Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.7 LAccepted-AOC | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹15.9 L+₹12,800 (0.81%)Rejected-Finance | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹17.5 L+₹1.7 L (11.0%)Rejected-Finance 1 A BASEMENT 30 31 RAJA HOUSE NEHRU PALACE NEW DELHI 110 019 | SOUTH EAST | DELHI | 110019 | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹17.6 L+₹1.8 L (11.7%)Rejected-Finance RZ BH 4 STREET NO 5 MAIN SAGARPUR NEW DELHI 110046 | NEW DELHI | DELHI | 110046 | L4 | Rejected-Finance Not Lowest | |
| 5 | L5₹19.5 L+₹3.8 L (24.0%)Rejected-Finance | L5 | Rejected-Finance Not Lowest |
Tender Value
₹17.6 L
EMD Value
₹35,100
Closing Date
30 May 2022, 6:00 pmClosed
CWE AF JODHPUR
HQ CWE AF JODHPUR
85924 E8 PROVN OF DG SET STANDBY POWER SUPPLY FOR FIRE HYDRANT SYSTEM (QTY-03) AT AF STN JAIPUR
2022_MES_520632_1
85924/E8
Open Tender
Miscellaneous Works
Item Rate
240 days
AGE (I) (AF) JAIPUR
As per NIT
7 documents required · 7 mandatory
₹500
AGE (I) (AF) JAIPUR
₹35,100
Yes
21 Jun 2022
28 Apr 2022
1 Jun 2022
28 Apr 2022
30 May 2022
15 May 2022
28 Apr 2022 - 29 Apr 2022
Amount
Supply, Installation, testing and commissioning of Factory Assembled silent Diesel Engine driven generating set,415volt, 3 phase, 4wire,engine as per IS 10002/10001 and alternator as per is 13364 of capacity 15 KVA at 0.8 PF, complete with sound proof canopy made of powder coated with specially designed lifting hooks, meet the latest CPCB norms of 75DB at 1 M distance, Inbuilt AMF Panel as per OEM Manufacturer guideline all as spd and directed and comprising of following :- (a) Engine: 2 cylinder,1500 RPM, water/Air cooled, four stroke, 20.5 BHP,diesel engine for 15 KVA alternator as per is 10002/10001 with sensor for low oil pressure, high water temprature including microprocessor based engine control panel , 12V DC start system with battery and fuel tank for 8 hr run all as spd and directed. (b) Alternator: alternator of rated capacity 15 KVA at1500 RPM, 0.8 lagging pf, 415 volts, 3 phase, 4 wire, Brushless,Single Bearing,self excited, self regulated an AVR with +- 1% voltage regulation, class H insulation all as spd and directed. (c) Control Panel: Control panel should have following parameter (i) Genset DIsplay Parameters( Line/Phase Voltage, Line Current,Frequency,Avg Voltage,Avg Current,Phase and Total KW,KWh and PF) (ii) Engine Display Parameters( Coolent Temp,Fuel status,Speed,Running Hrs, No of Starts, Battery Voltage. (iii)Electrical safeties(Under/Over voltage,Under/over frequency,Phase failure, Phase sequence reverse,over current,over kw) (iv) Mechanical Safeties (Under/OverSpeed,Low Lub oil Pressure,High engine coolant temprature,Battery charging indication,Low fuel level,start/stop fail. Location for installation: Air Force station Domestic Area-01, Tropo Technical (Radar) Area-01 Make : Ashok Leyland/Cummins/Kirloskar
Supply, Installation, testing and commissioning of Factory Assembled silent Diesel Engine driven generating set,415volt, 3 phase, 4wire,engine as per IS 10002/10001 and alternator as per is 13364 of capacity 40 KVA at 0.8 PF, complete with sound proof canopy made of powder coated with specially designed lifting hooks, meet the latest CPCB norms of 75DB at 1 M distance, Inbuilt AMF Panel as per OEM Manufacturer guideline all as spd and directed and comprising of following (a) Engine: 3 cylinder,1500 RPM, water cooled, four stroke, 52 BHP,diesel engine for 40 KVA alternator as per is 10002/10001 with sensor for low oil pressure, high water temprature including microprocessor based engine control panel , 12V DC start system with battery and fuel tank for 8 hr run all as spd and directed. (b) Alternator: alternator of rated capacity 40 KVA at1500 RPM, 0.8 lagging pf, 415 volts, 3 phase, 4 wire, Brushless,Single Bearing,self excited, self regulated an AVR with +- 1% voltage regulation, class H insulation all as spd and directed. (c) Control Panel: Control panel should have following parameter (i) Genset DIsplay Parameters( Line/Phase Voltage, Line Current,Frequency,Avg Voltage,Avg Current,Phase and Total KW,KWh and PF) (ii) Engine Display Parameters( Coolent Temp,Fuel status,Speed,Running Hrs, No of Starts, Battery Voltage. (iii)Electrical safeties(Under/Over voltage,Under/over frequency,Phase failure, Phase sequence reverse,over current,over kw) (iv) Mechanical Safeties (Under/OverSpeed,Low Lub oil Pressure,High engine coolant temprature,Battery charging indication,Low fuel level,start/stop fail. Location: Airforce station Domestic area fire pump Make : Ashok Leyland/Cummins/Kirloskar.
Supply and Fix on load changeover switch, side handletype.415 V in sheet metal enclouser, 4pole of capacity 63 Amps complete all as specified and directed by Engineer-in-Charge.
Supply and Fix on load changeover switch, side handletype.415 V in sheet metal enclouser, 4pole of capacity 32 Amps complete all as specified and directed by Engineer-in-Charge.
Supply and connect submersible cable copper conductor PVC insulated over all sheathed flat flexible ISI marked 1100 volt grade complete of size 10 Sqmm, 3 core complete all as specified and directed by Engineer-in-Charge. Make: Hevells/Finolex/L&T/Polycab
Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion . light grade pipe and watering pipe shall be 20 mm bore medium grade PCC pit with pre cast RCC cover, charcoal/salt funnel etc. complete all as directed. NOTE : (i) The conctrete pit shall be PCC 1:3:6 tye C -1 40 mm thick pre cast cover slab of RCC (1:2:4) type B-1 using 20 mm graded stone aggregate reinforced with 8 mm TMT bars @10 cm C/C on both sides with suitable cast iron handle shall be provided in liew of cast iron cover shown in electrical plate No.3 of MES SSR Part-1 (ii) Item includes the cost of 7.5 m GI pipe for protection of earth strip (iii) PCC pits shall be provided atleast 500 mm away from the pit and not on the earth pit itself and the extra cost of additional length of watering pipe, bends , elbows etc. shall be deemed to be included in the quioted rate. (iv) Item includes the cost of 7.5 mtr Earth lead wire of dia 4mm
LAKSHMI ASSOCIATES
MONA GENERATOR SEVICES PVT. LTD.
M/s ELECTROSHINE ENGINEERS
M/S Anil Enterprises
SHREE BHAGWATI ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .