DIRECTOR, CSIR-NAL, BENGALURU - 560 017
DIRECTOR, CSIR - NATIONAL AEROSPACE LABORATORIES, KODIHALLI, P.B.No.1779, BENGALURU - 560 017
Renovation of electrical installations in toilets and various Rooms at KTMD, Library buildings and other allied electrical works at CSIR-NAL Kodihalli, Bengaluru-560017
2023_CSIR_143290_1
ESD-NAL/17/E/2022-23
Open Tender
Electrical Works
Item Rate
150 days
CSIR-NAL, KODIHALLI, BENGALURU - 560 017
PLEASE REFER TENDER DOCUMENT
11 documents required · 11 mandatory
₹500
DIRECTOR, CSIR-NAL, BENGALURU - 560 017
₹18,456
9 Mar 2023
3 Feb 2023
21 Feb 2023
3 Feb 2023
20 Feb 2023
3 Feb 2023
Amount
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 3742019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
Wiring for light point / fan point / exhaust fan point / call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor cable in surface / recessed PVC conduit / casing capping, with modular switch , modular plate, suitable G.I / PVC box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor cable etc. as required. (Group C) Note: More than one light / fan / exhaust fan controls located at one place, the necessary modules may be used as against single PVC surface box and controls each point shall be individual with all other accessories as required.
Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.(Group C)
Supplying and fixing of 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Single pole and neutral
Triple pole and neutral
Supplying and drawing following sizes of FRLS PVC insulated copper conductor cable in the existing surface / recessed steel / PVC conduit / trunking / cable tray as required
1 x 1.5 sq. mm
2 x 2.5 sq. mm
2 x 4 sq.mm
Supplying and fixing of 25 mm size of medium class PVC conduit along with accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing of following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required
5/6 A switch
15 / 16 A switch
3 pin 5/6 A socket outlet
6 pin 15/16 A socket outlet
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc as required
1 or 2 Module (75mmX75mm)
3 Module (100mm X 75 mm)
4 Module (125mmX75mm)
6 Module (200mmX75mm)
Supplying and fixing 6 Modular base & cover plate on existing modular metal boxes etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required.
Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
Installation, testing and commissioning of pre-wired, fluorescent fitting / LED fittings / compact fluorescent fitting of all types, complete with all accessories including GI pipe bracket for mounting of building lights/street light and tube etc. directly on ceiling / wall/building, including connection with 3C x 1.5 sq.mm FR PVC insulated, copper conductor/1.5sq.mm single core cable and earthing etc all complete as required.
Installation upto 450 mm sweep exhaust fan in the existing opening, including connection, testing, commissioning etc all complete as required.
Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of sizes upto 450 mm as required.
Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 amps “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing 4 way (4 + 12), Double door horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
Providing & fixing 25 mm x 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Upto 35 Sq.mm
Above 35 Sq.mm and upto 95 Sq.mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of above 35 Sq.mm and upto 95 Sq.mm size on cable tray as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of upto 35 Sq.mm size in the existing RCC/ HUME/ METAL pipe as required
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required
4 C X 10 Sq.mm (25 mm)
4 C X 16 Sq.mm (28 mm)
4 C X 50 Sq.mm (35 mm)
Supply of 18 / 20 W, LED cool day white surface mounting square / round panel luminaries with high efficient LED & glare free opal diffuser having IP 20 protection luminaries with CRCA / aluminum housing enclosure including control electronic gear etc. all complete and suitable for operation on 230V, 50 Hz, AC power supply as required.
Supply of surface mounted LED flat panel of 36/40W, 4'x1' feet cool day light . The lumen output shall not be less than 100 lm / W, minimum colour temprature of 5700 k,high efficiency OPAL diffuser (OD) constant control electronic gear, PF > 0 .9 with CRCA front frame with high efficiency glare free opal diffuser & CRCA / aluminium housing with pre-coated white colour etc,. and ready for operation on 230V, 50 Hz, AC power supply.
Supply of Recess mounted LED flat panel of 36/40W, 2'x2' feet cool day light . The lumen output shall not be less than 100 lm / W, minimum colour temprature of 5700 k,high efficiency OPAL diffuser (OD) constant control electronic gear, PF > 0 .9 with CRCA front frame with high efficiency glare free opal diffuser & CRCA / aluminium housing with pre-coated white colour etc,. and ready for operation on 230V, 50 Hz, AC power supply.
Supply of 400 mm sweep wall mounted fan with speed of 1300 RPM,Aerodynamically designed & balanced blades for smooth oscillation, pull cords for speed regulation and wide oscillation control suitable to operate on 230 V, 50 Hz AC supply etc,. all complete as required.
Supplying and fixing 6 Modular PVC surface box for modular switches on surface etc as required.
Supply and fixing of DP metal enclosure suitable for fixing of SPN MCBs on surface / recess on the wall and matching with surroundings as required.
Supply of 300 mm sweep 1300 RPM powder coated metal finish exhaust fan suitable to operate on 230 V, 50 Hz AC supply etc,. all complete as required.
Supply of louvers / shutters made out of sheet steel including necessary painting suitable for 300 mm sweep medium duty exhaust fans as required.
Suppply and fixing of 32X12.5 mm mini DLP trunking with flexible cover on surface including fasteners as required.
Supply, installation, testing & commissioning of maintenance free earthing system using 3000 mm length, 77-80 mm outer dia copper bonded M.S. Pipe as primary electrode. The Copper bonded pipe electrodes shall be of molecularly bonding of pure electrolytic copper (99.9%). The hollow space of the electrode shall be duly filled using high conductive and non-corrosive compound to withstand fault current lands on the electrode. Both the ends of the pipe / electrode shall be permanently sealed and the top portion of the earth electrode shall be provided with extended lead holes on the terminal for connecting to the earth terminals. The earth pit shall be refilled using environment friendly low resistance grounding minerals having a combination of graphite & natural earth minerals to form a low resistance zone all round the electrode. The required quantity of water shall be poured inside the earth pit as per the OEM recommendations as required. The necessary earth chamber shall be provided using heavy duty weather proof plastic cover.
Supply & laying of 2000mm(L) x 1000mm(W) x 2mm thickness Insulating mats made of Elastomer (a generic term that includes rubbers, latex and elastomeric compounds that may be natural or synthetic or a mixture or a combination of both) the insulating mat shall be made out of elastomer with anti skid surface and without metallic derivatives. The mat shall be high dielectric strength and high insulation resistance with voltages up to 3.3kV AC as per IS15652 as required.
Supply Installation testing & commissioning of 90W LED lensed type street light pressure die cast aluminium housing, heat resistant control driver, toughened glass with frame, IP66 protection, better optics for uniform light distribution,Luminaire efficacy of > 100 lm/W , LED light output color shall be cool day white,THD < 10 %, PF > 0.9 including GI pipe bracket for mounting of building lights/street light suitable for operation on 230V, AC supply.
Supply & drawing of 1 x 2.5 sq.mm, FRLS PVC insulated copper conductor cable of 1.1 kV grade in the existing surface / recessed steel / PVC conduit / cable raceways / cable trunking as a earth conductor as required.
Supply of 4 C x 16 sq.mm size aluminum conductor, XLPE Insulated, cores laid up tape, PVC inner sheathed, flat GI armoured power cable (A2XFY) of 1.1kV grade as per IS - 7098 (part-I) - 1988. as required.
Supply of 4 C x 10 sq.mm size aluminum conductor, XLPE Insulated, cores laid up tape, PVC inner sheathed, flat GI armoured power cable (A2XFY) of 1.1kV grade as per IS - 7098 (part-I) - 1988. as required.
Supply of 4 C x 50 sq.mm size aluminum conductor, XLPE Insulated, cores laid up tape, PVC inner sheathed, flat GI armoured power cable (A2XFY) of 1.1kV grade as per IS - 7098 (part-I) - 1988. as required.
Providing, laying and fixing 50 mm dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required.
Disconnection & dismantling of existing Industrial light fixtures,Ceiling fans & exhaust fans. The dismantled items shall be shifted to central stores located at a distance of 300 meters from the site as directed by the Engineer In charge.
Dismantling of existing unserviceable recess / surface type, circuit mains / wiring, fan regulators,trunking, TPN switches, sockets of various rating & other accessories etc. all complete as required and same shall be shifted to CSIR-NAL central stores located at a distance of 300 meters as required.
AKEY ELECTRO TECHNIQUES
VEDAPRAKASH ELECTRICALS
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .