| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.7 LAccepted-AOC 205 PARSHAV VIHAR PLOT NO 50 IP EXTN PARPARGANJ DELHI 110092 | EAST | DELHI | 110092 | L1 | Accepted-AOC Ok | |
| 2 | L2₹29.8 L+₹2.4 L (8.94%)Rejected-Finance A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | L2 | Rejected-Finance Other than lowest tenderer | |
| 3 | L3₹34.4 L+₹7.1 L (25.8%)Rejected-Finance 131 SHINGANAPUR ROAD KOLKI KOLKI SATARA MAHARASHTRA 415523 | SATARA | MAHARASHTRA | 415523 | L3 | Rejected-Finance Other than lowest tenderer | |
| 4 | L4₹43.3 L+₹16.0 L (58.3%)Rejected-Finance N A | NEW DELHI | DELHI | 110001 | L4 | Rejected-Finance Other than lowest tenderer | |
| 5 | L5₹49.7 L+₹22.3 L (81.4%)Rejected-Finance 22 319 GALI NO 5 MAHABIR PARK BAHADURGARH 124507 HARYANA | JHAJJAR | HARYANA | 124507 | L5 | Rejected-Finance Other than lowest tenderer |
Tender Value
₹45.5 L
EMD Value
₹90,900
Closing Date
16 Dec 2021, 6:00 pmClosed
GE E/M BASE HOSPITAL DLEHI CANTT
GE E/M BASE HOSPITAL DLEHI CANTT-110010
REPAIR/ REPLACEMENT OF UNSERVICEABLE LT UG CABLE, LT FEEDER PILLAR BOXES, LT PANEL INCLUDING REPAIR/ REPLACEMENT OF GI WIRE STRIP/ CHEMICAL EARTHING AND OTHER MISC EXTERNAL ELECTRICAL WORKS WITH REROUTING OF HT/ LT CABLES UNDER GE (E/M) BASE HOSPITAL
2021_MES_487188_1
GE/BH-50/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE E/M BASE HOSPITAL DLEHI CANTT
Class D Category b(i)
7 documents required · 7 mandatory
₹500
GE E/M BASE HOSPITAL DLEHI NCANTT
₹90,900
Yes
2 Apr 2022
10 Nov 2021
18 Dec 2021
10 Nov 2021
16 Dec 2021
2 Dec 2021
Amount
Supply, installation, testing & commissioning in repair LT, outdoor type, switch gear panel board of size 1800 x 1500 x 450 mm, factory made, CPRI approved, Floor/platform mounted, totally enclosed, dust and vermin proof, made out of MS CRCA sheet of thickness not less than 3.15 mm & 50 x 50 x 6 mm thick MS angle iron frame and legs of size 0.5m, as per IS 5039, cubical type, front and rear side openable, provision of air vent, provision of cable alley, with 1000 Amps rated Aluminium bus bar for each phase (Total 03 Nos) and 400 Amps rated Aluminium bus bar for neutral, duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 Volts, 50 Hz 3 Phase, 4 wire system and bus bars fixed on porcelain or PVC insulators, thimbles, glands of brass and shall be complete including necessary earth work and PCC foundation complete all as required and directed with following accessories (As described in Srl No 1.01 here in after) complete all as specified and as directed:-
(a) INCOMMER: FP, 630A, 36KA, MCCB Microprocessor Based release for LSIG protection with ROH , AUX, Trip contact and Shunt release - 01 No. (b) Metering and Indication:- (i) Digital Multifunction Meter with RS 485 Port, CI -1 (ii) CT for Meter CI -1.0,15VA (iii) RYB phase Indication light (iv) On /off/trip indication light-ACB (v) Control MCB SP (c) Out Goings: (i) TPN MCCB thermal Magnetic Based release for (O/L &S/C) protection with ROH -250A, 25 KA - 01 No (ii) TPN MCCB thermal Magnetic Based release for (O/L &S/C) protection with ROH -160A, 25 KA - 02 Nos (iii) TPN MCCB thermal Magnetic Based release for (O/L &S/C) protection with ROH -125A, 25 KA - 04 Nos (iv) TPN MCCB thermal Magnetic Based release for (O/L &S/C) protection with ROH -100A, 25 KA - 03 Nos (v) TPN MCCB thermal Magnetic Based release for (O/L &S/C) protection with ROH -63A, 25 KA - 02 Nos
Supply, installation, testing & commissioning in repair LT, outdoor type, switch gear panel board of size 1800 x 1500 x 450 mm, factory made, CPRI approved, Floor/platform mounted, totally enclosed, dust and vermin proof, made out of MS CRCA sheet of thickness not less than 3.15 mm & 50 x 50 x 6 mm thick MS angle iron frame and legs of size 0.5m, as per IS 5039, cubical type, front and rear side openable, provision of air vent, provision of cable alley, with 1000 Amps rated Aluminium bus bar for each phase (Total 03 Nos) and 400 Amps rated Aluminium bus bar for neutral, duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 Volts, 50 Hz 3 Phase, 4 wire system and bus bars fixed on porcelain or PVC insulators, thimbles, glands of brass and shall be complete including necessary earth work and PCC foundation complete all as required and directed with following accessories (As described in Srl No 2.01 here in after) complete all as specified and as directed:-
(a) Incoming:- 400 A, 36 KA, MCCB, Microprocessor Based release for LSIG protection with ROH, AUX, Trip Contact - 1 No. (b) Metering and Indication:- (i) Digital Multifunction Meter with RS 485 Port, CI -1 (ii) CT for Meter CI -1.0,15VA 400/5A-03 Nos (iii) RYB phase Indication light (iv) On /off/trip indication light - ACB (v) Control MCB SP (c) Out Goings - (i) TPN MCCB Thermal Magnetic based release for (O/L &S/C) protection with ROH -200A, 25 KA - 01 No (ii)TPN MCCB Thermal Magnetic based release for (O/L &S/C) protection with ROH -100A,25 KA -05 Nos (iii) TPN MCCB Thermal Magnetic based release for (O/L &S/C) protection with ROH -63A, 25 KA -02 Nos
Supply, installation, testing & commissioning in repair LT, outdoor type, switch gear panel board of size 1500 x 1200 x 450 mm, factory made, CPRI approved, Floor/platform mounted, totally enclosed, dust and vermin proof, made out of MS CRCA sheet of thickness not less than 3.15 mm & 40 x 40 x 5 mm thick MS angle iron frame and legs of size 0.5m, as per IS 5039, cubical type, front and rear side openable, provision of air vent, provision of cable alley, with 600 Amps rated Aluminium bus bar for each phase (Total 03 Nos) and 400 Amps rated Aluminium bus bar for neutral, duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 Volts, 50 Hz 3 Phase, 4 wire system and bus bars fixed on porcelain or PVC insulators, thimbles, glands of brass and shall be complete including necessary earth work and PCC foundation complete all as required and directed with following accessories (As described in Srl No 3.01 here in after) complete all as specified and as directed:-
(a) Incoming:- MCCB, 4 Pole, 35 KA, 400 Amp - 01 No (b) Metering and Indication:- (i) Single Multifunction meter (RE485 Port -6436) - 01 No (ii) CT for Meter CI -1.0,15VA 400/5A-03 Nos (iii) RYB phase Indication light (iv) On /off/trip indication light (v) Control MCB SP (c) Out Goings - (i) MCCB, 4 Pole, 16 KA, 200 Amps - 02 Nos (ii) MCCB, 4 Pole, 16 KA, 100 Amps - 02 Nos (iii) MCCB, 4 Pole, 16 KA, 63 Amps - 02 Nos
Supply, installation, testing & commissioning in repair LT, outdoor type, switch gear panel board of size 1500 x 1200 x 450 mm, factory made, CPRI approved, Floor/platform mounted, totally enclosed, dust and vermin proof, made out of MS CRCA sheet of thickness not less than 3.15 mm & 40 x 40 x 5 mm thick MS angle iron frame and legs of size 0.5m, as per IS 5039, cubical type, front and rear side openable, provision of air vent, provision of cable alley, with 600 Amps rated Aluminium bus bar for each phase (Total 03 Nos) and 400 Amps rated Aluminium bus bar for neutral, duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 Volts, 50 Hz 3 Phase, 4 wire system and bus bars fixed on porcelain or PVC insulators, thimbles, glands of brass and shall be complete including necessary earth work and PCC foundation complete all as required and directed with following accessories (As described in Srl No 4.01 here in after) complete all as specified and as directed:-
(a) Incoming:- (i) MCCB, 4 Pole, 35 KA, 250 Amp - 01 No (b) Metering and Indication:- (i) Single Multifunction meter (RE485 Port -6436) - 01 No (ii) CT for Meter CI -1.0,15VA 400/5A-03 Nos (iii) RYB phase Indication light (iv) On /off/trip indication light (v) Control MCB SP (c) Out Goings:- (i) MCCB, 4 pole, 16 KA, 100 Amps - 04 Nos (ii) MCCB, 4 Pole, 16 KA, 63 Amps - 03 Nos (iii) MCB, 4 Pole, 10 KA, 63 Amp - 03 Nos (iv) MCB, 4 Pole, 10 KA, 40 Amp - 03 Nos
Supply, installation, testing & commissioning in repair Auto main failure ( AMF) panel, suitable for 220 KVA DG Set, factory made, CPRI approved, Floor/platform mounted, totally enclosed, dust and vermin proof, made out of MS CRCA sheet of thickness not less than 2.0 mm & 40 x 40 x 5 mm thick MS angle iron frame and legs of size 0.5m, as per IS 5039, cubical type, front and rear side openable, provision of air vent, provision of cable alley, with 1000 Amps rated Aluminium bus bar for each phase (Total 03 Nos) and 400 Amps rated Aluminium bus bar for neutral, duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 Volts, 50 Hz 3 Phase, 4 wire system and bus bars fixed on porcelain or PVC insulators, thimbles, glands of brass and shall be complete including necessary earth work and PCC foundation complete all as required and directed with following accessories (As described in Srl No 5.01 & 5.02 here in after) complete all as specified and as directed:-
(n) CT Coil 500 / 5 - 06 Nos. (o) DC Volt Meter 15/30 V - 01 No. (p) DC Amp Meter 0-15 A. - 01 No. (q) Trickle / Boost switch – 01 No. (r) Auto / Manual Switch - 01 No. (s) Start & Stop Push Button - 02 Nos. (t) Frequency Meter – 01 No. (u) Power Contactor MNX 630 A 3 Pole 415V for DG. - 01 No. (v) Power Contactor MNX 630 A 3 Pole 415V for Main.- 01 No. (w) MCCB 630 A 35 KA 3 Pole - 02 Nos. (x) Control Relay - 01 Set. (y) Over Load Relay 2.5-4A. – 01 No. (z) Hooter 24 V DC - 01 No. (aa) C/O Switch 630 A. for bye Pass Main Supply & DG – 02 Nos.
Supply, installation, testing & commissioning in repair LT panel, Made out of Thermoplastic Polycarbonate, indoor type, factory made, CPRI approved, wall mounted, environment friendly, recyclable, UV resistant, halogen & silicon free, anti-acid & anti corrosive, IP 65 Protection in accordance with IEC 60529, The gasket material shall be Polyurethane; while the gasket shall be internally embedded. Panel shall be cubical type, front openable, with provision of air vent, provision of cable alley, with following accessories & specifications (As described in Srl No 6.01 to 6.03 here in after) complete all as specified and as directed:-
General Specification & Electrical Parameter:- Type of Panel:- Thermoplastic Polycarbonate. Panel Size:- 1730x 1900x 750mm Degree of Protection:- IP54(EN60529) Bus Bar Rating:- 630A (Ph &N -30 x 10mmCu) System Voltage:415V,15Hz,4wire+E Installation :- Indoor /Wall Mounting Cable Entry:- Incoming/outgoing from bottom. Finish Shade:- Enclosure & Accessories: RAL 7035 Mounting structure: RAL 7016 Incomer: 630 A FP 36kA MCCB – 01 Nos R/Y/B LED Indicating lamp – 1 No /each Control fuse with base (2A/32A) – 3 Nos Outgoing : 200 A FP 36kA MCCB – 1 Nos 125 A FP 25kA MCCB – 6 Nos Terminal Detail:- 50 Sqmm Terminal Block-24 Nos
Notes:- (1) The manufacturer of board / panel shall submit a copy of type test report of Polycarbonate thermoplastic panel in accordance with IEC 60439-1. The report shall have mention of following tests performed and passed out satisfactorily: - (i) Temperature Rise. (ii) Dielectric Properties. (iii) Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current. (iv) Effectiveness of Protective Circuits. (v) Clearance & Creepage Distance. (vi) Mechanical Operation (2) For better safety the Polycarbonate enclosure shall be fire retardant & self-extinguishing in accordance with IEC 60 695-2-1, DIN VDE 0304 Part 3, UL Subject 94 for Flammability V-2. It shall be tested at Glow Wire test for 960 degree C. The impact strength of polycarbonate enclosures / boards i.e. the Degree of Protection against Mechanical load shall be in accordance with EN 50298-98 for IK 08. (3) The lid closing and opening shall be done by quick fastening spring mechanism latches.
(4) Compactness of the boards is main criteria due to space constraints. The board / panel shall be made compact meeting the technical requirements in accordance with relevant standards and also keeping adequate space for technicians to work. For MCB section the distance between centers of two consecutive DIN Channels in a row shall not be more than 140 mm. The MCB/ RCCB switching operations / accessing the MCB dolly shall be by opening of a window flap. (5) The board manufacturer shall submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS shall not be applicable. Each Board shall have individual routine test report of the manufacturer.
Supply, installation, testing and commissioning, in repair outdoor type, Floor/wall mounted, street light panel, 12 kW, three phase, confirming to IS 60947-4-1, with IP-54 protection, astronomical type, front openable, with provision of locking arrangement, dust & vermin proof, Consisting of the following equipments including dismantling of old Panel complete all as specified and as directed:- (a) Incoming: (b) Digital 24 Hour timer (c) Contactor for the automatic switching of luminaries, power tool control with 2 No 65A/TP contactors and raise lower push button. (d) MCB -63 Amp, TPN (e) Incoming 35 Sqmm and out going 16 & 2.5 Sqmm terminals. Make: Havells Cat Part No IHXTS0912A or equivalent model of Make mentioned in PS.
M&L for comprehensive maintenance of 30 KVA, UPS system of Make- Vertiv (13 Nos installed at different locations in Base Hospital). The item shall includes maintenance of 13 Nos online UPS including replacement of parts as required in case of found defective during attending complaints namely IGBT's, power components:- Transistors, Capacitors, Diodes, SCR, LCD screens, Harmonic filters and transformers, PCB cards and connected electrical and electronic components etc. (All spares and defective batteries any capacity and sizes) complete all as specified and as directed. Notes: (i) The tenderer shall submit the copy of letter or MOU from OEM of UPS i.e, M/s Vertiv Energy Pvt Ltd stating that work shall be carried out by the OEM or their authorised Channel Partner failing which financial bid shall not be opened. (ii) All spare parts required for repair/ Maintenance of UPS shall be provided by the contractor. Cost of the same shall deemed to be included in Quoted rate for this item. (iii) Complaint shall be attended and rectified within 24 hours of intimation by user's rep, JE-in-Charge or Engr-in-Charge verbally or telephonically. Failing which, a penalty of Rs 1000/- per complaint per day shall be imposed on the contractor.
(iv) After rectification of the complaint, contractor shall inform to the concerned JE E/M for fault rectification, which will be done by contractor and also recce to be done for functioning of UPS and rectifying the defects. (v) Contractor shall display his contact number (Mobile No.) near all UPS. (vi) Contractor's quoted rates shall also includes maintenance and charging of battery on monthly basis by cleaning & applying Petrolium jelly. (vii) Upkeeping the log books shall be done by contractor's rep. (viii) Field service report shall be maintained and submitted to JE after every month by the contractor's rep for checking.
Supply, laying and jointing in repair, in trenches / passing through pipes/ fixing on poles/fixing on wall with saddles in replacement LT under ground cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 400 Sqmm, 3.5 core including cable connecting lugs, glands, jointing fixing materials including taking out old unserviceable cables complete all as specified and as directed.
All as per item No 9.00 here in before but 300 Sqmm, 3.5 core cable complete all as specified and as directed.
All as per item No 9.00 here in before but 630 Sqmm, Single core cable complete all as specified and as directed.
All as per item No 9.00 here in before but 400 Sqmm, Single core cable complete all as specified and as directed.
S&F in repair ACB 4 Pole, 415 V, with microprocessor release (Manual Draw out type), of capacity 800 Amps, conforming to EMI/EMC standards (Overload and short circuit protection), Standard breaking capacity 100%, Conforming to IEC 60947-2 complete all as specified and directed. Make: Havells Cat Part No IHATE21080**# (Titania Series) or equivalent model of Make mentioned in PS.
S&F in repair ACB 4 Pole, 415 V, with microprocessor release (Manual Draw out type), of capacity 1000 Amps, conforming to EMI/EMC standards (Overload and short circuit protection), Standard breaking capacity 100%, Conforming to IEC 60947-2 complete all as specified and directed. Make: Havells Cat Part No IHATE21100**# (Titania Series) or equivalent model of Make mentioned in PS.
S&F in repair ACB 4 Pole, 415 V, with microprocessor release (Manual Draw out type), of capacity 630 Amps, conforming to EMI/EMC standards (Overload and short circuit protection), Standard breaking capacity 100%, Conforming to IEC 60947-2 complete all as specified and directed. Make: Havells Cat Part No IHATE21060**# (Titania Series) or equivalent model of Make mentioned in PS.
M&L in repair pipe earthing (PIP) comprising of GI 50mm bore pipe, wall thickness of pipe 4.85 mm (Medium grade), 3.00 Metre length, terminal size 40x6mm & internal strip 25x4mm with one bag of BFC (50 Kg) as per IS 3043-1987, tubing filled with jelly earthing compound, duly inserted in soil, boring of 100mm bore filled with back filled compound including fibre chamber cover 1x1 feet, openable type, including testing of earthing complete all as specified and as directed. Note: On testing after completion, if the earth resistance < 1 Ohms is not obtain, earthing shall be rejuvenated at no extra cost till the desired earth resistance is obtained.
Excavation in trenches not exc 1.50 metre wide or 10 Sqm on plan, 1.50 metre in depth for manholes & sewage lines, drain or for laying of cables etc and getting out in soft/loose soil complete all as specified and directed.
Supply and laying clean dry sand for cable cushion including gently punning complete all as specified and as directed. Note: Punned thickness of sand shall be measured for payment purpose.
M&L in repair burnt brick sub class ‘B’ laid in trenches abutting each other width equal to length of bricks all as specified and as directed.
Returning, filling in including spreading levelling, watering and well ramming in layers not exc 25 cm thick in any type of soil complete all as specified and directed.
Removing the surplus soil to a distance not exceeding 50 metre and depositing where directed at level not exc 1.5 metre above the starting point complete all as specified and directed.
M/s Adhikari construction co.
Vishal Traders
M/S Rohit Enterprises
R R Associates
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .