Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance UDHAMPUR | Admitted-Finance |
| 3 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹34,500
Closing Date
10 Jan 2022, 4:00 pmClosed
Executive Engineer
Electric Division JPDCL Udhampur
Creation of Substation alongwith HT LT Line
2021_PDD_150664_1
ED/UDH/57 of 2021-22 dt. 30-11-2021
Open Tender
Electrical Works
Turn-key
60 days
At AFS Sattani Dhar Road and Village Balay Rathian
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Engineer Electrci Division JPDCL
₹34,500
15 Jan 2022
30 Nov 2021
12 Jan 2022
30 Nov 2021
10 Jan 2022
30 Nov 2021
30 Nov 2021 - 7 Dec 2021
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for creation of 100 KVA Sub Station at AFS Sattani Dhar Road Udhampur of Sh. Sushil Kumar Online Grievance.
11/0.433kV, 3-phase 100 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
120 mm² Single-Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
LT Distribution box for 100 KVA DTR with MCCB for incomer and SFU's for outgoing circuits.
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Cement bottoming of ST poles in 1:2:4 mix as per REC standards
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Painting of sub station ST poles/cross arms/clamps with one coat of Red oxide and two coats of aluminium paint
Danger Plates with Clamps
Anti- Climbing Device with Clamps
3-Ø, 4 wire Prodigy meter
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line 3 phase 4 wire on 8 mtr long ST poles at AFS Sattani Dhar Road.
8 mtr. Long ST Pole (ST-410 SP15)
9 mtr. Long ST Pole (ST-410 SP33)
GI M-Clamp for shackle insulator
0.03 ACSR Conductor Weasel.
16kN Shackle Insulators
Galvinized Nuts and Bolts.
Danger Plates with Clamps
Anti- Climbing Device with Clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 32X3 mm for LT
Painting of 8/9 mtr ST poles including crossarms/clamps with one coat of Red oxide Paint.
Painting of 8/9 mtr ST poles including crossarms/clamps with two coat of Aluminium Paint.
LT line spacers
Fixing of LT ABC Cable 120 sq. mm including all Accessories (3X120 Sq. mm + 1X70 Sq. mm) (PROVIDED BY PDD DEPARTMENT)
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr long ST poles at Baley Rathian, Udhampur.
9 mtr. Long ST Pole (ST-410 SP33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
0.03 ACSR Weasel conductor
PG Clamps for 50 mm² ACSR Conductor.
11KV Pin Insulator (Polymeric) with Pins (12kv, 5KN) Creepage Distance 320mm
11KV Disc Insulators (Polymeric 45KN ) creepage distance 320 mm with tension fittings
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti- Climbing Device with Clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 32X3 mm for LT
Painting of 9 mtr ST poles including crossarms/clamps with one coat of Red oxide Paint.
Painting of 9 mtr ST poles including crossarms/clamps with two coat of Aluminium Paint.
Cement bottoming of ST poles in 1:2:4 mix as per REC standards
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for creation of 25 KVA Sub Station at village Baley Rathian.
11/0.433kV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
70 mm² Single-Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
LT Distribution box for 25 KVA DTR with MCCB for incomer and SFU's for outgoing circuits.
Cement bottoming of ST poles in 1:2:4 mix as per REC standards
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Painting of sub station ST poles/cross arms/clamps with one coat of Red oxide and two coats of aluminium paint
Danger Plates with Clamps
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long ST poles atBaley Rathian udhampur.
8 mtr. Long ST Pole (ST-410 SP15)
GI M-Clamp for shackle insulator
0.03 ACSR Conductor Weasel.
16kN Shackle Insulators
Galvinized Nuts and Bolts.
Danger Plates with Clamps
Anti- Climbing Device with Clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 32X3 mm for LT
Painting of 8 mtr ST poles including crossarms/clamps with one coat of Red oxide Paint.
Painting of 8 mtr ST poles including crossarms/clamps with two coat of Aluminium Paint.
LT line spacers
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
AJAY KAPOOR
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .