| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹1.2 CrAccepted-AOC 13 29 3RD FLOOR EAST PATEL NAGAR NEW DELHI 110 008 | WEST | DELHI | 110008 | ₹1.2 Cr | L-1 | Accepted-AOC Being lowest bidder |
| 2 | L-2₹1.4 Cr+₹11.9 L (9.51%)Rejected-Finance 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | NEW DELHI | DELHI | 110010 | ₹1.4 Cr+₹11.9 L (9.51%) | L-2 | Rejected-Finance Not being lowest bidder |
| 3 | L-3₹1.4 Cr+₹12.5 L (9.97%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | ₹1.4 Cr+₹12.5 L (9.97%) | L-3 | Rejected-Finance Not being lowest bidder |
| 4 | L-4₹1.4 Cr+₹15.6 L (12.5%)Rejected-Finance 3 1 4 GOPINATH BAZAR DELHI CANTT 110 010 | NEW DELHI | DELHI | 110010 | ₹1.4 Cr+₹15.6 L (12.5%) | L-4 | Rejected-Finance Not being lowest bidder |
| 5 | L-5₹1.4 Cr+₹19.2 L (15.4%)Rejected-Finance 38 49 D OLD IDGAH COLONY AGRA U P 282001 | AGRA | AGRA | UTTAR PRADESH | 282001 | ₹1.4 Cr+₹19.2 L (15.4%) | L-5 | Rejected-Finance Not being lowest bidder |
Tender Value
₹1.4 Cr
EMD Value
₹2.2 L
Closing Date
3 Jan 2024, 6:00 pmClosed
CE RnD Timarpur
HQ CE RND TIMARPUR DELHI-110054
REPLACEMENT OF TRANSFORMERS 11/0.433 KV, DG SET AND SUBMERSIBLE PUMP SET AGAINST BER WITH CONNECTED ITEMS AT DRDE GWALIOR UNDER GE (I) RnD DELHI
2023_MES_631241_1
CE R and D/DLI- 35/GWL/2023-24
Open Tender
Civil Works
Item Rate
365 days
Gwalior
Please refer tender documents
8 documents required · 8 mandatory
₹1,000
GE I RND DELHI
₹2.2 L
Yes
27 Feb 2024
5 Dec 2023
10 Jan 2024
5 Dec 2023
3 Jan 2024
27 Dec 2023
Amount
Dismantling of Transformers of any type and size/ Cap. by taking out electric connection and shifting to nearby site as directed by Engr-in-Charge.
Supply, Installation, testing and commissioning outdoor type of 200 KVA capacity of transformer step down 11/0.433 KV( at no load ), copper wound, AC supply 3 phase, 4 wire 50 HZ, oil immersed, Air naturally ( ONAN ) with external cooling tubes, delta connected on primary (HV side) and star connected on secondary (LV side) in accordance with vector group DYN 11 with neutral brought out on secondry side ( LV side ) having tapping at 7.5% + Insteps of 2.5 % each HV side to be changed by means of hand operated off load tap changing gear. The maximum temp rise should not exceed 45 degree celsius in oil and 55 degree Celsius in HV/LV winding when measured by resistance method after continous full load run on an ambient temperature of 40 degree Celsies, complete with all standard fittings as per IS-1180/2014 and shall comprise of the following:-
(a) One No cable box on LT side (secondary) consisting of 04 Nos porcelain bushing with brass rods with nuts bolts and washers complete. with cable glands suitable for reception / taking out XLPE Cable including gland, Joint and Jointing material (b) Oil conservator tank with filter type drain valve and oil level gauge. (c) De-hydrating breather with first fill dehydrating agent (Silica gel) (d) Explosive vent for release of pressure will be provided on the cover. (e) Thermometer pocket on tank cover. (f) One No 100 mm dia, dial type thermometer, vapour pressure type, having range (0-120) degree Celsius with metal guard having maximum parameter reading, temperature indicator with re-setting device for transformer (g) Two earthing terminal In LT Side box to facilitate fixing of 32x6mm galvanised iron earth strip for earthing of neutral & body. (h) Rating plate and terminal marking plate ( Diagramplate )
(j) Oil level gauge (k) Oil drain filter valve (l) 4 Nos Lifting lugs. (m) Oil filling hole with cap / plug complete. (n) Air release valve plug (o) Four plains solid Cast Steel detachable rollers (p) Extra bushing for neutral, out side the LT cable box for providing independent set of earthing for neutral (q) First filling of new and unused transformer oil IS-335/93 ( fourth revision ) marked filtered and tested upto 40 KV dielectric stength at 2.5 mm air gap between testing rod. (r) One dangers notice board having conventional danger sign of Skull and bones is painted in red colour
Supply, Installation, testing and commissioning outdoor type of 500 KVA capacity of transformer step down 11/0.433 KV( at no load ), copper wound, AC supply 3 phase, 4 wire 50 HZ, oil immersed, Air naturally ( ONAN ) with external cooling tubes, delta connected on primary (HV side) and star connected on secondary (LV side) in accordance with vector group DYN 11 with neutral brought out on secondry side ( LV side ) having tapping at 7.5% + Insteps of 2.5 % each HV side to be changed by means of hand operated off load tap changing gear. The maximum temp rise should not exceed 45 degree celsius in oil and 55 degree Celsius in HV/LV winding when measured by resistance method after continous full load run on an ambient temperature of 40 degree Celsies, complete as per IS-1180 /2014 (level-2) and shall comprise of the following:-
(a) One No cable box on LT side (secondary) consisting of 04 Nos porcelain bushing with brass rods with nuts bolts and washers complete. with cable glands suitable for reception / taking out XLPE Cable including gland, Joint and Jointing material (b) Oil conservator tank with filter type drain valve and oil level gauge. (c) De-hydrating breather with first fill dehydrating agent (Silica gel) (d) Explosive vent for release of pressure will be provided on the cover. (e) Thermometer pocket on tank cover. (f) One No 100 mm dia, dial type thermometer, vapour pressure type, having range (0-120) degree Celsius with metal guard having maximum parameter reading, temperature indicator with re-setting device for transformer (g) Two earthing terminal In LT Side box to facilitate fixing of 32x6mm galvanised iron earth strip for earthing of neutral & body. (h) Rating plate and terminal marking plate ( Diagram plate )
(j) Oil level gauge (k) Oil drain filter valve (l) 4 Nos Lifting lugs. (m) Oil filling hole with cap / plug complete. (n) Air release valve plug (o) Four plains solid Cast Steel detachable rollers (p) Extra bushing for neutral, out side the LT cable box for providing independent set of earthing for neutral (q) First filling of new and unused transformer oil IS-335/93 ( fourth revision ) marked filtered and tested upto 40 KV dielectric stength at 2.5 mm air gap between testing rod. ( r ) One dangers notice board having conventional danger sign of Skull and bones is painted in red colour
Supply, installation, testing and commissioning silent diesel engine driven generating set of latest Technology as per CPCB-IV Norms of capacity 25 KVA/20KW. at 42 BHP capacity water cooled diesel Engine 3 phase 4 wire, 415 Volts, 1500 RPM, 50 Hz AC power supply with power factor 0.8(Lag) coupled directly to alternator mounted on a common base plate on vibration pad complete with fuel tank, battery 12V, - 01 No, including Micro processor based AMF Panel with standard accessories and fittings. The DG set control panel for mounting oil pressure, hours run, emergency stop button, RPM meters, water temperature etc. which are required to check for smooth functioning of DG set during its running period. All other safety provisions shall be provided as per standard specifications of Model No KG1 - 25 WSE of KIRLOSKAR KOEL( KIRLOSKAR) Make or equiviliant in CUMMINS/GREAVES COTTON all as specified and directed and shall comprise of following:
Diesel engine : Water cooled multi cylinder inline type of mechanical fuel injection diesel engine of capacity 25 KVA/20KW at 42 BHP at 1500 RPM under NTP conditions confirming to IS-100001/ISO8528-1/BS 5514 with an overload capacity of 10% for one hour in any 12 hours, No of cylinders- 03 Nos,1500 RPM, water cooled naturally turbo charged capable of giving adequate BHP to drive alternator of capable 25 KVA at NTP, Diesel engine of rated speed at full load electric start and including mechanical operated governor control of class A1, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for automatic electric start with 12 V electric starting system for DG set capacity 25 KVA batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/flexible coupling guard complete of Model No 3R1040T G1 of KOEL( KIRLOSKAR) Make or equivilant in CUMMINS/GREAVES COTTON.
ALTERNATOR : Alternator shall be brush less type,rotating field type synchronous alternator continuously rated for 415 volts, 3 phase, 4 wire, 50 Hz, 0.8 power factor (lagging) at 1500 RPM, under NTP conditions in accordance with IS-4722 & IS-13361, 4 pole, screen protected, dip proof, horizontal foot- mounted type, the degree of protection will be IP-23 enclosure, solid state voltage regulation + 1% self excited, self regulated with static excitation system, One step load acceptance 100% of rating, 'H' Class insulation, 125 Deg C Temperature rise, Sealed type bearing - 01 no, flex disc coupling, 25% of rated amps unbalanced load capability The alternator should be capable for developing rated output and able to take 10% over load for 1 hr every 12 hrs of operation and will be suitable for tropical condition. Alternator Make: KOEL GREEN or equivilant in Stamford/Meccalte all as specified and directed.
Coupling & Mounting Arrangement: (i) The Engine and alternator shall be directly coupled by means of self-aligning flexible flange coupling to avoid misalignment. (ii) The coupling shall be provided with protecting guard to avoid accidental contract
Fuel tank : The tank shall be completed with an outlet, a drain plug, an air vent, an air breather and necessary piping. Fuel tank shall be inside the Acoustic Enclosure etc complete all as specified and directed.
Battery & Battery Charger – 1 No. 12 V Battery complete with all leads shall be provided with each DG Set. Each battery shall have sufficient capacity to give 10 nos. successive starting impulse to the engine.
Governing System – The Engine shall be supplied with Mechanical Governor for DG Set rating 25 KVA . This governor shall be directly mounted on the engine to enable the speed variation from idling speed to the maximum load speed.
Acoustic Enclosure : This is a special sheet metal fabricated on CNC machine and Powder coated. The enclosure is designed for reducing the sound level to 75 dB (A) (average) all round in green field, as per IS: 8528 Part 10 as per approved CPCB IV norms.
Supply, installing, commissioning and testing of silent Diesel Engine driven Generating set of capacity 75KVA/60 KW, alternator mounted on common base frame conforming to BS-5514 and IS-10002, rated for 415 volts 50 Hz, 0.8(Lag) PF complete with Fuel Tank, Batteries and Leads, Silencer -Residential, AVM Pads, First fill of Lube oil and Acoustic Enclosure with standard AMF Panel as per relevant IS, Prime rating, of model No GPWII - PII - 75S of Greaves Cotton or equivilant in Kirloskar/Sudhir complete all as per specified in PS including of the followings features and accessories / components:-
ENGINE (a) Diesel Engine of suitable for 75KVA/60KW 3 cylinders Vee arrangements, Displacement (L) is 3.66 , TCIC aspiration, BorexStroke(mm) is 108 x 133, 17.2 compression ratio, over speed trip RPM is 1650 rated at 1500 RPM, water cooled, Four Stroke, Electric start in accordance with BS-5514/ISO -3046 with capacity of 10% over loading for one hour in twelve hours duration, Gross engine power is 74.5 kWm, Direct injection, water cooled, three cylinder, 4 stroke, rated at 1500 RPM, of model No. 3G11TAG26 with the following accesssories :- (i) Isochronous Frequency Regulation (ii) Mechanical governor type. (iii) performance class is G2 (iv) 12 V DC solenoid coil. (v) Dry type air cleaner - 01 No (vi) Radiator cooling (vii) Exhaust manifold with SS exhaust flexible (viii) Flywheel and flywheel housing (ix) Fuel and lube oil filters (x) Starter motor, battery charger
ALTERNATOR. Alternator shall be brush less type,rotating field type synchronous alternator continuously rated for 415 volts, 104.34 Amps, 3 phase, 4 wire, 50 Hz, 0.8 power factor (lagging) at 1500 RPM, under NTP conditions in accordance with IS-4722 & IS-13361, 4 pole, screen protected, dip proof, horizontal foot- mounted type, the degree of protection will be IP-23 enclosure, solid state voltage regulation + 1% self excited, self regulated with static excitation system, One step load acceptance 100% of rating, 'H' Class insulation, 125 Deg C Temperature rise, Sealed type bearing - 01 no, flex disc coupling, 25% of rated amps unbalanced load capability The alternator should be capable for developing rated output and able to take 10% over load for 1 hr every 12 hrs of operation and will be suitable for tropical condition. Alternator Make: Stamford or equivilant in CG/Kirloskar/Cummins
Coupling & Mounting Arrangement: (i) The Engine and alternator shall be directly coupled by means of self-aligning flexible flange coupling to avoid misalignment. (ii) The coupling shall be provided with protecting guard to avoid accidental contract
Fuel tank : The tank shall be completed with an outlet, a drain plug, an air vent, an air breather and necessary piping. Fuel tank shall be inside the Acoustic Enclosure etc complete all as specified and directed.
Battery & Battery Charger – 1 No. 12 V/88AH Battery complete with all leads shall be provided with each DG Set. Battery shall have sufficient capacity to give successive starting impulse to the engine.
Governing System – The Engine shall be supplied with Mechanical Governor for DG Set rating 75 KVA . This governor shall be directly mounted on the engine to enable the speed variation from idling speed to the maximum load speed.
Acoustic Enclosure : This is a special sheet metal fabricated on CNC machine and Powder coated. The enclosure is designed for reducing the sound level to 75 dB (A) (average) all round in green field, as per IS: 8528 Part 10 as per approved CPCB IV norms.
Supply, installation, testing and commissioning silent diesel engine driven generating set of latest Technology as per CPCB-IV Norms of capacity 125 KVA/100KW. at 156BHP capacity water cooled diesel Engine 3 phase 4 wire, 415 Volts, 1500 RPM, 50 Hz AC power supply with power factor 0.8(Lag) coupled directly to alternator mounted on a common base plate on vibration pad complete with fuel tank, battery 12V, - 01 No, including Micro processor based AMF Panel with standard accessories and fittings. The DG set control panel for mounting oil pressure, hours run, emergency stop button, RPM meters, water temperature etc. which are required to check for smooth functioning of DG set during its running period. All other safety provisions shall be provided as per standard OEM specifications of Model No KG1 - 125 WS of KIRLOSKAR make or equivilant in CG/Sudhir complete all as specified and directed.
Diesel engine : Water cooled multi cylinder inline type of mechanical fuel injection diesel engine of capacity 125 KVA/100KW, 156 BHP at 1500 RPM under NTP conditions confirming to IS-100002/ISO8528-1/BS 5514 with an overload capacity of 10% for one hour in any 12 hours, No of cylinders- 04 No,1500 RPM, water cooled naturally turbo charged capable of giving adequate BHP to drive alternator of capable 125 KVA at NTP, Diesel engine of rated speed at full load electric start and including electronic governor control of class A1, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for automatic electric start with 12 V electric starting system for DG set capacity 125 KVA batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/flexible coupling guard complete of Model No 4K1080 TA G2 of KOEL( KIRLOSKAR) Make or equiviliant in CUMMINS/GREAVES COTTON all as specified and directed.
ALTERNATOR : Alternator shall be brush less type,rotating field type synchronous alternator continuously rated for 415 volts, 3 phase, 4 wire, 50 Hz, 0.8 power factor (lagging) at 1500 RPM, under NTP conditions in accordance with IS-4722 & IS-13361, 4 pole, screen protected, dip proof, horizontal foot- mounted type, the degree of protection will be IP-23 enclosure, solid state voltage regulation + 1% self excited, self regulated with static excitation system, One step load acceptance 100% of rating, 'H' Class insulation, 125 Deg C Temperature rise, Sealed type bearing - 01 no, flex disc coupling, 25% of rated amps unbalanced load capability The alternator should be capable for developing rated output and able to take 10% over load for 1 hr every 12 hrs of operation and will be suitable for tropical condition. Alternator Make: KOEL GREEN or equivilant in Stamford/Meccalte all as specified and directed.
Coupling & Mounting Arrangement: (i) The Engine and alternator shall be directly coupled by means of self-aligning flexible flange coupling to avoid misalignment. (ii) The coupling shall be provided with protecting guard to avoid accidental contract
Fuel tank : The tank shall be completed with an outlet, a drain plug, an air vent, an air breather and necessary piping. Fuel tank shall be inside the Acoustic Enclosure etc complete all as specified and directed.
Battery & Battery Charger – 12 V - 1 No Battery complete with all leads shall be provided with DG Set.
Governing System – The Engine shall be supplied with Electronic Governor for DG set rating 125 KVA. This governor shall be directly mounted on the engine to enable the speed variation from idling speed to the maximum load speed.
Acoustic Enclosure : This is made with special sheet metal fabricated on CNC machine and Powder coated. The enclosure is designed for reducing the sound level to 75 dB (A) (average) all round in green field, as per IS: 8528 Part 10 as per approved CPCB IV norms.
Supply, installation, testing and commissioning silent diesel engine driven generating set of latest Technology as per CPCB-IV Norms of capacity 160 KVA/128KW. at 200BHP capacity water cooled diesel Engine 3 phase 4 wire, 415 Volts, 1500 RPM, 50 Hz AC power supply with power factor 0.8(Lag) coupled directly to alternator mounted on a common base plate on vibration pad complete with fuel tank, battery 12V, - 01 No, including Micro processor based AMF Panel with standard accessories and fittings. The DG set control panel for mounting oil pressure, hours run, emergency stop button, RPM meters, water temperature etc. which are required to check for smooth functioning of DG set during its running period. All other safety provisions shall be provided as per standard OEM specifications of Model No KG1 - 160WS of KIRLOSKAR make or equivilant in CG/Sudhir complete all as specified and directed.
Diesel engine : Water cooled diesel engine of capacity 160KVA/128KW, 200 BHP at 1500 RPM under NTP conditions confirming to IS-100002/ISO3046/BS 5514 amended upto date and confirming to (Prime continues rating as per ISO 8528-1) with an overload capacity of 10% for one hour in any 12 hours, No of cylinders- 06 Nos,1500 RPM, water cooled naturally turbo charged capable of giving adequate BHP to drive alternator of capable 160 KVA at NTP, Diesel engine of rated speed at full load electric start and including electronic governor control of class A1, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for automatic electric start with 12 V electric starting system for DG set capacity 160 KVA batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/flexible coupling guard complete of Model No 6K1080 TA G2 of KOEL( KIRLOSKAR) Make or equiviliant in CUMMINS/GREAVES COTTON all as specified and directed.
ALTERNATOR : Alternator shall be brush less type,rotating field type synchronous alternator continuously rated for 415 volts, 3 phase, 4 wire, 50 Hz, 0.8 power factor (lagging) at 1500 RPM, under NTP conditions in accordance with IS-4722 & IS-13361, 4 pole, screen protected, dip proof, horizontal foot- mounted type, the degree of protection will be IP-23 enclosure, solid state voltage regulation + 1% self excited, self regulated with static excitation system, One step load acceptance 100% of rating, 'H' Class insulation, 125 Deg C Temperature rise, Sealed type bearing - 01 no, flex disc coupling, 25% of rated amps unbalanced load capability The alternator should be capable for developing rated output and able to take 10% over load for 1 hr every 12 hrs of operation and will be suitable for tropical condition. Alternator Make KOEL GREEN or equivilant in Stamford/Meccalte all as specified and directed.
Coupling & Mounting Arrangement: (i) The Engine and alternator shall be directly coupled by means of self-aligning flexible flange coupling to avoid misalignment. (ii) The coupling shall be provided with protecting guard to avoid accidental contract
Fuel tank : The tank shall be completed with an outlet, a drain plug, an air vent, an air breather and necessary piping. Fuel tank shall be inside the Acoustic Enclosure etc complete all as specified and directed.
Battery & Battery Charger – 12 V - 1 No Battery complete with all leads shall be provided with DG Set.
Governing System – The Engine shall be supplied with Electronic Governor for DG set rating 160 KVA. This governor shall be directly mounted on the engine to enable the speed variation from idling speed to the maximum load speed.
Acoustic Enclosure : This is made with special sheet metal fabricated on CNC machine and Powder coated. The enclosure is designed for reducing the sound level to 75 dB (A) (average) all round in green field, as per IS: 8528 Part 10 as per approved CPCB IV norms.
Supply, installation, testing and commissioning silent diesel engine driven generating set of latest Technology as per CPCB-IV Norms of capacity 250 KVA/200KW. 310BHP capacity water cooled diesel Engine 3 phase 4 wire, 415 Volts, 1500 RPM, 50 Hz AC power supply with power factor 0.8(Lag) coupled directly to alternator mounted on a common base plate on vibration pad complete with fuel tank, battery 24V, - 02 Nos, including Micro processor based AMF Panel with standard accessories and fittings. The DG set control panel for mounting oil pressure, hours run, emergency stop button, RPM meters, water temperature etc. which are required to check for smooth functioning of DG set during its running period. All other safety provisions shall be provided as per standard OEM specifications of Model No KG1 - 250 WS of KIRLOSKAR make or equivilant in CG/Sudhir complete all as specified and directed.
Diesel engine :Water cooled diesel engine of capacity 250KVA/200KW, 310 BHP at 1500 RPM under NTP conditions confirming to IS-100002/ISO3046/BS 5514 amended upto date and confirming to (Prime continues rating as per ISO 8528-1) with an overload capacity of 10% for one hour in any 12 hours, No of cylinders- 06 No, 1500 RPM, water cooled naturally turbo charged capable of giving adequate BHP to drive alternator of capable 250 KVA at NTP, Diesel engine of rated speed at full load electric start and including electronic governor control of class A1, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for automatic electric start with 24V electric starting system for DG set capacity 250 KVA batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/flexible coupling guard complete of Model No 6SL1500TA of KOEL( KIRLOSKAR) Make or equiviliant in CUMMINS/GREAVES COTTON all as specified and directed.
ALTERNATOR : Alternator shall be brush less type,rotating field type synchronous alternator continuously rated for 415 volts, 3 phase, 4 wire, 50 Hz, 0.8 power factor (lagging) at 1500 RPM, under NTP conditions in accordance with IS-4722 & IS-13361, 4 pole, screen protected, dip proof, horizontal foot- mounted type, the degree of protection will be IP-23 enclosure, solid state voltage regulation + 1% self excited, self regulated with static excitation system, One step load acceptance 100% of rating, 'H' Class insulation, 125 Deg C Temperature rise, Sealed type bearing - 01 no, flex disc coupling, 25% of rated amps unbalanced load capability The alternator should be capable for developing rated output and able to take 10% over load for 1 hr every 12 hrs of operation and will be suitable for tropical condition. Alternator Make: KOEL GREEN or equivilant in Stamford/Meccalte all as specified and directed.
Coupling & Mounting Arrangement: (i) The Engine and alternator shall be directly coupled by means of self-aligning flexible flange coupling to avoid misalignment. (ii) The coupling shall be provided with protecting guard to avoid accidental contract
Fuel tank : The tank shall be completed with an outlet, a drain plug, an air vent, an air breather and necessary piping. Fuel tank shall be inside the Acoustic Enclosure etc complete all as specified and directed.
Battery & Battery Charger – 2 Nos. 24 V Battery complete with all leads shall be provided with DG Set.
Governing System – The Engine shall be supplied with Electronic Governor for DG set rating 250 KVA. This governor shall be directly mounted on the engine to enable the speed variation from idling speed to the maximum load speed.
Acoustic Enclosure : This is made with special sheet metal fabricated on CNC machine and Powder coated. The enclosure is designed for reducing the sound level to 75 dB (A) (average) all round in green field, as per IS: 8528 Part 10 as per approved CPCB IV norms.
M&L for Steel structure movable Trolley suitable for carrying 250 KVA DG set , comprising of attached steel staircase upto platform, 04 nos of tubeless tyres for smooth run including Towing system of Size : 5500MMX3000MM(±10%), weight of Generator set with canopy is 4320 Kgs with maximum pay load 6000 Kgs,10mm thick MS chequared plate for flooring sheet (platform), one coat of primer and two coat of synthetic enamel pait for finishing with tool box and 4 Nos tyres all as specifed and directed
Supplying, installing, commissioning and testing of electrically driven submersible pump set suitable for discharge 360 LPM, 90mtr head, multi stage, 415V AC, 3 phase motor suitable for 200/250mm dia bore well and connecting to existing column pipes of 80mm bore and including taking out existing Submersible pump set from bore with column pipe and lowering the new pump set with motor in existing borewell complete all as directed by the Engineer-in-Charge.
Supply and installation, connecting of star delta starter with single phase preventer, relay range 20-32 Amps , 415V, suitable for 20 HP submersible pump set of model No MU-G20 FASD (With Wideband Coil) of L&T complete all as specified and directed.
M&L for Supplying, installing, commissioning and testing of electrically driven submersible pump set suitable for discharge 480 LPM, 90mtr head, multi stage, 415V AC, 3 phase motor suitable for 200/250mm dia bore well and connecting to existing column pipes of 80mm bore and including taking out existing Submersible pump set from bore with column pipe and lowering the new pump set with motor in existing borewell complete all as directed by the Engineer-in-Charge.
Supply and installation, connecting of star delta starter with single phase preventer relay range 9-14 Amps , 415V, suitable for 15 HP submersible pump set of model No MU-G20 FASD (With Wideband Coil) of L&T complete all as specified and directed.
Supplying, installing, connecting & terminating on site suitable flat PVC Sheathed Industrial 3 Core Flat Submersible Cable with Bare Bunched Copper Conductor for Submersible Pump Motors with Voltage Grade 1100 Volts as per IS:694/2010 complete all as specified and directed.
Taking out LT Cable any type any size from trenches complete all as specified and directed
Supply, laying, jointing and testing XLPE insulated, armoured, heavy duty, aluminium conductor cable 1100 volts grade of any description and any make laid in trenches/ducts, floors, fixed to walls etc size of 16 sqmm 4 core complete all as specified and directed
Supply, laying, jointing and testing XLPE insulated, armoured, heavy duty, aluminium conductor cable 1100 volts grade of any description and any make laid in trenches/ducts, floors, fixed to walls etc size of 70 sqmm 3.5 core complete all as specified and directed
Supply, laying, jointing and testing XLPE insulated, armoured, heavy duty, aluminium conductor cable 1100 volts grade of any description and any make laid in trenches/ducts, floors, fixed to walls etc size of 120 sqmm 3.5 core complete all as specified and directed
Supply, laying, jointing and testing XLPE insulated, armoured, heavy duty, aluminium conductor cable 1100 volts grade of any description and any make laid in trenches/ducts, floors, fixed to walls etc size of 400 sqmm 3.5 core complete all as specified and directed
Supply, laying, jointing and testing XLPE insulated, armoured, heavy duty, aluminium conductor cable 1100 volts grade of any description and any make laid in trenches/ducts, floors, fixed to walls etc size of 630 sqmm 3.5 core complete all as specified and directed
Excavation in trenches in soft & loose soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes etc. all as specified and directed by Engineer-in-Charge including removing cable protection PCC covers/ bricks & stacking serviceable covers / bricks for reuse and disposal of unserviceable covers within 50 m all as specified and directed. Note : Excavation shall be made carefully in order to avoid damage of existing cables and protection covers.
Returning, filling in including spreading, leveling, watering and well ramming in layers of 25 cm thick after the cables etc. are laid, jointed & tested complete all as specified and directed
Removal of surplus excavated soil exc. 50 mtr but n. exc. 250 mtr distance and depositing where directed by Engineer-in-Charge at a level not exceeding 1.5 M above the starting point etc complete all as directed.
M & L for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed . NOTE: - Punned thickness shall be measurement & paid.
Supplying & Laying Sub Class `B’ bricks old size with axis of the bricks perpendicular to the axis of the cable as in cable protection all as specified and directed
M & L for earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically to a depth not less than 2.25 mtr deep below GL with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to earth lead of GI strip 32x6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel and thimbles and other end of the earth lead connected to Plant/equipment and protected by galvanized iron or steel pipe light grade and water pipe 20mm bore GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of 2009 and also including making test point for testing of earthing made out of gun metal or phosphorous bronze size 75x75x25 mm complete . Note : On testing after completion of earthing if desired earth resistance below 5 ohms is not achieved, the earthing will be redone at no extra cost.
M P TYAGI ENGINEERS AND CONTRACTORS
R D Bansal
RAVINDRA BROTHERS
GUPTA ENGINEERING WORKS
M/s M.S. Electric Co.
M/s Kohli Builders
Vijaypower Generators Limited
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .