Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.9 LAccepted-AOC CHANDIGARH | CHANDIGARH | CHANDIGARH | 160001 | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹28.5 L+₹4.6 L (19.4%)Rejected-AOC 3082 SECTOR 20D CHANDIGARH 160 020 | CHANDIGARH | CHANDIGARH | 160020 | L2 | Rejected-AOC OTHER THAN LOWEST |
Tender Value
₹42 L
EMD Value
₹84,000
Closing Date
28 Sept 2024, 6:00 pmClosed
GE Chandigarh
GE Chandigarh N Area Pin-160003
REPAIRS/REPLACEMENT AND MAINT OF DG SET INCLUDING INTERNAL WIRING, FITTING AND FIXTURES AT PCDA OFFICE BLDG SEC-9A AND DAD RESIDENTIAL COLONY SEC- 35B UNDER GE CHANDIGARH
2024_MES_669707_1
GE/CHD-36/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Chandigarh
Class D category b(i) for contractor enlisted in MES
7 documents required · 7 mandatory
₹500
GE Chandigarh
₹84,000
Yes
21 Nov 2024
2 Sept 2024
30 Sept 2024
2 Sept 2024
28 Sept 2024
16 Sept 2024
2 Sept 2024 - 7 Sept 2024
Amount
Taking down carefully aluminum/copper point wiring (light, fan, socket or power) complete along with fittings such as switches, ceiling roses, pendants, regulators sockets etc, and removing from site and making good disturbed surfaces of walls, floors etc all as directed by Engineer in Charge.
Taking down existing unserviceable MCB DB along with MCBs complete by disconnecting all as directedby Engineer in Charge.
Taking down existing unserviceable T/Light fitting any type & Capacity
Taking down existing unserviceable sub main wiring with upto 2/3 core 1.5 to 6Sqmm aluminum/Copper cable all as directed by Engineer in Charge.
M&L Point wiring with 1.5 sq mm copper conductor FRLS (multistrand) PVC insulated ISI marked unseathed cable in and including concealed , non metalic rigid PVC conduit medium grade ISI marked as per IS colour coding, conduit not less than 19 mm with all fittings & other accessories and also including PVC insulated ISI marked unseathed FRLS cable of size 1.5 sq mm copper conductor as earth wire to common earth dolly including concealed in wall, mild steel Box, 1.6mm thick with 3mm thick plastic laminated sheet as required at site suitable for modular switches, sockets, fan regulator etc for One light point controlled by one way switch complete all as specified.
All as per item No 5 above but One ceiling /exhaust fan point controlled by one, one way 5 Amps switch
All as per item No 5 above but One 3 pin socket outlet 5 Amps on independent board
All as per item No 5 above but One 3 pin socket outlet 5 Amps on same board
All as per item No 5 above but One light point controled by two, two way 5 Amps switches.
All as per item No 5 above but One bell/ buzzer point controled by one bell push on same board with other switches or on independent board.
M&L for Point wiring complete with 2.5 Sqmm single core, PVC insulated unsheathed, FRLS cable, 1100 volts grade as per IS colour coding, multistranded copper conductor, drawn through and including rigid non metallic PVC conduit and conduit accessories fixed on surface of wall/ceilings or concealed etc., including provision of PVC insulated 2.5 Sqmm FRLS cable with copper conductor for earth continuity and connected to common earth dolly and metal boxes concealed in wall , modular cover plates with frames on top for housing the switches, socket outlet etc., all as specified and as directed for one switch socket outlet 16 Amps on independent board.
M&L for Sub main wiring/power wiring complete with two runs of 4.0 Sqmm, single core, PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistranded with copper conductor, drawn through and including suitable size of rigid non metallic PVC conduit pipe and accessories on surface wall/floors/concealed etc., with one run of PVC insulated, 4.0Sqmm FRLS copper conductor for earth continuity as per IS colour coding all as specified and as directed. NOTE :- Two runs of main copper conductor, one run of copper conductor for earth continuity and one run of conduit shall be measured as one unit length
All as per item No 12 here in above but with 2x6 Sqmm for phase and neutral and 1x6 Sqmm for earth wire complete.
M&L for 3x1.5 Sqmm PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistranded with copper conductor drawn in the existing metal/ PVC conduit & Casing capping including connecting of the ends into the switch / socket/ DB complete all as specified and as directed. Note : Three runs of cable shall be measured as one unit.
Supply and fixing switch piano flush type single pole one way 5 amps 230 volts complete all as specified and as directed.
Supply and fixing socket piano flush type universal 2 in 1,3 pin 5 Amps, 230 volts complete all as specified and as directed.
Supply and fixing switch piano flush type single pole one way 15 amps 230 volts complete all as specified and as directed.
Supply and fixing switch socket flush type universal 2 in 1, 3/6 pin 15 Amps 230 volts complete all as specified and as directed.
Supply and fixing switch socket combination 2 in 1, 3 pin, 6 and 16 Amp 230 volts flush type universal complete all as specified and as directed.
Supply and fixing switch socket combination modular type multipurpose 3 pin, 16 Amp and one pin 6 Amp contolled by one switch complete all as specified and as directed.
Supply and Fixing Ceiling rose 3 terminal 5 Amps 230 volts PVC/Polycarbonate, insulated body complete all as specified and as directed.
Supply and Fixing step type electronic fan regulator of capacity 100 watts 230 volts for ceiling / exhaust fan flush type complete all as specified and as directed.
Supply and Fixing socket type stepped electronic fan regulator flush type of capacity 100 watts 230 volts for ceiling / exhaust fan flush type complete all as specified and as directed.
Supply and Fixing stepped electronic modular fan regulator, 2 module flush type of capacity 120 watts 230 volts for ceiling / exhaust fan flush type complete all as specified and as directed.
Supply and Fixing Ding Dong Bell AC 230 volts single pole complete all as specified and as directed.
Supply & Fixing 6 Amps 1 way one module switch complete all as specified and as directed.
Supply & Fixing 6 Amps 2 way one module switch complete all as specified and as directed.
Supply & Fixing 16 Amps one way one module switch complete all as specified and as directed.
Supply & Fixing 6 Amps bell push one module switch complete all as specified and as directede.
Supply & Fixing 6 Amps 2/3 pin socket two module complete all as specified and as directed.
Supply & Fixing modular multi socket outlet 16 Amps 3 Pin socket complete all as specified and as directed.
S&F PVC casing caping of size 20mm including cut to shape and size to match the existing conduits suitable for LT electric supply along with necessary fixing arrangements including disconnection and removing the unserviceable PVC casing caping complete.
All as per Item No 32 here in above but of size 25mm
S&F MCB DB, SPN, 6 way with 200 Amps rated bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed.
S&F MCB DB, SPN, 8 way with 200 Amps rated bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed.
S&F MCB DB, SPN, 12 way with 200 Amps rated bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed.
S&F MCB DB, TPN, 4 way with 200 Amps rated bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc. complete all as specified and as directed.
S&F MCB DB, TPN, 12 way with 200 Amps rated bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc. complete all as specified and as directed.
S&F MCB DB, TPN, 24 way with 200 Amps rated bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc. complete all as specified and as directed.
S&F MCB SP 6-32 Amps 230 volts 10 KA ISI marked complete all as specified and directed by Engg-in-Charge. Note: contractor shall be have deemed to have quoted rates for both B & C curve MCB SP
All as per Item No 40 here in above but of capacity MCB SPN 40 Amps B Curve.
All as per Item No 40 here in above but of capacity MCB SPN 63 Amps C Curve.
All as per Item No 40 here in above but of capacity MCB DP 63 Amps C Curve.
All as per Item No 40 here in above but of capacity MCB TPN 40 Amps
All as per Item No 40 here in above but of capacity MCB TPN 63 Amps
S&F Single pole and neutral enclosure with a two pin earth plug and socket complete controlled by one single pole MCB 20 Amps 240 Volts, including taking out unserviceable MCB plug and socket unit complete all as specified and as directed.
S&F in repair batten for LED tube light 1X18/20 watts LED, 230Volt energy efficient, industrial batton type, powder coated, CRC Sheet complete with all as accessories internally pre wired and including connecting up with three core twisted flexible copper conductor cable with suitable size Complete all as specified and as directed.
Supply and fixing in repair LED tube rod 1X18/20 watts (retrofit LED tube) energy saving, recess / surface mounted luminaire suitable for fix in the batten fitting 1x18W to 20W, complete all as specified and directed by Engineer in Charge.
S&F as in repair batten for LED tube light 1X9/10/12 watts LED, 230Volt energy efficient, industrial batton type, powder coated, CRC Sheet complete with all as accessories internally pre wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size Complete all as specified and as directed.
Supply and fixing in repair LED tube rod 1X9/10/12 watts (retrofit LED tube) energy saving, recess / surface mounted luminaire suitable for fix in the batten fitting 1x9/10W, complete all as specified and directed by Engineer in Charge.
Disconnection and removing the u/s light fitting from the false ceiling carefully and S&F LED (2X2) indirect light fitting Square shape 36 Watts 230 volts with internally pre-wired and including connecting up with three core twisted flexible copper conductor cable with suitable size compelte all as specified and directed.
Disconnection and removing the u/s light fitting from the Surface mountend ceiling carefully and S&F LED (2X2) indirect light fitting square shape 36Watts, 230 volts with internally pre-wired and including connecting up with three core twisted flexible copper conductor cable with suitable size compelte all as specified and directed.
Supply and fixing in repair Surface mounted LED (1X4) Panel indirect light fitting 40Watts, 230 volts with internally pre-wired and including connecting up with three core twisted flexible copper conductor cable with suitable size compelte all as specified and directed.
S&F Ceiling mounted Slim design LED recessed round Downlight with Superior light output and internal driver 18 Watts 230 volts with internally pre-wired and including connecting up with two core twisted flexible copper conductor cable with suitable size compelte all as specified and directed. MAKE :- Philips/Wipro/C&S/Crompton
Supply and fixing in repair Ceiling mounted Slim design LED recessed Square Downlight with Superior light output and internal driver 18 Watts 230 volts with internally pre-wired and including connecting up with two core twisted flexible copper conductor cable with suitable size compelte all as specified and directed.
S&F in repair LED light fitting 9W, 230 Volts internally pre wired bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor wire of suitable size complete all as specified and directed.
Supply and fixing in repair Flood Slim LED light output and internal driver 150 Watts, 230 volts with internally pre-wired and including connecting up with two core twisted flexible copper conductor cable with suitable size compelte all as specified and directed.
Supply and Fixing lamp holder, angular type, PVC/ polycarbonate with back plate of capacity 5 Amps 230 volts suitabel for general lighting system complete all as specified and as directed. Make : Anchor/Cona/Leader/Bajaj
S&F LED lamp/T lamp 9/10 watts complete all as specified and as directed.
Supply and fix in repair MCCB 3 pole 100 Amps 25 KA complete with and including suitable size of MS box with locking arrangement flushed in wall complete all as specified and as directed.
All as per Item No 60 here in above but of capacity MCCB 125Amp, 25KA
All as per Item No 60 here in above but of capacity MCCB 160Amp, 25KA
All as per Item No 60 here in above but of capacity MCCB 63Amp, 25KA
All as per Item No 60 here in above but of capacity MCCB 200Amp, 35KA
Supply and fix in repair MCCB 4 pole 160 Amps 35 KA complete with and including suitable size of MS box with locking arrangement flushed in wall complete all as specified and as directed.
All as per Item No 65 here in above but of capacity MCCB 200Amp, 25KA
All as per Item No 65 here in above but of capacity MCCB 250Amp, 25KA
All as per Item No 65 here in above but of capacity MCCB 125Amp, 25KA
M&L for earthing with GI earth plate electrode 60cm x 60cm x 6.0 mm thick burried directly in ground vertically to depth of not less than 2.25 mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to GI earth wire of 4.0 mm dia by means of bolts, nuts, washers of GI and provision of earth lead, GI protection pipe with 15mm light grade galvanized including necessary earth work in any type of soil, PCC 1:3:6 type CI (using 20mm graded stone aggregate) earth chamber and 1:2:4 type B1 RCC cover fitted with50mm thick with 6mm dia MS bars complete all as shown in SSR Pt - 1 electrical plate No 3. Note : Qoted rate deemed to include the cost or excavation and earth work PCC Chamber, funnel cover etc. complete all as specified and directed by Engg-In-Charge
Supply and fix in repair decorative Post top LED 40Watt for 360* indirect light with IP 65 protection 230 volts with internally pre-wired and including connecting up with two core twisted flexible copper conductor cable with suitable size compelte all as specified and directed.
Disconnection and removing the unserviceable Engine unit 250 KVA diesel engine carefully from the alternator and transporting the same to the work shop for finding of the defects and servicing/ over hauling of Cylinder Head, Injectors, Fuel Pump, Turbo charger, radiator and self starter including renewal of spares such as Piston with pin, Piston rings, Linners, CR bearings, Valves, Gaskets, O Rings, Injector sleeves, gland nuts, cooling nozzles, air filter, hose pipes, hose clips, oil deisel filter set, radiator coolent, Engine oil, water pump etc and refixing the engine after completion of repairs at work shop at its original position and coupled with the alternator and all other accessories testing and commissioning complete. Note : (1) Over hauling items and spares will be measured and paid separately under respective Sch 'A' Items.
Disconnection and removing the unserviceable alternator suitable for 250 KVA diesel engine Carefully from the engine and transporting the same to the work shop for rewinding the same with single strand fine enamel copper conductor of same guage weight and tons and keeping the windings into hot air oven till the moisture evaporates and fixing the same init original position duly painted the alternator after completion of repairs connecting the cables and all the accessories testing and commissioning complete. Note : (1) All the misc items such as impregranted paper, warnising, cotton tape and other misc items required for satisfactory completion of job deemed to be included in the unit rate quoted. (2). Bearings, Terminal block and coupling will be measured and paid separately under respective Sch 'A' Items. (3) The above repairs are considered to meeet the anticipated requirement if any and based on the site requirement the scope will be handed over to the Contractor.
Disconnection and removing the unserviceable Engine unit 62.5 KVA diesel engine carefully from the alternator and transporting the same to the work shop for finding of the defects and servicing/ over hauling of Cylinder Head, Injectors, Fuel Pump, Turbo charger, radiator and self starter including renewal of spares such as Piston with pin, Piston rings, Linners, CR bearings, Valves, Gaskets, O Rings, Injector sleeves, gland nuts, cooling nozzles, air filter, hose pipes, hose clips, oil deisel filter set, radiator coolent, Engine oil, water pump etc and refixing the engine after completion of repairs at work shop at its original position and coupled with the alternator and all other accessories testing and commissioning complete. Note : (1) Over hauling items and spares will be measured and paid separately under respective Sch 'A' Items.
Disconnection and removing the unserviceable alternator suitable for 62.5 KVA diesel engine Carefully from the engine and transporting the same to the work shop for rewinding the same with single strand fine enamel copper conductor of same guage weight and tons and keeping the windings into hot air oven till the moisture evaporates and fixing the same init original position duly painted the alternator after completion of repairs connecting the cables and all the accessories testing and commissioning complete. Note : (1) All the misc items such as impregranted paper, warnising, cotton tape and other misc items required for satisfactory completion of job deemed to be included in the unit rate quoted. (2). Bearings, Terminal block and coupling will be measured and paid separately under respective Sch 'A' Items. (3) The above repairs are considered to meeet the anticipated requirement if any and based on the site requirement the scope will be handed over to the Contractor.
Supply only element diesel filter with gasket as per exiting make and model for 62.5 /63KVA, capacity of DG set
All as per Item No 75 here in above but capacity of 250KVA
Supply only element oil filter with gasket as per exiting make and model for 62.5 /63KVA, capacity of DG set
All as per Item No 77 here in above but capacity of 250KVA
Supply only Corrosion Resistor filter with gasket as per exiting make and model and CR plate for 62.5KVA to 250 KVA capacity of DG set
Supply only element bypass filter with gasketas per exiting make and model for 62.5 KVA to 250 KVA capacity of DG set
Supply only inner and outer air cleaner element as per exiting make and model for 62.5 KVA to 250 KVA capacity of DG set
Replacement of AVR unit and supply , fixing, connecting and testing AVR unit suitable for DG set upto 62.5 KVA capacity Make Kirloskar/National/Universal
Replacement of AVR unit and supply , fixing, connecting and testing AVR unit as per existing make and model suitable for DG set of 250 KVA capacity. Make Kirloskar/National/ Universal.
Disconnecting and taking out the radiator of 62.5 KVA to 63 KVA 3-phase 50 HZ capacity of DG sets and carrying out to work shop, strip opening completer radiator assembly, cleaning of tubes with using de-scaling solution, including soldering / gas welding of leakage of tubes. Cutting the rusted portion of in let or out let tubes including gas welding of new MS water tubes assembling the complete radiator including replacement of gasket, nut bolts, and testing for making it leak proof including oiling/servicing of water cooling assembly , replacing unserviceable parts, re-assembling and fixing the same in position and testing the system complete all as specified and directed by Engineer-in-Charge.
All as per Item No 84 here in above but capacity of 250KVA 3-phase 50 HZ
Supply only rubber hose pipe set as per exiting make and model complete for 62.5 to 63 KVA DG set suitable for water cooling assembly of DG Set.
Supply only water pump repair kit as per exiting make and model complete for 250 KVA DG set suitable for water cooling assembly of DG Set.
Supply only impeller water pumpset as per exiting make and model complete for 62.5 to 63 KVA DG set suitable for water cooling assembly of DG Set.
Supply only lubrication oil 20 W- 40 grade for DG set. Make: Kirloskar oil/ SERVO OF IOC/HINDUSTAN PETROLEUM/BPCL/ CASTROL)
Replacement of asbestos ropes with 12mm dia heat and fire resistance of exhaust pipe of any capacity of DG Set complete all as specified and directed by Engineer in charge.
Disconnecting and taking out defective battery lead and supplying, fixing, connecting and testing battery lead (Heavy duty) PVC insulated with multi strand copper conductor single core of size 25 Sqmm one side fixed with clamp and other side fixed with brass battery terminal of heavy duty for 2 metre length with battery charging complete all as specified and directed Engineer in charge.
Supply and filling of inhibitor corrosion (Coolent) suitable for radiators of 62.5 KVA to 250 KVA capacity DG set complete all as specified and directed
M&L for replacement of unserviceable fuel suction & injector return hose pipe with clamps and banjo washers as per existing make and size suitable for 62.5 to 250 KVA 3 phase 50 HZ capacity of DG sets complete all as specified and directed.
Taking out water separator & under mentioned unserviceable parts from the DG sets of any capacity and supply and fixing of new Water separator & following parts as per exiting make and model:-
Oil temperature gauge 40°C to 120°C
Water temperature gauge 40°C to 120°C
Oil pressure gauge 0 to 7 kg/cm2
RPM and Hrs meter complete with chain
Fuel connector
Hump hose & bend
Neon lamp with assly complete
Ampere meter with lead
Ignition switch along with duplicate keys
Toggle switch
Water safety control
Oil safety control
Disconnecting and taking out the exhaust system of DG set of any capacity and carrying out cleaning of choked, carbonized exhaust pipe including exhaust .silencer with de-scaling solution, including soldering / gas welding of leakage of pipe. Cutting the rusted portion of pipes including gas welding of pipes assembling the complete exhaust assembly including replacement of gasket, metallic flexible pipe, nut bolts, and testing for making it leak proof and fixing the same in position and testing the system complete all as specified and directed by Engineer-in-Charge.
M&L for Cleaning of MS fuel tank of DG sets of various capacity by collecting the fuel in cleaned barrels and removing sludge deposited/accumulated inside the tank of and disposal of sludge at a distance not exceeding 100 metre and cleaning the tank with kerosene oil , replacement of fuel tank strainer and unserviceable fuel gauge with new PVC fuel level indicator or float gauge and refilling the collected fuel after filtration complete all as specified and directed.
Disconnecting and taking out of unserviceable turbo drain hose and supply and fixing new turbo drain as per existing make and model suitable for 62.5 KVA to 250 KVA DG sets with clips nuts and bolts complete all as specified and directed by Engineer-in-Charge.
Disconnecting and taking out of unserviceable fuel suction pipe and supply and fixing new PVC flexible pipe as per existing make and size from fuel tank to fuel filter of DG sets complete all as specified and directed by Engineer-in-Charge.
Disconnecting and taking out old unserviceable belts of the DG set and supply and fixing fan belt of size C-49 suitable for DG set engine operation complete all as specified and directed by Engineer-in-Charge. Make : Fenner/Gemini/Hilton
All as per Item No 113 here in above but size B-33
All as per Item No 113 here in above but size B-44
Disconnecting & taking out of existing AMF panel of any description and in any position, of 62.5 KVA to 250 KVA capacity DG set & opening of AMF Panel, checking AC/DC circuits and replacement of unserviceable control wiring with 1.5 Sqmm, single core, copper conductor, flexible, PVC insulated, unsheathed cable suitable upto 1100 volts confirming to IS-694, taking out, removing and replacement of unserviceable parts / spares / items, reassembling the panel & fixing the same in position and testing the AMF panel on full load after completion of repairs all as specified and directed by Engineer-in-Charge. Note : The quoted rates of the contractor are deemed to include for fixing the serviceable parts in position and replacement of unserviceable parts with new parts. The new replaced parts shall be measured and paid for separately under appropriate item of Sch `A’ as `supply only ‘ but quoted rates are inclusive of replacement of small/minor parts such as nuts, bolts, washers/lugs/gaskets etc. all as specified and directed by Engineer-in-Charge
Supply only the SMPS (Switch mode power supply) /Transformer /Rectifier of 12 Volts DC supply & following spares/parts/ components of AMF Panels repaired under Schedule `A’ item No 116 above here in before. Note : (i) Fixing & testing element of the following items is deemed to be included in the rates quoted by the contractor for respective Schedule `A’ item. (ii) Contractor shall have no claim on account of variation of quantities of following items or non execution of the item.SMPS (Switch mode power supply) /Transformer /Rectifier of 12 Volts DC supply
Electronic timer, type ET-100, suitable of 240 Volts, 50 Hz, AC supply, for 0 -10 seconds (ON delay). Make : L&T/PIC/Aditya Electronic
Electronic timer, suitable of 240 / 415 Volts, 50 Hz, AC supply, for 0-60 seconds (OFF delay). Make : L&T / PIC / Aditya Electronic
Ammeter 0-15 Amps, Electromechanical type suitable for existing CTs Make : AE/IMP/Meco / Simco/Rishab.
Voltmeter 0-30 Volts, Electromechanical type for measuring DC supply. Make : AE/IMP/Meco / Simco/Rishab
Bimetal overload relay type MNX with relay range 24 – 40 Amps suitable for 3 phase 415 volts, AC supply Make : L&T /Indoasion/Standard
Electronic DC timer suitable for 12 Volts DC supply, for 0-60 seconds. (on delay). Make : L&T / PIC / Aditya Electronic
Under voltage relay suitable for 3 phase 415 volts, AC supply Make : PIC / Aditya Electronic
Engine starting relay with sequence timer & Master timer suitable for 12 / 24 Volts DC supply. Make : PIC / Aditya Electronic
Indicating lamps neon type with holder for 12 / 24 volts DC supply (RYB) Make : L&T/BCH/SIEMEN
Electronic timer, suitable of 240 / 415 Volts, 50 Hz, AC supply, for 0-180 seconds (ON delay). Make : L&T / PIC / Aditya Electronic
Ammeter 0-200 Amp/ 0-150 Amps/ 0-100 Amps, Ectromechanical type suitable for existing CTs of class 1.0 Make : AE/IMP/Meco / Simco/Rishab
Voltmeter 0-50 Volts, Electromechanical type for measuring DC supply. Make : AE/IMP/Meco / Simco/Rishab
Voltmeter 0-500 Volts, Electromechanical type, for measuring AC supply Make : AE/IMP/Meco / Simco/Rishab
3 pole Power contactor current rating AC 3 of MNX 200 Amp, 3 phase 415 Volt. Make : C&S/siemens/L&T/Standard /Legrand
3 pole Power contactor current rating AC 3 of MNX 400 Amp, 3 phase 415 Volt Make : C&S/siemens/L&T/Standard /Legrand
PLA relay 12 volt DC 11 pin, 2 change over, cat part No 2C/O-MPC-12 D as per existing make and model.
HRC fuse for 415 volt,250 Amp rating DIN type
HRC fuse for 415 volt, 350 TO 400Amp rating DIN type.
Supply and replace self starter 12Volt DC suitable for DG set 62.5 Kva to 250 KVA make as approved by GE complete all as directed by engineer in charge.
Supply only of the shim fuel pump governor & following new parts as per existing make and model suitable for fuel injection pump assembly repaired under Schedule `A' item Note :- Fixing element of these items is included under the rates quoted by the contractor for Schedule `A' items
Kit injector barrel plunger
Gasket fuel pump
Gasket Governor set
Ball Bearing
Nozzles with copper washers
Gasket fuel pump
Screen filter
Ball check
Gasket Injector
Seal ‘O’ ring
Shaft fuel pump drive
Shaft tachometer drive
Bushing tachometer drive
Seal key way
Bearing thrust
Plug injector orifice
Screen filter
Seal dust
Turbo Charger Repairing Kit
Disconnection and removing the u/s lead acid batteries 12 volts 180 AH carefully from the 62.50KVA to 250 KVA DG Set and S&F new lead acid batteries 12 volts 180 AH suitable for DG Set 62.5 to 250 KVA including testing and commissioning complete suitable for DG Set 62.5KVA to 250KVA with copper lead.
Disconnection and removing the u/s fuel injection pump carefully from the 250 KVA DG Set and S&F new fuel injection pump unit suitable for DG Set 250 KVA Make: Greaves Model TBD4V12 including testing and commissioning complete
M&L for earthing complete with galvanized steel earth plate eleteode 600mmX600mmX6mm thick buried directly in ground Verticaly to a depath not less than 2.25mtr deep below normal ground level with top edge of earth plate at a depth of not less than 1.5mtr below normal ground level connected to galvanized iron strip 32mmX6mm by means of bolts, nuts, check nuts and washers made out of galvanized iron and GI earth strip protected by 40MM bore light grade GI Pipe as well as 20mm dia medium grade pipe 1.5mtr fixed with funnel and wire mesh as Specified and connected allas shown in electrical plate No 03 of SSR Part I including necessary earth work and excavation in any type of soil and PCC 1:2:4 type B-1 in chamber and 40mm thick 1:2:4 type B-1 cover slab with 6mm dia mield steel bars at 100mm center to center both way with 6mm dia MS hoks Complate all as Specified and as directed by Engineer in charge. NOTE :- The GI strip 32mmx6mm & 40mm bore light grade GI Pipe up to 7.5mtr deep to be included in the rate quoted by the Complated.
S&F Aluminium lugs for cable of size 25 to 50 Sqmm complate all as specified and as directed.
S&F Aluminium lugs for cable of size 70 Sqmm complate all as specified and as directed.
S&F Aluminium lugs for cable of size 95 Sqmm complate all as specified and as directed.
S&F Indoor Type LT panel board outdoor type double door surface mounted made out of 3mm thick CRCA sheet Steel for load bearing and 2 mm thick for non load bearing and portions mounted on frame angle iron fo suitable size weather proof/veermin proof shutter type with locking arrangment of cubical type prewired with aluminium extendable busbar 300 Amps for 03 phases and aluminium busbar 300 Amps for neutral including suitable CTs etc and powder coated paint, agle iron frame base of size LT Panel (100CMX120CMX45CM) with provision for fixing of MCCB's mounting arrangement shall be adjustabile type,Comprising of following complate all as specified and in accordance with IEC 60529 with IP 65. Make of the Panel board confirming to CPRI specifications only. (i) MCCB 160 Amps, Breaking capacity 35 KA, 4 pole (Change over switch -1 No In coming) MAKE: Indoasian (ii) MCCB 125 Amps,Breaking capacity 25 KA, 4 pole -1 Nos (outgoing) MAKE: Indoasian (iii) MCCB 63 Amps,Breaking capacity 25 KA, four pole -2 Nos (outgoing) MAKE: Indoasian (iv) 4 Nos Aluminium Bus bar of Capacity 300 Amps for Phase & Neutral (v) LED/Neon indicator bulb in RYB Colour - 1 Set. (vi) Cable gland with necessary end terminations for incoming and out going cables complete (vii) Indication Lamp set of 3 for RYB & N (viii) Digital Ammeter with CTs Units - 01 Set (ix) Digital Voltmeter - 01 Set
Supply, Installation, Commissioning ant testing of Elecrical control LT Pannel indoor totally enclosed,1100 volts, 50 HZ AC supply, 3 Phase factory made fully compartmentalised made out of 3 mm thick CRCA sheet steel for load bearing and 2 mm thick for non load bearing and portions,complete with powder coated front side openable, front side with double door shutter with locking Arrangement, Wall mounted making necessary cable connection with cable Thimble, Aluminium busbar of capacity 400Amp, MCCB's Connection shall be with Aluminium bus strip of suitable rating from main busbar, LT Panel size (100CMX120CMX45CM) MCCB's mounting arrangement shall be adjustable type,Comprising of following complete all as specified. Make of the Panel board confirming to CPRI specifications only. (i) MCCB 250 Amps, Breaking capacity 35 KA, 4 pole -1 No (In coming) Make: legrand (ii) 4 Nos Aluminium Bus bar of Capacity 250 Amps for Phase & Neutral (iii) MCB SP 6-32 Amp - 48 N0s (out going) Make - legrand (iv) LED/Neon indicator bulb in RYB Colour - 1 Set. (v) Cable gland with necessary end terminations for incoming and out going cables complete (vi) Indication Lamp set of 3 for RYB & N (vii) Digital Ameter and rotery with CTs Units - 01 Set (viii) Digital Voltmeter and rotery - 01 Set
Supplying, laying, jointing and testing cable XLPE insulated IS 7098 (Part-I) -1988 marked, screened, PVC sheathed, armoured electric power cable (heavy duty) with aluminium conductor for working voltage upto and including 1100 volts, cross sectional area 3.5 core 70 sqmm laid in trenches/fixed on pole/wall/passed through pipe complete all as specified and directed
All as per Item No 168 herein above but cable size of 3.5 core 95 sqmm
LONGIA ENGINEERS (BID ID -3099323)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .