| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.6 LAccepted-AOC PLOT NO 16 INDUSTRIAL AREA PHASE I MANDI H P 175001 | MANDI | HIMACHAL PRADESH | 175001 | ₹3.6 L | L1 | Accepted-AOC lowest |
| 2 | L2₹3.8 L+₹19,710 (5.47%)Rejected-AOC CHOBATA STREET MANDI DISTT MANDI HP | MANDI | HIMACHAL PRADESH | 175001 | ₹3.8 L+₹19,710 (5.47%) | L2 | Rejected-AOC 2nd lowest |
| 3 | L3₹3.9 L+₹26,280 (7.29%)Rejected-AOC 82 10 POST OFFICE ROAD MANDI HP | KANGRA | HIMACHAL PRADESH | 175013 | ₹3.9 L+₹26,280 (7.29%) | L3 | Rejected-AOC 3rd lowest |
| 4 | L4₹4.2 L+₹59,130 (16.4%)Rejected-AOC 00 BHUSAR FARM KE PASS K K PURI NANDANPURA JHANSI UTTAR PRADESH 284003 | JHANSI | UTTAR PRADESH | 284003 | ₹4.2 L+₹59,130 (16.4%) | L4 | Rejected-AOC highest |
Tender Value
₹3.6 L
EMD Value
₹3,650
Closing Date
19 Aug 2026, 11:30 amClosed
Addl. Suprintending Engineer
HPSEBL ,Division Rampur
restoration by providing and fixing of damaged LT panel box
2026_HPSEB_141031_1
EDRMP/Db-Ten/2026-27-1581-85 dated 12/08/2026
Open Tender
Electrical Works
Percentage
90 days
rampur (indra market)
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
₹3,650
5 Sept 2026
12 Aug 2026
19 Aug 2026
12 Aug 2026
19 Aug 2026
12 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Tender for design, manufacturing, testing at work, supply, delivery, storage, preservations, assembly and commissioning of 415 volt AC 50 HZ, LT distribution panel of size 2000x1500x900mm or adjustable out door type, double door protection totally metal clad made of steel sheet of 1.63mm thickness duly powder quoted having 1 No.-1000 Amp. ACB fixed type L&T/heavells or equivalent make breaking capacity not less then 50 kA with adjustable over current earth fault protection and also to make confirming to latest version of ISI-2516 (Part-I&II) 385 for latest version thereof. Rectangular type alluminum alloy bus bar of 2000Amp. Having length not less than 800mm phase 600mm neutral and protective for 3No. outgoing feeders shall be made in panel 3No. MCCBs of 400Amp. 3No. with MCCB of 250Amp. Breaking capacity not less then 50 /36 kA L&T/Heavells or equivalent make shall be provided and digital Voltmeter and Amp. meter along with indicator shall be provided. The completed unit is to be housed in cubical panel having duble door with locking arrangment and properly made of MS angle 50x50x6mm. The panel shall be fully wired with insulated copper wire and shall have adequate clearance as per standard specification. | 1 | job | 3,65,000 | ₹3,65,000 |
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.04 MB
BOQ_209316.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .