Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.2 LAccepted-AOC 150 BC LINE MALL ROAD MEERUT CANTT 250001 | MEERUT | UTTAR PRADESH | 250001 | L1 | Accepted-AOC found lowest | |
| 2 | L2₹6.5 L+₹1.3 L (24.5%)Rejected-Finance | L2 | Rejected-Finance Not found lowest | |
| 3 | L3₹7.5 L+₹2.2 L (42.8%)Rejected-Finance | L3 | Rejected-Finance Not found lowest |
| Sl No | Description | Qty | Unit | KALSI CONSTRUCTION CO L3 | VIRAT CONSTRUCTIONS L1 | dinesh enterprises L2 |
|---|---|---|---|---|---|---|
| 1.00M&L for annual maintenance/servicing and repair of standby DG Set of existing make of following capacity i.e KVA maintenance schedule prescribed in repair and maintenance mannual (repair & maintenance should be carried out by the manufacturer's authorised mechanic from the servicing centre) including fixing charges for replacement of parts specified in relevent item here in after complete all as specified and directed. Note: Servicing of DG set to be carried out by engineers of authorised dealer/service centre of kirlosker/greaves/cummins only parts/components for replacement shall be measured and paid for seperately. Checking and servicing/repair and maintenance of (i) Lubricant oil leaking. (ii) Operation of oil filter and repair to lubricant oil leaking and cooling system leaking, radiator air restriction operation of coolant heater, hoses and connection, belt connection and tension. Fan hub drive pully and water pump heat exchanger, cleaning of water separator and cooling system. (iii) Leaking in air intake system,air cleaner restriction piping and connection. (iv) Fuel line and connection, fuel transfer pump, draining out fuel sidement from tank. (v) Leakage in exhaust system and exhaust restriction, drain out condensate trap, torquing to exhaust manifold and turbo charger capscrew. (vi) Battery charging system level up electrolyte and specific gravity, repair and maintenance of safety control and alarm. (vii) Cleaning of engine tighting of all nut bolt washer and unusual vibration. (viii) Air inlet and outlet for restriction and proper connection to electric connection, operation of generator heater strip greasing to all bearing and movable part, measurement and recording winding resistance cleaning up complete generator. (ix) Complete reset switch in automatic lightning of connection, instrumentation. | ||||||
| 1.01 | 63 KVA | 2 | Each Job | 2,000 ₹4,000 Lowest | 2,600 ₹5,200 | 4,500 ₹9,000 |
| 1.02 | 40 KVA | 1 | Each Job | 1,800 ₹1,800 Lowest | 2,000 ₹2,000 | 3,500 ₹3,500 |
| 1.03 | 30 KVA | 2 | Each Job | 1,500 ₹3,000 Lowest | 1,800 ₹3,600 | 3,500 ₹7,000 |
| 1.04 | 20 KVA | 3 | Each Job | 1,500 ₹4,500 Lowest | 1,800 ₹5,400 | 3,500 ₹10,500 |
| 2.00 | Labour only for attending the complaints of DG set with AMF Panel carried out by manufacturer's authorised mechanic from the servicing centre without any delay for rectifying the defects by carefully opening and check the DG set parts to find out defects if any at site and replace the defected parts from the DG Set for smooth functioning complete all as specified.and directed. (Replacement of parts shall be measured and paid seperately under respective items of BOQ). | 20 | Each Job | 500 ₹10,000 Lowest | 1,000 ₹20,000 | 2,500 ₹50,000 |
| 3.00Supply and fixing the following spares in replacement/ fixing at site for DG sets as per existing make and model complete all as specified and directed. | ||||||
| 3.01 | Fuel flexible pipe wire braded,1,1/4''to 3/8''PVC best quality. | 10 | RM | 450 ₹4,500 | 60 ₹600 Lowest | 150 ₹1,500 |
| 3.02 | Oil pressure gauge of existing make. | 2 | Each | 900 ₹1,800 | 950 ₹1,900 | 250 ₹500 Lowest |
| 3.03 | Water temperature gauge of existing make | 2 | Each | 800 ₹1,600 | 750 ₹1,500 | 250 ₹500 Lowest |
Tender Value
₹8 L
EMD Value
₹16,000
Closing Date
25 Mar 2026, 6:00 pmClosed
Sachin R Barshetty
GE Basoli PO Lakhanpur Distt Kathua (JK) 184152
GE/BAS-93/2025-26 Repair/replacement to diesel engine set of different capacity alongwith connected items at Madhopur Stn under GE Basoli
2026_MES_755222_1
GE/BAS-93/2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Madhopur station under GE Basoli
As per tender docs
8 documents required · 8 mandatory
₹500
GE Basoli
₹16,000
Yes
19 May 2026
5 Mar 2026
27 Mar 2026
5 Mar 2026
25 Mar 2026
18 Mar 2026
0M&L for
Labour only for attending the complaints of DG set with AMF Panel carried out by manufacturer's authorised mechanic from the servicing centre without any delay for rectifying the defects by carefully opening and check the DG set parts to find out defects if any at site and replace the defected parts from the DG Set for smooth functioning complete all as specified.and directed. (Replacement of parts shall be measured and paid seperately under respective items of BOQ).
Supply and fixing the following spares in replacement/ fixing at site for DG sets as per existing make and model complete all as specified and directed.
Fuel flexible pipe wire braded,1,1/4''to 3/8''PVC best quality.
Oil pressure gauge of existing make.
Water temperature gauge of existing make
Ignition switch of existing make
Indicating lamp
Battery terminal heavy duty of brass of existing make.
Distilled water.
Coolant for radiator. Sealed bottle make castrol.
Oil filter for DG set Cap 5 KVA to 63 KVA
Fuel filter set DG set Cap 5 KVA to 63 KVA
Engine oil premium blue 20W40. Make : Servo, Castrol or Equivalent as directed.
Fan belt set Make Fenner/ Dunlock or Equivalent make approved by GE.
Self starter 12 volts Make:Lucas/ Tvs or Equivalent make approved by GE.
Self starter 24 volts Make:Lucas or Equivalent make approved by GE.
Air Filter for DG set cap upto 63 KVA .Make Mico, Boss or Equivalent make approved by GE.
AVR for 63 KVA DG Set
AVR for 20 KVA to 40 KVA DG Set
Battery lead 1.5 metre long, heavy duty, multi stranded copper conductor, PVC insulated 16 Sqmm single core.
Dynamo 12 volts Make- Lucas or Equivalent make approved by GE.
Fuel injector pump or DG set cap 5 KVA to 63 KVA
Solenoid Valve
Vibration pad
M&L for cleaning and descaling of radiator assembly by using suitable chemical (MAC solution) and by blower fan and by injecting water in high pressure in water tubings so as to remove all dirts etc in the fins complete all as directed for 63 KVA DG set
Opening, dismentaling and repair/servicing of Self starter 12/24 volts replacing burnt/ wornout spares, parts asembling after repair and testing complete all specified and directed by Engineer-in-charge (spares shall be measured and paid separately)
Supply and fixing the following spares in self starter 12/24 voltas per existing make and model complete all as directed and specified.
Armature coil
Field coil
Carbon brush
Copper bush
Solenoid switch
M&L for replacement of battery 12 volts,150 AH complete. Make: Exide or Equivalent.
M&L for replacement of Dry battery 12 volts,100 AH complete.Make:Exide or Equivalent.
intenance/servicing and repair of standby DG Set of existing make of following capacity i.e KVA maintenance schedule prescribed in repair and maintenance mannual (repair & maintenance should be carried out by the manufacturer's authorised mechanic from the servicing centre) including fixing charges for replacement of parts specified in relevent item here in after complete all as specified and directed. Note: Servicing of DG set to be carried out by engineers of authorised dealer/service centre of kirlosker/greaves/cummins only parts/components for replacement shall be measured and paid for seperately. Checking and servicing/repair and maintenance of (i) Lubricant oil leaking. (ii) Operation of oil filter and repair to lubricant oil leaking and cooling system leaking, radiator air restriction operation of coolant heater, hoses and connection, belt connection and tension. Fan hub drive pully and water pump heat exchanger, cleaning of water separator and cooling system. (iii) Leaking in air intake system,air cleaner restriction piping and connection. (iv) Fuel line and connection, fuel transfer pump, draining out fuel sidement from tank. (v) Leakage in exhaust system and exhaust restriction, drain out condensate trap, torquing to exhaust manifold and turbo charger capscrew. (vi) Battery charging system level up electrolyte and specific gravity, repair and maintenance of safety control and alarm. (vii) Cleaning of engine tighting of all nut bolt washer and unusual vibration. (viii) Air inlet and outlet for restriction and proper connection to electric connection, operation of generator heater strip greasing to all bearing and movable part, measurement and recording winding resistance cleaning up complete generator. (ix) Complete reset switch in automatic lightning of connection, instrumentation.V h ¨ XMaterial and labour for Maintenance of AMF panel and cleaning of dust inside with blower, cleaning of moving part /contacts from CT cleaner, tightening of loose parts /electrical wires, cleaning of contactors, relays and junction points, servicing/ adjustment of relay, complete testing of AMF relay with necessary settings and load management system complete with replacement of worn out unserviceable components/burnt wires thimbles/ lugs complete tested For DG set up to 63 KVA complete all as specified and directed. Note: Parts/components for replacement shall be measured and paid seperately.¬Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soft loose of soil complete all as specified and directed.òMaterial and labour for well burnt, old size Sub Class 'B' brick for covering protection to the eletric cable laid dry flat transversally along the length of cable with width equal to length of brick complete all as specified and directed.-M&L for providing earthing complete with galvanised steel earth plate electrode 60 x 60cm x 6.0mm thick buried dirictly in ground (Earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to and including galvanised earth strip 32 X 6mm mm size upto 7.5 meter long by means of bolts,nuts check nuts and washers of all galvanised iron or steel all as shown in electrical plate No.3 of SSR Part-1 and connected to test point including GI pipe medium grade 40mm dia for protection of earth lead, necessary excavation/earth work in any type of soil/rock strata,funnel with wire mesh and watering pipe (GI, light grade) 20mm dia, PCC pit with 50mm thick PCC cover etc including testing complete all as directed and specified.
S&F following spare parts in AMF panels complete all as specified and directed.
Supply failure timer of existing make.
Restoration timer of existing make.
Microprocessor based AMF Module incorporating of supply and restoring timer 3 impulse automatic engine start /stop/ logic & fails to start locknut Mains/generator voltage, frequency sensing.
Diod 25 Amp thread type
Auxillary contactor 3 phase suitable for AMF Panel
NC/No relay of existing make
Under voltage relay of existing make
Time Delay relay of existing make
CT's coil 5/50 for up to 63 KVA DG Set
Contactor 4 pole 63 Amps for upto 63 KVA DG set
Battary charger in AMF Panel
Controller for 82.5 KVA TO 200 KVA
Controller for 05 KVA TO 62.5 KVA
Contactor coil for up to 63 KVA
HRC fuse for short circuit protection
M & L for removing existing old rusted paint on DG set of painted surface and applying with two coats of synthetic enamel spray paint to match with existing colour good finish of following capaity complete all as specified and directed.
Repair & Maintenance of existing canopy of eco friendly DG Set above cleaning of internal & external parts, tightening of loose parts, replacing of unserviceable door locks and keys, replacing of damaged or burned inside sponge insulations complete all as specified and directed.
M & L for rewinding of DG set alternator of capactity upto 63 KVA with existing size and gauge and adequate number of turns of super enamelled copper winding wire and bore conductor including varnishing insulating material drying baking heating and connection leads with thimble and making connection complete all as specified and directed.
Supply and fix in repair of unserviceable MCCBs of following capacity :-
100 Amps 4 pole 16 KA
63 Amps 4 pole 10 KA
S&F in repair of TPN 63 Amps 240 volts,50 Hz,16 KA rapturing capacity complete all as specifified and directed.
Supply,laying, Jointing and testing of LT underground cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) laid in trenches/ducts/fixed on wall/pole/laid under road/path/culvert encased in GI pipe, electric cable 1100 Volts grade with stranded aluminium conductor consisting necessary lugs and compression brass glands including taking down of old cable of following sizes complete all as specified and directed.
70 Sqmm 3.5 core
50 Sqmm 3.5 Core
25 Sqmm 4 Core
Excavation in trenches not exceeding 1.5 metres wide and not exceeding 1.5 metres in depth for foundation or laying/taking out existing pipe etc and getting out in soft/loose soil complete all as specified and directed
Removing excavated material to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and directed.
Supply & laying of approved quality natural river sand under cable upto 15cm before laying the cable and 8cm over the cable after laying, punned down to overall thickness of 18cm in trenches for cable cushioning complete all as specified and directed. (Punned thickness shall be measured)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.33 MB
Tender93.pdf
Tender Documents • 1.30 MB
BOQ_845889.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .