Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.3 CrAccepted-AOC | ₹4.3 Cr | L1 | Accepted-AOC Since 1st lowest |
| 2 | L2₹5.1 Cr+₹79.8 L (18.5%)Rejected-Finance BLDG NO 03 SF 3 SF 4 TECHNO CIDADE CHOGM ROAD ALTO PORVORIM BARDEZ GOA | NORTH GOA | GOA | 403524 | ₹5.1 Cr+₹79.8 L (18.5%) | L2 | Rejected-Finance 2nd lowest |
Tender Value
₹5.7 Cr
EMD Value
₹11.4 L
Closing Date
21 Mar 2022, 5:30 pmClosed
Chief Electrical Engineer
O/o of the Chief Electrical Engineer, 5 th Floor, Contract Service Cell, Vidyut bhavan, Panaji, North Goa, 403001
Work of providing smart street lighting for the proposed roads and universal path ways in the area befalling under CCP at the request of IPSDCL
2022_ED_3082_1
TENDER NO-65(21-22)
Open Tender
Electrical Works
Works
180 days
Panaji Goa
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,500
₹11.4 L
30 May 2022
12 Mar 2022
23 Mar 2022
14 Mar 2022
21 Mar 2022
14 Mar 2022
Amount
COST OF MATERIAL (I)
Supply of HDGI 8 mtrs long Octagonal pole made up of 4mm HDGI plate,Cable entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang GI pipe of 1 mtr with an angle of 15 degree for 8 mtrs long Octagonal pole
Supply of 120W ± 10 % and 1-10V Analogue Dimmable driver withTop Maintainable LED Street Light luminaire. System efficacy of more than 130 lm/W. LED Street Light shall be made up of Die Cast aluminium housing suitable to mounted on 40-60 mm OD bracket arm. Luminaire shall have two separate compartments for LEDs and driver and both compartments should be hermitically sealed to achieve IP 66 ingress protection. Optical compartment shall be provided with polycarbonate cover with lens to withstand IK 10 impact rating, while control gear shall be provided with die cast aluminium cover for safety. LM 80-08 compliant, LEDs from approved makes should be provided. LEDs used in the product shall comply with EN 62471 for Photo-biological safety and certificate for the same from manufacturer shall be provided for Risk Group 2 maximum. Luminaire manufacturer shall produce certificate of association with LED manufacturer for minimum 5 year. LEDs shall be of Ceramic Package with 1W to 5W capacity and shall be driver at 90% or lower wattage than maximum rated. LEDs used shall have maximum allowed junction temperature of 150 Deg C with actual operating junction temperature not more than 100 Deg C at an ambient temperature of 35 Deg C. The LENS used shall have optical grade Polycarbonate to provide street light distribution for Uniform lighting. LED optical lens should be properly fixed to 1.6mm thick MCPCB and should not be only fixed by glue. LED optical lens shall have temperature withstand capacity of 125 Deg C and Transmissivity of more than 90%.The LED shall be compliant with LM80-08 standard with Useful L70 life of 50000 Hrs. tested at maximum current and at 105 Deg C case temperature (Complete LM 80 test report for LED should be submitted for 10000 hrs. of testing). The LEDs used in Street Light should be MacAdam Step 5 standard Rated LED with CCT of 5700 K and CRI of Minimum 70. Maximum permissible driving current of LEDs are from 0.15A to 2A. Actual Driving Current of LEDs shall be less than 1000mA for life long reliability. LED Driver should be BIS Registered and shall be Isolated type, Constant Current topology driver in metal enclosure with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage – 240V) with 4KV internal surge protection in both Common Mode and Differential Mode. LED Driver shall be potted type. Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. LED driver shall have output short circuit & over voltage withstanding protection inbuilt. Luminaire shall be external SPD of 10KV. Compatibility report of SPD and Driver shall be submitted during inspection. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
Supply of HDGI 6 mtrs long Octagonal pole made up of 4mm HDGI plate, pole entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang HDGI pipe of 1 mtr with an angle of 15 degree 6 mtrs long Octagonal pole
Supply of 80W ± 10 % and 1-10V Analogue Dimmable driver withTop Maintainable LED Street Light luminaire. System efficacy of more than 130 lm/W. LED Street Light shall be made up of Die Cast aluminium housing suitable to mounted on 40-60 mm OD bracket arm. Luminaire shall have two separate compartments for LEDs and driver and both compartments should be hermitically sealed to achieve IP 66 ingress protection. Optical compartment shall be provided with polycarbonate cover with lens to withstand IK 10 impact rating, while control gear shall be provided with die cast aluminium cover for safety. LM 80-08 compliant, LEDs from approved makes should be provided. LEDs used in the product shall comply with EN 62471 for Photo-biological safety and certificate for the same from manufacturer shall be provided for Risk Group 2 maximum. Luminaire manufacturer shall produce certificate of association with LED manufacturer for minimum 5 year. LEDs shall be of EMC /Ceramic Package with 1W to 5W capacity and shall be driver at 90% or lower wattage than maximum rated. LEDs used shall have maximum allowed junction temperature of 150 Deg C with actual operating junction temperature not more than 100 Deg C at an ambient temperature of 35 Deg C. The LENS used shall have optical grade Polycarbonate to provide street light distribution for Uniform lighting. LED optical lens should be properly fixed to 1.6mm thick MCPCB and should not be only fixed by glue. LED optical lens shall have temperature withstand capacity of 125 Deg C and Transmissivity of more than 90%.The LED shall be compliant with LM80-08 standard with Useful L70 life of 50000 Hrs. tested at maximum current and at 105 Deg C case temperature (Complete LM 80 test report for LED should be submitted for 10000 hrs. of testing). The LEDs used in Street Light should be MacAdam Step 5 standard Rated LED with CCT of 5700 K and CRI of Minimum 70. Maximum permissible driving current of LEDs are from 0.15A to 1A. Actual Driving Current of LEDs shall be less than 1000mA for life long reliability. LED Driver should be BIS Registered and shall be Isolated type, Constant Current topology driver in metal enclosure with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage – 240V) with 4KV internal surge protection in both Common Mode and Differential Mode. LED Driver shall be potted type. Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. LED driver shall have output short circuit & over voltage withstanding protection inbuilt. Luminaire shall be external SPD of 10KV. Compatibility report of SPD and Driver shall be submitted during inspection. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
Supply of HDGI 4 mtrs long Octagonal pole made up of 4mm HDGI plate, cable entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang with 0.3 mtr pole bracket
Supply 40 W ± 10 % and 1-10V Analogue Dimmable driver withTop Maintainable LED Street Light luminaire. System efficacy of more than 130 lm/W. LED Street Light shall be made up of Die Cast aluminium housing suitable to mounted on 40-60 mm OD bracket arm. Luminaire shall have two separate compartments for LEDs and driver and both compartments should be hermitically sealed to achieve IP 66 ingress protection. Optical compartment shall be provided with polycarbonate cover with lens to withstand IK 10 impact rating, while control gear shall be provided with die cast aluminium cover for safety. LM 80-08 compliant, LEDs from approved makes should be provided. LEDs used in the product shall comply with EN 62471 for Photo-biological safety and certificate for the same from manufacturer shall be provided for Risk Group 2 maximum. Luminaire manufacturer shall produce certificate of association with LED manufacturer for minimum 5 year. LEDs shall be of EMC /Ceramic Package with 1W to 5W capacity and shall be driver at 90% or lower wattage than maximum rated. LEDs used shall have maximum allowed junction temperature of 150 Deg C with actual operating junction temperature not more than 100 Deg C at an ambient temperature of 35 Deg C. The LENS used shall have optical grade Polycarbonate to provide street light distribution for Uniform lighting. LED optical lens should be properly fixed to 1.6mm thick MCPCB and should not be only fixed by glue. LED optical lens shall have temperature withstand capacity of 125 Deg C and Transmissivity of more than 90%.The LED shall be compliant with LM80-08 standard with Useful L70 life of 50000 Hrs. tested at maximum current and at 105 Deg C case temperature (Complete LM 80 test report for LED should be submitted for 10000 hrs. of testing). The LEDs used in Street Light should be MacAdam Step 5 standard Rated LED with CCT of 5700 K and CRI of Minimum 70. Maximum permissible driving current of LEDs are from 0.15A to 1A. Actual Driving Current of LEDs shall be less than 1000mA for life long reliability. LED Driver should be BIS Registered and shall be Isolated type, Constant Current topology driver in metal enclosure with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage – 240V) with 4KV internal surge protection in both Common Mode and Differential Mode. LED Driver shall be potted type. Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. LED driver shall have output short circuit & over voltage withstanding protection inbuilt. Luminaire shall be external SPD of 10KV. Compatibility report of SPD and Driver shall be submitted during inspection. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
CCMS System: a) Smart Feeder Panel IP 54 b) Switching Point controller / CCMS Controller, astronomical timer, wireless communication,ineternal memory, RS485/RS232 series comunication, CCMS can be remotely configured from server, Street light gateway supports RS485 Modibus communication and HTTPS support for wireless comunivcation with server using SIM based GPRS connection c) Energy Meter d) Local / Local Managed application software e) Luminaire NEMA contriller - FEATURES PROPOSED in SYSTEM =>individual lamp level control with individual dimming facilty =>Turn ON/OFF lights as per predifined schedule =>Control of lights as per astrounomical time clock for sunset and sunrise times =>Dimming of light in non peakk traffic hours =>24 x 7 online monitoring => failure reporting => enery reports and measurement of base load
Cement concrete foundation for poles including Excavation, centering, shuttering, foundation bolts (i.e. 4 nosJ type bolt -bolts M 20 x 750 mm) and refilling of surrounding empty pit for 8 mtr for octagona,l classic, conical pole pole
Cement concrete foundation for poles including Excavation, centering, shuttering, foundation bolts (i.e. 4 nosJ type bolt- bolts M 16 x 600 mm) and refilling of surrounding empty pit for 6 mtr octagonal and classic pole
Cement concrete foundation for poles including Excavation, centering, shuttering, foundation bolts (i.e. 4 nosJ type bolt -bolts M 16 x 600 mm) and refilling of surrounding empty pit for 4 mtr octagonal and classic pole
Earthing as per IS 3043/1966. including supply, erection, testing & comm. of HDGI pipe 8 ft long 40 mm dia class B, fabricated & perforated confirming to I.E. rules of 1956 including alternate layers 30cm thick of charcoal, salt & earth (charcoal & salt --10Kgs each per pit) inclusive of earthwork excavation of size 0.50x0.50x2.5m, backfilling & spreading of excavated earth evenly toget required earth resistance as per enclosed specification
HDGI strip 25 *5 mm with proper welding wherever require and painting with red oxide paint at the portion of welding, drilling cutting etc
Supply 2 x 3 core 1.5 sqmm copper flexible wire from junction box upto the fixtures .
Supply PVC insulated PVC sheathed with aluminium conductor of 1.1 KV grade 4 core armoured cable direct in ground as required and directed by engineer in-charge CABLE OF SIZE 25 sq.mm including keeping loops near poles & taking cable upto the junction boxes for new and existing poles.
Supply PVC insulated PVC sheathed with aluminium conductor of 1.1 KV grade 3.5core armoured cable direct in ground as required and directed by engineer in-charge CABLE OF SIZE 95 sq.mm including keeping loops & taking cable upto the control panel.
Providing and laying of precast RCC protective cover of size 0.5 mts. X 0.25 width and 50 mm. thick of breaking load of 135 Kg. by riddled earth/sand up to a depth of 0.15 mts. (0.1 mts. above the top of the uppermost cable confirming to appendix C-1 and clause No. 9.2 of IS 1255-1967.
Disposal of surplus excavated soil/material by mechanical transportaion including loading and unloading stacking/levelling as directed within a distance of 2500 mts.
Supplying and laying of sand (0.35x 0.1 x800)
RCC Hume Pipe of 150 mm Dia
HDGI pipe 100 mm
Aluminium lugs 25 sqmm
COST OF ERECTION
Erection of HDGI 8 mtrs long Octagonal pole made up of 4mm HDGI plate,Cable entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang HDGI pipe of 1 mtr with an angle of 15 degree for 8 mtrs long Octagonal pole
Erection of 120W ± 10 % and 1-10V Analogue Dimmable driver withTop Maintainable LED Street Light luminaire. System efficacy of more than 130 lm/W. LED Street Light shall be made up of Die Cast aluminium housing suitable to mounted on 40-60 mm OD bracket arm. Luminaire shall have two separate compartments for LEDs and driver and both compartments should be hermitically sealed to achieve IP 66 ingress protection. Optical compartment shall be provided with polycarbonate cover with lens to withstand IK 10 impact rating, while control gear shall be provided with die cast aluminium cover for safety. LM 80-08 compliant, LEDs from approved makes should be provided. LEDs used in the product shall comply with EN 62471 for Photo-biological safety and certificate for the same from manufacturer shall be provided for Risk Group 2 maximum. Luminaire manufacturer shall produce certificate of association with LED manufacturer for minimum 5 year. LEDs shall be of Ceramic Package with 1W to 5W capacity and shall be driver at 90% or lower wattage than maximum rated. LEDs used shall have maximum allowed junction temperature of 150 Deg C with actual operating junction temperature not more than 100 Deg C at an ambient temperature of 35 Deg C. The LENS used shall have optical grade Polycarbonate to provide street light distribution for Uniform lighting. LED optical lens should be properly fixed to 1.6mm thick MCPCB and should not be only fixed by glue. LED optical lens shall have temperature withstand capacity of 125 Deg C and Transmissivity of more than 90%.The LED shall be compliant with LM80-08 standard with Useful L70 life of 50000 Hrs. tested at maximum current and at 105 Deg C case temperature (Complete LM 80 test report for LED should be submitted for 10000 hrs. of testing). The LEDs used in Street Light should be MacAdam Step 5 standard Rated LED with CCT of 5700 K and CRI of Minimum 70. Maximum permissible driving current of LEDs are from 0.15A to 2A. Actual Driving Current of LEDs shall be less than 1000mA for life long reliability. LED Driver should be BIS Registered and shall be Isolated type, Constant Current topology driver in metal enclosure with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage – 240V) with 4KV internal surge protection in both Common Mode and Differential Mode. LED Driver shall be potted type. Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. LED driver shall have output short circuit & over voltage withstanding protection inbuilt. Luminaire shall be external SPD of 10KV. Compatibility report of SPD and Driver shall be submitted during inspection. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
Erection of HDGI 6 mtrs long Octagonal pole made up of 4mm HDGI plate, pole entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang HDGI pipe of 1 mtr with an angle of 15 degree 6 mtrs long Octagonal pole
Erection of 80W ± 10 % and 1-10V Analogue Dimmable driver withTop Maintainable LED Street Light luminaire. System efficacy of more than 130 lm/W. LED Street Light shall be made up of Die Cast aluminium housing suitable to mounted on 40-60 mm OD bracket arm. Luminaire shall have two separate compartments for LEDs and driver and both compartments should be hermitically sealed to achieve IP 66 ingress protection. Optical compartment shall be provided with polycarbonate cover with lens to withstand IK 10 impact rating, while control gear shall be provided with die cast aluminium cover for safety. LM 80-08 compliant, LEDs from approved makes should be provided. LEDs used in the product shall comply with EN 62471 for Photo-biological safety and certificate for the same from manufacturer shall be provided for Risk Group 2 maximum. Luminaire manufacturer shall produce certificate of association with LED manufacturer for minimum 5 year. LEDs shall be of EMC /Ceramic Package with 1W to 5W capacity and shall be driver at 90% or lower wattage than maximum rated. LEDs used shall have maximum allowed junction temperature of 150 Deg C with actual operating junction temperature not more than 100 Deg C at an ambient temperature of 35 Deg C. The LENS used shall have optical grade Polycarbonate to provide street light distribution for Uniform lighting. LED optical lens should be properly fixed to 1.6mm thick MCPCB and should not be only fixed by glue. LED optical lens shall have temperature withstand capacity of 125 Deg C and Transmissivity of more than 90%.The LED shall be compliant with LM80-08 standard with Useful L70 life of 50000 Hrs. tested at maximum current and at 105 Deg C case temperature (Complete LM 80 test report for LED should be submitted for 10000 hrs. of testing). The LEDs used in Street Light should be MacAdam Step 5 standard Rated LED with CCT of 5700 K and CRI of Minimum 70. Maximum permissible driving current of LEDs are from 0.15A to 1A. Actual Driving Current of LEDs shall be less than 1000mA for life long reliability. LED Driver should be BIS Registered and shall be Isolated type, Constant Current topology driver in metal enclosure with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage – 240V) with 4KV internal surge protection in both Common Mode and Differential Mode. LED Driver shall be potted type. Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. LED driver shall have output short circuit & over voltage withstanding protection inbuilt. Luminaire shall be external SPD of 10KV. Compatibility report of SPD and Driver shall be submitted during inspection. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
Erection of HDGI 4 mtrs long Octagonal pole made up of 4mm HDGI plate, cable entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang with 0.3 mtr pole bracket
Erection of 40 W ± 10 % and 1-10V Analogue Dimmable driver withTop Maintainable LED Street Light luminaire. System efficacy of more than 130 lm/W. LED Street Light shall be made up of Die Cast aluminium housing suitable to mounted on 40-60 mm OD bracket arm. Luminaire shall have two separate compartments for LEDs and driver and both compartments should be hermitically sealed to achieve IP 66 ingress protection. Optical compartment shall be provided with polycarbonate cover with lens to withstand IK 10 impact rating, while control gear shall be provided with die cast aluminium cover for safety. LM 80-08 compliant, LEDs from approved makes should be provided. LEDs used in the product shall comply with EN 62471 for Photo-biological safety and certificate for the same from manufacturer shall be provided for Risk Group 2 maximum. Luminaire manufacturer shall produce certificate of association with LED manufacturer for minimum 5 year. LEDs shall be of EMC /Ceramic Package with 1W to 5W capacity and shall be driver at 90% or lower wattage than maximum rated. LEDs used shall have maximum allowed junction temperature of 150 Deg C with actual operating junction temperature not more than 100 Deg C at an ambient temperature of 35 Deg C. The LENS used shall have optical grade Polycarbonate to provide street light distribution for Uniform lighting. LED optical lens should be properly fixed to 1.6mm thick MCPCB and should not be only fixed by glue. LED optical lens shall have temperature withstand capacity of 125 Deg C and Transmissivity of more than 90%.The LED shall be compliant with LM80-08 standard with Useful L70 life of 50000 Hrs. tested at maximum current and at 105 Deg C case temperature (Complete LM 80 test report for LED should be submitted for 10000 hrs. of testing). The LEDs used in Street Light should be MacAdam Step 5 standard Rated LED with CCT of 5700 K and CRI of Minimum 70. Maximum permissible driving current of LEDs are from 0.15A to 1A. Actual Driving Current of LEDs shall be less than 1000mA for life long reliability. LED Driver should be BIS Registered and shall be Isolated type, Constant Current topology driver in metal enclosure with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage – 240V) with 4KV internal surge protection in both Common Mode and Differential Mode. LED Driver shall be potted type. Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. LED driver shall have output short circuit & over voltage withstanding protection inbuilt. Luminaire shall be external SPD of 10KV. Compatibility report of SPD and Driver shall be submitted during inspection. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
CCMS System: a) Smart Feeder Panel IP 54 b) Switching Point controller / CCMS Controller, astronomical timer, wireless communication, ineternal memory, RS485/RS232 series comunication, CCMS can be remotely configured from server, Street light gateway supports RS485 Modibus communication and HTTPS support for wireless comunivcation with server using SIM based GPRS connection c) Energy Meter d) Local / Local Managed application software e) Luminaire NEMA contriller - FEATURES PROPOSED in SYSTEM =>individual lamp level control with individual dimming facilty =>Turn ON/OFF lights as per predifined schedule =>Control of lights as per astrounomical time clock for sunset and sunrise times =>Dimming of light in non peakk traffic hours =>24 x 7 online monitoring => failure reporting => enery reports and measurement of base load
Earthing complete with 40mm GI Pipe, 2.5 mts long alongwith 20 kgs each salt, charcoal complete
HDGI strip 25 *5 mm with proper welding wherever require and painting with red oxide paint at the portion of welding, drilling cutting etc
Erection 2 x 3 core 1.5 sqmm copper flexible wire from junction box upto the fixtures .
Erection PVC insulated PVC sheathed with aluminium conductor of 1.1 KV grade 4 core armoured cable direct in ground as required and directed by engineer in-charge CABLE OF SIZE 25 sq.mm including keeping loops near poles & taking cable upto the junction boxes for new and existing poles.
Erection PVC insulated PVC sheathed with aluminium conductor of 1.1 KV grade 3.5core armoured cable direct in ground as required and directed by engineer in-charge CABLE OF SIZE 95 sq.mm including keeping loops & taking cable upto the control panel.
Earthwork excavation including opening of roads, chamber/pave-ments and soling, ramming, levelling of bottoms, making bottom freed from stones including removing out the excavated soil/materials as directed within a lead of 200 mts. (0.6 x 0.35 x800 )
Filling up of available excavated earth (excluding rock/stones) in trenches, plinth, sides, foundation etc. in layer not exceeding 0.2 mt. depth con-solidating each deposited layer by ramming and watering lead upto 200 mts. (0.6 x 0.35 x4000)
RCC Hume Pipe of 150 mm Dia
HDGI pipe 100 mm
Aluminium lugs 25 sqmm
Removing of existing tubular pole and transporting the same with vehicle to Margao Central store under supervision of GED
Removing of existing 130 W LED fixtures
Removing of existing 30 W LED fixtures
Removing of existing CCMS Panels
COST OF MATERIAL (II)
Supply of HDGI 8 mtrs long Octagonal pole made up of 4mm HDGI plate,Cable entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang HDGI pipe of 1 mtr with an angle of 15 degree for 8 mtrs long Octagonal pole
Supply of 80W ± 10 % and 1-10V Analogue Dimmable driver withTop Maintainable LED Street Light luminaire. System efficacy of more than 130 lm/W. LED Street Light shall be made up of Die Cast aluminium housing suitable to mounted on 40-60 mm OD bracket arm. Luminaire shall have two separate compartments for LEDs and driver and both compartments should be hermitically sealed to achieve IP 66 ingress protection. Optical compartment shall be provided with polycarbonate cover with lens to withstand IK 10 impact rating, while control gear shall be provided with die cast aluminium cover for safety. LM 80-08 compliant, LEDs from approved makes should be provided. LEDs used in the product shall comply with EN 62471 for Photo-biological safety and certificate for the same from manufacturer shall be provided for Risk Group 2 maximum. Luminaire manufacturer shall produce certificate of association with LED manufacturer for minimum 5 year. LEDs shall be of EMC /Ceramic Package with 1W to 5W capacity and shall be driver at 90% or lower wattage than maximum rated. LEDs used shall have maximum allowed junction temperature of 150 Deg C with actual operating junction temperature not more than 100 Deg C at an ambient temperature of 35 Deg C. The LENS used shall have optical grade Polycarbonate to provide street light distribution for Uniform lighting. LED optical lens should be properly fixed to 1.6mm thick MCPCB and should not be only fixed by glue. LED optical lens shall have temperature withstand capacity of 125 Deg C and Transmissivity of more than 90%.The LED shall be compliant with LM80-08 standard with Useful L70 life of 50000 Hrs. tested at maximum current and at 105 Deg C case temperature (Complete LM 80 test report for LED should be submitted for 10000 hrs. of testing). The LEDs used in Street Light should be MacAdam Step 5 standard Rated LED with CCT of 5700 K and CRI of Minimum 70. Maximum permissible driving current of LEDs are from 0.15A to 1A. Actual Driving Current of LEDs shall be less than 1000mA for life long reliability. LED Driver should be BIS Registered and shall be Isolated type, Constant Current topology driver in metal enclosure with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage – 240V) with 4KV internal surge protection in both Common Mode and Differential Mode. LED Driver shall be potted type. Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. LED driver shall have output short circuit & over voltage withstanding protection inbuilt. Luminaire shall be external SPD of 10KV. Compatibility report of SPD and Driver shall be submitted during inspection. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
Supply of HDGI 4 mtrs long Octagonal pole made up of 4mm HDGI plate, cable entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang with 0.3 mtr pole bracket
Supply 40 W ± 10 % and 1-10V Analogue Dimmable driver withTop Maintainable LED Street Light luminaire. System efficacy of more than 130 lm/W. LED Street Light shall be made up of Die Cast aluminium housing suitable to mounted on 40-60 mm OD bracket arm. Luminaire shall have two separate compartments for LEDs and driver and both compartments should be hermitically sealed to achieve IP 66 ingress protection. Optical compartment shall be provided with polycarbonate cover with lens to withstand IK 10 impact rating, while control gear shall be provided with die cast aluminium cover for safety. LM 80-08 compliant, LEDs from approved makes should be provided. LEDs used in the product shall comply with EN 62471 for Photo-biological safety and certificate for the same from manufacturer shall be provided for Risk Group 2 maximum. Luminaire manufacturer shall produce certificate of association with LED manufacturer for minimum 5 year. LEDs shall be of EMC /Ceramic Package with 1W to 5W capacity and shall be driver at 90% or lower wattage than maximum rated. LEDs used shall have maximum allowed junction temperature of 150 Deg C with actual operating junction temperature not more than 100 Deg C at an ambient temperature of 35 Deg C. The LENS used shall have optical grade Polycarbonate to provide street light distribution for Uniform lighting. LED optical lens should be properly fixed to 1.6mm thick MCPCB and should not be only fixed by glue. LED optical lens shall have temperature withstand capacity of 125 Deg C and Transmissivity of more than 90%.The LED shall be compliant with LM80-08 standard with Useful L70 life of 50000 Hrs. tested at maximum current and at 105 Deg C case temperature (Complete LM 80 test report for LED should be submitted for 10000 hrs. of testing). The LEDs used in Street Light should be MacAdam Step 5 standard Rated LED with CCT of 5700 K and CRI of Minimum 70. Maximum permissible driving current of LEDs are from 0.15A to 1A. Actual Driving Current of LEDs shall be less than 1000mA for life long reliability. LED Driver should be BIS Registered and shall be Isolated type, Constant Current topology driver in metal enclosure with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage – 240V) with 4KV internal surge protection in both Common Mode and Differential Mode. LED Driver shall be potted type. Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. LED driver shall have output short circuit & over voltage withstanding protection inbuilt. Luminaire shall be external SPD of 10KV. Compatibility report of SPD and Driver shall be submitted during inspection. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
CCMS System a) Smart Feeder Panel IP 54 b) Switching Point controller / CCMS Controller, astronomical timer, wireless communication,ineternal memory, RS485/RS232 series comunication, CCMS can be remotely configured from server, Street light gateway supports RS485 Modibus communication and HTTPS support for wireless comunivcation with server using SIM based GPRS connection c) Energy Meter d) Local / Local Managed application software e) Luminaire NEMA contriller FEATURES PROPOSED in SYSTEM =>individual lamp level control with individual dimming facilty =>Turn ON/OFF lights as per predifined schedule =>Control of lights as per astrounomical time clock for sunset and sunrise times =>Dimming of light in non peakk traffic hours =>24 x 7 online monitoring => failure reporting => enery reports and measurement of base load
Cement concrete foundation for poles including Excavation, centering, shuttering, foundation bolts (i.e. 4 nosJ type bolt -bolts M 20 x 750 mm) and refilling of surrounding empty pit for 8 mtr for octagona,l classic, conical pole pole
Cement concrete foundation for poles including Excavation, centering, shuttering, foundation bolts (i.e. 4 nosJ type bolt -bolts M 16 x 600 mm) and refilling of surrounding empty pit for 4 mtr octagonal and classic pole
Earthing as per IS 3043/1966. including supply, erection, testing & comm. of HDGI pipe 8 ft long 40 mm dia class B, fabricated & perforated confirming to I.E. rules of 1956 including alternate layers 30cm thick of charcoal, salt & earth (charcoal & salt --10Kgs each per pit) inclusive of earthwork excavation of size 0.50x0.50x2.5m, backfilling & spreading of excavated earth evenly toget required earth resistance as per enclosed specification
HDG strip 25 *5 mm with proper welding wherever require and painting with red oxide paint at the portion of welding, drilling cutting etc
Supply of 2 x 3 core 1.5 sqmm copper flexible wire from junction box upto the fixtures .
Supply PVC insulated PVC sheathed with aluminium conductor of 1.1 KV grade 4 core armoured cable direct in ground as required and directed by engineer in-charge CABLE OF SIZE 25 sq.mm including keeping loops near poles & taking cable upto the junction boxes for new and existing poles.
Supply of PVC insulated PVC sheathed with aluminium conductor of 1.1 KV grade 3.5core armoured cable direct in ground as required and directed by engineer in-charge CABLE OF SIZE 95 sq.mm including keeping loops & taking cable upto the control panel.
Providing and laying of precast RCC protective cover of size 0.5 mts. X 0.25 width and 50 mm. thick of breaking load of 135 Kg. by riddled earth/sand up to a depth of 0.15 mts. (0.1 mts. above the top of the uppermost cable confirming to appendix C-1 and clause No. 9.2 of IS 1255-1967.
Disposal of surplus excavated soil/material by mechanical transportaion including loading and unloading stacking/levelling as directed within a distance of 2500 mts.
Supplying and laying of sand (0.35x 0.1 x400)
RCC Hume Pipe of 150 mm Dia
HDGI pipe 100 mm
Aluminium lugs 25 sqmm
COST OF ERECTION
Erection of HDGI 8 mtrs long Octagonal pole made up of 4mm HDGI plate,Cable entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang HDGI pipe of 1 mtr with an angle of 15 degree for 8 mtrs long Octagonal pole
Erection of 80W ± 10 % and 1-10V Analogue Dimmable driver withTop Maintainable LED Street Light luminaire. System efficacy of more than 130 lm/W. LED Street Light shall be made up of Die Cast aluminium housing suitable to mounted on 40-60 mm OD bracket arm. Luminaire shall have two separate compartments for LEDs and driver and both compartments should be hermitically sealed to achieve IP 66 ingress protection. Optical compartment shall be provided with polycarbonate cover with lens to withstand IK 10 impact rating, while control gear shall be provided with die cast aluminium cover for safety. LM 80-08 compliant, LEDs from approved makes should be provided. LEDs used in the product shall comply with EN 62471 for Photo-biological safety and certificate for the same from manufacturer shall be provided for Risk Group 2 maximum. Luminaire manufacturer shall produce certificate of association with LED manufacturer for minimum 5 year. LEDs shall be of EMC /Ceramic Package with 1W to 5W capacity and shall be driver at 90% or lower wattage than maximum rated. LEDs used shall have maximum allowed junction temperature of 150 Deg C with actual operating junction temperature not more than 100 Deg C at an ambient temperature of 35 Deg C. The LENS used shall have optical grade Polycarbonate to provide street light distribution for Uniform lighting. LED optical lens should be properly fixed to 1.6mm thick MCPCB and should not be only fixed by glue. LED optical lens shall have temperature withstand capacity of 125 Deg C and Transmissivity of more than 90%.The LED shall be compliant with LM80-08 standard with Useful L70 life of 50000 Hrs. tested at maximum current and at 105 Deg C case temperature (Complete LM 80 test report for LED should be submitted for 10000 hrs. of testing). The LEDs used in Street Light should be MacAdam Step 5 standard Rated LED with CCT of 5700 K and CRI of Minimum 70. Maximum permissible driving current of LEDs are from 0.15A to 1A. Actual Driving Current of LEDs shall be less than 1000mA for life long reliability. LED Driver should be BIS Registered and shall be Isolated type, Constant Current topology driver in metal enclosure with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage – 240V) with 4KV internal surge protection in both Common Mode and Differential Mode. LED Driver shall be potted type. Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. LED driver shall have output short circuit & over voltage withstanding protection inbuilt. Luminaire shall be external SPD of 10KV. Compatibility report of SPD and Driver shall be submitted during inspection. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
Erection of HDGI 4 mtrs long Octagonal pole made up of 4mm HDGI plate, cable entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang with 0.3 mtr pole bracket
Erection of 40 W ± 10 % and 1-10V Analogue Dimmable driver withTop Maintainable LED Street Light luminaire. System efficacy of more than 130 lm/W. LED Street Light shall be made up of Die Cast aluminium housing suitable to mounted on 40-60 mm OD bracket arm. Luminaire shall have two separate compartments for LEDs and driver and both compartments should be hermitically sealed to achieve IP 66 ingress protection. Optical compartment shall be provided with polycarbonate cover with lens to withstand IK 10 impact rating, while control gear shall be provided with die cast aluminium cover for safety. LM 80-08 compliant, LEDs from approved makes should be provided. LEDs used in the product shall comply with EN 62471 for Photo-biological safety and certificate for the same from manufacturer shall be provided for Risk Group 2 maximum. Luminaire manufacturer shall produce certificate of association with LED manufacturer for minimum 5 year. LEDs shall be of EMC /Ceramic Package with 1W to 5W capacity and shall be driver at 90% or lower wattage than maximum rated. LEDs used shall have maximum allowed junction temperature of 150 Deg C with actual operating junction temperature not more than 100 Deg C at an ambient temperature of 35 Deg C. The LENS used shall have optical grade Polycarbonate to provide street light distribution for Uniform lighting. LED optical lens should be properly fixed to 1.6mm thick MCPCB and should not be only fixed by glue. LED optical lens shall have temperature withstand capacity of 125 Deg C and Transmissivity of more than 90%.The LED shall be compliant with LM80-08 standard with Useful L70 life of 50000 Hrs. tested at maximum current and at 105 Deg C case temperature (Complete LM 80 test report for LED should be submitted for 10000 hrs. of testing). The LEDs used in Street Light should be MacAdam Step 5 standard Rated LED with CCT of 5700 K and CRI of Minimum 70. Maximum permissible driving current of LEDs are from 0.15A to 1A. Actual Driving Current of LEDs shall be less than 1000mA for life long reliability. LED Driver should be BIS Registered and shall be Isolated type, Constant Current topology driver in metal enclosure with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage – 240V) with 4KV internal surge protection in both Common Mode and Differential Mode. LED Driver shall be potted type. Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. LED driver shall have output short circuit & over voltage withstanding protection inbuilt. Luminaire shall be external SPD of 10KV. Compatibility report of SPD and Driver shall be submitted during inspection. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
CCMS System a) Smart Feeder Panel IP 54 b) Switching Point controller / CCMS Controller, astronomical timer, wireless communication,ineternal memory, RS485/RS232 series comunication, CCMS can be remotely configured from server, Street light gateway supports RS485 Modibus communication and HTTPS support for wireless comunivcation with server using SIM based GPRS connection c) Energy Meter d) Local / Local Managed application software e) Luminaire NEMA contriller FEATURES PROPOSED in SYSTEM =>individual lamp level control with individual dimming facilty =>Turn ON/OFF lights as per predifined schedule =>Control of lights as per astrounomical time clock for sunset and sunrise times =>Dimming of light in non peakk traffic hours =>24 x 7 online monitoring => failure reporting => enery reports and measurement of base load
Earthing as per IS 3043/1966. including supply, erection, testing & comm. of HDGI pipe 8 ft long 40 mm dia class B, fabricated & perforated confirming to I.E. rules of 1956 including alternate layers 30cm thick of charcoal, salt & earth (charcoal & salt --10Kgs each per pit) inclusive of earthwork excavation of size 0.50x0.50x2.5m, backfilling & spreading of excavated earth evenly toget required earth resistance as per enclosed specification
HDGI strip 25 *5 mm with proper welding wherever require and painting with red oxide paint at the portion of welding, drilling cutting etc
Erection 2 x 3 core 1.5 sqmm copper flexible wire from junction box upto the fixtures .
Erection PVC insulated PVC sheathed with aluminium conductor of 1.1 KV grade 4 core armoured cable direct in ground as required and directed by engineer in-charge CABLE OF SIZE 25 sq.mm including keeping loops near poles & taking cable upto the junction boxes for new and existing poles.
Erection PVC insulated PVC sheathed with aluminium conductor of 1.1 KV grade 3.5core armoured cable direct in ground as required and directed by engineer in-charge CABLE OF SIZE 95 sq.mm including keeping loops & taking cable upto the control panel.
Earthwork excavation including opening of roads, chamber/pave-ments and soling, ramming, levelling of bottoms, making bottom freed from stones including removing out the excavated soil/materials as directed within a lead of 200 mts. (0.6 x 0.35 x400 )
Filling up of available excavated earth (excluding rock/stones) in trenches, plinth, sides, foundation etc. in layer not exceeding 0.2 mt. depth con-solidating each deposited layer by ramming and watering lead upto 200 mts. (0.6 x 0.35 x4000)
RCC Hume Pipe of 150 mm Dia
HDGI pipe 100 mm
Aluminium lugs 25 sqmm
Removing of existing tubular pole and transporting the same with vehicle to Margao Central store under supervision of GED
Removing of existing 130 W LED fixtures
Removing of existing 30 W LED fixtures
Removing of existing CCMS Panels
COST OF MATERIAL (III)
Supply of HDGI 8 mtrs long Octagonal pole made up of 4mm HDGI plate,Cable entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang HDGI pipe of 1 mtr with an angle of 15 degree and 8 mtrs long Octagonal pole
Supply of 80W ± 10 % and 1-10V Analogue Dimmable driver withTop Maintainable LED Street Light luminaire. System efficacy of more than 130 lm/W. LED Street Light shall be made up of Die Cast aluminium housing suitable to mounted on 40-60 mm OD bracket arm. Luminaire shall have two separate compartments for LEDs and driver and both compartments should be hermitically sealed to achieve IP 66 ingress protection. Optical compartment shall be provided with polycarbonate cover with lens to withstand IK 10 impact rating, while control gear shall be provided with die cast aluminium cover for safety. LM 80-08 compliant, LEDs from approved makes should be provided. LEDs used in the product shall comply with EN 62471 for Photo-biological safety and certificate for the same from manufacturer shall be provided for Risk Group 2 maximum. Luminaire manufacturer shall produce certificate of association with LED manufacturer for minimum 5 year. LEDs shall be of EMC /Ceramic Package with 1W to 5W capacity and shall be driver at 90% or lower wattage than maximum rated. LEDs used shall have maximum allowed junction temperature of 150 Deg C with actual operating junction temperature not more than 100 Deg C at an ambient temperature of 35 Deg C. The LENS used shall have optical grade Polycarbonate to provide street light distribution for Uniform lighting. LED optical lens should be properly fixed to 1.6mm thick MCPCB and should not be only fixed by glue. LED optical lens shall have temperature withstand capacity of 125 Deg C and Transmissivity of more than 90%.The LED shall be compliant with LM80-08 standard with Useful L70 life of 50000 Hrs. tested at maximum current and at 105 Deg C case temperature (Complete LM 80 test report for LED should be submitted for 10000 hrs. of testing). The LEDs used in Street Light should be MacAdam Step 5 standard Rated LED with CCT of 5700 K and CRI of Minimum 70. Maximum permissible driving current of LEDs are from 0.15A to 1A. Actual Driving Current of LEDs shall be less than 1000mA for life long reliability. LED Driver should be BIS Registered and shall be Isolated type, Constant Current topology driver in metal enclosure with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage – 240V) with 4KV internal surge protection in both Common Mode and Differential Mode. LED Driver shall be potted type. Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. LED driver shall have output short circuit & over voltage withstanding protection inbuilt. Luminaire shall be external SPD of 10KV. Compatibility report of SPD and Driver shall be submitted during inspection. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
Supply of HDGI 6 mtrs long Octagonal pole made up of 4mm HDGI plate, pole entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang HDGI pipe of 1 mtr with an angle of 15 degree
Supply of 3.8 mt hight blenheim pole made of GI and painted in matt black & gold embellishment with inbuilt terminal block and kit kat fuse including of cable with cable glands & lugs.
Supply of S“U” Bracket made of GI for mounting albary luminaire for 3.82 mtr high (3.6m above ground) blenhelm pole.
Supply of Decorative 43W Keselec Schreder make Albany LED for architectural victorian style urban lighting with Posttop type mounting arrangement. IP66 & IK08 housing with Body & cover made in spun aluminium, polyester powder coated in AKZO grey 900 sanded, Protector in UV resistant polycarbonate. Luminaires are composed of an upper and a lower body of spun aluminum and a protector, made of UV-resistant polycarbonate. Luminaire should offer easy & toolless access to LED engine and control gear from the lower body part. LED engine sealed onto the protector as a “FutureProof” optical unit, replaceable on-site, protected against lens degradation, with quick connectors for efficient maintenance. Fixture should be designed with Flatbed PCB with acrylic lens overlay principle. Luminaire should have CE Mark, ENEC Certified, ROHS Compliant. Luminaire should be vibration test compliant with modified IEC 68-2-6 (0.5G). Operating temperature range should be -30 °C up to +50 °C with wind effect. Product should be provided with Class I EU, Class II EU Electricals class, Surge Protection of 10kV & 10 kA, Power Factor - 0.9 and should comply to EN 55015 / EN 61000-3-2 / EN 61000-4-5 / EN 61547 for EMC. Product should be provided with Upward Light Output Ration (ULOR) < 5%. Product Dimension : Albany MIDI LED - 590x570x590 having weight not more than 8 Kg and having Aerodynamic resistance (CxS) of < 0.10 (m²) Lifetime residual flux @ Tq=25°C @ 100.000 hrs: 350mA & 500mA: 90%; 700mA: 80%. Life : 100000 burning hoursng with System Lumen Output - 6441 Lumens (150 Lm/Watt Efficacy) with 48 LED Count. Color Temperature : 4000K with CRI > 70. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
Supply of HDGI 4 mtrs long Octagonal pole made up of 4mm HDGI plate, cable entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang HDGI with 0.3 mtr pole bracket
Supply 40 W ± 10 % and 1-10V Analogue Dimmable driver withTop Maintainable LED Street Light luminaire. System efficacy of more than 130 lm/W. LED Street Light shall be made up of Die Cast aluminium housing suitable to mounted on 40-60 mm OD bracket arm. Luminaire shall have two separate compartments for LEDs and driver and both compartments should be hermitically sealed to achieve IP 66 ingress protection. Optical compartment shall be provided with polycarbonate cover with lens to withstand IK 10 impact rating, while control gear shall be provided with die cast aluminium cover for safety. LM 80-08 compliant, LEDs from approved makes should be provided. LEDs used in the product shall comply with EN 62471 for Photo-biological safety and certificate for the same from manufacturer shall be provided for Risk Group 2 maximum. Luminaire manufacturer shall produce certificate of association with LED manufacturer for minimum 5 year. LEDs shall be of EMC /Ceramic Package with 1W to 5W capacity and shall be driver at 90% or lower wattage than maximum rated. LEDs used shall have maximum allowed junction temperature of 150 Deg C with actual operating junction temperature not more than 100 Deg C at an ambient temperature of 35 Deg C. The LENS used shall have optical grade Polycarbonate to provide street light distribution for Uniform lighting. LED optical lens should be properly fixed to 1.6mm thick MCPCB and should not be only fixed by glue. LED optical lens shall have temperature withstand capacity of 125 Deg C and Transmissivity of more than 90%.The LED shall be compliant with LM80-08 standard with Useful L70 life of 50000 Hrs. tested at maximum current and at 105 Deg C case temperature (Complete LM 80 test report for LED should be submitted for 10000 hrs. of testing). The LEDs used in Street Light should be MacAdam Step 5 standard Rated LED with CCT of 5700 K and CRI of Minimum 70. Maximum permissible driving current of LEDs are from 0.15A to 1A. Actual Driving Current of LEDs shall be less than 1000mA for life long reliability. LED Driver should be BIS Registered and shall be Isolated type, Constant Current topology driver in metal enclosure with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage – 240V) with 4KV internal surge protection in both Common Mode and Differential Mode. LED Driver shall be potted type. Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. LED driver shall have output short circuit & over voltage withstanding protection inbuilt. Luminaire shall be external SPD of 10KV. Compatibility report of SPD and Driver shall be submitted during inspection. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
CCMS System a) Smart Feeder Panel IP 54 b) Switching Point controller / CCMS Controller, astronomical timer, wireless communication,ineternal memory, RS485/RS232 series comunication, CCMS can be remotely configured from server, Street light gateway supports RS485 Modibus communication and HTTPS support for wireless comunivcation with server using SIM based GPRS connection c) Energy Meter d) Local / Local Managed application software e) Luminaire NEMA contriller FEATURES PROPOSED in SYSTEM =>individual lamp level control with individual dimming facilty =>Turn ON/OFF lights as per predifined schedule =>Control of lights as per astrounomical time clock for sunset and sunrise times =>Dimming of light in non peakk traffic hours =>24 x 7 online monitoring => failure reporting => enery reports and measurement of base load
Earthing as per IS 3043/1966. including supply, erection, testing & comm. of HDGI pipe 8 ft long 40 mm dia class B, fabricated & perforated confirming to I.E. rules of 1956 including alternate layers 30cm thick of charcoal, salt & earth (charcoal & salt --10Kgs each per pit) inclusive of earthwork excavation of size 0.50x0.50x2.5m, backfilling & spreading of excavated earth evenly toget required earth resistance as per enclosed specification
HDGI strip 25 *5 mm with proper welding wherever require and painting with red oxide paint at the portion of welding, drilling cutting etc
Supply of 2 x 3 core 1.5 sqmm copper flexible wire from junction box upto the fixtures .
Cement concrete foundation for poles including Excavation, centering, shuttering, foundation bolts (i.e. 4 nosJ type bolt -bolts M 20 x 750 mm) and refilling of surrounding empty pit for 8 mtr for octagona,l classic, conical pole pole
Cement concrete foundation for poles including Excavation, centering, shuttering, foundation bolts (i.e. 4 nosJ type bolt -bolts M 16 x 600 mm) and refilling of surrounding empty pit for 6 mtr octagonal and classic pole
Cement concrete foundation for poles including Excavation, centering, shuttering, foundation bolts (i.e. 4 nosJ type bolt -bolts M 16 x 600 mm) and refilling of surrounding empty pit for4 mtr octagonal and classic pole
Supply of PVC insulated PVC sheathed with aluminium conductor of 1.1 KV grade 4 core armoured cable direct in ground as required and directed by engineer in-charge CABLE OF SIZE 25 sq.mm including keeping loops near poles & taking cable upto the junction boxes for new and existing poles.
Supply of PVC insulated PVC sheathed with aluminium conductor of 1.1 KV grade 3.5core armoured cable direct in ground as required and directed by engineer in-charge CABLE OF SIZE 95 sq.mm including keeping loops & taking cable upto the control panel.
Providing and laying of precast RCC protective cover of size 0.5 mts. X 0.25 width and 50 mm. thick of breaking load of 135 Kg. by riddled earth/sand up to a depth of 0.15 mts. (0.1 mts. above the top of the uppermost cable confirming to appendix C-1 and clause No. 9.2 of IS 1255-1967.
Disposal of surplus excavated soil/material by mechanical transportaion including loading and unloading stacking/levelling as directed within a distance of 2500 mts.
Supplying and laying of sand (0.35x 0.1 x3000)
RCC Hume Pipe of 150 mm Dia
HDGI pipe 100 mm
Aluminium lugs 25 sqmm
COST OF ERECTION
Erection of HDGI 8 mtrs long Octagonal pole made up of 4mm HDGI plate,Cable entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang GI pipe of 1 mtr with an angle of 15 degree and 8 mtrs long Octagonal pole
Supply of 80W ± 10 % and 1-10V Analogue Dimmable driver withTop Maintainable LED Street Light luminaire. System efficacy of more than 130 lm/W. LED Street Light shall be made up of Die Cast aluminium housing suitable to mounted on 40-60 mm OD bracket arm. Luminaire shall have two separate compartments for LEDs and driver and both compartments should be hermitically sealed to achieve IP 66 ingress protection. Optical compartment shall be provided with polycarbonate cover with lens to withstand IK 10 impact rating, while control gear shall be provided with die cast aluminium cover for safety. LM 80-08 compliant, LEDs from approved makes should be provided. LEDs used in the product shall comply with EN 62471 for Photo-biological safety and certificate for the same from manufacturer shall be provided for Risk Group 2 maximum. Luminaire manufacturer shall produce certificate of association with LED manufacturer for minimum 5 year. LEDs shall be of EMC /Ceramic Package with 1W to 5W capacity and shall be driver at 90% or lower wattage than maximum rated. LEDs used shall have maximum allowed junction temperature of 150 Deg C with actual operating junction temperature not more than 100 Deg C at an ambient temperature of 35 Deg C. The LENS used shall have optical grade Polycarbonate to provide street light distribution for Uniform lighting. LED optical lens should be properly fixed to 1.6mm thick MCPCB and should not be only fixed by glue. LED optical lens shall have temperature withstand capacity of 125 Deg C and Transmissivity of more than 90%.The LED shall be compliant with LM80-08 standard with Useful L70 life of 50000 Hrs. tested at maximum current and at 105 Deg C case temperature (Complete LM 80 test report for LED should be submitted for 10000 hrs. of testing). The LEDs used in Street Light should be MacAdam Step 5 standard Rated LED with CCT of 5700 K and CRI of Minimum 70. Maximum permissible driving current of LEDs are from 0.15A to 1A. Actual Driving Current of LEDs shall be less than 1000mA for life long reliability. LED Driver should be BIS Registered and shall be Isolated type, Constant Current topology driver in metal enclosure with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage – 240V) with 4KV internal surge protection in both Common Mode and Differential Mode. LED Driver shall be potted type. Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. LED driver shall have output short circuit & over voltage withstanding protection inbuilt. Luminaire shall be external SPD of 10KV. Compatibility report of SPD and Driver shall be submitted during inspection. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
Erection of HDGI 6 mtrs long Octagonal pole made up of 4mm HDGI plate, pole entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang HDGI pipe of 1 mtr with an angle of 15 degree
Erection 3.8 mt hight blenheim pole made of HDGI and painted in matt black & gold embellishment with inbuilt terminal block and kit kat fuse including of cable with cable glands & lugs.
Erection S“U” Bracket made of HDGI for mounting albary luminaire for 3.82 mtr high (3.6m above ground) blenhelm pole.
Erection of Decorative 43W keselec Schreder make Albany LED for architectural victorian style urban lighting with Posttop type mounting arrangement. IP66 & IK08 housing with Body & cover made in spun aluminium, polyester powder coated in AKZO grey 900 sanded, Protector in UV resistant polycarbonate. Luminaires are composed of an upper and a lower body of spun aluminum and a protector, made of UV-resistant polycarbonate. Luminaire should offer easy & toolless access to LED engine and control gear from the lower body part. LED engine sealed onto the protector as a “FutureProof” optical unit, replaceable on-site, protected against lens degradation, with quick connectors for efficient maintenance. Fixture should be designed with Flatbed PCB with acrylic lens overlay principle. Luminaire should have CE Mark, ENEC Certified, ROHS Compliant. Luminaire should be vibration test compliant with modified IEC 68-2-6 (0.5G). Operating temperature range should be -30 °C up to +50 °C with wind effect. Product should be provided with Class I EU, Class II EU Electricals class, Surge Protection of 10kV & 10 kA, Power Factor - 0.9 and should comply to EN 55015 / EN 61000-3-2 / EN 61000-4-5 / EN 61547 for EMC. Product should be provided with Upward Light Output Ration (ULOR) < 5%. Product Dimension : Albany MIDI LED - 590x570x590 having weight not more than 8 Kg and having Aerodynamic resistance (CxS) of < 0.10 (m²) Lifetime residual flux @ Tq=25°C @ 100.000 hrs: 350mA & 500mA: 90%; 700mA: 80%. Life : 100000 burning hoursng with System Lumen Output - 6441 Lumens (150 Lm/Watt Efficacy) with 48 LED Count. Color Temperature : 4000K with CRI > 70. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
Erection of HDGI 4 mtrs long Octagonal pole made up of 4mm HDGI plate, cable entry at the bottom of the pole, having weight not less then 97 KG,
Single over hang HDGI with 0.3 mtr pole bracket
Erection of 40 W ± 10 % and 1-10V Analogue Dimmable driver withTop Maintainable LED Street Light luminaire. System efficacy of more than 130 lm/W. LED Street Light shall be made up of Die Cast aluminium housing suitable to mounted on 40-60 mm OD bracket arm. Luminaire shall have two separate compartments for LEDs and driver and both compartments should be hermitically sealed to achieve IP 66 ingress protection. Optical compartment shall be provided with polycarbonate cover with lens to withstand IK 10 impact rating, while control gear shall be provided with die cast aluminium cover for safety. LM 80-08 compliant, LEDs from approved makes should be provided. LEDs used in the product shall comply with EN 62471 for Photo-biological safety and certificate for the same from manufacturer shall be provided for Risk Group 2 maximum. Luminaire manufacturer shall produce certificate of association with LED manufacturer for minimum 5 year. LEDs shall be of EMC /Ceramic Package with 1W to 5W capacity and shall be driver at 90% or lower wattage than maximum rated. LEDs used shall have maximum allowed junction temperature of 150 Deg C with actual operating junction temperature not more than 100 Deg C at an ambient temperature of 35 Deg C. The LENS used shall have optical grade Polycarbonate to provide street light distribution for Uniform lighting. LED optical lens should be properly fixed to 1.6mm thick MCPCB and should not be only fixed by glue. LED optical lens shall have temperature withstand capacity of 125 Deg C and Transmissivity of more than 90%.The LED shall be compliant with LM80-08 standard with Useful L70 life of 50000 Hrs. tested at maximum current and at 105 Deg C case temperature (Complete LM 80 test report for LED should be submitted for 10000 hrs. of testing). The LEDs used in Street Light should be MacAdam Step 5 standard Rated LED with CCT of 5700 K and CRI of Minimum 70. Maximum permissible driving current of LEDs are from 0.15A to 1A. Actual Driving Current of LEDs shall be less than 1000mA for life long reliability. LED Driver should be BIS Registered and shall be Isolated type, Constant Current topology driver in metal enclosure with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage – 240V) with 4KV internal surge protection in both Common Mode and Differential Mode. LED Driver shall be potted type. Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. LED driver shall have output short circuit & over voltage withstanding protection inbuilt. Luminaire shall be external SPD of 10KV. Compatibility report of SPD and Driver shall be submitted during inspection. NOTE: Light fittings must be equipped with requisite hardware and softare for commmunication with CCMS/GCMS panel and integrated command and control centre as per the modern sm art street lighting scheme. Data to be communicated must include current , voltage, over voltage, overcurrent, lighing strike, power failure, KW, KWh, Pf, Internal Fitting Fault etc.
CCMS System a) Smart Feeder Panel IP 54 b) Switching Point controller / CCMS Controller, astronomical timer, wireless communication,ineternal memory, RS485/RS232 series comunication, CCMS can be remotely configured from server, Street light gateway supports RS485 Modibus communication and HTTPS support for wireless comunivcation with server using SIM based GPRS connection c) Energy Meter d) Local / Local Managed application software e) Luminaire NEMA contriller FEATURES PROPOSED in SYSTEM =>individual lamp level control with individual dimming facilty =>Turn ON/OFF lights as per predifined schedule =>Control of lights as per astrounomical time clock for sunset and sunrise times =>Dimming of light in non peakk traffic hours =>24 x 7 online monitoring => failure reporting => enery reports and measurement of base load
Earthing as per IS 3043/1966. including supply, erection, testing & comm. of HDGI pipe 8 ft long 40 mm dia class B, fabricated & perforated confirming to I.E. rules of 1956 including alternate layers 30cm thick of charcoal, salt & earth (charcoal & salt --10Kgs each per pit) inclusive of earthwork excavation of size 0.50x0.50x2.5m, backfilling & spreading of excavated earth evenly toget required earth resistance as per enclosed specification
HDGI strip 25 *5 mm with proper welding wherever require and painting with red oxide paint at the portion of welding, drilling cutting etc
Erection 2 x 3 core 1.5 sqmm copper flexible wire from junction box upto the fixtures .
Erection PVC insulated PVC sheathed with aluminium conductor of 1.1 KV grade 4 core armoured cable direct in ground as required and directed by engineer in-charge CABLE OF SIZE 25 sq.mm including keeping loops near poles & taking cable upto the junction boxes for new and existing poles.
Erection PVC insulated PVC sheathed with aluminium conductor of 1.1 KV grade 3.5core armoured cable direct in ground as required and directed by engineer in-charge CABLE OF SIZE 95 sq.mm including keeping loops & taking cable upto the control panel.
Earthwork excavation including opening of roads, chamber/pave-ments and soling, ramming, levelling of bottoms, making bottom freed from stones including removing out the excavated soil/materials as directed within a lead of 200 mts. (0.6 x 0.35 x3000 )
Filling up of available excavated earth (excluding rock/stones) in trenches, plinth, sides, foundation etc. in layer not exceeding 0.2 mt. depth con-solidating each deposited layer by ramming and watering lead upto 200 mts. (0.6 x 0.35 x3000)
RCC Hume Pipe of 150 mm Dia
HDGI pipe 100 mm
Aluminium lugs 25 sqmm
Removing of existing tubular pole and transporting the same with vehicle to Margao Central store under supervision of GED
Removing of existing 130 W LED fixtures
Removing of existing 30 W LED fixtures
Removing of CCMS panel
BAGKIYA CONSTRUCTIONS PVT LTD
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .