Superintending Enginee
Office of the Superintending Engineer, Western Electrical Circle , PWD, Purta Bhavan, 1st floor, Burdwan-713103
SITC of 125 KVA diesel generator set with allied electrical installation work for Uttarpara SGH, Hooghly (RN- 17000817)---- SITC of 125 KVA DG set
2019_WBPWD_213390_1
WBPWD/SEWEC/HED /NIQ-176/2018-19
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Hooghly
Please refer Tender documents.
4 documents required · 4 mandatory
₹24,000
Yes
Office of the Superintending Engineer, Western Ele
12 Mar 2020
6 Feb 2019
3 Apr 2019
6 Feb 2019
1 Apr 2019
9 Feb 2019
6 Feb 2019 - 8 Feb 2019
8 Feb 2019
Amount
Supply , delivery at site on foundation & Commissioning of 125 -KVA, 415V, 50Hz, 30 silent new DG Set, comprising of Engine, alternator, separate AMF panel, Base frame, Fuel tank, Battery, CPCB-II approved Engin & Acoustic Enclosure having following specifications
ENGINE
Make : Cummins/Greaves/Kirloskar/Ashok Leyland
Engine Type : 4 Stroke Diesel Engine
Rated Output: 158 ВНР or Higher
Duty : PRIME
Cooling : Water cooled with radiator
Cylinder : 6
Aspiration : Turbo Charged
Type of Governer : Electronic
Fuel Tank Capacity : Minimum capacity 290 Ltrs.
Fuel Consumption at 75% rated Load with Radiator or Fan : 22.5 Ltr./ Hr. or Less
Fuel Consumption at 100% rated Load with Radiator or Fan : 30.25 Ltr./ Hr. or Less
Overload Capacity : 10% overload for one hour for every 12 hours continuous runninq at full load or better
Engine instrument Panel : Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter.
Safety Controls : Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Engine Water Temp, warning/ Shutdown, Sensor failure Indicator, Engine over speed indicator, Battery charging and low battery indicator
Exhaust Silencer : Residential Type
Starting system : 12V. starting system complete with starter motor, charging alternator with rectifier and Cutout as per manufacturer standard.
Battery : Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning
ALTERNATOR
Make: Stamford/Crompton Greaves /Kirloskar/ Ashok Ley Power
Ratinq : 415 V. 3Ph. 50 Hz., 125 KVA, 1500 rpm
Type : Brushless, self excited and self regulated
Insulation : Class H
Protection : screen-protected drip proof with Min.IP-23 degree of protection
Voltage Regulation (max) : ±1%
Winding connection : Star with Neutral
Total Distortion factor : Less than 3%
Total Harmonic distortion in output waveform : < 5%
AMF PANEL
Cubical type floor mounted AMF panel made from 16 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 125 KVA DG set having following specification/features.
i) 250A 36KA MCCB with O/L, S/C, E/F protection and microprocessor based protection release , U/V release etc. - 2Sets
ii) In Built By-Pass switch for rated capacity
iii) On -delay timer for load change over
iv) On-delay timer for engine shut off
v) Engine On-Off switch (Push button type)
vii) Minimum five number indicating lamps to indicate 'mains ON', 'load on mains', Set running', 'load on set' and 'battery charger on'.
viii) Audio visual alarm for 'Low lubricating oil pressure', 'High water temperature, Start failure', and DG over load'.
x) Microprocessor based relay with composite meter for digital display o' following.
Generator voltage/AC Mains voltage.
Generator Current in all phases
Frequency
Power Factor
Energy
Indication for alternator supply
Running time indications number of hours of operation and service intervals, service due indications
The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure.
ACOUSTIC ENCLOSURE
The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustict enclosure must be certified as per CPCB-II norms.
BASE FRAME
Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting Hook.
TERMS & CONDITIONS
(i) Rate should be quoted inclusive of all applicable taxes and Duty etc.
(ii) All materials, equipments & accessories must conform to relavent IS /IEC specifications. The DG Set to be supplied must be from the authorized OEM of the respective Engine Manufacturer.
(iii) Necessary manufacturer's test certificate for Diesel Engine, Alternator etc. Will have to submit in triplicate copy during delivery of the equipment.
(iv) Copy of "Type Approval Certificate" and Certificate of "COP" must be produced at the time of delivery issued from competent Authority (As per CPCB-II).
(v) Circuit Diagram for AMF Panel must be submitted from the Manufacturer/OEM.
(vi) The entire set must be warranted atleast 15 months from the date of Delivery/12 months/ 5000 Hrs from the date of Commissioning whichever is earlier. However Engine & Alternator should be warranted of 2 years/5000 Hrs, whichever is earlier.
Extending the exhaust pipe with 200 mm. dia MS black pipe (Thickness 4 mm) including connection with the existing silencer attached with the flexible coupler and S&F flange, nuts, bolts & washers etc. & necessary fixing materials etc. as required from DG set up to 2.5 Mts high of the near higher installation with Asbestos rope / glass wool insulation and chicken net and Aluminum fol covering, with end cap with suitable high temperature painting.
Making insulation by 2" glass wool including netting arrangement and covered with aluminum cladding as per direction of the EIC.
a) 200 mm. dia exhaust pipe.
b) Residential type silencer pipe
S&F special type MS angle iron bracket support made of 40x40x6 mm. MS angle with flat iron clamp with nuts, bolts & washers etc. for 90 mm. dia (Vertical Run).
S&F rain protection canopy.
Filling of HSD oil for initial refill with transportation.
Supply and delivery of best quality oil hand pump with 1" dia PVC flexible pipe (10 mtr. approx.)
Supply and delivery of 200 Itr. Capacity heavy gauge PVC barrel
Earthing with 50 mm dia Gl pipe 3.64 mm thick x 3.04 Mts. Long With TATA-Medium Gl pipe as per GS . [ 2(a)/G-1]
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) Cl hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, Gl reducer including drilling of 46 nos. 12 mm dia holes on the Gl pipe. [3(a)/G-2]
Excavation of soil for installation of Earth Electrode and filling & ramming for Morrum Soil.
Connecting the equipment with 25mmx6mm galvanised MS hot dip flat on wall/floor as to GS. [5d/G-3l
NARAYAN CHANDRA DAS
MOON LIGHT
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .