm and Gravity on Forced state Alarma y gravedad en estado forzado Alarme e gravidade em estado Forçado Тревога и важность статуса Forced Alarm and Gravity on Forced state
Alarm and Gravity on Substituted state Gravité d'alarme sur l'état substitué Alarm and Gravity on Substituted state Alarma y gravedad en estado Sustituido Alarme e gravidade em estado Substituído Тревога и важность статуса Substituted Alarm and Gravity on Substituted state
Masking due to control Masqué dû à la commande Masking due to control Enmascarar debido al control Mascarar devido ao controle Masking due to control Masking due to control
SBMC dependant Dépendance SBMC SBMC dependant SBMC dependiente SBMC dependente SBMC иждивенца SBMC unterhaltsberechtigte
Suppressed interlock value Valeur de l'interverrouillage supprimé Suppressed interlock value Valor de enclavamiento suprimido Valor de Intertravamento Suprimido Значение блокировки Suppressed Suppressed interlock value
Unknown interlock value Valeur de l'interverrouillage inconnu Unknown interlock value Valor de enclavamiento desconocido Valor de Intertravamento Desconhecido Значение блокировки Unknown Unknown interlock value
Toggling interlock value Valeur de l'interverrouillage de basculement Toggling interlock value Valor de enclavamiento curso Valor de Intertravamento Curso Значение блокировки Toggling Toggling interlock value
SelfCheckFault interlock value Valeur de l'interverrouillage sur l'auto vérification du défaut SelfCheckFault interlock value Valor de enclavamiento FallaAutoChequeo Valor de Intertravamento FalhaAutoCheque Значение блокировки SelfCheckFaul SelfCheckFault interlock value
Undefined interlock value Valeur de l'interverrouillage indéfini Undefined interlock value Valor de enclavamiento indefinido Valor de Intertravamento Indefinido Значение блокировки Undefined Undefined interlock value
Enable FSS (forcing / substituting / suppressing) Activer le FSS (forçage / substitution / suppression) Enable FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) позволить FSS (forcing / substituting / suppressing) Enable FSS (forcing / substituting / suppressing)
Single Digital Outputs Profiles Profils sorties numériques simples (SPC) Single Digital Outputs Profiles Perfiles de salidas digitales sencillas Perfis de saidas Digitais Únicas Профили одинарных DO Single Digital Outputs Profiles
Single System Digital Outputs Profiles Profils sorties numériques systèmes simples (SPC) Single System Digital Outputs Profiles Perfiles de systema de salidas digitales sencillas Perfis de Systema de saidas Digitais Únicas Профили одинарных системных DO Single System Digital Outputs Profiles
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
SPC General Parameters Paramètres généraux de la SPC SPC General Parameters Parámetros generales SPC Parâmetros Geração SPC Основные параметры SPC SPC General Parameters
Activation Mode Mode d'activation Activation Mode Modo de activación Modo de Ativação Режим активации Activation Mode
SBO Mode Mode de sélection avant opération SBO Mode Modo SBO Modo SBO Режим SBO SBO Mode
SBO Timeout [0-600s] Temps d'expiration pour la sélection avant opération [0-600s] SBO Timeout [0-600s] Tiempo fuera SBO [0-600s] Falha SBO [0-600s] Задержка SBO [0-600 с] SBO Timeout [0-600s]
Execution timeout (if any) [0..6000000] (x100ms) Temps d'expiration de l'exécution (si présent) [0..6000000] (x100ms) Execution timeout (if any) [0..6000000] (x100ms) Tiempo fuera de ejecución (si existe) [0..6000000] (x100ms) Falha de execução (se existe) [0..6000000] (x100ms) Задержка выполнения (если есть) [0..6000000] (х100 мс) Execution timeout (if any) [0..6000000] (x100ms)
NACK Alarm Parameters Paramètres NACK d'alarme NACK Alarm Parameters Parámetros de alarmas NACK Parâmetros de Alarmes NACK Параметры тревоги NACK NACK Alarm Parameters
Alarmed on Negative Ack state Etat de l'alarme sur réception négative Alarmed on Negative Ack state Alarmado en estado de adquisición negativo Alarme em estado de aquisição negativo Сигнализация на неподтвержденный статус Alarmed on Negative Ack state
Treatment on Negative Ack state Etat du Traitement sur réception Négative Treatment on Negative Ack state Manipulación en estado adquisición negativo Manipulação em estado de aquisição negativo Обработка неподтверденного статуса Treatment on Negative Ack state
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
Usage Parameters Paramètres d'Utilisation Usage Parameters Parámetros del Uso Parâmetros do Uso Параметры Usage Usage Parameters
Off Usage Valeur "Off" d'utilisation Off Usage Valor uso 'Off' Valor Uso 'Off' Значение Usage Off Off Usage
On Usage Valeur "On" d'utilisation On Usage Valor uso 'On' Valor Uso 'On' Значения Usage On On Usage
Interlocking Parameters Paramètres d'Interverrouillage Interlocking Parameters Parámetros de enclavamiento Parâmetros de Intertravamento Параметры блокировки Interlocking Parameters
Off Interlock Value Valeur "Off" de l'interverrouillage Off Interlock Value Valor enclavamiento 'Off' Valor Intertravamento 'Off' Значение блокировки Off Off Interlock Value
On Interlock Value Valeur "On" de l'interverrouillage On Interlock Value Valor enclavamiento 'On' Valor Intertravamento 'On' Значение блокировки On On Interlock Value
Order on duration (ms) Durée de l'ordre (ms) Order on duration (ms) Duración de 'Order on' (ms) Duração de 'Order on' (ms) Продолжительность 'Order on' (mc) Order on duration (ms)
Hold duration (ms) Durée de maintien (ms) Hold duration (ms) Duración de 'Hold' (ms) Duração de 'Hold' (ms) Продолжительность 'Hold' (mc) Hold duration (ms)
SPC Printing Parameters Paramètres d'impression de la SPC SPC Printing Parameters Parámetros de impresión SPC Parâmetros de Impressão SPC Параметры печати SPC SPC Printing Parameters
Printed on Sequence Of Events SOE 1 : Imprimer sur l'imprimante Fil de l'eau 1 : Printed on Sequence Of Events SOE 1 : Impreso en SOE 1 : Impresso em SOE 1 : Вывод на SOE 1 : Printed on Sequence Of Events SOE 1 :
Printed on Sequence Of Events SOE 2 : Imprimer sur l'imprimante Fil de l'eau 2 : Printed on Sequence Of Events SOE 2 : Impreso en SOE 2 : Impresso em SOE 1 : Вывод на SOE 2 : Printed on Sequence Of Events SOE 2 :
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
Default State labels Valeurs par défaut des Etats électriques Default State labels Por defecto las etiquetas de estado Estado padrão rótulos По умолчанию состояние этикетки Default State labels
Default Text at electrical state = 1 (16 char) Texte par défaut à l'état électrique = 1 (16 car) Default Text at electrical state = 1 (16 char) Texto predeterminado en estado eléctrico = 1 (16 caract) Texto padrão em estado Elétrico = 1 (16 caract) умолчанию текст электрического состояния = 1 (16 символов) Default Text at electrical state = 1 (16 char)
Default Text at electrical state = 0 (16 char) Texte par défaut à l'état électrique = 0 (16 car) Default Text at electrical state = 0 (16 char) Texto predeterminado en estado eléctrico = 0 (16 caract) Texto padrão em estado Elétrico = 0 (16 caract) умолчанию текст электрического состояния = 0 (16 символов) Default Text at electrical state = 0 (16 char)
Double Digital Outputs Profiles Profils des sorties numériques doubles (DPC) Double Digital Outputs Profiles Perfiles de salidas digitales dobles Perfis de saidas Digitais Duplas Профили двоичных DO Double Digital Outputs Profiles
Double System Digital Outputs Profiles Profils des sorties numériques systèmes doubles (DPC) Double System Digital Outputs Profiles Perfiles de systema de salidas digitales dobles Perfis de Systema de saidas Digitais Duplas Профили двоичных системных DO Double System Digital Outputs Profiles
Default State labels Valeurs par défaut des Etats électriques Default State labels Por defecto las etiquetas de estado Estado padrão rótulos По умолчанию состояние этикетки Default State labels
Default Text at electrical state = 10 (16 char) Texte par défaut à l'état électrique = 10 (16 car) Default Text at electrical state = 10 (16 char) Texto predeterminado en estado eléctrico = 10 (16 caract) Texto padrão em estado Elétrico = 10 (16 caract) умолчанию текст электрического состояния = 10 (16 символов) Default Text at electrical state = 10 (16 char)
Default Text at electrical state = 01 (16 char) Texte par défaut à l'état électrique = 01 (16 car) Default Text at electrical state = 01 (16 char) Texto predeterminado en estado eléctrico = 01 (16 caract) Texto padrão em estado Elétrico = 01 (16 caract) умолчанию текст электрического состояния = 01 (16 символов) Default Text at electrical state = 01 (16 char)
DPC Printing Parameters Paramètres d'impression de la DPC DPC Printing Parameters Parámetros de impresión DPC Parâmetros de Impressão DPC Параметры печати DPC DPC Printing Parameters
Printed on Sequence Of Events SOE 1 : Imprimer sur l'imprimante Fil de l'eau 1 : Printed on Sequence Of Events SOE 1 : Impreso en SOE 1 : Impresso em SOE 1 : Вывод на SOE 1 : Printed on Sequence Of Events SOE 1 :
Printed on Sequence Of Events SOE 2 : Imprimer sur l'imprimante Fil de l'eau 2 : Printed on Sequence Of Events SOE 2 : Impreso en SOE 2 : Impresso em SOE 1 : Вывод на SOE 2 : Printed on Sequence Of Events SOE 2 :
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
Open duration (ms) Durée d'ouverture (ms) Open duration (ms) Duración de 'Open' (ms) Duração de 'Open' (ms) Продолжительность 'Open' (mc) Open duration (ms)
Close duration (ms) Durée de fermeture (ms) Close duration (ms) Duración de 'Close' (ms) Duração de 'Close' (ms) Продолжительность 'Close' (mc) Close duration (ms)
Hold duration (ms) Durée de maintien (ms) Hold duration (ms) Duración de 'Hold' (ms) Duração de 'Hold' (ms) Продолжительность 'Hold' (mc) Hold duration (ms)
Usage Parameters Paramètres d'Utilisation Usage Parameters Parámetros del Uso Parâmetros do Uso Параметры Usage Usage Parameters
Open Usage 01 Valeur "Ouvert" d'utilisation 01 Open Usage 01 Valor uso 'Open' 01 Valor Uso 'Open' 01 Значение Usage 'Open' 01 Open Usage 01
Close Usage 10 Valeur "Fermé" d'utilisation 10 Close Usage 10 Valor uso 'Close' 10 Valor Uso 'Close' 10 Значения Usage 'Close' 10 Close Usage 10
Interlocking Parameters Paramètres d'Interverrouillage Interlocking Parameters Parámetros de enclavamiento Parâmetros de Intertravamento Параметры блокировки Interlocking Parameters
Open Interlock Value 01 Valeur "Ouvert" de l'interverrouillage 01 Open Interlock Value 01 Valor enclavamiento 'Open' 01 Valor Intertravamento 'Open' 01 Значение блокировки 'Open' 01 Open Interlock Value 01
Close Interlock Value 10 Valeur "Fermé" de l'interverrouillage 10 Close Interlock Value 10 Valor enclavamiento 'Close' 10 Valor Intertravamento 'Close' 10 Значение блокировки 'Close' 10 Close Interlock Value 10
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
DPC General Parameters Paramètres généraux de la DPC DPC General Parameters Parámetros generales DPC Parâmetros Geração DPC Основные параметры DPC DPC General Parameters
Activation Mode Mode d'activation Activation Mode Modo de activación Modo de Ativação Режим активации Activation Mode
SBO Mode Mode de sélection avant opération SBO Mode Modo SBO Modo SBO Режим SBO SBO Mode
SBO Timeout [0-600s] Temps d'expiration pour la sélection avant opération [0-600s] SBO Timeout [0-600s] Tiempo fuera SBO [0-600s] Falha SBO [0-600s] Задержка SBO [0-600 с] SBO Timeout [0-600s]
Execution timeout (if any) [0..6000000] (x100ms) Temps d'expiration de l'exécution (si présent) [0..6000000] (x100ms) Execution timeout (if any) [0..6000000] (x100ms) Tiempo fuera de ejecución (si existe) [0..6000000] (x100ms) Falha de execução (se existe) [0..6000000] (x100ms) Задержка выполнения (если есть) [0..6000000] (х100 мс) Execution timeout (if any) [0..6000000] (x100ms)
NACK Alarm Parameters Paramètres NACK d'alarme NACK Alarm Parameters Parámetros de alarmas NACK Parâmetros de Alarmes NACK Параметры тревоги NACK NACK Alarm Parameters
Alarmed on Negative Ack state Etat de l'alarme sur réception négative Alarmed on Negative Ack state Alarmado en estado de adquisición negativo Alarme em estado de aquisição negativo Сигнализация на неподтвержденный статус Alarmed on Negative Ack state
Treatment on Negative Ack state Etat du Traitement sur réception Négative Treatment on Negative Ack state Manipulación en estado adquisición negativo Manipulação em estado de aquisição negativo Обработка неподтверденного статуса Treatment on Negative Ack state
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
System SetPoint Profiles Profils SetPoint systèmes System SetPoint Profiles Perfiles de systema de SetPoint Perfis de Systema de SetPoint Профили системных SetPoint System SetPoint Profiles
SetPoint Profiles Profils SetPoint SetPoint Profiles Perfiles de SetPoint Perfis de SetPoint Профили SetPoint SetPoint Profiles
SetPoint Printing Parameters Paramètres d'impression de la SetPoint SetPoint Printing Parameters Parámetros de impresión SetPoint Parâmetros de Impressão SetPoint Параметры печати SetPoint SetPoint Printing Parameters
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
SetPoint General Parameters Paramètres généraux du SetPoint SetPoint General Parameters Parámetros generales SetPoint Parâmetros Geração SetPoint Основные параметры SetPoint SetPoint General Parameters
Activation Mode Mode d'activation Activation Mode Modo de activación Modo de Ativação Режим активации Activation Mode
SBO Mode Mode de sélection avant opération SBO Mode Modo SBO Modo SBO Режим SBO SBO Mode
SBO Timeout [0-600s] Temps d'expiration pour la sélection avant opération [0-600s] SBO Timeout [0-600s] Tiempo fuera SBO [0-600s] Falha SBO [0-600s] Задержка SBO [0-600 с] SBO Timeout [0-600s]
Execution timeout (if any) [0..6000000] (x100ms) Temps d'expiration de l'exécution (si présent) [0..6000000] (x100ms) Execution timeout (if any) [0..6000000] (x100ms) Tiempo fuera de ejecución (si existe) [0..6000000] (x100ms) Falha de execução (se existe) [0..6000000] (x100ms) Задержка выполнения (если есть) [0..6000000] (х100 мс) Execution timeout (if any) [0..6000000] (x100ms)
NACK Alarm Parameters Paramètres NACK d'alarme NACK Alarm Parameters Parámetros de alarmas NACK Parâmetros de Alarmes NACK Параметры тревоги NACK NACK Alarm Parameters
Alarmed on Negative Ack state Etat de l'alarme sur réception négative Alarmed on Negative Ack state Alarmado en estado de adquisición negativo Alarme em estado de aquisição negativo Сигнализация на неподтвержденный статус Alarmed on Negative Ack state
Treatment on Negative Ack state Etat du Traitement sur réception Négative Treatment on Negative Ack state Manipulación en estado adquisición negativo Manipulação em estado de aquisição negativo Обработка неподтверденного статуса Treatment on Negative Ack state
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
Measurement Profiles Profils analogiques Measurement Profiles Perfiles de mediciones Perfis de Medições Профили измерений Measurement Profiles
Measurement System Profiles Profils systèmes analogiques Measurement System Profiles Perfiles de systema de mediciones Perfis de Systema de Medições Профили системных измерений Measurement System Profiles
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
MV General Parameters Paramètres généraux de la MV MV General Parameters Parámetros generales MV Parâmetros Geração MV Основные параметры MV MV General Parameters
Number of decimal for display [0-4] Nombre de décimales pour l'affichage [0-4] Number of decimal for display [0-4] Número de decimales para pantalla [0-4] Número de decimaoes para Display [0-4] Количество цифр на дисплее [0-4] Number of decimal for display [0-4]
Short Acquisition period (ms) [100 … 1000] step 100 Période d'acquisition courte (ms) [100 … 1000] pas de 100 Short Acquisition period (ms) [100 … 1000] step 100 Periodo de adquisición corto (ms) [100 … 1000] escalón 100 Periodo de aquisição Curto (ms) [100 … 1000] Escala 100 Короткий период опроса (мс) [100 … 1000] с шагом 100 Short Acquisition period (ms) [100 … 1000] step 100
Long Acquisition period (ms) [500 … 10000] step 500 Période d'acquisition longue (ms) [500 … 10000] pas de 500 Long Acquisition period (ms) [500 … 10000] step 500 Periodo de adquisición largo (ms) [500 … 10000] escalón 500 Periodo de aquisição Longo (ms) [500 … 10000] Escala 500 Длинный период опроса (мс) [500 … 10000] с шагом 500 Long Acquisition period (ms) [500 … 10000] step 500
3rd Low Threshold (no or % of full scale) 3eme seuil bas (non ou % de la pleine échelle) 3rd Low Threshold (no or % of full scale) 3er Umbral bajo (no o % de la escala completa) 3ro Limite Baixo (Nãoo % da escala completa) Третий нижний предел (отсутствует или % от полной шкалы) 3rd Low Threshold (no or % der Skalenendwerts)
2nd Low Threshold (no or % of full scale) 2eme seuil bas (non ou % de la pleine échelle) 2nd Low Threshold (no or % of full scale) 2do Umbral bajo (no o % de la escala completa) 2do Limite Baixo (Nãoo % da escala completa) Второй нижний предел (отсутствует или % от полной шкалы) 2nd Low Threshold (no or % der Skalenendwerts)
1st Low Threshold (no or % of full scale) 1er seuil bas (non ou % de la pleine échelle) 1st Low Threshold (no or % of full scale) 1er Umbral bajo (no o % de la escala completa) 1ro Limite Baixo (Nãoo % da escala completa) Первый нижний предел (отсутствует или % от полной шкалы) 1st Low Threshold (no or % der Skalenendwerts)
1st High Threshold (no or % of full scale) 1er seuil haut (non ou % de la pleine échelle) 1st High Threshold (no or % of full scale) 1er Umbral alto (no o % de la escala completa) 1ro Limite Alto (Nãoo % da escala completa) Первый верхний предел (отсутствует или % от полной шкалы) 1st High Threshold (no or % der Skalenendwerts)
2nd High Threshold (no or % of full scale) 2em seuil haut (non ou % de la pleine échelle) 2nd High Threshold (no or % of full scale) 2do Umbral alto (no o % de la escala completa) 2do Limite Alto (Nãoo % da escala completa) Второй верхний предел (отсутствует или % от полной шкалы) 2nd High Threshold (no or % der Skalenendwerts)
3rd High Threshold (no or % of full scale) 3eme seuil haut(non ou % de la pleine échelle) 3rd High Threshold (no or % of full scale) 3er Umbral alto (no o % de la escala completa) 3ro Limite Alto (Nãoo % da escala completa) Третий верхний предел (отсутствует или % от полной шкалы) 3rd High Threshold (no or % der Skalenendwerts)
Scaling Graduation Scaling Escala Graduação Шкалирование Scaling
Number of Slopes [1-20] Nombres de pentes [1-20] Number of Slopes [1-20] Número de escalones [1-20] Número de Escala [1-20] Количество кривых c разным наклоном [1-20] Number of Slopes [1-20]
Associated Alarm Parameters Paramètres d'alarme associés à la MV Associated Alarm Parameters Associated Alarm Parameters Associated aoarm Parameters Параметры тревоги Associated Alarm Parameters
Generation Condition Condition de la Génération Generation Condition Condición de generación Condição de Geração Основное условие Generation Condition
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
MV Processing Parameters Paramètres de traitement de la MV MV Processing Parameters Parámetros de procesamiento MV Parâmetros de Processamento MV Пораметры обработки MV MV Processing Parameters
Valid state label Libellé de l'état valide Valid state label Etiqueta de estado válido Etiqueta de estado válido Метка статуса Valid Valid state label
SelfCheckFault state label Libellé de l'état d'auto vérification du défaut SelfCheckFault state label Etiqueta de estado FallaAutoChequeo Etiqueta de estado FalhaAutoCheque Метка статуса SelfCheckFault SelfCheckFault state label
Unknown state label Libellé de l'état inconnu Unknown state label Etiqueta de estado desconocido Etiqueta de estado Desconhecido Метка статуса Unknown Unknown state label
Suppressed state label Libellé de l'état supprimé Suppressed state label Etiqueta de estado suprimido Etiqueta de estado Suprimido Метка статуса Suppressed Suppressed state label
Forced state label Libellé de l'état forcé Forced state label Etiqueta de estado forzado Etiqueta de estado Forçado Метка статуса Forced Forced state label
Substituted state label Libellé de l'état substitué Substituted state label Etiqueta de estado sustituido Etiqueta de estado Substituído Метка статуса Substituted Substituted state label
OverRange state label Libellé de l'état au-dessus de l'échelle OverRange state label Etiqueta de estado fuera de rango Etiqueta de estado fora de Range Метка статуса OverRange OverRange state label
Undefined state label Libellé de l'état indéfini Undefined state label Etiqueta de estado Indefinido Etiqueta de estado Indefinido Метка статуса Undefined Undefined state label
OpenCircuit state label Libellé de l'état circuit ouvert OpenCircuit state label Etiqueta de estado circuito abierto Etiqueta de estado circuito Aberto Метка статуса OpenCircuit OpenCircuit state label
LLL Threshold state label Libellé de l'état seuil LLL LLL Threshold state label Etiqueta de estado umbral LLL Etiqueta de estado Limite LLL Метка статуса LLL Threshold LLL Threshold state label
LL Threshold state label Libellé de l'état seuil LL LL Threshold state label Etiqueta de estado umbral LL Etiqueta de estado Limite LL Метка статуса LL Threshold LL Threshold state label
L Threshold state label Libellé de l'état seuil L L Threshold state label Etiqueta de estado umbral L Etiqueta de estado Limite L Метка статуса L Threshold L Threshold state label
H Threshold state label Libellé de l'état seuil H H Threshold state label Etiqueta de estado umbral H Etiqueta de estado Limite H Метка статуса H Threshold H Threshold state label
HH Threshold state label Libellé de l'état seuil HH HH Threshold state label Etiqueta de estado umbral HH Etiqueta de estado Limite HH Метка статуса HH Threshold HH Threshold state label
HHH Threshold state label Libellé de l'état seuil HHH HHH Threshold state label Etiqueta de estado umbral HHH Etiqueta de estado Limite HHH Метка статуса HHH Threshold HHH Threshold state label
Treatment on Valid state Traitement sur l'état valide Treatment on Valid state Manipulación en estado válido Manipulação em estado válido Обработка статуса Valid Treatment on Valid state
Treatment on SelfCheckFault state Traitement sur l'état d'auto vérification du défaut Treatment on SelfCheckFault state Manipulación en estado FallaAutoChequeo Manipulação em estado FalhaAutoCheque Обработка статуса SelfCheckFault Treatment on SelfCheckFault state
Treatment on Unknown state Traitement sur l'état inconnu Treatment on Unknown state Manipulación en estado Desconocido Manipulação em estado Desconhecido Обрабока статуса Unknown Treatment on Unknown state
Treatment on Suppressed state Traitement sur l'état supprimé Treatment on Suppressed state Manipulación en estado Suprimido Manipulação em estado Suprimido Обработка статуса Suppressed Treatment on Suppressed state
Treatment on Forced state Traitement sur l'état forcé Treatment on Forced state Manipulación en estado Forzado Manipulação em estado Forçado Обработка статуса Forced Treatment on Forced state
Treatment on Substituted state Traitement sur l'état substitué Treatment on Substituted state Manipulación en estado sustituido Manipulação em estado Substituído Обработка статуса Substituted Treatment on Substituted state
Treatment on OverRange state Traitement sur l'état au-dessus de l'échelle Treatment on OverRange state Manipulación en estado fuera de rango Manipulação em estado fora de Range Обработка статуса OverRange Treatment on OverRange state
Treatment on Undefined state Traitement sur l'état indéfini Treatment on Undefined state Manipulación en estado Indefinido Manipulação em estado Indefinido Обработка статуса Undefined Treatment on Undefined state
Treatment on OpenCircuit state Traitement sur l'état circuit ouvert Treatment on OpenCircuit state Manipulación de estado en Circuito Abierto Manipulação de estado em Circuito Aberto Обработка статуса OpenCircuit Treatment on OpenCircuit state
Treatment on LLL Threshold state Traitement sur l'état LLL seuil Treatment on LLL Threshold state Manipualción de estado en umbral LLL Manipuaoción de estado em Limite LLL Обработка статуса LLL Threshold Treatment on LLL Threshold state
Treatment on LL Threshold state Traitement sur l'état LL seuil Treatment on LL Threshold state Manipulación de estado en umbral LL Manipulação de estado em Limite LL Обработка статуса LL Threshold Treatment on LL Threshold state
Treatment on L Threshold state Traitement sur l'état L seuil Treatment on L Threshold state Manipulación de estado en umbral L Manipulação de estado em Limite L Обработка статуса L Threshold Treatment on L Threshold state
Treatment on H Threshold state Traitement sur l'état H seuil Treatment on H Threshold state Manipulación de estado en umbral H Manipulação de estado em Limite H Обработка статуса Н Threshold Treatment on H Threshold state
Treatment on HH Threshold state Traitement sur l'état HH seuil Treatment on HH Threshold state Manipulación de estado en umbral HH Manipulação de estado em Limite HH Обработка статуса HH Threshold Treatment on HH Threshold state
Treatment on HHH Threshold state Traitement sur l'état HHH seuil Treatment on HHH Threshold state Manipulación de estado en umbral HHH Manipulação de estado em Limite HHH Обработка статуса HHH Threshold Treatment on HHH Threshold state
Valid interlock value Valeur de l'interverrouillage valide Valid interlock value Valor de enclavamiento válido Valor de Intertravamento válido Значение блокировки Valid Valid interlock value
SelfCheckFault interlock value Valeur de l'interverrouillage sur l'auto vérification du défaut SelfCheckFault interlock value Valor de enclavamiento FallaAutoChequeo Valor de Intertravamento FalhaAutoCheque Значение блокировки SelfCheckFaul SelfCheckFault interlock value
Unknown interlock value Valeur de l'interverrouillage inconnu Unknown interlock value Valor de enclavamiento desconocido Valor de Intertravamento Desconhecido Значение блокировки Unknown Unknown interlock value
Suppressed interlock value Valeur de l'interverrouillage supprimé Suppressed interlock value Valor de enclavamiento suprimido Valor de Intertravamento Suprimido Значение блокировки Suppressed Suppressed interlock value
Forced interlock value Valeur de l'interverrouillage forcé Forced interlock value Valor de enclavamiento forzado Valor de Intertravamento Forçado Значение блокировки Forced Forced interlock value
Substituted interlock value Valeur de l'interverrouillage substitué Substituted interlock value Valor de enclavamiento sustituido Valor de Intertravamento Substituído Значение блокировки Substituted Substituted interlock value
OverRange interlock value Valeur de l'interverrouillage au-dessus de l'échelle OverRange interlock value Valor de enclavamiento fuera de rango Valor de Intertravamento fora de Range Значение блокировки OverRange OverRange interlock value
Undefined interlock value Valeur de l'interverrouillage indéfini Undefined interlock value Valor de enclavamiento indefinido Valor de Intertravamento Indefinido Значение блокировки Undefined Undefined interlock value
OpenCircuit interlock value Valeur de l'interverrouillage circuit ouvert OpenCircuit interlock value Valor de enclavamiento Circuito Abierto Valor de Intertravamento Circuito Aberto Значение блокировки OpenCircuit OpenCircuit interlock value
LLL Threshold interlock value Valeur de l'interverrouillage seuil LLL LLL Threshold interlock value Valor de enclavamiento umbral LLL Valor de Intertravamento Limite LLL Значение блокировки LLL Threshold LLL Threshold interlock value
LL Threshold interlock value Valeur de l'interverrouillage seuil LL LL Threshold interlock value Valor de enclavamiento umbral LL Valor de Intertravamento Limite LL Значение блокировки LL Threshold LL Threshold interlock value
L Threshold interlock value Valeur de l'interverrouillage seuil L L Threshold interlock value Valor de enclavamiento umbral L Valor de Intertravamento Limite L Значение блокировки L Threshold L Threshold interlock value
H Threshold interlock value Valeur de l'interverrouillage seuil H H Threshold interlock value Valor de enclavamiento umbral H Valor de Intertravamento Limite H Значение блокировки H Threshold H Threshold interlock value
HH Threshold interlock value Valeur de l'interverrouillage seuil HH HH Threshold interlock value Valor de enclavamiento umbral HH Valor de Intertravamento Limite HH Значение блокировки HH Threshold HH Threshold interlock value
HHH Threshold interlock value Valeur de l'interverrouillage seuil HHH HHH Threshold interlock value Valor de enclavamiento umbral HHH Valor de Intertravamento Limite HHH Значение блокировки HHH Threshold HHH Threshold interlock value
Alarm and Gravity on Valid state Gravité d'alarme sur l'état valide Alarm and Gravity on Valid state Alarma y gravedad en estado valido Alarme e gravidade em estado vaoido Тревога и важность статуса Valid Alarm and Gravity on Valid state
Alarm and Gravity on SelfCheckFault state Gravité d'alarme sur l'état d'auto vérification du défaut Alarm and Gravity on SelfCheckFault state Alarma y gravedad en estado FallaAutoChequeo Alarme e gravidade em estado FalhaAutoCheque Тревога и важность статуса SelfCheckFault Alarm and Gravity on SelfCheckFault state
Alarm and Gravity on Unknown state Gravité d'alarme sur l'état inconnu Alarm and Gravity on Unknown state Alarma y gravedad en estado desconocido Alarme e gravidade em estado Desconhecido Тревога и важность статуса Unknown Alarm and Gravity on Unknown state
Alarm and Gravity on Suppressed state Gravité d'alarme sur l'état supprimé Alarm and Gravity on Suppressed state Alarma y gravedad en estado Suprimido Alarme e gravidade em estado Suprimido Тревога и важность статуса Suppressed Alarm and Gravity on Suppressed state
Alarm and Gravity on Forced state Gravité d'alarme sur l'état forcé Alarm and Gravity on Forced state Alarma y gravedad en estado forzado Alarme e gravidade em estado Forçado Тревога и важность статуса Forced Alarm and Gravity on Forced state
Alarm and Gravity on Substituted state Gravité d'alarme sur l'état substitué Alarm and Gravity on Substituted state Alarma y gravedad en estado Sustituido Alarme e gravidade em estado Substituído Тревога и важность статуса Substituted Alarm and Gravity on Substituted state
Alarm and Gravity on OverRange state Gravité d'alarme sur l'état au-dessus de l'échelle Alarm and Gravity on OverRange state Alarma y gravedad en estado fuera de rango Alarme e gravidade em estado fora de Range Тревога и важность статуса OverRange Alarm and Gravity on OverRange state
Alarm and Gravity on Undefined state Gravité d'alarme sur l'état indéfini Alarm and Gravity on Undefined state Alarma y gravedad en estado Indefinido Alarme e gravidade em estado Indefinido Тревога и важность статуса Undefined Alarm and Gravity on Undefined state
Alarm and Gravity on OpenCircuit state Gravité d'alarme sur l'état circuit ouvert Alarm and Gravity on OpenCircuit state Alarma y gravedad en estado circuito abierto Alarme e gravidade em estado Circuito Aberto Тревога и важность статуса OpenCircuit Alarm and Gravity on OpenCircuit state
Alarm and Gravity on LLL Threshold state Gravité d'alarme sur l'état de seuil LLL Alarm and Gravity on LLL Threshold state Alarma y gravedad en estado umbral LLL Alarme e gravidade em estado Limite LLL Тревога и важность статуса LLL Threshold Alarm and Gravity on LLL Threshold state
Alarm and Gravity on LL Threshold state Gravité d'alarme sur l'état de seuil LL Alarm and Gravity on LL Threshold state Alarma y gravedad en estado umbral LL Alarme e gravidade em estado Limite LL Тревога и важность статуса LL Threshold Alarm and Gravity on LL Threshold state
Alarm and Gravity on L Threshold state Gravité d'alarme sur l'état de seuil L Alarm and Gravity on L Threshold state Alarma y gravedad en estado umbral L Alarme e gravidade em estado Limite L Тревога и важность статуса L Threshold Alarm and Gravity on L Threshold state
Alarm and Gravity on H Threshold state Gravité d'alarme sur l'état de seuil H Alarm and Gravity on H Threshold state Alarma y gravedad en estado umbral H Alarme e gravidade em estado Limite H Тревога и важность статуса H Threshold Alarm and Gravity on H Threshold state
Alarm and Gravity on HH Threshold state Gravité d'alarme sur l'état de seuil HH Alarm and Gravity on HH Threshold state Alarma y gravedad en estado umbral HH Alarme e gravidade em estado Limite HH Тревога и важность статуса HH Threshold Alarm and Gravity on HH Threshold state
Alarm and Gravity on HHH Threshold state Gravité d'alarme sur l'état de seuil HHH Alarm and Gravity on HHH Threshold state Alarma y gravedad en estado umbral HHH Alarme e gravidade em estado Limite HHH Тревога и важность статуса HHH Threshold Alarm and Gravity on HHH Threshold state
Computation Calculé Computation Cómputación Computação Вычисление Computation
SBMC dependant Dépendance SBMC SBMC dependant SBMC dependiente SBMC dependente SBMC иждивенца SBMC unterhaltsberechtigte
Graphical Default Format Format graphique par défaut Graphical Default Format Formato gráfico del defecto Formato gráfico do defeito Стандартный графический формат Graphical Default Format
Transmission on Event Transmission sur événement Transmission on Event Transmisión en acontecimiento Transmissão no evento Передача события Transmission on Event
Deadband Bande morte Deadband Venda muerta Faixa muerta Порог чувствительности Deadband
MV Printing Parameters Paramètres d'impression de la MV MV Printing Parameters Parámetros de impresión MV Parâmetros de Impressão MV Параметры печати MV MV Printing Parameters
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
Enable FSS (forcing / substituting / suppressing) Activer le FSS (forçage / substitution / suppression) Enable FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) позволить FSS (forcing / substituting / suppressing) Enable FSS (forcing / substituting / suppressing)
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : System Information SHEET : Informations Systemes SHEET : System Information SHEET : System Information SHEET : System Information SHEET : Системная информация SHEET : System Information
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
SYSTEM INFORMATION DATA DESCRIPTION INFORMATION SYSTEME DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION ОПИСАНИЕ СИСТЕМНОЙ ИНФОРМАЦИИ SYSTEM INFORMATION DATA DESCRIPTION
Gateway Passerelle Gateway UTR UTR Шлюз Gateway
Port used (on gateway) Ports utilisés (sur la passerelle) Port used (on gateway) Puerto utilizado (en UTR) Porta utilizada (em UTR) Используемый порт (на шлюз) benutzter Port (Gateway)
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1
GE Reserved Réservé à GE GE Grid Reservado GE Reservado GE Зарезервировано GE GE Reserved
SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2
Auto generated Génération automatique Auto generated Auto generado Auto Geração Автоматически сгенерировано Auto generated
SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4
SYSTEM INFORMATION DATA DESCRIPTION INFORMATION SYSTEME DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION ОПИСАНИЕ СИСТЕМНОЙ ИНФОРМАЦИИ SYSTEM INFORMATION DATA DESCRIPTION
BAY OI Name : Nom de la BAIE OI : BAY OI Name : BAY OI Name : BAY OI Name : Имя BAY OI : BAY OI Name :
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels / States Libellés/Etats Labels / States Etiquetas/Estados Etiquetas/Estados Метки / Состояния Labels / States
Description Description Description Descripción Descrição Описание Beschreibung
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Groups Groupes Groups Grupos Grupos Группы Gruppen
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC 61850 Name : Nom de l'IEC 61850 : IEC 61850 Name : IEC 61850 Name : IEC 61850 Name : Имя IEC 61850 : IEC 61850 Name :
UCA2 IED Name : Nom de l'UCA2 IED : UCA2 IED Name : UCA2 IED Name : UCA2 IED Name : Имя UCA2 IED : UCA2 IED Name :
SERVER OI Name : Nom du SERVEUR d'E/S : SERVER OI Name : SERVER OI Name : SERVER OI Name : Имя сервера OI : SERVER OI Name :
CLIENT OI Name : Nom du CLIENT d'E/S : CLIENT OI Name : CLIENT OI Name : CLIENT OI Name : Имя клиента OI : CLIENT OI Name :
MiCOM C264 Name : Nom du MiCOM C264 : MiCOM C264 Name : MiCOM C264 Name : MiCOM C264 Name : Имя MiCOM C264 : MiCOM C264 Name :
GATEWAY Name : Nom de la PASSERELLE : GATEWAY Name : GATEWAY Name : GATEWAY Name : Имя шлюза : GATEWAY Name :
MiCOM C364 Name : Nom du MiCOM C364 : MiCOM C364 Name : MiCOM C364 Name : MiCOM C364 Name : Имя MiCOM C364 : MiCOM C364 Name :
SYSTEM INFORMATION GATEWAY INFORMATION SYSTEME PASSERELLE SYSTEM INFORMATION GATEWAY SYSTEM INFORMATION GATEWAY SYSTEM INFORMATION GATEWAY СИСТЕМНАЯ ИНФОРМАЦИЯ ПО ШЛЮЗУ SYSTEM INFORMATION GATEWAY
SYSTEM INFORMATION MiCOM C264 INFORMATION SYSTEME MiCOM C264 SYSTEM INFORMATION MiCOM C264 SYSTEM INFORMATION MiCOM C264 SYSTEM INFORMATION MiCOM C264 СИСТЕМНАЯ ИНФОРМАЦИЯ ПО MiCOM C264 SYSTEM INFORMATION MiCOM C264
SYSTEM INFORMATION MiCOM C364 INFORMATION SYSTEME MiCOM C364 SYSTEM INFORMATION MiCOM C364 SYSTEM INFORMATION MiCOM C364 SYSTEM INFORMATION MiCOM C364 СИСТЕМНАЯ ИНФОРМАЦИЯ ПО MiCOM C364 SYSTEM INFORMATION MiCOM C364
SYSTEM INFORMATION CLIENT OI INFORMATION SYSTEME CLIENT E/S SYSTEM INFORMATION CLIENT OI SYSTEM INFORMATION CLIENT OI SYSTEM INFORMATION CLIENT OI СИСТЕМНАЯ ИНФОРМАЦИЯ ПО КЛИЕНТУ OI SYSTEM INFORMATION CLIENT OI
SYSTEM INFORMATION SERVER OI INFORMATION SYSTEME SERVER E/S SYSTEM INFORMATION SERVER OI SYSTEM INFORMATION SERVER OI SYSTEM INFORMATION SERVER OI СИСТЕМНАЯ ИНФОРМАЦИЯ ПО СЕРВЕРУ OI SYSTEM INFORMATION SERVER OI
SYSTEM INFORMATION UCA2 IED INFORMATION SYSTEME UCA2 IED SYSTEM INFORMATION UCA2 IED SYSTEM INFORMATION UCA2 IED SYSTEM INFORMATION UCA2 IED СИСТЕМНАЯ ИНФОРМАЦИЯ ПО UCA2 IED SYSTEM INFORMATION UCA2 IED
SYSTEM INFORMATION IEC 61850 INFORMATION SYSTEME IEC 61850 SYSTEM INFORMATION IEC 61850 SYSTEM INFORMATION IEC 61850 SYSTEM INFORMATION IEC 61850 СИСТЕМНАЯ ИНФОРМАЦИЯ ПО IEC 61850 SYSTEM INFORMATION IEC 61850
SYSTEM INFORMATION BAY OI INFORMATION SYSTEME BAIE OI SYSTEM INFORMATION BAY OI SYSTEM INFORMATION BAY OI SYSTEM INFORMATION BAY OI СИСТЕМНАЯ ИНФОРМАЦИЯ ПО BAY OI SYSTEM INFORMATION BAY OI
Issue Révision Issue Revisión Revisão Версия Version
Equipment Link Lien Equipement Equipment Link Acoplamiento del equipo Ligação do equipamento Оборудование связи Equipment Link
Function Fonction Function Función Função Функция Function
Type Type Type Type Type Type Type
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 Multiple : pas utilisé MV : pas utilisé (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 Множественный: не используется MV : Не используется (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique =01 Multiple : pas utilisé MV : pas utilisé (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 Множественный: не используется MV : Не используется (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
Computers Groups (separator ";") Groupes de calculateur (séparateur ";") Computers Groups (separator ";") Grupos de Computadoras (separador ";") Grupos de Computadores (separador ";") Группы контроллеров (разделитель ";") Computers Gruppen (separator ";")
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
LED MV : Not used LED MV : Non utilisé LED MV : Not used LED MV : Not used LED MV : Not used Индикатор MV : Не используется LED MV : Not used
xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : Affichage LCD xPC : Contrôle LCD MV : Affichage LCD xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : LCD Дисплей xPC : Управление LCD MV : LCD Дисплей xPS : LCD Display xPC : LCD Control MV : LCD Display
xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Affichage HMI xPC : Contrôle HMI MV : Affichage HMI xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : HMI Дисплей xPC : Управление HMI MV : HMI Дисплей xPS : HMI Display xPC : HMI Control MV : HMI Display
xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer xPS : Est un retour de position xPC xPC : Est activé par xPS MV : Archivé xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer xPS : активируется с помощью xPC xPC : активируется с помощью xPS MV : Просмотр кривых xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used xPS, MV : Est utilisé par la distribution automatique (GOOSE) xPC : Non utilisé xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used xPS, MV : Используется распределенной автоматикой (GOOSE) xPC : Не используется xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used
Datapoint Name (in SCE Template) Nom du Point de Donnée (dans le modèle du SCE) Datapoint Name (in SCE Template) Nombre del dato (en plantilla SCE) Nome do Dado (em Panilha SCE) Имя точки данных (в SCE шаблоне) Datapoint Name (in SCE Template)
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Agency status Etat agence Agency status Agency status Agency status Agency status Agency status
Auto archiving Archivage auto Auto archiving Auto archiving Auto archiving Auto archiving Auto archiving
AIU status AIU statut AIU status AIU status AIU status AIU status AIU status
AIU status AIU statut AIU status AIU status AIU status AIU status AIU status
Backup printer status Etat imprimante backup Backup printer status Backup printer status Backup printer status Backup printer status Backup printer status
BIU status BIU statut BIU status BIU status BIU status BIU status BIU status
CCU status CCU statut CCU status CCU status CCU status CCU status CCU status
Central archive Archive centrale Central archive Central archive Central archive Central archive Central archive
Device link Lien équipement Device link Device link Device link Device link Device link
SPS Communication with the IED SPS de communication avec l'IED SPS Communication with the IED SPS Communication with the IED SPS Communication with the IED SPS Communication with the IED SPS Communication with the IED
OI client link Lien client OI OI client link OI client link OI client link OI client link OI client link
Communication SPS with the SCADA SPS de communication avec le SCADA Communication SPS with the SCADA Communication SPS with the SCADA Communication SPS with the SCADA Communication SPS with the SCADA Communication SPS with the SCADA
Counter Top Top compteur Counter Top Counter Top Counter Top Counter Top Counter Top
UCA2 Coupling Couplage UCA2 UCA2 Coupling UCA2 Coupling UCA2 Coupling UCA2 Coupling UCA2 Coupling
DB incohency SPS SPS DB incohérente DB incohency SPS DB incohency SPS DB incohency SPS DB incohency SPS DB incohency SPS
DB switch control contrôle basculement BD DB switch control DB switch control DB switch control DB switch control DB switch control
DI acquisition stopped Acquisition DI arrêtée DI acquisition stopped DI acquisition stopped DI acquisition stopped DI acquisition stopped DI acquisition stopped
SPS disturbance file ready SPS fichier de perturbo prête SPS disturbance file ready SPS disturbance file ready SPS disturbance file ready SPS disturbance file ready SPS disturbance file ready
SPS disturbance file ready SPS fichier de perturbo prête SPS disturbance file ready SPS disturbance file ready SPS disturbance file ready SPS disturbance file ready SPS disturbance file ready
DIU status DIU statut DIU status DIU status DIU status DIU status DIU status
DOU status DOU statut DOU status DOU status DOU status DOU status DOU status
External clock status Etat horloge external External clock status External clock status External clock status External clock status External clock status
GHU status GHU statut GHU status GHU status GHU status GHU status GHU status
ISAGRAF status Etat ISAGRAF ISAGRAF status ISAGRAF status ISAGRAF status ISAGRAF status ISAGRAF status
Local/remote DPS DPS local/distant Local/remote DPS Local/remote DPS Local/remote DPS Local/remote DPS Local/remote DPS
Local/remote controlDPC DPC de contrôle Local/distant Local/remote controlDPC Local/remote controlDPC Local/remote controlDPC Local/remote controlDPC Local/remote controlDPC
Local/remote SPS SPS loc/distant Local/remote SPS Local/remote SPS Local/remote SPS Local/remote SPS Local/remote SPS
Log Queue File du log Log Queue Log Queue Log Queue Log Queue Log Queue
Main computer status MV MV état calculateur principal Main computer status MV Main computer status MV Main computer status MV Main computer status MV Main computer status MV
Device mode Mode équip. Device mode Device mode Device mode Device mode Device mode
Mode control DPC DPC de contrôle du mode Mode control DPC Mode control DPC Mode control DPC Mode control DPC Mode control DPC
Operating mode Mode exploitation Operating mode Operating mode Operating mode Operating mode Operating mode
Printer status DPS état imprimante Printer status Printer status Printer status Printer status Printer status
Redundancy change mode control contrôle changement mode redondance Redundancy change mode control Redundancy change mode control Redundancy change mode control Redundancy change mode control Redundancy change mode control
Redundancy change status Statut changt redondance Redundancy change status Redundancy change status Redundancy change status Redundancy change status Redundancy change status
Redundancy change status control Contrôle changement statut redond. Redundancy change status control Redundancy change status control Redundancy change status control Redundancy change status control Redundancy change status control
Redundancy mode Mode redondance Redundancy mode Redundancy mode Redundancy mode Redundancy mode Redundancy mode
Redundancy SPS SPS de Redondance Redundancy SPS Redundancy SPS Redundancy SPS Redundancy SPS Redundancy SPS
OI client Client OI OI client OI client OI client OI client OI client
Software error SPS SPS erreur logicielle Software error SPS Software error SPS Software error SPS Software error SPS Software error SPS
Synchronisation Synchronisation Synchronisation Synchronisation Synchronisation Synchronisation Synchronisation
IED SPS Synchronisation SPS de Synchronisation de l'IED IED SPS Synchronisation IED SPS Synchronisation IED SPS Synchronisation IED SPS Synchronisation IED SPS Synchronisation
Test control DPC DPC de control de test Test control DPC Test control DPC Test control DPC Test control DPC Test control DPC
TMU status TMU statut TMU status TMU status TMU status TMU status TMU status
Watchdog error SPS SPS erreur watchdog Watchdog error SPS Watchdog error SPS Watchdog error SPS Watchdog error SPS Watchdog error SPS
HBU status HBU statut HBU status HBU status HBU status HBU status HBU status
Agency status Etat agence Agency status Agency status Agency status Agency status Agency status
AIU status AIU statut AIU status AIU status AIU status AIU status AIU status
AIU status AIU statut AIU status AIU status AIU status AIU status AIU status
Auto archiving Archivage auto Auto archiving Auto archiving Auto archiving Auto archiving Auto archiving
BackupPrint stat Etat imp. backup BackupPrint stat BackupPrint stat BackupPrint stat BackupPrint stat BackupPrint stat
BIU status BIU statut BIU status BIU status BIU status BIU status BIU status
DREC ready Perturbo prête DREC ready DREC ready DREC ready DREC ready DREC ready
CCU status CCU statut CCU status CCU status CCU status CCU status CCU status
Central archive Archive centrale Central archive Central archive Central archive Central archive Central archive
Counter Top Top compteur Counter Top Counter Top Counter Top Counter Top Counter Top
DB incoh. SPS SPS DB incoh. DB incoh. SPS DB incoh. SPS DB incoh. SPS DB incoh. SPS DB incoh. SPS
DB switch ctrl ctrl bascul. BD DB switch ctrl DB switch ctrl DB switch ctrl DB switch ctrl DB switch ctrl
Device link Lien équipement Device link Device link Device link Device link Device link
Device mode Mode équip. Device mode Device mode Device mode Device mode Device mode
DI acq stopped Acq DI arrêtée DI acq stopped DI acq stopped DI acq stopped DI acq stopped DI acq stopped
DIU status DIU statut DIU status DIU status DIU status DIU status DIU status
DOU status DOU statut DOU status DOU status DOU status DOU status DOU status
Ext clock status Etat horloge ext Ext clock status Ext clock status Ext clock status Ext clock status Ext clock status
GHU status GHU statut GHU status GHU status GHU status GHU status GHU status
IED DREC ready IED pert. prête IED DREC ready IED DREC ready IED DREC ready IED DREC ready IED DREC ready
IED SPS com. SPS com. IED IED SPS com. IED SPS com. IED SPS com. IED SPS com. IED SPS com.
IED SPS Synchro. SPS Synchro. IED IED SPS Synchro. IED SPS Synchro. IED SPS Synchro. IED SPS Synchro. IED SPS Synchro.
ISAGRAF status Etat ISAGRAF ISAGRAF status ISAGRAF status ISAGRAF status ISAGRAF status ISAGRAF status
ISAGRAF status Etat ISAGRAF ISAGRAF status ISAGRAF status ISAGRAF status ISAGRAF status ISAGRAF status
Loc/rem ctrl DPC DPC ctrl Loc/dis Loc/rem ctrl DPC Loc/rem ctrl DPC Loc/rem ctrl DPC Loc/rem ctrl DPC Loc/rem ctrl DPC
Local/remote DPS DPS local/distant Local/remote DPS Local/remote DPS Local/remote DPS Local/remote DPS Local/remote DPS
Local/remote SPS SPS loc/distant Local/remote SPS Local/remote SPS Local/remote SPS Local/remote SPS Local/remote SPS
Log Queue File du log Log Queue Log Queue Log Queue Log Queue Log Queue
Main status MV MV état princ. Main status MV Main status MV Main status MV Main status MV Main status MV
Mode control DPC DPC de contrôle du mode Mode control DPC Mode control DPC Mode control DPC Mode control DPC Mode control DPC
OI client link Lien client OI OI client link OI client link OI client link OI client link OI client link
Operating mode Mode exploitation Operating mode Operating mode Operating mode Operating mode Operating mode
Printer status DPS état imprimante Printer status Printer status Printer status Printer status Printer status
Red mode ctrl ctrl mode red Red mode ctrl Red mode ctrl Red mode ctrl Red mode ctrl Red mode ctrl
Red Status ctrl ctrl statut red Red Status ctrl Red Status ctrl Red Status ctrl Red Status ctrl Red Status ctrl
Red. change stat Stat changt red. Red. change stat Red. change stat Red. change stat Red. change stat Red. change stat
Redundancy mode Mode redondance Redundancy mode Redundancy mode Redundancy mode Redundancy mode Redundancy mode
Redundancy SPS SPS de Redondance Redundancy SPS Redundancy SPS Redundancy SPS Redundancy SPS Redundancy SPS
SCADA SPS com. SPS com. SCADA SCADA SPS com. SCADA SPS com. SCADA SPS com. SCADA SPS com. SCADA SPS com.
Soft. error SPS SPS erreur soft. Soft. error SPS Soft. error SPS Soft. error SPS Soft. error SPS Soft. error SPS
Synchronisation Synchronisation Synchronisation Synchronisation Synchronisation Synchronisation Synchronisation
Test control DPC DPC de control de test Test control DPC Test control DPC Test control DPC Test control DPC Test control DPC
TMU status TMU statut TMU status TMU status TMU status TMU status TMU status
HBU status HBU statut HBU status HBU status HBU status HBU status HBU status
UCA2 Coupling Couplage UCA2 UCA2 Coupling UCA2 Coupling UCA2 Coupling UCA2 Coupling UCA2 Coupling
Watchdog SPS SPS Watchdog Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS
Board status DPS DPS état carte Board status DPS Board status DPS Board status DPS Board status DPS Board status DPS
Red. change mode Mode changt red. Red. change mode Red. change mode Red. change mode Red. change mode Red. change mode
LD DREC ready LD DREC prêt LD DREC ready LD DREC ready LD DREC ready LD DREC ready LD DREC ready
AOU status AOU statut AOU status AOU status AOU status AOU status AOU status
Buff Ov Gtw 1 Buff Ov Gtw 1 Buff Ov Gtw 1 Buff Ov Gtw 1 Buff Ov Gtw 1 Buff Ov Gtw 1 Buff Ov Gtw 1
Buff Ov Gtw 2 Buff Ov Gtw 2 Buff Ov Gtw 2 Buff Ov Gtw 2 Buff Ov Gtw 2 Buff Ov Gtw 2 Buff Ov Gtw 2
Buff Ov OI Buff Ov OI Buff Ov OI Buff Ov OI Buff Ov OI Buff Ov OI Buff Ov OI
Buff Ov OI Bck Buff Ov OI Bck Buff Ov OI Bck Buff Ov OI Bck Buff Ov OI Bck Buff Ov OI Bck Buff Ov OI Bck
All IED status All IED status All IED status All IED status All IED status All IED status All IED status
All rack status All rack status All rack status All rack status All rack status All rack status All rack status
Local alarm ack Local alarm ack Local alarm ack Local alarm ack Local alarm ack Local alarm ack Local alarm ack
Setting done Setting done Setting done Setting done Setting done Setting done Setting done
Setting disc. Setting disc. Setting disc. Setting disc. Setting disc. Setting disc. Setting disc.
Setting in prog. Setting in prog. Setting in prog. Setting in prog. Setting in prog. Setting in prog. Setting in prog.
Setting incoher. Setting incoher. Setting incoher. Setting incoher. Setting incoher. Setting incoher. Setting incoher.
Rack link status Rack link status Rack link status Rack link status Rack link status Rack link status Rack link status
Red.Status Red.Status Red.Status Red.Status Red.Status Red.Status Red.Status
IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS
IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS
IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS
IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC
IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC
IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : System Functions SHEET : Fonctions Systèmes SHEET : System Functions SHEET : System Functions SHEET : System Functions SHEET : Функции системы SHEET : System Functions
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
SYSTEM PROFILES PROFILS SYSTEMES SYSTEM PROFILES SYSTEM PROFILES SYSTEM PROFILES Профили системы SYSTEM PROFILES
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : SystemInformation_Template SHEET : SystemInformation_Template SHEET : SystemInformation_Template SHEET : SystemInformation_Template SHEET : SystemInformation_Template SHEET : SystemInformation_Template SHEET : SystemInformation_Template
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
SYSTEM INFORMATION DATA DESCRIPTION INFORMATION SYSTEME DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION ОПИСАНИЕ СИСТЕМНОЙ ИНФОРМАЦИИ SYSTEM INFORMATION DATA DESCRIPTION
Gateway Passerelle Gateway UTR UTR Шлюз Gateway
Port used (on gateway) Ports utilisés (sur la passerelle) Port used (on gateway) Puerto utilizado (en UTR) Porta utilizada (em UTR) Используемый порт (на шлюз) benutzter Port (Gateway)
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2
Auto generated Génération automatique Auto generated Auto generado Auto Geração Автоматически сгенерировано Auto generated
SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : List of bays SHEET : Liste des Tranches SHEET : List of bays SHEET : Lista de bahías SHEET : Lista de Bays SHEET : Список ячеек SHEET : List of bays
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BAY INFORMATION INFORMATIONS SUR LES TRANCHES BAY INFORMATION INFORMACION DE BAHIAS Informação de Bays ИНФОРМАЦИЯ ПО ЯЧЕЙКЕ BAY INFORMATION
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Bay Name Nom de la Tranche Bay Name Nombre de bahía Nome do Painel Имя ячейки Bay Name
Bay Type Type de Tranche Bay Type Tipo de bahía Tipo de Painel Тип ячейки Bay Type
Computer Calculateur Computer Computador Computador Компьютер Computer
Redundant Computer Calculateur Redondant Redundant Computer Computador Redundante Computador Redundante Резервный компьютер Redundant Computer
Issue Révision Issue Revisión Revisão Версия Version
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : T101 Model SHEET : Modèles T101 SHEET : T101 Model SHEET : Modelo T101 SHEET : Modo T101 SHEET : Модель T101 SHEET : T101 Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA T101 DEBUT SCADA T101 BEGIN SCADA T101 COMIENZA SCADA T101 INÍCIO SCADA T101 НАЧАЛО ОПИСАНИЯ SCADA T101 BEGIN SCADA T101
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Grid
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Main communication channel Voie de communication principale Main communication channel Canal de comunicación principal Canal de Comunicação Principal Основной канал связи Main communication channel
Auxiliary Communication channel Voie de communication auxiliaire Auxiliary Communication channel Canal de comunciación auxiliar Canal de Comunicação auxiliar Запасной канал связи Auxiliary Communication channel
Baud rate (bit/s) Vitesse de transmission (bit/s) Baud rate (bit/s) Baudios (bit/s) Baud Rate (bit/s) Скорость в бодах (бит/с) Baud rate (bit/s)
Time Reference Temps de référence Time Reference Tiempo de referencia Tempo de referência Время ссылку Zeitplan
Redundancy type Type de redondance Redundancy type Tipo de redundancia Redundância tipo Избыточность типа Redundanz Typ
Link Address Adresse du lien Link Address Dirección del vínculo Endereço do Link Адрес связи Link Address
Redundant Link Address Adresse du lien redondant Redundant Link Address Dirección redundante del vínculo Endereço redundante do Vínculo Резервный адрес связи Redundant Link Address
Link Address Length Longueur de l'adresse du lien Link Address Length Longitud de la dirección del vínculo Tamanho do Endereço do Link Длина адреса связи Link Address Length
Common address of ASDU Adresse commune de l'ASDU Common address of ASDU Dirección común ASDU Endereço comum ASDU Общий адрес ASDU Common address of ASDU
Common address of ASDU Length Longueur de l'adresse commune de l'ASDU Common address of ASDU Length Longitud de la dirección común ASDU Tamanho do Endereço comum ASDU Длина общего адреса ASDU Common address of ASDU Length
Object structure Structure d'objet Object structure Estructura del objeto Estrutura do objeto Структура объекта Object structure
Frame max length Longueur maximale de la vue Frame max length Longitud máx de la trama Tamanho máx do frame Максимальная длина кадра Frame max length
Cause of Transmission Length Cause de longueur de transmission Cause of Transmission Length Longitud de la causa de transmisión Tamanho da causa de Transmissão Длина Cause of Transmission Cause of Transmission Length
Measurement periodic cycle Cycle Périodique de Mesure Measurement periodic cycle Ciclo de medición periódico Ciclo periódico de Medição Периодический цикл измерений Measurement periodic cycle
Binary Time Size Taille de Temps binaire Binary Time Size Tamaño de tiempo binario Tamanho Binário do Tempo Размер двоичной кодировки времени Binary Time Size
Background scan cycle Cycle de balayage Background scan cycle Ciclo "background scan" Ciclo "background scan" Фоновый цикл сканирования Background scan cycle
Type of link Type de lien Type of link Tipo de enlace Tipo de ligação Вид ссылки Art der Verknüpfung
Test frame timeout (T3) Expriration de la trame de test (T3) Test frame timeout (T3) Marco de tiempo de prueba (T3) Teste moldura Timeout (T3) Тест кадр тайм (T3) Prüfung Timeout (T3)
SBO timeout Temps d'expiration pour la sélection avant opération SBO timeout Tiempo fuera SBO Falha SBO Задержка SBO SBO Timeout
Inter frame duration Durée inter trame Inter frame duration Duración entre 2 fotogramas Duração entre 2 frames Продолжительность от 2 кадров Inter frame duration
Quality Value for 'Jammed' state Valeur de Qualité de l'état 'Jammed' Quality Value for 'Jammed' state Valor de calidad 'atascado' estado Qualidade Valor para 'emperrado' estado Качество стоимость для 'застряла' состояния Qualitäts für "gestaute" Zustand
Quality Value for toggling xPS Valeur de Qualité de bascule xPS Quality Value for toggling xPS Valor de calidad para alternar XPS Qualidade Valor para alternar xps Качество стоимость для переключения XPS Qualitäts für Makeln XPS
Quality Value for 'Unknown' state Valeur de Qualité de l'état 'Inconnu' Quality Value for 'Unknown' state Valor de calidad 'Desconocido' estado Qualidade Valor para 'Desconhecido' estado Качество стоимость для 'Неизвестное' состояние Qualitäts für "unbekannt" Zustand
SOE file support Support de fichier SOE SOE file support Archivo de apoyo SOE Arquivo apoio SOE файл поддержки SOE SOE file support
SOE file address Adresse de fichier SOE SOE file address Archivo dirección SOE Arquivo endereço SOE файл адрес SOE SOE file address
SOE file format Format de fichier SOE SOE file format Formato de archivo SOE Formato de arquivo SOE файл формата SOE SOE file format
SOE file nb of events Nb d'évenements dans le fichier SOE SOE file nb of events Número de expediente de hechos SOE Arquivo número de eventos SOE файл ряд мероприятий SOE SOE file nb of events
Nb max of SOE files Nombre maximum de fichiers SOE Nb max of SOE files número máximo de archivos de SOE Número máximo de arquivos SOE Максимальное количество SOE файлы Nb max of SOE files
Full SOE file nb of events Nb d'évenements dans le fichier SOE plein Full SOE file nb of events Completa número de expediente de hechos SOE Arquivo completo conjunto de eventos SOE полный файл SOE ряд мероприятий Full SOE file nb of events
Disturbance file support Support du fichier de Perturbographie Disturbance file support Perturbación archivo de apoyo Perturbação arquivo apoio Нарушение файл поддержки Disturbance-Unterstützung
Disturbance file address Adresse du fichier de Perturbographie Disturbance file address Perturbación archivo dirección Perturbação arquivo endereço Нарушение файл адрес Disturbance-Adresse
Disturbance file address for T103 Adresse du fichier de Perturbographie T103 Disturbance file address for T103 Perturbación archivo dirección T103 Perturbação arquivo endereço T103 Нарушение файл адрес T103 Disturbance-Adresse T103
Disturbance file address for S20 Adresse du fichier de Perturbographie S20 Disturbance file address for S20 Perturbación archivo dirección S20 Perturbação arquivo endereço S20 Нарушение файл адрес S20 Disturbance-Adresse S20
Disturbance file address for M300 Adresse du fichier de Perturbographie M300 Disturbance file address for M300 Perturbación archivo dirección M300 Perturbação arquivo endereço M300 Нарушение файл адрес M300 Disturbance-Adresse M300
Disturbance file address for SlowWave Adresse du fichier de Perturbographie SlowWave Disturbance file address for SlowWave Perturbación archivo dirección SlowWave Perturbação arquivo endereço SlowWave Нарушение файл адрес SlowWave Disturbance-Adresse SlowWave
Disturbance file address for FastWave Adresse du fichier de Perturbographie FastWave Disturbance file address for FastWave Perturbación archivo dirección FastWave Perturbação arquivo endereço FastWave Нарушение файл адрес FastWave Disturbance-Adresse FastWave
Nb max of Disturbance files Nombre maximum de fichiers de perturbographie Nb max of Disturbance files número máximo de archivos de perturbación Número máximo de arquivos Perturbação Максимальное количество нарушений файлы maximale Anzahl von Dateien Disturbance
Buffer Overflow file support Support du fichier de débordement de tampon Buffer Overflow file support Desbordamiento de búfer de archivo de apoyo Buffer overflow arquivo apoio Переполнение буфера файл поддержки Buffer Overflow-Unterstützung
Buffer Overflow file address Adresse du fichier de débordement de tampon Buffer Overflow file address Desbordamiento de búfer de archivo dirección Buffer overflow arquivo endereço Переполнение буфера файла адрес Buffer Overflow-Datei-Adresse
Buffer Overflow empty condition Condition vide de débordement de tampon Buffer Overflow empty condition Condición vacío de desbordamiento de búfer Buffer overflow vazio condição Переполнение буфера пустого состояния Buffer Overflow leeren Zustand
Balanced mode Mode balancé Balanced mode Modo Balanced Modo Balanced Сбалансированный режим Balanced mode
Balanced mode retry number Mode balancé nb d'essais Balanced mode retry number Modo Balanced el número de reintentos Modo Balanced número do reintentos Сбалансированный режим повтора номера Balanced mode retry Zahl
Balanced mode link timeout Expiration du mode balancé Balanced mode link timeout Tiempo de modo Balanced enlace Falha do modo Balanced Сбалансированный режим ссылку тайм Balanced mode link timeout
Sequence of Information value for TS Séquence d'Information valeur de TS Sequence of Information value for TS Secuencia de la información de valor para el TS Sequência de Informação valor para TS Последовательность Информация значение для ТП Sequence of Information value for TS
Sequence of Information value for TM Séquence d'Information valeur de TM Sequence of Information value for TM Secuencia de la información de valor para TM Sequência de Informação valor para TM Последовательность Информация значение для TM Sequence of Information value for TM
Sequence of Information value for Counter Séquence d'Information valeur de Compteur Sequence of Information value for Counter Secuencia de la información de valor para Counter Sequência de Informação valor para Counter Последовательность Информация значение для борьбы Sequence of Information value for Counter
Sequence of Information Gap address to split Séquence d'Information écart d'adresse de séparation Sequence of Information Gap address to split Secuencia de la Información Brecha dirección para dividir Sequência de Informação Gap endereço para dividir Последовательность информационных пробелов адрес разделить Sequence of Information Gap address to split
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority [1-255] Prioritée [1-255] Priority [1-255] Prioridad [1-255] Prioridade[1-255] Приоритет [1-255] Priority [1-255]
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Background scan Balayage de fond Background scan Background scan Background scan Сканирование в фоновом режиме Background scan
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority [1-255] Prioritée [1-255] Priority [1-255] Prioridad [1-255] Prioridade[1-255] Приоритет [1-255] Priority [1-255]
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Background scan Balayage de fond Background scan Background scan Background scan Сканирование в фоновом режиме Background scan
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
MPS Data Type MPS Donnée de Type MPS Data Type MPS Datos tipo MPS Dados tipo MPS Тип данных MPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority [1-255] Prioritée [1-255] Priority [1-255] Prioridad [1-255] Prioridade[1-255] Приоритет [1-255] Priority [1-255]
Bitstring usage Utilisation du Bistring Bitstring usage Bitstring uso Estado invertido Bitstring использования Bitstring Nutzung
Background scan Balayage de fond Background scan Background scan Background scan Сканирование в фоновом режиме Background scan
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
SBO timeout [0-65535 s] Temps d'expiration pour la sélection avant opération [0-65535 s] SBO timeout [0-65535 s] SBO tiempo fuera [0-65535 s] Tempo Limite SBO[0-65535 s] Задерка SBO [0-65535 с] SBO timeout [0-65535 s]
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
SBO timeout [0-65535 s] Temps d'expiration pour la sélection avant opération [0-65535 s] SBO timeout [0-65535 s] SBO tiempo fuera [0-65535 s] Tempo Limite SBO[0-65535 s] Задерка SBO [0-65535 с] SBO timeout [0-65535 s]
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority [1-255] Prioritée [1-255] Priority [1-255] Prioridad [1-255] Prioridade[1-255] Приоритет [1-255] Priority [1-255]
Format Format Format Formato Formato Формат Format
Cycle Type Type de Cycle Cycle Type Tipo de ciclo Tipo de Ciclo Тип цикла Cycle Type
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
Format Format Format Formato Formato Формат Format
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
SBO timeout [0-65535 s] Temps d'expiration pour la sélection avant opération [0-65535 s] SBO timeout [0-65535 s] SBO tiempo fuera [0-65535 s] Tempo Limite SBO[0-65535 s] Задерка SBO [0-65535 с] SBO timeout [0-65535 s]
Counter Data Type Compteur de Donnée de Type Counter Data Type Counter Datos tipo Contador de Dados tipo Counter Тип данных Counter Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-4] (0=no) Groupes [0-4] (0=non) Group [0-4] (0=no) Grupo [0-4] (0=no) Grupo [0-4] (0=não) Группа [0-4] (0=no) Gruppe [0-4] (0=no)
Priority [1-255] Prioritée [1-255] Priority [1-255] Prioridad [1-255] Prioridade[1-255] Приоритет [1-255] Priority [1-255]
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : DNP3 Model SHEET : Modèles DNP3 SHEET : DNP3 Model SHEET : Modelo DNP3 SHEET : Modo DNP3 SHEET : Модель DNP3 SHEET : DNP3 Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA DNP3 DEBUT SCADA DNP3 BEGIN SCADA DNP3 COMIENZA SCADA DNP3 INÍCIO SCADA DNP3 НАЧАЛО ОПИСАНИЯ SCADA ПРОТОКОЛА DNP3 BEGIN SCADA DNP3
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Main communication channel Voie de communication principale Main communication channel Canal de comunicación principal Canal de Comunicação Principal Основной канал связи Main communication channel
Auxiliary Communication channel Voie de communication auxiliaire Auxiliary Communication channel Canal de comunciación auxiliar Canal de Comunicação auxiliar Запасной канал связи Auxiliary Communication channel
Baud rate (bit/s) Vitesse de transmission (bit/s) Baud rate (bit/s) Baudios (bit/s) Baud Rate (bit/s) Скорость в бодах (бит/с) Baud rate (bit/s)
Time Reference Temps de référence Time Reference Tiempo de referencia Tempo de referência Время ссылку Zeitplan
TCP/IP usage Utilise TCP/IP TCP/IP usage Uso de TCP/IP Usos de TCP/IP использование TCP/IP TCP/IP usage
TCP/IP Address Adresse TCP/IP TCP/IP Address TCP/IP Dirección TCP/IP Endereço TCP/IP Адрес TCP/IP Address
Link Address Adresse du lien Link Address Dirección del vínculo Endereço do Link Адрес связи Link Address
Digital information class Classe d'information numérique Digital information class Clase de información digital Classe de Informação Digital Тип цифровой информации Digital information class
Measurement values class Classe de valeur de mesure Measurement values class Clase de valores de medición Classe de Valores de Medição Тип измеряемых величин Measurement values class
Counter class Classe de compteur Counter class Clase de contadores Classe de contadores Тип счетчика Counter class
Measurement format Format de mesure Measurement format El formato de medición Medição formato Измерение формате Messung format
Static Measurement Mesure statique Static Measurement Medida estática Static Medição Статические измерения Statische Messung
Event Measurement Mesure évènementielle Event Measurement Medida eventa Evento Medição Событие измерения Event-Messung
Counter format Format de compteur Counter format Contador el formato Contador formato Счетчик формате Counter-Format
Static Counter Compteur statique Static Counter Contador estática Static Contador Статические Счетчик Statische Counter
Event Counter Compteur évènementielle Event Counter Contador eventa Evento Contador Событие Счетчик Event Counter
Inter frame duration Durée inter trame Inter frame duration Duración entre 2 fotogramas Duração entre 2 frames Продолжительность от 2 кадров Inter frame duration
SBO timeout Temps d'expiration pour la sélection avant opération SBO timeout Tiempo fuera SBO Falha SBO Задержка SBO SBO Timeout
Spontaneous message enabled Message spontané actif Spontaneous message enabled Espontáneo mensaje habilitado Espontâneas mensagem ativado Спонтанные сообщения позволили Spontan Nachricht aktiviert
Spontaneous message class Classe de message spontané Spontaneous message class Espontánea clase de mensaje Espontâneas mensagem classe Спонтанное сообщение класс Spontan Nachrichtenklasse
SOE file support Support de fichier SOE SOE file support Archivo de apoyo SOE Arquivo apoio SOE файл поддержки SOE SOE file support
SOE file address Adresse de fichier SOE SOE file address Archivo dirección SOE Arquivo endereço SOE файл адрес SOE SOE file address
SOE file format Format de fichier SOE SOE file format Formato de archivo SOE Formato de arquivo SOE файл формата SOE SOE file format
SOE file nb of events Nb d'évenements dans le fichier SOE SOE file nb of events Número de expediente de hechos SOE Arquivo número de eventos SOE файл ряд мероприятий SOE SOE file nb of events
Full SOE file nb of events Nb d'évenements dans le fichier SOE plein Full SOE file nb of events Completa número de expediente de hechos SOE Arquivo completo conjunto de eventos SOE полный файл SOE ряд мероприятий Full SOE file nb of events
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
MPS Data Type MPS Donnée de Type MPS Data Type MPS Datos tipo MPS Dados tipo MPS Тип данных MPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Bitstring usage Utilisation du Bistring Bitstring usage Bitstring uso Estado invertido Bitstring использования Bitstring Nutzung
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Format Format Format Formato Formato Формат Format
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
Defined as counter Défini comme compteur Defined as counter Definido como contador Definido como contador Определяется как борьба Definiert als Zähler
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
Format Format Format Formato Formato Формат Format
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
Counter Data Type Compteur de Donnée de Type Counter Data Type Counter Datos tipo Contador de Dados tipo Counter Тип данных Counter Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : T104 Model SHEET : Modèles T104 SHEET : T104 Model SHEET : Modelo T104 SHEET : Modo T104 SHEET : Модель T104 SHEET : T104 Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA T104 DEBUT SCADA T104 BEGIN SCADA T104 COMIENZA SCADA T104 INÍCIO SCADA T104 НАЧАЛО ОПИСАНИЯ SCADA T104 BEGIN SCADA T104
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Time Reference Temps de référence Time Reference Tiempo de referencia Tempo de referência Время ссылку Zeitplan
TCP/IP Address Adresse TCP/IP TCP/IP Address TCP/IP Dirección TCP/IP Endereço TCP/IP Адрес TCP/IP Address
Common address of ASDU Adresse commune de l'ASDU Common address of ASDU Dirección común ASDU Endereço comum ASDU Общий адрес ASDU Common address of ASDU
Address structure Structure de l'adresse Address structure Estructura de la dirección Estrutura do endereço Структура решения Struktur der Adresse
Frame max length Longueur maximale de la vue Frame max length Longitud máx de la trama Tamanho máx do frame Максимальная длина кадра Frame max length
Measurement periodic cycle Cycle Périodique de Mesure Measurement periodic cycle Ciclo de medición periódico Ciclo periódico de Medição Периодический цикл измерений Measurement periodic cycle
Binary Time Size Taille de Temps binaire Binary Time Size Tamaño de tiempo binario Tamanho Binário do Tempo Размер двоичной кодировки времени Binary Time Size
Background scan cycle Cycle de balayage Background scan cycle Ciclo "background scan" Ciclo "background scan" Фоновый цикл сканирования Background scan cycle
Connection timeout (T0) Expiration de la Connexion (T0) Connection timeout (T0) Connection tiempo fuera (T0) Falha de Conexão (T0) Задержка соединения (T0) Connection timeout (T0)
APDU timeout (T1) Expiration de l'APDU (T1) APDU timeout (T1) APDU tiempo fuera (T1) Falha APDU (T1) Задержка APDU (T1) APDU timeout (T1)
Acknowledgement timeout (T2) Expiration de la Réception (T2) Acknowledgement timeout (T2) Acknowledgement tiempo fuera (T2) Falha de Reconhecimento (T2) Задержка подтвердения (T2) Acknowledgement timeout (T2)
Test frame timeout (T3) Expriration de la trame de test (T3) Test frame timeout (T3) Marco de tiempo de prueba (T3) Teste moldura Timeout (T3) Тест кадр тайм (T3) Prüfung Timeout (T3)
Sent unack. Frames window size (K) Taille de la fenêtre d'envoi d'acquis négatif Sent unack. Frames window size (K) Tamaño de ventana de tramas enviadas no reconocidas (K) Tamanho de janelas de frames enviadas Não reconhecidas (K) Sent unack. Frames window size (K) Sent unack. Frames window size (K)
Ack. Received frames window size (W) Taille de la fenêtre de réception d'acquis positif Ack. Received frames window size (W) Tamaño de ventana de tramas recibidas y reconocidas (W) Tamanho de janelas de frames recebidas e reconhecidas (W) Ack. Received frames window size (W) Ack. Received frames window size (W)
Max command delay Délai maximum de la Commande Max command delay Retardo de comando Máx Retardo de comando Máx Max command delay Max command delay
Socket IP #1 Socket IP #1 Socket IP #1 Socket IP #1 Socket IP #1 Socket IP #1 Socket IP #1
Socket IP #2 Socket IP #2 Socket IP #2 Socket IP #2 Socket IP #2 Socket IP #2 Socket IP #2
Socket IP #3 Socket IP #3 Socket IP #3 Socket IP #3 Socket IP #3 Socket IP #3 Socket IP #3
Socket IP #4 Socket IP #4 Socket IP #4 Socket IP #4 Socket IP #4 Socket IP #4 Socket IP #4
SBO timeout Temps d'expiration pour la sélection avant opération SBO timeout Tiempo fuera SBO Falha SBO Задержка SBO SBO Timeout
Quality Value for 'Jammed' state Valeur de Qualité de l'état 'Jammed' Quality Value for 'Jammed' state Valor de calidad 'atascado' estado Qualidade Valor para 'emperrado' estado Качество стоимость для 'застряла' состояния Qualitäts für "gestaute" Zustand
Quality Value for toggling xPS Valeur de Qualité de bascule xPS Quality Value for toggling xPS Valor de calidad para alternar XPS Qualidade Valor para alternar xps Качество стоимость для переключения XPS Qualitäts für Makeln XPS
Quality Value for 'Unknown' state Valeur de Qualité de l'état 'Inconnu' Quality Value for 'Unknown' state Valor de calidad 'Desconocido' estado Qualidade Valor para 'Desconhecido' estado Качество стоимость для 'Неизвестное' состояние Qualitäts für "unbekannt" Zustand
Switchover Switchover Switchover Switchover Switchover Switchover Switchover
SOE file support Support de fichier SOE SOE file support Archivo de apoyo SOE Arquivo apoio SOE файл поддержки SOE SOE file support
SOE file address Adresse de fichier SOE SOE file address Archivo dirección SOE Arquivo endereço SOE файл адрес SOE SOE file address
SOE file format Format de fichier SOE SOE file format Formato de archivo SOE Formato de arquivo SOE файл формата SOE SOE file format
SOE file nb of events Nb d'évenements dans le fichier SOE SOE file nb of events Número de expediente de hechos SOE Arquivo número de eventos SOE файл ряд мероприятий SOE SOE file nb of events
Nb max of SOE files Nombre maximum de fichiers SOE Nb max of SOE files número máximo de archivos de SOE Número máximo de arquivos SOE Максимальное количество SOE файлы Nb max of SOE files
Full SOE file nb of events Nb d'évenements dans le fichier SOE plein Full SOE file nb of events Completa número de expediente de hechos SOE Arquivo completo conjunto de eventos SOE полный файл SOE ряд мероприятий Full SOE file nb of events
Disturbance file support Support du fichier de Perturbographie Disturbance file support Perturbación archivo de apoyo Perturbação arquivo apoio Нарушение файл поддержки Disturbance-Unterstützung
Disturbance file address Adresse du fichier de Perturbographie Disturbance file address Perturbación archivo dirección Perturbação arquivo endereço Нарушение файл адрес Disturbance-Adresse
Disturbance file address for T103 Adresse du fichier de Perturbographie T103 Disturbance file address for T103 Perturbación archivo dirección T103 Perturbação arquivo endereço T103 Нарушение файл адрес T103 Disturbance-Adresse T103
Disturbance file address for S20 Adresse du fichier de Perturbographie S20 Disturbance file address for S20 Perturbación archivo dirección S20 Perturbação arquivo endereço S20 Нарушение файл адрес S20 Disturbance-Adresse S20
Disturbance file address for M300 Adresse du fichier de Perturbographie M300 Disturbance file address for M300 Perturbación archivo dirección M300 Perturbação arquivo endereço M300 Нарушение файл адрес M300 Disturbance-Adresse M300
Disturbance file address for SlowWave Adresse du fichier de Perturbographie SlowWave Disturbance file address for SlowWave Perturbación archivo dirección SlowWave Perturbação arquivo endereço SlowWave Нарушение файл адрес SlowWave Disturbance-Adresse SlowWave
Disturbance file address for FastWave Adresse du fichier de Perturbographie FastWave Disturbance file address for FastWave Perturbación archivo dirección FastWave Perturbação arquivo endereço FastWave Нарушение файл адрес FastWave Disturbance-Adresse FastWave
Nb max of Disturbance files Nombre maximum de fichiers de perturbographie Nb max of Disturbance files número máximo de archivos de perturbación Número máximo de arquivos Perturbação Максимальное количество нарушений файлы maximale Anzahl von Dateien Disturbance
Buffer Overflow file support Support du fichier de débordement de tampon Buffer Overflow file support Desbordamiento de búfer de archivo de apoyo Buffer overflow arquivo apoio Переполнение буфера файл поддержки Buffer Overflow-Unterstützung
Buffer Overflow file address Adresse du fichier de débordement de tampon Buffer Overflow file address Desbordamiento de búfer de archivo dirección Buffer overflow arquivo endereço Переполнение буфера файла адрес Buffer Overflow-Datei-Adresse
Buffer Overflow empty condition Condition vide de débordement de tampon Buffer Overflow empty condition Condición vacío de desbordamiento de búfer Buffer overflow vazio condição Переполнение буфера пустого состояния Buffer Overflow leeren Zustand
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority Prioritée Priority Prioridad Prioridade[1-255] Приоритет Priority
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Background scan Balayage de fond Background scan Background scan Background scan Сканирование в фоновом режиме Background scan
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority Prioritée Priority Prioridad Prioridade[1-255] Приоритет Priority
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Background scan Balayage de fond Background scan Background scan Background scan Сканирование в фоновом режиме Background scan
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
MPS Data Type MPS Donnée de Type MPS Data Type MPS Datos tipo MPS Dados tipo MPS Тип данных MPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority Prioritée Priority Prioridad Prioridade[1-255] Приоритет Priority
Bitstring usage Utilisation du Bistring Bitstring usage Bitstring uso Estado invertido Bitstring использования Bitstring Nutzung
Background scan Balayage de fond Background scan Background scan Background scan Сканирование в фоновом режиме Background scan
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
SBO timeout [0-65535 s] Temps d'expiration pour la sélection avant opération [0-65535 s] SBO timeout [0-65535 s] SBO tiempo fuera [0-65535 s] Tempo Limite SBO[0-65535 s] Задерка SBO [0-65535 с] SBO timeout [0-65535 s]
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
SBO timeout [0-65535 s] Temps d'expiration pour la sélection avant opération [0-65535 s] SBO timeout [0-65535 s] SBO tiempo fuera [0-65535 s] Tempo Limite SBO[0-65535 s] Задерка SBO [0-65535 с] SBO timeout [0-65535 s]
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority Prioritée Priority Prioridad Prioridade[1-255] Приоритет Priority
Format Format Format Formato Formato Формат Format
Cycle Type Type de Cycle Cycle Type Tipo de ciclo Tipo de Ciclo Тип цикла Cycle Type
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
Format Format Format Formato Formato Формат Format
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
SBO timeout [0-65535 s] Temps d'expiration pour la sélection avant opération [0-65535 s] SBO timeout [0-65535 s] SBO tiempo fuera [0-65535 s] Tempo Limite SBO[0-65535 s] Задерка SBO [0-65535 с] SBO timeout [0-65535 s]
Counter Data Type Compteur de Donnée de Type Counter Data Type Counter Datos tipo Contador de Dados tipo Counter Тип данных Counter Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-4] (0=no) Groupes [0-4] (0=non) Group [0-4] (0=no) Grupo [0-4] (0=no) Grupo [0-4] (0=não) Группа [0-4] (0=no) Gruppe [0-4] (0=no)
Priority Prioritée Priority Prioridad Prioridade[1-255] Приоритет Priority
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : MODBUS Model SHEET : Modèles MODBUS SHEET : MODBUS Model SHEET : Modelo MODBUS SHEET : Modo MODBUS SHEET : Модель MODBUS SHEET : MODBUS Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA MODBUS DEBUT SCADA MODBUS BEGIN SCADA MODBUS COMIENZA SCADA MODBUS INÍCIO SCADA MODBUS НАЧАЛО ОПИСАНИЯ ПРОТОКОЛА SCADA MODBUS BEGIN SCADA MODBUS
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Main communication channel Voie de communication principale Main communication channel Canal de comunicación principal Canal de Comunicação Principal Основной канал связи Main communication channel
Auxiliary Communication channel Voie de communication auxiliaire Auxiliary Communication channel Canal de comunciación auxiliar Canal de Comunicação auxiliar Запасной канал связи Auxiliary Communication channel
Baud rate (bit/s) Vitesse de transmission (bit/s) Baud rate (bit/s) Baudios (bit/s) Baud Rate (bit/s) Скорость в бодах (бит/с) Baud rate (bit/s)
TCP/IP usage Utilise TCP/IP TCP/IP usage Uso de TCP/IP Usos de TCP/IP использование TCP/IP TCP/IP usage
Link Address Adresse du lien Link Address Dirección del vínculo Endereço do Link Адрес связи Link Address
Inter frame duration Durée inter trame Inter frame duration Duración entre 2 fotogramas Duração entre 2 frames Продолжительность от 2 кадров Inter frame duration
Parity Parité Parity Paridad Paridade Четность Parity
SOE file support Support de fichier SOE SOE file support Archivo de apoyo SOE Arquivo apoio SOE файл поддержки SOE SOE file support
SOE file address Adresse de fichier SOE SOE file address Archivo dirección SOE Arquivo endereço SOE файл адрес SOE SOE file address
SOE file format Format de fichier SOE SOE file format Formato de archivo SOE Formato de arquivo SOE файл формата SOE SOE file format
SOE file nb of events Nb d'évenements dans le fichier SOE SOE file nb of events Número de expediente de hechos SOE Arquivo número de eventos SOE файл ряд мероприятий SOE SOE file nb of events
Full SOE file nb of events Nb d'évenements dans le fichier SOE plein Full SOE file nb of events Completa número de expediente de hechos SOE Arquivo completo conjunto de eventos SOE полный файл SOE ряд мероприятий Full SOE file nb of events
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Inversion Inversion Inversion Inversion Inversão Инверсия Inversion
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Double Address usage Utilisation du Double Adressage Double Address usage Doble dirección de uso Endereço duplo uso адрес двойного использования Double Address usage
Inversion Inversion Inversion Inversion Inversão Инверсия Inversion
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Format Format Format Formato Formato Формат Format
Precision [8-16] Précision [8-16] Precision [8-16] Precisión [8-16] Precisão [8-16] Точность [8-16] Precision [8-16]
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
Format Format Format Formato Formato Формат Format
Counter Data Type Compteur de Donnée de Type Counter Data Type Counter Datos tipo Contador de Dados tipo Counter Тип данных Counter Data Type
Format Format Format Formato Formato Формат Format
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : OPC Model SHEET : Modèles OPC SHEET : OPC Model SHEET : Modelo OPC SHEET : Modo OPC SHEET : Модель OPC SHEET : OPC Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA OPC DEBUT SCADA OPC BEGIN SCADA OPC COMIENZA SCADA OPC INÍCIO SCADA OPC НАЧАЛО ОПИСАНИЯ SCADA OPC BEGIN SCADA OPC
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
OPC value for 'Reset' OPC valeur pour 'Reset' OPC value for 'Reset' Valor OPC de 'Reajuste' Valor OPC de 'Reajuste' Значение OPC для статуса 'Reset' OPC value for 'Reset'
OPC value for 'Set' OPC valeur pour 'Set' OPC value for 'Set' Valor OPC de 'Ajuste' Valor OPC de 'Ajuste' Значение OPC для статуса 'Set' OPC value for 'Set'
OPC value for 'Jammed' OPC valeur pour 'Jammed' OPC value for 'Jammed' Valor OPC de 'Bloqueado' Valor OPC de 'bloqueado' Значение OPC для статуса 'Jammed' OPC value for 'Jammed'
OPC value for 'Open' OPC valeur pour 'Open' OPC value for 'Open' Valor OPC de 'Abierto' Valor OPC de 'Aberto' Значение OPC для статуса 'Open' OPC value for 'Open'
OPC value for 'Closed' OPC valeur pour 'Closed' OPC value for 'Closed' Valor OPC de 'Cerrado' Valor OPC de 'Fechado' Значение OPC для статуса 'Closed' OPC value for 'Closed'
OPC value for 'Undefined' OPC valeur pour 'Undefined' OPC value for 'Undefined' Valor OPC de 'Indefinido' Valor OPC de 'Indefinido' Значение OPC для статуса 'Undefined' OPC value for 'Undefined'
OPC value for 'Order Open' (set to 01) OPC valeur pour 'Order Open' (set to 01) OPC value for 'Order Open' (set to 01) Valor OPC de 'Orden de abierto' (estado 01) Valor OPC de 'Ordem de Aberto' (estado 01) Значение OPC для статуса 'Order Open' (установка в 01) OPC value for 'Order Open' (set to 01)
OPC value for 'Order Close' (set to 10) OPC valeur pour 'Order Close' (set to 10) OPC value for 'Order Close' (set to 10) Valor OPC de 'Orden de cerrado' (estado 10) Valor OPC de 'Ordem de Fechado' (estado 10) Значение OPC для статуса 'Order Close' (установка в 10) OPC value for 'Order Close' (set to 10)
OPC value for 'Order Reset' OPC valeur pour 'Order Reset' OPC value for 'Order Reset' Valor OPC de 'Order Reset' Valor OPC de 'Order Reset' Значение OPC для статуса 'Order Reset' OPC value for 'Order Reset'
OPC value for 'Order Set' OPC valeur pour 'Order Set' OPC value for 'Order Set' Valor OPC de 'Order Set' Valor OPC de 'Order Set' Значение OPC для статуса 'Order Set' OPC value for 'Order Set'
OPC Bool value for 'Reset' OPC Bool valeur pour 'Reset' OPC Bool value for 'Reset' Valor booleano OPC de 'Reset' Valor booleano OPC de 'Reset' OPC булево значение для 'Reset' OPC Bool value for 'Reset'
OPC Bool value for 'Set' OPC Bool valeur pour 'Set' OPC Bool value for 'Set' Valor booleano OPC de 'Set' Valor booleano OPC de 'Set' OPC булево значение для 'Set' OPC Bool value for 'Set'
OPC Bool value for 'Jammed' OPC Bool valeur pour 'Jammed' OPC Bool value for 'Jammed' Valor booleano OPC de 'Jammed' Valor booleano OPC de 'Jammed' OPC булево значение для 'Jammed' OPC Bool value for 'Jammed'
OPC Bool value for 'Open' OPC Bool valeur pour 'Open' OPC Bool value for 'Open' Valor booleano OPC de 'Open' Valor booleano OPC de 'Open' OPC булево значение для 'Open' OPC Bool value for 'Open'
OPC Bool value for 'Closed' OPC Bool valeur pour 'Closed' OPC Bool value for 'Closed' Valor booleano OPC de 'Closed' Valor booleano OPC de 'Closed' OPC булево значение для 'Closed' OPC Bool value for 'Closed'
OPC Bool value for 'Undefined' OPC Bool valeur pour 'Undefined' OPC Bool value for 'Undefined' Valor booleano OPC de 'Undefined' Valor booleano OPC de 'Undefined' OPC булево значение для 'Undefined' OPC Bool value for 'Undefined'
OPC Bool value for 'Order Open' (set to 01) OPC Bool valeur pour 'Order Open' (set to 01) OPC Bool value for 'Order Open' (set to 01) Valor booleano OPC de 'Order Open' (set to 01) Valor booleano OPC de 'Order Open' (set to 01) OPC булево значение для 'Order Open' (set to 01) OPC Bool value for 'Order Open' (set to 01)
OPC Bool value for 'Order Close' (set to 10) OPC Bool valeur pour 'Order Close' (set to 10) OPC Bool value for 'Order Close' (set to 10) Valor booleano OPC de 'Order Close' (set to 10) Valor booleano OPC de 'Order Close' (set to 10) OPC булево значение для 'Order Close' (set to 10) OPC Bool value for 'Order Close' (set to 10)
OPC Bool value for 'Order Reset' OPC Bool valeur pour 'Order Reset' OPC Bool value for 'Order Reset' Valor booleano OPC de 'Order Reset' Valor booleano OPC de 'Order Reset' OPC булево значение для 'Order Reset' OPC Bool value for 'Order Reset'
OPC Bool value for 'Order Set' OPC Bool valeur pour 'Order Set' OPC Bool value for 'Order Set' Valor booleano OPC de 'Order Set' Valor booleano OPC de 'Order Set' OPC булево значение для 'Order Set' OPC Bool value for 'Order Set'
OPC quality for 'SelfCheckFault' OPC qualité pour 'SelfCheckFault' OPC quality for 'SelfCheckFault' Calidad OPC de 'SelfCheckFault' Qualidade OPC de 'SelfCheckFault' OPC качество 'SelfCheckFault' OPC quality for 'SelfCheckFault'
OPC quality for 'Unknown' OPC qualité pour 'Unknown' OPC quality for 'Unknown' Calidad OPC de 'Unknown' Qualidade OPC de 'Unknown' OPC качество 'Unknown' OPC quality for 'Unknown'
OPC quality for 'Toggling' OPC qualité pour 'Toggling' OPC quality for 'Toggling' Calidad OPC de 'Toggling' Qualidade OPC de 'Toggling' OPC качество 'Toggling' OPC quality for 'Toggling'
OPC quality for 'Suppressed' OPC qualité pour 'Suppressed' OPC quality for 'Suppressed' Calidad OPC de 'Suppressed' Qualidade OPC de 'Suppressed' OPC качество 'Suppressed' OPC quality for 'Suppressed'
OPC quality for 'Forced' OPC qualité pour 'Forced' OPC quality for 'Forced' Calidad OPC de 'Forced' Qualidade OPC de 'Forced' OPC качество 'Forced' OPC quality for 'Forced'
OPC quality for 'Substituted' OPC qualité pour 'Substituted' OPC quality for 'Substituted' Calidad OPC de 'Substituted' Qualidade OPC de 'Substituted' OPC качество 'Substituted' OPC quality for 'Substituted'
OPC quality for 'Undefined' MPS MV Counter OPC qualité pour 'Undefined' MPS MV Compteur OPC quality for 'Undefined' MPS MV Counter Calidad OPC de 'Undefined' MPS MV Counter Qualidade OPC de 'Undefined' MPS MV Counter OPC качество 'Undefined' MPS MV Counter OPC quality for 'Undefined' MPS MV Counter
OPC quality for 'OverRange' MPS MV Counter OPC qualité pour 'OverRange' MPS MV Compteur OPC quality for 'OverRange' MPS MV Counter Calidad OPC de 'OverRange' MPS MV Counter Qualidade OPC de 'OverRange' MPS MV Counter OPC качество 'OverRange' MPS MV Counter OPC quality for 'OverRange' MPS MV Counter
OPC quality for 'OpenCircuit' MPS MV Counter OPC qualité pour 'OpenCircuit' MPS MV Compteur OPC quality for 'OpenCircuit' MPS MV Counter Calidad OPC de 'OpenCircuit' MPS MV Counter Qualidade OPC de 'OpenCircuit' MPS MV Counter OPC качество 'OpenCircuit' MPS MV Counter OPC quality for 'OpenCircuit' MPS MV Counter
OPC quality for 'LLLThreshold' OPC qualité pour 'LLLThreshold' OPC quality for 'LLLThreshold' Calidad OPC de 'LLLThreshold' Qualidade OPC de 'LLLThreshold' OPC качество 'LLLThreshold' OPC quality for 'LLLThreshold'
OPC quality for 'LLThreshold' OPC qualité pour 'LLThreshold' OPC quality for 'LLThreshold' Calidad OPC de 'LLThreshold' Qualidade OPC de 'LLThreshold' OPC качество 'LLThreshold' OPC quality for 'LLThreshold'
OPC quality for 'LThreshold' OPC qualité pour 'LThreshold' OPC quality for 'LThreshold' Calidad OPC de 'LThreshold' Qualidade OPC de 'LThreshold' OPC качество 'LThreshold' OPC quality for 'LThreshold'
OPC quality for 'HThreshold' OPC qualité pour 'HThreshold' OPC quality for 'HThreshold' Calidad OPC de 'HThreshold' Qualidade OPC de 'HThreshold' OPC качество 'HThreshold' OPC quality for 'HThreshold'
OPC quality for 'HHThreshold' OPC qualité pour 'HHThreshold' OPC quality for 'HHThreshold' Calidad OPC de 'HHThreshold' Qualidade OPC de 'HHThreshold' OPC качество 'HHThreshold' OPC quality for 'HHThreshold'
OPC quality for 'HHHThreshold' OPC qualité pour 'HHHThreshold' OPC quality for 'HHHThreshold' Calidad OPC de 'HHHThreshold' Qualidade OPC de 'HHHThreshold' OPC качество 'HHHThreshold' OPC quality for 'HHHThreshold'
OPC quality for 'Jammed' DPS OPC qualité pour 'Jammed' DPS OPC quality for 'Jammed' DPS Calidad OPC de 'Jammed' DPS Qualidade OPC de 'Jammed' DPS OPC качество 'Jammed' DPS OPC quality for 'Jammed' DPS
OPC quality for 'Undefined' DPS OPC qualité pour 'Undefined' DPS OPC quality for 'Undefined' DPS Calidad OPC de 'Undefined' DPS Qualidade OPC de 'Undefined' DPS OPC качество 'Undefined' DPS OPC quality for 'Undefined' DPS
OPC quality for 'Valid Set/Closed' OPC qualité pour 'Valid Set/Closed' OPC quality for 'Valid Set/Closed' Calidad OPC de 'Valid Set/Closed' Qualidade OPC de 'Valid Set/Closed' OPC качество 'Valid Set/Closed' OPC quality for 'Valid Set/Closed'
OPC quality for 'Valid Reset/Open' OPC qualité pour 'Valid Reset/Open' OPC quality for 'Valid Reset/Open' Calidad OPC de 'Valid Reset/Open' Qualidade OPC de 'Valid Reset/Open' OPC качество 'Valid Reset/Open' OPC quality for 'Valid Reset/Open'
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Historization Historisation Historization Histórico Histórico исторический Historischen
Format Format Format Formato Formato Формат Format
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Double Address usage Utilisation du Double Adressage Double Address usage Doble dirección de uso Endereço duplo uso адрес двойного использования Double Address usage
Historization Historisation Historization Histórico Histórico исторический Historischen
Format Format Format Formato Formato Формат Format
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
MPS Data Type MPS Donnée de Type MPS Data Type MPS Datos tipo MPS Dados tipo MPS Тип данных MPS Data Type
Historization Historisation Historization Histórico Histórico исторический Historischen
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
Format Format Format Formato Formato Формат Format
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
Format Format Format Formato Formato Формат Format
Double Address usage Utilisation du Double Adressage Double Address usage Doble dirección de uso Endereço duplo uso адрес двойного использования Double Address usage
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : Connections SHEET : Connectique SHEET : Connections SHEET : Conexiones SHEET : Conexões SHEET : Связи SHEET : Connections
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN DATA DEBUT DES DONNEES BEGIN DATA INICIO DE DATOS INICIO DOS DADOS НАЧАЛО ДАННЫХ BEGIN DATA
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : Column Presence Checking SHEET : Présence des Colonnes SHEET : Column Presence Checking SHEET : Columna de verificación SHEET : Checkup Coluna de Presença SHEET : Графа проведения проверки SHEET : Column Presence Checking
This sheet is to be used to indicate the cells/columns that are : Cette FEUILLE est utilisée pour indiquer les cellules/colonnes qui sont : This sheet is to be used to indicate the cells/columns that are : Esta hoja se utiliza para indicar las celdas/columnas que están : Esta Ficha se utiliza para indicar as céluas/colunas que estão : Этот лист используется для выделения ячеек/колонок, которые : This sheet is to be used to indicate the cells/columns that are :
- P : present in all corresponding sheets but the contents shall not be used by automatic tools - P : présentes dans toute les FEUILLES mais dont le contenu ne sera pas employé par les outils automatiques - P : present in all corresponding sheets but the contents shall not be used by automatic tools - P : presentes en todas las hojas correspondientes pero los contenidos no se deben utilizar por herramientas automáticas - P : Presentes em todas as Fichas correspondentes mas o conteúdo não podem ser utilizados por Ferramentas Automáticas -P : представлены во всех соответствующих листах, но содержание м.б. не использовано автоматич. Утилитами - P : present in all corresponding sheets but the contents shall not be used by automatic tools
- U : present in all corresponding sheets and shall be used by automatic tools - U : présentes dans toutes les FEUILLES et seront employées par les outils automatiques - U : present in all corresponding sheets and shall be used by automatic tools - U : presentes en todas las hojas correspondientes y se deben utilizar por herramientas automáticas - U : Presentes em todas as Fichas correspondentes e devem se utilizar por Ferramentas Automáticas -U : представлены во всех соответствующих листах и м.б. использованы автоматич. Утилитами - U : present in all corresponding sheets and shall be used by automatic tools
- A : not present in corresponding sheets - A : Absentes des FEUILLES - A : not present in corresponding sheets - A : no presentes en las hojas correspondientes - A : Não Presentes nas Fichas correspondentes -A : не представлены во всех соответствующих листах - A : not present in corresponding sheets
- PH : hide in all corresponding sheets but the contents shall not be used by automatic tools - PH :cachées dans toute les FEUILLES mais le contenu ne sera pas employée par les outils automatiques - PH : hide in all corresponding sheets but the contents shall not be used by automatic tools - PH : ocultas en todas las hojas correspondientes pero los contenidos no se deben utilizar por herramientas automáticas - PH : Ocultas em todas as Fichas correspondentes mas o conteúdo não podem ser utilizados por Ferramentas Automáticas -PH : скрыты во всех соответствующих листах, но содержание м.б. не использовано автоматич. Утилитами - PH : hide in all corresponding sheets but the contents shall not be used by automatic tools
- UH : hide in all corresponding sheets and shall be used by automatic tools - UH :cachées dans toutes les FEUILLES et seront employées par les outils automatiques - UH : hide in all corresponding sheets and shall be used by automatic tools - UH : ocultas en todas las hojas correspondientes y se deben utilizar por herramientas automáticas - UH : Ocultas em todas as Fichas correspondentes e devem se utilizar por Ferramentas Automáticas -UH : скрыты во всех соответствующих листах и м.б. использованы автоматич. Утилитами - UH : hide in all corresponding sheets and shall be used by automatic tools
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
MiCOM CXXX DESCRIPTION MiCOM CXXX DESCRIPTION MiCOM CXXX DESCRIPTION Descripción MiCOM CXXX Descrição MiCOM CXXX ОПИСАНИЕ MiCOM CXXX MiCOM CXXX DESCRIPTION
DI GROUPS GROUPES DES ENTREES NUMERIQUES DI GROUPS Grupos DI Grupos DI Группы DI DI GROUPS
SELF GENERATED DIGITAL INFORMATION ENTREES NUMERIQUES AUTOMATIQUES SELF GENERATED DIGITAL INFORMATION INFORMACION DIGITAL AUTO GENERADA Informação Digital Auto Gerada ЦИФРОВАЯ ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ SELBSTGENERIERTE DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION SORTIES NUMERIQUES AUTOMATIQUES SELF GENERATED DIGITAL OUTPUT INFORMATION INFORMACION DE SALIDAS DIGITALES AUTO GENERADAS Informação de saidas Digitais Auto Geradas ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ ЦИФРОВЫМИ ВЫХОДАМИ SELBSTGENERIERTE DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION ENTREES ANALOGIQUES AUTOMATIQUES SELF GENERATED ANALOG INFORMATION INFORMACION ANALOGICA AUTO GENERADA Informação Analógica Auto Gerada АНАЛОГОВАЯ ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ SELBSTGENERIERTE ANALOG INFORMATION
SHEET : Column Default Value SHEET : Valeurs par Défaut SHEET : Column Default Value SHEET : Valor por defecto de columna SHEET : Valor padrão da Coluna SHEET : Графа стандартных величин SHEET : Column Default Value
This sheet is used to set default parameter value for each data. Cette FEUILLE est employée pour remplacer des valeurs par de nouvelles. This sheet is used to set default parameter value for each data. Esta hoja se utiliza para ajustar el parámetro por defecto para cada dato Esta Ficha se utiliza para ajustar os parâmetros de defeitos para cada dado. Этот лист применяется при установке стандартного значения параметра для каждого данного This sheet is used to set default parameter value for each data.
- set the Old parameter value to change in the "Old Value" line - placez l'ancienne valeur de paramètre dans la ligne "Ancienne valeur" - set the Old parameter value to change in the "Old Value" line - Ajusta el valor del parámetro anterior que se va a cambiar en la línea: "Valor anterior" - Ajusta o Valor do parâmetro anterior usado para Sobrescrever na linha: "Valor anterior" - установите старые значения параметров, выбрав строку "Old Value" - set the Old parameter value to change in the "Old Value" line
- set the New parameter value used to overwrite Old one in the "New Value" line - placez la nouvelle valeur du paramètre dans la ligne "Nouvelle valeur" - set the New parameter value used to overwrite Old one in the "New Value" line - Ajusta el valor del parámetro anterior que se va a cambiar en la línea: "Valor nuevo" - Ajusta o Valor do parámetro anterior usado para Sobrescrever na linha: "Valor novo" - установите новые значения параметров, перезаписав старые значения в строке "New Value" - set the New parameter value used to overwrite Old one in the "New Value" line
- It is possible to use regular expressions as 'Old value' to locate data by using: - Il est possible d'employer des expressions régulières pour filtrer les "Anciennes valeurs". - It is possible to use regular expressions as 'Old value' to locate data by using: - Es posible utilizar expresiones regulares como 'Valor anterior' para localozar datos utilizando: - É possível utilizar expressões regulares como 'Valor anterior' para localizar Dados utilizando: - Возможно использование определ. значения в линии "Old Value" для группы данных путем использования: - It is possible to use regular expressions as 'Old value' to locate data by using:
? Any single character. ? Tout caractère simple. ? Any single character. ? Cualquier caracter sencillo. ? qualquer caracter Simples. знака "?" для любого одиночного символа ? Any single character.
* Zero or more characters. * Zéro caractère ou plus. * Zero or more characters. * Cero o más caracteres. * Zero ou mais Caracteres. знака "*" для обозначения большего количества символов или не использования символов * Zero or more characters.
# Any single digit (0-9). # Tout chiffre simple (0-9). # Any single digit (0-9). # Cuaquier dígito sencillo (0-9). # Qualquer dígito Simples (0-9). знака "#" для обозначения любой цифры (0-9) # Any single digit (0-9).
[charlist] Any single character in charlist. [charlist] Tout caractère simple dans charlist. [charlist] Any single character in charlist. [caractlist] Cualquier caracter simple en la lista de caracteres. [caractlist] qualquer caracter Simples da Lista de caracteres. [charlist] Любой единичный символ из charlist [charlist] Any single character in charlist.
[!charlist] Any single character not in charlist. [!charlist] Tout caractère simple non compris dans charlist. [!charlist] Any single character not in charlist. [!caractlist] Cualquier caracter simple no incluido en la lista de caracteres. [!caractlist] qualquer caracter Simples não incluido na Lista de caracteres. [!charlist] Любой единичный символ не из charlist [!charlist] Any single character not in charlist.
- A group of one or more characters (charlist) enclosed in brackets ([ ]) can be used to - un groupes d'un ou plusieurs caractères (charlist) inclus entre crochets ([ ]) peut être employé à - A group of one or more characters (charlist) enclosed in brackets ([ ]) can be used to - Un grupo de uno o más caracteres (lista de caracteres) entre corchetes ([ ]) se puede utilizar para - Um grupo de um o mais caracteres (Lista de caracteres) entre colchetes ([ ]) pode-se utilizar para Группа из одного или нескольких символов (charlist), заключенная в квадратные скобки ([ ]), м.б. Использована - A group of one or more characters (charlist) enclosed in brackets ([ ]) can be used to
match any single character in string and can include almost any character code, partir de n'importe quel caractère simple dans la chaine et pouvant inclure presque n'importe quel code de caractère, match any single character in string and can include almost any character code, enlazar cualquier caracter sencillo en cadena y puede incluir casi cualquier código de caracteres armazenar qualquer caracter Simples em string e pode incluir quase qualquer código de caracteres для обозначения любого одиночного символа в строке и может включать практически любой символьный код, match any single character in string and can include almost any character code,
including digits. y compris des chiffres. including digits. incluyendo dígitos. incluindo dígitos. включая цифры. including digits.
- Note: To match the special characters left bracket ([), question mark (?), number sign (#), - note : pour utiliser les caractères spéciaux tels le crochet ouvrant ([), le point d'interrogation (?), le signe de nombre (#), - Note: To match the special characters left bracket ([), question mark (?), number sign (#), - Nota: Para enlazar los caracteres especiales corchete izquierdo ([), signo de interrogación (?), signo de número (#), - Nota: Para armazenar os caracteres Especiais colchete esquerdo ([), seguido de interrogacão (?), seguido do número (#), - Примечание: для обозначения символов левой скобки ([), вопроса (?), числа (#), звездочки (*), заключайте - Note: To match the special characters left bracket ([), question mark (?), number sign (#),
and asterisk (*), enclose them in brackets. The right bracket (]) can't be used within a group et l'astérisque (*), les mettre entre crochets. Le crochet droit (]) ne peut pas être utilisé dans un Groupes and asterisk (*), enclose them in brackets. The right bracket (]) can't be used within a group y asterisco, se deben poner entre corchetes. El corchete derecho (]) no se puede utilizar dentro de un grupo e asterisco, se devem ser colocados entre colchetes. O colchete direito (]) não pode ser utilizado dentro de um grupo их в квадратные скобки. Правая скобка (]), должна использоваться вместе с соответствующей группой символов, and asterisk (*), enclose them in brackets. The right bracket (]) can't be used within a group
to match itself, but it can be used outside a group as an individual character. de sélection, mais peut être employé en dehors to match itself, but it can be used outside a group as an individual character. para enlazarse a si mismo, pero se puede utilizar fuera de un grupo como un carácter individual. para armazenar a si mesmo, mas pode-se utilizar fora de um grupo como un carácter individual. При использовании дефиса (-) для отделения верхних и нижних границ диапазона, charlist может определять to match itself, but it can be used outside a group as an individual character.
- By using a hyphen (-) to separate the upper and lower bounds of the range, charlist can - en employant un trait d'union (-) pour séparer les limites supérieures et inférieures de la liste, charlist peut - By using a hyphen (-) to separate the upper and lower bounds of the range, charlist can - Mediante el uso de un guión (-) para separar los extremos superior e inferior del rango, la lista de caracteres puede - Mediante eo uso de um hífem (-) para separar os extremos superior e inferior do Range, a Lista de caracteres pode несколько символов. Например, [A-Z] пишется в случае, если в соответствующих позициях в строке - By using a hyphen (-) to separate the upper and lower bounds of the range, charlist can
specify a range of characters. For example, [A-Z] results in a match if the corresponding indiquer une liste des caractères. Par exemple, [ A-Z ] correspond a toutes les lettres majuscules de l'alphabet. specify a range of characters. For example, [A-Z] results in a match if the corresponding especificar un rango de caracteres. Por ejemplo, [A-Z] da como resultado un conjunto si la posición correspondiente especificar um Range de caracteres. Por exemplo, [A-Z] da como resultado um conjunto se a posição correspondente встречаются любые заглавные буквы в диапазоне A-Z. Диапазон заключается в квадратные скобки без specify a range of characters. For example, [A-Z] results in a match if the corresponding
character position in string contains any uppercase letters in the range A-Z. Multiple ranges Les listes multiples sont incluses dans character position in string contains any uppercase letters in the range A-Z. Multiple ranges al carácter en cadena contiene algunas letras en mayúsculas en el rango A-Z. Múltiples rangos ao caracter em string Possui algumas letras em maiúsculass no Range A-Z. Multiplos Ranges estarão incluidos использования character position in string contains any uppercase letters in the range A-Z. Multiple ranges
are included within the brackets without delimiters. les crochets sans délimiteurs. are included within the brackets without delimiters. están incluidos dentro de los corchetes sin delimitadores. dentro dos colchetes sem domitadores. ограничителей. are included within the brackets without delimiters.
Example: Exemple: Example: Ejemplo: Exemplo: Примеры: Example:
aBBBa' is like 'a*a' aBBBa' est reconnu par l'expression régulière 'a*a' aBBBa' is like 'a*a' aBBBa' es similar 'a*a' aBBBa' é igual 'a*a' aBBBa' аналогично 'a*a' aBBBa' is like 'a*a'
F' is like '[A-Z]' F' est reconnu par l'expression régulière '[A-Z]' F' is like '[A-Z]' F' es similar '[A-Z]' F' é igual '[A-Z]' F' аналогично '[A-Z]' F' is like '[A-Z]'
F' is NOT like '[!A-Z]' F' n'est pas reconnu par l'expression régulière '[!A-Z]' F' is NOT like '[!A-Z]' F' NO es similar '[!A-Z]' F' Não é igual a '[!A-Z]' F' НЕ аналогично '[!A-Z]' F' is NOT like '[!A-Z]'
a2a' is like 'a#a' a2a' est reconnu par l'expression régulière 'a#a' a2a' is like 'a#a' a2a' es similar 'a#a' a2a' é igual a 'a#a' a2a' НЕ аналогично 'a#a' a2a' is like 'a#a'
aM5b' is like 'a[L-P]#[!c-e]' aM5b' est reconnu par l'expression régulière 'a[L-P]#[!c-e]' aM5b' is like 'a[L-P]#[!c-e]' aM5b' es similar 'a[L-P]#[!c-e]' aM5b' é igual a '[L-P]#[!c-e]' aM5b' аналогично 'a[L-P]#[!c-e]' aM5b' is like 'a[L-P]#[!c-e]'
BAT123khg' is like 'B?T*' BAT123khg' est reconnu par l'expression régulière 'B?T*' BAT123khg' is like 'B?T*' BAT123khg' es similar 'B?T*' BAT123khg' é igual a 'B?T*' BAT123khg' аналогично 'B?T*' BAT123khg' is like 'B?T*'
CAT123khg' is NOT like 'B?T*' CAT123khg' n'est pas reconnu par l'expression régulière 'B?T*' CAT123khg' is NOT like 'B?T*' CAT123khg' NO es similar 'B?T*' CAT123khg' Não é igual a 'B?T*' CAT123khg' НЕ аналогично 'B?T*' CAT123khg' is NOT like 'B?T*'
Old Value Ancienne valeur Old Value Valor anterior Valor anterior Старое значение Old Value
New Value Nouvelle valeur New Value Valor nuevo Valor novo Новое значение New Value
SHEET : Column Selection For Data Copy SHEET : Sélection Colonnes pour Copie SHEET : Column Selection For Data Copy SHEET : Selección de columna para Copia SHEET : Seleção de Coluna para Cópia SHEET : Выбор колонок для копирования данных SHEET : Column Selection For Data Copy
This sheet is to be used to indicate the cells/columns for which the contents shall be copied to a new DataList release. Cette FEUILLE est utilisée pour indiquer les cellules pour lesquelles le contenu sera copié dans une nouvelle version de Dataliste. This sheet is to be used to indicate the cells/columns for which the contents shall be copied to a new DataList release. Esta hoja se utiliza para indicar las celdas/columnas para las cuales los contenidos deben ser copiados a una versión Esta Ficha se utiliza para indicar as céluas/colunas para as quais os conteúdos devem ser copiados a uma versão Лист используется при выделении ячеек/колонок, содержимое которых м.б. скопировано в новую версию DataList. This sheet is to be used to indicate the cells/columns for which the contents shall be copied to a new DataList release.
The possible values are : Les valeurs possibles sont : The possible values are : nueva de lista de datos. Los valores posibles son : nova de Lista de Dados. os Valores possíveis são : Возможные значения: The possible values are :
- N : do not copy in any case - N : ne pas copier - N : do not copy in any case - N : No copiar en cualquier caso - N : Não copiar em qualquer caso -N : не копировать в любом случае - N : do not copy in any case
- C : copy in any case (when the line is significant) - C : copier de toute façon (quand la ligne est significative) - C : copy in any case (when the line is significant) - C : copiar solo en cierto caso (cuando la línea es significativa) - C : Copiar só em certo caso (quando a linha é significativa) -С : копировать в любом случае (если линия является значимой) - C : copy in any case (when the line is significant)
- E : copy only if the cell within new release is empty - E : copier seulement si la cellule dans la nouvelle version est vide - E : copy only if the cell within new release is empty - E : copiar solamente si la celda dentro de la nueva versión está vacía - E : Copiar somente se a célula dentro da nova versão está vazia -Е : копировать только в те ячейки, в которых новая версия отсутствует - E : copy only if the cell within new release is empty
SHEET : Matrix SHEET : Matrix SHEET : Matrix SHEET : Matrix SHEET : Matrix SHEET : Matrix SHEET : Matrix
This sheet indicates the cells/columns used for building comparison criteria. Cette FEUILLE indique les cellules/colonnes utilisées pour définir des critères de comparaison. This sheet indicates the cells/columns used for building comparison criteria. Esta hoja indica las celdas/columnas utilizadas para construir criterios de comparación Esta Ficha indica as céluas/colunas utilizadas para construir criterios de comparação Лист используется при выделении ячеек/колонок, используемых для построения критерия сравнения This sheet indicates the cells/columns used for building comparison criteria.
The possible values are : Les valeurs possibles sont : The possible values are : nueva de lista de datos. Los valores posibles son : nova de Lista de Dados. os Valores possíveis são : Возможные значения: The possible values are :
- P : present in all corresponding sheets but the contents shall not be used to build comparison criteria - P : présent dans tout la FEUILLE correspondante mais le contenu ne sera pas employé comme Critère de comparaison - P : present in all corresponding sheets but the contents shall not be used to build comparison criteria - P : presente en todas las hojas correspondientes pero los contenidos no deben ser utilizados para construir criterios de comparación - P : Presente em todas as Fichas correspondentes mas os conteúdos não devem ser utilizados para construir criterios de comparação -P : присутствует во всех соответствующих листах, но содержание не м.б. использовано для построения критерия - P : present in all corresponding sheets but the contents shall not be used to build comparison criteria
- U : present in all corresponding sheets and shall be used to build comparison criteria - U : présent dans toute les FEUILLEs et sera utilisé pour établir un critère de comparaison - U : present in all corresponding sheets and shall be used to build comparison criteria - U : presente en todas las hojas correspondientes y deben ser utilizados para construir criterios de comparación - U : Presente em todas as Fichas correspondentes e devem ser utilizados para construir criterios de comparação -U : присутствует во всех соответствующих листах и м.б. использовано для построения критерия - U : present in all corresponding sheets and shall be used to build comparison criteria
Use this Matrix Case Utiliser ce cas de Matrix Use this Matrix Case Caso utilizar ésta Matriz Caso utilizar ésta Matriz Используйте данных матричный блок Use this Matrix Case
SHEET : HELP_C264 SHEET : AIDE C264 SHEET : HELP_C264 SHEET : AYUDA C264 SHEET : AJUDA C264 SHEET : Помощь по C264 SHEET : HELP_C264
COUNTER INFORMATION FROM IED ENTREES COMPTEUR DE l'IED COUNTER INFORMATION FROM IED INFORMACION CONTADOR DESDE IED Informação CONTADOR deste IED Информация счетчика с IED COUNTER INFORMATION FROM IED
IED name NOM DE l'IED IED name NOMBRE DE IED Nome do IED Имя IED IED name
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
IED Counter Reference Référence de la carte d'entrée Compteur de l'IED IED Counter Reference Referencia Contador IED Referência Contador IED Ссылка счетчика IED IED Counter Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Link Lien Link Vínculo Vínculo Связь Link
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Information Adresse T103: ASDU nb;Fonction type MODBUS: Mapping Adresse;InputFormat DNP3: Adresse IEC: LD;LN T10X MASTER: Information Adresse T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Dirección de información T103: ASDU no;Tipo de función MODBUS: Dirección de mapeo;InputFormat DNP3: Dirección IEC: LD;LN T10X MASTER: Dirección de información T101: Endereço de Informação T103: ASDU no;Tipo de Função MODBUS: Endereço de Mapeamento;InputFormat DNP3: Endereço IEC: LD;LN T10X MASTER: Endereço de Informação T101: адрес информации T103: Номер ASDU ;Тип функции MODBUS: Адрес сигнала;InputFormat DNP3: Адрес IEC: LD;LN T10X MASTER: адрес информации T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address
T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101:Adresse Commune ASDU T103: Information nb;Adresse CommuneASDU MODBUS: Fonction DNP3: Non utilisé IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Adresse Commune ASDU;Data type T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Dirección común ASDU T103: No. de información;Dirección común ASDU MODBUS: Función DNP3: No utilizado IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Dirección común ASDU;Data type T101: Endereço comum ASDU T103: No. de Informação;Endereço comum ASDU MODBUS: Função DNP3: Não Utilizado IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Endereço comum ASDU;Data type T101: Общий адрес ASDU T103: информационный номер;Общий адрес ASDU MODBUS: Функция DNP3: Не используется IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Общий адрес ASDU;Data type T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Counter Type Type du Compteur Counter Type Tipo de Contador Tipo de Contador Противодействие Тип Counter Type
Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Standard: Validation (ms);Invalidité (ms);Cumul (mn) Energy: Facteur d'echelle;Periode de transmission (mn) Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Estándar: Válidación (ms);Inválidación (ms);Cumulación (mn) Energía: Factor de posicionamiento;Periode de la transmisión (mn) Padrão: Validação (ms);Invalidação (ms);Cumulação (mn) Energia: Fator de escala;Periode da transmissão (mn) Стандарт: Проверка (мс);Invalidity (ms);Cumul (mn) Энергия: Scale factor;Период передачи (мс) Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Integrate MV Intègre la MV Integrate MV Integrate MV Integrate MV Integrate MV Integrate MV
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
SELF GENERATED COUNTER INFORMATION ENTREES COMPTEUR AUTOMATIQUES SELF GENERATED COUNTER INFORMATION INFORMACION CONTADOR AUTO GENERADA Informação CONTADOR Auto Gerada Информация, сгенерированная счетчиком SELBSTGENERIERTE COUNTER INFORMATION
SELF GENERATED COUNTER INFORMATION ENTREES COMPTEUR AUTOMATIQUES SELF GENERATED COUNTER INFORMATION INFORMACION CONTADOR AUTO GENERADA Informação CONTADOR Auto Gerada Информация, сгенерированная счетчиком SELBSTGENERIERTE COUNTER INFORMATION
SELF GENERATED COUNTER INFORMATION ENTREES COMPTEUR AUTOMATIQUES SELF GENERATED COUNTER INFORMATION INFORMACION CONTADOR AUTO GENERADA Informação CONTADOR Auto Gerada Информация, сгенерированная счетчиком SELBSTGENERIERTE COUNTER INFORMATION
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
Self Counter Reference Référence interne du compteur Self Counter Reference Referencia Contador auto Referência Contador Automática Собственная ссылка Противодействие Self Counter Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Link Lien Link Vínculo Vínculo Связь Link
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Number Numéro Number Número Número Номер Number
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Counter Type Type du Compteur Counter Type Tipo de Contador Tipo de Contador Противодействие Тип Counter Type
Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Standard: Validation (ms);Invalidité (ms);Cumul (mn) Energy: Facteur d'echelle;Periode de transmission (mn) Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Estándar: Válidación (ms);Inválidación (ms);Cumulación (mn) Energía: Factor de posicionamiento;Periode de la transmisión (mn) Padrão: Validação (ms);Invalidação (ms);Cumulação (mn) Energia: Fator de escala;Periode da transmissão (mn) Стандарт: Проверка (мс);Invalidity (ms);Cumul (mn) Энергия: Scale factor;Период передачи (мс) Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Integrate MV Intègre la MV Integrate MV Integrate MV Integrate MV Integrate MV Integrate MV
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Automation Origin (if any) Automatisme d'origine (si existant) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Counter Profiles Profils Compteurs Counter Profiles Perfiles de Contador Perfis de Contador Профили счетчика Counter Profiles
System Counter Profiles Profils Compteurs systèmes System Counter Profiles Perfiles de systema de Contador Perfis de Systema de Contador Профили системного счетчика System Counter Profiles
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
Counter General Parameters Paramètres généraux du Compteur Counter General Parameters Parámetros generales Contador Parâmetros Geração Contador Основные параметры Борьба Counter General Parameters
Energy equivalent to a pulse Energie équivalente à un pulse Energy equivalent to a pulse Equivalente en energía a un pulso Energia equivalente a um pulso Energy equivalent to a pulse Energy equivalent to a pulse
Computation Calculé Computation Cómputación Computação Вычисление Computation
SBMC dependant Dépendance SBMC SBMC dependant SBMC dependiente SBMC dependente SBMC иждивенца SBMC unterhaltsberechtigte
Graphical Default Format Format graphique par défaut Graphical Default Format Formato gráfico del defecto Formato gráfico do defeito Стандартный графический формат Graphical Default Format
Associated Alarm Parameters Paramètres d'alarme associés à la MV Associated Alarm Parameters Associated Alarm Parameters Associated aoarm Parameters Параметры тревоги Associated Alarm Parameters
Generation Condition Condition de la Génération Generation Condition Condición de generación Condição de Geração Основное условие Generation Condition
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
Counter Processing Parameters Paramètres de traitement du Compteur Counter Processing Parameters Parámetros de procesamiento Contador Parâmetros de Processamento Contador Парметры обработки Борьба Counter Processing Parameters
Valid state label Libellé de l'état valide Valid state label Etiqueta de estado válido Etiqueta de estado válido Метка статуса Valid Valid state label
SelfCheckFault state label Libellé de l'état d'auto vérification du défaut SelfCheckFault state label Etiqueta de estado FallaAutoChequeo Etiqueta de estado FalhaAutoCheque Метка статуса SelfCheckFault SelfCheckFault state label
Unknown state label Libellé de l'état inconnu Unknown state label Etiqueta de estado desconocido Etiqueta de estado Desconhecido Метка статуса Unknown Unknown state label
Forced state label Libellé de l'état forcé Forced state label Etiqueta de estado forzado Etiqueta de estado Forçado Метка статуса Forced Forced state label
OverRange state label Libellé de l'état au-dessus de l'échelle OverRange state label Etiqueta de estado fuera de rango Etiqueta de estado fora de Range Метка статуса OverRange OverRange state label
Undefined state label Libellé de l'état indéfini Undefined state label Etiqueta de estado Indefinido Etiqueta de estado Indefinido Метка статуса Undefined Undefined state label
Treatment on Valid state Traitement sur l'état valide Treatment on Valid state Manipulación en estado válido Manipulação em estado válido Обработка статуса Valid Treatment on Valid state
Treatment on SelfCheckFault state Traitement sur l'état d'auto vérification du défaut Treatment on SelfCheckFault state Manipulación en estado FallaAutoChequeo Manipulação em estado FalhaAutoCheque Обработка статуса SelfCheckFault Treatment on SelfCheckFault state
Treatment on Unknown state Traitement sur l'état inconnu Treatment on Unknown state Manipulación en estado Desconocido Manipulação em estado Desconhecido Обрабока статуса Unknown Treatment on Unknown state
Treatment on Forced state Traitement sur l'état forcé Treatment on Forced state Manipulación en estado Forzado Manipulação em estado Forçado Обработка статуса Forced Treatment on Forced state
Treatment on OverRange state Traitement sur l'état au-dessus de l'échelle Treatment on OverRange state Manipulación en estado fuera de rango Manipulação em estado fora de Range Обработка статуса OverRange Treatment on OverRange state
Treatment on Undefined state Traitement sur l'état indéfini Treatment on Undefined state Manipulación en estado Indefinido Manipulação em estado Indefinido Обработка статуса Undefined Treatment on Undefined state
Treatment on Forcing state Traitement sur l'état de forçage Treatment on Forcing state Manipulación en estado Forzando Manipulação em estado Forzando Обработка статуса Forcing Treatment on Forcing state
Treatment on Substitution state Traitement sur l'état de substitution Treatment on Substitution state Manipulación en estado por sustitución Manipulação em estado por Substituição Обработка статуса Substitution Treatment on Substitution state
Treatment on Suppression state Traitement sur l'état de suppression Treatment on Suppression state Manipulación en estado por supresión Manipulação em estado por Supressão Обработка статуса Suppression Treatment on Suppression state
Alarm and Gravity on Valid state Gravité d'alarme sur l'état valide Alarm and Gravity on Valid state Alarma y gravedad en estado valido Alarme e gravidade em estado vaoido Тревога и важность статуса Valid Alarm and Gravity on Valid state
Alarm and Gravity on SelfCheckFault state Gravité d'alarme sur l'état d'auto vérification du défaut Alarm and Gravity on SelfCheckFault state Alarma y gravedad en estado FallaAutoChequeo Alarme e gravidade em estado FalhaAutoCheque Тревога и важность статуса SelfCheckFault Alarm and Gravity on SelfCheckFault state
Alarm and Gravity on Unknown state Gravité d'alarme sur l'état inconnu Alarm and Gravity on Unknown state Alarma y gravedad en estado desconocido Alarme e gravidade em estado Desconhecido Тревога и важность статуса Unknown Alarm and Gravity on Unknown state
Alarm and Gravity on Forced state Gravité d'alarme sur l'état forcé Alarm and Gravity on Forced state Alarma y gravedad en estado forzado Alarme e gravidade em estado Forçado Тревога и важность статуса Forced Alarm and Gravity on Forced state
Alarm and Gravity on OverRange state Gravité d'alarme sur l'état au-dessus de l'échelle Alarm and Gravity on OverRange state Alarma y gravedad en estado fuera de rango Alarme e gravidade em estado fora de Range Тревога и важность статуса OverRange Alarm and Gravity on OverRange state
Alarm and Gravity on Undefined state Gravité d'alarme sur l'état indéfini Alarm and Gravity on Undefined state Alarma y gravedad en estado Indefinido Alarme e gravidade em estado Indefinido Тревога и важность статуса Undefined Alarm and Gravity on Undefined state
Counter Printing Parameters Paramètres d'impression du Compteur Counter Printing Parameters Parámetros de impresión Contador Parâmetros de Impressão Contador Параметры печати Борьба Counter Printing Parameters
Printed on Sequence Of Events SOE 1 : Imprimer sur l'imprimante Fil de l'eau 1 : Printed on Sequence Of Events SOE 1 : Impreso en SOE 1 : Impresso em SOE 1 : Вывод на SOE 1 : Printed on Sequence Of Events SOE 1 :
Printed on Sequence Of Events SOE 2 : Imprimer sur l'imprimante Fil de l'eau 2 : Printed on Sequence Of Events SOE 2 : Impreso en SOE 2 : Impresso em SOE 1 : Вывод на SOE 2 : Printed on Sequence Of Events SOE 2 :
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
ANALOG OUTPUT BOARD AOU20x Carte de sorties analogiques AOU20x ANALOG OUTPUT BOARD AOU20x TARJETAS DE SALIDAS ANALOGICAS AOU20x Etiquetas de Saídas Analógicas AOU20x ПЛАТЫ AOU20x ANALOGE AUSGANGSKARTE AOU20x
Analog Output Board Number Numéro de la carte de sorties analogiques Analog Output Board Number Número de tarjeta de salidas analógicas Número de Etiqueta de Saídas Analógicas Номер платы AO Analogausgangskarten Nummer
Analog Output Board Slot Position de la carte de sortie analogiques Analog Output Board Slot Slot de Tarjeta de salidas analógicas Slot do Cartão de Saídas Analógicas Слот платы AO Analogausgangskarten Steckplatz
Analog Output Extension Rack Number Numéro rack d'extension de la carte de sorties analogiques Analog Output Extension Rack Number Tarjeta de salidas analógicas Extensión Rack Número Etiqueta de Saídas Analógicas Extensão Rack Número продлению стойки Количество AO Analogausgangskarten Extension Rack Nummer
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
AO Reference Référence AO AO Reference Referencia AO Referência AO Ссылка AO AO Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Slot Position Slot Slot Slot Слот Slot
Channel Voie Channel Canal Canal Канал Channel
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Corresponding Minimal Value Correspond à la valeur minimum Corresponding Minimal Value Valor correspondiente al mínimo Valor correspondente ao Mínimo Значение соответствующее минимуму Corresponding Minimal Value
Corresponding Maximal Value Correspond à la valeur maximum Corresponding Maximal Value Valor correspondiente al Máximo Valor correspondente ao Máximo Значение соответствующее максимуму Corresponding Maximal Value
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
SELF GENERATED SETPOINT INFORMATION SORTIES SETPOINT AUTOMATIQUES SELF GENERATED SETPOINT INFORMATION INFORMACION SETPOINT AUTO GENERADA Informação SETPOINT Auto Gerada Информация, сгенерированная SetPoint SELBSTGENERIERTE SETPOINT INFORMATION
SELF GENERATED SETPOINT INFORMATION SORTIES SETPOINT AUTOMATIQUES SELF GENERATED SETPOINT INFORMATION INFORMACION SETPOINT AUTO GENERADA Informação SETPOINT Auto Gerada Информация, сгенерированная SetPoint SELBSTGENERIERTE SETPOINT INFORMATION
SELF GENERATED SETPOINT INFORMATION SORTIES SETPOINT AUTOMATIQUES SELF GENERATED SETPOINT INFORMATION INFORMACION SETPOINT AUTO GENERADA Informação SETPOINT Auto Gerada Информация, сгенерированная SetPoint SELBSTGENERIERTE SETPOINT INFORMATION
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
SetPoint Reference Référence SetPoint SetPoint Reference Referencia SetPoint Referência SetPoint Ссылка SetPoint SetPoint Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Number Numéro Number Número Número Номер Number
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Corresponding Minimal Value Correspond à la valeur minimum Corresponding Minimal Value Valor correspondiente al mínimo Valor correspondente ao Mínimo Значение соответствующее минимуму Corresponding Minimal Value
Corresponding Maximal Value Correspond à la valeur maximum Corresponding Maximal Value Valor correspondiente al Máximo Valor correspondente ao Máximo Значение соответствующее максимуму Corresponding Maximal Value
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Automation Origin (if any) Automatisme d'origine (si existant) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
SHEET : IEC61850 Model SHEET : Modèles IEC61850 SHEET : IEC61850 Model SHEET : Modelo IEC61850 SHEET : Modo IEC61850 SHEET : Модель IEC61850 SHEET : IEC61850 Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA IEC 61850 DEBUT SCADA IEC 61850 BEGIN SCADA IEC 61850 COMIENZA SCADA IEC 61850 INÍCIO SCADA IEC 61850 НАЧАЛО ОПИСАНИЯ SCADA IEC 61850 BEGIN SCADA IEC 61850
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
TCP/IP Address Adresse TCP/IP TCP/IP Address TCP/IP Dirección TCP/IP Endereço TCP/IP Адрес TCP/IP Address
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
DSP210 BOARD Carte DSP210 DSP210 BOARD TARJETAS DSP210 Placas DSP210 ПЛАТЫ DSP210 KARTE DSP210
DSP210 Board Number Numéro de la carte DSP210 DSP210 Board Number Número de tarjeta DSP210 Número de Etiqueta de DSP210 Номер платы DSP210 DSP210 karte Nummer
DSP210 Board Slot Position de la carte DSP210 DSP210 Board Slot Slot de trajeta DSP210 Slot de trajeta de DSP210 Слот платы DSP210 DSP210 karte Steckplatz
DSP210 Extension Rack Number Numéro rack d'extension de la carte DSP210 DSP210 Extension Rack Number Tarjeta DSP210 Extensión Rack Número Etiqueta de DSP210 Extensão Rack Número продлению стойки Количество DSP210 DSP210 Extension Rack Nummer
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
DO Reference Référence DO DO Reference Referencia DO Referência DO Ссылка DO DO Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Control Contrôle Local Local Control Control Local Controle Local местного контроля Local Control
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Slot Position Slot Slot Slot Слот Slot
Channel Voie Channel Canal Canal Канал Channel
Function Fonction Function Función Função Функция Function
Type (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Simple/DPC=Double/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch) Tipo (SPC=Sencilla/DPC=Dual/DS=Dual Switch) Tipo (SPC=Simples/DPC=Duplo/DS=Dual Switch) Тип (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique =01 (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Control Contrôle LCD LCD Control Control LCD Ordem desde LCD Управление LCD LCD Control
HMI Control Contrôle HMI HMI Control Control IHM Ordem desde IHM Управление HMI HMI Control
Has a xPS Feedback A un retour de position xPS Has a xPS Feedback Contiene retroalimentación xPS Possui FeedBack xPS имеет xPS отзывы Has a xPS Feedback
Is activated by xPS Est activé par xPS Is activated by xPS Es activado por xPS É ativado por xPS Активируется с помощью xPS Is activated by xPS
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Relay Relais Relay Relé Relé Реле Relay
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
SHEET : List of Automations SHEET : Liste des Automatismes SHEET : List of Automations SHEET : Lista de Automations SHEET : Lista de Automations SHEET : Список Automations SHEET : List of Automations
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
AUTOMATIONS INFORMATION INFORMATIONS SUR LES AUTOMATISMES AUTOMATIONS INFORMATION INFORMACION DE AUTOMATIONS Informação de AUTOMATIONS ИНФОРМАЦИЯ ПО AUTOMATIONS AUTOMATIONS INFORMATION
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Number Numéro Number Número Número Номер Number
Automation Name Nom de l'Automatisme Automation Name Nombre de Automation Nome do Automation Имя Automation Automation Name
Automation Type Type d'Automatisme Automation Type Tipo de Automation Tipo de Automation Тип Automation Automation Type
Computer Calculateur Computer Computador Computador Компьютер Computer
Redundant Computer Calculateur Redondant Redundant Computer Computador Redundante Computador Redundante Резервный компьютер Redundant Computer
Issue Révision Issue Revisión Revisão Версия Version
Template Modèle Template Plantilla Panilha Образец Template
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : Equipments IEC Links SHEET : Liste des Liens IEC SHEET : Equipments IEC Links SHEET : Enlaces Equipos IEC SHEET : Ligações de Equipamentos IEC SHEET : аппаратура ссылки IEC SHEET : Equipments IEC Links
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
IEC LINKS INFORMATION INFORMATIONS SUR LES LIENS IEC IEC LINKS INFORMATION IEC LINKS INFORMATION IEC LINKS INFORMATION ИНФОРМАЦИЯ ПО IEC LINKS IEC LINKS INFORMATION
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Clients \ Servers Clients \ Servers Clients \ Servers Clients \ Servers Clients \ Servers Clients \ Servers Clients \ Servers
Issue Révision Issue Revisión Revisão Версия Version
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
Substation 1 Sous-station 1 Substation 1 Subestación 1 Substação 1 подстанции 1 Stations 1
Substation 2 Sous-station 2 Substation 2 Subestación 2 Substação 2 подстанции 2 Stations 2
Substation 3 Sous-station 3 Substation 3 Subestación 3 Substação 3 подстанции 3 Stations 3
Substation 4 Sous-station 4 Substation 4 Subestación 4 Substação 4 подстанции 4 Stations 4
Substation 5 Sous-station 5 Substation 5 Subestación 5 Substação 5 подстанции 5 Stations 5
Substation 6 Sous-station 6 Substation 6 Subestación 6 Substação 6 подстанции 6 Stations 6
Substation 7 Sous-station 7 Substation 7 Subestación 7 Substação 7 подстанции 7 Stations 7
Substation 8 Sous-station 8 Substation 8 Subestación 8 Substação 8 подстанции 8 Stations 8
Substation 9 Sous-station 9 Substation 9 Subestación 9 Substação 9 подстанции 9 Stations 9
Substation 10 Sous-station 10 Substation 10 Subestación 10 Substação 10 подстанции 10 Stations 10
Substation 11 Sous-station 11 Substation 11 Subestación 11 Substação 11 подстанции 11 Stations 11
Substation 12 Sous-station 12 Substation 12 Subestación 12 Substação 12 подстанции 12 Stations 12
Substation 13 Sous-station 13 Substation 13 Subestación 13 Substação 13 подстанции 13 Stations 13
Substation 14 Sous-station 14 Substation 14 Subestación 14 Substação 14 подстанции 14 Stations 14
Substation 15 Sous-station 15 Substation 15 Subestación 15 Substação 15 подстанции 15 Stations 15
Substation 16 Sous-station 16 Substation 16 Subestación 16 Substação 16 подстанции 16 Stations 16
Substation 17 Sous-station 17 Substation 17 Subestación 17 Substação 17 подстанции 17 Stations 17
Substation 18 Sous-station 18 Substation 18 Subestación 18 Substação 18 подстанции 18 Stations 18
Substation 19 Sous-station 19 Substation 19 Subestación 19 Substação 19 подстанции 19 Stations 19
Substation 20 Sous-station 20 Substation 20 Subestación 20 Substação 20 подстанции 20 Stations 20
Substation 21 Sous-station 21 Substation 21 Subestación 21 Substação 21 подстанции 21 Stations 21
Substation 22 Sous-station 22 Substation 22 Subestación 22 Substação 22 подстанции 22 Stations 22
Substation 23 Sous-station 23 Substation 23 Subestación 23 Substação 23 подстанции 23 Stations 23
Substation 24 Sous-station 24 Substation 24 Subestación 24 Substação 24 подстанции 24 Stations 24
Substation 25 Sous-station 25 Substation 25 Subestación 25 Substação 25 подстанции 25 Stations 25
Substation 26 Sous-station 26 Substation 26 Subestación 26 Substação 26 подстанции 26 Stations 26
Substation 27 Sous-station 27 Substation 27 Subestación 27 Substação 27 подстанции 27 Stations 27
Substation 28 Sous-station 28 Substation 28 Subestación 28 Substação 28 подстанции 28 Stations 28
Substation 29 Sous-station 29 Substation 29 Subestación 29 Substação 29 подстанции 29 Stations 29
Substation 30 Sous-station 30 Substation 30 Subestación 30 Substação 30 подстанции 30 Stations 30
Substation 31 Sous-station 31 Substation 31 Subestación 31 Substação 31 подстанции 31 Stations 31
Substation 32 Sous-station 32 Substation 32 Subestación 32 Substação 32 подстанции 32 Stations 32
Substation 33 Sous-station 33 Substation 33 Subestación 33 Substação 33 подстанции 33 Stations 33
Substation 34 Sous-station 34 Substation 34 Subestación 34 Substação 34 подстанции 34 Stations 34
Substation 35 Sous-station 35 Substation 35 Subestación 35 Substação 35 подстанции 35 Stations 35
Substation 36 Sous-station 36 Substation 36 Subestación 36 Substação 36 подстанции 36 Stations 36
Substation 37 Sous-station 37 Substation 37 Subestación 37 Substação 37 подстанции 37 Stations 37
Substation 38 Sous-station 38 Substation 38 Subestación 38 Substação 38 подстанции 38 Stations 38
Substation 39 Sous-station 39 Substation 39 Subestación 39 Substação 39 подстанции 39 Stations 39
Substation 40 Sous-station 40 Substation 40 Subestación 40 Substação 40 подстанции 40 Stations 40
SHEET : SAS Model SHEET : Modèles SAS SHEET : SAS Model SHEET : Modelo SAS SHEET : Modo SAS SHEET : Модель SAS SHEET : SAS Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA SAS DEBUT SCADA SAS BEGIN SCADA SAS COMIENZA SCADA SAS INÍCIO SCADA SAS НАЧАЛО ОПИСАНИЯ SCADA SAS BEGIN SCADA SAS
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Main communication channel Voie de communication principale Main communication channel Canal de comunicación principal Canal de Comunicação Principal Основной канал связи Main communication channel
Auxiliary Communication channel Voie de communication auxiliaire Auxiliary Communication channel Canal de comunciación auxiliar Canal de Comunicação auxiliar Запасной канал связи Auxiliary Communication channel
Baud rate (bit/s) Vitesse de transmission (bit/s) Baud rate (bit/s) Baudios (bit/s) Baud Rate (bit/s) Скорость в бодах (бит/с) Baud rate (bit/s)
Common address of ASDU Adresse commune de l'ASDU Common address of ASDU Dirección común ASDU Endereço comum ASDU Общий адрес ASDU Common address of ASDU
Common address of ASDU Length Longueur de l'adresse commune de l'ASDU Common address of ASDU Length Longitud de la dirección común ASDU Tamanho do Endereço comum ASDU Длина общего адреса ASDU Common address of ASDU Length
Object structure Structure d'objet Object structure Estructura del objeto Estrutura do objeto Структура объекта Object structure
Frame max length Longueur maximale de la vue Frame max length Longitud máx de la trama Tamanho máx do frame Максимальная длина кадра Frame max length
Measurement periodic cycle Cycle Périodique de Mesure Measurement periodic cycle Ciclo de medición periódico Ciclo periódico de Medição Периодический цикл измерений Measurement periodic cycle
Binary Time Size Taille de Temps binaire Binary Time Size Tamaño de tiempo binario Tamanho Binário do Tempo Размер двоичной кодировки времени Binary Time Size
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Send in General Interrogation Envoyé lors de l'Interrogation Générale Send in General Interrogation Enviar en general Interrogatorio Envie em Geral Interrogation Отправить в Генеральной Допрос Senden in den Allgemeinen Interrogation
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Send in General Interrogation Envoyé lors de l'Interrogation Générale Send in General Interrogation Enviar en general Interrogatorio Envie em Geral Interrogation Отправить в Генеральной Допрос Senden in den Allgemeinen Interrogation
MPS Data Type MPS Donnée de Type MPS Data Type MPS Datos tipo MPS Dados tipo MPS Тип данных MPS Data Type
Send in General Interrogation Envoyé lors de l'Interrogation Générale Send in General Interrogation Enviar en general Interrogatorio Envie em Geral Interrogation Отправить в Генеральной Допрос Senden in den Allgemeinen Interrogation
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Format Format Format Formato Formato Формат Format
Cycle Type Type de Cycle Cycle Type Tipo de ciclo Tipo de Ciclo Тип цикла Cycle Type
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : CDC Type II Model SHEET : Modèles CDC Type II SHEET : CDC Type II Model SHEET : Modelo CDC Type II SHEET : Modo CDC Type II SHEET : Модель CDC Type II SHEET : CDC Type II Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA CDC TYPE II DEBUT SCADA CDC TYPE II BEGIN SCADA CDC TYPE II COMIENZA SCADA CDC TYPE II INÍCIO SCADA CDC TYPE II НАЧАЛО ОПИСАНИЯ SCADA CDC TYPE II BEGIN SCADA CDC TYPE II
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Main communication channel Voie de communication principale Main communication channel Canal de comunicación principal Canal de Comunicação Principal Основной канал связи Main communication channel
Auxiliary Communication channel Voie de communication auxiliaire Auxiliary Communication channel Canal de comunciación auxiliar Canal de Comunicação auxiliar Запасной канал связи Auxiliary Communication channel
Baud rate (bit/s) Vitesse de transmission (bit/s) Baud rate (bit/s) Baudios (bit/s) Baud Rate (bit/s) Скорость в бодах (бит/с) Baud rate (bit/s)
Connection timeout (T0) Expiration de la Connexion (T0) Connection timeout (T0) Connection tiempo fuera (T0) Falha de Conexão (T0) Задержка соединения (T0) Connection timeout (T0)
Minimal int Value for Measurement Valeur minimale de mesure Minimal int Value for Measurement Mínimo valor de medición Minimal valor inteiro para Medição Минимальное значение за целое измерение Minimal-Integer-Wert für die Messung
Maximal int Value for Measurement Valeur maximale de mesure Maximal int Value for Measurement Máximo valor de medición Maximal valor inteiro para Medição Максимальное целое значение для измерения Maximale Integer-Wert für die Messung
Int Value for Invalid Measurement Valeur de mesure invalide Int Value for Invalid Measurement Valor no válido para la medición Valor inválido para a medição Стоимость за недействительные измерения Integer-Wert für ungültig Messung
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Sending mode Mode de transmission Sending mode Modo de transmisión Modo de Envio Коробка передач в режиме Übertragungsmodus
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Sending mode Mode de transmission Sending mode Modo de transmisión Modo de Envio Коробка передач в режиме Übertragungsmodus
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : GI74 Model SHEET : Modèles GI74 SHEET : GI74 Model SHEET : Modelo GI74 SHEET : Modo GI74 SHEET : Модель GI74 SHEET : GI74 Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA GI74 DEBUT SCADA GI74 BEGIN SCADA GI74 COMIENZA SCADA GI74 INÍCIO SCADA GI74 НАЧАЛО ОПИСАНИЯ SCADA GI74 BEGIN SCADA GI74
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
TCP/IP Address Adresse TCP/IP TCP/IP Address TCP/IP Dirección TCP/IP Endereço TCP/IP Адрес TCP/IP Address
Network Name NOM DU RESEAU Network Name Nombre de red Nome da rede Сетевое Имя Netzwerk Name
Port 1 : TE address Port 1 : Adresse TE Port 1 : TE address Puerto 1: TE dirección Porto 1: TE endereço Порт 1: TE-адрес Port 1: TE-Adresse
Port 1 : TE block size Port 1 : Taille de bloc TE Port 1 : TE block size Puerto 1: TE tamaño de bloque Porto 1: TE bloco tamanho Порт 1: TE размер блока Port 1: TE Blockgröße
Port 1 : Control Timeout in ms Port 1 : Expiration du contrôle en ms Port 1 : Control Timeout in ms Puerto 1: Control de Tiempo en ms Porto 1: Controlo Timeout em ms Порт 1: Контроль тайм-аута в мс Port 1: Control Timeout in ms
Port 1 : HK control function Port 1 : Fonction de contrôle HK Port 1 : HK control function Puerto 1: función de control de HK Porto 1: HK função de controlo Порт 1: HK функции контроля Port 1 : HK control function
Port 1 : HK control block Port 1 : Bloc de contrôle HK Port 1 : HK control block Puerto 1: bloque de control de HK Porto 1: HK bloco de controlo Порт 1: HK блок управления Port 1 : HK control block
Port 1 : HK control word Port 1 : Mot de contrôle HK Port 1 : HK control word Puerto 1: HK palabra de control Porto 1: HK controlo palavra Порт 1: HK управляющее слово Port 1 : HK control word
Port 2 : TE address Port 2 : Adresse TE Port 2 : TE address Puerto 2: TE dirección Porto 2: TE endereço Порт 2: TE-адрес Port 2: TE-Adresse
Port 2 : TE block size Port 2 : Taille de bloc TE Port 2 : TE block size Puerto 2: TE tamaño de bloque Porto 2: TE bloco tamanho Порт 2: TE размер блока Port 2: TE Blockgröße
Port 2 : Control Timeout in ms Port 2 : Expiration du contrôle en ms Port 2 : Control Timeout in ms Puerto 2: Control de Tiempo en ms Porto 2: Controlo Timeout em ms Порт 2: Контроль тайм-аута в мс Port 2: Control Timeout in ms
Port 2 : HK control function Port 2 : Fonction de contrôle HK Port 2 : HK control function Puerto 2: función de control de HK Porto 2: HK função de controlo Порт 2: HK функции контроля Port 2 : HK control function
Port 2 : HK control block Port 2 : Bloc de contrôle HK Port 2 : HK control block Puerto 2: bloque de control de HK Porto 2: HK bloco de controlo Порт 2: HK блок управления Port 2 : HK control block
Port 2 : HK control word Port 2 : Mot de contrôle HK Port 2 : HK control word Puerto 2: HK palabra de control Porto 2: HK controlo palavra Порт 2: HK управляющее слово Port 2 : HK control word
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Type propagation change Type de changement de propagation Type propagation change Tipo de cambio propagación Tipo de propagação mudança Вид распространения изменений Type propagation change
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Type propagation change Type de changement de propagation Type propagation change Tipo de cambio propagación Tipo de propagação mudança Вид распространения изменений Type propagation change
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
Port for feedback Port de retour Port for feedback Puerto de retroalimentación Porto de retorno Порт для обратной связи Port for feedback
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
Port for feedback Port de retour Port for feedback Puerto de retroalimentación Porto de retorno Порт для обратной связи Port for feedback
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Type measurement Type de la mesure Type measurement Tipo de medición Tipo de medição Тип измерений Type measurement
Type propagation change Type de changement de propagation Type propagation change Tipo de cambio propagación Tipo de propagação mudança Вид распространения изменений Type propagation change
Unit type Type de l'unité Unit type Tipo de unidad Unidade tipo Группы типа Unit type
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : HNZ Model SHEET : Modèles HNZ SHEET : HNZ Model SHEET : Modelo HNZ SHEET : Modo HNZ SHEET : Модель HNZ SHEET : HNZ Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA HNZ DEBUT SCADA HNZ BEGIN SCADA HNZ COMIENZA SCADA HNZ INÍCIO SCADA HNZ НАЧАЛО ОПИСАНИЯ SCADA HNZ BEGIN SCADA HNZ
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Main communication channel Voie de communication principale Main communication channel Canal de comunicación principal Canal de Comunicação Principal Основной канал связи Main communication channel
Auxiliary Communication channel Voie de communication auxiliaire Auxiliary Communication channel Canal de comunciación auxiliar Canal de Comunicação auxiliar Запасной канал связи Auxiliary Communication channel
Baud rate (bit/s) Vitesse de transmission (bit/s) Baud rate (bit/s) Baudios (bit/s) Baud Rate (bit/s) Скорость в бодах (бит/с) Baud rate (bit/s)
Protocol Protocole Protocol Protocolo Protocolo Протокола Protocol
Time Reference Temps de référence Time Reference Tiempo de referencia Tempo de referência Время ссылку Zeitplan
Station address Adresse de la Station Station address Estación de dirección Estação endereço Станция адрес Station address
Network station number Numéro de Station réseau Network station number Número de la estación de red Rede estação número Сетевой номер станции Network station number
RTU Db version RTU version base de donnée RTU Db version Base de datos versión RTU RTU versão base РТУ версию базы данных RTU Db version
Enable concatenation Concatenation possible Enable concatenation Permitir la concatenación Ativar concatenation Включить конкатенация Enable concatenation
Checksum size (fcs) Taille du Checksum (fcs) Checksum size (fcs) Checksum tamaño (fcs) Checksum tamanho (fcs) Checksum размера (fcs) Checksum size (fcs)
Max number of retries Nombre max de tentatives Max number of retries Max number of retries Max number of retries Max number of retries Max number of retries
Inter frame duration Durée inter trame Inter frame duration Duración entre 2 fotogramas Duração entre 2 frames Продолжительность от 2 кадров Inter frame duration
Anticipate rate Taux d'Anticipation Anticipate rate Anticipar tasa Antecipe taxa Предвидеть курс Anticipate rate
Frame max length Longueur maximale de la vue Frame max length Longitud máx de la trama Tamanho máx do frame Максимальная длина кадра Frame max length
Measurement Cycle 1 (s) Cycle de Mesure 1 (s) Measurement Cycle 1 (s) Ciclo de medición 1 (s) Medição ciclo 1 (s) Измерение цикла 1 (s) Measurement Cycle 1 (s)
Measurement Cycle 2 (s) Cycle de Mesure 2 (s) Measurement Cycle 2 (s) Ciclo de medición 2 (s) Medição ciclo 2 (s) Измерение цикла 2 (s) Measurement Cycle 2 (s)
Measurement Cycle 3 (s) Cycle de Mesure 3 (s) Measurement Cycle 3 (s) Ciclo de medición 3 (s) Medição ciclo 3 (s) Измерение цикла 3 (s) Measurement Cycle 3 (s)
Measurement Cycle 4 (s) Cycle de Mesure 4 (s) Measurement Cycle 4 (s) Ciclo de medición 4 (s) Medição ciclo 4 (s) Измерение цикла 4 (s) Measurement Cycle 4 (s)
Fifo : loss information or RTU init address (byte.bit) Fifo : adresse de perte de donnée ou RTU Init (octet.bit) Fifo : loss information or RTU init address (byte.bit) Fifo : pérdida de información de dirección o RTU Init (byte.bit) Fifo : perda informações endereço o RTU Init (byte.bit) Fifo : утрата информации - РТУ иниц адрес (byte.bit) Fifo : loss information or RTU init address (byte.bit)
Fifo : depth of chronologic sorting (ms) Fifo : profondeur de tri chronologique (ms) Fifo : depth of chronologic sorting (ms) Fifo : profundidad de la clasificación cronológica (ms) Fifo : profundidade de triagem cronológico (ms) Fifo : Глубина chronologic сортировка (ms) Fifo : depth of chronologic sorting (ms)
Fifo : empty condition Fifo : condition vide Fifo : empty condition Fifo : condición de vacío Fifo : vazias condição Fifo : пусто условие Fifo : empty condition
Fifo : No activity, retry or supervision delay (ms) Fifo : délai de non activité, nouvelle tentative ou supervision (ms) Fifo : No activity, retry or supervision delay (ms) Fifo : Ninguna actividad, o la supervisión de reintento de retraso (ms) Fifo : Sem atividade, tentar novamente ou supervisão atraso (ms) Fifo : Нет деятельности, повторить или надзор задержка (мс) Fifo : No activity, retry or supervision delay (ms)
RTE : Period to analyze quality of line (s) RTE : Periode d'analyse de qualité de ligne (s) RTE : Period to analyze quality of line (s) RTE : Período para analizar la calidad de la línea (s) RTE : Período para análise da qualidade de linha (s) РTE : Период для анализа качества линии (s) RTE : Period to analyze quality of line (s)
RTE : Bulle message allowed RTE : Message Bulle autorisé RTE : Bulle message allowed RTE : Bulle permitido mensaje RTE : Bulle mensagem permitido РTE : Бюль сообщений разрешен RTE : Bulle message allowed
RTE : Period for sending Bulle message (s) RTE : Periode d'envoi d'un message Bulle (s) RTE : Period for sending Bulle message (s) RTE : Período para el envío de Bulle mensaje (s) RTE : Prazo para envio Bulle mensagem (s) РTE : Срок отправки сообщения Бюль (s) RTE : Period for sending Bulle message (s)
RTE : TOR Battante address (byte.bit) RTE : Adresse de TOR Battante (octet.bit) RTE : TOR Battante address (byte.bit) RTE : TOR Battante dirección (byte.bit) RTE : TOR Battante endereço (byte.bit) РTE : TOР Battante адрес (byte.bit) RTE : TOR Battante address (byte.bit)
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Used cycle Cycle utilisé Used cycle Usado ciclo Usado ciclo Используется цикла Used cycle
Format Format Format Formato Formato Формат Format
Message Structure Structure de message Message Structure Estructura del mensaje Estrutura das mensagens Сообщение Структура Message Structure
Original Value converted Conversion de la valeur originale Original Value converted Valor original convertido Valor original convertido Первоначальная стоимость преобразованы Original Value converted
Sent on variation Envoyé sur variation Sent on variation Enviado en la variación Enviada em variação Переданные по вариации Sent on variation
Variation Mode Mode de variation Variation Mode Modo de variación Modo de variação вариации режиме Variation Mode
Deadband Bande morte Deadband Venda muerta Faixa muerta Порог чувствительности Deadband
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
Format Format Format Formato Formato Формат Format
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
Default Unit Unité par défaut Default Unit Unidad por defecto Unidade padrão Группа по умолчанию Default Unit
Default Unit for datapoint Unité par défaut pour le point de donnée Default Unit for datapoint Unidad por defecto de Datapoint Unidade padrão para Datapoint Группа по умолчанию Datapoint Default Unit for datapoint
Default Unit Unité par défaut Default Unit Unidad por defecto Unidade padrão Группа по умолчанию Default Unit
Default Unit for datapoint Unité par défaut pour le point de donnée Default Unit for datapoint Unidad por defecto de Datapoint Unidade padrão para Datapoint Группа по умолчанию Datapoint Default Unit for datapoint
Default Unit Unité par défaut Default Unit Unidad por defecto Unidade padrão Группа по умолчанию Default Unit
Default Unit for datapoint Unité par défaut pour le point de donnée Default Unit for datapoint Unidad por defecto de Datapoint Unidade padrão para Datapoint Группа по умолчанию Datapoint Default Unit for datapoint
SHEET : T101 MASTER Model SHEET : Modèles T101 MAITRE SHEET : T101 Model MASTER SHEET : Modelo T101 MASTER SHEET : Modo T101 MASTER SHEET : Модель T101 MASTER SHEET : T101 MASTER Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN T101 MASTER DEBUT T101 MAITRE BEGIN T101 MASTER COMIENZA T101 MASTER INÍCIO T101 MASTER НАЧАЛО ОПИСАНИЯ T101 MASTER BEGIN T101 MASTER
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Protocol Name Nom du protocole Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Short name (16 char) Nom court(16 char) Short name (16 char) Nombre corto(16 caract) Nome Curto(16 caract) Сокращенное имя(16 символов) short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Time Reference Temps de référence Time Reference Tiempo de referencia Tempo de referência Время ссылку Zeitplan
number of retries number of retries number of retries number of retries number of retries number of retries number of retries
station address size (bytes) station address size (bytes) station address size (bytes) station address size (bytes) station address size (bytes) station address size (bytes) station address size (bytes)
ASDU address size (bytes) ASDU address size (bytes) ASDU address size (bytes) ASDU address size (bytes) ASDU address size (bytes) ASDU address size (bytes) ASDU address size (bytes)
info address size (bytes) info address size (bytes) info address size (bytes) info address size (bytes) info address size (bytes) info address size (bytes) info address size (bytes)
transmission cause size (bytes) taill cause de transmission (bytes) transmission cause size (bytes) transmission cause size (bytes) transmission cause size (bytes) transmission cause size (bytes) transmission cause size (bytes)
acknowledgement time-out (x 100 ms) acknowledgement time-out (x 100 ms) acknowledgement time-out (x 100 ms) acknowledgement time-out (x 100 ms) acknowledgement time-out (x 100 ms) acknowledgement time-out (x 100 ms) acknowledgement time-out (x 100 ms)
synchronization cycle (x 10 s) synchronization cycle (x 10 s) synchronization cycle (x 10 s) synchronization cycle (x 10 s) synchronization cycle (x 10 s) synchronization cycle (x 10 s) synchronization cycle (x 10 s)
downgraded cycle (x 100 ms) downgraded cycle (x 100 ms) downgraded cycle (x 100 ms) downgraded cycle (x 100 ms) downgraded cycle (x 100 ms) downgraded cycle (x 100 ms) downgraded cycle (x 100 ms)
Type of link Type de lien Type of link Tipo de enlace Tipo de ligação Вид ссылки Art der Verknüpfung
test frame time-out (s) test frame time-out (s) test frame time-out (s) test frame time-out (s) test frame time-out (s) test frame time-out (s) test frame time-out (s)
Inter frame duration Durée inter trame Inter frame duration Duración entre 2 fotogramas Duração entre 2 frames Продолжительность от 2 кадров Inter frame duration
Baud rate (bit/s) Vitesse de transmission (bit/s) Baud rate (bit/s) Baudios (bit/s) Baud Rate (bit/s) Скорость в бодах (бит/с) Baud rate (bit/s)
Legacy IED parameters Legacy IED parameters Legacy IED parameters Legacy IED parameters Legacy IED parameters Legacy IED parameters Legacy IED parameters
automatic disturbance automatic disturbance automatic disturbance automatic disturbance automatic disturbance automatic disturbance automatic disturbance
localisation for disturbance file localisation for disturbance file localisation for disturbance file localisation for disturbance file localisation for disturbance file localisation for disturbance file localisation for disturbance file
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
contact identifier contact identifier contact identifier contact identifier contact identifier contact identifier contact identifier
MPS Data Type MPS Donnée de Type MPS Data Type MPS Datos tipo MPS Dados tipo MPS Тип данных MPS Data Type
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
order type Type de commande order type Tipo de orden Tipo de Ordem Тип команды order type
acknowledgement delay délai d'acquittement acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
order type Type de commande order type Tipo de orden Tipo de Ordem Тип команды order type
contact type Type de contact contact type contact tipo contact tipo Τύπος επαφής contact type
acknowledgement delay délai d'acquittement acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
output format output format output format output format output format output format output format
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
order type Type de commande order type Tipo de orden Tipo de Ordem Тип команды order type
output format output format output format output format output format output format output format
minimal value minimal value minimal value minimal value minimal value minimal value minimal value
maximal value maximal value maximal value maximal value maximal value maximal value maximal value
acknowledgement delay délai d'acquittement acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay
Counter Data Type Compteur de Donnée de Type Counter Data Type Counter Datos tipo Contador de Dados tipo Counter Тип данных Counter Data Type
output format output format output format output format output format output format output format
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : T104 MASTER Model SHEET : Modèles T104 MAITRE SHEET : T104 MASTER Model SHEET : Modelo T101 MASTER SHEET : Modo T101 MASTER SHEET : Модель T101 MASTER SHEET : T101 MASTER Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN T104 MASTER DEBUT T104 MAITRE BEGIN T104 MASTER COMIENZA T104 MASTER INÍCIO T104 MASTER НАЧАЛО ОПИСАНИЯ T104 MASTER BEGIN T104 MASTER
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Protocol Name Nom du protocole Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Short name (16 char) Nom court(16 char) Short name (16 char) Nombre corto(16 caract) Nome Curto(16 caract) Сокращенное имя(16 символов) short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Time Reference Référence horaire Time Reference Tiempo de referencia Tempo de referência Время ссылку Zeitplan
TCP/IP Address Adresse TCP/IP TCP/IP Address TCP/IP Address TCP/IP Address TCP/IP Address TCP/IP Address
Redundant TCP/IP Address Adresse TCP/IP redondée Redundant TCP/IP Address TCT/IP Address redundante TCP/IP Address redundante Redundant TCP/IP Address Redundant TCP/IP Address
t0: connection established timeout (s) t0: délai d'établissement de connexion (s) t0: connection established timeout (s) t0: connection established timeout (s) t0: connection established timeout (s) t0: connection established timeout (s) t0: connection established timeout (s)
t1: APDUs send or test time out (s) t1: délai d'envoi ou test d'APDU (s) t1: APDUs send or test time out (s) t1: APDUs send or test time out (s) t1: APDUs send or test time out (s) t1: APDUs send or test time out (s) t1: APDUs send or test time out (s)
t2: acknowledges in case of no data time out (s) t2: délai d'acquittement si pas de données (s) t2: acknowledges in case of no data time out (s) t2: acknowledges in case of no data time out (s) t2: acknowledges in case of no data time out (s) t2: acknowledges in case of no data time out (s) t2: acknowledges in case of no data time out (s)
t3: test frame sending in case of no data timeout (s) t3: délai d'envoi de trame de test en cas d'état en veille (s) t3: test frame sending in case of no data timeout (s) t3: test frame sending in case of no data timeout (s) t3: test frame sending in case of no data timeout (s) t3: test frame sending in case of no data timeout (s) t3: test frame sending in case of no data timeout (s)
k: window size of transmitted unacknowledged frames k: taille de la fenêtre des trames non transmises k: window size of transmitted unacknowledged frames k: window size of transmitted unacknowledged frames k: window size of transmitted unacknowledged frames k: window size of transmitted unacknowledged frames k: window size of transmitted unacknowledged frames
w: window size of acknowledged received frames w: taille de la fenêtre des trames reçues w: window size of acknowledged received frames w: window size of acknowledged received frames w: window size of acknowledged received frames w: window size of acknowledged received frames w: window size of acknowledged received frames
synchronization cycle (x 10s) Cycle de synchronisation (x 10s) synchronization cycle (x 10s) synchronization cycle (x 10s) synchronization cycle (x 10s) synchronization cycle (x 10s) synchronization cycle (x 10s)
Inter frame duration Durée inter trame Inter frame duration Duración entre 2 fotogramas Duração entre 2 frames Продолжительность от 2 кадров Inter frame duration
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
contact identifier Identifiant contact contact identifier contact identifier contact identifier contact identifier contact identifier
MPS Data Type MPS Donnée de Type MPS Data Type MPS Datos tipo MPS Dados tipo MPS Тип данных MPS Data Type
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
order type Type de commande order type Tipo de orden Tipo de Ordem Тип команды order type
acknowledgement delay Délai acquittement acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
order type Type de commande order type Tipo de orden Tipo de Ordem Тип команды order type
contact type Type de contact contact type contact tipo contact tipo Τύπος επαφής contact type
acknowledgement delay Délai acquittement acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
output format Format de sortie output format output format output format output format output format
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
order type Type de commande order type Tipo de orden Tipo de Ordem Тип команды order type
output format Format de sortie output format output format output format output format output format
minimal value Valeur minimale minimal value minimal value minimal value minimal value minimal value
maximal value Valeur maximale maximal value maximal value maximal value maximal value maximal value
acknowledgement delay Délai acquittement acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay
Counter Data Type Compteur de Donnée de Type Counter Data Type Counter Datos tipo Contador de Dados tipo Counter Тип данных Counter Data Type
output format Format de sortie output format output format output format output format output format
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
GE Standard Signals for 765kV Level
Revision History
Rev.No Description of Remarks Date Remarks
02 Old Signal list --
03 1. Distance relay - Missing internal signals related to functions such as AR, Weak-infeed, SOTF. 2. Addition of Differential Protection signals 3. Addition of Transformer phase wise Mechanical tripping signals 4. Addition of Centralized Busbar protection related signals. 5. Addition of tertiary transformer related protection signals. 6. Addition of Backup impedance protection signals for ICT & Reactor. 7. Addition of Directional OC & EF protection signals for ICT. 8. Addition of Mechanical trippings & alarms associated with REF. 9. Addition of NGR associated protection & CB Alarms 10. Addition of De-centralised - Busbar protection signals 11. Addition of Breaker failure protection initiation & Re-trip signals in standalone & centralized busbar protection 12. Addition of BCU – AR associated internal signals, TC phase wise, CSD related alarms, Bay wise measurements 16.01.2024
REVISION 3- STANDARD SIGNAL LIST FOR GE
BAY NUMBERS ARE SYMBOLIC. FOLLOWING IEDS REPRESENT THE APPLICATIONS AS MENTIONED BELOW.
WORKSHEET NO. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 P141 IEC BB7_P141_BVMT1 MEASUREMENT INPUT RELAY BHWD700BVMT1 If IED reports to HMI
2 P141 IEC BB7_P141_BVMT2 MEASUREMENT INPUT RELAY BHWD700BVMT2 If IED reports to HMI
3 P741 IEC BB7_P741_87CUA BUSBAR PROTECTION(DISTRIBUTED) MAIN 1 RELAY FOR 765KV BHWD700BBM1 Where same IED protects both Bus 1 & 2
4 P741 IEC BB7_P741_87CUB BUSBAR PROTECTION(DISTRIBUTED) MAIN 2 RELAY FOR 765KV BHWD700BBM2 Where same IED protects both Bus 1 & 2
5 P444 IEC R707_P444_21M1 LINE DISTANCE RELAY MAIN-1 BHWD7XXM1DIS Bay No. 7XX will be always the main bay number for the Line feeder
6 D60 IEC R707_D60_21M1 LINE DISTANCE RELAY MAIN-1 BHWD7XXM1DIS Bay No. 7XX will be always the main bay number for the Line feeder
7 P643 IEC R707_P643_87R REACTOR DIFFERENTIAL RELAY BHWD7XXLRDF Bay No. 7XX will be always the main bay number for the Line feeder
8 P141 IEC R707_P141_64R REACTOR REF RELAY BHWD7XXLRREF Bay No. 7XX will be always the main bay number for the Line feeder
9 P442 IEC R707_P442_21R REACTOR BACKUP IMPEDANCE RELAY BHWD7XXLRBU Bay No. 7XX will be always the main bay number for the Line feeder
10 P743 IEC R707_P743_50BF LINE REACTOR BREAKER FAILURE RELAY BHWD7XXLRBBFR Bay No. 7XX will be always the main bay number for the Line feeder. This IED name will be for switchable breaker's BFR relay and will beused Only if standalone reporting directly to HMI
11 P743 IEC R707_P743_PU_A LINE BAY PU-1 BHWD7XXM1PU Only if standalone reporting directly to HMI. Includes BFR related signals also
12 P743 IEC R707_P743_PU_B LINE BAY PU-2 BHWD7XXM2PU Only if standalone reporting directly to HMI. Includes BFR related signals also
13 P743 IEC R708_P743_50BF STANDALONE BREAKER FAILURE RELAY FOR TIE BREAKER BHWD7XXBFR Only if standalone reporting directly to HMI
14 P645 IEC R712_P645_87T ICT DIFFERENTIAL RELAY BHWD7XXTDIF Bay No. 7XX will be always the main bay number for the ICT feeder
15 P643 IEC R712_P643_64T ICT REF RELAY BHWD7XXTREF Bay No. 7XX will be always the main bay number for the ICT feeder
16 P442 IEC R712_P442_67 HV ICT HV OVERCURRENT RELAY BHWD7XXTHVBU Bay No. 7XX will be always the main bay number for the ICT feeder
17 P442 IEC R712_P442_67 LV ICT LV OVERCURRENT RELAY BHWD7XXTLVBU Bay No. 7XX will be always the main bay number for the ICT feeder
18 P141 IEC R712_P141_64S ICT SPARE PHASE REF RELAY BHWDB1SPTREF No Bay no. to be assigned.
19 P743 IEC R712_P743_PU_A ICT/REACTOR PU-1 BHWD7XXM1PU Only if standalone reporting directly to HMI. Includes BFR related signals also
20 P743 IEC R712_P743_PU_B ICT/REACTOR PU-2 BHWD7XXM2PU Only if standalone reporting directly to HMI. Includes BFR related signals also
21 BCU BCU B707_LINE LINE BCU BHWD7XXBCU BCU is for each bay so 7XX refers to Bay
22 BCU BCU B707_LR LINE REACTOR BCU BHWD7XXBCU BCU is for each bay so 7XX refers to Bay
23 BCU BCU B708_TIE TIE BAY BCU BHWD7XXBCU BCU is for each bay so 7XX refers to Bay
24 BCU BCU B712_ICT ICT BCU-1 BHWD7XXBCU For single phase ICT & Reactor & schemes additional BCU may be required. The first BCU will control the main bay switchgear and thus will be reeferrred by Bay no., the additional BCU will be have T or R depending on usage for Reactor or ICT and will control the Bank isolators and earthswitches.
25 BCU BCU B712_ICT T ICT BCU-2 BHWD7XXBCUT
26 BCU BCU B712_ICT_64X ICT 64 RELAY I/O EXTENDER IED name is not required as it is integrated through an IED
27 Time Synch TIME SYNC ADDRESS FOR ALL BCUS IS GIVEN IN THIS SHEET
28 P747 IEC 7BB1_P747_87_B BUS BAR PROTECTION(CENTRALIZED) MAIN-1 B PHASE BHWD7BB1M1R for IED of Bus 2 the name would be BHWD7BB1M1R
29 P747 IEC 7BB1_P747_87_R BUS BAR PROTECTION(CENTRALIZED) MAIN-1 R PHASE BHWD7BB1M1Y for IED of Bus 2 the name would be BHWD7BB1M1Y
30 P747 IEC 7BB1_P747_87_Y BUS BAR PROTECTION(CENTRALIZED) MAIN-1 Y PHASE BHWD7BB1M1B for IED of Bus 2 the name would be BHWD7BB1M1B
31 P747 IEC 7BB2_P747_87_B BUS BAR PROTECTION(CENTRALIZED) MAIN-2 B PHASE BHWD7BB1M2R for IED of Bus 2 the name would be BHIWDB1BB2M2R
32 P747 IEC 7BB2_P747_87_R BUS BAR PROTECTION(CENTRALIZED) MAIN-2 R PHASE BHWD7BB1M2Y for IED of Bus 2 the name would be BHIWDB1BB2M2RY
33 P747 IEC 7BB2_P747_87_Y BUS BAR PROTECTION(CENTRALIZED) MAIN-2 Y PHASE BHWD7BB1M2B for IED of Bus 2 the name would be BHIWDB1BB2M2B
** Each IED has to be 5 GGIO signal spare signals need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
** PLEASE NOTE THAT ALL BCU SHOULD HAVE TIME SYNC SIGNAL. HERE THEY ARE MENTIONED IN SEPARATE SHEET.
** The code BHWD in the IED name will be provided by POWERGRID for each substation that will be unique for database management.7XX refers to the bay.
** IEC61850 Node has to be from the Native node specfically for the protection related.
** IEC61850 Node has to be adopted as per the Edition -1 & Edition-2
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name BB7_P141_BVMT1 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : BB7_P141_BVMT1
DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV BB7_P141_BVMT1 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Normal_Fail SPS 765kV BB7_P141_BVMT1 GOOSE CVT FUSE Fail Normal NL_FL_CVT FUSE Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
A System;GosGGIO2 ST;Ind2;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV BB7_P141_BVMT1 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind2;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLA_Normal_Fail SPS 765kV BB7_P141_BVMT1 SYSTEM DC SOURCE-2 Fail Normal NL_FL_DC SOURCE2 Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
A SPARE Hz 765kV BB7_P141_BVMT1 SYSTEM FREQUENCY 45.0 55.0 FREQUENCY Transmitted to IEC Measurements;PriFouMMXU1 MX;Hz;mag;MV None No 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
A SPARE kV 765kV BB7_P141_BVMT1 SYSTEM R-Y VOLTAGE 0.0 918.0 R-Y VOLTAGE Transmitted to IEC Measurements;PriFouMMXU1 MX;PPV;phsAB;DELTA None No 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
A SPARE kV 765kV BB7_P141_BVMT1 SYSTEM Y-B VOLTAGE 0.0 918.0 Y-B VOLTAGE Transmitted to IEC Measurements;PriFouMMXU1 MX;PPV;phsBC;DELTA None No 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
A SPARE kV 765kV BB7_P141_BVMT1 SYSTEM B-R VOLTAGE 0.0 918.0 B-R VOLTAGE Transmitted to IEC Measurements;PriFouMMXU1 MX;PPV;phsCA;DELTA None No 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
SPS 765kV BB7_P141_BVMT1 SYSTEM SETTINGS CHANGED Set Reset
A SPARE None No 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
A SPARE None No 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
A SPARE None No 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
A SPARE None No 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
A SPARE None No 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
A SPARE None No 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
A SPARE ** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
A SPARE ** Any additional Signals as per Scheme & TS 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT1
ANALOG INFORMATION FROM IED IED name BB7_P141_BVMT1
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Measurements;PriFouMMXU1 MX;Hz;mag;MV MV_HLa_Frequency 6 ANALOG INFORMATION FROM IED IED name BB7_P141_BVMT1
A Measurements;PriFouMMXU1 MX;PPV;phsAB;DELTA MV_HLa_Voltage_2 6 ANALOG INFORMATION FROM IED IED name BB7_P141_BVMT1
A Measurements;PriFouMMXU1 MX;PPV;phsBC;DELTA MV_HLa_Voltage_2 6 ANALOG INFORMATION FROM IED IED name BB7_P141_BVMT1
A Measurements;PriFouMMXU1 MX;PPV;phsCA;DELTA MV_HLa_Voltage_2 6 ANALOG INFORMATION FROM IED IED name BB7_P141_BVMT1
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB7_P141_BVMT1
ANALOG INFORMATION TO IED IED name BB7_P141_BVMT1
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name BB7_P141_BVMT1
A SPARE 13 ANALOG INFORMATION TO IED IED name BB7_P141_BVMT1
COUNTER INFORMATION FROM IED IED name BB7_P141_BVMT1
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P141_BVMT1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P141_BVMT1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P141_BVMT1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P141_BVMT1
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name BB7_P141_BVMT2 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : BB7_P141_BVMT2
DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT2
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV BB7_P141_BVMT2 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT2
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Normal_Fail SPS 765kV BB7_P141_BVMT2 GOOSE CVT FUSE Fail Normal NL_FL_CVT FUSE Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT2
A System;GosGGIO2 ST;Ind2;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV BB7_P141_BVMT2 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind2;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT2
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLA_Normal_Fail SPS 765kV BB7_P141_BVMT2 SYSTEM DC SOURCE-1 Fail Normal NL_FL_DC SOURCE1 Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT2
A SPARE Hz 765kV BB7_P141_BVMT2 SYSTEM FREQUENCY 45.0 55.0 FREQUENCY Transmitted to IEC Measurements;PriFouMMXU1 MX;Hz;mag;MV None No 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT2
A SPARE kV 765kV BB7_P141_BVMT2 SYSTEM R-Y VOLTAGE 0.0 918.0 R-Y VOLTAGE Transmitted to IEC Measurements;PriFouMMXU1 MX;PPV;phsAB;DELTA None No 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT2
A SPARE kV 765kV BB7_P141_BVMT2 SYSTEM Y-B VOLTAGE 0.0 918.0 Y-B VOLTAGE Transmitted to IEC Measurements;PriFouMMXU1 MX;PPV;phsBC;DELTA None No 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT2
A SPARE kV 765kV BB7_P141_BVMT2 SYSTEM B-R VOLTAGE 0.0 918.0 B-R VOLTAGE Transmitted to IEC Measurements;PriFouMMXU1 MX;PPV;phsCA;DELTA None No 1 DIGITAL INFORMATION FROM IED IED name BB7_P141_BVMT2
SPS 765kV BB7_P141_BVMT1 SYSTEM SETTINGS CHANGED Set Reset
A SPARE None No 1 0
A SPARE None No 1 0
A SPARE None No 1 0
A SPARE None No 1 0
A SPARE None No 1 0
A SPARE ** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database None No 1 0
A SPARE ** Any additional Signals as per Scheme & TS None No 1 0
ANALOG INFORMATION FROM IED IED name BB7_P141_BVMT2
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Measurements;PriFouMMXU1 MX;Hz;mag;MV MV_HLa_Frequency 6 ANALOG INFORMATION FROM IED IED name BB7_P141_BVMT2
A Measurements;PriFouMMXU1 MX;PPV;phsAB;DELTA MV_HLa_Voltage_2 6 ANALOG INFORMATION FROM IED IED name BB7_P141_BVMT2
A Measurements;PriFouMMXU1 MX;PPV;phsBC;DELTA MV_HLa_Voltage_2 6 ANALOG INFORMATION FROM IED IED name BB7_P141_BVMT2
A Measurements;PriFouMMXU1 MX;PPV;phsCA;DELTA MV_HLa_Voltage_2 6 ANALOG INFORMATION FROM IED IED name BB7_P141_BVMT2
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB7_P141_BVMT2
ANALOG INFORMATION TO IED IED name BB7_P141_BVMT2
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name BB7_P141_BVMT2
A SPARE 13 ANALOG INFORMATION TO IED IED name BB7_P141_BVMT2
COUNTER INFORMATION FROM IED IED name BB7_P141_BVMT2
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P141_BVMT2
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P141_BVMT2
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P141_BVMT2
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P141_BVMT2
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name BB7_P741_87CUA GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : BB7_P741_87CUA
DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUA
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV BB7_P741_87CUA PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUA
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV BB7_P741_87CUA GOOSE B/B ZONE-1/2 Operated Reset RS_OP_ZONE1/2 Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS 113;193;227;284;318;375;410;76; None Yes 1 DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUA
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV BB7_P741_87CUA PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUA
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 765kV BB7_P741_87CUA PROTECTION ZONE-1 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 1 Transmitted to IEC System;GosGGIO2 ST;Ind5;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUA
SPS 765kV BB7_P741_87CUA PROTECTION ZONE-2 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 2 Transmitted to IEC System;GosGGIO2 ST;Ind6;stVal;SPS
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 765kV BB7_P741_87CUA PROTECTION Z1 BUSBAR BLOCKED DUE TO COMM. ERR Set Reset RS_ST_BB BLOCKC1 Transmitted to IEC System;GosGGIO2 ST;Ind7;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUA
SPS 765kV BB7_P741_87CUA PROTECTION Z2 BUSBAR BLOCKED DUE TO COMM. ERR Set Reset RS_ST_BB BLOCKC2 Transmitted to IEC System;GosGGIO2 ST;Ind8;stVal;SPS
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 765kV BB7_P741_87CUA PROTECTION ZONE-1 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI1 Transmitted to IEC System;GosGGIO2 ST;Ind9;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUA
SPS 765kV BB7_P741_87CUA PROTECTION ZONE-2 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI2 Transmitted to IEC System;GosGGIO2 ST;Ind10;stVal;SPS
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLa_Reset_In SPS 765kV BB7_P741_87CUA SYSTEM MAIN-1 B/B ZONE-1 In Reset RS_IN_M1 BB Z1 Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUA
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 765kV BB7_P741_87CUA SYSTEM 87CUB RELAY Healthy Unhealthy UH_HL_87CUB Transmitted to IEC System;OptGGIO1 ST;Ind3;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 765kV BB7_P741_87CUA SYSTEM BBMT2 RELAY Healthy Unhealthy UH_HL_BBMT2 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLa_Reset_In SPS 765kV BB7_P741_87CUA SYSTEM MAIN-1 B/B ZONE-2 In Reset RS_IN_M1 BB Z2 Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A Protection;CftPhsPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV BB7_P741_87CUA PROTECTION ZONE-1 CIRCUITRY FAULT Operated Reset RS_OP_ZONE1 CFT Transmitted to IEC Protection;CftPhsPDIF1 ST;Op;general;general;ACT None 1 #REF!
A Protection;CftPhsPDIF2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV BB7_P741_87CUA PROTECTION ZONE-2 CIRCUITRY FAULT Operated Reset RS_OP_ZONE2 CFT Transmitted to IEC Protection;CftPhsPDIF2 ST;Op;general;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765kV BB7_P741_87CUA PROTECTION B/B ZONE-1 TRIP Operated Reset RS_OP_ZONE1 Transmitted to IEC Protection;TrpPhsPDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765kV BB7_P741_87CUA PROTECTION B/B ZONE-2 TRIP Operated Reset RS_OP_ZONE2 Transmitted to IEC Protection;TrpPhsPDIF2 ST;Op;general;ACT None 1 #REF!
SPS 765kV BB7_P741_87CUA PROTECTION BUSBAR ZONE 1 R- PHASE TRIP Operated Reset RS_OP_ZONE1_R Protection;TrpPhsPDIF1 ST;Op;phs1
SPS 765kV BB7_P741_87CUA PROTECTION BUSBAR ZONE 1 Y- PHASE TRIP Operated Reset RS_OP_ZONE1_Y Protection;TrpPhsPDIF1 ST;Op;phs2
SPS 765kV BB7_P741_87CUA PROTECTION BUSBAR ZONE 1 B- PHASE TRIP Operated Reset RS_OP_ZONE1_B Protection;TrpPhsPDIF1 ST;Op;phs3
SPS 765kV BB7_P741_87CUA PROTECTION BUSBAR ZONE 2 R- PHASE TRIP Operated Reset RS_OP_ZONE2_R Protection;TrpPhsPDIF2 ST;Op;phs1
SPS 765kV BB7_P741_87CUA PROTECTION BUSBAR ZONE 2 Y- PHASE TRIP Operated Reset RS_OP_ZONE2_Y Protection;TrpPhsPDIF2 ST;Op;phs2
SPS 765kV BB7_P741_87CUA PROTECTION BUSBAR ZONE 2 B- PHASE TRIP Operated Reset RS_OP_ZONE2_B Protection;TrpPhsPDIF2 ST;Op;phs3
SPS 765kV BB7_P741_87CUA PROTECTION CHECK ZONE Operated Reset RS_OP_CHECKZONE
SPS 765kV BB7_P741_87CUA PROTECTION SETTINGS CHANGED Set Reset
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
A SPARE ** Any additional Signals as per Scheme & TS None No 1 #REF!
DIGITAL INFORMATION TO IED IED name BB7_P741_87CUA
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUA
ANALOG INFORMATION FROM IED IED name BB7_P741_87CUA
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB7_P741_87CUA
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB7_P741_87CUA
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB7_P741_87CUA
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB7_P741_87CUA
ANALOG INFORMATION TO IED IED name BB7_P741_87CUA
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name BB7_P741_87CUA
A SPARE 13 ANALOG INFORMATION TO IED IED name BB7_P741_87CUA
COUNTER INFORMATION FROM IED IED name BB7_P741_87CUA
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P741_87CUA
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P741_87CUA
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P741_87CUA
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P741_87CUA
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name BB7_P741_87CUB GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : BB7_P741_87CUB
DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUB
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV BB7_P741_87CUB PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUB
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV BB7_P741_87CUB GOOSE B/B ZONE-1/2 Operated Reset RS_OP_ZONE1/2 Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS 113;193;227;284;318;375;410;76; None Yes 1 DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUB
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV BB7_P741_87CUB PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUB
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 765kV BB7_P741_87CUB PROTECTION ZONE-1 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 1 Transmitted to IEC System;GosGGIO2 ST;Ind5;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUB
SPS 765kV BB7_P741_87CUB PROTECTION ZONE-2 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 2 Transmitted to IEC System;GosGGIO2 ST;Ind6;stVal;SPS
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 765kV BB7_P741_87CUB PROTECTION Z1 BUSBAR BLOCKED DUE TO COMM. ERR Set Reset RS_ST_BB BLOCKC1 Transmitted to IEC System;GosGGIO2 ST;Ind7;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUB
SPS 765kV BB7_P741_87CUB PROTECTION Z2 BUSBAR BLOCKED DUE TO COMM. ERR Set Reset RS_ST_BB BLOCKC2 Transmitted to IEC System;GosGGIO2 ST;Ind8;stVal;SPS
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 765kV BB7_P741_87CUB PROTECTION ZONE-1 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI1 Transmitted to IEC System;GosGGIO2 ST;Ind9;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUB
SPS 765kV BB7_P741_87CUB PROTECTION ZONE-2 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI2 Transmitted to IEC System;GosGGIO2 ST;Ind10;stVal;SPS
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLa_Reset_In SPS 765kV BB7_P741_87CUB SYSTEM MAIN-2 B/B ZONE-1 In Reset RS_IN_M2 BB Z1 Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name BB7_P741_87CUB
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 765kV BB7_P741_87CUB SYSTEM 87CUA RELAY Healthy Unhealthy UH_HL_87CUA Transmitted to IEC System;OptGGIO1 ST;Ind3;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 765kV BB7_P741_87CUB SYSTEM BBMT1 RELAY Healthy Unhealthy UH_HL_BBMT1 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLa_Reset_In SPS 765kV BB7_P741_87CUB SYSTEM MAIN-2 B/B ZONE-2 In Reset RS_IN_M2 BB Z2 Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A Protection;CftPhsPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV BB7_P741_87CUB PROTECTION ZONE-1 CIRCUITRY FAULT Operated Reset RS_OP_ZONE1 CFT Transmitted to IEC Protection;CftPhsPDIF1 ST;Op;general;general;ACT None 1 #REF!
A Protection;CftPhsPDIF2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV BB7_P741_87CUB PROTECTION ZONE-2 CIRCUITRY FAULT Operated Reset RS_OP_ZONE2 CFT Transmitted to IEC Protection;CftPhsPDIF2 ST;Op;general;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765kV BB7_P741_87CUB PROTECTION B/B ZONE-1 Operated Reset RS_OP_ZONE1 Transmitted to IEC Protection;TrpPhsPDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765kV BB7_P741_87CUB PROTECTION B/B ZONE-2 Operated Reset RS_OP_ZONE2 Transmitted to IEC Protection;TrpPhsPDIF2 ST;Op;general;ACT None 1 #REF!
SPS 765kV BB7_P741_87CUB PROTECTION BUSBAR ZONE 1 R- PHASE TRIP Operated Reset RS_OP_ZONE1_R Protection;TrpPhsPDIF1 ST;Op;phs1
SPS 765kV BB7_P741_87CUB PROTECTION BUSBAR ZONE 1 Y- PHASE TRIP Operated Reset RS_OP_ZONE1_Y Protection;TrpPhsPDIF1 ST;Op;phs2
SPS 765kV BB7_P741_87CUB PROTECTION BUSBAR ZONE 1 B- PHASE TRIP Operated Reset RS_OP_ZONE1_B Protection;TrpPhsPDIF1 ST;Op;phs3
SPS 765kV BB7_P741_87CUB PROTECTION BUSBAR ZONE 2 R- PHASE TRIP Operated Reset RS_OP_ZONE2_R Protection;TrpPhsPDIF2 ST;Op;phs1
SPS 765kV BB7_P741_87CUB PROTECTION BUSBAR ZONE 2 Y- PHASE TRIP Operated Reset RS_OP_ZONE2_Y Protection;TrpPhsPDIF2 ST;Op;phs2
SPS 765kV BB7_P741_87CUB PROTECTION BUSBAR ZONE 2 B- PHASE TRIP Operated Reset RS_OP_ZONE2_B Protection;TrpPhsPDIF2 ST;Op;phs3
SPS 765kV BB7_P741_87CUB PROTECTION CHECK ZONE Operated Reset RS_OP_CHECKZONE
SPS 765kV BB7_P741_87CUB PROTECTION SETTINGS CHANGED Set Reset
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
A SPARE ** Any additional Signals as per Scheme & TS None No 1 #REF!
DIGITAL INFORMATION TO IED IED name BB7_P741_87CUB
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB7_P741_87CUB
ANALOG INFORMATION FROM IED IED name BB7_P741_87CUB
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB7_P741_87CUB
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB7_P741_87CUB
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB7_P741_87CUB
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB7_P741_87CUB
ANALOG INFORMATION TO IED IED name BB7_P741_87CUB
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name BB7_P741_87CUB
A SPARE 13 ANALOG INFORMATION TO IED IED name BB7_P741_87CUB
COUNTER INFORMATION FROM IED IED name BB7_P741_87CUB
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P741_87CUB
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P741_87CUB
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P741_87CUB
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB7_P741_87CUB
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R707_P444_21M1 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R707_P444_21M1
DIGITAL INFORMATION FROM IED IED name R707_P444_21M1
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P444_21M1 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P444_21M1
A System;AlmGGIO1 ST;Alm6;stVal;SPS SPE_HLA_Normal_Fail SPS 765kV R707_P444_21M1 PROTECTION VT FUSE Alarm Normal NL_FL_VT-FUSE Transmitted to IEC System;AlmGGIO1 ST;Alm6;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P444_21M1
A System;AlmGGIO1 ST;Alm31;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION BROKEN CONDUCTOR Alarm Normal RS_OP_BRKN CND Transmitted to IEC System;AlmGGIO1 ST;Alm31;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P444_21M1
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION STUB PROTECTION Operated Reset RS_OP_STUB Transmitted to IEC System;GosGGIO2 ST;Ind3;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind15;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P444_21M1 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind15;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 SYSTEM GROUP A TRIP RELAY Operated Reset RS_OP_GRP-A Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_P444_21M1 SYSTEM CARRIER HEALTHY CH-1 Set Reset RS_set_CARr1 Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_P444_21M1 SYSTEM LINE ISO OPEN FOR STUB PROTN Set Reset RS_ST_ISO_OE_STU Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_P444_21M1 SYSTEM CB CLOSE CMD SOTF INITIATION Set Reset RS_ST_SOTF Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_NotRec_Recvd SPS 765kV R707_P444_21M1 SYSTEM CARRIER CH-2 Received Not Received NR_RV_CAR_R_CH2 Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Flty_Healthy SPS 765kV R707_P444_21M1 SYSTEM MAIN-2 RELAY Healthy Unhealthy UL_HL_M2_RLY Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_NotRec_Recvd SPS 765kV R707_P444_21M1 SYSTEM CARRIER CH-1 Received Not Received NR_RV_CARR CH1 Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_P444_21M1 SYSTEM CARRIER HEALTHY CH-2 Set Reset RS_set_CARr2 Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_NotRec_Recvd SPS 765kV R707_P444_21M1 SYSTEM DIRECT TRIP RECEIVED CH-1 Received Not Received NR_RV_DT_REV_CH1 Transmitted to IEC System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLA_NotRec_Recvd SPS 765kV R707_P444_21M1 SYSTEM DIRECT TRIP RECEIVED CH-2 Received Not Received NR_RV_DT_REV_CH2 Transmitted to IEC System;OptGGIO1 ST;Ind13;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind22;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 SYSTEM GROUP B TRIP RELAY Operated Reset RS_OP_GRPB Transmitted to IEC System;OptGGIO1 ST;Ind22;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind23;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 765kV R707_P444_21M1 SYSTEM 86RA SUPERVISION Healthy Unhealthy UL_HL_86RA Transmitted to IEC System;OptGGIO1 ST;Ind23;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind24;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 765kV R707_P444_21M1 SYSTEM TRIP RELAY 86A SUPERVISION Healthy Unhealthy RS_ST_86A SUPV Transmitted to IEC System;OptGGIO1 ST;Ind24;stVal;SPS None 1 #REF!
A Control;PsbRPSB3 ST;Str;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION POWER SWING DETECTED Set Reset RS_AL_PSB_STR Transmitted to IEC Control;PsbRPSB3 ST;Str;general;ACD None 1 #REF!
A Control;PsbRPSB3 ST;BlkZn;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION POWER SWING BLOCKING Set Reset RS_OP_PWR SW BLK Transmitted to IEC Control;PsbRPSB3 ST;BlkZn;stVal;SPS None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE ZONE-1 R-PH TRIP Operated Reset RS_OP_Z1R-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE ZONE-1 Y-PH TRIP Operated Reset RS_OP_Z1Y-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE ZONE-1 B-PH TRIP Operated Reset RS_OP_Z1B-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE PROTN ZONE-1 Operated Reset RS_OP_ZONE-1 Transmitted to IEC Protection;DisPDIS1 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE ZONE-1 START Set Reset RS_OP_DIS S Z1 Transmitted to IEC Protection;DisPDIS1 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE ZONE-2 R-PH TRIP Operated Reset RS_OP_Z2R-PH Transmitted to IEC Protection;DisPDIS2 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE ZONE-2 Y-PH TRIP Operated Reset RS_OP_Z2Y-PH Transmitted to IEC Protection;DisPDIS2 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE ZONE-2 B-PH TRIP Operated Reset RS_OP_Z2B-PH Transmitted to IEC Protection;DisPDIS2 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE PROTN ZONE-2 Operated Reset RS_OP_ZONE-2 Transmitted to IEC Protection;DisPDIS2 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsA;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE ZONE-2 R-PH START Set Reset RS_OP_DIS S Z2_R Transmitted to IEC Protection;DisPDIS2 ST;Str;phsA;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsB;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE ZONE-2 Y-PH START Set Reset RS_OP_DIS S Z2_Y Transmitted to IEC Protection;DisPDIS2 ST;Str;phsB;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsC;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE ZONE-2 B-PH START Set Reset RS_OP_DIS S Z2_B Transmitted to IEC Protection;DisPDIS2 ST;Str;phsC;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE ZONE-2 START Set Reset RS_OP_DIS S Z2 Transmitted to IEC Protection;DisPDIS2 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS3 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE PROTN ZONE-3 Operated Reset RS_OP_ZONE-3 Transmitted to IEC Protection;DisPDIS3 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS3 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE ZONE-3 START Set Reset RS_OP_DIS S Z3 Transmitted to IEC Protection;DisPDIS3 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS4 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE PROTN ZONE-4 Operated Reset RS_OP_ZONE-4 Transmitted to IEC Protection;DisPDIS4 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS4 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE ZONE-4 START Set Reset RS_OP_DIS S Z4 Transmitted to IEC Protection;DisPDIS4 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS5 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE PROTN ZONE-5 Operated Reset RS_OP_ZONE-5 Transmitted to IEC Protection;DisPDIS5 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS5 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DISTANCE ZONE-5 START Set Reset RS_OP_DIS S Z5 Transmitted to IEC Protection;DisPDIS5 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPSCH1 ST;CarRx;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION CARRIER AIDED SCHEME Operated Reset RS_OP_CARR_AIDED Transmitted to IEC Protection;DisPSCH1 ST;CarRx;general;ACT None 1 #REF!
A Protection;DisPSCH1 ST;ProRx;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_P444_21M1 PROTECTION CARRIER RECEIVE Set Reset RS_ST_CARR REC Transmitted to IEC Protection;DisPSCH1 ST;ProRx;stVal;SPS None 1 #REF!
A Protection;DisPSCH1 ST;ProTx;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_P444_21M1 PROTECTION CARRIER SEND Set Reset RS_ST_CARR SEND Transmitted to IEC Protection;DisPSCH1 ST;ProTx;stVal;SPS None 1 #REF!
A Protection;EfdPTOC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DIRECTIONAL E/F TRIP Operated Reset RS_OP_DEF Transmitted to IEC Protection;EfdPTOC1 ST;Op;general;general;ACT None 1 #REF!
A Protection;EfdPTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION DIRECTIONAL E/F START Set Reset RS_OP_DIR E/F S Transmitted to IEC Protection;EfdPTOC1 ST;Str;general;general;ACD None 1 #REF!
A Protection;SofPSOF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION SOTF Operated Reset RS_OP_SOTF Transmitted to IEC Protection;SofPSOF1 ST;Op;general;ACT None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION OVERVOLTAGE STAGE-1 TRIP Operated Reset RS_OP_O/V-I Transmitted to IEC Protection;VtpPhsPTOV1 ST;Op;general;ACT None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION OVERVOLTAGE STAGE-1 START Set Reset RS_OP_O/V STG1 S Transmitted to IEC Protection;VtpPhsPTOV1 ST;Str;general;general;ACD None 1 #REF!
A Protection;VtpPhsPTOV2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION OVERVOLTAGE STAGE-2 TRIP Operated Reset RS_OP_O/V-II Transmitted to IEC Protection;VtpPhsPTOV2 ST;Op;general;ACT None 1 #REF!
A System;GosGGIO1 ST;Ind19;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P444_21M1 PROTECTION STUB PROTECTION Operated Reset RS_OP_STUB System;GosGGIO2 ST;Ind19;stVal;SPS None No 1 #REF!
SPS 765kV R707_P444_21M1 PROTECTION DISTANCE BLOCKED Set Reset RS_ST_DIS BLK Protection;DisPDIS ST;BLK
SPS 765kV R707_P444_21M1 SYSTEM DT SEND CH 1 Set Reset RS_ST_DT_CH-1_S
SPS 765kV R707_P444_21M1 SYSTEM DT SEND CH 2 Set Reset RS_ST_DT_CH-2_S
SPS 765kV R707_P444_21M1 SYSTEM BCU RELAY Healthy Unhealthy RS_ST_BCU System;OptGGIO1 ST;Indx;stVal;SPS
SPS 765kV R707_P444_21M1 SYSTEM PREPARE 3-PH TRIP FROM TIE BCU Set Reset RS_ST_MAIN_3 PH System;OptGGIO1 ST;Indx;stVal;SPS
SPS 765kV R707_P444_21M1 SYSTEM PREPARE 3-PH TRIP FROM MAIN BCU Set Reset RS_ST_TIE_3 PH System;OptGGIO1 ST;Indx;stVal;SPS
SPS 765kV R707_P444_21M1 SYSTEM CURRENT REVERSAL DETECTED Set Reset
SPS 765kV R707_P444_21M1 SYSTEM WEAK INFEED ECHO SEND Set Reset
SPS 765kV R707_P444_21M1 SYSTEM WEAK INFEED TRIP Set Reset
SPS 765kV R707_P444_21M1 SYSTEM SETTINGS CHANGED Set Reset
Z 765kV R707_P444_21M1 PROTECTION FAULT IMPEDANCE -100.0 100.0 Fltz Transmitted to IEC Records;PriRFLO1 MX;FltZ;cVal;CMV
Km 765kV R707_P444_21M1 PROTECTION FAULT DISTANCE 0.0 1000.0 FltDiskm Transmitted to IEC Records;PriRFLO1 MX;FltDiskm;mag;MV
765kV R707_P444_21M1 SYSTEM CH-1 Code-1 Tx (MAIN-1 CARRIER RECEIVE CHANNEL-1) 0.0 COUNTER READING
765kV R707_P444_21M1 SYSTEM CH-1 Code-1 Rx (MAIN-1 CARRIER SEND CHANNEL-1) 0.0 COUNTER READING
765kV R707_P444_21M1 SYSTEM CH-1 Code-2 Tx (MAIN-2 CARRIER RECEIVE CHANNEL-1) 0.0 COUNTER READING
765kV R707_P444_21M1 SYSTEM CH-1 Code-2 Rx (MAIN-2 CARRIER SEND CHANNEL-1) 0.0 COUNTER READING
765kV R707_P444_21M1 SYSTEM CH-2 Code-2 Tx (MAIN-2 CARRIER RECEIVE CHANNEL-2) 0.0 COUNTER READING
765kV R707_P444_21M1 SYSTEM CH-2 Code-2 Rx (MAIN-2 CARRIER SEND CHANNEL-2) 0.0 COUNTER READING
765kV R707_P444_21M1 SYSTEM CH-2 Code-1 Tx (MAIN-1 CARRIER RECEIVE CHANNEL-2) 0.0 COUNTER READING
765kV R707_P444_21M1 SYSTEM CH-2 Code-1 Rx (MAIN-1 CARRIER SEND CHANNEL-2) 0.0 COUNTER READING
765kV R707_P444_21M1 SYSTEM CH-1 Code-3 Tx (DT RECEIVE CHANNEL-1) 0.0 COUNTER READING
765kV R707_P444_21M1 SYSTEM CH-1 Code-3 Rx (DT SEND CHANNEL-1) 0.0 COUNTER READING
765kV R707_P444_21M1 SYSTEM CH-2 Code-3 Tx (DT RECEIVE CHANNEL-2) 0.0 COUNTER READING
765kV R707_P444_21M1 SYSTEM CH-2 Code-3 Rx (DT SEND CHANNEL-2) 0.0 COUNTER READING
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
DIGITAL INFORMATION TO IED IED name R707_P444_21M1
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 2 DIGITAL INFORMATION TO IED IED name R707_P444_21M1
A SPARE 2 DIGITAL INFORMATION TO IED IED name R707_P444_21M1
A SPARE 2 DIGITAL INFORMATION TO IED IED name R707_P444_21M1
A SPARE 2 DIGITAL INFORMATION TO IED IED name R707_P444_21M1
A SPARE 2 #REF!
A SPARE 2 #REF!
A SPARE 2 #REF!
ANALOG INFORMATION FROM IED IED name R707_P444_21M1
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Records;PriRFLO1 MX;FltZ;cVal;CMV MV_hla_Fault_Impd 6 ANALOG INFORMATION FROM IED IED name R707_P444_21M1
A Records;PriRFLO1 MX;FltDiskm;mag;MV MV_Hla_Fault_Dist 6 ANALOG INFORMATION FROM IED IED name R707_P444_21M1
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P444_21M1
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P444_21M1
ANALOG INFORMATION TO IED IED name R707_P444_21M1
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P444_21M1
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P444_21M1
COUNTER INFORMATION FROM IED IED name R707_P444_21M1
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P444_21M1
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R707_P444_21M1 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R707_P444_21M1
DIGITAL INFORMATION FROM IED IED name R707_P444_21M1
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_D60_21M1 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P444_21M1
A System;AlmGGIO1 ST;Alm6;stVal;SPS SPE_HLA_Normal_Fail SPS 765kV R707_D60_21M1 PROTECTION VT FUSE Alarm Normal NL_FL_VT-FUSE Transmitted to IEC System;AlmGGIO1 ST;Alm6;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P444_21M1
A System;AlmGGIO1 ST;Alm31;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION BROKEN CONDUCTOR Alarm Normal RS_OP_BRKN CND Transmitted to IEC System;AlmGGIO1 ST;Alm31;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P444_21M1
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION STUB PROTECTION Operated Reset RS_OP_STUB Transmitted to IEC System;GosGGIO2 ST;Ind3;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind15;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_D60_21M1 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind15;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 SYSTEM GROUP A TRIP RELAY Operated Reset RS_OP_GRP-A Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_D60_21M1 SYSTEM CARRIER HEALTHY CH-1 Set Reset RS_set_CARr1 Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_D60_21M1 SYSTEM LINE ISO OPEN FOR STUB PROTN Set Reset RS_ST_ISO_OE_STU Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_D60_21M1 SYSTEM CB CLOSE CMD SOTF INITIATION Set Reset RS_ST_SOTF Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_NotRec_Recvd SPS 765kV R707_D60_21M1 SYSTEM CARRIER CH-2 Received Not Received NR_RV_CAR_R_CH2 Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Flty_Healthy SPS 765kV R707_D60_21M1 SYSTEM MAIN-2 RELAY Healthy Unhealthy UL_HL_M2_RLY Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_NotRec_Recvd SPS 765kV R707_D60_21M1 SYSTEM CARRIER CH-1 Received Not Received NR_RV_CARR CH1 Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_D60_21M1 SYSTEM CARRIER HEALTHY CH-2 Set Reset RS_set_CARr2 Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_NotRec_Recvd SPS 765kV R707_D60_21M1 SYSTEM DIRECT TRIP RECEIVED CH-1 Received Not Received NR_RV_DT_REV_CH1 Transmitted to IEC System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLA_NotRec_Recvd SPS 765kV R707_D60_21M1 SYSTEM DIRECT TRIP RECEIVED CH-2 Received Not Received NR_RV_DT_REV_CH2 Transmitted to IEC System;OptGGIO1 ST;Ind13;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind22;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 SYSTEM GROUP B TRIP RELAY Operated Reset RS_OP_GRPB Transmitted to IEC System;OptGGIO1 ST;Ind22;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind23;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 765kV R707_D60_21M1 SYSTEM 86RA SUPERVISION Healthy Unhealthy UL_HL_86RA Transmitted to IEC System;OptGGIO1 ST;Ind23;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind24;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 765kV R707_D60_21M1 SYSTEM TRIP RELAY 86A SUPERVISION Healthy Unhealthy RS_ST_86A SUPV Transmitted to IEC System;OptGGIO1 ST;Ind24;stVal;SPS None 1 #REF!
A Control;PsbRPSB3 ST;Str;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION POWER SWING DETECTED Set Reset RS_AL_PSB_STR Transmitted to IEC Protection;PwrSwgRPSB1 ST;Str None 1 #REF!
A Control;PsbRPSB3 ST;BlkZn;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION POWER SWING BLOCKING Set Reset RS_OP_PWR SW BLK Transmitted to IEC Protection;PwrSwgRPSB1 ST;BlkZn None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Prot.TrOutPTRC1 ST;Tr None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE ZONE-1 R-PH TRIP Operated Reset RS_OP_Z1R-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phs1 None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE ZONE-1 Y-PH TRIP Operated Reset RS_OP_Z1Y-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phs2 None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE ZONE-1 B-PH TRIP Operated Reset RS_OP_Z1B-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phs3 None 1 #REF!
A Protection;DisPDIS1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE PROTN ZONE-1 Operated Reset RS_OP_ZONE-1 Transmitted to IEC Protection;DisPDIS1 ST;Op None 1 #REF!
A Protection;DisPDIS1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE ZONE-1 START Set Reset RS_OP_DIS S Z1 Transmitted to IEC Protection;DisPDIS1 ST;Str None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE ZONE-2 R-PH TRIP Operated Reset RS_OP_Z2R-PH Transmitted to IEC Protection;DisPDIS2 ST;Op;phs1 None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE ZONE-2 Y-PH TRIP Operated Reset RS_OP_Z2Y-PH Transmitted to IEC Protection;DisPDIS2 ST;Op;phs2 None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE ZONE-2 B-PH TRIP Operated Reset RS_OP_Z2B-PH Transmitted to IEC Protection;DisPDIS2 ST;Op;phs3 None 1 #REF!
A Protection;DisPDIS2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE PROTN ZONE-2 Operated Reset RS_OP_ZONE-2 Transmitted to IEC Protection;DisPDIS2 ST;Op None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsA;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE ZONE-2 R-PH START Set Reset RS_OP_DIS S Z2_R Transmitted to IEC Protection;DisPDIS2 ST;str;phs1 None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsB;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE ZONE-2 Y-PH START Set Reset RS_OP_DIS S Z2_Y Transmitted to IEC Protection;DisPDIS2 ST;str;phs2 None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsC;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE ZONE-2 B-PH START Set Reset RS_OP_DIS S Z2_B Transmitted to IEC Protection;DisPDIS2 ST;str;phs3 None 1 #REF!
A Protection;DisPDIS2 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE ZONE-2 START Set Reset RS_OP_DIS S Z2 Transmitted to IEC Protection;DisPDIS2 ST;Str None 1 #REF!
A Protection;DisPDIS3 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE PROTN ZONE-3 Operated Reset RS_OP_ZONE-3 Transmitted to IEC Protection;DisPDIS3 ST;Op None 1 #REF!
A Protection;DisPDIS3 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE ZONE-3 START Set Reset RS_OP_DIS S Z3 Transmitted to IEC Protection;DisPDIS3 ST;Str None 1 #REF!
A Protection;DisPDIS4 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE PROTN ZONE-4 Operated Reset RS_OP_ZONE-4 Transmitted to IEC Protection;DisPDIS4 ST;Op None 1 #REF!
A Protection;DisPDIS4 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE ZONE-4 START Set Reset RS_OP_DIS S Z4 Transmitted to IEC Protection;DisPDIS4 ST;Str None 1 #REF!
A Protection;DisPDIS5 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE PROTN ZONE-5 Operated Reset RS_OP_ZONE-5 Transmitted to IEC Protection;DisPDIS5 ST;Op None 1 #REF!
A Protection;DisPDIS5 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DISTANCE ZONE-5 START Set Reset RS_OP_DIS S Z5 Transmitted to IEC Protection;DisPDIS5 ST;Str None 1 #REF!
A Protection;DisPSCH1 ST;CarRx;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION CARRIER AIDED SCHEME Operated Reset RS_OP_CARR_AIDED Transmitted to IEC Protection;DisPSCH1 ST;CarRx None 1 #REF!
A Protection;DisPSCH1 ST;ProRx;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_D60_21M1 PROTECTION CARRIER RECEIVE Set Reset RS_ST_CARR REC Transmitted to IEC Protection;DisPSCH1 ST;ProRx None 1 #REF!
A Protection;DisPSCH1 ST;ProTx;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_D60_21M1 PROTECTION CARRIER SEND Set Reset RS_ST_CARR SEND Transmitted to IEC Protection;DisPSCH1 ST;ProTx None 1 #REF!
A Protection;EfdPTOC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DIRECTIONAL E/F TRIP Operated Reset RS_OP_DEF Transmitted to IEC Prot.NeuTocPTOC1 ST;Str None 1 #REF!
A Protection;EfdPTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION DIRECTIONAL E/F START Set Reset RS_OP_DIR E/F S Transmitted to IEC Prot.NeuTocPTOC1 ST;Op None 1 #REF!
A Protection;SofPSOF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION SOTF Operated Reset RS_OP_SOTF Transmitted to IEC Protection;SofPSOF ST;Op None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION OVERVOLTAGE STAGE-1 TRIP Operated Reset RS_OP_O/V-I Transmitted to IEC Prot.PhsOvPTOV1 ST;Str None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION OVERVOLTAGE STAGE-1 START Set Reset RS_OP_O/V STG1 S Transmitted to IEC Prot.PhsOvPTOV1 ST;Op None 1 #REF!
A Protection;VtpPhsPTOV2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION OVERVOLTAGE STAGE-2 TRIP Operated Reset RS_OP_O/V-II Transmitted to IEC Prot.PhsOvPTOV2 ST;Op None 1 #REF!
A System;GosGGIO1 ST;Ind19;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_D60_21M1 PROTECTION STUB PROTECTION Operated Reset RS_OP_STUB System;GosGGIO2 ST;Ind19;stVal;SPS None No 1 #REF!
A SPARE SPS 765kV R707_D60_21M1 PROTECTION Distance Blocked Set Reset RS_ST_DIS BLK Protection;DisPDIS ST;BLK 2 DIGITAL INFORMATION TO IED IED name R707_P444_21M1
A SPARE SPS 765kV R707_D60_21M1 SYSTEM DT SEND CH 1 Set Reset RS_ST_DT_CH-1_S 2 DIGITAL INFORMATION TO IED IED name R707_P444_21M1
A SPARE SPS 765kV R707_D60_21M1 SYSTEM DT SEND CH 2 Set Reset RS_ST_DT_CH-2_S 2 DIGITAL INFORMATION TO IED IED name R707_P444_21M1
A SPARE SPS 765kV R707_D60_21M1 SYSTEM BCU RELAY Healthy Unhealthy RS_ST_BCU System;OptGGIO1 ST;Indx;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R707_P444_21M1
A SPARE SPS 765kV R707_D60_21M1 SYSTEM PREPARE 3-PH TRIP FROM TIE BCU Set Reset RS_ST_MAIN_3 PH System;OptGGIO1 ST;Indx;stVal;SPS 2 #REF!
A SPARE SPS 765kV R707_D60_21M1 SYSTEM PREPARE 3-PH TRIP FROM MAIN BCU Set Reset RS_ST_TIE_3 PH System;OptGGIO1 ST;Indx;stVal;SPS 2 #REF!
SPS 765kV R707_D60_21M1 SYSTEM SETTINGS CHANGED Set Reset
765kV R707_D60_21M1 SYSTEM CH-1 Code-1 Tx (MAIN-1 CARRIER RECEIVE CHANNEL-1) 0.0 COUNTER READING
765kV R707_D60_21M1 SYSTEM CH-1 Code-1 Rx (MAIN-1 CARRIER SEND CHANNEL-1) 0.0 COUNTER READING
765kV R707_D60_21M1 SYSTEM CH-1 Code-2 Tx (MAIN-2 CARRIER RECEIVE CHANNEL-1) 0.0 COUNTER READING
765kV R707_D60_21M1 SYSTEM CH-1 Code-2 Rx (MAIN-2 CARRIER SEND CHANNEL-1) 0.0 COUNTER READING
765kV R707_D60_21M1 SYSTEM CH-2 Code-2 Tx (MAIN-2 CARRIER RECEIVE CHANNEL-2) 0.0 COUNTER READING
765kV R707_D60_21M1 SYSTEM CH-2 Code-2 Rx (MAIN-2 CARRIER SEND CHANNEL-2) 0.0 COUNTER READING
765kV R707_D60_21M1 SYSTEM CH-2 Code-1 Tx (MAIN-1 CARRIER RECEIVE CHANNEL-2) 0.0 COUNTER READING
765kV R707_D60_21M1 SYSTEM CH-2 Code-1 Rx (MAIN-1 CARRIER SEND CHANNEL-2) 0.0 COUNTER READING
765kV R707_D60_21M1 SYSTEM CH-1 Code-3 Tx (DT RECEIVE CHANNEL-1) 0.0 COUNTER READING
765kV R707_D60_21M1 SYSTEM CH-1 Code-3 Rx (DT SEND CHANNEL-1) 0.0 COUNTER READING
765kV R707_D60_21M1 SYSTEM CH-2 Code-3 Tx (DT RECEIVE CHANNEL-2) 0.0 COUNTER READING
765kV R707_D60_21M1 SYSTEM CH-2 Code-3 Rx (DT SEND CHANNEL-2) 0.0 COUNTER READING
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
DIGITAL INFORMATION TO IED IED name R707_P444_21M1
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 2 #REF!
ANALOG INFORMATION FROM IED IED name R707_P444_21M1
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Records;PriRFLO1 MX;FltZ;cVal;CMV MV_hla_Fault_Impd Z 765kV R707_P444_21M1 PROTECTION FAULT IMPEDANCE -100.0 100.0 Fltz Transmitted to IEC Records;PriRFLO1 MX;FltZ;cVal;CMV 6 ANALOG INFORMATION FROM IED IED name R707_P444_21M1
A Records;PriRFLO1 MX;FltDiskm;mag;MV MV_Hla_Fault_Dist Km 765kV R707_P444_21M1 PROTECTION FAULT DISTANCE 0.0 1000.0 FltDiskm Transmitted to IEC Records;PriRFLO1 MX;FltDiskm;mag;MV 6 ANALOG INFORMATION FROM IED IED name R707_P444_21M1
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P444_21M1
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P444_21M1
ANALOG INFORMATION TO IED IED name R707_P444_21M1
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P444_21M1
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P444_21M1
COUNTER INFORMATION FROM IED IED name R707_P444_21M1
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P444_21M1
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R707_P643_87R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R707_P643_87R
DIGITAL INFORMATION FROM IED IED name R707_P643_87R
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P643_87R PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P643_87R
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P643_87R PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R PROTECTION DIFFERENTIAL R-PH TRIP Operated Reset RS_OP_DIFF R PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R PROTECTION DIFFERENTIAL Y-PH TRIP Operated Reset RS_OP_DIFF Y-PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R PROTECTION DIFFERENTIAL B-PH TRIP Operated Reset RS_OP_DIFF B-PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R PROTECTION DIFFERENTIAL TRIP Operated Reset RS_OP_DIFF Transmitted to IEC Protection;DifPDIF1 ST;Op;general;general;ACT None 1 #REF!
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLA_Flty_Healthy SPS 765kV R707_P643_87R SYSTEM REF RELAY Healthy Unhealthy Transmitted to IEC None 1 #REF!
SPS 765kV R707_P643_87R SYSTEM 86A SUPERVISION Healthy Unhealthy Transmitted to IEC System;OptGGIO1 ST;IndX;stVal;SPS
SPS 765kV R707_P643_87R SYSTEM 86B SUPERVISION Healthy Unhealthy UL_HL_86RA Transmitted to IEC System;OptGGIO1 ST;IndX;stVal;SPS
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLA_Flty_Healthy SPS 765kV R707_P643_87R SYSTEM BCU R Healthy Faulty FL_HL_ BCU R Transmitted to IEC None 1 #REF!
A System;OptGGIO1 ST;Ind18;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM MASTER TRIP 86A Operated Reset RS_OP_86RA Transmitted to IEC None 1 #REF!
A System;OptGGIO1 ST;Ind18;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM MASTER TRIP 86B Operated Reset RS_OP_86RA Transmitted to IEC None 1 #REF!
SPS 765kV R707_P643_87R PROTECTION DIFFERENTIAL CURRENT ALARM Set Reset RS_ST_DIFF_CURNT
SPS 765kV R707_P643_87R PROTECTION DIFFERENTIAL PROTECTION START Set Reset RS_ST_DIFF_STRT
SPS 765kV R707_P643_87R PROTECTION DIFFERENTIAL PROTECTION RPH START Set Reset RS_ST_DIFF_STR_R
SPS 765kV R707_P643_87R PROTECTION DIFFERENTIAL PROTECTION YPH START Set Reset RS_ST_DIFF_STR_Y
SPS 765kV R707_P643_87R PROTECTION DIFFERENTIAL PROTECTION BPH START Set Reset RS_ST_DIFF_STR_B
SPS 765kV R707_P643_87R PROTECTION DIFFERENTIAL BLOCKED Set Reset RS_ST_DIFF_BLK
A SPARE SPS 765kV R707_P643_87R PROTECTION DIFFERENTIAL PROTECTION 2nd HARMONIC BLOCK Set Reset RS_ST_DIFF_HBK 2 2 #REF!
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM BUCH-1 R PH TRIP Operated Reset RS_OP_BUCH-1 R Transmitted to IEC System;OptGGIO1 ST;Ind2;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM WTI TRIP R PH Operated Reset RS_OP_WDG TEMP R Transmitted to IEC System;OptGGIO1 ST;Ind3;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM PRV-1 RPH TRIP Operated Reset RS_OP_PRV-1 R Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P643_87R SYSTEM OTI R PH ALARM Set Reset NL_AL_BUCH 1-2 R Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM MOLG MAIN CON. LOW LEVEL R PH ALARM Set Reset RS_OP_MOLG LVL R Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM BUCH-1 Y PH TRIP Operated Reset RS_OP_BUCH-1 Y Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM WTI TRIP Y PH Operated Reset RS_OP_WDG TEMP Y Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM PRV-1 YPH TRIP Operated Reset RS_OP_PRV-1 Y Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P643_87R SYSTEM OTI Y PH ALARM Alarm Normal NL_AL_BUCH 1-2 Y Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM MOLG MAIN CON. LOW LEVEL Y PH ALARM Set Reset RS_OP_MOLG LVL Y Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM BUCH-1 B PH TRIP Operated Reset RS_OP_BUCH-1 B Transmitted to IEC System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM WTI TRIP B PH Operated Reset RS_OP_WDG TEMP B Transmitted to IEC System;OptGGIO1 ST;Ind13;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind14;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM PRV-1 BPH TRIP Operated Reset RS_OP_PRV-1 B Transmitted to IEC System;OptGGIO1 ST;Ind14;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind15;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P643_87R SYSTEM OTI B PH ALARM Set Reset NL_AL_BUCH 1-2 B Transmitted to IEC System;OptGGIO1 ST;Ind15;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind16;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM MOLG MAIN CON. LOW LEVEL B PH ALARM Set Reset RS_OP_MOLG LVL B Transmitted to IEC System;OptGGIO1 ST;Ind16;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind19;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM BUCH-1 TRIP SP PH Operated Reset RS_OP_BUCH-1 SP Transmitted to IEC System;OptGGIO1 ST;Ind19;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind20;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM WTI TRIP SP PH Operated Reset RS_OP_WTI SP PH Transmitted to IEC System;OptGGIO1 ST;Ind20;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind21;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM PRV-1 SPPH TRIP Operated Reset RS_OP_PRV-1 SP Transmitted to IEC System;OptGGIO1 ST;Ind21;stVal;SPS None 1 #REF!
SPS 765kV R707_P643_87R SYSTEM OTI SP PH ALARM Set Reset
A System;OptGGIO1 ST;Ind24;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P643_87R SYSTEM MOLG MAIN CON. LOW LEVEL S PH ALARM Set Normal RS_OP_MOLG LVL S Transmitted to IEC System;OptGGIO1 ST;Ind24;stVal;SPS None 1 #REF!
SPS 765kV R707_P643_87R SYSTEM SETTINGS CHANGED Set Reset
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
DIGITAL INFORMATION TO IED IED name R707_P643_87R
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 765kV R707_P643_87R SYSTEM REF RELAY Healthy Unhealthy UL_HL_REF Transmitted to IEC System;OptGGIO1 ST;IndX;stVal;SPS 2 #REF!
A SPARE SPC 2 #REF!
A SPARE SPC 2 #REF!
A SPARE SPC 2 #REF!
A SPARE SPC 2 #REF!
A SPARE SPC 2 #REF!
ANALOG INFORMATION FROM IED IED name R707_P643_87R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P643_87R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P643_87R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P643_87R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P643_87R
ANALOG INFORMATION TO IED IED name R707_P643_87R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P643_87R
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P643_87R
COUNTER INFORMATION FROM IED IED name R707_P643_87R
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P643_87R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P643_87R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P643_87R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P643_87R
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R707_P141_64R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R707_P141_64R
DIGITAL INFORMATION FROM IED IED name R707_P141_64R
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P141_64R PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P141_64R
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P141_64R GOOSE 86A TRIP RELAY Operated Reset RS_OP_86A Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R707_P141_64R
A System;GosGGIO2 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P141_64R GOOSE 86B TRIP RELAY Operated Reset RS_OP_86B Transmitted to IEC System;GosGGIO2 ST;Ind2;stVal;SPS 27;53; None Yes 1 DIGITAL INFORMATION FROM IED IED name R707_P141_64R
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_P141_64R GOOSE BB Set Reset RS_ST_BB Transmitted to IEC System;GosGGIO2 ST;Ind3;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R707_P141_64R
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P141_64R PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R707_P141_64R
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 765kV R707_P141_64R SYSTEM 86B TRIP RELAY SUPERVISION Healthy Unhealthy UH_HL_86B Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 0
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P141_64R PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 0
A Protection;SenRefPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P141_64R PROTECTION REF TRIP Operated Reset RS_OP_REF Transmitted to IEC Protection;SenRefPDIF1 ST;Op;general;general;ACT None 1 0
A SPARE SPS 765kV R707_P643_87R SYSTEM 87R RELAY Healthy Unhealthy UL_HL_ BCU R Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None No 1 0
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P141_64R SYSTEM 86RB TRIP RELAY Operated Reset RS_OP_86B Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P141_64R
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLA_Reset_Trip SPS 765kV R707_P141_64R SYSTEM SPR R PH ALARM SET Reset RS_TR_SDN PR R Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P141_64R
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Trip SPS 765kV R707_P141_64R SYSTEM SPR Y PH ALARM SET Reset RS_TR_SDN PR Y Transmitted to IEC System;OptGGIO1 ST;Ind2;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P141_64R
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLA_Reset_Trip SPS 765kV R707_P141_64R SYSTEM SPR B PH ALARM SET Reset RS_TR_SDN PR B Transmitted to IEC System;OptGGIO1 ST;Ind3;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P141_64R
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Trip SPS 765kV R707_P141_64R SYSTEM SPR SP PH ALARM SET Reset RS_TR_SDN PR SP Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P141_64R
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_In_Out SPS 765kV R707_P141_64R SYSTEM CSD Out In IN_OUT_CSD Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P141_64R
SPS 765kV R707_P141_64R SYSTEM BUCH -2 R PH TRIP Operated Reset RS_OP_BUCH-2 R System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM OTI R PH TRIP Operated Reset RS_OP_OTI R System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM PRV-2 R PH TRIP Operated Reset RS_OP_PRV-2 R System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM WTI R PH ALARM Set Reset NL_AL_OTI R System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM BUCH-2 Y PH TRIP Operated Reset RS_OP_BUCH-2 Y System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM OTI Y PH TRIP Operated Reset RS_OP_OTI Y System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM PRV-2 Y PH TRIP Operated Reset RS_OP_PRV-2 Y System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM WTI Y PH ALARM Set Reset NL_AL_OTI Y System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM BUCH-2 B PH TRIP Operated Reset RS_OP_BUCH-2 B System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM OTI B PH TRIP Operated Reset RS_OP_OTI B System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM PRV-2 B PH TRIP Operated Reset RS_OP_PRV-2 B System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM WTI B PH ALARM Set Reset NL_AL_OTI B System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM BUCH -2 SP PH TRIP Operated Reset RS_OP_BUCH-2 SP System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM OTI SP PH TRIP Operated Reset RS_OP_OTI- SP System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM PRV-2 SP PH TRIP Operated Reset RS_OP_PRV TRIP S System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM WTI SP PH ALARM Set Reset RS_OP_WTI TRIP S System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P141_64R SYSTEM SETTINGS CHANGED Set Reset
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
DIGITAL INFORMATION TO IED IED name R707_P141_64R
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 765kV R707_P141_64R SYSTEM REF ALARM Set Reset RS_ST_REF ALM 2 DIGITAL INFORMATION TO IED IED name R707_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P141_64R
ANALOG INFORMATION FROM IED IED name R707_P141_64R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P141_64R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P141_64R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P141_64R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P141_64R
ANALOG INFORMATION TO IED IED name R707_P141_64R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P141_64R
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P141_64R
COUNTER INFORMATION FROM IED IED name R707_P141_64R
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P141_64R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P141_64R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P141_64R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P141_64R
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R707_P442_21R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R707_P442_21R
DIGITAL INFORMATION FROM IED IED name R707_P442_21R
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P442_21R PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P442_21R
A System;AlmGGIO1 ST;Alm6;stVal;SPS SPE_HLA_Normal_Fail SPS 765kV R707_P442_21R PROTECTION CVT FUSE FAIL Alarm Normal NL_FL_VT FUSE Transmitted to IEC System;AlmGGIO1 ST;Alm6;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P442_21R
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P442_21R GOOSE 86A TRIP RELAY Alarm Reset RS_OP_86A Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R707_P442_21R
A System;GosGGIO2 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P442_21R GOOSE 86B TRIP RELAY Alarm Reset RS_OP_86B Transmitted to IEC System;GosGGIO2 ST;Ind2;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R707_P442_21R
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_P442_21R GOOSE BB Alarm Reset RS_ST_BB Transmitted to IEC System;GosGGIO2 ST;Ind3;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R707_P442_21R
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P442_21R PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R707_P442_21R
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P442_21R PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P442_21R PROTECTION BACKUP IMPEDENCE R-PH TRIP Operated Reset RS_OP_B/U IMP R Transmitted to IEC Protection;DisPDIS1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P442_21R PROTECTION BACKUP IMPEDENCE Y-PH TRIP Operated Reset RS_OP_B/U IMP Y Transmitted to IEC Protection;DisPDIS1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P442_21R PROTECTION BACKUP IMPEDENCE B-PH TRIP Operated Reset RS_OP_B/U IMP B Transmitted to IEC Protection;DisPDIS1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P442_21R PROTECTION BACKUP IMPEDENCE TRIP Operated Reset RS_OP_B/U IMP Transmitted to IEC Protection;DisPDIS1 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Str;general;general;ACD SPE_HLA_Reset_Start SPS 765kV R707_P442_21R PROTECTION BACKUP IMPEDANCE START Set Reset RS_ST_BUI START Transmitted to IEC Protection;DisPDIS1 ST;Str;general;general;ACD None 1 #REF!
A SPARE SPS 765kV R707_P442_21R SYSTEM BACKUP OVERCURRENT START Start Reset RS_ST_O/C Protection;OcpPTOC1 ST;Op;general;general;ACD 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPS 765kV R707_P442_21R SYSTEM BACKUP OVERCURRENT TRIP Trip Reset RS_OP_O/C Protection;OcpPTOC1 ST;Op;general;general;ACT 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPS 765kV R707_P442_21R SYSTEM BACKUP EARTHFAULT START Start Reset RS_ST_E/F Protection;EfdPTOC1 ST;Op;phsC;general;ACD 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPS 765kV R707_P442_21R SYSTEM BACKUP EARTHFAULT TRIP Trip Reset RS_ST_E/F Protection;EfdPTOC1 ST;Op;phsC;general;ACT 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
SPS 765kV R707_P442_21R SYSTEM NGR WTI ALARM Set Reset System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P442_21R SYSTEM NGR WTI TRIP Operated Reset System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P442_21R SYSTEM NGR OTI ALARM Set Reset System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P442_21R SYSTEM NGR OTI TRIP Operated Reset System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P442_21R SYSTEM NGR PRD TRIP Operated Reset System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P442_21R SYSTEM NGR BUCHHOLZ ALARM Operated Reset System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P442_21R SYSTEM NGR BUCHHOLZ TRIP Operated Reset System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 765kV R707_P442_21R PROTECTION NGR BYPASS STAGE Operated Reset
SPS 765kV R707_P442_21R PROTECTION NGR BYPASS CB CLOSE Set Reset
SPS 765kV R707_P442_21R SYSTEM NGR CLOSE COIL SUPERVISION Healthy Unhealthy System;OptGGIO1 ST;IndXX;stVal;SPS
A SPARE SPS 765kV R707_P442_21R SYSTEM SETTINGS CHANGED Set Reset None No 1 #REF!
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
DIGITAL INFORMATION TO IED IED name R707_P442_21R
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
ANALOG INFORMATION FROM IED IED name R707_P442_21R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P442_21R
ANALOG INFORMATION TO IED IED name R707_P442_21R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P442_21R
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P442_21R
COUNTER INFORMATION FROM IED IED name R707_P442_21R
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P442_21R
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R707_P743_50BF GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R707_P743_50BF
DIGITAL INFORMATION FROM IED IED name R707_P743_50BF
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P743_50BF PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P743_50BF
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P743_50BF PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R707_P743_50BF
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P743_50BF SYSTEM LBB INITIATION 3-PH Set Reset RS_OP_LBB INI 3P Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A Protection;CbfBbpRBRF1 ST;OpIn;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P743_50BF PROTECTION BREAKER FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF2 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P743_50BF PROTECTION BREAKER FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT None 1 #REF!
A SPARE SPS 765kV R707_P743_50BF PROTECTION BREAKER FAILURE RETRIP RPH Operated Reset RS_OP_CB FAILS1R Protection;CbfBbpRBRF3 ST;OpIn;phs1 None No 1 #REF!
A SPARE SPS 765kV R707_P743_50BF PROTECTION BREAKER FAILURE RETRIP YPH Operated Reset RS_OP_CB FAILS1Y Protection;CbfBbpRBRF3 ST;OpIn;phs1 None No 1 #REF!
A SPARE SPS 765kV R707_P743_50BF PROTECTION BREAKER FAILURE RETRIP BPH Operated Reset RS_OP_CB FAILS1B Protection;CbfBbpRBRF3 ST;OpIn;phs1 None No 1 #REF!
A SPARE SPS 765kV R707_P743_50BF SYSTEM SETTINGS CHANGED Set Reset None No 1 #REF!
A SPARE SPS None No 1 #REF!
A SPARE SPS None No 1 #REF!
A SPARE SPS ** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database No 1 #REF!
** Any additional Signals as per Scheme & TS
DIGITAL INFORMATION TO IED IED name R707_P743_50BF
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_50BF
ANALOG INFORMATION FROM IED IED name R707_P743_50BF
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P743_50BF
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P743_50BF
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P743_50BF
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P743_50BF
ANALOG INFORMATION TO IED IED name R707_P743_50BF
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P743_50BF
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P743_50BF
COUNTER INFORMATION FROM IED IED name R707_P743_50BF
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P743_50BF
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P743_50BF
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P743_50BF
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P743_50BF
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R707_P743_PU_A GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R707_P743_PU_A
DIGITAL INFORMATION FROM IED IED name R707_P743_PU_A
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P743_PU_A PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P743_PU_A
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_A GOOSE LBB START Set Reset RS_OP_LBB START Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R707_P743_PU_A
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P743_PU_A PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R707_P743_PU_A
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_A SYSTEM LBB INITIATION 3-PH Set Reset RS_OP_LBB INI 3P Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_A SYSTEM LBB INITIATION R-PH Set Reset RS_OP_LBB INI R Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_A SYSTEM LBB INITIATION Y-PH Set Reset RS_OP_LBB INI Y Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_A SYSTEM LBB INITIATION B-PH Set Reset RS_OP_LBB INI B Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A Protection;CbfBbpRBRF1 ST;OpIn;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_A PROTECTION EXTERNAL CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF1 ST;OpIn;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF2 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_A PROTECTION EXTERNAL CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF2 ST;OpEx;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF3 ST;OpIn;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_A PROTECTION INTERNAL CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S3 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF4 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_A PROTECTION INTERNAL CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S4 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT None 1 #REF!
A SPARE SPS 765kV R707_P743_PU_A SYSTEM FIB COMM ERROR Healthy Unhealthy UN_HL_BB_PU B None No 1 #REF!
A SPARE SPS 765kV R707_P743_PU_A SYSTEM B/B PU-B HEALTHY Healthy Unhealthy UN_HL_BB_PU B None No 1 #REF!
A SPARE SPS 765kV R707_P743_PU_A SYSTEM SETTINGS CHANGED Healthy Unhealthy UN_HL_BB_PU B None No 1 #REF!
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
DIGITAL INFORMATION TO IED IED name R707_P743_PU_A
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_A
ANALOG INFORMATION FROM IED IED name R707_P743_PU_A
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P743_PU_A
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P743_PU_A
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P743_PU_A
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P743_PU_A
ANALOG INFORMATION TO IED IED name R707_P743_PU_A
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P743_PU_A
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P743_PU_A
COUNTER INFORMATION FROM IED IED name R707_P743_PU_A
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P743_PU_A
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P743_PU_A
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P743_PU_A
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P743_PU_A
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R707_P743_PU_B GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R707_P743_PU_B
DIGITAL INFORMATION FROM IED IED name R707_P743_PU_B
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P743_PU_B PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R707_P743_PU_B
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_B GOOSE LBB START set Reset RS_OP_LBB START Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R707_P743_PU_B
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R707_P743_PU_B PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R707_P743_PU_B
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_B SYSTEM LBB INITIATION 3-PH set Reset RS_ST_LBB INI 3P Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_B SYSTEM LBB INITIATION R-PH set Reset RS_ST_LBB INI R Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_B SYSTEM LBB INITIATION Y-PH set Reset RS_ST_LBB INI Y Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_B SYSTEM LBB INITIATION B-PH set Reset RS_ST_LBB INI B Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A Protection;CbfBbpRBRF1 ST;OpIn;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_B PROTECTION EXTERNAL CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF1 ST;OpIn;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF2 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_B PROTECTION EXTERNAL CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF2 ST;OpEx;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF3 ST;OpIn;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_B PROTECTION CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S3 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF4 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 765kV R707_P743_PU_B PROTECTION CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S4 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT None 1 #REF!
A SPARE SPS 765kV R707_P743_PU_B PROTECTION B/B PU-A HEALTHY Healthy Unhealthy UN_HL_BB_PU A System;OptGGIO1 ST;IndX;stVal;SPS None No 1 #REF!
SPS 765kV R707_P743_PU_B SYSTEM FIB COMM ERROR Healthy Unhealthy UN_HL_BB_PU B None
SPS 765kV R707_P743_PU_B SYSTEM B/B PU-B HEALTHY Healthy Unhealthy UN_HL_BB_PU B None
SPS 765kV R707_P743_PU_B SYSTEM SETTINGS CHANGED Healthy Unhealthy UN_HL_BB_PU B None
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
DIGITAL INFORMATION TO IED IED name R707_P743_PU_B
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P743_PU_B
ANALOG INFORMATION FROM IED IED name R707_P743_PU_B
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P743_PU_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P743_PU_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P743_PU_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P743_PU_B
ANALOG INFORMATION TO IED IED name R707_P743_PU_B
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P743_PU_B
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P743_PU_B
COUNTER INFORMATION FROM IED IED name R707_P743_PU_B
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P743_PU_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P743_PU_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P743_PU_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P743_PU_B
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R708_P442_50BF GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R708_P442_50BF
DIGITAL INFORMATION FROM IED IED name R708_P442_50BF
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R708_P743_50BF PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R708_P442_50BF
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R708_P743_50BF PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R708_P442_50BF
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 765kV R708_P743_50BF SYSTEM BCU Healthy Unhealthy UL_HL_BCU Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R708_P743_50BF SYSTEM LBB INITIATION 3-PH Set Reset RS_OP_LBB INI 3P Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R708_P743_50BF SYSTEM LBB INITIATION R-PH Set Reset RS_OP_LBB INI R Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R708_P743_50BF SYSTEM LBB INITIATION Y-PH Set Reset RS_OP_LBB INI Y Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R708_P743_50BF SYSTEM LBB INITIATION B-PH Set Reset RS_OP_LBB INI B Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A Protection;CbfBbpRBRF2 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 765kV R708_P743_50BF PROTECTION BREAKER FAILURE REMOTE TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF4 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 765kV R708_P743_50BF PROTECTION BREAKER FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT None 1 #REF!
A SPARE SPS 765kV R708_P743_50BF PROTECTION BREAKER FAILURE RETRIP RPH Operated Reset RS_OP_CB FAILS1R Protection;CbfBbpRBRF3 ST;OpIn;phs1 None No 1 #REF!
A SPARE SPS 765kV R708_P743_50BF PROTECTION BREAKER FAILURE RETRIP YPH Operated Reset RS_OP_CB FAILS1Y Protection;CbfBbpRBRF3 ST;OpIn;phs1 None No 1 #REF!
A SPARE SPS 765kV R708_P743_50BF PROTECTION BREAKER FAILURE RETRIP BPH Operated Reset RS_OP_CB FAILS1B Protection;CbfBbpRBRF3 ST;OpIn;phs1 None No 1 #REF!
SPS 765kV R708_P743_50BF SYSTEM SETTINGS CHANGED Healthy Unhealthy UN_HL_BB_PU B None
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
DIGITAL INFORMATION TO IED IED name R708_P442_50BF
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R708_P442_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R708_P442_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R708_P442_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R708_P442_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R708_P442_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R708_P442_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R708_P442_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R708_P442_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R708_P442_50BF
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R708_P442_50BF
ANALOG INFORMATION FROM IED IED name R708_P442_50BF
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R708_P442_50BF
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R708_P442_50BF
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R708_P442_50BF
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R708_P442_50BF
ANALOG INFORMATION TO IED IED name R708_P442_50BF
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R708_P442_50BF
A SPARE 13 ANALOG INFORMATION TO IED IED name R708_P442_50BF
COUNTER INFORMATION FROM IED IED name R708_P442_50BF
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R708_P442_50BF
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R708_P442_50BF
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R708_P442_50BF
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R708_P442_50BF
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R712_P645_87T GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R712_P645_87T
DIGITAL INFORMATION FROM IED IED name R712_P645_87T
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P645_87T PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P645_87T
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P645_87T PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T PROTECTION RESTRAINED/UNRESTRAINED MODE Operated Reset RS_OP_R/U MODE Transmitted to IEC None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T PROTECTION OVEREXCITATION HV START Set Reset RS_OP_O/E HV S Transmitted to IEC Protection;VhzWg1PVPH1 ST;Str;general;ACD None Yes 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T PROTECTION DIFFERENTIAL R-PH TRIP Operated Reset RS_OP_DIFF R PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T PROTECTION DIFFERENTIAL Y-PH TRIP Operated Reset RS_OP_DIFF Y-PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T PROTECTION DIFFERENTIAL B-PH TRIP Operated Reset RS_OP_DIFF B-PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T PROTECTION DIFFERENTIAL TRIP Operated Reset RS_OP_DIFF Transmitted to IEC Protection;DifPDIF1 ST;Op;general;general;ACT None 1 #REF!
A Protection;VhzWg1PVPH1 ST;Op;general;ACT SPE_HLA_Normal_Alarm SPS 765kV R712_P645_87T PROTECTION OVEREXCITATION HV Alarm Normal NL_AL_O/E HV Transmitted to IEC Protection;VhzWg1PVPH1 ST;Op;general;ACT None 1 #REF!
A Protection;VhzWg1PVPH2 ST;Op;general;ACT SPE_HLA_Reset_Trip SPS 765kV R712_P645_87T PROTECTION OVEREXCITATION HV TRIP Operated Reset RS_TR_O/E HV Transmitted to IEC Protection;VhzWg1PVPH2 ST;Op;general;ACT None 1 #REF!
A SPARE SPS 765kV R712_P645_87T SYSTEM REF RELAY Healthy Unhealthy UL_HL_REF Transmitted to IEC System;OptGGIO1 ST;IndX;stVal;SPS ST;IndX;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R712_P645_87T
SPS 765kV R712_P645_87T SYSTEM 86A SUPERVISION Healthy Unhealthy Transmitted to IEC System;OptGGIO1 ST;IndX;stVal;SPS
SPS 765kV R712_P645_87T SYSTEM 86B SUPERVISION Healthy Unhealthy Transmitted to IEC System;OptGGIO1 ST;IndX;stVal;SPS
A System;OptGGIO1 ST;Ind18;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM MASTER TRIP 86A Operated Reset RS_OP_86RA Transmitted to IEC None 1 #REF!
A System;OptGGIO1 ST;Ind18;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM MASTER TRIP 86B Operated Reset RS_OP_86RA Transmitted to IEC None 1 #REF!
A SPARE SPS 765kV R712_P645_87T SYSTEM 86A SUPERVISION Healthy Unhealthy UL_HL_86A Transmitted to IEC System;OptGGIO1 ST;IndX;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R712_P645_87T
SPS 765kV R712_P645_87T PROTECTION DIFFERENTIAL CURRENT ALARM Set Reset RS_ST_DIFF_CURNT
SPS 765kV R712_P645_87T PROTECTION DIFFERENTIAL PROTECTION START Set Reset RS_ST_DIFF_STRT
SPS 765kV R712_P645_87T PROTECTION DIFFERENTIAL PROTECTION RPH START Set Reset RS_ST_DIFF_STR_R
SPS 765kV R712_P645_87T PROTECTION DIFFERENTIAL PROTECTION YPH START Set Reset RS_ST_DIFF_STR_Y
SPS 765kV R712_P645_87T PROTECTION DIFFERENTIAL PROTECTION BPH START Set Reset RS_ST_DIFF_STR_B
SPS 765kV R712_P645_87T PROTECTION DIFFERENTIAL BLOCKED Set Reset RS_ST_DIFF_BLK
SPS 765kV R712_P645_87T PROTECTION DIFFERENTIAL PROTECTION TRIP-HS1 Operated Reset RS_OP_DIFF_HS-1
SPS 765kV R712_P645_87T PROTECTION DIFFERENTIAL PROTECTION TRIP-HS2 Operated Reset RS_OP_DIFF_HS-2
A SPARE SPS 765kV R712_P645_87T PROTECTION DIFFERENTIAL PROTECTION 2nd HARMONIC BLOCK Set Reset RS_ST_DIFF_HBK 2 2 DIGITAL INFORMATION TO IED IED name R712_P645_87T
A SPARE SPS 765kV R712_P645_87T PROTECTION DIFFERENTIAL PROTECTION 5th HARMONIC BLOCK Set Reset RS_ST_DIFF_HBK 5 2 DIGITAL INFORMATION TO IED IED name R712_P645_87T
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM BUCHHOLZ-1 TRIP R PH Operated Reset RS_OP_BUCH-1 R Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM HV WTI TRIP R PH Operated Reset RS_OP_HV WDG R Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM IV WTI TRIP R PH Operated Reset RS_OP_IV WDG R Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM BUCH-2 R PH ALARM Set Reset NL_AL_BUCH R Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM PRV OLTC R PH ALARM SET Reset RS_OP_PRD OLTC R Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM BUCHHOLZ-1 TRIP Y PH Operated Reset RS_OP_BUCH-1 Y Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM HV WTI TRIP Y PH Operated Reset RS_OP_HV WDG Y Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM IV WTI TRIP Y PH Operated Reset RS_OP_IV WDG Y Transmitted to IEC System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM BUCH-2 ALARM Y PH Alarm Normal NL_AL_BUCH Y Transmitted to IEC System;OptGGIO1 ST;Ind13;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM BUCHHOLZ-1 TRIP Y PH Operated Reset RS_OP_BUCH-1 R Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind14;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM PRV OLTC Y PH ALARM Operated Reset RS_OP_PRD OLTC Y Transmitted to IEC System;OptGGIO1 ST;Ind14;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind15;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM BUCHHOLZ-1 TRIP B PH Operated Reset RS_OP_BUCH-1 B Transmitted to IEC System;OptGGIO1 ST;Ind15;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind16;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM HV WTI TRIP B PH Operated Reset RS_OP_HV WDG B Transmitted to IEC System;OptGGIO1 ST;Ind16;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind17;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM IV WTI TRIP B PH Operated Reset RS_OP_IV WDG B Transmitted to IEC System;OptGGIO1 ST;Ind17;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind18;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM BUCH-2 ALARM B PH Alarm Normal NL_AL_BUCH B Transmitted to IEC System;OptGGIO1 ST;Ind18;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind19;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM PRV OLTC B PH ALARM Operated Reset RS_OP_PRD OLTC B Transmitted to IEC System;OptGGIO1 ST;Ind19;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind20;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM BUCHHOLZ-1 TRIP SP PH Operated Reset RS_OP_BUCH-1 SP Transmitted to IEC System;OptGGIO1 ST;Ind20;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind21;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM HV WTI TRIP SP PH Operated Reset RS_OP_HV WDG SP Transmitted to IEC System;OptGGIO1 ST;Ind21;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind22;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM IV WTI TRIP SP PH Operated Reset RS_OP_IV WDG SP Transmitted to IEC System;OptGGIO1 ST;Ind22;stVal;SPS None 1 #REF!
OTI SP PH ALARM
A System;OptGGIO1 ST;Ind23;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM BUCH-2 ALARM SP PH Alarm Normal NL_AL_BUCH SP Transmitted to IEC System;OptGGIO1 ST;Ind23;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind24;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P645_87T SYSTEM PRV OLTC SP PH ALARM Operated Reset RS_OP_PRD OLTC S Transmitted to IEC System;OptGGIO1 ST;Ind24;stVal;SPS None 1 #REF!
SPS 765kV R712_P645_87T SYSTEM SETTINGS CHANGED Healthy Unhealthy UN_HL_BB_PU B None
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
DIGITAL INFORMATION TO IED IED name R712_P645_87T
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;PloGGIO1 CO;SPCSO1;sboClass;DPC SC_DE_Reset_Reset_1 SPC 765kV R712_P645_87T GOOSE XX_XX_86B RST RESET XX_XX_86 RST Transmitted to IEC System;PloGGIO1 CO;SPCSO1;sboClass;DPC 2 DIGITAL INFORMATION TO IED IED name R712_P645_87T
A SPARE 2 DIGITAL INFORMATION TO IED IED name R712_P645_87T
A SPARE 2 DIGITAL INFORMATION TO IED IED name R712_P645_87T
A SPARE 2 DIGITAL INFORMATION TO IED IED name R712_P645_87T
A SPARE 2 DIGITAL INFORMATION TO IED IED name R712_P645_87T
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P645_87T
ANALOG INFORMATION FROM IED IED name R712_P645_87T
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P645_87T
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P645_87T
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P645_87T
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P645_87T
ANALOG INFORMATION TO IED IED name R712_P645_87T
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R712_P645_87T
A SPARE 13 ANALOG INFORMATION TO IED IED name R712_P645_87T
COUNTER INFORMATION FROM IED IED name R712_P645_87T
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P645_87T
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P645_87T
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P645_87T
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P645_87T
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R712_P643_64 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R712_P643_64
DIGITAL INFORMATION FROM IED IED name R712_P643_64
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P643_64 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P643_64
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 PROTECTION OVEREXCITATION IV START Set Reset RS_OP_O/E IV S Transmitted to IEC Protection;VhzWg1PVPH1 ST;Str;general;ACD None Yes 1 #REF!
A System;GosGGIO2 ST;Ind8;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P643_64 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind8;stVal;SPS None Yes 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;HzrHvwPTOC1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 PROTECTION REF R PH TRIP Operated Reset RS_OP_REF R Transmitted to IEC Protection;HzrHvwPTOC1 ST;Op;general;ACT None 1 #REF!
A Protection;HzrHvwPTOC1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 PROTECTION REF Y PH TRIP Operated Reset RS_OP_REF Y Transmitted to IEC Protection;HzrLvwPTOC1 ST;Op;general;ACT None 1 #REF!
A Protection;HzrHvwPTOC1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 PROTECTION REF B PH TRIP Operated Reset RS_OP_REF B Transmitted to IEC Protection;HzrTvwPTOC1 ST;Op;general;ACT None 1 #REF!
A Protection;VhzWg1PVPH1 ST;Op;general;ACT SPE_HLA_Normal_Alarm SPS 765kV R712_P643_64 PROTECTION OVEREXCITATION IV Alarm Normal NL_AL_O/E IV Transmitted to IEC Protection;VhzWg1PVPH1 ST;Op;general;ACT None 1 #REF!
A Protection;VhzWg1PVPH2 ST;Op;general;ACT SPE_HLA_Reset_Trip SPS 765kV R712_P643_64 PROTECTION OVEREXCITATION IV TRIP Operated Reset RS_TR_O/E IV T Transmitted to IEC Protection;VhzWg1PVPH2 ST;Op;general;ACT None 1 #REF!
A SPARE SPS 765kV R712_P643_64 SYSTEM 87T RELAY Healthy Unhealthy UL_HL_86A Transmitted to IEC System;OptGGIO1 ST;IndX;stVal;SPS None No 1 #REF!
A SPARE 765kV R712_P643_64 SYSTEM REF ALARM Set Reset RS_ST_REF ALM Yes 6 ANALOG INFORMATION FROM IED IED name R712_P643_64
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM OTI TRIP R PH Operated Reset RS_OP_TOP R Transmitted to IEC System;OptGGIO1 ST;Ind2;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM OSR TRIP R PH Operated Reset RS_OP_OSR R Transmitted to IEC System;OptGGIO1 ST;Ind3;stVal;SPS None 1 #REF!
765kV R712_P643_65 SYSTEM BUCH TRIP-2 Y PH Operated Reset RS_OP_OSR R Transmitted to IEC System;OptGGIO2 ST;IndX;stVal;SPS
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM LV WTI TRIP R PH Operated Reset RS_OP_LV WDG R Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM PRV-1 TRIP R PH Operated Reset RS_OP_SDN PR R Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM BUCH TRIP-2 Y PH Operated Reset RS_OP_BUCH-2 Y Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM OTI TRIP Y PH Operated Reset RS_OP_TOP Y Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM OSR TRIP Y PH Operated Reset RS_OP_OSR Y Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM LV WTI TRIP Y PH Operated Reset RS_OP_LV WDG Y Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM PRV-1 TRIP Y PH Operated Reset RS_OP_SDN PR Y Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM BUCH TRIP-2 B PH Operated Reset RS_OP_BUCH-2 B Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM OTI TRIP B PH Operated Reset RS_OP_TOP B Transmitted to IEC System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM OSR TRIP B PH Operated Reset RS_OP_OSR B Transmitted to IEC System;OptGGIO1 ST;Ind13;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind14;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM LV WTI TRIP B PH Operated Reset RS_OP_LV WDG B Transmitted to IEC System;OptGGIO1 ST;Ind14;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind15;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM PRV-1 TRIP B PH Operated Reset RS_OP_SDN PR B Transmitted to IEC System;OptGGIO1 ST;Ind15;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind17;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM BUCH TRIP-2 SP PH Operated Reset RS_OP_BUCH-2 SP Transmitted to IEC System;OptGGIO1 ST;Ind17;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind18;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM OTI TRIP SP PH Operated Reset RS_OP_TOP SP Transmitted to IEC System;OptGGIO1 ST;Ind18;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind19;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM OSR TRIP SP Operated Reset RS_OP_PRO SURGSP Transmitted to IEC System;OptGGIO1 ST;Ind19;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind20;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM LV WTI SP PH Operated Reset RS_OP_LV WDG SP Transmitted to IEC System;OptGGIO1 ST;Ind20;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind21;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM PRV-1 TRIP SP PH Operated Reset RS_OP_SDN PR SP Transmitted to IEC System;OptGGIO1 ST;Ind21;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind22;stVal;SPS SPE_HLa_Dselect_Select SPS 765kV R712_P643_64 SYSTEM AT-1 Selected Deselected DE_SEL_AT-1 Transmitted to IEC System;OptGGIO1 ST;Ind22;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM HV WTI ALARM R PH Operated Reset RS_OP_HV WDG R Transmitted to IEC System;OptGGIO1 ST;IndX;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM IV WTI ALARM R PH Operated Reset RS_OP_IV WDG R Transmitted to IEC System;OptGGIO1 ST;IndX;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM HV WTI ALARM Y PH Operated Reset RS_OP_HV WDG R Transmitted to IEC System;OptGGIO1 ST;IndX;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM IV WTI ALARM Y PH Operated Reset RS_OP_IV WDG R Transmitted to IEC System;OptGGIO1 ST;IndX;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM HV WTI ALARM B PH Operated Reset RS_OP_HV WDG R Transmitted to IEC System;OptGGIO1 ST;IndX;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P643_64 SYSTEM IV WTI ALARM B PH Operated Reset RS_OP_IV WDG R Transmitted to IEC System;OptGGIO1 ST;IndX;stVal;SPS None 1 #REF!
SPS 765kV R712_P643_64 SYSTEM SETTINGS CHANGED Set Reset None
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
ANALOG INFORMATION FROM IED IED name R712_P643_64
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P643_64
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P643_64
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P643_64
ANALOG INFORMATION TO IED IED name R712_P643_64
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R712_P643_64
A SPARE 13 ANALOG INFORMATION TO IED IED name R712_P643_64
COUNTER INFORMATION FROM IED IED name R712_P643_64
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P643_64
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P643_64
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P643_64
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P643_64
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R707_P442_21R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R707_P442_21R
DIGITAL INFORMATION FROM IED IED name R712_P442_2167HV
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P442_21/67HV PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P442_2167HV
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P442_21R GOOSE 86A TRIP RELAY Alarm Reset RS_OP_86A Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P442_21R GOOSE 86B TRIP RELAY Alarm Reset RS_OP_86B Transmitted to IEC System;GosGGIO2 ST;Ind2;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_P442_21R GOOSE BB Alarm Reset RS_ST_BB Transmitted to IEC System;GosGGIO2 ST;Ind3;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P442_21/67HV PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67HV PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;OcpEI1PTOC1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67HV PROTECTION HV OVER CURRENT R-PH TRIP Operated Reset RS_OP_HV O/C R Transmitted to IEC Protection;OcpPTOC1 ST;Op;phsA;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67HV PROTECTION HV OVER CURRENT Y-PH TRIP Operated Reset RS_OP_HV O/C Y Transmitted to IEC Protection;OcpPTOC1 ST;Op;phsB;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67HV PROTECTION HV OVER CURRENT B-PH TRIP Operated Reset RS_OP_HV O/C B Transmitted to IEC Protection;OcpPTOC1 ST;Op;phsC;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67HV PROTECTION HV OVER CURRENT TRIP Operated Reset RS_OP_HV O/C Transmitted to IEC Protection;OcpPTOC1 ST;Op;general;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67HV PROTECTION HV OVER CURRENT START Set Reset RS_OP_HV O/C S Transmitted to IEC Protection;OcpPTOC1 ST;Str;general;general;ACD None 1 0
SPS 765kV R712_P442_21/67HV SYSTEM SETTINGS CHANGED Set Reset
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
A SPARE ** Any additional Signals as per Scheme & TS No 1 #REF!
DIGITAL INFORMATION TO IED IED name R712_P442_2167HV
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 765kV R712_P442_21/67HV SYSTEM PRV-2 TRIP R PH Operated Reset NL_AL_BUCH R System;OptGGIO1 ST;Ind1;stVal;SPS 2 #REF!
A SPARE SPS 765kV R712_P442_21/67HV SYSTEM PRV-2 TRIP Y PH Operated Reset NL_AL_BUCH Y System;OptGGIO1 ST;Ind2;stVal;SPS 2 #REF!
A SPARE SPS 765kV R712_P442_21/67HV SYSTEM PRV-2 TRIP B PH Operated Reset NL_AL_BUCH B System;OptGGIO1 ST;Ind3;stVal;SPS 2 #REF!
A SPARE SPS 765kV R712_P442_21/67HV SYSTEM PRV-2 TRIP SP PH Operated Reset NL_AL_BUCH SP System;OptGGIO1 ST;Ind4;stVal;SPS 2 #REF!
A SPARE SPS 765kV R712_P442_21/67HV SYSTEM PRV-3 TRIP R PH Alarm Normal RS_OP_WDG R System;OptGGIO1 ST;Ind5;stVal;SPS 2 #REF!
A SPARE SPS 765kV R712_P442_21/67HV SYSTEM PRV-3 TRIP Y PH Alarm Normal RS_OP_WDG Y System;OptGGIO1 ST;Ind6;stVal;SPS 2 #REF!
A SPARE SPS 765kV R712_P442_21/67HV SYSTEM PRV-3 TRIP B PH Alarm Normal RS_OP_WDG B System;OptGGIO1 ST;Ind7;stVal;SPS 2 #REF!
A SPARE SPS 765kV R712_P442_21/67HV SYSTEM PRV-3 TRIP SP PH Alarm Normal RS_OP_WDG SP System;OptGGIO1 ST;Ind8;stVal;SPS 2 #REF!
ANALOG INFORMATION FROM IED IED name R712_P442_2167HV
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 765kV R712_P442_21/67HV PROTECTION DIRECTIONAL EARTH FAULT START Start Reset RS_ST_E/F_S Protection;EfdPTOC1 ST;Op;phsC;general;ACD Yes 6 ANALOG INFORMATION FROM IED IED name R712_P442_2167HV
A SPARE SPS 765kV R712_P442_21/67HVHV PROTECTION DIRECTIONAL EARTH FAULT Trip Reset RS_ST_E/F Protection;EfdPTOC1 ST;Op;phsC;general;ACT Yes 6 ANALOG INFORMATION FROM IED IED name R712_P442_2167HV
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P442_2167HV
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P442_2167HV
ANALOG INFORMATION TO IED IED name R712_P442_2167HV
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R712_P442_2167HV
A SPARE 13 ANALOG INFORMATION TO IED IED name R712_P442_2167HV
COUNTER INFORMATION FROM IED IED name R712_P442_2167HV
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P442_2167HV
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P442_2167HV
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P442_2167HV
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P442_2167HV
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R707_P442_21R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R707_P442_21R
DIGITAL INFORMATION FROM IED IED name R712_P442_21/67LV
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P442_21/67LV PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P442_21/67LV
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P442_21R GOOSE 86A TRIP RELAY Alarm Reset RS_OP_86A Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P442_21R GOOSE 86B TRIP RELAY Alarm Reset RS_OP_86B Transmitted to IEC System;GosGGIO2 ST;Ind2;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_P442_21R GOOSE BB Alarm Reset RS_ST_BB Transmitted to IEC System;GosGGIO2 ST;Ind3;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P442_21/67LV PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67LV PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;OcpEI1PTOC1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67LV PROTECTION LV OVER CURRENT R-PH TRIP Operated Reset RS_OP_HV O/C R Transmitted to IEC Protection;OcpPTOC1 ST;Op;phsA;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67LV PROTECTION LV OVER CURRENT Y-PH TRIP Operated Reset RS_OP_HV O/C Y Transmitted to IEC Protection;OcpPTOC1 ST;Op;phsB;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67LV PROTECTION LV OVER CURRENT B-PH TRIP Operated Reset RS_OP_HV O/C B Transmitted to IEC Protection;OcpPTOC1 ST;Op;phsC;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67LV PROTECTION LV OVER CURRENT TRIP Operated Reset RS_OP_HV O/C Transmitted to IEC Protection;OcpPTOC1 ST;Op;general;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67LV PROTECTION LV OVER CURRENT STAGE START-1 Set Reset RS_OP_HV O/C S Transmitted to IEC Protection;OcpPTOC1 ST;Str;general;general;ACD None 1 0
A Protection;OcpEI1PTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67LV PROTECTION LV OVER CURRENT STAGE START-2 Set Reset RS_OP_HV O/C S Transmitted to IEC Protection;OcpPTOC1 ST;Str;general;general;ACD None 1 0
A Protection;OcpEI1PTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67LV PROTECTION LV OVER CURRENT STAGE TRIP-1 Set Reset RS_OP_HV O/C S Transmitted to IEC Protection;OcpPTOC1 ST;Str;general;general;ACD None 1 0
A Protection;OcpEI1PTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67LV PROTECTION LV OVER CURRENT STAGE TRIP-2 Set Reset RS_OP_HV O/C S Transmitted to IEC Protection;OcpPTOC1 ST;Str;general;general;ACD None 1 0
SPS 765kV R712_P442_21/67LV SYSTEM SETTINGS CHANGED Set Reset
A SPARE ** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database No 1 #REF!
** Any additional Signals as per Scheme & TS
A SPARE None No 1 #REF!
DIGITAL INFORMATION TO IED IED name R712_P442_21/67LV
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 765kV R712_P442_21/67LV SYSTEM SUDDEN PRESSURE HIGH TRIP R PH Operated Reset RS_OP_SPHT R System;OptGGIO1 ST;Ind1;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R712_P442_21/67LV
A SPARE SPS 765kV R712_P442_21/67LV SYSTEM SUDDEN PRESSURE HIGH TRIP Y PH Operated Reset RS_OP_SPHT Y System;OptGGIO1 ST;Ind2;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R712_P442_21/67LV
A SPARE SPS 765kV R712_P442_21/67LV SYSTEM SUDDEN PRESSURE HIGH TRIP B PH Operated Reset RS_OP_SPHT B System;OptGGIO1 ST;Ind3;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R712_P442_21/67LV
A SPARE SPS 765kV R712_P442_21/67LV SYSTEM SUDDEN PRESSURE HIGH TRIP SP PH Operated Reset RS_OP_SPHT SP System;OptGGIO1 ST;Ind4;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R712_P442_21/67LV
ANALOG INFORMATION FROM IED IED name R712_P442_21/67LV
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 765kV R712_P442_21/67LV PROTECTION DIRECTIONAL EARTH FAULT START Set Reset RS_ST_E/F_S Protection;EfdPTOC1 ST;Op;phsC;general;ACD Yes 6 ANALOG INFORMATION FROM IED IED name R712_P442_21/67LV
A SPARE SPS 765kV R712_P442_21/67LV PROTECTION DIRECTIONAL EARTH FAULT Trip Reset RS_ST_E/F Protection;EfdPTOC1 ST;Op;phsC;general;ACT Yes 6 ANALOG INFORMATION FROM IED IED name R712_P442_21/67LV
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P442_21/67LV
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P442_21/67LV
ANALOG INFORMATION TO IED IED name R712_P442_21/67LV
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R712_P442_21/67LV
A SPARE 13 ANALOG INFORMATION TO IED IED name R712_P442_21/67LV
COUNTER INFORMATION FROM IED IED name R712_P442_21/67LV
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P442_21/67LV
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P442_21/67LV
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P442_21/67LV
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P442_21/67LV
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R712_P141_64S GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R712_P141_64S
DIGITAL INFORMATION FROM IED IED name R712_P141_64S
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P141_64S PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P141_64S
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P141_64S PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R712_P141_64S
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLa_Dselect_Select SPS 765kV R712_P141_64S SYSTEM AT-2 SELECT Selected Deselected DE_SEL_AT-2 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P141_64S
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P141_64S SYSTEM DWTM TOP OIL TEMP HIGH TRIP R PH Operated Reset RS_OP_DWTM TOP R Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P141_64S
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P141_64S SYSTEM DWTM TOP OIL TEMP HIGH TRIP Y PH Operated Reset RS_OP_DWTM TOP Y Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P141_64S
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P141_64S SYSTEM DWTM TOP OIL TEMP HIGH TRIP B PH Operated Reset RS_OP_DWTM TOP B Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P141_64S
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P141_64S SYSTEM DWTM TOP OIL TEMP HIGH TRIP SP PH Operated Reset RS_OP_DWTM TOP S Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P141_64S
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P141_64S PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R712_P141_64S
A Protection;SenRefPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P141_64S PROTECTION REF Operated Reset RS_OP_REF Transmitted to IEC Protection;SenRefPDIF1 ST;Op;general;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R712_P141_64S
A SPARE SPS 765kV R712_P141_64S SYSTEM SETTINGS CHANGED Set Reset No 1 DIGITAL INFORMATION FROM IED IED name R712_P141_64S
A SPARE ** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database No 1 DIGITAL INFORMATION FROM IED IED name R712_P141_64S
A SPARE ** Any additional Signals as per Scheme & TS No 1 DIGITAL INFORMATION FROM IED IED name R712_P141_64S
DIGITAL INFORMATION TO IED IED name R712_P141_64S
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P141_64S
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P141_64S
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P141_64S
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P141_64S
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P141_64S
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P141_64S
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P141_64S
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P141_64S
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P141_64S
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P141_64S
ANALOG INFORMATION FROM IED IED name R712_P141_64S
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P141_64S
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P141_64S
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P141_64S
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P141_64S
ANALOG INFORMATION TO IED IED name R712_P141_64S
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R712_P141_64S
A SPARE 13 ANALOG INFORMATION TO IED IED name R712_P141_64S
COUNTER INFORMATION FROM IED IED name R712_P141_64S
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P141_64S
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P141_64S
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P141_64S
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P141_64S
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R712_P743_PU_A GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R712_P743_PU_A
DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P743_PU_A PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P743_PU_A GOOSE LBB START Set Reset RS_OP_LBB START Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P743_PU_A PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLa_Reset_Close SPS 765kV R712_P743_PU_A SYSTEM MAIN CB Close Reset RS_CL_MAIN CB Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Open SPS 765kV R712_P743_PU_A SYSTEM MAIN CB Open Normal RS_OE_MAIN CB Transmitted to IEC System;OptGGIO1 ST;Ind2;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLa_Reset_Close SPS 765kV R712_P743_PU_A SYSTEM 89A ISOLATOR Close Reset RS_CL_89A Transmitted to IEC System;OptGGIO1 ST;Ind3;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Open SPS 765kV R712_P743_PU_A SYSTEM 89A ISOLATOR Open Normal RS_OE_89A Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R712_P743_PU_A SYSTEM MAIN CB CLOSE COMMAND Set Reset RS_ST_M CB CLS C Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P743_PU_A SYSTEM LBB INITIATION 3-PH Set Reset RS_OP_LBB INI 3P Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
A Protection;CbfBbpRBRF1 ST;OpIn;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P743_PU_A PROTECTION EXTERNAL CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF1 ST;OpIn;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
A Protection;CbfBbpRBRF2 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P743_PU_A PROTECTION EXTERNAL CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF2 ST;OpEx;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
A Protection;CbfBbpRBRF3 ST;OpIn;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P743_PU_A PROTECTION CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S3 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
A Protection;CbfBbpRBRF4 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P743_PU_A PROTECTION CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S4 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT None 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
A SPARE SPS 765kV R712_P743_PU_A SYSTEM B/B PU-B HEALTHY Healthy Unhealthy UN_HL_BB_PU B System;OptGGIO1 ST;IndX;stVal;SPS None No 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
SPS 765kV R712_P743_PU_A SYSTEM SETTINGS CHANGED Set Reset
A SPARE ** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database No 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
A SPARE ** Any additional Signals as per Scheme & TS No 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_A
DIGITAL INFORMATION TO IED IED name R712_P743_PU_A
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_A
ANALOG INFORMATION FROM IED IED name R712_P743_PU_A
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P743_PU_A
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P743_PU_A
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P743_PU_A
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P743_PU_A
ANALOG INFORMATION TO IED IED name R712_P743_PU_A
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R712_P743_PU_A
A SPARE 13 ANALOG INFORMATION TO IED IED name R712_P743_PU_A
COUNTER INFORMATION FROM IED IED name R712_P743_PU_A
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P743_PU_A
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P743_PU_A
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P743_PU_A
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P743_PU_A
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R712_P743_PU_B GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R712_P743_PU_B
DIGITAL INFORMATION FROM IED IED name R712_P743_PU_B
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P743_PU_B PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_B
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P743_PU_B GOOSE LBB START Set Reset RS_OP_LBB START Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_B
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P743_PU_B PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R712_P743_PU_B
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R712_P743_PU_B SYSTEM LBB INITIATION 3-PH Set Reset RS_OP_LBB INI 3P Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A Protection;CbfBbpRBRF1 ST;OpIn;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P743_PU_B PROTECTION EXTERNAL CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF1 ST;OpIn;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF2 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P743_PU_B PROTECTION EXTERNAL CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF2 ST;OpEx;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF3 ST;OpIn;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P743_PU_B PROTECTION CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S3 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF4 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P743_PU_B PROTECTION CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S4 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT None 1 #REF!
A SPARE SPS 765kV R707_P743_PU_B PROTECTION B/B PU-A HEALTHY Healthy Unhealthy UN_HL_BB_PU A System;OptGGIO1 ST;IndX;stVal;SPS None No 1 #REF!
A SPARE SPS 765kV R712_P141_64S SYSTEM SETTINGS CHANGED Set Reset No 1 #REF!
A SPARE No 1 #REF!
A SPARE ** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database No 1 #REF!
A SPARE ** Any additional Signals as per Scheme & TS No 1 #REF!
DIGITAL INFORMATION TO IED IED name R712_P743_PU_B
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R712_P743_PU_B
ANALOG INFORMATION FROM IED IED name R712_P743_PU_B
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P743_PU_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P743_PU_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P743_PU_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R712_P743_PU_B
ANALOG INFORMATION TO IED IED name R712_P743_PU_B
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R712_P743_PU_B
A SPARE 13 ANALOG INFORMATION TO IED IED name R712_P743_PU_B
COUNTER INFORMATION FROM IED IED name R712_P743_PU_B
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P743_PU_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P743_PU_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P743_PU_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R712_P743_PU_B
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
MiCOM C264 DESCRIPTION
Computer Name B707_LINE GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) C264 Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 0
Digital Inputs Board Slot P
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A P 1 SPARE SPS 765kV B707_LINE 52 CB R PH POSITION Open OE_CL_R-PH_POS CONTROL2;XCBR2 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 2 SPARE SPS 765kV B707_LINE 52 CB R PH POSITION Closed OE_CL_R-PH_POS CONTROL2;XCBR2 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 3 SPARE SPS 765kV B707_LINE 52 CB Y PH POSITION Open OE_CL_Y-PH_POS CONTROL2;XCBR3 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 4 SPARE SPS 765kV B707_LINE 52 CB Y PH POSITION Closed OE_CL_Y-PH_POS CONTROL2;XCBR3 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 5 SPARE SPS 765kV B707_LINE 52 CB B PH POSITION Open OE_CL_B-PH_POS CONTROL2;XCBR4 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 6 SPARE SPS 765kV B707_LINE 52 CB B PH POSITION Closed OE_CL_B-PH_POS CONTROL2;XCBR4 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 7 SPE_HLA_Normal_Alarm SPS 765kV B707_LINE 52 SF6 GAS PRESSURE REFILL LOW Alarm Normal NL_AL_GAS RFL LO Transmitted to IEC CONTROL2;XCBR1 ST;Ind8;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 8 SPE_HLA_Normal_Alarm SPS 765kV B707_LINE 52 SF6 GAS PRESSURE REFILL LEVEL-1 LOW Alarm Normal NL_AL_GAS RFL L1 Transmitted to IEC CONTROL2;XCBR1 ST;Ind9;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 9 SPE_HLA_Unhlthy_Hlthy SPS 765kV B707_LINE CB HEALTHY AUTO RECLOSE CB Healthy Unhealthy UH_HL_CB Transmitted to IEC CONTROL1;GGIO5 ST;Ind1;stVal;SPS 15;16;17; None 1 DIGITAL INPUT BOARD DIU2xx
A P 10 SPE_HLa_Reset_Set SPS 765kV B707_LINE 52 CB IN REMOTE MODE Set Reset RS_ST_CB REMOTE Transmitted to IEC CONTROL2;XCBR1 ST;Ind2;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 11 SPE_HLA_Dischrgd_Charged SPS 765kV B707_LINE 52 CB SPRING Charged Discharged DC_CH_ SPRING Transmitted to IEC CONTROL2;XCBR1 ST;Ind10;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 12 SPE_HLA_Normal_Fail SPS 765kV B707_LINE 52 AC SUPPLY R Y B Fail Normal NL_FL_AC SUPPLY Transmitted to IEC CONTROL2;XCBR1 ST;Ind3;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 13 SPE_HLA_Normal_Alarm SPS 765kV B707_LINE 52 SF6 GAS SECOND STAGE LOW Alarm Normal NL_AL_SF6 L2 Transmitted to IEC CONTROL2;XCBR1 ST;Ind5;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 14 SPE_HLA_Normal_Fail SPS 765kV B707_LINE 52 DC SUPPLY-1/2 Fail Normal NL_FL_DC-1/2 SUP Transmitted to IEC CONTROL2;XCBR1 ST;Ind11;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 15 SPE_HLA_Normal_Alarm SPS 765kV B707_LINE 52 SF6 GAS PRESSURE LEVEL-2 LOW Alarm Normal NL_AL_SF6 L2 LOW Transmitted to IEC CONTROL2;XCBR1 ST;Ind1;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 16 SPE_HLa_Reset_Set SPS 765kV B707_LINE 52 SF6 GAS SECOND STAGE NORMAL Set Reset NL_AL_SF6 2ND ST Transmitted to IEC CONTROL2;XCBR1 ST;Ind7;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 1
Digital Inputs Board Slot O
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A O 1 SPE_HLA_Normal_Alarm SPS 765kV B707_LINE 52 PH. POSITION DISCORDANCE Alarm Normal NL_AL_PD Transmitted to IEC CONTROL2;XCBR1 ST;Ind4;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 2 SPE_HLA_Reset_Optd SPS 765kV B707_LINE 52 SF6 LOW PRESSURE LEVEL-2 NORMAL Operated Reset NL_AL_ LO PR L2 Transmitted to IEC CONTROL2;XCBR1 ST;Ind6;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 5 DP_HLA_ ISOOpen_Close DPS 765kV B707_LINE 89A POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 10;25;5;6; None 2 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 6 DP_HLA_ ISOOpen_Close DPS 765kV B707_LINE 89A POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 10;25;5;6; None 2 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 7 DP_HLa_ESOpen_Close DPS 765kV B707_LINE 89AE1 POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI3 ST;Pos;stVal;DPC 119;120;121;2;240;241;242;3;331;332;333;4; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 8 DP_HLa_ESOpen_Close DPS 765kV B707_LINE 89AE1 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI3 ST;Pos;stVal;DPC 119;120;121;2;240;241;242;3;331;332;333;4; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 9 DP_HLa_ESOpen_Close DPS 765kV B707_LINE 89AE2 POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI4 ST;Pos;stVal;DPC 2;3;4;7;8;9; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 10 DP_HLa_ESOpen_Close DPS 765kV B707_LINE 89AE2 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI4 ST;Pos;stVal;DPC 2;3;4;7;8;9; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 11 DP_HLA_ ISOOpen_Close DPS 765kV B707_LINE 89B POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 10;25;59;6; None 3 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 12 DP_HLA_ ISOOpen_Close DPS 765kV B707_LINE 89B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 10;25;59;6; None 3 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 13 DP_HLa_ESOpen_Close DPS 765kV B707_LINE 89BE POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI2 ST;Pos;stVal;DPC 2;3;4;7;8;9; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 14 DP_HLa_ESOpen_Close DPS 765kV B707_LINE 89BE POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI2 ST;Pos;stVal;DPC 2;3;4;7;8;9; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 15 DP_HLA_ ISOOpen_Close DPS 765kV B707_LINE 89L POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI3 ST;Pos;stVal;DPC 14;50;59;70; None 4 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 16 DP_HLA_ ISOOpen_Close DPS 765kV B707_LINE 89L POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI3 ST;Pos;stVal;DPC 14;50;59;70; None 4 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 2
Digital Inputs Board Slot N
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A N 1 DP_HLA_ ISOOpen_Close DPS 765kV B707_LINE 89LE POSTION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI1 ST;Pos;stVal;DPC 11;12;13; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 2 DP_HLA_ ISOOpen_Close DPS 765kV B707_LINE 89LE POSTION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI1 ST;Pos;stVal;DPC 11;12;13; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 3 SPE_HLA_Normal_Fail SPS 765kV B707_LINE PROTECTION CARRIOR SPEECH CH Fail Normal NL_FL_CARR SPECH Transmitted to IEC CONTROL1;GGIO2 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 4 SPE_HLA_Normal_Fail SPS 765kV B707_LINE PROTECTION DC SOURCE-1 Fail Normal NL_FL_DC-1 Transmitted to IEC CONTROL1;GGIO2 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 5 SPE_HLA_Normal_Fail SPS 765kV B707_LINE PROTECTION DC SOURCE-2 Fail Normal NL_FL_DC-2 Transmitted to IEC CONTROL1;GGIO2 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 7 SPE_HLA_Healthy_Flty SPS 765kV B707_LINE PROTECTION CB TC-2 Faulty Healthy HL_FT_CB TC2 Transmitted to IEC CONTROL1;GGIO2 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 8 SPE_HLA_Reset_Optd SPS 765kV B707_LINE AR FUNCTION-LINE BLOCK CONTACTS Operated Reset RS_OP_AR BLOCK Transmitted to IEC CONTROL1;RREC1 ST;Ind1;stVal;SPS 1; None ARFct AR_Blocking_SPS 1 DIGITAL INPUT BOARD DIU2xx
A N 9 SPE_HLA_Reset_Optd SPS 765kV B707_LINE AR FUNCTION-LINE R-PH INITIATION Operated Reset RS_OP_PHR INI Transmitted to IEC CONTROL1;RREC1 ST;Ind2;stVal;SPS 16; None ARFct TripPhA_SPS 1 DIGITAL INPUT BOARD DIU2xx
A N 10 SPE_HLA_Reset_Optd SPS 765kV B707_LINE AR FUNCTION-LINE Y-PH INITIATION Operated Reset RS_OP_PHY INI Transmitted to IEC CONTROL1;RREC1 ST;Ind3;stVal;SPS 16; None ARFct TripPhB_SPS 1 DIGITAL INPUT BOARD DIU2xx
A N 11 SPE_HLA_Reset_Optd SPS 765kV B707_LINE AR FUNCTION-LINE B-PH INITIATION Operated Reset RS_OP_PHB INI Transmitted to IEC CONTROL1;RREC1 ST;Ind4;stVal;SPS 16; None ARFct TripPhC_SPS 1 DIGITAL INPUT BOARD DIU2xx
A N 12 SPE_HLA_Alm_Reset SPS 765kV B707_LINE PROTECTION A/R LOCKOUT Reset Operated OP_RS_A/R LO Transmitted to IEC CONTROL1;GGIO2 ST;Ind7;stVal;SPS 1; None 1 DIGITAL INPUT BOARD DIU2xx
A N 13 SPE_HLA_Reset_Send SPS 765kV B707_LINE PROTECTION DIRECT TRIP CHANNEL-1 Send Reset RS_SE_DT CH-1 Transmitted to IEC CONTROL1;GGIO2 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 15 SPE_HLA_Reset_Send SPS 765kV B707_LINE PROTECTION DIRECT TRIP CHANNEL-2 Send Reset RS_SE_DT CH-2 Transmitted to IEC CONTROL1;GGIO2 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 3
Digital Inputs Board Slot M
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A M 1 DP_HLA_Trip_Closed DPS 765kV B707_LINE 52 EMERGENCY/MANUAL Closed TP_CL_EMRG/MAN Transmitted to IEC CONTROL2;XCBR1 ST;DPCSO1;stVal;DPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A M 2 DP_HLA_Trip_Closed DPS 765kV B707_LINE 52 EMERGENCY/MANUAL Trip TP_CL_EMRG/MAN Transmitted to IEC CONTROL2;XCBR1 ST;DPCSO1;stVal;DPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A M 3 SPE_HLa_Reset_Set SPS 765kV B707_LINE 707-LA LR-R PH OPEN Set Reset LR-R PH OPEN Transmitted to IEC CONTROL1;GGIO6 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 4 SPE_HLa_Reset_Set SPS 765kV B707_LINE 707-LA LR-Y PH OPEN Set Reset LR-Y PH OPEN Transmitted to IEC CONTROL1;GGIO6 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 5 SPE_HLa_Reset_Set SPS 765kV B707_LINE 707-LA LR-B PH OPEN Set Reset LR-B PH OPEN Transmitted to IEC CONTROL1;GGIO6 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 6 SPE_HLa_Reset_Set SPS 765kV B707_LINE 707-LA R PH OPEN Set Reset R PH OPEN Transmitted to IEC CONTROL1;GGIO6 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 7 SPE_HLa_Reset_Set SPS 765kV B707_LINE 707-LA Y PH OPEN Set Reset Y PH OPEN Transmitted to IEC CONTROL1;GGIO6 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 8 SPE_HLa_Reset_Set SPS 765kV B707_LINE 707-LA B PH OPEN Set Reset B PH OPEN Transmitted to IEC CONTROL1;GGIO6 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 4
Digital Inputs Board Slot L
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A L 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 0
Digital Outputs Board Slot D
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A D 1 DC_SBO_Open_Close DPC 765kV B707_LINE 52 CB CONTROL Open OP_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 1 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A D 2 SC_DE_Set_1 SPC 765kV B707_LINE PROTECTION CB TC-2 Set XX_XX_TC2 Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO1;ctlVal;DPC 285 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 3 DC_SBO_Open_Close DPC 765kV B707_LINE 52 CB CONTROL Close OP_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 1 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A D 4 SC_DE_Set_1 SPC 765kV B707_LINE PROTECTION CB CLOSE TO PU-A Set XX_XX_CB CL PUA Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO2;ctlVal;DPC 10 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 5 SC_DE_Set_1 SPC 765kV B707_LINE PROTECTION CB CLOSE TO PU-B Set XX_XX_CB CL PUB Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO3;ctlVal;DPC 9 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 6 SC_DE_Reset_Reset SPC 765kV B707_LINE AR DATA TO A/R CLSG. CKT RESET XX_XX_A/R CLSG C Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO1;ctlVal;DPC 42 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 7 SC_DE_Off_On SPC 765kV B707_LINE AR DATA A/R OFF On Off XX_XX_A/R OFF Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO2;ctlVal;DPC 1 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 8 SC_DE_Reset_Reset_1 SPC 765kV B707_LINE AR DATA A/R LOCKOUT TRIP RESET XX_XX_A/R L/O Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO3;ctlVal;DPC 40 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 9 SC_DE_NotPerm_Perm SPC 765kV B707_LINE AR DATA TO TIE A/R PROIRITY CKT HOLD RESET XX_XX_TI AR CKTH Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO4;ctlVal;DPC 43 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A D 10 SC_DE_Reset_Set SPC 765kV B707_LINE AR DATA MAIN CB A/R OPTD Set XX_XX_MAIN CB AR Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO5;ctlVal;DPC 41 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 1
Digital Outputs Board Slot E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A E 1 DC_SBO_Open_Close_1 DPC 765kV B707_LINE 89A CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 2 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 2 DC_SBO_Open_Close_1 DPC 765kV B707_LINE 89A CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 2 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 3 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LINE INTERLOCK PERM 89A IL PERM RESET XX_XX_89A Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO1;ctlVal;DPC 33 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 4 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LINE INTERLOCK PERM 89AE2 IL PERM RESET XX_XX_89AE2 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO2;ctlVal;DPC 35 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 5 DC_SBO_Open_Close_1 DPC 765kV B707_LINE 89B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 3 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 6 DC_SBO_Open_Close_1 DPC 765kV B707_LINE 89B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 3 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 7 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LINE INTERLOCK PERM 89B IL PERM RESET XX_XX_89B Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO3;ctlVal;DPC 36 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 8 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LINE INTERLOCK PERM 89BE IL PERM RESET XX_XX_89BE Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO4;ctlVal;DPC 37 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A E 10 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LINE INTERLOCK PERM 89AE1 IL PERM RESET XX_XX_89AE1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO5;ctlVal;DPC 34 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 2
Digital Outputs Board Slot F
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A F 1 DC_SBO_Open_Close_1 DPC 765kV B707_LINE 89L 89L CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 4 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 2 DC_SBO_Open_Close_1 DPC 765kV B707_LINE 89L 89L CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 4 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 3 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LINE INTERLOCK PERM 89L IL PERM RESET XX_XX_89L Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO6;ctlVal;DPC 38 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 4 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LINE INTERLOCK PERM 89LE IL PERM RESET XX_XX_89LE Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO7;ctlVal;DPC 39 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 5 SC_DE_Reset_Reset_1 SPC 765kV B707_LINE PROTECTION TRIP RELAY 86A RESET XX_RS_86A Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO5;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 6 SC_DE_Reset_Reset_1 SPC 765kV B707_LINE PROTECTION TRIP RELAY 86B RESET XX_RS_86B Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO6;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 7 SC_DE_Reset_Reset_1 SPC 765kV B707_LINE PROTECTION A/R RLY RESET XX_RS_A/R RLY Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO4;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 8 SC_DE_Set_1 SPC 765kV B707_LINE DT SEND DIRECT TRIP SEND CH-1 Set XX_XX_DT SD CH1 Transmitted to IEC CONTROL1;GGIO4 CO;SPCSO1;ctlVal;DPC 45 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 9 SC_DE_Set_1 SPC 765kV B707_LINE DT SEND DIRECT TRIP SEND CH-2 Set XX_XX_DT SD CH2 Transmitted to IEC CONTROL1;GGIO4 CO;SPCSO2;ctlVal;DPC 44 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A F 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 3
Digital Outputs Board Slot G
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A G 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A G 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
CT/VT ANALOG INPUT BOARD TMU2x0
CT/VT Board Number 0
CT/VT Board Slot Q
CT/VT Board Model TMU220
Nominal Current 1 (1A/5A)
Nominal Voltage 110.00 [1V … 500V]
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A DF MV_HLa_Frequency_2 Hz 765kV B707_LINE SYNCH DATA FREQUENCY DIFFERENCE 0.0 2.0 FREQUENCY DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifHzClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DV MV_HLa_Voltage_1 kV 765kV B707_LINE SYNCH DATA VOLTAGE DIFFERENCE 0.0 530.0 VOLTAGE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifVClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Dj MV_hla_PhaseDiff ˚ 765kV B707_LINE SYNCH DATA PHASE DIFFERENCE 0.0 360.0 PHASE ANGLE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifAngClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ia MV_HLa_AuxCurrent A 765kV B707_LINE METERING-LINE I-R PHASE CURRENT 0.0 2400.0 IR PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ib MV_HLa_AuxCurrent A 765kV B707_LINE METERING-LINE I-Y PHASE CURRENT 0.0 2400.0 IY PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ic MV_HLa_Frequency_1 Hz 765kV B707_LINE METERING-LINE I-B PHASE CURRENT 0.0 2400.0 IB PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsC;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vb MV_HLa_Voltage_1 kV 765kV B707_LINE SYNCH DATA INCOMING SUPPLY 0.0 530.02 INCOMING SUPPLY Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;PhV;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uab MV_HLa_Voltage kV 765kV B707_LINE METERING-LINE R-Y VOLTAGE 0.0 918.0 R-Y VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsAB;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ubc MV_HLa_Voltage kV 765kV B707_LINE METERING-LINE Y-B VOLTAGE 0.0 918.0 Y-B VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsBC;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uca MV_HLa_Voltage kV 765kV B707_LINE METERING-LINE B-R VOLTAGE 0.0 918.0 B-R VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsCA;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar MV_HLa_Voltage_1 kV 765kV B707_LINE SYNCH DATA RUNNING SUPPLY-1 0.0 530.02 RUNNING SPLY-1 Transmitted to IEC MEASUREMENT1;barMMXU1 MX;PhV;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Freq (Line) MV_HLa_Frequency Hz 765kV B707_LINE METERING-LINE FREQUENCY 45.0 55.0 FREQUENCY Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;Hz;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A P total (MW) MV_HLa_ActPower MW 765kV B707_LINE METERING-LINE ACTIVE POWER -3179.952 3179.952 ACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotW;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Q total (Mvar) MV_HLa_ReactPower MVAr 765kV B707_LINE METERING-LINE REACTIVE POWER -3179.952 3179.952 REACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotVAr;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar RMS 2 value of the busbar voltage phase MV_HLa_Voltage_1 kV 765kV B707_LINE SYNCH DATA RUNNING SUPPLY-2 0.0 530.02 RUNNING SPLY-2 Transmitted to IEC MEASUREMENT1;GGIO1 MX;AnIn1;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A cos ft : Power factor MV_HLa_PowerFactor 765kV B707_LINE METERING-LINE POWER FACTOR -1.2 1.2 POWER FACTOR Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotPF;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPE_HLa_Reset_Set SPS 765kV B707_LINE SYNCH FUNCTION CLOSE ORDER Set Reset RS_ST_CLS ODR Transmitted to IEC CONTROL1;RSYN1 ST;ClsOpSt;stVal;SPS None IntManualCSFct CS_CloseOrderState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPE_HLA_on_off SPS 765kV B707_LINE SYNCH FUNCTION ON/OFF SECONDARY SPS On Off RS_ST_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 ST;EnaSec;origin;SPC None 114 IntManualCSFct CS_OnOff_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPE_HLa_Reset_Set SPS 765kV B707_LINE SYNCH FUNCTION POSSIBLE CLOSING Set Reset RS_ST_POS CLS Transmitted to IEC CONTROL1;RSYN1 ST;Rel;stVal;SPS 24; None IntManualCSFct CS_AuthoState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPE_HLa_Reset_Set SPS 765kV B707_LINE SYNCH FUNCTION RS_ST_V CHOICE Set Reset RS_ST_V CHOICE Transmitted to IEC CONTROL1;RSYN1 ST;BusVC;stVal;SPS 25<; None IntManualCSFct CS_BusBarVChoice_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPE_HLa_Reset_Set SPS 765kV B707_LINE 52 | OP_CL_CONTROL CLOSE ORDER Set Reset CLOSE ORDER Transmitted to IEC CONTROL1;CSWI4 ST;ClsOrd;general;general;ACT 15;23; None 9;10 CB CloseOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPE_HLa_Notper_Perm SPS 765kV B707_LINE 52 | OP_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLOSE INTE Transmitted to IEC CONTROL2;CILO4 ST;EnaCls;stVal;SPS None CB CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPE_HLa_Notper_Perm SPS 765kV B707_LINE 89A | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPE_HLa_Notper_Perm SPS 765kV B707_LINE 89B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO2 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPE_HLa_Notper_Perm SPS 765kV B707_LINE 89L | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO3 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPE_HLa_Reset_Set SPS 765kV B707_LINE SYNCH FUNCTION PRESENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF U PRES Transmitted to IEC CONTROL1;RSYN1 ST;VRefInd;stVal;SPS 24; None IntManualCSFct CS_VoltageRefPresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPE_HLa_Reset_Set SPS 765kV B707_LINE SYNCH FUNCTION ABSENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF. U ABS Transmitted to IEC CONTROL1;RSYN1 ST;VRefAbs;stVal;SPS 24; None IntManualCSFct CS_VoltageRefAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPE_HLa_Reset_Set SPS 765kV B707_LINE SYNCH FUNCTION VOLT ABSENCE Set Reset RS_ST_VOLT ABS Transmitted to IEC CONTROL1;RSYN1 ST;VAbs;stVal;SPS 14;24; None IntManualCSFct CS_VoltageAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPE_HLa_Reset_Set SPS 765kV B707_LINE SYNCH FUNCTION VOLT PRESENCE Set Reset RS_ST_VOLT PRES Transmitted to IEC CONTROL1;RSYN1 ST;VP;stVal;SPS 24; None IntManualCSFct CS_VoltagePresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPE_HLa_Notper_Perm SPS 765kV B707_LINE 89A INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI1 ST;IndSys1;stVal;SPS 2<; None 33 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPE_HLa_Notper_Perm SPS 765kV B707_LINE 89AE1 INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL3;CSWI1 ST;IndSys1;stVal;SPS 5<; None 34 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPE_HLa_Notper_Perm SPS 765kV B707_LINE 89AE2 INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI1 ST;IndSys1;stVal;SPS 6<; None 35 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 17 SPE_HLa_Notper_Perm SPS 765kV B707_LINE 89B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI2 ST;IndSys1;stVal;SPS 7<; None 36 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 18 SPE_HLa_Notper_Perm SPS 765kV B707_LINE 89BE INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI3 ST;IndSys1;stVal;SPS 10<; None 37 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 19 SPE_HLa_Notper_Perm SPS 765kV B707_LINE 89L INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI3 ST;IndSys1;stVal;SPS 11<; None 38 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 20 SPE_HLa_Notper_Perm SPS 765kV B707_LINE 89LE INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI2 ST;IndSys1;stVal;SPS 14<; None 39 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 21 SPE_HLA_Reset_Optd SPS 765kV B707_LINE AR DATA LOCKOUT FROM AR LOGIC Operated Reset RS_OP_AR LO FBD Transmitted to IEC CONTROL1;GAPC2 ST;IndSys1;stVal;SPS 16<; None 40 1 C264 SELF GENERATED DIGITAL INFORMATION
A 22 SPE_HLA_Reset_Optd SPS 765kV B707_LINE AR DATA A/R OPTD FROM FBD Operated Reset RS_ST_AR OPTD FB Transmitted to IEC CONTROL1;GAPC2 ST;IndSys2;stVal;SPS 15<; None 41;42 1 C264 SELF GENERATED DIGITAL INFORMATION
A 22 SPE_HLa_Reset_Set SPS 765kV B707_LINE AR DATA AR IN PROGRESS / WAIT FOR CB OPEN Set Reset RS_ST_AR IN PROG Transmitted to IEC CONTROL1;GAPC2 ST;IndSys8;stVal;SPS 17<; None 43 1 C264 SELF GENERATED DIGITAL INFORMATION
A 23 SPE_HLa_Reset_Set SPS 765kV B707_LINE AR DATA PRIORITY CIRCUIT HOLD Set Reset RS_ST_PRI HLD ON Transmitted to IEC CONTROL1;GAPC2 ST;IndSys3;stVal;SPS 17<; None 43 1 C264 SELF GENERATED DIGITAL INFORMATION
A 24 SPE_HLa_Reset_Set SPS 765kV B707_LINE AR DATA LOCK Set Reset RS_ST_S10_LOCK Transmitted to IEC CONTROL1;GAPC2 ST;IndSys4;stVal;SPS 16; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 25 SPE_HLa_Reset_Set SPS 765kV B707_LINE AR DATA WAIT FOR CB CLOSE Set Reset RS_ST_S7_WT CB C Transmitted to IEC CONTROL1;GAPC2 ST;IndSys7;stVal;SPS 15; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 26 SPE_HLa_Reset_Set SPS 765kV B707_LINE AR DATA AR SUCCESSFUL / RECLAIM TIMER STRT Set Reset RS_ST_S8_RC TIM Transmitted to IEC CONTROL1;GAPC2 ST;IndSys6;stVal;SPS None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 27 SPE_HLa_Reset_Set SPS 765kV B707_LINE AR DATA LOCK_SHOTS Set Reset RS_ST_S9_LO SHTS Transmitted to IEC CONTROL1;GAPC2 ST;IndSys5;stVal;SPS 16; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 28 SPE_HLA_Flty_Healthy SPS 765kV B707_LINE CARRIER SIG AR CARRIER CH-1 Healthy Faulty FT_HL_CAR_CH-1 Transmitted to IEC CONTROL1;GAPC5 ST;IndSys1;stVal;SPS 16;19<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 29 SPE_HLA_Flty_Healthy SPS 765kV B707_LINE CARRIER SIG AR CARRIER CH-2 Healthy Faulty FT_HL_CAR_CH-2 Transmitted to IEC CONTROL1;GAPC5 ST;IndSys2;stVal;SPS 16;19<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 30 SPE_HLA_Reset_Alarm_Goose SPS 765kV B707_LINE CARRIER SIG AR GOOSE RECEIPT FAIL/TROUBLE Alarm Reset GOOSE RECIEPT FL Transmitted to IEC CONTROL1;GAPC5 ST;IndSys5;stVal;SPS 20<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 31 SPE_HLA_InServ_OutServ SPS 765kV B707_LINE CARRIER SIG AR CARRIER CH-1 Out Of Service In Service IS_OS_CARR_CH-1 Transmitted to IEC CONTROL1;GAPC5 ST;IndSys3;stVal;SPS 16;19<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 32 SPE_HLA_InServ_OutServ SPS 765kV B707_LINE CARRIER SIG AR CARRIER CH-2 Out Of Service In Service IS_OS_CARR_CH-2 Transmitted to IEC CONTROL1;GAPC5 ST;IndSys4;stVal;SPS 16;19<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 33 SPE_HLa_Reset_Set SPS 765kV B707_LINE DT SEND DT SEND Set Reset RS_ST_DT SEND Transmitted to IEC CONTROL1;GAPC4 ST;IndSys1;stVal;SPS 22<; None 44;45 1 C264 SELF GENERATED DIGITAL INFORMATION
A 34 SPS_HLA_Reset_Set SPS 765kV B707_LINE PROTECTION SOTF TO RLY Set Reset SOTF TO RLY Transmitted to IEC CONTROL1;GAPC1 ST;IndSys1;stVal;SPS 23<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 35 SPE_HLa_Reset_Set SPS 765kV B707_LINE SYNCH DATA CLOSE PERMISSIVE Set Reset RS_ST_CB CLOSE Transmitted to IEC CONTROL1;GAPC3 ST;IndSys5;stVal;SPS 24<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 36 SPE_HLa_Reset_Set SPS 765kV B707_LINE SYNCH DATA DEAD INCOMING DEAD RUNNING Set Reset RS_ST_DINC_DRUN Transmitted to IEC CONTROL1;GAPC3 ST;IndSys4;stVal;SPS 24<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 37 SPE_HLa_Reset_Set SPS 765kV B707_LINE SYNCH DATA DEAD INCOMING LIVE RUNNING Set Reset RS_ST_DINC_LRUN Transmitted to IEC CONTROL1;GAPC3 ST;IndSys3;stVal;SPS 24<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 38 SPE_HLa_Reset_Set SPS 765kV B707_LINE SYNCH DATA LIVE INCOMING DEAD RUNNING Set Reset RS_ST_LINC_DRUN Transmitted to IEC CONTROL1;GAPC3 ST;IndSys2;stVal;SPS 24<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 39 SPE_HLa_Reset_Set SPS 765kV B707_LINE SYNCH DATA LIVE INCOMING LIVE RUNNING Set Reset RS_ST_LINC_LRUN Transmitted to IEC CONTROL1;GAPC3 ST;IndSys1;stVal;SPS 24<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 40 SPE_HLa_Reset_Set SPS 765kV B707_LINE 52 | OP_CL_CONTROL OPEN ORDER Set Reset OPEN ORDER Transmitted to IEC CONTROL1;CSWI4 ST;OpnOrd;general;general;ACT 22; None 285 CB OpenOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 41 SPE_HLa_Notper_Perm SPS 765kV B707_LINE 89A | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 42 SPE_HLa_Notper_Perm SPS 765kV B707_LINE 89B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO2 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 43 SPE_HLa_Notper_Perm SPS 765kV B707_LINE 89L | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO3 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 44 SPE_HLA_Reset_Optd SPS 765kV B707_LINE AR FUNCTION-LINE TRIP 3-PHASES Operated Reset RS_OP_TRP 3PH Transmitted to IEC CONTROL1;RREC1 ST;Trip3P;stVal;SPS None ARFct Trip_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 45 SPS_hla_Set_Reset SPS 765kV B707_LINE Order running on the bay Set Reset Order running Transmitted to IEC CONTROL2;GBAY1 ST;OrdRun;stVal;SPS None OrderInProgress 1 C264 SELF GENERATED DIGITAL INFORMATION
A 46 DP_HLA_CBOpen_Close DPS 765kV B707_LINE 52 COMPUTED SWITCH POSITION Open OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;origin;DPC 11;111;12;13;2;22;3;4;50;7;70;71;8;9; None 1 21 CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 47 DP_HLA_CBOpen_Close DPS 765kV B707_LINE 52 COMPUTED SWITCH POSITION Closed OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;origin;DPC 11;111;12;13;2;22;3;4;50;7;70;71;8;9; None 1 21 CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 48 DP_HLA_On_Off DPS 765kV B707_LINE AR FUNCTION-LINE ON/OFF STATUS Off OF_ON_AR STATUS Transmitted to IEC CONTROL1;RREC1 ST;Ena;origin;DPC 17; None 5 1 ARFct AR_OnOff_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 49 DP_HLA_On_Off DPS 765kV B707_LINE AR FUNCTION-LINE ON/OFF STATUS On OF_ON_AR STATUS Transmitted to IEC CONTROL1;RREC1 ST;Ena;origin;DPC 17; None 5 1 ARFct AR_OnOff_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 50 DP_HLa_LocRem_Bay DPS 765kV B707_LINE BCU MODE Local LC_RM_MODE Transmitted to IEC CONTROL2;GBAY1 ST;Loc;origin;DPC None 6 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 51 DP_HLa_LocRem_Bay DPS 765kV B707_LINE BCU MODE Remote LC_RM_MODE Transmitted to IEC CONTROL2;GBAY1 ST;Loc;origin;DPC None 6 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 52 DP_HLa_LocRem_Bay DPS Local/remote DPS Local Local/remote DPS CONTROL1;GGSS1 ST;LocSubst;origin;DPC None 113 LocRemSubstation 1 C264 SELF GENERATED DIGITAL INFORMATION
A 53 DP_HLa_LocRem_Bay DPS Local/remote DPS Remote Local/remote DPS CONTROL1;GGSS1 ST;LocSubst;origin;DPC None 113 LocRemSubstation 1 C264 SELF GENERATED DIGITAL INFORMATION
A 54 MP_HLA_AR_Fault MPS 765kV B707_LINE AR FUNCTION-LINE AUTORECLOSER FAULT STATUS AUTORECLOSER FLT Transmitted to IEC CONTROL1;RREC1 ST;ARFlt;stVal;INS None ARFct AR_FaultReason_MPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 55 MP_HLA_AR_Status MPS 765kV B707_LINE AR FUNCTION-LINE AUTORECLOSER STATUS AUTORECLOSER ST Transmitted to IEC CONTROL1;RREC1 ST;ARSt;stVal;INS 17; None ARFct AR_Status_MPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 56 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SC_DE_Set SPC 765kV B707_LINE AR FUNCTION-LINE Force trip 3 Phase Set XX_XX_TRIP 3PH Transmitted to IEC CONTROL1;RREC1 CO;Trip3P;ctlVal;DPC ARFct Ctrl3PhaseTrip_SPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SC_DE_Off_On_1 SPC 765kV B707_LINE SYNCH FUNCTION ON/OFF SECONDARY CONTROL SPC On Off OF_ON_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 CO;EnaSec;ctlVal;DPC 114 IntManualCSFct CS_CtrlOnOff_SPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 DC_DE_AROff_AROn DPC 765kV B707_LINE AR FUNCTION-LINE OFF Off OF_ON_A/R OFF Transmitted to IEC CONTROL1;RREC1 CO;Ena;ctlVal;DPC 5 ARFct AR_CtrlOnOff_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 DC_DE_AROff_AROn DPC 765kV B707_LINE AR FUNCTION-LINE OFF On OF_ON_A/R OFF Transmitted to IEC CONTROL1;RREC1 CO;Ena;ctlVal;DPC 5 ARFct AR_CtrlOnOff_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 DC_DE_LocRem_BayCtrl DPC 765kV B707_LINE MODE CONTROL Local MODE CONTROL Transmitted to IEC CONTROL2;GBAY1 CO;Loc;ctlVal;DPC 6 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 DC_DE_LocRem_BayCtrl DPC 765kV B707_LINE MODE CONTROL Remote MODE CONTROL Transmitted to IEC CONTROL2;GBAY1 CO;Loc;ctlVal;DPC 6 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 DC_DE_LocRem_BayCtrl_1 DPC Local/remote control DPC Local Loc/rem ctrl DPC CONTROL1;GGSS1 CO;LocSubst;ctlVal;DPC 113 LocRemSubstation_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 DC_DE_LocRem_BayCtrl_1 DPC Local/remote control DPC Remote Loc/rem ctrl DPC CONTROL1;GGSS1 CO;LocSubst;ctlVal;DPC 113 LocRemSubstation_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 MV 765kV B707_LINE CB_COUNTER Count_Close 0.0 10000.0 Count_Close Transmitted to IEC CONTROL2;GAPC1 MX;AnIn2;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 MV 765kV B707_LINE CB_COUNTER Count_Open 0.0 10000.0 Count_Open Transmitted to IEC CONTROL2;GAPC1 MX;AnIn1;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
MiCOM C264 DESCRIPTION
Computer Name B707_LR GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) C264 Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 0
Digital Inputs Board Slot P
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A P 1 SPARE SPS 765kV B707_LR 52 CB R PH POSITION Open OE_CL_R-PH_POS CONTROL2;XCBR2 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 2 SPARE SPS 765kV B707_LR 52 CB R PH POSITION Closed OE_CL_R-PH_POS CONTROL2;XCBR2 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 3 SPARE SPS 765kV B707_LR 52 CB Y PH POSITION Open OE_CL_Y-PH_POS CONTROL2;XCBR3 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 4 SPARE SPS 765kV B707_LR 52 CB Y PH POSITION Closed OE_CL_Y-PH_POS CONTROL2;XCBR3 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 5 SPARE SPS 765kV B707_LR 52 CB B PH POSITION Open OE_CL_B-PH_POS CONTROL2;XCBR4 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 6 SPARE SPS 765kV B707_LR 52 CB B PH POSITION Closed OE_CL_B-PH_POS CONTROL2;XCBR4 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 7 SPE_HLA_Normal_Alarm SPS 765kV B707_LR 52 SF6 GAS PRESSURE REFILL LOW Alarm Normal NL_AL_GAS RFL LO Transmitted to IEC CONTROL2;XCBR1 ST;Ind7;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 8 SPE_HLA_Normal_Alarm SPS 765kV B707_LR 52 SF6 GAS PRESSURE REFILL LEVEL-1 LOW Alarm Normal NL_AL_GAS RFL L1 Transmitted to IEC CONTROL2;XCBR1 ST;Ind6;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 9 SPE_HLA_Unhlthy_Hlthy SPS 765kV B707_LR 52 AUTO RECLOSE CB Healthy Unhealthy UH_HL_CB Transmitted to IEC CONTROL2;XCBR1 ST;Ind4;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 10 SPE_HLa_Reset_Set SPS 765kV B707_LR 52 CB IN REMOTE MODE Set Reset RS_ST_CB REMOTE Transmitted to IEC CONTROL2;XCBR1 ST;Ind3;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 11 SPE_HLA_Dischrgd_Charged SPS 765kV B707_LR 52 CB SPRING Charged Discharged DC_CH_ SPRING Transmitted to IEC CONTROL2;XCBR1 ST;Ind1;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 12 SPE_HLA_Normal_Fail SPS 765kV B707_LR 52 AC SUPPLY R Y B Fail Normal NL_FL_AC SUPPLY Transmitted to IEC CONTROL2;XCBR1 ST;Ind12;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 13 SPE_HLA_Normal_Alarm SPS 765kV B707_LR 52 SF6 GAS SECOND STAGE LOW Alarm Normal NL_AL_SF6 L2 Transmitted to IEC CONTROL2;XCBR1 ST;Ind11;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 14 SPE_HLA_Normal_Fail SPS 765kV B707_LR 52 DC SUPPLY-1/2 Fail Normal NL_FL_DC-1/2 SUP Transmitted to IEC CONTROL2;XCBR1 ST;Ind2;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 15 SPE_HLA_Normal_Alarm SPS 765kV B707_LR 52 SF6 GAS PRESSURE LEVEL-2 LOW Alarm Normal NL_AL_SF6 L2 LOW Transmitted to IEC CONTROL2;XCBR1 ST;Ind10;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 16 SPE_HLa_Reset_Set SPS 765kV B707_LR 52 SF6 GAS SECOND STAGE NORMAL Set Reset NL_AL_SF6 2ND ST Transmitted to IEC CONTROL2;XCBR1 ST;Ind9;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 1
Digital Inputs Board Slot O
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A O 1 SPE_HLA_Normal_Alarm SPS 765kV B707_LR 52 PH. POSITION DISCORDANCE Alarm Normal NL_AL_PD Transmitted to IEC CONTROL2;XCBR1 ST;Ind8;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 2 SPE_HLA_Reset_Optd SPS 765kV B707_LR 52 SF6 LOW PRESSURE LEVEL-2 NORMAL Operated Reset NL_AL_ LO PR L2 Transmitted to IEC CONTROL2;XCBR1 ST;Ind5;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 5 DP_HLA_ ISOOpen_Close DPS 765kV B707_LR 89LR-R POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI1 ST;Pos;stVal;DPC 38;40;44;45;46; None 9 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 6 DP_HLA_ ISOOpen_Close DPS 765kV B707_LR 89LR-R POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI1 ST;Pos;stVal;DPC 38;40;44;45;46; None 9 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 7 DP_HLa_ESOpen_Close DPS 765kV B707_LR 89LRE-R POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI7 ST;Pos;stVal;DPC 11;12;13;31;32;33;56;57;58;7;8;9; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 8 DP_HLa_ESOpen_Close DPS 765kV B707_LR 89LRE-R POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI7 ST;Pos;stVal;DPC 11;12;13;31;32;33;56;57;58;7;8;9; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 9 DP_HLA_ ISOOpen_Close DPS 765kV B707_LR 89LR-Y POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI2 ST;Pos;stVal;DPC 39;40;47;48;49; None 10 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 10 DP_HLA_ ISOOpen_Close DPS 765kV B707_LR 89LR-Y POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI2 ST;Pos;stVal;DPC 39;40;47;48;49; None 10 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 11 DP_HLa_ESOpen_Close DPS 765kV B707_LR 89LRE-Y POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI9 ST;Pos;stVal;DPC 11;12;13;34;35;36;56;57;58;7;8;9; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 12 DP_HLa_ESOpen_Close DPS 765kV B707_LR 89LRE-Y POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI9 ST;Pos;stVal;DPC 11;12;13;34;35;36;56;57;58;7;8;9; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 13 DP_HLA_ ISOOpen_Close DPS 765kV B707_LR 89LR-B POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI3 ST;Pos;stVal;DPC 37;40;41;42;43; None 8 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 14 DP_HLA_ ISOOpen_Close DPS 765kV B707_LR 89LR-B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI3 ST;Pos;stVal;DPC 37;40;41;42;43; None 8 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 15 DP_HLa_ESOpen_Close DPS 765kV B707_LR 89LRE-B POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI10 ST;Pos;stVal;DPC 11;12;13;28;29;30;56;57;58;7;8;9; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 16 DP_HLa_ESOpen_Close DPS 765kV B707_LR 89LRE-B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI10 ST;Pos;stVal;DPC 11;12;13;28;29;30;56;57;58;7;8;9; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 2
Digital Inputs Board Slot N
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A N 1 DP_HLA_ ISOOpen_Close DPS 765kV B707_LR 89RS-1R & 2R POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI4 ST;Pos;stVal;DPC 156;158;159;160;161;162;163;164;165;166;31;32;33;40;41;42;43;47;48;49;52; None 12 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 2 DP_HLA_ ISOOpen_Close DPS 765kV B707_LR 89RS-1R & 2R POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI4 ST;Pos;stVal;DPC 156;158;159;160;161;162;163;164;165;166;31;32;33;40;41;42;43;47;48;49;52; None 12 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 5 DP_HLA_ ISOOpen_Close DPS 765kV B707_LR 89RS-1Y & 2Y POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI5 ST;Pos;stVal;DPC 156;158;159;160;161;162;163;164;165;166;34;35;36;40;41;42;43;44;45;46;52; None 13 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 6 DP_HLA_ ISOOpen_Close DPS 765kV B707_LR 89RS-1Y & 2Y POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI5 ST;Pos;stVal;DPC 156;158;159;160;161;162;163;164;165;166;34;35;36;40;41;42;43;44;45;46;52; None 13 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 9 DP_HLA_ ISOOpen_Close DPS 765kV B707_LR 89RS-1B & 2B POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI6 ST;Pos;stVal;DPC 156;158;159;160;161;162;163;164;165;166;28;29;30;40;44;45;46;47;48;49;52; None 11 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 10 DP_HLA_ ISOOpen_Close DPS 765kV B707_LR 89RS-1B & 2B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI6 ST;Pos;stVal;DPC 156;158;159;160;161;162;163;164;165;166;28;29;30;40;44;45;46;47;48;49;52; None 11 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 15 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB NGR OTI Alarm Normal NL_AL_NGR OTI Transmitted to IEC CONTROL1;GGIO6 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 16 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB NGR BUCHHOLZ Alarm Normal NL_AL_NGR BUCH Transmitted to IEC CONTROL1;GGIO6 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 3
Digital Inputs Board Slot M
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A M 1 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB OIL LAVEL HIGH R PH Alarm Normal NL_AL_OLH- R PH Transmitted to IEC CONTROL1;GGIO6 ST;Ind15;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 2 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB OIL LAVEL LOW R PH Alarm Normal NL_AL_OLL- R PH Transmitted to IEC CONTROL1;GGIO6 ST;Ind14;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 3 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB SHUT OFF VALVE R PH Alarm Normal NL_AL_SHUT VLV R Transmitted to IEC CONTROL1;GGIO6 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 4 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB OIL LAVEL HIGH Y PH Alarm Normal NL_AL_OLH- Y PH Transmitted to IEC CONTROL1;GGIO6 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 5 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB OIL LAVEL LOW Y PH Alarm Normal NL_AL_OLL-Y PH Transmitted to IEC CONTROL1;GGIO6 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 6 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB SHUT OFF VALVE Y PH Alarm Normal NL_AL_SHUT VLV Y Transmitted to IEC CONTROL1;GGIO6 ST;Ind9;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 7 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB OIL LAVEL HIGH B PH Alarm Normal NL_AL_OLH- B PH Transmitted to IEC CONTROL1;GGIO6 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 8 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB OIL LAVEL LOW B PH Alarm Normal NL_AL_OLL- B PH Transmitted to IEC CONTROL1;GGIO6 ST;Ind7;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 9 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB SHUT OFF VALVE B PH Alarm Normal NL_AL_SHUT VLV B Transmitted to IEC CONTROL1;GGIO6 ST;Ind10;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 10 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB BUCH 1&2 SP PH Alarm Normal NL_AL_BUCH12 SP Transmitted to IEC CONTROL1;GGIO6 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 11 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB WTI SP-PHASE Alarm Normal NL_AL_WTI SP Transmitted to IEC CONTROL1;GGIO6 ST;Ind11;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 12 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB 0TI SP-PHASE Alarm Normal NL_AL_OTI SP Transmitted to IEC CONTROL1;GGIO6 ST;Ind12;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 13 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB OIL LEVEL HIGH SP-PHASE Alarm Normal NL_AL_OLH SP Transmitted to IEC CONTROL1;GGIO6 ST;Ind13;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 4
Digital Inputs Board Slot L
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A L 1 SPE_HLa_Dselect_Select SPS 765kV B707_LR LR_SELECTION LR-1 CB R-PHASE Selected Deselected DE_SEL_LR1_R-PH Transmitted to IEC CONTROL1;GGIO4 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 2 SPE_HLa_Dselect_Select SPS 765kV B707_LR LR_SELECTION LR-1 CB Y-PHASE Selected Deselected DE_SEL_LR1_Y-PH Transmitted to IEC CONTROL1;GGIO4 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 3 SPE_HLa_Dselect_Select SPS 765kV B707_LR LR_SELECTION LR-1 CB B-PHASE Selected Deselected DE_SEL_LR1_B-PH Transmitted to IEC CONTROL1;GGIO4 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 4 SPE_HLa_Dselect_Select SPS 765kV B707_LR LR_SELECTION LR-1 CB SP-PHASE Selected Deselected DE_SEL_LR1_SP-PH Transmitted to IEC CONTROL1;GGIO4 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 5 SPE_HLA_Healthy_Flty SPS 765kV B707_LR PROTECTION CB TC-1 Faulty Healthy HL_FT_CB TC-1 Transmitted to IEC CONTROL1;GGIO3 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 6 SPE_HLA_Healthy_Flty SPS 765kV B707_LR PROTECTION CB TC-2 Faulty Healthy HL_FT_CB TC-2 Transmitted to IEC CONTROL1;GGIO3 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 7 SPE_HLA_Rdy_Notrdy SPS 765kV B707_LR PSD CONTROL SWITCHING DEVICE Not Ready Ready RD_NR_DEVICE Transmitted to IEC CONTROL2;GGIO1 ST;Ind1;stVal;SPS 54; None 1 DIGITAL INPUT BOARD DIU2xx
A L 8 SPE_HLA_Normal_Alarm SPS 765kV B707_LR PROTECTION CSD Alarm Normal NL_AL_CSD Transmitted to IEC CONTROL1;GGIO3 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 9 SPS_HLA_Nok_OK SPS 765kV B707_LR PSD CSD DEVICE OK Not OK NOK_OK_CSD Transmitted to IEC CONTROL2;GGIO1 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 10 SPE_HLA_Normal_Fail SPS 765kV B707_LR PROTECTION SPARE REACTOR DC Fail Normal NL_FL_SPARE DC Transmitted to IEC CONTROL1;GGIO3 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 11 SPE_HLA_Unhlthy_Hlthy SPS 765kV B707_LR PROTECTION 64R RELAY Healthy Unhealthy UH_HL_64R Transmitted to IEC CONTROL1;GGIO3 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 13 DP_HLA_Trip_Closed DPS 765kV B707_LR 52 EMERGENCY/MANUAL Closed TP_CL_EMRG/MAN Transmitted to IEC CONTROL2;XCBR1 ST;DPCSO1;stVal;DPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A L 14 DP_HLA_Trip_Closed DPS 765kV B707_LR 52 EMERGENCY/MANUAL Trip TP_CL_EMRG/MAN Transmitted to IEC CONTROL2;XCBR1 ST;DPCSO1;stVal;DPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A L 15 SPE_HLa_Reset_DSelect SPS 765kV B707_LR PROTECTION LR Deselected Reset SL_DS_LR#1 Transmitted to IEC CONTROL1;GGIO3 ST;Ind10;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 16 SPE_HLa_Reset_DSelect SPS 765kV B707_LR PROTECTION LR-R/Y/B Deselected Reset SL_DS_LR-RYB Transmitted to IEC CONTROL1;GGIO3 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 5
Digital Inputs Board Slot K
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A K 1 DP_HLA_CBOpen_Close DPS 765kV B707_LR 52-SP PHASE POSITION Open OE_CL_POSITION Transmitted to IEC CONTROL1;GGIO2 ST;DPCSO1;stVal;DPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 2 DP_HLA_CBOpen_Close DPS 765kV B707_LR 52-SP PHASE POSITION Closed OE_CL_POSITION Transmitted to IEC CONTROL1;GGIO2 ST;DPCSO1;stVal;DPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 3 SPE_HLa_Reset_Set SPS 765kV B707_LR 52-SP PHASE LA SP R PH OPEN Set Reset LA SP R PH OPEN Transmitted to IEC CONTROL1;GGIO2 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 4 SPE_HLa_Reset_Set SPS 765kV B707_LR 52-SP PHASE LA SP PH OPEN Set Reset LA SP Y PH OPEN Transmitted to IEC CONTROL1;GGIO2 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 5 SPE_HLa_Reset_Set SPS 765kV B707_LR 52-SP PHASE LA SP B PH OPEN Set Reset LA SP B PH OPEN Transmitted to IEC CONTROL1;GGIO2 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 14 SPE_HLA_Unhlthy_Hlthy SPS 765kV B707_LR PROTECTION 50BF RELAY Healthy Unhealthy UH_HL_50BF Transmitted to IEC CONTROL1;GGIO3 ST;Ind7;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 15 SPE_HLA_Unhlthy_Hlthy SPS 765kV B707_LR PROTECTION 21R RELAY Healthy Unhealthy UH_HL_21R Transmitted to IEC CONTROL1;GGIO3 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 16 SPE_HLA_Unhlthy_Hlthy SPS 765kV B707_LR PROTECTION 87R RELAY Healthy Unhealthy UH_HL_87R Transmitted to IEC CONTROL1;GGIO3 ST;Ind9;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 0
Digital Outputs Board Slot E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A E 1 DC_SBO_Open_Close DPC 765kV B707_LR 52 CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI7 CO;Pos;sboClass;DPC 7 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 2 DC_SBO_Open_Close DPC 765kV B707_LR 52 CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI7 CO;Pos;sboClass;DPC 7 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 3 SC_DE_Reset_Reset_2 SPC 765kV B707_LR INTERLOCK_PERM XX_TRPRLY 86RA RESET XX_TRPRLY 86RA Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO15;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 4 SC_DE_Reset_Reset_2 SPC 765kV B707_LR INTERLOCK_PERM XX_TRPRLY 86RB RESET XX_TRPRLY 86RB Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO16;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 5 SC_DE_Reset_Set_2 SPC 765kV B707_LR BUS SELECTION 765KV BUS-2 VT Set BUS-2_VT_SELECT Transmitted to IEC CONTROL1;GGIO5 CO;SPCSO4;ctlVal;DPC 50<; 158 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 6 SC_DE_Reset_Set_2 SPC 765kV B707_LR BUS SELECTION 765KV BUS-2 VT Set BUS-2_VT_DE-SEL Transmitted to IEC CONTROL1;GGIO5 CO;SPCSO3;ctlVal;DPC 50<; 157 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 7 SC_DE_Reset_Set_2 SPC 765kV B707_LR BUS SELECTION 765KV BUS-1 VT Set BUS-1_VT_SELECT Transmitted to IEC CONTROL1;GGIO5 CO;SPCSO2;ctlVal;DPC 50<; 156 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 8 SC_DE_Reset_Set_2 SPC 765kV B707_LR BUS SELECTION 765KV BUS-1 VT Set BUS-1_VT_DE-SEL Transmitted to IEC CONTROL1;GGIO5 CO;SPCSO1;ctlVal;DPC 50<; 155 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 9 SC_DE_Reset_Set_2 SPC 765kV B707_LR BUS SELECTION 765KV LINE VT SEL Set LINE_VT_SEL Transmitted to IEC CONTROL1;GGIO5 CO;SPCSO6;ctlVal;DPC 160 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A E 10 SC_DE_Reset_Set_2 SPC 765kV B707_LR BUS SELECTION 765KV LINE DESELECT Set LINE_VT_DE-SEL Transmitted to IEC CONTROL1;GGIO5 CO;SPCSO5;ctlVal;DPC 159 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 1
Digital Outputs Board Slot F
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A F 1 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM TO LR1 SELECT RESET XX_SL_LR1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO7;ctlVal;DPC 166 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 2 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM LR1 DESELECT RESET XX_DL_LR1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO8;ctlVal;DPC 163 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 3 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM TO LR R PH SELECT RESET XX_SL_LR R PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO10;ctlVal;DPC 165 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 4 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM LR R PH DESELECT RESET XX_DL_LR R PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO9;ctlVal;DPC 164 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 5 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM TO LR Y PH SELECT RESET XX_SL_LR Y PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO12;ctlVal;DPC 168 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 6 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM LR Y PH DESELECT RESET XX_DL_LR Y PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO11;ctlVal;DPC 167 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 7 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM TO LR B PH SELECT RESET XX_SL_LR B PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO14;ctlVal;DPC 162 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 8 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM LR B PH DESELECT RESET XX_DL_LR B PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO13;ctlVal;DPC 161 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 9 SC_DE_Reset_Set_2 SPC 765kV B707_LR PSD CSD BYPASS Set XX_XX_PSD Transmitted to IEC CONTROL2;GGIO1 CO;SPCSO1;ctlVal;DPC 169 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A F 10 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM TO LR1 SP SELECT RESET XX_SL_LR1 SP Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO18;ctlVal;DPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 2
Digital Outputs Board Slot G
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A G 1 DC_SBO_Open_Close_1 DPC 765kV B707_LR 89LR-R CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 9 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 2 DC_SBO_Open_Close_1 DPC 765kV B707_LR 89LR-R CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 9 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 3 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM 89R-R IL PERM RESET XX_XX_89R-R PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO6;ctlVal;DPC 150 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 4 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM 89RE-R IL PERM RESET XX_XX_89RE-R PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO19;ctlVal;DPC 148 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 5 DC_SBO_Open_Close_1 DPC 765kV B707_LR 89LR-Y CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 10 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 6 DC_SBO_Open_Close_1 DPC 765kV B707_LR 89LR-Y CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 10 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 7 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM 89R-Y IL PERM RESET XX_XX_89R-Y PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO20;ctlVal;DPC 151 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 8 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM 89RE-Y IL PERM RESET XX_XX_89RE-Y PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO21;ctlVal;DPC 149 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A G 10 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM LR1 DESELECT SPR RESET XX_DL_LR1 SPR Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO17;ctlVal;DPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 3
Digital Outputs Board Slot H
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A H 1 DC_SBO_Open_Close_1 DPC 765kV B707_LR 89LR-B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 8 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 2 DC_SBO_Open_Close_1 DPC 765kV B707_LR 89LR-B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 8 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 3 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM 89R-B IL PERM RESET XX_XX_89R-B PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO22;ctlVal;DPC 146 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 4 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM 89RE-B IL PERM RESET XX_XX_89RE-B PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO1;ctlVal;DPC 147 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 8 DC_SBO_Open_Close_2 DPC 765kV B707_LR PSD CSD CB Close CSD CB Transmitted to IEC CONTROL2;GGIO1 CO;DPCSO1;sboClass;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 9 DC_SBO_Open_Close_2 DPC 765kV B707_LR PSD CSD CB Open CSD CB Transmitted to IEC CONTROL2;GGIO1 CO;DPCSO1;sboClass;DPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A H 10 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM 89RS-2ER IL PERM RESET XX_XX_89RS-2ER Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO5;ctlVal;DPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 4
Digital Outputs Board Slot I
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A I 1 DC_SBO_Open_Close_1 DPC 765kV B707_LR 89RS-1R & 2R CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 12 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 2 DC_SBO_Open_Close_1 DPC 765kV B707_LR 89RS-1R & 2R CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 12 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 3 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM 89RS 1R2R IL PERM RESET XX_XX_89RS-1R 2R Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO2;ctlVal;DPC 153 NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 4 DC_SBO_Open_Close_1 DPC 765kV B707_LR 89RS-1Y & 2Y CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI5 CO;Pos;sboClass;DPC 13 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 5 DC_SBO_Open_Close_1 DPC 765kV B707_LR 89RS-1Y & 2Y CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI5 CO;Pos;sboClass;DPC 13 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 6 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM 89RS 1Y2Y IL PERM RESET XX_XX_89RS-1Y 2Y Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO3;ctlVal;DPC 154 NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 7 DC_SBO_Open_Close_1 DPC 765kV B707_LR 89RS-1B & 2B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI6 CO;Pos;sboClass;DPC 11 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 8 DC_SBO_Open_Close_1 DPC 765kV B707_LR 89RS-1B & 2B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI6 CO;Pos;sboClass;DPC 11 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 9 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM 89RS 1B2B IL PERM RESET XX_XX_89RS-1B 2B Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO4;ctlVal;DPC 152 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A I 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 5
Digital Outputs Board Slot J
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A J 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A J 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
ANALOG INPUT BOARD AIU21x
Analog Input Board Number 0
Analog Input Board Slot D
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 4/20 mA MV_hla_Temp ˚ Cel 765kV B707_LR REACTOR_MB OTI TEMP MONITOR R-PH 0.0 80.0 OTI_TEMP_R-PH Transmitted to IEC CONTROL1;GGIO6 MX;AnIn2;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 2 4/20 mA MV_hla_Temp ˚ Cel 765kV B707_LR REACTOR_MB WTI TEMP MONITOR R-PH 0.0 80.0 WTI_TEMP_R-PH Transmitted to IEC CONTROL1;GGIO6 MX;AnIn1;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 3 4/20 mA MV_hla_Temp ˚ Cel 765kV B707_LR REACTOR_MB OTI TEMP MONITOR Y-PH 0.0 80.0 OTI_TEMP_Y-PH Transmitted to IEC CONTROL1;GGIO6 MX;AnIn4;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 4 4/20 mA MV_hla_Temp ˚ Cel 765kV B707_LR REACTOR_MB WTI TEMP MONITOR Y-PH 0.0 80.0 WTI_TEMP_Y-PH Transmitted to IEC CONTROL1;GGIO6 MX;AnIn3;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 5 4/20 mA MV_hla_Temp ˚ Cel 765kV B707_LR REACTOR_MB OTI TEMP MONITOR B-PH 0.0 80.0 OTI_TEMP_B-PH Transmitted to IEC CONTROL1;GGIO6 MX;AnIn6;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 6 4/20 mA MV_hla_Temp ˚ Cel 765kV B707_LR REACTOR_MB WTI TEMP MONITOR B-PH 0.0 80.0 WTI_TEMP_B-PH Transmitted to IEC CONTROL1;GGIO6 MX;AnIn5;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 7 4/20 mA MV_hla_Temp ˚ Cel 765kV B707_LR REACTOR_MB OTI TEMP MONITOR SP-PH 0.0 80.0 OTI_TEMP_SP-PH Transmitted to IEC CONTROL1;GGIO6 MX;AnIn8;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 8 4/20 mA MV_hla_Temp ˚ Cel 765kV B707_LR REACTOR_MB WTI TEMP MONITOR SP-PH 0.0 80.0 WTI_TEMP_SP-PH Transmitted to IEC CONTROL1;GGIO6 MX;AnIn7;mag;MV 6 ANALOG INPUT BOARD AIU21x
CT/VT ANALOG INPUT BOARD TMU2x0
CT/VT Board Number 0
CT/VT Board Slot Q
CT/VT Board Model TMU220
Nominal Current 1 (1A/5A)
Nominal Voltage 110.00 [1V … 500V]
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Ia MV_HLa_AuxCurrent A 765kV B707_LR METERING I-R PHASE CURRENT 0.0 360.0 IR PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ib MV_HLa_AuxCurrent A 765kV B707_LR METERING I-Y PHASE CURRENT 0.0 360.0 IY PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ic MV_HLa_Frequency_1 Hz 765kV B707_LR METERING I-B PHASE CURRENT 0.0 360.0 IB PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsC;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uab MV_HLa_Voltage kV 765kV B707_LR METERING R-Y VOLTAGE 0.0 918.0 R-Y VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsAB;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ubc MV_HLa_Voltage kV 765kV B707_LR METERING Y-B VOLTAGE 0.0 918.0 Y-B VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsBC;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uca MV_HLa_Voltage kV 765kV B707_LR METERING B-R VOLTAGE 0.0 918.0 B-R VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsCA;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Freq (Line) MV_HLa_Frequency Hz 765kV B707_LR METERING FREQUENCY 45.0 55.0 FREQUENCY Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;Hz;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A P total (MW) MV_HLa_ActPower_1 MW 765kV B707_LR METERING ACTIVE POWER -476.99 476.99 ACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotW;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Q total (Mvar) MV_HLa_ReactPower_1 MVAr 765kV B707_LR METERING REACTIVE POWER -476.99 476.99 REACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotVAr;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A cos ft : Power factor MV_HLa_PowerFactor 765kV B707_LR METERING POWER FACTOR -1.2 1.2 POWER FACTOR Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotPF;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPE_HLa_Notper_Perm SPS 765kV B707_LR 52 | OE_CL_CONTROL Close interlock result SPS Permissive Not Permissive Close intlk SPS Transmitted to IEC CONTROL2;CILO7 ST;EnaCls;stVal;SPS None CB CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPE_HLa_Reset_Set SPS 765kV B707_LR 52 | OE_CL_CONTROL CLOSE ORDER Set Reset CLOSE ORDER Transmitted to IEC CONTROL1;CSWI7 ST;ClsOrd;general;general;ACT None CB CloseOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89LR-B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO3 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89LR-R | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89LR-Y | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO2 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89RS-1B & 2B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO6 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89RS-1R & 2R | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO4 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89RS-1Y & 2Y | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO5 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89LR-B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI3 ST;IndSys1;stVal;SPS 28<; None 146 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89LRE-B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI4 ST;IndSys1;stVal;SPS 37<; None 147 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89LRE-R INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI1 ST;IndSys1;stVal;SPS 38<; None 148 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89LRE-Y INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI3 ST;IndSys1;stVal;SPS 39<; None 149 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89LR-R INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI1 ST;IndSys1;stVal;SPS 31<; None 150 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89LR-Y INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI2 ST;IndSys1;stVal;SPS 34<; None 151 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPE_HLa_Reset_Close SPS 765kV B707_LR 89R POSITION Close Reset RS_CL_POS Transmitted to IEC CONTROL2;GAPC3 ST;IndSys2;stVal;SPS 40<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPE_HLA_Reset_Open SPS 765kV B707_LR 89R POSITION Open Normal RS_OE_POS Transmitted to IEC CONTROL2;GAPC3 ST;IndSys1;stVal;SPS 40<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 17 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89RS-1B & 2B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI6 ST;IndSys1;stVal;SPS 41<; None 152 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 18 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89RS-1R & 2R INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI4 ST;IndSys1;stVal;SPS 44<; None 153 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 19 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89RS-1Y & 2Y INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI5 ST;IndSys1;stVal;SPS 47<; None 154 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 20 SPE_HLa_Reset_DSelect SPS 765kV B707_LR BUS SELECTION 765KV BUS-1 VT Deselected Reset BUS-1_VT_DE-SEL Transmitted to IEC CONTROL1;GAPC5 ST;IndSys1;stVal;SPS 50<; None 155 1 C264 SELF GENERATED DIGITAL INFORMATION
A 21 SPE_HLa_Reset_Select SPS 765kV B707_LR BUS SELECTION 765KV BUS-1 VT Selected Reset BUS-1_VT_SELECT Transmitted to IEC CONTROL1;GAPC5 ST;IndSys2;stVal;SPS 50<; None 156 1 C264 SELF GENERATED DIGITAL INFORMATION
A 22 SPE_HLa_Reset_DSelect SPS 765kV B707_LR BUS SELECTION 765KV BUS-2 VT Deselected Reset BUS-2_VT_DE-SEL Transmitted to IEC CONTROL1;GAPC5 ST;IndSys3;stVal;SPS 50<; None 157 1 C264 SELF GENERATED DIGITAL INFORMATION
A 23 SPE_HLa_Reset_Select SPS 765kV B707_LR BUS SELECTION 765KV BUS-2 VT Selected Reset BUS-2_VT_SELECT Transmitted to IEC CONTROL1;GAPC5 ST;IndSys4;stVal;SPS 50<; None 158 1 C264 SELF GENERATED DIGITAL INFORMATION
A 24 SPE_HLa_Reset_Set SPS 765kV B707_LR BUS SELECTION LINE VT DESELECT Set Reset LINE VT DESELECT Transmitted to IEC CONTROL1;GAPC5 ST;IndSys6;stVal;SPS 50<; None 159 1 C264 SELF GENERATED DIGITAL INFORMATION
A 25 SPE_HLa_Reset_Set SPS 765kV B707_LR BUS SELECTION LINE VT SELECT Set Reset LINE VT SELECT Transmitted to IEC CONTROL1;GAPC5 ST;IndSys5;stVal;SPS 50<; None 160 1 C264 SELF GENERATED DIGITAL INFORMATION
A 26 SPE_HLa_Reset_DSelect SPS 765kV B707_LR LR_SELECTION LR1_B-PH_DE-SEL Deselected Reset LR1_B-PH_DE-SEL Transmitted to IEC CONTROL1;GAPC4 ST;IndSys3;stVal;SPS 52;52<; None 161 1 C264 SELF GENERATED DIGITAL INFORMATION
A 27 SPE_HLa_Reset_Select SPS 765kV B707_LR LR_SELECTION LR1_B-PH_SEL Selected Reset LR1_B-PH_SEL Transmitted to IEC CONTROL1;GAPC4 ST;IndSys4;stVal;SPS 52;52<; None 162 1 C264 SELF GENERATED DIGITAL INFORMATION
A 28 SPE_HLa_Reset_Select SPS 765kV B707_LR LR_SELECTION LR1_DE-SELECT Selected Reset LR1_DE-SELECT Transmitted to IEC CONTROL1;GAPC4 ST;IndSys2;stVal;SPS 52<; None 163 1 C264 SELF GENERATED DIGITAL INFORMATION
A 29 SPE_HLa_Reset_DSelect SPS 765kV B707_LR LR_SELECTION LR1_R-PH_DE-SEL Deselected Reset LR1_R-PH_DE-SEL Transmitted to IEC CONTROL1;GAPC4 ST;IndSys5;stVal;SPS 52;52<; None 164 1 C264 SELF GENERATED DIGITAL INFORMATION
A 30 SPE_HLa_Reset_Select SPS 765kV B707_LR LR_SELECTION LR1_R-PH_SEL Selected Reset LR1_R-PH_SEL Transmitted to IEC CONTROL1;GAPC4 ST;IndSys6;stVal;SPS 52;52<; None 165 1 C264 SELF GENERATED DIGITAL INFORMATION
A 31 SPE_HLa_Reset_Select SPS 765kV B707_LR LR_SELECTION LR1_SELECT Selected Reset LR1_SELECT Transmitted to IEC CONTROL1;GAPC4 ST;IndSys1;stVal;SPS 52<; None 166 1 C264 SELF GENERATED DIGITAL INFORMATION
A 32 SPE_HLa_Reset_DSelect SPS 765kV B707_LR LR_SELECTION LR1_Y-PH_DE-SEL Deselected Reset LR1_Y-PH_DE-SEL Transmitted to IEC CONTROL1;GAPC4 ST;IndSys7;stVal;SPS 52;52<; None 167 1 C264 SELF GENERATED DIGITAL INFORMATION
A 33 SPE_HLa_Reset_Select SPS 765kV B707_LR LR_SELECTION LR1_Y-PH_SEL Selected Reset LR1_Y-PH_SEL Transmitted to IEC CONTROL1;GAPC4 ST;IndSys8;stVal;SPS 52;52<; None 168 1 C264 SELF GENERATED DIGITAL INFORMATION
A 34 SPE_HLA_Flty_Healthy SPS 765kV B707_LR PROTECTION Dummy SPS Healthy Faulty Dummy SPS Transmitted to IEC CONTROL1;GAPC3 ST;IndSys1;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 35 SPE_HLA_Reset_Alarm_Goose SPS 765kV B707_LR PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Reset GOOSE RECIEPT FL Transmitted to IEC CONTROL1;GAPC3 ST;IndSys4;stVal;SPS 53<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 36 SPE_HLA_Normal_Alarm SPS 765kV B707_LR PROTECTION HV WINDING TEMP HIGH SP-PH Alarm Normal NL_AL_HV WDG TMP Transmitted to IEC CONTROL1;GAPC3 ST;IndSys2;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 37 SPE_HLA_Normal_Alarm SPS 765kV B707_LR PROTECTION MAIN TANK MOG-SP PH Alarm Normal NL_AL_MOG SP PH Transmitted to IEC CONTROL1;GAPC3 ST;IndSys3;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 38 SPE_HLa_Reset_Set SPS 765kV B707_LR PSD PSD BYPASS Set Reset RS_ST_PSD BYPASS Transmitted to IEC CONTROL2;GAPC2 ST;IndSys1;stVal;SPS 54<; None 169 1 C264 SELF GENERATED DIGITAL INFORMATION
A 39 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB BUCH 1&2 B PH Alarm Normal NL_AL_BUCH12 B Transmitted to IEC CONTROL2;GAPC1 ST;IndSys4;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 40 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB BUCH 1&2 R PH Alarm Normal NL_AL_BUCH12 R Transmitted to IEC CONTROL2;GAPC1 ST;IndSys2;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 41 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB BUCH 1&2 Y PH Alarm Normal NL_AL_BUCH12 Y Transmitted to IEC CONTROL2;GAPC1 ST;IndSys3;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 42 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB HV WINDING TEMP HIGH R PH Alarm Normal NL_AL_HV WDG R Transmitted to IEC CONTROL2;GAPC1 ST;IndSys10;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 43 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB HV WINDING TEMP HIGH B PH Alarm Normal NL_AL_HV WDG B Transmitted to IEC CONTROL2;GAPC1 ST;IndSys5;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 44 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB HV WINDING TEMP HIGH Y PH Alarm Normal NL_AL_HV WDG Y Transmitted to IEC CONTROL2;GAPC1 ST;IndSys8;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 45 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB MAIN TANK LOW OIL LEVEL-B PH Alarm Normal NL_AL_MOG B PH Transmitted to IEC CONTROL2;GAPC1 ST;IndSys6;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 46 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB MAIN TANK LOW OIL LEVEL-R PH Alarm Normal NL_AL_MOG R PH Transmitted to IEC CONTROL2;GAPC1 ST;IndSys1;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 47 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB MAIN TANK LOW OIL LEVEL-Y PH Alarm Normal NL_AL_MOG Y PH Transmitted to IEC CONTROL2;GAPC1 ST;IndSys9;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 48 SPE_HLA_Normal_Alarm SPS 765kV B707_LR REACTOR_MB OTI Alarm Normal NL_AL_OTI Transmitted to IEC CONTROL2;GAPC1 ST;IndSys7;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 49 SPE_HLa_Reset_Set SPS 765kV B707_LR 52 | OE_CL_CONTROL OPEN ORDER Set Reset OPEN ORDER Transmitted to IEC CONTROL1;CSWI7 ST;OpnOrd;general;general;ACT None CB OpenOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 50 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89LR-B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO3 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 51 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89LR-R | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 52 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89LR-Y | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO2 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 53 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89RS-1B & 2B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO6 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 54 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89RS-1R & 2R | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO4 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 55 SPE_HLa_Notper_Perm SPS 765kV B707_LR 89RS-1Y & 2Y | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO5 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 56 SPS_hla_Set_Reset SPS 765kV B707_LR Order running on the bay Set Reset Order running Transmitted to IEC CONTROL3;GBAY1 ST;OrdRun;stVal;SPS None OrderInProgress 1 C264 SELF GENERATED DIGITAL INFORMATION
A 57 DP_HLA_CBOpen_Close DPS 765kV B707_LR 52 COMPUTED SWITCH POSITION Open OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI7 ST;Pos;origin;DPC 28;29;30;31;32;33;34;35;36;41;42;43;44;45;46;47;48;49; None 7 51 CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 58 DP_HLA_CBOpen_Close DPS 765kV B707_LR 52 COMPUTED SWITCH POSITION Closed OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI7 ST;Pos;origin;DPC 28;29;30;31;32;33;34;35;36;41;42;43;44;45;46;47;48;49; None 7 51 CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 59 DP_HLA_ ISOOpen_Close DPS 765kV B707_LR 89R POSITION Open OE_CL_POS Transmitted to IEC CONTROL2;GAPC3 ST;DPCSO1;stVal;DPS 11;12;13;59; None Yes 1 C264 SELF GENERATED DIGITAL INFORMATION
A 60 DP_HLA_ ISOOpen_Close DPS 765kV B707_LR 89R POSITION Closed OE_CL_POS Transmitted to IEC CONTROL2;GAPC3 ST;DPCSO1;stVal;DPS 11;12;13;59; None Yes 1 C264 SELF GENERATED DIGITAL INFORMATION
A 61 DP_HLa_LocRem_Bay DPS 765kV B707_LR BCU MODE Local LC_RM_MODE Transmitted to IEC CONTROL3;GBAY1 ST;Loc;origin;DPC None 14 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 62 DP_HLa_LocRem_Bay DPS 765kV B707_LR BCU MODE Remote LC_RM_MODE Transmitted to IEC CONTROL3;GBAY1 ST;Loc;origin;DPC None 14 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 63 DP_HLA_CBOpen_Close DPS 765kV B707_LR RTCC_PANNEL OLTC Open OLTC Transmitted to IEC CONTROL1;GAPC1 ST;DPCSO1;origin;DPC None 15 1 C264 SELF GENERATED DIGITAL INFORMATION
A 64 DP_HLA_CBOpen_Close DPS 765kV B707_LR RTCC_PANNEL OLTC Closed OLTC Transmitted to IEC CONTROL1;GAPC1 ST;DPCSO1;origin;DPC None 15 1 C264 SELF GENERATED DIGITAL INFORMATION
A 65 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM TO TRP COIL RESET XX_XX_TRP COIL Transmitted to IEC CONTROL1;GAPC2 CO;SPCSO1;ctlVal;DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SC_DE_NotPerm_Perm_1 SPC 765kV B707_LR INTERLOCK_PERM TO TRP COIL RESET XX_XX_TRP COIL 2 Transmitted to IEC CONTROL1;GAPC2 CO;SPCSO2;ctlVal;DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SC_DE_Reset_Set_2 SPC 765kV B707_LR PROTECTION CB COMMAND Set XX_TP_CB Transmitted to IEC CONTROL1;GAPC3 CO;SPCSO1;ctlVal;DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SC_DE_Set SPC 765kV B707_LR PSD PSD OUT FROM HMI Set XX_ST_PSD OUT H Transmitted to IEC CONTROL2;GAPC2 CO;SPCSO1;ctlVal;DPC 54; 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 DC_DE_LocRem_BayCtrl DPC 765kV B707_LR MODE CONTROL Local MODE CONTROL Transmitted to IEC CONTROL2;GBAY1 CO;Loc;ctlVal;DPC 14 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 DC_DE_LocRem_BayCtrl DPC 765kV B707_LR MODE CONTROL Remote MODE CONTROL Transmitted to IEC CONTROL2;GBAY1 CO;Loc;ctlVal;DPC 14 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 DC_SBO_Open_Close_2 DPC 765kV B707_LR RTCC_PANNEL OLTC Open LO_RS_OLTC Transmitted to IEC CONTROL1;GAPC1 CO;DPCSO1;sboClass;DPC 15 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 DC_SBO_Open_Close_2 DPC 765kV B707_LR RTCC_PANNEL OLTC Close LO_RS_OLTC Transmitted to IEC CONTROL1;GAPC1 CO;DPCSO1;sboClass;DPC 15 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 MV 765kV B707_LR CB_COUNTER Count_Close 0.0 10000.0 Count_Close Transmitted to IEC CONTROL2;GAPC4 MX;AnIn2;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 MV 765kV B707_LR CB_COUNTER Count_Open 0.0 10000.0 Count_Open Transmitted to IEC CONTROL2;GAPC4 MX;AnIn1;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
MiCOM C264 DESCRIPTION
Computer Name B708_TIE GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) C264 Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 0
Digital Inputs Board Slot P
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A P 1 SPARE SPS 765kV B708_TIE 52 CB R PH POSITION Open OE_CL_R-PH_POS CONTROL2;XCBR2 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 2 SPARE SPS 765kV B708_TIE 52 CB R PH POSITION Closed OE_CL_R-PH_POS CONTROL2;XCBR2 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 3 SPARE SPS 765kV B708_TIE 52 CB Y PH POSITION Open OE_CL_Y-PH_POS CONTROL2;XCBR3 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 4 SPARE SPS 765kV B708_TIE 52 CB Y PH POSITION Closed OE_CL_Y-PH_POS CONTROL2;XCBR3 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 5 SPARE SPS 765kV B708_TIE 52 CB B PH POSITION Open OE_CL_B-PH_POS CONTROL2;XCBR4 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 6 SPARE SPS 765kV B708_TIE 52 CB B PH POSITION Closed OE_CL_B-PH_POS CONTROL2;XCBR4 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 7 SPE_HLA_Normal_Alarm SPS 765kV B708_TIE 52 SF6 GAS PRESSURE REFILL LOW Alarm Normal NL_AL_GAS RFL LO Transmitted to IEC CONTROL2;XCBR1 ST;Ind6;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 8 SPE_HLA_Normal_Alarm SPS 765kV B708_TIE 52 SF6 GAS PRESSURE REFILL LEVEL-1 LOW Alarm Normal NL_AL_GAS RFL L1 Transmitted to IEC CONTROL2;XCBR1 ST;Ind5;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 9 SPE_HLA_Unhlthy_Hlthy SPS 765kV B708_TIE CB HEALTHY CB Healthy Unhealthy UH_HL_CB Transmitted to IEC CONTROL1;GGIO4 ST;Ind1;stVal;SPS 67; None 68 1 DIGITAL INPUT BOARD DIU2xx
A P 10 SPE_HLa_Reset_Set SPS 765kV B708_TIE 52 CB IN REMOTE MODE Set Reset RS_ST_CB REMOTE Transmitted to IEC CONTROL2;XCBR1 ST;Ind3;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 11 SPE_HLA_Dischrgd_Charged SPS 765kV B708_TIE 52 CB SPRING Charged Discharged DC_CH_ SPRING Transmitted to IEC CONTROL2;XCBR1 ST;Ind1;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 12 SPE_HLA_Normal_Fail SPS 765kV B708_TIE 52 AC SUPPLY R Y B Fail Normal NL_FL_AC SUPPLY Transmitted to IEC CONTROL2;XCBR1 ST;Ind11;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 13 SPE_HLA_Normal_Alarm SPS 765kV B708_TIE 52 SF6 GAS SECOND STAGE LOW Alarm Normal NL_AL_SF6 L2 Transmitted to IEC CONTROL2;XCBR1 ST;Ind9;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 14 SPE_HLA_Normal_Fail SPS 765kV B708_TIE 52 DC SUPPLY-1/2 Fail Normal NL_FL_DC-1/2 SUP Transmitted to IEC CONTROL2;XCBR1 ST;Ind2;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 15 SPE_HLA_Normal_Alarm SPS 765kV B708_TIE 52 SF6 GAS PRESSURE LEVEL-2 LOW Alarm Normal NL_AL_SF6 L2 LOW Transmitted to IEC CONTROL2;XCBR1 ST;Ind10;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 16 SPE_HLa_Reset_Set SPS 765kV B708_TIE 52 SF6 GAS SECOND STAGE NORMAL Set Reset NL_AL_SF6 2ND ST Transmitted to IEC CONTROL2;XCBR1 ST;Ind8;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 1
Digital Inputs Board Slot O
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A O 1 SPE_HLA_Normal_Alarm SPS 765kV B708_TIE 52 PH. POSITION DISCORDANCE Alarm Normal NL_AL_PD Transmitted to IEC CONTROL2;XCBR1 ST;Ind7;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 2 SPE_HLA_Reset_Optd SPS 765kV B708_TIE 52 SF6 LOW PRESSURE LEVEL-2 NORMAL Operated Reset NL_AL_ LO PR L2 Transmitted to IEC CONTROL2;XCBR1 ST;Ind4;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 5 DP_HLA_ ISOOpen_Close DPS 765kV B708_TIE 89A POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 59;60;64; None 17 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 6 DP_HLA_ ISOOpen_Close DPS 765kV B708_TIE 89A POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 59;60;64; None 17 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 7 DP_HLa_ESOpen_Close DPS 765kV B708_TIE 89AE1 POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI1 ST;Pos;stVal;DPC 11;12;13;28;29;30;31;32;33;34;35;36;56;57;58;7;8;9; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 8 DP_HLa_ESOpen_Close DPS 765kV B708_TIE 89AE1 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI1 ST;Pos;stVal;DPC 11;12;13;28;29;30;31;32;33;34;35;36;56;57;58;7;8;9; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 9 DP_HLa_ESOpen_Close DPS 765kV B708_TIE 89AE2 POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI2 ST;Pos;stVal;DPC 56;57;58;61;62;63; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 10 DP_HLa_ESOpen_Close DPS 765kV B708_TIE 89AE2 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI2 ST;Pos;stVal;DPC 56;57;58;61;62;63; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 11 DP_HLA_ ISOOpen_Close DPS 765kV B708_TIE 89B POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 60;64;65; None 18 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 12 DP_HLA_ ISOOpen_Close DPS 765kV B708_TIE 89B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 60;64;65; None 18 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 13 DP_HLa_ESOpen_Close DPS 765kV B708_TIE 89BE1 POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI3 ST;Pos;stVal;DPC 56;57;58;61;62;63; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 14 DP_HLa_ESOpen_Close DPS 765kV B708_TIE 89BE1 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI3 ST;Pos;stVal;DPC 56;57;58;61;62;63; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 15 DP_HLa_ESOpen_Close DPS 765kV B708_TIE 89BE2 POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI4 ST;Pos;stVal;DPC 100;101;102;103;104;105;106;107;61;62;63;77;78;79;87;88;89;90;91;92;93;94;95;99; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 16 DP_HLa_ESOpen_Close DPS 765kV B708_TIE 89BE2 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI4 ST;Pos;stVal;DPC 100;101;102;103;104;105;106;107;61;62;63;77;78;79;87;88;89;90;91;92;93;94;95;99; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 2
Digital Inputs Board Slot N
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A N 1 SPE_HLA_Normal_Fail SPS 765kV B708_TIE PROTECTION 220V DC SOURCE-1 Fail Normal NL_FL_DC SUP1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 2 SPE_HLA_Normal_Fail SPS 765kV B708_TIE PROTECTION 220V DC SOURCE-2 Fail Normal NL_FL_DC SUP2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 3 SPE_HLA_Healthy_Flty SPS 765kV B708_TIE PROTECTION CB TC-1 Faulty Healthy HL_FT_CB TC1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 4 SPE_HLA_Healthy_Flty SPS 765kV B708_TIE PROTECTION CB TC-2 Faulty Healthy HL_FT_CB TC2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 5 SPE_HLA_Reset_Optd SPS 765kV B708_TIE PROTECTION A/R LOCKOUT Operated Reset RS_OP_A/R LO Transmitted to IEC CONTROL1;GGIO1 ST;Ind7;stVal;SPS 55; None 1 DIGITAL INPUT BOARD DIU2xx
A N 6 SPE_HLA_Reset_Optd SPS 765kV B708_TIE AR FUNCTION-TIE R-PHASE INITIATION Operated Reset RS_OP_PHR INI Transmitted to IEC CONTROL2;GGIO1 ST;Ind2;stVal;SPS 67; None 68 1 DIGITAL INPUT BOARD DIU2xx
A N 7 SPE_HLA_Reset_Optd SPS 765kV B708_TIE AR FUNCTION-TIE Y-PHASE INITIATION Operated Reset RS_OP_PHY INI Transmitted to IEC CONTROL2;GGIO1 ST;Ind3;stVal;SPS 67; None 68 1 DIGITAL INPUT BOARD DIU2xx
A N 8 SPE_HLA_Reset_Optd SPS 765kV B708_TIE AR FUNCTION-TIE B-PHASE INITIATION Operated Reset RS_OP_PHB INI Transmitted to IEC CONTROL2;GGIO1 ST;Ind4;stVal;SPS 67; None 68 1 DIGITAL INPUT BOARD DIU2xx
A N 9 SPE_HLa_Reset_Set SPS 765kV B708_TIE AR DATA PRIORITY CIRCUIT HOLD Set Reset RS_ST_PRI HLD ON Transmitted to IEC CONTROL1;GGIO2 ST;Ind1;stVal;SPS None 68 1 DIGITAL INPUT BOARD DIU2xx
A N 10 SPE_HLA_Reset_Optd SPS 765kV B708_TIE AR FUNCTION-TIE BLOCK Operated Reset RS_OP_AR BLOCK Transmitted to IEC CONTROL2;GGIO1 ST;Ind1;stVal;SPS 55; None 68 1 DIGITAL INPUT BOARD DIU2xx
A N 11 SPE_HLA_Unhlthy_Hlthy SPS 765kV B708_TIE PROTECTION LBB RELAY Healthy Unhealthy UH_HL_LBB RLY Transmitted to IEC CONTROL1;GGIO1 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 12 SPE_HLA_Rdy_Notrdy SPS 765kV B708_TIE PSD CSD DEVICE Not Ready Ready RD_NR_CSD Transmitted to IEC CONTROL1;GGIO6 ST;Ind1;stVal;SPS 73; None 1 DIGITAL INPUT BOARD DIU2xx
A N 13 SPE_HLA_Normal_Alarm SPS 765kV B708_TIE PROTECTION CSD Alarm Normal NL_AL_CSD Transmitted to IEC CONTROL1;GGIO1 ST;Ind9;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 15 SPE_HLA_In_Out SPS 765kV B708_TIE PROTECTION CSD Out In IN_OT_CSD Transmitted to IEC CONTROL1;GGIO1 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 16 SPS_HLA_Nok_OK SPS 765kV B708_TIE PROTECTION CSD DEVICE OK Not OK NO_OK CSD Transmitted to IEC CONTROL1;GGIO1 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 1
Digital Outputs Board Slot E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A E 1 DC_SBO_Open_Close DPC 765kV B708_TIE 52 52 CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 16 68 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 2 DC_SBO_Open_Close DPC 765kV B708_TIE 52 52 CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 16 68 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 7 SC_DE_Reset_Set_2 SPC 765kV B708_TIE PSD PSD BYPASS Set XX_XX_PSD Transmitted to IEC CONTROL1;GGIO6 CO;SPCSO1;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 8 SC_DE_Reset_Reset SPC 765kV B708_TIE AR DATA TO A/R CLSG. CKT RESET XX_XX_A/R CLSG C Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO4;ctlVal;DPC 187 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 9 SC_DE_Set_1 SPC 765kV B708_TIE DT SEND D/T SEND CH-1 LINE-1 Set XX_XX_DT SD CH1 Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO1;ctlVal;DPC 193 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A E 10 SC_DE_Set_1 SPC 765kV B708_TIE DT SEND D/T SEND CH-2 LINE-1 Set XX_XX_DT SD CH2 Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO2;ctlVal;DPC 194 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 2
Digital Outputs Board Slot F
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A F 1 SC_DE_NotPerm_Perm_1 SPC 765kV B708_TIE INTERLOCK_PERM 89AE1 IL PERM RESET XX_XX_89AE1 Transmitted to IEC CONTROL1;GGIO5 CO;SPCSO3;ctlVal;DPC 181 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 2 SC_DE_NotPerm_Perm_1 SPC 765kV B708_TIE INTERLOCK_PERM 89BE2 IL PERM RESET XX_XX_89BE2 Transmitted to IEC CONTROL1;GGIO5 CO;SPCSO4;ctlVal;DPC 185 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 3 DC_SBO_Open_Close_1 DPC 765kV B708_TIE 89A CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 17 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 4 DC_SBO_Open_Close_1 DPC 765kV B708_TIE 89A CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 17 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 5 SC_DE_NotPerm_Perm_1 SPC 765kV B708_TIE INTERLOCK_PERM 89A IL PERM RESET XX_XX_89A Transmitted to IEC CONTROL1;GGIO5 CO;SPCSO5;ctlVal;DPC 180 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 6 SC_DE_NotPerm_Perm_1 SPC 765kV B708_TIE INTERLOCK_PERM 89AE2 IL PERM RESET XX_XX_89AE2 Transmitted to IEC CONTROL1;GGIO5 CO;SPCSO1;ctlVal;DPC 182 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 7 DC_SBO_Open_Close_1 DPC 765kV B708_TIE 89B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 18 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 8 DC_SBO_Open_Close_1 DPC 765kV B708_TIE 89B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 18 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 9 SC_DE_NotPerm_Perm_1 SPC 765kV B708_TIE INTERLOCK_PERM 89B IL PERM RESET XX_XX_89B Transmitted to IEC CONTROL1;GGIO5 CO;SPCSO6;ctlVal;DPC 183 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A F 10 SC_DE_NotPerm_Perm_1 SPC 765kV B708_TIE INTERLOCK_PERM 89BE1 IL PERM RESET XX_XX_89BE1 Transmitted to IEC CONTROL1;GGIO5 CO;SPCSO2;ctlVal;DPC 184 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 3
Digital Outputs Board Slot G
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A G 1 SC_DE_Reset_Reset_1 SPC 765kV B708_TIE PROTECTION 186 RELAY RESET RESET XX_XX_186 LO Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO3;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 2 SC_DE_Reset_Set_3 SPC 765kV B708_TIE AR DATA LOCKOUT TRIP Set XX_XX_AR LO TRIP Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO2;ctlVal;DPC 186 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 3 SC_DE_Off_On SPC 765kV B708_TIE AR DATA A/R OFF On Off XX_XX_A/R_OFF Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO1;ctlVal;DPC 2 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 4 SC_DE_NotPerm_Perm_1 SPC 765kV B708_TIE AR DATA TO DR RESET XX_XX_TO DR Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO3;ctlVal;DPC 188 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 5 SC_DE_Reset_Reset_2 SPC 765kV B708_TIE CVT SELECTION 400KV SELECT AT LV VOLTAGE RESET XX_SL_400VT Transmitted to IEC CONTROL1;GGIO7 CO;SPCSO3;ctlVal;DPC 190 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 6 SC_DE_Reset_Set_3 SPC 765kV B708_TIE CVT SELECTION 400KV SELECT AT LV VOLTAGE Set XX_DL_400VT Transmitted to IEC CONTROL1;GGIO7 CO;SPCSO4;ctlVal;DPC 189 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 7 SC_DE_Reset_Reset_2 SPC 765kV B708_TIE CVT SELECTION SELECTION OF BUS-2 VT RESET XX_SL_BUS-2 VT Transmitted to IEC CONTROL1;GGIO7 CO;SPCSO2;ctlVal;DPC 191 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 8 SC_DE_Reset_Set_3 SPC 765kV B708_TIE CVT SELECTION SELECTION OF BUS-2 VT Set XX_DL_BUS-2 VT Transmitted to IEC CONTROL1;GGIO7 CO;SPCSO1;ctlVal;DPC 192 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 9 SC_DE_NotPerm_Perm_2 SPC 765kV B708_TIE PROTECTION CB CLS COMMAND TO FUTURE BAY (BB-1) RESET XX_XX_CB CL1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO1;ctlVal;DPC 11 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A G 10 SC_DE_NotPerm_Perm_2 SPC 765kV B708_TIE PROTECTION CB CLS COMMAND TO FUTURE BAY (BB-2) RESET XX_XX_CB CL2 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO2;ctlVal;DPC 12 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
CT/VT ANALOG INPUT BOARD TMU2x0
CT/VT Board Number 0
CT/VT Board Slot Q
CT/VT Board Model TMU220
Nominal Current 1 (1A/5A)
Nominal Voltage 110.00 [1V … 500V]
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A DF MV_HLa_Frequency_2 Hz 765kV B708_TIE SYNCH DATA FREQUENCY DIFFERENCE 0.0 2.0 FREQUENCY DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifHzClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DV MV_HLa_Voltage_1 kV 765kV B708_TIE SYNCH DATA VOLTAGE DIFFERENCE 0.0 530.0 VOLTAGE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifVClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Dj MV_hla_PhaseDiff ˚ 765kV B708_TIE SYNCH DATA PHASE DIFFERENCE 0.0 360.0 PHASE ANGLE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifAngClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ia MV_HLa_AuxCurrent A 765kV B708_TIE METERING I-R PHASE CURRENT 0.0 2400.0 IR PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;A;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ib MV_HLa_AuxCurrent A 765kV B708_TIE METERING I-Y PHASE CURRENT 0.0 2400.0 IY PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;A;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ic MV_HLa_Frequency_1 Hz 765kV B708_TIE METERING I-B PHASE CURRENT 0.0 2400.0 IB PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;A;phsC;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vb MV_HLa_Voltage_1 kV 765kV B708_TIE SYNCH DATA INCOMING SUPPLY 0.0 530.0 INCOMING SUPPLY Transmitted to IEC MEASUREMENT1;rmsMMXU3 MX;PhV;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar MV_HLa_Voltage_1 kV 765kV B708_TIE SYNCH DATA RUNNING SUPPLY-1 0.0 530.0 RUNNING SPLY-1 Transmitted to IEC MEASUREMENT1;barMMXU1 MX;PhV;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Freq (Line) MV_HLa_Frequency Hz 765kV B708_TIE METERING FREQUENCY 45.0 55.0 FREQUENCY Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;Hz;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar RMS 2 value of the busbar voltage phase MV_HLa_Voltage_1 kV 765kV B708_TIE SYNCH DATA RUNNING SUPPLY-2 0.0 530.0 RUNNING SPLY-2 Transmitted to IEC MEASUREMENT1;GGIO1 MX;AnIn1;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPE_HLa_Reset_Set SPS 765kV B708_TIE SYNCH FUNCTION CLOSE ORDER Set Reset RS_ST_CLS ODR Transmitted to IEC CONTROL1;RSYN1 ST;ClsOpSt;stVal;SPS None IntManualCSFct CS_CloseOrderState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPE_HLA_on_off SPS 765kV B708_TIE SYNCH FUNCTION ON/OFF SECONDARY SPS On Off RS_ST_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 ST;EnaSec;origin;SPC None 116 IntManualCSFct CS_OnOff_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPE_HLa_Reset_Set SPS 765kV B708_TIE SYNCH FUNCTION POSSIBLE CLOSING Set Reset RS_ST_POS CLS Transmitted to IEC CONTROL1;RSYN1 ST;Rel;stVal;SPS 74; None IntManualCSFct CS_AuthoState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPE_HLa_Reset_Set SPS 765kV B708_TIE SYNCH FUNCTION RS_ST_V CHOICE Set Reset RS_ST_V CHOICE Transmitted to IEC CONTROL1;RSYN1 ST;BusVC;stVal;SPS None IntManualCSFct CS_BusBarVChoice_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPE_HLa_Notper_Perm SPS 765kV B708_TIE 52 | OE_CL_CONTROL Close interlock result SPS Permissive Not Permissive Close intlk SPS Transmitted to IEC CONTROL2;CILO3 ST;EnaCls;stVal;SPS None CB CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPE_HLa_Reset_Set SPS 765kV B708_TIE 52 | OE_CL_CONTROL CLOSE ORDER Set Reset RS_ST_CLOSE ORD Transmitted to IEC CONTROL1;CSWI3 ST;ClsOrd;general;general;ACT 66;72; None 11;12 CB CloseOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPE_HLa_Notper_Perm SPS 765kV B708_TIE 89A | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPE_HLa_Notper_Perm SPS 765kV B708_TIE 89B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO2 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPE_HLa_Reset_Set SPS 765kV B708_TIE SYNCH FUNCTION PRESENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF U PRES Transmitted to IEC CONTROL1;RSYN1 ST;VRefInd;stVal;SPS 74; None IntManualCSFct CS_VoltageRefPresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPE_HLa_Reset_Set SPS 765kV B708_TIE SYNCH FUNCTION ABSENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF. U ABS Transmitted to IEC CONTROL1;RSYN1 ST;VRefAbs;stVal;SPS 74; None IntManualCSFct CS_VoltageRefAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPE_HLa_Reset_Set SPS 765kV B708_TIE SYNCH FUNCTION VOLT ABSENCE Set Reset RS_ST_VOLT ABS Transmitted to IEC CONTROL1;RSYN1 ST;VAbs;stVal;SPS 74; None IntManualCSFct CS_VoltageAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPE_HLa_Reset_Set SPS 765kV B708_TIE SYNCH FUNCTION VOLT PRESENCE Set Reset RS_ST_VOLT PRES Transmitted to IEC CONTROL1;RSYN1 ST;VP;stVal;SPS 74; None IntManualCSFct CS_VoltagePresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPE_HLa_Reset_Set SPS 765kV B708_TIE AR DATA LOCK Set Reset RS_ST_S10_LOCK Transmitted to IEC CONTROL1;GAPC1 ST;IndSys3;stVal;SPS 67; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPE_HLa_Reset_Set SPS 765kV B708_TIE AR DATA WAIT FOR CB CLOSE Set Reset RS_ST_S7_WT CB C Transmitted to IEC CONTROL1;GAPC1 ST;IndSys5;stVal;SPS 66; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPE_HLa_Reset_Set SPS 765kV B708_TIE AR DATA LOCK_SHOTS Set Reset RS_ST_S9_LO SHTS Transmitted to IEC CONTROL1;GAPC1 ST;IndSys4;stVal;SPS 67; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPE_HLa_Notper_Perm SPS 765kV B708_TIE 89A INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI1 ST;IndSys1;stVal;SPS 56<; None 180 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 17 SPE_HLa_Notper_Perm SPS 765kV B708_TIE 89AE1 INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI1 ST;IndSys1;stVal;SPS 59<; None 181 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 18 SPE_HLa_Notper_Perm SPS 765kV B708_TIE 89AE2 INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI2 ST;IndSys1;stVal;SPS 60<; None 182 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 19 SPE_HLa_Notper_Perm SPS 765kV B708_TIE 89B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI2 ST;IndSys1;stVal;SPS 61<; None 183 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 20 SPE_HLa_Notper_Perm SPS 765kV B708_TIE 89BE1 INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI3 ST;IndSys1;stVal;SPS 64<; None 184 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 21 SPE_HLa_Notper_Perm SPS 765kV B708_TIE 89BE2 INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI4 ST;IndSys1;stVal;SPS 65<; None 185 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 22 SPE_HLA_Normal_Alarm SPS 765kV B708_TIE AC-KIOSK FIRE DETECTED Alarm Normal NL_AL_FIRE Transmitted to IEC CONTROL1;GAPC7 ST;IndSys1;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 23 SPE_HLA_Alm_Reset SPS 765kV B708_TIE AC-KIOSK AC COMPRESSOR 1&2 Reset Operated OF_ON_AC COMP Transmitted to IEC CONTROL1;GAPC7 ST;IndSys2;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 24 SPE_HLA_Reset_Optd SPS 765kV B708_TIE AR DATA LOCKOUT FROM AR LOGIC Operated Reset RS_OP_AR LO FBD Transmitted to IEC CONTROL1;GAPC1 ST;IndSys1;stVal;SPS 67<; None 186 1 C264 SELF GENERATED DIGITAL INFORMATION
A 25 SPE_HLa_Reset_Set SPS 765kV B708_TIE AR DATA AR LOCK Set Reset RS_ST_AR LOCK IS Transmitted to IEC CONTROL1;GAPC1 ST;SPCSO1;origin;SPC None 115 68 1 C264 SELF GENERATED DIGITAL INFORMATION
A 26 SPE_HLA_Reset_Optd SPS 765kV B708_TIE AR DATA A/R OPTD FROM FBD Operated Reset RS_ST_AR OPTD FB Transmitted to IEC CONTROL1;GAPC1 ST;IndSys2;stVal;SPS 66<; None 187;188 1 C264 SELF GENERATED DIGITAL INFORMATION
A 27 SPE_HLa_Reset_Select SPS 765kV B708_TIE CVT SELECTION 400KV SELECT AT LV VOLTAGE Selected Reset AT_VOL_SEL Transmitted to IEC CONTROL2;GAPC1 ST;IndSys1;stVal;SPS None 189;190 1 C264 SELF GENERATED DIGITAL INFORMATION
A 28 SPE_HLa_Reset_Select SPS 765kV B708_TIE CVT SELECTION BUS-1 VOLTAGE Selected Reset BUS-1_SELECT Transmitted to IEC CONTROL2;GAPC1 ST;IndSys2;stVal;SPS 70<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 29 SPE_HLa_Reset_Select SPS 765kV B708_TIE CVT SELECTION 765KV BUS-2 CVT Selected Reset BUS-2_CVT_SEL Transmitted to IEC CONTROL2;GAPC1 ST;IndSys3;stVal;SPS None 191;192 1 C264 SELF GENERATED DIGITAL INFORMATION
A 30 SPE_HLa_Reset_Set SPS 765kV B708_TIE CVT SELECTION LINE VOLTAGE Set Reset LINE_SELECT Transmitted to IEC CONTROL2;GAPC1 ST;IndSys4;stVal;SPS 70<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 31 SPE_HLa_Reset_Set SPS 765kV B708_TIE DT SEND DT SEND Set Reset RS_ST_DT SEND Transmitted to IEC CONTROL1;GAPC5 ST;IndSys1;stVal;SPS 71<; None 193;194 1 C264 SELF GENERATED DIGITAL INFORMATION
A 32 SPS_HLA_Reset_Set SPS 765kV B708_TIE PROTECTION SOTF TO RLY Set Reset SOTF TO RLY Transmitted to IEC CONTROL1;GAPC3 ST;IndSys1;stVal;SPS 72<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 33 SPE_HLa_Reset_Set SPS 765kV B708_TIE PSD PSD BYPASS Set Reset RS_ST_PSD BYPASS Transmitted to IEC CONTROL1;GAPC6 ST;IndSys1;stVal;SPS 73<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 34 SPE_HLa_Reset_Set SPS 765kV B708_TIE SYNCH DATA CLOSE PERMISSIVE Set Reset RS_ST_CB CLOSE Transmitted to IEC CONTROL1;GAPC4 ST;IndSys5;stVal;SPS 74<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 35 SPE_HLa_Reset_Set SPS 765kV B708_TIE SYNCH DATA DEAD INCOMING DEAD RUNNING Set Reset RS_ST_DINC_DRUN Transmitted to IEC CONTROL1;GAPC4 ST;IndSys4;stVal;SPS 74<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 36 SPE_HLa_Reset_Set SPS 765kV B708_TIE SYNCH DATA DEAD INCOMING LIVE RUNNING Set Reset RS_ST_DINC_LRUN Transmitted to IEC CONTROL1;GAPC4 ST;IndSys3;stVal;SPS 74<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 37 SPE_HLa_Reset_Set SPS 765kV B708_TIE SYNCH DATA LIVE INCOMING DEAD RUNNING Set Reset RS_ST_LINC_DRUN Transmitted to IEC CONTROL1;GAPC4 ST;IndSys2;stVal;SPS 74<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 38 SPE_HLa_Reset_Set SPS 765kV B708_TIE SYNCH DATA LIVE INCOMING LIVE RUNNING Set Reset RS_ST_LINC_LRUN Transmitted to IEC CONTROL1;GAPC4 ST;IndSys1;stVal;SPS 74<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 39 SPE_HLa_Reset_Set SPS 765kV B708_TIE 52 | OE_CL_CONTROL OPEN ORDER Set Reset RS_ST_OPEN ORD Transmitted to IEC CONTROL1;CSWI3 ST;OpnOrd;general;general;ACT 22;71; None CB OpenOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 40 SPE_HLa_Notper_Perm SPS 765kV B708_TIE 89A | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 41 SPE_HLa_Notper_Perm SPS 765kV B708_TIE 89B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO2 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 42 SPS_hla_Set_Reset SPS 765kV B708_TIE Order running on the bay Set Reset Order running Transmitted to IEC CONTROL2;GBAY1 ST;OrdRun;stVal;SPS None OrderInProgress 1 C264 SELF GENERATED DIGITAL INFORMATION
A 43 DP_HLA_CBOpen_Close DPS 765kV B708_TIE 52 COMPUTED SWITCH POSITION Open OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;origin;DPC 100;101;102;103;104;105;106;107;11;111;12;13;22;50;56;57;58;61;62;63;71;87;88;89;90;91;92;93;94;95;99; None 16 68;69 CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 44 DP_HLA_CBOpen_Close DPS 765kV B708_TIE 52 COMPUTED SWITCH POSITION Closed OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;origin;DPC 100;101;102;103;104;105;106;107;11;111;12;13;22;50;56;57;58;61;62;63;71;87;88;89;90;91;92;93;94;95;99; None 16 68;69 CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 45 DP_HLA_Off_On DPS 765kV B708_TIE AR FUNCTION-TIE ON/OFF STATUS Off OF_ON_AR STATUS Transmitted to IEC CONTROL1;GAPC2 ST;DPCSO1;origin;DPC None 19 2 68 1 C264 SELF GENERATED DIGITAL INFORMATION
A 46 DP_HLA_Off_On DPS 765kV B708_TIE AR FUNCTION-TIE ON/OFF STATUS On OF_ON_AR STATUS Transmitted to IEC CONTROL1;GAPC2 ST;DPCSO1;origin;DPC None 19 2 68 1 C264 SELF GENERATED DIGITAL INFORMATION
A 47 DP_HLa_LocRem_Bay DPS 765kV B708_TIE BCU MODE Local LC_RM_MODE Transmitted to IEC CONTROL2;GBAY1 ST;Loc;origin;DPC None 20 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 48 DP_HLa_LocRem_Bay DPS 765kV B708_TIE BCU MODE Remote LC_RM_MODE Transmitted to IEC CONTROL2;GBAY1 ST;Loc;origin;DPC None 20 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 49 MP_HLA_AR_Fault MPS 765kV B708_TIE AR_1PH_1SHOT_ISA AUTORECLOSER FAULT STATUS AUTORECLOSER FLT Transmitted to IEC CONTROL2;GAPC2 ST;IntSys2;stVal;INS None UsrFct UserFunctionMPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 50 MP_HLA_AR_Status MPS 765kV B708_TIE AR_1PH_1SHOT_ISA AUTORECLOSER STATUS AUTORECLOSER ST Transmitted to IEC CONTROL2;GAPC2 ST;IntSys1;stVal;INS None UsrFct UserFunctionMPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 51 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SC_DE_Lock_Unlock SPC 765kV B708_TIE AR DATA A/R LOCK Unlock Request UL_LO_AR Transmitted to IEC CONTROL1;GAPC1 CO;SPCSO1;ctlVal;DPC 115 68 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SC_DE_Set SPC 765kV B708_TIE PSD PSD OUT FROM HMI Set XX_ST_PSD OUT H Transmitted to IEC CONTROL1;GAPC6 CO;SPCSO1;ctlVal;DPC 73; 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SC_DE_Off_On_1 SPC 765kV B708_TIE SYNCH FUNCTION ON/OFF SECONDARY CONTROL SPC On Off OF_ON_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 CO;EnaSec;ctlVal;DPC 116 IntManualCSFct CS_CtrlOnOff_SPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 DC_SBO_Open_Close_2 DPC 765kV B708_TIE AR FUNCTION-TIE OFF Open OF_ON_A/R OFF Transmitted to IEC CONTROL1;GAPC2 CO;DPCSO1;sboClass;DPC 19 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 DC_SBO_Open_Close_2 DPC 765kV B708_TIE AR FUNCTION-TIE OFF Close OF_ON_A/R OFF Transmitted to IEC CONTROL1;GAPC2 CO;DPCSO1;sboClass;DPC 19 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 DC_DE_LocRem_BayCtrl DPC 765kV B708_TIE MODE CONTROL Local LC_RM_MODE Transmitted to IEC CONTROL2;GBAY1 CO;Loc;ctlVal;DPC 20 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 DC_DE_LocRem_BayCtrl DPC 765kV B708_TIE MODE CONTROL Remote LC_RM_MODE Transmitted to IEC CONTROL2;GBAY1 CO;Loc;ctlVal;DPC 20 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 MV 765kV B708_TIE CB_COUNTER Count_Close 0.0 10000.0 Count_Close Transmitted to IEC CONTROL2;GAPC2 MX;AnIn2;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 MV 765kV B708_TIE CB_COUNTER Count_Open 0.0 10000.0 Count_Open Transmitted to IEC CONTROL2;GAPC2 MX;AnIn1;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
MiCOM C264 DESCRIPTION
Computer Name B709_BR GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) C264 Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 0
Digital Inputs Board Slot P
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A P 1 SPARE SPS 765kV B709_BR 52 CB R PH POSITION Open OE_CL_R-PH_POS CONTROL2;XCBR2 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 2 SPARE SPS 765kV B709_BR 52 CB R PH POSITION Closed OE_CL_R-PH_POS CONTROL2;XCBR2 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 3 SPARE SPS 765kV B709_BR 52 CB Y PH POSITION Open OE_CL_Y-PH_POS CONTROL2;XCBR3 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 4 SPARE SPS 765kV B709_BR 52 CB Y PH POSITION Closed OE_CL_Y-PH_POS CONTROL2;XCBR3 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 5 SPARE SPS 765kV B709_BR 52 CB B PH POSITION Open OE_CL_B-PH_POS CONTROL2;XCBR4 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 6 SPARE SPS 765kV B709_BR 52 CB B PH POSITION Closed OE_CL_B-PH_POS CONTROL2;XCBR4 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 7 SPE_HLA_Normal_Alarm SPS 765kV B709_BR 52 SF6 GAS PRESSURE REFILL LOW Alarm Normal NL_AL_GAS RFL LO Transmitted to IEC CONTROL3;XCBR1 ST;Ind7;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 8 SPE_HLA_Normal_Alarm SPS 765kV B709_BR 52 SF6 GAS PRESSURE REFILL LEVEL-1 LOW Alarm Normal NL_AL_GAS RFL L1 Transmitted to IEC CONTROL3;XCBR1 ST;Ind6;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 9 SPE_HLA_Unhlthy_Hlthy SPS 765kV B709_BR 52 AR CB Healthy Unhealthy UL_HL_AR CB Transmitted to IEC CONTROL3;XCBR1 ST;Ind4;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 10 SPE_HLa_Reset_Set SPS 765kV B709_BR 52 CB IN REMOTE MODE Set Reset RS_ST_CB REMOTE Transmitted to IEC CONTROL3;XCBR1 ST;Ind3;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 11 SPE_HLA_Dischrgd_Charged SPS 765kV B709_BR 52 CB SPRING Charged Discharged DC_CH_ SPRING Transmitted to IEC CONTROL3;XCBR1 ST;Ind1;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 12 SPE_HLA_Normal_Fail SPS 765kV B709_BR 52 AC SUPPLY R Y B Fail Normal NL_FL_AC SUPPLY Transmitted to IEC CONTROL3;XCBR1 ST;Ind12;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 13 SPE_HLA_Normal_Alarm SPS 765kV B709_BR 52 SF6 GAS SECOND STAGE LOW Alarm Normal NL_AL_SF6 L2 Transmitted to IEC CONTROL3;XCBR1 ST;Ind11;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 14 SPE_HLA_Normal_Fail SPS 765kV B709_BR 52 DC SUPPLY-1/2 Fail Normal NL_FL_DC-1/2 SUP Transmitted to IEC CONTROL3;XCBR1 ST;Ind2;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 15 SPE_HLA_Normal_Alarm SPS 765kV B709_BR 52 SF6 GAS PRESSURE LEVEL-2 LOW Alarm Normal NL_AL_SF6 L2 LOW Transmitted to IEC CONTROL3;XCBR1 ST;Ind10;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 16 SPE_HLa_Reset_Set SPS 765kV B709_BR 52 SF6 GAS SECOND STAGE NORMAL Set Reset NL_AL_SF6 2ND ST Transmitted to IEC CONTROL3;XCBR1 ST;Ind9;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 1
Digital Inputs Board Slot O
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A O 1 SPE_HLA_Normal_Alarm SPS 765kV B709_BR 52 PH. POSITION DISCORDANCE Alarm Normal NL_AL_PD Transmitted to IEC CONTROL3;XCBR1 ST;Ind8;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 2 SPE_HLA_Reset_Optd SPS 765kV B709_BR 52 SF6 LOW PRESSURE LEVEL-2 NORMAL Operated Reset NL_AL_ LO PR L2 Transmitted to IEC CONTROL3;XCBR1 ST;Ind5;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 5 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89A POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI4 ST;Pos;stVal;DPC 116;65;80;84; None 22 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 6 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89A POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI4 ST;Pos;stVal;DPC 116;65;80;84; None 22 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 7 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89AE POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI9 ST;Pos;stVal;DPC 77;78;79;81;82;83; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 8 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89AE POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI9 ST;Pos;stVal;DPC 77;78;79;81;82;83; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 11 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89B POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI5 ST;Pos;stVal;DPC 116;80;84;85; None 23 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 12 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI5 ST;Pos;stVal;DPC 116;80;84;85; None 23 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 13 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89BE1 POSITION Open OP_CL_POS Transmitted to IEC CONTROL4;XSWI5 ST;Pos;stVal;DPC 77;78;79;81;82;83; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 14 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89BE1 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL4;XSWI5 ST;Pos;stVal;DPC 77;78;79;81;82;83; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 15 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89BE2 POSITION Open OP_CL_POS Transmitted to IEC CONTROL4;XSWI3 ST;Pos;stVal;DPC 198;199;200;289;290;291;380;381;382;81;82;83; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 16 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89BE2 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL4;XSWI3 ST;Pos;stVal;DPC 198;199;200;289;290;291;380;381;382;81;82;83; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 2
Digital Inputs Board Slot N
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A N 1 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89R-R POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI6 ST;Pos;stVal;DPC 102;103;104;86;97; None 25 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 2 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89R-R POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI6 ST;Pos;stVal;DPC 102;103;104;86;97; None 25 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 3 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89RE-R POSITION Open OP_CL_POS Transmitted to IEC CONTROL4;XSWI6 ST;Pos;stVal;DPC 61;62;63;90;91;92; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 4 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89RE-R POSITION Closed OP_CL_POS Transmitted to IEC CONTROL4;XSWI6 ST;Pos;stVal;DPC 61;62;63;90;91;92; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 5 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89R-Y POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI7 ST;Pos;stVal;DPC 105;106;107;86;98; None 29 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 6 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89R-Y POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI7 ST;Pos;stVal;DPC 105;106;107;86;98; None 29 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 7 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89RE-Y POSITION Open OP_CL_POS Transmitted to IEC CONTROL4;XSWI7 ST;Pos;stVal;DPC 61;62;63;93;94;95; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 8 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89RE-Y POSITION Closed OP_CL_POS Transmitted to IEC CONTROL4;XSWI7 ST;Pos;stVal;DPC 61;62;63;93;94;95; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 9 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89R-B POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI8 ST;Pos;stVal;DPC 100;101;86;96;99; None 24 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 10 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89R-B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI8 ST;Pos;stVal;DPC 100;101;86;96;99; None 24 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 11 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89RE-B POSITION Open OP_CL_POS Transmitted to IEC CONTROL4;XSWI1 ST;Pos;stVal;DPC 61;62;63;87;88;89; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 12 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89RE-B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL4;XSWI1 ST;Pos;stVal;DPC 61;62;63;87;88;89; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 13 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89RS-1R & 2R POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI1 ST;Pos;stVal;DPC 100;101;105;106;107;108;110;86;90;91;92;99; None 27 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 14 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89RS-1R & 2R POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI1 ST;Pos;stVal;DPC 100;101;105;106;107;108;110;86;90;91;92;99; None 27 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 3
Digital Inputs Board Slot M
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A M 1 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89RS-1Y & 2Y POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI2 ST;Pos;stVal;DPC 100;101;102;103;104;108;110;86;93;94;95;99; None 28 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A M 2 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89RS-1Y & 2Y POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI2 ST;Pos;stVal;DPC 100;101;102;103;104;108;110;86;93;94;95;99; None 28 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A M 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 5 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89RS-1B & 2B POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI3 ST;Pos;stVal;DPC 102;103;104;105;106;107;108;110;86;87;88;89; None 26 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A M 6 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89RS-1B & 2B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI3 ST;Pos;stVal;DPC 102;103;104;105;106;107;108;110;86;87;88;89; None 26 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A M 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 9 SPE_HLa_Reset_Set SPS 765kV B709_BR 709-LA BR-R PH STATUS Set Reset BR-R PH STATUS Transmitted to IEC CONTROL1;GGIO2 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 10 SPE_HLA_Normal_Fail SPS 765kV B709_BR 709-LA BR-Y PH STATUS Fail Normal BR-Y PH STATUS Transmitted to IEC CONTROL1;GGIO2 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 11 SPE_HLa_Reset_Set SPS 765kV B709_BR 709-LA BR-B PH STATUS Set Reset BR-B PH STATUS Transmitted to IEC CONTROL1;GGIO2 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 12 SPE_HLa_Reset_Set SPS 765kV B709_BR 709-LA S-R PH STATUS Set Reset S-R PH STATUS Transmitted to IEC CONTROL1;GGIO2 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 13 SPE_HLa_Reset_Set SPS 765kV B709_BR 709-LA S-Y PH STATUS Set Reset S-Y PH STATUS Transmitted to IEC CONTROL1;GGIO2 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 14 SPE_HLa_Reset_Set SPS 765kV B709_BR 709-LA S-B PH STATUS Set Reset S-B PH STATUS Transmitted to IEC CONTROL1;GGIO2 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 15 SPE_HLA_OS_IS SPS 765kV B709_BR PSD CSD In Service Out Service OS_IS_CSD Transmitted to IEC CONTROL2;GGIO2 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 16 SPE_HLA_Normal_Fail SPS 765kV B709_BR PSD SENSOR/CB VOL./SYNC DATA ERR/SYN FL Fail Normal NL_FL_SEN/VOL/SY Transmitted to IEC CONTROL2;GGIO2 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 4
Digital Inputs Board Slot L
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A L 1 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB WINDING TEMP HIGH R PH Alarm Normal NL_AL_WDG R Transmitted to IEC CONTROL2;GGIO1 ST;Ind12;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 2 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB OIL LOW LEVEL R PH Alarm Normal NL_AL_OLL R Transmitted to IEC CONTROL2;GGIO1 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 3 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB WINDING TEMP HIGH Y PH Alarm Normal NL_AL_WDG Y Transmitted to IEC CONTROL2;GGIO1 ST;Ind11;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 4 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB OIL LOW LEVEL Y PH Alarm Normal NL_AL_OLL Y Transmitted to IEC CONTROL2;GGIO1 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 5 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB WINDING TEMP HIGH B PH Alarm Normal NL_AL_WDG B Transmitted to IEC CONTROL2;GGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 6 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB OIL LOW LEVEL Y PH Alarm Normal NL_AL_OLL B Transmitted to IEC CONTROL2;GGIO1 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 7 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB BUCH 1&2 R PH Alarm Normal NL_AL_BUCH12 R Transmitted to IEC CONTROL2;GGIO1 ST;Ind14;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 8 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB BUCH 1&2 Y PH Alarm Normal NL_AL_BUCH12 Y Transmitted to IEC CONTROL2;GGIO1 ST;Ind15;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 9 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB BUCH 1&2 B PH Alarm Normal NL_AL_BUCH12 B Transmitted to IEC CONTROL2;GGIO1 ST;Ind16;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 10 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB OIL VERY LOW LEVEL R PH Alarm Normal NL_AL_VOLL R Transmitted to IEC CONTROL2;GGIO1 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 11 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB OIL VERY LOW LEVEL Y PH Alarm Normal NL_AL_VOLL Y Transmitted to IEC CONTROL2;GGIO1 ST;Ind7;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 12 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB OIL VERY LOW LEVEL B PH Alarm Normal NL_AL_VOLL B Transmitted to IEC CONTROL2;GGIO1 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 13 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB WINDING TEMP HIGH SP PH Alarm Normal NL_AL_WDG SP Transmitted to IEC CONTROL2;GGIO1 ST;Ind13;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 14 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB BUCH 1&2 SP PH Alarm Normal NL_AL_BUCH12 SP Transmitted to IEC CONTROL2;GGIO1 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 15 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB MAIN LOW LEVEL SP PH Alarm Normal NL_AL_MOG SP PH Transmitted to IEC CONTROL2;GGIO1 ST;Ind9;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 16 SPE_HLA_Normal_Alarm SPS 765kV B709_BR REACTOR_MB OTI Alarm Normal NL_AL_OTI Transmitted to IEC CONTROL2;GGIO1 ST;Ind10;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 5
Digital Inputs Board Slot K
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A K 1 SPE_HLA_Normal_Fail SPS 765kV B709_BR PROTECTION SPARE REACTOR DC Fail Normal NL_FL_SP DC Transmitted to IEC CONTROL1;GGIO3 ST;Ind9;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 2 SPE_HLA_Normal_Fail SPS 765kV B709_BR PROTECTION DC SOURCE-1 Fail Normal NL_FL_DC SUP1 Transmitted to IEC CONTROL1;GGIO3 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 3 SPE_HLA_Normal_Fail SPS 765kV B709_BR PROTECTION DC SOURCE-2 Fail Normal NL_FL_DC SUP2 Transmitted to IEC CONTROL1;GGIO3 ST;Ind12;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 4 SPE_HLA_Unhlthy_Hlthy SPS 765kV B709_BR PROTECTION PU A RELAY Healthy Unhealthy UH_HL_PU-A Transmitted to IEC CONTROL1;GGIO3 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 5 SPE_HLA_Unhlthy_Hlthy SPS 765kV B709_BR PROTECTION PU B RELAY Healthy Unhealthy UH_HL_PU-B Transmitted to IEC CONTROL1;GGIO3 ST;Ind10;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 6 SPE_HLA_Healthy_Flty SPS 765kV B709_BR PROTECTION CB_TC-1 Faulty Healthy HL_FT_CB TC-1 Transmitted to IEC CONTROL1;GGIO3 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 7 SPE_HLA_Healthy_Flty SPS 765kV B709_BR PROTECTION CB_TC-2 Faulty Healthy HL_FT_CB TC-2 Transmitted to IEC CONTROL1;GGIO3 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 8 SPE_HLA_Unhlthy_Hlthy SPS 765kV B709_BR PROTECTION 87R RELAY Healthy Unhealthy UH_HL_87R Transmitted to IEC CONTROL1;GGIO3 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 9 SPE_HLA_Unhlthy_Hlthy SPS 765kV B709_BR PROTECTION 64R RELAY Healthy Unhealthy UH_HL_64R Transmitted to IEC CONTROL1;GGIO3 ST;Ind11;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 10 SPE_HLA_Reset_Optd SPS 765kV B709_BR PROTECTION LBB Operated Reset RS_OP_LBB Transmitted to IEC CONTROL1;GGIO3 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 11 SPE_HLa_Dselect_Select SPS 765kV B709_BR PROTECTION BR#1 Selected Deselected DS_SL_BR#1 Transmitted to IEC CONTROL1;GGIO3 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 12 SPE_HLa_Dselect_Select SPS 765kV B709_BR PROTECTION BR-R/Y/B Selected Deselected DS_SL_BR-RYB Transmitted to IEC CONTROL1;GGIO3 ST;Ind7;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 13 SPS_HLA_Nok_OK SPS 765kV B709_BR PSD CONTROL SWITCHING DEVICE OK Not OK NOK_OK_DEVICE Transmitted to IEC CONTROL2;GGIO2 ST;Ind3;stVal;SPS 114; None 1 DIGITAL INPUT BOARD DIU2xx
A K 14 SPE_HLA_OS_IS SPS 765kV B709_BR PSD CSD In Service Out Service IN_OUT_CSD Transmitted to IEC CONTROL2;GGIO2 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 15 DP_HLA_Trip_Closed DPS 765kV B709_BR 52 EMERGENCY/MANUAL Closed TP_CL_EMRG/MAN Transmitted to IEC CONTROL3;XCBR1 ST;DPCSO1;stVal;DPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A K 16 DP_HLA_Trip_Closed DPS 765kV B709_BR 52 EMERGENCY/MANUAL Trip TP_CL_EMRG/MAN Transmitted to IEC CONTROL3;XCBR1 ST;DPCSO1;stVal;DPS None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 0
Digital Outputs Board Slot E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A E 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 2 DC_SBO_Open_Close DPC 765kV B709_BR 52 CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI9 CO;Pos;sboClass;DPC 21 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 3 DC_SBO_Open_Close DPC 765kV B709_BR 52 CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI9 CO;Pos;sboClass;DPC 21 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 4 SC_DE_NotPerm_Perm_2 SPC 765kV B709_BR PROTECTION TO PUA RESET XX_XX_CB PUA Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO1;ctlVal;DPC 13 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 5 SC_DE_NotPerm_Perm_2 SPC 765kV B709_BR PROTECTION TO PUB RESET XX_XX_CB PUB Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO2;ctlVal;DPC 14 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 6 SC_DE_Reset_Set_2 SPC 765kV B709_BR PSD CSD BYPASS Set XX_XX_PSD Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO1;ctlVal;DPC 222 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 7 SC_DE_Reset_Set_2 SPC 765kV B709_BR BUS SELECTION 765KV BUS-2 VT Set BUS-2_VT_SELECT Transmitted to IEC CONTROL1;GGIO4 CO;SPCSO4;ctlVal;DPC 111<; 221 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 8 SC_DE_Reset_Set_2 SPC 765kV B709_BR BUS SELECTION 765KV BUS-2 VT Set BUS-2_VT_DE-SEL Transmitted to IEC CONTROL1;GGIO4 CO;SPCSO3;ctlVal;DPC 111<; 220 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 9 SC_DE_Reset_Set_2 SPC 765kV B709_BR BUS SELECTION 765KV BUS-1 VT Set BUS-1_VT_SELECT Transmitted to IEC CONTROL1;GGIO4 CO;SPCSO2;ctlVal;DPC 111<; 219 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A E 10 SC_DE_Reset_Set_2 SPC 765kV B709_BR BUS SELECTION 765KV BUS-1 VT Set BUS-1_VT_DE-SEL Transmitted to IEC CONTROL1;GGIO4 CO;SPCSO1;ctlVal;DPC 111<; 218 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 1
Digital Outputs Board Slot F
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A F 1 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89A CONTROL Open OP_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 22 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 2 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89A CONTROL Close OP_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 22 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 3 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM 89A IL PERM RESET XX_XX_89A PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO1;ctlVal;DPC 195 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 4 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM 89AE IL PERM RESET XX_XX_89AE Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO9;ctlVal;DPC 196 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 5 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI5 CO;Pos;sboClass;DPC 23 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 6 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI5 CO;Pos;sboClass;DPC 23 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 7 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM 89B IL PERM RESET XX_XX_89B PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO18;ctlVal;DPC 197 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 8 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM 89BE1 IL PERM RESET XX_XX_89BE1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO19;ctlVal;DPC 198 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 9 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM 89BE2_I/P RESET XX_XX_89BE2_I/P Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO20;ctlVal;DPC 199 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A F 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 2
Digital Outputs Board Slot G
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A G 1 SC_DE_Reset_Reset_2 SPC 765kV B709_BR INTERLOCK_PERM TO BR1 SELECT RESET XX_SL_BR1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO8;ctlVal;DPC 215 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 2 SC_DE_Reset_Set_3 SPC 765kV B709_BR INTERLOCK_PERM BR1 DESELECT Set XX_DL_BR1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO10;ctlVal;DPC 212 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 3 SC_DE_Reset_Reset_2 SPC 765kV B709_BR INTERLOCK_PERM TO BR R PH SELECT RESET XX_SL_BR R PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO12;ctlVal;DPC 214 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 4 SC_DE_Reset_Set_3 SPC 765kV B709_BR INTERLOCK_PERM BR R PH DESELECT Set XX_DL_BR R PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO11;ctlVal;DPC 213 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 5 SC_DE_Reset_Reset_2 SPC 765kV B709_BR INTERLOCK_PERM TO BR Y PH SELECT RESET XX_SL_BR Y PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO14;ctlVal;DPC 217 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 6 SC_DE_Reset_Set_3 SPC 765kV B709_BR INTERLOCK_PERM BR Y PH DESELECT Set XX_DL_BR Y PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO13;ctlVal;DPC 216 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 7 SC_DE_Reset_Reset_2 SPC 765kV B709_BR INTERLOCK_PERM TO BR B PH SELECT RESET XX_SL_BR B PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO16;ctlVal;DPC 211 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 8 SC_DE_Reset_Set_3 SPC 765kV B709_BR INTERLOCK_PERM BR B PH DESELECT Set XX_DL_BR B PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO15;ctlVal;DPC 210 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 9 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM TO TRP COIL RESET XX_XX_TRP COIL Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO17;ctlVal;DPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A G 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 3
Digital Outputs Board Slot H
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A H 1 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89R-R CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI6 CO;Pos;sboClass;DPC 25 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 2 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89R-R CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI6 CO;Pos;sboClass;DPC 25 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 3 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM 89R-R IL PERM RESET XX_XX_89R-R PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO7;ctlVal;DPC 204 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 4 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM 89RE-R IL PERM RESET XX_XX_89RE-R PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO21;ctlVal;DPC 202 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 5 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89R-Y CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI7 CO;Pos;sboClass;DPC 29 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 6 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89R-Y CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI7 CO;Pos;sboClass;DPC 29 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 7 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM 89R-Y IL PERM RESET XX_XX_89R-Y PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO22;ctlVal;DPC 209 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 8 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM 89RE-Y IL PERM RESET XX_XX_89RE-Y PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO23;ctlVal;DPC 203 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A H 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 4
Digital Outputs Board Slot I
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A I 1 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89R-B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI8 CO;Pos;sboClass;DPC 24 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 2 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89R-B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI8 CO;Pos;sboClass;DPC 24 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 3 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM 89R-B IL PERM RESET XX_XX_89R-B PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO24;ctlVal;DPC 200 NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 4 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM 89RE-B IL PERM RESET XX_XX_89RE-B PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO2;ctlVal;DPC 201 NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A I 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 5
Digital Outputs Board Slot J
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A J 1 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89RS-1R & 2R CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 27 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A J 2 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89RS-1R & 2R CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 27 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A J 3 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM 89RS 1R2R IL PERM RESET XX_XX_89RS-1R 2R Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO3;ctlVal;DPC 206 NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 4 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89RS-1Y & 2Y CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 28 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A J 5 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89RS-1Y & 2Y CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 28 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A J 6 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM 89RS 1Y2Y IL PERM RESET XX_XX_89RS-1Y 2Y Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO4;ctlVal;DPC 207 NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 7 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89RS-1B & 2B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 26 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A J 8 DC_SBO_Open_Close_1 DPC 765kV B709_BR 89RS-1B & 2B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 26 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A J 9 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM 89RS 1B2B IL PERM RESET XX_XX_89RS-1B 2B Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO5;ctlVal;DPC 205 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A J 10 SC_DE_NotPerm_Perm_1 SPC 765kV B709_BR INTERLOCK_PERM 89RS-2ER IL PERM RESET XX_XX_89RS-2ER Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO6;ctlVal;DPC 208 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
ANALOG INPUT BOARD AIU21x
Analog Input Board Number 0
Analog Input Board Slot D
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 4/20 mA MV_hla_Temp ˚ Cel 765kV B709_BR REACTOR_MB OTI TEMP MONITOR R-PH 0.0 80.0 OTI_TEMP_R-PH Transmitted to IEC CONTROL2;GGIO1 MX;AnIn2;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 2 4/20 mA MV_hla_Temp ˚ Cel 765kV B709_BR REACTOR_MB WTI TEMP MONITOR R-PH 0.0 80.0 WTI_TEMP_R-PH Transmitted to IEC CONTROL2;GGIO1 MX;AnIn1;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 3 4/20 mA MV_hla_Temp ˚ Cel 765kV B709_BR REACTOR_MB OTI TEMP MONITOR Y-PH 0.0 80.0 OTI_TEMP_Y-PH Transmitted to IEC CONTROL2;GGIO1 MX;AnIn4;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 4 4/20 mA MV_hla_Temp ˚ Cel 765kV B709_BR REACTOR_MB WTI TEMP MONITOR Y-PH 0.0 80.0 WTI_TEMP_Y-PH Transmitted to IEC CONTROL2;GGIO1 MX;AnIn3;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 5 4/20 mA MV_hla_Temp ˚ Cel 765kV B709_BR REACTOR_MB OTI TEMP MONITOR B-PH 0.0 80.0 OTI_TEMP_B-PH Transmitted to IEC CONTROL2;GGIO1 MX;AnIn6;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 6 4/20 mA MV_hla_Temp ˚ Cel 765kV B709_BR REACTOR_MB WTI TEMP MONITOR B-PH 0.0 80.0 WTI_TEMP_B-PH Transmitted to IEC CONTROL2;GGIO1 MX;AnIn5;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 7 4/20 mA MV_hla_Temp ˚ Cel 765kV B709_BR REACTOR_MB OTI TEMP MONITOR SP-PH 0.0 80.0 OTI_TEMP_SP-PH Transmitted to IEC CONTROL2;GGIO1 MX;AnIn8;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 8 4/20 mA MV_hla_Temp ˚ Cel 765kV B709_BR REACTOR_MB WTI TEMP MONITOR SP-PH 0.0 80.0 WTI_TEMP_SP-PH Transmitted to IEC CONTROL2;GGIO1 MX;AnIn7;mag;MV 6 ANALOG INPUT BOARD AIU21x
CT/VT ANALOG INPUT BOARD TMU2x0
CT/VT Board Number 0
CT/VT Board Slot Q
CT/VT Board Model TMU220
Nominal Current 1 (1A/5A)
Nominal Voltage 110.00 [1V … 500V]
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A DF MV_HLa_Frequency_2 Hz 765kV B709_BR SYNCH DATA FREQUENCY DIFFERENCE 0.0 2.0 FREQUENCY DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifHzClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DV MV_HLa_Voltage_1 kV 765kV B709_BR SYNCH DATA VOLTAGE DIFFERENCE 0.0 530.0 VOLTAGE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifVClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Dj MV_hla_PhaseDiff ˚ 765kV B709_BR SYNCH DATA PHASE DIFFERENCE 0.0 360.0 PHASE ANGLE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifAngClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ia MV_HLa_AuxCurrent A 765kV B709_BR METERING I-R PHASE CURRENT 0.0 2400.0 IR PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ib MV_HLa_AuxCurrent A 765kV B709_BR METERING I-Y PHASE CURRENT 0.0 2400.0 IY PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ic MV_HLa_Frequency_1 Hz 765kV B709_BR METERING I-B PHASE CURRENT 0.0 2400.0 IB PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsC;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vb MV_HLa_Voltage_1 kV 765kV B709_BR SYNCH DATA INCOMING SUPPLY 0.0 530.0 INCOMING SUPPLY Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;PhV;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uab MV_HLa_Voltage kV 765kV B709_BR METERING R-Y VOLTAGE 0.0 918.0 R-Y VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsAB;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ubc MV_HLa_Voltage kV 765kV B709_BR METERING Y-B VOLTAGE 0.0 918.0 Y-B VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsBC;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uca MV_HLa_Voltage kV 765kV B709_BR METERING B-R VOLTAGE 0.0 918.0 B-R VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsCA;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar MV_HLa_Voltage_1 kV 765kV B709_BR SYNCH DATA RUNNING SUPPLY-1 0.0 530.0 RUNNING SPLY-1 Transmitted to IEC MEASUREMENT1;barMMXU1 MX;PhV;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Freq (Line) MV_HLa_Frequency Hz 765kV B709_BR METERING FREQUENCY 45.0 55.0 FREQUENCY Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;Hz;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A P total (MW) MV_HLa_ActPower_2 MW 765kV B709_BR METERING ACTIVE POWER -3179.952 3179.952 ACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotW;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Q total (Mvar) MV_HLa_ReactPower_2 MVAr 765kV B709_BR METERING REACTIVE POWER -3179.952 3179.952 REACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotVAr;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar RMS 2 value of the busbar voltage phase MV_HLa_Voltage_1 kV 765kV B709_BR SYNCH DATA RUNNING SUPPLY-2 0.0 530.0 RUNNING SPLY-2 Transmitted to IEC MEASUREMENT1;GGIO1 MX;AnIn1;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A cos ft : Power factor MV_HLa_PowerFactor 765kV B709_BR METERING POWER FACTOR -1.2 1.2 POWER FACTOR Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotPF;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPE_HLa_Reset_Set SPS 765kV B709_BR SYNCH FUNCTION CLOSE ORDER Set Reset RS_ST_CLS ODR Transmitted to IEC CONTROL1;RSYN1 ST;ClsOpSt;stVal;SPS None IntManualCSFct CS_CloseOrderState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPE_HLA_on_off SPS 765kV B709_BR SYNCH FUNCTION ON/OFF SECONDARY SPS On Off RS_ST_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 ST;EnaSec;origin;SPC None 117 IntManualCSFct CS_OnOff_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPE_HLa_Reset_Set SPS 765kV B709_BR SYNCH FUNCTION POSSIBLE CLOSING Set Reset RS_ST_POS CLS Transmitted to IEC CONTROL1;RSYN1 ST;Rel;stVal;SPS 115; None IntManualCSFct CS_AuthoState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPE_HLa_Reset_Set SPS 765kV B709_BR SYNCH FUNCTION RS_ST_V CHOICE Set Reset RS_ST_V CHOICE Transmitted to IEC CONTROL1;RSYN1 ST;BusVC;stVal;SPS 116<; None IntManualCSFct CS_BusBarVChoice_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPE_HLa_Notper_Perm SPS 765kV B709_BR 52 | OE_CL_CONTROL Close interlock result SPS Permissive Not Permissive Close intlk SPS Transmitted to IEC CONTROL3;CILO2 ST;EnaCls;stVal;SPS None CB CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPE_HLa_Reset_Set SPS 765kV B709_BR 52 | OE_CL_CONTROL CLOSE ORDER Set Reset CLOSE ORDER Transmitted to IEC CONTROL1;CSWI9 ST;ClsOrd;general;general;ACT None 13;14 CB CloseOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89A | OP_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO4 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO5 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89R-B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL3;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89R-R | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO6 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89RS-1B & 2B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO3 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89RS-1R & 2R | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89RS-1Y & 2Y | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO2 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89R-Y | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL3;CILO7 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPE_HLa_Reset_Set SPS 765kV B709_BR SYNCH FUNCTION PRESENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF U PRES Transmitted to IEC CONTROL1;RSYN1 ST;VRefInd;stVal;SPS 115; None IntManualCSFct CS_VoltageRefPresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPE_HLa_Reset_Set SPS 765kV B709_BR SYNCH FUNCTION ABSENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF. U ABS Transmitted to IEC CONTROL1;RSYN1 ST;VRefAbs;stVal;SPS 115; None IntManualCSFct CS_VoltageRefAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 17 SPE_HLa_Reset_Set SPS 765kV B709_BR SYNCH FUNCTION VOLT ABSENCE Set Reset RS_ST_VOLT ABS Transmitted to IEC CONTROL1;RSYN1 ST;VAbs;stVal;SPS 115; None IntManualCSFct CS_VoltageAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 18 SPE_HLa_Reset_Set SPS 765kV B709_BR SYNCH FUNCTION VOLT PRESENCE Set Reset RS_ST_VOLT PRES Transmitted to IEC CONTROL1;RSYN1 ST;VP;stVal;SPS 115; None IntManualCSFct CS_VoltagePresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 19 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89A INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI4 ST;IndSys1;stVal;SPS 77<; None 195 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 20 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89AE INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI1 ST;IndSys1;stVal;SPS 80<; None 196 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 21 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI5 ST;IndSys1;stVal;SPS 81<; None 197 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 22 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89BE1 INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI4 ST;IndSys1;stVal;SPS 84<; None 198 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 23 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89BE2 INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL4;CSWI1 ST;IndSys1;stVal;SPS 85<; None 199 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 24 SPE_HLa_Reset_Close SPS 765kV B709_BR 89R POSITION Close Reset RS_CL_POS Transmitted to IEC CONTROL1;GAPC2 ST;IndSys2;stVal;SPS 86<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 25 SPE_HLA_Reset_Open SPS 765kV B709_BR 89R POSITION Open Normal RS_OE_POS Transmitted to IEC CONTROL1;GAPC2 ST;IndSys1;stVal;SPS 86<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 26 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89R-B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI8 ST;IndSys1;stVal;SPS 87<; None 200 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 27 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89RE-B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI2 ST;IndSys1;stVal;SPS 96<; None 201 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 28 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89RE-R INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI5 ST;IndSys1;stVal;SPS 97<; None 202 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 29 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89RE-Y INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL3;CSWI1 ST;IndSys1;stVal;SPS 98<; None 203 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 30 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89R-R INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI6 ST;IndSys1;stVal;SPS 90<; None 204 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 31 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89RS-1B & 2B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI3 ST;IndSys1;stVal;SPS 99<; None 205 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 32 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89RS-1R & 2R INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI1 ST;IndSys1;stVal;SPS 102<; None 206 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 33 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89RS-1Y & 2Y INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI2 ST;IndSys1;stVal;SPS 105<; None 207 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 34 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89RS2ER INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI3 ST;IndSys1;stVal;SPS 108<; None 208 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 35 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89R-Y INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI7 ST;IndSys1;stVal;SPS 93<; None 209 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 36 SPE_HLa_Reset_DSelect SPS 765kV B709_BR BR_SELECTION BR1_B-PH_DE-SEL Deselected Reset BR1_B-PH_DE-SEL Transmitted to IEC CONTROL1;GAPC4 ST;IndSys3;stVal;SPS 110;110<; None 210 1 C264 SELF GENERATED DIGITAL INFORMATION
A 37 SPE_HLa_Reset_Select SPS 765kV B709_BR BR_SELECTION BR1_B-PH_SEL Selected Reset BR1_B-PH_SEL Transmitted to IEC CONTROL1;GAPC4 ST;IndSys4;stVal;SPS 110;110<; None 211 1 C264 SELF GENERATED DIGITAL INFORMATION
A 38 SPE_HLa_Reset_Select SPS 765kV B709_BR BR_SELECTION BR1_DE-SELECT Selected Reset BR1_DE-SELECT Transmitted to IEC CONTROL1;GAPC4 ST;IndSys2;stVal;SPS 110<; None 212 1 C264 SELF GENERATED DIGITAL INFORMATION
A 39 SPE_HLa_Reset_DSelect SPS 765kV B709_BR BR_SELECTION BR1_R-PH_DE-SEL Deselected Reset BR1_R-PH_DE-SEL Transmitted to IEC CONTROL1;GAPC4 ST;IndSys5;stVal;SPS 110;110<; None 213 1 C264 SELF GENERATED DIGITAL INFORMATION
A 40 SPE_HLa_Reset_Select SPS 765kV B709_BR BR_SELECTION BR1_R-PH_SEL Selected Reset BR1_R-PH_SEL Transmitted to IEC CONTROL1;GAPC4 ST;IndSys6;stVal;SPS 110;110<; None 214 1 C264 SELF GENERATED DIGITAL INFORMATION
A 41 SPE_HLa_Reset_Select SPS 765kV B709_BR BR_SELECTION BR1_SELECT Selected Reset BR1_SELECT Transmitted to IEC CONTROL1;GAPC4 ST;IndSys1;stVal;SPS 109;110<; None 215 1 C264 SELF GENERATED DIGITAL INFORMATION
A 42 SPE_HLa_Reset_DSelect SPS 765kV B709_BR BR_SELECTION BR1_Y-PH_DE-SEL Deselected Reset BR1_Y-PH_DE-SEL Transmitted to IEC CONTROL1;GAPC4 ST;IndSys7;stVal;SPS 110;110<; None 216 1 C264 SELF GENERATED DIGITAL INFORMATION
A 43 SPE_HLa_Reset_Select SPS 765kV B709_BR BR_SELECTION BR1_Y-PH_SEL Selected Reset BR1_Y-PH_SEL Transmitted to IEC CONTROL1;GAPC4 ST;IndSys8;stVal;SPS 110;110<; None 217 1 C264 SELF GENERATED DIGITAL INFORMATION
A 44 SPE_HLA_Normal_Alarm SPS 765kV B709_BR BR_SELECTION BR1_SELECT DISCREPANCY Alarm Normal NL_AL_BR1_SEL Transmitted to IEC CONTROL1;GAPC4 ST;IndSys9;stVal;SPS 109<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 45 SPE_HLa_Reset_DSelect SPS 765kV B709_BR BUS SELECTION 765KV BUS-1 VT Deselected Reset BUS-1_VT_DE-SEL Transmitted to IEC CONTROL2;GAPC1 ST;IndSys1;stVal;SPS 111<; None 218 1 C264 SELF GENERATED DIGITAL INFORMATION
A 46 SPE_HLa_Reset_Select SPS 765kV B709_BR BUS SELECTION 765KV BUS-1 VT Selected Reset BUS-1_VT_SELECT Transmitted to IEC CONTROL2;GAPC1 ST;IndSys2;stVal;SPS 111<; None 219 1 C264 SELF GENERATED DIGITAL INFORMATION
A 47 SPE_HLa_Reset_DSelect SPS 765kV B709_BR BUS SELECTION 765KV BUS-2 VT Deselected Reset BUS-2_VT_DE-SEL Transmitted to IEC CONTROL2;GAPC1 ST;IndSys3;stVal;SPS 111<; None 220 1 C264 SELF GENERATED DIGITAL INFORMATION
A 48 SPE_HLa_Reset_Select SPS 765kV B709_BR BUS SELECTION 765KV BUS-2 VT Selected Reset BUS-2_VT_SELECT Transmitted to IEC CONTROL2;GAPC1 ST;IndSys4;stVal;SPS 111<; None 221 1 C264 SELF GENERATED DIGITAL INFORMATION
A 49 SPE_HLA_Flty_Healthy SPS 765kV B709_BR PROTECTION Dummy SPS Healthy Faulty Dummy SPS Transmitted to IEC CONTROL1;GAPC3 ST;IndSys3;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 50 SPE_HLA_Reset_Alarm_Goose SPS 765kV B709_BR PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Reset GOOSE RECIEPT FL Transmitted to IEC CONTROL1;GAPC3 ST;IndSys2;stVal;SPS 113<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 51 SPE_HLA_Normal_Alarm SPS 765kV B709_BR PROTECTION HV WINDING TEMP HIGH SP-PH Alarm Normal NL_AL_HV WDG TMP Transmitted to IEC CONTROL1;GAPC3 ST;IndSys5;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 52 SPE_HLA_Normal_Alarm SPS 765kV B709_BR PROTECTION MAIN TANK MOG-SP PH Alarm Normal NL_AL_MOG SP PH Transmitted to IEC CONTROL1;GAPC3 ST;IndSys6;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 53 SPE_HLA_Normal_Alarm SPS 765kV B709_BR PROTECTION OTI-SP PH Alarm Normal NL_AL_OTI SP PH Transmitted to IEC CONTROL1;GAPC3 ST;IndSys7;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 54 SPE_HLA_Normal_Alarm SPS 765kV B709_BR PROTECTION SYNCH OPERATION FAIL Alarm Normal NL_AL_SYNCH OP F Transmitted to IEC CONTROL1;GAPC3 ST;IndSys1;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 55 SPE_HLA_Unhlthy_Hlthy SPS 765kV B709_BR PROTECTION 21R RELAY Healthy Unhealthy UH_HL_21R Transmitted to IEC CONTROL1;GAPC3 ST;IndSys4;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 56 SPE_HLa_Reset_Set SPS 765kV B709_BR PSD PSD BYPASS Set Reset RS_ST_PSD BYPASS Transmitted to IEC CONTROL2;GAPC2 ST;IndSys1;stVal;SPS 114<; None 222 1 C264 SELF GENERATED DIGITAL INFORMATION
A 57 SPE_HLa_Reset_Set SPS 765kV B709_BR SYNCH DATA CLOSE PERMISSIVE Set Reset RS_ST_CB CLOSE Transmitted to IEC CONTROL2;GAPC3 ST;IndSys5;stVal;SPS 115<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 58 SPE_HLa_Reset_Set SPS 765kV B709_BR SYNCH DATA DEAD INCOMING DEAD RUNNING Set Reset RS_ST_DINC_DRUN Transmitted to IEC CONTROL2;GAPC3 ST;IndSys4;stVal;SPS 115<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 59 SPE_HLa_Reset_Set SPS 765kV B709_BR SYNCH DATA DEAD INCOMING LIVE RUNNING Set Reset RS_ST_DINC_LRUN Transmitted to IEC CONTROL2;GAPC3 ST;IndSys3;stVal;SPS 115<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 60 SPE_HLa_Reset_Set SPS 765kV B709_BR SYNCH DATA LIVE INCOMING DEAD RUNNING Set Reset RS_ST_LINC_DRUN Transmitted to IEC CONTROL2;GAPC3 ST;IndSys2;stVal;SPS 115<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 61 SPE_HLa_Reset_Set SPS 765kV B709_BR SYNCH DATA LIVE INCOMING LIVE RUNNING Set Reset RS_ST_LINC_LRUN Transmitted to IEC CONTROL2;GAPC3 ST;IndSys1;stVal;SPS 115<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 62 SPE_HLa_Reset_Set SPS 765kV B709_BR 52 | OE_CL_CONTROL OPEN ORDER Set Reset OPEN ORDER Transmitted to IEC CONTROL1;CSWI9 ST;OpnOrd;general;general;ACT None CB OpenOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 63 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89A | OP_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO4 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 64 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO5 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 65 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89R-B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL3;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 66 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89R-R | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO6 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 67 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89RS-1B & 2B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO3 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 68 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89RS-1R & 2R | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 69 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89RS-1Y & 2Y | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO2 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 70 SPE_HLa_Notper_Perm SPS 765kV B709_BR 89R-Y | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL3;CILO7 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 71 SPS_hla_Set_Reset SPS 765kV B709_BR Order running on the bay Set Reset Order running Transmitted to IEC CONTROL3;GBAY1 ST;OrdRun;stVal;SPS None OrderInProgress 1 C264 SELF GENERATED DIGITAL INFORMATION
A 72 DP_HLA_CBOpen_Close DPS 765kV B709_BR 52 COMPUTED SWITCH POSITION Open OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI9 ST;Pos;origin;DPC 100;101;102;103;104;105;106;107;111;50;77;78;79;81;82;83;87;88;89;90;91;92;93;94;95;99; None 21 112 CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 73 DP_HLA_CBOpen_Close DPS 765kV B709_BR 52 COMPUTED SWITCH POSITION Closed OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI9 ST;Pos;origin;DPC 100;101;102;103;104;105;106;107;111;50;77;78;79;81;82;83;87;88;89;90;91;92;93;94;95;99; None 21 112 CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 74 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89R POSITION Open OE_CL_POS Transmitted to IEC CONTROL1;GAPC2 ST;DPCSO1;stVal;DPS 65; None Yes 1 C264 SELF GENERATED DIGITAL INFORMATION
A 75 DP_HLA_ ISOOpen_Close DPS 765kV B709_BR 89R POSITION Closed OE_CL_POS Transmitted to IEC CONTROL1;GAPC2 ST;DPCSO1;stVal;DPS 65; None Yes 1 C264 SELF GENERATED DIGITAL INFORMATION
A 76 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89RS2 POSITION Open OP_CL_POS Transmitted to IEC CONTROL4;XSWI4 ST;Pos;stVal;DPC None SG SwitchPos 1 C264 SELF GENERATED DIGITAL INFORMATION
A 77 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89RS2 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL4;XSWI4 ST;Pos;stVal;DPC None SG SwitchPos 1 C264 SELF GENERATED DIGITAL INFORMATION
A 78 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89RS2ER POSITION Open OP_CL_POS Transmitted to IEC CONTROL4;XSWI2 ST;Pos;stVal;DPC 100;101;102;103;104;105;106;107;99; None SG SwitchPos 1 C264 SELF GENERATED DIGITAL INFORMATION
A 79 DP_HLa_ESOpen_Close DPS 765kV B709_BR 89RS2ER POSITION Closed OP_CL_POS Transmitted to IEC CONTROL4;XSWI2 ST;Pos;stVal;DPC 100;101;102;103;104;105;106;107;99; None SG SwitchPos 1 C264 SELF GENERATED DIGITAL INFORMATION
A 80 DP_HLa_LocRem_Bay DPS 765kV B709_BR BCU MODE Local LC_RM_MODE Transmitted to IEC CONTROL3;GBAY1 ST;Loc;origin;DPC None 30 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 81 DP_HLa_LocRem_Bay DPS 765kV B709_BR BCU MODE Remote LC_RM_MODE Transmitted to IEC CONTROL3;GBAY1 ST;Loc;origin;DPC None 30 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 82 DP_HLA_CBOpen_Close DPS 765kV B709_BR RTCC_PANNEL OLTC Open OLTC Transmitted to IEC CONTROL1;GAPC1 ST;DPCSO1;origin;DPC None 31 1 C264 SELF GENERATED DIGITAL INFORMATION
A 83 DP_HLA_CBOpen_Close DPS 765kV B709_BR RTCC_PANNEL OLTC Closed OLTC Transmitted to IEC CONTROL1;GAPC1 ST;DPCSO1;origin;DPC None 31 1 C264 SELF GENERATED DIGITAL INFORMATION
A 84 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SC_DE_Reset_Set_2 SPC 765kV B709_BR PROTECTION CB COMMAND Set XX_TP_CB Transmitted to IEC CONTROL1;GAPC3 CO;SPCSO1;ctlVal;DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SC_DE_Set SPC 765kV B709_BR PSD PSD OUT FROM HMI Set XX_ST_PSD OUT H Transmitted to IEC CONTROL2;GAPC2 CO;SPCSO1;ctlVal;DPC 114; 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SC_DE_Off_On_1 SPC 765kV B709_BR SYNCH FUNCTION ON/OFF SECONDARY CONTROL SPC On Off OF_ON_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 CO;EnaSec;ctlVal;DPC 117 IntManualCSFct CS_CtrlOnOff_SPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 DC_DE_LocRem_BayCtrl DPC 765kV B709_BR MODE CONTROL Local MODE CONTROL Transmitted to IEC CONTROL2;GBAY1 CO;Loc;ctlVal;DPC 30 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 DC_DE_LocRem_BayCtrl DPC 765kV B709_BR MODE CONTROL Remote MODE CONTROL Transmitted to IEC CONTROL2;GBAY1 CO;Loc;ctlVal;DPC 30 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 DC_SBO_Open_Close_2 DPC 765kV B709_BR RTCC_PANNEL OLTC Open LO_RS_OLTC Transmitted to IEC CONTROL1;GAPC1 CO;DPCSO1;sboClass;DPC 31 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 DC_SBO_Open_Close_2 DPC 765kV B709_BR RTCC_PANNEL OLTC Close LO_RS_OLTC Transmitted to IEC CONTROL1;GAPC1 CO;DPCSO1;sboClass;DPC 31 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 MV 765kV B709_BR CB_COUNTER Count_Close 0.0 10000.0 Count_Close Transmitted to IEC CONTROL3;GAPC1 MX;AnIn2;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 MV 765kV B709_BR CB_COUNTER Count_Open 0.0 10000.0 Count_Open Transmitted to IEC CONTROL3;GAPC1 MX;AnIn1;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
MiCOM C264 DESCRIPTION
Computer Name B712_AT GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) C264 Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 0
Digital Inputs Board Slot P
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A P 1 SPARE SPS 765kV B712_ICT 52 CB R PH POSITION Open OE_CL_R-PH_POS CONTROL2;XCBR2 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 2 SPARE SPS 765kV B712_ICT 52 CB R PH POSITION Closed OE_CL_R-PH_POS CONTROL2;XCBR2 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 3 SPARE SPS 765kV B712_ICT 52 CB Y PH POSITION Open OE_CL_Y-PH_POS CONTROL2;XCBR3 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 4 SPARE SPS 765kV B712_ICT 52 CB Y PH POSITION Closed OE_CL_Y-PH_POS CONTROL2;XCBR3 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 5 SPARE SPS 765kV B712_ICT 52 CB B PH POSITION Open OE_CL_B-PH_POS CONTROL2;XCBR4 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 6 SPARE SPS 765kV B712_ICT 52 CB B PH POSITION Closed OE_CL_B-PH_POS CONTROL2;XCBR4 ST;Pos;stVal;DPC None No 1 DIGITAL INPUT BOARD DIU2xx
A P 7 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT 52 SF6 GAS PRESSURE REFILL LOW Alarm Normal NL_AL_GAS RFL LO Transmitted to IEC CONTROL3;XCBR1 ST;Ind8;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 8 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT 52 SF6 GAS PRESSURE REFILL LEVEL-1 LOW Alarm Normal NL_AL_GAS RFL L1 Transmitted to IEC CONTROL3;XCBR1 ST;Ind7;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 9 SPE_HLA_Unhlthy_Hlthy SPS 765kV B712_ICT 52 AR CB Healthy Unhealthy UL_HL_AR CB Transmitted to IEC CONTROL3;XCBR1 ST;Ind1;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 10 SPE_HLa_Reset_Set SPS 765kV B712_ICT 52 CB IN REMOTE MODE Set Reset RS_ST_CB REMOTE Transmitted to IEC CONTROL3;XCBR1 ST;Ind4;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 11 SPE_HLA_Dischrgd_Charged SPS 765kV B712_ICT 52 CB SPRING Charged Discharged DC_CH_ SPRING Transmitted to IEC CONTROL3;XCBR1 ST;Ind5;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 12 SPE_HLA_Normal_Fail SPS 765kV B712_ICT 52 AC SUPPLY R Y B Fail Normal NL_FL_AC SUPPLY Transmitted to IEC CONTROL3;XCBR1 ST;Ind2;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 13 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT 52 SF6 GAS SECOND STAGE LOW Alarm Normal NL_AL_SF6 L2 Transmitted to IEC CONTROL3;XCBR1 ST;Ind12;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 14 SPE_HLA_Normal_Fail SPS 765kV B712_ICT 52 DC SUPPLY-1/2 Fail Normal NL_FL_DC-1/2 SUP Transmitted to IEC CONTROL3;XCBR1 ST;Ind3;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 15 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT 52 SF6 GAS PRESSURE LEVEL-2 LOW Alarm Normal NL_AL_SF6 L2 LOW Transmitted to IEC CONTROL3;XCBR1 ST;Ind11;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 16 SPE_HLa_Reset_Set SPS 765kV B712_ICT 52 SF6 GAS SECOND STAGE NORMAL Set Reset NL_AL_SF6 2ND ST Transmitted to IEC CONTROL3;XCBR1 ST;Ind10;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 1
Digital Inputs Board Slot O
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A O 1 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT 52 PH. POSITION DISCORDANCE Alarm Normal NL_AL_PD Transmitted to IEC CONTROL3;XCBR1 ST;Ind9;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 2 SPE_HLA_Reset_Optd SPS 765kV B712_ICT 52 SF6 LOW PRESSURE LEVEL-2 NORMAL Operated Reset NL_AL_ LO PR L2 Transmitted to IEC CONTROL3;XCBR1 ST;Ind6;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 5 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89A POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI4 ST;Pos;stVal;DPC 182;197;201;230; None 55 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 6 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89A POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI4 ST;Pos;stVal;DPC 182;197;201;230; None 55 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 7 DP_HLa_ESOpen_Close DPS 765kV B712_ICT 89AE POSITION Open OP_CL_POS Transmitted to IEC CONTROL4;XSWI1 ST;Pos;stVal;DPC 194;195;196;198;199;200;233;234; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 8 DP_HLa_ESOpen_Close DPS 765kV B712_ICT 89AE POSITION Closed OP_CL_POS Transmitted to IEC CONTROL4;XSWI1 ST;Pos;stVal;DPC 194;195;196;198;199;200;233;234; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 9 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89B POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI5 ST;Pos;stVal;DPC 197;201;230;85; None 56 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 10 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI5 ST;Pos;stVal;DPC 197;201;230;85; None 56 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 11 DP_HLa_ESOpen_Close DPS 765kV B712_ICT 89BE POSITION Open OP_CL_POS Transmitted to IEC CONTROL4;XSWI2 ST;Pos;stVal;DPC 194;195;196;198;199;200;233;234; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 12 DP_HLa_ESOpen_Close DPS 765kV B712_ICT 89BE POSITION Closed OP_CL_POS Transmitted to IEC CONTROL4;XSWI2 ST;Pos;stVal;DPC 194;195;196;198;199;200;233;234; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 2
Digital Inputs Board Slot N
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A N 1 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89T1-R POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI6 ST;Pos;stVal;DPC 202;213;218;219;220;236; None 58 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 2 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89T1-R POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI6 ST;Pos;stVal;DPC 202;213;218;219;220;236; None 58 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 3 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89TE1-R POSITION Open OP_CL_POS Transmitted to IEC CONTROL4;XSWI3 ST;Pos;stVal;DPC 178;179;180;206;207;208; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 4 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89TE1-R POSITION Closed OP_CL_POS Transmitted to IEC CONTROL4;XSWI3 ST;Pos;stVal;DPC 178;179;180;206;207;208; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 5 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89T1-Y POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI7 ST;Pos;stVal;DPC 202;214;221;222;223;236; None 59 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 6 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89T1-Y POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI7 ST;Pos;stVal;DPC 202;214;221;222;223;236; None 59 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 7 DP_HLa_ESOpen_Close DPS 765kV B712_ICT 89TE1-Y POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI9 ST;Pos;stVal;DPC 178;179;180;209;210;211; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 8 DP_HLa_ESOpen_Close DPS 765kV B712_ICT 89TE1-Y POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI9 ST;Pos;stVal;DPC 178;179;180;209;210;211; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 9 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89T1-B POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI8 ST;Pos;stVal;DPC 202;212;215;216;217;236; None 57 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 10 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89T1-B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI8 ST;Pos;stVal;DPC 202;212;215;216;217;236; None 57 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 11 DP_HLa_ESOpen_Close DPS 765kV B712_ICT 89TE1-B POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI10 ST;Pos;stVal;DPC 178;179;180;203;204;205; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 12 DP_HLa_ESOpen_Close DPS 765kV B712_ICT 89TE1-B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI10 ST;Pos;stVal;DPC 178;179;180;203;204;205; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 13 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89TS-2R & 3R POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI1 ST;Pos;stVal;DPC 202;206;207;208;215;216;217;221;222;223;224;236;306;307;308;309;310;311;312;313;314;397;398;399;400;401;402;403;404;405;406; None 61 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 14 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89TS-2R & 3R POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI1 ST;Pos;stVal;DPC 202;206;207;208;215;216;217;221;222;223;224;236;306;307;308;309;310;311;312;313;314;397;398;399;400;401;402;403;404;405;406; None 61 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 15 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89TS-2Y & 3Y POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI2 ST;Pos;stVal;DPC 202;209;210;211;215;216;217;218;219;220;224;236;306;307;308;309;310;311;312;313;314;397;398;399;400;401;402;403;404;405;406; None 62 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 16 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89TS-2Y & 3Y POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI2 ST;Pos;stVal;DPC 202;209;210;211;215;216;217;218;219;220;224;236;306;307;308;309;310;311;312;313;314;397;398;399;400;401;402;403;404;405;406; None 62 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 3
Digital Inputs Board Slot M
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A M 1 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89TS-2B & 3B POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI3 ST;Pos;stVal;DPC 202;203;204;205;218;219;220;221;222;223;224;236;306;307;308;309;310;311;312;313;314;397;398;399;400;401;402;403;404;405;406; None 60 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A M 2 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89TS-2B & 3B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI3 ST;Pos;stVal;DPC 202;203;204;205;218;219;220;221;222;223;224;236;306;307;308;309;310;311;312;313;314;397;398;399;400;401;402;403;404;405;406; None 60 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A M 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A None 1 DIGITAL INPUT BOARD DIU2xx
A None 1 DIGITAL INPUT BOARD DIU2xx
A 0 13 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_R-PH HV WINDING TEMP HIGH Alarm Normal NL_AL_HV WDG TMP Transmitted to IEC CONTROL1;GGIO3 ST;Ind15;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A 0 14 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_R-PH IV WDG TEMP HIGH ALARM-R PH Alarm Normal NL_AL_IV TEMP Transmitted to IEC CONTROL1;GGIO3 ST;Ind13;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A 0 15 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_R-PH LV WDG TEMP HIGH ALARM R PH Alarm Normal NL_AL_LV TEMP Transmitted to IEC CONTROL1;GGIO3 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A 0 16 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_R-PH TOP OIL TEMP HIGH Alarm Normal NL_AL_OIL HIGH Transmitted to IEC CONTROL1;GGIO3 ST;Ind16;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 4
Digital Inputs Board Slot L
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A L 1 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_R-PH MAIN TANK 1 LOW LEVEL R PH Alarm Normal NL_AL_MOG R PH L Transmitted to IEC CONTROL1;GGIO3 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 2 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_R-PH MAIN TANK 1 HIGH LEVEL R PH Alarm Normal NL_AL_MOG R PH H Transmitted to IEC CONTROL1;GGIO3 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 3 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_R-PH MAIN TANK 2 LOW LEVEL R PH Alarm Normal NL_AL_MOG2 RPH L Transmitted to IEC CONTROL1;GGIO3 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 4 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_R-PH MAIN TANK 2 HIGH LEVEL R PH Alarm Normal NL_AL_MOG2 RPH H Transmitted to IEC CONTROL1;GGIO3 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 5 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_R-PH OFI 1 2 R PH Alarm Normal NL_AL_OFI 12 Transmitted to IEC CONTROL1;GGIO3 ST;Ind10;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 6 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_R-PH OFI 3 4 R PH Alarm Normal NL_AL_OFI 34 Transmitted to IEC CONTROL1;GGIO3 ST;Ind11;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 7 SPE_HLA_Normal_Fail SPS 765kV B712_ICT TRAFO_MB_R-PH FAN-1/2/3/4 -R PH Fail Normal NL_FL_FAN Transmitted to IEC CONTROL1;GGIO3 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 8 SPE_HLA_Normal_Fail SPS 765kV B712_ICT TRAFO_MB_R-PH PUMP-1/2/3/4 NO OIL FLOW R PH Fail Normal NL_FL_PUMP Transmitted to IEC CONTROL1;GGIO3 ST;Ind12;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 9 SPE_HLA_Normal_Fail SPS 765kV B712_ICT TRAFO_MB_R-PH CONTROL SUPPLY-R PH Fail Normal NL_FL_CNTRL SUP Transmitted to IEC CONTROL1;GGIO3 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 10 SPE_HLA_Reset_Optd SPS 765kV B712_ICT TRAFO_MB_R-PH FIRE PROTECTION-R PH Operated Reset RS_OP_FIRE PRO Transmitted to IEC CONTROL1;GGIO3 ST;Ind7;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
OLTC MOTOR OVERLOAD - RPH
TAP CHANGE IN PROGRESS - RPH
TAP CHANGE IN COMPLETE - RPH
OLTC IN LOCAL - RPH
OLTC IN REMOTE - RPH
TAP CHANGE CONTROL SUPPLY FAIL - RPH
LOWEST POSITION REACHED - RPH
HIGHESHT POSITION REACHED - RPH
OLTC RAISE COMMAND - RPH
OLTC LOWER COMMAND - RPH
A OIL FLOW SENSITIVE VALVE ALARM - RPH None 1 DIGITAL INPUT BOARD DIU2xx
A LOW OIL FLOW/REVERSE FLOW - RPH None 1 DIGITAL INPUT BOARD DIU2xx
A 0 13 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_Y-PH HV WINDING TEMP HIGH- Y PH Alarm Normal NL_AL_HV TEMP Transmitted to IEC CONTROL1;GGIO5 ST;Ind13;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A 0 14 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_Y-PH IV WDG TEMP HIGH ALARM-Y PH Alarm Normal NL_AL_IV TEMP Transmitted to IEC CONTROL1;GGIO5 ST;Ind12;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A 0 15 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_Y-PH LV WDG TEMP HIGH ALARM-Y PH Alarm Normal NL_AL_LV TEMP Transmitted to IEC CONTROL1;GGIO5 ST;Ind15;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A 0 16 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_Y-PH TOP OIL TEMP HIGH-Y PH Alarm Normal NL_AL_TOP OIL Transmitted to IEC CONTROL1;GGIO5 ST;Ind14;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 5
Digital Inputs Board Slot K
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A K 1 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_Y-PH MAIN TANK 1 LOW LEVEL Y PH Alarm Normal NL_AL_MOG Y PH L Transmitted to IEC CONTROL1;GGIO5 ST;Ind7;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 2 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_Y-PH MAIN TANK 1 HIGH LEVEL Y PH Alarm Normal NL_AL_MOG Y PH H Transmitted to IEC CONTROL1;GGIO5 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 3 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_Y-PH MAIN TANK 2 LOW LEVEL Y PH Alarm Normal NL_AL_MOG2 YPH L Transmitted to IEC CONTROL1;GGIO5 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 4 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_Y-PH MAIN TANK 2 HIGH LEVEL Y PH Alarm Normal NL_AL_MOG2 YPH H Transmitted to IEC CONTROL1;GGIO5 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 5 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_Y-PH OFI 1 2 Y PH Alarm Normal NL_AL_OFI 1 2 Transmitted to IEC CONTROL1;GGIO5 ST;Ind9;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 6 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT TRAFO_MB_Y-PH OFI 3 4 Y PH Alarm Normal NL_AL_OFI 3 4 Transmitted to IEC CONTROL1;GGIO5 ST;Ind10;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 7 SPE_HLA_Normal_Fail SPS 765kV B712_ICT TRAFO_MB_Y-PH FAN-1/2/3/4-Y PH Fail Normal NL_FL_FAN Transmitted to IEC CONTROL1;GGIO5 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 8 SPE_HLA_Normal_Fail SPS 765kV B712_ICT TRAFO_MB_Y-PH PUMP-1/2/3/4-Y PH Fail Normal NL_FL_PUMP Transmitted to IEC CONTROL1;GGIO5 ST;Ind11;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 9 SPE_HLA_Normal_Fail SPS 765kV B712_ICT TRAFO_MB_Y-PH CONTROL SUPPLY-Y PH Fail Normal NL_FL_CNTRL SUP Transmitted to IEC CONTROL1;GGIO5 ST;Ind16;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 10 SPE_HLA_Reset_Optd SPS 765kV B712_ICT TRAFO_MB_Y-PH FIRE PROTECTION-Y PH Operated Reset RS_OP_FIRE PRO Transmitted to IEC CONTROL1;GGIO5 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
OLTC MOTOR OVERLOAD - YPH
TAP CHANGE IN PROGRESS - YPH
TAP CHANGE IN COMPLETE - YPH
OLTC IN LOCAL - YPH
OLTC IN REMOTE - YPH
TAP CHANGE CONTROL SUPPLY FAIL - YPH
LOWEST POSITION REACHED - YPH
HIGHESHT POSITION REACHED - YPH
OLTC RAISE COMMAND - YPH
OLTC LOWER COMMAND - YPH
A OIL FLOW SENSITIVE VALVE ALARM - YPH None 1 DIGITAL INPUT BOARD DIU2xx
A LOW OIL FLOW/REVERSE FLOW - YPH None 1 DIGITAL INPUT BOARD DIU2xx
A K 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 12 SPE_HLA_Unhlthy_Hlthy SPS 765kV B712_ICT PROTECTION_PANEL BCUT Healthy Unhealthy UH_HL_BCUT Transmitted to IEC CONTROL1;GGIO2 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 13 SPE_HLA_Unhlthy_Hlthy SPS 765kV B712_ICT PROTECTION_PANEL 64IOX RELAY Healthy Unhealthy UH_HL_64IOX Transmitted to IEC CONTROL1;GGIO2 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 14 SPE_HLA_Unhlthy_Hlthy SPS 765kV B712_ICT PROTECTION_PANEL PUB RELAY Healthy Unhealthy UH_HL_PU-B Transmitted to IEC CONTROL1;GGIO2 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 15 SPE_HLA_Healthy_Flty SPS 765kV B712_ICT PROTECTION_PANEL CB_TC-2 Faulty Healthy HL_FT_CB TC-2 Transmitted to IEC CONTROL1;GGIO2 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A K 16 SPE_HLA_OS_IS SPS 765kV B712_ICT PSD PSD In Service Out Service IN_OT_PSD Transmitted to IEC CONTROL1;GGIO4 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 0
Digital Outputs Board Slot E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A E 1 DC_SBO_Open_Close_2 DPC 765kV B712_ICT 52 CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI9 CO;Pos;sboClass;DPC 54 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 2 DC_SBO_Open_Close_2 DPC 765kV B712_ICT 52 CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI9 CO;Pos;sboClass;DPC 54 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 3 SC_DE_NotPerm_Perm_2 SPC 765kV B712_ICT PROTECTION_PANEL TO PUA RESET XX_XX_CB PUA Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO1;ctlVal;DPC 19 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 4 SC_DE_NotPerm_Perm_2 SPC 765kV B712_ICT PROTECTION_PANEL TO PUB RESET XX_XX_CB PUB Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO2;ctlVal;DPC 20 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 5 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM AT TROUBLE ANOLOG S/L SWITCHING RESET XX_XX_AT TRBL1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO10;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 6 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM AT TROUBLE ANOLOG S/L SWITCHING RESET XX_XX_AT TRBL2 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO11;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 7 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM AT TROUBLE ANOLOG S/L SWITCHING RESET XX_XX_AT TRBL3 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO12;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 8 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM AT TROUBLE ANOLOG S/L SWITCHING RESET XX_XX_AT TRBL4 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO13;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 9 DC_SBO_Open_Close_2 DPC 765kV B712_ICT RTCC_PANNEL OLTC Open LO_RS_OLTC Transmitted to IEC CONTROL2;GGIO1 CO;DPCSO1;sboClass;DPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A E 10 DC_SBO_Open_Close_2 DPC 765kV B712_ICT RTCC_PANNEL OLTC Close LO_RS_OLTC Transmitted to IEC CONTROL2;GGIO1 CO;DPCSO1;sboClass;DPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 1
Digital Outputs Board Slot F
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A F 1 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89A CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 55 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 2 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89A CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 55 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 3 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM 89A IL PERM RESET XX_XX_89A Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO1;ctlVal;DPC 297 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 4 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM 89AE IL PERM RESET XX_XX_89AE Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO8;ctlVal;DPC 298 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 5 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI5 CO;Pos;sboClass;DPC 56 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 6 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI5 CO;Pos;sboClass;DPC 56 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 7 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM 89B IL PERM RESET XX_XX_89B Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO14;ctlVal;DPC 299 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 8 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM 89BE IL PERM RESET XX_XX_89BE Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO15;ctlVal;DPC 300 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A F 10 SC_DE_Reset_Set_2 SPC 765kV B712_ICT PSD PSD BYPASS Set XX_XX_PSD Transmitted to IEC CONTROL1;GGIO4 CO;SPCSO1;ctlVal;DPC 284 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 2
Digital Outputs Board Slot G
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A G 1 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89T1-R CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI6 CO;Pos;sboClass;DPC 58 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 2 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89T1-R CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI6 CO;Pos;sboClass;DPC 58 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 3 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM 89T1-R IL PERM RESET XX_XX_89T1-R PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO6;ctlVal;DPC 302 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 4 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM 89T1E-R IL PERM RESET XX_XX_89TE1-R PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO16;ctlVal;DPC 304 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 5 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89T1-Y CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI7 CO;Pos;sboClass;DPC 59 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 6 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89T1-Y CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI7 CO;Pos;sboClass;DPC 59 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 7 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM 89T1-Y IL PERM RESET XX_XX_89T1-Y PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO17;ctlVal;DPC 303 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 8 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM 89TE1-Y IL PERM RESET XX_XX_89TE1-Y PH Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO18;ctlVal;DPC 276 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A G 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 3
Digital Outputs Board Slot H
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A H 1 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89T1-B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI8 CO;Pos;sboClass;DPC 57 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 2 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89T1-B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI8 CO;Pos;sboClass;DPC 57 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 3 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM 89T-B IL PERM RESET XX_XX_89T1-B Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO19;ctlVal;DPC 301 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 4 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM 89TE1-B IL PERM RESET XX_XX_89TE1-B Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO2;ctlVal;DPC 275 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 5 SC_DE_Reset_Reset_2 SPC 765kV B712_ICT INTERLOCK_PERM TO AT SELECT RESET XX_SL_AT Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO7;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 6 SC_DE_Reset_Set_3 SPC 765kV B712_ICT INTERLOCK_PERM TO AT DESELECT Set XX_DL_AT Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO9;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A H 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 4
Digital Outputs Board Slot I
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A I 1 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89TS-2R & 3R CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 61 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 2 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89TS-2R & 3R CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 61 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 3 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM 89TS 2R3R IL PERM RESET XX_XX_89TS-2R3R Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO3;ctlVal;DPC 278 NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 4 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89TS-2Y & 3Y CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 62 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 5 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89TS-2Y & 3Y CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 62 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 6 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM 89TS 2Y3Y IL PERM RESET XX_XX_89TS-2Y3Y Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO4;ctlVal;DPC 279 NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 7 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89TS-2B & 3B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 60 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 8 DC_SBO_Open_Close_1 DPC 765kV B712_ICT 89TS-2B & 3B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 60 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 9 SC_DE_NotPerm_Perm_1 SPC 765kV B712_ICT INTERLOCK_PERM 89TS_2B3B IL PERM RESET XX_XX_89TS-2B23B Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO5;ctlVal;DPC 277 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A I 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
ANALOG INPUT BOARD AIU21x
Analog Input Board Number 0
Analog Input Board Slot D
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT TRAFO_MB_R-PH WTI TEMP MONITOR HV WDG TEMP R-PH 0.0 80.0 WTI_TEMP_HV_R-PH Transmitted to IEC CONTROL1;GGIO3 MX;AnIn2;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 2 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT TRAFO_MB_R-PH WTI TEMP MONITOR IV WDG TEMP R-PH 0.0 80.0 WTI_TEMP_IV_R-PH Transmitted to IEC CONTROL1;GGIO3 MX;AnIn3;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 3 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT TRAFO_MB_R-PH WTI TEMP MONITOR LV WDG TEMP R-PH 0.0 80.0 WTI_TEMP_LV_R-PH Transmitted to IEC CONTROL1;GGIO3 MX;AnIn4;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 4 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT TRAFO_MB_R-PH WTI TEMP MONITOR TOP OIL TEMP R-PH 0.0 80.0 WTI_TEMP_OL_R-PH Transmitted to IEC CONTROL1;GGIO3 MX;AnIn5;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 5 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT TRAFO_MB_R-PH TAP SIGNAL SELSYN TRANSMITTER R-PH 1.0 17.0 TAP_SELSYN_R-PH Transmitted to IEC CONTROL1;GGIO3 MX;AnIn1;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 6 SPARE 6 ANALOG INPUT BOARD AIU21x
A 7 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT TRAFO_MB_Y-PH WTI TEMP MONITOR HV WDG TEMP Y-PH 0.0 80.0 WTI_TEMP_HV_Y-PH Transmitted to IEC CONTROL1;GGIO5 MX;AnIn1;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 8 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT TRAFO_MB_Y-PH WTI TEMP MONITOR IV WDG TEMP Y-PH 0.0 80.0 WTI_TEMP_IV_Y-PH Transmitted to IEC CONTROL1;GGIO5 MX;AnIn2;mag;MV 6 ANALOG INPUT BOARD AIU21x
CT/VT ANALOG INPUT BOARD TMU2x0
CT/VT Board Number 0
CT/VT Board Slot Q
CT/VT Board Model TMU220
Nominal Current 1 (1A/5A)
Nominal Voltage 63.50 [1V … 500V]
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A DF MV_HLa_Frequency_2 Hz 765kV B712_ICT SYNCH DATA FREQUENCY DIFFERENCE 0.0 2.0 FREQUENCY DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifHzClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DV MV_HLa_Voltage_1 kV 765kV B712_ICT SYNCH DATA VOLTAGE DIFFERENCE 0.0 530.0 VOLTAGE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifVClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Dj MV_hla_PhaseDiff ˚ 765kV B712_ICT SYNCH DATA PHASE DIFFERENCE 0.0 360.0 PHASE ANGLE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifAngClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ia MV_HLa_AuxCurrent A 765kV B712_ICT METERING I-R PHASE CURRENT 0.0 2400.0 IR PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ib MV_HLa_AuxCurrent A 765kV B712_ICT METERING I-Y PHASE CURRENT 0.0 2400.0 IY PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ic MV_HLa_Frequency_1 Hz 765kV B712_ICT METERING I-B PHASE CURRENT 0.0 2400.0 IB PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsC;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vb MV_HLa_Voltage_1 kV 765kV B712_ICT SYNCH DATA INCOMING SUPPLY 0.0 530.0 INCOMING SUPPLY Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;PhV;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uab MV_HLa_Voltage kV 765kV B712_ICT METERING R-Y VOLTAGE 0.0 918.0 R-Y VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsAB;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ubc MV_HLa_Voltage kV 765kV B712_ICT METERING Y-B VOLTAGE 0.0 918.0 Y-B VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsBC;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uca MV_HLa_Voltage kV 765kV B712_ICT METERING B-R VOLTAGE 0.0 918.0 B-R VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsCA;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar MV_HLa_Voltage_1 kV 765kV B712_ICT SYNCH DATA RUNNING SUPPLY-1 0.0 530.0 RUNNING SPLY-1 Transmitted to IEC MEASUREMENT1;barMMXU1 MX;PhV;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Freq (Line) MV_HLa_Frequency Hz 765kV B712_ICT METERING FREQUENCY 45.0 55.0 FREQUENCY Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;Hz;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A P total (MW) MV_HLa_ActPower MW 765kV B712_ICT METERING ACTIVE POWER -3179.952 3179.952 ACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotW;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Q total (Mvar) MV_HLa_ReactPower MVAr 765kV B712_ICT METERING REACTIVE POWER -3179.952 3179.952 REACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotVAr;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar RMS 2 value of the busbar voltage phase MV_HLa_Voltage_1 kV 765kV B712_ICT SYNCH DATA RUNNING SUPPLY-2 0.0 530.0 RUNNING SPLY-2 Transmitted to IEC MEASUREMENT1;GGIO1 MX;AnIn1;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A cos ft : Power factor MV_HLa_PowerFactor 765kV B712_ICT METERING POWER FACTOR -1.2 1.2 POWER FACTOR Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotPF;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPE_HLa_Reset_Set SPS 765kV B712_ICT SYNCH FUNCTION CLOSE ORDER Set Reset RS_ST_CLS ODR Transmitted to IEC CONTROL1;RSYN1 ST;ClsOpSt;stVal;SPS None IntManualCSFct CS_CloseOrderState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPE_HLa_Reset_Set SPS 765kV B712_ICT SYNCH FUNCTION POSSIBLE CLOSING Set Reset RS_ST_POS CLS Transmitted to IEC CONTROL1;RSYN1 ST;Rel;stVal;SPS 229; None IntManualCSFct CS_AuthoState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPE_HLa_Reset_Set SPS 765kV B712_ICT SYNCH FUNCTION RS_ST_V CHOICE Set Reset RS_ST_V CHOICE Transmitted to IEC CONTROL1;RSYN1 ST;BusVC;stVal;SPS 230<; None IntManualCSFct CS_BusBarVChoice_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 52 | OE_CL_CONTROL Close interlock result SPS Permissive Not Permissive Close intlk SPS Transmitted to IEC CONTROL3;CILO1 ST;EnaCls;stVal;SPS None CB CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPE_HLa_Reset_Set SPS 765kV B712_ICT 52 | OE_CL_CONTROL CLOSE ORDER Set Reset CLOSE ORDER Transmitted to IEC CONTROL1;CSWI9 ST;ClsOrd;general;general;ACT None 19;20 CB CloseOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89A | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO4 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO5 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89T1-B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL3;CILO8 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89T1-R | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO6 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89T1-Y | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO7 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89TS-2B & 3B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO3 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89TS-2R & 3R | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89TS-2Y & 3Y | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO2 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPE_HLA_on_off SPS 765kV B712_ICT SYNCH FUNCTION ON/OFF SECONDARY SPS On Off RS_ST_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 ST;EnaSec;origin;SPC None 120 IntManualCSFct CS_OnOff_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPE_HLa_Reset_Set SPS 765kV B712_ICT SYNCH FUNCTION PRESENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF U PRES Transmitted to IEC CONTROL1;RSYN1 ST;VRefInd;stVal;SPS 229; None IntManualCSFct CS_VoltageRefPresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPE_HLa_Reset_Set SPS 765kV B712_ICT SYNCH FUNCTION ABSENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF. U ABS Transmitted to IEC CONTROL1;RSYN1 ST;VRefAbs;stVal;SPS 229; None IntManualCSFct CS_VoltageRefAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 17 SPE_HLa_Reset_Set SPS 765kV B712_ICT SYNCH FUNCTION VOLT ABSENCE Set Reset RS_ST_VOLT ABS Transmitted to IEC CONTROL1;RSYN1 ST;VAbs;stVal;SPS 229; None IntManualCSFct CS_VoltageAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 18 SPE_HLa_Reset_Set SPS 765kV B712_ICT SYNCH FUNCTION VOLT PRESENCE Set Reset RS_ST_VOLT PRES Transmitted to IEC CONTROL1;RSYN1 ST;VP;stVal;SPS 229; None IntManualCSFct CS_VoltagePresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 19 SPE_HLa_Reset_Close SPS 765kV B712_ICT 89T POS_CLS_FBD Close Reset RS_CL_POS Transmitted to IEC CONTROL2;GAPC3 ST;IndSys2;stVal;SPS 202<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 20 SPE_HLA_Reset_Open SPS 765kV B712_ICT 89T POS_OPN_FBD Open Normal RS_OE_POS Transmitted to IEC CONTROL2;GAPC3 ST;IndSys1;stVal;SPS 202<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 21 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89TE1-B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI2 ST;IndSys1;stVal;SPS 212<; None 275 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 22 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89TE1-Y INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI1 ST;IndSys1;stVal;SPS 214<; None 276 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 23 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89TS-2B & 3B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI3 ST;IndSys1;stVal;SPS 215<; None 277 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 24 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89TS-2R & 3R INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI1 ST;IndSys1;stVal;SPS 218<; None 278 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 25 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89TS-2Y & 3Y INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI2 ST;IndSys1;stVal;SPS 221<; None 279 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 26 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT AT_SELECTION AT_SELECT DISCREPANCY Alarm Normal NL_AL_AT_SEL Transmitted to IEC CONTROL1;GAPC2 ST;IndSys9;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 27 SPE_HLa_Reset_DSelect SPS 765kV B712_ICT AT_SELECTION AT B-PH Deselected Reset T_B-PH_DE-SEL Transmitted to IEC CONTROL1;GAPC2 ST;IndSys3;stVal;SPS 224;224<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 28 SPE_HLa_Reset_Select SPS 765kV B712_ICT AT_SELECTION AT B-PH Selected Reset T_B-PH_SEL Transmitted to IEC CONTROL1;GAPC2 ST;IndSys4;stVal;SPS 224;224<;238; None Yes 1 C264 SELF GENERATED DIGITAL INFORMATION
A 29 SPE_HLa_Reset_DSelect SPS 765kV B712_ICT AT_SELECTION AT R-PH Deselected Reset T_R-PH_DE-SEL Transmitted to IEC CONTROL1;GAPC2 ST;IndSys5;stVal;SPS 224;224<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 30 SPE_HLa_Reset_Select SPS 765kV B712_ICT AT_SELECTION AT R-PH Selected Reset T_R-PH_SEL Transmitted to IEC CONTROL1;GAPC2 ST;IndSys6;stVal;SPS 224;224<;238; None Yes 1 C264 SELF GENERATED DIGITAL INFORMATION
A 31 SPE_HLa_Reset_DSelect SPS 765kV B712_ICT AT_SELECTION AT Y-PH Deselected Reset T_Y-PH_DE-SEL Transmitted to IEC CONTROL1;GAPC2 ST;IndSys7;stVal;SPS 224;224<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 32 SPE_HLa_Reset_Select SPS 765kV B712_ICT AT_SELECTION AT Y-PH Selected Reset T_Y-PH_SEL Transmitted to IEC CONTROL1;GAPC2 ST;IndSys8;stVal;SPS 224;224<;238; None Yes 1 C264 SELF GENERATED DIGITAL INFORMATION
A 33 SPE_HLa_Reset_DSelect SPS 765kV B712_ICT AT_SELECTION AT-1 Deselected Reset T-1_DE-SELECT Transmitted to IEC CONTROL1;GAPC2 ST;IndSys2;stVal;SPS 224<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 34 SPE_HLa_Reset_Select SPS 765kV B712_ICT AT_SELECTION AT-1 Selected Reset T-1_SELECT Transmitted to IEC CONTROL1;GAPC2 ST;IndSys1;stVal;SPS 224<; None 280;281;282;283 1 C264 SELF GENERATED DIGITAL INFORMATION
A 35 SPE_HLa_Reset_Set SPS 765kV B712_ICT PROTECTION_PANEL 4_X_52_OP-ORDER Set Reset 4_X_52_OP-ORDER Transmitted to IEC CONTROL1;GAPC1 ST;IndSys1;stVal;SPS 226<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 36 SPE_HLa_Reset_Set SPS 765kV B712_ICT PROTECTION_PANEL 4_Y_52_OP-ORDER Set Reset 4_Y_52_OP-ORDER Transmitted to IEC CONTROL1;GAPC1 ST;IndSys2;stVal;SPS 226<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 37 SPE_HLA_Reset_Alarm_Goose SPS 765kV B712_ICT PROTECTION_PANEL GOOSE RECEIPT FAIL/TROUBLE Alarm Reset GOOSE RECIEPT FL Transmitted to IEC CONTROL1;GAPC1 ST;IndSys3;stVal;SPS 227<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 38 SPE_HLa_Reset_Set SPS 765kV B712_ICT PSD PSD BYPASS Set Reset RS_ST_PSD BYPASS Transmitted to IEC CONTROL1;GAPC3 ST;IndSys1;stVal;SPS 228<; None 284 1 C264 SELF GENERATED DIGITAL INFORMATION
A 39 SPE_HLa_Reset_Set SPS 765kV B712_ICT SYNCH DATA CLOSE PERMISSIVE Set Reset RS_ST_CB CLOSE Transmitted to IEC CONTROL2;GAPC2 ST;IndSys5;stVal;SPS 229<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 40 SPE_HLa_Reset_Set SPS 765kV B712_ICT SYNCH DATA DEAD INCOMING DEAD RUNNING Set Reset RS_ST_DINC_DRUN Transmitted to IEC CONTROL2;GAPC2 ST;IndSys4;stVal;SPS 229<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 41 SPE_HLa_Reset_Set SPS 765kV B712_ICT SYNCH DATA DEAD INCOMING LIVE RUNNING Set Reset RS_ST_DINC_LRUN Transmitted to IEC CONTROL2;GAPC2 ST;IndSys3;stVal;SPS 229<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 42 SPE_HLa_Reset_Set SPS 765kV B712_ICT SYNCH DATA LIVE INCOMING DEAD RUNNING Set Reset RS_ST_LINC_DRUN Transmitted to IEC CONTROL2;GAPC2 ST;IndSys2;stVal;SPS 229<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 43 SPE_HLa_Reset_Set SPS 765kV B712_ICT SYNCH DATA LIVE INCOMING LIVE RUNNING Set Reset RS_ST_LINC_LRUN Transmitted to IEC CONTROL2;GAPC2 ST;IndSys1;stVal;SPS 229<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 44 SPE_HLa_Reset_Set SPS 765kV B712_ICT 52 | OE_CL_CONTROL OPEN ORDER Set Reset OPEN ORDER Transmitted to IEC CONTROL1;CSWI9 ST;OpnOrd;general;general;ACT 226; None CB OpenOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 45 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89A INTERLOCK Permissive Not Permissive MP_PE_I/L Transmitted to IEC CONTROL1;CSWI4 ST;IndSys1;stVal;SPS 194<; None 297 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 46 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89A | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO4 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 47 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89AE INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI3 ST;IndSys1;stVal;SPS 197<; None 298 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 48 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI5 ST;IndSys1;stVal;SPS 198<; None 299 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 49 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO5 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 50 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89BE INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI4 ST;IndSys1;stVal;SPS 201<; None 300 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 51 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89T1-B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI8 ST;IndSys1;stVal;SPS 203<; None 301 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 52 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89T1-B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL3;CILO8 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 53 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89T1-R INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI6 ST;IndSys1;stVal;SPS 206<; None 302 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 54 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89T1-R | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO6 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 55 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89T1-Y INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI7 ST;IndSys1;stVal;SPS 209<; None 303 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 56 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89T1-Y | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO7 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 57 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89TE1-R INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI5 ST;IndSys1;stVal;SPS 213<; None 304 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 58 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89TS-2B & 3B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO3 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 59 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89TS-2R & 3R | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 60 SPE_HLa_Notper_Perm SPS 765kV B712_ICT 89TS-2Y & 3Y | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO2 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 61 SPS_hla_Set_Reset SPS 765kV B712_ICT Order running on the bay Set Reset Order running Transmitted to IEC CONTROL3;GBAY1 ST;OrdRun;stVal;SPS None OrderInProgress 1 C264 SELF GENERATED DIGITAL INFORMATION
A 62 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Y_52 POS Open 4_Y_52 POS Transmitted to IEC CONTROL3;GAPC1 ST;DPCSO1;stVal;DPS 203;204;205;206;207;208;209;210;211;215;216;217;218;219;220;221;222;223; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 63 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Y_52 POS Closed 4_Y_52 POS Transmitted to IEC CONTROL3;GAPC1 ST;DPCSO1;stVal;DPS 203;204;205;206;207;208;209;210;211;215;216;217;218;219;220;221;222;223; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 64 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_52 POS Open 4_Z_52 POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO5;stVal;DPS 203;204;205;206;207;208;209;210;211;215;216;217;218;219;220;221;222;223; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 65 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_52 POS Closed 4_Z_52 POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO5;stVal;DPS 203;204;205;206;207;208;209;210;211;215;216;217;218;219;220;221;222;223; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 66 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TB POS Open 4_Z_TB POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO11;stVal;DPS 212; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 67 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TB POS Closed 4_Z_TB POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO11;stVal;DPS 212; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 68 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TEB POS Open 4_Z_TEB POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO8;stVal;DPS 203;204;205; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 69 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TEB POS Closed 4_Z_TEB POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO8;stVal;DPS 203;204;205; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 70 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TER POS Open 4_Z_TER POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO6;stVal;DPS 206;207;208; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 71 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TER POS Closed 4_Z_TER POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO6;stVal;DPS 206;207;208; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 72 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TEY POS Open 4_Z_TEY POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO7;stVal;DPS 209;210;211; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 73 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TEY POS Closed 4_Z_TEY POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO7;stVal;DPS 209;210;211; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 74 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TR POS Open 4_Z_TR POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO9;stVal;DPS 213; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 75 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TR POS Closed 4_Z_TR POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO9;stVal;DPS 213; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 76 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TSB POS Open 4_Z_TSB POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO4;stVal;DPS 224; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 77 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TSB POS Closed 4_Z_TSB POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO4;stVal;DPS 224; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 78 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TSR POS Open 4_Z_TSR POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO2;stVal;DPS 224; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 79 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TSR POS Closed 4_Z_TSR POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO2;stVal;DPS 224; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 80 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TSY POS Open 4_Z_TSY POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO3;stVal;DPS 224; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 81 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TSY POS Closed 4_Z_TSY POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO3;stVal;DPS 224; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 82 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TY POS Open 4_Z_TY POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO10;stVal;DPS 214; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 83 DP_HLA_CBOpen_Close DPS 765kV 400kV ICT1 GOOSE 4_Z_TY POS Closed 4_Z_TY POS Transmitted to IEC CONTROL4;GAPC1 ST;DPCSO10;stVal;DPS 214; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 84 DP_HLA_CBOpen_Close DPS 765kV B712_ICT 52 COMPUTED SWITCH POSITION Open OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI9 ST;Pos;origin;DPC 167;194;195;196;198;199;200;203;204;205;206;207;208;209;210;211;215;216;217;218;219;220;221;222;223;233;234; None 54 225 CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 85 DP_HLA_CBOpen_Close DPS 765kV B712_ICT 52 COMPUTED SWITCH POSITION Closed OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI9 ST;Pos;origin;DPC 167;194;195;196;198;199;200;203;204;205;206;207;208;209;210;211;215;216;217;218;219;220;221;222;223;233;234; None 54 225 CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 86 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89T POSITION Open OE_CL_POS Transmitted to IEC CONTROL2;GAPC3 ST;DPCSO1;stVal;DPS 182; None Yes 1 C264 SELF GENERATED DIGITAL INFORMATION
A 87 DP_HLA_ ISOOpen_Close DPS 765kV B712_ICT 89T POSITION Closed OE_CL_POS Transmitted to IEC CONTROL2;GAPC3 ST;DPCSO1;stVal;DPS 182; None Yes 1 C264 SELF GENERATED DIGITAL INFORMATION
A 88 DP_HLa_LocRem_Bay DPS 765kV B712_ICT BCU MODE Local LC_RM_MODE Transmitted to IEC CONTROL3;GBAY1 ST;Loc;origin;DPC None 63 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 89 DP_HLa_LocRem_Bay DPS 765kV B712_ICT BCU MODE Remote LC_RM_MODE Transmitted to IEC CONTROL3;GBAY1 ST;Loc;origin;DPC None 63 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 90 DP_HLA_CBOpen_Close DPS 765kV B712_ICT PROTECTION_PANEL 4_X_52_OP-ORDER Open 4_X_52_OP-ORDER Transmitted to IEC CONTROL1;GAPC1 ST;DPCSO1;stVal;DPS 226<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 91 DP_HLA_CBOpen_Close DPS 765kV B712_ICT PROTECTION_PANEL 4_X_52_OP-ORDER Closed 4_X_52_OP-ORDER Transmitted to IEC CONTROL1;GAPC1 ST;DPCSO1;stVal;DPS 226<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 92 DP_HLA_CBOpen_Close DPS 765kV B712_ICT RTCC_PANNEL OLTC Open OLTC Transmitted to IEC CONTROL2;GAPC1 ST;DPCSO1;stVal;DPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 93 DP_HLA_CBOpen_Close DPS 765kV B712_ICT RTCC_PANNEL OLTC Closed OLTC Transmitted to IEC CONTROL2;GAPC1 ST;DPCSO1;stVal;DPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 94 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SC_DE_Off_On_1 SPC 765kV B712_ICT SYNCH FUNCTION ON/OFF SECONDARY CONTROL SPC On Off OF_ON_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 CO;EnaSec;ctlVal;DPC 120 IntManualCSFct CS_CtrlOnOff_SPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SC_DE_Reset_Set_2 SPC 765kV B712_ICT AT_SELECTION AT TROUBLE ANALOG S/L SWITCH Set XX_XX_AT TRBLE1 Transmitted to IEC CONTROL1;GAPC2 CO;SPCSO1;ctlVal;DPC 281 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SC_DE_Reset_Set_2 SPC 765kV B712_ICT AT_SELECTION AT TROUBLE ANALOG S/L SWITCH Set XX_XX_AT TRBLE2 Transmitted to IEC CONTROL1;GAPC2 CO;SPCSO2;ctlVal;DPC 282 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SC_DE_Reset_Set_2 SPC 765kV B712_ICT AT_SELECTION AT TROUBLE ANALOG S/L SWITCH Set XX_XX_AT TRBLE3 Transmitted to IEC CONTROL1;GAPC2 CO;SPCSO3;ctlVal;DPC 283 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SC_DE_Reset_Set_2 SPC 765kV B712_ICT AT_SELECTION AT TROUBLE ANALOG S/L SWITCH Set XX_XX_AT TRBLE4 Transmitted to IEC CONTROL1;GAPC2 CO;SPCSO4;ctlVal;DPC 280 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SC_DE_Set SPC 765kV B712_ICT PSD PSD OUT FROM HMI Set XX_ST_PSD OUT H Transmitted to IEC CONTROL1;GAPC3 CO;SPCSO1;ctlVal;DPC 228; 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 DC_DE_LocRem_BayCtrl DPC 765kV B712_ICT MODE CONTROL Local MODE CONTROL Transmitted to IEC CONTROL2;GBAY1 CO;Loc;ctlVal;DPC 63 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 DC_DE_LocRem_BayCtrl DPC 765kV B712_ICT MODE CONTROL Remote MODE CONTROL Transmitted to IEC CONTROL2;GBAY1 CO;Loc;ctlVal;DPC 63 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 MV 765kV B712_ICT CB_COUNTER Count_Close 0.0 10000.0 Count_Close Transmitted to IEC CONTROL3;GAPC3 MX;AnIn2;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 MV 765kV B712_ICT CB_COUNTER Count_Open 0.0 10000.0 Count_Open Transmitted to IEC CONTROL3;GAPC3 MX;AnIn1;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 MV_hla_Temp_1 ˚ Cel 765kV B712_ICT TRAFO_MB_R-PH AC KIOSK TEMP 0.0 100.0 AC KIOSK TEMP Transmitted to IEC CONTROL3;GAPC2 MX;AnIn1;mag;MV 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
MiCOM C264 DESCRIPTION
Computer Name B712_AT T GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) C264C Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 0
Digital Inputs Board Slot H
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A H 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A H 2 SPE_HLA_Normal_Fail SPS 765kV B712_ICT T PROTECTION SPARE AT DC -1/2 SUPPLY FAIL Fail Normal NL_FL_DC SUP1 Transmitted to IEC CONTROL1;GGIO3 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 3 SPE_HLA_OS_IS SPS 765kV B712_ICT T PSD DEVICE In Service Out Service RD_NR_DEVICE Transmitted to IEC CONTROL1;GGIO2 ST;Ind1;stVal;SPS 228; None Yes 1 DIGITAL INPUT BOARD DIU2xx
A H 4 SPE_HLA_Normal_Fail SPS 765kV B712_ICT T PSD SENSOR/CB VOLTAGE/SYNCH OPTN Fail Normal NL_AL_PSD SEN Transmitted to IEC CONTROL1;GGIO2 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A H 6 SPS_HLA_Nok_OK SPS 765kV B712_ICT T PSD DEVICE OK Not OK NL_AL_PSD Transmitted to IEC CONTROL1;GGIO2 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 7 SPE_HLA_Unhlthy_Hlthy SPS 765kV B712_ICT T PROTECTION 87 RELAY Healthy Unhealthy UH_HL_87 RELAY Transmitted to IEC CONTROL1;GGIO3 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 8 SPE_HLA_Unhlthy_Hlthy SPS 765kV B712_ICT T PROTECTION 64 RELAY Healthy Unhealthy UH_HL_64 RELAY Transmitted to IEC CONTROL1;GGIO3 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 9 SPE_HLA_Unhlthy_Hlthy SPS 765kV B712_ICT T PROTECTION 64S RELAY Healthy Unhealthy UH_HL_64S RELAY Transmitted to IEC CONTROL1;GGIO3 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 10 SPE_HLA_Normal_Fail SPS 765kV B712_ICT T PROTECTION DC SOURCE-1 Fail Normal NL_FL_DC SRC-1 Transmitted to IEC CONTROL1;GGIO3 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A H 12 SPE_HLA_Normal_Fail SPS 765kV B712_ICT T PROTECTION DC SOURCE-2 Fail Normal NL_FL_DC SRC-2 Transmitted to IEC CONTROL1;GGIO3 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 13 DP_HLA_Trip_Closed DPS 765kV B712_ICT T PROTECTION EMERGENCY/MANUAL Closed TP_CL_EMRG/MAN Transmitted to IEC CONTROL1;GGIO3 ST;DPCSO1;stVal;DPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 14 DP_HLA_Trip_Closed DPS 765kV B712_ICT T PROTECTION EMERGENCY/MANUAL Trip TP_CL_EMRG/MAN Transmitted to IEC CONTROL1;GGIO3 ST;DPCSO1;stVal;DPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A H 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 1
Digital Inputs Board Slot G
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 232; None 1 DIGITAL INPUT BOARD DIU2xx
A None 1 DIGITAL INPUT BOARD DIU2xx
A 0 3 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT T TRAFO_MB_B-PH HV WINDING TEMP HIGH-B PH Alarm Normal NL_AL_HV WDG TMP Transmitted to IEC CONTROL1;GGIO1 ST;Ind13;stVal;SPS 232; None 1 DIGITAL INPUT BOARD DIU2xx
A 0 4 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT T TRAFO_MB_B-PH IV WDG TEMP HIGH ALARM B PH Alarm Normal NL_AL_IV TEMP Transmitted to IEC CONTROL1;GGIO1 ST;Ind11;stVal;SPS 232; None 1 DIGITAL INPUT BOARD DIU2xx
A 0 5 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT T TRAFO_MB_B-PH LV WDG TEMP HIGH ALARM B PH Alarm Normal NL_AL_LV TEMP Transmitted to IEC CONTROL1;GGIO1 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A 0 6 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT T TRAFO_MB_B-PH OTI Alarm Normal NL_AL_OTI Transmitted to IEC CONTROL1;GGIO1 ST;Ind14;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A 0 7 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT T TRAFO_MB_B-PH MAIN TANK 1 LOW LEVEL B PH Alarm Normal NL_AL_MOG B PH L Transmitted to IEC CONTROL1;GGIO1 ST;Ind2;stVal;SPS 232; None 1 DIGITAL INPUT BOARD DIU2xx
A 0 8 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT T TRAFO_MB_B-PH MAIN TANK 1 HIGH LEVEL B PH Alarm Normal NL_AL_MOG B PH H Transmitted to IEC CONTROL1;GGIO1 ST;Ind16;stVal;SPS 232; None 1 DIGITAL INPUT BOARD DIU2xx
A 0 9 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT T TRAFO_MB_B-PH MAIN TANK 2 LOW LEVEL B PH Alarm Normal NL_AL_MOG2 BPH L Transmitted to IEC CONTROL1;GGIO1 ST;Ind9;stVal;SPS 232; None 1 DIGITAL INPUT BOARD DIU2xx
A 0 10 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT T TRAFO_MB_B-PH MAIN TANK 2 HIGH LEVEL B PH Alarm Normal NL_AL_MOG2 BPH H Transmitted to IEC CONTROL1;GGIO1 ST;Ind15;stVal;SPS 232; None 1 DIGITAL INPUT BOARD DIU2xx
A 0 11 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT T TRAFO_MB_B-PH OFI 1 2 Alarm Normal NL_AL_OFI Transmitted to IEC CONTROL1;GGIO1 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A 0 12 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT T TRAFO_MB_B-PH OFI 3 4 Alarm Normal NL_AL_OFI 3 4 Transmitted to IEC CONTROL1;GGIO1 ST;Ind1;stVal;SPS 232; None 1 DIGITAL INPUT BOARD DIU2xx
OLTC MOTOR OVERLOAD - BPH
TAP CHANGE IN PROGRESS - BPH
TAP CHANGE IN COMPLETE - BPH
OLTC IN LOCAL - BPH
OLTC IN REMOTE - BPH
TAP CHANGE CONTROL SUPPLY FAIL - BPH
LOWEST POSITION REACHED - BPH
HIGHESHT POSITION REACHED - BPH
OLTC RAISE COMMAND - BPH
OLTC LOWER COMMAND - BPH
A OIL FLOW SENSITIVE VALVE ALARM - BPH None 1 DIGITAL INPUT BOARD DIU2xx
A LOW OIL FLOW/REVERSE FLOW - BPH None 1 DIGITAL INPUT BOARD DIU2xx
A 0 13 SPE_HLA_Normal_Fail SPS 765kV B712_ICT T TRAFO_MB_B-PH FAN GROUP-1/2/3/4-B PH Fail Normal NL_FL_FAN Transmitted to IEC CONTROL1;GGIO1 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A 0 14 SPE_HLA_Normal_Fail SPS 765kV B712_ICT T TRAFO_MB_B-PH PUMP-1/2/3/4/5/6 -B PH Fail Normal NL_FL_PUMP Transmitted to IEC CONTROL1;GGIO1 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A 0 15 SPE_HLA_Normal_Fail SPS 765kV B712_ICT T TRAFO_MB_B-PH CONTROL SUPPLY-B PH Fail Normal NL_FL_CNTRL SUP Transmitted to IEC CONTROL1;GGIO1 ST;Ind10;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A 0 16 SPE_HLA_Reset_Optd SPS 765kV B712_ICT T TRAFO_MB_B-PH FIRE PROTECTION-B PH Operated Reset RS_OP_FIRE PRO Transmitted to IEC CONTROL1;GGIO1 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
ANALOG INPUT BOARD AIU21x
Analog Input Board Number 0
Analog Input Board Slot C
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT T TRAFO_MB_Y-PH WTI TEMP MONITOR LV WDG TEMP Y-PH 0.0 80.0 WTI_TEMP_LV_Y-PH Transmitted to IEC CONTROL1;GGIO5 MX;AnIn1;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 2 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT T TRAFO_MB_Y-PH WTI TEMP MONITOR TOP OIL TEMP Y-PH 0.0 80.0 WTI_TEMP_OL_Y-PH Transmitted to IEC CONTROL1;GGIO5 MX;AnIn2;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 3 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT T TRAFO_MB_Y-PH TAP SIGNAL SELSYN TRANSMITTER Y-PH 1.0 17.0 TAP_SELSYN_Y-PH Transmitted to IEC CONTROL1;GGIO5 MX;AnIn3;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 4 SPARE 6 ANALOG INPUT BOARD AIU21x
A 5 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT T TRAFO_MB_B-PH WTI TEMP MONITOR HV WDG TEMP B-PH 0.0 80.0 WTI_TEMP_HV_B-PH Transmitted to IEC CONTROL1;GGIO1 MX;AnIn2;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 6 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT T TRAFO_MB_B-PH WTI TEMP MONITOR IV WDG TEMP B-PH 0.0 80.0 WTI_TEMP_IV_B-PH Transmitted to IEC CONTROL1;GGIO1 MX;AnIn3;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 7 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT T TRAFO_MB_B-PH WTI TEMP MONITOR LV WDG TEMP B-PH 0.0 80.0 WTI_TEMP_LV_B-PH Transmitted to IEC CONTROL1;GGIO1 MX;AnIn4;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 8 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT T TRAFO_MB_B-PH WTI TEMP MONITOR TOP OIL TEMP B-PH 0.0 80.0 WTI_TEMP_OL_B-PH Transmitted to IEC CONTROL1;GGIO1 MX;AnIn5;mag;MV 6 ANALOG INPUT BOARD AIU21x
ANALOG INPUT BOARD AIU21x
Analog Input Board Number 1
Analog Input Board Slot D
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT T TRAFO_MB_B-PH TAP SIGNAL SELSYN TRANSMITTER B-PH 1.0 17.0 TAP_SELSYN_B-PH Transmitted to IEC CONTROL1;GGIO1 MX;AnIn1;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 2 SPARE 6 ANALOG INPUT BOARD AIU21x
A 3 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT T TRAFO_MB_SP-PH WTI TEMP MONITOR HV WDG TEMP SP-PH 0.0 80.0 WTI_TEMP_HV_SP-P Transmitted to IEC CONTROL1;GGIO4 MX;AnIn1;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 4 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT T TRAFO_MB_SP-PH WTI TEMP MONITOR IV WDG TEMP SP-PH 0.0 80.0 WTI_TEMP_IV_SP-P Transmitted to IEC CONTROL1;GGIO4 MX;AnIn2;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 5 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT T TRAFO_MB_SP-PH WTI TEMP MONITOR LV WDG TEMP SP-PH 0.0 80.0 WTI_TEMP_LV_SP-P Transmitted to IEC CONTROL1;GGIO4 MX;AnIn3;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 6 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT T TRAFO_MB_SP-PH WTI TEMP MONITOR TOP OIL TEMP SP-PH 0.0 80.0 WTI_TEMP_OL_SP-P Transmitted to IEC CONTROL1;GGIO4 MX;AnIn4;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 7 4/20 mA MV_hla_Temp ˚ Cel 765kV B712_ICT T TRAFO_MB_SP-PH TAP SIGNAL SELSYN TRANSMITTER SP-PH 1.0 17.0 TAP_SELSYN_SP-PH Transmitted to IEC CONTROL1;GGIO4 MX;AnIn5;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 8 SPARE 6 ANALOG INPUT BOARD AIU21x
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPE_HLA_Normal_Alarm SPS 765kV B712_ICT T TRAFO_MB_B-PH TRAFO TROUBLE Alarm Normal NL_AL_TRF TRB Transmitted to IEC CONTROL1;GAPC1 ST;IndSys1;stVal;SPS 232<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPS_hla_Set_Reset SPS 765kV B712_ICT T Order running on the bay Set Reset Order running Transmitted to IEC CONTROL1;GBAY1 ST;OrdRun;stVal;SPS None OrderInProgress 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 DP_HLa_LocRem_Bay DPS 765kV B712_ICT T BCU MODE Local LC_RM_MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 64 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 DP_HLa_LocRem_Bay DPS 765kV B712_ICT T BCU MODE Remote LC_RM_MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 64 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 DC_DE_LocRem_BayCtrl DPC 765kV B712_ICT T MODE CONTROL Local MODE CONTROL Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 64 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 DC_DE_LocRem_BayCtrl DPC 765kV B712_ICT T MODE CONTROL Remote MODE CONTROL Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 64 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
MiCOM C264 DESCRIPTION
Computer Name B712_AT_64X GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) C264C Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 0
Digital Inputs Board Slot H
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A H 1 SPE_HLA_Reset_Optd SPS 765kV B712_64IOX PROTECTION_PANEL 86A2 Operated Reset RS_OP_86A2 Transmitted to IEC CONTROL1;GGIO3 ST;Ind11;stVal;SPS 237; None 1 DIGITAL INPUT BOARD DIU2xx
A H 2 SPE_HLA_Reset_Optd SPS 765kV B712_64IOX PROTECTION_PANEL 86B2 Operated Reset RS_OP_86B2 Transmitted to IEC CONTROL1;GGIO3 ST;Ind13;stVal;SPS 237; None 1 DIGITAL INPUT BOARD DIU2xx
A H 3 SPE_HLA_Reset_Optd SPS 765kV B712_64IOX PROTECTION_PANEL 86A1 Operated Reset RS_OP_86A1 Transmitted to IEC CONTROL1;GGIO3 ST;Ind10;stVal;SPS 237; None 1 DIGITAL INPUT BOARD DIU2xx
A H 4 SPE_HLA_Reset_Optd SPS 765kV B712_64IOX PROTECTION_PANEL 86B1 Operated Reset RS_OP_86B1 Transmitted to IEC CONTROL1;GGIO3 ST;Ind12;stVal;SPS 237; None 1 DIGITAL INPUT BOARD DIU2xx
A H 5 SPE_HLA_Reset_Optd SPS 765kV B712_64IOX PROTECTION_PANEL 86 33KV SIDE Operated Reset RS_OP_86 33KV Transmitted to IEC CONTROL1;GGIO3 ST;Ind14;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A H 7 SPE_HLA_Unhlthy_Hlthy SPS 765kV B712_64IOX PROTECTION_PANEL 86A2 SUPV Healthy Unhealthy UH_HL_86A2 SUPV Transmitted to IEC CONTROL1;GGIO3 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A H 9 SPE_HLA_Unhlthy_Hlthy SPS 765kV B712_64IOX PROTECTION_PANEL 86B2 SUPV Healthy Unhealthy UH_HL_86B2 SUPV Transmitted to IEC CONTROL1;GGIO3 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A H 11 SPE_HLA_Unhlthy_Hlthy SPS 765kV B712_64IOX PROTECTION_PANEL 86 SUPV 33KV SIDE Healthy Unhealthy UH_HL_86 SUPV 33 Transmitted to IEC CONTROL1;GGIO3 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A H 13 SPE_HLA_Unhlthy_Hlthy SPS 765kV B712_64IOX PROTECTION_PANEL 86A1 SUPV Healthy Unhealthy UH_HL_86A1 SUPV Transmitted to IEC CONTROL1;GGIO3 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A H 15 SPE_HLA_Unhlthy_Hlthy SPS 765kV B712_64IOX PROTECTION_PANEL 86B1 SUPV Healthy Unhealthy UH_HL_86B1 SUPV Transmitted to IEC CONTROL1;GGIO3 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A H 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 1
Digital Inputs Board Slot G
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A G 1 SPE_HLA_Reset_Trip SPS 765kV B712_64IOX TRAFO_MB PRD-2 R-PH Trip Reset RS_TR_PRD-2 R-PH Transmitted to IEC CONTROL1;GGIO4 ST;Ind1;stVal;SPS 238; None 1 DIGITAL INPUT BOARD DIU2xx
A G 2 SPE_HLA_Reset_Trip SPS 765kV B712_64IOX TRAFO_MB PRD-2 Y-PH Trip Reset RS_TR_PRD-2 Y-PH Transmitted to IEC CONTROL1;GGIO4 ST;Ind2;stVal;SPS 238; None 1 DIGITAL INPUT BOARD DIU2xx
A G 3 SPE_HLA_Reset_Trip SPS 765kV B712_64IOX TRAFO_MB PRD-2 B-PH Trip Reset RS_TR_PRD-2 B-PH Transmitted to IEC CONTROL1;GGIO4 ST;Ind3;stVal;SPS 232;238; None Yes 1 DIGITAL INPUT BOARD DIU2xx
A G 4 SPE_HLA_Reset_Trip SPS 765kV B712_64IOX TRAFO_MB PRD-2 SP-PH Trip Reset RS_TR_PRD-2 SP Transmitted to IEC CONTROL1;GGIO4 ST;Ind4;stVal;SPS 238; None 1 DIGITAL INPUT BOARD DIU2xx
A G 5 SPE_HLA_Reset_Optd SPS 765kV B712_64IOX PROTECTION_PANEL MAIN CB LBB Operated Reset RS_OP_MAIN LBB Transmitted to IEC CONTROL1;GGIO3 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A G 6 SPE_HLA_Unhlthy_Hlthy SPS 765kV B712_64IOX PROTECTION_PANEL BCU RELAY Healthy Unhealthy UH_HL_BCU Transmitted to IEC CONTROL1;GGIO3 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A G 7 SPE_HLA_Unhlthy_Hlthy SPS 765kV B712_64IOX PROTECTION_PANEL PUA RELAY Healthy Unhealthy UH_HL_PU-A Transmitted to IEC CONTROL1;GGIO3 ST;Ind7;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A G 8 SPE_HLA_Healthy_Flty SPS 765kV B712_64IOX PROTECTION_PANEL CB_TC-1 Faulty Healthy HL_FT_CB TC-1 Transmitted to IEC CONTROL1;GGIO3 ST;Ind9;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A G 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A G 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A G 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A G 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A G 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A G 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A G 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A G 16 SPE_HLa_Dselect_Select SPS 765kV B712_64IOX TRAFO_MB AT-S1 Selected Deselected DL_SL_AT S1 Transmitted to IEC CONTROL1;GGIO4 ST;Ind5;stVal;SPS 238; None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 2
Digital Inputs Board Slot F
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A F 1 DP_HLA_ ISOOpen_Close DPS 765kV B712_64IOX 33KV_52 | Triple phase POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XCBR1 ST;Pos;stVal;DPC None CB SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A F 2 DP_HLA_ ISOOpen_Close DPS 765kV B712_64IOX 33KV_52 | Triple phase POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XCBR1 ST;Pos;stVal;DPC None CB SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A F 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A F 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A F 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A F 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A F 7 DP_HLA_ ISOOpen_Close DPS 765kV B712_64IOX 33KV_89 POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 235; None 52 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A F 8 DP_HLA_ ISOOpen_Close DPS 765kV B712_64IOX 33KV_89 POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 235; None 52 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A F 9 DP_HLa_ESOpen_Close DPS 765kV B712_64IOX 33KV_89E POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A F 10 DP_HLa_ESOpen_Close DPS 765kV B712_64IOX 33KV_89E POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A F 11 DP_HLA_CBTrip_Close DPS 765kV B712_64IOX 33KV_52 EMERGENCY MANUAL Trip CL_TR_EM MAN Transmitted to IEC CONTROL1;XCBR1 ST;DPCSO1;stVal;DPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A F 12 DP_HLA_CBTrip_Close DPS 765kV B712_64IOX 33KV_52 EMERGENCY MANUAL Closed CL_TR_EM MAN Transmitted to IEC CONTROL1;XCBR1 ST;DPCSO1;stVal;DPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A F 13 SPE_HLA_Healthy_Flty SPS 765kV B712_64IOX 33KV_52 CB_TC-1 Faulty Healthy HL_FT_CB TC-1 Transmitted to IEC CONTROL1;XCBR1 ST;Ind2;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A F 14 SPE_HLA_Healthy_Flty SPS 765kV B712_64IOX 33KV_52 CB_TC-2 Faulty Healthy HL_FT_CB TC-2 Transmitted to IEC CONTROL1;XCBR1 ST;Ind1;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A F 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A F 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 3
Digital Inputs Board Slot E
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A E 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A E 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A E 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A E 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A E 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A E 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A E 7 DP_HLA_ ISOOpen_Close DPS 765kV B712_64IOX 711_52 | Triple phase POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XCBR3 ST;Pos;stVal;DPC None CB SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A E 8 DP_HLA_ ISOOpen_Close DPS 765kV B712_64IOX 711_52 | Triple phase POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XCBR3 ST;Pos;stVal;DPC None CB SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A E 9 DP_HLA_ ISOOpen_Close DPS 765kV B712_64IOX 710_52 | Triple phase POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XCBR2 ST;Pos;stVal;DPC None CB SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A E 10 DP_HLA_ ISOOpen_Close DPS 765kV B712_64IOX 710_52 | Triple phase POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XCBR2 ST;Pos;stVal;DPC None CB SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A E 11 DP_HLA_ ISOOpen_Close DPS 765kV B712_64IOX OTHER FDR ISO POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI3 ST;Pos;stVal;DPC 236; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A E 12 DP_HLA_ ISOOpen_Close DPS 765kV B712_64IOX OTHER FDR ISO POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI3 ST;Pos;stVal;DPC 236; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A E 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A E 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A E 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A E 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 0
Digital Outputs Board Slot C
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A C 1 SC_DE_Reset_Reset_1 SPC 765kV B712_64IOX PROTECTION_PANEL GRP-A TRIP (PRD OLTC) RESET XX_XX_GRP-A TRP Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO2;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A C 2 SC_DE_Reset_Reset_1 SPC 765kV B712_64IOX PROTECTION_PANEL GRP-B TRIP (PRD OLTC) RESET XX_XX_GRP-B TRP Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO3;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A C 3 SC_DE_Reset_Reset_1 SPC 765kV B712_64IOX PROTECTION_PANEL 33KV 86 RLY RESET RESET XX_XX_33 86 RLY Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO1;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A C 4 SC_DE_Reset_Set_2 SPC 765kV B712_64IOX PROTECTION_PANEL 33KV TC-1 REM TRIP Set XX_XX_33 TC-1 TR Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO4;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A C 5 SC_DE_Reset_Set_2 SPC 765kV B712_64IOX PROTECTION_PANEL 33KV TC-1 REM CLOSING Set XX_XX_33 TC-1 CL Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO6;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A C 6 SC_DE_Reset_Set_2 SPC 765kV B712_64IOX PROTECTION_PANEL 33KV TC-2 REM TRIP Set XX_XX_33 TC-2 TR Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO5;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A C 7 DC_SBO_Open_Close_1 DPC 765kV B712_64IOX 33KV_89 CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 52 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A C 8 DC_SBO_Open_Close_1 DPC 765kV B712_64IOX 33KV_89 CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 52 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A C 9 SC_DE_NotPerm_Perm_1 SPC 765kV B712_64IOX INTERLOCK_PERM 33KV 89 IL PERM RESET XX_XX_89 Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO1;ctlVal;DPC 287 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A C 10 SC_DE_NotPerm_Perm_1 SPC 765kV B712_64IOX INTERLOCK_PERM 33KV 89E IL PERM RESET XX_XX_89E Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO2;ctlVal;DPC 288 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 1
Digital Outputs Board Slot D
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A D 1 SC_DE_Reset_Set_2 SPC 765kV B712_64IOX BUS SELECTION 765KV BUS-1 VT Set BUS-1_VT_SELECT Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO2;ctlVal;DPC 236<; 292 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 2 SC_DE_Reset_Set_2 SPC 765kV B712_64IOX BUS SELECTION 765KV BUS-1 VT Set BUS-1_VT_DE-SEL Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO1;ctlVal;DPC 236<; 291 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 3 SC_DE_Reset_Set_2 SPC 765kV B712_64IOX BUS SELECTION 765KV BUS-2 VT Set BUS-2_VT_SELECT Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO4;ctlVal;DPC 236<; 294 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 4 SC_DE_Reset_Set_2 SPC 765kV B712_64IOX BUS SELECTION 765KV BUS-2 VT Set BUS-2_VT_DE-SEL Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO3;ctlVal;DPC 236<; 293 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 5 SC_DE_Reset_Set_2 SPC 765kV B712_64IOX BUS SELECTION 400KV AT CVT Set 4_AT_CVT_SEL Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO7;ctlVal;DPC 236<; 290 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 6 SC_DE_Reset_Set_2 SPC 765kV B712_64IOX BUS SELECTION 400KV AT CVT Set 4_AT_CVT_DE-SEL Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO8;ctlVal;DPC 236<; 289 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 7 SC_DE_Reset_Set_2 SPC 765kV B712_64IOX BUS SELECTION LINE Set LINE_SELECT Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO5;ctlVal;DPC 236<; 296 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 8 SC_DE_Reset_Set_2 SPC 765kV B712_64IOX BUS SELECTION LINE Set LINE_DE-SELECT Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO6;ctlVal;DPC 236<; 295 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A D 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPE_HLa_Notper_Perm SPS 765kV B712_64IOX 33KV_89 | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL1;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPE_HLa_Notper_Perm SPS 765kV B712_64IOX 33KV_89 INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI1 ST;IndSys1;stVal;SPS None 287 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPE_HLa_Notper_Perm SPS 765kV B712_64IOX 33KV_89 | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL1;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPE_HLa_Notper_Perm SPS 765kV B712_64IOX 33KV_89E INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI3 ST;IndSys1;stVal;SPS 235<; None 288 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPE_HLa_Dselect_Select SPS 765kV B712_64IOX BUS SELECTION 400KV AT CVT Selected Deselected 4_AT_CVT_DE-SEL Transmitted to IEC CONTROL1;GAPC1 ST;IndSys8;stVal;SPS 236<; None 289 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPE_HLa_Reset_Select SPS 765kV B712_64IOX BUS SELECTION 400KV AT CVT Selected Reset 4_AT_CVT_SEL Transmitted to IEC CONTROL1;GAPC1 ST;IndSys7;stVal;SPS 236<; None 290 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPE_HLa_Reset_DSelect SPS 765kV B712_64IOX BUS SELECTION 765KV BUS-1 VT Deselected Reset BUS-1_VT_DE-SEL Transmitted to IEC CONTROL1;GAPC1 ST;IndSys1;stVal;SPS 236<; None 291 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPE_HLa_Reset_Select SPS 765kV B712_64IOX BUS SELECTION 765KV BUS-1 VT Selected Reset BUS-1_VT_SELECT Transmitted to IEC CONTROL1;GAPC1 ST;IndSys2;stVal;SPS 236<; None 292 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPE_HLa_Reset_DSelect SPS 765kV B712_64IOX BUS SELECTION 765KV BUS-2 VT Deselected Reset BUS-2_VT_DE-SEL Transmitted to IEC CONTROL1;GAPC1 ST;IndSys3;stVal;SPS 236<; None 293 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPE_HLa_Reset_Select SPS 765kV B712_64IOX BUS SELECTION 765KV BUS-2 VT Selected Reset BUS-2_VT_SELECT Transmitted to IEC CONTROL1;GAPC1 ST;IndSys4;stVal;SPS 236<; None 294 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPE_HLa_Reset_Set SPS 765kV B712_64IOX BUS SELECTION LINE Set Reset LINE_DE-SELECT Transmitted to IEC CONTROL1;GAPC1 ST;IndSys6;stVal;SPS 236<; None 295 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPE_HLa_Reset_Set SPS 765kV B712_64IOX BUS SELECTION LINE Set Reset LINE_SELECT Transmitted to IEC CONTROL1;GAPC1 ST;IndSys5;stVal;SPS 236<; None 296 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPS_hla_Set_Reset SPS 765kV B712_64IOX Order running on the bay Set Reset Order running Transmitted to IEC CONTROL1;GBAY1 ST;OrdRun;stVal;SPS None OrderInProgress 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPE_HLA_Reset_Optd SPS 765kV B712_64IOX PROTECTION_PANEL RS_OP_86A Operated Reset RS_OP_86A Transmitted to IEC CONTROL2;GAPC1 ST;IndSys1;stVal;SPS 193;237<; None Yes 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPE_HLA_Reset_Optd SPS 765kV B712_64IOX PROTECTION_PANEL RS_OP_86B Operated Reset RS_OP_86B Transmitted to IEC CONTROL2;GAPC1 ST;IndSys2;stVal;SPS 193;237<; None Yes 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPE_HLA_Nrml_Optd SPS 765kV B712_64IOX TRAFO_MB NL_TR_TRB GRP_AB Operated Normal NL_TR_TRB GRP_AB Transmitted to IEC CONTROL1;GAPC2 ST;IndSys3;stVal;SPS 238<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 17 SPE_HLA_Nrml_Optd SPS 765kV B712_64IOX TRAFO_MB AT TRB TRIP GRP-A Operated Normal NL_TR_TRB GRPA Transmitted to IEC CONTROL1;GAPC2 ST;IndSys1;stVal;SPS 238<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 18 SPE_HLA_Nrml_Optd SPS 765kV B712_64IOX TRAFO_MB AT TRB TRIP GRP-B Operated Normal NL_TR_TRB GRPB Transmitted to IEC CONTROL1;GAPC2 ST;IndSys2;stVal;SPS 238<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 19 DP_HLA_CBOpen_Close DPS 765kV B712_64IOX 33KV_52 COMPUTED SWITCH POSITION Open OP_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;origin;DPC None CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 20 DP_HLA_CBOpen_Close DPS 765kV B712_64IOX 33KV_52 COMPUTED SWITCH POSITION Closed OP_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;origin;DPC None CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 21 DP_HLA_CBOpen_Close DPS 765kV B712_64IOX 710_52 COMPUTED SWITCH POSITION Open OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;origin;DPC 236; None CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 22 DP_HLA_CBOpen_Close DPS 765kV B712_64IOX 710_52 COMPUTED SWITCH POSITION Closed OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;origin;DPC 236; None CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 23 DP_HLA_CBOpen_Close DPS 765kV B712_64IOX 711_52 COMPUTED SWITCH POSITION Open OP_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI3 ST;Pos;origin;DPC 236; None CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 24 DP_HLA_CBOpen_Close DPS 765kV B712_64IOX 711_52 COMPUTED SWITCH POSITION Closed OP_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI3 ST;Pos;origin;DPC 236; None CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 25 DP_HLA_CBOpen_Close DPS 765kV B712_64IOX 712_52 COMPUTED SWITCH POSITION Open OP_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI2 ST;Pos;origin;DPC 236; None CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 26 DP_HLA_CBOpen_Close DPS 765kV B712_64IOX 712_52 COMPUTED SWITCH POSITION Closed OP_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI2 ST;Pos;origin;DPC 236; None CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 27 DP_HLa_LocRem_Bay DPS 765kV B712_64IOX BCU MODE Local LC_RM_MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 53 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 28 DP_HLa_LocRem_Bay DPS 765kV B712_64IOX BCU MODE Remote LC_RM_MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 53 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 29 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 DC_DE_LocRem_BayCtrl DPC 765kV B712_64IOX MODE CONTROL Local MODE CONTROL Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 53 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 DC_DE_LocRem_BayCtrl DPC 765kV B712_64IOX MODE CONTROL Remote MODE CONTROL Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 53 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
PATH SIGNAL IEC ADDRESS
Scs | Ethernet network | System Group | B707_LINE TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B707_LINE | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Scs | Ethernet network | System Group | B707_LR TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B707_LR | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Scs | Ethernet network | System Group | B708_TIE TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B708_TIE | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Scs | Ethernet network | System Group | B709_BR TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B709_BR | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Scs | Ethernet network | System Group | B712_ICT T TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B712_ICT T | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Scs | Ethernet network | System Group | B712_ICT TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B712_ICT | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Scs | Ethernet network | System Group | B712_ICT_64X TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B712_ICT_64X | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Scs | Ethernet network | System Group | B713_LINE FUT TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B713_LINE FUT | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 CCCC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : Site Name
IEC Description
Computer Name 7BB1_P747_87_R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
IED NAME : 7BB1_P747_87_R
DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765KV 7BB1_P747_87_R PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_R
SPS 765KV 7BB1_P747_87_R PROTECTION ZONE-1 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind3;stVal;SPS
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_R PROTECTION ZONE-2 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_R
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLA_Normal_Alarm SPS 765KV 7BB1_P747_87_R PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind6;stVal;SPS None Yes 1 #REF!
SPS 765KV 7BB1_P747_87_R PROTECTION ZONE-1 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind7;stVal;SPS
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_R PROTECTION ZONE-2 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind8;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 725 LBB Operated Reset RS_OP 725 LBB System;OptGGIO1 ST;Ind2;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 728 LBB Operated Reset RS_OP 728 LBB System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 726 LBB Operated Reset RS_OP 726 LBB System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 729 LBB Operated Reset RS_OP 729 LBB System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 7BS1 LBB Operated Reset RS_OP 7BS1 LBB System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 7BS2 LBB Operated Reset RS_OP 7BS2 LBB System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind14;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 719 LBB Operated Reset RS_OP 719 LBB System;OptGGIO1 ST;Ind14;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind16;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 722 LBB Operated Reset RS_OP 722 LBB System;OptGGIO1 ST;Ind16;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind18;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 721 LBB Operated Reset RS_OP 721 LBB System;OptGGIO1 ST;Ind18;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind20;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 724 LBB Operated Reset RS_OP 724 LBB System;OptGGIO1 ST;Ind20;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind25;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_R SYSTEM ZONE-1 MAIN-1 Rph SWITCH IN Set Reset RS_ST Z-1 IN System;OptGGIO1 ST;Ind25;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind27;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 765KV 7BB1_P747_87_R SYSTEM BB M2 RELAY R-PH Healthy Unhealthy UH_HL BB M2 RLY System;OptGGIO1 ST;Ind27;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind29;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_R SYSTEM ZONE-2 MAIN-1 Rph SWITCH IN Set Reset RS_ST Z-2 IN System;OptGGIO1 ST;Ind29;stVal;SPS None 1 #REF!
A Protection;CznPDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R PROTECTION CHECK ZONE DIFF PROT Operated Reset RS_OP_CHK ZONE Protection;CznPDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;BbpT01PDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R PROTECTION BUSBAR ZONE1 TRIP R PH Operated Reset RS_OP_BB ZONE1 Protection;BbpT01PDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;BbpT02PDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R PROTECTION BUSBAR ZONE2 TRIP R PH Operated Reset RS_OP_BB ZONE2 Protection;BbpT02PDIF1 ST;Op;general;ACT None 1 #REF!
SPS 765KV 7BB1_P747_87_R PROTECTION BUSBAR ZONE 1 PROTECTION BLOCKED Set Reset RS_ST_BB BLOCK
SPS 765KV 7BB1_P747_87_R PROTECTION BUSBAR ZONE 2 PROTECTION BLOCKED Set Reset RS_ST_BB BLOCK
SPS 765kV 7BB1_P747_87_R PROTECTION CHECK ZONE Operated Reset RS_OP_CHECKZONE
SPS 765kV 7BB1_P747_87_R SYSTEM SETTINGS CHANGED Set Reset
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
DIGITAL INFORMATION TO IED ** Any additional Signals as per Scheme & TS
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
ANALOG INFORMATION TO IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_R
COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 CCCC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : Site Name
IEC Description
Computer Name 7BB1_P747_87_Y GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
IED NAME : 7BB1_P747_87_Y
DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_Y
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765KV 7BB1_P747_87_Y PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_Y
SPS 765KV 7BB1_P747_87_Y PROTECTION ZONE-1 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind3;stVal;SPS
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_Y PROTECTION ZONE-2 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_Y
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLA_Normal_Alarm SPS 765KV 7BB1_P747_87_Y PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind6;stVal;SPS None Yes 1 #REF!
SPS 765KV 7BB1_P747_87_Y PROTECTION ZONE-1 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind7;stVal;SPS
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_Y PROTECTION ZONE-2 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind8;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 725 LBB Operated Reset RS_OP 725 LBB System;OptGGIO1 ST;Ind2;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 728 LBB Operated Reset RS_OP 728 LBB System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 726 LBB Operated Reset RS_OP 726 LBB System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 729 LBB Operated Reset RS_OP 729 LBB System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 7BS1 LBB Operated Reset RS_OP 7BS1 LBB System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 7BS2 LBB Operated Reset RS_OP 7BS2 LBB System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 719 LBB Operated Reset RS_OP 719 LBB System;OptGGIO1 ST;Ind14;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 722 LBB Operated Reset RS_OP 722 LBB System;OptGGIO1 ST;Ind16;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 721 LBB Operated Reset RS_OP 721 LBB System;OptGGIO1 ST;Ind18;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 724 LBB Operated Reset RS_OP 724 LBB System;OptGGIO1 ST;Ind20;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y SYSTEM ZONE-1 MAIN-1 Yph SWITCH IN Set Reset RS_ST Z-1 IN System;OptGGIO1 ST;Ind25;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y SYSTEM BB M2 RELAY Y-PH Healthy Unhealthy UH_HL BB M2 RLY System;OptGGIO1 ST;Ind27;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y SYSTEM ZONE-2 MAIN-1 Yph SWITCH IN Set Reset RS_ST Z-2 IN System;OptGGIO1 ST;Ind29;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind14;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y PROTECTION CHECK ZONE DIFF PROT Operated Reset RS_OP_CHK ZONE Protection;CznPDIF1 ST;Op;general;ACT None 1 #REF!
A System;OptGGIO1 ST;Ind15;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y PROTECTION BUSBAR ZONE1 TRIP Y PH Operated Reset RS_OP_BB ZONE1 Protection;BbpT01PDIF1 ST;Op;general;ACT None 1 #REF!
A System;OptGGIO1 ST;Ind16;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y PROTECTION BUSBAR ZONE2 TRIP Y PH Operated Reset RS_OP_BB ZONE2 Protection;BbpT02PDIF1 ST;Op;general;ACT None 1 #REF!
A System;OptGGIO1 ST;Ind17;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y PROTECTION BUSBAR ZONE 1 PROTECTION BLOCKED Set Reset RS_ST_BB BLOCK None 1 #REF!
A System;OptGGIO1 ST;Ind18;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y PROTECTION BUSBAR ZONE 2 PROTECTION BLOCKED Set Reset RS_ST_BB BLOCK None 1 #REF!
SPS 765kV 7BB1_P747_87_Y PROTECTION CHECK ZONE Operated Reset RS_OP_CHECKZONE
SPS 765kV 7BB1_P747_87_R SYSTEM SETTINGS CHANGED Set Reset
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_Y
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_Y
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_Y
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_Y
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_Y
ANALOG INFORMATION TO IED IED name 7BB1_P747_87_Y
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_Y
COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_Y
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_Y
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_Y
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_Y
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_Y
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 CCCC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : Site Name
IEC Description
Computer Name 7BB1_P747_87_B GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
IED NAME : 7BB1_P747_87_B
DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_B
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765KV 7BB1_P747_87_B PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC System;LLN0 ST;SyncSt;stVal;SPS System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_B
SPS 765KV 7BB1_P747_87_B PROTECTION ZONE-1 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind3;stVal;SPS System;GosGGIO2 ST;Ind3;stVal;SPS
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_B PROTECTION ZONE-2 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind4;stVal;SPS System;GosGGIO2 ST;Ind4;stVal;SPS
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLA_Normal_Alarm SPS 765KV 7BB1_P747_87_B PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind6;stVal;SPS System;GosGGIO2 ST;Ind6;stVal;SPS
SPS 765KV 7BB1_P747_87_B PROTECTION ZONE-1 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind7;stVal;SPS System;GosGGIO2 ST;Ind7;stVal;SPS
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_B PROTECTION ZONE-2 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind8;stVal;SPS System;GosGGIO2 ST;Ind8;stVal;SPS
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B SYSTEM BAY 725 LBB Operated Reset RS_OP 725 LBB System;OptGGIO1 ST;Ind2;stVal;SPS System;OptGGIO1 ST;Ind2;stVal;SPS
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B SYSTEM BAY 728 LBB Operated Reset RS_OP 728 LBB System;OptGGIO1 ST;Ind4;stVal;SPS System;OptGGIO1 ST;Ind4;stVal;SPS
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B SYSTEM BAY 726 LBB Operated Reset RS_OP 726 LBB System;OptGGIO1 ST;Ind6;stVal;SPS System;OptGGIO1 ST;Ind6;stVal;SPS
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B SYSTEM BAY 729 LBB Operated Reset RS_OP 729 LBB System;OptGGIO1 ST;Ind8;stVal;SPS System;OptGGIO1 ST;Ind8;stVal;SPS
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B SYSTEM BAY 7BS1 LBB Operated Reset RS_OP 7BS1 LBB System;OptGGIO1 ST;Ind10;stVal;SPS System;OptGGIO1 ST;Ind10;stVal;SPS
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B SYSTEM BAY 7BS2 LBB Operated Reset RS_OP 7BS2 LBB System;OptGGIO1 ST;Ind12;stVal;SPS System;OptGGIO1 ST;Ind12;stVal;SPS
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B SYSTEM BAY 719 LBB Operated Reset RS_OP 719 LBB System;OptGGIO1 ST;Ind14;stVal;SPS System;OptGGIO1 ST;Ind14;stVal;SPS
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B SYSTEM BAY 722 LBB Operated Reset RS_OP 722 LBB System;OptGGIO1 ST;Ind16;stVal;SPS System;OptGGIO1 ST;Ind16;stVal;SPS
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B SYSTEM BAY 721 LBB Operated Reset RS_OP 721 LBB System;OptGGIO1 ST;Ind18;stVal;SPS System;OptGGIO1 ST;Ind18;stVal;SPS
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B SYSTEM BAY 724 LBB Operated Reset RS_OP 724 LBB System;OptGGIO1 ST;Ind20;stVal;SPS System;OptGGIO1 ST;Ind20;stVal;SPS
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B SYSTEM ZONE-1 MAIN-1 Bph SWITCH IN Set Reset RS_ST Z-1 IN System;OptGGIO1 ST;Ind25;stVal;SPS System;OptGGIO1 ST;Ind25;stVal;SPS
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B SYSTEM BB M2 RELAY B-PH Healthy Unhealthy UH_HL BB M2 RLY System;OptGGIO1 ST;Ind27;stVal;SPS System;OptGGIO1 ST;Ind27;stVal;SPS
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B SYSTEM ZONE-2 MAIN-1 Bph SWITCH IN Set Reset RS_ST Z-2 IN System;OptGGIO1 ST;Ind29;stVal;SPS System;OptGGIO1 ST;Ind29;stVal;SPS
A System;OptGGIO1 ST;Ind14;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B PROTECTION CHECK ZONE DIFF PROT Operated Reset RS_OP_CHK ZONE Protection;CznPDIF1 ST;Op;general;ACT Protection;CznPDIF1 ST;Op;general;ACT
A System;OptGGIO1 ST;Ind15;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B PROTECTION BUSBAR ZONE1 TRIP B PH Operated Reset RS_OP_BB ZONE1 Protection;BbpT01PDIF1 ST;Op;general;ACT Protection;BbpT01PDIF1 ST;Op;general;ACT
A System;OptGGIO1 ST;Ind16;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B PROTECTION BUSBAR ZONE2 TRIP B PH Operated Reset RS_OP_BB ZONE2 Protection;BbpT02PDIF1 ST;Op;general;ACT Protection;BbpT02PDIF1 ST;Op;general;ACT
A System;OptGGIO1 ST;Ind17;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B PROTECTION BUSBAR ZONE 1 PROTECTION BLOCKED Set Reset RS_ST_BB BLOCK
A System;OptGGIO1 ST;Ind18;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B PROTECTION BUSBAR ZONE 2 PROTECTION BLOCKED Set Reset RS_ST_BB BLOCK
SPS 765kV 7BB1_P747_87_B PROTECTION CHECK ZONE Operated Reset RS_OP_CHECKZONE
SPS 765kV 7BB1_P747_87_R SYSTEM SETTINGS CHANGED Set Reset
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_B
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_B
ANALOG INFORMATION TO IED IED name 7BB1_P747_87_B
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_B
COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_B
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_B
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 CCCC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : Site Name
IEC Description
Computer Name 7BB1_P747_87_R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
IED NAME : 7BB1_P747_87_R
DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765KV 7BB1_P747_87_R PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_R
SPS 765KV 7BB1_P747_87_R PROTECTION ZONE-1 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind3;stVal;SPS
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_R PROTECTION ZONE-2 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_R
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLA_Normal_Alarm SPS 765KV 7BB1_P747_87_R PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind6;stVal;SPS None Yes 1 #REF!
SPS 765KV 7BB1_P747_87_R PROTECTION ZONE-1 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind7;stVal;SPS
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_R PROTECTION ZONE-2 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind8;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 725 LBB Operated Reset RS_OP 725 LBB System;OptGGIO1 ST;Ind2;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 728 LBB Operated Reset RS_OP 728 LBB System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 726 LBB Operated Reset RS_OP 726 LBB System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 729 LBB Operated Reset RS_OP 729 LBB System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 7BS1 LBB Operated Reset RS_OP 7BS1 LBB System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 7BS2 LBB Operated Reset RS_OP 7BS2 LBB System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind14;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 719 LBB Operated Reset RS_OP 719 LBB System;OptGGIO1 ST;Ind14;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind16;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 722 LBB Operated Reset RS_OP 722 LBB System;OptGGIO1 ST;Ind16;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind18;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 721 LBB Operated Reset RS_OP 721 LBB System;OptGGIO1 ST;Ind18;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind20;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R SYSTEM BAY 724 LBB Operated Reset RS_OP 724 LBB System;OptGGIO1 ST;Ind20;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind25;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_R SYSTEM ZONE-1 MAIN-2 Rph SWITCH IN Set Reset RS_ST Z-1 IN System;OptGGIO1 ST;Ind25;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind27;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 765KV 7BB1_P747_87_R SYSTEM BB M2 RELAY R-PH Healthy Unhealthy UH_HL BB M2 RLY System;OptGGIO1 ST;Ind27;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind29;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_R SYSTEM ZONE-2 MAIN-2 Rph SWITCH IN Set Reset RS_ST Z-2 IN System;OptGGIO1 ST;Ind29;stVal;SPS None 1 #REF!
A Protection;CznPDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R PROTECTION CHECK ZONE DIFF PROT Operated Reset RS_OP_CHK ZONE Protection;CznPDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;BbpT01PDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R PROTECTION BUSBAR ZONE1 TRIP R PH Operated Reset RS_OP_BB ZONE1 Protection;BbpT01PDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;BbpT02PDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_R PROTECTION BUSBAR ZONE2 TRIP R PH Operated Reset RS_OP_BB ZONE2 Protection;BbpT02PDIF1 ST;Op;general;ACT None 1 #REF!
SPS 765KV 7BB1_P747_87_R PROTECTION BUSBAR ZONE 1 PROTECTION BLOCKED Set Reset RS_ST_BB BLOCK
SPS 765KV 7BB1_P747_87_R PROTECTION BUSBAR ZONE 2 PROTECTION BLOCKED Set Reset RS_ST_BB BLOCK
SPS 765kV 7BB1_P747_87_R PROTECTION CHECK ZONE Operated Reset RS_OP_CHECKZONE
SPS 765kV 7BB1_P747_87_R SYSTEM SETTINGS CHANGED Set Reset
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
ANALOG INFORMATION TO IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_R
COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 CCCC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : Site Name
IEC Description
Computer Name 7BB1_P747_87_Y GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
IED NAME : 7BB1_P747_87_Y
DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_Y
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765KV 7BB1_P747_87_Y PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_Y
SPS 765KV 7BB1_P747_87_Y PROTECTION ZONE-1 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind3;stVal;SPS
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_Y PROTECTION ZONE-2 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_Y
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLA_Normal_Alarm SPS 765KV 7BB1_P747_87_Y PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind6;stVal;SPS None Yes 1 #REF!
SPS 765KV 7BB1_P747_87_Y PROTECTION ZONE-1 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind7;stVal;SPS
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_Y PROTECTION ZONE-2 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind8;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 725 LBB Operated Reset RS_OP 725 LBB System;OptGGIO1 ST;Ind2;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 728 LBB Operated Reset RS_OP 728 LBB System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 726 LBB Operated Reset RS_OP 726 LBB System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 729 LBB Operated Reset RS_OP 729 LBB System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 7BS1 LBB Operated Reset RS_OP 7BS1 LBB System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 7BS2 LBB Operated Reset RS_OP 7BS2 LBB System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 719 LBB Operated Reset RS_OP 719 LBB System;OptGGIO1 ST;Ind14;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 722 LBB Operated Reset RS_OP 722 LBB System;OptGGIO1 ST;Ind16;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 721 LBB Operated Reset RS_OP 721 LBB System;OptGGIO1 ST;Ind18;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y SYSTEM BAY 724 LBB Operated Reset RS_OP 724 LBB System;OptGGIO1 ST;Ind20;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y SYSTEM ZONE-1 MAIN-2 Yph SWITCH IN Set Reset RS_ST Z-1 IN System;OptGGIO1 ST;Ind25;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y SYSTEM BB M2 RELAY Y-PH Healthy Unhealthy UH_HL BB M2 RLY System;OptGGIO1 ST;Ind27;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y SYSTEM ZONE-2 MAIN-2 Yph SWITCH IN Set Reset RS_ST Z-2 IN System;OptGGIO1 ST;Ind29;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind14;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y PROTECTION CHECK ZONE DIFF PROT Operated Reset RS_OP_CHK ZONE Protection;CznPDIF1 ST;Op;general;ACT None 1 #REF!
A System;OptGGIO1 ST;Ind15;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y PROTECTION BUSBAR ZONE1 TRIP Y PH Operated Reset RS_OP_BB ZONE1 Protection;BbpT01PDIF1 ST;Op;general;ACT None 1 #REF!
A System;OptGGIO1 ST;Ind16;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y PROTECTION BUSBAR ZONE2 TRIP Y PH Operated Reset RS_OP_BB ZONE2 Protection;BbpT02PDIF1 ST;Op;general;ACT None 1 #REF!
A System;OptGGIO1 ST;Ind17;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_Y PROTECTION BUSBAR ZONE 1 PROTECTION BLOCKED Set Reset RS_ST_BB BLOCK None 1 #REF!
A System;OptGGIO1 ST;Ind18;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_Y PROTECTION BUSBAR ZONE 2 PROTECTION BLOCKED Set Reset RS_ST_BB BLOCK None 1 #REF!
SPS 765kV 7BB1_P747_87_Y PROTECTION CHECK ZONE Operated Reset RS_OP_CHECKZONE
SPS 765kV 7BB1_P747_87_Y SYSTEM SETTINGS CHANGED Set Reset
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_Y
ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_Y
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_Y
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_Y
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_Y
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_Y
ANALOG INFORMATION TO IED IED name 7BB1_P747_87_Y
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_Y
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_Y
COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_Y
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_Y
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_Y
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_Y
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_Y
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 CCCC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : Site Name
IEC Description
Computer Name 7BB1_P747_87_B GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
IED NAME : 7BB1_P747_87_B
DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_B
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765KV 7BB1_P747_87_B PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC System;LLN0 ST;SyncSt;stVal;SPS System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_B
SPS 765KV 7BB1_P747_87_B PROTECTION ZONE-1 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind3;stVal;SPS System;GosGGIO2 ST;Ind3;stVal;SPS
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_B PROTECTION ZONE-2 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind4;stVal;SPS System;GosGGIO2 ST;Ind4;stVal;SPS
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLA_Normal_Alarm SPS 765KV 7BB1_P747_87_B PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind6;stVal;SPS System;GosGGIO2 ST;Ind6;stVal;SPS
SPS 765KV 7BB1_P747_87_B PROTECTION ZONE-1 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind7;stVal;SPS System;GosGGIO2 ST;Ind7;stVal;SPS
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 765KV 7BB1_P747_87_B PROTECTION ZONE-2 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind8;stVal;SPS System;GosGGIO2 ST;Ind8;stVal;SPS
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B SYSTEM BAY 725 LBB Operated Reset RS_OP 725 LBB System;OptGGIO1 ST;Ind2;stVal;SPS System;OptGGIO1 ST;Ind2;stVal;SPS
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B SYSTEM BAY 728 LBB Operated Reset RS_OP 728 LBB System;OptGGIO1 ST;Ind4;stVal;SPS System;OptGGIO1 ST;Ind4;stVal;SPS
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B SYSTEM BAY 726 LBB Operated Reset RS_OP 726 LBB System;OptGGIO1 ST;Ind6;stVal;SPS System;OptGGIO1 ST;Ind6;stVal;SPS
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B SYSTEM BAY 729 LBB Operated Reset RS_OP 729 LBB System;OptGGIO1 ST;Ind8;stVal;SPS System;OptGGIO1 ST;Ind8;stVal;SPS
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B SYSTEM BAY 7BS1 LBB Operated Reset RS_OP 7BS1 LBB System;OptGGIO1 ST;Ind10;stVal;SPS System;OptGGIO1 ST;Ind10;stVal;SPS
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B SYSTEM BAY 7BS2 LBB Operated Reset RS_OP 7BS2 LBB System;OptGGIO1 ST;Ind12;stVal;SPS System;OptGGIO1 ST;Ind12;stVal;SPS
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B SYSTEM BAY 719 LBB Operated Reset RS_OP 719 LBB System;OptGGIO1 ST;Ind14;stVal;SPS System;OptGGIO1 ST;Ind14;stVal;SPS
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B SYSTEM BAY 722 LBB Operated Reset RS_OP 722 LBB System;OptGGIO1 ST;Ind16;stVal;SPS System;OptGGIO1 ST;Ind16;stVal;SPS
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B SYSTEM BAY 721 LBB Operated Reset RS_OP 721 LBB System;OptGGIO1 ST;Ind18;stVal;SPS System;OptGGIO1 ST;Ind18;stVal;SPS
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B SYSTEM BAY 724 LBB Operated Reset RS_OP 724 LBB System;OptGGIO1 ST;Ind20;stVal;SPS System;OptGGIO1 ST;Ind20;stVal;SPS
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B SYSTEM ZONE-1 MAIN-2 Bph SWITCH IN Set Reset RS_ST Z-1 IN System;OptGGIO1 ST;Ind25;stVal;SPS System;OptGGIO1 ST;Ind25;stVal;SPS
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B SYSTEM BB M2 RELAY B-PH Healthy Unhealthy UH_HL BB M2 RLY System;OptGGIO1 ST;Ind27;stVal;SPS System;OptGGIO1 ST;Ind27;stVal;SPS
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B SYSTEM ZONE-2 MAIN-2 Bph SWITCH IN Set Reset RS_ST Z-2 IN System;OptGGIO1 ST;Ind29;stVal;SPS System;OptGGIO1 ST;Ind29;stVal;SPS
A System;OptGGIO1 ST;Ind14;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B PROTECTION CHECK ZONE DIFF PROT Operated Reset RS_OP_CHK ZONE Protection;CznPDIF1 ST;Op;general;ACT Protection;CznPDIF1 ST;Op;general;ACT
A System;OptGGIO1 ST;Ind15;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B PROTECTION BUSBAR ZONE1 TRIP B PH Operated Reset RS_OP_BB ZONE1 Protection;BbpT01PDIF1 ST;Op;general;ACT Protection;BbpT01PDIF1 ST;Op;general;ACT
A System;OptGGIO1 ST;Ind16;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B PROTECTION BUSBAR ZONE2 TRIP B PH Operated Reset RS_OP_BB ZONE2 Protection;BbpT02PDIF1 ST;Op;general;ACT Protection;BbpT02PDIF1 ST;Op;general;ACT
A System;OptGGIO1 ST;Ind17;stVal;SPS SPE_HLa_Reset_Close SPS 765KV 7BB1_P747_87_B PROTECTION BUSBAR ZONE 1 PROTECTION BLOCKED Set Reset RS_ST_BB BLOCK
A System;OptGGIO1 ST;Ind18;stVal;SPS SPE_HLA_Reset_Optd SPS 765KV 7BB1_P747_87_B PROTECTION BUSBAR ZONE 2 PROTECTION BLOCKED Set Reset RS_ST_BB BLOCK
SPS 765kV 7BB1_P747_87_B PROTECTION CHECK ZONE Operated Reset RS_OP_CHECKZONE
SPS 765kV 7BB1_P747_87_B SYSTEM SETTINGS CHANGED Set Reset
** 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database
** Any additional Signals as per Scheme & TS
DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_B
ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_B
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_B
ANALOG INFORMATION TO IED IED name 7BB1_P747_87_B
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_B
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_B
COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_B
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_B
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
GE Standard Signals for 400kV Level
Revision History
Rev.No Description of Remarks Date Remarks
02 Old Signal list --
03 1. Distance relay - Missing internal signals related to functions such as AR, Weak-infeed, SOTF. 2. Addition of Differential Protection signals 3. Addition of Transformer phase wise Mechanical tripping signals 4. Addition of Centralized Busbar protection related signals. 5. Addition of tertiary transformer related protection signals. 6. Addition of Backup impedance protection signals for ICT & Reactor. 7. Addition of Directional OC & EF protection signals for ICT. 8. Addition of Mechanical trippings & alarms associated with REF. 9. Addition of NGR associated protection & CB Alarms 10. Addition of De-centralised - Busbar protection signals 11. Addition of Breaker failure protection initiation & Re-trip signals in standalone & centralized busbar protection 12. Addition of BCU – AR associated internal signals, TC phase wise, CSD related alarms, Bay wise measurements 16.01.2024
REVISION 3- STANDARD SIGNAL LIST FOR GE
BAY NUMBERS ARE SYMBOLIC. FOLLOWING IEDS REPRESENT THE APPLICATIONS AS MENTIONED BELOW.
Sheet Ref. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 P741 IEC BB4_P741_87CUA BUSBAR PROTECTION(DISTRIBUTED) MAIN 1 RELAY FOR 400KV BHWD400BBM1 Where same IED protects both Bus 1 & 2
2 P741 IEC BB4_P741_87CUB BUSBAR PROTECTION(DISTRIBUTED) MAIN 2 RELAY FOR 400KV BHWD400BBM2 Where same IED protects both Bus 1 & 2
3 B90 IEC BB4_B90_87 BUSBAR PROTECTION(CENTRALIZIED) MAIN RELAY FOR 400KV BHWD400BB1M1 Where same IED protects both Bus 1 & 2
4 P444 IEC R401_P444_21M1 LINE DISTANCE RELAY MAIN-1 BHWD4XXM1DIS Bay No. 4XX will be always the main bay number for the Line feeder
5 D60 IEC R401_D60_21M1 LINE DISTANCE RELAY MAIN-1 BHWD4XXM1DIS Bay No. 4XX will be always the main bay number for the Line feeder
6 L90 IEC R401_L90_21M2 LINE DIFFERENTIAL RELAY MAIN-2 BHWD4XXM2DIS Bay No. 4XX will be always the main bay number for the Line feeder
7 P546 IEC R401_P546_21M2 LINE DISTANCE RELAY MAIN-2 BHWD4XXM2DIS Bay No. 4XX will be always the main bay number for the Line feeder
8 P743 IEC R401_P743_PU_A LINE PU-1 BHWD4XXM1PU Only if standalone reporting directly to HMI. Includes BFR related signals also
9 P743 IEC R401_P743_PU_B LINE PU-2 BHWD4XXM2PU Only if standalone reporting directly to HMI. Includes BFR related signals also
10 P743 IEC R402_P743_50BF STANDALONE BREAKER FAILURE RELAY FOR TIE BREAKER BHWD4XXBFR Only if standalone reporting directly to HMI
11 P643 IEC R407_P643_87T ICT DIFFERENTIAL RELAY BHWD4XXTDIF Bay No. 4XX will be always the main bay number for the ICT feeder
12 P643 IEC R407_P643_64T ICT REF RELAY BHWD4XXTREF Bay No. 4XX will be always the main bay number for the ICT feeder
13 P442 IEC R407_P442_21R ICT BACKUP IMPEDNACE BHWD4XXTBU Bay No. 4XX will be always the main bay number for the ICT feeder
14 P743 IEC R407_P743_PU_A ICT PU-1 BHWD4XXM1PU Only if standalone reporting directly to HMI. Includes BFR related signals also
15 P743 IEC R407_P743_PU_B ICT PU-2 BHWD4XXM2PU Only if standalone reporting directly to HMI. Includes BFR related signals also
16 P643 IEC R412_P643_87R REACTOR DIFFERENTIAL RELAY BHWD4XXBRDIF Bay No. 4XX will be always the main bay number for the Bus Reactor feeder. BR for Bus Reactor & LR for Line reactor
17 P141 IEC R412_P141_64R REACTOR REF RELAY BHWD4XXBRREF Bay No. 4XX will be always the main bay number for the Bus Reactor feeder. BR for Bus Reactor & LR for Line reactor
18 P442 IEC R412_P442_21R REACTOR BACKUP IMPEDANCE RELAY BHWD4XXBRBU Bay No. 4XX will be always the main bay number for the Bus Reactor feeder. BR for Bus Reactor & LR for Line reactor
19 P743 IEC R412_P743_PU_A REACTOR PU-1 BHWD4XXM1PU Only if standalone reporting directly to HMI. Includes BFR related signals also
20 P743 IEC R412_P743_PU_B REACTOR PU-2 BHWD4XXM2PU Only if standalone reporting directly to HMI. Includes BFR related signals also
21 BCU BCU B401_LINE LINE BCU BHWD4XXBCU BCU is for each bay so 4XX refers to Bay
22 BCU BCU B402_TIE TIE BCU BHWD4XXBCU BCU is for each bay so 4XX refers to Bay
23 BCU BCU B409_ICT1 ICT BCU BHWD2XXBCU BCU is for each bay so 2XX refers to Bay
24 BCU BCU B412_BR BUS REACTOR BCU BHWD4XXBCU BCU is for each bay so 4XX refers to Bay
25 P442 IEC R407_P442_67 HV ICT LV OVERCURRENT RELAY BHWD4XXTLVBU Bay No. 4XX will be always the main bay number for the ICT feeder
26 P442 IEC R407_P442_67 LV ICT HV OVERCURRENT RELAY BHWD4XXTHVBU Bay No. 4XX will be always the main bay number for the ICT feeder
27 Time Synch TIME SYNC ADDRESS FOR ALL BCUs IS GIVEN IN THIS SHEET
28 Goose GOOSE FAIL ALARM ADDRESS FOR ALL BCUs IS GIVEN IN THIS SHEET
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name BB4_P741_87CUA GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : BB4_P741_87CUA
DIGITAL INFORMATION FROM IED IED name BB4_P741_87CUA
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV BB4_P741_87CUA PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV BB4_P741_87CUA PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 400kV BB4_P741_87CUA PROTECTION ZONE-1 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 1 Transmitted to IEC System;GosGGIO2 ST;Ind5;stVal;SPS None Yes 1 0
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 400kV BB4_P741_87CUA PROTECTION ZONE-2 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 2 Transmitted to IEC System;GosGGIO2 ST;Ind6;stVal;SPS None Yes 1 0
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 400kV BB4_P741_87CUA PROTECTION ZONE-1 BUSBAR BLOCKED Set Reset RS_ST_BB BLOCK 1 Transmitted to IEC System;GosGGIO2 ST;Indxx;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 400kV BB4_P741_87CUA PROTECTION ZONE-2 BUSBAR BLOCKED Set Reset RS_ST_BB BLOCK 2 Transmitted to IEC System;GosGGIO2 ST;Indxx;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 400kV BB4_P741_87CUA PROTECTION Z1 BUSBAR BLOCKED DUE TO COMM. ERR Set Reset RS_ST_BB BLOCKC1 Transmitted to IEC System;GosGGIO2 ST;Ind7;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 400kV BB4_P741_87CUA PROTECTION Z2 BUSBAR BLOCKED DUE TO COMM. ERR Set Reset RS_ST_BB BLOCKC2 Transmitted to IEC System;GosGGIO2 ST;Ind8;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 400kV BB4_P741_87CUA PROTECTION ZONE-1 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI1 Transmitted to IEC System;GosGGIO2 ST;Ind9;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 400kV BB4_P741_87CUA PROTECTION ZONE-2 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI2 Transmitted to IEC System;GosGGIO2 ST;Ind10;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLa_Reset_In SPS 400kV BB4_P741_87CUA SYSTEM MAIN-1 B/B ZONE-1 In Reset RS_IN_M1 BB Z1 Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400kV BB4_P741_87CUA SYSTEM 87CUB RELAY Healthy Unhealthy UH_HL_87CUB Transmitted to IEC System;OptGGIO1 ST;Ind3;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400kV BB4_P741_87CUA SYSTEM BBMT2 RELAY Healthy Unhealthy UH_HL_BBMT2 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLa_Reset_In SPS 400kV BB4_P741_87CUA SYSTEM MAIN-1 B/B ZONE-2 In Reset RS_IN_M1 BB Z2 Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A Protection;CftPhsPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV BB4_P741_87CUA PROTECTION ZONE-1 CIRCUITRY FAULT Operated Reset RS_OP_ZONE1 CFT Transmitted to IEC Protection;CftPhsPDIF1 ST;Op;general;general;ACT None 1 #REF!
A Protection;CftPhsPDIF2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV BB4_P741_87CUA PROTECTION ZONE-2 CIRCUITRY FAULT Operated Reset RS_OP_ZONE2 CFT Transmitted to IEC Protection;CftPhsPDIF2 ST;Op;general;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400kV BB4_P741_87CUA PROTECTION B/B ZONE-1 Operated Reset RS_OP_ZONE1 Transmitted to IEC Protection;TrpPhsPDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400kV BB4_P741_87CUA PROTECTION B/B ZONE-2 Operated Reset RS_OP_ZONE2 Transmitted to IEC Protection;TrpPhsPDIF2 ST;Op;general;ACT None 1 #REF!
SPS 400kV BB4_P741_87CUA PROTECTION ZONE MERGE (IF APPLICABLE ) Set Reset RS_ST_ZONE_MRG
SPS 400kV BB4_P741_87CUA PROTECTION BUSBAR ZONE 1 R- PHASE TRIP Operated Reset RS_OP_ZONE1_R Protection;TrpPhsPDIF1 ST;Op;phs1
SPS 400kV BB4_P741_87CUA PROTECTION BUSBAR ZONE 1 Y- PHASE TRIP Operated Reset RS_OP_ZONE1_Y Protection;TrpPhsPDIF1 ST;Op;phs2
SPS 400kV BB4_P741_87CUA PROTECTION BUSBAR ZONE 1 B- PHASE TRIP Operated Reset RS_OP_ZONE1_B Protection;TrpPhsPDIF1 ST;Op;phs3
SPS 400kV BB4_P741_87CUA PROTECTION BUSBAR ZONE 2 R- PHASE TRIP Operated Reset RS_OP_ZONE2_R Protection;TrpPhsPDIF2 ST;Op;phs1
SPS 400kV BB4_P741_87CUA PROTECTION BUSBAR ZONE 2 Y- PHASE TRIP Operated Reset RS_OP_ZONE2_Y Protection;TrpPhsPDIF2 ST;Op;phs2
SPS 400kV BB4_P741_87CUA PROTECTION BUSBAR ZONE 2 B- PHASE TRIP Operated Reset RS_OP_ZONE2_B Protection;TrpPhsPDIF2 ST;Op;phs3
A SPARE SPS 400kv BB4_P741_87CUA PROTECTION CHECK ZONE Operated Reset RS_OP_CHECKZONE None No 1 #REF!
DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUA
ANALOG INFORMATION FROM IED IED name BB4_P741_87CUA
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUA
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUA
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUA
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUA
ANALOG INFORMATION TO IED IED name BB4_P741_87CUA
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name BB4_P741_87CUA
A SPARE 13 ANALOG INFORMATION TO IED IED name BB4_P741_87CUA
COUNTER INFORMATION FROM IED IED name BB4_P741_87CUA
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUA
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUA
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUA
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUA
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name BB4_P741_87CUB GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : BB4_P741_87CUB
DIGITAL INFORMATION FROM IED IED name BB4_P741_87CUB
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV BB4_P741_87CUB PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name BB4_P741_87CUB
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV BB4_P741_87CUB PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 400kV BB4_P741_87CUB PROTECTION ZONE-1 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 1 Transmitted to IEC System;GosGGIO2 ST;Ind5;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 400kV BB4_P741_87CUB PROTECTION ZONE-2 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK 2 Transmitted to IEC System;GosGGIO2 ST;Ind6;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind5;stVal;SPS SPE_HLa_Reset_Set SPS 400kV BB4_P741_87CUB PROTECTION ZONE-1 BUSBAR BLOCKED Set Reset RS_ST_BB BLOCK 1 Transmitted to IEC System;GosGGIO2 ST;Indxx;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 400kV BB4_P741_87CUB PROTECTION ZONE-2 BUSBAR BLOCKED Set Reset RS_ST_BB BLOCK 2 Transmitted to IEC System;GosGGIO2 ST;Indxx;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 400kV BB4_P741_87CUB PROTECTION Z1 BUSBAR BLOCKED DUE TO COMM. ERR Set Reset RS_ST_BB BLOCKC1 Transmitted to IEC System;GosGGIO2 ST;Ind7;stVal;SPS None Yes 1 #REF!
SPS 400kV BB4_P741_87CUB PROTECTION Z2 BUSBAR BLOCKED DUE TO COMM. ERR Set Reset RS_ST_BB BLOCKC2 Transmitted to IEC System;GosGGIO2 ST;Ind8;stVal;SPS
SPS 400kV BB4_P741_87CUB PROTECTION ZONE-1 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI1 Transmitted to IEC System;GosGGIO2 ST;Ind9;stVal;SPS
SPS 400kV BB4_P741_87CUB PROTECTION ZONE-2 BB BLOCKED DUE TO INTERMED. Set Reset RS_ST_BB BLOCKI2 Transmitted to IEC System;GosGGIO2 ST;Ind10;stVal;SPS
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLa_Reset_In SPS 400kV BB4_P741_87CUB SYSTEM MAIN-1 B/B ZONE-1 In Reset RS_IN_M2 BB Z1 Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400kV BB4_P741_87CUB SYSTEM 87CUA RELAY Healthy Unhealthy UH_HL_87CUA Transmitted to IEC System;OptGGIO1 ST;Ind3;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400kV BB4_P741_87CUB SYSTEM BBMT2 RELAY Healthy Unhealthy UH_HL_BBMT1 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLa_Reset_In SPS 400kV BB4_P741_87CUB SYSTEM MAIN-1 B/B ZONE-2 In Reset RS_IN_M2 BB Z2 Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A Protection;CftPhsPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV BB4_P741_87CUB PROTECTION ZONE-1 CIRCUITRY FAULT Operated Reset RS_OP_ZONE1 CFT Transmitted to IEC Protection;CftPhsPDIF1 ST;Op;general;general;ACT None 1 #REF!
A Protection;CftPhsPDIF2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV BB4_P741_87CUB PROTECTION ZONE-2 CIRCUITRY FAULT Operated Reset RS_OP_ZONE2 CFT Transmitted to IEC Protection;CftPhsPDIF2 ST;Op;general;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400kV BB4_P741_87CUB PROTECTION B/B ZONE-1 Operated Reset RS_OP_ZONE1 Transmitted to IEC Protection;TrpPhsPDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;TrpPhsPDIF2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400kV BB4_P741_87CUB PROTECTION B/B ZONE-2 Operated Reset RS_OP_ZONE2 Transmitted to IEC Protection;TrpPhsPDIF2 ST;Op;general;ACT None 1 #REF!
SPS 400kV BB4_P741_87CUB PROTECTION ZONE MERGE (IF APPLICABLE ) Set Reset RS_ST_ZONE_MRG
SPS 400kV BB4_P741_87CUB PROTECTION BUSBAR ZONE 1 R- PHASE TRIP Operated Reset RS_OP_ZONE1_R Protection;TrpPhsPDIF1 ST;Op;phs1
SPS 400kV BB4_P741_87CUB PROTECTION BUSBAR ZONE 1 Y- PHASE TRIP Operated Reset RS_OP_ZONE1_Y Protection;TrpPhsPDIF1 ST;Op;phs2
SPS 400kV BB4_P741_87CUB PROTECTION BUSBAR ZONE 1 B- PHASE TRIP Operated Reset RS_OP_ZONE1_B Protection;TrpPhsPDIF1 ST;Op;phs3
SPS 400kV BB4_P741_87CUB PROTECTION BUSBAR ZONE 2 R- PHASE TRIP Operated Reset RS_OP_ZONE2_R Protection;TrpPhsPDIF2 ST;Op;phs1
SPS 400kV BB4_P741_87CUB PROTECTION BUSBAR ZONE 2 Y- PHASE TRIP Operated Reset RS_OP_ZONE2_Y Protection;TrpPhsPDIF2 ST;Op;phs2
SPS 400kV BB4_P741_87CUB PROTECTION BUSBAR ZONE 2 B- PHASE TRIP Operated Reset RS_OP_ZONE2_B Protection;TrpPhsPDIF2 ST;Op;phs3
SPS 400kV BB4_P741_87CUB PROTECTION CHECK ZONE Operated Reset RS_OP_CHECKZONE
DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name BB4_P741_87CUB
ANALOG INFORMATION FROM IED IED name BB4_P741_87CUB
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUB
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUB
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUB
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name BB4_P741_87CUB
ANALOG INFORMATION TO IED IED name BB4_P741_87CUB
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name BB4_P741_87CUB
A SPARE 13 ANALOG INFORMATION TO IED IED name BB4_P741_87CUB
COUNTER INFORMATION FROM IED IED name BB4_P741_87CUB
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUB
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUB
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUB
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name BB4_P741_87CUB
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 CCCC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : Site Name
IEC Description
Computer Name 7BB1_P747_87_R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
IED NAME : 7BB1_P747_87_R
DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400KV BB4_B90_87 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_R
SPS 400KV BB4_B90_87 PROTECTION ZONE-1 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind3;stVal;SPS
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLa_Reset_Set SPS 400KV BB4_B90_87 PROTECTION ZONE-2 BUSBAR BLOCKED EXTERNAL Set Reset RS_ST_BB BLOCK E System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name 7BB1_P747_87_R
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLA_Normal_Alarm SPS 400KV BB4_B90_87 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind6;stVal;SPS None Yes 1 #REF!
SPS 400KV BB4_B90_87 PROTECTION ZONE-1 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind7;stVal;SPS
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 400KV BB4_B90_87 PROTECTION ZONE-2 CIRCUITRY FAULT Operated Reset RS_ST_CT_CKT_Err System;GosGGIO2 ST;Ind8;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 400KV BB4_B90_87 SYSTEM BAY 425 LBB Operated Reset RS_OP 425 LBB System;OptGGIO1 ST;Ind2;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 400KV BB4_B90_87 SYSTEM BAY 428 LBB Operated Reset RS_OP 428 LBB System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 400KV BB4_B90_87 SYSTEM BAY 426 LBB Operated Reset RS_OP 426 LBB System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind25;stVal;SPS SPE_HLa_Reset_Set SPS 400KV BB4_B90_87 SYSTEM ZONE-1 MAIN-1 SWITCH IN Set Reset RS_ST Z-1 IN System;OptGGIO1 ST;Ind25;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind27;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400KV BB4_B90_87 SYSTEM BB M2 RELAY R-PH Healthy Unhealthy UH_HL BB M2 RLY System;OptGGIO1 ST;Ind27;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind29;stVal;SPS SPE_HLa_Reset_Set SPS 400KV W SYSTEM ZONE-2 MAIN-1 SWITCH IN Set Reset RS_ST Z-2 IN System;OptGGIO1 ST;Ind29;stVal;SPS None 1 #REF!
A Protection;CznPDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400KV BB4_B90_87 PROTECTION CHECK ZONE DIFF PROT Operated Reset RS_OP_CHK ZONE Protection;CznPDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;BbpT01PDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400KV BB4_B90_87 PROTECTION BUSBAR ZONE1 TRIP Operated Reset RS_OP_BB ZONE1 Protection;BbpT01PDIF1 ST;Op;general;ACT None 1 #REF!
A Protection;BbpT02PDIF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400KV BB4_B90_87 PROTECTION BUSBAR ZONE2 TRIP Operated Reset RS_OP_BB ZONE2 Protection;BbpT02PDIF1 ST;Op;general;ACT None 1 #REF!
SPS 400KV BB4_B90_87 PROTECTION BUSBAR ZONE 1 PROTECTION BLOCKED Set Reset
SPS 400KV BB4_B90_87 PROTECTION BUSBAR ZONE 2 PROTECTION BLOCKED Set Reset
DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name 7BB1_P747_87_R
ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name 7BB1_P747_87_R
ANALOG INFORMATION TO IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_R
A SPARE 13 ANALOG INFORMATION TO IED IED name 7BB1_P747_87_R
COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name 7BB1_P747_87_R
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R401_P444_21M1 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R401_P444_21M1
DIGITAL INFORMATION FROM IED IED name R401_P444_21M1
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R401_P444_21M1 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R401_P444_21M1
A System;AlmGGIO1 ST;Alm6;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION CVT FUSE Alarm Normal RS_OP_VT-FUSE Transmitted to IEC System;AlmGGIO1 ST;Alm6;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R401_P444_21M1
A System;AlmGGIO1 ST;Alm31;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION BROKEN CONDUCTOR Alarm Normal RS_OP_BRKN CND Transmitted to IEC System;AlmGGIO1 ST;Alm31;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R401_P444_21M1
A System;GosGGIO2 ST;Ind15;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R401_P444_21M1 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind15;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 SYSTEM GROUP A TRIP RELAY Operated Reset RS_OP_GRP-A Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 SYSTEM CARRIER CHANNEL-1 Healthy Unhealthy RS_set_CARr1 Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_P444_21M1 SYSTEM LINE ISO OPEN FOR STUB PROTN Set Reset RS_ST_ISO_OE_STU Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_P444_21M1 SYSTEM CB CLOSE CMD SOTF INITIATION Set Reset RS_ST_SOTF Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_NotRec_Recvd SPS 400kV R401_P444_21M1 SYSTEM CARRIER CHANNEL-2 Received Not Received NR_RV_CAR_R_CH2 Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Flty_Healthy SPS 400kV R401_P444_21M1 SYSTEM MAIN-2 RELAY Healthy Faulty FL_HL_M2_RLY Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_NotRec_Recvd SPS 400kV R401_P444_21M1 SYSTEM CARRIER CHANNEL-1 Received Not Received NR_RV_CARR CH1 Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 SYSTEM CARRIER CHANNEL-2 Healthy Unhealthy RS_set_CARr2 Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_NotRec_Recvd SPS 400kV R401_P444_21M1 SYSTEM DIRECT TRIP RECEIVED CH-1 Received Not Received NR_RV_DT_REV_CH1 Transmitted to IEC System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLA_NotRec_Recvd SPS 400kV R401_P444_21M1 SYSTEM DIRECT TRIP RECEIVED CH-2 Received Not Received NR_RV_DT_REV_CH2 Transmitted to IEC System;OptGGIO1 ST;Ind13;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind17;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 SYSTEM GROUP B TRIP RELAY Operated Reset RS_OP_GRP-B Transmitted to IEC System;OptGGIO1 ST;Ind17;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind24;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_P444_21M1 SYSTEM TRIP RELAY 86A SUPERVISION Healthy Unhealthy RS_ST_86A SUPV Transmitted to IEC System;OptGGIO1 ST;Ind24;stVal;SPS None 1 #REF!
A Control;PsbRPSB3 ST;Str;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION POWER SWING DETECTED Set Reset RS_AL_PSB_STR Transmitted to IEC Control;PsbRPSB3 ST;Str;general;ACD None 1 #REF!
A Control;PsbRPSB3 ST;BlkZn;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION POWER SWING BLOCKING Set Reset RS_OP_PWR SW BLK Transmitted to IEC Control;PsbRPSB3 ST;BlkZn;stVal;SPS None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE ZONE-1 R-PH Operated Reset RS_OP_Z1R-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE ZONE-1 Y-PH Operated Reset RS_OP_Z1Y-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE ZONE-1 B-PH Operated Reset RS_OP_Z1B-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE PROTN ZONE-1 Operated Reset RS_OP_ZONE-1 Transmitted to IEC Protection;DisPDIS1 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE ZONE-1 START Set Reset RS_OP_DIS S Z1 Transmitted to IEC Protection;DisPDIS1 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE PROTN ZONE-2 Operated Reset RS_OP_ZONE-2 Transmitted to IEC Protection;DisPDIS2 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsA;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE ZONE-2 START R-PH Set Reset RS_OP_DIS S Z2_R Transmitted to IEC Protection;DisPDIS2 ST;Str;phsA;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsB;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE ZONE-2 START Y-PH Set Reset RS_OP_DIS S Z2_Y Transmitted to IEC Protection;DisPDIS2 ST;Str;phsB;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsC;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE ZONE-2 START B-PH Set Reset RS_OP_DIS S Z2_B Transmitted to IEC Protection;DisPDIS2 ST;Str;phsC;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE ZONE-2 START Set Reset RS_OP_DIS S Z2 Transmitted to IEC Protection;DisPDIS2 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS3 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE PROTN ZONE-3 Operated Reset RS_OP_ZONE-3 Transmitted to IEC Protection;DisPDIS3 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS3 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE ZONE-3 START Set Reset RS_OP_DIS S Z3 Transmitted to IEC Protection;DisPDIS3 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS4 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE PROTN ZONE-4 Operated Reset RS_OP_ZONE-4 Transmitted to IEC Protection;DisPDIS4 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS4 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE ZONE-4 START Set Reset RS_OP_DIS S Z4 Transmitted to IEC Protection;DisPDIS4 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS5 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE PROTN ZONE-5 Operated Reset RS_OP_ZONE-5 Transmitted to IEC Protection;DisPDIS5 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS5 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE ZONE-5 START Set Reset RS_OP_DIS S Z5 Transmitted to IEC Protection;DisPDIS5 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPSCH1 ST;CarRx;general;ACT SPE_HLa_Reset_Set SPS 400kV R401_P444_21M1 PROTECTION CARRIER AIDED SCHEME Operated Reset RS_ST_CARR_AIDED Transmitted to IEC Protection;DisPSCH1 ST;CarRx;general;ACT None 1 #REF!
A Protection;DisPSCH1 ST;ProRx;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_P444_21M1 PROTECTION CARRIER RECEIVE Set Reset RS_ST_CARR REC Transmitted to IEC Protection;DisPSCH1 ST;ProRx;stVal;SPS None 1 #REF!
A Protection;DisPSCH1 ST;ProTx;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_P444_21M1 PROTECTION CARRIER SEND Set Reset RS_ST_CARR SEND Transmitted to IEC Protection;DisPSCH1 ST;ProTx;stVal;SPS None 1 #REF!
A Protection;EfdPTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DIRECTIONAL E/F START Set Reset RS_OP_DIR E/F S Transmitted to IEC Protection;EfdPTOC1 ST;Str;general;general;ACD None 1 #REF!
A Protection;EfdPTOC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DIRECTIONAL E/F Operated Reset RS_OP_DEF Transmitted to IEC Protection;EfdPTOC1 ST;Op;general;general;ACT None 1 #REF!
A Protection;SofPSOF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION SOTF Operated Reset RS_OP_SOTF Transmitted to IEC Protection;SofPSOF1 ST;Op;general;ACT None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION OVERVOLTAGE STAGE-1 Operated Reset RS_OP_O/V-I Transmitted to IEC Protection;VtpPhsPTOV1 ST;Op;general;ACT None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION OVERVOLTAGE STAGE-1 START Set Reset RS_OP_O/V STG1 S Transmitted to IEC Protection;VtpPhsPTOV1 ST;Str;general;general;ACD None 1 #REF!
A Protection;VtpPhsPTOV2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION OVERVOLTAGE STAGE-2 Operated Reset RS_OP_O/V-II Transmitted to IEC Protection;VtpPhsPTOV2 ST;Op;general;ACT None 1 #REF!
A System;GosGGIO1 ST;Ind19;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION STUB PROTECTION Operated Reset RS_OP_STUB System;GosGGIO2 ST;Ind19;stVal;SPS None No 1 #REF!
DIGITAL INFORMATION TO IED IED name R401_P444_21M1
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Protection;DisPDIS2 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE ZONE-2 R-PH TRIP Operated Reset RS_OP_DIS Z1 R Transmitted to IEC Protection;DisPDIS2 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE ZONE-2 Y-PH Operated Reset RS_OP_DIS Z1 Y Transmitted to IEC Protection;DisPDIS2 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P444_21M1 PROTECTION DISTANCE ZONE-2 B-PH Operated Reset RS_OP_DIS Z1 B Transmitted to IEC Protection;DisPDIS2 ST;Op;phsC;general;ACT None 1 #REF!
A SPARE SPS 400kV R401_P444_21M1 PROTECTION DISTANCE BLOCKED Set Reset RS_ST_DIS BLK Protection;DisPDIS ST;BLK 2 #REF!
A SPARE SPS 400kV R401_P444_21M1 PROTECTION DT SEND CH 1 Set Reset RS_ST_DT_CH-1_S 2 #REF!
A SPARE SPS 400kV R401_P444_21M1 PROTECTION DT SEND CH 2 Set Reset RS_ST_DT_CH-2_S 2 #REF!
A SPARE SPS 400kV R401_P444_21M1 SYSTEM BCU RELAY Healthy Unhealthy RS_ST_BCU System;OptGGIO1 ST;Indx;stVal;SPS 2 #REF!
SPS 400kV R401_P444_21M1 SYSTEM PREPARE 3-PH TRIP FROM TIE BCU Set Reset RS_ST_MAIN_3 PH System;OptGGIO1 ST;Indx;stVal;SPS
SPS 400kV R401_P444_21M1 SYSTEM PREPARE 3-PH TRIP FROM MAIN BCU Set Reset RS_ST_TIE_3 PH System;OptGGIO1 ST;Indx;stVal;SPS
SPS 400kV R401_P444_21M1 SYSTEM MAIN/ TIE CB AR OPTD Operated Reset RS_OP_A/R System;OptGGIO1 ST;Indx;stVal;SPS
SPS 400kV R401_P444_21M1 SYSTEM MAIN/ TIE LBB PROTECTION OPERATED Operated Reset RS_OP_LBB System;OptGGIO1 ST;Indx;stVal;SPS
A SPARE 2 #REF!
A SPARE 2 #REF!
ANALOG INFORMATION FROM IED IED name R401_P444_21M1
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Records;PriRFLO1 MX;FltZ;cVal;CMV MV_hla_Fault_Impd Z 400kV R401_P444_21M1 PROTECTION FAULT IMPEDANCE -100.0 100.0 Fltz Transmitted to IEC Records;PriRFLO1 MX;FltZ;cVal;CMV 6 ANALOG INFORMATION FROM IED IED name R401_P444_21M1
A Records;PriRFLO1 MX;FltDiskm;mag;MV MV_Hla_Fault_Dist Km 400kV R401_P444_21M1 PROTECTION FAULT DISTANCE 0.0 1000.0 FltDiskm Transmitted to IEC Records;PriRFLO1 MX;FltDiskm;mag;MV 6 ANALOG INFORMATION FROM IED IED name R401_P444_21M1
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P444_21M1
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P444_21M1
ANALOG INFORMATION TO IED IED name R401_P444_21M1
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R401_P444_21M1
A SPARE 13 ANALOG INFORMATION TO IED IED name R401_P444_21M1
COUNTER INFORMATION FROM IED IED name R401_P444_21M1
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P444_21M1
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R401_P444_21M1 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R401_P444_21M1
DIGITAL INFORMATION FROM IED IED name R401_P444_21M1
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R401_D60_21M1 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R401_P444_21M1
A System;AlmGGIO1 ST;Alm6;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION CVT FUSE Alarm Normal RS_OP_VT-FUSE Transmitted to IEC System;AlmGGIO1 ST;Alm6;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R401_P444_21M1
A System;AlmGGIO1 ST;Alm31;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION BROKEN CONDUCTOR Alarm Normal RS_OP_BRKN CND Transmitted to IEC System;AlmGGIO1 ST;Alm31;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R401_P444_21M1
A System;GosGGIO2 ST;Ind15;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R401_D60_21M1 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind15;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 SYSTEM GROUP A TRIP RELAY Operated Reset RS_OP_GRP-A Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 SYSTEM CARRIER CHANNEL-1 Healthy Unhealthy RS_set_CARr1 Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_D60_21M1 SYSTEM LINE ISO OPEN FOR STUB PROTN Set Reset RS_ST_ISO_OE_STU Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_D60_21M1 SYSTEM CB CLOSE CMD SOTF INITIATION Set Reset RS_ST_SOTF Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_NotRec_Recvd SPS 400kV R401_D60_21M1 SYSTEM CARRIER CHANNEL-2 Received Not Received NR_RV_CAR_R_CH2 Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Flty_Healthy SPS 400kV R401_D60_21M1 SYSTEM MAIN-2 RELAY Healthy Faulty FL_HL_M2_RLY Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_NotRec_Recvd SPS 400kV R401_D60_21M1 SYSTEM CARRIER CHANNEL-1 Received Not Received NR_RV_CARR CH1 Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 SYSTEM CARRIER CHANNEL-2 Healthy Unhealthy RS_set_CARr2 Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_NotRec_Recvd SPS 400kV R401_D60_21M1 SYSTEM DIRECT TRIP RECEIVED CH-1 Received Not Received NR_RV_DT_REV_CH1 Transmitted to IEC System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLA_NotRec_Recvd SPS 400kV R401_D60_21M1 SYSTEM DIRECT TRIP RECEIVED CH-2 Received Not Received NR_RV_DT_REV_CH2 Transmitted to IEC System;OptGGIO1 ST;Ind13;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind17;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 SYSTEM GROUP B TRIP RELAY Operated Reset RS_OP_GRP-B Transmitted to IEC System;OptGGIO1 ST;Ind17;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind24;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_D60_21M1 SYSTEM TRIP RELAY 86A SUPERVISION Healthy Unhealthy RS_ST_86A SUPV Transmitted to IEC System;OptGGIO1 ST;Ind24;stVal;SPS None 1 #REF!
A Control;PsbRPSB3 ST;Str;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION POWER SWING DETECTED Set Reset RS_AL_PSB_STR Transmitted to IEC Protection;PwrSwgRPSB1 ST;Str None 1 #REF!
A Control;PsbRPSB3 ST;BlkZn;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION POWER SWING BLOCKING Set Reset RS_OP_PWR SW BLK Transmitted to IEC Protection;PwrSwgRPSB1 ST;BlkZn None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Prot.TrOutPTRC1 ST;Tr None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE ZONE-1 R-PH TRIP Operated Reset RS_OP_Z1R-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phs1 None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE ZONE-1 Y-PH TRIP Operated Reset RS_OP_Z1Y-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phs2 None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE ZONE-1 B-PH TRIP Operated Reset RS_OP_Z1B-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phs3 None 1 #REF!
A Protection;DisPDIS1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE PROTN ZONE-1 Operated Reset RS_OP_ZONE-1 Transmitted to IEC Protection;DisPDIS1 ST;Op None 1 #REF!
A Protection;DisPDIS1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE ZONE-1 START Set Reset RS_OP_DIS S Z1 Transmitted to IEC Protection;DisPDIS1 ST;Str None 1 #REF!
A Protection;DisPDIS2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE PROTN ZONE-2 Operated Reset RS_OP_ZONE-2 Transmitted to IEC Protection;DisPDIS2 ST;Op None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsA;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE ZONE-2 START R-PH Set Reset RS_OP_DIS S Z2_R Transmitted to IEC Protection;DisPDIS2 ST;str;phs1 None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsB;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE ZONE-2 START Y-PH Set Reset RS_OP_DIS S Z2_Y Transmitted to IEC Protection;DisPDIS2 ST;str;phs2 None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsC;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE ZONE-2 START B-PH Set Reset RS_OP_DIS S Z2_B Transmitted to IEC Protection;DisPDIS2 ST;str;phs3 None 1 #REF!
A Protection;DisPDIS2 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE ZONE-2 START Set Reset RS_OP_DIS S Z2 Transmitted to IEC Protection;DisPDIS2 ST;Str None 1 #REF!
A Protection;DisPDIS3 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE PROTN ZONE-3 Operated Reset RS_OP_ZONE-3 Transmitted to IEC Protection;DisPDIS3 ST;Op None 1 #REF!
A Protection;DisPDIS3 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE ZONE-3 START Set Reset RS_OP_DIS S Z3 Transmitted to IEC Protection;DisPDIS3 ST;Str None 1 #REF!
A Protection;DisPDIS4 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE PROTN ZONE-4 Operated Reset RS_OP_ZONE-4 Transmitted to IEC Protection;DisPDIS4 ST;Op None 1 #REF!
A Protection;DisPDIS4 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE ZONE-4 START Set Reset RS_OP_DIS S Z4 Transmitted to IEC Protection;DisPDIS4 ST;Str None 1 #REF!
A Protection;DisPDIS5 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE PROTN ZONE-5 Operated Reset RS_OP_ZONE-5 Transmitted to IEC Protection;DisPDIS5 ST;Op None 1 #REF!
A Protection;DisPDIS5 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE ZONE-5 START Set Reset RS_OP_DIS S Z5 Transmitted to IEC Protection;DisPDIS5 ST;Str None 1 #REF!
A Protection;DisPSCH1 ST;CarRx;general;ACT SPE_HLa_Reset_Set SPS 400kV R401_D60_21M1 PROTECTION CARRIER AIDED SCHEME Operated Reset RS_ST_CARR_AIDED Transmitted to IEC Protection;DisPSCH1 ST;CarRx None 1 #REF!
A Protection;DisPSCH1 ST;ProRx;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_D60_21M1 PROTECTION CARRIER RECEIVE Set Reset RS_ST_CARR REC Transmitted to IEC Protection;DisPSCH1 ST;ProRx None 1 #REF!
A Protection;DisPSCH1 ST;ProTx;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_D60_21M1 PROTECTION CARRIER SEND Set Reset RS_ST_CARR SEND Transmitted to IEC Protection;DisPSCH1 ST;ProTx None 1 #REF!
A Protection;EfdPTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DIRECTIONAL E/F START Set Reset RS_OP_DIR E/F S Transmitted to IEC Prot.NeuTocPTOC1 ST;Str None 1 #REF!
A Protection;EfdPTOC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DIRECTIONAL E/F Operated Reset RS_OP_DEF Transmitted to IEC Prot.NeuTocPTOC1 ST;Op None 1 #REF!
A Protection;SofPSOF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION SOTF Operated Reset RS_OP_SOTF Transmitted to IEC Protection;SofPSOF ST;Op None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION OVERVOLTAGE STAGE-1 Operated Reset RS_OP_O/V-I Transmitted to IEC Prot.PhsOvPTOV1 ST;Str None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION OVERVOLTAGE STAGE-1 START Set Reset RS_OP_O/V STG1 S Transmitted to IEC Prot.PhsOvPTOV1 ST;Op None 1 #REF!
A Protection;VtpPhsPTOV2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION OVERVOLTAGE STAGE-2 Operated Reset RS_OP_O/V-II Transmitted to IEC Prot.PhsOvPTOV2 ST;Op None 1 #REF!
A System;GosGGIO1 ST;Ind19;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION STUB PROTECTION Operated Reset RS_OP_STUB System;GosGGIO2 ST;Ind19;stVal;SPS None No 1 #REF!
DIGITAL INFORMATION TO IED IED name R401_P444_21M1
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Protection;DisPDIS2 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE ZONE-2 R-PH Operated Reset RS_OP_DIS Z1 R Transmitted to IEC Protection;DisPDIS2 ST;Op;phs1 None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE ZONE-2 Y-PH Operated Reset RS_OP_DIS Z1 Y Transmitted to IEC Protection;DisPDIS2 ST;Op;phs2 None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_D60_21M1 PROTECTION DISTANCE ZONE-2 B-PH Operated Reset RS_OP_DIS Z1 B Transmitted to IEC Protection;DisPDIS2 ST;Op;phs3 None 1 #REF!
A SPARE SPS 400kV R401_D60_21M1 PROTECTION DISTANCE BLOCKED Set Reset RS_ST_DIS BLK Protection;DisPDIS ST;BLK 2 #REF!
A SPARE SPS 400kV R401_D60_21M1 PROTECTION DT SEND CH 1 Set Reset RS_ST_DT_CH-1_S 2 #REF!
A SPARE SPS 400kV R401_D60_21M1 PROTECTION DT SEND CH 2 Set Reset RS_ST_DT_CH-2_S 2 #REF!
A SPARE SPS 400kV R401_D60_21M1 SYSTEM BCU RELAY Healthy Unhealthy RS_ST_BCU System;OptGGIO1 ST;Indx;stVal;SPS 2 #REF!
SPS 400kV R401_D60_21M1 SYSTEM PREPARE 3-PH TRIP FROM TIE BCU Set Reset RS_ST_MAIN_3 PH System;OptGGIO1 ST;Indx;stVal;SPS
SPS 400kV R401_D60_21M1 SYSTEM PREPARE 3-PH TRIP FROM MAIN BCU Set Reset RS_ST_TIE_3 PH System;OptGGIO1 ST;Indx;stVal;SPS
SPS 400kV R401_D60_21M1 SYSTEM MAIN/ TIE CB AR OPTD Operated Reset RS_OP_A/R System;OptGGIO1 ST;Indx;stVal;SPS
SPS 400kV R401_D60_21M1 SYSTEM MAIN/ TIE LBB PROTECTION OPERATED Operated Reset RS_OP_LBB System;OptGGIO1 ST;Indx;stVal;SPS
A SPARE SPC 2 #REF!
A SPARE SPC 2 #REF!
ANALOG INFORMATION FROM IED IED name R401_P444_21M1
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Records;PriRFLO1 MX;FltZ;cVal;CMV MV_hla_Fault_Impd Z 400kV R401_P444_21M1 PROTECTION FAULT IMPEDANCE -100.0 100.0 Fltz Transmitted to IEC Records;PriRFLO1 MX;FltZ;cVal;CMV 6 ANALOG INFORMATION FROM IED IED name R401_P444_21M1
A Records;PriRFLO1 MX;FltDiskm;mag;MV MV_Hla_Fault_Dist Km 400kV R401_P444_21M1 PROTECTION FAULT DISTANCE 0.0 1000.0 FltDiskm Transmitted to IEC Records;PriRFLO1 MX;FltDiskm;mag;MV 6 ANALOG INFORMATION FROM IED IED name R401_P444_21M1
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P444_21M1
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P444_21M1
ANALOG INFORMATION TO IED IED name R401_P444_21M1
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R401_P444_21M1
A SPARE 13 ANALOG INFORMATION TO IED IED name R401_P444_21M1
COUNTER INFORMATION FROM IED IED name R401_P444_21M1
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P444_21M1
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R401_P444_21M1 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R401_P444_21M1
DIGITAL INFORMATION FROM IED IED name R401_P444_21M1
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R401_L90_21M1 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R401_P444_21M1
A System;AlmGGIO1 ST;Alm6;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION CVT FUSE Alarm Normal RS_OP_VT-FUSE Transmitted to IEC System;AlmGGIO1 ST;Alm6;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R401_P444_21M1
A System;AlmGGIO1 ST;Alm31;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION BROKEN CONDUCTOR Alarm Normal RS_OP_BRKN CND Transmitted to IEC System;AlmGGIO1 ST;Alm31;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R401_P444_21M1
A System;GosGGIO2 ST;Ind15;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R401_L90_21M1 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind15;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 SYSTEM GROUP A TRIP RELAY Operated Reset RS_OP_GRP-A Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 SYSTEM CARRIER CHANNEL-1 Healthy Unhealthy RS_set_CARr1 Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_L90_21M1 SYSTEM LINE ISO OPEN FOR STUB PROTN Set Reset RS_ST_ISO_OE_STU Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_L90_21M1 SYSTEM CB CLOSE CMD SOTF INITIATION Set Reset RS_ST_SOTF Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_NotRec_Recvd SPS 400kV R401_L90_21M1 SYSTEM CARRIER CHANNEL-2 Received Not Received NR_RV_CAR_R_CH2 Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Flty_Healthy SPS 400kV R401_L90_21M1 SYSTEM MAIN-2 RELAY Healthy Faulty FL_HL_M2_RLY Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_NotRec_Recvd SPS 400kV R401_L90_21M1 SYSTEM CARRIER CHANNEL-1 Received Not Received NR_RV_CARR CH1 Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 SYSTEM CARRIER CHANNEL-2 Healthy Unhealthy RS_set_CARr2 Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_NotRec_Recvd SPS 400kV R401_L90_21M1 SYSTEM DIRECT TRIP RECEIVED CH-1 Received Not Received NR_RV_DT_REV_CH1 Transmitted to IEC System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLA_NotRec_Recvd SPS 400kV R401_L90_21M1 SYSTEM DIRECT TRIP RECEIVED CH-2 Received Not Received NR_RV_DT_REV_CH2 Transmitted to IEC System;OptGGIO1 ST;Ind13;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind17;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 SYSTEM GROUP B TRIP RELAY Operated Reset RS_OP_GRP-B Transmitted to IEC System;OptGGIO1 ST;Ind17;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind24;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_L90_21M1 SYSTEM TRIP RELAY 86B SUPERVISION Healthy Unhealthy RS_ST_86A SUPV Transmitted to IEC System;OptGGIO1 ST;Ind24;stVal;SPS None 1 #REF!
A Control;PsbRPSB3 ST;Str;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION POWER SWING DETECTED Set Reset RS_AL_PSB_STR Transmitted to IEC Protection;PwrSwgRPSB1 ST;Str None 1 #REF!
A Control;PsbRPSB3 ST;BlkZn;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION POWER SWING BLOCKING Set Reset RS_OP_PWR SW BLK Transmitted to IEC Protection;PwrSwgRPSB1 ST;BlkZn None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Prot.TrOutPTRC1 ST;Tr None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE ZONE-1 R-PH Operated Reset RS_OP_Z1R-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phs1 None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE ZONE-1 Y-PH Operated Reset RS_OP_Z1Y-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phs2 None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE ZONE-1 B-PH Operated Reset RS_OP_Z1B-PH Transmitted to IEC Protection;DisPDIS1 ST;Op;phs3 None 1 #REF!
A Protection;DisPDIS1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE PROTN ZONE-1 Operated Reset RS_OP_ZONE-1 Transmitted to IEC Protection;DisPDIS1 ST;Op None 1 #REF!
A Protection;DisPDIS1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE ZONE-1 START Set Reset RS_OP_DIS S Z1 Transmitted to IEC Protection;DisPDIS1 ST;Str None 1 #REF!
A Protection;DisPDIS2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE PROTN ZONE-2 Operated Reset RS_OP_ZONE-2 Transmitted to IEC Protection;DisPDIS2 ST;Op None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsA;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE ZONE-2 START R-PH Set Reset RS_OP_DIS S Z2_R Transmitted to IEC Protection;DisPDIS2 ST;str;phs1 None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsB;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE ZONE-2 START Y-PH Set Reset RS_OP_DIS S Z2_Y Transmitted to IEC Protection;DisPDIS2 ST;str;phs2 None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsC;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE ZONE-2 START B-PH Set Reset RS_OP_DIS S Z2_B Transmitted to IEC Protection;DisPDIS2 ST;str;phs3 None 1 #REF!
A Protection;DisPDIS2 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE ZONE-2 START Set Reset RS_OP_DIS S Z2 Transmitted to IEC Protection;DisPDIS2 ST;Str None 1 #REF!
A Protection;DisPDIS3 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE PROTN ZONE-3 Operated Reset RS_OP_ZONE-3 Transmitted to IEC Protection;DisPDIS3 ST;Op None 1 #REF!
A Protection;DisPDIS3 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE ZONE-3 START Set Reset RS_OP_DIS S Z3 Transmitted to IEC Protection;DisPDIS3 ST;Str None 1 #REF!
A Protection;DisPDIS4 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE PROTN ZONE-4 Operated Reset RS_OP_ZONE-4 Transmitted to IEC Protection;DisPDIS4 ST;Op None 1 #REF!
A Protection;DisPDIS4 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE ZONE-4 START Set Reset RS_OP_DIS S Z4 Transmitted to IEC Protection;DisPDIS4 ST;Str None 1 #REF!
A Protection;DisPDIS5 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE PROTN ZONE-5 Operated Reset RS_OP_ZONE-5 Transmitted to IEC Protection;DisPDIS5 ST;Op None 1 #REF!
A Protection;DisPDIS5 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE ZONE-5 START Set Reset RS_OP_DIS S Z5 Transmitted to IEC Protection;DisPDIS5 ST;Str None 1 #REF!
A Protection;DisPSCH1 ST;CarRx;general;ACT SPE_HLa_Reset_Set SPS 400kV R401_L90_21M1 PROTECTION CARRIER AIDED SCHEME Operated Reset RS_ST_CARR_AIDED Transmitted to IEC Protection;DisPSCH1 ST;CarRx None 1 #REF!
A Protection;DisPSCH1 ST;ProRx;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_L90_21M1 PROTECTION CARRIER RECEIVE Set Reset RS_ST_CARR REC Transmitted to IEC Protection;DisPSCH1 ST;ProRx None 1 #REF!
A Protection;DisPSCH1 ST;ProTx;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_L90_21M1 PROTECTION CARRIER SEND Set Reset RS_ST_CARR SEND Transmitted to IEC Protection;DisPSCH1 ST;ProTx None 1 #REF!
A Protection;EfdPTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DIRECTIONAL E/F START Set Reset RS_OP_DIR E/F S Transmitted to IEC Prot.NeuTocPTOC1 ST;Str None 1 #REF!
A Protection;EfdPTOC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DIRECTIONAL E/F Operated Reset RS_OP_DEF Transmitted to IEC Prot.NeuTocPTOC1 ST;Op None 1 #REF!
A Protection;SofPSOF1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION SOTF Operated Reset RS_OP_SOTF Transmitted to IEC Protection;SofPSOF ST;Op None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION OVERVOLTAGE STAGE-1 Operated Reset RS_OP_O/V-I Transmitted to IEC Prot.PhsOvPTOV1 ST;Str None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION OVERVOLTAGE STAGE-1 START Set Reset RS_OP_O/V STG1 S Transmitted to IEC Prot.PhsOvPTOV1 ST;Op None 1 #REF!
A Protection;VtpPhsPTOV2 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION OVERVOLTAGE STAGE-2 Operated Reset RS_OP_O/V-II Transmitted to IEC Prot.PhsOvPTOV2 ST;Op None 1 #REF!
A System;GosGGIO1 ST;Ind19;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION STUB PROTECTION Operated Reset RS_OP_STUB System;GosGGIO2 ST;Ind19;stVal;SPS None No 1 #REF!
SPS 400kV R401_L90_21M1 PROTECTION LINE DIFFERENTIAL R PH Operated Reset RS_OP_DIF R Transmitted to IEC
SPS 400kV R401_L90_21M1 PROTECTION LINE DIFFERENTIAL Y PH Operated Reset RS_OP_DIF Y Transmitted to IEC
SPS 400kV R401_L90_21M1 PROTECTION LINE DIFFERENTIAL B PH Operated Reset RS_OP_DIF B Transmitted to IEC
SPS 400kV R401_L90_21M1 PROTECTION LINE DIFFERENTIAL Start Reset RS_ST_DIF Transmitted to IEC
SPS 400kV R401_L90_21M1 PROTECTION DIFFERENTIAL COMMUNICATION FAIL Set Reset RS_ST_DIFF_COM
SPS 400kV R401_L90_21M1 PROTECTION DIFFERENTIAL BLOCKED Set Reset RS_ST_DIFF_BLK
SPS 400kV R401_L90_21M1 PROTECTION DISTANCE ENABLED Set Reset RS_ST_DIS_EN
DIGITAL INFORMATION TO IED IED name R401_P444_21M1
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Protection;DisPDIS2 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE ZONE-2 R-PH TRIP Operated Reset RS_OP_DIS Z1 R Transmitted to IEC Protection;DisPDIS2 ST;Op;phs1 None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE ZONE-2 Y-PH TRIP Operated Reset RS_OP_DIS Z1 Y Transmitted to IEC Protection;DisPDIS2 ST;Op;phs2 None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_L90_21M1 PROTECTION DISTANCE ZONE-2 B-PH TRIP Operated Reset RS_OP_DIS Z1 B Transmitted to IEC Protection;DisPDIS2 ST;Op;phs3 None 1 #REF!
A SPARE SPS 400kV R401_L90_21M1 PROTECTION DISTANCE BLOCKED Set Reset RS_ST_DIS BLK Protection;DisPDIS ST;BLK 2 #REF!
A SPARE SPS 400kV R401_L90_21M1 PROTECTION DT SEND CH 1 Set Reset RS_ST_DT_CH-1_S 2 #REF!
A SPARE SPS 400kV R401_L90_21M1 PROTECTION DT SEND CH 2 Set Reset RS_ST_DT_CH-2_S 2 #REF!
A SPARE SPS 400kV R401_L90_21M1 SYSTEM BCU RELAY Healthy Unhealthy RS_ST_BCU System;OptGGIO1 ST;Indx;stVal;SPS 2 #REF!
SPS 400kV R401_L90_21M1 SYSTEM PREPARE 3-PH TRIP FROM TIE BCU Set Reset RS_ST_MAIN_3 PH System;OptGGIO1 ST;Indx;stVal;SPS
SPS 400kV R401_L90_21M1 SYSTEM PREPARE 3-PH TRIP FROM MAIN BCU Set Reset RS_ST_TIE_3 PH System;OptGGIO1 ST;Indx;stVal;SPS
SPS 400kV R401_L90_21M1 SYSTEM MAIN/ TIE CB AR OPTD Operated Reset RS_OP_A/R System;OptGGIO1 ST;Indx;stVal;SPS
SPS 400kV R401_L90_21M1 SYSTEM MAIN/ TIE LBB PROTECTION OPERATED Operated Reset RS_OP_LBB System;OptGGIO1 ST;Indx;stVal;SPS
A SPARE SPC 2 #REF!
A SPARE SPC 2 #REF!
ANALOG INFORMATION FROM IED IED name R401_P444_21M1
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Records;PriRFLO1 MX;FltZ;cVal;CMV MV_hla_Fault_Impd Z 400kV R401_P444_21M1 PROTECTION FAULT IMPEDANCE -100.0 100.0 Fltz Transmitted to IEC Records;PriRFLO1 MX;FltZ;cVal;CMV 6 ANALOG INFORMATION FROM IED IED name R401_P444_21M1
A Records;PriRFLO1 MX;FltDiskm;mag;MV MV_Hla_Fault_Dist Km 400kV R401_P444_21M1 PROTECTION FAULT DISTANCE 0.0 1000.0 FltDiskm Transmitted to IEC Records;PriRFLO1 MX;FltDiskm;mag;MV 6 ANALOG INFORMATION FROM IED IED name R401_P444_21M1
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P444_21M1
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P444_21M1
ANALOG INFORMATION TO IED IED name R401_P444_21M1
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R401_P444_21M1
A SPARE 13 ANALOG INFORMATION TO IED IED name R401_P444_21M1
COUNTER INFORMATION FROM IED IED name R401_P444_21M1
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P444_21M1
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P444_21M1
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R401_P546_21M2 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R401_P546_21M2
DIGITAL INFORMATION FROM IED IED name R401_P546_21M2
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R401_P546_21M2 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R401_P546_21M2
A System;AlmGGIO1 ST;Alm6;stVal;SPS SPE_HLA_Normal_Fail SPS 400kV R401_P546_21M2 PROTECTION CVT FUSE FAIL Alarm Normal NL_FL_CVT FUSE Transmitted to IEC System;AlmGGIO1 ST;Alm6;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R401_P546_21M2
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R401_P546_21M2 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind13;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R401_P546_21M2 PROTECTION BROKEN CONDUCTOR Alarm Normal NL_AL_BROKEN CON Transmitted to IEC System;AlmGGIO1 ST;Ind31;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400kV R401_P546_21M2 SYSTEM CARRIER CHANNEL-2 Healthy Unhealthy UN_HL_CARR CH-2 Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 SYSTEM 86B TRIP RLY Operated Reset RS_OP_86B RLY Transmitted to IEC System;OptGGIO1 ST;Ind2;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 SYSTEM MAIN -1 PROTECTION Operated Reset RS_OP_M1 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400kV R401_P546_21M2 SYSTEM TRIP RELAY 86B SUPERVISION Healthy Unhealthy UN_HL_86B SUPV Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind19;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400kV R401_P546_21M2 SYSTEM BCU HEALTHY Healthy Unhealthy UN_HL_BCU Transmitted to IEC System;OptGGIO1 ST;Ind19;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind20;stVal;SPS SPE_HLA_NotRec_Recvd SPS 400kV R401_P546_21M2 SYSTEM CARRIER CHANNEL-2 Received Not Received NR_RV_CARR CH-2 Transmitted to IEC System;OptGGIO1 ST;Ind20;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind21;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400kV R401_P546_21M2 SYSTEM MAIN-1 RELAY Healthy Unhealthy UN_HL_M1 Transmitted to IEC System;OptGGIO1 ST;Ind21;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind22;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R401_P546_21M2 SYSTEM LINE ISOL OPEN FOR STUB PROTN Set Reset NL_AL_ISO Transmitted to IEC System;OptGGIO1 ST;Ind22;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind23;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R401_P546_21M2 SYSTEM SOTF INITIATION Set Reset NL_AL_SOTF Transmitted to IEC System;OptGGIO1 ST;Ind23;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind24;stVal;SPS SPE_HLA_NotRec_Recvd SPS 400kV R401_P546_21M2 SYSTEM CARRIER CHANNEL-1 Received Not Received NR_RV_CARR CH-1 Transmitted to IEC System;OptGGIO1 ST;Ind24;stVal;SPS None 1 #REF!
A Control;PsbRPSB3 ST;Str1;general;ACD SPE_HLA_Normal_Alarm SPS 400kV R401_P546_21M2 PROTECTION POWER SWING DETECTED Set Reset NL_AL_PWR SW DET Transmitted to IEC Control;PsbRPSB3 ST;Str;general;ACD None 1 #REF!
A Control;PsbRPSB3 ST;BlkZn;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION POWER SWING BLOCKING Set Reset RS_OP_PWR SW BLK Transmitted to IEC Control;PsbRPSB3 ST;BlkZn;stVal;SPS None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION LINE DIFFERENTIAL Operated Reset RS_OP_DIF Transmitted to IEC Protection;DifPDIF1 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-1 R-PH Operated Reset RS_OP_DIS Z1 R Transmitted to IEC Protection;DisPDIS1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-1 Y-PH Operated Reset RS_OP_DIS Z1 Y Transmitted to IEC Protection;DisPDIS1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-1 B-PH Operated Reset RS_OP_DIS Z1 B Transmitted to IEC Protection;DisPDIS1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-1 Operated Reset RS_OP_DIS Z1 Transmitted to IEC Protection;DisPDIS1 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-1 START Set Reset RS_OP_DIS S Z1 Transmitted to IEC Protection;DisPDIS1 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-2 Operated Reset RS_OP_DIS Z2 Transmitted to IEC Protection;DisPDIS2 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-2 START Set Reset RS_OP_DIS S Z2 Transmitted to IEC Protection;DisPDIS2 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS3 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-3 Operated Reset RS_OP_DIS Z3 Transmitted to IEC Protection;DisPDIS3 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS3 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-3 START Set Reset RS_OP_DIS S Z3 Transmitted to IEC Protection;DisPDIS3 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPDIS4 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-4 Operated Reset RS_OP_DIS Z4 Transmitted to IEC Protection;DisPDIS4 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS4 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-4 START Set Reset RS_OP_DIS S Z4 Transmitted to IEC Protection;DisPDIS4 ST;Str;general;general;ACD None 1 #REF!
A Protection;EfdPTOC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DIRECTIONAL E/F Operated Reset RS_OP_DIR E/F Transmitted to IEC Protection;EfdPTOC1 ST;Op;general;general;ACT None 1 #REF!
A Protection;EfdPTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DIRECTIONAL E/F START Set Reset RS_OP_DIR E/F S Transmitted to IEC Protection;EfdPTOC1 ST;Str;general;general;ACD None 1 #REF!
A Protection;SofPSOF1 ST;Op1;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION SOTF Operated Reset RS_OP_SOTF Transmitted to IEC Protection;SofPSOF1 ST;Op1;general;ACT None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION OVERVOLTAGE STAGE-1 Operated Reset RS_OP_O/V STG1 Transmitted to IEC Protection;VtpPhsPTOV1 ST;Op;general;general;ACT None 1 #REF!
A Protection;VtpPhsPTOV1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION OVERVOLTAGE STAGE-1 START Set Reset RS_OP_O/V STG1 S Transmitted to IEC Protection;VtpPhsPTOV1 ST;Str;general;general;ACD None 1 #REF!
A Protection;VtpPhsPTOV2 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION OVERVOLTAGE STAGE-2 Operated Reset RS_OP_O/V STG2 Transmitted to IEC Protection;VtpPhsPTOV2 ST;Op;general;general;ACT None 1 #REF!
A System;GosGGIO1 ST;Ind19;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION STUB PROTECTION Operated Reset RS_OP_STUB System;GosGGIO2 ST;Ind7;stVal;SPS None No 1 0
DIGITAL INFORMATION TO IED IED name R401_P546_21M2
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Protection;DisPDIS5 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-5 START Set Reset RS_OP_DIS S Z5 Transmitted to IEC Protection;DisPDIS5 ST;Str;general;general;ACD None 1 #REF!
A Protection;DisPSCH1 ST;ProRx;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_P546_21M2 PROTECTION CARRIER RECEIVE Set Reset RS_ST_CARR REC Transmitted to IEC Protection;DisPSCH1 ST;ProRx;stVal;SPS None 1 #REF!
A Protection;DisPSCH1 ST;ProTx;stVal;SPS SPE_HLa_Reset_Set SPS 400kV R401_P546_21M2 PROTECTION CARRIER SEND Set Reset RS_ST_CARR SEND Transmitted to IEC Protection;DisPSCH1 ST;ProTx;stVal;SPS None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-2 R-PH Operated Reset RS_OP_DIS Z2 R Transmitted to IEC Protection;DisPDIS2 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-2 Y-PH Operated Reset RS_OP_DIS Z2 Y Transmitted to IEC Protection;DisPDIS2 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-2 B-PH Operated Reset RS_OP_DIS Z2 B Transmitted to IEC Protection;DisPDIS2 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsA;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-2 START R-PH Set Reset RS_OP_DIS S Z2 R Transmitted to IEC Protection;DisPDIS2 ST;Str;phsA;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsB;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-2 START Y-PH Set Reset RS_OP_DIS S Z2 Y Transmitted to IEC Protection;DisPDIS2 ST;Str;phsB;general;ACD None 1 #REF!
A Protection;DisPDIS2 ST;Str;phsC;general;ACD SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-2 START B-PH Set Reset RS_OP_DIS S Z2 B Transmitted to IEC Protection;DisPDIS2 ST;Str;phsC;general;ACD None 1 #REF!
A Protection;DisPDIS4 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION DISTANCE ZONE-5 Operated Reset RS_OP_DIS Z5 Transmitted to IEC Protection;DisPDIS5 ST;Op;general;general;ACT None 1 #REF!
A SPARE SPC 400kV R401_P546_21M2 PROTECTION CARRIER AIDED SCHEME Operated Reset RS_ST_CARR_AIDED Transmitted to IEC Protection;DisPSCH1 ST;CarRx;general;ACT 2 #REF!
A Protection;DifPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P546_21M2 PROTECTION LINE DIFFERENTIAL R PH Operated Reset RS_OP_DIF R Transmitted to IEC Protection;DifPDIF1 ST;Op;phsA;general;ACT None 1 #REF!
A SPARE SPC 400kV R401_P546_21M2 PROTECTION LINE DIFFERENTIAL Y PH Operated Reset RS_OP_DIF Y Transmitted to IEC Protection;DifPDIF1 ST;Op;phsB;general;ACT 2 #REF!
A SPARE SPC 400kV R401_P546_21M2 PROTECTION LINE DIFFERENTIAL B PH Operated Reset RS_OP_DIF B Transmitted to IEC Protection;DifPDIF1 ST;Op;phsC;general;ACT 2 #REF!
A SPARE SPS 400kV R401_P546_21M2 PROTECTION LINE DIFFERENTIAL START Reset RS_ST_DIF Transmitted to IEC Protection;DifPDIF1 ST;Str;general;general;ACT 2 #REF!
SPS 400kV R401_P546_21M2 SYSTEM CARRIER CHANNEL-1 Healthy Unhealthy UN_HL_CARR CH-1 Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS
SPS 400kV R401_P546_21M2 SYSTEM DIRECT TRIP CHANNEL-1 RECEIVED NOT RECEIVED NR_RC_DT-1 Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS
A SPARE SPS 400kV R401_P546_21M2 SYSTEM DIRECT TRIP CHANNEL-2 RECEIVED NOT RECEIVED NR_RC_DT-2 Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS 2 #REF!
SPS 400kV R401_P546_21M3 PROTECTION DISTANCE ENABLED Set Reset RS_ST_DIS_EN
SPS 400kV R401_P546_21M4 PROTECTION DT SEND CH 1 Set Reset RS_ST_DT_CH-1_S
SPS 400kV R401_P546_21M5 PROTECTION DT SEND CH 2 Set Reset RS_ST_DT_CH-2_S
SPS 400kV R401_P546_21M6 SYSTEM MAIN/ TIE CB AR OPTD Operated Reset RS_OP_A/R System;OptGGIO1 ST;Indx;stVal;SPS
SPS 400kV R401_P546_21M7 SYSTEM MAIN/ TIE LBB PROTECTION OPERATED Operated Reset RS_OP_LBB System;OptGGIO1 ST;Indx;stVal;SPS
SPS 400kV R401_P546_21M9 SYSTEM BCU RELAY Healthy Unhealthy RS_ST_BCU System;OptGGIO1 ST;Indx;stVal;SPS
SPS 400kV R401_P546_21M9 PROTECTION DIFFERENTIAL COMMUNICATION FAIL Set Reset RS_ST_DIFF_COM
SPS 400kV R401_P546_21M10 PROTECTION DIFFERENTIAL BLOCKED Set Reset RS_ST_DIFF_BLK
ANALOG INFORMATION FROM IED IED name R401_P546_21M2
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Records;RFLO1 MX;FltZ;cVal;CMV MV_hla_Fault_Impd_2 Z 400kV R401_P546_21M2 RECORDS Fltz -100.0 100.0 Fltz Transmitted to IEC Records;RFLO1 MX;FltZ;cVal;CMV 6 ANALOG INFORMATION FROM IED IED name R401_P546_21M2
A Records;RFLO1 MX;FltDiskm;mag;MV MV_Hla_Fault_Dist_1 Km 400kV R401_P546_21M2 RECORDS FltDiskm 0.0 1000.0 FltDiskm Transmitted to IEC Records;RFLO1 MX;FltDiskm;mag;MV 6 ANALOG INFORMATION FROM IED IED name R401_P546_21M2
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P546_21M2
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P546_21M2
ANALOG INFORMATION TO IED IED name R401_P546_21M2
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R401_P546_21M2
A SPARE 13 ANALOG INFORMATION TO IED IED name R401_P546_21M2
COUNTER INFORMATION FROM IED IED name R401_P546_21M2
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P546_21M2
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P546_21M2
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P546_21M2
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P546_21M2
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R401_P743_PU_A GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R401_P743_PU_A
DIGITAL INFORMATION FROM IED IED name R401_P743_PU_A
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R401_P743_PU_A PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R401_P743_PU_A
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R401_P743_PU_A PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R401_P743_PU_A
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_A GOOSE LBB START Set Reset RS_OP_LBB START Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R401_P743_PU_A
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_A SYSTEM LBB INITIATION 3-PH set Reset RS_OP_LBB INI 3P Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_A SYSTEM LBB INITIATION R-PH set Reset RS_OP_LBB INI R Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_A SYSTEM LBB INITIATION Y-PH set Reset RS_OP_LBB INI Y Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_A SYSTEM LBB INITIATION B-PH set Reset RS_OP_LBB INI B Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_A SYSTEM TIE LBB TO INIT BB set Reset RS_OP_T LBB OPTD Transmitted to IEC System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A Protection;CbfBbpRBRF1 ST;OpIn;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_A PROTECTION EXTERNAL BREAKER FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF1 ST;OpIn;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF2 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_A PROTECTION EXTERNAL BREAKER FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF2 ST;OpEx;general;ACT None 1 #REF!
A SPARE SPS 400kV R401_P743_PU_A PROTECTION BREAKER FAILURE RETRIP Operated Reset RS_OP_CB FAIL S3 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT None No 1 #REF!
A SPARE SPS 400kV R401_P743_PU_A PROTECTION BREAKER FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S4 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT None No 1 #REF!
R401_P743_PU_A SYSTEM B/B PU-B HEALTHY Healthy Unhealthy UN_HL_BB_PU B
A SPARE SPS None No 1 #REF!
DIGITAL INFORMATION TO IED IED name R401_P743_PU_A
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_A
ANALOG INFORMATION FROM IED IED name R401_P743_PU_A
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P743_PU_A
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P743_PU_A
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P743_PU_A
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P743_PU_A
ANALOG INFORMATION TO IED IED name R401_P743_PU_A
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R401_P743_PU_A
A SPARE 13 ANALOG INFORMATION TO IED IED name R401_P743_PU_A
COUNTER INFORMATION FROM IED IED name R401_P743_PU_A
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P743_PU_A
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P743_PU_A
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P743_PU_A
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P743_PU_A
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R401_P743_PU_B GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R401_P743_PU_B
DIGITAL INFORMATION FROM IED IED name R401_P743_PU_B
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R401_P743_PU_B PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R401_P743_PU_B
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R401_P743_PU_B PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R401_P743_PU_B
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_B GOOSE LBB START Set Reset RS_OP_LBB START Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R401_P743_PU_B
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_B SYSTEM LBB INITIATION 3-PH set Reset RS_OP_LBB INI 3P Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_B SYSTEM LBB INITIATION R-PH set Reset RS_OP_LBB INI R Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_B SYSTEM LBB INITIATION Y-PH set Reset RS_OP_LBB INI Y Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_B SYSTEM LBB INITIATION B-PH set Reset RS_OP_LBB INI B Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_B SYSTEM TIE LBB TO INIT BB set Reset RS_OP_T LBB OPTD Transmitted to IEC System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A Protection;CbfBbpRBRF1 ST;OpIn;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_B PROTECTION EXTERNAL BREAKER FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF1 ST;OpIn;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF2 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 400kV R401_P743_PU_B PROTECTION EXTERNAL BREAKER FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF2 ST;OpEx;general;ACT None 1 #REF!
SPS 400kV R401_P743_PU_B PROTECTION BREAKER FAILURE RETRIP Operated Reset RS_OP_CB FAIL S3 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT
SPS 400kV R401_P743_PU_B PROTECTION BREAKER FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S4 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT
SPS 400kV R401_P743_PU_B PROTECTION B/B PU-A HEALTHY Healthy Unhealthy UN_HL_BB_PU A
A SPARE None No 1 #REF!
DIGITAL INFORMATION TO IED IED name R401_P743_PU_B
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R401_P743_PU_B
ANALOG INFORMATION FROM IED IED name R401_P743_PU_B
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P743_PU_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P743_PU_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P743_PU_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R401_P743_PU_B
ANALOG INFORMATION TO IED IED name R401_P743_PU_B
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R401_P743_PU_B
A SPARE 13 ANALOG INFORMATION TO IED IED name R401_P743_PU_B
COUNTER INFORMATION FROM IED IED name R401_P743_PU_B
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P743_PU_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P743_PU_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P743_PU_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R401_P743_PU_B
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R402_P743_50BF GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R402_P743_50BF
DIGITAL INFORMATION FROM IED IED name R402_P743_50BF
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R402_P743_50BF PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R402_P743_50BF
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R402_P743_50BF PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R402_P743_50BF
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400kV R402_P743_50BF SYSTEM BCU Healthy Unhealthy UL_HL_BCU Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R402_P743_50BF
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R402_P743_50BF SYSTEM LBB INITIATION 3-PH Set Reset RS_OP_LBB INI 3P Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R402_P743_50BF
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R402_P743_50BF SYSTEM LBB INITIATION R-PH Set Reset RS_OP_LBB INI R Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R402_P743_50BF
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R402_P743_50BF SYSTEM LBB INITIATION B-PH Set Reset RS_OP_LBB INI B Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R402_P743_50BF
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R402_P743_50BF SYSTEM LBB INITIATION Y-PH Set Reset RS_OP_LBB INI Y Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R402_P743_50BF
A Protection;CbfBbpRBRF2 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 400kV R402_P743_50BF PROTECTION BREAKER FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT None 1 #REF!
A SPARE SPS 400kV R402_P743_50BF PROTECTION BREAKER FAILURE RETRIP TRIP Operated Reset RS_OP_CB FAIL S1 None No 1 #REF!
A SPARE SPS 400kV R402_P743_50BF PROTECTION BREAKER FAILURE RETRIP RPH Operated Reset RS_OP_CB FAILS1R None No 1 #REF!
SPS 400kV R402_P743_50BF PROTECTION BREAKER FAILURE RETRIP YPH Operated Reset RS_OP_CB FAILS1Y
A SPARE SPS 400kV R402_P743_50BF PROTECTION BREAKER FAILURE RETRIP BPH Operated Reset RS_OP_CB FAILS1B None No 1 #REF!
400kV R402_P743_50BF PROTECTION
DIGITAL INFORMATION TO IED 400kV R402_P743_50BF PROTECTION
Iss. Customer Ref IED DO Reference Electrical Data 400kV R402_P743_50BF PROTECTION Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) 400kV R402_P743_50BF PROTECTION Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 400kV R402_P743_50BF PROTECTION 2 DIGITAL INFORMATION TO IED IED name R402_P743_50BF
A SPARE SPC 400kV R402_P743_50BF PROTECTION 2 DIGITAL INFORMATION TO IED IED name R402_P743_50BF
A SPARE SPC 400kV R402_P743_50BF PROTECTION 2 DIGITAL INFORMATION TO IED IED name R402_P743_50BF
A SPARE SPC 400kV R402_P743_50BF PROTECTION 2 DIGITAL INFORMATION TO IED IED name R402_P743_50BF
A SPARE SPC 400kV R402_P743_50BF PROTECTION 2 DIGITAL INFORMATION TO IED IED name R402_P743_50BF
A SPARE SPC 400kV R402_P743_50BF PROTECTION 2 DIGITAL INFORMATION TO IED IED name R402_P743_50BF
A SPARE SPC 400kV R402_P743_50BF PROTECTION 2 DIGITAL INFORMATION TO IED IED name R402_P743_50BF
A SPARE SPC 400kV R402_P743_50BF PROTECTION 2 DIGITAL INFORMATION TO IED IED name R402_P743_50BF
A SPARE SPC 400kV R402_P743_50BF PROTECTION 2 DIGITAL INFORMATION TO IED IED name R402_P743_50BF
A SPARE SPC 400kV R402_P743_50BF PROTECTION 2 DIGITAL INFORMATION TO IED IED name R402_P743_50BF
400kV R402_P743_50BF PROTECTION
ANALOG INFORMATION FROM IED 400kV R402_P743_50BF PROTECTION
Iss. Customer Ref IED AI Reference Electrical Data 400kV R402_P743_50BF PROTECTION Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit 400kV R402_P743_50BF PROTECTION Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 400kV R402_P743_50BF PROTECTION Yes 6 ANALOG INFORMATION FROM IED IED name R402_P743_50BF
A SPARE 400kV R402_P743_50BF PROTECTION Yes 6 ANALOG INFORMATION FROM IED IED name R402_P743_50BF
A SPARE 400kV R402_P743_50BF PROTECTION Yes 6 ANALOG INFORMATION FROM IED IED name R402_P743_50BF
A SPARE 400kV R402_P743_50BF PROTECTION Yes 6 ANALOG INFORMATION FROM IED IED name R402_P743_50BF
400kV R402_P743_50BF PROTECTION
ANALOG INFORMATION TO IED 400kV R402_P743_50BF PROTECTION
Iss. Customer Ref IED AI Reference Electrical Data 400kV R402_P743_50BF PROTECTION Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit 400kV R402_P743_50BF PROTECTION Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 400kV R402_P743_50BF PROTECTION 13 ANALOG INFORMATION TO IED IED name R402_P743_50BF
A SPARE 400kV R402_P743_50BF PROTECTION 13 ANALOG INFORMATION TO IED IED name R402_P743_50BF
400kV R402_P743_50BF PROTECTION
COUNTER INFORMATION FROM IED 400kV R402_P743_50BF PROTECTION
Iss. Customer Ref IED Counter Reference Electrical Data 400kV R402_P743_50BF PROTECTION Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit 400kV R402_P743_50BF PROTECTION Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 400kV R402_P743_50BF PROTECTION Yes 39 COUNTER INFORMATION FROM IED IED name R402_P743_50BF
A SPARE 400kV R402_P743_50BF PROTECTION Yes 39 COUNTER INFORMATION FROM IED IED name R402_P743_50BF
A SPARE 400kV R402_P743_50BF PROTECTION Yes 39 COUNTER INFORMATION FROM IED IED name R402_P743_50BF
A SPARE 400kV R402_P743_50BF PROTECTION Yes 39 COUNTER INFORMATION FROM IED IED name R402_P743_50BF
END OF IED DATA 400kV R402_P743_50BF PROTECTION
400kV R402_P743_50BF PROTECTION
DI GROUPS 400kV R402_P743_50BF PROTECTION
Iss. Customer Ref Group DI Reference Electrical Data 400kV R402_P743_50BF PROTECTION Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) 400kV R402_P743_50BF PROTECTION Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
A 2 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
A 3 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
A 4 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
A 5 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
A 6 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
A 7 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
A 8 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
A 9 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
A 10 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
A 11 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
A 12 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
A 13 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
A 14 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
A 15 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
A 16 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 DI GROUPS
400kV R402_P743_50BF PROTECTION
SELF GENERATED DIGITAL INFORMATION 400kV R402_P743_50BF PROTECTION
Iss. Customer Ref Self DI Reference Electrical Data 400kV R402_P743_50BF PROTECTION Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) 400kV R402_P743_50BF PROTECTION Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS 400kV R402_P743_50BF PROTECTION None No 1 C264 SELF GENERATED DIGITAL INFORMATION
400kV R402_P743_50BF PROTECTION
SELF GENERATED DIGITAL OUTPUT INFORMATION 400kV R402_P743_50BF PROTECTION
Iss. Customer Ref Self DO Reference Electrical Data 400kV R402_P743_50BF PROTECTION Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) 400kV R402_P743_50BF PROTECTION Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC 400kV R402_P743_50BF PROTECTION NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC 400kV R402_P743_50BF PROTECTION NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC 400kV R402_P743_50BF PROTECTION NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC 400kV R402_P743_50BF PROTECTION NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC 400kV R402_P743_50BF PROTECTION NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC 400kV R402_P743_50BF PROTECTION NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC 400kV R402_P743_50BF PROTECTION NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC 400kV R402_P743_50BF PROTECTION NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC 400kV R402_P743_50BF PROTECTION NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC 400kV R402_P743_50BF PROTECTION NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
400kV R402_P743_50BF PROTECTION
SELF GENERATED ANALOG INFORMATION 400kV R402_P743_50BF PROTECTION
Iss. Customer Ref Self AI Reference Electrical Data 400kV R402_P743_50BF PROTECTION Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit 400kV R402_P743_50BF PROTECTION Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE 400kV R402_P743_50BF PROTECTION Yes 6 C264 SELF GENERATED ANALOG INFORMATION
400kV R402_P743_50BF PROTECTION
SELF GENERATED COUNTER INFORMATION 400kV R402_P743_50BF PROTECTION
Iss. Customer Ref Self Counter Reference Electrical Data 400kV R402_P743_50BF PROTECTION Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit 400kV R402_P743_50BF PROTECTION Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE 400kV R402_P743_50BF PROTECTION Yes 39 C264 SELF GENERATED COUNTER INFORMATION
400kV R402_P743_50BF PROTECTION
SELF GENERATED SETPOINT INFORMATION 400kV R402_P743_50BF PROTECTION
Iss. Customer Ref SetPoint Reference Electrical Data 400kV R402_P743_50BF PROTECTION Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit 400kV R402_P743_50BF PROTECTION Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE 400kV R402_P743_50BF PROTECTION Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
400kV R402_P743_50BF PROTECTION
END OF DATA 400kV R402_P743_50BF PROTECTION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R407_P643_87T GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R407_P643_87T
DIGITAL INFORMATION FROM IED IED name R407_P643_87T
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P643_87T PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R407_P643_87T
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P643_87T PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind6;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T PROTECTION OVEREXCITATION HV START Set Reset RS_OP_O/E HV S Transmitted to IEC Protection;VhzWg1PVPH1 ST;Str;general;ACD None Yes 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T SYSTEM 86A1 TRIP RELAY Operated Reset RS_OP_86A1 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T SYSTEM 86A2 TRIP RELAY Operated Reset RS_OP_86A2 Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Normal_Fail SPS 400kV R407_P643_87T SYSTEM DC SOURCE-2 Fail Normal NL_FL_DC S2 Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400kV R407_P643_87T SYSTEM 64 RELAY Healthy Unhealthy UL_HL_64 Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T SYSTEM BUCHHOLZ TRIP 1&2 Operated Reset RS_OP_BUCH12 Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P643_87T SYSTEM PRD 1 2 &3 Alarm Normal RS_OP_PRD123 Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T SYSTEM OSR1 Operated Reset RS_OP_OSR-1 Transmitted to IEC System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind13;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T SYSTEM OSR2 Operated Reset RS_OP_OSR-2 Transmitted to IEC System;OptGGIO1 ST;Ind13;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind14;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T SYSTEM OSR3 Operated Reset RS_OP_OSR-3 Transmitted to IEC System;OptGGIO1 ST;Ind14;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind15;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T SYSTEM OTI Operated Reset RS_OP_OTI Transmitted to IEC System;OptGGIO1 ST;Ind15;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind16;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T SYSTEM 86A2 SUPERVISION Healthy Unhealthy RS_OP_86A2 S Transmitted to IEC System;OptGGIO1 ST;Ind16;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind17;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T SYSTEM WTI HV Operated Reset RS_OP_WTI HV Transmitted to IEC System;OptGGIO1 ST;Ind17;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind18;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T SYSTEM WTI LV Operated Reset RS_OP_WTI LV Transmitted to IEC System;OptGGIO1 ST;Ind18;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind19;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T SYSTEM WTI IV Operated Reset RS_OP_WTI IV Transmitted to IEC System;OptGGIO1 ST;Ind19;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind20;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T SYSTEM LOW OIL LEVEL MAIN TANK Alarm Normal RS_OP_MOLG Transmitted to IEC System;OptGGIO1 ST;Ind20;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind21;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T SYSTEM LOW OIL LEVEL OLTC Alarm Normal RS_OP_MOLG O Transmitted to IEC System;OptGGIO1 ST;Ind21;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind24;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T SYSTEM 86A1 SUPERVISION Healthy Unhealthy RS_OP_86A1 S Transmitted to IEC System;OptGGIO1 ST;Ind24;stVal;SPS None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T PROTECTION DIFFERENTIAL R-PH TRIP Operated Reset RS_OP_DIFF R PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T PROTECTION DIFFERENTIAL Y-PH TRIP Operated Reset RS_OP_DIFF Y-PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T PROTECTION DIFFERENTIAL B-PH TRIP Operated Reset RS_OP_DIFF B-PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T PROTECTION DIFFERENTIAL TRIP Operated Reset RS_OP_DIFF Transmitted to IEC Protection;DifPDIF1 ST;Op;general;general;ACT None 1 #REF!
A Protection;EfmEl1PTOC1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T PROTECTION DIFFERENTIAL CURRENT ALARM Set Reset RS_ST_DIFF_CURNT None 1 #REF!
A Protection;EfmEl1PTOC1 ST;Str;general;ACD SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T PROTECTION DIFFERENTIAL PROTECTION START Set Reset RS_ST_DIFF_STRT None 1 #REF!
A Protection;OcpEI1PTOC1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T PROTECTION DIFFERENTIAL PROTECTION RPH START Set Reset RS_ST_DIFF_STR_R None 1 #REF!
A Protection;OcpEI1PTOC1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T PROTECTION DIFFERENTIAL PROTECTION YPH START Set Reset RS_ST_DIFF_STR_Y None 1 #REF!
A Protection;OcpEI1PTOC1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T PROTECTION DIFFERENTIAL PROTECTION BPH START Set Reset RS_ST_DIFF_STR_B None 1 #REF!
A Protection;OcpEI1PTOC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P643_87T PROTECTION DIFFERENTIAL BLOCKED Set Reset RS_ST_DIFF_BLK None 1 #REF!
SPS 400kV R407_P643_87T PROTECTION DIFFERENTIAL PROTECTION TRIP-HS1 Operated Reset RS_OP_DIFF_HS-1
SPS 400kV R407_P643_87T PROTECTION DIFFERENTIAL PROTECTION TRIP-HS2 Operated Reset RS_OP_DIFF_HS-2
SPS 400kV R407_P643_87T PROTECTION DIFFERENTIAL PROTECTION 2nd HARMONIC BLOCK Set Reset RS_ST_DIFF_HBK 2
SPS 400kV R407_P643_87T PROTECTION DIFFERENTIAL PROTECTION 5th HARMONIC BLOCK Set Reset RS_ST_DIFF_HBK 5
A Protection;VhzWg1PVPH1 ST;Op;general;ACT SPE_HLA_Normal_Alarm SPS 400kV R407_P643_87T PROTECTION OVEREXCITATION HV ALARM Set Reset NL_AL_O/E HV Transmitted to IEC Protection;VhzWg1PVPH1 ST;Op;general;ACT None 1 #REF!
A Protection;VhzWg1PVPH2 ST;Op;general;ACT SPE_HLA_Reset_Trip SPS 400kV R407_P643_87T PROTECTION OVEREXCITATION HV TRIP Operated Reset RS_TR_O/E HV Transmitted to IEC Protection;VhzWg1PVPH2 ST;Op;general;ACT None 1 #REF!
R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
DIGITAL INFORMATION TO IED IED name R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref IED DO Reference Electrical Data R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R407_P643_87T
A SPARE SPC R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R407_P643_87T
A SPARE SPC R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R407_P643_87T
A SPARE SPC R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R407_P643_87T
A SPARE SPC R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R407_P643_87T
A SPARE SPC R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R407_P643_87T
A SPARE SPC R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R407_P643_87T
A SPARE SPC R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R407_P643_87T
A SPARE SPC R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R407_P643_87T
A SPARE SPC R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 2 DIGITAL INFORMATION TO IED IED name R407_P643_87T
R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
ANALOG INFORMATION FROM IED IED name R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref IED AI Reference Electrical Data R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 ANALOG INFORMATION FROM IED IED name R407_P643_87T
A SPARE R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 ANALOG INFORMATION FROM IED IED name R407_P643_87T
A SPARE R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 ANALOG INFORMATION FROM IED IED name R407_P643_87T
A SPARE R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 ANALOG INFORMATION FROM IED IED name R407_P643_87T
R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
ANALOG INFORMATION TO IED IED name R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref IED AI Reference Electrical Data R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) R407_P643_87T SYSTEM OLTC ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 13 ANALOG INFORMATION TO IED IED name R407_P643_87T
A SPARE R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS 13 ANALOG INFORMATION TO IED IED name R407_P643_87T
R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
COUNTER INFORMATION FROM IED IED name R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref IED Counter Reference Electrical Data R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 COUNTER INFORMATION FROM IED IED name R407_P643_87T
A SPARE R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 COUNTER INFORMATION FROM IED IED name R407_P643_87T
A SPARE R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 COUNTER INFORMATION FROM IED IED name R407_P643_87T
A SPARE R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 COUNTER INFORMATION FROM IED IED name R407_P643_87T
END OF IED DATA R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
DI GROUPS R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref Group DI Reference Electrical Data R407_P643_87T SYSTEM OLTC ALARM Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 DI GROUPS
R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
SELF GENERATED DIGITAL INFORMATION R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref Self DI Reference Electrical Data R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) R407_P643_87T SYSTEM OLTC ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
SELF GENERATED DIGITAL OUTPUT INFORMATION R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref Self DO Reference Electrical Data R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
SELF GENERATED ANALOG INFORMATION R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref Self AI Reference Electrical Data R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
SELF GENERATED COUNTER INFORMATION R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref Self Counter Reference Electrical Data R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
SELF GENERATED SETPOINT INFORMATION R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
Iss. Customer Ref SetPoint Reference Electrical Data R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset Description Scada Interface System;OptGGIO1 ST;Ind10;stVal;SPS Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type System;OptGGIO1 ST;Ind10;stVal;SPS LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE R407_P643_87T SYSTEM WDG TEMP - HV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE R407_P643_87T SYSTEM WDG TEMP - IV & LV TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE R407_P643_87T SYSTEM PRV-2 TRIP Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE R407_P643_87T SYSTEM OIL TEMP ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
R407_P643_87T SYSTEM OLTC ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
END OF DATA R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Trip Reset System;OptGGIO1 ST;Ind10;stVal;SPS
R407_P643_87T SYSTEM BUCHHOLZ-1 TRIP Operated Reset RS_TR_BUCH-1 System;OptGGIO1 ST;Ind11;stVal;SPS
R407_P643_87T SYSTEM WTI-HV TRIP Operated Reset RS_TR_WTI-HV System;OptGGIO1 ST;Ind12;stVal;SPS
R407_P643_87T SYSTEM WTI - IV & LV TRIP Operated Reset RS_TR_WTI-LVIV System;OptGGIO1 ST;Ind13;stVal;SPS
R407_P643_87T SYSTEM PRD-2 TRIP Operated Reset RS_TR_PRV2 System;OptGGIO1 ST;Ind14;stVal;SPS
R407_P643_87T SYSTEM OTI ALARM Alarm Normal NL_AL_OTI System;OptGGIO1 ST;Ind15;stVal;SPS
R407_P643_87T SYSTEM PRV OLTC ALARM Set Reset NL_AL_OLTC System;OptGGIO1 ST;Ind17;stVal;SPS
R407_P643_87T SYSTEM OIL LEVEL LOW ALARM Set Reset NL_AL_OLL System;OptGGIO1 ST;Ind18;stVal;SPS
R407_P643_87T SYSTEM BUCHHOLZ-2 ALARM Set Reset RS_ST_BUCH ALM System;OptGGIO1 ST;IndXX;stVal;SPS
R407_P643_87T SYSTEM OSR-1 TRIP Operated Reset RS_OP_OSR-1 TR System;OptGGIO1 ST;IndXX;stVal;SPS
R407_P643_87T SYSTEM FIRE PROTECTION Operated Reset RS_OP_FIRE PRTN System;OptGGIO1 ST;IndXX;stVal;SPS
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R407_P643_64 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R407_P643_64
DIGITAL INFORMATION FROM IED IED name R407_P643_64
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P643_64 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R407_P643_64
A System;GosGGIO2 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_64 PROTECTION OVEREXCITATION IV START Set Reset RS_OP_O/E IV S Transmitted to IEC Protection;VhzWg1PVPH1 ST;Str;general;ACD None Yes 1 #REF!
A System;GosGGIO2 ST;Ind8;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P643_64 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind8;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400kV R407_P643_64 SYSTEM 87T RELAY Healthy Unhealthy UL_HL_87T Transmitted to IEC System;OptGGIO1 ST;Ind2;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind3;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_64 SYSTEM 86B1 TRIP RELAY Operated Reset RS_OP_86B1 Transmitted to IEC System;OptGGIO1 ST;Ind3;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_64 SYSTEM 86B2 TRIP RELAY Operated Reset RS_OP_86B2 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P643_64 SYSTEM WTI HV Alarm Normal NL_AL_WTI HV Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P643_64 SYSTEM WTI LV Alarm Normal NL_AL_WTI LV Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P643_64 SYSTEM WTI IV Alarm Normal NL_AL_WTI IV Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P643_64 SYSTEM BUCHHOLZ 1&2 Alarm Normal NL_AL_BUCH12 Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind10;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P643_64 SYSTEM OTI Alarm Normal NL_AL_OTI Transmitted to IEC System;OptGGIO1 ST;Ind10;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind11;stVal;SPS SPE_HLA_Normal_Fail SPS 400kV R407_P643_64 SYSTEM DC SOURCE-1 Fail Normal NL_FL_DC S1 Transmitted to IEC System;OptGGIO1 ST;Ind11;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind15;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_64 SYSTEM 86A1 SUPERVISION Healthy Unhealthy RS_OP_86B1 S Transmitted to IEC System;OptGGIO1 ST;Ind15;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind16;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P643_64 SYSTEM 86A2 SUPERVISION Healthy Unhealthy RS_OP_86B2 S Transmitted to IEC System;OptGGIO1 ST;Ind16;stVal;SPS None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P643_64 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;HzrHvwPTOC1 ST;Op;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P643_64 PROTECTION REF R PH TRIP Operated Reset RS_OP_REF Transmitted to IEC Protection;HzrHvwPTOC1 ST;Op;general;ACT None 1 #REF!
SPS 400kV R407_P643_64 PROTECTION REF Y PH TRIP Operated Reset RS_OP_REF Transmitted to IEC Protection;HzrLvwPTOC1 ST;Op;general;ACT
SPS 400kV R407_P643_64 PROTECTION REF B PH TRIP Operated Reset RS_OP_REF Transmitted to IEC Protection;HzrTvwPTOC1 ST;Op;general;ACT
A Protection;OcpEI1PTOC1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P643_65 PROTECTION REF ALARM Set Reset RS_ST_REF ALM None 1 #REF!
A Protection;OcpEI1PTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 400kV R407_P643_64 PROTECTION OVEREXCITATION IV START Set Reset RS_ST_O/E IV ST None 1 #REF!
A Protection;VhzWg1PVPH1 ST;Op;general;ACT SPE_HLA_Normal_Alarm SPS 400kV R407_P643_64 PROTECTION OVEREXCITATION IV ALARM Set Reset NL_AL_O/E IV Transmitted to IEC Protection;VhzWg1PVPH1 ST;Op;general;ACT None 1 #REF!
A Protection;VhzWg1PVPH2 ST;Op;general;ACT SPE_HLA_Reset_Trip SPS 400kV R407_P643_64 PROTECTION OVEREXCITATION IV TRIP Operated Reset RS_TR_O/E IV T Transmitted to IEC Protection;VhzWg1PVPH2 ST;Op;general;ACT None 1 #REF!
SPS 400kV R407_P643_64 SYSTEM OIL TEMP TRIP
DIGITAL INFORMATION TO IED SPS 400kV R407_P643_64 SYSTEM BUCHHOLZ-2 TRIP
Iss. Customer Ref IED DO Reference Electrical Data SPS 400kV R407_P643_64 SYSTEM BUCHHOLZ ALARM Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 400kV R407_P643_64 SYSTEM WDG TEMP - HV ALARM Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 400kV R407_P643_64 SYSTEM WDG TEMP - IV & LV ALARM 2 DIGITAL INFORMATION TO IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM OIL FLOW FAIL ALARM 2 DIGITAL INFORMATION TO IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM 2 DIGITAL INFORMATION TO IED IED name R407_P643_64
SPS 400kV R407_P643_64 SYSTEM
ANALOG INFORMATION FROM IED SPS 400kV R407_P643_64 SYSTEM
Iss. Customer Ref IED AI Reference Electrical Data SPS 400kV R407_P643_64 SYSTEM Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 400kV R407_P643_64 SYSTEM Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 ANALOG INFORMATION FROM IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 ANALOG INFORMATION FROM IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 ANALOG INFORMATION FROM IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 ANALOG INFORMATION FROM IED IED name R407_P643_64
SPS 400kV R407_P643_64 SYSTEM
ANALOG INFORMATION TO IED SPS 400kV R407_P643_64 SYSTEM
Iss. Customer Ref IED AI Reference Electrical Data SPS 400kV R407_P643_64 SYSTEM Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 400kV R407_P643_64 SYSTEM Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 400kV R407_P643_64 SYSTEM 13 ANALOG INFORMATION TO IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM 13 ANALOG INFORMATION TO IED IED name R407_P643_64
SPS 400kV R407_P643_64 SYSTEM
COUNTER INFORMATION FROM IED SPS 400kV R407_P643_64 SYSTEM
Iss. Customer Ref IED Counter Reference Electrical Data SPS 400kV R407_P643_64 SYSTEM Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 400kV R407_P643_64 SYSTEM Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 COUNTER INFORMATION FROM IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 COUNTER INFORMATION FROM IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 COUNTER INFORMATION FROM IED IED name R407_P643_64
A SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 COUNTER INFORMATION FROM IED IED name R407_P643_64
END OF IED DATA SPS 400kV R407_P643_64 SYSTEM
SPS 400kV R407_P643_64 SYSTEM
DI GROUPS SPS 400kV R407_P643_64 SYSTEM
Iss. Customer Ref Group DI Reference Electrical Data SPS 400kV R407_P643_64 SYSTEM Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function SPS 400kV R407_P643_64 SYSTEM Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 2 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 3 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 4 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 5 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 6 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 7 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 8 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 9 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 10 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 11 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 12 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 13 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 14 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 15 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
A 16 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 DI GROUPS
SPS 400kV R407_P643_64 SYSTEM
SELF GENERATED DIGITAL INFORMATION SPS 400kV R407_P643_64 SYSTEM
Iss. Customer Ref Self DI Reference Electrical Data SPS 400kV R407_P643_64 SYSTEM Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 400kV R407_P643_64 SYSTEM Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS 400kV R407_P643_64 SYSTEM None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SPS 400kV R407_P643_64 SYSTEM
SELF GENERATED DIGITAL OUTPUT INFORMATION SPS 400kV R407_P643_64 SYSTEM
Iss. Customer Ref Self DO Reference Electrical Data SPS 400kV R407_P643_64 SYSTEM Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 400kV R407_P643_64 SYSTEM Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV R407_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPS 400kV R407_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPS 400kV R407_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPS 400kV R407_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPS 400kV R407_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPS 400kV R407_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPS 400kV R407_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPS 400kV R407_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPS 400kV R407_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPS 400kV R407_P643_64 SYSTEM NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SPS 400kV R407_P643_64 SYSTEM
SELF GENERATED ANALOG INFORMATION SPS 400kV R407_P643_64 SYSTEM
Iss. Customer Ref Self AI Reference Electrical Data SPS 400kV R407_P643_64 SYSTEM Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 400kV R407_P643_64 SYSTEM Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SPS 400kV R407_P643_64 SYSTEM
SELF GENERATED COUNTER INFORMATION SPS 400kV R407_P643_64 SYSTEM
Iss. Customer Ref Self Counter Reference Electrical Data SPS 400kV R407_P643_64 SYSTEM Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 400kV R407_P643_64 SYSTEM Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SPS 400kV R407_P643_64 SYSTEM
SELF GENERATED SETPOINT INFORMATION SPS 400kV R407_P643_64 SYSTEM
Iss. Customer Ref SetPoint Reference Electrical Data SPS 400kV R407_P643_64 SYSTEM Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 400kV R407_P643_64 SYSTEM Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE SPS 400kV R407_P643_64 SYSTEM Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
SPS 400kV R407_P643_64 SYSTEM
END OF DATA SPS 400kV R407_P643_64 SYSTEM
SPS 400kV R407_P643_64 SYSTEM PRD-1 TRIP Operated Reset RS_TR_PRD-1 System;OptGGIO1 ST;Ind5;stVal;SPS
SPS 400kV R407_P643_64 SYSTEM OTI TRIP Operated Reset RS_TR_OTI System;OptGGIO1 ST;Ind6;stVal;SPS
SPS 400kV R407_P643_64 SYSTEM BUCHHOLZ-2 TRIP Operated Reset RS_TR_BUCH-2 System;OptGGIO1 ST;Ind7;stVal;SPS
SPS 400kV R407_P643_64 SYSTEM BUCHHOLZ-1 ALARM Set Reset NL_AL_BUCH System;OptGGIO1 ST;Ind8;stVal;SPS
SPS 400kV R407_P643_64 SYSTEM WTI - HV ALARM Set Reset NL_AL_WTI-HV System;OptGGIO1 ST;Ind9;stVal;SPS
SPS 400kV R407_P643_64 SYSTEM WTI - IV & LV ALARM Set Reset NL_AL_WTI IVLV System;OptGGIO1 ST;Ind10;stVal;SPS
SPS 400kV R407_P643_64 SYSTEM OSR-2 TRIP Operated Reset RS_OP_OSR-2 TRP System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 400kV R407_P643_64 SYSTEM PRD-3 TRIP Operated Reset RS_OP_PRD-3 TRP System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 400kV R407_P643_64 SYSTEM
SPS 400kV R407_P643_64 SYSTEM
SPS 400kV R407_P643_64 SYSTEM
SPS 400kV R407_P643_64 SYSTEM
SPS 400kV R407_P643_64 SYSTEM
SPS 400kV R407_P643_64 SYSTEM
SPS 400kV R407_P643_64 SYSTEM
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R412_P442_21R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R412_P442_21R
DIGITAL INFORMATION FROM IED IED name R412_P442_21R
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P442_21R PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R412_P442_21R
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P442_21R PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R412_P442_21R
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P442_21R PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;CbfRBRF1 ST;OpEx;general;ACT SPE_HLA_Normal_Fail SPS 400kV R407_P442_21R PROTECTION VT FUSE FAIL Alarm Normal NL_FL_VT FUSE Transmitted to IEC System;AlmGGIO1 ST;Alm6;stVal;SPS None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P442_21R PROTECTION BACKUP IMPEDENCE R-PH TRIP Operated Reset RS_OP_B/U IMP R Transmitted to IEC Protection;DisPDIS1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P442_21R PROTECTION BACKUP IMPEDENCE Y-PH TRIP Operated Reset RS_OP_B/U IMP Y Transmitted to IEC Protection;DisPDIS1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P442_21R PROTECTION BACKUP IMPEDENCE B-PH TRIP Operated Reset RS_OP_B/U IMP B Transmitted to IEC Protection;DisPDIS1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P442_21R PROTECTION BACKUP IMPEDENCE Operated Reset RS_OP_B/U IMP Transmitted to IEC Protection;DisPDIS1 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Str;general;general;ACD SPE_HLA_Reset_Start SPS 400kV R407_P442_21R PROTECTION REACTOR BACKUP IMPEDANE PICKUP set Reset RS_ST_Z1 START Transmitted to IEC Protection;DisPDIS1 ST;Str;general;general;ACD None 1 #REF!
A SPARE SPS 400kV R407_P442_21R PROTECTION BACKUP ZONE-1 TRIP Operated Reset RS_OP_Z1_TRP None No 1 #REF!
SPS R407_P442_21R
DIGITAL INFORMATION TO IED SPS IED name R407_P442_21R
Iss. Customer Ref IED DO Reference Electrical Data SPS R407_P442_21R Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS Voltage Level Short Name (16 char) R407_P442_21R Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS R407_P442_21R 2 DIGITAL INFORMATION TO IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R 2 DIGITAL INFORMATION TO IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R 2 DIGITAL INFORMATION TO IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R 2 DIGITAL INFORMATION TO IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R R 2 DIGITAL INFORMATION TO IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R 2 DIGITAL INFORMATION TO IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R 2 DIGITAL INFORMATION TO IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R 2 DIGITAL INFORMATION TO IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R 2 DIGITAL INFORMATION TO IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R 2 DIGITAL INFORMATION TO IED IED name R407_P442_21R
SPS R407_P442_21R
ANALOG INFORMATION FROM IED SPS IED name R407_P442_21R
Iss. Customer Ref IED AI Reference Electrical Data SPS R407_P442_21R Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS Voltage Level Short Name (16 char) R407_P442_21R Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS R407_P442_21R Yes 6 ANALOG INFORMATION FROM IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R Yes 6 ANALOG INFORMATION FROM IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R Yes 6 ANALOG INFORMATION FROM IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R Yes 6 ANALOG INFORMATION FROM IED IED name R407_P442_21R
SPS R407_P442_21R
ANALOG INFORMATION TO IED SPS IED name R407_P442_21R
Iss. Customer Ref IED AI Reference Electrical Data SPS R407_P442_21R Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS Voltage Level Short Name (16 char) R407_P442_21R Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS R407_P442_21R 13 ANALOG INFORMATION TO IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R 13 ANALOG INFORMATION TO IED IED name R407_P442_21R
SPS R407_P442_21R
COUNTER INFORMATION FROM IED SPS IED name R407_P442_21R
Iss. Customer Ref IED Counter Reference Electrical Data SPS R407_P442_21R Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS Voltage Level Short Name (16 char) R407_P442_21R Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS R407_P442_21R Yes 39 COUNTER INFORMATION FROM IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R Yes 39 COUNTER INFORMATION FROM IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R Yes 39 COUNTER INFORMATION FROM IED IED name R407_P442_21R
A SPARE SPS R407_P442_21R Yes 39 COUNTER INFORMATION FROM IED IED name R407_P442_21R
END OF IED DATA SPS R407_P442_21R
SPS R407_P442_21R
DI GROUPS SPS R407_P442_21R
Iss. Customer Ref Group DI Reference Electrical Data SPS R407_P442_21R Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function SPS Voltage Level Short Name (16 char) R407_P442_21R Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
A 2 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
A 3 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
A 4 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
A 5 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
A 6 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
A 7 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
A 8 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
A 9 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
A 10 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
A 11 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
A 12 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
A 13 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
A 14 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
A 15 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
A 16 SPARE SPS R407_P442_21R None No 1 C264 DI GROUPS
SPS R407_P442_21R
SELF GENERATED DIGITAL INFORMATION SPS R407_P442_21R
Iss. Customer Ref Self DI Reference Electrical Data SPS R407_P442_21R Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS Voltage Level Short Name (16 char) R407_P442_21R Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS R407_P442_21R None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SPS R407_P442_21R
SELF GENERATED DIGITAL OUTPUT INFORMATION SPS R407_P442_21R
Iss. Customer Ref Self DO Reference Electrical Data SPS R407_P442_21R Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS Voltage Level Short Name (16 char) R407_P442_21R Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS R407_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPS R407_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPS R407_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPS R407_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPS R407_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPS R407_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPS R407_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPS R407_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPS R407_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPS R407_P442_21R NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SPS R407_P442_21R
SELF GENERATED ANALOG INFORMATION SPS R407_P442_21R
Iss. Customer Ref Self AI Reference Electrical Data SPS R407_P442_21R Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS Voltage Level Short Name (16 char) R407_P442_21R Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE SPS R407_P442_21R Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SPS R407_P442_21R
SELF GENERATED COUNTER INFORMATION SPS R407_P442_21R
Iss. Customer Ref Self Counter Reference Electrical Data SPS R407_P442_21R Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS Voltage Level Short Name (16 char) R407_P442_21R Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE SPS R407_P442_21R Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SPS R407_P442_21R
SELF GENERATED SETPOINT INFORMATION SPS R407_P442_21R
Iss. Customer Ref SetPoint Reference Electrical Data SPS R407_P442_21R Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS Voltage Level Short Name (16 char) R407_P442_21R Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE SPS R407_P442_21R Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
SPS R407_P442_21R
END OF DATA SPS R407_P442_21R
SPS 400kV R407_P442_21R PROTECTION BACKUP OVERCURRENT START set Reset RS_ST_B/U O/C ST
SPS 400kV R407_P442_21R PROTECTION BACKUP OVERCURRENT TRIP Operated Reset RS_ST_B/C O/C TR
SPS 400kV R407_P442_21R PROTECTION BACKUP EARTHFAULT START set Reset RS_ST_B/U E/F_ST
SPS 400kV R407_P442_21R PROTECTION BACKUP EARTHFAULT TRIP Operated Reset RS_ST_B/C E/F TR
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R407_P743_PU_A GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R407_P743_PU_A
DIGITAL INFORMATION FROM IED IED name R407_P743_PU_A
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P743_PU_A PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R407_P743_PU_A
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P743_PU_A PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R407_P743_PU_A
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P743_PU_A GOOSE LBB START Set Reset RS_OP_LBB START Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R407_P743_PU_A
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P743_PU_A SYSTEM LBB INITIATION 3-PH set Reset RS_OP_LBB INI 3P Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P743_PU_A SYSTEM TIE LBB TO INIT BB set Reset RS_OP_T LBB OPTD Transmitted to IEC System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A Protection;CbfBbpRBRF1 ST;OpIn;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P743_PU_A PROTECTION EXTERNAL CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF1 ST;OpIn;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF2 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P743_PU_A PROTECTION EXTERNAL CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF2 ST;OpEx;general;ACT None 1 #REF!
SPS 400kV R407_P743_PU_A PROTECTION CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S3 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT
SPS 400kV R407_P743_PU_A PROTECTION CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S4 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT
A SPARE SPS 400kV R407_P743_PU_A SYSTEM B/B PU-B HEALTHY Healthy Unhealthy UH_HL_PUB System;GosGGIO1 ST;IndXX;stVal;SPS None No 1 #REF!
DIGITAL INFORMATION TO IED IED name R407_P743_PU_A
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_A
ANALOG INFORMATION FROM IED IED name R407_P743_PU_A
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R407_P743_PU_A
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R407_P743_PU_A
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R407_P743_PU_A
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R407_P743_PU_A
ANALOG INFORMATION TO IED IED name R407_P743_PU_A
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R407_P743_PU_A
A SPARE 13 ANALOG INFORMATION TO IED IED name R407_P743_PU_A
COUNTER INFORMATION FROM IED IED name R407_P743_PU_A
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R407_P743_PU_A
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R407_P743_PU_A
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R407_P743_PU_A
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R407_P743_PU_A
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R407_P743_PU_B GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R407_P743_PU_B
DIGITAL INFORMATION FROM IED IED name R407_P743_PU_B
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P743_PU_B PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R407_P743_PU_B
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R407_P743_PU_B PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R407_P743_PU_B
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P743_PU_B GOOSE LBB START Set Reset RS_OP_LBB START Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R407_P743_PU_B
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P743_PU_B SYSTEM LBB INITIATION 3-PH Set Reset RS_OP_LBB INI 3P Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind12;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R407_P743_PU_B SYSTEM TIE LBB TO INIT BB set Reset RS_OP_T LBB OPTD Transmitted to IEC System;OptGGIO1 ST;Ind12;stVal;SPS None 1 #REF!
A Protection;CbfBbpRBRF1 ST;OpIn;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P743_PU_B PROTECTION EXTERNAL CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF1 ST;OpIn;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF2 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 400kV R407_P743_PU_B PROTECTION EXTERNAL CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF2 ST;OpEx;general;ACT None 1 #REF!
SPS 400kV R407_P743_PU_B PROTECTION CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S3 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT
SPS 400kV R407_P743_PU_B PROTECTION CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S4 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT
SPS 400kV R407_P743_PU_B SYSTEM B/B PU-B HEALTHY Healthy Unhealthy UH_HL_PUA System;GosGGIO1 ST;IndXX;stVal;SPS
DIGITAL INFORMATION TO IED IED name R407_P743_PU_B
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R407_P743_PU_B
ANALOG INFORMATION FROM IED IED name R407_P743_PU_B
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R407_P743_PU_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R407_P743_PU_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R407_P743_PU_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R407_P743_PU_B
ANALOG INFORMATION TO IED IED name R407_P743_PU_B
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R407_P743_PU_B
A SPARE 13 ANALOG INFORMATION TO IED IED name R407_P743_PU_B
COUNTER INFORMATION FROM IED IED name R407_P743_PU_B
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R407_P743_PU_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R407_P743_PU_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R407_P743_PU_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R407_P743_PU_B
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R412_P643_87R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R412_P643_87R
DIGITAL INFORMATION FROM IED IED name R412_P643_87R
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R412_P643_87R PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R412_P643_87R
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R412_P643_87R PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R412_P643_87R SYSTEM 86A TRIP RELAY Operated Reset RS_OP_86A Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R412_P643_87R SYSTEM B/U IMPEDENCE Operated Reset RS_OP_B/U IMP Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind9;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400kV R412_P643_87R SYSTEM REF (64R) RELAY Healthy Unhealthy UH_HL_64R(REF) Transmitted to IEC System;OptGGIO1 ST;Ind9;stVal;SPS None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P643_87R PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P643_87R PROTECTION DIFFERENTIAL R-PH TRIP Operated Reset RS_OP_DIFF R PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P643_87R PROTECTION DIFFERENTIAL Y-PH TRIP Operated Reset RS_OP_DIFF Y-PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P643_87R PROTECTION DIFFERENTIAL B-PH TRIP Operated Reset RS_OP_DIFF B-PH Transmitted to IEC Protection;DifPDIF1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DifPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P643_87R PROTECTION DIFFERENTIAL TRIP Operated Reset RS_OP_DIFF Transmitted to IEC Protection;DifPDIF1 ST;Op;general;general;ACT None 1 #REF!
A SPARE SPS 400kV R412_P643_87R SYSTEM 86A SUPERVISION HEALTHY UNHEALTHY UL_HL_86A SUP System;OptGGIO1 ST;Ind10;stVal;SPS None No 1 #REF!
SPS 400kV R412_P643_87R PROTECTION DIFFERENTIAL CURRENT ALARM Set Reset RS_ST_DIFF_CURNT
SPS 400kV R412_P643_87R PROTECTION DIFFERENTIAL PROTECTION START Set Reset RS_ST_DIFF_STRT
SPS 400kV R412_P643_87R PROTECTION DIFFERENTIAL PROTECTION RPH START Set Reset RS_ST_DIFF_STR_R
SPS 400kV R412_P643_87R PROTECTION DIFFERENTIAL PROTECTION YPH START Set Reset RS_ST_DIFF_STR_Y
SPS 400kV R412_P643_87R PROTECTION DIFFERENTIAL PROTECTION BPH START Set Reset RS_ST_DIFF_STR_B
SPS 400kV R412_P643_87R PROTECTION DIFFERENTIAL BLOCKED Set Reset RS_ST_DIFF_BLK
A System;OptGGIO1 ST;Ind4;stVal;SPS SPE_HLA_Reset_Trip SPS 400kV R412_P643_87R SYSTEM REACTOR BUCHHOLZ Operated Reset RS_TR_BUCHHOLZ1 Transmitted to IEC System;OptGGIO1 ST;Ind4;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Reset_Trip SPS 400kV R412_P643_87R SYSTEM REACTOR WTI TRIP Operated Reset RS_TR_WTI Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Reset_Trip SPS 400kV R412_P643_87R SYSTEM REACTOR PNRV Trip Reset RS_TR_PNRV Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
SPS 400kV R412_P643_87R SYSTEM REACTOR PRD Operated Reset RS_OP_PRD-2 System;OptGGIO1 ST;Ind11;stVal;SPS
SPS 400kV R412_P643_87R SYSTEM REACTOR OTI ALARM Set Reset RS_ST_OTI ALM
SPS 400kV R412_P643_87R SYSTEM REACTOR OSR TRIP Operated Reset RS_OP_OSR_TR
SPS 400kV R412_P643_87R SYSTEM REACTOR OIL LOW LEVEL ALARM Set Reset RS_ST_OIL LO_ AL
A SPARE SPS 400kV R412_P643_87R SYSTEM FIRE PROTECTION Operated Reset RS_OP_FIRE_PTR None No 1 #REF!
DIGITAL INFORMATION TO IED SPS 400kV R412_P643_87R
Iss. Customer Ref IED DO Reference Electrical Data SPS 400kV Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 2 DIGITAL INFORMATION TO IED IED name R412_P643_87R
ANALOG INFORMATION FROM IED SPS 400kV R412_P643_87R
Iss. Customer Ref IED AI Reference Electrical Data SPS 400kV Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 400kV Yes 6 ANALOG INFORMATION FROM IED IED name R412_P643_87R
A SPARE SPS 400kV Yes 6 ANALOG INFORMATION FROM IED IED name R412_P643_87R
A SPARE SPS 400kV Yes 6 ANALOG INFORMATION FROM IED IED name R412_P643_87R
A SPARE SPS 400kV Yes 6 ANALOG INFORMATION FROM IED IED name R412_P643_87R
ANALOG INFORMATION TO IED SPS 400kV R412_P643_87R
Iss. Customer Ref IED AI Reference Electrical Data SPS 400kV Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 400kV 13 ANALOG INFORMATION TO IED IED name R412_P643_87R
A SPARE SPS 400kV 13 ANALOG INFORMATION TO IED IED name R412_P643_87R
COUNTER INFORMATION FROM IED SPS 400kV R412_P643_87R
Iss. Customer Ref IED Counter Reference Electrical Data SPS 400kV Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 400kV Yes 39 COUNTER INFORMATION FROM IED IED name R412_P643_87R
A SPARE SPS 400kV Yes 39 COUNTER INFORMATION FROM IED IED name R412_P643_87R
A SPARE SPS 400kV Yes 39 COUNTER INFORMATION FROM IED IED name R412_P643_87R
A SPARE SPS 400kV Yes 39 COUNTER INFORMATION FROM IED IED name R412_P643_87R
END OF IED DATA SPS 400kV
DI GROUPS SPS 400kV
Iss. Customer Ref Group DI Reference Electrical Data SPS 400kV Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 2 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 3 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 4 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 5 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 6 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 7 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 8 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 9 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 10 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 11 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 12 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 13 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 14 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 15 SPARE SPS 400kV None No 1 C264 DI GROUPS
A 16 SPARE SPS 400kV None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION SPS 400kV
Iss. Customer Ref Self DI Reference Electrical Data SPS 400kV Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS 400kV None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION SPS 400kV
Iss. Customer Ref Self DO Reference Electrical Data SPS 400kV Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPS 400kV NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION SPS 400kV
Iss. Customer Ref Self AI Reference Electrical Data SPS 400kV Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE SPS 400kV Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION SPS 400kV
Iss. Customer Ref Self Counter Reference Electrical Data SPS 400kV Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE SPS 400kV Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION SPS 400kV
Iss. Customer Ref SetPoint Reference Electrical Data SPS 400kV Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS 400kV Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE SPS 400kV Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
END OF DATA SPS 400kV
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R412_P141_64R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R412_P141_64R
DIGITAL INFORMATION FROM IED IED name R412_P141_64R
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R412_P141_64R PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R412_P141_64R
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R412_P141_64R PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A System;OptGGIO1 ST;Ind5;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400kV R412_P141_64R SYSTEM B/U IMPEDENCE PROT RELAY Healthy Unhealthy UH_HL_B/U IMP Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind6;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400kV R412_P141_64R SYSTEM 87R (REACTOR DIFFERENTIAL) RELAY Healthy Unhealthy UH_HL_87R(R DIF) Transmitted to IEC System;OptGGIO1 ST;Ind6;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind8;stVal;SPS SPE_HLA_Unhlthy_Hlthy SPS 400kV R412_P141_64R SYSTEM 86B TRIP RELAY SUPERVISION Healthy Unhealthy UH_HL_86B Transmitted to IEC System;OptGGIO1 ST;Ind8;stVal;SPS None 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P141_64R PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
SPS 400kV R412_P141_64R PROTECTION REF TRIP Operated Reset RS_OP_REF Transmitted to IEC Protection;SenRefPDIF1 ST;Op;general;general;ACT
SPS 400kV R412_P141_64R PROTECTION REF ALARM Set Reset RS_ST_REF ALM
SPS 400kV R412_P141_64R PROTECTION REF R PH TRIP Operated Reset RS_OP_REF_R
A Protection;SenRefPDIF1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P141_64R PROTECTION REF Y PH TRIP Operated Reset RS_OP_REF_Y None 1 #REF!
A SPARE SPS 400kV R412_P141_64R PROTECTION REF B PH TRIP Operated Reset RS_OP_REF_B None No 1 #REF!
A System;OptGGIO1 ST;Ind1;stVal;SPS SPE_HLA_Reset_Trip SPS 400kV R412_P141_64R SYSTEM REACTOR WTI ALARM Set Reset RS_TR_REC PRV Transmitted to IEC System;OptGGIO1 ST;Ind1;stVal;SPS None 1 #REF!
A System;OptGGIO1 ST;Ind2;stVal;SPS SPE_HLA_Reset_Trip SPS 400kV R412_P141_64R SYSTEM REACTOR OTI TRIP Operated Reset RS_TR_REC OTI Transmitted to IEC System;OptGGIO1 ST;Ind2;stVal;SPS None 1 #REF!
SPS 400kV R412_P141_64R SYSTEM BUCHHOLZ ALARM Set Reset RS_TR_BUCH Transmitted to IEC System;OptGGIO1 ST;Ind5;stVal;SPS
DIGITAL INFORMATION TO IED IED name R412_P141_64R
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P141_64R
ANALOG INFORMATION FROM IED IED name R412_P141_64R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P141_64R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P141_64R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P141_64R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P141_64R
ANALOG INFORMATION TO IED IED name R412_P141_64R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R412_P141_64R
A SPARE 13 ANALOG INFORMATION TO IED IED name R412_P141_64R
COUNTER INFORMATION FROM IED IED name R412_P141_64R
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P141_64R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P141_64R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P141_64R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P141_64R
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R412_P442_21R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R412_P442_21R
DIGITAL INFORMATION FROM IED IED name R412_P442_21R
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R412_P442_21R PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R412_P442_21R
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R412_P442_21R PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R412_P442_21R
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P442_21R PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;CbfRBRF1 ST;OpEx;general;ACT SPE_HLA_Normal_Fail SPS 400kV R412_P442_21R PROTECTION VT FUSE FAIL Alarm Normal NL_FL_VT FUSE Transmitted to IEC System;AlmGGIO1 ST;Alm6;stVal;SPS None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P442_21R PROTECTION BACKUP IMPEDENCE R-PH TRIP Operated Reset RS_OP_B/U IMP R Transmitted to IEC Protection;DisPDIS1 ST;Op;phsA;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P442_21R PROTECTION BACKUP IMPEDENCE Y-PH TRIP Operated Reset RS_OP_B/U IMP Y Transmitted to IEC Protection;DisPDIS1 ST;Op;phsB;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P442_21R PROTECTION BACKUP IMPEDENCE B-PH TRIP Operated Reset RS_OP_B/U IMP B Transmitted to IEC Protection;DisPDIS1 ST;Op;phsC;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P442_21R PROTECTION BACKUP IMPEDENCE Operated Reset RS_OP_B/U IMP Transmitted to IEC Protection;DisPDIS1 ST;Op;general;general;ACT None 1 #REF!
A Protection;DisPDIS1 ST;Str;general;general;ACD SPE_HLA_Reset_Start SPS 400kV R412_P442_21R PROTECTION REACTOR BACKUP IMPEDANE PICKUP set Reset RS_ST_Z1 START Transmitted to IEC Protection;DisPDIS1 ST;Str;general;general;ACD None 1 #REF!
A SPARE SPS 400kV R412_P442_21R PROTECTION BACKUP IMPEDANCE Z-1 TRIP Operated Reset RS_OP_Z1 TRP None No 1 #REF!
DIGITAL INFORMATION TO IED SPS IED name R412_P442_21R
Iss. Customer Ref IED DO Reference Electrical Data SPS Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 2 DIGITAL INFORMATION TO IED IED name R412_P442_21R
ANALOG INFORMATION FROM IED SPS IED name R412_P442_21R
Iss. Customer Ref IED AI Reference Electrical Data SPS Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS Yes 6 ANALOG INFORMATION FROM IED IED name R412_P442_21R
A SPARE SPS Yes 6 ANALOG INFORMATION FROM IED IED name R412_P442_21R
A SPARE SPS Yes 6 ANALOG INFORMATION FROM IED IED name R412_P442_21R
A SPARE SPS Yes 6 ANALOG INFORMATION FROM IED IED name R412_P442_21R
ANALOG INFORMATION TO IED SPS IED name R412_P442_21R
Iss. Customer Ref IED AI Reference Electrical Data SPS Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 13 ANALOG INFORMATION TO IED IED name R412_P442_21R
A SPARE SPS 13 ANALOG INFORMATION TO IED IED name R412_P442_21R
COUNTER INFORMATION FROM IED SPS IED name R412_P442_21R
Iss. Customer Ref IED Counter Reference Electrical Data SPS Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS Yes 39 COUNTER INFORMATION FROM IED IED name R412_P442_21R
A SPARE SPS Yes 39 COUNTER INFORMATION FROM IED IED name R412_P442_21R
A SPARE SPS Yes 39 COUNTER INFORMATION FROM IED IED name R412_P442_21R
A SPARE SPS Yes 39 COUNTER INFORMATION FROM IED IED name R412_P442_21R
END OF IED DATA SPS
Iss. Customer Ref Group DI Reference Electrical Data SPS Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION SPS
Iss. Customer Ref Self DI Reference Electrical Data SPS Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION SPS
Iss. Customer Ref Self DO Reference Electrical Data SPS Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPS NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION SPS
Iss. Customer Ref Self AI Reference Electrical Data SPS Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE SPS Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION SPS
Iss. Customer Ref Self Counter Reference Electrical Data SPS Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE SPS Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION SPS
Iss. Customer Ref SetPoint Reference Electrical Data SPS Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function SPS Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE SPS Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
END OF DATA SPS
SPS 400kV R412_P442_21R PROTECTION BACKUP OVERCURRENT START Start Reset RS_ST_O/C Protection;OcpPTOC1 ST;Op;general;general;ACD
SPS 400kV R412_P442_21R PROTECTION BACKUP OVERCURRENT TRIP Operated Reset RS_OP_O/C Protection;OcpPTOC1 ST;Str;general;general;ACT
SPS 400kV R412_P442_21R PROTECTION BACKUP EARTHFAULT START Start Reset RS_ST_O/C Protection;EfdPTOC1 ST;Op;general;ACD
SPS 400kV R412_P442_21R PROTECTION BACKUP EARTHFAULT TRIP Operated Reset RS_OP_O/C Protection;EfdPTOC1 ST;Str;general;ACT
SPS 400kV R412_P442_21R SYSTEM NGR OTI ALARM Set Reset RS_ST_NGR_OTI AM System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 400kV R412_P442_21R SYSTEM NGR OTI TRIP Operated Reset RS_OP_NGR_OTI OP System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 400kV R412_P442_21R SYSTEM NGR PRD TRIP Operated Reset RS_OP_NGR_PRD OP System;OptGGIO1 ST;IndXX;stVal;SPS
N SPS 400kV R412_P442_21R SYSTEM NGR BUCHHOLZ TRIP Operated Reset RS_OP_NGR_BUC TR System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 400kV R412_P442_21R PROTECTION NGR BYPASS STAGE Operated Reset RS_OP_NGR_BYP System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 400kV R412_P442_21R PROTECTION NGR BYPASS CB CLOSE Set Reset RS_ST_NGR_BYCB System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 400kV R412_P442_21R SYSTEM NGR CLOSE COIL SUPERVISION Healthy Unhealthy UHHL_NGR_CB SUP System;OptGGIO1 ST;IndXX;stVal;SPS
SPS 400kV R412_P442_21R
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R412_P743_PU_A GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R412_P743_PU_A
DIGITAL INFORMATION FROM IED IED name R412_P743_PU_A
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R412_P743_PU_A PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R412_P743_PU_A
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R412_P743_PU_A PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R412_P743_PU_A
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R412_P743_PU_A GOOSE LBB START Set Reset RS_OP_LBB START Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R412_P743_PU_A
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R412_P743_PU_A SYSTEM LBB INITIATION 3-PH Set Reset RS_OP_LBB INI 3P Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A Protection;CbfBbpRBRF1 ST;OpIn;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P743_PU_A PROTECTION EXTERNAL CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF1 ST;OpIn;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF2 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P743_PU_A PROTECTION EXTERNAL CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF2 ST;OpEx;general;ACT None 1 #REF!
SPS 400kV R412_P743_PU_A PROTECTION CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S3 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT
SPS 400kV R412_P743_PU_A PROTECTION CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S4 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT
DIGITAL INFORMATION TO IED IED name R412_P743_PU_A
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_A
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_A
ANALOG INFORMATION FROM IED IED name R412_P743_PU_A
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P743_PU_A
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P743_PU_A
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P743_PU_A
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P743_PU_A
ANALOG INFORMATION TO IED IED name R412_P743_PU_A
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R412_P743_PU_A
A SPARE 13 ANALOG INFORMATION TO IED IED name R412_P743_PU_A
COUNTER INFORMATION FROM IED IED name R412_P743_PU_A
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P743_PU_A
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P743_PU_A
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P743_PU_A
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P743_PU_A
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
IEC Description
Computer Name R412_P743_PU_B GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
IED NAME : R412_P743_PU_B
DIGITAL INFORMATION FROM IED IED name R412_P743_PU_B
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R412_P743_PU_B PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name R412_P743_PU_B
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 400kV R412_P743_PU_B PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R412_P743_PU_B
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R412_P743_PU_B GOOSE LBB START Set Reset RS_OP_LBB START Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 DIGITAL INFORMATION FROM IED IED name R412_P743_PU_B
A System;OptGGIO1 ST;Ind7;stVal;SPS SPE_HLA_Reset_Optd SPS 400kV R412_P743_PU_B SYSTEM LBB INITIATION 3-PH Set Reset RS_OP_LBB INI 3P Transmitted to IEC System;OptGGIO1 ST;Ind7;stVal;SPS None 1 #REF!
A Protection;CbfBbpRBRF1 ST;OpIn;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P743_PU_B PROTECTION EXTERNAL CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S1 Transmitted to IEC Protection;CbfBbpRBRF1 ST;OpIn;general;ACT None 1 #REF!
A Protection;CbfBbpRBRF2 ST;OpEx;general;ACT SPE_HLA_Reset_Optd SPS 400kV R412_P743_PU_B PROTECTION EXTERNAL CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S2 Transmitted to IEC Protection;CbfBbpRBRF2 ST;OpEx;general;ACT None 1 #REF!
SPS 400kV R412_P743_PU_B PROTECTION CB FAILURE RETRIP Operated Reset RS_OP_CB FAIL S3 Transmitted to IEC Protection;CbfBbpRBRF3 ST;OpIn;general;ACT
SPS 400kV R412_P743_PU_B PROTECTION CB FAILURE BACK TRIP Operated Reset RS_OP_CB FAIL S4 Transmitted to IEC Protection;CbfBbpRBRF4 ST;OpEx;general;ACT
DIGITAL INFORMATION TO IED IED name R412_P743_PU_B
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_B
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R412_P743_PU_B
ANALOG INFORMATION FROM IED IED name R412_P743_PU_B
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P743_PU_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P743_PU_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P743_PU_B
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R412_P743_PU_B
ANALOG INFORMATION TO IED IED name R412_P743_PU_B
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R412_P743_PU_B
A SPARE 13 ANALOG INFORMATION TO IED IED name R412_P743_PU_B
COUNTER INFORMATION FROM IED IED name R412_P743_PU_B
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P743_PU_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P743_PU_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P743_PU_B
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R412_P743_PU_B
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
MiCOM C264 DESCRIPTION
Computer Name B401_LINE GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) C264 Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 0
Digital Inputs Board Slot P
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A P 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 7 SPE_HLA_Reset_Optd SPS 400kV B401-LINE 52 GEN SF6 LOCKOUT Operated Reset RS_OP_SF6 L/O Transmitted to IEC CONTROL2;XCBR1 ST;Ind12;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 8 SPE_HLA_Normal_Alarm SPS 400kV B401-LINE 52 POLE DISCREPANCY Alarm Normal RS_OP_POLE DISC Transmitted to IEC CONTROL2;XCBR1 ST;Ind13;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 9 SPE_HLA_Normal_Alarm SPS 400kV B401-LINE 52 LOSS OF SF6 GAS POLE A/B/C-1 Alarm Normal NL_AL_LOSS SF6-1 Transmitted to IEC CONTROL2;XCBR1 ST;Ind14;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 10 SPE_HLA_Normal_Alarm SPS 400kV B401-LINE 52 LOSS OF SF6-2 Alarm Normal NL_AL_LOSS SF6-2 Transmitted to IEC CONTROL2;XCBR1 ST;Ind2;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 11 SPE_HLA_Normal_Alarm SPS 400kV B401-LINE 52 SF6 LO PRESSURE LOCKOUT Alarm Normal NO_LO_SF6 LO LOW Transmitted to IEC CONTROL2;XCBR1 ST;Ind3;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 12 SPE_HLA_Normal_Alarm SPS 400kV B401-LINE 52 POLE DISCREPANCY Alarm Normal NL_AL_POLE DIS Transmitted to IEC CONTROL2;XCBR1 ST;Ind4;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 13 SPE_HLA_Normal_Fail SPS 400kV B401-LINE 52 DC SUPPLY-1\2 Fail Normal NL_FL_DC SUP12 Transmitted to IEC CONTROL2;XCBR1 ST;Ind5;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 14 SPE_HLa_Reset_Set SPS 400kV B401-LINE 52 REMOTE POS Set Reset RS_ST_REMOTE Transmitted to IEC CONTROL2;XCBR1 ST;Ind6;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 15 SPE_HLA_Normal_Alarm SPS 400kV B401-LINE 52 SPRING CHARGE STATUS B Alarm Normal DS_CH_SPING ST A Transmitted to IEC CONTROL2;XCBR1 ST;Ind1;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 16 SPE_HLA_Normal_Alarm SPS 400kV B401-LINE 52 SPRING CHARGE STATUS A Alarm Normal DS_CH_SPING ST B Transmitted to IEC CONTROL2;XCBR1 ST;Ind10;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 1
Digital Inputs Board Slot O
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A O 1 SPE_HLA_Normal_Alarm SPS 400kV B401-LINE 52 SPRING CHARGE STATUS C Alarm Normal DS_CH_SPING ST C Transmitted to IEC CONTROL2;XCBR1 ST;Ind7;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 2 SPE_HLa_Dischrgd_Charged SPS 400kV B401-LINE 52 AR CB Charged Discharged DS_CH_SPRING Transmitted to IEC CONTROL2;XCBR1 ST;Ind11;stVal;SPS 215;216;217; None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 3 SPE_HLA_Normal_Alarm SPS 400kV B401-LINE 52 TROUBLE Alarm Normal NL_AL_TROUBLE1 Transmitted to IEC CONTROL2;XCBR1 ST;Ind8;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 4 SPE_HLA_Normal_Alarm SPS 400kV B401-LINE 52 TROUBLE Alarm Normal NL_AL_TROUBLE2 Transmitted to IEC CONTROL2;XCBR1 ST;Ind9;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 5 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89A POSITION Open OE_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 205;206;210; None 58 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 6 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89A POSITION Closed OE_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 205;206;210; None 58 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 7 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89AE POSITION Open OE_CL_POS Transmitted to IEC CONTROL2;XSWI3 ST;Pos;stVal;DPC 202;203;204;207;208;209; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 8 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89AE POSITION Closed OE_CL_POS Transmitted to IEC CONTROL2;XSWI3 ST;Pos;stVal;DPC 202;203;204;207;208;209; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 9 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89AE2 POSITION Open OE_CL_POS Transmitted to IEC CONTROL2;XSWI4 ST;Pos;stVal;DPC 202;203;204;268;269;270;333;334;335;409;410;411;462;463;464;538;539;540;602;603;604; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 10 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89AE2 POSITION Closed OE_CL_POS Transmitted to IEC CONTROL2;XSWI4 ST;Pos;stVal;DPC 202;203;204;268;269;270;333;334;335;409;410;411;462;463;464;538;539;540;602;603;604; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 11 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89B POSITION Open OE_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC 205;210; None 59 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 12 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89B POSITION Closed OE_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC 205;210; None 59 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 13 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89BE POSITION Open OE_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 202;203;204;207;208;209; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 14 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89BE POSITION Closed OE_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 202;203;204;207;208;209; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 15 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89L POSITION Open OE_CL_POS Transmitted to IEC CONTROL1;XSWI3 ST;Pos;stVal;DPC 214;242;244; None 60 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 16 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89L POSITION Closed OE_CL_POS Transmitted to IEC CONTROL1;XSWI3 ST;Pos;stVal;DPC 214;242;244; None 60 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 2
Digital Inputs Board Slot N
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A N 1 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89LE POSITION Open OE_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 211;212;213; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 2 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89LE POSITION Closed OE_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 211;212;213; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 3 SPE_HLA_Normal_Fail SPS 400kV B401-LINE PROTECTION CARRIER SPEECH CHANNEL Fail Normal NL_FL_CARR SPECH Transmitted to IEC CONTROL1;GGIO1 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 4 SPE_HLA_Normal_Fail SPS 400kV B401-LINE PROTECTION DC SOURCE-1 Fail Normal NL_FL_DC SOURCE1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 5 SPE_HLA_Normal_Fail SPS 400kV B401-LINE PROTECTION DC SOURCE-2 Fail Normal NL_FL_DC SOURCE2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 6 SPE_HLA_Unhlthy_Hlthy SPS 400kV B401-LINE PROTECTION PMU Healthy Unhealthy UH_HL_PMU Transmitted to IEC CONTROL1;GGIO1 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 7 SPE_HLA_Healthy_Flty SPS 400kV B401-LINE PROTECTION CB TC-2 Faulty Healthy HL_FT_CB TC2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 8 SPE_HLA_Reset_Optd SPS 400kV B401-LINE AR FUNCTION BLOCK CONTACTS Operated Reset RS_OP_AR BLOCK Transmitted to IEC CONTROL1;RREC1 ST;Ind1;stVal;SPS None ARFct AR_Blocking_SPS 1 DIGITAL INPUT BOARD DIU2xx
A N 9 SPE_HLA_Reset_Optd SPS 400kV B401-LINE AR FUNCTION R-PH INITIATION Operated Reset RS_OP_PHR INI Transmitted to IEC CONTROL1;RREC1 ST;Ind2;stVal;SPS 216; None ARFct TripPhA_SPS 1 DIGITAL INPUT BOARD DIU2xx
A N 10 SPE_HLA_Reset_Optd SPS 400kV B401-LINE AR FUNCTION Y-PH INITIATION Operated Reset RS_OP_PHY INI Transmitted to IEC CONTROL1;RREC1 ST;Ind3;stVal;SPS 216; None ARFct TripPhB_SPS 1 DIGITAL INPUT BOARD DIU2xx
A N 11 SPE_HLA_Reset_Optd SPS 400kV B401-LINE AR FUNCTION B-PH INITIATION Operated Reset RS_OP_PHB INI Transmitted to IEC CONTROL1;RREC1 ST;Ind4;stVal;SPS 216; None ARFct TripPhC_SPS 1 DIGITAL INPUT BOARD DIU2xx
A N 12 SPE_HLA_Reset_Optd SPS 400kV B401-LINE PROTECTION A/R LOCKOUT RELAY Operated Reset OP_RS_86LO Transmitted to IEC CONTROL1;GGIO1 ST;Ind7;stVal;SPS 201; None 1 DIGITAL INPUT BOARD DIU2xx
A N 13 SPE_HLA_Reset_Optd SPS 400kV B401-LINE PROTECTION DT SEND CHANNEL-1 Operated Reset RS_OP_DT SND CH1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind9;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 15 SPE_HLA_Reset_Optd SPS 400kV B401-LINE PROTECTION DT SEND CHANNEL-2 Operated Reset RS_OP_DT SND CH2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind10;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 3
Digital Inputs Board Slot M
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A M 1 DP_HLA_Trip_Closed DPS 400kV B401-LINE 52 EMERGENCY/MANUAL Closed TP_CL_EMRG/MAN Transmitted to IEC CONTROL2;XCBR1 ST;DPCSO1;stVal;DPC 220;221; None CB 1 DIGITAL INPUT BOARD DIU2xx
A M 2 DP_HLA_Trip_Closed DPS 400kV B401-LINE 52 EMERGENCY/MANUAL Trip TP_CL_EMRG/MAN Transmitted to IEC CONTROL2;XCBR1 ST;DPCSO1;stVal;DPC 220;221; None CB 1 DIGITAL INPUT BOARD DIU2xx
A M 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 4 SPE_HLa_Reset_Out SPS 400kV B401-LINE PROTECTION CARR CH-1 Out Reset RS_OT_CARR CH-1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind3;stVal;SPS 216; None 1 DIGITAL INPUT BOARD DIU2xx
A M 5 SPE_HLa_Reset_Out SPS 400kV B401-LINE PROTECTION CARR CH-2 Out Reset RS_OT_CARR CH-2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind4;stVal;SPS 216; None 1 DIGITAL INPUT BOARD DIU2xx
A M 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 7 SPE_HLa_Reset_Set SPS 400kV B401-LINE SURGE LA COUNTER R-PH Set Reset RS_ST_LA R-PH Transmitted to IEC CONTROL1;GGIO4 ST;Ind1;stVal;SPS None 222 1 DIGITAL INPUT BOARD DIU2xx
A M 8 SPE_HLa_Reset_Set SPS 400kV B401-LINE SURGE LA COUNTER Y-PH Set Reset RS_ST_LA Y-PH Transmitted to IEC CONTROL1;GGIO4 ST;Ind2;stVal;SPS None 222 1 DIGITAL INPUT BOARD DIU2xx
A M 9 SPE_HLa_Reset_Set SPS 400kV B401-LINE SURGE LA COUNTER B-PH Set Reset RS_ST_LA B-PH Transmitted to IEC CONTROL1;GGIO4 ST;Ind3;stVal;SPS None 222 1 DIGITAL INPUT BOARD DIU2xx
A M 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 4
Digital Inputs Board Slot L
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A L 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 0
Digital Outputs Board Slot D
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A D 1 DC_SBO_Open_Close DPC 400kV B401-LINE 52 CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 57 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A D 2 SC_DE_Reset_Set_1 SPC 400kV B401-LINE PROTECTION CB TRIP COIL-2 Set XX_XX_TC2 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO3;ctlVal;DPC 207 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 3 DC_SBO_Open_Close DPC 400kV B401-LINE 52 CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 57 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A D 4 SC_DE_Reset_Set_1 SPC 400kV B401-LINE PROTECTION CB CLOSE TO PUA Set XX_XX_CB CLS PUA Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO8;ctlVal;DPC 222 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 5 SC_DE_Reset_Set_1 SPC 400kV B401-LINE PROTECTION CB CLOSE TO PUB Set XX_XX_CB CLS PUB Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO9;ctlVal;DPC 221 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 6 SC_DE_Reset_Reset SPC 400kV B401-LINE AR DATA TO A/R CLSG. CKT Reset XX_XX_A/R CLSG C Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO1;ctlVal;DPC 335 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 7 SC_DE_Off_On_1 SPC 400kV B401-LINE AR DATA A/R OFF On Off XX_XX_A/R OFF Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO2;ctlVal;DPC 6 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 8 SC_DE_Reset_Reset SPC 400kV B401-LINE AR DATA A/R LOCKOUT TRIP Reset XX_XX_A/R L/O Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO3;ctlVal;DPC 334 NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 9 SC_DE_Reset_Set SPC 400kV B401-LINE AR DATA MAIN CB A/R OPTD Set XX_XX_MAIN CB AR Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO5;ctlVal;DPC 336 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A D 10 SC_DE_Reset_Set SPC 400kV B401-LINE AR DATA TO TIE A/R PROIRITY CKT HOLD Set XX_XX_TI AR CKTH Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO4;ctlVal;DPC 337 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 1
Digital Outputs Board Slot E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A E 1 DC_SBO_Open_Close DPC 400kV B401-LINE 89A CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 58 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 2 DC_SBO_Open_Close DPC 400kV B401-LINE 89A CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 58 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 3 SC_DE_NotPerm_Perm SPC 400kV B401-LINE IL PERMISSIVE 89A I/L PERMISSIVE XX_XX_89A Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO1;ctlVal;DPC 327 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 4 SC_DE_NotPerm_Perm SPC 400kV B401-LINE IL PERMISSIVE 89AE I/L PERMISSIVE XX_XX_89AE Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO3;ctlVal;DPC 328 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 5 DC_SBO_Open_Close DPC 400kV B401-LINE 89B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 59 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 6 DC_SBO_Open_Close DPC 400kV B401-LINE 89B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 59 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 7 SC_DE_NotPerm_Perm SPC 400kV B401-LINE IL PERMISSIVE 89B I/L PERMISSIVE XX_XX_89B Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO2;ctlVal;DPC 330 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 8 SC_DE_NotPerm_Perm SPC 400kV B401-LINE IL PERMISSIVE 89BE I/L PERMISSIVE XX_XX_89BE Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO5;ctlVal;DPC 331 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 9 SC_DE_Reset_Set SPC 400kV B401-LINE PROTECTION SOTF INI M-1 Set XX_XX_SOTF_M1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO10;ctlVal;DPC 341 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A E 10 SC_DE_Reset_Set SPC 400kV B401-LINE PROTECTION SOTF INI M-2 Set XX_XX_SOTF_M2 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO2;ctlVal;DPC 340 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 2
Digital Outputs Board Slot F
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A F 1 DC_SBO_Open_Close DPC 400kV B401-LINE 89L CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 60 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 2 DC_SBO_Open_Close DPC 400kV B401-LINE 89L CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 60 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 3 SC_DE_NotPerm_Perm SPC 400kV B401-LINE IL PERMISSIVE 89L I/L PERMISSIVE XX_XX_89L Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO4;ctlVal;DPC 332 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 4 SC_DE_NotPerm_Perm SPC 400kV B401-LINE IL PERMISSIVE 89LE I/L PERMISSIVE XX_XX_89LE Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO6;ctlVal;DPC 333 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 5 SC_DE_Reset_Set_1 SPC 400kV B401-LINE PROTECTION 86A TRIP RELAY Set XX_RS_86A Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO1;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 6 SC_DE_Reset_Set_1 SPC 400kV B401-LINE PROTECTION 86B TRIP RELAY Set XX_RS_86B Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO7;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 7 SC_DE_NotPerm_Perm_1 SPC 400kV B401-LINE PROTECTION 86LO TRIP RELAY XX_RS_86LO Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO5;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 8 SC_DE_Reset_Set SPC 400kV B401-LINE PROTECTION DT SEND CHANNEL-1 Set XX_XX_DT SND CH1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO4;ctlVal;DPC 338 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 9 SC_DE_Reset_Set SPC 400kV B401-LINE PROTECTION DT SEND CHANNEL-2 Set XX_XX_DT SND CH2 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO6;ctlVal;DPC 339 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A F 10 SC_DE_NotPerm_Perm SPC 400kV B401-LINE IL PERMISSIVE 89BE2 I/L PERMISSIVE XX_XX_89BE2 Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO7;ctlVal;DPC 329 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 3
Digital Outputs Board Slot G
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A G 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A G 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
CT/VT ANALOG INPUT BOARD TMU2x0
CT/VT Board Number 0
CT/VT Board Slot Q
CT/VT Board Model TMU220
Nominal Current 1 (1A/5A)
Nominal Voltage 110.00 [1V … 500V]
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A DF MV_HLa_Frequency_1 Hz 400kV B401-LINE SYNCH DATA FREQUENCY DIFFERENCE 0.0 2.0 FREQUENCY DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifHzClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DV MV_hla_ AuxVoltage_1 V 400kV B401-LINE SYNCH DATA VOLTAGE DIFFERENCE 0.0 277.13626 VOLTAGE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifVClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Dj MV_hla_PhaseDiff ˚ 400kV B401-LINE SYNCH DATA PHASE DIFFERENCE 0.0 360.0 PHASE ANGLE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifAngClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ia MV_HLa_AuxCurrent A 400kV B401-LINE METERING I-R PHASE CURRENT 0.0 2400.0 IR PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ib MV_HLa_AuxCurrent A 400kV B401-LINE METERING I-Y PHASE CURRENT 0.0 2400.0 IY PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ic MV_HLa_AuxCurrent A 400kV B401-LINE METERING I-B PHASE CURRENT 0.0 2400.0 IB PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsC;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vb MV_hla_ AuxVoltage_1 V 400kV B401-LINE SYNCH DATA INCOMING SUPPLY 0.0 277.13626 INCOMING SUPPLY Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;PhV;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uab MV_hla_ AuxVoltage V 400kV B401-LINE METERING R-Y VOLTAGE 0.0 480.0 R-Y VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsAB;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ubc MV_HLa_Voltage kV 400kV B401-LINE METERING Y-B VOLTAGE 0.0 480.0 Y-B VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsBC;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uca MV_HLa_Voltage kV 400kV B401-LINE METERING B-R VOLTAGE 0.0 480.0 B-R VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsCA;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar MV_hla_ AuxVoltage_1 V 400kV B401-LINE SYNCH DATA RUNNING SUPPLY 0.0 277.13626 RUNNING SPLY-1 Transmitted to IEC MEASUREMENT1;barMMXU1 MX;PhV;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Freq (Line) MV_HLa_Frequency Hz 400kV B401-LINE METERING FREQUENCY 45.0 55.0 FREQUENCY Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;Hz;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A P total (MW) MV_HLa_ActPower MW 400kV B401-LINE METERING ACTIVE POWER -1662.72 1662.72 ACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotW;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Q total (Mvar) MV_HLa_ActPower MW 400kV B401-LINE METERING REACTIVE POWER -1662.72 1662.72 REACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotVAr;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A cos ft : Power factor MV_HLa_PowerFactor 400kV B401-LINE METERING POWER FACTOR -1.2 1.2 POWER FACTOR Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotPF;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPE_HLa_Reset_Set SPS 400kV B401-LINE 52 | OE_CL_CONTROL OPEN ORDER Set Reset RS_ST_OPN ORD Transmitted to IEC CONTROL1;CSWI4 ST;OpnOrd;general;general;ACT 220; None 207 CB OpenOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPE_HLa_Notper_Perm SPS 400kV B401-LINE 89A | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPE_HLa_Notper_Perm SPS 400kV B401-LINE 89B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO2 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPE_HLa_Notper_Perm SPS 400kV B401-LINE 89L | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO3 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPS_hla_Set_Reset SPS 400kV B401-LINE ORDER RUNNING ON THE BAY Set Reset RS_ST_ORD RUNING Transmitted to IEC CONTROL1;GBAY1 ST;OrdRun;stVal;SPS None OrderInProgress 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPE_HLa_Notper_Perm SPS 400kV B401-LINE 52 | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLOSE ILK Transmitted to IEC CONTROL2;CILO4 ST;EnaCls;stVal;SPS None CB CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPE_HLa_Notper_Perm SPS 400kV B401-LINE 89A | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPE_HLa_Notper_Perm SPS 400kV B401-LINE 89B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO2 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPE_HLa_Notper_Perm SPS 400kV B401-LINE 89L | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO3 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPE_HLa_Reset_Set SPS 400kV B401-LINE SYNCH FUNCTION CLOSE ORDER Set Reset RS_ST_CLS ODR Transmitted to IEC CONTROL1;RSYN1 ST;ClsOpSt;stVal;SPS None IntManualCSFct CS_CloseOrderState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPE_HLA_on_off SPS 400kV B401-LINE SYNCH FUNCTION ON/OFF SECONDARY SPS Off On RS_ST_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 ST;EnaSec;origin;SPC None 191 IntManualCSFct CS_OnOff_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPE_HLa_Reset_Set SPS 400kV B401-LINE SYNCH FUNCTION POSSIBLE CLOSING Set Reset RS_ST_POS CLS Transmitted to IEC CONTROL1;RSYN1 ST;Rel;stVal;SPS 223; None IntManualCSFct CS_AuthoState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPE_HLa_Reset_Set SPS 400kV B401-LINE SYNCH FUNCTION PRESENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF U PRES Transmitted to IEC CONTROL1;RSYN1 ST;VRefInd;stVal;SPS 223; None IntManualCSFct CS_VoltageRefPresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPE_HLa_Reset_Set SPS 400kV B401-LINE SYNCH FUNCTION ABSENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF. U ABS Transmitted to IEC CONTROL1;RSYN1 ST;VRefAbs;stVal;SPS 223; None IntManualCSFct CS_VoltageRefAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPE_HLa_Reset_Set SPS 400kV B401-LINE SYNCH FUNCTION VOLT ABSENCE Set Reset RS_ST_VOLT ABS Transmitted to IEC CONTROL1;RSYN1 ST;VAbs;stVal;SPS 214;223; None IntManualCSFct CS_VoltageAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPE_HLa_Reset_Set SPS 400kV B401-LINE SYNCH FUNCTION VOLT PRESENCE Set Reset RS_ST_VOLT PRES Transmitted to IEC CONTROL1;RSYN1 ST;VP;stVal;SPS 223; None IntManualCSFct CS_VoltagePresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 17 SPE_HLa_Notper_Perm SPS 400kV B401-LINE 52 | OE_CL_CONTROL CLOSE ORDER Permissive Not Permissive RS_ST_CLS ORD Transmitted to IEC CONTROL1;CSWI4 ST;ClsOrd;general;general;ACT 215;221; None 221;222 CB CloseOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 18 SPE_HLa_Reset_Set SPS 400kV B401-LINE AR DATA LOCK Set Reset RS_ST_S10_LOCK Transmitted to IEC CONTROL1;GAPC3 ST;IndSys1;stVal;SPS 216; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 19 SPE_HLa_Reset_Set SPS 400kV B401-LINE AR DATA WAIT FOR CB CLOSE Set Reset RS_ST_S7_WT CB C Transmitted to IEC CONTROL1;GAPC3 ST;IndSys4;stVal;SPS 215; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 20 SPE_HLa_Reset_Set SPS 400kV B401-LINE AR DATA RECLAIM_TIMER Set Reset RS_ST_S8_RC TIM Transmitted to IEC CONTROL1;GAPC3 ST;IndSys3;stVal;SPS None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 21 SPE_HLa_Reset_Set SPS 400kV B401-LINE AR DATA LOCK_SHOTS Set Reset RS_ST_S9_LO SHTS Transmitted to IEC CONTROL1;GAPC3 ST;IndSys2;stVal;SPS 216; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 22 SPE_HLA_Unhlthy_Hlthy SPS 400kV B401-LINE 52 STATUS Healthy Unhealthy UH_HL_STATUS Transmitted to IEC CONTROL1;CSWI4 ST;IndSys1;stVal;SPS None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 23 SPE_HLa_Notper_Perm SPS 400kV B401-LINE 89A IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI1 ST;IndSys1;stVal;SPS 202<; None 327 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 24 SPE_HLa_Notper_Perm SPS 400kV B401-LINE 89AE IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI3 ST;IndSys1;stVal;SPS 205<; None 328 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 25 SPE_HLa_Notper_Perm SPS 400kV B401-LINE 89AE2 IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI4 ST;IndSys1;stVal;SPS 206<; None 329 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 26 SPE_HLa_Notper_Perm SPS 400kV B401-LINE 89B IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI2 ST;IndSys1;stVal;SPS 207<; None 330 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 27 SPE_HLa_Notper_Perm SPS 400kV B401-LINE 89BE IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI1 ST;IndSys1;stVal;SPS 210<; None 331 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 28 SPE_HLa_Notper_Perm SPS 400kV B401-LINE 89L IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI3 ST;IndSys1;stVal;SPS 211<; None 332 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 29 SPE_HLa_Notper_Perm SPS 400kV B401-LINE 89LE IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI2 ST;IndSys1;stVal;SPS 214<; None 333 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 30 SPE_HLA_Reset_Optd SPS 400kV B401-LINE AR DATA LOCKOUT FROM AR LOGIC Operated Reset RS_OP_AR LO FBD Transmitted to IEC CONTROL1;GAPC3 ST;IndSys5;stVal;SPS 216<; None 334 1 C264 SELF GENERATED DIGITAL INFORMATION
A 31 SPE_HLa_Reset_Set SPS 400kV B401-LINE AR DATA A/R OPTD FROM FBD Set Reset RS_ST_AR OPTD FB Transmitted to IEC CONTROL1;GAPC3 ST;IndSys6;stVal;SPS 215<; None 335;336 1 C264 SELF GENERATED DIGITAL INFORMATION
A 32 SPE_HLa_Reset_Set SPS 400kV B401-LINE AR DATA PRIORITY CIRCUIT HOLD Set Reset RS_ST_PRI HLD ON Transmitted to IEC CONTROL1;GAPC3 ST;IndSys7;stVal;SPS 217<; None 337 1 C264 SELF GENERATED DIGITAL INFORMATION
A 33 SPE_HLA_Reset_Optd SPS 400kV B401-LINE PROTECTION DT SEND FBD Operated Reset RS_OP_DT SND FBD Transmitted to IEC CONTROL1;GAPC2 ST;IndSys2;stVal;SPS 220<; None 338;339 1 C264 SELF GENERATED DIGITAL INFORMATION
A 34 SPE_HLa_Reset_Set SPS 400kV B401-LINE PROTECTION SOTF TO RELAY Set Reset RS_ST_SOTF TO RL Transmitted to IEC CONTROL1;GAPC2 ST;IndSys1;stVal;SPS 221<; None 340;341 1 C264 SELF GENERATED DIGITAL INFORMATION
A 35 SPE_HLa_Reset_Set SPS 400kV B401-LINE SYNCH DATA CLOSE PERMISSIVE Set Reset RS_ST_CB CLOSE Transmitted to IEC CONTROL1;GAPC1 ST;IndSys5;stVal;SPS 223<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 36 SPE_HLa_Reset_Set SPS 400kV B401-LINE SYNCH DATA DEAD INCOMING DEAD RUNNING Set Reset RS_ST_DINC_DRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys4;stVal;SPS 223<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 37 SPE_HLa_Reset_Set SPS 400kV B401-LINE SYNCH DATA DEAD INCOMING LIVE RUNNING Set Reset RS_ST_DINC_LRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys3;stVal;SPS 223<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 38 SPE_HLa_Reset_Set SPS 400kV B401-LINE SYNCH DATA LIVE INCOMING DEAD RUNNING Set Reset RS_ST_LINC_DRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys2;stVal;SPS 223<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 39 SPE_HLa_Reset_Set SPS 400kV B401-LINE SYNCH DATA LIVE INCOMING LIVE RUNNING Set Reset RS_ST_LINC_LRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys1;stVal;SPS 223<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 40 DP_HLA_ ISOOpen_Close DPS 400kV B401-LINE 52 POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;stVal;DPC 202;203;204;207;208;209;211;212;213;242;244; None 57 219 Yes CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 41 DP_HLA_ ISOOpen_Close DPS 400kV B401-LINE 52 POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;stVal;DPC 202;203;204;207;208;209;211;212;213;242;244; None 57 219 Yes CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 42 DP_HLA_ ISOOpen_Close DPS 400kV B401-LINE 89A COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 43 DP_HLA_ ISOOpen_Close DPS 400kV B401-LINE 89A COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 44 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89AE COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 45 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89AE COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 46 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89AE2 COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI4 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 47 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89AE2 COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI4 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 48 DP_HLA_ ISOOpen_Close DPS 400kV B401-LINE 89B COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 49 DP_HLA_ ISOOpen_Close DPS 400kV B401-LINE 89B COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 50 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89BE COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 51 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89BE COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 52 DP_HLA_ ISOOpen_Close DPS 400kV B401-LINE 89L COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 53 DP_HLA_ ISOOpen_Close DPS 400kV B401-LINE 89L COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 54 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89LE COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 55 DP_HLa_ESOpen_Close DPS 400kV B401-LINE 89LE COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 56 DP_HLA_On_Off DPS 400kV B401-LINE AR FUNCTION ON/OFF STATUS On OF_ON_AR STATUS Transmitted to IEC CONTROL1;RREC1 ST;Ena;origin;DPC 217; None 61 6 ARFct AR_OnOff_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 57 DP_HLA_On_Off DPS 400kV B401-LINE AR FUNCTION ON/OFF STATUS Off OF_ON_AR STATUS Transmitted to IEC CONTROL1;RREC1 ST;Ena;origin;DPC 217; None 61 6 ARFct AR_OnOff_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 58 DP_HLa_LocRem_Bay DPS 400kV B401-LINE BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 62 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 59 DP_HLa_LocRem_Bay DPS 400kV B401-LINE BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 62 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 60 DP_HLa_LocRem_Bay DPS Local/remote DPS Local Local/remote DPS CONTROL1;GGSS1 ST;LocSubst;origin;DPC None 181 LocRemSubstation 1 C264 SELF GENERATED DIGITAL INFORMATION
A 61 DP_HLa_LocRem_Bay DPS Local/remote DPS Remote Local/remote DPS CONTROL1;GGSS1 ST;LocSubst;origin;DPC None 181 LocRemSubstation 1 C264 SELF GENERATED DIGITAL INFORMATION
A 62 MP_HLA_AR_Fault MPS 400kV B401-LINE AR FUNCTION AUTORECLOSER FAULT STATUS AUTORECLOSER FLT Transmitted to IEC CONTROL1;RREC1 ST;ARFlt;stVal;INS None ARFct AR_FaultReason_MPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 63 MP_HLA_AR_Status MPS 400kV B401-LINE AR FUNCTION AUTORECLOSER STATUS AUTORECLOSER ST Transmitted to IEC CONTROL1;RREC1 ST;ARSt;stVal;INS 217; None ARFct AR_Status_MPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 64 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SC_DE_Off_On SPC 400kV B401-LINE SYNCH FUNCTION ON/OFF SECONDARY CONTROL SPC On Off OF_ON_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 CO;EnaSec;ctlVal;DPC 191 IntManualCSFct CS_CtrlOnOff_SPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 DC_DE_AROff_AROn_1 DPC 400kV B401-LINE AR FUNCTION OFF Off OF_ON_A/R OFF Transmitted to IEC CONTROL1;RREC1 CO;Ena;ctlVal;DPC 61 ARFct AR_CtrlOnOff_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 DC_DE_AROff_AROn_1 DPC 400kV B401-LINE AR FUNCTION OFF On OF_ON_A/R OFF Transmitted to IEC CONTROL1;RREC1 CO;Ena;ctlVal;DPC 61 ARFct AR_CtrlOnOff_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 DC_DE_LocRem_BayCtrl DPC 400kV B401-LINE BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 62 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 DC_DE_LocRem_BayCtrl DPC 400kV B401-LINE BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 62 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 DC_DE_LocRem_BayCtrl_1 DPC Local/remote control DPC Local Loc/rem ctrl DPC CONTROL1;GGSS1 CO;LocSubst;ctlVal;DPC 181 LocRemSubstation_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 DC_DE_LocRem_BayCtrl_1 DPC Local/remote control DPC Remote Loc/rem ctrl DPC CONTROL1;GGSS1 CO;LocSubst;ctlVal;DPC 181 LocRemSubstation_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 MV_HLa_Unused 400kV B401-LINE CB_COUNTER Count_Close 0.0 10000.0 Count_Close Transmitted to IEC CONTROL2;GAPC1 MX;AnIn5;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 MV_HLa_Unused 400kV B401-LINE CB_COUNTER Count_Open 0.0 10000.0 Count_Open Transmitted to IEC CONTROL2;GAPC1 MX;AnIn4;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 MV_HLa_Unused 400kV B401-LINE SURGE COUNTER Count_BPH 0.0 10000.0 Count_BPH CONTROL2;GAPC1 MX;AnIn3;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 MV_HLa_Unused 400kV B401-LINE SURGE COUNTER Count_RPH 0.0 10000.0 Count_RPH CONTROL2;GAPC1 MX;AnIn2;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 MV_HLa_Unused 400kV B401-LINE SURGE COUNTER Count_YPH 0.0 10000.0 Count_YPH CONTROL2;GAPC1 MX;AnIn1;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
MiCOM C264 DESCRIPTION
Computer Name B402_TIE GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) C264 Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 0
Digital Inputs Board Slot P
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A P 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 7 SPE_HLA_Reset_Optd SPS 400kV B402-TIE 52 GEN SF6 LOCKOUT Operated Reset RS_OP_SF6 L/O Transmitted to IEC CONTROL2;XCBR1 ST;Ind8;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 8 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE 52 POLE DISCREPANCY Alarm Normal RS_OP_POLE DISC Transmitted to IEC CONTROL2;XCBR1 ST;Ind12;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 9 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE 52 LOSS OF SF6 GAS POLE A/B/C-1 Alarm Normal NL_AL_LOSS SF6-1 Transmitted to IEC CONTROL2;XCBR1 ST;Ind11;stVal;SPS 240; None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 10 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE 52 LOSS OF SF6-2 Alarm Normal NL_AL_LOSS SF6-2 Transmitted to IEC CONTROL2;XCBR1 ST;Ind13;stVal;SPS 240; None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 11 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE 52 SF6 LO PRESSURE LOCKOUT Alarm Normal NO_LO_SF6 LO LOW Transmitted to IEC CONTROL2;XCBR1 ST;Ind9;stVal;SPS 235; None 236 CB 1 DIGITAL INPUT BOARD DIU2xx
A P 12 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE 52 POLE DISCREPANCY Alarm Normal NL_AL_POLE DIS Transmitted to IEC CONTROL2;XCBR1 ST;Ind1;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 13 SPE_HLA_Normal_Fail SPS 400kV B402-TIE 52 DC SUPPLY-1\2 Fail Normal NL_FL_DC SUP12 Transmitted to IEC CONTROL2;XCBR1 ST;Ind14;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 14 SPE_HLa_Reset_Set SPS 400kV B402-TIE 52 REMOTE POS Set Reset RS_ST_REMOTE Transmitted to IEC CONTROL2;XCBR1 ST;Ind10;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 15 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE 52 SPRING CHARGE STATUS B Alarm Normal DS_CH_SPING ST A Transmitted to IEC CONTROL2;XCBR1 ST;Ind4;stVal;SPS 225; None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 16 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE 52 SPRING CHARGE STATUS A Alarm Normal DS_CH_SPING ST B Transmitted to IEC CONTROL2;XCBR1 ST;Ind3;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 1
Digital Inputs Board Slot O
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A O 1 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE 52 SPRING CHARGE STATUS C Alarm Normal DS_CH_SPING ST C Transmitted to IEC CONTROL2;XCBR1 ST;Ind5;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 2 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE 52 NL_AL_TROUBLE Alarm Normal NL_AL_TROUBLE1 Transmitted to IEC CONTROL2;XCBR1 ST;Ind2;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 3 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE 52 NL_AL_TROUBLE Alarm Normal NL_AL_TROUBLE2 Transmitted to IEC CONTROL2;XCBR1 ST;Ind6;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 4 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE 52 NL_AL_TROUBLE Alarm Normal NL_AL_TROUBLE3 Transmitted to IEC CONTROL2;XCBR1 ST;Ind7;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 5 DP_HLa_ESOpen_Close DPS 400kV B402-TIE 89A POSITION Open OE_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 229;233; None 64 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 6 DP_HLa_ESOpen_Close DPS 400kV B402-TIE 89A POSITION Closed OE_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 229;233; None 64 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 7 DP_HLa_ESOpen_Close DPS 400kV B402-TIE 89AE POSITION Open OE_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 226;227;228;230;231;232; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 8 DP_HLa_ESOpen_Close DPS 400kV B402-TIE 89AE POSITION Closed OE_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 226;227;228;230;231;232; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 9 DP_HLa_ESOpen_Close DPS 400kV B402-TIE 89B POSITION Open OE_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC 229;233; None 65 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 10 DP_HLa_ESOpen_Close DPS 400kV B402-TIE 89B POSITION Closed OE_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC 229;233; None 65 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 11 DP_HLa_ESOpen_Close DPS 400kV B402-TIE 89BE POSITION Open OE_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 226;227;228;230;231;232;254;255;256; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 12 DP_HLa_ESOpen_Close DPS 400kV B402-TIE 89BE POSITION Closed OE_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 226;227;228;230;231;232;254;255;256; None Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A O 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 2
Digital Inputs Board Slot N
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A N 1 SPE_HLA_Normal_Fail SPS 400kV B402-TIE PROTECTION DC SOURCE-1 Fail Normal NL_FL_DC SOURCE1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 2 SPE_HLA_Normal_Fail SPS 400kV B402-TIE PROTECTION DC SOURCE-2 Fail Normal NL_FL_DC SOURCE2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 3 SPE_HLA_Healthy_Flty SPS 400kV B402-TIE PROTECTION CB TRIP COIL-1 Faulty Healthy HL_FT_CB TC1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 4 SPE_HLA_Healthy_Flty SPS 400kV B402-TIE PROTECTION CB TRIP COIL-2 Faulty Healthy HL_FT_CB TC2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 5 SPE_HLA_Reset_Optd SPS 400kV B402-TIE PROTECTION A/R LOCKOUT RELAY Operated Reset RS_OP_86LO Transmitted to IEC CONTROL1;GGIO1 ST;Ind4;stVal;SPS 225; None 1 DIGITAL INPUT BOARD DIU2xx
A N 6 SPE_HLA_Reset_Optd SPS 400kV B402-TIE AR FUNCTION R-PHASE INITIATION Operated Reset RS_OP_PHR INI Transmitted to IEC CONTROL1;GGIO5 ST;Ind2;stVal;SPS 235; None 236 1 DIGITAL INPUT BOARD DIU2xx
A N 7 SPE_HLA_Reset_Optd SPS 400kV B402-TIE AR FUNCTION Y-PHASE INITIATION Operated Reset RS_OP_PHY INI Transmitted to IEC CONTROL1;GGIO5 ST;Ind3;stVal;SPS 235; None 236 1 DIGITAL INPUT BOARD DIU2xx
A N 8 SPE_HLA_Reset_Optd SPS 400kV B402-TIE AR FUNCTION B-PHASE INITIATION Operated Reset RS_OP_PHB INI Transmitted to IEC CONTROL1;GGIO5 ST;Ind4;stVal;SPS 235; None 236 1 DIGITAL INPUT BOARD DIU2xx
A N 9 SPE_HLa_Reset_Set SPS 400kV B402-TIE AR DATA PRIORITY CIRCUIT HOLD Set Reset RS_ST_PRI HLD ON Transmitted to IEC CONTROL2;GGIO1 ST;Ind1;stVal;SPS None 236 1 DIGITAL INPUT BOARD DIU2xx
A N 10 SPE_HLA_Reset_Optd SPS 400kV B402-TIE AR FUNCTION BLOCK Operated Reset RS_OP_AR BLOCK Transmitted to IEC CONTROL1;GGIO5 ST;Ind1;stVal;SPS None 236 1 DIGITAL INPUT BOARD DIU2xx
A N 11 SPE_HLA_Unhlthy_Hlthy SPS 400kV B402-TIE PROTECTION LBB RELAY Healthy Unhealthy UH_HL_LBB RELAY Transmitted to IEC CONTROL1;GGIO1 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 15 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE PROTECTION AC KIOSK FIRE DETECTED Alarm Normal NL_AL_FIRE DETEC Transmitted to IEC CONTROL1;GGIO1 ST;Ind7;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 16 SPE_HLA_Off_On SPS 400kV B402-TIE PROTECTION AC KIOSK COMPRESSOR 1&2 On Off OF_ON_COMPR1&2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 3
Digital Inputs Board Slot M
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A M 1 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE CSD CSD DEVICE NOT READY Alarm Normal NL_AL_CSD NR Transmitted to IEC CONTROL1;GGIO4 ST;Ind2;stVal;SPS 238; None 1 DIGITAL INPUT BOARD DIU2xx
A M 2 SPE_HLa_In_Out SPS 400kV B402-TIE CSD CSD In Out IN_OT_CSD Transmitted to IEC CONTROL1;GGIO4 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 4
Digital Inputs Board Slot L
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A L 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 0
Digital Outputs Board Slot D
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A D 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A D 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A D 10 SC_DE_Reset_Set_1 SPC 400kV B402-TIE PROTECTION CB TRIP COIL-2 Set XX_XX_TC2 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO1;ctlVal;DPC 208 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 1
Digital Outputs Board Slot E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A E 1 DC_SBO_Open_Close DPC 400kV B402-TIE 52 CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 63 236 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 2 DC_SBO_Open_Close DPC 400kV B402-TIE 52 CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 63 236 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 3 SC_DE_Reset_Set SPC 400kV B402-TIE CSD CSD BYPASS Set XX_XX_CSD BYPASS Transmitted to IEC CONTROL1;GGIO4 CO;SPCSO1;ctlVal;DPC 349 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 4 SC_DE_Reset_Set_2 SPC 400kV B402-TIE VT SELECTION 400KV BUS-2 SELECT1 Set XX_XX_BUS2 SL1 Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO3;ctlVal;DPC 355 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 5 SC_DE_Reset_Set_2 SPC 400kV B402-TIE VT SELECTION 400KV BUS-2 SELECT2 Set XX_XX_BUS2 SL2 Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO4;ctlVal;DPC 353 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 8 SC_DE_Reset_Set_2 SPC 400kV B402-TIE AR DATA TO DR Set XX_XX_TO DR Transmitted to IEC CONTROL2;GGIO1 CO;SPCSO3;ctlVal;DPC 347 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 9 SC_DE_Reset_Set SPC 400kV B402-TIE PROTECTION DT SEND CHANNEL-1 LINE Set XX_XX_DT SND CH1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO2;ctlVal;DPC 226 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A E 10 SC_DE_Reset_Set SPC 400kV B402-TIE PROTECTION DT SEND CHANNEL-2 LINE Set XX_XX_DT SND CH2 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO4;ctlVal;DPC 225 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 2
Digital Outputs Board Slot F
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A F 1 SC_DE_Reset_Set_1 SPC 400kV B402-TIE VT SELECTION 400KV BUS-2 SELECT1 FOR PSD Set XX_XX_BUS2 SL1 P Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO5;ctlVal;DPC 354 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 2 SC_DE_Reset_Set_1 SPC 400kV B402-TIE VT SELECTION 400KV BUS-2 SELECT-2 FOR PSD Set XX_XX_BUS2 SL2 P Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO6;ctlVal;DPC 352 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 3 DC_SBO_Open_Close DPC 400kV B402-TIE 89A CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 64 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 4 DC_SBO_Open_Close DPC 400kV B402-TIE 89A CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 64 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 5 SC_DE_NotPerm_Perm SPC 400kV B402-TIE IL PERMISSIVE 89A I/L PERMISSIVE XX_XX_89A Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO1;ctlVal;DPC 342 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 6 SC_DE_NotPerm_Perm SPC 400kV B402-TIE IL PERMISSIVE 89AE I/L PERMISSIVE XX_XX_89AE Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO3;ctlVal;DPC 343 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 7 DC_SBO_Open_Close DPC 400kV B402-TIE 89B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 65 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 8 DC_SBO_Open_Close DPC 400kV B402-TIE 89B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 65 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 9 SC_DE_NotPerm_Perm SPC 400kV B402-TIE IL PERMISSIVE 89B I/L PERMISSIVE XX_XX_89B Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO2;ctlVal;DPC 344 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A F 10 SC_DE_NotPerm_Perm SPC 400kV B402-TIE IL PERMISSIVE 89BE I/L PERMISSIVE XX_XX_89BE Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO4;ctlVal;DPC 345 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 3
Digital Outputs Board Slot G
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A G 1 SC_DE_NotPerm_Perm_1 SPC 400kV B402-TIE PROTECTION 86LO TRIP RELAY XX_RS_86LO Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO3;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 2 SC_DE_Reset_Set_2 SPC 400kV B402-TIE AR DATA LOCKOUT TRIP Set XX_XX_AR LO TRIP Transmitted to IEC CONTROL2;GGIO1 CO;SPCSO2;ctlVal;DPC 346 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 3 SC_DE_Off_On_2 SPC 400kV B402-TIE AR DATA A/R OFF On Off XX_XX_A/R_OFF Transmitted to IEC CONTROL2;GGIO1 CO;SPCSO1;ctlVal;DPC 7 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 4 SC_DE_Reset_Reset SPC 400kV B402-TIE AR DATA TO A/R CLSG. CKT Reset XX_XX_A/R CLSG C Transmitted to IEC CONTROL2;GGIO1 CO;SPCSO4;ctlVal;DPC 348 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 5 SC_DE_Reset_Set_1 SPC 400kV B402-TIE PROTECTION CLS CMD TO SOTF M1 Set XX_XX_SOTF M1 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO6;ctlVal;DPC 224 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 6 SC_DE_Reset_Set_1 SPC 400kV B402-TIE PROTECTION CLS CMD TO SOTF M2 Set XX_XX_SOTF M2 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO5;ctlVal;DPC 223 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 7 SC_DE_Reset_Set_1 SPC 400kV B402-TIE VT SELECTION 400KV LINE SELECT1 Set XX_XX_LINE SL1 Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO7;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 8 SC_DE_Reset_Set_1 SPC 400kV B402-TIE VT SELECTION 400KV LINE SELECT2 Set XX_XX_LINE SL2 Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO8;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 9 SC_DE_Reset_Set_2 SPC 400kV B402-TIE VT SELECTION 765KV ICT SELECT1 Set XX_XX_ICT SL1 Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO1;ctlVal;DPC 350 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A G 10 SC_DE_Reset_Set_2 SPC 400kV B402-TIE VT SELECTION 765KV ICT SELECT2 Set XX_XX_ICT SL2 Transmitted to IEC CONTROL1;GGIO3 CO;SPCSO2;ctlVal;DPC 351 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
CT/VT ANALOG INPUT BOARD TMU2x0
CT/VT Board Number 0
CT/VT Board Slot Q
CT/VT Board Model TMU220
Nominal Current 1 (1A/5A)
Nominal Voltage 110.00 [1V … 500V]
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A DF MV_HLa_Frequency_1 Hz 400kV B402-TIE SYNCH DATA FREQUENCY DIFFERENCE 0.0 2.0 FREQUENCY DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifHzClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DV MV_hla_ AuxVoltage_1 V 400kV B402-TIE SYNCH DATA VOLTAGE DIFFERENCE 0.0 277.13626 VOLTAGE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifVClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Dj MV_hla_PhaseDiff ˚ 400kV B402-TIE SYNCH DATA PHASE DIFFERENCE 0.0 360.0 PHASE ANGLE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifAngClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ia MV_HLa_AuxCurrent A 400kV B402-TIE METERING-TIE_400 I-R PHASE CURRENT 0.0 2400.0 IR PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;A;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ib MV_HLa_AuxCurrent A 400kV B402-TIE METERING-TIE_400 I-Y PHASE CURRENT 0.0 2400.0 IY PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;A;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ic MV_HLa_AuxCurrent A 400kV B402-TIE METERING-TIE_400 I-B PHASE CURRENT 0.0 2400.0 IB PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;A;phsC;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vb MV_hla_ AuxVoltage_1 V 400kV B402-TIE SYNCH DATA INCOMING SUPPLY 0.0 277.13626 INCOMING SUPPLY Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PhV;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar MV_hla_ AuxVoltage_1 V 400kV B402-TIE SYNCH DATA RUNNING SUPPLY 0.0 277.13626 RUNNING SPLY-1 Transmitted to IEC MEASUREMENT1;barMMXU1 MX;PhV;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Freq (Line) MV_HLa_Frequency Hz 400kV B402-TIE METERING-TIE_400 FREQUENCY 45.0 55.0 FREQUENCY Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;Hz;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A cos ft : Power factor MV_HLa_PowerFactor 400kV B402-TIE METERING-TIE_400 POWER FACTOR -1.2 1.2 POWER FACTOR Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotPF;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPE_HLa_Reset_Set SPS 400kV B402-TIE 52 | OE_CL_CONTROL OPEN ORDER Set Reset RS_ST_OPN ORD Transmitted to IEC CONTROL1;CSWI3 ST;OpnOrd;general;general;ACT 239; None 208 CB OpenOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPE_HLa_Notper_Perm SPS 400kV B402-TIE 89A | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPE_HLa_Notper_Perm SPS 400kV B402-TIE 89B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO2 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPS_hla_Set_Reset SPS 400kV B402-TIE ORDER RUNNING ON THE BAY Set Reset RS_ST_ORD RUNING Transmitted to IEC CONTROL1;GBAY1 ST;OrdRun;stVal;SPS None OrderInProgress 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPE_HLa_Notper_Perm SPS 400kV B402-TIE 52 | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLOSE ILK Transmitted to IEC CONTROL2;CILO3 ST;EnaCls;stVal;SPS None CB CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPE_HLa_Notper_Perm SPS 400kV B402-TIE 89A | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPE_HLa_Notper_Perm SPS 400kV B402-TIE 89B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO2 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPE_HLa_Reset_Set SPS 400kV B402-TIE SYNCH FUNCTION CLOSE ORDER Set Reset RS_ST_CLS ODR Transmitted to IEC CONTROL1;RSYN1 ST;ClsOpSt;stVal;SPS None IntManualCSFct CS_CloseOrderState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPE_HLA_on_off SPS 400kV B402-TIE SYNCH FUNCTION ON/OFF SECONDARY SPS Off On RS_ST_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 ST;EnaSec;origin;SPC None 193 IntManualCSFct CS_OnOff_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPE_HLa_Reset_Set SPS 400kV B402-TIE SYNCH FUNCTION POSSIBLE CLOSING Set Reset RS_ST_POS CLS Transmitted to IEC CONTROL1;RSYN1 ST;Rel;stVal;SPS 241; None IntManualCSFct CS_AuthoState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPE_HLa_Reset_Set SPS 400kV B402-TIE SYNCH FUNCTION PRESENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF U PRES Transmitted to IEC CONTROL1;RSYN1 ST;VRefInd;stVal;SPS 241; None IntManualCSFct CS_VoltageRefPresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPE_HLa_Reset_Set SPS 400kV B402-TIE SYNCH FUNCTION ABSENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF. U ABS Transmitted to IEC CONTROL1;RSYN1 ST;VRefAbs;stVal;SPS 241; None IntManualCSFct CS_VoltageRefAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPE_HLa_Reset_Set SPS 400kV B402-TIE SYNCH FUNCTION RS_ST_V CHOICE Set Reset RS_ST_V CHOICE Transmitted to IEC CONTROL1;RSYN1 ST;BusVC;stVal;SPS 242<; None IntManualCSFct CS_BusBarVChoice_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPE_HLa_Reset_Set SPS 400kV B402-TIE SYNCH FUNCTION VOLT ABSENCE Set Reset RS_ST_VOLT ABS Transmitted to IEC CONTROL1;RSYN1 ST;VAbs;stVal;SPS 241; None IntManualCSFct CS_VoltageAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPE_HLa_Reset_Set SPS 400kV B402-TIE SYNCH FUNCTION VOLT PRESENCE Set Reset RS_ST_VOLT PRES Transmitted to IEC CONTROL1;RSYN1 ST;VP;stVal;SPS 241; None IntManualCSFct CS_VoltagePresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPE_HLa_Notper_Perm SPS 400kV B402-TIE 52 | OE_CL_CONTROL CLOSE ORDER Permissive Not Permissive RS_ST_CLS ORD Transmitted to IEC CONTROL1;CSWI3 ST;ClsOrd;general;general;ACT 234; None 223;224;225;226 CB CloseOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 17 SPE_HLa_Reset_Set SPS 400kV B402-TIE AR DATA LOCK Set Reset RS_ST_S10_LOCK Transmitted to IEC CONTROL1;GAPC1 ST;IndSys1;stVal;SPS 235; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 18 SPE_HLa_Reset_Set SPS 400kV B402-TIE AR DATA WAIT FOR CB CLOSE Set Reset RS_ST_S7_WT CB C Transmitted to IEC CONTROL1;GAPC1 ST;IndSys3;stVal;SPS 234; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 19 SPE_HLa_Reset_Set SPS 400kV B402-TIE AR DATA LOCK_SHOTS Set Reset RS_ST_S9_LO SHTS Transmitted to IEC CONTROL1;GAPC1 ST;IndSys2;stVal;SPS 235; None MappingSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 20 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE 52 LOSS OF SF6 GAS POLE A/B/C Alarm Normal NL_AL_LOSS SF6 Transmitted to IEC CONTROL1;CSWI3 ST;IndSys1;stVal;SPS 240<; None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 21 SPE_HLa_Notper_Perm SPS 400kV B402-TIE 89A IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI1 ST;IndSys1;stVal;SPS 226<; None 342 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 22 SPE_HLa_Notper_Perm SPS 400kV B402-TIE 89AE IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI2 ST;IndSys1;stVal;SPS 229<; None 343 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 23 SPE_HLa_Notper_Perm SPS 400kV B402-TIE 89B IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI2 ST;IndSys1;stVal;SPS 230<; None 344 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 24 SPE_HLa_Notper_Perm SPS 400kV B402-TIE 89BE IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL2;CSWI1 ST;IndSys1;stVal;SPS 233<; None 345 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 25 SPE_HLA_Reset_Optd SPS 400kV B402-TIE AR DATA LOCKOUT FROM AR LOGIC Operated Reset RS_OP_AR LO FBD Transmitted to IEC CONTROL1;GAPC1 ST;IndSys4;stVal;SPS 235<; None 346 1 C264 SELF GENERATED DIGITAL INFORMATION
A 26 SPE_HLa_Reset_Set SPS 400kV B402-TIE AR DATA AR LOCK Set Reset RS_ST_AR LOCK IS Transmitted to IEC CONTROL1;GAPC1 ST;SPCSO1;origin;SPC None 192 236 1 C264 SELF GENERATED DIGITAL INFORMATION
A 27 SPE_HLa_Reset_Set SPS 400kV B402-TIE AR DATA A/R OPTD FROM FBD Set Reset RS_ST_AR OPTD FB Transmitted to IEC CONTROL1;GAPC1 ST;IndSys5;stVal;SPS 234<; None 347;348 1 C264 SELF GENERATED DIGITAL INFORMATION
A 28 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE CSD RPH-1 Alarm Normal NL_AL_RPH1 Transmitted to IEC CONTROL1;GAPC4 ST;IndSys1;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 29 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE CSD RPH-2 Alarm Normal NL_AL_RPH2 Transmitted to IEC CONTROL1;GAPC4 ST;IndSys2;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 30 SPE_HLA_Normal_Alarm SPS 400kV B402-TIE CSD RPH-3 Alarm Normal NL_AL_RPH3 Transmitted to IEC CONTROL1;GAPC4 ST;IndSys3;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 31 SPE_HLa_Reset_Set SPS 400kV B402-TIE CSD CSD BYPASS Set Reset RS_ST_CSD BYPASS Transmitted to IEC CONTROL1;GAPC4 ST;IndSys4;stVal;SPS 238<; None 349 1 C264 SELF GENERATED DIGITAL INFORMATION
A 32 SPE_HLa_Reset_Select SPS 400kV B402-TIE INTER TRIPPING TO HV ICT 706-52 OPEN ORDER Selected Reset TO HV ICT 706-52 Transmitted to IEC CONTROL1;GAPC5 ST;IndSys1;stVal;SPS 239<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 33 SPE_HLa_Reset_Select SPS 400kV B402-TIE INTER TRIPPING TO HV TIE 705-52 OPEN ORDER Selected Reset TO HV TIE 705-52 Transmitted to IEC CONTROL1;GAPC5 ST;IndSys2;stVal;SPS 239<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 34 SPE_HLa_Reset_Set SPS 400kV B402-TIE SYNCH DATA CLOSE PERMISSIVE Set Reset RS_ST_CB CLOSE Transmitted to IEC CONTROL1;GAPC2 ST;IndSys5;stVal;SPS 241<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 35 SPE_HLa_Reset_Set SPS 400kV B402-TIE SYNCH DATA DEAD INCOMING DEAD RUNNING Set Reset RS_ST_DINC_DRUN Transmitted to IEC CONTROL1;GAPC2 ST;IndSys4;stVal;SPS 241<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 36 SPE_HLa_Reset_Set SPS 400kV B402-TIE SYNCH DATA DEAD INCOMING LIVE RUNNING Set Reset RS_ST_DINC_LRUN Transmitted to IEC CONTROL1;GAPC2 ST;IndSys3;stVal;SPS 241<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 37 SPE_HLa_Reset_Set SPS 400kV B402-TIE SYNCH DATA LIVE INCOMING DEAD RUNNING Set Reset RS_ST_LINC_DRUN Transmitted to IEC CONTROL1;GAPC2 ST;IndSys2;stVal;SPS 241<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 38 SPE_HLa_Reset_Set SPS 400kV B402-TIE SYNCH DATA LIVE INCOMING LIVE RUNNING Set Reset RS_ST_LINC_LRUN Transmitted to IEC CONTROL1;GAPC2 ST;IndSys1;stVal;SPS 241<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 39 SPE_HLa_Reset_Set SPS 400kV B402-TIE VT SELECTION 765KV HV SELECT Set Reset RS_ST_765KV HV Transmitted to IEC CONTROL1;GAPC3 ST;IndSys3;stVal;SPS 244<; None 350;351 1 C264 SELF GENERATED DIGITAL INFORMATION
A 40 SPE_HLa_Reset_Set SPS 400kV B402-TIE VT SELECTION BUS1 SELECT Set Reset RS_ST_BUS1 Transmitted to IEC CONTROL1;GAPC3 ST;IndSys1;stVal;SPS 244<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 41 SPE_HLa_Reset_Set SPS 400kV B402-TIE VT SELECTION BUS2 SELECT Set Reset RS_ST_BUS2 Transmitted to IEC CONTROL1;GAPC3 ST;IndSys2;stVal;SPS None 352;353;354;355 1 C264 SELF GENERATED DIGITAL INFORMATION
A 42 DP_HLA_ ISOOpen_Close DPS 400kV B402-TIE 52 POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC 211;212;213;226;227;228;230;231;232;254;255;256; None 63 236;237 Yes CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 43 DP_HLA_ ISOOpen_Close DPS 400kV B402-TIE 52 POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC 211;212;213;226;227;228;230;231;232;254;255;256; None 63 236;237 Yes CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 44 DP_HLA_ ISOOpen_Close DPS 400kV B402-TIE 89A COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 45 DP_HLA_ ISOOpen_Close DPS 400kV B402-TIE 89A COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 46 DP_HLa_ESOpen_Close DPS 400kV B402-TIE 89AE COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 47 DP_HLa_ESOpen_Close DPS 400kV B402-TIE 89AE COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 48 DP_HLA_ ISOOpen_Close DPS 400kV B402-TIE 89B COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 49 DP_HLA_ ISOOpen_Close DPS 400kV B402-TIE 89B COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 50 DP_HLa_ESOpen_Close DPS 400kV B402-TIE 89BE COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 51 DP_HLa_ESOpen_Close DPS 400kV B402-TIE 89BE COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 52 DP_HLA_On_Off DPS 400kV B402-TIE AR FUNCTION ON/OFF STATUS On OF_ON_AR STATUS Transmitted to IEC CONTROL1;GAPC6 ST;DPCSO1;stVal;DPC 235; None 66 7 236 1 C264 SELF GENERATED DIGITAL INFORMATION
A 53 DP_HLA_On_Off DPS 400kV B402-TIE AR FUNCTION ON/OFF STATUS Off OF_ON_AR STATUS Transmitted to IEC CONTROL1;GAPC6 ST;DPCSO1;stVal;DPC 235; None 66 7 236 1 C264 SELF GENERATED DIGITAL INFORMATION
A 54 DP_HLa_LocRem_Bay DPS 400kV B402-TIE BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 67 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 55 DP_HLa_LocRem_Bay DPS 400kV B402-TIE BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 67 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 56 MP_HLA_AR_Fault MPS 400kV B402-TIE AR_1PH_1SHOT_ISA AUTORECLOSER FAULT STATUS AUTORECLOSER FLT Transmitted to IEC CONTROL2;GAPC2 ST;IntSys2;stVal;INS None UsrFct UserFunctionMPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 57 MP_HLA_AR_Status MPS 400kV B402-TIE AR_1PH_1SHOT_ISA AUTORECLOSER STATUS AUTORECLOSER ST Transmitted to IEC CONTROL2;GAPC2 ST;IntSys1;stVal;INS None UsrFct UserFunctionMPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 58 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SC_DE_Reset_Set_Int_1 SPC 400kV B402-TIE AR DATA A/R LOCK Set UL_LO_AR Transmitted to IEC CONTROL1;GAPC1 CO;SPCSO1;ctlVal;DPC 192 236 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SC_DE_Reset_Set SPC 400kV B402-TIE CSD CSD OUT FROM HMI Set XX_ST_CSD OUT H Transmitted to IEC CONTROL1;GAPC4 CO;SPCSO1;ctlVal;DPC 238; 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SC_DE_Off_On SPC 400kV B402-TIE SYNCH FUNCTION ON/OFF SECONDARY CONTROL SPC On Off OF_ON_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 CO;EnaSec;ctlVal;DPC 193 IntManualCSFct CS_CtrlOnOff_SPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 DC_DE_AROff_AROn DPC 400kV B402-TIE AR FUNCTION OFF Off OF_ON_A/R OFF Transmitted to IEC CONTROL1;GAPC6 CO;DPCSO1;ctlVal;DPC 66 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 DC_DE_AROff_AROn DPC 400kV B402-TIE AR FUNCTION OFF On OF_ON_A/R OFF Transmitted to IEC CONTROL1;GAPC6 CO;DPCSO1;ctlVal;DPC 66 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 DC_DE_LocRem_BayCtrl DPC 400kV B402-TIE BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 67 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 DC_DE_LocRem_BayCtrl DPC 400kV B402-TIE BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 67 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 MV_HLa_Unused 400kV B402-TIE CB_COUNTER Count_Close 0.0 10000.0 Count_Close Transmitted to IEC CONTROL2;GAPC2 MX;AnIn2;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 MV_HLa_Unused 400kV B402-TIE CB_COUNTER Count_Open 0.0 10000.0 Count_Open Transmitted to IEC CONTROL2;GAPC2 MX;AnIn1;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
MiCOM C264 DESCRIPTION
Computer Name B409_ICT1 GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) C264 Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 0
Digital Inputs Board Slot P
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS 400kV B409-ICT-1 RPH MOG LOW OIL LEVEL ALARM None No 1 DIGITAL INPUT BOARD DIU2xx
A 2 SPARE SPS 400kV B409-ICT-1 YPH MOG LOW OIL LEVEL ALARM None No 1 DIGITAL INPUT BOARD DIU2xx
A 3 SPARE SPS 400kV B409-ICT-1 BPH MOG LOW OIL LEVEL ALARM None No 1 DIGITAL INPUT BOARD DIU2xx
A 4 SPARE SPS 400kV B409-ICT-1 SP-PH MOG LOW OIL LEVEL ALARM None No 1 DIGITAL INPUT BOARD DIU2xx
A 5 SPARE SPS 400kV B409-ICT-1 RPH MOG HIGH OIL LEVEL ALARM None No 1 DIGITAL INPUT BOARD DIU2xx
A 6 SPARE SPS 400kV B409-ICT-1 YPH MOG HIGH OIL LEVEL ALARM None No 1 DIGITAL INPUT BOARD DIU2xx
A 1 SPARE SPS 400kV B409-ICT-1 BPH MOG HIGH OIL LEVEL ALARM None No 1 DIGITAL INPUT BOARD DIU2xx
A 2 SPARE SPS 400kV B409-ICT-1 SP-PH MOG HIGH OIL LEVEL ALARM None No 1 DIGITAL INPUT BOARD DIU2xx
A 3 SPARE SPS 400kV B409-ICT-1 R-PH OIL FLOW SENSITIVE VALVE ALARM None No 1 DIGITAL INPUT BOARD DIU2xx
A 4 SPARE SPS 400kV B409-ICT-1 Y-PH OIL FLOW SENSITIVE VALVE ALARM None No 1 DIGITAL INPUT BOARD DIU2xx
A 5 SPARE SPS 400kV B409-ICT-1 B-PH OIL FLOW SENSITIVE VALVE ALARM None No 1 DIGITAL INPUT BOARD DIU2xx
A 6 SPARE SPS 400kV B409-ICT-1 SP-PH OIL FLOW SENSITIVE VALVE ALARM None No 1 DIGITAL INPUT BOARD DIU2xx
A 1 SPARE SPS 400kV B409-ICT-1 RPH PUMP FAIL - BANK A None No 1 DIGITAL INPUT BOARD DIU2xx
A 2 SPARE SPS 400kV B409-ICT-1 RPH PUMP FAIL - BANK B None No 1 DIGITAL INPUT BOARD DIU2xx
A 1 SPARE SPS 400kV B409-ICT-1 RPH PUMP FAIL - BANK C None No 1 DIGITAL INPUT BOARD DIU2xx
A 2 SPARE SPS 400kV B409-ICT-1 RPH PUMP FAIL - BANK D None No 1 DIGITAL INPUT BOARD DIU2xx
A 3 SPARE SPS 400kV B409-ICT-1 YPH PUMP FAIL - BANK A None No 1 DIGITAL INPUT BOARD DIU2xx
A 4 SPARE SPS 400kV B409-ICT-1 YPH PUMP FAIL - BANK B None No 1 DIGITAL INPUT BOARD DIU2xx
A 5 SPARE SPS 400kV B409-ICT-1 YPH PUMP FAIL - BANK C None No 1 DIGITAL INPUT BOARD DIU2xx
A 6 SPARE SPS 400kV B409-ICT-1 YPH PUMP FAIL - BANK D None No 1 DIGITAL INPUT BOARD DIU2xx
A 1 SPARE SPS 400kV B409-ICT-1 BPH PUMP FAIL - BANK A None No 1 DIGITAL INPUT BOARD DIU2xx
A 2 SPARE SPS 400kV B409-ICT-1 BPH PUMP FAIL - BANK B None No 1 DIGITAL INPUT BOARD DIU2xx
A 3 SPARE SPS 400kV B409-ICT-1 BPH PUMP FAIL - BANK C None No 1 DIGITAL INPUT BOARD DIU2xx
A 4 SPARE SPS 400kV B409-ICT-1 BPH PUMP FAIL - BANK D None No 1 DIGITAL INPUT BOARD DIU2xx
A 5 SPARE SPS 400kV B409-ICT-1 SPH PUMP FAIL - BANK A None No 1 DIGITAL INPUT BOARD DIU2xx
A 6 SPARE SPS 400kV B409-ICT-1 SPH PUMP FAIL - BANK B None No 1 DIGITAL INPUT BOARD DIU2xx
A 1 SPARE SPS 400kV B409-ICT-1 SPH PUMP FAIL - BANK C None No 1 DIGITAL INPUT BOARD DIU2xx
A 2 SPARE SPS 400kV B409-ICT-1 SPH PUMP FAIL - BANK D None No 1 DIGITAL INPUT BOARD DIU2xx
A 3 SPARE SPS 400kV B409-ICT-1 RPH THERMAL OVERLOAD TRIP - BANK A None No 1 DIGITAL INPUT BOARD DIU2xx
A 4 SPARE SPS 400kV B409-ICT-1 RPH THERMAL OVERLOAD TRIP - BANK B None No 1 DIGITAL INPUT BOARD DIU2xx
A 5 SPARE SPS 400kV B409-ICT-1 RPH THERMAL OVERLOAD TRIP - BANK C None No 1 DIGITAL INPUT BOARD DIU2xx
A 6 SPARE SPS 400kV B409-ICT-1 RPH THERMAL OVERLOAD TRIP - BANK D None No 1 DIGITAL INPUT BOARD DIU2xx
A 1 SPARE SPS 400kV B409-ICT-1 YPH THERMAL OVERLOAD TRIP - BANK A None No 1 DIGITAL INPUT BOARD DIU2xx
A 2 SPARE SPS 400kV B409-ICT-1 YPH THERMAL OVERLOAD TRIP - BANK B None No 1 DIGITAL INPUT BOARD DIU2xx
A 3 SPARE SPS 400kV B409-ICT-1 YPH THERMAL OVERLOAD TRIP - BANK C None No 1 DIGITAL INPUT BOARD DIU2xx
A 4 SPARE SPS 400kV B409-ICT-1 YPH THERMAL OVERLOAD TRIP - BANK D None No 1 DIGITAL INPUT BOARD DIU2xx
A 5 SPARE SPS 400kV B409-ICT-1 BPH THERMAL OVERLOAD TRIP - BANK A None No 1 DIGITAL INPUT BOARD DIU2xx
A 6 SPARE SPS 400kV B409-ICT-1 BPH THERMAL OVERLOAD TRIP - BANK B None No 1 DIGITAL INPUT BOARD DIU2xx
A 1 SPARE SPS 400kV B409-ICT-1 BPH THERMAL OVERLOAD TRIP - BANK C None No 1 DIGITAL INPUT BOARD DIU2xx
A 2 SPARE SPS 400kV B409-ICT-1 BPH THERMAL OVERLOAD TRIP - BANK D None No 1 DIGITAL INPUT BOARD DIU2xx
A 3 SPARE SPS 400kV B409-ICT-1 SPH THERMAL OVERLOAD TRIP - BANK A None No 1 DIGITAL INPUT BOARD DIU2xx
A 4 SPARE SPS 400kV B409-ICT-1 SPH THERMAL OVERLOAD TRIP - BANK B None No 1 DIGITAL INPUT BOARD DIU2xx
A 5 SPARE SPS 400kV B409-ICT-1 SPH THERMAL OVERLOAD TRIP - BANK C None No 1 DIGITAL INPUT BOARD DIU2xx
A 6 SPARE SPS 400kV B409-ICT-1 SPH THERMAL OVERLOAD TRIP - BANK D None No 1 DIGITAL INPUT BOARD DIU2xx
A 1 SPARE SPS 400kV B409-ICT-1 RPH LOW OIL FLOW/REVERSE FLOW - BANK A None No 1 DIGITAL INPUT BOARD DIU2xx
A 2 SPARE SPS 400kV B409-ICT-1 RPH LOW OIL FLOW/REVERSE FLOW - BANK B None No 1 DIGITAL INPUT BOARD DIU2xx
A 3 SPARE SPS 400kV B409-ICT-1 RPH LOW OIL FLOW/REVERSE FLOW - BANK C None No 1 DIGITAL INPUT BOARD DIU2xx
A 4 SPARE SPS 400kV B409-ICT-1 RPH LOW OIL FLOW/REVERSE FLOW - BANK D None No 1 DIGITAL INPUT BOARD DIU2xx
A 5 SPARE SPS 400kV B409-ICT-1 YPH LOW OIL FLOW/REVERSE FLOW - BANK A None No 1 DIGITAL INPUT BOARD DIU2xx
A 6 SPARE SPS 400kV B409-ICT-1 YPH LOW OIL FLOW/REVERSE FLOW - BANK B None No 1 DIGITAL INPUT BOARD DIU2xx
A 1 SPARE SPS 400kV B409-ICT-1 YPH LOW OIL FLOW/REVERSE FLOW - BANK C None No 1 DIGITAL INPUT BOARD DIU2xx
A 2 SPARE SPS 400kV B409-ICT-1 YPH LOW OIL FLOW/REVERSE FLOW - BANK D None No 1 DIGITAL INPUT BOARD DIU2xx
A 1 SPARE SPS 400kV B409-ICT-1 BPH LOW OIL FLOW/REVERSE FLOW - BANK A None No 1 DIGITAL INPUT BOARD DIU2xx
A 2 SPARE SPS 400kV B409-ICT-1 BPH LOW OIL FLOW/REVERSE FLOW - BANK B None No 1 DIGITAL INPUT BOARD DIU2xx
A 3 SPARE SPS 400kV B409-ICT-1 BPH LOW OIL FLOW/REVERSE FLOW - BANK C None No 1 DIGITAL INPUT BOARD DIU2xx
A 4 SPARE SPS 400kV B409-ICT-1 BPH LOW OIL FLOW/REVERSE FLOW - BANK D None No 1 DIGITAL INPUT BOARD DIU2xx
A 5 SPARE SPS 400kV B409-ICT-1 SPH LOW OIL FLOW/REVERSE FLOW - BANK A None No 1 DIGITAL INPUT BOARD DIU2xx
A 6 SPARE SPS 400kV B409-ICT-1 SPH LOW OIL FLOW/REVERSE FLOW - BANK B None No 1 DIGITAL INPUT BOARD DIU2xx
A 1 SPARE SPS 400kV B409-ICT-1 SPH LOW OIL FLOW/REVERSE FLOW - BANK C None No 1 DIGITAL INPUT BOARD DIU2xx
A 2 SPARE SPS 400kV B409-ICT-1 SPH LOW OIL FLOW/REVERSE FLOW - BANK D None No 1 DIGITAL INPUT BOARD DIU2xx
A 3 SPARE SPS 400kV B409-ICT-1 RPH COOLER CONTROL SUPPLY FAIL None No 1 DIGITAL INPUT BOARD DIU2xx
A 4 SPARE SPS 400kV B409-ICT-1 YPH COOLER CONTROL SUPPLY FAIL None No 1 DIGITAL INPUT BOARD DIU2xx
A 5 SPARE SPS 400kV B409-ICT-1 BPH COOLER CONTROL SUPPLY FAIL None No 1 DIGITAL INPUT BOARD DIU2xx
A 6 SPARE SPS 400kV B409-ICT-1 SPH COOLER CONTROL SUPPLY FAIL None No 1 DIGITAL INPUT BOARD DIU2xx
A 1 SPARE SPS 400kV B409-ICT-1 RPH SUPPLY CHANGE OVER FAIL None No 1 DIGITAL INPUT BOARD DIU2xx
A 2 SPARE SPS 400kV B409-ICT-1 YPH SUPPLY CHANGE OVER FAIL None No 1 DIGITAL INPUT BOARD DIU2xx
SPS 400kV B409-ICT-1 BPH SUPPLY CHANGE OVER FAIL
SPS 400kV B409-ICT-1 SPH SUPPLY CHANGE OVER FAIL
SPS 400kV B409-ICT-1 RPH SUPPLY - A FAIL
SPS 400kV B409-ICT-1 YPH SUPPLY - A FAIL
SPS 400kV B409-ICT-1 BPH SUPPLY - A FAIL
SPS 400kV B409-ICT-1 SPH SUPPLY - A FAIL
SPS 400kV B409-ICT-1 RPH SUPPLY - B FAIL
SPS 400kV B409-ICT-1 YPH SUPPLY - B FAIL
SPS 400kV B409-ICT-1 BPH SUPPLY - B FAIL
SPS 400kV B409-ICT-1 SPH SUPPLY - B FAIL
SPS 400kV B409-ICT-1 RPH OLTC MOTOR OVERLOAD
A 3 SPARE SPS 400kV B409-ICT-1 RPH TAP CHANGE IN PROGRESS None No 1 DIGITAL INPUT BOARD DIU2xx
A 4 SPARE SPS 400kV B409-ICT-1 RPH TAP CHANGE IN COMPLETE None No 1 DIGITAL INPUT BOARD DIU2xx
A 5 SPARE SPS 400kV B409-ICT-1 RPH OLTC IN LOCAL None No 1 DIGITAL INPUT BOARD DIU2xx
A 6 SPARE SPS 400kV B409-ICT-1 RPH OLTC IN REMOTE None No 1 DIGITAL INPUT BOARD DIU2xx
A P 1 SPARE SPS 400kV B409-ICT-1 RPH TAP CHANGE CONTROL SUPPLY FAIL None No 1 DIGITAL INPUT BOARD DIU2xx
A P 2 SPARE SPS 400kV B409-ICT-1 RPH LOWEST POSITION REACHDED None No 1 DIGITAL INPUT BOARD DIU2xx
A P 3 SPARE SPS 400kV B409-ICT-1 RPH HIGHESHT POSITION REACHDED None No 1 DIGITAL INPUT BOARD DIU2xx
A P 4 SPARE SPS 400kV B409-ICT-1 RPH OLTC RAISE COMMAND None No 1 DIGITAL INPUT BOARD DIU2xx
A P 5 SPARE SPS 400kV B409-ICT-1 RPH OLTC LOWER COMMAND None No 1 DIGITAL INPUT BOARD DIU2xx
A P 6 SPARE SPS 400kV B409-ICT-1 YPH OLTC MOTOR OVERLOAD None No 1 DIGITAL INPUT BOARD DIU2xx
A P 7 SPE_HLA_Reset_Optd SPS 400kV B409-ICT-1 52 YPH TAP CHANGE IN PROGRESS Operated Reset RS_OP_SF6 L/O Transmitted to IEC CONTROL4;XCBR1 ST;Ind12;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 8 SPE_HLA_Normal_Alarm SPS 400kV B409-ICT-1 52 YPH TAP CHANGE IN COMPLETE Alarm Normal RS_OP_POLE DISC Transmitted to IEC CONTROL4;XCBR1 ST;Ind8;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 9 SPE_HLA_Normal_Alarm SPS 400kV B409-ICT-1 52 YPH OLTC IN LOCAL Alarm Normal NL_AL_LOSS SF6-1 Transmitted to IEC CONTROL4;XCBR1 ST;Ind9;stVal;SPS 403; None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 10 SPE_HLA_Normal_Alarm SPS 400kV B409-ICT-1 52 YPH OLTC IN REMOTE Alarm Normal NL_AL_LOSS SF6-2 Transmitted to IEC CONTROL4;XCBR1 ST;Ind13;stVal;SPS 403; None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 11 SPE_HLA_Normal_Alarm SPS 400kV B409-ICT-1 52 YPH TAP CHANGE CONTROL SUPPLY FAIL Alarm Normal NO_LO_SF6 LO LOW Transmitted to IEC CONTROL4;XCBR1 ST;Ind6;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 12 SPE_HLA_Normal_Alarm SPS 400kV B409-ICT-1 52 YPH LOWEST POSITION REACHDED Alarm Normal NL_AL_POLE DIS Transmitted to IEC CONTROL4;XCBR1 ST;Ind7;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 13 SPE_HLA_Normal_Fail SPS 400kV B409-ICT-1 52 YPH HIGHESHT POSITION REACHDED Fail Normal NL_FL_DC SUP12 Transmitted to IEC CONTROL4;XCBR1 ST;Ind1;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 14 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 52 YPH OLTC RAISE COMMAND Set Reset RS_ST_REMOTE Transmitted to IEC CONTROL4;XCBR1 ST;Ind2;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 15 SPE_HLA_Normal_Alarm SPS 400kV B409-ICT-1 52 YPH OLTC LOWER COMMAND Alarm Normal DS_CH_SPING ST A Transmitted to IEC CONTROL4;XCBR1 ST;Ind3;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 16 SPE_HLA_Normal_Alarm SPS 400kV B409-ICT-1 52 BPH OLTC MOTOR OVERLOAD Alarm Normal DS_CH_SPING ST B Transmitted to IEC CONTROL4;XCBR1 ST;Ind4;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
BPH TAP CHANGE IN PROGRESS
DIGITAL INPUT BOARD DIU2xx BPH TAP CHANGE IN COMPLETE
Digital Inputs Board Number 1 BPH OLTC IN LOCAL
Digital Inputs Board Slot O BPH OLTC IN REMOTE
Iss. Customer Ref DI Reference Electrical Data BPH TAP CHANGE CONTROL SUPPLY FAIL Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) BPH LOWEST POSITION REACHDED Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A O 1 SPE_HLA_Normal_Alarm SPS 400kV B409-ICT-1 52 BPH HIGHESHT POSITION REACHDED Alarm Normal DS_CH_SPING ST C Transmitted to IEC CONTROL4;XCBR1 ST;Ind5;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 2 SPE_HLA_Normal_Alarm SPS 400kV B409-ICT-1 52 BPH OLTC RAISE COMMAND Alarm Normal NL_AL_CB TROUBL4 Transmitted to IEC CONTROL4;XCBR1 ST;Ind11;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 3 SPE_HLA_Normal_Alarm SPS 400kV B409-ICT-1 52 BPH OLTC LOWER COMMAND Alarm Normal NL_AL_CB TROUB 1 Transmitted to IEC CONTROL4;XCBR1 ST;Ind14;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 4 SPE_HLA_Normal_Alarm SPS 400kV B409-ICT-1 52 SPH OLTC MOTOR OVERLOAD Alarm Normal NL_AL_CB TROUBL3 Transmitted to IEC CONTROL4;XCBR1 ST;Ind10;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 5 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89A SPH TAP CHANGE IN PROGRESS Open OE_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 370;374; None 101 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 6 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89A SPH TAP CHANGE IN COMPLETE Closed OE_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 370;374; None 101 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 7 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89AE SPH OLTC IN LOCAL Open OE_CL_POS Transmitted to IEC CONTROL3;XSWI6 ST;Pos;stVal;DPC 367;368;369;371;372;373; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 8 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89AE SPH OLTC IN REMOTE Closed OE_CL_POS Transmitted to IEC CONTROL3;XSWI6 ST;Pos;stVal;DPC 367;368;369;371;372;373; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 9 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 SPH TAP CHANGE CONTROL SUPPLY FAIL Open 7_Z_TSR POS Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO8;stVal;DPC 398; None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 10 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 SPH LOWEST POSITION REACHDED Closed 7_Z_TSR POS Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO8;stVal;DPC 398; None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 11 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89B SPH HIGHESHT POSITION REACHDED Open OE_CL_POS Transmitted to IEC CONTROL1;XSWI6 ST;Pos;stVal;DPC 370;374; None 102 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 12 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89B SPH OLTC RAISE COMMAND Closed OE_CL_POS Transmitted to IEC CONTROL1;XSWI6 ST;Pos;stVal;DPC 370;374; None 102 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 13 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89BE SPH OLTC LOWER COMMAND Open OE_CL_POS Transmitted to IEC CONTROL3;XSWI4 ST;Pos;stVal;DPC 367;368;369;371;372;373; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 14 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89BE POSITION Closed OE_CL_POS Transmitted to IEC CONTROL3;XSWI4 ST;Pos;stVal;DPC 367;368;369;371;372;373; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 15 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 7_Z_TE R POS Open 7_Z_TE R POS Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO7;stVal;DPC 376;377;378;379;380;381; None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 16 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 7_Z_TE R POS Closed 7_Z_TE R POS Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO7;stVal;DPC 376;377;378;379;380;381; None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 2
Digital Inputs Board Slot N
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A N 1 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89T-R POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 375;386;391;392;393;409; None 104 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 2 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89T-R POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 375;386;391;392;393;409; None 104 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 3 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE-R POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI1 ST;Pos;stVal;DPC 379;380;381; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 4 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE-R POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI1 ST;Pos;stVal;DPC 379;380;381; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 5 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89T-Y POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC 375;387;395;396;397;409; None 108 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 6 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89T-Y POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI2 ST;Pos;stVal;DPC 375;387;395;396;397;409; None 108 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 7 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE-Y POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI2 ST;Pos;stVal;DPC 382;383;384; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 8 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE-Y POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI2 ST;Pos;stVal;DPC 382;383;384; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 9 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89T-B POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI7 ST;Pos;stVal;DPC 375;385;388;389;390;409; None 103 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 10 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89T-B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI7 ST;Pos;stVal;DPC 375;385;388;389;390;409; None 103 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 11 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE-B POSITION Open OP_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 376;377;378; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 12 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE-B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 376;377;378; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 13 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TS-R POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI4 ST;Pos;stVal;DPC 375;379;380;381;388;389;390;394;395;396;397;398;409;517;518;519;520;521;522;523;524;525;526;666;667;668;669;670;671;672;673;674;675; None 106 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 14 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TS-R POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI4 ST;Pos;stVal;DPC 375;379;380;381;388;389;390;394;395;396;397;398;409;517;518;519;520;521;522;523;524;525;526;666;667;668;669;670;671;672;673;674;675; None 106 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 15 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TS-Y POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI5 ST;Pos;stVal;DPC 375;382;383;384;388;389;390;391;392;393;394;398;409;517;518;519;520;521;522;523;524;525;526;666;667;668;669;670;671;672;673;674;675; None 107 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A N 16 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TS-Y POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI5 ST;Pos;stVal;DPC 375;382;383;384;388;389;390;391;392;393;394;398;409;517;518;519;520;521;522;523;524;525;526;666;667;668;669;670;671;672;673;674;675; None 107 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 3
Digital Inputs Board Slot M
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A M 1 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TS-B POSITION Open OP_CL_POS Transmitted to IEC CONTROL1;XSWI3 ST;Pos;stVal;DPC 375;376;377;378;391;392;393;394;395;396;397;398;409;517;518;519;520;521;522;523;524;525;526;666;667;668;669;670;671;672;673;674;675; None 105 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A M 2 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TS-B POSITION Closed OP_CL_POS Transmitted to IEC CONTROL1;XSWI3 ST;Pos;stVal;DPC 375;376;377;378;391;392;393;394;395;396;397;398;409;517;518;519;520;521;522;523;524;525;526;666;667;668;669;670;671;672;673;674;675; None 105 Yes SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A M 3 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TS-RE POSITION Open OP_CL_POS Transmitted to IEC CONTROL3;XSWI3 ST;Pos;stVal;DPC None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A M 4 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TS-RE POSITION Closed OP_CL_POS Transmitted to IEC CONTROL3;XSWI3 ST;Pos;stVal;DPC None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A M 5 SPE_HLA_Normal_Fail SPS 400kV B409-ICT-1 PROTECTION DC SUPPLY-1 Fail Normal NL_FL_DC SUP1 Transmitted to IEC CONTROL2;GGIO1 ST;Ind11;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 6 SPE_HLA_Normal_Fail SPS 400kV B409-ICT-1 PROTECTION DC SUPPLY-2 Fail Normal NL_FL_DC SUP-2 Transmitted to IEC CONTROL2;GGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 7 SPE_HLA_Healthy_Flty SPS 400kV B409-ICT-1 PROTECTION TRIP COIL-1 Faulty Healthy HL_FT_TC1 Transmitted to IEC CONTROL2;GGIO1 ST;Ind10;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 8 SPE_HLA_Healthy_Flty SPS 400kV B409-ICT-1 PROTECTION TRIP COIL-2 Faulty Healthy HL_FT_TC2 Transmitted to IEC CONTROL2;GGIO1 ST;Ind9;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 9 SPE_HLA_Healthy_Flty SPS 400kV B409-ICT-1 PROTECTION PUA RELAY Faulty Healthy HL_FT_PUA RLY Transmitted to IEC CONTROL2;GGIO1 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 10 SPE_HLA_Healthy_Flty SPS 400kV B409-ICT-1 PROTECTION PUB RELAY Faulty Healthy HL_FT_PUB RLY Transmitted to IEC CONTROL2;GGIO1 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M -12 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 PROTECTION AT SELECT Set Reset RS_ST_AT SELECT Transmitted to IEC CONTROL2;GGIO1 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M -13 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 PROTECTION R/Y/B AT SELECT Set Reset RS_ST_R/Y/B AT Transmitted to IEC CONTROL2;GGIO1 ST;Ind5;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A M 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 15 DP_HLA_Trip_Closed DPS 400kV B409-ICT-1 52 EMERGENCY/MANUAL Trip TP_CL_EMRG/MAN Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO1;stVal;DPC 404; None CB 1 DIGITAL INPUT BOARD DIU2xx
A M 16 DP_HLA_Trip_Closed DPS 400kV B409-ICT-1 52 EMERGENCY/MANUAL Closed TP_CL_EMRG/MAN Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO1;stVal;DPC 404; None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 4
Digital Inputs Board Slot L
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A L 1 SPE_HLA_Normal_Alarm SPS 400kV B409-ICT-1 CSD CSD DEVICE NOT READY Alarm Normal NL_AL_CSD NR Transmitted to IEC CONTROL2;GGIO3 ST;Ind2;stVal;SPS 400; None 1 DIGITAL INPUT BOARD DIU2xx
A L 2 SPE_HLa_In_Out SPS 400kV B409-ICT-1 CSD CSD In Out IN_OT_CSD Transmitted to IEC CONTROL2;GGIO3 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 3 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 PROTECTION LA COUNTER R PHASE Set Reset RS_ST_LA COUN R Transmitted to IEC CONTROL2;GGIO1 ST;Ind6;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 4 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 PROTECTION LA COUNTER Y PHASE Set Reset RS_ST_LA COUN Y Transmitted to IEC CONTROL2;GGIO1 ST;Ind7;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 5 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 PROTECTION LA COUNTER B PHASE Set Reset RS_ST_LA COUN B Transmitted to IEC CONTROL2;GGIO1 ST;Ind8;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A L 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 7 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 7_Y_52 POS Open 7_Y_52 POS Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO2;stVal;DPC 376;377;378;379;380;381;382;383;384;388;389;390;391;392;393;395;396;397; None CB 1 DIGITAL INPUT BOARD DIU2xx
A L 8 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 7_Y_52 POS Closed 7_Y_52 POS Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO2;stVal;DPC 376;377;378;379;380;381;382;383;384;388;389;390;391;392;393;395;396;397; None CB 1 DIGITAL INPUT BOARD DIU2xx
A L 9 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 7_Z_52 POS Open 7_Z_52 POS Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO3;stVal;DPC 376;377;378;379;380;381;382;383;384;388;389;390;391;392;393;395;396;397; None CB 1 DIGITAL INPUT BOARD DIU2xx
A L 10 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 7_Z_52 POS Closed 7_Z_52 POS Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO3;stVal;DPC 376;377;378;379;380;381;382;383;384;388;389;390;391;392;393;395;396;397; None CB 1 DIGITAL INPUT BOARD DIU2xx
A L 11 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 7_Z_TR POS Open 7_Z_TR POS Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO4;stVal;DPC 386; None CB 1 DIGITAL INPUT BOARD DIU2xx
A L 12 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 7_Z_TR POS Closed 7_Z_TR POS Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO4;stVal;DPC 386; None CB 1 DIGITAL INPUT BOARD DIU2xx
A L 13 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 7_Z_TY POS Open 7_Z_TY POS Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO5;stVal;DPC 387; None CB 1 DIGITAL INPUT BOARD DIU2xx
A L 14 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 7_Z_TY POS Closed 7_Z_TY POS Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO5;stVal;DPC 387; None CB 1 DIGITAL INPUT BOARD DIU2xx
A L 15 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 7_Z_TB POS Open 7_Z_TB POS Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO6;stVal;DPC 385; None CB 1 DIGITAL INPUT BOARD DIU2xx
A L 16 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 7_Z_TB POS Closed 7_Z_TB POS Transmitted to IEC CONTROL4;XCBR1 ST;DPCSO6;stVal;DPC 385; None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 5
Digital Inputs Board Slot K
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A K 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A K 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 0
Digital Outputs Board Slot E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A E 1 DC_SBO_Open_Close DPC 400kV B409-ICT-1 52 CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI9 CO;Pos;sboClass;DPC 100 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 3 DC_SBO_Open_Close DPC 400kV B409-ICT-1 52 CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI9 CO;Pos;sboClass;DPC 100 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 4 SC_DE_Reset_Set_1 SPC 400kV B409-ICT-1 PROTECTION CB CLOSE TO PUA Set XX_XX_CB CLS PUA Transmitted to IEC CONTROL2;GGIO1 CO;SPCSO2;ctlVal;DPC 239 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 5 SC_DE_Reset_Set_1 SPC 400kV B409-ICT-1 PROTECTION CB CLOSE TO PUB Set XX_XX_CB CLS PUB Transmitted to IEC CONTROL2;GGIO1 CO;SPCSO3;ctlVal;DPC 240 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A E 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 1
Digital Outputs Board Slot F
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A F 1 DC_SBO_Open_Close DPC 400kV B409-ICT-1 89A CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 101 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 2 DC_SBO_Open_Close DPC 400kV B409-ICT-1 89A CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 101 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 3 SC_DE_NotPerm_Perm SPC 400kV B409-ICT-1 IL PERMISSIVE 89A I/L PERMISSIVE XX_XX_89A Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO1;ctlVal;DPC 384 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 4 SC_DE_NotPerm_Perm SPC 400kV B409-ICT-1 IL PERMISSIVE 89AE I/L PERMISSIVE XX_XX_89AE Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO11;ctlVal;DPC 385 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 5 DC_SBO_Open_Close DPC 400kV B409-ICT-1 89B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI6 CO;Pos;sboClass;DPC 102 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 6 DC_SBO_Open_Close DPC 400kV B409-ICT-1 89B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI6 CO;Pos;sboClass;DPC 102 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 7 SC_DE_NotPerm_Perm SPC 400kV B409-ICT-1 IL PERMISSIVE 89B I/L PERMISSIVE XX_XX_89B Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO10;ctlVal;DPC 386 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 8 SC_DE_NotPerm_Perm SPC 400kV B409-ICT-1 IL PERMISSIVE 89BE I/L PERMISSIVE XX_XX_89BE Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO12;ctlVal;DPC 387 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A F 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 2
Digital Outputs Board Slot G
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A G 1 DC_SBO_Open_Close_1 DPC 400kV B409-ICT-1 89T-R CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI8 CO;Pos;sboClass;DPC 104 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 2 DC_SBO_Open_Close_1 DPC 400kV B409-ICT-1 89T-R CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI8 CO;Pos;sboClass;DPC 104 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 3 SC_DE_NotPerm_Perm SPC 400kV B409-ICT-1 IL PERMISSIVE 89T-R IL PERM XX_XX_89T-R Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO13;ctlVal;DPC 392 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 4 SC_DE_NotPerm_Perm SPC 400kV B409-ICT-1 IL PERMISSIVE 89TE-R IL PERM XX_XX_89TE-R Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO3;ctlVal;DPC 390 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 5 DC_SBO_Open_Close_1 DPC 400kV B409-ICT-1 89T-Y CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 108 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 6 DC_SBO_Open_Close_1 DPC 400kV B409-ICT-1 89T-Y CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 108 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 7 SC_DE_NotPerm_Perm SPC 400kV B409-ICT-1 IL PERMISSIVE 89T-Y IL PERM XX_XX_89T-Y Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO14;ctlVal;DPC 397 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 8 SC_DE_NotPerm_Perm SPC 400kV B409-ICT-1 IL PERMISSIVE 89TE-Y IL PERM XX_XX_89TE-Y Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO4;ctlVal;DPC 391 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 9 SC_DE_NotPerm_Perm_1 SPC 400kV B409-ICT-1 VT SELECTION 765KV AT CVT 7_AT_CVT_SEL Transmitted to IEC CONTROL2;GGIO4 CO;SPCSO7;ctlVal;DPC 409<; 408 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A G 10 SC_DE_NotPerm_Perm_1 SPC 400kV B409-ICT-1 VT SELECTION 765KV AT CVT 7_AT_CVT_DE-SEL Transmitted to IEC CONTROL2;GGIO4 CO;SPCSO8;ctlVal;DPC 409<; 409 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 3
Digital Outputs Board Slot H
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A H 1 DC_SBO_Open_Close_1 DPC 400kV B409-ICT-1 89T-B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI7 CO;Pos;sboClass;DPC 103 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 2 DC_SBO_Open_Close_1 DPC 400kV B409-ICT-1 89T-B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI7 CO;Pos;sboClass;DPC 103 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A H 3 SC_DE_NotPerm_Perm SPC 400kV B409-ICT-1 IL PERMISSIVE 89T-B IL PERM XX_XX_89T-B Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO9;ctlVal;DPC 388 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 4 SC_DE_NotPerm_Perm SPC 400kV B409-ICT-1 IL PERMISSIVE 89TE-B IL PERM XX_XX_89TE-B Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO2;ctlVal;DPC 389 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 5 SC_DE_Reset_Set_Int_2 SPC 400kV B409-ICT-1 VT SELECTION 400KV BUS-1 VT Set BUS-1_VT_SELECT Transmitted to IEC CONTROL2;GGIO4 CO;SPCSO2;ctlVal;DPC 409<; 410 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 6 SC_DE_Reset_Set_Int_2 SPC 400kV B409-ICT-1 VT SELECTION 400KV BUS-1 VT Set BUS-1_VT_DE-SEL Transmitted to IEC CONTROL2;GGIO4 CO;SPCSO1;ctlVal;DPC 409<; 409 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 7 SC_DE_Reset_Set_Int_2 SPC 400kV B409-ICT-1 VT SELECTION 400KV BUS-2 VT Set BUS-2_VT_SELECT Transmitted to IEC CONTROL2;GGIO4 CO;SPCSO4;ctlVal;DPC 409<; 412 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 8 SC_DE_Reset_Set_Int_2 SPC 400kV B409-ICT-1 VT SELECTION 400KV BUS-2 VT Set BUS-2_VT_DE-SEL Transmitted to IEC CONTROL2;GGIO4 CO;SPCSO3;ctlVal;DPC 409<; 411 NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 9 SC_DE_Reset_Set_Int_2 SPC 400kV B409-ICT-1 VT SELECTION 400KV LINE Set LINE_SELECT Transmitted to IEC CONTROL2;GGIO4 CO;SPCSO5;ctlVal;DPC 409<; 414 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A H 10 SC_DE_Reset_Set_Int_2 SPC 400kV B409-ICT-1 VT SELECTION 400KV LINE Set LINE_DE-SELECT Transmitted to IEC CONTROL2;GGIO4 CO;SPCSO6;ctlVal;DPC 409<; 413 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 4
Digital Outputs Board Slot I
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A I 1 DC_SBO_Open_Close_1 DPC 400kV B409-ICT-1 89TS-R CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 106 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 2 DC_SBO_Open_Close_1 DPC 400kV B409-ICT-1 89TS-R CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI4 CO;Pos;sboClass;DPC 106 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 3 SC_DE_NotPerm_Perm SPC 400kV B409-ICT-1 IL PERMISSIVE 89TS-R IL PERM XX_XX_89TS-R Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO5;ctlVal;DPC 394 NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 4 DC_SBO_Open_Close_1 DPC 400kV B409-ICT-1 89TS-Y CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI5 CO;Pos;sboClass;DPC 107 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 5 DC_SBO_Open_Close_1 DPC 400kV B409-ICT-1 89TS-Y CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI5 CO;Pos;sboClass;DPC 107 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 6 SC_DE_Reset_Reset_1 SPC 400kV B409-ICT-1 IL PERMISSIVE 89TS-Y IL PERM Reset XX_XX_89TS-Y Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO6;ctlVal;DPC 396 NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 7 DC_SBO_Open_Close_1 DPC 400kV B409-ICT-1 89TS-B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 105 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 8 DC_SBO_Open_Close_1 DPC 400kV B409-ICT-1 89TS-B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI3 CO;Pos;sboClass;DPC 105 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A I 9 SC_DE_NotPerm_Perm SPC 400kV B409-ICT-1 IL PERMISSIVE 89TS-B IL PERM XX_XX_89TS-B Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO8;ctlVal;DPC 393 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A I 10 SC_DE_NotPerm_Perm SPC 400kV B409-ICT-1 IL PERMISSIVE 89TS-RE IL PERM XX_XX_89TS-RE Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO7;ctlVal;DPC 395 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 5
Digital Outputs Board Slot J
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A J 1 SC_DE_Reset_Set_1 SPC 400kV B409-ICT-1 AT_SELECTION AT#1 SELECT Set XX_XX_AT#1 SELEC Transmitted to IEC CONTROL2;GGIO5 CO;SPCSO8;ctlVal;DPC 405 NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 2 SC_DE_Reset_Set_1 SPC 400kV B409-ICT-1 AT_SELECTION AT#1 DESELECT Set XX_XX_AT#1 DSELE Transmitted to IEC CONTROL2;GGIO5 CO;SPCSO7;ctlVal;DPC 404 NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 3 SC_DE_Reset_Set_1 SPC 400kV B409-ICT-1 AT_SELECTION AT#1 R PH SELECT Set XX_XX_AT#1 R SEL Transmitted to IEC CONTROL2;GGIO5 CO;SPCSO6;ctlVal;DPC 401 NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 4 SC_DE_Reset_Set_1 SPC 400kV B409-ICT-1 AT_SELECTION AT#1 R PH DESELECT Set XX_XX_AT#1 R DSE Transmitted to IEC CONTROL2;GGIO5 CO;SPCSO5;ctlVal;DPC 400 NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 5 SC_DE_Reset_Set_1 SPC 400kV B409-ICT-1 AT_SELECTION AT#1 Y PH SELECT Set XX_XX_AT#1 Y SEL Transmitted to IEC CONTROL2;GGIO5 CO;SPCSO4;ctlVal;DPC 403 NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 6 SC_DE_Reset_Set_1 SPC 400kV B409-ICT-1 AT_SELECTION AT#1 Y PH DESELECT Set XX_XX_AT#1 Y DSE Transmitted to IEC CONTROL2;GGIO5 CO;SPCSO3;ctlVal;DPC 402 NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 7 SC_DE_Reset_Set_1 SPC 400kV B409-ICT-1 AT_SELECTION AT#1 B PH SELECT Set XX_XX_AT#1 B SEL Transmitted to IEC CONTROL2;GGIO5 CO;SPCSO2;ctlVal;DPC 399 NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 8 SC_DE_Reset_Set_1 SPC 400kV B409-ICT-1 AT_SELECTION AT#1 B PH DESELECT Set XX_XX_AT#1 B DSE Transmitted to IEC CONTROL2;GGIO5 CO;SPCSO1;ctlVal;DPC 398 NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 9 SC_DE_Reset_Set SPC 400kV B409-ICT-1 CSD CSD BYPASS Set XX_XX_CSD BYPASS Transmitted to IEC CONTROL2;GGIO3 CO;SPCSO1;ctlVal;DPC 406 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A J 10 SC_DE_Reset_Set_1 SPC 400kV B409-ICT-1 PROTECTION CB TRIP COIL-2 Set XX_XX_TC2 Transmitted to IEC CONTROL2;GGIO1 CO;SPCSO1;ctlVal;DPC 213 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
ANALOG INPUT BOARD AIU21x
Analog Input Board Number 0
Analog Input Board Slot D
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE 6 ANALOG INPUT BOARD AIU21x
A 2 SPARE 6 ANALOG INPUT BOARD AIU21x
A 3 SPARE 6 ANALOG INPUT BOARD AIU21x
A 4 SPARE 6 ANALOG INPUT BOARD AIU21x
A 5 SPARE 6 ANALOG INPUT BOARD AIU21x
A 6 SPARE 6 ANALOG INPUT BOARD AIU21x
A 7 SPARE 6 ANALOG INPUT BOARD AIU21x
A 8 4/20 mA MV_hla_Temp ˚ Cel 400kV B409-ICT-1 PROTECTION AC KIOSK TEMP 0.0 100.0 AC KIOSK TEMP Transmitted to IEC CONTROL2;GGIO1 MX;AnIn1;mag;MV 6 ANALOG INPUT BOARD AIU21x
CT/VT ANALOG INPUT BOARD TMU2x0
CT/VT Board Number 0
CT/VT Board Slot Q
CT/VT Board Model TMU220
Nominal Current 1 (1A/5A)
Nominal Voltage 110.00 [1V … 500V]
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A DF MV_HLa_Frequency_1 Hz 400kV B409-ICT-1 SYNCH DATA FREQUENCY DIFFERENCE 0.0 2.0 FREQUENCY DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifHzClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DV MV_hla_ AuxVoltage_1 V 400kV B409-ICT-1 SYNCH DATA VOLTAGE DIFFERENCE 0.0 277.13626 VOLTAGE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifVClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Dj MV_hla_PhaseDiff ˚ 400kV B409-ICT-1 SYNCH DATA PHASE DIFFERENCE 0.0 360.0 PHASE ANGLE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifAngClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ia MV_HLa_AuxCurrent A 400kV B409-ICT-1 METERING I-R PHASE CURRENT 0.0 3600.0 IR PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ib MV_HLa_AuxCurrent_1 A 400kV B409-ICT-1 METERING I-Y PHASE CURRENT 0.0 3600.0 IY PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ic MV_HLa_AuxCurrent A 400kV B409-ICT-1 METERING I-B PHASE CURRENT 0.0 3600.0 IB PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsC;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vb MV_hla_ AuxVoltage_1 V 400kV B409-ICT-1 SYNCH DATA INCOMING SUPPLY 0.0 277.13626 INCOMING SUPPLY Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;PhV;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uab MV_hla_ AuxVoltage V 400kV B409-ICT-1 METERING R-Y VOLTAGE 0.0 480.0 R-Y VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsAB;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ubc MV_HLa_Voltage kV 400kV B409-ICT-1 METERING Y-B VOLTAGE 0.0 480.0 Y-B VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsBC;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uca MV_HLa_Voltage kV 400kV B409-ICT-1 METERING B-R VOLTAGE 0.0 480.0 B-R VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsCA;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar MV_hla_ AuxVoltage_1 V 400kV B409-ICT-1 SYNCH DATA RUNNING SUPPLY 0.0 277.13626 RUNNING SPLY-1 Transmitted to IEC MEASUREMENT1;barMMXU1 MX;PhV;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Freq (Line) MV_HLa_Frequency Hz 400kV B409-ICT-1 METERING FREQUENCY 45.0 55.0 FREQUENCY Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;Hz;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A P total (MW) MV_HLa_ActPower MW 400kV B409-ICT-1 METERING ACTIVE POWER -1662.72 1662.72 ACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotW;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Q total (Mvar) MV_HLa_ActPower MW 400kV B409-ICT-1 METERING REACTIVE POWER -1662.72 1662.72 REACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotVAr;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A cos ft : Power factor MV_HLa_PowerFactor 400kV B409-ICT-1 METERING POWER FACTOR -1.2 1.2 POWER FACTOR Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotPF;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 52 | OE_CL_CONTROL OPEN ORDER Set Reset RS_ST_OPN ORD Transmitted to IEC CONTROL1;CSWI9 ST;OpnOrd;general;general;ACT 401; None 213 CB OpenOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89A | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL3;CILO4 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89T-B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL3;CILO5 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89T-R | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL3;CILO6 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89TS-B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL3;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89TS-R | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL3;CILO2 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89TS-Y | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL3;CILO3 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89T-Y | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive OPEN INTERLOCK Transmitted to IEC CONTROL2;CILO2 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPS_hla_Set_Reset SPS 400kV B409-ICT-1 ORDER RUNNING ON THE BAY Set Reset RS_ST_ORD RUNING Transmitted to IEC CONTROL1;GBAY1 ST;OrdRun;stVal;SPS None OrderInProgress 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 52 | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLOSE ILK Transmitted to IEC CONTROL4;CILO1 ST;EnaCls;stVal;SPS None CB CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89A | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL3;CILO4 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89T-B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL3;CILO5 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89T-R | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL3;CILO6 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89TS-B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL3;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 17 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89TS-R | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL3;CILO2 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 18 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89TS-Y | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL3;CILO3 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 19 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89T-Y | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive CLOSE INTERLOCK Transmitted to IEC CONTROL2;CILO2 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 20 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 SYNCH FUNCTION CLOSE ORDER Set Reset RS_ST_CLS ODR Transmitted to IEC CONTROL1;RSYN1 ST;ClsOpSt;stVal;SPS None IntManualCSFct CS_CloseOrderState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 21 SPE_HLA_on_off SPS 400kV B409-ICT-1 SYNCH FUNCTION ON/OFF SECONDARY SPS Off On RS_ST_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 ST;EnaSec;origin;SPC None 201 IntManualCSFct CS_OnOff_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 22 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 SYNCH FUNCTION POSSIBLE CLOSING Set Reset RS_ST_POS CLS Transmitted to IEC CONTROL1;RSYN1 ST;Rel;stVal;SPS 405; None IntManualCSFct CS_AuthoState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 23 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 SYNCH FUNCTION PRESENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF U PRES Transmitted to IEC CONTROL1;RSYN1 ST;VRefInd;stVal;SPS 405; None IntManualCSFct CS_VoltageRefPresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 24 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 SYNCH FUNCTION ABSENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF. U ABS Transmitted to IEC CONTROL1;RSYN1 ST;VRefAbs;stVal;SPS 405; None IntManualCSFct CS_VoltageRefAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 25 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 SYNCH FUNCTION VOLT ABSENCE Set Reset RS_ST_VOLT ABS Transmitted to IEC CONTROL1;RSYN1 ST;VAbs;stVal;SPS 405; None IntManualCSFct CS_VoltageAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 26 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 SYNCH FUNCTION VOLT PRESENCE Set Reset RS_ST_VOLT PRES Transmitted to IEC CONTROL1;RSYN1 ST;VP;stVal;SPS 405; None IntManualCSFct CS_VoltagePresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 27 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 52 | OE_CL_CONTROL CLOSE ORDER Permissive Not Permissive RS_ST_CLS ORD Transmitted to IEC CONTROL1;CSWI9 ST;ClsOrd;general;general;ACT 404; None 239;240 CB CloseOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 28 SPE_HLA_Normal_Alarm SPS 400kV B409-ICT-1 52 LOSS OF SF6 GAS POLE A/B/C Alarm Normal NL_AL_LOSS SF6 Transmitted to IEC CONTROL1;CSWI9 ST;IndSys2;stVal;SPS 403<; None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 29 SPE_HLA_Normal_Alarm SPS 400kV B409-ICT-1 52 SPRING CHARGE STATUS Alarm Normal NL_AL_SPING ST 2 Transmitted to IEC CONTROL1;CSWI9 ST;IndSys1;stVal;SPS None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 30 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89A IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI1 ST;IndSys1;stVal;SPS 367<; None 384 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 31 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89AE IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL3;CSWI6 ST;IndSys1;stVal;SPS 370<; None 385 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 32 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89B IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI6 ST;IndSys1;stVal;SPS 371<; None 386 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 33 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89BE IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL3;CSWI4 ST;IndSys1;stVal;SPS 374<; None 387 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 34 SPE_HLA_Reset_Optd SPS 400kV B409-ICT-1 89T POS_CLOSE_FBD Operated Reset RS_CL_POS Transmitted to IEC CONTROL2;GAPC1 ST;IndSys2;stVal;SPS 375<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 35 SPE_HLA_Reset_Optd SPS 400kV B409-ICT-1 89T POS_OPEN_FBD Operated Reset RS_OE_POS Transmitted to IEC CONTROL2;GAPC1 ST;IndSys1;stVal;SPS 375<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 36 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89T-B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI7 ST;IndSys1;stVal;SPS 376<; None 388 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 37 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89TE-B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL2;CSWI1 ST;IndSys1;stVal;SPS 385<; None 389 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 38 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89TE-R INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL3;CSWI1 ST;IndSys1;stVal;SPS 386<; None 390 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 39 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89TE-Y INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL3;CSWI2 ST;IndSys1;stVal;SPS 387<; None 391 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 40 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89T-R INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI8 ST;IndSys1;stVal;SPS 379<; None 392 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 41 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89TS-B INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI3 ST;IndSys1;stVal;SPS 388<; None 393 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 42 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89TS-R INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI4 ST;IndSys1;stVal;SPS 391<; None 394 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 43 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89TS-RE INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL3;CSWI3 ST;IndSys1;stVal;SPS 394<; None 395 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 44 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89TS-Y INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI5 ST;IndSys1;stVal;SPS 395<; None 396 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 45 SPE_HLa_Notper_Perm SPS 400kV B409-ICT-1 89T-Y INTERLOCK Permissive Not Permissive NP_PE_I/L Transmitted to IEC CONTROL1;CSWI2 ST;IndSys1;stVal;SPS 382<; None 397 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 46 SPE_HLa_Dselect_Select SPS 400kV B409-ICT-1 AT_SELECTION AT B-PH Selected Deselected T_B-PH_DE-SEL Transmitted to IEC CONTROL2;GAPC7 ST;IndSys3;stVal;SPS 398;398<; None 398 1 C264 SELF GENERATED DIGITAL INFORMATION
A 47 SPE_HLa_Reset_Select SPS 400kV B409-ICT-1 AT_SELECTION AT B-PH Selected Reset T_B-PH_SEL Transmitted to IEC CONTROL2;GAPC7 ST;IndSys4;stVal;SPS 398;398<; None 399 1 C264 SELF GENERATED DIGITAL INFORMATION
A 48 SPE_HLa_Dselect_Select SPS 400kV B409-ICT-1 AT_SELECTION AT R-PH Selected Deselected T_R-PH_DE-SEL Transmitted to IEC CONTROL2;GAPC7 ST;IndSys5;stVal;SPS 398;398<; None 400 1 C264 SELF GENERATED DIGITAL INFORMATION
A 49 SPE_HLa_Reset_Select SPS 400kV B409-ICT-1 AT_SELECTION AT R-PH Selected Reset T_R-PH_SEL Transmitted to IEC CONTROL2;GAPC7 ST;IndSys6;stVal;SPS 398;398<; None 401 1 C264 SELF GENERATED DIGITAL INFORMATION
A 50 SPE_HLa_Reset_Select SPS 400kV B409-ICT-1 AT_SELECTION AT Y-PH Selected Reset T_Y-PH_DE-SEL Transmitted to IEC CONTROL2;GAPC7 ST;IndSys7;stVal;SPS 398;398<; None 402 1 C264 SELF GENERATED DIGITAL INFORMATION
A 51 SPE_HLa_Reset_Select SPS 400kV B409-ICT-1 AT_SELECTION AT Y-PH Selected Reset T_Y-PH_SEL Transmitted to IEC CONTROL2;GAPC7 ST;IndSys8;stVal;SPS 398;398<; None 403 1 C264 SELF GENERATED DIGITAL INFORMATION
A 52 SPE_HLa_Dselect_Select SPS 400kV B409-ICT-1 AT_SELECTION AT-1 Selected Deselected T-1_DE-SELECT Transmitted to IEC CONTROL2;GAPC7 ST;IndSys2;stVal;SPS 398<; None 404 1 C264 SELF GENERATED DIGITAL INFORMATION
A 53 SPE_HLa_Reset_Select SPS 400kV B409-ICT-1 AT_SELECTION AT-1 Selected Reset T-1_SELECT Transmitted to IEC CONTROL2;GAPC7 ST;IndSys1;stVal;SPS 398<; None 405 1 C264 SELF GENERATED DIGITAL INFORMATION
A 54 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 CSD CSD BYPASS Set Reset RS_ST_CSD BYPASS Transmitted to IEC CONTROL2;GAPC4 ST;IndSys1;stVal;SPS 400<; None 406 1 C264 SELF GENERATED DIGITAL INFORMATION
A 55 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 INTER TRIPPING HV ICT CB OPEN ORDER-1 Set Reset RS_ST_HV ICT CB1 Transmitted to IEC CONTROL2;GAPC5 ST;IndSys1;stVal;SPS 401<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 56 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 INTER TRIPPING HV ICT CB OPEN ORDER-2 Set Reset RS_ST_HV ICT CB2 Transmitted to IEC CONTROL2;GAPC5 ST;IndSys2;stVal;SPS 401<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 57 SPE_HLA_Reset_Optd SPS 400kV B409-ICT-1 PROTECTION 86A TRIP RELAY Operated Reset RS_OP_86A Transmitted to IEC CONTROL2;GAPC3 ST;IndSys3;stVal;SPS 351;366;402<; None Yes 1 C264 SELF GENERATED DIGITAL INFORMATION
A 58 SPE_HLA_Reset_Optd SPS 400kV B409-ICT-1 PROTECTION 86A1 TRIP RELAY Operated Reset RS_OP_86A1 Transmitted to IEC CONTROL2;GAPC3 ST;IndSys5;stVal;SPS 402; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 59 SPE_HLA_Reset_Optd SPS 400kV B409-ICT-1 PROTECTION 86A2 TRIP RELAY Operated Reset RS_OP_86A2 Transmitted to IEC CONTROL2;GAPC3 ST;IndSys6;stVal;SPS 402; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 60 SPE_HLA_Reset_Optd SPS 400kV B409-ICT-1 PROTECTION 86B TRIP RELAY Operated Reset RS_OP_86B Transmitted to IEC CONTROL2;GAPC3 ST;IndSys4;stVal;SPS 351;366;402<; None Yes 1 C264 SELF GENERATED DIGITAL INFORMATION
A 61 SPE_HLA_Reset_Optd SPS 400kV B409-ICT-1 PROTECTION 86B1 TRIP RELAY Operated Reset RS_OP_86B1 Transmitted to IEC CONTROL2;GAPC3 ST;IndSys7;stVal;SPS 402; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 62 SPE_HLA_Reset_Optd SPS 400kV B409-ICT-1 PROTECTION 86B2 TRIP RELAY Operated Reset RS_OP_86B2 Transmitted to IEC CONTROL2;GAPC3 ST;IndSys8;stVal;SPS 402; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 63 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 PROTECTION SOTF TO RELAY Set Reset RS_ST_SOTF TO RL Transmitted to IEC CONTROL2;GAPC3 ST;IndSys1;stVal;SPS 404<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 64 SPE_HLA_Unhlthy_Hlthy SPS 400kV B409-ICT-1 PROTECTION 33KV 50/59N RELAY Healthy Unhealthy UH_HL_33KV50/59N Transmitted to IEC CONTROL2;GAPC3 ST;IndSys2;stVal;SPS None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 65 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 SYNCH DATA CLOSE PERMISSIVE Set Reset RS_ST_CB CLOSE Transmitted to IEC CONTROL2;GAPC2 ST;IndSys5;stVal;SPS 405<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 66 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 SYNCH DATA DEAD INCOMING DEAD RUNNING Set Reset RS_ST_DINC_DRUN Transmitted to IEC CONTROL2;GAPC2 ST;IndSys4;stVal;SPS 405<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 67 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 SYNCH DATA DEAD INCOMING LIVE RUNNING Set Reset RS_ST_DINC_LRUN Transmitted to IEC CONTROL2;GAPC2 ST;IndSys3;stVal;SPS 405<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 68 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 SYNCH DATA LIVE INCOMING DEAD RUNNING Set Reset RS_ST_LINC_DRUN Transmitted to IEC CONTROL2;GAPC2 ST;IndSys2;stVal;SPS 405<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 69 SPE_HLa_Reset_Set SPS 400kV B409-ICT-1 SYNCH DATA LIVE INCOMING LIVE RUNNING Set Reset RS_ST_LINC_LRUN Transmitted to IEC CONTROL2;GAPC2 ST;IndSys1;stVal;SPS 405<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 70 SPE_HLa_Reset_DSelect SPS 400kV B409-ICT-1 VT SELECTION 765KV AT CVT Deselected Reset 7_AT_CVT_DE-SEL Transmitted to IEC CONTROL2;GAPC6 ST;IndSys8;stVal;SPS 409<; None 409 1 C264 SELF GENERATED DIGITAL INFORMATION
A 71 SPE_HLa_Reset_Select SPS 400kV B409-ICT-1 VT SELECTION 765KV AT CVT Selected Reset 7_AT_CVT_SEL Transmitted to IEC CONTROL2;GAPC6 ST;IndSys7;stVal;SPS 409<; None 408 1 C264 SELF GENERATED DIGITAL INFORMATION
A 72 SPE_HLa_Reset_DSelect SPS 400kV B409-ICT-1 VT SELECTION 765KV BUS-1 VT Deselected Reset BUS-1_VT_DE-SEL Transmitted to IEC CONTROL2;GAPC6 ST;IndSys1;stVal;SPS 409<; None 409 1 C264 SELF GENERATED DIGITAL INFORMATION
A 73 SPE_HLa_Reset_Select SPS 400kV B409-ICT-1 VT SELECTION 765KV BUS-1 VT Selected Reset BUS-1_VT_SELECT Transmitted to IEC CONTROL2;GAPC6 ST;IndSys2;stVal;SPS 409<; None 410 1 C264 SELF GENERATED DIGITAL INFORMATION
A 74 SPE_HLa_Reset_Select SPS 400kV B409-ICT-1 VT SELECTION 765KV BUS-2 VT Selected Reset BUS-2_VT_DE-SEL Transmitted to IEC CONTROL2;GAPC6 ST;IndSys3;stVal;SPS 409<; None 411 1 C264 SELF GENERATED DIGITAL INFORMATION
A 75 SPE_HLa_Reset_Select SPS 400kV B409-ICT-1 VT SELECTION 765KV BUS-2 VT Selected Reset BUS-2_VT_SELECT Transmitted to IEC CONTROL2;GAPC6 ST;IndSys4;stVal;SPS 409<; None 412 1 C264 SELF GENERATED DIGITAL INFORMATION
A 76 SPE_HLa_Reset_Select SPS 400kV B409-ICT-1 VT SELECTION LINE Selected Reset LINE_DE-SELECT Transmitted to IEC CONTROL2;GAPC6 ST;IndSys6;stVal;SPS 409<; None 413 1 C264 SELF GENERATED DIGITAL INFORMATION
A 77 SPE_HLa_Reset_Select SPS 400kV B409-ICT-1 VT SELECTION LINE Selected Reset LINE_SELECT Transmitted to IEC CONTROL2;GAPC6 ST;IndSys5;stVal;SPS 409<; None 414 1 C264 SELF GENERATED DIGITAL INFORMATION
A 78 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 7_Z_TE Y POS Open 7_Z_TE Y POS Transmitted to IEC CONTROL1;CSWI9 ST;DPCSO1;stVal;DPC 382;383;384; None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 79 DP_HLA_CBOpen_Close DPS 400kV B409-ICT-1 52 7_Z_TE Y POS Closed 7_Z_TE Y POS Transmitted to IEC CONTROL1;CSWI9 ST;DPCSO1;stVal;DPC 382;383;384; None CB 1 C264 SELF GENERATED DIGITAL INFORMATION
A 80 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 52 POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI9 ST;Pos;stVal;DPC 350;365;366;367;368;369;371;372;373;376;377;378;379;380;381;382;383;384;388;389;390;391;392;393;395;396;397;409; None 100 399 Yes CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 81 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 52 POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI9 ST;Pos;stVal;DPC 350;365;366;367;368;369;371;372;373;376;377;378;379;380;381;382;383;384;388;389;390;391;392;393;395;396;397;409; None 100 399 Yes CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 82 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89A COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 83 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89A COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 84 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89AE COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL3;CSWI6 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 85 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89AE COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL3;CSWI6 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 86 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89B COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI6 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 87 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89B COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI6 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 88 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89BE COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL3;CSWI4 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 89 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89BE COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL3;CSWI4 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 90 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89T POSITION Open OE_CL_POS Transmitted to IEC CONTROL2;GAPC1 ST;DPCSO1;stVal;DPC 365; None Yes 1 C264 SELF GENERATED DIGITAL INFORMATION
A 91 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89T POSITION Closed OE_CL_POS Transmitted to IEC CONTROL2;GAPC1 ST;DPCSO1;stVal;DPC 365; None Yes 1 C264 SELF GENERATED DIGITAL INFORMATION
A 92 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89T-B Computed switchgear position Open OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI7 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 93 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89T-B Computed switchgear position Closed OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI7 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 94 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL3;CSWI5 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 95 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL3;CSWI5 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 96 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE POSITION Open OE_CL_POS Transmitted to IEC CONTROL3;XSWI5 ST;Pos;stVal;DPC None SG SwitchPos 1 C264 SELF GENERATED DIGITAL INFORMATION
A 97 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE POSITION Closed OE_CL_POS Transmitted to IEC CONTROL3;XSWI5 ST;Pos;stVal;DPC None SG SwitchPos 1 C264 SELF GENERATED DIGITAL INFORMATION
A 98 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE-B Computed switchgear position Open OP_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 99 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE-B Computed switchgear position Closed OP_CL_COMP_POS Transmitted to IEC CONTROL2;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 0 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE-R Computed switchgear position Open OP_CL_COMP_POS Transmitted to IEC CONTROL3;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 101 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE-R Computed switchgear position Closed OP_CL_COMP_POS Transmitted to IEC CONTROL3;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 0 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE-Y Computed switchgear position Open OP_CL_COMP_POS Transmitted to IEC CONTROL3;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 101 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TE-Y Computed switchgear position Closed OP_CL_COMP_POS Transmitted to IEC CONTROL3;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 102 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89T-R Computed switchgear position Open OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI8 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 103 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89T-R Computed switchgear position Closed OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI8 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 104 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89TS-B Computed switchgear position Open OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 105 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89TS-B Computed switchgear position Closed OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 106 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89TS-R Computed switchgear position Open OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 107 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89TS-R Computed switchgear position Closed OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI4 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 108 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TS-RE Computed switchgear position Open OP_CL_COMP_POS Transmitted to IEC CONTROL3;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 109 DP_HLa_ESOpen_Close DPS 400kV B409-ICT-1 89TS-RE Computed switchgear position Closed OP_CL_COMP_POS Transmitted to IEC CONTROL3;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 110 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89TS-Y Computed switchgear position Open OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI5 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 111 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89TS-Y Computed switchgear position Closed OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI5 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 112 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89T-Y Computed switchgear position Open OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 113 DP_HLA_ ISOOpen_Close DPS 400kV B409-ICT-1 89T-Y Computed switchgear position Closed OP_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 114 DP_HLa_LocRem_Bay DPS 400kV B409-ICT-1 BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 109 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 115 DP_HLa_LocRem_Bay DPS 400kV B409-ICT-1 BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 109 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 116 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SC_DE_Reset_Set SPC 400kV B409-ICT-1 CSD CSD OUT FROM HMI Set XX_ST_CSD OUT H Transmitted to IEC CONTROL2;GAPC4 CO;SPCSO1;ctlVal;DPC 400; 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SC_DE_Reset_Set_1 SPC 400kV B409-ICT-1 PROTECTION 86A TRIP RELAY Set XX_RS_86A Transmitted to IEC CONTROL2;GAPC3 CO;SPCSO1;ctlVal;DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SC_DE_Reset_Set_1 SPC 400kV B409-ICT-1 PROTECTION 86B TRIP RELAY Set XX_RS_86B Transmitted to IEC CONTROL2;GAPC3 CO;SPCSO2;ctlVal;DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SC_DE_Off_On SPC 400kV B409-ICT-1 SYNCH FUNCTION ON/OFF SECONDARY CONTROL SPC On Off OF_ON_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 CO;EnaSec;ctlVal;DPC 201 IntManualCSFct CS_CtrlOnOff_SPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 DC_DE_LocRem_BayCtrl DPC 400kV B409-ICT-1 BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 109 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 DC_DE_LocRem_BayCtrl DPC 400kV B409-ICT-1 BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 109 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 MV_HLa_Unused 400kV B409-ICT-1 CB_COUNTER Count_Close 0.0 10000.0 Count_Close Transmitted to IEC CONTROL4;GAPC1 MX;AnIn2;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 MV_HLa_Unused 400kV B409-ICT-1 CB_COUNTER Count_Open 0.0 10000.0 Count_Open Transmitted to IEC CONTROL4;GAPC1 MX;AnIn1;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF! CCCC
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
MiCOM C264 DESCRIPTION
Computer Name B412_BR GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) C264 Read Only
Gateway Port used (on gateway)
SCADA 1 400KV SERVER M 1
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 0
Digital Inputs Board Slot P
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A P 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A P 7 SPE_HLA_Normal_Alarm SPS 400kV B412-BR 52 GEN SF6 LOCKOUT Alarm Normal RS_OP_SF6 L/O Transmitted to IEC CONTROL1;XCBR1 ST;Ind7;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 8 SPE_HLA_Normal_Alarm SPS 400kV B412-BR 52 POLE DISCREPANCY Alarm Normal RS_OP_POLE DISC Transmitted to IEC CONTROL1;XCBR1 ST;Ind8;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 9 SPE_HLA_Normal_Alarm SPS 400kV B412-BR 52 LOSS OF SF6 GAS POLE A/B/C-1 Alarm Normal NL_AL_LOSS SF6-1 Transmitted to IEC CONTROL1;XCBR1 ST;Ind9;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 10 SPE_HLA_Normal_Alarm SPS 400kV B412-BR 52 LOSS OF SF6-2 Alarm Normal LOSS OF SF6-2 Transmitted to IEC CONTROL1;XCBR1 ST;Ind10;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 11 SPE_HLA_Normal_Alarm SPS 400kV B412-BR 52 SF6 LO PRESSURE LOCKOUT Alarm Normal NO_LO_SF6 LO LOW Transmitted to IEC CONTROL1;XCBR1 ST;Ind11;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 12 SPE_HLA_Normal_Alarm SPS 400kV B412-BR 52 POLE DISCREPANCY Alarm Normal NL_AL_POLE DIS Transmitted to IEC CONTROL1;XCBR1 ST;Ind12;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 13 SPE_HLA_Normal_Alarm SPS 400kV B412-BR 52 DC SUPPLY-1\2 Alarm Normal NL_FL_DC SUP12 Transmitted to IEC CONTROL1;XCBR1 ST;Ind13;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 14 SPE_HLA_Normal_Alarm SPS 400kV B412-BR 52 REMOTE POS Alarm Normal RS_ST_REMOTE Transmitted to IEC CONTROL1;XCBR1 ST;Ind14;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 15 SPE_HLA_Normal_Alarm SPS 400kV B412-BR 52 SPRING CHARGE STATUS B Alarm Normal DS_CH_SPING ST A Transmitted to IEC CONTROL1;XCBR1 ST;Ind1;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A P 16 SPE_HLA_Normal_Alarm SPS 400kV B412-BR 52 SPRING CHARGE STATUS A Alarm Normal DS_CH_SPING ST B Transmitted to IEC CONTROL1;XCBR1 ST;Ind2;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 1
Digital Inputs Board Slot O
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A O 1 SPE_HLA_Normal_Alarm SPS 400kV B412-BR 52 SPRING CHARGE STATUS C Alarm Normal DS_CH_SPING ST C Transmitted to IEC CONTROL1;XCBR1 ST;Ind4;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 2 SPE_HLA_Normal_Alarm SPS 400kV B412-BR 52 CB TROUBLE-4 Alarm Normal NL_AL_CB TROUBL4 Transmitted to IEC CONTROL1;XCBR1 ST;Ind3;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 3 SPE_HLA_Normal_Alarm SPS 400kV B412-BR 52 CB TROUBLE-5 Alarm Normal NL_AL_CB TROUBL5 Transmitted to IEC CONTROL1;XCBR1 ST;Ind6;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 4 SPE_HLA_Normal_Alarm SPS 400kV B412-BR 52 CB TROUBLE-4 Alarm Normal CB TROUBLE-4 Transmitted to IEC CONTROL1;XCBR1 ST;Ind5;stVal;SPS None CB 1 DIGITAL INPUT BOARD DIU2xx
A O 5 DP_HLA_ ISOOpen_Close DPS 400kV B412-BR 89A POSITION Open OE_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 446;450;451; None 120 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 6 DP_HLA_ ISOOpen_Close DPS 400kV B412-BR 89A POSITION Closed OE_CL_POS Transmitted to IEC CONTROL1;XSWI1 ST;Pos;stVal;DPC 446;450;451; None 120 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 7 DP_HLa_ESOpen_Close DPS 400kV B412-BR 89AE POSITION Open OE_CL_POS Transmitted to IEC CONTROL2;XSWI5 ST;Pos;stVal;DPC 443;444;445;447;448;449; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 8 DP_HLa_ESOpen_Close DPS 400kV B412-BR 89AE POSITION Closed OE_CL_POS Transmitted to IEC CONTROL2;XSWI5 ST;Pos;stVal;DPC 443;444;445;447;448;449; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 9 DP_HLA_ ISOOpen_Close DPS 400kV B412-BR 89B POSITION Open OE_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 446;450; None 121 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 10 DP_HLA_ ISOOpen_Close DPS 400kV B412-BR 89B POSITION Closed OE_CL_POS Transmitted to IEC CONTROL2;XSWI1 ST;Pos;stVal;DPC 446;450; None 121 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 11 DP_HLa_ESOpen_Close DPS 400kV B412-BR 89BE POSITION Open OE_CL_POS Transmitted to IEC CONTROL2;XSWI3 ST;Pos;stVal;DPC 443;444;445;447;448;449; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 12 DP_HLa_ESOpen_Close DPS 400kV B412-BR 89BE POSITION Closed OE_CL_POS Transmitted to IEC CONTROL2;XSWI3 ST;Pos;stVal;DPC 443;444;445;447;448;449; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 13 DP_HLA_ ISOOpen_Close DPS 400kV B412-BR 89R POSITION Open OE_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 454; None 122 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 14 DP_HLA_ ISOOpen_Close DPS 400kV B412-BR 89R POSITION Closed OE_CL_POS Transmitted to IEC CONTROL2;XSWI2 ST;Pos;stVal;DPC 454; None 122 SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 15 DP_HLa_ESOpen_Close DPS 400kV B412-BR 89RE POSITION Open OE_CL_POS Transmitted to IEC CONTROL2;XSWI6 ST;Pos;stVal;DPC 451;452;453; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
A O 16 DP_HLa_ESOpen_Close DPS 400kV B412-BR 89RE POSITION Closed OE_CL_POS Transmitted to IEC CONTROL2;XSWI6 ST;Pos;stVal;DPC 451;452;453; None SG SwitchPos 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 2
Digital Inputs Board Slot N
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A N 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N -7 SPE_HLA_Normal_Fail SPS 400kV B412-BR PROTECTION DC SOURCE-1 Fail Normal NL_FL_DC SOURCE1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind4;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N -8 SPE_HLA_Normal_Fail SPS 400kV B412-BR PROTECTION DC SOURCE-2 Fail Normal NL_FL_DC SOURCE2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N -9 SPE_HLA_Healthy_Flty SPS 400kV B412-BR PROTECTION CB TRIP COIL-2 Faulty Healthy HL_FT_CB TC1 Transmitted to IEC CONTROL1;GGIO1 ST;Ind2;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N -10 SPE_HLA_Healthy_Flty SPS 400kV B412-BR PROTECTION CB TRIP COIL-2 Faulty Healthy HL_FT_CB TC2 Transmitted to IEC CONTROL1;GGIO1 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 11 DP_HLA_Trip_Closed DPS 400kV B412-BR 52 EMERGENCY/MANUAL Closed TP_CL_EMRG/MAN Transmitted to IEC CONTROL1;XCBR1 ST;DPCSO1;stVal;DPC 457; None CB 1 DIGITAL INPUT BOARD DIU2xx
A N 12 DP_HLA_Trip_Closed DPS 400kV B412-BR 52 EMERGENCY/MANUAL Trip TP_CL_EMRG/MAN Transmitted to IEC CONTROL1;XCBR1 ST;DPCSO1;stVal;DPC 457; None CB 1 DIGITAL INPUT BOARD DIU2xx
A N 13 SPE_HLA_Normal_Alarm SPS 400kV B412-BR CSD CSD DEVICE NOT READY Alarm Normal NL_AL_CSD NR Transmitted to IEC CONTROL1;GGIO2 ST;Ind2;stVal;SPS 456; None 1 DIGITAL INPUT BOARD DIU2xx
A N 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A N 15 SPE_HLA_Normal_Alarm SPS 400kV B412-BR CSD CSD Alarm Normal NL_AL_CSD Transmitted to IEC CONTROL1;GGIO2 ST;Ind3;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
A N 16 SPE_HLa_In_Out SPS 400kV B412-BR CSD CSD In Out IN_OT_CSD Transmitted to IEC CONTROL1;GGIO2 ST;Ind1;stVal;SPS None 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 3
Digital Inputs Board Slot M
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A M 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A M 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number 4
Digital Inputs Board Slot L
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A L 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A L 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 0
Digital Outputs Board Slot E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A E 1 DC_SBO_Open_Close DPC 400kV B412-BR 52 CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI8 CO;Pos;sboClass;DPC 119 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 6 SC_DE_Reset_Set SPC 400kV B412-BR CSD CSD BYPASS Set XX_XX_CSD BYPASS Transmitted to IEC CONTROL1;GGIO2 CO;SPCSO1;ctlVal;DPC 513 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 7 DC_SBO_Open_Close DPC 400kV B412-BR 52 CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI8 CO;Pos;sboClass;DPC 119 NO CB Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A E 8 SC_DE_Reset_Set_1 SPC 400kV B412-BR PROTECTION CB CLOSE TO PUA Set XX_XX_CB CLS PUA Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO4;ctlVal;DPC 244 NO 2 DIGITAL OUTPUT BOARD DOU20x
A E 9 SC_DE_Reset_Set_1 SPC 400kV B412-BR PROTECTION CB CLOSE TO PUB Set XX_XX_CB CLS PUB Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO5;ctlVal;DPC 243 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A E 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 1
Digital Outputs Board Slot F
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A F 1 DC_SBO_Open_Close DPC 400kV B412-BR 89B CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 121 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 2 DC_SBO_Open_Close DPC 400kV B412-BR 89B CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI2 CO;Pos;sboClass;DPC 121 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 3 SC_DE_NotPerm_Perm SPC 400kV B412-BR IL PERMISSIVE 89B I/L PERMISSIVE XX_XX_89B Transmitted to IEC CONTROL2;GGIO1 CO;SPCSO2;ctlVal;DPC 509 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 4 SC_DE_NotPerm_Perm SPC 400kV B412-BR IL PERMISSIVE 89BE I/L PERMISSIVE XX_XX_89BE Transmitted to IEC CONTROL2;GGIO1 CO;SPCSO4;ctlVal;DPC 510 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 5 DC_SBO_Open_Close DPC 400kV B412-BR 89A CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 120 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 6 DC_SBO_Open_Close DPC 400kV B412-BR 89A CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI1 CO;Pos;sboClass;DPC 120 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A F 7 SC_DE_NotPerm_Perm SPC 400kV B412-BR IL PERMISSIVE 89A I/L PERMISSIVE XX_XX_89A Transmitted to IEC CONTROL2;GGIO1 CO;SPCSO1;ctlVal;DPC 507 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 8 SC_DE_NotPerm_Perm SPC 400kV B412-BR IL PERMISSIVE 89AE I/L PERMISSIVE XX_XX_89AE Transmitted to IEC CONTROL2;GGIO1 CO;SPCSO7;ctlVal;DPC 508 NO 2 DIGITAL OUTPUT BOARD DOU20x
A F 9 SC_DE_NotPerm_Perm SPC 400kV B412-BR IL PERMISSIVE 89AE1 I/L PERMISSIVE XX_XX_89AE1 Transmitted to IEC CONTROL2;GGIO1 CO;SPCSO6;ctlVal;DPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A F 10 SC_DE_Reset_Set_1 SPC 400kV B412-BR PROTECTION TO CB TC-2 CKT Set XX_XX_TC2 Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO2;ctlVal;DPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 2
Digital Outputs Board Slot G
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A G 1 DC_SBO_Open_Close_2 DPC 400kV B412-BR 89R CONTROL Open OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI6 CO;Pos;sboClass;DPC 122 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 2 DC_SBO_Open_Close_2 DPC 400kV B412-BR 89R CONTROL Close OE_CL_CONTROL Transmitted to IEC CONTROL1;CSWI6 CO;Pos;sboClass;DPC 122 NO SG Switch_DPC 2 DIGITAL OUTPUT BOARD DOU20x
A G 3 SC_DE_NotPerm_Perm SPC 400kV B412-BR IL PERMISSIVE 89BR I/L PERMISSIVE XX_XX_89BR Transmitted to IEC CONTROL2;GGIO1 CO;SPCSO3;ctlVal;DPC 511 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 4 SC_DE_NotPerm_Perm SPC 400kV B412-BR IL PERMISSIVE 89BRE I/L PERMISSIVE XX_XX_89BRE Transmitted to IEC CONTROL2;GGIO1 CO;SPCSO5;ctlVal;DPC 512 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 5 SC_DE_Reset_Set_1 SPC 400kV B412-BR PROTECTION 86A TRIP RELAY Set XX_RS_86A Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO1;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 6 SC_DE_Reset_Set_1 SPC 400kV B412-BR PROTECTION 86B TRIP RELAY Set XX_RS_86B Transmitted to IEC CONTROL1;GGIO1 CO;SPCSO3;ctlVal;DPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 7 SC_DE_Reset_Reset_2 SPC 400kV B412-BR VT SELECTION 400KV BUS-2 SELECT Reset XX_XX_400KV B2 S Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO1;ctlVal;DPC 517 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 8 SC_DE_Reset_Reset_2 SPC 400kV B412-BR VT SELECTION 400KV BUS-2 DESELECT Reset XX_XX_400KV B2 D Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO2;ctlVal;DPC 516 NO 2 DIGITAL OUTPUT BOARD DOU20x
A G 9 SC_DE_Reset_Reset_2 SPC 400kV B412-BR VT SELECTION 400KV BUS-1 SELECT Reset XX_XX_400KV B1 S Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO3;ctlVal;DPC 515 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A G 10 SC_DE_Reset_Reset_2 SPC 400kV B412-BR VT SELECTION 400KV BUS-1 DESELECT Reset XX_XX_400KV B1 D Transmitted to IEC CONTROL2;GGIO2 CO;SPCSO4;ctlVal;DPC 514 NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 3
Digital Outputs Board Slot H
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A H 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A H 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A H 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 4
Digital Outputs Board Slot I
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A I 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A I 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A I 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number 5
Digital Outputs Board Slot J
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A J 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A J 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A J 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
ANALOG INPUT BOARD AIU21x
Analog Input Board Number 0
Analog Input Board Slot D
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 4/20 mA MV_hla_ AuxVoltage_2 V 400kV B412-BR REACTOR MB OTI HI ALM 0.0 150.0 OTI HI ALM Transmitted to IEC CONTROL2;GGIO3 MX;AnIn1;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 2 4/20 mA MV_hla_ AuxVoltage_2 V 400kV B412-BR REACTOR MB OTI HI TRIP 0.0 150.0 OTI HI TRIP Transmitted to IEC CONTROL2;GGIO3 MX;AnIn2;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 3 4/20 mA MV_hla_ AuxVoltage_2 V 400kV B412-BR REACTOR MB WTI HI ALM 0.0 150.0 WTI HI ALM Transmitted to IEC CONTROL2;GGIO3 MX;AnIn3;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 4 4/20 mA MV_HLa_AuxCurrent_2 A 400kV B412-BR REACTOR MB WTI HI TRIP 0.0 150.0 WTI HI TRIP Transmitted to IEC CONTROL2;GGIO3 MX;AnIn4;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 5 4/20 mA MV_hla_Temp ˚ Cel 400kV B412-BR REACTOR MB AC KIOSK TEMP 0.0 100.0 AC KIOSK TEMP Transmitted to IEC CONTROL2;GGIO3 MX;AnIn5;mag;MV 6 ANALOG INPUT BOARD AIU21x
A 6 SPARE 6 ANALOG INPUT BOARD AIU21x
A 7 SPARE 6 ANALOG INPUT BOARD AIU21x
A 8 SPARE 6 ANALOG INPUT BOARD AIU21x
CT/VT ANALOG INPUT BOARD TMU2x0
CT/VT Board Number 0
CT/VT Board Slot Q
CT/VT Board Model TMU220
Nominal Current 1 (1A/5A)
Nominal Voltage 110.00 [1V … 500V]
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A DF MV_HLa_Frequency_1 Hz 400kV B412-BR SYNCH DATA FREQUENCY DIFFERENCE 0.0 2.0 FREQUENCY DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifHzClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DV MV_hla_ AuxVoltage_1 V 400kV B412-BR SYNCH DATA VOLTAGE DIFFERENCE 0.0 277.13626 VOLTAGE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifVClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Dj MV_hla_PhaseDiff ˚ 400kV B412-BR SYNCH DATA PHASE DIFFERENCE 0.0 360.0 PHASE ANGLE DIFF Transmitted to IEC CONTROL1;RSYN1 MX;DifAngClc;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ia MV_HLa_AuxCurrent A 400kV B412-BR METERING I-R PHASE CURRENT 0.0 2400.0 IR PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ib MV_HLa_AuxCurrent A 400kV B412-BR METERING I-Y PHASE CURRENT 0.0 2400.0 IY PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ic MV_HLa_AuxCurrent A 400kV B412-BR METERING I-B PHASE CURRENT 0.0 2400.0 IB PHASE CURRENT Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;A;phsC;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vb MV_hla_ AuxVoltage_1 V 400kV B412-BR SYNCH DATA INCOMING SUPPLY 0.0 277.13626 INCOMING SUPPLY Transmitted to IEC MEASUREMENT1;rmsMMXU2 MX;PhV;phsB;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uab MV_hla_ AuxVoltage V 400kV B412-BR METERING R-Y VOLTAGE 0.0 480.0 R-Y VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsAB;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ubc MV_HLa_Voltage kV 400kV B412-BR METERING Y-B VOLTAGE 0.0 480.0 Y-B VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsBC;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uca MV_HLa_Voltage kV 400kV B412-BR METERING B-R VOLTAGE 0.0 480.0 B-R VOLTAGE Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;PPV;phsCA;DELTA 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar MV_hla_ AuxVoltage_1 V 400kV B412-BR SYNCH DATA RUNNING SUPPLY 0.0 277.13626 RUNNING SPLY-1 Transmitted to IEC MEASUREMENT1;barMMXU1 MX;PhV;phsA;WYE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Freq (Line) MV_HLa_Frequency Hz 400kV B412-BR METERING FREQUENCY 45.0 55.0 FREQUENCY Transmitted to IEC MEASUREMENT1;rmsMMXU1 MX;Hz;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A P total (MW) MV_HLa_ActPower MW 400kV B412-BR METERING ACTIVE POWER -1662.72 1662.72 ACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotW;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Q total (Mvar) MV_HLa_ActPower MW 400kV B412-BR METERING REACTIVE POWER -1662.72 1662.72 REACTIVE POWER Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotVAr;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A cos ft : Power factor MV_HLa_PowerFactor 400kV B412-BR METERING POWER FACTOR -1.2 1.2 POWER FACTOR Transmitted to IEC MEASUREMENT1;powMMXU1 MX;TotPF;mag;MV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
A SPARE 6 CT/VT ANALOG INPUT BOARD TMU2x0
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPE_HLa_Notper_Perm SPS 400kV B412-BR 52 | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPEN ILK Transmitted to IEC CONTROL2;CILO4 ST;EnaOpn;stVal;SPS None CB OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPE_HLa_Reset_Set SPS 400kV B412-BR 52 | OE_CL_CONTROL OPEN ORDER Set Reset RS_ST_OPN ORD Transmitted to IEC CONTROL1;CSWI8 ST;OpnOrd;general;general;ACT None CB OpenOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPE_HLa_Notper_Perm SPS 400kV B412-BR 89A | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO1 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPE_HLa_Notper_Perm SPS 400kV B412-BR 89B | OE_CL_CONTROL OPEN INTERLOCK Permissive Not Permissive NP_PE_OPN ILK Transmitted to IEC CONTROL2;CILO2 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPE_HLa_Notper_Perm SPS 400kV B412-BR 89R | OE_CL_CONTROL Open/raise interlock result SPS Permissive Not Permissive Open/raise intlk Transmitted to IEC CONTROL2;CILO3 ST;EnaOpn;stVal;SPS None SG OpenIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPS_hla_Set_Reset SPS 400kV B412-BR ORDER RUNNING ON THE BAY Set Reset RS_ST_ORD RUNING Transmitted to IEC CONTROL1;GBAY1 ST;OrdRun;stVal;SPS None OrderInProgress 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPE_HLa_Notper_Perm SPS 400kV B412-BR 52 | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLOSE ILK Transmitted to IEC CONTROL2;CILO4 ST;EnaCls;stVal;SPS None CB CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPE_HLa_Notper_Perm SPS 400kV B412-BR 89A | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO1 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPE_HLa_Notper_Perm SPS 400kV B412-BR 89B | OE_CL_CONTROL CLOSE INTERLOCK Permissive Not Permissive NP_PE_CLS ILK Transmitted to IEC CONTROL2;CILO2 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPE_HLa_Notper_Perm SPS 400kV B412-BR 89R | OE_CL_CONTROL Close/lower interlock result SPS Permissive Not Permissive Close/low. intlk Transmitted to IEC CONTROL2;CILO3 ST;EnaCls;stVal;SPS None SG CloseIntlkSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPE_HLa_Reset_Set SPS 400kV B412-BR SYNCH FUNCTION CLOSE ORDER Set Reset RS_ST_CLS ODR Transmitted to IEC CONTROL1;RSYN1 ST;ClsOpSt;stVal;SPS None IntManualCSFct CS_CloseOrderState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPE_HLA_on_off SPS 400kV B412-BR SYNCH FUNCTION ON/OFF SECONDARY SPS Off On RS_ST_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 ST;EnaSec;origin;SPC None 204 IntManualCSFct CS_OnOff_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPE_HLa_Reset_Set SPS 400kV B412-BR SYNCH FUNCTION POSSIBLE CLOSING Set Reset RS_ST_POS CLS Transmitted to IEC CONTROL1;RSYN1 ST;Rel;stVal;SPS 458; None IntManualCSFct CS_AuthoState_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPE_HLa_Reset_Set SPS 400kV B412-BR SYNCH FUNCTION PRESENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF U PRES Transmitted to IEC CONTROL1;RSYN1 ST;VRefInd;stVal;SPS 458; None IntManualCSFct CS_VoltageRefPresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPE_HLa_Reset_Set SPS 400kV B412-BR SYNCH FUNCTION ABSENCE OF REFERENCE VOLTAGE Set Reset RS_ST_REF. U ABS Transmitted to IEC CONTROL1;RSYN1 ST;VRefAbs;stVal;SPS 458; None IntManualCSFct CS_VoltageRefAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPE_HLa_Reset_Set SPS 400kV B412-BR SYNCH FUNCTION VOLT ABSENCE Set Reset RS_ST_VOLT ABS Transmitted to IEC CONTROL1;RSYN1 ST;VAbs;stVal;SPS 458; None IntManualCSFct CS_VoltageAbsence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 17 SPE_HLa_Reset_Set SPS 400kV B412-BR SYNCH FUNCTION VOLT PRESENCE Set Reset RS_ST_VOLT PRES Transmitted to IEC CONTROL1;RSYN1 ST;VP;stVal;SPS 458; None IntManualCSFct CS_VoltagePresence_SPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 18 SPE_HLa_Notper_Perm SPS 400kV B412-BR 52 | OE_CL_CONTROL CLOSE ORDER Permissive Not Permissive RS_ST_CLS ORD Transmitted to IEC CONTROL1;CSWI8 ST;ClsOrd;general;general;ACT 457; None 243;244 CB CloseOrderSPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 19 SPE_HLa_Notper_Perm SPS 400kV B412-BR 89A IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI1 ST;IndSys1;stVal;SPS 443<; None 507 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 20 SPE_HLa_Notper_Perm SPS 400kV B412-BR 89AE IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI5 ST;IndSys1;stVal;SPS 446<; None 508 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 21 SPE_HLa_Notper_Perm SPS 400kV B412-BR 89B IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI2 ST;IndSys1;stVal;SPS 447<; None 509 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 22 SPE_HLa_Notper_Perm SPS 400kV B412-BR 89BE IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI3 ST;IndSys1;stVal;SPS 450<; None 510 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 23 SPE_HLa_Notper_Perm SPS 400kV B412-BR 89R IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI6 ST;IndSys1;stVal;SPS 451<; None 511 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 24 SPE_HLa_Notper_Perm SPS 400kV B412-BR 89RE IL PERMISSIVE Permissive Not Permissive NP_PE_I/L PERM Transmitted to IEC CONTROL1;CSWI7 ST;IndSys1;stVal;SPS 454<; None 512 SG 1 C264 SELF GENERATED DIGITAL INFORMATION
A 25 SPE_HLa_Reset_Set SPS 400kV B412-BR CSD CSD BYPASS Set Reset RS_ST_CSD BYPASS Transmitted to IEC CONTROL1;GAPC4 ST;IndSys1;stVal;SPS 456<; None 513 1 C264 SELF GENERATED DIGITAL INFORMATION
A 26 SPE_HLa_Reset_Set SPS 400kV B412-BR PROTECTION SOTF TO RELAY Set Reset RS_ST_SOTF TO RL Transmitted to IEC CONTROL1;GAPC2 ST;IndSys1;stVal;SPS 457<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 27 SPE_HLa_Reset_Set SPS 400kV B412-BR SYNCH DATA CLOSE PERMISSIVE Set Reset RS_ST_CB CLOSE Transmitted to IEC CONTROL1;GAPC1 ST;IndSys5;stVal;SPS 458<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 28 SPE_HLa_Reset_Set SPS 400kV B412-BR SYNCH DATA DEAD INCOMING DEAD RUNNING Set Reset RS_ST_DINC_DRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys4;stVal;SPS 458<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 29 SPE_HLa_Reset_Set SPS 400kV B412-BR SYNCH DATA DEAD INCOMING LIVE RUNNING Set Reset RS_ST_DINC_LRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys3;stVal;SPS 458<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 30 SPE_HLa_Reset_Set SPS 400kV B412-BR SYNCH DATA LIVE INCOMING DEAD RUNNING Set Reset RS_ST_LINC_DRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys2;stVal;SPS 458<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 31 SPE_HLa_Reset_Set SPS 400kV B412-BR SYNCH DATA LIVE INCOMING LIVE RUNNING Set Reset RS_ST_LINC_LRUN Transmitted to IEC CONTROL1;GAPC1 ST;IndSys1;stVal;SPS 458<; None 1 C264 SELF GENERATED DIGITAL INFORMATION
A 32 SPE_HLa_Reset_Set SPS 400kV B412-BR VT SELECTION 400KV BUS-1 DESELECT Set Reset RS_ST_400KV B1 D Transmitted to IEC CONTROL1;GAPC3 ST;IndSys3;stVal;SPS 460<; None 514 1 C264 SELF GENERATED DIGITAL INFORMATION
A 33 SPE_HLa_Reset_Set SPS 400kV B412-BR VT SELECTION 400KV BUS-1 SELECT Set Reset RS_ST_400KV B1 S Transmitted to IEC CONTROL1;GAPC3 ST;IndSys1;stVal;SPS 460<; None 515 1 C264 SELF GENERATED DIGITAL INFORMATION
A 34 SPE_HLa_Reset_Set SPS 400kV B412-BR VT SELECTION 400KV BUS-2 DESELECT Set Reset RS_ST_400KV B2 D Transmitted to IEC CONTROL1;GAPC3 ST;IndSys4;stVal;SPS 460<; None 516 1 C264 SELF GENERATED DIGITAL INFORMATION
A 35 SPE_HLa_Reset_Set SPS 400kV B412-BR VT SELECTION 400KV BUS-2 SELECT Set Reset RS_ST_400KV B2 S Transmitted to IEC CONTROL1;GAPC3 ST;IndSys2;stVal;SPS 460<; None 517 1 C264 SELF GENERATED DIGITAL INFORMATION
A 36 DP_HLA_CBOpen_Close DPS 400kV B412-BR 52 POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI8 ST;Pos;stVal;DPC 426;441;442;443;444;445;447;448;449;452;453;460; None 119 455 Yes CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 37 DP_HLA_CBOpen_Close DPS 400kV B412-BR 52 POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI8 ST;Pos;stVal;DPC 426;441;442;443;444;445;447;448;449;452;453;460; None 119 455 Yes CB ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 38 DP_HLA_ ISOOpen_Close DPS 400kV B412-BR 89A COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 39 DP_HLA_ ISOOpen_Close DPS 400kV B412-BR 89A COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI1 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 40 DP_HLa_ESOpen_Close DPS 400kV B412-BR 89AE COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI5 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 41 DP_HLa_ESOpen_Close DPS 400kV B412-BR 89AE COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI5 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 42 DP_HLA_ ISOOpen_Close DPS 400kV B412-BR 89B COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 43 DP_HLA_ ISOOpen_Close DPS 400kV B412-BR 89B COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI2 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 44 DP_HLa_ESOpen_Close DPS 400kV B412-BR 89BE COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 45 DP_HLa_ESOpen_Close DPS 400kV B412-BR 89BE COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI3 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 46 DP_HLA_ ISOOpen_Close DPS 400kV B412-BR 89R COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI6 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 47 DP_HLA_ ISOOpen_Close DPS 400kV B412-BR 89R COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI6 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 48 DP_HLa_ESOpen_Close DPS 400kV B412-BR 89RE COMP. POSITION Open OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI7 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 49 DP_HLa_ESOpen_Close DPS 400kV B412-BR 89RE COMP. POSITION Closed OE_CL_COMP_POS Transmitted to IEC CONTROL1;CSWI7 ST;Pos;stVal;DPC None SG ComputedSwitchPos_DPS 1 C264 SELF GENERATED DIGITAL INFORMATION
A 50 DP_HLa_LocRem_Bay DPS 400kV B412-BR BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 123 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 51 DP_HLa_LocRem_Bay DPS 400kV B412-BR BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 ST;Loc;origin;DPC None 123 LocRemBay 1 C264 SELF GENERATED DIGITAL INFORMATION
A 52 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SC_DE_Off_On SPC 400kV B412-BR SYNCH FUNCTION ON/OFF SECONDARY CONTROL SPC On Off OF_ON_ON/OFF SEC Transmitted to IEC CONTROL1;RSYN1 CO;EnaSec;ctlVal;DPC 204 IntManualCSFct CS_CtrlOnOff_SPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SC_DE_Reset_Set SPC 400kV B412-BR CSD CSD OUT FROM HMI Set XX_ST_CSD OUT H Transmitted to IEC CONTROL1;GAPC4 CO;SPCSO1;ctlVal;DPC 456; 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 DC_DE_LocRem_BayCtrl DPC 400kV B412-BR BCU MODE Local LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 123 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 DC_DE_LocRem_BayCtrl DPC 400kV B412-BR BCU MODE Remote LC_RM_BCU MODE Transmitted to IEC CONTROL1;GBAY1 CO;Loc;ctlVal;DPC 123 LocRemBay_DPC 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 MV_HLa_Unused 400kV B412-BR CB_COUNTER Count_Close 0.0 10000.0 Count_Close Transmitted to IEC CONTROL2;GAPC1 MX;AnIn2;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 MV_HLa_Unused 400kV B412-BR CB_COUNTER Count_Open 0.0 10000.0 Count_Open Transmitted to IEC CONTROL2;GAPC1 MX;AnIn1;mag;MV UsrFct UserFunctionMV 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
PATH SIGNAL IEC ADDRESS
Scs | Ethernet network | System Group | B401_LINE TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B401_LINE | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Scs | Ethernet network | System Group | B402_TIE TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B402_TIE | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Scs | Ethernet network | System Group | B403_FUT TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B403_FUT | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Scs | Ethernet network | System Group | B407_AT TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B407_AT | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Scs | Ethernet network | System Group | B409_ICT1 TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B409_ICT1 | C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
Scs | Ethernet network | System Group | B412_BR TIME SYNCHRONISATION ERROR Scs | Ethernet network | System Group | B412_BR| C26x IEC Map. | SYSTEM | C26xLDIA1 | ST | SyncSt
PATH PROFILE SIGNAL IEC ADDRESS
B401-LINE| PROTECTION |NL_AL_GOOSE RECP 46 : SPE_HLA_Normal_Alarm GOOSE RECEIPT FAIL/TROUBLE CONTROL2; GAPC2 ST; IndSys2
B402-TIE | PROTECTION |NL_AL_GOOSE RECP 46 : SPE_HLA_Normal_Alarm GOOSE RECEIPT FAIL/TROUBLE CONTROL2; GAPC2 ST; IndSys2
B407-AT | PROTECTION |NL_AL_GOOSE RECP 46 : SPE_HLA_Normal_Alarm GOOSE RECEIPT FAIL/TROUBLE CONTROL2; GAPC2 ST; IndSys2
B409-ICT-1 | PROTECTION |NL_AL_GOOSE RECP 46 : SPE_HLA_Normal_Alarm GOOSE RECEIPT FAIL/TROUBLE CONTROL2; GAPC2 ST; IndSys2
B412-BR | PROTECTION |NL_AL_GOOSE RECP 46 : SPE_HLA_Normal_Alarm GOOSE RECEIPT FAIL/TROUBLE CONTROL2; GAPC2 ST; IndSys2
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R707_P442_21R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R707_P442_21R
DIGITAL INFORMATION FROM IED IED name
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R407_P442_21/67 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P442_21R GOOSE 86A TRIP RELAY Alarm Reset RS_OP_86A Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P442_21R GOOSE 86B TRIP RELAY Alarm Reset RS_OP_86B Transmitted to IEC System;GosGGIO2 ST;Ind2;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_P442_21R GOOSE BB Alarm Reset RS_ST_BB Transmitted to IEC System;GosGGIO2 ST;Ind3;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R407_P442_21/67 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 765kV R407_P442_21/67 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;OcpEI1PTOC1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 765kV R407_P442_21/67 PROTECTION HV OVER CURRENT R-PH TRIP Operated Reset RS_OP_HV O/C R Transmitted to IEC Protection;OcpPTOC1 ST;Op;phsA;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 765kV R407_P442_21/67 PROTECTION HV OVER CURRENT Y-PH TRIP Operated Reset RS_OP_HV O/C Y Transmitted to IEC Protection;OcpPTOC1 ST;Op;phsB;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 765kV R407_P442_21/67 PROTECTION HV OVER CURRENT B-PH TRIP Operated Reset RS_OP_HV O/C B Transmitted to IEC Protection;OcpPTOC1 ST;Op;phsC;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R407_P442_21/67 PROTECTION HV OVER CURRENT TRIP Operated Reset RS_OP_HV O/C Transmitted to IEC Protection;OcpPTOC1 ST;Op;general;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R407_P442_21/67 PROTECTION HV OVER CURRENT START Set Reset RS_OP_HV O/C S Transmitted to IEC Protection;OcpPTOC1 ST;Str;general;general;ACD None 1 0
A SPARE SPS None No 1 #REF!
DIGITAL INFORMATION TO IED IED name R707_P442_21R
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 765kV R407_P442_21/67 PROTECTION DIRECTIONAL EARTH FAULT START Set Reset RS_ST_E/F_S Protection;EfdPTOC1 ST;Op;phsC;general;ACD 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPS 765kV R407_P442_21/67 PROTECTION DIRECTIONAL EARTH FAULT TRIP Operated Reset RS_ST_E/F Protection;EfdPTOC1 ST;Op;phsC;general;ACT 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
ANALOG INFORMATION FROM IED IED name R707_P442_21R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P442_21R
ANALOG INFORMATION TO IED IED name R707_P442_21R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P442_21R
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P442_21R
COUNTER INFORMATION FROM IED IED name R707_P442_21R
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P442_21R
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.3.0 ACAC
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : BHADLA
IEC Description
Computer Name R707_P442_21R GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) IEC Read Only
Gateway Port used (on gateway)
SCADA 1 765KV SERVER M 1
IED NAME : R707_P442_21R
DIGITAL INFORMATION FROM IED IED name
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A System;LLN0 ST;SyncSt;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P442_21/67 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC Transmitted to IEC System;LLN0 ST;SyncSt;stVal;SPS None 1 DIGITAL INFORMATION FROM IED IED name
A System;GosGGIO2 ST;Ind1;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P442_21R GOOSE 86A TRIP RELAY Alarm Reset RS_OP_86A Transmitted to IEC System;GosGGIO2 ST;Ind1;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind2;stVal;SPS SPE_HLA_Reset_Optd SPS 765kV R707_P442_21R GOOSE 86B TRIP RELAY Alarm Reset RS_OP_86B Transmitted to IEC System;GosGGIO2 ST;Ind2;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind3;stVal;SPS SPE_HLa_Reset_Set SPS 765kV R707_P442_21R GOOSE BB Alarm Reset RS_ST_BB Transmitted to IEC System;GosGGIO2 ST;Ind3;stVal;SPS None Yes 1 #REF!
A System;GosGGIO2 ST;Ind4;stVal;SPS SPE_HLA_Normal_Alarm SPS 765kV R712_P442_21/67 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP Transmitted to IEC System;GosGGIO2 ST;Ind4;stVal;SPS None Yes 1 #REF!
A Protection;PTRC1 ST;Tr;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Transmitted to IEC Protection;PTRC1 ST;Tr;general;ACT None 1 #REF!
A Protection;OcpEI1PTOC1 ST;Op;phsA;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67 PROTECTION LV OVER CURRENT R-PH TRIP Operated Reset RS_OP_HV O/C R Transmitted to IEC Protection;OcpPTOC1 ST;Op;phsA;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Op;phsB;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67 PROTECTION LV OVER CURRENT Y-PH TRIP Operated Reset RS_OP_HV O/C Y Transmitted to IEC Protection;OcpPTOC1 ST;Op;phsB;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Op;phsC;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67 PROTECTION LV OVER CURRENT B-PH TRIP Operated Reset RS_OP_HV O/C B Transmitted to IEC Protection;OcpPTOC1 ST;Op;phsC;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Op;general;general;ACT SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67 PROTECTION LV OVER CURRENT TRIP Operated Reset RS_OP_HV O/C Transmitted to IEC Protection;OcpPTOC1 ST;Op;general;general;ACT None 1 0
A Protection;OcpEI1PTOC1 ST;Str;general;general;ACD SPE_HLA_Reset_Optd SPS 765kV R712_P442_21/67 PROTECTION LV OVER CURRENT START Set Reset RS_OP_HV O/C S Transmitted to IEC Protection;OcpPTOC1 ST;Str;general;general;ACD None 1 0
A SPARE SPS None No 1 #REF!
DIGITAL INFORMATION TO IED IED name R707_P442_21R
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS 765kV R407_P442_21/67 PROTECTION DIRECTIONAL EARTH FAULT START Set Reset RS_ST_E/F_S Protection;EfdPTOC1 ST;Op;phsC;general;ACD 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPS 765kV R407_P442_21/67 PROTECTION DIRECTIONAL EARTH FAULT TRIP Operated Reset RS_ST_E/F Protection;EfdPTOC1 ST;Op;phsC;general;ACT 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name R707_P442_21R
ANALOG INFORMATION FROM IED IED name R707_P442_21R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name R707_P442_21R
ANALOG INFORMATION TO IED IED name R707_P442_21R
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P442_21R
A SPARE 13 ANALOG INFORMATION TO IED IED name R707_P442_21R
COUNTER INFORMATION FROM IED IED name R707_P442_21R
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P442_21R
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name R707_P442_21R
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF!
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
SYSTEM INFORMATION DATA DESCRIPTION
Gateway Port used (on gateway) Keys :
SCADA 1 GE Reserved
SCADA 2 Auto generated
SCADA 3 Read Only
SYSTEM INFORMATION SERVER OI
SERVER OI Name :
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Sp0000 SPS AGENCY STATUS HEALTHY FAULTY Agency status 40 SYSTEM INFORMATION SERVER OI AgencyStatus
Sp0000 SPS AUTOMATIC ARCHIVING STATUS HEALTHY FAULTY Auto archiving 40 SYSTEM INFORMATION SERVER OI AutomaticArchiving
Mp0000OIHist MPS HISTORIAN DATABASE STATUS Central archive 40 SYSTEM INFORMATION SERVER OI CentralArchiving
Sp0000 SPS OI SBUS LINK HEALTHY FAULTY Device link 40 SYSTEM INFORMATION SERVER OI CommDevice
Sp0H00 SPS SBUS ACQUISITION STATUS HEALTHY FAULTY IEC Coupling 40 SYSTEM INFORMATION SERVER OI CouplingStatus
Sp0H00 SPS LOGGING QUEUE STATUS HEALTHY FAULTY Log Queue 40 SYSTEM INFORMATION SERVER OI LogQueue
Mp0HLAOpMod MPS OPERATING MODE Operating mode 40 SYSTEM INFORMATION SERVER OI OperatingMode
Sp0H00 SPS REDUNDANCY MODE ACTIVE STANDBY Redundancy mode 40 SYSTEM INFORMATION SERVER OI RedDevice
Mp0HLAOpMod MPS REDUNDANCY STATUS Redundancy status No 40 SYSTEM INFORMATION SERVER OI RedundancyStatus
Sp0H00 SPS SYNCHRONIZATION STATUS HEALTHY FAULTY Synchronisation 40 SYSTEM INFORMATION SERVER OI SyncDevice
OI printer Mp0HLAOIPrt MPS PRINTER STATUS Printer status 40 SYSTEM INFORMATION SERVER OI Printing
OI printer Mp0HLAOIPrt MPS BACKUP PRINTER STATUS BackupPrint stat No 40 SYSTEM INFORMATION SERVER OI BackupPrinting
SYSTEM INFORMATION CLIENT OI
CLIENT OI Name :
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Sp0HLARev SPS CONNECTION STATUS HEALTHY FAULTY OI client link 41 SYSTEM INFORMATION CLIENT OI CommS2K_C
SYSTEM INFORMATION MiCOM C264
MiCOM C264 Name :
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Sp0000 SPS DATABASE INCONSISTENCY YES NO DB incoh. SPS 42 SYSTEM INFORMATION MiCOM C264 DBIncoherency
ScD000Pul SPC C264 DATABASE SWITCHING EXECUTE - DB switch ctrl 42 SYSTEM INFORMATION MiCOM C264 DBSwitch_SPC
Sp0000 SPS C264 SBUS LINK HEALTHY FAULTY Device link 42 SYSTEM INFORMATION MiCOM C264 CommDevice
Sp0000 SPS DIGITAL INPUT ACQUISITION FAULTY HEALTHY DI acq stopped 42 SYSTEM INFORMATION MiCOM C264 DIAcquisitionStopped
DcD000Pul DPC C264 BAYS CONTROL MODE CHANGE REMOTE LOCAL Loc/rem ctrl DPC 42 SYSTEM INFORMATION MiCOM C264 LocRemDevice_DPC
Dp0000 DPS C264 MANAGED BAYS IN CONTROL MODE REMOTE LOCAL Local/remote DPS 42 SYSTEM INFORMATION MiCOM C264 LocRemDevice
Sp0HL0 SPS C264 BAYS IN CONTROL MODE REMOTE LOCAL Local/remote SPS 42 SYSTEM INFORMATION MiCOM C264 LocRemDeviceForIEC
Mv0000Mst MV C264 FAULT LEVEL FOR REDUNDANCY Main status MV 42 SYSTEM INFORMATION MiCOM C264 MainInternalStatus
DcD000Pul DPC C264 FORCE OPERATION MODE TO OPERATIONNAL MAINTENANCE Mode control DPC 42 SYSTEM INFORMATION MiCOM C264 ModeDevice_DPC
Mp0HLAOpMod MPS C264 OPERATING MODE Operating mode 42 SYSTEM INFORMATION MiCOM C264 OperatingMode
ScD000Pul SPC C264 BIU REDUNDANCY RELAY CO 2 ACTIVATE DEACTIVATE Red mode ctrl 42 SYSTEM INFORMATION MiCOM C264 RedChangeMode_SPC
ScD000Pul SPC C264 BIU REDUNDANCY RELAY CO 1 ACTIVATE DEACTIVATE Red Status ctrl 42 SYSTEM INFORMATION MiCOM C264 RedChangeStatus_SPC
Sp0HL0 SPS REDUNDANT C264 CHANGE MODE ACTIVE STANDBY Red. change mode 42 SYSTEM INFORMATION MiCOM C264 RedChangeMode
Sp0HL0 SPS REDUNDANT C264 STATUS ACTIVE STANDBY Red. change stat 42 SYSTEM INFORMATION MiCOM C264 RedChangeStatus
Sp0000 SPS SOFTWARE ERROR DETECTED YES NO Soft. error SPS 42 SYSTEM INFORMATION MiCOM C264 SoftError
Sp0H00 SPS C264 SYNCHRONIZATION STATUS HEALTHY FAULTY Synchronisation 42 SYSTEM INFORMATION MiCOM C264 SyncDevice
DcD000Pul DPC C264 CHANGE EXPLOITATION MODE NORMAL TEST Test control DPC 42 SYSTEM INFORMATION MiCOM C264 TestDevice_DPC
Sp0000 SPS C264 WATCHDOG RELAY STATUS HEALTHY FAULTY Watchdog SPS 42 SYSTEM INFORMATION MiCOM C264 WatchdogError
Dp0000OpM DPS C264 OPERATING MODE RUNNING MAINTENANCE Device mode No 42 SYSTEM INFORMATION MiCOM C264 ModeDevice
Sp0H00 SPS DISTURBANCE FILE ON C264 READY NOT READY DREC ready No 42 SYSTEM INFORMATION MiCOM C264 DisturbUCA2
Sp0000 SPS C264 COUNTERS ACQUISITION TOP YES NO Counter Top No 42 SYSTEM INFORMATION MiCOM C264 CounterTop
Sp0HLARev SPS GPS SYNCHRONISATION SOURCE HEALTHY FAULTY Ext clock status No 42 SYSTEM INFORMATION MiCOM C264 ExtClockStatus
Sp0HL0 SPS C264 REDUNDANCY MODE ACTIVE STANDBY Redundancy mode No 42 SYSTEM INFORMATION MiCOM C264 RedDevice
Sp0HL0 SPS REPORT BUFFER OVERFLOW GTW 1 YES NO Buff Ov Gtw 1 42 SYSTEM INFORMATION MiCOM C264
Sp0HL0 SPS REPORT BUFFER OVERFLOW GTW 2 YES NO Buff Ov Gtw 2
Sp0HL0 SPS REPORT BUFFER OVERFLOW OI YES NO Buff Ov OI
Sp0HL0 SPS REPORT BUFFER OVERFLOW OI BACKUP YES NO Buff Ov OI Bck
Sp0HL0 SPS ALL AIU STATUS FAULTY HEALTHY All AIU status 42 SYSTEM INFORMATION MiCOM C264 GlobalAIUStatus
Sp0HL0 SPS ALL AOU STATUS FAULTY HEALTHY All AOU status 42 SYSTEM INFORMATION MiCOM C264 GlobalAOUStatus
Sp0HL0 SPS ALL CCU STATUS FAULTY HEALTHY All CCU status 42 SYSTEM INFORMATION MiCOM C264 GlobalCCUStatus
Sp0HL0 SPS ALL DIU STATUS FAULTY HEALTHY All DIU status 42 SYSTEM INFORMATION MiCOM C264 GlobalDIUStatus
Sp0HL0 SPS ALL DOU STATUS FAULTY HEALTHY All DOU status 42 SYSTEM INFORMATION MiCOM C264 GlobalDOUStatus
Sp0HL0 SPS ALL TMU STATUS FAULTY HEALTHY All TMU status 42 SYSTEM INFORMATION MiCOM C264 GlobalTMUStatus
Sp0HL0 SPS ALL HBU STATUS FAULTY HEALTHY All HBU status
Sp0HL0 SPS ALL IED STATUS FAULTY HEALTHY All IED status 42 SYSTEM INFORMATION MiCOM C264 GlobalIEDStatus
Sp0HL0 SPS ALL Printer STATUS FAULTY HEALTHY All Printer stat 42 SYSTEM INFORMATION MiCOM C264 GlobalPrinterStatus
Sp0HL0 SPS ALL RACK STATUS FAULTY HEALTHY All rack status 42 SYSTEM INFORMATION MiCOM C264 GlobalRackLinkStatus
Sp0HL0 SPS LOCAL ALARM ACKNOWLEDGEMENT YES NO Local alarm ack No 42 SYSTEM INFORMATION MiCOM C264 LocalAlarmAck_SPS
Sp0HL0 SPS SETTING DONE YES NO Setting done 42 SYSTEM INFORMATION MiCOM C264 SettingDone
Sp0HL0 SPS SETTING FILE DISCORDANCE YES NO Setting disc. 42 SYSTEM INFORMATION MiCOM C264 SettingFileDiscordance
Sp0HL0 SPS SETTING IN PROGRESS YES NO Setting in prog. 42 SYSTEM INFORMATION MiCOM C264 SettingInProgress
Sp0HL0 SPS SETTING INCOHERENCY YES NO Setting incoher. 42 SYSTEM INFORMATION MiCOM C264 SettingIncoherency
BoardBIU Mp0HLABoard MPS BIU BOARD STATUS BIU status 42 SYSTEM INFORMATION MiCOM C264 BIUStatus
BoardGHU Mp0HLABoard MPS GHU BOARD STATUS GHU status 42 SYSTEM INFORMATION MiCOM C264 GHUStatus
BoardAIU201 Mp0HLABoard MPS AIU20x BOARD STATUS AIU status 42 SYSTEM INFORMATION MiCOM C264 AIUStatus
BoardAIU210 Mp0HLABoard MPS AIU20x BOARD STATUS AIU status 42 SYSTEM INFORMATION MiCOM C264 AIUStatus
BoardAOU200 Mp0HLABoard MPS AOU200 BOARD STATUS AOU status 42 SYSTEM INFORMATION MiCOM C264 AOUStatus
BoardDIU Mp0HLABoard MPS DIU BOARD STATUS DIU status 42 SYSTEM INFORMATION MiCOM C264 DIUStatus
BoardDOU Mp0HLABoard MPS DOU BOARD STATUS DOU status 42 SYSTEM INFORMATION MiCOM C264 DOUStatus
BoardCCU Mp0HLABoard MPS CCU BOARD STATUS CCU status 42 SYSTEM INFORMATION MiCOM C264 CCUStatus
BoardTMU Mp0HLABoard MPS TMU BOARD STATUS TMU status 42 SYSTEM INFORMATION MiCOM C264 TIUStatus
BoardHBU Mp0HLABoard MPS HBU BOARD STATUS HBU status
IED Sp0HLARev SPS IED CONNECTION STATUS TO C264 HEALTHY FAULTY IED SPS com. 42 SYSTEM INFORMATION MiCOM C264 CommIED
IED Sp0H00 SPS IED SYNCHRONISATION STATUS HEALTHY FAULTY IED SPS Synchro. 42 SYSTEM INFORMATION MiCOM C264 SyncIED
IED Sp0000 SPS IED DISTURBANCE FILE READY NOT READY IED DREC ready No 42 SYSTEM INFORMATION MiCOM C264 DisturbIED
RackLink Dp0000OpM DPS RACK LINK STATUS HEALTHY FAULTY Rack link status 42 SYSTEM INFORMATION MiCOM C264 RackLinkStatus
PLC Isagraph Mp0HLAIsag MPS ISAGRAF STATUS ISAGRAF status 42 SYSTEM INFORMATION MiCOM C264 ISAGRAFStatus
BoardPrinter Dp0000OpM DPS PRINTER STATUS DPS Printer st. DPS No 42 SYSTEM INFORMATION MiCOM C264 PrinterStatus
BoardPrinter Mp0HLAOIPrt MPS LOCAL PRINTER STATUS Printer Status 42 SYSTEM INFORMATION MiCOM C264 Printing
SCADA Sp0H00 SPS C264 SCADA PORT COMMUNICATION ACTIVE STANDBY Redundancy SPS 42 SYSTEM INFORMATION MiCOM C264 RedSCADA
SCADA Sp0HLARev SPS SCADA CONNECTION STATUS TO C264 HEALTHY FAULTY SCADA SPS com. 42 SYSTEM INFORMATION MiCOM C264 CommSCADA
SYSTEM INFORMATION MiCOM C364
MiCOM C364 Name :
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Sp0000 SPS DATABASE INCONSISTENCY YES NO DB incoh. SPS 43 SYSTEM INFORMATION MiCOM C364 DBIncoherency
ScD000Pul SPC C364 DATABASE SWITCHING EXECUTE - DB switch ctrl 43 SYSTEM INFORMATION MiCOM C364 DBSwitch_SPC
Sp0000 SPS C364 SBUS LINK HEALTHY FAULTY Device link 43 SYSTEM INFORMATION MiCOM C364 CommDevice
DcD000Pul DPC C364 BAYS CONTROL MODE CHANGE REMOTE LOCAL Loc/rem ctrl DPC 43 SYSTEM INFORMATION MiCOM C364 LocRemDevice_DPC
Dp0000 DPS C364 MANAGED BAYS IN CONTROL MODE REMOTE LOCAL Local/remote DPS 43 SYSTEM INFORMATION MiCOM C364 LocRemDevice
Sp0HL0 SPS C364 BAYS IN CONTROL MODE REMOTE LOCAL Local/remote SPS 43 SYSTEM INFORMATION MiCOM C364 LocRemDeviceForIEC
Sp0H00 SPS LOGGING QUEUE STATUS HEALTHY FAULTY Log Queue 43 SYSTEM INFORMATION MiCOM C364 LogQueue
DcD000Pul DPC C364 FORCE OPERATION MODE TO OPERATIONNAL MAINTENANCE Mode control DPC 43 SYSTEM INFORMATION MiCOM C364 ModeDevice_DPC
Mp0HLAOpMod MPS C364 OPERATING MODE Operating mode 43 SYSTEM INFORMATION MiCOM C364 OperatingMode
Sp0000 SPS SOFTWARE ERROR DETECTED YES NO Soft. error SPS 43 SYSTEM INFORMATION MiCOM C364 SoftError
Sp0H00 SPS C364 SYNCHRONIZATION STATUS HEALTHY FAULTY Synchronisation 43 SYSTEM INFORMATION MiCOM C364 SyncDevice
DcD000Pul DPC C364 CHANGE EXPLOITATION MODE NORMAL TEST Test control DPC 43 SYSTEM INFORMATION MiCOM C364 TestDevice_DPC
Sp0000 SPS C364 WATCHDOG RELAY STATUS HEALTHY FAULTY Watchdog SPS 43 SYSTEM INFORMATION MiCOM C364 WatchdogError
Dp0000OpM DPS C364 OPERATING MODE RUNNING MAINTENANCE Device mode No 43 SYSTEM INFORMATION MiCOM C364 ModeDevice
Sp0HLARev SPS GPS SYNCHRONISATION SOURCE HEALTHY FAULTY Ext clock status No 43 SYSTEM INFORMATION MiCOM C364 ExtClockStatus
Sp0HL0 SPS C364 REDUNDANCY MODE ACTIVE STANDBY Redundancy mode No 43 SYSTEM INFORMATION MiCOM C364 RedDevice
IED Sp0HLARev SPS IED CONNECTION STATUS TO C364 HEALTHY FAULTY IED SPS com. 43 SYSTEM INFORMATION MiCOM C364 CommIED
IED Sp0H00 SPS IED SYNCHRONISATION STATUS HEALTHY FAULTY IED SPS Synchro. 43 SYSTEM INFORMATION MiCOM C364 SyncIED
IED Sp0000 SPS IED DISTURBANCE FILE READY NOT READY IED DREC ready No 43 SYSTEM INFORMATION MiCOM C364 DisturbIED
PLC Isagraph Mp0HLAIsag MPS ISAGRAF STATUS ISAGRAF status 43 SYSTEM INFORMATION MiCOM C364 ISAGRAFStatus
SCADA Sp0H00 SPS C364 SCADA PORT COMMUNICATION ACTIVE STANDBY Redundancy SPS 43 SYSTEM INFORMATION MiCOM C364 RedSCADA
SCADA Sp0HLARev SPS SCADA CONNECTION STATUS TO C364 HEALTHY FAULTY SCADA SPS com. 43 SYSTEM INFORMATION MiCOM C364 CommSCADA
SYSTEM INFORMATION UCA2 IED
UCA2 IED Name :
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Sp0HLARev SPS IED SBUS LINK HEALTHY FAULTY Device link 44 SYSTEM INFORMATION UCA2 IED CommDevice
SYSTEM INFORMATION GATEWAY
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
ScD000Pul SPC GTW DATABASE SWITCHING EXECUTE - DB switch ctrl 45 SYSTEM INFORMATION GATEWAY DBSwitch_SPC
Sp0000 SPS GTW SBUS LINK HEALTHY FAULTY Device link 45 SYSTEM INFORMATION GATEWAY CommDevice
DcD000Pul DPC GTW FORCE OPERATION MODE TO OPERATIONNAL MAINTENANCE Mode control DPC 45 SYSTEM INFORMATION GATEWAY ModeDevice_DPC
Mp0HLAOpMod MPS GTW OPERATING MODE Operating mode 45 SYSTEM INFORMATION GATEWAY OperatingMode
Sp0H00 SPS GTW SYNCHRONISATION STATUS HEALTHY FAULTY Synchronisation 45 SYSTEM INFORMATION GATEWAY SyncDevice
SCADA Sp0H00 SPS GTW SCADA PORT COMMUNICATION ACTIVE STANDBY Redundancy SPS 45 SYSTEM INFORMATION GATEWAY RedSCADA
SCADA Sp0HLARev SPS SCADA CONNECTION STATUS TO GTW HEALTHY FAULTY SCADA SPS com. 45 SYSTEM INFORMATION GATEWAY CommSCADA
IED Sp0HLARev SPS IED CONNECTION STATUS TO GTW HEALTHY FAULTY IED SPS com. 42 SYSTEM INFORMATION MiCOM C264 CommIED
IED Sp0H00 SPS IED SYNCHRONISATION STATUS HEALTHY FAULTY IED SPS Synchro. 42 SYSTEM INFORMATION MiCOM C264 SyncIED
PLC Isagraph Mp0HLAIsag MPS ISAGRAF STATUS ISAGRAF status 43 SYSTEM INFORMATION MiCOM C364 ISAGRAFStatus_GTW
SYSTEM INFORMATION IEC 61850
IEC 61850 Name :
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Sp0HLARev SPS IED SBUS LINK HEALTHY FAULTY Device link 46 SYSTEM INFORMATION IEC 61850 CommDevice
Mp0HLAOpMod MPS IED OPERATING MODE Operating mode No 46 SYSTEM INFORMATION IEC 61850 OperatingMode
DcD000Pul DPC IED FORCE OPERATION MODE TO OPERATIONNAL MAINTENANCE Mode control DPC No 46 SYSTEM INFORMATION IEC 61850 ModeDevice_DPC
Sp0H00 SPS REDUNDANCY MODE ACTIVE STANDBY Redundancy mode No 46 SYSTEM INFORMATION IEC 61850 RedDevice
Sp0H00 SPS DISTURBANCE FILE ON IED READY NOT READY DREC ready No 46 SYSTEM INFORMATION IEC 61850 DisturbUCA2
Sp0H00 SPS LOGICAL DEVICE DISTURBANCE FILE READY NOT READY LD DREC ready No 46 SYSTEM INFORMATION IEC 61850 DisturbLD
Sp0000 SPS IEC61850 GENERIC SPS HEALTHY FAULTY IEC61850 gen SPS No 46 SYSTEM INFORMATION IEC 61850 UCA2GenSPS
Dp0000 DPS IEC61850 GENERIC DPS HEALTHY FAULTY IEC61850 gen DPS No 46 SYSTEM INFORMATION IEC 61850 UCA2GenDPS
Mp0000OIHist MPS IEC61850 GENERIC MPS IEC61850 gen MPS No 46 SYSTEM INFORMATION IEC 61850 UCA2GenMPS
ScD000Pul SPC IEC61850 GENERIC SPC HEALTHY FAULTY IEC61850 gen SPC No 46 SYSTEM INFORMATION IEC 61850 UCA2GenSPC
DcD000Pul DPC IEC61850 GENERIC DPC HEALTHY FAULTY IEC61850 gen DPC No 46 SYSTEM INFORMATION IEC 61850 UCA2GenDPC
Mv0000Mst MV IEC61850 GENERIC MV IEC61850 gen MV No 46 SYSTEM INFORMATION IEC 61850 UCA2GenMV
SYSTEM INFORMATION BAY OI
Iss. Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Sp0000 SPS AGENCY STATUS HEALTHY FAULTY Agency status 47 SYSTEM INFORMATION BAY OI AgencyStatus
Sp0000 SPS AUTOMATIC ARCHIVING STATUS HEALTHY FAULTY Auto archiving 47 SYSTEM INFORMATION BAY OI AutomaticArchiving
Mp0000OIHist MPS HISTORIAN DATABASE STATUS Central archive 47 SYSTEM INFORMATION BAY OI CentralArchiving
Sp0000 SPS OI SBUS LINK HEALTHY FAULTY Device link 47 SYSTEM INFORMATION BAY OI CommDevice
Sp0H00 SPS SBUS ACQUISITION STATUS HEALTHY FAULTY IEC Coupling 47 SYSTEM INFORMATION BAY OI CouplingStatus
Sp0H00 SPS LOGGING QUEUE STATUS HEALTHY FAULTY Log Queue 47 SYSTEM INFORMATION BAY OI LogQueue
Sp0HLARev SPS CONNECTION STATUS HEALTHY FAULTY OI client link 47 SYSTEM INFORMATION BAY OI CommS2K_C
Mp0HLAOpMod MPS OPERATING MODE Operating mode 47 SYSTEM INFORMATION BAY OI OperatingMode
Sp0H00 SPS REDUNDANCY MODE ACTIVE STANDBY Redundancy mode 47 SYSTEM INFORMATION BAY OI RedDevice
Sp0H00 SPS SYNCHRONIZATION STATUS HEALTHY FAULTY Synchronisation 47 SYSTEM INFORMATION BAY OI SyncDevice
Français English Spanish Português Brasil Russian German
First column to begin translation is column 5
SYSTEM INFORMATION SERVER OI SYSTEM INFORMATION SERVER OI SYSTEM INFORMATION SERVER OI SYSTEM INFORMATION SERVER OI SYSTEM INFORMATION SERVER OI SYSTEM INFORMATION SERVER OI
1 | AgencyStatus 1 | AgencyStatus 1 | AgencyStatus 1 | AgencyStatus 1 | AgencyStatus 1 | AgencyStatus
ETAT DE L'AGENCE AGENCY STATUS ESTADO AGENCY ESTADO DA AGENCY IEC СТАТУС ДРАЙВЕРА AGENCY STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Etat de l'agence Agency status Estado Agency Estado Agency Статус драйвера Agency status
1 | AutomaticArchiving 1 | AutomaticArchiving 1 | AutomaticArchiving 1 | AutomaticArchiving 1 | AutomaticArchiving 1 | AutomaticArchiving
ETAT DE L'ARCHIVAGE AUTOMATIQUE AUTOMATIC ARCHIVING STATUS ESTADO ARCHIVO AUTOMATICO ESTADO DO ARQUIVO AUTOMATICO СТАТУС АВТОМАТИЧЕСКОЙ АРХИВАЦИИ AUTOMATIC ARCHIVING STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Archivage Auto Auto archiving Archivo Auto Arquivo Auto Авто архивация Auto archiving
1 | CentralArchiving 1 | CentralArchiving 1 | CentralArchiving 1 | CentralArchiving 1 | CentralArchiving 1 | CentralArchiving
ETAT DE LA BD HISTORIAN HISTORIAN DATABASE STATUS ESTADO BASE DE DATOS HISTORIAN ESTADO BASE DE DADOS HISTORIAN Статус БД Историк HISTORIAN DATABASE STATUS
Archive Centrale Central archive Archivo Central Archivo Central Центр. архив Central archive
1 | CommDevice 1 | CommDevice 1 | CommDevice 1 | CommDevice 1 | CommDevice 1 | CommDevice
ETAT DU LIEN SBUS OI SBUS LINK ENLACE OI SBUS ESTADO DA CONEXAO SBUS СОЕДИНЕНИЕ OI и SBUS OI SBUS LINK
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien SBUS Device link Enlace SBUS Conexao SBUS Связь устройств. Device link
1 | LogQueue 1 | LogQueue 1 | LogQueue 1 | LogQueue 1 | LogQueue 1 | LogQueue
ETAT DE LA FILE D'IMPRESSION LOGGING QUEUE STATUS ESTADO COLA DE EVENTOS ESTADO DA FILA DE EVENTOS СНЯТИЕ ПОКАЗАНИЯ СТАТУСА ОЧЕРЕДИ LOGGING QUEUE STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
File impression Log Queue Cola de Eventos Fila de Eventos Лог очереди Log Queue
1 | OperatingMode 1 | OperatingMode 1 | OperatingMode 1 | OperatingMode 1 | OperatingMode 1 | OperatingMode
MODE OPERATIONNEL OPERATING MODE MODO OPERACIONAL MODO DE OPERACAO РЕЖИМ РАБОТЫ OPERATING MODE
Mode d'Operation Operating mode Modo Operacional Modo do operacao Режим работы Operating mode
1 | RedDevice 1 | RedDevice 1 | RedDevice 1 | RedDevice 1 | RedDevice 1 | RedDevice
MODE DE REDONDANCE REDUNDANCY MODE MODO REDUNDANCIA MODO REDUNDANCIA РЕЖИМ РЕЗЕРВА REDUNDANCY MODE
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
Mode Redondance Redundancy mode Modo Redundancia Modo Redundancia Режим резерва Redundanzmodus
1 | RedundancyStatus 1 | RedundancyStatus 1 | RedundancyStatus 1 | RedundancyStatus 1 | RedundancyStatus 1 | RedundancyStatus
ETAT DE REDONDANCE REDUNDANCY STATUS ESTADO REDUNDANCIA ESTADO REDUNDANCIA СТАТУС РЕЗЕРВА REDUNDANCY STATUS
Etat Redondance Redundancy status Estado Redundancia Estado Redundancia СТАТУС резерва Redundanzstatus
1 | SyncDevice 1 | SyncDevice 1 | SyncDevice 1 | SyncDevice 1 | SyncDevice 1 | SyncDevice
ETAT DE SYNCHRONISATION SYNCHRONIZATION STATUS ESTADO SINCRONIZACION ESTADO DA SINCRONIZACAO СТАТУС СИНХРОНИЗАЦИИ SYNCHRONISIERUNG STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchronisation Synchronisation Sincronización Sincronizacao Синхронизация Synchronisation
1 | CouplingStatus 1 | CouplingStatus 1 | CouplingStatus 1 | CouplingStatus 1 | CouplingStatus 1 | CouplingStatus
ETAT DU COUPLAGE AGENCE SBUS ACQUISITION STATUS ESTADO ADQUISICION SBUS ESTADO AQUISICAO SBUS SBUS СТАТУС СБОРА ДАННЫХ SBUS ACQUISITION STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Couplage IEC IEC Coupling Acople IEC Aquisicao IEC Связь с IEC IEC Coupling
1 | Printing 1 | Printing 1 | Printing 1 | Printing 1 | Printing 1 | Printing
ETAT DE L'IMPRIMANTE PRINTER STATUS ESTADO IMPRESORA ESTADO IMPRESSORA СТАТУС ПРИНТЕРА DRUCKER STATUS
Etat Imprimante Printer status Estado Impresora Estado Impresora СТАТУС ПРИНТЕРА Drucker Status
1 | BackupPrinting 1 | BackupPrinting 1 | BackupPrinting 1 | BackupPrinting 1 | BackupPrinting 1 | BackupPrinting
ETAT DE L'IMPRIMANTE DE RESERVE BACKUP PRINTER STATUS ESTADO IMPRESORA DE RESPALDO ESTADO IMPRESSORA RESERVA СТАТУС РЕЗЕРВНОГО ПРИНТЕРА RESERVE DRUCKER STATUS
Etat Imp Reserve BackupPrint stat Estado Impr.Res. Estado Impr.Res. Ст.резе.принтера Res.Druck stat
SYSTEM INFORMATION CLIENT OI SYSTEM INFORMATION CLIENT OI SYSTEM INFORMATION CLIENT OI SYSTEM INFORMATION CLIENT OI SYSTEM INFORMATION CLIENT OI SYSTEM INFORMATION CLIENT OI
2 | CommS2K_C 2 | CommS2K_C 2 | CommS2K_C 2 | CommS2K_C 2 | CommS2K_C 2 | CommS2K_C
ETAT DE LA CONNECTION CONNECTION STATUS ESTADO CONEXIÓN ESTADO DA CONEXAO СТАТУС СОЕДИНЕНИЯ VERBINDUNG STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien OI CLIENT OI client link Enlace CLIENTE Conexao CLIENTE Связь клиента OI client link
SYSTEM INFORMATION MiCOM C264 SYSTEM INFORMATION MiCOM C264 SYSTEM INFORMATION MiCOM C264 SYSTEM INFORMATION MiCOM C264 SYSTEM INFORMATION MiCOM C264 SYSTEM INFORMATION MiCOM C264
3 | DBIncoherency 3 | DBIncoherency 3 | DBIncoherency 3 | DBIncoherency 3 | DBIncoherency 3 | DBIncoherency
BD INCOHERENTE DATABASE INCONSISTENCY INCONSISTENCIA BASE DE DATOS BD INCOERENTE НЕСОВМЕСТИМОСТЬ БД DATABASE INKONSISTENZ
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
DB incoh. SPS DB incoh. SPS DB incoh. SPS DB incoh. SPS БД несовм. SPS DB incoh. SPS
3 | DBSwitch_SPC 3 | DBSwitch_SPC 3 | DBSwitch_SPC 3 | DBSwitch_SPC 3 | DBSwitch_SPC 3 | DBSwitch_SPC
PERMUTATION DE BD C264 DATABASE SWITCHING CAMBIANDO BASE DE DATOS C264 CHAVEAMENTO DE BD ПЕРЕКЛЮЧЕНИЕ БД НА С264 C264 DATABASE UMSCHALTUNG
EXECUTER EXECUTE EJECUTAR EXECUTAR ВЫПОЛНЕНИЕ AUSFÜHREN
Permutation BD DB switch ctrl Ctrl Cambio BD Chaveamento BD БД Ком переключ. DB switch ctrl
3 | CommDevice 3 | CommDevice 3 | CommDevice 3 | CommDevice 3 | CommDevice 3 | CommDevice
ETAT DU LIEN SBUS C264 SBUS LINK ENLACE C264 SBUS ESTADO DA CONEXAO SBUS СВЯЗЬ с сетью SBUS C264 SBUS LINK
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien Equipement Device link Enlace Dispo. Enlace Dispo. Связь устройств. Gerät Link
3 | DIAcquisitionStopped 3 | DIAcquisitionStopped 3 | DIAcquisitionStopped 3 | DIAcquisitionStopped 3 | DIAcquisitionStopped 3 | DIAcquisitionStopped
ACQUISITION CARTES ENTREES DIGITAL INPUT ACQUISITION ADQUISICION ENTRADAS DIGITALES AQUISICAO ENTRADAS DIGITAIS ОПРОС DI DIGITAL EINGANGSERFASSUNG
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
DI acq arrêtée DI acq stopped Adq. ED detenida Adq. ED detenida Остано.опроса DI DI acq stopped
3 | LocRemDevice_DPC 3 | LocRemDevice_DPC 3 | LocRemDevice_DPC 3 | LocRemDevice_DPC 3 | LocRemDevice_DPC 3 | LocRemDevice_DPC
CHANGEMENT MODE DE CONTRÔLE C264 C264 BAYS CONTROL MODE CHANGE CAMBIO MODO CONTROL BAHIAS C264 CHAVEAR MODO DE CONTROLE DA C264 ИЗМЕНЕНИЕ РЕЖИМА УПРАВЛЕНИЯ ЯЧЕЙКАМИ С264 C264 BAYS CONTROL MODE CHANGE
DISTANT REMOTE REMOTO REMOTO ДИСТАНЦИОННЫЙ FERN
LOCAL LOCAL LOCAL LOCAL МЕСТНЫЙ LOKAL
Loc/Dst ctrl DPC Loc/rem ctrl DPC Loc/rem ctrl DPC Loc/rem ctrl DPC Мес/Дист ком DPC Loc/rem ctrl DPC
3 | LocRemDevice 3 | LocRemDevice 3 | LocRemDevice 3 | LocRemDevice 3 | LocRemDevice 3 | LocRemDevice
ETAT DU MODE DE CONTRÔLE C264 C264 MANAGED BAYS IN CONTROL MODE BAHIAS DEL C264 EN MODO CONTROL MODO DE CONTROLE DA C264 С264 ОБСЛУЖИВАЕТ ЯЧЕЙКИ В РЕЖИМЕ УПРАВЛЕНИЯ C264 MANAGED BAYS IN CONTROL MODE
DISTANT REMOTE REMOTO REMOTO ДИСТАНЦИОННЫЙ FERN
LOCAL LOCAL LOCAL LOCAL МЕСТНЫЙ LOKAL
Local/Dist DPS Local/remote DPS Local/remoto DPS Local/remoto DPS Мес/Дист ком DPS Fern/Lokal Sps
3 | LocRemDeviceForIEC 3 | LocRemDeviceForIEC 3 | LocRemDeviceForIEC 3 | LocRemDeviceForIEC 3 | LocRemDeviceForIEC 3 | LocRemDeviceForIEC
ETAT DU MODE DE CONTRÔLE C264 C264 BAYS IN CONTROL MODE BAHIAS C264 EN MODO CONTROL MODO DE CONTROLE DA C264 РЕЖИМ УПРАВЛЕНИЯ ЯЧЕЙКАМИ С264 C264 FELDSTEUERMODUS
DISTANT REMOTE REMOTO REMOTO ДИСТАНЦИОННЫЙ FERN
LOCAL LOCAL LOCAL LOCAL МЕСТНЫЙ LOKAL
Local/Dist SPS Local/remote SPS Local/remoto SPS Local/remoto SPS Мес/Дист ком SPS Fern/Lokal SPS
3 | MainInternalStatus 3 | MainInternalStatus 3 | MainInternalStatus 3 | MainInternalStatus 3 | MainInternalStatus 3 | MainInternalStatus
NIVEAU DU DEFAUT C264 POUR REDONDANCE C264 FAULT LEVEL FOR REDUNDANCY C264 NIVEL DE FALLA PARA REDUNDANCIA NIVEL DE DEFEITO DA C264 P/ REDUNDANCIA C264 Вины уровня избыточности C264 FEHLERLEVEL REDUNDANZ
Etat Princial MV Main status MV Estado Princ MV Estado Princ MV Основной статус Main status MV
3 | ModeDevice_DPC 3 | ModeDevice_DPC 3 | ModeDevice_DPC 3 | ModeDevice_DPC 3 | ModeDevice_DPC 3 | ModeDevice_DPC
CHANGER LE MODE D'EXPLOITATION C264 FORCE OPERATION MODE TO FORZAR C264 MODO DE OPERACIÓN A CHAVEAR MODO DE OPERACAO C264 Силу режиме для C264 SETZE GERÄTEMODUS IN
OPERATIONNEL OPERATIONNAL OPERACIONAL OPERACIONAL В РАБОТЕ BERTIEBSMODUS
MAINTENANCE MAINTENANCE MANTENIMIENTO MANUTENCAO ОБСЛУЖИВАНИЕ WARTUNG
Mode ctrl DPC Mode control DPC Modo control DPC Modo control DPC Команда режима MODUS UMSCHALT
3 | OperatingMode 3 | OperatingMode 3 | OperatingMode 3 | OperatingMode 3 | OperatingMode 3 | OperatingMode
MODE OPERATIONNEL C264 OPERATING MODE C264 MODO OPERACIÓN MODO DE OPERACAO Режим работы C264 C264 BETRIEBSMODUS
Mode d'Operation Operating mode Modo Operacional Modo do operacao Режим работы Operating mode
3 | RedChangeMode_SPC 3 | RedChangeMode_SPC 3 | RedChangeMode_SPC 3 | RedChangeMode_SPC 3 | RedChangeMode_SPC 3 | RedChangeMode_SPC
RELAIS DE REDONDANCE BIU CO2 C264 BIU REDUNDANCY RELAY CO 2 C264 BIU RELE REDUNDANCIA CO 2 C264 BIU RELE REDUNDANCIA CO 2 C264 BIU Pезервирования Pелейной CO 2 C264 BIU REDUNDANZ RELAIS CO 2
ACTIVER ACTIVATE ACTIVAR ATIVAR АКТИВНО AKTIVIERE
DESACTIVER DEACTIVATE DESACTIVAR DESATIVAR НЕАКТИВНО DEAKTIVIERE
Mode Ctrl Red Red mode ctrl Ctrl Modo Red. Ctrl Modo Red. управ.режи.резер Red Mod Befehl
3 | RedChangeStatus_SPC 3 | RedChangeStatus_SPC 3 | RedChangeStatus_SPC 3 | RedChangeStatus_SPC 3 | RedChangeStatus_SPC 3 | RedChangeStatus_SPC
RELAIS DE REDONDANCE BIU CO1 C264 BIU REDUNDANCY RELAY CO 1 C264 BIU RELE REDUNDANCIA CO 1 C264 BIU RELE REDUNDANCIA CO 1 C264 BIU Pезервирования Pелейной CO 1 C264 BIU REDUNDANZ RELAIS CO 1
ACTIVER ACTIVATE ACTIVAR ATIVAR АКТИВНО AKTIVIERE
DESACTIVER DEACTIVATE DESACTIVAR DESATIVAR НЕАКТИВНО DEAKTIVIERE
Etat Ctrl Red Red Status ctrl Ctrl Estado Red. Ctrl Estado Red. Управ.стат.резер Red Mod Befehl
3 | RedChangeMode 3 | RedChangeMode 3 | RedChangeMode 3 | RedChangeMode 3 | RedChangeMode 3 | RedChangeMode
MODE DE REDONDANCE REDUNDANT C264 CHANGE MODE MODO REDUNDANCIA C264 MODO DA REDUNDANCIA Режим РЕЗЕРВНОГО C264 RESERVE C264 MODE
ACTIF ACTIVE ACTIVA ATIVO ОСНОВНОЙ ACTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
Mode Chgt Red Red. change mode Mod. Cambio Red. Mod. Cambio Red. Реж.перек.резер Red. Änderung Md
3 | RedChangeStatus 3 | RedChangeStatus 3 | RedChangeStatus 3 | RedChangeStatus 3 | RedChangeStatus 3 | RedChangeStatus
ETAT DE REDONDANCE REDUNDANT C264 STATUS ESTADO REDUNDANCIA C264 ESTADO DA REDUNDANCIA СТАТУС РЕЗЕРВНОГО C264 RESERVE C264 STATUS
ACTIF ACTIVE ACTIVA ATIVO ОСНОВНОЙ ACTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
Etat Chgt Red Red. change stat Est. Cambio Red. Est. Cambio Red. Стат.перек.резер Red. Änderung St
3 | SoftError 3 | SoftError 3 | SoftError 3 | SoftError 3 | SoftError 3 | SoftError
ERREUR LOGICIELLE DETECTEE SOFTWARE ERROR DETECTED ERROR DETECTADO SOFTWARE ERRO DE SOFTWARE DETECTADO ОБНАРУЖЕНА ОШИБКА ПО SOFTWAREFEHLER
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Err. Logicielle Soft. error SPS Error Soft. SPS Soft. error SPS Ошибка по SPS Softwarefehler
3 | SyncDevice 3 | SyncDevice 3 | SyncDevice 3 | SyncDevice 3 | SyncDevice 3 | SyncDevice
ETAT DE SYNCHRONISATION C264 SYNCHRONIZATION STATUS ESATDO SINCRONIZACION C264 ESTADO DA SINCRONIZACAO СТАТУС СИНХРОНИЗАЦИИ C264 C264 SYNCHRONISIERUNG STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchronisation Synchronisation Sincronización Sincronizacao Синхронизация Synchronisation
3 | TestDevice_DPC 3 | TestDevice_DPC 3 | TestDevice_DPC 3 | TestDevice_DPC 3 | TestDevice_DPC 3 | TestDevice_DPC
CHANGEMENT MODE EXPLOITATION C264 CHANGE EXPLOITATION MODE CAMBIO MODO EXPLOTACION C264 CHAVEAR MODO DE OPERACAO Смена режима работы C264 C264 TESTMODUS UMSCHALT
OPERATIONNEL NORMAL NORMAL OPERACIONAM НОРМАЛЬНЫЙ NORMAL
TEST TEST PRUEBA TESTE ТЕСТОВОЙ TEST
Ctrl Test DPC Test control DPC Ctrl Prueba DPC Ctrl Prueba DPC ком Тестов. DPC Testmodus DPC
3 | WatchdogError 3 | WatchdogError 3 | WatchdogError 3 | WatchdogError 3 | WatchdogError 3 | WatchdogError
ETAT DU CHIEN DE GARDE C264 C264 WATCHDOG RELAY STATUS ESTADO RELE WATCHDOG C264 ESTADO RELE WATCHDOG C264 СТАТУС WATCHDOG C264 C264 WATCHDOG RELAIS STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA ATIVO НЕИСПРАВНЫЙ FEHLER
Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS
3 | ModeDevice 3 | ModeDevice 3 | ModeDevice 3 | ModeDevice 3 | ModeDevice 3 | ModeDevice
V3 MODE OPERATIONNEL C264 OPERATING MODE C264 MODO OPERACIÓN DISPOSITIVO V3 MODO DE OPERACAO РЕЖИМ РАБОТЫ C264 C264 BETRIEBSMODUS
OPERATIONNEL RUNNING EN SERVICIO EM SERVICO Рабочее BETRIEB
MAINTENANCE MAINTENANCE MANTENIMIENTO MANUTENCAO ОБСЛУЖИВАНИЕ WARTUNG
Mode Eqpt Device mode Modo Dispositivo Modo Dispositivo Режим устройства Gerätemodus
3 | DisturbUCA2 3 | DisturbUCA2 3 | DisturbUCA2 3 | DisturbUCA2 3 | DisturbUCA2 3 | DisturbUCA2
FICHIER DE PERTURBOGRAPHIE C264 DISTURBANCE FILE ON C264 ARCHIVO DE DISTURBIO EN C264 ARQUIVO DE OSCILOGRAFIA C264 ФАЙЛ ОСЦИЛОГРАМ НА C264 STÖRFALLDATEI AUF C264
PRÊT READY LISTO PRONTO ГОТОВ BEREIT
ABSENT NOT READY NO LISTO AUSENTE НЕ ГОТОВ NICHT BEREIT
DREC prêt DREC ready DREC Listo DREC Pronto DREC готов DREC ready
3 | CounterTop 3 | CounterTop 3 | CounterTop 3 | CounterTop 3 | CounterTop 3 | CounterTop
DEMARRAGE DU COMPTAGE C264 COUNTERS ACQUISITION TOP ADQ MAX CONTADORES C264 CONTAGEM PARTIDA Счетчик C264 макс C264 ZÄHLERSTAND MAX
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Max Compteur Counter Top Max Contadores Max Contagem Счетчик макс Zähler max
3 | ExtClockStatus 3 | ExtClockStatus 3 | ExtClockStatus 3 | ExtClockStatus 3 | ExtClockStatus 3 | ExtClockStatus
ETAT DE LA SOURCE DE SYNCHRONISATION GPS SYNCHRONISATION SOURCE FUENTE SINCRONIZACION GPS FONTE SINCRONIZACAO GPS GPS ИСТОЧНИК СИНХРОНИЗАЦИИ GPS SYNCHRONISIERUNG QUELLE
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Etat Horloge Ext clock status Estado Reloj GPS Estado Reloj GPS Статус IRIG-B Ext Uhr Status
3 | RedDevice 3 | RedDevice 3 | RedDevice 3 | RedDevice 3 | RedDevice 3 | RedDevice
MODE DE REDONDANCE C264 REDUNDANCY MODE MODO REDUNDANCIA C264 MODO REDUNDANCIA C264 C264 Режим резервирования C264 REDUNDANZ MODUS
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
Mode Redondance Redundancy mode Modo Redundancia Modo Redundancia Режим резерва Redundanzmodus
3 | BuffOvGtw1 3 | BuffOvGtw1 3 | BuffOvGtw1 3 | BuffOvGtw1 3 | BuffOvGtw1 3 | BuffOvGtw1
DEBORDEMENT DE TAMPON GTW 1 REPORT BUFFER OVERFLOW GTW 1 DESBORDAMIENTO DE BUFER GTW 1 DESBORDAMIENTO DE BUFER GTW 1 Переполнение буфера GTW 1 Pufferüberlauf GTW 1
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Débord. Tampon Gtw 1 Buff Ov Gtw 1 Desbord. Búfer Gtw 1 Desbord. Búfer Gtw 1 Переп. Буфера Gtw 1 Pufferüberlauf Gtw 1
3 | BuffOvGtw2 3 | BuffOvGtw2 3 | BuffOvGtw2 3 | BuffOvGtw2 3 | BuffOvGtw2 3 | BuffOvGtw2
DEBORDEMENT DE TAMPON GTW 2 REPORT BUFFER OVERFLOW GTW 2 DESBORDAMIENTO DE BUFER GTW 2 DESBORDAMIENTO DE BUFER GTW 2 Переполнение буфера GTW 2 Pufferüberlauf GTW 2
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Débord. Tampon OI Buff Ov Gtw 2 Desbord. Búfer Gtw 2 Desbord. Búfer Gtw 2 Переп. Буфера Gtw 2 Pufferüberlauf Gtw 2
3 | BuffOvOI 3 | BuffOvOI 3 | BuffOvOI 3 | BuffOvOI 3 | BuffOvOI 3 | BuffOvOI
DEBORDEMENT DE TAMPON OI REPORT BUFFER OVERFLOW OI DESBORDAMIENTO DE BUFER OI DESBORDAMIENTO DE BUFER OI Переполнение буфера OI Pufferüberlauf OI
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Débord. Tampon Oi Buff Ov Oi Desbord. Búfer Oi Desbord. Búfer Oi Переп. Буфера Oi Pufferüberlauf Oi
3 | BuffOvOIBck 3 | BuffOvOIBck 3 | BuffOvOI Bck 3 | BuffOvOIBck 3 | BuffOvOIBck 3 | BuffOvOIBck
DEBORDEMENT DE TAMPON OI BACKUP REPORT BUFFER OVERFLOW OI BACKUP DESBORDAMIENTO DE BUFER OI BACKUP DESBORDAMIENTO DE BUFER OI BACKUP Переполнение буфера OI BACKUP Pufferüberlauf OI BACKUP
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Débord. Tampon Oi Bck Buff Ov Oi Bck Desbord. Búfer Oi Bck Desbord. Búfer Oi Bck Переп. Буфера Oi Bck Pufferüberlauf Oi Bck
3 | BIUStatus 3 | BIUStatus 3 | BIUStatus 3 | BIUStatus 3 | BIUStatus 3 | BIUStatus
ETAT DE LA CARTE BIU BIU BOARD STATUS ESTADO TARJETA BIU ESTADO DO CARTAO BIU СТАТУС ПЛАТЫ BIU BIU KARTEN STATUS
Etat BIU BIU status Estado BIU Estado BIU BIU статус BIU status
3 | GHUStatus 3 | GHUStatus 3 | GHUStatus 3 | GHUStatus 3 | GHUStatus 3 | GHUStatus
ETAT DE LA CARTE GHU GHU BOARD STATUS ESTADO TARJETA GHU ESTADO DO CARTAO GHU GHU СТАТУС ПЛАТЫ GHU KARTEN STATUS
Etat GHU GHU status Estado GHU Estado GHU GHU статус GHU status
3 | AIUStatus 3 | AIUStatus 3 | AIUStatus 3 | AIUStatus 3 | AIUStatus 3 | AIUStatus
ETAT DE LA CARTE AIU20x AIU20x BOARD STATUS ESTADO TARJETA AIU20x ESTADO DO CARTAO AIU20x AIU20x СТАТУС ПЛАТЫ AIU20x KARTEN STATUS
Etat AIU AIU status Estado AIU Estado AIU AIU статус AIU status
3 | AIUStatus 3 | AIUStatus 3 | AIUStatus 3 | AIUStatus 3 | AIUStatus 3 | AIUStatus
ETAT DE LA CARTE AIU21x AIU21x BOARD STATUS ESTADO TARJETA AIU21x ESTADO DO CARTAO AIU21x AIU21x СТАТУС ПЛАТЫ AIU21x KARTEN STATUS
Etat AIU AIU status Estado AIU Estado AIU AIU статус AIU status
3 | AOUStatus 3 | AOUStatus 3 | AOUStatus 3 | AOUStatus 3 | AOUStatus 3 | AOUStatus
ETAT DE LA CARTE AOU200 AOU200 BOARD STATUS ESTADO TARJETA AOU200 ESTADO DO CARTAO AOU200 AOU200 СТАТУС ПЛАТЫ AOU200 KARTEN STATUS
Etat AOU AOU status Estado AOU Estado AOU AOU статус AOU status
3 | DIUStatus 3 | DIUStatus 3 | DIUStatus 3 | DIUStatus 3 | DIUStatus 3 | DIUStatus
ETAT DE LA CARTE DIU DIU BOARD STATUS ESTADO TARJETA DIU ESTADO DO CARTAO DIU DIU СТАТУС ПЛАТЫ DIU KARTEN STATUS
Etat DIU DIU status Estado DIU Estado DIU DIU статус DIU status
3 | DOUStatus 3 | DOUStatus 3 | DOUStatus 3 | DOUStatus 3 | DOUStatus 3 | DOUStatus
ETAT DE LA CARTE DOU DOU BOARD STATUS ESTADO TARJETA DOU ESTADO DO CARTAO DOU DOU СТАТУС ПЛАТЫ DOU KARTEN STATUS
Etat DOU DOU status Estado DOU Estado DOU DOU статус DOU status
3 | CCUStatus 3 | CCUStatus 3 | CCUStatus 3 | CCUStatus 3 | CCUStatus 3 | CCUStatus
ETAT DE LA CARTE CCU CCU BOARD STATUS ESTADO TARJETA CCU ESTADO DO CARTAO CCU CCU СТАТУС ПЛАТЫ CCU KARTEN STATUS
Etat CCU CCU status Estado CCU Estado CCU CCU статус CCU status
3 | TIUStatus 3 | TIUStatus 3 | TIUStatus 3 | TIUStatus 3 | TIUStatus 3 | TIUStatus
ETAT DE LA CARTE TMU TMU BOARD STATUS ESTADO TARJETA TMU ESTADO DO CARTAO TMU TMU СТАТУС ПЛАТЫ TMU KARTEN STATUS
Etat TMU TMU status Estado TMU Estado TMU TMU статус TMU status
3 | HBUStatus 3 | HBUStatus 3 HBUStatus 3 | HBUStatus 3 |HBUStatus 3 |HBUStatus
ETAT DE LA CARTE HBU HBU BOARD STATUS ESTADO TARJETA HBU ESTADO DO CARTAO HBU HBU СТАТУС ПЛАТЫ HBU KARTEN STATUS
Etat HBU HBU status Estado HBU Estado HBU HBU статус HBU status
3 | CommIED 3 | CommIED 3 | CommIED 3 | CommIED 3 | CommIED 3 | CommIED
ETAT DE LA CONNECTION AU C264 IED CONNECTION STATUS TO C264 ESTADO COMUNICACIÓN IED AL C264 ESTADO DA CONEXAO COM A C264 СТАТУС СВЯЗИ IED С С264 IED VERBINDUNGSSTATUS C264
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Com. IED SPS IED SPS com. IED SPS com. IED SPS com. IED SPS связь. IED SPS com.
3 | SyncIED 3 | SyncIED 3 | SyncIED 3 | SyncIED 3 | SyncIED 3 | SyncIED
ETAT DE LA SYNCHRONISATION DE L'IED IED SYNCHRONISATION STATUS ESTADO SINCRONIZACION IED ESTADO DA SINCRONIZACAO DO RELE IED СТАТУС СИНХРОНИЗАЦИИ IED SYNCHRONISIERUNGSSTATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchro. IED SPS IED SPS Synchro. IED SPS Sincro. IED SPS Sincro. IED SPS синхр. IED SPS Synchro.
3 | DisturbIED 3 | DisturbIED 3 | DisturbIED 3 | DisturbIED 3 | DisturbIED 3 | DisturbIED
FICHIER DE PERTURBOGRAPHIE IED IED DISTURBANCE FILE ARCHIVO DE DISTURBIO EN IED ARQUIVO DE OSCILOGRAFIA IED IED ФАЙЛ ОСЦИЛОГРАМ IED DISTURBANCE FILE
PRÊT READY LISTO PRONTO ГОТОВ BEREIT
ABSENT NOT READY NO LISTO AUSENTE НЕ ГОТОВ NICHT BEREIT
IED DREC Prêt IED DREC ready IED DREC Listo IED DREC Pronto IED DRECготов IED DREC ready
3 | ISAGRAFStatus 3 | ISAGRAFStatus 3 | ISAGRAFStatus 3 | ISAGRAFStatus 3 | ISAGRAFStatus 3 | ISAGRAFStatus
ETAT ISAGRAF ISAGRAF STATUS ESTADO ISAGRAF ESTADO ISAGRAF ISAGRAF статус ISAGRAF STATUS
Etat ISAGRAF ISAGRAF status Estado ISAGRAF Estado ISAGRAF ISAGRAF статус ISAGRAF status
3 | PrinterStatus 3 | PrinterStatus 3 | PrinterStatus 3 | PrinterStatus 3 | PrinterStatus 3 | PrinterStatus
PRINTER STATUS DPS PRINTER STATUS DPS DPS ESTADO IMPRESORA DPS ESTADO IMPRESSORA СТАТУС ПРИНТЕРА DPS DRUCKER STATUS DPS
Etat Impr. DPS Printer st. DPS Edo. Impr. DPS Edo. Impr. DPS стат принт DPS Druckerstat. DPS
3 | Printing 3 | Printing 3 | Printing 3 | Printing 3 | Printing 3 | Printing
ETAT DE L'IMPRIMANTE LOCAL LOCAL PRINTER STATUS ESTADO IMPRESORA LOCAL ESTADO IMPRESSORA LOCAL СТАТУС ПРИНТЕРА LOKAL DRUCKER STATUS
Etat Imprimante Printer Status Edo. Impresora Edo. Impressora статус принтера Drucker Status
3 | RedSCADA 3 | RedSCADA 3 | RedSCADA 3 | RedSCADA 3 | RedSCADA 3 | RedSCADA
PORT DE COMMUNICATION AVEC LE SCADA C264 SCADA PORT COMMUNICATION PTO. COM C264 SCADA CANAL DE COMUNICACAO C/ SCADA СТАТУС ПОРТА СВЯЗЬ C264 с SCADA C264 FWL PORT KOMMUNIKATION
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
SPS Redondance Redundancy SPS Redundancia SPS Redundancia SPS резервирование Redundancy SPS
3 | CommSCADA 3 | CommSCADA 3 | CommSCADA 3 | CommSCADA 3 | CommSCADA 3 | CommSCADA
ETAT DE LA COMMUNICATION SCADA SCADA CONNECTION STATUS TO C264 EDO. CONEXIÓN SCADA AL C264 ESTADO DA CONEXAO C/ SCADA СТАТУС СОЕДИНЕНИЯ SCADA С C264 FWL VERBINDUNGSSTATUS C264
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Com. SCADA SPS SCADA SPS com. SCADA SPS com. SCADA SPS com. SCADA SPS связь FWL SPS KOMMU
3 | GlobalAIUStatus 3 | GlobalAIUStatus 3 | GlobalAIUStatus 3 | GlobalAIUStatus 3 | GlobalAIUStatus 3 | GlobalAIUStatus
TOUS LES ETATS AIU ALL AIU STATUS TODOS LOS AIU ESTADO AIU TODO ESTADO ВСЕ AIU СТАТУС ALLE AIU STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états AIU All AIU status Todos AIU estado AIU todo estado Все AIU статус Alle AIU Status
3 | GlobalAOUStatus 3 | GlobalAOUStatus 3 | GlobalAOUStatus 3 | GlobalAOUStatus 3 | GlobalAOUStatus 3 | GlobalAOUStatus
TOUS LES ETATS AOU ALL AOU STATUS TODOS LOS AOU ESTADO AOU TODO ESTADO ВСЕ АOU СТАТУС ALLE AOU STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états AOU All AOU status Todos AOU estado AOU todo estado Все AOU статус Alle AOU Status
3 | GlobalCCUStatus 3 | GlobalCCUStatus 3 | GlobalCCUStatus 3 | GlobalCCUStatus 3 | GlobalCCUStatus 3 | GlobalCCUStatus
TOUS LES ETATS CCU ALL CCU STATUS TODOS LOS CCU ESTADO CCU TODO ESTADO ВСЕ CCU СТАТУС ALLE CCU STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états CCU All CCU status Todos CCU estado CCU todo estado Все CCU статус Alle CCU Status
3 | GlobalDIUStatus 3 | GlobalDIUStatus 3 | GlobalDIUStatus 3 | GlobalDIUStatus 3 | GlobalDIUStatus 3 | GlobalDIUStatus
TOUS LES ETATS DIU ALL DIU STATUS TODOS LOS DIU ESTADO DIU TODO ESTADO ВСЕ DIU СТАТУС ALLE DIU STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états DIU All DIU status Todos DIU estado DIU todo estado Все DIU статус Alle DIU Status
3 | GlobalDOUStatus 3 | GlobalDOUStatus 3 | GlobalDOUStatus 3 | GlobalDOUStatus 3 | GlobalDOUStatus 3 | GlobalDOUStatus
TOUS LES ETATS DOU ALL DOU STATUS TODOS LOS DOU ESTADO DOU TODO ESTADO ВСЕ DOU СТАТУС ALLE DOU STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états DOU All DOU status Todos DOU estado DOU todo estado Все DOU статус Alle DOU Status
3 | GlobalTMUStatus 3 | GlobalTMUStatus 3 | GlobalTMUStatus 3 | GlobalTMUStatus 3 | GlobalTMUStatus 3 | GlobalTMUStatus
TOUS LES ETATS TMU ALL TMU STATUS TODOS LOS TMU ESTADO TMU TODO ESTADO ВСЕ TMU СТАТУС ALLE TMU STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états TMU All TMU status Todos TMU estado TMU todo estado Все TMU статус Alle TMU Status
3 | GlobalHBUStatus 3 | GlobaHBMUStatus 3 | GlobalHBUStatus 3 | GlobalHBUStatus 3 | GlobalHBUStatus 3 | GlobalHBUStatus
TOUS LES ETATS HBU ALL HBU STATUS TODOS LOS HBU ESTADO HBU TODO ESTADO ВСЕ HBU СТАТУС ALLE HBU STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états HBU All HBU status Todos HBU estado HBU todo estado Все HBU статус Alle HBU Status
3 | GlobalIEDStatus 3 | GlobalIEDStatus 3 | GlobalIEDStatus 3 | GlobalIEDStatus 3 | GlobalIEDStatus 3 | GlobalIEDStatus
TOUS LES ETATS IED ALL IED STATUS TODOS LOS IED ESTADO IED TODO ESTADO ВСЕ IED СТАТУС ALLE IED STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états IED All IED status Todos IED estado IED todo estado Все IED статус Alle IED Status
3 | GlobalPrinterStatus 3 | GlobalPrinterStatus 3 | GlobalPrinterStatus 3 | GlobalPrinterStatus 3 | GlobalPrinterStatus 3 | GlobalPrinterStatus
TOUS LES ETATS D'IMPRIMANTES ALL Printer STATUS TODOS LOS IMPRESSORA ESTADO IMPRESSORA TODO ESTADO ВСЕ ПРИНТЕР СТАТУС ALLE DRUCKER-STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états Impr. All Printer stat Todos Imp.estado Todos Imp.estado Все Принтер стат Alle Druck.Status
3 | GlobalRackLinkStatus 3 | GlobalRackLinkStatus 3 | GlobalRackLinkStatus 3 | GlobalRackLinkStatus 3 | GlobalRackLinkStatus 3 | GlobalRackLinkStatus
TOUS LES ETATS RACK ALL RACK STATUS TODOS LOS RACK ESTADO RACK TODO ESTADO ВСЕ RACK СТАТУС ALLE RACK STATUS
ARRETEE FAULTY PARADO PARADA ИСПРАВНЫЙ FEHLER
NORMAL HEALTHY CORRECTO NORMAL НЕИСПРАВНЫЙ BETRIEB
Tous états rack All rack status Todos rack estado rack todo estado Все rack статус Alle rack status
3 | RackLinkStatus 3 | RackLinkStatus 3 | RackLinkStatus 3 | RackLinkStatus 3 | RackLinkStatus 3 | RackLinkStatus
ETAT DU LIEN RACK RACK LINK STATUS RACK DE ENLACE DE ESTADO RACK LINK ESTADO RACK СТАТУС RACK LINK STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Etat lien Rack Rack link status Rack estado Rack estado Rack статус Rack link status
3 | LocalAlarmAck_SPS 3 | LocalAlarmAck_SPS 3 | LocalAlarmAck_SPS 3 | LocalAlarmAck_SPS 3 | LocalAlarmAck_SPS 3 | LocalAlarmAck_SPS
ACQUITTEMENT ALARME LOCALE LOCAL ALARM ACKNOWLEDGEMENT RECONOCIMIENTO DE ALARMA LOCAL LOCAIS ALARME AVISO МЕСТНЫЕ СИГНАЛА ПОДТВЕРЖДЕНИЯ LOKALEN ALARM ANERKENNUNG
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Acq. Alarm loc Local alarm ack Recon Alarma loc Loc Alarme aviso Mес Сигнала подт Zähler max
3 | SettingDone 3 | SettingDone 3 | SettingDone 3 | SettingDone 3 | SettingDone 3 | SettingDone
PARAMETRAGE EFFECTUE SETTING DONE AJUSTE DE HECHO DEFINIR FEITO НАСТРОЙКА ДЕЛАЕТСЯ EINSTELLUNG ERFOLGT
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Parametrage fait Setting done Ajuste de hecho Definir feito Настр делается Einst. Erfolgt
3 | SettingFileDiscordance 3 | SettingFileDiscordance 3 | SettingFileDiscordance 3 | SettingFileDiscordance 3 | SettingFileDiscordance 3 | SettingFileDiscordance
DISCORDANCE FICHIER PARAMETRAGE SETTING FILE DISCORDANCE ARCHIVO DE CONFIGURACION DISCORDANCIA DEFINIÇÃO ARQUIVO DISCORDANCIA НАСТРОЙКА ФАЙЛОВ РАЗНОГОЛОСИЦА EINSTELLUNG DATEI DISSONANZ
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Disc.fich.param Setting disc. Arch.Conf.Disc. Def.Arquivo Disc Настр файлов раз Einst.Dat.Diss.
3 | SettingInProgress 3 | SettingInProgress 3 | SettingInProgress 3 | SettingInProgress 3 | SettingInProgress 3 | SettingInProgress
PARAMETRAGE EN COURS SETTING IN PROGRESS AJUSTE EN MARCHA DEFINIR EM ANDAMENTO УСТАНОВЛЕНИЕ В ХОДЕ EINSTELLUNG IN PROGRESS
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Param en cours Setting in prog. Ajuste en marcha Definir em Andam Устан В Ходе Einst. In prog.
3 | SettingIncoherency 3 | SettingIncoherency 3 | SettingIncoherency 3 | SettingIncoherency 3 | SettingIncoherency 3 | SettingIncoherency
PARAMETRAGE INCOHERENT SETTING INCOHERENCY AJUSTE INCOHERENCY DEFINIR INCOHERENCY УСТАНОВЛЕНИЕ НЕПОСЛЕДОВАТЕЛЬНОСТЬ EINSTELLUNG INCOHERENCY
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Param Invalide Setting incoher. Ajuste incoher. Definir incoher. Устан Непосл Einst. Incoher.
SYSTEM INFORMATION MiCOM C364 SYSTEM INFORMATION MiCOM C364 SYSTEM INFORMATION MiCOM C364 SYSTEM INFORMATION MiCOM C364 SYSTEM INFORMATION MiCOM C364 SYSTEM INFORMATION MiCOM C364
4 | DBIncoherency 4 | DBIncoherency 4 | DBIncoherency 4 | DBIncoherency 4 | DBIncoherency 4 | DBIncoherency
BD INCOHERENTE DATABASE INCONSISTENCY INCONSISTENCIA BASE DE DATOS BD INCOERENTE НЕСОВМЕСТИМОСТЬ БД DATENBANK INKONSISTENZ
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
DB incoh. SPS DB incoh. SPS DB incoh. SPS DB incoh. SPS БД несовм. SPS DB Inkonsistenz
4 | DBSwitch_SPC 4 | DBSwitch_SPC 4 | DBSwitch_SPC 4 | DBSwitch_SPC 4 | DBSwitch_SPC 4 | DBSwitch_SPC
PERMUTATION DE BD C364 C364 DATABASE SWITCHING CAMBIANDO BASE DE DATOS C364 CHAVEAMENTO DE BD C364 ПЕРЕКЛЮЧЕНИЕ БД НА С364 C364 DATABASE UMSCHALTUNG
EXECUTER EXECUTE EJECUTAR EXECUTAR ВЫПОЛНЕНИЕ AUSFÜHREN
Permutation BD DB switch ctrl Ctrl Cambio BD Chaveamento BD БД Ком переключ. DB switch ctrl
4 | CommDevice 4 | CommDevice 4 | CommDevice 4 | CommDevice 4 | CommDevice 4 | CommDevice
ETAT DU LIEN SBUS C364 SBUS LINK ENLACE C364 SBUS ESTADO DA CONEXAO SBUS СВЯЗЬ с сетью SBUS C364 SBUS LINK
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien Equipement Device link Enlace Dispo. Enlace Dispo. Связь устройств. Gerät Link
4 | LocRemDevice_DPC 4 | LocRemDevice_DPC 4 | LocRemDevice_DPC 4 | LocRemDevice_DPC 4 | LocRemDevice_DPC 4 | LocRemDevice_DPC
CHANGEMENT MODE DE CONTRÔLE C364 C364 BAYS CONTROL MODE CHANGE CAMBIO MODO CONTROL BAHIAS C364 CHAVEAR MODO DE CONTROLE DA C364 ИЗМЕНЕНИЕ РЕЖИМА УПРАВЛЕНИЯ ЯЧЕЙКАМИ С264 C364 BAYS CONTROL MODE CHANGE
DISTANT REMOTE REMOTO REMOTO ДИСТАНЦИОННЫЙ FERN
LOCAL LOCAL LOCAL LOCAL МЕСТНЫЙ LOKAL
Loc/Dst ctrl DPC Loc/rem ctrl DPC Loc/rem ctrl DPC Loc/rem ctrl DPC Мес/Дист ком DPC Loc/rem ctrl DPC
4 | LocRemDevice 4 | LocRemDevice 4 | LocRemDevice 4 | LocRemDevice 4 | LocRemDevice 4 | LocRemDevice
ETAT DU MODE DE CONTRÔLE C364 C364 MANAGED BAYS IN CONTROL MODE BAHIAS DEL C364 EN MODO CONTROL MODO DE CONTROLE DA C364 С264 ОБСЛУЖИВАЕТ ЯЧЕЙКИ В РЕЖИМЕ УПРАВЛЕНИЯ C364 MANAGED BAYS IN CONTROL MODE
DISTANT REMOTE REMOTO REMOTO ДИСТАНЦИОННЫЙ FERN
LOCAL LOCAL LOCAL LOCAL МЕСТНЫЙ LOKAL
Local/Dist DPS Local/remote DPS Local/remoto DPS Local/remoto DPS Мес/Дист ком DPS Fern/Lokal Sps
4 | LocRemDeviceForIEC 4 | LocRemDeviceForIEC 4 | LocRemDeviceForIEC 4 | LocRemDeviceForIEC 4 | LocRemDeviceForIEC 4 | LocRemDeviceForIEC
ETAT DU MODE DE CONTRÔLE C364 C364 BAYS IN CONTROL MODE BAHIAS C364 EN MODO CONTROL MODO DE CONTROLE DA C364 РЕЖИМ УПРАВЛЕНИЯ ЯЧЕЙКАМИ С264 C364 FELDSTEUERMODUS
DISTANT REMOTE REMOTO REMOTO ДИСТАНЦИОННЫЙ FERN
LOCAL LOCAL LOCAL LOCAL МЕСТНЫЙ LOKAL
Local/Dist SPS Local/remote SPS Local/remoto SPS Local/remoto SPS Мес/Дист ком SPS Fern/Lokal SPS
4 | LogQueue 4 | LogQueue 4 | LogQueue 4 | LogQueue 4 | LogQueue 4 | LogQueue
ETAT DE LA FILE D'IMPRESSION LOGGING QUEUE STATUS ESTADO COLA DE EVENTOS ESTADO DA FILA DE EVENTOS СНЯТИЕ ПОКАЗАНИЯ СТАТУСА ОЧЕРЕДИ LOGGING QUEUE STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
File impression Log Queue Cola de Eventos Fila de Eventos Лог очереди Log Queue
4 | ModeDevice_DPC 4 | ModeDevice_DPC 4 | ModeDevice_DPC 4 | ModeDevice_DPC 4 | ModeDevice_DPC 4 | ModeDevice_DPC
CHANGER LE MODE D'EXPLOITATION C364 C364 FORCE OPERATION MODE TO FORZAR C364 MODO DE OPERACIÓN A CHAVEAR C364 MODO DE OPERACAO C364 Силу режиме для C364 SETZE GERÄTEMODUS IN
OPERATIONNEL OPERATIONNAL OPERACIONAL OPERACIONAL В РАБОТЕ BERTIEBSMODUS
MAINTENANCE MAINTENANCE MANTENIMIENTO MANUTENCAO ОБСЛУЖИВАНИЕ WARTUNG
Mode ctrl DPC Mode control DPC Modo control DPC Modo control DPC Команда режима MODUS UMSCHALT
4 | OperatingMode 4 | OperatingMode 4 | OperatingMode 4 | OperatingMode 4 | OperatingMode 4 | OperatingMode
MODE OPERATIONNEL C364 C364 OPERATING MODE C364 MODO OPERACIÓN C364 MODO DE OPERACAO Режим работы C364 C364 BETRIEBSMODUS
Mode d'Operation Operating mode Modo Operacional Modo do operacao Режим работы Operating mode
4 | SoftError 4 | SoftError 4 | SoftError 4 | SoftError 4 | SoftError 4 | SoftError
ERREUR LOGICIELLE DETECTEE SOFTWARE ERROR DETECTED ERROR DETECTADO SOFTWARE ERRO DE SOFTWARE DETECTADO ОБНАРУЖЕНА ОШИБКА ПО SOFTWAREFEHLER
OUI YES SI SIM ДА JA
NON NO NO NAO НЕТ NEIN
Err. Logicielle Soft. error SPS Error Soft. SPS Soft. error SPS Ошибка по SPS Softwarefehler
4 | SyncDevice 4 | SyncDevice 4 | SyncDevice 4 | SyncDevice 4 | SyncDevice 4 | SyncDevice
ETAT DE SYNCHRONISATION C364 C364 SYNCHRONIZATION STATUS ESATDO SINCRONIZACION C364 ESTADO DA SINCRONIZACAO C364 СТАТУС СИНХРОНИЗАЦИИ C364 C364 SYNCHRONISIERUNG STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchronisation Synchronisation Sincronización Sincronizacao Синхронизация Synchronisation
4 | TestDevice_DPC 4 | TestDevice_DPC 4 | TestDevice_DPC 4 | TestDevice_DPC 4 | TestDevice_DPC 4 | TestDevice_DPC
CHANGEMENT MODE EXPLOITATION C364 C364 CHANGE EXPLOITATION MODE CAMBIO MODO EXPLOTACION C364 CHAVEAR MODO DE OPERACAO C364 Смена режима работы C364 C364 TESTMODUS UMSCHALT
OPERATIONNEL NORMAL NORMAL OPERACIONAM НОРМАЛЬНЫЙ NORMAL
TEST TEST PRUEBA TESTE ТЕСТОВОЙ TEST
Ctrl Test DPC Test control DPC Ctrl Prueba DPC Ctrl Prueba DPC ком Тестов. DPC Testmodus DPC
4 | WatchdogError 4 | WatchdogError 4 | WatchdogError 4 | WatchdogError 4 | WatchdogError 4 | WatchdogError
ETAT DU CHIEN DE GARDE C364 C364 WATCHDOG RELAY STATUS ESTADO RELE WATCHDOG C364 ESTADO RELE WATCHDOG C364 СТАТУС WATCHDOG C364 C364 WATCHDOG RELAIS STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA ATIVO НЕИСПРАВНЫЙ FEHLER
Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS
4 | ModeDevice 4 | ModeDevice 4 | ModeDevice 4 | ModeDevice 4 | ModeDevice 4 | ModeDevice
V3 MODE OPERATIONNEL C364 OPERATING MODE C364 MODO OPERACIÓN DISPOSITIVO V3 MODO DE OPERACAO РЕЖИМ РАБОТЫ C364 C364 BETRIEBSMODUS
OPERATIONNEL RUNNING EN SERVICIO EM SERVICO Рабочее BETRIEB
MAINTENANCE MAINTENANCE MANTENIMIENTO MANUTENCAO ОБСЛУЖИВАНИЕ WARTUNG
Mode Eqpt Device mode Modo Dispositivo Modo Dispositivo Режим устройства Gerätemodus
4 | ExtClockStatus 4 | ExtClockStatus 4 | ExtClockStatus 4 | ExtClockStatus 4 | ExtClockStatus 4 | ExtClockStatus
ETAT DE LA SOURCE DE SYNCHRONISATION GPS SYNCHRONISATION SOURCE FUENTE SINCRONIZACION GPS FONTE SINCRONIZACAO GPS GPS ИСТОЧНИК СИНХРОНИЗАЦИИ GPS SYNCHRONISIERUNG QUELLE
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Etat Horloge Ext clock status Estado Reloj GPS Estado Reloj GPS Статус IRIG-B Ext Uhr Status
4 | RedDevice 4 | RedDevice 4 | RedDevice 4 | RedDevice 4 | RedDevice 4 | RedDevice
MODE DE REDONDANCE C364 C364 REDUNDANCY MODE MODO REDUNDANCIA C364 MODO REDUNDANCIA C364 C364 Режим резервирования C364 REDUNDANZ MODUS
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
Mode Redondance Redundancy mode Modo Redundancia Modo Redundancia Режим резерва Redundanzmodus
4 | CommIED 4 | CommIED 4 | CommIED 4 | CommIED 4 | CommIED 4 | CommIED
ETAT DE LA CONNECTION AU C364 IED CONNECTION STATUS TO C364 ESTADO COMUNICACIÓN IED AL C364 ESTADO DA CONEXAO COM A C364 СТАТУС СВЯЗИ IED С С264 IED VERBINDUNGSSTATUS C364
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Com. IED SPS IED SPS com. IED SPS com. IED SPS com. IED SPS связь. IED SPS com.
4 | SyncIED 4 | SyncIED 4 | SyncIED 4 | SyncIED 4 | SyncIED 4 | SyncIED
ETAT DE LA SYNCHRONISATION DE L'IED IED SYNCHRONISATION STATUS ESTADO SINCRONIZACION IED ESTADO DA SINCRONIZACAO DO RELE IED СТАТУС СИНХРОНИЗАЦИИ IED SYNCHRONISIERUNGSSTATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchro. IED SPS IED SPS Synchro. IED SPS Sincro. IED SPS Sincro. IED SPS синхр. IED SPS Synchro.
4 | DisturbIED 4 | DisturbIED 4 | DisturbIED 4 | DisturbIED 4 | DisturbIED 4 | DisturbIED
FICHIER DE PERTURBOGRAPHIE IED IED DISTURBANCE FILE ARCHIVO DE DISTURBIO EN IED ARQUIVO DE OSCILOGRAFIA IED IED ФАЙЛ ОСЦИЛОГРАМ IED DISTURBANCE FILE
PRÊT READY LISTO PRONTO ГОТОВ BEREIT
ABSENT NOT READY NO LISTO AUSENTE НЕ ГОТОВ NICHT BEREIT
IED DREC Prêt IED DREC ready IED DREC Listo IED DREC Pronto IED DRECготов IED DREC ready
4 | ISAGRAFStatus 4 | ISAGRAFStatus 4 | ISAGRAFStatus 4 | ISAGRAFStatus 4 | ISAGRAFStatus 4 | ISAGRAFStatus
ETAT ISAGRAF ISAGRAF STATUS ESTADO ISAGRAF ESTADO ISAGRAF ISAGRAF статус ISAGRAF STATUS
Etat ISAGRAF ISAGRAF status Estado ISAGRAF Estado ISAGRAF ISAGRAF статус ISAGRAF status
4 | RedSCADA 4 | RedSCADA 4 | RedSCADA 4 | RedSCADA 4 | RedSCADA 4 | RedSCADA
PORT DE COMMUNICATION C364 AVEC LE SCADA C364 SCADA PORT COMMUNICATION PTO. COM C364 SCADA CANAL DE COMUNICACAO C364 C/ SCADA СТАТУС ПОРТА СВЯЗЬ C364 с SCADA C364 FWL PORT KOMMUNIKATION
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
SPS Redondance Redundancy SPS Redundancia SPS Redundancia SPS резервирование Redundancy SPS
4 | CommSCADA 4 | CommSCADA 4 | CommSCADA 4 | CommSCADA 4 | CommSCADA 4 | CommSCADA
ETAT DE LA COMMUNICATION SCADA C364 SCADA CONNECTION STATUS TO C364 EDO. CONEXIÓN SCADA AL C364 ESTADO DA CONEXAO C364 C/ SCADA СТАТУС СОЕДИНЕНИЯ SCADA С C364 FWL VERBINDUNGSSTATUS C364
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Com. SCADA SPS SCADA SPS com. SCADA SPS com. SCADA SPS com. SCADA SPS связь FWL SPS KOMMU
SYSTEM INFORMATION UCA2 IED SYSTEM INFORMATION UCA2 IED SYSTEM INFORMATION UCA2 IED SYSTEM INFORMATION UCA2 IED SYSTEM INFORMATION UCA2 IED SYSTEM INFORMATION UCA2 IED
5 | CommDevice 5 | CommDevice 5 | CommDevice 5 | CommDevice 5 | CommDevice 5 | CommDevice
ETAT DU LIEN IED SBUS IED SBUS LINK ENLACE IED SBUS ESTADO DA CONEXAO IED SBUS IED SBUS связь IED SBUS LINK
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien Equipement Device link Enlace Dispo. Enlace Dispo. Связь устройств. Gerät Link
SYSTEM INFORMATION GATEWAY SYSTEM INFORMATION GATEWAY SYSTEM INFORMATION GATEWAY SYSTEM INFORMATION GATEWAY SYSTEM INFORMATION GATEWAY SYSTEM INFORMATION GATEWAY
6 | DBSwitch_SPC 6 | DBSwitch_SPC 6 | DBSwitch_SPC 6 | DBSwitch_SPC 6 | DBSwitch_SPC 6 | DBSwitch_SPC
PERMUTATION DE BD GTW GTW DATABASE SWITCHING CAMBIANDO BASE DE DATOS GTW CHAVEAMENTO DE BD GTW ПЕРЕКЛЮЧЕНИЕ БД GTW GTW DATENBANKUMSCHALTUNG
EXECUTER EXECUTE EJECUTAR EXECUTAR ВЫПОЛНЕНИЕ AUSFÜHREN
Permutation BD DB switch ctrl Ctrl Cambio BD Chaveamento BD БД Ком переключ. DB switch ctrl
6 | CommDevice 6 | CommDevice 6 | CommDevice 6 | CommDevice 6 | CommDevice 6 | CommDevice
ETAT DU LIEN GTW SBUS GTW SBUS LINK ENLACE GTW SBUS ESTADO DA CONEXAO GTW SBUS GTW SBUS СВЯЗЬ GTW SBUS LINK
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien Equipement Device link Enlace Dispo. Enlace Dispo. Связь устройств. Device link
6 | ModeDevice_DPC 6 | ModeDevice_DPC 6 | ModeDevice_DPC 6 | ModeDevice_DPC 6 | ModeDevice_DPC 6 | ModeDevice_DPC
CHANGER LE MODE D'EXPLOITATION GTW GTW FORCE OPERATION MODE TO FORZAR GTW MODO DE OPERACIÓN A CHAVEAR GTW MODO DE OPERACAO GTW ПЕРЕЙТИ В РЕЖИМ GTW UMSCHALTUNG BETRIEBSMODUS
OPERATIONNEL OPERATIONNAL OPERACIONAL OPERACIONAL В РАБОТЕ BERTIEBSMODUS
MAINTENANCE MAINTENANCE MANTENIMIENTO MANUTENCAO ОБСЛУЖИВАНИЕ WARTUNG
Mode ctrl DPC Mode control DPC Modo control DPC Modo control DPC Команда режима MODUS UMSCHALT
6 | OperatingMode 6 | OperatingMode 6 | OperatingMode 6 | OperatingMode 6 | OperatingMode 6 | OperatingMode
MODE OPERATIONNEL GTW GTW OPERATING MODE MODO OPERACIONAL GTW GTW MODO DE OPERACAO GTW Режим работы GTW BETRIEBSMODUS
Mode d'Operation Operating mode Modo Operacional Modo do operacao Режим работы Operating mode
6 | SyncDevice 6 | SyncDevice 6 | SyncDevice 6 | SyncDevice 6 | SyncDevice 6 | SyncDevice
ETAT DE SYNCHRONISATION GTW GTW SYNCHRONISATION STATUS ESTADO SINCRONIZACION GTW ESTADO DA SINCRONIZACAO GTW GTW СТАТУС СИНХРОНИЗАЦИИ GTW SYNCHRONISATION STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchronisation Synchronisation Sincronización Sincronizacao Синхронизация Synchronisation
6 | RedSCADA 6 | RedSCADA 6 | RedSCADA 6 | RedSCADA 6 | RedSCADA 6 | RedSCADA
PORT DE COMMUNICATION GTW AVEC LE SCADA GTW SCADA PORT COMMUNICATION PTO. COM GTW SCADA CANAL DE COMUNICACAO GTW C/ SCADA СТАТУС ПОРТА СВЯЗЬ GTW c SCADA GTW FWL PORT KOMMUNIKATION
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
SPS Redondance Redundancy SPS Redundancia SPS Redundancia SPS резервирование Redundancy SPS
6 | CommSCADA 6 | CommSCADA 6 | CommSCADA 6 | CommSCADA 6 | CommSCADA 6 | CommSCADA
ETAT DE LA COMMUNICATION GTW SCADA SCADA CONNECTION STATUS TO GTW EDO. CONEXIÓN SCADA AL GTW ESTADO DA CONEXAO GTW C/ SCADA СТАТУС СОЕДИНЕНИЯ SCADA С GTW FWL VERBINDUNGSSTATUS GTW
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Com. SCADA SPS SCADA SPS com. SCADA SPS com. SCADA SPS com. SCADA SPS связь FWL SPS KOMMU
6 | CommIED 6 | CommIED 6 | CommIED 6 | CommIED 6 | CommIED 6 | CommIED
ETAT DE LA CONNECTION GTW IED CONNECTION STATUS TO GTW ESTADO COMUNICACIÓN IED AL GTW ESTADO DA CONEXAO COM A GTW СТАТУС СВЯЗИ IED С GTW IED VERBINDUNGSSTATUS GTW
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Com. IED SPS IED SPS com. IED SPS com. IED SPS com. IED SPS связь. IED SPS com.
6 | SyncIED 6| SyncIED 6 | SyncIED 6 | SyncIED 6 | SyncIED 6 | SyncIED
ETAT DE LA SYNCHRONISATION DE L'IED IED SYNCHRONISATION STATUS ESTADO SINCRONIZACION IED ESTADO DA SINCRONIZACAO DO RELE IED СТАТУС СИНХРОНИЗАЦИИ IED SYNCHRONISIERUNGSSTATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchro. IED SPS IED SPS Synchro. IED SPS Sincro. IED SPS Sincro. IED SPS синхр. IED SPS Synchro.
6 | ISAGRAFStatus 6 | ISAGRAFStatus 6 | ISAGRAFStatus 6 | ISAGRAFStatus 6 | ISAGRAFStatus 6 | ISAGRAFStatus
ETAT ISAGRAF ISAGRAF STATUS ESTADO ISAGRAF ESTADO ISAGRAF ISAGRAF статус ISAGRAF STATUS
Etat ISAGRAF ISAGRAF status Estado ISAGRAF Estado ISAGRAF ISAGRAF статус ISAGRAF status
SYSTEM INFORMATION IEC 61850 SYSTEM INFORMATION IEC 61850 SYSTEM INFORMATION IEC 61850 SYSTEM INFORMATION IEC 61850 SYSTEM INFORMATION IEC 61850 SYSTEM INFORMATION IEC 61850
7 | CommDevice 7 | CommDevice 7 | CommDevice 7 | CommDevice 7 | CommDevice 7 | CommDevice
ETAT DU LIEN IED SBUS IED SBUS LINK ENLACE IED SBUS ESTADO DA CONEXAO IED SBUS IED SBUS связь IED SBUS LINK
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien Equipement Device link Enlace Dispo. Enlace Dispo. Связь устройств. Gerät Link
7 | OperatingMode 7 | OperatingMode 7 | OperatingMode 7 | OperatingMode 7 | OperatingMode 7 | OperatingMode
MODE OPERATIONNEL IED OPERATING MODE IED MODO OPERACIÓN MODO DE OPERACAO Режим работы IED IED BETRIEBSMODUS
Mode d'Operation Operating mode Modo Operacional Modo do operacao Режим работы Operating mode
7 | ModeDevice_DPC 7 | ModeDevice_DPC 7 | ModeDevice_DPC 7 | ModeDevice_DPC 7 | ModeDevice_DPC 7 | ModeDevice_DPC
CHANGER LE MODE D'EXPLOITATION IED FORCE OPERATION MODE TO FORZAR IED MODO DE OPERACIÓN A CHAVEAR MODO DE OPERACAO IED Силу режиме для IED SETZE GERÄTEMODUS IN
OPERATIONNEL OPERATIONNAL OPERACIONAL OPERACIONAL В РАБОТЕ BERTIEBSMODUS
MAINTENANCE MAINTENANCE MANTENIMIENTO MANUTENCAO ОБСЛУЖИВАНИЕ WARTUNG
Mode ctrl DPC Mode control DPC Modo control DPC Modo control DPC Команда режима MODUS UMSCHALT
7 | RedDevice 7 | RedDevice 7 | RedDevice 7 | RedDevice 7 | RedDevice 7 | RedDevice
MODE DE REDONDANCE REDUNDANCY MODE MODO REDUNDANCIA MODO REDUNDANCIA РЕЖИМ РЕЗЕРВА REDUNDANCY MODE
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
Mode Redondance Redundancy mode Modo Redundancia Modo Redundancia Режим резерва Redundanzmodus
7 | DisturbUCA2 7 | DisturbUCA2 7 | DisturbUCA2 7 | DisturbUCA2 7 | DisturbUCA2 7 | DisturbUCA2
FICHIER DE PERTURBOGRAPHIE IED DISTURBANCE FILE ON IED ARCHIVO DE DISTURBIO EN IED ARQUIVO DE OSCILOGRAFIA IED ФАЙЛ ОСЦИЛОГРАМ НА IED STÖRFALLDATEI AUF IED
PRÊT READY LISTO PRONTO ГОТОВ BEREIT
ABSENT NOT READY NO LISTO AUSENTE НЕ ГОТОВ NICHT BEREIT
DREC prêt DREC ready DREC Listo DREC Pronto DREC готов DREC ready
7 | DisturbLD 7 | DisturbLD 7 | DisturbLD 7 | DisturbLD 7 | DisturbLD 7 | DisturbLD
FICHIER DE PERTURBOGRAPHIE LD LOGICAL DEVICE DISTURBANCE FILE ARCHIVO DE DISTURBIO LD ARQUIVO DE OSCILOGRAFIA LD ФАЙЛ ОСЦИЛОГРАМ LD STÖRFALLDATEI LD
PRÊT READY LISTO PRONTO ГОТОВ BEREIT
ABSENT NOT READY NO LISTO AUSENTE НЕ ГОТОВ NICHT BEREIT
LD DREC prêt LD DREC ready LD DREC Listo LD DREC Pronto LD DREC готов LD DREC ready
7 | UCA2GenSPS 7 | UCA2GenSPS 7 | UCA2GenSPS 7 | UCA2GenSPS 7 | UCA2GenSPS 7 | UCA2GenSPS
IEC61850 GENERIC SPS IEC61850 GENERIC SPS IEC61850 GENERIC SPS IEC61850 GENERIC SPS IEC61850 GENERIC SPS IEC61850 GENERIC SPS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS
7 | UCA2GenDPS 7 | UCA2GenDPS 7 | UCA2GenDPS 7 | UCA2GenDPS 7 | UCA2GenDPS 7 | UCA2GenDPS
IEC61850 GENERIC DPS IEC61850 GENERIC DPS IEC61850 GENERIC DPS IEC61850 GENERIC DPS IEC61850 GENERIC DPS IEC61850 GENERIC DPS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS
7 | UCA2GenMPS 7 | UCA2GenMPS 7 | UCA2GenMPS 7 | UCA2GenMPS 7 | UCA2GenMPS 7 | UCA2GenMPS
IEC61850 GENERIC MPS IEC61850 GENERIC MPS IEC61850 GENERIC MPS IEC61850 GENERIC MPS IEC61850 GENERIC MPS IEC61850 GENERIC MPS
IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS
7 | UCA2GenSPC 7 | UCA2GenSPC 7 | UCA2GenSPC 7 | UCA2GenSPC 7 | UCA2GenSPC 7 | UCA2GenSPC
IEC61850 GENERIC SPC IEC61850 GENERIC SPC IEC61850 GENERIC SPC IEC61850 GENERIC SPC IEC61850 GENERIC SPC IEC61850 GENERIC SPC
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC
7 | UCA2GenDPC 7 | UCA2GenDPC 7 | UCA2GenDPC 7 | UCA2GenDPC 7 | UCA2GenDPC 7 | UCA2GenDPC
IEC61850 GENERIC DPC IEC61850 GENERIC DPC IEC61850 GENERIC DPC IEC61850 GENERIC DPC IEC61850 GENERIC DPC IEC61850 GENERIC DPC
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC
7 | UCA2GenMV 7 | UCA2GenMV 7 | UCA2GenMV 7 | UCA2GenMV 7 | UCA2GenMV 7 | UCA2GenMV
IEC61850 GENERIC MV IEC61850 GENERIC MV IEC61850 GENERIC MV IEC61850 GENERIC MV IEC61850 GENERIC MV IEC61850 GENERIC MV
IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV
SYSTEM INFORMATION BAY OI SYSTEM INFORMATION BAY OI SYSTEM INFORMATION BAY OI SYSTEM INFORMATION BAY OI SYSTEM INFORMATION BAY OI SYSTEM INFORMATION BAY OI
8 | AgencyStatus 8 | AgencyStatus 8 | AgencyStatus 8 | AgencyStatus 8 | AgencyStatus 8 | AgencyStatus
ETAT DE L'AGENCE AGENCY STATUS ESTADO AGENCY ESTADO DA AGENCY IEC СТАТУС ДРАЙВЕРА AGENCY STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Etat de l'agence Agency status Estado Agency Estado Agency Статус драйвера Agency status
8 | AutomaticArchiving 8 | AutomaticArchiving 8 | AutomaticArchiving 8 | AutomaticArchiving 8 | AutomaticArchiving 8 | AutomaticArchiving
ETAT DE L'ARCHIVAGE AUTOMATIQUE AUTOMATIC ARCHIVING STATUS ESTADO ARCHIVO AUTOMATICO ESTADO DO ARQUIVO AUTOMATICO СТАТУС АВТОМАТИЧЕСКОЙ АРХИВАЦИИ AUTOMATIC ARCHIVING STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Archivage Auto Auto archiving Archivo Auto Arquivo Auto Авто архивация Auto archiving
8 | CentralArchiving 8 | CentralArchiving 8 | CentralArchiving 8 | CentralArchiving 8 | CentralArchiving 8 | CentralArchiving
ETAT DE LA BD HISTORIAN HISTORIAN DATABASE STATUS ESTADO BASE DE DATOS HISTORIAN ESTADO BASE DE DADOS HISTORIAN Статус БД Историк HISTORIAN DATABASE STATUS
Archive Centrale Central archive Archivo Central Archivo Central Центр. архив Central archive
8 | CommDevice 8 | CommDevice 8 | CommDevice 8 | CommDevice 8 | CommDevice 8 | CommDevice
ETAT DU LIEN SBUS OI SBUS LINK ENLACE OI SBUS ESTADO DA CONEXAO SBUS СОЕДИНЕНИЕ OI и SBUS OI SBUS LINK
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien SBUS Device link Enlace SBUS Conexao SBUS Связь устройств. Device link
8 | LogQueue 8 | LogQueue 8 | LogQueue 8 | LogQueue 8 | LogQueue 8 | LogQueue
ETAT DE LA FILE D'IMPRESSION LOGGING QUEUE STATUS ESTADO COLA DE EVENTOS ESTADO DA FILA DE EVENTOS СНЯТИЕ ПОКАЗАНИЯ СТАТУСА ОЧЕРЕДИ LOGGING QUEUE STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
File impression Log Queue Cola de Eventos Fila de Eventos Лог очереди Log Queue
8 | OperatingMode 8 | OperatingMode 8 | OperatingMode 8 | OperatingMode 8 | OperatingMode 8 | OperatingMode
MODE OPERATIONNEL OPERATING MODE MODO OPERACIONAL MODO DE OPERACAO РЕЖИМ РАБОТЫ OPERATING MODE
Mode d'Operation Operating mode Modo Operacional Modo do operacao Режим работы Operating mode
8 | RedDevice 8 | RedDevice 8 | RedDevice 8 | RedDevice 8 | RedDevice 8 | RedDevice
MODE DE REDONDANCE REDUNDANCY MODE MODO REDUNDANCIA MODO REDUNDANCIA РЕЖИМ РЕЗЕРВА REDUNDANCY MODE
ACTIF ACTIVE ACTIVO ATIVO ОСНОВНОЙ AKTIV
RESERVE STANDBY EN ESPERA RESERVA РЕЗЕРВНЫЙ RESERVE
Mode Redondance Redundancy mode Modo Redundancia Modo Redundancia Режим резерва Redundanzmodus
8 | SyncDevice 8 | SyncDevice 8 | SyncDevice 8 | SyncDevice 8 | SyncDevice 8 | SyncDevice
ETAT DE SYNCHRONISATION SYNCHRONIZATION STATUS ESTADO SINCRONIZACION ESTADO DA SINCRONIZACAO СТАТУС СИНХРОНИЗАЦИИ SYNCHRONISIERUNG STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Synchronisation Synchronisation Sincronización Sincronizacao Синхронизация Synchronisation
8 | CouplingStatus 8 | CouplingStatus 8 | CouplingStatus 8 | CouplingStatus 8 | CouplingStatus 8 | CouplingStatus
ETAT DU COUPLAGE AGENCE SBUS ACQUISITION STATUS ESTADO ADQUISICION SBUS ESTADO AQUISICAO SBUS SBUS СТАТУС СБОРА ДАННЫХ SBUS ACQUISITION STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Couplage IEC IEC Coupling Acople IEC Aquisicao IEC Связь с IEC IEC Coupling
8 | CommS2K_C 8 | CommS2K_C 8 | CommS2K_C 8 | CommS2K_C 8 | CommS2K_C 8 | CommS2K_C
ETAT DE LA CONNECTION CONNECTION STATUS ESTADO CONEXIÓN ESTADO DA CONEXAO СТАТУС СОЕДИНЕНИЯ VERBINDUNG STATUS
NORMAL HEALTHY CORRECTO NORMAL ИСПРАВНЫЙ BETRIEB
DEFAUT FAULTY EN FALLA FALHA НЕИСПРАВНЫЙ FEHLER
Lien OI CLIENT OI client link Enlace CLIENTE Conexao CLIENTE Связь клиента OI client link
SPSPrf | SPSNoAlLogArc ;
DPSPrf | DPSNoAlLogArc ;
MPSPrf | MPSNoAlLogArc ;
SPCPrf | SPCNoAlLogArc ;
DPCPrf | DPCNoAlLogArc ;
MVPrf | MVNoAlLogArc ;
SetPointPrf | SPNoAlLogArc ;
CounterPrf | CTNoAlLogArc ;
Designation : #REF! Symbol : #REF!
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
This sheet is used to choose what are the default Menu Options for this Datalist
The goal is to allow only given Menu Options to a customer for example.
GE Menu: Menu Option Display in Datalist Menu
Show Datalist Yes
Hide Sheets Yes
Display Sheets Yes
Check Datalist consistency Yes
Set Default parameter Values Yes
Add or Modify a BCU, UCA2 IED or IEC 61850 IED Yes
Import PES Signal List Yes
Count SPARE Data Yes
Translate this Datalist Yes
About this Datalist Yes
CUSTOMER Menu: Menu Option Display in Datalist Menu
Show Datalist Yes
Display Sheets No
Check Datalist consistency No
Set Default parameter Values No
Add or Modify a BCU, UCA2 IED or IEC 61850 IED Yes
Import PES Signal List Yes
Count SPARE Data Yes
Translate this Datalist No
About this Datalist Yes
Designation : #REF! Symbol : #REF!
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
MiCOM C264 DESCRIPTION
Computer Name GE Reserved
Redundant Computer Auto generated
Computer type (C264/C264C) Read Only
Gateway Port used (on gateway)
DIGITAL INPUT BOARD DIU2xx
Digital Inputs Board Number
Digital Inputs Board Slot
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 2 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 3 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 4 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 5 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 6 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 7 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 8 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 9 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 10 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 11 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 12 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 13 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 14 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 15 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
A 16 SPARE SPS None No 1 DIGITAL INPUT BOARD DIU2xx
DIGITAL OUTPUT BOARD DOU20x
Digital Outputs Board Number
Digital Outputs Board Slot
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
HIGH BREAK UNIT BOARD HBU20x
HBU Board Number
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 5 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 6 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 7 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 8 SPARE SPC NO 2 DIGITAL OUTPUT BOARD DOU20x
A 9 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
A 10 SPARE SPC NO/NC 2 DIGITAL OUTPUT BOARD DOU20x
DIGITAL INPUT/OUTPUT BOARD CCU20x
DI/DO Board Number
DI/DO Board Slot
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
A 2 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
A 3 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
A 4 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
A 5 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
A 6 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
A 7 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
A 8 SPARE SPS None No 1 DIGITAL INPUT BOARDS CCU20x
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 DIGITAL OUTPUT BOARDS CCU20x
A 2 SPARE SPC NO 2 DIGITAL OUTPUT BOARDS CCU20x
A 3 SPARE SPC NO 2 DIGITAL OUTPUT BOARDS CCU20x
A 4 SPARE SPC NO 2 DIGITAL OUTPUT BOARDS CCU20x
ANALOG INPUT BOARD AIU20x
Analog Input Board Number
Analog Input Board Slot
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE 6 ANALOG INPUT BOARD AIU20x
A 2 SPARE 6 ANALOG INPUT BOARD AIU20x
A 3 SPARE 6 ANALOG INPUT BOARD AIU20x
A 4 SPARE 6 ANALOG INPUT BOARD AIU20x
ANALOG INPUT BOARD AIU21x
Analog Input Board Number
Analog Input Board Slot
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE 6 ANALOG INPUT BOARD AIU21x
A 2 SPARE 6 ANALOG INPUT BOARD AIU21x
A 3 SPARE 6 ANALOG INPUT BOARD AIU21x
A 4 SPARE 6 ANALOG INPUT BOARD AIU21x
A 5 SPARE 6 ANALOG INPUT BOARD AIU21x
A 6 SPARE 6 ANALOG INPUT BOARD AIU21x
A 7 SPARE 6 ANALOG INPUT BOARD AIU21x
A 8 SPARE 6 ANALOG INPUT BOARD AIU21x
CT/VT ANALOG INPUT BOARD TMU2x0
CT/VT Board Number
CT/VT Board Slot
CT/VT Board Model
Nominal Current (1A/5A)
Nominal Voltage [1V … 500V]
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A Va Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vb Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vc Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Vbusbar Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ia Mv0000Current A 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ib Mv0000Current A 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ic Mv0000Current A 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uab Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Ubc Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Uca Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Freq (Line) Mv000Freq Hz 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DV Mv0000Voltage kV 6 CT/VT ANALOG INPUT BOARD TMU2x0
A DF Mv000Freq Hz 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Dj Mv0000Current ° 6 CT/VT ANALOG INPUT BOARD TMU2x0
A P total (MW) Mv0000Power MW 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Q total (Mvar) Mv0000RePower Mvar 6 CT/VT ANALOG INPUT BOARD TMU2x0
A Power Factor Mv000PowerF - 6 CT/VT ANALOG INPUT BOARD TMU2x0
DSP210 Board Number
DSP210 Board Slot
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 DSP210 BOARD
A 5 SPARE SPC NO 2 DSP210 BOARD
ANALOG OUTPUT BOARD AOU20x
Analog Output Board Number
Analog Output Board Slot
Iss. Customer Ref AO Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE 13 ANALOG OUTPUT BOARD AOU20x
A 2 SPARE 13 ANALOG OUTPUT BOARD AOU20x
A 3 SPARE 13 ANALOG OUTPUT BOARD AOU20x
A 4 SPARE 13 ANALOG OUTPUT BOARD AOU20x
DIGITAL INFORMATION FROM IED IED name
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
DIGITAL INFORMATION TO IED IED name
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
ANALOG INFORMATION FROM IED IED name
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
ANALOG INFORMATION TO IED IED name
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name
A SPARE 13 ANALOG INFORMATION TO IED IED name
COUNTER INFORMATION FROM IED IED name
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name
A SPARE Yes 39 COUNTER INFORMATION FROM IED IED name
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 DI GROUPS
A 2 SPARE SPS None No 1 C264 DI GROUPS
A 3 SPARE SPS None No 1 C264 DI GROUPS
A 4 SPARE SPS None No 1 C264 DI GROUPS
A 5 SPARE SPS None No 1 C264 DI GROUPS
A 6 SPARE SPS None No 1 C264 DI GROUPS
A 7 SPARE SPS None No 1 C264 DI GROUPS
A 8 SPARE SPS None No 1 C264 DI GROUPS
A 9 SPARE SPS None No 1 C264 DI GROUPS
A 10 SPARE SPS None No 1 C264 DI GROUPS
A 11 SPARE SPS None No 1 C264 DI GROUPS
A 12 SPARE SPS None No 1 C264 DI GROUPS
A 13 SPARE SPS None No 1 C264 DI GROUPS
A 14 SPARE SPS None No 1 C264 DI GROUPS
A 15 SPARE SPS None No 1 C264 DI GROUPS
A 16 SPARE SPS None No 1 C264 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C264 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C264 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C264 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C264 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C264 SELF GENERATED SETPOINT INFORMATION
Designation : #REF! Symbol : #REF!
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
MiCOM C364 DESCRIPTION
Computer Name Auto generated
Redundant Computer Read Only
Gateway Port used (on gateway)
DIGITAL INFORMATION FROM IED IED name
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
A SPARE SPS None No 1 DIGITAL INFORMATION FROM IED IED name
DIGITAL INFORMATION TO IED IED name
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
A SPARE SPC 2 DIGITAL INFORMATION TO IED IED name
ANALOG INFORMATION FROM IED IED name
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
A SPARE Yes 6 ANALOG INFORMATION FROM IED IED name
ANALOG INFORMATION TO IED IED name
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE 13 ANALOG INFORMATION TO IED IED name
A SPARE 13 ANALOG INFORMATION TO IED IED name
COUNTER INFORMATION FROM IED IED name
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A SPARE Yes 39 COUNTER INFORMATION FROM IED name
A SPARE Yes 39 COUNTER INFORMATION FROM IED name
A SPARE Yes 39 COUNTER INFORMATION FROM IED name
A SPARE Yes 39 COUNTER INFORMATION FROM IED name
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C364 DI GROUPS
A 2 SPARE SPS None No 1 C364 DI GROUPS
A 3 SPARE SPS None No 1 C364 DI GROUPS
A 4 SPARE SPS None No 1 C364 DI GROUPS
A 5 SPARE SPS None No 1 C364 DI GROUPS
A 6 SPARE SPS None No 1 C364 DI GROUPS
A 7 SPARE SPS None No 1 C364 DI GROUPS
A 8 SPARE SPS None No 1 C364 DI GROUPS
A 9 SPARE SPS None No 1 C364 DI GROUPS
A 10 SPARE SPS None No 1 C364 DI GROUPS
A 11 SPARE SPS None No 1 C364 DI GROUPS
A 12 SPARE SPS None No 1 C364 DI GROUPS
A 13 SPARE SPS None No 1 C364 DI GROUPS
A 14 SPARE SPS None No 1 C364 DI GROUPS
A 15 SPARE SPS None No 1 C364 DI GROUPS
A 16 SPARE SPS None No 1 C364 DI GROUPS
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 2 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 3 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 4 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 5 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 6 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 7 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 8 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 9 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 10 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 11 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 12 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 13 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 14 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 15 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
A 16 SPARE SPS None No 1 C364 SELF GENERATED DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 2 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 3 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 4 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 5 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 6 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 7 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 8 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 9 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
A 10 SPARE SPC NO 2 C364 SELF GENERATED DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 2 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 3 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 4 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 5 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 6 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 7 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 8 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 9 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 10 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 11 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 12 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 13 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 14 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 15 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
A 16 SPARE Yes 6 C364 SELF GENERATED ANALOG INFORMATION
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 2 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 3 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 4 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 5 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 6 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 7 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 8 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 9 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 10 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 11 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 12 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 13 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 14 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 15 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
A 16 SPARE Yes 39 C364 SELF GENERATED COUNTER INFORMATION
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
A 1 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 2 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 3 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 4 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 5 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 6 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 7 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 8 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 9 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 10 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 11 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 12 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 13 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 14 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 15 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
A 16 SPARE Yes 13 C364 SELF GENERATED SETPOINT INFORMATION
Designation : Project Name Symbol : SAM-DTL-DS Agile-4.3.0.0
Issue : A Ref : PROJECTNAME-Xnn-DTL
Date : 0 Substation Automation Data Of : Site Name
This sheet is to be used to indicate the cells/columns that are : GE Reserved
- P : present in all corresponding sheets but the contents shall not be used by automatic tools Auto generated
- U : present in all corresponding sheets and shall be used by automatic tools Read Only
- A : not present in corresponding sheets
- PH : hide in all corresponding sheets but the contents shall not be used by automatic tools
- UH : hide in all corresponding sheets and shall be used by automatic tools
MiCOM CXXX DESCRIPTION
DIGITAL INPUT BOARD DIU2xx
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U
DIGITAL OUTPUT BOARD DOU20x
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U A U U U U U
HIGH BREAK UNIT BOARD HBU20x
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U A U U U U U
DIGITAL INPUT/OUTPUT BOARD CCU20x
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U A U U U U U
ANALOG INPUT BOARD AIU20x
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U U U U U U U
ANALOG INPUT BOARD AIU21x
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U U U U U U U
CT/VT ANALOG INPUT BOARD TMU2x0
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U A U U U U U U U U U U U U U U U U U U U A U A U U U U U U U U U U U
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U A U U U U U
ANALOG OUTPUT BOARD AOU20x
Iss. Customer Ref AO Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A A A U U A U U A U U U U U
DIGITAL INFORMATION FROM IED
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U
DIGITAL INFORMATION TO IED
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U A U U U U U
ANALOG INFORMATION FROM IED
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U U U U U U U
ANALOG INFORMATION TO IED
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A A A U U A U U A U U U U U
COUNTER INFORMATION FROM IED
Iss. Customer Ref IED Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A A A U U U U U A U U U U U
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U A U U U U U
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A U A U U U U U U U U U U U
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Type Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A A A U U U U U A U U U U U
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U A A A U U A U U A U U U U U
SUBSTATION DATA DESCRIPTION
SUBSTATION DI GROUPS
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Managed by Computer Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U U
SYSTEM INFORMATION DATA DESCRIPTION
SYSTEM INFORMATION SERVER OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U A U U U U A U U U A A U U U
SYSTEM INFORMATION CLIENT OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U A U U U U A U U U A A U U U
SYSTEM INFORMATION MiCOM C264
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U U U U U U A U U U A A U U U
SYSTEM INFORMATION MiCOM C364
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U U U U U U A U U U A A U U U
SYSTEM INFORMATION UCA2 IED
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U U U U U U A U U U A A U U U
SYSTEM INFORMATION GATEWAY
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U A U U U U A U U U A A U U U
SYSTEM INFORMATION IEC 61850
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U U U U U U A U U U A A U U U
SYSTEM INFORMATION BAY OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U A A U A U U A A A U U U U U U U U U U U U U U A U U U U A U U U A A U U U
Designation : #REF! Symbol : #REF! BABA
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
This sheet is used to set default parameter value for each data. GE Reserved
- set the Old parameter value to change in the "Old Value" line Auto generated
- set the New parameter value used to overwrite Old one in the "New Value" line Read Only
- It is possible to use regular expressions as 'Old value' to locate data by using:
? Any single character.
* Zero or more characters.
# Any single digit (0-9).
[charlist] Any single character in charlist.
[!charlist] Any single character not in charlist.
- A group of one or more characters (charlist) enclosed in brackets ([ ]) can be used to
match any single character in string and can include almost any character code,
including digits.
- Note: To match the special characters left bracket ([), question mark (?), number sign (#),
and asterisk (*), enclose them in brackets. The right bracket (]) can't be used within a group
to match itself, but it can be used outside a group as an individual character.
- By using a hyphen (-) to separate the upper and lower bounds of the range, charlist can
specify a range of characters. For example, [A-Z] results in a match if the corresponding
character position in string contains any uppercase letters in the range A-Z. Multiple ranges
'aBBBa' is like 'a*a'
'F' is like '[A-Z]'
'F' is NOT like '[!A-Z]'
'a2a' is like 'a#a'
'aM5b' is like 'a[L-P]#[!c-e]'
'BAT123khg' is like 'B?T*'
'CAT123khg' is NOT like 'B?T*'
MiCOM CXXX DESCRIPTION
DIGITAL INPUT BOARD DIU2xx
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
DIGITAL OUTPUT BOARD DOU20x
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
HIGH BREAK UNIT BOARD HBU20x
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
DIGITAL INPUT/OUTPUT BOARD CCU20x
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
ANALOG INPUT BOARD AIU20x
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
ANALOG INPUT BOARD AIU21x
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
CT/VT ANALOG INPUT BOARD TMU2x0
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
ANALOG OUTPUT BOARD AOU20x
Iss. Customer Ref AO Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
DIGITAL INFORMATION FROM IED
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
DIGITAL INFORMATION TO IED
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
ANALOG INFORMATION FROM IED
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
ANALOG INFORMATION TO IED
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
COUNTER INFORMATION FROM IED
Iss. Customer Ref IED Counter Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
SUBSTATION DATA DESCRIPTION
SUBSTATION DI GROUPS
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Managed by Computer Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
SYSTEM INFORMATION DATA DESCRIPTION
SYSTEM INFORMATION SERVER OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
SYSTEM INFORMATION CLIENT OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
SYSTEM INFORMATION MiCOM C264
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
SYSTEM INFORMATION MiCOM C364
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
SYSTEM INFORMATION UCA2 IED
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
SYSTEM INFORMATION GATEWAY
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
SYSTEM INFORMATION IEC 61850
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
SYSTEM INFORMATION BAY OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
Designation : #REF! Symbol : #REF!
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
This sheet is to be used to indicate the cells/columns for which the contents shall be copied to a new DataList release. GE Reserved
The possible values are : Auto generated
- N : do not copy in any case Read Only
- C : copy in any case (when the line is significant)
- E : copy only if the cell within new release is empty
MiCOM CXXX DESCRIPTION
DIGITAL INPUT BOARD DIU2xx
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
DIGITAL OUTPUT BOARD DOU20x
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E N E N E E E E E N E E E E E
HIGH BREAK UNIT BOARD HBU20x
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E N E N E E E E E N E E E E E
DIGITAL INPUT/OUTPUT BOARD CCU20x
Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E N E N E E E E E N E E E E E
ANALOG INPUT BOARD AIU20x
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N E N E E E E E E E E E E E
ANALOG INPUT BOARD AIU21x
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N E N E E E E E E E E E E E
CT/VT ANALOG INPUT BOARD TMU2x0
Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E N E N E E E E E E E E E E E
Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E N E N E E E E E N E E E E E
ANALOG OUTPUT BOARD AOU20x
Iss. Customer Ref AO Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Slot Channel Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N N E E E E E E E E E E E E E E E E E E E N N N E E N E E N E E E E E
DIGITAL INFORMATION FROM IED
Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
DIGITAL INFORMATION TO IED
Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N E N E E E E E N E E E E E
ANALOG INFORMATION FROM IED
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N E N E E E E E E E E E E E
ANALOG INFORMATION TO IED
Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N N N E E N E E N E E E E E
COUNTER INFORMATION FROM IED
Iss. Customer Ref IED Counter Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N N N E E E E E N E E E E E
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N E N E E E E E N E E E E E
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N E N E E E E E E E E E E E
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N N N E E E E E N E E E E E
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E N N N E E N E E N E E E E E
SUBSTATION DATA DESCRIPTION
SUBSTATION DI GROUPS
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Managed by Computer Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
E E E N E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
SYSTEM INFORMATION DATA DESCRIPTION
SYSTEM INFORMATION SERVER OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E N E E E E N E E E N N E E E
SYSTEM INFORMATION CLIENT OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E N E E E E N E E E N N E E E
SYSTEM INFORMATION MiCOM C264
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E E E E E E N E E E N N E E E
SYSTEM INFORMATION MiCOM C364
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E E E E E E N E E E N N E E E
SYSTEM INFORMATION UCA2 IED
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E E E E E E N E E E N N E E E
SYSTEM INFORMATION GATEWAY
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E N E E E E N E E E N N E E E
SYSTEM INFORMATION IEC 61850
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E E E E E E N E E E N N E E E
SYSTEM INFORMATION BAY OI
Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
E N N E N E E N N N E E E E E E E E E E E E E E N E E E E N E E E N N E E E
Designation : #REF! Symbol : #REF!
Issue : #REF! Ref : #REF!
Date : #REF! Substation Automation Data Of : #REF!
This sheet indicates the cells/columns used for building comparison criteria. GE Reserved
The possible values are : Auto generated
- P : present in all corresponding sheets but the contents shall not be used to build comparison criteria Read Only
- U : present in all corresponding sheets and shall be used to build comparison criteria
- A : not present in corresponding sheets
MiCOM CXXX DESCRIPTION
DIGITAL INPUT BOARD DIU2xx
Description Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case Digital Inputs Board Number Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
DIGITAL OUTPUT BOARD DOU20x
Description Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case Digital Outputs Board Number Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
HIGH BREAK UNIT BOARD HBU20x
Description Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case Digital Outputs Board Number Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
DIGITAL INPUT/OUTPUT BOARD CCU20x
Description Iss. Customer Ref DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case DI/DO Board Number Issue Panel Number Tag Number Slot Channel Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
Description Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case DI/DO Board Number Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
ANALOG INPUT BOARD AIU20x
Description Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Use this Matrix Case Analog Input Board Number Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
ANALOG INPUT BOARD AIU21x
Description Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Use this Matrix Case Analog Input Board Number Issue Panel Number Tag Number Channel Transducer Type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
CT/VT ANALOG INPUT BOARD TMU2x0
Description Iss. Customer Ref AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Use this Matrix Case CT/VT Board Number Issue Panel Number Tag Number Input type (U/I) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P P A U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P A U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P A U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
P U P P P P A P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
P P P P P P A P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
Description Iss. Customer Ref DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case DSP210 Board Number Issue Panel Number Tag Number Slot Channel Function Type (SPC=Single/DPC=Dual/DS=Dual Switch) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
ANALOG OUTPUT BOARD AOU20x
Description Iss. Customer Ref AO Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case Analog Output Board Number Issue Panel Number Tag Number Slot Channel Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P P U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P P P U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P P P U U U P U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P P P U U U U P P U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P P P U U U U U U P P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P P P U U U P P P U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P P P U U U U P P P P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P U U P P P U U U U P P P P P P P P P P A A A P P A P P A P P P P P
P U P P P U U P P P P P P P P P P P P P P P P P P P A A A P P A P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A A A P P A P P A P P P P P
DIGITAL INFORMATION FROM IED
Description Iss. Customer Ref IED DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case IED name Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P P P U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P U U U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U U P P P U U P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
DIGITAL INFORMATION TO IED
Description Iss. Customer Ref IED DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case IED name Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
ANALOG INFORMATION FROM IED
Description Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Use this Matrix Case IED name Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P U U U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U U P P P U U P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
ANALOG INFORMATION TO IED
Description Iss. Customer Ref IED AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case IED name Issue Panel Number Tag Number T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at minimum Corresponding AI Value at Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P U U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P P U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P P P U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P P P U U U P U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P P P U U U U P P U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P P P U U U U U U P P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P P P U U U P P P U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P P P U U U U P P P P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P P P U U P P P U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P U U U U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U U P P P U U P P P P P P P P P P P P P P P P P P P A A A P P A P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A A A P P A P P A P P P P P
COUNTER INFORMATION FROM IED
Description Iss. Customer Ref IED Counter Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Use this Matrix Case IED name Issue Panel Number Tag Number T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U U P P P U U U U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P U U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P P U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P P U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P P P U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P P U U U P U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P P P U U U P U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P P U U U U P P U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P P P U U U U P P U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P P U U U U U U P P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P P P U U U U U U P P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P P U U U P P P U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P P P U U U P P P U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P P U U U U P P P P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P P P U U U U P P P P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U U U P P P U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P P P U U P P P U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U P P P P U U U U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U P P P P P P U U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U U P P P U U P P P P P P P P P P P P P P P P P P P A A A P P P P P A P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P A A A P P P P P A P P P P P
END OF IED DATA
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U A P P P P U U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
P A P P P U U P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
P A P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
SELF GENERATED DIGITAL INFORMATION
Iss. Customer Ref Self DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPS=Single/DPS=Dual/MPS=Multiple) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U A P P P P P U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
P A P P P U P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
P A P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
SELF GENERATED DIGITAL OUTPUT INFORMATION
Iss. Customer Ref Self DO Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Control HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case Issue Panel Number Tag Number Number Automation Origin (if any) Function Type (SPC=Single/DPC=Dual) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Control HMI Control Has a xPS Feedback Is activated by xPS Used by ISaGRAF Relay Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U A P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P A P P P P P
U A P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P A P P P P P
P A P P P U P P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
P A P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P A P P P P P
SELF GENERATED ANALOG INFORMATION
Iss. Customer Ref Self AI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Use this Matrix Case Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding AI Value at Transducer minimum Corresponding AI Value at Transducer Maximum Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Automations links (separator ";") (add "<" if output) LCD Display HMI Display Integrated by COUNTER Trend Viewer Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U A P P P P P U U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P P U U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P P P U U U U U U U P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P P P U U U P U U U P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P P P U U U U P P U P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P P P U U U U U U P P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P P P U U U P P P U P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P P P U U U U P P P P P P P P P P P P P A P A P P P P P P P P P P P
U A P P P P P U U P P P U U U U P P P P P P P P P P A P A P P P P P P P P P P P
P A P P P U P P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
P A P P P P P P P P P P P P P P P P P P P P P P P P A P A P P P P P P P P P P P
SELF GENERATED COUNTER INFORMATION
Iss. Customer Ref Self Counter Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Local Display HMI Link Automation Template Conf. Mng.
Use this Matrix Case Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Counter Type Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Integrate MV Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U A P P P P P U U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P P U U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P P P U U U U U U U P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P P P U U U P U U U P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P P P U U U U P P U P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P P P U U U U U U P P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P P P U U U P P P U P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P P P U U U U P P P P P P P P P P P P P A A A P P P P P A P P P P P
U A P P P P P U U P P P U U U U P P P P P P P P P P A A A P P P P P A P P P P P
P A P P P U P P P P P P P P P P P P P P P P P P P P A A A P P P P P A P P P P P
P A P P P P P P P P P P P P P P P P P P P P P P P P A A A P P P P P A P P P P P
SELF GENERATED SETPOINT INFORMATION
Iss. Customer Ref SetPoint Reference Electrical Data Description Labels Description Scada Interface IEC Interface Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case Issue Panel Number Tag Number Number Automation Origin (if any) Function Unit Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Corresponding Minimal Value Corresponding Maximal Value Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) LCD Display HMI Display Trend Viewer Used by ISaGRAF Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U A P P P P P U U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P P U U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P P P U U U U U U U P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P P P U U U P U U U P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P P P U U U U P P U P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P P P U U U U U U P P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P P P U U U P P P U P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P P P U U U U P P P P P P P P P P P P P A A A P P A P P A P P P P P
U A P P P P P U U P P P U U U U P P P P P P P P P P A A A P P A P P A P P P P P
P A P P P U P P P P P P P P P P P P P P P P P P P P A A A P P A P P A P P P P P
P A P P P P P P P P P P P P P P P P P P P P P P P P A A A P P A P P A P P P P P
SUBSTATION DATA DESCRIPTION
SUBSTATION DI GROUPS
Iss. Customer Ref Group DI Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI DI/DO Link Automation Template Conf. Mng.
Use this Matrix Case Issue Panel Number Tag Number Number Group Operator Function Type (S=Single) Voltage Level Short Name (16 char) Bay Short Name (16 char) Module Short Name (16 char) Long name (35 char) Single : Text at electrical state = 1 (16 char) Single : Text at electrical state = 0 (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Managed by Computer Automations links (separator ";") (add "<" if output) LED LCD Display HMI Display Is a xPC Feedback Acts on xPC Used by ISaGRAF Is used by distributed Automation (GOOSE) Bay Name (in SCE Template) or Bay Type Module Name (in SCE Template) or Module Type Datapoint Name (in SCE Template) or Datapoint Type Process Comments
U A P P P P U U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P U U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P U U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U P U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U U U P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U P P P U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P U U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
U A P P P P P U U P P P U U U U P P P P P P P P P P P P P P P P P P P P P P P P
P A P P P U U P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
P A P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P
SYSTEM INFORMATION DATA DESCRIPTION
SYSTEM INFORMATION SERVER OI
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case SERVER OI Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
SYSTEM INFORMATION CLIENT OI
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case CLIENT OI Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
SYSTEM INFORMATION MiCOM C264
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case MiCOM C264 Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
SYSTEM INFORMATION MiCOM C364
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case MiCOM C364 Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
SYSTEM INFORMATION UCA2 IED
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case UCA2 IED Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
SYSTEM INFORMATION GATEWAY
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case GATEWAY Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
SYSTEM INFORMATION IEC 61850
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case IEC 61850 Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P P P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P P P P P P A P P P A A P P P
SYSTEM INFORMATION BAY OI
Description Iss. Reference Electrical Data Description Labels / States Description Scada Interface IEC Interface Groups Local Display HMI Special Automation Template Conf. Mng.
Use this Matrix Case BAY OI Name : Issue Equipment Link Function Type Long name (35 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Short Name (16 char) SCADA 1 Address SCADA1 Data type SCADA 2 Address SCADA2 Data type SCADA 3 Address SCADA3 Data type SCADA 4 Address SCADA4 Data type IEC Address Part 1 (IEC: LD;LN) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Computers Groups (separator ";") Automations links (separator ";") (add "<" if output) LED MV : Not used xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer Used by ISaGRAF xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used Datapoint Name (in SCE Template) Process Comments
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A U U U P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A P P A A A P P P U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U U U U P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A U A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
U U P A A P A U U A A A U P P P P P P P P P P P P P A P P P P A P P P A A P P P
P U P A A U A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
P P P A A P A P P A A A P P P P P P P P P P P P P P A P P P P A P P P A A P P P
Mapping Language English Français English Spanish Português Brasil Russian German
SHEET : Customer Front Page SHEET : Page de Garde Client SHEET : Customer Front Page SHEET : Página principal Cliente SHEET : Página Inicial Cliente SHEET : Первая Страница Клиента SHEET : Customer Front Page
SHEET : GE Front Page SHEET : Page de Garde GE SHEET : GE Front Page SHEET : Página principal GE SHEET : Pagina Inicial GE SHEET : Первая Страница GE SHEET : GE Front Page
ISSUE REVISION ISSUE REVISION REVISÃO ВЕРСИЯ VERSION
DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPCION DESCRIÇÃO ОПИСАНИЕ BESCHREIBUNG
DATE DATE DATE FECHA DATA ДАТА DATUM
CUSTOMER CLIENT CUSTOMER CLIENTE Cliente ЗАКАЗЧИК KUNDE
GE GE GE GE GE GE GE
CUSTOMER CLIENT CUSTOMER CLIENTE Cliente ЗАКАЗЧИК KUNDE
CONTRACT No. CONTRAT N° CONTRACT No. NO. de CONTRATO Num. do CONTRATO КОНТРАКТ No. AUFTRAG Nr.
ORDER No. Commande N° ORDER No. No. De ORDEN Num. Da Ordem ЗАКАЗ No. BESTELL Nr.
PROJECT: PROJET: PROJECT: PROYECTO: PROJETO: ПРОЕКТ: PROJEKT:
Project Name Nom du Projet Project Name Nombre del proyecto Nome do projeto Название проекта : Projektname
SITE: SITE: SITE: SITIO: OBRA: ОБЪЕКТ: Anlage:
DOCUMENT NUMBER: Numéro de Document : DOCUMENT NUMBER: DOCUMENTO NUMERO: DOCUMENTO Número: НОМЕР ДОКУМЕНТА: Dokument Nummer:
Site Name Nom du Site Site Name Nombre del sitio Nome da obra Название объекта Anlagen Name
xyz-SC-DTL xyz-SC-DTL xyz-SC-DTL xyz-SC-DTL xez-SC-DTL xyz-SC-DTL xyz-SC-DTL
DATE DATE DATE FECHA DATA ДАТА DATUM
SIGNATURE SIGNATURE SIGNATURE FIRMA Assinatura ПОДПИСЬ UNTERSCHRIFT
DOCUMENT TITLE SUBSTATION CONTROL SYSTEM DATA LIST Titre du document LISTE DE DONNEES DU SYSTEME DE Contrôle DE SOUS-STATION DOCUMENT TITLE SUBSTATION CONTROL SYSTEM DATA LIST TITULO DEL DOCUMENTO LISTADO DE DATOS DEL SISTEMA DE CONTROL DE LA SUBESTACION Título DO DOCUMENTO Lista de DADOS DO Sistema de CONTROLE DA SUBESTAÇÃO Заголовок документа ТАБЛИЦА СИГНАЛОВ АСУ DOKUMENT TITEL LEITTECHNIKSYSTEM DatumNPUNKTLISTE
DRAWN CREE DRAWN DRAWN Desenho МНЕМОСХЕМЫ ERSTELLT
DSAgile SUBSTATION CONTROL SYSTEM Data List DSAgile SYSTEME DE COMMANDE DE SOUS-STATION Liste de données DSAgile SUBSTATION CONTROL SYSTEM Data List DSAgile SISTEMA DE CONTROL DE SUBESTACIONES Data List DSAgile Sistema de CONTROLE de SUBESTAÇÕES Lista de Dados DSAgile АВТОМАТИЗИРОВАННАЯ СИСТЕМА УПРАВЛЕНИЯ Таблица Сигналов DSAgile LEITTECHNIK Data List
CHECKED VERIFIE CHECKED REVISADO REVISADO ПРОВЕРЕНО GEPRÜFT
APPROVED APPROUVE APPROVED APROBADO APROVADO УТВЕРЖДЕНО BESTÄTIGT
ISSUED BY: EDITE PAR: ISSUED BY: EMITIDO POR: EMITIDO POR: Выпущено: ERSTELLT VON:
SIZE TAILLE SIZE TAMAÑO TAMANHO РАЗМЕР Größe
PAGES PAGES PAGES PAGINAS PÁGINAS СТРАНИЦЫ SEITEN
ISSUE REVISION ISSUE REVISION REVISÃO ВЕРСИЯ VERSION
A3 A3 A3 A3 A3 A3 A3
GE Parc Eurêka 81, rue Euclide 34000 MONTPELLIER GE Parc Eurêka 81, rue Euclide 34000 MONTPELLIER GE Parc Eurêka 81, rue Euclide 34000 MONTPELLIER GE Parc Eurêka 81, rue Euclide 34000 MONTPELLIER GE Parc Eurêka 81, rue Euclide 34000 MONTPELLIER GE Parc Eurêka 81, rue Euclide 34000 MONTPELLIER GE Parc Eurêka 81, rue Euclide 34000 MONTPELLIER
ESTABLISHED ETABLI PAR ESTABLISHED ESTABLISHED ESTABLISHED ESTABLISHED ESTABLISHED
SHEET : History SHEET : Journal SHEET : History SHEET : Historia SHEET : Histórico SHEET : История SHEET : History
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
PACIDL-A PACIDL-A PACIDL-A PACIDL-A PACIDL-A PACIDL-A PACIDL-A
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN DATA DEBUT DES DONNEES BEGIN DATA INICIO DE DATOS INICIO DOS DADOS НАЧАЛО ДАННЫХ BEGIN DATA
Issue Révision Issue Revisión Revisão Версия Version
Date Date Date Fecha Data Дата Datum
Author Auteur Author Autor Autor Автор Autor
Company Compagnie Company Compañia Companhia Компания Firma
Modifications Modifications Modifications Modificaciones Modificações Изменения Änderungen
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : Equipments SHEET : Equipements SHEET : Equipments SHEET : Equipos SHEET : Equipamentos SHEET : Оборудование SHEET : Equipments
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
EQUIPMENT LIST LISTE DES EQUIPEMENTS EQUIPMENT LIST LISTA DE EQUIPOS Lista de Equipamentos СПИСОК ОБОРУДОВАНИЯ EQUIPMENT LISTE
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Usual Communication Communication usuelle Usual Communication Habitual Comunicación Comunicação usual Передача данных Ublichen Kommunikation
Legacy T104 Master Legacy T104 Maître Legacy T104 Master Legacy T104 Master Legacy T104 Master Legacy T104 Master Legacy T104 Master
Legacy T101 Master Legacy T101 Maître Legacy T101 Master Legacy T101 Master Legacy T101 Master Legacy T101 Master Legacy T101 Master
Boards Cartes Boards Tarjetas Placa Платы Karten
Issue Révision Issue Revisión Revisão Версия Version
NAME NOM NAME NOMBRE NOME ИМЯ NAME
DESCRIPTION (LONG NAME) DESCRIPTION (NOM LONG) DESCRIPTION (LONG NAME) DESCRIPCION (NOMBRE COMPLETO) Descrição (Nome COMPLETO) ОПИСАНИЕ (ДЛИННОЕ ИМЯ) Beschreibung(Long Name)
LINK COMMUNICATION LINK VINCULO VINCULO СВЯЗЬ LINK
REDUNDANT REDONDANCE REDUNDANT REDUNDANTE REDUNDANTE С РЕЗЕРВИРОВАНИЕМ REDUNDANT
TYPE TYPE TYPE TIPO TIPO МОДЕЛЬ TYPE
Substation Name Nom de la Sous-station Substation Name Nombre de subestación Nome do Substação Имя подстанции Stationsname:
Bay mimic Tranche mimic Bay mimic Mímico de bahía Mímico do Painel Мнемосхема Ячейки Bay mimic
Synchronisation mode MODE DE SYNCHRONISATION Synchronisation mode Modo de sincronización Modo de Sincronização Режим синхронизации Synchronisation mode
Network Name NOM DU RESEAU Network Name Nombre de red Nome da rede Сетевое Имя Netzwerk Name
TCP/IP (IEC) Address Adresse TCP/IP (IEC) TCP/IP (IEC) Address Dirección TCP/IP (IEC) Endereço TCP/IP (IEC) TCP/IP (IEC) Адрес TCP/IP (IEC) Addresse
Port 1 Port 1 Port 1 Puerto 1 Porta 1 Порт 1 Port 1
Protocol Name Nom de protocole Protocol Name Nombre de Protocolo Nome do Protocolo ИМЯ Протокола Protocol Name
Port 2 Port 2 Port 2 Puerto 2 Porta 2 Порт 2 Port 2
Protocol Name Nom de protocole Protocol Name Nombre de Protocolo Nome do Protocolo ИМЯ Протокола Protocol Name
Port 3 Port 3 Port 3 Puerto 3 Porta 3 Порт 3 Port 3
Protocol Name Nom de protocole Protocol Name Nombre de Protocolo Nome do Protocolo ИМЯ Протокола Protocol Name
Port 4 Port 4 Port 4 Puerto 4 Porta 4 Порт 4 Port 4
Protocol Name Nom de protocole Protocol Name Nombre de Protocolo Nome do Protocolo ИМЯ Протокола Protocol Name
Id1 T104M (+ IED Addr) Id1 T104M (+ IED Adr) Id1 T104M (+ IED Addr) Id1 T104M (Direcc + IED) Id1 T104M (Direcc + IED) Id1 T104M (+ адрес IED) Id1 T104M (+ IED Addr)
Id2 T104M (+ IED Addr) Id2 T104M (+ IED Adr) Id2 T104M (+ IED Addr) Id2 T104M (Direcc + IED) Id2 T104M (Direcc + IED) Id2 T104M (+ адрес IED) Id2 T104M (+ IED Addr)
Id3 T104M (+ IED Addr) Id3 T104M (+ IED Adr) Id3 T104M (+ IED Addr) Id3 T104M (Direcc + IED) Id3 T104M (Direcc + IED) Id3 T104M (+ адрес IED) Id3 T104M (+ IED Addr)
Id4 T104M (+ IED Addr) Id4 T104M (+ IED Adr) Id4 T104M (+ IED Addr) Id4 T104M (Direcc + IED) Id4 T104M (Direcc + IED) Id4 T104M (+ адрес IED) Id4 T104M (+ IED Addr)
Id1 T101M (+ IED Addr) Id1 T101M (+ IED Adr) Id1 T101M (+ IED Addr) Id1 T101M (Direcc + IED) Id1 T101M (Direcc + IED) Id1 T101M (+ адрес IED) Id1 T101M (+ IED Addr)
Id2 T101M (+ IED Addr) Id2 T101M (+ IED Adr) Id2 T101M (+ IED Addr) Id2 T101M (Direcc + IED) Id2 T101M (Direcc + IED) Id2 T101M (+ адрес IED) Id2 T101M (+ IED Addr)
Id3 T101M (+ IED Addr) Id3 T101M (+ IED Adr) Id3 T101M (+ IED Addr) Id3 T101M (Direcc + IED) Id3 T101M (Direcc + IED) Id3 T101M (+ адрес IED) Id3 T101M (+ IED Addr)
Id4 T101M (+ IED Addr) Id4 T101M (+ IED Adr) Id4 T101M (+ IED Addr) Id4 T101M (Direcc + IED) Id4 T101M (Direcc + IED) Id4 T101M (+ адрес IED) Id4 T101M (+ IED Addr)
IEC61850 Protocol Id Id Protocole IEC61850 IEC61850 Protocol Id IEC61850 Protocolo Id IEC61850 Protocolo Id IEC61850 Протокола Id IEC61850 Protocol Id
OPC Protocol Id Id Protocole OPC OPC Protocol Id OPC Protocolo Id OPC Protocolo Id OPC Протокола Id OPC Protocol Id
DIU2xx DIU2xx DIU2xx DIU2xx DIU2xx DIU2xx DIU2xx
CCU20x CCU20x CCU20x CCU20x CCU20x CCU20x CCU20x
DOU20x DOU20x DOU20x DOU20x DOU20x DOU20x DOU20x
HBU20x HBU20x HBU20x HBU20x HBU20x HBU20x HBU20x
AIU20x AIU20x AIU20x AIU20x AIU20x AIU20x AIU20x
AIU21x AIU21x AIU21x AIU21x AIU21x AIU21x AIU21x
TMU2x0 TMU2x0 TMU2x0 TMU2x0 TMU2x0 TMU2x0 TMU2x0
DSP210 DSP210 DSP210 DSP210 DSP210 DSP210 DSP210
AOU20x AOU20x AOU20x AOU20x AOU20x AOU20x AOU20x
SWx SWx SWx SWx SWx SWx SWx
Extension Racks Racks d'Extension Extension Racks Extensión bastidores Extensão Racks продление стеллажи Erweiterung Racks
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Template Modèle Template Plantilla Panilha Образец Template
Sheet Name Nom de la Feuille Sheet Name Nombre de hoja Nome da Planilha Имя Страницы Sheet Name
DIU32 DIU32 DIU32 DIU32 DIU32 DIU32 DIU32
SUMMARY RESUME SUMMARY RESUMEN RESUMO КРАТКИЙ ZUSAMMENFASSUNG
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : Computers Arrangement SHEET : Arrangement des Calculateurs SHEET : Computers Arrangement SHEET : Computadors Arrangement SHEET : Arranjo dos Computadores SHEET : Компановка контроллеров SHEET : Computers Arrangement
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
MiCOM COMPUTERS HARDWARE DESCRIPTION DESCRIPTION MATERIELLE DES CALCULATEURS MICOM MiCOM COMPUTERS HARDWARE DESCRIPTION DESCRIPCION DEL HARDWARE COMPUTADOR MiCOM Descrição DO HARDWARE COMPUTADOR MiCOM ОПИСАНИЕ УСТРОЙСТВА КОНТРОЛЛЕРОВ MiCOM MiCOM COMPUTERS HARDWARE BESCHREIBUNG
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Auto generated Génération automatique Auto generated Auto generado Auto Geração Автоматически сгенерировано Auto generated
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
ERROR ERREUR ERROR ERROR ERRO ОШИБКА FEHLER
C264 Ext Rack C264 Rack d'Ext. C264 Ext Rack C264 Ext Rack C264 Ext Rack C264 Ext Rack C264 Ext Rack
C264C Ext Rack C264C Rack d'Ext. C264C Ext Rack C264C Ext Rack C264C Ext Rack C264C Ext Rack C264C Ext Rack
Computer type (C264/C264C): Type de Calculateur (C264/C264C): Computer type (C264/C264C): Typo de computador (C264/C264C): Tipo de computador (C264/C264C): Тип контроллера (C264/C264C): Computer type (C264/C264C):
back face Face arriere back face panel posterior Painel Traseiro Тыльная сторона back face
APPLICABLE PRINCIPAL APPLICABLE APLICABLE Aplicável ПРИМЕНЯЕМЫЙ APPLICABLE
REDUNDANT REDONDANCE REDUNDANT REDUNDANTE REDUNDANTE С РЕЗЕРВИРОВАНИЕМ REDUNDANT
PANEL ECRAN PANEL PANEL PAINEL ПАНЕЛЬ PANEL
COMMENTS COMMENTAIRES COMMENTS COMENTARIOS COMENTÃRIOS КОММЕНТАРИИ KOMMENTAR
Port 1 Port 1 Port 1 Puerto 1 Porta 1 Порт 1 Port 1
Port 2 Port 2 Port 2 Puerto 2 Porta 2 Порт 2 Port 2
Port 3 Port 3 Port 3 Puerto 3 Porta 3 Порт 3 Port 3
Port 4 Port 4 Port 4 Puerto 4 Porta 4 Порт 4 Port 4
front slot number: Numéro de position devant: front slot number: número de slot frontal: Número do Slot Frontal: номер слота на фронтальной стороне: front slot number:
COMPUTER NAME NOM DU CALCULATEUR COMPUTER NAME NOMBRE DEL COMPUTADOR Nome do Computador ИМЯ КОНТРОЛЛЕРА COMPUTER NAME
NUMBER NUMERO NUMBER NUMERO NUMERO НОМЕР ANZAHL
BIU240 Port 1 BIU240 Port 1 BIU240 Port 1 BIU240 Puerto 1 BIU240 Porta 1 BIU240 Порт 1 BIU240 Port 1
BIU240 Port 2 BIU240 Port 2 BIU240 Port 2 BIU240 Puerto 2 BIU240 Porta 2 BIU240 Порт 2 BIU240 Port 2
CPU Port 1 CPU Port 1 CPU Port 1 CPU Puerto 1 CPU Porta 1 CPU Портt 1 CPU Port 1
CPU Port 2 CPU Port 2 CPU Port 2 CPU Puerto 2 CPU Porta 2 CPU Порт 2 CPU Port 2
back slot number: Numéro de position arrière: back slot number: número de slot posterior: número de Slot posterior: номер слота на тыльной стороне: back slot number:
Protocol Type Type de Protocole Protocol Type Tipo de protocolo Tipo de Protocolo Тип протокола Protocol Type
CPU 260 + COMMUNICATION CPU 260 + COMMUNICATION CPU 260 + COMMUNICATION CPU 260 + COMUNICACION CPU 260 + COMUNICAÇÃO CPU 260 + ЛИНИИ СВЯЗИ CPU 260 + COMMUNICATION
BIU 241 BIU 241 BIU 241 BIU 241 BIU 241 BIU 241 BIU 241
Baud Rate Vitesse de la communication (en Baud) Baud Rate Bauidos Baud Rate Скорость в бодах Baud Rate
RS Type RS Type RS Type Tipo de RS Tipo de RS Тип RS RS Type
Parity Parité Parity Paridad Paridade Четность Parity
Number Stop bits Nombre de bits de stop Number Stop bits Número de bits de paro Número de bits de paro Number Stop bits Anzahl Stop bits
Number bits Nombre de bits Number bits Número de bits Número de bits Number bits Anzahl bits
Rx Management Gestion de RX Rx Management Administración de Rx Administração de Rx Управление Rx Rx Management
Tx Management Gestion de TX Tx Management Administración de Tx Administração de Tx Управление Tx Tx Management
CTS wired CTS Câblé CTS wired CTS cableadas CTS Linkados CTS wired CTS wired
DTS wired Câblage de DTS DTS wired DTS cableadas DTS Linkados DTS wired DTS wired
CD wired Câblage de CD CD wired CD cableadas CD Linkados CD wired CD wired
logical number: Numéro logique: logical number: número lógico: número lógico: логический номер: logical number:
DCR wired Câblage de DCR DCR wired DCR cableadas DCR Linkados DCR wired DCR wired
CPU 270 + COMMUNICATION CPU 270 + COMMUNICATION CPU 270 + COMMUNICATION CPU 270 + COMUNICACION CPU 270 + COMUNICAÇÃO CPU 270 + ЛИНИИ СВЯЗИ CPU 270 + COMMUNICATION
Computer type (C264/C264C): Type de Calculateur (C264/C264C): Computer type (C264/C264C): Typo de computador (C264/C264C): Tipo de computador (C264/C264C): Тип контроллера (C264/C264C): Computer type (C264/C264C):
C264C C264C C264C C264C C264C C264C C264C
back face Face arriere back face panel posterior Painel Traseiro Тыльная сторона back face
APPLICABLE PRINCIPAL APPLICABLE APLICABLE Aplicável ПРИМЕНЯЕМЫЙ APPLICABLE
REDUNDANT REDONDANCE REDUNDANT REDUNDANTE REDUNDANTE С РЕЗЕРВИРОВАНИЕМ REDUNDANT
PANEL ECRAN PANEL PANEL PAINEL ПАНЕЛЬ PANEL
COMMENTS COMMENTAIRES COMMENTS COMENTARIOS COMENTÃRIOS КОММЕНТАРИИ KOMMENTAR
Port 1 Port 1 Port 1 Puerto 1 Porta 1 Порт 1 Port 1
Port 2 Port 2 Port 2 Puerto 2 Porta 2 Порт 2 Port 2
Port 3 Port 3 Port 3 Puerto 3 Porta 3 Порт 3 Port 3
Port 4 Port 4 Port 4 Puerto 4 Porta 4 Порт 4 Port 4
front slot number: Numéro de position devant: front slot number: número de slot frontal: Número do Slot Frontal: номер слота на фронтальной стороне: front slot number:
COMPUTER NAME NOM DU CALCULATEUR COMPUTER NAME NOMBRE DEL COMPUTADOR Nome do Computador ИМЯ КОНТРОЛЛЕРА COMPUTER NAME
NUMBER NUMERO NUMBER NUMERO NUMERO НОМЕР ANZAHL
BIU240 Port 1 BIU240 Port 1 BIU240 Port 1 BIU240 Puerto 1 BIU240 Porta 1 BIU240 Порт 1 BIU240 Port 1
BIU240 Port 2 BIU240 Port 2 BIU240 Port 2 BIU240 Puerto 2 BIU240 Porta 2 BIU240 Порт 2 BIU240 Port 2
CPU Port 1 CPU Port 1 CPU Port 1 CPU Puerto 1 CPU Porta 1 CPU Портt 1 CPU Port 1
CPU Port 2 CPU Port 2 CPU Port 2 CPU Puerto 2 CPU Porta 2 CPU Порт 2 CPU Port 2
back slot number: Numéro de position arrière: back slot number: número de slot posterior: número de Slot posterior: номер слота на тыльной стороне: back slot number:
Protocol Type Type de Protocole Protocol Type Tipo de protocolo Tipo de Protocolo Тип протокола Protocol Type
TMU2x0 (slot 2/2) TMU2x0 (slot 2/2) TMU2x0 (slot 2/2) TMU2x0 (slot 2/2) TMU2x0 (Slot 2/2) TMU2x0 (слот 2/2) TMU2x0 (slot 2/2)
TMU2x0 (slot 1/2) TMU2x0 (slot 1/2) TMU2x0 (slot 1/2) TMU2x0 (slot 1/2) TMU2x0 (Slot 1/2) TMU2x0 (слот 1/2) TMU2x0 (slot 1/2)
CPU 260 + COMMUNICATION CPU 260 + COMMUNICATION CPU 260 + COMMUNICATION CPU 260 + COMUNICACION CPU 260 + COMUNICAÇÃO CPU 260 + ЛИНИИ СВЯЗИ CPU 260 + COMMUNICATION
BIU 241 BIU 241 BIU 241 BIU 241 BIU 241 BIU 241 BIU 241
Baud Rate Vitesse de la communication (en Baud) Baud Rate Bauidos Baud Rate Скорость в бодах Baud Rate
RS Type RS Type RS Type Tipo de RS Tipo de RS Тип RS RS Type
Parity Parité Parity Paridad Paridade Четность Parity
Number Stop bits Nombre de bits de stop Number Stop bits Número de bits de paro Número de bits de paro Number Stop bits Anzahl Stop bits
Number bits Nombre de bits Number bits Número de bits Número de bits Number bits Anzahl bits
Rx Management Gestion de RX Rx Management Administración de Rx Administração de Rx Управление Rx Rx Management
Tx Management Gestion de TX Tx Management Administración de Tx Administração de Tx Управление Tx Tx Management
CTS wired CTS Câblé CTS wired CTS cableadas CTS Linkados CTS wired CTS wired
DTS wired Câblage de DTS DTS wired DTS cableadas DTS Linkados DTS wired DTS wired
CD wired Câblage de CD CD wired CD cableadas CD Linkados CD wired CD wired
logical number: Numéro logique: logical number: número lógico: número lógico: логический номер: logical number:
DCR wired Câblage de DCR DCR wired DCR cableadas DCR Linkados DCR wired DCR wired
CPU 270 + COMMUNICATION CPU 270 + COMMUNICATION CPU 270 + COMMUNICATION CPU 270 + COMUNICACION CPU 270 + COMUNICAÇÃO CPU 270 + ЛИНИИ СВЯЗИ CPU 270 + COMMUNICATION
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : C264_Template SHEET : C264_Template SHEET : C264_Template SHEET : C264_Template SHEET : C264_Template SHEET : C264_Template SHEET : C264_Template
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
MiCOM C264 DESCRIPTION DESCRIPTION DU MiCOM C264 MiCOM C264 DESCRIPTION DESCRIPCION MiCOM C264 Descrição MiCOM C264 ОПИСАНИЕ MiCOM C264 MiCOM C264 BESCHREIBUNG
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
Computer Name Nom du Calculateur Computer Name Nombre de computador Nome do computador Имя контроллера Computer Name
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Redundant Computer Calculateur Redondant Redundant Computer Computador Redundante Computador Redundante Резервный компьютер Redundant Computer
Auto generated Génération automatique Auto generated Auto generado Auto Geração Автоматически сгенерировано Auto generated
Computer type (C264/C264C) Type de Calculateur (C264/C264C) Computer type (C264/C264C) Tipo de computador (C264/C264C) Tipo de computador (C264/C264C) Тип контроллера (C264/C264C) Computer type (C264/C264C)
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Gateway Passerelle Gateway UTR UTR Шлюз Gateway
Port used (on gateway) Ports utilisés (sur la passerelle) Port used (on gateway) Puerto utilizado (en UTR) Porta utilizada (em UTR) Используемый порт (на шлюз) benutzter Port (Gateway)
SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1
SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2
SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3
SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4
DIGITAL INPUT BOARD DIU32 Carte d'entrées numériques DIU32 DIGITAL INPUT BOARD DIU32 TARJETAS DE ENTRADAS DIGITALES DIU32 Etiquetas de Entradas Digitais DIU32 ПЛАТЫ DIU32 DIGITALE EINGANGSKARTE DIU32
DIGITAL INPUT BOARD DIU2xx Carte d'entrées numériques DIU2xx DIGITAL INPUT BOARD DIU2xx TARJETAS DE ENTRADAS DIGITALES DIU2xx Etiquetas de Entradas Digitais DIU2xx ПЛАТЫ DIU2xx DIGITALE EINGANGSKARTE DIU2xx
Digital Inputs Board Number Numéro de la carte d'entrées numériques Digital Inputs Board Number Tarjeta de entradas digitales Número Etiqueta de Entradas digitais Número Номер платы DI Digital Inputs Board Number
Digital Inputs Board Slot Position de la carte d'entrées numériques Digital Inputs Board Slot Tarjeta de entradas digitales Slot Etiqueta de Entradas digitais Slot Слот платы DI Digital Inputs Board Slot
Digital Inputs Extension Rack Number Numéro rack d'extension de la carte d'entrées numériques Digital Inputs Extension Rack Number Tarjeta de entradas digitales Extensión Rack Número Etiqueta de Entradas digitais Extensão Rack Número продлению стойки Количество DI Digital Inputs Extension Rack Number
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
DI Reference Référence DI DI Reference DI Referencia DI Referência Ссылка DI DI Referenz
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels / States Libellés/Etats Labels / States Etiquetas/Estados Etiquetas/Estados Метки / Состояния Labels / States
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Groups Groupes Groups Grupos Grupos Группы Gruppen
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Slot Position Slot Slot Slot Слот Slot
Channel Voie Channel Canal Canal Канал Channel
Function Fonction Function Función Função Функция Function
Type (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Simple/DPS=Double/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple) Tipo (SPS=Sencilla/DPS=Dual/MPS=Multiple) Tipo (SPS=Simples/DPS=Duplo/MPS=Múltiplo) Тип (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 Multiple : label d'état (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 Multiple : Texto (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 Múltiplo : Texto (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 Множественный: Обозначение (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique = 01 Multiple : Numéro d'état (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 Multiple : Número de estado (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 Múltiplo : Número de estado (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 Множественный : Состояние Number (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
Computers Groups (separator ";") Groupes de calculateur (séparateur ";") Computers Groups (separator ";") Grupos de Computadoras (separador ";") Grupos de Computadores (separador ";") Группы контроллеров (разделитель ";") Computers Gruppen (separator ";")
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
LED LED LED LED LED индикатор LED
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Is a xPC Feedback Est un retour de position xPC Is a xPC Feedback Es una xPC de retroalimentación É FeedBack de xPC Присутствует xPC обратная связь Is a xPC Feedback
Acts on xPC Acté sur xPC Acts on xPC Actúa en xPC Atua em xPC Действует на с xPC Acts on xPC
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
DIGITAL OUTPUT BOARD DOU20x Carte de sorties numériques DOU20x DIGITAL OUTPUT BOARD DOU20x TARJETAS DIGITALES SALIDAS DOU20x Placas de Saídas Digitais DOU20x ПЛАТЫ DOU20x DIGITALE AUSGANGSKARTE DOU20x
Digital Outputs Board Number Numéro de la carte de sorties numériques Digital Outputs Board Number Número de tarjeta de salidas digitales Número de Etiqueta de saidas digitais Номер платы DO Digitale Ausgangskarte Nummer
Digital Outputs Board Slot Position de la carte de sorties numériques Digital Outputs Board Slot Slot de trajeta de salidas digitales Slot de trajeta de saidas digitais Слот платы DO Digitale Ausgangskarte Steckplatz
Digital Outputs Extension Rack Number Numéro rack d'extension de la carte de sorties numériques Digital Outputs Extension Rack Number Tarjeta de salidas digitales Extensión Rack Número Etiqueta de saidas digitais Extensão Rack Número продлению стойки Количество DO Digitale Ausgangskarte Extension Rack Nummer
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
DO Reference Référence DO DO Reference Referencia DO Referência DO Ссылка DO DO Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Control Contrôle Local Local Control Control Local Controle Local местного контроля Local Control
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Slot Position Slot Slot Slot Слот Slot
Channel Voie Channel Canal Canal Канал Channel
Function Fonction Function Función Função Функция Function
Type (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Simple/DPC=Double/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch) Tipo (SPC=Sencilla/DPC=Dual/DS=Dual Switch) Tipo (SPC=Simples/DPC=Duplo/DS=Dual Switch) Тип (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique =01 (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Control Contrôle LCD LCD Control Control LCD Ordem desde LCD Управление LCD LCD Control
HMI Control Contrôle HMI HMI Control Control IHM Ordem desde IHM Управление HMI HMI Control
Has a xPS Feedback A un retour de position xPS Has a xPS Feedback Contiene retroalimentación xPS Possui FeedBack xPS имеет xPS отзывы Has a xPS Feedback
Is activated by xPS Est activé par xPS Is activated by xPS Es activado por xPS É ativado por xPS Активируется с помощью xPS Is activated by xPS
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Relay Relais Relay Relé Relé Реле Relay
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
HIGH BREAK UNIT BOARD HBU20x Carte de sorties numériques HBU20x HIGH BREAK UNIT BOARD HBU20x TARJETAS HBU SALIDAS HBU20x Placas de Saídas Digitais DOU20x ПЛАТЫ HBU20x HBU AUSGANGSKARTE HBU20x
HBU Board Number Numéro de la carte de sorties numériques HBU HBU Board Number Número de tarjeta de salidas digitales Número de Etiqueta de saidas HBU Номер платы HBU HBU Ausgangskarte Nummer
HBU Board Slot Position de la carte de sorties numériques HBU HBU Board Slot Slot de trajeta de salidas digitales Slot de trajeta de saidas HBU Слот платы HBU HBU Ausgangskarte Steckplatz
HBU Extension Rack Number Numéro rack d'extension de la carte de sorties numériques HBU HBU Extension Rack Number Tarjeta de salidas digitales Extensión Rack Número Etiqueta de saidas HBU Extensão Rack Número продлению стойки Количество HBU HBU Ausgangskarte Extension Rack Nummer
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
DO Reference Référence DO DO Reference Referencia DO Referência DO Ссылка DO DO Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Control Contrôle Local Local Control Control Local Controle Local местного контроля Local Control
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Slot Position Slot Slot Slot Слот Slot
Channel Voie Channel Canal Canal Канал Channel
Function Fonction Function Función Função Функция Function
Type (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Simple/DPC=Double/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch) Tipo (SPC=Sencilla/DPC=Dual/DS=Dual Switch) Tipo (SPC=Simples/DPC=Duplo/DS=Dual Switch) Тип (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique =01 (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Control Contrôle LCD LCD Control Control LCD Ordem desde LCD Управление LCD LCD Control
HMI Control Contrôle HMI HMI Control Control IHM Ordem desde IHM Управление HMI HMI Control
Has a xPS Feedback A un retour de position xPS Has a xPS Feedback Contiene retroalimentación xPS Possui FeedBack xPS имеет xPS отзывы Has a xPS Feedback
Is activated by xPS Est activé par xPS Is activated by xPS Es activado por xPS É ativado por xPS Активируется с помощью xPS Is activated by xPS
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Relay Relais Relay Relé Relé Реле Relay
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
DIGITAL INPUT/OUTPUT BOARD CCU20x Carte entrées/sorties numériques CCU20x DIGITAL INPUT/OUTPUT BOARD CCU20x TARJETAS DIGITALES ENTRADAS/SALIDAS CCU20x Etiquetas digitais Entradas/saidas CCU20x ПЛАТЫ CCU20x DIGITAL EINGANGS-/AUSGANGSKARTE U200
DI/DO Board Number Numéro de la carte DI/DO DI/DO Board Number Número de tarjeta DI/DO Número de Etiqueta DI/DO Номер плат DI/DO DI/DO Karte Nummer
DI/DO Board Slot Position de la carte DI/DO DI/DO Board Slot Slot de Tarjeta DI/DO Slot do Cartão DI/DO Слот платы DI/DO DI/DO Karte Steckplatz
DI/DO Extension Rack Number Numéro rack d'extension de la carte DI/DO DI/DO Extension Rack Number Tarjeta DI/DO Extensión Rack Número Etiqueta DI/DO Extensão Rack Número продлению стойки Количество DI/DO DI/DO Extension Rack Nummer
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
DI Reference Référence DI DI Reference DI Referencia DI Referência Ссылка DI DI Referenz
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels / States Libellés/Etats Labels / States Etiquetas/Estados Etiquetas/Estados Метки / Состояния Labels / States
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Groups Groupes Groups Grupos Grupos Группы Gruppen
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Slot Position Slot Slot Slot Слот Slot
Channel Voie Channel Canal Canal Канал Channel
Function Fonction Function Función Função Функция Function
Type (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Simple/DPS=Double/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple) Tipo (SPS=Sencilla/DPS=Dual/MPS=Multiple) Tipo (SPS=Simples/DPS=Duplo/MPS=Múltiplo) Тип (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 Multiple : label d'état (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 Multiple : Texto (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 Múltiplo : Texto (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 Множественный: Обозначение (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique = 01 Multiple : Numéro d'état (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 Multiple : Número de estado (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 Múltiplo : Número de estado (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 Множественный : Состояние Number (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
Computers Groups (separator ";") Groupes de calculateur (séparateur ";") Computers Groups (separator ";") Grupos de Computadoras (separador ";") Grupos de Computadores (separador ";") Группы контроллеров (разделитель ";") Computers Gruppen (separator ";")
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
LED LED LED LED LED индикатор LED
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Is a xPC Feedback Est un retour de position xPC Is a xPC Feedback Es una xPC de retroalimentación É FeedBack de xPC Присутствует xPC обратная связь Is a xPC Feedback
Acts on xPC Acté sur xPC Acts on xPC Actúa en xPC Atua em xPC Действует на с xPC Acts on xPC
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
DO Reference Référence DO DO Reference Referencia DO Referência DO Ссылка DO DO Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Control Contrôle Local Local Control Control Local Controle Local местного контроля Local Control
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Slot Position Slot Slot Slot Слот Slot
Channel Voie Channel Canal Canal Канал Channel
Function Fonction Function Función Função Функция Function
Type (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Simple/DPC=Double/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch) Tipo (SPC=Sencilla/DPC=Dual/DS=Dual Switch) Tipo (SPC=Simples/DPC=Duplo/DS=Dual Switch) Тип (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique =01 (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Control Contrôle LCD LCD Control Control LCD Ordem desde LCD Управление LCD LCD Control
HMI Control Contrôle HMI HMI Control Control IHM Ordem desde IHM Управление HMI HMI Control
Has a xPS Feedback A un retour de position xPS Has a xPS Feedback Contiene retroalimentación xPS Possui FeedBack xPS имеет xPS отзывы Has a xPS Feedback
Is activated by xPS Est activé par xPS Is activated by xPS Es activado por xPS É ativado por xPS Активируется с помощью xPS Is activated by xPS
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Relay Relais Relay Relé Relé Реле Relay
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
ANALOG INPUT BOARD AIU21x Carte d'entrées analogiques AIU21x ANALOG INPUT BOARD AIU21x TARJETAS DE ENTRADAS ANALOGICAS AIU21x Etiquetas de Entradas Analógicas AIU21x ПЛАТЫ AIU21x ANALOGE EINGANGSKARTE AIU21x
ANALOG INPUT BOARD AIU20x Carte d'entrées analogiques AIU20x ANALOG INPUT BOARD AIU20x TARJETAS DE ENTRADAS ANALOGICAS AIU20x Etiquetas de Entradas Analógicas AIU20x ПЛАТЫ AIU20x ANALOGE EINGANGSKARTE AIU20x
Analog Input Board Number Numéro de la carte d'entrées analogiques Analog Input Board Number Número de tarjeta de entradas analógicas Número de Etiqueta de Entradas Analógicas Номер платы AI Analogeingangskarten Nummer
Analog Input Board Slot Position de la carte d'entrées analogiques Analog Input Board Slot Slot de Tarjeta de entradas analógicas Slot do Cartão de Entradas Analógicas Слот платы AI Analogeingangskarten Steckplatz
Analog Input Extension Rack Number Numéro rack d'extension de la carte d'entrées analogiques Analog Input Extension Rack Number Tarjeta de entradas analógicas Extensión Rack Número Etiqueta de Entradas Analógicas Extensão Rack Número продлению стойки Количество AI Analogeingangskarten Extension Rack Nummer
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
AI Reference Référence AI AI Reference Referencia AI Referência AI Ссылка AI AI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Link Lien Link Vínculo Vínculo Связь Link
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Channel Voie Channel Canal Canal Канал Channel
Transducer Type Type de Transducteur Transducer Type Tipo de transductor Tipo de Transdutor Тип преобразователя Transducer Type
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Corresponding AI Value at Transducer minimum Correspond à la valeur AI minimum du transducteur Corresponding AI Value at Transducer minimum Valor AI correspondiente al mínimo del transductor Valor AI correspondente ao Mínimo do Transdutor Значение AI, соответствующее минимуму преобразователя Corresponding AI Value at Transducer minimum
Corresponding AI Value at Transducer Maximum Correspond à la valeur AI maximum du transducteur Corresponding AI Value at Transducer Maximum Valor AI correspondiente al Máximo del transductor Valor AI correspondente ao Máximo do Transdutor Значение AI, соответствующее максимуму преобразователя Corresponding AI Value at Transducer Maximum
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Integrated by COUNTER Intégré par le Compteur Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
CT/VT ANALOG INPUT BOARD TMU2x0 Module Analogique CT/VT TMU2x0 CT/VT ANALOG INPUT BOARD TMU2x0 CT/VT TARJETAS DE ENTRADAS ANALOGICAS TMU2x0 CT/VT Etiquetas de Entradas Analógicas TMU2x0 ПЛАТЫ АНАЛОГОВЫЙ ВХОД CT/VT TMU2x0 CT/VT ANALOGE EINGANGSKARTE TMU2x0
CT/VT Board Number Numéro du module CT/VT CT/VT Board Number CT/VT Número de tarjeta Número do Cartão CT/VT Номер платы CT/VT CT/VT Karte Nummer
CT/VT Board Slot Position du module CT/VT CT/VT Board Slot CT/VT Slot de Tarjeta CT/VT Slot do Cartão Слот платы CT/VT CT/VT Karte Steckplatz
CT acquisition Acquisition TC CT acquisition CT adquisición CT aquisição Снятие значения тока CT acquisition
VT acquisition Acquisition TT VT acquisition VT adquisición VT aquisição Снятие значения напряжения VT acquisition
Nominal Current Courant Nominal Nominal Current Corriente nominal Corrente Nominal Номинальный ток Nennstrom
Nominal Voltage Tension Nominale Nominal Voltage Voltaje nominal Tensão Nominal Номинальное напряжение Nennspannung
CT/VT Board Model Modèle de carte CT/VT CT/VT Board Model CT/VT Modelo de Tarjeta CT/VT Modo do Cartão CT/VT борту модели CT/VT Board Model
CT/VT Extension Rack Number Numéro rack d'extension de la carte CT/VT CT/VT Extension Rack Number CT/VT Extensión Rack Número CT/VT Extensão Rack Número продлению стойки Количество CT/VT CT/VT Extension Rack Nummer
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
AI Reference Référence AI AI Reference Referencia AI Referência AI Ссылка AI AI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Link Lien Link Vínculo Vínculo Связь Link
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Input type (U/I) Type d'entrée (U/I) Input type (U/I) Tipo de entrada (U/I) Tipo de Entrada (U/I) Тип входа (U/I) Input type (U/I)
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Corresponding AI Value at minimum Correspond à la valeur AI minimum Corresponding AI Value at minimum Valor AI correspondiente al mínimo Valor AI correspondente ao Mínimo Значение AI, соответствующее минимуму Corresponding AI Value at minimum
Corresponding AI Value at Maximum Correspond à la valeur AI maximum Corresponding AI Value at Maximum Valor AI correspondiente al Máximo Valor AI correspondente ao Máximo Значение AI, соответствующее максимуму Corresponding AI Value at Maximum
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Integrated by COUNTER Intégré par le Compteur Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
IED NAME : NOM DE l'IED : IED NAME : NOMBRE DE IED : Nome do IED : ИМЯ IED : IED NAME :
DIGITAL INFORMATION FROM IED ENTREES NUMERIQUES DE l'IED DIGITAL INFORMATION FROM IED INFORMACION DIGITAL DESDE IED Informação Digital deste IED ЦИФРОВАЯ ИНФОРМАЦИЯ С IED DIGITALE INFORMATIONEN VON IED
IED name NOM DE l'IED IED name NOMBRE DE IED Nome do IED Имя IED IED name
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
IED DI Reference Référence de la carte d'entrée numérique de l'IED IED DI Reference DI Referencia IED DI Referência IED IED DI ссылка IED DI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels / States Libellés/Etats Labels / States Etiquetas/Estados Etiquetas/Estados Метки / Состояния Labels / States
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Groups Groupes Groups Grupos Grupos Группы Gruppen
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Information Adresse T103: ASDU nb;Fonction type MODBUS: Mapping Adresse;Bit nb DNP3: Adresse IEC: LD;LN T10X MASTER: Information Address T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Dirección de información T103: ASDU no;Tipo de función MODBUS: Dirección de mapeo;Bit no. DNP3: Dirección IEC: LD;LN T10X MASTER: Information Address T101: Endereço de Informação T103: ASDU no;Tipo de Função MODBUS: Endereço de Mapeamento;Bit no. DNP3: Endereço IEC: LD;LN T10X MASTER: Information Address T101: адрес информации T103: Номер ASDU ;Тип функции MODBUS: Адрес сигнала;Номер бита DNP3: Адрес IEC: LD;LN T10X MASTER: Information Address T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address
T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101:Adresse Commune ASDU;;Mode de détection T103: Information nb;Adresse CommuneASDU;Mode de détection MODBUS: Fonction;;Mode de détection DNP3: ;;Mode de détection IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Dirección común ASDU;;DetectMode T103: No. de información;Dirección común ASDU;DetectMode MODBUS: Función;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Endereço comum ASDU;;DetectMode T103: No. de Informação;Endereço comum ASDU;DetectMode MODBUS: Função;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Общий адрес ASDU;;DetectMode T103: информационный номер;Общий адрес ASDU;DetectMode MODBUS: Функция;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU;;DetectMode T103: Information nb;Common address ASDU;DetectMode MODBUS: Function;;DetectMode DNP3: ;;DetectMode IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type
Function Fonction Function Función Função Функция Function
Type (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Simple/DPS=Double/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple) Tipo (SPS=Sencilla/DPS=Dual/MPS=Multiple) Tipo (SPS=Simples/DPS=Duplo/MPS=Múltiplo) Тип (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 Multiple : label d'état (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 Multiple : Texto (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 Múltiplo : Texto (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 Множественный: Обозначение (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique = 01 Multiple : Numéro d'état (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 Multiple : Número de estado (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 Múltiplo : Número de estado (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 Множественный : Состояние Number (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
Computers Groups (separator ";") Groupes de calculateur (séparateur ";") Computers Groups (separator ";") Grupos de Computadoras (separador ";") Grupos de Computadores (separador ";") Группы контроллеров (разделитель ";") Computers Gruppen (separator ";")
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
LED LED LED LED LED индикатор LED
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Is a xPC Feedback Est un retour de position xPC Is a xPC Feedback Es una xPC de retroalimentación É FeedBack de xPC Присутствует xPC обратная связь Is a xPC Feedback
Acts on xPC Acté sur xPC Acts on xPC Actúa en xPC Atua em xPC Действует на с xPC Acts on xPC
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
DIGITAL INFORMATION TO IED SORTIES NUMERIQUES DE l'IED DIGITAL INFORMATION TO IED INFORMACION DIGITAL HACIA IED Informação Digital Ajuste do IED ЦИФРОВАЯ ИНФОРМАЦИЯ К IED DIGITALE INFORMATIONEN AN IED
IED name NOM DE l'IED IED name NOMBRE DE IED Nome do IED Имя IED IED name
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
IED DO Reference Référence de la carte de sortie numérique de l'IED IED DO Reference IED Referencia DO IED Referência DO IED DO ссылка IED DO Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Control Contrôle Local Local Control Control Local Controle Local местного контроля Local Control
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Information Adresse T103: ASDU nb;Fonction type MODBUS: Mapping Adresse;Bit nb DNP3: Adresse IEC: LD;LN T10X MASTER: Information Address T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Dirección de información T103: ASDU no;Tipo de función MODBUS: Dirección de mapeo;Bit no. DNP3: Dirección IEC: LD;LN T10X MASTER: Information Address T101: Endereço de Informação T103: ASDU no;Tipo de Função MODBUS: Endereço de Mapeamento;Bit no. DNP3: Endereço IEC: LD;LN T10X MASTER: Information Address T101: адрес информации T103: Номер ASDU ;Тип функции MODBUS: Адрес сигнала;Номер бита DNP3: Адрес IEC: LD;LN T10X MASTER: Information Address T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;Bit nb DNP3: Address IEC: LD;LN T10X MASTER: Information Address
T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101:Adresse Commune ASDU;;Type d'Ordre T103: Information nb;Adresse Commune ASDU;Type d'Ordre MODBUS: Fonction;;Type d'Ordre DNP3: ;;Type d'Ordre IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Dirección común ASDU;;OrderType T103: No. de información;Dirección común ASDU;OrderType MODBUS: Función;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Endereço comum ASDU;;OrderType T103: No. de Informação;Endereço comum ASDU;OrderType MODBUS: Função;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Общий адрес ASDU;;OrderType T103: информационный номер;Общий адрес ASDU;OrderType MODBUS: Функция;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type
Function Fonction Function Función Função Функция Function
Type (SPC=Single/DPC=Dual) Type (SPC=Simple/DPC=Double) Type (SPC=Single/DPC=Dual) Tipo (SPC=Sencilla/DPC=Dual) Tipo (SPC=Simples/DPC=Duplo) Тип (SPC=Single/DPC=Dual) Type (SPC=Single/DPC=Dual)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique =01 (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Control Contrôle LCD LCD Control Control LCD Ordem desde LCD Управление LCD LCD Control
HMI Control Contrôle HMI HMI Control Control IHM Ordem desde IHM Управление HMI HMI Control
Has a xPS Feedback A un retour de position xPS Has a xPS Feedback Contiene retroalimentación xPS Possui FeedBack xPS имеет xPS отзывы Has a xPS Feedback
Is activated by xPS Est activé par xPS Is activated by xPS Es activado por xPS É ativado por xPS Активируется с помощью xPS Is activated by xPS
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
ANALOG INFORMATION FROM IED ENTREES ANALOGIQUES DE l'IED ANALOG INFORMATION FROM IED INFORMACION ANALOGICA DESDE IED Informação Analógica deste IED АНАЛОГОВАЯ ИНФОРМАЦИЯ С IED ANALOGINFORMATIONEN VON IED
IED name NOM DE l'IED IED name NOMBRE DE IED Nome do IED Имя IED IED name
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
IED AI Reference Référence de la carte d'entrée analogique de l'IED IED AI Reference Referencia AI IED Referência AI IED IED AI ссылка IED AI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Link Lien Link Vínculo Vínculo Связь Link
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Information Adresse T103: ASDU nb;Fonction type; Unité de la MV MODBUS: Mapping Adresse;Format de la donnée DNP3: Adresse IEC: LD;LN T10X MASTER: Information Address T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Dirección de información T103: ASDU no;Tipo de función;Unidad de MV MODBUS: Dirección de mapeo;Format de Dado DNP3: Dirección IEC: LD;LN T10X MASTER: Information Address T101: Endereço de Informação T103: ASDU no;Tipo de Função;Unidade do MV MODBUS: Endereço de Mapeamento;Format de Dado DNP3: Endereço IEC: LD;LN T10X MASTER: Information Address T101: адрес информации T103: Номер ASDU ;Тип функции;Unit ofr the MV MODBUS: Адрес сигнала;DataFormat DNP3: Адрес IEC: LD;LN T10X MASTER: Information Address T101: Information Address T103: ASDU nb;Function type;Unit of the MEAS MODBUS: Mapping address;Data Format DNP3: Address IEC: LD;LN T10X MASTER: Information Address
T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101:Adresse Commune ASDU T103: Information nb;Adresse Commune ASDU; index dans l'ASDU MODBUS: Fonction DNP3: Non utilisé IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Dirección común ASDU T103: No. de información;Dirección común ASDU;Indice in ASDU MODBUS: Función DNP3: No utilizado IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Endereço comum ASDU T103: No. de Informação;Endereço comum ASDU;Indice in ASDU MODBUS: Função DNP3: Não Utilizado IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Общий адрес ASDU T103: информационный номер;Общий адрес ASDU;Index in ASDU MODBUS: Функция DNP3: Не используется IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU T103: Information nb;Common address ASDU;Index in ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Corresponding AI Value at minimum Correspond à la valeur AI minimum Corresponding AI Value at minimum Valor AI correspondiente al mínimo Valor AI correspondente ao Mínimo Значение AI, соответствующее минимуму Corresponding AI Value at minimum
Corresponding AI Value at Maximum Correspond à la valeur AI maximum Corresponding AI Value at Maximum Valor AI correspondiente al Máximo Valor AI correspondente ao Máximo Значение AI, соответствующее максимуму Corresponding AI Value at Maximum
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Integrated by COUNTER Intégré par le Compteur Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
ANALOG INFORMATION TO IED SORTIES ANALOGIQUES DE l'IED ANALOG INFORMATION TO IED INFORMACION ANALOGICA HACIA IED Informação Analógica Ajuste do IED АНАЛОГОВАЯ ИНФОРМАЦИЯ К IED ANALOGINFORMATIONEN AN IED
IED name NOM DE l'IED IED name NOMBRE DE IED Nome do IED Имя IED IED name
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
IED AI Reference Référence de la carte d'entrée analogique de l'IED IED AI Reference Referencia AI IED Referência AI IED IED AI ссылка IED AI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Information Adresse;Format de Sortie T103: ASDU nb;Fonction type;Format de Sortie MODBUS: Mapping Adresse DNP3: Adresse IEC: LD;LN T10X MASTER: Information Address T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Dirección de información;Output Format T103: ASDU no;Tipo de función;Output Format MODBUS: Dirección de mapeo DNP3: Dirección IEC: LD;LN T10X MASTER: Information Address T101: Endereço de Informação;Output Format T103: ASDU no;Tipo de Função;Output Format MODBUS: Endereço de Mapeamento DNP3: Endereço IEC: LD;LN T10X MASTER: Information Address T101: адрес информации;Output Format T103: Номер ASDU ;Тип функции;Output Format MODBUS: Адрес сигнала DNP3: Адрес IEC: LD;LN T10X MASTER: Information Address T101: Information Address;Output Format T103: ASDU nb;Function type;Output Format MODBUS: Mapping address DNP3: Address IEC: LD;LN T10X MASTER: Information Address
T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101:Adresse Commune ASDU;;Type d'Ordre T103: Information nb;Adresse Commune ASDU;Type d'Ordre MODBUS: Fonction;;Type d'Ordre DNP3: ;;Type d'Ordre IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Dirección común ASDU;;OrderType T103: No. de información;Dirección común ASDU;OrderType MODBUS: Función;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Endereço comum ASDU;;OrderType T103: No. de Informação;Endereço comum ASDU;OrderType MODBUS: Função;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Общий адрес ASDU;;OrderType T103: информационный номер;Общий адрес ASDU;OrderType MODBUS: Функция;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Common address ASDU;;OrderType T103: Information nb;Common address ASDU;OrderType MODBUS: Function;;OrderType DNP3: ;;OrderType IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Corresponding AI Value at minimum Correspond à la valeur AI minimum Corresponding AI Value at minimum Valor AI correspondiente al mínimo Valor AI correspondente ao Mínimo Значение AI, соответствующее минимуму Corresponding AI Value at minimum
Corresponding AI Value at Maximum Correspond à la valeur AI maximum Corresponding AI Value at Maximum Valor AI correspondiente al Máximo Valor AI correspondente ao Máximo Значение AI, соответствующее максимуму Corresponding AI Value at Maximum
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
END OF IED DATA FIN DES DONNEES DE l'IED END OF IED DATA FIN DE DATOS IED FIM DOS DADOS IED КОНЕЦ ДАННЫХ ПО IED END OF IED DATA
DI GROUPS GROUPES ENTREES NUMERIQUES DI GROUPS Grupos DI Grupos DI Группы DI DI GROUPS
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
Group DI Reference Référence du Groupes des DI Group DI Reference Referencia de grupo DI Referência de grupo DI Группа DI ссылку Gruppe DI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Groups Groupes Groups Grupos Grupos Группы Gruppen
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Number Numéro Number Número Número Номер Number
Group Operator Opérateur du Groupe Group Operator Operador de grupo Operador de grupo Группа оператора Gruppe Operator
Function Fonction Function Función Função Функция Function
Type (S=Single) Type (S=Simple) Type (S=Single) Tipo (S=Sencilla) Tipo (S=Simples) Тип (S=Single) Type (S=Single)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 (16 char) Simple : Texte à l'état électrique = 1 (16 car) Single : Text at electrical state = 1 (16 char) Sencilla : Texto en estado eléctrico = 1 (16 caract) Simples: Texto em estado Elétrico = 1 (16 caract) Одиночный : Обозначение электрического состояния = 1 (16 символов) Single : Text at electrical state = 1 (16 char)
Single : Text at electrical state = 0 (16 char) Simple : Texte à l'état électrique = 0 (16 car) Single : Text at electrical state = 0 (16 char) Sencilla : Texto en estado eléctrico = 0 (16 caract) Simples: Texto em estado Elétrico = 0 (16 caract) Одиночный : Обозначение электрического состояния = 0 (16 символов) Single : Text at electrical state = 0 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
Computers Groups (separator ";") Groupes de calculateur (séparateur ";") Computers Groups (separator ";") Grupos de Computadoras (separador ";") Grupos de Computadores (separador ";") Группы контроллеров (разделитель ";") Computers Gruppen (separator ";")
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
LED LED LED LED LED индикатор LED
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Is a xPC Feedback Est un retour de position xPC Is a xPC Feedback Es una xPC de retroalimentación É FeedBack de xPC Присутствует xPC обратная связь Is a xPC Feedback
Acts on xPC Acté sur xPC Acts on xPC Actúa en xPC Atua em xPC Действует на с xPC Acts on xPC
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
SELF GENERATED DIGITAL INFORMATION ENTREES NUMERIQUES AUTOMATIQUES SELF GENERATED DIGITAL INFORMATION INFORMACION DIGITAL AUTO GENERADA Informação Digital Auto Gerada ЦИФРОВАЯ ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ SELBSTGENERIERTE DIGITALE INFORMATIONEN
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
Self DI Reference Référence interne DI Self DI Reference Referencia DI auto Referência DI Auto Собственная ссылка DI Self DI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels / States Libellés/Etats Labels / States Etiquetas/Estados Etiquetas/Estados Метки / Состояния Labels / States
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Groups Groupes Groups Grupos Grupos Группы Gruppen
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Number Numéro Number Número Número Номер Number
Function Fonction Function Función Função Функция Function
Type (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Simple/DPS=Double/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple) Tipo (SPS=Sencilla/DPS=Dual/MPS=Multiple) Tipo (SPS=Simples/DPS=Duplo/MPS=Múltiplo) Тип (SPS=Single/DPS=Dual/MPS=Multiple) Type (SPS=Single/DPS=Dual/MPS=Multiple)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 Multiple : label d'état (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 Multiple : Texto (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 Múltiplo : Texto (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 Множественный: Обозначение (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Text label (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique = 01 Multiple : Numéro d'état (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 Multiple : Número de estado (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 Múltiplo : Número de estado (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 Множественный : Состояние Number (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : State Number (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
Computers Groups (separator ";") Groupes de calculateur (séparateur ";") Computers Groups (separator ";") Grupos de Computadoras (separador ";") Grupos de Computadores (separador ";") Группы контроллеров (разделитель ";") Computers Gruppen (separator ";")
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
LED LED LED LED LED индикатор LED
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Is a xPC Feedback Est un retour de position xPC Is a xPC Feedback Es una xPC de retroalimentación É FeedBack de xPC Присутствует xPC обратная связь Is a xPC Feedback
Acts on xPC Acté sur xPC Acts on xPC Actúa en xPC Atua em xPC Действует на с xPC Acts on xPC
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Automation Origin (if any) Automatisme d'origine (si existant) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
SELF GENERATED DIGITAL OUTPUT INFORMATION SORTIES NUMERIQUES AUTOMATIQUES SELF GENERATED DIGITAL OUTPUT INFORMATION INFORMACION DE SALIDAS DIGITALES AUTO GENERADAS Informação de saidas Digitais Auto Geradas ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ ЦИФРОВЫМИ ВЫХОДАМИ SELBSTGENERIERTE DIGITALE AUSGANGSINFORMATIONEN
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
Self DO Reference Référence interne DO Self DO Reference Referencia DO Auto Referência DO Auto Собственная DO ссылка Self DO Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Control Contrôle Local Local Control Control Local Controle Local местного контроля Local Control
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Number Numéro Number Número Número Номер Number
Function Fonction Function Función Função Функция Function
Type (SPC=Single/DPC=Dual) Type (SPC=Simple/DPC=Double) Type (SPC=Single/DPC=Dual) Tipo (SPC=Sencilla/DPC=Dual) Tipo (SPC=Simples/DPC=Duplo) Тип (SPC=Single/DPC=Dual) Type (SPC=Single/DPC=Dual)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique =01 (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Control Contrôle LCD LCD Control Control LCD Ordem desde LCD Управление LCD LCD Control
HMI Control Contrôle HMI HMI Control Control IHM Ordem desde IHM Управление HMI HMI Control
Has a xPS Feedback A un retour de position xPS Has a xPS Feedback Contiene retroalimentación xPS Possui FeedBack xPS имеет xPS отзывы Has a xPS Feedback
Is activated by xPS Est activé par xPS Is activated by xPS Es activado por xPS É ativado por xPS Активируется с помощью xPS Is activated by xPS
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Relay Relais Relay Relé Relé Реле Relay
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Automation Origin (if any) Automatisme d'origine (si existant) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
SELF GENERATED ANALOG INFORMATION ENTREES ANALOGIQUES AUTOMATIQUES SELF GENERATED ANALOG INFORMATION INFORMACION ANALOGICA AUTO GENERADA Informação Analógica Auto Gerada АНАЛОГОВАЯ ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ SELBST GENERIERTE ANALOGINFORMATIONEN
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
Self AI Reference Référence interne AI Self AI Reference Referencia AI auto Referência AI Automática Собственная ссылка AI Self AI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Link Lien Link Vínculo Vínculo Связь Link
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Number Numéro Number Número Número Номер Number
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Corresponding AI Value at Transducer minimum Correspond à la valeur AI minimum du transducteur Corresponding AI Value at Transducer minimum Valor AI correspondiente al mínimo del transductor Valor AI correspondente ao Mínimo do Transdutor Значение AI, соответствующее минимуму преобразователя Corresponding AI Value at Transducer minimum
Corresponding AI Value at Transducer Maximum Correspond à la valeur AI maximum du transducteur Corresponding AI Value at Transducer Maximum Valor AI correspondiente al Máximo del transductor Valor AI correspondente ao Máximo do Transdutor Значение AI, соответствующее максимуму преобразователя Corresponding AI Value at Transducer Maximum
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Integrated by COUNTER Intégré par le Compteur Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER Integrated by COUNTER
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Automation Origin (if any) Automatisme d'origine (si existant) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : C364_Template SHEET : C364_Template SHEET : C364_Template SHEET : C364_Template SHEET : C364_Template SHEET : C364_Template SHEET : C364_Template
MiCOM C364 DESCRIPTION DESCRIPTION DU MiCOM C364 MiCOM C364 DESCRIPTION Descripción MiCOM C364 Descrição MiCOM C364 ОПИСАНИЕ MiCOM C364 MiCOM C364 BESCHREIBUNG
DI GROUPS GROUPES DES ENTREES NUMERIQUES DI GROUPS Grupos DI Grupos DI DI Группы DI GROUPS
SELF GENERATED DIGITAL INFORMATION ENTREES NUMERIQUES AUTOMATIQUES SELF GENERATED DIGITAL INFORMATION INFORMACION DIGITAL AUTO GENERADA Informação Digital Auto Gerada ЦИФРОВАЯ ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ SELBSTGENERIERTE DIGITALE INFORMATIONEN
SELF GENERATED DIGITAL OUTPUT INFORMATION SORTIES NUMERIQUES AUTOMATIQUES SELF GENERATED DIGITAL OUTPUT INFORMATION INFORMACION DE SALIDAS DIGITALES AUTO GENERADAS Informação de saidas digitais Auto Geradas ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ ЦИФРОВЫМИ ВЫХОДАМИ SELBSTGENERIERTE DIGITALE AUSGANGS INFORMATIONEN
SELF GENERATED ANALOG INFORMATION ENTREES ANALOGIQUES AUTOMATIQUES SELF GENERATED ANALOG INFORMATION INFORMACION ANALOGICA AUTO GENERADA Informação Analógica Auto Gerada АНАЛОГОВАЯ ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ SELBSTGENERIERTE ANALOG INFORMATIONEN
SHEET : Substation data SHEET : Données de la Soustation SHEET : Substation data SHEET : Datos de subestación SHEET : Dados da Substação SHEET : Данные подстанции SHEET : Substation data
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
SUBSTATION DATA DESCRIPTION DESCRIPTION DES DONNEES DE SOUS-STATION SUBSTATION DATA DESCRIPTION DESCRIPCION DE DATOS DE SUBESTACION Descrição de Dados de Substação ДАННЫЕ ОПИСАНИЯ ПОДСТАНЦИИ SUBSTATION DATA DESCRIPTION
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
Substation Name Nom de la Sous-station Substation Name Nombre de subestación Nome do Substação Имя подстанции Stationsname:
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Control Uniqueness Contrôle Uniquement Control Uniqueness Unequidad de control Unicidade de Controle Однозначность управления Control Uniqueness
Substation Sous-station Substation Subestación Substação Подстанция Substation
No / Substation / Bay / Specific Non / Sous-station / Tranche / Spécifique No / Substation / Bay / Specific No / Subestación / Bahía / Specifico Não/ Substação / Painel / Específico No / Substation / Bay / Specific No / Substation / Bay / Specific
Auto generated Génération automatique Auto generated Auto generado Auto Geração Автоматически сгенерировано Auto generated
Site taking control Emplacement prenant le contrôle Site taking control Toma de control de sitio Controle de Sítio Site taking control Site taking control
SCADA & Local SCADA & Local SCADA & Local SCADA & Local SCADA & Local SCADA & Local SCADA & Local
SCADA / Local / SCADA & Local SCADA / Local / SCADA & Local SCADA / Local / SCADA & Local SCADA / Local / SCADA & Local SCADA / Local / SCADA & Local SCADA / Local / SCADA & Local SCADA / Local / SCADA & Local
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Gateway Passerelle Gateway UTR UTR Шлюз Gateway
Port used (on gateway) Ports utilisés (sur la passerelle) Port used (on gateway) Puerto utilizado (en UTR) Porta utilizada (em UTR) Используемый порт (на шлюз) benutzter Port (Gateway)
SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1
SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2
SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3
SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4
Default Computer that manages Substation Calculateur par défaut gérant la Sous-station Default Computer that manages Substation Equipo que gestiona Subestación Computador que gerencia Subestação компьютер, который управляет Подстанция Computer verwaltet Substation
SUBSTATION DI GROUPS GROUPES DES DI DE LA SOUS-STATION SUBSTATION DI GROUPS GRUPOS DI SUBSTATION GRUPOS DE SUBSTAÇÃO Группы DI подстанции SUBSTATION DI GROUPS
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
Group DI Reference Référence du Groupes des DI Group DI Reference Referencia de grupo DI Referência de grupo DI Группа DI ссылку Gruppe DI Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Description Description Description Descripción Descrição Описание Beschreibung
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Groups Groupes Groups Grupos Grupos Группы Gruppen
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Number Numéro Number Número Número Номер Number
Group Operator Opérateur du Groupe Group Operator Operador de grupo Operador de grupo Группа оператора Gruppe Operator
Function Fonction Function Función Função Функция Function
Type (S=Single) Type (S=Simple) Type (S=Single) Tipo (S=Sencilla) Tipo (S=Simples) Тип (S=Single) Type (S=Single)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 (16 char) Simple : Texte à l'état électrique = 1 (16 car) Single : Text at electrical state = 1 (16 char) Sencilla : Texto en estado eléctrico = 1 (16 caract) Simples: Texto em estado Elétrico = 1 (16 caract) Одиночный : Обозначение электрического состояния = 1 (16 символов) Single : Text at electrical state = 1 (16 char)
Single : Text at electrical state = 0 (16 char) Simple : Texte à l'état électrique = 0 (16 car) Single : Text at electrical state = 0 (16 char) Sencilla : Texto en estado eléctrico = 0 (16 caract) Simples: Texto em estado Elétrico = 0 (16 caract) Одиночный : Обозначение электрического состояния = 0 (16 символов) Single : Text at electrical state = 0 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
Managed by Computer Géré par le Calcultateur Managed by Computer Manejado por la computadora Controlado por Computador управляет компьютер Managed by Computer
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
LED LED LED LED LED индикатор LED
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Is a xPC Feedback Est un retour de position xPC Is a xPC Feedback Es una xPC de retroalimentación É FeedBack de xPC Присутствует xPC обратная связь Is a xPC Feedback
Acts on xPC Acté sur xPC Acts on xPC Actúa en xPC Atua em xPC Действует на с xPC Acts on xPC
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Is used by distributed Automation (GOOSE) Est utilisé par la distribution automatique (GOOSE) Is used by distributed Automation (GOOSE) Se utiliza por automatización distribuida (GOOSE) Se utiliza por Automação distribuida (GOOSE) Используется распределенной автоматикой (GOOSE) Is used by distributed Automation (GOOSE)
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : Electric Functions SHEET : Fonctions Electriques SHEET : Electric Functions SHEET : Funciones eléctricas SHEET : FUNÇÕES ELÉTRICAS SHEET : Функции электрической части SHEET : Electric Functions
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
ELECTRICAL PROFILES PROFILS ELECTRIQUES ELECTRICAL PROFILES PERFILES ELECTRICOS Perfis Elétricos ПРОФИЛИ ЭЛЕКТРИЧЕСКОЙ ЧАСТИ ELECTRICAL PROFILES
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Single Digital Inputs Profiles Profils des entrées numériques simples (SPS) Single Digital Inputs Profiles Perfiles de entradas digitales sencillas Perfis de Entradas Digitais Únicas Профили одинарных DI Single Digital Inputs Profiles
Single System Digital Inputs Profiles Profils des entrées numériques systèmes simples (SPS) Single System Digital Inputs Profiles Pérfiles de sistema de entradas digitales sencillas Perfis de Sistema de Entradas Digitais Únicas Профили одинарных системных DI Single System Digital Inputs Profiles
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
SPS General Parameters Paramètres généraux de la SPS SPS General Parameters Parámetros generales SPS Parâmetros Geração SPS Основные параметры SPS SPS General Parameters
Generation Condition Condition de la Génération Generation Condition Condición de generación Condição de Geração Основное условие Generation Condition
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
Fugitive Alarm (Spurious) Alarme fugitive Fugitive Alarm (Spurious) Alarma fujitiva (Spurious) Alarme de Fuga(Spurious) Fugitive Alarm (Spurious) Fugitive Alarm (Spurious)
State 1 confirmation delay (x100 ms) Etat 1 confirmation du retard (x100 ms) State 1 confirmation delay (x100 ms) Confirmación de retardo Estado 1 (x100 ms) Confirmação de retardo Estado 1 (x100 ms) Состояние 1 задержка подтверждения (х100 мс) State 1 confirmation delay (x100 ms)
State 1 Gravity level Etat 1 niveau de gravité State 1 Gravity level Nivel de gravedad estado 1 Nivel de gravidade estado 1 Состояние 1 уровень сложности State 1 Gravity level
State 0 confirmation delay (x100 ms) Etat 0 confirmation du retard (x100 ms) State 0 confirmation delay (x100 ms) Confirmación de retardo Estado 0 (x100 ms) Confirmação de retardo Estado 0 (x100 ms) Состояние 0 задержка подтверждения (х100 мс) State 0 confirmation delay (x100 ms)
State 0 Gravity level Etat 0 niveau de gravité State 0 Gravity level Nivel de gravedad estado 0 Nivel de gravidade estado 0 Состояние 0 - уровень сложности State 0 Gravity level
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
SPS Printing Parameters Paramètres d'impression de la SPS SPS Printing Parameters Parámetros de impresión SPS Parâmetros de Impressão SPS Параметры печати SPS SPS Printing Parameters
Printed on Sequence Of Events SOE 1 : Imprimer sur l'imprimante Fil de l'eau 1 : Printed on Sequence Of Events SOE 1 : Impreso en SOE 1 : Impresso em SOE 1 : Вывод на SOE 1 : Printed on Sequence Of Events SOE 1 :
Printed on Sequence Of Events SOE 2 : Imprimer sur l'imprimante Fil de l'eau 2 : Printed on Sequence Of Events SOE 2 : Impreso en SOE 2 : Impresso em SOE 1 : Вывод на SOE 2 : Printed on Sequence Of Events SOE 2 :
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
SPS Interlocking Parameters Paramètres d'Interverrouillage de la SPS SPS Interlocking Parameters Parámetros de enclavamientos SPS Parâmetros de Intertravamento SPS Параметры блокировки SPS SPS Interlocking Parameters
Reset Interlock Value Reset des valeurs de l'interverrouillage Reset Interlock Value Reiniciar valor de enclavamiento Reiniciar Valor de Intertravamento Сбросить значение блокировки Reset Interlock Value
Set Interlock Value Niveau haut des valeurs de l'interverrouillage Set Interlock Value Ajustar valor de enclavamiento Ajustar Valor de Intertravamento Установить значение блокировки Set Interlock Value
SPS Processing Parameters Paramètres de traitement de la SPS SPS Processing Parameters Parámetros de procesamiento SPS Parâmetros de Processamento SPS Пораметры обработки SPS SPS Processing Parameters
Toggling state label Libellé de l'état de basculement Toggling state label Etiqueta de estado en curso Etiqueta de estado em Curso Метка статуса Toggling Toggling state label
SelfCheckFault state label Libellé de l'état d'auto vérification du défaut SelfCheckFault state label Etiqueta de estado FallaAutoChequeo Etiqueta de estado FalhaAutoCheque Метка статуса SelfCheckFault SelfCheckFault state label
Unknown state label Libellé de l'état inconnu Unknown state label Etiqueta de estado desconocido Etiqueta de estado Desconhecido Метка статуса Unknown Unknown state label
Suppressed state label Libellé de l'état supprimé Suppressed state label Etiqueta de estado suprimido Etiqueta de estado Suprimido Метка статуса Suppressed Suppressed state label
Forced state label Libellé de l'état forcé Forced state label Etiqueta de estado forzado Etiqueta de estado Forçado Метка статуса Forced Forced state label
Substituted state label Libellé de l'état substitué Substituted state label Etiqueta de estado sustituido Etiqueta de estado Substituído Метка статуса Substituted Substituted state label
Treatment on Set state Traitement sur l'état Set Treatment on Set state Manipulación en estado de Ajuste Manipulação em estado de Ajuste Обработка статуса Set Treatment on Set state
Treatment on Reset state Traitement sur l'état Reset Treatment on Reset state Manipulación en estado de reajuste Manipulação em estado de Reajuste Обработка статуса Reset Treatment on Reset state
Treatment on Open state Traitement sur l'état Ouvert Treatment on Open state Manipulación en estado Abierto Manipulação em estado Aberto Обработка статуса Open Treatment on Open state
Treatment on Close state Traitement sur l'état Fermé Treatment on Close state Manipulación en estado Cerrado Manipulação em estado Fechado Обрабока статуса Close Treatment on Close state
Treatment on Toggling state Traitement sur l'état de basculement Treatment on Toggling state Manipulación en estado en curso Manipulação em estado em Curso Обработка статуса Toggling Treatment on Toggling state
Treatment on SelfCheckFault state Traitement sur l'état d'auto vérification du défaut Treatment on SelfCheckFault state Manipulación en estado FallaAutoChequeo Manipulação em estado FalhaAutoCheque Обработка статуса SelfCheckFault Treatment on SelfCheckFault state
Treatment on Unknown state Traitement sur l'état inconnu Treatment on Unknown state Manipulación en estado Desconocido Manipulação em estado Desconhecido Обрабока статуса Unknown Treatment on Unknown state
Treatment on Suppressed state Traitement sur l'état supprimé Treatment on Suppressed state Manipulación en estado Suprimido Manipulação em estado Suprimido Обработка статуса Suppressed Treatment on Suppressed state
Treatment on Forced state Traitement sur l'état forcé Treatment on Forced state Manipulación en estado Forzado Manipulação em estado Forçado Обработка статуса Forced Treatment on Forced state
Treatment on Substituted state Traitement sur l'état substitué Treatment on Substituted state Manipulación en estado sustituido Manipulação em estado Substituído Обработка статуса Substituted Treatment on Substituted state
Treatment on Forcing state Traitement sur l'état de forçage Treatment on Forcing state Manipulación en estado Forzando Manipulação em estado Forzando Обработка статуса Forcing Treatment on Forcing state
Treatment on Substitution state Traitement sur l'état de substitution Treatment on Substitution state Manipulación en estado por sustitución Manipulação em estado por Substituição Обработка статуса Substitution Treatment on Substitution state
Treatment on Suppression state Traitement sur l'état de suppression Treatment on Suppression state Manipulación en estado por supresión Manipulação em estado por Supressão Обработка статуса Suppression Treatment on Suppression state
Alarm and Gravity on Toggling state Gravité d'alarme sur l'état de basculement Alarm and Gravity on Toggling state Alarma y gravedad en estado en curso Alarme e gravidade em estado em Curso Тревога и важность статуса Toggling Alarm and Gravity on Toggling state
Alarm and Gravity on SelfCheckFault state Gravité d'alarme sur l'état d'auto vérification du défaut Alarm and Gravity on SelfCheckFault state Alarma y gravedad en estado FallaAutoChequeo Alarme e gravidade em estado FalhaAutoCheque Тревога и важность статуса SelfCheckFault Alarm and Gravity on SelfCheckFault state
Alarm and Gravity on Unknown state Gravité d'alarme sur l'état inconnu Alarm and Gravity on Unknown state Alarma y gravedad en estado desconocido Alarme e gravidade em estado Desconhecido Тревога и важность статуса Unknown Alarm and Gravity on Unknown state
Alarm and Gravity on Suppressed state Gravité d'alarme sur l'état supprimé Alarm and Gravity on Suppressed state Alarma y gravedad en estado Suprimido Alarme e gravidade em estado Suprimido Тревога и важность статуса Suppressed Alarm and Gravity on Suppressed state
Alarm and Gravity on Forced state Gravité d'alarme sur l'état forcé Alarm and Gravity on Forced state Alarma y gravedad en estado forzado Alarme e gravidade em estado Forçado Тревога и важность статуса Forced Alarm and Gravity on Forced state
Alarm and Gravity on Substituted state Gravité d'alarme sur l'état substitué Alarm and Gravity on Substituted state Alarma y gravedad en estado Sustituido Alarme e gravidade em estado Substituído Тревога и важность статуса Substituted Alarm and Gravity on Substituted state
Masking due to control Masqué dû à la commande Masking due to control Enmascarar debido al control Mascarar devido ao controle Masking due to control Masking due to control
SBMC dependant Dépendance SBMC SBMC dependant SBMC dependiente SBMC dependente SBMC иждивенца SBMC unterhaltsberechtigte
Toggling filtering Basculement du filtrage Toggling filtering Curso de la filtración Curso de filtrar Toggling filtering Toggling filtering
Initial status Status initial Initial status Estado inicial Estado inicial Начальный статус Initial status
Forced Reset Interlock Value Reset forcé des valeurs de l'interverrouillage Forced Reset Interlock Value Reiniciar forzado valor de enclavamiento Reiniciar Forçado Valor de Intertravamento Сброс значения блокировки Forced Forced Reset Interlock Value
Forced Set Interlock Value Niveau haut forcé des valeurs de l'interverrouillage Forced Set Interlock Value Ajustar forzado valor de enclavamiento Ajustar Forçado Valor de Intertravamento Установка значения блокировки Forced Forced Set Interlock Value
Substituted Reset Interlock Value Reset substitué des valeurs de l'interverrouillage Substituted Reset Interlock Value Reiniciar Sustituido valor de enclavamiento Reiniciar Substituído Valor de Intertravamento Сброс значения блокировки Substituted Substituted Reset Interlock Value
Substituted Set Interlock Value Niveau haut substitué des valeurs de l'interverrouillage Substituted Set Interlock Value Ajustar Sustituido valor de enclavamiento Ajustar Substituído Valor de Intertravamento Установка значения блокировки Substituted Substituted Set Interlock Value
Suppressed interlock value Valeur de l'interverrouillage supprimé Suppressed interlock value Valor de enclavamiento suprimido Valor de Intertravamento Suprimido Значение блокировки Suppressed Suppressed interlock value
Unknown interlock value Valeur de l'interverrouillage inconnu Unknown interlock value Valor de enclavamiento desconocido Valor de Intertravamento Desconhecido Значение блокировки Unknown Unknown interlock value
Toggling interlock value Valeur de l'interverrouillage de basculement Toggling interlock value Valor de enclavamiento curso Valor de Intertravamento Curso Значение блокировки Toggling Toggling interlock value
SelfCheckFault interlock value Valeur de l'interverrouillage sur l'auto vérification du défaut SelfCheckFault interlock value Valor de enclavamiento FallaAutoChequeo Valor de Intertravamento FalhaAutoCheque Значение блокировки SelfCheckFaul SelfCheckFault interlock value
Default State labels Valeurs par défaut des Etats électriques Default State labels Por defecto las etiquetas de estado Estado padrão rótulos По умолчанию состояние этикетки Default State labels
Default Text at electrical state = 1 (16 char) Texte par défaut à l'état électrique = 1 (16 car) Default Text at electrical state = 1 (16 char) Texto predeterminado en estado eléctrico = 1 (16 caract) Texto padrão em estado Elétrico = 1 (16 caract) умолчанию текст электрического состояния = 1 (16 символов) Default Text at electrical state = 1 (16 char)
Default Text at electrical state = 0 (16 char) Texte par défaut à l'état électrique = 0 (16 car) Default Text at electrical state = 0 (16 char) Texto predeterminado en estado eléctrico = 0 (16 caract) Texto padrão em estado Elétrico = 0 (16 caract) умолчанию текст электрического состояния = 0 (16 символов) Default Text at electrical state = 0 (16 char)
Enable FSS (forcing / substituting / suppressing) Activer le FSS (forçage / substitution / suppression) Enable FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) позволить FSS (forcing / substituting / suppressing) Enable FSS (forcing / substituting / suppressing)
Double Digital Inputs Profiles Profils des entrées numériques doubles (DPS) Double Digital Inputs Profiles Perfiles entradas digitales Dobles Perfis Entradas Digitais Duplas Профили двоичных DI Double Digital Inputs Profiles
Double System Digital Inputs Profiles Profils des entrées numériques systèmes doubles (DPS) Double System Digital Inputs Profiles Pérfiles de sistema de entradas digitales dobles Perfis de Sistema de Entradas Digitais Duplas Профили двоичных системных DI Double System Digital Inputs Profiles
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
DPS General Parameters Paramètres généraux de la DPS DPS General Parameters Parámetros generales DPS Parâmetros Geração DPS Основные параметры DPS DPS General Parameters
Generation Condition Condition de la Génération Generation Condition Condición de generación Condição de Geração Основное условие Generation Condition
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
State 10 Gravity level Etat 10 niveau de gravité State 10 Gravity level Nivel de gravedad 10 Nivel de gravidade 10 Состояние 10 Уровень важности State 10 Gravity level
State 10 confirmation delay (x100 ms) Etat 10 confirmation de retard (x100 ms) State 10 confirmation delay (x100 ms) Confirmación de retardo Estado 10 (x100 ms) Confirmação de retardo Estado 10 (x100 ms) Состояние 10 задержка подтверждения (х100 мс) State 10 confirmation delay (x100 ms)
State 01 Gravity level Etat 01 niveau de gravité State 01 Gravity level Nivel de gravedad Estado 01 Nivel de gravidade Estado 01 Состояние 01 Уровень важности State 01 Gravity level
State 01 confirmation delay (x100 ms) Etat 01 confirmation du retard (x100 ms) State 01 confirmation delay (x100 ms) Confirmación de retardo Estado 01 (x100 ms) Confirmação de retardo Estado 01 (x100 ms) Состояние 01 задержка подтверждения (х100 мс) State 01 confirmation delay (x100 ms)
Complementary [00] delay (x100 ms) Complémentarité [00] retard (x100 ms) Complementary [00] delay (x100 ms) Retardo [00] complementario (x100 ms) Retardo [00] complememtario (x100 ms) Дополнительная [00] задержка (х100 мс) Complementary [00] delay (x100 ms)
Complementary [11] delay (x100 ms) Complémentarité [11] retard (x100 ms) Complementary [11] delay (x100 ms) Retardo [11] complementario (x100 ms) Retardo [11] complememtario (x100 ms) Дополнительная [11] задержка (х100 мс) Complementary [11] delay (x100 ms)
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
DPS Printing Parameters Paramètres d'impression de la DPS DPS Printing Parameters Parámetros de impresión DPS Parâmetros de Impressão DPS Параметры печати DPS DPS Printing Parameters
Printed on Sequence Of Events SOE 1 : Imprimer sur l'imprimante Fil de l'eau 1 : Printed on Sequence Of Events SOE 1 : Impreso en SOE 1 : Impresso em SOE 1 : Вывод на SOE 1 : Printed on Sequence Of Events SOE 1 :
Printed on Sequence Of Events SOE 2 : Imprimer sur l'imprimante Fil de l'eau 2 : Printed on Sequence Of Events SOE 2 : Impreso en SOE 2 : Impresso em SOE 1 : Вывод на SOE 2 : Printed on Sequence Of Events SOE 2 :
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
DPS Interlocking Parameters Paramètres d'Interverrouillage de la DPS DPS Interlocking Parameters Parámetros de enclavamiento DPS Parâmetros de Intertravamento DPS Параметры блокировки DPS DPS Interlocking Parameters
Jammed Interlock Value Valeur "bloqué" de l'interverrouillage Jammed Interlock Value Valor enclavamiento bloqueado Valor Intertravamento bloqueado Значение блокировки Jammed Jammed Interlock Value
Open Interlock Value Valeur "ouvert" de l'interverrouillage Open Interlock Value Valor enclavamiento abierto Valor Intertravamento Aberto Значение блокировки Open Open Interlock Value
Closed Interlock Value Valeur "fermé" de l'interverrouillage Closed Interlock Value Valor enclavamiento cerrado Valor Intertravamento Fechado Значение блокировки Closed Closed Interlock Value
DPS Processing Parameters Paramètres de traitement de la DPS DPS Processing Parameters Parámetros de procesadmiento DPS Parâmetros de Processamento DPS Пораметры обработки DPS DPS Processing Parameters
Jammed (=DBI 00) state label Libellé de l'état bloqué (=DBI 00) Jammed (=DBI 00) state label Etiqueta de estado bloqueado (=DBI 00) Etiqueta de estado bloqueado (=DBI 00) Метка статуса Jammed (=DBI 00) Jammed (=DBI 00) state label
Undefined (=DBI 11) state label Libellé de l'état indéfini (=DBI 11) Undefined (=DBI 11) state label Etiqueta de estado indefinido (=DBI 11) Etiqueta de estado Indefinido (=DBI 11) Метка статуса Undefined (=DBI 11) Undefined (=DBI 11) state label
Toggling state label Libellé de l'état de basculement Toggling state label Etiqueta de estado en curso Etiqueta de estado em Curso Метка статуса Toggling Toggling state label
SelfCheckFault state label Libellé de l'état d'auto vérification du défaut SelfCheckFault state label Etiqueta de estado FallaAutoChequeo Etiqueta de estado FalhaAutoCheque Метка статуса SelfCheckFault SelfCheckFault state label
Unknown state label Libellé de l'état inconnu Unknown state label Etiqueta de estado desconocido Etiqueta de estado Desconhecido Метка статуса Unknown Unknown state label
Suppressed state label Libellé de l'état supprimé Suppressed state label Etiqueta de estado suprimido Etiqueta de estado Suprimido Метка статуса Suppressed Suppressed state label
Forced state label Libellé de l'état forcé Forced state label Etiqueta de estado forzado Etiqueta de estado Forçado Метка статуса Forced Forced state label
Substituted state label Libellé de l'état substitué Substituted state label Etiqueta de estado sustituido Etiqueta de estado Substituído Метка статуса Substituted Substituted state label
Motion interlock value Valeur de l'interverrouillage Motion Motion interlock value Valor de enclavamiento Motion Valor de Intertravamento Motion Значение блокировки Motion Motion interlock value
Treatment on Open state Traitement sur l'état Ouvert Treatment on Open state Manipulación en estado Abierto Manipulação em estado Aberto Обработка статуса Open Treatment on Open state
Treatment on Close state Traitement sur l'état Fermé Treatment on Close state Manipulación en estado Cerrado Manipulação em estado Fechado Обрабока статуса Close Treatment on Close state
Treatment on Jammed state Traitement sur l'état bloqué Treatment on Jammed state Manipulación en estado bloqueado Manipulação em estado bloqueado Обработка статуса Jammed Treatment on Jammed state
Treatment on Undefined state Traitement sur l'état indéfini Treatment on Undefined state Manipulación en estado Indefinido Manipulação em estado Indefinido Обработка статуса Undefined Treatment on Undefined state
Treatment on Toggling state Traitement sur l'état de basculement Treatment on Toggling state Manipulación en estado en curso Manipulação em estado em Curso Обработка статуса Toggling Treatment on Toggling state
Treatment on SelfCheckFault state Traitement sur l'état d'auto vérification du défaut Treatment on SelfCheckFault state Manipulación en estado FallaAutoChequeo Manipulação em estado FalhaAutoCheque Обработка статуса SelfCheckFault Treatment on SelfCheckFault state
Treatment on Unknown state Traitement sur l'état inconnu Treatment on Unknown state Manipulación en estado Desconocido Manipulação em estado Desconhecido Обрабока статуса Unknown Treatment on Unknown state
Treatment on Suppressed state Traitement sur l'état supprimé Treatment on Suppressed state Manipulación en estado Suprimido Manipulação em estado Suprimido Обработка статуса Suppressed Treatment on Suppressed state
Treatment on Forced state Traitement sur l'état forcé Treatment on Forced state Manipulación en estado Forzado Manipulação em estado Forçado Обработка статуса Forced Treatment on Forced state
Treatment on Substituted state Traitement sur l'état substitué Treatment on Substituted state Manipulación en estado sustituido Manipulação em estado Substituído Обработка статуса Substituted Treatment on Substituted state
Treatment on Forcing state Traitement sur l'état de forçage Treatment on Forcing state Manipulación en estado Forzando Manipulação em estado Forzando Обработка статуса Forcing Treatment on Forcing state
Treatment on Substitution state Traitement sur l'état de substitution Treatment on Substitution state Manipulación en estado por sustitución Manipulação em estado por Substituição Обработка статуса Substitution Treatment on Substitution state
Treatment on Suppression state Traitement sur l'état de suppression Treatment on Suppression state Manipulación en estado por supresión Manipulação em estado por Supressão Обработка статуса Suppression Treatment on Suppression state
Alarm and Gravity on Jammed state Gravité d'alarme sur l'état bloqué Alarm and Gravity on Jammed state Alarma y gravedad en estado bloqueado Alarme e gravidade em estado bloqueado Тревога и важность статуса Jammed Alarm and Gravity on Jammed state
Alarm and Gravity on Undefined state Gravité d'alarme sur l'état indéfini Alarm and Gravity on Undefined state Alarma y gravedad en estado Indefinido Alarme e gravidade em estado Indefinido Тревога и важность статуса Undefined Alarm and Gravity on Undefined state
Alarm and Gravity on Toggling state Gravité d'alarme sur l'état de basculement Alarm and Gravity on Toggling state Alarma y gravedad en estado en curso Alarme e gravidade em estado em Curso Тревога и важность статуса Toggling Alarm and Gravity on Toggling state
Alarm and Gravity on SelfCheckFault state Gravité d'alarme sur l'état d'auto vérification du défaut Alarm and Gravity on SelfCheckFault state Alarma y gravedad en estado FallaAutoChequeo Alarme e gravidade em estado FalhaAutoCheque Тревога и важность статуса SelfCheckFault Alarm and Gravity on SelfCheckFault state
Alarm and Gravity on Unknown state Gravité d'alarme sur l'état inconnu Alarm and Gravity on Unknown state Alarma y gravedad en estado desconocido Alarme e gravidade em estado Desconhecido Тревога и важность статуса Unknown Alarm and Gravity on Unknown state
Alarm and Gravity on Suppressed state Gravité d'alarme sur l'état supprimé Alarm and Gravity on Suppressed state Alarma y gravedad en estado Suprimido Alarme e gravidade em estado Suprimido Тревога и важность статуса Suppressed Alarm and Gravity on Suppressed state
Alarm and Gravity on Forced state Gravité d'alarme sur l'état forcé Alarm and Gravity on Forced state Alarma y gravedad en estado forzado Alarme e gravidade em estado Forçado Тревога и важность статуса Forced Alarm and Gravity on Forced state
Alarm and Gravity on Substituted state Gravité d'alarme sur l'état substitué Alarm and Gravity on Substituted state Alarma y gravedad en estado Sustituido Alarme e gravidade em estado Substituído Тревога и важность статуса Substituted Alarm and Gravity on Substituted state
Fugitive Alarm (Spurious) Alarme fugitive Fugitive Alarm (Spurious) Alarma fujitiva (Spurious) Alarme de Fuga(Spurious) Fugitive Alarm (Spurious) Fugitive Alarm (Spurious)
Masking due to control Masqué dû à la commande Masking due to control Enmascarar debido al control Mascarar devido ao controle Masking due to control Masking due to control
SBMC dependant Dépendance SBMC SBMC dependant SBMC dependiente SBMC dependente SBMC иждивенца SBMC unterhaltsberechtigte
Toggling filtering Basculement du filtrage Toggling filtering Curso de la filtración Curso de filtrar Toggling filtering Toggling filtering
Initial status Status initial Initial status Estado inicial Estado inicial Начальный статус Initial status
Forced Jammed Interlock Value Bloquage forcé des valeurs de l'interverrouillage Forced Jammed Interlock Value Bloqueado forzado valor de enclavamiento Bloqueado Forçado Valor de Intertravamento Значение блокировки Forced Jammed Forced Jammed Interlock Value
Forced Open Interlock Value Ouverture forcée des valeurs de l'interverrouillage Forced Open Interlock Value Abierto forzado valor de enclavamiento Aberto Forçado Valor de Intertravamento Значение блокировки Forced Open Forced Open Interlock Value
Forced Closed Interlock Value Fermeture forcée des valeurs de l'interverrouillage Forced Closed Interlock Value Cerrado forzado valor de enclavamiento Fechado Forçado Valor de Intertravamento Значение блокировки Forced Closed Forced Closed Interlock Value
Substituted Jammed Interlock Value Bloquage substitué des valeurs de l'interverrouillage Substituted Jammed Interlock Value Bloqueado Sustituido valor de enclavamiento Bloqueado Substituído Valor de Intertravamento Значение блокировки Substituted Jammed Substituted Jammed Interlock Value
Substituted Open Interlock Value Ouverture substituée des valeurs de l'interverrouillage Substituted Open Interlock Value Abierto Sustituido valor de enclavamiento Aberto Substituído Valor de Intertravamento Значение блокировки Substituted Open Substituted Open Interlock Value
Substituted Closed Interlock Value Fermeture substituée des valeurs de l'interverrouillage Substituted Closed Interlock Value Cerrado Sustituido valor de enclavamiento Fechado Substituído Valor de Intertravamento Значение блокировки Substituted Closed Substituted Closed Interlock Value
Suppressed interlock value Valeur de l'interverrouillage supprimé Suppressed interlock value Valor de enclavamiento suprimido Valor de Intertravamento Suprimido Значение блокировки Suppressed Suppressed interlock value
Unknown interlock value Valeur de l'interverrouillage inconnu Unknown interlock value Valor de enclavamiento desconocido Valor de Intertravamento Desconhecido Значение блокировки Unknown Unknown interlock value
Toggling interlock value Valeur de l'interverrouillage de basculement Toggling interlock value Valor de enclavamiento curso Valor de Intertravamento Curso Значение блокировки Toggling Toggling interlock value
SelfCheckFault interlock value Valeur de l'interverrouillage sur l'auto vérification du défaut SelfCheckFault interlock value Valor de enclavamiento FallaAutoChequeo Valor de Intertravamento FalhaAutoCheque Значение блокировки SelfCheckFaul SelfCheckFault interlock value
Undefined interlock value Valeur de l'interverrouillage indéfini Undefined interlock value Valor de enclavamiento indefinido Valor de Intertravamento Indefinido Значение блокировки Undefined Undefined interlock value
Default State labels Valeurs par défaut des Etats électriques Default State labels Por defecto las etiquetas de estado Estado padrão rótulos По умолчанию состояние этикетки Default State labels
Default Text at electrical state = 10 (16 char) Texte par défaut à l'état électrique = 10 (16 car) Default Text at electrical state = 10 (16 char) Texto predeterminado en estado eléctrico = 10 (16 caract) Texto padrão em estado Elétrico = 10 (16 caract) умолчанию текст электрического состояния = 10 (16 символов) Default Text at electrical state = 10 (16 char)
Default Text at electrical state = 01 (16 char) Texte par défaut à l'état électrique = 01 (16 car) Default Text at electrical state = 01 (16 char) Texto predeterminado en estado eléctrico = 01 (16 caract) Texto padrão em estado Elétrico = 01 (16 caract) умолчанию текст электрического состояния = 01 (16 символов) Default Text at electrical state = 01 (16 char)
Enable FSS (forcing / substituting / suppressing) Activer le FSS (forçage / substitution / suppression) Enable FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) позволить FSS (forcing / substituting / suppressing) Enable FSS (forcing / substituting / suppressing)
Multiple Digital Inputs Profiles Profils des entrées numériques multiples (MPS) Multiple Digital Inputs Profiles Perfiles de entradas digitales Múltiples Perfis de Entradas digitais Múltiplas Профили множественных DI Multiple Digital Inputs Profiles
Multiple System Digital Inputs Profiles Profils des entrées numériques systèmes multiples (MPS) Multiple System Digital Inputs Profiles Perfiles de systema de entradas digitales Múltiples Perfis de Systema de Entradas Digitais Múltiplas Профили множественных системных DI Multiple System Digital Inputs Profiles
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
MPS General Parameters Paramètres généraux de la MPS MPS General Parameters Parámetros generales MPS Parâmetros Geração MPS Основные параметры MPS MPS General Parameters
Generation Condition Condition de la Génération Generation Condition Condición de generación Condição de Geração Основное условие Generation Condition
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
MPS Printing Parameters Paramètres d'impression de la MPS MPS Printing Parameters Parámetros de impresión MPS Parâmetros de Impressão MPS Параметры печати MPS MPS Printing Parameters
Printed on Sequence Of Events SOE 1 : Imprimer sur l'imprimante Fil de l'eau 1 : Printed on Sequence Of Events SOE 1 : Impreso en SOE 1 : Impresso em SOE 1 : Вывод на SOE 1 : Printed on Sequence Of Events SOE 1 :
Printed on Sequence Of Events SOE 2 : Imprimer sur l'imprimante Fil de l'eau 2 : Printed on Sequence Of Events SOE 2 : Impreso en SOE 2 : Impresso em SOE 1 : Вывод на SOE 2 : Printed on Sequence Of Events SOE 2 :
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
MPS Interlocking Parameters Paramètres d'Interverrouillage de la MPS MPS Interlocking Parameters Parámetros de enclavamiento MPS Parâmetros de Intertravamento MPS Параметры блокировки MPS MPS Interlocking Parameters
State 0 Interlock Value Valeur de l'interverrouillage à l'état 0 State 0 Interlock Value Valor de enclavamiento estado 0 Valor de Intertravamento estado 0 Состояние 0 значения блокировки State 0 Interlock Value
State 1 Interlock Value Valeur de l'interverrouillage à l'état 1 State 1 Interlock Value Valor de enclavamiento estado 1 Valor de Intertravamento estado 1 Состояние 1 значения блокировки State 1 Interlock Value
State 2 Interlock Value Valeur de l'interverrouillage à l'état 2 State 2 Interlock Value Valor de enclavamiento estado 2 Valor de Intertravamento estado 2 Состояние 2 значения блокировки State 2 Interlock Value
State 3 Interlock Value Valeur de l'interverrouillage à l'état 3 State 3 Interlock Value Valor de enclavamiento estado 3 Valor de Intertravamento estado 3 Состояние 3 значения блокировки State 3 Interlock Value
State 4 Interlock Value Valeur de l'interverrouillage à l'état 4 State 4 Interlock Value Valor de enclavamiento estado 4 Valor de Intertravamento estado 4 Состояние 4 значения блокировки State 4 Interlock Value
State 5 Interlock Value Valeur de l'interverrouillage à l'état 5 State 5 Interlock Value Valor de enclavamiento estado 5 Valor de Intertravamento estado 5 Состояние 5 значения блокировки State 5 Interlock Value
State 6 Interlock Value Valeur de l'interverrouillage à l'état 6 State 6 Interlock Value Valor de enclavamiento estado 6 Valor de Intertravamento estado 6 Состояние 6 значения блокировки State 6 Interlock Value
State 7 Interlock Value Valeur de l'interverrouillage à l'état 7 State 7 Interlock Value Valor de enclavamiento estado 7 Valor de Intertravamento estado 7 Состояние 7 значения блокировки State 7 Interlock Value
State 8 Interlock Value Valeur de l'interverrouillage à l'état 8 State 8 Interlock Value Valor de enclavamiento estado 8 Valor de Intertravamento estado 8 Состояние 8 значения блокировки State 8 Interlock Value
State 9 Interlock Value Valeur de l'interverrouillage à l'état 9 State 9 Interlock Value Valor de enclavamiento estado 9 Valor de Intertravamento estado 9 Состояние 9 значения блокировки State 9 Interlock Value
State 10 Interlock Value Valeur de l'interverrouillage à l'état 10 State 10 Interlock Value Valor de enclavamiento estado 10 Valor de Intertravamento estado 10 Состояние 10 значения блокировки State 10 Interlock Value
State 11 Interlock Value Valeur de l'interverrouillage à l'état 11 State 11 Interlock Value Valor de enclavamiento estado 11 Valor de Intertravamento estado 11 Состояние 11 значения блокировки State 11 Interlock Value
State 12 Interlock Value Valeur de l'interverrouillage à l'état 12 State 12 Interlock Value Valor de enclavamiento estado 12 Valor de Intertravamento estado 12 Состояние 12 значения блокировки State 12 Interlock Value
State 13 Interlock Value Valeur de l'interverrouillage à l'état 13 State 13 Interlock Value Valor de enclavamiento estado 13 Valor de Intertravamento estado 13 Состояние 13 значения блокировки State 13 Interlock Value
State 14 Interlock Value Valeur de l'interverrouillage à l'état 14 State 14 Interlock Value Valor de enclavamiento estado 14 Valor de Intertravamento estado 14 Состояние 14 значения блокировки State 14 Interlock Value
State 15 Interlock Value Valeur de l'interverrouillage à l'état 15 State 15 Interlock Value Valor de enclavamiento estado 15 Valor de Intertravamento estado 15 Состояние 15 значения блокировки State 15 Interlock Value
MPS Processing Parameters Paramètres de traitement de la MPS MPS Processing Parameters Parámetros de procesamiento MPS Parâmetros de Processamento MPS Пораметры обработки MPS MPS Processing Parameters
State 0 label Libellé de l'état 0 State 0 label Etiqueta de estado 0 Etiqueta de estado 0 Состояние 0 метки State 0 label
State 1 label Libellé de l'état 1 State 1 label Etiqueta de estado 1 Etiqueta de estado 1 Состояние 1 метки State 1 label
State 2 label Libellé de l'état 2 State 2 label Etiqueta de estado 2 Etiqueta de estado 2 Состояние 2 метки State 2 label
State 3 label Libellé de l'état 3 State 3 label Etiqueta de estado 3 Etiqueta de estado 3 Состояние 3 метки State 3 label
State 4 label Libellé de l'état 4 State 4 label Etiqueta de estado 4 Etiqueta de estado 4 Состояние 4 метки State 4 label
State 5 label Libellé de l'état 5 State 5 label Etiqueta de estado 5 Etiqueta de estado 5 Состояние 5 метки State 5 label
State 6 label Libellé de l'état 6 State 6 label Etiqueta de estado 6 Etiqueta de estado 6 Состояние 6 метки State 6 label
State 7 label Libellé de l'état 7 State 7 label Etiqueta de estado 7 Etiqueta de estado 7 Состояние 7 метки State 7 label
State 8 label Libellé de l'état 8 State 8 label Etiqueta de estado 8 Etiqueta de estado 8 Состояние 8 метки State 8 label
State 9 label Libellé de l'état 9 State 9 label Etiqueta de estado 9 Etiqueta de estado 9 Состояние 9 метки State 9 label
State 10 label Libellé de l'état 10 State 10 label Etiqueta de estado 10 Etiqueta de estado 10 Состояние 10 метки State 10 label
State 11 label Libellé de l'état 11 State 11 label Etiqueta de estado 11 Etiqueta de estado 11 Состояние 11 метки State 11 label
State 12 label Libellé de l'état 12 State 12 label Etiqueta de estado 12 Etiqueta de estado 12 Состояние 12 метки State 12 label
State 13 label Libellé de l'état 13 State 13 label Etiqueta de estado 13 Etiqueta de estado 13 Состояние 13 метки State 13 label
State 14 label Libellé de l'état 14 State 14 label Etiqueta de estado 14 Etiqueta de estado 14 Состояние 14 метки State 14 label
State 15 label Libellé de l'état 15 State 15 label Etiqueta de estado 15 Etiqueta de estado 15 Состояние 15 метки State 15 label
Undefined state label Libellé de l'état indéfini Undefined state label Etiqueta de estado Indefinido Etiqueta de estado Indefinido Метка статуса Undefined Undefined state label
Toggling state label Libellé de l'état de basculement Toggling state label Etiqueta de estado en curso Etiqueta de estado em Curso Метка статуса Toggling Toggling state label
SelfCheckFault state label Libellé de l'état d'auto vérification du défaut SelfCheckFault state label Etiqueta de estado FallaAutoChequeo Etiqueta de estado FalhaAutoCheque Метка статуса SelfCheckFault SelfCheckFault state label
Unknown state label Libellé de l'état inconnu Unknown state label Etiqueta de estado desconocido Etiqueta de estado Desconhecido Метка статуса Unknown Unknown state label
Suppressed state label Libellé de l'état supprimé Suppressed state label Etiqueta de estado suprimido Etiqueta de estado Suprimido Метка статуса Suppressed Suppressed state label
Forced state label Libellé de l'état forcé Forced state label Etiqueta de estado forzado Etiqueta de estado Forçado Метка статуса Forced Forced state label
Substituted state label Libellé de l'état substitué Substituted state label Etiqueta de estado sustituido Etiqueta de estado Substituído Метка статуса Substituted Substituted state label
Treatment on state 0 Traitement sur l'état 0 Treatment on state 0 Manipulación en estado 0 Manipulação em estado 0 Обработка статуса 0 Treatment on state 0
Treatment on state 1 Traitement sur l'état 1 Treatment on state 1 Manipulación en estado 1 Manipulação em estado 1 Обработка статуса 1 Treatment on state 1
Treatment on state 2 Traitement sur l'état 2 Treatment on state 2 Manipulación en estado 2 Manipulação em estado 2 Обработка статуса 2 Treatment on state 2
Treatment on state 3 Traitement sur l'état 3 Treatment on state 3 Manipulación en estado 3 Manipulação em estado 3 Обработка статуса 3 Treatment on state 3
Treatment on state 4 Traitement sur l'état 4 Treatment on state 4 Manipulación en estado 4 Manipulação em estado 4 Обработка статуса 4 Treatment on state 4
Treatment on state 5 Traitement sur l'état 5 Treatment on state 5 Manipulación en estado 5 Manipulação em estado 5 Обработка статуса 5 Treatment on state 5
Treatment on state 6 Traitement sur l'état 6 Treatment on state 6 Manipulación en estado 6 Manipulação em estado 6 Обработка статуса 6 Treatment on state 6
Treatment on state 7 Traitement sur l'état 7 Treatment on state 7 Manipulación en estado 7 Manipulação em estado 7 Обработка статуса 7 Treatment on state 7
Treatment on state 8 Traitement sur l'état 8 Treatment on state 8 Manipulación en estado 8 Manipulação em estado 8 Обработка статуса 8 Treatment on state 8
Treatment on state 9 Traitement sur l'état 9 Treatment on state 9 Manipulación en estado 9 Manipulação em estado 9 Обработка статуса 9 Treatment on state 9
Treatment on state 10 Traitement sur l'état 10 Treatment on state 10 Manipulación en estado 10 Manipulação em estado 10 Обработка статуса 10 Treatment on state 10
Treatment on state 11 Traitement sur l'état 11 Treatment on state 11 Manipulación en estado 11 Manipulação em estado 11 Обработка статуса 11 Treatment on state 11
Treatment on state 12 Traitement sur l'état 12 Treatment on state 12 Manipulación en estado 12 Manipulação em estado 12 Обработка статуса 12 Treatment on state 12
Treatment on state 13 Traitement sur l'état 13 Treatment on state 13 Manipulación en estado 13 Manipulação em estado 13 Обработка статуса 13 Treatment on state 13
Treatment on state 14 Traitement sur l'état 14 Treatment on state 14 Manipulación en estado 14 Manipulação em estado 14 Обработка статуса 14 Treatment on state 14
Treatment on state 15 Traitement sur l'état 15 Treatment on state 15 Manipulación en estado 15 Manipulação em estado 15 Обработка статуса 15 Treatment on state 15
Treatment on Undefined state Traitement sur l'état indéfini Treatment on Undefined state Manipulación en estado Indefinido Manipulação em estado Indefinido Обработка статуса Undefined Treatment on Undefined state
Treatment on Toggling state Traitement sur l'état de basculement Treatment on Toggling state Manipulación en estado en curso Manipulação em estado em Curso Обработка статуса Toggling Treatment on Toggling state
Treatment on SelfCheckFault state Traitement sur l'état d'auto vérification du défaut Treatment on SelfCheckFault state Manipulación en estado FallaAutoChequeo Manipulação em estado FalhaAutoCheque Обработка статуса SelfCheckFault Treatment on SelfCheckFault state
Treatment on Unknown state Traitement sur l'état inconnu Treatment on Unknown state Manipulación en estado Desconocido Manipulação em estado Desconhecido Обрабока статуса Unknown Treatment on Unknown state
Treatment on Suppressed state Traitement sur l'état supprimé Treatment on Suppressed state Manipulación en estado Suprimido Manipulação em estado Suprimido Обработка статуса Suppressed Treatment on Suppressed state
Treatment on Forced state Traitement sur l'état forcé Treatment on Forced state Manipulación en estado Forzado Manipulação em estado Forçado Обработка статуса Forced Treatment on Forced state
Treatment on Substituted state Traitement sur l'état substitué Treatment on Substituted state Manipulación en estado sustituido Manipulação em estado Substituído Обработка статуса Substituted Treatment on Substituted state
Treatment on Forcing state Traitement sur l'état de forçage Treatment on Forcing state Manipulación en estado Forzando Manipulação em estado Forzando Обработка статуса Forcing Treatment on Forcing state
Treatment on Substitution state Traitement sur l'état de substitution Treatment on Substitution state Manipulación en estado por sustitución Manipulação em estado por Substituição Обработка статуса Substitution Treatment on Substitution state
Treatment on Suppression state Traitement sur l'état de suppression Treatment on Suppression state Manipulación en estado por supresión Manipulação em estado por Supressão Обработка статуса Suppression Treatment on Suppression state
Alarm and Gravity on state 0 Gravité d'alarme sur l'état 0 Alarm and Gravity on state 0 Alarma y gravedad en estado 0 Alarme e gravidade em estado 0 Тревога и важность статуса 0 Alarm and Gravity on state 0
Alarm and Gravity on state 1 Gravité d'alarme sur l'état 1 Alarm and Gravity on state 1 Alarma y gravedad en estado 1 Alarme e gravidade em estado 1 Тревога и важность статуса 1 Alarm and Gravity on state 1
Alarm and Gravity on state 2 Gravité d'alarme sur l'état 2 Alarm and Gravity on state 2 Alarma y gravedad en estado 2 Alarme e gravidade em estado 2 Тревога и важность статуса 2 Alarm and Gravity on state 2
Alarm and Gravity on state 3 Gravité d'alarme sur l'état 3 Alarm and Gravity on state 3 Alarma y gravedad en estado 3 Alarme e gravidade em estado 3 Тревога и важность статуса 3 Alarm and Gravity on state 3
Alarm and Gravity on state 4 Gravité d'alarme sur l'état 4 Alarm and Gravity on state 4 Alarma y gravedad en estado 4 Alarme e gravidade em estado 4 Тревога и важность статуса 4 Alarm and Gravity on state 4
Alarm and Gravity on state 5 Gravité d'alarme sur l'état 5 Alarm and Gravity on state 5 Alarma y gravedad en estado 5 Alarme e gravidade em estado 5 Тревога и важность статуса 5 Alarm and Gravity on state 5
Alarm and Gravity on state 6 Gravité d'alarme sur l'état 6 Alarm and Gravity on state 6 Alarma y gravedad en estado 6 Alarme e gravidade em estado 6 Тревога и важность статуса 6 Alarm and Gravity on state 6
Alarm and Gravity on state 7 Gravité d'alarme sur l'état 7 Alarm and Gravity on state 7 Alarma y gravedad en estado 7 Alarme e gravidade em estado 7 Тревога и важность статуса 7 Alarm and Gravity on state 7
Alarm and Gravity on state 8 Gravité d'alarme sur l'état 8 Alarm and Gravity on state 8 Alarma y gravedad en estado 8 Alarme e gravidade em estado 8 Тревога и важность статуса 8 Alarm and Gravity on state 8
Alarm and Gravity on state 9 Gravité d'alarme sur l'état 9 Alarm and Gravity on state 9 Alarma y gravedad en estado 9 Alarme e gravidade em estado 9 Тревога и важность статуса 9 Alarm and Gravity on state 9
Alarm and Gravity on state 10 Gravité d'alarme sur l'état 10 Alarm and Gravity on state 10 Alarma y gravedad en estado 10 Alarme e gravidade em estado 10 Тревога и важность статуса 10 Alarm and Gravity on state 10
Alarm and Gravity on state 11 Gravité d'alarme sur l'état 11 Alarm and Gravity on state 11 Alarma y gravedad en estado 11 Alarme e gravidade em estado 11 Тревога и важность статуса 11 Alarm and Gravity on state 11
Alarm and Gravity on state 12 Gravité d'alarme sur l'état 12 Alarm and Gravity on state 12 Alarma y gravedad en estado 12 Alarme e gravidade em estado 12 Тревога и важность статуса 12 Alarm and Gravity on state 12
Alarm and Gravity on state 13 Gravité d'alarme sur l'état 13 Alarm and Gravity on state 13 Alarma y gravedad en estado 13 Alarme e gravidade em estado 13 Тревога и важность статуса 13 Alarm and Gravity on state 13
Alarm and Gravity on state 14 Gravité d'alarme sur l'état 14 Alarm and Gravity on state 14 Alarma y gravedad en estado 14 Alarme e gravidade em estado 14 Тревога и важность статуса 14 Alarm and Gravity on state 14
Alarm and Gravity on state 15 Gravité d'alarme sur l'état 15 Alarm and Gravity on state 15 Alarma y gravedad en estado 15 Alarme e gravidade em estado 15 Тревога и важность статуса 15 Alarm and Gravity on state 15
Alarm and Gravity on Undefined state Gravité d'alarme sur l'état indéfini Alarm and Gravity on Undefined state Alarma y gravedad en estado Indefinido Alarme e gravidade em estado Indefinido Тревога и важность статуса Undefined Alarm and Gravity on Undefined state
Alarm and Gravity on Toggling state Gravité d'alarme sur l'état de basculement Alarm and Gravity on Toggling state Alarma y gravedad en estado en curso Alarme e gravidade em estado em Curso Тревога и важность статуса Toggling Alarm and Gravity on Toggling state
Alarm and Gravity on SelfCheckFault state Gravité d'alarme sur l'état d'auto vérification du défaut Alarm and Gravity on SelfCheckFault state Alarma y gravedad en estado FallaAutoChequeo Alarme e gravidade em estado FalhaAutoCheque Тревога и важность статуса SelfCheckFault Alarm and Gravity on SelfCheckFault state
Alarm and Gravity on Unknown state Gravité d'alarme sur l'état inconnu Alarm and Gravity on Unknown state Alarma y gravedad en estado desconocido Alarme e gravidade em estado Desconhecido Тревога и важность статуса Unknown Alarm and Gravity on Unknown state
Alarm and Gravity on Suppressed state Gravité d'alarme sur l'état supprimé Alarm and Gravity on Suppressed state Alarma y gravedad en estado Suprimido Alarme e gravidade em estado Suprimido Тревога и важность статуса Suppressed Alarm and Gravity on Suppressed state
Alarm and Gravity on Forced state Gravité d'alarme sur l'état forcé Alarm and Gravity on Forced state Alarma y gravedad en estado forzado Alarme e gravidade em estado Forçado Тревога и важность статуса Forced Alarm and Gravity on Forced state
Alarm and Gravity on Substituted state Gravité d'alarme sur l'état substitué Alarm and Gravity on Substituted state Alarma y gravedad en estado Sustituido Alarme e gravidade em estado Substituído Тревога и важность статуса Substituted Alarm and Gravity on Substituted state
Masking due to control Masqué dû à la commande Masking due to control Enmascarar debido al control Mascarar devido ao controle Masking due to control Masking due to control
SBMC dependant Dépendance SBMC SBMC dependant SBMC dependiente SBMC dependente SBMC иждивенца SBMC unterhaltsberechtigte
Suppressed interlock value Valeur de l'interverrouillage supprimé Suppressed interlock value Valor de enclavamiento suprimido Valor de Intertravamento Suprimido Значение блокировки Suppressed Suppressed interlock value
Unknown interlock value Valeur de l'interverrouillage inconnu Unknown interlock value Valor de enclavamiento desconocido Valor de Intertravamento Desconhecido Значение блокировки Unknown Unknown interlock value
Toggling interlock value Valeur de l'interverrouillage de basculement Toggling interlock value Valor de enclavamiento curso Valor de Intertravamento Curso Значение блокировки Toggling Toggling interlock value
SelfCheckFault interlock value Valeur de l'interverrouillage sur l'auto vérification du défaut SelfCheckFault interlock value Valor de enclavamiento FallaAutoChequeo Valor de Intertravamento FalhaAutoCheque Значение блокировки SelfCheckFaul SelfCheckFault interlock value
Undefined interlock value Valeur de l'interverrouillage indéfini Undefined interlock value Valor de enclavamiento indefinido Valor de Intertravamento Indefinido Значение блокировки Undefined Undefined interlock value
Enable FSS (forcing / substituting / suppressing) Activer le FSS (forçage / substitution / suppression) Enable FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) позволить FSS (forcing / substituting / suppressing) Enable FSS (forcing / substituting / suppressing)
Single Digital Outputs Profiles Profils sorties numériques simples (SPC) Single Digital Outputs Profiles Perfiles de salidas digitales sencillas Perfis de saidas Digitais Únicas Профили одинарных DO Single Digital Outputs Profiles
Single System Digital Outputs Profiles Profils sorties numériques systèmes simples (SPC) Single System Digital Outputs Profiles Perfiles de systema de salidas digitales sencillas Perfis de Systema de saidas Digitais Únicas Профили одинарных системных DO Single System Digital Outputs Profiles
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
SPC General Parameters Paramètres généraux de la SPC SPC General Parameters Parámetros generales SPC Parâmetros Geração SPC Основные параметры SPC SPC General Parameters
Activation Mode Mode d'activation Activation Mode Modo de activación Modo de Ativação Режим активации Activation Mode
SBO Mode Mode de sélection avant opération SBO Mode Modo SBO Modo SBO Режим SBO SBO Mode
SBO Timeout [0-600s] Temps d'expiration pour la sélection avant opération [0-600s] SBO Timeout [0-600s] Tiempo fuera SBO [0-600s] Falha SBO [0-600s] Задержка SBO [0-600 с] SBO Timeout [0-600s]
Execution timeout (if any) [0..6000000] (x100ms) Temps d'expiration de l'exécution (si présent) [0..6000000] (x100ms) Execution timeout (if any) [0..6000000] (x100ms) Tiempo fuera de ejecución (si existe) [0..6000000] (x100ms) Falha de execução (se existe) [0..6000000] (x100ms) Задержка выполнения (если есть) [0..6000000] (х100 мс) Execution timeout (if any) [0..6000000] (x100ms)
NACK Alarm Parameters Paramètres NACK d'alarme NACK Alarm Parameters Parámetros de alarmas NACK Parâmetros de Alarmes NACK Параметры тревоги NACK NACK Alarm Parameters
Alarmed on Negative Ack state Etat de l'alarme sur réception négative Alarmed on Negative Ack state Alarmado en estado de adquisición negativo Alarme em estado de aquisição negativo Сигнализация на неподтвержденный статус Alarmed on Negative Ack state
Treatment on Negative Ack state Etat du Traitement sur réception Négative Treatment on Negative Ack state Manipulación en estado adquisición negativo Manipulação em estado de aquisição negativo Обработка неподтверденного статуса Treatment on Negative Ack state
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
Usage Parameters Paramètres d'Utilisation Usage Parameters Parámetros del Uso Parâmetros do Uso Параметры Usage Usage Parameters
Off Usage Valeur "Off" d'utilisation Off Usage Valor uso 'Off' Valor Uso 'Off' Значение Usage Off Off Usage
On Usage Valeur "On" d'utilisation On Usage Valor uso 'On' Valor Uso 'On' Значения Usage On On Usage
Interlocking Parameters Paramètres d'Interverrouillage Interlocking Parameters Parámetros de enclavamiento Parâmetros de Intertravamento Параметры блокировки Interlocking Parameters
Off Interlock Value Valeur "Off" de l'interverrouillage Off Interlock Value Valor enclavamiento 'Off' Valor Intertravamento 'Off' Значение блокировки Off Off Interlock Value
On Interlock Value Valeur "On" de l'interverrouillage On Interlock Value Valor enclavamiento 'On' Valor Intertravamento 'On' Значение блокировки On On Interlock Value
Order on duration (ms) Durée de l'ordre (ms) Order on duration (ms) Duración de 'Order on' (ms) Duração de 'Order on' (ms) Продолжительность 'Order on' (mc) Order on duration (ms)
Hold duration (ms) Durée de maintien (ms) Hold duration (ms) Duración de 'Hold' (ms) Duração de 'Hold' (ms) Продолжительность 'Hold' (mc) Hold duration (ms)
SPC Printing Parameters Paramètres d'impression de la SPC SPC Printing Parameters Parámetros de impresión SPC Parâmetros de Impressão SPC Параметры печати SPC SPC Printing Parameters
Printed on Sequence Of Events SOE 1 : Imprimer sur l'imprimante Fil de l'eau 1 : Printed on Sequence Of Events SOE 1 : Impreso en SOE 1 : Impresso em SOE 1 : Вывод на SOE 1 : Printed on Sequence Of Events SOE 1 :
Printed on Sequence Of Events SOE 2 : Imprimer sur l'imprimante Fil de l'eau 2 : Printed on Sequence Of Events SOE 2 : Impreso en SOE 2 : Impresso em SOE 1 : Вывод на SOE 2 : Printed on Sequence Of Events SOE 2 :
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
Default State labels Valeurs par défaut des Etats électriques Default State labels Por defecto las etiquetas de estado Estado padrão rótulos По умолчанию состояние этикетки Default State labels
Default Text at electrical state = 1 (16 char) Texte par défaut à l'état électrique = 1 (16 car) Default Text at electrical state = 1 (16 char) Texto predeterminado en estado eléctrico = 1 (16 caract) Texto padrão em estado Elétrico = 1 (16 caract) умолчанию текст электрического состояния = 1 (16 символов) Default Text at electrical state = 1 (16 char)
Default Text at electrical state = 0 (16 char) Texte par défaut à l'état électrique = 0 (16 car) Default Text at electrical state = 0 (16 char) Texto predeterminado en estado eléctrico = 0 (16 caract) Texto padrão em estado Elétrico = 0 (16 caract) умолчанию текст электрического состояния = 0 (16 символов) Default Text at electrical state = 0 (16 char)
Double Digital Outputs Profiles Profils des sorties numériques doubles (DPC) Double Digital Outputs Profiles Perfiles de salidas digitales dobles Perfis de saidas Digitais Duplas Профили двоичных DO Double Digital Outputs Profiles
Double System Digital Outputs Profiles Profils des sorties numériques systèmes doubles (DPC) Double System Digital Outputs Profiles Perfiles de systema de salidas digitales dobles Perfis de Systema de saidas Digitais Duplas Профили двоичных системных DO Double System Digital Outputs Profiles
Default State labels Valeurs par défaut des Etats électriques Default State labels Por defecto las etiquetas de estado Estado padrão rótulos По умолчанию состояние этикетки Default State labels
Default Text at electrical state = 10 (16 char) Texte par défaut à l'état électrique = 10 (16 car) Default Text at electrical state = 10 (16 char) Texto predeterminado en estado eléctrico = 10 (16 caract) Texto padrão em estado Elétrico = 10 (16 caract) умолчанию текст электрического состояния = 10 (16 символов) Default Text at electrical state = 10 (16 char)
Default Text at electrical state = 01 (16 char) Texte par défaut à l'état électrique = 01 (16 car) Default Text at electrical state = 01 (16 char) Texto predeterminado en estado eléctrico = 01 (16 caract) Texto padrão em estado Elétrico = 01 (16 caract) умолчанию текст электрического состояния = 01 (16 символов) Default Text at electrical state = 01 (16 char)
DPC Printing Parameters Paramètres d'impression de la DPC DPC Printing Parameters Parámetros de impresión DPC Parâmetros de Impressão DPC Параметры печати DPC DPC Printing Parameters
Printed on Sequence Of Events SOE 1 : Imprimer sur l'imprimante Fil de l'eau 1 : Printed on Sequence Of Events SOE 1 : Impreso en SOE 1 : Impresso em SOE 1 : Вывод на SOE 1 : Printed on Sequence Of Events SOE 1 :
Printed on Sequence Of Events SOE 2 : Imprimer sur l'imprimante Fil de l'eau 2 : Printed on Sequence Of Events SOE 2 : Impreso en SOE 2 : Impresso em SOE 1 : Вывод на SOE 2 : Printed on Sequence Of Events SOE 2 :
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
Open duration (ms) Durée d'ouverture (ms) Open duration (ms) Duración de 'Open' (ms) Duração de 'Open' (ms) Продолжительность 'Open' (mc) Open duration (ms)
Close duration (ms) Durée de fermeture (ms) Close duration (ms) Duración de 'Close' (ms) Duração de 'Close' (ms) Продолжительность 'Close' (mc) Close duration (ms)
Hold duration (ms) Durée de maintien (ms) Hold duration (ms) Duración de 'Hold' (ms) Duração de 'Hold' (ms) Продолжительность 'Hold' (mc) Hold duration (ms)
Usage Parameters Paramètres d'Utilisation Usage Parameters Parámetros del Uso Parâmetros do Uso Параметры Usage Usage Parameters
Open Usage 01 Valeur "Ouvert" d'utilisation 01 Open Usage 01 Valor uso 'Open' 01 Valor Uso 'Open' 01 Значение Usage 'Open' 01 Open Usage 01
Close Usage 10 Valeur "Fermé" d'utilisation 10 Close Usage 10 Valor uso 'Close' 10 Valor Uso 'Close' 10 Значения Usage 'Close' 10 Close Usage 10
Interlocking Parameters Paramètres d'Interverrouillage Interlocking Parameters Parámetros de enclavamiento Parâmetros de Intertravamento Параметры блокировки Interlocking Parameters
Open Interlock Value 01 Valeur "Ouvert" de l'interverrouillage 01 Open Interlock Value 01 Valor enclavamiento 'Open' 01 Valor Intertravamento 'Open' 01 Значение блокировки 'Open' 01 Open Interlock Value 01
Close Interlock Value 10 Valeur "Fermé" de l'interverrouillage 10 Close Interlock Value 10 Valor enclavamiento 'Close' 10 Valor Intertravamento 'Close' 10 Значение блокировки 'Close' 10 Close Interlock Value 10
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
DPC General Parameters Paramètres généraux de la DPC DPC General Parameters Parámetros generales DPC Parâmetros Geração DPC Основные параметры DPC DPC General Parameters
Activation Mode Mode d'activation Activation Mode Modo de activación Modo de Ativação Режим активации Activation Mode
SBO Mode Mode de sélection avant opération SBO Mode Modo SBO Modo SBO Режим SBO SBO Mode
SBO Timeout [0-600s] Temps d'expiration pour la sélection avant opération [0-600s] SBO Timeout [0-600s] Tiempo fuera SBO [0-600s] Falha SBO [0-600s] Задержка SBO [0-600 с] SBO Timeout [0-600s]
Execution timeout (if any) [0..6000000] (x100ms) Temps d'expiration de l'exécution (si présent) [0..6000000] (x100ms) Execution timeout (if any) [0..6000000] (x100ms) Tiempo fuera de ejecución (si existe) [0..6000000] (x100ms) Falha de execução (se existe) [0..6000000] (x100ms) Задержка выполнения (если есть) [0..6000000] (х100 мс) Execution timeout (if any) [0..6000000] (x100ms)
NACK Alarm Parameters Paramètres NACK d'alarme NACK Alarm Parameters Parámetros de alarmas NACK Parâmetros de Alarmes NACK Параметры тревоги NACK NACK Alarm Parameters
Alarmed on Negative Ack state Etat de l'alarme sur réception négative Alarmed on Negative Ack state Alarmado en estado de adquisición negativo Alarme em estado de aquisição negativo Сигнализация на неподтвержденный статус Alarmed on Negative Ack state
Treatment on Negative Ack state Etat du Traitement sur réception Négative Treatment on Negative Ack state Manipulación en estado adquisición negativo Manipulação em estado de aquisição negativo Обработка неподтверденного статуса Treatment on Negative Ack state
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
System SetPoint Profiles Profils SetPoint systèmes System SetPoint Profiles Perfiles de systema de SetPoint Perfis de Systema de SetPoint Профили системных SetPoint System SetPoint Profiles
SetPoint Profiles Profils SetPoint SetPoint Profiles Perfiles de SetPoint Perfis de SetPoint Профили SetPoint SetPoint Profiles
SetPoint Printing Parameters Paramètres d'impression de la SetPoint SetPoint Printing Parameters Parámetros de impresión SetPoint Parâmetros de Impressão SetPoint Параметры печати SetPoint SetPoint Printing Parameters
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
SetPoint General Parameters Paramètres généraux du SetPoint SetPoint General Parameters Parámetros generales SetPoint Parâmetros Geração SetPoint Основные параметры SetPoint SetPoint General Parameters
Activation Mode Mode d'activation Activation Mode Modo de activación Modo de Ativação Режим активации Activation Mode
SBO Mode Mode de sélection avant opération SBO Mode Modo SBO Modo SBO Режим SBO SBO Mode
SBO Timeout [0-600s] Temps d'expiration pour la sélection avant opération [0-600s] SBO Timeout [0-600s] Tiempo fuera SBO [0-600s] Falha SBO [0-600s] Задержка SBO [0-600 с] SBO Timeout [0-600s]
Execution timeout (if any) [0..6000000] (x100ms) Temps d'expiration de l'exécution (si présent) [0..6000000] (x100ms) Execution timeout (if any) [0..6000000] (x100ms) Tiempo fuera de ejecución (si existe) [0..6000000] (x100ms) Falha de execução (se existe) [0..6000000] (x100ms) Задержка выполнения (если есть) [0..6000000] (х100 мс) Execution timeout (if any) [0..6000000] (x100ms)
NACK Alarm Parameters Paramètres NACK d'alarme NACK Alarm Parameters Parámetros de alarmas NACK Parâmetros de Alarmes NACK Параметры тревоги NACK NACK Alarm Parameters
Alarmed on Negative Ack state Etat de l'alarme sur réception négative Alarmed on Negative Ack state Alarmado en estado de adquisición negativo Alarme em estado de aquisição negativo Сигнализация на неподтвержденный статус Alarmed on Negative Ack state
Treatment on Negative Ack state Etat du Traitement sur réception Négative Treatment on Negative Ack state Manipulación en estado adquisición negativo Manipulação em estado de aquisição negativo Обработка неподтверденного статуса Treatment on Negative Ack state
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
Measurement Profiles Profils analogiques Measurement Profiles Perfiles de mediciones Perfis de Medições Профили измерений Measurement Profiles
Measurement System Profiles Profils systèmes analogiques Measurement System Profiles Perfiles de systema de mediciones Perfis de Systema de Medições Профили системных измерений Measurement System Profiles
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
MV General Parameters Paramètres généraux de la MV MV General Parameters Parámetros generales MV Parâmetros Geração MV Основные параметры MV MV General Parameters
Number of decimal for display [0-4] Nombre de décimales pour l'affichage [0-4] Number of decimal for display [0-4] Número de decimales para pantalla [0-4] Número de decimaoes para Display [0-4] Количество цифр на дисплее [0-4] Number of decimal for display [0-4]
Short Acquisition period (ms) [100 … 1000] step 100 Période d'acquisition courte (ms) [100 … 1000] pas de 100 Short Acquisition period (ms) [100 … 1000] step 100 Periodo de adquisición corto (ms) [100 … 1000] escalón 100 Periodo de aquisição Curto (ms) [100 … 1000] Escala 100 Короткий период опроса (мс) [100 … 1000] с шагом 100 Short Acquisition period (ms) [100 … 1000] step 100
Long Acquisition period (ms) [500 … 10000] step 500 Période d'acquisition longue (ms) [500 … 10000] pas de 500 Long Acquisition period (ms) [500 … 10000] step 500 Periodo de adquisición largo (ms) [500 … 10000] escalón 500 Periodo de aquisição Longo (ms) [500 … 10000] Escala 500 Длинный период опроса (мс) [500 … 10000] с шагом 500 Long Acquisition period (ms) [500 … 10000] step 500
3rd Low Threshold (no or % of full scale) 3eme seuil bas (non ou % de la pleine échelle) 3rd Low Threshold (no or % of full scale) 3er Umbral bajo (no o % de la escala completa) 3ro Limite Baixo (Nãoo % da escala completa) Третий нижний предел (отсутствует или % от полной шкалы) 3rd Low Threshold (no or % der Skalenendwerts)
2nd Low Threshold (no or % of full scale) 2eme seuil bas (non ou % de la pleine échelle) 2nd Low Threshold (no or % of full scale) 2do Umbral bajo (no o % de la escala completa) 2do Limite Baixo (Nãoo % da escala completa) Второй нижний предел (отсутствует или % от полной шкалы) 2nd Low Threshold (no or % der Skalenendwerts)
1st Low Threshold (no or % of full scale) 1er seuil bas (non ou % de la pleine échelle) 1st Low Threshold (no or % of full scale) 1er Umbral bajo (no o % de la escala completa) 1ro Limite Baixo (Nãoo % da escala completa) Первый нижний предел (отсутствует или % от полной шкалы) 1st Low Threshold (no or % der Skalenendwerts)
1st High Threshold (no or % of full scale) 1er seuil haut (non ou % de la pleine échelle) 1st High Threshold (no or % of full scale) 1er Umbral alto (no o % de la escala completa) 1ro Limite Alto (Nãoo % da escala completa) Первый верхний предел (отсутствует или % от полной шкалы) 1st High Threshold (no or % der Skalenendwerts)
2nd High Threshold (no or % of full scale) 2em seuil haut (non ou % de la pleine échelle) 2nd High Threshold (no or % of full scale) 2do Umbral alto (no o % de la escala completa) 2do Limite Alto (Nãoo % da escala completa) Второй верхний предел (отсутствует или % от полной шкалы) 2nd High Threshold (no or % der Skalenendwerts)
3rd High Threshold (no or % of full scale) 3eme seuil haut(non ou % de la pleine échelle) 3rd High Threshold (no or % of full scale) 3er Umbral alto (no o % de la escala completa) 3ro Limite Alto (Nãoo % da escala completa) Третий верхний предел (отсутствует или % от полной шкалы) 3rd High Threshold (no or % der Skalenendwerts)
Scaling Graduation Scaling Escala Graduação Шкалирование Scaling
Number of Slopes [1-20] Nombres de pentes [1-20] Number of Slopes [1-20] Número de escalones [1-20] Número de Escala [1-20] Количество кривых c разным наклоном [1-20] Number of Slopes [1-20]
Associated Alarm Parameters Paramètres d'alarme associés à la MV Associated Alarm Parameters Associated Alarm Parameters Associated aoarm Parameters Параметры тревоги Associated Alarm Parameters
Generation Condition Condition de la Génération Generation Condition Condición de generación Condição de Geração Основное условие Generation Condition
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
MV Processing Parameters Paramètres de traitement de la MV MV Processing Parameters Parámetros de procesamiento MV Parâmetros de Processamento MV Пораметры обработки MV MV Processing Parameters
Valid state label Libellé de l'état valide Valid state label Etiqueta de estado válido Etiqueta de estado válido Метка статуса Valid Valid state label
SelfCheckFault state label Libellé de l'état d'auto vérification du défaut SelfCheckFault state label Etiqueta de estado FallaAutoChequeo Etiqueta de estado FalhaAutoCheque Метка статуса SelfCheckFault SelfCheckFault state label
Unknown state label Libellé de l'état inconnu Unknown state label Etiqueta de estado desconocido Etiqueta de estado Desconhecido Метка статуса Unknown Unknown state label
Suppressed state label Libellé de l'état supprimé Suppressed state label Etiqueta de estado suprimido Etiqueta de estado Suprimido Метка статуса Suppressed Suppressed state label
Forced state label Libellé de l'état forcé Forced state label Etiqueta de estado forzado Etiqueta de estado Forçado Метка статуса Forced Forced state label
Substituted state label Libellé de l'état substitué Substituted state label Etiqueta de estado sustituido Etiqueta de estado Substituído Метка статуса Substituted Substituted state label
OverRange state label Libellé de l'état au-dessus de l'échelle OverRange state label Etiqueta de estado fuera de rango Etiqueta de estado fora de Range Метка статуса OverRange OverRange state label
Undefined state label Libellé de l'état indéfini Undefined state label Etiqueta de estado Indefinido Etiqueta de estado Indefinido Метка статуса Undefined Undefined state label
OpenCircuit state label Libellé de l'état circuit ouvert OpenCircuit state label Etiqueta de estado circuito abierto Etiqueta de estado circuito Aberto Метка статуса OpenCircuit OpenCircuit state label
LLL Threshold state label Libellé de l'état seuil LLL LLL Threshold state label Etiqueta de estado umbral LLL Etiqueta de estado Limite LLL Метка статуса LLL Threshold LLL Threshold state label
LL Threshold state label Libellé de l'état seuil LL LL Threshold state label Etiqueta de estado umbral LL Etiqueta de estado Limite LL Метка статуса LL Threshold LL Threshold state label
L Threshold state label Libellé de l'état seuil L L Threshold state label Etiqueta de estado umbral L Etiqueta de estado Limite L Метка статуса L Threshold L Threshold state label
H Threshold state label Libellé de l'état seuil H H Threshold state label Etiqueta de estado umbral H Etiqueta de estado Limite H Метка статуса H Threshold H Threshold state label
HH Threshold state label Libellé de l'état seuil HH HH Threshold state label Etiqueta de estado umbral HH Etiqueta de estado Limite HH Метка статуса HH Threshold HH Threshold state label
HHH Threshold state label Libellé de l'état seuil HHH HHH Threshold state label Etiqueta de estado umbral HHH Etiqueta de estado Limite HHH Метка статуса HHH Threshold HHH Threshold state label
Treatment on Valid state Traitement sur l'état valide Treatment on Valid state Manipulación en estado válido Manipulação em estado válido Обработка статуса Valid Treatment on Valid state
Treatment on SelfCheckFault state Traitement sur l'état d'auto vérification du défaut Treatment on SelfCheckFault state Manipulación en estado FallaAutoChequeo Manipulação em estado FalhaAutoCheque Обработка статуса SelfCheckFault Treatment on SelfCheckFault state
Treatment on Unknown state Traitement sur l'état inconnu Treatment on Unknown state Manipulación en estado Desconocido Manipulação em estado Desconhecido Обрабока статуса Unknown Treatment on Unknown state
Treatment on Suppressed state Traitement sur l'état supprimé Treatment on Suppressed state Manipulación en estado Suprimido Manipulação em estado Suprimido Обработка статуса Suppressed Treatment on Suppressed state
Treatment on Forced state Traitement sur l'état forcé Treatment on Forced state Manipulación en estado Forzado Manipulação em estado Forçado Обработка статуса Forced Treatment on Forced state
Treatment on Substituted state Traitement sur l'état substitué Treatment on Substituted state Manipulación en estado sustituido Manipulação em estado Substituído Обработка статуса Substituted Treatment on Substituted state
Treatment on OverRange state Traitement sur l'état au-dessus de l'échelle Treatment on OverRange state Manipulación en estado fuera de rango Manipulação em estado fora de Range Обработка статуса OverRange Treatment on OverRange state
Treatment on Undefined state Traitement sur l'état indéfini Treatment on Undefined state Manipulación en estado Indefinido Manipulação em estado Indefinido Обработка статуса Undefined Treatment on Undefined state
Treatment on OpenCircuit state Traitement sur l'état circuit ouvert Treatment on OpenCircuit state Manipulación de estado en Circuito Abierto Manipulação de estado em Circuito Aberto Обработка статуса OpenCircuit Treatment on OpenCircuit state
Treatment on LLL Threshold state Traitement sur l'état LLL seuil Treatment on LLL Threshold state Manipualción de estado en umbral LLL Manipuaoción de estado em Limite LLL Обработка статуса LLL Threshold Treatment on LLL Threshold state
Treatment on LL Threshold state Traitement sur l'état LL seuil Treatment on LL Threshold state Manipulación de estado en umbral LL Manipulação de estado em Limite LL Обработка статуса LL Threshold Treatment on LL Threshold state
Treatment on L Threshold state Traitement sur l'état L seuil Treatment on L Threshold state Manipulación de estado en umbral L Manipulação de estado em Limite L Обработка статуса L Threshold Treatment on L Threshold state
Treatment on H Threshold state Traitement sur l'état H seuil Treatment on H Threshold state Manipulación de estado en umbral H Manipulação de estado em Limite H Обработка статуса Н Threshold Treatment on H Threshold state
Treatment on HH Threshold state Traitement sur l'état HH seuil Treatment on HH Threshold state Manipulación de estado en umbral HH Manipulação de estado em Limite HH Обработка статуса HH Threshold Treatment on HH Threshold state
Treatment on HHH Threshold state Traitement sur l'état HHH seuil Treatment on HHH Threshold state Manipulación de estado en umbral HHH Manipulação de estado em Limite HHH Обработка статуса HHH Threshold Treatment on HHH Threshold state
Valid interlock value Valeur de l'interverrouillage valide Valid interlock value Valor de enclavamiento válido Valor de Intertravamento válido Значение блокировки Valid Valid interlock value
SelfCheckFault interlock value Valeur de l'interverrouillage sur l'auto vérification du défaut SelfCheckFault interlock value Valor de enclavamiento FallaAutoChequeo Valor de Intertravamento FalhaAutoCheque Значение блокировки SelfCheckFaul SelfCheckFault interlock value
Unknown interlock value Valeur de l'interverrouillage inconnu Unknown interlock value Valor de enclavamiento desconocido Valor de Intertravamento Desconhecido Значение блокировки Unknown Unknown interlock value
Suppressed interlock value Valeur de l'interverrouillage supprimé Suppressed interlock value Valor de enclavamiento suprimido Valor de Intertravamento Suprimido Значение блокировки Suppressed Suppressed interlock value
Forced interlock value Valeur de l'interverrouillage forcé Forced interlock value Valor de enclavamiento forzado Valor de Intertravamento Forçado Значение блокировки Forced Forced interlock value
Substituted interlock value Valeur de l'interverrouillage substitué Substituted interlock value Valor de enclavamiento sustituido Valor de Intertravamento Substituído Значение блокировки Substituted Substituted interlock value
OverRange interlock value Valeur de l'interverrouillage au-dessus de l'échelle OverRange interlock value Valor de enclavamiento fuera de rango Valor de Intertravamento fora de Range Значение блокировки OverRange OverRange interlock value
Undefined interlock value Valeur de l'interverrouillage indéfini Undefined interlock value Valor de enclavamiento indefinido Valor de Intertravamento Indefinido Значение блокировки Undefined Undefined interlock value
OpenCircuit interlock value Valeur de l'interverrouillage circuit ouvert OpenCircuit interlock value Valor de enclavamiento Circuito Abierto Valor de Intertravamento Circuito Aberto Значение блокировки OpenCircuit OpenCircuit interlock value
LLL Threshold interlock value Valeur de l'interverrouillage seuil LLL LLL Threshold interlock value Valor de enclavamiento umbral LLL Valor de Intertravamento Limite LLL Значение блокировки LLL Threshold LLL Threshold interlock value
LL Threshold interlock value Valeur de l'interverrouillage seuil LL LL Threshold interlock value Valor de enclavamiento umbral LL Valor de Intertravamento Limite LL Значение блокировки LL Threshold LL Threshold interlock value
L Threshold interlock value Valeur de l'interverrouillage seuil L L Threshold interlock value Valor de enclavamiento umbral L Valor de Intertravamento Limite L Значение блокировки L Threshold L Threshold interlock value
H Threshold interlock value Valeur de l'interverrouillage seuil H H Threshold interlock value Valor de enclavamiento umbral H Valor de Intertravamento Limite H Значение блокировки H Threshold H Threshold interlock value
HH Threshold interlock value Valeur de l'interverrouillage seuil HH HH Threshold interlock value Valor de enclavamiento umbral HH Valor de Intertravamento Limite HH Значение блокировки HH Threshold HH Threshold interlock value
HHH Threshold interlock value Valeur de l'interverrouillage seuil HHH HHH Threshold interlock value Valor de enclavamiento umbral HHH Valor de Intertravamento Limite HHH Значение блокировки HHH Threshold HHH Threshold interlock value
Alarm and Gravity on Valid state Gravité d'alarme sur l'état valide Alarm and Gravity on Valid state Alarma y gravedad en estado valido Alarme e gravidade em estado vaoido Тревога и важность статуса Valid Alarm and Gravity on Valid state
Alarm and Gravity on SelfCheckFault state Gravité d'alarme sur l'état d'auto vérification du défaut Alarm and Gravity on SelfCheckFault state Alarma y gravedad en estado FallaAutoChequeo Alarme e gravidade em estado FalhaAutoCheque Тревога и важность статуса SelfCheckFault Alarm and Gravity on SelfCheckFault state
Alarm and Gravity on Unknown state Gravité d'alarme sur l'état inconnu Alarm and Gravity on Unknown state Alarma y gravedad en estado desconocido Alarme e gravidade em estado Desconhecido Тревога и важность статуса Unknown Alarm and Gravity on Unknown state
Alarm and Gravity on Suppressed state Gravité d'alarme sur l'état supprimé Alarm and Gravity on Suppressed state Alarma y gravedad en estado Suprimido Alarme e gravidade em estado Suprimido Тревога и важность статуса Suppressed Alarm and Gravity on Suppressed state
Alarm and Gravity on Forced state Gravité d'alarme sur l'état forcé Alarm and Gravity on Forced state Alarma y gravedad en estado forzado Alarme e gravidade em estado Forçado Тревога и важность статуса Forced Alarm and Gravity on Forced state
Alarm and Gravity on Substituted state Gravité d'alarme sur l'état substitué Alarm and Gravity on Substituted state Alarma y gravedad en estado Sustituido Alarme e gravidade em estado Substituído Тревога и важность статуса Substituted Alarm and Gravity on Substituted state
Alarm and Gravity on OverRange state Gravité d'alarme sur l'état au-dessus de l'échelle Alarm and Gravity on OverRange state Alarma y gravedad en estado fuera de rango Alarme e gravidade em estado fora de Range Тревога и важность статуса OverRange Alarm and Gravity on OverRange state
Alarm and Gravity on Undefined state Gravité d'alarme sur l'état indéfini Alarm and Gravity on Undefined state Alarma y gravedad en estado Indefinido Alarme e gravidade em estado Indefinido Тревога и важность статуса Undefined Alarm and Gravity on Undefined state
Alarm and Gravity on OpenCircuit state Gravité d'alarme sur l'état circuit ouvert Alarm and Gravity on OpenCircuit state Alarma y gravedad en estado circuito abierto Alarme e gravidade em estado Circuito Aberto Тревога и важность статуса OpenCircuit Alarm and Gravity on OpenCircuit state
Alarm and Gravity on LLL Threshold state Gravité d'alarme sur l'état de seuil LLL Alarm and Gravity on LLL Threshold state Alarma y gravedad en estado umbral LLL Alarme e gravidade em estado Limite LLL Тревога и важность статуса LLL Threshold Alarm and Gravity on LLL Threshold state
Alarm and Gravity on LL Threshold state Gravité d'alarme sur l'état de seuil LL Alarm and Gravity on LL Threshold state Alarma y gravedad en estado umbral LL Alarme e gravidade em estado Limite LL Тревога и важность статуса LL Threshold Alarm and Gravity on LL Threshold state
Alarm and Gravity on L Threshold state Gravité d'alarme sur l'état de seuil L Alarm and Gravity on L Threshold state Alarma y gravedad en estado umbral L Alarme e gravidade em estado Limite L Тревога и важность статуса L Threshold Alarm and Gravity on L Threshold state
Alarm and Gravity on H Threshold state Gravité d'alarme sur l'état de seuil H Alarm and Gravity on H Threshold state Alarma y gravedad en estado umbral H Alarme e gravidade em estado Limite H Тревога и важность статуса H Threshold Alarm and Gravity on H Threshold state
Alarm and Gravity on HH Threshold state Gravité d'alarme sur l'état de seuil HH Alarm and Gravity on HH Threshold state Alarma y gravedad en estado umbral HH Alarme e gravidade em estado Limite HH Тревога и важность статуса HH Threshold Alarm and Gravity on HH Threshold state
Alarm and Gravity on HHH Threshold state Gravité d'alarme sur l'état de seuil HHH Alarm and Gravity on HHH Threshold state Alarma y gravedad en estado umbral HHH Alarme e gravidade em estado Limite HHH Тревога и важность статуса HHH Threshold Alarm and Gravity on HHH Threshold state
Computation Calculé Computation Cómputación Computação Вычисление Computation
SBMC dependant Dépendance SBMC SBMC dependant SBMC dependiente SBMC dependente SBMC иждивенца SBMC unterhaltsberechtigte
Graphical Default Format Format graphique par défaut Graphical Default Format Formato gráfico del defecto Formato gráfico do defeito Стандартный графический формат Graphical Default Format
Transmission on Event Transmission sur événement Transmission on Event Transmisión en acontecimiento Transmissão no evento Передача события Transmission on Event
Deadband Bande morte Deadband Venda muerta Faixa muerta Порог чувствительности Deadband
MV Printing Parameters Paramètres d'impression de la MV MV Printing Parameters Parámetros de impresión MV Parâmetros de Impressão MV Параметры печати MV MV Printing Parameters
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
Enable FSS (forcing / substituting / suppressing) Activer le FSS (forçage / substitution / suppression) Enable FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) Permitir FSS (forcing / substituting / suppressing) позволить FSS (forcing / substituting / suppressing) Enable FSS (forcing / substituting / suppressing)
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : System Information SHEET : Informations Systemes SHEET : System Information SHEET : System Information SHEET : System Information SHEET : Системная информация SHEET : System Information
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
SYSTEM INFORMATION DATA DESCRIPTION INFORMATION SYSTEME DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION ОПИСАНИЕ СИСТЕМНОЙ ИНФОРМАЦИИ SYSTEM INFORMATION DATA DESCRIPTION
Gateway Passerelle Gateway UTR UTR Шлюз Gateway
Port used (on gateway) Ports utilisés (sur la passerelle) Port used (on gateway) Puerto utilizado (en UTR) Porta utilizada (em UTR) Используемый порт (на шлюз) benutzter Port (Gateway)
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1
GE Reserved Réservé à GE GE Grid Reservado GE Reservado GE Зарезервировано GE GE Reserved
SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2
Auto generated Génération automatique Auto generated Auto generado Auto Geração Автоматически сгенерировано Auto generated
SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4
SYSTEM INFORMATION DATA DESCRIPTION INFORMATION SYSTEME DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION ОПИСАНИЕ СИСТЕМНОЙ ИНФОРМАЦИИ SYSTEM INFORMATION DATA DESCRIPTION
BAY OI Name : Nom de la BAIE OI : BAY OI Name : BAY OI Name : BAY OI Name : Имя BAY OI : BAY OI Name :
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels / States Libellés/Etats Labels / States Etiquetas/Estados Etiquetas/Estados Метки / Состояния Labels / States
Description Description Description Descripción Descrição Описание Beschreibung
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Groups Groupes Groups Grupos Grupos Группы Gruppen
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC 61850 Name : Nom de l'IEC 61850 : IEC 61850 Name : IEC 61850 Name : IEC 61850 Name : Имя IEC 61850 : IEC 61850 Name :
UCA2 IED Name : Nom de l'UCA2 IED : UCA2 IED Name : UCA2 IED Name : UCA2 IED Name : Имя UCA2 IED : UCA2 IED Name :
SERVER OI Name : Nom du SERVEUR d'E/S : SERVER OI Name : SERVER OI Name : SERVER OI Name : Имя сервера OI : SERVER OI Name :
CLIENT OI Name : Nom du CLIENT d'E/S : CLIENT OI Name : CLIENT OI Name : CLIENT OI Name : Имя клиента OI : CLIENT OI Name :
MiCOM C264 Name : Nom du MiCOM C264 : MiCOM C264 Name : MiCOM C264 Name : MiCOM C264 Name : Имя MiCOM C264 : MiCOM C264 Name :
GATEWAY Name : Nom de la PASSERELLE : GATEWAY Name : GATEWAY Name : GATEWAY Name : Имя шлюза : GATEWAY Name :
MiCOM C364 Name : Nom du MiCOM C364 : MiCOM C364 Name : MiCOM C364 Name : MiCOM C364 Name : Имя MiCOM C364 : MiCOM C364 Name :
SYSTEM INFORMATION GATEWAY INFORMATION SYSTEME PASSERELLE SYSTEM INFORMATION GATEWAY SYSTEM INFORMATION GATEWAY SYSTEM INFORMATION GATEWAY СИСТЕМНАЯ ИНФОРМАЦИЯ ПО ШЛЮЗУ SYSTEM INFORMATION GATEWAY
SYSTEM INFORMATION MiCOM C264 INFORMATION SYSTEME MiCOM C264 SYSTEM INFORMATION MiCOM C264 SYSTEM INFORMATION MiCOM C264 SYSTEM INFORMATION MiCOM C264 СИСТЕМНАЯ ИНФОРМАЦИЯ ПО MiCOM C264 SYSTEM INFORMATION MiCOM C264
SYSTEM INFORMATION MiCOM C364 INFORMATION SYSTEME MiCOM C364 SYSTEM INFORMATION MiCOM C364 SYSTEM INFORMATION MiCOM C364 SYSTEM INFORMATION MiCOM C364 СИСТЕМНАЯ ИНФОРМАЦИЯ ПО MiCOM C364 SYSTEM INFORMATION MiCOM C364
SYSTEM INFORMATION CLIENT OI INFORMATION SYSTEME CLIENT E/S SYSTEM INFORMATION CLIENT OI SYSTEM INFORMATION CLIENT OI SYSTEM INFORMATION CLIENT OI СИСТЕМНАЯ ИНФОРМАЦИЯ ПО КЛИЕНТУ OI SYSTEM INFORMATION CLIENT OI
SYSTEM INFORMATION SERVER OI INFORMATION SYSTEME SERVER E/S SYSTEM INFORMATION SERVER OI SYSTEM INFORMATION SERVER OI SYSTEM INFORMATION SERVER OI СИСТЕМНАЯ ИНФОРМАЦИЯ ПО СЕРВЕРУ OI SYSTEM INFORMATION SERVER OI
SYSTEM INFORMATION UCA2 IED INFORMATION SYSTEME UCA2 IED SYSTEM INFORMATION UCA2 IED SYSTEM INFORMATION UCA2 IED SYSTEM INFORMATION UCA2 IED СИСТЕМНАЯ ИНФОРМАЦИЯ ПО UCA2 IED SYSTEM INFORMATION UCA2 IED
SYSTEM INFORMATION IEC 61850 INFORMATION SYSTEME IEC 61850 SYSTEM INFORMATION IEC 61850 SYSTEM INFORMATION IEC 61850 SYSTEM INFORMATION IEC 61850 СИСТЕМНАЯ ИНФОРМАЦИЯ ПО IEC 61850 SYSTEM INFORMATION IEC 61850
SYSTEM INFORMATION BAY OI INFORMATION SYSTEME BAIE OI SYSTEM INFORMATION BAY OI SYSTEM INFORMATION BAY OI SYSTEM INFORMATION BAY OI СИСТЕМНАЯ ИНФОРМАЦИЯ ПО BAY OI SYSTEM INFORMATION BAY OI
Issue Révision Issue Revisión Revisão Версия Version
Equipment Link Lien Equipement Equipment Link Acoplamiento del equipo Ligação do equipamento Оборудование связи Equipment Link
Function Fonction Function Función Função Функция Function
Type Type Type Type Type Type Type
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 Multiple : pas utilisé MV : pas utilisé (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 Множественный: не используется MV : Не используется (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 Multiple : Not used MV : Not used (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique =01 Multiple : pas utilisé MV : pas utilisé (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 Множественный: не используется MV : Не используется (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 Multiple : Not used MV : Not used (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
Computers Groups (separator ";") Groupes de calculateur (séparateur ";") Computers Groups (separator ";") Grupos de Computadoras (separador ";") Grupos de Computadores (separador ";") Группы контроллеров (разделитель ";") Computers Gruppen (separator ";")
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
LED MV : Not used LED MV : Non utilisé LED MV : Not used LED MV : Not used LED MV : Not used Индикатор MV : Не используется LED MV : Not used
xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : Affichage LCD xPC : Contrôle LCD MV : Affichage LCD xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : LCD Display xPC : LCD Control MV : LCD Display xPS : LCD Дисплей xPC : Управление LCD MV : LCD Дисплей xPS : LCD Display xPC : LCD Control MV : LCD Display
xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : Affichage HMI xPC : Contrôle HMI MV : Affichage HMI xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : HMI Display xPC : HMI Control MV : HMI Display xPS : HMI Дисплей xPC : Управление HMI MV : HMI Дисплей xPS : HMI Display xPC : HMI Control MV : HMI Display
xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer xPS : Est un retour de position xPC xPC : Est activé par xPS MV : Archivé xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer xPS : активируется с помощью xPC xPC : активируется с помощью xPS MV : Просмотр кривых xPS : Acts on xPC xPC : Is activated by xPS MV : Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used xPS, MV : Est utilisé par la distribution automatique (GOOSE) xPC : Non utilisé xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used xPS, MV : Используется распределенной автоматикой (GOOSE) xPC : Не используется xPS, MV : Is used by distributed Automation (GOOSE) xPC : Not used
Datapoint Name (in SCE Template) Nom du Point de Donnée (dans le modèle du SCE) Datapoint Name (in SCE Template) Nombre del dato (en plantilla SCE) Nome do Dado (em Panilha SCE) Имя точки данных (в SCE шаблоне) Datapoint Name (in SCE Template)
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Agency status Etat agence Agency status Agency status Agency status Agency status Agency status
Auto archiving Archivage auto Auto archiving Auto archiving Auto archiving Auto archiving Auto archiving
AIU status AIU statut AIU status AIU status AIU status AIU status AIU status
AIU status AIU statut AIU status AIU status AIU status AIU status AIU status
Backup printer status Etat imprimante backup Backup printer status Backup printer status Backup printer status Backup printer status Backup printer status
BIU status BIU statut BIU status BIU status BIU status BIU status BIU status
CCU status CCU statut CCU status CCU status CCU status CCU status CCU status
Central archive Archive centrale Central archive Central archive Central archive Central archive Central archive
Device link Lien équipement Device link Device link Device link Device link Device link
SPS Communication with the IED SPS de communication avec l'IED SPS Communication with the IED SPS Communication with the IED SPS Communication with the IED SPS Communication with the IED SPS Communication with the IED
OI client link Lien client OI OI client link OI client link OI client link OI client link OI client link
Communication SPS with the SCADA SPS de communication avec le SCADA Communication SPS with the SCADA Communication SPS with the SCADA Communication SPS with the SCADA Communication SPS with the SCADA Communication SPS with the SCADA
Counter Top Top compteur Counter Top Counter Top Counter Top Counter Top Counter Top
UCA2 Coupling Couplage UCA2 UCA2 Coupling UCA2 Coupling UCA2 Coupling UCA2 Coupling UCA2 Coupling
DB incohency SPS SPS DB incohérente DB incohency SPS DB incohency SPS DB incohency SPS DB incohency SPS DB incohency SPS
DB switch control contrôle basculement BD DB switch control DB switch control DB switch control DB switch control DB switch control
DI acquisition stopped Acquisition DI arrêtée DI acquisition stopped DI acquisition stopped DI acquisition stopped DI acquisition stopped DI acquisition stopped
SPS disturbance file ready SPS fichier de perturbo prête SPS disturbance file ready SPS disturbance file ready SPS disturbance file ready SPS disturbance file ready SPS disturbance file ready
SPS disturbance file ready SPS fichier de perturbo prête SPS disturbance file ready SPS disturbance file ready SPS disturbance file ready SPS disturbance file ready SPS disturbance file ready
DIU status DIU statut DIU status DIU status DIU status DIU status DIU status
DOU status DOU statut DOU status DOU status DOU status DOU status DOU status
External clock status Etat horloge external External clock status External clock status External clock status External clock status External clock status
GHU status GHU statut GHU status GHU status GHU status GHU status GHU status
ISAGRAF status Etat ISAGRAF ISAGRAF status ISAGRAF status ISAGRAF status ISAGRAF status ISAGRAF status
Local/remote DPS DPS local/distant Local/remote DPS Local/remote DPS Local/remote DPS Local/remote DPS Local/remote DPS
Local/remote controlDPC DPC de contrôle Local/distant Local/remote controlDPC Local/remote controlDPC Local/remote controlDPC Local/remote controlDPC Local/remote controlDPC
Local/remote SPS SPS loc/distant Local/remote SPS Local/remote SPS Local/remote SPS Local/remote SPS Local/remote SPS
Log Queue File du log Log Queue Log Queue Log Queue Log Queue Log Queue
Main computer status MV MV état calculateur principal Main computer status MV Main computer status MV Main computer status MV Main computer status MV Main computer status MV
Device mode Mode équip. Device mode Device mode Device mode Device mode Device mode
Mode control DPC DPC de contrôle du mode Mode control DPC Mode control DPC Mode control DPC Mode control DPC Mode control DPC
Operating mode Mode exploitation Operating mode Operating mode Operating mode Operating mode Operating mode
Printer status DPS état imprimante Printer status Printer status Printer status Printer status Printer status
Redundancy change mode control contrôle changement mode redondance Redundancy change mode control Redundancy change mode control Redundancy change mode control Redundancy change mode control Redundancy change mode control
Redundancy change status Statut changt redondance Redundancy change status Redundancy change status Redundancy change status Redundancy change status Redundancy change status
Redundancy change status control Contrôle changement statut redond. Redundancy change status control Redundancy change status control Redundancy change status control Redundancy change status control Redundancy change status control
Redundancy mode Mode redondance Redundancy mode Redundancy mode Redundancy mode Redundancy mode Redundancy mode
Redundancy SPS SPS de Redondance Redundancy SPS Redundancy SPS Redundancy SPS Redundancy SPS Redundancy SPS
OI client Client OI OI client OI client OI client OI client OI client
Software error SPS SPS erreur logicielle Software error SPS Software error SPS Software error SPS Software error SPS Software error SPS
Synchronisation Synchronisation Synchronisation Synchronisation Synchronisation Synchronisation Synchronisation
IED SPS Synchronisation SPS de Synchronisation de l'IED IED SPS Synchronisation IED SPS Synchronisation IED SPS Synchronisation IED SPS Synchronisation IED SPS Synchronisation
Test control DPC DPC de control de test Test control DPC Test control DPC Test control DPC Test control DPC Test control DPC
TMU status TMU statut TMU status TMU status TMU status TMU status TMU status
Watchdog error SPS SPS erreur watchdog Watchdog error SPS Watchdog error SPS Watchdog error SPS Watchdog error SPS Watchdog error SPS
HBU status HBU statut HBU status HBU status HBU status HBU status HBU status
Agency status Etat agence Agency status Agency status Agency status Agency status Agency status
AIU status AIU statut AIU status AIU status AIU status AIU status AIU status
AIU status AIU statut AIU status AIU status AIU status AIU status AIU status
Auto archiving Archivage auto Auto archiving Auto archiving Auto archiving Auto archiving Auto archiving
BackupPrint stat Etat imp. backup BackupPrint stat BackupPrint stat BackupPrint stat BackupPrint stat BackupPrint stat
BIU status BIU statut BIU status BIU status BIU status BIU status BIU status
DREC ready Perturbo prête DREC ready DREC ready DREC ready DREC ready DREC ready
CCU status CCU statut CCU status CCU status CCU status CCU status CCU status
Central archive Archive centrale Central archive Central archive Central archive Central archive Central archive
Counter Top Top compteur Counter Top Counter Top Counter Top Counter Top Counter Top
DB incoh. SPS SPS DB incoh. DB incoh. SPS DB incoh. SPS DB incoh. SPS DB incoh. SPS DB incoh. SPS
DB switch ctrl ctrl bascul. BD DB switch ctrl DB switch ctrl DB switch ctrl DB switch ctrl DB switch ctrl
Device link Lien équipement Device link Device link Device link Device link Device link
Device mode Mode équip. Device mode Device mode Device mode Device mode Device mode
DI acq stopped Acq DI arrêtée DI acq stopped DI acq stopped DI acq stopped DI acq stopped DI acq stopped
DIU status DIU statut DIU status DIU status DIU status DIU status DIU status
DOU status DOU statut DOU status DOU status DOU status DOU status DOU status
Ext clock status Etat horloge ext Ext clock status Ext clock status Ext clock status Ext clock status Ext clock status
GHU status GHU statut GHU status GHU status GHU status GHU status GHU status
IED DREC ready IED pert. prête IED DREC ready IED DREC ready IED DREC ready IED DREC ready IED DREC ready
IED SPS com. SPS com. IED IED SPS com. IED SPS com. IED SPS com. IED SPS com. IED SPS com.
IED SPS Synchro. SPS Synchro. IED IED SPS Synchro. IED SPS Synchro. IED SPS Synchro. IED SPS Synchro. IED SPS Synchro.
ISAGRAF status Etat ISAGRAF ISAGRAF status ISAGRAF status ISAGRAF status ISAGRAF status ISAGRAF status
ISAGRAF status Etat ISAGRAF ISAGRAF status ISAGRAF status ISAGRAF status ISAGRAF status ISAGRAF status
Loc/rem ctrl DPC DPC ctrl Loc/dis Loc/rem ctrl DPC Loc/rem ctrl DPC Loc/rem ctrl DPC Loc/rem ctrl DPC Loc/rem ctrl DPC
Local/remote DPS DPS local/distant Local/remote DPS Local/remote DPS Local/remote DPS Local/remote DPS Local/remote DPS
Local/remote SPS SPS loc/distant Local/remote SPS Local/remote SPS Local/remote SPS Local/remote SPS Local/remote SPS
Log Queue File du log Log Queue Log Queue Log Queue Log Queue Log Queue
Main status MV MV état princ. Main status MV Main status MV Main status MV Main status MV Main status MV
Mode control DPC DPC de contrôle du mode Mode control DPC Mode control DPC Mode control DPC Mode control DPC Mode control DPC
OI client link Lien client OI OI client link OI client link OI client link OI client link OI client link
Operating mode Mode exploitation Operating mode Operating mode Operating mode Operating mode Operating mode
Printer status DPS état imprimante Printer status Printer status Printer status Printer status Printer status
Red mode ctrl ctrl mode red Red mode ctrl Red mode ctrl Red mode ctrl Red mode ctrl Red mode ctrl
Red Status ctrl ctrl statut red Red Status ctrl Red Status ctrl Red Status ctrl Red Status ctrl Red Status ctrl
Red. change stat Stat changt red. Red. change stat Red. change stat Red. change stat Red. change stat Red. change stat
Redundancy mode Mode redondance Redundancy mode Redundancy mode Redundancy mode Redundancy mode Redundancy mode
Redundancy SPS SPS de Redondance Redundancy SPS Redundancy SPS Redundancy SPS Redundancy SPS Redundancy SPS
SCADA SPS com. SPS com. SCADA SCADA SPS com. SCADA SPS com. SCADA SPS com. SCADA SPS com. SCADA SPS com.
Soft. error SPS SPS erreur soft. Soft. error SPS Soft. error SPS Soft. error SPS Soft. error SPS Soft. error SPS
Synchronisation Synchronisation Synchronisation Synchronisation Synchronisation Synchronisation Synchronisation
Test control DPC DPC de control de test Test control DPC Test control DPC Test control DPC Test control DPC Test control DPC
TMU status TMU statut TMU status TMU status TMU status TMU status TMU status
HBU status HBU statut HBU status HBU status HBU status HBU status HBU status
UCA2 Coupling Couplage UCA2 UCA2 Coupling UCA2 Coupling UCA2 Coupling UCA2 Coupling UCA2 Coupling
Watchdog SPS SPS Watchdog Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS Watchdog SPS
Board status DPS DPS état carte Board status DPS Board status DPS Board status DPS Board status DPS Board status DPS
Red. change mode Mode changt red. Red. change mode Red. change mode Red. change mode Red. change mode Red. change mode
LD DREC ready LD DREC prêt LD DREC ready LD DREC ready LD DREC ready LD DREC ready LD DREC ready
AOU status AOU statut AOU status AOU status AOU status AOU status AOU status
Buff Ov Gtw 1 Buff Ov Gtw 1 Buff Ov Gtw 1 Buff Ov Gtw 1 Buff Ov Gtw 1 Buff Ov Gtw 1 Buff Ov Gtw 1
Buff Ov Gtw 2 Buff Ov Gtw 2 Buff Ov Gtw 2 Buff Ov Gtw 2 Buff Ov Gtw 2 Buff Ov Gtw 2 Buff Ov Gtw 2
Buff Ov OI Buff Ov OI Buff Ov OI Buff Ov OI Buff Ov OI Buff Ov OI Buff Ov OI
Buff Ov OI Bck Buff Ov OI Bck Buff Ov OI Bck Buff Ov OI Bck Buff Ov OI Bck Buff Ov OI Bck Buff Ov OI Bck
All IED status All IED status All IED status All IED status All IED status All IED status All IED status
All rack status All rack status All rack status All rack status All rack status All rack status All rack status
Local alarm ack Local alarm ack Local alarm ack Local alarm ack Local alarm ack Local alarm ack Local alarm ack
Setting done Setting done Setting done Setting done Setting done Setting done Setting done
Setting disc. Setting disc. Setting disc. Setting disc. Setting disc. Setting disc. Setting disc.
Setting in prog. Setting in prog. Setting in prog. Setting in prog. Setting in prog. Setting in prog. Setting in prog.
Setting incoher. Setting incoher. Setting incoher. Setting incoher. Setting incoher. Setting incoher. Setting incoher.
Rack link status Rack link status Rack link status Rack link status Rack link status Rack link status Rack link status
Red.Status Red.Status Red.Status Red.Status Red.Status Red.Status Red.Status
IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS IEC61850 gen SPS
IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS IEC61850 gen DPS
IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS IEC61850 gen MPS
IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC IEC61850 gen SPC
IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC IEC61850 gen DPC
IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV IEC61850 gen MV
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : System Functions SHEET : Fonctions Systèmes SHEET : System Functions SHEET : System Functions SHEET : System Functions SHEET : Функции системы SHEET : System Functions
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
SYSTEM PROFILES PROFILS SYSTEMES SYSTEM PROFILES SYSTEM PROFILES SYSTEM PROFILES Профили системы SYSTEM PROFILES
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : SystemInformation_Template SHEET : SystemInformation_Template SHEET : SystemInformation_Template SHEET : SystemInformation_Template SHEET : SystemInformation_Template SHEET : SystemInformation_Template SHEET : SystemInformation_Template
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
SYSTEM INFORMATION DATA DESCRIPTION INFORMATION SYSTEME DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION SYSTEM INFORMATION DATA DESCRIPTION ОПИСАНИЕ СИСТЕМНОЙ ИНФОРМАЦИИ SYSTEM INFORMATION DATA DESCRIPTION
Gateway Passerelle Gateway UTR UTR Шлюз Gateway
Port used (on gateway) Ports utilisés (sur la passerelle) Port used (on gateway) Puerto utilizado (en UTR) Porta utilizada (em UTR) Используемый порт (на шлюз) benutzter Port (Gateway)
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1 SCADA 1
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2 SCADA 2
Auto generated Génération automatique Auto generated Auto generado Auto Geração Автоматически сгенерировано Auto generated
SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3 SCADA 3
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4 SCADA 4
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : List of bays SHEET : Liste des Tranches SHEET : List of bays SHEET : Lista de bahías SHEET : Lista de Bays SHEET : Список ячеек SHEET : List of bays
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BAY INFORMATION INFORMATIONS SUR LES TRANCHES BAY INFORMATION INFORMACION DE BAHIAS Informação de Bays ИНФОРМАЦИЯ ПО ЯЧЕЙКЕ BAY INFORMATION
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Bay Name Nom de la Tranche Bay Name Nombre de bahía Nome do Painel Имя ячейки Bay Name
Bay Type Type de Tranche Bay Type Tipo de bahía Tipo de Painel Тип ячейки Bay Type
Computer Calculateur Computer Computador Computador Компьютер Computer
Redundant Computer Calculateur Redondant Redundant Computer Computador Redundante Computador Redundante Резервный компьютер Redundant Computer
Issue Révision Issue Revisión Revisão Версия Version
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : T101 Model SHEET : Modèles T101 SHEET : T101 Model SHEET : Modelo T101 SHEET : Modo T101 SHEET : Модель T101 SHEET : T101 Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA T101 DEBUT SCADA T101 BEGIN SCADA T101 COMIENZA SCADA T101 INÍCIO SCADA T101 НАЧАЛО ОПИСАНИЯ SCADA T101 BEGIN SCADA T101
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Grid
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Main communication channel Voie de communication principale Main communication channel Canal de comunicación principal Canal de Comunicação Principal Основной канал связи Main communication channel
Auxiliary Communication channel Voie de communication auxiliaire Auxiliary Communication channel Canal de comunciación auxiliar Canal de Comunicação auxiliar Запасной канал связи Auxiliary Communication channel
Baud rate (bit/s) Vitesse de transmission (bit/s) Baud rate (bit/s) Baudios (bit/s) Baud Rate (bit/s) Скорость в бодах (бит/с) Baud rate (bit/s)
Time Reference Temps de référence Time Reference Tiempo de referencia Tempo de referência Время ссылку Zeitplan
Redundancy type Type de redondance Redundancy type Tipo de redundancia Redundância tipo Избыточность типа Redundanz Typ
Link Address Adresse du lien Link Address Dirección del vínculo Endereço do Link Адрес связи Link Address
Redundant Link Address Adresse du lien redondant Redundant Link Address Dirección redundante del vínculo Endereço redundante do Vínculo Резервный адрес связи Redundant Link Address
Link Address Length Longueur de l'adresse du lien Link Address Length Longitud de la dirección del vínculo Tamanho do Endereço do Link Длина адреса связи Link Address Length
Common address of ASDU Adresse commune de l'ASDU Common address of ASDU Dirección común ASDU Endereço comum ASDU Общий адрес ASDU Common address of ASDU
Common address of ASDU Length Longueur de l'adresse commune de l'ASDU Common address of ASDU Length Longitud de la dirección común ASDU Tamanho do Endereço comum ASDU Длина общего адреса ASDU Common address of ASDU Length
Object structure Structure d'objet Object structure Estructura del objeto Estrutura do objeto Структура объекта Object structure
Frame max length Longueur maximale de la vue Frame max length Longitud máx de la trama Tamanho máx do frame Максимальная длина кадра Frame max length
Cause of Transmission Length Cause de longueur de transmission Cause of Transmission Length Longitud de la causa de transmisión Tamanho da causa de Transmissão Длина Cause of Transmission Cause of Transmission Length
Measurement periodic cycle Cycle Périodique de Mesure Measurement periodic cycle Ciclo de medición periódico Ciclo periódico de Medição Периодический цикл измерений Measurement periodic cycle
Binary Time Size Taille de Temps binaire Binary Time Size Tamaño de tiempo binario Tamanho Binário do Tempo Размер двоичной кодировки времени Binary Time Size
Background scan cycle Cycle de balayage Background scan cycle Ciclo "background scan" Ciclo "background scan" Фоновый цикл сканирования Background scan cycle
Type of link Type de lien Type of link Tipo de enlace Tipo de ligação Вид ссылки Art der Verknüpfung
Test frame timeout (T3) Expriration de la trame de test (T3) Test frame timeout (T3) Marco de tiempo de prueba (T3) Teste moldura Timeout (T3) Тест кадр тайм (T3) Prüfung Timeout (T3)
SBO timeout Temps d'expiration pour la sélection avant opération SBO timeout Tiempo fuera SBO Falha SBO Задержка SBO SBO Timeout
Inter frame duration Durée inter trame Inter frame duration Duración entre 2 fotogramas Duração entre 2 frames Продолжительность от 2 кадров Inter frame duration
Quality Value for 'Jammed' state Valeur de Qualité de l'état 'Jammed' Quality Value for 'Jammed' state Valor de calidad 'atascado' estado Qualidade Valor para 'emperrado' estado Качество стоимость для 'застряла' состояния Qualitäts für "gestaute" Zustand
Quality Value for toggling xPS Valeur de Qualité de bascule xPS Quality Value for toggling xPS Valor de calidad para alternar XPS Qualidade Valor para alternar xps Качество стоимость для переключения XPS Qualitäts für Makeln XPS
Quality Value for 'Unknown' state Valeur de Qualité de l'état 'Inconnu' Quality Value for 'Unknown' state Valor de calidad 'Desconocido' estado Qualidade Valor para 'Desconhecido' estado Качество стоимость для 'Неизвестное' состояние Qualitäts für "unbekannt" Zustand
SOE file support Support de fichier SOE SOE file support Archivo de apoyo SOE Arquivo apoio SOE файл поддержки SOE SOE file support
SOE file address Adresse de fichier SOE SOE file address Archivo dirección SOE Arquivo endereço SOE файл адрес SOE SOE file address
SOE file format Format de fichier SOE SOE file format Formato de archivo SOE Formato de arquivo SOE файл формата SOE SOE file format
SOE file nb of events Nb d'évenements dans le fichier SOE SOE file nb of events Número de expediente de hechos SOE Arquivo número de eventos SOE файл ряд мероприятий SOE SOE file nb of events
Nb max of SOE files Nombre maximum de fichiers SOE Nb max of SOE files número máximo de archivos de SOE Número máximo de arquivos SOE Максимальное количество SOE файлы Nb max of SOE files
Full SOE file nb of events Nb d'évenements dans le fichier SOE plein Full SOE file nb of events Completa número de expediente de hechos SOE Arquivo completo conjunto de eventos SOE полный файл SOE ряд мероприятий Full SOE file nb of events
Disturbance file support Support du fichier de Perturbographie Disturbance file support Perturbación archivo de apoyo Perturbação arquivo apoio Нарушение файл поддержки Disturbance-Unterstützung
Disturbance file address Adresse du fichier de Perturbographie Disturbance file address Perturbación archivo dirección Perturbação arquivo endereço Нарушение файл адрес Disturbance-Adresse
Disturbance file address for T103 Adresse du fichier de Perturbographie T103 Disturbance file address for T103 Perturbación archivo dirección T103 Perturbação arquivo endereço T103 Нарушение файл адрес T103 Disturbance-Adresse T103
Disturbance file address for S20 Adresse du fichier de Perturbographie S20 Disturbance file address for S20 Perturbación archivo dirección S20 Perturbação arquivo endereço S20 Нарушение файл адрес S20 Disturbance-Adresse S20
Disturbance file address for M300 Adresse du fichier de Perturbographie M300 Disturbance file address for M300 Perturbación archivo dirección M300 Perturbação arquivo endereço M300 Нарушение файл адрес M300 Disturbance-Adresse M300
Disturbance file address for SlowWave Adresse du fichier de Perturbographie SlowWave Disturbance file address for SlowWave Perturbación archivo dirección SlowWave Perturbação arquivo endereço SlowWave Нарушение файл адрес SlowWave Disturbance-Adresse SlowWave
Disturbance file address for FastWave Adresse du fichier de Perturbographie FastWave Disturbance file address for FastWave Perturbación archivo dirección FastWave Perturbação arquivo endereço FastWave Нарушение файл адрес FastWave Disturbance-Adresse FastWave
Nb max of Disturbance files Nombre maximum de fichiers de perturbographie Nb max of Disturbance files número máximo de archivos de perturbación Número máximo de arquivos Perturbação Максимальное количество нарушений файлы maximale Anzahl von Dateien Disturbance
Buffer Overflow file support Support du fichier de débordement de tampon Buffer Overflow file support Desbordamiento de búfer de archivo de apoyo Buffer overflow arquivo apoio Переполнение буфера файл поддержки Buffer Overflow-Unterstützung
Buffer Overflow file address Adresse du fichier de débordement de tampon Buffer Overflow file address Desbordamiento de búfer de archivo dirección Buffer overflow arquivo endereço Переполнение буфера файла адрес Buffer Overflow-Datei-Adresse
Buffer Overflow empty condition Condition vide de débordement de tampon Buffer Overflow empty condition Condición vacío de desbordamiento de búfer Buffer overflow vazio condição Переполнение буфера пустого состояния Buffer Overflow leeren Zustand
Balanced mode Mode balancé Balanced mode Modo Balanced Modo Balanced Сбалансированный режим Balanced mode
Balanced mode retry number Mode balancé nb d'essais Balanced mode retry number Modo Balanced el número de reintentos Modo Balanced número do reintentos Сбалансированный режим повтора номера Balanced mode retry Zahl
Balanced mode link timeout Expiration du mode balancé Balanced mode link timeout Tiempo de modo Balanced enlace Falha do modo Balanced Сбалансированный режим ссылку тайм Balanced mode link timeout
Sequence of Information value for TS Séquence d'Information valeur de TS Sequence of Information value for TS Secuencia de la información de valor para el TS Sequência de Informação valor para TS Последовательность Информация значение для ТП Sequence of Information value for TS
Sequence of Information value for TM Séquence d'Information valeur de TM Sequence of Information value for TM Secuencia de la información de valor para TM Sequência de Informação valor para TM Последовательность Информация значение для TM Sequence of Information value for TM
Sequence of Information value for Counter Séquence d'Information valeur de Compteur Sequence of Information value for Counter Secuencia de la información de valor para Counter Sequência de Informação valor para Counter Последовательность Информация значение для борьбы Sequence of Information value for Counter
Sequence of Information Gap address to split Séquence d'Information écart d'adresse de séparation Sequence of Information Gap address to split Secuencia de la Información Brecha dirección para dividir Sequência de Informação Gap endereço para dividir Последовательность информационных пробелов адрес разделить Sequence of Information Gap address to split
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority [1-255] Prioritée [1-255] Priority [1-255] Prioridad [1-255] Prioridade[1-255] Приоритет [1-255] Priority [1-255]
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Background scan Balayage de fond Background scan Background scan Background scan Сканирование в фоновом режиме Background scan
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority [1-255] Prioritée [1-255] Priority [1-255] Prioridad [1-255] Prioridade[1-255] Приоритет [1-255] Priority [1-255]
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Background scan Balayage de fond Background scan Background scan Background scan Сканирование в фоновом режиме Background scan
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
MPS Data Type MPS Donnée de Type MPS Data Type MPS Datos tipo MPS Dados tipo MPS Тип данных MPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority [1-255] Prioritée [1-255] Priority [1-255] Prioridad [1-255] Prioridade[1-255] Приоритет [1-255] Priority [1-255]
Bitstring usage Utilisation du Bistring Bitstring usage Bitstring uso Estado invertido Bitstring использования Bitstring Nutzung
Background scan Balayage de fond Background scan Background scan Background scan Сканирование в фоновом режиме Background scan
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
SBO timeout [0-65535 s] Temps d'expiration pour la sélection avant opération [0-65535 s] SBO timeout [0-65535 s] SBO tiempo fuera [0-65535 s] Tempo Limite SBO[0-65535 s] Задерка SBO [0-65535 с] SBO timeout [0-65535 s]
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
SBO timeout [0-65535 s] Temps d'expiration pour la sélection avant opération [0-65535 s] SBO timeout [0-65535 s] SBO tiempo fuera [0-65535 s] Tempo Limite SBO[0-65535 s] Задерка SBO [0-65535 с] SBO timeout [0-65535 s]
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority [1-255] Prioritée [1-255] Priority [1-255] Prioridad [1-255] Prioridade[1-255] Приоритет [1-255] Priority [1-255]
Format Format Format Formato Formato Формат Format
Cycle Type Type de Cycle Cycle Type Tipo de ciclo Tipo de Ciclo Тип цикла Cycle Type
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
Format Format Format Formato Formato Формат Format
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
SBO timeout [0-65535 s] Temps d'expiration pour la sélection avant opération [0-65535 s] SBO timeout [0-65535 s] SBO tiempo fuera [0-65535 s] Tempo Limite SBO[0-65535 s] Задерка SBO [0-65535 с] SBO timeout [0-65535 s]
Counter Data Type Compteur de Donnée de Type Counter Data Type Counter Datos tipo Contador de Dados tipo Counter Тип данных Counter Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-4] (0=no) Groupes [0-4] (0=non) Group [0-4] (0=no) Grupo [0-4] (0=no) Grupo [0-4] (0=não) Группа [0-4] (0=no) Gruppe [0-4] (0=no)
Priority [1-255] Prioritée [1-255] Priority [1-255] Prioridad [1-255] Prioridade[1-255] Приоритет [1-255] Priority [1-255]
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : DNP3 Model SHEET : Modèles DNP3 SHEET : DNP3 Model SHEET : Modelo DNP3 SHEET : Modo DNP3 SHEET : Модель DNP3 SHEET : DNP3 Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA DNP3 DEBUT SCADA DNP3 BEGIN SCADA DNP3 COMIENZA SCADA DNP3 INÍCIO SCADA DNP3 НАЧАЛО ОПИСАНИЯ SCADA ПРОТОКОЛА DNP3 BEGIN SCADA DNP3
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Main communication channel Voie de communication principale Main communication channel Canal de comunicación principal Canal de Comunicação Principal Основной канал связи Main communication channel
Auxiliary Communication channel Voie de communication auxiliaire Auxiliary Communication channel Canal de comunciación auxiliar Canal de Comunicação auxiliar Запасной канал связи Auxiliary Communication channel
Baud rate (bit/s) Vitesse de transmission (bit/s) Baud rate (bit/s) Baudios (bit/s) Baud Rate (bit/s) Скорость в бодах (бит/с) Baud rate (bit/s)
Time Reference Temps de référence Time Reference Tiempo de referencia Tempo de referência Время ссылку Zeitplan
TCP/IP usage Utilise TCP/IP TCP/IP usage Uso de TCP/IP Usos de TCP/IP использование TCP/IP TCP/IP usage
TCP/IP Address Adresse TCP/IP TCP/IP Address TCP/IP Dirección TCP/IP Endereço TCP/IP Адрес TCP/IP Address
Link Address Adresse du lien Link Address Dirección del vínculo Endereço do Link Адрес связи Link Address
Digital information class Classe d'information numérique Digital information class Clase de información digital Classe de Informação Digital Тип цифровой информации Digital information class
Measurement values class Classe de valeur de mesure Measurement values class Clase de valores de medición Classe de Valores de Medição Тип измеряемых величин Measurement values class
Counter class Classe de compteur Counter class Clase de contadores Classe de contadores Тип счетчика Counter class
Measurement format Format de mesure Measurement format El formato de medición Medição formato Измерение формате Messung format
Static Measurement Mesure statique Static Measurement Medida estática Static Medição Статические измерения Statische Messung
Event Measurement Mesure évènementielle Event Measurement Medida eventa Evento Medição Событие измерения Event-Messung
Counter format Format de compteur Counter format Contador el formato Contador formato Счетчик формате Counter-Format
Static Counter Compteur statique Static Counter Contador estática Static Contador Статические Счетчик Statische Counter
Event Counter Compteur évènementielle Event Counter Contador eventa Evento Contador Событие Счетчик Event Counter
Inter frame duration Durée inter trame Inter frame duration Duración entre 2 fotogramas Duração entre 2 frames Продолжительность от 2 кадров Inter frame duration
SBO timeout Temps d'expiration pour la sélection avant opération SBO timeout Tiempo fuera SBO Falha SBO Задержка SBO SBO Timeout
Spontaneous message enabled Message spontané actif Spontaneous message enabled Espontáneo mensaje habilitado Espontâneas mensagem ativado Спонтанные сообщения позволили Spontan Nachricht aktiviert
Spontaneous message class Classe de message spontané Spontaneous message class Espontánea clase de mensaje Espontâneas mensagem classe Спонтанное сообщение класс Spontan Nachrichtenklasse
SOE file support Support de fichier SOE SOE file support Archivo de apoyo SOE Arquivo apoio SOE файл поддержки SOE SOE file support
SOE file address Adresse de fichier SOE SOE file address Archivo dirección SOE Arquivo endereço SOE файл адрес SOE SOE file address
SOE file format Format de fichier SOE SOE file format Formato de archivo SOE Formato de arquivo SOE файл формата SOE SOE file format
SOE file nb of events Nb d'évenements dans le fichier SOE SOE file nb of events Número de expediente de hechos SOE Arquivo número de eventos SOE файл ряд мероприятий SOE SOE file nb of events
Full SOE file nb of events Nb d'évenements dans le fichier SOE plein Full SOE file nb of events Completa número de expediente de hechos SOE Arquivo completo conjunto de eventos SOE полный файл SOE ряд мероприятий Full SOE file nb of events
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
MPS Data Type MPS Donnée de Type MPS Data Type MPS Datos tipo MPS Dados tipo MPS Тип данных MPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Bitstring usage Utilisation du Bistring Bitstring usage Bitstring uso Estado invertido Bitstring использования Bitstring Nutzung
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Format Format Format Formato Formato Формат Format
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
Defined as counter Défini comme compteur Defined as counter Definido como contador Definido como contador Определяется как борьба Definiert als Zähler
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
Format Format Format Formato Formato Формат Format
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
Counter Data Type Compteur de Donnée de Type Counter Data Type Counter Datos tipo Contador de Dados tipo Counter Тип данных Counter Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : T104 Model SHEET : Modèles T104 SHEET : T104 Model SHEET : Modelo T104 SHEET : Modo T104 SHEET : Модель T104 SHEET : T104 Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA T104 DEBUT SCADA T104 BEGIN SCADA T104 COMIENZA SCADA T104 INÍCIO SCADA T104 НАЧАЛО ОПИСАНИЯ SCADA T104 BEGIN SCADA T104
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Time Reference Temps de référence Time Reference Tiempo de referencia Tempo de referência Время ссылку Zeitplan
TCP/IP Address Adresse TCP/IP TCP/IP Address TCP/IP Dirección TCP/IP Endereço TCP/IP Адрес TCP/IP Address
Common address of ASDU Adresse commune de l'ASDU Common address of ASDU Dirección común ASDU Endereço comum ASDU Общий адрес ASDU Common address of ASDU
Address structure Structure de l'adresse Address structure Estructura de la dirección Estrutura do endereço Структура решения Struktur der Adresse
Frame max length Longueur maximale de la vue Frame max length Longitud máx de la trama Tamanho máx do frame Максимальная длина кадра Frame max length
Measurement periodic cycle Cycle Périodique de Mesure Measurement periodic cycle Ciclo de medición periódico Ciclo periódico de Medição Периодический цикл измерений Measurement periodic cycle
Binary Time Size Taille de Temps binaire Binary Time Size Tamaño de tiempo binario Tamanho Binário do Tempo Размер двоичной кодировки времени Binary Time Size
Background scan cycle Cycle de balayage Background scan cycle Ciclo "background scan" Ciclo "background scan" Фоновый цикл сканирования Background scan cycle
Connection timeout (T0) Expiration de la Connexion (T0) Connection timeout (T0) Connection tiempo fuera (T0) Falha de Conexão (T0) Задержка соединения (T0) Connection timeout (T0)
APDU timeout (T1) Expiration de l'APDU (T1) APDU timeout (T1) APDU tiempo fuera (T1) Falha APDU (T1) Задержка APDU (T1) APDU timeout (T1)
Acknowledgement timeout (T2) Expiration de la Réception (T2) Acknowledgement timeout (T2) Acknowledgement tiempo fuera (T2) Falha de Reconhecimento (T2) Задержка подтвердения (T2) Acknowledgement timeout (T2)
Test frame timeout (T3) Expriration de la trame de test (T3) Test frame timeout (T3) Marco de tiempo de prueba (T3) Teste moldura Timeout (T3) Тест кадр тайм (T3) Prüfung Timeout (T3)
Sent unack. Frames window size (K) Taille de la fenêtre d'envoi d'acquis négatif Sent unack. Frames window size (K) Tamaño de ventana de tramas enviadas no reconocidas (K) Tamanho de janelas de frames enviadas Não reconhecidas (K) Sent unack. Frames window size (K) Sent unack. Frames window size (K)
Ack. Received frames window size (W) Taille de la fenêtre de réception d'acquis positif Ack. Received frames window size (W) Tamaño de ventana de tramas recibidas y reconocidas (W) Tamanho de janelas de frames recebidas e reconhecidas (W) Ack. Received frames window size (W) Ack. Received frames window size (W)
Max command delay Délai maximum de la Commande Max command delay Retardo de comando Máx Retardo de comando Máx Max command delay Max command delay
Socket IP #1 Socket IP #1 Socket IP #1 Socket IP #1 Socket IP #1 Socket IP #1 Socket IP #1
Socket IP #2 Socket IP #2 Socket IP #2 Socket IP #2 Socket IP #2 Socket IP #2 Socket IP #2
Socket IP #3 Socket IP #3 Socket IP #3 Socket IP #3 Socket IP #3 Socket IP #3 Socket IP #3
Socket IP #4 Socket IP #4 Socket IP #4 Socket IP #4 Socket IP #4 Socket IP #4 Socket IP #4
SBO timeout Temps d'expiration pour la sélection avant opération SBO timeout Tiempo fuera SBO Falha SBO Задержка SBO SBO Timeout
Quality Value for 'Jammed' state Valeur de Qualité de l'état 'Jammed' Quality Value for 'Jammed' state Valor de calidad 'atascado' estado Qualidade Valor para 'emperrado' estado Качество стоимость для 'застряла' состояния Qualitäts für "gestaute" Zustand
Quality Value for toggling xPS Valeur de Qualité de bascule xPS Quality Value for toggling xPS Valor de calidad para alternar XPS Qualidade Valor para alternar xps Качество стоимость для переключения XPS Qualitäts für Makeln XPS
Quality Value for 'Unknown' state Valeur de Qualité de l'état 'Inconnu' Quality Value for 'Unknown' state Valor de calidad 'Desconocido' estado Qualidade Valor para 'Desconhecido' estado Качество стоимость для 'Неизвестное' состояние Qualitäts für "unbekannt" Zustand
Switchover Switchover Switchover Switchover Switchover Switchover Switchover
SOE file support Support de fichier SOE SOE file support Archivo de apoyo SOE Arquivo apoio SOE файл поддержки SOE SOE file support
SOE file address Adresse de fichier SOE SOE file address Archivo dirección SOE Arquivo endereço SOE файл адрес SOE SOE file address
SOE file format Format de fichier SOE SOE file format Formato de archivo SOE Formato de arquivo SOE файл формата SOE SOE file format
SOE file nb of events Nb d'évenements dans le fichier SOE SOE file nb of events Número de expediente de hechos SOE Arquivo número de eventos SOE файл ряд мероприятий SOE SOE file nb of events
Nb max of SOE files Nombre maximum de fichiers SOE Nb max of SOE files número máximo de archivos de SOE Número máximo de arquivos SOE Максимальное количество SOE файлы Nb max of SOE files
Full SOE file nb of events Nb d'évenements dans le fichier SOE plein Full SOE file nb of events Completa número de expediente de hechos SOE Arquivo completo conjunto de eventos SOE полный файл SOE ряд мероприятий Full SOE file nb of events
Disturbance file support Support du fichier de Perturbographie Disturbance file support Perturbación archivo de apoyo Perturbação arquivo apoio Нарушение файл поддержки Disturbance-Unterstützung
Disturbance file address Adresse du fichier de Perturbographie Disturbance file address Perturbación archivo dirección Perturbação arquivo endereço Нарушение файл адрес Disturbance-Adresse
Disturbance file address for T103 Adresse du fichier de Perturbographie T103 Disturbance file address for T103 Perturbación archivo dirección T103 Perturbação arquivo endereço T103 Нарушение файл адрес T103 Disturbance-Adresse T103
Disturbance file address for S20 Adresse du fichier de Perturbographie S20 Disturbance file address for S20 Perturbación archivo dirección S20 Perturbação arquivo endereço S20 Нарушение файл адрес S20 Disturbance-Adresse S20
Disturbance file address for M300 Adresse du fichier de Perturbographie M300 Disturbance file address for M300 Perturbación archivo dirección M300 Perturbação arquivo endereço M300 Нарушение файл адрес M300 Disturbance-Adresse M300
Disturbance file address for SlowWave Adresse du fichier de Perturbographie SlowWave Disturbance file address for SlowWave Perturbación archivo dirección SlowWave Perturbação arquivo endereço SlowWave Нарушение файл адрес SlowWave Disturbance-Adresse SlowWave
Disturbance file address for FastWave Adresse du fichier de Perturbographie FastWave Disturbance file address for FastWave Perturbación archivo dirección FastWave Perturbação arquivo endereço FastWave Нарушение файл адрес FastWave Disturbance-Adresse FastWave
Nb max of Disturbance files Nombre maximum de fichiers de perturbographie Nb max of Disturbance files número máximo de archivos de perturbación Número máximo de arquivos Perturbação Максимальное количество нарушений файлы maximale Anzahl von Dateien Disturbance
Buffer Overflow file support Support du fichier de débordement de tampon Buffer Overflow file support Desbordamiento de búfer de archivo de apoyo Buffer overflow arquivo apoio Переполнение буфера файл поддержки Buffer Overflow-Unterstützung
Buffer Overflow file address Adresse du fichier de débordement de tampon Buffer Overflow file address Desbordamiento de búfer de archivo dirección Buffer overflow arquivo endereço Переполнение буфера файла адрес Buffer Overflow-Datei-Adresse
Buffer Overflow empty condition Condition vide de débordement de tampon Buffer Overflow empty condition Condición vacío de desbordamiento de búfer Buffer overflow vazio condição Переполнение буфера пустого состояния Buffer Overflow leeren Zustand
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority Prioritée Priority Prioridad Prioridade[1-255] Приоритет Priority
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Background scan Balayage de fond Background scan Background scan Background scan Сканирование в фоновом режиме Background scan
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority Prioritée Priority Prioridad Prioridade[1-255] Приоритет Priority
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Background scan Balayage de fond Background scan Background scan Background scan Сканирование в фоновом режиме Background scan
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
MPS Data Type MPS Donnée de Type MPS Data Type MPS Datos tipo MPS Dados tipo MPS Тип данных MPS Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority Prioritée Priority Prioridad Prioridade[1-255] Приоритет Priority
Bitstring usage Utilisation du Bistring Bitstring usage Bitstring uso Estado invertido Bitstring использования Bitstring Nutzung
Background scan Balayage de fond Background scan Background scan Background scan Сканирование в фоновом режиме Background scan
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
SBO timeout [0-65535 s] Temps d'expiration pour la sélection avant opération [0-65535 s] SBO timeout [0-65535 s] SBO tiempo fuera [0-65535 s] Tempo Limite SBO[0-65535 s] Задерка SBO [0-65535 с] SBO timeout [0-65535 s]
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
SBO timeout [0-65535 s] Temps d'expiration pour la sélection avant opération [0-65535 s] SBO timeout [0-65535 s] SBO tiempo fuera [0-65535 s] Tempo Limite SBO[0-65535 s] Задерка SBO [0-65535 с] SBO timeout [0-65535 s]
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-16] (0=no) Groupes [0-16] (0=non) Group [0-16] (0=no) Grupo [0-16] (0=no) Grupo [0-16] (0=não) Группа [0-16] (0=no) Gruppe [0-16] (0=no)
Priority Prioritée Priority Prioridad Prioridade[1-255] Приоритет Priority
Format Format Format Formato Formato Формат Format
Cycle Type Type de Cycle Cycle Type Tipo de ciclo Tipo de Ciclo Тип цикла Cycle Type
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
Format Format Format Formato Formato Формат Format
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
SBO timeout [0-65535 s] Temps d'expiration pour la sélection avant opération [0-65535 s] SBO timeout [0-65535 s] SBO tiempo fuera [0-65535 s] Tempo Limite SBO[0-65535 s] Задерка SBO [0-65535 с] SBO timeout [0-65535 s]
Counter Data Type Compteur de Donnée de Type Counter Data Type Counter Datos tipo Contador de Dados tipo Counter Тип данных Counter Data Type
Event transmission Transmission d'évènements Event transmission Transmisión de eventos Transmissão de Eventos Событие передачи Event transmission
Group [0-4] (0=no) Groupes [0-4] (0=non) Group [0-4] (0=no) Grupo [0-4] (0=no) Grupo [0-4] (0=não) Группа [0-4] (0=no) Gruppe [0-4] (0=no)
Priority Prioritée Priority Prioridad Prioridade[1-255] Приоритет Priority
Event Record Enregistrement d'évènement Event Record Registro de eventos Registro de Eventos Запись события Event Record
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : MODBUS Model SHEET : Modèles MODBUS SHEET : MODBUS Model SHEET : Modelo MODBUS SHEET : Modo MODBUS SHEET : Модель MODBUS SHEET : MODBUS Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA MODBUS DEBUT SCADA MODBUS BEGIN SCADA MODBUS COMIENZA SCADA MODBUS INÍCIO SCADA MODBUS НАЧАЛО ОПИСАНИЯ ПРОТОКОЛА SCADA MODBUS BEGIN SCADA MODBUS
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Main communication channel Voie de communication principale Main communication channel Canal de comunicación principal Canal de Comunicação Principal Основной канал связи Main communication channel
Auxiliary Communication channel Voie de communication auxiliaire Auxiliary Communication channel Canal de comunciación auxiliar Canal de Comunicação auxiliar Запасной канал связи Auxiliary Communication channel
Baud rate (bit/s) Vitesse de transmission (bit/s) Baud rate (bit/s) Baudios (bit/s) Baud Rate (bit/s) Скорость в бодах (бит/с) Baud rate (bit/s)
TCP/IP usage Utilise TCP/IP TCP/IP usage Uso de TCP/IP Usos de TCP/IP использование TCP/IP TCP/IP usage
Link Address Adresse du lien Link Address Dirección del vínculo Endereço do Link Адрес связи Link Address
Inter frame duration Durée inter trame Inter frame duration Duración entre 2 fotogramas Duração entre 2 frames Продолжительность от 2 кадров Inter frame duration
Parity Parité Parity Paridad Paridade Четность Parity
SOE file support Support de fichier SOE SOE file support Archivo de apoyo SOE Arquivo apoio SOE файл поддержки SOE SOE file support
SOE file address Adresse de fichier SOE SOE file address Archivo dirección SOE Arquivo endereço SOE файл адрес SOE SOE file address
SOE file format Format de fichier SOE SOE file format Formato de archivo SOE Formato de arquivo SOE файл формата SOE SOE file format
SOE file nb of events Nb d'évenements dans le fichier SOE SOE file nb of events Número de expediente de hechos SOE Arquivo número de eventos SOE файл ряд мероприятий SOE SOE file nb of events
Full SOE file nb of events Nb d'évenements dans le fichier SOE plein Full SOE file nb of events Completa número de expediente de hechos SOE Arquivo completo conjunto de eventos SOE полный файл SOE ряд мероприятий Full SOE file nb of events
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Inversion Inversion Inversion Inversion Inversão Инверсия Inversion
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Double Address usage Utilisation du Double Adressage Double Address usage Doble dirección de uso Endereço duplo uso адрес двойного использования Double Address usage
Inversion Inversion Inversion Inversion Inversão Инверсия Inversion
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Format Format Format Formato Formato Формат Format
Precision [8-16] Précision [8-16] Precision [8-16] Precisión [8-16] Precisão [8-16] Точность [8-16] Precision [8-16]
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
Format Format Format Formato Formato Формат Format
Counter Data Type Compteur de Donnée de Type Counter Data Type Counter Datos tipo Contador de Dados tipo Counter Тип данных Counter Data Type
Format Format Format Formato Formato Формат Format
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : OPC Model SHEET : Modèles OPC SHEET : OPC Model SHEET : Modelo OPC SHEET : Modo OPC SHEET : Модель OPC SHEET : OPC Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA OPC DEBUT SCADA OPC BEGIN SCADA OPC COMIENZA SCADA OPC INÍCIO SCADA OPC НАЧАЛО ОПИСАНИЯ SCADA OPC BEGIN SCADA OPC
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
OPC value for 'Reset' OPC valeur pour 'Reset' OPC value for 'Reset' Valor OPC de 'Reajuste' Valor OPC de 'Reajuste' Значение OPC для статуса 'Reset' OPC value for 'Reset'
OPC value for 'Set' OPC valeur pour 'Set' OPC value for 'Set' Valor OPC de 'Ajuste' Valor OPC de 'Ajuste' Значение OPC для статуса 'Set' OPC value for 'Set'
OPC value for 'Jammed' OPC valeur pour 'Jammed' OPC value for 'Jammed' Valor OPC de 'Bloqueado' Valor OPC de 'bloqueado' Значение OPC для статуса 'Jammed' OPC value for 'Jammed'
OPC value for 'Open' OPC valeur pour 'Open' OPC value for 'Open' Valor OPC de 'Abierto' Valor OPC de 'Aberto' Значение OPC для статуса 'Open' OPC value for 'Open'
OPC value for 'Closed' OPC valeur pour 'Closed' OPC value for 'Closed' Valor OPC de 'Cerrado' Valor OPC de 'Fechado' Значение OPC для статуса 'Closed' OPC value for 'Closed'
OPC value for 'Undefined' OPC valeur pour 'Undefined' OPC value for 'Undefined' Valor OPC de 'Indefinido' Valor OPC de 'Indefinido' Значение OPC для статуса 'Undefined' OPC value for 'Undefined'
OPC value for 'Order Open' (set to 01) OPC valeur pour 'Order Open' (set to 01) OPC value for 'Order Open' (set to 01) Valor OPC de 'Orden de abierto' (estado 01) Valor OPC de 'Ordem de Aberto' (estado 01) Значение OPC для статуса 'Order Open' (установка в 01) OPC value for 'Order Open' (set to 01)
OPC value for 'Order Close' (set to 10) OPC valeur pour 'Order Close' (set to 10) OPC value for 'Order Close' (set to 10) Valor OPC de 'Orden de cerrado' (estado 10) Valor OPC de 'Ordem de Fechado' (estado 10) Значение OPC для статуса 'Order Close' (установка в 10) OPC value for 'Order Close' (set to 10)
OPC value for 'Order Reset' OPC valeur pour 'Order Reset' OPC value for 'Order Reset' Valor OPC de 'Order Reset' Valor OPC de 'Order Reset' Значение OPC для статуса 'Order Reset' OPC value for 'Order Reset'
OPC value for 'Order Set' OPC valeur pour 'Order Set' OPC value for 'Order Set' Valor OPC de 'Order Set' Valor OPC de 'Order Set' Значение OPC для статуса 'Order Set' OPC value for 'Order Set'
OPC Bool value for 'Reset' OPC Bool valeur pour 'Reset' OPC Bool value for 'Reset' Valor booleano OPC de 'Reset' Valor booleano OPC de 'Reset' OPC булево значение для 'Reset' OPC Bool value for 'Reset'
OPC Bool value for 'Set' OPC Bool valeur pour 'Set' OPC Bool value for 'Set' Valor booleano OPC de 'Set' Valor booleano OPC de 'Set' OPC булево значение для 'Set' OPC Bool value for 'Set'
OPC Bool value for 'Jammed' OPC Bool valeur pour 'Jammed' OPC Bool value for 'Jammed' Valor booleano OPC de 'Jammed' Valor booleano OPC de 'Jammed' OPC булево значение для 'Jammed' OPC Bool value for 'Jammed'
OPC Bool value for 'Open' OPC Bool valeur pour 'Open' OPC Bool value for 'Open' Valor booleano OPC de 'Open' Valor booleano OPC de 'Open' OPC булево значение для 'Open' OPC Bool value for 'Open'
OPC Bool value for 'Closed' OPC Bool valeur pour 'Closed' OPC Bool value for 'Closed' Valor booleano OPC de 'Closed' Valor booleano OPC de 'Closed' OPC булево значение для 'Closed' OPC Bool value for 'Closed'
OPC Bool value for 'Undefined' OPC Bool valeur pour 'Undefined' OPC Bool value for 'Undefined' Valor booleano OPC de 'Undefined' Valor booleano OPC de 'Undefined' OPC булево значение для 'Undefined' OPC Bool value for 'Undefined'
OPC Bool value for 'Order Open' (set to 01) OPC Bool valeur pour 'Order Open' (set to 01) OPC Bool value for 'Order Open' (set to 01) Valor booleano OPC de 'Order Open' (set to 01) Valor booleano OPC de 'Order Open' (set to 01) OPC булево значение для 'Order Open' (set to 01) OPC Bool value for 'Order Open' (set to 01)
OPC Bool value for 'Order Close' (set to 10) OPC Bool valeur pour 'Order Close' (set to 10) OPC Bool value for 'Order Close' (set to 10) Valor booleano OPC de 'Order Close' (set to 10) Valor booleano OPC de 'Order Close' (set to 10) OPC булево значение для 'Order Close' (set to 10) OPC Bool value for 'Order Close' (set to 10)
OPC Bool value for 'Order Reset' OPC Bool valeur pour 'Order Reset' OPC Bool value for 'Order Reset' Valor booleano OPC de 'Order Reset' Valor booleano OPC de 'Order Reset' OPC булево значение для 'Order Reset' OPC Bool value for 'Order Reset'
OPC Bool value for 'Order Set' OPC Bool valeur pour 'Order Set' OPC Bool value for 'Order Set' Valor booleano OPC de 'Order Set' Valor booleano OPC de 'Order Set' OPC булево значение для 'Order Set' OPC Bool value for 'Order Set'
OPC quality for 'SelfCheckFault' OPC qualité pour 'SelfCheckFault' OPC quality for 'SelfCheckFault' Calidad OPC de 'SelfCheckFault' Qualidade OPC de 'SelfCheckFault' OPC качество 'SelfCheckFault' OPC quality for 'SelfCheckFault'
OPC quality for 'Unknown' OPC qualité pour 'Unknown' OPC quality for 'Unknown' Calidad OPC de 'Unknown' Qualidade OPC de 'Unknown' OPC качество 'Unknown' OPC quality for 'Unknown'
OPC quality for 'Toggling' OPC qualité pour 'Toggling' OPC quality for 'Toggling' Calidad OPC de 'Toggling' Qualidade OPC de 'Toggling' OPC качество 'Toggling' OPC quality for 'Toggling'
OPC quality for 'Suppressed' OPC qualité pour 'Suppressed' OPC quality for 'Suppressed' Calidad OPC de 'Suppressed' Qualidade OPC de 'Suppressed' OPC качество 'Suppressed' OPC quality for 'Suppressed'
OPC quality for 'Forced' OPC qualité pour 'Forced' OPC quality for 'Forced' Calidad OPC de 'Forced' Qualidade OPC de 'Forced' OPC качество 'Forced' OPC quality for 'Forced'
OPC quality for 'Substituted' OPC qualité pour 'Substituted' OPC quality for 'Substituted' Calidad OPC de 'Substituted' Qualidade OPC de 'Substituted' OPC качество 'Substituted' OPC quality for 'Substituted'
OPC quality for 'Undefined' MPS MV Counter OPC qualité pour 'Undefined' MPS MV Compteur OPC quality for 'Undefined' MPS MV Counter Calidad OPC de 'Undefined' MPS MV Counter Qualidade OPC de 'Undefined' MPS MV Counter OPC качество 'Undefined' MPS MV Counter OPC quality for 'Undefined' MPS MV Counter
OPC quality for 'OverRange' MPS MV Counter OPC qualité pour 'OverRange' MPS MV Compteur OPC quality for 'OverRange' MPS MV Counter Calidad OPC de 'OverRange' MPS MV Counter Qualidade OPC de 'OverRange' MPS MV Counter OPC качество 'OverRange' MPS MV Counter OPC quality for 'OverRange' MPS MV Counter
OPC quality for 'OpenCircuit' MPS MV Counter OPC qualité pour 'OpenCircuit' MPS MV Compteur OPC quality for 'OpenCircuit' MPS MV Counter Calidad OPC de 'OpenCircuit' MPS MV Counter Qualidade OPC de 'OpenCircuit' MPS MV Counter OPC качество 'OpenCircuit' MPS MV Counter OPC quality for 'OpenCircuit' MPS MV Counter
OPC quality for 'LLLThreshold' OPC qualité pour 'LLLThreshold' OPC quality for 'LLLThreshold' Calidad OPC de 'LLLThreshold' Qualidade OPC de 'LLLThreshold' OPC качество 'LLLThreshold' OPC quality for 'LLLThreshold'
OPC quality for 'LLThreshold' OPC qualité pour 'LLThreshold' OPC quality for 'LLThreshold' Calidad OPC de 'LLThreshold' Qualidade OPC de 'LLThreshold' OPC качество 'LLThreshold' OPC quality for 'LLThreshold'
OPC quality for 'LThreshold' OPC qualité pour 'LThreshold' OPC quality for 'LThreshold' Calidad OPC de 'LThreshold' Qualidade OPC de 'LThreshold' OPC качество 'LThreshold' OPC quality for 'LThreshold'
OPC quality for 'HThreshold' OPC qualité pour 'HThreshold' OPC quality for 'HThreshold' Calidad OPC de 'HThreshold' Qualidade OPC de 'HThreshold' OPC качество 'HThreshold' OPC quality for 'HThreshold'
OPC quality for 'HHThreshold' OPC qualité pour 'HHThreshold' OPC quality for 'HHThreshold' Calidad OPC de 'HHThreshold' Qualidade OPC de 'HHThreshold' OPC качество 'HHThreshold' OPC quality for 'HHThreshold'
OPC quality for 'HHHThreshold' OPC qualité pour 'HHHThreshold' OPC quality for 'HHHThreshold' Calidad OPC de 'HHHThreshold' Qualidade OPC de 'HHHThreshold' OPC качество 'HHHThreshold' OPC quality for 'HHHThreshold'
OPC quality for 'Jammed' DPS OPC qualité pour 'Jammed' DPS OPC quality for 'Jammed' DPS Calidad OPC de 'Jammed' DPS Qualidade OPC de 'Jammed' DPS OPC качество 'Jammed' DPS OPC quality for 'Jammed' DPS
OPC quality for 'Undefined' DPS OPC qualité pour 'Undefined' DPS OPC quality for 'Undefined' DPS Calidad OPC de 'Undefined' DPS Qualidade OPC de 'Undefined' DPS OPC качество 'Undefined' DPS OPC quality for 'Undefined' DPS
OPC quality for 'Valid Set/Closed' OPC qualité pour 'Valid Set/Closed' OPC quality for 'Valid Set/Closed' Calidad OPC de 'Valid Set/Closed' Qualidade OPC de 'Valid Set/Closed' OPC качество 'Valid Set/Closed' OPC quality for 'Valid Set/Closed'
OPC quality for 'Valid Reset/Open' OPC qualité pour 'Valid Reset/Open' OPC quality for 'Valid Reset/Open' Calidad OPC de 'Valid Reset/Open' Qualidade OPC de 'Valid Reset/Open' OPC качество 'Valid Reset/Open' OPC quality for 'Valid Reset/Open'
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Historization Historisation Historization Histórico Histórico исторический Historischen
Format Format Format Formato Formato Формат Format
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Double Address usage Utilisation du Double Adressage Double Address usage Doble dirección de uso Endereço duplo uso адрес двойного использования Double Address usage
Historization Historisation Historization Histórico Histórico исторический Historischen
Format Format Format Formato Formato Формат Format
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
MPS Data Type MPS Donnée de Type MPS Data Type MPS Datos tipo MPS Dados tipo MPS Тип данных MPS Data Type
Historization Historisation Historization Histórico Histórico исторический Historischen
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
Format Format Format Formato Formato Формат Format
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
Format Format Format Formato Formato Формат Format
Double Address usage Utilisation du Double Adressage Double Address usage Doble dirección de uso Endereço duplo uso адрес двойного использования Double Address usage
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : Connections SHEET : Connectique SHEET : Connections SHEET : Conexiones SHEET : Conexões SHEET : Связи SHEET : Connections
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN DATA DEBUT DES DONNEES BEGIN DATA INICIO DE DATOS INICIO DOS DADOS НАЧАЛО ДАННЫХ BEGIN DATA
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : Column Presence Checking SHEET : Présence des Colonnes SHEET : Column Presence Checking SHEET : Columna de verificación SHEET : Checkup Coluna de Presença SHEET : Графа проведения проверки SHEET : Column Presence Checking
This sheet is to be used to indicate the cells/columns that are : Cette FEUILLE est utilisée pour indiquer les cellules/colonnes qui sont : This sheet is to be used to indicate the cells/columns that are : Esta hoja se utiliza para indicar las celdas/columnas que están : Esta Ficha se utiliza para indicar as céluas/colunas que estão : Этот лист используется для выделения ячеек/колонок, которые : This sheet is to be used to indicate the cells/columns that are :
- P : present in all corresponding sheets but the contents shall not be used by automatic tools - P : présentes dans toute les FEUILLES mais dont le contenu ne sera pas employé par les outils automatiques - P : present in all corresponding sheets but the contents shall not be used by automatic tools - P : presentes en todas las hojas correspondientes pero los contenidos no se deben utilizar por herramientas automáticas - P : Presentes em todas as Fichas correspondentes mas o conteúdo não podem ser utilizados por Ferramentas Automáticas -P : представлены во всех соответствующих листах, но содержание м.б. не использовано автоматич. Утилитами - P : present in all corresponding sheets but the contents shall not be used by automatic tools
- U : present in all corresponding sheets and shall be used by automatic tools - U : présentes dans toutes les FEUILLES et seront employées par les outils automatiques - U : present in all corresponding sheets and shall be used by automatic tools - U : presentes en todas las hojas correspondientes y se deben utilizar por herramientas automáticas - U : Presentes em todas as Fichas correspondentes e devem se utilizar por Ferramentas Automáticas -U : представлены во всех соответствующих листах и м.б. использованы автоматич. Утилитами - U : present in all corresponding sheets and shall be used by automatic tools
- A : not present in corresponding sheets - A : Absentes des FEUILLES - A : not present in corresponding sheets - A : no presentes en las hojas correspondientes - A : Não Presentes nas Fichas correspondentes -A : не представлены во всех соответствующих листах - A : not present in corresponding sheets
- PH : hide in all corresponding sheets but the contents shall not be used by automatic tools - PH :cachées dans toute les FEUILLES mais le contenu ne sera pas employée par les outils automatiques - PH : hide in all corresponding sheets but the contents shall not be used by automatic tools - PH : ocultas en todas las hojas correspondientes pero los contenidos no se deben utilizar por herramientas automáticas - PH : Ocultas em todas as Fichas correspondentes mas o conteúdo não podem ser utilizados por Ferramentas Automáticas -PH : скрыты во всех соответствующих листах, но содержание м.б. не использовано автоматич. Утилитами - PH : hide in all corresponding sheets but the contents shall not be used by automatic tools
- UH : hide in all corresponding sheets and shall be used by automatic tools - UH :cachées dans toutes les FEUILLES et seront employées par les outils automatiques - UH : hide in all corresponding sheets and shall be used by automatic tools - UH : ocultas en todas las hojas correspondientes y se deben utilizar por herramientas automáticas - UH : Ocultas em todas as Fichas correspondentes e devem se utilizar por Ferramentas Automáticas -UH : скрыты во всех соответствующих листах и м.б. использованы автоматич. Утилитами - UH : hide in all corresponding sheets and shall be used by automatic tools
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
MiCOM CXXX DESCRIPTION MiCOM CXXX DESCRIPTION MiCOM CXXX DESCRIPTION Descripción MiCOM CXXX Descrição MiCOM CXXX ОПИСАНИЕ MiCOM CXXX MiCOM CXXX DESCRIPTION
DI GROUPS GROUPES DES ENTREES NUMERIQUES DI GROUPS Grupos DI Grupos DI Группы DI DI GROUPS
SELF GENERATED DIGITAL INFORMATION ENTREES NUMERIQUES AUTOMATIQUES SELF GENERATED DIGITAL INFORMATION INFORMACION DIGITAL AUTO GENERADA Informação Digital Auto Gerada ЦИФРОВАЯ ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ SELBSTGENERIERTE DIGITAL INFORMATION
SELF GENERATED DIGITAL OUTPUT INFORMATION SORTIES NUMERIQUES AUTOMATIQUES SELF GENERATED DIGITAL OUTPUT INFORMATION INFORMACION DE SALIDAS DIGITALES AUTO GENERADAS Informação de saidas Digitais Auto Geradas ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ ЦИФРОВЫМИ ВЫХОДАМИ SELBSTGENERIERTE DIGITAL OUTPUT INFORMATION
SELF GENERATED ANALOG INFORMATION ENTREES ANALOGIQUES AUTOMATIQUES SELF GENERATED ANALOG INFORMATION INFORMACION ANALOGICA AUTO GENERADA Informação Analógica Auto Gerada АНАЛОГОВАЯ ИНФОРМАЦИЯ, СГЕНЕРИРОВАННАЯ SELBSTGENERIERTE ANALOG INFORMATION
SHEET : Column Default Value SHEET : Valeurs par Défaut SHEET : Column Default Value SHEET : Valor por defecto de columna SHEET : Valor padrão da Coluna SHEET : Графа стандартных величин SHEET : Column Default Value
This sheet is used to set default parameter value for each data. Cette FEUILLE est employée pour remplacer des valeurs par de nouvelles. This sheet is used to set default parameter value for each data. Esta hoja se utiliza para ajustar el parámetro por defecto para cada dato Esta Ficha se utiliza para ajustar os parâmetros de defeitos para cada dado. Этот лист применяется при установке стандартного значения параметра для каждого данного This sheet is used to set default parameter value for each data.
- set the Old parameter value to change in the "Old Value" line - placez l'ancienne valeur de paramètre dans la ligne "Ancienne valeur" - set the Old parameter value to change in the "Old Value" line - Ajusta el valor del parámetro anterior que se va a cambiar en la línea: "Valor anterior" - Ajusta o Valor do parâmetro anterior usado para Sobrescrever na linha: "Valor anterior" - установите старые значения параметров, выбрав строку "Old Value" - set the Old parameter value to change in the "Old Value" line
- set the New parameter value used to overwrite Old one in the "New Value" line - placez la nouvelle valeur du paramètre dans la ligne "Nouvelle valeur" - set the New parameter value used to overwrite Old one in the "New Value" line - Ajusta el valor del parámetro anterior que se va a cambiar en la línea: "Valor nuevo" - Ajusta o Valor do parámetro anterior usado para Sobrescrever na linha: "Valor novo" - установите новые значения параметров, перезаписав старые значения в строке "New Value" - set the New parameter value used to overwrite Old one in the "New Value" line
- It is possible to use regular expressions as 'Old value' to locate data by using: - Il est possible d'employer des expressions régulières pour filtrer les "Anciennes valeurs". - It is possible to use regular expressions as 'Old value' to locate data by using: - Es posible utilizar expresiones regulares como 'Valor anterior' para localozar datos utilizando: - É possível utilizar expressões regulares como 'Valor anterior' para localizar Dados utilizando: - Возможно использование определ. значения в линии "Old Value" для группы данных путем использования: - It is possible to use regular expressions as 'Old value' to locate data by using:
? Any single character. ? Tout caractère simple. ? Any single character. ? Cualquier caracter sencillo. ? qualquer caracter Simples. знака "?" для любого одиночного символа ? Any single character.
* Zero or more characters. * Zéro caractère ou plus. * Zero or more characters. * Cero o más caracteres. * Zero ou mais Caracteres. знака "*" для обозначения большего количества символов или не использования символов * Zero or more characters.
# Any single digit (0-9). # Tout chiffre simple (0-9). # Any single digit (0-9). # Cuaquier dígito sencillo (0-9). # Qualquer dígito Simples (0-9). знака "#" для обозначения любой цифры (0-9) # Any single digit (0-9).
[charlist] Any single character in charlist. [charlist] Tout caractère simple dans charlist. [charlist] Any single character in charlist. [caractlist] Cualquier caracter simple en la lista de caracteres. [caractlist] qualquer caracter Simples da Lista de caracteres. [charlist] Любой единичный символ из charlist [charlist] Any single character in charlist.
[!charlist] Any single character not in charlist. [!charlist] Tout caractère simple non compris dans charlist. [!charlist] Any single character not in charlist. [!caractlist] Cualquier caracter simple no incluido en la lista de caracteres. [!caractlist] qualquer caracter Simples não incluido na Lista de caracteres. [!charlist] Любой единичный символ не из charlist [!charlist] Any single character not in charlist.
- A group of one or more characters (charlist) enclosed in brackets ([ ]) can be used to - un groupes d'un ou plusieurs caractères (charlist) inclus entre crochets ([ ]) peut être employé à - A group of one or more characters (charlist) enclosed in brackets ([ ]) can be used to - Un grupo de uno o más caracteres (lista de caracteres) entre corchetes ([ ]) se puede utilizar para - Um grupo de um o mais caracteres (Lista de caracteres) entre colchetes ([ ]) pode-se utilizar para Группа из одного или нескольких символов (charlist), заключенная в квадратные скобки ([ ]), м.б. Использована - A group of one or more characters (charlist) enclosed in brackets ([ ]) can be used to
match any single character in string and can include almost any character code, partir de n'importe quel caractère simple dans la chaine et pouvant inclure presque n'importe quel code de caractère, match any single character in string and can include almost any character code, enlazar cualquier caracter sencillo en cadena y puede incluir casi cualquier código de caracteres armazenar qualquer caracter Simples em string e pode incluir quase qualquer código de caracteres для обозначения любого одиночного символа в строке и может включать практически любой символьный код, match any single character in string and can include almost any character code,
including digits. y compris des chiffres. including digits. incluyendo dígitos. incluindo dígitos. включая цифры. including digits.
- Note: To match the special characters left bracket ([), question mark (?), number sign (#), - note : pour utiliser les caractères spéciaux tels le crochet ouvrant ([), le point d'interrogation (?), le signe de nombre (#), - Note: To match the special characters left bracket ([), question mark (?), number sign (#), - Nota: Para enlazar los caracteres especiales corchete izquierdo ([), signo de interrogación (?), signo de número (#), - Nota: Para armazenar os caracteres Especiais colchete esquerdo ([), seguido de interrogacão (?), seguido do número (#), - Примечание: для обозначения символов левой скобки ([), вопроса (?), числа (#), звездочки (*), заключайте - Note: To match the special characters left bracket ([), question mark (?), number sign (#),
and asterisk (*), enclose them in brackets. The right bracket (]) can't be used within a group et l'astérisque (*), les mettre entre crochets. Le crochet droit (]) ne peut pas être utilisé dans un Groupes and asterisk (*), enclose them in brackets. The right bracket (]) can't be used within a group y asterisco, se deben poner entre corchetes. El corchete derecho (]) no se puede utilizar dentro de un grupo e asterisco, se devem ser colocados entre colchetes. O colchete direito (]) não pode ser utilizado dentro de um grupo их в квадратные скобки. Правая скобка (]), должна использоваться вместе с соответствующей группой символов, and asterisk (*), enclose them in brackets. The right bracket (]) can't be used within a group
to match itself, but it can be used outside a group as an individual character. de sélection, mais peut être employé en dehors to match itself, but it can be used outside a group as an individual character. para enlazarse a si mismo, pero se puede utilizar fuera de un grupo como un carácter individual. para armazenar a si mesmo, mas pode-se utilizar fora de um grupo como un carácter individual. При использовании дефиса (-) для отделения верхних и нижних границ диапазона, charlist может определять to match itself, but it can be used outside a group as an individual character.
- By using a hyphen (-) to separate the upper and lower bounds of the range, charlist can - en employant un trait d'union (-) pour séparer les limites supérieures et inférieures de la liste, charlist peut - By using a hyphen (-) to separate the upper and lower bounds of the range, charlist can - Mediante el uso de un guión (-) para separar los extremos superior e inferior del rango, la lista de caracteres puede - Mediante eo uso de um hífem (-) para separar os extremos superior e inferior do Range, a Lista de caracteres pode несколько символов. Например, [A-Z] пишется в случае, если в соответствующих позициях в строке - By using a hyphen (-) to separate the upper and lower bounds of the range, charlist can
specify a range of characters. For example, [A-Z] results in a match if the corresponding indiquer une liste des caractères. Par exemple, [ A-Z ] correspond a toutes les lettres majuscules de l'alphabet. specify a range of characters. For example, [A-Z] results in a match if the corresponding especificar un rango de caracteres. Por ejemplo, [A-Z] da como resultado un conjunto si la posición correspondiente especificar um Range de caracteres. Por exemplo, [A-Z] da como resultado um conjunto se a posição correspondente встречаются любые заглавные буквы в диапазоне A-Z. Диапазон заключается в квадратные скобки без specify a range of characters. For example, [A-Z] results in a match if the corresponding
character position in string contains any uppercase letters in the range A-Z. Multiple ranges Les listes multiples sont incluses dans character position in string contains any uppercase letters in the range A-Z. Multiple ranges al carácter en cadena contiene algunas letras en mayúsculas en el rango A-Z. Múltiples rangos ao caracter em string Possui algumas letras em maiúsculass no Range A-Z. Multiplos Ranges estarão incluidos использования character position in string contains any uppercase letters in the range A-Z. Multiple ranges
are included within the brackets without delimiters. les crochets sans délimiteurs. are included within the brackets without delimiters. están incluidos dentro de los corchetes sin delimitadores. dentro dos colchetes sem domitadores. ограничителей. are included within the brackets without delimiters.
Example: Exemple: Example: Ejemplo: Exemplo: Примеры: Example:
aBBBa' is like 'a*a' aBBBa' est reconnu par l'expression régulière 'a*a' aBBBa' is like 'a*a' aBBBa' es similar 'a*a' aBBBa' é igual 'a*a' aBBBa' аналогично 'a*a' aBBBa' is like 'a*a'
F' is like '[A-Z]' F' est reconnu par l'expression régulière '[A-Z]' F' is like '[A-Z]' F' es similar '[A-Z]' F' é igual '[A-Z]' F' аналогично '[A-Z]' F' is like '[A-Z]'
F' is NOT like '[!A-Z]' F' n'est pas reconnu par l'expression régulière '[!A-Z]' F' is NOT like '[!A-Z]' F' NO es similar '[!A-Z]' F' Não é igual a '[!A-Z]' F' НЕ аналогично '[!A-Z]' F' is NOT like '[!A-Z]'
a2a' is like 'a#a' a2a' est reconnu par l'expression régulière 'a#a' a2a' is like 'a#a' a2a' es similar 'a#a' a2a' é igual a 'a#a' a2a' НЕ аналогично 'a#a' a2a' is like 'a#a'
aM5b' is like 'a[L-P]#[!c-e]' aM5b' est reconnu par l'expression régulière 'a[L-P]#[!c-e]' aM5b' is like 'a[L-P]#[!c-e]' aM5b' es similar 'a[L-P]#[!c-e]' aM5b' é igual a '[L-P]#[!c-e]' aM5b' аналогично 'a[L-P]#[!c-e]' aM5b' is like 'a[L-P]#[!c-e]'
BAT123khg' is like 'B?T*' BAT123khg' est reconnu par l'expression régulière 'B?T*' BAT123khg' is like 'B?T*' BAT123khg' es similar 'B?T*' BAT123khg' é igual a 'B?T*' BAT123khg' аналогично 'B?T*' BAT123khg' is like 'B?T*'
CAT123khg' is NOT like 'B?T*' CAT123khg' n'est pas reconnu par l'expression régulière 'B?T*' CAT123khg' is NOT like 'B?T*' CAT123khg' NO es similar 'B?T*' CAT123khg' Não é igual a 'B?T*' CAT123khg' НЕ аналогично 'B?T*' CAT123khg' is NOT like 'B?T*'
Old Value Ancienne valeur Old Value Valor anterior Valor anterior Старое значение Old Value
New Value Nouvelle valeur New Value Valor nuevo Valor novo Новое значение New Value
SHEET : Column Selection For Data Copy SHEET : Sélection Colonnes pour Copie SHEET : Column Selection For Data Copy SHEET : Selección de columna para Copia SHEET : Seleção de Coluna para Cópia SHEET : Выбор колонок для копирования данных SHEET : Column Selection For Data Copy
This sheet is to be used to indicate the cells/columns for which the contents shall be copied to a new DataList release. Cette FEUILLE est utilisée pour indiquer les cellules pour lesquelles le contenu sera copié dans une nouvelle version de Dataliste. This sheet is to be used to indicate the cells/columns for which the contents shall be copied to a new DataList release. Esta hoja se utiliza para indicar las celdas/columnas para las cuales los contenidos deben ser copiados a una versión Esta Ficha se utiliza para indicar as céluas/colunas para as quais os conteúdos devem ser copiados a uma versão Лист используется при выделении ячеек/колонок, содержимое которых м.б. скопировано в новую версию DataList. This sheet is to be used to indicate the cells/columns for which the contents shall be copied to a new DataList release.
The possible values are : Les valeurs possibles sont : The possible values are : nueva de lista de datos. Los valores posibles son : nova de Lista de Dados. os Valores possíveis são : Возможные значения: The possible values are :
- N : do not copy in any case - N : ne pas copier - N : do not copy in any case - N : No copiar en cualquier caso - N : Não copiar em qualquer caso -N : не копировать в любом случае - N : do not copy in any case
- C : copy in any case (when the line is significant) - C : copier de toute façon (quand la ligne est significative) - C : copy in any case (when the line is significant) - C : copiar solo en cierto caso (cuando la línea es significativa) - C : Copiar só em certo caso (quando a linha é significativa) -С : копировать в любом случае (если линия является значимой) - C : copy in any case (when the line is significant)
- E : copy only if the cell within new release is empty - E : copier seulement si la cellule dans la nouvelle version est vide - E : copy only if the cell within new release is empty - E : copiar solamente si la celda dentro de la nueva versión está vacía - E : Copiar somente se a célula dentro da nova versão está vazia -Е : копировать только в те ячейки, в которых новая версия отсутствует - E : copy only if the cell within new release is empty
SHEET : Matrix SHEET : Matrix SHEET : Matrix SHEET : Matrix SHEET : Matrix SHEET : Matrix SHEET : Matrix
This sheet indicates the cells/columns used for building comparison criteria. Cette FEUILLE indique les cellules/colonnes utilisées pour définir des critères de comparaison. This sheet indicates the cells/columns used for building comparison criteria. Esta hoja indica las celdas/columnas utilizadas para construir criterios de comparación Esta Ficha indica as céluas/colunas utilizadas para construir criterios de comparação Лист используется при выделении ячеек/колонок, используемых для построения критерия сравнения This sheet indicates the cells/columns used for building comparison criteria.
The possible values are : Les valeurs possibles sont : The possible values are : nueva de lista de datos. Los valores posibles son : nova de Lista de Dados. os Valores possíveis são : Возможные значения: The possible values are :
- P : present in all corresponding sheets but the contents shall not be used to build comparison criteria - P : présent dans tout la FEUILLE correspondante mais le contenu ne sera pas employé comme Critère de comparaison - P : present in all corresponding sheets but the contents shall not be used to build comparison criteria - P : presente en todas las hojas correspondientes pero los contenidos no deben ser utilizados para construir criterios de comparación - P : Presente em todas as Fichas correspondentes mas os conteúdos não devem ser utilizados para construir criterios de comparação -P : присутствует во всех соответствующих листах, но содержание не м.б. использовано для построения критерия - P : present in all corresponding sheets but the contents shall not be used to build comparison criteria
- U : present in all corresponding sheets and shall be used to build comparison criteria - U : présent dans toute les FEUILLEs et sera utilisé pour établir un critère de comparaison - U : present in all corresponding sheets and shall be used to build comparison criteria - U : presente en todas las hojas correspondientes y deben ser utilizados para construir criterios de comparación - U : Presente em todas as Fichas correspondentes e devem ser utilizados para construir criterios de comparação -U : присутствует во всех соответствующих листах и м.б. использовано для построения критерия - U : present in all corresponding sheets and shall be used to build comparison criteria
Use this Matrix Case Utiliser ce cas de Matrix Use this Matrix Case Caso utilizar ésta Matriz Caso utilizar ésta Matriz Используйте данных матричный блок Use this Matrix Case
SHEET : HELP_C264 SHEET : AIDE C264 SHEET : HELP_C264 SHEET : AYUDA C264 SHEET : AJUDA C264 SHEET : Помощь по C264 SHEET : HELP_C264
COUNTER INFORMATION FROM IED ENTREES COMPTEUR DE l'IED COUNTER INFORMATION FROM IED INFORMACION CONTADOR DESDE IED Informação CONTADOR deste IED Информация счетчика с IED COUNTER INFORMATION FROM IED
IED name NOM DE l'IED IED name NOMBRE DE IED Nome do IED Имя IED IED name
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
IED Counter Reference Référence de la carte d'entrée Compteur de l'IED IED Counter Reference Referencia Contador IED Referência Contador IED Ссылка счетчика IED IED Counter Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Link Lien Link Vínculo Vínculo Связь Link
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Information Adresse T103: ASDU nb;Fonction type MODBUS: Mapping Adresse;InputFormat DNP3: Adresse IEC: LD;LN T10X MASTER: Information Adresse T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address T101: Dirección de información T103: ASDU no;Tipo de función MODBUS: Dirección de mapeo;InputFormat DNP3: Dirección IEC: LD;LN T10X MASTER: Dirección de información T101: Endereço de Informação T103: ASDU no;Tipo de Função MODBUS: Endereço de Mapeamento;InputFormat DNP3: Endereço IEC: LD;LN T10X MASTER: Endereço de Informação T101: адрес информации T103: Номер ASDU ;Тип функции MODBUS: Адрес сигнала;InputFormat DNP3: Адрес IEC: LD;LN T10X MASTER: адрес информации T101: Information Address T103: ASDU nb;Function type MODBUS: Mapping address;InputFormat DNP3: Address IEC: LD;LN T10X MASTER: Information Address
T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101:Adresse Commune ASDU T103: Information nb;Adresse CommuneASDU MODBUS: Fonction DNP3: Non utilisé IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Adresse Commune ASDU;Data type T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type T101: Dirección común ASDU T103: No. de información;Dirección común ASDU MODBUS: Función DNP3: No utilizado IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Dirección común ASDU;Data type T101: Endereço comum ASDU T103: No. de Informação;Endereço comum ASDU MODBUS: Função DNP3: Não Utilizado IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Endereço comum ASDU;Data type T101: Общий адрес ASDU T103: информационный номер;Общий адрес ASDU MODBUS: Функция DNP3: Не используется IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Общий адрес ASDU;Data type T101: Common address ASDU T103: Information nb;Common address ASDU MODBUS: Function DNP3: Not used IEC: FC;Data Object;DataAttribute;CDC T10X MASTER: Common address ASDU;Data type
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Counter Type Type du Compteur Counter Type Tipo de Contador Tipo de Contador Противодействие Тип Counter Type
Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Standard: Validation (ms);Invalidité (ms);Cumul (mn) Energy: Facteur d'echelle;Periode de transmission (mn) Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Estándar: Válidación (ms);Inválidación (ms);Cumulación (mn) Energía: Factor de posicionamiento;Periode de la transmisión (mn) Padrão: Validação (ms);Invalidação (ms);Cumulação (mn) Energia: Fator de escala;Periode da transmissão (mn) Стандарт: Проверка (мс);Invalidity (ms);Cumul (mn) Энергия: Scale factor;Период передачи (мс) Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Integrate MV Intègre la MV Integrate MV Integrate MV Integrate MV Integrate MV Integrate MV
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
SELF GENERATED COUNTER INFORMATION ENTREES COMPTEUR AUTOMATIQUES SELF GENERATED COUNTER INFORMATION INFORMACION CONTADOR AUTO GENERADA Informação CONTADOR Auto Gerada Информация, сгенерированная счетчиком SELBSTGENERIERTE COUNTER INFORMATION
SELF GENERATED COUNTER INFORMATION ENTREES COMPTEUR AUTOMATIQUES SELF GENERATED COUNTER INFORMATION INFORMACION CONTADOR AUTO GENERADA Informação CONTADOR Auto Gerada Информация, сгенерированная счетчиком SELBSTGENERIERTE COUNTER INFORMATION
SELF GENERATED COUNTER INFORMATION ENTREES COMPTEUR AUTOMATIQUES SELF GENERATED COUNTER INFORMATION INFORMACION CONTADOR AUTO GENERADA Informação CONTADOR Auto Gerada Информация, сгенерированная счетчиком SELBSTGENERIERTE COUNTER INFORMATION
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
Self Counter Reference Référence interne du compteur Self Counter Reference Referencia Contador auto Referência Contador Automática Собственная ссылка Противодействие Self Counter Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Link Lien Link Vínculo Vínculo Связь Link
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Number Numéro Number Número Número Номер Number
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Counter Type Type du Compteur Counter Type Tipo de Contador Tipo de Contador Противодействие Тип Counter Type
Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Standard: Validation (ms);Invalidité (ms);Cumul (mn) Energy: Facteur d'echelle;Periode de transmission (mn) Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn) Estándar: Válidación (ms);Inválidación (ms);Cumulación (mn) Energía: Factor de posicionamiento;Periode de la transmisión (mn) Padrão: Validação (ms);Invalidação (ms);Cumulação (mn) Energia: Fator de escala;Periode da transmissão (mn) Стандарт: Проверка (мс);Invalidity (ms);Cumul (mn) Энергия: Scale factor;Период передачи (мс) Standard: Validation (ms);Invalidity (ms);Cumul (mn) Energy: Scale factor;Transmission period (mn)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Integrate MV Intègre la MV Integrate MV Integrate MV Integrate MV Integrate MV Integrate MV
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Automation Origin (if any) Automatisme d'origine (si existant) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Counter Profiles Profils Compteurs Counter Profiles Perfiles de Contador Perfis de Contador Профили счетчика Counter Profiles
System Counter Profiles Profils Compteurs systèmes System Counter Profiles Perfiles de systema de Contador Perfis de Systema de Contador Профили системного счетчика System Counter Profiles
Function Name Nom de la fonction Function Name Nombre de función Nome da Função Функция Name Function Name
SCE Name (13 char) Nom dans le SCE (13 char) SCE Name (13 char) Nombre SCE (13 caract) Nome SCE (13 caract) Имя SCE (13 символов) SCE Name (13 char)
Counter General Parameters Paramètres généraux du Compteur Counter General Parameters Parámetros generales Contador Parâmetros Geração Contador Основные параметры Борьба Counter General Parameters
Energy equivalent to a pulse Energie équivalente à un pulse Energy equivalent to a pulse Equivalente en energía a un pulso Energia equivalente a um pulso Energy equivalent to a pulse Energy equivalent to a pulse
Computation Calculé Computation Cómputación Computação Вычисление Computation
SBMC dependant Dépendance SBMC SBMC dependant SBMC dependiente SBMC dependente SBMC иждивенца SBMC unterhaltsberechtigte
Graphical Default Format Format graphique par défaut Graphical Default Format Formato gráfico del defecto Formato gráfico do defeito Стандартный графический формат Graphical Default Format
Associated Alarm Parameters Paramètres d'alarme associés à la MV Associated Alarm Parameters Associated Alarm Parameters Associated aoarm Parameters Параметры тревоги Associated Alarm Parameters
Generation Condition Condition de la Génération Generation Condition Condición de generación Condição de Geração Основное условие Generation Condition
Audible Alarm Alarme audible Audible Alarm Alarma audible Alarme Auditível Звуковая тревога Audible Alarm
Clearing Mode Mode d'effacement Clearing Mode Modo Clearing Modo de Limpeza Режим очистки Clearing Mode
Alarm appearance delay (0-120 s) Retard d'apparition de l'alarme (0-120 s) Alarm appearance delay (0-120 s) Retardo de aparición de Alarma (0-120 s) Retardo de aparição de Alarme (0-120 s) Задержка появления тревоги (0-120 с) Alarm appearance delay (0-120 s)
Counter Processing Parameters Paramètres de traitement du Compteur Counter Processing Parameters Parámetros de procesamiento Contador Parâmetros de Processamento Contador Парметры обработки Борьба Counter Processing Parameters
Valid state label Libellé de l'état valide Valid state label Etiqueta de estado válido Etiqueta de estado válido Метка статуса Valid Valid state label
SelfCheckFault state label Libellé de l'état d'auto vérification du défaut SelfCheckFault state label Etiqueta de estado FallaAutoChequeo Etiqueta de estado FalhaAutoCheque Метка статуса SelfCheckFault SelfCheckFault state label
Unknown state label Libellé de l'état inconnu Unknown state label Etiqueta de estado desconocido Etiqueta de estado Desconhecido Метка статуса Unknown Unknown state label
Forced state label Libellé de l'état forcé Forced state label Etiqueta de estado forzado Etiqueta de estado Forçado Метка статуса Forced Forced state label
OverRange state label Libellé de l'état au-dessus de l'échelle OverRange state label Etiqueta de estado fuera de rango Etiqueta de estado fora de Range Метка статуса OverRange OverRange state label
Undefined state label Libellé de l'état indéfini Undefined state label Etiqueta de estado Indefinido Etiqueta de estado Indefinido Метка статуса Undefined Undefined state label
Treatment on Valid state Traitement sur l'état valide Treatment on Valid state Manipulación en estado válido Manipulação em estado válido Обработка статуса Valid Treatment on Valid state
Treatment on SelfCheckFault state Traitement sur l'état d'auto vérification du défaut Treatment on SelfCheckFault state Manipulación en estado FallaAutoChequeo Manipulação em estado FalhaAutoCheque Обработка статуса SelfCheckFault Treatment on SelfCheckFault state
Treatment on Unknown state Traitement sur l'état inconnu Treatment on Unknown state Manipulación en estado Desconocido Manipulação em estado Desconhecido Обрабока статуса Unknown Treatment on Unknown state
Treatment on Forced state Traitement sur l'état forcé Treatment on Forced state Manipulación en estado Forzado Manipulação em estado Forçado Обработка статуса Forced Treatment on Forced state
Treatment on OverRange state Traitement sur l'état au-dessus de l'échelle Treatment on OverRange state Manipulación en estado fuera de rango Manipulação em estado fora de Range Обработка статуса OverRange Treatment on OverRange state
Treatment on Undefined state Traitement sur l'état indéfini Treatment on Undefined state Manipulación en estado Indefinido Manipulação em estado Indefinido Обработка статуса Undefined Treatment on Undefined state
Treatment on Forcing state Traitement sur l'état de forçage Treatment on Forcing state Manipulación en estado Forzando Manipulação em estado Forzando Обработка статуса Forcing Treatment on Forcing state
Treatment on Substitution state Traitement sur l'état de substitution Treatment on Substitution state Manipulación en estado por sustitución Manipulação em estado por Substituição Обработка статуса Substitution Treatment on Substitution state
Treatment on Suppression state Traitement sur l'état de suppression Treatment on Suppression state Manipulación en estado por supresión Manipulação em estado por Supressão Обработка статуса Suppression Treatment on Suppression state
Alarm and Gravity on Valid state Gravité d'alarme sur l'état valide Alarm and Gravity on Valid state Alarma y gravedad en estado valido Alarme e gravidade em estado vaoido Тревога и важность статуса Valid Alarm and Gravity on Valid state
Alarm and Gravity on SelfCheckFault state Gravité d'alarme sur l'état d'auto vérification du défaut Alarm and Gravity on SelfCheckFault state Alarma y gravedad en estado FallaAutoChequeo Alarme e gravidade em estado FalhaAutoCheque Тревога и важность статуса SelfCheckFault Alarm and Gravity on SelfCheckFault state
Alarm and Gravity on Unknown state Gravité d'alarme sur l'état inconnu Alarm and Gravity on Unknown state Alarma y gravedad en estado desconocido Alarme e gravidade em estado Desconhecido Тревога и важность статуса Unknown Alarm and Gravity on Unknown state
Alarm and Gravity on Forced state Gravité d'alarme sur l'état forcé Alarm and Gravity on Forced state Alarma y gravedad en estado forzado Alarme e gravidade em estado Forçado Тревога и важность статуса Forced Alarm and Gravity on Forced state
Alarm and Gravity on OverRange state Gravité d'alarme sur l'état au-dessus de l'échelle Alarm and Gravity on OverRange state Alarma y gravedad en estado fuera de rango Alarme e gravidade em estado fora de Range Тревога и важность статуса OverRange Alarm and Gravity on OverRange state
Alarm and Gravity on Undefined state Gravité d'alarme sur l'état indéfini Alarm and Gravity on Undefined state Alarma y gravedad en estado Indefinido Alarme e gravidade em estado Indefinido Тревога и важность статуса Undefined Alarm and Gravity on Undefined state
Counter Printing Parameters Paramètres d'impression du Compteur Counter Printing Parameters Parámetros de impresión Contador Parâmetros de Impressão Contador Параметры печати Борьба Counter Printing Parameters
Printed on Sequence Of Events SOE 1 : Imprimer sur l'imprimante Fil de l'eau 1 : Printed on Sequence Of Events SOE 1 : Impreso en SOE 1 : Impresso em SOE 1 : Вывод на SOE 1 : Printed on Sequence Of Events SOE 1 :
Printed on Sequence Of Events SOE 2 : Imprimer sur l'imprimante Fil de l'eau 2 : Printed on Sequence Of Events SOE 2 : Impreso en SOE 2 : Impresso em SOE 1 : Вывод на SOE 2 : Printed on Sequence Of Events SOE 2 :
Printed on Logbook LB 1 : Imprimer sur l'imprimante Journal de Bord 1 : Printed on Logbook LB 1 : Impreso en LB 1 : Impresso em LB 1 : Вывод на LB 1 : Printed on Logbook LB 1 :
Printed on Logbook LB 2 : Imprimer sur l'imprimante Journal de Bord 2 : Printed on Logbook LB 2 : Impreso en LB 2 : Impresso em LB 2 : Вывод на LB 2 : Printed on Logbook LB 2 :
ANALOG OUTPUT BOARD AOU20x Carte de sorties analogiques AOU20x ANALOG OUTPUT BOARD AOU20x TARJETAS DE SALIDAS ANALOGICAS AOU20x Etiquetas de Saídas Analógicas AOU20x ПЛАТЫ AOU20x ANALOGE AUSGANGSKARTE AOU20x
Analog Output Board Number Numéro de la carte de sorties analogiques Analog Output Board Number Número de tarjeta de salidas analógicas Número de Etiqueta de Saídas Analógicas Номер платы AO Analogausgangskarten Nummer
Analog Output Board Slot Position de la carte de sortie analogiques Analog Output Board Slot Slot de Tarjeta de salidas analógicas Slot do Cartão de Saídas Analógicas Слот платы AO Analogausgangskarten Steckplatz
Analog Output Extension Rack Number Numéro rack d'extension de la carte de sorties analogiques Analog Output Extension Rack Number Tarjeta de salidas analógicas Extensión Rack Número Etiqueta de Saídas Analógicas Extensão Rack Número продлению стойки Количество AO Analogausgangskarten Extension Rack Nummer
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
AO Reference Référence AO AO Reference Referencia AO Referência AO Ссылка AO AO Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Slot Position Slot Slot Slot Слот Slot
Channel Voie Channel Canal Canal Канал Channel
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Corresponding Minimal Value Correspond à la valeur minimum Corresponding Minimal Value Valor correspondiente al mínimo Valor correspondente ao Mínimo Значение соответствующее минимуму Corresponding Minimal Value
Corresponding Maximal Value Correspond à la valeur maximum Corresponding Maximal Value Valor correspondiente al Máximo Valor correspondente ao Máximo Значение соответствующее максимуму Corresponding Maximal Value
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
SELF GENERATED SETPOINT INFORMATION SORTIES SETPOINT AUTOMATIQUES SELF GENERATED SETPOINT INFORMATION INFORMACION SETPOINT AUTO GENERADA Informação SETPOINT Auto Gerada Информация, сгенерированная SetPoint SELBSTGENERIERTE SETPOINT INFORMATION
SELF GENERATED SETPOINT INFORMATION SORTIES SETPOINT AUTOMATIQUES SELF GENERATED SETPOINT INFORMATION INFORMACION SETPOINT AUTO GENERADA Informação SETPOINT Auto Gerada Информация, сгенерированная SetPoint SELBSTGENERIERTE SETPOINT INFORMATION
SELF GENERATED SETPOINT INFORMATION SORTIES SETPOINT AUTOMATIQUES SELF GENERATED SETPOINT INFORMATION INFORMACION SETPOINT AUTO GENERADA Informação SETPOINT Auto Gerada Информация, сгенерированная SetPoint SELBSTGENERIERTE SETPOINT INFORMATION
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
SetPoint Reference Référence SetPoint SetPoint Reference Referencia SetPoint Referência SetPoint Ссылка SetPoint SetPoint Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Display Affichage Local Local Display Despliegue Local Display Local Локальный дисплей Local Display
HMI HMI HMI IHM IHM HMI HMI
Special Spécial Special Especial Especial Специальный Special
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Number Numéro Number Número Número Номер Number
Function Fonction Function Función Função Функция Function
Unit Unité Unit Unidad Unidade Плата Unit
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Corresponding Minimal Value Correspond à la valeur minimum Corresponding Minimal Value Valor correspondiente al mínimo Valor correspondente ao Mínimo Значение соответствующее минимуму Corresponding Minimal Value
Corresponding Maximal Value Correspond à la valeur maximum Corresponding Maximal Value Valor correspondiente al Máximo Valor correspondente ao Máximo Значение соответствующее максимуму Corresponding Maximal Value
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Display Affichage LCD LCD Display Pantalla LCD Vista LCD LCD Дисплей LCD Display
HMI Display Affichage HMI HMI Display Pantalla IHM Vista IHM HMI Дисплей HMI Display
Trend Viewer Archivé Trend Viewer Archivado Arquivado Просмотр кривых Trend Viewer
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Automation Origin (if any) Automatisme d'origine (si existant) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any) Automation Origin (if any)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
SHEET : IEC61850 Model SHEET : Modèles IEC61850 SHEET : IEC61850 Model SHEET : Modelo IEC61850 SHEET : Modo IEC61850 SHEET : Модель IEC61850 SHEET : IEC61850 Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA IEC 61850 DEBUT SCADA IEC 61850 BEGIN SCADA IEC 61850 COMIENZA SCADA IEC 61850 INÍCIO SCADA IEC 61850 НАЧАЛО ОПИСАНИЯ SCADA IEC 61850 BEGIN SCADA IEC 61850
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
TCP/IP Address Adresse TCP/IP TCP/IP Address TCP/IP Dirección TCP/IP Endereço TCP/IP Адрес TCP/IP Address
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
DSP210 BOARD Carte DSP210 DSP210 BOARD TARJETAS DSP210 Placas DSP210 ПЛАТЫ DSP210 KARTE DSP210
DSP210 Board Number Numéro de la carte DSP210 DSP210 Board Number Número de tarjeta DSP210 Número de Etiqueta de DSP210 Номер платы DSP210 DSP210 karte Nummer
DSP210 Board Slot Position de la carte DSP210 DSP210 Board Slot Slot de trajeta DSP210 Slot de trajeta de DSP210 Слот платы DSP210 DSP210 karte Steckplatz
DSP210 Extension Rack Number Numéro rack d'extension de la carte DSP210 DSP210 Extension Rack Number Tarjeta DSP210 Extensión Rack Número Etiqueta de DSP210 Extensão Rack Número продлению стойки Количество DSP210 DSP210 Extension Rack Nummer
Iss. Rév. Iss. Rev. Rev. Вер. Iss.
Customer Ref Réf. Client Customer Ref Ref Cliente Ref Cliente Ссылка заказчика Kundenreferenz
DO Reference Référence DO DO Reference Referencia DO Referência DO Ссылка DO DO Reference
Electrical Data Données électriques Electrical Data Datos Eléctricos Dados Elétricos Данные электрической части Elektrische Datumn
Description Description Description Descripción Descrição Описание Beschreibung
Labels Libellés Labels Etiquetas Etiquetas Метки Labels
Scada Interface Interface Scada Scada Interface Interfaz Scada Interface Scada Scada интерфейс FW Interface
Local Control Contrôle Local Local Control Control Local Controle Local местного контроля Local Control
HMI HMI HMI IHM IHM HMI HMI
DI/DO Link Lien DI/DO DI/DO Link DI/DO Vínculo DI/DO Vínculo DI/DO связи DI/DO Link
Automation Automatisme Automation Automatización Automação Автоматика Automation
Template Modèle Template Plantilla Panilha Образец Template
Conf. Mng. Conf. Mng. Conf. Mng. Admin. Config. Admin. Config. Управление конфигурацией Conf. Mng.
IEC Interface Interface IEC IEC Interface Interfaz IEC Interface IEC IEC интерфейс IEC Interface
Issue Révision Issue Revisión Revisão Версия Version
Panel Number Numéro d'armoire Panel Number Número de panel Número do Painel Номер панели Panel Number
Tag Number Numéro d'étiquette Tag Number Número de etiquetado Número do Tag Номер тега Tag Number
Slot Position Slot Slot Slot Слот Slot
Channel Voie Channel Canal Canal Канал Channel
Function Fonction Function Función Função Функция Function
Type (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Simple/DPC=Double/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch) Tipo (SPC=Sencilla/DPC=Dual/DS=Dual Switch) Tipo (SPC=Simples/DPC=Duplo/DS=Dual Switch) Тип (SPC=Single/DPC=Dual/DS=Dual Switch) Type (SPC=Single/DPC=Dual/DS=Dual Switch)
Voltage Level Short Name (16 char) Niveau de tension Nom court (16 car) Voltage Level Short Name (16 char) Nivel de voltaje Nombre Corto (16 caract) Nivel de Tensão Nome Curto (16 caract) Уровень напряжения Краткое имя (16 символов) Spannungsebene Short Name (16 char)
Bay Short Name (16 char) Tranche Nom court (16 car) Bay Short Name (16 char) Bahía Nombre Corto (16 caract) Painel Nome Curto (16 caract) Имя ячейки Краткое имя (16 символов) FELD Short Name (16 char)
Module Short Name (16 char) Module Nom court (16 car) Module Short Name (16 char) Módulo Nombre Corto (16 caract) Módulo Nome Curto (16 caract) Имя Краткое имя (16 символов) Modul Short Name (16 char)
Long name (35 char) Nom long (35 car) Long name (35 char) Nombre largo (35 caract) Nome Longo (35 caract) Полное имя (35 символов) Long name (35 char)
Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Simple : Texte à l'état électrique = 1 Double : Texte à l'état électrique = 10 (16 car) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char) Sencilla : Texto en estado eléctrico = 1 Dual : Texto en estado eléctrico = 10 (16 caract) Simples: Texto em estado Elétrico = 1 Duplo : Texto em estado Elétrico = 10 (16 caract) Одиночный : Обозначение электрического состояния = 1 Двойной : Обозначение электрического состояния = 10 (16 символов) Single : Text at electrical state = 1 Dual : Text at electrical state = 10 (16 char)
Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Simple : Texte à l'état électrique = 0 Double : Texte à l'état électrique =01 (16 car) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char) Sencilla : Texto en estado eléctrico = 0 Dual : Texto en estado eléctrico = 01 (16 caract) Simples: Texto em estado Elétrico = 0 Duplo : Texto em estado Elétrico = 01 (16 caract) Одиночный : Обозначение электрического состояния = 0 Двойной : Обозначение электрического состояния = 01 (16 символов) Single : Text at electrical state = 0 Dual : Text at electrical state = 01 (16 char)
Short Name (16 char) Nom court (16 car) Short Name (16 char) Nombre Corto (16 caract) Nome Curto (16 caract) Краткое имя (16 символов) Short Name (16 char)
SCADA 1 Address SCADA 1 Adresse SCADA 1 Address SCADA 1 Dirección SCADA 1 Endereço SCADA 1 Адрес SCADA 1 Address
SCADA1 Data type SCADA 1 Type de donnée SCADA1 Data type SCADA1 Tipo de dato SCADA1 Tipo de Dado SCADA1 Тип данных SCADA1 Data type
SCADA 2 Address SCADA 2 Adresse SCADA 2 Address SCADA 2 Dirección SCADA 2 Endereço SCADA 2 Адрес SCADA 2 Address
SCADA2 Data type SCADA 2 Type de donnée SCADA2 Data type SCADA2 Tipo de dato SCADA2 Tipo de Dado SCADA2 Тип данных SCADA2 Data type
SCADA 3 Address SCADA 3 Adresse SCADA 3 Address SCADA 3 Dirección SCADA 3 Endereço SCADA 3 Адрес SCADA 3 Address
SCADA3 Data type SCADA 3 Type de donnée SCADA3 Data type SCADA3 Tipo de dato SCADA3 Tipo de Dado SCADA3 Тип данных SCADA3 Data type
SCADA 4 Address SCADA 4 Adresse SCADA 4 Address SCADA 4 Dirección SCADA 4 Endereço SCADA 4 Адрес SCADA 4 Address
SCADA4 Data type SCADA 4 Type de donnée SCADA4 Data type SCADA4 Tipo de dato SCADA4 Tipo de Dado SCADA4 Тип данных SCADA4 Data type
LCD Control Contrôle LCD LCD Control Control LCD Ordem desde LCD Управление LCD LCD Control
HMI Control Contrôle HMI HMI Control Control IHM Ordem desde IHM Управление HMI HMI Control
Has a xPS Feedback A un retour de position xPS Has a xPS Feedback Contiene retroalimentación xPS Possui FeedBack xPS имеет xPS отзывы Has a xPS Feedback
Is activated by xPS Est activé par xPS Is activated by xPS Es activado por xPS É ativado por xPS Активируется с помощью xPS Is activated by xPS
Used by ISaGRAF Utilisé par ISaGRAF Used by ISaGRAF ISaGRAF Nome ISaGRAF (8 car) Используется ISaGRAFом Used by ISaGRAF
Relay Relais Relay Relé Relé Реле Relay
Bay Name (in SCE Template) or Bay Type Nom de la Tranche (dans le modèle du SCE) ou Type de la Tranche Bay Name (in SCE Template) or Bay Type Nombre de bahía (en plantilla SCE) o tipo de bahía Nome do Painel (em Panilha SCE) ou tipo do Painel Имя ячейки (в SCE шаблоне) или ячейки типа Bay Name (in SCE Template) or Bay Type
Module Name (in SCE Template) or Module Type Nom du Module (dans le modèle du SCE) ou Type du Module Module Name (in SCE Template) or Module Type Nombre de módulo (en plantilla SCE) o tipo de módulo Nome do Módulo (em Panilha SCE) ou tipo do Módulo Имя модуля (в SCE шаблоне) или модуля типа Module Name (in SCE Template) or Module Type
Datapoint Name (in SCE Template) or Datapoint Type Nom du Point de Donnée (dans le modèle du SCE) ou Type du Point de Donnée Datapoint Name (in SCE Template) or Datapoint Type Nombre del dato (en plantilla SCE) o tipo del dato Nome do Dado (em Panilha SCE) ou tipo do Dado Имя точки данных (в SCE шаблоне) или точки данных типа Datapoint Name (in SCE Template) or Datapoint Type
Process Utiliser Process Proceso Processo Процесс Process
IEC Address Part 1 (IEC: LD;LN) Addresse IEC Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN) IEC Dirección Part 1 (IEC: LD;LN) IEC Endereço Part 1 (IEC: LD;LN) IEC Адрес Part 1 (IEC: LD;LN) IEC Address Part 1 (IEC: LD;LN)
IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) Addresse IEC Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Dirección Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Endereço Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Адрес Part 2 (IEC: FC;Data Object;DataAttribute;CDC) IEC Address Part 2 (IEC: FC;Data Object;DataAttribute;CDC)
Comments Commentaires Comments Comentarios Comentários Комментарии Comments
Automations links (separator ";") (add "<" if output) Liens d'Automatismes (séparateur ";") (ajouter "<" si c'est une sortie) Automations links (separator ";") (add "<" if output) conexión Automatión (separador ";") (añadir "<" si la producción) Automatião conexão (separador ";") (acrescentar "<" se a produção) связи Автоматизация (разделитель ";") (добавить "<" если выход) Automations links (separator ";") (add "<" if output)
SHEET : List of Automations SHEET : Liste des Automatismes SHEET : List of Automations SHEET : Lista de Automations SHEET : Lista de Automations SHEET : Список Automations SHEET : List of Automations
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
AUTOMATIONS INFORMATION INFORMATIONS SUR LES AUTOMATISMES AUTOMATIONS INFORMATION INFORMACION DE AUTOMATIONS Informação de AUTOMATIONS ИНФОРМАЦИЯ ПО AUTOMATIONS AUTOMATIONS INFORMATION
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Number Numéro Number Número Número Номер Number
Automation Name Nom de l'Automatisme Automation Name Nombre de Automation Nome do Automation Имя Automation Automation Name
Automation Type Type d'Automatisme Automation Type Tipo de Automation Tipo de Automation Тип Automation Automation Type
Computer Calculateur Computer Computador Computador Компьютер Computer
Redundant Computer Calculateur Redondant Redundant Computer Computador Redundante Computador Redundante Резервный компьютер Redundant Computer
Issue Révision Issue Revisión Revisão Версия Version
Template Modèle Template Plantilla Panilha Образец Template
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : Equipments IEC Links SHEET : Liste des Liens IEC SHEET : Equipments IEC Links SHEET : Enlaces Equipos IEC SHEET : Ligações de Equipamentos IEC SHEET : аппаратура ссылки IEC SHEET : Equipments IEC Links
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
IEC LINKS INFORMATION INFORMATIONS SUR LES LIENS IEC IEC LINKS INFORMATION IEC LINKS INFORMATION IEC LINKS INFORMATION ИНФОРМАЦИЯ ПО IEC LINKS IEC LINKS INFORMATION
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Clients \ Servers Clients \ Servers Clients \ Servers Clients \ Servers Clients \ Servers Clients \ Servers Clients \ Servers
Issue Révision Issue Revisión Revisão Версия Version
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
Substation 1 Sous-station 1 Substation 1 Subestación 1 Substação 1 подстанции 1 Stations 1
Substation 2 Sous-station 2 Substation 2 Subestación 2 Substação 2 подстанции 2 Stations 2
Substation 3 Sous-station 3 Substation 3 Subestación 3 Substação 3 подстанции 3 Stations 3
Substation 4 Sous-station 4 Substation 4 Subestación 4 Substação 4 подстанции 4 Stations 4
Substation 5 Sous-station 5 Substation 5 Subestación 5 Substação 5 подстанции 5 Stations 5
Substation 6 Sous-station 6 Substation 6 Subestación 6 Substação 6 подстанции 6 Stations 6
Substation 7 Sous-station 7 Substation 7 Subestación 7 Substação 7 подстанции 7 Stations 7
Substation 8 Sous-station 8 Substation 8 Subestación 8 Substação 8 подстанции 8 Stations 8
Substation 9 Sous-station 9 Substation 9 Subestación 9 Substação 9 подстанции 9 Stations 9
Substation 10 Sous-station 10 Substation 10 Subestación 10 Substação 10 подстанции 10 Stations 10
Substation 11 Sous-station 11 Substation 11 Subestación 11 Substação 11 подстанции 11 Stations 11
Substation 12 Sous-station 12 Substation 12 Subestación 12 Substação 12 подстанции 12 Stations 12
Substation 13 Sous-station 13 Substation 13 Subestación 13 Substação 13 подстанции 13 Stations 13
Substation 14 Sous-station 14 Substation 14 Subestación 14 Substação 14 подстанции 14 Stations 14
Substation 15 Sous-station 15 Substation 15 Subestación 15 Substação 15 подстанции 15 Stations 15
Substation 16 Sous-station 16 Substation 16 Subestación 16 Substação 16 подстанции 16 Stations 16
Substation 17 Sous-station 17 Substation 17 Subestación 17 Substação 17 подстанции 17 Stations 17
Substation 18 Sous-station 18 Substation 18 Subestación 18 Substação 18 подстанции 18 Stations 18
Substation 19 Sous-station 19 Substation 19 Subestación 19 Substação 19 подстанции 19 Stations 19
Substation 20 Sous-station 20 Substation 20 Subestación 20 Substação 20 подстанции 20 Stations 20
Substation 21 Sous-station 21 Substation 21 Subestación 21 Substação 21 подстанции 21 Stations 21
Substation 22 Sous-station 22 Substation 22 Subestación 22 Substação 22 подстанции 22 Stations 22
Substation 23 Sous-station 23 Substation 23 Subestación 23 Substação 23 подстанции 23 Stations 23
Substation 24 Sous-station 24 Substation 24 Subestación 24 Substação 24 подстанции 24 Stations 24
Substation 25 Sous-station 25 Substation 25 Subestación 25 Substação 25 подстанции 25 Stations 25
Substation 26 Sous-station 26 Substation 26 Subestación 26 Substação 26 подстанции 26 Stations 26
Substation 27 Sous-station 27 Substation 27 Subestación 27 Substação 27 подстанции 27 Stations 27
Substation 28 Sous-station 28 Substation 28 Subestación 28 Substação 28 подстанции 28 Stations 28
Substation 29 Sous-station 29 Substation 29 Subestación 29 Substação 29 подстанции 29 Stations 29
Substation 30 Sous-station 30 Substation 30 Subestación 30 Substação 30 подстанции 30 Stations 30
Substation 31 Sous-station 31 Substation 31 Subestación 31 Substação 31 подстанции 31 Stations 31
Substation 32 Sous-station 32 Substation 32 Subestación 32 Substação 32 подстанции 32 Stations 32
Substation 33 Sous-station 33 Substation 33 Subestación 33 Substação 33 подстанции 33 Stations 33
Substation 34 Sous-station 34 Substation 34 Subestación 34 Substação 34 подстанции 34 Stations 34
Substation 35 Sous-station 35 Substation 35 Subestación 35 Substação 35 подстанции 35 Stations 35
Substation 36 Sous-station 36 Substation 36 Subestación 36 Substação 36 подстанции 36 Stations 36
Substation 37 Sous-station 37 Substation 37 Subestación 37 Substação 37 подстанции 37 Stations 37
Substation 38 Sous-station 38 Substation 38 Subestación 38 Substação 38 подстанции 38 Stations 38
Substation 39 Sous-station 39 Substation 39 Subestación 39 Substação 39 подстанции 39 Stations 39
Substation 40 Sous-station 40 Substation 40 Subestación 40 Substação 40 подстанции 40 Stations 40
SHEET : SAS Model SHEET : Modèles SAS SHEET : SAS Model SHEET : Modelo SAS SHEET : Modo SAS SHEET : Модель SAS SHEET : SAS Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA SAS DEBUT SCADA SAS BEGIN SCADA SAS COMIENZA SCADA SAS INÍCIO SCADA SAS НАЧАЛО ОПИСАНИЯ SCADA SAS BEGIN SCADA SAS
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Main communication channel Voie de communication principale Main communication channel Canal de comunicación principal Canal de Comunicação Principal Основной канал связи Main communication channel
Auxiliary Communication channel Voie de communication auxiliaire Auxiliary Communication channel Canal de comunciación auxiliar Canal de Comunicação auxiliar Запасной канал связи Auxiliary Communication channel
Baud rate (bit/s) Vitesse de transmission (bit/s) Baud rate (bit/s) Baudios (bit/s) Baud Rate (bit/s) Скорость в бодах (бит/с) Baud rate (bit/s)
Common address of ASDU Adresse commune de l'ASDU Common address of ASDU Dirección común ASDU Endereço comum ASDU Общий адрес ASDU Common address of ASDU
Common address of ASDU Length Longueur de l'adresse commune de l'ASDU Common address of ASDU Length Longitud de la dirección común ASDU Tamanho do Endereço comum ASDU Длина общего адреса ASDU Common address of ASDU Length
Object structure Structure d'objet Object structure Estructura del objeto Estrutura do objeto Структура объекта Object structure
Frame max length Longueur maximale de la vue Frame max length Longitud máx de la trama Tamanho máx do frame Максимальная длина кадра Frame max length
Measurement periodic cycle Cycle Périodique de Mesure Measurement periodic cycle Ciclo de medición periódico Ciclo periódico de Medição Периодический цикл измерений Measurement periodic cycle
Binary Time Size Taille de Temps binaire Binary Time Size Tamaño de tiempo binario Tamanho Binário do Tempo Размер двоичной кодировки времени Binary Time Size
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Send in General Interrogation Envoyé lors de l'Interrogation Générale Send in General Interrogation Enviar en general Interrogatorio Envie em Geral Interrogation Отправить в Генеральной Допрос Senden in den Allgemeinen Interrogation
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Send in General Interrogation Envoyé lors de l'Interrogation Générale Send in General Interrogation Enviar en general Interrogatorio Envie em Geral Interrogation Отправить в Генеральной Допрос Senden in den Allgemeinen Interrogation
MPS Data Type MPS Donnée de Type MPS Data Type MPS Datos tipo MPS Dados tipo MPS Тип данных MPS Data Type
Send in General Interrogation Envoyé lors de l'Interrogation Générale Send in General Interrogation Enviar en general Interrogatorio Envie em Geral Interrogation Отправить в Генеральной Допрос Senden in den Allgemeinen Interrogation
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Format Format Format Formato Formato Формат Format
Cycle Type Type de Cycle Cycle Type Tipo de ciclo Tipo de Ciclo Тип цикла Cycle Type
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : CDC Type II Model SHEET : Modèles CDC Type II SHEET : CDC Type II Model SHEET : Modelo CDC Type II SHEET : Modo CDC Type II SHEET : Модель CDC Type II SHEET : CDC Type II Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA CDC TYPE II DEBUT SCADA CDC TYPE II BEGIN SCADA CDC TYPE II COMIENZA SCADA CDC TYPE II INÍCIO SCADA CDC TYPE II НАЧАЛО ОПИСАНИЯ SCADA CDC TYPE II BEGIN SCADA CDC TYPE II
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Main communication channel Voie de communication principale Main communication channel Canal de comunicación principal Canal de Comunicação Principal Основной канал связи Main communication channel
Auxiliary Communication channel Voie de communication auxiliaire Auxiliary Communication channel Canal de comunciación auxiliar Canal de Comunicação auxiliar Запасной канал связи Auxiliary Communication channel
Baud rate (bit/s) Vitesse de transmission (bit/s) Baud rate (bit/s) Baudios (bit/s) Baud Rate (bit/s) Скорость в бодах (бит/с) Baud rate (bit/s)
Connection timeout (T0) Expiration de la Connexion (T0) Connection timeout (T0) Connection tiempo fuera (T0) Falha de Conexão (T0) Задержка соединения (T0) Connection timeout (T0)
Minimal int Value for Measurement Valeur minimale de mesure Minimal int Value for Measurement Mínimo valor de medición Minimal valor inteiro para Medição Минимальное значение за целое измерение Minimal-Integer-Wert für die Messung
Maximal int Value for Measurement Valeur maximale de mesure Maximal int Value for Measurement Máximo valor de medición Maximal valor inteiro para Medição Максимальное целое значение для измерения Maximale Integer-Wert für die Messung
Int Value for Invalid Measurement Valeur de mesure invalide Int Value for Invalid Measurement Valor no válido para la medición Valor inválido para a medição Стоимость за недействительные измерения Integer-Wert für ungültig Messung
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Sending mode Mode de transmission Sending mode Modo de transmisión Modo de Envio Коробка передач в режиме Übertragungsmodus
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Sending mode Mode de transmission Sending mode Modo de transmisión Modo de Envio Коробка передач в режиме Übertragungsmodus
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : GI74 Model SHEET : Modèles GI74 SHEET : GI74 Model SHEET : Modelo GI74 SHEET : Modo GI74 SHEET : Модель GI74 SHEET : GI74 Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA GI74 DEBUT SCADA GI74 BEGIN SCADA GI74 COMIENZA SCADA GI74 INÍCIO SCADA GI74 НАЧАЛО ОПИСАНИЯ SCADA GI74 BEGIN SCADA GI74
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
TCP/IP Address Adresse TCP/IP TCP/IP Address TCP/IP Dirección TCP/IP Endereço TCP/IP Адрес TCP/IP Address
Network Name NOM DU RESEAU Network Name Nombre de red Nome da rede Сетевое Имя Netzwerk Name
Port 1 : TE address Port 1 : Adresse TE Port 1 : TE address Puerto 1: TE dirección Porto 1: TE endereço Порт 1: TE-адрес Port 1: TE-Adresse
Port 1 : TE block size Port 1 : Taille de bloc TE Port 1 : TE block size Puerto 1: TE tamaño de bloque Porto 1: TE bloco tamanho Порт 1: TE размер блока Port 1: TE Blockgröße
Port 1 : Control Timeout in ms Port 1 : Expiration du contrôle en ms Port 1 : Control Timeout in ms Puerto 1: Control de Tiempo en ms Porto 1: Controlo Timeout em ms Порт 1: Контроль тайм-аута в мс Port 1: Control Timeout in ms
Port 1 : HK control function Port 1 : Fonction de contrôle HK Port 1 : HK control function Puerto 1: función de control de HK Porto 1: HK função de controlo Порт 1: HK функции контроля Port 1 : HK control function
Port 1 : HK control block Port 1 : Bloc de contrôle HK Port 1 : HK control block Puerto 1: bloque de control de HK Porto 1: HK bloco de controlo Порт 1: HK блок управления Port 1 : HK control block
Port 1 : HK control word Port 1 : Mot de contrôle HK Port 1 : HK control word Puerto 1: HK palabra de control Porto 1: HK controlo palavra Порт 1: HK управляющее слово Port 1 : HK control word
Port 2 : TE address Port 2 : Adresse TE Port 2 : TE address Puerto 2: TE dirección Porto 2: TE endereço Порт 2: TE-адрес Port 2: TE-Adresse
Port 2 : TE block size Port 2 : Taille de bloc TE Port 2 : TE block size Puerto 2: TE tamaño de bloque Porto 2: TE bloco tamanho Порт 2: TE размер блока Port 2: TE Blockgröße
Port 2 : Control Timeout in ms Port 2 : Expiration du contrôle en ms Port 2 : Control Timeout in ms Puerto 2: Control de Tiempo en ms Porto 2: Controlo Timeout em ms Порт 2: Контроль тайм-аута в мс Port 2: Control Timeout in ms
Port 2 : HK control function Port 2 : Fonction de contrôle HK Port 2 : HK control function Puerto 2: función de control de HK Porto 2: HK função de controlo Порт 2: HK функции контроля Port 2 : HK control function
Port 2 : HK control block Port 2 : Bloc de contrôle HK Port 2 : HK control block Puerto 2: bloque de control de HK Porto 2: HK bloco de controlo Порт 2: HK блок управления Port 2 : HK control block
Port 2 : HK control word Port 2 : Mot de contrôle HK Port 2 : HK control word Puerto 2: HK palabra de control Porto 2: HK controlo palavra Порт 2: HK управляющее слово Port 2 : HK control word
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Type propagation change Type de changement de propagation Type propagation change Tipo de cambio propagación Tipo de propagação mudança Вид распространения изменений Type propagation change
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
Inverted state Etat Inversé Inverted state Estado invertido Estado invertido Инвертированное состояние Inverted state
Type propagation change Type de changement de propagation Type propagation change Tipo de cambio propagación Tipo de propagação mudança Вид распространения изменений Type propagation change
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
Port for feedback Port de retour Port for feedback Puerto de retroalimentación Porto de retorno Порт для обратной связи Port for feedback
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
Port for feedback Port de retour Port for feedback Puerto de retroalimentación Porto de retorno Порт для обратной связи Port for feedback
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Type measurement Type de la mesure Type measurement Tipo de medición Tipo de medição Тип измерений Type measurement
Type propagation change Type de changement de propagation Type propagation change Tipo de cambio propagación Tipo de propagação mudança Вид распространения изменений Type propagation change
Unit type Type de l'unité Unit type Tipo de unidad Unidade tipo Группы типа Unit type
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : HNZ Model SHEET : Modèles HNZ SHEET : HNZ Model SHEET : Modelo HNZ SHEET : Modo HNZ SHEET : Модель HNZ SHEET : HNZ Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN SCADA HNZ DEBUT SCADA HNZ BEGIN SCADA HNZ COMIENZA SCADA HNZ INÍCIO SCADA HNZ НАЧАЛО ОПИСАНИЯ SCADA HNZ BEGIN SCADA HNZ
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
SCADA Protocol Name Nom de protocole SCADA SCADA Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Scada short name (16 char) Nom court du SCADA (16 char) Scada short name (16 char) Nombre corto Scada (16 caract) Nome Curto Scada (16 caract) Сокращенное имя SCADA (16 символов) Scada short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Main communication channel Voie de communication principale Main communication channel Canal de comunicación principal Canal de Comunicação Principal Основной канал связи Main communication channel
Auxiliary Communication channel Voie de communication auxiliaire Auxiliary Communication channel Canal de comunciación auxiliar Canal de Comunicação auxiliar Запасной канал связи Auxiliary Communication channel
Baud rate (bit/s) Vitesse de transmission (bit/s) Baud rate (bit/s) Baudios (bit/s) Baud Rate (bit/s) Скорость в бодах (бит/с) Baud rate (bit/s)
Protocol Protocole Protocol Protocolo Protocolo Протокола Protocol
Time Reference Temps de référence Time Reference Tiempo de referencia Tempo de referência Время ссылку Zeitplan
Station address Adresse de la Station Station address Estación de dirección Estação endereço Станция адрес Station address
Network station number Numéro de Station réseau Network station number Número de la estación de red Rede estação número Сетевой номер станции Network station number
RTU Db version RTU version base de donnée RTU Db version Base de datos versión RTU RTU versão base РТУ версию базы данных RTU Db version
Enable concatenation Concatenation possible Enable concatenation Permitir la concatenación Ativar concatenation Включить конкатенация Enable concatenation
Checksum size (fcs) Taille du Checksum (fcs) Checksum size (fcs) Checksum tamaño (fcs) Checksum tamanho (fcs) Checksum размера (fcs) Checksum size (fcs)
Max number of retries Nombre max de tentatives Max number of retries Max number of retries Max number of retries Max number of retries Max number of retries
Inter frame duration Durée inter trame Inter frame duration Duración entre 2 fotogramas Duração entre 2 frames Продолжительность от 2 кадров Inter frame duration
Anticipate rate Taux d'Anticipation Anticipate rate Anticipar tasa Antecipe taxa Предвидеть курс Anticipate rate
Frame max length Longueur maximale de la vue Frame max length Longitud máx de la trama Tamanho máx do frame Максимальная длина кадра Frame max length
Measurement Cycle 1 (s) Cycle de Mesure 1 (s) Measurement Cycle 1 (s) Ciclo de medición 1 (s) Medição ciclo 1 (s) Измерение цикла 1 (s) Measurement Cycle 1 (s)
Measurement Cycle 2 (s) Cycle de Mesure 2 (s) Measurement Cycle 2 (s) Ciclo de medición 2 (s) Medição ciclo 2 (s) Измерение цикла 2 (s) Measurement Cycle 2 (s)
Measurement Cycle 3 (s) Cycle de Mesure 3 (s) Measurement Cycle 3 (s) Ciclo de medición 3 (s) Medição ciclo 3 (s) Измерение цикла 3 (s) Measurement Cycle 3 (s)
Measurement Cycle 4 (s) Cycle de Mesure 4 (s) Measurement Cycle 4 (s) Ciclo de medición 4 (s) Medição ciclo 4 (s) Измерение цикла 4 (s) Measurement Cycle 4 (s)
Fifo : loss information or RTU init address (byte.bit) Fifo : adresse de perte de donnée ou RTU Init (octet.bit) Fifo : loss information or RTU init address (byte.bit) Fifo : pérdida de información de dirección o RTU Init (byte.bit) Fifo : perda informações endereço o RTU Init (byte.bit) Fifo : утрата информации - РТУ иниц адрес (byte.bit) Fifo : loss information or RTU init address (byte.bit)
Fifo : depth of chronologic sorting (ms) Fifo : profondeur de tri chronologique (ms) Fifo : depth of chronologic sorting (ms) Fifo : profundidad de la clasificación cronológica (ms) Fifo : profundidade de triagem cronológico (ms) Fifo : Глубина chronologic сортировка (ms) Fifo : depth of chronologic sorting (ms)
Fifo : empty condition Fifo : condition vide Fifo : empty condition Fifo : condición de vacío Fifo : vazias condição Fifo : пусто условие Fifo : empty condition
Fifo : No activity, retry or supervision delay (ms) Fifo : délai de non activité, nouvelle tentative ou supervision (ms) Fifo : No activity, retry or supervision delay (ms) Fifo : Ninguna actividad, o la supervisión de reintento de retraso (ms) Fifo : Sem atividade, tentar novamente ou supervisão atraso (ms) Fifo : Нет деятельности, повторить или надзор задержка (мс) Fifo : No activity, retry or supervision delay (ms)
RTE : Period to analyze quality of line (s) RTE : Periode d'analyse de qualité de ligne (s) RTE : Period to analyze quality of line (s) RTE : Período para analizar la calidad de la línea (s) RTE : Período para análise da qualidade de linha (s) РTE : Период для анализа качества линии (s) RTE : Period to analyze quality of line (s)
RTE : Bulle message allowed RTE : Message Bulle autorisé RTE : Bulle message allowed RTE : Bulle permitido mensaje RTE : Bulle mensagem permitido РTE : Бюль сообщений разрешен RTE : Bulle message allowed
RTE : Period for sending Bulle message (s) RTE : Periode d'envoi d'un message Bulle (s) RTE : Period for sending Bulle message (s) RTE : Período para el envío de Bulle mensaje (s) RTE : Prazo para envio Bulle mensagem (s) РTE : Срок отправки сообщения Бюль (s) RTE : Period for sending Bulle message (s)
RTE : TOR Battante address (byte.bit) RTE : Adresse de TOR Battante (octet.bit) RTE : TOR Battante address (byte.bit) RTE : TOR Battante dirección (byte.bit) RTE : TOR Battante endereço (byte.bit) РTE : TOР Battante адрес (byte.bit) RTE : TOR Battante address (byte.bit)
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
Used cycle Cycle utilisé Used cycle Usado ciclo Usado ciclo Используется цикла Used cycle
Format Format Format Formato Formato Формат Format
Message Structure Structure de message Message Structure Estructura del mensaje Estrutura das mensagens Сообщение Структура Message Structure
Original Value converted Conversion de la valeur originale Original Value converted Valor original convertido Valor original convertido Первоначальная стоимость преобразованы Original Value converted
Sent on variation Envoyé sur variation Sent on variation Enviado en la variación Enviada em variação Переданные по вариации Sent on variation
Variation Mode Mode de variation Variation Mode Modo de variación Modo de variação вариации режиме Variation Mode
Deadband Bande morte Deadband Venda muerta Faixa muerta Порог чувствительности Deadband
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
SCADA order type Type de commande SCADA SCADA order type Tipo de orden SCADA Tipo de Ordem SCADA Тип команды SCADA SCADA order type
Format Format Format Formato Formato Формат Format
Minimum value Valeur Min Minimum value Valor al mínimo Valor ao Mínimo Значение минимуму Minimum value
Maximum value Valeur Max Maximum value Valor al Máximo Valor ao Máximo Значение максимуму Maximum value
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
Default Unit Unité par défaut Default Unit Unidad por defecto Unidade padrão Группа по умолчанию Default Unit
Default Unit for datapoint Unité par défaut pour le point de donnée Default Unit for datapoint Unidad por defecto de Datapoint Unidade padrão para Datapoint Группа по умолчанию Datapoint Default Unit for datapoint
Default Unit Unité par défaut Default Unit Unidad por defecto Unidade padrão Группа по умолчанию Default Unit
Default Unit for datapoint Unité par défaut pour le point de donnée Default Unit for datapoint Unidad por defecto de Datapoint Unidade padrão para Datapoint Группа по умолчанию Datapoint Default Unit for datapoint
Default Unit Unité par défaut Default Unit Unidad por defecto Unidade padrão Группа по умолчанию Default Unit
Default Unit for datapoint Unité par défaut pour le point de donnée Default Unit for datapoint Unidad por defecto de Datapoint Unidade padrão para Datapoint Группа по умолчанию Datapoint Default Unit for datapoint
SHEET : T101 MASTER Model SHEET : Modèles T101 MAITRE SHEET : T101 Model MASTER SHEET : Modelo T101 MASTER SHEET : Modo T101 MASTER SHEET : Модель T101 MASTER SHEET : T101 MASTER Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN T101 MASTER DEBUT T101 MAITRE BEGIN T101 MASTER COMIENZA T101 MASTER INÍCIO T101 MASTER НАЧАЛО ОПИСАНИЯ T101 MASTER BEGIN T101 MASTER
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Protocol Name Nom du protocole Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Short name (16 char) Nom court(16 char) Short name (16 char) Nombre corto(16 caract) Nome Curto(16 caract) Сокращенное имя(16 символов) short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Time Reference Temps de référence Time Reference Tiempo de referencia Tempo de referência Время ссылку Zeitplan
number of retries number of retries number of retries number of retries number of retries number of retries number of retries
station address size (bytes) station address size (bytes) station address size (bytes) station address size (bytes) station address size (bytes) station address size (bytes) station address size (bytes)
ASDU address size (bytes) ASDU address size (bytes) ASDU address size (bytes) ASDU address size (bytes) ASDU address size (bytes) ASDU address size (bytes) ASDU address size (bytes)
info address size (bytes) info address size (bytes) info address size (bytes) info address size (bytes) info address size (bytes) info address size (bytes) info address size (bytes)
transmission cause size (bytes) taill cause de transmission (bytes) transmission cause size (bytes) transmission cause size (bytes) transmission cause size (bytes) transmission cause size (bytes) transmission cause size (bytes)
acknowledgement time-out (x 100 ms) acknowledgement time-out (x 100 ms) acknowledgement time-out (x 100 ms) acknowledgement time-out (x 100 ms) acknowledgement time-out (x 100 ms) acknowledgement time-out (x 100 ms) acknowledgement time-out (x 100 ms)
synchronization cycle (x 10 s) synchronization cycle (x 10 s) synchronization cycle (x 10 s) synchronization cycle (x 10 s) synchronization cycle (x 10 s) synchronization cycle (x 10 s) synchronization cycle (x 10 s)
downgraded cycle (x 100 ms) downgraded cycle (x 100 ms) downgraded cycle (x 100 ms) downgraded cycle (x 100 ms) downgraded cycle (x 100 ms) downgraded cycle (x 100 ms) downgraded cycle (x 100 ms)
Type of link Type de lien Type of link Tipo de enlace Tipo de ligação Вид ссылки Art der Verknüpfung
test frame time-out (s) test frame time-out (s) test frame time-out (s) test frame time-out (s) test frame time-out (s) test frame time-out (s) test frame time-out (s)
Inter frame duration Durée inter trame Inter frame duration Duración entre 2 fotogramas Duração entre 2 frames Продолжительность от 2 кадров Inter frame duration
Baud rate (bit/s) Vitesse de transmission (bit/s) Baud rate (bit/s) Baudios (bit/s) Baud Rate (bit/s) Скорость в бодах (бит/с) Baud rate (bit/s)
Legacy IED parameters Legacy IED parameters Legacy IED parameters Legacy IED parameters Legacy IED parameters Legacy IED parameters Legacy IED parameters
automatic disturbance automatic disturbance automatic disturbance automatic disturbance automatic disturbance automatic disturbance automatic disturbance
localisation for disturbance file localisation for disturbance file localisation for disturbance file localisation for disturbance file localisation for disturbance file localisation for disturbance file localisation for disturbance file
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
contact identifier contact identifier contact identifier contact identifier contact identifier contact identifier contact identifier
MPS Data Type MPS Donnée de Type MPS Data Type MPS Datos tipo MPS Dados tipo MPS Тип данных MPS Data Type
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
order type Type de commande order type Tipo de orden Tipo de Ordem Тип команды order type
acknowledgement delay délai d'acquittement acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
order type Type de commande order type Tipo de orden Tipo de Ordem Тип команды order type
contact type Type de contact contact type contact tipo contact tipo Τύπος επαφής contact type
acknowledgement delay délai d'acquittement acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
output format output format output format output format output format output format output format
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
order type Type de commande order type Tipo de orden Tipo de Ordem Тип команды order type
output format output format output format output format output format output format output format
minimal value minimal value minimal value minimal value minimal value minimal value minimal value
maximal value maximal value maximal value maximal value maximal value maximal value maximal value
acknowledgement delay délai d'acquittement acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay
Counter Data Type Compteur de Donnée de Type Counter Data Type Counter Datos tipo Contador de Dados tipo Counter Тип данных Counter Data Type
output format output format output format output format output format output format output format
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
SHEET : T104 MASTER Model SHEET : Modèles T104 MAITRE SHEET : T104 MASTER Model SHEET : Modelo T101 MASTER SHEET : Modo T101 MASTER SHEET : Модель T101 MASTER SHEET : T101 MASTER Model
Designation : Désignation : Designation : Denominación : Denominação : Назначение : Bezeichnung:
Symbol : Réf. GE : Symbol : Símbolo : Símbolo : Обозначение : Symbol :
Issue : Révision : Issue : Revisión : Revisão : Версия : Version:
Ref : N° Document : Ref : Ref : Ref : Ссылка : Ref :
Date : Date : Date : Fecha : Data : Дата : Datum:
Substation Automation Sous-Station Automation Substation Automation Automatización de Subestaciones Automação de Subestações Автоматизация Подстанций Substation Automation
Data Of : Données de : Data Of : Datos de : Dados de : Пpoekt : Data Of :
BEGIN T104 MASTER DEBUT T104 MAITRE BEGIN T104 MASTER COMIENZA T104 MASTER INÍCIO T104 MASTER НАЧАЛО ОПИСАНИЯ T104 MASTER BEGIN T104 MASTER
Keys : Légende : Keys : Claves : CHAVES : Ключи : Keys :
GE Reserved Réservé à GE GE Reserved Reservado GE Reservado GE Зарезервировано GE GE Reserved
Read Only Lecture seule Read Only Solo lectura Somemte Leitura Только Чтение Read Only
Protocol Name Nom du protocole Protocol Name Nombre de Protocolo SCADA Nome do Protocolo SCADA SCADA ИМЯ Протокола SCADA Protocol Name
Short name (16 char) Nom court(16 char) Short name (16 char) Nombre corto(16 caract) Nome Curto(16 caract) Сокращенное имя(16 символов) short name (16 char)
Protocol General Parameters Paramètres généraux du Protocole Protocol General Parameters Parámetros generales del protocolo Parâmetros Geração do Protocolo Основные параметры протокола Protocol General Parameters
Time Reference Référence horaire Time Reference Tiempo de referencia Tempo de referência Время ссылку Zeitplan
TCP/IP Address Adresse TCP/IP TCP/IP Address TCP/IP Address TCP/IP Address TCP/IP Address TCP/IP Address
Redundant TCP/IP Address Adresse TCP/IP redondée Redundant TCP/IP Address TCT/IP Address redundante TCP/IP Address redundante Redundant TCP/IP Address Redundant TCP/IP Address
t0: connection established timeout (s) t0: délai d'établissement de connexion (s) t0: connection established timeout (s) t0: connection established timeout (s) t0: connection established timeout (s) t0: connection established timeout (s) t0: connection established timeout (s)
t1: APDUs send or test time out (s) t1: délai d'envoi ou test d'APDU (s) t1: APDUs send or test time out (s) t1: APDUs send or test time out (s) t1: APDUs send or test time out (s) t1: APDUs send or test time out (s) t1: APDUs send or test time out (s)
t2: acknowledges in case of no data time out (s) t2: délai d'acquittement si pas de données (s) t2: acknowledges in case of no data time out (s) t2: acknowledges in case of no data time out (s) t2: acknowledges in case of no data time out (s) t2: acknowledges in case of no data time out (s) t2: acknowledges in case of no data time out (s)
t3: test frame sending in case of no data timeout (s) t3: délai d'envoi de trame de test en cas d'état en veille (s) t3: test frame sending in case of no data timeout (s) t3: test frame sending in case of no data timeout (s) t3: test frame sending in case of no data timeout (s) t3: test frame sending in case of no data timeout (s) t3: test frame sending in case of no data timeout (s)
k: window size of transmitted unacknowledged frames k: taille de la fenêtre des trames non transmises k: window size of transmitted unacknowledged frames k: window size of transmitted unacknowledged frames k: window size of transmitted unacknowledged frames k: window size of transmitted unacknowledged frames k: window size of transmitted unacknowledged frames
w: window size of acknowledged received frames w: taille de la fenêtre des trames reçues w: window size of acknowledged received frames w: window size of acknowledged received frames w: window size of acknowledged received frames w: window size of acknowledged received frames w: window size of acknowledged received frames
synchronization cycle (x 10s) Cycle de synchronisation (x 10s) synchronization cycle (x 10s) synchronization cycle (x 10s) synchronization cycle (x 10s) synchronization cycle (x 10s) synchronization cycle (x 10s)
Inter frame duration Durée inter trame Inter frame duration Duración entre 2 fotogramas Duração entre 2 frames Продолжительность от 2 кадров Inter frame duration
SPS Data Type SPS Donnée de Type SPS Data Type SPS Datos tipo SPS Dados tipo SPS Тип данных SPS Data Type
DPS Data Type DPS Donnée de Type DPS Data Type DPS Datos tipo DPS Dados tipo DPS Тип данных DPS Data Type
contact identifier Identifiant contact contact identifier contact identifier contact identifier contact identifier contact identifier
MPS Data Type MPS Donnée de Type MPS Data Type MPS Datos tipo MPS Dados tipo MPS Тип данных MPS Data Type
SPC Data Type SPC Donnée de Type SPC Data Type SPC Datos tipo SPC Dados tipo SPC Тип данных SPC Data Type
order type Type de commande order type Tipo de orden Tipo de Ordem Тип команды order type
acknowledgement delay Délai acquittement acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay
DPC Data Type DPC Donnée de Type DPC Data Type DPC Datos tipo DPC Dados tipo DPC Тип данных DPC Data Type
order type Type de commande order type Tipo de orden Tipo de Ordem Тип команды order type
contact type Type de contact contact type contact tipo contact tipo Τύπος επαφής contact type
acknowledgement delay Délai acquittement acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay
MV Data Type MV Donnée de Type MV Data Type MV Datos tipo MV Dados tipo MV Тип данных MV Data Type
output format Format de sortie output format output format output format output format output format
Setpoint Data Type SetPoint Donnée de Type Setpoint Data Type SetPoint Datos tipo SetPoint Dados tipo SetPoint Тип данных Setpoint Data Type
order type Type de commande order type Tipo de orden Tipo de Ordem Тип команды order type
output format Format de sortie output format output format output format output format output format
minimal value Valeur minimale minimal value minimal value minimal value minimal value minimal value
maximal value Valeur maximale maximal value maximal value maximal value maximal value maximal value
acknowledgement delay Délai acquittement acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay acknowledgement delay
Counter Data Type Compteur de Donnée de Type Counter Data Type Counter Datos tipo Contador de Dados tipo Counter Тип данных Counter Data Type
output format Format de sortie output format output format output format output format output format
END OF DATA FIN DES DONNEES END OF DATA FIN DE DATOS FIM DOS DADOS КОНЕЦ ДАННЫХ END OF DATA
Hitachi/ABB Standard Signal List
Sl. No Description Revision Remarks
1 Standard Signals for 765kV Level Rev-00
2 Standard Signals for 400kV Level Rev-00
3 Standard Signals for 220kV Level Rev-00
4 Standard Signals for Aux System Rev-00
Revision History
Rev.No Description of Remarks Date Remarks
01 Initital Release 16.01.2024
ABB SCADA GENERAL SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (INDEX)
BAY IED MODEL IED SYMBOLIC NAME APPLICATION IED NAME IN SCD
LINE REC670 R_REC670_BCU Bay Control Unit STNMB1Q01LBCU
REL670 R_REL670_21M1 Main 1 Distance Protection STNMB1Q01M1DIS
** R_RELAY NAME_21M2 Main 2 Distance Protection **
ICT REC670 R_REC670_BCU Bay Control Unit STNMB1Q01TBCU
RET670 R_RET670_87T Differential Protection STNMB1Q01TDIF
RET670 R_RET670_64 Restricted Earthfault Protection STNMB1Q01TREF
REL670 R_REL670_BIMP HV Backup Impedance Protection STNMB1Q01THVBIMP
REL670 R_REL670_BIMP LV Backup Impedance Protection STNMB1Q01TLVBIMP
REL670 R_REL670_HVBUP HV Backup OC/EF Protection STNMB1Q01THBU
REL670 R_REL670_LVBUP LV Backup OC/EF Protection STNMB1Q01TLBU
BUSREACTOR REC670 R_REC670_BCU Bay Control Unit STNMB1Q01BRBCU
RET670 R_RET670_87R Differential Protection STNMB1Q01BRDIF
RET670 R_RET670_64R Restricted Earthfault Protection STNMB1Q01BRREF
REL670 R_REL670_BIMP Backup Impedance Protection STNMB1Q01BRBIMP
LINE REACTOR REC670 R_REC670_BCU Bay Control Unit STNMB1Q01LRBCU
RET670 R_RET670_87R Differential Protection STNMB1Q01LRDIF
RET670 R_RET670_64R Restricted Earthfault Protection STNMB1Q01LRREF
REL670 R_REL670_BIMP Backup Impedance Protection STNMB1Q01LRBIMP
TIE REC670 R_REC670_BCU Bay Control Unit STNMB1Q01TIEBCU
LBB REL670 R_RELAY NAME_50BFR Breaker Failure Protection STNMB1Q01BFR
BUSBAR PROTECTION (DECENTRALIZED) REB500 BB_REB500_87BM1 Main1 Busbar Protection STNMB1BBM1
REB500 BB_REB500_87BM2 Main2 Busbar Protection STNMB1BBM2
BUSBAR PROTECTION (CENTRALIZED) REB670 BB_REB670_87BM1 Main1 Busbar Protection STNMB1BBM1
REB670 BB_REB670_87BM2 Main2 Busbar Protection STNMB1BBM2
NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "B1" stand for Voltage level, this will be vary based on station voltage level eg. B1 for 765kV, C1 for 400kV & D1 for 220kV etc…
NOTE 3: The characters "Q01" stand for Bay Number, this will be vary based on Bay number eg. Q01 for BAY01, Q02 for BAY02 etc…
NOTE 4: ** Line Main2 Distance protection IED name will be subject to provision availability of maximum number of characters in the IED
ABB SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (765kV)
REQUIRED SIGNALS FOR DISTANCE RELAYS
IED name: R_REL670_21M1
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV1/Str/general SPI OVERVOLATGE STAGE 1 START
2 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV1/Op/general SPI OVERVOLATGE STAGE 1 TRIP Y
3 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/OV2PTOV2/Str/general SPI OVER VOLTAGE STAGE-2 START Y Addition Agreed
4 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV2/Op/general SPI OVERVOLATGE STAGE 2 TRIP Y
5 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/EF4_1/EF4PTOC1/Str/general SPI DEF START
6 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/EF4_1/EF4PTOC1/Op/general SPI DEF TRIP Y
7 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/STBPTOC1/Op/general SPI STUB PROTECTION OPERATED Y Applicable for One and Half CB Busbar system
8 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCVPSOF1/Op/general SPI SOTF OPERATED Y
9 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Str/general SPI START, Z1
10 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/general SPI START, Z2
11 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsA SPI START, Z2 R PH
12 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsB SPI START, Z2 Y PH
13 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsC SPI START, Z2 B PH
14 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS3/Str/general SPI START, Z3
15 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS4/Str/general SPI START, Z4(REVERSE) ** Whichever the zone choses as Reverse Text correction Agreed
16 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS5/Str/general SPI START, Z5
17 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/general SPI GENERAL TRIP, Z1 Y
18 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsA SPI TRIP, Z1 R PH Y
19 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsB SPI TRIP, Z1 Y PH Y
20 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsC SPI TRIP, Z1 B PH Y
21 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/general SPI GENERAL TRIP, Z2 Y
22 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsA SPI TRIP, Z2 R PH Y
23 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsB SPI TRIP, Z2 Y PH Y
24 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsC SPI TRIP, Z2 B PH Y
25 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS3/Op/general SPI GENERAL TRIP, Z3 Y
26 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS4/Op/general SPI GENERAL TRIP, Z4(REVERSE) Y ** Whichever the zone choses as Reverse Text correction Agreed
27 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS5/Op/general SPI GENERAL TRIP, Z5 Y
28 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/ProTx/stVal SPI CARRIER SEND Y
29 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/ProRx/stVal SPI CARRIER RECEIVE Y
30 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/Op/general SPI CARRIER AIDED SCHEME OPERATED Y
31 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMRPSB1/Str/general SPI POWER SWING DETECTED Y
32 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMRPSB1/BlkZn/stVal SPI POWER SWING BLOCKING Y
33 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SMPPTRC1/Op/general SPI DISTANCE RELAY GENERAL TRIP Y
34 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI R PHASE FAULT Y Addition Agreed
35 765kV STNMB1Q01M1DIS SPI Y PHASE FAULT Y Addition Agreed
36 765kV STNMB1Q01M1DIS SPI B PHASE FAULT Y Addition Agreed
37 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltDiskm/mag DINT FAULT LOCATOR DISTANCE
38 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltZ/cVal.mag DINT FAULT LOCATOR IMPEDANCE
39 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
40 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/BRCPTOC1/Op/general SPI BROKEN CONDUCTOR ALARM Y
41 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
42 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/LPHD1/PhyHealth/stVal SPI M1 IED UNHEALTHY Y
43 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI START AR TO BCU Text correction Agreed
44 765kV STNMB1Q01M1DIS SPI BLOCK AR TO BCU Text correction Agreed
45 765kV STNMB1Q01M1DIS SPI LINE ISOLATOR OPEN FOR STUB ACTIVATION Applicable for One and Half CB Busbar system
46 765kV STNMB1Q01M1DIS SPI DT SEND CH 1 Y
47 765kV STNMB1Q01M1DIS SPI DT SEND CH 2 Y
48 765kV STNMB1Q01M1DIS SPI DT RECEIVE CH 1 Y Only for DR in REL670, for SCADA to be configured from BCU
49 765kV STNMB1Q01M1DIS SPI DT RECEIVE CH 2 Y Only for DR in REL670, for SCADA to be configured from BCU
50 765kV STNMB1Q01M1DIS SPI TRIP RELAY 86 A HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
51 765kV STNMB1Q01M1DIS SPI TRIP RELAY 86 B HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
52 765kV STNMB1Q01M1DIS SPI GR A RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in REL670, for SCADA to be configured from BCU
53 765kV STNMB1Q01M1DIS SPI GR B RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in REL670, for SCADA to be configured from BCU
54 765kV STNMB1Q01M1DIS SPI CARRIER RECEIVE CH-1 Y
55 765kV STNMB1Q01M1DIS SPI CARRIER RECEIVE CH-2 Y
56 765kV STNMB1Q01M1DIS SPI CARRIER CHANNEL 1 OUT OF SERVICE Y
57 765kV STNMB1Q01M1DIS SPI CARRIER CHANNEL 2 OUT OF SERVICE Y
58 765kV STNMB1Q01M1DIS SPI CARRIER CHANNEL 1 FAIL Y
59 765kV STNMB1Q01M1DIS SPI CARRIER CHANNEL 2 FAIL Y
60 765kV STNMB1Q01M1DIS SPI MAIN 2/1 RELAY FAIL Y
61 765kV STNMB1Q01M1DIS SPI CB CLOSE COMMAND FOR SOTF INITIATION Text correction
62 765kV STNMB1Q01M1DIS SPI BCU RELAY FAIL Y
63 765kV STNMB1Q01M1DIS SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
64 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsA SPI START, Z1 R PH Addition
65 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsB SPI START, Z1 Y PH Addition
66 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsC SPI START, Z1 B PH Addition
67 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP 3PH Y Addition
68 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP R PH Y Addition
69 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP Y PH Y Addition
70 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP B PH Y Addition
71 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI PREPARE 3-PH TRIP FROM TIE BCU Y Addition, Available in BCU It is also required in REL670
72 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI PREPARE 3-PH TRIP FROM MAIN BCU Y Addition, Available in BCU It is also required in REL670
73 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI MAIN/ TIE CB AR OPTD Y Addition, Available in BCU Only for DR in REL670, for SCADA to be configured from BCU
74 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI MAIN/TIE LBB PROTECTION OPERATED Y Addition, Available in BBP Only for DR in REL670, for SCADA to be configured from LBB/BBP relay
75 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI BUSBAR M1/M2 OPTD Y Addition, Available in BBP Only for DR in REL670, for SCADA to be configured from BBP relay
76 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI GROUP RELAY 86A OPTD Y Available in REL670 (Sig. 52) Agreed
77 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/EchoWei/stVal SPI WEAK INFEED ECHO SEND Y Addition
78 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/EchoWeiOp/stVal SPI WEAK INFEED TRIP Y Addition
79 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/RvABlk/stVal SPI CURRENT REVERSAL DETECTED Y Addition
80 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
81 765kV STNMB1Q01M1DIS SPI SETTINGS CHANGED Y Addition
82 765kV STNMB1Q01M1DIS SPI DR MEMMORY 80% FULL Y Addition
83 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltDiskm/mag AI DISTANCE MEASUREMENT IN KM Y Available in REL670 (Sig. 37) Agreed
84 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltZ/cVal/mag AI DISTANCE MEASUREMENT IN IMPEDANCE Y Available in REL670 (Sig. 38) Agreed
85 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/MON/L4UFCNTn/CntVal/actVal AI CH-1 Code-1 Tx (MAIN-1 CARRIER RECEIVE CHANNEL-1) CH-1 Code-1 Tx (MAIN-1 CARRIER SEND CHANNEL-1)
86 765kV STNMB1Q01M1DIS AI CH-1 Code-1 Rx (MAIN-1 CARRIER SEND CHANNEL-1) CH-1 Code-1 Rx (MAIN-1 CARRIER RECEIVE CHANNEL-1)
87 765kV STNMB1Q01M1DIS AI CH-1 Code-2 Tx (MAIN-2 CARRIER RECEIVE CHANNEL-1) CH-1 Code-2 Tx (MAIN-2 CARRIER SEND CHANNEL-1)
88 765kV STNMB1Q01M1DIS AI CH-1 Code-2 Rx (MAIN-2 CARRIER SEND CHANNEL-1) CH-1 Code-2 Rx (MAIN-2 CARRIER RECEIVE CHANNEL-1)
89 765kV STNMB1Q01M1DIS AI CH-2 Code-2 Tx (MAIN-2 CARRIER RECEIVE CHANNEL-2) CH-2 Code-2 Tx (MAIN-2 CARRIER SEND CHANNEL-2)
90 765kV STNMB1Q01M1DIS AI CH-2 Code-2 Rx (MAIN-2 CARRIER SEND CHANNEL-2) CH-2 Code-2 Rx (MAIN-2 CARRIER RECEIVECHANNEL-2)
91 765kV STNMB1Q01M1DIS AI CH-2 Code-1 Tx (MAIN-1 CARRIER RECEIVE CHANNEL-2) CH-2 Code-1 Tx (MAIN-1 CARRIER SEND CHANNEL-2)
92 765kV STNMB1Q01M1DIS AI CH-2 Code-1 Rx (MAIN-1 CARRIER SEND CHANNEL-2) CH-2 Code-1 Rx (MAIN-1 CARRIER RECEIVE CHANNEL-2)
93 765kV STNMB1Q01M1DIS AI CH-1 Code-3 Tx (DT RECEIVE CHANNEL-1) CH-1 Code-3 Tx (DT SEND CHANNEL-1)
94 765kV STNMB1Q01M1DIS AI CH-1 Code-3 Rx (DT SEND CHANNEL-1) CH-1 Code-3 Rx (DT RECEIVE CHANNEL-1)
95 765kV STNMB1Q01M1DIS AI CH-2 Code-3 Tx (DT RECEIVE CHANNEL-2) CH-2 Code-3 Tx (DT SEND CHANNEL-2)
96 765kV STNMB1Q01M1DIS AI CH-2 Code-3 Rx (DT SEND CHANNEL-2) CH-2 Code-3 Rx (DT RECEIVE CHANNEL-2)
97 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
98 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-2 Y Addition
99 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-3 Y Addition
100 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-4 Y Addition
101 765kV STNMB1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-5 Y Addition
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR ICT DIFFERENTIAL RELAYS
IED name: R_RET670_87T
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/OEXPVPH1/Str/general SPI OVEREXCITATION HV START
2 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/OEXPVPH1/Alm/stVal SPI OVEREXCITATION HV ALARM Y
3 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/OEXPVPH1/Op/general SPI OVEREXCITATION HV TRIP Y
4 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/DifAlm/stVal SPI DIFFERENTIAL CURRENT ALARM Y
5 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/general SPI DIFFERENTIAL PROTECTION START
6 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsA SPI DIFFERENTIAL PROTECTION RPH START
7 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsB SPI DIFFERENTIAL PROTECTION YPH START
8 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsC SPI DIFFERENTIAL PROTECTION BPH START
9 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Op/general SPI DIFFERENTIAL PROTECTION TRIP Y
10 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION RPH TRIP Y
11 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION YPH TRIP Y
12 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION BPH TRIP Y
13 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/OpRst/stVal SPI DIFFERENTIAL PROTECTION TRIP (RESTRAINED MODE) Y
14 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/OpUnRst/stVal SPI DIFFERENTIAL PROTECTION TRIP (UNRESTRAINED MODE) Y
15 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Blk2H/stVal SPI DIFFERENTIAL PROTECTION 2nd HARMONIC BLOCK
16 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Blk5H/stVal SPI DIFFERENTIAL PROTECTION 5th HARMONIC BLOCK
17 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SMPPTRC1/Op/general SPI DIFFERENTIAL RELAY GENERAL TRIP Y
18 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
19 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/LPHD1/PhyHealth/stVal SPI DIFFRENTIAL IED UNHEALTHY Y
20 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI OTI ALARM Y APPLICABLE FOR 3 PHASE TRANSFORMERS
21 765kV STNMB1Q01TDIF SPI WTI HV ALARM Y
22 765kV STNMB1Q01TDIF SPI WTI IV ALARM Y
23 765kV STNMB1Q01TDIF SPI WTI MV ALARM Y
24 765kV STNMB1Q01TDIF SPI BUCCHOLZ_n ALARM Y Addition
25 765kV STNMB1Q01TDIF SPI BUCCHOLZ_n TRIP Y Text correction
26 765kV STNMB1Q01TDIF SPI OSR _n TRIP Y Text correction
27 765kV STNMB1Q01TDIF SPI PRD _n TRIP Y Text correction
28 765kV STNMB1Q01TDIF SPI FIRE PROTECTION OPERATED Y
29 765kV STNMB1Q01TDIF SPI LOW OIL LEVEL Y
30 765kV STNMB1Q01TDIF SPI OTI R PH ALARM Y APPLICABLE FOR SINGLE PHASE TRANSFORMERS (If a dedicated IED is provided for spare transformer protection, only spare phase signals are required to be used)
31 765kV STNMB1Q01TDIF SPI OTI Y PH ALARM Y
32 765kV STNMB1Q01TDIF SPI OTI B PH ALARM Y
33 765kV STNMB1Q01TDIF SPI OTI SPARE ICT ALARM Y
34 765kV STNMB1Q01TDIF SPI WTI HV R PH ALARM Y
35 765kV STNMB1Q01TDIF SPI WTI HV Y PH ALARM Y
36 765kV STNMB1Q01TDIF SPI WTI HV B PH ALARM Y
37 765kV STNMB1Q01TDIF SPI WTI HV SPARE ICT ALARM Y
38 765kV STNMB1Q01TDIF SPI WTI MV R PH ALARM Y
39 765kV STNMB1Q01TDIF SPI WTI MV Y PH ALARM Y
40 765kV STNMB1Q01TDIF SPI WTI MV B PH ALARM Y
41 765kV STNMB1Q01TDIF SPI WTI MV SPARE ICT ALARM Y
42 765kV STNMB1Q01TDIF SPI WTI IV R PH ALARM Y
43 765kV STNMB1Q01TDIF SPI WTI IV Y PH ALARM Y
44 765kV STNMB1Q01TDIF SPI WTI IV B PH ALARM Y
45 765kV STNMB1Q01TDIF SPI WTI IV SPARE ICT ALARM Y
46 765kV STNMB1Q01TDIF SPI BUCHHOLZ_n R PH ALARM Y Addition
47 765kV STNMB1Q01TDIF SPI BUCHHOLZ_n Y PH ALARM Y Addition
48 765kV STNMB1Q01TDIF SPI BUCHHOLZ_n B PH ALARM Y Addition
49 765kV STNMB1Q01TDIF SPI BUCHHOLZ_n SPARE ICT TRIP Y Addition, BUCHHOLZ_n SPARE ICT ALARM
50 765kV STNMB1Q01TDIF SPI BUCHHOLZ_n R PH TRIP Y Text correction
51 765kV STNMB1Q01TDIF SPI BUCHHOLZ_n Y PH TRIP Y Text correction
52 765kV STNMB1Q01TDIF SPI BUCHHOLZ_n B PH TRIP Y Text correction
53 765kV STNMB1Q01TDIF SPI BUCHHOLZ_n SPARE ICT TRIP Y Text correction
54 765kV STNMB1Q01TDIF SPI OSR_n R PH TRIP Y Text correction
55 765kV STNMB1Q01TDIF SPI OSR_n Y PH TRIP Y Text correction
56 765kV STNMB1Q01TDIF SPI OSR_n B PH TRIP Y Text correction
57 765kV STNMB1Q01TDIF SPI OSR_n SPARE ICT TRIP Y Text correction
58 765kV STNMB1Q01TDIF SPI PRD n R PH TRIP Y Text correction
59 765kV STNMB1Q01TDIF SPI PRD nY PH TRIP Y Text correction
60 765kV STNMB1Q01TDIF SPI PRD n B PH TRIP Y Text correction
61 765kV STNMB1Q01TDIF SPI PRD n SPARE ICT TRIP Y Text correction
62 765kV STNMB1Q01TDIF SPI LOW OIL LEVEL R PH Y
63 765kV STNMB1Q01TDIF SPI LOW OIL LEVEL Y PH Y
64 765kV STNMB1Q01TDIF SPI LOW OIL LEVEL B PH Y
65 765kV STNMB1Q01TDIF SPI LOW OIL LEVEL SPARE ICT Y
66 765kV STNMB1Q01TDIF SPI FIRE PROTECTION R PH OPERATED Y
67 765kV STNMB1Q01TDIF SPI FIRE PROTECTION Y PH OPERATED Y
68 765kV STNMB1Q01TDIF SPI FIRE PROTECTION B PH OPERATED Y
69 765kV STNMB1Q01TDIF SPI FIRE PROTECTION SPARE ICT OPERATED Y
70 765kV STNMB1Q01TDIF SPI TRIP RELAY 86 A HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
71 765kV STNMB1Q01TDIF SPI TRIP RELAY 86 B HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
72 765kV STNMB1Q01TDIF SPI GR A RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RET670, for SCADA to be configured from BCU
73 765kV STNMB1Q01TDIF SPI GR B RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RET670, for SCADA to be configured from BCU
74 765kV STNMB1Q01TDIF SPI REF RELAY FAIL Y
75 765kV STNMB1Q01TDIF SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
** It may be noted that the Body Protection alarms & trips have been Grouped into two separate relays Differential (Group A) & REF (Group B) relays. The hardwiring for same must be done accordingly and approved scheme shall be modified if required. Same is applicable for Reactor protection also.
76 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/OC4_1/OC4PTOC1/Str/general SPI TERTIARY 33kV PHASE OVERCURRENT START Y Addition
77 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/OC4_1/OC4PTOC1/Op/general SPI TERTIARY33kV PHASE OVERCURRENT TRIP Y Addition
78 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/EF4_1/EF4PTOC1/Str/general SPI TERTIARY 33kV PHASE EARTHFAULT START Y Addition
79 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/EF4_1/EF4PTOC1/Op/general SPI TERTIARY 33kV PHASE EARTHFAULT TRIP Y Addition
80 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/ROV2_1/ROV2PTOV1/Str/general SPI TERTIARY 33kV PHASE RESIDUAL OVERVOLTAGE START Y Addition
81 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/ROV2_1/ROV2PTOV1/OP/general SPI TERTIARY 33kV PHASE RESIDUAL OVERVOLTAGE TRIP Y Addition
82 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI TERTIARY 33kV 86 OPTD Y Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
83 765kV STNMB1Q01TDIF SPI TERTIARY TRAFO - BUCHHOLZ ALARM Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
84 765kV STNMB1Q01TDIF SPI TERTIARY TRAFO - BUCHHOLZ TRIP Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
85 765kV STNMB1Q01TDIF SPI TERTIARY TRAFO - WTI ALARM Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
86 765kV STNMB1Q01TDIF SPI TERTIARY TRAFO - WTI TRIP Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
87 765kV STNMB1Q01TDIF SPI TERTIARY TRAFO - OTI ALARM Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
88 765kV STNMB1Q01TDIF SPI TERTIARY TRAFO - OTI TRIP Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
89 765kV STNMB1Q01TDIF SPI TERTIARY TRAFO - PRD ALARM Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
90 765kV STNMB1Q01TDIF SPI TERTIARY TRAFO - PRD TRIP Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
91 765kV STNMB1Q01TDIF SPI TERTIARY 33KV_TC-1 FAULTY Y Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
92 765kV STNMB1Q01TDIF SPI TERTIARY 33KV_TC-2 FAULTY Y Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
93 765kV STNMB1Q01TDIF SPI TERTIARY 33kV CB ASSOCIATED ALARMS Y Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
94 765kV STNMB1Q01TDIF SPI RELAY IN TEST MODE Y Addition
95 765kV STNMB1Q01TDIF SPI SETTINGS CHANGED Y Addition
96 765kV STNMB1Q01TDIF SPI DR MEMORY 80% FULL Y Addition
97 765kV STNMB1Q01TDIF CMD DELUGE COMMAND APPLICABLE FOR 3 PHASE TRANSFORMERS Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
98 765kV STNMB1Q01TDIF CMD DELUGE COMMAND R PH APPLICABLE FOR SINGLE PHASE TRANSFORMERS (If a dedicated IED is provided for spare transformer protection, only spare phase signals are required to be used) Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
99 765kV STNMB1Q01TDIF CMD DELUGE COMMAND Y PH Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
100 765kV STNMB1Q01TDIF CMD DELUGE COMMAND B PH Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
101 765kV STNMB1Q01TDIF CMD DELUGE COMMAND SPARE Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
102 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL//EF4_1/EF4PTOC2/Str/general SPI NEUTRAL OVERCURRENT ALARM Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
103 765kV STNMB1Q01TDIF SS_BAY_DIFFERENTIAL//LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
104 765kV STNMB1Q01TDIF SPI SPARE ALARM-2 Y Addition
105 765kV STNMB1Q01TDIF SPI SPARE ALARM-3 Y Addition
106 765kV STNMB1Q01TDIF SPI SPARE ALARM-4 Y Addition
107 765kV STNMB1Q01TDIF SPI SPARE ALARM-5 Y Addition
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR ICT REF RELAYS
IED name: R_RET670_64
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 765kV STNMB1Q01TREF SS_BAY_REF/LD0/OEXPVPH1/Str/general SPI OVEREXCITATION MV START
2 765kV STNMB1Q01TREF SS_BAY_REF/LD0/OEXPVPH1/Alm/stVal SPI OVEREXCITATION MV ALARM Y
3 765kV STNMB1Q01TREF SS_BAY_REF/LD0/OEXPVPH1/Op/general SPI OVEREXCITATION MV TRIP Y
4 765kV STNMB1Q01TREF SS_BAY_REF/LD0/HZPDIF1/Alm/stVal SPI REF ALARM
5 765kV STNMB1Q01TREF SS_BAY_REF/LD0/HZPDIF1/Op/general SPI REF TRIP Y
6 765kV STNMB1Q01TREF SS_BAY_REF/LD0/SMPPTRC1/Op/general SPI REF RELAY GENERAL TRIP Y
7 765kV STNMB1Q01TREF SS_BAY_REF/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
8 765kV STNMB1Q01TREF SS_BAY_REF/LD0/LPHD1/PhyHealth/stVal SPI REF IED UNHEALTHY Y
9 765kV STNMB1Q01TREF SS_BAY_REF/LD0/SP16GGIO n/Ind n/stVal SPI OTI TRIP Y APPLICABLE FOR 3 PHASE TRANSFORMERS
10 765kV STNMB1Q01TREF SPI WTI HV TRIP Y
11 765kV STNMB1Q01TREF SPI WTI MV TRIP Y
12 765kV STNMB1Q01TREF SPI WTI LV TRIP Y
13 765kV STNMB1Q01TREF SPI OSR 2 TRIP Y
14 765kV STNMB1Q01TREF SPI PRD 2 TRIP Y
15 765kV STNMB1Q01TREF SPI BUCCHOLZ_n ALARM Y Text correction
16 765kV STNMB1Q01TREF SPI BUCCHOLZ_n TRIP Y Addition
17 765kV STNMB1Q01TREF SPI OTI R PH TRIP Y APPLICABLE FOR SINGLE PHASE TRANSFORMERS (If a dedicated IED is provided for spare transformer protection, only spare phase signals are required to be used)
18 765kV STNMB1Q01TREF SPI OTI Y PH TRIP Y
19 765kV STNMB1Q01TREF SPI OTI B PH TRIP Y
20 765kV STNMB1Q01TREF SPI OTI SPARE ICT TRIP Y
21 765kV STNMB1Q01TREF SPI WTI HV R PH TRIP Y
22 765kV STNMB1Q01TREF SPI WTI HV Y PH TRIP Y
23 765kV STNMB1Q01TREF SPI WTI HV B PH TRIP Y
24 765kV STNMB1Q01TREF SPI WTI HV SPARE ICT TRIP Y
25 765kV STNMB1Q01TREF SPI WTI MV R PH TRIP Y
26 765kV STNMB1Q01TREF SPI WTI MV Y PH TRIP Y
27 765kV STNMB1Q01TREF SPI WTI MV B PH TRIP Y
28 765kV STNMB1Q01TREF SPI WTI MV SPARE ICT TRIP Y
29 765kV STNMB1Q01TREF SPI WTI IV R PH TRIP Y
30 765kV STNMB1Q01TREF SPI WTI IV Y PH TRIP Y
31 765kV STNMB1Q01TREF SPI WTI IV B PH TRIP Y
32 765kV STNMB1Q01TREF SPI WTI IV SPARE ICT TRIP Y
33 765kV STNMB1Q01TREF SPI BUCCHOLZ R PH ALARM Y
34 765kV STNMB1Q01TREF SPI BUCCHOLZ Y PH ALARM Y
35 765kV STNMB1Q01TREF SPI BUCCHOLZ B PH ALARM Y
36 765kV STNMB1Q01TREF SPI BUCCHOLZ SPARE ICT ALARM Y
37 765kV STNMB1Q01TREF SPI OSR 2 R PH TRIP Y
38 765kV STNMB1Q01TREF SPI OSR 2 Y PH TRIP Y
39 765kV STNMB1Q01TREF SPI OSR 2 B PH TRIP Y
40 765kV STNMB1Q01TREF SPI OSR 2 SPARE ICT TRIP Y
41 765kV STNMB1Q01TREF SPI PRD 2 R PH TRIP Y
42 765kV STNMB1Q01TREF SPI PRD 2 Y PH TRIP Y
43 765kV STNMB1Q01TREF SPI PRD 2 B PH TRIP Y
44 765kV STNMB1Q01TREF SPI PRD 2 SPARE ICT TRIP Y
45 765kV STNMB1Q01TREF SPI DIFFERENTIAL RELAY FAIL Y
46 765kV STNMB1Q01TREF SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
47 765kV STNMB1Q01TREF SPI RELAY IN TEST MODE Y Addition
48 765kV STNMB1Q01TREF SPI SETTINGS CHANGED Y Addition
49 765kV STNMB1Q01TREF SPI DR MEMORY 80% FULL Y Addition
50 765kV STNMB1Q01TREF SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
51 765kV STNMB1Q01TREF SPI SPARE ALARM-2 Y Addition
52 765kV STNMB1Q01TREF SPI SPARE ALARM-3 Y Addition
53 765kV STNMB1Q01TREF SPI SPARE ALARM-4 Y Addition
54 765kV STNMB1Q01TREF SPI SPARE ALARM-5 Y Addition
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR ICT BACKUP HV IMPEDANCE PROTECTION RELAY Additional Relay - Impedance Protection Signals are part of ICT REF PROTECTION RELAY
IED name: R_REL670_21T
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/ZMCAPDIS1/Str/phsA SPI BACKUP IMPEDANCE START, Z1 R PH
2 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/ZMCAPDIS1/Str/phsB SPI BACKUP IMPEDANCE START, Z1 Y PH
3 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMPE/LD0/ZMCAPDIS1/Str/phsC SPI BACKUP IMPEDANCE START, Z1 B PH
4 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS1.Str.general SPI BACKUP IMPEDANCE START BACKUP IMPEDANCE ZONE-1 START Agreed
5 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS1.Op.general SPI BACKUP IMPEDANCE ZONE-1 TRIP Y
6 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/ZMCAPDIS2/Str/phsA SPI BACKUP IMPEDANCE START, Z2 R PH
7 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/ZMCAPDIS2/Str/phsB SPI BACKUP IMPEDANCE START, Z2 Y PH
8 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMPE/LD0/ZMCAPDIS2/Str/phsC SPI BACKUP IMPEDANCE START, Z2 B PH
9 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS2.Str.general SPI BACKUP IMPEDANCE ZONE-2 START
10 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS2.Op.general SPI BACKUP IMPEDANCE ZONE-2 TRIP Y
11 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS3.Str.general SPI BACKUP IMPEDANCE ZONE-3 START
12 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS3.Op.general SPI BACKUP IMPEDANCE ZONE-3 TRIP Y
13 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS4.Str.general SPI BACKUP IMPEDANCE ZONE-4 START
14 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS4.Op.general SPI BACKUP IMPEDANCE ZONE-4 TRIP Y
15 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SMPPTRC1/Op/general SPI BACKUP IMPEDANCE RELAY GENERAL TRIP Y
16 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/OC4_1/OC4PTOC1/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-1 START OC/EF PROTECTION SIGNALS ARE PART OF HV DIRECTIONAL OVERCURRENT & EARTHFAULT PROTECTION RELAY
17 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/OC4_1/OC4PTOC1/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-1 TRIP Y
18 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/EF4_1/EF4PTOC1/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-1 START
19 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/EF4_1/EF4PTOC1/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-1 TRIP Y
20 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/OC4_1/OC4PTOC2/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-2 START
21 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/OC4_1/OC4PTOC2/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-2 TRIP Y
22 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/EF4_1/EF4PTOC2/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-2 START
23 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/EF4_1/EF4PTOC2/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-2 TRIP Y
24 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP 3PH Y
25 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP R PH Y
26 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP Y PH Y
27 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP B PH Y
28 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
29 765kV STNMB1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
30 765kV STNMB1Q01THVBIMP SPI BACKUP IMPEDANCE IED UNHEALTHY Y
31 765kV STNMB1Q01THVBIMP SPI RELAY IN TEST MODE Y
32 765kV STNMB1Q01THVBIMP SPI SETTINGS CHANGED Y
33 765kV STNMB1Q01THVBIMP SPI DR MEMORY 80% FULL Y
34 765kV STNMB1Q01THVBIMP SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
35 765kV STNMB1Q01THVBIMP SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
36 765kV STNMB1Q01THVBIMP SPI SPARE ALARM-2 Y
37 765kV STNMB1Q01THVBIMP SPI SPARE ALARM-3 Y
38 765kV STNMB1Q01THVBIMP SPI SPARE ALARM-4 Y
39 765kV STNMB1Q01THVBIMP SPI SPARE ALARM-5 Y
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR ICT BACKUP IV IMPEDANCE PROTECTION RELAY
IED name: R_REL670_21T
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 765kV SS_BAY_LV BACKUP IMP/LD0/ZMCAPDIS1/Str/phsA SPI BACKUP IMPEDANCE START, Z1 R PH
2 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0/ZMCAPDIS1/Str/phsB SPI BACKUP IMPEDANCE START, Z1 Y PH
3 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMPE/LD0/ZMCAPDIS1/Str/phsC SPI BACKUP IMPEDANCE START, Z1 B PH
4 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0.ZMHPDIS1.Str.general SPI BACKUP IMPEDANCE START BACKUP IMPEDANCE ZONE-1 START Agreed
5 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0.ZMHPDIS1.Op.general SPI BACKUP IMPEDANCE ZONE-1 TRIP Y
6 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0/ZMCAPDIS2/Str/phsA SPI BACKUP IMPEDANCE START, Z2 R PH
7 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0/ZMCAPDIS2/Str/phsB SPI BACKUP IMPEDANCE START, Z2 Y PH
8 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMPE/LD0/ZMCAPDIS2/Str/phsC SPI BACKUP IMPEDANCE START, Z2B PH
9 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0.ZMHPDIS2.Str.general SPI BACKUP IMPEDANCE ZONE-2 START
10 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0.ZMHPDIS2.Op.general SPI BACKUP IMPEDANCE ZONE-2 TRIP Y
11 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0.ZMHPDIS3.Str.general SPI BACKUP IMPEDANCE ZONE-3 START
12 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0.ZMHPDIS3.Op.general SPI BACKUP IMPEDANCE ZONE-3 TRIP Y
13 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0.ZMHPDIS4.Str.general SPI BACKUP IMPEDANCE ZONE-4 START
14 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0.ZMHPDIS4.Op.general SPI BACKUP IMPEDANCE ZONE-4 TRIP Y
15 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0/SMPPTRC1/Op/general SPI BACKUP IMPEDANCE RELAY GENERAL TRIP Y
16 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/OC4_1/OC4PTOC1/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-1 START
17 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/OC4_1/OC4PTOC1/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-1 TRIP Y
18 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/EF4_1/EF4PTOC1/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-1 START
19 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/EF4_1/EF4PTOC1/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-1 TRIP Y
20 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/OC4_1/OC4PTOC2/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-2 START
21 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/OC4_1/OC4PTOC2/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-2 TRIP Y
22 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/EF4_1/EF4PTOC2/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-2 START
23 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/EF4_1/EF4PTOC2/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-2 TRIP Y
24 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP 3PH Y
25 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP R PH Y
26 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP Y PH Y
27 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP B PH Y
28 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
29 765kV STNMB1Q01TLVBIMP SS_BAY_LV BACKUP IMP/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
30 765kV STNMB1Q01TLVBIMP SPI BACKUP IMPEDANCE IED UNHEALTHY Y
31 765kV STNMB1Q01TLVBIMP SPI RELAY IN TEST MODE Y
32 765kV STNMB1Q01TLVBIMP SPI SETTINGS CHANGED Y
33 765kV STNMB1Q01TLVBIMP SPI DR MEMORY 80% FULL Y
34 765kV STNMB1Q01TLVBIMP SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
35 765kV STNMB1Q01TLVBIMP SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
36 765kV STNMB1Q01TLVBIMP SPI SPARE ALARM-2 Y
37 765kV STNMB1Q01TLVBIMP SPI SPARE ALARM-3 Y
38 765kV STNMB1Q01TLVBIMP SPI SPARE ALARM-4 Y
39 765kV STNMB1Q01TLVBIMP SPI SPARE ALARM-5 Y
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR HV DIRECTIONAL OVERCURRENT AND EARTH FAULT RELAYS
IED name: R_REL670_HVBUP
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 765kV STNDB1Q01THBU SS_BAY_HV BACKUP OC EF/OC4_1/OC4PTOC1/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-1 START Text correction
2 765kV STNDB1Q01THBU SS_BAY_HV BACKUP OC EFE/OC4_1/OC4PTOC1/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-1 TRIP Y Text correction
3 765kV STNDB1Q01THBU SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTOC1/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-1 START Text correction
4 765kV STNDB1Q01THBU SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTOC1/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-1 TRIP Y Text correction
5 765kV STNDB1Q01THBU SS_BAY_HV BACKUP OC EF/OC4_1/OC4PTOC2/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-2 START if Non Directional then name has to be replaced with Directional to Non-Directional Addition
6 765kV STNDB1Q01THBU SS_BAY_HV BACKUP OC EF/OC4_1/OC4PTOC2/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-2 TRIP Y Addition
7 765kV STNDB1Q01THBU SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTOC2/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-2 START Addition
8 765kV STNDB1Q01THBU SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTOC2/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-2 TRIP Y Addition
9 765kV STNDB1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
10 765kV STNDB1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/SMPPTRC1/Op/general SPI GENERAL TRIP Y
11 765kV STNDB1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
12 765kV STNDB1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal SPI BACKUP OC/EF IED UNHEALTHY Y
13 765kV STNDB1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
14 765kV STNDB1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
15 765kV STNDB1Q01THBU SPI SETTINGS CHANGED Y Addition
16 765kV STNDB1Q01THBU SPI DR MEMORY 80% FULL Y Addition
17 765kV STNDB1Q01THBU SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
18 765kV STNDB1Q01THBU SPI SPARE ALARM-2 Y Addition
19 765kV STNDB1Q01THBU SPI SPARE ALARM-3 Y Addition
20 765kV STNDB1Q01THBU SPI SPARE ALARM-4 Y Addition
21 765kV STNDB1Q01THBU SPI SPARE ALARM-5 Y Addition
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR LV DIRECTIONAL OVERCURRENT AND EARTH FAULT RELAYS This Protection Signals are part of ICT BACKUP IV IMPEDANCE PROTECTION RELAY
IED name: R_REL670_LVBUP
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 765kV STNMB1Q01TLBU SS_BAY_LV BACKUP OC EF/OC4_1/OC4PTOC1/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-1 START Text correction
2 765kV STNMB1Q01TLBU SS_BAY_LV BACKUP OC EFE/OC4_1/OC4PTOC1/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-1 TRIP Y Text correction
3 765kV STNMB1Q01TLBU SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTOC1/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-1 START Text correction
4 765kV STNMB1Q01TLBU SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTOC1/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-1 TRIP Y Text correction
5 765kV STNMB1Q01TLBU SS_BAY_LV BACKUP OC EF/OC4_1/OC4PTOC2/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-2 START if Non Directional then name has to be replaced with Directional to Non-Directional Addition
6 765kV STNMB1Q01TLBU SS_BAY_LV BACKUP OC EF/OC4_1/OC4PTOC2/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-2 TRIP Y Addition
7 765kV STNMB1Q01TLBU SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTOC2/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-2 START Addition
8 765kV STNMB1Q01TLBU SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTOC2/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-2 TRIP Y Addition
9 765kV STNMB1Q01TLBU SS_BAY_LV BACKUP OC EF/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
10 765kV STNMB1Q01TLBU SS_BAY_LV BACKUP OC EF/LD0/SMPPTRC1/Op/general SPI GENERAL TRIP Y
11 765kV STNMB1Q01TLBU SS_BAY_LV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
12 765kV STNMB1Q01TLBU SS_BAY_LV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal SPI BACKUP OC/EF IED UNHEALTHY Y
13 765kV STNMB1Q01TLBU SS_BAY_LV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
14 765kV STNMB1Q01TLBU SPI SETTINGS CHANGED Y Addition
15 765kV STNMB1Q01TLBU SPI DR MEMORY 80% FULL Y Addition
16 765kV STNMB1Q01TLBU SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR REACTOR DIFFERENTIAL RELAYS
IED name: R_RET670_87R
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Op/general SPI DIFFERENTIAL PROTECTION TRIP Y
2 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION RPH TRIP Y
3 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION YPH TRIP Y
4 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION BPH TRIP Y
5 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/DifAlm/stVal SPI DIFFERENTIAL CURRENT ALARM Y
6 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/general SPI DIFFERENTIAL PROTECTION START
7 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsA SPI DIFFERENTIAL PROTECTION RPH START
8 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsB SPI DIFFERENTIAL PROTECTION YPH START
9 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsC SPI DIFFERENTIAL PROTECTION BPH START
10 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SMPPTRC1/Op/general SPI DIFFERENTIAL RELAY GENERAL TRIP Y
11 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/OpRst/stVal SPI DIFFERENTIAL PROTECTION TRIP (RESTRAINED MODE) Y Addition
12 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/OpUnRst/stVal SPI DIFFERENTIAL PROTECTION TRIP (UNRESTRAINED MODE) Y Addition
13 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Blk2H/stVal SPI DIFFERENTIAL PROTECTION 2nd HARMONIC BLOCK Y Addition
14 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Blk5H/stVal SPI DIFFERENTIAL PROTECTION 5th HARMONIC BLOCK Y Addition
15 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI BUSBAR PROT OPTD Y Addition, Need to discuss Only for DR in RET670, for SCADA to be configured from BBP relay
16 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
17 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI DIFFRENTIAL IED UNHEALTHY Y *
18 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI OTI TRIP Y APPLICABLE FOR 3 PHASE REACTORS Interchanged between Diff. & REF relays
19 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI WTI ALARM Y Already available
20 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI BUCCHOLZ-A TRIP Y Addition
21 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI BUCCHOLZ-B ALARM Y Addition
22 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI PRV-1 TRIP(NO) Y Text correction
23 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI FIRE PROTECTION OPERATED Y Already available
24 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI LOW OIL LEVEL ALARM Y Already available
25 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI PRV-1 TRIP(NC) Y Addition, Need to discuss Yet to be finalized by PGCIL
26 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI FLOW SENSITIVE CONSERVATOR VALVE ALARM Y Addition
27 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI REACTOR MB ALARMS Y Addition
28 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI OTI R PH ALARM Y APPLICABLE FOR SINGLE PHASE REACTORS (If a dedicated IED is provided for spare reactor protection, only spare phase signals are required to be used)
29 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI OTI Y PH ALARM Y
30 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI OTI B PH ALARM Y
31 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI OTI SPARE PH ALARM Y
32 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI WTI R PH ALARM Y
33 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI WTI Y PH ALARM Y
34 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI WTI B PH ALARM Y
35 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI WTI SPARE PH ALARM Y
36 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI BUCCHOLZ_n R PH ALARM Y Interchanged between Diff. & REF relays
37 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI BUCCHOLZ_n Y PH ALARM Y Interchanged between Diff. & REF relays
38 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI BUCCHOLZ_n B PH ALARM Y Interchanged between Diff. & REF relays
39 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI BUCCHOLZ_n SPARE PH ALARM Y Interchanged between Diff. & REF relays
40 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI BUCCHOLZ_n R PH TRIP Y Text correction
41 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI BUCCHOLZ_n Y PH TRIP Y Text correction
42 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI BUCCHOLZ_n B PH TRIP Y Text correction
43 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI BUCCHOLZ_n SPARE PH TRIP Y Text correction
44 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI OSR R PH TRIP Y
45 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI OSR Y PH TRIP Y
46 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI OSR B PH TRIP Y
47 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI OSR SPARE PH TRIP Y
48 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI PRD R PH TRIP Y Yet to be finalized by PGCIL
49 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI PRD Y PH TRIP Y Yet to be finalized by PGCIL
50 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI PRD B PH TRIP Y Yet to be finalized by PGCIL
51 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI PRD SPARE PH TRIP Y
52 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI LOW OIL LEVEL R PH Y
53 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI LOW OIL LEVEL Y PH Y
54 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI LOW OIL LEVEL B PH Y
55 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI LOW OIL LEVEL SPARE PH Y
56 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI FIRE PROTECTION R PH OPERATED Y
57 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI FIRE PROTECTION Y PH OPERATED Y
58 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI FIRE PROTECTION B PH OPERATED Y
59 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI FIRE PROTECTION SPARE OPERATED Y
60 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI TRIP RELAY 86 A HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
61 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI TRIP RELAY 86 B HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
62 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI GR A RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RET670, for SCADA to be configured from BBP relay
63 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI GR B RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RET670, for SCADA to be configured from BBP relay
64 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI GR A RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Available in RET670 (Sig. 62)
65 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI GR B RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Available in RET670 (Sig. 63)
66 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI REF RELAY FAIL Y
67 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI RELAY IN TEST MODE Y Addition
68 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI SETTINGS CHANGED Y Addition
69 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI DR MEMORY 80% FULL Y Addition
70 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
71 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
72 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI SPARE ALARM-2 Y Addition
73 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI SPARE ALARM-3 Y Addition
74 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI SPARE ALARM-4 Y Addition
75 765kV STNMB1Q01LRDIF /STNMB1Q01BRDIF SPI SPARE ALARM-5 Y Addition
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR REACTOR REF RELAYS
IED name: R_RET670_64R
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SS_BAY_REF/LD0/HZPDIF1/Alm/stVal SPI REF ALARM
2 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SS_BAY_REF/LD0/HZPDIF1/Op/general SPI REF TRIP Y
3 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SS_BAY_REF/LD0/SMPPTRC1/Op/general SPI REF RELAY GENERAL TRIP Y
4 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SS_BAY_REF/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
5 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SS_BAY_REF/LD0/LPHD1/PhyHealth/stVal SPI REF IED UNHEALTHY Y
6 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SS_BAY_REF/LD0/SP16GGIO n/Ind n/stVal SPI OTI ALARM Y APPLICABLE FOR 3 PHASE REACTORS Interchanged between Diff. & REF relays
7 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI WTI TRIP Y Already available
8 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI BUCCHOLZ-A ALARM Y Addition
9 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI BUCCHOLZ-B TRIP Y Addition
10 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI PRV-2 TRIP Y Addition
11 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI FIRE PROTECTION OPERATED Y Addition
12 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI HIGH LEVEL OIL ALARM Y Addition
13 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI 86B TRIP RELAY SUPERVSION ALARM Y Addition, Need to discuss
14 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI REACTOR MB ALARMS Y Addition
15 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI OTI R PH TRIP Y APPLICABLE FOR SINGLE PHASE REACTORS (If a dedicated IED is provided for spare Reactor protection, only spare phase signals are required to be used)
16 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI OTI Y PH TRIP Y
17 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI OTI B PH TRIP Y
18 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI OTI SPARE PH TRIP Y
19 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI WTI R PH TRIP Y
20 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI WTI Y PH TRIP Y
21 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI WTI B PH TRIP Y
22 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI WTI SPARE PH TRIP Y
23 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI BUCCHOLZ R PH ALARM Y
24 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI BUCCHOLZ Y PH ALARM Y
25 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI BUCCHOLZ B PH ALARM Y
26 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI BUCCHOLZ SPARE PH ALARM Y
27 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI DIFFERENTIAL RELAY FAIL Y
28 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI RELAY IN TEST MODE Y Addition
29 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI SETTINGS CHANGED Y Addition
30 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI DR MEMORY 80% FULL Y Addition
31 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
32 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI SPARE ALARM-2 Y Addition
33 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI SPARE ALARM-3 Y Addition
34 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI SPARE ALARM-4 Y Addition
35 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI SPARE ALARM-5 Y Addition
36 765kV STNMB1Q01LRREF /STNMB1Q01BRREF SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR REACTOR BACKUP IMPEDANCE PROTECTION RELAY
IED name: R_REL670_21R
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SS_BAY_BUP IMPEDANCE/LD0.ZMHPDIS1.Str.general SPI BACKUP IMPEDANCE START
2 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SS_BAY_BUP IMPEDANCE/LD0.ZMHPDIS1.Op.general SPI BACKUP IMPEDANCE TRIP Y
3 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SS_BAY_BUP IMPEDANCE/LD0/SMPPTRC1/Op/general SPI BACKUP IMPEDANCE RELAY GENERAL TRIP Y
4 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SS_BAY_BUP IMPEDANCE/OC4_1/OC4PTOC1/Str/general SPI BACKUP OVERCURRENT START
5 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SS_BAY_BUP IMPEDANCE/OC4_1/OC4PTOC1/Op/general SPI BACKUP OVERCURRENT TRIP Y
6 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SS_BAY_BUP IMPEDANCE/EF4_1/EF4PTOC1/Str/general SPI BACKUP EARTHFAULT START
7 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SS_BAY_BUP IMPEDANCE/EF4_1/EF4PTOC1/Op/general SPI BACKUP EARTHFAULT TRIP Y
8 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SS_BAY_BUP IMPEDANCE/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
9 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SS_BAY_BUP IMPEDANCE/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
10 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SS_BAY_BUP IMPEDANCE/LD0/LPHD1/PhyHealth/stVal SPI BACKUP IMPEDANCE IED UNHEALTHY Y
11 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SS_BAY_HV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal SPI NGR BUCHHOLZ ALARM Y For Line Reactor NGR associated alarms Addition
12 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI NGR BUCHHOLZ TRIP Y Addition
13 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI NGR OTI ALARM Y Addition
14 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI NGR OTI TRIP Y Addition
15 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI NGR WTI ALARM Y Addition
16 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI NGR WTI TRIP Y Addition
17 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI NGR OSR TRIP Y Addition
18 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI NGR CB ASSOCIATED ALARMS Y All NGC CB associated alarms to be monitored Addition
19 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI NGR BYPASS ISOLATOR ASSOCIATED ALARMS Y All NGR Bypass Isolator associated alarms to be monitored Addition
20 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI BACKUP IMPEDANCE IED UNHEALTHY Y Addition
21 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP CMD NGR BYPASS COMMAND Y Addition
22 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI RELAY IN TEST MODE Y Addition
23 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI SETTINGS CHANGED Y Addition
24 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI DR MEMMORY 80% FULL Y Addition
25 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
26 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
27 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI SPARE ALARM-2 Y Addition
28 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI SPARE ALARM-3 Y Addition
29 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI SPARE ALARM-4 Y Addition
30 765kV STNMB1Q01LRBIMP /STNMB1Q01LRBIMP SPI SPARE ALARM-5 Y Addition
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR BUSBAR PROTECTION RELAYS (DECENTRALIZED) - REB 500
IED name: BB_REB500_87B
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/BCZ_PDIF1/DifAlm SPI BUSBAR CHECKZONE ALARM Y Addition
2 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/BCZ_PDIF1/Op/general SPI BUSBAR CHECKZONE TRIP Y Addition
3 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/CALH1/GrAlm2/stVal SPI BUSBAR CT CIRCUIT ERROR Y Agreed
4 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF1/Op/PhsA SPI BUSBAR ZONE 1 TRIP R- PHASE Y Addition, BUSBAR TRIP R- PHASE is configurable (Zone1/2 phasewise trip signal is not configurable) Agreed
5 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF1/Op/PhsB SPI BUSBAR ZONE 1 TRIP Y- PHASE Y Addition, BUSBAR TRIP Y- PHASE Is configurable (Zone1/2 phasewise trip signal is not configurable) Agreed
6 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF1/Op/PhsC SPI BUSBAR ZONE 1 TRIP B- PHASE Y Addition, BUSBAR TRIP B- PHASE Is configurable (Zone1/2 phasewise trip signal is not configurable) Agreed
7 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF1/Op/general SPI BUSBAR ZONE 1 TRIP Y
8 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/BZ_PDIF1/Blk SPI BUSBAR ZONE 1 BLOCKED Y
9 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI BREAKER FAILURE - BUSBAR 1 BLOCKED Y Addition, Need to discuss (Signal not configurable), Sig. 8 (BUSBAR ZONE 1 BLOCKED) is common blocking signal which will active when busbar blocked from external switch, Isolator intermidiate status, CT Circuit error conditions)
10 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF1/DifAlm SPI BUSBAR ZONE-1 CT CIRCUIT ERROR Y BUSBAR CT CIRCUIT ERROR is configured in Signal No.-03 (Zone1/2 CT CIRCUIT signal not configurable)
11 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI BUSBAR ZONE 1 BLOCKED EXTERNAL BY SWITCH Y
12 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF2/Op/PhsA SPI BUSBAR ZONE 2 TRIP R- PHASE Y Addition, BUSBAR TRIP R- PHASE is configurable (Zone1/2 phasewise trip signal is not configurable)
13 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF2/Op/PhsB SPI BUSBAR ZONE 2 TRIP Y- PHASE Y Addition, BUSBAR TRIP Y- PHASE Is configurable (Zone1/2 phasewise trip signal is not configurable)
14 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF2/Op/PhsC SPI BUSBAR ZONE 2 TRIP B- PHASE Y Addition, BUSBAR TRIP B- PHASE Is configurable (Zone1/2 phasewise trip signal is not configurable)
15 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF2/Op/general SPI BUSBAR ZONE 2 TRIP Y
16 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/BZ_PDIF2/Blk SPI BUSBAR ZONE 2 BLOCKED Y
17 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI BREAKER FAILURE - BUSBAR 2 BLOCKED Y Addition, Need to discuss (Signal not configurable), Sig. 15 (BUSBAR ZONE 2 BLOCKED) is common blocking signal which will active when busbar blocked from external switch, Isolator intermidiate status, CT Circuit error conditions)
18 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF2/DifAlm SPI BUSBAR ZONE-2 CT CIRCUIT ERROR Y BUSBAR CT CIRCUIT ERROR is configured in Signal No.-03 (Zone1/2 CT CIRCUIT signal not configurable)
19 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI BUSBAR ZONE 2 BLOCKED EXTERNAL BY SWITCH Y
20 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/CALH1/GrAlm1/stVal SPI ISOLATOR IN INTERMEDIATE STATUS Y TO BE USED RELATES TO STATUS OF SWITCHING ELEMENT
21 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/PTRC/Tr/general SPI BAY N TRIP Y For each Bays Addition
22 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB0 n/LPHD n/PhyHealth/stVal SPI BUSBAR BLOCKED DUE TO COMMUNICATION ERROR_Bay_n Y For each Bays Addition
23 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/GAPC/Ind08/stVal SPI BAY_N_BREAKER FAILURE R-PH INITIATION Y For each Bays Addition
24 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/GAPC/Ind09/stVal SPI BAY_N_BREAKER FAILURE Y-PH INITIATION Y For each Bays Addition
25 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/GAPC/Ind10/stVal SPI BAY_N_BREAKER FAILURE B-PH INITIATION Y For each Bays Addition
26 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/GAPC/Ind11/stVal SPI BAY_N_BREAKER FAILURE 3PH INITIATION Y For each Bays Addition
27 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/GAPC/Ind04/stVal SPI BAY_N_EXTERNAL BUSBAR ZONE n Y For signals where BB tripped through External Tripping commands(GD, Half Dia) Addition
28 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/RBRF/OpIn/general SPI BAY_N_BREAKER FAILURE RETRIP Y For each Bays Addition
29 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/RBRF/OpEx/general SPI BAY_N_BREAKER FAILURE BACKTRIP Y For each Bays Addition
30 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/RBRF/OpIn/PhsA SPI BAY_N_BREAKER FAILURE RPH- RETRIP Y For each Bays Addition
31 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/RBRF/OpIn/PhsB SPI BAY_N_BREAKER FAILURE YPH- RETRIP Y For each Bays Addition
32 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/RBRF/OpIn/PhsC SPI BAY_N_BREAKER FAILURE BPH- RETRIP Y For each Bays Addition
33 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/LPHD1/PhyHealth/stVal SPI BBP CENTRAL UNIT IED UNHEALTHY Y
34 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
35 765kV STNMB1BBM1 /STNMB1BBM2 SPI SETTINGS CHANGED Y Addition, Need to discuss (Signal not configurable)
36 765kV STNMB1BBM1 /STNMB1BBM2 SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme Addition
37 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-1 Y ** 10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
38 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-2 Y Addition
39 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-3 Y Addition
40 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-4 Y Addition
41 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-5 Y Addition
42 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-6 Y Addition
43 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-7 Y Addition
44 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-8 Y Addition
45 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-9 Y Addition
46 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-10 Y Addition
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR BUSBAR PROTECTION RELAYS (CENTRALIZED) - REB 670
IED name: BB_REB670_87B
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/BBS/BZBSPDIF1/Op/general SPI BUSBAR ZONE 1 TRIP Y BBS - Single Phase & BBT-Three Phase Variant. STNMD1BBM1R/Y/B if phasewise Busbar IEDs are deployed.
2 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/BBS/BZBSPDIF2/Op/general SPI BUSBAR ZONE 2 TRIP Y
3 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/BBS/BZBSPDIF1/OpnCTAlm/stVal SPI BUSBAR ZONE 1 CT CIRCUIT ERROR Y
4 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/BBS/BZBSPDIF2/OpnCTAlm/stVal SPI BUSBAR ZONE 2 CT CIRCUIT ERROR Y
5 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n /Ind n/stVal SPI BUSBAR ZONE 1 BLOCKED EXTERNAL BY SWITCH Y
6 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n /Ind n/stVal SPI BUSBAR ZONE 2 BLOCKED EXTERNAL BY SWITCH Y
7 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n /Ind n/stVal SPI BUSBAR ZONE 1 PROTECTION BLOCKED Y
8 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n /Ind n/stVal SPI BUSBAR ZONE 2 PROTECTION BLOCKED Y
9 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/BBS6/BCZPDIF1/Op/general SPI BUSBAR CHECKZONE TRIP Y
10 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/BBS/BBSPTRC n/Tr/general SPI BAY n TRIP Y **** If Bay Breaker Failure function internally utilised then BFP related Initiation, Retrip, Backtrip & other signal refered with Standalone LBB relay.
11 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n/Ind n/stVal SPI BAY n BREAKER FAILURE BACKUP TRIP Y For each bay signals to be configured and reported Addition
12 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n/Ind n/stVal SPI LCC BUSBAR GAS ZONE TRIP Y IF Applicable for GIS Addition
13 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
14 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/LD0/LPHD1/PhyHealth/stVal SPI BBP IED UNHEALTHY Y
15 765kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
16 765kV STNMB1BBM1 /STNMB1BBM2 SPI SETTINGS CHANGED Y Addition
17 765kV STNMB1BBM1 /STNMB1BBM2 SPI DR MEMMORY 80% FULL Y Addition
18 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-1 Y **10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
19 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-2 Y Addition
20 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-3 Y Addition
21 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-4 Y Addition
22 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-5 Y Addition
23 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-6 Y Addition
24 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-7 Y Addition
25 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-8 Y Addition
26 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-9 Y Addition
27 765kV STNMB1BBM1 /STNMB1BBM2 SPI SPARE ALARM-10 Y Addition
28 765kV STNMB1BBM1 /STNMB1BBM2 SPI BUSBAR ZONE 1 TRIP R- PHASE Y Addition
29 765kV STNMB1BBM1 /STNMB1BBM2 SPI BUSBAR ZONE 1 TRIP Y- PHASE Y Addition
30 765kV STNMB1BBM1 /STNMB1BBM2 SPI BUSBAR ZONE 1 TRIP B- PHASE Y Addition
31 765kV STNMB1BBM1 /STNMB1BBM2 SPI BUSBAR ZONE 2 TRIP R- PHASE Y Addition
32 765kV STNMB1BBM1 /STNMB1BBM2 SPI BUSBAR ZONE 2 TRIP Y- PHASE Y Addition
33 765kV STNMB1BBM1 /STNMB1BBM2 SPI BUSBAR ZONE 2 TRIP B- PHASE Y Addition
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR BREAKER FAILURE PROTECTION RELAY
IED name: R_RELAY NAME_50BFR
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILURE/LD0/GGIO n/ST/ Ind n SPI BREAKER FAILURE PROTECTION START Y
2 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpEx/general SPI BREAKER FAILURE BACKUP TRIP Y Text correction
3 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpIn/general SPI BREAKER FAILURE RETRIP Y
4 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpIn/PhsA SPI BREAKER FAILURE RETRIP RPH Y Addition
5 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpIn/PhsB SPI BREAKER FAILURE RETRIP YPH Y Addition
6 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpIn/PhsC SPI BREAKER FAILURE RETRIP BPH Y Addition
7 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILURE/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
8 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILURE/LD0/LPHD1/PhyHealth/stVal SPI BFP IED UNHEALTHY Y
9 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI BREAKER FAILURE R-PHASE INITIATION FROM M1/M2 Y Addition
10 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI BREAKER FAILURE Y-PHASE INITIATION FROM M1/M2 Y Addition
11 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI BREAKER FAILURE B-PHASE INITIATION FROM M1/M2 Y Addition
12 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI BREAKER FAILURE 3-PHASE INITIATION FROM 86A/86B/BB Y Addition
13 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI BREAKER FAILURE FROM LCC (If applicable) Y Applicable for GIS LCC Addition
14 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI IV GR-A INT TRIP RELAY OPTD (If applicable) Y Applicable for ICT Bays incomers Addition
15 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI IV GR-B INT TRIP RELAY OPTD (If applicable) Y Addition
17 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
18 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI SETTINGS CHANGED Y Addition
19 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI DR MEMMORY 80% FULL Y Addition
20 765kV STNMB1Q01BFR SS_BAY_BREAKER FAILURE/LD0/SP16GGIO n/Ind n/stVal SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
21 765kV STNMB1Q01BFR SPI SPARE ALARM-1 Y ** 10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
22 765kV STNMB1Q01BFR SPI SPARE ALARM-2 Y Addition
23 765kV STNMB1Q01BFR SPI SPARE ALARM-3 Y Addition
24 765kV STNMB1Q01BFR SPI SPARE ALARM-4 Y Addition
25 765kV STNMB1Q01BFR SPI SPARE ALARM-5 Y Addition
26 765kV STNMB1Q01BFR SPI SPARE ALARM-6 Y Addition
27 765kV STNMB1Q01BFR SPI SPARE ALARM-7 Y Addition
28 765kV STNMB1Q01BFR SPI SPARE ALARM-8 Y Addition
29 765kV STNMB1Q01BFR SPI SPARE ALARM-9 Y Addition
30 765kV STNMB1Q01BFR SPI SPARE ALARM-10 Y Addition
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR BAY CONTROL UNIT
IED name: R_REC670_BCU
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS ADDITIONAL REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/QCBAY1/LocSwPos/stVal INT BCU IN LOCAL/ REMOTE
2 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/Op/general SPI CLOSE COMMAND FROM BCU FOR AUTORECLOSE FOR BCUs HAVING AUTORECLSOURE FUNCTION INBUILT
3 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI GR-A TRIP RELAY FAULTY Y Addition
4 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI GR-B TRIP RELAY FAULTY Y Addition
5 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI DT RECEIVE CHANNEL-1 Y Addition, Available in REL670 Only for DR in REL670, for SCADA to be configured from BCU
6 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI DT RECEIVE CHANNEL-2 Y Addition, Available in REL670 Only for DR in REL670, for SCADA to be configured from BCU
7 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/AutoRecSt/StVal SPI AUTORECLOSE FUNCTION ON Y Addition
8 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/AutoRecSt/StVal SPI AUTORECLOSE FUNCTION OFF Y Addition
9 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI START AUTORECLOSE FUNCTION Y Addition
10 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/BlkRec/stVal SPI BLOCK AUTORECLOSE FUNCTION Y
11 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/Prp3PhOp/stVal SPI PREPARE 3PH TRIP AUTORECLOSE Y
12 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/RdyRec/stVal SPI AUTORECLOSE FUNCTION READY Text correction
13 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/ActRec/stVal SPI AUTORECLOSE IN PROGRESS Y Text correction
14 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/SucRec/stVal SPI AUTORECLOSE SUCCESSFUL Y Text correction
15 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/UnsRec/stVal SPI AUTORECLOSE UNSUCCESSFUL Y Text correction
16 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SXCBR1/Pos/stVal DPI BAY_CB R PH POSITION
17 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SXCBR2/Pos/stVal DPI BAY_CB Y PH POSITION
18 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SXCBR3/Pos/stVal DPI BAY_CB B PH POSITION
19 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI1/Pos/stVal DPI BAY_CB POSITION
20 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI1/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI1/Pos/ctlOperOn for Close CMD BAY_CB_COMMAND CLOSE / OPEN
21 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO1/EnaOpn/stVal SPI BAY_CB_OPEN PERMITTED OR ENABLED
22 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO1/EnaCls/stVal SPI BAY_CB_CLOSE PERMITTED OR ENABLED
23 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI2/Pos/stVal DPI BAY_89A_ISOLATOR POSITION
24 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI2/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI2/Pos/ctlOperOn for Close CMD BAY_89A_ISO COMMAND CLOSE / OPEN
25 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO2/EnaOpn/stVal SPI BAY_89A_ISO OPEN PERMITTED OR ENABLED
26 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO2/EnaCls/stVal SPI BAY_89A_ISO CLOSE PERMITTED OR ENABLED
27 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI3/Pos/stVal DPI BAY_89AE/AE1_ISOLATOR POSITION
28 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI3/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI3/Pos/ctlOperOn for Close CMD BAY_89AE/AE1_ISO COMMAND CLOSE / OPEN
29 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO3/EnaOpn/stVal SPI BAY_89AE/AE1_ISO OPEN PERMITTED OR ENABLED
30 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO3/EnaCls/stVal SPI BAY_89AE/AE1_ISO CLOSE PERMITTED OR ENABLED
31 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI4/Pos/stVal DPI BAY_89B_ISOLATOR POSITION
32 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI4/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI4/Pos/ctlOperOn for Close CMD BAY_89B_ISO COMMAND CLOSE / OPEN
33 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO4/EnaOpn/stVal SPI BAY_89B_ISO OPEN PERMITTED OR ENABLED
34 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO4/EnaCls/stVal SPI BAY_89B_ISO CLOSE PERMITTED OR ENABLED
35 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI5/Pos/stVal DPI BAY_89BE/BE1_ISOLATOR POSITION
36 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI5/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI5/Pos/ctlOperOn for Close CMD BAY_89BE/BE1_ISO COMMAND CLOSE / OPEN
37 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO5/EnaOpn/stVal SPI BAY_89BE/BE1_ISO OPEN PERMITTED OR ENABLED
38 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO5/EnaCls/stVal SPI BAY_89BE/BE1_ISO CLOSE PERMITTED OR ENABLED
39 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI6/Pos/stVal DPI BAY_89L/T/BR_ISOLATOR POSITION FOR 3 PHASE TRANSFORMERS & REACTORS CSWI6 MAY BE USED FOR 89T/BR, BUT FOR SINGLE PHASE TRANSFORMERS & REACTORS SAME HAS BEEN SEPARATELY MENTIONED
40 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI6/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI6/Pos/ctlOperOn for Close CMD BAY_89L/T/BR_ISO COMMAND CLOSE / OPEN
41 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO6/EnaOpn/stVal SPI BAY_89L/T/BR_ISO OPEN PERMITTED OR ENABLED
42 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO6/EnaCls/stVal SPI BAY_89L/T/BR_ISO CLOSE PERMITTED OR ENABLED
43 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI7/Pos/stVal DPI BAY_89LE/TE/BRE_ISOLATOR POSITION FOR 3 PHASE TRANSFORMERS & REACTORS CSWI7 MAY BE USED FOR 89TE/BRE, BUT FOR SINGLE PHASE PHASE TRANSFORMERS & REACTORS SAME HAS BEEN SEPARATELY MENTIONED
44 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI7/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI7/Pos/ctlOperOn for Close CMD BAY_89LE/TE/BRE_ISO COMMAND CLOSE / OPEN
45 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO7/EnaOpn/stVal SPI BAY_89LE/TE/BRE_ISO OPEN PERMITTED OR ENABLED
46 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO7/EnaCls/stVal SPI BAY_89LE/TE/BRE_ISO CLOSE PERMITTED OR ENABLED
47 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI8/Pos/stVal DPI BAY_89LR/89C_ISOLATOR POSITION FOR 3 PHASE LINE REACTORS CSWI8 MAY BE USED FOR 89LR, BUT FOR SINGLE PHASE LINE REACTORS SAME HAS BEEN SEPARATELY MENTIONED
48 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI8/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI8/Pos/ctlOperOn for Close CMD BAY_89LR/89C_ISO COMMAND CLOSE / OPEN
49 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO8/EnaOpn/stVal SPI BAY_89LR/89C_ISO OPEN PERMITTED OR ENABLED
50 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO8/EnaCls/stVal SPI BAY_89LR/89C_ISO CLOSE PERMITTED OR ENABLED
51 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI9/Pos/stVal DPI BAY_89LRE_ISOLATOR POSITION FOR 3 PHASE LINE REACTORS CSWI9 MAY BE USED FOR 89LRE, BUT FOR SINGLE PHASE LINE REACTORS SAME HAS BEEN SEPARATELY MENTIONED
52 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI9/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI9/Pos/ctlOperOn for Close CMD BAY_89LRE_ISO COMMAND CLOSE / OPEN
53 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO9/EnaOpn/stVal SPI BAY_89LRE_ISO OPEN PERMITTED OR ENABLED
54 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO9/EnaCls/stVal SPI BAY_89LRE_ISO CLOSE PERMITTED OR ENABLED
55 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI10/Pos/stVal DPI BAY_89BRS1&2_ISOLATOR POSITION FOR 3 PHASE BUS & LINE REACTORS CSWI10 MAY BE USED FOR 89BRS1&2, BUT FOR SINGLE PHASE TRANSFORMERS SAME HAS BEEN SEPARATELY MENTIONED
56 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI10Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI10/Pos/ctlOperOn for Close CMD BAY_89BRS1&2_ISO COMMAND CLOSE / OPEN
57 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO10/EnaOpn/stVal SPI BAY_89BRS1&2_ISO OPEN PERMITTED OR ENABLED
58 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO10/EnaCls/stVal SPI BAY_89BRS1&2_ISO CLOSE PERMITTED OR ENABLED
59 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI11/Pos/stVal DPI BAY_89BRS1E_ISOLATOR POSITION FOR 3 PHASE TRANSFORMERS & REACTORS CSWI11 MAY BE USED FOR 89BRS1E, BUT FOR SINGLE PHASE TRANSFORMERS SAME HAS BEEN SEPARATELY MENTIONED
60 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI11/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI11/Pos/ctlOperOn for Close CMD BAY_89BRS1E_ISO COMMAND CLOSE / OPEN
61 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO11/EnaOpn/stVal SPI BAY_89BRS1E_ISO OPEN PERMITTED OR ENABLED
62 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO11/EnaCls/stVal SPI BAY_89BRS1E_ISO CLOSE PERMITTED OR ENABLED
63 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI12/Pos/stVal DPI BAY_89AE2/BE2_ISOLATOR POSITION USED FOR BUS EARTH SWITCH OF ISOLATOR, WHEN BUS EARTH SWITCH (89AE2/BE2) IS PROVIDED
64 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI12/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI12/Pos/ctlOperOn for Close CMD BAY_89AE2/BE2_ISO COMMAND CLOSE / OPEN
65 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO12/EnaOpn/stVal SPI BAY_89AE2/BE2_ISO OPEN PERMITTED OR ENABLED
66 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SCILO12/EnaCls/stVal SPI BAY_89AE2/BE2_ISO CLOSE PERMITTED OR ENABLED
THE LOGICAL NODE INSTANCE NUMBER (SCSWIn/SCILOn) FOR BUS EARTH SWITCHES, ISOLATOR & EARTHSWITCHES FOR 3 PH/1PH REACTORS & ITCs, e.g 89 BR, BRE, LR, LRE, RS1, RS2, RS1E, 89T,TE, 89AE2, 89BE2 MAY BE ASSIGNED AS PER AVAILABILITY
67 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
68 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/LPHD1/PhyHealth/stVal SPI BCU UNHEALTHY Y
69 765kV STNMB1Q01BNMBCU SS_BAY_BCU/SES_1/SESRSYN2/Rel/stVal SPI CONDITIONS OK FOR SYNCHRONIZATION
70 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI APPLICABLE FOR ONE AND HALF CIRCUIT BREAKER
71 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI SPRING DISCHARGED Y FOR SPRING MECHANISM CBs ANNUNCIATION FOR CIRCUIT BREAKER
72 765kV STNMB1Q01BNMBCU SPI AC MOTOR SUPPLY FAIL Y
73 765kV STNMB1Q01BNMBCU SPI SF6 GAS LOW Y
74 765kV STNMB1Q01BNMBCU SPI OPERATION LOCKED OUT Y
75 765kV STNMB1Q01BNMBCU SPI CB READY FOR AUTORECLOSURE Y
76 765kV STNMB1Q01BNMBCU SPI DC SUPPLY FAIL Y
77 765kV STNMB1Q01BNMBCU SPI TC-1 FAIL Y
78 765kV STNMB1Q01BNMBCU SPI TC-2 FAIL Y
79 765kV STNMB1Q01BNMBCU SPI TRIP RELAY 86 A FAULTY (SUPERVISION) Y Addition
80 765kV STNMB1Q01BNMBCU SPI TRIP RELAY 86 B FAULTY (SUPERVISION) Y Addition
81 765kV STNMB1Q01BNMBCU SPI TC-1 FAULTY R-PH Y Addition
82 765kV STNMB1Q01BNMBCU SPI TC-1 FAULTY Y-PH Y Addition
83 765kV STNMB1Q01BNMBCU SPI TC-1 FAULTY B-PH Y Addition
84 765kV STNMB1Q01BNMBCU SPI TC-2 FAULTY R-PH Y Addition
85 765kV STNMB1Q01BNMBCU SPI TC-2 FAULTY Y-PH Y Addition
86 765kV STNMB1Q01BNMBCU SPI TC-2 FAULTY B-PH Y Addition
87 765kV STNMB1Q01BNMBCU SPI DT RECEIVE CH-1 Y Available in REC670 (Sig. 5) Agreed
88 765kV STNMB1Q01BNMBCU SPI DT RECEIVE CH-2 Y Available in REC670 (Sig. 6) Agreed
89 765kV STNMB1Q01BNMBCU SPI CB MANUAL TRIP CMD Y Addition
90 765kV STNMB1Q01BNMBCU SPI CB MANUAL CLOSE CMD Y Addition
91 765kV STNMB1Q01BNMBCU SPI START A/R Y Addition
92 765kV STNMB1Q01BNMBCU SPI BLOCK A/R Y Addition
93 765kV STNMB1Q01BNMBCU SPI PREPARE 3PH TRIP Y Addition, Available in REC670 (Sig. 11) Agreed
94 765kV STNMB1Q01BNMBCU SPI BUSBAR PROTN OPTD Y Addition
95 765kV STNMB1Q01BNMBCU SPI S.A. COUNTER R-PH Y Addition As per CRP scheme will be configured in BCU/Protection relay 0
96 765kV STNMB1Q01BNMBCU SPI S.A. COUNTER Y-PH Y Addition As per CRP scheme will be configured in BCU/Protection relay
97 765kV STNMB1Q01BNMBCU SPI S.A. COUNTER B-PH Y Addition As per CRP scheme will be configured in BCU/Protection relay
98 765kV STNMB1Q01BNMBCU SPI INCOMER DC-1 FAIL Y Addition
99 765kV STNMB1Q01BNMBCU SPI INCOMER DC-2 FAIL Y Addition
100 765kV STNMB1Q01BNMBCU SPI POLE DISCREPANCY RELAY OPTD Y
101 765kV STNMB1Q01BNMBCU SPI COMPRESSOR SUPPLY FAIL Y FOR HYDRAULLIC MECHANISM CBs
102 765kV STNMB1Q01BNMBCU SPI AIR PRESSURE LOW Y
103 765kV STNMB1Q01BNMBCU SPI COMPRESSOR RUN TIME SUPERVISION Y
104 765kV STNMB1Q01BNMBCU SPI CB R-PH RECLOSE ALARM Y Addition
105 765kV STNMB1Q01BNMBCU SPI CB Y-PH RECLOSE ALARM Y Addition
106 765kV STNMB1Q01BNMBCU SPI CB B-PH RECLOSE ALARM Y Addition
107 765kV STNMB1Q01BNMBCU SPI CSD OPERATION LIMIT ALARM WHEN OPENING Y Addition
108 765kV STNMB1Q01BNMBCU SPI CSD OPERATION LIMIT ALARM WHEN CLOSING Y Addition
109 765kV STNMB1Q01BNMBCU SPI CSD GROUP ALARM Y Addition
110 765kV STNMB1Q01BNMBCU SPI CSD RESERVED Y Addition
111 765kV STNMB1Q01BNMBCU SPI CSD SYNCHROTEQ IN LOCAL MODE Y Addition
112 765kV STNMB1Q01BNMBCU SPI CSD CB INTERFACE ALARM Y Addition
113 765kV STNMB1Q01BNMBCU SPI CSD SENSOR ALARM Y Addition
114 765kV STNMB1Q01BNMBCU SPI CSD IN Y Addition
115 765kV STNMB1Q01BNMBCU SPI CSD BYPASS Y Addition
116 765kV STNMB1Q01BNMBCU SPI CSD FAIL Y
117 765kV STNMB1Q01BNMBCU SPI ICT/REACTOR-n R PH OUT OF SERVICE Y Single phase ICT/Reactor OUT of service & Spare reactor out of service information Addition
118 765kV STNMB1Q01BNMBCU SPI ICT/REACTOR-n Y PH OUT OF SERVICE Y Addition
119 765kV STNMB1Q01BNMBCU SPI ICT/REACTOR-n B PH OUT OF SERVICE Y Addition
120 765kV STNMB1Q01BNMBCU SPI ICT/REACTOR SPARE PH IN SERVICE IN ICT/REACTOR-N Y Addition
121 765kV STNMB1Q01BNMBCU SPI BUS-1 VT RESET VT SELECTION FOR TRANSFORMER & REACTOR
122 765kV STNMB1Q01BNMBCU SPI BUS-2 VT RESET
123 765kV STNMB1Q01BNMBCU SPI LINE VT RESET
124 765kV STNMB1Q01BNMBCU SPI BUS-1 VT SELECTED
125 765kV STNMB1Q01BNMBCU SPI BUS-2 VT SELECTED
126 765kV STNMB1Q01BNMBCU SPI LINE VTSELECTED
127 765kV STNMB1Q01BNMBCU SPI GAS COMPARTMENT n Alarm Stage n Y Stage 1 to n as per scheme ANNUNCIATION FOR GIS BAYS
128 765kV STNMB1Q01BNMBCU SPI LCC PANEL AC SUPPLY FAIL Y
129 765kV STNMB1Q01BNMBCU SPI LCC PANEL DC SUPPLY FAIL Y
130 765kV STNMB1Q01BNMBCU SPI SELECTOR SWITCH POSITION LOCAL/REMOTE Y
131 765kV STNMB1Q01BNMBCU SPI BUS VT MCB TRIP Y FOR BCUs HAVING BUS VT INPUT
132 765kV STNMB1Q01BNMBCU SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
133 765kV STNMB1Q01BNMBCU SPI RELAY IN TEST MODE Y Addition
134 765kV STNMB1Q01BNMBCU SPI SETTINGS CHANGED Y Addition
135 765kV STNMB1Q01BNMBCU SPI DR MEMMORY 80% FULL Y Addition
136 765kV STNMB1Q01BNMBCU SS_BAY_BCU/MON/CMMXU1/A/phsA/cVal/mag AI CURRENT L1 Addition
137 765kV STNMB1Q01BNMBCU SS_BAY_BCU/MON/CMMXU1/A/phsB/cVal/mag AI CURRENT L2 Addition
138 765kV STNMB1Q01BNMBCU SS_BAY_BCU/MON/CMMXU1/A/phsC/cVal/mag AI CURRENT L3 Addition
139 765kV STNMB1Q01BNMBCU SS_BAY_BCU/MON/VMMXU1/PPV/phsAB/cVal/mag AI VOLTAGE U12 Addition
140 765kV STNMB1Q01BNMBCU SS_BAY_BCU/MON/VMMXU1/PPV/phsBC/cVal/mag AI VOLTAGE U23 Addition
141 765kV STNMB1Q01BNMBCU SS_BAY_BCU/MON/VMMXU1/PPV/phsCA/cVal/mag AI VOLTAGE U31 Addition
142 765kV STNMB1Q01BNMBCU SS_BAY_BCU/MON/CVMMXN1/Watt/mag AI ACTIVE POWER (P) Addition
143 765kV STNMB1Q01BNMBCU SS_BAY_BCU/MON/CVMMXN1/VolAmpr/mag AI REACTIVE POWER (Q) Addition
144 765kV STNMB1Q01BNMBCU SS_BAY_BCU/MON/CVMMXN1/PwrFact/mag AI POWER FACTOR (PF) Addition
145 765kV STNMB1Q01BNMBCU SS_BAY_BCU/MON/CVMMXN1/PwrFact/mag AI FREQUENCY (HZ) Addition
146 765kV STNMB1Q01BNMBCU SS_BAY_BCUMON/L4UFCNTn/CntVal/actVal AI S.A. COUNTER R-PH Available in REC670 (Sig. 95) Agreed
147 765kV STNMB1Q01BNMBCU AI S.A. COUNTER Y-PH Available in REC670 (Sig. 95) Agreed
148 765kV STNMB1Q01BNMBCU AI S.A. COUNTER B-PH Available in REC670 (Sig. 95) Agreed
149 765kV STNMB1Q01BNMBCU SS_BAY_BCU/MON/MVGAPC/AnIn_n/mag AI TAP POSITION R PH Addition
150 765kV STNMB1Q01BNMBCU AI TAP POSITION Y PH Addition
151 765kV STNMB1Q01BNMBCU AI TAP POSITION B PH Addition
152 765kV STNMB1Q01BNMBCU AI WTI HV R PH Addition
153 765kV STNMB1Q01BNMBCU AI WTI IV R PH Addition
154 765kV STNMB1Q01BNMBCU AI WTI LV R PH Addition
155 765kV STNMB1Q01BNMBCU AI OTI R PH Addition
156 765kV STNMB1Q01BNMBCU AI WTI HV Y PH Addition
157 765kV STNMB1Q01BNMBCU AI WTI IV Y PH Addition
158 765kV STNMB1Q01BNMBCU AI WTI LV Y PH Addition
159 765kV STNMB1Q01BNMBCU AI OTI Y PH Addition
160 765kV STNMB1Q01BNMBCU AI WTI HV B PH Addition
161 765kV STNMB1Q01BNMBCU AI WTI IV B PH Addition
162 765kV STNMB1Q01BNMBCU AI WTI LV B PH Addition
163 765kV STNMB1Q01BNMBCU AI OTI B PH Addition
164 765kV STNMB1Q01BNMBCU SS_BAY_BCUMON/L4UFCNTn/CntVal/actVal AI BREAKER R-PHASE OPERATION COUNTER Addition
165 765kV STNMB1Q01BNMBCU AI BREAKER Y-PHASE OPERATION COUNTER Addition
166 765kV STNMB1Q01BNMBCU AI BREAKER B-PHASE OPERATION COUNTER Addition
167 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI RPH MOG LOW OIL LEVEL ALARM Y FOR 3Phase TRANSFORMER, INPUTS CAN BE DISTRIBUTED TO ANY IED. BUTSIGNAL SHOULD BE AS PER TRANSFORMER AVIALABLE SIGNAL Addition
168 765kV STNMB1Q01BNMBCU SPI YPH MOG LOW OIL LEVEL ALARM Y Addition
169 765kV STNMB1Q01BNMBCU SPI BPH MOG LOW OIL LEVEL ALARM Y Addition
170 765kV STNMB1Q01BNMBCU SPI SP-PH MOG LOW OIL LEVEL ALARM Y Addition
171 765kV STNMB1Q01BNMBCU SPI RPH MOG HIGH OIL LEVEL ALARM Y Addition
172 765kV STNMB1Q01BNMBCU SPI YPH MOG HIGH OIL LEVEL ALARM Y Addition
173 765kV STNMB1Q01BNMBCU SPI BPH MOG HIGH OIL LEVEL ALARM Y Addition
174 765kV STNMB1Q01BNMBCU SPI SP-PH MOG HIGH OIL LEVEL ALARM Y Addition
175 765kV STNMB1Q01BNMBCU SPI R-PH OIL FLOW SENSITIVE VALVE ALARM Y Addition
176 765kV STNMB1Q01BNMBCU SPI Y-PH OIL FLOW SENSITIVE VALVE ALARM Y Addition
177 765kV STNMB1Q01BNMBCU SPI B-PH OIL FLOW SENSITIVE VALVE ALARM Y Addition
178 765kV STNMB1Q01BNMBCU SPI SP-PH OIL FLOW SENSITIVE VALVE ALARM Y Addition
179 765kV STNMB1Q01BNMBCU SPI RPH PUMP FAIL - BANK A Y Addition
180 765kV STNMB1Q01BNMBCU SPI RPH PUMP FAIL - BANK B Y Addition
181 765kV STNMB1Q01BNMBCU SPI RPH PUMP FAIL - BANK C Y Addition
182 765kV STNMB1Q01BNMBCU SPI RPH PUMP FAIL - BANK D Y Addition
183 765kV STNMB1Q01BNMBCU SPI YPH PUMP FAIL - BANK A Y Addition
184 765kV STNMB1Q01BNMBCU SPI YPH PUMP FAIL - BANK B Y Addition
185 765kV STNMB1Q01BNMBCU SPI YPH PUMP FAIL - BANK C Y Addition
186 765kV STNMB1Q01BNMBCU SPI YPH PUMP FAIL - BANK D Y Addition
187 765kV STNMB1Q01BNMBCU SPI BPH PUMP FAIL - BANK A Y Addition
188 765kV STNMB1Q01BNMBCU SPI BPH PUMP FAIL - BANK B Y Addition
189 765kV STNMB1Q01BNMBCU SPI BPH PUMP FAIL - BANK C Y Addition
190 765kV STNMB1Q01BNMBCU SPI BPH PUMP FAIL - BANK D Y Addition
191 765kV STNMB1Q01BNMBCU SPI SPH PUMP FAIL - BANK A Y Addition
192 765kV STNMB1Q01BNMBCU SPI SPH PUMP FAIL - BANK B Y Addition
193 765kV STNMB1Q01BNMBCU SPI SPH PUMP FAIL - BANK C Y Addition
194 765kV STNMB1Q01BNMBCU SPI SPH PUMP FAIL - BANK D Y Addition
195 765kV STNMB1Q01BNMBCU SPI RPH THERMAL OVERLOAD TRIP - BANK A Y Addition
196 765kV STNMB1Q01BNMBCU SPI RPH THERMAL OVERLOAD TRIP - BANK B Y Addition
197 765kV STNMB1Q01BNMBCU SPI RPH THERMAL OVERLOAD TRIP - BANK C Y Addition
198 765kV STNMB1Q01BNMBCU SPI RPH THERMAL OVERLOAD TRIP - BANK D Y Addition
199 765kV STNMB1Q01BNMBCU SPI YPH THERMAL OVERLOAD TRIP - BANK A Y Addition
200 765kV STNMB1Q01BNMBCU SPI YPH THERMAL OVERLOAD TRIP - BANK B Y Addition
201 765kV STNMB1Q01BNMBCU SPI YPH THERMAL OVERLOAD TRIP - BANK C Y Addition
202 765kV STNMB1Q01BNMBCU SPI YPH THERMAL OVERLOAD TRIP - BANK D Y Addition
203 765kV STNMB1Q01BNMBCU SPI BPH THERMAL OVERLOAD TRIP - BANK A Y Addition
204 765kV STNMB1Q01BNMBCU SPI BPH THERMAL OVERLOAD TRIP - BANK B Y Addition
205 765kV STNMB1Q01BNMBCU SPI BPH THERMAL OVERLOAD TRIP - BANK C Y Addition
206 765kV STNMB1Q01BNMBCU SPI BPH THERMAL OVERLOAD TRIP - BANK D Y Addition
207 765kV STNMB1Q01BNMBCU SPI SPH THERMAL OVERLOAD TRIP - BANK A Y Addition
208 765kV STNMB1Q01BNMBCU SPI SPH THERMAL OVERLOAD TRIP - BANK B Y Addition
209 765kV STNMB1Q01BNMBCU SPI SPH THERMAL OVERLOAD TRIP - BANK C Y Addition
210 765kV STNMB1Q01BNMBCU SPI SPH THERMAL OVERLOAD TRIP - BANK D Y Addition
211 765kV STNMB1Q01BNMBCU SPI RPH LOW OIL FLOW/REVERSE FLOW - BANK A Y Addition
212 765kV STNMB1Q01BNMBCU SPI RPH LOW OIL FLOW/REVERSE FLOW - BANK B Y Addition
213 765kV STNMB1Q01BNMBCU SPI RPH LOW OIL FLOW/REVERSE FLOW - BANK C Y Addition
214 765kV STNMB1Q01BNMBCU SPI RPH LOW OIL FLOW/REVERSE FLOW - BANK D Y Addition
215 765kV STNMB1Q01BNMBCU SPI YPH LOW OIL FLOW/REVERSE FLOW - BANK A Y Addition
216 765kV STNMB1Q01BNMBCU SPI YPH LOW OIL FLOW/REVERSE FLOW - BANK B Y Addition
217 765kV STNMB1Q01BNMBCU SPI YPH LOW OIL FLOW/REVERSE FLOW - BANK C Y Addition
218 765kV STNMB1Q01BNMBCU SPI YPH LOW OIL FLOW/REVERSE FLOW - BANK D Y Addition
219 765kV STNMB1Q01BNMBCU SPI BPH LOW OIL FLOW/REVERSE FLOW - BANK A Y Addition
220 765kV STNMB1Q01BNMBCU SPI BPH LOW OIL FLOW/REVERSE FLOW - BANK B Y Addition
221 765kV STNMB1Q01BNMBCU SPI BPH LOW OIL FLOW/REVERSE FLOW - BANK C Y Addition
222 765kV STNMB1Q01BNMBCU SPI BPH LOW OIL FLOW/REVERSE FLOW - BANK D Y Addition
223 765kV STNMB1Q01BNMBCU SPI SPH LOW OIL FLOW/REVERSE FLOW - BANK A Y Addition
224 765kV STNMB1Q01BNMBCU SPI SPH LOW OIL FLOW/REVERSE FLOW - BANK B Y Addition
225 765kV STNMB1Q01BNMBCU SPI SPH LOW OIL FLOW/REVERSE FLOW - BANK C Y Addition
226 765kV STNMB1Q01BNMBCU SPI SPH LOW OIL FLOW/REVERSE FLOW - BANK D Y Addition
227 765kV STNMB1Q01BNMBCU SPI RPH COOLER CONTROL SUPPLY FAIL Y Addition
228 765kV STNMB1Q01BNMBCU SPI YPH COOLER CONTROL SUPPLY FAIL Y Addition
229 765kV STNMB1Q01BNMBCU SPI BPH COOLER CONTROL SUPPLY FAIL Y Addition
230 765kV STNMB1Q01BNMBCU SPI SPH COOLER CONTROL SUPPLY FAIL Y Addition
231 765kV STNMB1Q01BNMBCU SPI RPH SUPPLY CHANGE OVER FAIL Y Addition
232 765kV STNMB1Q01BNMBCU SPI YPH SUPPLY CHANGE OVER FAIL Y Addition
233 765kV STNMB1Q01BNMBCU SPI BPH SUPPLY CHANGE OVER FAIL Y Addition
234 765kV STNMB1Q01BNMBCU SPI SPH SUPPLY CHANGE OVER FAIL Y Addition
235 765kV STNMB1Q01BNMBCU SPI RPH SUPPLY - A FAIL Y Addition
236 765kV STNMB1Q01BNMBCU SPI YPH SUPPLY - A FAIL Y Addition
237 765kV STNMB1Q01BNMBCU SPI BPH SUPPLY - A FAIL Y Addition
238 765kV STNMB1Q01BNMBCU SPI SPH SUPPLY - A FAIL Y Addition
239 765kV STNMB1Q01BNMBCU SPI RPH SUPPLY - B FAIL Y Addition
240 765kV STNMB1Q01BNMBCU SPI YPH SUPPLY - B FAIL Y Addition
241 765kV STNMB1Q01BNMBCU SPI BPH SUPPLY - B FAIL Y Addition
242 765kV STNMB1Q01BNMBCU SPI SPH SUPPLY - B FAIL Y Addition
243 765kV STNMB1Q01BNMBCU SPI RPH OLTC MOTOR OVERLOAD Y Addition
244 765kV STNMB1Q01BNMBCU SPI RPH TAP CHANGE IN PROGRESS Y Addition
245 765kV STNMB1Q01BNMBCU SPI RPH TAP CHANGE IN COMPLETE Y Addition
246 765kV STNMB1Q01BNMBCU SPI RPH OLTC IN LOCAL Y Addition
247 765kV STNMB1Q01BNMBCU SPI RPH OLTC IN REMOTE Y Addition
248 765kV STNMB1Q01BNMBCU SPI RPH TAP CHANGE CONTROL SUPPLY FAIL Y Addition
249 765kV STNMB1Q01BNMBCU SPI RPH LOWEST POSITION REACHDED Y Addition
250 765kV STNMB1Q01BNMBCU SPI RPH HIGHESHT POSITION REACHDED Y Addition
251 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SPC1CGGIO n/ctlOpen CMD RPH OLTC RAISE COMMAND Y Addition
252 765kV STNMB1Q01BNMBCU CMD RPH OLTC LOWER COMMAND Y Addition
253 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI YPH OLTC MOTOR OVERLOAD Y Addition
254 765kV STNMB1Q01BNMBCU SPI YPH TAP CHANGE IN PROGRESS Y Addition
255 765kV STNMB1Q01BNMBCU SPI YPH TAP CHANGE IN COMPLETE Y Addition
256 765kV STNMB1Q01BNMBCU SPI YPH OLTC IN LOCAL Y Addition
257 765kV STNMB1Q01BNMBCU SPI YPH OLTC IN REMOTE Y Addition
258 765kV STNMB1Q01BNMBCU SPI YPH TAP CHANGE CONTROL SUPPLY FAIL Y Addition
259 765kV STNMB1Q01BNMBCU SPI YPH LOWEST POSITION REACHDED Y Addition
260 765kV STNMB1Q01BNMBCU SPI YPH HIGHESHT POSITION REACHDED Y Addition
261 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SPC1CGGIO n/ctlOpen CMD YPH OLTC RAISE COMMAND Y Addition
262 765kV STNMB1Q01BNMBCU CMD YPH OLTC LOWER COMMAND Y Addition
263 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI BPH OLTC MOTOR OVERLOAD Y Addition
264 765kV STNMB1Q01BNMBCU SPI BPH TAP CHANGE IN PROGRESS Y Addition
265 765kV STNMB1Q01BNMBCU SPI BPH TAP CHANGE IN COMPLETE Y Addition
266 765kV STNMB1Q01BNMBCU SPI BPH OLTC IN LOCAL Y Addition
267 765kV STNMB1Q01BNMBCU SPI BPH OLTC IN REMOTE Y Addition
268 765kV STNMB1Q01BNMBCU SPI BPH TAP CHANGE CONTROL SUPPLY FAIL Y Addition
269 765kV STNMB1Q01BNMBCU SPI BPH LOWEST POSITION REACHDED Y Addition
270 765kV STNMB1Q01BNMBCU SPI BPH HIGHESHT POSITION REACHDED Y Addition
271 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SPC1CGGIO n/ctlOpen CMD BPH OLTC RAISE COMMAND Y Addition
272 765kV STNMB1Q01BNMBCU CMD BPH OLTC LOWER COMMAND Y Addition
273 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI SPH OLTC MOTOR OVERLOAD Y Addition
274 765kV STNMB1Q01BNMBCU SPI SPH TAP CHANGE IN PROGRESS Y Addition
275 765kV STNMB1Q01BNMBCU SPI SPH TAP CHANGE IN COMPLETE Y Addition
276 765kV STNMB1Q01BNMBCU SPI SPH OLTC IN LOCAL Y Addition
277 765kV STNMB1Q01BNMBCU SPI SPH OLTC IN REMOTE Y Addition
278 765kV STNMB1Q01BNMBCU SPI SPH TAP CHANGE CONTROL SUPPLY FAIL Y Addition
279 765kV STNMB1Q01BNMBCU SPI SPH LOWEST POSITION REACHDED Y Addition
280 765kV STNMB1Q01BNMBCU SPI SPH HIGHESHT POSITION REACHDED Y Addition
281 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SPC1CGGIO n/ctlOpen CMD SPH OLTC RAISE COMMAND Y Addition
282 765kV STNMB1Q01BNMBCU CMD SPH OLTC LOWER COMMAND Y Addition
283 765kV STNMB1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-1 Y ** 10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
284 765kV STNMB1Q01BNMBCU SPI SPARE ALARM-2 Y Addition
285 765kV STNMB1Q01BNMBCU SPI SPARE ALARM-3 Y Addition
286 765kV STNMB1Q01BNMBCU SPI SPARE ALARM-4 Y Addition
287 765kV STNMB1Q01BNMBCU SPI SPARE ALARM-5 Y Addition
288 765kV STNMB1Q01BNMBCU SPI SPARE ALARM-6 Y Addition
289 765kV STNMB1Q01BNMBCU SPI SPARE ALARM-7 Y Addition
290 765kV STNMB1Q01BNMBCU SPI SPARE ALARM-8 Y Addition
291 765kV STNMB1Q01BNMBCU SPI SPARE ALARM-9 Y Addition
292 765kV STNMB1Q01BNMBCU SPI SPARE ALARM-10 Y Addition
ADDITIONAL SIGNAL FOR CB TROUBLE ETC AS PER SCHEME
** 10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
NOTE 1: The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified.
NOTE 2: If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
NOTE 3: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 4: The characters "Q01" stand for Bay Number, this will be vary based on Bay number eg. Q01 for BAY01, Q02 for BAY02 etc…
NOTE 5: The characters "BNM" stand for Bay Name, this will be vary based on Bay name eg. L for LINE, BR for BUSREACTOR, LR for LINEREACTOR, TIE for TIE & ICT fo ICT bay.
REQUIRED SIGNALS FOR LINE DIFFERENTAIL cum DISTANCE RELAYS
IED name: R_REL670_21M1
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV1/Str/general SPI OVERVOLATGE STAGE 1 START
2 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV1/Op/general SPI OVERVOLATGE STAGE 1 TRIP Y
3 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/OV2PTOV2/Str/general SPI OVER VOLTAGE STAGE-2 START Y Addition
4 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV2/Op/general SPI OVERVOLATGE STAGE 2 TRIP Y
5 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/EF4_1/EF4PTOC1/Str/general SPI DEF START
6 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/EF4_1/EF4PTOC1/Op/general SPI DEF TRIP Y
7 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/STBPTOC1/Op/general SPI STUB PROTECTION OPERATED Y Applicable for One and Half CB Busbar system
8 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCVPSOF1/Op/general SPI SOTF OPERATED Y
9 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Str/general SPI START, Z1
10 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/general SPI START, Z2
11 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsA SPI START, Z2 R PH
12 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsB SPI START, Z2 Y PH
13 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsC SPI START, Z2 B PH
14 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS3/Str/general SPI START, Z3
15 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS4/Str/general SPI START, Z4(REVERSE) ** Whichever the zone choses as Reverse Text correction
16 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS5/Str/general SPI START, Z5
17 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/general SPI GENERAL TRIP, Z1 Y
18 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsA SPI TRIP, Z1 R PH Y
19 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsB SPI TRIP, Z1 Y PH Y
20 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsC SPI TRIP, Z1 B PH Y
21 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/general SPI GENERAL TRIP, Z2 Y
22 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsA SPI TRIP, Z2 R PH Y
23 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsB SPI TRIP, Z2 Y PH Y
24 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsC SPI TRIP, Z2 B PH Y
25 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS3/Op/general SPI GENERAL TRIP, Z3 Y
26 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS4/Op/general SPI GENERAL TRIP, Z4(REVERSE) Y ** Whichever the zone choses as Reverse Text correction
27 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS5/Op/general SPI GENERAL TRIP, Z5 Y
28 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/ProTx/stVal SPI CARRIER SEND Y
29 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/ProRx/stVal SPI CARRIER RECEIVE Y
30 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/Op/general SPI CARRIER AIDED SCHEME OPERATED Y
31 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMRPSB1/Str/general SPI POWER SWING DETECTED Y
32 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMRPSB1/BlkZn/stVal SPI POWER SWING BLOCKING Y
33 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SMPPTRC1/Op/general SPI DISTANCE RELAY GENERAL TRIP Y
34 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI R PHASE FAULT Y Addition
35 765kV STNMB1Q01LM1DIF SPI Y PHASE FAULT Y Addition
36 765kV STNMB1Q01LM1DIF SPI B PHASE FAULT Y Addition
37 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltDiskm/mag DINT FAULT LOCATOR DISTANCE
38 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltZ/cVal.mag DINT FAULT LOCATOR IMPEDANCE
39 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
40 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/BRCPTOC1/Op/general SPI BROKEN CONDUCTOR ALARM Y
41 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
42 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/LPHD1/PhyHealth/stVal SPI M1 IED UNHEALTHY Y
43 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI START AR TO BCU Text correction
44 765kV STNMB1Q01LM1DIF SPI BLOCK AR TO BCU Text correction
45 765kV STNMB1Q01LM1DIF SPI LINE ISOLATOR OPEN FOR STUB ACTIVATION Applicable for One and Half CB Busbar system
46 765kV STNMB1Q01LM1DIF SPI DT SEND CH 1 Y
47 765kV STNMB1Q01LM1DIF SPI DT SEND CH 2 Y
48 765kV STNMB1Q01LM1DIF SPI DT RECEIVE CH 1 Y Only for DR in RED670, for SCADA to be configured from BCU
49 765kV STNMB1Q01LM1DIF SPI DT RECEIVE CH 2 Y Only for DR in RED670, for SCADA to be configured from BCU
50 765kV STNMB1Q01LM1DIF SPI TRIP RELAY 86 A HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
51 765kV STNMB1Q01LM1DIF SPI TRIP RELAY 86 B HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
52 765kV STNMB1Q01LM1DIF SPI GR A RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RED670, for SCADA to be configured from BCU
53 765kV STNMB1Q01LM1DIF SPI GR B RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RED670, for SCADA to be configured from BCU
54 765kV STNMB1Q01LM1DIF SPI CARRIER RECEIVE CH-1 Y
55 765kV STNMB1Q01LM1DIF SPI CARRIER RECEIVE CH-2 Y
56 765kV STNMB1Q01LM1DIF SPI CARRIER CHANNEL 1 OUT OF SERVICE Y
57 765kV STNMB1Q01LM1DIF SPI CARRIER CHANNEL 2 OUT OF SERVICE Y
58 765kV STNMB1Q01LM1DIF SPI CARRIER CHANNEL 1 FAIL Y
59 765kV STNMB1Q01LM1DIF SPI CARRIER CHANNEL 2 FAIL Y
60 765kV STNMB1Q01LM1DIF SPI MAIN 2/1 RELAY FAIL Y
61 765kV STNMB1Q01LM1DIF SPI CB CLOSE COMMAND FOR SOTF INITIATION Text correction
62 765kV STNMB1Q01LM1DIF SPI BCU RELAY FAIL Y
63 765kV STNMB1Q01LM1DIF SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
64 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsA SPI START, Z1 R PH Addition
65 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsB SPI START, Z1 Y PH Addition
66 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsC SPI START, Z1 B PH Addition
67 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP 3PH Y Addition
68 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP R PH Y Addition
69 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP Y PH Y Addition
70 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP B PH Y Addition
71 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI PREPARE 3-PH TRIP FROM TIE BCU Y Addition, Available in BCU It is also required in RED670
72 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI PREPARE 3-PH TRIP FROM MAIN BCU Y Addition, Available in BCU It is also required in RED670
73 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI MAIN/ TIE CB AR OPTD Y Addition, Available in BCU Only for DR in RED670, for SCADA to be configured from BCU
74 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI MAIN/TIE LBB PROTECTION OPERATED Y Addition, Available in BBP Only for DR in RED670, for SCADA to be configured from LBB/BBP relay
75 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI BUSBAR M1/M2 OPTD Y Addition, Available in BBP Only for DR in RED670, for SCADA to be configured from BBP relay
76 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI GROUP RELAY 86A OPTD Y Available in REL670 (Sig. 52) Agreed
77 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/EchoWei/stVal SPI WEAK INFEED ECHO SEND Y Addition
78 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/EchoWeiOp/stVal SPI WEAK INFEED TRIP Y Addition
79 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/RvABlk/stVal SPI CURRENT REVERSAL DETECTED Y Addition
80 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
81 765kV STNMB1Q01LM1DIF SPI SETTINGS CHANGED Y Addition
82 765kV STNMB1Q01LM1DIF SPI DR MEMMORY 80% FULL Y Addition
83 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltDiskm/mag AI DISTANCE MEASUREMENT IN KM Y Available in REL670 (Sig. 37) Agreed
84 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltZ/cVal/mag AI DISTANCE MEASUREMENT IN IMPEDANCE Y Available in REL670 (Sig. 38) Agreed
85 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/MON/L4UFCNTn/CntVal/actVal AI CH-1 Code-1 Tx (MAIN-1 CARRIER RECEIVE CHANNEL-1) CH-1 Code-1 Tx (MAIN-1 CARRIER SEND CHANNEL-1)
86 765kV STNMB1Q01LM1DIF AI CH-1 Code-1 Rx (MAIN-1 CARRIER SEND CHANNEL-1) CH-1 Code-1 Rx (MAIN-1 CARRIER RECEIVE CHANNEL-1)
87 765kV STNMB1Q01LM1DIF AI CH-1 Code-2 Tx (MAIN-2 CARRIER RECEIVE CHANNEL-1) CH-1 Code-2 Tx (MAIN-2 CARRIER SEND CHANNEL-1)
88 765kV STNMB1Q01LM1DIF AI CH-1 Code-2 Rx (MAIN-2 CARRIER SEND CHANNEL-1) CH-1 Code-2 Rx (MAIN-2 CARRIER RECEIVE CHANNEL-1)
89 765kV STNMB1Q01LM1DIF AI CH-2 Code-2 Tx (MAIN-2 CARRIER RECEIVE CHANNEL-2) CH-2 Code-2 Tx (MAIN-2 CARRIER SEND CHANNEL-2)
90 765kV STNMB1Q01LM1DIF AI CH-2 Code-2 Rx (MAIN-2 CARRIER SEND CHANNEL-2) CH-2 Code-2 Rx (MAIN-2 CARRIER RECEIVECHANNEL-2)
91 765kV STNMB1Q01LM1DIF AI CH-2 Code-1 Tx (MAIN-1 CARRIER RECEIVE CHANNEL-2) CH-2 Code-1 Tx (MAIN-1 CARRIER SEND CHANNEL-2)
92 765kV STNMB1Q01LM1DIF AI CH-2 Code-1 Rx (MAIN-1 CARRIER SEND CHANNEL-2) CH-2 Code-1 Rx (MAIN-1 CARRIER RECEIVE CHANNEL-2)
93 765kV STNMB1Q01LM1DIF AI CH-1 Code-3 Tx (DT RECEIVE CHANNEL-1) CH-1 Code-3 Tx (DT SEND CHANNEL-1)
94 765kV STNMB1Q01LM1DIF AI CH-1 Code-3 Rx (DT SEND CHANNEL-1) CH-1 Code-3 Rx (DT RECEIVE CHANNEL-1)
95 765kV STNMB1Q01LM1DIF AI CH-2 Code-3 Tx (DT RECEIVE CHANNEL-2) CH-2 Code-3 Tx (DT SEND CHANNEL-2)
96 765kV STNMB1Q01LM1DIF AI CH-2 Code-3 Rx (DT SEND CHANNEL-2) CH-2 Code-3 Rx (DT RECEIVE CHANNEL-2)
97 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
98 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-2 Y Addition
99 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-3 Y Addition
100 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-4 Y Addition
101 765kV STNMB1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-5 Y Addition
102 765kV STNMB1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Op/general SPI DIFFERENTIAL PROTECTION TRIP Y Line Differential protection, 3 CT sets, 2-3 line ends Variant
103 765kV SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Op/general SPI Y Line Differential protection, 6 CT sets, 3-5 line ends Variant
104 765kV STNMB1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Op/phsA SPI DIFFERENTIAL PROTECTION RPH TRIP Y Line Differential protection, 3 CT sets, 2-3 line ends Variant
105 765kV SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Op/phsA SPI Y Line Differential protection, 6 CT sets, 3-5 line ends Variant
106 765kV STNMB1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Op/phsB SPI DIFFERENTIAL PROTECTION YPH TRIP Y Line Differential protection, 3 CT sets, 2-3 line ends Variant
107 765kV SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Op/phsB SPI Y Line Differential protection, 6 CT sets, 3-5 line ends Variant
108 765kV STNMB1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Op/phsC SPI DIFFERENTIAL PROTECTION BPH TRIP Y Line Differential protection, 3 CT sets, 2-3 line ends Variant
109 765kV SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Op/phsC SPI Y Line Differential protection, 6 CT sets, 3-5 line ends Variant
110 765kV STNMB1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Str/general SPI DIFFERENTIAL PROTECTION START Line Differential protection, 3 CT sets, 2-3 line ends Variant
111 765kV SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Str/general SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
112 765kV STNMB1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Str/phsA SPI DIFFERENTIAL PROTECTION RPH START Line Differential protection, 3 CT sets, 2-3 line ends Variant
113 765kV SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Str/phsA SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
114 765kV STNMB1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Str/phsB SPI DIFFERENTIAL PROTECTION YPH START Line Differential protection, 3 CT sets, 2-3 line ends Variant
115 765kV SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Str/phsB SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
116 765kV STNMB1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Str/phsC SPI DIFFERENTIAL PROTECTION BPH START Line Differential protection, 3 CT sets, 2-3 line ends Variant
117 765kV SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Str/phsC SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
102 765kV STNMB1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/OpnCTAlm/stVal SPI DIFFERENTIAL PROTECTION OCT ALARM Line Differential protection, 3 CT sets, 2-3 line ends Variant
103 765kV SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/OpnCTAlm/stVal SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
104 765kV STNMB1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/StrRst/stVal SPI DIFFERENTIAL PROTECTION OPTD (RESTRAINED MODE) Line Differential protection, 3 CT sets, 2-3 line ends Variant
105 765kV SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/StrRst/stVal SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
106 765kV STNMB1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/StrUnRst/stVal SPI DIFFERENTIAL PROTECTION OPTD (UNRESTRAINED MODE) Line Differential protection, 3 CT sets, 2-3 line ends Variant
107 765kV SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/StrUnRst/stVal SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
108 765kV STNMB1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Blk2H/stVal SPI DIFFERENTIAL PROTECTION 2nd HARMONIC BLOCK Line Differential protection, 3 CT sets, 2-3 line ends Variant Applicable for Line cum Transformer bay
109 765kV SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Blk2H/stVal SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
110 765kV STNMB1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Blk5H/stVal SPI DIFFERENTIAL PROTECTION 5th HARMONIC BLOCK Line Differential protection, 3 CT sets, 2-3 line ends Variant Applicable for Line cum Transformer bay
111 765kV SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Blk5H/stVal SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
112 765kV STNMB1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION COMMUNICATION FAIL
113 765kV STNMB1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI REMOTE END INTERTRIP RECEIVE
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
ABB SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (400kV)
REQUIRED SIGNALS FOR DISTANCE RELAYS
IED name: R_REL670_21M1
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV1/Str/general SPI OVERVOLATGE STAGE 1 START
2 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV1/Op/general SPI OVERVOLATGE STAGE 1 TRIP Y
3 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV2/Str/general SPI OVER VOLTAGE STAGE-2 START Y Addition
4 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV2/Op/general SPI OVERVOLATGE STAGE 2 TRIP Y
5 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/EF4_1/EF4PTOC1/Str/general SPI DEF START
6 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/EF4_1/EF4PTOC1/Op/general SPI DEF TRIP Y
7 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/STBPTOC1/Op/general SPI STUB PROTECTION OPERATED Y Applicable for One and Half CB Busbar system
8 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCVPSOF1/Op/general SPI SOTF OPERATED Y
9 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Str/general SPI START, Z1
10 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/general SPI START, Z2
11 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsA SPI START, Z2 R PH
12 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsB SPI START, Z2 Y PH
13 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsC SPI START, Z2 B PH
14 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS3/Str/general SPI START, Z3
15 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS4/Str/general SPI START, Z4(REVERSE) ** Whichever the zone choses as Reverse Text correction
16 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS5/Str/general SPI START, Z5
17 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/general SPI GENERAL TRIP, Z1 Y
18 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsA SPI TRIP, Z1 R PH Y
19 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsB SPI TRIP, Z1 Y PH Y
20 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsC SPI TRIP, Z1 B PH Y
21 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/general SPI GENERAL TRIP, Z2 Y
22 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsA SPI TRIP, Z2 R PH Y
23 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsB SPI TRIP, Z2 Y PH Y
24 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsC SPI TRIP, Z2 B PH Y
25 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS3/Op/general SPI GENERAL TRIP, Z3 Y
26 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS4/Op/general SPI GENERAL TRIP, Z4(REVERSE) Y ** Whichever the zone choses as Reverse Text correction
27 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS5/Op/general SPI GENERAL TRIP, Z5 Y
28 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/ProTx/stVal SPI CARRIER SEND Y
29 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/ProRx/stVal SPI CARRIER RECEIVE Y
30 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/Op/general SPI CARRIER AIDED SCHEME OPERATED Y
31 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMRPSB1/Str/general SPI POWER SWING DETECTED Y
32 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMRPSB1/BlkZn/stVal SPI POWER SWING BLOCKING Y
33 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SMPPTRC1/Op/general SPI DISTANCE RELAY GENERAL TRIP Y
34 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI R PHASE FAULT Y Addition
35 400kV STNMC1Q01M1DIS SPI Y PHASE FAULT Y Addition
36 400kV STNMC1Q01M1DIS SPI B PHASE FAULT Y Addition
37 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltDiskm/mag DINT FAULT LOCATOR DISTANCE
38 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltZ/cVal.mag DINT FAULT LOCATOR IMPEDANCE
39 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
40 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/BRCPTOC1/Op/general SPI BROKEN CONDUCTOR ALARM Y
41 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
42 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/LPHD1/PhyHealth/stVal SPI M1 IED UNHEALTHY Y
43 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI START AR TO BCU Text correction
44 400kV STNMC1Q01M1DIS SPI BLOCK AR TO BCU Text correction
45 400kV STNMC1Q01M1DIS SPI LINE ISOLATOR OPEN FOR STUB ACTIVATION Applicable for One and Half CB Busbar system
46 400kV STNMC1Q01M1DIS SPI DT SEND CH 1 Y
47 400kV STNMC1Q01M1DIS SPI DT SEND CH 2 Y
48 400kV STNMC1Q01M1DIS SPI DT RECEIVE CH 1 Y Only for DR in REL670, for SCADA to be configured from BCU
49 400kV STNMC1Q01M1DIS SPI DT RECEIVE CH 2 Y Only for DR in REL670, for SCADA to be configured from BCU
50 400kV STNMC1Q01M1DIS SPI TRIP RELAY 86 A HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
51 400kV STNMC1Q01M1DIS SPI TRIP RELAY 86 B HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
52 400kV STNMC1Q01M1DIS SPI GR A RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in REL670, for SCADA to be configured from BCU
53 400kV STNMC1Q01M1DIS SPI GR B RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in REL670, for SCADA to be configured from BCU
54 400kV STNMC1Q01M1DIS SPI CARRIER RECEIVE CH-1 Y
55 400kV STNMC1Q01M1DIS SPI CARRIER RECEIVE CH-2 Y
56 400kV STNMC1Q01M1DIS SPI CARRIER CHANNEL 1 OUT OF SERVICE Y
57 400kV STNMC1Q01M1DIS SPI CARRIER CHANNEL 2 OUT OF SERVICE Y
58 400kV STNMC1Q01M1DIS SPI CARRIER CHANNEL 1 FAIL Y
59 400kV STNMC1Q01M1DIS SPI CARRIER CHANNEL 2 FAIL Y
60 400kV STNMC1Q01M1DIS SPI MAIN 2/1 RELAY FAIL Y
61 400kV STNMC1Q01M1DIS SPI CB CLOSE COMMAND FOR SOTF INITIATION Text correction
62 400kV STNMC1Q01M1DIS SPI BCU RELAY FAIL Y
63 400kV STNMC1Q01M1DIS SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
64 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsA SPI START, Z1 R PH Addition
65 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsB SPI START, Z1 Y PH Addition
66 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsC SPI START, Z1 B PH Addition
67 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP 3PH Y Addition
68 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP R PH Y Addition
69 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP Y PH Y Addition
70 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP B PH Y Addition
71 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI PREPARE 3-PH TRIP FROM TIE BCU Y Addition, Available in BCU It is also required in REL670
72 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI PREPARE 3-PH TRIP FROM MAIN BCU Y Addition, Available in BCU It is also required in REL670
73 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI MAIN/ TIE CB AR OPTD Y Addition, Available in BCU Only for DR in REL670, for SCADA to be configured from BCU
74 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI MAIN/ TIE LBB PROTECTION OPERATED Y Addition, Available in BBP Only for DR in REL670, for SCADA to be configured from LBB/BBP relay
75 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI BUSBAR M1/M2 OPTD Y Addition, Available in BBP Only for DR in REL670, for SCADA to be configured from BBP relay
76 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI GROUP RELAY 86A OPTD Y Available in REL670 (Sig. 52) Agreed
77 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/EchoWei/stVal SPI WEAK INFEED ECHO SEND Y Addition
78 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/EchoWeiOp/stVal SPI WEAK INFEED TRIP Y Addition
79 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/RvABlk/stVal SPI CURRENT REVERSAL DETECTED Y Addition
80 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
81 400kV STNMC1Q01M1DIS SPI SETTINGS CHANGED Y Addition
82 400kV STNMC1Q01M1DIS SPI DR MEMMORY 80% FULL Y Addition
83 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltDiskm/mag AI DISTANCE MEASUREMENT IN KM Y Available in REL670 (Sig. 37) Agreed
84 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltZ/cVal/mag AI DISTANCE MEASUREMENT IN IMPEDANCE Y Available in REL670 (Sig. 38) Agreed
85 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/MON/L4UFCNTn/CntVal/actVal AI CH-1 Code-1 Tx CH-1 Code-1 Tx (MAIN-1 CARRIER SEND CHANNEL-1)
86 400kV STNMC1Q01M1DIS AI CH-1 Code-1 Rx CH-1 Code-1 Rx (MAIN-1 CARRIER RECEIVE CHANNEL-1)
87 400kV STNMC1Q01M1DIS AI CH-1 Code-2 Tx CH-1 Code-2 Tx (MAIN-2 CARRIER SEND CHANNEL-1)
88 400kV STNMC1Q01M1DIS AI CH-1 Code-2 Rx CH-1 Code-2 Rx (MAIN-2 CARRIER RECEIVE CHANNEL-1)
89 400kV STNMC1Q01M1DIS AI CH-2 Code-2 Tx CH-2 Code-2 Tx (MAIN-2 CARRIER SEND CHANNEL-2)
90 400kV STNMC1Q01M1DIS AI CH-2 Code-2 Rx CH-2 Code-2 Rx (MAIN-2 CARRIER RECEIVECHANNEL-2)
91 400kV STNMC1Q01M1DIS AI CH-2 Code-1 Tx CH-2 Code-1 Tx (MAIN-1 CARRIER SEND CHANNEL-2)
92 400kV STNMC1Q01M1DIS AI CH-2 Code-1 Rx CH-2 Code-1 Rx (MAIN-1 CARRIER RECEIVE CHANNEL-2)
93 400kV STNMC1Q01M1DIS AI CH-1 Code-3 Tx CH-1 Code-3 Tx (DT SEND CHANNEL-1)
94 400kV STNMC1Q01M1DIS AI CH-1 Code-3 Rx CH-1 Code-3 Rx (DT RECEIVE CHANNEL-1)
95 400kV STNMC1Q01M1DIS AI CH-2 Code-3 Tx CH-2 Code-3 Tx (DT SEND CHANNEL-2)
96 400kV STNMC1Q01M1DIS AI CH-2 Code-3 Rx CH-2 Code-3 Rx (DT RECEIVE CHANNEL-2)
97 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
98 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-2 Y Addition
99 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-3 Y Addition
100 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-4 Y Addition
101 400kV STNMC1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-5 Y Addition
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR ICT DIFFERENTIAL RELAYS
IED name: R_RET670_87T
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/OEXPVPH1/Str/general SPI OVEREXCITATION HV START
2 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/OEXPVPH1/Alm/stVal SPI OVEREXCITATION HV ALARM Y
3 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/OEXPVPH1/Op/general SPI OVEREXCITATION HV TRIP Y
4 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/DifAlm/stVal SPI DIFFERENTIAL CURRENT ALARM Y
5 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/general SPI DIFFERENTIAL PROTECTION START
6 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsA SPI DIFFERENTIAL PROTECTION RPH START
7 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsB SPI DIFFERENTIAL PROTECTION YPH START
8 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsC SPI DIFFERENTIAL PROTECTION BPH START
9 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Op/general SPI DIFFERENTIAL PROTECTION TRIP Y
10 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION RPH TRIP Y
11 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION YPH TRIP Y
12 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION BPH TRIP Y
13 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/OpRst/stVal SPI DIFFERENTIAL PROTECTION TRIP (RESTRAINED MODE) Y
14 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/OpUnRst/stVal SPI DIFFERENTIAL PROTECTION TRIP (UNRESTRAINED MODE) Y
15 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Blk2H/stVal SPI DIFFERENTIAL PROTECTION 2nd HARMONIC BLOCK
16 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Blk5H/stVal SPI DIFFERENTIAL PROTECTION 5th HARMONIC BLOCK
17 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SMPPTRC1/Op/general SPI DIFFERENTIAL RELAY GENERAL TRIP Y
18 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
19 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/LPHD1/PhyHealth/stVal SPI DIFFRENTIAL IED UNHEALTHY Y
20 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI OTI ALARM Y APPLICABLE FOR 3 PHASE TRANSFORMERS
21 400kV STNMC1Q01TDIF SPI WTI HV ALARM Y
22 400kV STNMC1Q01TDIF SPI WTI IV ALARM Y
23 400kV STNMC1Q01TDIF SPI WTI MV ALARM Y
24 400kV STNMC1Q01TDIF SPI BUCCHOLZ_n ALARM Y Addition
25 400kV STNMC1Q01TDIF SPI BUCCHOLZ_n TRIP Y Text correction
26 400kV STNMC1Q01TDIF SPI OSR _n TRIP Y Text correction
27 400kV STNMC1Q01TDIF SPI PRD _n TRIP Y Text correction
28 400kV STNMC1Q01TDIF SPI FIRE PROTECTION OPERATED Y
29 400kV STNMC1Q01TDIF SPI LOW OIL LEVEL Y
30 400kV STNMC1Q01TDIF SPI OTI R PH ALARM Y APPLICABLE FOR SINGLE PHASE TRANSFORMERS (If a dedicated IED is provided for spare transformer protection, only spare phase signals are required to be used)
31 400kV STNMC1Q01TDIF SPI OTI Y PH ALARM Y
32 400kV STNMC1Q01TDIF SPI OTI B PH ALARM Y
33 400kV STNMC1Q01TDIF SPI OTI SPARE ICT ALARM Y
34 400kV STNMC1Q01TDIF SPI WTI HV R PH ALARM Y
35 400kV STNMC1Q01TDIF SPI WTI HV Y PH ALARM Y
36 400kV STNMC1Q01TDIF SPI WTI HV B PH ALARM Y
37 400kV STNMC1Q01TDIF SPI WTI HV SPARE ICT ALARM Y
38 400kV STNMC1Q01TDIF SPI WTI MV R PH ALARM Y
39 400kV STNMC1Q01TDIF SPI WTI MV Y PH ALARM Y
40 400kV STNMC1Q01TDIF SPI WTI MV B PH ALARM Y
41 400kV STNMC1Q01TDIF SPI WTI MV SPARE ICT ALARM Y
42 400kV STNMC1Q01TDIF SPI WTI IV R PH ALARM Y
43 400kV STNMC1Q01TDIF SPI WTI IV Y PH ALARM Y
44 400kV STNMC1Q01TDIF SPI WTI IV B PH ALARM Y
45 400kV STNMC1Q01TDIF SPI WTI IV SPARE ICT ALARM Y
46 400kV STNMC1Q01TDIF SPI BUCHHOLZ_n R PH ALARM Y Addition
47 400kV STNMC1Q01TDIF SPI BUCHHOLZ_n Y PH ALARM Y Addition
48 400kV STNMC1Q01TDIF SPI BUCHHOLZ_n B PH ALARM Y Addition
49 400kV STNMC1Q01TDIF SPI BUCHHOLZ_n SPARE ICT TRIP Y Addition, BUCHHOLZ_n SPARE ICT ALARM
50 400kV STNMC1Q01TDIF SPI BUCHHOLZ_n R PH TRIP Y Text correction
51 400kV STNMC1Q01TDIF SPI BUCHHOLZ_n Y PH TRIP Y Text correction
52 400kV STNMC1Q01TDIF SPI BUCHHOLZ_n B PH TRIP Y Text correction
53 400kV STNMC1Q01TDIF SPI BUCHHOLZ_n SPARE ICT TRIP Y Text correction
54 400kV STNMC1Q01TDIF SPI OSR_n R PH TRIP Y Text correction
55 400kV STNMC1Q01TDIF SPI OSR_n Y PH TRIP Y Text correction
56 400kV STNMC1Q01TDIF SPI OSR_n B PH TRIP Y Text correction
57 400kV STNMC1Q01TDIF SPI OSR_n SPARE ICT TRIP Y Text correction
58 400kV STNMC1Q01TDIF SPI PRD n R PH TRIP Y Text correction
59 400kV STNMC1Q01TDIF SPI PRD nY PH TRIP Y Text correction
60 400kV STNMC1Q01TDIF SPI PRD n B PH TRIP Y Text correction
61 400kV STNMC1Q01TDIF SPI PRD n SPARE ICT TRIP Y Text correction
62 400kV STNMC1Q01TDIF SPI LOW OIL LEVEL R PH Y
63 400kV STNMC1Q01TDIF SPI LOW OIL LEVEL Y PH Y
64 400kV STNMC1Q01TDIF SPI LOW OIL LEVEL B PH Y
65 400kV STNMC1Q01TDIF SPI LOW OIL LEVEL SPARE ICT Y
66 400kV STNMC1Q01TDIF SPI FIRE PROTECTION R PH OPERATED Y
67 400kV STNMC1Q01TDIF SPI FIRE PROTECTION Y PH OPERATED Y
68 400kV STNMC1Q01TDIF SPI FIRE PROTECTION B PH OPERATED Y
69 400kV STNMC1Q01TDIF SPI FIRE PROTECTION SPARE ICT OPERATED Y
70 400kV STNMC1Q01TDIF SPI TRIP RELAY 86 A HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
71 400kV STNMC1Q01TDIF SPI TRIP RELAY 86 B HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
72 400kV STNMC1Q01TDIF SPI GR A RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RET670, for SCADA to be configured from BCU
73 400kV STNMC1Q01TDIF SPI GR B RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RET670, for SCADA to be configured from BCU
74 400kV STNMC1Q01TDIF SPI REF RELAY FAIL Y
75 400kV STNMC1Q01TDIF SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
** It may be noted that the Body Protection alarms & trips have been Grouped into two separate relays Differential (Group A) & REF (Group B) relays. The hardwiring for same must be done accordingly and approved scheme shall be modified if required. Same is applicable for Reactor protection also.
76 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/OC4_1/OC4PTOC1/Str/general SPI TERTIARY 33kV PHASE OVERCURRENT START Y Addition
77 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/OC4_1/OC4PTOC1/Op/general SPI TERTIARY33kV PHASE OVERCURRENT TRIP Y Addition
78 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/EF4_1/EF4PTOC1/Str/general SPI TERTIARY 33kV PHASE EARTHFAULT START Y Addition
79 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/EF4_1/EF4PTOC1/Op/general SPI TERTIARY 33kV PHASE EARTHFAULT TRIP Y Addition
80 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/ROV2_1/ROV2PTOV1/Str/general SPI TERTIARY 33kV PHASE RESIDUAL OVERVOLTAGE START Y Addition
81 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/ROV2_1/ROV2PTOV1/OP/general SPI TERTIARY 33kV PHASE RESIDUAL OVERVOLTAGE TRIP Y Addition
82 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI TERTIARY 33kV 86 OPTD Y Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
83 400kV STNMC1Q01TDIF SPI TERTIARY TRAFO - BUCHHOLZ ALARM Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
84 400kV STNMC1Q01TDIF SPI TERTIARY TRAFO - BUCHHOLZ TRIP Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
85 400kV STNMC1Q01TDIF SPI TERTIARY TRAFO - WTI ALARM Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
86 400kV STNMC1Q01TDIF SPI TERTIARY TRAFO - WTI TRIP Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
87 400kV STNMC1Q01TDIF SPI TERTIARY TRAFO - OTI ALARM Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
88 400kV STNMC1Q01TDIF SPI TERTIARY TRAFO - OTI TRIP Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
89 400kV STNMC1Q01TDIF SPI TERTIARY TRAFO - PRD ALARM Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
90 400kV STNMC1Q01TDIF SPI TERTIARY TRAFO - PRD TRIP Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
91 400kV STNMC1Q01TDIF SPI TERTIARY 33KV_TC-1 FAULTY Y Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
92 400kV STNMC1Q01TDIF SPI TERTIARY 33KV_TC-2 FAULTY Y Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
93 400kV STNMC1Q01TDIF SPI TERTIARY 33kV CB ASSOCIATED ALARMS Y Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
94 400kV STNMC1Q01TDIF SPI RELAY IN TEST MODE Y Addition
95 400kV STNMC1Q01TDIF SPI SETTINGS CHANGED Y Addition
96 400kV STNMC1Q01TDIF SPI DR MEMORY 80% FULL Y Addition
97 400kV STNMC1Q01TDIF CMD DELUGE COMMAND APPLICABLE FOR 3 PHASE TRANSFORMERS Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
98 400kV STNMC1Q01TDIF CMD DELUGE COMMAND R PH APPLICABLE FOR SINGLE PHASE TRANSFORMERS (If a dedicated IED is provided for spare transformer protection, only spare phase signals are required to be used) Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
99 400kV STNMC1Q01TDIF CMD DELUGE COMMAND Y PH Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
100 400kV STNMC1Q01TDIF CMD DELUGE COMMAND B PH Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
101 400kV STNMC1Q01TDIF CMD DELUGE COMMAND SPARE Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
102 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL//EF4_1/EF4PTOC2/Str/general SPI NEUTRAL OVERCURRENT ALARM Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
103 400kV STNMC1Q01TDIF SS_BAY_DIFFERENTIAL//LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
104 400kV STNMC1Q01TDIF SPI SPARE ALARM-2 Y Addition
105 400kV STNMC1Q01TDIF SPI SPARE ALARM-3 Y Addition
106 400kV STNMC1Q01TDIF SPI SPARE ALARM-4 Y Addition
107 400kV STNMC1Q01TDIF SPI SPARE ALARM-5 Y Addition
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR ICT REF RELAYS
IED name: R_RET670_64
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 400kV STNMC1Q01TREF SS_BAY_REF/LD0/OEXPVPH1/Str/general SPI OVEREXCITATION MV START
2 400kV STNMC1Q01TREF SS_BAY_REF/LD0/OEXPVPH1/Alm/stVal SPI OVEREXCITATION MV ALARM Y
3 400kV STNMC1Q01TREF SS_BAY_REF/LD0/OEXPVPH1/Op/general SPI OVEREXCITATION MV TRIP Y
4 400kV STNMC1Q01TREF SS_BAY_REF/LD0/HZPDIF1/Alm/stVal SPI REF ALARM Y
5 400kV STNMC1Q01TREF SS_BAY_REF/LD0/HZPDIF1/Op/general SPI REF TRIP Y
6 400kV STNMC1Q01TREF SS_BAY_REF/LD0/SMPPTRC1/Op/general SPI REF RELAY GENERAL TRIP Y
7 400kV STNMC1Q01TREF SS_BAY_REF/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
8 400kV STNMC1Q01TREF SS_BAY_REF/LD0/LPHD1/PhyHealth/stVal SPI REF IED UNHEALTHY Y
9 400kV STNMC1Q01TREF SS_BAY_REF/LD0/SP16GGIO n/Ind n/stVal SPI OTI TRIP Y APPLICABLE FOR 3 PHASE TRANSFORMERS
10 400kV STNMC1Q01TREF SPI WTI HV TRIP Y
11 400kV STNMC1Q01TREF SPI WTI MV TRIP Y
12 400kV STNMC1Q01TREF SPI WTI LV TRIP Y
13 400kV STNMC1Q01TREF SPI OSR 2 TRIP Y
14 400kV STNMC1Q01TREF SPI PRD 2 TRIP Y
15 400kV STNMC1Q01TREF SPI BUCCHOLZ_n ALARM Y Text correction
16 400kV STNMC1Q01TREF SPI BUCCHOLZ_n TRIP Y Addition
17 400kV STNMC1Q01TREF SPI OTI R PH TRIP Y APPLICABLE FOR SINGLE PHASE TRANSFORMERS (If a dedicated IED is provided for spare transformer protection, only spare phase signals are required to be used)
18 400kV STNMC1Q01TREF SPI OTI Y PH TRIP Y
19 400kV STNMC1Q01TREF SPI OTI B PH TRIP Y
20 400kV STNMC1Q01TREF SPI OTI SPARE ICT TRIP Y
21 400kV STNMC1Q01TREF SPI WTI HV R PH TRIP Y
22 400kV STNMC1Q01TREF SPI WTI HV Y PH TRIP Y
23 400kV STNMC1Q01TREF SPI WTI HV B PH TRIP Y
24 400kV STNMC1Q01TREF SPI WTI HV SPARE ICT TRIP Y
25 400kV STNMC1Q01TREF SPI WTI MV R PH TRIP Y
26 400kV STNMC1Q01TREF SPI WTI MV Y PH TRIP Y
27 400kV STNMC1Q01TREF SPI WTI MV B PH TRIP Y
28 400kV STNMC1Q01TREF SPI WTI MV SPARE ICT TRIP Y
29 400kV STNMC1Q01TREF SPI WTI IV R PH TRIP Y
30 400kV STNMC1Q01TREF SPI WTI IV Y PH TRIP Y
31 400kV STNMC1Q01TREF SPI WTI IV B PH TRIP Y
32 400kV STNMC1Q01TREF SPI WTI IV SPARE ICT TRIP Y
33 400kV STNMC1Q01TREF SPI BUCCHOLZ R PH ALARM Y
34 400kV STNMC1Q01TREF SPI BUCCHOLZ Y PH ALARM Y
35 400kV STNMC1Q01TREF SPI BUCCHOLZ B PH ALARM Y
36 400kV STNMC1Q01TREF SPI BUCCHOLZ SPARE ICT ALARM Y
37 400kV STNMC1Q01TREF SPI OSR 2 R PH TRIP Y
38 400kV STNMC1Q01TREF SPI OSR 2 Y PH TRIP Y
39 400kV STNMC1Q01TREF SPI OSR 2 B PH TRIP Y
40 400kV STNMC1Q01TREF SPI OSR 2 SPARE ICT TRIP Y
41 400kV STNMC1Q01TREF SPI PRD 2 R PH TRIP Y
42 400kV STNMC1Q01TREF SPI PRD 2 Y PH TRIP Y
43 400kV STNMC1Q01TREF SPI PRD 2 B PH TRIP Y
44 400kV STNMC1Q01TREF SPI PRD 2 SPARE ICT TRIP Y
45 400kV STNMC1Q01TREF SPI DIFFERENTIAL RELAY FAIL Y
46 400kV STNMC1Q01TREF SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
47 400kV STNMC1Q01TREF SPI RELAY IN TEST MODE Y Addition
48 400kV STNMC1Q01TREF SPI SETTINGS CHANGED Y Addition
49 400kV STNMC1Q01TREF SPI DR MEMORY 80% FULL Y Addition
50 400kV STNMC1Q01TREF SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
51 400kV STNMC1Q01TREF SPI SPARE ALARM-2 Y Addition
52 400kV STNMC1Q01TREF SPI SPARE ALARM-3 Y Addition
53 400kV STNMC1Q01TREF SPI SPARE ALARM-4 Y Addition
54 400kV STNMC1Q01TREF SPI SPARE ALARM-5 Y Addition
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR ICT BACKUP IMPEDANCE PROTECTION RELAY Additional Relay - Impedance Protection Signals are part of ICT REF PROTECTION RELAY
IED name: R_REL670_21T
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/ZMCAPDIS1/Str/phsA SPI BACKUP IMPEDANCE START, Z1 R PH
2 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/ZMCAPDIS1/Str/phsB SPI BACKUP IMPEDANCE START, Z1 Y PH
3 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMPE/LD0/ZMCAPDIS1/Str/phsC SPI BACKUP IMPEDANCE START, Z1 B PH
4 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS1.Str.general SPI BACKUP IMPEDANCE START BACKUP IMPEDANCE ZONE-1 START Agreed
5 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS1.Op.general SPI BACKUP IMPEDANCE ZONE-1 TRIP Y
6 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/ZMCAPDIS2/Str/phsA SPI BACKUP IMPEDANCE START, Z2 R PH
7 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/ZMCAPDIS2/Str/phsB SPI BACKUP IMPEDANCE START, Z2 Y PH
8 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMPE/LD0/ZMCAPDIS2/Str/phsC SPI BACKUP IMPEDANCE START, Z2B PH
9 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS2.Str.general SPI BACKUP IMPEDANCE ZONE-2 START
10 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS2.Op.general SPI BACKUP IMPEDANCE ZONE-2 TRIP Y
11 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS3.Str.general SPI BACKUP IMPEDANCE ZONE-3 START
12 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS3.Op.general SPI BACKUP IMPEDANCE ZONE-3 TRIP Y
13 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS4.Str.general SPI BACKUP IMPEDANCE ZONE-4 START
14 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS4.Op.general SPI BACKUP IMPEDANCE ZONE-4 TRIP Y
15 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SMPPTRC1/Op/general SPI BACKUP IMPEDANCE RELAY GENERAL TRIP Y
16 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/OC4_1/OC4PTOC1/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-1 START OC/EF PROTECTION SIGNALS ARE PART OF HV DIRECTIONAL OVERCURRENT & EARTHFAULT PROTECTION RELAY
17 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/OC4_1/OC4PTOC1/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-1 TRIP Y
18 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/EF4_1/EF4PTOC1/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-1 START
19 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/EF4_1/EF4PTOC1/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-1 TRIP Y
20 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/OC4_1/OC4PTOC2/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-2 START
21 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/OC4_1/OC4PTOC2/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-2 TRIP Y
22 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/EF4_1/EF4PTOC2/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-2 START
23 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/EF4_1/EF4PTOC2/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-2 TRIP Y
24 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP 3PH Y
25 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP R PH Y
26 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP Y PH Y
27 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP B PH Y
28 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
29 400kV STNMC1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
30 400kV STNMC1Q01THVBIMP SPI BACKUP IMPEDANCE IED UNHEALTHY Y
31 400kV STNMC1Q01THVBIMP SPI RELAY IN TEST MODE Y
32 400kV STNMC1Q01THVBIMP SPI SETTINGS CHANGED Y
33 400kV STNMC1Q01THVBIMP SPI DR MEMORY 80% FULL Y
34 400kV STNMC1Q01THVBIMP SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
35 400kV STNMC1Q01THVBIMP SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
36 400kV STNMC1Q01THVBIMP SPI SPARE ALARM-2 Y
37 400kV STNMC1Q01THVBIMP SPI SPARE ALARM-3 Y
38 400kV STNMC1Q01THVBIMP SPI SPARE ALARM-4 Y
39 400kV STNMC1Q01THVBIMP SPI SPARE ALARM-5 Y
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR HV DIRECTIONAL OVERCURRENT AND EARTH FAULT RELAYS
IED name: R_REL670_HVBUP
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 400kV STNMC1Q01THBU SS_BAY_HV BACKUP OC EF/OC4_1/OC4PTOC1/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-1 START Text correction
2 400kV STNMC1Q01THBU SS_BAY_HV BACKUP OC EFE/OC4_1/OC4PTOC1/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-1 TRIP Y Text correction
3 400kV STNMC1Q01THBU SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTOC1/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-1 START Text correction
4 400kV STNMC1Q01THBU SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTOC1/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-1 TRIP Y Text correction
5 400kV STNMC1Q01THBU SS_BAY_HV BACKUP OC EF/OC4_1/OC4PTOC2/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-2 START if Non Directional then name has to be replaced with Directional to Non-Directional Addition
6 400kV STNMC1Q01THBU SS_BAY_HV BACKUP OC EF/OC4_1/OC4PTOC2/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-2 TRIP Y Addition
7 400kV STNMC1Q01THBU SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTOC2/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-2 START Addition
8 400kV STNMC1Q01THBU SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTOC2/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-2 TRIP Y Addition
9 400kV STNMC1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
10 400kV STNMC1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/SMPPTRC1/Op/general SPI GENERAL TRIP Y
11 400kV STNMC1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
12 400kV STNMC1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal SPI BACKUP OC/EF IED UNHEALTHY Y
13 400kV STNMC1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
14 400kV STNMC1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
15 400kV STNMC1Q01THBU SPI SETTINGS CHANGED Y Addition
16 400kV STNMC1Q01THBU SPI DR MEMORY 80% FULL Y Addition
17 400kV STNMC1Q01THBU SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
18 400kV STNMC1Q01THBU SPI SPARE ALARM-2 Y Addition
19 400kV STNMC1Q01THBU SPI SPARE ALARM-3 Y Addition
20 400kV STNMC1Q01THBU SPI SPARE ALARM-4 Y Addition
21 400kV STNMC1Q01THBU SPI SPARE ALARM-5 Y Addition
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR LV DIRECTIONAL OVERCURRENT AND EARTH FAULT RELAYS
IED name: R_REL670_LVBUP
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 400kV STNMC1Q01TLBU SS_BAY_LV BACKUP OC EF/OC4_1/OC4PTOC1/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-1 START Text correction
2 400kV STNMC1Q01TLBU SS_BAY_LV BACKUP OC EFE/OC4_1/OC4PTOC1/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-1 TRIP Y Text correction
3 400kV STNMC1Q01TLBU SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTOC1/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-1 START Text correction
4 400kV STNMC1Q01TLBU SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTOC1/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-1 TRIP Y Text correction
5 400kV STNMC1Q01TLBU SS_BAY_LV BACKUP OC EF/OC4_1/OC4PTOC2/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-2 START if Non Directional then name has to be replaced with Directional to Non-Directional Addition
6 400kV STNMC1Q01TLBU SS_BAY_LV BACKUP OC EF/OC4_1/OC4PTOC2/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-2 TRIP Y Addition
7 400kV STNMC1Q01TLBU SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTOC2/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-2 START Addition
8 400kV STNMC1Q01TLBU SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTOC2/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-2 TRIP Y Addition
9 400kV STNMC1Q01TLBU SS_BAY_LV BACKUP OC EF/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
10 400kV STNMC1Q01TLBU SS_BAY_LV BACKUP OC EF/LD0/SMPPTRC1/Op/general SPI GENERAL TRIP Y
11 400kV STNMC1Q01TLBU SS_BAY_LV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
12 400kV STNMC1Q01TLBU SS_BAY_LV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal SPI BACKUP OC/EF IED UNHEALTHY Y
13 400kV STNMC1Q01TLBU SS_BAY_LV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
14 400kV STNMC1Q01TLBU SPI SETTINGS CHANGED Y Addition
15 400kV STNMC1Q01TLBU SPI DR MEMORY 80% FULL Y Addition
16 400kV STNMC1Q01TLBU SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR REACTOR DIFFERENTIAL RELAYS
IED name: R_RET670_87R
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Op/general SPI DIFFERENTIAL PROTECTION TRIP Y
2 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION RPH TRIP Y
3 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION YPH TRIP Y
4 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION BPH TRIP Y
5 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/DifAlm/stVal SPI DIFFERENTIAL CURRENT ALARM
6 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/general SPI DIFFERENTIAL PROTECTION START
7 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsA SPI DIFFERENTIAL PROTECTION RPH START
8 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsB SPI DIFFERENTIAL PROTECTION YPH START
9 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsC SPI DIFFERENTIAL PROTECTION BPH START
10 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SMPPTRC1/Op/general SPI DIFFERENTIAL RELAY GENERAL TRIP Y
11 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/OpRst/stVal SPI DIFFERENTIAL PROTECTION TRIP (RESTRAINED MODE) Y Addition
12 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/OpUnRst/stVal SPI DIFFERENTIAL PROTECTION TRIP (UNRESTRAINED MODE) Y Addition
13 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Blk2H/stVal SPI DIFFERENTIAL PROTECTION 2nd HARMONIC BLOCK Addition
14 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Blk5H/stVal SPI DIFFERENTIAL PROTECTION 5th HARMONIC BLOCK Addition
15 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI BUSBAR PROT OPTD Y Addition, Need to discuss Only for DR in RET670, for SCADA to be configured from BBP relay
16 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
17 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/LPHD1/PhyHealth/stVal SPI DIFFRENTIAL IED UNHEALTHY Y *
18 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI OTI TRIP Y APPLICABLE FOR 3 PHASE REACTORS Interchanged between Diff. & REF relays
19 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI WTI ALARM Y Already available
20 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI BUCCHOLZ-A TRIP Y Addition
21 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI BUCCHOLZ-B ALARM Y Addition
22 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI PRV-1 TRIP(NO) Y Text correction
23 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI FIRE PROTECTION OPERATED Y Already available
24 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI LOW OIL LEVEL ALARM Y Already available
25 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI PRV-1 TRIP(NC) Y Addition, Need to discuss Yet to be finalized by PGCIL
26 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI FLOW SENSITIVE CONSERVATOR VALVE ALARM Y Addition
27 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI REACTOR MB ALARMS Y Addition
28 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI OTI R PH ALARM Y APPLICABLE FOR SINGLE PHASE REACTORS (If a dedicated IED is provided for spare reactor protection, only spare phase signals are required to be used)
29 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI OTI Y PH ALARM Y
30 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI OTI B PH ALARM Y
31 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI OTI SPARE PH ALARM Y
32 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI WTI R PH ALARM Y
33 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI WTI Y PH ALARM Y
34 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI WTI B PH ALARM Y
35 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI WTI SPARE PH ALARM Y
36 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI BUCCHOLZ_n R PH ALARM Y Interchanged between Diff. & REF relays
37 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI BUCCHOLZ_n Y PH ALARM Y Interchanged between Diff. & REF relays
38 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI BUCCHOLZ_n B PH ALARM Y Interchanged between Diff. & REF relays
39 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI BUCCHOLZ_n SPARE PH ALARM Y Interchanged between Diff. & REF relays
40 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI BUCCHOLZ_n R PH TRIP Y Text correction
41 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI BUCCHOLZ_n Y PH TRIP Y Text correction
42 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI BUCCHOLZ_n B PH TRIP Y Text correction
43 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI BUCCHOLZ_n SPARE PH TRIP Y Text correction
44 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI OSR R PH TRIP Y
45 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI OSR Y PH TRIP Y
46 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI OSR B PH TRIP Y
47 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI OSR SPARE PH TRIP Y
48 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI PRD R PH TRIP Y Yet to be finalized by PGCIL
49 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI PRD Y PH TRIP Y Yet to be finalized by PGCIL
50 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI PRD B PH TRIP Y Yet to be finalized by PGCIL
51 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI PRD SPARE PH TRIP Y
52 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI LOW OIL LEVEL R PH Y
53 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI LOW OIL LEVEL Y PH Y
54 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI LOW OIL LEVEL B PH Y
55 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI LOW OIL LEVEL SPARE PH Y
56 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI FIRE PROTECTION R PH OPERATED Y
57 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI FIRE PROTECTION Y PH OPERATED Y
58 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI FIRE PROTECTION B PH OPERATED Y
59 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI FIRE PROTECTION SPARE ICT OPERATED Y
60 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI TRIP RELAY 86 A HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
61 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI TRIP RELAY 86 B HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
62 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI GR A RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RET670, for SCADA to be configured from BBP relay
63 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI GR B RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RET670, for SCADA to be configured from BBP relay
64 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI GR A RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Available in RET670 (Sig. 62)
65 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI GR B RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Available in RET670 (Sig. 63)
66 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI REF RELAY FAIL Y
67 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI RELAY IN TEST MODE Y Addition
68 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI SETTINGS CHANGED Y Addition
69 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI DR MEMORY 80% FULL Y Addition
70 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
71 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
72 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI SPARE ALARM-2 Y Addition
73 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI SPARE ALARM-3 Y Addition
74 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI SPARE ALARM-4 Y Addition
75 400kV STNMC1Q01LRDIF /STNMC1Q01BRDIF SPI SPARE ALARM-5 Y Addition
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR REACTOR REF RELAYS
IED name: R_RET670_64R
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SS_BAY_REF/LD0/HZPDIF1/Alm/stVal SPI REF ALARM Y
2 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SS_BAY_REF/LD0/HZPDIF1/Op/general SPI REF TRIP Y
3 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SS_BAY_REF/LD0/SMPPTRC1/Op/general SPI REF RELAY GENERAL TRIP Y
4 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SS_BAY_REF/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
5 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SS_BAY_REF/LD0/LPHD1/PhyHealth/stVal SPI REF IED UNHEALTHY Y
6 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SS_BAY_REF/LD0/SP16GGIO n/Ind n/stVal SPI OTI ALARM Y APPLICABLE FOR 3 PHASE REACTORS Interchanged between Diff. & REF relays
7 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI WTI TRIP Y Already available
8 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI BUCCHOLZ-A ALARM Y Addition
9 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI BUCCHOLZ-B TRIP Y Addition
10 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI PRV-2 TRIP Y Addition
11 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI FIRE PROTECTION OPERATED Y Addition
12 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI HIGH LEVEL OIL ALARM Y Addition
13 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI 86B TRIP RELAY SUPERVSION ALARM Y Addition, Need to discuss
14 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI REACTOR MB ALARMS Y Addition
15 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI OTI R PH TRIP Y APPLICABLE FOR SINGLE PHASE REACTORS (If a dedicated IED is provided for spare Reactor protection, only spare phase signals are required to be used)
16 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI OTI Y PH TRIP Y
17 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI OTI B PH TRIP Y
18 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI OTI SPARE PH TRIP Y
19 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI WTI R PH TRIP Y
20 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI WTI Y PH TRIP Y
21 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI WTI B PH TRIP Y
22 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI WTI SPARE PH TRIP Y
23 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI BUCCHOLZ R PH ALARM Y
24 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI BUCCHOLZ Y PH ALARM Y
25 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI BUCCHOLZ B PH ALARM Y
26 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI BUCCHOLZ SPARE PH ALARM Y
27 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI DIFFERENTIAL RELAY FAIL Y
28 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI RELAY IN TEST MODE Y Addition
29 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI SETTINGS CHANGED Y Addition
30 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI DR MEMORY 80% FULL Y Addition
31 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
32 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI SPARE ALARM-2 Y Addition
33 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI SPARE ALARM-3 Y Addition
34 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI SPARE ALARM-4 Y Addition
35 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI SPARE ALARM-5 Y Addition
36 400kV STNMC1Q01LRREF /STNMC1Q01BRREF SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR REACTOR BACKUP IMPEDANCE PROTECTION RELAY
IED name: R_REL670_21R
SL. NO. Voltage Level ` IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SS_BAY_BUP IMPEDANCE/LD0.ZMHPDIS1.Str.general SPI BACKUP IMPEDANCE START
2 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SS_BAY_BUP IMPEDANCE/LD0.ZMHPDIS1.Op.general SPI BACKUP IMPEDANCE TRIP Y
3 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SS_BAY_BUP IMPEDANCE/LD0/SMPPTRC1/Op/general SPI BACKUP IMPEDANCE RELAY GENERAL TRIP Y
4 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SS_BAY_BUP IMPEDANCE/OC4_1/OC4PTOC1/Str/general SPI BACKUP OVERCURRENT START
5 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SS_BAY_BUP IMPEDANCE/OC4_1/OC4PTOC1/Op/general SPI BACKUP OVERCURRENT TRIP Y
6 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SS_BAY_BUP IMPEDANCE/EF4_1/EF4PTOC1/Str/general SPI BACKUP EARTHFAULT START
7 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SS_BAY_BUP IMPEDANCE/EF4_1/EF4PTOC1/Op/general SPI BACKUP EARTHFAULT TRIP Y
8 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SS_BAY_BUP IMPEDANCE/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
9 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SS_BAY_BUP IMPEDANCE/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
10 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SS_BAY_BUP IMPEDANCE/LD0/LPHD1/PhyHealth/stVal SPI BACKUP IMPEDANCE IED UNHEALTHY Y
11 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SS_BAY_HV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal SPI NGR BUCHHOLZ ALARM Y For Line Reactor NGR associated alarms Addition
12 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI NGR BUCHHOLZ TRIP Y Addition
13 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI NGR OTI ALARM Y Addition
14 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI NGR OTI TRIP Y Addition
15 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI NGR WTI ALARM Y Addition
16 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI NGR WTI TRIP Y Addition
17 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI NGR OSR TRIP Y Addition
18 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI NGR CB ASSOCIATED ALARMS Y All NGC CB associated alarms to be monitored Addition
19 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI NGR BYPASS ISOLATOR ASSOCIATED ALARMS Y All NGR Bypass Isolator associated alarms to be monitored Addition
20 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI BACKUP IMPEDANCE IED UNHEALTHY Y Addition
21 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP CMD NGR BYPASS COMMAND Y Addition
22 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI RELAY IN TEST MODE Y Addition
23 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI SETTINGS CHANGED Y Addition
24 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI DR MEMMORY 80% FULL Y Addition
25 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
26 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
27 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI SPARE ALARM-2 Y Addition
28 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI SPARE ALARM-3 Y Addition
29 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI SPARE ALARM-4 Y Addition
30 400kV STNMC1Q01LRBIMP /STNMC1Q01LRBIMP SPI SPARE ALARM-5 Y Addition
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR BUSBAR PROTECTION RELAYS (DECENTRALIZED) - REB 500
IED name: BB_REB500_87B
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/BCZ_PDIF1/DifAlm SPI BUSBAR CHECKZONE ALARM Y Addition
2 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/BCZ_PDIF1/Op/general SPI BUSBAR CHECKZONE TRIP Y Addition
3 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/CALH1/GrAlm2/stVal SPI BUSBAR CT CIRCUIT ERROR Y Agreed
4 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF1/Op/PhsA SPI BUSBAR ZONE 1 TRIP R- PHASE Y Addition, BUSBAR TRIP R- PHASE is configurable (Zone1/2 phasewise trip signal is not configurable)
5 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF1/Op/PhsB SPI BUSBAR ZONE 1 TRIP Y- PHASE Y Addition, BUSBAR TRIP Y- PHASE Is configurable (Zone1/2 phasewise trip signal is not configurable)
6 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF1/Op/PhsC SPI BUSBAR ZONE 1 TRIP B- PHASE Y Addition, BUSBAR TRIP B- PHASE Is configurable (Zone1/2 phasewise trip signal is not configurable)
7 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF1/Op/general SPI BUSBAR ZONE 1 TRIP Y
8 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/BZ_PDIF1/Blk SPI BUSBAR ZONE 1 BLOCKED Y
9 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI BREAKER FAILURE - BUSBAR 1 BLOCKED Y Addition, Need to discuss (Signal not configurable), Sig. 8 (BUSBAR ZONE 1 BLOCKED) is common blocking signal which will active when busbar blocked from external switch, Isolator intermidiate status, CT Circuit error conditions)
10 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF1/DifAlm SPI BUSBAR ZONE-1 CT CIRCUIT ERROR Y BUSBAR CT CIRCUIT ERROR is configured in Signal No.-03 (Zone1/2 CT CIRCUIT signal not configurable)
11 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI BUSBAR ZONE 1 BLOCKED EXTERNAL BY SWITCH Y
12 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF2/Op/PhsA SPI BUSBAR ZONE 2 TRIP R- PHASE Y Addition, BUSBAR TRIP R- PHASE is configurable (Zone1/2 phasewise trip signal is not configurable)
13 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF2/Op/PhsB SPI BUSBAR ZONE 2 TRIP Y- PHASE Y Addition, BUSBAR TRIP Y- PHASE Is configurable (Zone1/2 phasewise trip signal is not configurable)
14 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF2/Op/PhsC SPI BUSBAR ZONE 2 TRIP B- PHASE Y Addition, BUSBAR TRIP B- PHASE Is configurable (Zone1/2 phasewise trip signal is not configurable)
15 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF2/Op/general SPI BUSBAR ZONE 2 TRIP Y
16 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/BZ_PDIF2/Blk SPI BUSBAR ZONE 2 BLOCKED Y
17 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI BREAKER FAILURE - BUSBAR 2 BLOCKED Y Addition, Need to discuss (Signal not configurable), Sig. 15 (BUSBAR ZONE 2 BLOCKED) is common blocking signal which will active when busbar blocked from external switch, Isolator intermidiate status, CT Circuit error conditions)
18 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/BBP_PDIF2/DifAlm SPI BUSBAR ZONE-2 CT CIRCUIT ERROR Y BUSBAR CT CIRCUIT ERROR is configured in Signal No.-03 (Zone1/2 CT CIRCUIT signal not configurable)
19 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI BUSBAR ZONE 2 BLOCKED EXTERNAL BY SWITCH Y
20 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/CALH1/GrAlm1/stVal SPI ISOLATOR IN INTERMEDIATE STATUS Y TO BE USED RELATES TO STATUS OF SWITCHING ELEMENT
21 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/PTRC/Tr/general SPI BAY N TRIP Y For each Bays
22 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB0 n/LPHD n/PhyHealth/stVal SPI BUSBAR BLOCKED DUE TO COMMUNICATION ERROR_Bay_n Y For each Bays
23 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/GAPC/Ind08/stVal SPI BAY_N_BREAKER FAILURE R-PH INITIATION Y For each Bays Addition
24 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/GAPC/Ind09/stVal SPI BAY_N_BREAKER FAILURE Y-PH INITIATION Y For each Bays Addition
25 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/GAPC/Ind10/stVal SPI BAY_N_BREAKER FAILURE B-PH INITIATION Y For each Bays Addition
26 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/GAPC/Ind11/stVal SPI BAY_N_BREAKER FAILURE 3PH INITIATION Y For each Bays Addition
27 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/GAPC/Ind04/stVal SPI BAY_N_EXTERNAL BUSBAR ZONE n Y For signals where BB tripped through External Tripping commands(GD, Half Dia) Addition
28 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/RBRF/OpIn/general SPI BAY_N_BREAKER FAILURE RETRIP Y For each Bays Addition
29 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/RBRF/OpEx/general SPI BAY_N_BREAKER FAILURE BACKTRIP Y For each Bays Addition
30 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/RBRF/OpIn/PhsA SPI BAY_N_BREAKER FAILURE RPH- RETRIP Y For each Bays Addition
31 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/RBRF/OpIn/PhsB SPI BAY_N_BREAKER FAILURE YPH- RETRIP Y For each Bays Addition
32 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB0/BP_n/RBRF/OpIn/PhsC SPI BAY_N_BREAKER FAILURE BPH- RETRIP Y For each Bays Addition
33 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/LPHD1/PhyHealth/stVal SPI BBP CENTRAL UNIT IED UNHEALTHY Y
34 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
35 400kV STNMC1BBM1 /STNMC1BBM2 SPI SETTINGS CHANGED Y Addition, Need to discuss (Signal not configurable)
36 400kV STNMC1BBM1 /STNMC1BBM2 SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme Addition
37 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-1 Y ** 10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
38 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-2 Y Addition
39 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-3 Y Addition
40 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-4 Y Addition
41 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-5 Y Addition
42 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-6 Y Addition
43 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-7 Y Addition
44 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-8 Y Addition
45 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-9 Y Addition
46 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-10 Y Addition
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR BUSBAR PROTECTION RELAYS (CENTRALIZED) - REB 670
IED name: BB_REB670_87B
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/BBS/BZBSPDIF1/Op/general SPI BUSBAR ZONE 1 TRIP Y BBS - Single Phase & BBT-Three Phase Variant. STNMD1BBM1R/Y/B if phasewise Busbar IEDs are deployed.
2 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/BBS/BZBSPDIF2/Op/general SPI BUSBAR ZONE 2 TRIP Y
3 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/BBS/BZBSPDIF1/OpnCTAlm/stVal SPI BUSBAR ZONE 1 CT CIRCUIT ERROR Y
4 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/BBS/BZBSPDIF2/OpnCTAlm/stVal SPI BUSBAR ZONE 2 CT CIRCUIT ERROR Y
5 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n /Ind n/stVal SPI BUSBAR ZONE 1 BLOCKED EXTERNAL BY SWITCH Y
6 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n /Ind n/stVal SPI BUSBAR ZONE 2 BLOCKED EXTERNAL BY SWITCH Y
7 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n /Ind n/stVal SPI BUSBAR ZONE 1 PROTECTION BLOCKED Y
8 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n /Ind n/stVal SPI BUSBAR ZONE 2 PROTECTION BLOCKED Y
9 400kV STNMB1BBM1 /STNMB1BBM2 SS_BAY_BUSBAR/BBS6/BCZPDIF1/Op/general SPI BUSBAR CHECKZONE TRIP Y
10 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/BBS/BBSPTRC n/Tr/general SPI BAY n TRIP Y **** If Bay Breaker Failure function internally utilised then BFP related Initiation, Retrip, Backtrip & other signal refered with Standalone LBB relay.
11 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n/Ind n/stVal SPI BAY n BREAKER FAILURE BACKUP TRIP Y For each bay signals to be configured and reported Addition
12 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n/Ind n/stVal SPI LCC BUSBAR GAS ZONE TRIP Y If Applicable for GIS Addition
13 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
14 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/LD0/LPHD1/PhyHealth/stVal SPI BBP IED UNHEALTHY Y
15 400kV STNMC1BBM1 /STNMC1BBM2 SS_BAY_BUSBAR/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
16 400kV STNMC1BBM1 /STNMC1BBM2 SPI SETTINGS CHANGED Y Addition
17 400kV STNMC1BBM1 /STNMC1BBM2 SPI DR MEMMORY 80% FULL Y Addition
18 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-1 Y ** 10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
19 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-2 Y Addition
20 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-3 Y Addition
21 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-4 Y Addition
22 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-5 Y Addition
23 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-6 Y Addition
24 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-7 Y Addition
25 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-8 Y Addition
26 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-9 Y Addition
27 400kV STNMC1BBM1 /STNMC1BBM2 SPI SPARE ALARM-10 Y Addition
28 765kV STNMB1BBM1 /STNMB1BBM2 SPI BUSBAR ZONE 1 TRIP R- PHASE Y Addition
29 765kV STNMB1BBM1 /STNMB1BBM2 SPI BUSBAR ZONE 1 TRIP Y- PHASE Y Addition
30 765kV STNMB1BBM1 /STNMB1BBM2 SPI BUSBAR ZONE 1 TRIP B- PHASE Y Addition
31 765kV STNMB1BBM1 /STNMB1BBM2 SPI BUSBAR ZONE 2 TRIP R- PHASE Y Addition
32 765kV STNMB1BBM1 /STNMB1BBM2 SPI BUSBAR ZONE 2 TRIP Y- PHASE Y Addition
33 765kV STNMB1BBM1 /STNMB1BBM2 SPI BUSBAR ZONE 2 TRIP B- PHASE Y Addition
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR BREAKER FAILURE PROTECTION RELAY
IED name: R_RELAY NAME_50BFR
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILURE/LD0/GGIO n/ST/ Ind n SPI BREAKER FAILURE PROTECTION START Y
2 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpEx/general SPI BREAKER FAILURE BACKUP TRIP Y Text correction
3 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpIn/general SPI BREAKER FAILURE RETRIP Y
4 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpIn/PhsA SPI BREAKER FAILURE RETRIP RPH Y Addition
5 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpIn/PhsB SPI BREAKER FAILURE RETRIP YPH Y Addition
6 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpIn/PhsC SPI BREAKER FAILURE RETRIP BPH Y Addition
7 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILURE/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
8 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILURE/LD0/LPHD1/PhyHealth/stVal SPI BFP IED UNHEALTHY Y
9 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI BREAKER FAILURE R-PHASE INITIATION FROM M1/M2 Y Addition
10 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI BREAKER FAILURE Y-PHASE INITIATION FROM M1/M2 Y Addition
11 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI BREAKER FAILURE B-PHASE INITIATION FROM M1/M2 Y Addition
12 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI BREAKER FAILURE 3-PHASE INITIATION FROM 86A/86B/BB Y Addition
13 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI BREAKER FAILURE FROM LCC (If applicable) Y Applicable for GIS LCC Addition
14 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI IV GR-A INT TRIP RELAY OPTD (If applicable) Y Applicable for ICT Bays incomers Addition
15 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI IV GR-B INT TRIP RELAY OPTD (If applicable) Y Addition
16 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
17 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI SETTINGS CHANGED Y Addition
18 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI DR MEMMORY 80% FULL Y Addition
19 400kV STNMC1Q01BFR SS_BAY_BREAKER FAILURE/LD0/SP16GGIO n/Ind n/stVal SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
20 400kV STNMC1Q01BFR SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
21 400kV STNMC1Q01BFR SPI SPARE ALARM-2 Y Addition
22 400kV STNMC1Q01BFR SPI SPARE ALARM-3 Y Addition
23 400kV STNMC1Q01BFR SPI SPARE ALARM-4 Y Addition
24 400kV STNMC1Q01BFR SPI SPARE ALARM-5 Y Addition
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR BAY CONTROL UNIT
IED name: R_REC670_BCU
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS ADDITIONAL REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/QCBAY1/LocSwPos/stVal INT BCU IN LOCAL/ REMOTE
2 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/Op/general SPI CLOSE COMMAND FROM BCU FOR AUTORECLOSE FOR BCUs HAVING AUTORECLSOURE FUNCTION INBUILT
3 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI GR-A TRIP RELAY FAULTY Y Addition
4 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI GR-B TRIP RELAY FAULTY Y Addition
5 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI DT RECEIVE CHANNEL-1 Y Addition, Available in REL670 Only for DR in REL670, for SCADA to be configured from BCU
6 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI DT RECEIVE CHANNEL-2 Y Addition, Available in REL670 Only for DR in REL670, for SCADA to be configured from BCU
7 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/AutoRecSt/StVal SPI AUTORECLOSE FUNCTION ON Y Addition
8 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/AutoRecSt/StVal SPI AUTORECLOSE FUNCTION OFF Y Addition
9 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI START AUTORECLOSE FUNCTION Y Addition
10 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/BlkRec/stVal SPI BLOCK AUTORECLOSE FUNCTION Y
11 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/Prp3PhOp/stVal SPI PREPARE 3PH TRIP AUTORECLOSE Y
12 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/RdyRec/stVal SPI AUTORECLOSE FUNCTION READY Text correction
13 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/ActRec/stVal SPI AUTORECLOSE IN PROGRESS Y Text correction
14 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/SucRec/stVal SPI AUTORECLOSE SUCCESSFUL Y Text correction
15 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/UnsRec/stVal SPI AUTORECLOSE UNSUCCESSFUL Y Text correction
16 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SXCBR1/Pos/stVal DPI BAY_CB R PH POSITION
17 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SXCBR2/Pos/stVal DPI BAY_CB Y PH POSITION
18 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SXCBR3/Pos/stVal DPI BAY_CB B PH POSITION
19 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI1/Pos/stVal DPI BAY_CB POSITION
20 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI1/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI1/Pos/ctlOperOn for Close CMD BAY_CB_COMMAND CLOSE / OPEN
21 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO1/EnaOpn/stVal SPI BAY_CB_OPEN PERMITTED OR ENABLED
22 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO1/EnaCls/stVal SPI BAY_CB_CLOSE PERMITTED OR ENABLED
23 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI2/Pos/stVal DPI BAY_89A_ISOLATOR POSITION
24 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI2/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI2/Pos/ctlOperOn for Close CMD BAY_89A_ISO COMMAND CLOSE / OPEN
25 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO2/EnaOpn/stVal SPI BAY_89A_ISO OPEN PERMITTED OR ENABLED
26 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO2/EnaCls/stVal SPI BAY_89A_ISO CLOSE PERMITTED OR ENABLED
27 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI3/Pos/stVal DPI BAY_89AE/AE1_ISOLATOR POSITION
28 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI3/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI3/Pos/ctlOperOn for Close CMD BAY_89AE/AE1_ISO COMMAND CLOSE / OPEN
29 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO3/EnaOpn/stVal SPI BAY_89AE/AE1_ISO OPEN PERMITTED OR ENABLED
30 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO3/EnaCls/stVal SPI BAY_89AE/AE1_ISO CLOSE PERMITTED OR ENABLED
31 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI4/Pos/stVal DPI BAY_89B_ISOLATOR POSITION
32 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI4/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI4/Pos/ctlOperOn for Close CMD BAY_89B_ISO COMMAND CLOSE / OPEN
33 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO4/EnaOpn/stVal SPI BAY_89B_ISO OPEN PERMITTED OR ENABLED
34 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO4/EnaCls/stVal SPI BAY_89B_ISO CLOSE PERMITTED OR ENABLED
35 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI5/Pos/stVal DPI BAY_89BE/BE1_ISOLATOR POSITION
36 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI5/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI5/Pos/ctlOperOn for Close CMD BAY_89BE/BE1_ISO COMMAND CLOSE / OPEN
37 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO5/EnaOpn/stVal SPI BAY_89BE/BE1_ISO OPEN PERMITTED OR ENABLED
38 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO5/EnaCls/stVal SPI BAY_89BE/BE1_ISO CLOSE PERMITTED OR ENABLED
39 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI6/Pos/stVal DPI BAY_89L/T/BR_ISOLATOR POSITION FOR 3 PHASE TRANSFORMERS & REACTORS CSWI6 MAY BE USED FOR 89T/BR, BUT FOR SINGLE PHASE TRANSFORMERS & REACTORS SAME HAS BEEN SEPARATELY MENTIONED
40 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI6/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI6/Pos/ctlOperOn for Close CMD BAY_89L/T/BR_ISO COMMAND CLOSE / OPEN
41 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO6/EnaOpn/stVal SPI BAY_89L/T/BR_ISO OPEN PERMITTED OR ENABLED
42 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO6/EnaCls/stVal SPI BAY_89L/T/BR_ISO CLOSE PERMITTED OR ENABLED
43 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI7/Pos/stVal DPI BAY_89LE/TE/BRE_ISOLATOR POSITION FOR 3 PHASE TRANSFORMERS & REACTORS CSWI7 MAY BE USED FOR 89TE/BRE, BUT FOR SINGLE PHASE PHASE TRANSFORMERS & REACTORS SAME HAS BEEN SEPARATELY MENTIONED
44 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI7/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI7/Pos/ctlOperOn for Close CMD BAY_89LE/TE/BRE_ISO COMMAND CLOSE / OPEN
45 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO7/EnaOpn/stVal SPI BAY_89LE/TE/BRE_ISO OPEN PERMITTED OR ENABLED
46 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO7/EnaCls/stVal SPI BAY_89LE/TE/BRE_ISO CLOSE PERMITTED OR ENABLED
47 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI8/Pos/stVal DPI BAY_89LR/89C_ISOLATOR POSITION FOR 3 PHASE LINE REACTORS CSWI8 MAY BE USED FOR 89LR, BUT FOR SINGLE PHASE LINE REACTORS SAME HAS BEEN SEPARATELY MENTIONED
48 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI8/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI8/Pos/ctlOperOn for Close CMD BAY_89LR/89C_ISO COMMAND CLOSE / OPEN
49 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO8/EnaOpn/stVal SPI BAY_89LR/89C_ISO OPEN PERMITTED OR ENABLED
50 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO8/EnaCls/stVal SPI BAY_89LR/89C_ISO CLOSE PERMITTED OR ENABLED
51 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI9/Pos/stVal DPI BAY_89LRE_ISOLATOR POSITION FOR 3 PHASE LINE REACTORS CSWI9 MAY BE USED FOR 89LRE, BUT FOR SINGLE PHASE LINE REACTORS SAME HAS BEEN SEPARATELY MENTIONED
52 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI9/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI9/Pos/ctlOperOn for Close CMD BAY_89LRE_ISO COMMAND CLOSE / OPEN
53 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO9/EnaOpn/stVal SPI BAY_89LRE_ISO OPEN PERMITTED OR ENABLED
54 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO9/EnaCls/stVal SPI BAY_89LRE_ISO CLOSE PERMITTED OR ENABLED
55 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI10/Pos/stVal DPI BAY_89BRS1&2_ISOLATOR POSITION FOR 3 PHASE BUS & LINE REACTORS CSWI10 MAY BE USED FOR 89BRS1&2, BUT FOR SINGLE PHASE TRANSFORMERS SAME HAS BEEN SEPARATELY MENTIONED
56 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI10Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI10/Pos/ctlOperOn for Close CMD BAY_89BRS1&2_ISO COMMAND CLOSE / OPEN
57 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO10/EnaOpn/stVal SPI BAY_89BRS1&2_ISO OPEN PERMITTED OR ENABLED
58 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO10/EnaCls/stVal SPI BAY_89BRS1&2_ISO CLOSE PERMITTED OR ENABLED
59 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI11/Pos/stVal DPI BAY_89BRS1E_ISOLATOR POSITION FOR 3 PHASE TRANSFORMERS & REACTORS CSWI11 MAY BE USED FOR 89BRS1E, BUT FOR SINGLE PHASE TRANSFORMERS SAME HAS BEEN SEPARATELY MENTIONED
60 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI11/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI11/Pos/ctlOperOn for Close CMD BAY_89BRS1E_ISO COMMAND CLOSE / OPEN
61 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO11/EnaOpn/stVal SPI BAY_89BRS1E_ISO OPEN PERMITTED OR ENABLED
62 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO11/EnaCls/stVal SPI BAY_89BRS1E_ISO CLOSE PERMITTED OR ENABLED
63 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI12/Pos/stVal DPI BAY_89AE2/BE2_ISOLATOR POSITION USED FOR BUS EARTH SWITCH OF ISOLATOR, WHEN BUS EARTH SWITCH (89AE2/BE2) IS PROVIDED
64 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI12/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI12/Pos/ctlOperOn for Close CMD BAY_89AE2/BE2_ISO COMMAND CLOSE / OPEN
65 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO12/EnaOpn/stVal SPI BAY_89AE2/BE2_ISO OPEN PERMITTED OR ENABLED
66 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SCILO12/EnaCls/stVal SPI BAY_89AE2/BE2_ISO CLOSE PERMITTED OR ENABLED
THE LOGICAL NODE INSTANCE NUMBER (SCSWIn/SCILOn) FOR BUS EARTH SWITCHES, ISOLATOR & EARTHSWITCHES FOR 3 PH/1PH REACTORS & ITCs, e.g 89 BR, BRE, LR, LRE, RS1, RS2, RS1E, 89T,TE, 89AE2, 89BE2 MAY BE ASSIGNED AS PER AVAILABILITY
67 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
68 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/LPHD1/PhyHealth/stVal SPI BCU UNHEALTHY Y
69 400kV STNMC1Q01BNMBCU SS_BAY_BCU/SES_1/SESRSYN2/Rel/stVal SPI CONDITIONS OK FOR SYNCHRONIZATION
70 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI APPLICABLE FOR ONE AND HALF CIRCUIT BREAKER
71 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI SPRING DISCHARGED Y FOR SPRING MECHANISM CBs ANNUNCIATION FOR CIRCUIT BREAKER
72 400kV STNMC1Q01BNMBCU SPI AC MOTOR SUPPLY FAIL Y
73 400kV STNMC1Q01BNMBCU SPI SF6 GAS LOW Y
74 400kV STNMC1Q01BNMBCU SPI OPERATION LOCKED OUT Y
75 400kV STNMC1Q01BNMBCU SPI CB READY FOR AUTORECLOSURE Y
76 400kV STNMC1Q01BNMBCU SPI DC SUPPLY FAIL Y
77 400kV STNMC1Q01BNMBCU SPI TC-1 FAIL Y
78 400kV STNMC1Q01BNMBCU SPI TC-2 FAIL Y
79 400kV STNMC1Q01BNMBCU SPI TRIP RELAY 86 A FAULTY (SUPERVISION) Y Addition
80 400kV STNMC1Q01BNMBCU SPI TRIP RELAY 86 B FAULTY (SUPERVISION) Y Addition
81 400kV STNMC1Q01BNMBCU SPI TC-1 FAULTY R-PH Y Addition
82 400kV STNMC1Q01BNMBCU SPI TC-1 FAULTY Y-PH Y Addition
83 400kV STNMC1Q01BNMBCU SPI TC-1 FAULTY B-PH Y Addition
84 400kV STNMC1Q01BNMBCU SPI TC-2 FAULTY R-PH Y Addition
85 400kV STNMC1Q01BNMBCU SPI TC-2 FAULTY Y-PH Y Addition
86 400kV STNMC1Q01BNMBCU SPI TC-2 FAULTY B-PH Y Addition
87 400kV STNMC1Q01BNMBCU SPI DT RECEIVE CH-1 Y Available in REC670 (Sig. 5) Agreed
88 400kV STNMC1Q01BNMBCU SPI DT RECEIVE CH-2 Y Available in REC670 (Sig. 6) Agreed
89 400kV STNMC1Q01BNMBCU SPI CB MANUAL TRIP CMD Y Addition
90 400kV STNMC1Q01BNMBCU SPI CB MANUAL CLOSE CMD Y Addition
91 400kV STNMC1Q01BNMBCU SPI START A/R Y Addition
92 400kV STNMC1Q01BNMBCU SPI BLOCK A/R Y Addition
93 400kV STNMC1Q01BNMBCU SPI PREPARE 3PH TRIP Y Addition, Available in REC670 (Sig. 11) Agreed
94 400kV STNMC1Q01BNMBCU SPI BUSBAR PROTN OPTD Y Addition
95 400kV STNMC1Q01BNMBCU SPI S.A. COUNTER R-PH Y Addition As per CRP scheme will be configured in BCU/Protection relay
96 400kV STNMC1Q01BNMBCU SPI S.A. COUNTER Y-PH Y Addition As per CRP scheme will be configured in BCU/Protection relay
97 400kV STNMC1Q01BNMBCU SPI S.A. COUNTER B-PH Y Addition As per CRP scheme will be configured in BCU/Protection relay
98 400kV STNMC1Q01BNMBCU SPI INCOMER DC-1 FAIL Y Addition
99 400kV STNMC1Q01BNMBCU SPI INCOMER DC-2 FAIL Y Addition
100 400kV STNMC1Q01BNMBCU SPI POLE DISCREPANCY RELAY OPTD Y
101 400kV STNMC1Q01BNMBCU SPI COMPRESSOR SUPPLY FAIL Y FOR HYDRAULLIC MECHANISM CBs
102 400kV STNMC1Q01BNMBCU SPI AIR PRESSURE LOW Y
103 400kV STNMC1Q01BNMBCU SPI COMPRESSOR RUN TIME SUPERVISION Y
104 400kV STNMC1Q01BNMBCU SPI CB R-PH RECLOSE ALARM Y Addition
105 400kV STNMC1Q01BNMBCU SPI CB Y-PH RECLOSE ALARM Y Addition
106 400kV STNMC1Q01BNMBCU SPI CB B-PH RECLOSE ALARM Y Addition
107 400kV STNMC1Q01BNMBCU SPI CSD OPERATION LIMIT ALARM WHEN OPENING Y Addition
108 400kV STNMC1Q01BNMBCU SPI CSD OPERATION LIMIT ALARM WHEN CLOSING Y Addition
109 400kV STNMC1Q01BNMBCU SPI CSD GROUP ALARM Y Addition
110 400kV STNMC1Q01BNMBCU SPI CSD RESERVED Y Addition
111 400kV STNMC1Q01BNMBCU SPI CSD SYNCHROTEQ IN LOCAL MODE Y Addition
112 400kV STNMC1Q01BNMBCU SPI CSD CB INTERFACE ALARM Y Addition
113 400kV STNMC1Q01BNMBCU SPI CSD SENSOR ALARM Y Addition
114 400kV STNMC1Q01BNMBCU SPI CSD IN Y Addition
115 400kV STNMC1Q01BNMBCU SPI CSD BYPASS Y Addition
116 400kV STNMC1Q01BNMBCU SPI CSD FAIL Y
117 400kV STNMC1Q01BNMBCU SPI ICT/REACTOR-n R PH OUT OF SERVICE Single phase ICT/Reactor OUT of service & Spare reactor out of service information Addition
118 400kV STNMC1Q01BNMBCU SPI ICT/REACTOR-n Y PH OUT OF SERVICE Addition
119 400kV STNMC1Q01BNMBCU SPI ICT/REACTOR-n B PH OUT OF SERVICE Y Addition
120 400kV STNMC1Q01BNMBCU SPI ICT/REACTOR SPARE PH IN SERVICE IN ICT/REACTOR-N Y Addition
121 765kV STNMB1Q01BNMBCU SPI BUS-1 VT RESET VT SELECTION FOR TRANSFORMER & REACTOR
122 765kV STNMB1Q01BNMBCU SPI BUS-2 VT RESET
123 765kV STNMB1Q01BNMBCU SPI LINE VT RESET
124 765kV STNMB1Q01BNMBCU SPI BUS-1 VT SELECTED
125 765kV STNMB1Q01BNMBCU SPI BUS-2 VT SELECTED
126 765kV STNMB1Q01BNMBCU SPI LINE VTSELECTED
127 400kV STNMC1Q01BNMBCU SPI GAS COMPARTMENT n Alarm Stage n Y Stage 1 to n as per scheme ANNUNCIATION FOR GIS BAYS
128 400kV STNMC1Q01BNMBCU SPI LCC PANEL AC SUPPLY FAIL Y
129 400kV STNMC1Q01BNMBCU SPI LCC PANEL DC SUPPLY FAIL Y
130 400kV STNMC1Q01BNMBCU SPI SELECTOR SWITCH POSITION LOCAL/REMOTE Y
131 400kV STNMC1Q01BNMBCU SPI BUS VT MCB TRIP Y FOR BCUs HAVING BUS VT INPUT
132 400kV STNMC1Q01BNMBCU SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
133 400kV STNMC1Q01BNMBCU SPI RELAY IN TEST MODE Y Addition
134 400kV STNMC1Q01BNMBCU SPI SETTINGS CHANGED Y Addition
135 400kV STNMC1Q01BNMBCU SPI DR MEMMORY 80% FULL Y Addition
136 400kV STNMC1Q01BNMBCU SS_BAY_BCU/MON/CMMXU1/A/phsA/cVal/mag AI CURRENT L1 Addition
137 400kV STNMC1Q01BNMBCU SS_BAY_BCU/MON/CMMXU1/A/phsB/cVal/mag AI CURRENT L2 Addition
138 400kV STNMC1Q01BNMBCU SS_BAY_BCU/MON/CMMXU1/A/phsC/cVal/mag AI CURRENT L3 Addition
139 400kV STNMC1Q01BNMBCU SS_BAY_BCU/MON/VMMXU1/PPV/phsAB/cVal/mag AI VOLTAGE U12 Addition
140 400kV STNMC1Q01BNMBCU SS_BAY_BCU/MON/VMMXU1/PPV/phsBC/cVal/mag AI VOLTAGE U23 Addition
141 400kV STNMC1Q01BNMBCU SS_BAY_BCU/MON/VMMXU1/PPV/phsCA/cVal/mag AI VOLTAGE U31 Addition
142 400kV STNMC1Q01BNMBCU SS_BAY_BCU/MON/CVMMXN1/Watt/mag AI ACTIVE POWER (P) Addition
143 400kV STNMC1Q01BNMBCU SS_BAY_BCU/MON/CVMMXN1/VolAmpr/mag AI REACTIVE POWER (Q) Addition
144 400kV STNMC1Q01BNMBCU SS_BAY_BCU/MON/CVMMXN1/PwrFact/mag AI POWER FACTOR (PF) Addition
145 400kV STNMC1Q01BNMBCU SS_BAY_BCU/MON/CVMMXN1/PwrFact/mag AI FREQUENCY (HZ) Addition
146 400kV STNMC1Q01BNMBCU SS_BAY_BCUMON/L4UFCNTn/CntVal/actVal AI S.A. COUNTER R-PH Available in REC670 (Sig. 95) Agreed
147 400kV STNMC1Q01BNMBCU AI S.A. COUNTER Y-PH Available in REC670 (Sig. 95) Agreed
148 400kV STNMC1Q01BNMBCU AI S.A. COUNTER B-PH Available in REC670 (Sig. 95) Agreed
149 400kV STNMC1Q01BNMBCU SS_BAY_BCU/MON/MVGAPC/AnIn_n/mag AI TAP POSITION R PH Addition
150 400kV STNMC1Q01BNMBCU AI TAP POSITION Y PH Addition
151 400kV STNMC1Q01BNMBCU AI TAP POSITION B PH Addition
152 400kV STNMC1Q01BNMBCU AI WTI HV R PH Addition
153 400kV STNMC1Q01BNMBCU AI WTI IV R PH Addition
154 400kV STNMC1Q01BNMBCU AI WTI LV R PH Addition
155 400kV STNMC1Q01BNMBCU AI OTI R PH Addition
156 400kV STNMC1Q01BNMBCU AI WTI HV Y PH Addition
157 400kV STNMC1Q01BNMBCU AI WTI IV Y PH Addition
158 400kV STNMC1Q01BNMBCU AI WTI LV Y PH Addition
159 400kV STNMC1Q01BNMBCU AI OTI Y PH Addition
160 400kV STNMC1Q01BNMBCU AI WTI HV B PH Addition
161 400kV STNMC1Q01BNMBCU AI WTI IV B PH Addition
162 400kV STNMC1Q01BNMBCU AI WTI LV B PH Addition
163 400kV STNMC1Q01BNMBCU AI OTI B PH Addition
164 400kV STNMC1Q01BNMBCU SS_BAY_BCUMON/L4UFCNTn/CntVal/actVal AI BREAKER R-PHASE OPERATION COUNTER Addition
165 400kV STNMC1Q01BNMBCU AI BREAKER Y-PHASE OPERATION COUNTER Addition
166 400kV STNMC1Q01BNMBCU AI BREAKER B-PHASE OPERATION COUNTER Addition
167 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI RPH MOG LOW OIL LEVEL ALARM Y FOR 3Phase TRANSFORMER, INPUTS CAN BE DISTRIBUTED TO ANY IED. BUTSIGNAL SHOULD BE AS PER TRANSFORMER AVIALABLE SIGNAL Addition
168 400kV STNMC1Q01BNMBCU SPI YPH MOG LOW OIL LEVEL ALARM Y Addition
169 400kV STNMC1Q01BNMBCU SPI BPH MOG LOW OIL LEVEL ALARM Y Addition
170 400kV STNMC1Q01BNMBCU SPI SP-PH MOG LOW OIL LEVEL ALARM Y Addition
171 400kV STNMC1Q01BNMBCU SPI RPH MOG HIGH OIL LEVEL ALARM Y Addition
172 400kV STNMC1Q01BNMBCU SPI YPH MOG HIGH OIL LEVEL ALARM Y Addition
173 400kV STNMC1Q01BNMBCU SPI BPH MOG HIGH OIL LEVEL ALARM Y Addition
174 400kV STNMC1Q01BNMBCU SPI SP-PH MOG HIGH OIL LEVEL ALARM Y Addition
175 400kV STNMC1Q01BNMBCU SPI R-PH OIL FLOW SENSITIVE VALVE ALARM Y Addition
176 400kV STNMC1Q01BNMBCU SPI Y-PH OIL FLOW SENSITIVE VALVE ALARM Y Addition
177 400kV STNMC1Q01BNMBCU SPI B-PH OIL FLOW SENSITIVE VALVE ALARM Y Addition
178 400kV STNMC1Q01BNMBCU SPI SP-PH OIL FLOW SENSITIVE VALVE ALARM Y Addition
179 400kV STNMC1Q01BNMBCU SPI RPH PUMP FAIL - BANK A Y Addition
180 400kV STNMC1Q01BNMBCU SPI RPH PUMP FAIL - BANK B Y Addition
181 400kV STNMC1Q01BNMBCU SPI RPH PUMP FAIL - BANK C Y Addition
182 400kV STNMC1Q01BNMBCU SPI RPH PUMP FAIL - BANK D Y Addition
183 400kV STNMC1Q01BNMBCU SPI YPH PUMP FAIL - BANK A Y Addition
184 400kV STNMC1Q01BNMBCU SPI YPH PUMP FAIL - BANK B Y Addition
185 400kV STNMC1Q01BNMBCU SPI YPH PUMP FAIL - BANK C Y Addition
186 400kV STNMC1Q01BNMBCU SPI YPH PUMP FAIL - BANK D Y Addition
187 400kV STNMC1Q01BNMBCU SPI BPH PUMP FAIL - BANK A Y Addition
188 400kV STNMC1Q01BNMBCU SPI BPH PUMP FAIL - BANK B Y Addition
189 400kV STNMC1Q01BNMBCU SPI BPH PUMP FAIL - BANK C Y Addition
190 400kV STNMC1Q01BNMBCU SPI BPH PUMP FAIL - BANK D Y Addition
191 400kV STNMC1Q01BNMBCU SPI SPH PUMP FAIL - BANK A Y Addition
192 400kV STNMC1Q01BNMBCU SPI SPH PUMP FAIL - BANK B Y Addition
193 400kV STNMC1Q01BNMBCU SPI SPH PUMP FAIL - BANK C Y Addition
194 400kV STNMC1Q01BNMBCU SPI SPH PUMP FAIL - BANK D Y Addition
195 400kV STNMC1Q01BNMBCU SPI RPH THERMAL OVERLOAD TRIP - BANK A Y Addition
196 400kV STNMC1Q01BNMBCU SPI RPH THERMAL OVERLOAD TRIP - BANK B Y Addition
197 400kV STNMC1Q01BNMBCU SPI RPH THERMAL OVERLOAD TRIP - BANK C Y Addition
198 400kV STNMC1Q01BNMBCU SPI RPH THERMAL OVERLOAD TRIP - BANK D Y Addition
199 400kV STNMC1Q01BNMBCU SPI YPH THERMAL OVERLOAD TRIP - BANK A Y Addition
200 400kV STNMC1Q01BNMBCU SPI YPH THERMAL OVERLOAD TRIP - BANK B Y Addition
201 400kV STNMC1Q01BNMBCU SPI YPH THERMAL OVERLOAD TRIP - BANK C Y Addition
202 400kV STNMC1Q01BNMBCU SPI YPH THERMAL OVERLOAD TRIP - BANK D Y Addition
203 400kV STNMC1Q01BNMBCU SPI BPH THERMAL OVERLOAD TRIP - BANK A Y Addition
204 400kV STNMC1Q01BNMBCU SPI BPH THERMAL OVERLOAD TRIP - BANK B Y Addition
205 400kV STNMC1Q01BNMBCU SPI BPH THERMAL OVERLOAD TRIP - BANK C Y Addition
206 400kV STNMC1Q01BNMBCU SPI BPH THERMAL OVERLOAD TRIP - BANK D Y Addition
207 400kV STNMC1Q01BNMBCU SPI SPH THERMAL OVERLOAD TRIP - BANK A Y Addition
208 400kV STNMC1Q01BNMBCU SPI SPH THERMAL OVERLOAD TRIP - BANK B Y Addition
209 400kV STNMC1Q01BNMBCU SPI SPH THERMAL OVERLOAD TRIP - BANK C Y Addition
210 400kV STNMC1Q01BNMBCU SPI SPH THERMAL OVERLOAD TRIP - BANK D Y Addition
211 400kV STNMC1Q01BNMBCU SPI RPH LOW OIL FLOW/REVERSE FLOW - BANK A Y Addition
212 400kV STNMC1Q01BNMBCU SPI RPH LOW OIL FLOW/REVERSE FLOW - BANK B Y Addition
213 400kV STNMC1Q01BNMBCU SPI RPH LOW OIL FLOW/REVERSE FLOW - BANK C Y Addition
214 400kV STNMC1Q01BNMBCU SPI RPH LOW OIL FLOW/REVERSE FLOW - BANK D Y Addition
215 400kV STNMC1Q01BNMBCU SPI YPH LOW OIL FLOW/REVERSE FLOW - BANK A Y Addition
216 400kV STNMC1Q01BNMBCU SPI YPH LOW OIL FLOW/REVERSE FLOW - BANK B Y Addition
217 400kV STNMC1Q01BNMBCU SPI YPH LOW OIL FLOW/REVERSE FLOW - BANK C Y Addition
218 400kV STNMC1Q01BNMBCU SPI YPH LOW OIL FLOW/REVERSE FLOW - BANK D Y Addition
219 400kV STNMC1Q01BNMBCU SPI BPH LOW OIL FLOW/REVERSE FLOW - BANK A Y Addition
220 400kV STNMC1Q01BNMBCU SPI BPH LOW OIL FLOW/REVERSE FLOW - BANK B Y Addition
221 400kV STNMC1Q01BNMBCU SPI BPH LOW OIL FLOW/REVERSE FLOW - BANK C Y Addition
222 400kV STNMC1Q01BNMBCU SPI BPH LOW OIL FLOW/REVERSE FLOW - BANK D Y Addition
223 400kV STNMC1Q01BNMBCU SPI SPH LOW OIL FLOW/REVERSE FLOW - BANK A Y Addition
224 400kV STNMC1Q01BNMBCU SPI SPH LOW OIL FLOW/REVERSE FLOW - BANK B Y Addition
225 400kV STNMC1Q01BNMBCU SPI SPH LOW OIL FLOW/REVERSE FLOW - BANK C Y Addition
226 400kV STNMC1Q01BNMBCU SPI SPH LOW OIL FLOW/REVERSE FLOW - BANK D Y Addition
227 400kV STNMC1Q01BNMBCU SPI RPH COOLER CONTROL SUPPLY FAIL Y Addition
228 400kV STNMC1Q01BNMBCU SPI YPH COOLER CONTROL SUPPLY FAIL Y Addition
229 400kV STNMC1Q01BNMBCU SPI BPH COOLER CONTROL SUPPLY FAIL Y Addition
230 400kV STNMC1Q01BNMBCU SPI SPH COOLER CONTROL SUPPLY FAIL Y Addition
231 400kV STNMC1Q01BNMBCU SPI RPH SUPPLY CHANGE OVER FAIL Y Addition
232 400kV STNMC1Q01BNMBCU SPI YPH SUPPLY CHANGE OVER FAIL Y Addition
233 400kV STNMC1Q01BNMBCU SPI BPH SUPPLY CHANGE OVER FAIL Y Addition
234 400kV STNMC1Q01BNMBCU SPI SPH SUPPLY CHANGE OVER FAIL Y Addition
235 400kV STNMC1Q01BNMBCU SPI RPH SUPPLY - A FAIL Y Addition
236 400kV STNMC1Q01BNMBCU SPI YPH SUPPLY - A FAIL Y Addition
237 400kV STNMC1Q01BNMBCU SPI BPH SUPPLY - A FAIL Y Addition
238 400kV STNMC1Q01BNMBCU SPI SPH SUPPLY - A FAIL Y Addition
239 400kV STNMC1Q01BNMBCU SPI RPH SUPPLY - B FAIL Y Addition
240 400kV STNMC1Q01BNMBCU SPI YPH SUPPLY - B FAIL Y Addition
241 400kV STNMC1Q01BNMBCU SPI BPH SUPPLY - B FAIL Y Addition
242 400kV STNMC1Q01BNMBCU SPI SPH SUPPLY - B FAIL Y Addition
243 400kV STNMC1Q01BNMBCU SPI RPH OLTC MOTOR OVERLOAD Y Addition
244 400kV STNMC1Q01BNMBCU SPI RPH TAP CHANGE IN PROGRESS Y Addition
245 400kV STNMC1Q01BNMBCU SPI RPH TAP CHANGE IN COMPLETE Y Addition
246 400kV STNMC1Q01BNMBCU SPI RPH OLTC IN LOCAL Y Addition
247 400kV STNMC1Q01BNMBCU SPI RPH OLTC IN REMOTE Y Addition
248 400kV STNMC1Q01BNMBCU SPI RPH TAP CHANGE CONTROL SUPPLY FAIL Y Addition
249 400kV STNMC1Q01BNMBCU SPI RPH LOWEST POSITION REACHDED Y Addition
250 400kV STNMC1Q01BNMBCU SPI RPH HIGHESHT POSITION REACHDED Y Addition
251 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SPC1CGGIO n/ctlOpen CMD RPH OLTC RAISE COMMAND Y Addition
252 400kV STNMC1Q01BNMBCU CMD RPH OLTC LOWER COMMAND Y Addition
253 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI YPH OLTC MOTOR OVERLOAD Y Addition
254 400kV STNMC1Q01BNMBCU SPI YPH TAP CHANGE IN PROGRESS Y Addition
255 400kV STNMC1Q01BNMBCU SPI YPH TAP CHANGE IN COMPLETE Y Addition
256 400kV STNMC1Q01BNMBCU SPI YPH OLTC IN LOCAL Y Addition
257 400kV STNMC1Q01BNMBCU SPI YPH OLTC IN REMOTE Y Addition
258 400kV STNMC1Q01BNMBCU SPI YPH TAP CHANGE CONTROL SUPPLY FAIL Y Addition
259 400kV STNMC1Q01BNMBCU SPI YPH LOWEST POSITION REACHDED Y Addition
260 400kV STNMC1Q01BNMBCU SPI YPH HIGHESHT POSITION REACHDED Y Addition
261 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SPC1CGGIO n/ctlOpen CMD YPH OLTC RAISE COMMAND Y Addition
262 400kV STNMC1Q01BNMBCU CMD YPH OLTC LOWER COMMAND Y Addition
263 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI BPH OLTC MOTOR OVERLOAD Y Addition
264 400kV STNMC1Q01BNMBCU SPI BPH TAP CHANGE IN PROGRESS Y Addition
265 400kV STNMC1Q01BNMBCU SPI BPH TAP CHANGE IN COMPLETE Y Addition
266 400kV STNMC1Q01BNMBCU SPI BPH OLTC IN LOCAL Y Addition
267 400kV STNMC1Q01BNMBCU SPI BPH OLTC IN REMOTE Y Addition
268 400kV STNMC1Q01BNMBCU SPI BPH TAP CHANGE CONTROL SUPPLY FAIL Y Addition
269 400kV STNMC1Q01BNMBCU SPI BPH LOWEST POSITION REACHDED Y Addition
270 400kV STNMC1Q01BNMBCU SPI BPH HIGHESHT POSITION REACHDED Y Addition
271 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SPC1CGGIO n/ctlOpen CMD BPH OLTC RAISE COMMAND Y Addition
272 400kV STNMC1Q01BNMBCU CMD BPH OLTC LOWER COMMAND Y Addition
273 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI SPH OLTC MOTOR OVERLOAD Y Addition
274 400kV STNMC1Q01BNMBCU SPI SPH TAP CHANGE IN PROGRESS Y Addition
275 400kV STNMC1Q01BNMBCU SPI SPH TAP CHANGE IN COMPLETE Y Addition
276 400kV STNMC1Q01BNMBCU SPI SPH OLTC IN LOCAL Y Addition
277 400kV STNMC1Q01BNMBCU SPI SPH OLTC IN REMOTE Y Addition
278 400kV STNMC1Q01BNMBCU SPI SPH TAP CHANGE CONTROL SUPPLY FAIL Y Addition
279 400kV STNMC1Q01BNMBCU SPI SPH LOWEST POSITION REACHDED Y Addition
280 400kV STNMC1Q01BNMBCU SPI SPH HIGHESHT POSITION REACHDED Y Addition
281 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SPC1CGGIO n/ctlOpen CMD SPH OLTC RAISE COMMAND Y Addition
282 400kV STNMC1Q01BNMBCU CMD SPH OLTC LOWER COMMAND Y Addition
283 400kV STNMC1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
284 400kV STNMC1Q01BNMBCU SPI SPARE ALARM-2 Y Addition
285 400kV STNMC1Q01BNMBCU SPI SPARE ALARM-3 Y Addition
286 400kV STNMC1Q01BNMBCU SPI SPARE ALARM-4 Y Addition
287 400kV STNMC1Q01BNMBCU SPI SPARE ALARM-5 Y Addition
288 400kV STNMC1Q01BNMBCU SPI SPARE ALARM-6 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
289 400kV STNMC1Q01BNMBCU SPI SPARE ALARM-7 Y Addition
290 400kV STNMC1Q01BNMBCU SPI SPARE ALARM-8 Y Addition
291 400kV STNMC1Q01BNMBCU SPI SPARE ALARM-9 Y Addition
292 400kV STNMC1Q01BNMBCU SPI SPARE ALARM-10 Y Addition
ADDITIONAL SIGNAL FOR CB TROUBLE ETC AS PER SCHEME
** 10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
NOTE 1: The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified.
NOTE 2: If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
NOTE 3: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 4: The characters "Q01" stand for Bay Number, this will be vary based on Bay number eg. Q01 for BAY01, Q02 for BAY02 etc…
NOTE 5: The characters "BNM" stand for Bay Name, this will be vary based on Bay name eg. L for LINE, BR for BUSREACTOR, LR for LINEREACTOR, TIE for TIE & ICT fo ICT bay.
REQUIRED SIGNALS FOR LINE DIFFERENTAIL cum DISTANCE RELAYS
IED name: R_REL670_21M1
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV1/Str/general SPI OVERVOLATGE STAGE 1 START
2 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV1/Op/general SPI OVERVOLATGE STAGE 1 TRIP Y
3 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/OV2PTOV2/Str/general SPI OVER VOLTAGE STAGE-2 START Y Addition
4 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV2/Op/general SPI OVERVOLATGE STAGE 2 TRIP Y
5 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/EF4_1/EF4PTOC1/Str/general SPI DEF START
6 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/EF4_1/EF4PTOC1/Op/general SPI DEF TRIP Y
7 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/STBPTOC1/Op/general SPI STUB PROTECTION OPERATED Y Applicable for One and Half CB Busbar system
8 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCVPSOF1/Op/general SPI SOTF OPERATED Y
9 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Str/general SPI START, Z1
10 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/general SPI START, Z2
11 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsA SPI START, Z2 R PH
12 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsB SPI START, Z2 Y PH
13 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsC SPI START, Z2 B PH
14 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS3/Str/general SPI START, Z3
15 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS4/Str/general SPI START, Z4(REVERSE) ** Whichever the zone choses as Reverse Text correction
16 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS5/Str/general SPI START, Z5
17 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/general SPI GENERAL TRIP, Z1 Y
18 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsA SPI TRIP, Z1 R PH Y
19 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsB SPI TRIP, Z1 Y PH Y
20 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsC SPI TRIP, Z1 B PH Y
21 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/general SPI GENERAL TRIP, Z2 Y
22 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsA SPI TRIP, Z2 R PH Y
23 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsB SPI TRIP, Z2 Y PH Y
24 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsC SPI TRIP, Z2 B PH Y
25 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS3/Op/general SPI GENERAL TRIP, Z3 Y
26 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS4/Op/general SPI GENERAL TRIP, Z4(REVERSE) Y ** Whichever the zone choses as Reverse Text correction
27 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS5/Op/general SPI GENERAL TRIP, Z5 Y
28 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/ProTx/stVal SPI CARRIER SEND Y
29 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/ProRx/stVal SPI CARRIER RECEIVE Y
30 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/Op/general SPI CARRIER AIDED SCHEME OPERATED Y
31 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMRPSB1/Str/general SPI POWER SWING DETECTED Y
32 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMRPSB1/BlkZn/stVal SPI POWER SWING BLOCKING Y
33 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SMPPTRC1/Op/general SPI DISTANCE RELAY GENERAL TRIP Y
34 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI R PHASE FAULT Y Addition
35 400kV STNMC1Q01LM1DIF SPI Y PHASE FAULT Y Addition
36 400kV STNMC1Q01LM1DIF SPI B PHASE FAULT Y Addition
37 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltDiskm/mag DINT FAULT LOCATOR DISTANCE
38 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltZ/cVal.mag DINT FAULT LOCATOR IMPEDANCE
39 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
40 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/BRCPTOC1/Op/general SPI BROKEN CONDUCTOR ALARM Y
41 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
42 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/LPHD1/PhyHealth/stVal SPI M1 IED UNHEALTHY Y
43 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI START AR TO BCU Text correction
44 400kV STNMC1Q01LM1DIF SPI BLOCK AR TO BCU Text correction
45 400kV STNMC1Q01LM1DIF SPI LINE ISOLATOR OPEN FOR STUB ACTIVATION Applicable for One and Half CB Busbar system
46 400kV STNMC1Q01LM1DIF SPI DT SEND CH 1 Y
47 400kV STNMC1Q01LM1DIF SPI DT SEND CH 2 Y
48 400kV STNMC1Q01LM1DIF SPI DT RECEIVE CH 1 Y Only for DR in RED670, for SCADA to be configured from BCU
49 400kV STNMC1Q01LM1DIF SPI DT RECEIVE CH 2 Y Only for DR in RED670, for SCADA to be configured from BCU
50 400kV STNMC1Q01LM1DIF SPI TRIP RELAY 86 A HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
51 400kV STNMC1Q01LM1DIF SPI TRIP RELAY 86 B HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
52 400kV STNMC1Q01LM1DIF SPI GR A RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RED670, for SCADA to be configured from BCU
53 400kV STNMC1Q01LM1DIF SPI GR B RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RED670, for SCADA to be configured from BCU
54 400kV STNMC1Q01LM1DIF SPI CARRIER RECEIVE CH-1 Y
55 400kV STNMC1Q01LM1DIF SPI CARRIER RECEIVE CH-2 Y
56 400kV STNMC1Q01LM1DIF SPI CARRIER CHANNEL 1 OUT OF SERVICE Y
57 400kV STNMC1Q01LM1DIF SPI CARRIER CHANNEL 2 OUT OF SERVICE Y
58 400kV STNMC1Q01LM1DIF SPI CARRIER CHANNEL 1 FAIL Y
59 400kV STNMC1Q01LM1DIF SPI CARRIER CHANNEL 2 FAIL Y
60 400kV STNMC1Q01LM1DIF SPI MAIN 2/1 RELAY FAIL Y
61 400kV STNMC1Q01LM1DIF SPI CB CLOSE COMMAND FOR SOTF INITIATION Text correction
62 400kV STNMC1Q01LM1DIF SPI BCU RELAY FAIL Y
63 400kV STNMC1Q01LM1DIF SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
64 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsA SPI START, Z1 R PH Addition
65 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsB SPI START, Z1 Y PH Addition
66 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsC SPI START, Z1 B PH Addition
67 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP 3PH Y Addition
68 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP R PH Y Addition
69 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP Y PH Y Addition
70 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP B PH Y Addition
71 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI PREPARE 3-PH TRIP FROM TIE BCU Y Addition, Available in BCU It is also required in RED670
72 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI PREPARE 3-PH TRIP FROM MAIN BCU Y Addition, Available in BCU It is also required in RED670
73 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI MAIN/ TIE CB AR OPTD Y Addition, Available in BCU Only for DR in RED670, for SCADA to be configured from BCU
74 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI MAIN/TIE LBB PROTECTION OPERATED Y Addition, Available in BBP Only for DR in RED670, for SCADA to be configured from LBB/BBP relay
75 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI BUSBAR M1/M2 OPTD Y Addition, Available in BBP Only for DR in RED670, for SCADA to be configured from BBP relay
76 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI GROUP RELAY 86A OPTD Y Available in REL670 (Sig. 52) Agreed
77 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/EchoWei/stVal SPI WEAK INFEED ECHO SEND Y Addition
78 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/EchoWeiOp/stVal SPI WEAK INFEED TRIP Y Addition
79 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/RvABlk/stVal SPI CURRENT REVERSAL DETECTED Y Addition
80 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
81 400kV STNMC1Q01LM1DIF SPI SETTINGS CHANGED Y Addition
82 400kV STNMC1Q01LM1DIF SPI DR MEMMORY 80% FULL Y Addition
83 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltDiskm/mag AI DISTANCE MEASUREMENT IN KM Y Available in REL670 (Sig. 37) Agreed
84 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltZ/cVal/mag AI DISTANCE MEASUREMENT IN IMPEDANCE Y Available in REL670 (Sig. 38) Agreed
85 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/MON/L4UFCNTn/CntVal/actVal AI CH-1 Code-1 Tx (MAIN-1 CARRIER RECEIVE CHANNEL-1) CH-1 Code-1 Tx (MAIN-1 CARRIER SEND CHANNEL-1)
86 400kV STNMC1Q01LM1DIF AI CH-1 Code-1 Rx (MAIN-1 CARRIER SEND CHANNEL-1) CH-1 Code-1 Rx (MAIN-1 CARRIER RECEIVE CHANNEL-1)
87 400kV STNMC1Q01LM1DIF AI CH-1 Code-2 Tx (MAIN-2 CARRIER RECEIVE CHANNEL-1) CH-1 Code-2 Tx (MAIN-2 CARRIER SEND CHANNEL-1)
88 400kV STNMC1Q01LM1DIF AI CH-1 Code-2 Rx (MAIN-2 CARRIER SEND CHANNEL-1) CH-1 Code-2 Rx (MAIN-2 CARRIER RECEIVE CHANNEL-1)
89 400kV STNMC1Q01LM1DIF AI CH-2 Code-2 Tx (MAIN-2 CARRIER RECEIVE CHANNEL-2) CH-2 Code-2 Tx (MAIN-2 CARRIER SEND CHANNEL-2)
90 400kV STNMC1Q01LM1DIF AI CH-2 Code-2 Rx (MAIN-2 CARRIER SEND CHANNEL-2) CH-2 Code-2 Rx (MAIN-2 CARRIER RECEIVECHANNEL-2)
91 400kV STNMC1Q01LM1DIF AI CH-2 Code-1 Tx (MAIN-1 CARRIER RECEIVE CHANNEL-2) CH-2 Code-1 Tx (MAIN-1 CARRIER SEND CHANNEL-2)
92 400kV STNMC1Q01LM1DIF AI CH-2 Code-1 Rx (MAIN-1 CARRIER SEND CHANNEL-2) CH-2 Code-1 Rx (MAIN-1 CARRIER RECEIVE CHANNEL-2)
93 400kV STNMC1Q01LM1DIF AI CH-1 Code-3 Tx (DT RECEIVE CHANNEL-1) CH-1 Code-3 Tx (DT SEND CHANNEL-1)
94 400kV STNMC1Q01LM1DIF AI CH-1 Code-3 Rx (DT SEND CHANNEL-1) CH-1 Code-3 Rx (DT RECEIVE CHANNEL-1)
95 400kV STNMC1Q01LM1DIF AI CH-2 Code-3 Tx (DT RECEIVE CHANNEL-2) CH-2 Code-3 Tx (DT SEND CHANNEL-2)
96 400kV STNMC1Q01LM1DIF AI CH-2 Code-3 Rx (DT SEND CHANNEL-2) CH-2 Code-3 Rx (DT RECEIVE CHANNEL-2)
97 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
98 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-2 Y Addition
99 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-3 Y Addition
100 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-4 Y Addition
101 400kV STNMC1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-5 Y Addition
102 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Op/general SPI DIFFERENTIAL PROTECTION TRIP Y Line Differential protection, 3 CT sets, 2-3 line ends Variant
103 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Op/general SPI Y Line Differential protection, 6 CT sets, 3-5 line ends Variant
104 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Op/phsA SPI DIFFERENTIAL PROTECTION RPH TRIP Y Line Differential protection, 3 CT sets, 2-3 line ends Variant
105 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Op/phsA SPI Y Line Differential protection, 6 CT sets, 3-5 line ends Variant
106 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Op/phsB SPI DIFFERENTIAL PROTECTION YPH TRIP Y Line Differential protection, 3 CT sets, 2-3 line ends Variant
107 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Op/phsB SPI Y Line Differential protection, 6 CT sets, 3-5 line ends Variant
108 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Op/phsC SPI DIFFERENTIAL PROTECTION BPH TRIP Y Line Differential protection, 3 CT sets, 2-3 line ends Variant
109 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Op/phsC SPI Y Line Differential protection, 6 CT sets, 3-5 line ends Variant
110 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Str/general SPI DIFFERENTIAL PROTECTION START Line Differential protection, 3 CT sets, 2-3 line ends Variant
111 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Str/general SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
112 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Str/phsA SPI DIFFERENTIAL PROTECTION RPH START Line Differential protection, 3 CT sets, 2-3 line ends Variant
113 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Str/phsA SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
114 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Str/phsB SPI DIFFERENTIAL PROTECTION YPH START Line Differential protection, 3 CT sets, 2-3 line ends Variant
115 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Str/phsB SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
116 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Str/phsC SPI DIFFERENTIAL PROTECTION BPH START Line Differential protection, 3 CT sets, 2-3 line ends Variant
117 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Str/phsC SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
102 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/OpnCTAlm/stVal SPI DIFFERENTIAL PROTECTION OCT ALARM Line Differential protection, 3 CT sets, 2-3 line ends Variant
103 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/OpnCTAlm/stVal SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
104 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/StrRst/stVal SPI DIFFERENTIAL PROTECTION OPTD (RESTRAINED MODE) Line Differential protection, 3 CT sets, 2-3 line ends Variant
105 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/StrRst/stVal SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
106 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/StrUnRst/stVal SPI DIFFERENTIAL PROTECTION OPTD (UNRESTRAINED MODE) Line Differential protection, 3 CT sets, 2-3 line ends Variant
107 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/StrUnRst/stVal SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
108 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Blk2H/stVal SPI DIFFERENTIAL PROTECTION 2nd HARMONIC BLOCK Line Differential protection, 3 CT sets, 2-3 line ends Variant Applicable for Line cum Transformer bay
109 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Blk2H/stVal SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
110 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Blk5H/stVal SPI DIFFERENTIAL PROTECTION 5th HARMONIC BLOCK Line Differential protection, 3 CT sets, 2-3 line ends Variant Applicable for Line cum Transformer bay
111 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Blk5H/stVal SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
112 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION COMMUNICATION FAIL
113 400kV STNMC1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI REMOTE END INTERTRIP RECEIVE
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
ABB SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (220kV)
REQUIRED SIGNALS FOR DISTANCE RELAYS
IED name: R_REL670_21M1
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/OV2PTOV1/Str/general SPI OVER VOLTAGE STAGE-1 START Y
2 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/OV2PTOV1/Op/general SPI OVER VOLTAGE STAGE-1 TRIP Y
3 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/OV2PTOV2/Str/general SPI OVER VOLTAGE STAGE-2 START Y Addition
4 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/OV2PTOV2/Op/general SPI OVER VOLTAGE STAGE-2 TRIP Y
5 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/EF4_1/EF4PTOC1/Str/general SPI DEF START
6 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/EF4_1/EF4PTOC1/Op/general SPI DEF TRIP Y
7 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/STBPTOC1/Op/general SPI STUB PROTECTION OPERATED Y Applicable for One and Half CB Busbar system
8 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCVPSOF1/Op/general SPI SOTF OPERATED Y
9 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Str/general SPI START, Z1
10 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/general SPI START, Z2
11 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsA SPI START, Z2 R PH
12 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsB SPI START, Z2 Y PH
13 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsC SPI START, Z2 B PH
14 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS3/Str/general SPI START, Z3
15 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS4/Str/general SPI START, Z4(REVERSE) ** Whichever the zone choses as Reverse Text correction
16 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS5/Str/general SPI START, Z5
17 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/general SPI GENERAL TRIP, Z1 Y
18 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsA SPI TRIP, Z1 R PH Y
19 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsB SPI TRIP, Z1 Y PH Y
20 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsC SPI TRIP, Z1 B PH Y
21 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/general SPI GENERAL TRIP, Z2 Y
22 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsA SPI TRIP, Z2 R PH Y
23 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsB SPI TRIP, Z2 Y PH Y
24 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsC SPI TRIP, Z2 B PH Y
25 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS3/Op/general SPI GENERAL TRIP, Z3 Y
26 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS4/Op/general SPI GENERAL TRIP, Z4(REVERSE) Y ** Whichever the zone choses as Reverse Text correction
27 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS5/Op/general SPI GENERAL TRIP, Z5 Y
28 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/ProTx/stVal SPI CARRIER SEND Y
29 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/ProRx/stVal SPI CARRIER RECEIVE Y
30 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/Op/general SPI CARRIER AIDED SCHEME OPERATED Y
31 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMRPSB1/Str/general SPI POWER SWING DETECTED Y
32 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMRPSB1/BlkZn/stVal SPI POWER SWING BLOCKING Y
33 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SMPPTRC1/Op/general SPI DISTANCE RELAY GENERAL TRIP Y
34 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI R PHASE FAULT Addition
35 220kV STNMD1Q01M1DIS SPI Y PHASE FAULT Addition
36 220kV STNMD1Q01M1DIS SPI B PHASE FAULT Y Addition
37 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltDiskm/mag DINT FAULT LOCATOR DISTANCE
38 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltZ/cVal.mag DINT FAULT LOCATOR IMPEDANCE
39 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
40 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/BRCPTOC1/Op/general SPI BROKEN CONDUCTOR ALARM Y
41 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
42 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/LPHD1/PhyHealth/stVal SPI M1 IED UNHEALTHY Y
43 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI START AR TO BCU Text correction
44 220kV STNMD1Q01M1DIS SPI BLOCK AR TO BCU Text correction
45 220kV STNMD1Q01M1DIS SPI LINE ISOLATOR OPEN FOR STUB ACTIVATION Applicable for One and Half CB Busbar system
46 220kV STNMD1Q01M1DIS SPI DT SEND CH 1 Y
47 220kV STNMD1Q01M1DIS SPI DT SEND CH 2 Y
48 220kV STNMD1Q01M1DIS SPI DT RECEIVE CH 1 Y Only for DR in REL670, for SCADA to be configured from BCU
49 220kV STNMD1Q01M1DIS SPI DT RECEIVE CH 2 Y Only for DR in REL670, for SCADA to be configured from BCU
50 220kV STNMD1Q01M1DIS SPI TRIP RELAY 86 A HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
51 220kV STNMD1Q01M1DIS SPI TRIP RELAY 86 B HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
52 220kV STNMD1Q01M1DIS SPI GR A RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in REL670, for SCADA to be configured from BCU
53 220kV STNMD1Q01M1DIS SPI GR B RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in REL670, for SCADA to be configured from BCU
54 220kV STNMD1Q01M1DIS SPI CARRIER RECEIVE CH-1 Y
55 220kV STNMD1Q01M1DIS SPI CARRIER RECEIVE CH-2 Y
56 220kV STNMD1Q01M1DIS SPI CARRIER CHANNEL 1 OUT OF SERVICE Y
57 220kV STNMD1Q01M1DIS SPI CARRIER CHANNEL 2 OUT OF SERVICE Y
58 220kV STNMD1Q01M1DIS SPI CARRIER CHANNEL 1 FAIL Y
59 220kV STNMD1Q01M1DIS SPI CARRIER CHANNEL 2 FAIL Y
60 220kV STNMD1Q01M1DIS SPI MAIN 2/1 RELAY FAIL Y
61 220kV STNMD1Q01M1DIS SPI CB CLOSE COMMAND FOR SOTF INITIATION Y Text correction
62 220kV STNMD1Q01M1DIS SPI BCU RELAY FAIL Y
63 220kV STNMD1Q01M1DIS SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
64 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsA SPI START, Z1 R PH Addition
65 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsB SPI START, Z1 Y PH Addition
66 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsC SPI START, Z1 B PH Addition
67 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP 3PH Y Addition
68 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP R PH Y Addition
69 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP Y PH Y Addition
70 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP B PH Y Addition
71 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI PREPARE 3-PH TRIP FROM TIE BCU Y Addition, Available in BCU It is also required in REL670
72 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI PREPARE 3-PH TRIP FROM MAIN BCU Y Addition, Available in BCU It is also required in REL670
73 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI MAIN/ TIE CB AR OPTD Y Addition, Available in BCU Only for DR in REL670, for SCADA to be configured from BCU
74 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI MAIN/ TIE LBB PROTECTION OPERATED Y Addition, Available in BBP Only for DR in REL670, for SCADA to be configured from LBB/BBP relay
75 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI BUSBAR M1/M2 OPTD Y Addition, Available in BBP Only for DR in REL670, for SCADA to be configured from BBP relay
76 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI GROUP RELAY 86A OPTD Y Available in REL670 (Sig. 52) Agreed
77 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/EchoWei/stVal SPI WEAK INFEED ECHO SEND Y Addition
78 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/EchoWeiOp/stVal SPI WEAK INFEED TRIP Y Addition
79 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/RvABlk/stVal SPI CURRENT REVERSAL DETECTED Y Addition
80 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
81 220kV STNMD1Q01M1DIS SPI SETTINGS CHANGED Y Addition
82 220kV STNMD1Q01M1DIS SPI DR MEMMORY 80% FULL Y Addition
83 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltDiskm/mag AI DISTANCE MEASUREMENT IN KM Y Available in REL670 (Sig. 37) Agreed
84 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltZ/cVal/mag AI DISTANCE MEASUREMENT IN IMPEDANCE Y Available in REL670 (Sig. 38) Agreed
85 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/MON/L4UFCNTn/CntVal/actVal AI CH-1 Code-1 Tx CH-1 Code-1 Tx (MAIN-1 CARRIER SEND CHANNEL-1)
86 220kV STNMD1Q01M1DIS AI CH-1 Code-1 Rx CH-1 Code-1 Rx (MAIN-1 CARRIER RECEIVE CHANNEL-1)
87 220kV STNMD1Q01M1DIS AI CH-1 Code-2 Tx CH-1 Code-2 Tx (MAIN-2 CARRIER SEND CHANNEL-1)
88 220kV STNMD1Q01M1DIS AI CH-1 Code-2 Rx CH-1 Code-2 Rx (MAIN-2 CARRIER RECEIVE CHANNEL-1)
89 220kV STNMD1Q01M1DIS AI CH-2 Code-2 Tx CH-2 Code-2 Tx (MAIN-2 CARRIER SEND CHANNEL-2)
90 220kV STNMD1Q01M1DIS AI CH-2 Code-2 Rx CH-2 Code-2 Rx (MAIN-2 CARRIER RECEIVECHANNEL-2)
91 220kV STNMD1Q01M1DIS AI CH-2 Code-1 Tx CH-2 Code-1 Tx (MAIN-1 CARRIER SEND CHANNEL-2)
92 220kV STNMD1Q01M1DIS AI CH-2 Code-1 Rx CH-2 Code-1 Rx (MAIN-1 CARRIER RECEIVE CHANNEL-2)
93 220kV STNMD1Q01M1DIS AI CH-1 Code-3 Tx CH-1 Code-3 Tx (DT SEND CHANNEL-1)
94 220kV STNMD1Q01M1DIS AI CH-1 Code-3 Rx CH-1 Code-3 Rx (DT RECEIVE CHANNEL-1)
95 220kV STNMD1Q01M1DIS AI CH-2 Code-3 Tx CH-2 Code-3 Tx (DT SEND CHANNEL-2)
96 220kV STNMD1Q01M1DIS AI CH-2 Code-3 Rx CH-2 Code-3 Rx (DT RECEIVE CHANNEL-2)
97 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
98 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-2 Y Addition
99 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-3 Y Addition
100 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-4 Y Addition
101 220kV STNMD1Q01M1DIS SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-5 Y Addition
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR ICT DIFFERENTIAL RELAYS
IED name: R_RET670_87T
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/OEXPVPH1/Str/general SPI OVEREXCITATION HV START Y
2 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/OEXPVPH1/Alm/stVal SPI OVEREXCITATION HV ALARM Y
3 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/OEXPVPH1/Op/general SPI OVEREXCITATION HV TRIP Y
4 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/DifAlm/stVal SPI DIFFERENTIAL CURRENT ALARM Y
5 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/general SPI DIFFERENTIAL PROTECTION START Y
6 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsA SPI DIFFERENTIAL PROTECTION RPH START Y
7 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsB SPI DIFFERENTIAL PROTECTION YPH START Y
8 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsC SPI DIFFERENTIAL PROTECTION BPH START Y
9 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Op/general SPI DIFFERENTIAL PROTECTION TRIP Y
10 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION RPH TRIP Y
11 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION YPH TRIP Y
12 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION BPH TRIP Y
13 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/OpRst/stVal SPI DIFFERENTIAL PROTECTION TRIP (RESTRAINED MODE) Y
14 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/OpUnRst/stVal SPI DIFFERENTIAL PROTECTION TRIP (UNRESTRAINED MODE) Y
15 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Blk2H/stVal SPI DIFFERENTIAL PROTECTION 2nd HARMONIC BLOCK
16 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Blk5H/stVal SPI DIFFERENTIAL PROTECTION 5th HARMONIC BLOCK
17 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SMPPTRC1/Op/general SPI DIFFERENTIAL RELAY GENERAL TRIP Y
18 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
19 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/LPHD1/PhyHealth/stVal SPI DIFFRENTIAL IED UNHEALTHY Y
20 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI OTI ALARM Y APPLICABLE FOR 3 PHASE TRANSFORMERS
21 220kV STNMD1Q01TDIF SPI WTI HV ALARM Y
22 220kV STNMD1Q01TDIF SPI WTI IV ALARM Y
23 220kV STNMD1Q01TDIF SPI WTI MV ALARM Y
24 220kV STNMD1Q01TDIF SPI BUCCHOLZ_n ALARM Y Addition
25 220kV STNMD1Q01TDIF SPI BUCCHOLZ_n TRIP Y Text correction
26 220kV STNMD1Q01TDIF SPI OSR _n TRIP Y Text correction
27 220kV STNMD1Q01TDIF SPI PRD _n TRIP Y Text correction
28 220kV STNMD1Q01TDIF SPI FIRE PROTECTION OPERATED Y
29 220kV STNMD1Q01TDIF SPI LOW OIL LEVEL Y
30 220kV STNMD1Q01TDIF SPI OTI R PH ALARM Y APPLICABLE FOR SINGLE PHASE TRANSFORMERS (If a dedicated IED is provided for spare transformer protection, only spare phase signals are required to be used)
31 220kV STNMD1Q01TDIF SPI OTI Y PH ALARM Y
32 220kV STNMD1Q01TDIF SPI OTI B PH ALARM Y
33 220kV STNMD1Q01TDIF SPI OTI SPARE ICT ALARM Y
34 220kV STNMD1Q01TDIF SPI WTI HV R PH ALARM Y
35 220kV STNMD1Q01TDIF SPI WTI HV Y PH ALARM Y
36 220kV STNMD1Q01TDIF SPI WTI HV B PH ALARM Y
37 220kV STNMD1Q01TDIF SPI WTI HV SPARE ICT ALARM Y
38 220kV STNMD1Q01TDIF SPI WTI MV R PH ALARM Y
39 220kV STNMD1Q01TDIF SPI WTI MV Y PH ALARM Y
40 220kV STNMD1Q01TDIF SPI WTI MV B PH ALARM Y
41 220kV STNMD1Q01TDIF SPI WTI MV SPARE ICT ALARM Y
42 220kV STNMD1Q01TDIF SPI WTI IV R PH ALARM Y
43 220kV STNMD1Q01TDIF SPI WTI IV Y PH ALARM Y
44 220kV STNMD1Q01TDIF SPI WTI IV B PH ALARM Y
45 220kV STNMD1Q01TDIF SPI WTI IV SPARE ICT ALARM Y
46 220kV STNMD1Q01TDIF SPI BUCHHOLZ_n R PH ALARM Y Addition
47 220kV STNMD1Q01TDIF SPI BUCHHOLZ_n Y PH ALARM Y Addition
48 220kV STNMD1Q01TDIF SPI BUCHHOLZ_n B PH ALARM Y Addition
49 220kV STNMD1Q01TDIF SPI BUCHHOLZ_n SPARE ICT TRIP Y Addition, BUCHHOLZ_n SPARE ICT ALARM
50 220kV STNMD1Q01TDIF SPI BUCHHOLZ_n R PH TRIP Y Text correction
51 220kV STNMD1Q01TDIF SPI BUCHHOLZ_n Y PH TRIP Y Text correction
52 220kV STNMD1Q01TDIF SPI BUCHHOLZ_n B PH TRIP Y Text correction
53 220kV STNMD1Q01TDIF SPI BUCHHOLZ_n SPARE ICT TRIP Y Text correction
54 220kV STNMD1Q01TDIF SPI OSR_n R PH TRIP Y Text correction
55 220kV STNMD1Q01TDIF SPI OSR_n Y PH TRIP Y Text correction
56 220kV STNMD1Q01TDIF SPI OSR_n B PH TRIP Y Text correction
57 220kV STNMD1Q01TDIF SPI OSR_n SPARE ICT TRIP Y Text correction
58 220kV STNMD1Q01TDIF SPI PRD n R PH TRIP Y Text correction
59 220kV STNMD1Q01TDIF SPI PRD nY PH TRIP Y Text correction
60 220kV STNMD1Q01TDIF SPI PRD n B PH TRIP Y Text correction
61 220kV STNMD1Q01TDIF SPI PRD n SPARE ICT TRIP Y Text correction
62 220kV STNMD1Q01TDIF SPI LOW OIL LEVEL R PH Y
63 220kV STNMD1Q01TDIF SPI LOW OIL LEVEL Y PH Y
64 220kV STNMD1Q01TDIF SPI LOW OIL LEVEL B PH Y
65 220kV STNMD1Q01TDIF SPI LOW OIL LEVEL SPARE ICT Y
66 220kV STNMD1Q01TDIF SPI FIRE PROTECTION R PH OPERATED Y
67 220kV STNMD1Q01TDIF SPI FIRE PROTECTION Y PH OPERATED Y
68 220kV STNMD1Q01TDIF SPI FIRE PROTECTION B PH OPERATED Y
69 220kV STNMD1Q01TDIF SPI FIRE PROTECTION SPARE ICT OPERATED Y
70 220kV STNMD1Q01TDIF SPI TRIP RELAY 86 A HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
71 220kV STNMD1Q01TDIF SPI TRIP RELAY 86 B HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
72 220kV STNMD1Q01TDIF SPI GR A RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RET670, for SCADA to be configured from BCU
73 220kV STNMD1Q01TDIF SPI GR B RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RET670, for SCADA to be configured from BCU
74 220kV STNMD1Q01TDIF SPI REF RELAY FAIL Y
75 220kV STNMD1Q01TDIF SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
** It may be noted that the Body Protection alarms & trips have been Grouped into two separate relays Differential (Group A) & REF (Group B) relays. The hardwiring for same must be done accordingly and approved scheme shall be modified if required. Same is applicable for Reactor protection also.
76 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/OC4_1/OC4PTOC1/Str/general SPI TERTIARY 33kV PHASE OVERCURRENT START Y Addition
77 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/OC4_1/OC4PTOC1/Op/general SPI TERTIARY33kV PHASE OVERCURRENT TRIP Y Addition
78 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/EF4_1/EF4PTOC1/Str/general SPI TERTIARY 33kV PHASE EARTHFAULT START Y Addition
79 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/EF4_1/EF4PTOC1/Op/general SPI TERTIARY 33kV PHASE EARTHFAULT TRIP Y Addition
80 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/ROV2_1/ROV2PTOV1/Str/general SPI TERTIARY 33kV PHASE RESIDUAL OVERVOLTAGE START Y Addition
81 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/ROV2_1/ROV2PTOV1/OP/general SPI TERTIARY 33kV PHASE RESIDUAL OVERVOLTAGE TRIP Y Addition
82 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI TERTIARY 33kV 86 OPTD Y Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
83 220kV STNMD1Q01TDIF SPI TERTIARY TRAFO - BUCHHOLZ ALARM Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
84 220kV STNMD1Q01TDIF SPI TERTIARY TRAFO - BUCHHOLZ TRIP Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
85 220kV STNMD1Q01TDIF SPI TERTIARY TRAFO - WTI ALARM Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
86 220kV STNMD1Q01TDIF SPI TERTIARY TRAFO - WTI TRIP Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
87 220kV STNMD1Q01TDIF SPI TERTIARY TRAFO - OTI ALARM Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
88 220kV STNMD1Q01TDIF SPI TERTIARY TRAFO - OTI TRIP Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
89 220kV STNMD1Q01TDIF SPI TERTIARY TRAFO - PRD ALARM Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
90 220kV STNMD1Q01TDIF SPI TERTIARY TRAFO - PRD TRIP Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
91 220kV STNMD1Q01TDIF SPI TERTIARY 33KV_TC-1 FAULTY Y Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
92 220kV STNMD1Q01TDIF SPI TERTIARY 33KV_TC-2 FAULTY Y Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
93 220kV STNMD1Q01TDIF SPI TERTIARY 33kV CB ASSOCIATED ALARMS Y Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
94 220kV STNMD1Q01TDIF SPI RELAY IN TEST MODE Y Addition
95 220kV STNMD1Q01TDIF SPI SETTINGS CHANGED Y Addition
96 220kV STNMD1Q01TDIF SPI DR MEMORY 80% FULL Y Addition
97 220kV STNMD1Q01TDIF CMD DELUGE COMMAND APPLICABLE FOR 3 PHASE TRANSFORMERS Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
98 220kV STNMD1Q01TDIF CMD DELUGE COMMAND R PH APPLICABLE FOR SINGLE PHASE TRANSFORMERS (If a dedicated IED is provided for spare transformer protection, only spare phase signals are required to be used) Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
99 220kV STNMD1Q01TDIF CMD DELUGE COMMAND Y PH Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
100 220kV STNMD1Q01TDIF CMD DELUGE COMMAND B PH Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
101 220kV STNMD1Q01TDIF CMD DELUGE COMMAND SPARE Addition, This signal can be moved to BCU, Need to discuss As per the CRP scheme this will be configured in Main BCU/Aux. BCU
102 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL//EF4_1/EF4PTOC2/Str/general SPI NEUTRAL OVERCURRENT ALARM Y Addition As per the CRP scheme this will be configured in Main BCU/Aux. BCU
103 220kV STNMD1Q01TDIF SS_BAY_DIFFERENTIAL//LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
104 220kV STNMD1Q01TDIF SPI SPARE ALARM-2 Y Addition
105 220kV STNMD1Q01TDIF SPI SPARE ALARM-3 Y Addition
106 220kV STNMD1Q01TDIF SPI SPARE ALARM-4 Y Addition
107 220kV STNMD1Q01TDIF SPI SPARE ALARM-5 Y Addition
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR ICT REF RELAYS
IED name: R_RET670_64
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 220kV STNMD1Q01TREF SS_BAY_REF/LD0/OEXPVPH1/Str/general SPI OVEREXCITATION MV START
2 220kV STNMD1Q01TREF SS_BAY_REF/LD0/OEXPVPH1/Alm/stVal SPI OVEREXCITATION MV ALARM Y
3 220kV STNMD1Q01TREF SS_BAY_REF/LD0/OEXPVPH1/Op/general SPI OVEREXCITATION MV TRIP Y
4 220kV STNMD1Q01TREF SS_BAY_REF/LD0/HZPDIF1/Alm/stVal SPI REF ALARM
5 220kV STNMD1Q01TREF SS_BAY_REF/LD0/HZPDIF1/Op/general SPI REF TRIP Y
6 220kV STNMD1Q01TREF SS_BAY_REF/LD0/SMPPTRC1/Op/general SPI REF RELAY GENERAL TRIP Y
7 220kV STNMD1Q01TREF SS_BAY_REF/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
8 220kV STNMD1Q01TREF SS_BAY_REF/LD0/LPHD1/PhyHealth/stVal SPI REF IED UNHEALTHY Y
9 220kV STNMD1Q01TREF SS_BAY_REF/LD0/SP16GGIO n/Ind n/stVal SPI OTI TRIP Y APPLICABLE FOR 3 PHASE TRANSFORMERS
10 220kV STNMD1Q01TREF SPI WTI HV TRIP Y
11 220kV STNMD1Q01TREF SPI WTI MV TRIP Y
12 220kV STNMD1Q01TREF SPI WTI LV TRIP Y
13 220kV STNMD1Q01TREF SPI OSR 2 TRIP Y
14 220kV STNMD1Q01TREF SPI PRD 2 TRIP Y
15 220kV STNMD1Q01TREF SPI BUCCHOLZ_n ALARM Y Text correction
16 220kV STNMD1Q01TREF SPI BUCCHOLZ_n TRIP Y Addition
17 220kV STNMD1Q01TREF SPI OTI R PH TRIP Y APPLICABLE FOR SINGLE PHASE TRANSFORMERS (If a dedicated IED is provided for spare transformer protection, only spare phase signals are required to be used)
18 220kV STNMD1Q01TREF SPI OTI Y PH TRIP Y
19 220kV STNMD1Q01TREF SPI OTI B PH TRIP Y
20 220kV STNMD1Q01TREF SPI OTI SPARE ICT TRIP Y
21 220kV STNMD1Q01TREF SPI WTI HV R PH TRIP Y
22 220kV STNMD1Q01TREF SPI WTI HV Y PH TRIP Y
23 220kV STNMD1Q01TREF SPI WTI HV B PH TRIP Y
24 220kV STNMD1Q01TREF SPI WTI HV SPARE ICT TRIP Y
25 220kV STNMD1Q01TREF SPI WTI MV R PH TRIP Y
26 220kV STNMD1Q01TREF SPI WTI MV Y PH TRIP Y
27 220kV STNMD1Q01TREF SPI WTI MV B PH TRIP Y
28 220kV STNMD1Q01TREF SPI WTI MV SPARE ICT TRIP Y
29 220kV STNMD1Q01TREF SPI WTI IV R PH TRIP Y
30 220kV STNMD1Q01TREF SPI WTI IV Y PH TRIP Y
31 220kV STNMD1Q01TREF SPI WTI IV B PH TRIP Y
32 220kV STNMD1Q01TREF SPI WTI IV SPARE ICT TRIP Y
33 220kV STNMD1Q01TREF SPI BUCCHOLZ R PH ALARM Y
34 220kV STNMD1Q01TREF SPI BUCCHOLZ Y PH ALARM Y
35 220kV STNMD1Q01TREF SPI BUCCHOLZ B PH ALARM Y
36 220kV STNMD1Q01TREF SPI BUCCHOLZ SPARE ICT ALARM Y
37 220kV STNMD1Q01TREF SPI OSR 2 R PH TRIP Y
38 220kV STNMD1Q01TREF SPI OSR 2 Y PH TRIP Y
39 220kV STNMD1Q01TREF SPI OSR 2 B PH TRIP Y
40 220kV STNMD1Q01TREF SPI OSR 2 SPARE ICT TRIP Y
41 220kV STNMD1Q01TREF SPI PRD 2 R PH TRIP Y
42 220kV STNMD1Q01TREF SPI PRD 2 Y PH TRIP Y
43 220kV STNMD1Q01TREF SPI PRD 2 B PH TRIP Y
44 220kV STNMD1Q01TREF SPI PRD 2 SPARE ICT TRIP Y
45 220kV STNMD1Q01TREF SPI DIFFERENTIAL RELAY FAIL Y
46 220kV STNMD1Q01TREF SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
47 220kV STNMD1Q01TREF SPI RELAY IN TEST MODE Y Addition
48 220kV STNMD1Q01TREF SPI SETTINGS CHANGED Y Addition
49 220kV STNMD1Q01TREF SPI DR MEMORY 80% FULL Y Addition
50 220kV STNMD1Q01TREF SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
51 220kV STNMD1Q01TREF SPI SPARE ALARM-2 Y Addition
52 220kV STNMD1Q01TREF SPI SPARE ALARM-3 Y Addition
53 220kV STNMD1Q01TREF SPI SPARE ALARM-4 Y Addition
54 220kV STNMD1Q01TREF SPI SPARE ALARM-5 Y Addition
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR REACTOR ICT IMPEDANCE PROTECTION RELAY Additional Relay - The Impedance Preotection is not applicable for 220kV Voltage
IED name: R_REL670_21T
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/ZMCAPDIS1/Str/phsA SPI BACKUP IMPEDANCE START, Z1 R PH
2 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/ZMCAPDIS1/Str/phsB SPI BACKUP IMPEDANCE START, Z1 Y PH
3 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMPE/LD0/ZMCAPDIS1/Str/phsC SPI BACKUP IMPEDANCE START, Z1 B PH
4 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS1.Str.general SPI BACKUP IMPEDANCE START BACKUP IMPEDANCE ZONE-1 START Agreed
5 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS1.Op.general SPI BACKUP IMPEDANCE ZONE-1 TRIP Y
6 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/ZMCAPDIS2/Str/phsA SPI BACKUP IMPEDANCE START, Z2 R PH
7 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/ZMCAPDIS2/Str/phsB SPI BACKUP IMPEDANCE START, Z2 Y PH
8 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMPE/LD0/ZMCAPDIS2/Str/phsC SPI BACKUP IMPEDANCE START, Z2B PH
9 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS2.Str.general SPI BACKUP IMPEDANCE ZONE-2 START
10 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS2.Op.general SPI BACKUP IMPEDANCE ZONE-2 TRIP Y
11 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS3.Str.general SPI BACKUP IMPEDANCE ZONE-3 START
12 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS3.Op.general SPI BACKUP IMPEDANCE ZONE-3 TRIP Y
13 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS4.Str.general SPI BACKUP IMPEDANCE ZONE-4 START
14 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0.ZMHPDIS4.Op.general SPI BACKUP IMPEDANCE ZONE-4 TRIP Y
15 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SMPPTRC1/Op/general SPI BACKUP IMPEDANCE RELAY GENERAL TRIP Y
16 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/OC4_1/OC4PTOC1/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-1 START
17 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/OC4_1/OC4PTOC1/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-1 TRIP Y
18 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/EF4_1/EF4PTOC1/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-1 START
19 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/EF4_1/EF4PTOC1/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-1 TRIP Y
20 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/OC4_1/OC4PTOC2/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-2 START
21 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/OC4_1/OC4PTOC2/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-2 TRIP Y
22 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/EF4_1/EF4PTOC2/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-2 START
23 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/EF4_1/EF4PTOC2/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-2 TRIP Y
24 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP 3PH Y
25 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP R PH Y
26 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP Y PH Y
27 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SMPPTRC/*** SPI BACKUP IMPEDANCE GENERAL TRIP B PH Y
28 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
29 220kV STNMD1Q01THVBIMP SS_BAY_HV BACKUP IMP/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
30 220kV STNMD1Q01THVBIMP SPI BACKUP IMPEDANCE IED UNHEALTHY Y
31 220kV STNMD1Q01THVBIMP SPI RELAY IN TEST MODE Y
32 220kV STNMD1Q01THVBIMP SPI SETTINGS CHANGED Y
33 220kV STNMD1Q01THVBIMP SPI DR MEMORY 80% FULL Y
34 220kV STNMD1Q01THVBIMP SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
35 220kV STNMD1Q01THVBIMP SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
36 220kV STNMD1Q01THVBIMP SPI SPARE ALARM-2 Y
37 220kV STNMD1Q01THVBIMP SPI SPARE ALARM-3 Y
38 220kV STNMD1Q01THVBIMP SPI SPARE ALARM-4 Y
39 220kV STNMD1Q01THVBIMP SPI SPARE ALARM-5 Y
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR HV DIRECTIONAL OVERCURRENT AND EARTH FAULT RELAYS
IED name: R_REL670_HVBUP
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 220kV STNMD1Q01THBU SS_BAY_HV BACKUP OC EF/OC4_1/OC4PTOC1/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-1 START Text correction
2 220kV STNMD1Q01THBU SS_BAY_HV BACKUP OC EFE/OC4_1/OC4PTOC1/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-1 TRIP Y Text correction
3 220kV STNMD1Q01THBU SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTOC1/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-1 START Text correction
4 220kV STNMD1Q01THBU SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTOC1/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-1 TRIP Y Text correction
5 220kV STNMD1Q01THBU SS_BAY_HV BACKUP OC EF/OC4_1/OC4PTOC2/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-2 START if Non Directional then name has to be replaced with Directional to Non-Directional Addition
6 220kV STNMD1Q01THBU SS_BAY_HV BACKUP OC EF/OC4_1/OC4PTOC2/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-2 TRIP Y Addition
7 220kV STNMD1Q01THBU SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTOC2/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-2 START Addition
8 220kV STNMD1Q01THBU SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTOC2/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-2 TRIP Y Addition
9 220kV STNMD1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
10 220kV STNMD1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/SMPPTRC1/Op/general SPI GENERAL TRIP Y
11 220kV STNMD1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
12 220kV STNMD1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal SPI BACKUP OC/EF IED UNHEALTHY Y
13 220kV STNMD1Q01THBU SS_BAY_HV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y
14 220kV STNMD1Q01THBU SPI SETTINGS CHANGED Y Addition
15 220kV STNMD1Q01THBU SPI DR MEMORY 80% FULL Y Addition
16 220kV STNMD1Q01THBU SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme Addition
17 220kV STNMD1Q01THBU SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
18 220kV STNMD1Q01THBU SPI SPARE ALARM-2 Y Addition
19 220kV STNMD1Q01THBU SPI SPARE ALARM-3 Y Addition
20 220kV STNMD1Q01THBU SPI SPARE ALARM-4 Y Addition
21 220kV STNMD1Q01THBU SPI SPARE ALARM-5 Y Addition
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR LV DIRECTIONAL OVERCURRENT AND EARTH FAULT RELAYS
IED name: R_REL670_LVBUP
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 220kV STNMD1Q01TLBU SS_BAY_LV BACKUP OC EF/OC4_1/OC4PTOC1/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-1 START Text correction
2 220kV STNMD1Q01TLBU SS_BAY_LV BACKUP OC EFE/OC4_1/OC4PTOC1/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-1 TRIP Y Text correction
3 220kV STNMD1Q01TLBU SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTOC1/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-1 START Text correction
4 220kV STNMD1Q01TLBU SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTOC1/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-1 TRIP Y Text correction
5 220kV STNMD1Q01TLBU SS_BAY_LV BACKUP OC EF/OC4_1/OC4PTOC2/Str/general SPI DIRECTIONAL OVERCURRENT STAGE-2 START if Non Directional then name has to be replaced with Directional to Non-Directional Addition
6 220kV STNMD1Q01TLBU SS_BAY_LV BACKUP OC EF/OC4_1/OC4PTOC2/Op/general SPI DIRECTIONAL OVERCURRENT STAGE-2 TRIP Y Addition
7 220kV STNMD1Q01TLBU SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTOC2/Str/general SPI DIRECTIONAL EARTHFAULT STAGE-2 START Addition
8 220kV STNMD1Q01TLBU SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTOC2/Op/general SPI DIRECTIONAL EARTHFAULT STAGE-2 TRIP Y Addition
9 220kV STNMD1Q01TLBU SS_BAY_LV BACKUP OC EF/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
10 220kV STNMD1Q01TLBU SS_BAY_LV BACKUP OC EF/LD0/SMPPTRC1/Op/general SPI GENERAL TRIP Y
11 220kV STNMD1Q01TLBU SS_BAY_LV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
12 220kV STNMD1Q01TLBU SS_BAY_LV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal SPI BACKUP OC/EF IED UNHEALTHY Y
13 220kV STNMD1Q01TLBU SS_BAY_LV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
14 220kV STNMD1Q01TLBU SPI SETTINGS CHANGED Y Addition
15 220kV STNMD1Q01TLBU SPI DR MEMORY 80% FULL Y Addition
16 220kV STNMD1Q01TLBU SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
REQUIRED SIGNALS FOR REACTOR DIFFERENTIAL RELAYS
IED name: R_RET670_87R
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Op/general SPI DIFFERENTIAL PROTECTION TRIP Y
2 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION RPH TRIP Y
3 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION YPH TRIP Y
4 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION BPH TRIP Y
5 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/DifAlm/stVal SPI DIFFERENTIAL CURRENT ALARM
6 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/general SPI DIFFERENTIAL PROTECTION START
7 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsA SPI DIFFERENTIAL PROTECTION RPH START
8 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsB SPI DIFFERENTIAL PROTECTION YPH START
9 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsC SPI DIFFERENTIAL PROTECTION BPH START
10 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SMPPTRC1/Op/general SPI DIFFERENTIAL RELAY GENERAL TRIP Y
11 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/OpRst/stVal SPI DIFFERENTIAL PROTECTION TRIP (RESTRAINED MODE) Y Addition
12 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/OpUnRst/stVal SPI DIFFERENTIAL PROTECTION TRIP (UNRESTRAINED MODE) Y Addition
13 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Blk2H/stVal SPI DIFFERENTIAL PROTECTION 2nd HARMONIC BLOCK Addition
14 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Blk5H/stVal SPI DIFFERENTIAL PROTECTION 5th HARMONIC BLOCK Addition
15 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI BUSBAR PROT OPTD Y Addition, Need to discuss Only for DR in RET670, for SCADA to be configured from BBP relay
16 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI TIME SYNCHRONIZATION ERROR Y
17 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/LPHD1/PhyHealth/stVal SPI DIFFERENTIAL IED UNHEALTHY Y *
18 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI OTI TRIP Y APPLICABLE FOR 3 PHASE REACTORS Interchanged between Diff. & REF relays
19 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI WTI ALARM Y Already available
20 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI BUCCHOLZ-A TRIP Y Addition
21 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI BUCCHOLZ-B ALARM Y Addition
22 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI PRV-1 TRIP(NO) Y Text correction
23 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI FIRE PROTECTION OPERATED Y Already available
24 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI LOW OIL LEVEL ALARM Y Already available
25 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI PRV-1 TRIP(NC) Y Addition, Need to discuss Yet to be finalized by PGCIL
26 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI FLOW SENSITIVE CONSERVATOR VALVE ALARM Y Addition
27 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI REACTOR MB ALARMS Y Addition
28 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI OTI R PH ALARM Y APPLICABLE FOR SINGLE PHASE REACTORS (If a dedicated IED is provided for spare reactor protection, only spare phase signals are required to be used)
29 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI OTI Y PH ALARM Y
30 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI OTI B PH ALARM Y
31 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI OTI SPARE PH ALARM Y
32 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI WTI R PH ALARM Y
33 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI WTI Y PH ALARM Y
34 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI WTI B PH ALARM Y
35 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI WTI SPARE PH ALARM Y
36 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI BUCCHOLZ_n R PH ALARM Y Interchanged between Diff. & REF relays
37 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI BUCCHOLZ_n Y PH ALARM Y Interchanged between Diff. & REF relays
38 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI BUCCHOLZ_n B PH ALARM Y Interchanged between Diff. & REF relays
39 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI BUCCHOLZ_n SPARE PH ALARM Y Interchanged between Diff. & REF relays
40 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI BUCCHOLZ_n R PH TRIP Y Text correction
41 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI BUCCHOLZ_n Y PH TRIP Y Text correction
42 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI BUCCHOLZ_n B PH TRIP Y Text correction
43 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI BUCCHOLZ_n SPARE PH TRIP Y Text correction
44 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI OSR R PH TRIP Y
45 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI OSR Y PH TRIP Y
46 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI OSR B PH TRIP Y
47 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI OSR SPARE PH TRIP Y
48 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI PRD R PH TRIP Y Yet to be finalized by PGCIL
49 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI PRD Y PH TRIP Y Yet to be finalized by PGCIL
50 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI PRD B PH TRIP Y Yet to be finalized by PGCIL
51 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI PRD SPARE PH TRIP Y
52 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI LOW OIL LEVEL R PH Y
53 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI LOW OIL LEVEL Y PH Y
54 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI LOW OIL LEVEL B PH Y
55 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI LOW OIL LEVEL SPARE PH Y
56 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI FIRE PROTECTION R PH OPERATED Y
57 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI FIRE PROTECTION Y PH OPERATED Y
58 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI FIRE PROTECTION B PH OPERATED Y
59 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI FIRE PROTECTION SPARE ICT OPERATED Y
60 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI TRIP RELAY 86 A HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
61 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI TRIP RELAY 86 B HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
62 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI GR A RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RET670, for SCADA to be configured from BBP relay
63 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI GR B RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RET670, for SCADA to be configured from BBP relay
64 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI GR A RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Available in RET670 (Sig. 62)
65 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI GR B RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Available in RET670 (Sig. 63)
66 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI REF RELAY FAIL Y
67 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI RELAY IN TEST MODE Y Addition
68 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI SETTINGS CHANGED Y Addition
69 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI DR MEMORY 80% FULL Y Addition
70 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
71 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
72 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI SPARE ALARM-2 Y Addition
73 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI SPARE ALARM-3 Y Addition
74 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI SPARE ALARM-4 Y Addition
75 220kV STNMD1Q01LRDIF /STNMD1Q01BRDIF SPI SPARE ALARM-5 Y Addition
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR REACTOR REF RELAYS
IED name: R_RET670_64R
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SS_BAY_REF/LD0/HZPDIF1/Alm/stVal SPI REF ALARM
2 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SS_BAY_REF/LD0/HZPDIF1/Op/general SPI REF TRIP Y
3 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SS_BAY_REF/LD0/SMPPTRC1/Op/general SPI REF RELAY GENERAL TRIP Y
4 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SS_BAY_REF/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
5 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SS_BAY_REF/LD0/LPHD1/PhyHealth/stVal SPI REF IED UNHEALTHY Y
6 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SS_BAY_REF/LD0/SP16GGIO n/Ind n/stVal SPI OTI ALARM Y APPLICABLE FOR 3 PHASE REACTORS Interchanged between Diff. & REF relays
7 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI WTI TRIP Y Already available
8 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI BUCCHOLZ-A ALARM Y Addition
9 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI BUCCHOLZ-B TRIP Y Addition
10 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI PRV-2 TRIP Y Addition
11 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI FIRE PROTECTION OPERATED Y Addition
12 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI HIGH LEVEL OIL ALARM Y Addition
13 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI 86B TRIP RELAY SUPERVSION ALARM Y Addition, Need to discuss
14 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI REACTOR MB ALARMS Y Addition
15 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI OTI R PH TRIP Y APPLICABLE FOR SINGLE PHASE REACTORS (If a dedicated IED is provided for spare Reactor protection, only spare phase signals are required to be used)
16 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI OTI Y PH TRIP Y
17 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI OTI B PH TRIP Y
18 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI OTI SPARE PH TRIP Y
19 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI WTI R PH TRIP Y
20 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI WTI Y PH TRIP Y
21 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI WTI B PH TRIP Y
22 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI WTI SPARE PH TRIP Y
23 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI BUCCHOLZ R PH ALARM Y
24 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI BUCCHOLZ Y PH ALARM Y
25 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI BUCCHOLZ B PH ALARM Y
26 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI BUCCHOLZ SPARE PH ALARM Y
27 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI DIFFERENTIAL RELAY FAIL Y
28 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI RELAY IN TEST MODE Y Addition
29 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI SETTINGS CHANGED Y Addition
30 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI DR MEMORY 80% FULL Y Addition
31 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
32 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI SPARE ALARM-2 Y Addition
33 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI SPARE ALARM-3 Y Addition
34 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI SPARE ALARM-4 Y Addition
35 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI SPARE ALARM-5 Y Addition
36 220kV STNMD1Q01LRREF /STNMD1Q01BRREF SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR REACTOR BACKUP IMPEDANCE PROTECTION RELAY
IED name: R_REL670_21R
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SS_BAY_HV BACKUP OC EF/LD0.ZMHPDIS1.Str.general SPI BACKUP IMPEDANCE START
2 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SS_BAY_HV BACKUP OC EF/LD0.ZMHPDIS1.Op.general SPI BACKUP IMPEDANCE TRIP Y
3 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SS_BAY_HV BACKUP OC EF/LD0/SMPPTRC1/Op/general SPI BACKUP IMPEDANCE RELAY GENERAL TRIP Y
4 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SS_BAY_HV BACKUP OC EF/OC4_1/OC4PTOC1/Str/general SPI BACKUP OVERCURRENT START No of stage Overcurrent need to be monitored
5 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SS_BAY_HV BACKUP OC EF/OC4_1/OC4PTOC1/Op/general SPI BACKUP OVERCURRENT TRIP Y
6 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTOC1/Str/general SPI BACKUP EARTHFAULT START
7 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTOC1/Op/general SPI BACKUP EARTHFAULT TRIP Y
8 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SS_BAY_HV BACKUP OC EF/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
9 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SS_BAY_HV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
10 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SS_BAY_HV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal SPI BACKUP IMPEDANCE IED UNHEALTHY Y
11 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SS_BAY_HV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal SPI NGR BUCHHOLZ ALARM Y For Line Reactor NGR associated alarms Addition
12 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI NGR BUCHHOLZ TRIP Y Addition
13 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI NGR OTI ALARM Y Addition
14 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI NGR OTI TRIP Y Addition
15 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI NGR WTI ALARM Y Addition
16 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI NGR WTI TRIP Y Addition
17 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI NGR OSR TRIP Y Addition
18 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI NGR CB ASSOCIATED ALARMS Y All NGC CB associated alarms to be monitored Addition
19 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI NGR BYPASS ISOLATOR ASSOCIATED ALARMS Y All NGR Bypass Isolator associated alarms to be monitored Addition
20 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI BACKUP IMPEDANCE IED UNHEALTHY Y Addition
21 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP CMD NGR BYPASS COMMAND Y Addition
22 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI RELAY IN TEST MODE Y Addition
23 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI SETTINGS CHANGED Y Addition
24 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI DR MEMMORY 80% FULL Y Addition
25 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
26 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
27 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI SPARE ALARM-2 Y Addition
28 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI SPARE ALARM-3 Y Addition
29 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI SPARE ALARM-4 Y Addition
30 220kV STNMD1Q01LRBIMP /STNMD1Q01BRBIMP SPI SPARE ALARM-5 Y Addition
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR BUSBAR PROTECTION RELAYS (DECENTRALIZED) - REB 500
IED name: BB_REB500_87B
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BCZ_PDIF1/DifAlm SPI BUSBAR CHECKZONE ALARM Y Addition
2 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BCZ_PDIF1/Op/general SPI BUSBAR CHECKZONE TRIP Y Addition
3 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/CALH1/GrAlm2/stVal SPI BUSBAR CT CIRCUIT ERROR Y Agreed
4 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BBP_PDIF1/Op/PhsA SPI BUSBAR ZONE 1 TRIP R- PHASE Y Addition, BUSBAR TRIP R- PHASE is configurable (Zone1/2/3 phasewise trip signal is not configurable)
5 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BBP_PDIF1/Op/PhsB SPI BUSBAR ZONE 1 TRIP Y- PHASE Y Addition, BUSBAR TRIP Y- PHASE Is configurable (Zone1/2/3 phasewise trip signal is not configurable)
6 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BBP_PDIF1/Op/PhsC SPI BUSBAR ZONE 1 TRIP B- PHASE Y Addition, BUSBAR TRIP B- PHASE Is configurable (Zone1/2/3 phasewise trip signal is not configurable)
7 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BBP_PDIF1/Op/general SPI BUSBAR ZONE 1 TRIP Y
8 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BZ_PDIF1/Blk SPI BUSBAR ZONE 1 BLOCKED Y
9 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI BREAKER FAILURE - BUSBAR 1 BLOCKED Y Addition, Need to discuss (Signal not configurable), Sig. 8 (BUSBAR ZONE 1 BLOCKED) is common blocking signal which will active when busbar blocked from external switch, Isolator intermidiate status, CT Circuit error conditions)
10 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BBP_PDIF1/DifAlm SPI BUSBAR ZONE-1 CT CIRCUIT ERROR Y BUSBAR CT CIRCUIT ERROR is configured in Signal No.-03 (Zone1/2/3 CT CIRCUIT signal not configurable)
11 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI BUSBAR ZONE 1 BLOCKED EXTERNAL BY SWITCH Y
12 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BBP_PDIF2/Op/PhsA SPI BUSBAR ZONE 2 TRIP R- PHASE Y Addition, BUSBAR TRIP R- PHASE is configurable (Zone1/2/3 phasewise trip signal is not configurable)
13 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BBP_PDIF2/Op/PhsB SPI BUSBAR ZONE 2 TRIP Y- PHASE Y Addition, BUSBAR TRIP Y- PHASE Is configurable (Zone1/2/3 phasewise trip signal is not configurable)
14 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BBP_PDIF2/Op/PhsC SPI BUSBAR ZONE 2 TRIP B- PHASE Y Addition, BUSBAR TRIP B- PHASE Is configurable (Zone1/2/3 phasewise trip signal is not configurable)
15 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BBP_PDIF2/Op/general SPI BUSBAR ZONE 2 TRIP Y
16 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BZ_PDIF2/Blk SPI BUSBAR ZONE 2 BLOCKED Y
17 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI BREAKER FAILURE - BUSBAR 2 BLOCKED Y Addition, Need to discuss (Signal not configurable), Sig. 15 (BUSBAR ZONE 2 BLOCKED) is common blocking signal which will active when busbar blocked from external switch, Isolator intermidiate status, CT Circuit error conditions)
18 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BBP_PDIF2/DifAlm SPI BUSBAR ZONE-2 CT CIRCUIT ERROR Y BUSBAR CT CIRCUIT ERROR is configured in Signal No.-03 (Zone1/2/3 CT CIRCUIT signal not configurable)
19 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI BUSBAR ZONE 2 BLOCKED EXTERNAL BY SWITCH Y
20 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BBP_PDIF3/Op/PhsA SPI BUSBAR ZONE 3 TRIP R- PHASE Y Addition, BUSBAR TRIP R- PHASE is configurable (Zone1/2/3 phasewise trip signal is not configurable)
21 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BBP_PDIF3/Op/PhsB SPI BUSBAR ZONE 3 TRIP Y- PHASE Y Addition, BUSBAR TRIP Y- PHASE Is configurable (Zone1/2/3 phasewise trip signal is not configurable)
22 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BBP_PDIF3/Op/PhsC SPI BUSBAR ZONE 3 TRIP B- PHASE Y Addition, BUSBAR TRIP B- PHASE Is configurable (Zone1/2/3 phasewise trip signal is not configurable)
23 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BBP_PDIF3/Op/general SPI BUSBAR ZONE 3 TRIP Y
24 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BZ_PDIF3/Blk SPI BUSBAR ZONE 3 BLOCKED Y
25 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI BREAKER FAILURE - BUSBAR 3 BLOCKED Y Addition, Need to discuss (Signal not configurable), Sig. 16 (BUSBAR ZONE 3 BLOCKED) is common blocking signal which will active when busbar blocked from external switch, Isolator intermidiate status, CT Circuit error conditions)
26 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/BBP_PDIF3/DifAlm SPI BUSBAR ZONE-3 CT CIRCUIT ERROR Y BUSBAR CT CIRCUIT ERROR is configured in Signal No.-03 (Zone1/2/3 CT CIRCUIT signal not configurable)
27 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI BUSBAR ZONE 3 BLOCKED EXTERNAL BY SWITCH Y
28 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/CALH1/GrAlm1/stVal SPI ISOLATOR IN INTERMEDIATE STATUS Y TO BE USED RELATES TO STATUS OF SWITCHING ELEMENT Addition 0
29 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB0/BP_n/PTRC/Tr/general SPI BAY N TRIP Y For each Bays Addition
30 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB0 n/LPHD n/PhyHealth/stVal SPI BUSBAR BLOCKED DUE TO COMMUNICATION ERROR_Bay_n Y For each Bays Addition
31 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB0/BP_n/GAPC/Ind08/stVal SPI BAY_N_BREAKER FAILURE R-PH INITIATION Y For each Bays Addition
32 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB0/BP_n/GAPC/Ind09/stVal SPI BAY_N_BREAKER FAILURE Y-PH INITIATION Y For each Bays Addition
33 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB0/BP_n/GAPC/Ind10/stVal SPI BAY_N_BREAKER FAILURE B-PH INITIATION Y For each Bays Addition
34 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB0/BP_n/GAPC/Ind11/stVal SPI BAY_N_BREAKER FAILURE 3PH INITIATION Y For each Bays Addition
35 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB0/BP_n/GAPC/Ind04/stVal SPI BAY_N_EXTERNAL BUSBAR ZONE n Y For signals where BB tripped through External Tripping commands(GD, Half Dia) Addition
36 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB0/BP_n/RBRF/OpIn/general SPI BAY_N_BREAKER FAILURE RETRIP Y For each Bays Addition
37 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB0/BP_n/RBRF/OpEx/general SPI BAY_N_BREAKER FAILURE BACKTRIP Y For each Bays Addition
38 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB0/BP_n/RBRF/OpIn/PhsA SPI BAY_N_BREAKER FAILURE RPH- RETRIP Y For each Bays Addition
39 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB0/BP_n/RBRF/OpIn/PhsB SPI BAY_N_BREAKER FAILURE YPH- RETRIP Y For each Bays Addition
40 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB0/BP_n/RBRF/OpIn/PhsC SPI BAY_N_BREAKER FAILURE BPH- RETRIP Y For each Bays Addition
41 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/LPHD1/PhyHealth/stVal SPI BBP CENTRAL UNIT IED UNHEALTHY Y
42 220kV STNMD1BBM1 SS_BAY_BUSBAR/ABB00/GGIO1/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
43 220kV STNMD1BBM1 SPI SETTINGS CHANGED Y Addition, Signal not configurable
44 220kV STNMD1BBM1 SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme Addition
45 220kV STNMD1BBM1 SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
46 220kV STNMD1BBM1 SPI SPARE ALARM-2 Y Addition
47 220kV STNMD1BBM1 SPI SPARE ALARM-3 Y Addition
48 220kV STNMD1BBM1 SPI SPARE ALARM-4 Y Addition
49 220kV STNMD1BBM1 SPI SPARE ALARM-5 Y Addition
50 220kV STNMD1BBM1 SPI SPARE ALARM-6 Y Addition
51 220kV STNMD1BBM1 SPI SPARE ALARM-7 Y Addition
52 220kV STNMD1BBM1 SPI SPARE ALARM-8 Y Addition
53 220kV STNMD1BBM1 SPI SPARE ALARM-9 Y Addition
54 220kV STNMD1BBM1 SPI SPARE ALARM-10 Y Addition
55 220kV STNMD1BBM1 SPI ZONE-1 AND ZONE-2 INTERCONNECTED Y Addition, Signal not configurable
56 220kV STNMD1BBM1 SPI ZONE-1 AND ZONE-3 INTERCONNECTED Y Addition, Signal not configurable
57 220kV STNMD1BBM1 SPI ZONE-2 AND ZONE-3 INTERCONNECTED Y Addition, Signal not configurable
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR BUSBAR PROTECTION RELAYS (CENTRALIZED) - REB 670
IED name: BB_REB670_87B
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 220kV STNMD1BBM1 SS_BAY_BUSBAR/BBS/BZBSPDIF1/Op/general SPI BUSBAR ZONE 1 TRIP Y BBS - Single Phase & BBT-Three Phase Variant. STNMD1BBM1R/Y/B if phasewise Busbar IEDs are deployed.
2 220kV STNMD1BBM1 SS_BAY_BUSBAR/BBS/BZBSPDIF2/Op/general SPI BUSBAR ZONE 2 TRIP Y
3 220kV STNMD1BBM1 SS_BAY_BUSBAR/BBS/BBSPDIF1/Op/general SPI BUSBAR ZONE 3 TRIP Y
4 220kV STNMD1BBM1 SS_BAY_BUSBAR/BBS/BZBSPDIF1/OpnCTAlm/stVal SPI BUSBAR ZONE 1 CT CIRCUIT ERROR Y
5 220kV STNMD1BBM1 SS_BAY_BUSBAR/BBS/BZBSPDIF2/OpnCTAlm/stVal SPI BUSBAR ZONE 2 CT CIRCUIT ERROR Y
6 220kV STNMD1BBM1 SS_BAY_BUSBAR/BBS/BBSPDIF1/OpnCTAlm/stVal SPI BUSBAR ZONE 3 CT CIRCUIT ERROR Y
7 220kV STNMD1BBM1 SS_BAY_BUSBAR/LD0/SP16GGIO n /Ind n/stVal SPI BUSBAR ZONE 1 BLOCKED EXTERNAL BY SWITCH Y
8 220kV STNMD1BBM1 SS_BAY_BUSBAR/LD0/SP16GGIO n /Ind n/stVal SPI BUSBAR ZONE 2 BLOCKED EXTERNAL BY SWITCH Y
9 220kV STNMD1BBM1 SS_BAY_BUSBAR/LD0/SP16GGIO n /Ind n/stVal SPI BUSBAR ZONE 3 BLOCKED EXTERNAL BY SWITCH Y
10 220kV STNMD1BBM1 SS_BAY_BUSBAR/LD0/SP16GGIO n /Ind n/stVal SPI BUSBAR ZONE 1 PROTECTION BLOCKED Y
11 220kV STNMD1BBM1 SS_BAY_BUSBAR/LD0/SP16GGIO n /Ind n/stVal SPI BUSBAR ZONE 2 PROTECTION BLOCKED Y
12 220kV STNMD1BBM1 SS_BAY_BUSBAR/LD0/SP16GGIO n /Ind n/stVal SPI BUSBAR ZONE 3 PROTECTION BLOCKED Y
13 220kV STNMD1BBM1 SS_BAY_BUSBAR/BBS6/BCZPDIF1/Op/general SPI BUSBAR CHECKZONE TRIP Y
14 220kV STNMD1BBM1 SS_BAY_BUSBAR/BBS/BBSPTRC n/Tr/general SPI BAY n TRIP Y **** If Bay Breaker Failure function internally utilised then BFP related Initiation, Retrip, Backtrip & other signal refered with Standalone LBB relay.
15 220kV STNMD1BBM1 SS_BAY_BUSBAR/LD0/SP16GGIO n/Ind n/stVal SPI BAY n BREAKER FAILURE BACKUP TRIP Y For each bay signals to be configured and reported Addition
16 220kV STNMD1BBM1 SS_BAY_BUSBAR/LD0/SP16GGIO n/Ind n/stVal SPI LCC BUSBAR GAS ZONE TRIP Y IF Applicable for GIS Addition
17 220kV STNMD1BBM1 SS_BAY_BUSBAR/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
18 220kV STNMD1BBM1 SS_BAY_BUSBAR/LD0/LPHD1/PhyHealth/stVal SPI BBP IED UNHEALTHY Y
19 220kV STNMD1BBM1 SS_BAY_BUSBAR/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
20 220kV STNMD1BBM1 SPI SETTINGS CHANGED Y Addition
21 220kV STNMD1BBM1 SPI DR MEMMORY 80% FULL Y Addition
22 220kV STNMD1BBM1 SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
23 220kV STNMD1BBM1 SPI SPARE ALARM-2 Y Addition
24 220kV STNMD1BBM1 SPI SPARE ALARM-3 Y Addition
25 220kV STNMD1BBM1 SPI SPARE ALARM-4 Y Addition
26 220kV STNMD1BBM1 SPI SPARE ALARM-5 Y Addition
27 220kV STNMD1BBM1 SPI SPARE ALARM-6 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
28 220kV STNMD1BBM1 SPI SPARE ALARM-7 Y Addition
29 220kV STNMD1BBM1 SPI SPARE ALARM-8 Y Addition
30 220kV STNMD1BBM1 SPI SPARE ALARM-9 Y Addition
31 220kV STNMD1BBM1 SPI SPARE ALARM-10 Y Addition
32 220kV STNMD1BBM1 SPI BUSBAR ZONE 1 TRIP R- PHASE Y Addition
33 220kV STNMD1BBM1 SPI BUSBAR ZONE 1 TRIP Y- PHASE Y Addition
34 220kV STNMD1BBM1 SPI BUSBAR ZONE 1 TRIP B- PHASE Y Addition
35 220kV STNMD1BBM1 SPI BUSBAR ZONE 2 TRIP R- PHASE Y Addition
36 220kV STNMD1BBM1 SPI BUSBAR ZONE 2 TRIP Y- PHASE Y Addition
37 220kV STNMD1BBM1 SPI BUSBAR ZONE 2 TRIP B- PHASE Y Addition
38 220kV STNMD1BBM1 SPI BUSBAR ZONE 3 TRIP R- PHASE Y Addition
39 220kV STNMD1BBM1 SPI BUSBAR ZONE 3 TRIP Y- PHASE Y Addition
40 220kV STNMD1BBM1 SPI BUSBAR ZONE 3 TRIP B- PHASE Y Addition
41 220kV STNMD1BBM1 SS_BAY_BUSBAR/LD0/SP16GGIO n/Ind n/stVal SPI ZONE-1 AND ZONE-2 INTERCONNECTED Y Addition
42 220kV STNMD1BBM1 SPI ZONE-1 AND ZONE-3 INTERCONNECTED Y Addition
43 220kV STNMD1BBM1 SPI ZONE-2 AND ZONE-3 INTERCONNECTED Y Addition
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR BREAKER FAILURE PROTECTION RELAY
IED name: R_RELAY NAME_50BFR
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILURE/LD0/GGIO n/ST/ Ind n SPI BREAKER FAILURE PROTECTION START Y
2 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpEx/general SPI BREAKER FAILURE BACKUP TRIP Y Text correction
3 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpIn/general SPI BREAKER FAILURE RETRIP Y
4 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpIn/PhsA SPI BREAKER FAILURE RETRIP RPH Y Addition
5 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpIn/PhsB SPI BREAKER FAILURE RETRIP YPH Y Addition
6 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpIn/PhsC SPI BREAKER FAILURE RETRIP BPH Y Addition
7 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILURE/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
8 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILURE/LD0/LPHD1/PhyHealth/stVal SPI BFP IED UNHEALTHY Y
9 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI BREAKER FAILURE R-PHASE INITIATION FROM M1/M2 Y Addition
10 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI BREAKER FAILURE Y-PHASE INITIATION FROM M1/M2 Y Addition
11 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI BREAKER FAILURE B-PHASE INITIATION FROM M1/M2 Y Addition
12 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI BREAKER FAILURE 3-PHASE INITIATION FROM 86A/86B/BB Y Addition
13 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI BREAKER FAILURE FROM LCC (If applicable) Y If applicable for GIS LCC Addition
14 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI IV GR-A INT TRIP RELAY OPTD (If applicable) Y Addition
15 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI IV GR-B INT TRIP RELAY OPTD (If applicable) Y Addition
16 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
17 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI SETTINGS CHANGED Y Addition
18 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILUR/LD0/SP16GGIO n/Ind n/stVal SPI DR MEMMORY 80% FULL Y Addition
19 220kV STNMD1Q1BFR SS_BAY_BREAKER FAILURE/LD0/SP16GGIO n/Ind n/stVal SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
20 220kV STNMD1Q1BFR SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
21 220kV STNMD1Q1BFR SPI SPARE ALARM-2 Y Addition
22 220kV STNMD1Q1BFR SPI SPARE ALARM-3 Y Addition
23 220kV STNMD1Q1BFR SPI SPARE ALARM-4 Y Addition
24 220kV STNMD1Q1BFR SPI SPARE ALARM-5 Y Addition
ANY ADDITIONAL SIGNAL AS PER SCHEME
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
REQUIRED SIGNALS FOR BAY CONTROL UNIT
IED name: R_REC670_BCU
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS ADDITIONAL REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/QCBAY1/LocSwPos/stVal INT BCU IN LOCAL/ REMOTE *
2 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/Op/general SPI CLOSE COMMAND FROM BCU FOR AUTORECLOSE FOR BCUs HAVING AUTORECLSOURE FUNCTION INBUILT
3 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI GR-A TRIP RELAY FAULTY Y Addition
4 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI GR-B TRIP RELAY FAULTY Y Addition
5 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI DT RECEIVE CHANNEL-1 Y Addition, Available in REL670 Only for DR in REL670, for SCADA to be configured from BCU
6 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI DT RECEIVE CHANNEL-2 Y Addition, Available in REL670 Only for DR in REL670, for SCADA to be configured from BCU
7 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/AutoRecSt/StVal SPI AUTORECLOSE FUNCTION ON Y Addition
8 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/AutoRecSt/StVal SPI AUTORECLOSE FUNCTION OFF Y Addition
9 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI START AUTORECLOSE FUNCTION Y Addition
10 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/BlkRec/stVal SPI BLOCK AUTORECLOSE FUNCTION Y
11 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/Prp3PhOp/stVal SPI PREPARE 3PH TRIP AUTORECLOSE Y
12 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/RdyRec/stVal SPI AUTORECLOSE FUNCTION READY Text correction
13 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/ActRec/stVal AUTORECLOSE IN PROGRESS Y Text correction
14 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/SucRec/stVal AUTORECLOSE SUCCESSFUL Y Text correction
15 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SMBRREC1/UnsRec/stVal AUTORECLOSE UNSUCCESSFUL Y Text correction
16 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SXCBR1/Pos/stVal DPI BAY_CB R PH POSITION
17 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SXCBR2/Pos/stVal DPI BAY_CB Y PH POSITION
18 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SXCBR3/Pos/stVal DPI BAY_CB B PH POSITION
19 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI1/Pos/stVal DPI BAY_CB POSITION
20 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI1/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI1/Pos/ctlOperOn for Close CMD BAY_CB_COMMAND CLOSE / OPEN
21 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO1/EnaOpn/stVal SPI BAY_CB_OPEN PERMITTED OR ENABLED
22 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO1/EnaCls/stVal SPI BAY_CB_CLOSE PERMITTED OR ENABLED
23 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI2/Pos/stVal DPI BAY_89A_ISOLATOR POSITION
24 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI2/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI2/Pos/ctlOperOn for Close CMD BAY_89A_ISO COMMAND CLOSE / OPEN
25 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO2/EnaOpn/stVal SPI BAY_89A_ISO OPEN PERMITTED OR ENABLED
26 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO2/EnaCls/stVal SPI BAY_89A_ISO CLOSE PERMITTED OR ENABLED
27 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI3/Pos/stVal DPI BAY_89AE_ISOLATOR POSITION
28 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI3/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI3/Pos/ctlOperOn for Close CMD BAY_89AE_ISO COMMAND CLOSE / OPEN
29 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO3/EnaOpn/stVal SPI BAY_89AE_ISO OPEN PERMITTED OR ENABLED
30 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO3/EnaCls/stVal SPI BAY_89AE_ISO CLOSE PERMITTED OR ENABLED
31 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI4/Pos/stVal DPI BAY_89B_ISOLATOR POSITION
32 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI4/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI4/Pos/ctlOperOn for Close CMD BAY_89B_ISO COMMAND CLOSE / OPEN
33 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO4/EnaOpn/stVal SPI BAY_89B_ISO OPEN PERMITTED OR ENABLED
34 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO4/EnaCls/stVal SPI BAY_89B_ISO CLOSE PERMITTED OR ENABLED
35 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI5/Pos/stVal DPI BAY_89AE_ISOLATOR POSITION
36 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI5/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI5/Pos/ctlOperOn for Close CMD BAY_89AE_ISO COMMAND CLOSE / OPEN
37 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO5/EnaOpn/stVal SPI BAY_89AE_ISO OPEN PERMITTED OR ENABLED
38 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO5/EnaCls/stVal SPI BAY_89AE_ISO CLOSE PERMITTED OR ENABLED
39 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI6/Pos/stVal DPI BAY_89L/T/BR_ISOLATOR POSITION
40 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI6/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI6/Pos/ctlOperOn for Close CMD BAY_89L/T/BR_ISO COMMAND CLOSE / OPEN
41 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO6/EnaOpn/stVal SPI BAY_89L/T/BR_ISO OPEN PERMITTED OR ENABLED
42 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO6/EnaCls/stVal SPI BAY_89L/T/BR_ISO CLOSE PERMITTED OR ENABLED
43 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI7/Pos/stVal DPI BAY_89LE/TE/BRE_ISOLATOR POSITION
44 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI7/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI7/Pos/ctlOperOn for Close CMD BAY_89LE/TE/BRE_ISO COMMAND CLOSE / OPEN
45 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO7/EnaOpn/stVal SPI BAY_89LE/TE/BRE_ISO OPEN PERMITTED OR ENABLED
46 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO7/EnaCls/stVal SPI BAY_89LE/TE/BRE_ISO CLOSE PERMITTED OR ENABLED
47 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI8/Pos/stVal DPI BAY_89C_ISOLATOR POSITION
48 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI8/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI8/Pos/ctlOperOn for Close CMD BAY_89C_ISO COMMAND CLOSE / OPEN
49 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO8/EnaOpn/stVal SPI BAY_89C_ISO OPEN PERMITTED OR ENABLED
50 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO8/EnaCls/stVal SPI BAY_89C_ISO CLOSE PERMITTED OR ENABLED
51 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI9/Pos/stVal DPI BAY_89AE2/BE2_ISOLATOR POSITION USED FOR BUS EARTH SWITCH OF ISOLATOR, WHEN BUS EARTH SWITCH (89AE2/BE2) IS PROVIDED
52 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCSWI9/Pos/ctlOperOff for Open SS_BAY_BCU/LD0/SCSWI9/Pos/ctlOperOn for Close CMD BAY_89AE2/BE2_ISO COMMAND CLOSE / OPEN
53 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO9/EnaOpn/stVal SPI BAY_89AE2/BE2_ISO OPEN PERMITTED OR ENABLED
54 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SCILO9/EnaCls/stVal SPI BAY_89AE2/BE2_ISO CLOSE PERMITTED OR ENABLED
THE LOGICAL NODE INSTANCE NUMBER (SCSWIn/SCILOn) FOR BUS EARTH SWITCHES MAY BE ASSIGNED AS PER AVAILABILITY
55 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
56 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/LPHD1/PhyHealth/stVal SPI BCU UNHEALTHY Y
57 220kV STNMD1Q01BNMBCU SS_BAY_BCU/SES_1/SESRSYN2/Rel/stVal SPI CONDITIONS OK FOR SYNCHRONIZATION
58 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI SPRING DISCHARGED Y FOR SPRING MECHANISM CBs ANNUNCIATION FOR CIRCUIT BREAKER
59 220kV STNMD1Q01BNMBCU SPI AC MOTOR SUPPLY FAIL Y
60 220kV STNMD1Q01BNMBCU SPI SF6 GAS LOW Y
61 220kV STNMD1Q01BNMBCU SPI OPERATION LOCKED OUT Y
62 220kV STNMD1Q01BNMBCU SPI CB READY FOR AUTORECLOSURE Y
63 220kV STNMD1Q01BNMBCU SPI DC SUPPLY FAIL Y
64 220kV STNMD1Q01BNMBCU SPI TRIP RELAY 86 A FAULTY (SUPERVISION) Y Addition
65 220kV STNMD1Q01BNMBCU SPI TRIP RELAY 86 B FAULTY (SUPERVISION) Y Addition
66 220kV STNMD1Q01BNMBCU SPI TC-1 FAULTY R-PH Y Addition
67 220kV STNMD1Q01BNMBCU SPI TC-1 FAULTY Y-PH Y Addition
68 220kV STNMD1Q01BNMBCU SPI TC-1 FAULTY B-PH Y Addition
69 220kV STNMD1Q01BNMBCU SPI TC-2 FAULTY R-PH Y Addition
70 220kV STNMD1Q01BNMBCU SPI TC-2 FAULTY Y-PH Y Addition
71 220kV STNMD1Q01BNMBCU SPI TC-2 FAULTY B-PH Y Addition
72 220kV STNMD1Q01BNMBCU SPI DT RECEIVE CH-1 Y Available in REC670 (Sig. 5) Agreed
73 220kV STNMD1Q01BNMBCU SPI DT RECEIVE CH-2 Y Available in REC670 (Sig. 6) Agreed
74 220kV STNMD1Q01BNMBCU SPI CB MANUAL TRIP CMD Y Addition
75 220kV STNMD1Q01BNMBCU SPI CB MANUAL CLOSE CMD Y Addition
76 220kV STNMD1Q01BNMBCU SPI START A/R Y Addition
77 220kV STNMD1Q01BNMBCU SPI BLOCK A/R Y Addition
78 220kV STNMD1Q01BNMBCU SPI PREPARE 3PH TRIP Y Addition, Available in REC670 (Sig. 11) Agreed
79 220kV STNMD1Q01BNMBCU SPI BUSBAR PROTN OPTD Y Addition
80 220kV STNMD1Q01BNMBCU SPI S.A. COUNTER R-PH Y Addition As per CRP scheme will be configured in BCU/Protection relay
81 220kV STNMD1Q01BNMBCU SPI S.A. COUNTER Y-PH Y Addition As per CRP scheme will be configured in BCU/Protection relay
82 220kV STNMD1Q01BNMBCU SPI S.A. COUNTER B-PH Y Addition As per CRP scheme will be configured in BCU/Protection relay
83 220kV STNMD1Q01BNMBCU SPI INCOMER DC-1 FAIL Y Addition
84 220kV STNMD1Q01BNMBCU SPI INCOMER DC-2 FAIL Y Addition
85 220kV STNMD1Q01BNMBCU SPI POLE DISCREPANCY RELAY OPTD Y
86 220kV STNMD1Q01BNMBCU SPI COMPRESSOR SUPPLY FAIL Y FOR HYDRAULLIC MECHANISM CBs
87 220kV STNMD1Q01BNMBCU SPI AIR PRESSURE LOW Y
88 220kV STNMD1Q01BNMBCU SPI COMPRESSOR RUN TIME SUPERVISION Y
89 220kV STNMD1Q01BNMBCU SPI CB R-PH RECLOSE ALARM Y Addition
90 220kV STNMD1Q01BNMBCU SPI CB Y-PH RECLOSE ALARM Y CSD Related Eventsf (if Applicable) Addition
91 220kV STNMD1Q01BNMBCU SPI CB B-PH RECLOSE ALARM Y Addition
92 220kV STNMD1Q01BNMBCU SPI CSD OPERATION LIMIT ALARM WHEN OPENING Y Addition
93 220kV STNMD1Q01BNMBCU SPI CSD OPERATION LIMIT ALARM WHEN CLOSING Y Addition
94 220kV STNMD1Q01BNMBCU SPI CSD GROUP ALARM Y Addition
95 220kV STNMD1Q01BNMBCU SPI CSD RESERVED Y Addition
96 220kV STNMD1Q01BNMBCU SPI CSD SYNCHROTEQ IN LOCAL MODE Y Addition
97 220kV STNMD1Q01BNMBCU SPI CSD CB INTERFACE ALARM Y Addition
98 220kV STNMD1Q01BNMBCU SPI CSD SENSOR ALARM Y Addition
99 220kV STNMD1Q01BNMBCU SPI CSD IN Y Addition
100 220kV STNMD1Q01BNMBCU SPI CSD BYPASS Y
101 220kV STNMD1Q01BNMBCU SPI CSD FAIL Y
102 220kV STNMD1Q01BNMBCU SPI ICT/REACTOR-n R PH OUT OF SERVICE Single phase ICT/Reactor OUT of service & Spare reactor out of service information Addition
103 220kV STNMD1Q01BNMBCU SPI ICT/REACTOR-n Y PH OUT OF SERVICE Addition
104 220kV STNMD1Q01BNMBCU SPI ICT/REACTOR-n B PH OUT OF SERVICE Y Addition
105 220kV STNMD1Q01BNMBCU SPI ICT/Reactor- SPARE PH IN SERVICE IN ICT/Reactor-n Y Addition
106 220kV STNMD1Q01BNMBCU SPI BUS-1 VT RESET VT SELECTION FOR TRANSFORMER & REACTOR
107 220kV STNMD1Q01BNMBCU SPI BUS-2 VT RESET
108 220kV STNMD1Q01BNMBCU SPI LINE VT RESET
109 220kV STNMD1Q01BNMBCU SPI BUS-1 VT SELECTED
110 220kV STNMD1Q01BNMBCU SPI BUS-2 VT SELECTED
111 220kV STNMD1Q01BNMBCU SPI LINE VTSELECTED
112 220kV STNMD1Q01BNMBCU SPI GAS COMPARTMENT n Alarm Stage n Y Stage 1 to n as per scheme ANNUNCIATION FOR GIS BAYS
113 220kV STNMD1Q01BNMBCU SPI LCC PANEL AC SUPPLY FAIL Y
114 220kV STNMD1Q01BNMBCU SPI LCC PANEL DC SUPPLY FAIL Y
115 220kV STNMD1Q01BNMBCU SPI SELECTOR SWITCH POSITION LOCAL/REMOTE Y
116 220kV STNMD1Q01BNMBCU SPI BUS VT MCB TRIP Y FOR BCUs HAVING BUS VT INPUT
117 220kV STNMD1Q01BNMBCU SPI Bay IN NORMAL Applicable for Double Main Transfer Busbar system Addition
118 220kV STNMD1Q01BNMBCU SPI Bay IN TRANSFER Addition
119 220kV STNMD1Q01BNMBCU SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme Addition
120 220kV STNMD1Q01BNMBCU SPI RELAY IN TEST MODE Y Addition
121 220kV STNMD1Q01BNMBCU SPI SETTINGS CHANGED Y Addition
122 220kV STNMD1Q01BNMBCU SPI DR MEMMORY 80% FULL Y Addition
123 220kV STNMD1Q01BNMBCU SS_BAY_BCU/MON/CMMXU1/A/phsA/cVal/mag AI CURRENT L1 Addition
124 220kV STNMD1Q01BNMBCU SS_BAY_BCU/MON/CMMXU1/A/phsB/cVal/mag AI CURRENT L2 Addition
125 220kV STNMD1Q01BNMBCU SS_BAY_BCU/MON/CMMXU1/A/phsC/cVal/mag AI CURRENT L3 Addition
126 220kV STNMD1Q01BNMBCU SS_BAY_BCU/MON/VMMXU1/PPV/phsAB/cVal/mag AI VOLTAGE U12 Addition
127 220kV STNMD1Q01BNMBCU SS_BAY_BCU/MON/VMMXU1/PPV/phsBC/cVal/mag AI VOLTAGE U23 Addition
128 220kV STNMD1Q01BNMBCU SS_BAY_BCU/MON/VMMXU1/PPV/phsCA/cVal/mag AI VOLTAGE U31 Addition
129 220kV STNMD1Q01BNMBCU SS_BAY_BCU/MON/CVMMXN1/Watt/mag AI ACTIVE POWER (P) Addition
130 220kV STNMD1Q01BNMBCU SS_BAY_BCU/MON/CVMMXN1/VolAmpr/mag AI REACTIVE POWER (Q) Available in REC670 (Sig. 95) Agreed
131 220kV STNMD1Q01BNMBCU SS_BAY_BCU/MON/CVMMXN1/PwrFact/mag AI POWER FACTOR (PF) Available in REC670 (Sig. 95) Agreed
132 220kV STNMD1Q01BNMBCU SS_BAY_BCU/MON/CVMMXN1/PwrFact/mag AI FREQUENCY (HZ) Available in REC670 (Sig. 95) Agreed
133 220kV STNMD1Q01BNMBCU SS_BAY_BCUMON/L4UFCNTn/CntVal/actVal AI S.A. COUNTER R-PH Addition
134 220kV STNMD1Q01BNMBCU AI S.A. COUNTER Y-PH Addition
135 220kV STNMD1Q01BNMBCU AI S.A. COUNTER B-PH Addition
136 220kV STNMD1Q01BNMBCU SS_BAY_BCU/MON/MVGAPC/AnIn_n/mag AI TAP POSITION R PH Addition
137 220kV STNMD1Q01BNMBCU AI TAP POSITION Y PH Addition
138 220kV STNMD1Q01BNMBCU AI TAP POSITION B PH Addition
139 220kV STNMD1Q01BNMBCU AI WTI HV R PH Addition
140 220kV STNMD1Q01BNMBCU AI WTI IV R PH Addition
141 220kV STNMD1Q01BNMBCU AI WTI LV R PH Addition
142 220kV STNMD1Q01BNMBCU AI OTI R PH Addition
143 220kV STNMD1Q01BNMBCU AI WTI HV Y PH Addition
144 220kV STNMD1Q01BNMBCU AI WTI IV Y PH Addition
145 220kV STNMD1Q01BNMBCU AI WTI LV Y PH Addition
146 220kV STNMD1Q01BNMBCU AI OTI Y PH Addition
147 220kV STNMD1Q01BNMBCU AI WTI HV B PH Addition
148 220kV STNMD1Q01BNMBCU AI WTI IV B PH Addition
149 220kV STNMD1Q01BNMBCU AI WTI LV B PH Addition
150 220kV STNMD1Q01BNMBCU AI OTI B PH Addition
151 220kV STNMD1Q01BNMBCU SS_BAY_BCUMON/L4UFCNTn/CntVal/actVal AI BREAKER R-PHASE OPERATION COUNTER Addition
152 220kV STNMD1Q01BNMBCU AI BREAKER Y-PHASE OPERATION COUNTER Addition
153 220kV STNMD1Q01BNMBCU AI BREAKER B-PHASE OPERATION COUNTER Addition
154 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI RPH MOG LOW OIL LEVEL ALARM Y FOR 3Phase TRANSFORMER, INPUTS CAN BE DISTRIBUTED TO ANY IED. BUTSIGNAL SHOULD BE AS PER TRANSFORMER AVIALABLE SIGNAL Addition
155 220kV STNMD1Q01BNMBCU SPI YPH MOG LOW OIL LEVEL ALARM Y Addition
156 220kV STNMD1Q01BNMBCU SPI BPH MOG LOW OIL LEVEL ALARM Y Addition
157 220kV STNMD1Q01BNMBCU SPI SP-PH MOG LOW OIL LEVEL ALARM Y Addition
158 220kV STNMD1Q01BNMBCU SPI RPH MOG HIGH OIL LEVEL ALARM Y Addition
159 220kV STNMD1Q01BNMBCU SPI YPH MOG HIGH OIL LEVEL ALARM Y Addition
160 220kV STNMD1Q01BNMBCU SPI BPH MOG HIGH OIL LEVEL ALARM Y Addition
161 220kV STNMD1Q01BNMBCU SPI SP-PH MOG HIGH OIL LEVEL ALARM Y Addition
162 220kV STNMD1Q01BNMBCU SPI R-PH OIL FLOW SENSITIVE VALVE ALARM Y Addition
163 220kV STNMD1Q01BNMBCU SPI Y-PH OIL FLOW SENSITIVE VALVE ALARM Y Addition
164 220kV STNMD1Q01BNMBCU SPI B-PH OIL FLOW SENSITIVE VALVE ALARM Y Addition
165 220kV STNMD1Q01BNMBCU SPI SP-PH OIL FLOW SENSITIVE VALVE ALARM Y Addition
166 220kV STNMD1Q01BNMBCU SPI RPH PUMP FAIL - BANK A Y Addition
167 220kV STNMD1Q01BNMBCU SPI RPH PUMP FAIL - BANK B Y Addition
168 220kV STNMD1Q01BNMBCU SPI RPH PUMP FAIL - BANK C Y Addition
169 220kV STNMD1Q01BNMBCU SPI RPH PUMP FAIL - BANK D Y Addition
170 220kV STNMD1Q01BNMBCU SPI YPH PUMP FAIL - BANK A Y Addition
171 220kV STNMD1Q01BNMBCU SPI YPH PUMP FAIL - BANK B Y Addition
172 220kV STNMD1Q01BNMBCU SPI YPH PUMP FAIL - BANK C Y Addition
173 220kV STNMD1Q01BNMBCU SPI YPH PUMP FAIL - BANK D Y Addition
174 220kV STNMD1Q01BNMBCU SPI BPH PUMP FAIL - BANK A Y Addition
175 220kV STNMD1Q01BNMBCU SPI BPH PUMP FAIL - BANK B Y Addition
176 220kV STNMD1Q01BNMBCU SPI BPH PUMP FAIL - BANK C Y Addition
177 220kV STNMD1Q01BNMBCU SPI BPH PUMP FAIL - BANK D Y Addition
178 220kV STNMD1Q01BNMBCU SPI SPH PUMP FAIL - BANK A Y Addition
179 220kV STNMD1Q01BNMBCU SPI SPH PUMP FAIL - BANK B Y Addition
180 220kV STNMD1Q01BNMBCU SPI SPH PUMP FAIL - BANK C Y Addition
181 220kV STNMD1Q01BNMBCU SPI SPH PUMP FAIL - BANK D Y Addition
182 220kV STNMD1Q01BNMBCU SPI RPH THERMAL OVERLOAD TRIP - BANK A Y Addition
183 220kV STNMD1Q01BNMBCU SPI RPH THERMAL OVERLOAD TRIP - BANK B Y Addition
184 220kV STNMD1Q01BNMBCU SPI RPH THERMAL OVERLOAD TRIP - BANK C Y Addition
185 220kV STNMD1Q01BNMBCU SPI RPH THERMAL OVERLOAD TRIP - BANK D Y Addition
186 220kV STNMD1Q01BNMBCU SPI YPH THERMAL OVERLOAD TRIP - BANK A Y Addition
187 220kV STNMD1Q01BNMBCU SPI YPH THERMAL OVERLOAD TRIP - BANK B Y Addition
188 220kV STNMD1Q01BNMBCU SPI YPH THERMAL OVERLOAD TRIP - BANK C Y Addition
189 220kV STNMD1Q01BNMBCU SPI YPH THERMAL OVERLOAD TRIP - BANK D Y Addition
190 220kV STNMD1Q01BNMBCU SPI BPH THERMAL OVERLOAD TRIP - BANK A Y Addition
191 220kV STNMD1Q01BNMBCU SPI BPH THERMAL OVERLOAD TRIP - BANK B Y Addition
192 220kV STNMD1Q01BNMBCU SPI BPH THERMAL OVERLOAD TRIP - BANK C Y Addition
193 220kV STNMD1Q01BNMBCU SPI BPH THERMAL OVERLOAD TRIP - BANK D Y Addition
194 220kV STNMD1Q01BNMBCU SPI SPH THERMAL OVERLOAD TRIP - BANK A Y Addition
195 220kV STNMD1Q01BNMBCU SPI SPH THERMAL OVERLOAD TRIP - BANK B Y Addition
196 220kV STNMD1Q01BNMBCU SPI SPH THERMAL OVERLOAD TRIP - BANK C Y Addition
197 220kV STNMD1Q01BNMBCU SPI SPH THERMAL OVERLOAD TRIP - BANK D Y Addition
198 220kV STNMD1Q01BNMBCU SPI RPH LOW OIL FLOW/REVERSE FLOW - BANK A Y Addition
199 220kV STNMD1Q01BNMBCU SPI RPH LOW OIL FLOW/REVERSE FLOW - BANK B Y Addition
200 220kV STNMD1Q01BNMBCU SPI RPH LOW OIL FLOW/REVERSE FLOW - BANK C Y Addition
201 220kV STNMD1Q01BNMBCU SPI RPH LOW OIL FLOW/REVERSE FLOW - BANK D Y Addition
202 220kV STNMD1Q01BNMBCU SPI YPH LOW OIL FLOW/REVERSE FLOW - BANK A Y Addition
203 220kV STNMD1Q01BNMBCU SPI YPH LOW OIL FLOW/REVERSE FLOW - BANK B Y Addition
204 220kV STNMD1Q01BNMBCU SPI YPH LOW OIL FLOW/REVERSE FLOW - BANK C Y Addition
205 220kV STNMD1Q01BNMBCU SPI YPH LOW OIL FLOW/REVERSE FLOW - BANK D Y Addition
206 220kV STNMD1Q01BNMBCU SPI BPH LOW OIL FLOW/REVERSE FLOW - BANK A Y Addition
207 220kV STNMD1Q01BNMBCU SPI BPH LOW OIL FLOW/REVERSE FLOW - BANK B Y Addition
208 220kV STNMD1Q01BNMBCU SPI BPH LOW OIL FLOW/REVERSE FLOW - BANK C Y Addition
209 220kV STNMD1Q01BNMBCU SPI BPH LOW OIL FLOW/REVERSE FLOW - BANK D Y Addition
210 220kV STNMD1Q01BNMBCU SPI SPH LOW OIL FLOW/REVERSE FLOW - BANK A Y Addition
211 220kV STNMD1Q01BNMBCU SPI SPH LOW OIL FLOW/REVERSE FLOW - BANK B Y Addition
212 220kV STNMD1Q01BNMBCU SPI SPH LOW OIL FLOW/REVERSE FLOW - BANK C Y Addition
213 220kV STNMD1Q01BNMBCU SPI SPH LOW OIL FLOW/REVERSE FLOW - BANK D Y Addition
214 220kV STNMD1Q01BNMBCU SPI RPH COOLER CONTROL SUPPLY FAIL Y Addition
215 220kV STNMD1Q01BNMBCU SPI YPH COOLER CONTROL SUPPLY FAIL Y Addition
216 220kV STNMD1Q01BNMBCU SPI BPH COOLER CONTROL SUPPLY FAIL Y Addition
217 220kV STNMD1Q01BNMBCU SPI SPH COOLER CONTROL SUPPLY FAIL Y Addition
218 220kV STNMD1Q01BNMBCU SPI RPH SUPPLY CHANGE OVER FAIL Y Addition
219 220kV STNMD1Q01BNMBCU SPI YPH SUPPLY CHANGE OVER FAIL Y Addition
220 220kV STNMD1Q01BNMBCU SPI BPH SUPPLY CHANGE OVER FAIL Y Addition
221 220kV STNMD1Q01BNMBCU SPI SPH SUPPLY CHANGE OVER FAIL Y Addition
222 220kV STNMD1Q01BNMBCU SPI RPH SUPPLY - A FAIL Y Addition
223 220kV STNMD1Q01BNMBCU SPI YPH SUPPLY - A FAIL Y Addition
224 220kV STNMD1Q01BNMBCU SPI BPH SUPPLY - A FAIL Y Addition
225 220kV STNMD1Q01BNMBCU SPI SPH SUPPLY - A FAIL Y Addition
226 220kV STNMD1Q01BNMBCU SPI RPH SUPPLY - B FAIL Y Addition
227 220kV STNMD1Q01BNMBCU SPI YPH SUPPLY - B FAIL Y Addition
228 220kV STNMD1Q01BNMBCU SPI BPH SUPPLY - B FAIL Y Addition
229 220kV STNMD1Q01BNMBCU SPI SPH SUPPLY - B FAIL Y Addition
230 220kV STNMD1Q01BNMBCU SPI RPH OLTC MOTOR OVERLOAD Y Addition
231 220kV STNMD1Q01BNMBCU SPI RPH TAP CHANGE IN PROGRESS Y Addition
232 220kV STNMD1Q01BNMBCU SPI RPH TAP CHANGE IN COMPLETE Y Addition
233 220kV STNMD1Q01BNMBCU SPI RPH OLTC IN LOCAL Y Addition
234 220kV STNMD1Q01BNMBCU SPI RPH OLTC IN REMOTE Y Addition
235 220kV STNMD1Q01BNMBCU SPI RPH TAP CHANGE CONTROL SUPPLY FAIL Y Addition
236 220kV STNMD1Q01BNMBCU SPI RPH LOWEST POSITION REACHDED Y Addition
237 220kV STNMD1Q01BNMBCU SPI RPH HIGHESHT POSITION REACHDED Y Addition
238 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SPC1CGGIO n/ctlOpen CMD RPH OLTC RAISE COMMAND Y Addition
239 220kV STNMD1Q01BNMBCU CMD RPH OLTC LOWER COMMAND Y Addition
240 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI YPH OLTC MOTOR OVERLOAD Y Addition
241 220kV STNMD1Q01BNMBCU SPI YPH TAP CHANGE IN PROGRESS Y Addition
242 220kV STNMD1Q01BNMBCU SPI YPH TAP CHANGE IN COMPLETE Y Addition
243 220kV STNMD1Q01BNMBCU SPI YPH OLTC IN LOCAL Y Addition
244 220kV STNMD1Q01BNMBCU SPI YPH OLTC IN REMOTE Y Addition
245 220kV STNMD1Q01BNMBCU SPI YPH TAP CHANGE CONTROL SUPPLY FAIL Y Addition
246 220kV STNMD1Q01BNMBCU SPI YPH LOWEST POSITION REACHDED Y Addition
247 220kV STNMD1Q01BNMBCU SPI YPH HIGHESHT POSITION REACHDED Y Addition
248 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SPC1CGGIO n/ctlOpen CMD YPH OLTC RAISE COMMAND Y Addition
249 220kV STNMD1Q01BNMBCU CMD YPH OLTC LOWER COMMAND Y Addition
250 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI BPH OLTC MOTOR OVERLOAD Y Addition
251 220kV STNMD1Q01BNMBCU SPI BPH TAP CHANGE IN PROGRESS Y Addition
252 220kV STNMD1Q01BNMBCU SPI BPH TAP CHANGE IN COMPLETE Y Addition
253 220kV STNMD1Q01BNMBCU SPI BPH OLTC IN LOCAL Y Addition
254 220kV STNMD1Q01BNMBCU SPI BPH OLTC IN REMOTE Y Addition
255 220kV STNMD1Q01BNMBCU SPI BPH TAP CHANGE CONTROL SUPPLY FAIL Y Addition
256 220kV STNMD1Q01BNMBCU SPI BPH LOWEST POSITION REACHDED Y Addition
257 220kV STNMD1Q01BNMBCU SPI BPH HIGHESHT POSITION REACHDED Y Addition
258 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SPC1CGGIO n/ctlOpen CMD BPH OLTC RAISE COMMAND Y Addition
259 220kV STNMD1Q01BNMBCU CMD BPH OLTC LOWER COMMAND Y Addition
260 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI SPH OLTC MOTOR OVERLOAD Y Addition
261 220kV STNMD1Q01BNMBCU SPI SPH TAP CHANGE IN PROGRESS Y Addition
262 220kV STNMD1Q01BNMBCU SPI SPH TAP CHANGE IN COMPLETE Y Addition
263 220kV STNMD1Q01BNMBCU SPI SPH OLTC IN LOCAL Y Addition
264 220kV STNMD1Q01BNMBCU SPI SPH OLTC IN REMOTE Y Addition
265 220kV STNMD1Q01BNMBCU SPI SPH TAP CHANGE CONTROL SUPPLY FAIL Y Addition
266 220kV STNMD1Q01BNMBCU SPI SPH LOWEST POSITION REACHDED Y Addition
267 220kV STNMD1Q01BNMBCU SPI SPH HIGHESHT POSITION REACHDED Y Addition
268 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SPC1CGGIO n/ctlOpen CMD SPH OLTC RAISE COMMAND Y Addition
269 220kV STNMD1Q01BNMBCU CMD SPH OLTC LOWER COMMAND Y Addition
270 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
271 220kV STNMD1Q01BNMBCU SPI SPARE ALARM-2 Y Addition
272 220kV STNMD1Q01BNMBCU SPI SPARE ALARM-3 Y Addition
273 220kV STNMD1Q01BNMBCU SPI SPARE ALARM-4 Y Addition
274 220kV STNMD1Q01BNMBCU SPI SPARE ALARM-5 Y Addition
275 220kV STNMD1Q01BNMBCU SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-6 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
276 220kV STNMD1Q01BNMBCU SPI SPARE ALARM-7 Y Addition
277 220kV STNMD1Q01BNMBCU SPI SPARE ALARM-8 Y Addition
278 220kV STNMD1Q01BNMBCU SPI SPARE ALARM-9 Y Addition
279 220kV STNMD1Q01BNMBCU SPI SPARE ALARM-10 Y Addition
ADDITIONAL SIGNAL FOR CB TROUBLE ETC AS PER SCHEME
** 10 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
NOTE 1: The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified.
NOTE 2: If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
NOTE 3: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 4: The characters "Q01" stand for Bay Number, this will be vary based on Bay number eg. Q01 for BAY01, Q02 for BAY02 etc…
NOTE 5: The characters "BNM" stand for Bay Name, this will be vary based on Bay name eg. L for LINE, BR for BUSREACTOR, LR for LINEREACTOR, TIE for TIE & ICT fo ICT bay.
REQUIRED SIGNALS FOR LINE DIFFERENTAIL cum DISTANCE RELAYS
IED name: R_REL670_21M1
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS HE Comments POWERGRID Reply (Meeting on 07/12/2023)
1 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV1/Str/general SPI OVERVOLATGE STAGE 1 START
2 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV1/Op/general SPI OVERVOLATGE STAGE 1 TRIP Y
3 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/OV2PTOV2/Str/general SPI OVER VOLTAGE STAGE-2 START Y Addition
4 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV2/Op/general SPI OVERVOLATGE STAGE 2 TRIP Y
5 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/EF4_1/EF4PTOC1/Str/general SPI DEF START
6 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/EF4_1/EF4PTOC1/Op/general SPI DEF TRIP Y
7 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/STBPTOC1/Op/general SPI STUB PROTECTION OPERATED Y Applicable for One and Half CB Busbar system
8 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCVPSOF1/Op/general SPI SOTF OPERATED Y
9 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Str/general SPI START, Z1
10 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/general SPI START, Z2
11 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsA SPI START, Z2 R PH
12 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsB SPI START, Z2 Y PH
13 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsC SPI START, Z2 B PH
14 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS3/Str/general SPI START, Z3
15 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS4/Str/general SPI START, Z4(REVERSE) ** Whichever the zone choses as Reverse Text correction
16 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS5/Str/general SPI START, Z5
17 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/general SPI GENERAL TRIP, Z1 Y
18 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsA SPI TRIP, Z1 R PH Y
19 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsB SPI TRIP, Z1 Y PH Y
20 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsC SPI TRIP, Z1 B PH Y
21 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/general SPI GENERAL TRIP, Z2 Y
22 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsA SPI TRIP, Z2 R PH Y
23 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsB SPI TRIP, Z2 Y PH Y
24 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsC SPI TRIP, Z2 B PH Y
25 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS3/Op/general SPI GENERAL TRIP, Z3 Y
26 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS4/Op/general SPI GENERAL TRIP, Z4(REVERSE) Y ** Whichever the zone choses as Reverse Text correction
27 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS5/Op/general SPI GENERAL TRIP, Z5 Y
28 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/ProTx/stVal SPI CARRIER SEND Y
29 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/ProRx/stVal SPI CARRIER RECEIVE Y
30 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/Op/general SPI CARRIER AIDED SCHEME OPERATED Y
31 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMRPSB1/Str/general SPI POWER SWING DETECTED Y
32 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMRPSB1/BlkZn/stVal SPI POWER SWING BLOCKING Y
33 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SMPPTRC1/Op/general SPI DISTANCE RELAY GENERAL TRIP Y
34 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI R PHASE FAULT Y Addition
35 220kV STNMD1Q01LM1DIF SPI Y PHASE FAULT Y Addition
36 220kV STNMD1Q01LM1DIF SPI B PHASE FAULT Y Addition
37 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltDiskm/mag DINT FAULT LOCATOR DISTANCE
38 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltZ/cVal.mag DINT FAULT LOCATOR IMPEDANCE
39 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SDDRFUF1/Str/general SPI CVT FUSE FAIL Y
40 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/BRCPTOC1/Op/general SPI BROKEN CONDUCTOR ALARM Y
41 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI TIME SYNCHRONIZATION ERROR Y
42 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/LPHD1/PhyHealth/stVal SPI M1 IED UNHEALTHY Y
43 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI START AR TO BCU Text correction
44 220kV STNMD1Q01LM1DIF SPI BLOCK AR TO BCU Text correction
45 220kV STNMD1Q01LM1DIF SPI LINE ISOLATOR OPEN FOR STUB ACTIVATION Applicable for One and Half CB Busbar system
46 220kV STNMD1Q01LM1DIF SPI DT SEND CH 1 Y
47 220kV STNMD1Q01LM1DIF SPI DT SEND CH 2 Y
48 220kV STNMD1Q01LM1DIF SPI DT RECEIVE CH 1 Y Only for DR in RED670, for SCADA to be configured from BCU
49 220kV STNMD1Q01LM1DIF SPI DT RECEIVE CH 2 Y Only for DR in RED670, for SCADA to be configured from BCU
50 220kV STNMD1Q01LM1DIF SPI TRIP RELAY 86 A HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
51 220kV STNMD1Q01LM1DIF SPI TRIP RELAY 86 B HEALTHY (SUPERVISION) Y This signal can be moved to BCU, Need to discuss Agreed
52 220kV STNMD1Q01LM1DIF SPI GR A RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RED670, for SCADA to be configured from BCU
53 220kV STNMD1Q01LM1DIF SPI GR B RELAY OPERATED Y This signal can be moved to BCU, Need to discuss Only for DR in RED670, for SCADA to be configured from BCU
54 220kV STNMD1Q01LM1DIF SPI CARRIER RECEIVE CH-1 Y
55 220kV STNMD1Q01LM1DIF SPI CARRIER RECEIVE CH-2 Y
56 220kV STNMD1Q01LM1DIF SPI CARRIER CHANNEL 1 OUT OF SERVICE Y
57 220kV STNMD1Q01LM1DIF SPI CARRIER CHANNEL 2 OUT OF SERVICE Y
58 220kV STNMD1Q01LM1DIF SPI CARRIER CHANNEL 1 FAIL Y
59 220kV STNMD1Q01LM1DIF SPI CARRIER CHANNEL 2 FAIL Y
60 220kV STNMD1Q01LM1DIF SPI MAIN 2/1 RELAY FAIL Y
61 220kV STNMD1Q01LM1DIF SPI CB CLOSE COMMAND FOR SOTF INITIATION Text correction
62 220kV STNMD1Q01LM1DIF SPI BCU RELAY FAIL Y
63 220kV STNMD1Q01LM1DIF SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
64 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsA SPI START, Z1 R PH Addition
65 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsB SPI START, Z1 Y PH Addition
66 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS1/Str/phsC SPI START, Z1 B PH Addition
67 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP 3PH Y Addition
68 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP R PH Y Addition
69 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP Y PH Y Addition
70 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SMPPTRC/*** SPI GENERAL TRIP B PH Y Addition
71 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI PREPARE 3-PH TRIP FROM TIE BCU Y Addition, Available in BCU It is also required in RED670
72 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI PREPARE 3-PH TRIP FROM MAIN BCU Y Addition, Available in BCU It is also required in RED670
73 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI MAIN/ TIE CB AR OPTD Y Addition, Available in BCU Only for DR in RED670, for SCADA to be configured from BCU
74 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI MAIN/TIE LBB PROTECTION OPERATED Y Addition, Available in BBP Only for DR in RED670, for SCADA to be configured from LBB/BBP relay
75 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI BUSBAR M1/M2 OPTD Y Addition, Available in BBP Only for DR in RED670, for SCADA to be configured from BBP relay
76 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI GROUP RELAY 86A OPTD Y Available in REL670 (Sig. 52) Agreed
77 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/EchoWei/stVal SPI WEAK INFEED ECHO SEND Y Addition
78 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/EchoWeiOp/stVal SPI WEAK INFEED TRIP Y Addition
79 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/ZCRWPSCH/RvABlk/stVal SPI CURRENT REVERSAL DETECTED Y Addition
80 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI RELAY IN TEST MODE Y Addition
81 220kV STNMD1Q01LM1DIF SPI SETTINGS CHANGED Y Addition
82 220kV STNMD1Q01LM1DIF SPI DR MEMMORY 80% FULL Y Addition
83 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltDiskm/mag AI DISTANCE MEASUREMENT IN KM Y Available in REL670 (Sig. 37) Agreed
84 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltZ/cVal/mag AI DISTANCE MEASUREMENT IN IMPEDANCE Y Available in REL670 (Sig. 38) Agreed
85 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/MON/L4UFCNTn/CntVal/actVal AI CH-1 Code-1 Tx (MAIN-1 CARRIER RECEIVE CHANNEL-1) CH-1 Code-1 Tx (MAIN-1 CARRIER SEND CHANNEL-1)
86 220kV STNMD1Q01LM1DIF AI CH-1 Code-1 Rx (MAIN-1 CARRIER SEND CHANNEL-1) CH-1 Code-1 Rx (MAIN-1 CARRIER RECEIVE CHANNEL-1)
87 220kV STNMD1Q01LM1DIF AI CH-1 Code-2 Tx (MAIN-2 CARRIER RECEIVE CHANNEL-1) CH-1 Code-2 Tx (MAIN-2 CARRIER SEND CHANNEL-1)
88 220kV STNMD1Q01LM1DIF AI CH-1 Code-2 Rx (MAIN-2 CARRIER SEND CHANNEL-1) CH-1 Code-2 Rx (MAIN-2 CARRIER RECEIVE CHANNEL-1)
89 220kV STNMD1Q01LM1DIF AI CH-2 Code-2 Tx (MAIN-2 CARRIER RECEIVE CHANNEL-2) CH-2 Code-2 Tx (MAIN-2 CARRIER SEND CHANNEL-2)
90 220kV STNMD1Q01LM1DIF AI CH-2 Code-2 Rx (MAIN-2 CARRIER SEND CHANNEL-2) CH-2 Code-2 Rx (MAIN-2 CARRIER RECEIVECHANNEL-2)
91 220kV STNMD1Q01LM1DIF AI CH-2 Code-1 Tx (MAIN-1 CARRIER RECEIVE CHANNEL-2) CH-2 Code-1 Tx (MAIN-1 CARRIER SEND CHANNEL-2)
92 220kV STNMD1Q01LM1DIF AI CH-2 Code-1 Rx (MAIN-1 CARRIER SEND CHANNEL-2) CH-2 Code-1 Rx (MAIN-1 CARRIER RECEIVE CHANNEL-2)
93 220kV STNMD1Q01LM1DIF AI CH-1 Code-3 Tx (DT RECEIVE CHANNEL-1) CH-1 Code-3 Tx (DT SEND CHANNEL-1)
94 220kV STNMD1Q01LM1DIF AI CH-1 Code-3 Rx (DT SEND CHANNEL-1) CH-1 Code-3 Rx (DT RECEIVE CHANNEL-1)
95 220kV STNMD1Q01LM1DIF AI CH-2 Code-3 Tx (DT RECEIVE CHANNEL-2) CH-2 Code-3 Tx (DT SEND CHANNEL-2)
96 220kV STNMD1Q01LM1DIF AI CH-2 Code-3 Rx (DT SEND CHANNEL-2) CH-2 Code-3 Rx (DT RECEIVE CHANNEL-2)
97 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-1 Y ** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database Addition
98 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-2 Y Addition
99 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-3 Y Addition
100 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-4 Y Addition
101 220kV STNMD1Q01LM1DIF SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SPI SPARE ALARM-5 Y Addition
102 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Op/general SPI DIFFERENTIAL PROTECTION TRIP Y Line Differential protection, 3 CT sets, 2-3 line ends Variant
103 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Op/general SPI Y Line Differential protection, 6 CT sets, 3-5 line ends Variant
104 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Op/phsA SPI DIFFERENTIAL PROTECTION RPH TRIP Y Line Differential protection, 3 CT sets, 2-3 line ends Variant
105 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Op/phsA SPI Y Line Differential protection, 6 CT sets, 3-5 line ends Variant
106 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Op/phsB SPI DIFFERENTIAL PROTECTION YPH TRIP Y Line Differential protection, 3 CT sets, 2-3 line ends Variant
107 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Op/phsB SPI Y Line Differential protection, 6 CT sets, 3-5 line ends Variant
108 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Op/phsC SPI DIFFERENTIAL PROTECTION BPH TRIP Y Line Differential protection, 3 CT sets, 2-3 line ends Variant
109 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Op/phsC SPI Y Line Differential protection, 6 CT sets, 3-5 line ends Variant
110 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Str/general SPI DIFFERENTIAL PROTECTION START Line Differential protection, 3 CT sets, 2-3 line ends Variant
111 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Str/general SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
112 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Str/phsA SPI DIFFERENTIAL PROTECTION RPH START Line Differential protection, 3 CT sets, 2-3 line ends Variant
113 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Str/phsA SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
114 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Str/phsB SPI DIFFERENTIAL PROTECTION YPH START Line Differential protection, 3 CT sets, 2-3 line ends Variant
115 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Str/phsB SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
116 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Str/phsC SPI DIFFERENTIAL PROTECTION BPH START Line Differential protection, 3 CT sets, 2-3 line ends Variant
117 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Str/phsC SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
102 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/OpnCTAlm/stVal SPI DIFFERENTIAL PROTECTION OCT ALARM Line Differential protection, 3 CT sets, 2-3 line ends Variant
103 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/OpnCTAlm/stVal SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
104 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/StrRst/stVal SPI DIFFERENTIAL PROTECTION OPTD (RESTRAINED MODE) Line Differential protection, 3 CT sets, 2-3 line ends Variant
105 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/StrRst/stVal SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
106 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/StrUnRst/stVal SPI DIFFERENTIAL PROTECTION OPTD (UNRESTRAINED MODE) Line Differential protection, 3 CT sets, 2-3 line ends Variant
107 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/StrUnRst/stVal SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
108 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Blk2H/stVal SPI DIFFERENTIAL PROTECTION 2nd HARMONIC BLOCK Line Differential protection, 3 CT sets, 2-3 line ends Variant Applicable for Line cum Transformer bay
109 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Blk2H/stVal SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
110 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L3CPDIF4/Blk5H/stVal SPI DIFFERENTIAL PROTECTION 5th HARMONIC BLOCK Line Differential protection, 3 CT sets, 2-3 line ends Variant Applicable for Line cum Transformer bay
111 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/L6CPDIF2/Blk5H/stVal SPI Line Differential protection, 6 CT sets, 3-5 line ends Variant
112 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI DIFFERENTIAL PROTECTION COMMUNICATION FAIL
113 220kV STNMD1Q01LM1DIF SS_BAY_M1_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SPI REMOTE END INTERTRIP RECEIVE
** 5 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ANY ADDITIONAL SIGNAL AS PER SCHEME
ABB SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (AUX SYSTEM)
REQUIRED SIGNALS FOR AUX SYSTEM
IED name: R_REC670_BCU
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS
1 415V STNMN1AUXBCU SS_AUX_BCU/LD0/QCBAY1/LocSwPos/stVal INT BCU IN LOCAL/ REMOTE
2 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaOpn/stVal SPI DG_CB_OPEN PERMITTED OR ENABLED
3 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaCls/stVal SPI DG_CB_CLOSE PERMITTED OR ENABLED
4 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/stVal DPI DG_CB POSITION
5 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOff for Open SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOn for Close CMD DG_CB COMMAND CLOSE / OPEN
6 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaOpn/stVal SPI MSB_INCOMER_1_CB_OPEN PERMITTED OR ENABLED
7 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaCls/stVal SPI MSB_INCOMER_1_CB_CLOSE PERMITTED OR ENABLED
8 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/stVal DPI MSB_INCOMER_1_CB POSITION
9 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOff for Open SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOn for Close CMD MSB_INCOMER_1_CB COMMAND CLOSE / OPEN
10 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaOpn/stVal SPI MSB_INCOMER_2_CB_OPEN PERMITTED OR ENABLED
11 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaCls/stVal SPI MSB_INCOMER_2_CB_CLOSE PERMITTED OR ENABLED
12 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/stVal DPI MSB_INCOMER_2_CB POSITION
13 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOff for Open SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOn for Close CMD MSB_INCOMER_2_CB COMMAND CLOSE / OPEN
14 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaOpn/stVal SPI MSB_BUSCOUPLER_CB_OPEN PERMITTED OR ENABLED
15 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaCls/stVal SPI MSB_BUSCOUPLER_CB_CLOSE PERMITTED OR ENABLED
16 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/stVal DPI MSB_BUSCOUPLER_CB POSITION
17 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOff for Open SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOn for Close CMD MSB_BUSCOUPLER_CB COMMAND CLOSE / OPEN
18 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaOpn/stVal SPI ACDB_INCOMER_1_CB_OPEN PERMITTED OR ENABLED
19 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaCls/stVal SPI ACDB_INCOMER_1_CB_CLOSE PERMITTED OR ENABLED
20 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/stVal DPI ACDB_INCOMER_1_CB POSITION
21 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOff for Open SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOn for Close CMD ACDB_INCOMER_1_CB COMMAND CLOSE / OPEN
22 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaOpn/stVal SPI ACDB_INCOMER_2_CB_OPEN PERMITTED OR ENABLED
23 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaCls/stVal SPI ACDB_INCOMER_2_CB_CLOSE PERMITTED OR ENABLED
24 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/stVal DPI ACDB_INCOMER_2_CB POSITION
25 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOff for Open SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOn for Close CMD ACDB_INCOMER_2_CB COMMAND CLOSE / OPEN
26 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaOpn/stVal SPI ACDB_BUSCOPULER_CB_OPEN PERMITTED OR ENABLED
27 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaCls/stVal SPI ACDB_BUSCOPULER_CB_CLOSE PERMITTED OR ENABLED
28 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/stVal DPI ACDB_BUSCOPULER_CB POSITION
29 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOff for Open SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOn for Close CMD ACDB_BUSCOPULER_CB COMMAND CLOSE / OPEN
30 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaOpn/stVal SPI HVW_MOTOR_CB_OPEN PERMITTED OR ENABLED
31 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaCls/stVal SPI HVW_MOTOR_CB_CLOSE PERMITTED OR ENABLED
32 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/stVal DPI HVW_MOTOR_CB_ POSITION
33 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOff for Open SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOn for Close CMD HVW_MOTOR_CB_ COMMAND CLOSE / OPEN
34 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaOpn/stVal SPI SEB_33kV_CB_OPEN PERMITTED OR ENABLED
35 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaCls/stVal SPI SEB_33kV_CB_CLOSE PERMITTED OR ENABLED
36 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/stVal DPI SEB_33kV_CB_ POSITION
37 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOff for Open SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOn for Close CMD SEB_33kV_CB_ COMMAND CLOSE / OPEN
38 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaOpn/stVal SPI SEB_33kV_ISOLATOR_OPEN PERMITTED OR ENABLED
39 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaCls/stVal SPI SEB_33kV_ISOLATOR_CLOSE PERMITTED OR ENABLED
40 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/stVal DPI SEB_33kV_ISOLATOR_ POSITION
41 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOff for Open SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOn for Close CMD SEB_33kV_ISOLATOR_ COMMAND CLOSE / OPEN
42 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaOpn/stVal SPI TERTIARY TRAFO_33kV_CB_OPEN PERMITTED OR ENABLED If the inputs taken in Respecetive ICT Protection/BCU these signals may be omitted.
43 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaCls/stVal SPI TERTIARY TRAFO_33kV_CB_CLOSE PERMITTED OR ENABLED
44 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/stVal DPI TERTIARY TRAFO_33kV_CB_ POSITION
45 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOff for Open SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOn for Close CMD TERTIARY TRAFO_33kV_CB_ COMMAND
46 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaOpn/stVal SPI TERTIARY TRAFO_33kV_ISOLATOR_OPEN PERMITTED OR ENABLED
47 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCILOn/EnaCls/stVal SPI TERTIARY TRAFO_33kV_ISOLATOR_CLOSE PERMITTED OR ENABLED
48 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/stVal DPI TERTIARY TRAFO_33kV_ISOLATOR_ POSITION
49 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOff for Open SS_AUX_BCU/LD0/SCSWIn/Pos/ctlOperOn for Close CMD TERTIARY TRAFO_33kV_ISOLATOR_ COMMAND
THE LOGICAL NODE INSTANCE NUMBER (SCSWIn/SCILOn) FOR BBREAKERS MAY BE ASSIGNED AS PER AVAILABILITY
50 415V STNMN1AUXBCU SS_AUX_BCU/MON/CMMXUn/A/phsA/cVal/mag AI DG INCOMER CURRENT L1
51 415V STNMN1AUXBCU SS_AUX_BCU/MON/CMMXUn/A/phsB/cVal/mag AI DG INCOMER CURRENT L2
52 415V STNMN1AUXBCU SS_AUX_BCU/MON/CMMXUn/A/phsC/cVal/mag AI DG INCOMER CURRENT L3
53 415V STNMN1AUXBCU SS_AUX_BCU/MON/VMMXUn/PPV/phsAB/cVal/mag AI DG INCOMER VOLTAGE U12
54 415V STNMN1AUXBCU SS_AUX_BCU/MON/VMMXUn/PPV/phsBC/cVal/mag AI DG INCOMER VOLTAGE U23
55 415V STNMN1AUXBCU SS_AUX_BCU/MON/VMMXUn/PPV/phsCA/cVal/mag AI DG INCOMER VOLTAGE U31
56 415V STNMN1AUXBCU SS_AUX_BCU/MON/CVMMXNn/Watt/mag AI DG INCOMER ACTIVE POWER (P)
57 415V STNMN1AUXBCU SS_AUX_BCU/MON/CVMMXNn/VolAmpr/mag AI DG INCOMER REACTIVE POWER (Q)
58 415V STNMN1AUXBCU SS_AUX_BCU/MON/CVMMXNn/PwrFact/mag AI DG INCOMER POWER FACTOR (PF)
59 415V STNMN1AUXBCU SS_AUX_BCU/MON/CVMMXNn/PwrFact/mag AI DG INCOMER FREQUENCY (HZ)
60 415V STNMN1AUXBCU SS_AUX_BCU/MON/CMMXUn/A/phsA/cVal/mag AI MSB INCOMER-1 CURRENT L1
61 415V STNMN1AUXBCU SS_AUX_BCU/MON/CMMXUn/A/phsB/cVal/mag AI MSB INCOMER-1 CURRENT L2
62 415V STNMN1AUXBCU SS_AUX_BCU/MON/CMMXUn/A/phsC/cVal/mag AI MSB INCOMER-1 CURRENT L3
63 415V STNMN1AUXBCU SS_AUX_BCU/MON/VMMXUn/PPV/phsAB/cVal/mag AI MSB INCOMER-1 VOLTAGE U12
64 415V STNMN1AUXBCU SS_AUX_BCU/MON/VMMXUn/PPV/phsBC/cVal/mag AI MSB INCOMER-1 VOLTAGE U23
65 415V STNMN1AUXBCU SS_AUX_BCU/MON/VMMXUn/PPV/phsCA/cVal/mag AI MSB INCOMER-1 VOLTAGE U31
66 415V STNMN1AUXBCU SS_AUX_BCU/MON/CVMMXNn/Watt/mag AI MSB INCOMER-1 ACTIVE POWER (P)
67 415V STNMN1AUXBCU SS_AUX_BCU/MON/CVMMXNn/VolAmpr/mag AI MSB INCOMER-1 REACTIVE POWER (Q)
68 415V STNMN1AUXBCU SS_AUX_BCU/MON/CVMMXNn/PwrFact/mag AI MSB INCOMER-1 POWER FACTOR (PF)
69 415V STNMN1AUXBCU SS_AUX_BCU/MON/CVMMXNn/PwrFact/mag AI MSB INCOMER-1 FREQUENCY (HZ)
70 415V STNMN1AUXBCU SS_AUX_BCU/MON/CMMXUn/A/phsA/cVal/mag AI MSB INCOMER-2 CURRENT L1
71 415V STNMN1AUXBCU SS_AUX_BCU/MON/CMMXUn/A/phsB/cVal/mag AI MSB INCOMER-2 CURRENT L2
72 415V STNMN1AUXBCU SS_AUX_BCU/MON/CMMXUn/A/phsC/cVal/mag AI MSB INCOMER-2 CURRENT L3
73 415V STNMN1AUXBCU SS_AUX_BCU/MON/VMMXUn/PPV/phsAB/cVal/mag AI MSB INCOMER-2 VOLTAGE U12
74 415V STNMN1AUXBCU SS_AUX_BCU/MON/VMMXUn/PPV/phsBC/cVal/mag AI MSB INCOMER-2 VOLTAGE U23
75 415V STNMN1AUXBCU SS_AUX_BCU/MON/VMMXUn/PPV/phsCA/cVal/mag AI MSB INCOMER-2 VOLTAGE U31
76 415V STNMN1AUXBCU SS_AUX_BCU/MON/CVMMXNn/Watt/mag AI MSB INCOMER-2 ACTIVE POWER (P)
77 415V STNMN1AUXBCU SS_AUX_BCU/MON/CVMMXNn/VolAmpr/mag AI MSB INCOMER-2 REACTIVE POWER (Q)
78 415V STNMN1AUXBCU SS_AUX_BCU/MON/CVMMXNn/PwrFact/mag AI MSB INCOMER-2 POWER FACTOR (PF)
79 415V STNMN1AUXBCU SS_AUX_BCU/MON/CVMMXNn/PwrFact/mag AI MSB INCOMER-2 FREQUENCY (HZ)
80 415V STNMN1AUXBCU SS_AUX_BCU/MON/MVGAPC/AnIn_n/mag AI 220V CHARGER 1 CURRENT
81 415V STNMN1AUXBCU AI 220V CHARGER 2 CURRENT
82 415V STNMN1AUXBCU AI 48V CHARGER 1 CURRENT
83 415V STNMN1AUXBCU AI 48V CHARGER 2 CURRENT
84 415V STNMN1AUXBCU AI 220V DCDB 1 VOLTAGE
85 415V STNMN1AUXBCU AI 220V DCDB 1 CURRENT
86 415V STNMN1AUXBCU AI 220V DCDB 2 VOLTAGE
87 415V STNMN1AUXBCU AI 220V DCDB 2 CURRENT
88 415V STNMN1AUXBCU AI 48V DCDB 1 VOLTAGE
89 415V STNMN1AUXBCU AI 48V DCDB 1 CURRENT
90 415V STNMN1AUXBCU AI 48V DCDB 2 VOLTAGE
91 415V STNMN1AUXBCU AI 48V DCDB 2 CURRENT
92 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SP16GGIO n/Ind n/stVal SPI 220V CHARGER-1 ON FLOAT MODE
93 415V STNMN1AUXBCU SPI 220V CHARGER-1 ON BOAST MODE
94 415V STNMN1AUXBCU SPI 220V CHARGER 1 TROUBLE Y CLOSE / OPEN
95 415V STNMN1AUXBCU SPI 220V DCDB-1 EARTH FAULT OPTD Y
96 415V STNMN1AUXBCU SPI 220V CHARGER-2 ON FLOAT MODE
97 415V STNMN1AUXBCU SPI 220V CHARGER-2 ON BOAST MODE
98 415V STNMN1AUXBCU SPI 220V CHARGER 2 TROUBLE Y
99 415V STNMN1AUXBCU SPI 220V DCDB-2 EARTH FAULT OPTD Y
100 415V STNMN1AUXBCU SPI 48V CHARGER-1 ON FLOAT MODE CLOSE / OPEN
101 415V STNMN1AUXBCU SPI 48V CHARGER-1 ON BOAST MODE
102 415V STNMN1AUXBCU SPI 48V CHARGER 1 TROUBLE Y
103 415V STNMN1AUXBCU SPI 48V CHARGER-2 ON FLOAT MODE
104 415V STNMN1AUXBCU SPI 48V CHARGER-2 ON BOAST MODE CLOSE / OPEN
105 415V STNMN1AUXBCU SPI 48V CHARGER 2 TROUBLE Y
106 415V STNMN1AUXBCU SPI 415V INCOMER-1 UNDERVOLTAGE Y
107 415V STNMN1AUXBCU SPI 415V INCOMER-2 UNDERVOLTAGE Y CLOSE / OPEN
108 415V STNMN1AUXBCU SPI SEB TRAFO - BUCHHOLZ ALARM Y
109 415V STNMN1AUXBCU SPI SEB TRAFO - BUCHHOLZ TRIP Y
110 415V STNMN1AUXBCU SPI SEB TRAFO - WTI ALARM Y
111 415V STNMN1AUXBCU SPI SEB TRAFO - WTI TRIP Y
112 415V STNMN1AUXBCU SPI SEB TRAFO - OTI ALARM Y
113 415V STNMN1AUXBCU SPI SEB TRAFO - OTI TRIP Y
114 415V STNMN1AUXBCU SPI SEB TRAFO - PRD ALARM Y
115 415V STNMN1AUXBCU SPI SEB TRAFO - PRD TRIP Y
116 415V STNMN1AUXBCU SPI SEB 33KV_TC-1 FAULTY Y
117 415V STNMN1AUXBCU SPI SEB 33KV_TC-2 FAULTY Y
118 415V STNMN1AUXBCU SS_AUX_BCU/OC4_1/OC4PTOC1/Str/general SPI SEB 33kV PHASE OVERCURRENT START Y
119 415V STNMN1AUXBCU SS_AUX_BCU/OC4_1/OC4PTOC1/Op/general SPI SEB33kV PHASE OVERCURRENT TRIP Y
120 415V STNMN1AUXBCU SS_AUX_BCU/EF4_1/EF4PTOC1/Str/general SPI SEB 33kV PHASE EARTHFAULT START Y
121 415V STNMN1AUXBCU SS_AUX_BCU/EF4_1/EF4PTOC1/Op/general SPI SEB 33kV PHASE EARTHFAULT TRIP Y
122 415V STNMN1AUXBCU SS_AUX_BCU/ROV2_1/ROV2PTOV1/Str/general SPI SEB 33kV PHASE RESIDUAL OVERVOLTAGE START Y
123 415V STNMN1AUXBCU SS_AUX_BCU/ROV2_1/ROV2PTOV1/OP/general SPI SEB 33kV PHASE RESIDUAL OVERVOLTAGE TRIP Y
124 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SP16GGIO n/Ind n/stVal SPI SEB 33kV 86 OPTD Y
125 415V STNMN1AUXBCU SPI SEB 33kV CB ASSOCIATED ALARMS Y
126 415V STNMN1AUXBCU SPI TERTIARY TRAFO - BUCHHOLZ ALARM Y If the inputs taken in Respecetive ICT Protection/BCU these signals may be omitted.
127 415V STNMN1AUXBCU SPI TERTIARY TRAFO - BUCHHOLZ TRIP Y
128 415V STNMN1AUXBCU SPI TERTIARY TRAFO - WTI ALARM Y
129 415V STNMN1AUXBCU SPI TERTIARY TRAFO - WTI TRIP Y
130 415V STNMN1AUXBCU SPI TERTIARY TRAFO - OTI ALARM Y
131 415V STNMN1AUXBCU SPI TERTIARY TRAFO - OTI TRIP Y
132 415V STNMN1AUXBCU SPI TERTIARY TRAFO - PRD ALARM Y
133 415V STNMN1AUXBCU SPI TERTIARY TRAFO - PRD TRIP Y
134 415V STNMN1AUXBCU SPI TERTIARY 33KV_TC-1 FAULTY Y
135 415V STNMN1AUXBCU SPI TERTIARY 33KV_TC-2 FAULTY Y
136 415V STNMN1AUXBCU SS_AUX_BCU/OC4_1/OC4PTOC2/Str/general SPI TERTIARY 33kV PHASE OVERCURRENT START Y
137 415V STNMN1AUXBCU SS_AUX_BCU/OC4_1/OC4PTOC2/Op/general SPI TERTIARY33kV PHASE OVERCURRENT TRIP Y
138 415V STNMN1AUXBCU SS_AUX_BCU/EF4_1/EF4PTOC2/Str/general SPI TERTIARY 33kV PHASE EARTHFAULT START Y
139 415V STNMN1AUXBCU SS_AUX_BCU/EF4_1/EF4PTOC2/Op/general SPI TERTIARY 33kV PHASE EARTHFAULT TRIP Y
140 415V STNMN1AUXBCU SS_AUX_BCU/ROV2_1/ROV2PTOV2/Str/general SPI TERTIARY 33kV PHASE RESIDUAL OVERVOLTAGE START Y
141 415V STNMN1AUXBCU SS_AUX_BCU/ROV2_1/ROV2PTOV2/OP/general SPI TERTIARY 33kV PHASE RESIDUAL OVERVOLTAGE TRIP Y
142 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SP16GGIO n/Ind n/stVal SPI TERTIARY 33kV 86 OPTD Y
143 415V STNMN1AUXBCU SPI TERTIARY 33kV CB ASSOCIATED ALARMS Y
144 415V STNMN1AUXBCU SPI AUX INCOMER DC-1 FAULTY Y
145 415V STNMN1AUXBCU SPI AUX INCOMER DC-2 FAULTY Y
146 415V STNMN1AUXBCU SPI WATER STORAGE TANK-1 LEVEL LOW Y
147 415V STNMN1AUXBCU SPI WATER STORAGE TANK-2 LEVEL LOW Y
148 415V STNMN1AUXBCU SPI HVW MOTOR DRIVEN PUMP RUNNING
149 415V STNMN1AUXBCU SPI HVW MOTOR DRIVEN PUMP FAILS TO START Y
150 415V STNMN1AUXBCU SPI HVW MOTOR PUMP TRIP FEEDBACK Y
151 415V STNMN1AUXBCU SPI DIESEL ENGINE RUNNING
152 415V STNMN1AUXBCU SPI DIESEL ENGINE FAILS TO START Y
153 415V STNMN1AUXBCU SPI DIESEL ENGINE TANK LEVEL LOW Y
154 415V STNMN1AUXBCU SPI JOCKEY PUMP -1 RUNNING
155 415V STNMN1AUXBCU SPI JOCKEY PUMP -2 RUNNING
156 415V STNMN1AUXBCU SPI JOCKEY PUMP -1 FAILS TO START Y
157 415V STNMN1AUXBCU SPI JOCKEY PUMP -2 FAILS TO START Y
158 415V STNMN1AUXBCU SPI JOCKEY PUMP O/L TRIP Y
159 415V STNMN1AUXBCU SPI JOCKEY PUMP PANEL DC HEALTHY Y
160 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SPC8GAPCn/SPCSOn/ctlOper CMD HVW MOTORT START
161 415V STNMN1AUXBCU CMD HVW MOTORT STOP
162 415V STNMN1AUXBCU CMD DIESEL ENGINE START
163 415V STNMN1AUXBCU CMD DIESEL ENGINE STOP
164 415V STNMN1AUXBCU CMD JOCKEY PUMP-1 START
165 415V STNMN1AUXBCU CMD JOCKEY PUMP-1 STOP
166 415V STNMN1AUXBCU CMD JOCKEY PUMP-2 START
167 415V STNMN1AUXBCU CMD JOCKEY PUMP-2 STOP
168 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SP16GGIO n/Ind n/stVal SPI FIRE IN ZONE -1 Y
169 415V STNMN1AUXBCU SPI FIRE IN ZONE -2 Y
170 415V STNMN1AUXBCU SPI FIRE IN ZONE -3 Y
171 415V STNMN1AUXBCU SPI FIRE IN ZONE -4 Y
172 415V STNMN1AUXBCU SPI FIRE IN ZONE -5 Y
173 415V STNMN1AUXBCU SPI FIRE IN ZONE -N Y
174 415V STNMN1AUXBCU SPI FIRE IN TRANSFORMER-1 Y If the inputs taken in Respecetive ICT Protection/BCU these signals may be omitted.
175 415V STNMN1AUXBCU SPI FIRE IN TRANSFORMER-2 Y
176 415V STNMN1AUXBCU SPI FIRE IN TRANSFORMER-N Y
177 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SPC8GAPCn/SPCSOn/ctlOper CMD DELUGE COMMAND TO TRANSFORMER-1
178 415V STNMN1AUXBCU CMD DELUGE COMMAND TO TRANSFORMER-2
179 415V STNMN1AUXBCU CMD DELUGE COMMAND TO TRANSFORMER-N
180 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SP16GGIO n/Ind n/stVal SPI DG DIFFERENTIAL PROT TRIP Y
181 415V STNMN1AUXBCU SPI DG OC/EF PROT TRIP Y
182 415V STNMN1AUXBCU SPI DG FAIL TO START Y
183 415V STNMN1AUXBCU SPI ALTERNATOR ON
184 415V STNMN1AUXBCU SPI DG LUBE OIL LOW PRESSURE ALARM Y
185 415V STNMN1AUXBCU SPI HIGH WATER TEMP TRIP Y CLOSE / OPEN
186 415V STNMN1AUXBCU SPI ENGG. COM FAULT Y
187 415V STNMN1AUXBCU SPI LACK OF FUEL ALARM Y
188 415V STNMN1AUXBCU SPI DG CHARGER-1 ON
189 415V STNMN1AUXBCU SPI DG CHARGER-1 OFF Y CLOSE / OPEN
190 415V STNMN1AUXBCU SPI DG CHARGER-2 ON
191 415V STNMN1AUXBCU SPI DG CHARGER-2 OFF Y
192 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SPC8GAPCn/SPCSO1/ctlOper CMD DG START/STOP COMMAND CLOSE / OPEN
193 415V STNMN1AUXBCU SS_AUX_BCU/LD0/SP16GGIO n/Ind n/stVal SPI AUX INCOMER DC-1 FAULTY Y
194 415V STNMN1AUXBCU SPI AUX INCOMER DC-2 FAULTY Y
195 415V STNMN1AUXBCU SPI TIME SYNCHRONIZATION ERROR Y
196 415V STNMN1AUXBCU SPI BCU UNHEALTHY Y
197 415V STNMN1AUXBCU SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
198 415V STNMN1AUXBCU SPI RELAY IN TEST MODE Y
199 415V STNMN1AUXBCU SPI SETTINGS CHANGED Y
200 415V STNMN1AUXBCU SPI DR MEMMORY 80% FULL Y
201 415V STNMN1AUXBCU SPI SPARE ALARM-1 ** 20 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
202 415V STNMN1AUXBCU SPI SPARE ALARM-2
203 415V STNMN1AUXBCU SPI SPARE ALARM-3
204 415V STNMN1AUXBCU SPI SPARE ALARM-4
205 415V STNMN1AUXBCU SPI SPARE ALARM-5
206 415V STNMN1AUXBCU SPI SPARE ALARM-6
207 415V STNMN1AUXBCU SPI SPARE ALARM-7
208 415V STNMN1AUXBCU SPI SPARE ALARM-8
209 415V STNMN1AUXBCU SPI SPARE ALARM-9
210 415V STNMN1AUXBCU SPI SPARE ALARM-10
211 415V STNMN1AUXBCU SPI SPARE ALARM-11
212 415V STNMN1AUXBCU SPI SPARE ALARM-12
213 415V STNMN1AUXBCU SPI SPARE ALARM-13
214 415V STNMN1AUXBCU SPI SPARE ALARM-14
215 415V STNMN1AUXBCU SPI SPARE ALARM-15
216 415V STNMN1AUXBCU SPI SPARE ALARM-16
217 415V STNMN1AUXBCU SPI SPARE ALARM-17
218 415V STNMN1AUXBCU SPI SPARE ALARM-18
219 415V STNMN1AUXBCU SPI SPARE ALARM-19
220 415V STNMN1AUXBCU SPI SPARE ALARM-20
ADDITIONAL SIGNAL FOR CB TROUBLE ETC AS PER SCHEME
** 20 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
Sr. No. Voltage Level Feeder Name NAME ( BAY-213 BC )
SIGNAL DESCRIPTION Information type Telegram address Position EVENT ALARM
BINARY INPUT (Double Point)
1 200KV 200KV BC 89A POSITION DP B213_BCU89A$CSWI1$ST$Pos:2 stVal √
2 89AE1 POSITION DP B213_BCU89AE1$CSWI1$ST$Pos:2 stVal √
3 89AE2 POSITION DP B213_BCU89AE2$CSWI1$ST$Pos:2 stVal √
4 89B POSITION DP B213_BCU89B$CSWI1$ST$Pos:2 stVal √
5 89BE1 POSITION DP B213_BCU89BE1$CSWI1$ST$Pos:2 stVal √
6 89BE2 POSITION DP B213_BCU89BE2$CSWI1$ST$Pos:2 stVal √
7 CB B-PH POSITION DP B213_BCUCB_1P_POSITION$RSLEDGAPC1$ST$DPS2 stVal √
8 CB R-PH POSITION DP B213_BCUCB_1P_POSITION$RSLEDGAPC1$ST$DPS stVal √
9 CB Y-PH POSITION DP B213_BCUCB_1P_POSITION$RSLEDGAPC1$ST$DPS1 stVal √
10 CB POSITION DP B213_BCUCB$CSWI1$ST$Pos:2 stVal √
14 89A CONTROL DC B213_BCU89A$CSWI1$CO$Pos:8 Oper$ctlVal √
15 89AE1 CONTROL DC B213_BCU89AE1$CSWI1$CO$Pos:8 Oper$ctlVal √
16 89AE2 CONTROL DC B213_BCU89AE2$CSWI1$CO$Pos:8 Oper$ctlVal √
17 89B CONTROL DC B213_BCU89B$CSWI1$CO$Pos:8 Oper$ctlVal √
18 89BE1 CONTROL DC B213_BCU89BE1$CSWI1$CO$Pos:8 Oper$ctlVal √
19 89BE2 CONTROL DC B213_BCU89BE2$CSWI1$CO$Pos:8 Oper$ctlVal √
20 CB CONTROL DC B213_BCUCB$CSWI1$CO$Pos:8 Oper$ctlVal √
21 86A TRIP RELAY RESET SC B213_BCUUD1$RSLEDGAPC1$CO$SPC:8 Oper$ctlVal √
22 86B TRIP RELAY RESET SC
26 POWER FACTOR ME_FL B213_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotPF:1 mag$f
27 FREQUENCY ME_FL B213_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$Hz:1 mag$f
28 ACTIVE POWER ME_FL B213_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotW:1 mag$f
29 REACTIVE POWER ME_FL B213_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVAr:1 mag$f
30 APPARENT POWER ME_FL B213_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVA:1 mag$f
31 I-R -PH CURRENT ME_FL B213_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsA$cVal$mag$f
32 I-Y -PH CURRENT ME_FL B213_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsB$cVal$mag$f
33 I-B -PH CURRENT ME_FL B213_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsC$cVal$mag$f
34 R-Y VOLTAGE ME_FL B213_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsAB$cVal$mag$f
35 Y-B VOLTAGE ME_FL B213_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsBC$cVal$mag$f
36 B-R VOLYAGE ME_FL B213_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsCA$cVal$mag$f
38 CB-B PH COUNTER ME_I B213_BCUUD3$RSLEDGAPC1$ST$INS2 stVal √
39 CB-R PH COUNTER ME_I B213_BCUUD3$RSLEDGAPC1$ST$INS stVal √
40 CB-Y PH COUNTER ME_I B213_BCUUD3$RSLEDGAPC1$ST$INS1 stVal √
42 BINARY INPUT (Single Point)
44 LED RESET SP B213_BCUApplication$LLN0$ST$LEDRs:2 stVal √
45 BCU MODE SP B213_BCUApplication$LLN0$ST$LocKey stVal √
46 87B RELAY SUPERVISION SP B213_BCUUD1$RSLEDGAPC1$ST$SPS14 stVal √ √
47 86A TRIP RELAY RESET
48 86A TRIP RELAY SUPERVISION
49 86A TRIP RELAY OPERATED
50 86B TRIP RELAY RESET SP B213_BCUUD1$RSLEDGAPC1$ST$SPC:2 stVal √ √
51 86B TRIP RELAY SUPERVISION SP B213_BCUUD1$RSLEDGAPC1$ST$SPS12 stVal √ √
52 86B TRIP RELAY OPERATED SP B213_BCUUD1$RSLEDGAPC1$ST$SPS11 stVal √ √
53 AC KIOSK SMOKE DETECTED SP B213_BCUUD1$RSLEDGAPC1$ST$SPS19 stVal √ √
54 AC KIOSK HEAT FIRE DETECTED SP B213_BCUUD1$RSLEDGAPC1$ST$SPS18 stVal √
55 CB AC SUPPLY FAIL SP B213_BCUUD1$RSLEDGAPC1$ST$SPS9 stVal √ √
56 AC SUPPLY-1 ON SP B213_BCUUD1$RSLEDGAPC1$ST$SPS20 stVal √ √
57 AC SUPPLY-1/2 FAIL SP B213_BCUUD1$RSLEDGAPC1$ST$SPS22 stVal √ √
58 AC SUPPLY-2 ON SP B213_BCUUD1$RSLEDGAPC1$ST$SPS21 stVal √ √
59 CB DC SUPPLY-1 FAIL SP B213_BCUUD1$RSLEDGAPC1$ST$SPS5 stVal √ √
60 CB DC SUPPLY-2 FAIL SP B213_BCUUD1$RSLEDGAPC1$ST$SPS6 stVal √ √
61 CB LOCAL SP B213_BCUUD1$RSLEDGAPC1$ST$SPS7 stVal √ √
62 EMERGENCY/MANUAL CLOSE SP B213_BCUUD1$RSLEDGAPC1$ST$SPS16 stVal √ √
63 EMERGENCY/MANUAL TRIP SP B213_BCUUD1$RSLEDGAPC1$ST$SPS15 stVal √ √
64 CB POLE DISCREPANCY OPERATED SP B213_BCUUD1$RSLEDGAPC1$ST$SPS1 stVal √ √
65 CB REMOTE POSITION SELECTED SP B213_BCUUD1$RSLEDGAPC1$ST$SPS8 stVal √ √
66 CB SF6 LOCKOUT SP B213_BCUUD1$RSLEDGAPC1$ST$SPS3 stVal √
67 CB SF6 LOW ALARM SP B213_BCUUD1$RSLEDGAPC1$ST$SPS2 stVal √
68 CB SPRING CHARGE STATUS SP B213_BCUUD1$RSLEDGAPC1$ST$SPS stVal √
69 DC SUPPLY-1 FAIL SP B213_BCUUD1$RSLEDGAPC1$ST$SPS13 stVal √
70 CB TC-1 R-PHASE FAULTY √ √
71 CB TC-1 Y-PHASE FAULTY √ √
72 CB TC-1 B-PHASE FAULTY √ √
73 CB TC-2 R-PHASE FAULTY √ √
74 CB TC-2 Y-PHASE FAULTY √ √
75 CB TC-2 B-PHASE FAULTY √ √
76 TIME SYNCHRONISATION ERROR SP B706_BCUApplication$LMTS0$ST$TmSynErr stVal √ √
77 GOOSE RECEIPT FAIL/TROUBLE SP B213_BCUUD1$RSLEDGAPC1$ST$SPS35 stVal √
78 CB MANUAL TRIP
79 CB MANUAL CLOSE
80 BUSBAR OPERATED
81 BCU IN LOCAL/REMOTE
82 SETTINGS CHANGED √
83 RELAY IN TEST MODE √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Feeder Name NAME ( 213 BC )
SIGNAL DESCRIPTION Information type Telegram address Position EVENT ALARM
BINARY INPUT (Single Point)
2 TIME SYNCHRONISATION ERROR SP B213_5051NEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
3 VT FUSE FAILURE SP B213_5051NEXT$pdGGIO3$ST$SPCSO41:0 stVal √ √
4 DIRECTIONAL DMT TRIP SP B213_5051NPROT$PTRC3$ST$Op stVal √ √
5 DIRECTIONAL DMT PICKUP SP B213_5051NPROT$PTRC3$ST$Str stVal √
6 DIRECTIONAL DMT OVERCURRENT STAGE-1 TRIP SP B213_5051NPROT$PTOC10$ST$Op stVal √ √
7 DIRECTIONAL DMT OVERCURRENT STAGE-1 PICKUP SP B213_5051NPROT$PTOC10$ST$Str stVal √
8 DIRECTIONAL DMT OVERCURRENT STAGE-2 TRIP SP B213_5051NPROT$PTOC11$ST$Op stVal √ √
9 DIRECTIONAL DMT OVERCURRENT STAGE-2 PICKUP SP B213_5051NPROT$PTOC11$ST$Str stVal √
10 DIRECTIONAL DMT EARTHFAULT STAGE-1 TRIP SP B213_5051NPROT$PTOC12$ST$Op stVal √ √
11 DIRECTIONAL DMT EARTHFAULT STAGE-1 PICKUP SP B213_5051NPROT$PTOC12$ST$Str stVal √
12 DIRECTIONAL DMT EARTHFAULT STAGE-2 TRIP SP B213_5051NPROT$PTOC13$ST$Op stVal √ √
13 DIRECTIONAL DMT EARTHFAULT STAGE-2 PICKUP SP B213_5051NPROT$PTOC13$ST$Str stVal √
14 DIRECTIONAL IDMT EARTHFAULT TRIP SP B213_5051NPROT$PTOC4$ST$Op stVal √ √
15 DIRECTIONAL IDMT EARTHFAULT PICKUP SP B213_5051NPROT$PTOC4$ST$Str stVal √
16 DIRECTIONAL IDMT OVERCURRENT TRIP SP B213_5051NPROT$PTOC3$ST$Op stVal √ √
17 DIRECTIONAL IDMT OVERCURRENT PICKUP SP B213_5051NPROT$PTOC3$ST$Str stVal √
18 DMT TRIP SP B213_5051NPROT$PTRC2$ST$Op stVal √ √
19 DMT PICKUP SP B213_5051NPROT$PTRC2$ST$Str stVal √
20 DMT OVERCURRENT STAGE-1 TRIP SP B213_5051NPROT$PTOC6$ST$Op stVal √ √
21 DMT OVERCURRENT STAGE-1 PICKUP SP B213_5051NPROT$PTOC6$ST$Str stVal √
22 DMT OVERCURRENT STAGE-2 TRIP SP B213_5051NPROT$PTOC7$ST$Op stVal √ √
23 DMT OVERCURRENT STAGE-2 PICKUP SP B213_5051NPROT$PTOC7$ST$Str stVal √
24 DMT OVERCURRENT STAGE-3 TRIP SP B213_5051NPROT$PTOC18$ST$Op stVal √ √
25 DMT OVERCURRENT STAGE-3 PICKUP SP B213_5051NPROT$PTOC18$ST$Str stVal √
26 DMT EARTHFAULT STAGE-1 TRIP SP B213_5051NPROT$PTOC8$ST$Op stVal √ √
27 DMT EARTHFAULT STAGE-1 PICKUP SP B213_5051NPROT$PTOC8$ST$Str stVal √
28 DMT EARTHFAULT STAGE-2 TRIP SP B213_5051NPROT$PTOC9$ST$Op stVal √ √
29 DMT EARTHFAULT STAGE-2 PICKUP SP B213_5051NPROT$PTOC9$ST$Str stVal √
30 THERMAL OVERLOAD TRIP SP B213_5051NPROT$PTTR1$ST$Op stVal √ √
31 THERMAL OVERLOAD PICKUP SP B213_5051NPROT$PTTR1$ST$Str stVal √
32 GENERAL TRIP SP B213_5051NPROT$PTRC1$ST$Tr stVal √ √
33 GENERAL PICKUP SP B213_5051NPROT$PTRC1$ST$Str stVal √
34 SETTINGS CHANGED √
35 RELAY IN TEST MODE √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
220kV ICT incomer
Sr. No. Voltage Level Feeder Name NAME ( BAY-205 ICT )
SIGNAL DESCRIPTION Information type Telegram address Position EVENT ALARM
BINARY INPUT (Double Point)
1 200KV 400kV ICT CB B-PH POSITION DP B205_BCUCB_1P_POSITION$RSLEDGAPC1$ST$DPS2 stVal √
2 CB R-PH POSITION DP B205_BCUCB_1P_POSITION$RSLEDGAPC1$ST$DPS stVal √
3 CB Y-PH POSITION DP B205_BCUCB_1P_POSITION$RSLEDGAPC1$ST$DPS1 stVal √
4 CB POSITION DP B205_BCUCB$CSWI1$ST$Pos:2 stVal √
5 89A POSITION DP B205_BCU89A$CSWI1$ST$Pos:2 stVal √
6 89AE POSITION DP B205_BCU89AE$CSWI1$ST$Pos:2 stVal √
7 89B POSITION DP B205_BCU89B$CSWI1$ST$Pos:2 stVal √
8 89C POSITION DP B205_BCU89C$CSWI1$ST$Pos:2 stVal √
9 89T POSITION DP B205_BCU89T$CSWI1$ST$Pos:2 stVal √
10 89TE1 POSITION DP B205_BCU89TE1$CSWI1$ST$Pos:2 stVal √
11 89TE2 POSITION DP B205_BCU89TE2$CSWI1$ST$Pos:2 stVal √
13 BINARY INPUT (Single Point)
15 LED RESET SP B205_BCUApplication$LLN0$ST$LEDRs:2 stVal √
16 BCU MODE SP B205_BCUApplication$LLN0$ST$LocKey stVal √
17 86A TRIP RELAY RESET SP B205_BCUUD1$RSLEDGAPC1$ST$SPC:2 stVal √ √
18 86A TRIP RELAY FAULTY SP B205_BCUUD1$RSLEDGAPC1$ST$SPS12 stVal √ √
19 86A TRIP RELAY OPTD SP B205_BCUUD1$RSLEDGAPC1$ST$SPS11 stVal √ √
20 86B TRIP RELAY RESET SP B205_BCUUD1$RSLEDGAPC1$ST$SPC1:2 stVal √ √
21 86B TRIP RELAY FAULTY SP B205_BCUUD1$RSLEDGAPC1$ST$SPS24 stVal √ √
22 86B TRIP RELAY OPTD SP B205_BCUUD1$RSLEDGAPC1$ST$SPS23 stVal √ √
23 87B RELAY FAULTY SP B205_BCUUD1$RSLEDGAPC1$ST$SPS14 stVal √ √
24 AC KIOSK HEAT FIRE DETECTION SP B205_BCUUD1$RSLEDGAPC1$ST$SPS19 stVal √ √
25 AC KIOSK SMOKE DETECTION SP B205_BCUUD1$RSLEDGAPC1$ST$SPS18 stVal √ √
26 CB AC SUPPLY FAIL SP B205_BCUUD1$RSLEDGAPC1$ST$SPS9 stVal √ √
27 AC-1 ON SP B205_BCUUD1$RSLEDGAPC1$ST$SPS20 stVal √
28 AC-1/2 POWER FAIL SP B205_BCUUD1$RSLEDGAPC1$ST$SPS22 stVal √ √
29 AC-2 ON SP B205_BCUUD1$RSLEDGAPC1$ST$SPS21 stVal √
30 BAY IN NORMAL MODE SP B205_BCUUD1$RSLEDGAPC1$ST$SPS26 stVal √
31 BAY IN TRANSFER MODE SP B205_BCUUD1$RSLEDGAPC1$ST$SPS25 stVal √
32 BUS-1 VT DESELECTED SP B205_BCUUD1$RSLEDGAPC1$ST$SPS35 stVal √
33 BUS-1 VT SELECTED SP B205_BCUUD1$RSLEDGAPC1$ST$SPS34 stVal √
34 BUS-2 VT DESELECTED SP B205_BCUUD1$RSLEDGAPC1$ST$SPS28 stVal √
35 BUS-2 VT SELECTED SP B205_BCUUD1$RSLEDGAPC1$ST$SPS27 stVal √
36 CB DC-1 SUPPLY FAIL SP B205_BCUUD1$RSLEDGAPC1$ST$SPS5 stVal √
37 CB DC-2 SUPPLY FAIL SP B205_BCUUD1$RSLEDGAPC1$ST$SPS6 stVal √
38 CB IN LOCAL MODE SP B205_BCUUD1$RSLEDGAPC1$ST$SPS7 stVal √
39 EMERGENCY/MANUAL CB CLOSE SP B205_BCUUD1$RSLEDGAPC1$ST$SPS16 stVal √ √
40 EMERGENCY/MANUAL CB TRIP SP B205_BCUUD1$RSLEDGAPC1$ST$SPS15 stVal √ √
41 CB POLE DISCREPANCY OPTD SP B205_BCUUD1$RSLEDGAPC1$ST$SPS1 stVal √ √
42 CB REMOTE POSITION SELECTED SP B205_BCUUD1$RSLEDGAPC1$ST$SPS8 stVal √ √
43 CB SF6 LOCKOUT SP B205_BCUUD1$RSLEDGAPC1$ST$SPS3 stVal √ √
44 CB SF6 GAS PRESSURE REFILL LOW ALARM SP B205_BCUUD1$RSLEDGAPC1$ST$SPS2 stVal √ √
45 CB SPRING CHARGED SP B205_BCUUD1$RSLEDGAPC1$ST$SPS stVal √ √
46 DC SUPPLY-1 FAIL SP B205_BCUUD1$RSLEDGAPC1$ST$SPS13 stVal √ √
47 CB TC-1 R-PHASE FAULTY √ √
48 CB TC-1 Y-PHASE FAULTY √ √
49 CB TC-1 B-PHASE FAULTY SP stVal √ √
50 CB TC-2 R-PHASE FAULTY SP stVal √ √
51 CB TC-2 Y-PHASE FAULTY SP stVal √ √
52 CB TC-2 B-PHASE FAULTY SP stVal √ √
53 NORMAL MODE SP B205_BCUUD1$RSLEDGAPC1$ST$SPS33 stVal √
54 TRANSFER MODE SP B205_BCUUD1$RSLEDGAPC1$ST$SPS32 stVal √
55 GOOSE RECEIPT FAIL/TROUBLE SP B205_BCUUD1$RSLEDGAPC1$ST$SPS35 stVal √ √
56 TIME SYNCHRONISATION ERROR SP B205_BCUApplication$LMTS0$ST$TmSynErr stVal √ √
60 POWER FACTOR ME_FL B205_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotPF:1 mag$f
61 FREQUENCY ME_FL B205_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$Hz:1 mag$f
62 ACTIVE POWER ME_FL B205_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotW:1 mag$f
63 REACTIVE POWER ME_FL B205_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVAr:1 mag$f
64 APPARENT POWER ME_FL B205_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVA:1 mag$f
65 I-R-PH CURRENT ME_FL B205_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsA$cVal$mag$f
66 I-Y-PH CURRENT ME_FL B205_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsB$cVal$mag$f
67 I-B-PH CURRENT ME_FL B205_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsC$cVal$mag$f
68 R-Y VOLTAGE ME_FL B205_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsAB$cVal$mag$f
69 Y-B VOLTAGE ME_FL B205_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsBC$cVal$mag$f
70 B-R VOLYAGE ME_FL B205_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsCA$cVal$mag$f
72 CB B-PH COUNTER ME_I B205_BCUUD3$RSLEDGAPC1$ST$INS2 stVal
73 CB R-PH COUNTER ME_I B205_BCUUD3$RSLEDGAPC1$ST$INS stVal
74 CB Y-PH COUNTER ME_I B205_BCUUD3$RSLEDGAPC1$ST$INS1 stVal
78 89A CONTROL DC B205_BCU89A$CSWI1$CO$Pos:8 Oper$ctlVal √
79 89AE CONTROL DC B205_BCU89AE$CSWI1$CO$Pos:8 Oper$ctlVal √
80 89B CONTROL DC B205_BCU89B$CSWI1$CO$Pos:8 Oper$ctlVal √
81 89C CONTROL DC B205_BCU89C$CSWI1$CO$Pos:8 Oper$ctlVal √
82 89T CONTROL DC B205_BCU89T$CSWI1$CO$Pos:8 Oper$ctlVal √
83 89TE1 CONTROL DC B205_BCU89TE1$CSWI1$CO$Pos:8 Oper$ctlVal √
84 89TE2 CONTROL DC B205_BCU89TE2$CSWI1$CO$Pos:8 Oper$ctlVal √
85 CB CONTROL DC B205_BCUCB$CSWI1$CO$Pos:8 Oper$ctlVal √
86 TRANSFER/NORMALCONTROL DC B205_BCUDc8$CSWI1$CO$Pos:8 Oper$ctlVal √
87 86A TRIP RELAY RESET COMMAND SC B205_BCUUD1$RSLEDGAPC1$CO$SPC:8 Oper$ctlVal √
88 86B TRIP RELAY RESET COMMAND SC B205_BCUUD1$RSLEDGAPC1$CO$SPC1:8 Oper$ctlVal √
89 CB MANUAL TRIP
90 CB MANUAL CLOSE
91 BUSBAR OPERATED
92 BCU IN LOCAL/REMOTE
93 SETTINGS CHANGED √
94 RELAY IN TEST MODE √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
SIEMENS SCADA GENERAL SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (INDEX)
Sheet Ref. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 6MD66 BCU LINE BCU STNM7XXLBCU BCU is for each bay so 7XX refers to Bay
2 7SA522 7SA522_21M1 LINE DISTANCE MAIN-1 STNM7XXL21M1 Bay No. 7XX will be always the main bay number for the ICT feeder
3 7SD522 7SD522_87M1 LINE DIFFERENTIAL/DISTANCE MAIN-2 STNM7XXL87M1 Bay No. 7XX will be always the main bay number for the ICT feeder
NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "7XX" stand for Bay name, example if the bay no 701 then same has to be implemented like STNM701BCU
Sr. No. Voltage Level Feeder Name
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Double Point)
1 220kV 220kV LINE CB B-PH POSITION DP B206_BCUCBB$XCBR1$ST$Pos:2 stVal √
2 CB R-PH POSITION DP B206_BCUCBR$XCBR1$ST$Pos:2 stVal √
3 CB Y-PH POSITION DP B206_BCUCBY$XCBR1$ST$Pos:2 stVal √
4 CB POSITION DP B206_BCUCB$CSWI1$ST$Pos:2 stVal √
5 89AE1 POSITION DP B206_BCU89AE1$CSWI3$ST$Pos:2 stVal √
6 89AE2 POSITION DP B206_BCU89AE2$CSWI8$ST$Pos:2 stVal √
7 89BE POSITION DP B206_BCU89BE$CSWI5$ST$Pos:2 stVal √
8 89A POSITION DP B206_BCU89A$CSWI2$ST$Pos:2 stVal √
9 89B POSITION DP B206_BCU89B$CSWI4$ST$Pos:2 stVal √
10 89L POSITION DP B206_BCU89L$CSWI6$ST$Pos:2 stVal √
11 89LE POSITION DP B206_BCU89LE$CSWI7$ST$Pos:2 stVal √
12 89 BE1 POSITION
13 89 BE2 POSITION
14 THE LOGICAL NODE FOR BUS EARTH SWITCHES, ISOLATOR & EARTHSWITCHES FOR 3 PH/1PH REACTORS & ITCs, e.g 89 BR, BRE, LR, LRE, RS1, RS2, RS1E, 89T,TE, 89AE2, 89BE2 MAY BE ASSIGNED AS PER AVAILABILITY/SCHEME
15 BINARY INPUT (Single Point)
17 AUX POWER FAIL SP B206_BCUApplication$LPHD0$ST$AuxPwrFail stVal √ √
18 TIME SYNCHRONISATION ERROR SP B206_BCUApplication$LMTS0$ST$TmSynErr stVal √ √
19 BCU MODE SP B206_BCUApplication$LLN0$ST$LocKey stVal √
22 CT SF6 GAS PRESSURE REFILL LOW ALARM SP B206_BCUApplication$USER1$ST$SPS stVal √ √
23 CT SF6 GAS PRESSURE LOCKOUT SP B206_BCUApplication$USER1$ST$SPS1 stVal √ √
24 TRIP RELAY SUPERVISION SP B206_BCUApplication$USER5$ST$SPS stVal √ √
25 CARRIER CHANNEL-2 OUT SP B206_BCUApplication$USER5$ST$SPS1 stVal √ √
26 MAIN-2 RELAY FAULTY SP B206_BCUApplication$USER5$ST$SPS2 stVal √ √
27 EMERGENCY/MANUAL TRIP SP B206_BCUApplication$USER5$ST$SPS4 stVal √ √
28 SPEECH CHANNEL FAIL SP B206_BCUApplication$USER5$ST$SPS3 stVal √ √
29 SURGE ARRESTER B-PH SP B206_BCUApplication$USER5$ST$SPS7 stVal √ √
30 SURGE ARRESTER R-PH SP B206_BCUApplication$USER5$ST$SPS5 stVal √ √
31 SURGE ARRESTER Y-PH SP B206_BCUApplication$USER5$ST$SPS6 stVal √ √
32 89A POLE DESCREPENCY SP B206_BCUApplication$USER3$ST$SPS5 stVal √ √
33 89B POLE DESCREPENCY SP B206_BCUApplication$USER3$ST$SPS6 stVal √ √
34 CB DC SUPPLY-1/2 FAIL SP B206_BCUApplication$USER3$ST$SPS1 stVal √ √
35 CB SPRING NOT CHARGED B-PH SP B206_BCUApplication$USER3$ST$SPS4 stVal √ √
36 CB SPRING NOT CHARGED R-PH SP B206_BCUApplication$USER3$ST$SPS2 stVal √ √
37 CB SPRING NOT CHARGED Y-PH SP B206_BCUApplication$USER3$ST$SPS3 stVal √ √
38 CB SF6 GAS PRESSURE LOCKOUT SP B206_BCUApplication$USER3$ST$SPS stVal √ √
39 86B TRIP RELAY FAULTY SP B206_BCUApplication$USER4$ST$SPS3 stVal √ √
40 86A TRIP RELAY FAULTY SP B206_BCUApplication$USER4$ST$SPS3 stVal √ √
41 86A TRIP RELAY OPERATED SP B206_BCUApplication$USER4$ST$SPS2 stVal √ √
42 86B TRIP RELAY OPERATED SP B206_BCUApplication$USER4$ST$SPS6 stVal √ √
43 89L POLE DESCREPENCY SP B206_BCUApplication$USER4$ST$SPS stVal √ √
44 CARRIER CHANNEL-1 OUT SP B206_BCUApplication$USER4$ST$SPS4 stVal √ √
45 CB TC-1 R-PHASE FAULTY
46 CB TC-1 Y-PHASE FAULTY
47 CB TC-1 B-PHASE FAULTY
48 CB TC-2 R-PHASE FAULTY
49 CB TC-2 Y-PHASE FAULTY SP B206_BCUApplication$USER4$ST$SPS1 stVal √ √
50 CB TC-2 B-PHASE FAULTY SP B206_BCUApplication$USER4$ST$SPS5 stVal √ √
51 CB POLE DESCREPENCY OPTD-1
52 CB POLE DESCREPENCY OPTD-2 SP B206_BCUApplication$USER2$ST$SPS1 stVal √ √
53 CB SF6 GAS PRESSURE REFILL LOW ALARM SP B206_BCUApplication$USER2$ST$SPS stVal √ √
54 BUS-1 VT SELECTED SP B206_BCUApplication$USER6$ST$SPS1 stVal √
55 ICT LV VT SELECTED SP B206_BCUApplication$USER6$ST$SPS2 stVal √
56 LINE VT SELECTED SP B206_BCUApplication$USER6$ST$SPS stVal √
57 CB READY SP B206_BCUCB$XCBR1$ST$Rdy stVal √
58 EMERGENCY/MANUAL CB CLOSE SP B206_BCUCB$GAPC2$ST$Detected stVal √
59 DEVICE HEALTHY SP B206_BCUApplication$LPHD0$ST$PhyHealth:0 stVal:1 √
60 CB POSITION NO SYNC SP B206_BCUCB$CSWI1$ST$Pos noSync √ √
61 CB CLOSE INTERLOCK SP B206_BCUCB$CILO1$ST$EnaCls stVal √ √
62 765kV 765kV LINE 89AE1 OPEN INTERLOCK SP B206_BCU89AE1$CILO3$ST$EnaOpn stVal √ √
63 89AE2 OPEN INTERLOCK SP B206_BCU89AE2$CILO8$ST$EnaOpn stVal √ √
64 89BE OPEN INTERLOCK SP B206_BCU89BE$CILO5$ST$EnaOpn stVal √ √
65 89A OPEN INTERLOCK SP B206_BCU89A$CILO2$ST$EnaOpn stVal √ √
66 89B OPEN INTERLOCK SP B206_BCU89B$CILO4$ST$EnaOpn stVal √ √
67 89L OPEN INTERLOCK SP B206_BCU89L$CILO6$ST$EnaOpn stVal √ √
68 89LE OPEN INTERLOCK SP B206_BCU89LE$CILO7$ST$EnaOpn stVal √ √
71 BUSBAR 7ES-B1 OPEN(BUS EARTH SWITCH)
72 BUSBAR 7ES-B2 OPEN(BUS EARTH SWITCH)
73 BUSBAR 7ES-B1 CLOSE INTERLOCK
74 BUSBAR 7ES-B2 CLOSE INTERLOCK
75 GOOSE RECEIPT FAIL/TROUBLE SP B206_BCUApplication$USER6$ST$SPS3 stVal √ √
76 DFR/DR FAIL ALARM
77 GOOSE RECEIPT FAIL/TROUBLE SP B206_BCUApplication$LLN0$ST$SPS stVal √
78 A/R BLOCK SP B206_BCUCB1_79AutoReclosing$GEN_RREC1$ST$BlkFct stVal √
79 A/R FUNCTION OFF SP B206_BCUCB1_79AutoReclosing$GEN_RREC1$ST$Off stVal √
80 A/R FUNCTION ON SP B206_BCUCB1_79AutoReclosing$GEN_RREC1$ST$On stVal √
81 A/R READY SP B206_BCUCB1_79AutoReclosing$GEN_RREC1$ST$AutoRecSt:0 stVal:1 √
82 A/R UNSUCCESSFUL SP B206_BCUCB1_79AutoReclosing$GEN_RREC1$ST$AutoRecSt:0 stVal:10 √ √
84 A/R SUCCESSFUL SP B206_BCUCB1_79AutoReclosing$GEN_RREC1$ST$Successful stVal √
85 RECLAIM IN PROGRESS
86 MAIN A/R LOCKOUT
87 TIE A/R LOCKOUT
88 Tie CB A/R PRIORITY CLOSE
89 MAIN/TIE BCU HEALTHY
90 AR SINGLE PHASE TRIP PERMITTED
91 CB NOT READY SP B206_BCUCB1_79AutoReclosing$GEN_RREC1$ST$CBnotRdy stVal √
92 A/R CLOSE COMMAND INDICATION SP B206_BCUCB1_79AutoReclosing$GEN_RREC1$ST$OpCls general √
93 A/R IN PROGRESS SP B206_BCUCB1_79AutoReclosing$GEN_RREC1$ST$RecInit stVal √
94 RELAY IN TEST MODE
95 SETTINGS CHANGED
96 CB MANUAL TRIP
97 CB MANUAL CLOSE
98 BUSBAR OPERATED
99 BCU IN LOCAL/REMOTE
100 MEASUREMENT
102 POWER FACTOR ME_FL B206_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotPF:1 mag$f
103 FREQUENCY ME_FL B206_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$Hz:1 mag$f
104 ACTIVE POWER ME_FL B206_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotW:1 mag$f
105 REACTIVE POWER ME_FL B206_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVAr:1 mag$f
106 APPARENT POWER ME_FL B206_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVA:1 mag$f
107 I-R-PH CURRENT ME_FL B206_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsA$cVal$mag$f
108 I-Y-PH CURRENT ME_FL B206_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsB$cVal$mag$f
109 I-B-PH CURRENT ME_FL B206_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsC$cVal$mag$f
110 R-Y VOLTAGE ME_FL B206_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsAB$cVal$mag$f
111 Y-B VOLTAGE ME_FL B206_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsBC$cVal$mag$f
112 B-R VOLYAGE ME_FL B206_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsCA$cVal$mag$f
113 CB-B-PH COUNTER ME_I B206_BCUCBB$XCBR1$ST$OpCnt stVal
114 CB-R-PH COUNTER ME_I B206_BCUCBR$XCBR1$ST$OpCnt stVal
115 CB-Y-PH COUNTER ME_I B206_BCUCBY$XCBR1$ST$OpCnt stVal
116 SURGE ARRESTER B-PH ME_I
117 SURGE ARRESTER R-PH ME_I
118 SURGE ARRESTER Y-PH ME_I
119 CB R-PHASE OPERATION COUNTER ME_I
120 CB Y-PHASE OPERATION COUNTER ME_I
121 CB B-PHASE OPERATION COUNTER ME_I
125 CB CONTROL DC B206_BCUCB$CSWI1$CO$Pos:8 Oper$ctlVal √
126 89AE1 CONTROL DC B206_BCU89AE1$CSWI3$CO$Pos:8 Oper$ctlVal √
127 89AE2 CONTROL DC B206_BCU89AE2$CSWI8$CO$Pos:8 Oper$ctlVal √
128 89BE CONTROL DC B206_BCU89BE$CSWI5$CO$Pos:8 Oper$ctlVal √
129 89A CONTROL DC B206_BCU89A$CSWI2$CO$Pos:8 Oper$ctlVal √
130 89B CONTROL DC B206_BCU89B$CSWI4$CO$Pos:8 Oper$ctlVal √
131 89L CONTROL DC B206_BCU89L$CSWI6$CO$Pos:8 Oper$ctlVal √
132 89LE CONTROL DC B206_BCU89LE$CSWI7$CO$Pos:8 Oper$ctlVal √
133 CB CONTROL NO SYNC SC B206_BCUCB$CSWI1$CO$Pos Oper$noSync √
134 86A TRIP RELAY RESET COMMAND SC B206_BCUApplication$USER2$CO$SPC:8 Oper$ctlVal √
135 86B TRIP RELAY RESET COMMAND SC B206_BCUApplication$USER2$CO$SPC1:8 Oper$ctlVal √
136 A/R ON CONTROL SC B206_BCUApplication$USER8$CO$SPC:8 Oper$ctlVal √
137 A/R OFF CONTROL SC B206_BCUApplication$USER8$CO$SPC1:8 Oper$ctlVal √
138 MAIN-1 LED RESET SC
139 MAIN-2 LED RESET SC
140 SETTINGS CHANGED
141 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Feeder Name Assumed as Main-1 relay
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION EVENT ALARM
1 220kV 220kV LINE FAULT DISTANCE ME_FL B206_21_1PROT$RFLO1$MX$FltDiskm:0 mag$f
2 FAULT CURRENT ME_FL
3 FAULT LOCATION DISTANCE ME_FL
4 MAIN-1 CARRIER RECEIVE CHANNEL-1 ME_I
5 MAIN-1 CARRIER SEND CHANNEL-1 ME_I
6 MAIN-2 CARRIER RECEIVE CHANNEL-1 ME_I
7 MAIN-2 CARRIER SEND CHANNEL-1 ME_I
8 MAIN-2 CARRIER RECEIVE CHANNEL-2 ME_I
9 MAIN-2 CARRIER SEND CHANNEL-2 ME_I
10 MAIN-1 CARRIER RECEIVE CHANNEL-2 ME_I
11 MAIN-1 CARRIER SEND CHANNEL-2 ME_I
12 DT RECEIVE CHANNEL-1 ME_I
13 DT SEND CHANNEL-1 ME_I
14 DT RECEIVE CHANNEL-2 ME_I
15 DT SEND CHANNEL-2 ME_I
16 CARRIER FAIL CHANNEL-1 ME_I
17 CARRIER FAIL CHANNEL-2 ME_I
18 CARRIER RECEIVED CHANNEL-1 ME_I B206_21_1CTRL$GGIO1$ST$ISCSO3:0 stVal
19 CARRIER RECEIVED CHANNEL-2 ME_I B206_21_1CTRL$GGIO1$ST$ISCSO4:0 stVal
20 CARRIER SEND CHANNEL-2 ME_I B206_21_1CTRL$GGIO1$ST$ISCSO1:0 stVal
21 CARRIER SEND CHANNEL-1 ME_I B206_21_1CTRL$GGIO1$ST$ISCSO2:0 stVal
22 DIRECT TRIP RECEIVED CHANNEL-1 ME_I B206_21_1CTRL$GGIO1$ST$ISCSO6:0 stVal
23 DIRECT TRIP SEND CHANNEL-1 ME_I B206_21_1CTRL$GGIO1$ST$ISCSO5:0 stVal
24 CARRIER FAIL CHANNEL-1 ME_I B206_21_1CTRL$GGIO2$ST$ISCSO7:0 stVal
25 CARRIER FAIL CHANNEL-2 ME_I B206_21_1CTRL$GGIO2$ST$ISCSO8:0 stVal
27 BINARY INPUT (Single Point)
28 DIRECT TRIP SEND CHANNEL-2 GOOSE
29 CARRIER FAIL CHANNEL-1 SP B206_21_1CTRL$GGIO1$ST$SPCSO25:0 stVal √ √
30 NO VOLTAGE IN LINE SP B206_21_1CTRL$GGIO1$ST$SPCSO21:0 stVal √ √
31 A/R BLOCK SP B206_21_1CTRL$GGIO1$ST$SPCSO14:0 stVal √
32 MAIN A/R LOCKOUT
33 TIE A/R LOCKOUT
34 DIRECT TRIP SEND CHANNEL-1 SP B206_21_1CTRL$GGIO1$ST$SPCSO18:0 stVal √ √
35 GOOSE RECEIPT FAIL/TROUBLE SP B206_21_1CTRL$GGIO1$ST$SPCSO24:0 stVal √ √
36 MAIN-2 RELAY FAIL SP B206_21_1CTRL$GGIO1$ST$SPCSO20:0 stVal √
37 89L OPEN FOR STUB SP B206_21_1CTRL$GGIO1$ST$SPCSO17:0 stVal √ √
38 DIRECT TRIP RECEIVED CHANNEL-1 SP B206_21_1CTRL$GGIO1$ST$SPCSO16:0 stVal √ √
39 LBB OPERATED SP B206_21_1CTRL$GGIO1$ST$SPCSO10:0 stVal √ √
40 TIME SYNCHRONISATION ERROR SP B206_21_1EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
41 VT FUSE FAILURE SP B206_21_1EXT$pdGGIO3$ST$SPCSO42:0 stVal √ √
42 BROKEN CONDUCTOR SP B206_21_1EXT$pdGGIO4$ST$SPCSO3:0 stVal √ √
43 EMERGENCY/MANUAL CLOSE SP B206_21_1EXT$pdGGIO6$ST$SPCSO36:0 stVal √
44 CARRIER RECEIVED CHANNEL-1 SP B206_21_1EXT$pdGGIO63$ST$SPCSO38:0 stVal √ √
45 CARRIER RECEIVED CHANNEL-2 SP B206_21_1EXT$pdGGIO63$ST$SPCSO42:0 stVal √ √
46 CARRIER FAULTY SP B206_21_1EXT$pdGGIO63$ST$SPCSO37:0 stVal √ √ NOT REQUIRED
47 SOTF PICKUP SP B206_21_1EXT$pdGGIO67$ST$SPCSO57:0 stVal √
48 SOTF TRIP( OC)
49 SOTF TRIP( IMPEDANCE Z1B) SP B206_21_1EXT$pdGGIO68$ST$SPCSO7:0 stVal √ √
50 CARRIER SEND CHANNEL-1 SP B206_21_1PROT$PSCH1$ST$ProTx stVal √ √
51 CARRIER SEND CHANNEL-2 GOOSE
52 DIRECT TRIP RECEIVED CHANNEL-2 GOOSE
53 CARRIER RECEIVED SP B206_21_1PROT$PSCH1$ST$ProRx stVal √ √ NOT REQUIRED
54 CARRIER ADDIED TRIP/Z COM. TRIP SP B206_21_1PROT$PSCH1$ST$Op general √ √
55 MAIN A/R OPTD
56 TIE A/R OPTD
57 CB MANUAL CLOSE
58 CB MANUAL TRIP
59 86 GROUP-A OPTD
60 86 GROUP-B OPTD
61 MAIN A/R START
62 TIE A/R START
63 DISTANCE ZONE-1 PICKUP SP B206_21_1PROT$PDIS1$ST$Str general √
64 DISTANCE PROTN ZONE-1 TRIP SP B206_21_1PROT$PDIS1$ST$Op general √ √
65 DISTANCE PROTN ZONE-1 R-PH TRIP SP B206_21_1PROT$PDIS1$ST$Op phsA √ √
66 DISTANCE PROTN ZONE-1 Y-PH TRIP SP B206_21_1PROT$PDIS1$ST$Op phsB √ √
67 DISTANCE PROTN ZONE-1 B-PH TRIP SP B206_21_1PROT$PDIS1$ST$Op phsC √ √
68 DISTANCE ZONE-2 PICKUP SP B206_21_1PROT$PDIS2$ST$Str general √
69 DISTANCE PROTN ZONE-2 TRIP SP B206_21_1PROT$PDIS2$ST$Op general √ √
70 DISTANCE PROTN ZONE-2 R-PH TRIP SP B206_21_1PROT$PDIS2$ST$Op phsA √ √
71 DISTANCE PROTN ZONE-2 Y-PH TRIP SP B206_21_1PROT$PDIS2$ST$Op phsB √ √
72 DISTANCE PROTN ZONE-2 B-PH TRIP SP B206_21_1PROT$PDIS2$ST$Op phsC √ √
73 DISTANCE ZONE-3 PICKUP SP B206_21_1PROT$PDIS3$ST$Str general √
74 DISTANCE PROTN ZONE-3 TRIP SP B206_21_1PROT$PDIS3$ST$Op general √ √
75 DISTANCE ZONE-4 PICKUP SP B206_21_1PROT$PDIS4$ST$Str general √
76 DISTANCE PROTN ZONE-4 TRIP SP B206_21_1PROT$PDIS4$ST$Op general √ √
77 DISTANCE PROTN ZONE-4 R-PH TRIP
78 DISTANCE PROTN ZONE-4 Y-PH TRIP
79 DISTANCE PROTN ZONE-4 B-PH TRIP
80 DISTANCE PROTN ZONE-1B PICKUP SP B206_21_1PROT$PDIS10$ST$Str general √
81 DISTANCE PROTN ZONE-1B TRIP SP B206_21_1PROT$PDIS10$ST$Op general √ √
82 DISTANCE PROTN ZONE-1B B-PH TRIP SP B206_21_1PROT$PDIS10$ST$Op phsC √ √
83 DISTANCE PROTN ZONE-1B R-PH TRIP SP B206_21_1PROT$PDIS10$ST$Op phsA √ √
84 DISTANCE PROTN ZONE-1B Y-PH TRIP SP B206_21_1PROT$PDIS10$ST$Op phsB √ √
85 DISTANCE PROTN ZONE-5 PICKUP
86 STUB PICKUP SP B206_21_1PROT$PTOC4$ST$Str general √
87 STUB OPERATED SP B206_21_1PROT$PTOC4$ST$Op general √ √
88 DEF FAULT PICKUP SP B206_21_1PROT$PTOC8$ST$Str general √
89 DEF FAULT TRIP SP B206_21_1PROT$PTOC8$ST$Op general √ √
90 OVERVOLTAGE STAGE-1-PH-N PICKUP SP B206_21_1PROT$PTOV1$ST$Str general √
91 OVERVOLTAGE STAGE-1 -PH-N TRIP SP B206_21_1PROT$PTOV1$ST$Op general √ √
92 OVERVOLTAGE STAGE-2-PH-N PICKUP SP B206_21_1PROT$PTOV2$ST$Str general √
93 OVERVOLTAGE STAGE-2-PH-N TRIP SP B206_21_1PROT$PTOV2$ST$Op general √ √
94 OVERVOLTAGE STAGE-1-PH-PH PICKUP SP B206_21_1PROT$PTOV3$ST$Str general √
95 OVERVOLTAGE STAGE-1-PH-PH TRIP SP B206_21_1PROT$PTOV3$ST$Op general √ √
96 OVERVOLTAGE STAGE-2-PH-PH PICKUP SP B206_21_1PROT$PTOV4$ST$Str general √
97 OVERVOLTAGE STAGE-2-PH-PH TRIP SP B206_21_1PROT$PTOV4$ST$Op general √ √
98 POWER SWING ZONE-1 DETECTED SP B206_21_1PROT$RPSB1$ST$Str general √ √
99 POWER SWING ZONE-1 BLOCK SP B206_21_1PROT$RPSB1$ST$BlkZn stVal √
100 POWER SWING ZONE-1B DETECTED SP B206_21_1PROT$RPSB10$ST$Str general √ √
101 POWER SWING ZONE-1B BLOCK SP B206_21_1PROT$RPSB10$ST$BlkZn stVal √
102 POWER SWING ZONE-2 DETECTED SP B206_21_1PROT$RPSB2$ST$Str general √ √
103 POWER SWING ZONE-2 BLOCK SP B206_21_1PROT$RPSB2$ST$BlkZn stVal √
104 POWER SWING ZONE-3 DETECTED SP B206_21_1PROT$RPSB3$ST$Str general √ √
105 POWER SWING ZONE-3 BLOCK SP B206_21_1PROT$RPSB3$ST$BlkZn stVal √
106 POWER SWING ZONE-4 DETECTED SP B206_21_1PROT$RPSB4$ST$Str general √ √
107 POWER SWING ZONE-4 BLOCK SP B206_21_1PROT$RPSB4$ST$BlkZn stVal √
108 BUSBAR PROTN OPTD
109 RELAY LED RESET SC
110 MAIN BCU FAIL
111 TIE BCU FAIL
112 MANUAL DR TRIGGER SC
113 GENERAL TRIP SP B206_21_1PROT$PTRC1$ST$Tr general √ √
114 DEVICE HEALTHY SP B707_21_1PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
115 MAIN-2 PROTN OPTD
116 STUB BLOCKED SP B206_21_1PROT$PTOC4$ST$Blk stVal √ √
117 SETTINGS CHANGED
118 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Feeder Name Assumed as Main-1 relay
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION EVENT ALARM
1 220kV 220kV LINE FAULT DISTANCE ME_FL B206_21_1PROT$RFLO1$MX$FltDiskm:0 mag$f
2 FAULT CURRENT ME_FL
3 FAULT LOCATION DISTANCE ME_FL
4 MAIN-1 CARRIER RECEIVE CHANNEL-1 ME_I
5 MAIN-1 CARRIER SEND CHANNEL-1 ME_I
6 MAIN-2 CARRIER RECEIVE CHANNEL-1 ME_I
7 MAIN-2 CARRIER SEND CHANNEL-1 ME_I
8 MAIN-2 CARRIER RECEIVE CHANNEL-2 ME_I
9 MAIN-2 CARRIER SEND CHANNEL-2 ME_I
10 MAIN-1 CARRIER RECEIVE CHANNEL-2 ME_I
11 MAIN-1 CARRIER SEND CHANNEL-2 ME_I
12 DT RECEIVE CHANNEL-1 ME_I
13 DT SEND CHANNEL-1 ME_I
14 DT RECEIVE CHANNEL-2 ME_I
15 DT SEND CHANNEL-2 ME_I
16 CARRIER FAIL CHANNEL-1 ME_I
17 CARRIER FAIL CHANNEL-2 ME_I
18 CARRIER RECEIVED CHANNEL-1 ME_I B206_21_1CTRL$GGIO1$ST$ISCSO3:0 stVal
19 CARRIER RECEIVED CHANNEL-2 ME_I B206_21_1CTRL$GGIO1$ST$ISCSO4:0 stVal
20 CARRIER SEND CHANNEL-2 ME_I B206_21_1CTRL$GGIO1$ST$ISCSO1:0 stVal
21 CARRIER SEND CHANNEL-1 ME_I B206_21_1CTRL$GGIO1$ST$ISCSO2:0 stVal
22 DIRECT TRIP RECEIVED CHANNEL-1 ME_I B206_21_1CTRL$GGIO1$ST$ISCSO6:0 stVal
23 DIRECT TRIP SEND CHANNEL-1 ME_I B206_21_1CTRL$GGIO1$ST$ISCSO5:0 stVal
24 CARRIER FAIL CHANNEL-1 ME_I B206_21_1CTRL$GGIO2$ST$ISCSO7:0 stVal
25 CARRIER FAIL CHANNEL-2 ME_I B206_21_1CTRL$GGIO2$ST$ISCSO8:0 stVal
27 BINARY INPUT (Single Point)
28 LINE DIFFERENTIAL GENERAL TIP
29 LINE DIFFERENTIAL REMOTE TRIP
30 LINE DIFFERENTIAL R-PH TRIP
31 LINE DIFFERENTIAL Y-PH TRIP
32 LINE DIFFERENTIAL -PH TRIP
33 LINE COMMUNICATION CHANNEL-1 FAULTY
34 LINE COMMUNICATION CHANNEL-2 FAULTY
35 DIRECT TRIP SEND CHANNEL-2 GOOSE
36 CARRIER FAIL CHANNEL-1 SP B206_21_1CTRL$GGIO1$ST$SPCSO25:0 stVal √ √
37 NO VOLTAGE IN LINE SP B206_21_1CTRL$GGIO1$ST$SPCSO21:0 stVal √ √
38 A/R BLOCK SP B206_21_1CTRL$GGIO1$ST$SPCSO14:0 stVal √
39 MAIN A/R LOCKOUT
40 TIE A/R LOCKOUT
41 DIRECT TRIP SEND CHANNEL-1 SP B206_21_1CTRL$GGIO1$ST$SPCSO18:0 stVal √ √
42 GOOSE RECEIPT FAIL/TROUBLE SP B206_21_1CTRL$GGIO1$ST$SPCSO24:0 stVal √ √
43 MAIN-2 RELAY FAIL SP B206_21_1CTRL$GGIO1$ST$SPCSO20:0 stVal √
44 89L OPEN FOR STUB SP B206_21_1CTRL$GGIO1$ST$SPCSO17:0 stVal √ √
45 DIRECT TRIP RECEIVED CHANNEL-1 SP B206_21_1CTRL$GGIO1$ST$SPCSO16:0 stVal √ √
46 LBB OPERATED SP B206_21_1CTRL$GGIO1$ST$SPCSO10:0 stVal √ √
47 TIME SYNCHRONISATION ERROR SP B206_21_1EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
48 VT FUSE FAILURE SP B206_21_1EXT$pdGGIO3$ST$SPCSO42:0 stVal √ √
49 BROKEN CONDUCTOR SP B206_21_1EXT$pdGGIO4$ST$SPCSO3:0 stVal √ √
50 EMERGENCY/MANUAL CLOSE SP B206_21_1EXT$pdGGIO6$ST$SPCSO36:0 stVal √
51 CARRIER RECEIVED CHANNEL-1 SP B206_21_1EXT$pdGGIO63$ST$SPCSO38:0 stVal √ √
52 CARRIER RECEIVED CHANNEL-2 SP B206_21_1EXT$pdGGIO63$ST$SPCSO42:0 stVal √ √
53 CARRIER FAULTY SP B206_21_1EXT$pdGGIO63$ST$SPCSO37:0 stVal √ √ NOT REQUIRED
54 SOTF PICKUP SP B206_21_1EXT$pdGGIO67$ST$SPCSO57:0 stVal √
55 SOTF TRIP( OC)
56 SOTF TRIP( IMPEDANCE Z1B) SP B206_21_1EXT$pdGGIO68$ST$SPCSO7:0 stVal √ √
57 CARRIER SEND CHANNEL-1 SP B206_21_1PROT$PSCH1$ST$ProTx stVal √ √
58 CARRIER SEND CHANNEL-2 GOOSE
59 DIRECT TRIP RECEIVED CHANNEL-2 GOOSE
60 CARRIER RECEIVED SP B206_21_1PROT$PSCH1$ST$ProRx stVal √ √ NOT REQUIRED
61 CARRIER ADDIED TRIP/Z COM. TRIP SP B206_21_1PROT$PSCH1$ST$Op general √ √
62 MAIN A/R OPTD
63 TIE A/R OPTD
64 CB MANUAL CLOSE
65 CB MANUAL TRIP
66 86 GROUP-A OPTD
67 86 GROUP-B OPTD
68 MAIN A/R START
69 TIE A/R START
70 DISTANCE ZONE-1 PICKUP SP B206_21_1PROT$PDIS1$ST$Str general √
71 DISTANCE PROTN ZONE-1 TRIP SP B206_21_1PROT$PDIS1$ST$Op general √ √
72 DISTANCE PROTN ZONE-1 R-PH TRIP SP B206_21_1PROT$PDIS1$ST$Op phsA √ √
73 DISTANCE PROTN ZONE-1 Y-PH TRIP SP B206_21_1PROT$PDIS1$ST$Op phsB √ √
74 DISTANCE PROTN ZONE-1 B-PH TRIP SP B206_21_1PROT$PDIS1$ST$Op phsC √ √
75 DISTANCE ZONE-2 PICKUP SP B206_21_1PROT$PDIS2$ST$Str general √
76 DISTANCE PROTN ZONE-2 TRIP SP B206_21_1PROT$PDIS2$ST$Op general √ √
77 DISTANCE PROTN ZONE-2 R-PH TRIP SP B206_21_1PROT$PDIS2$ST$Op phsA √ √
78 DISTANCE PROTN ZONE-2 Y-PH TRIP SP B206_21_1PROT$PDIS2$ST$Op phsB √ √
79 DISTANCE PROTN ZONE-2 B-PH TRIP SP B206_21_1PROT$PDIS2$ST$Op phsC √ √
80 DISTANCE ZONE-3 PICKUP SP B206_21_1PROT$PDIS3$ST$Str general √
81 DISTANCE PROTN ZONE-3 TRIP SP B206_21_1PROT$PDIS3$ST$Op general √ √
82 DISTANCE ZONE-4 PICKUP SP B206_21_1PROT$PDIS4$ST$Str general √
83 DISTANCE PROTN ZONE-4 TRIP SP B206_21_1PROT$PDIS4$ST$Op general √ √
84 DISTANCE PROTN ZONE-4 R-PH TRIP
85 DISTANCE PROTN ZONE-4 Y-PH TRIP
86 DISTANCE PROTN ZONE-4 B-PH TRIP
87 DISTANCE PROTN ZONE-1B PICKUP SP B206_21_1PROT$PDIS10$ST$Str general √
88 DISTANCE PROTN ZONE-1B TRIP SP B206_21_1PROT$PDIS10$ST$Op general √ √
89 DISTANCE PROTN ZONE-1B B-PH TRIP SP B206_21_1PROT$PDIS10$ST$Op phsC √ √
90 DISTANCE PROTN ZONE-1B R-PH TRIP SP B206_21_1PROT$PDIS10$ST$Op phsA √ √
91 DISTANCE PROTN ZONE-1B Y-PH TRIP SP B206_21_1PROT$PDIS10$ST$Op phsB √ √
92 DISTANCE PROTN ZONE-5 PICKUP
93 STUB PICKUP SP B206_21_1PROT$PTOC4$ST$Str general √
94 STUB OPERATED SP B206_21_1PROT$PTOC4$ST$Op general √ √
95 DEF FAULT PICKUP SP B206_21_1PROT$PTOC8$ST$Str general √
96 DEF FAULT TRIP SP B206_21_1PROT$PTOC8$ST$Op general √ √
97 OVERVOLTAGE STAGE-1-PH-N PICKUP SP B206_21_1PROT$PTOV1$ST$Str general √
98 OVERVOLTAGE STAGE-1 -PH-N TRIP SP B206_21_1PROT$PTOV1$ST$Op general √ √
99 OVERVOLTAGE STAGE-2-PH-N PICKUP SP B206_21_1PROT$PTOV2$ST$Str general √
100 OVERVOLTAGE STAGE-2-PH-N TRIP SP B206_21_1PROT$PTOV2$ST$Op general √ √
101 OVERVOLTAGE STAGE-1-PH-PH PICKUP SP B206_21_1PROT$PTOV3$ST$Str general √
102 OVERVOLTAGE STAGE-1-PH-PH TRIP SP B206_21_1PROT$PTOV3$ST$Op general √ √
103 OVERVOLTAGE STAGE-2-PH-PH PICKUP SP B206_21_1PROT$PTOV4$ST$Str general √
104 OVERVOLTAGE STAGE-2-PH-PH TRIP SP B206_21_1PROT$PTOV4$ST$Op general √ √
105 POWER SWING ZONE-1 DETECTED SP B206_21_1PROT$RPSB1$ST$Str general √ √
106 POWER SWING ZONE-1 BLOCK SP B206_21_1PROT$RPSB1$ST$BlkZn stVal √
107 POWER SWING ZONE-1B DETECTED SP B206_21_1PROT$RPSB10$ST$Str general √ √
108 POWER SWING ZONE-1B BLOCK SP B206_21_1PROT$RPSB10$ST$BlkZn stVal √
109 POWER SWING ZONE-2 DETECTED SP B206_21_1PROT$RPSB2$ST$Str general √ √
110 POWER SWING ZONE-2 BLOCK SP B206_21_1PROT$RPSB2$ST$BlkZn stVal √
111 POWER SWING ZONE-3 DETECTED SP B206_21_1PROT$RPSB3$ST$Str general √ √
112 POWER SWING ZONE-3 BLOCK SP B206_21_1PROT$RPSB3$ST$BlkZn stVal √
113 POWER SWING ZONE-4 DETECTED SP B206_21_1PROT$RPSB4$ST$Str general √ √
114 POWER SWING ZONE-4 BLOCK SP B206_21_1PROT$RPSB4$ST$BlkZn stVal √
115 BUSBAR PROTN OPTD
116 RELAY LED RESET SC
117 MAIN BCU FAIL
118 TIE BCU FAIL
119 MANUAL DR TRIGGER SC
120 GENERAL TRIP SP B206_21_1PROT$PTRC1$ST$Tr general √ √
121 DEVICE HEALTHY SP B707_21_1PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
122 MAIN-2 PROTN OPTD
123 STUB BLOCKED SP B206_21_1PROT$PTOC4$ST$Blk stVal √ √
124 SETTINGS CHANGED
125 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Feeder Name NAME ( 200 MCU )
SIGNAL DESCRIPTION Information type Telegram address Position EVENT ALARM
BINARY INPUT (Single Point)
1 200KV 200KV MCU GENERAL TRIP R-PH SP BBP_220KV_MCUPROT$PTRC1$ST$Tr phsA √ √
2 GENERAL TRIP Y-PH SP BBP_220KV_MCUPROT$PTRC1$ST$Tr phsB √ √
3 GENERAL TRIP B-PH SP BBP_220KV_MCUPROT$PTRC1$ST$Tr phsC √ √
4 TRIP COMMAND BUS-BUS-3 B-PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO23:0 stVal √ √
5 TRIP COMMAND BUS-BUS-3 Y-PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO22:0 stVal √ √
6 TRIP COMMAND BUS-BUS-3 R-PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO21:0 stVal √ √
7 TRIP COMMAND BUS-2 B- PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO13:0 stVal √ √
8 TRIP COMMAND BUS-2 Y- PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO12:0 stVal √ √
9 TRIP COMMAND BUS-2 R- PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO11:0 stVal √ √
10 TRIP COMMAND BUS-1 B- PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO3:0 stVal √ √
11 TRIP COMMAND BUS-1 Y- PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO2:0 stVal √ √
12 TRIP COMMAND BUS-1 R- PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO1:0 stVal √ √
13 BREAKER FAILURE OPERATED BUS-3 B-PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO26:0 stVal √ √
14 BREAKER FAILURE OPERATED BUS-3 Y-PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO25:0 stVal √ √
15 BREAKER FAILURE OPERATED BUS-3 R-PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO24:0 stVal √ √
16 BREAKER FAILURE OPERATED BUS-2 B-PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO16:0 stVal √ √
17 BREAKER FAILURE OPERATED BUS-2 Y-PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO15:0 stVal √ √
18 BREAKER FAILURE OPERATED BUS-2 R-PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO14:0 stVal √ √
19 BREAKER FAILURE OPERATED BUS-1 B-PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO6:0 stVal √ √
20 BREAKER FAILURE OPERATED BUS-1 Y-PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO5:0 stVal √ √
21 BREAKER FAILURE OPERATED BUS-1 R-PH SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO4:0 stVal √ √
22 BUS-3 BUS CT SUPERVISION ALARM SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO30:0 stVal √ √
23 BUS-2 CT SUPERVISION ALARM SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO20:0 stVal √ √
24 BUS-1 CT SUPERVISION ALARM SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO10:0 stVal √ √
25 BLOCKED TRIP COMMAND BUS-3 (BUS-3) SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO28:0 stVal √ √
26 BLOCKED TRIP COMMAND BUS-2 SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO18:0 stVal √ √
27 BLOCKED TRIP COMMAND BUS-1 SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO8:0 stVal √ √
28 BLOCKED BY BUS-3 SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO27:0 stVal √ √
29 BLOCKED BY BUS-2 SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO17:0 stVal √ √
30 BLOCKED BY BUS-1 SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO7:0 stVal √ √
31 BUS-3 PROTECTION BLOCKED BY HANDLE SP BBP_220KV_MCUPROT$GGIO1$ST$SPCSO33:0 stVal √ √
32 BUS-1 PROTECTION BLOCKED BY HANDLE SP BBP_220KV_MCUPROT$GGIO1$ST$SPCSO32:0 stVal √ √
33 BUS-2 PROTECTION BLOCKED BY HANDLE SP BBP_220KV_MCUPROT$GGIO1$ST$SPCSO31:0 stVal √ √
34 BLOCKED BREAKER FAILURE PROTECTION BUS-3 SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO29:0 stVal √ √
35 BLOCKED BREAKER FAILURE PROTECTION BUS-2 SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO19:0 stVal √ √
36 BLOCKED BREAKER FAILURE PROTECTION BUS-1 SP BBP_220KV_MCUPROT$GGIO4$ST$SPCSO9:0 stVal √ √
37 BUS-3 BUS TRIP SP BBP_220KV_MCUPROT$GGIO3$ST$SPCSO14:0 stVal √ √
38 BUSBAR TRIP SP BBP_220KV_MCUPROT$PDIF1$ST$Op stVal √ √
39 BUS ZONE 1 TRIP SP BBP_220KV_MCUPROT$GGIO3$ST$SPCSO13:0 stVal √ √
40 BUS ZONE 2 TRIP SP BBP_220KV_MCUPROT$GGIO3$ST$SPCSO12:0 stVal √ √
41 BLOCKED BREAKER FAILURE PROTECTION BUS-3 SP BBP_220KV_MCUPROT$GGIO3$ST$SPCSO17:0 stVal √ √
42 BLOCKED BREAKER FAILURE PROTECTION BUS-2 SP BBP_220KV_MCUPROT$GGIO3$ST$SPCSO16:0 stVal √ √
43 BLOCKED BREAKER FAILURE PROTECTION BUS-1 SP BBP_220KV_MCUPROT$GGIO3$ST$SPCSO15:0 stVal √ √
44 B213- BAY UNIT OUT OF SERVICE SP BBP_220KV_MCUPROT$GGIO3$ST$SPCSO7:0 stVal √ √
45 B213- BAY UNIT FAILURE SP BBP_220KV_MCUPROT$GGIO3$ST$SPCSO1:0 stVal √ √
46 B212- BAY UNIT OUT OF SERVICE SP BBP_220KV_MCUPROT$GGIO2$ST$SPCSO57:0 stVal √ √
47 B212- BAY UNIT FAILURE SP BBP_220KV_MCUPROT$GGIO2$ST$SPCSO51:0 stVal √ √
48 B211- BAY UNIT OUT OF SERVICE SP BBP_220KV_MCUPROT$GGIO2$ST$SPCSO47:0 stVal √ √
49 B211- BAY UNIT FAILURE SP BBP_220KV_MCUPROT$GGIO2$ST$SPCSO41:0 stVal √ √
50 B210- BAY UNIT OUT OF SERVICE SP BBP_220KV_MCUPROT$GGIO2$ST$SPCSO37:0 stVal √ √
51 B210- BAY UNIT FAILURE SP BBP_220KV_MCUPROT$GGIO2$ST$SPCSO31:0 stVal √ √
52 B209- BAY UNIT OUT OF SERVICE SP BBP_220KV_MCUPROT$GGIO2$ST$SPCSO27:0 stVal √ √
53 B209- BAY UNIT FAILURE SP BBP_220KV_MCUPROT$GGIO2$ST$SPCSO21:0 stVal √ √
54 B208- BAY UNIT OUT OF SERVICE SP BBP_220KV_MCUPROT$GGIO2$ST$SPCSO17:0 stVal √ √
55 B208- BAY UNIT FAILURE SP BBP_220KV_MCUPROT$GGIO2$ST$SPCSO11:0 stVal √ √
56 B207- BAY UNIT OUT OF SERVICE SP BBP_220KV_MCUPROT$GGIO2$ST$SPCSO7:0 stVal √ √
57 B207- BAY UNIT FAILURE SP BBP_220KV_MCUPROT$GGIO2$ST$SPCSO1:0 stVal √ √
58 B206- BAY UNIT OUT OF SERVICE SP BBP_220KV_MCUPROT$GGIO1$ST$SPCSO57:0 stVal √ √
59 B206- BAY UNIT FAILURE SP BBP_220KV_MCUPROT$GGIO1$ST$SPCSO51:0 stVal √ √
60 B205- BAY UNIT OUT OF SERVICE SP BBP_220KV_MCUPROT$GGIO1$ST$SPCSO47:0 stVal √ √
61 B205- BAY UNIT FAILURE SP BBP_220KV_MCUPROT$GGIO1$ST$SPCSO41:0 stVal √ √
62 B204- BAY UNIT OUT OF SERVICE SP BBP_220KV_MCUPROT$GGIO1$ST$SPCSO37:0 stVal √ √
63 B204- BAY UNIT FAILURE SP BBP_220KV_MCUPROT$GGIO1$ST$SPCSO31:0 stVal √ √
64 B203- BAY UNIT OUT OF SERVICE SP BBP_220KV_MCUPROT$GGIO1$ST$SPCSO27:0 stVal √ √
65 B203- BAY UNIT FAILURE SP BBP_220KV_MCUPROT$GGIO1$ST$SPCSO21:0 stVal √ √
66 B202- BAY UNIT OUT OF SERVICE SP BBP_220KV_MCUPROT$GGIO1$ST$SPCSO17:0 stVal √ √
67 B202- BAY UNIT FAILURE SP BBP_220KV_MCUPROT$GGIO1$ST$SPCSO11:0 stVal √ √
68 B201- BAY UNIT OUT OF SERVICE SP BBP_220KV_MCUPROT$GGIO1$ST$SPCSO7:0 stVal √ √
69 B201- BAY UNIT FAILURE SP BBP_220KV_MCUPROT$GGIO1$ST$SPCSO1:0 stVal √ √
70 TIME SYNCHRONISATION ERROR SP BBP_220KV_MCUEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
71 BAY UNIT FAILURE GROUP ALARM SP BBP_220KV_MCUEXT$pdGGIO164$ST$SPCSO23:0 stVal √ √
72 BAY OUT OF SERVICE GROUP ALARM SP BBP_220KV_MCUEXT$pdGGIO164$ST$SPCSO21:0 stVal √ √
73 BUS-3 BUS SWITCH OUT SP BBP_220KV_MCUCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
74 DC SOURCE-2 FAIL SP BBP_220KV_MCUCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
75 DC SOURCE-1 FAIL SP BBP_220KV_MCUCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
76 BUS-2 SWITCH OUT SP BBP_220KV_MCUCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
77 BUS-1 SWITCH OUT SP BBP_220KV_MCUCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
78 LED RESET SP BBP_220KV_MCUCTRL$LLN0$ST$LEDRs:2 stVal √
79 Busbar-1 Zone OPERATED SP BBP_220KV_MCUPROT$GGIO3$SPCSO12 stVal √ √
80 Busbar-2 Zone OPERATED SP BBP_220KV_MCUPROT$GGIO3$SPCSO13 stVal √ √
81 BUS-3 BUSBAR ZONE OPERATED SP BBP_220KV_MCUPROT$GGIO3$SPCSO14 stVal √ √
82 BUS-1 BLOCK DUE TO INDERM STATE SP BBP_220KV_MCUCTRL$GGIO1$SPCSO9 stVal √ √
83 BUS-1 BLOCK DUE TO COMMUNICATION FAIL SP BBP_220KV_MCUCTRL$GGIO1$SPCSO10 stVal √ √
84 BUS-2 BLOCK DUE TO INDERM STATE SP BBP_220KV_MCUCTRL$GGIO1$SPCSO11 stVal √ √
85 BUS-2 BLOCK DUE TO COMMUNICATION FAIL SP BBP_220KV_MCUCTRL$GGIO1$SPCSO12 stVal √ √
86 BUS-3 BLOCK DUE TO INDERM STATE SP BBP_220KV_MCUCTRL$GGIO1$SPCSO13 stVal √ √
87 BUS-3 BLOCK DUE TO COMMUNICATION FAIL SP BBP_220KV_MCUCTRL$GGIO1$SPCSO14 stVal √ √
88 LBB TRIP SP BBP_220KV_MCUPROT$RBRF1$OpEx stVal √ √
89 LBB RETRIP SP BBP_220KV_MCUPROT$RBRF1$OpIn stVal √ √
90 GOOSE RECEIPT FAIL/TROUBLE SP BBP_220KV_MCUCTRL$GGIO1$SPCSO15 stVal √ √
71 BUSBAR CHECKZONE ALARM
72 BUSBAR CHECKZONE TRIP
73 BREAKER FAILURE - BUSBAR 1 BLOCKED
74 BREAKER FAILURE - BUSBAR 2 BLOCKED
75 ISOLATOR IN INTERMEDIATE STATUS
77 BUSBAR BLOCKED DUE TO COMMUNICATION ERROR_Bay_n
78 BAY_N_BREAKER FAILURE R-PH INITIATION
79 BAY_N_BREAKER FAILURE Y-PH INITIATION
80 BAY_N_BREAKER FAILURE B-PH INITIATION
81 BAY_N_BREAKER FAILURE 3PH INITIATION
82 BAY_N_EXTERNAL BUSBAR ZONE n
83 BAY_N_BREAKER FAILURE RETRIP
84 BAY_N_BREAKER FAILURE BACKTRIP
85 BAY_N_BREAKER FAILURE RPH- RETRIP
86 BAY_N_BREAKER FAILURE YPH- RETRIP
87 BAY_N_BREAKER FAILURE BPH- RETRIP
88 BBP CENTRAL UNIT IED UNHEALTHY
89 SETTING CHANGE
90 BUS ZONE MERGE/BUS INTERCONNECT ALARM
91 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Feeder Name NAME ( BAY-207 TBC )
SIGNAL DESCRIPTION Information type Telegram address Position EVENT ALARM
BINARY INPUT (Double Point)
1 200KV 200KV TBC 89A POSITION DP B209_BCU89A$CSWI1$ST$Pos:2 stVal √
2 89AE POSITION DP B209_BCU89AE$CSWI1$ST$Pos:2 stVal √
3 89B POSITION DP B209_BCU89B$CSWI1$ST$Pos:2 stVal √
4 89C POSITION DP B209_BCU89C$CSWI1$ST$Pos:2 stVal √
5 89C POSITION DP B209_BCU89C$CSWI1$ST$Pos:2 stVal √
6 89CE1 POSITION DP B209_BCU89CE1$CSWI1$ST$Pos:2 stVal √
7 89CE2 POSITION DP B209_BCU89CE2$CSWI1$ST$Pos:2 stVal √
8 CB B-PH POSITION DP B209_BCUCB_1P_POSITION$RSLEDGAPC1$ST$DPS2 stVal √
9 CB R-PH POSITION DP B209_BCUCB_1P_POSITION$RSLEDGAPC1$ST$DPS stVal √
10 CB Y-PH POSITION DP B209_BCUCB_1P_POSITION$RSLEDGAPC1$ST$DPS1 stVal √
11 CB POSITION DP B209_BCUCB$CSWI1$ST$Pos:2 stVal √
13 BINARY INPUT (Single Point)
15 LED RESET SP B209_BCUApplication$LLN0$ST$LEDRs:2 stVal √
16 BCU MODE SP B209_BCUApplication$LLN0$ST$LocKey stVal √
17 86A TRIP RELAY RESET SP B209_BCUUD1$RSLEDGAPC1$ST$SPC:2 stVal √ √
18 86A TRIP RELAY SUPERVISION SP B209_BCUUD1$RSLEDGAPC1$ST$SPS12 stVal √ √
19 86A TRIP RELAY OPERATED SP B209_BCUUD1$RSLEDGAPC1$ST$SPS11 stVal √ √
20 86B TRIP RELAY RESET SP B209_BCUUD1$RSLEDGAPC1$ST$SPC1:2 stVal √ √
21 86B TRIP RELAY SUPERVISION SP B209_BCUUD1$RSLEDGAPC1$ST$SPS24 stVal √ √
22 86B TRIP RELAY OPERATED SP B209_BCUUD1$RSLEDGAPC1$ST$SPS23 stVal √ √
23 87B TRIP RELAY SUPERVISION SP B209_BCUUD1$RSLEDGAPC1$ST$SPS14 stVal √ √
24 AC KIOSK HEAT FIRE DETECTED SP B209_BCUUD1$RSLEDGAPC1$ST$SPS19 stVal √ √
25 AC KIOSK SMOKE DETECTED SP B209_BCUUD1$RSLEDGAPC1$ST$SPS18 stVal √ √
26 CB AC SUPPLY FAIL SP B209_BCUUD1$RSLEDGAPC1$ST$SPS9 stVal √ √
27 AC SUPPLY-1 ON SP B209_BCUUD1$RSLEDGAPC1$ST$SPS20 stVal √ √
28 AC SUPPLY-1/2 FAIL SP B209_BCUUD1$RSLEDGAPC1$ST$SPS22 stVal √ √
29 AC SUPPLY-2 ON SP B209_BCUUD1$RSLEDGAPC1$ST$SPS21 stVal √ √
30 NORMAL MODE SP B209_BCUUD1$RSLEDGAPC1$ST$SPS26 stVal √ √
31 TRANSFER MODE SP B209_BCUUD1$RSLEDGAPC1$ST$SPS25 stVal √
32 BUS-1 VT RESET SP B209_BCUUD1$RSLEDGAPC1$ST$SPS35 stVal √ √
33 BUS-1 VT SELECTED SP B209_BCUUD1$RSLEDGAPC1$ST$SPS34 stVal √ √
34 BUS-2 VT RESET SP B209_BCUUD1$RSLEDGAPC1$ST$SPS28 stVal √ √
35 BUS-2 VT SELECTED SP B209_BCUUD1$RSLEDGAPC1$ST$SPS27 stVal √ √
36 CB DC SUPPLY-1 FAIL SP B209_BCUUD1$RSLEDGAPC1$ST$SPS5 stVal √ √
37 CB DC SUPPLY-2 FAIL SP B209_BCUUD1$RSLEDGAPC1$ST$SPS6 stVal √ √
38 CB LOCAL SP B209_BCUUD1$RSLEDGAPC1$ST$SPS7 stVal √ √
39 EMERGENCY/MANUAL CLOSE SP B209_BCUUD1$RSLEDGAPC1$ST$SPS16 stVal √ √
40 EMERGENCY/MANUAL TRIP SP B209_BCUUD1$RSLEDGAPC1$ST$SPS15 stVal √ √
41 CB POLE DISCREPANCY OPERATED SP B209_BCUUD1$RSLEDGAPC1$ST$SPS1 stVal √ √
42 CB REMOTE POSITION SELECTED SP B209_BCUUD1$RSLEDGAPC1$ST$SPS8 stVal √ √
43 CB SF6 LOCKOUT SP B209_BCUUD1$RSLEDGAPC1$ST$SPS3 stVal √ √
44 CB SF6 LOW ALARM SP B209_BCUUD1$RSLEDGAPC1$ST$SPS2 stVal √
45 CB SPRING CHARGE STATUS SP B209_BCUUD1$RSLEDGAPC1$ST$SPS stVal √
46 DC SUPPLY-1 FAIL SP B209_BCUUD1$RSLEDGAPC1$ST$SPS13 stVal √
47 CB TC-1 R-PHASE FAULTY √ √
48 CB TC-1 Y-PHASE FAULTY √ √
49 CB TC-1 B-PHASE FAULTY √ √
50 CB TC-2 R-PHASE FAULTY √ √
51 CB TC-2 Y-PHASE FAULTY √ √
52 CB TC-2 B-PHASE FAULTY √ √
53 TRANSFER RESET SP B209_BCUUD1$RSLEDGAPC1$ST$SPS33 stVal √
54 TRANSFER SELECTED SP B209_BCUUD1$RSLEDGAPC1$ST$SPS32 stVal √
55 TIME SYNCHRONISATION ERROR SP B706_BCUApplication$LMTS0$ST$TmSynErr stVal √ √
56 GOOSE RECEIPT FAIL/TROUBLE SP B209_BCUUD1$RSLEDGAPC1$ST$SPS35 stVal √
60 POWER FACTOR ME_FL B209_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotPF:1 mag$f
61 FREQUENCY ME_FL B209_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$Hz:1 mag$f
62 ACTIVE POWER ME_FL B209_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotW:1 mag$f
63 REACTIVE POWER ME_FL B209_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVAr:1 mag$f
64 APPARENT POWER ME_FL B209_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVA:1 mag$f
65 I-R -PH CURRENT ME_FL B209_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsA$cVal$mag$f
66 I-Y -PH CURRENT ME_FL B209_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsB$cVal$mag$f
67 I-B -PH CURRENT ME_FL B209_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsC$cVal$mag$f
68 R-Y VOLTAGE ME_FL B209_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsAB$cVal$mag$f
69 Y-B VOLTAGE ME_FL B209_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsBC$cVal$mag$f
70 B-R VOLYAGE ME_FL B209_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsCA$cVal$mag$f
72 CB-B PH COUNTER ME_I B209_BCUUD3$RSLEDGAPC1$ST$INS2 stVal √
73 CB-R PH COUNTER ME_I B209_BCUUD3$RSLEDGAPC1$ST$INS stVal √
74 CB-Y PH COUNTER ME_I B209_BCUUD3$RSLEDGAPC1$ST$INS1 stVal √
78 89A CONTROL DC B209_BCU89A$CSWI1$CO$Pos:8 Oper$ctlVal √
79 89AE CONTROL DC B209_BCU89AE$CSWI1$CO$Pos:8 Oper$ctlVal √ √
80 89B CONTROL DC B209_BCU89B$CSWI1$CO$Pos:8 Oper$ctlVal √
81 89C CONTROL DC B209_BCU89C$CSWI1$CO$Pos:8 Oper$ctlVal √
82 89C CONTROL DC B209_BCU89C$CSWI1$CO$Pos:8 Oper$ctlVal √ √
83 89CE1 CONTROL DC B209_BCU89CE1$CSWI1$CO$Pos:8 Oper$ctlVal √
84 89CE2 CONTROL DC B209_BCU89CE2$CSWI1$CO$Pos:8 Oper$ctlVal √
85 CB CONTROL DC B209_BCUCB$CSWI1$CO$Pos:8 Oper$ctlVal √
86 TRANSFER/NORMAL CONTROL DC B209_BCUDc8$CSWI1$CO$Pos:8 Oper$ctlVal √
87 86A TRIP RELAY RESET COMMAND SC B209_BCUUD1$RSLEDGAPC1$CO$SPC:8 Oper$ctlVal √
88 86B TRIP RELAY RESET COMMAND SC B209_BCUUD1$RSLEDGAPC1$CO$SPC1:8 Oper$ctlVal √
89 CB MANUAL TRIP
90 CB MANUAL CLOSE
91 BUSBAR OPERATED
92 BCU IN LOCAL/REMOTE
93 SETTINGS CHANGED √
94 RELAY IN TEST MODE √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sheet Ref. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 6MD66 BCU BCU FOR BUS REACTOR STNM4XXBCU BCU is for each bay so 4XX refers to Bay
2 7SA522 BR 21R BACKUP IMPEDANCE RELAY FOR BUS REACTOR STNM4XXBRBU Bay No. 4XX will be always the main bay number for the BUS REACTOR feeder. BR for BUS REACTOR and LR for LINE REACTOR.
3 7SJ80 BR 64.2R REF RELAY FOR BUS REACTOR STNM4XXBRREF Bay No. 4XX will be always the main bay number for the BUS REACTOR feeder. BR for BUS REACTOR and LR for LINE REACTOR.
4 7UT BR 87R DIFFERENTIAL RELAY FOR BUS REACTOR STNM4XXBRDIF Bay No. 4XX will be always the main bay number for the BUS REACTOR feeder. BR for BUS REACTOR and LR for LINE REACTOR.
NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "4XX" stand for Bay name, example if the bay no 401 then same has to be implemented like STNM401BCU
400kV BUS REACTOR (BCU)
Sr. No. Voltage Level Feeder Name Source NAME ( BAY-403 BUS REACTOR )
Signal Decription INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Double Point)
1 400kV 400kV BUS REACTOR BCU CB R-PH POSITION DP B403_BCUCBB$XCBR1$ST$Pos:2 stVal √
2 CB Y-PH POSITION DP B403_BCUCBR$XCBR1$ST$Pos:2 stVal √
3 CB B-PH POSITION DP B403_BCUCBY$XCBR1$ST$Pos:2 stVal √
4 CB POSITION DP B403_BCUCB$CSWI1$ST$Pos:2 stVal √
5 89AE POSITION DP B403_BCU89AE$CSWI3$ST$Pos:2 stVal √
6 89AE2 POSITION DP B403_BCU89AE2$CSWI6$ST$Pos:2 stVal √
7 89BE1 POSITION DP B403_BCU89BE1$CSWI5$ST$Pos:2 stVal √
8 89BE POSITION DP B403_BCU89BE$CSWI7$ST$Pos:2 stVal √
9 89RE-B POSITION DP B403_BCU89REB$CSWI9$ST$Pos:2 stVal √
10 89RE POSITION DP B403_BCU89RE$CSWI9$ST$Pos:2 stVal √
11 89RE-Y POSITION DP B403_BCU89REY$CSWI9$ST$Pos:2 stVal √
12 89A POSITION DP B403_BCU89A$CSWI2$ST$Pos:2 stVal √
13 89B POSITION DP B403_BCU89B$CSWI4$ST$Pos:2 stVal √
14 89R-B POSITION DP B403_BCU89RB$CSWI8$ST$Pos:2 stVal √
15 89R POSITION DP B403_BCU89R$CSWI8$ST$Pos:2 stVal √
16 89R-Y POSITION DP B403_BCU89RY$CSWI8$ST$Pos:2 stVal √
19 BINARY INPUT (Single Point)
21 AUX POWER FAIL SP B403_BCUApplication$LPHD0$ST$AuxPwrFail stVal √ √
22 TIME SYNCHRONISATION ERROR SP B403_BCUApplication$LMTS0$ST$TmSynErr stVal √ √
23 BCU MODE SP B403_BCUApplication$LLN0$ST$LocKey stVal √ √
24 CB SF6 GAS PRESSURE REFILL LOW ALARM SP B403_BCUApplication$USER1$ST$SPS stVal √ √
25 CB SF6 GAS PRESSURE LOCKOUT SP B403_BCUApplication$USER1$ST$SPS1 stVal √ √
26 89A POLE DESCREPENCY SP B403_BCUApplication$USER3$ST$SPS3 stVal √ √
27 89B POLE DESCREPENCY SP B403_BCUApplication$USER3$ST$SPS4 stVal √ √
28 CB DC SUPPLY-1/2 FAIL SP B403_BCUApplication$USER3$ST$SPS1 stVal √
29 CB SPRING CHARGED SP B403_BCUApplication$USER3$ST$SPS2 stVal √
30 CB SF6 GAS PRESSURE LOCKOUT SP B403_BCUApplication$USER3$ST$SPS stVal √ √
31 EMERGENCY/MANUAL CB TRIP SP B403_BCUApplication$USER6$ST$SPS stVal √ √
32 PSD DEVICE HEALTHY SP B403_BCUApplication$USER6$ST$SPS19 stVal √
33 PSD DEVICE IN SERVICE SP B403_BCUApplication$USER6$ST$SPS20 stVal √
34 WTI ALARM SP B403_BCUApplication$USER6$ST$SPS23 stVal √ √
35 OTI ALARM SP B403_BCUApplication$USER6$ST$SPS24 stVal √ √
36 PSD ALARM SP B403_BCUApplication$USER6$ST$SPS21 stVal √ √
37 PSD SYNCH DATA ERROR SP B403_BCUApplication$USER6$ST$SPS22 stVal √ √
38 SURGE ARRESTER B-PH SP B403_BCUApplication$USER6$ST$SPS18 stVal √
39 SURGE ARRESTER R-PH SP B403_BCUApplication$USER6$ST$SPS16 stVal √
40 SURGE ARRESTER Y-PH SP B403_BCUApplication$USER6$ST$SPS17 stVal √
41 86A TRIP RELAY SUPERVISION SP B403_BCUApplication$USER5$ST$SPS2 stVal √ √
42 86A TRIP RELAY OPERATED SP B403_BCUApplication$USER5$ST$SPS1 stVal √ √
43 86B TRIP RELAY SUPERVISION SP B403_BCUApplication$USER5$ST$SPS5 stVal √ √
44 86B TRIP RELAY OPERATED SP B403_BCUApplication$USER5$ST$SPS4 stVal √ √
45 CB TC-1 FAULTY SP B403_BCUApplication$USER5$ST$SPS stVal √ √
46 CB TC-2 FAULTY SP B403_BCUApplication$USER5$ST$SPS3 stVal √ √
47 CB POLE DISCREPANCY SP B403_BCUApplication$USER2$ST$SPS1 stVal √ √
48 CB SF6 GAS PRESSURE REFILL LOW ALARM SP B403_BCUApplication$USER2$ST$SPS stVal √ √
49 BUS-1 VT RESET SP B403_BCUApplication$USER7$ST$SPS1 stVal √
50 BUS-2 VT RESET SP B403_BCUApplication$USER7$ST$SPS3 stVal √
51 LINE VT RESET SP B403_BCUApplication$USER7$ST$SPS5 stVal √
52 BUS-1 VT SELECTED SP B403_BCUApplication$USER7$ST$SPS stVal √
53 BUS-2 VT SELECTED SP B403_BCUApplication$USER7$ST$SPS2 stVal √
54 ICT LV VT SELECTED SP B403_BCUApplication$USER7$ST$SPS4 stVal √
55 CB READY SP B403_BCUCB$XCBR1$ST$Rdy stVal √
56 CB POSITION NO SYNC SP B403_BCUCB$CSWI1$ST$Pos noSync √
57 GAS PRESSURE LOW ALARM-1 GC401-1 Y-PH SP B403_BCUApplication$USER5$ST$SPS10 stVal √ √
58 GAS PRESSURE LOW ALARM -1 GC401-1 B-PH SP B403_BCUApplication$USER5$ST$SPS11 stVal √ √
59 GAS PRESSURE LOW ALARM-1 GC401-2 R-PH SP B403_BCUApplication$USER5$ST$SPS12 stVal √ √
60 GAS PRESSURE LOW ALARM -1 GC401-2 Y-PH SP B403_BCUApplication$USER5$ST$SPS13 stVal √ √
61 400kV 400kV BUS REACTOR BCU GAS PRESSURE LOW ALARM-1 GC401-2 B-PH SP B403_BCUApplication$USER5$ST$SPS14 stVal √ √
62 GAS PRESSURE LOW ALARM-1 GC401-3 R-PH SP B403_BCUApplication$USER5$ST$SPS15 stVal √ √
63 GAS PRESSURE LOW ALARM -1 GC401-3 Y-PH SP B403_BCUApplication$USER5$ST$SPS16 stVal √ √
64 GAS PRESSURE LOW ALARM-1 GC401-3 B-PH SP B403_BCUApplication$USER5$ST$SPS17 stVal √ √
65 GAS PRESSURE LOW ALARM-1 GC401-4 R-PH SP B403_BCUApplication$USER5$ST$SPS18 stVal √ √
66 GAS PRESSURE LOW ALARM -1 GC401-4 Y-PH SP B403_BCUApplication$USER5$ST$SPS19 stVal √ √
67 GAS PRESSURE LOW ALARM-1 GC401-4 B-PH SP B403_BCUApplication$USER5$ST$SPS20 stVal √ √
68 GAS PRESSURE LOW ALARM-1 GC401-5 R-PH SP B403_BCUApplication$USER5$ST$SPS21 stVal √ √
69 GAS PRESSURE LOW ALARM -1 GC401-5 Y-PH SP B403_BCUApplication$USER5$ST$SPS22 stVal √ √
70 GAS PRESSURE LOW ALARM-1 GC401-5 B-PH SP B403_BCUApplication$USER5$ST$SPS23 stVal √ √
71 GAS PRESSURE LOW ALARM-1 GC401-6 R-PH SP B403_BCUApplication$USER5$ST$SPS24 stVal √ √
72 GAS PRESSURE LOW ALARM -1 GC401-6 Y-PH SP B403_BCUApplication$USER5$ST$SPS25 stVal √ √
73 GAS PRESSURE LOW ALARM-1 GC401-6 B-PH SP B403_BCUApplication$USER5$ST$SPS26 stVal √ √
74 GAS PRESSURE LOW ALARM-1 GC401-7 R-PH SP B403_BCUApplication$USER5$ST$SPS27 stVal √ √
75 GAS PRESSURE LOW ALARM -1 GC401-7 Y-PH SP B403_BCUApplication$USER5$ST$SPS28 stVal √ √
76 GAS PRESSURE LOW ALARM-1 GC401-7 B-PH SP B403_BCUApplication$USER5$ST$SPS29 stVal √ √
77 GAS PRESSURE LOW ALARM-2 GC401-1 SP B403_BCUApplication$USER5$ST$SPS30 stVal √ √
78 GAS PRESSURE LOW ALARM-2 GC401-2 SP B403_BCUApplication$USER5$ST$SPS31 stVal √ √
79 GAS PRESSURE LOW ALARM-2 GC401-3 SP B403_BCUApplication$USER5$ST$SPS32 stVal √ √
80 GAS PRESSURE LOW ALARM-2 GC401-4 SP B403_BCUApplication$USER5$ST$SPS33 stVal √ √
81 GAS PRESSURE LOW ALARM-2 GC401-5 SP B403_BCUApplication$USER5$ST$SPS34 stVal √ √
82 GAS PRESSURE LOW ALARM-2 GC401-6 SP B403_BCUApplication$USER5$ST$SPS35 stVal √ √
83 GAS PRESSURE LOW ALARM-2 GC401-7 SP B403_BCUApplication$USER5$ST$SPS36 stVal √ √
84 GAS COMPARTMENT ZONE TRIP GC401-52 SP B403_BCUApplication$USER5$ST$SPS37 stVal √ √
85 GAS COMPARTMENT ZONE TRIP GC401-1 SP B403_BCUApplication$USER5$ST$SPS38 stVal √ √
86 GAS COMPARTMENT ZONE TRIP GC401-2 SP B403_BCUApplication$USER5$ST$SPS39 stVal √ √
87 GAS COMPARTMENT ZONE TRIP GC401-3 SP B403_BCUApplication$USER5$ST$SPS40 stVal √ √
88 GAS COMPARTMENT ZONE TRIP GC401-4 SP B403_BCUApplication$USER5$ST$SPS41 stVal √ √
89 GAS COMPARTMENT ZONE TRIP GC401-5 SP B403_BCUApplication$USER5$ST$SPS42 stVal √ √
90 GAS COMPARTMENT ZONE TRIP GC401-6 SP B403_BCUApplication$USER5$ST$SPS43 stVal √ √
91 GAS COMPARTMENT ZONE TRIP GC401-7 SP B403_BCUApplication$USER5$ST$SPS44 stVal √ √
92 GAS PRESSURE LOW ALARM-1 GC401-8 R-PH SP B403_BCUApplication$USER7$ST$SPS26 stVal √ √
93 GAS PRESSURE LOW ALARM -1 GC401-8 Y-PH SP B403_BCUApplication$USER7$ST$SPS27 stVal √ √
94 GAS PRESSURE LOW ALARM-1 GC401-8 B-PH SP B403_BCUApplication$USER7$ST$SPS28 stVal √ √
95 GAS PRESSURE LOW ALARM-2 GC401-8 SP B403_BCUApplication$USER7$ST$SPS29 stVal √ √
96 DEVICE HEALTHY SP B403_BCUApplication$LPHD0$ST$PhyHealth:0 stVal:1 √
97 GOOSE RECEIPT FAIL/TROUBLE SP B403_BCUApplication$USER7$ST$SPS30 stVal √ √
98 CB CLOSE INTERLOCK SP B403_BCUCB$CILO1$ST$EnaCls stVal √
99 89AE OPEN INTERLOCK SP B403_BCU89AE$CILO3$ST$EnaOpn stVal √
100 89AE2 OPEN INTERLOCK SP B403_BCU89AE2$CILO6$ST$EnaOpn stVal √
101 89BE OPEN INTERLOCK SP B403_BCU89BE$CILO5$ST$EnaOpn stVal √
102 89BE2 OPEN INTERLOCK SP B403_BCU89BE2$CILO7$ST$EnaOpn stVal √
103 89BRE OPEN INTERLOCK SP B403_BCU89RE$CILO9$ST$EnaOpn stVal √
104 89RE-R-PH OPEN INTERLOCK SP B403_BCU89RER$CILO9$ST$EnaOpn stVal √
105 89RE-Y-PH OPEN INTERLOCK SP B403_BCU89REY$CILO9$ST$EnaOpn stVal √
106 89A OPEN INTERLOCK SP B403_BCU89A$CILO2$ST$EnaOpn stVal √
107 89B OPEN INTERLOCK SP B403_BCU89B$CILO4$ST$EnaOpn stVal √
108 89BR OPEN INTERLOCK SP B403_BCU89R$CILO8$ST$EnaOpn stVal √
109 89R-R-PH OPEN INTERLOCK SP B403_BCU89RR$CILO8$ST$EnaOpn stVal √
110 89R-Y-PH OPEN INTERLOCK SP B403_BCU89RY$CILO8$ST$EnaOpn stVal √
111 DC -1/2 SUPPLY HEALTHY
112 89BR POLE DISCREPANCY ALARM
113 CT SF6 ALARM
114 CT SF6 LOCKOUT
115 PSD IN POSITION
116 PSD OUT POSITION
117 PSD OPENING PROBLEM
118 PSD CLOSING PROBLEM
121 MEASUREMENT
123 POWER FACTOR ME_FL B403_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotPF:1 mag$f
124 FREQUENCY ME_FL B403_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$Hz:1 mag$f
125 ACTIVE POWER ME_FL B403_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotW:1 mag$f
126 REACTIVE POWER ME_FL B403_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVAr:1 mag$f
127 APPARENT POWER ME_FL B403_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVA:1 mag$f
128 I-R-PH CURRENT ME_FL B403_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsA$cVal$mag$f
129 I-Y-PH CURRENT ME_FL B403_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsB$cVal$mag$f
130 I-B-PH CURRENT ME_FL B403_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsC$cVal$mag$f
131 R-Y VOLTAGE ME_FL B403_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsAB$cVal$mag$f
132 Y-B VOLTAGE ME_FL B403_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsBC$cVal$mag$f
133 B-R VOLYAGE ME_FL B403_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsCA$cVal$mag$f
135 CB-B-PH COUNTER ME_I B403_BCUCBB$XCBR1$ST$OpCnt stVal
136 CB-R-PH COUNTER ME_I B403_BCUCBR$XCBR1$ST$OpCnt stVal
137 CB-Y-PH COUNTER ME_I B403_BCUCBY$XCBR1$ST$OpCnt stVal
141 89BR CONTROL DC B403_BCU89BR$CSWI8$CO$Pos:8 Oper$ctlVal √
142 89B CONTROL DC B403_BCU89B$CSWI4$CO$Pos:8 Oper$ctlVal √
143 89A CONTROL DC B403_BCU89A$CSWI2$CO$Pos:8 Oper$ctlVal √
144 89BRE CONTROL DC B403_BCU89RE$CSWI9$CO$Pos:8 Oper$ctlVal √
145 89BE CONTROL DC B403_BCU89BE$CSWI7$CO$Pos:8 Oper$ctlVal √
146 89AE CONTROL DC B403_BCU89AE$CSWI3$CO$Pos:8 Oper$ctlVal √
147 CB CONTROL DC B403_BCUCB$CSWI1$CO$Pos:8 Oper$ctlVal √
148 CB CONTROL NO SYNC SC B403_BCUCB$CSWI1$CO$Pos Oper$noSync √
149 86B TRIP RELAY RESET COMMAND SC B403_BCUApplication$USER2$CO$SPC1:8 Oper$ctlVal √
150 86A TRIP RELAY RESET COMMAND SC B403_BCUApplication$USER2$CO$SPC:8 Oper$ctlVal √
151 PSD SWITCH IN CONTROL SC
152 PSD SWITCH OUT CONTROL SC
153 SETTINGS CHANGED √ √
154 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Feeder Name NAME ( BAY-403 BUS REACTOR )
Signal Decription INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Single Point)
1 400kV 400kV BR RESET LED SP B403_64RCTRL$LLN0$ST$LEDRs:2 stVal √
2 BCU UNHEALTHY SP B403_64RCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
3 GOOSE RECEIPT FAIL/TROUBLE SP B403_64RCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
4 DC SUPPLY-1 FAIL SP B403_64RCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
5 PRV-1 TRIP SP B403_64RCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
6 TIME SYNCHRONISATION ERROR SP B403_64REXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
7 REF STAGE 1 TRIP SP B403_64RPROT$PTOC16$ST$Op general √ √
8 REF STAGE 1 PICKUP SP B403_64RPROT$PTOC16$ST$Str general √
9 REF STAGE 2 TRIP SP B403_64RPROT$PTOC17$ST$Op general √ √
10 REF STAGE 2 PICKUP SP B403_64RPROT$PTOC17$ST$Str general √
11 GENERAL TRIP SP B403_64RPROT$PTRC1$ST$Tr general √ √
12 GENERAL PICKUP SP B403_64RPROT$PTRC1$ST$Str general √
13 COMMUNICATION STATUS SP stVal:1 √ √
16 WTI TRIP SP B403_64RCTRL$GGIO1$ST$SPCSO6:0 stVal √ √
17 MAIN TANK BUCHHOLZ A TRIP SP B403_64RCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
18 PNRV ALARM SP B403C_64RCTRL$BIBOGGIO1$ST$SPCSO5:0 stVal √ √
19 MAIN TANK BUCHHOLZ A ALARM
22 SETTINGS CHANGED √ √
23 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Feeder Name NAME ( BAY-403 BUS REACTOR )
Signal Decription INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Single Point)
1 400kV 400kV BR RESET LED SP B403_21RCTRL$LLN0$ST$LEDRs:2 stVal √
2 87.1R RELAY UNHEALTHY SP B403_21RCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
3 64.2R RELAY UNHEALTHY SP B403_21RCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
4 GOOSE RECEIPT FAIL/TROUBLE SP B403_21RCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
5 MOG ALARM SP B403_21RCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
6 MAIN TANK BUCHHOLZ ALARM SP B403_21RCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
7 OTI TRIP SP B403_21RCTRL$GGIO1$ST$SPCSO6:0 stVal √ √
8 TIME SYNCHRONISATION ERROR SP B403_21REXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
9 VT FUSE FAILURE SP B403_21REXT$pdGGIO3$ST$SPCSO41:0 stVal √ √
10 BROKEN CONDUCTOR SP B403_21REXT$pdGGIO4$ST$SPCSO3:0 stVal √ √
11 BACKUP IMPEDENCE ACTIVE SP B403_21REXT$pdGGIO58$ST$SPCSO5:0 stVal √ √
12 BACKUP IMPEDENCE BLOCKED SP B403_21REXT$pdGGIO58$ST$SPCSO4:0 stVal √
13 BACKUP IMPEDENCE ZONE-1 PICKUP SP B403_21RPROT$PDIS1$ST$Str general √
14 BACKUP IMPEDENCE ZONE-1 TRIP SP B403_21RPROT$PDIS1$ST$Op general √ √
15 BACKUP IMPEDENCE R-PH TRIP SP B403_21RPROT$PDIS1$ST$Op phsA √ √
16 BACKUP IMPEDENCE Y-PH TRIP SP B403_21RPROT$PDIS1$ST$Op phsB √ √
17 BACKUP IMPEDENCE B-PH TRIP SP B403_21RPROT$PDIS1$ST$Op phsC √ √
18 FAULT DISTANCE ME_FL B403_21RPROT$RFLO1$MX$FltDiskm:0 mag$f
19 GENERAL TRIP SP B403_21RPROT$PTRC1$ST$Tr general √ √
20 GENERAL PICKUP SP B403_21RPROT$PTRC1$ST$Str general √
21 COMMUNICATION STATUS ORG _ComFault √ √
22 LOW OIL LEVEL ALARM SP B403C_21RCTRL$BIBOGGIO1$ST$SPCSO7:0 stVal √ √
23 NON-DIRECTIONAL OVERCURRENT PICKUP SP B403C_21RPROT$PTOC2$ST$Str general √
24 NON-DIRECTIONAL OVERCURRENT TRIP SP B403C_21RPROT$PTOC2$ST$Op general √ √
25 HIGH OIL LEVEL ALARM
26 REACTOR MB AC FAIL
27 FLOW SENSITIVE VALVE ALARM
32 SETTINGS CHANGED
33 RELAY IN TEST MODE
34 NON-DIRECTIONAL EARTHFAULT TRIP
35 NON-DIRECTIONAL EARTHFAULT START
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Feeder Name
Signal Decription INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Single Point)
1 400kV 400kV BR RESET LED SP B403R_87RCTRL$LLN0$ST$LEDRs:2 stVal √
2 GOOSE RECEIPT FAIL/TROUBLE SP B403R_87RCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
3 REACTOR CB OPEN SP B403R_87RCTRL$GGIO1$ST$SPCSO1:0 stVal √
4 TIME SYNCHRONISATION ERROR SP B403R_87REXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
5 DIFFERENTIAL PROTECTION ACTIVE SP B403R_87REXT$pdGGIO88$ST$SPCSO49:0 stVal √ √
6 DIFFERENTIAL PROTECTION BLOCKED SP B403R_87REXT$pdGGIO88$ST$SPCSO48:0 stVal √
7 DIFFERENTIAL TRIP R-PH SP B403R_87REXT$pdGGIO89$ST$SPCSO40:0 stVal √ √
8 DIFFERENTIAL TRIP Y-PH SP B403R_87REXT$pdGGIO89$ST$SPCSO41:0 stVal √ √
9 DIFFERENTIAL TRIP B-PH SP B403R_87REXT$pdGGIO89$ST$SPCSO42:0 stVal √ √
10 DIFFERENTIAL STAGE 1 TRIP SP B403R_87RPROT$PDIF1$ST$Op general √ √
11 DIFFERENTIAL STAGE 1 PICKUP SP B403R_87RPROT$PDIF1$ST$Str general √
12 DIFFERENTIAL STAGE 2 TRIP SP B403R_87RPROT$PDIF2$ST$Op general √ √
13 DIFFERENTIAL STAGE 2 PICKUP SP B403R_87RPROT$PDIF2$ST$Str general √
14 GENERAL TRIP SP B403R_87RPROT$PTRC1$ST$Tr general √ √
15 GENERAL PICKUP SP B403R_87RPROT$PTRC1$ST$Str general √
16 COMMUNICATION STATUS ORG _ComFault √ √
17 MAIN CB OPEN SP B403C_87RCTRL$BIBOGGIO1$ST$SPCSO3:0 stVal √
18 TIE CB OPEN SP B403C_87RCTRL$BIBOGGIO1$ST$SPCSO4:0 stVal √
19 2ND HARMONIC
20 5TH HARMONIC
21 SUDDEN PRESSURE RELAY TRIP ALARM
22 BUCHHOLZ ALARM-B
23 BUCHHOLZ-A TRIP
24 PRESSURE RELIEF VALVE-2 OPERATED(TRIP)
26 64R RELAY UNHEALTHY
27 86-A/B TRIP RELAY OPTD
29 SETTINGS CHANGED √
30 RELAY IN TEST MODE √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
SIEMENS SCADA GENERAL SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (INDEX)
Sheet Ref. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 6MD66 BCU ICT BCU STNM4XXBCU BCU is for each bay so 4XX refers to Bay
2 7SJ80 7SJ8_51N ICT BACKUP EARTHFAULT RELAY (IF GIVEN SEPARATE) STNM4XXTBU Bay No. 4XX will be always the main bay number for the ICT feeder
3 7SJ80 7SJ8_64T.2B REF RELAY PHASE B FOR ICT STNM4XXTREFB Bay No. 4XX will be always the main bay number for the ICT feeder
4 7SJ80 7SJ8_64T.2R REF RELAY PHASE R FOR ICT STNM4XXTREFR Bay No. 4XX will be always the main bay number for the ICT feeder
5 7SJ80 7SJ8_64T.2Y REF RELAY PHASE Y FOR ICT STNM4XXTREFY Bay No. 4XX will be always the main bay number for the ICT feeder
6 7SJ80 7SJ8_67_1 LV ICT LV BACKUP OVERCURRENT AND EARTHFAULT RELAY STNM4XXTLVBU Bay No. 4XX will be always the main bay number for the ICT feeder
7 7SJ80 7SJ8_67_2HV ICT HV BACKUP OVERCURRENT AND EARTHFAULT RELAY STNM4XXTHVBU Bay No. 4XX will be always the main bay number for the ICT feeder
8 7RW 7RW_99LV ICT OVERFLUX RELAY STNM4XXTOF Bay No. 4XX will be always the main bay number for the ICT feeder
9 7UT85 7UT85_99HV ICT DIFFERENTIAL RELAY STNM4XXTDIF Bay No. 4XX will be always the main bay number for the ICT feeder
10 7SA522 7SA522_21R ICT BACKUP IMPEDANCE RELAY STNM4XXTBUIMP Bay No. 4XX will be always the main bay number for the ICT feeder
NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "4XX" stand for Bay name, example if the bay no 401 then same has to be implemented like STNM401BCU
400kV ICT-(BCU)
Sr. No. Voltage Level Feeder Name Source
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Double Point)
1 400kV 400kV ICT BCU CB B-PH POSITION DP B701_BCUCBB$XCBR1$ST$Pos:2 stVal √
2 CB R-PH POSITION DP B701_BCUCBR$XCBR1$ST$Pos:2 stVal √
3 CB Y-PH POSITION DP B701_BCUCBY$XCBR1$ST$Pos:2 stVal √
4 CB POSITION DP B701_BCUCB$CSWI1$ST$Pos:2 stVal √
S89T-R POSITION
S89T-Y POSITION
5 S89T-B POSITION DP B701_BCUES89AE1$CSWI3$ST$Pos:2 stVal √
6 89AE POSITION DP B701_BCUES89AE2$CSWI10$ST$Pos:2 stVal √
7 89BE POSITION DP B701_BCUES89BE$CSWI5$ST$Pos:2 stVal √
8 89TE B-PH POSITION DP B701_BCUES89TEB$CSWI7$ST$Pos:2 stVal √
9 89TE R-PH POSITION DP B701_BCUES89TER$CSWI7$ST$Pos:2 stVal √
10 89TE Y-PH POSITION DP B701_BCUES89TEY$CSWI7$ST$Pos:2 stVal √
11 89STE B-PH POSITION DP B701_BCUESTSE1B$CSWI9$ST$Pos:2 stVal √
12 89STE R-PH POSITION DP B701_BCUESTSE1R$CSWI9$ST$Pos:2 stVal √
13 89STE Y-PH POSITION DP B701_BCUESTSE1Y$CSWI9$ST$Pos:2 stVal √
14 89STE POSITION DP B701_BCUESTSE2$CSWI11$ST$Pos:2 stVal √
15 89A POSITION DP B701_BCUIS89A$CSWI2$ST$Pos:2 stVal √
16 89B POSITION DP B701_BCUIS89B$CSWI4$ST$Pos:2 stVal √
17 89T B-PH POSITION DP B701_BCUIS89TB$CSWI6$ST$Pos:2 stVal √
18 89T R-PH POSITION DP B701_BCUIS89TR$CSWI6$ST$Pos:2 stVal √
19 89T Y-PH POSITION DP B701_BCUIS89TY$CSWI6$ST$Pos:2 stVal √
20 89TS1_TS2 B-PH POSITION DP B701_BCUIS89TS1_TS2B$CSWI8$ST$Pos:2 stVal √
21 89TS1_TS2 R-PH POSITION DP B701_BCUIS89TS1_TS2R$CSWI8$ST$Pos:2 stVal √
22 89TS1_TS2 Y-PH POSITION DP B701_BCUIS89TS1_TS2Y$CSWI8$ST$Pos:2 stVal √
24 BINARY INPUT (Single Point)
26 AUX POWER FAIL SP B701_BCUApplication$LPHD0$ST$AuxPwrFail stVal √ √
27 TIME SYNCHRONISATION ERROR SP B701_BCUApplication$LMTS0$ST$TmSynErr stVal √ √
28 LED RESET SP B701_BCUApplication$LLN0$ST$LEDRs:2 stVal √
29 BCU MODE SP B701_BCUApplication$LLN0$ST$LocKey stVal √
30 CB SF6 GAS PRESSURE REFILL LOW ALARM SP B701_BCUApplication$USER1$ST$SPS stVal √ √
31 CB SF6 GAS PRESSURE LOCKOUT SP B701_BCUApplication$USER1$ST$SPS1 stVal √ √
32 CB DC SUPPLY-1/2 FAIL SP B701_BCUApplication$USER3$ST$SPS3 stVal √ √
33 CB SF6 GAS PRESSURE LOCKOUT SP B701_BCUApplication$USER3$ST$SPS2 stVal √ √
34 POLE DESCREPENCY SP B701_BCUApplication$USER3$ST$SPS1 stVal √ √
35 CB SPRING CHARGED B-PH SP B701_BCUApplication$USER3$ST$SPS6 stVal √ √
36 CB SPRING CHARGED R-PH SP B701_BCUApplication$USER3$ST$SPS4 stVal √ √
37 CB SPRING CHARGED Y-PH SP B701_BCUApplication$USER3$ST$SPS5 stVal √ √
38 89A POLE DESCREPENCY SP B701_BCUApplication$USER4$ST$SPS stVal √ √
39 89B POLE DESCREPENCY SP B701_BCUApplication$USER4$ST$SPS1 stVal √ √
40 86A TRIP RELAY SUPERVISION SP B701_BCUApplication$USER7$ST$SPS2 stVal √ √
41 86A TRIP RELAY OPERATED SP B701_BCUApplication$USER7$ST$SPS1 stVal √ √
42 86B TRIP RELAY SUPERVISION SP B701_BCUApplication$USER7$ST$SPS5 stVal √ √
43 86B TRIP RELAY OPERATED SP B701_BCUApplication$USER7$ST$SPS4 stVal √ √
44 EMERGENCY/MANUAL TRIP SP B701_BCUApplication$USER7$ST$SPS6 stVal √ √
45 CB TC-1 FAULTY SP B701_BCUApplication$USER7$ST$SPS stVal √ √
46 CB TC-2 FAULTY SP B701_BCUApplication$USER7$ST$SPS3 stVal √ √
47 PSD DEVICE IN SERVICE SP B701_BCUApplication$USER8$ST$SPS1 stVal √ √
48 PSD DEVICE HEALTHY SP B701_BCUApplication$USER8$ST$SPS stVal √ √
49 PSD ALARM SP B701_BCUApplication$USER8$ST$SPS2 stVal √ √
50 PSD SYNCH DATA ERROR SP B701_BCUApplication$USER8$ST$SPS3 stVal √ √
51 PSD SELECTOR SWITCH OUT
52 PSD SELECTOR SWITCH IN
53 DGA GAS HIGH ALARM SP-PH SP B701_BCUApplication$USER9$ST$SPS31 stVal √ √
54 DGA GAS HIGH ALARM R_Y_B-PH SP B701_BCUApplication$USER9$ST$SPS15 stVal √ √
55 MOISTER HIGH ALARM R_Y_B-PH SP B701_BCUApplication$USER9$ST$SPS16 stVal √ √
56 MOISTER HIGH ALARM SP-PH SP B701_BCUApplication$USER9$ST$SPS32 stVal √ √
57 OLTC OIL TEMP HIGH B-PH ALARM SP B701_BCUApplication$USER9$ST$SPS22 stVal √ √
58 OLTC OIL TEMP HIGH R-PH ALARM SP B701_BCUApplication$USER9$ST$SPS18 stVal √ √
59 OLTC OIL TEMP HIGH SP-PH ALARM SP B701_BCUApplication$USER9$ST$SPS34 stVal √ √
60 OLTC OIL TEMP HIGH Y-PH ALARM SP B701_BCUApplication$USER9$ST$SPS20 stVal √ √
61 OLTC OIL TEMP LOW B-PH ALARM SP B701_BCUApplication$USER9$ST$SPS21 stVal √ √
62 OLTC OIL TEMP LOW R-PH ALARM SP B701_BCUApplication$USER9$ST$SPS17 stVal √ √
63 OLTC OIL TEMP LOW SP-PH ALARM SP B701_BCUApplication$USER9$ST$SPS33 stVal √ √
64 OLTC OIL TEMP LOW Y-PH ALARM SP B701_BCUApplication$USER9$ST$SPS19 stVal √ √
65 OLTC LOW OIL REFILL B-PH ALARM SP B701_BCUApplication$USER9$ST$SPS12 stVal √ √
66 OLTC LOW OIL REFILL SP-PH ALARM SP B701_BCUApplication$USER9$ST$SPS28 stVal √ √
67 OLTC LOW OIL REFILL R-PH ALARM SP B701_BCUApplication$USER9$ST$SPS2 stVal √ √
68 OLTC LOW OIL REFILL Y-PH ALARM SP B701_BCUApplication$USER9$ST$SPS7 stVal √ √
69 RPH MOG LOW OIL LEVEL ALARM SP
70 YPH MOG LOW OIL LEVEL ALARM SP
71 BPH MOG LOW OIL LEVEL ALARM SP
72 SP-PH MOG LOW OIL LEVEL ALARM SP
73 RPH MOG HIGH OIL LEVEL ALARM SP
74 YPH MOG HIGH OIL LEVEL ALARM SP
75 BPH MOG HIGH OIL LEVEL ALARM SP
76 SP-PH MOG HIGH OIL LEVEL ALARM SP
77 R-PH OIL FLOW SENSITIVE VALVE ALARM SP
78 Y-PH OIL FLOW SENSITIVE VALVE ALARM SP
79 B-PH OIL FLOW SENSITIVE VALVE ALARM SP
80 SP-PH OIL FLOW SENSITIVE VALVE ALARM SP
81 RPH PUMP FAIL - BANK A SP
82 RPH PUMP FAIL - BANK B SP
83 RPH PUMP FAIL - BANK C SP
84 RPH PUMP FAIL - BANK D SP
85 YPH PUMP FAIL - BANK A SP
86 YPH PUMP FAIL - BANK B SP
87 YPH PUMP FAIL - BANK C SP
88 YPH PUMP FAIL - BANK D SP
89 BPH PUMP FAIL - BANK A SP
90 BPH PUMP FAIL - BANK B SP
91 BPH PUMP FAIL - BANK C SP
92 BPH PUMP FAIL - BANK D SP
93 SPH PUMP FAIL - BANK A SP
94 SPH PUMP FAIL - BANK B SP
95 SPH PUMP FAIL - BANK C SP
96 SPH PUMP FAIL - BANK D SP
97 RPH THERMAL OVERLOAD TRIP - BANK A SP
98 RPH THERMAL OVERLOAD TRIP - BANK B SP
99 RPH THERMAL OVERLOAD TRIP - BANK C SP
100 RPH THERMAL OVERLOAD TRIP - BANK D SP
101 YPH THERMAL OVERLOAD TRIP - BANK A SP
102 YPH THERMAL OVERLOAD TRIP - BANK B SP
103 YPH THERMAL OVERLOAD TRIP - BANK C SP
104 YPH THERMAL OVERLOAD TRIP - BANK D SP
105 BPH THERMAL OVERLOAD TRIP - BANK A SP
106 BPH THERMAL OVERLOAD TRIP - BANK B SP
107 BPH THERMAL OVERLOAD TRIP - BANK C SP
108 BPH THERMAL OVERLOAD TRIP - BANK D SP
109 SPH THERMAL OVERLOAD TRIP - BANK A SP
110 SPH THERMAL OVERLOAD TRIP - BANK B SP
111 SPH THERMAL OVERLOAD TRIP - BANK C SP
112 SPH THERMAL OVERLOAD TRIP - BANK D SP
113 RPH LOW OIL FLOW/REVERSE FLOW - BANK A SP
114 RPH LOW OIL FLOW/REVERSE FLOW - BANK B SP
115 RPH LOW OIL FLOW/REVERSE FLOW - BANK C SP
116 RPH LOW OIL FLOW/REVERSE FLOW - BANK D SP
117 YPH LOW OIL FLOW/REVERSE FLOW - BANK A SP
118 YPH LOW OIL FLOW/REVERSE FLOW - BANK B SP
119 YPH LOW OIL FLOW/REVERSE FLOW - BANK C SP
120 YPH LOW OIL FLOW/REVERSE FLOW - BANK D SP
121 BPH LOW OIL FLOW/REVERSE FLOW - BANK A SP
122 BPH LOW OIL FLOW/REVERSE FLOW - BANK B SP
123 BPH LOW OIL FLOW/REVERSE FLOW - BANK C SP
124 BPH LOW OIL FLOW/REVERSE FLOW - BANK D SP
125 SPH LOW OIL FLOW/REVERSE FLOW - BANK A SP
126 SPH LOW OIL FLOW/REVERSE FLOW - BANK B SP
127 SPH LOW OIL FLOW/REVERSE FLOW - BANK C SP
128 SPH LOW OIL FLOW/REVERSE FLOW - BANK D SP
129 RPH COOLER CONTROL SUPPLY FAIL SP
130 YPH COOLER CONTROL SUPPLY FAIL SP
131 BPH COOLER CONTROL SUPPLY FAIL SP
132 SPH COOLER CONTROL SUPPLY FAIL SP
133 RPH SUPPLY CHANGE OVER FAIL SP
134 YPH SUPPLY CHANGE OVER FAIL SP
135 BPH SUPPLY CHANGE OVER FAIL SP
136 SPH SUPPLY CHANGE OVER FAIL SP
137 RPH SUPPLY - A FAIL SP
138 YPH SUPPLY - A FAIL SP
139 BPH SUPPLY - A FAIL SP
140 SPH SUPPLY - A FAIL SP
141 RPH SUPPLY - B FAIL SP
142 YPH SUPPLY - B FAIL SP
143 BPH SUPPLY - B FAIL SP
144 SPH SUPPLY - B FAIL SP
145 RPH OLTC MOTOR OVERLOAD SP
146 RPH TAP CHANGE IN PROGRESS SP
147 RPH TAP CHANGE IN COMPLETE SP
148 RPH OLTC IN LOCAL SP
149 RPH OLTC IN REMOTE SP
150 RPH TAP CHANGE CONTROL SUPPLY FAIL SP
151 RPH LOWEST POSITION REACHDED SP
152 RPH HIGHESHT POSITION REACHDED SP
153 RPH OLTC RAISE COMMAND CMD
154 RPH OLTC LOWER COMMAND CMD
155 YPH OLTC MOTOR OVERLOAD SP
156 YPH TAP CHANGE IN PROGRESS SP
157 YPH TAP CHANGE IN COMPLETE SP
158 YPH OLTC IN LOCAL SP
159 YPH OLTC IN REMOTE SP
160 YPH TAP CHANGE CONTROL SUPPLY FAIL SP
161 YPH LOWEST POSITION REACHDED SP
162 YPH HIGHESHT POSITION REACHDED SP
163 YPH OLTC RAISE COMMAND CMD
164 YPH OLTC LOWER COMMAND CMD
165 BPH OLTC MOTOR OVERLOAD SP
166 BPH TAP CHANGE IN PROGRESS SP
167 BPH TAP CHANGE IN COMPLETE SP
168 BPH OLTC IN LOCAL SP
169 BPH OLTC IN REMOTE SP
170 BPH TAP CHANGE CONTROL SUPPLY FAIL SP
171 BPH LOWEST POSITION REACHDED SP
172 BPH HIGHESHT POSITION REACHDED SP
173 BPH OLTC RAISE COMMAND CMD
174 BPH OLTC LOWER COMMAND CMD
175 SPH OLTC MOTOR OVERLOAD SP
176 SPH TAP CHANGE IN PROGRESS SP
177 SPH TAP CHANGE IN COMPLETE SP
178 SPH OLTC IN LOCAL SP
179 SPH OLTC IN REMOTE SP
180 SPH TAP CHANGE CONTROL SUPPLY FAIL SP
181 SPH LOWEST POSITION REACHDED SP
182 SPH HIGHESHT POSITION REACHDED SP
183 SPH OLTC RAISE COMMAND CMD
184 SPH OLTC LOWER COMMAND CMD
185 OTI B-PH ALARM SP B701_BCUApplication$USER9$ST$SPS14 stVal √ √
186 OTI R-PH ALARM SP B701_BCUApplication$USER9$ST$SPS4 stVal √ √
187 OTI SP-PH ALARM SP B701_BCUApplication$USER9$ST$SPS30 stVal √ √
188 OTI Y-PH ALARM SP B701_BCUApplication$USER9$ST$SPS9 stVal √ √
189 PUMP FAIL B-PH SP B701_BCUApplication$USER9$ST$SPS25 stVal √ √
190 PUMP FAIL R-PH SP B701_BCUApplication$USER9$ST$SPS23 stVal √ √
191 PUMP FAIL SP-PH SP B701_BCUApplication$USER9$ST$SPS35 stVal √ √
192 PUMP FAIL Y-PH SP B701_BCUApplication$USER9$ST$SPS24 stVal √ √
193 SURGE ARRESTER B-PH SP B701_BCUApplication$USER9$ST$SPS38 stVal √ √
194 SURGE ARRESTER R-PH SP B701_BCUApplication$USER9$ST$SPS36 stVal √ √
195 SURGE ARRESTER Y-PH SP B701_BCUApplication$USER9$ST$SPS37 stVal √ √
196 WTI HV_IV_LV ALARM B-PH SP B701_BCUApplication$USER9$ST$SPS13 stVal √ √
197 WTI HV_IV_LV ALARM R-PH SP B701_BCUApplication$USER9$ST$SPS3 stVal √ √
198 WTI HV_IV_LV ALARM SP-PH SP B701_BCUApplication$USER9$ST$SPS29 stVal √ √
199 WTI HV_IV_LV ALARM Y-PH SP B701_BCUApplication$USER9$ST$SPS8 stVal √ √
200 CB SF6 LOW PRESSURE ALARM B-PH SP B701_BCUApplication$USER2$ST$SPS2 stVal √ √
201 CB SF6 LOW PRESSURE ALARM R-PH SP B701_BCUApplication$USER2$ST$SPS stVal √ √
202 CB SF6 LOW PRESSURE ALARM Y-PH SP B701_BCUApplication$USER2$ST$SPS1 stVal √ √
203 SP ICT B-PH SELECTED SP B701_BCUApplication$USER12$ST$SPS2 stVal √
204 SP ICT R-PH SELECTED SP B701_BCUApplication$USER12$ST$SPS stVal √
205 SP ICT Y-PH SELECTED SP B701_BCUApplication$USER12$ST$SPS1 stVal √
206 BUS-1 VT RESET SP B701_BCUApplication$USER10$ST$SPS1 stVal √
207 BUS-2 VT RESET SP B701_BCUApplication$USER10$ST$SPS3 stVal √
208 LINE VT RESET SP B701_BCUApplication$USER10$ST$SPS5 stVal √
209 BUS-1 VT SELECTED SP B701_BCUApplication$USER10$ST$SPS stVal √
210 BUS-2 VT SELECTED SP B701_BCUApplication$USER10$ST$SPS2 stVal √
211 LINE VTSELECTED SP B701_BCUApplication$USER10$ST$SPS4 stVal √
212 CB READY SP B701_BCUCB$XCBR1$ST$Rdy stVal √
213 EMERGENCY/MANUAL CB CLOSE SP B701_BCUCB$GAPC2$ST$Detected stVal √
214 GOOSE RECEIPT FAIL/TROUBLE SP B701_BCUApplication$USER10$ST$SPS3 stVal √ √
215 CB POSITION NO SYNC SP B701_BCUCB$CSWI1$ST$Pos noSync √
216 CB CLOSE INTERLOCK SP B701_BCUCB$CILO1$ST$EnaCls stVal √
217 89AE1 OPEN INTERLOCK SP B701_BCUES89AE1$CILO3$ST$EnaOpn stVal √
218 89AE2 OPEN INTERLOCK SP B701_BCUES89AE2$CILO10$ST$EnaOpn stVal √
219 89BE OPEN INTERLOCK SP B701_BCUES89BE$CILO5$ST$EnaOpn stVal √
220 89TE B-PH OPEN INTERLOCK SP B701_BCUES89TEB$CILO7$ST$EnaOpn stVal √
221 89TE R-PH OPEN INTERLOCK SP B701_BCUES89TER$CILO7$ST$EnaOpn stVal √
222 89TE Y-PH OPEN INTERLOCK SP B701_BCUES89TEY$CILO7$ST$EnaOpn stVal √
223 TSE1 B-PH OPEN INTERLOCK SP B701_BCUESTSE1B$CILO9$ST$EnaOpn stVal √
224 TSE1 R-PH OPEN INTERLOCK SP B701_BCUESTSE1R$CILO9$ST$EnaOpn stVal √
225 TSE1 Y-PH OPEN INTERLOCK SP B701_BCUESTSE1Y$CILO9$ST$EnaOpn stVal √
226 TSE2 OPEN INTERLOCK SP B701_BCUESTSE2$CILO11$ST$EnaOpn stVal √
227 89A OPEN INTERLOCK SP B701_BCUIS89A$CILO2$ST$EnaOpn stVal √
228 89B OPEN INTERLOCK SP B701_BCUIS89B$CILO4$ST$EnaOpn stVal √
229 89T B-PH OPEN INTERLOCK SP B701_BCUIS89TB$CILO6$ST$EnaOpn stVal √
230 89T R-PH OPEN INTERLOCK SP B701_BCUIS89TR$CILO6$ST$EnaOpn stVal √
231 89T Y-PH OPEN INTERLOCK SP B701_BCUIS89TY$CILO6$ST$EnaOpn stVal √
232 89TS1_TS2 B-PH OPEN INTERLOCK SP B701_BCUIS89TS1_TS2B$CILO8$ST$EnaOpn stVal √
233 89TS1_TS2 R-PH OPEN INTERLOCK SP B701_BCUIS89TS1_TS2R$CILO8$ST$EnaOpn stVal √
234 89TS1_TS2 Y-PH OPEN INTERLOCK SP B701_BCUIS89TS1_TS2Y$CILO8$ST$EnaOpn stVal √
235 RELAY IN TEST MODE √ √
236 SETTINGS CHANGED √ √
237 ICT-n R PH OUT OF SERVICE √
238 ICT-n Y PH OUT OF SERVICE √
239 ICT-n B PH OUT OF SERVICE √
240 ICT SPARE PH IN SERVICE IN ICT-N √
241 CB MANUAL TRIP √
242 CB MANUAL CLOSE √
243 BUSBAR OPERATED √ √
244 BCU IN LOCAL/REMOTE √
245 CB TC-1 R-PHASE FAULTY √ √
246 CB TC-1 Y-PHASE FAULTY √ √
247 CB TC-1 B-PHASE FAULTY √ √
248 CB TC-2 R-PHASE FAULTY √ √
249 CB TC-2 Y-PHASE FAULTY √ √
250 CB TC-2 B-PHASE FAULTY √ √
252 MEASUREMENT
254 POWER FACTOR ME_FL B701_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotPF:1 mag$f
255 FREQUENCY ME_FL B701_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$Hz:1 mag$f
256 ACTIVE POWER ME_FL B701_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotW:1 mag$f
257 REACTIVE POWER ME_FL B701_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVAr:1 mag$f
258 APPARENT POWER ME_FL B701_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVA:1 mag$f
259 I-R-PH CURRENT ME_FL B701_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsA$cVal$mag$f
260 I-Y-PH CURRENT ME_FL B701_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsB$cVal$mag$f
261 I-B-PH CURRENT ME_FL B701_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsC$cVal$mag$f
262 R-Y VOLTAGE ME_FL B701_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsAB$cVal$mag$f
263 Y-B VOLTAGE ME_FL B701_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsBC$cVal$mag$f
264 400kV 400kV ICT BCU B-R VOLYAGE ME_FL B701_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsCA$cVal$mag$f
265 CB-B-PH COUNTER ME_I B701_BCUCBB$XCBR1$ST$OpCnt stVal
266 CB-R-PH COUNTER ME_I B701_BCUCBR$XCBR1$ST$OpCnt stVal
267 CB-Y-PH COUNTER ME_I B701_BCUCBY$XCBR1$ST$OpCnt stVal
271 CB CONTROL DC B701_BCUCB$CSWI1$CO$Pos:8 Oper$ctlVal √
272 89AE1 CONTROL DC B701_BCUES89AE1$CSWI3$CO$Pos:8 Oper$ctlVal √ NO command in AIS.
273 89AE2 CONTROL DC B701_BCUES89AE2$CSWI10$CO$Pos:8 Oper$ctlVal √
274 89BE CONTROL DC B701_BCUES89BE$CSWI5$CO$Pos:8 Oper$ctlVal √
275 89TE B-PH CONTROL DC B701_BCUES89TEB$CSWI7$CO$Pos:8 Oper$ctlVal √
276 89TE R-PH CONTROL DC B701_BCUES89TER$CSWI7$CO$Pos:8 Oper$ctlVal √
277 89TE Y-PH CONTROL DC B701_BCUES89TEY$CSWI7$CO$Pos:8 Oper$ctlVal √
278 TSE1 B-PH CONTROL DC B701_BCUESTSE1B$CSWI9$CO$Pos:8 Oper$ctlVal √
279 TSE1 R-PH CONTROL DC B701_BCUESTSE1R$CSWI9$CO$Pos:8 Oper$ctlVal √
280 TSE1 Y-PH CONTROL DC B701_BCUESTSE1Y$CSWI9$CO$Pos:8 Oper$ctlVal √
281 TSE2 CONTROL DC B701_BCUESTSE2$CSWI11$CO$Pos:8 Oper$ctlVal √
282 89A CONTROL DC B701_BCUIS89A$CSWI2$CO$Pos:8 Oper$ctlVal √
283 89B CONTROL DC B701_BCUIS89B$CSWI4$CO$Pos:8 Oper$ctlVal √
284 89T B-PH CONTROL DC B701_BCUIS89TB$CSWI6$CO$Pos:8 Oper$ctlVal √
285 89T R-PH CONTROL DC B701_BCUIS89TR$CSWI6$CO$Pos:8 Oper$ctlVal √
286 89TS1_TS2 B-PH CONTROL DC B701_BCUIS89TS1_TS2B$CSWI8$CO$Pos:8 Oper$ctlVal √
287 89TS1_TS2 R-PH CONTROL DC B701_BCUIS89TS1_TS2R$CSWI8$CO$Pos:8 Oper$ctlVal √
288 89TS1_TS2 Y-PH CONTROL DC B701_BCUIS89TS1_TS2Y$CSWI8$CO$Pos:8 Oper$ctlVal √
289 89T Y-PH CONTROL DC B701_BCUIS89TY$CSWI6$CO$Pos:8 Oper$ctlVal √
290 CB CONTROL NO SYN SC B701_BCUCB$CSWI1$CO$Pos Oper$noSync √
291 86A TRIP RELAY RESET COMMAND SC B701_BCUApplication$USER2$CO$SPC:8 Oper$ctlVal √
292 86B TRIP RELAY RESET COMMAND SC B701_BCUApplication$USER2$CO$SPC1:8 Oper$ctlVal √
293 TAP RAISER SC B701_BCUApplication$USER8$CO$SPC:8 Oper$ctlVal √
294 TAP LOWER SC B701_BCUApplication$USER8$CO$SPC1:8 Oper$ctlVal √
Note: 1. All the switchgear status signals as per the actual primary equipment status. 2. Additional signal for CB Trouble, etc as per scheme 3. 10 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 4. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 5. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
400kV ICT- 51N-(7SJ80)
Sr. No. Voltage Level Feeder Name Source
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 400kV 400kV ICT 7SJ80 DMT EARTHFAULT STAGE 1 TRIP SP B701_51NPROT$PTOC8$ST$Op general √ √
2 DMT EARTHFAULT STAGE 1 PICKUP SP B701_51NPROT$PTOC8$ST$Str general √
3 DMT EARTHFAULT STAGE 2 TRIP SP B701_51NPROT$PTOC9$ST$Op general √ √
4 DMT EARTHFAULT STAGE 2 PICKUP SP B701_51NPROT$PTOC9$ST$Str general √
5 IDMT EARTHFAULT TRIP SP B701_51NPROT$PTOC2$ST$Op general √ √
6 IDMT EARTHFAULT PICKUP SP B701_51NPROT$PTOC2$ST$Str general √
7 GENERAL TRIP SP B701_51NPROT$PTRC1$ST$Tr general √ √
8 GENERAL PICKUP SP B701_51NPROT$PTRC1$ST$Str general √
9 DEVICE HEALTHY SP B701_51NPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
10 TIME SYNCHRONISATION ERROR SP B701_51NEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
11 VT FUSE FAILURE SP B701_51NEXT$pdGGIO3$ST$SPCSO41:0 stVal √ √
12 OLTC OSR TRIP R PH SP B701_51NCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
13 OLTC OSR TRIP Y PH SP B701_51NCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
14 OLTC OSR TRIP B PH SP B701_51NCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
15 OIL FLOW SENSITIVE VALVE TRIP R PH SP B701_51NCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
16 OIL FLOW SENSITIVE VALVE TRIP Y PH SP B701_51NCTRL$GGIO1$ST$SPCSO6:0 stVal √ √
17 GOOSE RECEIPT FAIL/TROUBLE SP B701_51NCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
18 SETTINGS CHANGED √ √
19 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
400kV ICT- 64T.2B-(7SJ80)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 400kV 400kV ICT 7SJ80 99LV_51N RELAY UNHEALTHY SP B701_64T_2BCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
2 RAPID PRESSURE TRIP B-PH SP B701_64T_2BCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
3 REF STAGE 1 TRIP SP B701_64T_2BPROT$PTOC16$ST$Op general √ √
4 REF STAGE 1 PICKUP SP B701_64T_2BPROT$PTOC16$ST$Str general √
5 REF STAGE 2 TRIP SP B701_64T_2BPROT$PTOC17$ST$Op general √ √
6 REF STAGE 2 PICKUP SP B701_64T_2BPROT$PTOC17$ST$Str general √
7 GENERAL TRIP SP B701_64T_2BPROT$PTRC1$ST$Tr general √ √
8 GENERAL PICKUP SP B701_64T_2BPROT$PTRC1$ST$Str general √
9 DEVICE HEALTHY SP B701_64T_2BPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
10 TIME SYNCHRONISATION ERROR SP B701_64T_2BEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
11 GOOSE RECEIPT FAIL/TROUBLE SP B701_64T_2BCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
12 BUCHHOLZ 1 TRIP B-PH SP B701_64T_2BCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
13 OTI TRIP B-PH SP B701_64T_2BCTRL$GGIO1$ST$SPCSO6:0 stVal √ √
14 BUCHHOLZ 2 ALARM B-PH SP B701_64T_2BCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
15 PRD OLTC TRIP B-PH SP B701_64T_2BCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
16 SETTINGS CHANGED √ √
17 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, Mechanical trips, alarms etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
400kV ICT- 64T.2R-(7SJ80)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 400kV 400kV ICT 7SJ80 MAIN CB OPEN SP B701_64T_2RCTRL$GGIO1$ST$SPCSO1:0 stVal √
2 TIE CB OPEN SP B701_64T_2RCTRL$GGIO1$ST$SPCSO2:0 stVal √
3 BUCHHOLZ 1 TRIP R-PH SP B701_64T_2RCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
4 BUCHHOLZ 2 ALARM R-PH B701_64T_2RCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
5 OTI TRIP R-PH SP B701_64T_2RCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
6 PRD OLTC TRIP R-PH SP B701_64T_2RCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
7 REF STAGE 1 TRIP SP B701_64T_2RPROT$PTOC16$ST$Op general √ √
8 REF STAGE 1 PICKUP SP B701_64T_2RPROT$PTOC16$ST$Str general √
9 REF STAGE 2 TRIP SP B701_64T_2RPROT$PTOC17$ST$Op general √ √
10 REF STAGE 2 PICKUP SP B701_64T_2RPROT$PTOC17$ST$Str general √
11 GENERAL TRIP SP B701_64T_2RPROT$PTRC1$ST$Tr general √ √
12 GENERAL PICKUP SP B701_64T_2RPROT$PTRC1$ST$Str general √
13 DEVICE HEALTHY SP B701_64T_2RPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
14 TIME SYNCHRONISATION ERROR SP B701_64T_2REXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
15 GOOSE RECEIPT FAIL/TROUBLE SP B701_64T_2RCTRL$GGIO1$ST$SPCSO6:0 stVal √ √
16 SETTINGS CHANGED √ √
17 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, Mechanical trips, alarms etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
400kV ICT- 64T.2Y-(7SJ80)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 400kV 400kV ICT 7SJ80 BUCHHOLZ 1 TRIP Y-PH SP B701_64T_2YCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
2 OTI TRIP Y-PH SP B701_64T_2YCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
3 PRD OLTC TRIP Y-PH SP B701_64T_2YCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
4 REF STAGE 1 TRIP SP B701_64T_2YPROT$PTOC16$ST$Op general √ √
5 REF STAGE 1 PICKUP SP B701_64T_2YPROT$PTOC16$ST$Str general √
6 REF STAGE 2 TRIP SP B701_64T_2YPROT$PTOC17$ST$Op general √ √
7 REF STAGE 2 PICKUP SP B701_64T_2YPROT$PTOC17$ST$Str general √
8 GENERAL TRIP SP B701_64T_2YPROT$PTRC1$ST$Tr general √ √
9 GENERAL PICKUP SP B701_64T_2YPROT$PTRC1$ST$Str general √
10 DEVICE HEALTHY SP B701_64T_2YPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
11 TIME SYNCHRONISATION ERROR SP B701_64T_2YEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
12 BUCHHOLZ 2 ALARM Y-PH SP B701_64T_2YCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
13 GOOSE RECEIPT FAIL/TROUBLE SP B701_64T_2YCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
16 SETTINGS CHANGED √ √
17 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, Mechanical trips, alarms etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
400kV ICT- 67-1-LV (7SJ80)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 400kV 400kV ICT 7SJ80 67. 2 HV RELAY UNHEALTHY SP B701_67_1_LVCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
2 87.1_99HV HV RELAY UNHEALTHY SP B701_67_1_LVCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
3 BCU UNHEALTHY SP B701_67_1_LVCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
4 DIRECTIONAL DMT OVERCURRENT STAGE-1 BLOCKED SP B701_67_1_LVPROT$PTOC10$ST$Blk stVal √
5 DIRECTIONAL DMT OVERCURRENT STAGE-1 TRIP SP B701_67_1_LVPROT$PTOC10$ST$Op general √ √
6 DIRECTIONAL DMT OVERCURRENT STAGE-1 PICKUP SP B701_67_1_LVPROT$PTOC10$ST$Str general √
7 DIRECTIONAL DMT OVERCURRENT STAGE-2 BLOCKED SP B701_67_1_LVPROT$PTOC11$ST$Blk stVal √
8 DIRECTIONAL DMT OVERCURRENT STAGE-2 TRIP SP B701_67_1_LVPROT$PTOC11$ST$Op general √ √
9 DIRECTIONAL DMT OVERCURRENT STAGE-2 PICKUP SP B701_67_1_LVPROT$PTOC11$ST$Str general √
10 DIRECTIONAL DMT OVERCURRENT STAGE-3 TRIP SP B701_67_1_LVPROT$PTOC19$ST$Op general √ √
11 DIRECTIONAL DMT OVERCURRENT STAGE-3 PICKUP SP B701_67_1_LVPROT$PTOC19$ST$Str general √
12 DIRECTIONAL DMT EARTHFAULT STAGE-1 BLOCKED SP B701_67_1_LVPROT$PTOC12$ST$Blk stVal √
13 DIRECTIONAL DMT EARTHFAULT STAGE-1 TRIP SP B701_67_1_LVPROT$PTOC12$ST$Op general √ √
14 DIRECTIONAL DMT EARTHFAULT STAGE-1 PICKUP SP B701_67_1_LVPROT$PTOC12$ST$Str general √
15 DIRECTIONAL DMT EARTHFAULT STAGE-2 BLOCKED SP B701_67_1_LVPROT$PTOC13$ST$Blk stVal √
16 DIRECTIONAL DMT EARTHFAULT STAGE-2 TRIP SP B701_67_1_LVPROT$PTOC13$ST$Op general √ √
17 DIRECTIONAL DMT EARTHFAULT STAGE-2 PICKUP SP B701_67_1_LVPROT$PTOC13$ST$Str general √
18 DIRECTIONAL DMT EARTHFAULT STAGE-3 TRIP SP B701_67_1_LVPROT$PTOC20$ST$Op general √ √
19 DIRECTIONAL DMT EARTHFAULT STAGE-3 PICKUP SP B701_67_1_LVPROT$PTOC20$ST$Str general √
20 DIRECTIONAL IDMT OVERCURRENT BLOCKED SP B701_67_1_LVPROT$PTOC4$ST$Blk stVal √
21 DIRECTIONAL IDMT OVERCURRENT TRIP SP B701_67_1_LVPROT$PTOC4$ST$Op general √ √
22 DIRECTIONAL IDMT EARTHFAULT BLOCKED SP B701_67_1_LVPROT$PTOC3$ST$Blk stVal √
23 DIRECTIONAL IDMT EARTHFAULT TRIP SP B701_67_1_LVPROT$PTOC3$ST$Op general √ √
24 GENERAL TRIP SP B701_67_1_LVPROT$PTRC1$ST$Tr general √ √
25 GENERAL PICKUP SP B701_67_1_LVPROT$PTRC1$ST$Str general √
26 DEVICE HEALTHY SP B701_67_1_LVPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
27 TIME SYNCHRONISATION ERROR SP B701_67_1_LVEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
28 GOOSE RECEIPT FAIL/TROUBLE SP B701_67_1_LVCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
16 SETTINGS CHANGED √ √
17 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, Mechanical trips, alarms etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
400kV ICT-67-2HV (7SJ80)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 400kV 400kV ICT 7SJ80 RAPID PRESSURE TRIP R-PH SP B701_67_2HVCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
2 BUCHHOLZ 2 TRIP SP-PH SP B701_67_2HVCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
3 WTI HV_IV_LV TRIP SP-PH SP B701_67_2HVCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
4 WTI HV_LV_IV TRIP B-PH SP B701_67_2HVCTRL$GGIO1$ST$SPCSO6:0 stVal √ √
5 WTI HV_LV_IV TRIP R-PH SP B701_67_2HVCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
6 WTI HV_LV_IV TRIP Y-PH SP B701_67_2HVCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
7 DIRECTIONAL DMT OVERCURRENT STAGE-1 BLOCKED SP B701_67_2HVPROT$PTOC10$ST$Blk stVal √
8 DIRECTIONAL DMT OVERCURRENT STAGE-1 TRIP SP B701_67_2HVPROT$PTOC10$ST$Op general √ √
9 DIRECTIONAL DMT OVERCURRENT STAGE-1 PICKUP SP B701_67_2HVPROT$PTOC10$ST$Str general √
10 DIRECTIONAL DMT OVERCURRENT STAGE-2 BLOCKED SP B701_67_2HVPROT$PTOC11$ST$Blk stVal √
11 DIRECTIONAL DMT OVERCURRENT STAGE-2 TRIP SP B701_67_2HVPROT$PTOC11$ST$Op general √ √
12 DIRECTIONAL DMT OVERCURRENT STAGE-2 PICKUP SP B701_67_2HVPROT$PTOC11$ST$Str general √
13 DIRECTIONAL DMT OVERCURRENT STAGE-3 TRIP SP B701_67_2HVPROT$PTOC19$ST$Op general √ √
14 DIRECTIONAL DMT OVERCURRENT STAGE-3 PICKUP SP B701_67_2HVPROT$PTOC19$ST$Str general √
15 DIRECTIONAL DMT EARTHFAULT STAGE-1 BLOCKED SP B701_67_2HVPROT$PTOC12$ST$Blk stVal √
16 DIRECTIONAL DMT EARTHFAULT STAGE-1 TRIP SP B701_67_2HVPROT$PTOC12$ST$Op general √ √
17 DIRECTIONAL DMT EARTHFAULT STAGE-1 PICKUP SP B701_67_2HVPROT$PTOC12$ST$Str general √
18 DIRECTIONAL DMT EARTHFAULT STAGE-2 BLOCKED SP B701_67_2HVPROT$PTOC13$ST$Blk stVal √
19 DIRECTIONAL DMT EARTHFAULT STAGE-2 TRIP SP B701_67_2HVPROT$PTOC13$ST$Op general √ √
20 DIRECTIONAL DMT EARTHFAULT STAGE-2 PICKUP SP B701_67_2HVPROT$PTOC13$ST$Str general √
21 DIRECTIONAL DMT EARTHFAULT STAGE-3 TRIP SP B701_67_2HVPROT$PTOC20$ST$Op general √ √
22 DIRECTIONAL DMT EARTHFAULT STAGE-3 PICKUP SP B701_67_2HVPROT$PTOC20$ST$Str general √
23 GENERAL TRIP SP B701_67_2HVPROT$PTRC1$ST$Tr general √ √
24 GENERAL PICKUP SP B701_67_2HVPROT$PTRC1$ST$Str general √
25 DEVICE HEALTHY SP B701_67_2HVPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
26 TIME SYNCHRONISATION ERROR SP B701_67_2HVEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
27 GOOSE RECEIPT FAIL/TROUBLE SP B701_67_2HVCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
28 SETTINGS CHANGED √ √
29 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, Mechanical trips, alarms etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
400kV ICT-99LV (7RW)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 400kV 400kV ICT 7RW 64.2 R_Y_B_SP RELAY UNHEALTHY SP B701_99LVCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
2 67.1 LV RELAY UNHEALTHY SP B701_99LVCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
3 RAPID PRESSURE TRIP Y-PH SP B701_99LVCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
4 OIL FLOW SENSITIVE VALVE TRIP B PH SP B701_99LVCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
5 OIL FLOW SENSITIVE VALVE TRIP SP PH B701_99LVCTRL$GGIO1$ST$SPCSO3:0
6 OVERFLUX STAGE-2 OPERATED SP B701_99LVPROT$PVPH2$ST$Op general √ √
7 OVERFLUX STAGE-2 PICKUP SP B701_99LVPROT$PVPH2$ST$Str general √
8 OVERFLUX STAGE-1 OPERATED SP B701_99LVPROT$PVPH1$ST$Op general √ √
9 OVERFLUX STAGE-1 PICKUP SP B701_99LVPROT$PVPH1$ST$Str general √
10 GENERAL TRIP SP B701_99LVPROT$PTRC1$ST$Tr general √ √
11 GENERAL PICKUP SP B701_99LVPROT$PTRC1$ST$Str general √
12 DEVICE HEALTHY SP B701_99LVPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
13 TIME SYNCHRONISATION ERROR SP B701_99LVEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
14 OVERFLUX ALARM SP B701_99LVEXT$pdGGIO84$ST$SPCSO55:0 stVal √ √
15 GOOSE RECEIPT FAIL/TROUBLE SP B701_99LVCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
16 SETTINGS CHANGED √ √
17 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, Mechanical trips, alarms etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
400kV ICT- 99HV-(7UT85)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 400kV 400kV ICT 7UT85 TIME SYNCHRONISATION ERROR SP B701_87T_1_99HVApplication$LPHD0$ST$ClkFail stVal √ √
2 MAIN CB OPEN SP B701_87T_1_99HVApplication$USER1$ST$SPS stVal √
3 MAIN CB CLOSE SP B701_87T_1_99HVApplication$USER1$ST$SPS1 stVal √
4 REF PROTECTION OPERATED SP B701_87T_1_99HVApplication$USER1$ST$SPS11 stVal √ √
5 86 A/86 B RELAY OPERATED SP B701_87T_1_99HVApplication$USER1$ST$SPS12 stVal √ √
6 BUCHHOLZ 2 TRIP R-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS13 stVal √ √
7 BUCHHOLZ 2 TRIP Y-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS14 stVal √ √
8 BUCHHOLZ 2 TRIP B-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS15 stVal √ √
9 BUCHHOLZ 1 ALARM R-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS3 stVal √ √
10 BUCHHOLZ 1 ALARM Y-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS4 stVal √ √
11 BUCHHOLZ 1ALARM B-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS5 stVal √ √
12 BUCHHOLZ 1 ALARM SP-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS10 stVal √ √
13 TIE CB OPEN SP B701_87T_1_99HVApplication$USER1$ST$SPS2 stVal √
14 PRD1, 2 & 3 TRIP SP-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS6 stVal √ √
15 PRD1, 2 & 3 TRIP R-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS7 stVal √ √
16 PRD1, 2 & 3 TRIP Y-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS8 stVal √ √
17 PRD1, 2 & 3 TRIP B-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS9 stVal √ √
18 2nd HARMONIC BLOCK PH-R SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Irs2HaDet phsA √
19 2nd HARMONIC BLOCK PH-Y SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Irs2HaDet phsB √
20 2nd HARMONIC BLOCK PH-B SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Irs2HaDet phsC √
21 5th HARMONIC BLOCK PH-R SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Irs5HaDet phsA √
22 5th HARMONIC BLOCK PH-Y SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Irs5HaDet phsB √
23 5th HARMONIC BLOCK PH-B SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Irs5HaDet phsC √
24 DIFFERENTIAL TRIP SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Op general √ √
25 DIFFERENTIAL TRIP R-PH SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Op phsA √ √
26 DIFFERENTIAL TRIP Y-PH SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Op phsB √ √
27 DIFFERENTIAL TRIP B-PH SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Op phsC √ √
28 DIFFERENTIAL STAGE-1 TRIP SP general √ √
29 DIFFERENTIAL STAGE-1 PICKUP
30 DIFFERENTIAL STAGE-2 TRIP
31 DIFFERENTIAL STAGE-2 PICKUP
34 OVER FLUX TRIP SP B701_87T_1_99HVPTS1$PTRC1$ST$Op general √ √
35 OVERFLUX STAGE-2 TRIP SP B701_87T_1_99HVPTS1_24Overexcitation1$ODP_PVPH1$ST$Op general √ √
36 OVERFLUX STAGE-1 TRIP SP B701_87T_1_99HVPTS1_24Overexcitation1$ODP_PVPH2$ST$Op general √ √
37 OVERFLUX HV ALARM SP B701_87T_1_99HVEXT$pdGGIO84$ST$SPCSO55:0 stVal √ √
38 DEVICE HEALTHY SP B701_87T_1_99HVApplication$LPHD0$ST$PhyHealth:0 stVal:1 √
39 GOOSE RECEIPT FAIL/TROUBLE SP B701_87T_1_99HVApplication$USER1$ST$SPS16 stVal √ √
40 SETTINGS CHANGED √ √
41 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, Mechanical trips, alarms etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
400kV BUS REACTOR (7SA522)
Sr. No. Voltage Level Feeder Name Source
Signal Decription
INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Single Point)
1 400kV 400kV BUS REACTOR 7SA522 GOOSE RECEIPT FAIL/TROUBLE SP B403_21R_1CTRL$GGIO1$ST$SPCSO1:0 stVal √ √
2 WTI TRIP B-PH SP B403_21R_1CTRL$GGIO1$ST$SPCSO4:0 stVal √ √
3 WTI TRIP Y-PH SP B403_21R_1CTRL$GGIO1$ST$SPCSO2:0 stVal √ √
4 64.2-R_Y_B SP RELAY UNHEALTHY SP B403_21R_1CTRL$GGIO1$ST$SPCSO3:0 stVal √ √
5 TIME SYNCHRONISATION ERROR SP B403_21R_1EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
6 BACKUP IMPEDENCE ZONE-1 START SP B403_21R_1PROT$PDIS1$ST$Str general √
7 BACKUP IMPEDENCE ZONE-1 TRIP SP B403_21R_1PROT$PDIS1$ST$Op general √ √
8 BACKUP IMPEDENCE R-PH TRIP SP B403_21R_1PROT$PDIS1$ST$Op phsA √ √
9 BACKUP IMPEDENCE Y-PH TRIP SP B403_21R_1PROT$PDIS1$ST$Op phsB √ √
10 BACKUP IMPEDENCE B-PH TRIP SP B403_21R_1PROT$PDIS1$ST$Op phsC √ √
11 BACKUP IMPEDENCE BLOCKED SP B403_21R_1PROT$PDIS1$ST$Blk stVal √
12 GENERAL TRIP SP B403_21R_1PROT$PTRC1$ST$Tr general √ √
13 NON-DIRECTIONAL OVERCURRENT TRIP SP B403_21R_1PROT$PTOC2$ST$Op general √ √
14 NON-DIRECTIONAL OVERCURRENT START SP B403_21R_1PROT$PTOC2$ST$Str general √
15 DEVICE HEALTHY SP B403_21R_1PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
16 NO VOLTAGE IN LINE SP B403_21R_1EXT$pdGGIO3$ST$SPCSO40:0 stVal √ √
17 VT FUSE FAILURE SP B403_21R_1EXT$pdGGIO3$ST$SPCSO42:0 stVal √ √
18 SETTINGS CHANGED √ √
19 RELAY IN TEST MODE √ √
20 NON-DIRECTIONAL EARTHFAULT TRIP √ √
21 NON-DIRECTIONAL EARTHFAULT START √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
SIEMENS SCADA GENERAL SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (INDEX)
Sheet Ref. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 6MD66 BCU ICT BCU STNM4XXBCU BCU is for each bay so 4XX refers to Bay
2 7SJ80 7SJ8_64T.2B REF RELAY PHASE B FOR ICT STNM4XXTREFB Bay No. 4XX will be always the main bay number for the ICT feeder
3 7UT85 7UT85_99HV ICT DIFFERENTIAL RELAY STNM4XXTDIF Bay No. 4XX will be always the main bay number for the ICT feeder
4 7SA522 7SA522_21R ICT BACKUP IMPEDANCE RELAY STNM4XXTBUIMP Bay No. 4XX will be always the main bay number for the ICT feeder
NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "4XX" stand for Bay name, example if the bay no 401 then same has to be implemented like STNM401BCU
400kV LINE REACTOR-(BCU)
Sr. No. Voltage Level Feeder Name Source
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Double Point)
1 400kV 400kV LINE REACTOR BCU CB R-PH POSITION DP B707_BCUCBs3$XCBR1$ST$Pos:2 stVal √
2 CB Y-PH POSITION DP B707_BCUCBs1$XCBR1$ST$Pos:2 stVal √
3 CB B-PH POSITION DP B707_BCUCBs2$XCBR1$ST$Pos:2 stVal √
4 CB POSITION DP B707_BCUCB$CSWI1$ST$Pos:2 stVal √
5 89AE POSITION DP B707_BCU89AE$CSWI4$ST$Pos:2 stVal √
6 89BE POSITION DP B707_BCU89BE$CSWI5$ST$Pos:2 stVal √
7 89LRE1 POSITION DP B707_BCU89LE$CSWI7$ST$Pos:2 stVal √
8 89RE-B POSITION DP B707_BCU89REB$CSWI9$ST$Pos:2 stVal √
9 89RE-R POSITION DP B707_BCU89RER$CSWI9$ST$Pos:2 stVal √
10 89RE-Y POSITION DP B707_BCU89REY$CSWI9$ST$Pos:2 stVal √
11 89RSE1-B POSITION DP B707_BCU89RSE1B$CSWI11$ST$Pos:2 stVal √
12 89RSE1-R POSITION DP B707_BCU89RSE1R$CSWI11$ST$Pos:2 stVal √
13 89RSE1-Y POSITION DP B707_BCU89RSE1Y$CSWI11$ST$Pos:2 stVal √
14 89A POSITION DP B707_BCU89A$CSWI2$ST$Pos:2 stVal √
15 89B POSITION DP B707_BCU89B$CSWI3$ST$Pos:2 stVal √
16 89LR POSITION DP B707_BCU89L$CSWI6$ST$Pos:2 stVal √
17 89R-B POSITION DP B707_BCU89RB$CSWI8$ST$Pos:2 stVal √
18 89R-R POSITION DP B707_BCU89RR$CSWI8$ST$Pos:2 stVal √
19 89R-Y POSITION DP B707_BCU89RY$CSWI8$ST$Pos:2 stVal √
20 89RS1_RS2-B POSITION DP B707_BCU89RS1RS2B$CSWI10$ST$Pos:2 stVal √
21 89RS1_RS2-R POSITION DP B707_BCU89RS1RS2R$CSWI10$ST$Pos:2 stVal √
22 89RS1_RS2-Y POSITION DP B707_BCU89RS1RS2Y$CSWI10$ST$Pos:2 stVal √
S89R-R POSITION
S89R-Y POSITION
S89R-B POSITION
23 NGR CB POSITION DP B707_BCUNGRCB$CSWI1$ST$Pos:2 stVal √
25 BINARY INPUT (Single Point)
27 AUX POWER FAIL SP B707_BCUApplication$LPHD0$ST$AuxPwrFail stVal √ √
28 TIME SYNCHRONISATION ERROR SP B707_BCUApplication$LMTS0$ST$TmSynErr stVal √ √
29 GOOSE RECEIPT FAIL/TROUBLE SP B707_BCUApplication$LLN0$ST$SPS stVal √ √
30 BCU MODE SP B707_BCUApplication$LLN0$ST$LocKey stVal √
31 CB DC SUPPLY-1/2 FAIL SP B707_BCUApplication$USER3$ST$SPS1 stVal √ √
32 CB SPRING CHARGED B-PH SP B707_BCUApplication$USER3$ST$SPS4 stVal √
33 CB SPRING CHARGED R-PH SP B707_BCUApplication$USER3$ST$SPS2 stVal √
34 CB SPRING CHARGED Y-PH SP B707_BCUApplication$USER3$ST$SPS3 stVal √
35 CB SF6 GAS PRESSURE LOCKOUT SP B707_BCUApplication$USER3$ST$SPS stVal √ √
36 CT SF6 GAS PRESSURE REFILL LOW ALARM SP B707_BCUApplication$USER1$ST$SPS stVal √ √
37 CT SF6 GAS PRESSURE LOCKOUT SP B707_BCUApplication$USER1$ST$SPS1 stVal √ √
38 A/R BLOCK MAIN1-1 SP B707_BCUApplication$USER8$ST$SPS6 stVal √ √
39 A/R BLOCK MAIN-2 SP B707_BCUApplication$USER8$ST$SPS7 stVal √ √
40 SPARE REACTOR B-PH SELECTED SP B707_BCUApplication$USER8$ST$SPS2 stVal √
41 SPARE REACTOR R-PH SELECTED SP B707_BCUApplication$USER8$ST$SPS stVal √
42 SPARE REACTOR Y-PH SELECTED SP B707_BCUApplication$USER8$ST$SPS1 stVal √
43 SURGE ARRESTER B-PH SP B707_BCUApplication$USER8$ST$SPS5 stVal √
44 SURGE ARRESTER R-PH SP B707_BCUApplication$USER8$ST$SPS3 stVal √
45 SURGE ARRESTER Y-PH SP B707_BCUApplication$USER8$ST$SPS4 stVal √
46 86A TRIP RELAY SUPERVISION SP B707_BCUApplication$USER9$ST$SPS2 stVal √ √
47 86A TRIP RELAY OPERATED SP B707_BCUApplication$USER9$ST$SPS1 stVal √ √
48 86B TRIP RELAY SUPERVISION SP B707_BCUApplication$USER9$ST$SPS6 stVal √ √
49 86B TRIP RELAY OPERATED SP B707_BCUApplication$USER9$ST$SPS5 stVal √ √
50 CARRIER CHANNEL-1 OUT SP B707_BCUApplication$USER9$ST$SPS3 stVal √ √
51 CARRIER CHANNEL-2 OUT SP B707_BCUApplication$USER9$ST$SPS7 stVal √ √
52 MAIN-2 RELAY UNHEALTHY SP B707_BCUApplication$USER9$ST$SPS8 stVal √ √
53 EMERGENCY/MANUAL CB TRIP SP B707_BCUApplication$USER9$ST$SPS10 stVal √ √
54 MAIN TANK HIGH LEVEL ALARM B-PH SP B707_BCUApplication$USER9$ST$SPS25 stVal √ √
55 MAIN TANK HIGH LEVEL ALARM R-PH SP B707_BCUApplication$USER9$ST$SPS15 stVal √ √
56 MAIN TANK HIGH LEVEL ALARM Y-PH SP B707_BCUApplication$USER9$ST$SPS20 stVal √ √
57 MAIN TANK LOW LEVEL ALARM B-PH SP B707_BCUApplication$USER9$ST$SPS24 stVal √ √
58 MAIN TANK LOW LEVEL ALARM R-PH SP B707_BCUApplication$USER9$ST$SPS14 stVal √ √
59 MAIN TANK LOW LEVEL ALARM Y-PH SP B707_BCUApplication$USER9$ST$SPS19 stVal √ √
60 OTI ALARM B-PH SP B707_BCUApplication$USER9$ST$SPS23 stVal √ √
61 OTI ALARM R-PH SP B707_BCUApplication$USER9$ST$SPS13 stVal √ √
62 OTI ALARM Y-PH SP B707_BCUApplication$USER9$ST$SPS18 stVal √ √
63 SPEECH CHANNEL FAIL SP B707_BCUApplication$USER9$ST$SPS9 stVal √ √
64 CB TC-1 FAULTY SP B707_BCUApplication$USER9$ST$SPS stVal √ √
65 CB TC-2 FAULTY SP B707_BCUApplication$USER9$ST$SPS4 stVal √ √
66 WTI ALARM B-PH SP B707_BCUApplication$USER9$ST$SPS22 stVal √ √
67 WTI ALARM R-PH SP B707_BCUApplication$USER9$ST$SPS12 stVal √ √
68 WTI ALARM Y-PH SP B707_BCUApplication$USER9$ST$SPS17 stVal √ √
69 CB POLE DESCREPENCY ALARM SP B707_BCUApplication$USER2$ST$SPS1 stVal √ √
70 CB SF6 GAS PRESSURE REFILL LOW ALARM SP B707_BCUApplication$USER2$ST$SPS stVal √ √
71 TIME SYNCHRONISATION ERROR SP B707_BCUApplication$LTMS0$ST$TmSynErr stVal √ √
72 BUS-1 VT RESET SP B707_BCUApplication$USER11$ST$SPS1 stVal √
73 BUS-2 VT RESET SP B707_BCUApplication$USER11$ST$SPS3 stVal √
74 LINE VT RESET SP B707_BCUApplication$USER11$ST$SPS5 stVal √
75 BUS-1 VT SELECTED SP B707_BCUApplication$USER11$ST$SPS stVal √
76 BUS-2 VT SELECTED SP B707_BCUApplication$USER11$ST$SPS2 stVal √
77 LINE VT SELECTED SP B707_BCUApplication$USER11$ST$SPS4 stVal √
78 EMERGENCY/MANUAL CB CLOSE SP B707_BCUCB$GAPC2$ST$Detected stVal √
79 A/R FUNCTION ON SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$On stVal √
80 CB READY FOR A/R SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$AutoRecSt:0 stVal:1 √
81 A/R UNSUCCESSFUL SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$AutoRecSt:0 stVal:10 √ √
82 A/R SUCCESSFUL SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$Successful stVal √
83 CB NOT READY SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$CBnotRdy stVal √
84 A/R CLOSE COMMAND INDICATION SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$OpCls general √
85 A/R IN PROGRESS SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$RecInit stVal √
86 A/R FUNCTION OFF SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$Off stVal √
87 A/R FUNCTION ON SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$On stVal √
88 CB POSITION NO SYNC SP B707_BCUCB$CSWI1$ST$Pos noSync √
89 400kV 400kV LINE REACTOR BCU CB CLOSE INTERLOCK SP B707_BCUCB$CILO1$ST$EnaCls stVal √
90 89AE OPEN INTERLOCK SP B707_BCU89AE$CILO1$ST$EnaOpn stVal √
91 89BE OPEN INTERLOCK SP B707_BCU89BE$CILO1$ST$EnaOpn stVal √
92 89LE OPEN INTERLOCK SP B707_BCU89LE$CILO1$ST$EnaOpn stVal √
93 89RE-B-PH OPEN INTERLOCK SP B707_BCU89REB$CILO1$ST$EnaOpn stVal √
94 89RE-R-PH OPEN INTERLOCK SP B707_BCU89RER$CILO1$ST$EnaOpn stVal √
95 89RE-Y-PH OPEN INTERLOCK SP B707_BCU89REY$CILO1$ST$EnaOpn stVal √
96 89RSE1-B-PH OPEN INTERLOCK SP B707_BCU89RSE1B$CILO1$ST$EnaOpn stVal √
97 89RSE1-R-PH OPEN INTERLOCK SP B707_BCU89RSE1R$CILO1$ST$EnaOpn stVal √
98 89RSE1-Y-PH OPEN INTERLOCK SP B707_BCU89RSE1Y$CILO1$ST$EnaOpn stVal √
99 89A-PH OPEN INTERLOCK SP B707_BCU89A$CILO1$ST$EnaOpn stVal √
100 89B-PH OPEN INTERLOCK SP B707_BCU89B$CILO1$ST$EnaOpn stVal √
101 89L-PH OPEN INTERLOCK SP B707_BCU89L$CILO1$ST$EnaOpn stVal √
102 89R-B-PH OPEN INTERLOCK SP B707_BCU89RB$CILO1$ST$EnaOpn stVal √
103 89R-R-PH OPEN INTERLOCK SP B707_BCU89RR$CILO1$ST$EnaOpn stVal √
104 89R-Y-PH OPEN INTERLOCK SP B707_BCU89RY$CILO1$ST$EnaOpn stVal √
105 89RS1_RS2-B-PH OPEN INTERLOCK SP B707_BCU89RS1RS2B$CILO1$ST$EnaOpn stVal √
106 89RS1_RS2-R-PH OPEN INTERLOCK SP B707_BCU89RS1RS2R$CILO1$ST$EnaOpn stVal √
107 89RS1_RS2-Y-PH OPEN INTERLOCK SP B707_BCU89RS1RS2Y$CILO1$ST$EnaOpn stVal √
108 NGR CB CLOSE INTERLOCK SP B707_BCUNGRCB$CILO1$ST$EnaCls stVal √
109 RELAY IN TEST MODE √ √
110 SETTINGS CHANGED √ √
111 REACTOR-n R PH OUT OF SERVICE √
112 REACTOR-n Y PH OUT OF SERVICE √
113 REACTOR-n B PH OUT OF SERVICE √
114 REACTOR SPARE PH IN SERVICE IN REACTOR-N √
115 CB MANUAL TRIP √
116 CB MANUAL CLOSE √
117 BUSBAR OPERATED √ √
118 BCU IN LOCAL/REMOTE √
119 CB TC-1 R-PHASE FAULTY √ √
120 CB TC-1 Y-PHASE FAULTY √ √
121 CB TC-1 B-PHASE FAULTY √ √
122 CB TC-2 R-PHASE FAULTY √ √
123 CB TC-2 Y-PHASE FAULTY √ √
124 CB TC-2 B-PHASE FAULTY √ √
125 NGR CB TC-1 FAULTY
125 NGR CB TC-2 FAULTY
125 NGR CB DC FAULTY
125 NGR CB AC FAULTY
125 NGR CB SPRING NOT CHARGED
125 NGR CB SF6 GAS LOW
125 NGR CB SF6 CB TROUBLE ALARM
125 NGR MECHANICAL TRIPPING IF ASSIGNED
127 MEASUREMENTS
129 POWER FACTOR ME_FL B707_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotPF:1 mag$f
130 FREQUENCY ME_FL B707_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$Hz:1 mag$f
131 ACTIVE POWER ME_FL B707_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotW:1 mag$f
132 REACTIVE POWER ME_FL B707_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVAr:1 mag$f
133 APPARENT POWER ME_FL B707_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVA:1 mag$f
134 I-R-PH CURRENT ME_FL B707_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsA$cVal$mag$f
135 I-Y-PH CURRENT ME_FL B707_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsB$cVal$mag$f
136 I-B-PH CURRENT ME_FL B707_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsC$cVal$mag$f
137 R-Y VOLTAGE ME_FL B707_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsAB$cVal$mag$f
138 Y-B VOLTAGE ME_FL B707_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsBC$cVal$mag$f
139 B-R VOLYAGE ME_FL B707_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsCA$cVal$mag$f
143 CB CONTROL DC B707_BCUCB$CSWI1$CO$Pos:8 Oper$ctlVal √
144 89AE CONTROL DC B707_BCU89AE$CSWI4$CO$Pos:8 Oper$ctlVal √
145 89BE CONTROL DC B707_BCU89BE$CSWI5$CO$Pos:8 Oper$ctlVal √
146 89LE CONTROL DC B707_BCU89LE$CSWI7$CO$Pos:8 Oper$ctlVal √
147 89RE-B CONTROL DC B707_BCU89REB$CSWI9$CO$Pos:8 Oper$ctlVal √
148 89RE-R CONTROL DC B707_BCU89RER$CSWI9$CO$Pos:8 Oper$ctlVal √
149 89RE-Y CONTROL DC B707_BCU89REY$CSWI9$CO$Pos:8 Oper$ctlVal √
150 89RSE1-B CONTROL DC B707_BCU89RSE1B$CSWI11$CO$Pos:8 Oper$ctlVal √
151 89RSE1-R CONTROL DC B707_BCU89RSE1R$CSWI11$CO$Pos:8 Oper$ctlVal √
152 89RSE1-Y CONTROL DC B707_BCU89RSE1Y$CSWI11$CO$Pos:8 Oper$ctlVal √
153 89A CONTROL DC B707_BCU89A$CSWI2$CO$Pos:8 Oper$ctlVal √
154 89B CONTROL DC B707_BCU89B$CSWI3$CO$Pos:8 Oper$ctlVal √
155 89L CONTROL DC B707_BCU89L$CSWI6$CO$Pos:8 Oper$ctlVal √
156 89R-B CONTROL DC B707_BCU89RB$CSWI8$CO$Pos:8 Oper$ctlVal √
157 89R-R CONTROL DC B707_BCU89RR$CSWI8$CO$Pos:8 Oper$ctlVal √
158 89R-Y CONTROL DC B707_BCU89RY$CSWI8$CO$Pos:8 Oper$ctlVal √
159 89RS1_RS2-B CONTROL DC B707_BCU89RS1RS2B$CSWI10$CO$Pos:8 Oper$ctlVal √
160 89RS1_RS2-R CONTROL DC B707_BCU89RS1RS2R$CSWI10$CO$Pos:8 Oper$ctlVal √
161 89RS1_RS2-Y CONTROL DC B707_BCU89RS1RS2Y$CSWI10$CO$Pos:8 Oper$ctlVal √
162 NGR CB CONTROL DC B707_BCUNGRCB$CSWI1$CO$Pos:8 Oper$ctlVal √
163 CB CONTROL NO SYNC SC B707_BCUCB$CSWI1$CO$Pos Oper$noSync √
164 NGR CB CONTROL NO SYNC SC B707_BCUNGRCB$CSWI1$CO$Pos Oper$noSync √
165 86B TRIP RELAY RESET COMMAND SC B707_BCUApplication$USER2$CO$SPC:8 Oper$ctlVal √
166 86A TRIP RELAY RESET COMMAND SC B707_BCUApplication$USER2$CO$SPC1:8 Oper$ctlVal √
167 A/R ON CONTROL SC B707_BCUApplication$USER12$CO$SPC:8 Oper$ctlVal √
168 A/R OFF CONTROL SC B707_BCUApplication$USER12$CO$SPC1:8 Oper$ctlVal √
Note: 1. All the switchgear status signals as per the actual primary equipment status. 2. Additional signal for CB Trouble, etc as per scheme 3. 10 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 4. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 5. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
400kV LINE REACTOR-(7SA52)
Sr. No. Voltage Level Feeder Name Source
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION REMARKS Events Alarms
BINARY INPUT (Single Point)
1 400kV Line Reactor 7SA522 WTI TRIP B-PH SP B407_21R_1CTRL$GGIO1$ST$SPCSO2:0 stVal √ √
2 WTI TRIP Y-PH SP B407_21R_1CTRL$GGIO1$ST$SPCSO1:0 stVal √ √
3 OTI TRIP B-PH SP B407_64R_2CTRL$GGIO1$ST$SPCSO4:0 stVal √ √
4 OTI TRIP R-PH SP B407_64R_2CTRL$GGIO1$ST$SPCSO5:0 stVal √ √
5 BUCHHOLZ-1/2 TRIP R-PH SP B407_21R_1CTRL$GGIO1$ST$SPCSO3:0 stVal √ √
6 BUCHHOLZ-1/2 TRIP Y-PH SP B407_21R_1CTRL$GGIO1$ST$SPCSO6:0 stVal √ √
7 BUCHHOLZ-1/2 TRIP B-PH SP B407_21R_1CTRL$xGGIO1$ST$SPCSO7:0 stVal √ √
9 BCU-1/2 RELAY FAIL
10 REACTOR DC-2 FAIL
11 GROUP-B PROTECTION RELAY FAIL
12 BACKUP IMPEDENCE ZONE-1 PICKUP SP B407_21R_1PROT$PDIS1$ST$Str general √
13 BACKUP IMPEDENCE ZONE-1 TRIP SP B407_21R_1PROT$PDIS1$ST$Op general √ √
14 BACKUP IMPEDENCE R-PH TRIP SP B407_21R_1PROT$PDIS1$ST$Op phsA √ √
15 BACKUP IMPEDENCE Y-PH TRIP SP B407_21R_1PROT$PDIS1$ST$Op phsB √ √
16 BACKUP IMPEDENCE B-PH TRIP SP B407_21R_1PROT$PDIS1$ST$Op phsC √ √
17 GENERAL TRIP SP B407_21R_1PROT$PTRC1$ST$Tr general √ √
18 BACKUP IMPEDENCE BLOCKED SP B407_21R_1PROT$PDIS1$ST$Blk stVal √
19 DEVICE HEALTHY SP B407_21R_1PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
20 GOOSE RECEIPT FAIL/TROUBLE SP B407_21R_1CTRL$GGIO1$ST$SPCSO8:0 stVal √ √
21 VOLTAGE ABSENT SP B407_21R_1EXT$pdGGIO3$ST$SPCSO40:0 stVal √ √
22 VT FUSE FAILURE SP B407_21R_1EXT$pdGGIO3$ST$SPCSO42:0 stVal √ √
23 TIME SYNCHRONISATION ERROR SP B407_21R_2EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
24 BROKEN CONDUCTOR SP B407_21R_1EXT$pdGGIO4$ST$SPCSO3:0 stVal √ √
25 NON-DIRECTIONAL OVERCURRENT TRIP SP B407_21R_1PROT$PTOC2$ST$Op general √ √
26 NON-DIRECTIONAL OVERCURRENT START SP B407_21R_1PROT$PTOC2$ST$Str general √
27 NON-DIRECTIONAL EARTHFAULT TRIP √ √
28 NON-DIRECTIONAL EARTHFAULT START √
29 SETTINGS CHANGED √
30 RELAY IN TEST MODE √
31 NGR CLOSE COMMAND BY E/F PICKUP(5 SEC) √ √
32 NGR CLOSE COMMAND BY MECH TRIP √ √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
400kV LINE REACTOR-(7SJ80)
Sr. No. Voltage Level Feeder Name Source NOTE: THESE SIGNAL STANDARDIZATION IS SCHEME BASED
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION Events Alarms
BINARY INPUT (Single Point)
1 400kV 400kV LINE REACTOR 7SJ80 BUCHHOLZ TRIP B-PH SP B707_64R_2CTRL$GGIO1$ST$SPCSO5:0 stVal √ √
2 BUCHHOLZ TRIP R-PH SP B707_64R_2CTRL$GGIO1$ST$SPCSO1:0 stVal √ √
3 BUCHHOLZ TRIP Y-PH SP B707_64R_2CTRL$GGIO1$ST$SPCSO3:0 stVal √ √
4 OTI TRIP Y-PH SP B707_64R_2CTRL$GGIO1$ST$SPCSO4:0 stVal √ √
5 REF STAGE 1 TRIP SP B707_64R_2PROT$PTOC16$ST$Op general √ √
6 REF STAGE 1 PICKUP SP B707_64R_2PROT$PTOC16$ST$Str general √
7 REF STAGE 2 TRIP SP B707_64R_2PROT$PTOC17$ST$Op general √ √
8 REF STAGE 2 PICKUP SP B707_64R_2PROT$PTOC17$ST$Str general √
9 GENERAL TRIP SP B707_64R_2PROT$PTRC1$ST$Tr general √ √
10 DEVICE HEALTHY SP B707_64R_2PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
11 GOOSE RECEIPT FAIL/TROUBLE SP B707_64R_2CTRL$GGIO1$ST$SPCSO7:0 stVal √ √
12 NGR THERMAL OVERLOAD TRIP SP B707_64R_2PROT$PTTR1$ST$OP stVal √ √
13 TIME SYNCHRONISATION ERROR SP B707_64R_2EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
14 SETTINGS CHANGED √
15 RELAY IN TEST MODE √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
400kV LINE REACTOR-(7UT)
Sr. No. Voltage Level Feeder Name Source NOTE: THESE SIGNAL STANDARDIZATION IS SCHEME BASED
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION Events Alarms
BINARY INPUT (Single Point)
1 400kV 400kV LINE REACTOR 7UT PRV-1 TRIP B-PH(NO) SP stVal √ √
2 PRV-1 TRIP R-PH(NO) SP stVal √ √
3 PRV-1 TRIP Y-PH(NO) SP stVal √ √
4 PRV-1 TRIP B-PH(NC) SP stVal √ √
5 PRV-1 TRIP R-PH(NC) SP stVal √ √
6 PRV-1 TRIP Y-PH(NC) SP stVal √ √
7 PRV-2 TRIP B-PH(NO) SP stVal √ √
8 PRV-2 TRIP R-PH(NO) SP stVal √ √
9 PRV-2 TRIP Y-PH(NO) SP stVal √ √
10 PRV-2 TRIP B-PH(NC) SP stVal √ √
11 PRV-2 TRIP R-PH(NC) SP stVal √ √
12 PRV-2 TRIP Y-PH(NC) SP stVal √ √
13 PRV-1 TRIP B-PH SP stVal √ √
14 PRV-1 TRIP R-PH SP stVal √ √
15 PRV-1 TRIP Y-PH SP stVal √ √
16 PRV-2 TRIP B-PH SP stVal √ √
17 PRV-2 TRIP R-PH SP stVal √ √
18 PRV-2 TRIP Y-PH SP stVal √ √
19 WTI TRIP R-PH SP stVal √ √
20 DIFFERENTIAL TRIP R-PH SP B707_87R_1EXT$pdGGIO89$ST$SPCSO40:0 stVal √ √
21 DIFFERENTIAL TRIP Y-PH SP B707_87R_1EXT$pdGGIO89$ST$SPCSO41:0 stVal √ √
22 DIFFERENTIAL TRIP B-PH SP B707_87R_1EXT$pdGGIO89$ST$SPCSO42:0 stVal √ √
23 DIFFERENTIAL STAGE 1 OPERATED SP B707_87R_1PROT$PDIF1$ST$Op general √ √
24 DIFFERENTIAL STAGE 1 PICKUP SP B707_87R_1PROT$PDIF1$ST$Str general √
25 DIFFERENTIAL STAGE 2 OPERATED SP B707_87R_1PROT$PDIF2$ST$Op general √ √
26 DIFFERENTIAL STAGE 2 PICKUP SP B707_87R_1PROT$PDIF2$ST$Str general √
27 GENERAL TRIP SP B707_87R_1PROT$PTRC1$ST$Tr general √ √
28 DEVICE HEALTHY SP B707_87R_1PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
29 GOOSE RECEIPT FAIL/TROUBLE SP B707_87R_1CTRL$GGIO1$ST$SPCSO5:0 stVal √ √
30 TIME SYNCHRONISATION ERROR SP B707_87R_1EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
31 SETTINGS CHANGED √
32 RELAY IN TEST MODE √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
SIEMENS SCADA GENERAL SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (INDEX)
Sheet Ref. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 6MD66 BCU LINE BCU STNM4XXLBCU BCU is for each bay so 4XX refers to Bay
2 7SA522 7SA522_21M1 LINE DISTANCE MAIN-1 STNM4XXL21M1 Bay No. 4XX will be always the main bay number for the ICT feeder
3 7SD522 7SD522_87M1 LINE DIFFERENTIAL/DISTANCE MAIN-2 STNM4XXL87M1 Bay No. 4XX will be always the main bay number for the ICT feeder
NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "4XX" stand for Bay name, example if the bay no 401 then same has to be implemented like STNM401BCU
Sr. No. Voltage Level Feeder Name
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Double Point)
1 400kV 400kV LINE CB B-PH POSITION DP B706_BCUCBB$XCBR1$ST$Pos:2 stVal √
2 CB R-PH POSITION DP B706_BCUCBR$XCBR1$ST$Pos:2 stVal √
3 CB Y-PH POSITION DP B706_BCUCBY$XCBR1$ST$Pos:2 stVal √
4 CB POSITION DP B706_BCUCB$CSWI1$ST$Pos:2 stVal √
5 89AE1 POSITION DP B706_BCU89AE1$CSWI3$ST$Pos:2 stVal √
6 89AE2 POSITION DP B706_BCU89AE2$CSWI8$ST$Pos:2 stVal √
7 89BE POSITION DP B706_BCU89BE$CSWI5$ST$Pos:2 stVal √
8 89A POSITION DP B706_BCU89A$CSWI2$ST$Pos:2 stVal √
9 89B POSITION DP B706_BCU89B$CSWI4$ST$Pos:2 stVal √
10 89L POSITION DP B706_BCU89L$CSWI6$ST$Pos:2 stVal √
11 89LE POSITION DP B706_BCU89LE$CSWI7$ST$Pos:2 stVal √
12 89 BE1 POSITION
13 89 BE2 POSITION
14 THE LOGICAL NODE FOR BUS EARTH SWITCHES, ISOLATOR & EARTHSWITCHES FOR 3 PH/1PH REACTORS & ITCs, e.g 89 BR, BRE, LR, LRE, RS1, RS2, RS1E, 89T,TE, 89AE2, 89BE2 MAY BE ASSIGNED AS PER AVAILABILITY/SCHEME
15 BINARY INPUT (Single Point)
17 AUX POWER FAIL SP B706_BCUApplication$LPHD0$ST$AuxPwrFail stVal √ √
18 TIME SYNCHRONISATION ERROR SP B706_BCUApplication$LMTS0$ST$TmSynErr stVal √ √
19 BCU MODE SP B706_BCUApplication$LLN0$ST$LocKey stVal √
22 CT SF6 GAS PRESSURE REFILL LOW ALARM SP B706_BCUApplication$USER1$ST$SPS stVal √ √
23 CT SF6 GAS PRESSURE LOCKOUT SP B706_BCUApplication$USER1$ST$SPS1 stVal √ √
24 TRIP RELAY SUPERVISION SP B706_BCUApplication$USER5$ST$SPS stVal √ √
25 CARRIER CHANNEL-2 OUT SP B706_BCUApplication$USER5$ST$SPS1 stVal √ √
26 MAIN-2 RELAY FAULTY SP B706_BCUApplication$USER5$ST$SPS2 stVal √ √
27 EMERGENCY/MANUAL TRIP SP B706_BCUApplication$USER5$ST$SPS4 stVal √ √
28 SPEECH CHANNEL FAIL SP B706_BCUApplication$USER5$ST$SPS3 stVal √ √
29 SURGE ARRESTER B-PH SP B706_BCUApplication$USER5$ST$SPS7 stVal √ √
30 SURGE ARRESTER R-PH SP B706_BCUApplication$USER5$ST$SPS5 stVal √ √
31 SURGE ARRESTER Y-PH SP B706_BCUApplication$USER5$ST$SPS6 stVal √ √
32 89A POLE DESCREPENCY SP B706_BCUApplication$USER3$ST$SPS5 stVal √ √
33 89B POLE DESCREPENCY SP B706_BCUApplication$USER3$ST$SPS6 stVal √ √
34 CB DC SUPPLY-1/2 FAIL SP B706_BCUApplication$USER3$ST$SPS1 stVal √ √
35 CB SPRING NOT CHARGED B-PH SP B706_BCUApplication$USER3$ST$SPS4 stVal √ √
36 CB SPRING NOT CHARGED R-PH SP B706_BCUApplication$USER3$ST$SPS2 stVal √ √
37 CB SPRING NOT CHARGED Y-PH SP B706_BCUApplication$USER3$ST$SPS3 stVal √ √
38 CB SF6 GAS PRESSURE LOCKOUT SP B706_BCUApplication$USER3$ST$SPS stVal √ √
39 86B TRIP RELAY FAULTY SP B706_BCUApplication$USER4$ST$SPS3 stVal √ √
40 86A TRIP RELAY FAULTY SP B706_BCUApplication$USER4$ST$SPS3 stVal √ √
41 86A TRIP RELAY OPERATED SP B706_BCUApplication$USER4$ST$SPS2 stVal √ √
42 86B TRIP RELAY OPERATED SP B706_BCUApplication$USER4$ST$SPS6 stVal √ √
43 89L POLE DESCREPENCY SP B706_BCUApplication$USER4$ST$SPS stVal √ √
44 CARRIER CHANNEL-1 OUT SP B706_BCUApplication$USER4$ST$SPS4 stVal √ √
45 CB TC-1 R-PHASE FAULTY
46 CB TC-1 Y-PHASE FAULTY
47 CB TC-1 B-PHASE FAULTY
48 CB TC-2 R-PHASE FAULTY
49 CB TC-2 Y-PHASE FAULTY SP B706_BCUApplication$USER4$ST$SPS1 stVal √ √
50 CB TC-2 B-PHASE FAULTY SP B706_BCUApplication$USER4$ST$SPS5 stVal √ √
51 CB POLE DESCREPENCY OPTD-1
52 CB POLE DESCREPENCY OPTD-2 SP B706_BCUApplication$USER2$ST$SPS1 stVal √ √
53 CB SF6 GAS PRESSURE REFILL LOW ALARM SP B706_BCUApplication$USER2$ST$SPS stVal √ √
54 BUS-1 VT SELECTED SP B706_BCUApplication$USER6$ST$SPS1 stVal √
55 ICT LV VT SELECTED SP B706_BCUApplication$USER6$ST$SPS2 stVal √
56 LINE VT SELECTED SP B706_BCUApplication$USER6$ST$SPS stVal √
57 CB READY SP B706_BCUCB$XCBR1$ST$Rdy stVal √
58 EMERGENCY/MANUAL CB CLOSE SP B706_BCUCB$GAPC2$ST$Detected stVal √
59 DEVICE HEALTHY SP B706_BCUApplication$LPHD0$ST$PhyHealth:0 stVal:1 √
60 CB POSITION NO SYNC SP B706_BCUCB$CSWI1$ST$Pos noSync √ √
61 CB CLOSE INTERLOCK SP B706_BCUCB$CILO1$ST$EnaCls stVal √ √
62 765kV 765kV LINE 89AE1 OPEN INTERLOCK SP B706_BCU89AE1$CILO3$ST$EnaOpn stVal √ √
63 89AE2 OPEN INTERLOCK SP B706_BCU89AE2$CILO8$ST$EnaOpn stVal √ √
64 89BE OPEN INTERLOCK SP B706_BCU89BE$CILO5$ST$EnaOpn stVal √ √
65 89A OPEN INTERLOCK SP B706_BCU89A$CILO2$ST$EnaOpn stVal √ √
66 89B OPEN INTERLOCK SP B706_BCU89B$CILO4$ST$EnaOpn stVal √ √
67 89L OPEN INTERLOCK SP B706_BCU89L$CILO6$ST$EnaOpn stVal √ √
68 89LE OPEN INTERLOCK SP B706_BCU89LE$CILO7$ST$EnaOpn stVal √ √
71 BUSBAR 7ES-B1 OPEN(BUS EARTH SWITCH)
72 BUSBAR 7ES-B2 OPEN(BUS EARTH SWITCH)
73 BUSBAR 7ES-B1 CLOSE INTERLOCK
74 BUSBAR 7ES-B2 CLOSE INTERLOCK
75 GOOSE RECEIPT FAIL/TROUBLE SP B706_BCUApplication$USER6$ST$SPS3 stVal √ √
76 DFR/DR FAIL ALARM
77 GOOSE RECEIPT FAIL/TROUBLE SP B706_BCUApplication$LLN0$ST$SPS stVal √
78 A/R BLOCK SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$BlkFct stVal √
79 A/R FUNCTION OFF SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$Off stVal √
80 A/R FUNCTION ON SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$On stVal √
81 A/R READY SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$AutoRecSt:0 stVal:1 √
82 A/R UNSUCCESSFUL SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$AutoRecSt:0 stVal:10 √ √
84 A/R SUCCESSFUL SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$Successful stVal √
85 RECLAIM IN PROGRESS
86 MAIN A/R LOCKOUT
87 TIE A/R LOCKOUT
88 Tie CB A/R PRIORITY CLOSE
89 MAIN/TIE BCU HEALTHY
90 AR SINGLE PHASE TRIP PERMITTED
91 CB NOT READY SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$CBnotRdy stVal √
92 A/R CLOSE COMMAND INDICATION SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$OpCls general √
93 A/R IN PROGRESS SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$RecInit stVal √
94 RELAY IN TEST MODE
95 SETTINGS CHANGED
96 CB MANUAL TRIP
97 CB MANUAL CLOSE
98 BUSBAR OPERATED
99 BCU IN LOCAL/REMOTE
100 MEASUREMENT
102 POWER FACTOR ME_FL B706_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotPF:1 mag$f
103 FREQUENCY ME_FL B706_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$Hz:1 mag$f
104 ACTIVE POWER ME_FL B706_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotW:1 mag$f
105 REACTIVE POWER ME_FL B706_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVAr:1 mag$f
106 APPARENT POWER ME_FL B706_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVA:1 mag$f
107 I-R-PH CURRENT ME_FL B706_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsA$cVal$mag$f
108 I-Y-PH CURRENT ME_FL B706_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsB$cVal$mag$f
109 I-B-PH CURRENT ME_FL B706_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsC$cVal$mag$f
110 R-Y VOLTAGE ME_FL B706_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsAB$cVal$mag$f
111 Y-B VOLTAGE ME_FL B706_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsBC$cVal$mag$f
112 B-R VOLYAGE ME_FL B706_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsCA$cVal$mag$f
113 CB-B-PH COUNTER ME_I B706_BCUCBB$XCBR1$ST$OpCnt stVal
114 CB-R-PH COUNTER ME_I B706_BCUCBR$XCBR1$ST$OpCnt stVal
115 CB-Y-PH COUNTER ME_I B706_BCUCBY$XCBR1$ST$OpCnt stVal
116 SURGE ARRESTER B-PH ME_I
117 SURGE ARRESTER R-PH ME_I
118 SURGE ARRESTER Y-PH ME_I
119 CB R-PHASE OPERATION COUNTER ME_I
120 CB Y-PHASE OPERATION COUNTER ME_I
121 CB B-PHASE OPERATION COUNTER ME_I
125 CB CONTROL DC B706_BCUCB$CSWI1$CO$Pos:8 Oper$ctlVal √
126 89AE1 CONTROL DC B706_BCU89AE1$CSWI3$CO$Pos:8 Oper$ctlVal √
127 89AE2 CONTROL DC B706_BCU89AE2$CSWI8$CO$Pos:8 Oper$ctlVal √
128 89BE CONTROL DC B706_BCU89BE$CSWI5$CO$Pos:8 Oper$ctlVal √
129 89A CONTROL DC B706_BCU89A$CSWI2$CO$Pos:8 Oper$ctlVal √
130 89B CONTROL DC B706_BCU89B$CSWI4$CO$Pos:8 Oper$ctlVal √
131 89L CONTROL DC B706_BCU89L$CSWI6$CO$Pos:8 Oper$ctlVal √
132 89LE CONTROL DC B706_BCU89LE$CSWI7$CO$Pos:8 Oper$ctlVal √
133 CB CONTROL NO SYNC SC B706_BCUCB$CSWI1$CO$Pos Oper$noSync √
134 86A TRIP RELAY RESET COMMAND SC B706_BCUApplication$USER2$CO$SPC:8 Oper$ctlVal √
135 86B TRIP RELAY RESET COMMAND SC B706_BCUApplication$USER2$CO$SPC1:8 Oper$ctlVal √
136 A/R ON CONTROL SC B706_BCUApplication$USER8$CO$SPC:8 Oper$ctlVal √
137 A/R OFF CONTROL SC B706_BCUApplication$USER8$CO$SPC1:8 Oper$ctlVal √
138 MAIN-1 LED RESET SC
139 MAIN-2 LED RESET SC
140 SETTINGS CHANGED
141 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Feeder Name Assumed as Main-1 relay
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION EVENT ALARM
1 400kV 400kV LINE FAULT DISTANCE ME_FL B706_21_1PROT$RFLO1$MX$FltDiskm:0 mag$f
2 FAULT CURRENT ME_FL
3 FAULT LOCATION DISTANCE ME_FL
4 MAIN-1 CARRIER RECEIVE CHANNEL-1 ME_I
5 MAIN-1 CARRIER SEND CHANNEL-1 ME_I
6 MAIN-2 CARRIER RECEIVE CHANNEL-1 ME_I
7 MAIN-2 CARRIER SEND CHANNEL-1 ME_I
8 MAIN-2 CARRIER RECEIVE CHANNEL-2 ME_I
9 MAIN-2 CARRIER SEND CHANNEL-2 ME_I
10 MAIN-1 CARRIER RECEIVE CHANNEL-2 ME_I
11 MAIN-1 CARRIER SEND CHANNEL-2 ME_I
12 DT RECEIVE CHANNEL-1 ME_I
13 DT SEND CHANNEL-1 ME_I
14 DT RECEIVE CHANNEL-2 ME_I
15 DT SEND CHANNEL-2 ME_I
16 CARRIER FAIL CHANNEL-1 ME_I
17 CARRIER FAIL CHANNEL-2 ME_I
18 CARRIER RECEIVED CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO3:0 stVal
19 CARRIER RECEIVED CHANNEL-2 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO4:0 stVal
20 CARRIER SEND CHANNEL-2 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO1:0 stVal
21 CARRIER SEND CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO2:0 stVal
22 DIRECT TRIP RECEIVED CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO6:0 stVal
23 DIRECT TRIP SEND CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO5:0 stVal
24 CARRIER FAIL CHANNEL-1 ME_I B706_21_1CTRL$GGIO2$ST$ISCSO7:0 stVal
25 CARRIER FAIL CHANNEL-2 ME_I B706_21_1CTRL$GGIO2$ST$ISCSO8:0 stVal
27 BINARY INPUT (Single Point)
28 DIRECT TRIP SEND CHANNEL-2 GOOSE
29 CARRIER FAIL CHANNEL-1 SP B706_21_1CTRL$GGIO1$ST$SPCSO25:0 stVal √ √
30 NO VOLTAGE IN LINE SP B706_21_1CTRL$GGIO1$ST$SPCSO21:0 stVal √ √
31 A/R BLOCK SP B706_21_1CTRL$GGIO1$ST$SPCSO14:0 stVal √
32 MAIN A/R LOCKOUT
33 TIE A/R LOCKOUT
34 DIRECT TRIP SEND CHANNEL-1 SP B706_21_1CTRL$GGIO1$ST$SPCSO18:0 stVal √ √
35 GOOSE RECEIPT FAIL/TROUBLE SP B706_21_1CTRL$GGIO1$ST$SPCSO24:0 stVal √ √
36 MAIN-2 RELAY FAIL SP B706_21_1CTRL$GGIO1$ST$SPCSO20:0 stVal √
37 89L OPEN FOR STUB SP B706_21_1CTRL$GGIO1$ST$SPCSO17:0 stVal √ √
38 DIRECT TRIP RECEIVED CHANNEL-1 SP B706_21_1CTRL$GGIO1$ST$SPCSO16:0 stVal √ √
39 LBB OPERATED SP B706_21_1CTRL$GGIO1$ST$SPCSO10:0 stVal √ √
40 TIME SYNCHRONISATION ERROR SP B706_21_1EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
41 VT FUSE FAILURE SP B706_21_1EXT$pdGGIO3$ST$SPCSO42:0 stVal √ √
42 BROKEN CONDUCTOR SP B706_21_1EXT$pdGGIO4$ST$SPCSO3:0 stVal √ √
43 EMERGENCY/MANUAL CLOSE SP B706_21_1EXT$pdGGIO6$ST$SPCSO36:0 stVal √
44 CARRIER RECEIVED CHANNEL-1 SP B706_21_1EXT$pdGGIO63$ST$SPCSO38:0 stVal √ √
45 CARRIER RECEIVED CHANNEL-2 SP B706_21_1EXT$pdGGIO63$ST$SPCSO42:0 stVal √ √
46 CARRIER FAULTY SP B706_21_1EXT$pdGGIO63$ST$SPCSO37:0 stVal √ √ NOT REQUIRED
47 SOTF PICKUP SP B706_21_1EXT$pdGGIO67$ST$SPCSO57:0 stVal √
48 SOTF TRIP( OC)
49 SOTF TRIP( IMPEDANCE Z1B) SP B706_21_1EXT$pdGGIO68$ST$SPCSO7:0 stVal √ √
50 CARRIER SEND CHANNEL-1 SP B706_21_1PROT$PSCH1$ST$ProTx stVal √ √
51 CARRIER SEND CHANNEL-2 GOOSE
52 DIRECT TRIP RECEIVED CHANNEL-2 GOOSE
53 CARRIER RECEIVED SP B706_21_1PROT$PSCH1$ST$ProRx stVal √ √ NOT REQUIRED
54 CARRIER ADDIED TRIP/Z COM. TRIP SP B706_21_1PROT$PSCH1$ST$Op general √ √
55 MAIN A/R OPTD
56 TIE A/R OPTD
57 CB MANUAL CLOSE
58 CB MANUAL TRIP
59 86 GROUP-A OPTD
60 86 GROUP-B OPTD
61 MAIN A/R START
62 TIE A/R START
63 DISTANCE ZONE-1 PICKUP SP B706_21_1PROT$PDIS1$ST$Str general √
64 DISTANCE PROTN ZONE-1 TRIP SP B706_21_1PROT$PDIS1$ST$Op general √ √
65 DISTANCE PROTN ZONE-1 R-PH TRIP SP B706_21_1PROT$PDIS1$ST$Op phsA √ √
66 DISTANCE PROTN ZONE-1 Y-PH TRIP SP B706_21_1PROT$PDIS1$ST$Op phsB √ √
67 DISTANCE PROTN ZONE-1 B-PH TRIP SP B706_21_1PROT$PDIS1$ST$Op phsC √ √
68 DISTANCE ZONE-2 PICKUP SP B706_21_1PROT$PDIS2$ST$Str general √
69 DISTANCE PROTN ZONE-2 TRIP SP B706_21_1PROT$PDIS2$ST$Op general √ √
70 DISTANCE PROTN ZONE-2 R-PH TRIP SP B706_21_1PROT$PDIS2$ST$Op phsA √ √
71 DISTANCE PROTN ZONE-2 Y-PH TRIP SP B706_21_1PROT$PDIS2$ST$Op phsB √ √
72 DISTANCE PROTN ZONE-2 B-PH TRIP SP B706_21_1PROT$PDIS2$ST$Op phsC √ √
73 DISTANCE ZONE-3 PICKUP SP B706_21_1PROT$PDIS3$ST$Str general √
74 DISTANCE PROTN ZONE-3 TRIP SP B706_21_1PROT$PDIS3$ST$Op general √ √
75 DISTANCE ZONE-4 PICKUP SP B706_21_1PROT$PDIS4$ST$Str general √
76 DISTANCE PROTN ZONE-4 TRIP SP B706_21_1PROT$PDIS4$ST$Op general √ √
77 DISTANCE PROTN ZONE-4 R-PH TRIP
78 DISTANCE PROTN ZONE-4 Y-PH TRIP
79 DISTANCE PROTN ZONE-4 B-PH TRIP
80 DISTANCE PROTN ZONE-1B PICKUP SP B706_21_1PROT$PDIS10$ST$Str general √
81 DISTANCE PROTN ZONE-1B TRIP SP B706_21_1PROT$PDIS10$ST$Op general √ √
82 DISTANCE PROTN ZONE-1B B-PH TRIP SP B706_21_1PROT$PDIS10$ST$Op phsC √ √
83 DISTANCE PROTN ZONE-1B R-PH TRIP SP B706_21_1PROT$PDIS10$ST$Op phsA √ √
84 DISTANCE PROTN ZONE-1B Y-PH TRIP SP B706_21_1PROT$PDIS10$ST$Op phsB √ √
85 DISTANCE PROTN ZONE-5 PICKUP
86 STUB PICKUP SP B706_21_1PROT$PTOC4$ST$Str general √
87 STUB OPERATED SP B706_21_1PROT$PTOC4$ST$Op general √ √
88 DEF FAULT PICKUP SP B706_21_1PROT$PTOC8$ST$Str general √
89 DEF FAULT TRIP SP B706_21_1PROT$PTOC8$ST$Op general √ √
90 OVERVOLTAGE STAGE-1-PH-N PICKUP SP B706_21_1PROT$PTOV1$ST$Str general √
91 OVERVOLTAGE STAGE-1 -PH-N TRIP SP B706_21_1PROT$PTOV1$ST$Op general √ √
92 OVERVOLTAGE STAGE-2-PH-N PICKUP SP B706_21_1PROT$PTOV2$ST$Str general √
93 OVERVOLTAGE STAGE-2-PH-N TRIP SP B706_21_1PROT$PTOV2$ST$Op general √ √
94 OVERVOLTAGE STAGE-1-PH-PH PICKUP SP B706_21_1PROT$PTOV3$ST$Str general √
95 OVERVOLTAGE STAGE-1-PH-PH TRIP SP B706_21_1PROT$PTOV3$ST$Op general √ √
96 OVERVOLTAGE STAGE-2-PH-PH PICKUP SP B706_21_1PROT$PTOV4$ST$Str general √
97 OVERVOLTAGE STAGE-2-PH-PH TRIP SP B706_21_1PROT$PTOV4$ST$Op general √ √
98 POWER SWING ZONE-1 DETECTED SP B706_21_1PROT$RPSB1$ST$Str general √ √
99 POWER SWING ZONE-1 BLOCK SP B706_21_1PROT$RPSB1$ST$BlkZn stVal √
100 POWER SWING ZONE-1B DETECTED SP B706_21_1PROT$RPSB10$ST$Str general √ √
101 POWER SWING ZONE-1B BLOCK SP B706_21_1PROT$RPSB10$ST$BlkZn stVal √
102 POWER SWING ZONE-2 DETECTED SP B706_21_1PROT$RPSB2$ST$Str general √ √
103 POWER SWING ZONE-2 BLOCK SP B706_21_1PROT$RPSB2$ST$BlkZn stVal √
104 POWER SWING ZONE-3 DETECTED SP B706_21_1PROT$RPSB3$ST$Str general √ √
105 POWER SWING ZONE-3 BLOCK SP B706_21_1PROT$RPSB3$ST$BlkZn stVal √
106 POWER SWING ZONE-4 DETECTED SP B706_21_1PROT$RPSB4$ST$Str general √ √
107 POWER SWING ZONE-4 BLOCK SP B706_21_1PROT$RPSB4$ST$BlkZn stVal √
108 BUSBAR PROTN OPTD
109 RELAY LED RESET SC
110 MAIN BCU FAIL
111 TIE BCU FAIL
112 MANUAL DR TRIGGER SC
113 GENERAL TRIP SP B706_21_1PROT$PTRC1$ST$Tr general √ √
114 DEVICE HEALTHY SP B707_21_1PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
115 MAIN-2 PROTN OPTD
116 STUB BLOCKED SP B706_21_1PROT$PTOC4$ST$Blk stVal √ √
117 SETTINGS CHANGED
118 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Feeder Name Assumed as Main-1 relay
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION EVENT ALARM
1 400kV 400kV LINE FAULT DISTANCE ME_FL B706_21_1PROT$RFLO1$MX$FltDiskm:0 mag$f
2 FAULT CURRENT ME_FL
3 FAULT LOCATION DISTANCE ME_FL
4 MAIN-1 CARRIER RECEIVE CHANNEL-1 ME_I
5 MAIN-1 CARRIER SEND CHANNEL-1 ME_I
6 MAIN-2 CARRIER RECEIVE CHANNEL-1 ME_I
7 MAIN-2 CARRIER SEND CHANNEL-1 ME_I
8 MAIN-2 CARRIER RECEIVE CHANNEL-2 ME_I
9 MAIN-2 CARRIER SEND CHANNEL-2 ME_I
10 MAIN-1 CARRIER RECEIVE CHANNEL-2 ME_I
11 MAIN-1 CARRIER SEND CHANNEL-2 ME_I
12 DT RECEIVE CHANNEL-1 ME_I
13 DT SEND CHANNEL-1 ME_I
14 DT RECEIVE CHANNEL-2 ME_I
15 DT SEND CHANNEL-2 ME_I
16 CARRIER FAIL CHANNEL-1 ME_I
17 CARRIER FAIL CHANNEL-2 ME_I
18 CARRIER RECEIVED CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO3:0 stVal
19 CARRIER RECEIVED CHANNEL-2 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO4:0 stVal
20 CARRIER SEND CHANNEL-2 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO1:0 stVal
21 CARRIER SEND CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO2:0 stVal
22 DIRECT TRIP RECEIVED CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO6:0 stVal
23 DIRECT TRIP SEND CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO5:0 stVal
24 CARRIER FAIL CHANNEL-1 ME_I B706_21_1CTRL$GGIO2$ST$ISCSO7:0 stVal
25 CARRIER FAIL CHANNEL-2 ME_I B706_21_1CTRL$GGIO2$ST$ISCSO8:0 stVal
27 BINARY INPUT (Single Point)
28 LINE DIFFERENTIAL GENERAL TIP
29 LINE DIFFERENTIAL REMOTE TRIP
30 LINE DIFFERENTIAL R-PH TRIP
31 LINE DIFFERENTIAL Y-PH TRIP
32 LINE DIFFERENTIAL -PH TRIP
33 LINE COMMUNICATION CHANNEL-1 FAULTY
34 LINE COMMUNICATION CHANNEL-2 FAULTY
35 DIRECT TRIP SEND CHANNEL-2 GOOSE
36 CARRIER FAIL CHANNEL-1 SP B706_21_1CTRL$GGIO1$ST$SPCSO25:0 stVal √ √
37 NO VOLTAGE IN LINE SP B706_21_1CTRL$GGIO1$ST$SPCSO21:0 stVal √ √
38 A/R BLOCK SP B706_21_1CTRL$GGIO1$ST$SPCSO14:0 stVal √
39 MAIN A/R LOCKOUT
40 TIE A/R LOCKOUT
41 DIRECT TRIP SEND CHANNEL-1 SP B706_21_1CTRL$GGIO1$ST$SPCSO18:0 stVal √ √
42 GOOSE RECEIPT FAIL/TROUBLE SP B706_21_1CTRL$GGIO1$ST$SPCSO24:0 stVal √ √
43 MAIN-2 RELAY FAIL SP B706_21_1CTRL$GGIO1$ST$SPCSO20:0 stVal √
44 89L OPEN FOR STUB SP B706_21_1CTRL$GGIO1$ST$SPCSO17:0 stVal √ √
45 DIRECT TRIP RECEIVED CHANNEL-1 SP B706_21_1CTRL$GGIO1$ST$SPCSO16:0 stVal √ √
46 LBB OPERATED SP B706_21_1CTRL$GGIO1$ST$SPCSO10:0 stVal √ √
47 TIME SYNCHRONISATION ERROR SP B706_21_1EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
48 VT FUSE FAILURE SP B706_21_1EXT$pdGGIO3$ST$SPCSO42:0 stVal √ √
49 BROKEN CONDUCTOR SP B706_21_1EXT$pdGGIO4$ST$SPCSO3:0 stVal √ √
50 EMERGENCY/MANUAL CLOSE SP B706_21_1EXT$pdGGIO6$ST$SPCSO36:0 stVal √
51 CARRIER RECEIVED CHANNEL-1 SP B706_21_1EXT$pdGGIO63$ST$SPCSO38:0 stVal √ √
52 CARRIER RECEIVED CHANNEL-2 SP B706_21_1EXT$pdGGIO63$ST$SPCSO42:0 stVal √ √
53 CARRIER FAULTY SP B706_21_1EXT$pdGGIO63$ST$SPCSO37:0 stVal √ √ NOT REQUIRED
54 SOTF PICKUP SP B706_21_1EXT$pdGGIO67$ST$SPCSO57:0 stVal √
55 SOTF TRIP( OC)
56 SOTF TRIP( IMPEDANCE Z1B) SP B706_21_1EXT$pdGGIO68$ST$SPCSO7:0 stVal √ √
57 CARRIER SEND CHANNEL-1 SP B706_21_1PROT$PSCH1$ST$ProTx stVal √ √
58 CARRIER SEND CHANNEL-2 GOOSE
59 DIRECT TRIP RECEIVED CHANNEL-2 GOOSE
60 CARRIER RECEIVED SP B706_21_1PROT$PSCH1$ST$ProRx stVal √ √ NOT REQUIRED
61 CARRIER ADDIED TRIP/Z COM. TRIP SP B706_21_1PROT$PSCH1$ST$Op general √ √
62 MAIN A/R OPTD
63 TIE A/R OPTD
64 CB MANUAL CLOSE
65 CB MANUAL TRIP
66 86 GROUP-A OPTD
67 86 GROUP-B OPTD
68 MAIN A/R START
69 TIE A/R START
70 DISTANCE ZONE-1 PICKUP SP B706_21_1PROT$PDIS1$ST$Str general √
71 DISTANCE PROTN ZONE-1 TRIP SP B706_21_1PROT$PDIS1$ST$Op general √ √
72 DISTANCE PROTN ZONE-1 R-PH TRIP SP B706_21_1PROT$PDIS1$ST$Op phsA √ √
73 DISTANCE PROTN ZONE-1 Y-PH TRIP SP B706_21_1PROT$PDIS1$ST$Op phsB √ √
74 DISTANCE PROTN ZONE-1 B-PH TRIP SP B706_21_1PROT$PDIS1$ST$Op phsC √ √
75 DISTANCE ZONE-2 PICKUP SP B706_21_1PROT$PDIS2$ST$Str general √
76 DISTANCE PROTN ZONE-2 TRIP SP B706_21_1PROT$PDIS2$ST$Op general √ √
77 DISTANCE PROTN ZONE-2 R-PH TRIP SP B706_21_1PROT$PDIS2$ST$Op phsA √ √
78 DISTANCE PROTN ZONE-2 Y-PH TRIP SP B706_21_1PROT$PDIS2$ST$Op phsB √ √
79 DISTANCE PROTN ZONE-2 B-PH TRIP SP B706_21_1PROT$PDIS2$ST$Op phsC √ √
80 DISTANCE ZONE-3 PICKUP SP B706_21_1PROT$PDIS3$ST$Str general √
81 DISTANCE PROTN ZONE-3 TRIP SP B706_21_1PROT$PDIS3$ST$Op general √ √
82 DISTANCE ZONE-4 PICKUP SP B706_21_1PROT$PDIS4$ST$Str general √
83 DISTANCE PROTN ZONE-4 TRIP SP B706_21_1PROT$PDIS4$ST$Op general √ √
84 DISTANCE PROTN ZONE-4 R-PH TRIP
85 DISTANCE PROTN ZONE-4 Y-PH TRIP
86 DISTANCE PROTN ZONE-4 B-PH TRIP
87 DISTANCE PROTN ZONE-1B PICKUP SP B706_21_1PROT$PDIS10$ST$Str general √
88 DISTANCE PROTN ZONE-1B TRIP SP B706_21_1PROT$PDIS10$ST$Op general √ √
89 DISTANCE PROTN ZONE-1B B-PH TRIP SP B706_21_1PROT$PDIS10$ST$Op phsC √ √
90 DISTANCE PROTN ZONE-1B R-PH TRIP SP B706_21_1PROT$PDIS10$ST$Op phsA √ √
91 DISTANCE PROTN ZONE-1B Y-PH TRIP SP B706_21_1PROT$PDIS10$ST$Op phsB √ √
92 DISTANCE PROTN ZONE-5 PICKUP
93 STUB PICKUP SP B706_21_1PROT$PTOC4$ST$Str general √
94 STUB OPERATED SP B706_21_1PROT$PTOC4$ST$Op general √ √
95 DEF FAULT PICKUP SP B706_21_1PROT$PTOC8$ST$Str general √
96 DEF FAULT TRIP SP B706_21_1PROT$PTOC8$ST$Op general √ √
97 OVERVOLTAGE STAGE-1-PH-N PICKUP SP B706_21_1PROT$PTOV1$ST$Str general √
98 OVERVOLTAGE STAGE-1 -PH-N TRIP SP B706_21_1PROT$PTOV1$ST$Op general √ √
99 OVERVOLTAGE STAGE-2-PH-N PICKUP SP B706_21_1PROT$PTOV2$ST$Str general √
100 OVERVOLTAGE STAGE-2-PH-N TRIP SP B706_21_1PROT$PTOV2$ST$Op general √ √
101 OVERVOLTAGE STAGE-1-PH-PH PICKUP SP B706_21_1PROT$PTOV3$ST$Str general √
102 OVERVOLTAGE STAGE-1-PH-PH TRIP SP B706_21_1PROT$PTOV3$ST$Op general √ √
103 OVERVOLTAGE STAGE-2-PH-PH PICKUP SP B706_21_1PROT$PTOV4$ST$Str general √
104 OVERVOLTAGE STAGE-2-PH-PH TRIP SP B706_21_1PROT$PTOV4$ST$Op general √ √
105 POWER SWING ZONE-1 DETECTED SP B706_21_1PROT$RPSB1$ST$Str general √ √
106 POWER SWING ZONE-1 BLOCK SP B706_21_1PROT$RPSB1$ST$BlkZn stVal √
107 POWER SWING ZONE-1B DETECTED SP B706_21_1PROT$RPSB10$ST$Str general √ √
108 POWER SWING ZONE-1B BLOCK SP B706_21_1PROT$RPSB10$ST$BlkZn stVal √
109 POWER SWING ZONE-2 DETECTED SP B706_21_1PROT$RPSB2$ST$Str general √ √
110 POWER SWING ZONE-2 BLOCK SP B706_21_1PROT$RPSB2$ST$BlkZn stVal √
111 POWER SWING ZONE-3 DETECTED SP B706_21_1PROT$RPSB3$ST$Str general √ √
112 POWER SWING ZONE-3 BLOCK SP B706_21_1PROT$RPSB3$ST$BlkZn stVal √
113 POWER SWING ZONE-4 DETECTED SP B706_21_1PROT$RPSB4$ST$Str general √ √
114 POWER SWING ZONE-4 BLOCK SP B706_21_1PROT$RPSB4$ST$BlkZn stVal √
115 BUSBAR PROTN OPTD
116 RELAY LED RESET SC
117 MAIN BCU FAIL
118 TIE BCU FAIL
119 MANUAL DR TRIGGER SC
120 GENERAL TRIP SP B706_21_1PROT$PTRC1$ST$Tr general √ √
121 DEVICE HEALTHY SP B707_21_1PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
122 MAIN-2 PROTN OPTD
123 STUB BLOCKED SP B706_21_1PROT$PTOC4$ST$Blk stVal √ √
124 SETTINGS CHANGED
125 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
SIEMENS SCADA GENERAL SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (INDEX)
Sheet Ref. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 7SS52 MCU-1 BUSBAR MAIN-1 STNM4XXBB1M1 BCU is for each bay so 4XX refers to Bay
4 7SS52 MCU-2 BUSBAR MAIN-1 STNM4XXBB1M2 Bay No. 4XX will be always the main bay number for the ICT feeder
NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "4XX" stand for Bay name, example if the bay no 701 then same has to be implemented like STNM701BCU
Sr. No. Voltage Level Source NAME ( 400KV MCU-1)
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION Event Alarm Remarks
BINARY INPUT (Double Point)
1 400kV MCU-1 DC SOURCE-2 FAIL SP MCU_II_400kVCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
2 MCU-2 UNHEALTHY SP MCU_II_400kVCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
3 BREAKER FAILURE TRANSFER TRIP SP MCU_II_400kVEXT$pdGGIO164$ST$SPCSO1:0 stVal √ √
4 TIME SYNCHRONISATION ERROR SP MCU_II_400kVEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
5 BUSBAR TRIP SP MCU_II_400kVPROT$PDIF1$ST$Op general √ √
6 BAY UNIT-01 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO1:0 stVal √ √
7 BAY UNIT-02 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO8:0 stVal √ √
8 BAY UNIT-03 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO16:0 stVal √ √
9 BAY UNIT-03 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO24:0 stVal √ √
10 BAY UNIT-05 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO33:0 stVal √ √
11 BAY UNIT-06 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO41:0 stVal √ √
12 BAY UNIT-07 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO49:0 stVal √ √
13 BAY UNIT-08 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO57:0 stVal √ √
14 BUS-1 PROTECTION BLOCKED BY HANDLE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO9:0 stVal √ √
15 BUS-2 PROTECTION BLOCKED BY HANDLE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO26:0 stVal √ √
16 BUS-1 PROTECTION BLOCKED BY INTERM STATE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO17:0 stVal √ √
17 BUS-2 PROTECTION BLOCKED BY INTERM STATE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO33:0 stVal √ √
18 CURRENT SUPERVISION BUS-1 SP MCU_II_400kVPROT$GGIO2$ST$SPCSO10:0 stVal √ √
19 CURRENT SUPERVISION BUS-2 SP MCU_II_400kVPROT$GGIO2$ST$SPCSO27:0 stVal √ √
20 Trip command BF for BUS-1 R-PH SP MCU_II_400kVPROT$GGIO2$ST$SPCSO5:0 stVal √ √
21 Trip command BF for BUS-1 Y-PH SP MCU_II_400kVPROT$GGIO2$ST$SPCSO6:0 stVal √ √
22 Trip command BF for BUS-1 B-PH SP MCU_II_400kVPROT$GGIO2$ST$SPCSO7:0 stVal √ √
23 Trip command BF for BUS-2 R-PH SP MCU_II_400kVPROT$GGIO2$ST$SPCSO22:0 stVal √ √
24 Trip command BF for BUS-2 Y-PH SP MCU_II_400kVPROT$GGIO2$ST$SPCSO23:0 stVal √ √
25 Trip command BF for BUS-2 B-PH SP MCU_II_400kVPROT$GGIO2$ST$SPCSO24:0 stVal √ √
26 3-PH Trip command BF for BUS-1 SP MCU_II_400kVPROT$GGIO2$ST$SPCSO1:0 stVal √ √
27 3-PH Trip command BF for BUS-2 SP MCU_II_400kVPROT$GGIO2$ST$SPCSO18:0 stVal √ √
28 LBB RETRIP SP MCU_II_400kVPROT$RBRF1$ST$OpIn general √ √
29 LBB TRIP SP MCU_II_400kVPROT$RBRF1$ST$OpEx general √ √
30 GENERAL TRIP SP MCU_II_400kVPROT$PTRC1$ST$Tr general √ √
31 GENERAL TRIP R-PH SP MCU_II_400kVPROT$PTRC1$ST$Tr phsA √ √
32 GENERAL TRIP Y-PH SP MCU_II_400kVPROT$PTRC1$ST$Tr phsB √ √
33 GENERAL TRIP B-PH SP MCU_II_400kVPROT$PTRC1$ST$Tr phsC √ √
34 DEVICE OK SP MCU_II_400kVPROT$LPHD1$ST$PhyHealth:0 stVal:1 √ √
35 BAY UNIT-01 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO34:0 stVal √ √
36 BAY UNIT-02 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO35:0 stVal √ √
37 BAY UNIT-03 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO36:0 stVal √ √
38 BAY UNIT-04 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO37:0 stVal √ √
39 BAY UNIT-05 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO38:0 stVal √ √
40 BAY UNIT-06 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO39:0 stVal √ √
41 BAY UNIT-07 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO40:0 stVal √ √
42 BAY UNIT-08 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO41:0 stVal √ √
43 Trip repeat Bay Unit-01 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO2:0 stVal √ √
44 Trip repeat Bay Unit-01 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO3:0 stVal √ √
45 Trip repeat Bay Unit-01 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO4:0 stVal √ √
46 Trip repeat Bay Unit-02 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO9:0 stVal √ √
47 Trip repeat Bay Unit-02 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO10:0 stVal √ √
48 Trip repeat Bay Unit-02 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO11:0 stVal √ √
49 Trip repeat Bay Unit-03 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO17:0 stVal √ √
50 Trip repeat Bay Unit-03 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO18:0 stVal √ √
51 Trip repeat Bay Unit-03 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO19:0 stVal √ √
52 Trip repeat Bay Unit-04 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO25:0 stVal √ √
53 Trip repeat Bay Unit-04 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO26:0 stVal √ √
54 Trip repeat Bay Unit-04 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO27:0 stVal √ √
55 Trip repeat Bay Unit-05 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO34:0 stVal √ √
56 Trip repeat Bay Unit-05 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO35:0 stVal √ √
57 Trip repeat Bay Unit-05 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO36:0 stVal √ √
58 Trip repeat Bay Unit-06 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO42:0 stVal √ √
59 Trip repeat Bay Unit-06 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO43:0 stVal √ √
60 Trip repeat Bay Unit-06 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO44:0 stVal √ √
61 Trip repeat Bay Unit-07 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO50:0 stVal √ √
62 Trip repeat Bay Unit-07 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO51:0 stVal √ √
63 Trip repeat Bay Unit-07 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO52:0 stVal √ √
64 Trip repeat Bay Unit-08 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO58:0 stVal √ √
65 Trip repeat Bay Unit-08 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO59:0 stVal √ √
66 Trip repeat Bay Unit-08 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO60:0 stVal √ √
67 Transfer Trip BUS-1 SP MCU_II_400kVPROT$GGIO2$ST$SPCSO8:0 stVal √ √
68 Transfer Trip BUS-2 SP MCU_II_400kVPROT$GGIO2$ST$SPCSO25:0 stVal √ √
69 BUS ZONE 1 TRIP SP MCU_II_400kVPROT$GGIO2$ST$SPCSO28:0 stVal √ √
70 BUS ZONE 2 TRIP SP MCU_II_400kVPROT$GGIO2$ST$SPCSO24:0 stVal √ √
71 BUSBAR CHECKZONE ALARM
72 BUSBAR CHECKZONE TRIP
73 BREAKER FAILURE - BUSBAR 1 BLOCKED
74 BREAKER FAILURE - BUSBAR 2 BLOCKED
75 ISOLATOR IN INTERMEDIATE STATUS
77 BUSBAR BLOCKED DUE TO COMMUNICATION ERROR_Bay_n
78 BAY_N_BREAKER FAILURE R-PH INITIATION
79 BAY_N_BREAKER FAILURE Y-PH INITIATION
80 BAY_N_BREAKER FAILURE B-PH INITIATION
81 BAY_N_BREAKER FAILURE 3PH INITIATION
82 BAY_N_EXTERNAL BUSBAR ZONE n
83 BAY_N_BREAKER FAILURE RETRIP
84 BAY_N_BREAKER FAILURE BACKTRIP
85 BAY_N_BREAKER FAILURE RPH- RETRIP
86 BAY_N_BREAKER FAILURE YPH- RETRIP
87 BAY_N_BREAKER FAILURE BPH- RETRIP
88 BBP CENTRAL UNIT IED UNHEALTHY
89 SETTING CHANGE
90 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Source NAME ( 400KV MCU-2)
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION Event Alarm Remarks
BINARY INPUT (Double Point)
1 400kV MCU-1 DC SOURCE-1 FAIL SP MCU_II_400kVCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
2 MCU-1 UNHEALTHY SP MCU_II_400kVCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
3 BREAKER FAILURE TRANSFER TRIP SP MCU_II_400kVEXT$pdGGIO164$ST$SPCSO1:0 stVal √ √
4 TIME SYNCHRONISATION ERROR SP MCU_II_400kVEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
5 BUSBAR TRIP SP MCU_II_400kVPROT$PDIF1$ST$Op general √ √
6 BAY UNIT-01 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO1:0 stVal √ √
7 BAY UNIT-02 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO8:0 stVal √ √
8 BAY UNIT-03 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO16:0 stVal √ √
9 BAY UNIT-04 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO24:0 stVal √ √
10 BAY UNIT-05 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO33:0 stVal √ √
11 BAY UNIT-06 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO41:0 stVal √ √
12 BAY UNIT-07 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO49:0 stVal √ √
13 BAY UNIT-08 FAILURE SP MCU_II_400kVPROT$GGIO1$ST$SPCSO57:0 stVal √ √
14 BUS-1 PROTECTION BLOCKED BY HANDLE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO9:0 stVal √ √
15 BUS-2 PROTECTION BLOCKED BY HANDLE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO26:0 stVal √ √
16 BUS-1 PROTECTION BLOCKED BY INTERM STATE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO17:0 stVal √ √
17 BUS-2 PROTECTION BLOCKED BY INTERM STATE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO33:0 stVal √ √
18 CURRENT SUPERVISION BUS-1 SP MCU_II_400kVPROT$GGIO2$ST$SPCSO10:0 stVal √ √
19 CURRENT SUPERVISION BUS-2 SP MCU_II_400kVPROT$GGIO2$ST$SPCSO27:0 stVal √ √
20 Trip command BF for BUS-1 R-PH SP MCU_II_400kVPROT$GGIO2$ST$SPCSO5:0 stVal √ √
21 Trip command BF for BUS-1 Y-PH SP MCU_II_400kVPROT$GGIO2$ST$SPCSO6:0 stVal √ √
22 Trip command BF for BUS-1 B-PH SP MCU_II_400kVPROT$GGIO2$ST$SPCSO7:0 stVal √ √
23 Trip command BF for BUS-2 R-PH SP MCU_II_400kVPROT$GGIO2$ST$SPCSO22:0 stVal √ √
24 Trip command BF for BUS-2 Y-PH SP MCU_II_400kVPROT$GGIO2$ST$SPCSO23:0 stVal √ √
25 Trip command BF for BUS-2 B-PH SP MCU_II_400kVPROT$GGIO2$ST$SPCSO24:0 stVal √ √
26 3-PH Trip command BF for BUS-1 SP MCU_II_400kVPROT$GGIO2$ST$SPCSO1:0 stVal √ √
27 3-PH Trip command BF for BUS-2 SP MCU_II_400kVPROT$GGIO2$ST$SPCSO18:0 stVal √ √
28 LBB RETRIP SP MCU_II_400kVPROT$RBRF1$ST$OpIn general √ √
29 LBB TRIP SP MCU_II_400kVPROT$RBRF1$ST$OpEx general √ √
30 GENERAL TRIP SP MCU_II_400kVPROT$PTRC1$ST$Tr general √ √
31 GENERAL TRIP R-PH SP MCU_II_400kVPROT$PTRC1$ST$Tr phsA √ √
32 GENERAL TRIP Y-PH SP MCU_II_400kVPROT$PTRC1$ST$Tr phsB √ √
33 GENERAL TRIP B-PH SP MCU_II_400kVPROT$PTRC1$ST$Tr phsC √ √
34 DEVICE OK SP MCU_II_400kVPROT$LPHD1$ST$PhyHealth:0 stVal:1 √ √
35 BAY UNIT-01 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO34:0 stVal √ √
36 BAY UNIT-02 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO35:0 stVal √ √
37 BAY UNIT-03 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO36:0 stVal √ √
38 BAY UNIT-04 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO37:0 stVal √ √
39 BAY UNIT-05 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO38:0 stVal √ √
40 BAY UNIT-06 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO39:0 stVal √ √
41 BAY UNIT-07 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO40:0 stVal √ √
42 BAY UNIT-08 OUT OF SERVICE SP MCU_II_400kVPROT$GGIO2$ST$SPCSO41:0 stVal √ √
43 Trip repeat Bay Unit-01 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO2:0 stVal √ √
44 Trip repeat Bay Unit-01 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO3:0 stVal √ √
45 Trip repeat Bay Unit-01 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO4:0 stVal √ √
46 Trip repeat Bay Unit-02 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO9:0 stVal √ √
47 Trip repeat Bay Unit-02 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO10:0 stVal √ √
48 Trip repeat Bay Unit-02 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO11:0 stVal √ √
49 Trip repeat Bay Unit-03 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO17:0 stVal √ √
50 Trip repeat Bay Unit-03 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO18:0 stVal √ √
51 Trip repeat Bay Unit-03 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO19:0 stVal √ √
52 Trip repeat Bay Unit-04 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO25:0 stVal √ √
53 Trip repeat Bay Unit-04 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO26:0 stVal √ √
54 Trip repeat Bay Unit-04 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO27:0 stVal √ √
55 Trip repeat Bay Unit-05 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO34:0 stVal √ √
56 Trip repeat Bay Unit-05 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO35:0 stVal √ √
57 Trip repeat Bay Unit-05 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO36:0 stVal √ √
58 Trip repeat Bay Unit-06 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO42:0 stVal √ √
59 Trip repeat Bay Unit-06 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO43:0 stVal √ √
60 Trip repeat Bay Unit-06 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO44:0 stVal √ √
61 Trip repeat Bay Unit-07 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO50:0 stVal √ √
62 Trip repeat Bay Unit-07 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO51:0 stVal √ √
63 Trip repeat Bay Unit-07 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO52:0 stVal √ √
64 Trip repeat Bay Unit-08 R-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO58:0 stVal √ √
65 Trip repeat Bay Unit-08 Y-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO59:0 stVal √ √
66 Trip repeat Bay Unit-08 B-PH SP MCU_II_400kVPROT$GGIO1$ST$SPCSO60:0 stVal √ √
67 Transfer Trip BUS-1 SP MCU_II_400kVPROT$GGIO2$ST$SPCSO8:0 stVal √ √
68 Transfer Trip BUS-2 SP MCU_II_400kVPROT$GGIO2$ST$SPCSO25:0 stVal √ √
69 BUS ZONE 1 TRIP SP MCU_II_400kVPROT$GGIO2$ST$SPCSO28:0 stVal √ √
70 BUS ZONE 2 TRIP SP MCU_II_400kVPROT$GGIO2$ST$SPCSO24:0 stVal √ √
71 BUSBAR CHECKZONE ALARM
72 BUSBAR CHECKZONE TRIP
73 BREAKER FAILURE - BUSBAR 1 BLOCKED
74 BREAKER FAILURE - BUSBAR 2 BLOCKED
75 ISOLATOR IN INTERMEDIATE STATUS
77 BUSBAR BLOCKED DUE TO COMMUNICATION ERROR_Bay_n
78 BAY_N_BREAKER FAILURE R-PH INITIATION
79 BAY_N_BREAKER FAILURE Y-PH INITIATION
80 BAY_N_BREAKER FAILURE B-PH INITIATION
81 BAY_N_BREAKER FAILURE 3PH INITIATION
82 BAY_N_EXTERNAL BUSBAR ZONE n
83 BAY_N_BREAKER FAILURE RETRIP
84 BAY_N_BREAKER FAILURE BACKTRIP
85 BAY_N_BREAKER FAILURE RPH- RETRIP
86 BAY_N_BREAKER FAILURE YPH- RETRIP
87 BAY_N_BREAKER FAILURE BPH- RETRIP
88 BBP CENTRAL UNIT IED UNHEALTHY
89 SETTING CHANGE
90 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
SIEMENS SCADA GENERAL SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (INDEX)
Sheet Ref. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 6MD66 BCU TIE BCU STNM4XXTBCU BCU is for each bay so 4XX refers to Bay
4 7VK61 7VK_50ZT TIE STAND ALONE LBB RELAY STNM4XXTBFR Bay No. 4XX will be always the main bay number for the ICT feeder
NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "4XX" stand for Bay name, example if the bay no 401 then same has to be implemented like STNM401BCU
Sr. No. Voltage Level Feeder Name INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Double Point)
1 400kV 400kV TIE CB R-PH POSITION DP B702_BCUCBB$XCBR1$ST$Pos:2 stVal √
2 CB Y-PH POSITION DP B702_BCUCBR$XCBR1$ST$Pos:2 stVal √
3 CB B-PH POSITION DP B702_BCUCBY$XCBR1$ST$Pos:2 stVal √
4 CB POSITION DP B702_BCUCB$CSWI1$ST$Pos:2 stVal √
5 89AE POSITION DP B702_BCU89AE$CSWI3$ST$Pos:2 stVal √
6 89BE POSITION DP B702_BCU89BE$CSWI5$ST$Pos:2 stVal √
7 89A POSITION DP B702_BCU89A$CSWI2$ST$Pos:2 stVal √
8 89B POSITION DP B702_BCU89B$CSWI4$ST$Pos:2 stVal √
10 BINARY INPUT (Single Point)
12 AUX POWER FAIL SP B702_BCUApplication$LPHD0$ST$AuxPwrFail stVal √ √
13 TIME SYNCHRONISATION ERROR SP B702_BCUApplication$LMTS0$ST$TmSynErr stVal √ √
14 BCU MODE SP B702_BCUApplication$LLN0$ST$LocKey stVal √
15 CT SF6 GAS PRESSURE REFILL LOW ALARM SP B702_BCUApplication$USER1$ST$SPS stVal √ √
16 CT SF6 GAS PRESSURE LOCKOUT SP B702_BCUApplication$USER1$ST$SPS1 stVal √ √
17 CB DC SUPPLY-1/2 FAIL SP B702_BCUApplication$USER3$ST$SPS1 stVal √ √
18 CB SPRING NOT CHARGED B-PH SP B702_BCUApplication$USER3$ST$SPS4 stVal √
19 CB SPRING NOT CHARGED R-PH SP B702_BCUApplication$USER3$ST$SPS2 stVal √
20 CB SPRING NOT CHARGED Y-PH SP B702_BCUApplication$USER3$ST$SPS3 stVal √
21 CB SF6 GAS PRESSURE LOCKOUT SP B702_BCUApplication$USER3$ST$SPS stVal √ √
22 MAIN DC-1 SUPPLY Fail SP B702_BCUApplication$USER3$ST$SPS5 stVal √ √
23 89A POLE DESCREPENCY SP B702_BCUApplication$USER4$ST$SPS stVal √ √
24 89B POLE DESCREPENCY SP B702_BCUApplication$USER4$ST$SPS1 stVal √ √
25 86A TRIP RELAY SUPERVISION SP B702_BCUApplication$USER5$ST$SPS2 stVal √ √
26 86A TRIP RELAY OPERATED SP B702_BCUApplication$USER5$ST$SPS1 stVal √ √
27 86B TRIP RELAY SUPERVISION SP B702_BCUApplication$USER5$ST$SPS5 stVal √ √
28 86B TRIP RELAY OPERATED SP B702_BCUApplication$USER5$ST$SPS4 stVal √ √
29 CB TC-1 R-PHASE FAULTY
30 CB TC-1 Y-PHASE FAULTY
31 CB TC-1 B-PHASE FAULTY
32 CB TC-2 R-PHASE FAULTY
33 CB TC-2 Y-PHASE FAULTY SP B702_BCUApplication$USER5$ST$SPS stVal √ √
34 CB TC-2 B-PHASE FAULTY SP B702_BCUApplication$USER5$ST$SPS3 stVal √ √
35 KIOSK AC 1_2 Power Fail SP B702_BCUApplication$USER6$ST$SPS7 stVal √ √
36 KIOSK AC 1_2 ON STATUS SP B702_BCUApplication$USER6$ST$SPS6 stVal √
37 DC SOURCE-2 FAIL SP B702_BCUApplication$USER6$ST$SPS2 stVal √ √
38 KIOSK HEAT DETECTED SP B702_BCUApplication$USER6$ST$SPS5 stVal √ √
39 KIOSK SMOKE DETECTED SP B702_BCUApplication$USER6$ST$SPS4 stVal √ √
40 EMERGENCY/MANUAL CB TRIP SP B702_BCUApplication$USER6$ST$SPS stVal √ √
41 PSD DEVICE HEALTHY SP B702_BCUApplication$USER6$ST$SPS8 stVal √
42 PSD DEVICE IN SERVICE SP B702_BCUApplication$USER6$ST$SPS9 stVal √
43 PSD SENSSOR ERROR/CB VOLTAGE ERROR
45 PSD SYNCH OPERATION FAIL/DEFECTIVE SYNC DATA ALARM SP B702_BCUApplication$USER6$ST$SPS10 stVal √ √
46 SYNC OPERATION FAIL SP B702_BCUApplication$USER6$ST$SPS11 stVal √ √
47 TIE LBB RELAY UNHEALTHY SP B702_BCUApplication$USER6$ST$SPS1 stVal √ √
48 TIE LBB OPTD
49 CB POLE DESCREPENCY SP B702_BCUApplication$USER2$ST$SPS1 stVal √ √
50 CB SF6 GAS PRESSURE REFILL LOW ALARM SP B702_BCUApplication$USER2$ST$SPS stVal √ √
51 BUS-1 VT SELECTED SP B702_BCUApplication$USER7$ST$SPS stVal √
52 BUS-2 VT SELECTED SP B702_BCUApplication$USER7$ST$SPS1 stVal √
53 ICT LV VT SELECTED SP B702_BCUApplication$USER7$ST$SPS2 stVal √
54 CB READY SP B702_BCUCB$XCBR1$ST$Rdy stVal √
55 EMERGENCY/MANUAL CB TRIP SP B702_BCUCB$GAPC2$ST$Detected stVal √ √
56 CB MANUAL CLOSE
57 CB CONTROL NO SYNC SP B702_BCUCB$CSWI1$ST$Pos noSync √
58 CB CLOSE INTERLOCK SP B702_BCUCB$CILO1$ST$EnaCls stVal √
59 89AE OPEN INTERLOCK SP B702_BCU89AE$CILO3$ST$EnaOpn stVal √
60 89BE OPEN INTERLOCK SP B702_BCU89BE$CILO5$ST$EnaOpn stVal √
61 89A OPEN INTERLOCK SP B702_BCU89A$CILO2$ST$EnaOpn stVal √
62 89B OPEN INTERLOCK SP B702_BCU89B$CILO4$ST$EnaOpn stVal √
63 DEVICE HEALTHY SP B702_BCUApplication$LPHD0$ST$PhyHealth:0 stVal:1 √ √
64 GOOSE RECEIPT FAIL/TROUBLE SP B702_BCUApplication$USER7$ST$SPS3 stVal √ √
66 A/R FUNCTION OFF
67 A/R FUNCTION ON
69 A/R UNSUCCESSFUL
71 A/R SUCCESSFUL
72 RECLAIM IN PROGRESS
73 MAIN A/R LOCKOUT
74 TIE A/R LOCKOUT
75 Tie CB A/R PRIORITY CLOSE
76 MAIN/TIE BCU HEALTHY
77 AR SINGLE PHASE TRIP PERMITTED
78 CB NOT READY
79 A/R CLOSE COMMAND INDICATION
80 A/R IN PROGRESS
81 RELAY IN TEST MODE
82 SETTINGS CHANGED
83 CB MANUAL TRIP
84 CB MANUAL CLOSE
85 BUSBAR OPERATED
86 BCU IN LOCAL/REMOTE
89 POWER FACTOR ME_FL B702_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotPF:1 mag$f
90 FREQUENCY ME_FL B702_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$Hz:1 mag$f
91 400kV 400kV TIE ACTIVE POWER ME_FL B702_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotW:1 mag$f
92 REACTIVE POWER ME_FL B702_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVAr:1 mag$f
93 APPARENT POWER ME_FL B702_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVA:1 mag$f
94 I-R -PH CURRENT ME_FL B702_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsA$cVal$mag$f
95 I-Y -PH CURRENT ME_FL B702_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsB$cVal$mag$f
96 I-B -PH CURRENT ME_FL B702_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsC$cVal$mag$f
97 R-Y VOLTAGE ME_FL B702_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsAB$cVal$mag$f
98 Y-B VOLTAGE ME_FL B702_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsBC$cVal$mag$f
99 B-R VOLYAGE ME_FL B702_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsCA$cVal$mag$f
100 KIOSK TEMPERATURE ME_FL
101 CB-B-PH COUNTER ME_I B702_BCUCBB$XCBR1$ST$OpCnt stVal
102 CB-R-PH COUNTER ME_I B702_BCUCBR$XCBR1$ST$OpCnt stVal
103 CB-Y-PH COUNTER ME_I B702_BCUCBY$XCBR1$ST$OpCnt stVal
107 89B CONTROL DC B702_BCU89B$CSWI4$CO$Pos:8 Oper$ctlVal √
108 89A CONTROL DC B702_BCU89A$CSWI2$CO$Pos:8 Oper$ctlVal √
109 89BE CONTROL DC B702_BCU89BE$CSWI5$CO$Pos:8 Oper$ctlVal √
110 89AE CONTROL DC B702_BCU89AE$CSWI3$CO$Pos:8 Oper$ctlVal √
111 CB CONTROL DC B702_BCUCB$CSWI1$CO$Pos:8 Oper$ctlVal √
112 89B CONTROL NO LOCK SC B702_BCU89B$CSWI4$CO$Pos Oper$noLock √
113 89A CONTROL NO LOCK SC B702_BCU89A$CSWI2$CO$Pos Oper$noLock √
114 89BE CONTROL NO LOCK SC B702_BCU89BE$CSWI5$CO$Pos Oper$noLock √
115 89AE CONTROL NO LOCK SC B702_BCU89AE$CSWI3$CO$Pos Oper$noLock √
116 CB CONTROL NO SYNC SC B702_BCUCB$CSWI1$CO$Pos Oper$noSync √
117 CB CONTROL NO LOCK SC B702_BCUCB$CSWI1$CO$Pos Oper$noLock √
118 86B TRIP RELAY RESET COMMAND SC B702_BCUApplication$USER2$CO$SPC1:8 Oper$ctlVal √
119 86A TRIP RELAY RESET COMMAND SC B702_BCUApplication$USER2$CO$SPC:8 Oper$ctlVal √
120 BAY BLOCK SC
121 TELECONTROL BLOCK SC
122 GOOSE RECEIPT FAIL/TROUBLE SP B702_BCUApplication$LLN0$ST$SPS stVal √ √
123 A/R ON CONTROL SC B706_BCUApplication$USER8$CO$SPC:8 Oper$ctlVal √
124 A/R OFF CONTROL SC B706_BCUApplication$USER8$CO$SPC1:8 Oper$ctlVal √
125 A/R BLOCK SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$BlkFct stVal √
126 A/R FUNCTION OFF SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$Off stVal √
127 A/R FUNCTION ON SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$On stVal √
128 CB READY FOR A/R SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$AutoRecSt:0 stVal:1 √
129 A/R UNSUCCESSFUL SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$AutoRecSt:0 stVal:10 √ √
130 A/R SUCCESSFUL SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$Successful stVal √
131 CB NOT READY SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$CBnotRdy stVal √
132 A/R CLOSE COMMAND INDICATION SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$OpCls general √
133 TIE A/R START √
134 A/R IN PROGRESS SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$RecInit stVal √
135 SETTINGS CHANGED
136 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Feeder Name
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Single Point)
1 400kV 400kV TIE BREAKER FAILURE RPH- RETRIP SP B702_50ZTPROT$RBRF1$ST$OpIn phsC √ √
2 BREAKER FAILURE YPH- RETRIP SP B702_50ZTPROT$RBRF1$ST$OpIn phsB √ √
3 BREAKER FAILURE BPH- RETRIP SP B702_50ZTPROT$RBRF1$ST$OpIn phsA √ √
4 BREAKER FAILURE BACKTRIP SP B702_50ZTPROT$RBRF1$ST$OpIn general √ √
5 BREAKER FAILURE TRIP EXTERNAL SP B702_50ZTPROT$RBRF1$ST$OpEx general √ √
6 GENERAL TRIP SP B702_50ZTPROT$PTRC1$ST$Tr general √ √
7 BREAKER FAILURE INITIATION 3-PH SP B702_50ZTPROT$RBRF1$ST$Str general √ √
8 TIE CB FAIL SP B702_50ZTCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
9 TIE BCU UNHEALTHY SP B702_50ZTCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
10 DEVICE HEALTHY SP B702_50ZTPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
11 LBB EXTERNAL INITIATION 3-PH SP B702_50ZTEXT$pdGGIO23$ST$SPCSO7:0 stVal √ √
12 TIME SYNCHRONISATION ERROR SP B702_50ZTEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
13 LBB EXTERNAL INITIATION R-PH SP B702_50ZTEXT$pdGGIO23$ST$SPCSO27:0 stVal √ √
14 LBB EXTERNAL INITIATION Y-PH SP B702_50ZTEXT$pdGGIO23$ST$SPCSO28:0 stVal √ √
15 LBB EXTERNAL INITIATION B-PH SP B702_50ZTEXT$pdGGIO23$ST$SPCSO29:0 stVal √ √
16 POLE DISCREPANCY PICKUP SP B702_50ZTEXT$pdGGIO24$ST$SPCSO24:0 stVal √
17 POLE DISCREPANCY TRIP SP B702_50ZTEXT$pdGGIO24$ST$SPCSO28:0 stVal √ √
18 LBB ACTIVE SP B702_50ZTEXT$pdGGIO23$ST$SPCSO45:0 stVal √
20 GOOSE RECEIPT FAIL/TROUBLE SP B702_50ZTCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
21 SETTINGS CHANGED
22 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
SIEMENS SCADA GENERAL SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (INDEX)
Sheet Ref. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 6MD66 BCU REACTOR BCU STNM7XXBCU BCU is for each bay so 7XX refers to Bay
2 7SJ80 7SJ8_64T.2B REF RELAY PHASE B FOR ICT STNM7XXTREFB Bay No. 7XX will be always the main bay number for the ICT feeder
3 7SJ80 7SJ8_64T.2R REF RELAY PHASE R FOR ICT STNM7XXTREFR Bay No. 7XX will be always the main bay number for the ICT feeder
4 7SJ80 7SJ8_64T.2Y REF RELAY PHASE Y FOR ICT STNM7XXTREFY Bay No. 7XX will be always the main bay number for the ICT feeder
5 7SJ80 7SJ8_64T.2SP REF RELAY PHASE SP FOR ICT STNM7XXTREFS Bay No. 7XX will be always the main bay number for the ICT feeder
6 7SA522 7SJ8_67_1 LV REACTOR BACKUP IMPEDANCE STNM7XXTLVBU Bay No. 7XX will be always the main bay number for the ICT feeder
7 7UT613 7UT613_87T_99HV ICT DIFFERENTIAL RELAY STNM7XXTDIF Bay No. 7XX will be always the main bay number for the ICT feeder
NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "7XX" stand for Bay name, example if the bay no 701 then same has to be implemented like STNM701BCU
765kV BUS REACTOR (BCU)
Sr. No. Voltage Level Feeder Name Source Signal Decription
NAME ( BAY-703 BUS REACTOR ) INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Double Point)
1 765kV 765kV BUS REACTOR BCU CB R-PH POSITION DP B703_BCUCBB$XCBR1$ST$Pos:2 stVal √
2 CB Y-PH POSITION DP B703_BCUCBR$XCBR1$ST$Pos:2 stVal √
3 CB B-PH POSITION DP B703_BCUCBY$XCBR1$ST$Pos:2 stVal √
4 CB POSITION DP B703_BCUCB$CSWI1$ST$Pos:2 stVal √
5 89AE1 POSITION DP B703_BCU89AE1$CSWI3$ST$Pos:2 stVal √
6 89AE2 POSITION DP B703_BCU89AE2$CSWI6$ST$Pos:2 stVal √
7 89BE1 POSITION DP B703_BCU89BE1$CSWI5$ST$Pos:2 stVal √
8 89BE2 POSITION DP B703_BCU89BE2$CSWI7$ST$Pos:2 stVal √
9 89RE-B POSITION DP B703_BCU89REB$CSWI9$ST$Pos:2 stVal √
10 89RE-R POSITION DP B703_BCU89RER$CSWI9$ST$Pos:2 stVal √
11 89RE-Y POSITION DP B703_BCU89REY$CSWI9$ST$Pos:2 stVal √
12 89A POSITION DP B703_BCU89A$CSWI2$ST$Pos:2 stVal √
13 89B POSITION DP B703_BCU89B$CSWI4$ST$Pos:2 stVal √
14 89R-B POSITION DP B703_BCU89RB$CSWI8$ST$Pos:2 stVal √
15 89R-R POSITION DP B703_BCU89RR$CSWI8$ST$Pos:2 stVal √
16 89R-Y POSITION DP B703_BCU89RY$CSWI8$ST$Pos:2 stVal √
17 S89RE2 POSITION
18 S89R-R POSITION
19 S89R-Y POSITION
20 S89R-B POSITION
21 BINARY INPUT (Single Point)
23 BCU IN LOCAL/REMOTE SP √
24 AUX POWER FAIL SP B703_BCUApplication$LPHD0$ST$AuxPwrFail stVal √ √
25 TIME SYNCHRONISATION ERROR SP B703_BCUApplication$LMTS0$ST$TmSynErr stVal √
26 BCU MODE SP B703_BCUApplication$LLN0$ST$LocKey stVal √ √
27 CB SF6 GAS PRESSURE REFILL LOW ALARM SP B703_BCUApplication$USER1$ST$SPS stVal √ √
28 CB SF6 GAS PRESSURE LOCKOUT SP B703_BCUApplication$USER1$ST$SPS1 stVal √ √
29 89A POLE DESCREPENCY SP B703_BCUApplication$USER3$ST$SPS3 stVal √ √
30 89B POLE DESCREPENCY SP B703_BCUApplication$USER3$ST$SPS4 stVal √ √
31 CB DC SUPPLY-1/2 FAIL SP B703_BCUApplication$USER3$ST$SPS1 stVal √
32 CB SPRING CHARGED SP B703_BCUApplication$USER3$ST$SPS2 stVal √
33 CB SF6 GAS PRESSURE LOCKOUT SP B703_BCUApplication$USER3$ST$SPS stVal √ √
34 EMERGENCY/MANUAL CB TRIP SP B703_BCUApplication$USER6$ST$SPS stVal √ √
35 MAIN TANK HIGH LEVEL ALARM B-PH SP B703_BCUApplication$USER6$ST$SPS15 stVal √ √
36 MAIN TANK HIGH LEVEL ALARM R-PH SP B703_BCUApplication$USER6$ST$SPS5 stVal √ √
37 MAIN TANK HIGH LEVEL ALARM Y-PH SP B703_BCUApplication$USER6$ST$SPS10 stVal √ √
38 MAIN TANK LOW LEVEL ALARM B-PH SP B703_BCUApplication$USER6$ST$SPS14 stVal √ √
39 MAIN TANK LOW LEVEL ALARM R-PH SP B703_BCUApplication$USER6$ST$SPS4 stVal √ √
40 765kV 765kV BUS REACTOR BCU MAIN TANK LOW LEVEL ALARM Y-PH SP B703_BCUApplication$USER6$ST$SPS9 stVal √ √
41 OTI ALARM B-PH SP B703_BCUApplication$USER6$ST$SPS13 stVal √ √
42 OTI ALARM R-PH SP B703_BCUApplication$USER6$ST$SPS3 stVal √ √
43 OTI ALARM Y-PH SP B703_BCUApplication$USER6$ST$SPS8 stVal √ √
44 PSD DEVICE HEALTHY SP B703_BCUApplication$USER6$ST$SPS19 stVal √
45 PSD DEVICE IN SERVICE SP B703_BCUApplication$USER6$ST$SPS20 stVal √
46 PSD ALARM SP B703_BCUApplication$USER6$ST$SPS21 stVal √ √
47 PSD SYNCH DATA ERROR SP B703_BCUApplication$USER6$ST$SPS22 stVal √ √
48 SURGE ARRESTER B-PH SP B703_BCUApplication$USER6$ST$SPS18 stVal √
49 SURGE ARRESTER R-PH SP B703_BCUApplication$USER6$ST$SPS16 stVal √
50 SURGE ARRESTER Y-PH SP B703_BCUApplication$USER6$ST$SPS17 stVal √
51 WTI ALARM B-PH SP B703_BCUApplication$USER6$ST$SPS12 stVal √ √
52 WTI ALARM R-PH SP B703_BCUApplication$USER6$ST$SPS2 stVal √ √
53 WTI ALARM Y-PH SP B703_BCUApplication$USER6$ST$SPS7 stVal √ √
54 86A TRIP RELAY SUPERVISION SP B703_BCUApplication$USER5$ST$SPS2 stVal √ √
55 86A TRIP RELAY OPERATED SP B703_BCUApplication$USER5$ST$SPS1 stVal √ √
56 86B TRIP RELAY SUPERVISION SP B703_BCUApplication$USER5$ST$SPS5 stVal √ √
57 86B TRIP RELAY OPERATED SP B703_BCUApplication$USER5$ST$SPS4 stVal √ √
58 CB TC-1 R-PHASE FAULTY SP B703_BCUApplication$USER5$ST$SPS stVal √ √
59 CB TC-1 Y-PHASE FAULTY SP stVal √ √
60 CB TC-1 B-PHASE FAULTY SP stVal √ √
61 CB TC-2 R-PHASE FAULTY SP B703_BCUApplication$USER5$ST$SPS3 stVal √ √
62 CB TC-2 Y-PHASE FAULTY SP stVal √ √
63 CB TC-2 B-PHASE FAULTY SP stVal √ √
64 CB POLE DISCREPANCY SP B703_BCUApplication$USER2$ST$SPS1 stVal √ √
65 CB SF6 GAS PRESSURE REFILL LOW ALARM SP B703_BCUApplication$USER2$ST$SPS stVal √ √ repeated
66 BUS-1 VT RESET SP B703_BCUApplication$USER7$ST$SPS1 stVal √
67 BUS-2 VT RESET SP B703_BCUApplication$USER7$ST$SPS3 stVal √
68 LINE VT RESET SP B703_BCUApplication$USER7$ST$SPS5 stVal √
69 BUS-1 VT SELECTED SP B703_BCUApplication$USER7$ST$SPS stVal √
70 BUS-2 VT SELECTED SP B703_BCUApplication$USER7$ST$SPS2 stVal √
71 ICT LV VT SELECTED SP B703_BCUApplication$USER7$ST$SPS4 stVal √
72 CB READY SP B703_BCUCB$XCBR1$ST$Rdy stVal √
73 CB POSITION NO SYNC SP B703_BCUCB$CSWI1$ST$Pos noSync √
74 DEVICE HEALTHY SP B703_BCUApplication$LPHD0$ST$PhyHealth:0 stVal:1 √
75 S89RE2 OPEN INTERLOCK √
76 64R.2R RELAY FAIL √ √
77 64R.2Y RELAY FAIL √ √
78 64R.2B RELAY FAIL √ √
79 PSD SELECTOR SWITCH IN √ √
80 PSD SELECTOR SWITCH OUT √ √
81 64R.2S relay Unhealthy √ √
82 87R.1 relay Unhealthy √ √
83 21R.1 relay Unhealthy √
84 Manual close √
85 CB CLOSE INTERLOCK SP B703_BCUCB$CILO1$ST$EnaCls stVal √
86 89AE1 OPEN INTERLOCK SP B703_BCU89AE1$CILO3$ST$EnaOpn stVal √
87 765kV 765kV BUS REACTOR BCU 89AE2 OPEN INTERLOCK SP B703_BCU89AE2$CILO6$ST$EnaOpn stVal √
88 89BE1 OPEN INTERLOCK SP B703_BCU89BE1$CILO5$ST$EnaOpn stVal √
89 89BE2 OPEN INTERLOCK SP B703_BCU89BE2$CILO7$ST$EnaOpn stVal √
90 89RE-B-PH OPEN INTERLOCK SP B703_BCU89REB$CILO9$ST$EnaOpn stVal √
91 89RE-R-PH OPEN INTERLOCK SP B703_BCU89RER$CILO9$ST$EnaOpn stVal √
92 89RE-Y-PH OPEN INTERLOCK SP B703_BCU89REY$CILO9$ST$EnaOpn stVal √
93 89A OPEN INTERLOCK SP B703_BCU89A$CILO2$ST$EnaOpn stVal √
94 89B OPEN INTERLOCK SP B703_BCU89B$CILO4$ST$EnaOpn stVal √
95 89R-B-PH OPEN INTERLOCK SP B703_BCU89RB$CILO8$ST$EnaOpn stVal √
96 89R-R-PH OPEN INTERLOCK SP B703_BCU89RR$CILO8$ST$EnaOpn stVal √
97 89R-Y-PH OPEN INTERLOCK SP B703_BCU89RY$CILO8$ST$EnaOpn stVal √
98 RELAY IN TEST MODE √ √
99 SETTINGS CHANGED √ √
100 REACTOR-n R PH OUT OF SERVICE √
101 REACTOR-n Y PH OUT OF SERVICE √
102 REACTOR-n B PH OUT OF SERVICE √
103 REACTOR SPARE PH IN SERVICE IN REACTOR-N √
104 CB MANUAL TRIP √
105 CB MANUAL CLOSE √
106 BUSBAR OPERATED √ √
107 GOOSE RECEIPT FAIL/TROUBLE SP B703_BCUApplication$USER7$ST$SPS6 stVal √ √
108 MEASUREMENT
110 POWER FACTOR ME_FL B703_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotPF:1 mag$f
111 FREQUENCY ME_FL B703_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$Hz:1 mag$f
112 ACTIVE POWER ME_FL B703_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotW:1 mag$f
113 REACTIVE POWER ME_FL B703_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVAr:1 mag$f
114 APPARENT POWER ME_FL B703_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVA:1 mag$f
115 I-R-PH CURRENT ME_FL B703_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsA$cVal$mag$f
116 I-Y-PH CURRENT ME_FL B703_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsB$cVal$mag$f
117 I-B-PH CURRENT ME_FL B703_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsC$cVal$mag$f
118 R-Y VOLTAGE ME_FL B703_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsAB$cVal$mag$f
119 Y-B VOLTAGE ME_FL B703_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsBC$cVal$mag$f
120 B-R VOLYAGE ME_FL B703_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsCA$cVal$mag$f
122 CB-B-PH COUNTER ME_I B703_BCUCBB$XCBR1$ST$OpCnt stVal
123 CB-R-PH COUNTER ME_I B703_BCUCBR$XCBR1$ST$OpCnt stVal
124 CB-Y-PH COUNTER ME_I B703_BCUCBY$XCBR1$ST$OpCnt stVal
128 89R-Y CONTROL DC B703_BCU89RY$CSWI8$CO$Pos:8 Oper$ctlVal √
129 89R-R CONTROL DC B703_BCU89RR$CSWI8$CO$Pos:8 Oper$ctlVal √
130 89R-B CONTROL DC B703_BCU89RB$CSWI8$CO$Pos:8 Oper$ctlVal √
131 89B CONTROL DC B703_BCU89B$CSWI4$CO$Pos:8 Oper$ctlVal √
132 89A CONTROL DC B703_BCU89A$CSWI2$CO$Pos:8 Oper$ctlVal √
133 89RE-Y CONTROL DC B703_BCU89REY$CSWI9$CO$Pos:8 Oper$ctlVal √
134 89RE-R CONTROL DC B703_BCU89RER$CSWI9$CO$Pos:8 Oper$ctlVal √
135 89RE-B CONTROL DC B703_BCU89REB$CSWI9$CO$Pos:8 Oper$ctlVal √
136 89BE2 CONTROL DC B703_BCU89BE2$CSWI7$CO$Pos:8 Oper$ctlVal √
137 89BE1 CONTROL DC B703_BCU89BE1$CSWI5$CO$Pos:8 Oper$ctlVal √
138 89AE2 CONTROL DC B703_BCU89AE2$CSWI6$CO$Pos:8 Oper$ctlVal √
139 89AE1 CONTROL DC B703_BCU89AE1$CSWI3$CO$Pos:8 Oper$ctlVal √
140 CB CONTROL DC B703_BCUCB$CSWI1$CO$Pos:8 Oper$ctlVal √
141 CB CONTROL NO SYNC SC B703_BCUCB$CSWI1$CO$Pos Oper$noSync √
142 86B TRIP RELAY RESET COMMAND SC B703_BCUApplication$USER2$CO$SPC1:8 Oper$ctlVal √
143 86A TRIP RELAY RESET COMMAND SC B703_BCUApplication$USER2$CO$SPC:8 Oper$ctlVal √
Note: 1. All the switchgear status signals as per the actual primary equipment status. 2. Additional signal for CB Trouble, etc as per scheme 3. 10 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 4. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 5. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV BUS REACTOR (7SJ80)- 64R-R-PH
Sr. No. Voltage Level Feeder Name Source
Signal Decription
NAME ( BAY-703 BUS REACTOR ) INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Single Point)
1 765kV 765kV BUS REACTOR 7SJ80 MAIN CB OPEN SP B703_64R_RphCTRL$GGIO1$ST$SPCSO1:0 stVal √
2 TIE CB OPEN SP B703_64R_RphCTRL$GGIO1$ST$SPCSO2:0 stVal √
3 GOOSE RECEIPT FAIL/TROUBLE SP B703_64R_RphCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
4 OTI TRIP R-PH SP B703_64R_RphCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
5 WTI TRIP R-PH SP B703_64R_RphCTRL$GGIO1$ST$SPCSO6:0 stVal √ √
6 PRV-1, 2 & 3 TRIP R-PH SP B703_64R_RphCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
7 TIME SYNCHRONISATION ERROR SP B703_64R_RphEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
8 REF STAGE 1 TRIP SP B703_64R_RphPROT$PTOC16$ST$Op general √ √
9 REF STAGE 1 PICKUP SP B703_64R_RphPROT$PTOC16$ST$Str general √
10 REF STAGE 2 TRIP SP B703_64R_RphPROT$PTOC17$ST$Op general √ √
11 REF STAGE 2 PICKUP SP B703_64R_RphPROT$PTOC17$ST$Str general √
12 GENERAL TRIP SP B703_64R_RphPROT$PTRC1$ST$Tr general √ √
13 GENERAL PICKUP SP B703_64R_RphPROT$PTRC1$ST$Str general √
14 MAIN TANK BUCHHOLZ-1&2 ALARM R-PH SP B703_64R_RphCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
15 DEVICE HEALTHY SP B703_64R_RphPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
16 SETTINGS CHANGED √
17 RELAY IN TEST MODE √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV BUS REACTOR (7SJ80)- 64R-Y-PH
Sr. No. Voltage Level Feeder Name Source
Signal Decription
NAME ( BAY-703 BUS REACTOR ) INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Single Point)
1 765kV 765kV BUS REACTOR 7SJ80 21R RELAY UNHEALTHY SP B703_64R_YphCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
2 87R RELAY UNHEALTHY SP B703_64R_YphCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
3 BCU UNHEALTHY SP B703_64R_YphCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
4 GOOSE RECEIPT FAIL/TROUBLE SP B703_64R_YphCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
5 OTI TRIP Y-PH SP B703_64R_YphCTRL$GGIO1$ST$SPCSO6:0 stVal √ √
6 PRV-1, 2 & 3 TRIP Y-PH SP B703_64R_YphCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
7 TIME SYNCHRONISATION ERROR SP B703_64R_YphEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
8 REF STAGE 1 TRIP SP B703_64R_YphPROT$PTOC16$ST$Op general √ √
9 REF STAGE 1 PICKUP SP B703_64R_YphPROT$PTOC16$ST$Str general √
10 REF STAGE 2 TRIP SP B703_64R_YphPROT$PTOC17$ST$Op general √ √
11 REF STAGE 2 PICKUP SP B703_64R_YphPROT$PTOC17$ST$Str general √
12 GENERAL TRIP SP B703_64R_YphPROT$PTRC1$ST$Tr general √ √
13 GENERAL PICKUP SP B703_64R_YphPROT$PTRC1$ST$Str general √
14 MAIN TANK BUCHHOLZ-1&2 ALARM Y-PH SP B703_64R_YphCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
15 DEVICE HEALTHY SP B703_64R_YphPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
16 SETTINGS CHANGED √
17 RELAY IN TEST MODE √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV BUS REACTOR (7SJ80)- 64R-B-PH
Sr. No. Voltage Level Feeder Name Source
Signal Decription
NAME ( BAY-703 BUS REACTOR ) INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Single Point)
1 765kV 765kV BUS REACTOR 7SJ80 GOOSE RECEIPT FAIL/TROUBLE SP B703_64R_BphCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
2 TIME SYNCHRONISATION ERROR SP B703_64R_BphEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
3 REF STAGE 1 TRIP SP B703_64R_BphPROT$PTOC16$ST$Op general √ √
4 REF STAGE 1 PICKUP SP B703_64R_BphPROT$PTOC16$ST$Str general √
5 REF STAGE 2 TRIP SP B703_64R_BphPROT$PTOC17$ST$Op general √ √
6 REF STAGE 2 PICKUP SP B703_64R_BphPROT$PTOC17$ST$Str general √
7 GENERAL TRIP SP B703_64R_BphPROT$PTRC1$ST$Tr general √ √
8 OTI TRIP B-PH SP B703_64R_BphCTRL$GGIO1$ST$SPCSO6:0 stVal √ √
9 PRV-1,2 & 3 TRIP B-PH SP B703_64R_BphCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
10 DEVICE HEALTHY SP B703_64R_BphPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
11 MAIN TANK BUCHHOLZ-1&2 ALARM B-PH SP B703_64R_BphCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
12 MAIN TANK BUCHHOLZ-1&2 TRIP SP-PH SP B703_64R_BphCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
13 NGR THERMAL OVERLOAD TRIP SP B703_64R_BphPROT$PTTR1$ST$OP stVal √ √
14 87R RELAY UNHEALTHY SP B703_64R_YphCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
15 GENERAL PICKUP SP B703_64R_BphPROT$PTRC1$ST$Str general √
16 SETTINGS CHANGED √
17 RELAY IN TEST MODE √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV BUS REACTOR (7SJ80)- 64R-SP-PH
Sr. No. Voltage Level Feeder Name Source
Signal Decription
NAME ( BAY-703 BUS REACTOR ) INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Single Point)
1 765kV 765kV BUS REACTOR 7SJ80 GOOSE RECEIPT FAIL/TROUBLE SP B703_64R_SPCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
2 OTI TRIP SP-PH SP B703_64R_SPCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
3 MAIN TANK BUCHHOLZ-1&2 ALARM SP-PH B703_64R_SPCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
4 PRV-1, 2 & 3 TRIP SP-PH SP B703_64R_SPCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
5 TIME SYNCHRONISATION ERROR SP B703_64R_SPEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
6 REF STAGE 1 TRIP SP B703_64R_SPPROT$PTOC16$ST$Op general √ √
7 REF STAGE 1 PICKUP SP B703_64R_SPPROT$PTOC16$ST$Str general √
8 REF STAGE 2 TRIP SP B703_64R_SPPROT$PTOC17$ST$Op general √ √
9 REF STAGE 2 PICKUP SP B703_64R_SPPROT$PTOC17$ST$Str general √
10 GENERAL TRIP SP B703_64R_SPPROT$PTRC1$ST$Tr general √ √
11 GENERAL PICKUP SP B703_64R_SPPROT$PTRC1$ST$Str general √
12 DEVICE HEALTHY SP B703_64R_SPPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
13 SETTINGS CHANGED √
14 RELAY IN TEST MODE √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV BUS REACTOR (7SA522)
Sr. No. Voltage Level Feeder Name Source
Signal Decription
NAME ( BAY-703 BUS REACTOR ) INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Single Point)
1 765kV 765kV BUS REACTOR 7SA522 GOOSE RECEIPT FAIL/TROUBLE SP B703_21R_1CTRL$GGIO1$ST$SPCSO1:0 stVal √ √
2 WTI TRIP B-PH SP B703_21R_1CTRL$GGIO1$ST$SPCSO4:0 stVal √ √
3 WTI TRIP Y-PH SP B703_21R_1CTRL$GGIO1$ST$SPCSO2:0 stVal √ √
4 64.2-R_Y_B SP RELAY UNHEALTHY SP B703_21R_1CTRL$GGIO1$ST$SPCSO3:0 stVal √ √
5 TIME SYNCHRONISATION ERROR SP B703_21R_1EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
6 BACKUP IMPEDENCE ZONE-1 START SP B703_21R_1PROT$PDIS1$ST$Str general √
7 BACKUP IMPEDENCE ZONE-1 TRIP SP B703_21R_1PROT$PDIS1$ST$Op general √ √
8 BACKUP IMPEDENCE R-PH TRIP SP B703_21R_1PROT$PDIS1$ST$Op phsA √ √
9 BACKUP IMPEDENCE Y-PH TRIP SP B703_21R_1PROT$PDIS1$ST$Op phsB √ √
10 BACKUP IMPEDENCE B-PH TRIP SP B703_21R_1PROT$PDIS1$ST$Op phsC √ √
11 BACKUP IMPEDENCE BLOCKED SP B703_21R_1PROT$PDIS1$ST$Blk stVal √
12 GENERAL TRIP SP B703_21R_1PROT$PTRC1$ST$Tr general √ √
13 NON-DIRECTIONAL OVERCURRENT TRIP SP B703_21R_1PROT$PTOC2$ST$Op general √ √
14 NON-DIRECTIONAL OVERCURRENT START SP B703_21R_1PROT$PTOC2$ST$Str general √
15 DEVICE HEALTHY SP B703_21R_1PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
16 NO VOLTAGE IN LINE SP B703_21R_1EXT$pdGGIO3$ST$SPCSO40:0 stVal √ √
17 VT FUSE FAILURE SP B703_21R_1EXT$pdGGIO3$ST$SPCSO42:0 stVal √ √
18 SETTINGS CHANGED √ √
19 RELAY IN TEST MODE √ √
20 NON-DIRECTIONAL EARTHFAULT TRIP √ √
21 NON-DIRECTIONAL EARTHFAULT START √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV BUS REACTOR (7UT613)
Sr. No. Voltage Level Feeder Name Source
Signal Decription
NAME ( BAY-703 BUS REACTOR ) INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Single Point)
1 GOOSE RECEIPT FAIL/TROUBLE SP B703_87_1CTRL$GGIO1$ST$SPCSO5:0 stVal √ √
2 MAIN TANK BUCHHOLZ-1 TRIP B-PH SP B703_87_1CTRL$GGIO1$ST$SPCSO3:0 stVal √ √
3 MAIN TANK BUCHHOLZ-1 TRIP R-PH SP B703_87_1CTRL$GGIO1$ST$SPCSO4:0 stVal √ √
4 MAIN TANK BUCHHOLZ-1TRIP Y-PH SP B703_87_1CTRL$GGIO1$ST$SPCSO2:0 stVal √ √
5 REACTOR CB OPEN SP B703_87_1CTRL$GGIO1$ST$SPCSO1:0 stVal √
6 WTI R-PH TRIP SP
7 WTI Y-PH TRIP SP
8 WTI B-PH TRIP SP
9 PRESSURE RELIF VALVE-2 TRIP R-PH SP
10 PRESSURE RELIF VALVE-2 TRIP Y-PH SP
11 PRESSURE RELIF VALVE-2 TRIP B-PH SP
12 BUCHHOLZ-1 SP PH TRIP SP
13 WTI SP PH TRIP SP
14 PRESSURE RELIF VALVE-2 SP PH TRIP SP
15 TIME SYNCHRONISATION ERROR SP B703_87_1EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
16 DIFFERENTIAL TRIP R-PH SP B703_87_1EXT$pdGGIO89$ST$SPCSO40:0 stVal √ √
17 DIFFERENTIAL TRIP Y-PH SP B703_87_1EXT$pdGGIO89$ST$SPCSO41:0 stVal √ √
18 DIFFERENTIAL TRIP B-PH SP B703_87_1EXT$pdGGIO89$ST$SPCSO42:0 stVal √ √
19 DIFFERENTIAL STAGE 1 TRIP SP B703_87_1PROT$PDIF1$ST$Op general √ √
20 DIFFERENTIAL STAGE 1 PICKUP SP B703_87_1PROT$PDIF1$ST$Str general √
21 DIFFERENTIAL STAGE 2 TRIP SP B703_87_1PROT$PDIF2$ST$Op general √ √
22 DIFFERENTIAL STAGE 2 PICKUP SP B703_87_1PROT$PDIF2$ST$Str general √
23 21R RELAY UNHEALTHY
24 GENERAL TRIP SP B703_87_1PROT$PTRC1$ST$Tr general √ √
25 DEVICE HEALTHY SP B703_87_1PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
16 SETTINGS CHANGED √
17 RELAY IN TEST MODE √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
SIEMENS SCADA GENERAL SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (INDEX)
Sheet Ref. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 6MD66 BCU ICT BCU STNM7XXBCU BCU is for each bay so 7XX refers to Bay
2 7SJ80 7SJ8_51N ICT BACKUP EARTHFAULT RELAY (IF GIVEN SEPARATE) STNM7XXTBU Bay No. 7XX will be always the main bay number for the ICT feeder
3 7SJ80 7SJ8_64T.2B REF RELAY PHASE B FOR ICT STNM7XXTREFB Bay No. 7XX will be always the main bay number for the ICT feeder
4 7SJ80 7SJ8_64T.2R REF RELAY PHASE R FOR ICT STNM7XXTREFR Bay No. 7XX will be always the main bay number for the ICT feeder
5 7SJ80 7SJ8_64T.2SP REF RELAY PHASE SP FOR ICT STNM7XXTREFS Bay No. 7XX will be always the main bay number for the ICT feeder
6 7SJ80 7SJ8_64T.2Y REF RELAY PHASE Y FOR ICT STNM7XXTREFY Bay No. 7XX will be always the main bay number for the ICT feeder
7 7SJ80 7SJ8_67_1 LV ICT LV BACKUP OVERCURRENT AND EARTHFAULT RELAY STNM7XXTLVBU Bay No. 7XX will be always the main bay number for the ICT feeder
8 7SJ80 7SJ8_67_2HV ICT HV BACKUP OVERCURRENT AND EARTHFAULT RELAY STNM7XXTHVBU Bay No. 7XX will be always the main bay number for the ICT feeder
9 7RW 7RW_99LV ICT OVERFLUX RELAY STNM7XXTOF Bay No. 7XX will be always the main bay number for the ICT feeder
10 7UT85 7UT85_99HV ICT DIFFERENTIAL RELAY STNM7XXTDIF Bay No. 7XX will be always the main bay number for the ICT feeder
10 7SA522 7SA522_21R ICT BACKUP IMPEDANCE RELAY STNM7XXTBUIMP Bay No. 7XX will be always the main bay number for the ICT feeder
NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "7XX" stand for Bay name, example if the bay no 701 then same has to be implemented like STNM701BCU
765kV ICT-(BCU)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Double Point)
1 765kV 765kV ICT BCU CB B-PH POSITION DP B701_BCUCBB$XCBR1$ST$Pos:2 stVal √
2 CB R-PH POSITION DP B701_BCUCBR$XCBR1$ST$Pos:2 stVal √
3 CB Y-PH POSITION DP B701_BCUCBY$XCBR1$ST$Pos:2 stVal √
4 CB POSITION DP B701_BCUCB$CSWI1$ST$Pos:2 stVal √
5 S89T-R POSITION
6 S89T-Y POSITION
7 S89T-B POSITION DP B701_BCUES89AE1$CSWI3$ST$Pos:2 stVal √
8 89AE POSITION DP B701_BCUES89AE2$CSWI10$ST$Pos:2 stVal √
9 89BE POSITION DP B701_BCUES89BE$CSWI5$ST$Pos:2 stVal √
10 89TE B-PH POSITION DP B701_BCUES89TEB$CSWI7$ST$Pos:2 stVal √
11 89TE R-PH POSITION DP B701_BCUES89TER$CSWI7$ST$Pos:2 stVal √
12 89TE Y-PH POSITION DP B701_BCUES89TEY$CSWI7$ST$Pos:2 stVal √
13 89STE B-PH POSITION DP B701_BCUESTSE1B$CSWI9$ST$Pos:2 stVal √
14 89STE R-PH POSITION DP B701_BCUESTSE1R$CSWI9$ST$Pos:2 stVal √
15 89STE Y-PH POSITION DP B701_BCUESTSE1Y$CSWI9$ST$Pos:2 stVal √
16 89STE POSITION DP B701_BCUESTSE2$CSWI11$ST$Pos:2 stVal √
17 89A POSITION DP B701_BCUIS89A$CSWI2$ST$Pos:2 stVal √
18 89B POSITION DP B701_BCUIS89B$CSWI4$ST$Pos:2 stVal √
19 89T B-PH POSITION DP B701_BCUIS89TB$CSWI6$ST$Pos:2 stVal √
20 89T R-PH POSITION DP B701_BCUIS89TR$CSWI6$ST$Pos:2 stVal √
21 89T Y-PH POSITION DP B701_BCUIS89TY$CSWI6$ST$Pos:2 stVal √
22 89TS1_TS2 B-PH POSITION DP B701_BCUIS89TS1_TS2B$CSWI8$ST$Pos:2 stVal √
23 89TS1_TS2 R-PH POSITION DP B701_BCUIS89TS1_TS2R$CSWI8$ST$Pos:2 stVal √
24 89TS1_TS2 Y-PH POSITION DP B701_BCUIS89TS1_TS2Y$CSWI8$ST$Pos:2 stVal √
26 BINARY INPUT (Single Point)
28 AUX POWER FAIL SP B701_BCUApplication$LPHD0$ST$AuxPwrFail stVal √ √
29 TIME SYNCHRONISATION ERROR SP B701_BCUApplication$LMTS0$ST$TmSynErr stVal √ √
30 LED RESET SP B701_BCUApplication$LLN0$ST$LEDRs:2 stVal √
31 BCU MODE SP B701_BCUApplication$LLN0$ST$LocKey stVal √
32 CB SF6 GAS PRESSURE REFILL LOW ALARM SP B701_BCUApplication$USER1$ST$SPS stVal √ √
33 CB SF6 GAS PRESSURE LOCKOUT SP B701_BCUApplication$USER1$ST$SPS1 stVal √ √
34 CB DC SUPPLY-1/2 FAIL SP B701_BCUApplication$USER3$ST$SPS3 stVal √ √
35 CB SF6 GAS PRESSURE LOCKOUT SP B701_BCUApplication$USER3$ST$SPS2 stVal √ √
36 POLE DESCREPENCY SP B701_BCUApplication$USER3$ST$SPS1 stVal √ √
37 CB SPRING CHARGED B-PH SP B701_BCUApplication$USER3$ST$SPS6 stVal √ √
38 CB SPRING CHARGED R-PH SP B701_BCUApplication$USER3$ST$SPS4 stVal √ √
39 CB SPRING CHARGED Y-PH SP B701_BCUApplication$USER3$ST$SPS5 stVal √ √
40 89A POLE DESCREPENCY SP B701_BCUApplication$USER4$ST$SPS stVal √ √
41 89B POLE DESCREPENCY SP B701_BCUApplication$USER4$ST$SPS1 stVal √ √
42 86A TRIP RELAY SUPERVISION SP B701_BCUApplication$USER7$ST$SPS2 stVal √ √
43 86A TRIP RELAY OPERATED SP B701_BCUApplication$USER7$ST$SPS1 stVal √ √
44 86B TRIP RELAY SUPERVISION SP B701_BCUApplication$USER7$ST$SPS5 stVal √ √
45 86B TRIP RELAY OPERATED SP B701_BCUApplication$USER7$ST$SPS4 stVal √ √
46 EMERGENCY/MANUAL TRIP SP B701_BCUApplication$USER7$ST$SPS6 stVal √ √
47 CB TC-1 FAULTY SP B701_BCUApplication$USER7$ST$SPS stVal √ √
48 CB TC-2 FAULTY SP B701_BCUApplication$USER7$ST$SPS3 stVal √ √
49 PSD DEVICE IN SERVICE SP B701_BCUApplication$USER8$ST$SPS1 stVal √ √
50 PSD DEVICE HEALTHY SP B701_BCUApplication$USER8$ST$SPS stVal √ √
51 PSD ALARM SP B701_BCUApplication$USER8$ST$SPS2 stVal √ √
52 PSD SYNCH DATA ERROR SP B701_BCUApplication$USER8$ST$SPS3 stVal √ √
53 PSD SELECTOR SWITCH OUT
54 PSD SELECTOR SWITCH IN
55 DGA GAS HIGH ALARM SP-PH SP B701_BCUApplication$USER9$ST$SPS31 stVal √ √
56 DGA GAS HIGH ALARM R_Y_B-PH SP B701_BCUApplication$USER9$ST$SPS15 stVal √ √
57 MOISTER HIGH ALARM R_Y_B-PH SP B701_BCUApplication$USER9$ST$SPS16 stVal √ √
58 MOISTER HIGH ALARM SP-PH SP B701_BCUApplication$USER9$ST$SPS32 stVal √ √
59 OLTC OIL TEMP HIGH B-PH ALARM SP B701_BCUApplication$USER9$ST$SPS22 stVal √ √
60 OLTC OIL TEMP HIGH R-PH ALARM SP B701_BCUApplication$USER9$ST$SPS18 stVal √ √
61 OLTC OIL TEMP HIGH SP-PH ALARM SP B701_BCUApplication$USER9$ST$SPS34 stVal √ √
62 OLTC OIL TEMP HIGH Y-PH ALARM SP B701_BCUApplication$USER9$ST$SPS20 stVal √ √
63 OLTC OIL TEMP LOW B-PH ALARM SP B701_BCUApplication$USER9$ST$SPS21 stVal √ √
64 OLTC OIL TEMP LOW R-PH ALARM SP B701_BCUApplication$USER9$ST$SPS17 stVal √ √
65 OLTC OIL TEMP LOW SP-PH ALARM SP B701_BCUApplication$USER9$ST$SPS33 stVal √ √
66 OLTC OIL TEMP LOW Y-PH ALARM SP B701_BCUApplication$USER9$ST$SPS19 stVal √ √
67 OLTC LOW OIL REFILL B-PH ALARM SP B701_BCUApplication$USER9$ST$SPS12 stVal √ √
68 OLTC LOW OIL REFILL SP-PH ALARM SP B701_BCUApplication$USER9$ST$SPS28 stVal √ √
69 OLTC LOW OIL REFILL R-PH ALARM SP B701_BCUApplication$USER9$ST$SPS2 stVal √ √
70 OLTC LOW OIL REFILL Y-PH ALARM SP B701_BCUApplication$USER9$ST$SPS7 stVal √ √
71 RPH MOG LOW OIL LEVEL ALARM SP
72 YPH MOG LOW OIL LEVEL ALARM SP
73 BPH MOG LOW OIL LEVEL ALARM SP
74 SP-PH MOG LOW OIL LEVEL ALARM SP
75 RPH MOG HIGH OIL LEVEL ALARM SP
76 YPH MOG HIGH OIL LEVEL ALARM SP
77 BPH MOG HIGH OIL LEVEL ALARM SP
78 SP-PH MOG HIGH OIL LEVEL ALARM SP
79 R-PH OIL FLOW SENSITIVE VALVE ALARM SP
80 Y-PH OIL FLOW SENSITIVE VALVE ALARM SP
81 B-PH OIL FLOW SENSITIVE VALVE ALARM SP
82 SP-PH OIL FLOW SENSITIVE VALVE ALARM SP
83 RPH PUMP FAIL - BANK A SP
84 RPH PUMP FAIL - BANK B SP
85 RPH PUMP FAIL - BANK C SP
86 RPH PUMP FAIL - BANK D SP
87 YPH PUMP FAIL - BANK A SP
88 YPH PUMP FAIL - BANK B SP
89 YPH PUMP FAIL - BANK C SP
90 YPH PUMP FAIL - BANK D SP
91 BPH PUMP FAIL - BANK A SP
92 BPH PUMP FAIL - BANK B SP
93 BPH PUMP FAIL - BANK C SP
94 BPH PUMP FAIL - BANK D SP
95 SPH PUMP FAIL - BANK A SP
96 SPH PUMP FAIL - BANK B SP
97 SPH PUMP FAIL - BANK C SP
98 SPH PUMP FAIL - BANK D SP
99 RPH THERMAL OVERLOAD TRIP - BANK A SP
100 RPH THERMAL OVERLOAD TRIP - BANK B SP
101 RPH THERMAL OVERLOAD TRIP - BANK C SP
102 RPH THERMAL OVERLOAD TRIP - BANK D SP
103 YPH THERMAL OVERLOAD TRIP - BANK A SP
104 YPH THERMAL OVERLOAD TRIP - BANK B SP
105 YPH THERMAL OVERLOAD TRIP - BANK C SP
106 YPH THERMAL OVERLOAD TRIP - BANK D SP
107 BPH THERMAL OVERLOAD TRIP - BANK A SP
108 BPH THERMAL OVERLOAD TRIP - BANK B SP
109 BPH THERMAL OVERLOAD TRIP - BANK C SP
110 BPH THERMAL OVERLOAD TRIP - BANK D SP
111 SPH THERMAL OVERLOAD TRIP - BANK A SP
112 SPH THERMAL OVERLOAD TRIP - BANK B SP
113 SPH THERMAL OVERLOAD TRIP - BANK C SP
114 SPH THERMAL OVERLOAD TRIP - BANK D SP
115 RPH LOW OIL FLOW/REVERSE FLOW - BANK A SP
116 RPH LOW OIL FLOW/REVERSE FLOW - BANK B SP
117 RPH LOW OIL FLOW/REVERSE FLOW - BANK C SP
118 RPH LOW OIL FLOW/REVERSE FLOW - BANK D SP
119 YPH LOW OIL FLOW/REVERSE FLOW - BANK A SP
120 YPH LOW OIL FLOW/REVERSE FLOW - BANK B SP
121 YPH LOW OIL FLOW/REVERSE FLOW - BANK C SP
122 YPH LOW OIL FLOW/REVERSE FLOW - BANK D SP
123 BPH LOW OIL FLOW/REVERSE FLOW - BANK A SP
124 BPH LOW OIL FLOW/REVERSE FLOW - BANK B SP
125 BPH LOW OIL FLOW/REVERSE FLOW - BANK C SP
126 BPH LOW OIL FLOW/REVERSE FLOW - BANK D SP
127 SPH LOW OIL FLOW/REVERSE FLOW - BANK A SP
128 SPH LOW OIL FLOW/REVERSE FLOW - BANK B SP
129 SPH LOW OIL FLOW/REVERSE FLOW - BANK C SP
130 SPH LOW OIL FLOW/REVERSE FLOW - BANK D SP
131 RPH COOLER CONTROL SUPPLY FAIL SP
132 YPH COOLER CONTROL SUPPLY FAIL SP
133 BPH COOLER CONTROL SUPPLY FAIL SP
134 SPH COOLER CONTROL SUPPLY FAIL SP
135 RPH SUPPLY CHANGE OVER FAIL SP
136 YPH SUPPLY CHANGE OVER FAIL SP
137 BPH SUPPLY CHANGE OVER FAIL SP
138 SPH SUPPLY CHANGE OVER FAIL SP
139 RPH SUPPLY - A FAIL SP
140 YPH SUPPLY - A FAIL SP
141 BPH SUPPLY - A FAIL SP
142 SPH SUPPLY - A FAIL SP
143 RPH SUPPLY - B FAIL SP
144 YPH SUPPLY - B FAIL SP
145 BPH SUPPLY - B FAIL SP
146 SPH SUPPLY - B FAIL SP
147 RPH OLTC MOTOR OVERLOAD SP
148 RPH TAP CHANGE IN PROGRESS SP
149 RPH TAP CHANGE IN COMPLETE SP
150 RPH OLTC IN LOCAL SP
151 RPH OLTC IN REMOTE SP
152 RPH TAP CHANGE CONTROL SUPPLY FAIL SP
153 RPH LOWEST POSITION REACHDED SP
154 RPH HIGHESHT POSITION REACHDED SP
155 RPH OLTC RAISE COMMAND CMD
156 RPH OLTC LOWER COMMAND CMD
157 YPH OLTC MOTOR OVERLOAD SP
158 YPH TAP CHANGE IN PROGRESS SP
159 YPH TAP CHANGE IN COMPLETE SP
160 YPH OLTC IN LOCAL SP
161 YPH OLTC IN REMOTE SP
162 YPH TAP CHANGE CONTROL SUPPLY FAIL SP
163 YPH LOWEST POSITION REACHDED SP
164 YPH HIGHESHT POSITION REACHDED SP
165 YPH OLTC RAISE COMMAND CMD
166 YPH OLTC LOWER COMMAND CMD
167 BPH OLTC MOTOR OVERLOAD SP
168 BPH TAP CHANGE IN PROGRESS SP
169 BPH TAP CHANGE IN COMPLETE SP
170 BPH OLTC IN LOCAL SP
171 BPH OLTC IN REMOTE SP
172 BPH TAP CHANGE CONTROL SUPPLY FAIL SP
173 BPH LOWEST POSITION REACHDED SP
174 BPH HIGHESHT POSITION REACHDED SP
175 BPH OLTC RAISE COMMAND CMD
176 BPH OLTC LOWER COMMAND CMD
177 SPH OLTC MOTOR OVERLOAD SP
178 SPH TAP CHANGE IN PROGRESS SP
179 SPH TAP CHANGE IN COMPLETE SP
180 SPH OLTC IN LOCAL SP
181 SPH OLTC IN REMOTE SP
182 SPH TAP CHANGE CONTROL SUPPLY FAIL SP
183 SPH LOWEST POSITION REACHDED SP
184 SPH HIGHESHT POSITION REACHDED SP
185 SPH OLTC RAISE COMMAND CMD
186 SPH OLTC LOWER COMMAND CMD
187 OTI B-PH ALARM SP B701_BCUApplication$USER9$ST$SPS14 stVal √ √
188 OTI R-PH ALARM SP B701_BCUApplication$USER9$ST$SPS4 stVal √ √
189 OTI SP-PH ALARM SP B701_BCUApplication$USER9$ST$SPS30 stVal √ √
190 OTI Y-PH ALARM SP B701_BCUApplication$USER9$ST$SPS9 stVal √ √
191 PUMP FAIL B-PH SP B701_BCUApplication$USER9$ST$SPS25 stVal √ √
192 PUMP FAIL R-PH SP B701_BCUApplication$USER9$ST$SPS23 stVal √ √
193 PUMP FAIL SP-PH SP B701_BCUApplication$USER9$ST$SPS35 stVal √ √
194 PUMP FAIL Y-PH SP B701_BCUApplication$USER9$ST$SPS24 stVal √ √
195 SURGE ARRESTER B-PH SP B701_BCUApplication$USER9$ST$SPS38 stVal √ √
196 SURGE ARRESTER R-PH SP B701_BCUApplication$USER9$ST$SPS36 stVal √ √
197 SURGE ARRESTER Y-PH SP B701_BCUApplication$USER9$ST$SPS37 stVal √ √
198 WTI HV_IV_LV ALARM B-PH SP B701_BCUApplication$USER9$ST$SPS13 stVal √ √
199 WTI HV_IV_LV ALARM R-PH SP B701_BCUApplication$USER9$ST$SPS3 stVal √ √
200 WTI HV_IV_LV ALARM SP-PH SP B701_BCUApplication$USER9$ST$SPS29 stVal √ √
201 WTI HV_IV_LV ALARM Y-PH SP B701_BCUApplication$USER9$ST$SPS8 stVal √ √
202 CB SF6 LOW PRESSURE ALARM B-PH SP B701_BCUApplication$USER2$ST$SPS2 stVal √ √
203 CB SF6 LOW PRESSURE ALARM R-PH SP B701_BCUApplication$USER2$ST$SPS stVal √ √
204 CB SF6 LOW PRESSURE ALARM Y-PH SP B701_BCUApplication$USER2$ST$SPS1 stVal √ √
205 SP ICT B-PH SELECTED SP B701_BCUApplication$USER12$ST$SPS2 stVal √
206 SP ICT R-PH SELECTED SP B701_BCUApplication$USER12$ST$SPS stVal √
207 SP ICT Y-PH SELECTED SP B701_BCUApplication$USER12$ST$SPS1 stVal √
208 BUS-1 VT RESET SP B701_BCUApplication$USER10$ST$SPS1 stVal √
209 BUS-2 VT RESET SP B701_BCUApplication$USER10$ST$SPS3 stVal √
210 LINE VT RESET SP B701_BCUApplication$USER10$ST$SPS5 stVal √
211 BUS-1 VT SELECTED SP B701_BCUApplication$USER10$ST$SPS stVal √
212 BUS-2 VT SELECTED SP B701_BCUApplication$USER10$ST$SPS2 stVal √
213 LINE VTSELECTED SP B701_BCUApplication$USER10$ST$SPS4 stVal √
214 CB READY SP B701_BCUCB$XCBR1$ST$Rdy stVal √
215 EMERGENCY/MANUAL CB CLOSE SP B701_BCUCB$GAPC2$ST$Detected stVal √
216 GOOSE RECEIPT FAIL/TROUBLE SP B701_BCUApplication$USER10$ST$SPS3 stVal √ √
217 CB POSITION NO SYNC SP B701_BCUCB$CSWI1$ST$Pos noSync √
218 CB CLOSE INTERLOCK SP B701_BCUCB$CILO1$ST$EnaCls stVal √
219 89AE1 OPEN INTERLOCK SP B701_BCUES89AE1$CILO3$ST$EnaOpn stVal √
220 89AE2 OPEN INTERLOCK SP B701_BCUES89AE2$CILO10$ST$EnaOpn stVal √
221 89BE OPEN INTERLOCK SP B701_BCUES89BE$CILO5$ST$EnaOpn stVal √
222 89TE B-PH OPEN INTERLOCK SP B701_BCUES89TEB$CILO7$ST$EnaOpn stVal √
223 89TE R-PH OPEN INTERLOCK SP B701_BCUES89TER$CILO7$ST$EnaOpn stVal √
224 89TE Y-PH OPEN INTERLOCK SP B701_BCUES89TEY$CILO7$ST$EnaOpn stVal √
225 TSE1 B-PH OPEN INTERLOCK SP B701_BCUESTSE1B$CILO9$ST$EnaOpn stVal √
226 TSE1 R-PH OPEN INTERLOCK SP B701_BCUESTSE1R$CILO9$ST$EnaOpn stVal √
227 TSE1 Y-PH OPEN INTERLOCK SP B701_BCUESTSE1Y$CILO9$ST$EnaOpn stVal √
228 TSE2 OPEN INTERLOCK SP B701_BCUESTSE2$CILO11$ST$EnaOpn stVal √
229 89A OPEN INTERLOCK SP B701_BCUIS89A$CILO2$ST$EnaOpn stVal √
230 89B OPEN INTERLOCK SP B701_BCUIS89B$CILO4$ST$EnaOpn stVal √
231 89T B-PH OPEN INTERLOCK SP B701_BCUIS89TB$CILO6$ST$EnaOpn stVal √
232 89T R-PH OPEN INTERLOCK SP B701_BCUIS89TR$CILO6$ST$EnaOpn stVal √
233 89T Y-PH OPEN INTERLOCK SP B701_BCUIS89TY$CILO6$ST$EnaOpn stVal √
234 89TS1_TS2 B-PH OPEN INTERLOCK SP B701_BCUIS89TS1_TS2B$CILO8$ST$EnaOpn stVal √
235 89TS1_TS2 R-PH OPEN INTERLOCK SP B701_BCUIS89TS1_TS2R$CILO8$ST$EnaOpn stVal √
236 89TS1_TS2 Y-PH OPEN INTERLOCK SP B701_BCUIS89TS1_TS2Y$CILO8$ST$EnaOpn stVal √
237 RELAY IN TEST MODE √ √
238 SETTINGS CHANGED √ √
239 ICT-n R PH OUT OF SERVICE √
240 ICT-n Y PH OUT OF SERVICE √
241 ICT-n B PH OUT OF SERVICE √
242 ICT SPARE PH IN SERVICE IN ICT-N √
243 CB MANUAL TRIP √
244 CB MANUAL CLOSE √
245 BUSBAR OPERATED √ √
246 BCU IN LOCAL/REMOTE √
247 CB TC-1 R-PHASE FAULTY √ √
248 CB TC-1 Y-PHASE FAULTY √ √
249 CB TC-1 B-PHASE FAULTY √ √
250 CB TC-2 R-PHASE FAULTY √ √
251 CB TC-2 Y-PHASE FAULTY √ √
252 CB TC-2 B-PHASE FAULTY √ √
254 MEASUREMENT
256 POWER FACTOR ME_FL B701_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotPF:1 mag$f
257 FREQUENCY ME_FL B701_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$Hz:1 mag$f
258 ACTIVE POWER ME_FL B701_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotW:1 mag$f
259 REACTIVE POWER ME_FL B701_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVAr:1 mag$f
260 APPARENT POWER ME_FL B701_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVA:1 mag$f
261 I-R-PH CURRENT ME_FL B701_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsA$cVal$mag$f
262 I-Y-PH CURRENT ME_FL B701_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsB$cVal$mag$f
263 I-B-PH CURRENT ME_FL B701_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsC$cVal$mag$f
264 R-Y VOLTAGE ME_FL B701_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsAB$cVal$mag$f
265 Y-B VOLTAGE ME_FL B701_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsBC$cVal$mag$f
266 765kV 765kV ICT BCU B-R VOLYAGE ME_FL B701_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsCA$cVal$mag$f
267 CB-B-PH COUNTER ME_I B701_BCUCBB$XCBR1$ST$OpCnt stVal
268 CB-R-PH COUNTER ME_I B701_BCUCBR$XCBR1$ST$OpCnt stVal
269 CB-Y-PH COUNTER ME_I B701_BCUCBY$XCBR1$ST$OpCnt stVal
273 CB CONTROL DC B701_BCUCB$CSWI1$CO$Pos:8 Oper$ctlVal √
274 89AE1 CONTROL DC B701_BCUES89AE1$CSWI3$CO$Pos:8 Oper$ctlVal √ NO command in AIS.
275 89AE2 CONTROL DC B701_BCUES89AE2$CSWI10$CO$Pos:8 Oper$ctlVal √
276 89BE CONTROL DC B701_BCUES89BE$CSWI5$CO$Pos:8 Oper$ctlVal √
277 89TE B-PH CONTROL DC B701_BCUES89TEB$CSWI7$CO$Pos:8 Oper$ctlVal √
278 89TE R-PH CONTROL DC B701_BCUES89TER$CSWI7$CO$Pos:8 Oper$ctlVal √
279 89TE Y-PH CONTROL DC B701_BCUES89TEY$CSWI7$CO$Pos:8 Oper$ctlVal √
280 TSE1 B-PH CONTROL DC B701_BCUESTSE1B$CSWI9$CO$Pos:8 Oper$ctlVal √
281 TSE1 R-PH CONTROL DC B701_BCUESTSE1R$CSWI9$CO$Pos:8 Oper$ctlVal √
282 TSE1 Y-PH CONTROL DC B701_BCUESTSE1Y$CSWI9$CO$Pos:8 Oper$ctlVal √
283 TSE2 CONTROL DC B701_BCUESTSE2$CSWI11$CO$Pos:8 Oper$ctlVal √
284 89A CONTROL DC B701_BCUIS89A$CSWI2$CO$Pos:8 Oper$ctlVal √
285 89B CONTROL DC B701_BCUIS89B$CSWI4$CO$Pos:8 Oper$ctlVal √
286 89T B-PH CONTROL DC B701_BCUIS89TB$CSWI6$CO$Pos:8 Oper$ctlVal √
287 89T R-PH CONTROL DC B701_BCUIS89TR$CSWI6$CO$Pos:8 Oper$ctlVal √
288 89TS1_TS2 B-PH CONTROL DC B701_BCUIS89TS1_TS2B$CSWI8$CO$Pos:8 Oper$ctlVal √
289 89TS1_TS2 R-PH CONTROL DC B701_BCUIS89TS1_TS2R$CSWI8$CO$Pos:8 Oper$ctlVal √
290 89TS1_TS2 Y-PH CONTROL DC B701_BCUIS89TS1_TS2Y$CSWI8$CO$Pos:8 Oper$ctlVal √
291 89T Y-PH CONTROL DC B701_BCUIS89TY$CSWI6$CO$Pos:8 Oper$ctlVal √
292 CB CONTROL NO SYN SC B701_BCUCB$CSWI1$CO$Pos Oper$noSync √
293 86A TRIP RELAY RESET COMMAND SC B701_BCUApplication$USER2$CO$SPC:8 Oper$ctlVal √
294 86B TRIP RELAY RESET COMMAND SC B701_BCUApplication$USER2$CO$SPC1:8 Oper$ctlVal √
295 TAP RAISER SC B701_BCUApplication$USER8$CO$SPC:8 Oper$ctlVal √
296 TAP LOWER SC B701_BCUApplication$USER8$CO$SPC1:8 Oper$ctlVal √
Note: 1. All the switchgear status signals as per the actual primary equipment status. 2. Additional signal for CB Trouble, etc as per scheme 3. 10 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 4. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 5. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV ICT- 51N-(7SJ80)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 765kV 765kV ICT 7SJ80 DMT EARTHFAULT STAGE 1 TRIP SP B701_51NPROT$PTOC8$ST$Op general √ √
2 DMT EARTHFAULT STAGE 1 PICKUP SP B701_51NPROT$PTOC8$ST$Str general √
3 DMT EARTHFAULT STAGE 2 TRIP SP B701_51NPROT$PTOC9$ST$Op general √ √
4 DMT EARTHFAULT STAGE 2 PICKUP SP B701_51NPROT$PTOC9$ST$Str general √
5 IDMT EARTHFAULT TRIP SP B701_51NPROT$PTOC2$ST$Op general √ √
6 IDMT EARTHFAULT PICKUP SP B701_51NPROT$PTOC2$ST$Str general √
7 GENERAL TRIP SP B701_51NPROT$PTRC1$ST$Tr general √ √
8 GENERAL PICKUP SP B701_51NPROT$PTRC1$ST$Str general √
9 DEVICE HEALTHY SP B701_51NPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
10 TIME SYNCHRONISATION ERROR SP B701_51NEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
11 VT FUSE FAILURE SP B701_51NEXT$pdGGIO3$ST$SPCSO41:0 stVal √ √
12 OLTC OSR TRIP R PH SP B701_51NCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
13 OLTC OSR TRIP Y PH SP B701_51NCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
14 OLTC OSR TRIP B PH SP B701_51NCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
15 OIL FLOW SENSITIVE VALVE TRIP R PH SP B701_51NCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
16 OIL FLOW SENSITIVE VALVE TRIP Y PH SP B701_51NCTRL$GGIO1$ST$SPCSO6:0 stVal √ √
17 GOOSE RECEIPT FAIL/TROUBLE SP B701_51NCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
18 SETTINGS CHANGED √ √
19 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV ICT- 64T.2B-(7SJ80)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 765kV 765kV ICT 7SJ80 99LV_51N RELAY UNHEALTHY SP B701_64T_2BCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
2 RAPID PRESSURE TRIP B-PH SP B701_64T_2BCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
3 REF STAGE 1 TRIP SP B701_64T_2BPROT$PTOC16$ST$Op general √ √
4 REF STAGE 1 PICKUP SP B701_64T_2BPROT$PTOC16$ST$Str general √
5 REF STAGE 2 TRIP SP B701_64T_2BPROT$PTOC17$ST$Op general √ √
6 REF STAGE 2 PICKUP SP B701_64T_2BPROT$PTOC17$ST$Str general √
7 GENERAL TRIP SP B701_64T_2BPROT$PTRC1$ST$Tr general √ √
8 GENERAL PICKUP SP B701_64T_2BPROT$PTRC1$ST$Str general √
9 DEVICE HEALTHY SP B701_64T_2BPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
10 TIME SYNCHRONISATION ERROR SP B701_64T_2BEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
11 GOOSE RECEIPT FAIL/TROUBLE SP B701_64T_2BCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
12 BUCHHOLZ 1 TRIP B-PH SP B701_64T_2BCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
13 OTI TRIP B-PH SP B701_64T_2BCTRL$GGIO1$ST$SPCSO6:0 stVal √ √
14 BUCHHOLZ 2 ALARM B-PH SP B701_64T_2BCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
15 PRD OLTC TRIP B-PH SP B701_64T_2BCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
16 SETTINGS CHANGED √ √
17 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, Mechanical trips, alarms etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV ICT- 64T.2R-(7SJ80)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 765kV 765kV ICT 7SJ80 MAIN CB OPEN SP B701_64T_2RCTRL$GGIO1$ST$SPCSO1:0 stVal √
2 TIE CB OPEN SP B701_64T_2RCTRL$GGIO1$ST$SPCSO2:0 stVal √
3 BUCHHOLZ 1 TRIP R-PH SP B701_64T_2RCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
4 BUCHHOLZ 2 ALARM R-PH B701_64T_2RCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
5 OTI TRIP R-PH SP B701_64T_2RCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
6 PRD OLTC TRIP R-PH SP B701_64T_2RCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
7 REF STAGE 1 TRIP SP B701_64T_2RPROT$PTOC16$ST$Op general √ √
8 REF STAGE 1 PICKUP SP B701_64T_2RPROT$PTOC16$ST$Str general √
9 REF STAGE 2 TRIP SP B701_64T_2RPROT$PTOC17$ST$Op general √ √
10 REF STAGE 2 PICKUP SP B701_64T_2RPROT$PTOC17$ST$Str general √
11 GENERAL TRIP SP B701_64T_2RPROT$PTRC1$ST$Tr general √ √
12 GENERAL PICKUP SP B701_64T_2RPROT$PTRC1$ST$Str general √
13 DEVICE HEALTHY SP B701_64T_2RPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
14 TIME SYNCHRONISATION ERROR SP B701_64T_2REXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
15 GOOSE RECEIPT FAIL/TROUBLE SP B701_64T_2RCTRL$GGIO1$ST$SPCSO6:0 stVal √ √
16 SETTINGS CHANGED √ √
17 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, Mechanical trips, alarms etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV ICT- 64T.2SP-(7SJ80)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 765kV 765kV ICT 7SJ80 BUCHHOLZ 1 TRIP SP-PH SP B701_64T_2SPCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
2 OTI TRIP SP-PH SP B701_64T_2SPCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
3 OLTC OSR TRIP SP PH SP B701_64T_2SPCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
4 BUCHHOLZ 2 ALARM SP-PH SP B701_64T_2SPCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
5 PRD OLTC TRIP SP-PH SP B701_64T_2SPCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
6 REF STAGE 1 TRIP SP B701_64T_2SPPROT$PTOC16$ST$Op general √ √
7 REF STAGE 1 PICKUP SP B701_64T_2SPPROT$PTOC16$ST$Str general √
8 REF STAGE 2 TRIP SP B701_64T_2SPPROT$PTOC17$ST$Op general √ √
9 REF STAGE 2 PICKUP SP B701_64T_2SPPROT$PTOC17$ST$Str general √
10 GENERAL TRIP SP B701_64T_2SPPROT$PTRC1$ST$Tr general √ √
11 GENERAL PICKUP SP B701_64T_2SPPROT$PTRC1$ST$Str general √
12 DEVICE HEALTHY SP B701_64T_2SPPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
13 TIME SYNCHRONISATION ERROR SP B701_64T_2SPEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
14 GOOSE RECEIPT FAIL/TROUBLE SP B701_64T_2SPCTRL$GGIO1$ST$SPCSO6:0 stVal √ √
16 SETTINGS CHANGED √ √
17 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, Mechanical trips, alarms etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV ICT- 64T.2Y-(7SJ80)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 765kV 765kV ICT 7SJ80 BUCHHOLZ 1 TRIP Y-PH SP B701_64T_2YCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
2 OTI TRIP Y-PH SP B701_64T_2YCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
3 PRD OLTC TRIP Y-PH SP B701_64T_2YCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
4 REF STAGE 1 TRIP SP B701_64T_2YPROT$PTOC16$ST$Op general √ √
5 REF STAGE 1 PICKUP SP B701_64T_2YPROT$PTOC16$ST$Str general √
6 REF STAGE 2 TRIP SP B701_64T_2YPROT$PTOC17$ST$Op general √ √
7 REF STAGE 2 PICKUP SP B701_64T_2YPROT$PTOC17$ST$Str general √
8 GENERAL TRIP SP B701_64T_2YPROT$PTRC1$ST$Tr general √ √
9 GENERAL PICKUP SP B701_64T_2YPROT$PTRC1$ST$Str general √
10 DEVICE HEALTHY SP B701_64T_2YPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
11 TIME SYNCHRONISATION ERROR SP B701_64T_2YEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
12 BUCHHOLZ 2 ALARM Y-PH SP B701_64T_2YCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
13 GOOSE RECEIPT FAIL/TROUBLE SP B701_64T_2YCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
16 SETTINGS CHANGED √ √
17 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, Mechanical trips, alarms etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV ICT- 67-1-LV (7SJ80)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 765kV 765kV ICT 7SJ80 67. 2 HV RELAY UNHEALTHY SP B701_67_1_LVCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
2 87.1_99HV HV RELAY UNHEALTHY SP B701_67_1_LVCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
3 BCU UNHEALTHY SP B701_67_1_LVCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
4 DIRECTIONAL DMT OVERCURRENT STAGE-1 BLOCKED SP B701_67_1_LVPROT$PTOC10$ST$Blk stVal √
5 DIRECTIONAL DMT OVERCURRENT STAGE-1 TRIP SP B701_67_1_LVPROT$PTOC10$ST$Op general √ √
6 DIRECTIONAL DMT OVERCURRENT STAGE-1 PICKUP SP B701_67_1_LVPROT$PTOC10$ST$Str general √
7 DIRECTIONAL DMT OVERCURRENT STAGE-2 BLOCKED SP B701_67_1_LVPROT$PTOC11$ST$Blk stVal √
8 DIRECTIONAL DMT OVERCURRENT STAGE-2 TRIP SP B701_67_1_LVPROT$PTOC11$ST$Op general √ √
9 DIRECTIONAL DMT OVERCURRENT STAGE-2 PICKUP SP B701_67_1_LVPROT$PTOC11$ST$Str general √
10 DIRECTIONAL DMT OVERCURRENT STAGE-3 TRIP SP B701_67_1_LVPROT$PTOC19$ST$Op general √ √
11 DIRECTIONAL DMT OVERCURRENT STAGE-3 PICKUP SP B701_67_1_LVPROT$PTOC19$ST$Str general √
12 DIRECTIONAL DMT EARTHFAULT STAGE-1 BLOCKED SP B701_67_1_LVPROT$PTOC12$ST$Blk stVal √
13 DIRECTIONAL DMT EARTHFAULT STAGE-1 TRIP SP B701_67_1_LVPROT$PTOC12$ST$Op general √ √
14 DIRECTIONAL DMT EARTHFAULT STAGE-1 PICKUP SP B701_67_1_LVPROT$PTOC12$ST$Str general √
15 DIRECTIONAL DMT EARTHFAULT STAGE-2 BLOCKED SP B701_67_1_LVPROT$PTOC13$ST$Blk stVal √
16 DIRECTIONAL DMT EARTHFAULT STAGE-2 TRIP SP B701_67_1_LVPROT$PTOC13$ST$Op general √ √
17 DIRECTIONAL DMT EARTHFAULT STAGE-2 PICKUP SP B701_67_1_LVPROT$PTOC13$ST$Str general √
18 DIRECTIONAL DMT EARTHFAULT STAGE-3 TRIP SP B701_67_1_LVPROT$PTOC20$ST$Op general √ √
19 DIRECTIONAL DMT EARTHFAULT STAGE-3 PICKUP SP B701_67_1_LVPROT$PTOC20$ST$Str general √
20 DIRECTIONAL IDMT OVERCURRENT BLOCKED SP B701_67_1_LVPROT$PTOC4$ST$Blk stVal √
21 DIRECTIONAL IDMT OVERCURRENT TRIP SP B701_67_1_LVPROT$PTOC4$ST$Op general √ √
22 DIRECTIONAL IDMT EARTHFAULT BLOCKED SP B701_67_1_LVPROT$PTOC3$ST$Blk stVal √
23 DIRECTIONAL IDMT EARTHFAULT TRIP SP B701_67_1_LVPROT$PTOC3$ST$Op general √ √
24 GENERAL TRIP SP B701_67_1_LVPROT$PTRC1$ST$Tr general √ √
25 GENERAL PICKUP SP B701_67_1_LVPROT$PTRC1$ST$Str general √
26 DEVICE HEALTHY SP B701_67_1_LVPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
27 TIME SYNCHRONISATION ERROR SP B701_67_1_LVEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
28 GOOSE RECEIPT FAIL/TROUBLE SP B701_67_1_LVCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
16 SETTINGS CHANGED √ √
17 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, Mechanical trips, alarms etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV ICT-67-2HV (7SJ80)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 765kV 765kV ICT 7SJ80 RAPID PRESSURE TRIP R-PH SP B701_67_2HVCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
2 BUCHHOLZ 2 TRIP SP-PH SP B701_67_2HVCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
3 WTI HV_IV_LV TRIP SP-PH SP B701_67_2HVCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
4 WTI HV_LV_IV TRIP B-PH SP B701_67_2HVCTRL$GGIO1$ST$SPCSO6:0 stVal √ √
5 WTI HV_LV_IV TRIP R-PH SP B701_67_2HVCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
6 WTI HV_LV_IV TRIP Y-PH SP B701_67_2HVCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
7 DIRECTIONAL DMT OVERCURRENT STAGE-1 BLOCKED SP B701_67_2HVPROT$PTOC10$ST$Blk stVal √
8 DIRECTIONAL DMT OVERCURRENT STAGE-1 TRIP SP B701_67_2HVPROT$PTOC10$ST$Op general √ √
9 DIRECTIONAL DMT OVERCURRENT STAGE-1 PICKUP SP B701_67_2HVPROT$PTOC10$ST$Str general √
10 DIRECTIONAL DMT OVERCURRENT STAGE-2 BLOCKED SP B701_67_2HVPROT$PTOC11$ST$Blk stVal √
11 DIRECTIONAL DMT OVERCURRENT STAGE-2 TRIP SP B701_67_2HVPROT$PTOC11$ST$Op general √ √
12 DIRECTIONAL DMT OVERCURRENT STAGE-2 PICKUP SP B701_67_2HVPROT$PTOC11$ST$Str general √
13 DIRECTIONAL DMT OVERCURRENT STAGE-3 TRIP SP B701_67_2HVPROT$PTOC19$ST$Op general √ √
14 DIRECTIONAL DMT OVERCURRENT STAGE-3 PICKUP SP B701_67_2HVPROT$PTOC19$ST$Str general √
15 DIRECTIONAL DMT EARTHFAULT STAGE-1 BLOCKED SP B701_67_2HVPROT$PTOC12$ST$Blk stVal √
16 DIRECTIONAL DMT EARTHFAULT STAGE-1 TRIP SP B701_67_2HVPROT$PTOC12$ST$Op general √ √
17 DIRECTIONAL DMT EARTHFAULT STAGE-1 PICKUP SP B701_67_2HVPROT$PTOC12$ST$Str general √
18 DIRECTIONAL DMT EARTHFAULT STAGE-2 BLOCKED SP B701_67_2HVPROT$PTOC13$ST$Blk stVal √
19 DIRECTIONAL DMT EARTHFAULT STAGE-2 TRIP SP B701_67_2HVPROT$PTOC13$ST$Op general √ √
20 DIRECTIONAL DMT EARTHFAULT STAGE-2 PICKUP SP B701_67_2HVPROT$PTOC13$ST$Str general √
21 DIRECTIONAL DMT EARTHFAULT STAGE-3 TRIP SP B701_67_2HVPROT$PTOC20$ST$Op general √ √
22 DIRECTIONAL DMT EARTHFAULT STAGE-3 PICKUP SP B701_67_2HVPROT$PTOC20$ST$Str general √
23 GENERAL TRIP SP B701_67_2HVPROT$PTRC1$ST$Tr general √ √
24 GENERAL PICKUP SP B701_67_2HVPROT$PTRC1$ST$Str general √
25 DEVICE HEALTHY SP B701_67_2HVPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
26 TIME SYNCHRONISATION ERROR SP B701_67_2HVEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
27 GOOSE RECEIPT FAIL/TROUBLE SP B701_67_2HVCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
28 SETTINGS CHANGED √ √
29 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, Mechanical trips, alarms etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV ICT-99LV (7RW)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 765kV 765kV ICT 7RW 64.2 R_Y_B_SP RELAY UNHEALTHY SP B701_99LVCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
2 67.1 LV RELAY UNHEALTHY SP B701_99LVCTRL$GGIO1$ST$SPCSO4:0 stVal √ √
3 RAPID PRESSURE TRIP Y-PH SP B701_99LVCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
4 OIL FLOW SENSITIVE VALVE TRIP B PH SP B701_99LVCTRL$GGIO1$ST$SPCSO5:0 stVal √ √
5 OIL FLOW SENSITIVE VALVE TRIP SP PH B701_99LVCTRL$GGIO1$ST$SPCSO3:0
6 OVERFLUX STAGE-2 OPERATED SP B701_99LVPROT$PVPH2$ST$Op general √ √
7 OVERFLUX STAGE-2 PICKUP SP B701_99LVPROT$PVPH2$ST$Str general √
8 OVERFLUX STAGE-1 OPERATED SP B701_99LVPROT$PVPH1$ST$Op general √ √
9 OVERFLUX STAGE-1 PICKUP SP B701_99LVPROT$PVPH1$ST$Str general √
10 GENERAL TRIP SP B701_99LVPROT$PTRC1$ST$Tr general √ √
11 GENERAL PICKUP SP B701_99LVPROT$PTRC1$ST$Str general √
12 DEVICE HEALTHY SP B701_99LVPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
13 TIME SYNCHRONISATION ERROR SP B701_99LVEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
14 OVERFLUX ALARM SP B701_99LVEXT$pdGGIO84$ST$SPCSO55:0 stVal √ √
15 GOOSE RECEIPT FAIL/TROUBLE SP B701_99LVCTRL$GGIO1$ST$SPCSO7:0 stVal √ √
16 SETTINGS CHANGED √ √
17 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, Mechanical trips, alarms etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV ICT- 99HV-(7UT85)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-701 ICT-1)
Signal Decription INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Single Point)
1 765kV 765kV ICT 7UT85 TIME SYNCHRONISATION ERROR SP B701_87T_1_99HVApplication$LPHD0$ST$ClkFail stVal √ √
2 MAIN CB OPEN SP B701_87T_1_99HVApplication$USER1$ST$SPS stVal √
3 MAIN CB CLOSE SP B701_87T_1_99HVApplication$USER1$ST$SPS1 stVal √
4 REF PROTECTION OPERATED SP B701_87T_1_99HVApplication$USER1$ST$SPS11 stVal √ √
5 86 A/86 B RELAY OPERATED SP B701_87T_1_99HVApplication$USER1$ST$SPS12 stVal √ √
6 BUCHHOLZ 2 TRIP R-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS13 stVal √ √
7 BUCHHOLZ 2 TRIP Y-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS14 stVal √ √
8 BUCHHOLZ 2 TRIP B-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS15 stVal √ √
9 BUCHHOLZ 1 ALARM R-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS3 stVal √ √
10 BUCHHOLZ 1 ALARM Y-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS4 stVal √ √
11 BUCHHOLZ 1ALARM B-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS5 stVal √ √
12 BUCHHOLZ 1 ALARM SP-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS10 stVal √ √
13 TIE CB OPEN SP B701_87T_1_99HVApplication$USER1$ST$SPS2 stVal √
14 PRD1, 2 & 3 TRIP SP-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS6 stVal √ √
15 PRD1, 2 & 3 TRIP R-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS7 stVal √ √
16 PRD1, 2 & 3 TRIP Y-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS8 stVal √ √
17 PRD1, 2 & 3 TRIP B-PH SP B701_87T_1_99HVApplication$USER1$ST$SPS9 stVal √ √
18 2nd HARMONIC BLOCK PH-R SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Irs2HaDet phsA √
19 2nd HARMONIC BLOCK PH-Y SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Irs2HaDet phsB √
20 2nd HARMONIC BLOCK PH-B SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Irs2HaDet phsC √
21 5th HARMONIC BLOCK PH-R SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Irs5HaDet phsA √
22 5th HARMONIC BLOCK PH-Y SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Irs5HaDet phsB √
23 5th HARMONIC BLOCK PH-B SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Irs5HaDet phsC √
24 DIFFERENTIAL TRIP SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Op general √ √
25 DIFFERENTIAL TRIP R-PH SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Op phsA √ √
26 DIFFERENTIAL TRIP Y-PH SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Op phsB √ √
27 DIFFERENTIAL TRIP B-PH SP B701_87T_1_99HVPTD1_87TrafoDiffProt1$TR_PDIF1$ST$Op phsC √ √
28 DIFFERENTIAL STAGE-1 TRIP SP general √ √
29 DIFFERENTIAL STAGE-1 PICKUP
30 DIFFERENTIAL STAGE-2 TRIP
31 DIFFERENTIAL STAGE-2 PICKUP
34 OVER FLUX TRIP SP B701_87T_1_99HVPTS1$PTRC1$ST$Op general √ √
35 OVERFLUX STAGE-2 TRIP SP B701_87T_1_99HVPTS1_24Overexcitation1$ODP_PVPH1$ST$Op general √ √
36 OVERFLUX STAGE-1 TRIP SP B701_87T_1_99HVPTS1_24Overexcitation1$ODP_PVPH2$ST$Op general √ √
37 OVERFLUX HV ALARM SP B701_87T_1_99HVEXT$pdGGIO84$ST$SPCSO55:0 stVal √ √
38 DEVICE HEALTHY SP B701_87T_1_99HVApplication$LPHD0$ST$PhyHealth:0 stVal:1 √
39 GOOSE RECEIPT FAIL/TROUBLE SP B701_87T_1_99HVApplication$USER1$ST$SPS16 stVal √ √
40 SETTINGS CHANGED √ √
41 RELAY IN TEST MODE √ √
Note: 1. Additional signal for CB Trouble, Mechanical trips, alarms etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV BUS REACTOR (7SA522)
Sr. No. Voltage Level Feeder Name Source
Signal Decription
NAME ( BAY-703 BUS REACTOR ) INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Single Point)
1 765kV 765kV BUS REACTOR 7SA522 GOOSE RECEIPT FAIL/TROUBLE SP B703_21R_1CTRL$GGIO1$ST$SPCSO1:0 stVal √ √
2 WTI TRIP B-PH SP B703_21R_1CTRL$GGIO1$ST$SPCSO4:0 stVal √ √
3 WTI TRIP Y-PH SP B703_21R_1CTRL$GGIO1$ST$SPCSO2:0 stVal √ √
4 64.2-R_Y_B SP RELAY UNHEALTHY SP B703_21R_1CTRL$GGIO1$ST$SPCSO3:0 stVal √ √
5 TIME SYNCHRONISATION ERROR SP B703_21R_1EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
6 BACKUP IMPEDENCE ZONE-1 START SP B703_21R_1PROT$PDIS1$ST$Str general √
7 BACKUP IMPEDENCE ZONE-1 TRIP SP B703_21R_1PROT$PDIS1$ST$Op general √ √
8 BACKUP IMPEDENCE R-PH TRIP SP B703_21R_1PROT$PDIS1$ST$Op phsA √ √
9 BACKUP IMPEDENCE Y-PH TRIP SP B703_21R_1PROT$PDIS1$ST$Op phsB √ √
10 BACKUP IMPEDENCE B-PH TRIP SP B703_21R_1PROT$PDIS1$ST$Op phsC √ √
11 BACKUP IMPEDENCE BLOCKED SP B703_21R_1PROT$PDIS1$ST$Blk stVal √
12 GENERAL TRIP SP B703_21R_1PROT$PTRC1$ST$Tr general √ √
13 NON-DIRECTIONAL OVERCURRENT TRIP SP B703_21R_1PROT$PTOC2$ST$Op general √ √
14 NON-DIRECTIONAL OVERCURRENT START SP B703_21R_1PROT$PTOC2$ST$Str general √
15 DEVICE HEALTHY SP B703_21R_1PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
16 NO VOLTAGE IN LINE SP B703_21R_1EXT$pdGGIO3$ST$SPCSO40:0 stVal √ √
17 VT FUSE FAILURE SP B703_21R_1EXT$pdGGIO3$ST$SPCSO42:0 stVal √ √
18 SETTINGS CHANGED √ √
19 RELAY IN TEST MODE √ √
20 NON-DIRECTIONAL EARTHFAULT TRIP √ √
21 NON-DIRECTIONAL EARTHFAULT START √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
SIEMENS SCADA GENERAL SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (INDEX)
Sheet Ref. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 6MD66 BCU ICT BCU STNM7XXBCU BCU is for each bay so 7XX refers to Bay
2 7SJ80 7SJ8_64T.2B REF RELAY PHASE B FOR ICT STNM7XXTREFB Bay No. 7XX will be always the main bay number for the ICT feeder
3 7UT85 7UT85_99HV ICT DIFFERENTIAL RELAY STNM7XXTDIF Bay No. 7XX will be always the main bay number for the ICT feeder
4 7SA522 7SA522_21R ICT BACKUP IMPEDANCE RELAY STNM7XXTBUIMP Bay No. 7XX will be always the main bay number for the ICT feeder
NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "7XX" stand for Bay name, example if the bay no 701 then same has to be implemented like STNM701BCU
765kV LINE REACTOR-(BCU)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-707 LINE REACTOR)
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Double Point)
1 765kV 765kV LINE REACTOR BCU CB R-PH POSITION DP B707_BCUCBs3$XCBR1$ST$Pos:2 stVal √
2 CB Y-PH POSITION DP B707_BCUCBs1$XCBR1$ST$Pos:2 stVal √
3 CB B-PH POSITION DP B707_BCUCBs2$XCBR1$ST$Pos:2 stVal √
4 CB POSITION DP B707_BCUCB$CSWI1$ST$Pos:2 stVal √
5 89AE POSITION DP B707_BCU89AE$CSWI4$ST$Pos:2 stVal √
6 89BE POSITION DP B707_BCU89BE$CSWI5$ST$Pos:2 stVal √
7 89LRE1 POSITION DP B707_BCU89LE$CSWI7$ST$Pos:2 stVal √
8 89RE-B POSITION DP B707_BCU89REB$CSWI9$ST$Pos:2 stVal √
9 89RE-R POSITION DP B707_BCU89RER$CSWI9$ST$Pos:2 stVal √
10 89RE-Y POSITION DP B707_BCU89REY$CSWI9$ST$Pos:2 stVal √
11 89RSE1-B POSITION DP B707_BCU89RSE1B$CSWI11$ST$Pos:2 stVal √
12 89RSE1-R POSITION DP B707_BCU89RSE1R$CSWI11$ST$Pos:2 stVal √
13 89RSE1-Y POSITION DP B707_BCU89RSE1Y$CSWI11$ST$Pos:2 stVal √
14 89A POSITION DP B707_BCU89A$CSWI2$ST$Pos:2 stVal √
15 89B POSITION DP B707_BCU89B$CSWI3$ST$Pos:2 stVal √
16 89LR POSITION DP B707_BCU89L$CSWI6$ST$Pos:2 stVal √
17 89R-B POSITION DP B707_BCU89RB$CSWI8$ST$Pos:2 stVal √
18 89R-R POSITION DP B707_BCU89RR$CSWI8$ST$Pos:2 stVal √
19 89R-Y POSITION DP B707_BCU89RY$CSWI8$ST$Pos:2 stVal √
20 89RS1_RS2-B POSITION DP B707_BCU89RS1RS2B$CSWI10$ST$Pos:2 stVal √
21 89RS1_RS2-R POSITION DP B707_BCU89RS1RS2R$CSWI10$ST$Pos:2 stVal √
22 89RS1_RS2-Y POSITION DP B707_BCU89RS1RS2Y$CSWI10$ST$Pos:2 stVal √
S89R-R POSITION
S89R-Y POSITION
S89R-B POSITION
23 NGR CB POSITION DP B707_BCUNGRCB$CSWI1$ST$Pos:2 stVal √
25 BINARY INPUT (Single Point)
27 AUX POWER FAIL SP B707_BCUApplication$LPHD0$ST$AuxPwrFail stVal √ √
28 TIME SYNCHRONISATION ERROR SP B707_BCUApplication$LMTS0$ST$TmSynErr stVal √ √
29 GOOSE RECEIPT FAIL/TROUBLE SP B707_BCUApplication$LLN0$ST$SPS stVal √ √
30 BCU MODE SP B707_BCUApplication$LLN0$ST$LocKey stVal √
31 CB DC SUPPLY-1/2 FAIL SP B707_BCUApplication$USER3$ST$SPS1 stVal √ √
32 CB SPRING CHARGED B-PH SP B707_BCUApplication$USER3$ST$SPS4 stVal √
33 CB SPRING CHARGED R-PH SP B707_BCUApplication$USER3$ST$SPS2 stVal √
34 CB SPRING CHARGED Y-PH SP B707_BCUApplication$USER3$ST$SPS3 stVal √
35 CB SF6 GAS PRESSURE LOCKOUT SP B707_BCUApplication$USER3$ST$SPS stVal √ √
36 CT SF6 GAS PRESSURE REFILL LOW ALARM SP B707_BCUApplication$USER1$ST$SPS stVal √ √
37 CT SF6 GAS PRESSURE LOCKOUT SP B707_BCUApplication$USER1$ST$SPS1 stVal √ √
38 A/R BLOCK MAIN1-1 SP B707_BCUApplication$USER8$ST$SPS6 stVal √ √
39 A/R BLOCK MAIN-2 SP B707_BCUApplication$USER8$ST$SPS7 stVal √ √
40 SPARE REACTOR B-PH SELECTED SP B707_BCUApplication$USER8$ST$SPS2 stVal √
41 SPARE REACTOR R-PH SELECTED SP B707_BCUApplication$USER8$ST$SPS stVal √
42 SPARE REACTOR Y-PH SELECTED SP B707_BCUApplication$USER8$ST$SPS1 stVal √
43 SURGE ARRESTER B-PH SP B707_BCUApplication$USER8$ST$SPS5 stVal √
44 SURGE ARRESTER R-PH SP B707_BCUApplication$USER8$ST$SPS3 stVal √
45 SURGE ARRESTER Y-PH SP B707_BCUApplication$USER8$ST$SPS4 stVal √
46 86A TRIP RELAY SUPERVISION SP B707_BCUApplication$USER9$ST$SPS2 stVal √ √
47 86A TRIP RELAY OPERATED SP B707_BCUApplication$USER9$ST$SPS1 stVal √ √
48 86B TRIP RELAY SUPERVISION SP B707_BCUApplication$USER9$ST$SPS6 stVal √ √
49 86B TRIP RELAY OPERATED SP B707_BCUApplication$USER9$ST$SPS5 stVal √ √
50 CARRIER CHANNEL-1 OUT SP B707_BCUApplication$USER9$ST$SPS3 stVal √ √
51 CARRIER CHANNEL-2 OUT SP B707_BCUApplication$USER9$ST$SPS7 stVal √ √
52 MAIN-2 RELAY UNHEALTHY SP B707_BCUApplication$USER9$ST$SPS8 stVal √ √
53 EMERGENCY/MANUAL CB TRIP SP B707_BCUApplication$USER9$ST$SPS10 stVal √ √
54 MAIN TANK HIGH LEVEL ALARM B-PH SP B707_BCUApplication$USER9$ST$SPS25 stVal √ √
55 MAIN TANK HIGH LEVEL ALARM R-PH SP B707_BCUApplication$USER9$ST$SPS15 stVal √ √
56 MAIN TANK HIGH LEVEL ALARM Y-PH SP B707_BCUApplication$USER9$ST$SPS20 stVal √ √
57 MAIN TANK LOW LEVEL ALARM B-PH SP B707_BCUApplication$USER9$ST$SPS24 stVal √ √
58 MAIN TANK LOW LEVEL ALARM R-PH SP B707_BCUApplication$USER9$ST$SPS14 stVal √ √
59 MAIN TANK LOW LEVEL ALARM Y-PH SP B707_BCUApplication$USER9$ST$SPS19 stVal √ √
60 OTI ALARM B-PH SP B707_BCUApplication$USER9$ST$SPS23 stVal √ √
61 OTI ALARM R-PH SP B707_BCUApplication$USER9$ST$SPS13 stVal √ √
62 OTI ALARM Y-PH SP B707_BCUApplication$USER9$ST$SPS18 stVal √ √
63 SPEECH CHANNEL FAIL SP B707_BCUApplication$USER9$ST$SPS9 stVal √ √
64 CB TC-1 FAULTY SP B707_BCUApplication$USER9$ST$SPS stVal √ √
65 CB TC-2 FAULTY SP B707_BCUApplication$USER9$ST$SPS4 stVal √ √
66 WTI ALARM B-PH SP B707_BCUApplication$USER9$ST$SPS22 stVal √ √
67 WTI ALARM R-PH SP B707_BCUApplication$USER9$ST$SPS12 stVal √ √
68 WTI ALARM Y-PH SP B707_BCUApplication$USER9$ST$SPS17 stVal √ √
69 CB POLE DESCREPENCY ALARM SP B707_BCUApplication$USER2$ST$SPS1 stVal √ √
70 CB SF6 GAS PRESSURE REFILL LOW ALARM SP B707_BCUApplication$USER2$ST$SPS stVal √ √
71 TIME SYNCHRONISATION ERROR SP B707_BCUApplication$LTMS0$ST$TmSynErr stVal √ √
72 BUS-1 VT RESET SP B707_BCUApplication$USER11$ST$SPS1 stVal √
73 BUS-2 VT RESET SP B707_BCUApplication$USER11$ST$SPS3 stVal √
74 LINE VT RESET SP B707_BCUApplication$USER11$ST$SPS5 stVal √
75 BUS-1 VT SELECTED SP B707_BCUApplication$USER11$ST$SPS stVal √
76 BUS-2 VT SELECTED SP B707_BCUApplication$USER11$ST$SPS2 stVal √
77 LINE VT SELECTED SP B707_BCUApplication$USER11$ST$SPS4 stVal √
78 EMERGENCY/MANUAL CB CLOSE SP B707_BCUCB$GAPC2$ST$Detected stVal √
79 A/R FUNCTION ON SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$On stVal √
80 CB READY FOR A/R SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$AutoRecSt:0 stVal:1 √
81 A/R UNSUCCESSFUL SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$AutoRecSt:0 stVal:10 √ √
82 A/R SUCCESSFUL SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$Successful stVal √
83 CB NOT READY SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$CBnotRdy stVal √
84 A/R CLOSE COMMAND INDICATION SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$OpCls general √
85 A/R IN PROGRESS SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$RecInit stVal √
86 A/R FUNCTION OFF SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$Off stVal √
87 A/R FUNCTION ON SP B707_BCUCB1_79AutoReclosing$GEN_RREC1$ST$On stVal √
88 CB POSITION NO SYNC SP B707_BCUCB$CSWI1$ST$Pos noSync √
89 765kV 765kV LINE REACTOR BCU CB CLOSE INTERLOCK SP B707_BCUCB$CILO1$ST$EnaCls stVal √
90 89AE OPEN INTERLOCK SP B707_BCU89AE$CILO1$ST$EnaOpn stVal √
91 89BE OPEN INTERLOCK SP B707_BCU89BE$CILO1$ST$EnaOpn stVal √
92 89LE OPEN INTERLOCK SP B707_BCU89LE$CILO1$ST$EnaOpn stVal √
93 89RE-B-PH OPEN INTERLOCK SP B707_BCU89REB$CILO1$ST$EnaOpn stVal √
94 89RE-R-PH OPEN INTERLOCK SP B707_BCU89RER$CILO1$ST$EnaOpn stVal √
95 89RE-Y-PH OPEN INTERLOCK SP B707_BCU89REY$CILO1$ST$EnaOpn stVal √
96 89RSE1-B-PH OPEN INTERLOCK SP B707_BCU89RSE1B$CILO1$ST$EnaOpn stVal √
97 89RSE1-R-PH OPEN INTERLOCK SP B707_BCU89RSE1R$CILO1$ST$EnaOpn stVal √
98 89RSE1-Y-PH OPEN INTERLOCK SP B707_BCU89RSE1Y$CILO1$ST$EnaOpn stVal √
99 89A-PH OPEN INTERLOCK SP B707_BCU89A$CILO1$ST$EnaOpn stVal √
100 89B-PH OPEN INTERLOCK SP B707_BCU89B$CILO1$ST$EnaOpn stVal √
101 89L-PH OPEN INTERLOCK SP B707_BCU89L$CILO1$ST$EnaOpn stVal √
102 89R-B-PH OPEN INTERLOCK SP B707_BCU89RB$CILO1$ST$EnaOpn stVal √
103 89R-R-PH OPEN INTERLOCK SP B707_BCU89RR$CILO1$ST$EnaOpn stVal √
104 89R-Y-PH OPEN INTERLOCK SP B707_BCU89RY$CILO1$ST$EnaOpn stVal √
105 89RS1_RS2-B-PH OPEN INTERLOCK SP B707_BCU89RS1RS2B$CILO1$ST$EnaOpn stVal √
106 89RS1_RS2-R-PH OPEN INTERLOCK SP B707_BCU89RS1RS2R$CILO1$ST$EnaOpn stVal √
107 89RS1_RS2-Y-PH OPEN INTERLOCK SP B707_BCU89RS1RS2Y$CILO1$ST$EnaOpn stVal √
108 NGR CB CLOSE INTERLOCK SP B707_BCUNGRCB$CILO1$ST$EnaCls stVal √
109 RELAY IN TEST MODE √ √
110 SETTINGS CHANGED √ √
111 REACTOR-n R PH OUT OF SERVICE √
112 REACTOR-n Y PH OUT OF SERVICE √
113 REACTOR-n B PH OUT OF SERVICE √
114 REACTOR SPARE PH IN SERVICE IN REACTOR-N √
115 CB MANUAL TRIP √
116 CB MANUAL CLOSE √
117 BUSBAR OPERATED √ √
118 BCU IN LOCAL/REMOTE √
119 CB TC-1 R-PHASE FAULTY √ √
120 CB TC-1 Y-PHASE FAULTY √ √
121 CB TC-1 B-PHASE FAULTY √ √
122 CB TC-2 R-PHASE FAULTY √ √
123 CB TC-2 Y-PHASE FAULTY √ √
124 CB TC-2 B-PHASE FAULTY √ √
125 NGR CB TC-1 FAULTY
125 NGR CB TC-2 FAULTY
125 NGR CB DC FAULTY
125 NGR CB AC FAULTY
125 NGR CB SPRING NOT CHARGED
125 NGR CB SF6 GAS LOW
125 NGR CB SF6 CB TROUBLE ALARM
125 NGR MECHANICAL TRIPPING IF ASSIGNED
127 MEASUREMENTS
129 POWER FACTOR ME_FL B707_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotPF:1 mag$f
130 FREQUENCY ME_FL B707_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$Hz:1 mag$f
131 ACTIVE POWER ME_FL B707_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotW:1 mag$f
132 REACTIVE POWER ME_FL B707_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVAr:1 mag$f
133 APPARENT POWER ME_FL B707_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVA:1 mag$f
134 I-R-PH CURRENT ME_FL B707_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsA$cVal$mag$f
135 I-Y-PH CURRENT ME_FL B707_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsB$cVal$mag$f
136 I-B-PH CURRENT ME_FL B707_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsC$cVal$mag$f
137 R-Y VOLTAGE ME_FL B707_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsAB$cVal$mag$f
138 Y-B VOLTAGE ME_FL B707_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsBC$cVal$mag$f
139 B-R VOLYAGE ME_FL B707_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsCA$cVal$mag$f
143 CB CONTROL DC B707_BCUCB$CSWI1$CO$Pos:8 Oper$ctlVal √
144 89AE CONTROL DC B707_BCU89AE$CSWI4$CO$Pos:8 Oper$ctlVal √
145 89BE CONTROL DC B707_BCU89BE$CSWI5$CO$Pos:8 Oper$ctlVal √
146 89LE CONTROL DC B707_BCU89LE$CSWI7$CO$Pos:8 Oper$ctlVal √
147 89RE-B CONTROL DC B707_BCU89REB$CSWI9$CO$Pos:8 Oper$ctlVal √
148 89RE-R CONTROL DC B707_BCU89RER$CSWI9$CO$Pos:8 Oper$ctlVal √
149 89RE-Y CONTROL DC B707_BCU89REY$CSWI9$CO$Pos:8 Oper$ctlVal √
150 89RSE1-B CONTROL DC B707_BCU89RSE1B$CSWI11$CO$Pos:8 Oper$ctlVal √
151 89RSE1-R CONTROL DC B707_BCU89RSE1R$CSWI11$CO$Pos:8 Oper$ctlVal √
152 89RSE1-Y CONTROL DC B707_BCU89RSE1Y$CSWI11$CO$Pos:8 Oper$ctlVal √
153 89A CONTROL DC B707_BCU89A$CSWI2$CO$Pos:8 Oper$ctlVal √
154 89B CONTROL DC B707_BCU89B$CSWI3$CO$Pos:8 Oper$ctlVal √
155 89L CONTROL DC B707_BCU89L$CSWI6$CO$Pos:8 Oper$ctlVal √
156 89R-B CONTROL DC B707_BCU89RB$CSWI8$CO$Pos:8 Oper$ctlVal √
157 89R-R CONTROL DC B707_BCU89RR$CSWI8$CO$Pos:8 Oper$ctlVal √
158 89R-Y CONTROL DC B707_BCU89RY$CSWI8$CO$Pos:8 Oper$ctlVal √
159 89RS1_RS2-B CONTROL DC B707_BCU89RS1RS2B$CSWI10$CO$Pos:8 Oper$ctlVal √
160 89RS1_RS2-R CONTROL DC B707_BCU89RS1RS2R$CSWI10$CO$Pos:8 Oper$ctlVal √
161 89RS1_RS2-Y CONTROL DC B707_BCU89RS1RS2Y$CSWI10$CO$Pos:8 Oper$ctlVal √
162 NGR CB CONTROL DC B707_BCUNGRCB$CSWI1$CO$Pos:8 Oper$ctlVal √
163 CB CONTROL NO SYNC SC B707_BCUCB$CSWI1$CO$Pos Oper$noSync √
164 NGR CB CONTROL NO SYNC SC B707_BCUNGRCB$CSWI1$CO$Pos Oper$noSync √
165 86B TRIP RELAY RESET COMMAND SC B707_BCUApplication$USER2$CO$SPC:8 Oper$ctlVal √
166 86A TRIP RELAY RESET COMMAND SC B707_BCUApplication$USER2$CO$SPC1:8 Oper$ctlVal √
167 A/R ON CONTROL SC B707_BCUApplication$USER12$CO$SPC:8 Oper$ctlVal √
168 A/R OFF CONTROL SC B707_BCUApplication$USER12$CO$SPC1:8 Oper$ctlVal √
Note: 1. All the switchgear status signals as per the actual primary equipment status. 2. Additional signal for CB Trouble, etc as per scheme 3. 10 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 4. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 5. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV LINE REACTOR-(7SA52)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-707 LINE REACTOR)
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION REMARKS Events Alarms
BINARY INPUT (Single Point)
1 WTI TRIP B-PH SP B707_21R_1CTRL$GGIO1$ST$SPCSO2:0 stVal √ √
2 WTI TRIP Y-PH SP B707_21R_1CTRL$GGIO1$ST$SPCSO1:0 stVal √ √
3 OTI TRIP B-PH SP B707_64R_2CTRL$GGIO1$ST$SPCSO4:0 stVal √ √
4 OTI TRIP R-PH SP B707_64R_2CTRL$GGIO1$ST$SPCSO5:0 stVal √ √
5 BUCHHOLZ-1/2 TRIP R-PH SP B707_21R_1CTRL$GGIO1$ST$SPCSO3:0 stVal √ √
6 BUCHHOLZ-1/2 TRIP Y-PH SP B707_21R_1CTRL$GGIO1$ST$SPCSO6:0 stVal √ √
7 BUCHHOLZ-1/2 TRIP B-PH SP B707_21R_1CTRL$xGGIO1$ST$SPCSO7:0 stVal √ √
BCU-1/2 RELAY FAIL
REACTOR DC-2 FAIL
GROUP-B PROTECTION RELAY FAIL
8 BACKUP IMPEDENCE ZONE-1 PICKUP SP B707_21R_1PROT$PDIS1$ST$Str general √
9 BACKUP IMPEDENCE ZONE-1 TRIP SP B707_21R_1PROT$PDIS1$ST$Op general √ √
10 BACKUP IMPEDENCE R-PH TRIP SP B707_21R_1PROT$PDIS1$ST$Op phsA √ √
11 BACKUP IMPEDENCE Y-PH TRIP SP B707_21R_1PROT$PDIS1$ST$Op phsB √ √
12 BACKUP IMPEDENCE B-PH TRIP SP B707_21R_1PROT$PDIS1$ST$Op phsC √ √
13 GENERAL TRIP SP B707_21R_1PROT$PTRC1$ST$Tr general √ √
14 BACKUP IMPEDENCE BLOCKED SP B707_21R_1PROT$PDIS1$ST$Blk stVal √
15 DEVICE HEALTHY SP B707_21R_1PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
16 GOOSE RECEIPT FAIL/TROUBLE SP B707_21R_1CTRL$GGIO1$ST$SPCSO8:0 stVal √ √
17 VOLTAGE ABSENT SP B707_21R_1EXT$pdGGIO3$ST$SPCSO40:0 stVal √ √
18 VT FUSE FAILURE SP B707_21R_1EXT$pdGGIO3$ST$SPCSO42:0 stVal √ √
19 TIME SYNCHRONISATION ERROR SP B707_21R_2EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
20 BROKEN CONDUCTOR SP B707_21R_1EXT$pdGGIO4$ST$SPCSO3:0 stVal √ √
21 NON-DIRECTIONAL OVERCURRENT TRIP SP B703_21R_1PROT$PTOC2$ST$Op general √ √
22 NON-DIRECTIONAL OVERCURRENT START SP B703_21R_1PROT$PTOC2$ST$Str general √
23 NON-DIRECTIONAL EARTHFAULT TRIP √ √
24 NON-DIRECTIONAL EARTHFAULT START √
25 SETTINGS CHANGED √
26 RELAY IN TEST MODE √
27 NGR CLOSE COMMAND BY E/F PICKUP(5 SEC) √ √
28 NGR CLOSE COMMAND BY MECH TRIP √ √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV LINE REACTOR-(7SJ80)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-707 LINE REACTOR) NOTE: THESE SIGNAL STANDARDIZATION IS SCHEME BASED
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION Events Alarms
BINARY INPUT (Single Point)
1 765kV 765kV LINE REACTOR 7SJ80 BUCHHOLZ TRIP B-PH SP B707_64R_2CTRL$GGIO1$ST$SPCSO5:0 stVal √ √
2 BUCHHOLZ TRIP R-PH SP B707_64R_2CTRL$GGIO1$ST$SPCSO1:0 stVal √ √
3 BUCHHOLZ TRIP Y-PH SP B707_64R_2CTRL$GGIO1$ST$SPCSO3:0 stVal √ √
4 OTI TRIP Y-PH SP B707_64R_2CTRL$GGIO1$ST$SPCSO4:0 stVal √ √
5 REF STAGE 1 TRIP SP B707_64R_2PROT$PTOC16$ST$Op general √ √
6 REF STAGE 1 PICKUP SP B707_64R_2PROT$PTOC16$ST$Str general √
7 REF STAGE 2 TRIP SP B707_64R_2PROT$PTOC17$ST$Op general √ √
8 REF STAGE 2 PICKUP SP B707_64R_2PROT$PTOC17$ST$Str general √
9 GENERAL TRIP SP B707_64R_2PROT$PTRC1$ST$Tr general √ √
10 DEVICE HEALTHY SP B707_64R_2PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
11 GOOSE RECEIPT FAIL/TROUBLE SP B707_64R_2CTRL$GGIO1$ST$SPCSO7:0 stVal √ √
12 NGR THERMAL OVERLOAD TRIP SP B707_64R_2PROT$PTTR1$ST$OP stVal √ √
13 TIME SYNCHRONISATION ERROR SP B707_64R_2EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
14 SETTINGS CHANGED √
15 RELAY IN TEST MODE √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
765kV LINE REACTOR-(7UT)
Sr. No. Voltage Level Feeder Name Source NAME (BAY-707 LINE REACTOR) NOTE: THESE SIGNAL STANDARDIZATION IS SCHEME BASED
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION Events Alarms
BINARY INPUT (Single Point)
1 PRV-1 TRIP B-PH(NO) SP stVal √ √
2 PRV-1 TRIP R-PH(NO) SP stVal √ √
3 PRV-1 TRIP Y-PH(NO) SP stVal √ √
4 PRV-1 TRIP B-PH(NC) SP stVal √ √
5 PRV-1 TRIP R-PH(NC) SP stVal √ √
6 PRV-1 TRIP Y-PH(NC) SP stVal √ √
7 PRV-2 TRIP B-PH(NO) SP stVal √ √
8 PRV-2 TRIP R-PH(NO) SP stVal √ √
9 PRV-2 TRIP Y-PH(NO) SP stVal √ √
10 765kV 765kV LINE REACTOR 7UT PRV-2 TRIP B-PH(NC) SP stVal √ √
11 PRV-2 TRIP R-PH(NC) SP stVal √ √
12 PRV-2 TRIP Y-PH(NC) SP stVal √ √
13 PRV-1 TRIP B-PH SP stVal √ √
14 PRV-1 TRIP R-PH SP stVal √ √
15 PRV-1 TRIP Y-PH SP stVal √ √
16 PRV-2 TRIP B-PH SP stVal √ √
17 PRV-2 TRIP R-PH SP stVal √ √
18 PRV-2 TRIP Y-PH SP stVal √ √
19 WTI TRIP R-PH SP stVal √ √
20 DIFFERENTIAL TRIP R-PH SP B707_87R_1EXT$pdGGIO89$ST$SPCSO40:0 stVal √ √
21 DIFFERENTIAL TRIP Y-PH SP B707_87R_1EXT$pdGGIO89$ST$SPCSO41:0 stVal √ √
22 DIFFERENTIAL TRIP B-PH SP B707_87R_1EXT$pdGGIO89$ST$SPCSO42:0 stVal √ √
23 DIFFERENTIAL STAGE 1 OPERATED SP B707_87R_1PROT$PDIF1$ST$Op general √ √
24 DIFFERENTIAL STAGE 1 PICKUP SP B707_87R_1PROT$PDIF1$ST$Str general √
25 DIFFERENTIAL STAGE 2 OPERATED SP B707_87R_1PROT$PDIF2$ST$Op general √ √
26 DIFFERENTIAL STAGE 2 PICKUP SP B707_87R_1PROT$PDIF2$ST$Str general √
27 GENERAL TRIP SP B707_87R_1PROT$PTRC1$ST$Tr general √ √
28 DEVICE HEALTHY SP B707_87R_1PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
29 GOOSE RECEIPT FAIL/TROUBLE SP B707_87R_1CTRL$GGIO1$ST$SPCSO5:0 stVal √ √
30 TIME SYNCHRONISATION ERROR SP B707_87R_1EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
31 SETTINGS CHANGED √
32 RELAY IN TEST MODE √
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
SIEMENS SCADA GENERAL SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (INDEX)
Sheet Ref. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 6MD66 BCU LINE BCU STNM7XXLBCU BCU is for each bay so 7XX refers to Bay
2 7SA522 7SA522_21M1 LINE DISTANCE MAIN-1 STNM7XXL21M1 Bay No. 7XX will be always the main bay number for the ICT feeder
3 7SD522 7SD522_87M1 LINE DIFFERENTIAL/DISTANCE MAIN-2 STNM7XXL87M1 Bay No. 7XX will be always the main bay number for the ICT feeder
NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "7XX" stand for Bay name, example if the bay no 701 then same has to be implemented like STNM701BCU
Sr. No. Voltage Level Feeder Name
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION EVENT ALARM
BINARY INPUT (Double Point)
1 765kV 765kV LINE CB B-PH POSITION DP B706_BCUCBB$XCBR1$ST$Pos:2 stVal √
2 CB R-PH POSITION DP B706_BCUCBR$XCBR1$ST$Pos:2 stVal √
3 CB Y-PH POSITION DP B706_BCUCBY$XCBR1$ST$Pos:2 stVal √
4 CB POSITION DP B706_BCUCB$CSWI1$ST$Pos:2 stVal √
5 89AE1 POSITION DP B706_BCU89AE1$CSWI3$ST$Pos:2 stVal √
6 89AE2 POSITION DP B706_BCU89AE2$CSWI8$ST$Pos:2 stVal √
7 89BE POSITION DP B706_BCU89BE$CSWI5$ST$Pos:2 stVal √
8 89A POSITION DP B706_BCU89A$CSWI2$ST$Pos:2 stVal √
9 89B POSITION DP B706_BCU89B$CSWI4$ST$Pos:2 stVal √
10 89L POSITION DP B706_BCU89L$CSWI6$ST$Pos:2 stVal √
11 89LE POSITION DP B706_BCU89LE$CSWI7$ST$Pos:2 stVal √
12 89 BE1 POSITION
13 89 BE2 POSITION
14 THE LOGICAL NODE FOR BUS EARTH SWITCHES, ISOLATOR & EARTHSWITCHES FOR 3 PH/1PH REACTORS & ITCs, e.g 89 BR, BRE, LR, LRE, RS1, RS2, RS1E, 89T,TE, 89AE2, 89BE2 MAY BE ASSIGNED AS PER AVAILABILITY/SCHEME
15 BINARY INPUT (Single Point)
17 AUX POWER FAIL SP B706_BCUApplication$LPHD0$ST$AuxPwrFail stVal √ √
18 TIME SYNCHRONISATION ERROR SP B706_BCUApplication$LMTS0$ST$TmSynErr stVal √ √
19 BCU MODE SP B706_BCUApplication$LLN0$ST$LocKey stVal √
22 CT SF6 GAS PRESSURE REFILL LOW ALARM SP B706_BCUApplication$USER1$ST$SPS stVal √ √
23 CT SF6 GAS PRESSURE LOCKOUT SP B706_BCUApplication$USER1$ST$SPS1 stVal √ √
24 TRIP RELAY SUPERVISION SP B706_BCUApplication$USER5$ST$SPS stVal √ √
25 CARRIER CHANNEL-2 OUT SP B706_BCUApplication$USER5$ST$SPS1 stVal √ √
26 MAIN-2 RELAY FAULTY SP B706_BCUApplication$USER5$ST$SPS2 stVal √ √
27 EMERGENCY/MANUAL TRIP SP B706_BCUApplication$USER5$ST$SPS4 stVal √ √
28 SPEECH CHANNEL FAIL SP B706_BCUApplication$USER5$ST$SPS3 stVal √ √
29 SURGE ARRESTER B-PH SP B706_BCUApplication$USER5$ST$SPS7 stVal √ √
30 SURGE ARRESTER R-PH SP B706_BCUApplication$USER5$ST$SPS5 stVal √ √
31 SURGE ARRESTER Y-PH SP B706_BCUApplication$USER5$ST$SPS6 stVal √ √
32 89A POLE DESCREPENCY SP B706_BCUApplication$USER3$ST$SPS5 stVal √ √
33 89B POLE DESCREPENCY SP B706_BCUApplication$USER3$ST$SPS6 stVal √ √
34 CB DC SUPPLY-1/2 FAIL SP B706_BCUApplication$USER3$ST$SPS1 stVal √ √
35 CB SPRING NOT CHARGED B-PH SP B706_BCUApplication$USER3$ST$SPS4 stVal √ √
36 CB SPRING NOT CHARGED R-PH SP B706_BCUApplication$USER3$ST$SPS2 stVal √ √
37 CB SPRING NOT CHARGED Y-PH SP B706_BCUApplication$USER3$ST$SPS3 stVal √ √
38 CB SF6 GAS PRESSURE LOCKOUT SP B706_BCUApplication$USER3$ST$SPS stVal √ √
39 86B TRIP RELAY FAULTY SP B706_BCUApplication$USER4$ST$SPS3 stVal √ √
40 86A TRIP RELAY FAULTY SP B706_BCUApplication$USER4$ST$SPS3 stVal √ √
41 86A TRIP RELAY OPERATED SP B706_BCUApplication$USER4$ST$SPS2 stVal √ √
42 86B TRIP RELAY OPERATED SP B706_BCUApplication$USER4$ST$SPS6 stVal √ √
43 89L POLE DESCREPENCY SP B706_BCUApplication$USER4$ST$SPS stVal √ √
44 CARRIER CHANNEL-1 OUT SP B706_BCUApplication$USER4$ST$SPS4 stVal √ √
45 CB TC-1 FAULTY SP B706_BCUApplication$USER4$ST$SPS1 stVal √ √
46 CB TC-2 FAULTY SP B706_BCUApplication$USER4$ST$SPS5 stVal √ √
47 CB POLE DESCREPENCY OPTD-1
48 CB POLE DESCREPENCY OPTD-2 SP B706_BCUApplication$USER2$ST$SPS1 stVal √ √
49 CB SF6 GAS PRESSURE REFILL LOW ALARM SP B706_BCUApplication$USER2$ST$SPS stVal √ √
50 BUS-1 VT SELECTED SP B706_BCUApplication$USER6$ST$SPS1 stVal √
51 ICT LV VT SELECTED SP B706_BCUApplication$USER6$ST$SPS2 stVal √
52 LINE VT SELECTED SP B706_BCUApplication$USER6$ST$SPS stVal √
53 CB READY SP B706_BCUCB$XCBR1$ST$Rdy stVal √
54 EMERGENCY/MANUAL CB CLOSE SP B706_BCUCB$GAPC2$ST$Detected stVal √
55 DEVICE HEALTHY SP B706_BCUApplication$LPHD0$ST$PhyHealth:0 stVal:1 √
56 CB POSITION NO SYNC SP B706_BCUCB$CSWI1$ST$Pos noSync √ √
57 CB CLOSE INTERLOCK SP B706_BCUCB$CILO1$ST$EnaCls stVal √ √
58 765kV 765kV LINE 89AE1 OPEN INTERLOCK SP B706_BCU89AE1$CILO3$ST$EnaOpn stVal √ √
59 89AE2 OPEN INTERLOCK SP B706_BCU89AE2$CILO8$ST$EnaOpn stVal √ √
60 89BE OPEN INTERLOCK SP B706_BCU89BE$CILO5$ST$EnaOpn stVal √ √
61 89A OPEN INTERLOCK SP B706_BCU89A$CILO2$ST$EnaOpn stVal √ √
62 89B OPEN INTERLOCK SP B706_BCU89B$CILO4$ST$EnaOpn stVal √ √
63 89L OPEN INTERLOCK SP B706_BCU89L$CILO6$ST$EnaOpn stVal √ √
64 89LE OPEN INTERLOCK SP B706_BCU89LE$CILO7$ST$EnaOpn stVal √ √
67 BUSBAR 7ES-B1 OPEN(BUS EARTH SWITCH)
68 BUSBAR 7ES-B2 OPEN(BUS EARTH SWITCH)
69 BUSBAR 7ES-B1 CLOSE INTERLOCK
70 BUSBAR 7ES-B2 CLOSE INTERLOCK
71 GOOSE RECEIPT FAIL/TROUBLE SP B706_BCUApplication$USER6$ST$SPS3 stVal √ √
72 DFR/DR FAIL ALARM
73 GOOSE RECEIPT FAIL/TROUBLE SP B706_BCUApplication$LLN0$ST$SPS stVal √
74 A/R BLOCK SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$BlkFct stVal √
75 A/R FUNCTION OFF SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$Off stVal √
76 A/R FUNCTION ON SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$On stVal √
77 A/R READY SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$AutoRecSt:0 stVal:1 √
78 A/R UNSUCCESSFUL SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$AutoRecSt:0 stVal:10 √ √
80 A/R SUCCESSFUL SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$Successful stVal √
81 RECLAIM IN PROGRESS
82 MAIN A/R LOCKOUT
83 TIE A/R LOCKOUT
84 Tie CB A/R PRIORITY CLOSE
85 MAIN/TIE BCU HEALTHY
86 AR SINGLE PHASE TRIP PERMITTED
87 CB NOT READY SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$CBnotRdy stVal √
88 A/R CLOSE COMMAND INDICATION SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$OpCls general √
89 A/R IN PROGRESS SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$RecInit stVal √
92 POWER FACTOR ME_FL B706_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotPF:1 mag$f
93 FREQUENCY ME_FL B706_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$Hz:1 mag$f
94 ACTIVE POWER ME_FL B706_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotW:1 mag$f
95 REACTIVE POWER ME_FL B706_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVAr:1 mag$f
96 APPARENT POWER ME_FL B706_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVA:1 mag$f
97 I-R-PH CURRENT ME_FL B706_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsA$cVal$mag$f
98 I-Y-PH CURRENT ME_FL B706_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsB$cVal$mag$f
99 I-B-PH CURRENT ME_FL B706_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsC$cVal$mag$f
100 R-Y VOLTAGE ME_FL B706_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsAB$cVal$mag$f
101 Y-B VOLTAGE ME_FL B706_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsBC$cVal$mag$f
102 B-R VOLYAGE ME_FL B706_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsCA$cVal$mag$f
103 CB-B-PH COUNTER ME_I B706_BCUCBB$XCBR1$ST$OpCnt stVal
104 CB-R-PH COUNTER ME_I B706_BCUCBR$XCBR1$ST$OpCnt stVal
105 CB-Y-PH COUNTER ME_I B706_BCUCBY$XCBR1$ST$OpCnt stVal
106 SURGE ARRESTER B-PH ME_I
107 SURGE ARRESTER R-PH ME_I
108 SURGE ARRESTER Y-PH ME_I
109 CB R-PHASE OPERATION COUNTER ME_I
110 CB Y-PHASE OPERATION COUNTER ME_I
111 CB B-PHASE OPERATION COUNTER ME_I
115 CB CONTROL DC B706_BCUCB$CSWI1$CO$Pos:8 Oper$ctlVal √
116 89AE1 CONTROL DC B706_BCU89AE1$CSWI3$CO$Pos:8 Oper$ctlVal √
117 89AE2 CONTROL DC B706_BCU89AE2$CSWI8$CO$Pos:8 Oper$ctlVal √
118 89BE CONTROL DC B706_BCU89BE$CSWI5$CO$Pos:8 Oper$ctlVal √
119 89A CONTROL DC B706_BCU89A$CSWI2$CO$Pos:8 Oper$ctlVal √
120 89B CONTROL DC B706_BCU89B$CSWI4$CO$Pos:8 Oper$ctlVal √
121 89L CONTROL DC B706_BCU89L$CSWI6$CO$Pos:8 Oper$ctlVal √
122 89LE CONTROL DC B706_BCU89LE$CSWI7$CO$Pos:8 Oper$ctlVal √
123 CB CONTROL NO SYNC SC B706_BCUCB$CSWI1$CO$Pos Oper$noSync √
124 86A TRIP RELAY RESET COMMAND SC B706_BCUApplication$USER2$CO$SPC:8 Oper$ctlVal √
125 86B TRIP RELAY RESET COMMAND SC B706_BCUApplication$USER2$CO$SPC1:8 Oper$ctlVal √
126 A/R ON CONTROL SC B706_BCUApplication$USER8$CO$SPC:8 Oper$ctlVal √
127 A/R OFF CONTROL SC B706_BCUApplication$USER8$CO$SPC1:8 Oper$ctlVal √
128 MAIN-1 LED RESET SC
129 MAIN-2 LED RESET SC
130 SETTINGS CHANGED
131 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Feeder Name Assumed as Main-1 relay
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION EVENT ALARM
1 765kV 765kV LINE FAULT DISTANCE ME_FL B706_21_1PROT$RFLO1$MX$FltDiskm:0 mag$f
2 FAULT CURRENT ME_FL
3 FAULT LOCATION DISTANCE ME_FL
4 MAIN-1 CARRIER RECEIVE CHANNEL-1 ME_I
5 MAIN-1 CARRIER SEND CHANNEL-1 ME_I
6 MAIN-2 CARRIER RECEIVE CHANNEL-1 ME_I
7 MAIN-2 CARRIER SEND CHANNEL-1 ME_I
8 MAIN-2 CARRIER RECEIVE CHANNEL-2 ME_I
9 MAIN-2 CARRIER SEND CHANNEL-2 ME_I
10 MAIN-1 CARRIER RECEIVE CHANNEL-2 ME_I
11 MAIN-1 CARRIER SEND CHANNEL-2 ME_I
12 DT RECEIVE CHANNEL-1 ME_I
13 DT SEND CHANNEL-1 ME_I
14 DT RECEIVE CHANNEL-2 ME_I
15 DT SEND CHANNEL-2 ME_I
16 CARRIER FAIL CHANNEL-1 ME_I
17 CARRIER FAIL CHANNEL-2 ME_I
18 CARRIER RECEIVED CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO3:0 stVal
19 CARRIER RECEIVED CHANNEL-2 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO4:0 stVal
20 CARRIER SEND CHANNEL-2 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO1:0 stVal
21 CARRIER SEND CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO2:0 stVal
22 DIRECT TRIP RECEIVED CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO6:0 stVal
23 DIRECT TRIP SEND CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO5:0 stVal
24 CARRIER FAIL CHANNEL-1 ME_I B706_21_1CTRL$GGIO2$ST$ISCSO7:0 stVal
25 CARRIER FAIL CHANNEL-2 ME_I B706_21_1CTRL$GGIO2$ST$ISCSO8:0 stVal
27 BINARY INPUT (Single Point)
28 DIRECT TRIP SEND CHANNEL-2 GOOSE
29 CARRIER FAIL CHANNEL-1 SP B706_21_1CTRL$GGIO1$ST$SPCSO25:0 stVal √ √
30 NO VOLTAGE IN LINE SP B706_21_1CTRL$GGIO1$ST$SPCSO21:0 stVal √ √
31 A/R BLOCK SP B706_21_1CTRL$GGIO1$ST$SPCSO14:0 stVal √
32 MAIN A/R LOCKOUT
33 TIE A/R LOCKOUT
34 DIRECT TRIP SEND CHANNEL-1 SP B706_21_1CTRL$GGIO1$ST$SPCSO18:0 stVal √ √
35 GOOSE RECEIPT FAIL/TROUBLE SP B706_21_1CTRL$GGIO1$ST$SPCSO24:0 stVal √ √
36 MAIN-2 RELAY FAIL SP B706_21_1CTRL$GGIO1$ST$SPCSO20:0 stVal √
37 89L OPEN FOR STUB SP B706_21_1CTRL$GGIO1$ST$SPCSO17:0 stVal √ √
38 DIRECT TRIP RECEIVED CHANNEL-1 SP B706_21_1CTRL$GGIO1$ST$SPCSO16:0 stVal √ √
39 LBB OPERATED SP B706_21_1CTRL$GGIO1$ST$SPCSO10:0 stVal √ √
40 TIME SYNCHRONISATION ERROR SP B706_21_1EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
41 VT FUSE FAILURE SP B706_21_1EXT$pdGGIO3$ST$SPCSO42:0 stVal √ √
42 BROKEN CONDUCTOR SP B706_21_1EXT$pdGGIO4$ST$SPCSO3:0 stVal √ √
43 EMERGENCY/MANUAL CLOSE SP B706_21_1EXT$pdGGIO6$ST$SPCSO36:0 stVal √
44 CARRIER RECEIVED CHANNEL-1 SP B706_21_1EXT$pdGGIO63$ST$SPCSO38:0 stVal √ √
45 CARRIER RECEIVED CHANNEL-2 SP B706_21_1EXT$pdGGIO63$ST$SPCSO42:0 stVal √ √
46 CARRIER FAULTY SP B706_21_1EXT$pdGGIO63$ST$SPCSO37:0 stVal √ √ NOT REQUIRED
47 SOTF PICKUP SP B706_21_1EXT$pdGGIO67$ST$SPCSO57:0 stVal √
48 SOTF TRIP( OC)
49 SOTF TRIP( IMPEDANCE Z1B) SP B706_21_1EXT$pdGGIO68$ST$SPCSO7:0 stVal √ √
50 CARRIER SEND CHANNEL-1 SP B706_21_1PROT$PSCH1$ST$ProTx stVal √ √
51 CARRIER SEND CHANNEL-2 GOOSE
52 DIRECT TRIP RECEIVED CHANNEL-2 GOOSE
53 CARRIER RECEIVED SP B706_21_1PROT$PSCH1$ST$ProRx stVal √ √ NOT REQUIRED
54 CARRIER ADDIED TRIP/Z COM. TRIP SP B706_21_1PROT$PSCH1$ST$Op general √ √
55 MAIN A/R OPTD
56 TIE A/R OPTD
57 CB MANUAL CLOSE
58 CB MANUAL TRIP
59 86 GROUP-A OPTD
60 86 GROUP-B OPTD
61 MAIN A/R START
62 TIE A/R START
63 DISTANCE ZONE-1 PICKUP SP B706_21_1PROT$PDIS1$ST$Str general √
64 DISTANCE PROTN ZONE-1 TRIP SP B706_21_1PROT$PDIS1$ST$Op general √ √
65 DISTANCE PROTN ZONE-1 R-PH TRIP SP B706_21_1PROT$PDIS1$ST$Op phsA √ √
66 DISTANCE PROTN ZONE-1 Y-PH TRIP SP B706_21_1PROT$PDIS1$ST$Op phsB √ √
67 DISTANCE PROTN ZONE-1 B-PH TRIP SP B706_21_1PROT$PDIS1$ST$Op phsC √ √
68 DISTANCE ZONE-2 PICKUP SP B706_21_1PROT$PDIS2$ST$Str general √
69 DISTANCE PROTN ZONE-2 TRIP SP B706_21_1PROT$PDIS2$ST$Op general √ √
70 DISTANCE PROTN ZONE-2 R-PH TRIP SP B706_21_1PROT$PDIS2$ST$Op phsA √ √
71 DISTANCE PROTN ZONE-2 Y-PH TRIP SP B706_21_1PROT$PDIS2$ST$Op phsB √ √
72 DISTANCE PROTN ZONE-2 B-PH TRIP SP B706_21_1PROT$PDIS2$ST$Op phsC √ √
73 DISTANCE ZONE-3 PICKUP SP B706_21_1PROT$PDIS3$ST$Str general √
74 DISTANCE PROTN ZONE-3 TRIP SP B706_21_1PROT$PDIS3$ST$Op general √ √
75 DISTANCE ZONE-4 PICKUP SP B706_21_1PROT$PDIS4$ST$Str general √
76 DISTANCE PROTN ZONE-4 TRIP SP B706_21_1PROT$PDIS4$ST$Op general √ √
77 DISTANCE PROTN ZONE-4 R-PH TRIP
78 DISTANCE PROTN ZONE-4 Y-PH TRIP
79 DISTANCE PROTN ZONE-4 B-PH TRIP
80 DISTANCE PROTN ZONE-1B PICKUP SP B706_21_1PROT$PDIS10$ST$Str general √
81 DISTANCE PROTN ZONE-1B TRIP SP B706_21_1PROT$PDIS10$ST$Op general √ √
82 DISTANCE PROTN ZONE-1B B-PH TRIP SP B706_21_1PROT$PDIS10$ST$Op phsC √ √
83 DISTANCE PROTN ZONE-1B R-PH TRIP SP B706_21_1PROT$PDIS10$ST$Op phsA √ √
84 DISTANCE PROTN ZONE-1B Y-PH TRIP SP B706_21_1PROT$PDIS10$ST$Op phsB √ √
85 DISTANCE PROTN ZONE-5 PICKUP
86 STUB PICKUP SP B706_21_1PROT$PTOC4$ST$Str general √
87 STUB OPERATED SP B706_21_1PROT$PTOC4$ST$Op general √ √
88 DEF FAULT PICKUP SP B706_21_1PROT$PTOC8$ST$Str general √
89 DEF FAULT TRIP SP B706_21_1PROT$PTOC8$ST$Op general √ √
90 OVERVOLTAGE STAGE-1-PH-N PICKUP SP B706_21_1PROT$PTOV1$ST$Str general √
91 OVERVOLTAGE STAGE-1 -PH-N TRIP SP B706_21_1PROT$PTOV1$ST$Op general √ √
92 OVERVOLTAGE STAGE-2-PH-N PICKUP SP B706_21_1PROT$PTOV2$ST$Str general √
93 OVERVOLTAGE STAGE-2-PH-N TRIP SP B706_21_1PROT$PTOV2$ST$Op general √ √
94 OVERVOLTAGE STAGE-1-PH-PH PICKUP SP B706_21_1PROT$PTOV3$ST$Str general √
95 OVERVOLTAGE STAGE-1-PH-PH TRIP SP B706_21_1PROT$PTOV3$ST$Op general √ √
96 OVERVOLTAGE STAGE-2-PH-PH PICKUP SP B706_21_1PROT$PTOV4$ST$Str general √
97 OVERVOLTAGE STAGE-2-PH-PH TRIP SP B706_21_1PROT$PTOV4$ST$Op general √ √
98 POWER SWING ZONE-1 DETECTED SP B706_21_1PROT$RPSB1$ST$Str general √ √
99 POWER SWING ZONE-1 BLOCK SP B706_21_1PROT$RPSB1$ST$BlkZn stVal √
100 POWER SWING ZONE-1B DETECTED SP B706_21_1PROT$RPSB10$ST$Str general √ √
101 POWER SWING ZONE-1B BLOCK SP B706_21_1PROT$RPSB10$ST$BlkZn stVal √
102 POWER SWING ZONE-2 DETECTED SP B706_21_1PROT$RPSB2$ST$Str general √ √
103 POWER SWING ZONE-2 BLOCK SP B706_21_1PROT$RPSB2$ST$BlkZn stVal √
104 POWER SWING ZONE-3 DETECTED SP B706_21_1PROT$RPSB3$ST$Str general √ √
105 POWER SWING ZONE-3 BLOCK SP B706_21_1PROT$RPSB3$ST$BlkZn stVal √
106 POWER SWING ZONE-4 DETECTED SP B706_21_1PROT$RPSB4$ST$Str general √ √
107 POWER SWING ZONE-4 BLOCK SP B706_21_1PROT$RPSB4$ST$BlkZn stVal √
108 BUSBAR PROTN OPTD
109 RELAY LED RESET SC
110 MAIN BCU FAIL
111 TIE BCU FAIL
112 MANUAL DR TRIGGER SC
113 GENERAL TRIP SP B706_21_1PROT$PTRC1$ST$Tr general √ √
114 DEVICE HEALTHY SP B707_21_1PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
115 MAIN-2 PROTN OPTD
116 STUB BLOCKED SP B706_21_1PROT$PTOC4$ST$Blk stVal √ √
117 SETTINGS CHANGED
118 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Feeder Name Assumed as Main-1 relay
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION EVENT ALARM
1 765kV 765kV LINE FAULT DISTANCE ME_FL B706_21_1PROT$RFLO1$MX$FltDiskm:0 mag$f
2 FAULT CURRENT ME_FL
3 FAULT LOCATION DISTANCE ME_FL
4 MAIN-1 CARRIER RECEIVE CHANNEL-1 ME_I
5 MAIN-1 CARRIER SEND CHANNEL-1 ME_I
6 MAIN-2 CARRIER RECEIVE CHANNEL-1 ME_I
7 MAIN-2 CARRIER SEND CHANNEL-1 ME_I
8 MAIN-2 CARRIER RECEIVE CHANNEL-2 ME_I
9 MAIN-2 CARRIER SEND CHANNEL-2 ME_I
10 MAIN-1 CARRIER RECEIVE CHANNEL-2 ME_I
11 MAIN-1 CARRIER SEND CHANNEL-2 ME_I
12 DT RECEIVE CHANNEL-1 ME_I
13 DT SEND CHANNEL-1 ME_I
14 DT RECEIVE CHANNEL-2 ME_I
15 DT SEND CHANNEL-2 ME_I
16 CARRIER FAIL CHANNEL-1 ME_I
17 CARRIER FAIL CHANNEL-2 ME_I
18 CARRIER RECEIVED CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO3:0 stVal
19 CARRIER RECEIVED CHANNEL-2 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO4:0 stVal
20 CARRIER SEND CHANNEL-2 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO1:0 stVal
21 CARRIER SEND CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO2:0 stVal
22 DIRECT TRIP RECEIVED CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO6:0 stVal
23 DIRECT TRIP SEND CHANNEL-1 ME_I B706_21_1CTRL$GGIO1$ST$ISCSO5:0 stVal
24 CARRIER FAIL CHANNEL-1 ME_I B706_21_1CTRL$GGIO2$ST$ISCSO7:0 stVal
25 CARRIER FAIL CHANNEL-2 ME_I B706_21_1CTRL$GGIO2$ST$ISCSO8:0 stVal
27 BINARY INPUT (Single Point)
28 LINE DIFFERENTIAL GENERAL TIP
29 LINE DIFFERENTIAL REMOTE TRIP
30 LINE DIFFERENTIAL R-PH TRIP
31 LINE DIFFERENTIAL Y-PH TRIP
32 LINE DIFFERENTIAL -PH TRIP
33 LINE COMMUNICATION CHANNEL-1 FAULTY
34 LINE COMMUNICATION CHANNEL-2 FAULTY
35 DIRECT TRIP SEND CHANNEL-2 GOOSE
36 CARRIER FAIL CHANNEL-1 SP B706_21_1CTRL$GGIO1$ST$SPCSO25:0 stVal √ √
37 NO VOLTAGE IN LINE SP B706_21_1CTRL$GGIO1$ST$SPCSO21:0 stVal √ √
38 A/R BLOCK SP B706_21_1CTRL$GGIO1$ST$SPCSO14:0 stVal √
39 MAIN A/R LOCKOUT
40 TIE A/R LOCKOUT
41 DIRECT TRIP SEND CHANNEL-1 SP B706_21_1CTRL$GGIO1$ST$SPCSO18:0 stVal √ √
42 GOOSE RECEIPT FAIL/TROUBLE SP B706_21_1CTRL$GGIO1$ST$SPCSO24:0 stVal √ √
43 MAIN-2 RELAY FAIL SP B706_21_1CTRL$GGIO1$ST$SPCSO20:0 stVal √
44 89L OPEN FOR STUB SP B706_21_1CTRL$GGIO1$ST$SPCSO17:0 stVal √ √
45 DIRECT TRIP RECEIVED CHANNEL-1 SP B706_21_1CTRL$GGIO1$ST$SPCSO16:0 stVal √ √
46 LBB OPERATED SP B706_21_1CTRL$GGIO1$ST$SPCSO10:0 stVal √ √
47 TIME SYNCHRONISATION ERROR SP B706_21_1EXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
48 VT FUSE FAILURE SP B706_21_1EXT$pdGGIO3$ST$SPCSO41:0 stVal √ √
49 BROKEN CONDUCTOR SP B706_21_1EXT$pdGGIO4$ST$SPCSO3:0 stVal √ √
50 EMERGENCY/MANUAL CLOSE SP B706_21_1EXT$pdGGIO6$ST$SPCSO36:0 stVal √
51 CARRIER RECEIVED CHANNEL-1 SP B706_21_1EXT$pdGGIO63$ST$SPCSO38:0 stVal √ √
52 CARRIER RECEIVED CHANNEL-2 SP B706_21_1EXT$pdGGIO63$ST$SPCSO42:0 stVal √ √
53 CARRIER FAULTY SP B706_21_1EXT$pdGGIO63$ST$SPCSO37:0 stVal √ √ NOT REQUIRED
54 SOTF PICKUP SP B706_21_1EXT$pdGGIO67$ST$SPCSO57:0 stVal √
55 SOTF TRIP( OC)
56 SOTF TRIP( IMPEDANCE Z1B) SP B706_21_1EXT$pdGGIO68$ST$SPCSO7:0 stVal √ √
57 CARRIER SEND CHANNEL-1 SP B706_21_1PROT$PSCH1$ST$ProTx stVal √ √
58 CARRIER SEND CHANNEL-2 GOOSE
59 DIRECT TRIP RECEIVED CHANNEL-2 GOOSE
60 CARRIER RECEIVED SP B706_21_1PROT$PSCH1$ST$ProRx stVal √ √ NOT REQUIRED
61 CARRIER ADDIED TRIP/Z COM. TRIP SP B706_21_1PROT$PSCH1$ST$Op general √ √
62 MAIN A/R OPTD
63 TIE A/R OPTD
64 CB MANUAL CLOSE
65 CB MANUAL TRIP
66 86 GROUP-A OPTD
67 86 GROUP-B OPTD
68 MAIN A/R START
69 TIE A/R START
70 DISTANCE ZONE-1 PICKUP SP B706_21_1PROT$PDIS1$ST$Str general √
71 DISTANCE PROTN ZONE-1 TRIP SP B706_21_1PROT$PDIS1$ST$Op general √ √
72 DISTANCE PROTN ZONE-1 R-PH TRIP SP B706_21_1PROT$PDIS1$ST$Op phsA √ √
73 DISTANCE PROTN ZONE-1 Y-PH TRIP SP B706_21_1PROT$PDIS1$ST$Op phsB √ √
74 DISTANCE PROTN ZONE-1 B-PH TRIP SP B706_21_1PROT$PDIS1$ST$Op phsC √ √
75 DISTANCE ZONE-2 PICKUP SP B706_21_1PROT$PDIS2$ST$Str general √
76 DISTANCE PROTN ZONE-2 TRIP SP B706_21_1PROT$PDIS2$ST$Op general √ √
77 DISTANCE PROTN ZONE-2 R-PH TRIP SP B706_21_1PROT$PDIS2$ST$Op phsA √ √
78 DISTANCE PROTN ZONE-2 Y-PH TRIP SP B706_21_1PROT$PDIS2$ST$Op phsB √ √
79 DISTANCE PROTN ZONE-2 B-PH TRIP SP B706_21_1PROT$PDIS2$ST$Op phsC √ √
80 DISTANCE ZONE-3 PICKUP SP B706_21_1PROT$PDIS3$ST$Str general √
81 DISTANCE PROTN ZONE-3 TRIP SP B706_21_1PROT$PDIS3$ST$Op general √ √
82 DISTANCE ZONE-4 PICKUP SP B706_21_1PROT$PDIS4$ST$Str general √
83 DISTANCE PROTN ZONE-4 TRIP SP B706_21_1PROT$PDIS4$ST$Op general √ √
84 DISTANCE PROTN ZONE-4 R-PH TRIP
85 DISTANCE PROTN ZONE-4 Y-PH TRIP
86 DISTANCE PROTN ZONE-4 B-PH TRIP
87 DISTANCE PROTN ZONE-1B PICKUP SP B706_21_1PROT$PDIS10$ST$Str general √
88 DISTANCE PROTN ZONE-1B TRIP SP B706_21_1PROT$PDIS10$ST$Op general √ √
89 DISTANCE PROTN ZONE-1B B-PH TRIP SP B706_21_1PROT$PDIS10$ST$Op phsC √ √
90 DISTANCE PROTN ZONE-1B R-PH TRIP SP B706_21_1PROT$PDIS10$ST$Op phsA √ √
91 DISTANCE PROTN ZONE-1B Y-PH TRIP SP B706_21_1PROT$PDIS10$ST$Op phsB √ √
92 DISTANCE PROTN ZONE-5 PICKUP
93 STUB PICKUP SP B706_21_1PROT$PTOC4$ST$Str general √
94 STUB OPERATED SP B706_21_1PROT$PTOC4$ST$Op general √ √
95 DEF FAULT PICKUP SP B706_21_1PROT$PTOC8$ST$Str general √
96 DEF FAULT TRIP SP B706_21_1PROT$PTOC8$ST$Op general √ √
97 OVERVOLTAGE STAGE-1-PH-N PICKUP SP B706_21_1PROT$PTOV1$ST$Str general √
98 OVERVOLTAGE STAGE-1 -PH-N TRIP SP B706_21_1PROT$PTOV1$ST$Op general √ √
99 OVERVOLTAGE STAGE-2-PH-N PICKUP SP B706_21_1PROT$PTOV2$ST$Str general √
100 OVERVOLTAGE STAGE-2-PH-N TRIP SP B706_21_1PROT$PTOV2$ST$Op general √ √
101 OVERVOLTAGE STAGE-1-PH-PH PICKUP SP B706_21_1PROT$PTOV3$ST$Str general √
102 OVERVOLTAGE STAGE-1-PH-PH TRIP SP B706_21_1PROT$PTOV3$ST$Op general √ √
103 OVERVOLTAGE STAGE-2-PH-PH PICKUP SP B706_21_1PROT$PTOV4$ST$Str general √
104 OVERVOLTAGE STAGE-2-PH-PH TRIP SP B706_21_1PROT$PTOV4$ST$Op general √ √
105 POWER SWING ZONE-1 DETECTED SP B706_21_1PROT$RPSB1$ST$Str general √ √
106 POWER SWING ZONE-1 BLOCK SP B706_21_1PROT$RPSB1$ST$BlkZn stVal √
107 POWER SWING ZONE-1B DETECTED SP B706_21_1PROT$RPSB10$ST$Str general √ √
108 POWER SWING ZONE-1B BLOCK SP B706_21_1PROT$RPSB10$ST$BlkZn stVal √
109 POWER SWING ZONE-2 DETECTED SP B706_21_1PROT$RPSB2$ST$Str general √ √
110 POWER SWING ZONE-2 BLOCK SP B706_21_1PROT$RPSB2$ST$BlkZn stVal √
111 POWER SWING ZONE-3 DETECTED SP B706_21_1PROT$RPSB3$ST$Str general √ √
112 POWER SWING ZONE-3 BLOCK SP B706_21_1PROT$RPSB3$ST$BlkZn stVal √
113 POWER SWING ZONE-4 DETECTED SP B706_21_1PROT$RPSB4$ST$Str general √ √
114 POWER SWING ZONE-4 BLOCK SP B706_21_1PROT$RPSB4$ST$BlkZn stVal √
115 BUSBAR PROTN OPTD
116 RELAY LED RESET SC
117 MAIN BCU FAIL
118 TIE BCU FAIL
119 MANUAL DR TRIGGER SC
120 GENERAL TRIP SP B706_21_1PROT$PTRC1$ST$Tr general √ √
121 DEVICE HEALTHY SP B707_21_1PROT$LPHD1$ST$PhyHealth:0 stVal:1 √
122 MAIN-2 PROTN OPTD
123 STUB BLOCKED SP B706_21_1PROT$PTOC4$ST$Blk stVal √ √
124 SETTINGS CHANGED
125 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
SIEMENS SCADA GENERAL SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (INDEX)
Sheet Ref. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 7SS52 MCU-1 BUSBAR MAIN-1 STNM7XXBB1M1 BCU is for each bay so 7XX refers to Bay
4 7SS52 MCU-2 BUSBAR MAIN-1 STNM7XXBB1M2 Bay No. 7XX will be always the main bay number for the ICT feeder
NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "7XX" stand for Bay name, example if the bay no 701 then same has to be implemented like STNM701BCU
Sr. No. Voltage Level Source NAME ( 765KV MCU-1)
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION Event Alarm Remarks
BINARY INPUT (Double Point)
1 765kV MCU-1 DC SOURCE-2 FAIL SP MCU_II_765kVCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
2 MCU-2 UNHEALTHY SP MCU_II_765kVCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
3 BREAKER FAILURE TRANSFER TRIP SP MCU_II_765kVEXT$pdGGIO164$ST$SPCSO1:0 stVal √ √
4 TIME SYNCHRONISATION ERROR SP MCU_II_765kVEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
5 BUSBAR TRIP SP MCU_II_765kVPROT$PDIF1$ST$Op general √ √
6 BAY UNIT-01 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO1:0 stVal √ √
7 BAY UNIT-02 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO8:0 stVal √ √
8 BAY UNIT-03 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO16:0 stVal √ √
9 BAY UNIT-03 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO24:0 stVal √ √
10 BAY UNIT-05 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO33:0 stVal √ √
11 BAY UNIT-06 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO41:0 stVal √ √
12 BAY UNIT-07 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO49:0 stVal √ √
13 BAY UNIT-08 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO57:0 stVal √ √
14 BUS-1 PROTECTION BLOCKED BY HANDLE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO9:0 stVal √ √
15 BUS-2 PROTECTION BLOCKED BY HANDLE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO26:0 stVal √ √
16 BUS-1 PROTECTION BLOCKED BY INTERM STATE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO17:0 stVal √ √
17 BUS-2 PROTECTION BLOCKED BY INTERM STATE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO33:0 stVal √ √
18 CURRENT SUPERVISION BUS-1 SP MCU_II_765kVPROT$GGIO2$ST$SPCSO10:0 stVal √ √
19 CURRENT SUPERVISION BUS-2 SP MCU_II_765kVPROT$GGIO2$ST$SPCSO27:0 stVal √ √
20 Trip command BF for BUS-1 R-PH SP MCU_II_765kVPROT$GGIO2$ST$SPCSO5:0 stVal √ √
21 Trip command BF for BUS-1 Y-PH SP MCU_II_765kVPROT$GGIO2$ST$SPCSO6:0 stVal √ √
22 Trip command BF for BUS-1 B-PH SP MCU_II_765kVPROT$GGIO2$ST$SPCSO7:0 stVal √ √
23 Trip command BF for BUS-2 R-PH SP MCU_II_765kVPROT$GGIO2$ST$SPCSO22:0 stVal √ √
24 Trip command BF for BUS-2 Y-PH SP MCU_II_765kVPROT$GGIO2$ST$SPCSO23:0 stVal √ √
25 Trip command BF for BUS-2 B-PH SP MCU_II_765kVPROT$GGIO2$ST$SPCSO24:0 stVal √ √
26 3-PH Trip command BF for BUS-1 SP MCU_II_765kVPROT$GGIO2$ST$SPCSO1:0 stVal √ √
27 3-PH Trip command BF for BUS-2 SP MCU_II_765kVPROT$GGIO2$ST$SPCSO18:0 stVal √ √
28 LBB RETRIP SP MCU_II_765kVPROT$RBRF1$ST$OpIn general √ √
29 LBB TRIP SP MCU_II_765kVPROT$RBRF1$ST$OpEx general √ √
30 GENERAL TRIP SP MCU_II_765kVPROT$PTRC1$ST$Tr general √ √
31 GENERAL TRIP R-PH SP MCU_II_765kVPROT$PTRC1$ST$Tr phsA √ √
32 GENERAL TRIP Y-PH SP MCU_II_765kVPROT$PTRC1$ST$Tr phsB √ √
33 GENERAL TRIP B-PH SP MCU_II_765kVPROT$PTRC1$ST$Tr phsC √ √
34 DEVICE OK SP MCU_II_765kVPROT$LPHD1$ST$PhyHealth:0 stVal:1 √ √
35 BAY UNIT-01 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO34:0 stVal √ √
36 BAY UNIT-02 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO35:0 stVal √ √
37 BAY UNIT-03 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO36:0 stVal √ √
38 BAY UNIT-04 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO37:0 stVal √ √
39 BAY UNIT-05 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO38:0 stVal √ √
40 BAY UNIT-06 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO39:0 stVal √ √
41 BAY UNIT-07 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO40:0 stVal √ √
42 BAY UNIT-08 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO41:0 stVal √ √
43 Trip repeat Bay Unit-01 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO2:0 stVal √ √
44 Trip repeat Bay Unit-01 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO3:0 stVal √ √
45 Trip repeat Bay Unit-01 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO4:0 stVal √ √
46 Trip repeat Bay Unit-02 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO9:0 stVal √ √
47 Trip repeat Bay Unit-02 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO10:0 stVal √ √
48 Trip repeat Bay Unit-02 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO11:0 stVal √ √
49 Trip repeat Bay Unit-03 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO17:0 stVal √ √
50 Trip repeat Bay Unit-03 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO18:0 stVal √ √
51 Trip repeat Bay Unit-03 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO19:0 stVal √ √
52 Trip repeat Bay Unit-04 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO25:0 stVal √ √
53 Trip repeat Bay Unit-04 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO26:0 stVal √ √
54 Trip repeat Bay Unit-04 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO27:0 stVal √ √
55 Trip repeat Bay Unit-05 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO34:0 stVal √ √
56 Trip repeat Bay Unit-05 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO35:0 stVal √ √
57 Trip repeat Bay Unit-05 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO36:0 stVal √ √
58 Trip repeat Bay Unit-06 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO42:0 stVal √ √
59 Trip repeat Bay Unit-06 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO43:0 stVal √ √
60 Trip repeat Bay Unit-06 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO44:0 stVal √ √
61 Trip repeat Bay Unit-07 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO50:0 stVal √ √
62 Trip repeat Bay Unit-07 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO51:0 stVal √ √
63 Trip repeat Bay Unit-07 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO52:0 stVal √ √
64 Trip repeat Bay Unit-08 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO58:0 stVal √ √
65 Trip repeat Bay Unit-08 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO59:0 stVal √ √
66 Trip repeat Bay Unit-08 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO60:0 stVal √ √
67 Transfer Trip BUS-1 SP MCU_II_765kVPROT$GGIO2$ST$SPCSO8:0 stVal √ √
68 Transfer Trip BUS-2 SP MCU_II_765kVPROT$GGIO2$ST$SPCSO25:0 stVal √ √
69 BUS ZONE 1 TRIP SP MCU_II_765kVPROT$GGIO2$ST$SPCSO28:0 stVal √ √
70 BUS ZONE 2 TRIP SP MCU_II_765kVPROT$GGIO2$ST$SPCSO24:0 stVal √ √
71 BUSBAR CHECKZONE ALARM
72 BUSBAR CHECKZONE TRIP
73 BREAKER FAILURE - BUSBAR 1 BLOCKED
74 BREAKER FAILURE - BUSBAR 2 BLOCKED
75 ISOLATOR IN INTERMEDIATE STATUS
77 BUSBAR BLOCKED DUE TO COMMUNICATION ERROR_Bay_n
78 BAY_N_BREAKER FAILURE R-PH INITIATION
79 BAY_N_BREAKER FAILURE Y-PH INITIATION
80 BAY_N_BREAKER FAILURE B-PH INITIATION
81 BAY_N_BREAKER FAILURE 3PH INITIATION
82 BAY_N_EXTERNAL BUSBAR ZONE n
83 BAY_N_BREAKER FAILURE RETRIP
84 BAY_N_BREAKER FAILURE BACKTRIP
85 BAY_N_BREAKER FAILURE RPH- RETRIP
86 BAY_N_BREAKER FAILURE YPH- RETRIP
87 BAY_N_BREAKER FAILURE BPH- RETRIP
88 BBP CENTRAL UNIT IED UNHEALTHY
89 SETTING CHANGE
90 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Source NAME ( 765KV MCU-2)
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION Event Alarm Remarks
BINARY INPUT (Double Point)
1 765kV MCU-1 DC SOURCE-1 FAIL SP MCU_II_765kVCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
2 MCU-1 UNHEALTHY SP MCU_II_765kVCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
3 BREAKER FAILURE TRANSFER TRIP SP MCU_II_765kVEXT$pdGGIO164$ST$SPCSO1:0 stVal √ √
4 TIME SYNCHRONISATION ERROR SP MCU_II_765kVEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
5 BUSBAR TRIP SP MCU_II_765kVPROT$PDIF1$ST$Op general √ √
6 BAY UNIT-01 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO1:0 stVal √ √
7 BAY UNIT-02 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO8:0 stVal √ √
8 BAY UNIT-03 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO16:0 stVal √ √
9 BAY UNIT-04 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO24:0 stVal √ √
10 BAY UNIT-05 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO33:0 stVal √ √
11 BAY UNIT-06 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO41:0 stVal √ √
12 BAY UNIT-07 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO49:0 stVal √ √
13 BAY UNIT-08 FAILURE SP MCU_II_765kVPROT$GGIO1$ST$SPCSO57:0 stVal √ √
14 BUS-1 PROTECTION BLOCKED BY HANDLE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO9:0 stVal √ √
15 BUS-2 PROTECTION BLOCKED BY HANDLE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO26:0 stVal √ √
16 BUS-1 PROTECTION BLOCKED BY INTERM STATE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO17:0 stVal √ √
17 BUS-2 PROTECTION BLOCKED BY INTERM STATE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO33:0 stVal √ √
18 CURRENT SUPERVISION BUS-1 SP MCU_II_765kVPROT$GGIO2$ST$SPCSO10:0 stVal √ √
19 CURRENT SUPERVISION BUS-2 SP MCU_II_765kVPROT$GGIO2$ST$SPCSO27:0 stVal √ √
20 Trip command BF for BUS-1 R-PH SP MCU_II_765kVPROT$GGIO2$ST$SPCSO5:0 stVal √ √
21 Trip command BF for BUS-1 Y-PH SP MCU_II_765kVPROT$GGIO2$ST$SPCSO6:0 stVal √ √
22 Trip command BF for BUS-1 B-PH SP MCU_II_765kVPROT$GGIO2$ST$SPCSO7:0 stVal √ √
23 Trip command BF for BUS-2 R-PH SP MCU_II_765kVPROT$GGIO2$ST$SPCSO22:0 stVal √ √
24 Trip command BF for BUS-2 Y-PH SP MCU_II_765kVPROT$GGIO2$ST$SPCSO23:0 stVal √ √
25 Trip command BF for BUS-2 B-PH SP MCU_II_765kVPROT$GGIO2$ST$SPCSO24:0 stVal √ √
26 3-PH Trip command BF for BUS-1 SP MCU_II_765kVPROT$GGIO2$ST$SPCSO1:0 stVal √ √
27 3-PH Trip command BF for BUS-2 SP MCU_II_765kVPROT$GGIO2$ST$SPCSO18:0 stVal √ √
28 LBB RETRIP SP MCU_II_765kVPROT$RBRF1$ST$OpIn general √ √
29 LBB TRIP SP MCU_II_765kVPROT$RBRF1$ST$OpEx general √ √
30 GENERAL TRIP SP MCU_II_765kVPROT$PTRC1$ST$Tr general √ √
31 GENERAL TRIP R-PH SP MCU_II_765kVPROT$PTRC1$ST$Tr phsA √ √
32 GENERAL TRIP Y-PH SP MCU_II_765kVPROT$PTRC1$ST$Tr phsB √ √
33 GENERAL TRIP B-PH SP MCU_II_765kVPROT$PTRC1$ST$Tr phsC √ √
34 DEVICE OK SP MCU_II_765kVPROT$LPHD1$ST$PhyHealth:0 stVal:1 √ √
35 BAY UNIT-01 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO34:0 stVal √ √
36 BAY UNIT-02 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO35:0 stVal √ √
37 BAY UNIT-03 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO36:0 stVal √ √
38 BAY UNIT-04 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO37:0 stVal √ √
39 BAY UNIT-05 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO38:0 stVal √ √
40 BAY UNIT-06 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO39:0 stVal √ √
41 BAY UNIT-07 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO40:0 stVal √ √
42 BAY UNIT-08 OUT OF SERVICE SP MCU_II_765kVPROT$GGIO2$ST$SPCSO41:0 stVal √ √
43 Trip repeat Bay Unit-01 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO2:0 stVal √ √
44 Trip repeat Bay Unit-01 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO3:0 stVal √ √
45 Trip repeat Bay Unit-01 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO4:0 stVal √ √
46 Trip repeat Bay Unit-02 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO9:0 stVal √ √
47 Trip repeat Bay Unit-02 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO10:0 stVal √ √
48 Trip repeat Bay Unit-02 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO11:0 stVal √ √
49 Trip repeat Bay Unit-03 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO17:0 stVal √ √
50 Trip repeat Bay Unit-03 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO18:0 stVal √ √
51 Trip repeat Bay Unit-03 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO19:0 stVal √ √
52 Trip repeat Bay Unit-04 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO25:0 stVal √ √
53 Trip repeat Bay Unit-04 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO26:0 stVal √ √
54 Trip repeat Bay Unit-04 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO27:0 stVal √ √
55 Trip repeat Bay Unit-05 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO34:0 stVal √ √
56 Trip repeat Bay Unit-05 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO35:0 stVal √ √
57 Trip repeat Bay Unit-05 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO36:0 stVal √ √
58 Trip repeat Bay Unit-06 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO42:0 stVal √ √
59 Trip repeat Bay Unit-06 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO43:0 stVal √ √
60 Trip repeat Bay Unit-06 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO44:0 stVal √ √
61 Trip repeat Bay Unit-07 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO50:0 stVal √ √
62 Trip repeat Bay Unit-07 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO51:0 stVal √ √
63 Trip repeat Bay Unit-07 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO52:0 stVal √ √
64 Trip repeat Bay Unit-08 R-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO58:0 stVal √ √
65 Trip repeat Bay Unit-08 Y-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO59:0 stVal √ √
66 Trip repeat Bay Unit-08 B-PH SP MCU_II_765kVPROT$GGIO1$ST$SPCSO60:0 stVal √ √
67 Transfer Trip BUS-1 SP MCU_II_765kVPROT$GGIO2$ST$SPCSO8:0 stVal √ √
68 Transfer Trip BUS-2 SP MCU_II_765kVPROT$GGIO2$ST$SPCSO25:0 stVal √ √
69 BUS ZONE 1 TRIP SP MCU_II_765kVPROT$GGIO2$ST$SPCSO28:0 stVal √ √
70 BUS ZONE 2 TRIP SP MCU_II_765kVPROT$GGIO2$ST$SPCSO24:0 stVal √ √
71 BUSBAR CHECKZONE ALARM
72 BUSBAR CHECKZONE TRIP
73 BREAKER FAILURE - BUSBAR 1 BLOCKED
74 BREAKER FAILURE - BUSBAR 2 BLOCKED
75 ISOLATOR IN INTERMEDIATE STATUS
77 BUSBAR BLOCKED DUE TO COMMUNICATION ERROR_Bay_n
78 BAY_N_BREAKER FAILURE R-PH INITIATION
79 BAY_N_BREAKER FAILURE Y-PH INITIATION
80 BAY_N_BREAKER FAILURE B-PH INITIATION
81 BAY_N_BREAKER FAILURE 3PH INITIATION
82 BAY_N_EXTERNAL BUSBAR ZONE n
83 BAY_N_BREAKER FAILURE RETRIP
84 BAY_N_BREAKER FAILURE BACKTRIP
85 BAY_N_BREAKER FAILURE RPH- RETRIP
86 BAY_N_BREAKER FAILURE YPH- RETRIP
87 BAY_N_BREAKER FAILURE BPH- RETRIP
88 BBP CENTRAL UNIT IED UNHEALTHY
89 SETTING CHANGE
90 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
SIEMENS SCADA GENERAL SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (INDEX)
Sheet Ref. IED MODEL IED SYMBOLIC NAME(TYPICAL) APPLICATION IED NAME IN SCD Additional Remarks
1 6MD66 BCU TIE BCU STNM7XXTBCU BCU is for each bay so 7XX refers to Bay
4 7VK61 7VK_50ZT TIE STAND ALONE LBB RELAY STNM7XXTBFR Bay No. 7XX will be always the main bay number for the ICT feeder
NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "7XX" stand for Bay name, example if the bay no 701 then same has to be implemented like STNM701BCU
Sr. No. Voltage Level Feeder Name NAME ( BAY-702 TIE ) INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Double Point)
1 765kV 765kV TIE CB R-PH POSITION DP B702_BCUCBB$XCBR1$ST$Pos:2 stVal √
2 CB Y-PH POSITION DP B702_BCUCBR$XCBR1$ST$Pos:2 stVal √
3 CB B-PH POSITION DP B702_BCUCBY$XCBR1$ST$Pos:2 stVal √
4 CB POSITION DP B702_BCUCB$CSWI1$ST$Pos:2 stVal √
5 89AE POSITION DP B702_BCU89AE$CSWI3$ST$Pos:2 stVal √
6 89BE POSITION DP B702_BCU89BE$CSWI5$ST$Pos:2 stVal √
7 89A POSITION DP B702_BCU89A$CSWI2$ST$Pos:2 stVal √
8 89B POSITION DP B702_BCU89B$CSWI4$ST$Pos:2 stVal √
10 BINARY INPUT (Single Point)
12 AUX POWER FAIL SP B702_BCUApplication$LPHD0$ST$AuxPwrFail stVal √ √
13 TIME SYNCHRONISATION ERROR SP B702_BCUApplication$LMTS0$ST$TmSynErr stVal √ √
14 BCU MODE SP B702_BCUApplication$LLN0$ST$LocKey stVal √
15 CT SF6 GAS PRESSURE REFILL LOW ALARM SP B702_BCUApplication$USER1$ST$SPS stVal √ √
16 CT SF6 GAS PRESSURE LOCKOUT SP B702_BCUApplication$USER1$ST$SPS1 stVal √ √
17 CB DC SUPPLY-1/2 FAIL SP B702_BCUApplication$USER3$ST$SPS1 stVal √ √
18 CB SPRING NOT CHARGED B-PH SP B702_BCUApplication$USER3$ST$SPS4 stVal √
19 CB SPRING NOT CHARGED R-PH SP B702_BCUApplication$USER3$ST$SPS2 stVal √
20 CB SPRING NOT CHARGED Y-PH SP B702_BCUApplication$USER3$ST$SPS3 stVal √
21 CB SF6 GAS PRESSURE LOCKOUT SP B702_BCUApplication$USER3$ST$SPS stVal √ √
22 MAIN DC-1 SUPPLY Fail SP B702_BCUApplication$USER3$ST$SPS5 stVal √ √
23 89A POLE DESCREPENCY SP B702_BCUApplication$USER4$ST$SPS stVal √ √
24 89B POLE DESCREPENCY SP B702_BCUApplication$USER4$ST$SPS1 stVal √ √
25 86A TRIP RELAY SUPERVISION SP B702_BCUApplication$USER5$ST$SPS2 stVal √ √
26 86A TRIP RELAY OPERATED SP B702_BCUApplication$USER5$ST$SPS1 stVal √ √
27 86B TRIP RELAY SUPERVISION SP B702_BCUApplication$USER5$ST$SPS5 stVal √ √
28 86B TRIP RELAY OPERATED SP B702_BCUApplication$USER5$ST$SPS4 stVal √ √
29 CB TC-1 R-PHASE FAULTY
30 CB TC-1 Y-PHASE FAULTY
31 CB TC-1 B-PHASE FAULTY
32 CB TC-2 R-PHASE FAULTY
33 CB TC-2 Y-PHASE FAULTY SP B702_BCUApplication$USER5$ST$SPS stVal √ √
34 CB TC-2 B-PHASE FAULTY SP B702_BCUApplication$USER5$ST$SPS3 stVal √ √
35 KIOSK AC 1_2 Power Fail SP B702_BCUApplication$USER6$ST$SPS7 stVal √ √
36 KIOSK AC 1_2 ON STATUS SP B702_BCUApplication$USER6$ST$SPS6 stVal √
37 DC SOURCE-2 FAIL SP B702_BCUApplication$USER6$ST$SPS2 stVal √ √
38 KIOSK HEAT DETECTED SP B702_BCUApplication$USER6$ST$SPS5 stVal √ √
39 KIOSK SMOKE DETECTED SP B702_BCUApplication$USER6$ST$SPS4 stVal √ √
40 EMERGENCY/MANUAL CB TRIP SP B702_BCUApplication$USER6$ST$SPS stVal √ √
41 PSD DEVICE HEALTHY SP B702_BCUApplication$USER6$ST$SPS8 stVal √
42 PSD DEVICE IN SERVICE SP B702_BCUApplication$USER6$ST$SPS9 stVal √
43 PSD SENSSOR ERROR/CB VOLTAGE ERROR
45 PSD SYNCH OPERATION FAIL/DEFECTIVE SYNC DATA ALARM SP B702_BCUApplication$USER6$ST$SPS10 stVal √ √
46 SYNC OPERATION FAIL SP B702_BCUApplication$USER6$ST$SPS11 stVal √ √
47 TIE LBB RELAY UNHEALTHY SP B702_BCUApplication$USER6$ST$SPS1 stVal √ √
48 TIE LBB OPTD
49 CB POLE DESCREPENCY SP B702_BCUApplication$USER2$ST$SPS1 stVal √ √
50 CB SF6 GAS PRESSURE REFILL LOW ALARM SP B702_BCUApplication$USER2$ST$SPS stVal √ √
51 BUS-1 VT SELECTED SP B702_BCUApplication$USER7$ST$SPS stVal √
52 BUS-2 VT SELECTED SP B702_BCUApplication$USER7$ST$SPS1 stVal √
53 ICT LV VT SELECTED SP B702_BCUApplication$USER7$ST$SPS2 stVal √
54 CB READY SP B702_BCUCB$XCBR1$ST$Rdy stVal √
55 EMERGENCY/MANUAL CB TRIP SP B702_BCUCB$GAPC2$ST$Detected stVal √ √
56 CB MANUAL CLOSE
57 CB CONTROL NO SYNC SP B702_BCUCB$CSWI1$ST$Pos noSync √
58 CB CLOSE INTERLOCK SP B702_BCUCB$CILO1$ST$EnaCls stVal √
59 89AE OPEN INTERLOCK SP B702_BCU89AE$CILO3$ST$EnaOpn stVal √
60 89BE OPEN INTERLOCK SP B702_BCU89BE$CILO5$ST$EnaOpn stVal √
61 89A OPEN INTERLOCK SP B702_BCU89A$CILO2$ST$EnaOpn stVal √
62 89B OPEN INTERLOCK SP B702_BCU89B$CILO4$ST$EnaOpn stVal √
63 DEVICE HEALTHY SP B702_BCUApplication$LPHD0$ST$PhyHealth:0 stVal:1 √ √
64 GOOSE RECEIPT FAIL/TROUBLE SP B702_BCUApplication$USER7$ST$SPS3 stVal √ √
66 A/R FUNCTION OFF
67 A/R FUNCTION ON
69 A/R UNSUCCESSFUL
71 A/R SUCCESSFUL
72 RECLAIM IN PROGRESS
73 MAIN A/R LOCKOUT
74 TIE A/R LOCKOUT
75 Tie CB A/R PRIORITY CLOSE
76 MAIN/TIE BCU HEALTHY
77 AR SINGLE PHASE TRIP PERMITTED
78 CB NOT READY
79 A/R CLOSE COMMAND INDICATION
80 A/R IN PROGRESS
81 RELAY IN TEST MODE
82 SETTINGS CHANGED
83 CB MANUAL TRIP
84 CB MANUAL CLOSE
85 BUSBAR OPERATED
86 BCU IN LOCAL/REMOTE
89 POWER FACTOR ME_FL B702_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotPF:1 mag$f
90 FREQUENCY ME_FL B702_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$Hz:1 mag$f
91 765kV 765kV TIE ACTIVE POWER ME_FL B702_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotW:1 mag$f
92 REACTIVE POWER ME_FL B702_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVAr:1 mag$f
93 APPARENT POWER ME_FL B702_BCUVI3p1_OperationalValues$PPRE_MMXU1$MX$TotVA:1 mag$f
94 I-R -PH CURRENT ME_FL B702_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsA$cVal$mag$f
95 I-Y -PH CURRENT ME_FL B702_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsB$cVal$mag$f
96 I-B -PH CURRENT ME_FL B702_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$A:1 phsC$cVal$mag$f
97 R-Y VOLTAGE ME_FL B702_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsAB$cVal$mag$f
98 Y-B VOLTAGE ME_FL B702_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsBC$cVal$mag$f
99 B-R VOLYAGE ME_FL B702_BCUVI3p1_OperationalValues$RPRE_MMXU1$MX$PPV:1 phsCA$cVal$mag$f
100 KIOSK TEMPERATURE ME_FL
101 CB-B-PH COUNTER ME_I B702_BCUCBB$XCBR1$ST$OpCnt stVal
102 CB-R-PH COUNTER ME_I B702_BCUCBR$XCBR1$ST$OpCnt stVal
103 CB-Y-PH COUNTER ME_I B702_BCUCBY$XCBR1$ST$OpCnt stVal
107 89B CONTROL DC B702_BCU89B$CSWI4$CO$Pos:8 Oper$ctlVal √
108 89A CONTROL DC B702_BCU89A$CSWI2$CO$Pos:8 Oper$ctlVal √
109 89BE CONTROL DC B702_BCU89BE$CSWI5$CO$Pos:8 Oper$ctlVal √
110 89AE CONTROL DC B702_BCU89AE$CSWI3$CO$Pos:8 Oper$ctlVal √
111 CB CONTROL DC B702_BCUCB$CSWI1$CO$Pos:8 Oper$ctlVal √
112 89B CONTROL NO LOCK SC B702_BCU89B$CSWI4$CO$Pos Oper$noLock √
113 89A CONTROL NO LOCK SC B702_BCU89A$CSWI2$CO$Pos Oper$noLock √
114 89BE CONTROL NO LOCK SC B702_BCU89BE$CSWI5$CO$Pos Oper$noLock √
115 89AE CONTROL NO LOCK SC B702_BCU89AE$CSWI3$CO$Pos Oper$noLock √
116 CB CONTROL NO SYNC SC B702_BCUCB$CSWI1$CO$Pos Oper$noSync √
117 CB CONTROL NO LOCK SC B702_BCUCB$CSWI1$CO$Pos Oper$noLock √
118 86B TRIP RELAY RESET COMMAND SC B702_BCUApplication$USER2$CO$SPC1:8 Oper$ctlVal √
119 86A TRIP RELAY RESET COMMAND SC B702_BCUApplication$USER2$CO$SPC:8 Oper$ctlVal √
120 BAY BLOCK SC
121 TELECONTROL BLOCK SC
122 GOOSE RECEIPT FAIL/TROUBLE SP B702_BCUApplication$LLN0$ST$SPS stVal √ √
123 A/R ON CONTROL SC B706_BCUApplication$USER8$CO$SPC:8 Oper$ctlVal √
124 A/R OFF CONTROL SC B706_BCUApplication$USER8$CO$SPC1:8 Oper$ctlVal √
125 A/R BLOCK SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$BlkFct stVal √
126 A/R FUNCTION OFF SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$Off stVal √
127 A/R FUNCTION ON SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$On stVal √
128 CB READY FOR A/R SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$AutoRecSt:0 stVal:1 √
129 A/R UNSUCCESSFUL SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$AutoRecSt:0 stVal:10 √ √
130 A/R SUCCESSFUL SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$Successful stVal √
131 CB NOT READY SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$CBnotRdy stVal √
132 A/R CLOSE COMMAND INDICATION SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$OpCls general √
133 TIE A/R START √
134 A/R IN PROGRESS SP B706_BCUCB1_79AutoReclosing$GEN_RREC1$ST$RecInit stVal √
135 SETTINGS CHANGED
136 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
Sr. No. Voltage Level Feeder Name
SIGNAL DESCRIPTION INFORMATION TYPE Telegram Address POSITION Event Alarm
BINARY INPUT (Single Point)
1 765kV 765kV TIE BREAKER FAILURE RPH- RETRIP SP B702_50ZTPROT$RBRF1$ST$OpIn phsC √ √
2 BREAKER FAILURE YPH- RETRIP SP B702_50ZTPROT$RBRF1$ST$OpIn phsB √ √
3 BREAKER FAILURE BPH- RETRIP SP B702_50ZTPROT$RBRF1$ST$OpIn phsA √ √
4 BREAKER FAILURE BACKTRIP SP B702_50ZTPROT$RBRF1$ST$OpIn general √ √
5 BREAKER FAILURE TRIP EXTERNAL SP B702_50ZTPROT$RBRF1$ST$OpEx general √ √
6 GENERAL TRIP SP B702_50ZTPROT$PTRC1$ST$Tr general √ √
7 BREAKER FAILURE INITIATION 3-PH SP B702_50ZTPROT$RBRF1$ST$Str general √ √
8 TIE CB FAIL SP B702_50ZTCTRL$GGIO1$ST$SPCSO2:0 stVal √ √
9 TIE BCU UNHEALTHY SP B702_50ZTCTRL$GGIO1$ST$SPCSO1:0 stVal √ √
10 DEVICE HEALTHY SP B702_50ZTPROT$LPHD1$ST$PhyHealth:0 stVal:1 √
11 LBB EXTERNAL INITIATION 3-PH SP B702_50ZTEXT$pdGGIO23$ST$SPCSO7:0 stVal √ √
12 TIME SYNCHRONISATION ERROR SP B702_50ZTEXT$pdGGIO2$ST$SPCSO4:0 stVal √ √
13 LBB EXTERNAL INITIATION R-PH SP B702_50ZTEXT$pdGGIO23$ST$SPCSO27:0 stVal √ √
14 LBB EXTERNAL INITIATION Y-PH SP B702_50ZTEXT$pdGGIO23$ST$SPCSO28:0 stVal √ √
15 LBB EXTERNAL INITIATION B-PH SP B702_50ZTEXT$pdGGIO23$ST$SPCSO29:0 stVal √ √
16 POLE DISCREPANCY PICKUP SP B702_50ZTEXT$pdGGIO24$ST$SPCSO24:0 stVal √
17 POLE DISCREPANCY TRIP SP B702_50ZTEXT$pdGGIO24$ST$SPCSO28:0 stVal √ √
18 LBB ACTIVE SP B702_50ZTEXT$pdGGIO23$ST$SPCSO45:0 stVal √
20 GOOSE RECEIPT FAIL/TROUBLE SP B702_50ZTCTRL$GGIO1$ST$SPCSO3:0 stVal √ √
21 SETTINGS CHANGED
22 RELAY IN TEST MODE
Note: 1. Additional signal for CB Trouble, etc as per scheme & As per standard DR signal requirement the input not considered in HMI signal list 2. 5 Nos of GGIO signal need to be configured as SPARE till the SCADA Database 3. The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified. 4. If the logical nodes have been made more specific under the same logical node class by adding prefixes, same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV03 (AUX SYSTEM)
REQUIRED SIGNALS FOR AUX SYSTEM
SL. NO. Voltage Level IED name in SCD IEC 61850 ADDRESS TYPE EVENT/ALARM NAME WHETHER ALARM TO BE GENERATED REMARKS
1 415V STNMN1AUXBCU INT BCU IN LOCAL/ REMOTE
2 415V STNMN1AUXBCU SPI DG_CB_OPEN PERMITTED OR ENABLED
3 415V STNMN1AUXBCU SPI DG_CB_CLOSE PERMITTED OR ENABLED
4 415V STNMN1AUXBCU DPI DG_CB POSITION
5 415V STNMN1AUXBCU CMD DG_CB COMMAND CLOSE / OPEN
6 415V STNMN1AUXBCU SPI MSB_INCOMER_1_CB_OPEN PERMITTED OR ENABLED
7 415V STNMN1AUXBCU SPI MSB_INCOMER_1_CB_CLOSE PERMITTED OR ENABLED
8 415V STNMN1AUXBCU DPI MSB_INCOMER_1_CB POSITION
9 415V STNMN1AUXBCU CMD MSB_INCOMER_1_CB COMMAND CLOSE / OPEN
10 415V STNMN1AUXBCU SPI MSB_INCOMER_2_CB_OPEN PERMITTED OR ENABLED
11 415V STNMN1AUXBCU SPI MSB_INCOMER_2_CB_CLOSE PERMITTED OR ENABLED
12 415V STNMN1AUXBCU DPI MSB_INCOMER_2_CB POSITION
13 415V STNMN1AUXBCU CMD MSB_INCOMER_2_CB COMMAND CLOSE / OPEN
14 415V STNMN1AUXBCU SPI MSB_BUSCOUPLER_CB_OPEN PERMITTED OR ENABLED
15 415V STNMN1AUXBCU SPI MSB_BUSCOUPLER_CB_CLOSE PERMITTED OR ENABLED
16 415V STNMN1AUXBCU DPI MSB_BUSCOUPLER_CB POSITION
17 415V STNMN1AUXBCU CMD MSB_BUSCOUPLER_CB COMMAND CLOSE / OPEN
18 415V STNMN1AUXBCU SPI ACDB_INCOMER_1_CB_OPEN PERMITTED OR ENABLED
19 415V STNMN1AUXBCU SPI ACDB_INCOMER_1_CB_CLOSE PERMITTED OR ENABLED
20 415V STNMN1AUXBCU DPI ACDB_INCOMER_1_CB POSITION
21 415V STNMN1AUXBCU CMD ACDB_INCOMER_1_CB COMMAND CLOSE / OPEN
22 415V STNMN1AUXBCU SPI ACDB_INCOMER_2_CB_OPEN PERMITTED OR ENABLED
23 415V STNMN1AUXBCU SPI ACDB_INCOMER_2_CB_CLOSE PERMITTED OR ENABLED
24 415V STNMN1AUXBCU DPI ACDB_INCOMER_2_CB POSITION
25 415V STNMN1AUXBCU CMD ACDB_INCOMER_2_CB COMMAND CLOSE / OPEN
26 415V STNMN1AUXBCU SPI ACDB_BUSCOPULER_CB_OPEN PERMITTED OR ENABLED
27 415V STNMN1AUXBCU SPI ACDB_BUSCOPULER_CB_CLOSE PERMITTED OR ENABLED
28 415V STNMN1AUXBCU DPI ACDB_BUSCOPULER_CB POSITION
29 415V STNMN1AUXBCU CMD ACDB_BUSCOPULER_CB COMMAND CLOSE / OPEN
30 415V STNMN1AUXBCU SPI HVW_MOTOR_CB_OPEN PERMITTED OR ENABLED
31 415V STNMN1AUXBCU SPI HVW_MOTOR_CB_CLOSE PERMITTED OR ENABLED
32 415V STNMN1AUXBCU DPI HVW_MOTOR_CB_ POSITION
33 415V STNMN1AUXBCU CMD HVW_MOTOR_CB_ COMMAND CLOSE / OPEN
34 415V STNMN1AUXBCU SPI SEB_33kV_CB_OPEN PERMITTED OR ENABLED
35 415V STNMN1AUXBCU SPI SEB_33kV_CB_CLOSE PERMITTED OR ENABLED
36 415V STNMN1AUXBCU DPI SEB_33kV_CB_ POSITION
37 415V STNMN1AUXBCU CMD SEB_33kV_CB_ COMMAND CLOSE / OPEN
38 415V STNMN1AUXBCU SPI SEB_33kV_ISOLATOR_OPEN PERMITTED OR ENABLED
39 415V STNMN1AUXBCU SPI SEB_33kV_ISOLATOR_CLOSE PERMITTED OR ENABLED
40 415V STNMN1AUXBCU DPI SEB_33kV_ISOLATOR_ POSITION
41 415V STNMN1AUXBCU CMD SEB_33kV_ISOLATOR_ COMMAND CLOSE / OPEN
42 415V STNMN1AUXBCU SPI TERTIARY TRAFO_33kV_CB_OPEN PERMITTED OR ENABLED If the inputs taken in Respecetive ICT Protection/BCU these signals may be omitted.
43 415V STNMN1AUXBCU SPI TERTIARY TRAFO_33kV_CB_CLOSE PERMITTED OR ENABLED
44 415V STNMN1AUXBCU DPI TERTIARY TRAFO_33kV_CB_ POSITION
45 415V STNMN1AUXBCU CMD TERTIARY TRAFO_33kV_CB_ COMMAND
46 415V STNMN1AUXBCU SPI TERTIARY TRAFO_33kV_ISOLATOR_OPEN PERMITTED OR ENABLED
47 415V STNMN1AUXBCU SPI TERTIARY TRAFO_33kV_ISOLATOR_CLOSE PERMITTED OR ENABLED
48 415V STNMN1AUXBCU DPI TERTIARY TRAFO_33kV_ISOLATOR_ POSITION
49 415V STNMN1AUXBCU CMD TERTIARY TRAFO_33kV_ISOLATOR_ COMMAND
THE LOGICAL NODE INSTANCE NUMBER (SCSWIn/SCILOn) FOR BBREAKERS MAY BE ASSIGNED AS PER AVAILABILITY
50 415V STNMN1AUXBCU AI DG INCOMER CURRENT L1
51 415V STNMN1AUXBCU AI DG INCOMER CURRENT L2
52 415V STNMN1AUXBCU AI DG INCOMER CURRENT L3
53 415V STNMN1AUXBCU AI DG INCOMER VOLTAGE U12
54 415V STNMN1AUXBCU AI DG INCOMER VOLTAGE U23
55 415V STNMN1AUXBCU AI DG INCOMER VOLTAGE U31
56 415V STNMN1AUXBCU AI DG INCOMER ACTIVE POWER (P)
57 415V STNMN1AUXBCU AI DG INCOMER REACTIVE POWER (Q)
58 415V STNMN1AUXBCU AI DG INCOMER POWER FACTOR (PF)
59 415V STNMN1AUXBCU AI DG INCOMER FREQUENCY (HZ)
60 415V STNMN1AUXBCU AI MSB INCOMER-1 CURRENT L1
61 415V STNMN1AUXBCU AI MSB INCOMER-1 CURRENT L2
62 415V STNMN1AUXBCU AI MSB INCOMER-1 CURRENT L3
63 415V STNMN1AUXBCU AI MSB INCOMER-1 VOLTAGE U12
64 415V STNMN1AUXBCU AI MSB INCOMER-1 VOLTAGE U23
65 415V STNMN1AUXBCU AI MSB INCOMER-1 VOLTAGE U31
66 415V STNMN1AUXBCU AI MSB INCOMER-1 ACTIVE POWER (P)
67 415V STNMN1AUXBCU AI MSB INCOMER-1 REACTIVE POWER (Q)
68 415V STNMN1AUXBCU AI MSB INCOMER-1 POWER FACTOR (PF)
69 415V STNMN1AUXBCU AI MSB INCOMER-1 FREQUENCY (HZ)
70 415V STNMN1AUXBCU AI MSB INCOMER-2 CURRENT L1
71 415V STNMN1AUXBCU AI MSB INCOMER-2 CURRENT L2
72 415V STNMN1AUXBCU AI MSB INCOMER-2 CURRENT L3
73 415V STNMN1AUXBCU AI MSB INCOMER-2 VOLTAGE U12
74 415V STNMN1AUXBCU AI MSB INCOMER-2 VOLTAGE U23
75 415V STNMN1AUXBCU AI MSB INCOMER-2 VOLTAGE U31
76 415V STNMN1AUXBCU AI MSB INCOMER-2 ACTIVE POWER (P)
77 415V STNMN1AUXBCU AI MSB INCOMER-2 REACTIVE POWER (Q)
78 415V STNMN1AUXBCU AI MSB INCOMER-2 POWER FACTOR (PF)
79 415V STNMN1AUXBCU AI MSB INCOMER-2 FREQUENCY (HZ)
80 415V STNMN1AUXBCU AI 220V CHARGER 1 CURRENT
81 415V STNMN1AUXBCU AI 220V CHARGER 2 CURRENT
82 415V STNMN1AUXBCU AI 48V CHARGER 1 CURRENT
83 415V STNMN1AUXBCU AI 48V CHARGER 2 CURRENT
84 415V STNMN1AUXBCU AI 220V DCDB 1 VOLTAGE
85 415V STNMN1AUXBCU AI 220V DCDB 1 CURRENT
86 415V STNMN1AUXBCU AI 220V DCDB 2 VOLTAGE
87 415V STNMN1AUXBCU AI 220V DCDB 2 CURRENT
88 415V STNMN1AUXBCU AI 48V DCDB 1 VOLTAGE
89 415V STNMN1AUXBCU AI 48V DCDB 1 CURRENT
90 415V STNMN1AUXBCU AI 48V DCDB 2 VOLTAGE
91 415V STNMN1AUXBCU AI 48V DCDB 2 CURRENT
92 415V STNMN1AUXBCU SPI 220V CHARGER-1 ON FLOAT MODE
93 415V STNMN1AUXBCU SPI 220V CHARGER-1 ON BOAST MODE
94 415V STNMN1AUXBCU SPI 220V CHARGER 1 TROUBLE Y CLOSE / OPEN
95 415V STNMN1AUXBCU SPI 220V DCDB-1 EARTH FAULT OPTD Y
96 415V STNMN1AUXBCU SPI 220V CHARGER-2 ON FLOAT MODE
97 415V STNMN1AUXBCU SPI 220V CHARGER-2 ON BOAST MODE
98 415V STNMN1AUXBCU SPI 220V CHARGER 2 TROUBLE Y
99 415V STNMN1AUXBCU SPI 220V DCDB-2 EARTH FAULT OPTD Y
100 415V STNMN1AUXBCU SPI 48V CHARGER-1 ON FLOAT MODE CLOSE / OPEN
101 415V STNMN1AUXBCU SPI 48V CHARGER-1 ON BOAST MODE
102 415V STNMN1AUXBCU SPI 48V CHARGER 1 TROUBLE Y
103 415V STNMN1AUXBCU SPI 48V CHARGER-2 ON FLOAT MODE
104 415V STNMN1AUXBCU SPI 48V CHARGER-2 ON BOAST MODE CLOSE / OPEN
105 415V STNMN1AUXBCU SPI 48V CHARGER 2 TROUBLE Y
106 415V STNMN1AUXBCU SPI 415V INCOMER-1 UNDERVOLTAGE Y
107 415V STNMN1AUXBCU SPI 415V INCOMER-2 UNDERVOLTAGE Y CLOSE / OPEN
108 415V STNMN1AUXBCU SPI SEB TRAFO - BUCHHOLZ ALARM Y
109 415V STNMN1AUXBCU SPI SEB TRAFO - BUCHHOLZ TRIP Y
110 415V STNMN1AUXBCU SPI SEB TRAFO - WTI ALARM Y
111 415V STNMN1AUXBCU SPI SEB TRAFO - WTI TRIP Y
112 415V STNMN1AUXBCU SPI SEB TRAFO - OTI ALARM Y
113 415V STNMN1AUXBCU SPI SEB TRAFO - OTI TRIP Y
114 415V STNMN1AUXBCU SPI SEB TRAFO - PRD ALARM Y
115 415V STNMN1AUXBCU SPI SEB TRAFO - PRD TRIP Y
116 415V STNMN1AUXBCU SPI SEB 33KV_TC-1 FAULTY Y
117 415V STNMN1AUXBCU SPI SEB 33KV_TC-2 FAULTY Y
118 415V STNMN1AUXBCU SPI SEB 33kV PHASE OVERCURRENT START Y
119 415V STNMN1AUXBCU SPI SEB33kV PHASE OVERCURRENT TRIP Y
120 415V STNMN1AUXBCU SPI SEB 33kV PHASE EARTHFAULT START Y
121 415V STNMN1AUXBCU SPI SEB 33kV PHASE EARTHFAULT TRIP Y
122 415V STNMN1AUXBCU SPI SEB 33kV PHASE RESIDUAL OVERVOLTAGE START Y
123 415V STNMN1AUXBCU SPI SEB 33kV PHASE RESIDUAL OVERVOLTAGE TRIP Y
124 415V STNMN1AUXBCU SPI SEB 33kV 86 OPTD Y
125 415V STNMN1AUXBCU SPI SEB 33kV CB ASSOCIATED ALARMS Y
126 415V STNMN1AUXBCU SPI TERTIARY TRAFO - BUCHHOLZ ALARM Y If the inputs taken in Respecetive ICT Protection/BCU these signals may be omitted.
127 415V STNMN1AUXBCU SPI TERTIARY TRAFO - BUCHHOLZ TRIP Y
128 415V STNMN1AUXBCU SPI TERTIARY TRAFO - WTI ALARM Y
129 415V STNMN1AUXBCU SPI TERTIARY TRAFO - WTI TRIP Y
130 415V STNMN1AUXBCU SPI TERTIARY TRAFO - OTI ALARM Y
131 415V STNMN1AUXBCU SPI TERTIARY TRAFO - OTI TRIP Y
132 415V STNMN1AUXBCU SPI TERTIARY TRAFO - PRD ALARM Y
133 415V STNMN1AUXBCU SPI TERTIARY TRAFO - PRD TRIP Y
134 415V STNMN1AUXBCU SPI TERTIARY 33KV_TC-1 FAULTY Y
135 415V STNMN1AUXBCU SPI TERTIARY 33KV_TC-2 FAULTY Y
136 415V STNMN1AUXBCU SPI TERTIARY 33kV PHASE OVERCURRENT START Y
137 415V STNMN1AUXBCU SPI TERTIARY33kV PHASE OVERCURRENT TRIP Y
138 415V STNMN1AUXBCU SPI TERTIARY 33kV PHASE EARTHFAULT START Y
139 415V STNMN1AUXBCU SPI TERTIARY 33kV PHASE EARTHFAULT TRIP Y
140 415V STNMN1AUXBCU SPI TERTIARY 33kV PHASE RESIDUAL OVERVOLTAGE START Y
141 415V STNMN1AUXBCU SPI TERTIARY 33kV PHASE RESIDUAL OVERVOLTAGE TRIP Y
142 415V STNMN1AUXBCU SPI TERTIARY 33kV 86 OPTD Y
143 415V STNMN1AUXBCU SPI TERTIARY 33kV CB ASSOCIATED ALARMS Y
144 415V STNMN1AUXBCU SPI AUX INCOMER DC-1 FAULTY Y
145 415V STNMN1AUXBCU SPI AUX INCOMER DC-2 FAULTY Y
146 415V STNMN1AUXBCU SPI WATER STORAGE TANK-1 LEVEL LOW Y
147 415V STNMN1AUXBCU SPI WATER STORAGE TANK-2 LEVEL LOW Y
148 415V STNMN1AUXBCU SPI HVW MOTOR DRIVEN PUMP RUNNING
149 415V STNMN1AUXBCU SPI HVW MOTOR DRIVEN PUMP FAILS TO START Y
150 415V STNMN1AUXBCU SPI HVW MOTOR PUMP TRIP FEEDBACK Y
151 415V STNMN1AUXBCU SPI DIESEL ENGINE RUNNING
152 415V STNMN1AUXBCU SPI DIESEL ENGINE FAILS TO START Y
153 415V STNMN1AUXBCU SPI DIESEL ENGINE TANK LEVEL LOW Y
154 415V STNMN1AUXBCU SPI JOCKEY PUMP -1 RUNNING
155 415V STNMN1AUXBCU SPI JOCKEY PUMP -2 RUNNING
156 415V STNMN1AUXBCU SPI JOCKEY PUMP -1 FAILS TO START Y
157 415V STNMN1AUXBCU SPI JOCKEY PUMP -2 FAILS TO START Y
158 415V STNMN1AUXBCU SPI JOCKEY PUMP O/L TRIP Y
159 415V STNMN1AUXBCU SPI JOCKEY PUMP PANEL DC HEALTHY Y
160 415V STNMN1AUXBCU CMD HVW MOTORT START
161 415V STNMN1AUXBCU CMD HVW MOTORT STOP
162 415V STNMN1AUXBCU CMD DIESEL ENGINE START
163 415V STNMN1AUXBCU CMD DIESEL ENGINE STOP
164 415V STNMN1AUXBCU CMD JOCKEY PUMP-1 START
165 415V STNMN1AUXBCU CMD JOCKEY PUMP-1 STOP
166 415V STNMN1AUXBCU CMD JOCKEY PUMP-2 START
167 415V STNMN1AUXBCU CMD JOCKEY PUMP-2 STOP
168 415V STNMN1AUXBCU SPI FIRE IN ZONE -1 Y
169 415V STNMN1AUXBCU SPI FIRE IN ZONE -2 Y
170 415V STNMN1AUXBCU SPI FIRE IN ZONE -3 Y
171 415V STNMN1AUXBCU SPI FIRE IN ZONE -4 Y
172 415V STNMN1AUXBCU SPI FIRE IN ZONE -5 Y
173 415V STNMN1AUXBCU SPI FIRE IN ZONE -N Y
174 415V STNMN1AUXBCU SPI FIRE IN TRANSFORMER-1 Y If the inputs taken in Respecetive ICT Protection/BCU these signals may be omitted.
175 415V STNMN1AUXBCU SPI FIRE IN TRANSFORMER-2 Y
176 415V STNMN1AUXBCU SPI FIRE IN TRANSFORMER-N Y
177 415V STNMN1AUXBCU CMD DELUGE COMMAND TO TRANSFORMER-1
178 415V STNMN1AUXBCU CMD DELUGE COMMAND TO TRANSFORMER-2
179 415V STNMN1AUXBCU CMD DELUGE COMMAND TO TRANSFORMER-N
180 415V STNMN1AUXBCU SPI DG DIFFERENTIAL PROT TRIP Y
181 415V STNMN1AUXBCU SPI DG OC/EF PROT TRIP Y
182 415V STNMN1AUXBCU SPI DG FAIL TO START Y
183 415V STNMN1AUXBCU SPI ALTERNATOR ON
184 415V STNMN1AUXBCU SPI DG LUBE OIL LOW PRESSURE ALARM Y
185 415V STNMN1AUXBCU SPI HIGH WATER TEMP TRIP Y CLOSE / OPEN
186 415V STNMN1AUXBCU SPI ENGG. COM FAULT Y
187 415V STNMN1AUXBCU SPI LACK OF FUEL ALARM Y
188 415V STNMN1AUXBCU SPI DG CHARGER-1 ON
189 415V STNMN1AUXBCU SPI DG CHARGER-1 OFF Y CLOSE / OPEN
190 415V STNMN1AUXBCU SPI DG CHARGER-2 ON
191 415V STNMN1AUXBCU SPI DG CHARGER-2 OFF Y
192 415V STNMN1AUXBCU CMD DG START/STOP COMMAND CLOSE / OPEN
193 415V STNMN1AUXBCU SPI AUX INCOMER DC-1 FAULTY Y
194 415V STNMN1AUXBCU SPI AUX INCOMER DC-2 FAULTY Y
195 415V STNMN1AUXBCU SPI TIME SYNCHRONIZATION ERROR Y
196 415V STNMN1AUXBCU SPI BCU UNHEALTHY Y
197 415V STNMN1AUXBCU SPI GOOSE RECEIPT FAIL/TROUBLE Y Only if the IED subscriber to GOOSE messgaes as per the scheme
198 415V STNMN1AUXBCU SPI RELAY IN TEST MODE Y
199 415V STNMN1AUXBCU SPI SETTINGS CHANGED Y
200 415V STNMN1AUXBCU SPI DR MEMMORY 80% FULL Y
201 415V STNMN1AUXBCU SPI SPARE ALARM-1 ** 20 nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
202 415V STNMN1AUXBCU SPI SPARE ALARM-2
203 415V STNMN1AUXBCU SPI SPARE ALARM-3
204 415V STNMN1AUXBCU SPI SPARE ALARM-4
205 415V STNMN1AUXBCU SPI SPARE ALARM-5
206 415V STNMN1AUXBCU SPI SPARE ALARM-6
207 415V STNMN1AUXBCU SPI SPARE ALARM-7
208 415V STNMN1AUXBCU SPI SPARE ALARM-8
209 415V STNMN1AUXBCU SPI SPARE ALARM-9
210 415V STNMN1AUXBCU SPI SPARE ALARM-10
211 415V STNMN1AUXBCU SPI SPARE ALARM-11
212 415V STNMN1AUXBCU SPI SPARE ALARM-12
213 415V STNMN1AUXBCU SPI SPARE ALARM-13
214 415V STNMN1AUXBCU SPI SPARE ALARM-14
215 415V STNMN1AUXBCU SPI SPARE ALARM-15
216 415V STNMN1AUXBCU SPI SPARE ALARM-16
217 415V STNMN1AUXBCU SPI SPARE ALARM-17
218 415V STNMN1AUXBCU SPI SPARE ALARM-18
219 415V STNMN1AUXBCU SPI SPARE ALARM-19
220 415V STNMN1AUXBCU SPI SPARE ALARM-20
ADDITIONAL SIGNAL FOR CB TROUBLE ETC AS PER SCHEME
** 20 Nos of SP16GGIO signal need to be configured as SPARE till the SCADA Database
ATTACHMENTS General guidelines for filling up the Attachments 400kV GIS Substation Package SS-149
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459]
1 Fill up only green shaded cells in the relevent attachments.
2 Attachments 3(QR), 4, 4(A), 5, 5(A), 6, 7, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 23, 26, 28, 30, 31, 32 and Bid Form for 1st Envelope are included here.
3 Attachment 1 Bid Security : Not Applicable
4 Attachment 2 Power of Attorney : No specific format is provided by POWERGRID. Bidder may use their own format.
5 Attachment 8 Manufacturer’s Authorisation Form : To be furnished as per proforma provided in the bidding document, on the letter head of the each Manufactures proposed to supply main items. This attachment is not included here.
6 Attachment 10 Guarantee Declaration: We hereby declare that Attachment-10 (Guarantee Declaration) is provided in our Second Envelope Bid.
6 Attachment 14 Integrity Pact : To be submitted as per ITB Clause No. 9.3(o) and as per remarks in the Attach 14-IP.
7 Attachment 20, 21, 22, 24, 25, 29: To be submitted as per the provisions of the Bidding Documents (Formats Attached seperately in Volume-III if Bidding Documents.
8 Attachment 24: Confirmation in regard to Design and Type Test (to be furnished in case bidder is proposing to qualify through Note-4 under Route-1 of QR)
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] Individual Firm (Route-1)
Individual Firm (Route-2)
Enter the details of the bidder below: Individual Firm (Route-3)
Individual Firm (Route-4)
Specify type of Bidder [Select from drop down menu] Joint Venture Bid
{as per sl. no. 1.1 OR 1.2 OR 1.3 OR 1.4 (as applicable) of Annexure-A (BDS) of Vol-I (Conditions of Contract)} 1
Whether the bidder is an MSE (Micro & Small Enterprise)
Enter the Name of Registration Authority
Name of the Bidder 1
Address of Registered Office 2 or more
Address of Registered Office
email ID(s) of Contact Person
Mobile No(s). of Contact Person
Tel No(s). of Contact Person
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-3 (JV) #REF! #REF!
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Joint Venture Agreement and Power of Attorney for Joint Venture*)
Bidder’s Name and Address : To:
0 Contract Services 1 #REF!
Name : 0 Power Grid Corporation of India Ltd., 0
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
The Joint Venture Agreement (as per the proforma attached at no. 15 in Section-VI, Sample Forms and Procedures, Conditions of Contract, Vol.-I of the Bidding Documents) and Power of Attorney for Joint Venture (as per the proforma attached at no. 14 in Section-VI, Sample Forms and Procedures, Conditions of Contract, Vol.-I of the Bidding Documents) are enclosed herewith.
* applicable for Joint Venture
Date : 00-Jan-00 Printed Name : 0 #REF!
Place : 0 Designation : 0 #REF!
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] Attachment-3 (QR)
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Qualifying Requirement Data)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Name : 0 "Saudamini", Plot No. 2, Sector 29
Address : 0 Gurgaon (Haryana) - 122001
In support of the Qualification Requirements (QR) for bidders, stipulated in Annexure-A (BDS) of the Section - III (BDS), Volume-I & Additional Information required as per ITB clause 9.3(c) of the Bidding Documents, we furnish herewith our QR data/details along with other information, as follows herewith our stipulations have been reproduced in italics for ready reference, however, in case of any discrepancy the QR as given in BDS shall prevail).
* We have submitted bid as individual firm.
* We have submitted bid as joint venture of following firms :
(* Strike-off whichever is not applicable)
[For details regarding Qualification Requirements of a Joint Venture, please refer para 4.0 below.]
We are furnishing the following details/document in support of Qualifying requirement for the subject package.
A Attached copies of original documents defining :
a) The constitution or legal status;
b) The principal place of business;
c) The place of incorporation (for bidders who are corporations); or the place of registration and the nationality of the Owners (for applicants who are partnerships or individually-owned firms).
B Attached original & copies of the following documents :
a) Written power of attorney of the signatory of the Bid to commit the bidder.
b) Joint Venture Agreement.
GENERAL INFORMATION
Bidder is required to provide general information as per the following format.
[Where the Bidder proposes to use named subcontractor(s) for critical components of the works or for work contents in excess of ten (10) percent of the bid price, the following information should also be supplied for the subcontractor(s)].
S No. Particulars Bidder/Lead Partner In case of Joint Venture
For Other Partner(s) For Other Partner(s)
1 Name of the Firm
2 Head Office/ Registered Office Address
5 Contact Person
6 Place of Incorporation/ Registration
7 Year of Incorporation/ Registration
8 Nationality of
1.0 TECHNICAL REQUIREMENTS {Reference para 1.0 of Annexure-A (BDS)}
Using the following format, each Bidder (individual firms or partners of a joint venture) is requested to list the experience as detailed above, on the basis of which the Bidder wishes to qualify. The information is to be summarised using following format for each experience of the Bidder or of each Partner of a Joint Venture.
(The bidder shall attach documentary evidence, such as copies of utility certificates for completed contracts and copies of award letters etc. for ongoing contracts in support of his experience as listed in the following proforma for each Contract with the help of "Attach" Buttons provided in table given below).
Format for the Bidder/Collaborator/ Parent/Principal/Partner of JV in case of Joint Venture/Indian GIS Mnaufacturer in support of meeting the requirement of para 1.1, Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
Name of Bidder/Collaborator/ Parent/Principal/Partner of a JV/Indian GIS Manufacturer #REF!
1 Name of Contract Undertaken #REF!
2 Contract Reference No. & Date of Award
3 Name and Address of the Employer/Utility for whom the Contract was executed by the firm/Partner of a JV
4(a)(i) Voltage Level of GIS Substation commissioned under the Contract (Indicate 345KV or above class only)
No. of GIS Circuit Breaker equipped bays under the above contract
(Indicate nos. of GIS Circuit Breaker equipped bays of 345KV or above voltage level where one no. of circuit breaker bay shall be considered as a bay used for controlling a line or a transformer or a reactor or a bus section or a bus coupler and comprising of at least one circuit breaker, one disconnector and three nos. of single phase CTs / Bushing CTs)
Name of the substation or switchyard
(a)(ii) No. of years, the above Substation have been in operation as on the originally scheduled last date of bid submission mentioned above
Scope of work involved under the Contract
(Tick whichever is/are applicable)
NOTE: type test reports of Collaborator/ Parent Company/ Subsidiary Company/ Group Company shall also be acceptable, for which a confirmation shall be furnished along with the bid as per format attached in the bidding documents (Attachment-24 in Volume-III)
of Gas Insulated Switchgear (GIS) circuit breaker bays. of Gas Insulated Switchgear (GIS) circuit breaker bays.
In case of foreign entity, whether bidder have established/ commence the establishment of facility as Indian Subsidiary/ Group Company/ Joint Venture Company for manufacturing & testing of 765kV or above voltage level GIS in India (as per Companies Act 1956 or 2013 of India)
Whether bidder want to propose its above subsidiary/ Group Company/ Joint Venture Company as its associate for executing On-Shore Supply Contract
Foreign Bidder can offer to supply more than one 765kV GIS circuit breaker bay* from India provided his Subsidiary or Group Company or a Joint Venture Company (JVC) must have manufactured at least one (1) number 765kV or above voltage level GIS Circuit Breaker bay* and this bay either should have been supplied or should have been type tested ( as per IEC or equivalent standard) as on the originally scheduled date of bid opening as mentioned above
Whether Undertaking (as per enclosed format in Section-VI, Sample Forms and Procedures of bidding document) for above is enclosed with the bid
Details of documents uploaded in support of the above stated experience
Format for the Indian Associate executing the On-Shore Supply and On-Shore Services Contract for a Foreign Entity submitting its bid as an Individual Firm or in a Joint Venture without any Indian Entity as a Partner, in support of meeting the requirement of para 1.1.1(i) of Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
Name of the Indian Associate executing the On-Shore Supply and On-Shore Services Contract
1 Name of Contract Undertaken
2 Contract Reference No. & Date of Award
3 Name and Address of the Employer/Utility for whom the Contract was executed by the Bidder
4 No. of GIS/AIS Circuit Breaker equipped bays under the contract
(Indicate nos. of Circuit Breaker equipped bays of 220 kV or above voltage level where one no. of circuit breaker bay shall be considered as a bay used for controlling a line or a transformer or a reactor or a bus section or a bus coupler and comprising of at least one circuit breaker, one disconnector and three nos. of single phase CTs / Bushing CTs)
Name of the substation or switchyard
No. of years, the above CB bays are in operation as on the originally scheduled date of bid opening.
Scope of work involved under the Contract
(Tick whichever is/are applicable)
Details of documents uploaded in support of the above stated experience
Format-B (Route-2):
Format in support of meeting the requirement of para 1.2 Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
1 Name of the Collaborator
2 Whether bidder have established manufacturing and testing facilities in India for 345KV or above voltage level Gas Insulated Switchgear (GIS)
3 Whether 345KV or above voltage level Gas Insulated Switchgear (GIS) Circuit Breaker bay manufactured by bidder based on technological support of the collaborator have been supplied or Type tested
A if Type tested details of Type test Report
B Details of GIS supplied by them
i Name of Contract Undertaken for manufacturing 345KV or above voltage level Gas Insulated Switchgear (GIS) Circuit Breaker bays
ii Contract Reference No. & Date of Award
iii Name and Address of the Employer/Utility for whom the Contract was executed by the firm/Partner of a JV
iv No. of 345KV Gas Insulated Switchgear (GIS) Circuit Breaker bays manufactured under the contract (Indicate nos. of Gas Insulated Switchgear (GIS) Circuit Breaker equipped bays of 345KV or above voltage level, where circuit breaker bay shall be considered as a bay used for controlling a line or a transformer or a reactor or a bus section or a bus coupler and comprising of at least one circuit breaker, one disconnector and three nos. of single phase CTs/Bushing CTs. GIS means SF6 Gas insulated Switchgear.)
Name of the substation or switchyard
Whether 345KV or above voltage level Gas Insulated Switchgear (GIS) Circuit breaker bays, as mentioned above, has been manufactured based on technological support of the Collaborator under the Contract.
Scope of work involved under the Contract
Details of documents uploaded in support of the above stated experience
Format in support of meeting the requirement of para 1.2 (as applicable) Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
Name of the Collaborator (refer para 1.2), if applicable : #REF!
Name of the 110KV Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS Equipment Manufacturer (refer para 1.2), if applicable : #REF!
1 Name of Contract Undertaken #REF!
2 Contract Reference No. & Date of Award
4(a)(i) No. of Circuit Breaker bays under the contract
(Indicate nos. of Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS Circuit Breaker bays of 110KV or above)
Name of the substation or switchyard
(a)(ii) No. of years, the above Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS CB bays are in operation as on the originally scheduled date of bid opening.
Scope of work involved under the Contract as per IEC
(Tick whichever is/are applicable)
Whether Collaborator(s) meets the technical experience criteria stipulated at 1.1 above, and the details of which is mentioned at Format-A above. (Applicable for the Bidder/Manufacturer(s) wish/proposes to qualify through Route-2 of Annexure-A(BDS))
Whether legally enforceable undertaking jointly by Bidder/Manufacturer and the Collaborator(s) (as per enclosed format in Section-VI: Sample Forms and Procedures of bidding document) is furnished along with the bid. (Applicable for the Bidder/Manufacturer(s) wish/proposes to qualify through Route-2 of Annexure-A(BDS))
Confirmation letter from the Collaborator(s) along with the bid stating that Collaborator(s) shall furnish performance guarantee, in addition to contract performance guarantee to be submitted by the bidder, for an amount of 10% of the cost of equipment(s) to be manufactured and supplied from the works in India. (Applicable for the Bidder/Manufacturer wish/proposes to qualify through Route-2 of Annexure-A(BDS))
Whether valid collaboration agreement for technology transfer / license to design, manufacture, test and supply 345kV or above voltage level GIS equipment in India furnished along with the bid. (Applicable for the Bidder/Manufacturer(s) wish/proposes to qualify through Route-2 of Annexure-A(BDS))
Details of documents uploaded in support of the above stated experience
Format-C: (Route-3)
Format in support of meeting the requirement of para 1.3 Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
1 Name of the Bidder established as Subsidiary/JVC/Group company by its parent/principal Company
2 Name of the parent/principal Company
3 Whether bidder have established manufacturing and testing facilities in India for 345KV or above voltage level Gas Insulated Switchgear (GIS)
4 Whether 345KV or above voltage level Gas Insulated Switchgear (GIS) Circuit Breaker bay manufactured by bidder have been supplied or Type tested based on Technological support of their Parent/ Principal Company
A if Type tested details of Type test Report
B Details of Gas Insulated Switchgear (GIS) Circuit Breaker Bays supplied by them
i Name of Contract Undertaken for manufacturing 345KV or above voltage level Gas Insulated Switchgear (GIS) Circuit Breaker bays
ii Contract Reference No. & Date of Award
iii Name and Address of the Employer/Utility for whom the Contract was executed by the firm/Partner of a JV
iv No. of 345KV Gas Insulated Switchgear (GIS) Circuit Breaker bays manufactured under the contract (Indicate nos. of Gas Insulated Switchgear (GIS) Circuit Breaker equipped bays of 345KV or above voltage level, where circuit breaker bay shall be considered as a bay used for controlling a line or a transformer or a reactor or a bus section or a bus coupler and comprising of at least one circuit breaker, one disconnector and three nos. of single phase CTs/Bushing CTs. GIS means SF6 Gas insulated Switchgear.)
Name of the substation or switchyard
Whether 345KV or above voltage level Gas Insulated Switchgear (GIS) Circuit breaker bays, as mentioned above, has been manufactured based on technological support of the Parent/Principal Company under the Contract.
Scope of work involved under the Contract
Details of documents uploaded in support of the above stated experience
Format in support of meeting the requirement of para 1.2 (as applicable) Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
Name of the Collaborator (refer para 1.2), if applicable : #REF!
Name of the 110KV Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS Equipment Manufacturer (refer para 1.2), if applicable : #REF!
1 Name of Contract Undertaken #REF!
2 Contract Reference No. & Date of Award
4(a)(i) No. of Circuit Breaker bays under the contract
(Indicate nos. of Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS Circuit Breaker bays of 110KV or above)
Name of the substation or switchyard
(a)(ii) No. of years, the above Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS CB bays are in operation as on the originally scheduled date of bid opening.
Scope of work involved under the Contract as per IEC
(Tick whichever is/are applicable)
Whether Parent/Principal Company meets the technical experience criteria stipulated at 1.1 above, and the details of which is mentioned at Format-A above. (Applicable for the Bidder/Manufacturer(s) wish/proposes to qualify through Route-3 of Annexure-A(BDS))
Whether legally enforceable undertaking jointly by Bidder/Manufacturer and the Parent/Principal Company (as per enclosed format in Section-VI: Sample Forms and Procedures of bidding document) is furnished along with the bid. (Applicable for the Bidder/Manufacturer(s) wish/proposes to qualify through Route-3 of Annexure-A(BDS))
Confirmation letter from the parent/principal company along with the bid stating that parent/principal company shall furnish performance guarantee, in addition to contract performance guarantee to be submitted by the bidder, for an amount of 10% of the cost of equipment(s) to be manufactured and supplied from the works in India. (Applicable for the Bidder/Manufacturer wish/proposes to qualify through Route-3 of Annexure-A(BDS))
Whether valid collaboration agreement for technology transfer / license to design, manufacture, test and supply 345KV or above voltage level GIS equipment in India furnished along with the bid. (Applicable for the Bidder/Manufacturer(s) wish/proposes to qualify through Route-3 of Annexure-A(BDS))
Name of the substation or switchyard
Whether 110KV or above voltage level Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS Circuit breaker bays, as mentioned above, has been manufactured based on technological support of the Parent/ Principal Company under the Contract.
If Yes, indicate the Name of Parent/ Principal Company(s)
No. of years, the above AIS/GIS Subatation(s) are in operation as on the originally scheduled date of bid opening.
Scope of work involved under the Contract for the above 110KV Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS bay as per IEC as on the originally scheduled date of bid opening
(Tick whichever is/are applicable)
Details of documents uploaded in support of the above stated experience
Format in support of meeting the requirement of para 1.3 (as applicable) Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
Name of the Parent Company/ Principal (refer para 1.3), if applicable: #REF!
Name of the 110KV Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS Equipment Manufacturer (refer para 1.3), if applicable : 0 #REF!
1 Name of Contract Undertaken #REF!
2 Contract Reference No. & Date of Award
4(a)(i) No. of Circuit Breaker bays under the contract
(Indicate nos. of Circuit Breaker bays of 110KV or above)
Name of the substation or switchyard
(a)(ii) No. of years, the above Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS CB bays are in operation as on the originally scheduled date of bid opening.
Scope of work involved under the Contract as per IEC
(Tick whichever is/are applicable)
Whether Joint Deed of Undertaking executed between The Bidder and 110KV Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS Equipment Manufaturer has been enclosed with bid ? (in line with para 1.3 (b)(i) of Annexure-A (BDS)
Whether confirmation letter from the parent/principal company stating that the parent/principal company shall furnish performance guarantee for an amount of 10% of the ex-works cost of such equipment(s) has been enclosed with bid? (in line with para 1.3(b)(ii) of Annexure-A (BDS)
Whether valid collaboration agreement for technology transfer / license to design, manufacture, test and supply 110KV Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS equipment in India has been enclosed with bid ? (in line with para 1.3(b)(iii) of Annexure-A (BDS)
Details of documents uploaded in support of the above stated experience
Format-D: (Route-4)
Format in support of meeting the requirement of para 1.4(Route-4) (as applicable) Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
Bidder’s Name :
1 Name of Contract Undertaken
2 Contract Reference No. & Date of Award
3 Name and Address of the Employer/Utility for whom the Contract was executed by the firm
4(a)(i) Voltage Level of GIS Substation commissioned under the Contract (Indicate 345KV or above class only)
No. of GIS Circuit Breaker equipped bays under the above contract (Indicate nos. of Gas Insulated Switchgear (GIS) Circuit Breaker equipped bays of 345KV or above voltage level, where circuit breaker bay shall be considered as a bay used for controlling a line or a transformer or a reactor or a bus section or a bus coupler and comprising of at least one circuit breaker, one disconnector and three nos. of single phase CTs/Bushing CTs. GIS means SF6 Gas insulated Switchgear.)
Name of the New substation or switchyard
Scope of work involved under the Contract (Tick whichever is/are applicable)
No. of years, the above GIS Circuit Breaker equipped bays have been in operation as on the originally scheduled last date of bid submission mentioned above.
Details of documents uploaded in support of the above stated experience
Name of the Proposed Indian GIS Manufacturer (as per the Route-4 of Annexure-A(BDS)
Whether above Indian GIS Manufacturer meets the requirement mentioned at Route-1 or Route-2 or Route-3 above. (If Yes, Please mentioned the details in the Format-A/Format-B/Format-C above)
Whether Undertaking (Jointly with the GIS Manufacturer) (as per enclosed format in Section-VI, Vol-I of bidding document) for above is enclosed with the bid
Details of documents uploaded in support of the above stated experience
2.0 FINANCIAL REQUIREMENTS :
{In support of its ‘Financial Position’, in line with the above, the Bidder (in case of bidding by single firm ) or each of the Partners of a Joint Venture (in case of bidding by a Joint Venture) or Company/Constituents must provide the relevant information in support of the same, along with documentary evidence, in the following format}
2.1 Financial Qualification Data: 2 or more
Name of the Bidder
Details of documentary evidence submitted in support of Qualification Data
Networth (in Rs. Millions)
Sl No Financial year
Do you have audited results for FY 2020-21 No
B Turnover details:
Details of documentary evidence submitted in support of Qualification Data
Turnover (in Rs. Millions)
Sl No Financial year
Do you have audited results for FY 2016-17 Yes
Do you have audited results for FY 2020-21
Average Annual Turnover for best Three Years is
C Liquid Assets
LA (in Rs. Million)
Details of evidence of having Liquid assets (LA)
Details of evidence of access to or availability of credit facilities
Name of Other Partner-1 of JV
Details of documentary evidence submitted in support of Qualification Data
Networth (in Rs. Millions)
Sl No Financial year
Do you have audited results for FY 2016-17 Yes
Do you have audited results for FY 2020-21
B Turnover details:
Details of documentary evidence submitted in support of Qualification Data
Turnover (in Rs. Millions)
Sl No Financial year
Do you have audited results for FY 2016-17 Yes
Do you have audited results for FY 2020-21
C Liquid Assets
Details of evidence of having Liquid assets (LA)
Details of evidence of access to or availability of credit facilities
Name of Other Partner-2 of JV
Details of documentary evidence submitted in support of Qualification Data
Networth (in Rs. Millions)
Sl No Financial year
Do you have audited results for FY 2016-17 Yes
Do you have audited results for FY 2020-21
B Turnover details:
Details of documentary evidence submitted in support of Qualification Data
Turnover (in Millions)
Sl No Financial year
Do you have audited results for FY 2020-21
Average Annual Turnover for best Three Years is
C Liquid Assets
LA (in Rs. Million)
Details of evidence of having Liquid assets (LA)
Details of evidence of access to or availability of credit facilities
3.0 Joint Venture (JV) Firms {Reference para 3.0 of Annexure-A (BDS)}
JOINT VENTURE BIDS: a) In case a bid is submitted by a Joint Venture (JV) of two or more firms as partners, all the partners of Joint Venture shall meet collectively the complete requirements stipulated at para 1.0 and 2.0 (b) & (c) above. Further, the partner(s) of JV must also meet the following minimum criteria: i. All the partners of the JV shall meet individually the Financial Position criteria given at 2.0(a) above. ii. The Lead Partner shall meet, not less than 40% of the minimum Financial Position criteria given at para 2.0 (b) & (c) iii. Each of the other partner(s) individually shall meet not less than 25% of the minimum Financial Position criteria given at para 2.0 (b) & (c) above The figure of average annual turnover and liquid assets/credit facilities for each of the partners of the JV shall be added together to determine the JV’s compliance with the minimum qualifying criteria set out in Para 2.0 (b) & (c) above. b) However, for a JV to be qualified, the partners of JV must also meet the following minimum criteria: i. One of the partner(s) of JV must meet the Technical Experience criteria and the requirements stipulated under Route-1 or Route-2 or Route-3 as per para 1.0 above. ii. The remaining partner(s) of JV must have erected, tested and commissioned at least two (2) nos. GIS/AIS Circuit Breaker equipped bays@ of 345KV or above voltage level in one (1) substation or switchyard during the last seven (7) years in India and these bays@ must be in satisfactory operation# as on the originally scheduled last date of bid submission mentioned above. Note :- (#) Satisfactory operation means certificate issued by the Employer certifying the operation without any adverse remark.
b) However, for a JV to be qualified, the partners of JV must also meet the following minimum criteria: i. One of the partner(s) of JV must meet the Technical Experience criteria and the requirements stipulated under Route-1 or Route-2 or Route-3 as per para 1.0 above ii. The remaining partner(s) of JV must meet the Technical Experience criteria and the requirements stipulated under Route-1 or Route-2 or Route-3 as per para 1.0 above or must have erected, tested and commissioned at least two (2) nos. GIS/AIS Circuit Breaker equipped bays* of 110kV or above voltage level in one (1) substation or switchyard during the last seven (7) years and these bays must be in satisfactory operation# as on the originally scheduled date of bid opening mentioned above.
In case of Joint venture, the following conditions shall also apply:
(a) the bid, and in case of successful bid, the specified Form of Agreement shall be signed so as to be legally binding on all partners (as per enclosed format in Section-VI, Vol.-I of bidding document).
(b) one of the partners shall be nominated as Lead Partner, and the Lead Partner shall be authorized to incur liabilities and receive instructions for and on behalf of any and all partners of the Joint Venture, and the entire execution of the Contract shall be done with the Lead Partner and payment under the contract shall be received by the Lead Partner on behalf of the Joint Venture as per power conferred to him in the Power of Attorney. The authorization shall be evidenced by submitting a Power of Attorney signed by legally authorized signatory of all the partners as per Performa in in Section-VI, Vol.-I of bidding documents. The payment under the Contract can also be received by other partner(s) based on authorization of Lead Partner.
(c) All partners of the joint venture shall be liable jointly and severally for the execution of the Contract in accordance with the Contract terms and a statement to this effect shall be included in the authorisation mentioned under (b) above as well as in the Bid Form and in the Contract Form (in case of a successful bid);
(d) Agreement entered into by the Joint Venture partners shall be submitted with the bid.
Note :- 1. (#) Satisfactory operation means certificate issued by the Employer certifying the operation without any adverse remark 2. (*) For the purpose of qualifying requirement, one no. of circuit breaker bay shall be considered as a bay used for controlling a line or a transformer or a reactor or a bus section or a bus coupler and comprising of at least one circuit breaker, one disconnector and three nos. of single phase CTs / Bushing CTs. 3. ($) In case of a JV bid involving an Indian Entity qualifying through Route-3 and its parent/ principal company as partner(s), the Indian Entity shall meet the applicable Financial Position criteria on its own and not based on its parent/principal company.
4 The bidder shall furnish documentary evidence in support of the qualifying requirement stipulated as above
4.1 In accordance with the above, in case of JV bidders, it should be ensured that necessary details including those pertaining to each JV partner are furnished and the documents are submitted alongwith the bid. Further, the JV bidders should also ensure that other requirements are complied with. The lists of documents furnished are to be indicated below :
A For Name of the Bidder
B For Name of Other Partner-1 of JV
C For Name of Other Partner-2 of JV
Format in support of meeting the requirement of para 3.0(b)(ii) of Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
Name of the Partner of JV
1 Name of Contract Undertaken
2 Contract Reference No. & Date of Award
3 Name and Address of the Employer/Utility for whom the Contract was executed by the firm
4(a)(i) Voltage Level of AIS/GIS Substation commissioned under the Contract (Indicate 345KV or above class only)
No. of AIS/GIS Circuit Breaker equipped bays under the above contract (Indicate nos. of AIS/Gas Insulated Switchgear (GIS) Circuit Breaker equipped bays of 345KV or above voltage level, where circuit breaker bay shall be considered as a bay used for controlling a line or a transformer or a reactor or a bus section or a bus coupler and comprising of at least one circuit breaker, one disconnector and three nos. of single phase CTs/Bushing CTs.)
Name of the substation or switchyard
Scope of work involved under the Contract (Tick whichever is/are applicable)
No. of years, the above AIS/GIS Circuit Breaker equipped bays have been in operation as on the originally scheduled last date of bid submission mentioned above.
Details of documents uploaded in support of the above stated experience
5.0 The Bidder shall also furnish following documents/details with its bid. {Reference ITB clause 9.3 (c)}
5.1 The complete annual reports together with Audited statement of accounts of the company for last five years of its own (separate) immediately preceding the date of submission of bid.
Note I. In the event the bidder is not able to furnish the information of its own (i.e separate), being a subsidiary company and its accounts are being consolidated with its group/holding/parent company, the bidder should submit the audited balance sheets, income statements, other information pertaining to it only (not of its group/Holding/Parent Company) duly certified by any one of the authority [ (i) Statutory Auditor of the bidder /(ii) Company Secretary of the bidder or (iii) A certified Public Accountant] certifying that such information/documents are based on the audited accounts as the case may be.
II. Similarly, if the bidder happens to be a Group/Holding/Parent Company, the bidder should submit the above documents/information of its own (i.e. exclusive of its subsidiaries) duly certified by any one of the authority mentioned in Note-I above certifying that these information/documents are based on the audited accounts, as the case may be.
5.2 The Bidder should accordingly also provide the following information/documents (In case of JV bidders, information should be provided separately for all the Partners of JV in the given format):
Audited balance sheet and income statements for the last five years as per the following:
For Name of Other Partner-1 of JV For Name of Other Partner-2 of JV
A Years preceding to the bid opening Audited Balance Sheet and Income Statements enclosed Audited Balance Sheet and Income Statements enclosed
1st Year Yes Yes
2nd Year Yes Yes
3rd Year Yes Yes
4th Year Yes Yes
5th Year Yes Yes
6 In addition to the data/details furnished as above, the information available at ‘Information on Record’ (IoR) portal of POWERGRID may also be considered as our submission for purpose of QR compliance.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-4
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Form of Certificate of Origin and Eligibility)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We hereby certify that equipment and materials to be supplied are produced in [Enter the name of country where from equipments & material shall be supplied] eligible source country. Equipments & Materials produced in [Name of countries] Company incorporated & registered in [Name of countries]
We hereby certify that our company is incorporated and registered in [Enter the name of country where from equipments & material shall be supplied] eligible source country.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
country. country. [Enter the name of country where from equipments & material shall be supplied] [Enter the name of country where from equipments & material shall be supplied]
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-4 (A)
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(List of Special Maintenance Tools & Tackles)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We are furnishing below the list of special maintenance tools & tackles for various equipment under the subject package. The prices for these tools & tackles are included in our lumpsum bid price. We further confirm that the list of special maintenance tools & tackles includes all the items specifically identified in your bidding documents as brought out below:
S.No. For Equipment Item Description Unit Quantity
Notwithstanding what is stated above, we further confirm that any additional special maintenance tools and tackles, required for the equipment under this package shall be furnished by us at no extra cost to the employer.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-4 (A)
(List of Special Maintenance Tools & Tackles)
S.No. For Equipment Item Description Unit Quantity
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-5
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Bought-out & Sub-contracted Items)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We hereby furnish the details of the all major items of supply or services i.e. items, whose price is more than 10% of the Bid Price, we propose to buy for the purpose of furnishing and installation of the subject 400kV GIS Substation Package SS-149 :
Sl. No. Item Description Quantity proposed to be bought/sub-contracted Details of the proposed sub-contractor/sub-vendor
Name Nationality
We hereby furnish the details of the items/ sub-assemblies propose to supply from our own works (i.e. as direct transactions) in additiona to the supplies the same from other vendors (i.e. as Bought-out transactions) as detailed in the table given above.
Sl. No. Item Description Quantity proposed to be supplied Details of the plant from where supplies are proposed.
Name of Plant Address
2. We hereby declare that, we would not subcontract the erection portion of the contract without the prior approval of Employer.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-5
(Bought-out & Sub-contracted Items)
Sl. No. Item Description Quantity proposed to be bought/sub-contracted Details of the proposed sub-contractor/sub-vendor
Name Nationality
Date : 00-Jan-00 Printed Name : 0
Place : 00-Jan-00 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-5A
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Items, Components, Raw Material, Services proposed to be sourced from Micro and Small Enterprises)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
1. We hereby furnish the details of the items, components, raw material, services which we propose to buy/avail from Micro and Small Enterprises (MSEs) for the purpose of completion of works under the package. i.e.,400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS. 400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
Sl. No. Item Description Quantity proposed to be bought/sub-contracted Name of Micro and Small Enterprises (MSEs)
Name Category (Micro or Small)
We hereby furnish the details of the items/ sub-assemblies propose to supply from our own works (i.e. as direct transactions) in additiona to the supplies the same from other vendors (i.e. as Bought-out transactions) as detailed in the table given above.
Sl. No. Item Description Quantity proposed to be supplied Details of the plant from where supplies are proposed.
Name of Plant Address
2. The above is a list of items we propose to procure from MSEs. However, based on the situations during the execution of the contract, the above list may undergo changes. We hereby confirm that the details regarding actual procurement from MSEs carried out by us, as per the format provided at Section VI, Sample Forms and Procedures (FORMS), Volume-I of bidding documents, shall be submitted along with the bills for payment against supplies made/works done during execution of contract.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-5A
(Items, Components, Raw Material, Services proposed to be sourced from Micro and Small Enterprises)
Sl. No. Item Description Quantity proposed to be bought/sub-contracted Name of Micro and Small Enterprises (MSEs)
Name Category (Micro or Small)
Date : 00-Jan-00 Printed Name : 0
Place : 00-Jan-00 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-6
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Alternative, Deviations and Exceptions to the Provisions)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
The bidder shall itemize any deviation from the Specifications included in his bid. Each item shall be listed (separate sheets may be used and enclosed with this Attachment) with the following information:
Sl. No. Reference clause in the Specifications Deviation Reason for change The change in Bid Prices if the deviation is withdrawn and the Bidder conforms to the Specifications
Any proposed deviation will be applicable only for the bidder whose bid is substantially responsive in accordance with Clause 22, Section ITB, Vol. I of the bidding documents. If a bid is not substantially responsive, it will be rejected and may not subsequently be made responsive by the bidder by correction of the non-conformity.
The above deviations and variations are exhaustive. We confirm that we shall withdraw the deviations proposed by us at the cost of withdrawal indicated in this attachment, failing which our bid may be rejected and Bid Security forfeited.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-6
(Alternative, Deviations and Exceptions to the Provisions)
Sl. No. Reference clause in the Specifications Deviation Cost of withdrawal of the deviation
Date : 00-Jan-00 Printed Name : 0
Place : 00-Jan-00 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-7
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Details of Alternative Bid)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
No Alternative Bid
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-9
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Work Completion Schedule)
Bidder’s Name and Address :
0 Contract Services
Name : Power Grid Corporation of India Ltd.,
Name : 0 "Saudamini", Plot No. 2, Sector 29
Address : 0 Gurgaon (Haryana) - 122001
We hereby declare that the following Work Completion Schedule shall be followed by us in furnishing and installation of the subject package i.e., 400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS. for the period commencing from the effective date of Contract to us :
Sl. No. Description of Work Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS
L1 schedule (Months) 16 16 15
1 Detailed Engineering and drawing submission a) commencement
2 Procurement of equipment/ components & assembly a) commencement
3 Type Tests a) commencement
4 Manufacturing a) commencement
5 Shipments & Delivery a) commencement
6 Establishment of site office
7 Installation at Site a) commencement
8 Testing & Pre-commissioning a) commencement
9 Trial Operation a) commencement
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation: 0
Note: Bidders to enclose a detailed network covering all the activities to be undertaken for completion of the project indicating key dates for various milestones for each phase constituent-wise
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-10
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Guarantee Declaration)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We confirm that the equipments offered shall have minimum (or a maximum, as the case may be) performance specified in Technical Specifications. We further guarantee the performance/ efficency of the equipments in response to the Technical Specifications
We declare that the ratings, performance figures and availability of the system furnished by us for subject Package covered under this specification are guaranteed by us. In particular, we declare that the 1) 10MVA, (220/V3)/(132/V3) kV, 1-phase Autotransformer; 2) 160MVA, 220/132/33 KV, 3-phase Autotransformer as per scope of package) offered under this package shall meet the maximum loss requirement as stipulated in Technical Specifications
We confirm that the equipment offered shall have minimum (or a maximum, as the case may be) performance specified in technical specification. We further guarantee the performance/efficiency of the equipments in response to the technical specification.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-11
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Information regarding Ex-employees of POWERGRID in our Organisation)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We hereby furnish the details of ex-employees of POWERGRID who had retired/ resigned at the level of General Manager and above from POWERGRID and subsequently have been employed by us:
Sl. No. Name of the person with designation in POWERGRID Date of Retirement/ resignation from POWERGRID Date of joining and designation in our organisation
*In case the date of joining in the bidder’s organization of such ex-employee is within 1 year from the date of retirement/resignation from POWERGRID, No Objection Certificate/ approval from the Competent Authority must be furnished along with the bid or subsequent through clarification pursuant to ITB Clause 21.
In case of non-submission of No Objection Certificate/approval of the Competent Authority, as required, We understand that POWERGRID shall deal with such cases as per its Policy and procedures in vogue, which may also result in rejection of our bid. We also confirm that POWERGRID shall be the sole judge in this regard. We further declare that any misrepresentation or submission of false/forged documents/information in this regard shall be dealt with as per the provisions of the Integrity Pact and/or the Bidding Documents and/or POWERGRID’s policy and procedures.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
Note: The information in similar format should be furnished for each partner of joint venture in case of joint venture bid.
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-11
(Information regarding Ex-employees of POWERGRID in our Organisation)
Sl. No. Name of the person with designation in POWERGRID Date of Retirement/ resignation from POWERGRID Date of joining and designation in our organisation
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-11
(Information regarding Ex-employees of POWERGRID in our Organisation)
Sl. No. Name of the person with designation in POWERGRID Date of Retirement/ resignation from POWERGRID Date of joining and designation in our organisation
Date : 00-Jan-00 Printed Name : 0
Place : 00-Jan-00 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-12
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Price Adjustment Data)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No.-2
0 Gurgaon (Haryana) - 122001
We hereby furnish the relevant details pertaining to the price adjustment provisions for equipment as specified in your specifications and documents for the Substation Package SS-149. The necessary documentary evidence is enclosed.
Sl. No. Name of Materials/Labour Value of co-efficient Name of the published index Value of index as on thirty (30) days prior to date of opening in line with Appendix-2, Section-VI, Volume-I
A) For Ex-Works Price Component of AIS Equipment
I Current Transformer
a) Raw Material
b) Labour l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
a) Raw Material
b) Labour l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
II Capacitive Voltage Transformer
a) Raw Material
b) Labour I= l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
III Current Transformer
a) Raw Material
b) Labour l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
IV Circuit Breaker
a) Raw Material
b) Labour l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
V) Surge Arrestor
a) Raw Material
b) Labour I= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
VI) PVC/XLPE Insulated Power and Control Cable
a) a=PVC Compound 0.15
b) Published Price of Metal IEEMA
i) Aluminium per MT IEEMA
ii) Copper per MT IEEMA
c) Weight in MT of Metal per kM (Size wise)
VII) Sub Station Structures (including Bolts & Nuts)
i) Lattice Steel Structures & Pipe Structures (including bolts & nuts, washers & foundation bolts)
a) Raw Materials
i) a=Structural steel a= 0.58 JPC Market Price (Retail) for average Price of Steel Angles of size 50 x 50 x 6 mm of all cities in Rs./MT as published by Joint Plant Committee(JPC).
ii) b=Electrolytic Zinc b= 0.16 IEEMA
b) Labour l= 0.11 Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
VIII. Series Reactor [ 420 kV, 12 ohm, 2500A, 1-ph air core dry type Series Reactor]
a) Raw Material Copper(a)
i) Aluminium(a) Aluminium(a)
b) Labour I= 0.85 Indian field labour index – namely All India average consumer price index for Industrial Workers (monthly) (Base: 2001= 100), as published by Labour Bureau, Shimla, Government of India (www.labourbureau.nic.in).
The value of coefficient for raw materials: a=0.65 to 0.73 and value of coefficient for labour shall be between 0.12 and 0.20, so that sum of all the coefficients including labour shall be a+l=0.85
B. For Installation (including Civil Works) Price Component
I Installation price component (including Civil works but excluding ‘supply & placement of reinforcement steel’ and ‘concreting’)
i) Labour I= l= 0.80 Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
II Supply & Placement of Reinforcement Steel
i) HSD a= 0.10 Wholesale Price Index Number for `HSD’(Individual Commodity) (monthly) (Base: 2011-12=100), as published by Office of Economic Advisor, Ministry of Commerce & Industry(www.eaindustry.nic.in).
ii) Labour I= l= 0.05 Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
iii) Manufacture of Basic Metals b= 0.65 Wholesale Price Index Number for `Manufacture of Basic Metals’(Group Item) (monthly) (Base: 2011-12=100), as published by Office of Economic Advisor, Ministry of Commerce & Industry(www.eaindustry.nic.in).
III For Concereting
i) HSD a= 0.20 Wholesale Price Index Number for `HSD’(Individual Commodity) (monthly) (Base: 2011-12=100), as published by Office of Economic Advisor, Ministry of Commerce & Industry(www.eaindustry.nic.in).
ii) Labour I= l= 0.10 Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
iii) Manufacture of cement, lime and plaster b= 0.30 Wholesale Price Index Number for `Manufacture of cement, lime and plaster’(Group Item) (monthly) (Base: 2011-12=100), as published by Office of Economic Advisor, Ministry of Commerce & Industry (www.eaindustry.nic.in)
iv) Cutting, shaping and finishing of stone c= 0.20 Wholesale Price Index Number for `Cutting, shaping and finishing of stone’(Group Item) (monthly) (Base: 2011-12=100), as published by Office of Economic Advisor, Ministry of Commerce & Industry(www.eaindustry.nic.in).
The Bidders are required to estimate and indicate the values of different coefficients for each of the items in the price variation formulae within the specified range such that their summation is as specified in the Bidding Documents. Where no value or ‘-’ or ‘shall be furnished later’ is specified against the coefficient, the same will be deemed to be zero and the fixed component would be suitably adjusted. If the values of all coefficients in price variation formulae indicated by the Bidder are within the specified range but their sum exceeds the summation specified in the Bidding Documents, the values of the coefficients shall be pro-rata adjusted such that the summation remains as per the provisions of the Bidding Documents. If the values of all coefficients indicated by the Bidder are within the specified range but their summation is less than the value specified in the Bidding Documents, the values of the coefficients as indicated by the Bidder shall be considered as such and the fixed component in the price variation formulae would be suitably adjusted. Further, if any of values of the coefficients indicated by the Bidder is out of the range specified in the Bidding Documents, the lower of the values, as indicated by the Bidder vis-à-vis lower value of the range for that coefficient specified in the Bidding Documents, shall be considered and the fixed component would be suitably adjusted.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-13
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Declaration regarding Social Accountability)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We conform that we stand committed to comply to all requirements of Social Accountability Standards i.e., SA8000 (latest Standard available at www.sa-intl.org) and maintain the necessary records.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-14
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
Integrity Pact is annexed herewith this Volume.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
Instruction for printing & submitting Integrity Pact
1. The requisite format of Integrity Pact is getting generated automatically and displayed here below.
2. Take print out of first page on a non-judicial stamp paper of Rs. 100/- and other seven pages on plain A4 size paper. Such two sets shall be prepared by the bidder.
3. All the pages of both the copies of the Integrity Pact shall be signed by the authorised representative of the bidder and duly stamped.
4. Both the original copies shall be submitted by the bidder in the form of Hard Copy as part of the first envelope before due date & time of submission of the bid.
5. For further details bidders may please refer ITB Clause 9.3 (o).
Power Grid Corporation of India Limited 0 0
having its Registered Office at B-9, Qutab Institutional Area, Katwaria Sarai, New Delhi – 110016 hereinafter referred to as 0 0
"POWERGRID", 0 0
having its Registered Office at 1 having its Registered Office at ,
hereinafter referred to as
"The Bidder/Contractor"
POWERGRID intends to award, under laid-down organisational procedures, contract(s) for 400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS., [Specification No.: CC/NT/W-GIS/DOM/A10/25/06459]
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Integrity Pact Page 1 of 8
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS., [Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] values full compliance with all relevant laws of the land, rules, regulations, economic use of resources, and of fairness / transparency in its relations with its Bidders/ Contractors.
In order to achieve these goals, POWERGRID and the above named Bidder/Contractor enter into this agreement called 'Integrity Pact' which will form a part of the bid.
It is hereby agreed by and between the parties as under:
Section I - Commitments of POWERGRID
(1) POWERGRID commits itself to take all measures necessary to prevent corruption and to observe the following principles :
a) No employee of POWERGRID, personally or through family members, will in connection with the tender, or the execution of the contract, demand, take a promise for or accept, for him/herself or third person, any material or other benefit which he/she is not legally entitled to.
b) POWERGRID will, during the tender process treat all Bidder(s) with equity, fairness and reason. POWERGRID will in particular, before and during the tender process, provide to all Bidder(s) the same information and will not provide to any Bidder(s) confidential/ additional information through which the Bidder(s) could obtain an advantage in relation to the tender process or the contract execution.
c) POWERGRID will exclude from evaluation of Bids its such employee(s) who has any personnel interest in the Companies/Agencies participating in the Bidding/Tendering process and all known prejudiced persons.
(2) If POWERGRID obtains information on the conduct of any of its employee which is a criminal offence under the IPC / PC Act , or if there be a substantive suspicion in this regard, POWERGRID will inform its Chief Vigilance Officer and in addition disciplinary actions can be initiated under POWERGRID’s Rules.
Section II - Commitments of the Bidder/Contractor
(1) The Bidder/Contractor commits itself to take all measures necessary to prevent corruption. The Bidder/Contractor commits itself to observe the following principles
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Integrity Pact Page 2 of 8
during his participation in the tender process and during the contract execution :
a) The Bidder/Contractor will not, directly or through any other person or firm, offer, promise or give to any of POWERGRID's employees involved in the tender process or the execution of the contract or to any third person any material or other benefit which it is not legally entitled to, in order to obtain in exchange an advantage of any kind whatsoever during the tender process or during the execution of the contract
b) The Bidder/Contractor will not enter into any illegal or undisclosed agreement or understanding, whether formal or informal with other Bidders/Contractors. This applies in particular to prices, specifications, certifications, subsidiary contracts, submission or non-submission of bids or actions to restrict competitiveness or to introduce cartelization in the bidding process.
c) The Bidder/Contractor shall not pass any information provided by POWERGRID as part of business relationship to others and shall not commit any offence under PC / IPC Act.
d) The Bidder/Contractor of foreign origin shall disclose the name and address of the Agents/representatives in India, if any, involved directly or indirectly in the Bidding. Similarly, the Bidder/Contractor of Indian Nationality shall furnish the name and address of the foreign principals, if any, involved directly or indirectly in the Bidding.
e) The Bidder/Contractor will, when presenting his bid, disclose any and all payments made, or committed to or intends to make to agents, brokers or any other intermediaries in connection with the award of the contract and/or with the execution of the contract.
f) The Bidder/Contractor will not misrepresent facts or furnish false/forged documents/information in order to influence the bidding process or the execution of the contract to the detriment of POWERGRID.
g) The Bidder/Contractor shall ensure adoption of Integrity Pact by its Sub-contractors and shall be responsible for the same.
(2) The Bidder/Contractor will not instigate third persons to commit offences outlined above or be an accessory to such offences.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Integrity Pact Page 3 of 8
Section III- Disqualification from tender process and exclusion from future contracts
(1) If the Bidder, before contract award, has committed a transgression through a violation of Section II or in any other form such as to put his reliability or credibility as Bidder into question, POWERGRID may disqualify the Bidder from the tender process or terminate the contract, if already signed, for such reason.
(2) If the Bidder/Contractor has committed a transgression through a violation of Section II such as to put his reliability or credibility into question, POWERGRID may, after following due procedures, ban /blacklist the Bidder/Contractor in line with POWERGRID’s policy for “Black-Listing of Firms / Banning of Business”. The imposition and duration of the ban will be determined by the severity of the transgression. The severity will be determined by the circumstances of the case, in particular the number of transgressions, the position of the transgressors within the company hierarchy of the Bidder/Contractor and the amount of the damage. The ban will be imposed for a maximum of 3 years.
(3) If the Bidder/Contractor can prove that he has restored/recouped the damage caused by him and has installed a suitable corruption prevention system, POWERGRID may revoke the ban prematurely.
Section IV - Liability for violation of Integrity Pact
(1) If POWERGRID has disqualified the Bidder from the tender process prior to the award under Section III, POWERGRID is entitled for forfeiture of the Bid Guarantee under the Bid.
(2) If POWERGRID has terminated the contract under Section III or if POWERGRID is entitled to terminate the contract under Section III, POWERGRID shall be entitled to forfeit the Contract Performance Guarantee of this contract, in full or part thereof as may be decided, besides resorting to other remedies under the contract.
Section V- Previous Transgression
(1) The Bidder shall disclose in its Bid any transgressions occurred in the last 10 years with any other Public Sector Undertaking or Government Department or any other Company, in any country, that may impinge on the Anti-corruption principle.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Integrity Pact Page 4 of 8
(2) If the Bidder makes incorrect statement on this subject, it can be disqualified from the tender process or the contract, if already awarded, can be terminated for such reason and further action can be taken in line with POWERGRID’s policies.
Section VI - Equal treatment to all Bidders / Contractors
(1) POWERGRID will enter into agreements with identical conditions as this one with all Bidders.
(2) POWERGRID will disqualify from the tender process any bidder who does not sign this Pact or violate its provisions.
Section VII - Punitive Action against violating Bidders / Contractors
If POWERGRID obtains knowledge of conduct of a Bidder or a Contractor or his subcontractor or of an employee or a representative or an associate of a Bidder or Contractor or his Subcontractor which constitutes corruption, or if POWERGRID has substantive suspicion in this regard, POWERGRID will inform the Chief Vigilance Officer (CVO).
(*)Section VIII - Independent External Monitor/Monitors
(1) POWERGRID has appointed a panel of Independent External Monitors (IEMs) for this Pact with the approval of Central Vigilance Commission (CVC), Government of India. The names of the IEMs have been indicated in the Bidding Documents.
(2) The panel of IEMs shall review independently and objectively, whether and to what extent the parties comply with the obligations under this agreement. The panel of IEMs has right of access to all project documentation. The panel of IEMs may examine any complaint received by them and submit a report to Chairman-cum-Managing Director, POWERGRID, giving joint findings, at the earliest. The panel of IEMs may also submit a report directly to the CVO and the CVC, in case of suspicion of serious irregularities attracting the provisions of the PC Act.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Integrity Pact Page 5 of 8
(3) The IEM is not subject to instructions by the representatives of the parties and performs his functions neutrally and independently. He / She reports to the Chairman-cum-Managing Director, POWERGRID.
(4) The Bidder(s)/Contractor(s) accepts that the IEM has the right to access without restriction to all documentation of POWERGRID related to this contract including that provided by the Contractor/Bidder. The Bidder/Contractor will also grant the IEM, upon his / her request and demonstration of a valid interest, unrestricted and unconditional access to their documentation. The same is applicable to Subcontractors. The IEM is under contractual obligation to treat the information and documents of the Bidder(s)/Contractor(s)/Subcontractor(s) with confidentiality.
(5) POWERGRID will provide to the IEMs information as sought by him / her which could have an impact on the contractual relations between POWERGRID and the Bidder/Contractor related to this contract. The IEMs shall also sign declaration on ’Non-Disclosure of Confidential Information’ and of ‘Absence of Conflict of Interest’. In case of any conflict of interest arising at a later date, the IEM shall inform Chairman-cum-Managing Director, POWERGRID and recuse himself/herself from that case.
(6) As soon as the IEM notices, or believes to notice, a violation of this agreement, he / she will so inform the Chairman-cum-Managing Director, POWERGRID and request the Chairman-cum-Managing Director, POWERGRID to discontinue or take corrective action, or to take other relevant action. The IEM can in this regard submit non-binding recommendations. Beyond this, the IEM has no right to demand from the parties that they act in a specific manner, refrain from action or tolerate action. However, the IEM shall give an opportunity to POWERGRID and the Bidder/Contractor, as deemed fit, to present its case before making its recommendations to POWERGRID.
(7) The IEM will submit a written report to the Chairman-cum-Managing Director, POWERGRID within 8 to 10 weeks from the date of reference or intimation to him by POWERGRID and, should the occasion arise, submit proposals for correcting problematic situations.
(8) If the IEM has reported to the Chairman-cum-Managing Director, POWERGRID, a substantiated suspicion of an offence under PC / IPC Act, and the Chairman-cum-Managing Director, POWERGRID has not, within the reasonable time taken visible action to proceed against such offence or reported it to the CVO, the Monitor may also transmit this information directly to the CVC, Government of India.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Integrity Pact Page 6 of 8
(9) While representing any matter in relation to the Integrity pact inter-alia including its transgression to the panel of IEMs, POWERGRID and Bidder/Contractor shall not approach the court of law and await the decision of the IEM in the matter.
(10) The word ‘IEM’ would include both singular and plural.
(*) This Section shall be applicable for only those packages wherein the IEMs have been identified in Section – I : Invitation for Bids and/or Clause ITB 9.3 in Section – III: Bid Data Sheets of Conditions of Contract, Volume-I of the Bidding Documents.
Section IX - Pact Duration
This Pact begins when both parties have legally signed it. It expires for the Contractor after the closure of the contract and for all other Bidder's six month after the contract has been awarded.
Section X - Other Provisions
(1) This agreement is subject to Indian Law. Place of performance and jurisdiction is the establishment of POWERGRID. The Arbitration/Conciliation clause provided in the main tender document / contract shall not be applicable for any issue / dispute arising under Integrity Pact.
(2) Changes and supplements as well as termination notices need to be made in writing. Side agreements have not been made.
(3) If the Contractor is a partnership firm or a consortium or Joint Venture, this agreement must be signed by all partners, consortium members and Joint Venture partners.
(4) Nothing in this agreement shall affect the rights of the parties available under the General Conditions of Contract (GCC) and Special Conditions of Contract (SCC).
(5) Issues like Warranty/Guarantees etc. shall be outside the purview of IEMs.
(6) Views expressed or suggestions/submissions made by the parties and the recommendations of the CVO/IEM# in respect of the violation of this agreement, shall not be relied on or introduced as evidence in the arbitral/conciliation or judicial proceedings (arising out of the arbitral/conciliation proceedings) by the parties in connection with the disputes/differences arising out of the subject contract
# CVO shall be applicable for packages wherein IEM are not identified in Section IFB/BDS of Condition of Contract, Volume-I. IEM shall be applicable for packages wherein IEM are identified in Section IFB/BDS of Condition of Contract, Volume-I.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Integrity Pact Page 7 of 8
(7) Should one or several provisions of this agreement turn out to be invalid, the remainder of this agreement remains valid. In this case, the parties will strive to come to an agreement to their original intentions.
Signature Signature
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
(Office Seal) (Office Seal)
Designation : Designation :
Witness 1 : Witness 1 :
Designation : Designation :
Witness 2 : Witness 2 :
Designation : Designation :
Integrity Pact Page 8 of 8
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] Attachment-15
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
Option for Initial Advance (either Interest Bearing Initial Advance or No Initial Advance) and Information for E – payment, PF details and declaration for Micro/Small and Medium Enterprise
Bidder’s Name and Address : To:
0 Contract Services
Name : Power Grid Corporation of India Ltd.,
Name : 0 "Saudamini", Plot No. 2, Sector 29
Address : 0 Gurgaon (Haryana) - 122001
I We have read the provisions in the Bidding Documents regarding furnishing the option for advance payment. Accordingly, as per ITB Clause 9.3 as provided in Section BDS, Section III, Vol.-I of the Bidding Documents, we hereby confirm to opt the following:
A1 Interest Bearing Initial Advance
Supply Portion:
Services Portion:
A2 Interest Bearing Engineering Advance :
II We are furnishing the following details of Statutory Registration Numbers and details of Bank for electronic payment.
1. Name of the Supplier/ Contractor in whose favour payment is to be made #REF!
2. Address with PIN Code and State
Registered Office:
Correspondence Address:
3. (a) Status – Company/others
[Declaration of Micro/ Small/ Medium Enterprise under Micro/ Small & Medium Enterprises Development Act 2006, if applicable]
3. (b) Are you a MSE owned by SC/ST* entrepreneurs in line with Public Procurement Policy for Micro and Small Enterprises (MSEs) order 2012 including subsequent amendment/notification/order (Indicate Yes/No) Note: Documentary evidence is to be attached. Please refer remarks at the end of the attachment. No
3. (c ) If 3(b) is ‘Yes’ please mention whether you are (Proprietary MSE/ Partnership MSE/ Private Limited Company) owned by SC/ST entrepreneurs
3. (d ) Are you a MSE owned by women in line with Public Procurement Policy for Micro and Small Enterprises (MSEs) order 2012, Public Procurement Policy for Micro and Small Enterprises (MSEs) Amendment order 2018 including subsequent amendment/notification/order (Indicate Yes/No) Note: Documentary evidence is to be attached.
4. Permanent Account (PAN) No.
5. GSTIN Numbers
I. GSTIN in the Sates/UT from where the supply of goods take place
Name of the States/UT GSTIN number
II. GSTIN in the States/UT where the supply for services take place (states where sites under the subject package is situated)
Name of the States/UT GSTIN number
6 PF Registration No. of the Company
7 PF Regional Office covered (with Address)
8 Name of Contact Person
9 Contact Details
10 Bank Details for Electronic Payment
Name of the Bank:
Address of Branch:
Type of Account:
Type of Account: Saving Account
11 9 digit MICR code printed at bottom in middle, next to cheque no.
12 IFSC (for RTGS)/NEFT Code (to be obtained from the Bank) Sample Cancelled Cheque to be enclosed
We hereby declare that the above information are true and correct and we agree that the payment on account of this Contract, in the event of award, be made in the above account maintained in the above mentioned Bank.
*The definition of MSEs owned by SC/ST is as given under:
a. In case of proprietary MSE, proprietor(s) shall be SC /ST.
b. In case of partnership MSE, the SC/ST partners shall be holding at least 51% shares in the unit.
c. In case of Private Limited companies, at least 51% share shall be held by SC/ST promoters.
Documentary evidence: Please provide scanned copy(ies) of the SC/ST certificate(s) issued by District Authority as applicable for SC/ST MSE category as per (a), (b) or (c) above.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-16
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Additional Information)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
In support of the additional information required as per ITB Sub-Clause 9.3 (q) of the Bidding Documents, we furnish herewith our data/details/documents etc., alongwith other information, as follows (the stipulations have been reproduced in italics for ready reference):
1.0 The Bidder shall furnish
Certificate from their Banker(s) (as per prescribed formats in Form 16, Section-VI: Sample Forms and Procedures) indicating various fund based/non fund based limits sanctioned to the Bidder and the extent of utilization as on date. Such certificate should have been issued not earlier than three months prior to the date of bid opening. Wherever necessary the Employer may make queries with the Bidders’ Bankers. [Reference ITB clause 9.3(q)(i)]
1.1 In accordance with 1.0, certificate(s) from banker as per requisite format, indicating various fund based/non fund based limits sanctioned to the bidder or each member of the joint venture and the extent of utilization as on date is/are enclosed, as per the following details:
Name of the Bidder : 0 1
Name of the Banker by whom certificate issued 0
Date of certificate (should not be earlier than 3 months prior to date of bid opening)
Whether fund based/non fund based limits are indicated in the certificate
Whether extent of utilization is indicated in the certificate
1.2 The Bidder should accordingly also provide the following information/documents
(i) Details of Banker:
Address of Banker
Contact Name and Title
(ii) As per para 1.0, Authorization Letter(s) from the bidder addressed to the Banker(s), authorizing POWERGRID to seek queries about the bidder with the Banker(s) and advising the Banker(s) to reply the same promptly, is/are enclosed as per following details:
Sl. No. Letter Ref. Date Addressed to (name of the Bank)
2.0 Litigation History
The bidder should provide detailed information on any litigation or arbitration arising out of contracts completed or under execution by it over the last five years. A consistent history of awards involving litigation against the Bidder or any partner of JV may result in rejection of Bid. [Reference ITB clause 9.3(q)(ii)]
2.1 Details of litigation history resulting from Contracts completed or under execution by the bidder over the last five years. A consistent history of awards invlolving litigation against the Bidder or any patner of JV may result in rejection of Bid. [(Refer ITB Clause 9.3 (q)(ii))]
Year Name of client, cause of litigation/arbitration and matter in dispute Details of Contract and date Award for or against the bidder Disputed amount
3.0 Details regarding previous transgressions of Integrity Pact The bidder should provide detailed information on any transgression of Integrity Pact that occurred in the last 10 years with any other Public Sector Undertaking or Government Department or any other Company, in any country
3.1 Details regarding previous transgressions of Integrity Pact that occurred in the last 10 years
Year Name of the Clients Details of Transgression of Integrity Pact by the bidder
4.0 OTHER INFORMATION
4.1 Current Contract Commitments of works in progress
Bidders should provide information on their current commitments on all contracts that have been awarded, or for which a letter of intent or acceptance has been received, or for contracts approaching completion, but for which an unqualified, full completion certificate has yet to be issued.
Details of Contract Value of outstanding work (Rs.) Estimated completion date
4.2 Financial Data:
Figures Rs in Million
Details Actual (Previous five years) Projection for next five years
Total Liability
Current Liability
Profit before taxes
Profit after taxes
4.3 Details of Provident Fund Code Number of the Bidder
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-17
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Declaration for tax exemptions, reductions, allowances or benefits)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
Dear Sirs, 1. We confirm that we are solely responsible for obtaining following tax exemptions, reductions, allowances or benefits in respect of supplies under the subject package, in case of award. We further confirm that we have considered the same in our bid thereby passing on the benefit to POWERGRID while quoting our prices. In case of our failure to receive such benefits, partly or fully, for any reason whatsoever, the Employer will not compensate us. 2. We are furnishing the following information required by the Employer for issue of requisite certificate if and as permitted in terms of the applicable Govt. of India policies/procedures (in case of award):
Applicable Act, Notification No. and Clause Ref. No. Sl. No. Description of item on which applicable Country of origin Remarks, if any
(The requirements listed above are as per current Notification of Govt. of India indicated above. These may be modified, if necessary, in terms of the Notifications.)
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
Instruction for printing & submitting Safety Pact
1. The requisite format of Safety Pact is getting generated automatically and displayed here below:
2. Take print out of first page on a non-judicial stamp paper of Rs. 100/- and other four pages on plain A4 size paper. Such two sets shall be prepared by the bidder.
3. All the pages of both the copies of the Safety Pact shall be signed by the authorised representative of the bidder and duly stamped.
4. Both the original copies shall be submitted by the bidder in the form of Hard Copy as part of the first envelope before due date & time of submission of the bid.
5. For further details bidders may please refer ITB Clause 9.3 (s).
Power Grid Corporation of India Limited 0 0
having its Registered Office at B-9, Qutab Institutional Area, Katwaria Sarai, New Delhi – 110016 hereinafter referred to as 0 0
"POWERGRID", 0 0
0 1 having its Registered Office at ,
having its Registered Office at, 0, 0, 0 0 AND
hereinafter referred to as
"The Bidder/Contractor"
POWERGRID intends to award, under laid-down organisational procedures, contract(s) for 400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459]
POWERGRID values full compliance with all relevant laws and regulations and the principles of Safety, Health& Environment in its relations with its Bidders/ Contractors
In order to achieve these goals, POWERGRID and the above named Bidder / Contractor enter into this agreement called “Safety Pact” which will form part of the Bid. It is hereby agreed by and between the parties as under:
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Safety Pact Page 1 of 5
Section I – Commitments of POWERGRID:
POWERGRID commits itself to take all measures necessary to prevent accidents duringConstruction and Operation of the Transmission Assets and to observe the following:
In order to achieve these goals, POWERGRID and the above named Bidder/Contractor enter into this agreement called 'Safety Pact' which will form a part of the bid.
1 POWERGRID recognizes and accepts its statutory responsibilities for ensuring construction, operation and maintenance of equipments and for the provision of safe methods of work and safe working conditions.
2 POWERGRID recognizes and accepts its statutory responsibilities for ensuring safety of not only its employees but also that of the Contracting Agencies as Principal Employer.
3 POWERGRID shall review the accidents in a structured manner and take necessary actions to ensure that the safety criteria are strengthened for safe construction as well as Operation & Maintenance of the Transmission Assets.
4 POWERGRID shall conduct necessary awareness and training programmes to its Employees to augment the various safety requirements to be followed during Construction and Operation & Maintenance of the Transmission Assets from time to time
5 POWERGRID shall, from time to time, issue necessary guidelines,instructions and deterrents to its employees as well as to the Contracting Agencies, to update them to take necessary preventive measures to avoid repetition of similar accident attributes.
6 POWERGRID shall review and provide necessary guidanceto the Contracting Agencies, as and when, any abnormality / special situations are brought to its notice by the Contracting Agencies during execution of the Transmission Projects being executed by them.
7 POWERGRID shall conduct periodical surveillance site inspections / audits to identify the unsafe conditions and unsafe actions, and bring them to the knowledge of the Contracting Agencies for taking timely corrective actions.
8 POWERGRIDshall investigate all accidents, fatal as well as non-fatal, to identify the lapses, the reason for the accident / incident and suggest measures for prevention of recurrence of such accidents, and fix responsibility for the lapses leading to the accident.
9 POWERGRID shall augment the training to the workers and supervising personnel of the Contracting Agencies, as per schedules, upon nomination by the Contracting Agencies in reasonable time frame.
10 POWERGRID shall exercise the right to claim and recover compensation from the Contracting Agencies in case of any violation of the safety requirements / provisions during execution of the Transmission Projects, as built in the applicable Laws and contractual specifications / guidelines in vogue / issued by POWERGRID from time to time.
11 Section II – Commitments of the Bidder / Contractor:
The Bidder / Contractor commits himself to take all measures necessary to prevent / minimise accidents at their construction / erection sites and to observe the following:
1 The Bidder / Contractor recognizes and acceptsthe statutory and comprehensive responsibility for ensuring safe construction and Testing & Commissioning in the Transmission Projects being executed by thembyproviding safe methods of work, working conditions and Tools & Plants for human safety.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Safety Pact Page 2 of 5
2 The Bidder / Contractor recognizes and accepts the responsibilities for ensuring safety of not only their employees but also that of the Sub-contractors, Principal Employer and the general public during execution of the Transmission Projects / works.
3 The Bidder / Contractor shall review the accidents in a structured manner and take necessary actions to ensure that the safety criteria are strengthened for safe construction of the Transmission Assets.
4 The Bidder / Contractor shall endeavour continuous development of safe methods of work to ensure that the effect of risks and perils are minimised to the extent possible and implement the same at their worksites.
5 The Bidder / Contractor shall conduct periodical Training to their Employees as well as to that of theirSub-contractors for safety awareness during construction works being executed by them.
6 The Bidder / Contractor shall provide all requisite Tools & Plants required for the work and ensure their healthiness by periodical inspections / testing as required. Unhealthy and sub-standard Tools & Plants will be immediately removed from site as and when they are identified.
7 The Bidder / Contractor shall,at their cost, provide all necessary Personal Protective Equipments such as Double Lanyard Safety Belts, Appropriate Fall Arrest Systems, Safety Helmets, Foot Wear, Hand Gloves, etc., as required for various activities pertaining to execution of the Projects / works, confirming to relevant Indian Standards.
8 The Bidder / Contractor shall ensure that dedicated qualified Safety Officers are posted in the construction projects being executed by them and ensure that the Safety Officer visits each and every gang periodically and conducts audits / inspections to identify the unsafe conditions and unsafe actions, to be rectified by the site supervising personnel promptly.
9 The Bidder / Contractor shall conduct appropriate medical checks-up for the workers before deploying them at their construction sites to ensure that only those who are medically fit are deployed in the Projects / works to be executed by them. The copy of the Medical Reports shall be provided by the Bidder / Contractor to POWERGRID, whenever requested by POWERGRID.
10 The Bidder / Contractor shall screen the workers before deploying them at their construction sites to ensure that only those with the skills, experience and competence to work at heightand also medically fitfor work at height are deployed for work at height in the Projects executed by them.
11 The Bidder / Contractor shall ensure daily before starting the work thattheir site Supervising Personnel / Safety Officer briefs the workers about the work for the day and the safety measures / precautions required to be taken by them.
12 The Bidder / Contractor shall investigate all the accidents at their working sites to ascertain the lapses leading to the incident and the precautionary / corrective measures required to be taken to avoid recurrence of such accidents. These accidents will be reviewed at the Board Management level of the Agencies and the findings / recommendations will be put up to POWERGRID Apex Safety Board within the stipulated period.
13 The Bidder / Contractor shall ensure that all accidents, whether fatal or non-fatal in nature, will be informed to POWERGRID, in writing, immediately on the occurrence of the same,and in any case, within not more than 24 hours of occurrence of the same.
14 The Bidder / Contractor shall ensure that in case of any accident, all necessary medical help / supportshall be provided to the victims / injured till they are completely fit to return to work.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Safety Pact Page 3 of 5
15 The Bidder / Contractorshall ensure that in case of fatal accidents, all statutory Authorities, including Police, concerned Labour Dept. Officials, concerned Workmen Compensation Commissioner, etc., will be intimated in writing as required by the statutory Law, and followed up for compliance of all statutory obligations. The Bidder / Contractor shall own full responsibility of timely accident reporting to various authorities, including POWERGRID.
16 The Bidder / Contractor shall ensure that in case of fatality or serious injury leading to permanent disablement of the victims, the compensation amount will be deposited with the concerned authorities, as required by the Laws, and followed up for early disbursement to the beneficiaries of the victims.
17 The Bidder / Contractor assures that they shall co-operate to the fullest extent for carrying out any investigation of the accidents at their work sites by POWERGRID to identify the lapses, the reason for the accident / incident and suggest measures for prevention of recurrence of such accidents. All factual details of the occurrence of the accident will be provided to POWERGRID, as and when required.
18 The Bidder / Contractor assures that they take full responsibility of meeting the statutory obligations in case of accidents, and in case of any reference by any Statutory Body at a later date also, they shall provide all information to POWERGRID and meet all the statutory obligations, including payment of additional compensation, if any.
19 The Bidder / Contractor assures that in case of any inspection of their work site or Notice by any Statutory Authority, they shall comply promptly and inform POWERGRID Site Officials of the same, and also provide all necessary information and assistance for smooth compliance of the observations / instructions of such Authorities.
20 The Bidder / Contractor accepts the provisions regarding safety, including payment of any sums to POWERGRID, in case of any violation of the safety requirements / provisions during execution of the Transmission Projects, as built in the Contractual Conditions, Safety Planand the Safety Pact, and confirm to abide by the same.
Section III – Equal treatment to all Bidders / Contractors:
1 POWERGRID will enter into agreements with identical conditions as this one with all Bidders.
2 POWERGRID will disqualify, from the tender process, any bidder/ take punitive actions on the bidder, who does not sign this Pact or violate its provisions.
Section IV – Pact Duration:
This Pact begins when both parties have legally signed it. It expires for the successful Bidder / Contractor after closure of the contract and, for all other Bidders, after the contract has been awarded.
Section V – Other Provisions:
1 This agreement is subject to Indian Law. Place of performance and jurisdiction is the establishment of POWERGRID. The Arbitration/Conciliation clause provided in the main tender document / contract shall not be applicable for any issue / dispute arising under the Safety Pact.
2 Changes and supplements need to be made in writing, which shall come into force only upon mutual agreement / acceptance.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Safety Pact Page 4 of 5
3 If the Contractor is a partnership firm or consortium of Joint Venture, this agreement must be signed by all partners, consortium members and Joint Venue partners, as applicable as per the Tender Specifications.
4 Nothing in this agreement shall affect the rights of the parties available under General Conditions of Contract (GCC) and Special Conditions of Contract (SCC).
5 Should one or several provisions of this agreement turn out to be invalid, the reminder of this agreement remains valid. In this case, the parties will strive to come to an agreement to their original intentions.
Signature Signature
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
(Office Seal) (Office Seal)
Designation : Designation :
Witness 1 : Witness 1 :
Name & Address: Name & Address:
Witness 2 : Witness 2 :
Name & Address: Name & Address:
Safety Pact Page 5 of 5
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-19
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
Further, we hereby confirm that except as mentioned in the Attachment – 6 (Alternative, Deviations and Exceptions to the Provisions) hereof, forming part of our First Envelope :
(i) there are no discrepancies/inconsistencies and deviations/omissions/ reservations to the Bidding Documents, in the Second Envelope bid;
We also confirm that in case any discrepancies/ inconsistencies and deviations/ omissions/ reservations, as referred to in para (i) and (ii) above, is observed in the Second Envelope, the same shall be deemed as withdrawn/rectified without any financial implication, whatsoever to POWERGRID. However, in case of any arithmetical errors, the same shall be governed as per the provision of ITB Sub-Clause 27.2 read in conjunction with BDS
Date 0-Jan-1900 Printed Name 0
Place 0 Designation 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-23-A
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
Declaration by the Bidder in line with Annexure-A (BDS) regarding already having manufacturing & testing facilities for 400kV or above voltage level GIS in India as on the originally scheduled date of bid opening.
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We hereby confirm that we have already incorporated Subsidiary Company */Group Company * /Joint Venture Company * as per Companies Act of India, in line with GCC clause 5.1 to manufacture 400KV or above voltage level GIS in India as on the originally scheduled date of bid opening mentioned in Annexure-A (BDS).
We further confirm that the said Subsidiary Company */Group Company * /Joint Venture Company * has manufacturing & testing facilities for 400kV or above voltage level GIS in India as on the originally scheduled date of bid opening mentioned in Annexure-A (BDS).
Further, we are furnishing the requisite document in support of the above which are attached herewith.
* Stike out which ever is not applicable
Date 0-Jan-1900 Printed Name 0
Place 0 Designation 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-23-B
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
Declaration by the Bidder in line with Annexure-A (BDS) regarding commencement of construction activities for establishment of 400kV or above voltage level GIS manufacturing and testing facilities in India as on the originally scheduled date of bid opening.
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We hereby confirm that we have already incorporated Subsidiary Company */Group Company * /Joint Venture Company * as per Companies Act of India, in line with GCC clause 5.1 to manufacture 400KV or above voltage level GIS in India and have commenced the Construction activities for establishment of manufacturing & testing facilities for 400kV or above voltage level GIS in India as on the originally scheduled date of bid opening mentioned in Annexure-A (BDS)
Regarding incorporation of Subsidiary Company */Group Company * /Joint Venture Company * in India and Commencement of Construction activities, we here by declare as under :
a) Our Subsidiary Company */Group Company * /Joint Venture Company * has been incorporated on ___________________ as per Companies Act of India (Documentary Evidence is Attached herewith).
b) Land is in legal and physical possession (Documentary evidence is attached herewith)
c) All Building designs, ordering of civil works have been completed and civil work at site have commenced (Documentary evidence is attached herewith)
d) Purchase order for major long delivery testing equipment have been placed with delivery and commissioning schedule (Documentary evidence is attached herewith)
e) Action plan for availability of trained manpower to take up manufacturing and testing of GIS module is attached herewith.
* Stike out which ever is not applicable
Date 0-Jan-1900 Printed Name 0
Place 0 Designation 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] Attachment-23
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Compliance to the process related to the e-RA Terms & Conditions and the Business Rules governing the e-RA)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Name : 0 "Saudamini", Plot No. 2, Sector 29
Address : 0 Gurgaon (Haryana) - 122001
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] Attachment-26
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Undertaking by the bidder regarding Compliance of DMI&SP policy)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Name : 0 "Saudamini", Plot No. 2, Sector 29
Address : 0 Gurgaon (Haryana) - 122001
1.0 We have read and understood the provisions of “Policy for providing preference to Domestically Manufactured Iron & Steel Products in Government Procurement” (hereinafter “DMI&SP policy”) issued by Ministry of Steel, Government of India vide Notification dated 8th May 2017 and its revision dated 29th May 2019 and including subsequent amendments/ modifications, if any. 2.0 We undertake that we shall comply with the requirement of DMI&SP policy including its subsequent amendments issued from time to time. Further, we undertake that in case of award on us, the requisite Affidavit of self-certification regarding Domestic Value Addition and/or Authorization certificate from the domestic manufacturer/ supplier of iron and steel products (whose HS codes are falling in Appendix-A of the DMI&SP policy as revised from time to time) included in the BoQ/ scope of the package shall be submitted by us to Employer before supply of the said iron and steel products required under the contract.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] Attachment-28
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
Certification by the Bidder per order no. F.No.6/18/2019-PPD dated 23/07/2020 issued by Public Procurement Division, Department of Expenditure, Ministry of Finance, Government of India (DoE Order) in line with ITB 2.1
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Name : 0 "Saudamini", Plot No. 2, Sector 29
Address : 0 Gurgaon (Haryana) - 122001
We have read and understood the provisions of Order no. F.No.6/18/2019-PPD (Order Public Procurement no.1) dated 23/07/2020 regarding “Restriction under Rule 144(xi) of General Financial Rules” and F.No.6/18/2019-PPD (Order Public Procurement no.2) dated 23/07/2020 regarding “Exclusions from Restriction under Rule 144(xi) of General Financial Rules” issued by Public Procurement Division, Department of Expenditure, Ministry of Finance, Government of India [hereinafter collectively “DoE Order’’] and any subsequent modifications/Amendments, if any. Particularly, we, the Bidder, have read the clause regarding restrictions on procurement from a ‘Bidder of a country which shares a land border with India’ and on sub-contracting to contractors from such countries. We certify that we, the bidder is/are not from such a country or, if from such a country, has been registered as per provisions of the Bidding Documents with the Competent Authority and will not subcontract any work to a subcontractor/sub vendor from such countries unless such subcontractor/sub vendor fulfils all requirement in this regard and is eligible to be considered. [Where applicable, evidence of valid registration by the Competent Authority shall be attached.] We further declare that any misrepresentation or submission of false/forged document/information in this regard shall be dealt with as per the provisions of Integrity Pact and/or Bidding Documents and/or POWERGRID’s policy and procedures.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] Attachment-30
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
Undertaking regarding submission of original/Hard copy part of the bid
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Name : 0 "Saudamini", Plot No. 2, Sector 29
Address : 0 Gurgaon (Haryana) - 122001
1.0 We have read the provisions of the bidding documents regarding submission of original/ Hard copy part of the bid. Accordingly, as per ITB Clause 9(I) of the Bidding Documents, we hereby confirm the following: (i) We have uploaded the scanned copy of the requisite documents in accordance with the bidding provisions along with the soft part of the bid. (ii) We shall furnish all the original/Hard copy part of the bid in physical form on receipt of request from the Employer. Further, there shall be no contradictions/ inconsistencies between the documents submitted in physical form and the scanned version submitted along with the soft part of the bid except for requirement like execution on Stamp paper/ attestation/ notarization as per provisions of the bidding documents. 2.0 We also accept that in case of our failure of submission of documents in original/hard part, the same shall be considered as withdrawal of bids and Employer has the right to take punitive measures against us as deemed fit.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Note: The Bidder (Lead Partner in case of Joint Venture) shall submit the undertaking on the company’s letterhead].
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-31
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Declaration by the bidder for ‘Code of Integrity for Public procurement’)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
Dear Sirs, 1. We have read the provisions of the bidding documents regarding abiding by the ‘Code of Integrity for Public Procurement’. Accordingly, we hereby declare that we shall abide by the ‘Code of Integrity for Public Procurement’ as mentioned under ITB Clause 36 of the Bidding Documents. The details of any previous transgressions of the code of integrity with any entity in any country during the last three years or of being debarred by any other Procuring Entity are as under:
2. We also accept that in case of violation/transgression of this code by us in competing for or in executing the Contract, Employer has the right to take punitive measures as per the provisions of the Bidding Documents and/or POWERGRID’s policy and procedure.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] ATTACHMENT-32
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS.
(Declaration for Acknowledgement and Acceptance of Supplier Code of Conduct)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
Dear Sirs, 1.0 We hereby confirm that we have gone through the POWERGRID Supplier Code of Conduct, attached as Appendix-III to the Special Conditions of Contract and commit to comply with the same in letter and spirit, if awarded value for the subject package will be Rs. 250 Crore or above.
2.0 Upon the occurrence of any breach to the terms and conditions of POWERGRID Supplier Code of Conduct, we shall take all corrective actions in timely manner. Further, we also understand that in case of our failure to comply with this Code, then POWERGRID may take actions against us as per its extant Policies and Procedures including suspension or termination as POWERGRID’s supplier.
3.0 We also hereby confirm that in case we are awarded the subject package with an award value of Rs. 250 Crore or above, we shall submit a signed copy of ‘Supplier Code of Conduct’ within 30 days of the issuance of NOA.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
Before filling up the Bid Form, the Bidder is required to fill up the details as under :
1 Tick whichever is applicable:
1 Enter Details of Amendments:
Amendments to Bidding Documents issued:
6* In case the Bidder is MSE, then insert the Designated Authority under GoI with which they are Registered: ghtg
* applicable for MSE only
[Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] Bid Form (First Envelope) 1 st 1 January 1 one
2 nd 2 February 2 two
BID FORM (First Envelope) 3 rd 3 March 3 three
4 th 4 April 4 four
Bid Proposal Ref. No.: 5 th 5 May 5 five
Date : 00-Jan-00 7 th 0 6 June 7 seven
8 th 1 7 July 8 eight
To: 9 th January 8 August 9 nine
Contract Services 10 th 1900 9 September 10 ten
Power Grid Corporation of India Ltd., 11 th 10 October 11 eleven
"Saudamini", Plot No. 2, Sector 29 12 th 11 November 12 twelve
Gurgaon (Haryana) - 122001 13 th 12 December 13 thirteen
14 th Zero 14 fourteen
15 th () 15 fifteen
Name of Contract : 400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS. [Specification No.: CC/NT/W-GIS/DOM/A10/25/06459] the receipt of which is hereby acknowledged, we the undersigned, offer to design, manufacture, test, deliver, install and commission (including carrying out Trial Operation, Performance & Guarantee Test as per provision of Technical Specification) the Facilities under the above-named package in full conformity with the said Bidding Documents. In accordance with ITB Clause 9.1 of the Bidding Documents, as per which the bid shall be submitted by the bidder under “Single Stage - Two Envelope” procedure of bidding. Accordingly, we hereby submit our Bid, in two envelopes i.e. First Envelope – Techno – Commercial Part & Second Envelope - Price Part (to be opened subsequently).0 16 th 16 sixteen
Dear Ladies and/or Gentlemen, 17 th 17 seventeen
1.0 Having examined the Bidding Documents, including Amendment Nos. dated 00/01/1900, the receipt of which is hereby acknowledged, we the undersigned, offer to design, manufacture, test, deliver, install and commission (including carrying out Trial Operation, Performance & Guarantee Test as per provision of Technical Specification) the Facilities under the above-named package in full conformity with the said Bidding Documents. In accordance with ITB Clause 9.1 of the Bidding Documents, as per which the bid shall be submitted by the bidder under “Single Stage - Two Envelope” procedure of bidding. Accordingly, we hereby submit our Bid, in two envelopes i.e. First Envelope – Techno – Commercial Part & Second Envelope - Price Part (to be opened subsequently). the receipt of which is hereby acknowledged, we the undersigned, offer to design, manufacture, test, deliver, install and commission (including carrying out Trial Operation, Performance & Guarantee Test as per provision of Technical Specification) the Facilities under the above-named package in full conformity with the said Bidding Documents. In accordance with ITB Clause 9.1 of the Bidding Documents, as per which the bid shall be submitted by the bidder under “Single Stage - Two Envelope” procedure of bidding. Accordingly, we hereby submit our Bid, in two envelopes i.e. First Envelope – Techno – Commercial Part & Second Envelope - Price Part (to be opened subsequently). 0 18 th 18 eighteen
1.1 We meet the eligibility requirements and have no conflict of interest in accordance with ITB Clause 2 19 th 19 nineteen
2.0 Attachments to the Bid Form (First Envelope) 20 th 20 twenty
2.1 In line with the requirement of the Bidding Documents, we enclose herewith the following Attachments to the Bid Form : 21 st
(a) Attachment 1: NOT APPLICABLE Bank Draft 22 th
Banks certified Cheque
(b) Attachment 2: Attachment 2: A power of attorney duly authorized by a Notary Public indicating that the person(s) signing the bid have the authority to sign the bid and thus that the bid is binding upon us during the full period of its validity in accordance with the ITB Clause 14. *Further the requisite deed of Joint Undertaking as per stipulated qualification requirement in Annexure-A (BDS) has also been furnished as per your format. * Delete if not applicable A power of attorney duly authorized by a Notary Public indicating that the person(s) signing the bid have the authority to sign the bid and thus that the bid is binding upon us during the full period of its validity in accordance with the ITB Clause 14. Bank Guarantee 23 th
(c) Attachment 3: The documentary evidence that we are eligible to bid in accordance with ITB Clause 2. Further, in terms of ITB Clause 9.3(c) & (e), the qualification data has been furnished as per your format enclosed with the bidding documents [Attachment – 3(QR)]. 24 th
* Further, the required deed of Joint Venture Agreement signed by us and our Partners has also been furnished as per your format [Attachment – 3(JV)].
(d) Attachment 4: The documentary evidence establishing in accordance with ITB Clause 3, Vol.-I of the Bidding Documents that the facility offered by us are eligible facilities and conform to the Bidding Documents has been furnished as Attachment 4 . Moreover, a list of Special Tools & Tackles to be furnished by us, the cost of which is included in our Bid Price, is also enclosed as per your format as Attachment- 4A. 25 th
(e) Attachment 5: The details of all major items of services or supply which we propose subletting in case of award, giving details of the name and nationality of the proposed subcontractor/sub-vendor for each item. 26 th
(f) Attachment 5A: (Items, Components, Raw Material, Services proposed to be sourced from Micro and Small Enterprises): The details of the items, components, raw material, services which is proposed to bought/availed from Micro and Small Enterprises for the purpose of completion of works
(g) Attachment 6: The variation and deviations from the requirements of the Conditions of Contract, Bid Data Sheet and other commercial conditions, Technical Specification and Drawings (excluding critical provisions as mentioned at clause 6.0 below) in your format enclosed with the Bidding Documents, including, inter-alia, the cost of withdrawal of the variations and deviations indicated therein. 27 th
(h) Attachment 7: The details of Alternative Bids made by us indicating the complete Technical Specifications and the deviation to contractual and commercial conditions. [NOT APPLICABLE] 28 th
(i) Attachment 8: Manufacturer’s Authorisation Forms 29 th
(j) Attachment 9: Work Completion Schedule
(k) Attachment 10: Guarantee Declaration
(l) Attachment 11: Information regarding ex-employees of Employer in our firm
(m) Attachment 12: Filled up information regarding Price Adjustment Data as per the format enclosed in the bidding documents
(n) Attachment 13: Declaration regarding Social Accountability
(o) Attachment 14: Integrity Pact, in a separate envelope, duly signed on each page by the person signing the bid.
(p) Attachment 15: Option for Initial Advance (either Interest Bearing Initial Advance or No Initial Advance) and Information for E – payment, PF details and declaration for Micro/Small and Medium Enterprise
(q) Attachment 16: Additional information
(r) Attachment 17: Declaration for tax exemptions, reductions, allowances or benefits
(s) Attachment 18: Safety Pact
(t) Attachment 19: Declaration
(u) Attachment 20: Declaration of Key Managerial Person jointly with Power of Attorney holder is attached herewith
(v) Attachment 21: Affidavit of Self certification regarding Minimum Local Content in line with PPP-MII Order and MoP Order, if applicable
(w) Attachment 22: Certificate from statutory auditor or cost auditor of the company (in the case of companies) or from a practicing cost accountant or practicing chartered accountant (in respect of suppliers other than companies) giving the percentage of Local Content, in line with PPP-MII Order and MoP Order, if applicable
(x) Attachment 23: Compliance to the process related to the e-RA Terms & Conditions and the Business Rules governing the e-RA
(y) Attachment 24: Confirmation in regard to Design and Type Test (to be furnished in case bidder is proposing to qualify through Note-4 under Route-1 of QR)
(z) Attachment 25: Declaration by the Bidder regarding events encountered pursuant to ITB Clause 2.1
(aa) Attachment 26: Undertaking by the bidder regarding Compliance of DMI&SP policy
(bb) Attachment 27: VOID
(cc) Attachment 28: Certification by the Bidder as per DoE Order in line with ITB Clause 2.1 (In case of a Joint Venture bid, the declaration shall be given by all partners of the Joint Venture)
(dd) Attachment 29: Bid Securing Declaration to be submitted by the Bidder
(ee) Attachment 30: Undertaking regarding submission of original/Hard copy part of the bid
(ff) Attachment 31: Declaration by the bidder for ‘Code of Integrity for Public procurement
(gg) Attachment 32: Declaration by the bidder for Acknowledgement and Acceptance of ‘Supplier Code of Conduct’
3.0 We are aware that, in line with Clause No. 27.1 (ITB), our Second Envelope (Price Part) is liable to be rejected in case the same contains any deviation/omission from the contractual and commercial conditions and technical Specifications other than those identified in this First Envelope.
4.0 We confirm that except as otherwise specifically provided our Bid Prices in Second Envelope include all taxes, duties, levies and charges as may be assessed on us, our Sub-Contractor/Sub-Vendor or their employees by all municipal, state or national government authorities in connection with the Facilities, in and outside of India.
4.1 100% of applicable Taxes and Duties i.e. GST which are payable by the Employer under the Contract, shall be reimbursed by the Employer on production of satisfactory documentary evidence by the Contractor in accordance with the provisions of the Bidding Documents.
5.0 Construction of the Contract
, whose capacity, capability and experience are enclosed with our Bid as our Associate(s) for the purpose of executing the ‘Second Contract’ and / or the ‘Third Contract’ and written unequivocal consent of the above mentioned proposed Associate(s) to work as your independent Contractor, on the same terms and conditions as offered by us to you in this bid, is also enclosed with the Bid Form. We shall, however, be overall responsible for the execution of all the three Contracts.
5.1 We declare that we have studied Clause GCC 2.1 relating to mode of contracting for Domestic Bidders and we are making this proposal with a stipulation that you shall award us two separate Contracts viz ‘First Contract’ for ex-works supply of all equipment and materials including mandatory spares and ‘Second Contract’ for providing all the services i.e. inland transportation for delivery at site, In-transit insurance, unloading, handling at site, installation, testing and commissioning including Trial operation in respect of all the equipment supplied under the ‘First Contract’ and other services specified in the Contract Documents. We declare that the award of two contracts, will not, in any way, dilute our responsibility for successful operation of plant/equipment and fulfillment of all obligations as per Bidding Documents and that both the Contracts will have a cross-fall breach clause i.e. a breach in one Contract will automatically be classified as a breach of the other contract which will confer on you the right to terminate the other contract at our risk and cost.
6.0 We have read the provisions of following clauses and confirm that the specified stipulations of these clauses are acceptable to us:
(a) ITB 13 Bid Security-Not Applicable
(b) GCC 2.14 Governing Law
(c) GCC 5.1 Contractor’s Responsibilities
(d) GCC 8 Terms of Payment
(e) GCC 9.3 Performance Security
(f) GCC 10 Taxes and Duties
(g) GCC 21.2 Completion Time Guarantee
(h) GCC 22 Defect Liability
(i) GCC 23 Functional Guarantee
(j) GCC 25 Patent Indemnity
(k) GCC 26 Limitation of Liability
(l) GCC 38 Settlement of Disputes
(m) GCC 39 Arbitration
(n) GCC 40 Conciliation
(o) Appendix 2 to Form of Contract Agreement Price Adjustment
Further we understand that deviation taken in any of the above clauses by us shall make our bid non-responsive as per provision of bidding documents and rejected by you.
7.0 We undertake, if our bid is accepted, to commence the work on Facilities immediately upon your Notification of Award to us, and to achieve Completion within the time stated in the Bidding Documents.
8.0 If our bid is accepted, we undertake to provide an Advance Payment Security and Performance Security(ies) in the form and amounts, and within the times specified in the Bidding Documents.
9.0 We agree to abide by this bid for a period of Six (06) months after the date of opening of Techno - Commercial Part i.e. First Envelope as stipulated in the Bidding Documents, and it shall remain binding upon us and may be accepted by you at any time before the expiration of that period.
10.0 Until a formal Contract is prepared and executed between us, this bid, together with your written acceptance thereof in the form of your Notification of Award shall constitute a binding contract between us.
11.0 We understand that you are not bound to accept the lowest or any bid you may receive.
*12.0 (for Joint Venture only) We, the partners of Joint Venture submitting this bid, do agree and confirm that in case of Award of Contract on the Joint Venture, we shall be jointly and severally liable and responsible for the execution of the Contract in accordance with Contract terms and conditions. 1
13.0 We are a Micro and Small Enterprise (MSE) registered with , a designated Authority of GoI under the Public Procurement Policy for MSEs order 2012 Notification dated 01/06/2020 ,26/06/2020 and 19/01/2022 read in conjunction with related notifications issued from time to time for such enterprises. 0 2 2
13.0 We, hereby, declare that only the persons or firms interested in this proposal as principals are named here and that no other persons or firms other than those mentioned herein have any interest in this proposal or in the Contract to be entered into, if the award is made on us, that this proposal is made without any connection with any other person, firm or party likewise submitting a proposal is in all respects for and in good faith, without collusion or fraud.
Thanking you, we remain
Yours faithfully,
For and on behalf of : 0
Date : 00 January 1900 Printed Name: 0
Place : 00-Jan-00 Designation : 0
Please provide additional information of the Bidder
Business Address :
Country of Incorporation :
(State/Province to be indicated)
Name of Principal Officer :
Address of Principal Officer :
USD One Lac Fifty Five Thousand Eight Hundred Eighty Five Only EURO Four Thousand Nine Hundred Sixty Only RMB Ten Thousand Three Hundred Fifty Two Only INR Six Lac Ninety One Thousand Six Hundred Forty Seven Only USD 155885/- + EURO 4960/- + RMB 10352/- + INR 691647/-
USD One Lac Fifty Five Thousand Eight Hundred Eighty Five Only plus EURO Four Thousand Nine Hundred Sixty Only plus RMB Ten Thousand Three Hundred Fifty Two Only plus INR Six Lac Ninety One Thousand Six Hundred Forty Seven Only
85 Eighty Five 60 Sixty 52 Fifty Two 47 Forty Seven
8 Eight Hundred 9 Nine Hundred 3 Three Hundred 6 Six Hundred
55 Fifty Five Thousand 4 Four Thousand 10 Ten Thousand 91 Ninety One Thousand 0 0 0 0 0 plus
1 One Lac 0 0 6 Six Lac 0 0 0 0 1
1 One 1 One 1 One 1 One 0 0 1 0 1
2 Two 2 Two 2 Two 2 Two 0 0 1 1 0
3 Three 3 Three 3 Three 3 Three 0 0 1 1 1
4 Four 4 Four 4 Four 4 Four 0 1 0 0 0
5 Five 5 Five 5 Five 5 Five 0 1 0 0 1
6 Six 6 Six 6 Six 6 Six 0 1 0 1 0
7 Seven 7 Seven 7 Seven 7 Seven 0 1 0 1 1
8 Eight 8 Eight 8 Eight 8 Eight 0 1 1 0 0
9 Nine 9 Nine 9 Nine 9 Nine 0 1 1 0 1
10 Ten 10 Ten 10 Ten 10 Ten 0 1 1 1 0
11 Eleven 11 Eleven 11 Eleven 11 Eleven 1 1 1 1 1 USD One Lac Fifty Five Thousand Eight Hundred Eighty Five Only plus EURO Four Thousand Nine Hundred Sixty Only plus RMB Ten Thousand Three Hundred Fifty Two Only plus INR Six Lac Ninety One Thousand Six Hundred Forty Seven Only
12 Twelve 12 Twelve 12 Twelve 12 Twelve
13 Thirteen 13 Thirteen 13 Thirteen 13 Thirteen
14 Fourteen 14 Fourteen 14 Fourteen 14 Fourteen
15 Fifteen 15 Fifteen 15 Fifteen 15 Fifteen
16 Sixteen 16 Sixteen 16 Sixteen 16 Sixteen 0 0 0 0 0 +
17 Seventeen 17 Seventeen 17 Seventeen 17 Seventeen 0 0 0 0 1 /- +
18 Eighteen 18 Eighteen 18 Eighteen 18 Eighteen 0 0 0 1 0 /-
19 Nineteen 19 Nineteen 19 Nineteen 19 Nineteen 0 0 0 1 1
20 Twenty 20 Twenty 20 Twenty 20 Twenty 0 0 1 0 0
21 Twenty One 21 Twenty One 21 Twenty One 21 Twenty One 0 0 1 0 1
22 Twenty Two 22 Twenty Two 22 Twenty Two 22 Twenty Two 0 0 1 1 0
23 Twenty Three 23 Twenty Three 23 Twenty Three 23 Twenty Three 0 0 1 1 1
24 Twenty Four 24 Twenty Four 24 Twenty Four 24 Twenty Four 0 1 0 0 0
25 Twenty Five 25 Twenty Five 25 Twenty Five 25 Twenty Five 0 1 0 0 1
26 Twenty Six 26 Twenty Six 26 Twenty Six 26 Twenty Six 0 1 0 1 0
27 Twenty Seven 27 Twenty Seven 27 Twenty Seven 27 Twenty Seven 0 1 0 1 1
28 Twenty Eight 28 Twenty Eight 28 Twenty Eight 28 Twenty Eight 0 1 1 0 0
29 Twenty Nine 29 Twenty Nine 29 Twenty Nine 29 Twenty Nine 0 1 1 0 1
30 Thirty 30 Thirty 30 Thirty 30 Thirty 0 1 1 1 0
31 Thirty One 31 Thirty One 31 Thirty One 31 Thirty One 1 1 1 1 1 USD 155885/- + EURO 4960/- + RMB 10352/- + INR 691647/-
32 Thirty Two 32 Thirty Two 32 Thirty Two 32 Thirty Two
33 Thirty Three 33 Thirty Three 33 Thirty Three 33 Thirty Three
34 Thirty Four 34 Thirty Four 34 Thirty Four 34 Thirty Four
35 Thirty Fivr 35 Thirty Fivr 35 Thirty Fivr 35 Thirty Fivr
36 Thirty Six 36 Thirty Six 36 Thirty Six 36 Thirty Six
37 Thirty Seven 37 Thirty Seven 37 Thirty Seven 37 Thirty Seven
38 Thirty Eight 38 Thirty Eight 38 Thirty Eight 38 Thirty Eight
39 Thirty Nine 39 Thirty Nine 39 Thirty Nine 39 Thirty Nine
40 Forty 40 Forty 40 Forty 40 Forty
41 Forty One 41 Forty One 41 Forty One 41 Forty One
42 Forty Two 42 Forty Two 42 Forty Two 42 Forty Two
43 Forty Three 43 Forty Three 43 Forty Three 43 Forty Three
44 Forty Four 44 Forty Four 44 Forty Four 44 Forty Four
45 Forty Five 45 Forty Five 45 Forty Five 45 Forty Five
46 Forty Six 46 Forty Six 46 Forty Six 46 Forty Six
47 Forty Seven 47 Forty Seven 47 Forty Seven 47 Forty Seven
48 Forty Eight 48 Forty Eight 48 Forty Eight 48 Forty Eight
49 Forty Nine 49 Forty Nine 49 Forty Nine 49 Forty Nine
50 Fifty 50 Fifty 50 Fifty 50 Fifty
51 Fifty One 51 Fifty One 51 Fifty One 51 Fifty One
52 Fifty Two 52 Fifty Two 52 Fifty Two 52 Fifty Two
53 Fifty Three 53 Fifty Three 53 Fifty Three 53 Fifty Three
54 Fifty Four 54 Fifty Four 54 Fifty Four 54 Fifty Four
55 Fifty Five 55 Fifty Five 55 Fifty Five 55 Fifty Five
56 Fifty Six 56 Fifty Six 56 Fifty Six 56 Fifty Six
57 Fifty Seven 57 Fifty Seven 57 Fifty Seven 57 Fifty Seven
58 Fifty Eight 58 Fifty Eight 58 Fifty Eight 58 Fifty Eight
59 Fifty Nine 59 Fifty Nine 59 Fifty Nine 59 Fifty Nine
60 Sixty 60 Sixty 60 Sixty 60 Sixty
61 Sixty One 61 Sixty One 61 Sixty One 61 Sixty One
62 Sixty Two 62 Sixty Two 62 Sixty Two 62 Sixty Two
63 Sixty Three 63 Sixty Three 63 Sixty Three 63 Sixty Three
64 Sixty Four 64 Sixty Four 64 Sixty Four 64 Sixty Four
65 Sixty Five 65 Sixty Five 65 Sixty Five 65 Sixty Five
66 Sixty Six 66 Sixty Six 66 Sixty Six 66 Sixty Six
67 Sixty Seven 67 Sixty Seven 67 Sixty Seven 67 Sixty Seven
68 Sixty Eight 68 Sixty Eight 68 Sixty Eight 68 Sixty Eight
69 Sixty Nine 69 Sixty Nine 69 Sixty Nine 69 Sixty Nine
70 Seventy 70 Seventy 70 Seventy 70 Seventy
71 Seventy One 71 Seventy One 71 Seventy One 71 Seventy One
72 Seventy Two 72 Seventy Two 72 Seventy Two 72 Seventy Two
73 Seventy Three 73 Seventy Three 73 Seventy Three 73 Seventy Three
74 Seventy Four 74 Seventy Four 74 Seventy Four 74 Seventy Four
75 Seventy Five 75 Seventy Five 75 Seventy Five 75 Seventy Five
76 Seventy Six 76 Seventy Six 76 Seventy Six 76 Seventy Six
77 Seventy Seven 77 Seventy Seven 77 Seventy Seven 77 Seventy Seven
78 Seventy Eight 78 Seventy Eight 78 Seventy Eight 78 Seventy Eight
79 Seventy Nine 79 Seventy Nine 79 Seventy Nine 79 Seventy Nine
80 Eighty 80 Eighty 80 Eighty 80 Eighty
81 Eighty One 81 Eighty One 81 Eighty One 81 Eighty One
82 Eighty Two 82 Eighty Two 82 Eighty Two 82 Eighty Two
83 Eighty Three 83 Eighty Three 83 Eighty Three 83 Eighty Three
84 Eighty Four 84 Eighty Four 84 Eighty Four 84 Eighty Four
85 Eighty Five 85 Eighty Five 85 Eighty Five 85 Eighty Five
86 Eighty Six 86 Eighty Six 86 Eighty Six 86 Eighty Six
87 Eighty Seven 87 Eighty Seven 87 Eighty Seven 87 Eighty Seven
88 Eighty Eight 88 Eighty Eight 88 Eighty Eight 88 Eighty Eight
89 Eighty Nine 89 Eighty Nine 89 Eighty Nine 89 Eighty Nine
90 Ninety 90 Ninety 90 Ninety 90 Ninety
91 Ninety One 91 Ninety One 91 Ninety One 91 Ninety One
92 Ninety Two 92 Ninety Two 92 Ninety Two 92 Ninety Two
93 Ninety Three 93 Ninety Three 93 Ninety Three 93 Ninety Three
94 Ninety Four 94 Ninety Four 94 Ninety Four 94 Ninety Four
95 Ninety Five 95 Ninety Five 95 Ninety Five 95 Ninety Five
96 Ninety Six 96 Ninety Six 96 Ninety Six 96 Ninety Six
97 Ninety Seven 97 Ninety Seven 97 Ninety Seven 97 Ninety Seven
98 Ninety Eight 98 Ninety Eight 98 Ninety Eight 98 Ninety Eight
99 Ninety Nine 99 Ninety Nine 99 Ninety Nine 99 Ninety Nine
100 One Hundred 100 One Hundred 100 One Hundred 100 One Hundred
23 Twenty Three
27 Twenty Seven
28 Twenty Eight
33 Thirty Three
37 Thirty Seven
38 Thirty Eight
73 Seventy Three
74 Seventy Four
75 Seventy Five
77 Seventy Seven
78 Seventy Eight
79 Seventy Nine
83 Eighty Three
87 Eighty Seven
88 Eighty Eight
93 Ninety Three
97 Ninety Seven
98 Ninety Eight
100 One Hundred
USD One Lac Fifty Five Thousand Eight Hundred Eighty Five Only EURO Four Thousand Nine Hundred Sixty Only RMB Ten Thousand Three Hundred Fifty Two Only INR Six Lac Ninety One Thousand Six Hundred Forty Seven Only USD 155885/- + EURO 4960/- + RMB 10352/- + INR 691647/-
USD One Lac Fifty Five Thousand Eight Hundred Eighty Five Only plus EURO Four Thousand Nine Hundred Sixty Only plus RMB Ten Thousand Three Hundred Fifty Two Only plus INR Six Lac Ninety One Thousand Six Hundred Forty Seven Only
85 Eighty Five 60 Sixty 52 Fifty Two 47 Forty Seven
8 Eight Hundred 9 Nine Hundred 3 Three Hundred 6 Six Hundred
55 Fifty Five Thousand 4 Four Thousand 10 Ten Thousand 91 Ninety One Thousand 0 0 0 0 0 plus
1 One Lac 0 0 6 Six Lac 0 0 0 0 1
1 One 1 One 1 One 1 One 0 0 1 0 1
2 Two 2 Two 2 Two 2 Two 0 0 1 1 0
3 Three 3 Three 3 Three 3 Three 0 0 1 1 1
4 Four 4 Four 4 Four 4 Four 0 1 0 0 0
5 Five 5 Five 5 Five 5 Five 0 1 0 0 1
6 Six 6 Six 6 Six 6 Six 0 1 0 1 0
7 Seven 7 Seven 7 Seven 7 Seven 0 1 0 1 1
8 Eight 8 Eight 8 Eight 8 Eight 0 1 1 0 0
9 Nine 9 Nine 9 Nine 9 Nine 0 1 1 0 1
10 Ten 10 Ten 10 Ten 10 Ten 0 1 1 1 0
11 Eleven 11 Eleven 11 Eleven 11 Eleven 1 1 1 1 1 USD One Lac Fifty Five Thousand Eight Hundred Eighty Five Only plus EURO Four Thousand Nine Hundred Sixty Only plus RMB Ten Thousand Three Hundred Fifty Two Only plus INR Six Lac Ninety One Thousand Six Hundred Forty Seven Only
12 Twelve 12 Twelve 12 Twelve 12 Twelve
13 Thirteen 13 Thirteen 13 Thirteen 13 Thirteen
14 Fourteen 14 Fourteen 14 Fourteen 14 Fourteen
15 Fifteen 15 Fifteen 15 Fifteen 15 Fifteen
16 Sixteen 16 Sixteen 16 Sixteen 16 Sixteen 0 0 0 0 0 +
17 Seventeen 17 Seventeen 17 Seventeen 17 Seventeen 0 0 0 0 1 /- +
18 Eighteen 18 Eighteen 18 Eighteen 18 Eighteen 0 0 0 1 0 /-
19 Nineteen 19 Nineteen 19 Nineteen 19 Nineteen 0 0 0 1 1
20 Twenty 20 Twenty 20 Twenty 20 Twenty 0 0 1 0 0
21 Twenty One 21 Twenty One 21 Twenty One 21 Twenty One 0 0 1 0 1
22 Twenty Two 22 Twenty Two 22 Twenty Two 22 Twenty Two 0 0 1 1 0
23 Twenty Three 23 Twenty Three 23 Twenty Three 23 Twenty Three 0 0 1 1 1
24 Twenty Four 24 Twenty Four 24 Twenty Four 24 Twenty Four 0 1 0 0 0
25 Twenty Five 25 Twenty Five 25 Twenty Five 25 Twenty Five 0 1 0 0 1
26 Twenty Six 26 Twenty Six 26 Twenty Six 26 Twenty Six 0 1 0 1 0
27 Twenty Seven 27 Twenty Seven 27 Twenty Seven 27 Twenty Seven 0 1 0 1 1
28 Twenty Eight 28 Twenty Eight 28 Twenty Eight 28 Twenty Eight 0 1 1 0 0
29 Twenty Nine 29 Twenty Nine 29 Twenty Nine 29 Twenty Nine 0 1 1 0 1
30 Thirty 30 Thirty 30 Thirty 30 Thirty 0 1 1 1 0
31 Thirty One 31 Thirty One 31 Thirty One 31 Thirty One 1 1 1 1 1 USD 155885/- + EURO 4960/- + RMB 10352/- + INR 691647/-
32 Thirty Two 32 Thirty Two 32 Thirty Two 32 Thirty Two
33 Thirty Three 33 Thirty Three 33 Thirty Three 33 Thirty Three
34 Thirty Four 34 Thirty Four 34 Thirty Four 34 Thirty Four
35 Thirty Fivr 35 Thirty Fivr 35 Thirty Fivr 35 Thirty Fivr
36 Thirty Six 36 Thirty Six 36 Thirty Six 36 Thirty Six
37 Thirty Seven 37 Thirty Seven 37 Thirty Seven 37 Thirty Seven
38 Thirty Eight 38 Thirty Eight 38 Thirty Eight 38 Thirty Eight
39 Thirty Nine 39 Thirty Nine 39 Thirty Nine 39 Thirty Nine
40 Forty 40 Forty 40 Forty 40 Forty
41 Forty One 41 Forty One 41 Forty One 41 Forty One
42 Forty Two 42 Forty Two 42 Forty Two 42 Forty Two
43 Forty Three 43 Forty Three 43 Forty Three 43 Forty Three
44 Forty Four 44 Forty Four 44 Forty Four 44 Forty Four
45 Forty Five 45 Forty Five 45 Forty Five 45 Forty Five
46 Forty Six 46 Forty Six 46 Forty Six 46 Forty Six
47 Forty Seven 47 Forty Seven 47 Forty Seven 47 Forty Seven
48 Forty Eight 48 Forty Eight 48 Forty Eight 48 Forty Eight
49 Forty Nine 49 Forty Nine 49 Forty Nine 49 Forty Nine
50 Fifty 50 Fifty 50 Fifty 50 Fifty
51 Fifty One 51 Fifty One 51 Fifty One 51 Fifty One
52 Fifty Two 52 Fifty Two 52 Fifty Two 52 Fifty Two
53 Fifty Three 53 Fifty Three 53 Fifty Three 53 Fifty Three
54 Fifty Four 54 Fifty Four 54 Fifty Four 54 Fifty Four
55 Fifty Five 55 Fifty Five 55 Fifty Five 55 Fifty Five
56 Fifty Six 56 Fifty Six 56 Fifty Six 56 Fifty Six
57 Fifty Seven 57 Fifty Seven 57 Fifty Seven 57 Fifty Seven
58 Fifty Eight 58 Fifty Eight 58 Fifty Eight 58 Fifty Eight
59 Fifty Nine 59 Fifty Nine 59 Fifty Nine 59 Fifty Nine
60 Sixty 60 Sixty 60 Sixty 60 Sixty
61 Sixty One 61 Sixty One 61 Sixty One 61 Sixty One
62 Sixty Two 62 Sixty Two 62 Sixty Two 62 Sixty Two
63 Sixty Three 63 Sixty Three 63 Sixty Three 63 Sixty Three
64 Sixty Four 64 Sixty Four 64 Sixty Four 64 Sixty Four
65 Sixty Five 65 Sixty Five 65 Sixty Five 65 Sixty Five
66 Sixty Six 66 Sixty Six 66 Sixty Six 66 Sixty Six
67 Sixty Seven 67 Sixty Seven 67 Sixty Seven 67 Sixty Seven
68 Sixty Eight 68 Sixty Eight 68 Sixty Eight 68 Sixty Eight
69 Sixty Nine 69 Sixty Nine 69 Sixty Nine 69 Sixty Nine
70 Seventy 70 Seventy 70 Seventy 70 Seventy
71 Seventy One 71 Seventy One 71 Seventy One 71 Seventy One
72 Seventy Two 72 Seventy Two 72 Seventy Two 72 Seventy Two
73 Seventy Three 73 Seventy Three 73 Seventy Three 73 Seventy Three
74 Seventy Four 74 Seventy Four 74 Seventy Four 74 Seventy Four
75 Seventy Five 75 Seventy Five 75 Seventy Five 75 Seventy Five
76 Seventy Six 76 Seventy Six 76 Seventy Six 76 Seventy Six
77 Seventy Seven 77 Seventy Seven 77 Seventy Seven 77 Seventy Seven
78 Seventy Eight 78 Seventy Eight 78 Seventy Eight 78 Seventy Eight
79 Seventy Nine 79 Seventy Nine 79 Seventy Nine 79 Seventy Nine
80 Eighty 80 Eighty 80 Eighty 80 Eighty
81 Eighty One 81 Eighty One 81 Eighty One 81 Eighty One
82 Eighty Two 82 Eighty Two 82 Eighty Two 82 Eighty Two
83 Eighty Three 83 Eighty Three 83 Eighty Three 83 Eighty Three
84 Eighty Four 84 Eighty Four 84 Eighty Four 84 Eighty Four
85 Eighty Five 85 Eighty Five 85 Eighty Five 85 Eighty Five
86 Eighty Six 86 Eighty Six 86 Eighty Six 86 Eighty Six
87 Eighty Seven 87 Eighty Seven 87 Eighty Seven 87 Eighty Seven
88 Eighty Eight 88 Eighty Eight 88 Eighty Eight 88 Eighty Eight
89 Eighty Nine 89 Eighty Nine 89 Eighty Nine 89 Eighty Nine
90 Ninety 90 Ninety 90 Ninety 90 Ninety
91 Ninety One 91 Ninety One 91 Ninety One 91 Ninety One
92 Ninety Two 92 Ninety Two 92 Ninety Two 92 Ninety Two
93 Ninety Three 93 Ninety Three 93 Ninety Three 93 Ninety Three
94 Ninety Four 94 Ninety Four 94 Ninety Four 94 Ninety Four
95 Ninety Five 95 Ninety Five 95 Ninety Five 95 Ninety Five
96 Ninety Six 96 Ninety Six 96 Ninety Six 96 Ninety Six
97 Ninety Seven 97 Ninety Seven 97 Ninety Seven 97 Ninety Seven
98 Ninety Eight 98 Ninety Eight 98 Ninety Eight 98 Ninety Eight
99 Ninety Nine 99 Ninety Nine 99 Ninety Nine 99 Ninety Nine
100 One Hundred 100 One Hundred 100 One Hundred 100 One Hundred
23 Twenty Three
27 Twenty Seven
28 Twenty Eight
33 Thirty Three
37 Thirty Seven
38 Thirty Eight
73 Seventy Three
74 Seventy Four
75 Seventy Five
77 Seventy Seven
78 Seventy Eight
79 Seventy Nine
83 Eighty Three
87 Eighty Seven
88 Eighty Eight
93 Ninety Three
97 Ninety Seven
98 Ninety Eight
100 One Hundred
Package Name 400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS;
Package Code 400kV GIS Substation Package SS-149
Specification No. Specification No.: CC/NT/W-GIS/DOM/A10/25/06459
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459
1 Fill up only green shaded cells in Sch-1, Sch-2, Sch-3, Sch-4, Sch-7 and Bid Form 2nd Envelope.
2 All the cells in Sch-5 & Sch-6 are auto filled, therefore no cell is required to be filled up there.
3 Instructions / error messages, if any, will be displayed automatically after selecting the cell.
4 After filling up all the schedues, save the file, take print out of all the schedules and Bid form and sign & stamp and submit them as hard copy of the 2nd envelope (Price part) of the bid. Also ensure to submit the soft copy of the the same file on CD/ DVD.
I While filling up the worksheets following may please be observed :
(i) Fill up only green shaded cells.
(ii) Certain data type entries have been restricted, such as Numeric values or limits of numeric values.
(iii) Select only the options provided in pull down menus.
(iv) Do not link any cell of this work book with any other work book.
(v) Do not use copy & paste or cut & paste options for filling up the data.
(vi) Do not reformat any of the cell of the work book.
II This Workbook consists of following worksheets :
Opening page of the workbook.
Names of Bidder :
● Select Sole Bidder or JV (Joint Venture) from the pull down menu. Do not leave this cell blank.
● Select nos. of the JV Partners other than the Lead Partner from drop down menu.
● In case of JV partners more than 2, enter details of 3rd & more partners along with details of 2nd partner.
● Fill up names and address of the Sole Bidder and /or Joint Venture.
● Fill up date in dd-mmm-yyyy format from drop down menu.
● Click for Sch-1 given at the right top of the worksheet to go to Sch-1.
Sch-1 (Ex-works Prices) :
● Fill up unit rates for all the items in numeric values greater than 0 (zero). If unit rate is left blank, the corresponding item shall be deemed to be included in the total price.
● Corresponding cell for mode of transaction shall be come enable only after filling up the unit rate, therefore first fill up the unit rate and then mode of transaction for the corresponding item.
● Select either Direct or Bought-out from the drop down menu. Do not leave the cell blank the same shall be deemed to be Bought-out if the cell is left blank.
● Total amount shall get calculated automatically.
● Type Test charges shall appear automatically after filling up Sch-7 appropriately.
Sch-2 (Freight & Insurance Charges) :
● Fill up unit rates for all the items in numeric values greater than 0 (zero). If unit rate is left blank, the corresponding item shall be deemed to be included in the total price.
● Total amount shall get calculated automatically.
Sch-3 (Installation Charges) :
● Fill up unit rates for all the items in numeric values greater than 0 (zero). If unit rate is left blank, the corresponding item shall be deemed to be included in the total price.
● Total amount shall get calculated automatically.
Sch-4 (Training Charges) :
● Fill up unit rates for all the items in numeric values greater than 0 (zero). If unit rate is left blank, the corresponding item shall be deemed to be included in the total price.
● Total amount shall get calculated automatically.
Sch-4b (Maintenance Charges during and after Defect Liability Period) :
● Not applicable, hence no cell is required to be filled up.
Sch-5 (Summary of Taxes and Duties applicable on the Goods) :
● No cell is required to be filled in by the bidder in this worksheet.
● Summary of all the Schedules without considering discount (mentioned in the work sheet discount) shall be displayed automatically.
● No cell is required to be filled in by the bidder in this worksheet.
Sch-7 (Type Test Charges) :
● Fill up the rates & location where type tests are proposed.
● Total of this Sch-7 shall automatically appear in Sch-1.
Bid from 2nd Envelope :
● Fill up ref. no. as bidder's ref no. of this letter.
● This letter shall consider the net price as per Sch-6 (After Discount).
● Fill up names & Designation of the representatives of other JV partner(s) if the bidder is JV (Joint Venture) .
● Fill up additional information as required.
Happy Bidding !
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS;
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Sole Bidder 1 Sole Bidder 1
Joint Venture 2 or More JV (Joint Venture) 2 or More
Enter following details of the bidder
Specify type of Bidder [Select from drop down menu] 0 2 0 0 2 0
Name of Lead Partner …….. …….. …….. …….. …….. ……..
Address of Sole Bidder …….. …….. …….. …….. …….. ……..
Name of other Partner - 1
Address of other Partner - 1
Name of other Partner - 2 (more, if any) …….. …….. …….. …….. …….. ……..
Address of other Partner - 2 (more, if any) …….. …….. …….. …….. …….. ……..
email ID of Bid Signatory
Mobile No. of Bid Signatory
Tel No. of Bid Signatory
Fax No. of Bid Signatory
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Schedule - 1 Direct Total 0 0 `
BO Total #REF! 0
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS;
(SCHEDULE OF RATES AND PRICES)
Bidder’s Name and Address (Lead Partner) : To:
Contracts Services, 3rd Floor
Name : …….. …….. …….. …….. …….. …….. Power Grid Corporation of India Ltd.,
Address : …….. …….. …….. …….. …….. …….. "Saudamini", Plot No.-2
PLANT AND EQUIPMENT (INCLUDING MANDATORY SPARES PARTS) TO BE SUPPLIED, INCLUDING TYPE TEST CHARGES FOR TESTS TO BE CONDUCTED Direct
All Prices are in Indian Rupees. Bought-Out
SI. No. PR No PR Line Item No Activity Description Material Code HSN Code Whether HSN in column ‘ 6 ’ is confirmed. If not indicate applicable the HSN code * Rate of GST applicable ( in %) Whether rate of GST in column ‘8’ is confirmed. If not indicate applicable rate of GST * Item Description Unit Qty. Unit Ex-works price (excluding GST) Total Ex-works price (excluding GST) GST Tax as confirmed by Bidder
A Augmentation at Bhuj-II PS 400kV ICT 0% Revaluation of J column Tax Calculation
1 7000030922 220 GIS Portion- 420 kV GIS Equipments 1000032802 85359030 18% 420KV, 4000A,63KA GIS BUSBAR MODULE EXTENSION SET 2 Included 0.00 0 0.00
2 7000030922 230 GIS Portion- 420 kV GIS Equipments 1000004637 85359030 18% 420kV, 3150 A, 63 kA, SF6 GIS ICT feederbay module as per Section-Project,Technical specification SET 2 Included 0.00 0 0.00
3 7000030922 320 GIS Portion- 420 kV GIS Equipments 1000065958 85359030 18% EXTENSION OF 420 KV, 3150A, 63KA, SF6 GIS AUXILIARY BUS MODULE FOR SPARETRANSFORMER AS PER SECTION-PROJECT, TECHNICAL SPECIFICATION SET 1 Included 0.00 0 0.00
4 7000030922 240 GIS Portion- 420 kV GIS Equipments 1000004634 85359030 18% 420 kV, 3150 A, 63 kA, SF6 GIS Linefeeder bay module(with PIR) as perSection-Project, Technicalspecification SET 1 Included 0.00 0 0.00
5 7000030922 250 GIS Portion- 420 kV GIS Equipments 1000004635 85359030 18% 420kV, 3150 A, 63 kA, SF6 GIS Tie baymodule(with PIR) as perSection-Project, Technicalspecification SET 1 Included 0.00 0 0.00
6 7000030922 260 GIS Portion- 420 kV GIS Equipments 1000055830 85359030 18% 420KV, 3150 A, 63 KA, SF6 GIS SWITCHABLE LINE REACTOR BAY MODULE ASPER SECTION-PROJECT, TECHNICAL SPECIFICATION SET 1 Included 0.00 0 0.00
7 7000030922 270 GIS Portion- 420 kV GIS Equipments 1000004287 85389000 18% 420kV, 3000A, 63kA, Single phase, SF6Gas Insulated Bus Duct (GIB) outsideGIS Hall alongwith associated supportstructure M 450 Included 0.00 0 0.00
8 7000030922 350 GIS Portion- 420 kV GIS Equipments 1000032796 85389000 18% 420KV, 3150A, 63KA SF6 TO AIR BUSHING including support structure SET 9 Included 0.00 0 0.00
9 7000030922 280 GIS Portion- 420 kV GIS Equipments 1000009713 85389000 18% Controlled Switching Device for 420 kV, 3-ph Circuit Breaker EA 6 Included 0.00 0 0.00
10 7000030922 290 GIS Portion- 420 kV GIS Equipments 1000004505 85359030 18% 420kV, 3150 A, 63 kA, SF6 GIS Tie baymodule(without PIR) as perSection-Project, Technicalspecification SET 1 Included 0.00 0 0.00
11 7000030922 300 GIS Portion- 420 kV GIS Equipments 1000059208 85359030 18% 420KV, 3150 A, 63 KA, SF6 GIS ICT FEEDER BAY MODULE FOR IV SIDECONNECTION WITH 765KV ICT AS PER SECTION-PROJECT, TECHNICALSPECIFICATION SET 1 Included 0.00 0 0.00
12 7000030922 310 GIS Portion- 420 kV GIS Equipments 1000004295 85389000 18% 420kV, 4000A,63kA, Single phase SF6 GasInsulated Bus Duct (GIB) outside GISHall alongwith associated supportstructure M 495 Included 0.00 0 0.00
13 7000030922 330 GIS Portion- 420 kV GIS Equipments 1000077609 85359030 18% 420KV,4000A, 63KA, 3-PHASE GIS EXTENSION PIECE (INTERFACE) MODULESUITABLE FOR EXTENDING EXISTING NHVS MAKE GIS BUS BAR/DUCT AS PERTECHNICAL SPECIFICATION SET 2 Included 0.00 0 0.00
14 7000030922 340 GIS Portion- 420 kV GIS Equipments 1000077935 85359030 18% 420KV, 1-PHASE GIS EXTENSION PIECE (INTERFACE) MODULE SUITABLE FOREXTENDING EXISTING NHVS MAKE GIS AUXILIARY BUS BAR FOR CONNECTINGWITH SPARE ICT UNIT AS PER TECHNICAL SPECIFICATION SET 1 Included 0.00 0 0.00
15 7000030922 410 EOT CRANE 400kV GIS HALL 1000024691 85389000 18% EOT Crane for GIS Building for 400kV GIS station SET 1 Included 0.00 0 0.00
16 7000030922 20 420 kV AIS equipments 1000004401 85462040 18% 420 kV, 1 phase Bus Post Insulator (except for Line Traps) EA 15 Included 0.00 0 0.00
17 7000030922 10 420 kV AIS equipments 1000020419 85354010 18% 336kV Surge Arrester (1-phase) EA 9 Included 0.00 0 0.00
18 7000030922 360 CONTROL & RELAY PANEL-400KV 1000055446 85371000 18% 400KV CIRCUIT BREAKER RELAY PANEL (WITH AUTOMATION) EA 7 Included 0.00 0 0.00
19 7000030922 370 CONTROL & RELAY PANEL-400KV 1000004274 85371000 18% 400kV Transformer Protection Panel (For both HV & MV side)-(withAutomation) EA 2 Included 0.00 0 0.00
20 7000030922 380 SUBSTATION AUTOMATION SYSTEM 1000003409 85371000 18% Augmentation of Substation automation System for 400kV Main bay as perTechnical Specification EA 4 Included 0.00 0 0.00
21 7000030922 390 SUBSTATION AUTOMATION SYSTEM 1000003411 85371000 18% Augmentation of Substation automation System for 400kV Tie bay as perTechnical Specification EA 2 Included 0.00 0 0.00
22 7000030922 400 SUBSTATION AUTOMATION SYSTEM 1000003412 85371000 18% Augmentation of Substation automation System for 400kV Switchable LineReactor Bay as per Technical Specification EA 1 Included 0.00 0 0.00
23 7000030922 30 FIRE PROTECTION SYSTEM 1000012010 85311020 18% Fire Detection and Alarm System for 400kV GIS Hall SET 1 Included 0.00 0 0.00
24 7000030922 40 FIRE PROTECTION SYSTEM 1000012069 84248990 18% HVW spray system, Hydrant system and complete U/G & O/G piping andaccessories etc. out side the pump house for 500MVA , 400KV/220/33kV, 3-phase Autotransformer SET 2 Included 0.00 0 0.00
25 7000030922 50 FIRE PROTECTION SYSTEM 1000012022 84241000 18% 4.5 kg CO2 type Portable Fire extinguisher EA 5 Included 0.00 0 0.00
26 7000030922 80 FIRE PROTECTION SYSTEM 1000012026 84241000 18% 6Kg dry chemical powered type Portable Fire extinguisher EA 5 Included 0.00 0 0.00
27 7000030922 60 FIRE PROTECTION SYSTEM 1000012037 84819090 18% Hydrant system, complete U/G piping and accessories etc. outside thePump House for Fire Protection of 400/220kV (Ext) Substation SET 1 Included 0.00 0 0.00
28 7000030922 70 FIRE PROTECTION SYSTEM 1000049460 84818090 18% FIRE PROTECTION SYSTEM FOR LOCAL RELAY ROOM FOR 400KV GIS SET 1 Included 0.00 0 0.00
29 7000030922 530 POWER & CONTROL CABLE 1000000443 85446020 18% 1.1kV grade Power Cables (PVCinsulated)along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0.00
30 7000030922 540 POWER & CONTROL CABLE 1000000442 85446020 18% 1.1kV grade Control Cables (PVCinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0.00
31 7000030922 550 POWER & CONTROL CABLE 1000000444 85446090 18% 1.1kV grade Power Cables (XLPEinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0.00
32 7000030922 90 AIR CONDITIONING SYS & VENTILATION SYS 1000025963 84151090 28% Air conditioning sys-400kV GIS Hall LCC SET 1 Included 0.00 0 0.00
33 7000030922 100 AIR CONDITIONING SYS & VENTILATION SYS 1000022408 84159000 28% Ventillation system for 400KV GIS Hall SET 1 Included 0.00 0 0.00
34 7000030922 110 LIGHTING SYSTEM 1000038385 94059900 18% FIRE WALL MOUNTED LED LUMINARIE TYPE FL-2 (250W) EA 4 Included 0.00 0 0.00
35 7000030922 120 LIGHTING SYSTEM 1000038325 94059900 18% LIGHTING FIXTURE LED LUMINAIRES TYPE FL2 AS PER TECH. SPECIFICATIONS EA 9 Included 0.00 0 0.00
36 7000030922 130 LIGHTING SYSTEM 1000038387 94051090 18% LED FLOOD LIGHT LUMINARIESTYPE FL-1 (150W) AS PER TECHNICALSPECIFICATION EA 9 Included 0.00 0 0.00
37 7000030922 140 LIGHTING SYSTEM 1000001894 94059900 18% Outdoor Power Receptacle for oilfiltration unit (250A) EA 1 Included 0.00 0 0.00
38 7000030922 150 LIGHTING SYSTEM 1000014547 85371000 18% Lighting Panel type ACP-2 as per technical specification EA 2 Included 0.00 0 0.00
39 7000030922 160 LIGHTING SYSTEM 1000049467 94059900 18% INDOOR LIGHTNING FOR GIS BUILDING (AS PER TECHNICAL SPECIFICATION) including AHU & Relay Rooms as applicable SET 1 Included 0.00 0 0.00
40 7000030922 170 MAIN EARTHMAT 1000032055 72159090 18% 40 MM MS ROD FOR MAIN EARTHMAT KM 1 Included 0.00 0 0.00
41 7000030922 180 ERECTION HARDWARE 1000011334 72169990 18% Erection Hardware for 400kV I type layout for GIS terminationarrangement-Transformer bay as per technical specification SET 3 Included 0.00 0 0.00
42 7000030922 190 MANDATORY SPARES-AIS 1000024186 85354010 18% SPARES FOR 336KV SURGE ARRESTER LS 1 Included 0.00 0 0.00
43 7000030922 200 MANDATORY SPARES-AIS 1000019912 85371000 18% Relay & protection Panels (with automation) LS 1 Included 0.00 0 0.00
44 7000030922 210 MANDATORY SPARES-AIS 1000019925 84819090 18% Spares for Fire Protection System LS 1 Included 0.00 0 0.00
45 7000030922 560 MANDATORY SPARES FOR SAS-AIS 1000062002 85371000 18% BAY CONTROL UNIT (IED) OF MAIN SYSTEM EA 1 Included 0.00 0 0.00
46 7000030922 570 MANDATORY SPARES FOR SAS-AIS 1000062004 85371000 18% ETHERNET SWITCH SUITABLE FOR 19€ RACK MOUNTING WITH 24 FIBER OPTICPORTS EA 1 Included 0.00 0 0.00
47 7000030922 710 GIS PORTION-TESTING & MAINTENANCE EQPT 1000038259 84289090 18% SCISSOR LIFT EA 1 Included 0.00 0 0.00
48 7000030922 600 Supply of non standard structure 1000015954 73082011 18% Fabrication, galvanising and supply of Lattice Structures (MS Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 7 Included 0.00 0 0.00
49 7000030922 610 Supply of non standard structure 1000015953 73082011 18% Fabrication, galvanising and supply of Lattice Structures (HT Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 2 Included 0.00 0 0.00
50 7000030922 620 Supply of non standard structure 1000011713 73082011 18% Fabrication, galvanising and supply of fasteners ( nuts, bolts andwashers ) including step bolts for lattice and pipe structures to bedesigned during detailed engineering MT 1 Included 0.00 0 0.00
51 7000030922 630 Supply of non standard structure 1000012373 73082011 18% Fabrication, galvanising and supply of foundation bolts including nuts,checknut and washers for lattice and pipe structures to be designedduring detailed engineering MT 3 Included 0.00 0 0.00
52 7000030922 640 PMUs for 400kV Bhuj-II PS 1000017518 85364900 18% PMU with GPS Clock (clock can be either internal or external) EA 3 Included 0.00 0 0.00
53 7000030922 650 PMUs for 400kV Bhuj-II PS 1000022512 90311000 18% WAMS Hardware - Time System (GPS receiver) EA 3 Included 0.00 0 0.00
54 7000030922 660 PMUs for 400kV Bhuj-II PS 1000071061 85176290 18% SUBSTATION GRADE LAYER 2 LAN SWITCH EA 3 Included 0.00 0 0.00
55 7000030922 670 PMUs for 400kV Bhuj-II PS 1000071062 85176290 18% SUBSTATION GRADE LAYER 3 LAN SWITCH EA 1 Included 0.00 0 0.00
56 7000030922 680 PMUs for 400kV Bhuj-II PS 1000022487 85447090 18% WAMS Miscellaneous - Armored Fibre Optic Cable and associatedtermination (e.g. L2 Switch) for connecting PMU panels located indifferent control room of a station EA 1 Included 0.00 0 0.00
57 7000030922 690 PMUs for 400kV Bhuj-II PS 1000030641 85389000 18% LIU - FO PATCH PANEL-12 PORT EA 4 Included 0.00 0 0.00
B 220kV line bays at Bhuj-II PS
1 7000030923 10 GIS Portion- 245kV GIS Equipments 1000039036 73079210 18% 245KV,3000 A, 50KA FOR 1 SECOND, SF6 GAS-INSULATED METAL ENCLOSED BUSSECTION BAY MODULE AS PER SECTION-PROJECT, TECHNICAL SPECIFICATION EA 2 Included 0.00 0 0.00
2 7000030923 20 GIS Portion- 245kV GIS Equipments 1000001840 85359030 18% 245kV, 3000 A, 50 kA, SF6 GIS Buscoupler bay module as perSection-Project, Technicalspecification SET 1 Included 0.00 0 0.00
3 7000030923 30 GIS Portion- 245kV GIS Equipments 1000001691 85359030 18% 245kV, 1600 A, 50 kA, SF6 GIS Linefeeder bay module as perSection-Project, Technicalspecification SET 1 Included 0.00 0 0.00
4 7000030923 40 GIS Portion- 245kV GIS Equipments 1000001690 85359030 18% 245kV, 1600 A, 50 kA, SF6 GIS ICT feederbay module as per Section-Project,Technical specification SET 2 Included 0.00 0 0.00
5 7000030923 50 GIS Portion- 245kV GIS Equipments 1000001693 85389000 18% 245kV,1600A, 50kA,3 Single phase/3Phase, SF6 Gas Insulated Bus Duct (GIB)outside GIS Hall alongwith associatedsupport structure(Quantity mentionedhere is for 3 Phase type) M 108 Included 0.00 0 0.00
6 7000030923 60 GIS Portion- 245kV GIS Equipments 1000029503 85389000 18% 245kV, 1600A, 50kA Single phase SF6 to Air Bushing EA 9 Included 0.00 0 0.00
7 7000030923 70 GIS Portion- 245kV GIS Equipments 1000001752 85359030 18% 245kV,3000A,50kA,3 Single phase/3 Phase,SF6 Gas Insulated Bus Duct (GIB)outside GIS Hall alongwith associatedsupport structure(Quantity mentionedhere is for 3 Phase type) M 196 Included 0.00 0 0.00
8 7000030923 80 GIS Portion- 245kV GIS Equipments 1000032784 85359030 18% 245 KV,3000 A, 50 KA SF6 GIS BUS BAR MODULE EXTENSION AS PERSECTION-PROJECT, TECHNICAL SPECIFICATION SET 2 Included 0.00 0 0.00
9 7000030923 90 GIS Portion- 245kV GIS Equipments 1000001838 85359030 18% 245 kV, 3000A, 50kA, SF6 GIS Bus barmodule as per Section-Project,Technical specification SET 2 Included 0.00 0 0.00
10 7000030923 100 GIS Portion- 245kV GIS Equipments 1000077602 85359030 18% 245KV,3000A, 50KA, 3-PHASE GIS EXTENSION PIECE (INTERFACE) MODULESUITABLE FOR EXTENDING EXISTING NHVS MAKE GIS BUS BAR/DUCT AS PERTECHNICAL SPECIFICATION SET 2 Included 0.00 0 0.00
11 7000030923 110 EOT CRANE 220kV GIS HALL 1000024690 85389000 18% EOT Crane for GIS Building for 220kV GIS Station SET 1 Included 0.00 0 0.00
12 7000030923 120 245kV AIS equipments 1000001695 85462040 18% 245 kV, 1 phase Bus Post Insulator (except for Line Traps) EA 21 Included 0.00 0 0.00
13 7000030923 130 245kV AIS equipments 1000020417 85354010 18% 216kV Surge Arrester (1-phase) EA 9 Included 0.00 0 0.00
14 7000030923 140 245kV AIS equipments 1000001772 85359090 18% 245 kV, 4400pf Capacitive Voltage Transformer (1- Phase) EA 3 Included 0.00 0 0.00
15 7000030923 150 245kV AIS equipments 1000001568 85176210 18% 220kV,1600A,0.5mH ,50kA Line Trap EA 2 Included 0.00 0 0.00
16 7000030923 160 245kV AIS equipments 1000001694 85462040 18% 245 kV ,1 phase Bus Post Insulators for Line Traps EA 6 Included 0.00 0 0.00
17 7000030923 170 CONTROL & RELAY PANEL-220KV 1000055443 85371000 18% 220KV CIRCUIT BREAKER RELAY PANEL (WITH AUTOMATION) EA 6 Included 0.00 0 0.00
18 7000030923 180 CONTROL & RELAY PANEL-220KV 1000001330 85371000 18% 220kV Line Protection Panel (with Automation) EA 1 Included 0.00 0 0.00
19 7000030923 190 CONTROL & RELAY PANEL-220KV 1000001166 85371000 18% 220kV Bus Bar Protection Panel (Single)-(with Automation) SET 1 Included 0.00 0 0.00
20 7000030923 200 SUBSTATION AUTOMATION SYSTEM 1000001333 85371000 18% Augmentation of Substation automation System for 220kV bay as perTechnical Specification EA 6 Included 0.00 0 0.00
21 7000030923 210 FIRE PROTECTION SYSTEM 1000012009 85311020 18% Fire Detection and Alarm System for 220kV GIS Hall SET 1 Included 0.00 0 0.00
22 7000030923 220 FIRE PROTECTION SYSTEM 1000012022 84241000 18% 4.5 kg CO2 type Portable Fire extinguisher EA 5 Included 0.00 0 0.00
23 7000030923 250 FIRE PROTECTION SYSTEM 1000012026 84241000 18% 6Kg dry chemical powered type Portable Fire extinguisher EA 5 Included 0.00 0 0.00
24 7000030923 230 FIRE PROTECTION SYSTEM 1000012034 84819090 18% Hydrant system, complete U/G piping andaccessories etc. outside the Pump Housefor Fire Protection of 220kV (Ext) S/S SET 1 Included 0.00 0 0.00
25 7000030923 240 FIRE PROTECTION SYSTEM 1000049459 84818090 18% FIRE PROTECTION SYSTEM FOR LOCAL RELAY ROOM FOR 220KV GIS SET 1 Included 0.00 0 0.00
26 7000030923 490 POWER & CONTROL CABLE 1000000443 85446020 18% 1.1kV grade Power Cables (PVCinsulated)along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0.00
27 7000030923 500 POWER & CONTROL CABLE 1000000442 85446020 18% 1.1kV grade Control Cables (PVCinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0.00
28 7000030923 510 POWER & CONTROL CABLE 1000000444 85446090 18% 1.1kV grade Power Cables (XLPEinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0.00
29 7000030923 260 AIR CONDITIONING SYSTEM 1000032700 84151090 28% AIRCONDITIONING SYSTEM FOR LCR IN 245KV GIS BUILDING SET 1 Included 0.00 0 0.00
30 7000030923 270 AIR CONDITIONING SYSTEM 1000022406 84159000 28% Ventillation system for 220KV GIS Hall SET 1 Included 0.00 0 0.00
31 7000030923 310 LIGHTING SYSTEM 1000038325 94059900 18% LIGHTING FIXTURE LED LUMINAIRES TYPE FL2 AS PER TECH. SPECIFICATIONS EA 5 Included 0.00 0 0.00
32 7000030923 320 LIGHTING SYSTEM 1000038387 94051090 18% LED FLOOD LIGHT LUMINARIESTYPE FL-1 (150W) AS PER TECHNICALSPECIFICATION EA 5 Included 0.00 0 0.00
33 7000030923 330 LIGHTING SYSTEM 1000014547 85371000 18% Lighting Panel type ACP-2 as per technical specification EA 1 Included 0.00 0 0.00
34 7000030923 340 LIGHTING SYSTEM 1000049467 94059900 18% INDOOR LIGHTNING FOR GIS BUILDING (AS PER TECHNICAL SPECIFICATION) including AHU & Relay Rooms as applicable SET 1 Included 0.00 0 0.00
35 7000030923 350 LIGHTING SYSTEM 1000038392 94059900 18% RP TYPE RECEPTACLE OF 63A AS PER TECHNICAL SPECIFICATION EA 1 Included 0.00 0 0.00
36 7000030923 280 MAIN EARTHMAT 1000032055 72159090 18% 40 MM MS ROD FOR MAIN EARTHMAT KM 1 Included 0.00 0 0.00
37 7000030923 290 ERECTION HARDWARE 1000011246 72169990 18% Erection Hardware for 220kV DM-type layout for GIS terminationarrangement-Line bay as per technical specification SET 1 Included 0.00 0 0.00
38 7000030923 300 ERECTION HARDWARE 1000011252 72169990 18% Erection Hardware for 220kV DM-type layout for GIS terminationarrangement-Transformer bay as per technical specification SET 2 Included 0.00 0 0.00
39 7000030923 360 MANDATORY SPARES-AIS 1000025930 85354010 18% Spare-216kV Surge Arrester SET 1 Included 0.00 0 0.00
40 7000030923 370 MANDATORY SPARES-AIS 1000025934 85359090 18% Spare-245kV CVT SET 1 Included 0.00 0 0.00
41 7000030923 580 GIS PORTION-TESTING & MAINTENANCE EQPT 1000038259 84289090 18% SCISSOR LIFT EA 1 Included 0.00 0 0.00
42 7000030923 540 Supply of Non standard structure 1000015954 73082011 18% Fabrication, galvanising and supply of Lattice Structures (MS Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 30 Included 0.00 0 0.00
43 7000030923 550 Supply of Non standard structure 1000015953 73082011 18% Fabrication, galvanising and supply of Lattice Structures (HT Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 5 Included 0.00 0 0.00
44 7000030923 560 Supply of Non standard structure 1000011713 73082011 18% Fabrication, galvanising and supply of fasteners ( nuts, bolts andwashers ) including step bolts for lattice and pipe structures to bedesigned during detailed engineering MT 2 Included 0.00 0 0.00
45 7000030923 570 Supply of Non standard structure 1000012373 73082011 18% Fabrication, galvanising and supply of foundation bolts including nuts,checknut and washers for lattice and pipe structures to be designedduring detailed engineering MT 5 Included 0.00 0 0.00
C Extn. of 400/220kV Bhuj-II GIS S/S
1 7000030924 10 GIS Portion- 420 kV GIS Equipments 1000055830 85359030 18% 420KV, 3150 A, 63 KA, SF6 GIS SWITCHABLE LINE REACTOR BAY MODULE ASPER SECTION-PROJECT, TECHNICAL SPECIFICATION SET 2 Included 0.00 0 0.00
2 7000030924 20 GIS Portion- 420 kV GIS Equipments 1000059208 85359030 18% 420KV, 3150 A, 63 KA, SF6 GIS ICT FEEDER BAY MODULE FOR IV SIDECONNECTION WITH 765KV ICT AS PER SECTION-PROJECT, TECHNICALSPECIFICATION SET 1 Included 0.00 0 0.00
3 7000030924 30 GIS Portion- 420 kV GIS Equipments 1000004505 85359030 18% 420kV, 3150 A, 63 kA, SF6 GIS Tie baymodule(without PIR) as perSection-Project, Technicalspecification SET 1 Included 0.00 0 0.00
4 7000030924 40 GIS Portion- 420 kV GIS Equipments 1000009713 85389000 18% Controlled Switching Device for 420 kV, 3-ph Circuit Breaker EA 9 Included 0.00 0 0.00
5 7000030924 90 GIS Portion- 420 kV GIS Equipments 1000032796 85389000 18% 420KV, 3150A, 63KA SF6 TO AIR BUSHING including support structure SET 12 Included 0.00 0 0.00
6 7000030924 50 GIS Portion- 420 kV GIS Equipments 1000004287 85389000 18% 420kV, 3000A, 63kA, Single phase, SF6Gas Insulated Bus Duct (GIB) outsideGIS Hall alongwith associated supportstructure M 535 Included 0.00 0 0.00
7 7000030924 60 GIS Portion- 420 kV GIS Equipments 1000004635 85359030 18% 420kV, 3150 A, 63 kA, SF6 GIS Tie baymodule(with PIR) as perSection-Project, Technicalspecification SET 2 Included 0.00 0 0.00
8 7000030924 70 GIS Portion- 420 kV GIS Equipments 1000004634 85359030 18% 420 kV, 3150 A, 63 kA, SF6 GIS Linefeeder bay module(with PIR) as perSection-Project, Technicalspecification SET 2 Included 0.00 0 0.00
9 7000030924 80 GIS Portion- 420 kV GIS Equipments 1000004637 85359030 18% 420kV, 3150 A, 63 kA, SF6 GIS ICT feederbay module as per Section-Project,Technical specification SET 3 Included 0.00 0 0.00
10 7000030924 680 GIS Portion- 245 kV GIS Equipments 1000029503 85389000 18% 245kV, 1600A, 50kA Single phase SF6 to Air Bushing EA 27 Included 0.00 0 0.00
11 7000030924 690 GIS Portion- 245 kV GIS Equipments 1000001693 85389000 18% 245kV,1600A, 50kA,3 Single phase/3Phase, SF6 Gas Insulated Bus Duct (GIB)outside GIS Hall alongwith associatedsupport structure(Quantity mentionedhere is for 3 Phase type) M 314 Included 0.00 0 0.00
12 7000030924 700 GIS Portion- 245 kV GIS Equipments 1000001690 85359030 18% 245kV, 1600 A, 50 kA, SF6 GIS ICT feederbay module as per Section-Project,Technical specification SET 3 Included 0.00 0 0.00
13 7000030924 710 GIS Portion- 245 kV GIS Equipments 1000001691 85359030 18% 245kV, 1600 A, 50 kA, SF6 GIS Linefeeder bay module as perSection-Project, Technicalspecification SET 6 Included 0.00 0 0.00
14 7000030924 100 420 kV AIS EQUIPMENTS 1000004401 85462040 18% 420 kV, 1 phase Bus Post Insulator (except for Line Traps) EA 18 Included 0.00 0 0.00
15 7000030924 110 420 kV AIS EQUIPMENTS 1000020419 85354010 18% 336kV Surge Arrester (1-phase) EA 12 Included 0.00 0 0.00
16 7000030924 720 245 kV AIS EQUIPMENTS 1000001695 85462040 18% 245 kV, 1 phase Bus Post Insulator (except for Line Traps) EA 45 Included 0.00 0 0.00
17 7000030924 730 245 kV AIS EQUIPMENTS 1000020417 85354010 18% 216kV Surge Arrester (1-phase) EA 27 Included 0.00 0 0.00
18 7000030924 740 245 kV AIS EQUIPMENTS 1000001772 85359090 18% 245 kV, 4400pf Capacitive Voltage Transformer (1- Phase) EA 18 Included 0.00 0 0.00
19 7000030924 750 245 kV AIS EQUIPMENTS 1000001568 85176210 18% 220kV,1600A,0.5mH ,50kA Line Trap EA 12 Included 0.00 0 0.00
20 7000030924 760 245 kV AIS EQUIPMENTS 1000001694 85462040 18% 245 kV ,1 phase Bus Post Insulators for Line Traps EA 36 Included 0.00 0 0.00
21 7000030924 120 CONTROL & RELAY PANEL 1000055446 85371000 18% 400KV CIRCUIT BREAKER RELAY PANEL (WITH AUTOMATION) EA 11 Included 0.00 0 0.00
22 7000030924 130 CONTROL & RELAY PANEL 1000004274 85371000 18% 400kV Transformer Protection Panel (For both HV & MV side)-(withAutomation) EA 3 Included 0.00 0 0.00
23 7000030924 140 CONTROL & RELAY PANEL 1000055443 85371000 18% 220KV CIRCUIT BREAKER RELAY PANEL (WITH AUTOMATION) EA 9 Included 0.00 0 0.00
24 7000030924 150 CONTROL & RELAY PANEL 1000001330 85371000 18% 220kV Line Protection Panel (with Automation) EA 6 Included 0.00 0 0.00
25 7000030924 190 SUBSTATION AUTOMATION SYSTEM 1000003412 85371000 18% Augmentation of Substation automation System for 400kV Switchable LineReactor Bay as per Technical Specification EA 2 Included 0.00 0 0.00
26 7000030924 160 SUBSTATION AUTOMATION SYSTEM 1000001333 85371000 18% Augmentation of Substation automation System for 220kV bay as perTechnical Specification EA 9 Included 0.00 0 0.00
27 7000030924 170 SUBSTATION AUTOMATION SYSTEM 1000003409 85371000 18% Augmentation of Substation automation System for 400kV Main bay as perTechnical Specification EA 6 Included 0.00 0 0.00
28 7000030924 180 SUBSTATION AUTOMATION SYSTEM 1000003411 85371000 18% Augmentation of Substation automation System for 400kV Tie bay as perTechnical Specification EA 3 Included 0.00 0 0.00
29 7000030924 200 FIRE PROTECTION SYSTEM 1000012069 84248990 18% HVW spray system, Hydrant system and complete U/G & O/G piping andaccessories etc. out side the pump house for 500MVA , 400KV/220/33kV, 3-phase Autotransformer SET 3 Included 0.00 0 0.00
30 7000030924 1280 POWER & CONTROL CABLE 1000000443 85446020 18% 1.1kV grade Power Cables (PVCinsulated)along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0.00
31 7000030924 1290 POWER & CONTROL CABLE 1000000442 85446020 18% 1.1kV grade Control Cables (PVCinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0.00
32 7000030924 1300 POWER & CONTROL CABLE 1000000444 85446090 18% 1.1kV grade Power Cables (XLPEinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0.00
33 7000030924 250 LIGHTING SYSTEM 1000038385 94059900 18% FIRE WALL MOUNTED LED LUMINARIE TYPE FL-2 (250W) EA 6 Included 0.00 0 0.00
34 7000030924 260 LIGHTING SYSTEM 1000038325 94059900 18% LIGHTING FIXTURE LED LUMINAIRES TYPE FL2 AS PER TECH. SPECIFICATIONS EA 20 Included 0.00 0 0.00
35 7000030924 270 LIGHTING SYSTEM 1000038387 94051090 18% LED FLOOD LIGHT LUMINARIESTYPE FL-1 (150W) AS PER TECHNICALSPECIFICATION EA 20 Included 0.00 0 0.00
36 7000030924 280 LIGHTING SYSTEM 1000014547 85371000 18% Lighting Panel type ACP-2 as per technical specification EA 1 Included 0.00 0 0.00
37 7000030924 290 LIGHTING SYSTEM 1000038392 94059900 18% RP TYPE RECEPTACLE OF 63A AS PER TECHNICAL SPECIFICATION EA 2 Included 0.00 0 0.00
38 7000030924 210 MAIN EARTHMAT 1000032055 72159090 18% 40 MM MS ROD FOR MAIN EARTHMAT KM 4 Included 0.00 0 0.00
39 7000030924 220 ERECTION HARDWARE 1000011334 72169990 18% Erection Hardware for 400kV I type layout for GIS terminationarrangement-Transformer bay as per technical specification SET 4 Included 0.00 0 0.00
40 7000030924 230 ERECTION HARDWARE 1000011252 72169990 18% Erection Hardware for 220kV DM-type layout for GIS terminationarrangement-Transformer bay as per technical specification SET 3 Included 0.00 0 0.00
41 7000030924 240 ERECTION HARDWARE 1000011246 72169990 18% Erection Hardware for 220kV DM-type layout for GIS terminationarrangement-Line bay as per technical specification SET 6 Included 0.00 0 0.00
42 7000030924 300 GIS Portion-Mandatory Spares-400kV GIS 1000058332 85359030 18% 400KV GIS-SF6 GAS PRESSURE RELIEF DEVICE ASSEMBLY OF EACH TYPE EA 1 Included 0.00 0 0.00
43 7000030924 310 GIS Portion-Mandatory Spares-400kV GIS 1000049817 85359030 18% SF6 PRESSURE GAUGE CUM SWITCH /DENSITY MONITORS AND PRESSURESWITCH AS APPLICABLE, OF EACH TYPE-400KV GIS SET 2 Included 0.00 0 0.00
44 7000030924 320 GIS Portion-Mandatory Spares-400kV GIS 1000049753 85359030 18% COUPLING DEVICE FOR PRESSURE GAUGE CUM SWITCH FOR CONNECTINGGAS HANDLING PLANT OF EACH TYPE-400KV GIS SET 1 Included 0.00 0 0.00
45 7000030924 330 GIS Portion-Mandatory Spares-400kV GIS 1000049762 85359030 18% RUBBER GASKETS, €ŒO€ RINGS AND SEALS FOR SF6 GAS FOR GISENCLOSURE OF EACH TYPE-400KV GIS SET 2 Included 0.00 0 0.00
46 7000030924 340 GIS Portion-Mandatory Spares-400kV GIS 1000058330 85359030 18% 400KV GIS-MOLECULAR FILTER FOR SF6 GAS WITH FILTER BAGS (5 % OF TOTALWEIGHT) SET 1 Included 0.00 0 0.00
47 7000030924 350 GIS Portion-Mandatory Spares-400kV GIS 1000049750 85359030 18% CONTROL VALVES FOR SF6 GAS OF EACH TYPE-400KV GIS SET 2 Included 0.00 0 0.00
48 7000030924 360 GIS Portion-Mandatory Spares-400kV GIS 1000058331 85359030 18% 400KV GIS-SF6 GAS (5 % OF TOTAL GAS QUANTITY) LOT 1 Included 0.00 0 0.00
49 7000030924 370 GIS Portion-Mandatory Spares-400kV GIS 1000049783 85359030 18% LOCKING DEVICE TO KEEP THE DIS-CONNECTORS (ISOLATORS)AND EARTHING/FAST EARTHING SWITCHES IN CLOSE OR OPEN POSITION IN CASEOF REMOVAL OF THE DRIVING MECHANISM-400KV GIS SET 2 Included 0.00 0 0.00
50 7000030924 380 GIS Portion-Mandatory Spares-400kV GIS 1000049505 85359030 18% UHF PD SENSORS OF EACH TYPE ALONG WITH BNC CONNECTOR FOR 420KV GIS EA 3 Included 0.00 0 0.00
51 7000030924 390 GIS Portion-Mandatory Spares-400kV GIS 1000058334 85359030 18% 400KV GIS-SUPPORT INSULATORS (GAS THROUGH) OF EACH TYPE (COMPLETE WITHMETAL RING ETC.) ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 3 Included 0.00 0 0.00
52 7000030924 400 GIS Portion-Mandatory Spares-400kV GIS 1000058329 85359030 18% 400KV GIS-GAS BARRIERS OF EACH TYPE (COMPLETE WITH METAL RING ETC.)ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 3 Included 0.00 0 0.00
53 7000030924 410 GIS Portion-Mandatory Spares-400kV GIS 1000058333 85359030 18% 400KV GIS- 3150A SF6 TO AIR BUSHING COMPLETE IN ALL RESPECT EA 1 Included 0.00 0 0.00
54 7000030924 420 GIS Portion-Mandatory Spares-400kV GIS 1000049498 85359030 18% LCC SPARES - AUX. RELAYS, CONTACTORS,PUSH BUTTONS, SWITCHES,LAMPS,ANNUNCIATION WINDOWS, MCB, FUSES,TIMERS, TERMINAL BLOCKS ETC. OF EACHTYPE & RATING-400kV GIS SET 1 Included 0.00 0 0.00
55 7000030924 430 GIS Portion-Mandatory Spares-400kV GIS 1000058317 85359030 18% 400KV GIS-ONE POLE OF 3150A CIRCUIT BREAKER WITHOUT PIR WITHINTERRUPTER, MAIN CIRCUIT, ENCLOSURE AND OPERATING MECHANISM COMPLETEIN ALL RESPECT SET 1 Included 0.00 0 0.00
56 7000030924 670 GIS Portion-Mandatory Spares-400kV GIS 1000058316 85359030 18% 400KV GIS-ONE POLE OF 3150A CIRCUIT BREAKER WITH PIR WITH INTERRUPTER,MAIN CIRCUIT, ENCLOSURE AND OPERATING MECHANISM COMPLETE IN ALLRESPECT SET 1 Included 0.00 0 0.00
57 7000030924 440 GIS Portion-Mandatory Spares-400kV GIS 1000021873 85389000 18% Trip coil assembly with resistor for420kV GIS Circuit Breaker (asapplicable) SET 3 Included 0.00 0 0.00
58 7000030924 450 GIS Portion-Mandatory Spares-400kV GIS 1000009208 85389000 18% Closing coil assembly with resistor for420kV GIS Circuit Breaker (asapplicable) SET 3 Included 0.00 0 0.00
59 7000030924 460 GIS Portion-Mandatory Spares-400kV GIS 1000058324 85359030 18% RELAYS, POWER CONTACTORS, PUSH BUTTONS, TIMERS & MCBS ETC. (ASAPPLICABLE) OF EACH TYPE FOR 400KV GIS CIRCUIT BREAKER SET 1 Included 0.00 0 0.00
60 7000030924 470 GIS Portion-Mandatory Spares-400kV GIS 1000007067 85389000 18% Auxiliary switch assembly of each type for 420kV GIS Circuit Breaker SET 1 Included 0.00 0 0.00
61 7000030924 480 GIS Portion-Mandatory Spares-400kV GIS 1000058323 85359030 18% 400KV GIS CIRCUIT BREAKER-OPERATION COUNTER EA 1 Included 0.00 0 0.00
62 7000030924 490 GIS Portion-Mandatory Spares-400kV GIS 1000058325 85359030 18% 400KV GIS CIRCUIT BREAKER-COMPLETE SPRING OPERATING MECHANISMINCLUDING CHARGING MECHANISM ETC. (FOR SPRING OPERATED MECHANISM, IFAPPLICABLE) SET 1 Included 0.00 0 0.00
63 7000030924 500 GIS Portion-Mandatory Spares-400kV GIS 1000058374 85359030 18% 400kV GIS- Single phase of 3150Adisconnector switch including maincircuit, enclosure, driving mechanismand support insulator etc., complete inall respect (Note 1- The contractorshall supply spare for disconnectorswitch to ensure one to one replacementof all disconnector switch supplied asmain equipment without any requirementof modification in fittings at site tocover all different types ofdisconnector switch supplied. In case,quantity of supplied dis-connectorswitch types (for one to onereplacement) are more than the quantitymentioned in BPS for spare, thecontractor shall supply theseadditional types of disconnector switchwithout any additional priceimplication to POWERGRID and quantitiesof these additional type ofdisconnector switch are deem to beincluded in the quantities mentioned inBPS for spare disconnector. Note 2 - Incase, Dis-connector Switch (DS) & EarthSwitch (ES) is provided in a sameenclosure with common operatingmechanism, then the module comprisingof Dis-connector & Earth switch insingle enclosure with common operatingmechanism is to be provided under thehead of spare Dis-connector only. Note3- In case, Dis-connector Switch (DS)&Earth Switch (ES) is provided in asame enclosure with separate operatingmechanism, then the module comprisingof Dis-connector & Earth switch insingle enclosure with separateoperating mechanism is to be providedunder the head of spare Dis-connectoronly.) EA 2 Included 0.00 0 0.00
64 7000030924 510 GIS Portion-Mandatory Spares-400kV GIS 1000058314 85359030 18% 400KV GIS- SINGLE PHASE MAINTENANCE EARTHING SWITCH INCLUDING MAINCIRCUIT, ENCLOSURE, DRIVING MECHANISM AND SUPPORT INSULATOR ETC.,COMPLETE IN ALL RESPECT (NOTE 1 - IN CASE, DIS-CONNECTOR SWITCH (DS) &EARTH SWITCH (ES) IS PROVIDED IN A SAME ENCLOSURE WITH COMMONOPERATING MECHANISM, THEN THE MODULE COMPRISING OF DIS-CONNECTOR &EARTH SWITCH IN SINGLE ENCLOSURE WITH COMMON OPERATING MECHANISM IS TOBE PROVIDED UNDER THE HEAD OF SPARE DIS-CONNECTOR ONLY. NOTE 2 - INCASE, DIS-CONNECTOR SWITCH (DS) & EARTH SWITCH (ES) IS PROVIDED IN ASAME ENCLOSURE WITH SEPARATE OPERATING MECHANISM, THEN THE MODULECOMPRISING OF DIS-CONNECTOR & EARTH SWITCH IN SINGLE ENCLOSURE WITHSEPARATE OPERATING MECHANISM IS TO BE PROVIDED UNDER THE HEAD OF SPAREDIS-CONNECTOR ONLY.) EA 1 Included 0.00 0 0.00
65 7000030924 520 GIS Portion-Mandatory Spares-400kV GIS 1000058310 85359030 18% 400KV GIS - SINGLE PHASE FAST EARTHING SWITCH INCLUDING MAIN CIRCUIT,ENCLOSURE, DRIVING MECHANISM AND SUPPORT INSULATOR ETC., COMPLETE INALL RESPECT (NOTE 1 - IN CASE, DIS-CONNECTOR SWITCH (DS) & EARTHSWITCH (ES) IS PROVIDED IN A SAME ENCLOSURE WITH COMMON OPERATINGMECHANISM, THEN THE MODULE COMPRISING OF DIS-CONNECTOR & EARTH SWITCHIN SINGLE ENCLOSURE WITH COMMON OPERATING MECHANISM IS TO BE PROVIDEDUNDER THE HEAD OF SPARE DIS-CONNECTOR ONLY. NOTE 2 - IN CASE,DIS-CONNECTOR SWITCH (DS) & EARTH SWITCH (ES) IS PROVIDED IN A SAMEENCLOSURE WITH SEPARATE OPERATING MECHANISM, THEN THE MODULECOMPRISING OF DIS-CONNECTOR & EARTH SWITCH IN SINGLE ENCLOSURE WITHSEPARATE OPERATING MECHANISM IS TO BE PROVIDED UNDER THE HEAD OF SPAREDIS-CONNECTOR ONLY.) EA 1 Included 0.00 0 0.00
66 7000030924 530 GIS Portion-Mandatory Spares-400kV GIS 1000058305 85359030 18% OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 400KV GIS DISCONNECTORSWITCH SET 1 Included 0.00 0 0.00
67 7000030924 540 GIS Portion-Mandatory Spares-400kV GIS 1000058312 85359030 18% OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 400KV GIS MAINTENANCE EARTHSWITCH SET 1 Included 0.00 0 0.00
68 7000030924 550 GIS Portion-Mandatory Spares-400kV GIS 1000058308 85359030 18% OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 400KV GIS FAST EARTHINGSWITCH SET 1 Included 0.00 0 0.00
69 7000030924 560 GIS Portion-Mandatory Spares-400kV GIS 1000049776 85359030 18% LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FORDISCONNECTOR-400KV GIS SET 1 Included 0.00 0 0.00
70 7000030924 570 GIS Portion-Mandatory Spares-400kV GIS 1000049778 85359030 18% LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FORMAINTENANCE EARTHING SWITCH-400KV GIS SET 1 Included 0.00 0 0.00
71 7000030924 580 GIS Portion-Mandatory Spares-400kV GIS 1000049777 85359030 18% LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FOR FASTEARTHING SWITCH (IF APPLICABLE)-400KV GIS SET 1 Included 0.00 0 0.00
72 7000030924 590 GIS Portion-Mandatory Spares-400kV GIS 1000058306 85359030 18% DRIVE MECHANISM FOR 400KV GIS DISCONNECTOR SWITCH SET 1 Included 0.00 0 0.00
73 7000030924 600 GIS Portion-Mandatory Spares-400kV GIS 1000058313 85359030 18% DRIVE MECHANISM FOR 400KV GIS MAINTENANCE EARTH SWITCH SET 1 Included 0.00 0 0.00
74 7000030924 610 GIS Portion-Mandatory Spares-400kV GIS 1000058309 85359030 18% DRIVE MECHANISM FOR 400KV GIS FAST EARTHING SWITCH SET 1 Included 0.00 0 0.00
75 7000030924 620 GIS Portion-Mandatory Spares-400kV GIS 1000058307 85359030 18% MOTOR FOR DRIVE MECHANISM FOR 400KV GIS DISCONNECTOR SWITCH EA 1 Included 0.00 0 0.00
76 7000030924 630 GIS Portion-Mandatory Spares-400kV GIS 1000058315 85359030 18% MOTOR FOR DRIVE MECHANISM FOR 400KVGIS MAINTENANCE EARTH SWITCH EA 1 Included 0.00 0 0.00
77 7000030924 640 GIS Portion-Mandatory Spares-400kV GIS 1000058311 85359030 18% MOTOR FOR DRIVE MECHANISM FOR 400KV GIS FAST EARTHING SWITCH EA 1 Included 0.00 0 0.00
78 7000030924 650 GIS Portion-Mandatory Spares-400kV GIS 1000058327 85359030 18% 400KV GIS- SINGLE PHASE OF CURRENT TRANSFORMER (3 CORES, TYPE-CTA)WITH ASSOCIATED ENCLOSURE AND PRIMARY CONDUCTOR COMPLETE IN ALLRESPECT EA 1 Included 0.00 0 0.00
79 7000030924 660 GIS Portion-Mandatory Spares-400kV GIS 1000058326 85359030 18% 400KV GIS- SINGLE PHASE OF CURRENT TRANSFORMER (2 CORES, TYPE-CTB)WITH ASSOCIATED ENCLOSURE AND PRIMARY CONDUCTOR COMPLETE IN ALLRESPECT EA 1 Included 0.00 0 0.00
80 7000030924 1150 GIS Portion-Mandatory Spares-220kV GIS 1000058295 85359030 18% 220KV GIS- CABLE CONNECTION ENCLOSURE WITH MAIN CIRCUIT SET 1 Included 0.00 0 0.00
81 7000030924 770 GIS Portion-Mandatory Spares-220kV GIS 1000058300 85359030 18% 220KV GIS-SF6 GAS PRESSURE RELIEF DEVICE ASSEMBLY OF EACH TYPE EA 1 Included 0.00 0 0.00
82 7000030924 780 GIS Portion-Mandatory Spares-220kV GIS 1000049816 85359030 18% SF6 PRESSURE GAUGE CUM SWITCH /DENSITY MONITORS AND PRESSURESWITCH AS APPLICABLE, OF EACH TYPE-220KV GIS SET 2 Included 0.00 0 0.00
83 7000030924 790 GIS Portion-Mandatory Spares-220kV GIS 1000049752 85359030 18% COUPLING DEVICE FOR PRESSURE GAUGE CUM SWITCH FOR CONNECTINGGAS HANDLING PLANT OF EACH TYPE-220KV GIS SET 1 Included 0.00 0 0.00
84 7000030924 800 GIS Portion-Mandatory Spares-220kV GIS 1000049761 85359030 18% RUBBER GASKETS, €ŒO€ RINGS AND SEALS FOR SF6 GAS FOR GISENCLOSURE OF EACH TYPE-220KV GIS SET 2 Included 0.00 0 0.00
85 7000030924 810 GIS Portion-Mandatory Spares-220kV GIS 1000058298 85359030 18% 220KV GIS-MOLECULAR FILTER FOR SF6 GAS WITH FILTER BAGS (5 % OF TOTALWEIGHT) SET 1 Included 0.00 0 0.00
86 7000030924 820 GIS Portion-Mandatory Spares-220kV GIS 1000049749 85359030 18% CONTROL VALVES FOR SF6 GAS OF EACH TYPE-220KV GIS SET 2 Included 0.00 0 0.00
87 7000030924 830 GIS Portion-Mandatory Spares-220kV GIS 1000058299 85359030 18% 220KV GIS-SF6 GAS (5 % OF TOTAL GAS QUANTITY) LOT 1 Included 0.00 0 0.00
88 7000030924 840 GIS Portion-Mandatory Spares-220kV GIS 1000049782 85359030 18% LOCKING DEVICE TO KEEP THE DIS-CONNECTORS (ISOLATORS)AND EARTHING/FAST EARTHING SWITCHES (AS APPLICABLE) IN CLOSE OR OPENPOSITION IN CASE OF REMOVAL OF THE DRIVING MECHANISM-220KV GIS SET 2 Included 0.00 0 0.00
89 7000030924 850 GIS Portion-Mandatory Spares-220kV GIS 1000049504 85359030 18% UHF PD SENSORS OF EACH TYPE ALONG WITH BNC CONNECTOR FOR 245KV GIS EA 3 Included 0.00 0 0.00
90 7000030924 860 GIS Portion-Mandatory Spares-220kV GIS 1000058302 85359030 18% 220KV GIS-SUPPORT INSULATORS (GAS THROUGH) OF EACH TYPE (COMPLETE WITHMETAL RING ETC.) ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 3 Included 0.00 0 0.00
91 7000030924 870 GIS Portion-Mandatory Spares-220kV GIS 1000058297 85359030 18% 220KV GIS-GAS BARRIERS OF EACH TYPE (COMPLETE WITH METAL RING ETC.)ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 3 Included 0.00 0 0.00
92 7000030924 880 GIS Portion-Mandatory Spares-220kV GIS 1000058301 85359030 18% 220KV GIS- 1600A SF6 TO AIR BUSHING COMPLETE IN ALL RESPECT EA 1 Included 0.00 0 0.00
93 7000030924 890 GIS Portion-Mandatory Spares-220kV GIS 1000049497 85359030 18% LCC SPARES - AUX. RELAYS, CONTACTORS,PUSH BUTTONS, SWITCHES, LAMPS,ANNUNCIATION WINDOWS, MCB, FUSES,TIMERS, TERMINAL BLOCKS ETC. OF EACHTYPE & RATING-220kV GIS SET 1 Included 0.00 0 0.00
94 7000030924 900 GIS Portion-Mandatory Spares-220kV GIS 1000058284 85359030 18% 220KV GIS-ONE POLE OF 1600A CIRCUIT BREAKER WITH INTERRUPTER, MAINCIRCUIT, ENCLOSURE AND OPERATING MECHANISM COMPLETE IN ALL RESPECT SET 1 Included 0.00 0 0.00
95 7000030924 910 GIS Portion-Mandatory Spares-220kV GIS 1000058285 85359030 18% 220KV GIS-ONE POLE OF 3000A CIRCUIT BREAKER WITH INTERRUPTER, MAINCIRCUIT, ENCLOSURE AND OPERATING MECHANISM COMPLETE IN ALL RESPECT SET 1 Included 0.00 0 0.00
96 7000030924 920 GIS Portion-Mandatory Spares-220kV GIS 1000021871 85389000 18% Trip coil assembly with resistor for245kV GIS Circuit Breaker (asapplicable) SET 3 Included 0.00 0 0.00
97 7000030924 930 GIS Portion-Mandatory Spares-220kV GIS 1000009185 85389000 18% Closing coil assembly with resistor for245kV GIS Circuit Breaker (asapplicable) SET 3 Included 0.00 0 0.00
98 7000030924 940 GIS Portion-Mandatory Spares-220kV GIS 1000058292 85359030 18% RELAYS, POWER CONTACTORS, PUSH BUTTONS, TIMERS & MCBS ETC. (ASAPPLICABLE) OF EACH TYPE FOR 220KV GIS CIRCUIT BREAKER SET 1 Included 0.00 0 0.00
99 7000030924 950 GIS Portion-Mandatory Spares-220kV GIS 1000007066 85389000 18% Auxiliary switch assembly of each type for 245kV GIS Circuit Breaker SET 1 Included 0.00 0 0.00
100 7000030924 960 GIS Portion-Mandatory Spares-220kV GIS 1000058291 85359030 18% 220KV GIS CIRCUIT BREAKER-OPERATION COUNTER EA 1 Included 0.00 0 0.00
101 7000030924 970 GIS Portion-Mandatory Spares-220kV GIS 1000058293 85359030 18% 220KV GIS CIRCUIT BREAKER-COMPLETE SPRING OPERATING MECHANISMINCLUDING CHARGING MECHANISM ETC. (FOR SPRING OPERATED MECHANISM, IFAPPLICABLE) SET 1 Included 0.00 0 0.00
102 7000030924 980 GIS Portion-Mandatory Spares-220kV GIS 1000058371 85359030 18% 220kV GIS- Three phase of 1600Adisconnector switch including maincircuit, enclosure, driving mechanismand support insulator etc., complete inall respect (Note 1- The contractorshall supply spare for disconnectorswitch to ensure one to one replacementof all disconnector switch supplied asmain equipment without any requirementof modification in fittings at site tocover all different types ofdisconnector switch supplied. In case,quantity of supplied dis-connectorswitch types (for one to onereplacement) are more than the quantitymentioned in BPS for spare, thecontractor shall supply theseadditional types of disconnector switchwithout any additional priceimplication to POWERGRID and quantitiesof these additional type ofdisconnector switch are deem to beincluded in the quantities mentioned inBPS for spare disconnector. Note 2 - Incase, Dis-connector Switch (DS) & EarthSwitch (ES) is provided in a sameenclosure with common operatingmechanism, then the module comprisingof Dis-connector & Earth switch insingle enclosure with common operatingmechanism is to be provided under thehead of spare Dis-connector only. Note3- In case, Dis-connector Switch (DS)&Earth Switch (ES) is provided in asame enclosure with separate operatingmechanism, then the module comprisingof Dis-connector & Earth switch insingle enclosure with separateoperating mechanism is to be providedunder the head of spare Dis-connectoronly.) EA 2 Included 0.00 0 0.00
103 7000030924 990 GIS Portion-Mandatory Spares-220kV GIS 1000058373 85359030 18% 220kV GIS- Three phase of 3000Adisconnector switch including maincircuit, enclosure, driving mechanismand support insulator etc., complete inall respect (Note 1- The contractorshall supply spare for disconnectorswitch to ensure one to one replacementof all disconnector switch supplied asmain equipment without any requirementof modification in fittings at site tocover all different types ofdisconnector switch supplied. In case,quantity of supplied dis-connectorswitch types (for one to onereplacement) are more than the quantitymentioned in BPS for spare, thecontractor shall supply theseadditional types of disconnector switchwithout any additional priceimplication to POWERGRID and quantitiesof these additional type ofdisconnector switch are deem to beincluded in the quantities mentioned inBPS for spare disconnector. Note 2 - Incase, Dis-connector Switch (DS) & EarthSwitch (ES) is provided in a sameenclosure with common operatingmechanism, then the module comprisingof Dis-connector & Earth switch insingle enclosure with common operatingmechanism is to be provided under thehead of spare Dis-connector only. Note3- In case, Dis-connector Switch (DS)&Earth Switch (ES) is provided in asame enclosure with separate operatingmechanism, then the module comprisingof Dis-connector & Earth switch insingle enclosure with separateoperating mechanism is to be providedunder the head of spare Dis-connectoronly.) EA 1 Included 0.00 0 0.00
104 7000030924 1000 GIS Portion-Mandatory Spares-220kV GIS 1000058282 85359030 18% 220KV GIS- THREE PHASE MAINTENANCE EARTHING SWITCH INCLUDING MAINCIRCUIT, ENCLOSURE, DRIVING MECHANISM AND SUPPORT INSULATOR ETC.,COMPLETE IN ALL RESPECT (NOTE 1 - IN CASE, DIS-CONNECTOR SWITCH (DS) &EARTH SWITCH (ES) IS PROVIDED IN A SAME ENCLOSURE WITH COMMONOPERATING MECHANISM, THEN THE MODULE COMPRISING OF DIS-CONNECTOR &EARTH SWITCH IN SINGLE ENCLOSURE WITH COMMON OPERATING MECHANISM IS TOBE PROVIDED UNDER THE HEAD OF SPARE DIS-CONNECTOR ONLY. NOTE 2 - INCASE, DIS-CONNECTOR SWITCH (DS) & EARTH SWITCH (ES) IS PROVIDED IN ASAME ENCLOSURE WITH SEPARATE OPERATING MECHANISM, THEN THE MODULECOMPRISING OF DIS-CONNECTOR & EARTH SWITCH IN SINGLE ENCLOSURE WITHSEPARATE OPERATING MECHANISM IS TO BE PROVIDED UNDER THE HEAD OF SPAREDIS-CONNECTOR ONLY.) EA 1 Included 0.00 0 0.00
105 7000030924 1010 GIS Portion-Mandatory Spares-220kV GIS 1000058278 85359030 18% 220KV GIS - THREE PHASE FAST EARTHING SWITCH INCLUDING MAIN CIRCUIT,ENCLOSURE, DRIVING MECHANISM AND SUPPORT INSULATOR ETC., COMPLETE INALL RESPECT (NOTE 1 - IN CASE, DIS-CONNECTOR SWITCH (DS) & EARTHSWITCH (ES) IS PROVIDED IN A SAME ENCLOSURE WITH COMMON OPERATINGMECHANISM, THEN THE MODULE COMPRISING OF DIS-CONNECTOR & EARTH SWITCHIN SINGLE ENCLOSURE WITH COMMON OPERATING MECHANISM IS TO BE PROVIDEDUNDER THE HEAD OF SPARE DIS-CONNECTOR ONLY. NOTE 2 - IN CASE,DIS-CONNECTOR SWITCH (DS) & EARTH SWITCH (ES) IS PROVIDED IN A SAMEENCLOSURE WITH SEPARATE OPERATING MECHANISM, THEN THE MODULECOMPRISING OF DIS-CONNECTOR & EARTH SWITCH IN SINGLE ENCLOSURE WITHSEPARATE OPERATING MECHANISM IS TO BE PROVIDED UNDER THE HEAD OF SPAREDIS-CONNECTOR ONLY.) EA 1 Included 0.00 0 0.00
106 7000030924 1020 GIS Portion-Mandatory Spares-220kV GIS 1000058273 85359030 18% OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 220KV GIS DISCONNECTORSWITCH SET 1 Included 0.00 0 0.00
107 7000030924 1030 GIS Portion-Mandatory Spares-220kV GIS 1000058280 85359030 18% OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 220KV GIS MAINTENANCE EARTHSWITCH SET 1 Included 0.00 0 0.00
108 7000030924 1040 GIS Portion-Mandatory Spares-220kV GIS 1000058276 85359030 18% OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 220KV GIS FAST EARTHINGSWITCH SET 1 Included 0.00 0 0.00
109 7000030924 1050 GIS Portion-Mandatory Spares-220kV GIS 1000049773 85359030 18% LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FORDISCONNECTOR-220KV GIS SET 1 Included 0.00 0 0.00
110 7000030924 1060 GIS Portion-Mandatory Spares-220kV GIS 1000049775 85359030 18% LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FORMAINTENANCE EARTHING SWITCH-220KV GIS SET 1 Included 0.00 0 0.00
111 7000030924 1070 GIS Portion-Mandatory Spares-220kV GIS 1000049774 85359030 18% LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FOR FASTEARTHING SWITCH (IF APPLICABLE)-220KV GIS SET 1 Included 0.00 0 0.00
112 7000030924 1080 GIS Portion-Mandatory Spares-220kV GIS 1000058274 85359030 18% DRIVE MECHANISM FOR 220KV GIS DISCONNECTOR SWITCH SET 1 Included 0.00 0 0.00
113 7000030924 1090 GIS Portion-Mandatory Spares-220kV GIS 1000058281 85359030 18% DRIVE MECHANISM FOR 220KV GIS MAINTENANCE EARTH SWITCH SET 1 Included 0.00 0 0.00
114 7000030924 1100 GIS Portion-Mandatory Spares-220kV GIS 1000058277 85359030 18% DRIVE MECHANISM FOR 220KV GIS FAST EARTHING SWITCH SET 1 Included 0.00 0 0.00
115 7000030924 1110 GIS Portion-Mandatory Spares-220kV GIS 1000058275 85359030 18% MOTOR FOR DRIVE MECHANISM FOR 220KV GIS DISCONNECTOR SWITCH EA 1 Included 0.00 0 0.00
116 7000030924 1120 GIS Portion-Mandatory Spares-220kV GIS 1000058283 85359030 18% MOTOR FOR DRIVE MECHANISM FOR 220KVGIS MAINTENANCE EARTH SWITCH EA 1 Included 0.00 0 0.00
117 7000030924 1130 GIS Portion-Mandatory Spares-220kV GIS 1000058279 85359030 18% MOTOR FOR DRIVE MECHANISM FOR 220KV GIS FAST EARTHING SWITCH EA 1 Included 0.00 0 0.00
118 7000030924 1160 GIS Portion-Mandatory Spares-220kV GIS 1000075085 85359030 18% 220KV GIS- SINGLE PHASE OF CURRENT TRANSFORMER (5 CORES) WITHASSOCIATED ENCLOSURE AND PRIMARY CONDUCTOR COMPLETE IN ALL RESPECT EA 2 Included 0.00 0 0.00
119 7000030924 1140 GIS Portion-Mandatory Spares-220kV GIS 1000058296 85359030 18% 220KV GIS- SINGLE PHASE VT WITH ASSOCIATED ENCLOSURE COMPLETE IN ALLRESPECT EA 1 Included 0.00 0 0.00
120 7000030924 1330 Supply of non standard structure 1000015954 73082011 18% Fabrication, galvanising and supply of Lattice Structures (MS Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 146 Included 0.00 0 0.00
121 7000030924 1340 Supply of non standard structure 1000015953 73082011 18% Fabrication, galvanising and supply of Lattice Structures (HT Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 5 Included 0.00 0 0.00
122 7000030924 1350 Supply of non standard structure 1000011713 73082011 18% Fabrication, galvanising and supply of fasteners ( nuts, bolts andwashers ) including step bolts for lattice and pipe structures to bedesigned during detailed engineering MT 6 Included 0.00 0 0.00
123 7000030924 1360 Supply of non standard structure 1000012373 73082011 18% Fabrication, galvanising and supply of foundation bolts including nuts,checknut and washers for lattice and pipe structures to be designedduring detailed engineering MT 22 Included 0.00 0 0.00
124 7000030924 1370 Supply-Tele eqpt 1000066613 83071000 18% GI FLEXIBLE CONDUIT INSTALLATION HARDWARE FOR APPROAH CABLING EA 24 Included 0.00 0 0.00
125 7000030924 1380 Supply-Tele eqpt 1000066612 73071900 18% GI ELBOW INSTALLATION HARDWARE FOR APPROAH CABLING EA 32 Included 0.00 0 0.00
126 7000030924 1390 Supply-Tele eqpt 1000066614 73069011 18% GI PIPE INSTALLATION HARDWARE FOR APPROACH CABLING KM 4 Included 0.00 0 0.00
127 7000030924 1400 Supply-Tele eqpt 1000026228 85176290 18% Equipment Cabinets For SDH EA 1 Included 0.00 0 0.00
128 7000030924 1410 Supply-Tele eqpt 1000031381 85176290 18% TRIBUTARY INTERFACE-GIGABIT ETHERNET INTERFACES 10/100 MBPS WITH LAYER-2 SWITCHING (MINIMUM 2 NOS.) SET 2 Included 0.00 0 0.00
129 7000030924 1420 Supply-Tele eqpt 1000034950 85176990 18% ETHERNET INTERFACE 10/100 BASE T WITH LAYER-2 SWITCHING (MIN 8INTERFACES PER CARD) EA 4 Included 0.00 0 0.00
130 7000030924 1430 Supply-Tele eqpt 1000031374 85176290 18% TRIBUTARY INTERFACE- E1 INTERFACE (MINIMUM 16 NOS.) SET 4 Included 0.00 0 0.00
132 7000030924 1450 Supply-Tele eqpt 1000031367 85176260 18% SDH EQUIPMENT (STM-16 MADM UPTO 5 MSP PROTECTED DIRECTIONS)-BASEEQUIPMENT (COMMON CARDS, CROSS CONNECT/CONTROL CARDS, OPTICAL BASECARDS, POWER SUPPLY CARDS, POWER CABLING, OTHER HARDWARE ANDACCESSORIES INCLUDING SUB RACKS, PATCH CORD, DDF ETC FULLY EQUIPEDEXCLUDING OPTICAL INTERFACE & TRIBUTARY CARDS EA 2 Included 0.00 0 0.00
133 7000030924 1460 Supply-Tele eqpt 1000037546 85447090 18% 48F (DWSM) APPROACH FIBRE OPTIC CABLE KM 4 Included 0.00 0 0.00
134 7000030924 1470 Supply-Tele eqpt 1000076844 85372000 18% 192 FIBRE FODP : INDOOR TYPE, RACK MOUNTED WITH FCPC COUPLING & PIGTAILS(5MTRS) EA 2 Included 0.00 0 0.00
135 7000030924 1480 Spares- Tele eqpt 1000066613 83071000 18% GI FLEXIBLE CONDUIT INSTALLATION HARDWARE FOR APPROAH CABLING EA 1 Included 0.00 0 0.00
136 7000030924 1490 Spares- Tele eqpt 1000066612 73071900 18% GI ELBOW INSTALLATION HARDWARE FOR APPROAH CABLING EA 1 Included 0.00 0 0.00
137 7000030924 1500 Spares- Tele eqpt 1000066614 73069011 18% GI PIPE INSTALLATION HARDWARE FOR APPROACH CABLING KM 0.14 Included 0.00 0 0.00
138 7000030924 1510 Spares- Tele eqpt 1000031398 85171890 18% PRE CONNECTORIZED OPTICAL FIBER PATCH CORDS(10 MTRS) – PACK OF SIXPATCH CORDS SET 1 Included 0.00 0 0.00
139 7000030924 1520 Spares- Tele eqpt 1000031381 85176290 18% TRIBUTARY INTERFACE-GIGABIT ETHERNET INTERFACES 10/100 MBPS WITH LAYER-2 SWITCHING (MINIMUM 2 NOS.) SET 1 Included 0.00 0 0.00
140 7000030924 1530 Spares- Tele eqpt 1000034950 85176990 18% ETHERNET INTERFACE 10/100 BASE T WITH LAYER-2 SWITCHING (MIN 8INTERFACES PER CARD) EA 1 Included 0.00 0 0.00
141 7000030924 1540 Spares- Tele eqpt 1000031374 85176290 18% TRIBUTARY INTERFACE- E1 INTERFACE (MINIMUM 16 NOS.) SET 1 Included 0.00 0 0.00
143 7000030924 1560 Spares- Tele eqpt 1000031369 85176260 18% SDH EQUIPMENT (STM-16 MADM UPTO 5 MSP PROTECTED DIRECTIONS)-COMMONCARDS, CROSS-CONNECT/CONTROL CARDS, OPTICAL BASE CARD, POWER SUPPLYCARDS, POWER CABLING, OTHER HARDWARE & ACCESSORIES (EACH). SET 1 Included 0.00 0 0.00
144 7000030924 1570 Spares- Tele eqpt 1000037546 85447090 18% 48F (DWSM) APPROACH FIBRE OPTIC CABLE KM 1 Included 0.00 0 0.00
D SS EXTN-400/220kV ICT(10th) AT BHUJ PS Revaluation of J column Tax Calculation
1 7000030914 10 400 kV & 220 kV AIS EQUIPMENT 1000020419 85354010 18% 336kV Surge Arrester (1-phase) EA 3 Included 0.00 0 0.00
2 7000030914 20 400 kV & 220 kV AIS EQUIPMENT 1000020417 85354010 18% 216kV Surge Arrester (1-phase) EA 3 Included 0.00 0 0.00
3 7000030914 30 400 kV & 220 kV AIS EQUIPMENT 1000001695 85462040 18% 245 kV, 1 phase Bus Post Insulator (except for Line Traps) EA 22 Included 0.00 0 0.00
4 7000030914 40 400 kV & 220 kV AIS EQUIPMENT 1000004401 85462040 18% 420 kV, 1 phase Bus Post Insulator (except for Line Traps) EA 3 Included 0.00 0 0.00
5 7000030914 50 400 kV & 220 kV AIS EQUIPMENT 1000004498 85353090 18% 420kV, 3150A, 63KA, Isolator (3-phase)(Double Break) with one E/S EA 2 Included 0.00 0 0.00
6 7000030914 60 400 kV & 220 kV AIS EQUIPMENT 1000004501 85352913 18% 420kV, 3150A, 63kA Circuit Breaker (3-Phase) without closing resistorand with Support Structure EA 1 Included 0.00 0 0.00
7 7000030914 70 400 kV & 220 kV AIS EQUIPMENT 1000004463 85359090 18% 420 kV, 3000A, 63KA, 1-Phase CurrentTransformer with 120% extended currentrating EA 3 Included 0.00 0 0.00
8 7000030914 80 400 kV & 220 kV AIS EQUIPMENT 1000009713 85389000 18% Controlled Switching Device for 420 kV, 3-ph Circuit Breaker EA 1 Included 0.00 0 0.00
9 7000030914 90 GIS Portion-220 kV GIS Equipment 1000029503 85389000 18% 245kV, 1600A, 50kA Single phase SF6 to Air Bushing EA 6 Included 0.00 0 0.00
10 7000030914 100 GIS Portion-220 kV GIS Equipment 1000001693 85389000 18% 245kV,1600A, 50kA,3 Single phase/3Phase, SF6 Gas Insulated Bus Duct (GIB)outside GIS Hall alongwith associatedsupport structure(Quantity mentionedhere is for 3 Phase type) M 400 Included 0.00 0 0.00
11 7000030914 110 Erection Hardware (400kV & 220 kV) 1000011320 72169990 18% Erection Hardware for 400kV I type layout-Any feeder Extn. on existinghalf dia. as per technical specification SET 1 Included 0.00 0 0.00
12 7000030914 120 Erection Hardware (400kV & 220 kV) 1000029216 72169990 18% Erection Hardware for 220kV DM type layout-Transformer bay as pertechnical specification SET 1 Included 0.00 0 0.00
13 7000030914 250 CONTROL & RELAY PANEL 1000004274 85371000 18% 400kV Transformer Protection Panel (For both HV & MV side)-(withAutomation) EA 1 Included 0.00 0 0.00
14 7000030914 260 CONTROL & RELAY PANEL 1000001167 85371000 18% Augmentation of existing 220kV bus bar protection scheme.(No. of baysas per specification)-(with Automation) SET 1 Included 0.00 0 0.00
15 7000030914 270 CONTROL & RELAY PANEL 1000055443 85371000 18% 220KV CIRCUIT BREAKER RELAY PANEL (WITH AUTOMATION) EA 1 Included 0.00 0 0.00
16 7000030914 280 CONTROL & RELAY PANEL 1000055446 85371000 18% 400KV CIRCUIT BREAKER RELAY PANEL (WITH AUTOMATION) EA 1 Included 0.00 0 0.00
17 7000030914 600 SUBSTATION AUTOMATION SYSTEM 1000001333 85371000 18% Augmentation of Substation automation System for 220kV bay as perTechnical Specification EA 1 Included 0.00 0 0.00
18 7000030914 610 SUBSTATION AUTOMATION SYSTEM 1000003409 85371000 18% Augmentation of Substation automation System for 400kV Main bay as perTechnical Specification EA 1 Included 0.00 0 0.00
19 7000030914 290 ILLUMINATION SYSTEM (OUTDOOR) 1000014547 85371000 18% Lighting Panel type ACP-2 as per technical specification EA 1 Included 0.00 0 0.00
20 7000030914 300 ILLUMINATION SYSTEM (OUTDOOR) 1000020262 85371000 18% Sub Lighting panel (outdoor) type SLP (Switchyard and Street Lighting) EA 2 Included 0.00 0 0.00
21 7000030914 310 ILLUMINATION SYSTEM (OUTDOOR) 1000038039 94051090 18% LIGHTING FIXTURE LED LUMINAIRES TYPE FL-1 AS PER TECH. SPECIFICATIONS EA 8 Included 0.00 0 0.00
22 7000030914 320 ILLUMINATION SYSTEM (OUTDOOR) 1000038325 94059900 18% LIGHTING FIXTURE LED LUMINAIRES TYPE FL2 AS PER TECH. SPECIFICATIONS EA 8 Included 0.00 0 0.00
23 7000030914 330 Power & Control cables 1000000443 85446020 18% 1.1kV grade Power Cables (PVCinsulated)along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0.00
24 7000030914 340 Power & Control cables 1000000442 85446020 18% 1.1kV grade Control Cables (PVCinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0.00
25 7000030914 350 Power & Control cables 1000000444 85446090 18% 1.1kV grade Power Cables (XLPEinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0.00
26 7000030914 360 FIRE PROTECTION SYSTEM 1000012069 84248990 18% HVW spray system, Hydrant system and complete U/G & O/G piping andaccessories etc. out side the pump house for 500MVA , 400KV/220/33kV, 3-phase Autotransformer SET 1 Included 0.00 0 0.00
27 7000030914 370 FIRE PROTECTION SYSTEM 1000055457 84248990 18% HVW SPRAY SYSTEM, HYDRANT SYSTEM AND COMPLETE U/G & O/G PIPING ANDACCESSORIES ETC. OUT SIDE THE PUMP HOUSE FOR 420KV 3 PHASE BUSREACTOR SET 1 Included 0.00 0 0.00
28 7000030914 380 VISUAL MONITORING SYSTEM 1000030433 85287390 18% COLOR IP CAMERA, WITH PAN, TILT AND ZOOM FACILITIES, ALONGWITH ALLREQUIRED ITEMS, ACCESSORIES, LINE INTERFACE UNITS, FIBER PATCH CORDS,POWER SUPPLY UNITS, JUNCTION BOXES, CABLES, FIBER OPTIC CABLES, ETC.,AND INCLUDING INTEGRATION IN EXISTING HARDWARE AND SOFTWARE FORAUGMENTATION OF VISUAL MONITORING SYSTEM AS PER TECHNICALSPECIFICATION. SET 1 Included 0.00 0 0.00
29 7000030914 470 220 kV HYBRID GIS 1000045815 85389000 18% 245KV, 1600 A, DM TYPE SF6 MTS/HYBRID GIS ICT/LINEFEEDER BAYSWITCHGEAR ASSEMBLY AS PER SECTION-PROJECT, TECHNICAL SPECIFICATION EA 1 Included 0.00 0 0.00
30 7000030914 480 Main Earthmat 1000032055 72159090 18% 40 MM MS ROD FOR MAIN EARTHMAT KM 1 Included 0.00 0 0.00
31 7000030914 130 GIS Portion-Mandatory Spares-220kV GIS 1000058300 85359030 18% 220KV GIS-SF6 GAS PRESSURE RELIEF DEVICE ASSEMBLY OF EACH TYPE EA 1 Included 0.00 0 0.00
32 7000030914 140 GIS Portion-Mandatory Spares-220kV GIS 1000049816 85359030 18% SF6 PRESSURE GAUGE CUM SWITCH /DENSITY MONITORS AND PRESSURESWITCH AS APPLICABLE, OF EACH TYPE-220KV GIS SET 2 Included 0.00 0 0.00
33 7000030914 150 GIS Portion-Mandatory Spares-220kV GIS 1000049752 85359030 18% COUPLING DEVICE FOR PRESSURE GAUGE CUM SWITCH FOR CONNECTINGGAS HANDLING PLANT OF EACH TYPE-220KV GIS SET 1 Included 0.00 0 0.00
34 7000030914 160 GIS Portion-Mandatory Spares-220kV GIS 1000049761 85359030 18% RUBBER GASKETS, €ŒO€ RINGS AND SEALS FOR SF6 GAS FOR GISENCLOSURE OF EACH TYPE-220KV GIS SET 2 Included 0.00 0 0.00
35 7000030914 170 GIS Portion-Mandatory Spares-220kV GIS 1000058298 85359030 18% 220KV GIS-MOLECULAR FILTER FOR SF6 GAS WITH FILTER BAGS (5 % OF TOTALWEIGHT) SET 1 Included 0.00 0 0.00
36 7000030914 180 GIS Portion-Mandatory Spares-220kV GIS 1000049749 85359030 18% CONTROL VALVES FOR SF6 GAS OF EACH TYPE-220KV GIS SET 2 Included 0.00 0 0.00
37 7000030914 190 GIS Portion-Mandatory Spares-220kV GIS 1000058299 85359030 18% 220KV GIS-SF6 GAS (5 % OF TOTAL GAS QUANTITY) LOT 1 Included 0.00 0 0.00
38 7000030914 200 GIS Portion-Mandatory Spares-220kV GIS 1000049504 85359030 18% UHF PD SENSORS OF EACH TYPE ALONG WITH BNC CONNECTOR FOR 245KV GIS EA 3 Included 0.00 0 0.00
39 7000030914 210 GIS Portion-Mandatory Spares-220kV GIS 1000058302 85359030 18% 220KV GIS-SUPPORT INSULATORS (GAS THROUGH) OF EACH TYPE (COMPLETE WITHMETAL RING ETC.) ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 3 Included 0.00 0 0.00
40 7000030914 220 GIS Portion-Mandatory Spares-220kV GIS 1000058297 85359030 18% 220KV GIS-GAS BARRIERS OF EACH TYPE (COMPLETE WITH METAL RING ETC.)ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 3 Included 0.00 0 0.00
41 7000030914 230 GIS Portion-Mandatory Spares-220kV GIS 1000058301 85359030 18% 220KV GIS- 1600A SF6 TO AIR BUSHING COMPLETE IN ALL RESPECT EA 1 Included 0.00 0 0.00
42 7000030914 240 GIS Portion-Mandatory Spares-220kV GIS 1000049497 85359030 18% LCC SPARES - AUX. RELAYS, CONTACTORS,PUSH BUTTONS, SWITCHES, LAMPS,ANNUNCIATION WINDOWS, MCB, FUSES,TIMERS, TERMINAL BLOCKS ETC. OF EACHTYPE & RATING-220kV GIS SET 1 Included 0.00 0 0.00
43 7000030914 390 MANDATORY SPARES-AIS 1000019912 85371000 18% Relay & protection Panels (with automation) LS 1 Included 0.00 0 0.00
44 7000030914 400 MANDATORY SPARES-AIS 1000019925 84819090 18% Spares for Fire Protection System LS 1 Included 0.00 0 0.00
45 7000030914 410 MANDATORY SPARES-AIS 1000024186 85354010 18% SPARES FOR 336KV SURGE ARRESTER LS 1 Included 0.00 0 0.00
46 7000030914 440 MANDATORY SPARES-AIS 1000019918 85359090 18% Spares for 420kV Circuit Breaker LS 1 Included 0.00 0 0.00
47 7000030914 450 MANDATORY SPARES-AIS 1000025941 85389000 18% Spare-420kV CT 1 SET 1 Included 0.00 0 0.00
48 7000030914 460 MANDATORY SPARES-AIS 1000019919 85353090 18% Spares for 420kV Double break Isolator LS 1 Included 0.00 0 0.00
49 7000030914 430 MANDATORY SPARES-AIS 1000025934 85359090 18% Spare-245kV CVT SET 1 Included 0.00 0 0.00
50 7000030914 420 MANDATORY SPARES-AIS 1000025930 85354010 18% Spare-216kV Surge Arrester SET 1 Included 0.00 0 0.00
51 7000030914 630 MANDATORY SPARES FOR SAS-AIS 1000062002 85371000 18% BAY CONTROL UNIT (IED) OF MAIN SYSTEM EA 1 Included 0.00 0 0.00
52 7000030914 640 MANDATORY SPARES FOR SAS-AIS 1000062004 85371000 18% ETHERNET SWITCH SUITABLE FOR 19€ RACK MOUNTING WITH 24 FIBER OPTICPORTS EA 1 Included 0.00 0 0.00
53 7000030914 670 Non-Standard structures-Supply 1000015954 73082011 18% Fabrication, galvanising and supply of Lattice Structures (MS Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 30 Included 0.00 0 0.00
54 7000030914 680 Non-Standard structures-Supply 1000011713 73082011 18% Fabrication, galvanising and supply of fasteners ( nuts, bolts andwashers ) including step bolts for lattice and pipe structures to bedesigned during detailed engineering MT 1 Included 0.00 0 0.00
55 7000030914 690 Non-Standard structures-Supply 1000012373 73082011 18% Fabrication, galvanising and supply of foundation bolts including nuts,checknut and washers for lattice and pipe structures to be designedduring detailed engineering MT 3 Included 0.00 0 0.00
56 7000030914 700 PMUs for Bhuj PS 1000017518 85364900 18% PMU with GPS Clock (clock can be either internal or external) EA 2 Included 0.00 0 0.00
57 7000030914 710 PMUs for Bhuj PS 1000022512 90311000 18% WAMS Hardware - Time System (GPS receiver) EA 2 Included 0.00 0 0.00
58 7000030914 720 PMUs for Bhuj PS 1000071061 85176290 18% SUBSTATION GRADE LAYER 2 LAN SWITCH EA 2 Included 0.00 0 0.00
59 7000030914 730 PMUs for Bhuj PS 1000071062 85176290 18% SUBSTATION GRADE LAYER 3 LAN SWITCH EA 1 Included 0.00 0 0.00
60 7000030914 740 PMUs for Bhuj PS 1000022487 85447090 18% WAMS Miscellaneous - Armored Fibre Optic Cable and associatedtermination (e.g. L2 Switch) for connecting PMU panels located indifferent control room of a station EA 1 Included 0.00 0 0.00
61 7000030914 750 PMUs for Bhuj PS 1000030641 85389000 18% LIU - FO PATCH PANEL-12 PORT EA 3 Included 0.00 0 0.00
E 220kV line bays at Bhuj PS
1 7000030914 780 220 kV AIS EQUIPMENT 1000001772 85359090 18% 245 kV, 4400pf Capacitive Voltage Transformer (1- Phase) EA 6 Included 0.00 0 0.00
2 7000030914 790 220 kV AIS EQUIPMENT 1000020417 85354010 18% 216kV Surge Arrester (1-phase) EA 6 Included 0.00 0 0.00
3 7000030914 800 220 kV AIS EQUIPMENT 1000001695 85462040 18% 245 kV, 1 phase Bus Post Insulator (except for Line Traps) EA 32 Included 0.00 0 0.00
4 7000030914 810 220 kV AIS EQUIPMENT 1000001567 85176210 18% 220kV, 1600A, 0.5mH, 40 kA Line Trap EA 4 Included 0.00 0 0.00
5 7000030914 820 220 kV AIS EQUIPMENT 1000001694 85462040 18% 245 kV ,1 phase Bus Post Insulators for Line Traps EA 12 Included 0.00 0 0.00
6 7000030914 770 220 kV HYBRID GIS 1000045815 85389000 18% 245KV, 1600 A, DM TYPE SF6 MTS/HYBRID GIS ICT/LINEFEEDER BAYSWITCHGEAR ASSEMBLY AS PER SECTION-PROJECT, TECHNICAL SPECIFICATION EA 2 Included 0.00 0 0.00
7 7000030914 890 Erection Hardware (220kV) 1000033099 72169990 18% ERECTION HARDWARE FOR 220KV LAYOUT (DOUBLE MAIN SCHEME)-LINE BAY ASPER TECHNICAL SPECIFICATION SET 2 Included 0.00 0 0.00
8 7000030914 830 CONTROL & RELAY PANEL 1000001167 85371000 18% Augmentation of existing 220kV bus bar protection scheme.(No. of baysas per specification)-(with Automation) SET 1 Included 0.00 0 0.00
9 7000030914 840 CONTROL & RELAY PANEL 1000001330 85371000 18% 220kV Line Protection Panel (with Automation) EA 2 Included 0.00 0 0.00
10 7000030914 850 CONTROL & RELAY PANEL 1000055443 85371000 18% 220KV CIRCUIT BREAKER RELAY PANEL (WITH AUTOMATION) EA 2 Included 0.00 0 0.00
11 7000030914 1320 SUBSTATION AUTOMATION SYSTEM 1000001333 85371000 18% Augmentation of Substation automation System for 220kV bay as perTechnical Specification EA 2 Included 0.00 0 0.00
12 7000030914 860 Illumination System (Outdoor) 1000014547 85371000 18% Lighting Panel type ACP-2 as per technical specification EA 1 Included 0.00 0 0.00
13 7000030914 870 Illumination System (Outdoor) 1000038039 94051090 18% LIGHTING FIXTURE LED LUMINAIRES TYPE FL-1 AS PER TECH. SPECIFICATIONS EA 10 Included 0.00 0 0.00
14 7000030914 880 Illumination System (Outdoor) 1000038325 94059900 18% LIGHTING FIXTURE LED LUMINAIRES TYPE FL2 AS PER TECH. SPECIFICATIONS EA 10 Included 0.00 0 0.00
15 7000030914 900 POWER & CONTROL CABLE 1000000442 85446020 18% 1.1kV grade Control Cables (PVCinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0.00
16 7000030914 910 POWER & CONTROL CABLE 1000000443 85446020 18% 1.1kV grade Power Cables (PVCinsulated)along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0.00
17 7000030914 920 AC+FIRE PROTN+ILLUM FOR SPR 1000006284 84151090 28% Air conditioning system for Switchyard Panel Room of 6m length SET 1 Included 0.00 0 0.00
18 7000030914 930 AC+FIRE PROTN+ILLUM FOR SPR 1000012022 84241000 18% 4.5 kg CO2 type Portable Fire extinguisher EA 2 Included 0.00 0 0.00
19 7000030914 940 AC+FIRE PROTN+ILLUM FOR SPR 1000012018 85311020 18% Fire Detection and Alarm System for Switchyard Panel Room of 6 mlength SET 1 Included 0.00 0 0.00
20 7000030914 950 AC+FIRE PROTN+ILLUM FOR SPR 1000013795 94059900 18% Illumination System for switchyard panel room of 6 m length LS 1 Included 0.00 0 0.00
21 7000030914 960 Main Earthmat 1000032055 72159090 18% 40 MM MS ROD FOR MAIN EARTHMAT KM 1 Included 0.00 0 0.00
22 7000030914 970 MANDATORY SPARES-220 kV HYBRID GIS 1000045815 85389000 18% 245KV, 1600 A, DM TYPE SF6 MTS/HYBRID GIS ICT/LINEFEEDER BAYSWITCHGEAR ASSEMBLY AS PER SECTION-PROJECT, TECHNICAL SPECIFICATION EA 1 Included 0.00 0 0.00
23 7000030914 980 MANDATORY SPARES-220 kV HYBRID GIS 1000049497 85359030 18% LCC SPARES - AUX. RELAYS, CONTACTORS,PUSH BUTTONS, SWITCHES, LAMPS,ANNUNCIATION WINDOWS, MCB, FUSES,TIMERS, TERMINAL BLOCKS ETC. OF EACHTYPE & RATING-220kV GIS SET 2 Included 0.00 0 0.00
24 7000030914 990 MANDATORY SPARES-220 kV HYBRID GIS 1000049774 85359030 18% LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FOR FASTEARTHING SWITCH (IF APPLICABLE)-220KV GIS SET 1 Included 0.00 0 0.00
25 7000030914 1000 MANDATORY SPARES-220 kV HYBRID GIS 1000049775 85359030 18% LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FORMAINTENANCE EARTHING SWITCH-220KV GIS SET 1 Included 0.00 0 0.00
26 7000030914 1010 MANDATORY SPARES-220 kV HYBRID GIS 1000049773 85359030 18% LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FORDISCONNECTOR-220KV GIS SET 1 Included 0.00 0 0.00
27 7000030914 1020 MANDATORY SPARES-220 kV HYBRID GIS 1000058276 85359030 18% OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 220KV GIS FAST EARTHINGSWITCH SET 1 Included 0.00 0 0.00
28 7000030914 1030 MANDATORY SPARES-220 kV HYBRID GIS 1000058280 85359030 18% OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 220KV GIS MAINTENANCE EARTHSWITCH SET 1 Included 0.00 0 0.00
29 7000030914 1040 MANDATORY SPARES-220 kV HYBRID GIS 1000058273 85359030 18% OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 220KV GIS DISCONNECTORSWITCH SET 1 Included 0.00 0 0.00
30 7000030914 1050 MANDATORY SPARES-220 kV HYBRID GIS 1000049801 85359030 18% PRESSURE GAUGE WITH COUPLING DEVICE OF EACH TYPE (FOR HYDRAULIC-SPRINGOPERATED MECHANISM, IF APPLICABLE)-220KV GIS CIRCUIT BREKAER SET 1 Included 0.00 0 0.00
31 7000030914 1060 MANDATORY SPARES-220 kV HYBRID GIS 1000049797 85359030 18% PRESSURE SWITCHES OF EACH TYPE (FOR HYDRAULIC-SPRING OPERATEDMECHANISM, IF APPLICABLE)-220KV GIS CIRCUIT BREAKER SET 1 Included 0.00 0 0.00
32 7000030914 1070 MANDATORY SPARES-220 kV HYBRID GIS 1000058293 85359030 18% 220KV GIS CIRCUIT BREAKER-COMPLETE SPRING OPERATING MECHANISMINCLUDING CHARGING MECHANISM ETC. (FOR SPRING OPERATED MECHANISM, IFAPPLICABLE) SET 1 Included 0.00 0 0.00
33 7000030914 1080 MANDATORY SPARES-220 kV HYBRID GIS 1000058291 85359030 18% 220KV GIS CIRCUIT BREAKER-OPERATION COUNTER EA 3 Included 0.00 0 0.00
34 7000030914 1090 MANDATORY SPARES-220 kV HYBRID GIS 1000007066 85389000 18% Auxiliary switch assembly of each type for 245kV GIS Circuit Breaker SET 1 Included 0.00 0 0.00
35 7000030914 1100 MANDATORY SPARES-220 kV HYBRID GIS 1000058292 85359030 18% RELAYS, POWER CONTACTORS, PUSH BUTTONS, TIMERS & MCBS ETC. (ASAPPLICABLE) OF EACH TYPE FOR 220KV GIS CIRCUIT BREAKER SET 1 Included 0.00 0 0.00
36 7000030914 1110 MANDATORY SPARES-220 kV HYBRID GIS 1000009185 85389000 18% Closing coil assembly with resistor for245kV GIS Circuit Breaker (asapplicable) SET 3 Included 0.00 0 0.00
37 7000030914 1120 MANDATORY SPARES-220 kV HYBRID GIS 1000021871 85389000 18% Trip coil assembly with resistor for245kV GIS Circuit Breaker (asapplicable) SET 3 Included 0.00 0 0.00
38 7000030914 1130 MANDATORY SPARES-220 kV HYBRID GIS 1000058301 85359030 18% 220KV GIS- 1600A SF6 TO AIR BUSHING COMPLETE IN ALL RESPECT EA 1 Included 0.00 0 0.00
39 7000030914 1140 MANDATORY SPARES-220 kV HYBRID GIS 1000058297 85359030 18% 220KV GIS-GAS BARRIERS OF EACH TYPE (COMPLETE WITH METAL RING ETC.)ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 2 Included 0.00 0 0.00
40 7000030914 1150 MANDATORY SPARES-220 kV HYBRID GIS 1000058302 85359030 18% 220KV GIS-SUPPORT INSULATORS (GAS THROUGH) OF EACH TYPE (COMPLETE WITHMETAL RING ETC.) ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 2 Included 0.00 0 0.00
41 7000030914 1160 MANDATORY SPARES-220 kV HYBRID GIS 1000049782 85359030 18% LOCKING DEVICE TO KEEP THE DIS-CONNECTORS (ISOLATORS)AND EARTHING/FAST EARTHING SWITCHES (AS APPLICABLE) IN CLOSE OR OPENPOSITION IN CASE OF REMOVAL OF THE DRIVING MECHANISM-220KV GIS SET 1 Included 0.00 0 0.00
42 7000030914 1170 MANDATORY SPARES-220 kV HYBRID GIS 1000058299 85359030 18% 220KV GIS-SF6 GAS (5 % OF TOTAL GAS QUANTITY) LOT 1 Included 0.00 0 0.00
43 7000030914 1180 MANDATORY SPARES-220 kV HYBRID GIS 1000049749 85359030 18% CONTROL VALVES FOR SF6 GAS OF EACH TYPE-220KV GIS SET 2 Included 0.00 0 0.00
44 7000030914 1190 MANDATORY SPARES-220 kV HYBRID GIS 1000058298 85359030 18% 220KV GIS-MOLECULAR FILTER FOR SF6 GAS WITH FILTER BAGS (5 % OF TOTALWEIGHT) SET 1 Included 0.00 0 0.00
45 7000030914 1200 MANDATORY SPARES-220 kV HYBRID GIS 1000049761 85359030 18% RUBBER GASKETS, €ŒO€ RINGS AND SEALS FOR SF6 GAS FOR GISENCLOSURE OF EACH TYPE-220KV GIS SET 2 Included 0.00 0 0.00
46 7000030914 1210 MANDATORY SPARES-220 kV HYBRID GIS 1000049752 85359030 18% COUPLING DEVICE FOR PRESSURE GAUGE CUM SWITCH FOR CONNECTINGGAS HANDLING PLANT OF EACH TYPE-220KV GIS SET 2 Included 0.00 0 0.00
47 7000030914 1220 MANDATORY SPARES-220 kV HYBRID GIS 1000049816 85359030 18% SF6 PRESSURE GAUGE CUM SWITCH /DENSITY MONITORS AND PRESSURESWITCH AS APPLICABLE, OF EACH TYPE-220KV GIS SET 2 Included 0.00 0 0.00
48 7000030914 1230 MANDATORY SPARES-220 kV HYBRID GIS 1000058300 85359030 18% 220KV GIS-SF6 GAS PRESSURE RELIEF DEVICE ASSEMBLY OF EACH TYPE EA 1 Included 0.00 0 0.00
49 7000030914 1340 Supply Tele BOQ at Bhuj-II 1000031367 85176260 18% SDH EQUIPMENT (STM-16 MADM UPTO 5 MSP PROTECTED DIRECTIONS)-BASEEQUIPMENT (COMMON CARDS, CROSS CONNECT/CONTROL CARDS, OPTICAL BASECARDS, POWER SUPPLY CARDS, POWER CABLING, OTHER HARDWARE ANDACCESSORIES INCLUDING SUB RACKS, PATCH CORD, DDF ETC FULLY EQUIPEDEXCLUDING OPTICAL INTERFACE & TRIBUTARY CARDS EA 1 Included 0.00 0 0.00
50 7000030914 1350 Supply Tele BOQ at Bhuj-II 1000018706 85176990 18% S16.1 SFP EA 4 Included 0.00 0 0.00
51 7000030914 1360 Supply Tele BOQ at Bhuj-II 1000031374 85176290 18% TRIBUTARY INTERFACE- E1 INTERFACE (MINIMUM 16 NOS.) SET 2 Included 0.00 0 0.00
52 7000030914 1370 Supply Tele BOQ at Bhuj-II 1000034950 85176990 18% ETHERNET INTERFACE 10/100 BASE T WITH LAYER-2 SWITCHING (MIN 8INTERFACES PER CARD) EA 2 Included 0.00 0 0.00
53 7000030914 1380 Supply Tele BOQ at Bhuj-II 1000031381 85176290 18% TRIBUTARY INTERFACE-GIGABIT ETHERNET INTERFACES 10/100 MBPS WITH LAYER-2 SWITCHING (MINIMUM 2 NOS.) SET 1 Included 0.00 0 0.00
54 7000030914 1390 Supply Tele BOQ at Bhuj-II 1000026228 85176290 18% Equipment Cabinets For SDH EA 1 Included 0.00 0 0.00
55 7000030914 1440 Supply Tele BOQ at Bhuj-II 1000037546 85447090 18% 48F (DWSM) APPROACH FIBRE OPTIC CABLE KM 0.5 Included 0.00 0 0.00
56 7000030914 1400 Supply Tele BOQ at Bhuj-II 1000066614 73069011 18% GI PIPE INSTALLATION HARDWARE FOR APPROACH CABLING KM 0.5 Included 0.00 0 0.00
57 7000030914 1410 Supply Tele BOQ at Bhuj-II 1000066612 73071900 18% GI ELBOW INSTALLATION HARDWARE FOR APPROAH CABLING EA 8 Included 0.00 0 0.00
58 7000030914 1420 Supply Tele BOQ at Bhuj-II 1000066613 83071000 18% GI FLEXIBLE CONDUIT INSTALLATION HARDWARE FOR APPROAH CABLING EA 6 Included 0.00 0 0.00
59 7000030914 1430 Supply Tele BOQ at Bhuj-II 1000023471 85372000 18% OPGW Fibre Optic Distribution Panel (FODP): Indoor Type: 96F EA 1 Included 0.00 0 0.00
60 7000030914 1460 Spares-tele BOQ 1000031369 85176260 18% SDH EQUIPMENT (STM-16 MADM UPTO 5 MSP PROTECTED DIRECTIONS)-COMMONCARDS, CROSS-CONNECT/CONTROL CARDS, OPTICAL BASE CARD, POWER SUPPLYCARDS, POWER CABLING, OTHER HARDWARE & ACCESSORIES (EACH). SET 1 Included 0.00 0 0.00
62 7000030914 1480 Spares-tele BOQ 1000031374 85176290 18% TRIBUTARY INTERFACE- E1 INTERFACE (MINIMUM 16 NOS.) SET 1 Included 0.00 0 0.00
63 7000030914 1490 Spares-tele BOQ 1000034950 85176990 18% ETHERNET INTERFACE 10/100 BASE T WITH LAYER-2 SWITCHING (MIN 8INTERFACES PER CARD) EA 1 Included 0.00 0 0.00
64 7000030914 1500 Spares-tele BOQ 1000031381 85176290 18% TRIBUTARY INTERFACE-GIGABIT ETHERNET INTERFACES 10/100 MBPS WITH LAYER-2 SWITCHING (MINIMUM 2 NOS.) SET 1 Included 0.00 0 0.00
65 7000030914 1510 Spares-tele BOQ 1000031398 85171890 18% PRE CONNECTORIZED OPTICAL FIBER PATCH CORDS(10 MTRS) – PACK OF SIXPATCH CORDS SET 1 Included 0.00 0 0.00
66 7000030914 1550 Spares-tele BOQ 1000037546 85447090 18% 48F (DWSM) APPROACH FIBRE OPTIC CABLE KM 0.5 Included 0.00 0 0.00
67 7000030914 1520 Spares-tele BOQ 1000066614 73069011 18% GI PIPE INSTALLATION HARDWARE FOR APPROACH CABLING KM 0.035 Included 0.00 0 0.00
68 7000030914 1530 Spares-tele BOQ 1000066612 73071900 18% GI ELBOW INSTALLATION HARDWARE FOR APPROAH CABLING EA 1 Included 0.00 0 0.00
69 7000030914 1540 Spares-tele BOQ 1000066613 83071000 18% GI FLEXIBLE CONDUIT INSTALLATION HARDWARE FOR APPROAH CABLING EA 1 Included 0.00 0 0.00
70 7000030914 1580 Non-Standard structures-Supply 1000015954 73082011 18% Fabrication, galvanising and supply of Lattice Structures (MS Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 13 Included 0.00 0 0.00
71 7000030914 1590 Non-Standard structures-Supply 1000011713 73082011 18% Fabrication, galvanising and supply of fasteners ( nuts, bolts andwashers ) including step bolts for lattice and pipe structures to bedesigned during detailed engineering MT 1 Included 0.00 0 0.00
72 7000030914 1600 Non-Standard structures-Supply 1000012373 73082011 18% Fabrication, galvanising and supply of foundation bolts including nuts,checknut and washers for lattice and pipe structures to be designedduring detailed engineering MT 2 Included 0.00 0 0.00
Total Ex-works Price 0.00
Total Type Test charges as per Schedule-7 0.00
Total Ex-works Price including Type Test charges 0.00
Total GST Tax as confirmed by Bidder 0.00
Note : Specify amount of GST on the transaction between the Contractor and the Employer.
* In case the bidder leaves the cell for confirmation of the HSN code and/or GST rate “blank”, the HSN code and corresponding GST rate indicated by the Employer shall be deemed to be the one confirmed by the Bidder.
Place : Printed Name :
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Schedule - 1 Direct Total 0 0 `
BO Total #REF! 0
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS;
(SCHEDULE OF RATES AND PRICES : EX-WORKS PRICES)
Bidder’s Name and Address (Lead Partner) : To:
Contract Services
Name : …….. …….. …….. …….. …….. …….. Power Grid Corporation of India Ltd.,
Address : …….. …….. …….. …….. …….. …….. "Saudamini", Plot No.-2
Plant and Equipment (including Mandatory Spares Parts) to be supplied, including Type Test Charges for Tests to be conducted. Direct
All Prices are in Indian Rupees. Bought-Out
SI. No. Item Description Unit Qty. Unit Ex-works price Total Ex-works price Mode of Transaction (Direct / Bought-out)
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
Total Ex-Works Price Direct 0.00 Direct
Total Ex-Works Price Bought Out 0.00
Total Ex-Works Price 0.00
Total Type Test charges as per Schedule-7 #REF! #REF! #REF!
Total Ex-works Price including Type Test charges #REF! #REF! #REF!
Discount Sch-1 #REF! MPD Sch-1 #REF!
Dis Alert #REF!
Note : Specify amount of Excise Duty, Sales Tax/'VAT and other taxes payable on the transaction between the Contractor and the Employer and octroi/entry tax as applicable for destination site/state on all items of supply including bought-out finished items (to be identified in the Contract), which shall be dispatched directly from the sub-vendor’s works to the Employer’s site (sale-in-transit), separately in Schedule-5. Excise Duty, Sales tax and other levies for all the bought-out items are to be included in the EXW Price (Col. No. 5) only and not to be indicated in Schedule-5.
Place : Printed Name :
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Schedule - 2
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS;
(SCHEDULE OF RATES AND PRICES)
Bidder’s Name and Address (Lead Partner) : To:
Contracts Services, 3rd Floor
Name : …….. …….. …….. …….. …….. …….. Power Grid Corporation of India Ltd.,
Address : …….. …….. …….. …….. …….. …….. "Saudamini", Plot No.-2
LOCAL TRANSPORTATION, IN-TRANSIT INSURANCE, LOADING AND UNLOADING
All Prices are in Indian Rupees.
SI. No. PR No PR Line Item No Activity Description Material Code Description Unit Quantity Unit Freight, In-transit Insurance, loading & unloading Charges Total Freight, In-transit Insurance, loading & unloading Charges
A Augmentation at Bhuj-II PS 400kV ICT
1 7000030922 220 GIS Portion- 420 kV GIS Equipments 1000032802 420KV, 4000A,63KA GIS BUSBAR MODULE EXTENSION SET 2 Included
2 7000030922 230 GIS Portion- 420 kV GIS Equipments 1000004637 420kV, 3150 A, 63 kA, SF6 GIS ICT feederbay module as per Section-Project,Technical specification SET 2 Included
3 7000030922 320 GIS Portion- 420 kV GIS Equipments 1000065958 EXTENSION OF 420 KV, 3150A, 63KA, SF6 GIS AUXILIARY BUS MODULE FOR SPARETRANSFORMER AS PER SECTION-PROJECT, TECHNICAL SPECIFICATION SET 1 Included
4 7000030922 240 GIS Portion- 420 kV GIS Equipments 1000004634 420 kV, 3150 A, 63 kA, SF6 GIS Linefeeder bay module(with PIR) as perSection-Project, Technicalspecification SET 1 Included
5 7000030922 250 GIS Portion- 420 kV GIS Equipments 1000004635 420kV, 3150 A, 63 kA, SF6 GIS Tie baymodule(with PIR) as perSection-Project, Technicalspecification SET 1 Included
6 7000030922 260 GIS Portion- 420 kV GIS Equipments 1000055830 420KV, 3150 A, 63 KA, SF6 GIS SWITCHABLE LINE REACTOR BAY MODULE ASPER SECTION-PROJECT, TECHNICAL SPECIFICATION SET 1 Included
7 7000030922 270 GIS Portion- 420 kV GIS Equipments 1000004287 420kV, 3000A, 63kA, Single phase, SF6Gas Insulated Bus Duct (GIB) outsideGIS Hall alongwith associated supportstructure M 450 Included
8 7000030922 350 GIS Portion- 420 kV GIS Equipments 1000032796 420KV, 3150A, 63KA SF6 TO AIR BUSHING including support structure SET 9 Included
9 7000030922 280 GIS Portion- 420 kV GIS Equipments 1000009713 Controlled Switching Device for 420 kV, 3-ph Circuit Breaker EA 6 Included
10 7000030922 290 GIS Portion- 420 kV GIS Equipments 1000004505 420kV, 3150 A, 63 kA, SF6 GIS Tie baymodule(without PIR) as perSection-Project, Technicalspecification SET 1 Included
11 7000030922 300 GIS Portion- 420 kV GIS Equipments 1000059208 420KV, 3150 A, 63 KA, SF6 GIS ICT FEEDER BAY MODULE FOR IV SIDECONNECTION WITH 765KV ICT AS PER SECTION-PROJECT, TECHNICALSPECIFICATION SET 1 Included
12 7000030922 310 GIS Portion- 420 kV GIS Equipments 1000004295 420kV, 4000A,63kA, Single phase SF6 GasInsulated Bus Duct (GIB) outside GISHall alongwith associated supportstructure M 495 Included
13 7000030922 330 GIS Portion- 420 kV GIS Equipments 1000077609 420KV,4000A, 63KA, 3-PHASE GIS EXTENSION PIECE (INTERFACE) MODULESUITABLE FOR EXTENDING EXISTING NHVS MAKE GIS BUS BAR/DUCT AS PERTECHNICAL SPECIFICATION SET 2 Included
14 7000030922 340 GIS Portion- 420 kV GIS Equipments 1000077935 420KV, 1-PHASE GIS EXTENSION PIECE (INTERFACE) MODULE SUITABLE FOREXTENDING EXISTING NHVS MAKE GIS AUXILIARY BUS BAR FOR CONNECTINGWITH SPARE ICT UNIT AS PER TECHNICAL SPECIFICATION SET 1 Included
15 7000030922 410 EOT CRANE 400kV GIS HALL 1000024691 EOT Crane for GIS Building for 400kV GIS station SET 1 Included
16 7000030922 20 420 kV AIS equipments 1000004401 420 kV, 1 phase Bus Post Insulator (except for Line Traps) EA 15 Included
17 7000030922 10 420 kV AIS equipments 1000020419 336kV Surge Arrester (1-phase) EA 9 Included
18 7000030922 360 CONTROL & RELAY PANEL-400KV 1000055446 400KV CIRCUIT BREAKER RELAY PANEL (WITH AUTOMATION) EA 7 Included
19 7000030922 370 CONTROL & RELAY PANEL-400KV 1000004274 400kV Transformer Protection Panel (For both HV & MV side)-(withAutomation) EA 2 Included
20 7000030922 380 SUBSTATION AUTOMATION SYSTEM 1000003409 Augmentation of Substation automation System for 400kV Main bay as perTechnical Specification EA 4 Included
21 7000030922 390 SUBSTATION AUTOMATION SYSTEM 1000003411 Augmentation of Substation automation System for 400kV Tie bay as perTechnical Specification EA 2 Included
22 7000030922 400 SUBSTATION AUTOMATION SYSTEM 1000003412 Augmentation of Substation automation System for 400kV Switchable LineReactor Bay as per Technical Specification EA 1 Included
23 7000030922 30 FIRE PROTECTION SYSTEM 1000012010 Fire Detection and Alarm System for 400kV GIS Hall SET 1 Included
24 7000030922 40 FIRE PROTECTION SYSTEM 1000012069 HVW spray system, Hydrant system and complete U/G & O/G piping andaccessories etc. out side the pump house for 500MVA , 400KV/220/33kV, 3-phase Autotransformer SET 2 Included
25 7000030922 50 FIRE PROTECTION SYSTEM 1000012022 4.5 kg CO2 type Portable Fire extinguisher EA 5 Included
26 7000030922 80 FIRE PROTECTION SYSTEM 1000012026 6Kg dry chemical powered type Portable Fire extinguisher EA 5 Included
27 7000030922 60 FIRE PROTECTION SYSTEM 1000012037 Hydrant system, complete U/G piping and accessories etc. outside thePump House for Fire Protection of 400/220kV (Ext) Substation SET 1 Included
28 7000030922 70 FIRE PROTECTION SYSTEM 1000049460 FIRE PROTECTION SYSTEM FOR LOCAL RELAY ROOM FOR 400KV GIS SET 1 Included
29 7000030922 530 POWER & CONTROL CABLE 1000000443 1.1kV grade Power Cables (PVCinsulated)along withlugs,glands,straight joints &accessories,etc. LS 1 Included
30 7000030922 540 POWER & CONTROL CABLE 1000000442 1.1kV grade Control Cables (PVCinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included
31 7000030922 550 POWER & CONTROL CABLE 1000000444 1.1kV grade Power Cables (XLPEinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included
32 7000030922 90 AIR CONDITIONING SYS & VENTILATION SYS 1000025963 Air conditioning sys-400kV GIS Hall LCC SET 1 Included
33 7000030922 100 AIR CONDITIONING SYS & VENTILATION SYS 1000022408 Ventillation system for 400KV GIS Hall SET 1 Included
34 7000030922 110 LIGHTING SYSTEM 1000038385 FIRE WALL MOUNTED LED LUMINARIE TYPE FL-2 (250W) EA 4 Included
35 7000030922 120 LIGHTING SYSTEM 1000038325 LIGHTING FIXTURE LED LUMINAIRES TYPE FL2 AS PER TECH. SPECIFICATIONS EA 9 Included
36 7000030922 130 LIGHTING SYSTEM 1000038387 LED FLOOD LIGHT LUMINARIESTYPE FL-1 (150W) AS PER TECHNICALSPECIFICATION EA 9 Included
37 7000030922 140 LIGHTING SYSTEM 1000001894 Outdoor Power Receptacle for oilfiltration unit (250A) EA 1 Included
38 7000030922 150 LIGHTING SYSTEM 1000014547 Lighting Panel type ACP-2 as per technical specification EA 2 Included
39 7000030922 160 LIGHTING SYSTEM 1000049467 INDOOR LIGHTNING FOR GIS BUILDING (AS PER TECHNICAL SPECIFICATION) including AHU & Relay Rooms as applicable SET 1 Included
40 7000030922 170 MAIN EARTHMAT 1000032055 40 MM MS ROD FOR MAIN EARTHMAT KM 1 Included
41 7000030922 180 ERECTION HARDWARE 1000011334 Erection Hardware for 400kV I type layout for GIS terminationarrangement-Transformer bay as per technical specification SET 3 Included
42 7000030922 190 MANDATORY SPARES-AIS 1000024186 SPARES FOR 336KV SURGE ARRESTER LS 1 Included
43 7000030922 200 MANDATORY SPARES-AIS 1000019912 Relay & protection Panels (with automation) LS 1 Included
44 7000030922 210 MANDATORY SPARES-AIS 1000019925 Spares for Fire Protection System LS 1 Included
45 7000030922 560 MANDATORY SPARES FOR SAS-AIS 1000062002 BAY CONTROL UNIT (IED) OF MAIN SYSTEM EA 1 Included
46 7000030922 570 MANDATORY SPARES FOR SAS-AIS 1000062004 ETHERNET SWITCH SUITABLE FOR 19€ RACK MOUNTING WITH 24 FIBER OPTICPORTS EA 1 Included
47 7000030922 710 GIS PORTION-TESTING & MAINTENANCE EQPT 1000038259 SCISSOR LIFT EA 1 Included
48 7000030922 600 Supply of non standard structure 1000015954 Fabrication, galvanising and supply of Lattice Structures (MS Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 7 Included
49 7000030922 610 Supply of non standard structure 1000015953 Fabrication, galvanising and supply of Lattice Structures (HT Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 2 Included
50 7000030922 620 Supply of non standard structure 1000011713 Fabrication, galvanising and supply of fasteners ( nuts, bolts andwashers ) including step bolts for lattice and pipe structures to bedesigned during detailed engineering MT 1 Included
51 7000030922 630 Supply of non standard structure 1000012373 Fabrication, galvanising and supply of foundation bolts including nuts,checknut and washers for lattice and pipe structures to be designedduring detailed engineering MT 3 Included
52 7000030922 640 PMUs for 400kV Bhuj-II PS 1000017518 PMU with GPS Clock (clock can be either internal or external) EA 3 Included
53 7000030922 650 PMUs for 400kV Bhuj-II PS 1000022512 WAMS Hardware - Time System (GPS receiver) EA 3 Included
54 7000030922 660 PMUs for 400kV Bhuj-II PS 1000071061 SUBSTATION GRADE LAYER 2 LAN SWITCH EA 3 Included
55 7000030922 670 PMUs for 400kV Bhuj-II PS 1000071062 SUBSTATION GRADE LAYER 3 LAN SWITCH EA 1 Included
56 7000030922 680 PMUs for 400kV Bhuj-II PS 1000022487 WAMS Miscellaneous - Armored Fibre Optic Cable and associatedtermination (e.g. L2 Switch) for connecting PMU panels located indifferent control room of a station EA 1 Included
57 7000030922 690 PMUs for 400kV Bhuj-II PS 1000030641 LIU - FO PATCH PANEL-12 PORT EA 4 Included
B 220kV line bays at Bhuj-II PS
1 7000030923 10 GIS Portion- 245kV GIS Equipments 1000039036 245KV,3000 A, 50KA FOR 1 SECOND, SF6 GAS-INSULATED METAL ENCLOSED BUSSECTION BAY MODULE AS PER SECTION-PROJECT, TECHNICAL SPECIFICATION EA 2 Included
2 7000030923 20 GIS Portion- 245kV GIS Equipments 1000001840 245kV, 3000 A, 50 kA, SF6 GIS Buscoupler bay module as perSection-Project, Technicalspecification SET 1 Included
3 7000030923 30 GIS Portion- 245kV GIS Equipments 1000001691 245kV, 1600 A, 50 kA, SF6 GIS Linefeeder bay module as perSection-Project, Technicalspecification SET 1 Included
4 7000030923 40 GIS Portion- 245kV GIS Equipments 1000001690 245kV, 1600 A, 50 kA, SF6 GIS ICT feederbay module as per Section-Project,Technical specification SET 2 Included
5 7000030923 50 GIS Portion- 245kV GIS Equipments 1000001693 245kV,1600A, 50kA,3 Single phase/3Phase, SF6 Gas Insulated Bus Duct (GIB)outside GIS Hall alongwith associatedsupport structure(Quantity mentionedhere is for 3 Phase type) M 108 Included
6 7000030923 60 GIS Portion- 245kV GIS Equipments 1000029503 245kV, 1600A, 50kA Single phase SF6 to Air Bushing EA 9 Included
7 7000030923 70 GIS Portion- 245kV GIS Equipments 1000001752 245kV,3000A,50kA,3 Single phase/3 Phase,SF6 Gas Insulated Bus Duct (GIB)outside GIS Hall alongwith associatedsupport structure(Quantity mentionedhere is for 3 Phase type) M 196 Included
8 7000030923 80 GIS Portion- 245kV GIS Equipments 1000032784 245 KV,3000 A, 50 KA SF6 GIS BUS BAR MODULE EXTENSION AS PERSECTION-PROJECT, TECHNICAL SPECIFICATION SET 2 Included
9 7000030923 90 GIS Portion- 245kV GIS Equipments 1000001838 245 kV, 3000A, 50kA, SF6 GIS Bus barmodule as per Section-Project,Technical specification SET 2 Included
10 7000030923 100 GIS Portion- 245kV GIS Equipments 1000077602 245KV,3000A, 50KA, 3-PHASE GIS EXTENSION PIECE (INTERFACE) MODULESUITABLE FOR EXTENDING EXISTING NHVS MAKE GIS BUS BAR/DUCT AS PERTECHNICAL SPECIFICATION SET 2 Included
11 7000030923 110 EOT CRANE 220kV GIS HALL 1000024690 EOT Crane for GIS Building for 220kV GIS Station SET 1 Included
12 7000030923 120 245kV AIS equipments 1000001695 245 kV, 1 phase Bus Post Insulator (except for Line Traps) EA 21 Included
13 7000030923 130 245kV AIS equipments 1000020417 216kV Surge Arrester (1-phase) EA 9 Included
14 7000030923 140 245kV AIS equipments 1000001772 245 kV, 4400pf Capacitive Voltage Transformer (1- Phase) EA 3 Included
15 7000030923 150 245kV AIS equipments 1000001568 220kV,1600A,0.5mH ,50kA Line Trap EA 2 Included
16 7000030923 160 245kV AIS equipments 1000001694 245 kV ,1 phase Bus Post Insulators for Line Traps EA 6 Included
17 7000030923 170 CONTROL & RELAY PANEL-220KV 1000055443 220KV CIRCUIT BREAKER RELAY PANEL (WITH AUTOMATION) EA 6 Included
18 7000030923 180 CONTROL & RELAY PANEL-220KV 1000001330 220kV Line Protection Panel (with Automation) EA 1 Included
19 7000030923 190 CONTROL & RELAY PANEL-220KV 1000001166 220kV Bus Bar Protection Panel (Single)-(with Automation) SET 1 Included
20 7000030923 200 SUBSTATION AUTOMATION SYSTEM 1000001333 Augmentation of Substation automation System for 220kV bay as perTechnical Specification EA 6 Included
21 7000030923 210 FIRE PROTECTION SYSTEM 1000012009 Fire Detection and Alarm System for 220kV GIS Hall SET 1 Included
22 7000030923 220 FIRE PROTECTION SYSTEM 1000012022 4.5 kg CO2 type Portable Fire extinguisher EA 5 Included
23 7000030923 250 FIRE PROTECTION SYSTEM 1000012026 6Kg dry chemical powered type Portable Fire extinguisher EA 5 Included
24 7000030923 230 FIRE PROTECTION SYSTEM 1000012034 Hydrant system, complete U/G piping andaccessories etc. outside the Pump Housefor Fire Protection of 220kV (Ext) S/S SET 1 Included
25 7000030923 240 FIRE PROTECTION SYSTEM 1000049459 FIRE PROTECTION SYSTEM FOR LOCAL RELAY ROOM FOR 220KV GIS SET 1 Included
26 7000030923 490 POWER & CONTROL CABLE 1000000443 1.1kV grade Power Cables (PVCinsulated)along withlugs,glands,straight joints &accessories,etc. LS 1 Included
27 7000030923 500 POWER & CONTROL CABLE 1000000442 1.1kV grade Control Cables (PVCinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included
28 7000030923 510 POWER & CONTROL CABLE 1000000444 1.1kV grade Power Cables (XLPEinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included
29 7000030923 260 AIR CONDITIONING SYSTEM 1000032700 AIRCONDITIONING SYSTEM FOR LCR IN 245KV GIS BUILDING SET 1 Included
30 7000030923 270 AIR CONDITIONING SYSTEM 1000022406 Ventillation system for 220KV GIS Hall SET 1 Included
31 7000030923 310 LIGHTING SYSTEM 1000038325 LIGHTING FIXTURE LED LUMINAIRES TYPE FL2 AS PER TECH. SPECIFICATIONS EA 5 Included
32 7000030923 320 LIGHTING SYSTEM 1000038387 LED FLOOD LIGHT LUMINARIESTYPE FL-1 (150W) AS PER TECHNICALSPECIFICATION EA 5 Included
33 7000030923 330 LIGHTING SYSTEM 1000014547 Lighting Panel type ACP-2 as per technical specification EA 1 Included
34 7000030923 340 LIGHTING SYSTEM 1000049467 INDOOR LIGHTNING FOR GIS BUILDING (AS PER TECHNICAL SPECIFICATION) including AHU & Relay Rooms as applicable SET 1 Included
35 7000030923 350 LIGHTING SYSTEM 1000038392 RP TYPE RECEPTACLE OF 63A AS PER TECHNICAL SPECIFICATION EA 1 Included
36 7000030923 280 MAIN EARTHMAT 1000032055 40 MM MS ROD FOR MAIN EARTHMAT KM 1 Included
37 7000030923 290 ERECTION HARDWARE 1000011246 Erection Hardware for 220kV DM-type layout for GIS terminationarrangement-Line bay as per technical specification SET 1 Included
38 7000030923 300 ERECTION HARDWARE 1000011252 Erection Hardware for 220kV DM-type layout for GIS terminationarrangement-Transformer bay as per technical specification SET 2 Included
39 7000030923 360 MANDATORY SPARES-AIS 1000025930 Spare-216kV Surge Arrester SET 1 Included
40 7000030923 370 MANDATORY SPARES-AIS 1000025934 Spare-245kV CVT SET 1 Included
41 7000030923 580 GIS PORTION-TESTING & MAINTENANCE EQPT 1000038259 SCISSOR LIFT EA 1 Included
42 7000030923 540 Supply of Non standard structure 1000015954 Fabrication, galvanising and supply of Lattice Structures (MS Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 30 Included
43 7000030923 550 Supply of Non standard structure 1000015953 Fabrication, galvanising and supply of Lattice Structures (HT Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 5 Included
44 7000030923 560 Supply of Non standard structure 1000011713 Fabrication, galvanising and supply of fasteners ( nuts, bolts andwashers ) including step bolts for lattice and pipe structures to bedesigned during detailed engineering MT 2 Included
45 7000030923 570 Supply of Non standard structure 1000012373 Fabrication, galvanising and supply of foundation bolts including nuts,checknut and washers for lattice and pipe structures to be designedduring detailed engineering MT 5 Included
C Extn. of 400/220kV Bhuj-II GIS S/S
1 7000030924 10 GIS Portion- 420 kV GIS Equipments 1000055830 420KV, 3150 A, 63 KA, SF6 GIS SWITCHABLE LINE REACTOR BAY MODULE ASPER SECTION-PROJECT, TECHNICAL SPECIFICATION SET 2 Included
2 7000030924 20 GIS Portion- 420 kV GIS Equipments 1000059208 420KV, 3150 A, 63 KA, SF6 GIS ICT FEEDER BAY MODULE FOR IV SIDECONNECTION WITH 765KV ICT AS PER SECTION-PROJECT, TECHNICALSPECIFICATION SET 1 Included
3 7000030924 30 GIS Portion- 420 kV GIS Equipments 1000004505 420kV, 3150 A, 63 kA, SF6 GIS Tie baymodule(without PIR) as perSection-Project, Technicalspecification SET 1 Included
4 7000030924 40 GIS Portion- 420 kV GIS Equipments 1000009713 Controlled Switching Device for 420 kV, 3-ph Circuit Breaker EA 9 Included
5 7000030924 90 GIS Portion- 420 kV GIS Equipments 1000032796 420KV, 3150A, 63KA SF6 TO AIR BUSHING including support structure SET 12 Included
6 7000030924 50 GIS Portion- 420 kV GIS Equipments 1000004287 420kV, 3000A, 63kA, Single phase, SF6Gas Insulated Bus Duct (GIB) outsideGIS Hall alongwith associated supportstructure M 535 Included
7 7000030924 60 GIS Portion- 420 kV GIS Equipments 1000004635 420kV, 3150 A, 63 kA, SF6 GIS Tie baymodule(with PIR) as perSection-Project, Technicalspecification SET 2 Included
8 7000030924 70 GIS Portion- 420 kV GIS Equipments 1000004634 420 kV, 3150 A, 63 kA, SF6 GIS Linefeeder bay module(with PIR) as perSection-Project, Technicalspecification SET 2 Included
9 7000030924 80 GIS Portion- 420 kV GIS Equipments 1000004637 420kV, 3150 A, 63 kA, SF6 GIS ICT feederbay module as per Section-Project,Technical specification SET 3 Included
10 7000030924 680 GIS Portion- 245 kV GIS Equipments 1000029503 245kV, 1600A, 50kA Single phase SF6 to Air Bushing EA 27 Included
11 7000030924 690 GIS Portion- 245 kV GIS Equipments 1000001693 245kV,1600A, 50kA,3 Single phase/3Phase, SF6 Gas Insulated Bus Duct (GIB)outside GIS Hall alongwith associatedsupport structure(Quantity mentionedhere is for 3 Phase type) M 314 Included
12 7000030924 700 GIS Portion- 245 kV GIS Equipments 1000001690 245kV, 1600 A, 50 kA, SF6 GIS ICT feederbay module as per Section-Project,Technical specification SET 3 Included
13 7000030924 710 GIS Portion- 245 kV GIS Equipments 1000001691 245kV, 1600 A, 50 kA, SF6 GIS Linefeeder bay module as perSection-Project, Technicalspecification SET 6 Included
14 7000030924 100 420 kV AIS EQUIPMENTS 1000004401 420 kV, 1 phase Bus Post Insulator (except for Line Traps) EA 18 Included
15 7000030924 110 420 kV AIS EQUIPMENTS 1000020419 336kV Surge Arrester (1-phase) EA 12 Included
16 7000030924 720 245 kV AIS EQUIPMENTS 1000001695 245 kV, 1 phase Bus Post Insulator (except for Line Traps) EA 45 Included
17 7000030924 730 245 kV AIS EQUIPMENTS 1000020417 216kV Surge Arrester (1-phase) EA 27 Included
18 7000030924 740 245 kV AIS EQUIPMENTS 1000001772 245 kV, 4400pf Capacitive Voltage Transformer (1- Phase) EA 18 Included
19 7000030924 750 245 kV AIS EQUIPMENTS 1000001568 220kV,1600A,0.5mH ,50kA Line Trap EA 12 Included
20 7000030924 760 245 kV AIS EQUIPMENTS 1000001694 245 kV ,1 phase Bus Post Insulators for Line Traps EA 36 Included
21 7000030924 120 CONTROL & RELAY PANEL 1000055446 400KV CIRCUIT BREAKER RELAY PANEL (WITH AUTOMATION) EA 11 Included
22 7000030924 130 CONTROL & RELAY PANEL 1000004274 400kV Transformer Protection Panel (For both HV & MV side)-(withAutomation) EA 3 Included
23 7000030924 140 CONTROL & RELAY PANEL 1000055443 220KV CIRCUIT BREAKER RELAY PANEL (WITH AUTOMATION) EA 9 Included
24 7000030924 150 CONTROL & RELAY PANEL 1000001330 220kV Line Protection Panel (with Automation) EA 6 Included
25 7000030924 190 SUBSTATION AUTOMATION SYSTEM 1000003412 Augmentation of Substation automation System for 400kV Switchable LineReactor Bay as per Technical Specification EA 2 Included
26 7000030924 160 SUBSTATION AUTOMATION SYSTEM 1000001333 Augmentation of Substation automation System for 220kV bay as perTechnical Specification EA 9 Included
27 7000030924 170 SUBSTATION AUTOMATION SYSTEM 1000003409 Augmentation of Substation automation System for 400kV Main bay as perTechnical Specification EA 6 Included
28 7000030924 180 SUBSTATION AUTOMATION SYSTEM 1000003411 Augmentation of Substation automation System for 400kV Tie bay as perTechnical Specification EA 3 Included
29 7000030924 200 FIRE PROTECTION SYSTEM 1000012069 HVW spray system, Hydrant system and complete U/G & O/G piping andaccessories etc. out side the pump house for 500MVA , 400KV/220/33kV, 3-phase Autotransformer SET 3 Included
30 7000030924 1280 POWER & CONTROL CABLE 1000000443 1.1kV grade Power Cables (PVCinsulated)along withlugs,glands,straight joints &accessories,etc. LS 1 Included
31 7000030924 1290 POWER & CONTROL CABLE 1000000442 1.1kV grade Control Cables (PVCinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included
32 7000030924 1300 POWER & CONTROL CABLE 1000000444 1.1kV grade Power Cables (XLPEinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included
33 7000030924 250 LIGHTING SYSTEM 1000038385 FIRE WALL MOUNTED LED LUMINARIE TYPE FL-2 (250W) EA 6 Included
34 7000030924 260 LIGHTING SYSTEM 1000038325 LIGHTING FIXTURE LED LUMINAIRES TYPE FL2 AS PER TECH. SPECIFICATIONS EA 20 Included
35 7000030924 270 LIGHTING SYSTEM 1000038387 LED FLOOD LIGHT LUMINARIESTYPE FL-1 (150W) AS PER TECHNICALSPECIFICATION EA 20 Included
36 7000030924 280 LIGHTING SYSTEM 1000014547 Lighting Panel type ACP-2 as per technical specification EA 1 Included
37 7000030924 290 LIGHTING SYSTEM 1000038392 RP TYPE RECEPTACLE OF 63A AS PER TECHNICAL SPECIFICATION EA 2 Included
38 7000030924 210 MAIN EARTHMAT 1000032055 40 MM MS ROD FOR MAIN EARTHMAT KM 4 Included
39 7000030924 220 ERECTION HARDWARE 1000011334 Erection Hardware for 400kV I type layout for GIS terminationarrangement-Transformer bay as per technical specification SET 4 Included
40 7000030924 230 ERECTION HARDWARE 1000011252 Erection Hardware for 220kV DM-type layout for GIS terminationarrangement-Transformer bay as per technical specification SET 3 Included
41 7000030924 240 ERECTION HARDWARE 1000011246 Erection Hardware for 220kV DM-type layout for GIS terminationarrangement-Line bay as per technical specification SET 6 Included
42 7000030924 300 GIS Portion-Mandatory Spares-400kV GIS 1000058332 400KV GIS-SF6 GAS PRESSURE RELIEF DEVICE ASSEMBLY OF EACH TYPE EA 1 Included
43 7000030924 310 GIS Portion-Mandatory Spares-400kV GIS 1000049817 SF6 PRESSURE GAUGE CUM SWITCH /DENSITY MONITORS AND PRESSURESWITCH AS APPLICABLE, OF EACH TYPE-400KV GIS SET 2 Included
44 7000030924 320 GIS Portion-Mandatory Spares-400kV GIS 1000049753 COUPLING DEVICE FOR PRESSURE GAUGE CUM SWITCH FOR CONNECTINGGAS HANDLING PLANT OF EACH TYPE-400KV GIS SET 1 Included
45 7000030924 330 GIS Portion-Mandatory Spares-400kV GIS 1000049762 RUBBER GASKETS, €ŒO€ RINGS AND SEALS FOR SF6 GAS FOR GISENCLOSURE OF EACH TYPE-400KV GIS SET 2 Included
46 7000030924 340 GIS Portion-Mandatory Spares-400kV GIS 1000058330 400KV GIS-MOLECULAR FILTER FOR SF6 GAS WITH FILTER BAGS (5 % OF TOTALWEIGHT) SET 1 Included
47 7000030924 350 GIS Portion-Mandatory Spares-400kV GIS 1000049750 CONTROL VALVES FOR SF6 GAS OF EACH TYPE-400KV GIS SET 2 Included
48 7000030924 360 GIS Portion-Mandatory Spares-400kV GIS 1000058331 400KV GIS-SF6 GAS (5 % OF TOTAL GAS QUANTITY) LOT 1 Included
49 7000030924 370 GIS Portion-Mandatory Spares-400kV GIS 1000049783 LOCKING DEVICE TO KEEP THE DIS-CONNECTORS (ISOLATORS)AND EARTHING/FAST EARTHING SWITCHES IN CLOSE OR OPEN POSITION IN CASEOF REMOVAL OF THE DRIVING MECHANISM-400KV GIS SET 2 Included
50 7000030924 380 GIS Portion-Mandatory Spares-400kV GIS 1000049505 UHF PD SENSORS OF EACH TYPE ALONG WITH BNC CONNECTOR FOR 420KV GIS EA 3 Included
51 7000030924 390 GIS Portion-Mandatory Spares-400kV GIS 1000058334 400KV GIS-SUPPORT INSULATORS (GAS THROUGH) OF EACH TYPE (COMPLETE WITHMETAL RING ETC.) ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 3 Included
52 7000030924 400 GIS Portion-Mandatory Spares-400kV GIS 1000058329 400KV GIS-GAS BARRIERS OF EACH TYPE (COMPLETE WITH METAL RING ETC.)ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 3 Included
53 7000030924 410 GIS Portion-Mandatory Spares-400kV GIS 1000058333 400KV GIS- 3150A SF6 TO AIR BUSHING COMPLETE IN ALL RESPECT EA 1 Included
54 7000030924 420 GIS Portion-Mandatory Spares-400kV GIS 1000049498 LCC SPARES - AUX. RELAYS, CONTACTORS,PUSH BUTTONS, SWITCHES,LAMPS,ANNUNCIATION WINDOWS, MCB, FUSES,TIMERS, TERMINAL BLOCKS ETC. OF EACHTYPE & RATING-400kV GIS SET 1 Included
55 7000030924 430 GIS Portion-Mandatory Spares-400kV GIS 1000058317 400KV GIS-ONE POLE OF 3150A CIRCUIT BREAKER WITHOUT PIR WITHINTERRUPTER, MAIN CIRCUIT, ENCLOSURE AND OPERATING MECHANISM COMPLETEIN ALL RESPECT SET 1 Included
56 7000030924 670 GIS Portion-Mandatory Spares-400kV GIS 1000058316 400KV GIS-ONE POLE OF 3150A CIRCUIT BREAKER WITH PIR WITH INTERRUPTER,MAIN CIRCUIT, ENCLOSURE AND OPERATING MECHANISM COMPLETE IN ALLRESPECT SET 1 Included
57 7000030924 440 GIS Portion-Mandatory Spares-400kV GIS 1000021873 Trip coil assembly with resistor for420kV GIS Circuit Breaker (asapplicable) SET 3 Included
58 7000030924 450 GIS Portion-Mandatory Spares-400kV GIS 1000009208 Closing coil assembly with resistor for420kV GIS Circuit Breaker (asapplicable) SET 3 Included
59 7000030924 460 GIS Portion-Mandatory Spares-400kV GIS 1000058324 RELAYS, POWER CONTACTORS, PUSH BUTTONS, TIMERS & MCBS ETC. (ASAPPLICABLE) OF EACH TYPE FOR 400KV GIS CIRCUIT BREAKER SET 1 Included
60 7000030924 470 GIS Portion-Mandatory Spares-400kV GIS 1000007067 Auxiliary switch assembly of each type for 420kV GIS Circuit Breaker SET 1 Included
61 7000030924 480 GIS Portion-Mandatory Spares-400kV GIS 1000058323 400KV GIS CIRCUIT BREAKER-OPERATION COUNTER EA 1 Included
62 7000030924 490 GIS Portion-Mandatory Spares-400kV GIS 1000058325 400KV GIS CIRCUIT BREAKER-COMPLETE SPRING OPERATING MECHANISMINCLUDING CHARGING MECHANISM ETC. (FOR SPRING OPERATED MECHANISM, IFAPPLICABLE) SET 1 Included
63 7000030924 500 GIS Portion-Mandatory Spares-400kV GIS 1000058374 400kV GIS- Single phase of 3150Adisconnector switch including maincircuit, enclosure, driving mechanismand support insulator etc., complete inall respect (Note 1- The contractorshall supply spare for disconnectorswitch to ensure one to one replacementof all disconnector switch supplied asmain equipment without any requirementof modification in fittings at site tocover all different types ofdisconnector switch supplied. In case,quantity of supplied dis-connectorswitch types (for one to onereplacement) are more than the quantitymentioned in BPS for spare, thecontractor shall supply theseadditional types of disconnector switchwithout any additional priceimplication to POWERGRID and quantitiesof these additional type ofdisconnector switch are deem to beincluded in the quantities mentioned inBPS for spare disconnector. Note 2 - Incase, Dis-connector Switch (DS) & EarthSwitch (ES) is provided in a sameenclosure with common operatingmechanism, then the module comprisingof Dis-connector & Earth switch insingle enclosure with common operatingmechanism is to be provided under thehead of spare Dis-connector only. Note3- In case, Dis-connector Switch (DS)&Earth Switch (ES) is provided in asame enclosure with separate operatingmechanism, then the module comprisingof Dis-connector & Earth switch insingle enclosure with separateoperating mechanism is to be providedunder the head of spare Dis-connectoronly.) EA 2 Included
64 7000030924 510 GIS Portion-Mandatory Spares-400kV GIS 1000058314 400KV GIS- SINGLE PHASE MAINTENANCE EARTHING SWITCH INCLUDING MAINCIRCUIT, ENCLOSURE, DRIVING MECHANISM AND SUPPORT INSULATOR ETC.,COMPLETE IN ALL RESPECT (NOTE 1 - IN CASE, DIS-CONNECTOR SWITCH (DS) &EARTH SWITCH (ES) IS PROVIDED IN A SAME ENCLOSURE WITH COMMONOPERATING MECHANISM, THEN THE MODULE COMPRISING OF DIS-CONNECTOR &EARTH SWITCH IN SINGLE ENCLOSURE WITH COMMON OPERATING MECHANISM IS TOBE PROVIDED UNDER THE HEAD OF SPARE DIS-CONNECTOR ONLY. NOTE 2 - INCASE, DIS-CONNECTOR SWITCH (DS) & EARTH SWITCH (ES) IS PROVIDED IN ASAME ENCLOSURE WITH SEPARATE OPERATING MECHANISM, THEN THE MODULECOMPRISING OF DIS-CONNECTOR & EARTH SWITCH IN SINGLE ENCLOSURE WITHSEPARATE OPERATING MECHANISM IS TO BE PROVIDED UNDER THE HEAD OF SPAREDIS-CONNECTOR ONLY.) EA 1 Included
65 7000030924 520 GIS Portion-Mandatory Spares-400kV GIS 1000058310 400KV GIS - SINGLE PHASE FAST EARTHING SWITCH INCLUDING MAIN CIRCUIT,ENCLOSURE, DRIVING MECHANISM AND SUPPORT INSULATOR ETC., COMPLETE INALL RESPECT (NOTE 1 - IN CASE, DIS-CONNECTOR SWITCH (DS) & EARTHSWITCH (ES) IS PROVIDED IN A SAME ENCLOSURE WITH COMMON OPERATINGMECHANISM, THEN THE MODULE COMPRISING OF DIS-CONNECTOR & EARTH SWITCHIN SINGLE ENCLOSURE WITH COMMON OPERATING MECHANISM IS TO BE PROVIDEDUNDER THE HEAD OF SPARE DIS-CONNECTOR ONLY. NOTE 2 - IN CASE,DIS-CONNECTOR SWITCH (DS) & EARTH SWITCH (ES) IS PROVIDED IN A SAMEENCLOSURE WITH SEPARATE OPERATING MECHANISM, THEN THE MODULECOMPRISING OF DIS-CONNECTOR & EARTH SWITCH IN SINGLE ENCLOSURE WITHSEPARATE OPERATING MECHANISM IS TO BE PROVIDED UNDER THE HEAD OF SPAREDIS-CONNECTOR ONLY.) EA 1 Included
66 7000030924 530 GIS Portion-Mandatory Spares-400kV GIS 1000058305 OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 400KV GIS DISCONNECTORSWITCH SET 1 Included
67 7000030924 540 GIS Portion-Mandatory Spares-400kV GIS 1000058312 OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 400KV GIS MAINTENANCE EARTHSWITCH SET 1 Included
68 7000030924 550 GIS Portion-Mandatory Spares-400kV GIS 1000058308 OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 400KV GIS FAST EARTHINGSWITCH SET 1 Included
69 7000030924 560 GIS Portion-Mandatory Spares-400kV GIS 1000049776 LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FORDISCONNECTOR-400KV GIS SET 1 Included
70 7000030924 570 GIS Portion-Mandatory Spares-400kV GIS 1000049778 LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FORMAINTENANCE EARTHING SWITCH-400KV GIS SET 1 Included
71 7000030924 580 GIS Portion-Mandatory Spares-400kV GIS 1000049777 LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FOR FASTEARTHING SWITCH (IF APPLICABLE)-400KV GIS SET 1 Included
72 7000030924 590 GIS Portion-Mandatory Spares-400kV GIS 1000058306 DRIVE MECHANISM FOR 400KV GIS DISCONNECTOR SWITCH SET 1 Included
73 7000030924 600 GIS Portion-Mandatory Spares-400kV GIS 1000058313 DRIVE MECHANISM FOR 400KV GIS MAINTENANCE EARTH SWITCH SET 1 Included
74 7000030924 610 GIS Portion-Mandatory Spares-400kV GIS 1000058309 DRIVE MECHANISM FOR 400KV GIS FAST EARTHING SWITCH SET 1 Included
75 7000030924 620 GIS Portion-Mandatory Spares-400kV GIS 1000058307 MOTOR FOR DRIVE MECHANISM FOR 400KV GIS DISCONNECTOR SWITCH EA 1 Included
76 7000030924 630 GIS Portion-Mandatory Spares-400kV GIS 1000058315 MOTOR FOR DRIVE MECHANISM FOR 400KVGIS MAINTENANCE EARTH SWITCH EA 1 Included
77 7000030924 640 GIS Portion-Mandatory Spares-400kV GIS 1000058311 MOTOR FOR DRIVE MECHANISM FOR 400KV GIS FAST EARTHING SWITCH EA 1 Included
78 7000030924 650 GIS Portion-Mandatory Spares-400kV GIS 1000058327 400KV GIS- SINGLE PHASE OF CURRENT TRANSFORMER (3 CORES, TYPE-CTA)WITH ASSOCIATED ENCLOSURE AND PRIMARY CONDUCTOR COMPLETE IN ALLRESPECT EA 1 Included
79 7000030924 660 GIS Portion-Mandatory Spares-400kV GIS 1000058326 400KV GIS- SINGLE PHASE OF CURRENT TRANSFORMER (2 CORES, TYPE-CTB)WITH ASSOCIATED ENCLOSURE AND PRIMARY CONDUCTOR COMPLETE IN ALLRESPECT EA 1 Included
80 7000030924 1150 GIS Portion-Mandatory Spares-220kV GIS 1000058295 220KV GIS- CABLE CONNECTION ENCLOSURE WITH MAIN CIRCUIT SET 1 Included
81 7000030924 770 GIS Portion-Mandatory Spares-220kV GIS 1000058300 220KV GIS-SF6 GAS PRESSURE RELIEF DEVICE ASSEMBLY OF EACH TYPE EA 1 Included
82 7000030924 780 GIS Portion-Mandatory Spares-220kV GIS 1000049816 SF6 PRESSURE GAUGE CUM SWITCH /DENSITY MONITORS AND PRESSURESWITCH AS APPLICABLE, OF EACH TYPE-220KV GIS SET 2 Included
83 7000030924 790 GIS Portion-Mandatory Spares-220kV GIS 1000049752 COUPLING DEVICE FOR PRESSURE GAUGE CUM SWITCH FOR CONNECTINGGAS HANDLING PLANT OF EACH TYPE-220KV GIS SET 1 Included
84 7000030924 800 GIS Portion-Mandatory Spares-220kV GIS 1000049761 RUBBER GASKETS, €ŒO€ RINGS AND SEALS FOR SF6 GAS FOR GISENCLOSURE OF EACH TYPE-220KV GIS SET 2 Included
85 7000030924 810 GIS Portion-Mandatory Spares-220kV GIS 1000058298 220KV GIS-MOLECULAR FILTER FOR SF6 GAS WITH FILTER BAGS (5 % OF TOTALWEIGHT) SET 1 Included
86 7000030924 820 GIS Portion-Mandatory Spares-220kV GIS 1000049749 CONTROL VALVES FOR SF6 GAS OF EACH TYPE-220KV GIS SET 2 Included
87 7000030924 830 GIS Portion-Mandatory Spares-220kV GIS 1000058299 220KV GIS-SF6 GAS (5 % OF TOTAL GAS QUANTITY) LOT 1 Included
88 7000030924 840 GIS Portion-Mandatory Spares-220kV GIS 1000049782 LOCKING DEVICE TO KEEP THE DIS-CONNECTORS (ISOLATORS)AND EARTHING/FAST EARTHING SWITCHES (AS APPLICABLE) IN CLOSE OR OPENPOSITION IN CASE OF REMOVAL OF THE DRIVING MECHANISM-220KV GIS SET 2 Included
89 7000030924 850 GIS Portion-Mandatory Spares-220kV GIS 1000049504 UHF PD SENSORS OF EACH TYPE ALONG WITH BNC CONNECTOR FOR 245KV GIS EA 3 Included
90 7000030924 860 GIS Portion-Mandatory Spares-220kV GIS 1000058302 220KV GIS-SUPPORT INSULATORS (GAS THROUGH) OF EACH TYPE (COMPLETE WITHMETAL RING ETC.) ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 3 Included
91 7000030924 870 GIS Portion-Mandatory Spares-220kV GIS 1000058297 220KV GIS-GAS BARRIERS OF EACH TYPE (COMPLETE WITH METAL RING ETC.)ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 3 Included
92 7000030924 880 GIS Portion-Mandatory Spares-220kV GIS 1000058301 220KV GIS- 1600A SF6 TO AIR BUSHING COMPLETE IN ALL RESPECT EA 1 Included
93 7000030924 890 GIS Portion-Mandatory Spares-220kV GIS 1000049497 LCC SPARES - AUX. RELAYS, CONTACTORS,PUSH BUTTONS, SWITCHES, LAMPS,ANNUNCIATION WINDOWS, MCB, FUSES,TIMERS, TERMINAL BLOCKS ETC. OF EACHTYPE & RATING-220kV GIS SET 1 Included
94 7000030924 900 GIS Portion-Mandatory Spares-220kV GIS 1000058284 220KV GIS-ONE POLE OF 1600A CIRCUIT BREAKER WITH INTERRUPTER, MAINCIRCUIT, ENCLOSURE AND OPERATING MECHANISM COMPLETE IN ALL RESPECT SET 1 Included
95 7000030924 910 GIS Portion-Mandatory Spares-220kV GIS 1000058285 220KV GIS-ONE POLE OF 3000A CIRCUIT BREAKER WITH INTERRUPTER, MAINCIRCUIT, ENCLOSURE AND OPERATING MECHANISM COMPLETE IN ALL RESPECT SET 1 Included
96 7000030924 920 GIS Portion-Mandatory Spares-220kV GIS 1000021871 Trip coil assembly with resistor for245kV GIS Circuit Breaker (asapplicable) SET 3 Included
97 7000030924 930 GIS Portion-Mandatory Spares-220kV GIS 1000009185 Closing coil assembly with resistor for245kV GIS Circuit Breaker (asapplicable) SET 3 Included
98 7000030924 940 GIS Portion-Mandatory Spares-220kV GIS 1000058292 RELAYS, POWER CONTACTORS, PUSH BUTTONS, TIMERS & MCBS ETC. (ASAPPLICABLE) OF EACH TYPE FOR 220KV GIS CIRCUIT BREAKER SET 1 Included
99 7000030924 950 GIS Portion-Mandatory Spares-220kV GIS 1000007066 Auxiliary switch assembly of each type for 245kV GIS Circuit Breaker SET 1 Included
100 7000030924 960 GIS Portion-Mandatory Spares-220kV GIS 1000058291 220KV GIS CIRCUIT BREAKER-OPERATION COUNTER EA 1 Included
101 7000030924 970 GIS Portion-Mandatory Spares-220kV GIS 1000058293 220KV GIS CIRCUIT BREAKER-COMPLETE SPRING OPERATING MECHANISMINCLUDING CHARGING MECHANISM ETC. (FOR SPRING OPERATED MECHANISM, IFAPPLICABLE) SET 1 Included
102 7000030924 980 GIS Portion-Mandatory Spares-220kV GIS 1000058371 220kV GIS- Three phase of 1600Adisconnector switch including maincircuit, enclosure, driving mechanismand support insulator etc., complete inall respect (Note 1- The contractorshall supply spare for disconnectorswitch to ensure one to one replacementof all disconnector switch supplied asmain equipment without any requirementof modification in fittings at site tocover all different types ofdisconnector switch supplied. In case,quantity of supplied dis-connectorswitch types (for one to onereplacement) are more than the quantitymentioned in BPS for spare, thecontractor shall supply theseadditional types of disconnector switchwithout any additional priceimplication to POWERGRID and quantitiesof these additional type ofdisconnector switch are deem to beincluded in the quantities mentioned inBPS for spare disconnector. Note 2 - Incase, Dis-connector Switch (DS) & EarthSwitch (ES) is provided in a sameenclosure with common operatingmechanism, then the module comprisingof Dis-connector & Earth switch insingle enclosure with common operatingmechanism is to be provided under thehead of spare Dis-connector only. Note3- In case, Dis-connector Switch (DS)&Earth Switch (ES) is provided in asame enclosure with separate operatingmechanism, then the module comprisingof Dis-connector & Earth switch insingle enclosure with separateoperating mechanism is to be providedunder the head of spare Dis-connectoronly.) EA 2 Included
103 7000030924 990 GIS Portion-Mandatory Spares-220kV GIS 1000058373 220kV GIS- Three phase of 3000Adisconnector switch including maincircuit, enclosure, driving mechanismand support insulator etc., complete inall respect (Note 1- The contractorshall supply spare for disconnectorswitch to ensure one to one replacementof all disconnector switch supplied asmain equipment without any requirementof modification in fittings at site tocover all different types ofdisconnector switch supplied. In case,quantity of supplied dis-connectorswitch types (for one to onereplacement) are more than the quantitymentioned in BPS for spare, thecontractor shall supply theseadditional types of disconnector switchwithout any additional priceimplication to POWERGRID and quantitiesof these additional type ofdisconnector switch are deem to beincluded in the quantities mentioned inBPS for spare disconnector. Note 2 - Incase, Dis-connector Switch (DS) & EarthSwitch (ES) is provided in a sameenclosure with common operatingmechanism, then the module comprisingof Dis-connector & Earth switch insingle enclosure with common operatingmechanism is to be provided under thehead of spare Dis-connector only. Note3- In case, Dis-connector Switch (DS)&Earth Switch (ES) is provided in asame enclosure with separate operatingmechanism, then the module comprisingof Dis-connector & Earth switch insingle enclosure with separateoperating mechanism is to be providedunder the head of spare Dis-connectoronly.) EA 1 Included
104 7000030924 1000 GIS Portion-Mandatory Spares-220kV GIS 1000058282 220KV GIS- THREE PHASE MAINTENANCE EARTHING SWITCH INCLUDING MAINCIRCUIT, ENCLOSURE, DRIVING MECHANISM AND SUPPORT INSULATOR ETC.,COMPLETE IN ALL RESPECT (NOTE 1 - IN CASE, DIS-CONNECTOR SWITCH (DS) &EARTH SWITCH (ES) IS PROVIDED IN A SAME ENCLOSURE WITH COMMONOPERATING MECHANISM, THEN THE MODULE COMPRISING OF DIS-CONNECTOR &EARTH SWITCH IN SINGLE ENCLOSURE WITH COMMON OPERATING MECHANISM IS TOBE PROVIDED UNDER THE HEAD OF SPARE DIS-CONNECTOR ONLY. NOTE 2 - INCASE, DIS-CONNECTOR SWITCH (DS) & EARTH SWITCH (ES) IS PROVIDED IN ASAME ENCLOSURE WITH SEPARATE OPERATING MECHANISM, THEN THE MODULECOMPRISING OF DIS-CONNECTOR & EARTH SWITCH IN SINGLE ENCLOSURE WITHSEPARATE OPERATING MECHANISM IS TO BE PROVIDED UNDER THE HEAD OF SPAREDIS-CONNECTOR ONLY.) EA 1 Included
105 7000030924 1010 GIS Portion-Mandatory Spares-220kV GIS 1000058278 220KV GIS - THREE PHASE FAST EARTHING SWITCH INCLUDING MAIN CIRCUIT,ENCLOSURE, DRIVING MECHANISM AND SUPPORT INSULATOR ETC., COMPLETE INALL RESPECT (NOTE 1 - IN CASE, DIS-CONNECTOR SWITCH (DS) & EARTHSWITCH (ES) IS PROVIDED IN A SAME ENCLOSURE WITH COMMON OPERATINGMECHANISM, THEN THE MODULE COMPRISING OF DIS-CONNECTOR & EARTH SWITCHIN SINGLE ENCLOSURE WITH COMMON OPERATING MECHANISM IS TO BE PROVIDEDUNDER THE HEAD OF SPARE DIS-CONNECTOR ONLY. NOTE 2 - IN CASE,DIS-CONNECTOR SWITCH (DS) & EARTH SWITCH (ES) IS PROVIDED IN A SAMEENCLOSURE WITH SEPARATE OPERATING MECHANISM, THEN THE MODULECOMPRISING OF DIS-CONNECTOR & EARTH SWITCH IN SINGLE ENCLOSURE WITHSEPARATE OPERATING MECHANISM IS TO BE PROVIDED UNDER THE HEAD OF SPAREDIS-CONNECTOR ONLY.) EA 1 Included
106 7000030924 1020 GIS Portion-Mandatory Spares-220kV GIS 1000058273 OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 220KV GIS DISCONNECTORSWITCH SET 1 Included
107 7000030924 1030 GIS Portion-Mandatory Spares-220kV GIS 1000058280 OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 220KV GIS MAINTENANCE EARTHSWITCH SET 1 Included
108 7000030924 1040 GIS Portion-Mandatory Spares-220kV GIS 1000058276 OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 220KV GIS FAST EARTHINGSWITCH SET 1 Included
109 7000030924 1050 GIS Portion-Mandatory Spares-220kV GIS 1000049773 LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FORDISCONNECTOR-220KV GIS SET 1 Included
110 7000030924 1060 GIS Portion-Mandatory Spares-220kV GIS 1000049775 LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FORMAINTENANCE EARTHING SWITCH-220KV GIS SET 1 Included
111 7000030924 1070 GIS Portion-Mandatory Spares-220kV GIS 1000049774 LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FOR FASTEARTHING SWITCH (IF APPLICABLE)-220KV GIS SET 1 Included
112 7000030924 1080 GIS Portion-Mandatory Spares-220kV GIS 1000058274 DRIVE MECHANISM FOR 220KV GIS DISCONNECTOR SWITCH SET 1 Included
113 7000030924 1090 GIS Portion-Mandatory Spares-220kV GIS 1000058281 DRIVE MECHANISM FOR 220KV GIS MAINTENANCE EARTH SWITCH SET 1 Included
114 7000030924 1100 GIS Portion-Mandatory Spares-220kV GIS 1000058277 DRIVE MECHANISM FOR 220KV GIS FAST EARTHING SWITCH SET 1 Included
115 7000030924 1110 GIS Portion-Mandatory Spares-220kV GIS 1000058275 MOTOR FOR DRIVE MECHANISM FOR 220KV GIS DISCONNECTOR SWITCH EA 1 Included
116 7000030924 1120 GIS Portion-Mandatory Spares-220kV GIS 1000058283 MOTOR FOR DRIVE MECHANISM FOR 220KVGIS MAINTENANCE EARTH SWITCH EA 1 Included
117 7000030924 1130 GIS Portion-Mandatory Spares-220kV GIS 1000058279 MOTOR FOR DRIVE MECHANISM FOR 220KV GIS FAST EARTHING SWITCH EA 1 Included
118 7000030924 1160 GIS Portion-Mandatory Spares-220kV GIS 1000075085 220KV GIS- SINGLE PHASE OF CURRENT TRANSFORMER (5 CORES) WITHASSOCIATED ENCLOSURE AND PRIMARY CONDUCTOR COMPLETE IN ALL RESPECT EA 2 Included
119 7000030924 1140 GIS Portion-Mandatory Spares-220kV GIS 1000058296 220KV GIS- SINGLE PHASE VT WITH ASSOCIATED ENCLOSURE COMPLETE IN ALLRESPECT EA 1 Included
120 7000030924 1330 Supply of non standard structure 1000015954 Fabrication, galvanising and supply of Lattice Structures (MS Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 146 Included
121 7000030924 1340 Supply of non standard structure 1000015953 Fabrication, galvanising and supply of Lattice Structures (HT Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 5 Included
122 7000030924 1350 Supply of non standard structure 1000011713 Fabrication, galvanising and supply of fasteners ( nuts, bolts andwashers ) including step bolts for lattice and pipe structures to bedesigned during detailed engineering MT 6 Included
123 7000030924 1360 Supply of non standard structure 1000012373 Fabrication, galvanising and supply of foundation bolts including nuts,checknut and washers for lattice and pipe structures to be designedduring detailed engineering MT 22 Included
124 7000030924 1370 Supply-Tele eqpt 1000066613 GI FLEXIBLE CONDUIT INSTALLATION HARDWARE FOR APPROAH CABLING EA 24 Included
125 7000030924 1380 Supply-Tele eqpt 1000066612 GI ELBOW INSTALLATION HARDWARE FOR APPROAH CABLING EA 32 Included
126 7000030924 1390 Supply-Tele eqpt 1000066614 GI PIPE INSTALLATION HARDWARE FOR APPROACH CABLING KM 4 Included
127 7000030924 1400 Supply-Tele eqpt 1000026228 Equipment Cabinets For SDH EA 1 Included
128 7000030924 1410 Supply-Tele eqpt 1000031381 TRIBUTARY INTERFACE-GIGABIT ETHERNET INTERFACES 10/100 MBPS WITH LAYER-2 SWITCHING (MINIMUM 2 NOS.) SET 2 Included
129 7000030924 1420 Supply-Tele eqpt 1000034950 ETHERNET INTERFACE 10/100 BASE T WITH LAYER-2 SWITCHING (MIN 8INTERFACES PER CARD) EA 4 Included
130 7000030924 1430 Supply-Tele eqpt 1000031374 TRIBUTARY INTERFACE- E1 INTERFACE (MINIMUM 16 NOS.) SET 4 Included
131 7000030924 1440 Supply-Tele eqpt 1000018706 S16.1 SFP EA 4 Included
132 7000030924 1450 Supply-Tele eqpt 1000031367 SDH EQUIPMENT (STM-16 MADM UPTO 5 MSP PROTECTED DIRECTIONS)-BASEEQUIPMENT (COMMON CARDS, CROSS CONNECT/CONTROL CARDS, OPTICAL BASECARDS, POWER SUPPLY CARDS, POWER CABLING, OTHER HARDWARE ANDACCESSORIES INCLUDING SUB RACKS, PATCH CORD, DDF ETC FULLY EQUIPEDEXCLUDING OPTICAL INTERFACE & TRIBUTARY CARDS EA 2 Included
133 7000030924 1460 Supply-Tele eqpt 1000037546 48F (DWSM) APPROACH FIBRE OPTIC CABLE KM 4 Included
134 7000030924 1470 Supply-Tele eqpt 1000076844 192 FIBRE FODP : INDOOR TYPE, RACK MOUNTED WITH FCPC COUPLING & PIGTAILS(5MTRS) EA 2 Included
135 7000030924 1480 Spares- Tele eqpt 1000066613 GI FLEXIBLE CONDUIT INSTALLATION HARDWARE FOR APPROAH CABLING EA 1 Included
136 7000030924 1490 Spares- Tele eqpt 1000066612 GI ELBOW INSTALLATION HARDWARE FOR APPROAH CABLING EA 1 Included
137 7000030924 1500 Spares- Tele eqpt 1000066614 GI PIPE INSTALLATION HARDWARE FOR APPROACH CABLING KM 0.14 Included
138 7000030924 1510 Spares- Tele eqpt 1000031398 PRE CONNECTORIZED OPTICAL FIBER PATCH CORDS(10 MTRS) – PACK OF SIXPATCH CORDS SET 1 Included
139 7000030924 1520 Spares- Tele eqpt 1000031381 TRIBUTARY INTERFACE-GIGABIT ETHERNET INTERFACES 10/100 MBPS WITH LAYER-2 SWITCHING (MINIMUM 2 NOS.) SET 1 Included
140 7000030924 1530 Spares- Tele eqpt 1000034950 ETHERNET INTERFACE 10/100 BASE T WITH LAYER-2 SWITCHING (MIN 8INTERFACES PER CARD) EA 1 Included
141 7000030924 1540 Spares- Tele eqpt 1000031374 TRIBUTARY INTERFACE- E1 INTERFACE (MINIMUM 16 NOS.) SET 1 Included
142 7000030924 1550 Spares- Tele eqpt 1000018706 S16.1 SFP EA 1 Included
143 7000030924 1560 Spares- Tele eqpt 1000031369 SDH EQUIPMENT (STM-16 MADM UPTO 5 MSP PROTECTED DIRECTIONS)-COMMONCARDS, CROSS-CONNECT/CONTROL CARDS, OPTICAL BASE CARD, POWER SUPPLYCARDS, POWER CABLING, OTHER HARDWARE & ACCESSORIES (EACH). SET 1 Included
144 7000030924 1570 Spares- Tele eqpt 1000037546 48F (DWSM) APPROACH FIBRE OPTIC CABLE KM 1 Included
D SS EXTN-400/220kV ICT(10th) AT BHUJ PS
1 7000030914 10 400 kV & 220 kV AIS EQUIPMENT 1000020419 336kV Surge Arrester (1-phase) EA 3 Included
2 7000030914 20 400 kV & 220 kV AIS EQUIPMENT 1000020417 216kV Surge Arrester (1-phase) EA 3 Included
3 7000030914 30 400 kV & 220 kV AIS EQUIPMENT 1000001695 245 kV, 1 phase Bus Post Insulator (except for Line Traps) EA 22 Included
4 7000030914 40 400 kV & 220 kV AIS EQUIPMENT 1000004401 420 kV, 1 phase Bus Post Insulator (except for Line Traps) EA 3 Included
5 7000030914 50 400 kV & 220 kV AIS EQUIPMENT 1000004498 420kV, 3150A, 63KA, Isolator (3-phase)(Double Break) with one E/S EA 2 Included
6 7000030914 60 400 kV & 220 kV AIS EQUIPMENT 1000004501 420kV, 3150A, 63kA Circuit Breaker (3-Phase) without closing resistorand with Support Structure EA 1 Included
7 7000030914 70 400 kV & 220 kV AIS EQUIPMENT 1000004463 420 kV, 3000A, 63KA, 1-Phase CurrentTransformer with 120% extended currentrating EA 3 Included
8 7000030914 80 400 kV & 220 kV AIS EQUIPMENT 1000009713 Controlled Switching Device for 420 kV, 3-ph Circuit Breaker EA 1 Included
9 7000030914 90 GIS Portion-220 kV GIS Equipment 1000029503 245kV, 1600A, 50kA Single phase SF6 to Air Bushing EA 6 Included
10 7000030914 100 GIS Portion-220 kV GIS Equipment 1000001693 245kV,1600A, 50kA,3 Single phase/3Phase, SF6 Gas Insulated Bus Duct (GIB)outside GIS Hall alongwith associatedsupport structure(Quantity mentionedhere is for 3 Phase type) M 400 Included
11 7000030914 110 Erection Hardware (400kV & 220 kV) 1000011320 Erection Hardware for 400kV I type layout-Any feeder Extn. on existinghalf dia. as per technical specification SET 1 Included
12 7000030914 120 Erection Hardware (400kV & 220 kV) 1000029216 Erection Hardware for 220kV DM type layout-Transformer bay as pertechnical specification SET 1 Included
13 7000030914 250 CONTROL & RELAY PANEL 1000004274 400kV Transformer Protection Panel (For both HV & MV side)-(withAutomation) EA 1 Included
14 7000030914 260 CONTROL & RELAY PANEL 1000001167 Augmentation of existing 220kV bus bar protection scheme.(No. of baysas per specification)-(with Automation) SET 1 Included
15 7000030914 270 CONTROL & RELAY PANEL 1000055443 220KV CIRCUIT BREAKER RELAY PANEL (WITH AUTOMATION) EA 1 Included
16 7000030914 280 CONTROL & RELAY PANEL 1000055446 400KV CIRCUIT BREAKER RELAY PANEL (WITH AUTOMATION) EA 1 Included
17 7000030914 600 SUBSTATION AUTOMATION SYSTEM 1000001333 Augmentation of Substation automation System for 220kV bay as perTechnical Specification EA 1 Included
18 7000030914 610 SUBSTATION AUTOMATION SYSTEM 1000003409 Augmentation of Substation automation System for 400kV Main bay as perTechnical Specification EA 1 Included
19 7000030914 290 ILLUMINATION SYSTEM (OUTDOOR) 1000014547 Lighting Panel type ACP-2 as per technical specification EA 1 Included
20 7000030914 300 ILLUMINATION SYSTEM (OUTDOOR) 1000020262 Sub Lighting panel (outdoor) type SLP (Switchyard and Street Lighting) EA 2 Included
21 7000030914 310 ILLUMINATION SYSTEM (OUTDOOR) 1000038039 LIGHTING FIXTURE LED LUMINAIRES TYPE FL-1 AS PER TECH. SPECIFICATIONS EA 8 Included
22 7000030914 320 ILLUMINATION SYSTEM (OUTDOOR) 1000038325 LIGHTING FIXTURE LED LUMINAIRES TYPE FL2 AS PER TECH. SPECIFICATIONS EA 8 Included
23 7000030914 330 Power & Control cables 1000000443 1.1kV grade Power Cables (PVCinsulated)along withlugs,glands,straight joints &accessories,etc. LS 1 Included
24 7000030914 340 Power & Control cables 1000000442 1.1kV grade Control Cables (PVCinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included
25 7000030914 350 Power & Control cables 1000000444 1.1kV grade Power Cables (XLPEinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included
26 7000030914 360 FIRE PROTECTION SYSTEM 1000012069 HVW spray system, Hydrant system and complete U/G & O/G piping andaccessories etc. out side the pump house for 500MVA , 400KV/220/33kV, 3-phase Autotransformer SET 1 Included
27 7000030914 370 FIRE PROTECTION SYSTEM 1000055457 HVW SPRAY SYSTEM, HYDRANT SYSTEM AND COMPLETE U/G & O/G PIPING ANDACCESSORIES ETC. OUT SIDE THE PUMP HOUSE FOR 420KV 3 PHASE BUSREACTOR SET 1 Included
28 7000030914 380 VISUAL MONITORING SYSTEM 1000030433 COLOR IP CAMERA, WITH PAN, TILT AND ZOOM FACILITIES, ALONGWITH ALLREQUIRED ITEMS, ACCESSORIES, LINE INTERFACE UNITS, FIBER PATCH CORDS,POWER SUPPLY UNITS, JUNCTION BOXES, CABLES, FIBER OPTIC CABLES, ETC.,AND INCLUDING INTEGRATION IN EXISTING HARDWARE AND SOFTWARE FORAUGMENTATION OF VISUAL MONITORING SYSTEM AS PER TECHNICALSPECIFICATION. SET 1 Included
29 7000030914 470 220 kV HYBRID GIS 1000045815 245KV, 1600 A, DM TYPE SF6 MTS/HYBRID GIS ICT/LINEFEEDER BAYSWITCHGEAR ASSEMBLY AS PER SECTION-PROJECT, TECHNICAL SPECIFICATION EA 1 Included
30 7000030914 480 Main Earthmat 1000032055 40 MM MS ROD FOR MAIN EARTHMAT KM 1 Included
31 7000030914 130 GIS Portion-Mandatory Spares-220kV GIS 1000058300 220KV GIS-SF6 GAS PRESSURE RELIEF DEVICE ASSEMBLY OF EACH TYPE EA 1 Included
32 7000030914 140 GIS Portion-Mandatory Spares-220kV GIS 1000049816 SF6 PRESSURE GAUGE CUM SWITCH /DENSITY MONITORS AND PRESSURESWITCH AS APPLICABLE, OF EACH TYPE-220KV GIS SET 2 Included
33 7000030914 150 GIS Portion-Mandatory Spares-220kV GIS 1000049752 COUPLING DEVICE FOR PRESSURE GAUGE CUM SWITCH FOR CONNECTINGGAS HANDLING PLANT OF EACH TYPE-220KV GIS SET 1 Included
34 7000030914 160 GIS Portion-Mandatory Spares-220kV GIS 1000049761 RUBBER GASKETS, €ŒO€ RINGS AND SEALS FOR SF6 GAS FOR GISENCLOSURE OF EACH TYPE-220KV GIS SET 2 Included
35 7000030914 170 GIS Portion-Mandatory Spares-220kV GIS 1000058298 220KV GIS-MOLECULAR FILTER FOR SF6 GAS WITH FILTER BAGS (5 % OF TOTALWEIGHT) SET 1 Included
36 7000030914 180 GIS Portion-Mandatory Spares-220kV GIS 1000049749 CONTROL VALVES FOR SF6 GAS OF EACH TYPE-220KV GIS SET 2 Included
37 7000030914 190 GIS Portion-Mandatory Spares-220kV GIS 1000058299 220KV GIS-SF6 GAS (5 % OF TOTAL GAS QUANTITY) LOT 1 Included
38 7000030914 200 GIS Portion-Mandatory Spares-220kV GIS 1000049504 UHF PD SENSORS OF EACH TYPE ALONG WITH BNC CONNECTOR FOR 245KV GIS EA 3 Included
39 7000030914 210 GIS Portion-Mandatory Spares-220kV GIS 1000058302 220KV GIS-SUPPORT INSULATORS (GAS THROUGH) OF EACH TYPE (COMPLETE WITHMETAL RING ETC.) ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 3 Included
40 7000030914 220 GIS Portion-Mandatory Spares-220kV GIS 1000058297 220KV GIS-GAS BARRIERS OF EACH TYPE (COMPLETE WITH METAL RING ETC.)ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 3 Included
41 7000030914 230 GIS Portion-Mandatory Spares-220kV GIS 1000058301 220KV GIS- 1600A SF6 TO AIR BUSHING COMPLETE IN ALL RESPECT EA 1 Included
42 7000030914 240 GIS Portion-Mandatory Spares-220kV GIS 1000049497 LCC SPARES - AUX. RELAYS, CONTACTORS,PUSH BUTTONS, SWITCHES, LAMPS,ANNUNCIATION WINDOWS, MCB, FUSES,TIMERS, TERMINAL BLOCKS ETC. OF EACHTYPE & RATING-220kV GIS SET 1 Included
43 7000030914 390 MANDATORY SPARES-AIS 1000019912 Relay & protection Panels (with automation) LS 1 Included
44 7000030914 400 MANDATORY SPARES-AIS 1000019925 Spares for Fire Protection System LS 1 Included
45 7000030914 410 MANDATORY SPARES-AIS 1000024186 SPARES FOR 336KV SURGE ARRESTER LS 1 Included
46 7000030914 440 MANDATORY SPARES-AIS 1000019918 Spares for 420kV Circuit Breaker LS 1 Included
47 7000030914 450 MANDATORY SPARES-AIS 1000025941 Spare-420kV CT 1 SET 1 Included
48 7000030914 460 MANDATORY SPARES-AIS 1000019919 Spares for 420kV Double break Isolator LS 1 Included
49 7000030914 430 MANDATORY SPARES-AIS 1000025934 Spare-245kV CVT SET 1 Included
50 7000030914 420 MANDATORY SPARES-AIS 1000025930 Spare-216kV Surge Arrester SET 1 Included
51 7000030914 630 MANDATORY SPARES FOR SAS-AIS 1000062002 BAY CONTROL UNIT (IED) OF MAIN SYSTEM EA 1 Included
52 7000030914 640 MANDATORY SPARES FOR SAS-AIS 1000062004 ETHERNET SWITCH SUITABLE FOR 19€ RACK MOUNTING WITH 24 FIBER OPTICPORTS EA 1 Included
53 7000030914 670 Non-Standard structures-Supply 1000015954 Fabrication, galvanising and supply of Lattice Structures (MS Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 30 Included
54 7000030914 680 Non-Standard structures-Supply 1000011713 Fabrication, galvanising and supply of fasteners ( nuts, bolts andwashers ) including step bolts for lattice and pipe structures to bedesigned during detailed engineering MT 1 Included
55 7000030914 690 Non-Standard structures-Supply 1000012373 Fabrication, galvanising and supply of foundation bolts including nuts,checknut and washers for lattice and pipe structures to be designedduring detailed engineering MT 3 Included
56 7000030914 700 PMUs for Bhuj PS 1000017518 PMU with GPS Clock (clock can be either internal or external) EA 2 Included
57 7000030914 710 PMUs for Bhuj PS 1000022512 WAMS Hardware - Time System (GPS receiver) EA 2 Included
58 7000030914 720 PMUs for Bhuj PS 1000071061 SUBSTATION GRADE LAYER 2 LAN SWITCH EA 2 Included
59 7000030914 730 PMUs for Bhuj PS 1000071062 SUBSTATION GRADE LAYER 3 LAN SWITCH EA 1 Included
60 7000030914 740 PMUs for Bhuj PS 1000022487 WAMS Miscellaneous - Armored Fibre Optic Cable and associatedtermination (e.g. L2 Switch) for connecting PMU panels located indifferent control room of a station EA 1 Included
61 7000030914 750 PMUs for Bhuj PS 1000030641 LIU - FO PATCH PANEL-12 PORT EA 3 Included
E 220kV line bays at Bhuj PS
1 7000030914 780 220 kV AIS EQUIPMENT 1000001772 245 kV, 4400pf Capacitive Voltage Transformer (1- Phase) EA 6 Included
2 7000030914 790 220 kV AIS EQUIPMENT 1000020417 216kV Surge Arrester (1-phase) EA 6 Included
3 7000030914 800 220 kV AIS EQUIPMENT 1000001695 245 kV, 1 phase Bus Post Insulator (except for Line Traps) EA 32 Included
4 7000030914 810 220 kV AIS EQUIPMENT 1000001567 220kV, 1600A, 0.5mH, 40 kA Line Trap EA 4 Included
5 7000030914 820 220 kV AIS EQUIPMENT 1000001694 245 kV ,1 phase Bus Post Insulators for Line Traps EA 12 Included
6 7000030914 770 220 kV HYBRID GIS 1000045815 245KV, 1600 A, DM TYPE SF6 MTS/HYBRID GIS ICT/LINEFEEDER BAYSWITCHGEAR ASSEMBLY AS PER SECTION-PROJECT, TECHNICAL SPECIFICATION EA 2 Included
7 7000030914 890 Erection Hardware (220kV) 1000033099 ERECTION HARDWARE FOR 220KV LAYOUT (DOUBLE MAIN SCHEME)-LINE BAY ASPER TECHNICAL SPECIFICATION SET 2 Included
8 7000030914 830 CONTROL & RELAY PANEL 1000001167 Augmentation of existing 220kV bus bar protection scheme.(No. of baysas per specification)-(with Automation) SET 1 Included
9 7000030914 840 CONTROL & RELAY PANEL 1000001330 220kV Line Protection Panel (with Automation) EA 2 Included
10 7000030914 850 CONTROL & RELAY PANEL 1000055443 220KV CIRCUIT BREAKER RELAY PANEL (WITH AUTOMATION) EA 2 Included
11 7000030914 1320 SUBSTATION AUTOMATION SYSTEM 1000001333 Augmentation of Substation automation System for 220kV bay as perTechnical Specification EA 2 Included
12 7000030914 860 Illumination System (Outdoor) 1000014547 Lighting Panel type ACP-2 as per technical specification EA 1 Included
13 7000030914 870 Illumination System (Outdoor) 1000038039 LIGHTING FIXTURE LED LUMINAIRES TYPE FL-1 AS PER TECH. SPECIFICATIONS EA 10 Included
14 7000030914 880 Illumination System (Outdoor) 1000038325 LIGHTING FIXTURE LED LUMINAIRES TYPE FL2 AS PER TECH. SPECIFICATIONS EA 10 Included
15 7000030914 900 POWER & CONTROL CABLE 1000000442 1.1kV grade Control Cables (PVCinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included
16 7000030914 910 POWER & CONTROL CABLE 1000000443 1.1kV grade Power Cables (PVCinsulated)along withlugs,glands,straight joints &accessories,etc. LS 1 Included
17 7000030914 920 AC+FIRE PROTN+ILLUM FOR SPR 1000006284 Air conditioning system for Switchyard Panel Room of 6m length SET 1 Included
18 7000030914 930 AC+FIRE PROTN+ILLUM FOR SPR 1000012022 4.5 kg CO2 type Portable Fire extinguisher EA 2 Included
19 7000030914 940 AC+FIRE PROTN+ILLUM FOR SPR 1000012018 Fire Detection and Alarm System for Switchyard Panel Room of 6 mlength SET 1 Included
20 7000030914 950 AC+FIRE PROTN+ILLUM FOR SPR 1000013795 Illumination System for switchyard panel room of 6 m length LS 1 Included
21 7000030914 960 Main Earthmat 1000032055 40 MM MS ROD FOR MAIN EARTHMAT KM 1 Included
22 7000030914 970 MANDATORY SPARES-220 kV HYBRID GIS 1000045815 245KV, 1600 A, DM TYPE SF6 MTS/HYBRID GIS ICT/LINEFEEDER BAYSWITCHGEAR ASSEMBLY AS PER SECTION-PROJECT, TECHNICAL SPECIFICATION EA 1 Included
23 7000030914 980 MANDATORY SPARES-220 kV HYBRID GIS 1000049497 LCC SPARES - AUX. RELAYS, CONTACTORS,PUSH BUTTONS, SWITCHES, LAMPS,ANNUNCIATION WINDOWS, MCB, FUSES,TIMERS, TERMINAL BLOCKS ETC. OF EACHTYPE & RATING-220kV GIS SET 2 Included
24 7000030914 990 MANDATORY SPARES-220 kV HYBRID GIS 1000049774 LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FOR FASTEARTHING SWITCH (IF APPLICABLE)-220KV GIS SET 1 Included
25 7000030914 1000 MANDATORY SPARES-220 kV HYBRID GIS 1000049775 LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FORMAINTENANCE EARTHING SWITCH-220KV GIS SET 1 Included
26 7000030914 1010 MANDATORY SPARES-220 kV HYBRID GIS 1000049773 LIMIT SWITCHES AND AUX. SWITCHES FOR ONE COMPLETE MOM BOX FORDISCONNECTOR-220KV GIS SET 1 Included
27 7000030914 1020 MANDATORY SPARES-220 kV HYBRID GIS 1000058276 OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 220KV GIS FAST EARTHINGSWITCH SET 1 Included
28 7000030914 1030 MANDATORY SPARES-220 kV HYBRID GIS 1000058280 OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 220KV GIS MAINTENANCE EARTHSWITCH SET 1 Included
29 7000030914 1040 MANDATORY SPARES-220 kV HYBRID GIS 1000058273 OPEN/CLOSE CONTACTOR ASSEMBLY, TIMERS, KEY INTERLOCK, INTERLOCKINGCOILS, RELAYS, PUSH BUTTONS, INDICATING LAMPS, POWER CONTACTORS,RESISTORS, FUSES, MCBS & DRIVE CONTROL CARDS ETC. (AS APPLICABLE) ONEOF EACH TYPE FOR ONE COMPLETE MOM BOX FOR 220KV GIS DISCONNECTORSWITCH SET 1 Included
30 7000030914 1050 MANDATORY SPARES-220 kV HYBRID GIS 1000049801 PRESSURE GAUGE WITH COUPLING DEVICE OF EACH TYPE (FOR HYDRAULIC-SPRINGOPERATED MECHANISM, IF APPLICABLE)-220KV GIS CIRCUIT BREKAER SET 1 Included
31 7000030914 1060 MANDATORY SPARES-220 kV HYBRID GIS 1000049797 PRESSURE SWITCHES OF EACH TYPE (FOR HYDRAULIC-SPRING OPERATEDMECHANISM, IF APPLICABLE)-220KV GIS CIRCUIT BREAKER SET 1 Included
32 7000030914 1070 MANDATORY SPARES-220 kV HYBRID GIS 1000058293 220KV GIS CIRCUIT BREAKER-COMPLETE SPRING OPERATING MECHANISMINCLUDING CHARGING MECHANISM ETC. (FOR SPRING OPERATED MECHANISM, IFAPPLICABLE) SET 1 Included
33 7000030914 1080 MANDATORY SPARES-220 kV HYBRID GIS 1000058291 220KV GIS CIRCUIT BREAKER-OPERATION COUNTER EA 3 Included
34 7000030914 1090 MANDATORY SPARES-220 kV HYBRID GIS 1000007066 Auxiliary switch assembly of each type for 245kV GIS Circuit Breaker SET 1 Included
35 7000030914 1100 MANDATORY SPARES-220 kV HYBRID GIS 1000058292 RELAYS, POWER CONTACTORS, PUSH BUTTONS, TIMERS & MCBS ETC. (ASAPPLICABLE) OF EACH TYPE FOR 220KV GIS CIRCUIT BREAKER SET 1 Included
36 7000030914 1110 MANDATORY SPARES-220 kV HYBRID GIS 1000009185 Closing coil assembly with resistor for245kV GIS Circuit Breaker (asapplicable) SET 3 Included
37 7000030914 1120 MANDATORY SPARES-220 kV HYBRID GIS 1000021871 Trip coil assembly with resistor for245kV GIS Circuit Breaker (asapplicable) SET 3 Included
38 7000030914 1130 MANDATORY SPARES-220 kV HYBRID GIS 1000058301 220KV GIS- 1600A SF6 TO AIR BUSHING COMPLETE IN ALL RESPECT EA 1 Included
39 7000030914 1140 MANDATORY SPARES-220 kV HYBRID GIS 1000058297 220KV GIS-GAS BARRIERS OF EACH TYPE (COMPLETE WITH METAL RING ETC.)ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 2 Included
40 7000030914 1150 MANDATORY SPARES-220 kV HYBRID GIS 1000058302 220KV GIS-SUPPORT INSULATORS (GAS THROUGH) OF EACH TYPE (COMPLETE WITHMETAL RING ETC.) ALONG WITH ASSOCIATED CONTACTS AND SHIELDS EA 2 Included
41 7000030914 1160 MANDATORY SPARES-220 kV HYBRID GIS 1000049782 LOCKING DEVICE TO KEEP THE DIS-CONNECTORS (ISOLATORS)AND EARTHING/FAST EARTHING SWITCHES (AS APPLICABLE) IN CLOSE OR OPENPOSITION IN CASE OF REMOVAL OF THE DRIVING MECHANISM-220KV GIS SET 1 Included
42 7000030914 1170 MANDATORY SPARES-220 kV HYBRID GIS 1000058299 220KV GIS-SF6 GAS (5 % OF TOTAL GAS QUANTITY) LOT 1 Included
43 7000030914 1180 MANDATORY SPARES-220 kV HYBRID GIS 1000049749 CONTROL VALVES FOR SF6 GAS OF EACH TYPE-220KV GIS SET 2 Included
44 7000030914 1190 MANDATORY SPARES-220 kV HYBRID GIS 1000058298 220KV GIS-MOLECULAR FILTER FOR SF6 GAS WITH FILTER BAGS (5 % OF TOTALWEIGHT) SET 1 Included
45 7000030914 1200 MANDATORY SPARES-220 kV HYBRID GIS 1000049761 RUBBER GASKETS, €ŒO€ RINGS AND SEALS FOR SF6 GAS FOR GISENCLOSURE OF EACH TYPE-220KV GIS SET 2 Included
46 7000030914 1210 MANDATORY SPARES-220 kV HYBRID GIS 1000049752 COUPLING DEVICE FOR PRESSURE GAUGE CUM SWITCH FOR CONNECTINGGAS HANDLING PLANT OF EACH TYPE-220KV GIS SET 2 Included
47 7000030914 1220 MANDATORY SPARES-220 kV HYBRID GIS 1000049816 SF6 PRESSURE GAUGE CUM SWITCH /DENSITY MONITORS AND PRESSURESWITCH AS APPLICABLE, OF EACH TYPE-220KV GIS SET 2 Included
48 7000030914 1230 MANDATORY SPARES-220 kV HYBRID GIS 1000058300 220KV GIS-SF6 GAS PRESSURE RELIEF DEVICE ASSEMBLY OF EACH TYPE EA 1 Included
49 7000030914 1340 Supply Tele BOQ at Bhuj-II 1000031367 SDH EQUIPMENT (STM-16 MADM UPTO 5 MSP PROTECTED DIRECTIONS)-BASEEQUIPMENT (COMMON CARDS, CROSS CONNECT/CONTROL CARDS, OPTICAL BASECARDS, POWER SUPPLY CARDS, POWER CABLING, OTHER HARDWARE ANDACCESSORIES INCLUDING SUB RACKS, PATCH CORD, DDF ETC FULLY EQUIPEDEXCLUDING OPTICAL INTERFACE & TRIBUTARY CARDS EA 1 Included
50 7000030914 1350 Supply Tele BOQ at Bhuj-II 1000018706 S16.1 SFP EA 4 Included
51 7000030914 1360 Supply Tele BOQ at Bhuj-II 1000031374 TRIBUTARY INTERFACE- E1 INTERFACE (MINIMUM 16 NOS.) SET 2 Included
52 7000030914 1370 Supply Tele BOQ at Bhuj-II 1000034950 ETHERNET INTERFACE 10/100 BASE T WITH LAYER-2 SWITCHING (MIN 8INTERFACES PER CARD) EA 2 Included
53 7000030914 1380 Supply Tele BOQ at Bhuj-II 1000031381 TRIBUTARY INTERFACE-GIGABIT ETHERNET INTERFACES 10/100 MBPS WITH LAYER-2 SWITCHING (MINIMUM 2 NOS.) SET 1 Included
54 7000030914 1390 Supply Tele BOQ at Bhuj-II 1000026228 Equipment Cabinets For SDH EA 1 Included
55 7000030914 1440 Supply Tele BOQ at Bhuj-II 1000037546 48F (DWSM) APPROACH FIBRE OPTIC CABLE KM 0.5 Included
56 7000030914 1400 Supply Tele BOQ at Bhuj-II 1000066614 GI PIPE INSTALLATION HARDWARE FOR APPROACH CABLING KM 0.5 Included
57 7000030914 1410 Supply Tele BOQ at Bhuj-II 1000066612 GI ELBOW INSTALLATION HARDWARE FOR APPROAH CABLING EA 8 Included
58 7000030914 1420 Supply Tele BOQ at Bhuj-II 1000066613 GI FLEXIBLE CONDUIT INSTALLATION HARDWARE FOR APPROAH CABLING EA 6 Included
59 7000030914 1430 Supply Tele BOQ at Bhuj-II 1000023471 OPGW Fibre Optic Distribution Panel (FODP): Indoor Type: 96F EA 1 Included
60 7000030914 1460 Spares-tele BOQ 1000031369 SDH EQUIPMENT (STM-16 MADM UPTO 5 MSP PROTECTED DIRECTIONS)-COMMONCARDS, CROSS-CONNECT/CONTROL CARDS, OPTICAL BASE CARD, POWER SUPPLYCARDS, POWER CABLING, OTHER HARDWARE & ACCESSORIES (EACH). SET 1 Included
61 7000030914 1470 Spares-tele BOQ 1000018706 S16.1 SFP EA 1 Included
62 7000030914 1480 Spares-tele BOQ 1000031374 TRIBUTARY INTERFACE- E1 INTERFACE (MINIMUM 16 NOS.) SET 1 Included
63 7000030914 1490 Spares-tele BOQ 1000034950 ETHERNET INTERFACE 10/100 BASE T WITH LAYER-2 SWITCHING (MIN 8INTERFACES PER CARD) EA 1 Included
64 7000030914 1500 Spares-tele BOQ 1000031381 TRIBUTARY INTERFACE-GIGABIT ETHERNET INTERFACES 10/100 MBPS WITH LAYER-2 SWITCHING (MINIMUM 2 NOS.) SET 1 Included
65 7000030914 1510 Spares-tele BOQ 1000031398 PRE CONNECTORIZED OPTICAL FIBER PATCH CORDS(10 MTRS) – PACK OF SIXPATCH CORDS SET 1 Included
66 7000030914 1550 Spares-tele BOQ 1000037546 48F (DWSM) APPROACH FIBRE OPTIC CABLE KM 0.5 Included
67 7000030914 1520 Spares-tele BOQ 1000066614 GI PIPE INSTALLATION HARDWARE FOR APPROACH CABLING KM 0.035 Included
68 7000030914 1530 Spares-tele BOQ 1000066612 GI ELBOW INSTALLATION HARDWARE FOR APPROAH CABLING EA 1 Included
69 7000030914 1540 Spares-tele BOQ 1000066613 GI FLEXIBLE CONDUIT INSTALLATION HARDWARE FOR APPROAH CABLING EA 1 Included
70 7000030914 1580 Non-Standard structures-Supply 1000015954 Fabrication, galvanising and supply of Lattice Structures (MS Steel),to be designed during detailed engineering, for towers, beams andequipment support structure including pack plates / packwashers andgusset plates excluding fasteners and foundation bolts MT 13 Included
71 7000030914 1590 Non-Standard structures-Supply 1000011713 Fabrication, galvanising and supply of fasteners ( nuts, bolts andwashers ) including step bolts for lattice and pipe structures to bedesigned during detailed engineering MT 1 Included
72 7000030914 1600 Non-Standard structures-Supply 1000012373 Fabrication, galvanising and supply of foundation bolts including nuts,checknut and washers for lattice and pipe structures to be designedduring detailed engineering MT 2 Included
Total F&I Price 0.00
Place: Printed Name :
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Schedule - 2 Dis
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS; As per Lum-sum 0
(SCHEDULE OF RATES AND PRICES : FREIGHT & INSURANCE CHARGES) AS per Percent #REF!
As per lum-sum on Sch-2 0.00%
Bidder’s Name and Address (Lead Partner) : To: As per Percent on Sch-2 #REF!
Contracts Services, 3rd Floor Total Discount #REF!
Name : …….. …….. …….. …….. …….. …….. Power Grid Corporation of India Ltd.,
Address : …….. …….. …….. …….. …….. …….. "Saudamini", Plot No.-2
…….. …….. …….. …….. …….. …….. Sector-29, Multipackage Discount 0.00%
All Prices are in Indian Rupees. Amount after Discount (Rs.) Dis Alert Amount after MPD (Rs.)
SI. No. Description Unit Quantity Unit Freight & Insurance Charges Total Freight & Insurance Charges Unit Freight & Insurance Charges Total Freight & Insurance Charges Unit Freight & Insurance Charges Total Freight & Insurance Charges
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
Total F&I Price #REF!
Place : Printed Name :
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Schedule - 3
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS; As per Lum-sum 0.00%
(SCHEDULE OF RATES AND PRICES ) AS per Percent #REF!
As per lum-sum on Sch-3 0.00%
Bidder’s Name and Address (Lead Partner) : To: As per Percent on Sch-3 #REF!
Contracts Services, 3rd Floor Total Discount #REF!
Name : …….. …….. …….. …….. …….. …….. Power Grid Corporation of India Ltd.,
Address : …….. …….. …….. …….. …….. …….. "Saudamini", Plot No.-2
…….. …….. …….. …….. …….. …….. Sector-29, Multipackage lum-sum 0.00%
INSTALLATION CHARGES Amount after Discount (Rs.) Dis Alert Amount after MPD (Rs.)
All Prices are in Indian Rupees.
SI. No. PR No PR Line Item No Activity Header PR Activity No Activity Description Service Code SAC (Service Accounting Codes) Whether SAC in column '8’ is confirmed. If not indicate applicable the SAC * Rate of GST applicable ( in %) Whether rate of GST in column ‘10’ is confirmed. If not indicate applicable rate of GST * Description Unit Quantity Unit Charges Total Charges Total GST as confirmed by Bidder Unit Erection Charges Total Erection Charges Unit Erection Charges Total Erection Charges
A Augmentation at Bhuj-II PS 400kV ICT Revaluation of J column Tax Calculation
1 7000030922 420 170 10 Inst. GIS Portion- 420 kV GIS Equipmen 100003557 998736 18% Extension of 420kV , 4000 A, 63 kA3 -phase SF6 GIS bus bar SET 2 Included 0.00 0 0
2 7000030922 420 170 20 Inst. GIS Portion- 420 kV GIS Equipmen 100001826 998736 18% 420kV, 3150 A, 63 kA, SF6 GIS ICT feeder bay module as per Section-Project, Technical specification SET 2 Included 0.00 0 0
3 7000030922 420 170 40 Inst. GIS Portion- 420 kV GIS Equipmen 100001832 998736 18% 420 kV, 3150 A, 63 kA, SF6 GIS Line feeder bay module(with PIR) as per Section-Project, Technical specification SET 1 Included 0.00 0 0
4 7000030922 420 170 50 Inst. GIS Portion- 420 kV GIS Equipmen 100001843 998736 18% 420kV, 3150 A, 63 kA, SF6 GIS Tie bay module(with PIR) as per Section-Project, Technical specification SET 1 Included 0.00 0 0
5 7000030922 420 170 60 Inst. GIS Portion- 420 kV GIS Equipmen 100017060 998736 18% 420KV, 3150 A, 63 KA, SF6 GIS SWITCHABLE LINE REACTOR BAY MODULE AS PER SECTION-PROJECT, TECHNICAL SPECIFICATION SET 1 Included 0.00 0 0
6 7000030922 420 170 70 Inst. GIS Portion- 420 kV GIS Equipmen 100002140 998736 18% 420kV, 3000A/3150, 63kA, Single phase, SF6 Gas Insulated Bus Duct (GIB) outsideGIS Hall along with associated support structure M 450 Included 0.00 0 0
7 7000030922 420 170 80 Inst. GIS Portion- 420 kV GIS Equipmen 100002392 998736 18% 420kV, SF6 to Air Bushing alongwithassociated support structure for 3150A,63 kA for 1 sec. Single Phase EA 9 Included 0.00 0 0
8 7000030922 420 170 90 Inst. GIS Portion- 420 kV GIS Equipmen 100000268 998736 18% Controlled Switching Device for 420 kV, 3-ph Circuit Breaker EA 6 Included 0.00 0 0
9 7000030922 420 170 100 Inst. GIS Portion- 420 kV GIS Equipmen 100002132 998736 18% 420kV, 3150 A, 63 kA, SF6 GIS Tie bay module(without PIR) as per Section-Project, Technical specification SET 1 Included 0.00 0 0
10 7000030922 420 170 110 Inst. GIS Portion- 420 kV GIS Equipmen 100023510 998736 18% 420kV, 3150 A, 63 kA, SF6 GIS ICT feeder bay module for IV side connection with 765kV ICT as per Section-Project, Technicalspecification SET 1 Included 0.00 0 0
11 7000030922 420 170 120 Inst. GIS Portion- 420 kV GIS Equipmen 100002142 998736 18% 420kV, 4000A,63kA, Single phase SF6 GasInsulated Bus Duct (GIB) outside GISHall alongwith associated supportstructure M 495 Included 0.00 0 0
12 7000030922 420 170 130 Inst. GIS Portion- 420 kV GIS Equipmen 100040373 998736 18% EXTENSION OF 420 KV, 3150A, 63KA, SF6 GIS AUXILIARY BUS MODULE FOR SPARE TRANSFORMER AS PER SECTION-PROJECT, TECHNICAL SPECIFICATION SET 1 Included 0.00 0 0
13 7000030922 420 170 140 Inst. GIS Portion- 420 kV GIS Equipmen 100057114 998736 18% 420kV,4000A, 63kA, 3-Phase GIS Extension Piece (Interface) module suitable for extending existing NHVS make GIS Bus Bar/Duct as perTechnical Specification SET 2 Included 0.00 0 0
14 7000030922 420 170 150 Inst. GIS Portion- 420 kV GIS Equipmen 100057315 998736 18% 420kV, 1-Phase GIS Extension Piece (Interface) module suitable for extending existing NHVS make GIS Auxiliary Bus Bar forconnecting with spare ICT unit as per Technical Specification SET 1 Included 0.00 0 0
15 7000030922 430 180 10 Inst. EOT CRANE 400kV GIS HALL 100000259 998736 18% EOT Crane for GIS Building for 400kV GIS station SET 1 Included 0.00 0 0
16 7000030922 440 190 10 Inst. 420 kV AIS equipments 100005443 998734 18% 420KV, 1-PHASE BUS POST INSULATORS EA 15 Included 0.00 0 0
17 7000030922 440 190 20 Inst. 420 kV AIS equipments 100000328 998736 18% 336kV Surge Arrester (1-phase) EA 9 Included 0.00 0 0
18 7000030922 450 200 10 Inst. CONTROL & RELAY PANEL-400KV 100016779 998736 18% 400kV Circuit Breaker Relay Panel (with Automation) EA 7 Included 0.00 0 0
19 7000030922 450 200 20 Inst. CONTROL & RELAY PANEL-400KV 100000731 998736 18% 400kV Transformer Protection Panel (For both HV & MV side)-(with Automation) EA 2 Included 0.00 0 0
20 7000030922 450 200 30 Inst. CONTROL & RELAY PANEL-400KV 100000735 998736 18% Augmentation of existing 400kV bus bar protection scheme.(No. of bays as per specification)-(with Automation) SET 1 Included 0.00 0 0
21 7000030922 460 210 10 Inst. SUBSTATION AUTOMATION SYSTEM 100002069 998736 18% Augmentation of Substation automation System for 400kV Main bay as per Technical Specification EA 4 Included 0.00 0 0
22 7000030922 460 210 20 Inst. SUBSTATION AUTOMATION SYSTEM 100002075 998736 18% Augmentation of Substation automation System for 400kV Tie bay as per Technical Specification EA 2 Included 0.00 0 0
23 7000030922 460 210 30 Inst. SUBSTATION AUTOMATION SYSTEM 100002077 998736 18% Augmentation of Substation automation System for 400kV Switchable Line Reactor Bay as per Technical Specification EA 1 Included 0.00 0 0
24 7000030922 470 220 10 Inst. FIRE PROTECTION SYSTEM 100002059 995461 18% Fire Detection and Alarm System for 400kV GIS Hall SET 1 Included 0.00 0 0
25 7000030922 470 220 20 Inst. FIRE PROTECTION SYSTEM 100000983 998736 18% HVW spray system, Hydrant system and complete U/G & O/G piping and accessories etc. out side the pump house for 500MVA ,400KV/220/33 kV, 3-phase Autotransformer SET 2 Included 0.00 0 0
26 7000030922 470 220 30 Inst. FIRE PROTECTION SYSTEM 100000975 995461 18% 4.5 kg CO2 type Portable Fire extinguisher EA 5 Included 0.00 0 0
27 7000030922 470 220 40 Inst. FIRE PROTECTION SYSTEM 100000976 998736 18% 6Kg dry chemical powered type Portable Fire extinguisher EA 5 Included 0.00 0 0
28 7000030922 470 220 70 Inst. FIRE PROTECTION SYSTEM 100008181 998736 18% Fire Protection System for local relay room for 400kV GIS SET 1 Included 0.00 0 0
29 7000030922 470 220 80 Inst. FIRE PROTECTION SYSTEM 100001868 998736 18% Hydrant system, complete U/G piping and accessories etc. outside the Pump House for Fire Protection of 400/220kV (Ext) Substation SET 1 Included 0.00 0 0
30 7000030922 480 230 10 Inst. POWER & CONTROL CABLE 100002180 998736 18% 1.1kV grade Power Cables (XLPEinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0
31 7000030922 480 230 20 Inst. POWER & CONTROL CABLE 100002181 998736 18% 1.1kV grade Power Cables (PVCinsulated)along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0
32 7000030922 480 230 30 Inst. POWER & CONTROL CABLE 100002182 998736 18% 1.1kV grade Control Cables (PVCinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0
33 7000030922 490 240 10 Inst. AIR CONDITIONING & VENTILATION SYS 100002754 995463 18% Airconditioning system-LCR-400kV GIS HALL LS 1 Included 0.00 0 0
34 7000030922 490 240 20 Inst. AIR CONDITIONING & VENTILATION SYS 100001874 995463 18% Ventillation system for 400KV GIS Hall SET 1 Included 0.00 0 0
35 7000030922 500 250 20 Inst. LIGHTING SYSTEM 100004937 998731 18% Fire Wall Mounted LED Luminarie Type FL-2 (250W) EA 4 Included 0.00 0 0
36 7000030922 500 250 30 Inst. LIGHTING SYSTEM 100004926 998731 18% Lighting Fixture LED Luminaires type FL2 as per tech. specifications EA 9 Included 0.00 0 0
37 7000030922 500 250 40 Inst. LIGHTING SYSTEM 100004852 998731 18% Lighting Fixture LED Luminaires type FL-1 as per tech. specifications EA 9 Included 0.00 0 0
38 7000030922 500 250 50 Inst. LIGHTING SYSTEM 100001885 998739 18% Outdoor Power Receptacle for oilfiltration unit (250A) EA 1 Included 0.00 0 0
39 7000030922 500 250 60 Inst. LIGHTING SYSTEM 100001021 995461 18% Lighting Panel type ACP-2 as per technical specification EA 2 Included 0.00 0 0
40 7000030922 500 250 100 Inst. LIGHTING SYSTEM 100008185 998736 18% Indoor Lightning for GIS Building (As per Technical specification) including AHU & Relay Rooms as applicable SET 1 Included 0.00 0 0
41 7000030922 510 260 10 Inst. MAIN EARTHMAT 100003103 998731 18% 40 mm MS rod for Main Earthmat KM 1 Included 0.00 0 0
42 7000030922 520 270 10 Inst. ERECTION HARDWARE 100002188 998731 18% Erection Hardware for 400kV I type layout for GIS termination arrangement-Transformer bay as per technical specification SET 3 Included 0.00 0 0
43 7000030922 580 290 10 Civil Works 100004518 995433 18% Excavation in all kind of soil including rock for all leads and lifts, backfilling, disposal of surplus earth within a lead up to2Km as per technical specification. The surplus earth shall be roughly graded . M3 3916 Included 0.00 0 0
44 7000030922 580 290 20 Civil Works 100011662 995433 18% Excavation in hard rock which require blasting (including chemical blasting and rock excavated using specialized tools) for allfoundation works including stacking, measuring, disposal etc.for all leads and lifts as per technical specification. M3 2611 Included 0.00 0 0
45 7000030922 580 290 30 Civil Works 100001325 995454 18% Providing and laying of Plain Cement Concrete (PCC) (1:4:8) M3 264 Included 0.00 0 0
46 7000030922 580 290 40 Civil Works 100001326 995454 18% Providing and laying of Plain Cement Concrete (PCC) (1:2:4) M3 26 Included 0.00 0 0
47 7000030922 580 290 50 Civil Works 100048595 995423 18% Providing & laying non-woven Geo-synthetics fabric of minimum 200 GSM in separration layer between sub garde and stone spreading inswitchyard as per Technical Specification and direction of Engineer-in-Charge. M2 2275 Included 0.00 0 0
48 7000030922 580 290 60 Civil Works 100016607 995451 18% Providing and laying of Reinforced Cement Concrete M30 including pre cast, shuttering, Grouting of pockets & underpinning butexcluding steel reinforcement M3 2749 Included 0.00 0 0
49 7000030922 580 290 70 Civil Works 100016681 995454 18% Reinforcement steel meeting corrosion resistance properties as per IS:1786 and manufacturer specification​ MT 186 Included 0.00 0 0
50 7000030922 580 290 80 Civil Works 100001331 995455 18% Misc. Structural steel including rails, embedments, edge protection angles, gratings etc. but excluding the reinforcement steel andsteel for lattice and pipe structures. MT 61 Included 0.00 0 0
51 7000030922 580 290 90 Civil Works 100001330 995428 18% Stone filling (40 mm size) for transformer/Reactor foundation M3 41 Included 0.00 0 0
52 7000030922 580 290 100 Civil Works 100001714 995428 18% Stone spreading in switchyard excluding PCC M2 2025 Included 0.00 0 0
53 7000030922 580 290 110 Civil Works 100001713 995424 18% Antiweed treatment M2 2275 Included 0.00 0 0
54 7000030922 580 290 120 Civil Works 100001712 995428 18% Removing,cleaning and washing of existing stones and respreading of stones in switchyard excluding PCC M2 250 Included 0.00 0 0
55 7000030922 580 290 130 Civil Works 100054773 995454 18% External finishing/ painting of fire wall with cement wash M2 480 Included 0.00 0 0
56 7000030922 580 290 140 Civil Works 100002911 995432 18% Earthwork in excavation & filling in all types of soil and soft/disintegrated rock in open areas/nallas/channels, to the requiredslopes, shapes, levels, elevations and profile, including trimming of bottom and slopes of excavation, bailing out rain(dewatering), pumping, removal of slush, preparing embankments/marginal banks, loosening, dressing, spreading material in layers notexceeding 200mm, as per direction of Engineer-in-Charge, water flooding, compacting to achieve 95% consolidation at optimum moisturecontent, finishing etc. all complete, for all leads and lifts within leveling boundary, including disposal of surplus earth andstacking of unsuitable material within a lead of 2.0 Km beyond substation boundary, with all labour, material, tools, tackles andequipment, safeguards and incidentals, Royalty,taxes etc. as necessary, as per drawings, specification and directions of theEngineer-in-Charge. Clearing of jungle is included in this item. (Only excavation/cutting will be measured for payment purpose.) M3 8438 Included 0.00 0 0
57 7000030922 580 290 150 Civil Works 100004467 995432 18% Earthwork in Excavation in hard rock including stacking of serviceable material within substation boundary and disposal ofunserviceable material for leads up to 2000 meters beyond the levelling boundary as per TS M3 4219 Included 0.00 0 0
58 7000030922 580 290 160 Civil Works 100002583 995432 18% Supply of earth (excluding rock & boulders) at site including royalty, carriage and filling in specified areas in layers notexceeding 200mm in depth, compacting under optimum moisture condition to achieve 95% of Proctor density, finishing etc. allcomplete, for all leads & lifts, with all labour, material, tools, tackles, equipments, safeguards & incidentals as necessary as perdrawings, specification and direction of the Engineer- in- Charge. M3 100 Included 0.00 0 0
59 7000030922 580 290 170 Civil Works 100001478 995454 18% Cable Trench including all types of crossings, all metallic works and sump pit including concrte and reinforcement steel Section 2-2 M 225 Included 0.00 0 0
60 7000030922 580 290 180 Civil Works 100001479 995454 18% Cable Trench including all types of crossings, all metallic works and sump pit including concrte and reinforcement steel Section 3-3 M 100 Included 0.00 0 0
61 7000030922 580 290 190 Civil Works 100001480 995454 18% Cable Trench including all types of crossings, all metallic works and sump pit including concrte and reinforcement steel Section 4-4 M 25 Included 0.00 0 0
62 7000030922 580 290 200 Civil Works 100007701 995462 18% Supplying and erecting dewatering pumps- 2 HP EA 1 Included 0.00 0 0
63 7000030922 580 290 210 Civil Works 100001409 995462 18% Supplying and erecting dewatering pumps-5 HP EA 1 Included 0.00 0 0
64 7000030922 580 290 220 Civil Works 100008110 995421 18% 3.75m wide Bitumen road with earthen shoulder including 100 mm dia RCC Hume Pipe @ 100 metre interval as per drawing and TS (as perDSR item no 16.35 and 16.30.1) and including 225 mm thick WBM in three equal layers of 75 mm each as per CPWD specification. M2 1069 Included 0.00 0 0
65 7000030922 580 290 230 Civil Works 100001457 995421 18% Construction of rail cum road as per drawing including all item such as excavation,compactions, rolling watering, WBM etc. butexcluding concrete reinforcement and structural steel-Section having four rails for auto transformer. M2 221 Included 0.00 0 0
66 7000030922 580 290 240 Civil Works 100015791 995454 18% All civil works for Drains construction of Section A-A including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 285 Included 0.00 0 0
67 7000030922 580 290 250 Civil Works 100015792 995454 18% All civil works for Drains construction of Section B-B including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 200 Included 0.00 0 0
68 7000030922 580 290 260 Civil Works 100015793 995454 18% All civil works for Drains construction of Section C-C including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 86 Included 0.00 0 0
69 7000030922 580 290 270 Civil Works 100015794 995454 18% All civil works for Drains construction of Section D-D including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 30 Included 0.00 0 0
70 7000030922 580 290 280 Civil Works 100001743 995414 18% PEB - 400 kV GIS - Civil Works. All civil works as per drawing and specifications complete, including - brickwork, finishing(external and internal), windows etc. However, excavation, PCC, RCC and reinforcement shall be paid separately as per BPS. M2 930 Included 0.00 0 0
71 7000030922 580 290 290 Civil Works 100004431 995416 18% 400 kV PEB Panel Room for GIS Hall - Civil Works All civil works complete as per TS, including - brickwork, finishing (externaland internal), windows etc. However, excavation, concrete (all types) and reinforcement steel shall be measured and paid separatelyas per respective item of BPS. M2 84 Included 0.00 0 0
72 7000030922 580 290 300 Civil Works 100004427 995416 18% 400 kV PEB AHU Room for GIS Hall - Civil Works All civil works complete as per TS, including - brickwork, finishing (external andinternal), windows etc. However, excavation, concrete (all types) and reinforcement steel shall be measured and paid separately asper respective item of BPS. M2 30 Included 0.00 0 0
73 7000030922 580 290 310 Civil Works 130000761 995428 18% 14.4.2 Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointingwith cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. : 150 mm dia M 50 Included 0.00 0 0
74 7000030922 580 290 320 Civil Works 130000762 995428 18% 14.4.3 Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointingwith cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. : 250 mm dia M 50 Included 0.00 0 0
75 7000030922 580 290 330 Civil Works 100001721 995428 18% Supplying, filling and compacting stone boulders mixed with sand under foundations, roads, cable trenches, drains etc in layers notexceeding 250mm thickness including ramming, watering compacting M3 50 Included 0.00 0 0
76 7000030922 580 290 340 Civil Works 100003295 995429 18% Dismantling of RCC in foundation including disposal of debris and reinforcement bars of dismantled RCC works within substationboundaries as per direction of enginner incahrge M3 10 Included 0.00 0 0
77 7000030922 580 290 350 Civil Works 100001442 995456 18% Dismantling of existing brick drain (300mm widex500mm deep) M 15 Included 0.00 0 0
78 7000030922 580 290 360 Civil Works 100004463 995456 18% Random Rubble masonry for Retaining wall with locally available stone in cement sand mortar 1:6 (1 Cement: 6 coarse sand) includinglevelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size), Raised and Cutpointing on exposed surface, weep holes/PVC pipe sleeves of 100 mm dia (medium class) @ 1 metre C/C staggered . The top of theretaining wall to be provided with cement concrete 1:2:4. However items of excavation, concrete (1:2:4) shall be payable underrespective items of BPS M3 50 Included 0.00 0 0
79 7000030922 590 300 10 Erection of non standard structure 100001210 995455 18% Erection of Lattice Structures (MS Steel), to be designed during detailed engineering, for towers, beams and equipment supportstructure including pack plates / packwashers and gusset plates excluding fasteners and foundation bolts MT 7 Included 0.00 0 0
80 7000030922 590 300 20 Erection of non standard structure 100001209 995455 18% Erection of Lattice Structures (HT Steel), to be designed during detailed engineering, for towers, beams and equipment supportstructure including pack plates / packwashers and gusset plates excluding fasteners and foundation bolts. MT 2 Included 0.00 0 0
81 7000030922 590 300 30 Erection of non standard structure 100001680 995455 18% Erection of fasteners ( nuts, bolts and washers ) including step bolts for lattice and pipe structures to be designed duringdetailed engineering MT 1 Included 0.00 0 0
82 7000030922 590 300 40 Erection of non standard structure 100001681 995455 18% Erection of foundation bolts including nuts, checknut and washers for lattice and pipe structures to be designed during detailedengineering MT 3 Included 0.00 0 0
83 7000030922 700 330 10 PMUs for 400kV Bhuj-II PS 170000502 998713 18% Service:- Phasor Measurement Unit (PMU) EA 3 Included 0.00 0 0
84 7000030922 700 330 20 PMUs for 400kV Bhuj-II PS 170000530 998734 18% WAMS TIME SYSTEM(GPS RECEIVER) EA 3 Included 0.00 0 0
85 7000030922 700 330 30 PMUs for 400kV Bhuj-II PS 170004701 998734 18% SUBSTATION GRADE Layer 2 LAN SWITCH EA 3 Included 0.00 0 0
86 7000030922 700 330 40 PMUs for 400kV Bhuj-II PS 170004700 998734 18% SUBSTATION GRADE Layer 3 LAN SWITCH EA 1 Included 0.00 0 0
87 7000030922 700 330 50 PMUs for 400kV Bhuj-II PS 170000504 998713 18% Services:- Armored Fibre Optic Cable and associated termination equipment LOT 1 Included 0.00 0 0
88 7000030922 700 330 60 PMUs for 400kV Bhuj-II PS 170003449 998316 18% SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF LIU-FO PATCH PANEL-12 PORT EA 4 Included 0.00 0 0
89 7000030922 700 330 70 PMUs for 400kV Bhuj-II PS 170000501 998734 18% Integration of PMU with the PDC (Phasor Data Concentrator) of RLDCs and respective SLDCs as required. LOT 1 Included 0.00 0 0
B 220kV line bays at Bhuj-II PS
1 7000030923 380 190 10 Inst. GIS Portion- 245kV GIS Equipments 100003578 998736 18% 245 kV,3000 A, 50 kA SF6 GIS Bus bar module Extension as per Section-Project, Technical specification SET 2 Included 0.00 0 0
2 7000030923 380 190 20 Inst. GIS Portion- 245kV GIS Equipments 100005107 998736 18% 245KV,3000 A, 50KA FOR 1 SECOND, SF6 GAS-INSULATED METAL ENCLOSED BUS SECTION BAY MODULE AS PER SECTION-PROJECT, TECHNICALSPECIFICATION EA 2 Included 0.00 0 0
3 7000030923 380 190 30 Inst. GIS Portion- 245kV GIS Equipments 100000410 998736 18% 245kV, 3000 A, 50 kA, SF6 GIS Bus coupler bay module SET 1 Included 0.00 0 0
4 7000030923 380 190 40 Inst. GIS Portion- 245kV GIS Equipments 100000377 998736 18% 245kV, 1600 A, 50 kA, SF6 GIS Line feeder bay module for connecting Overhead line (Air/SF6) with GIS through gas insulatedinterconnection bus etc SET 1 Included 0.00 0 0
5 7000030923 380 190 50 Inst. GIS Portion- 245kV GIS Equipments 100000367 998736 18% 245kV, 1600 A, 50 kA, SF6 GIS ICT feeder bay module SET 2 Included 0.00 0 0
6 7000030923 380 190 60 Inst. GIS Portion- 245kV GIS Equipments 100002153 998736 18% 245kV,1600A, 50kA,3 Single phase/3Phase, SF6 Gas Insulated Bus Duct(GIB) outside GIS Hall alongwithassociated support structure(Quantitymentioned here is for 3 Phase type) M 108 Included 0.00 0 0
7 7000030923 380 190 70 Inst. GIS Portion- 245kV GIS Equipments 100002390 998736 18% 245kV,1600A, 50 kA for 1 sec SF6 to Air Bushing EA 9 Included 0.00 0 0
8 7000030923 380 190 80 Inst. GIS Portion- 245kV GIS Equipments 100002156 998736 18% 245kV,3000A,50kA,3 Single phase/3 Phase,SF6 Gas Insulated Bus Duct (GIB)outside GIS Hall alongwith associatedsupport structure(Quantity mentionedhere is for 3 Phase type) M 196 Included 0.00 0 0
9 7000030923 380 190 90 Inst. GIS Portion- 245kV GIS Equipments 100057262 998736 18% 245 kV, 3000A, 50kA, SF6 GIS Bus bar module as per Section-Project, Technical specification SET 2 Included 0.00 0 0
10 7000030923 380 190 100 Inst. GIS Portion- 245kV GIS Equipments 100057122 998736 18% 245kV,3000A, 50kA, 3-Phase GIS Extension Piece (Interface) module suitable for extending existing NHVS make GIS Bus Bar/Duct as perTechnical Specification SET 2 Included 0.00 0 0
11 7000030923 390 200 10 Inst. EOT CRANE 220kV GIS HALL 100000433 998736 18% EOT Crane for GIS Building for 220kV GIS Station SET 1 Included 0.00 0 0
12 7000030923 400 210 10 Inst. 245kV AIS equipments 100001907 998736 18% 245 kV,1 phase Bus Post Insulator (except for Line Traps) EA 21 Included 0.00 0 0
13 7000030923 400 210 20 Inst. 245kV AIS equipments 100000484 998736 18% 216kV Surge Arrester (1-phase) EA 9 Included 0.00 0 0
14 7000030923 400 210 30 Inst. 245kV AIS equipments 100000448 998736 18% 245 kV, 4400pf Capacitive Voltage Transformer (1- Phase) EA 3 Included 0.00 0 0
15 7000030923 400 210 40 Inst. 245kV AIS equipments 100002048 998734 18% 220kV,1600A,0.5mH ,50kA Line Trap EA 2 Included 0.00 0 0
16 7000030923 400 210 50 Inst. 245kV AIS equipments 100000884 998734 18% 245 kV ,1 phase Bus Post Insulators for Line Traps EA 6 Included 0.00 0 0
17 7000030923 410 220 10 Inst. CONTROL & RELAY PANEL-220KV 100016778 998736 18% 220kV Circuit Breaker Relay Panel (with Automation) EA 6 Included 0.00 0 0
18 7000030923 410 220 20 Inst. CONTROL & RELAY PANEL-220KV 100000738 998736 18% 220kV Line Protection Panel (with Automation) EA 1 Included 0.00 0 0
19 7000030923 410 220 30 Inst. CONTROL & RELAY PANEL-220KV 100000743 998736 18% Augmentation of existing 220kV bus bar protection scheme.(No. of bays as per specification)-(with Automation) SET 1 Included 0.00 0 0
20 7000030923 410 220 40 Inst. CONTROL & RELAY PANEL-220KV 100000741 998736 18% 220kV Bus Bar Protection Panel (Single)-(with Automation) SET 1 Included 0.00 0 0
21 7000030923 420 230 10 Inst. SUBSTATION AUTOMATION SYSTEM 100002070 998736 18% Augmentation of Substation automation System for 220kV bay as per Technical Specification EA 6 Included 0.00 0 0
22 7000030923 430 240 10 Inst. FIRE PROTECTION SYSTEM 100002060 995461 18% Fire Detection and Alarm System for 220kV GIS Hall SET 1 Included 0.00 0 0
23 7000030923 430 240 20 Inst. FIRE PROTECTION SYSTEM 100000975 995461 18% 4.5 kg CO2 type Portable Fire extinguisher EA 5 Included 0.00 0 0
24 7000030923 430 240 30 Inst. FIRE PROTECTION SYSTEM 100000976 998736 18% 6Kg dry chemical powered type Portable Fire extinguisher EA 5 Included 0.00 0 0
25 7000030923 430 240 40 Inst. FIRE PROTECTION SYSTEM 100001869 998736 18% Hydrant system, complete U/G piping andaccessories etc. outside the Pump Housefor Fire Protection of 220kV (Ext) S/S SET 1 Included 0.00 0 0
26 7000030923 430 240 50 Inst. FIRE PROTECTION SYSTEM 100008182 998736 18% Fire Protection System for local relay room for 220kV GIS SET 1 Included 0.00 0 0
27 7000030923 440 250 10 Inst. POWER & CONTROL CABLE 100002180 998736 18% 1.1kV grade Power Cables (XLPEinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0
28 7000030923 440 250 20 Inst. POWER & CONTROL CABLE 100002181 998736 18% 1.1kV grade Power Cables (PVCinsulated)along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0
29 7000030923 440 250 30 Inst. POWER & CONTROL CABLE 100002182 998736 18% 1.1kV grade Control Cables (PVCinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0
30 7000030923 450 260 10 Inst. AIR CONDITIONING SYSTEM 100003516 995463 18% Airconditioning system for LCR in 245kV GIS building LS 1 Included 0.00 0 0
31 7000030923 450 260 20 Inst. AIR CONDITIONING SYSTEM 100001875 995463 18% Ventillation system for 220KV GIS Hall SET 1 Included 0.00 0 0
32 7000030923 460 270 20 Inst. LIGHTING SYSTEM 100004926 998731 18% Lighting Fixture LED Luminaires type FL2 as per tech. specifications EA 5 Included 0.00 0 0
33 7000030923 460 270 30 Inst. LIGHTING SYSTEM 100004852 998731 18% Lighting Fixture LED Luminaires type FL-1 as per tech. specifications EA 5 Included 0.00 0 0
34 7000030923 460 270 40 Inst. LIGHTING SYSTEM 100001021 995461 18% Lighting Panel type ACP-2 as per technical specification EA 1 Included 0.00 0 0
35 7000030923 460 270 70 Inst. LIGHTING SYSTEM 100004941 998731 18% RP Type Receptacle of 63A as per technical specification EA 1 Included 0.00 0 0
36 7000030923 460 270 80 Inst. LIGHTING SYSTEM 100008185 998736 18% Indoor Lightning for GIS Building (As per Technical specification) including AHU & Relay Rooms as applicable SET 1 Included 0.00 0 0
37 7000030923 470 280 10 Inst. MAIN EARTHMAT 100003103 998731 18% 40 mm MS rod for Main Earthmat KM 1 Included 0.00 0 0
38 7000030923 480 290 10 Inst. ERECTION HARDWARE 100000512 998731 18% Erection Hardware for 220kV DM-type layout for GIS termination arrangement-Line bay as per specification SET 1 Included 0.00 0 0
39 7000030923 480 290 20 Inst. ERECTION HARDWARE 100000513 998731 18% Erection Hardware for 220kV DM-type layout for GIS termination arrangement-Transformer bay as per specification SET 2 Included 0.00 0 0
40 7000030923 520 350 10 Civil works 100004518 995433 18% Excavation in all kind of soil including rock for all leads and lifts, backfilling, disposal of surplus earth within a lead up to2Km as per technical specification. The surplus earth shall be roughly graded . M3 1898 Included 0.00 0 0
41 7000030923 520 350 20 Civil works 100011662 995433 18% Excavation in hard rock which require blasting (including chemical blasting and rock excavated using specialized tools) for allfoundation works including stacking, measuring, disposal etc.for all leads and lifts as per technical specification. M3 1265 Included 0.00 0 0
42 7000030923 520 350 30 Civil works 100001325 995454 18% Providing and laying of Plain Cement Concrete (PCC) (1:4:8) M3 154 Included 0.00 0 0
43 7000030923 520 350 40 Civil works 100001326 995454 18% Providing and laying of Plain Cement Concrete (PCC) (1:2:4) M3 40 Included 0.00 0 0
44 7000030923 520 350 50 Civil works 100048595 995423 18% Providing & laying non-woven Geo-synthetics fabric of minimum 200 GSM in separration layer between sub garde and stone spreading inswitchyard as per Technical Specification and direction of Engineer-in-Charge. M2 2275 Included 0.00 0 0
45 7000030923 520 350 60 Civil works 100016607 995451 18% Providing and laying of Reinforced Cement Concrete M30 including pre cast, shuttering, Grouting of pockets & underpinning butexcluding steel reinforcement M3 1374 Included 0.00 0 0
46 7000030923 520 350 70 Civil works 100016681 995454 18% Reinforcement steel meeting corrosion resistance properties as per IS:1786 and manufacturer specification​ MT 111 Included 0.00 0 0
47 7000030923 520 350 80 Civil works 100001714 995428 18% Stone spreading in switchyard excluding PCC M2 2025 Included 0.00 0 0
48 7000030923 520 350 90 Civil works 100001713 995424 18% Antiweed treatment M2 2275 Included 0.00 0 0
49 7000030923 520 350 100 Civil works 100001712 995428 18% Removing,cleaning and washing of existing stones and respreading of stones in switchyard excluding PCC M2 250 Included 0.00 0 0
50 7000030923 520 350 110 Civil works 100002911 995432 18% Earthwork in excavation & filling in all types of soil and soft/disintegrated rock in open areas/nallas/channels, to the requiredslopes, shapes, levels, elevations and profile, including trimming of bottom and slopes of excavation, bailing out rain(dewatering), pumping, removal of slush, preparing embankments/marginal banks, loosening, dressing, spreading material in layers notexceeding 200mm, as per direction of Engineer-in-Charge, water flooding, compacting to achieve 95% consolidation at optimum moisturecontent, finishing etc. all complete, for all leads and lifts within leveling boundary, including disposal of surplus earth andstacking of unsuitable material within a lead of 2.0 Km beyond substation boundary, with all labour, material, tools, tackles andequipment, safeguards and incidentals, Royalty,taxes etc. as necessary, as per drawings, specification and directions of theEngineer-in-Charge. Clearing of jungle is included in this item. (Only excavation/cutting will be measured for payment purpose.) M3 8438 Included 0.00 0 0
51 7000030923 520 350 120 Civil works 100004467 995432 18% Earthwork in Excavation in hard rock including stacking of serviceable material within substation boundary and disposal ofunserviceable material for leads up to 2000 meters beyond the levelling boundary as per TS M3 4219 Included 0.00 0 0
52 7000030923 520 350 130 Civil works 100002583 995432 18% Supply of earth (excluding rock & boulders) at site including royalty, carriage and filling in specified areas in layers notexceeding 200mm in depth, compacting under optimum moisture condition to achieve 95% of Proctor density, finishing etc. allcomplete, for all leads & lifts, with all labour, material, tools, tackles, equipments, safeguards & incidentals as necessary as perdrawings, specification and direction of the Engineer- in- Charge. M3 100 Included 0.00 0 0
53 7000030923 520 350 140 Civil works 100001478 995454 18% Cable Trench including all types of crossings, all metallic works and sump pit including concrte and reinforcement steel Section 2-2 M 225 Included 0.00 0 0
54 7000030923 520 350 150 Civil works 100001479 995454 18% Cable Trench including all types of crossings, all metallic works and sump pit including concrte and reinforcement steel Section 3-3 M 100 Included 0.00 0 0
55 7000030923 520 350 160 Civil works 100001480 995454 18% Cable Trench including all types of crossings, all metallic works and sump pit including concrte and reinforcement steel Section 4-4 M 25 Included 0.00 0 0
56 7000030923 520 350 170 Civil works 100007701 995462 18% Supplying and erecting dewatering pumps- 2 HP EA 1 Included 0.00 0 0
57 7000030923 520 350 180 Civil works 100008110 995421 18% 3.75m wide Bitumen road with earthen shoulder including 100 mm dia RCC Hume Pipe @ 100 metre interval as per drawing and TS (as perDSR item no 16.35 and 16.30.1) and including 225 mm thick WBM in three equal layers of 75 mm each as per CPWD specification. M2 1069 Included 0.00 0 0
58 7000030923 520 350 190 Civil works 100015791 995454 18% All civil works for Drains construction of Section A-A including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 285 Included 0.00 0 0
59 7000030923 520 350 200 Civil works 100015792 995454 18% All civil works for Drains construction of Section B-B including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 200 Included 0.00 0 0
60 7000030923 520 350 210 Civil works 100015793 995454 18% All civil works for Drains construction of Section C-C including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 86 Included 0.00 0 0
61 7000030923 520 350 220 Civil works 100015794 995454 18% All civil works for Drains construction of Section D-D including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 30 Included 0.00 0 0
62 7000030923 520 350 230 Civil works 100001744 995414 18% PEB - 220 kV GIS - Civil Works. All civil works as per drawing and specifications complete, including - brickwork,finishing(external and internal), windows etc. However, excavation, PCC, RCC and reinforcement shall be paid separately as per BPS M2 648 Included 0.00 0 0
63 7000030923 520 350 240 Civil works 100004430 995416 18% 220 kV PEB Panel Room for GIS Hall - Civil Works All civil works complete as per TS, including - brickwork, finishing (externaland internal), windows etc. However, excavation, concrete (all types) and reinforcement steel shall be measured and paid separatelyas per respective item of BPS. M2 105 Included 0.00 0 0
64 7000030923 520 350 250 Civil works 100004426 995416 18% 220 kV PEB AHU Room for GIS Hall - Civil Works All civil works complete as per TS, including - brickwork, finishing (external andinternal), windows etc. However, excavation, concrete (all types) and reinforcement steel shall be measured and paid separately asper respective item of BPS. M2 27 Included 0.00 0 0
65 7000030923 520 350 260 Civil works 100001721 995428 18% Supplying, filling and compacting stone boulders mixed with sand under foundations, roads, cable trenches, drains etc in layers notexceeding 250mm thickness including ramming, watering compacting M3 50 Included 0.00 0 0
66 7000030923 520 350 270 Civil works 100003295 995429 18% Dismantling of RCC in foundation including disposal of debris and reinforcement bars of dismantled RCC works within substationboundaries as per direction of enginner incahrge M3 10 Included 0.00 0 0
67 7000030923 520 350 280 Civil works 100001442 995456 18% Dismantling of existing brick drain (300mm widex500mm deep) M 15 Included 0.00 0 0
68 7000030923 520 350 290 Civil works 100004463 995456 18% Random Rubble masonry for Retaining wall with locally available stone in cement sand mortar 1:6 (1 Cement: 6 coarse sand) includinglevelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size), Raised and Cutpointing on exposed surface, weep holes/PVC pipe sleeves of 100 mm dia (medium class) @ 1 metre C/C staggered . The top of theretaining wall to be provided with cement concrete 1:2:4. However items of excavation, concrete (1:2:4) shall be payable underrespective items of BPS M3 50 Included 0.00 0 0
69 7000030923 520 350 300 Civil works 100039289 998335 18% Preparation of design and all types ofdrawings for 765 kV or 400 kV or 220 kVtowers. EA 1 Included 0.00 0 0
70 7000030923 520 350 310 Civil works 100039290 998335 18% Preparation of design and all types ofdrawings for 765 kV or 400 kV or 220 kVbeams. EA 1 Included 0.00 0 0
71 7000030923 520 350 320 Civil works 100039291 998335 18% Preparation of design and all types of drawings for LM. EA 1 Included 0.00 0 0
72 7000030923 530 360 10 Erection of non standard structure 100001210 995455 18% Erection of Lattice Structures (MS Steel), to be designed during detailed engineering, for towers, beams and equipment supportstructure including pack plates / packwashers and gusset plates excluding fasteners and foundation bolts MT 30 Included 0.00 0 0
73 7000030923 530 360 20 Erection of non standard structure 100001209 995455 18% Erection of Lattice Structures (HT Steel), to be designed during detailed engineering, for towers, beams and equipment supportstructure including pack plates / packwashers and gusset plates excluding fasteners and foundation bolts. MT 5 Included 0.00 0 0
74 7000030923 530 360 30 Erection of non standard structure 100001680 995455 18% Erection of fasteners ( nuts, bolts and washers ) including step bolts for lattice and pipe structures to be designed duringdetailed engineering MT 2 Included 0.00 0 0
75 7000030923 530 360 40 Erection of non standard structure 100001681 995455 18% Erection of foundation bolts including nuts, checknut and washers for lattice and pipe structures to be designed during detailedengineering MT 5 Included 0.00 0 0
C Extn. of 400/220kV Bhuj-II GIS S/S
1 7000030924 1170 150 130 Inst. GIS Portion-420 kV GIS Equipments 100017060 998736 18% 420KV, 3150 A, 63 KA, SF6 GIS SWITCHABLE LINE REACTOR BAY MODULE AS PER SECTION-PROJECT, TECHNICAL SPECIFICATION SET 2 Included 0.00 0 0
2 7000030924 1170 150 150 Inst. GIS Portion-420 kV GIS Equipments 100023510 998736 18% 420kV, 3150 A, 63 kA, SF6 GIS ICT feeder bay module for IV side connection with 765kV ICT as per Section-Project, Technicalspecification SET 1 Included 0.00 0 0
3 7000030924 1170 150 160 Inst. GIS Portion-420 kV GIS Equipments 100002132 998736 18% 420kV, 3150 A, 63 kA, SF6 GIS Tie bay module(without PIR) as per Section-Project, Technical specification SET 1 Included 0.00 0 0
4 7000030924 1170 150 170 Inst. GIS Portion-420 kV GIS Equipments 100000268 998736 18% Controlled Switching Device for 420 kV, 3-ph Circuit Breaker EA 9 Included 0.00 0 0
5 7000030924 1170 150 180 Inst. GIS Portion-420 kV GIS Equipments 100002392 998736 18% 420kV, SF6 to Air Bushing alongwithassociated support structure for 3150A,63 kA for 1 sec. Single Phase EA 12 Included 0.00 0 0
6 7000030924 1170 150 190 Inst. GIS Portion-420 kV GIS Equipments 100002140 998736 18% 420kV, 3000A/3150, 63kA, Single phase, SF6 Gas Insulated Bus Duct (GIB) outsideGIS Hall along with associated support structure M 535 Included 0.00 0 0
7 7000030924 1170 150 200 Inst. GIS Portion-420 kV GIS Equipments 100001843 998736 18% 420kV, 3150 A, 63 kA, SF6 GIS Tie bay module(with PIR) as per Section-Project, Technical specification SET 2 Included 0.00 0 0
8 7000030924 1170 150 210 Inst. GIS Portion-420 kV GIS Equipments 100001832 998736 18% 420 kV, 3150 A, 63 kA, SF6 GIS Line feeder bay module(with PIR) as per Section-Project, Technical specification SET 2 Included 0.00 0 0
9 7000030924 1170 150 230 Inst. GIS Portion-420 kV GIS Equipments 100001826 998736 18% 420kV, 3150 A, 63 kA, SF6 GIS ICT feeder bay module as per Section-Project, Technical specification SET 3 Included 0.00 0 0
10 7000030924 1260 160 50 Inst. GIS Portion-245 kV GIS Equipments 100002390 998736 18% 245kV,1600A, 50 kA for 1 sec SF6 to Air Bushing EA 27 Included 0.00 0 0
11 7000030924 1260 160 70 Inst. GIS Portion-245 kV GIS Equipments 100002153 998736 18% 245kV,1600A, 50kA,3 Single phase/3Phase, SF6 Gas Insulated Bus Duct(GIB) outside GIS Hall alongwithassociated support structure(Quantitymentioned here is for 3 Phase type) M 314 Included 0.00 0 0
12 7000030924 1260 160 80 Inst. GIS Portion-245 kV GIS Equipments 100000367 998736 18% 245kV, 1600 A, 50 kA, SF6 GIS ICT feeder bay module SET 3 Included 0.00 0 0
13 7000030924 1260 160 90 Inst. GIS Portion-245 kV GIS Equipments 100000377 998736 18% 245kV, 1600 A, 50 kA, SF6 GIS Line feeder bay module for connecting Overhead line (Air/SF6) with GIS through gas insulatedinterconnection bus etc SET 6 Included 0.00 0 0
14 7000030924 1180 170 10 Inst. 420 kV AIS EQUIPMENTS 100000328 998736 18% 336kV Surge Arrester (1-phase) EA 12 Included 0.00 0 0
15 7000030924 1180 170 20 Inst. 420 kV AIS EQUIPMENTS 100005443 998734 18% 420KV, 1-PHASE BUS POST INSULATORS EA 18 Included 0.00 0 0
16 7000030924 1270 180 10 Inst. 245 kV AIS EQUIPMENTS 100001907 998736 18% 245 kV,1 phase Bus Post Insulator (except for Line Traps) EA 45 Included 0.00 0 0
17 7000030924 1270 180 20 Inst. 245 kV AIS EQUIPMENTS 100000484 998736 18% 216kV Surge Arrester (1-phase) EA 27 Included 0.00 0 0
18 7000030924 1270 180 30 Inst. 245 kV AIS EQUIPMENTS 100000448 998736 18% 245 kV, 4400pf Capacitive Voltage Transformer (1- Phase) EA 18 Included 0.00 0 0
19 7000030924 1270 180 40 Inst. 245 kV AIS EQUIPMENTS 100002048 998734 18% 220kV,1600A,0.5mH ,50kA Line Trap EA 12 Included 0.00 0 0
20 7000030924 1270 180 50 Inst. 245 kV AIS EQUIPMENTS 100000884 998734 18% 245 kV ,1 phase Bus Post Insulators for Line Traps EA 36 Included 0.00 0 0
21 7000030924 1190 190 10 Inst. CONTROL & RELAY PANEL 100016779 998736 18% 400kV Circuit Breaker Relay Panel (with Automation) EA 11 Included 0.00 0 0
22 7000030924 1190 190 20 Inst. CONTROL & RELAY PANEL 100000731 998736 18% 400kV Transformer Protection Panel (For both HV & MV side)-(with Automation) EA 3 Included 0.00 0 0
23 7000030924 1190 190 30 Inst. CONTROL & RELAY PANEL 100016778 998736 18% 220kV Circuit Breaker Relay Panel (with Automation) EA 9 Included 0.00 0 0
24 7000030924 1190 190 40 Inst. CONTROL & RELAY PANEL 100000738 998736 18% 220kV Line Protection Panel (with Automation) EA 6 Included 0.00 0 0
25 7000030924 1190 190 50 Inst. CONTROL & RELAY PANEL 100000743 998736 18% Augmentation of existing 220kV bus bar protection scheme.(No. of bays as per specification)-(with Automation) SET 1 Included 0.00 0 0
26 7000030924 1190 190 60 Inst. CONTROL & RELAY PANEL 100000735 998736 18% Augmentation of existing 400kV bus bar protection scheme.(No. of bays as per specification)-(with Automation) SET 1 Included 0.00 0 0
27 7000030924 1200 200 10 Inst. SUBSTATION AUTOMATION SYSTEM 100002075 998736 18% Augmentation of Substation automation System for 400kV Tie bay as per Technical Specification EA 3 Included 0.00 0 0
28 7000030924 1200 200 20 Inst. SUBSTATION AUTOMATION SYSTEM 100002069 998736 18% Augmentation of Substation automation System for 400kV Main bay as per Technical Specification EA 6 Included 0.00 0 0
29 7000030924 1200 200 30 Inst. SUBSTATION AUTOMATION SYSTEM 100002070 998736 18% Augmentation of Substation automation System for 220kV bay as per Technical Specification EA 9 Included 0.00 0 0
30 7000030924 1200 200 40 Inst. SUBSTATION AUTOMATION SYSTEM 100002077 998736 18% Augmentation of Substation automation System for 400kV Switchable Line Reactor Bay as per Technical Specification EA 2 Included 0.00 0 0
31 7000030924 1210 210 10 Inst. FIRE PROTECTION SYSTEM 100000983 998736 18% HVW spray system, Hydrant system and complete U/G & O/G piping and accessories etc. out side the pump house for 500MVA ,400KV/220/33 kV, 3-phase Autotransformer SET 3 Included 0.00 0 0
32 7000030924 1220 220 10 Inst. POWER & CONTROL CABLE 100002182 998736 18% 1.1kV grade Control Cables (PVCinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0
33 7000030924 1220 220 20 Inst. POWER & CONTROL CABLE 100002181 998736 18% 1.1kV grade Power Cables (PVCinsulated)along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0
34 7000030924 1220 220 30 Inst. POWER & CONTROL CABLE 100002180 998736 18% 1.1kV grade Power Cables (XLPEinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0
35 7000030924 1250 230 30 Inst. LIGHTING SYSTEM 100004941 998731 18% RP Type Receptacle of 63A as per technical specification EA 2 Included 0.00 0 0
36 7000030924 1250 230 60 Inst. LIGHTING SYSTEM 100001021 995461 18% Lighting Panel type ACP-2 as per technical specification EA 1 Included 0.00 0 0
37 7000030924 1250 230 80 Inst. LIGHTING SYSTEM 100004852 998731 18% Lighting Fixture LED Luminaires type FL-1 as per tech. specifications EA 20 Included 0.00 0 0
38 7000030924 1250 230 90 Inst. LIGHTING SYSTEM 100004926 998731 18% Lighting Fixture LED Luminaires type FL2 as per tech. specifications EA 20 Included 0.00 0 0
39 7000030924 1250 230 100 Inst. LIGHTING SYSTEM 100004937 998731 18% Fire Wall Mounted LED Luminarie Type FL-2 (250W) EA 6 Included 0.00 0 0
40 7000030924 1230 240 10 Inst. MAIN EARTHMAT 100003103 998731 18% 40 mm MS rod for Main Earthmat KM 4 Included 0.00 0 0
41 7000030924 1240 250 10 Inst. ERECTION HARDWARE 100002188 998731 18% Erection Hardware for 400kV I type layout for GIS termination arrangement-Transformer bay as per technical specification SET 4 Included 0.00 0 0
42 7000030924 1240 250 20 Inst. ERECTION HARDWARE 100000512 998731 18% Erection Hardware for 220kV DM-type layout for GIS termination arrangement-Line bay as per specification SET 6 Included 0.00 0 0
43 7000030924 1240 250 30 Inst. ERECTION HARDWARE 100000513 998731 18% Erection Hardware for 220kV DM-type layout for GIS termination arrangement-Transformer bay as per specification SET 3 Included 0.00 0 0
44 7000030924 1310 270 10 civil works 100004518 995433 18% Excavation in all kind of soil including rock for all leads and lifts, backfilling, disposal of surplus earth within a lead up to2Km as per technical specification. The surplus earth shall be roughly graded . M3 7123 Included 0.00 0 0
45 7000030924 1310 270 20 civil works 100011662 995433 18% Excavation in hard rock which require blasting (including chemical blasting and rock excavated using specialized tools) for allfoundation works including stacking, measuring, disposal etc.for all leads and lifts as per technical specification. M3 4317 Included 0.00 0 0
46 7000030924 1310 270 30 civil works 100001325 995454 18% Providing and laying of Plain Cement Concrete (PCC) (1:4:8) M3 349 Included 0.00 0 0
47 7000030924 1310 270 40 civil works 100001326 995454 18% Providing and laying of Plain Cement Concrete (PCC) (1:2:4) M3 10 Included 0.00 0 0
48 7000030924 1310 270 50 civil works 100048595 995423 18% Providing & laying non-woven Geo-synthetics fabric of minimum 200 GSM in separration layer between sub garde and stone spreading inswitchyard as per Technical Specification and direction of Engineer-in-Charge. M2 7160 Included 0.00 0 0
49 7000030924 1310 270 60 civil works 100016607 995451 18% Providing and laying of Reinforced Cement Concrete M30 including pre cast, shuttering, Grouting of pockets & underpinning butexcluding steel reinforcement M3 3329 Included 0.00 0 0
50 7000030924 1310 270 70 civil works 100016681 995454 18% Reinforcement steel meeting corrosion resistance properties as per IS:1786 and manufacturer specification​ MT 219 Included 0.00 0 0
51 7000030924 1310 270 80 civil works 100001331 995455 18% Misc. Structural steel including rails, embedments, edge protection angles, gratings etc. but excluding the reinforcement steel andsteel for lattice and pipe structures. MT 91 Included 0.00 0 0
52 7000030924 1310 270 90 civil works 100001330 995428 18% Stone filling (40 mm size) for transformer/Reactor foundation M3 62 Included 0.00 0 0
53 7000030924 1310 270 100 civil works 100001714 995428 18% Stone spreading in switchyard excluding PCC M2 6660 Included 0.00 0 0
54 7000030924 1310 270 110 civil works 100001713 995424 18% Antiweed treatment M2 7160 Included 0.00 0 0
55 7000030924 1310 270 120 civil works 100001712 995428 18% Removing,cleaning and washing of existing stones and respreading of stones in switchyard excluding PCC M2 500 Included 0.00 0 0
56 7000030924 1310 270 130 civil works 100054773 995454 18% External finishing/ painting of fire wall with cement wash M2 720 Included 0.00 0 0
57 7000030924 1310 270 140 civil works 100002911 995432 18% Earthwork in excavation & filling in all types of soil and soft/disintegrated rock in open areas/nallas/channels, to the requiredslopes, shapes, levels, elevations and profile, including trimming of bottom and slopes of excavation, bailing out rain(dewatering), pumping, removal of slush, preparing embankments/marginal banks, loosening, dressing, spreading material in layers notexceeding 200mm, as per direction of Engineer-in-Charge, water flooding, compacting to achieve 95% consolidation at optimum moisturecontent, finishing etc. all complete, for all leads and lifts within leveling boundary, including disposal of surplus earth andstacking of unsuitable material within a lead of 2.0 Km beyond substation boundary, with all labour, material, tools, tackles andequipment, safeguards and incidentals, Royalty,taxes etc. as necessary, as per drawings, specification and directions of theEngineer-in-Charge. Clearing of jungle is included in this item. (Only excavation/cutting will be measured for payment purpose.) M3 27750 Included 0.00 0 0
58 7000030924 1310 270 150 civil works 100004467 995432 18% Earthwork in Excavation in hard rock including stacking of serviceable material within substation boundary and disposal ofunserviceable material for leads up to 2000 meters beyond the levelling boundary as per TS M3 13875 Included 0.00 0 0
59 7000030924 1310 270 160 civil works 100002583 995432 18% Supply of earth (excluding rock & boulders) at site including royalty, carriage and filling in specified areas in layers notexceeding 200mm in depth, compacting under optimum moisture condition to achieve 95% of Proctor density, finishing etc. allcomplete, for all leads & lifts, with all labour, material, tools, tackles, equipments, safeguards & incidentals as necessary as perdrawings, specification and direction of the Engineer- in- Charge. M3 100 Included 0.00 0 0
60 7000030924 1310 270 170 civil works 100001478 995454 18% Cable Trench including all types of crossings, all metallic works and sump pit including concrte and reinforcement steel Section 2-2 M 200 Included 0.00 0 0
61 7000030924 1310 270 180 civil works 100001479 995454 18% Cable Trench including all types of crossings, all metallic works and sump pit including concrte and reinforcement steel Section 3-3 M 200 Included 0.00 0 0
62 7000030924 1310 270 190 civil works 100001480 995454 18% Cable Trench including all types of crossings, all metallic works and sump pit including concrte and reinforcement steel Section 4-4 M 50 Included 0.00 0 0
63 7000030924 1310 270 200 civil works 100020960 995461 18% RCC culvert crossings including supplying and laying hume pipe 250mm dia of grade (NP-3) excluding concrete as per specification. M 10 Included 0.00 0 0
64 7000030924 1310 270 210 civil works 100020961 995461 18% RCC culvert crossings including supplying and laying hume pipe 300mm dia of grade (NP-3) excluding concrete as per specification. M 10 Included 0.00 0 0
65 7000030924 1310 270 220 civil works 100020962 995461 18% RCC culvert crossings including supplying and laying hume pipe 450mm dia of grade (NP-3) excluding concrete as per specification. M 10 Included 0.00 0 0
66 7000030924 1310 270 230 civil works 100007701 995462 18% Supplying and erecting dewatering pumps- 2 HP EA 1 Included 0.00 0 0
67 7000030924 1310 270 240 civil works 100001409 995462 18% Supplying and erecting dewatering pumps-5 HP EA 1 Included 0.00 0 0
68 7000030924 1310 270 250 civil works 100001457 995421 18% Construction of rail cum road as per drawing including all item such as excavation,compactions, rolling watering, WBM etc. butexcluding concrete reinforcement and structural steel-Section having four rails for auto transformer. M2 332 Included 0.00 0 0
69 7000030924 1310 270 260 civil works 100015791 995454 18% All civil works for Drains construction of Section A-A including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 20 Included 0.00 0 0
70 7000030924 1310 270 270 civil works 100015792 995454 18% All civil works for Drains construction of Section B-B including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 20 Included 0.00 0 0
71 7000030924 1310 270 280 civil works 100015793 995454 18% All civil works for Drains construction of Section C-C including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 20 Included 0.00 0 0
72 7000030924 1310 270 290 civil works 100015794 995454 18% All civil works for Drains construction of Section D-D including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 10 Included 0.00 0 0
73 7000030924 1310 270 300 civil works 130000761 995428 18% 14.4.2 Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointingwith cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. : 150 mm dia M 75 Included 0.00 0 0
74 7000030924 1310 270 310 civil works 130000762 995428 18% 14.4.3 Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointingwith cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. : 250 mm dia M 75 Included 0.00 0 0
75 7000030924 1310 270 320 civil works 100001721 995428 18% Supplying, filling and compacting stone boulders mixed with sand under foundations, roads, cable trenches, drains etc in layers notexceeding 250mm thickness including ramming, watering compacting M3 100 Included 0.00 0 0
76 7000030924 1310 270 330 civil works 100003295 995429 18% Dismantling of RCC in foundation including disposal of debris and reinforcement bars of dismantled RCC works within substationboundaries as per direction of enginner incahrge M3 10 Included 0.00 0 0
77 7000030924 1310 270 340 civil works 100001442 995456 18% Dismantling of existing brick drain (300mm widex500mm deep) M 20 Included 0.00 0 0
78 7000030924 1310 270 350 civil works 100004463 995456 18% Random Rubble masonry for Retaining wall with locally available stone in cement sand mortar 1:6 (1 Cement: 6 coarse sand) includinglevelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size), Raised and Cutpointing on exposed surface, weep holes/PVC pipe sleeves of 100 mm dia (medium class) @ 1 metre C/C staggered . The top of theretaining wall to be provided with cement concrete 1:2:4. However items of excavation, concrete (1:2:4) shall be payable underrespective items of BPS M3 50 Included 0.00 0 0
79 7000030924 1310 270 360 civil works 100039289 998335 18% Preparation of design and all types ofdrawings for 765 kV or 400 kV or 220 kVtowers. EA 2 Included 0.00 0 0
80 7000030924 1310 270 370 civil works 100039290 998335 18% Preparation of design and all types ofdrawings for 765 kV or 400 kV or 220 kVbeams. EA 1 Included 0.00 0 0
81 7000030924 1310 270 380 civil works 100039291 998335 18% Preparation of design and all types of drawings for LM. EA 1 Included 0.00 0 0
82 7000030924 1320 280 10 Erection of non standard structure 100001210 995455 18% Erection of Lattice Structures (MS Steel), to be designed during detailed engineering, for towers, beams and equipment supportstructure including pack plates / packwashers and gusset plates excluding fasteners and foundation bolts MT 146 Included 0.00 0 0
83 7000030924 1320 280 20 Erection of non standard structure 100001209 995455 18% Erection of Lattice Structures (HT Steel), to be designed during detailed engineering, for towers, beams and equipment supportstructure including pack plates / packwashers and gusset plates excluding fasteners and foundation bolts. MT 5 Included 0.00 0 0
84 7000030924 1320 280 30 Erection of non standard structure 100001680 995455 18% Erection of fasteners ( nuts, bolts and washers ) including step bolts for lattice and pipe structures to be designed duringdetailed engineering MT 6 Included 0.00 0 0
85 7000030924 1320 280 40 Erection of non standard structure 100001681 995455 18% Erection of foundation bolts including nuts, checknut and washers for lattice and pipe structures to be designed during detailedengineering MT 22 Included 0.00 0 0
86 7000030924 1580 320 10 Service-Tele BoQ 100002812 998734 18% SDH Equipment (STM-16 MADM upto 5 MSP protected directions)-Base Equipment (Common cards, Cross Connect/control cards, optical basecards, power supply cards, power cabling, other hardware and accessories including sub racks, patch cord, DDF etc fully equipedexcluding optical interface & Tributary cards EA 2 Included 0.00 0 0
87 7000030924 1580 320 20 Service-Tele BoQ 170000433 998734 18% Optical Interface Cards/SFP# -S16.1 for SDH Equipment-STM-16 EA 4 Included 0.00 0 0
88 7000030924 1580 320 30 Service-Tele BoQ 100002825 998734 18% Tributary interface- E1 interface (Minimum 16 nos.) SET 4 Included 0.00 0 0
89 7000030924 1580 320 40 Service-Tele BoQ 170000550 998336 18% Ethernet Interface 10/100 Base T with Layer-2 switching (Min 8 Interfaces per card) EA 4 Included 0.00 0 0
90 7000030924 1580 320 50 Service-Tele BoQ 100002829 998734 18% Tributary interface-Gigabit Ethernet Interfaces 10/100 Mbps with Layer -2 Switching (minimum 2 nos.) SET 2 Included 0.00 0 0
91 7000030924 1580 320 60 Service-Tele BoQ 170000375 998734 18% Equipment Cabinets-For SDH Equipments EA 1 Included 0.00 0 0
92 7000030924 1580 320 90 Service-Tele BoQ 170004395 998336 18% Fibre Optic Approach cabling: Including installation hardware like GI pipe, elbow, conduits, accessories etc.: 48 Fibre KM 2 Included 0.00 0 0
93 7000030924 1580 320 100 Service-Tele BoQ 170005265 998336 18% Installation of 192 Fibre FODP : Indoor Type, Rack Mounted with FCPC Coupling & Pigtails (5mtrs) EA 2 Included 0.00 0 0
D SS EXTN-400/220kV ICT(10th) AT BHUJ PS Revaluation of J column Tax Calculation
1 7000030914 490 170 10 Inst. 400 kV & 220 kV AIS EQUIPMENT 100000328 998736 18% 336kV Surge Arrester (1-phase) EA 3 Included 0.00 0 0
2 7000030914 490 170 20 Inst. 400 kV & 220 kV AIS EQUIPMENT 100000484 998736 18% 216kV Surge Arrester (1-phase) EA 3 Included 0.00 0 0
3 7000030914 490 170 30 Inst. 400 kV & 220 kV AIS EQUIPMENT 100000498 998736 18% 245 kV Bust Post Insulator (Except for wave traps) EA 22 Included 0.00 0 0
4 7000030914 490 170 40 Inst. 400 kV & 220 kV AIS EQUIPMENT 100000340 998736 18% 420 kV Bus Post Insulator (Except for wave traps) EA 3 Included 0.00 0 0
5 7000030914 490 170 50 Inst. 400 kV & 220 kV AIS EQUIPMENT 100000287 998736 18% 420kV, 3150A, 63KA, Isolator (3-phase)(Double Break) with one E/S EA 2 Included 0.00 0 0
6 7000030914 490 170 60 Inst. 400 kV & 220 kV AIS EQUIPMENT 100000267 998736 18% 420kV, 3150A, 63kA Circuit Breaker(3-Phase) without closing resistor(with support structure) EA 1 Included 0.00 0 0
7 7000030914 490 170 70 Inst. 400 kV & 220 kV AIS EQUIPMENT 100000274 998736 18% 420 kV, 3000A, 63KA, 1-Phase CurrentTransformer with 120% extended currentrating EA 3 Included 0.00 0 0
8 7000030914 490 170 80 Inst. 400 kV & 220 kV AIS EQUIPMENT 100000268 998736 18% Controlled Switching Device for 420 kV, 3-ph Circuit Breaker EA 1 Included 0.00 0 0
9 7000030914 500 180 10 Inst. GIS Portion-220 kV GIS Equipment 100002390 998736 18% 245kV,1600A, 50 kA for 1 sec SF6 to Air Bushing EA 6 Included 0.00 0 0
10 7000030914 500 180 20 Inst. GIS Portion-220 kV GIS Equipment 100002153 998736 18% 245kV,1600A, 50kA,3 Single phase/3Phase, SF6 Gas Insulated Bus Duct(GIB) outside GIS Hall alongwithassociated support structure(Quantitymentioned here is for 3 Phase type) M 400 Included 0.00 0 0
11 7000030914 510 190 10 Inst. Erection Hardware (400kV & 220 kV) 100002891 998731 18% Erection Hardware for 400kV I type layout-Any feeder Extn. on existing half dia(for ICT Bay)(including all required interconnectionsfor the transformer area) as per technical specification SET 1 Included 0.00 0 0
12 7000030914 510 190 20 Inst. Erection Hardware (400kV & 220 kV) 100002306 998731 18% Erection Hardware for 220kV DM type layout-Transformer bay as per technical specification SET 1 Included 0.00 0 0
13 7000030914 520 200 10 Inst. CONTROL & RELAY PANEL 100000743 998736 18% Augmentation of existing 220kV bus bar protection scheme.(No. of bays as per specification)-(with Automation) SET 1 Included 0.00 0 0
14 7000030914 520 200 40 Inst. CONTROL & RELAY PANEL 100000731 998736 18% 400kV Transformer Protection Panel (For both HV & MV side)-(with Automation) EA 1 Included 0.00 0 0
15 7000030914 520 200 50 Inst. CONTROL & RELAY PANEL 100016778 998736 18% 220kV Circuit Breaker Relay Panel (with Automation) EA 1 Included 0.00 0 0
16 7000030914 520 200 60 Inst. CONTROL & RELAY PANEL 100016779 998736 18% 400kV Circuit Breaker Relay Panel (with Automation) EA 1 Included 0.00 0 0
17 7000030914 520 200 70 Inst. CONTROL & RELAY PANEL 100000735 998736 18% Augmentation of existing 400kV bus bar protection scheme.(No. of bays as per specification)-(with Automation) SET 1 Included 0.00 0 0
18 7000030914 620 210 10 Inst. SUBSTATION AUTOMATION SYSTEM 100002070 998736 18% Augmentation of Substation automation System for 220kV bay as per Technical Specification EA 1 Included 0.00 0 0
19 7000030914 620 210 20 Inst. SUBSTATION AUTOMATION SYSTEM 100002069 998736 18% Augmentation of Substation automation System for 400kV Main bay as per Technical Specification EA 1 Included 0.00 0 0
20 7000030914 530 220 10 Inst. ILLUMINATION SYSTEM (OUTDOOR) 100001021 995461 18% Lighting Panel type ACP-2 as per technical specification EA 1 Included 0.00 0 0
21 7000030914 530 220 20 Inst. ILLUMINATION SYSTEM (OUTDOOR) 100001024 998731 18% Sub Lighting panel (outdoor) type SLP (Switchyard and Street Lighting) EA 2 Included 0.00 0 0
22 7000030914 530 220 30 Inst. ILLUMINATION SYSTEM (OUTDOOR) 100004852 998731 18% Lighting Fixture LED Luminaires type FL-1 as per tech. specifications EA 8 Included 0.00 0 0
23 7000030914 530 220 40 Inst. ILLUMINATION SYSTEM (OUTDOOR) 100004926 998731 18% Lighting Fixture LED Luminaires type FL2 as per tech. specifications EA 8 Included 0.00 0 0
24 7000030914 540 230 10 Inst. Power & Control cables 100002182 998736 18% 1.1kV grade Control Cables (PVCinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0
25 7000030914 540 230 20 Inst. Power & Control cables 100002180 998736 18% 1.1kV grade Power Cables (XLPEinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0
26 7000030914 540 230 30 Inst. Power & Control cables 100002181 998736 18% 1.1kV grade Power Cables (PVCinsulated)along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0
27 7000030914 550 240 10 Inst. FIRE PROTECTION SYSTEM 100000983 998736 18% HVW spray system, Hydrant system and complete U/G & O/G piping and accessories etc. out side the pump house for 500MVA ,400KV/220/33 kV, 3-phase Autotransformer SET 1 Included 0.00 0 0
28 7000030914 550 240 20 Inst. FIRE PROTECTION SYSTEM 100016787 998736 18% HVW spray system, Hydrant system and complete U/G & O/G piping and accessories etc. out side the pump house for 420kV 3 phase BUSReactor SET 1 Included 0.00 0 0
29 7000030914 560 250 10 Inst. VISUAL MONITORING SYSTEM 100002500 998731 18% Color IP camera, with PAN, TILT and ZOOM facilities, alongwith all required Items, Accessories, Line Interface units, Fiber patchcords, Power supply units, Junction Boxes, Cables, Fiber Optic Cables, etc., and including Integration in existing Hardware andSoftware for Augmentation of Visual Monitoring System as per technical specification. SET 1 Included 0.00 0 0
30 7000030914 580 260 10 Inst. 220 kV HYBRID GIS 100007282 998736 18% 245kV, 1600 A, DM Type SF6 MTS/HYBRID GIS ICT/LINEfeeder baySwitchgear Assembly as per Section-Project, Technical specification . EA 1 Included 0.00 0 0
31 7000030914 590 270 10 Inst. Main Earthmat 100003103 998731 18% 40 mm MS rod for Main Earthmat KM 1 Included 0.00 0 0
32 7000030914 570 290 10 Shifting of 125 MVAr 420kV Bus Reactor 100003800 995429 18% Dismantling, shifting and re-erection of 125MVAR Shunt reactor as per TS EA 1 Included 0.00 0 0
33 7000030914 650 310 10 Civil Works 100004518 995433 18% Excavation in all kind of soil including rock for all leads and lifts, backfilling, disposal of surplus earth within a lead up to2Km as per technical specification. The surplus earth shall be roughly graded . M3 3354 Included 0.00 0 0
34 7000030914 650 310 20 Civil Works 100001325 995454 18% Providing and laying of Plain Cement Concrete (PCC) (1:4:8) M3 241 Included 0.00 0 0
35 7000030914 650 310 30 Civil Works 100016607 995451 18% Providing and laying of Reinforced Cement Concrete M30 including pre cast, shuttering, Grouting of pockets & underpinning butexcluding steel reinforcement M3 1030 Included 0.00 0 0
36 7000030914 650 310 40 Civil Works 100016681 995454 18% Reinforcement steel meeting corrosion resistance properties as per IS:1786 and manufacturer specification​ MT 73 Included 0.00 0 0
37 7000030914 650 310 50 Civil Works 100001330 995428 18% Stone filling (40 mm size) for transformer/Reactor foundation M3 35 Included 0.00 0 0
38 7000030914 650 310 60 Civil Works 100001331 995455 18% Misc. Structural steel including rails, embedments, edge protection angles, gratings etc. but excluding the reinforcement steel andsteel for lattice and pipe structures. MT 36 Included 0.00 0 0
39 7000030914 650 310 70 Civil Works 100001714 995428 18% Stone spreading in switchyard excluding PCC M2 2000 Included 0.00 0 0
40 7000030914 650 310 80 Civil Works 100001712 995428 18% Removing,cleaning and washing of existing stones and respreading of stones in switchyard excluding PCC M2 1500 Included 0.00 0 0
41 7000030914 650 310 90 Civil Works 100001713 995424 18% Antiweed treatment M2 3500 Included 0.00 0 0
42 7000030914 650 310 100 Civil Works 100048595 995423 18% Providing & laying non-woven Geo-synthetics fabric of minimum 200 GSM in separration layer between sub garde and stone spreading inswitchyard as per Technical Specification and direction of Engineer-in-Charge. M2 3500 Included 0.00 0 0
43 7000030914 650 310 110 Civil Works 100004507 995421 18% 3.75m wide Cement Concrete road with PCC shoulder including 100 mm dia RCC Hume Pipe @ 100 metre interval as per drawing and TS.However, reinforcement steel and all type concrete shall be paid separately under relevant items M2 750 Included 0.00 0 0
44 7000030914 650 310 120 Civil Works 100001457 995421 18% Construction of rail cum road as per drawing including all item such as excavation,compactions, rolling watering, WBM etc. butexcluding concrete reinforcement and structural steel-Section having four rails for auto transformer. M2 86 Included 0.00 0 0
45 7000030914 650 310 130 Civil Works 100001458 995421 18% Construction of rail cum road as per drawing including all item such as excavation,compactions, rolling watering, WBM etc. butexcluding concrete reinforcement and structural steel-Section having two rails for Reactor. M2 62 Included 0.00 0 0
46 7000030914 650 310 140 Civil Works 100001735 995462 18% RCC culverts and cable trench crossings including supplying and laying hume pipe 250mm dia of grade (NP-3) excluding concrete as perspecification. M 10 Included 0.00 0 0
47 7000030914 650 310 150 Civil Works 100001736 995462 18% RCC culverts and cable trench crossings including supplying and laying hume pipe 300mm dia of grade (NP-3) excluding concrete as perspecification. M 10 Included 0.00 0 0
48 7000030914 650 310 160 Civil Works 100001737 995462 18% RCC culverts and cable trench crossings including supplying and laying hume pipe 450mm dia of grade (NP-3) excluding concrete as perspecification. M 10 Included 0.00 0 0
49 7000030914 650 310 170 Civil Works 100020963 995461 18% RCC culvert crossings including supplying and laying hume pipe 600mm dia of grade (NP-3) excluding concrete as per specification. M 10 Included 0.00 0 0
50 7000030914 650 310 180 Civil Works 100001478 995454 18% Cable Trench including all types of crossings, all metallic works and sump pit including concrte and reinforcement steel Section 2-2 M 100 Included 0.00 0 0
51 7000030914 650 310 190 Civil Works 100001479 995454 18% Cable Trench including all types of crossings, all metallic works and sump pit including concrte and reinforcement steel Section 3-3 M 270 Included 0.00 0 0
52 7000030914 650 310 200 Civil Works 100001480 995454 18% Cable Trench including all types of crossings, all metallic works and sump pit including concrte and reinforcement steel Section 4-4 M 150 Included 0.00 0 0
53 7000030914 650 310 210 Civil Works 100015791 995454 18% All civil works for Drains construction of Section A-A including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 120 Included 0.00 0 0
54 7000030914 650 310 220 Civil Works 100015792 995454 18% All civil works for Drains construction of Section B-B including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 160 Included 0.00 0 0
55 7000030914 650 310 230 Civil Works 100015793 995454 18% All civil works for Drains construction of Section C-C including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 80 Included 0.00 0 0
56 7000030914 650 310 240 Civil Works 100015794 995454 18% All civil works for Drains construction of Section D-D including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 40 Included 0.00 0 0
57 7000030914 650 310 250 Civil Works 100002911 995432 18% Earthwork in excavation & filling in all types of soil and soft/disintegrated rock in open areas/nallas/channels, to the requiredslopes, shapes, levels, elevations and profile, including trimming of bottom and slopes of excavation, bailing out rain(dewatering), pumping, removal of slush, preparing embankments/marginal banks, loosening, dressing, spreading material in layers notexceeding 200mm, as per direction of Engineer-in-Charge, water flooding, compacting to achieve 95% consolidation at optimum moisturecontent, finishing etc. all complete, for all leads and lifts within leveling boundary, including disposal of surplus earth andstacking of unsuitable material within a lead of 2.0 Km beyond substation boundary, with all labour, material, tools, tackles andequipment, safeguards and incidentals, Royalty,taxes etc. as necessary, as per drawings, specification and directions of theEngineer-in-Charge. Clearing of jungle is included in this item. (Only excavation/cutting will be measured for payment purpose.) M3 1000 Included 0.00 0 0
58 7000030914 650 310 260 Civil Works 100002583 995432 18% Supply of earth (excluding rock & boulders) at site including royalty, carriage and filling in specified areas in layers notexceeding 200mm in depth, compacting under optimum moisture condition to achieve 95% of Proctor density, finishing etc. allcomplete, for all leads & lifts, with all labour, material, tools, tackles, equipments, safeguards & incidentals as necessary as perdrawings, specification and direction of the Engineer- in- Charge. M3 500 Included 0.00 0 0
59 7000030914 650 310 270 Civil Works 100001720 995428 18% Supplying, filling and compacting CNS material as per specification under floors, foundations, roads, cable trenches, drains etc inlayers not exceeding 200 mm thickness M3 100 Included 0.00 0 0
60 7000030914 650 310 280 Civil Works 100007701 995462 18% Supplying and erecting dewatering pumps- 2 HP EA 2 Included 0.00 0 0
61 7000030914 650 310 290 Civil Works 170002351 995421 18% DISMANTLING OF EXISTING -CONCRETE ROAD . M2 100 Included 0.00 0 0
62 7000030914 650 310 300 Civil Works 100003295 995429 18% Dismantling of RCC in foundation including disposal of debris and reinforcement bars of dismantled RCC works within substationboundaries as per direction of enginner incahrge M3 10 Included 0.00 0 0
63 7000030914 660 320 10 Non-Standard structures-Service 100001210 995455 18% Erection of Lattice Structures (MS Steel), to be designed during detailed engineering, for towers, beams and equipment supportstructure including pack plates / packwashers and gusset plates excluding fasteners and foundation bolts MT 30 Included 0.00 0 0
64 7000030914 660 320 20 Non-Standard structures-Service 100001680 995455 18% Erection of fasteners ( nuts, bolts and washers ) including step bolts for lattice and pipe structures to be designed duringdetailed engineering MT 1 Included 0.00 0 0
65 7000030914 660 320 30 Non-Standard structures-Service 100001681 995455 18% Erection of foundation bolts including nuts, checknut and washers for lattice and pipe structures to be designed during detailedengineering MT 3 Included 0.00 0 0
66 7000030914 760 350 10 PMUs for Bhuj PS 170000502 998713 18% Service:- Phasor Measurement Unit (PMU) EA 2 Included 0.00 0 0
67 7000030914 760 350 20 PMUs for Bhuj PS 170000530 998734 18% WAMS TIME SYSTEM(GPS RECEIVER) EA 2 Included 0.00 0 0
68 7000030914 760 350 30 PMUs for Bhuj PS 170004701 998734 18% SUBSTATION GRADE Layer 2 LAN SWITCH EA 2 Included 0.00 0 0
69 7000030914 760 350 40 PMUs for Bhuj PS 170004700 998734 18% SUBSTATION GRADE Layer 3 LAN SWITCH EA 1 Included 0.00 0 0
70 7000030914 760 350 50 PMUs for Bhuj PS 170000504 998713 18% Services:- Armored Fibre Optic Cable and associated termination equipment LOT 1 Included 0.00 0 0
71 7000030914 760 350 60 PMUs for Bhuj PS 170003449 998316 18% SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF LIU-FO PATCH PANEL-12 PORT EA 3 Included 0.00 0 0
72 7000030914 760 350 70 PMUs for Bhuj PS 170000501 998734 18% Integration of PMU with the PDC (Phasor Data Concentrator) of RLDCs and respective SLDCs as required. LOT 1 Included 0.00 0 0
E 220kV line bays at Bhuj PS
1 7000030914 1250 120 10 Inst. 220kV AIS Equipments 100000448 998736 18% 245 kV, 4400pf Capacitive Voltage Transformer (1- Phase) EA 6 Included 0.00 0 0
2 7000030914 1250 120 20 Inst. 220kV AIS Equipments 100000484 998736 18% 216kV Surge Arrester (1-phase) EA 6 Included 0.00 0 0
3 7000030914 1250 120 30 Inst. 220kV AIS Equipments 100000498 998736 18% 245 kV Bust Post Insulator (Except for wave traps) EA 32 Included 0.00 0 0
4 7000030914 1250 120 40 Inst. 220kV AIS Equipments 100002048 998734 18% 220kV,1600A,0.5mH ,50kA Line Trap EA 4 Included 0.00 0 0
5 7000030914 1250 120 50 Inst. 220kV AIS Equipments 100000884 998734 18% 245 kV ,1 phase Bus Post Insulators for Line Traps EA 12 Included 0.00 0 0
6 7000030914 1240 130 10 Inst. 220 kV HYBRID GIS 100007282 998736 18% 245kV, 1600 A, DM Type SF6 MTS/HYBRID GIS ICT/LINEfeeder baySwitchgear Assembly as per Section-Project, Technical specification . EA 2 Included 0.00 0 0
7 7000030914 1280 140 10 Inst. Erection Hardware (220kV) 100003724 998731 18% Erection Hardware for 220kV layout (Double Main Scheme)-Line Bay as per technical specification SET 2 Included 0.00 0 0
8 7000030914 1260 150 10 Inst. CONTROL & RELAY PANEL 100016778 998736 18% 220kV Circuit Breaker Relay Panel (with Automation) EA 2 Included 0.00 0 0
9 7000030914 1260 150 20 Inst. CONTROL & RELAY PANEL 100000738 998736 18% 220kV Line Protection Panel (with Automation) EA 2 Included 0.00 0 0
10 7000030914 1260 150 30 Inst. CONTROL & RELAY PANEL 100000743 998736 18% Augmentation of existing 220kV bus bar protection scheme.(No. of bays as per specification)-(with Automation) SET 1 Included 0.00 0 0
11 7000030914 1330 160 20 Inst. SUBSTATION AUTOMATION SYSTEM 100002070 998736 18% Augmentation of Substation automation System for 220kV bay as per Technical Specification EA 2 Included 0.00 0 0
12 7000030914 1270 170 10 Inst. Illumination System (Outdoor) 100001021 995461 18% Lighting Panel type ACP-2 as per technical specification EA 1 Included 0.00 0 0
13 7000030914 1270 170 20 Inst. Illumination System (Outdoor) 100004930 998731 18% LED Flood Light Luminaries Type-FL-1 as per technical specification EA 10 Included 0.00 0 0
14 7000030914 1270 170 30 Inst. Illumination System (Outdoor) 100004931 998731 18% LED Flood Light Luminaries Type FL-2 (250W) as per technical specification EA 10 Included 0.00 0 0
15 7000030914 1290 180 10 Inst. Power & Control Cable 100002182 998736 18% 1.1kV grade Control Cables (PVCinsulated) along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0
16 7000030914 1290 180 20 Inst. Power & Control Cable 100002181 998736 18% 1.1kV grade Power Cables (PVCinsulated)along withlugs,glands,straight joints &accessories,etc. LS 1 Included 0.00 0 0
17 7000030914 1300 190 10 Inst. AC+FIRE PROTN+ILLUM FOR SPR 100001882 995463 18% Air conditioning system for Switchyard Panel Room of 6m length SET 1 Included 0.00 0 0
18 7000030914 1300 190 20 Inst. AC+FIRE PROTN+ILLUM FOR SPR 100000975 995461 18% 4.5 kg CO2 type Portable Fire extinguisher EA 2 Included 0.00 0 0
19 7000030914 1300 190 30 Inst. AC+FIRE PROTN+ILLUM FOR SPR 100002062 995461 18% Fire Detection and Alarm System for Switchyard Panel Room of 6 m length SET 1 Included 0.00 0 0
20 7000030914 1300 190 40 Inst. AC+FIRE PROTN+ILLUM FOR SPR 100001116 998739 18% Illumination System for switchyard panel room of 6 m length SET 1 Included 0.00 0 0
21 7000030914 1310 200 10 Inst. Main Earthmat 100003103 998731 18% 40 mm MS rod for Main Earthmat KM 1 Included 0.00 0 0
22 7000030914 1450 230 10 Service-tele BOQ at Bhuj-II 100002812 998734 18% SDH Equipment (STM-16 MADM upto 5 MSP protected directions)-Base Equipment (Common cards, Cross Connect/control cards, optical basecards, power supply cards, power cabling, other hardware and accessories including sub racks, patch cord, DDF etc fully equipedexcluding optical interface & Tributary cards EA 1 Included 0.00 0 0
23 7000030914 1450 230 20 Service-tele BOQ at Bhuj-II 170000433 998734 18% Optical Interface Cards/SFP# -S16.1 for SDH Equipment-STM-16 EA 4 Included 0.00 0 0
24 7000030914 1450 230 30 Service-tele BOQ at Bhuj-II 100002825 998734 18% Tributary interface- E1 interface (Minimum 16 nos.) SET 2 Included 0.00 0 0
25 7000030914 1450 230 40 Service-tele BOQ at Bhuj-II 170000550 998336 18% Ethernet Interface 10/100 Base T with Layer-2 switching (Min 8 Interfaces per card) EA 2 Included 0.00 0 0
26 7000030914 1450 230 50 Service-tele BOQ at Bhuj-II 100002829 998734 18% Tributary interface-Gigabit Ethernet Interfaces 10/100 Mbps with Layer -2 Switching (minimum 2 nos.) SET 1 Included 0.00 0 0
27 7000030914 1450 230 60 Service-tele BOQ at Bhuj-II 170000375 998734 18% Equipment Cabinets-For SDH Equipments EA 1 Included 0.00 0 0
28 7000030914 1450 230 80 Service-tele BOQ at Bhuj-II 170004395 998336 18% Fibre Optic Approach cabling: Including installation hardware like GI pipe, elbow, conduits, accessories etc.: 48 Fibre KM 0.5 Included 0.00 0 0
29 7000030914 1450 230 90 Service-tele BOQ at Bhuj-II 170000356 998336 18% Fibre Optic Distribution Panel (FODP): Indoor Type: FC Coupling and mounted on ETSI 19" rack or slimline rack: Type 2 (96 Fibre) EA 1 Included 0.00 0 0
30 7000030914 1560 250 10 Civil Works 100004518 995433 18% Excavation in all kind of soil including rock for all leads and lifts, backfilling, disposal of surplus earth within a lead up to2Km as per technical specification. The surplus earth shall be roughly graded . M3 914 Included 0.00 0 0
31 7000030914 1560 250 20 Civil Works 100001325 995454 18% Providing and laying of Plain Cement Concrete (PCC) (1:4:8) M3 99 Included 0.00 0 0
32 7000030914 1560 250 30 Civil Works 100001326 995454 18% Providing and laying of Plain Cement Concrete (PCC) (1:2:4) M3 4 Included 0.00 0 0
33 7000030914 1560 250 40 Civil Works 100016607 995451 18% Providing and laying of Reinforced Cement Concrete M30 including pre cast, shuttering, Grouting of pockets & underpinning butexcluding steel reinforcement M3 252 Included 0.00 0 0
34 7000030914 1560 250 50 Civil Works 100016681 995454 18% Reinforcement steel meeting corrosion resistance properties as per IS:1786 and manufacturer specification​ MT 18 Included 0.00 0 0
35 7000030914 1560 250 60 Civil Works 100001331 995455 18% Misc. Structural steel including rails, embedments, edge protection angles, gratings etc. but excluding the reinforcement steel andsteel for lattice and pipe structures. MT 1 Included 0.00 0 0
36 7000030914 1560 250 70 Civil Works 100001714 995428 18% Stone spreading in switchyard excluding PCC M2 1000 Included 0.00 0 0
37 7000030914 1560 250 80 Civil Works 100001712 995428 18% Removing,cleaning and washing of existing stones and respreading of stones in switchyard excluding PCC M2 500 Included 0.00 0 0
38 7000030914 1560 250 90 Civil Works 100001713 995424 18% Antiweed treatment M2 1500 Included 0.00 0 0
39 7000030914 1560 250 100 Civil Works 100048595 995423 18% Providing & laying non-woven Geo-synthetics fabric of minimum 200 GSM in separration layer between sub garde and stone spreading inswitchyard as per Technical Specification and direction of Engineer-in-Charge. M2 1500 Included 0.00 0 0
40 7000030914 1560 250 110 Civil Works 100004507 995421 18% 3.75m wide Cement Concrete road with PCC shoulder including 100 mm dia RCC Hume Pipe @ 100 metre interval as per drawing and TS.However, reinforcement steel and all type concrete shall be paid separately under relevant items M2 375 Included 0.00 0 0
41 7000030914 1560 250 120 Civil Works 100001735 995462 18% RCC culverts and cable trench crossings including supplying and laying hume pipe 250mm dia of grade (NP-3) excluding concrete as perspecification. M 10 Included 0.00 0 0
42 7000030914 1560 250 130 Civil Works 100001736 995462 18% RCC culverts and cable trench crossings including supplying and laying hume pipe 300mm dia of grade (NP-3) excluding concrete as perspecification. M 10 Included 0.00 0 0
43 7000030914 1560 250 140 Civil Works 100001737 995462 18% RCC culverts and cable trench crossings including supplying and laying hume pipe 450mm dia of grade (NP-3) excluding concrete as perspecification. M 10 Included 0.00 0 0
44 7000030914 1560 250 150 Civil Works 100020963 995461 18% RCC culvert crossings including supplying and laying hume pipe 600mm dia of grade (NP-3) excluding concrete as per specification. M 10 Included 0.00 0 0
45 7000030914 1560 250 160 Civil Works 100001478 995454 18% Cable Trench including all types of crossings, all metallic works and sump pit including concrte and reinforcement steel Section 2-2 M 100 Included 0.00 0 0
46 7000030914 1560 250 170 Civil Works 100001479 995454 18% Cable Trench including all types of crossings, all metallic works and sump pit including concrte and reinforcement steel Section 3-3 M 250 Included 0.00 0 0
47 7000030914 1560 250 180 Civil Works 100001480 995454 18% Cable Trench including all types of crossings, all metallic works and sump pit including concrte and reinforcement steel Section 4-4 M 60 Included 0.00 0 0
48 7000030914 1560 250 190 Civil Works 100015791 995454 18% All civil works for Drains construction of Section A-A including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 60 Included 0.00 0 0
49 7000030914 1560 250 200 Civil Works 100015792 995454 18% All civil works for Drains construction of Section B-B including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 80 Included 0.00 0 0
50 7000030914 1560 250 210 Civil Works 100015793 995454 18% All civil works for Drains construction of Section C-C including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 40 Included 0.00 0 0
51 7000030914 1560 250 220 Civil Works 100015794 995454 18% All civil works for Drains construction of Section D-D including crossings if any as per technical specification and tender drawingscomplete in all respect with all labour and materials. M 20 Included 0.00 0 0
52 7000030914 1560 250 230 Civil Works 100002911 995432 18% Earthwork in excavation & filling in all types of soil and soft/disintegrated rock in open areas/nallas/channels, to the requiredslopes, shapes, levels, elevations and profile, including trimming of bottom and slopes of excavation, bailing out rain(dewatering), pumping, removal of slush, preparing embankments/marginal banks, loosening, dressing, spreading material in layers notexceeding 200mm, as per direction of Engineer-in-Charge, water flooding, compacting to achieve 95% consolidation at optimum moisturecontent, finishing etc. all complete, for all leads and lifts within leveling boundary, including disposal of surplus earth andstacking of unsuitable material within a lead of 2.0 Km beyond substation boundary, with all labour, material, tools, tackles andequipment, safeguards and incidentals, Royalty,taxes etc. as necessary, as per drawings, specification and directions of theEngineer-in-Charge. Clearing of jungle is included in this item. (Only excavation/cutting will be measured for payment purpose.) M3 1000 Included 0.00 0 0
53 7000030914 1560 250 240 Civil Works 100002583 995432 18% Supply of earth (excluding rock & boulders) at site including royalty, carriage and filling in specified areas in layers notexceeding 200mm in depth, compacting under optimum moisture condition to achieve 95% of Proctor density, finishing etc. allcomplete, for all leads & lifts, with all labour, material, tools, tackles, equipments, safeguards & incidentals as necessary as perdrawings, specification and direction of the Engineer- in- Charge. M3 500 Included 0.00 0 0
54 7000030914 1560 250 250 Civil Works 100001720 995428 18% Supplying, filling and compacting CNS material as per specification under floors, foundations, roads, cable trenches, drains etc inlayers not exceeding 200 mm thickness M3 100 Included 0.00 0 0
55 7000030914 1560 250 260 Civil Works 100003437 995454 18% Switchyard Panel Room - Civil Works. All civil works as per drawing and specifications complete, including - brickwork, finishing(external and internal), windows etc. However, excavation, PCC, RCC and reinforcement shall be paid separately as per BPS. M2 29.5 Included 0.00 0 0
56 7000030914 1560 250 270 Civil Works 100003295 995429 18% Dismantling of RCC in foundation including disposal of debris and reinforcement bars of dismantled RCC works within substationboundaries as per direction of enginner incahrge M3 10 Included 0.00 0 0
57 7000030914 1570 260 10 Non-Standard structures-Service 100001210 995455 18% Erection of Lattice Structures (MS Steel), to be designed during detailed engineering, for towers, beams and equipment supportstructure including pack plates / packwashers and gusset plates excluding fasteners and foundation bolts MT 13 Included 0.00 0 0
58 7000030914 1570 260 20 Non-Standard structures-Service 100001680 995455 18% Erection of fasteners ( nuts, bolts and washers ) including step bolts for lattice and pipe structures to be designed duringdetailed engineering MT 1 Included 0.00 0 0
59 7000030914 1570 260 30 Non-Standard structures-Service 100001681 995455 18% Erection of foundation bolts including nuts, checknut and washers for lattice and pipe structures to be designed during detailedengineering MT 2 Included 0.00 0 0
Total Installation Charges 0.00 0
Total GST as confirmed by Bidder 0.00
* In case the bidder leaves the cell for confirmation of the SAC and/or GST rate “blank”, the SAC and corresponding GST rate indicated by the Employer shall be deemed to be the one confirmed by the Bidder.
Place : Printed Name :
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Schedule - 3
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS; As per Lum-sum 0.00%
(SCHEDULE OF RATES AND PRICES : ERECTION CHARGES) AS per Percent #REF!
As per lum-sum on Sch-3 0.00%
Bidder’s Name and Address (Lead Partner) : To: As per Percent on Sch-3 #REF!
Contracts Services, 3rd Floor Total Discount #REF!
Name : …….. …….. …….. …….. …….. …….. Power Grid Corporation of India Ltd.,
Address : …….. …….. …….. …….. …….. …….. "Saudamini", Plot No.-2
…….. …….. …….. …….. …….. …….. Sector-29, Multipackage lum-sum 0.00%
All Prices are in Indian Rupees. Amount after Discount (Rs.) Dis Alert Amount after MPD (Rs.)
SI. No. Description Unit Quantity Unit Erection Charges Total Erection Charges Unit Erection Charges Total Erection Charges Unit Erection Charges Total Erection Charges
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! (a) Detailed Soil Investigation
#REF! #REF! #REF! #REF! #REF! (b) All kinds of soil except fissured rock & hard rock
#REF! #REF! #REF! #REF! #REF! (e) River Crossing Location
#REF! #REF! #REF! #REF! #REF! (f)
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
Total Erection Price (A+B) #REF!
Place : Printed Name :
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Schedule - 4
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS;
(SCHEDULE OF RATES AND PRICES )
Bidder’s Name and Address (Lead Partner) : To:
Contracts Services, 3rd Floor
Name : …….. …….. …….. …….. …….. …….. Power Grid Corporation of India Ltd.,
Address : …….. …….. …….. …….. …….. …….. "Saudamini", Plot No.-2
Training Charges for Training to be imparted
SI. No. PR No PR Line Item No Activity Header PR Activity No Activity Description Service Code SAC (Service Accounting Codes) Whether SAC in column '8’ is confirmed. If not indicate applicable the SAC * Rate of GST applicable ( in %) Whether rate of GST in column ‘10’ is confirmed. If not indicate applicable rate of GST * Description Unit Quantity Unit Training Charges excluding GST Total Training Charges excluding GST Total GST as confirmed by Bidder
Revaluation of J column Tax Calculation
NOT APPLICABLE 0 0
Total Training Charges 0.00 #REF!
Total GST as confirmed by Bidder 0.00
Date : -- Printed Name :
Place : Designation :
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Schedule - 4b
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS;
(SCHEDULE OF RATES AND PRICES )
Bidder’s Name and Address (Lead Partner) : To:
Contracts Services, 3rd Floor
Name : …….. …….. …….. …….. …….. …….. Power Grid Corporation of India Ltd.,
Address : …….. …….. …….. …….. …….. …….. "Saudamini", Plot No.-2
Maintenance Charges during & after Defect Laibility Period
SI. No. PR No PR Line Item No Activity Header PR Activity No Activity Description Service Code SAC (Service Accounting Codes) Whether SAC in column '8’ is confirmed. If not indicate applicable the SAC * Rate of GST applicable ( in %) Whether rate of GST in column ‘4’ is confirmed. If not indicate applicable rate of GST * Description Unit Quantity Unit Maintenance Charges excluding GST Total Maintenance Charges excluding GST Total GST as confirmed by Bidder
0 Revaluation of P column Tax Calculation
A. #REF! Revaluation of P column Tax Calculation
1 Included 0.00 0 0
2 Included 0.00 0 0
3 Included 0.00 0 0
4 Included 0.00 0 0
B. #REF! Revaluation of P column Tax Calculation
1 Included 0.00 0 0
2 Included 0.00 0 0
3 Included 0.00 0 0
4 Included 0.00 0 0
Total Maintenance Charges during and after Defect Liabilty Period 0.00 0
Total GST as confirmed by Bidder 0.00
Date : -- Printed Name :
Place : Designation :
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Schedule - 5
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS;
(SUMMARY OF TAXES & DUTIES APPLICABLE ON PLANT & EQUIPMENT)
Bidder’s Name and Address (Lead Partner) : To:
Contracts Services, 3rd Floor
Name : …….. …….. …….. …….. …….. …….. Power Grid Corporation of India Ltd.,
Address : …….. …….. …….. …….. …….. …….. "Saudamini", Plot No.-2
Sl. No. Item Nos. Total Price (INR) After Discount After MPDiscount
1 TOTAL GST ON GOODS Excise Duty #REF! Excise Duty #REF!
Total GST for Supply of Goods (inter-alia including Type Test Charges) between the Contractor and the Employer (identified in Schedule 1') which are not included in the Ex-works price as per the provision of the Bidding Documents, as applicable. 0.00
2 TOTAL GST ON SERVICES Sales Tax 0.00 Sales Tax 0.00
Total GST on Installation Services (Schedule-3), Training to be imparted in India (Schedule-4) 0.00 #REF! 0 #REF! 0
GRAND TOTAL [1+2] 0.00 Grand Total after Discount #REF! Grand Total after MPD #REF!
Date : -- Printed Name :
Place : Designation :
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Schedule - 5
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS;
SUMMARY OF TAXES & DUTIES APPLICABLE ON GOODS
Bidder’s Name and Address (Lead Partner) : To:
Contracts Services, 3rd Floor
Name : …….. …….. …….. …….. …….. …….. Power Grid Corporation of India Ltd.,
Address : …….. …….. …….. …….. …….. …….. "Saudamini", Plot No.-2
Sl. No. Item Nos. Total Price (INR)
1 TOTAL GST ON GOODS 0.00
Total GST for Supply of Goods (inter-alia including Type Test Charges) between the Contractor and the Employer (identified in Schedule 1') which are not included in the Ex-works price as per the provision of the Bidding Documents, as applicable.
2 TOTAL GST ON SERVICES 0.00
Total GST on Installation Services (Schedule-3), Training to be imparted in India (Schedule-4a) and Maintenance Charges during and after Defect Liabilty Period (Schedule-4b)
GRAND TOTAL [1+2] 0.00
Date : -- Printed Name :
Place : Designation :
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Schedule - 6
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS;
(GRAND SUMMARY)
Bidder’s Name and Address (Lead Partner) : To:
Contracts Services, 3rd Floor
Name : …….. …….. …….. …….. …….. …….. Power Grid Corporation of India Ltd.,
Address : …….. …….. …….. …….. …….. …….. "Saudamini", Plot No.-2
Sl. No. Description Total Price (INR)
1 TOTAL SCHEDULE NO. 1 0.00
Ex-works price of Plant and Equipment including Type Test Charges
2 TOTAL SCHEDULE NO. 2 0.00
Local Transportation, In-transit Insurance, loading & unloading
3 TOTAL SCHEDULE NO. 3 0.00
Installation Charges
4 TOTAL SCHEDULE NO. 4 0.00
Training Charges
4b TOTAL SCHEDULE NO. 4b 0.00
Maintenance Charges during & after Defect Laibility Period
5 TOTAL SCHEDULE NO. 5 0.00
Taxes and Duties
6 TOTAL SCHEDULE NO. 7 0.00
Type Test Charges [Total of this Schedule is included in Schedule - 1 above.]
GRAND TOTAL [1+2+3+4+5] 0.00
Date : -- Printed Name :
Place : Designation :
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Schedule - 6 After Discount
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS;
(GRAND SUMMARY)
Bidder’s Name and Address (Lead Partner) : To:
Contracts Services, 3rd Floor
Name : …….. …….. …….. …….. …….. …….. Power Grid Corporation of India Ltd.,
Address : …….. …….. …….. …….. …….. …….. "Saudamini", Plot No.-2
Sl. No. Description Total Price (INR)
1 TOTAL SCHEDULE NO. 1 0.00
Ex-works price of Plant and Equipment including Type Test Charges
2 TOTAL SCHEDULE NO. 2 0.00
Local Transportation, In-transit Insurance, loading & unloading
3 TOTAL SCHEDULE NO. 3 0.00
Installation Charges
4 TOTAL SCHEDULE NO. 4 0.00
Training Charges
4b TOTAL SCHEDULE NO. 4b 0.00
Maintenance Charges during & after Defect Laibility Period
5 TOTAL SCHEDULE NO. 5 0.00
Taxes and Duties
6 TOTAL SCHEDULE NO. 7 0.00
Type Test Charges [Total of this Schedule is included in Schedule - 1 above.]
GRAND TOTAL [1+2+3+4+5] 0.00
Date : -- Printed Name :
Place : Designation :
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Schedule 7
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS; As per Lum-sum 0.00%
(SCHEDULE OF RATES AND PRICES ) AS per Percent #REF!
As per lum-sum on Sch-7 0.00%
Bidder’s Name and Address (Lead Partner) : To: As per Percent on Sch-7 #REF!
Contracts Services, 3rd Floor Total Discount #REF!
Name : …….. …….. …….. …….. …….. …….. Power Grid Corporation of India Ltd.,
Address : …….. …….. …….. …….. …….. …….. "Saudamini", Plot No.-2
…….. …….. …….. …….. …….. …….. Sector-29, Multipackage Discount 0.0000%
Type tests on Earthwire, Hardwar Fittings & accessories of conductor & earthwire:
SL. NO. PR No Line Item No Code HSN Code Whether HSN in column ‘2’ is confirmed. If not indicate applicable the HSN code * Rate of GST applicable ( in %) Whether rate of GST in column ‘4’ is confirmed. If not indicate applicable rate of GST * Description of Test Unit Quantity Unit Test Charge Total Test Charges (Rs.) Total GST as confirmed by Bidder Revaluation of M column Tax Calculation Total Test Charges After Discount (Rs.) Dis Alert Total Test Charges After MPD (Rs.)
1 Included 0.00 0 0.00
2 Included 0.00 0 0.00
TOTAL TYPE TEST CHARGES 0.00
Total GST as confirmed by Bidder 0.00
Date : -- Printed Name :
Place : Designation :
Note : Bidder should indicate the name of test laboratories where type tests are proposed to be conducted
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS; 0 0
(SCHEDULE OF RATES AND PRICES ) 0 0
Bidder’s Name and Address (Lead Partner) :
SL. NO. Description of Test #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS; As per Lum-sum 0.00%
(SCHEDULE OF RATES AND PRICES : TYPE TEST CHARGES) AS per Percent #REF!
As per lum-sum on Sch-7 0.00%
Bidder’s Name and Address (Lead Partner) : To: As per Percent on Sch-7 #REF!
Contracts Services, 3rd Floor Total Discount #REF!
Name : …….. …….. …….. …….. …….. …….. Power Grid Corporation of India Ltd.,
Address : …….. …….. …….. …….. …….. …….. "Saudamini", Plot No.-2
…….. …….. …….. …….. …….. …….. Sector-29, Multipackage Discount 0.0000%
Type Tests on Earthwire
SL. NO. Description of Test Unit Quantity Unit Test Charge Total Test Charges (Rs.) Total Test Charges After Discount (Rs.) Dis Alert Total Test Charges After MPD (Rs.)
(a) #REF! #REF! #REF! #REF! #REF!
(b) #REF! #REF! #REF! #REF! #REF!
Sub-Total (I) #REF!
TOTAL TEST CHARGES (I) #REF!
Discount Sche-7 #REF! MPD Sche-7 #REF!
Dis Alert #REF!
Date : -- Printed Name :
Place : Designation :
Note : Bidder should indicate the name of test laboratories where type tests are proposed to be conducted
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS; 0 0 0
(SCHEDULE OF RATES AND PRICES : TYPE TEST CHARGES) 0 0 0
Bidder’s Name and Address (Lead Partner) : 0
SL. NO. Description of Test 0
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
This letter of discount is optional. Bidder may / may not offer any discount.
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Letter of Discount
LETTER OF DISCOUNT
Contract Services
Power Grid Corporation of India Ltd.,
"Saudamini", Plot No.-2
Sector-29, (near IFFCO Chowk)
Gurgaon (Haryana) - 122001
Subject : 400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS;
With reference to the subject tender, we hereby offer unconditional discount on the prices quoted by us as per details given here below : Eq Weightage of Rs/ % Final Discount Factor
1 Discount on lum-sum basis on total price quoted by us without Taxes & Duties. [The discount shall be proportionately applicable on all the items of all the Schdules i.e. Sch-1 (without type test charges), Sch-2, Sch-3, Sch-4a, Sch-4b & Sch-7] In Rs. 0.00 0.0000000000%
2 Discount on percent basis on total price quoted by us without Taxes & Duties. [The discount shall be applicable on all the items of all the Schdules i.e. Sch-1 (without type test charges), Sch-2 , Sch-3, Sch-4a, Sch-4b & Sch-7] In Percent (%) 0.00 0.00%
3 Discount on lum-sum basis on the Schedules as given below : [The discount shall be proportionately applicable on all the relevent items of the respective Schdules.] In Rs.
Schedule-1 : Ex works prices In Rs. 0.00 0.0000000000% Schedule-1 : Ex-Works Price 0.0000000000%
Schedule-2 : Freight & Insurance In Rs. 0.00 0.0000000000% Schedule-2 : Freight & Insurance 0.0000000000%
Schedule-3 : Erection Charges In Rs. 0.00 0.0000000000% Schedule-3 : Erection Charges 0.0000000000%
Schedule-4a : Training Charges In Rs. 0.00 0.0000000000% Schedule-4a : Training Charges 0.0000000000%
Schedule-4b : Maintenance Charges during and after DLP In Rs. 0.00 0.0000000000% Schedule-4b : Maintenance Charges 0.0000000000%
Schedule-7 : Type Test Charges In Rs. 0.00 0.0000000000% Schedule-7 : Type Test Charges 0.0000000000%
4 Discount on percent basis on the Schedules as given below : [The discount shall be applicable on all the relevent items of the respective Schdules.] In Percent (%)
Schedule-1 : Ex works prices In Percent (%) 0.00 0.00%
Schedule-2 : Freight & Insurance In Percent (%) 0.00 0.00%
Schedule-3 : Erection Charges In Percent (%) 0.00 0.00%
Schedule-4a : Training Charges In Percent (%) 0.00 0.00%
Schedule-4b : Maintenance Charges during and after DLP In Percent (%) 0.00 0.00%
Schedule-7 : Type Test Charges In Percent (%) 0.00 0.00%
Discount(s) offered at sl. No. 1 to 4 will get displayed and accounted for automatically in the respective items of the Schedules.
5 We hereby offer Multi-package discount as given below:
Multi-Package Discount(s) offered at sl. No. 5 will not get automatically accounted for in the respective items of the Schedules. The same shall be worked out saparately for evaluation.
Please consider this letter of discount as the integral part of our price bid.
Thanking you, we remain,
Yours faithfully,
For and on behalf of …….. …….. …….. …….. …….. ……..
Date : -- Printed Name :
Place : Designation :
Details of Octroi
Sl No. Description of Items Amount on which Octroi is applicable Rate of Octroi Octroi
Details of Entry Tax
Sl No. Description of Items Amount on which Entry Tax is applicable Rate of Entry Tax Entry Tax
Details of Other Taxes & Duties
Sl No. Description of Items Amount on which Other Taxes & Duties are applicable Description of Taxes & Duties Rate of Taxes & Duties Amount of Taxes & Duties
Specification No.: CC/NT/W-GIS/DOM/A10/25/06459 Bid Form 2nd Envelope 0 1 st 1 January
0 2 nd 2 February
BID FORM (Second Envelope) 3 rd 3 March
Bid Proposal Ref. No. 5 th 5 May
Date : -- 6 th #VALUE! 6 June
7 th #VALUE! 7 July
To: 8 th #VALUE! 8 August
Contracts Services, 3rd Floor 9 th #VALUE! 9 September
Power Grid Corporation of India Ltd., 10 th 10 October
"Saudamini", Plot No.-2 11 th 11 November
Sector-29, 12 th 12 December
Gurgaon (Haryana) - 122001 13 th
Name of Contract : 400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS; 15 th
Dear Ladies and/or Gentlemen, 16 th
Schedule 1 Plant and Equipment (Including Mandatory Spare Parts) to be supplied, including Type Test Charges. 21 st
Schedule 2 Local Transportation, In-transit Insurance, loading and unloading 22 th
Schedule 3 Installation Charges. 23 th
Schedule 4 Training charges for training to be imparted. 24 th
Schedule 4b Maintenance Charges during & after Defect Laibility Period.
Schedule 5 Taxes and Duties not included in Schedule 1 25 th
Schedule 6 Grand Summary [Schedule 1to 5] 26 th
Schedule 7 Break-up of Type Test Charges for Type Tests to be conducted 27 th
2.5 We declare that items left blank in the Schedules will be deemed to have been included in other items. The TOTAL for each Schedule and the TOTAL of Grand Summary shall be deemed to be the total price for executing the Facilities and sections thereof in complete accordance with the Contract, whether or not each individual item has been priced. 31 st
3.0 We confirm that except as otherwise specifically provided our Bid Prices in this Second Envelope include all taxes, duties, levies and charges as may be assessed on us/our Associate (applicable for Foreign Bidder), our Sub-Contractor/Sub-Vendor or their employees by all municipal, state or national government authorities in connection with the Facilities, in and outside of India.
3.1 100% of applicable Taxes and Duties i.e GST which are payable by the Employer under the Contract, shall be reimbursed by the Employer on production of satisfactory documentary evidence by the Contractor in accordance with the provisions of the Bidding Documents.
3.3 We confirm that we have also registered/we shall also get registered in the GST Network with a GSTIN, in all the states where the project is located and the states from which we shall make our supply of goods.
4.0 # (For Joint Venture only) We, the partners of Joint Venture submitting this bid, do agree and confirm that in case of Award of Contract on the Joint Venture, we shall be jointly and severally liable and responsible for the execution of the Contract in accordance with Contract terms and conditions. 2
5.0 We, hereby, declare that only the persons or firms interested in this proposal as principals are named here and that no other persons or firms other than those mentioned herein have any interest in this proposal or in the Contract to be entered into, if the award is made on us, that this proposal is made without any connection with any other person, firm or party likewise submitting a proposal is in all respects for and in good faith, without collusion or fraud.
Thanking you, we remain,
Yours faithfully,
For and on behalf of …….. …….. …….. …….. …….. ……..
Date : -- Printed Name :
Place : Designation :
In case of bid from a Joint Venture, name & designation of representative of JV partner is to be provided and Bid Form is also to be signed by him.
Please provide additional information of the Bidder
Business Address :
Country of Incorporation :
State/Province to be indicated :
Name of Principal Officer :
Address of Principal Officer :
Note: Bidders may note that no prescribed proforma has been enclosed for Attachment 2 : Power of Attorney. Bidders may use their own proforma for furnishing the required information with the bid.
STATEMENT OF QUOTED / CORRECTED PRICES
All Figures are in Rupees
Sl. No. Price Component Quoted Price Corrected Price
1 TOTAL SCHEDULE NO. 1:Ex-Works Price of Plant and Equipment including Type Test Charges 0.00 0.00
2 TOTAL SCHEDULE NO.2: Local Transportation, Insurance and other Incidental Services. 0.00 0.00
3 TOTAL SCHEDULE NO.3: Installation Charges 0.00 0.00
4 TOTAL SCHEDULE NO.4: Training Charges Not Applicable Not Applicable
5 TOTAL BID PRICE: (Excluding Taxes & Duties) 0.00 0.00
6 DISCOUNT #REF! #REF! #REF!
7 NET BID PRICE (Excluding Taxes & Duties) #REF! #REF!
8 TAXES & DUTIES PAYABLE ADDITIONALLY
A) EXCISE DUTY 0 0.00
B) CENTRAL SALES TAX 0 0.00
C) VAT #REF! 0.00
D) ENTRY TAX / OCTROI #REF! 0.00
F) TOTAL TAXES & DUTIES #REF! 0.00
8 TOTAL BID PRICE (INCLUDING TAXES & DUTIES) #REF! 0.00
9 TOTAL SCHEDULE NO.7: Type Test Charges [Total of this Schedule is included in Schedule-1 above] 0.00 0.00
I) Bidder has indicated the following taxes and duties additionally applicable for their bid:
Excise Duty % as Excise Duty
#REF! VAT #REF! #REF!
#REF! Entry Tax/ Octroi #REF! #REF!
Others as Others
II) With regard to Entry Tax, it may be mentioned that the substations covered under the subject pacakge falls in State of MP, where an entry tax @ 2% of Purchase Price is applicable. In view of the above, the taxes and duties inter-alia including entry tax applicable for the bids are calculated :
a) Ex-Works Price of Direct Supplies (after discount, if any) Rs. 0
b) Excise Duty, as applicable on (a) above at the rate : 10.00% Rs. 0
c) Amount on which Sales Tax is applicable 0.00 0
d) CST, as applicable on (a) + ED (b) above at the rate : 2.00% Rs. 0
e) VAT, as applicable on (a) + ED (b) above at the rate : 1.00% 0
g) Purchase Price for Entry Tax (Total Ex-Works+F&I+ED+CST+Others) Rs. 0
h) Entry Tax, as applicable on (e) above at the rate : Rs. 0.00
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS; Statement of Quoted / Corrected Prices Page
Spec. No. Specification No.: CC/NT/W-GIS/DOM/A10/25/06459
STATEMENT OF QUOTED / CORRECTED PRICES
All Figures are in Rupees
Sl. No. Price Component Quoted Price Corrected Price
1 TOTAL SCHEDULE NO. 1:Ex-Works Price of Plant and Equipment including Type Test Charges 0.00 0.00
2 TOTAL SCHEDULE NO.2: Local Transportation, Insurance and other Incidental Services. 0.00 0.00
3 TOTAL SCHEDULE NO.3: Installation Charges 0.00 0.00
4 TOTAL SCHEDULE NO.4: Training Charges Not Applicable Not Applicable
5 TOTAL BID PRICE: (Excluding Taxes & Duties) 0.00 0.00
6 DISCOUNT #REF! #REF!
7 NET BID PRICE (Excluding Taxes & Duties) #REF! #REF!
8 TAXES & DUTIES PAYABLE ADDITIONALLY
A) EXCISE DUTY #REF! 0.00
B) CENTRAL SALES TAX /VAT #REF! #REF!
C) ENTRY TAX / OCTROI #REF! #REF!
D) OTHERS #REF! 0.00
E) TOTAL TAXES & DUTIES #REF! #REF!
8 TOTAL BID PRICE (INCLUDING TAXES & DUTIES) #REF! #REF!
9 TOTAL SCHEDULE NO.7: Type Test Charges [Total of this Schedule is included in Schedule-1 above] 0.00 0.00
I) Bidder has indicated the following taxes and duties additionally applicable for their bid:
a) Excise Duty Rs. #REF!
b) CST /VAT Rs. #REF!
c) Entry Tax / Octroi Rs. #REF!
d) Others Rs. #REF!
II) Bidder has offered following discount(s)
III) With regard to Entry Tax, it may be mentioned that the substations covered under the subject pacakge falls in State of MP, where an entry tax @ 1% of Purchase Price is applicable. In view of the above, the taxes and duties inter-alia including entry tax applicable for the bids are calculated : Details of dicounts
a) Ex-Works Price of Direct Supplies (after discount, if any) Rs. 0 Gross LS #REF! #REF! #REF! Gross % #REF! #REF! #REF!
b) Excise Duty @ 10.3% of (a) above Rs. 0 #REF! #REF!
c) CST / VAT @ 2% of Ex-Works of Direct Supplies (a) + ED (b) above Rs. #REF! Sch-1 Direct LS #REF! #REF! #REF! Sch-1 Direct % #REF! #REF! #REF!
d) Others Rs. Sch-1 BO LS #REF! #REF! #REF! Sch-1 BO % #REF! #REF! #REF!
e) Purchase Price for Entry Tax (Total Ex-Works+F&I+ED+CST+Others) Rs. #REF! Sch-2 LS #REF! #REF! #REF! Sch-2 % #REF! #REF! #REF!
f) Entry Tax @ 1% of (e) above Rs. #REF! Sch-3 LS #REF! #REF! #REF! Sch-3 % #REF! #REF! #REF!
Sch-7 LS #REF! #REF! #REF! Sch-7 % #REF! #REF! #REF!
400kV GIS Substation Package SS-149 under (a) Extn. of 400/220kV Bhuj-II PS associated with Augmentation of transformation capacity at Bhuj-II PS (GIS) (b) Extn. of 400/220kV Bhuj-II PS associated with Provision of ICT Augmentation and Bus Reactor at Bhuj-II PS (c) Extn. of 400/220kV Bhuj PS associated with Transmission scheme for providing connectivity to REGS at Bhuj PS; Statement of Quoted / Corrected Prices Page Different Manner #REF!
Text for Discount #REF!
23 Twenty Three
27 Twenty Seven
28 Twenty Eight
33 Thirty Three
37 Thirty Seven
38 Thirty Eight
73 Seventy Three
74 Seventy Four
75 Seventy Five
77 Seventy Seven
78 Seventy Eight
79 Seventy Nine
83 Eighty Three
87 Eighty Seven
88 Eighty Eight
93 Ninety Three
97 Ninety Seven
98 Ninety Eight
100 One Hundred
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html
Existing_Electrical Layout_Bhuj-II GIS.pdf
pdf • 10.43 MB
1_Typical module drawings.pdf
pdf • 0.14 MB
EXISTING_OUTDOOR_EARTHMAT_LAYOUT_BHUJ-II.pdf
pdf • 8.35 MB
EXISTING_OUTDOOR_CABLE_TRENCH_LAYOUT_BHUJ-II.pdf
pdf • 8.45 MB
ELECTRICAL_LAYOUT_SECTION_BHUJ-II.pdf
pdf • 1.90 MB
EXISTING_OUTDOOR_EARTHMAT_LAYOUT_BHUJ-II_1.pdf
pdf • 8.35 MB
EXISTING_P&I_DIAGRAM_BHUJ-II.pdf
pdf • 0.24 MB
compressed_400kV_GIS_GAS_SLD_BHUJ-II.pdf
pdf • 0.86 MB
220KV_GIS_EXTENSION_MODULE_DRAWING_NHVS_BHUJ-II.pdf
pdf • 0.51 MB
220KV_GIS_LAYOUT_&_SECTION_BHUJ-II.pdf
pdf • 2.03 MB
400KV_GIS_EXTENSION_MODULE_DRAWING_NHVS_BHUJ-II.pdf
pdf • 0.67 MB
420KV_GIS_LAYOUT_&_SECTION_BHUJ-II.pdf
pdf • 2.36 MB
compressed_220kV_GIS_GAS_SLD_BHUJ-II.pdf
pdf • 1.22 MB
GENERAL_ARRANGEMENT_DRAWING_REV-00_BHUJ_PS.pdf
pdf • 6.61 MB
SINGLE_LINE_DIAGRAM_REV-00_BHUJ_PS.pdf
pdf • 0.77 MB
SINGLE_LINE_DIAGRAM_REV-00_BHUJ-II_PS_GIS.pdf
pdf • 1.36 MB
GENERAL_ARRANGEMENT_DRAWING_Rev00_BHUJ-II_PS_GIS.pdf
pdf • 7.37 MB
1_BITUMEN ROAD.pdf
pdf • 0.44 MB
2 Standard Drain Section.pdf
pdf • 0.17 MB
3_ROAD CULVERTS.pdf
pdf • 1.50 MB
4_CABLE TRENCH & CROSSING DETAILS.pdf
pdf • 0.63 MB
5_RAIL CUM ROAD.pdf
pdf • 1.30 MB
6_Standard_400kV_GISBUILDING__Architectural_Drawing.PDF
pdf • 0.58 MB
Details of cable trench and cable trench road crossings.pdf
pdf • 0.63 MB
DETAILS OF CONCRETE ROAD.pdf
pdf • 1.25 MB
DETAILS OF DRAIN.pdf
pdf • 1.06 MB
RAIL CUM ROAD.pdf
pdf • 1.30 MB
STANDARD PANEL ROOM(6M).pdf
pdf • 1.56 MB
STANDARD ROAD CULVERTS.pdf
pdf • 1.50 MB
Annexure-IV_DESCRIPTION OF 420KV & 245KV GIS BAY MODULES & EQUIPMENTS.pdf
pdf • 0.46 MB
Annexure-V_220KV_CT_TS.pdf
pdf • 0.42 MB
Section_Project_400kV_GIS_Pkg_SS 149Rev00.pdf
pdf • 1.04 MB
Annexure-III_Specific_Requirement_Rev 10.pdf
pdf • 9.19 MB
Annexure-I List of Drawings-Rev-00.pdf
pdf • 0.37 MB
Annexure-II LIST OF Breakup of Mandatory Spares.pdf
pdf • 0.49 MB
Annexure-1-Hirchman Ethernet Network switch Configuration.pptx
pptx • 1.51 MB
Annexure-2-Magnum Ethernet Network switch Configuration.pptx
pptx • 0.69 MB
Annexure-3-Ruggedcom Ethernet Network switch Configuration.pptx
pptx • 0.41 MB
Configuration for Root & Non-Root Ethernet Switch.docx
docx • 0.06 MB
AC SS datalist.xlsx
xlsx • 0.66 MB
FSC Datalist Rev1.xlsx
xlsx • 0.04 MB
NTAMC signal list -HVDC rev03.xlsx
xlsx • 0.02 MB
STATCOM NTAMC Signal proposed list for TS.xlsx
xlsx • 0.02 MB
SVC Datalist-Rev1.xlsx
xlsx • 0.04 MB
01_PROT_TRIP_ONE & HALF_Rev 00_Page_01.pdf
pdf • 0.19 MB
01_PROT_TRIP_ONE & HALF_Rev 00_Page_02.pdf
pdf • 0.19 MB
02_PROT_TRIP_DM & DMT_Rev 00-Page 01.pdf
pdf • 0.19 MB
02_PROT_TRIP_DM & DMT_Rev 00-Page 02.pdf
pdf • 0.18 MB
03_PROT_TRIP_400_220_ICT_Rev 00-Page_01.pdf
pdf • 0.10 MB
03_PROT_TRIP_400_220_ICT_Rev 00-Page_02.pdf
pdf • 0.10 MB
03_PROT_TRIP_400_220_ICT_Rev 00-Page_03.pdf
pdf • 0.06 MB
04_PROT_TRIP_765_400_ICT_Rev 00-Page-01.pdf
pdf • 0.11 MB
04_PROT_TRIP_765_400_ICT_Rev 00-Page-02.pdf
pdf • 0.08 MB
04_PROT_TRIP_765_400_ICT_Rev 00-Page-03.pdf
pdf • 0.07 MB
05_PROT_TRIP_BUS REACTOR_Rev 00-Page-01.pdf
pdf • 0.08 MB
05_PROT_TRIP_BUS REACTOR_Rev 00-Page-02.pdf
pdf • 0.08 MB
05_PROT_TRIP_BUS REACTOR_Rev 00-Page-03.pdf
pdf • 0.06 MB
06_PROT_TRIP_NON SW LR_Rev 00-Page-01.pdf
pdf • 0.05 MB
06_PROT_TRIP_NON SW LR_Rev 00-Page-02.pdf
pdf • 0.08 MB
06_PROT_TRIP_NON SW LR_Rev 00-Page-03.pdf
pdf • 0.07 MB
07_PROT_TRIP_SW LR_Rev 00-Page-01.pdf
pdf • 0.06 MB
07_PROT_TRIP_SW LR_Rev 00-Page-02.pdf
pdf • 0.09 MB
07_PROT_TRIP_SW LR_Rev 00-Page-03.pdf
pdf • 0.06 MB
08_ SPARE SELECTION LOGIC_ICT.pdf
pdf • 0.13 MB
09_ SPARE SELECTION LOGIC_REACTOR.pdf
pdf • 0.12 MB
01_CT_VT_Conn_ONE AND HALF_LINE_Rev00.pdf
pdf • 0.05 MB
02_CT_VT_Conn_DMT_LINE_Rev00.pdf
pdf • 0.04 MB
03_CT_VT_Conn_SERIES REACTOR_01_Rev00_PAGE_01.pdf
pdf • 0.05 MB
03_CT_VT_Conn_SERIES REACTOR_01_Rev00_PAGE_02.pdf
pdf • 0.03 MB
04_CT_VT_Conn_1Phase_LR_SW_01_Rev00_PAGE_01.pdf
pdf • 0.06 MB
04_CT_VT_Conn_1Phase_LR_SW_01_Rev00_PAGE_02.pdf
pdf • 0.07 MB
05_CT_VT_Conn_3Phase_LR_SW_01_Rev00_PAGE_01.pdf
pdf • 0.05 MB
05_CT_VT_Conn_3Phase_LR_SW_01_Rev00_PAGE_02.pdf
pdf • 0.04 MB
06_CT_VT_Conn_1Ph_NON_LR_SW_Rev00_PAGE_01.pdf
pdf • 0.06 MB
06_CT_VT_Conn_1Ph_NON_LR_SW_Rev00_PAGE_02.pdf
pdf • 0.06 MB
07_CT_VT_Conn_3Ph_NON_LR_SW_Rev00_PAGE_01.pdf
pdf • 0.06 MB
07_CT_VT_Conn_3Ph_NON_LR_SW_Rev00_PAGE_02.pdf
pdf • 0.04 MB
08_CT_VT_Conn_1Phase_ICT01_Rev00_PAGE_01.pdf
pdf • 0.05 MB
08_CT_VT_Conn_1Phase_ICT01_Rev00_PAGE_02.pdf
pdf • 0.07 MB
08_CT_VT_Conn_1Phase_ICT01_Rev00_PAGE_03.pdf
pdf • 0.05 MB
09_CT_VT_Conn_3Phase_ICT01_Rev00_PAGE_01.pdf
pdf • 0.05 MB
09_CT_VT_Conn_3Phase_ICT01_Rev00_PAGE_02.pdf
pdf • 0.05 MB
09_CT_VT_Conn_3Phase_ICT01_Rev00_PAGE_03.pdf
pdf • 0.03 MB
10_CT_VT_Conn_BR_1PHASE_Rev00_PAGE_01.pdf
pdf • 0.05 MB
10_CT_VT_Conn_BR_1PHASE_Rev00_PAGE_02.pdf
pdf • 0.06 MB
11_CT_VT_Conn_BR_3PHASE_Rev00_PAGE_01.pdf
pdf • 0.05 MB
11_CT_VT_Conn_BR_3PHASE_Rev00_PAGE_02.pdf
pdf • 0.03 MB
FAT-SAT procedure_Router firemwall_Rev_0.pdf
pdf • 0.30 MB
Trip logic Diagram & CT VT connection.pdf
pdf • 0.62 MB
Referece_GE_Aux system.xlsx
xlsx • 0.02 MB
REV_03_GE_ 220kV_26_12_2023.xlsx
xlsx • 1.84 MB
REV_03_GE_ 765kV_26_12_2023.xlsx
xlsx • 1.45 MB
REV_03_GE_400kV_26_12_2023.xlsx
xlsx • 1.99 MB
REV 03_ABB_12122023_Final.xlsx
xlsx • 0.56 MB
220kV_BC.xlsx
xlsx • 0.02 MB
220kV_ICT_INCOMER.xlsx
xlsx • 0.02 MB
220kV_LINE.xlsx
xlsx • 0.07 MB
220kV_MCU.xlsx
xlsx • 0.02 MB
220kV_TBC.xlsx
xlsx • 0.02 MB
400kV_BR.xlsx
xlsx • 0.04 MB
400kV_ICT.xlsx
xlsx • 0.07 MB
400kV_LINE REACTOR.xlsx
xlsx • 0.04 MB
400kV_LINE.xlsx
xlsx • 0.07 MB
400kV_MCU.xlsx
xlsx • 0.03 MB
400kV_TIE.xlsx
xlsx • 0.03 MB
765kV_BUS REACTOR.xlsx
xlsx • 0.05 MB
765kV_ICT.xlsx
xlsx • 0.08 MB
765kV_LINE REACTOR.xlsx
xlsx • 0.04 MB
765kV_LINE.xlsx
xlsx • 0.07 MB
765kV_MCU.xlsx
xlsx • 0.03 MB
765kV_TIE.xlsx
xlsx • 0.03 MB
Referece_Siemens_Aux system.xlsx
xlsx • 0.02 MB
DR Channel Standardization Revision Edition_02.pdf
pdf • 1.15 MB
19_Section PMU Rev 01.pdf
pdf • 0.45 MB
18-TS-Telecommunication System-Rev 05.pdf
pdf • 7.09 MB
16_Control & Relay Panel Rev9.pdf
pdf • 0.37 MB
17_Section-Sub-station Automation Rev4.pdf
pdf • 0.98 MB
13_Section_Switchyard Erection_Rev10.pdf
pdf • 4.45 MB
14_Structure Rev 7.pdf
pdf • 0.30 MB
15_Civil Works Rev 12.pdf
pdf • 0.99 MB
10_Fire Protection Rev 6.pdf
pdf • 1.97 MB
11_Power & Control Cable Rev R6.pdf
pdf • 0.26 MB
12_Air conditioning R4.pdf
pdf • 0.04 MB
5_Section-Switchgear-SA_Rev13.pdf
pdf • 0.87 MB
6_Section-Switchgear-CB_Rev11.pdf
pdf • 0.61 MB
7_Section-Switchgear-ISO_Rev13.pdf
pdf • 0.68 MB
8_Lighting Specification Rev7.pdf
pdf • 4.29 MB
9_LT Switchgear R5.pdf
pdf • 0.47 MB
2_GTR Rev 15.pdf
pdf • 7.12 MB
3_GIS Rev-05A.pdf
pdf • 1.95 MB
4_Section-Switchgear-INST_rev12.pdf
pdf • 0.86 MB
00_Cover Pages Volume-III.doc
doc • 0.81 MB
01_Attachment-8_Manufacturer Authorization Form.docx
docx • 0.03 MB
02_Attachment-20_KMP Declaration.doc
doc • 0.03 MB
03_Attachment_21_Affidavit for Self-Certification_PPP-MII.DOCX
docx • 0.02 MB
04_Attachment 22_Certificate by Auditor_PPP-MII.docx
docx • 0.02 MB
05_Attachment-24_Confirmation in regard to Design and Type Test.docx
docx • 0.02 MB
06_Attachment-25_Declaration regarding events encountered.docx
docx • 0.03 MB
07_Attachment-29_Bid Securing Declaration.docx
docx • 0.02 MB
14_Legends for Units.pdf
pdf • 0.03 MB
First_Envelope_and_Bid_Forms.xlsx
xlsx • 2.04 MB
Price_Schedule.xlsx
xlsx • 1.71 MB
00_Cover Page.doc
doc • 0.81 MB
01_Main Index_Vol-I.doc
doc • 0.02 MB
02-Section - I IFB SSTE_Vol-I.docx
docx • 0.04 MB
03_ Section - II ITB SSTE S&I DCB-PRANIT_Vol-I.docx
docx • 0.10 MB
04- Section-III-BDS.docx
docx • 0.09 MB
04-Annexure-A (BDS).doc
doc • 0.06 MB
04-Annexure-B to BDS.docx
docx • 0.02 MB
04-Annexure-C to BDS.docx
docx • 0.03 MB
05-Section - IV GCC -S&I Rev 3-DCB.pdf
pdf • 1.93 MB
06- Section-V-SCC (GIS).docx
docx • 0.09 MB
07- Appendix-I to SCC.docx
docx • 0.03 MB
08_Appendix-II_SCC.docx
docx • 0.03 MB
09_Appendix-III_SCC.pdf
pdf • 0.62 MB
10-Section - VI Forms and Procedures.doc
doc • 0.64 MB
Letter_for_Extn-VIII.docx
docx • 0.20 MB
01_Amendment No-V.pdf
pdf • 0.31 MB
Letter_for_Extn-VII.docx
docx • 0.20 MB
03_Attachment 8(b).docx
docx • 0.02 MB
Letter_for_Extn-VI.docx
docx • 0.20 MB
Letter_for_Extn-V.docx
docx • 0.20 MB
01_Clarification no-V.pdf
pdf • 0.11 MB
01-Amendment-I_SS149.docx
docx • 0.06 MB
01-Clarification-IV.pdf
pdf • 0.22 MB
Letter_for_Extn-IV.docx
docx • 0.20 MB
00_Letter to the Bidders.docx
docx • 0.19 MB
01_Amendment No-II.pdf
pdf • 0.15 MB
Letter_for_Extn-III.docx
docx • 0.16 MB
Letter_for_Extn-II.docx
docx • 0.20 MB
Letter_for_Extn-I.docx
docx • 0.20 MB
00_Letter to the Bidders.docx
docx • 0.19 MB
05_Annexure-A-Form 7(b)_Surety Bond Form for Advance.doc
doc • 0.07 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .