Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 1008 A PREMIER ENGINEERING COMPANY PURVI RITHANI MEERUT DELHI ROAD MEERUT UTTAR PRADESH 250103 INDIA | MEERUT | UTTAR PRADESH | 250103 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹3,200
Closing Date
8 Jun 2020, 2:00 pmClosed
EXECUTIVE ENGINEER (EM) WS SOUTH-I
GREATER KAILASH, PART-I, NEW DELHI
SITC of 3200 and 800 Amp. ACB at LT Panel of Deer Park BPS.
2020_DJB_191218_1
NITNo.3/EE(EM)WS S-I/(20-21)
Open Tender
Electrical Work/ Equipment
Works
30 days
EXECUTIVE ENGINEER (EM) WS SOUTH-I
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Delhi Jal Board
₹3,200
Yes
11 Jun 2020
2 Jun 2020
8 Jun 2020
2 Jun 2020
8 Jun 2020
2 Jun 2020
Part –A Installation, Testing, Commissioning of 3200ACB incomer no 2. at Deer Park With carry out the following works- Dismantling of old ACB 3200Amp. & other accessories from existing Panel, removing of all cable connection after taking shut down with help of gas cutter, heavy labor etc.
Providing /fixing and making connection of bus bar for connection of 3200Amp. ACB links, bends, aluminum bus bar will be of electrolytic grade 55% conductivity or as per relevant IS having sufficient cross section area insulated with heat shrinkable PVC sleeve in phase color identification. The bus bar support insulator shall be of class F insulation made out of non-hygroscopic material as SMC/DMC. All hard ware for connection/joints shall be in high tensile.
Arrangement of incoming / outgoing cable termination by providing & fixing of terminal link of current carrying capacity 3200Amp. With phase separator in sheet .Removable cable gland plate to be provided for each cable entry with cable gland. Making connection of both incoming & out going side as required with proper insulation.
Fixing of the 3200Amp. ACB in the existing L T Panel Board including providing & fabrication & fixing of the base frames of suitable sizes for ACBs in the chamber. Modification in panel door Re-Fixing of existing all the measuring instruments, CT’s, lamps, etc. at the metering chamber along with complete wiring through 2.5 sq mm single core copper wire including providing and fixing of necessary ferrules etc. and fixing the backup fuses as per requirement(ACB shall be provided by department)
Providing & fixing of under voltage trip unit complete with control wiring & setting of tripping
Part - B Installation, Testing, Commissioning of 800ACB incomer no 1. at Geetanjali Bps With carry out the following works- Dismantling of old ACB 800Amp & other accessories from existing Panel ,removing of all cable connection after taking shut down with help of gas cutter, heavy labor etc.
Providing /fixing and making connection of bus bar for connection of 800Amp. ACB size 100x10mm including links, bends, aluminum bus bar will be of electrolytic grade 55% conductivity or as per relevant IS having sufficient cross section area insulated with heat shrinkable PVC sleeve in phase color identification. The bus bar support insulator shall be of class F insulation made out of non-hygroscopic material as SMC/DMC. All hard ware for connection/joints shall be in high tensile.
Arrangement of incoming / outgoing cable termination by providing & fixing of terminal link of current carrying capacity 630Amp. With phase separator in acrylic sheet .Removable cable gland plate to be provided for each cable entry with cable gland. Making connection of both incoming & out going side as required with proper insulation.
Fixing of the 800Amp. ACB in the existing L T Panel Board including providing & fabrication & fixing of the base frames of suitable sizes for ACBs in the chamber. Modification in panel door Re-Fixing of existing all the measuring instruments, CT’s , lamps, over current & earth fault relay etc. at the metering chamber along with complete wiring through 2.5 sq mm single core copper wire including providing and fixing of necessary ferrules etc. and fixing the backup fuses as per requirement. (ACB shall be provided by department)
Testing & commissioning of installed equipment’s, as per required parameters with relevant IS .testing of the panel prior to switching on as follow i)Continuity and earth testing ii) Meggering of all equipments for phase to phase, neutral to body, neutral to earth and phase to earth. iii)checking for all tightness of nut and bolts iv) Alignments of doors etc. v) Interlocking tests. vi) All function tests
Raj Engineering Co.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .