Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹45.2 CrAccepted-AOC YOGESHWARI NAGARI RING ROAD AMBAJOGAI | AMBAJOGAI | BEED | MAHARASHTRA | ₹45.2 Cr | L1 | Accepted-AOC Accepted-Finance |
| 2 | L2₹46.1 CrAccepted-AOC THIRD FLOOR AMIT CRYSTAL SENAPATI BAPAT ROAD PUNE 411 016 | PUNE | PUNE | MAHARASHTRA | 411016 | ₹46.1 Cr | L2 | Accepted-AOC Rejected Finance |
| 3 | L3₹46.8 CrAccepted-AOC OFFICE NO 515 PLOT NO 194 NMS ICON SECTOR 19 ULWE NAVI MUMBAI MAHARASHTRA 410206 | NAVI MUMBAI | THANE | MAHARASHTRA | 410206 | ₹46.8 Cr | L3 | Accepted-AOC Rejected Finance |
Tender Value
₹43.0 Cr
EMD Value
₹21.6 L
Closing Date
6 Sept 2024, 6:55 pmClosed
Executive Engineer, Public Works Division, Beed
Executive Engineer, Public Works Division, Beed
Construction of Mahsul Bhavan, Type-II, Type-III and Type-IV Revenue Quarters and Balance Work of Collector Bunglow Allied Works at Beed Dist. Beed
2024_PWR_1075145_1
PWD_Beed/1E/2024-25
Open Tender
Civil Works
545 days
Beed
Please refer tender document
2 documents required · 2 mandatory
₹5,900
₹21.6 L
Yes
office of the C Engineer, P W Region Ch. Samnhajin
7 Oct 2024
23 Aug 2024
9 Sept 2024
23 Aug 2024
6 Sept 2024
23 Aug 2024
27 Aug 2024
Amount
Excavation for foundation in earth, soil of all types, sand, gravel and soft murum, including removing the excavated material up to a distance of 50 metre beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etcetera complete. (Lift upto 1.5 metre) By Mechanical Means
Excavation for foundation in earth, soils of all types, sand,gravel and soft murum, including removing the excavated material upto a distance of 50 Metre beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etcetera complete. (Lift from 1.50 metre to 3.0 metre) By Mechanical Means
Filling in plinth and floors with approved excavated material in 15 centi metre. to 20 centi metre layers including watering and compacting etcetera complete.
Filling in plinth and floors with contractors material/brought from outside and approved by Engineer incharge in layers of 15 centi metre to 20 centi metre including watering and compaction etcetera complete.
Conveying materials obtained from road cutting including all lifts, laying in layers of 20 centi metre to 30 centi metre breaking clods, dressing to the required lines, curves, grades and section, watering and compacting to not less than 97% of standard Proctor density for a lead of over 50 metre to 300 metre inclusive from the site of excavation to the site of deposition as directed.
Conveying materials obtained from road cutting including all lifts, laying in layers of 20 centi metre to 30 centi metre breaking clods, dressing to the required lines, curves, grades and section, watering and compacting to not less than 97% of standard Proctor density for a lead of over 50 metre to 300 metre inclusive from the site of excavation to the site of deposition as directed.
Providing soling using 80 mili metre size trap metal in 15 centi metre layer including filling voids with Crushed sand/grit, ramming, watering etcetera complete.
Providing preconstructional antitermite treatment as per Indian Standard 6313 (Part-II) by treating the bottom surface and sides of excavation at the rate of 5 litres of emulsion concentrate of 1.0 percent of chlorophyrifos per square meter of surface area covering 10 years guarantee on bond paper.
Providing preconstructional antitermite treatment as per Indian Standard 6313 (Part-II) treatment by treating the backfill in immediate contact with foundation at the rate of 5 litres of emulsion concentrate of 1.0 percent of clorophyrifos per square metre of vertical surface area covering 10 years guarantee on bond paper.
Providing preconstructional antitermite treatment as per Indian Standard 6313 (Part-II) by treating the top surface of plinth filling at the rate of 5 litres of emulsion concentrate at 1.0 percent of clorophyrifos per square metre of surface area covering ten years guarantee on bond paper.
Providing preconstructional antitermite treatment as per Indian Standard 6313 (Part-I) to the soil along the external face of building by punching holes of 1.2 of 1.5 Cement Mortor diametre about 30 -60 centi metre deep at 15 centi metre centre to centre as close to the wall as possible and to inject 0.5 percent of aldrin or clorophyrifos at the rate of 7.5 litres per hole and sealing the same with proper filling and covering 10 years guarantee on bond paper.
Providing and laying Cast in situ/Ready Mix cement concrete in M-10 of trap/ granite/ quartzite/ gneiss metal for foundation and bedding including bailing out water, Steel centering, formwork, laying/ pumping, compacting, roughening them if special finish is to be provided, finishing if required and curing complete, with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying Cast in situ/Ready Mix cement concrete in M-15 of trap/ granite/quartzite/gneiss metal for bed blocks, foundation blocks and such other items including bailing out water, Steel centering, formwork, laying/ pumping, compacting, roughening them if special finish is to be provided, finishing uneven and honeycombed surface and curing etcetera complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface only. Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etcetera (Wooden centering will not be allowed.), with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying in situ cement concrete M-30 with tremix treatment for 200 mili metre thickness for flooring with groove cutting of 4 mili metre wide and 20 mili metre deep with necessary refilling with bitumen etcetera complete.
Providing and laying Cast in situ/Ready Mix cement concrete in M-15 of trap/ granite/quartzite/gneiss metal for plain or molded sills, cornice, jambs, block in course, or architraves of required size and shapes including steel centering, formwork, laying/ pumping, compacting, roughening them if special finish is to be provided,finishing uneven and honeycombed surface and curing etcetera complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface only. Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etcetera (Wooden centering will not be allowed.) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-15 of trap/ granite/quartzite/gneiss metal for coping to plinth or parapet, moulded or chamfered as per drawing or as directed including steel centering, plywood/ steel formwork compacting, roughening them if special finish is to be provided, finishing uneven and honeycombed surface and curing etcetera complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface only. Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etcetera (Wooden centering will not be allowed.) With fine aggregate (Crushed sand VSI Grade)
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap / granite /quartzite/ gneiss metal for Reinforced Cement Concrete work in foundations like raft, strip foundations, grillage and footings of Reinforced Cement Concrete columns and steel stanchions etcetera including bailing out water, Steel centering, formwork ,cover blocks, laying/ pumping, compaction and curing roughening the surface if special finish is to be provided (Excluding reinforcement and structural steel) etcetera complete, with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap / granite /quartzite/ gneiss metal for Reinforced Cement Concrete columns as per detailed designs and drawings or as directed including steel centering, formwork, cover blocks, laying/ pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etcetera complete,(Excluding reinforcement and structural steel) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and laying Cast in situ/Ready Mix cement concrete in M-25 of trap/ granite/ quartzite/ gneiss metal for Reinforced Cement Concrete beams and lintels as per detailed designs and drawings or as directed including steel centering, formwork, cover blocks, laying/ pumping, compactionand roughening the surface if special finish is to be provided and curing etcetera complete. (Excluding reinforcement and structural steel) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap/ granite / quartzite/ gneiss metal for Reinforced Cement Concrete slabs and landings as per detailed designs and drawings including steel centering, formwork, cover blocks, laying/ pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etcetera complete,(Excluding reinforcement and structural steel) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap/ granite/ quartzite/ gneiss metal for Reinforced Cement Concrete chajja as per detailed design and drawings including steel centering, formwork, cover blocks, laying/ pumping, compacting and roughening the surface if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap / granite / quartzite / gneiss metal for Reinforced Cement Concrete canopy as per detailed designs and drawings including steel centering, formwork, laying/ pumping, compacting and roughening the surface if special finish is to be provided and curing etcetera complete (excluding reinforcement). with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
A] Parking Floor/Ground Floor
B] First Floor
Providing and laying Cast in situ/Ready Mix cement concrete in M-25 of trap/ granite/ quartzite/ gneiss metal for Reinforced Cement Concrete pardi of required thickness including steel centering, formwork, cover blocks, laying/ pumping, compacting and roughening them if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and laying Cast in situ/Ready Mix cement concrete in M-25 of trap / quartzite /granite /gneiss metal for Reinforced Cement Concrete Waist slab, and steps of staircases as per detailed design and drawings or as directed including steel centering, plywood/ steel formwork, steel props, laying/ pumping, compaction, finishing uneven and honeycombed surface with Cement Mortor 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening the surface if special finish is to be provided and curing etcetera complete. (Excluding reinforcement, including cover block).(Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etcetera) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing in position Thermo Mechanical Treated (TMT) - FE - 500 bar reinforcement of various diameters for Reinforced Cement Concrete pile caps, footings, foundations, slabs, beams columns, canopies, staircase, newels, chajjas, lintels pardis, copings, fins, arches etcetera as per detailed designs, drawings and schedules. including cutting, bending, hooking the bars, binding with wires or tack welding and supporting as required complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fabricating structural steel work in rolled sections like joists, channels, angles, tees etcetera as per detailed design and drawings or as directed including cutting, fabricating, hoisting, erecting, fixing in position making riveted / bolted /welded connections without connecting plates, braces etcetera and including one coat of anticorrosive paint and over it two coats of oil painting of approved quality and shade etcetera complete.
A] Parking Floor/Ground Floor
C] Second Floor
E] Fourth Floor
F] Fifth Floor
Providing fly ash brick masonry with conventional / Indian Standard type fly ash bricks in Cement Mortor 1:6 in foundation and plinth including bailing out water manually striking joints, racking out joints watering and scaffolding etcetera complete.
A] Parking Floor/Ground Floor
Providing Autoclaved Aerated Concrete Block masonary of Ecolite or equivalent make conforming to IS:2185 (Part 3) - 1984 in extra fine jointing mortar of fixoblock of UltraTech or equivalent in superstructure including striking joints, raking out joints and scaffolding etcetera Complete. (The test shall be carried out conforming to IS:6441 (Part I) - 1972)
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing Autoclaved Aerated Concrete Block masonary of Ecolite or equivalent make conforming to IS:2185 (Part 3) - 1984 in extra fine jointing mortar of fixoblock of UltraTech or equivalent in Half brick thick wall including striking joints, raking out joints and scaffolding etcetera Complete. (The test shall be carried out conforming to IS:6441 (Part I) - 1972)
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing Brick Masonry with first Class Wire cut bricks of good quality of size 218 x 101 x 76 mm for superstructure in cement mortor 1:4 bricks of uniform size laid flush in mortor in a bond as per pattern illustrated on drawings and as directed by the Engineer - in - charge with joints not more than 9mm, including scafolding,racking out joints, watering, cleaning, curing. including all texes, lead, lift, labour etc. complete. Spec. As directed by Engineer in charge.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
Providing cement based water proofing treatment to terraces (Indian water proofing or alike) with brick bats laid in required slope to drain the water for any span after cleaning the base surface. Applying a coat of cement slurry admixed with approved water proofing compound and laying the brick bats on bottom layer in Cement Mortor1:5 admixed with approved water proofing compound filling up to half depth of brick bats, curing this layer for 3 days, applying cement slurry over this layer joints of brick bats with Cement Mortor1:3 admixed with approved water proofing compound and finally top finishing with average 20 mili metre. thick layers of same mortar added with jute fiber at 1 Kilogram per bag including finishing the surface smooth with cement slurry admixed with approved water proofing compound. Marking finished surface with false squares of 300 mili metre x 300 mili metre making the junctions at the parapet rounded and tapered top for required height, with drip mould at the junction of plaster and parapet and curing and covering 10 years Guarantee against leakproofness on Court fee stamp paper of Rs. 500/- including ponding test etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing water proof bedding for flooring of Bath and Water Closet 25 mili metre thick in Cement Mortor 1:3 including using approved water proofing compound in specified proportion as per manufacturers specifications for per bag of cement including leveling, curing and covering 10 years guarantee on court fee stamp paper of Rs.500/- including ponding test etcetera complete.
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and applying two coats of High Albedo paint having minimum Solar Reflective Index (SRI) 108 (with solar reflectance & thermal emittance tested as per ASTM) C 1549 and ASTM C 1371 respectively, VOC less than 10 cc/gm. The coating thickness and the methodology of application shall strctly as per manufacturer's specifitions and as approved by engineer in charge. Surface preparation includes cleaning with metal wire brush to remove all dust, fungus etcetera washing with water all complete.The contractor shall give guarantee for the performance of SRI and also the durabitity of coating, all complete as per direction of Engineer - in- incharge.
A] Parking Floor/Ground Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing internal cement plaster 12 mili metre thick in single coat in cement mortar 1:5 without neeru finish to concrete or brick surfaces, in all positions including scaffolding and curing etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and applying plaster / wall punning with plaster of paris ( with plaster of paris material of Ambuja / Mor Chap or equivalent make ) in 10 to 13 mili metre thickness to previously plastered surface / or on newly brick surface (Excluding rough cast plaster) in all position including preparing and Finishing the surface scaffolding etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing sand faced plaster externally in cement mortar using approved screened sand, in all positions including base coat of 15 mili metre thick in cement mortar 1:4 using waterproofing compound at 1 Kilogram per cement bag curing the same for not less than 2 days and keeping the surface of the base coat rough to receive the sand faced treatment 6 to 8 mili metre thick in cement mortar 1:4 finishing the surface by taking out grains and curing for Fourtheen days scaffolding etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing fine cement finish 1.5 mili metre thick over green plaster surface including scaffolding curing etcetera complete.
A] Parking Floor/Ground Floor
Providing patti/ band 75 mili metre wide on plastered surface 12 mili metre to 15 mili metre thick in Cement Mortor 1:3 line and level including neat finishing scaffolding curing etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing patti/ band 100 mili metre wide on plastered surface 12 mili metre to 15 mili metre thick in Cement Mortor 1:3 line and level including neat finishing scaffolding curing etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing patti/ band 150 mili metre wide on plastered surface 12 mili metre to 15 mili metre thick in Cement Mortor 1:3 line and level including neat finishing scaffolding curing etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing chicken mesh of 22 gauge, with about 30 centi metre width at the junction of Reinforced Cement Concrete members and brick work, of approved quality including fixing mesh in position by necessary drilling in concrete /Burnt Brick Masonry and or tying by binding wire etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and applying Two coats of wall care Putty on plastered surface and Ceiling and Walls to prepare surface even and smooth of approved make, etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing Modular false ceiling of 600 x 600 mili metre center to center and 13 mili metre thick square mineral fiber board to be fixed on frame work of alluminium sections for suspended false ceiling consisting of alluminium T 2”x1 ½” (50 mili metre x 40 mili metre) weighing 0.39 Kilogram/ metre at 60 centi metre center center and fixed with ½” x ½” (15 x 15 mili metre) flanges weighing 0.19 Kilogram/ metre suspended on 6 mili metre diametre mild steel rod weighing 0.22 Kilogram/ metre, fixed on wall and beams including rounding of the edges with alluinium T of 2” x 1 ½” (50 mili metre x 40 mili metre) weighing 0.39 Kilogram/ metre etcetera (all alluminium sections shall be anodized) including all labour, material, lifts etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing groove to required size at specified location as directed by Engineer, at junction of brick masonry wall and Reinforced Cement Concrete beams or Column, at junction of composite masonry, including scaffolding, finishing, curing etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and laying vitrified matt fininsh tiles having size 590 mili metre to 605 mili metre x to 605 mili metre of 8 to 10 mili metre thickness and confirming Indian Standard 15622-2006 (Group Bla) of approved make, shade and pattern for flooring in required position laid on a bed of 1:4 cement morar including neat cement float, filling joints, curing and cleaning etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and laying vitrified stone effect finish tiles having size 590 to 605 mili metre x 590 to 605 mili metre of 8 to 10 mili metre thickness and confirming to Indian Standard 15622-2006 (Group Bla) of approved make, shade and pattern for dado & skirting in required position laid on a bed of 1:4 cement mortar including required position laid on a bed of 1:4 cement mortarincluding neat cement float, filling joints, curign and cleaning etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and laying ceramic tiles having size 30 centi metre x 45 centi metre confirming to corresponding Indian Standard for dado and skirting in required position with readymade adhesive mortar of approved quality on plaster of 1:2 cement mortar including joint filling with white/ colour cement slurry cleaning curing etcetera complete.
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and laying Antiskid Ceramic tiles of approved quality of size 30 centi metre x 30 centi metre and Confirming to Indian Standard 15622-2006 (Group-B IIA) for antiskid flooring in required position laid on a bed of 1:4 cement mortar including cement float, filling joint with cement slurry cleaning curing etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing heavy duty inter locking concrete Coloured paving blocks of 80 mili metre thickness of having a strength of 300 Kilogram/Square Centi Metre of approved quality and shape on a bed of crushed sand of 25 to 30 mili metre thick including skirting joints and cleaning etcetera complete
Providing and laying machine cut machine Polished Kota stone flooring 25 mili metre to 30 mili metre thick and required width in plain/ diamond pattern on bed of 1:6 Cement Mortor including cement float, filling joints with neat cement slurry, curing, polishing and cleaning etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Providing Mirror polishing to Kota Stone including using all necessary stones and equipments cleaning, washing etcetera complete. For Flooring
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Providing and laying in position flooring of telephone black / Amba White / Cat bary brown / Ruby red / Ocean Brown granite stone of approved shade and size 18 mili metre to 20 mili metre thick on bed 1:6 cement mortar including cement floats striking joints, pointing in Cement Mortor 1:3 curing and cleaning etcetera complete.
Providing and fixing machine cut machine polished 18 mili metre to 20 mili metre thick telephone black / Amba White / Cat bary brown / RBI red / Ocean Brown granite stone for treads and risers of steps and staircases of approved colour and shade with full moulding and three grooved line for the treads on bed of 1:4 Cement mortar including float filling joints with neat cement slurry curing polishing and cleaning etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing leather finished polishing to Granite Stone slab by continuous grinding in 4 coats of different bits to receive rough and matt finish including buffing process before laying and fixing of stone as per drawing and design, including cleaning, washing and finishing etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and laying telephone black / Amba White / Cadburybrown / Ruby red / Ocean Brown granite stone of 18 to 20 mili metre thick for door frame/ dado/ window boxing etcetera On Cement Mortor 1:6 including filling joints with polymer base filler nosing/moulding the sharp edges wherever necessary, curing, etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and constructing granite kitchen platform with fixing of stainless steel sink 600 mili metre x 450 mili metre size as per detailed drawing including vertical both side polished kadappah stone 25 to 30 mili metre thick supports with kadappah top 35 to 40 mili metre thick and polished granite 16 to 20 mili metre top with side strips of granite at front and both sides of platform raised with two vertical granite supports 15 centi metre height and top granite of 75 x 40 centi metre including cutting, opening for sink of required size in kadappah as well as granite etcetera complete. (Platform top size 5.00 metre x 0.60 metre and height is 0.75 m)
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Kitchen Trolley Providing and Fixing stainless steel kitchen trolley of overall 26 " height and 22" depth,supported on aluminium pipes ,trolley basket made out of 5 mili Mild Steeltainless steel rod fitted on telescopic channel of size 1.5 " x 20 " x 22 " on both sides of trolley of 12 " or above size, panel having 40 Kilogram load bearing capacity of trolley made out of 20 mili metrePUC coated plywood and colour combination as directed by E-I-C.Inner side of panel covered by white mica ,100 mili Mild Steels. decorative handle.(The width and height of individual compartments shall be kept as directed by Engineer-in-charge)
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and applying priming coat on concrete/ masonary/ Asbestos Cement plastered surfaces including scaffolding if necessary, preparing the surface by thoroughly cleaning oil, grease, dirt and other foreign matter and sand papering as required etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and applying washable oil-bound distemper of approved colour and shade to old and new surfaces in two coats including scaffolding, preparing the surfaces. (excluding the primer coat.) etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and applying 2 coats of 100% Pure acrylic low VOC and APEO & HCHO free water based paint of approved colour that belongs to class 1 flame spread resistance of approved make Paint should provide durable and long lasting silk finish with a high crack tolerance of upto 1 mili metre Paint should have an oustanding washability with high resistance to wide range of bacteria and fungus. Paint has to be applied on smooth and uniform surface prepared by an acrylic copolymer low VOC & Odour putty. This surface should be primed with water based low VOC Primer. The work activity should cover all aspects of applying paints from surface preparation as directed by Engineer in charge.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and applying 2 Coats of 100% Pure acrylic water based paint with special heat reflectance property to withstand the harsh climate for period of atleast 10 years of approved make. Paint system should provide durable and long lasting finish with DFT of min 90 microns and should protect against concrete carbonation with R value of minimum 600 and equivalent concrete layer thickness value of min 150 centi metre Paint should have breathability property and should be able to cover hairline cracks in the surface upto 0.5 mili metre The paint has to be applied on a coat of high quality acrylic copolymer based alkali resistant primer with excellent penetrating properties including cleaning, with all leads and lifts at all levels etcetera complete, as directed by Engineer in charge.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and applying Dezzly texture paint of Hammer / Screetech on the external plastered surface of approved quality. As directed by Engineer in charge
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Providing and fixing in position, Double shuttered aluminium extruded powder coated openable door of specified size with aluminium door frame of powder coated section 101.60 x 44.75 mili metre, 3.18 mili metre thick and shutter comprising of powder coated section having bottom and lock rail of size 150 mili metre x 44.5 mili metre x 3.00 mili metre thick top rails 47.62 x 44.45 mili metre x 3.00 mili metre thick, vertical style 47.62 x 44.45 mili metre, 3.00 mili metre thick and for shutter plain glass panes 5 mili metre thick for top panels and 12 mili metre thick both side laminated phenol bonded particle board panels for bottom panels etcetera, Indian Standard Institute mark, heavy duty, Hydraulic floor spring of 150 Kilogram capacity, having heavy duty concealed lock, necessary beading, glazing clips, Polyvenyle Chloride gaskets, 250 mili metre length aluminium tower bolts, 150 mili metre diametre pad handle, etcetera as per detailed design and drawing or as directed by engineer in charge including all materials, labours, and equipment etcetera complete
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing in position structural glazing faces of building made out of colour anodized aluminium frame curtain wall of 63 mm x 57 mm x 2.20 mm thick including toughened reflective glass 5 mm thick of 900x1200 mm size. The item shall include toughened coloured reflective glass 5 mm thick water proofing silicon sealant, G.E. winsil 10/20, G.E.ultra glaze including alumnium fixtures.S3 screws and nut bolts, scaffolding , m.s.angle cleats and frame work of 65 mm x 65 mm x 6 mm and scaffolding etc. complete. Minimum 20% area of structural glazing shall be openable for openable panels. aluminum hinges, wind stays and locking arrangements and aluminum angle or tee section of required size as directed by Engineer in Charge Spec No. As directed by Engineer Incharge. Aurangabad DSR I.No.802, P.No.222 (Aurangabad DSR 2015-16)
A] Parking Floor/Ground Floor
B] First Floor
Providing and fixing 34 mili metre thick moulded door shutter consisting of solid core single leaf flush door of 30 mili metre thickness lipped with 15 mili metre( 5 mili metre x 3) thick x 30 mili metre width on one style and top rail and 10 mili metre(5 mili metre x 2) thick x 30 mili metre width on other style and bottom rails. The inner panels laminated with 2 mili metre thick termite proof, water proof and fire resistant moulded Polyvenyle Chloride sheet with 2,4,6 design in different plain and /or prelim colours on one side after routing the moulded design on flush doors and 2 mili metreplain and /or pre lam Polyvenyle Chloride on other side using rubber adhesive on flush door and solvent cement adhesive on the Polyvenyle Chloride lipping etcetera as per direction of Engineer in charge and manufacturers specification and drawing etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing in position powder coated aluminium louvered windows / ventilator of various sizes with powder coating as per detailed drawing and specifications including aluminium frames 80 x 38 mili metre x 1.22 mili metre box type, 5 mili metre thick sheet glass louvers, of approved quality etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and Fixing 30 mili metre thick BOTH SIDE PRELAMINATED SOLID PANEL Polyvenyle Chloride DOOR SHUTTER consisting of frame made out of Mild Steel tubes of 19 guage thickness and, size 19 x 19 mili metre for styles and 15 x15 mili metre for the top and bottom rails, Mild Steel frame shall have a coat of metel primer of approved make and manufacture. Mild Steel frame shall be covered with heat mouled Polyvenyle Chloride 'C' channel made from 5 mili metre(+/0.25) thick prelaminated sheet of density 600 Kilogram/cbm ,of size 30 mili metre thickness 70 mili metre width out of which 50 mili metre shall be flat and 20 mili metre shall be tapered in 45 angle on either side forming stiles ; and 5 mili metre thick ,95 mili metre wide Polyvenyle Chloride sheet out of which 75 mili metre shall be falt and 20 mili metre shall be tapered in 45 on the inner side to form top and bottom rail and 115 mili metre wide Polyvenyle Chloride sheet out of which 75 mili metre shall be falt and 20 mili metre shall be tapered on both sides to form lock rail.Top,bottom and lock rail shall be provided either side of the panel. An additional 5 mili metre(+/0.25) thick Polyvenyle Chloride strip of 20 mili metre width is to be stuck on the bottom side of the ' c ' channel prelaminated paneling of 5 mili metre(+/0.25) thick Polyvenyle Chloride sheet to be fitted inside the Mild Steel frame welded/ sealed to the styles and rails with 5 mili metre(+/0.25) x 30 mili metrePolyvenyle Chloride sheet beading on either side and joined together with solvent cement adhesive etcetera ,10 mili metre thickness (5 mili metre(+/0.25) x 2 nos ) 20 mili metre wide cross Polyvenyle Chloride sheet as gap insert for the rail and bottom rail. Door to be fixed to frames with 3 nos Mild Steelpowder coated but hinges of size 100 mili metre x 25 mili metre x 2 mili metre using 32 mili metre long steel screws drilled suitable to pass through both the walls of the Mild Steel tube. Other hardwares should be fixed with 19 x 6 mili metre size steel screws including fixture fasting. Complete as per direction of engineer in charge .
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing in position. (as per Indian Standard 1868 / 1982) Aluminium sliding window of two tracks with rectangular pipe having overall dimension 63.50 x 38.10 x 1.02 mili metre at weight 0.547 Kilogram/Running Metre and window frame bottom track section 61.85 x 31.75 x 1.20 mili metre at weight 0.695 Kilogram/Running Metre Top and side track section 61.85 x 31.75 x 1.30 mili metre at weight 0.659 Kilogram/Running Metre The shutter should be of bearing bottom 40 x 18 x 1.25 mili metre at weight 0.417 Kilogram/Running Metre Inter locking section 40 x 18 x 1.10 mili metre at weight 0.469 Kilogram/Running Metre And handle section 40 x 18 x 1.25 mili metre at weight 0.417 Kilogram/Running Metre and top section 40 x 18 x 1.25 mili metre at weight 0.417 Kilogram/Running Metre As per detailed drawings and as directed by Engineer in charge with all necessary Aluminium sections fixtures and fastenings such as roller bearing in nylon casting and self locking catch fitted in vertical section of shutter including 5 mili metre thick plain glass with all required screws and nuts etcetera complete. With powder coating without box
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing in position (as per 1868 / 1982) Aluminium sliding window of three tracks with rectangular pipe 95 x 38.10 x 0.90 mili metre at weight 0.637 Kilogram/Running Metre with window frame bottom track section 92 x 31.75 x 1.30 mili metre at weight 1.070 Kilogram/Running metre Top and side track section 92 x 31.75 x 1.30 mili metre at weight 0.933 Kilogram/Running Metre The shutter should be of bearing bottom 40 x 18 x 1.25 mili metre at weight 0.417 Kilogram/Running Metre Inter locking section 40 x 18 x 1.10 mili metre at weight 0.469 Kilogram/Running Metre and handle and top section 40 x 18 x 1.25 mili metre at weight o.417 Kilogram/Running Metre As per detailed drawings and as directed by Engineer-in-charge with all necessary Aluminium sections fixtures and fastenings such as roller bearing in nylon casting and self locking catch fitted in vertical section of shutter including 5 mili metre thick plain glass and aluminium mosquito net shutter with stainless steel jail with all required screws and nuts etcetera complete. With powder coating without box
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing M-40 grade thick vibrated pull cast or similar type concrete frame with chamfer conforming to Indian Standard 6524-1983 having 6 mili metre diametre bars 3 Numbers And stirrups @250 mili metre centre to centre and fixing in wall with 6 Nos of hold fast of 12 mili metre diametre bars 500 mili metre long including primer and oil painting etcetera complete) frame size 60 mili metre x 100 mili metre
C] Second Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing mild steel grill work for windows, ventilators etcetera 20 Kilogram/Square Metre as per drawing including fixtures, necessary welding and painting with one coats of anticorrosive paint and two coats of oil painting complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and Fixing mat finish stainless steel (of 302 grade ) railing with top pipe of 50 mili metre diametre and vertical pipe of 38 mili metre diametre at 0.60 metre centre to centre or as required and horizontal pipes of 25 mili metre diametre in three rows, all pipes of 2 mili metre thick including buffing,fabricating fixtures and fastening including pipe base of appropriate diameter and ball base of 75 mili metre diametre above newel post of 75 mili metre diametre etcetera complete (Prior approval of sample and brand by Executive Engineer is necessary before use)
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing C.P. 2 Way BIB cock with wall flange of approved make including necessary sockets/ union nut etcetera complete as directed by Engineer in charge.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing 25 mili metre diameter water meter with non-return valve including strainer, sockets/ union nut and including water meter box making locking arrangement and lock. [Without chamber].
Providing and fixing 15 mili metre diametre screw down bib/ stop tap of brass including necessary socket union nut complete.
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing 20 mili metre diametre screw down bib/ stop tap of brass including necessary socket union nut complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing screw down 15 mili metre diametre wheeled stop tap of brass including necessary sockets/union nut complete
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing push cock (Self closing tap) symet type of 15 mili metre diametre including necessary socket, testing etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing White glazed with bottle trap earthenware Wash Hand Basin of 63x45 centi metre size including cold water piller taps, brackets, rubber plugs and brass chain, stop tap, chromium plate bottle trap and necessary pipe connections including UPAC waste pipe and trap upto the outside face of the wall, making good the damaged surface, testing etcetera complete.
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
providing and fixing oval type under counter wash hand basin of 16 inch x 22 inch size and of special colour shade having telephonic black / coloured granite of 180 mili metre thick stone black kadappa framework including chromium plated coupling bottle - Trap using CERA company or equivalent oval typa wash basin model no 3448 as per detailed drawing or as directed by engg incharge etcetera complete. (Counter size 1.20 metre x 0.60 metre)
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing 15 centi metre x 10 centi metre salt glazed stoneware gully trap in cement concrete 1:4:8 outside the building including cast iron grating in the sink, connecting glazed stoneware pipe, brick masonry chamber with cast iron lid and cast iron grating for the gully trap.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and laying concrete pipes of Indian Standard NP. class of 150 mili metre diameter in proper line, level and slope including necessary collars, excavation, laying, fixing with collars in cement mortar 1:1 and refilling the trench complete.
Providing and laying concrete pipes of Indian Standard NP. class of 300 mili metre diameter in proper line, level and slope including necessary collars, excavation, laying, fixing with collars in cement mortar 1:1 and refilling the trench complete.
Providing, constructing and fixing 450 mili metre diametre Inspection chamber made up of Polypropylene / polyethylene material of thickness 3.5 mili metre and height of 388 mili metre with 160 or 200 mili metreain inlet (s) outlet and 110 and / or 160 mili metrebranch inlets, with 450 mili metre diametre Ultra shaft pipe of HDPE material having height of 460 mm, having Reinforced Cement Concrete cover and frame fixing in 150 mili metre thick in Cement Concrete1:2:4, having crushed sand bed of 150 mili metre thick of size 750 mili metre diametre Including excavation and refilling the sides of chamber by sand crushed cushioning 150 mili metre thickness, connecting all required Unplastisized Polyvenyle Chloride fittings with rubber lubricant etcetera complete.
Providing, constructing and fixing 600 mili metre diametre Inspection chamber made up of Polypropylene / polyethylene material Having 315 mili metre diametre inlet(s)/outlets and with eccentric reducers as per requirement to connect 160 mili metre and 200 mili metrepipes having thickness of 5 mili metre and 600 mili metre in height, with inbuilt shaft achieve the invert depth as per site condition of wall thickness of 5 mili metrehaving Reinforced Cement Concrete cover and frame fixing in 150 mili metre thick in Cement Concrete1:2:4, having crushed sand bed of 150 mili metre thick of size 750 mili metre diametre Including excavation and refilling the sides of chamber by ?sand crushed cushioning 150 mili metre thickness, connecting all required Unplastisized Polyvenyle Chloride fittings with rubber lubricant etcetera complete.
Providing and fixing 450 mili metre x 550 mili metre size superior type Belgium mirror with 16 mili metre diametre nickel plated towel rod etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing chromium plated towel rod 16 mili metre diametre and 75 centi metre in length including all accessories complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing stainless steel sink of size 600 x 510 x 200 mili metre incluidng coupling, outlet pipe, elbow and other necessary fitting, finishing etcetera complete.
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing C.P. Angular stop clock with wall flange of approved make continental including necessary sockets/union nut etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing C.P. BIB cock with wall flange of approved make including necessary sockets/ union nut etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing C.P. sink cock with raised J" shaped swinging casted spout ofapproved make including necessary sockets/ union nut etcetera complete."
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing 40 mili metre diametre Ball cock medium type with Polyvenyle Chloride float including sockets and necessary fittings and tested as per municipal requirements etcetera complete.
C] Second Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing 15 mili metre diametre Ball cock medium type with Polyvenyle Chloride float including sockets and necessary fittings and tested as per municipal requirement etcetera complete.
C] Second Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing wall mixer with over head shower, shower arm, hand shower with wall bracket having flow rate upto 12 liters/minutes of Jaquar/Cera/Hindware/Perryware or equivalent make including all necessary pipes, fittings etc. complete as directed by Engineer In Charge. (Make shall conform to manufacturer's Green product and shall got approved from the Engineer In Charge.)
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing C.P. wall mixer with provision for overhead shower with 115 mili metre long bend pipe and wall flange of approved make including necessary sockets/union nut etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and Fixing half turn 25 mili metre diametre gun metal flushing cock including all accessories etcetera complete.
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing Orissa Pan of size 580x445x260 mili metre with approved make flush valve including trap, Cast Iron soil and vent pipe upto outside face of wall including 100 mili metre diametre Cast Iron plug, bend and necessary pipe connection, etcetera complete. As directed by Engineer in charge.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing white Opal series European type wall-hung, of size 400 mili metrex370mmx575 mili metre with approved make flush valve including soil pipe, vent pipe upto outside face of wall, 100 mili metre diametre Cast Iron plug bend inlet pipe all fittings, cutting & making good walls, floors etcetera as directed by Engineer in charge.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing 75 mili metre diametre stabiliser pipe/ Poly Venyle Chloride soil vent/waste pipe and with necessary fixtures and fitting such as bends, tees, single junctions, slotted vent, clamps etcetera complete
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing 100 mili metre diametre stabiliser pipe/ Poly Venyle Chloride soil vent/waste pipe and with necessary fixtures and fitting such as bends, tees, single junctions, slotted vent, clamps etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing H.D.P container Syntex or alike one piece moulded water tank made out of low density polythyler and built corrugation including of delivery up to destination hoisting and fixing of accessories such as inlet, outlet overflow of all tanks capacity above 1000 to 20,000 litres
A] Parking Floor/Ground Floor
C] Second Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing on walls/ ceiling/ floor 15 mili metre diametre CPolyvenyle Chloride pipe with necessary fittings, remaking good the demolished portion etcetera complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing on walls/ceiling/floor 20 mili metre diametre CPolyvenyle Chloride pipe with necessary fittings, remaking good the demolished portion etcetera complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing on walls/ ceiling/ floor 25 mili metre diametre CPolyvenyle Chloride pipe with necessary fittings, remaking good the demolished portion etcetera complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing on walls/ ceiling/ floor 32 mili metre diametre CPolyvenyle Chloride pipe with necessary fittings, remaking good the demolished portion etcetera complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing on walls /ceiling/ floor 40 mili metre diametre CPolyvenyle Chloride pipe with necessary fittings, remaking good the demolished portion etcetera complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing on walls/ ceiling/ floor 50 mili metre diametre CPolyvenyle Chloride pipe with necessary fittings, remaking good the demolished portion etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing 15 centi metre rigid Polyvenyle Chloride Nahani trap including Polyvenyle Chloride grating ,bend,connectingpiece of Unplastisized Polyvenyle Chloride pipe up to the outside face of wall ,making the good damaged surface and testing etcetera complete ( Prior approval of sample and brand by Ex. Engr. is necessary before use)
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing Poly Venyle Chloride Rain water pipes of 110 mili metre outer diameter and having wall thickness of 2.2 to 2.7 mili metre confirming to Indian Standard 13592-1992 including proper rainwater receiving recess with Poly Venyle Chloride plug, bend, necessary fittings, such as, offsets, shoes, inluding fixing the pipe on wall using approved wooden cleats projecting 25 mili metre to 40 mili metre from face of wall a fixing with clips of approved quality and number ,filing the joint using rubber gasket with solvent cement and properly resting the shoe of pipes on Cement Concrete or masonry blocks, including necessary scaffolding and maintenance for 3 yrs for any leakages or dislocations of pipes. All the Poly Venyle Chloride fittings and additional 2 piece socket clips shall be got approved from engineer in charge etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and laying in trenches 15 mili metre diameter CPolyvenyle Chloride pipe including necessary excavation, fittings. Refilling trenches etcetera complete Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etcetera complete.
Providing and laying in trenches 20 mili metre diameter CPolyvenyle Chloride pipe including necessary excavation, fittings. Refilling trenches etcetera complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etcetera complete.
Providing and laying in trenches 25 mili metre diameter CPolyvenyle Chloride pipe including necessary excavation, fittings. Refilling trenches etcetera complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etcetera complete.
Providing and laying in trenches 32 mili metre diameter CPolyvenyle Chloride pipe including necessary excavation, fittings. Refilling trenches etcetera complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etcetera complete.
Providing and laying in trenches 40 mili metre diameter CPolyvenyle Chloride pipe including necessary excavation, fittings. Refilling trenches etcetera complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etcetera complete.
Providing and laying in trenches 50 mili metre diameter CPolyvenyle Chloride pipe including necessary excavation, fittings. Refilling trenches etcetera complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etcetera complete.
Providing and fixing in position Unplastisized Polyvenyle Chloride ultra violet stabilized 110 mili metre outer diameter cowl dome confirming to Indian Standard-4985 including making joints with solvent cement etcetera complete
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing Glass self 125 mili metre wide and 600 mili metre long with necessary chromium plated brackets providing Teak Wood gutties etcetera complete
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing & Supplying corrosion inhibiting admixture in concrete to protect steel bars for all concrete in every part Polyalk CP 293 of approved make & approved by Engineer in charge migrating, non-nitrite based corrosion inhibiting admixture shall be added at a dose of 3 Kilograms per Cubic Metre of concrete. The admixture should protect both cathodic and anodic sites and have been accredited by Indian Roads Congress, recommended for use by Ministry of Road Transport & Highways and should have a 4 year track record of use in both the Gulf Region and Indiametre Admixture should have evaluated test reports demonstrating a corrosion rate of zero coulombs after 9 test cycles as per ASTM G 109 when tested from a research institution NBA accredited Grade A and internationally ranked among top 5 research institutions in the world in Annual Survey conducted by Georgia Institute of Technology ranking of research institutions. PH of admixture should be alkaline in nature, specific gravity of 0.99 – 1.1, colour : brownish. The contractor must intimate the engineer in charge prior to addition in concrete for recording. If the admixture is put in the concrete mix at the batching plant, a written record of the amount of admixture used shall be supplied to the engineer. The engineer must ensure that the specified dosage of admixture is added in the concrete mix. (Material Cost Analysis only)
Providing and applying two coats of protective membrane over the cured concrete surface like Reinforced Cement Concrete footings, columns, plinth beams etcetera which will be submerged under soil so as to protect the same. Apply two pack coal tar epoxy system of Sunepoxy Coaltar of approved make & approved by Engineer in charge, having solid content ranges from 80-100%, Tack free time 4-6 hrs. Recoat after 16-24 hrs. Mix Part A and Part B of Sunepoxy Coaltar of approved make & approved by Engineer in charge in 1:1 ratio with slow speed stirrer and apply the same on a clean Reinforced Cement Concrete surface by brush. Allow to set for 8-10 hours and apply the second coat. The rate to include for application at all levels to various Reinforced Cement Concrete elements to the satisfaction of the EIC etcetera complete.
Providing and fixing in position alluminium strips of size 50 mili metre x 3 mili metre for nosing the steps including fixing with screws and raval plugs, bending and cutting to the required shape and size, finishing with paint, necessary mortar bedding of 1:3 cement mortar to get exact line and level including watering and curing etcetera complete
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
D] Third Floor
E] Fourth Floor
F] Fifth Floor
Providing and fixing lioghtening conductor system comprising of erecting Air-Termination consisting of tubular copper rod of 25 mili metre diametre 1.2 mili metre thick with multiple points head 1.2 Metric Tonne. long ( Heavy Duty) welded or clamped to Galvanised Iron pipe pole B grade 50 mili metre diametre of requiired length with Mild Steel round bnase plate 25 centi metre diam and 10 mili metre thick at bottom embeded in cement concrete 1:3:6 dfoundation of size 45 centi metre diam x 45 centi metre Height and providing earthing with copper earth plate of size 60 x 60 x 0.3 centi metre with cadmium plated nut bolts to fix earthing strip burried in specially prepared earth pits 1.5 metre below ground level with 40 Kilogram charcoal and salt with altemate layers of charcoal and salt and Galvanised Iron pipe 40 mili metre diametre 2 meter length burried in earthe upto earthling plate remining portion above ground level for watering and refilling comcpete Note- Copper strip fropm lightening conductor is not considered in this item.
Providing and fixing 90 centi metre x 60 centi metre Granite plate engraving 10 centi metre height letter, figures including painting the lefters/figures with approved colour and shade complete
Providing soak pit of size 120 centi metre x 120 centi metre x 120 centi metre including excavating and filling with brick-bats.
RWH - Shallow Percolation Pit providing, constructing 2.0m deep shallow depth percolation pit comprising of 1.0m dia pre-cast Reinforced Cement Concrete rings, 300 mili metre thick side filling around outside of Reinforced Cement Concrete rings (annular space) with 40 mili metre size boulders including filling of percolation pit up to 0.5m depth (from bottom up) with 25-75 mili metre clean washed gravels followed by 0.5m depth of 10-25 mili metre of clean washed stones followed by 0.5m of washed river fine aggregate (natural sand/crushed sand VSI grade finely washed etcetera) including netlon mesh between each gravel/fine aggregate (natural sand/crushed sand VSI grade finely washed etcetera) media layer including covering with Reinforced Cement Concrete slab, manhole frame & cover, Polyvenyle Chloride rungs etcetera including arrangement for inlet & outlet pipe, excavation & backfilling as shown in the drawing. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, taxes, including all leads, lifts at all levels. All material should be of approved make. All works complete as per the drawing, technical specification and direction of the Engineer in charge
Providing and installing bio digester unit based on DRDO technology made of fibre reinforced plastic (FRP) having composition and following technical specifications and including necessary pipe and accessories up to 3 meter length, excluding the necessary excavation for installing the bio digester. Percentage of fibre glass (glass content in fibre glass should be minimum 30%): -33.33% Percentage of polyester resin: - 66.67% Water absorption (as per ASTM):-0.30% Flammability as per ASTM Tensile strength:-115 MPA Specific Gravity at 25 degree centigrade 1.45 Izod impact strength:-65KJ/M2 Heat defection/distort temperature:-65deg C Corrosion resistance (Non Corrosive) fitted with Inlet pipe size rigid Polyvenyle Chloride: -100 mili metre Outlet pipe size rigid Polyvenyle Chloride:-80 mili metre Gas outlet rigid Polyvenyle Chloride with Valve: 20 mili metre Bacteria immobilization Polyvenyle Chloride mattes (on all partition) With DRDO TOT licensee and latest batch certificate(month & year of supply) and capacity as below c) Up to 25 user size (1.50 metrex1.0mx1.0m), Capacity of biodgester:-1500 liters, Area of top, bottom and side walls:- 8 Square Metre, Area of partition walls: 2 Square Metre, Total weight of frp: - 82.80 Kilogram, Bacteria inoculums quantity: - 600 liters, Minimum thickness of side walls / top and bottom: 5 mili metre, Number of inside partitions: - 3, Minimum thickness of partition wall: 3 mili metre
Providing and installing bio digester unit based on DRDO technology made of fibre reinforced plastic (FRP) having composition and following technical specifications and including necessary pipe and accessories up to 3 meter length, excluding the necessary excavation for installing the bio digester. Percentage of fibre glass (glass content in fibre glass should be minimum 30%): -33.33% Percentage of polyester resin: - 66.67% Water absorption (as per ASTM):-0.30% Flammability as per ASTM Tensile strength:-115 MPA Specific Gravity at 25 degree centigrade 1.45 Izod impact strength:-65KJ/M2 Heat defection/distort temperature:-65deg C Corrosion resistance (Non Corrosive) fitted with Inlet pipe size rigid Polyvenyle Chloride: -100 mili metre Outlet pipe size rigid Polyvenyle Chloride:-80 mili metre Gas outlet rigid Polyvenyle Chloride with Valve: 20 mili metre Bacteria immobilization Polyvenyle Chloride mattes (on all partition) With DRDO TOT licensee and latest batch certificate(month & year of supply) and capacity as below d) Up to 40 user size (2.0mx1.0mx1.0m), Capacity of biodgester:-2000 liters, Area of top, bottom and side walls: - 10 Square Metre, Area of partition walls: 3 Square Metre, Total weight of frp: - 106.20 Kilogram, Bacteria inoculums quantity: - 600 liters, Minimum thickness of side walls / top and bottom: 5 mili metre, Number of inside partitions: - 3, Minimum thickness of partition wall: 3 mili metre
Supply, fixing and installation of 4mm thick Aluminium Composite Panel (ACP) of approved colour for external cladding in combination of solid and metallic colours, including all necessary Framework, support and complete weather sealing as per architectural drawing. The Aluminium Composite Panel (ACP) should be made out of thermoplastic core of low-density polyethylene LDPE (100% virgin mix), sandwiched between two aluminium sheets of ALLOY GRADE- 5000 series, each not less than 0.50 mm thick, total thickness of aluminium composite panels not to be less than 4 mm, the exposed surface thereof shall have Stove lacquered finishing coat not less than (26 + - 2) micron (containing minimum 70% kynar 500 based PVDF) of colour and shade as per architectural design. The inside surface (facing the building exterior surface)shall have polyster based powder coating not less than 25 Micron with protective peel-off foil on the exterior face (peel off film will in no case leave any adhesive mark over the composite panel surface after it is peeled off). The supporting framework shall be made out of 50 mm X25mm X 3mm thick Aluminium section to be spaced horizontally and vertically for fixing of panel of size 900 mm X 1200 mm and fixed to the building structure as per design through 50mm X50mm X5 mm MS angle clamps prefixed to masonry or slab, columns with Hilti make anchor fastener screws. The fixing of panel to be done with the help of VHB tapes and screws and all the sealing of joints to be done with weather sealent Silicon as directed by Engineer-in-charge. (Prior permission of S.E. is necessary before inclusion of this item in estimate)
A] Ground Floor
B] First Floor
Providing and laying vitrified matt finish tiles having size 590 mili metre to 605 mili metre x to 605 mili metre of 8 to 10 mili metre thickness and confirming Indian Standard 15622-2006 (Group Bla) of approved make, shade and pattern for dado & skirting in required position laid on a bed of 1:4 cement mortar including neat cement float, filling joints, curing and cleaning etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Providing and laying ceramic tiles having size 30 centi metre x 60 centi metre confirming to corresponding Indian Standard for dado and skirting in required position with readymade adhesive mortar of approved quality on plaster of 1:2 cement mortar including joint filling with white/ colour cement slurry cleaning curing etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Providing and applying two coats Apex Ultima Puranature Anti-Pollution Or equivalent approved brand, paint should decomposes organic substances and inorganic gases(NOx, VOC’s, CO, SOx, formaldehydes, etcetera) in presence of natural or artificial light. It contains Graphene and nanoparticles of titanium oxide. and Absorbs CO2 (4.8 Kilogram/15 l). plaster crack should be filled by Acrylic base Crack seal/Textured Crack filler, Paint has to applied on one coat of Apex Ultima Puranature Anti-Pollution Primer or Equivalent. Warranty Should be given by the Manufaturer The work should be done by the Manufacturer Recommended applicator and he should be able to furnish stage wise onsite technical reports from the concerned company technologist.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Providing and fixing frame with / without ventilator of size as specified with Country cut teak wood for doors and windows including chamfering, rounding, rebating, iron holdfast of size 300 mili metre x 40 mili metre x 5 mili metre with oil painting, etcetera complete
A] Parking Floor/Ground Floor
Providing and fixing Country cut teak wood double or single leaf panelled shutters, 35 mili metre thick style top and freze rail 95 x 35 thick with lock and bottam rail 195 x 25 mili metre thick and panels without ventilator as per detailed drawing excluding the door frame, stainless steel fixtures and fastening and finishing the wood work with oil painting 3 coats complete
A] Parking Floor/Ground Floor
Sliding Window- 3 Track (2 Glass shutter + 1 flymesh) of approved make with DGU, providing and fixing of Sliding Window- 3 Track (2 Glass shutter + 1 flymesh ). For details refer to Specifications. As directed by Engineer in charge.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Providing and fixing aluminium grill diamond mesh type DG202 of 7.5 mili metre thick including fixing in position anodised aluminium frame section of 80 x 38 mili metre x 1.22 mili metre size box, cutting to the required size with all wastage, labour, lead lift etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Providing and fixing 15 mili metre diametre screw down bib/ stop tap of brass including necessary socket union nut complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Providing and fixing White glazed with bottle trap earthenware Wash Hand Basin of 63x45 centi metre size including cold water piller taps, brackets, rubber plugs and brass chain, stop tap, chromium plate bottle trap and necessary pipe connections including UPAC waste pipe and trap upto the outside face of the wall, making good the damaged surface, testing etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Providing and fixing Oval Type Under Counter Wash Hand Basin of 420 x 590 x 195 mili metre size with pillar cock, C.P.Angular stop cock, long thread of approved make continental including SS bottle trap of necessary pipe connection up to the outside face of the wall, having Telephonic Black / Colour Granite of 180 mili metre thick fixed on Black Kadappa Framework, etcetera Complete as directed by Engineer in charge.
B] First Floor
C] Second Floor
Providing, constructing and fixing 250 mili metre diametre Inspection chamber made up of Unplastisized Polyvenyle Chloride material of thickness 3.5 mili metre and height of 259 mili metre with inlet and outlet of 110 mili metre diametre with 75 mili metre diametre U Trap, Ultra shaft pipe of Unplastisized Polyvenyle Chloride material having height of 470 mili metre and fixing Ultra 250 mili metre diametre Unplastisized Polyvenyle Chloride cover and frame in 150 mili metre thick in Cement Concrete1:2:4, having crushed sand bed of 100 mili metre thick of size 550 mili metre diametre Including excavation and refilling the sides of chamber by crushed sand cushioning 150 mili metre thickness, connecting all required Unplastisized Polyvenyle Chloride fittings with rubber lubricant etcetera complete.
A] Parking Floor/Ground Floor
Providing and fixing white glazed earthenware lipped flat back/corner type Urinal with Polyvenyle Chloride 5 liters flushing cistern with fittings, inlet pipe with stop tap, brackets for fixing the cistern, 32 mili metre diametre Polyvenyle Chloride flush pipe with fitting including lead soil pipe, lead trap and soil pipe connection up to the outside face of wall.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Providing and fixing Poly Venyle Chloride Rain water pipes of 160 mili metre outer diameter and having wall thickness of 2.2 to 2.7 mili metreconfirming to Indian Standard 13592-1992 including proper rainwater receiving recess with Poly Venyle Chloride plug, bend, necessary fittings, such as, offsets, shoes, inluding fixing the pipe on wall using approved wooden cleats projecting 25 mili metre to 40 mili metre from face of wall a fixing with clips of approved quality and number ,filing the joint using rubber gasket with solvent cement and properly resting the shoe of pipes on Cement Concrete or masonry blocks, including necessary scaffolding and maintenance for 3 yrs for any leakages or dislocations of pipes. All the Poly Venyle Chloride fittings and additional 2 piece socket clips shall be got approved from engineer in charge etcetera complete.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Providing and fixing self supporting steel roofing system (Proflex) for a Godown or alike made up of structural grade steel sheet of 912 millimeter width ( tolerance + / - 2 millimeter ), moulded at site using mechanical press dies to the desired curve and shape to form 605 millimeter wide interlocking panels . The interlocking panels shall be pressed to close the seam forming water tight joints for a span of 32.5 meter having arch rise as 6.5 meter, arch length 37.7 meter. The base material made up of imported galvalume steel complying to ASTM A792 having base metal thickness of 1.60 millimeter ( tolerace + / - 0.02 millimeter ) with alloy coating AZ 150 and paint coating of regular modified polyster , top coat 25 micron and bottom coat 12 micron as perapproved colour , including fixing hangers , clamps etc.as may be necessary of Proflex standard, including fixing sky light of 2 millimeter thick polycarbonate sheet of size 2' x 14' and turbo ventilator of 24'' diameter to be installed at every 30 feet along the length of roof including finishing , testing and cleaning etc. complete.
C] Second Floor
Providing fly ash brick masonry with conventional/ Indian Standard type bricks in cement mortar 1:6 in superstructure including striking joints, raking out joints, watering and scaffolding etcetera Complete
Providing and fixing 50 mili metre diametre medium class Galvanised Ironpipe gate with wicket gate of approved drawing with all fixtures and fittings in two leaves with strong hold fast embedded in Cement Concrete block at top and bottom with locking arrangement including cutting, bending, making holes and with one coat of primer etcetera complete.
Providing and erecting 1.5 metre high wire fencing with seven rows of barbed wire supported on Mild SteelAngles ( 50 mili metre x 50 mili metre x 6 mili metre) at 2.5 Mild Steel, Center to center including excavating pits for foundqtion, fixing post in cement cocnrete 1:4:8 of size 45 x 45 x 45 centi metre fastening the wire and painting the Mild SteelAngles with one coat of red lead primer and two coats of painting etcetera complete.
Excavation for roadway in earth, soil of all sorts, sand, gravel or soft murum including dressing section to the required grade, camber and side slopes and conveying the excavated materials with all lifts upto a lead of 50 metre and spreading for embankment or stacking as directed.
Construction of granular sub-base by providing close graded Material, mixing in a mechanical mix plant at Optimum Moisture Content, carriage of mixed Material to work site, spreading in uniform layers with motor grader/ Paver on prepared surface and compacting with vibratory roller to achieve the desired density, complete as per clause 401 -- Plant Mix Method and Grading - I Material
Supplying hard murum/ kankar at the road site, including conveying and stacking complete.
Spreading hard murum/ soft murum/ gravel or kankar for side width complete
Compacting the hard murum side widths including laying in layers on each side with vibratory roller including artificial watering etcetera complete.
Construction of dry lean cement concrete Sub- base over a prepared sub-grade with coarse and fine aggregate (Natural Sand/ VSI grade finely washed crushed sand) conforming to IS: 383, the size of coarse aggregate not exceeding 25 mili metre,, cement content not to be less than 150 Kilogram/ Cubic Metre, Optimum Moisture Content (OMC)to be determined during trial length construction, concrete strength not to be less than 10 Mpa at 7 days, mixed in a batching plant/ Weigh batch mixer, transported to site with all leads and lifts, laid with a paver with electronic sensor /by suitable means as approved by Engineer-in-charge, compacting with vibratory roller, finishing, curing and including preparation of sub-grade surface if required etcetera complete.
Providing and laying in situ cement concrete M -30 with tremix treatment for specified thickness for Concrete Road is including laying plastic sheet for 125 micron thickness with groove cutting of 4 mili metre wide and 20 mili metre deep with necessary refilling with polysuphide sealant (Pouring grade) confirming to BS : 5212 - 1989 into sawed groove widened at top for sealant reservoir of specified size and shape as per detailed drawing including fixing Polyethylene foam backer rod of required diameter ( excluding reinforcement) with coarsen and fine aggregate Using V.S.I. Quality Artificial Sand etcetera complete
Providing and fixing in position Thermo Mechanical Treated (TMT) FE 500, tie bars precoated with anticorrosive epoxy paint of 12 mili metre diametre 70 centi metre long and at 30.00 centi metre centre to centre and wherever directed including handling, straightening wrapping with paper of approved quality for half length, necessary cutting, handling, straightening, supported by assembly of Thermo Mechanical Treated (TMT) FE 500, chairs with proper alignment etcetera complete.
Providing and fixing 20 to 25 mili metre thick rough shahabad box type waterproofing for basement or underground floor on a base of Cement concrete 1:3:6, including sub base of 2.50 centimeter thick Cement mortar 1:3 with conceal, secrete (RMW), Algae proof or other alike waterproofing liquids, raking of joints upto 35 mili metre depth, filling the joints with 6 mili metre size crushed metal, hand grouting with cement slurry, curing and cleaning, with 7 years guarantee on court fee stamp of Rs. 100/- with ponding test etcetera complete. (excluding Cement concrete 1:3:6 base concrete )
Providing and fixing 20 to 25 mili metre thick rough shahabad box type waterproofing treatment to vertical outside faces of Reinforced Cement concrete walls of basement or underground floor including filling the gap of 25 mili metre between rough shahabad and Reinforced Cement Concrete walls with cement grout mixed with water proofing liquid Algae proof or other alike with one tile lift method, brushing the joints horizontally with cement slurry mixed with water proofing liquid for width 30 to 35 mili metre and sloping coping over topmost tile with cement mortar 1:3, butting the bottom most with Cement concrete 1:2:4 mixed with water proofing liquid, curing, with 7 years guarantee on court fee stamp of Rs.100/- with ponding test etcetera complete. (excluding Cement concrete 1:3:6 base concrete)
Providing internal cement plaster 20 mili metre thick in single coats in cement mortar 1:5 without neeru finish, to concrete, brick surface, in all positions including scaffolding and curing etcetera complete
Providing neeru finish to plastered surfaces in all positions including scaffolding and curing etcetera complete.
Providing and laying vitrified mirror / glossy finish tiles decorative type having size 590 mili metre to 605 mili metre x 590 mili metre to 605 mili metre of 8 to 10 mili metre thickness and confirming to Indian Standard 15622-2006 ( group Bla) of approved make, shade and pattern for flooring in required position laid on a bed of 1:4 cement mortar including neat cement float, filling joints, curing and clearing etcetera complete.
Providing and applying three coats of water proof cement paint of approved manufacture and of approved colour to old plastered surfaces including scaffolding if necessary, cleaning and preparing the surface, watering for two days etcetera complete.
Providing and fixing rolling shutter fabricated from steel laths of minimum thickness 0.9 mili metre with lock plate of 3.15 mili metre thickness reinforced with 35 x 35 x 5 mili metre angle section fitted with sliding bolts and handles for both sides, deep Mild Steel channel section of depth and thickness not less than 65 mili metre and 3.15 mili metre respectively with hold fast arrangements, Mild Steel Bracket plate 300 x 300 x 3.15 mili metre minimum size and shape with square bar, suspension shaft of minimum 32 mili metre diametre, hood cover of Mild Steel sheet not less than 0.9 mili metre thickness and of any size at top and safety devices including mechanical gear operation arrangement consisting of worm gear wheels and worms of high grade cast iron or mild steel and one coat of red lead primer etcetera complete. (Indian Standard 62481979) (With mechanical gear)
Boring work (including transport.) 200/215 mm diameter in the soil / gravel surface Bore diameter of 150 mm in solid rock. This includes diameter drilling work. (Wet drilling) MJP Bore Well
After completion of drilling bore well, capacity test by flushing (air lift method) is measured with 90 degree "V" notch. MJP Bore Well
180 mm diameter PVC Casing pipe (8 kg / cm2) (IS 4985-1988) In exceptional circumstances / Casing pipes with a rock surface and if more than 40 feet of casing pipe is required, the casing should be used with the technical approval of the Deputy Engineer and Geologist
180 mm diameter PVC Casing pipe (8 kg / cm2) (IS 4985-1988) Casing lowering, grounding
180 mm diameter cap for PVC pipe.
Providing and Fixing Rollar Blinds AMI Make or approved make & shade of 38mm round Aluminium channel with Blackout fabric & telting with chain (Ball) system with all necessary fixtures and fitting etcetera complete. (Sample to be final by Engineer In-charge prior execution of work)
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Full Height Steel Storage @ 750Lx450Dx2100HT Providing and fixing Openable Steel Storage of 750 x 450 x 2100Ht, with 4 adjustable shelves, Complete body & shutter made in 0.8 mili metre thick & Top in 2 mili metre thick CRCA, 4 Shutter to be mounted with the help of cup hinges, and 4 adjustable levelers, enitre storage in powder coated finish with 60 to 80 microns as as per drawing.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Low Height Openable Storage @ 900Lx450x750HT Providing and fixing Openable Steel Storage of 900 x 450 x 750Ht, with 2 adjustable shelves, Complete body & shutter made in 0.8 mili metre thick & Top in 2 mili metre thick CRCA, 2 Shutter to be mounted with the help of cup hinges, and 4 adjustable levelers, enitre storage in powder coated finish with 60 to 80 microns. with 25 mili metre thk additional Top on top of storage as as per drawing
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Book Case with Glass Shutter @ 825Lx300Dx1650HT Providing & Fixing of Book Case with Glass Shutter @ 825Lx300Dx1650HT:- To be made out of complete body & in 0.7mm thick CRCA & Shutter in 1.2 mili metre thick CRCA with glass pannel in Powder coating finish as per drawing.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Providing & Arrangemnt of High Back, Synchronized Mechanism with Multiple Locking, Adjustable Armrest, Gaslift for Seat height adjustment, Standard 5-prong P/Nylon Base with Leatherite Upholstery
B] First Floor
C] Second Floor
Providing & Arrangemnt of MId Back, Normal Syncro Mechanism, Fixed Armrest, Gaslift for Seat height adjustment, Standard 5-prong/Nylon Base with Leather Upholstery
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Providing & Arrangemnt of Mid Back, ECO CTS Mechanism, Fixed Armrest, Gaslift for Seat height adjustment, Standard 5-prong P/Nylon Base with Fabric Upholstery
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Public Seating Chair. - 3 Seater Providing and Fixing 3 seater Public seating chair made of complete metal with Legs in Crome finish and seates in silver powder coating finish.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Free Standing Table @ 1200Lx600Dx750HT Providing and fixing Table of Size 1200 x 600 x 750 mili metre Top: made from 25 mili metrePrelaminated Particle board. All edges are covered by 2 mm. Thk. Polyvenyle Chloride edge bands glued by hot melt glue applied by auto edge banding machine. Legs : C Shape made from CRCA Sheet with Powder Coat finish. Modesty panel : Made from 18mm both side prelaminated particle boards.All edges are covered by 0.8mm Polyvenyle Chloride edge bands glued by hot melt glue applied by auto edge banding machine.KEYBOARD TRAY ( WITHOUT MOUSE TRAY ) :- Metal Powder Coated - Black Color, CPU TROLLEY :- Metal Powder Coated - Black Color, 3 DRAWER PEDESTAL UNIT having overall size 392L x 450D x 680Ht. mm. with central lock and key. Drawers and body are complete metal with powder coat finish, facia in 18 mili metreprelaminated particle board,
B] First Floor
C] Second Floor
Free Standing Table @ 1500Lx600Dx750HT Providing and fixing Table of Size 1500 x 600 x 750 mili metre Top: made from 25 mili metrePrelaminated Particle board. All edges are covered by 2 mm. Thk. Polyvenyle Chloride edge bands glued by hot melt glue applied by auto edge banding machine. Legs : C Shape made from CRCA Sheet with Powder Coat finish. Modesty panel : Made from 18mm both side prelaminated particle boards.All edges are covered by 0.8mm Polyvenyle Chloride edge bands glued by hot melt glue applied by auto edge banding machine.KEYBOARD TRAY ( WITHOUT MOUSE TRAY ) :- Metal Powder Coated - Black Color, CPU TROLLEY :- Metal Powder Coated - Black Color, 3 DRAWER PEDESTAL UNIT having overall size 392L x 450D x 680Ht. mm. with central lock and key. Drawers and body are complete metal with powder coat finish, facia in 18 mili metreprelaminated particle board,
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
12 Seater Reading Table for Library @ 3600Lx1200Dx750HT Providing and Fixing 12 Seater Reading Table for Liberary @ 3600Lx1200Dx750HT Top: made from 25 mili metrePrelaminated Particle board. All edges are covered by 2 mm. Thk. Polyvenyle Chloride edge bands glued by hot melt glue applied by auto edge banding machine. Gable Ends : made from 25 mili metrePrelaminated Particle board. All edges are covered by 2 mm. Thk. Polyvenyle Chloride edge bands glued by hot melt glue applied by auto edge banding machine. Modesty panel : Made from 18mm both side prelaminated particle boards.All edges are covered by 0.8mm Polyvenyle Chloride edge bands glued by hot melt glue applied by auto edge banding machine.
B] First Floor
C] Second Floor
Executive Table @ 2250Lx2100Dx750HT including Low Height Credestal @ 1200Lx450Dx650HT Providing & Fixing of Table @ 2250Lx2100Dx750HT TOP & GABLE END to be made of Membrane finish with soft water fall edges & curved panel & Decorated Anodized section MODESTY PANEL to be made of 18 mili metre thick Prelaminated particle board with Polyvenyle Chloride edge band. INCLUDING CREDESTAL @ 1200L X 450D X 650H :- To be made out of Membrane Finish ( 2 Openable Shutter & 3 Drawer Pedestal in between ) as per drawing.
B] First Floor
C] Second Floor
Medium Height Partition @ 1800/1200HT TILE BASED PARTITION SYSTEM:- Tile based Aluminum partition system of 1800/1200 mili metreht. made of 60 mili metre thk aluminum frames having two separate race ways for laying electrical & computer wiring. The wire management shall be through to the race way to be fitted at bottom of partition and other immediately below of work top with hook on type raceway cover for easy access of wires. Frames to be joined by aluminum connectors with M6 x 16 pan-head machin screw and washer with aluminum post cover. Post cover of snap on fashion to be connected on aluminum connectors. All visible aluminium to be in anodized finish. The top/ exposed sides of the frame and posts should be covered with horizontal/ Vertical trim and caps made of Aluminum in anodized finish in order to enhance its look.Upper tiles of partition to be in Soft Board or Marker tile of 9 mili metre thk., and prelaminated partical board lower tiles in laminate finish of 9 mili metre thk. on both the sides.
B] First Floor
C] Second Floor
Double Faced Mobile Unit for Compactor 2150 mili metreH x 2745 mili metreW x 900 mli metreD Providing and fixing Double Faced Mobile Unit for Compactor 2150 mili metreH x 2745 mili metreW x 900 mli metreD - BASE FRAME : Base Frame shall be fabricated in channel Type from minimum 2.5 mili metre thick MS Sheet Size of Channel 25 mili metre x 100 mili metre x 45 mili metre GUIDE RAILS : The guide rails shall be made out of 28mm Bright bar placed on 1.2 mili metre thick Mild Steel Plate which will be above the floor and are as per the international standard of safety. SUPER STRUCTURE : Super structure of the Mobile storage system will consist of knock down type panels. All the components such as shelves, front panel, end panel, vertical rear panel, central partition etcetera Will act as an integral member of the Unit. SHELVES : Shelves made of 22SWG thick Prime Quality C.R.C.A. having 10 folds each will be provided each designed to carry a U.D.L. of 70 Kilograms. VERTICAL PANEL : Vertical panel consists of the front, Centre & rear panel shall be made out of 20SWG thick C.R.C.A. Prime quality Mild Steel & designed to take the load of shelves. DRIVE COVER PANEL : Made out of 22SWG thick C. R.C. A. prime quality Steel to cover the entire drive mechanism. CENTRE PARTITION : The Centre partition will comprise of a full C.R.C.A. prime quality Mild Steel 22SWG Sheet. LOCKING : System will be provided with individual rack locking as well as centralised locking arrangement on the last unit when all units are brought together, central lock when operated gets locked with the floor & does not allow access to the units. DRIVE MECHANISM : Driving Mechanism will be provided externally supported on special grade anti-friction bearing to have smooth & effortless movement. Entire mechanism or gear & sprockets shall be incorporated within the front panel provided in the front of the unit within an area of 1000 mli metre x 200 mili metre x 60 mili metre DRIVING WHEEL : Fully Powder Coated three pronged drive wheel for better torque & free movement of the rack over the guide rail. INDEXING ARRANGEMENT : Acrylic card holders provided on the front panel for easy identification & retrieval. FINAL FINISH : Powder Coating (8 tanks process with 70 microns).
A] Parking Floor/Ground Floor
Stool for Lab and Class-IV Providing and fixing 4 legged Lab stool, Legs made of 16 Guage 45 mili metre outer dimension MS Pipe, Duly painted, With a 304 Grade Stainless steel 12 inch wide seat with a 1 inch collar, Height adjustment via a screw. as per design and drawing and instructions of Engineer in charge.
A] Parking Floor/Ground Floor
B] First Floor
C] Second Floor
Pedestal Unit @ 420Lx450Dx650HT Providing & Fixing of PEDESTAL @ 420Lx450Dx650HT :- To be made out of Complete Membrane consist of three Drawers as per drawing.
B] First Floor
C] Second Floor
Providing and laying in situ /Ready Mix cement concrete M-20 of trap / granite /quartzite/ gneiss metal for Reinforced Cement Concrete work in foundations like raft, strip foundations, grillage and footings of Reinforced Cement Concrete columns and steel stanchions etcetera including bailing out water, Steel centering formwork, laying/ pumping cover blocks, compaction and curing roughening the surface if special finish is to be provided (Excluding reinforcement and structural steel) etcetera complete, with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying Cast in situ/Ready Mix cement concrete M-20 of trap / granite /quartzite/ gneiss metal for Reinforced Cement Concrete columns as per detailed designs and drawing or as directed including steel centering, formwork, cover blocks, laying/ pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etcetera complete,(Excluding reinforcement and structural steel) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying Cast in situ/Ready Mix cement concrete M-20 of trap / granite /quartzite/ gneiss metal for Reinforced Cement Concrete beams and lintels as per detailed designs and drawings or as directed including steel centering, formwork, cover blocks, laying/ pumping, compactionand roughening the surface if special finish is to be provided and curing etcetera complete. (Excluding reinforcement and structural steel) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying Cast in situ/Ready Mix cement concrete M-20 of trap/ granite / quartzite/ gneiss metal for Reinforced Cement Concrete slabs and landings as per detailed designs and drawings including steel centering, formwork, cover blocks, laying/ pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etcetera complete,(Excluding reinforcement and structural steel) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying Cast in situ/Ready Mix cement concrete in M-20 of trap/ granite/ quartzite/ gneiss metal for Reinforced Cement Concrete pardi of required thickness including steel centering, formwork, cover blocks, laying/ pumping, compacting, curing, finishing and rougheningthem if special finish is to be provided and curing complete.(Excluding reinforcement and structural steel) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
Providing second class Burnt Brick masonry with conventional/ Indian Standard type bricks in cement mortar 1:6 in superstructure including striking joints, raking out joints, watering and scaffolding etcetera Complete
Providing and fixing mild steel grill work for windows, ventilators, etcetera 15 Kilogram/Square Metre as per drawing including fixtures necessary welding and painting with one coat of anticorrosive paint and two coats of oil painting complete.
Providing dry/ trap/ granite/ quartzite/ gneiss rubble stone soling 15 centi metre to 20 centi metre thick including hand packing and compacting etcetera complete.
Providing and laying Cast in situ/Ready Mix cement concrete M-20 of trap/ granite/ quartzite/ gneiss metal for Reinforced Cement Concrete chajja as per detailed design and drawings including steel centering, formwork, cover blocks, laying/ pumping, compacting and roughening the surface if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
Providing second class Burnt Brick masonry with conventional/ Indian Standard type bricks in cement mortar 1:6 in foundations and plinth of inner walls/ in plinth external walls including bailing out water manually, striking joints on unexposed faces, raking out joints on exposed faces and watering etcetera Complete.
Providing and laying vitrified mirror / glossy finish tiles having size 590 mili metre to 605 mili metre x 590 mili metre to 605 mili metre of 8 to 10 mili metre thickness and confirming to Indian Standard 15622-2006 ( group Bla) of approved make, shade and pattern for dado & skirting in required position laid on a bed of 1:4 cement mortar including neat cement float, filling joints, curing and clearing etcetera complete.
Providing and laying ceramic tiles of having size 30 centi metre x 30 centi metre and confirming to corresponding Indian Standard for dado and skirting in required position with readymade adhesive mortar of approved quality on plaster of 1:2 cement mortar including joint filling with white/ colour cement slurry cleaning curing etcetera complete.
Providing and applying plastic emulsion paint of approved quality, colour and shade to old surface in three coats including scaffolding, preparing the surface. (excluding primer coat) etcetera complete.
Providing and applying antipeel paint of approved make & approved brand exterior Emulsion paint of approved quality, colour and shade to old and new surface in two coats, including exterior acrylic primer coat, scaffolding, preparing the surface etcetera complete (Heat Reflective Paint).
Providing and fixing solid core flush door shutter in single leaf 32 mili metre thick decorative type of exterior grade as per detailed drawings approved face veneers 3 mili metre thick on both faces or as directed, all necessary beads, mouldings and lipping, wrought iron hold fasts, chromium plated fixtures and fastenings, with brass mortise lock, chromium plated handles on both sides, and finishing with French Polish etcetera complete.
Providing and fixing fiber glass reinforced polyster door shutter 30 mili metre thick as per Indian Standard 14856 (2000) (Reaffirmed 2006) without ventilator including chromium plated fixtures and fastening with chromium plated handles on both sides, etcetera complete
Providing and fixing screw down for 25 mili metre diametre wheeled stop tap of brass including necessary sockets/union nut complete.
Providing and fixing Orissa type white glazed earthenware 575 mili metrewater closet pan including S trap with earthenware foot rests, cast iron soil and vent pipe upto outside face of the wall 1:2:4 brick bat lime concrete bedding without flushing tank and its accessories etcetera complete.
Providing and fixing white glazed earthenware Wash Hand Basin of 55 centi metre x 40 centi metre size including cold water pillar tap/cold and hot water pillar tap brackets, rubber plugs and brass chain, stop tap and necessary pipe connections including Polyvenyle Chloride waste pipe and trap up to the outside face of the wall. Making good the damaged surface, testing etcetera complete.
Providing and constructing Brick Masonry Inspection Chamber 60 centi metre x 45 centi metre x 90 centi metre including 1:4:8 cement concrete foundation 1:2:4 cement concrete channels half round G.S.W. pipes, Brick Masonry, plastering from inside and with frame fixed in cement concrete with Reinforced Cement Concrete Cover medium duty 140 Kilogram with frame etcetera complete.
Providing and constructing Brick Masonry Inspection Chamber 90 centi metre x 45 centi metre x 90 centi metre including 1:4:8 cement concrete foundation 1:2:4 cement concrete channels half round G.S.W.pipes, Brick Masonry, plastering from inside and with frame fixed in cement concrete with Reinforced Cement Concrete Cover medium duty 140 Kilogram with frame etcetera complete.
Providing and fixing 10 centi metre Polyvenyle Chloride nahani trap with grating etcetera complete.
RWH - Recharge Pit Providing and constructing recharge pit of 2.0m deep and 1.0m dia of pre-cast Reinforced Cement Concrete rings with 6.5" dia x 25m deep borewell at the floor of recharge pit including installation of combination of solid/perforated Polyvenyle Chloride casing pipe wrapped around with netlon mesh including 300 mili metre thick sidefilling around outside of Reinforced Cement Concrete rings (annular space) with 40 mili metre size boulders including filling of recharge pit up to 0.5m depth with 25-75 mili metre clean washed gravels from bottom up followed by 0.5m depth of 10-25 mili metre of clean washed stones followed by 0.5m of washed river fine aggregate (natural sand/crushed sand VSI grade finely washed etcetera) including netlon mesh between each gravel/fine aggregate (natural sand/crushed sand VSI grade finely washed etcetera) media layer including covering with Reinforced Cement Concrete slab, manhole frame & cover, Polyvenyle Chloride rungs, Polyvenyle Chloride end-caps, fittings etcetera including arrangement for inlet & outlet pipe excavation & backfilling as shown in the drawing.The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, taxes, including all leads, lifts at all levels. All material should be of approved make. All works complete as per the drawing, technical specification and direction of the Engineer in charge.
Transportation of excavated material with lead & lifts away from site 5.00 km. etcetera complete as directed by Engineer in Charge.
Providing and laying Cast in situ/Ready Mix cement concrete in M-20 of trap/ granite/ quartzite/ gneiss metal for Reinforced Cement Concrete coping to plinth or parapet and sill of doors and windows moulded as per detailed drawings or chamfered as approved by the Engineer including steel centering, formwork, cover blocks, laying/ pumping, compacting, curing, finishing and roughening them if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etcetera complete. With fine aggregate (Crushed sand VSI Grade)
Providing and fixing bituminous pad 25 mili metre thick for expansion joints in retaining wall, compound wall etcetera complete.
Providing, laying, spreading and compacting stone aggregates of specific sizes to water bound macadam specification including spreading in uniform thickness, hand packing to proper grade and camber, applying and brooming requisite type of screening/ binding Materials to fill up the interstices of coarse aggregate, watering and compacting with Vibratory roller. to the required density. By Mechanical Means - Grading I (Using Screening Type A (13.2) mili metre Aggregate)
Providing and laying in situ cement concrete M -30 with tremix treatment for 200 mili metre thickness for Concrete Road is including laying plastic sheet for 125 micron thickness with groove cutting of 4 mili metre wide and 20 mili metre deep with necessary refilling with bitumen ( excluding reinforcement) with coarse and fine aggregate (Natural sand/ VSI grade finely washed crushed sand) etcetera complete
Providing uncoursed rubble masonry of trap / granite / quartzite / gneiss stones in cement mortar 1:6 in foundation and plinth of inner walls / in plinth of external walls including bailing out water manually, striking joints on un exposed faces and watering etcetera complete.
GARDEN SOIL :- Supplying on site garden soil well sieved 90% to pass through I.S. sieve of 10mm sixe free from stones rubbish like dried grass roots and other such materials. The soil should be fresh from quarry. The colour of the soil generally be red. The soil will be measured by measureing box. ( Farma ) ( Item includes Royalty charges., Transporting, loading unloading etc. ) lead charges for 20 Km. is considered.
FARM YARD MANURE :- Supplying on site well decayed, well dried, well powered, without clods and free from stones, dried grass and other rubbish materials. The colour of the soil generally be black. The manure will be measured by measureing box. ( Farma ) ( Item includes Transporting, loading unloading etc. ) lead charges for 20 Km. is considered.
Preparing Instant Lawn :- Excavating the ground to a required depth of 20cms. Removing & conveying unwanted stuff to a required distance as directed. Filling fresh garden soil / silt & manure in 3:1 proportion to a height of 20cms. Mixing soil and Manure thoroughly well, leveling with required slope, light watering on previous night, rolling on surface, fixing readymade lawn turf, rolls or slabs of required variety as directed. Ramming on it for proper fixing & maintaining till well established by watering, wedding, clipping or mowing etc complete.
Rose Plant :- Excavating pit with size 0.30 x 0.30 x 0.30 m Removing and conveying unwanted stuff to a required distance as directed. Filling the pit with fresh garden soil and manure in 3:1 proportion to a height of 30cms. Mixing garden soil and manure, throughtly well, levelling, watering on previous night, planting 40 to 50 cms. height healthy plants of required Rose variety maintaining till well established by watering weeding, stirring, prunning, replacing the casualties etc complete.
Planting Large Flowering / Shady Trees :- ( Minimum Height to 1 Mtr. ) Digging pit with size 0.9m x 0.9m x 0.9m Removing & conveying unwanted stuff to a required distance as directed. Filling the pit with approved excavated material up to a height of 0.30m and remaining height of 0.60m with fresh garden soil & manure in 3:1 proportion. Mixing soil and manure thoroughly well, levelling as directed, watering previous night. Planting one or two years old, minimum 1.0 mtr. height, healthy tree sapling as per specifications. Maintaining till well established by watering, weedings, stirring of soil, staking replacing, casualaties etc complete.
Planting small and medium size ornamental / flowering plant :- Digging pit with size 0.6m x 0.6m x 0.6m Removing & conveying unwanted stuff to a required distance as directed. Filling the pit with fresh garden soil & Farm Uard Manure up to a height of 0.60m in in 3:1 proportion. Mixing soil and manure thoroughly well, levelling as directed, watering previous night. Planting one or two years old healthy plants sapling as per specifications. Maintaining till well established by watering, stirring of soil and manure, replacing of casualties etc complete.
Preparing Flower Bed :- Excavating the ground to a required depth of 30 cms. Removing & conveying unwanted stuff to a required distance as directed. Filling fresh garden soil & manure in excavated area in 3:1 proportion to a required height of 30 cms. Mixing garden soil and manure thoroughly, well leveling, watering on previous night, Planting seedlings of required annuals 25 cms. aprt Maintaining till well established by watering, weedings, stirring replacing of casualties etc complete.
Excavation for catch / side water gutter in all sorts of soils to the specified section including stacking the excavated stuff in a regular bund and disposing of unsuitable or excess stuff as directed all sorts of soils.
Providing cast in situ / ready mix M-20 grade cement concrete for head walls of Cross Drainage Work / retaining walls etcetera including necessary form work, compaction, finishing and curing etcetera complete. (with reversible drum type mixer/ concrete batch mix plant (pan mixer) with SCADA
Providing and laying in situ / ready mix M-20 cement concrete of trap /granite /quartzite /gneiss metal for approach slab / Rigid pavement including compacting, finishing, curing etcetera complete. (excluding reinforcement) (with reversible drum type mixer/ concrete batch mix plant (pan mixer) with SCADA with fine aggregates of required specifications ( Natural sand / VSI sand finely washed etcetera ), cement 6.40 bags/Cubic Metre)
Providing and laying cement concrete pipe of IS 458:2003 NP-2 class of 450 mili metre diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etcetera complete.
Providing and fixing reinforced cement concrete cover of size 90 centi metre x 45 centi metre with frame over inspection chamber etcetera complete. Heavy duty (225 Kilogram)
Providing and fixing heavy duty inter locking concrete Rubber mould glossy paving blocks of 80 mili metre thickness of having a strength of 400 Kilogram/Square Centi Metre of approved quality and shape on a bed of crushed sand of 25 to 30 mili metre thick including skirting joints and cleaning etcetera complete. (using 100% crushed sand)
Drilling surface bore well 150 mm dia in all types starta including tranportation etc complete.
Providing and fixing U.P.V.C casing pipe 180mm dia( 6 kg / cm2 ) for 150 mm dia bore well etc complete.
Yeild testing by V noteches etc complete. Spec. No. As directed by Engineer in Charge.
Providing and fixing PVC Cap for 180mm casing pipe etc complete.
Providing and supplying in standard lengths Polythelene Pipes including all local & central taxes, octri, inspection charges, transportation to stores etc complete. ( 6 Kg/Sqcm. - 63mm dia. )
Lowering, laying, jointing in standard lengths Polythelene pipes ( 6 Kg/Sqcm - 63mm Dia. ) including all labour cost, transportation etc complete.
Supplying and erecting submersible pumpset of 5.625 KW/7.5 HP with 415 V, 50 c/s AC supply suitable for 150 mm dia. borewell suitable for 250 to 700 LPM discharge at 44 to 20m head & (max.efficiency at 32 m head & 500 lpm) discharge & delivery pipe ofSize-65 mm diameter with a necessary H type clamps as per specification no. WP-SMP
Supplying and erecting flat flexible 3 core 4 sq mm PVC sheathed submersible type copper cable suitably clamped at fixed intervals with column pipe assembly complete.
Providing internal cement plaster 20 mili metre thick in single coats in cement mortar 1:3 without neeru finish, to concrete, brick surface, in all positions including scaffolding and curing etcetera complete.
Providing earth work in embankment with approved materials obtained from departmental land upto lead of 50 metre including all lifts, laying in layers of 20 centi metre to 30 centi metre thickness breaking clods, dressing to the required lines, curves, grades & section, watering and compaction with vibratory roller to achieve not less than 97 % of standard proctor density etcetera complete. (Material obtained from departmental Land)
Supply and Installation of Dpi Flux translucent roof with standing seam multicell polycarbonate panel system. The system with complete assembly of co extruded UV protected multicell panels incorporated into a complete system. Co-extruded UV protected polycarbonate panel system of min 16 mm thick of 1200mm (min.) width with angular daylighting concept. Panels shall have minimum seven layers in a truss bridge design for higher flexibility & strength. Panels with opaque and translucent clear combination as per required lux level and design requirements with all fixing accessories to ensure best performance for wind uplift, vibration, oil canning and visual appearance. Panels shall have an additional IR Blocking features for enhance thermal comfort. Panels shall be manufactured with vertical standing seam at both sides of the panel. Panels shall be fixed on Purlin with snap on connectors with double tooth grip lock locking mechanism and will be secured on MS structure (will be paid Separately) with 3 numbers self-drilling screws & trapezoid SS fasteners holding the base of the standing seam offering best stability having a pull-out load of min. 7000N (7KN) tested as per ISO 6892:1998 and IS 1608: 2005, as per design requirement. Panels must satisfy Dart drop impact test as per IS 14443-97 shall show no sign of breakage on Polycarbonate sheets which have been exposed to UV for a min. of 500 Hours as per ASTM G 155. Panels shall not have Yellowness Index as per ASTM D 1925 of 15
Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC.
Supplying and laying HMS PVC conduit FRLS grade 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.
Supplying and erecting 25 mm dia. corrugated flexible polypropylene conduit
Supplying and erecting mains with 1x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting mains with 1x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 2x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 2x6 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 1x6 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 4x6 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type switch 16A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type bell-push 6A / 10A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type blanking plate one module, duly erected on provided plate & box.
Supplying and erecting modular type (two module) electronic step regulator for fan, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 1 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 2 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 6 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 12 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Point wiring for light/bell hybrid type (Surface type under false ceiling and concealed type for drops & switch boards on walls) in min 20 mm PVC conduit / casing n capping with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No: WG-PW/HW
Point wiring for ceiling fan (Surface type under false ceiling and concealed type for drops & switch boards on walls) in min 20 mm PVC conduit / casing n capping with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No: WG-PW/HW
Point wiring for light/bell/exhaust fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG-PW/SW
Point wiring for ceiling fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG-PW/SW
Wiring for plug on board with Switch socket surface/concealed type, copper wiring and earthing and with modular accessories as per specification No: WG-PW/CW
Supplying & erecting 2 pair telephone copper cable 0.5 mm dia. with high density polyethylene insulation, polyester taped, Nylon Rip Cord & grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113C laid in provided PVC casing capping/conduit as per specification No. WG-TW
Supplying & erecting 10 pair, 0.5 mm dia. jelly filled armoured telephone copper cable with poly-al laminate moisture barrier, polythene sheathed, G.S.Tape armoured polythene jacketed having laid in provided trench as per specification No. WG-TW
Supplying and erecting LED square / circular Max. 18 W down lighter/ Panel Light having pressure die-cast aluminium housing, polystyrene diffuser having system lumens output of Min. 2000 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty.
Supplying and erecting LED Panel Light(600mm X 600mm) Max. 35 W having CRCA powder coated housing, polystyrene diffuser having system lumens output of Min 4200 Lumens, min. efficacy of 120 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50 including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty.
Supplying and erecting bulk head LED fitting max. 10W with high transitivity diffuser with system lumens output of min. 1100 lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., THD<10%, p.f. >0.95, operating range of 140-260V, in built surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, IP66, IK09 rated on provided PVC Block / wooden board with 3 years warranty.
Supplying and erecting anodized aluminium corridor / passage light LED fitting (4 feet) Max. 22W with high transitivity diffuser with system lumens output of Min.2200 lumens , min. efficacy of 100 lumen/W, CRI>80, CCT upto 6000K, Beam Angle of 110 deg., Ripple<5%, THD<10%, p.f. >0.95, operating range of 200-270V, surge protection of 2 kV, Life class of 50,000 Hrs. at L70B50, including driver, with end caps on provided PVC Block / wooden board with 3 years warranty.
Supplying and erecting ding dong / electronic musical type call bell with heavy duty coil suitable to operate on 230V A.C. supply erected on polished double wooden block/sunmica block of suitable size.
Supplying and erecting exhaust fan medium duty 230 V A.C. 50 cycles 225 mm. 1400 RPM with condenser complete erected in position with necessary materials. Fan motor with moisture proof treatment and ‘E’ class insulation.
Supplying and erecting Energy Saving BLDC Ceiling fan 230 V A.C. 50 cycles 1200 mm, max. energy consumption of 28W having service ratio (CMM/W) of Min. 8 , PF>0.9, THD<10% without IR remote control/compatible speed regulator, Temperature Rise of Max. 40 deg. C, having external mounted control PCB completely erected in position as per specification no. FG-FN/CF
Supplying & fixing anchor type fastener fan hook, with 2 nos. of 10 mm dia x 75 mm long with necessary materials for ceiling fan.
Supplying, erecting, testing and commissioning self contained water cooler 230/250V 50Hz nominal cooling capacity of 150 litres per hour and storage capacity 150 litres with partially stainless steel body as per specification no. AP-WCR/WC
Supplying and erecting ultra violet storage type water purifier (RO+UV+UF) with softener for safe drinking water consisting of UV germicidal tube of 8W capacity choke made of copper wire and two indicator lamps with output of purified water minimum 0.33 litre/min with activated carbon filter and softener operating on 230V, single phase A.C. supply with UV fail & filter change indication system .(for TDS more than 200)
Supplying, erecting & marking SPMCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking SPMCB 6A to 32A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking DPMCB 40A to 63A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking TPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking FPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying & erecting triple pole and neutral distribution board (TPNDB), SPMCB of 4 ways/phase (12 poles), with door, 1.2mm thickness, surface/flush mounted, IP 43 protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB
Supplying and erecting single pole and neutral distribution board (SPNDB), with 2 ways for incoming and 10 ways (10 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB
Supplying & erecting triple pole and neutral distribution board (TPNDB), 3 pole/ 4 pole MCCB as incomer & outgoing SP MCB (12 poles) or TP MCB of 4 ways (12 poles), with door, 1.2mm thickness, surface/flush mounted, on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB1
Providing & erecting 4 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB
Providing & erecting 4 Pole MCCB 415V, 250A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB
Providing & erecting floor/wall mounting, MCCB panel board, with door, suitable for four pole incoming 250A, 8 ways Four pole outgoing, up to 100 A MCCBs on iron frame, as per specification no SW-SWR/MCCBPB. (Excluding MCCBs)
Providing & erecting incoming and outgoing cable alleys suitable for MCCB panel board with door, 250A incoming and 8 way outgoing or 400A incoming and 6 way outgoing made from CRCA sheet 1.6 mm thick duly powder coated and having vertical insulated partition for shielding between the shared face of cableway and DB.
Providing & erecting prewired meter module suitable for MCCB panel board with CTs and emfs VIF meter.
Supplying and erecting metal work in CRCA sheet including Iron work for supports with fabrication of boxes, panel boards, etc. including cutting, bending, drilling, welding, riveting, treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete.
Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 35 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 120 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 2 core 4 sq mm copper conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying & erecting G.I. pipe ‘A’ class 50 mm dia. erected for enclosing XLPE armoured cable on wall/pole as per specification no. CB-CE
Supplying and laying (including excavation of suitable width & depth up to 90 cm) 90 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete.
Providng earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP.
Supplying and erecting GI wire of high purity of required sizes used for earthing or any other purposes on wall with necessary G. I. Clamps fixed on wall/cable/ conduit with screws complete.
Supplying and erecting street light Wall bracket made from 40 mm. dia ‘ G.I. pipe 1.2 m. in total length complete as per specification no. FG-BKT/WB
Supplying and erecting integrated LED street light fitting 70-75W IP65 & IK08 class having single piece pressure die-cast aluminium housing, having system lumens output of Min. 7700 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K,THD<10%, p.f. >0.95, operating range of 140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs. at L70B50, including driver complete with 3 Years warranty as per specification No FG-ODF/FLS2.
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 120 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 185 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying and erecting rolled steel joist (girder) pole 125 x 70 mm (13.3 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ (9m X 5 + 8m X1 = 53m)
Supplying and erecting rolled steel joist (girder) pole 100 x 116 mm (23 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ (11m X7 + 10m X1 = 87m)
Supplying & erecting MS pole bracket for guarding/LT OH line, fabricated from angle iron 50x50x6mm and 1100mm long for necessary nos. of provided insulators, and erecting on pole with 50x6mm clamp complete as per specification no. OH-PL/BKT
Supplying and erecting V cross arm with ISM channel of 75x40x6mm for 11kV HT OH line with arrangement to fix insulator at 45mm from the end & horizontal distance between insulators 1220mm bent at angle of 60 degree keeping base 305mm and the total vertical height of V cross arm as 460mm, and fixed on pole with MS clamp of 80x10 mm, nut bolts, washers complete as per specification no. OH-PL/VCA
Supplying and erecting 75x40 x6mm with 4.4mm thick web and 7.3mm thick flange channel (top pin) with clamp of suitable length so as to maintain vertical clearance of 1065mm for 11kV, 1320mm for 22kV between insulators for erection of top pin insulators complete as per specification no. OH-PL/VCA
Supplying and erecting bracket for guarding of HT OH Line, made from channel iron 1600mm in length and 75x40x6mm. erected on pole complete as per specification no. OH-PL/VCA
Supplying & erecting single pole cut point channel set of for 11kV HT OH line two channel of size 100x50x6mm 1.6m long having stud angle of size 50x50x6mm 1.5m long with necessary clamps, nut bolts etc. complete as per drawing.
Supplying & erecting inline cut point end pole D. P. Structure for 11/0.415 kV, 100 kVA Transformer with R.S.J. Pole 2 Nos. of size 100 x 116 mm x 11 Mtr. Long with suitable Distribution Box of C.R.C.A. Sheet 16 SWG with 4 Pole MCCB 200 Amps as incomer & 6 Nos.100 Amps Kitkat /MCCB for out going circuits. Transformer D.P. Structure includes the A. B. Switch 200 Amps, D.O. fuse Set & L.A. Set. 2 Nos. Top channel of size 100 mmx 50 mm for erection of A.B. Switch & 2 Nos. Base channel of size 100 mm x 50 x mm for erecting Transformer Channel of size 75 x40 mm for erecting D.O. Fuse Set, L.A., A.B. Switch handle etc. Angle of size 50 x 50 x6 mm for erecting Distribution Box, Transformer Belt etc. as per drawing (min. 176 Kg. iron work) with necessary clamps, Nut-bolts. V cross arm, top clip, insulators etc. complete with caution board & barbed wire. D.P. Structure shall be erected in c.c. foundation complete.
Supplying and erecting pin type LT medium insulator 100mmx 62mm dia. with suitable G.l. spindle, nut, bolts complete.
Supplying and erecting aluminium bobbin with G.l. (shackle) strip, nuts complete.
Supplying and erecting G.I. stay set for poles, including loop insulators at inaccessible height with anchor plate 300x300x6mm., straining screws, G.l. stay wire 7/10 SWG, G.l. stay rod 20mmx1.8m length and pole clamps duly erected in provided cement concrete foundation complete.
Supplying and erecting G.I. stay set for poles, including loop insulators at inaccessible height with anchor plate 300x300x6 mm., straining screws, G.l. stay wire 7/8 SWG, G.l. stay rod 20mmx1.8m length and pole clamps duly erected in provided cement concrete foundation complete.
Supplying and erecting ‘D’ type pole clamps, fabricated from 50x6mm MS flat with 15mm bolts and nuts fixed to steel tubular pole duly painted with one coat of red oxide and two coats of aluminium paint complete.
Supplying and erecting guarding loop using G.l. wire no. 8SWG for LT OH line of horizontal formation erected with 20SWG G.l. wire as binding wire and 50mm section on each side complete.
Supplying and erecting fibre/PVC spacers for LT overhead line 3 to 5 conductors complete erected.
Supplying and erecting GI wire of high purity of required sizes used for earthing or any other purposes on wall with necessary G. I. Clamps fixed on wall/cable/ conduit with screws complete. ((5x30x2 = 300)+(6x50x2 = 600) = 900 @ 9.8 mtr/Kg = 91.83 Kg)
Supplying and erecting guarding lace for HT OH line with 8SWG G.l. wire to protect the HT OH line with binding wire of 20SWG G.l. wire for 75mm section on either side.
Supplying & erecting MS pole bracket for guarding/LT OH line, fabricated from angle iron 50x50x6mm and 550mm long for necessary nos. of provided insulators, and erecting on pole with 50x6mm clamp complete as per specification no. OH-PL/BKT
Supplying and erecting double leaf hinged door each 1500 mm in width x 1850 mm in height using B class, GI pipe with angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation, and painted complete as per specification no SS-AS/DLD
Supplying and erecting fencing of section having size 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete as per specification no SS-AS/FSG
Supplying and erecting 50 x 50 x 6 mm angle iron as corner support 2m long fixed at the middle of the fencing frame and the other side inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminium paint complete.
Providing pipe type earthing with 40mm. dia. G.I. pipe or 20 mm dia. G.I. Rod complete with all materials testing and recording the results as per specification no. EA-EP
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP.
Supplying & erecting barbed wire two ply with 12 SWG ply and 12 SWG barb with a gap between two bars of 75 mm. firmly fixed on provided angle supports with necessary materials complete. (6.044 meters/kg.).
Making cement concrete foundation including excavation (60 x 60) cm x deep 1/6 of pole length in 1:3:6 cement concrete 20 x 25 mm stone metal, 45 cm x 45 cm x 45 cm /45 cm dia. x 45 cm. height plinth duly plastered, with necessary curing and finishing complete. (for above 9 m poles)
Making cement concrete foundation including excavation (60 x 60 x 150) cm deep in 1:3:6 cement concrete, (20 to 25) mm stone metal with necessary curing and finishing complete.(for stay).
Supplying and erecting porcelain disc type insulator 45KN with necessary hardware suitable for 11kV line, complete as per specification no. OH-INS/DI
Supplying and erecting porcelain pin type insulator with GI pin suitable for 11kV line, complete as per specification no. OH-INS/PN
Providng earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP
Supplying and erecting GI sheet 1.6 mm (16 SWG) caution board of size 200 x 150 mm duly painted with red oxide and enamel paint in Marathi, Hindi and English erected at position for medium voltage (415 Volt) installation with compliance to IS 2551-1982
Supplying and erecting extra thick alkathene pipe 10 mm dia. erected to enclose bare conductor wires complete.. (use shall be restricted to H.T.)
Making cement concrete foundation in 1:3:6 cement concrete, (20 to 25) mm. stone metal duly plastered with necessary curing for complete. (pole muffing or any other purpose).
Supplying and spreading stone metal 25 mm size for 100 mm depth above the ground level complete.
Supplying, installing, testing & commissioning of 3 phase, 11/0.433 kV, 50 Hz., 100 kVA, Mineral oil immersed and naturally cooled outdoor type, aluminium wound Non-sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 40℃ by thermometer in oil and 45℃ by the resistance method in winding at full load rating, using type A winding insulation (kraft paper) , with standard accessories complete with test certificate with losses below 475 Watts at 50% load, 1650 Watts at 100% load as per IS:1180 (part 1) : 2014, with necessary permissions of Electrical Inspector, as per specification no SS- TR-NSL.
Supplying and erecting modular type telephone socket one gang with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying & erecting 2 pair telephone copper cable 0.5 mm dia. with high density polyethylene insulation, polyester taped, Nylon Rip Cord & grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113C laid in provided PVC casing capping/conduit as per specification No. WG-TW
Supplying & erecting 10 pair, 0.5 mm dia. jelly filled armoured telephone copper cable with poly-al laminate moisture barrier, polythene sheathed, G.S.Tape armoured polythene jacketed having laid in provided trench as per specification No. WG-TW
Supplying and erecting 10m HDMI cord low voltage grade minimum 4k compliant to be laid in provided conduits with male/female 19 pin HDMI connectors complete.
Supplying, erecting & commissioning MDF Box 50x50 pairs made from min. 1.5mm thick MS sheet as per specification no. WG-TW
Supplying, erecting & commissioning 10 pairs FR junction box with moulded plastic enclosure as per specification no. WG-TW
Supplying, erecting & commissioning 10 pair module for connection & disconnection of telephone cable as per specification no. WG-TW
Supplying and installing, testing & commissioning of digital (hybrid) type EPABX of 6 x 32 extensions suitable upto 96 extensions complete.
Supplying, installing, testing & commissioning push button telephone instrument desk top unit as per specification complete
Supplying, installing, testing & commissioning IP telephone instrument as per specification complete.
Supplying and installing cat-6 cable suitable for networking as per specification no. WG-COC/NC
Supplying and fixing 1 m UTP patch cord of Cat 6 type in position as per specification No. WG-COC/PC
Supplying, fixing, and configuring 24 ports, POE switch in provided rack as per specification No. WG-NWC/ENS
Supplying, fixing, and configuring 24 ports with 4 (SFP+) port, ethernet managed switch with web view/CLI, 6KV surge protection on ethernet port and console port for management in provided rack as per specification no. WG-NWC/GBS
Supplying and fixing tool-less IO (Ethernet) flush/surface type in provided modular box as per specification no. WG-NAS/IO
Supplying and fixing 24 port patch panel with tool-less keystone jacks in provided U Rack complete as per specification no. WG-NAS/PP
Supplying and fixing 6U wall mount rack (Dimension-DxWxH – 500x600x367 mm) as per specification No. WG-NAS/RAK
Supplying and fixing 9U wall mount rack (Dimension-DxWxH – 500x600x500 mm) as per specification No. WG-NAS/RAK
Supplying & erecting of High definition 4/5 Megapixel IP IR Dome Camera with following featuresImage Sensor : minimum 1/2.8" Progressive Scan CMOS, Video Resolution : minimum 2592 x 1520Video Compression : H.264, H.265 or higher, at least Three individually configurable stream, Frame rate : minimum 25 fps at all resolutions, WDR : minimum 120 dB Wide Dynamic Range, ONVIF profile conformant, minimum IR distance : 50m, Lens Type : 2.8/4/6 mm Lens, fixed focal, Field of View :2.8 mm, horizontal FOV 107°, vertical FOV 57°, diagonal FOV 129°4 mm, horizontal FOV 86°, vertical FOV 47°, diagonal FOV 102°6 mm, horizontal FOV 55°, vertical FOV 29°, diagonal FOV 65°Lux sensitivity - minimum 0.2 Lux at color, minimum 0.05 Lux at Black & White, 0.0 Lux (IR) Night Vision Distance minimum IR - 50m. Camera minimum Adjustment Angles - Pan : 350°, Tilt : 72°, Rotate : 350°. Power Supply : Support 12VDC & PoE, IP67, IK10 - Vandal Resistant. Built in micro SD/SDHC/SDXC card slot of minimum 128 GB, Built in microphone. minimum Input/Output - Audio in × 1, Audio Out × 1, Alarm in × 1, Alarm Out × 1. Image Settings : Rotate mode, saturation, brightness, contrast, sharpness, gain, white balance. Image Enhancements : Day/Night-Auto (ICR)/Color/Black & White, 3D Digital Noise Reduction, Automatic White Balance, Automatic Gain Control, Backlight Compensation, Highlight Compensation.
Supplying & erecting of High definition 4/5 Megapixel IP IR Bullet Camera with following featuresImage Sensor : minimum 1/2.8" Progressive Scan CMOS, Video Resolution : minimum 2592 x 1520Video Compression : H.264, H.265 or higher, at least Three individually configurable stream, Frame rate : minimum 25 fps at all resolutions, WDR : minimum 120 dB Wide Dynamic Range, ONVIF profile conformant, minimum IR distance : 50m, Lens Type : 2.8/4/6 mm Lens, fixed focal, Field of View :2.8 mm, horizontal FOV 107°, vertical FOV 57°, diagonal FOV 129°4 mm, horizontal FOV 86°, vertical FOV 47°, diagonal FOV 102°6 mm, horizontal FOV 55°, vertical FOV 29°, diagonal FOV 65°Lux sensitivity - minimum 0.2 Lux at color, minimum 0.05 Lux at Black & White, 0.0 Lux (IR) Night Vision Distance minimum IR - 50m. Camera minimum Adjustment Angles - Pan : 350°, Tilt : 72°, Rotate : 350°. Power Supply : Support 12VDC & PoE, IP67, IK10 - Vandal Resistant. Built in micro SD/SDHC/SDXC card slot of minimum 128 GB, Built in microphone. minimum Input/Output - Audio in × 1, Audio Out × 1, Alarm in × 1, Alarm Out × 1. Image Settings : Rotate mode, saturation, brightness, contrast, sharpness, gain, white balance. Image Enhancements : Day/Night-Auto (ICR)/Color/Black & White, 3D Digital Noise Reduction, Automatic White Balance, Automatic Gain Control, Backlight Compensation, Highlight Compensation.
Supplying, installing, testing & commissioning of 32/40 Ch. Network Video Recorder (NVR), suitable connect Min. 32 IP Cameras, up to 5 Megapixel Resolution, with HDMI/VGA outputs, provided HDMI output of 4K resolution or VGA output with output up to 1920 × 1080. Support H.265 or higher, H.264, MJPEG, Incoming Bandwidth 250Mbps with minimum 4 SATA Hard Disks, ANR Technology, 4 SATA interfaces for 4 HDDs and capacity of each HDD up to 8TB, minimum 02 USB port, Alarm I/O 16/4, RJ-45 10/100/ 1000 Mbps self-adaptive Ethernet interface, ONVIF conformance, Multiple network monitoring: Web viewer . support protocol TCP/IP, DHCP, DNS, DDNS, NTP, SADP, SMTP, NFS, iSCSI, UPnP™, HTTPS. RoHS, UL, CE, FCC certified.duly erected in provided U Rack with wiring connections, tagging and programming etc. complete as per specification no. CCTV-NVR
Supplying & erecting 8 TB internal Surveillance HDD suitable for SATA Port of NVR, interface transfer rate 6 GB/S, maximum sustained transfer rate 210 MB/Sec to 213 MB/S. Drive bay supported 08+, Cameras supported up to 64, Cache (MB) 256, Load/Unload Cycle -3000000, Work Load Rating per Year 180TB, MTBF 1000000 Hrs. HTTPS. RoHS, UL, CE certified, duly erected in position in provided NVR as per specification no. CCTV-HDD
Supplying & erecting 43" professional LED display with 1920*1080 (Full HD) Display, suitable for 16/32 channel NVR and following featuresBrightness: minimum 500 Cd/m2Contrast Ratio: minimum 1000:1Viewing angle: 178/178 deg.Response time: maximum 8 msInputs: HDMI, VGA, BNC,USB, Audio In, Built-in speakers maximum 10 W, Suitable to operate on 100-240 V 50 Hz AC supply and 24/7 Duty Cycle duly erected on wall or table top with standard accessories like wall mount stand and wiring connections etc. complete as per specifications no. CCTV-MON
Supplying and erecting minimum Three & above star rated submersible pump set suitable for erection on open well of 5.625 KW/7.5 HP with 415 V 50 c/s. A.C. supply, having delivery head from 36 to 14m and discharge from 225 to 1680 litres. per minute& pip
Supplying & erecting automatic control panel for 3 Phase , 415 volt, A.C, Submersible/centrifugal pump set up to 7.5 HP consisting of DOL starter having relay range 9-14 AMP,S.P.P., Combined ammeter/ voltmeter, phase indicating lamp enclosed in CRCA powde
Supplying and erecting ISI mark GI pipe 50 mm dia.‘B’ class at position with accessories complete as per specification no. CW-PLB/GP.
Supplying and erecting non return valve 50 mm dia in position made of gun metal complete.
Supplying & erecting flat flexible 3 core 4 sq.mm PVC sheathed submersible type copper cable suitably clamped at fixed intervals with column pipe assembly complete.
Supplying, erecting & marking TPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying & erecting four pole ON LOAD change over switch, 415V, 63A, open execution having staggered termination, phase barrier, shroud termination and terminal cover along with auxiliary contacts and ready to upgrade with fuse protection kit, rotary handle, operational current category AC23A complying to IS/IEC 60947-3 Part-1/3.
Supplying & erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBO complete erected on angle iron/GI frame.
Providng earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP
Supplying & erecting three phase, 415V, street light control panel up to the max load of 6kW, TPN MCB 40A, powder coated CRCA 14 SWG sheet, outdoor type, having IP54,IK10 protection, suitable rating contactor, 24 hrs. astronomical time switch with minimu
Supplying, erecting & marking SPMCB 0.5A to 5A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 6 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per s
Providing & erecting 6 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 130 mm A/F, top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL
Providing and erecting galvanised 1000mm single arm sword type bracket with FRP dome and ball as per specification no. OH-PL/PBKT
Providing and erecting galvanised 1000mm double arm sword type bracket with FRP dome and ball as per specification no. OH-PL/PBKT
Providng earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP
Providing pipe type earthing with 40mm. dia. G.I. pipe or 20 mm dia. G.I. Rod complete with all materials testing and recording the results as per specification no. EA-EP
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP.
Supplying and erecting GI wire of high purity of required sizes used for earthing or any other purposes on wall with necessary G. I. Clamps fixed on wall/cable/ conduit with screws complete.
Making M- 20 grade reinforced cement concrete foundation by considering the safe soil bearing capacity at site as 10 T/sq.m at 1.5 m depth including supply of steel, concrete, excavation and fixing provided nut bolts with the help of template, duly pla
Supplying and erecting hylam sheet/ ebonite 6 mm thick for covering wall entries including cutting, drilling and fixing with nut bolts / screws etc. complete.
Supplying & erecting 415V, 16A porcelain base neutral link complete erected in provided M.S. box.
Supplying & erecting integral post top lantern fixtures (light house type) suitable upto LED 18 W Lamp consisting of combination of spun aluminium canopy & clear acrylic top cover, cast aluminium pole cap on provided pole/ bracket as per specification no. FG-ODF/PTL
Supplying & erecting 18W, 230V integral type LED Lamp suitable for B-22 / E-27 base.
Supplying & erecting FRP box of size 250mm x 200mm x 100 mm, 2.7 mm thick complete on pole/wall as per specification No. CB-SB
Supplying & erecting G.I. pipe ‘A’ class 50 mm dia. erected for enclosing XLPE armoured cable on wall/pole as per specification no. CB-CE
Supplying and erecting PVC insulated PVC round sheathed 1.5 sq.mm (30 no. x 0.25 mm dia.) 3 core flexible multi stranded copper Industrial cable for voltage grade up to 1.1 kV
Supplying and erecting integrated LED street light fitting 70-75W IP65 & IK08 class having single piece pressure die-cast aluminium housing, having system lumens output of Min. 7700 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K,THD<10%, p
Supplying, erecting & marking DPMCB 40A to 63A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking FPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying & erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBO complete erected on angle iron/GI frame.
Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.
Supplying, erecting & commissioning 2 pole RCCB 40A, electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB
Supplying, erecting & commissioning 4 pole RCCB 63A, electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 2 core 4 sq mm copper conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per speci
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per s
SITC of Electric Traction Passenger Lift with · Rated capacity :- 8 Passenger/544Kg · Floors :- G+3 floor (4 Stops/4 Landings) · Travel :- 3 to 4.2 mtrs · Location of Lift Machine:- MR/MRL · Rated speed :- 1.0 mps VS · Car/Landing door clear opening of 800 mm wide x 2000 mm high · Clear Car size of 1100mm wide x 1300mm deep x 2250mm high · Lift shaft available having clear size of1500mm wide x 2620mm deep, 1800mm Pit depth, 1800mm Overhead. · Doors type :- COPO/TOPO Doors with frame made from SS 304 grade solid(non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing doors with SS door architraves/frames The lift doors shall have minimum 1 hour fire rating (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory). · Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interior design shall be done as per the directions of engineer in charge. · COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor. · LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings. · Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port. The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protection for phase loss at input or output etc. various operation modes such as maintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility, auto return to home landing, fireman evacuation operation, earthquake operation, door open/close operation from COP etc. The system can record information for minimum 30 latest faults, with real-time clock management and handheld keypad with LCD screen for view and setting of parameters. The control panel duly wired with proper size & strength, copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class. · ARD complete with necessary SMF VRLA batteries. · Fireman controller having fireman switch at fire Landing. · CCTV surveillance system comprises of 2 nos minimum 2.0 MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup min. 90 days with min. 18” FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. · Lift Machine of Gearless PMSM of suitable kW with duty cycle of minimum 120 starts/hr (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. · Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work. · Minor civil work such as alteration work if any necessary for erection of landing door frames and it's accessories e.g. sill, header, hole pass etc complete with plaster finish, civil work for erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT. · General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. · The above rate includes Fully Comprehensive AMC for one year from the date of commissioning. (Main lift: 1087600+Add on A(2) (137031x1)+ B(1) 27340= 1251971.00)
Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete.
Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following :(a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP
Supplying & erecting automatic control panel for 3 Ph, 415 volt, A.C. Submersible/centrifugal type booster pump 1no up to 7.5 HP - 10 H.P. consisting of DOL starter having relay range 13-22 AMP,S.P.P., Combined ammeter/voltmeter, phase indicating lamp enclosed in CRCA powder coated Vibration proof enclosure with IP 54 protection. Control Panel should offer single phasing, phase reversal, phase imbalance etc.
Supplying and erecting metal work in CRCA sheet including Iron work for supports with fabrication of boxes, panel boards, etc. including cutting, bending, drilling, welding, riveting, treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete.
Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.
Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG
Supplying and erecting 12/15 mm dia pressure switch with provided isolation valve, G.I. nipple, elbow, etc complete as per specification no. FF-FFA/PS
Providing and fixing high-density polyethylene (HDPE) container one piece moulded triple layer water tank made out of high density polyethylene and built corrugated inclusive of delivery up to destination hoisting and fixing of accessories such as inlet, outlet overflow pipe inclusive of all tanks capacity up to 20000 litres.
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying and erecting 100 mm dia cast iron double flange NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV
Supplying and erecting 100 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting G.I. pipe ‘C’ class ERW 25 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 75/80 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 100 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting 100 mm dia cast iron foot valve ball type/flap type with strainer for negative suction complete as per specification no. FF-VL/FV
Supplying and erecting 25 mm dia gun metal gate valve complete with PN16 pressure rating, as per specification no. FF-VL/GV
Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) along with necessary accessories complete as per specification no. FF-FFA/HV
Supplying and erecting M.S./CRCA cabinet for housing single hydrant valve of size ( 400 x 400 x 400)mm or hose pipe box of size ( 600 x 600 x 200)mm made from min. 1.5 mm thick CRCA sheet with angle iron work of min. of size (25 x 25 x 4) mm having front doors with viewing glass of size (200x150) mm and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5)
Supplying and erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specifications no. FF-FFA/NZ
Supplying and erecting 63mm dia, reinforced rubber lined (R.R.L.) hose pipe, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying and erecting gun metal single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV
Supplying, erecting testing and commissioning optical type smoke detector on suitable back box with necessary connections complete as per specification no. FF-FAS/SD
Supplying, installing, testing and commissioning FR, XLPE armoured cable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU
Supplying, installing, testing and commissioning of 2 Zones Microprocessor based conventional fire alarm control panel (FACP) with standard accessories , 16x2 Character LCD Display, provision for zone wise contact and beep sound alarm, suitable to operate on 120-220 V AC, 0 - 49 Deg C, 93 ± 2 Percentage RH (non- condensing) at 32 ± 2 Deg C complete as per specification no. FF-FAAS/FACP
Supplying & erecting four pole ON LOAD change over switch, 415V, 200A, open execution having staggered termination, phase barrier, shroud termination and terminal cover along with auxiliary contacts and ready to upgrade with fuse protection kit, operat
Supplying, erecting, testing and commissioning of diesel generating set with alternator of 62.5 kVA output continuous rating, 3 Phase, 415 V, 50c/s 0.8 p. f. A.C supply, a totally enclosed air cooled / liquid cooled multi-cylinder diesel engine developing
Supplying, erecting, testing and commissioning of microprocessor based AMF panel suitable for diesel generating set of above 50 kVA up to 62.5 kVA capacity Three phase, 415 Volts, 50Hz A.C. with all standard features, safeties etc as per specification no
Providing earthing with copper earth plate size 30 x 30 x 0.315 cm complete with all materials, testing & recording the results as per specification no. EA-EP
Supplying and erecting copper strip of high purity required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint with joints required. As per specification no. EA-EP.
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 95 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per
Excavating hard murum / stone metal road by chiselling for preparing pit for poles stay or earth plates or for laying cables, pipes & clearing the site by removing debris & making the site as required complete.
Making cement concrete foundation in 1:3:6 cement concrete, (20 to 25) mm. stone metal duly plastered with necessary curing for complete. (pole muffing or any other purpose).
Supplying, installing, testing and commissioning of 25 kWp ON-GRID Solar PV System / Plant consisting Solar PV Poly Crystalline Panel (335 Wp X 75 Nos.) and Solar ON-GRID Inverter of similar capacity (THD<3%) with interconnecting wires / cables up to solar ON GRID inverter, proper base plate, canopy box to house Inverter and necessary accessories i.e. ACDB/ DCDB , MCB etc. wiring up to solar Inverter in casing and capping, display board, sign board, two distinct earthing, lightning arrester, liaisoning charges, remote monitoring system with maintaining card / chip for 5 years including net charges for RMS System, complete up to net meter installation and export to the grid with 5 year ON-SITE warranty and fully comprehensive maintenance contract as per Specification no. ESD-RT-ONG.
Providing & erecting 3 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact.
Supplying and erecting SS enclosure for MCCB suitable for up to 100A MCCB.
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 50 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per
Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding
Supplying and erecting AC three phase LT CT multifunction net meter DLMS compliance of accuracy class 0.5, 3 x 240V, 50Hz, with backlit LCD display, optical port & RS 232 port (measures import kWh, kVAh, export kWh, kVAh, Net kWh, kVAh, V, I, kW,
Supplying and erecting LT CT multifunction DLMS compliance energy meter of accuracy of class 0.5 , 3x240V,50 Hz with optical & RS 232 port, backlit LCD, measure & display trivector energy, load survey, TOD, tamper detection & logging, power ON /OFF ev
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included) (for pumps).
Supplying and erecting LT current with bar primary 50/5 to 1000/5 ratio with 15 VA burden erected in provided CRCA box duly secured with insulating materials connected to the meter with test certificates.
Supplying, installation and testing of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fi
Supplying and erecting copper strip of high purity required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint with joints required. As per specification no. EA-EP.
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP.
Providng earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP
Supplying & erecting conventional spike type air termination suitable to carry lightning stroke made up of heavy gauge 40 mm dia copper pipe of standard length with 5 Nos. copper spikes fixed on copper ball as air terminals duly threaded in copper pip
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral with compliance to IEC 61643-11 as per specification
Supplying and erecting HMS PVC conduit FRLS grade 20 mm dia. with necessary accessories in wall/floor with chiselling appropriately
Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification
Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No:
Supplying and erecting mains with 1x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No:
Supplying and erecting mains with 2x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No:
Supplying and erecting green earth wire 1x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification
Supplying and erecting mains with 2x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification
Supplying and erecting green earth wire with 1x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification
Supplying and erecting mains with 4x6 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification
Supplying and erecting Ceiling rose / Batten holder / Slanting holder / hanging cord switch / hanging bell push / pendant holder bakelite base 6A. erected on filled polypropylene board or polished double wooden block/ PVC junction box.
Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type switch 16A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type bell-push with indicator 2 modules 6A / 10A, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type (two module) electronic step regulator for fan, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type blanking plate one module, duly erected on provided plate & box.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 2 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 3 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 6 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 12 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Point wiring for light/bell concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification
Point wiring for ceiling fan concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No:
Wiring for plug on board with Switch socket surface/concealed type, copper wiring and earthing and with modular accessories as per specification No:
Supplying and erecting LED square / circular Max. 18 W down lighter/ Panel Light having pressure die-cast aluminium housing, polystyrene diffuser having system lumens output of Min. 2000 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty.
Supplying and erecting anodized aluminium corridor / passage / mirror light LED fitting (2 feet) Max. 12W with high transitivity diffuser with min. system lumens output of 1200 lumens, min. efficacy of 100 lumen/W, CRI>80, CCT upto 6000K, Beam Angle of 110 deg., Ripple<5%, THD<10%, p.f. >0.95, operating range of 200-270V, surge protection of 2 kV, Life class of 50,000 Hrs. at L70B50, including driver with end caps on provided PVC Block / wooden board with 3 years warranty.
Supplying & erecting inverter LED batten 20W tube light fitting with polycarbonate housing, heat sink, integrated HF electronic driver, Min. 2600 mAh Lithium ion Battery with charging time of 8-10 Hours and backup time of Min. 3 hrs. with minimum 25% of initial Watts having luminous efficacy of 100 lumen/watt, CRI>80, CCT of 6500K and THD<=20% having useful life of minimum 25000 hrs. with overheating protection with 2 years warranty.
Supplying and erecting Energy Saving BLDC Ceiling fan 230 V A.C. 50 cycles 1200 mm, max. energy consumption of 28W having service ratio (CMM/W) of Min. 8 , PF>0.9, THD<10% with IR remote control/compatible speed regulator, Temperature Rise of Max. 40 deg. C, having external mounted control PCB completely erected in position as per specification no.
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 225mm. 1400 RPM rust proof body & blades, wire mesh, duly erected, complete.
Supplying, erecting & marking SPMCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no.
Supplying, erecting & marking SPMCB 6A to 32A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no.
Supplying, erecting and marking four pole isolators only switch version of miniature circuit breakers of 40A in provided distribution board.
Supplying, erecting and marking four pole isolators only switch version of miniature circuit breakers of 63A in provided distribution board.
Supplying & erecting triple pole and neutral distribution board (TPNDB), SPMCB of 4 ways/phase (12 poles), with door, 1.2mm thickness, surface/flush mounted, IP 43 protection on iron/GI frame (horizontal busbar type) as per specification no.
Supplying and installing cat-6 cable suitable for networking as per specification no.
Supplying and fixing 2 m UTP patch cord of cat 6 type in position as per specification No.
Supplying and fixing 9U wall mount rack (Dimension-DxWxH – 500x600x500 mm) as per specification No.
Supplying and fixing 24 ports light guide unloaded interconnect unit, rack mounted type, with adapter panel for termination of optical fibre cables in provided U rack complete as per specification no.
Supplying and fixing Power Distribution Unit for networking rack comprises of 6/16A (6 Nos. sockets), 25 A modular MCB, appropriate rating fuse and indicator lamp, enclosed in black powder coated metal with necessary arrangement for fixing as per specification No.
Supplying and fixing 24 port patch panel with tool-less keystone jacks in provided U Rack complete as per specification no.
Supplying and fixing tool-less IO (Ethernet) flush/surface type in provided modular box as per specification no.
Supplying and erecting 10m HDMI cord low voltage grade minimum 4k compliant to be laid in provided conduits with male/female 19 pin HDMI connectors complete.
Supplying and installing cat-6 STP cable suitable for networking complete as per specification.
Supplying, fixing, and configuring 8-ports 1 G unmanaged gigabit POE switch erected in provided rack complete.
Supplying, installing and testing UTP connector (RJ-45) as per specification No.
Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.
Supplying, installing, testing & commissioning of 32/40 Ch. Network Video Recorder (NVR), suitable connect Min. 32 IP Cameras, up to 5 Megapixel Resolution, with HDMI/VGA outputs, provided HDMI output of 4K resolution or VGA output with output up to 1920 x 1080.Support H.265 or higher, H.264, MJPEG,Incoming Bandwidth 250Mbps with minimum 4 SATA Hard Disks, ANR Technology,4 SATA interfaces for 4 HDDs and capacity of each HDD up to 8TB, minimum 02 USB port, Alarm 1/0 16/4, RJ-45 10/100/1000 Mbps self-adaptive Ethernet interface, ONVIF conformance, Multiple network monitoring: Web viewer. support protocol TCP/IP, DHCP, DNS, DDNS, NTP, SADP, SMTP, NFS, iSCSI, UPnP, HTTPS. RoHS, UL, CE, FCC certified.Duly erected in provided U Rack with wiring connections, tagging and programming etc. complete as per specification no.
Supplying & erecting of High definition 4/5 Megapixel IP IR Bullet Camera with following features Image Sensor: Minimum 1/2.8" Progressive Scan CMOS, Video Resolution: Minimum 2592 x 1520 Video Compression: H.264, H.265 or higher, at least Three individually configurable stream, Frame rate: Minimum 25 (ps at all resolutions, WDR: minimum 120 dB Wide Dynamic Range, ONVIF conforming profile, Minimum IR distance: 50m, Lens Type: 2.8/4/6 mm Lens, fixed focal, Field of View: 2.8 mm, horizontal FOV 107°, vertical FOV 57°, diagonal FOV 129° 4 mm, horizontal FOV 86°, vertical FOV 47°, diagonal FOV 102° 6 mm, horizontal FOV 55°, vertical FOV 29°, diagonal FOV 65°Lux sensitivity - Minimum 0.2 Lux at color, Minimum 0.05 Lux at Black & White, 0.0 Lux (IR) Night Vision Distance Minimum IR - 50m. Camera minimum Adjustment Angles - Pan: 350°, Tilt: 72°, Rotate :350°. Power Supply: Support 12VDC & PoE, IP67, IK10-Vandal Resistant. Built in micro SD/SDHC/SDXC card slot of Minimum 128 GB, Built in microphone. Minimum Input/Output - Audio in x 1, Audio Out x 1, Alarm in 1, Alarm Out x 1. Image Settings: Rotate mode, saturation, brightness, contrast, sharpness, gain, white balance. Image Enhancements: Day/Night Auto (ICR)/Color/Black & White, 3D Digital Noise Reduction, Automatic White Balance, Automatic Gain Control, Backlight Compensation, Highlight Sanctioned by SE Nanded vide letter no 47122 Est no 1653 22-23
Supplying & erecting 8 TB internal Surveillance HDD suitable for SATA Port of NVR, interface transfer rate 6 GB/S, Maximum sustained transfer rate 210 MB/Sec to 213 MB/S. Drive bay supported 08+, Cameras supported up to 64, Cache (MB) 256, Load/Unload Cycle-3000000, Work Load Rating per Year 180TB, MTBF 1000000 Hrs. HTTPS, RoHS, UL, CE certified, duly erected in position in provided NVR as per specifications CCTV
Supplying & erecting 43" professional LED display with 1920*1080 (Full HD) Display, suitable for 16/32 channel NVR and following features Brightness: minimum 500 cd/m2 Contrast Ratio: minimum 1000:1 Viewing angle: 178/178 deg.Response time: maximum 8 ms Inputs: HDMI, VGA, BNC,USB, Audio In, Built-in speakers maximum 10 W, Suitable to operate on 100-240 V 50 Hz AC supply and 24/7 Duty Cycle duly erected on wall or table top with standard accessories like wall mount stand and wiring connections etc. complete as per specifications no. CCTV-MON Sanctioned by SE Nanded vide letter no 47122 Est no 1653 22-23
Supplying & erecting triple pole and neutral distribution board (TPNDB), 3 pole/ 4 pole MCCB as incomer & outgoing SP MCB (12 poles) or TP MCB of 4 ways (12 poles), with door, 1.2mm thickness, surface/flush mounted, on iron/GI frame (vertical busbar type) as per specification no.
Providing & erecting 3 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no.
Supplying, erecting & marking TPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no.
Supplying, erecting & marking SPMCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no.
Supplying and erecting switch disconnector fuse (SDF) 415V, 100A, with enclosure, four pole AC23 A rated with terminal shrouds on both sides and phase barriers along with telescopic shaft for depth adjustments and door interlock and padlock complying to IS/IEC 60947-3 Part-1/3 HRC - DIN type fuse switch, insulation voltage 1000 V , with rotary handle for ON / OFF operation (without HRC fuse)
Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.
Providng earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no.
Providing pipe type earthing with 40mm. dia. G.I. pipe or 20 mm dia. G.I. Rod complete with all materials testing and recording the results as per specification no.
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 50 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no.
Supplying and laying (including excavation of suitable width & depth up to 90 cm) 90 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete.
MSEDCL charges
Supplying, installing, testing and commissioning of 3 kWp ON-GRID Solar PV System / Plant consisting solar PV poly crystalline panel (335 Wp X 09 Nos.) and Solar ON-GRID Inverter of similar capacity (THD<3%) with interconnecting wires / cables up to solar ON GRID inverter, proper base plate, canopy box to house Inverter and necessary accessories i.e. ACDB/ DCDB , MCB etc. wiring up to solar Inverter in casing and capping, display board, sign board, two distinct earthing, lightning arrester, liaisoning charges, remote monitoring system with maintaining card / chip for 5 years including net charges for RMS system, complete up to net meter installation and export to the grid with 5 year ON-SITE warranty and fully comprehensive maintenance contract as per specification no.
Supplying, erecting & marking TPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no.
Supplying & erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBO complete erected on angle iron/GI frame.
Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.
Supplying and erecting Intelligent flush mounted panel meter three phase four wire (IPM) input voltage measurement range 50-550 V AC (P-P) 415V, aux. supply 90-300 V AC/DC, flush mounted (96 x 96 mm) meter constant Wh viewing in LCD multifunction meters in auto scroll mode with voltage, current, frequency, power factor kW, kVA, kVAR, kWh, kVAh, kVARh, phase angle, interrupts, THD, complete with RS 485 communication protocol, class 1 accuracy and wiring connections and mounting hardware on provided panels complete with calibration certificate from manufacturer.
Supplying and erecting AC three phase LT CT multifunction net meter DLMS compliance of accuracy class 0.5, 3 x 240V, 50Hz, with backlit LCD display, optical port & RS 232 port (measures import kWh, kVAh, export kWh, kVAh, Net kWh, kVAh, V, I, kW, 6 months history of energy, load survey, TOD, tamper detection & logging, power ON/OFF events, instantaneous parameters of rating 1/5A with display in absence of power) with wiring connections and mounting hardware on provided panels complete with calibration certificate from manufacturer.
Supplying, installation & marking of surge arrestor/ surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 50 kA for three phase and neutral with compliance to IEC 61643-11 as per specification no.
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 6 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no.
Providing earthing with copper earth plate size 30 x 30 x 0.315 cm complete with all materials, testing & recording the results as per specification no.
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no
Supplying & erecting conventional spike type air termination suitable to carry lightning stroke made up of heavy gauge 40 mm dia copper pipe of standard length with 5 Nos. copper spikes fixed on copper ball as air terminals duly threaded in copper pipe erected on provided foundation complete.
Supplying and erecting GI sheet 0.6 mm (24 SWG) having zinc coating of 275 microns with galvanization process compliance to IS 2629:1985 to be used for fabrication of boxes panel boards etc. including cutting, bending, drilling, welding, riveting etc. and painting with one coat of red lead paint and 2 coats of enamel paint.
Supplying & erecting of required size electrolyte copper bus patti or bar tin plated in bus bar chamber/in panel or any other purpose, suitable for 500 volt with require capacity having thermal conductivity of 400W per meter with composition Pure copper 99.9% Current density 1.8 with fixing arrangement (like lug or bottle type lug) to both the end with high grade polyolefin insulation sleeve complete as per specification no.
Making trench in soft soil having 0.75 m depth and minimum 0.3 m width for laying provided cables up to voltage level of 1.1kV complete As per specification No.
Making cement concrete foundation in 1:3:6 cement concrete, (20 to 25) mm. stone metal duly plastered with necessary curing for complete. (pole muffing or any other purpose).
Providing & erecting 6 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 130 mm A/F, top 70 mm A/F on provided foundation as per specification no.
Providing and erecting galvanised 1000mm single arm sword type bracket with FRP dome and ball as per specification no.
Providing and erecting galvanised 1000mm double arm sword type bracket with FRP dome and ball as per specification no.
Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V 2 core 4 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no.
Supplying and laying (including excavation of suitable width & depth up to 90 cm) 50 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete.
Supplying and erecting integrated LED street light fitting 60W IP65 & IK08 class having single piece pressure die-cast aluminium housing, having system lumens output of Min. 6600 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.95, operating range of 140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs. at L70B50, including driver complete with 3 Years warranty as per specification No
Supplying and erecting PVC insulated PVC round sheathed 2.5 sq.mm (50 no. x 0.25 mm dia.) 3 core flexible multi stranded copper Industrial cable for voltage grade up to 1.1 kV
Supplying, erecting & marking SPMCB 0.5A to 5A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no.
Providng earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no.
Providing pipe type earthing with 40mm. dia. G.I. pipe or 20 mm dia. G.I. Rod complete with all materials testing and recording the results as per specification no.
Supplying and erecting hylam sheet/ ebonite 6 mm thick for covering wall entries including cutting, drilling and fixing with nut bolts / screws etc. complete.
Supplying & erecting 415V, 16A porcelain base neutral link complete erected in provided M.S. box.
Making M- 20 grade reinforced cement concrete foundation by considering the safe soil bearing capacity at site as 10 T/sq.m at 1.5 m depth including supply of steel, concrete, excavation and fixing provided nut bolts with the help of template, duly plastered as per design complete (for 6m to 8m high octagonal /conical GI pole).
Supplying & erecting integral post top lantern fixtures (light house type) suitable upto LED 18 W Lamp consisting of combination of spun aluminium canopy & clear acrylic top cover, cast aluminium pole cap on provided pole/ bracket as per specification no.
Supplying & erecting 18W, 230V integral type LED Lamp suitable for B-22 / E-27 base.
Supplying & erecting FRP box of size 250mm x 200mm x 100 mm, 2.7 mm thick complete on pole/wall as per specification No.
Supplying & erecting G.I. pipe ‘A’ class 50 mm dia. erected for enclosing XLPE armoured cable on wall/pole as per specification no.
Supplying, installing, testing & commissioning split type variable speed inverter technology with minimum 3 to 1 convertible mode for compressor. room air conditioning unit 1.7TR to 2.0TR capacity having ISEER minimum 5.0 suitable to operate on 250V, 50 Hz, A.C. supply having 1 no of air handling unit hi-wall/floor mounting type complete with refrigerant R32 having copper condenser, minimum 2.5PM filter, self diagnosis feature, stabilizer free operation & temperature display on indoor unit, noise level maximum 50dBA at position in provided recess with wooden frame complete specification no.
Supplying, installing, testing & commissioning split type variable speed inverter technology with minimum 3 to 1 convertible mode for compressor, room air conditioning unit 1.3TR to 1.6TR capacity having ISEER minimum 5.00 suitable to operate on 250V, 50 Hz, A.C. supply having 1 no of air handling unit hi-wall/floor mounting type complete with refrigerant R32 having copper condenser, minimum 2.5PM filter, self diagnosis feature, stabilizer free operation & temperature display on indoor unit, noise level maximum 50dBA at position as per specification no.
Supplying & erecting seamless outside & inside, smooth, dry and clean copper pipe with ROHS compliant suitable for refrigerant having 22SWG thickness and inner dia/size 12mm complete.
Supplying & erecting seamless outside & inside, smooth, dry and clean copper pipe with ROHS compliant suitable for refrigerant having 22SWG thickness and inner dia/size 22mm complete.
Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.
Supplying and erecting elastomeric nitrile rubber / foam tube type sleeves for coating and insulating on provided PC / copper pipes having 9 mm thickness and inner diameter / sizes 12 mm for solar water heater/AC system.
Supplying and erecting elastomeric nitrile rubber / foam tube type sleeves for coating and insulating on provided PC / copper pipes having 9 mm thickness and inner diameter / sizes 22 mm for solar water heater/AC system.
Shubham EPC Private Limited
OMKAR CONSTRUCTION
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF