Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹7.8 LAccepted-AOC N A | ₹7.8 L | 1 | Accepted-AOC L1 |
| 2 | 2₹8.2 LRejected-Finance KAUTILYA APPT MIG 133 PKT B PH II SEC 14 DWARKA NEW DELHI 110075 | SOUTH WEST DELHI | DELHI | 110075 | ₹8.2 L | 2 | Rejected-Finance 2 |
| 3 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Others-Registration not valid as per NIT |
Tender Value
₹9.2 L
EMD Value
₹19,500
Closing Date
25 May 2026, 11:00 amClosed
EE/Elect./Auto/EM/CLZ
EE/Elect./Auto/EM/CLZ
Providing and fixing of lights in J Block Jahangir puri, Dhaka, Mukherjee Nagar Old, Mukherjee nagar New, SFS-I, SFS-II, Nehru Vihar-I, Nehru Vihar-II, Gopal Pur, Gandhi Vihar Pumping station and Timar pur Store under Civil line zone.
2026_MCD_277761_1
EE/Elect/EndM/ Auto/RZ/2026-27/TC/04.1
Open Tender
Electrical Works
60 days
EE/Elect./Auto/EM/CLZ
Please refer Tender documents.
3 documents required · 3 mandatory
₹590
₹19,500
15 Jun 2026
16 May 2026
25 May 2026
16 May 2026
25 May 2026
16 May 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1.001 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy >135 lm/Watt)
Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). (a) 50 watt | 80 | Each | 2,089 | ₹1,67,120 |
| 2.001 | 100 watt | 12 | Each | 2,567 | ₹30,804 |
| 3.001 | LED Batten light (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) (a) 18- 22 Watt | 138 | Each | 787 | ₹1,08,606 |
| 4.001 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V "C" curve DP MCB complete with connections, testing and commissioning etc. as required. | 16 | Each | 1,258 | ₹20,128 |
| 5.001 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C"curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (a) Single pole | 30 | Each | 285 | ₹8,550 |
| 6.001 | (b) Double Pole | 12 | Each | 696 | ₹8,352 |
| 7.001 | Supply of 250 mm (10 inch) sweep 1250 rpm exhaust fan complete with shutter blades etc. as required. | 12 | Each | 1,955 | ₹23,460 |
| 8.001 | Supply of 15" (380mm) sweep 1400 rpm exhaust fan heavy duty complete with shutter blades etc. as required. | 18 | Each | 3,061 | ₹55,098 |
| 9.001 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required Upto 450 mm sweep | 30 | Each | 556 | ₹16,680 |
| 10.001 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. . 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) | 30 | Each | 2,695 | ₹80,850 |
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.23 MB
TenderCondition.pdf
Tender Documents • 0.44 MB
MCD_GCC_2025Updated2026.pdf
Tender Documents • 16.45 MB
BOQ_324348.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid