Loading…
Loading…
Tender Value
₹36.0 L
EMD Value
₹72,000
Closing Date
7 Sept 2026, 3:00 pm
DGM BSBCCL PATNA
DEPUTY GENERAL MANAGER PATNA
BSBCCL, Hospital Road, Sastri Nagar, Patna 800023
ANIL KUMAR
CGM
Electrification work for the operation of the dehumidifier installed at the Regional Office of the Bihar State Seed Corporation in Kudra, Kaimur district.
137912
18/BSBCCL/2026-27 GR02
Open Tender
ELECTRICAL
Patna
• Registration with Building Construction Department, Government of Bihar.
• Electrical Registration.
• GST registration certificate and Up to date clearance.
• PAN and Income Tax Return of previous financial Year.
• SELF DECLRAETION AFFIDAVIT.
• Character Certificate.
ELECTRICAL
PERCENTAGE
L1
1
6 documents required · 6 mandatory
₹5,000
Processing Fee: 1180
₹72,000
CGM BSBCCL
12 Aug 2026
12 Aug 2026
8 Sept 2026
12 Aug 2026
7 Sept 2026
12 Aug 2026
20 Aug 2026
BIHAR STATE BUILDING CONSTRUCTION CORPORATION LTD
Project:-Electrical Work for Dehumidifier at BEEJ Nigam,Kudra (Kaimur) .
Sr.No SOR-23 Descriptions Unit Quantity Rate Amount
1 2.33 Supplying and fixing following ways, surface/recess mounting, Vertical three phase distribution board ( VTPN DB's ) of CRCA sheet steel, dust protected, duly powder painted suitable for upto 160 amp, four pole MCCB as Incomer and SP/TP MCB's as outgoing inclusive of tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's etc as required. (but without MCCB & MCBs)
2.33.1 4 way, Double door, I/C 160A, MCCB Each 6 12107.00 72642.00
2 2.4 Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections etc. as required.
3 7.7 Supply of following sizes and core PVC/XLPE insulated, PVC sheathed (heavy duty) armoured electrical power cable with aluminium conductor for working voltage upto 1.1 KV as required.
7.7.16 300 sq. mm, 3.5 core (Single RUN) Metre 100 2764.00 276400.00
4 7.9 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed PVC conduit as required.
5 1.7 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
1.7.1 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire Meter 375 201.00 75375.00
6 2.6 Providing and fixing following capacity double pole/ four pole OFF-load changeover switches with side handle operation, in sheet enclosure in existing metal board, including drilling holes in metal panel, making connections etc. as required.
7 2.12 Supplying and fixing following rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive loads of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
2.12.1 6 A to 32 A, Single pole Each 15 237.00 3555.00
8 2.5 Providing and fixing following capacity busbar chamber with 4 strips of suitable size made of copper, heavy duty, complete with all accessories including connections, earthing the body etc. as required.
9 8.11 Supply and fixing of fabricated Electrical control panel of cubical construction, floor/wall mounted type, fabricated out of 16 SWG CRCA sheet, compartmentalised with hinged doors, dust and vermin proof, powder coated painting of approved shade after 7 tank treatment process, cable alley, internal wiring, earth terminals, Bus bar Chamber, insulator and complete in all respect etc and panel manufactures must be approved by CPRI. (But without RYB inicator, ammeter, voltmeter, inter-connection copper conductor cable/solid copper strip, switchgears etc.) Sq.ft. 35 1809.00 63315.00
10 8.13 Supply and fixing panel mounted digital multimeter (Voltmeter & ammeter) including CT coil and RYB pilot indictor in the existing cubical panel board including drilling holes in the panel board making connections etc as required. Each 7 6536.00 45752.00
11 Derived 4261 80mm dia G.I. Pipe Meter 25 692.00 17300.00
12 AR Animal Resource Center Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanisation thickness not less than mininmum 70 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, bends, reducers, tee etc. as required.
150 mm width X 50 mm depth X 1.6 mm thickness Meter 50 604.00 30200.00
13 AR Beltron a) 800 A ACB, Compartment drawout type with micro processor release, 4pole, 65kA breaking capacity, with release range of 400-800A (min.)and mechanical and electrical interlock (Model SR18G -C-Power of L&T or similar Superior make) - 4 nos. (as per SLD) Each 1 225800.00 225800.00
a) 400A MCCB, with micro processor release, 4pole, 50kA breaking capacity, with release range of 160-400A a(Model D sine of L&T or similar Superior make) - 4 no.
b) 400A, 4 pole MCCB, 36kA, with thermal release 250-320A (Model D sine DN3-400D of L&T or SS make) - 3 no
c) 250A, 4 pole MCCB, 36kA, with Microprocessor release 100-250A (Model D sine DN2-250D of L&T or SS make) - 1 no
d) 100A, 4 pole MCCB, 36kA, with thermal release 80-100A (Model D-Sine, DN0-100D of L&T or SS make) - 1 no
e) 63A, 4 pole MCCB, 36kA, with thermal release 40-63A (Model D-Sine, DN0-100D of L&T or SS make) -2 no
f) 4 strip Alluminium Bus bar suitable for 1000A (preferably 60mm x 10mm x 2 nos Al flat) with heat shrinkable tube as per the drawing)
g) Multi function meter Digital- 10 set with CT and accessories
h) RYB Neon/ LED indicating lamp -5 set
i) Trip/ON/OFF indicating lamp -5 set
j) 500A ammeter with selector switch and CT - 2 set
k) All MCCB shall have rotary operating mechanism.
n) Inter connection of Bus bar and switch gears shall be made through suitable size Alluminium flats. Copper multi core cable shall be used for ineter connection upto 63A capacity.
j) 40 x 5 mm Allumnium Earth bus with insulation.
k) The Cubicle should have 2-part hinged door with front and back openeable system.
l) All other required accessories, wirings, as per SLD
Supplying and making indoor end termination with brass compression gland and copper lugs for following size of XLPE insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1kV grade as required. .
14 8.12 Supply and fixing fabricated Feeder pillar of cubical construction, floor mounted type, fabricated out of 14 SWG CRCA sheet, compartmentalised with hinged doors, dust and vermin proof, powder coated painting of approved shade after 7 tank treatment process, cable alley, internal wiring, earth terminals, Bus bar Chamber, insulator, with 40mm X 40mm X 5mm angle iron stand and complete in all respect etc and must be CPRI approved panel manufactures. (But without RYB LED lamp, ammeter, voltmeter, inter-connection copper conductor cable/solid copper strip, switchgears, PCC work etc.) Sq.ft. 70 2261.00 158270.00
15 9.13 Providing , laying and fixing of following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc as required.(Road Cutting & Laying)
16 9.10 Providing and laying in position reinforced cement concrete 1: 2: 4 (1 : cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc. as required. (excluding reinforcement) Cum 5 8721.00 43605.00
Total Amount : RS 3597501.00
BIHAR STATE BUILDING CONSTRUCTION CORPORATION LTD
Project:-Electrical Work for Dehumidifier at BEEJ Nigam,Kudra (Kaimur) .
Sr.No SOR-23 Descriptions Unit Quantity Rate Amount
1 2.33 Supplying and fixing following ways, surface/recess mounting, Vertical three phase distribution board ( VTPN DB's ) of CRCA sheet steel, dust protected, duly powder painted suitable for upto 160 amp, four pole MCCB as Incomer and SP/TP MCB's as outgoing inclusive of tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's etc as required. (but without MCCB & MCBs)
2.33.1 4 way, Double door, I/C 160A, MCCB Each 6 12107.00 72642.00
2 2.4 Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections etc. as required.
3 7.7 Supply of following sizes and core PVC/XLPE insulated, PVC sheathed (heavy duty) armoured electrical power cable with aluminium conductor for working voltage upto 1.1 KV as required.
7.7.16 300 sq. mm, 3.5 core (Single RUN) Metre 100 2764.00 276400.00
4 7.9 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed PVC conduit as required.
5 1.7 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
1.7.1 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire Meter 375 201.00 75375.00
6 2.6 Providing and fixing following capacity double pole/ four pole OFF-load changeover switches with side handle operation, in sheet enclosure in existing metal board, including drilling holes in metal panel, making connections etc. as required.
7 2.12 Supplying and fixing following rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive loads of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
2.12.1 6 A to 32 A, Single pole Each 15 237.00 3555.00
8 2.5 Providing and fixing following capacity busbar chamber with 4 strips of suitable size made of copper, heavy duty, complete with all accessories including connections, earthing the body etc. as required.
9 8.11 Supply and fixing of fabricated Electrical control panel of cubical construction, floor/wall mounted type, fabricated out of 16 SWG CRCA sheet, compartmentalised with hinged doors, dust and vermin proof, powder coated painting of approved shade after 7 tank treatment process, cable alley, internal wiring, earth terminals, Bus bar Chamber, insulator and complete in all respect etc and panel manufactures must be approved by CPRI. (But without RYB inicator, ammeter, voltmeter, inter-connection copper conductor cable/solid copper strip, switchgears etc.) Sq.ft. 35 1809.00 63315.00
10 8.13 Supply and fixing panel mounted digital multimeter (Voltmeter & ammeter) including CT coil and RYB pilot indictor in the existing cubical panel board including drilling holes in the panel board making connections etc as required. Each 7 6536.00 45752.00
11 Derived 4261 80mm dia G.I. Pipe Meter 25 692.00 17300.00
12 AR Animal Resource Center Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanisation thickness not less than mininmum 70 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, bends, reducers, tee etc. as required.
150 mm width X 50 mm depth X 1.6 mm thickness Meter 50 604.00 30200.00
13 AR Beltron a) 800 A ACB, Compartment drawout type with micro processor release, 4pole, 65kA breaking capacity, with release range of 400-800A (min.)and mechanical and electrical interlock (Model SR18G -C-Power of L&T or similar Superior make) - 4 nos. (as per SLD) Each 1 225800.00 225800.00
a) 400A MCCB, with micro processor release, 4pole, 50kA breaking capacity, with release range of 160-400A a(Model D sine of L&T or similar Superior make) - 4 no.
b) 400A, 4 pole MCCB, 36kA, with thermal release 250-320A (Model D sine DN3-400D of L&T or SS make) - 3 no
c) 250A, 4 pole MCCB, 36kA, with Microprocessor release 100-250A (Model D sine DN2-250D of L&T or SS make) - 1 no
d) 100A, 4 pole MCCB, 36kA, with thermal release 80-100A (Model D-Sine, DN0-100D of L&T or SS make) - 1 no
e) 63A, 4 pole MCCB, 36kA, with thermal release 40-63A (Model D-Sine, DN0-100D of L&T or SS make) -2 no
f) 4 strip Alluminium Bus bar suitable for 1000A (preferably 60mm x 10mm x 2 nos Al flat) with heat shrinkable tube as per the drawing)
g) Multi function meter Digital- 10 set with CT and accessories
h) RYB Neon/ LED indicating lamp -5 set
i) Trip/ON/OFF indicating lamp -5 set
j) 500A ammeter with selector switch and CT - 2 set
k) All MCCB shall have rotary operating mechanism.
n) Inter connection of Bus bar and switch gears shall be made through suitable size Alluminium flats. Copper multi core cable shall be used for ineter connection upto 63A capacity.
j) 40 x 5 mm Allumnium Earth bus with insulation.
k) The Cubicle should have 2-part hinged door with front and back openeable system.
l) All other required accessories, wirings, as per SLD
Supplying and making indoor end termination with brass compression gland and copper lugs for following size of XLPE insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1kV grade as required. .
14 8.12 Supply and fixing fabricated Feeder pillar of cubical construction, floor mounted type, fabricated out of 14 SWG CRCA sheet, compartmentalised with hinged doors, dust and vermin proof, powder coated painting of approved shade after 7 tank treatment process, cable alley, internal wiring, earth terminals, Bus bar Chamber, insulator, with 40mm X 40mm X 5mm angle iron stand and complete in all respect etc and must be CPRI approved panel manufactures. (But without RYB LED lamp, ammeter, voltmeter, inter-connection copper conductor cable/solid copper strip, switchgears, PCC work etc.) Sq.ft. 70 2261.00 158270.00
15 9.13 Providing , laying and fixing of following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc as required.(Road Cutting & Laying)
16 9.10 Providing and laying in position reinforced cement concrete 1: 2: 4 (1 : cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc. as required. (excluding reinforcement) Cum 5 8721.00 43605.00
Total Amount : RS 3597501.00
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT 18 Gr02.pdf
NIT • 1.44 MB
NIT 18 Gr02-2.pdf
NIT • 1.44 MB
BOQ_ KUDARA DEHUMIDIFIER.xlsx
NIT • 0.02 MB
BOQ_ KUDARA DEHUMIDIFIER-2.xlsx
NIT • 0.02 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].