Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.6 LAccepted-AOC 3 4 JEEVAN DEEP BUILDING 10 PARLIAMENT STREET NEW DELHI 1 PH 011 43573493 9899713006 | L1 | Accepted-AOC L1 | |
| 2 | L2₹19.7 L+₹2.1 L (12.1%)Rejected-Finance 4TH FLOOR VOLTAS HOUSE A BLOCK DR BABASAHEB AMBEDKAR ROAD CHINCHPOKLI MUMBAI MAHARASHTRA 400033 | MUMBAI | MAHARASHTRA | 400033 | L2 | Rejected-Finance L2 |
Tender Value
₹18.6 L
EMD Value
₹37,300
Closing Date
31 Oct 2022, 12:00 pmClosed
AGM (E-E)
Asst. General Manager (Engg-Elect), Airports Authority of India, Southern Region, Operational Offices, Chennai Airport, Chennai 600 016
Replacement of AHUs (Phase-I, 8 Nos.) of ATS Complex, Southern Region, Chennai Airport. SH Replacement of AHUs at ATC Control Tower and Automation Area
2022_AAI_130554_1
AAI/RHQ-SR/AGM(E-E)/AHUs/2022
Open Tender
Electrical Works
Item Rate
181 days
ATS Complex
Please refer Tender documents.
18 documents required · 18 mandatory
₹1,120
₹37,300
27 Jan 2023
30 Sept 2022
1 Nov 2022
30 Sept 2022
31 Oct 2022
30 Sept 2022
30 Sept 2022 - 7 Oct 2022
Dismantling the existing air handling units of following capacity i/c motor, blower, cooling coil, electrical panel, Chilled water pipelines at Inlet & Outlet of AHUs upto 3-way mixing valve, etc with all associated accessories and handing over of all dismantled items to AAI stores, including transportatioin, etc complete as required.
9.27 TR capacity at ATC control tower
28 TR capacity at Second floor & Third floor
Supply of factory built floor mounted chilled water double skin type Air Handling Units made of 25mm thick panels consisting pre plasticised G.I casing of thickness 0.8mm outside layer and 0.8mm inside layer with polyurethene foam(PUF) insulation having 38 kg/cu.M density, factory injected between them by injection moulding machine, complete with blower section with Backward curve blower, blower suitable for static pressure as detailed below, PVC drift eliminators, cooling coil section with aluminium finned copper tubes (tube thickness not less than 0.5mm) cooling coil, filter sections with 50mm thick metal viscous /washable synthetic type air pre-filters, belt drive package with TEFC drive motor of efficiency class IE5 suitable for 415 ± 10% volts, 50Hz, 3 phase, AC Supply, suitably designed for variable frequency drive applications, drain connections, stainless steel (18G) drain pan with PUF insulation, LED light with door switch, Provision to install UVGI lamps between cooling coil and blower, PCC cubicals to position the base frame of AHUs, necessary vibration isolation arrangement etc., complete as per specification and of following capacities:
a)10 TR Capacity, 5,600 CFM b)K.Calorie per hour-30,000 c)C.M Hr.- 9,515 d)Rows deep-4 e)Static pressure -55mmWC f) Pre-Filter: Having Filtration standard-90% efficiency down to 10 Microns g) MERV-13 Box type filter - 6 nos having size 540x540x300D each & to be fixed on the existing frame in the supply air Plenum. h) Supply blower - 1 No
a)30 TR Capacity, 16,800CFM b)K.Calorie per hour-90,000 c)C.M Hr.- 28,544 d)Rows deep-4 e)Static pressure -75mmWC f) Pre-Filter: Having Filtration standard-90% efficiency down to 10 Microns g) MERV-13 Box type filter - 9 nos having size 540x540x300D each suitable for 2000CFM & to be fixed on the existing frame in the supply air Plenum. h) Supply blower - 1 No
Installation, Testing & Commissioning of above air handling units at following locations for successful operation i/c refixing of dismantled UV lamp system, etc complete as required. Note: Since the location of item no 3.1 (i.e. 10 TR AHUs) is 30mtr hight from ground level and narrow passage to shift the materail to AHU room, the agencies are requested to inspect the site before qouting their rates.
10 TR & 5,600 CFM Capacity at ATC Control Tower (Fifth floor)
30 TR & 16,800 CFM Capacity at Third floor of ATS Complex
The associated works complete to enable the commissioning of AHUs as required as below: a) Necessary modification in the existing GI ducting to made suit the mouth connection with the new AHU including supply & fixing of necessary thermal & acoustic insulation as required b) Necessary modification in the existing MS Chilled water pipeline including supply & fabrication of required new MS 'C' class pipes, 2 nos drain valves, supports, insulation with PUF sections, vapour barrier, GI wire mesh, sand cement plastering, Coloring, etc between butterfly valves & AHU. c) Necessary modification in the existing drain water piping for trouble free draining of condensate water including fabricating, supplying, fixing a 'U' trap with both side flanges (easy removal for cleaning) at the drain outlet of AHU. d) Termination of existing power cable, earth wires, control cables, etc
10 TR & 5,600 CFM Capacity at ATC Control Tower (Fifth floor)
30 TR & 16,800 CFM Capacity at Third floor of ATS Complex
10 TR & 5,600 CFM Capacity AHU at ATC Control Tower (Fifth floor)
30 TR & 16,800 CFM Capacity AHU at Third floor of ATS Complex
Supply of following size butterfly valve wafer type with matching flanges, bolt nuts and insulation for chilled water header pipes in the AHU rooms.
100 mm dia
Fixing of following size butterfly valves wafer type with matching flanges, bolt nuts, insulation, etc after made cutting in the existing chilled water header pipes of AHU rooms including removal of existing insulation etc complete as required.
100 mm dia
Supply of following size butterfly valve wafer type with matching flanges, bolt nuts and insulation for supply & return chilled water pipes of AHUs.
80 mm dia
50 mm dia
Fixing of following size butterfly valve wafer type with matching flanges, bolt nuts, insulation, etc after made cutting in the existing supply & return chilled water pipes of AHUs including removal of existing insulation etc complete as required.
80 mm dia
50 mm dia
Supply of following size balancing valve with matching flanges and insulation
80 mm dia
50 mm dia
Fixing of following size balancing valve with matching flanges and insulation
80 mm dia
50 mm dia
Supply of following size MS " Y" Strainer with matching flanges and insulation
80 mm dia
50 mm dia
Fixing of following size MS " Y" Strainer with matching flanges and insulation
80 mm dia
50 mm dia
Supply of following size 3-way Modulating valve with actuator, matching flanges, insulation. Thermostat with temperature adjustment, necessary wiring for normal working, etc complete as required.
80 mm dia
50 mm dia
ITC of following size 3-way Modulating valve with actuator, matching flanges, insulation. Thermostat with temperature adjustment, necessary wiring for normal working, etc complete as required.
80 mm dia
50 mm dia
Supply of 25 mm ball valve with MS pipe nipple for AHU Chilled water Header lines
Fixing of 25 mm ball valve with MS pipe nipple for AHU Chilled water Header lines
Supply of industrial type Thermometer with adopter for AHU chilled water line,etc complete as required.
Fixing of industrial type Thermometer with adopter for AHU chilled water line,etc complete as required.
Supply of dial type Pressure gauges having 150mm dia for AHUs including forged ball valves and pipe stem,etc complete as required.
Fixing of dial type Pressure gauges having 150mm dia for AHUs including forged ball valves and pipe stem,etc complete as required.
Supply of Canvass Connection between AHU & Duct made of fire retardant type cloth etc complete as required.
Fixing of Canvass Connection between AHU & Duct made of fire retardant type cloth etc complete as required.
Supply of Opposed blade G.I Construction box type factory fabricated duct Volume Control Damper made of 18 SWG thick GI Sheet complete with nuts, bolts, screw, linkage, flanges, etc duct lever and quadrants etc complete as required.
ITC of Opposed blade G.I Construction box type factory fabricated duct Volume Control Damper made of 16 SWG thick GI Sheet complete with nuts, bolts, screw, linkage, flanges, etc duct lever and quadrants etc complete as required.
VOLTAS LIMITED
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .