| 1 | Admitted-Fee/PreQual/Technical/Finance 37 LACHMAN PORA BATAMALOO SRINAGAR J K | Admitted-Fee/PreQual/Technical/Finance |
| 2 | Admitted-Fee/PreQual/Technical/Finance SARCH GANDERBAL J K 191131 | GANDERBAL | JAMMU AND KASHMIR | 191131 | Admitted-Fee/PreQual/Technical/Finance |
Tender Value
₹10.8 L
EMD Value
₹21,660
Closing Date
12 Jan 2023, 4:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer Water Works Division Srinagar
Executive Engineer Water Works Division Srinagar Lal Chowk Exchange Road Srinagar
Providing of Electro Mechanical Works to be carried out for proposed construction of 25000 gallons capacity Sump cum Pump House at Reck Chowk Batamaloo Srinagar.
2023_PHE_201659_1
E-NIT No.54/WWD of 2022-23
Open Tender
Civil Works - Water Works
Item Rate
10 days
Batamaloo
As per NIT
5 documents required · 5 mandatory
₹1,000
Yes
Executive Engineer Water Works Division Srinagar
₹21,660
Yes
13 Jan 2023
5 Jan 2023
13 Jan 2023
5 Jan 2023
12 Jan 2023
5 Jan 2023
Amount
Supply, installation, testing & successful commissioning of Open Well Submersible Pump suitable for below mentioned specification. Pump: Rated Discharge = 7500 GPH Rated Head = 35 meters. Type of pump = Submersible Horizontal Pump. MATERIAL OF CONSTRUCTION: Pump casing = cast iron Impeller = cast iorn Pump shaft = stainless steel Motor body = cast Iron Sealing = dual mech. Scal The bowl plat shall be provided with name plate depicting all specifications of pump and motor. Motor: Rating = as per OEM but not less than 10 HP Speed = 2900 RPM, Method of starting star = Delta, Frequency = 50HZ + 3%, Voltage = 415 ± 15 V Insulation B class Protection IP 68 Fitted with low water level controller The job includes providing and fitting of required size heavy duty GI nipple with flange/as per site requirement and as per pump outlet size. The job includes lowering of the pump-motor assembly in the Sump and fitting it with column pipes. The Job includes cost of all carriages, skilled labor, tools and tackles and includes all incidental works thereof. Finally connecting the pump motors with A.C Supply for proper testing on full load at site. The pump shall be fitted with suitable suction strainer, dual Manufactures Test Certificate to be appended.
Providing /supplying laying and fitting of G.I class: C(Heavy) size: DN 100 rising main at site including bends, tees, nipples, elbows, joints sockets etc. the pipe shall be hot dip Galvanized, class-C confirming to IS 1239. The job includes providing and fitting of M.S Flanges where ever required conforming to BIS 6392/1997 Table 17 (Rating PN 16). Providing and fitting of DI Tee of size DN 100 with flanges gaskets nuts bolts etc. (Rating PN 16) fastened with weld joints on three ends.
Providing & fitting of DI Tee of size DN 100 with flanges gaskets nuts bolts etc. (Rating PN 16) fastened with weld joints on three ends.
Providing and fitting of Ductile Iron double flanged, non-rising spindle soft seated glandless gate/sluice vales as per ISI 14846for regulating the water supply outside the pumping units size 100PN 1.6/16 rating.
Providing & fitting of ductile iron double flanged, slanted seat swing check valve (NRV) as per IS 5312 of size: DN 100 MM PN1.6/16 rating.
Providing & fitting of 50mm Bronze open discharge screwed spring loaded safety relief vale as per ISI 12992 part 1
Providing and fixing cast iron double flanged.SS 304 dis butterfly valves complete with bolts, nuts, 3.0mm thick compressed asbestos gasket size 100mm PN 1.6/16 rating to be fitted at wash out arm.
Fabrication, providing and fitting of 90-120 degree bend/elbow to be fabricated out of G.I pipe, 1m length and flanged on both ends to make it leak proof. The flanges shall be M.S flanges of size DN 100mm, conforming to BIS 6392/1997 Table 17 (rating PN 16) and welded on both sies. The job includes nuts, bolts, gaskets etc as per site requirement.
Fabrication, providing and fitting of split type MS clamps 10mm thick, 2 ft long ad 3 inch wide for lowering and holding of pumping unit fitted. The job includes the cost of required size of nuts and bolts size100mm
Providing , installation and testing of manual type triple spur gear chain pulley block along with monorail geared travelling trolley having following features: Gears: - the hoist shall have precision machine case hardened alloy steel gear mounted on bearings and housed in a dust proof gear box. The lubrication of gears should be of high viscosity and temperature for longer life of gears. Load Chain: The load chain be made of high tensile alloy steel having wear resistance and greatest mobility. The chain should be accurately collaborated, tested and have adequate in built factor of safety for safer operation. Load chain wheel:- The load chain well should be double ball bearing supported and specially designed, perfectly machine wheel providing correct grip of load chain to makes the hoist most safe and reliable against any failure. The main specification of C.P Block are given below Make = Reputed make Capacity = 2 ton No of load chain falls = 2 or above Min. Height of lift = 6 M Testing/inspection certificate is mandatory and is to be produced at the time of supply of material.
S/I/T/C of 11/0.433 KVA, 3 phase distribution transformer with Bimetallic Terminal connectors energy level-2 aluminum wound specifications conforming to IS: 1180 (part 1) 2014 with latest amendments. The job includes providing and laying of concrete bed of size 2mx 2m x 1m over which the transformer is to be rested. The bed shall be properly MS fenced, Rating: 63 KVA HT Transformer, 3 phase. Type: HT/LT transformer (level-2) Type of cooling:ONAN Operating conditions: Input = 11000 volts Output = 433 volts AC supply in 3- phase. Terminals: Input = 3 No. HT Brass bush rods with insulators, washer, nuts etc. Output = 4 No. LT Brass bush rods switch insulators, washers, nuts etc. Core: The core shall be high permeability to reduced core losses & the strips shall be of suitable size and gauge. Transformer coils: Suitable number of HT and LT coils in each leg of the core. The transformer coils shall be fabricated out of superior quality aluminum wire/strips, properly wound. the HT transformer is completely filled with suitable grade transformer oil up to required level. The job includes carriage, and all leads and lifts involved. The HT transformer shall be of reputed make from an ISO certified company as per relevant standards and a test certificate shall be provided before installation. The transformer shall also be provided with breather fill with silica jel crystals, conservator with oil level indicator, explosion vet and adequate radiator fins/tubes. The impedance of transformer shall be as per IS: 1180 (part-1) 2014 with latest amendments. Note: the scope of the work shall include obtaining of necessary inspection/ clearance certificate from the concerned department for all the required equipment. The testing and commissioning shall be completed only after obtaining above certificate manufacturer’s certificate be appended.
Providing and fitting G.I channel/ Angle /Flat of sizes including clamps. The job includes fitting of channels on two poles for the installation of insulators and safety devices, GC set (lighting arrestor) etc it also includes the channels for fitting of LT meter and LT distribution box. Size of channel= ISMC 75 x 40mm V crosses to be fitted on each pole shall be fabricated out of ISMC 75 x 40mm includes pole Top, Black clamp, Nuts and bolts etc. the job includes providing and fitting of GI channels for installation of GO set at tapping point with handle and locking arrangement.
Supply, installation, testing and commissioning of polymeric gang operated air break switch, outdoor type, triple pole, suitable for vertical installation, single break provided with locking arrangement at both ON and Off position consisting of HT post double insulator, copper or copper alloy high pressure heavy contact assembly, rod with bearings, operating handle and 2 length of 32mm dia. G.I pipe conforming to IS 1818 1961, o6 No of insulators, rated voltage 11 KV 200A complete as per IS speces.01 No Go set is to be fitted at tapping point and 01 No, at HT transformer.
Supply, installation, testing and commissioning of 11 KV polymer fuses set horn cap 3 –phase 200 A suitable for vertical installation.
Supply, installation, testing and commissioning of Gapless surge arrestor station class, k10KA, 9KV, LA with polymer housing, station type.
Supply and fitting of 11 KV polymeric composite pin insulator 12 KV, 5KN, Lighting impulse 75 KV positive, and 80KV Negative, creep age distance 320mm.
Supply installation, erection of 9 mtrs long H.T pope of specifications ST-410 (SP-33). The job further includes drilling of holes for installation of various accessories. Wherever required including concreting, the job further includes G.I wire creating of pole as per REC standard. The tubular steel poles shall conform to the latest edition of Indian standard specification IS: 2713 (part-I, III): 1980. The materials used in construction of tubular steel poles shall be of the tested quality of steels of minimum tensile strength 540 MPa. The poles shall be fitted with base plate as per above standard. The poles shall be applied with Red Oxide primer and two coats of anti- corrosive Red paint at bottom up to the length of 4M and two coats of paint of silver shade for the rest. 02 ST poles are to be fitted at tapping poit for the installation of Gang operated switch including GI channels etc for complete job.
P/F of Galvanized nuts bolts of various sizes as per site requirement.
P/F danger plate with clamps
Providing and fixing G.I Barbed wire for anti climbing/anti climbing devices with clamps. The barbed wire shall be tightly close wrapped around the pole for 10-12 turns, commencing at 2.50m above the datum line.
Providing and fitting of Galvanized stay set with 50 x 8mm stay clamp , guy insulator (2 no) ,Anchor plate (200x200x6mm) nuts & bolts, 2 No. turn buckle, 1.8m long , 16mm diameter solid G.I stay rod & 7/3.15mm dia . G.I stranded wire complete.
Providing and fitting of ACSR as per IS 398 (part-2) 1996 for 50 sq. mm ACSR (galvanized steel reinforced) for fitment of various accessories
Supply, installation and testing of 50sq mm XLPE Aluminum H.T cable (ABC type) of 11 KV grade with following specification. Size (cross sectional area in sq mm) = 3x50 with reinforced wire with messenger wire. Phases= Red, yellow, Blue The job includes providing and fitting of Anchoring clamps comprising clamp body, plastic wedge, steel bill bracket, straps and buckles or nuts and bolts required for holding of 3 –core, 50sq mm H.T AB cable.
P/F of 11 KV cable termination kit
Providing and fitting of LT distribution box for H.T transformer with MCCB for incomer and SFU for outgoing circuits. The LT distribution box is to be fitted on GI channels. Capacity of transformer: 63 KVA
Providing and fitting of PRODIGY LT Meter of following specification complete with all fixtures required for fitment at site: Type: E3L100, 3 Phase, 4 wire Measurements Offered: KWh, KVARh,KVAh,KVA Voltage: 3 x 240 V (415v), 50HZ Ib: 40A Imax :200A Battery: Lithium The prodigy meter must be fitted inside the box; that is to be fitted GI channels near LT Distribution box. Both the enclosures must be symmetrical Sealing/inspection report of prodigy meter for JKPDCL (concerned) is to be submitted by the firm at the time of charging of SUBSTATION.
Fabrication providing & fitting of modular control panel of appropriate size fabricated out of 14 SWG sheet having required openings/vents & protection class: IP -55 and fitted with accessories complete internal wiring. Fabrication, providing and fitting of Modular motor control panel of appropriate size fabricated out of 14 SWG sheet having required openings./vents and protection class IP-55 & fitted with accessories as under:
Busbar chamber: The bus bar chamber shall be fitted at the top of the panel horizontally throughout the length. There shall be 3 Nos. of phase busbar & 1 no neutral busbar & 1 no. earthling busbar. The busbars shall be air insulated & made up of high conductivity copper with current density of suitable rating for 20Ampere. All panel compartments shall be provided with suitable cable alley & vertical busbar alley. Suitable segregation shall be provided in between busbar chamber & adjoining compartments. The busbar shall be PVC sleeved with color strips of red, yellow, blue and black & the same be arranged in accordance with IS- 375 speces. Electrical clearances shall be maintained between phases, neutral & body as pe standards.
Main circuit breaker (in comer MCCB) Qut= 02 No. of poles = 4 pole Cuttent rating = 100 A Rated operational voltage = 415 V + 15% Rated frequency = 50 +/- 3% Hz Ambinent, temperature = 40ºC Type of release = Thermal magnetic Overload protection = 0.8 – 1 x1n adjustable Short circuit protection = 6 – 10 x in adjustable Ultimate S.C Breaking Cap. at(415VAC, 50Hz) = 50kA
Change over Switch: Qty = 01 No. Rating = 100 A Type = front operated, on load , 4 pole, 400 + 15% V, 50 + 3% Hz.
Submersible starters= fully automatic star delta starters. Powere space= 3, 415 + - 15 V, 50 +3% Hz. Relay range = 13 – 22A, 20-32 A or suitable as per requirement. Coil voltage = 380 v Protection = single phasing, phase reversal, phase unbalance ( 55 ±5 V)
Conformity to standard = IS/ IES 60947 -4-1 Qty = 2 Nos.
Auxiliary MCCB for heating /lighting Circuit breaker = MCCB (Outgoing) Qty = 1 No. No. of poles = 4 p Current rating = 63 A Rated operational voltage = 415V + 15% Ultimate S.C breaking cap at (415V AC,50 Hz) 36 kA
Motor protection Relay: Digital motor protection relay with LCD display for 3 –phase supply with following protections suitable for the modular control panel. Protections= thermal overload with pre alarm, short circuit, phase loss, unbalance, phase reversal, under current, prolong starting, locked rotor & earth fault and over current. Qty = 02 No (01 nor for each starter)
M- Power module for mobile starter for submersible motor 1 P/3P 3 wire. Qty = 2 No IVRS languages- English, Hindi Suitable region- North India.
Over voltage and under voltage protection relay (02 Nos) to be fitted separately for both starters. The panel shall be provided with phase indicators (03No) and digital ammeter of range 0-100 A, digital voltmeter of range 0-500 V, and digital frequency meter (01 no each) .The job includes complete internal wiring of the panel of suitable size. The enclosure of the panel shall be of excellent fit and finish, corrosion resistant and powder coated glidig hinges for smooth and noiseless movement of windows and advanced locking arrangements
Providing and fitting of 3.5 core, KLPE.1.1KV grade armored aluminum cable of various sizes conforming to IS: 7098 part Ist as service line from the HT transformer to control panel including necessary thimbling, crimping, taping etc.
50 sq mm , 3.5 core, LT Cable
25 sq mm 2 core. LT cable
Providing and fitting of 3- core flat submersible copper cable conforming to IS: 694 (Part-1) 1964 & IS: 694 (Part-ii) the cable connections terminal shall be fitted with copper thimbles of required size. Size 10sq mm.
P/I of chemical earthling station for electric substation, LT panel and stabilizer comprising of company abricated erthinng electrode as per IS: 3043. The includes Auguring of bore of required dia/ depth for installation of electrode along with backfill compound mixed with soil and all other items required therof for achieving the best result. The job includes connecting of electric gadgets through GI strip as per relevant standards.
Supply, installation of 6 kg CO² extinguisher should be suitable for class B&C fire and also for fire involving electrical equipment’s
Providing, laying & fixing with adhesive/bonding material of insulation rubber mats on the floor of the pump house, covering area around electro –mechanical machinery for safeguarding the life & limb of the workmen due to possible leakage of current & short circuit. The floor surface shall be made good & shall be free from dust, grease, foreign material & moisture free. The mats shall be as per IS 15652:2006 & shall have the following specifications:
Hydro Engineers
stage.html
html • 0.02 MB
finance_538979.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .