| Sl No | Description | Qty | Unit | Mukesh Enterprises L2 | JAI SHITLA CONSTRUCTION COMPANY L1 |
|---|---|---|---|---|---|
| 1.00 | M&L in replacement of complete AMF panel control wiring of AMF panel Outdoor type by dismantling and disconnecting the existing electrical connection of the existing AMF panel ,totally enclosed, dust and vermin proof, floor mounted , including powder coated with all control wiring , panel shall have provision for termination of UG cable for incomming / outgoing and necessary gland plates including replacement of cable termination with cable glands shall be provided at bottom of the panel suitable for DG set 160 KVA,415V, 3 phase 50 Hz 4 wire system including replacement of Auto main supply failure monitor (AMF) control relays, voltage & current sensors, supply failure timer, restoration timer control unit incorporating automatic engine start/stop/Auto/manual/test, indicators for load/mains status, Push button for engine start/stop, 250 Amps 4 Pole Power contactors with OLR relay - 02 Nos and MCCB 4 Poles 250 Amps 36 KA rating with ics=100%icu with adjustable thermal over load and magnetic short circuit releases - 2 Nos, with replacement of on load change over system of capacity 250 Amps, with replacement of busbar having 400A rating for phase & Neutral which is duly insulated with proper colour coding , One battery charger in built for charging batteries with 24V 20A SCR Controlled Battery Charger , selector switch and DC voltmeter & Ammeter all as specified and directed by Engineer-in-charge. Note : - (1) The outdoor panel enclosure only will be taken to the workshop for powder coated painting ,welding ,denting . (2) The materials inside the Panel shall be completely replaced with new one as approved make .(3) Rewiring ,fixing of spares & complete testing of AMF Panel shall be done at the site only .(4) Reconnecting /restoration of the existing connection shall be the contractor's responsiblity (5) Cost of Foundation work & cleaning the site after installation included in the quoted rate . | 1 | Each Job | 1,00,000 ₹1,00,000 | 5,000 ₹5,000 Lowest |
| 2.00 | Supply, installation, testing and commissioning in replacement of factory made AMF panel Outdoor type,Doubledoor , cubical type front operated, totally enclosed, dust and vermin proof, floor mounted made out of CRCA sheet 3.15 mm thick , powder coated with all control wiring from front, oprated panel shall have provision for termination of UG cable for incomming / outgoing and necessary gland plates including cable termination with cable glands shall be provided at bottom of the panel suitable for DG set 250 KVA,415V, 3 phase 50 Hz 4 wire system including Auto main supply failure monitor (AMF) control relays, voltage & current sensors, supply failure timer, restoration timer control unit incorporating automatic engine start/stop/Auto/manual/test, indicators for load/mains status with announciator, Push button for engine start/stop, 320 Amps 4 Pole Power contactors with OLR relay - 02 Nos and MCCB 4 Poles 320 Amps 36 KA rating with ics=100%icu with adjustable thermal over load and magnetic short circuit releases - 2 Nos, with in build seperate chamber for On load change over switch with the the same having capacity of 320 Amps - 02 Nos ( for Main & DG by pass system), Copper busbar having 600A rating for phase & Neutral which is duly insulated with proper colour coding , One battery charger in built for charging batteries with 24V 20A SCR Controlled Battery Charger , selector switch and DC voltmeter & Ammeter all as specified and directed by Engineer-in-charge. | 1 | Each Job | 3,00,000 ₹3,00,000 Lowest | 4,50,000 ₹4,50,000 |
| 3.00 | Supply, installation, testing and commissioning in replacement of factory made AMF panel Outdoor type,Doubledoor , cubical type front operated, totally enclosed, dust and vermin proof, floor mounted made out of CRCA sheet 3.15 mm thick , powder coated with all control wiring from front, oprated panel shall have provision for termination of UG cable for incomming / outgoing and necessary gland plates including cable termination with cable glands shall be provided at bottom of the panel suitable for DG set 40 KVA,415V, 3 phase 50 Hz 4 wire system including Auto main supply failure monitor (AMF) control relays, voltage & current sensors, supply failure timer, restoration timer control unit incorporating automatic engine start/stop/Auto/manual/test, indicators for load/mains status with announciator, Push button for engine start/stop, 63 Amps 4 Pole Power contactors with OLR relay - 02 Nos and MCCB 4 Poles 63 Amps 25 KA rating with ics=100%icu with adjustable thermal over load and magnetic short circuit releases - 2 Nos, with in build seperate chamber for On load change over switch with the the same having capacity of 63 Amps - 02 Nos ( for Main & DG by pass system), Copper busbar having 200A rating for phase & Neutral which is duly insulated with proper colour coding , One battery charger in built for charging batteries with 24V 20A SCR Controlled Battery Charger , selector switch and DC voltmeter & Ammeter all as specified and directed by Engineer-in-charge. | 1 | Each Job | 70,000 ₹70,000 Lowest | 2,00,000 ₹2,00,000 |
| 4.00 | M&L in replacement of complete AMF panel control wiring of AMF panel Outdoor type by dismantling and disconnecting the existing electrical connection of the existing AMF panel ,totally enclosed, dust and vermin proof, floor mounted , including powder coated with all control wiring , panel shall have provision for termination of UG cable for incomming / outgoing and necessary gland plates including replacement of cable termination with cable glands shall be provided at bottom of the panel suitable for DG set 100 KVA,415V, 3 phase 50 Hz 4 wire system including replacement of Auto main supply failure monitor (AMF) control relays, voltage & current sensors, supply failure timer, restoration timer control unit incorporating automatic engine start/stop/Auto/manual/test, indicators for load/mains status, Push button for engine start/stop, 200 Amps 4 Pole Power contactors with OLR relay - 02 Nos and MCCB 4 Poles 200 Amps 36 KA rating with ics=100%icu with adjustable thermal over load and magnetic short circuit releases - 2 Nos, with replacement of on load change over system of capacity 250 Amps, with replacement of busbar having 400A rating for phase & Neutral which is duly insulated with proper colour coding , One battery charger in built for charging batteries with 24V 20A SCR Controlled Battery Charger , selector switch and DC voltmeter & Ammeter all as specified and directed by Engineer-in-charge. Note : - 1. The outdoor panel enclosure only will be taken to the workshop for powder coated painting ,welding ,denting . 2. The materials inside the Panel shall be completely replaced with new one as approved make 3. Rewiring ,fixing of spares & complete testing of AMF Panel shall be done at the site only 4. Reconnecting /restoration of the existing connection shall be the contractor's responsiblity (5) Cost of Foundation work & cleaning the site after installation included in the quoted rate . | 2 | Each Job | 70,000 ₹1,40,000 | 2,000 ₹4,000 Lowest |
| 5.00 | M&L in replacement of complete AMF panel control wiring of AMF panel Outdoor type by dismantling and disconnecting the existing electrical connection of the existing AMF panel ,totally enclosed, dust and vermin proof, floor mounted , including powder coated with all control wiring , panel shall have provision for termination of UG cable for incomming / outgoing and necessary gland plates including replacement of cable termination with cable glands shall be provided at bottom of the panel suitable for DG set 125 KVA,415V, 3 phase 50 Hz 4 wire system including replacement of Auto main supply failure monitor (AMF) control relays, voltage & current sensors, supply failure timer, restoration timer control unit incorporating automatic engine start/stop/Auto/manual/test, indicators for load/mains status, Push button for engine start/stop, 200 Amps 4 Pole Power contactors with OLR relay - 02 Nos and MCCB 4 Poles 200 Amps 36 KA rating with ics=100%icu with adjustable thermal over load and magnetic short circuit releases - 2 Nos, with replacement of on load change over system of capacity 250 Amps, with replacement of busbar having 400A rating for phase & Neutral which is duly insulated with proper colour coding , One battery charger in built for charging batteries with 24V 20A SCR Controlled Battery Charger , selector switch and DC voltmeter & Ammeter all as specified and directed by Engineer-in-charge. Note : - 1. The outdoor panel enclosure only will be taken to the workshop for powder coated painting ,welding ,denting . 2. The materials inside the Panel shall be completely replaced with new one as approved make 3. Rewiring ,fixing of spares & complete testing of AMF Panel shall be done at the site only 4. Reconnecting /restoration of the existing connection shall be the contractor's responsiblity (5) Cost of Foundation work & cleaning the site after installation included in the quoted rate . | 2 | Each Job | 1,05,000 ₹2,10,000 | 2,000 ₹4,000 Lowest |
| 6.00 | M & L for overhauling of complete DG set of capacity 40 KVA by disconnecting and removing the following parts from the engine, and refixing/re-assembling the new parts on site/workshop including replacement of rusted and damaged canopy of the DG set by welding the door hinges or roof sheets complete all as specified and directed by Engr-in-Charge. (a)Valve,intake (b) Bearing,coonecting rod (c) seal,oil (d) Seal, O ring (e) Sender-pressure (f) Valve,exhaust (g) collet valve (h) spring, valve (i) Gasket Cylinder head (j) Camshaft (k) Kit, Engine piston (l) Cover, accessory drive (m) Injector (n) Pin, Piston (o) Retainer , Valve spring (p) Gasket, Gear cover (q) Sensor-Temperature.
Note: (1)The rate quoted shall be inclusive of transporting of the complete engine to the workshop and back and all incidental charges. (2) The overhauling will be carried out by only the OEM and the parts should be purchased from the authorised dealer only. | 1 | Each Job | 25,000 ₹25,000 Lowest | 80,000 ₹80,000 |
| 7.00 | Supply & fixing, in repair including testing and commissioning of Fire alrm Control panel complying with BSEN54 addressable two loop panel including controller card of capacity from 99 detector and 99 modules upto 200 detector and modules complete with battery 12 volts 7 AH capacity (02 Nos ) all as specified and directed Make :- Apollo/System Sensor/Agni devices/Ravel | 3 | Each | 12,000 ₹36,000 Lowest | 1,00,000 ₹3,00,000 |
| 8.00 | Repair/Maint of following capacity engine start system Fire Fighting Pump sets installed at DWR complete all as specifed and as directed by Engr-in-Charge. The repair/maintenance cost includes 01 preventive maintenance visits and unlimited breakdown calls during the Contract period. The Maintenance Shall include the following works and services.
a) Cleaning, Oiling,Greasing, topping, calibration, repairs to Main Pump Electric driven, Jockey Pump electric driven,diesel engine driven pump
b) Checking the tention in V Belt of any size of diesel engine,pipe with fittings, check the level of coolant in radiator, repairs to leakage in radiator etc. Gaskets & Oil seals,bushes, servicing of the water pump, adjustment of fuel firing, repair to self starter,
c) Battery top up with Electrolite solution, arresting the oil leakage and topping up of engine oil, operator interface device OID display,replacement of U/S oil level tube provided on the fuel tank for checking of oil level, cleaning of fuel tank etc.
d) The tank has to be calibrated and level marked on the tank, cleaning of tank for dust and mud.
e) Repair of wiring control panel of diesel engine by checking of condition of control wiring and tightning of screws etc as required at site. DG including repair/Replacement off toggle switch,
f) Inspection of Motor Control system with cleaning of all the switch gears and contactors
g) Inspection, testing of entire Hydrant System, through maintenance service Centre having experience in Fire Fighting maintainance or any other agency as approved by GE,checking of complete pipe line and cleaning of the complete line by passing rod or SWR wire. (h) Replacement of spare parts will be measure seperate.
(i)A register shall be maintained by the contractor for each visit and kept in record duly signed by user and JE/ Engr-in-Charge. | 1 | Each Job | 2,00,000 ₹2,00,000 | 30,000 ₹30,000 Lowest |
| 8.01The list of fire fighting eqipments installed is appended below. | |||||
| 8.021.Motor driven main pump 60 HP 1415RPM 17M Head -kirloskar Make 01 Nos | |||||
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
3 Sept 2025, 6:00 pmClosed
GE (AF) TA GWALIOR
GE (AF) TA GWALIOR-474020
REPAIR MAINTENANCE OF MISC EM WORKS INCLUDING DG SETS CABLES ELECTRIC PANELS AND CONNECTED ITEMS ETC. UNDER GE AF TA GWALIOR
2025_MES_723908_1
8900/1612/GWL/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Gwalior
Please ref tender documents
7 documents required · 7 mandatory
₹500
GE(AF) TA GWALIOR
₹50,000
Yes
17 Oct 2025
1 Aug 2025
10 Sept 2025
1 Aug 2025
3 Sept 2025
15 Aug 2025
Amount
M & L for overhauling of complete DG set of capacity 40 KVA by disconnecting and removing the following parts from the engine, and refixing/re-assembling the new parts on site/workshop including replacement of rusted and damaged canopy of the DG set by welding the door hinges or roof sheets complete all as specified and directed by Engr-in-Charge. (a)Valve,intake (b) Bearing,coonecting rod (c) seal,oil (d) Seal, O ring (e) Sender-pressure (f) Valve,exhaust (g) collet valve (h) spring, valve (i) Gasket Cylinder head (j) Camshaft (k) Kit, Engine piston (l) Cover, accessory drive (m) Injector (n) Pin, Piston (o) Retainer , Valve spring (p) Gasket, Gear cover (q) Sensor-Temperature. Note: (1)The rate quoted shall be inclusive of transporting of the complete engine to the workshop and back and all incidental charges. (2) The overhauling will be carried out by only the OEM and the parts should be purchased from the authorised dealer only.
Supply & fixing, in repair including testing and commissioning of Fire alrm Control panel complying with BSEN54 addressable two loop panel including controller card of capacity from 99 detector and 99 modules upto 200 detector and modules complete with battery 12 volts 7 AH capacity (02 Nos ) all as specified and directed Make :- Apollo/System Sensor/Agni devices/Ravel
Repair/Maint of following capacity engine start system Fire Fighting Pump sets installed at DWR complete all as specifed and as directed by Engr-in-Charge. The repair/maintenance cost includes 01 preventive maintenance visits and unlimited breakdown calls during the Contract period. The Maintenance Shall include the following works and services. a) Cleaning, Oiling,Greasing, topping, calibration, repairs to Main Pump Electric driven, Jockey Pump electric driven,diesel engine driven pump b) Checking the tention in V Belt of any size of diesel engine,pipe with fittings, check the level of coolant in radiator, repairs to leakage in radiator etc. Gaskets & Oil seals,bushes, servicing of the water pump, adjustment of fuel firing, repair to self starter, c) Battery top up with Electrolite solution, arresting the oil leakage and topping up of engine oil, operator interface device OID display,replacement of U/S oil level tube provided on the fuel tank for checking of oil level, cleaning of fuel tank etc. d) The tank has to be calibrated and level marked on the tank, cleaning of tank for dust and mud. e) Repair of wiring control panel of diesel engine by checking of condition of control wiring and tightning of screws etc as required at site. DG including repair/Replacement off toggle switch, f) Inspection of Motor Control system with cleaning of all the switch gears and contactors g) Inspection, testing of entire Hydrant System, through maintenance service Centre having experience in Fire Fighting maintainance or any other agency as approved by GE,checking of complete pipe line and cleaning of the complete line by passing rod or SWR wire. (h) Replacement of spare parts will be measure seperate. (i)A register shall be maintained by the contractor for each visit and kept in record duly signed by user and JE/ Engr-in-Charge.
The list of fire fighting eqipments installed is appended below.
1.Motor driven main pump 60 HP 1415RPM 17M Head -kirloskar Make 01 Nos
2. Motor driven Jockey pump 15 HP 2900 RPM 17M head -01 Nos
3. Diesel driven std by pump 68 HP 1620LPM 1500RPM 88M head o kirloskar make 01 Nos
4. Complete Hydrant System with UG MS Pipe ,02 Nos Fire Hydrants and 04 Nos Hose cabinets & Hose reel drum.
Note for Item No 8 : The Repair of fire fighting system shall also include the following checks
1. Cleaning, Checking and operating all fire pumps. Checking noise, vibration and temperature of the pumps in their working state.
2. Cleaning, Checking electrical Control Panel (MCC) of the fire pumps.
3. Checking of Engine Driven Starter Panel, Servicing of Fire Diesel pump At the interval of 06 Month
4. Checking of Volt Meter; Amp meter; Starter etc.
5. Checking of batteries, fan belt, temperature gauge, Fuel gauge etc. of diesel generator fire pump.
6. Greasing of pump shafts, hydrant post male/female connector head
7. Overhauling of all Pumps if required
8. Cleaning of all pumps and its accessories.
9.Checking & servicing of Strainers, Gate / Butterfly Valves, Non return Valves, Air Vessel, Pressure Gauges, Pressure Switches and other related accessories therein.
10.Checking of Diesel Tank flow pipe condition, Display pipe condition.
M&L for Cleaning of UG Sump of capacity 5000 Gallons of any description cleaning inside of the UG Sump by removing all despositions/fungus other micro organism, sediment loose dirt/mud sludge, Vegetation, other foreign materials etc and also removing loose/unsound concrete/plaster including taking out and removing all disposal waste / spoil to a distance not exceeding 50 mtr and Brushing with nylon brush on walls & bottom surfaces , washing the surfaces with clean water and washing repeatedly with Rebekiense solution and clean with water & cleaning of external surface with water, including two coats of white wash and opening washout/drain pipe and sluice valve cleaning and refixing drain/washout pipe and painting two coats of drain pipe ,overflow pipe ,inlet,outlet pipe 150/100 mm dia,and and panting of cleaning date and next due cleaning date of each tank complete all as specified and directed :-
M & L in replacement of GI tubing 25 mm dia GI pipe , medium grade, galvanized, in trenches or fixed on walls/ floors/ roofs etc with and including provision of all connected fittings complete all as specified and as directed.
M&L in replacement of ball brass valves,25 mm dia ,high pressure,with polythenefloat and flynut complete,screwed for iron pipe or brass ferrule and fixed complete all as specified and directed.
M&L of Boring of holes under road pavement hard standing /road by manual boring incl making good the disturbed surfaces complete all as specified and directed
M&L in replacement of existing damaged GI sheet duct and S&F pre fabricated ducting made out of GI sheet duct of 22 Gauge sheet and bolting with proper gaskets,supports,rods etc as per standard. All flange joint shall be sealed with RTV sealent to make air tight as per SMACNA standard to match with the existing duct complete all as specified Make Jindal/Tata/SAIL
Supply & Fixing in replacement of sealed maintenance free batteries 12 V ,45 AH suitable for 30 KVA UPS system complete for its satisfactory operation
S & F following items in AMF Panel of any description and in any position of capacity DG Set upto 500 KVA including checking AC/DC circuits, tightning of all power / control wiring connection and replacement of unserviceable control wiring with suitable size, single core, copper conductor, flexible, PVC insulated, unsheathed cable suitable upto 1100 volts confirming to IS-694, taking out, removing and replacement of unserviceable parts / spares / items to make AMF functional inclusing testing complete all as specified and directed.
Ammeter size 96 mm X 96mm, flush mounted digital type, three phase of class 1.0 complete all as specified and directed.
Voltmeter size 96 mm X 96mm, flush mounted digital type, three phase, class 1.0 complete all as specified and directed.
Frequency meter size 96 mm X 96mm, flush mounted digital type, three phase, class 0.2 complete all as specified and directed.
Under voltage relay suitable for 3 phase 415 volts, AC supply complete all as specified and directed.
Engine starting relay with sequence timer & master timer suitable for 12 / 24 Volts DC supply complete all as specified and directed.
Electronic timer, time range from 3 seconds to 10 seconds , suitable of 12/ 24 Volts, 50 Hz, AC supply complete all as specified and directed.
LED Indicator 22.5mm for 12 /24 volts AC/DC supply complete all as specified and directed.
Battery charging transformer 0 to 10 Amperes, 12 Volts DC tapping 0-12-18-24 Volts complete all as specified and directed.
MCB single pole, 10 KA, rating 6 to 32 Amps ‘C’ series, 240 volts complete all as specified and directed.
Material and labour for dismantling and taking out and rewinding of Alternator startor assembly of 125 KVA DG Set and rewinding of approved suitable gauge super enamel insulated copper winding wire with necessary insulating materials reassembling and transportation to workshop and bring back to orgins at installation and fixing,testing and commissioning complete all as specified and directed by Eng-in-charge.
M& L in complete repair /servicing of Air compressor MAKE : Elg by opening the complete system of capacity 2.83 cum/min ,motor power 18.5 kw ,max working pressure 8.5 kgf/cm square and replacement of unserviceable piston ring,head polish ,filter ,coolant,NRV, oil 12.5 Ltr (Elgi) ,Contactor,drain ,ball valve,,pressure switch,pressure guage ,check valve,magnetic starter,drive belt, electric power pump motor ,control panel ,PCB ,output ports,AC cords, setting including servicing,testing the complete Air compressor system complete all as specified and directed. i.
M& L in complete repair /servicing of Air compressor MAKE : Ingersoll Rand by opening the complete system of capacity 2.87 cum/min ,motor power 18.5 kw ,max working pressure 8.5 kgf/cm square and replacement of unserviceable piston ring,head polish ,filter ,coolant,NRV, oil 12.5 Ltr (IR) ,Contactor,drain ,ball valve,,pressure switch,pressure guage ,check valve,magnetic starter,drive belt, electric power pump motor ,control panel ,PCB ,output ports,AC cords, setting including servicing,testing the complete Air compressor system complete all as specified and directed.
Supply & fixing in replacement of of DG altrnator diode rectifier of the capacity 200/250 KVA DG sets complete all as specified and as directed.
M& L in replacement of Speed controller of DG sets of capacity 125 KVA complete all as specified and directed.
Supply & Fixing in replacement of Onload changeover switch with metal enclosure of capacity 250 Amps 4 pole complete all as specified and directed
M& L in complete repair /servicing of oil cooled servo controlled voltage stabilizer by opening the complete system of capacity 150 KVA and replacement of unserviceable variable transformer or dimmer ,series transformer ,synchronising motor or servo motor - 03 Nos,electronic circuits, carbon bush and carbon bush holder ,servicing/ cleaning of cooling fins replacement of PCB-03 Nos,RC net work,limit switches ,pot for voltage setting including servicing,testing the complete oil cooled stabilizer complete all as specified and directed. Note : transformer oil shall be measured seperately under relevent items.
M& L in complete repair /servicing of oil cooled servo controlled voltage stabilizer by opening the complete system of capacity 75 KVA and replacement of unserviceable variable transformer or dimmer ,series transformer ,synchronising motor or servo motor - 03 Nos,electronic circuits, carbon bush and carbon bush holder ,servicing/ cleaning of cooling fins replacement of PCB-03 Nos,RC net work,limit switches ,pot for voltage setting including servicing,testing the complete oil cooled stabilizer complete all as specified and directed. Note : transformer oil shall be measured seperately under relevent items.
M& L in replacement of transformrer oil suitable for servo controlled oil cooled voltage stabilizer complete all as specified and directed.
M&L in replacment of AMF Power contactor , 4 pole, 415 Volts, 100 Amps, 50 Hz, AC , with 2 NO and 2 NC contacts including any modification to existing panel frame size and fixing new contactor with connecting bars to the main busbar, incoming/ out going cables with suitable lugs and testing complete all as specified and as directed.Make:L&T Cat : CS97017, Model MCX 22 or equivalent of Havells/ABB as approved by GE
M&L in replacment of AMF Power contactor , 4 pole, 415 Volts, 63 Amps, 50 Hz, AC , with 2 NO and 2 NC contacts including any modification to existing panel frame size and fixing new contactor with connecting bars to the main busbar, incoming/ out going cables with suitable lugs and testing complete all as specified and as directed.Make:L & T ,Cat : CS97027, Model MCX 44 or equivalent of Havells/ABB as approved by GE
Mukesh Enterprises (BID ID -3415220)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .