Tender Value
Refer Docs
EMD Value
₹19,400
Closing Date
28 Jul 2023, 4:00 pmClosed
Executive Engineer Electric Division UdhampurJPDCL
Executive Engineer Electric Division UdhampurJPDCL
(1) Buffer of Electric Pole, Kulwanta (2) Creation of Transformer 63 KVA in the land of Ram Dass S/o Massu Atta Chakki, W.No. 1 Lower Katwalt
2023_PDD_220476_1
ED/Udh/28 of 2023-24 dt. 08-07-2023
Open Tender
Electrical Works
Turn-key
95 days
In District Udhampur
Please refer Tender documents.
2 documents required · 2 mandatory
₹600
Executive Engineer Electric Division UdhampurJPDCL
₹19,400
8 Aug 2023
8 Jul 2023
31 Jul 2023
8 Jul 2023
28 Jul 2023
8 Jul 2023
8 Jul 2023 - 13 Jul 2023
Survey, Transportation, Carriage, Testing and Commissioning for Erection of LT line on 8 mtr long ST Poles, 30 mm² ACSR Weasel Conductor for Installation/Buffer of Electric poles in Kulwanta under DDC Grants.
8 mtr. Long ST Poles (ST 410 SP15)
GI M-Clamps for shackle insulator
30 mm² ACSR Weasel Conductor
Shackle Insulators
Galvanized Nuts and Bolts
Earthing complete by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr long through GI strip.
LT Circuit Switch made of 50*6 flat iron and Aluminum flat 50*6 fixed on busbar insulators
Painting of 8 mtr long ST poles with two coats of aluminium paint
Survey, Supply, Design, Transportation, Carriage, erection, Testing and Commissioning for erection of 11 KV line on 9 mtr long ST poles, 30 mm² ACSR condcutor for 63 KVA transformer in the land of Ram Dass S/o Massu Atta Chakki W.No. 1 Lower katlwat under DDC grants
9 mtr. Long ST Pole (ST 410 SP33)
GI V-Cross arm with top bracket including clamps
GI Channel X-arm including clamps and Braces
0.03 mm² ACSR Weasel Conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 9 mtr long ST poles with two coats of aluminium paint
Survey, Supply, Design, Transportation, Carriage, erection, Testing and Commissioning for Creation of 63 KVA transformer in the land of Ram Dass S/o Massu Atta Chakki, W.No. 1 Lower Katwalt under DDC Grants.
11/0.433kV, 3-phase Distribution Transformers 63 KVA with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
95 mm² (2ckt.) 1.1 kv Grade, PVC insulated stranded conductor FRLS type
9 Mtr. Long Pole( ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
LT Circuit Switch made of 50*6 flat iron and Aluminum flat 50*6 fixed on busbar insulators
Galvanized stay set with 50*8 mm stay clamp, guy insulator(2 nos), anchor plate (200*6mm), nuts-bolts, 2 Nos turn buckets, 1.8m long, 16 mm diameter solid GS stay rod & 7/15 mm dia GI strandard wire complete.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made.
Survey, Supply, Design, Transportation, Carriage, erection, Testing and Commissioning for erection of LT line on 8 mtr long ST poles, 30 mm² ACSR condcutor at W.No. 1 Lower Katwalt under DDC Grants.
8 mtr. Long ST Pole (ST 410 SP15)
GI M clamps for Shackle Insulator
0.03 mm² ACSR Weasel Conductor
Shackle Insulator
Galvanized Nuts and Bolts
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 8 mtr long ST poles with two coats of aluminium paint
SWASTIK ELECTRICAL AND CONSTRUCTION WORKS
SATPAUL & SONS
RAJINDER KUMAR
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .