Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.8 LAccepted-AOC | L1 | Accepted-AOC Being the Lowest bidder | |
| 2 | L2₹14.8 L+₹3.9 L (35.9%)Rejected-Finance C O OPPOSITE MH MANDA POONCH ROAD AKHNOOR 181201 J K | JAMMU | JAMMU AND KASHMIR | 181201 | L2 | Rejected-Finance L2 | |
| 3 | L3₹18.0 L+₹7.1 L (65.4%)Rejected-Finance C O SECTOR 02 HOUSING COLONY CHANNI HIMMAT JAMMU J K PIN 180015 | JAMMU | JAMMU AND KASHMIR | 180015 | L3 | Rejected-Finance L3 |
| Sl No | Description | Qty | Unit | M/S JIWAN SINGH L1 | MAMTA ENTERPRISES L3 | Usha Engineering Co. L2 |
|---|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing and commissioning of Indoor type Metal Clad VCB, totally enclosed & fully interlocked horizontal draw out type breaker as per IEC 6227-100. 3.3/6.6/11KV, single break trip free breker with motor operater spring charged mechanism, complete with self contained operated fully internlocked rack in & rack out mecsm. Breaker is featured with mechinical ON & OFF Indicator with hand trip device, spring release coil, shunt trip coil & auxialry switch off 4NO+4NC - Breaker current rating 800 A and extensive type busbar connection with existing VCBs including complete wiring with the existing wiring system including taking down of the unserviceable VCB compartment, 750 MVA, tripping coil voltage 30 v DC, short circuit time 1 sec, insulation level 75 KV peak with controls & relays as under & all as specified fitted of following :-
a. Manually changing & closing mechanism, 1- motorised spring charged closing mechanism.
i. Mechanical close/strip knob- 01 set .
ii. Mechanical ON/OFF indicator- 01 No
iii. Mechanical spring charged/ free indicator -01 No
iv. 1- set of 6 Nos + 6 NC Aux contact block - 01 No
v. DC 30 volt, shut strip - 01 No
b. 1- set space heaters 1x60 watt -03 nos, 230v AC with switch humidity sensor and thermostat.
c. VCB ON & OFF switch, trip ckt heating, auto trip, seice position, test position.
d. 1- set of Red/ Green indicating lamps for circuit breaker on/ off auto trip indication.
e. 3 resin cast type twin secondary current transformer of ratio 300-100/5-5A, class of accuracy 0.5/5P10, burden 10VA/10 VA burden for protection & metering.
f. 1-3 phrasing cast draw out type potential transfer ratio 11 KV root 3/ 110V class 0.5 accuracy. 50 VA/ph burden, complete HT & LT fuses and connected to incoming side ( one per incoming VCB )
luminous push button for trip circuit check.
g. microprocessor based relay with local display & communication port.
h.multifunction electronic digital meter consisting of measurement of current, voltage frequency, KW, KWH, KWARH etc type PM 500.
i. 1 No- cut out plate for cable entry for 300 sq mm 3 core cable.
j. PVC FRLS copper cable single core multistranded of size 2.5 sq mm for all control wiring.
k. MCB DP 32A- 01 No for control supply.
( make for VCB :- Schnfider ) | 1 | Each | 3,72,222 ₹3,72,222 Lowest | 11,99,999 ₹11,99,999 | 7,98,765 ₹7,98,765 |
| 2.00 | Repair of 33 Kv control and relay ( repair of control Wiring, master trip each relays, switches etc. ) | 2 | Each | 7,222 ₹14,444 | 5,000 ₹10,000 Lowest | 22,000 ₹44,000 |
| 3.00 | Supply only control cable 8 core armoured control 2.5 sqmm copper for RM interconnectiong from remote panel to VCB outdoor unit all as directed. | 170 | RM | 350 ₹59,500 Lowest | 600 ₹1,02,000 | 680 ₹1,15,600 |
| 4.00 | Supply only control cable 4 core armoured control cable 2.5 sqmm copper for RM interconnection from remote panel to VCB outdoor unit. | 205 | RM | 300 ₹61,500 Lowest | 500 ₹1,02,500 | 360 ₹73,800 |
| 5.00 | Repair and maintance of battery charger 36 volts, DC stationery automatic floot each cum boostiner trickle battery bank having 16 nos batteries , each cell having voltage job 2x100 AH for 33KV remote control braker panel/11KV VCB panel including free maintance , battery complete maint free batteries of 2 volt 100 AH 16 nos with battery stant and other accessories. | 1 | Each Job | 30,000 ₹30,000 Lowest | 85,000 ₹85,000 | 74,000 ₹74,000 |
| 6.00 | Repair and maintenance of FCBC battery charging unit. | 1 | Each Job | 2,28,222 ₹2,28,222 | 15,000 ₹15,000 | 6,000 ₹6,000 Lowest |
| 7.00 | Repair of 33 KV SF 6 braker outdoor type and control wiring tripping and control circuit and overhauling etc. | 2 | Nos | 22,222 ₹44,444 | 7,000 ₹14,000 Lowest | 24,000 ₹48,000 |
| 8.00 | Maintenance of 33 KV roatating, horizontal type, isolator switch 400 Amp complete with Greasing, Tightening of nut and bolts, jaw contracts etc after disconnecting all electric connections all as directed. | 1 | Nos | 15,222 ₹15,222 | 5,000 ₹5,000 Lowest | 16,000 ₹16,000 |
| 9.00 | Numerical IDMT 3 overcurrent with 1 earthfault. | 1 | Nos | 42,222 ₹42,222 | 25,000 ₹25,000 | 21,000 ₹21,000 Lowest |
| 10.00 | Battery bank of capacity 30 V ( consisting of 15x2V battery interconnected in series for 11 KV. | 1 | Nos | 1,05,000 ₹1,05,000 | 1,55,000 ₹1,55,000 | 78,000 ₹78,000 Lowest |
Tender Value
₹19.3 L
EMD Value
₹38,700
Closing Date
19 Jul 2025, 9:00 amClosed
Anurag Anand DCWE
HQ 135 WKS ENGRS PIN 914135
Spl repair/replacement of HT VCB Incomer at main Power House at Akhnoor Mil Stn under GE (S) Akhnoor
2025_MES_714602_1
CWE/JA-06/2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AKHNOOR
AS PER NIT
9 documents required · 9 mandatory
₹500
GE SOUTH AKHNOOR
₹38,700
18 Oct 2025
14 Jun 2025
26 Jul 2025
14 Jun 2025
19 Jul 2025
28 Jun 2025
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .