Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.6 LAccepted-AOC ROWRIAH KB ROAD PO CHALIHA JORHAT 785004 ASSAM | JORHAT | JORHAT | ASSAM | 785004 | ₹28.6 L | L1 | Accepted-AOC Lowest and Reasonable |
| 2 | L2₹34.2 L+₹5.7 L (19.8%)Rejected-Finance | ₹34.2 L+₹5.7 L (19.8%) | L2 | Rejected-Finance Other than Reasonable |
| 3 | L3₹35.0 L+₹6.4 L (22.5%)Rejected-Finance | ₹35.0 L+₹6.4 L (22.5%) | L3 | Rejected-Finance Other than Reasonable |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
14 Dec 2022, 6:00 pmClosed
CWE (AF) Jorhat
HQ CWE (AF) Jorhat, Rowriah, Assam - 785005
REPAIR/ MAINTENANCE OF CENTRAL AC PLANT, PACKAGE TYPE OF AC PLANT, DUCTILE SPLIT AC PLANT ALONGWITH REPAIR/ MAINT OF ALL TYPES OF DUCTS, DIFFUSER, FILTERS, CT LT PANELS AND OTHER CONNECTEDF WORKS AND REPAIRS TO TEMP AND HUMIDITY CONTROL SYSTEM AT AFS
2022_MES_547158_2
83966/E8
Open Tender
Civil Works
Item Rate
240 days
AF Stn Jorhat under GE (AF) Jorhat
Please refer tender documents
5 documents required · 5 mandatory
₹500
Yes
GE (AF) Jorhat
₹60,000
Yes
17 Feb 2023
24 Nov 2022
21 Dec 2022
24 Nov 2022
14 Dec 2022
30 Nov 2022
Amount
CENTRAL TYPE AC PLANT 40 TR CAPACITY (3 x 20 TR) Material and labour for opening head of open type reciprocating compressor 20 TR Capacity of make: ACCEL, MODEL: SMC-6-65 including dismantling completely 20 TR capacity compressor parts in presence of MES representative and display all the parts/ components of compressor for inspection of Engineer-in-Charge to ascertain the serviceability of existing parts for repair/ replacement of unserviceable/ defective parts, re-assembling and re-installation of compressor in original position after repair, reconnecting and making functional in all respect complete all as specified and as directed. (Note:- Spare parts shall be measured and paid separately under relevant item here-in after)
Supply only for shaft oil seal with 'O' rings complete as all as specified.
Supply only for suction and dicharge valve plate complete as all as specified.
Supply only for ring set for piston complete as all as specified.
Supply only for oil filter complete as all as specified.
Supply only for loader/ unloader complete all as specified.
Supply only for main bearing complete all as specified
Supply only for crank shaft model SMC-6-65 complete all as specified.
Supply only for connecting rod complete all as specified.
Supply only for half section bearing complete all as specified.
Supply only for of piston with pin and ring set complete all as specified.
Supply only for suction valve retaining plate complete all as specified.
CENTRAL TYPE AC PLANT (15 TR CAPACITY) (3 x 7.5 TR) Opening head of open type reciprocating compressor 7.5 TR capacity of make: FREEZE KING including dismantling complete 7.5TR capacity compressor parts in presence of MES representative and display all the parts/ components of compressor for inspection of Engineer-in-Charge to ascertain the serviceability of existing parts for repair/ replacement of unserviceable/ defective parts, re-assembling and re-installation of compressor in original position after repaired, reconnecting and making functional in all respect complete all as specified and as directed. (Note :- Spares parts shall be measured and paid separately under relevant items here-in-after).
Supply only for ring set for piston complete all as specified.
Supply only for oil filter complete all as specified.
Supply only for main bearing complete all as specified.
Supply only for crank shaft model SMC-6-65 complete all as specified.
Supply only for of connecting rod complete all as specified.
Supply only for half section bearing complete all as specified.
Supply only for piston with pin and ring set complete all as specified.
Supply only for head gasket set as approved and suitable complete all as specified.
Supply only shaft seal complete all as specified.
Supply only for spring guard as approved and suitable complete all as specified.
Supply and fix for suction and discharge valve plate suitable for compressor 7.5 TR complete all as specified and as directed.
Supply and fix for 'V' belt B-76 as approved and suitable including taking down old unserviceable one complete all as specified and as directed.
Supply and fix for refrigerant high pressure gauge as approved and suitable including taking down old unserviceable one complete all as specified and as directed.
Supply and fix for refrigerant low pressure gauge as approved and suitable including taking down old unserviceable one complete all as specified and as directed.
Supply and fix for LP/ HP cut out with operating range at 0/ PSI to 30/ PSI as approved and suitable including taking down old unservice able one complete all as specified and as directed.
Supply and fix for oil pressure gauge as approved and suitable including taking down old unserviceable one complete all as specified and as directed.
Supply and fix for safety valve for condenser as approved including taking down old unserviceable one complete all as specified and as directed.
Supply and fix for 'V' belt B-85 as approved and suitable including taking down old unserviceable one complete all as specified and as directed.
Supply and filling only compressor oil as approved and suitable for compressor of central AC plant complete all as specified and as directed
Supply and filling only refrigerant gas R–22 as approved and suitable for compressor of central and package AC plant/ unit of various locations complete all as specified and as directed.
Supply and filling only refrigerant gas R–407 C as approved and suitable for Compressor of spli tductable AC unit at Auditorium complete all as specified and as directed.
Supply and fix for 'V' Belt T-51B as approved and suitable including taking down old unserviceable one complete all as specified and as directed.
PACKAGE TYPE AC PLANT Taking down defective compressor sealed unit 3.75 TR capacity suitable for R-22 refrigerant, 3 phase 415 volt after disconnecting all electrical connections and replaced the same with new compressor of same capacity and including flushing the old gas and recharging with appropriate quantity of R-132a refrigerant gas complete all as specified and as directed.
All as per Item No. 37 here-in-before but 5.5 TR Capacity complete all as specified and as directed.
All as per Item No. 37 here-in-before but 20 TR Capacity complete all as specified and as directed.
Taking down defective compressor sealed unit 2.5 TR capacity, 3 phase 415 volt of split ductable type AC unit after disconnecting all electrical connections and replaced the same with new compressor of same capacity and including flushing the old gas and rechanging with appropriate quantity of refrigerant gas complete all as specified and as directed.
Supply and fix for 'V' belt A-32, as approved and suitable for air blower motor including taking down old unserviceable one complete all as specified and as directed.
Supply and fix for PCB with FRC cable for package type AC unit 11TR capacity of make: VOLTAS complete all as specified and as directed.
Supply and fix for printed circuit board for package type AC unit 10 to 15 TR of make: BLUE STAR complete all as specified and as directed.
Supply and fix for printed circuit board for split ductable AC plant unit 17TR of make: BLUE STAR complete all as specified and as directed.
REPLACEMENT OF LT PANEL ELECTRICAL SPARE COMPONANTS Supply and fix for 1NO+1NC for Contactor CL-25A310T as approved and suitable for LT panel starter of central AC plant including taking down old unserviceable one complete all as specified and as directed. Make: GE/ L&T/ BCH/ SIEMENS as approved.
Supply and fix for contactor CL-00A310T as approved and suitable for LT panel starter of central AC plant including taking down old unserviceable one complete all as specified and as directed. Make: GE/ L&T/ BCH/ SIEMENS as approved.
Supply and fix for contactor CL-01A310T as approved and suitable for LT Panel Starter of CENTRAL AC PLANT including Taking down Old Unserviceable One, complete all as specified and as directed. Make : GE/ L&T/BCH/SIEMENS as approved.
Supply and fix for contactor CL-02A310T as approved and suitable for LT panel starter of central AC plant including taking down old unserviceable one complete all as specified and as directed. Make: GE/ L&T/ BCH/ SIEMENS as approved.
SSupply and fix for contactor CL-06A311M as approved and suitable for LT panel starter of central AC plant including taking down old unserviceable one complete all as specified and as directed. Make: GE/ L&T/ BCH/ SIEMENS as approved.
Supply and fix for contactor relay MXO coil voltage 240 volt as approved and suitable for LT panel starter of package type AC plant unit including taking down old unserviceable one complete all as specified and as directed. Make: SIEMENS/ L&T/ BCH/ GE as approved.
Supply and contactor relay SICOP 3TF, 32/35, coil voltage 415 volt as approved and suitable for LT panel starter of package type AC unit 7.5 TR capacity at including taking down old unserviceable one complete all as specified and as directed. Make: Simens/ L&T/ BCH/ GE as approved.
Supply only for MCB TP 63 Amp complete all as specified. Make L&T/GE/Legrand/ Havells as approved.
Supply only for MCB TP 32 Amp complete all as specified. L&T/GE/Legrand/ Havells as approved.
Supply only for MCCB TP 125 Amp, 415 volt 50 Hz 25KA complete all as specified. Make: L&T/GE/Legrand/ Havells as approved.
Supply and fix for pre filter box type having dust filtration capacity 90% efficiency down to 10 micron of size 500 x 400 x 50mm complete all as specified and as directed.
Supply and fix for MCCB 100 Amp, 4 pole, 16 KA, 415V, 50Hz capacity as approved and suitable for LT Panel of central and package AC plant including taking down old unserviceable one, complete all as specified and as directed. Make- L&T/GE/Legrand/ Havells as approved.
Supply and fix for MCCB 63 Amp, 3 pole, 16 KA, 415V, 50Hz capacity as approved and suitable for LT Panel of central and package AC plant including taking down old unserviceable one, complete all as specified and as directed. Make- L&T/GE/Legrand/ Havells as approved.
Supply and fix for isolator 4 pole, 63Amp, 415V, 50Hz capacity as approved and suitable for LT Panel of central and package AC plant including taking down old unserviceable one, complete all as specified and as directed. Make- L&T/GE/Legrand/ Havells as approved.
Supply and fix for isolator TP, 63Amp, 415V, 50Hz capacity as approved and suitable for LT Panel of central and package AC Plant including taking down old unserviceable one, complete all as specified and as directed. Make- L&T/GE/Legrand/ Havells as approved.
Supply and fix for isolator TP, 32/40 Amp, 415V, 50Hz capacity as approved and suitable for LT Panel of central and package AC plant including taking down old unserviceable one, complete all as specified and as directed. Make- L&T/GE/Legrand/ Havells as approved.
Supply and fix for digital Ammeter 0-300 Amps of size 4x4", capacity, 3 phase, 415 volt, suitable for the LT Panel board including electrical connection with suitable size of copper wire including taking out unserviceable/ brunt ammeter, complete all as specified and as directed. Make:L&T/ AE/HPL Cat No.PAMEBRITA 32 as approved.
Supply and fix for digital voltmeter 0-500volt rage of size 4x4", 3 phase, 415 volt suitable for the LT Panel board with suitable size of copper wire including taking out unserviceable/ brunt voltmeter complete all as specified and as directed. Make:L&T/ AE/HPL Cat No.PAMEBRITV 32 as approved.
Supply and fixing Indicator LED assy 3 pcs per set suitable for 230 volt matching with exisisting one for the LT Panel board where directed including taking out old U/S indicator assy, electrical connection with suitable size of copper wire complete all as specified and as directed. Make: AE/ HPL or equivalent as approved.
Supply and fix for cast iron sluice valve PN-1.6 with flanged ends 80mm nominal bore ISI marked complete with gun metal or stainless steel spindle and cast iron cap including rubber/ fiber board gasket, nuts, washers etc including taking down old unserviceable sluice valves complete all as specified and as directed. Make: KIRLOSKAR/ BIR/ SANT/ ZOLOTO as approved.
Supply and fix for lugs copper 95 sqmm of required type suitable at site complete all as specified and as directed.
Supply and fix for lugs copper 16sqmm of required type suitable at site complete all as specified and as directed.
Supply and fix for thermometer suitable for reading wet bulb and dry bulb temperature with digital type complete all as specified and as directed.
Supply and fix for temperature and humidity meter suitable for reading for temperature and humidity complete all as specified and as directed.
Material and labour for overhauling of condenser pump, monoblock pumpset complete with cleaning of impeller strainer and including replacement of rubber gasket, gland packings, bearing etc for 3 HP capacity complete all as specified and as directed.
Material and labour for overhauling of condenser pump, monoblock pumpset complete with cleaning of impeller strainer and including replacement of rubber gasket, gland packings, bearing etc for 5 HP capacity complete all as specified and as directed.
Taking down defective burn out cooling tower motor of capacity 1 HP/0.75KW after disconnecting all electrical connections and replaced the same with new cooling tower motor of same capacity including testing and commissioning complete all as specified and as directed.
Supply and fix for voltage stabilizer for automatic operation, single phase, naturally air cooled, indoor type and designed for input variation between 170 volt to 250 volt with output voltage at 230 volt with accuracy ±2.5% of capacity 5 KVA complete all as specified and as directed.
Material and labour for nitrogen gas pressure testing by pressurising with nitrogen gas upto 300 psi the complete system to find out the leakage and maintaining pressure for 24 hours and rectifying leakages in the system, vacuumising complete system of central A/C plant with double stage vacuum pump of 2kg/Sq cm vacuum pressure complete all as specified and as directed.
Supply, laying commissioning and testing of LT XLPE under ground cable of size 50 Sq mm 3.5 core 1100 volts grade armoured, PVC sheathed with aluminium conductor heavy duty confirming to IS 1554 laid in trenches, fixing on wall, under road crossing through protection pipe etc complete all as specified and as directed.
Excavation in trenches n.exc 1.5m wide and n.exc 1.50m depth for laying of cables etc and getting out in soft/ loose soil complete all as specified and as directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exc 25 cm complete all as specified and as directed
Removing of excavated material (soil) to distance not exceeding 50metre and deposited where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and as directed.
Material and labour for dry river sand as in sand cushioning in trenches/ ducts for protection of underground cable (below, above and around the UG cable laid in trenches) of 23 cm spread thickness ( 8 cm in depth before laying the cable and 15 cm in depth after laying the cable) and consolidated (punned) up to 18 cm thickness complete all as specified and as directed. Note : - Thickness after punning shall be measured for payment
Material and labour for sub class 'B', old size bricks for cable protection cover, common burnt clay building bricks, laid dry and flat abutting each other with width equal to length of brick and gap between adjacent bricks not exc.10mm complete all as specified and as directed.
Supply and fix for 1.5 Sqmm PVC insulated and PVC sheathed 3 core armoured copper cable complete all as specified and as directed. Make POLYCAB/FINOLEX/HAVELLS as approved.
Comprehensive maintenance of AC plant remote monitoring system including servicing of unserviceable part equipments complete all as specified and as directed.
Supply only of wireless modem suitable for GSM/GPRS based communication system to be mounted in TRU enclosure. Make CIMCON/ SIEMENS/ MOTOROLA as approved. INSTALLED AT WWR-20 (1 Building) WWR-6 (1 Building)
Supply and fix for humidity sensor with transmitter (signal convereter), working range 0-50C and 0-100% RH, transmitter output 4-20mA, accuracy at 25C± 2% RH suitable for inside room humidity measurement complete all as specified and as directed.
Supply and fix for CPU card for IRTU-6000 with all required accessories complete all as specified and as directed.
Supply and fix for analog input (AI) card all required fitting and accessories complete all as specified and as directed.
Supply and fix for 12 V/5 V SMPS with battery charging circuit and necessary fittings complete all as specified and as directed.
Supply and fix for 24 V SMPS with battery charging circuit and necessary fittings complete all as specified and as directed.
Material and labour for preventive and comprehensive maintenance of central AC chiller plant of capacity 3 x 80 TR strictly through OEM i.e. M/S Blue Star for the plant and equipment of Model No. XAC2YS-080A. The scope of work is as under:- (a) Checking and rectification if required for abnormal noise, vibration, leakage of refrigerant , oil etc. (b) Topping up of system with refrigerant and oil replace dehydrators etc. (c) Checking of operation of oil heater, motor protector, flow switch, loading unloading etc. (d) Checking of control valve. (e) Develop action plan for rectifying abnormalies if any observed in the performance of the system. (f) Attend breakdown calls as and when required, investigation, locate defect and submit action plan to rectify the same. (g) All the maintenance/ servicing work should be done in such a way so that the equipment /unit can be used for its optimum performance. (h) Adjustment in the system to achieve required temprature and RH level . (j) Cleaning of all type of air filter (k) Checking and servicing of AHU. (l) Descaling of copper tube of cooling coil bu suitable means as per manufacturer recommandation. (m) Cleaning of ducting system having diffuser, grills, damper etc. (n) Servicing of evaporators, expansion valve, water cooled condenser, oil cooler, oil piping, oil filter, refrigerant piping, refrigerant filter, solenoid valve, AHU control panel. NOTE :- (a) Scope of work also include supply of material like timer, chiller in/out sensor, filter drier and solenoid coil during AMC. (b) Comprehensive maintenance is to be carried out by OEM i.e. M/S Blue Star only. The contractor shall be required to submit an MOU with OEM for the same and it will be essential requirement and technical evaluation stage.
Taking down carefully burnt out electric driven compressor motor 15 HP capacity from foundation channel after disconnecting main electric supply from the motor starter Panel, dismantling motor carefully for checking, removing to workshop for repairing, taking out burnt, coils from the slots of stator, other accessories such as ball bearing, rotor, cleaning the stator slots and rewinding the same with new supper enameled copper winding wire with appropriate gauge and quantity, heating, varnishing with Doctor Beck's insulated varnish, Re-assembling the same after greasing the ball bearing motor, painting on monor body, refixing to original position after repairing from workshop, re-installation on existing channel and re-connecting to electric supply, commissioning and testing complete all as specified and as directed.
All as per serial item No.1 here-in-before but for 12.5 HP capacity of compressor motor.
All as per serial item No.1 here-in-before but for 7.5 HP capacity condenser/ chiller water pump motor.
All as per serial item No.1 here-in-before but for 5 HP capacity cooling tower motor/ AHU motor and air blower motor.
All as per serial item No.1 here-in-before but for 3.0 HP capacity water pump motor.
All as per serial item No.1 here-in-before but for 2.5 HP capacity of air blower of condensing fan motors.
Material and labour for preparing old painted surface of equipments such as compressor, condenser, chiller, motor, copper pipe, GI pipes, pump set, belt guard, cooling tower etc installed at central type AC plant of capacity 3 x 20 TR and applying one coat of synthetic enamel paint over a coat of red oxide primer. The colour code of equipment/ pipes will be same as per existing.
All as per serial item No. 7 here-in-before but CENTRAL TYPE AC PLANT 3 x 7.5 TR Capacity.
Material and labour for descaling of copper tubes of condenser suitable for 20 TR compressor by circulating discaling solution ( diluted HCL) with pump and rodding into the tubes for removing all deposited materials complete all as directed.
All as per serial item No. 9 here-in-before but suitable for condenser for 7.5 TR compressor.
Servicing of AHU complete of various capacities including cooling coil, filters, removing dirt, scales etc with cleaning chemicals (coil cleaner) and applying a coat of synthetic enamel paint on outer body of the existing colour code complete all as specified and as directed.
Servicing of condensor unit including cleaning of condensor coil with and fins with solvent material by using pressure water pump, servicing fan motor complete and applying a coat of synthetic enamel paint on outer body complete all as specified and as directed.
Carefully dismantling ceiling below indoor unit of package type AC plant of capacity 17 TR, dismantling worn out insulation, drain water collecting tray and material and labour for replacement of worn out insulation and fabrication of water collecting tray with 20 SWG GI sheet as required at site not exc.1.5 m x 1.5 m, reassembling the ceiling including replacement of broken/ damage ceiling board as per existing complete al as specified and as directed.
Servicing of air blower including replacement of motor, block bearing, blower shaft re-metalling, polishing and reassembling complete all as specified and directed.
Supply and replacement of damper of the plenum of AHU of any size including replacement of canvas cloth and bolts nuts etc. complete all as specified and as directed.
Supply and replacing of liquid line filter drier for use with CFC, HCFC & HFC , R22, R134a of any capacity complete all as specified and as directed. Make : EMERSON/ CatchAll/ Indfoss as approved.
Supply and replacing expansion valve of capacity up to 5.5 TR including taking down complete all as specified and as directed.
All as per serial item No17 here-in-before but for valve of capacity up to 7.5 TR.
All as per serial item No17 here-in-before but for valve of capacity up to 40 TR.
Supply and replacement of condenser motor fan blade suitable upto 0.5HP 3 phase 415V motor including taking down unserviceable one complete all as specified and directed.
Supply and replacement of condenser motor epoxy coated weather proof upto 0.5 HP 3 phase 415V with bracket and leg including taking down unserviceable one complete all as specified and as directed.
Supply and replacement 'Y' stainer in condensing water line complete with MS body of size 80/50 mm including modification of pipe line for refixing the stainer in another location of the water pipe line and replacement of flanges and nuts & bolts, packing ete complete all as specified and as directed.
Supply and replace cooling tower sprinkler with gear box, drive shaft, FRP fan suitable to motor assembly ,base, bearings and arms stay supporter etc suitable for 40 TR AC plant including taking down unserviceable one complete all as specified and directed.
Supply and fix for heating rod/ element of capacity 2KW and taking down burnt electric heating rod/ element including electric connection from AC plant and complete all as specified and as directed.
Supply and replacing solenoid valves, C castle, valve consists of MKC 2 coil and series 2 body MOO-275 type SWP-500 suitable for 15 TR central AC Plant (General purpose solenoid valve) complete all as specified and as directed.
Supply and replacing solenoid valves, C castle, valve consists of MKC 2 coil and series 2 body MOO-275 Type SWP-500 suitable for 20 TR AC Plant (General purpose solenoid valve) complete all as specified and as directed.
Supply and fix for flexible PVC insulated copper conductor wire, nominal cross-sectional area 16 Sqmm, single core for connection of outer/ inner unit/ Panels including taking down old unserviceable wire complete all as specified and as directed. Make : Havells/ Finolex/ Payal as approval.
Supply and fix for flexible PVC insulated copper conductor wire, nominal cross-sectional area 6 Sqmm, single core for connection of outer/ inner unit/ panels including taking down old unserviceable wire complete all as specified and as directed. Make : Havells/ Finolex/ Payal as specified.
Supply and fix flexible PVC insulated copper conductor wire, nominal cross-sectional area 10 Sqmm, single core for connection of outer/ inner unit/ Panels including taking down old unserviceable wire complete all as specified and as directed. Make : Havells/ Finolex/ Payal approved.
Suply and fix for flexible PVC insulated copper conductor wire, nominal cross-sectional area 1.5 Sqmm, 3 core for connection of OP/ LP connection of AC plnat including taking down old unserviceable wire complete all as specified and as directed. Make : Havells/ Finolex/ Payal as approved.
Supply and fix for MCCB 200 Amp, 415volt, 50 HZ, breaking capacity 35KA, 3 Pole (thermal setting 80-100% in & megnetic setting 6-10), Icu=Ics100% capacity as suitable for indoor electric panel board including dismantling/ opening the existing burnt out/ unserviceable MCCB 4 pole with disconnected the electrical connection and making the electrical connection with aluminum thimbles as per existing position complete all as specified and as directed. Make L&T/ GE/ Havells as approved.
LESS SCHEDULE OF CREDIT (NOTE : The bidders are required to quote the same amount as inserted in estimated rate column against the group of credit items. For details refer Schedule of Credit including notes therein of tender documents.
NIHAR ENTERPRISE
M/S BARUA REFRIGERATION WORKS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .