Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.4 CrAccepted-AOC 261 BHARAT NAGAR BATHINDA PB 151001 | BATHINDA | BATHINDA | PUNJAB | 151001 | ₹2.4 Cr | L1 | Accepted-AOC Being L1 |
| 2 | L2₹2.4 CrRejected-Finance | ₹2.4 Cr | L2 | Rejected-Finance Other than L1 |
| 3 | L3₹2.7 CrRejected-Finance | ₹2.7 Cr | L3 | Rejected-Finance Other than L1 |
| 4 | Rejected-Technical | - | - | Rejected-Technical Not approved |
| Sl No | Description | Qty | Unit | V S BUILDER L3 | Surindera Kumar Bansal L1 | M/s NIRMAN BUILDERS L2 |
|---|---|---|---|---|---|---|
| 1.00 | S&F in replacement centrifugal Pump Set of 75000GPH and 40 mtr Head Primary pump house :-
Usage: Water Requirement
Pump Model- UP 150/38A,Stages 1,Type - Horizontal Split Casing (Gland Packing fitted);
1475 rpm(Approx.),Suction size: 200 mm and Delivery size: 150 mm;
Material of Construction:
Casing: CI IS210:FG260 (012);
Impeller: ST ST ASTM A351/M-CF8M (232);
Shaft: ST ST ASTM A276-410 ANLD (253);
KPML Motor- 45 KW/ 4P / 415V/TEFC/F/IE3 with below scope of supply
Coupling + Coupling Guard Baseplate as directed
Note :- The Quotated rate shall include construction of RCC plinth Reccomnded by OEM. | 2 | Each | 6,00,000 ₹12 L | 5,95,000 ₹11.9 L | 4,80,000 ₹9.6 L |
| 2.00 | S&F in replacement centrifugal Pump Set of 75000GPH and 60 mtr Head Secondary Pump House:-
Pump Model- UP 150/45,Stages 1,Type - Horizontal Split Casing (Gland Packing fitted);
1480 rpm(Approx.),Suction size: 200 mm and Delivery size: 150 mm;
Material of Construction:
Casing: CI IS210:FG260 (012);
Impeller: ST ST ASTM A351/M-CF8M (232);
Shaft: ST ST ASTM A276-410 ANLD (253);
KPML Motor- 75 KW/ 4P / 415V/TEFC/F/IE3 with below scope of supply
Coupling + Coupling Guard Baseplat as directed .
Note :- The Quotated rate shall include construction of RCC plinth Reccomnded by OEM. | 2 | Each | 7,20,000 ₹14.4 L | 7,85,000 ₹15.7 L | 5,80,000 ₹11.6 L |
| 3.00 | S&F in replacement centrifugal Pump Set of 72LPS and 37 mtr Head: Location :- Golf
Pump Model- UP 125/35,Stages 1,Type - Horizontal Split Casing (Gland Packing fitted);
1475 rpm(Approx.),Suction size: 150 mm and Delivery size: 125 mm;
Material of Construction:
Casing: CI IS210:FG260 (012);
Impeller: ST ST ASTM A351/M-CF8M (232);
Shaft: ST ST ASTM A276-410 ANLD (253);
KPML Motor- 37 KW/ 4P / 415V/TEFC/F/IE3 with below scope of supply
Coupling + Coupling Guard Baseplat as directed .
Note :- The Quotated rate shall include construction of RCC plinth Reccomnded by OEM. | 1 | Each | 4,50,000 ₹4.5 L | 4,90,000 ₹4.9 L | 3,75,000 ₹3.8 L |
| 4.00 | S&F in replacement Motor Secondary Pump House KPML Motor- 90 KW/ 4P / 415V/TEFC/IE3/1450 RPM. as directed. | 1 | Each | 4,50,000 ₹4.5 L | 4,50,000 ₹4.5 L | 3,30,000 ₹3.3 L |
| 5.00 | S&F in replacement centrifugal Pump Set of 15.5LPS and 58 mtr Head Primary pump house :-
Usage: Water Requirement
Pump Model- DSM 65/32A,Stages 2,Type - Horizontal Split Casing (Gland Packing fitted);
1465 rpm(Approx.),Suction size: 80 mm and Delivery size: 65 mm;
Material of Construction:
Casing: CI IS210:FG260 (012);
Impeller: ST ST ASTM A351/M-CF8M (232);
Shaft: ST ST ASTM A276-410 ANLD (253);
KPML Motor- 18.5 KW/ 4P / 415V/TEFC/F/IE3 with below scope of supply
Coupling + Coupling Guard Baseplate as directed .
Note :- The Quotated rate shall include construction of RCC plinth Reccomnded by OEM. | 1 | Each | 3,50,000 ₹3.5 L | 3,65,000 ₹3.6 L | 2,31,000 ₹2.3 L |
| 6.00 | Excavation in trenches, not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for pipe line etc. not exceeding 10 sqm area on plan and not exceeding 1.5 metre in depth and getting out in soft / loose soil complete all as specified. | 504 | Cum | 90 ₹45,360 | 150 ₹75,600 | 80 ₹40,320 |
| 7.00 | Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm thick complete all as specified. | 453.6 | Cum | 50 ₹22,680 | 70 ₹31,752 | 10 ₹4,536 |
| 8.00 | Removing excavated soil to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified. | 50.4 | Cum | 50 ₹2,520 | 70 ₹3,528 | 10 ₹504 |
| 9.00 | Taking out from trenchs / from under roads/ceiling/walls existing old unservicable HDPE/PVC /GI pipe 50 mm bore and connections including all fittings complete all as specified and as directed.Excavation and earth work shall be measured & paid separately under respective items of schedule of works. | 1,000 | RM | 40 ₹40,000 | 40 ₹40,000 | 10 ₹10,000 |
| 10.00 | Taking out from trenchs / from under roads/ceiling/walls existing old unservicable HDPE/PVC /GI pipe 25 mm bore and connections including all fittings complete all as specified and as directed.Excavation and earth work shall be measured & paid separately under respective items of schedule of works. | 3,500 | RM | 30 ₹1.1 L | 35 ₹1.2 L | 10 ₹35,000 |
Updated dates
Tender Value
₹2.5 Cr
EMD Value
₹3.2 L
Closing Date
24 Mar 2026, 6:00 pmClosed
Chief Engineer Bathinda zone
HQ CE Bathinda Zone, Bathinda Mil Stn-151004
REPAIR/MAINT TO SLUICE VALVE, NRV, CLEANING OF UG SUMP AND OH TANK, CENTRIFUGAL PUMP REPLACEMENT, EXTERNAL WATER SUPPLY PIPELINE AND ACCESSORIES UNDER GE (U) BATHINDA
2026_MES_753194_1
84563 CE BTZ/BTD/TOKEN-69 OF 2025-26
Open Tender
Civil Works
180 days
GE (U) Bathinda
As per NIT
8 documents required · 8 mandatory
₹2,000
GE (U) Bathinda
₹3.2 L
Yes
9 Apr 2026
18 Feb 2026
26 Mar 2026
18 Feb 2026
24 Mar 2026
11 Mar 2026
S&F in replacement centrifugal Pump Set of 75000GPH and 40 mtr Head Primary pump house :- Usage: Water Requirement Pump Model- UP 150/38A,Stages 1,Type - Horizontal Split Casing (Gland Packing fitted); 1475 rpm(Approx.),Suction size: 200 mm and Delivery size: 150 mm; Material of Construction: Casing: CI IS210:FG260 (012); Impeller: ST ST ASTM A351/M-CF8M (232); Shaft: ST ST ASTM A276-410 ANLD (253); KPML Motor- 45 KW/ 4P / 415V/TEFC/F/IE3 with below scope of supply Coupling + Coupling Guard Baseplate as directed Note :- The Quotated rate shall include construction of RCC plinth Reccomnded by OEM.
S&F in replacement centrifugal Pump Set of 75000GPH and 60 mtr Head Secondary Pump House:- Pump Model- UP 150/45,Stages 1,Type - Horizontal Split Casing (Gland Packing fitted); 1480 rpm(Approx.),Suction size: 200 mm and Delivery size: 150 mm; Material of Construction: Casing: CI IS210:FG260 (012); Impeller: ST ST ASTM A351/M-CF8M (232); Shaft: ST ST ASTM A276-410 ANLD (253); KPML Motor- 75 KW/ 4P / 415V/TEFC/F/IE3 with below scope of supply Coupling + Coupling Guard Baseplat as directed . Note :- The Quotated rate shall include construction of RCC plinth Reccomnded by OEM.
S&F in replacement centrifugal Pump Set of 72LPS and 37 mtr Head: Location :- Golf Pump Model- UP 125/35,Stages 1,Type - Horizontal Split Casing (Gland Packing fitted); 1475 rpm(Approx.),Suction size: 150 mm and Delivery size: 125 mm; Material of Construction: Casing: CI IS210:FG260 (012); Impeller: ST ST ASTM A351/M-CF8M (232); Shaft: ST ST ASTM A276-410 ANLD (253); KPML Motor- 37 KW/ 4P / 415V/TEFC/F/IE3 with below scope of supply Coupling + Coupling Guard Baseplat as directed . Note :- The Quotated rate shall include construction of RCC plinth Reccomnded by OEM.
S&F in replacement Motor Secondary Pump House KPML Motor- 90 KW/ 4P / 415V/TEFC/IE3/1450 RPM. as directed.
S&F in replacement centrifugal Pump Set of 15.5LPS and 58 mtr Head Primary pump house :- Usage: Water Requirement Pump Model- DSM 65/32A,Stages 2,Type - Horizontal Split Casing (Gland Packing fitted); 1465 rpm(Approx.),Suction size: 80 mm and Delivery size: 65 mm; Material of Construction: Casing: CI IS210:FG260 (012); Impeller: ST ST ASTM A351/M-CF8M (232); Shaft: ST ST ASTM A276-410 ANLD (253); KPML Motor- 18.5 KW/ 4P / 415V/TEFC/F/IE3 with below scope of supply Coupling + Coupling Guard Baseplate as directed . Note :- The Quotated rate shall include construction of RCC plinth Reccomnded by OEM.
Excavation in trenches, not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for pipe line etc. not exceeding 10 sqm area on plan and not exceeding 1.5 metre in depth and getting out in soft / loose soil complete all as specified.
Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm thick complete all as specified.
Removing excavated soil to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified.
Supply and fixing in repairs Gun metal gate valve with locking device and open shut indicator for 50 mm bore iron pipe , with iron wheel head, screwed both ends conforming to IS 778 - 1984 complete all as specified and directed.
Supply and fixing in repairs Gun metal gate valve with locking device and open shut indicator for 25 mm bore iron pipe , with iron wheel head, screwed both ends conforming to IS 778 - 1984 complete all as specified and directed.
Supply and fixing in repairs Gun metal gate valve with locking device and open shut indicator for 20 mm bore iron pipe , with iron wheel head, screwed both ends conforming to IS 778 - 1984 complete all as specified and directed.
Material and Labour Construction of valve pit Type 'B' of size 75 cm x 75 cm x 75 cm ( internal dimension ) of brick masonry laid with cement mortar (1:4). from the top of surface including cover of MS sheet 3.15 mm thick and angle iron 50mm x 50mm x 6mm with hinges, handle and locking arrangement including painting with two coat of synthetic enamelled paint over a coat of red oxide and grouting to PCC 1:2:4 type B-1, using 20mm graded crushed stone aggregates , Rendering 15mm thick in cement mortar 1:3, including three coats of white wash on internal surfaces and external exposed surfaces , foundation concrete 1:3:6 type C-2 using 40mm graded crushed stone aggregates including necessary earthwork , returning filling , removal complete all as specified and shown on drawings.Note : Applicable drawing for valve pit is Drawing No. BTD-811 sheet 1/2 to 2/2
Supply and fixing in repair 600 mm dia flanged sluice valve , ISI marked PN 1.0 confirming to IS-14846-2000, both end flanged ,drilled , steel spindle and iron wheel handle , CI gate with MS ring including jointing material such as nuts, bolts, washers and rubber sheet complete all directed.
Supply and fixing in repair 500 mm dia flanged sluice valve , ISI marked PN 1.0 confirming to IS-14846-2000, both end flanged ,drilled , steel spindle and iron wheel handle , CI gate with MS ring including jointing material such as nuts, bolts, washers and rubber sheet complete all directed.
Supply and fixing in repair 450 mm dia flanged sluice valve , ISI marked PN 1.0 confirming to IS-14846-2000, both end flanged ,drilled , steel spindle and iron wheel handle , CI gate with MS ring including jointing material such as nuts, bolts, washers and rubber sheet complete all directed.
Supply and fixing in repair 350 mm dia flanged sluice valve , ISI marked PN 1.0 confirming to IS-14846-2000, both end flanged ,drilled , steel spindle and iron wheel handle , CI gate with MS ring including jointing material such as nuts, bolts, washers and rubber sheet complete all directed.
Supply and fixing in repair 300 mm dia flanged sluice valve , ISI marked PN 1.0 with PAD LOCK confirming to IS-14846-2000, both end flanged ,drilled , steel spindle and with iron wheel handle , CI gate with MS ring including jointing material such as nuts, bolts, washers and rubber sheet complete all directed.
Supply and fixing in repair 250 mm dia flanged sluice valve , ISI marked PN 1.0 with PAD LOCK confirming to IS-14846-2000, both end flanged ,drilled , steel spindle and with iron wheel handle , CI gate with MS ring including jointing material such as nuts, bolts, washers and rubber sheet complete all directed.
Supply and fixing in repair 200 mm dia flanged sluice valve , ISI marked PN 1.0 with PAD LOCK confirming to IS-14846-2000, both end flanged ,drilled , steel spindle and with iron wheel handle , CI gate with MS ring including jointing material such as nuts, bolts, washers and rubber sheet complete all directed.
Supply and fixing in repair 150 mm dia flanged sluice valve , ISI marked PN 1.0 with PAD LOCK confirming to IS-14846-2000, both end flanged ,drilled , steel spindle and with iron wheel handle , CI gate with MS ring including jointing material such as nuts, bolts, washers and rubber sheet complete all directed.
Supply and fixing in repair 100 mm dia flanged sluice valve , ISI marked PN 1.0 with PAD LOCK confirming to IS-14846-2000, both end flanged ,drilled , steel spindle and with iron wheel handle , CI gate with MS ring including jointing material such as nuts, bolts, washers and rubber sheet complete all directed.
S&F in repair 200 mm dia foot valve BALL TYPE , ISI marked confirming to IS-4038, flanged and drilled with MS ring including jointing material such as nuts, bolts, washers and rubber sheet etc complete all directed by Engr-in-Charge.
S&F in repair 150 mm dia foot valve BALL TYPE , ISI marked confirming to IS-4038, flanged and drilled with MS ring including jointing material such as nuts, bolts, washers and rubber sheet etc complete all directed by Engr-in-Charge.
S&F in repair 250 mm dia Cast Iron non return valve , PN1.6 ISI marked confirming to IS-5312-2004, both end flanged drilled complete with MS ring and rubber flap plate including jointing material such as nuts, bolts, washers and rubber sheet etc complete all as directed by Engr-in-Charge.
S&F in repair 200 mm dia Cast Iron non return valve , PN1.6 ISI marked confirming to IS-5312-2004, both end flanged drilled complete with MS ring and rubber flap plate including jointing material such as nuts, bolts, washers and rubber sheet etc complete all as directed by Engr-in-Charge.
S&F in repair 150 mm dia Cast Iron non return valve , PN1.6 ISI marked confirming to IS-5312-2004, both end flanged drilled complete with MS ring and rubber flap plate including jointing material such as nuts, bolts, washers and rubber sheet etc complete all as directed by Engr-in-Charge.
S&F in repair 100 mm dia Cast Iron non return valve , PN1.6 ISI marked confirming to IS-5312-2004, both end flanged drilled complete with MS ring and rubber flap plate including jointing material such as nuts, bolts, washers and rubber sheet etc complete all as directed by Engr-in-Charge.
S&F in repair 80 mm dia Cast Iron non return valve , PN1.6 ISI marked confirming to IS-5312-2004, both end flanged drilled complete with MS ring and rubber flap plate including jointing material such as nuts, bolts, washers and rubber sheet etc complete all as directed by Engr-in-Charge.
S&F in replacement Ductile Iron Dual Plate Wafer Type Check Valve, PN 16 for size 200mm Test Pressure (Hydrostatic) : Shell : 24 bar Seat : 17.6 bar Maximum Working Temperature : -18°C to 80°c Body Ductile Iron IS 1865 Gr. 400 / 15 ,Body Lining Nitrile Rubber IS 5192 – 1,Flap / Disc Stainless Steel / Bronze ASTM A 351 Gr. CF8,Hinge Pin Stainless Steel ASTM A 276 Type 304,Stop Pin Stainless Steel ASTM A 276 Type 304,Spring Stainless Steel Type 304, Packing Washer PTFE,Packing Washer Nitrile Rubber IS : 5192-1,Retainer Plug Carbon Steel as directed
S&F in replacement Ductile Iron Dual Plate Wafer Type Check Valve, PN 16 for size 150mm Test Pressure (Hydrostatic) : Shell : 24 bar Seat : 17.6 bar Maximum Working Temperature : -18°C to 80°c Body Ductile Iron IS 1865 Gr. 400 / 15 ,Body Lining Nitrile Rubber IS 5192 – 1,Flap / Disc Stainless Steel / Bronze ASTM A 351 Gr. CF8,Hinge Pin Stainless Steel ASTM A 276 Type 304,Stop Pin Stainless Steel ASTM A 276 Type 304,Spring Stainless Steel Type 304, Packing Washer PTFE,Packing Washer Nitrile Rubber IS : 5192-1,Retainer Plug Carbon Steel as directed
S&F in replacement Ductile Iron Dual Plate Wafer Type Check Valve, PN 16 for size 100mm Test Pressure (Hydrostatic) : Shell : 24 bar Seat : 17.6 bar Maximum Working Temperature : -18°C to 80°c Body Ductile Iron IS 1865 Gr. 400 / 15 ,Body Lining Nitrile Rubber IS 5192 – 1,Flap / Disc Stainless Steel / Bronze ASTM A 351 Gr. CF8,Hinge Pin Stainless Steel ASTM A 276 Type 304,Stop Pin Stainless Steel ASTM A 276 Type 304,Spring Stainless Steel Type 304, Packing Washer PTFE,Packing Washer Nitrile Rubber IS : 5192-1,Retainer Plug Carbon Steel as directed
S&F in replacement of Pipe cast Iron both ends flanged and drilled, including specials ,gaskit and nut bolts ,Class "B" ,200 mm (8") dia. as directed.NOTE:- The Pipe shall connected to Suction side of pumps at Pump House including all accessories and T&P as directed
S&F in replacement of Pipe cast Iron both ends flanged and drilled, including specials ,gaskit and nut bolts ,Class "B" ,250 mm (10") dia. as directed.NOTE:- The Pipe shall connected to Suction side of pumps at Pump House including all accessories and T&P as directed
S&F in replacement of Pipe cast Iron both ends flanged and drilled, including specials ,gaskit and nut bolts,Class "B" ,150 mm (6") dia. as directed.NOTE:- The Pipe shall connected to Suction side of pumps at Pump House including all accessories and T&P as directed
S&F in replacement of Pipe cast Iron both ends flanged and drilled, including specials ,gaskit and nut bolts ,Class "B" ,100 mm (4") dia. as directed.NOTE:- The Pipe shall connected to Suction side of pumps at Pump House including all accessories and T&P as directed
Dewatering/bailing out muddy staganated water manually or with the help of non clogging pumping set from Sludge tank of size 27 X 27 metres at top and 8 x 8 meters at bottom 3 mtr deep, Removing silt from Sludge tank manually by bucket and rope depth exceeding 4.0 mtr but not exceeding 6 mtr and depositing where directed by Engr-in- Charge at a distance exe 50 mtr away from outer wall of installation.Cutting existing bushes/herbs/unwanted plants, Scrapping out silt, algae etc from side walls and floor by washing, cleaning the same with steel wire brush ,brooming etc and washing the side walls with bleaching powder solution and washing again with clear water after washing with bleaching powder to entire satisfaction of Eng-in-Charge complete all as directed by Eng-in-Charge. Note : Contractor shall provide all necessary arrangements such as Lighting , Non clog Pumps,ladder etc and will make good to disturbed surface with out any extra cost to the department on this account.
Draining out of water from RCC overhead reservoir staging 21 meter, upto 1 lakh gallon capacity as per direction of engineer-in-charge and after draining, High pressure water jets shall be used to blast waste material from the inside of tanks, including the top, sides, and surface. scrapping the bottom and upper surface and side walls of reservoir inner surfaces by high pressure jet machine, removal of sludge/mud/silt and other foreign material from the tank and final wash with concentrated bleaching powder and water solution and disposal of collected sludge/mud material to outside the tank through wash out pipe complete all as specified and as directed by Engineer-in-Charge.Note:- 1) The rate quoted by the tenderer is including the cost of labour insurance and other safety precautions etc. 2) The cost of high pressure jet machine shall be provided by contractor .
Draining out of water from RCC overhead reservoir staging 21 meter, exceeding 1 lakh gallon and upto 2 lakh gallon capacity as per direction of engineer-in-charge and after draining, High pressure water jets shall be used to blast waste material from the inside of tanks, including the top, sides, and surface. scrapping the bottom and upper surface and side walls of reservoir inner surfaces by high pressure jet machine, removal of sludge/mud/silt and other foreign material from the tank and final wash with concentrated bleaching powder and water solution and disposal of collected sludge/mud material to outside the tank through wash out pipe complete all as specified and as directed by Engineer-in-Charge.Note:- 1) The rate quoted by the tenderer is including the cost of labour insurance and other safety precautions etc. 2) The cost of high pressure jet machine shall be provided by contractor .
Draining out of water from RCC overhead reservoir staging 21 meter, exceeding 2 lakh gallon capacity as per direction of engineer-in-charge and after draining, High pressure water jets shall be used to blast waste material from the inside of tanks, including the top, sides, and surface. scrapping the bottom and upper surface and side walls of reservoir inner surfaces by high pressure jet machine, removal of sludge/mud/silt and other foreign material from the tank and final wash with concentrated bleaching powder and water solution and disposal of collected sludge/mud material to outside the tank through wash out pipe complete all as specified and as directed by Engineer-in-Charge.Note:- 1) The rate quoted by the tenderer is including the cost of labour insurance and other safety precautions etc. 2) The cost of high pressure jet machine shall be provided by contractor .
Dewatering/bailing out muddy staganated water manually or with the help of non clogging pumping set from clear water Under ground sump of cap of 4 LG and upto 8 LG including jeckwell Removing silt from under ground sump manually by bucket and rope depth 4.0 mtr but not exe 6 mtr and depositing where directed by Eng-in- Charge at a distance exe 50 mtr away from outer wall of installation,High pressure water jets shall be used to blast waste material from the inside of tanks, including the top, sides, and surface. Scrapping out silt, alge etc from side walls , roofand floor by washing, cleaning the same with steel wire brush ,brooming etc and washing the side walls with bleaching powder solution and washing again with clear water after washing with bleaching powder and white washing with two coats of white wash to entire satisfaction complete all as specified and directed by Eng-in-Charge. Note : Contractor should provide all necessary arrangements such as Lighting , Non clog Pumps,ladder etc and will make good to disturbed surface no extra cost will be paid on this account,The high pressure jet machine will provided by contractor .
All as above item above but from Under ground sump of cap exceeding 1 LG and upto 2 LG Note : Contractor should provide all necessary arrangements such as Lighting , Non clog Pumps,ladder etc and will make good to disturbed surface no extra cost will be paid on this account,The high pressure jet machine will provided by contractor .
All as above item above but from Under ground sump of cap upto 1.0 LG Note : Contractor should provide all necessary arrangements such as Lighting , Non clog Pumps,ladder etc and will make good to disturbed surface no extra cost will be paid on this account,The high pressure jet machine will provided by contractor .
S&F in replacement Rotational moulded poly-ethylene three water storage tanks (cylinderical vertical with closed top) 1000 litres capacity,hoisted and fixed in position with and including all fittings and fixtures complete all as specified and directed.NOTE:- The Quotated rate also includes rate of fittings and football.
Supply only oil imeressed graphite gland packing off sizes of superior quality complete all as directed. Make - Champion or equivalent as approved by GE
MS work (Preparation of Gate/ fancing) as in plate form/Frame, clamps/base frames made out of angle etc complete including cutting welding riveting, locking arrangement and applying two coat of synthetic enamel paint over a coat of red oxide primer on exposed surfaces complete all as directed by Engineer-in-charge.
Cutting /Cleaning away all grass,bushes,under growth small tree roots,hedges,vegetation, branches of trees etc at installation of water supply up to entire satisfaction of Engineer -in-charge and disposing the same at a distance upto 50 mtr away from the prepherial area under clearence complete all as directed by Engineer-in -charge.
Dismantling the air blower of any capacity, 1440RPM, reciprocating type from the foundation and drain of comressor oil carefully and disconnecting electric motor connection and earthing etc and transportation to civil workshop for repair, opening the air blower and removing of defective piston rings, bearings and cleaning of piston and boring of cylinder if required and reassembling the complete air blower after replacement of bearing and piston rings and comressor oil and re-fixing at site and reassebmling with electric motor, earthing and testing the air blower on full load at site up to entire satisfaction of Engineer-in-charge.
S&F in repair replacement of 3 phase electric motor 3HP for clariflauculator at primary pump house asper existing on site as directed.
S&F of Horizontal Openwell Submersible Pump, JOS ULTRA-540, 5 HP, Three Phase, 380 Volts, Size 65mm X 50mm fountain as directed
S&F in Borewell Submersible Pump, KP4 JALRAAJ UVA 60-1010, 1 HP, Single Phase, 220 Volts, Size 32mm with control panel as directed
S&F in Pressure Boosting Pump, K-Booster, 0.5 HP, Single Phase, 220 Volts, Size 25mm X 25mm as directed
S&F of Monobloc Pump, KDI-515 EE5, 5HP, Three Phase, 415 Volts, Size 100 mm X 100mm as direted
S&F of Monobloc Pump, KDI-216 EE2, 2 HP, Three Phase, 415 Volts, Size 65mm X 50mm as direted
S&F in Openwell Submersible Pump, KOSi -135, 1 HP, Single Phase, 210 Volts, Size 25mm X 25mm with Control Paneldirected
M&L in replacement direct on line (DOL) starter in sheet metal enclosure type, 415 Volt, 3 Phase, suitable for and upto 5 HP electric motor complete all as specified and as directed by Engineer-in-charge.
M&L in replacement direct on line (DOL) starter in sheet metal enclosure type, 415 Volt, 3 Phase, suitable for and upto 7.5 HP electric motor complete all as specified and as directed by Engineer-in-charge.
M&L in replacement direct on line (DOL) starter in sheet metal enclosure type, 415 Volt, MK-1 suitable for and upto 3 HP electric motor complete all as specified and as directed by Engineer-in-charge.
M&L in replacement direct on line (DOL) starter in sheet metal enclosure type, Single phase 240 Volt, MK-1 suitable for and upto 3 HP electric motor complete all as specified and as directed by Engineer-in-charge.
M&L in replacement star delta starter in sheet metal enclosure type, 415 Volt, 3 Phase, suitable for and upto 10 HP electric motor complete all as specified and as directed by Engineer-in-charge.
M&L in replacement ML2 FASD, Fully Automatic Star Delta Starter - 20 HP | Relay Range 13-21A | 360V AC | with MU Relayfor electric motor complete all as specified and as directed by Engineer-in-charge.
M&L in replacement ML1.5 FASD, Fully Automatic Star Delta Starter - 25 HP | Relay Range 20-32A | 360V AC for electric motor complete all as specified and as directed by Engineer-in-charge.
M&L in replacement of starter for 1 hp submersible pump complete all as specified and as directed by Engineer-in-charge.
M&L in replacement 16 sqmm three core PVC 1100 V confirming to IS:694 insulated industrial grade copper conductor (sheathed) flexible cable including copper thimble complete all as specified and as directed by Engineer-in-charge.
M&L in replacement flate 6 sqmm three core PVC 1100 V confirming to IS:694 insulated industrial grade copper conductor (sheathed) flexible cable including copper thimble complete all as specified and as directed by Engineer-in-charge.
M&L in replacement 4 sqmm three core PVC 1100 V confirming to IS:694 insulated industrial grade copper conductor (sheathed) flexible cable including copper complete all as specified and as directed by Engineer-in-charge.
M&L in replacement 95 sqmm three core PVC 1100 V confirming to IS:694 insulated industrial grade copper conductor (sheathed) flexible cable including copper complete all as specified and as directed by Engineer-in-charge.
M&L in replacement 50 sqmm three core PVC 1100 V confirming to IS:694 insulated industrial grade copper conductor (sheathed) flexible cable including copper complete all as specified and as directed by Engineer-in-charge.
M&L in replacement power contactor 415 volt, 50 cycles, 3 phase, type AF-16-30-01 with suitable size of thermal overload relay and auxillary contact complete all as specified and as directed by Engineer-in-charge.
M&L in replacement power contactor 415 volt, 50 cycles, 3 phase, type AF-40-30-00 with suitable size of thermal overload relay and auxillary contact complete all as specified and as directed by Engineer-in-charge.
M&L in replacement power contactor 415 volt, 50 cycles, 3 phase, type AF-65-30-00 with suitable size of thermal overload relay and auxillary contact complete all as specified and as directed by Engineer-in-charge.
M&L in replacement power contactor 415 volt, 50 cycles, 3 phase, type AF-80-30-00 with suitable size of thermal overload relay and auxillary contact complete all as specified and as directed by Engineer-in-charge.
M&L in replacement power contactor 415 volt, 50 cycles, 3 phase, type AF-96-30-00 with suitable size of thermal overload relay and auxillary contact complete all as specified and as directed by Engineer-in-charge.
M&L in replacement power contactor 415 volt, 50 cycles, 3 phase, type AF-116-30-11 with suitable size of thermal overload relay and auxillary contact complete all as specified and as directed by Engineer-in-charge.
M&L in replacement bimetal over load relay single phase protection directly mounted 28 to 42 Amps, range ML2/ML3 complete all as specified and as directed by Engineer-in-charge.
M&L in replacement bimetal over load relay single phase protection directly mounted 66 to 110 Amps, range MN5 complete all as specified and as directed by Engineer-in-charge
M&Lin replacement bimetal over load relay single phase protection directly mounted 45 to 75 Amps, range MN5 complete all as specified and as directed by Engineer-in-charge.
M&L in replacement power contactor 415 volt, 50 cycles, 3 phase, type MNX-80 complete all as specified and as directed by Engineer-in-charge.
M&L in replacement power contactor 415 volt, 50 cycles, 3 phase, type MNX-70 complete all as specified and as directed by Engineer-in-charge.
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
techsummary_843617.pdf
BOQ Comparative Chart
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.26 MB
tender.pdf
Tender Documents • 1.16 MB
BOQ_843617.xls
BOQ • 0.38 MB
Download all tender documents and submit your bid