| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.8 LAccepted-AOC 728 1 JOGIWARA VISHAVKARMA MANDIR ROAD AMBALA CITY | AMBALA CITY | AMBALA | HARYANA | 134003 | L1 | Accepted-AOC L1 | |
| 2 | L2₹34.0 L+₹5.3 L (18.3%)Accepted-AOC | L2 | Accepted-AOC L2 | |
| 3 | L3₹35.6 L+₹6.8 L (23.7%)Accepted-AOC | L3 | Accepted-AOC L3 | |
| 4 | L4₹36.0 L+₹7.2 L (25.0%)Accepted-AOC DOOR NO 43 2 BESIDES VIZAG DEFENCE ACADEMY 104 AREA KAPPARADA VISAKHAPATNAM 530013 | VISAKHAPATNAM | VISAKHAPATNAM | ANDHRA PRADESH | 530013 | L4 | Accepted-AOC L4 |
Tender Value
Refer Docs
EMD Value
₹69,000
Closing Date
30 Jan 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (AF) Hakimpet
GE (AF) Hakimpet Secunderabad-14
PROVN OF 3 PHASE POWER SUPPLY DISTRIBUTION PANEL, AIR CONDITION AND POWER SOCKETS FOR 12 TS AND SRE BLDG AND CERTAIN MAJOR REVENUE AND MINOR WORKS AT AFS HAKIMPET UNDER GE(AF) HAKIMPET
2021_MES_409061_1
8239/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
HAKIMPET
As per NIT
6 documents required · 6 mandatory
₹500
GE (AF) HAKIMPET
₹69,000
Yes
19 Mar 2021
2 Jan 2021
1 Feb 2021
2 Jan 2021
30 Jan 2021
16 Jan 2021
60 days
Amount
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth in hard/dense soil for laying of LT cable / pole, complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick in hard/dense soil, complete all as specified and directed.
Removing, surplus excavated material to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point, complete all as specified and directed.
Dismanting of existing light fittings/fans in any type complete and re-fixing the same after making good including flexible wire for connection and testing complete all as specified and directed.
M&L for opening of glass/stone or brick wall carefully suitable for fixing of exhaust fan and finshed the surfaces neatly including suitable required copper conductor, complete all as specified and directed.
M&L for opening of stone or brick wall carefully suitable for fixing of exhaust fan and finshed the surfaces neatly including suitable required copper conductor, complete all as specified and directed.
M&L for drilling on ceiling carefully and inserting the threaded bolts for fixing of ceiling fan and testing after completion of work complete all as specified and directed.
Boaring/ drilling (horizontally) of holes under road, pavement, hard standing by trenchess technology suitable for passing GI/HDPE pipe 80mm dia, complete all as specified and directed.
M&L for sand cushioning with a layer of river sand 23 cm thick under and above the cable complete all as specified and as directed
M&L for sub class B' burnt bricks for cable protection, complete as specified as directed
M&L for Plain cement concrete 1:4:8, Type D2(using 40mm graded crushed granite stone aggregate) laid in base, mass concrete, complete all as specified and directed.
M&L for Plain Cement Concrete 1:2:4, Type B1 (using 20 mm graded granite stone aggregate) as in roof kerbs, coping, bed block etc and the like edge slightly rounded or chamfered including necessary use and waste of form work, complete all as specified and directed.
M&L for Pre-cast cement concrete block masonry with solid blocks, 1:3:6, Type C1 (using 20 mm graded crushed granite stone aggregate) exceeding 10 cm in width and setting in cement mortar 1:6, for fixing of GI pipe 50 mm bore on roof of bldg and necessary bracket incuding nut, bolts etc complete all as specified and directed.
M&L for XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured power cables (heavy duty) with solid aluminium conductor, 1100 volts sgrade, cross sectional area 10 Sqmm, 2 core laid in trenches complete all as specified and directed.
M&L for XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured power cables (heavy duty) with solid aluminium conductor, 1100 volts sgrade, cross sectional area 16Sqmm, 2 core laid in trenches complete all as specified and directed.
M&L for XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured power cables (heavy duty) with solid aluminium conductor, 1100 volts sgrade, cross sectional area 25 Sqmm, 3.5 core laid in trenches complete all as specified and directed.
M&L for XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured power cables (heavy duty) with solid aluminium conductor, 1100 volts sgrade, cross sectional area 50 Sqmm, 3.5 core laid in trenches complete all as specified and directed.
M&L for XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured power cables (heavy duty) with solid aluminium conductor, 1100 volts grade, cross sectional area 16 Sqmm, 4 core laid in trenches complete all as specified and directed.
M&L for 3 core, 1.5sqmm, 1100 volts, round stranded, PVC Insulated, PVC Sheathed, copper conductor industrial cables(Flexible), complete all as specified and directed.
S&F Ceiling rose surface type bakelite of size 65 x 50 mm, 2 to 3 terminals for tube light , bulk head fittings and wall mounting fitting, ceiling fans etc all as specified and dirceted.
S&F switch flush type 5 Amps, single pole, one way on laminated sheet complete all as specified and directed.
S&F Flush type Fan regulator Electronic step type 120W, 230V 2 module complete all as specifed and directed.
S&F switch flush type 15 Amps, single pole, one way on laminated sheet complete all as specified and directed
S&F Socket outlet, 5 Pin, 5 Amps,Piano flush type on laminated sheet etc complete all as specified and directed.
S&F Socket outletmultipurpose 6 Pin, 15 Amps,Piano flush type on laminated sheet etc complete all as specified and directed.
S&F of 15 Amps Plug top, 3 PIN, complete all as specified and directed.
S&F of Metal clad plug and socket with two pin and earth single pole with 20-32 Amps MCB 10KA 'C' Series ISI Marked, 230 Volts AC complete all as specified and directed.
M&L for point wiring with single core PVC insulated FRLS unsheathed, 1100 volt grade cable with multi stranded copper conductor of size 1.5 Sq mm (Nominal area) drawn through and including non metallic PVC conduit / casing & caping, medium grade, ISI marked of suitable size, surface on wall, ceiling with GI screws, rawl plugs with all fittings including Tee, Junction boxes and provision of pressed steel terminal box powder coated or PVC of suitable size with 3 mm thick laminated sheet cover for mounting switch sockets and regulators and drawing continuous earth wire of PVC insulated FRLS unsheathed 1100 Volts grade cable with stranded copper conductor of size 1.5 Sq mm (Nominal area) complete all as specified. Note: (i) Cost for cutting, chasing and making good to existing surfaces are deemed to be included in the Quoted Rate. (ii) Metal flush boxes, Cover plates, switches, sockets and fan regulator will be measured and paid under respective item of schedule.
All as per Item No.28 here-in-before but for one 3 pin socket out let 5 Amps on independent board.
All as per Item No.28 here-in-before but for one 3 pin socket out let 5 Amps on same board.
M&L for point wiring with 2.5 sq.mm FRLS insulated multistranded copper conductor, 1100 volts grade single core PVC insulated and unsheathed cable drawn in and including concealed stove enamelled steel conduit not less than 20 mm dia on surface of stone/concrete wall /roof etc all as per site requirement including FRLS,PVC insulated and unsheathed cable with copper conductor cable of size 2.50 sqmm as earth conductor and pressed steel terminal boxes made of 1.0 mm thick MS sheet on wall for mounting, 60mm deep covered including laminated sheet cover 3mm thick laminated hylam sheet fixed with cadmium plated screws for mounting switches,sockets etc including making good the disturbed surfaces of walls and painting to match with the existing surfaces as per site requirement complete all as specified and directed.
M&L for surface type point wiring with single core PVC insulated FRLS unsheathed, 1100 volt grade cable with multi stranded copper conductor of size 1.5 Sq mm (Nominal area) drawn through and including Stove enamelled steel conduit , ISI marked of suitable size, surface on wall, ceiling with GI screws, rawl plugs with all fittings including Tee, Junction boxes and provision of pressed steel terminal box powder coated or PVC of suitable size with 3 mm thick laminated sheet cover for mounting switch sockets and regulators and drawing continuous earth wire of PVC insulated FRLS unsheathed 1100 Volts grade cable with stranded copper conductor of size 1.5 Sq mm (Nominal area) complete all as specified.
All as per Item No. 30 here-in-before but for one 3 pin socket out let 5 Amps on independent board.
All as per Srl item No. 30 here-in-before but for 15 Amps socket outlet by using 2.5 Sqmm PVC insulated unsheathed copper conductor multi stranded on independent board including provn of 1.5 Sqmm PVC insulated solid copper conductor continus as earth wire
S&F of sub main wiring two single core 6 Sqmm FRLS PVC insulated unsheatheed 1100 volts copper conductor including 4 Sqmm singlecore copper conductor earth wire drawn in and including new PVC rigid non metallic 20 mm dia conduit medium density ISI marked complete all as specified and directed Note: (i) Two runs of 6.0 Sqmm and one run of 6.0 Sqmm copper cable and one run of PVC conduit will be measured as one unit length.
M&L for submain wiring with 2 runs of 4 Sqmm and 1 run of 2.5 Sqmm FRLS insulated, unsheathed, multistranded, 1100 Volts grade copper conductor cable single core, drawn through and including rgid non-metallic PVC Conduit and its accessories of suitable size but not less than 20mm (OD) on stone/concrete wall/roof surfaces complete all as specified and directed. Note: (i) Two runs of 4 Sqmm, one run of 2.5 Sqmm copper cable and one run of PVC conduit will be measured as one unit length.
M&L for sub main wiring surface/recessed as required with four single core 4 sqmm PVC insulated and unsheathed copper conductor, multistranded 1100 volts grade through and including non metalic rigid PVC conduit/suitable size casing caping including 4 sqmm copper conductor multistranded PVC insulated and unsheathed wire as earth continuity conductor along the wiring and connected to the common earth dolly complete including removing the existing unserviceable sub main wiring and making good the disturbed surface to match with the existing all as specified and directed.
Supply and fixing MCB distribution board double door type, TPN 4 way, 415 Volts sheet steel powder painted IP 43 protection with bus bar, neutral link & earth bar etc. for incoming MCCB and outgoing MCBs complete all as specified and directed. Note :- MCCB and MCB's shall be measured and paid seperately.
Supply and fixing MCB distribution board double door type, SPN 8 way,240 Volts sheet steel powder painted IP 43 protection with bus bar, neutral link & earth bar etc. for incoming and outgoing MCBs complete all as specified and directed. Note :- MCB's shall be measured and paid seperately.
Supply and fixing MCB distribution board double door type, SPN 4 way, 240 Volts sheet steel powder painted IP 43 protection with bus bar, neutral link & earth bar etc. for incoming and outgoing MCBs complete all as specified and directed. Note :- MCB's shall be measured and paid seperately.
S&F MCB SP 6-32 Amp (ISI marked) 'C' series complete all as specified and directed. Note :- Rating of MCB shall be decided by Engineer-in-Charge.
S&F MCB SPN 63 Amp (ISI marked) 'C' series complete all as specified and directed.
S&F MCCB 4 pole 415 Volts, fixed type 125 Amps breaking capacity 16 KA complete all as specified and directed.
Supply and fixing of MCB FP 40 Amps ISI marked 415 volt 50Hz breaking capacity 10 KA complete all as specified and directed.
Supply and fixing of MCB TP 40 Amps ISI marked 415 volt 50Hz breaking capacity 10 KA, complete all as specified and directed.
Supply and fix sheet metal triple pole and neutral enclosure (TPN) with a three pin and earth plug and socket complete with one triple pole MCB of 32 Amps rating complete all as specified and directed.
Supply & Fix loop-in, loop-out box for street/security lights, made out of 2.0mm thick MS sheet of size 250mm x 200 mm x150 mm with pre-treated & powder coated finish, comprising suitable size busbar or terminator duly fitted on PVC insulators, with one SP MCB 6A, 10 KA breaking capacity for street light control, complete including suitable clamps made of 25x3mm flat iron for fixing, complete all as specified and directed.
Supply, installation, connecting, testing and commissioning of wall mounted split units indoor & outdoor complete with cordless remote control unit, with 5 star rating, with inverter technology of capacity 1.5 TR, inclusive of suction and discharge lines of suitable size and length of copper tube including necesary brazing and providing nitrile tubing over gas circulating copper tubes and neatly tying the ends with PVC insulating tape and mounting on suitable bracket inclusive of suitable drain pipe for disposal of waste water upto ground level, including cutting holes in to stone/brick walls built in cement mortar or cement lime mortar and wall of cement concrete not exc. 150 sq.cm area of holes for running copper tubes from indoor to outdoor split unit and testing, neatly finishing the disturbed surfaces of walls to match with the surroundings complete all as specified and directed. Make: Carrier/Voltas/Blue star/Usha-Daikin/Hitachi.
Supply, installation, connecting, testing and commissioning of wall mounted split AC units indoor & outdoor complete with cordless remote control unit, with inverter technology of capacity 2 TR, 5 star adjustable inclusive of suction and discharge lines of suitable size and length of copper tube including necessary brazing and providing nitrile tubing over gas circulating copper tubes and neatly tying the ends with PVC insulating tape and mounting on suitable bracket inclusive of suitable drain pipe for disposal of waste water upto ground level including cutting holes in to stone /walls built in cement mortar or cement lime mortar and wall of cement concrete not exceeding 150 sqcm area of holes for running copper tubes from indoor to outdoor split unit and testing neatly finishing the distrubed surfaces of walls to match with the surroundings complete etc all as specified and directed. Make : Carrier Hitachi/Voltas/Blue star/ Daikin
Supply and fixing of Electronic Voltage Stablizer having 5 KVA capacity , wall mounting type naturally air cooled having features such as intelligent time delay system, low and high voltage cutoff protection , latest IC technology to protect from power fluctuations thermal over load protection wide input variation between 170V to 270V with output voltage stablized at 220 to 240V with accuracy of + 2.5% suitable for Airconditioner complete all as specified and directed. Make : V Guard /Automatic Electrical/ Vinitec/Brent Ford/Power Ware meerut
Supply and fixing of Electronic Voltage Stablizer having 4 KVA capacity, wall mounting type naturally air cooled having features such as intelligent time delay system, low and high voltage cutoff protection , latest IC technology to protect from power fluctuations thermal over load protection wide input variation between 170V to 270V with output voltage stablized at 220 to 240V with accuracy of + 2.5% suitable for Airconditioner complete all as specified and directed. Make : V Guard /Automatic Electrical/ Vinitec/Brent Ford/Power Ware meerut
M&L for earthing complete with galvanized steel earth plate electrode 60 x 60cm x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 m deep below GL with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt and connected to earth lead GI wire 4mm dia by means of bolts, nuts, check nuts and washers of galvd iron or steel and thimbles and other end of the earth wire connected to DB and protected by galvd iron or steel pipe light grade 15 mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES SSR Pt-I of 2009. (including taking down of old existing earthing). Note : (a) RCC pit cover shall be pre-cast of RCC (1:2:4) type B1, 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover. (b) Quoted rate includes GI pipe 20mm bore with GI wire 4mm dia upto 7.5 m length.
Material & labour for earthing with Copper earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using copper strip 20 x 3 mm as earthing lead (upto the body of the equipment) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 20mm dia GI pipe connected to main switch board or main control board and GI pipe light grade 20mm bore for watering and including funnel , wire mesh , RCC pit cover and PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type of soil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 5 of MES SSR Pt-I of 2009 Complete all as specified and directed.
Supply, installation, testing & commissioning of maintenance free chemical earthing system conforming to IS: 3043 and as per the detailed specifications given below:- (a) Earth Electrode: Earth electrode shall be non-corrosive, solid copper round rod of size 17.20 mm dia, 3000mm long, made of high tensile low carbon steel with molecularly bonded copper coating of thickness 250 microns on the outside. (b) Bore hole: The electrode shall be installed in a 1200 mm dia 3000mm deep augured bore hole and to be filled 400mm outer dia with black soil (Note: Rates deemed to be including as supply and filling of black soil in proper manner). (c) Ground enhancing compound: The augured bore hole shall be filled with highly conductive and eco friendly grounnd enhancing carbon based backfill compound suitable for any type of soil. The quantity of ground enhancing compound shall not be less than 30 Kg per pit. (d) Earth termination clamp: The electrode shall be provided on its top with an earth termination clamp made of electrolytic grade copper, joined by exothermic welding suitable for terminating both round and flat type conductors of size 50 sqmm and above with stainless steel hardware. (e) Earth chamber: PCC chamber 300mmx300mmx300mm with cover shall be provided on the top of the earthing system on 100 mm thick PCC 1:3:6, Type C1, bed concrete. The chamber shall be flushed with ground surface. (f) Earth point test box: Copper strip of size 25mmx3mm size, 200mm long mounted on insulators and enclosed in suitable size of 2mm thick MS sheet box made of 2 mm thick & size 250mmx200mmx120mm sloped top outdoor type duly painted with two coats of synthetic enamel paint over a coat of red oxide primer shall be provided at a suitable location . (g)Copper Strip : Copper strip of size 25X3 mm from earth pit to test point box upto 7.5 m. Make: JEF Techno Solutions/ Railtech Engineering/ JMV Earthing
NOTES : Above item includes the following notes:- (i) The length of copper strip beyond 7.5 m will be measured and paid separately. (ii) Earthing is to be done in front of the Engineer-in-charge. (iii)Test results of earthing to be submitted by the contractor for all earthing pits. (iv) The contractor shall have to give written guarantee for maintaining earth resistance of less than 1 Ohm for a period of 5 (Five) years after certified date of completion and shall deposit Rs.2200/- per earthing pit as security deposit for a period of 5(Five) years. (v) Failing to maintain resistance of earthing pit less than 1 Ohm, new earthing pit to be provided by the contractor without any extra cost. (vi) Necessary earth work excavation shall be carried out in any type of soil strata, returning, filling in and making good the surrounding area complete.
M&L for earthing pit display boards made out of 3mm thick MS sheet of size 30 cm x 35 cm welded to 75 cm long 25 x 25 x 5 mm thick MS angle iron grouted in PCC 1:3:6, Type C1(with 20mm graded granite stone aggregate) to a depth of 20 cm and applying two coats of synthetic enamel paint of approved colour over a coat of red oxide primer and writing the letters on plate for showing the following details, complete all as directed:- 1. EARTHING PIT NO. : 2. DATE OF MEASUREMENT : 3. NEXT DUE DATE : 4. STANDARD VALUE : 5. VALUE OBTAINED : 6. MEASURED BY : 7. SUPERVISED BY : 8. DATE OF EXPIRY OF GUARANTEE : Note : Shape and colour of display board should be approved by GE before fixing on site.
M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried 60 mm depth in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc, as required 20X3mm copper strip, complete all as specified and directed. Note: Necessary brazing shall be completed at every joint alongwith nut bolt and the quoted unit rate deemed included the cost of brazing.
Supply and laying GI pipe light grade 50 mm dia in trenches for cable protection complete with all fixing accessories I.e GI clamp, nut bolts and washers complete all as directed
Supply and laying GI pipe medium grade 50 mm dia in trenches for cable protection complete with all fixing accessories I.e GI clamp, nut bolts and washers complete all as directed
S&F GI tubing medium grade 15 mm bore with all fittingssuch as Tee, bend, elbow etc, fixed to walls & ceilings or laid in floor etc, complete all as specified and directed.
S&F Gun metal globe or gate valve(ISI marked). With iron wheel head, screwed both ends, suitable for 20mm bore iron pipe and fixed including testing, complete all as specified and directed.
S&F Gun metal globe or gate valve(ISI marked). With iron wheel head, screwed both ends, suitable for 25mm bore iron pipe and fixed including testing, complete all as specified and directed.
S&F Gun metal globe or gate valve(ISI marked). With iron wheel head, screwed both ends, suitable for 40mm bore iron pipe and fixed including testing, complete all as specified and directed.
S&F Gun metal globe or gate valve(ISI marked). With iron wheel head, screwed both ends, suitable for 50mm bore iron pipe and fixed including testing, complete all as specified and directed.
S&F 15 mm bore Stop valves, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends of pipe or for unions and fixed fancy type cromium plated, complete all as specified and directed.
S&F 15 mm bore Bib taps, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends of pipe or for unions and fixed fancy type cromium plated, complete all as specified and directed.
S&F PVC connection pipe 15 mm size with PTMT nuts of length 450 mm suitable for hot and cold water, complete all as specified and directed.
S&F LED street light fitiing of 72 Watts with driver inside a pressure die cast aluminium housing with toughened glass cover, IP 66 degree of protection including suitable size clamps with nut & bolts for fixing on pole/Bldg complete all as specified and diretced.. Make Havells Cat Part No LHFAXU7DPN6J070 or equivqlent in Philips/Bajaj.
S&F LED Flood light fitiing of 200 Watts with driver inside a pressure die cast aluminium housing with toughened glass cover ,IP 66 degree of protection including suitable size clamps with nut & bolts for fixing on pole/Bldg complete all as specified and diretced. Make : Havells Cat No JETAVALOURFL200WLED757PINTWBLTG or equivalent in Philips/Bajaj
S&F LED flood light fitting of 180 Watts with driver inside a pressure die cast aluminium housing with toughened front glass cover, IP 66 degree of protection of any description complete all as specified. Make: Havells Cat No. JETAVALOURFLS180WLED757MODASYMLTG or equivalent in Philips / Wipro / CG.
S&F LED light fitting 20 watt including LED rod, wall mounted LED batten with polycarbonate housing & integrated electronic driver complete all as specified and directed. Make : Havells Cat Part no LUMILINEBS20WLED865SPCWH or eqvilent in Bajaj/Philips
S&F LED Street light fitting 40W with driver inside a pressure die cast aluminium housing with toughened glass cover ,IP 66degree of protection including suitable size clamps with nut & bolts for fixing on pole/Bldg complete all as specified and diretced. pressue die-cast aluminum complete fixing arragne ment complete all as specified and directed. Make :Havells Cat No ENDURAPEARLNEOSL40WLED757PASYTOPC or eqvilent in Bajaj/Philips
S&F Flame proof LED light fitting 30 watt including rod and fixxing arrnagement on wall and testing complete all as specified and directed. Make : Shyam Switchgears Cat Part No SSPL/WG/1231 or equivalent in Sudhir/Baliga.
S&F Flame proof rotary type with termination box in LM6, 16A single pole 250 volts complete all as specified and directed. Make : Shyam Switchgears / Sudhir/Baliga.
S&F of flame proof retardant exhaust fan and suitable louvers of 380 mm size, 230 volts 1440 RPM, 0.25 HP including testing after fixing complete all as specified and directed Make : Shyam Switchgears Cat Pat No SSPL/EF/140 380 or equivalent in Sudhir/Baliga.
S&F Ceiling Fan complete with all accessories 230 V, 1200 mm sweep BEE 5 star rating, complete all as specified and directed.
S&F Exhaust fan , AC Single Phase, 230 Volts of size 300 mm sweep, built in louvers including all necessary fixing arrangements complete all as specified and directed.
S&F Exhaust fan , AC Single Phase, 230 Volts of size 450 mm sweep, built in louvers including all necessary fixing arrangements complete all as specified and directed.
Supplying, fixing and installation testing of storage water heater type (Geysers) 25 Ltrs capacity five star rating with steel tank, ABS body, including pressure valve & electric supply connection with using inlet & outlet heavy duty connection for hot/cold water supply complete including grouting nut & bolts of 15 mm dia 100 mm long for hanging the geysers and plastering and finishing of plastered surface of wall as per exixting finish and testing complete all as specified and directed. Make :- Bajaj / Usha / Havells / Recold.
M&L for iron work of round shape GI tubing for fixing of light fittings on steel tubular pole including welding and necessary accessories i.e. nut, bolts washers etc including supports, bracing MS clamps etc made out of MS angle iron of size 40x40x6 mm of length not less than 1.0 m, fixed to pole/ earth and grout using PCC & clamp, nut & bolts including painting of bracket with two coats of aluminium paint over a coat of red oxide primer, complete all as specified and directed.
M&L for Steel tubular swaged poles complete with cast iron base plate, finial taper Plug, bolts, nuts & Screws as specified type 410 SP-22, 9 m long inclusive of provision of two holes of dia not less than 15mm, edges of hole duly chamfered for drawing 3core copper cable to connect to light, inclusive of two coats of aluminium paint over a coat of red oxide primer including removing the old poles made of cement / steel, complete all as specified and directed.
S & F Bracket made out of GI tubing medium grade 40 mm bore , 90 cm long bend position of 90 degree including MS clamps made out of MS flat iron 25 x 10 mm , nuts, bolts, washers etc and including before fixing applying two coats of aluminum paint over a coat of red oxide primer complete all as specified and directed.
Supply, Installation,Testing and Commissioning of Open Well Submersible Pumpset 3 phase 415 volts, capacity 7.5 HP, Head range 36-48 m (Pipe size:- Suction/Discharge 65mm x50mm) with suitable size submersible cable 40 m, complete all as specified and directed. Make : Kirloskar or equivalent make in KSB / Jyoti.
S&F of Semi automatic star delta starter suitable for 7.5 HP motor including fixing arrangement in MS sheet encloser, outdoor type, complete all as specified and directed. Make : L&T Cat Part No.MSK SASD or equivalent make in Havells / Seimens.
M&L for Construction of valve chammber with brick masonary having inner 750x750x750 mm ( suitable for 50 mm Gate valves & reflux valves) with PCC 1:4:8 type D2 for foundation, brick work wall in CM 1:4, PCC 1:2:4 type B1 for coping, 15 mm thick plaster in cement mortar 1:4, including provision of 5 mm thick MS sheet top cover with welding of brazing of MS flat of size 25mmx4mm at edges and in diagonal and angle iron base frame of 40x40x5 mm, including preparation of new steel / iron surface & applying two coats of synthetic enamel paint over a coat of red oxide primer, two coats of white wash on internal & extternal surfaces of plastering and including locking arrangement with lock & key, including demolition of existing chamber & necessary excavation and earth work, complete all as specified and directed .
K LAKSHMAN SINGH AND CO
Srinivash Engineers
Mavee Syndicate
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .