Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.5 LAccepted-AOC 7TH MILE UPPER SHILLONG P O NONGLYER SHILLONG MEGHALAYA | EAST KHASI HILLS | MEGHALAYA | 793009 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹29.0 L+₹1.6 L (5.70%)Rejected-AOC | L2 | Rejected-AOC Not Lowest Bidder | |
| 3 | L3₹30.6 L+₹3.1 L (11.4%)Rejected-AOC 7TH MILE UPPER SHILLONG P O NONGLYER SHILLONG MEGHALAYA | EAST KHASI HILLS | MEGHALAYA | 793009 | L3 | Rejected-AOC Not Lowest Bidder |
Tender Value
₹28 L
EMD Value
₹56,000
Closing Date
27 Feb 2023, 6:00 pmClosed
GE (I) (AF) Shillong
GE (I) (AF) Shillong Elephant Falls Camp PO Nonglyer Shillong-793009
CA NO. GE(I)(AF)/SHL/ 2022-23 REPAIRS/MAINTENANCE OF LT UG CABLES, LT PANELS, FEEDER PILLAR BOXES AND OTHER ALLIED WORKS AT 509 SU, AF STN LAITKOR PEAK UNDER GE (I) (AF) SHILLONG
2023_MES_573006_2
8070/22/SHL/2022/23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Laitkor Peak Shillong
For Enlisted Contractors Class D Category b i and for unenlisted contractors meeting enlistment criteria for required Class and Category
8 documents required · 8 mandatory
₹500
GE (I) (AF) Shillong
₹56,000
Yes
16 Mar 2023
8 Feb 2023
1 Mar 2023
8 Feb 2023
27 Feb 2023
10 Feb 2023
8 Feb 2023 - 9 Feb 2023
Amount
Excavation in trenches in soft / loose soil, not exc 1.5 m wide and n. exc 1.5 m depth or n exc 10 Sqm on plan & getting out, for laying of cables, foundations of poles, struts, stays etc. and getting out including triming and forming bottom surface complete, all as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cms thick in soft / loose soil back in trenches after cables have been laid and tested, poles, stays , struts have been erected and tested complete all as directed.
Removing excavated materials to a distance not exc 50m and depositing where directed at a level not exc 1.5 m above the starting point in soils complete all as directed.
Taking out old unserviceable LT UG cable and Supplying, Fixing/laying, jointing and testing and commissioning, LT under ground cables, 1100 Volts grade, XLPE insulated, armoured heavy duty electric cable with stranded aluminuim conductors, laid in trenches, ducts/fixed on poles/walls/laid under roads/paths/drains/culverts or encased in GI pipe complete all as specified and directed of following sizes:-
2 core 10 Sqmm
4 core 16 Sqmm
3.5 core 25 Sqmm
3.5 core 35 Sqmm
3.5 core 50 Sqmm
3.5 core 70 Sqmm
3.5 core 95 Sqmm
3.5 core 120 Sqmm Notes :- (a) Excavation & earth work, GI pipe for laying of cable, sand cushioning, cable protection cover shall be measured and paid for seprately under respective items of the schedule. (b) Old serviceable cable cover obtained from taking out of cable shall be re-used under respective item of the BOQ.
M & L in replacement for outdoor type heat shrinkable cable end termination jointing kit for LT 1100 Volts (Earthed) grade cable of following size complete with jointing material and accessories complete all as directed :-
25 to 50 Sqmm, 3.5 core
70 to 150 Sqmm, 3.5 core
S & F in replacement Galvanised steel tubing light grade for protection of under ground cable on poles / walls/under road crossing/laid in trenches etc conforming to IS-1239 for following bore complete all as directed:-
50 mm bore
100 mm bore (Note : Excavation & earth work shall be measured & paid separately under respective items of this Schedule).
M & L for dry sand cushioning to PVC under ground cable with screened and washed sand and punning to provide a required cover complete all as specified and directed. Note :- Thickness after punning shall be considered for payment.
M & L for brick protection for UG XLPE cable with burnt clay old size sub class 'B' bricks laid dry and flat abutting each other with gaps between adjacent brick not more than 10mm and width equal to length of brick in trenches across the cable complete all as directed.
S & F in replacement following components/parts in existing LT panel boards complete all as directed:-
MCCB four pole 63 Amp confirming to IEC 60947-2 & IS – 13947-3 thermal magnetic release and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 16 KA at 415 V AC , 50 Hz
MCCB four pole 100 Amp confirming to IEC 60947-2 & IS – 13947-3 thermal magnetic release and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 16 KA at 415 V AC , 50 Hz
MCCB four pole 125 Amp confirming to IEC 60947-2 & IS – 13947-3 thermal magnetic release and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 16 KA at 415 V AC , 50 Hz
MCCB three pole 160 Amp confirming to IEC 60947-2 & IS – 13947-3 thermal magnetic release and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 36 KA at 415 V AC , 50 Hz
MCCB three pole 200 Amp confirming to IEC 60947-2 & IS – 13947-3 thermal magnetic release and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 36 KA at 415 V AC , 50 Hz
MCCB three pole 250 Amp confirming to IEC 60947-2 & IS – 13947-3 thermal magnetic release and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 36 KA at 415 V AC , 50 Hz
MCCB three pole 400 Amp confirming to IEC 60947-2 & IS – 13947-3 thermal magnetic release and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 36 KA at 415 V AC , 50 Hz
MCCB three pole 630 Amp confirming to IEC 60947-2 & IS – 13947-3 thermal magnetic release and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 50 KA at 415 V AC , 50 Hz
Amp meter digital type 0-400 Amps, of class I accuracy, 0.5 VA burden, analog type 96mm square dial. Make : Securemeters/Schneider/L&T
Digital type Voltmeter 0-500 volts, 3 Phase, 4 digit, high resolution analog type 96mm square dial. Make : Securemeters/Schneider/L&T
Current Transformer copper wound of ratio 100/5
Aluminium bus bar of rating 400 Amps including PVC heat shrink sleeves
Indicator lamp with holder key flush mounted, LED type Red, yellow, blue.
M & L for preparation of external and internal old painted steel surfaces of LT Panel boards/LT feeder pillar boxes/Bus Bar Chambers etc in position by removing/scrapping old disintegrated and deteriorated paint and painting two coats of synthetic enamel paint by spray gun over a coat of red oxide zinc chromer primer including writing letter complete all as specified and directed.
M & L for earthing complete with galvanized steel earth plate 60 cm X 60 cm X 6 mm thick buried vertically in ground to depth not less than 2.25 metres deep below ground level, with top edge of earth plate not less than 1.5 m below ground level, connected to galvanized earth lead wire 4.00mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel besides welding at all joints as shown in drawing and including excavation and earth work, GI pipe light grade 15mm bore for protection of earth wire and connected to continous earth lead on pole/test point, supplying and laying charcoal dust common salt PCC 1:2:4 type B1, chamber and MS angle iron frame 40x40x3mm and RCC cover 40mm thick (1:2:4) type B1 using 20mm graded stone aggregate reinforced with 6mm dia round bars @ 75mm C/C both ways with MS handle 12mm dia, PGI funnel and wire mesh, 20mm dia GI pipe medium grade for watering all as shown in electrical plate No 5 on srl page No 497 of SSR Part I (2009) drawing and connection to earth test point including testing and including dismantling and taking out old earthing complete all as specified and directed. Note : (i) The cost of earth lead /strip and GI pipe for protection of earth lead/strip upto 7.5m is included in the quoted rate. (ii) The cost of excavation, earth work is included in the quoted rate.
OUTGOING (a) MCCB four pole 250 Amp confirming to IEC 60947-2 & IS – 13947-3 thermal magnetic release and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 36 KA at 415 V AC , 50 Hz complete - 02 Nos. (b) MCCB four pole 125 Amp confirming to IEC 60947-2 & IS – 13947-3 thermal magnetic release and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 25 KA at 415 V AC , 50 Hz complete - 02 Nos. (c) Two spare compartment. Notes:- (a) All armoured cables shall enter through bottom of the feeder pillar duly glanded and socketed and connected to MCCB/cable terminal. Cost of glanding socketing etc are deemed to be included in the unit rate of feeder pillar. (b) All the out going cable shall be terminated in bakellite cable connector and shall be duly glanded and socketed. (c) All the cables (power and control wiring ) should be terminated duly socketed with heavy duty tinned copper lugs, GI bolts/screws nuts, flat washers and spring washers as required. (d) White acrylic marker plate (for feeder / switch marking ) to be provided with black lettering by heat press machine as indicated in drawing and to be pasted over the panel door/near the cable connector with high quality adhesive. (e) The cost of platform/foundation with PCC shall deemed to be included in the quoted rates. (f) The consolidated rate for Srl No. 12.00 & 12.10 shall be quoted against Srl No. 12.00 of BOQ.
Taking down existing old unserviceable Busbar Chamber and Supply, installing, testing and commissioning Busbar Chamber outdoor type of size 1200x1500x450mm, totally enclosed, cubical type, front openable, single door, made out of 3.15 mm thick CRCA sheet on MS angle 50x50x6mm frame welded to the bottom, powder coated finish over one coat of red oxide primer, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, and to accommodate following components. The Busbar Chamber shall be dust and vermin proof, IP 65 class protection with aprons for cable entry, with locking arrangement {including provn of 65mm Godrej (Freedom) lock with 2 keys}, internal wiring with PVC insulated, multistranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 4 sqmm. The scope of work includes the following:- (a) Copper bus bar of rating 300 Amps for four pole including PVC heat shrink sleeves (RYB & N ) : 02 Sets (a) MCCB four pole 125 Amp confirming to IEC 60947-2 & IS – 13947-3 thermal magnetic release and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 16 KA at 415 V AC , 50 Hz complete - 01 No.
Notes (a) All armoured cables shall enter through bottom of the Busbar Chamber duly glanded and socketed and connected to MCCB/cable terminal/fixed to busbar. Cost of glanding/socketing etc are deemed to be included in the unit rate of Busbar Chamber. (b) All the out going cable shall be terminated in bakellite cable connector and shall be duly glanded and socketed. (c) All the cables should be terminated duly socketed with heavy duty tinned copper lugs, GI bolts/screws nuts, flat washers and spring washers as required. (d) White acrylic marker plate (for feeder / switch marking ) to be provided with black lettering by heat press machine and to be pasted over the Busbar Chamber door/near the cable connector with high quality adhesive. (e) The cost of platform/foundation with PCC shall deemed to be included in the quoted rates. (f) The consolidated rate for Srl No. 13.00 & 13.10 shall be quoted against Srl No. 13.00 of BOQ.
Taking down existing old unserviceable Busbar Chamber and Supply, installing, testing and commissioning Busbar Chamber outdoor type of size 1200x1500x450mm, totally enclosed, cubical type, front openable, single door, made out of 3.15 mm thick CRCA sheet on MS angle 50x50x6mm frame welded to the bottom, powder coated finish over one coat of red oxide primer, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, and to accommodate following components. The Busbar Chamber shall be dust and vermin proof, IP 65 class protection with aprons for cable entry, with locking arrangement {including provn of 65mm Godrej (Freedom) lock with 2 keys}, internal wiring with PVC insulated, multistranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 4 sqmm. The scope of work includes the following:- (a) Copper bus bar of rating 400 Amps for four pole including PVC heat shrink sleeves (RYB & N ) : 02 Sets (a) MCCB four pole 160 Amp confirming to IEC 60947-2 & IS – 13947-3 thermal magnetic release and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 16 KA at 415 V AC , 50 Hz complete - 01 No.
Notes (a) All armoured cables shall enter through bottom of the Busbar Chamber duly glanded and socketed and connected to MCCB/cable terminal/fixed to busbar. Cost of glanding/socketing etc are deemed to be included in the unit rate of Busbar Chamber. (b) All the out going cable shall be terminated in bakellite cable connector and shall be duly glanded and socketed. (c) All the cables should be terminated duly socketed with heavy duty tinned copper lugs, GI bolts/screws nuts, flat washers and spring washers as required. (d) White acrylic marker plate (for feeder / switch marking ) to be provided with black lettering by heat press machine and to be pasted over the Busbar Chamber door/near the cable connector with high quality adhesive. (e) The cost of platform/foundation with PCC shall deemed to be included in the quoted rates. (f) The consolidated rate for Srl No. 14.00 & 14.10 shall be quoted against Srl No. 14.00 of BOQ.
M/S A K C ENTERPRISE
M/S DEEDAR ENTERPRISE
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .