Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance MIRZAPUR MUMTAZ NAGAR AYODHYA AYODHYA UTTAR PRADESH 224001 | AYODHYA | UTTAR PRADESH | 224001 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Rejected-Technical | Rejected-Technical required documents not submitted |
Tender Value
₹12.0 L
EMD Value
₹12,000
Closing Date
16 Jan 2023, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE EWC AYODHYA
Office of the Superintending Engineer Electricity Works Circle, Ayodhya
12/SE/EWC/AYO/2023-24
2023_MVVNL_765767_1
12/SE/EWC/AYO/2023-24
Open Tender
Electrical Works
Item Rate
30 days
amethi
Please refer Tender documents.
3 documents required · 3 mandatory
₹3,540
SUPERINTENDING ENGINEER, ELECTRICITY WORKS CIRCLE
₹12,000
Yes
12 Jan 2024
10 Jan 2023
17 Jan 2023
10 Jan 2023
16 Jan 2023
10 Jan 2023
Amount
Safe Loading, Carriage and then safe unloading of the following material from Store Centres Under the jurisdiction of EEESD Ayodhaya to dump site proper stacking.
33 KV Bus Isolator
33 KV Post Insulator
33 KV Lightening Arrestor
33 KV VCB 800A, 750 MVA
33 KV Double T/F control pannel
C.T. O/D 33 KV CTR 200/100/1-1A
11 KV Incoming switch gear 600/300/5A, 350 MVA
Out going 11 KV switch gear 200/100/5A 250 MVA
11 KV 3 Core Cable 3x300 mm XLPE
11 KV 3x185 mm XLPE
11 KV cable jointing kit indoor 3x300 sq.mm. XLPE
11 KV cable jointing kit outdoor 3x300 sq.mm. XLPE
11 KV cable jointing kit indoor 3x185 sq.mm.
11 KV cable jointing kit outdoor 3x185 sq.mm.
ACSR Dog Conductor
M.S. Channel 125x65 (for Structures)
M.S. Angle 75x75x8 (for Structures)
ST Pole 11Mtr
Dropper Channel 100x50 mm 2028 mm
M.S.Angle iron 65x65x6 bracing 2700 mm
11 KV Top channel 100X50X2240 mm
11 KV Polymer pin insulator
6 SWG Wire
Stay wire 7/10
11 KV disc insulator T&C type
Opening of all the 33 KV Jumpers, Neutral connections, cable connections, opening of earth strips and then shifting of 5 MVA T/F from plinth to Other side in yard.
Shifting 33 KV Jumpers, from actual position to the new shifted place along with 11 KV cable and other accessories for maintaining & restoring the S/S supply
Plinth of 10 MVA, 33/11 KV T/Fs Expansion and major repairing of existing 5 MVA T/F plinth of less size to 3.5 Mtr x 3.5 Mtr suitable for 10 MVA T/F by RCC work of ratio 1:2:4 using M.S. Bar 10 mm dia (TOR) inreinforcement including cutting, bending and binding in required shape complete in all respect and shall be plastered/Finished on top and side of the Plinth.
Plinth for 33KV VCB Construction of plinth of size 2.0x1.5x0.9 (Mtr) suitable for erection of super structure for 33 Kv VCB including grouting of Anchor bolts in proper allingment and level. Scope of work includes excavation of foundation base concreting in CC 1:6:12 ( cement, fine sand and brick ballast) 1st class brick work in cement mortor of ratio 1:4 CC in Ratio 1:4:8 and RCC work in ratio 1:2:4 ( Cement, coarse sand and stone grit of 20 mm gauge) as per Drawing
H.T. Cable Laying Laying & dressing of 11 KV, 3x300 and 3X185 Sq.mm XLPE cable underground from 5 MVA T/F to 11 KV incoming switchgear in the trench 450mm wide, 900mm deep, providing 150mm fine sand cushion bench and 150mm fine sand cushion above the cable. The cable shall be duly protected by 1st class bricks two either side and third on top of the cables, laid in series one after the other, the work includes supplying of fine sand and bricks, refilling and ramming of the left out soil, closing the trench and leveling. Spare cable shall be left and buried in the trench in the safe of rings at both ends. Cable laying work includes unrolling, cutting, meggering and sealing both end of the cable. (All the material will be supplied by the contractor)
Erection and Installation of 33/11 KV 10 MVA Transformer Dragging of 33/11KV 10 MVA T/F from Dump site to road site and shifting of the T/F from road site to new constructed plinth distance about 150 mtr ,along with loading, unloading and carriage, fixing and fitting of all the accessiories and filling of T/F oil to the desired level and insuring that there is no leakage. Erection and installation of 33/11 Kv, 10 MVA Transformer in a leveled position on the plinth.
Installation of Bus Isolators Assembling and installation of Bus isolator on the Isolator structure , adjusting of opening mechanism in proper alignment so as to ensured smooth operation of the same. In case of line Isolator proper operation of earth links shall also be ensured. The work includes fabrication for proper fixing if required.
Installation of Post Insulator Installation of post insulator on the post insulator structure . The work includes fabrication for proper fixing if required.
Installation of Lightening Arrestors Assembling and installation/ mounting of three Nos.Lightening Arrestors on the L.A. structure/ complete with making earth connection ( Separate ) and line connections. The work includes fabrication for proper fixing if required.
Installation of 33 KV VCB Installation of 33 KV 750 MVA 800 Amp VCB on 33 KV VCB structure along with earthing by G.I. strip 50x6 mm size with main earthmat of Switchyards complete in all respect including commissioning.
Shifting carefully and installation of Single/double Transformer Control pannel in control room and its proper connection.
Installation Of CT Installation of 3 Nos CTs of ratio 200/100/1A on the CTs structure. The work includes fabrication for proper fixing if required. (All the material will be supplied by the contractor except Steel Section)
Installation of Switchgears in Control room Shifting carefully and safely 11 Kv incoming Switchgear, 11 KV outgoing Switchgear and 11 KV Bus Coupler from out side of the switch gear room, as per direction of Engineer Incharge, Placing and fixing of switchgear on foundation providing nuts & bolt of proper size in proper position and alignment and mountting of P.T. on incoming S/G.
Installation of Heat Shrinkable Type cable jointing kits indoor and O/D end Termination and S/T Joint suitable for 11 KV XLPE cable confirming to IS ESI-09-13-IS-13573 of 1992 amendment I&II VDE-0278 of latest version there of if any.
Cable stand Structure Fabrication & erection of 11 KV Cable Stand made of 02 No. M.S chanel 125x65x6 mm 3 Mtr. Jointed to each other by M.S Channel horizontally and also jointed to each other by means of 05 No. M.S Strip 50x6 mm of size 150 mm long each by welding at actual distance interval as per norms. And grouting in block of 300x300x700 completely providing 02 no. cable clamps also and eathing by G.I strip 50x6 mm size with the earth mat of switchyard both side of legs and provideing clamps , post/ pin insulator for holding cable. (All the materials will be arranged by the contractor such that clamps nut bolts and civil materials except M.S channel.)
Neutral stand Fabrication and grouting of M.S Channel 125x65 mm L shape & in proper size and allignment to provide support for the two separate earthing strips for pwer T/F neutral including supply & fixing of two No.Flexible copper bonds for neutral earthing. (All the materials will be arranged by the contractor such that clamps nut bolts and civil materials except M.S channel.)
33 KV Bay Bus Bar & Stringing. Stringing of 33KV Bay Bus Bar by using and laying of ACSR Dog Conductor including making Vertical/Horizontal (Y-shape) jumper connection through PG clamps , copper L piece and connector and connecting all the equipments ( Bus isolator, P.I. , C.T. , VCB, L.A & T/F) with each other through connecting clamps. (All the material will be supplied by the contractor)
Construction of 11 KV Double pole Erection & Grouting of 2 Nos 11Mtr STP support for making DP structure Including fabrication, Fixing of MS Channel, M.S. angle, Disc Insulators/ Pin Insulators etc. The work Includes suply and fixing of necessary clamp with nut, bolts and washers. complete in all respect. (All the material will be supplied by the contractor except steel section)
Provding, fixing and mounting of following equipments (All the material will be supplied by the contractor)
11 KV TPMO switch with fixing clamps.
11 KV Fuse set with fixing clamps
Grouting of following structure by digging of pit 1.83 Mtr deep for 11 Mtr STP,with 1:4:8 Ratio cement, sand & first class brickballast0.285 cu mtr for 11 mtr STP, plinthing 0.3 Mtr above G/L and proper plastering.
Providing and fixing of earth rod for earthing of support by G.I. Wire 6 SWG as per norms. (All material will be arranged by the contractor Like earth rod and 6 swg wire)
Painting of Structure Painting of 11 Mtr ST Pole with one coat of ready mixed primer and 2 coats of AL.Paint of good quality including cost of material, Labour and T&P complete in all respect.
Nozeling and grouting of stay set. (All the civil material and stay set will be arranged by the contractor excluding Stay wire)
Supply & Laying of 6x2.5 sq.mm. Sq. control cable from power T/F to controle board in the ground as per RESPO Norm with proper connection VCB, CT & Control Pannel with T/F to battery and battrey charger, Bucholz Relay, low higher and winding temperture protection alarm etc with including all the civil material. (All the material will be supplied by the contractor)
Supply & Laying of 4x2.5 sq.mm. Sq. control cable from power T/F to controle board in the ground as per RESPO Norm with proper connection VCB, CT & Control Pannel with T/F to battery and battrey charger, Bucholz Relay, low higher and winding temperture protection alarm etc with including all the civil material. (All the material will be supplied by the contractor)
Supply & Laying of 2x2.5 sq.mm. Sq. control cable from power T/F to controle board in the ground as per RESPO Norm with proper connection VCB, CT & Control Pannel with T/F to battery and battrey charger, Bucholz Relay, low higher and winding temperture protection alarm etc with including all the civil material. (All the material will be supplied by the contractor)
Special Earthing by way of boring and lowering of "B" class G.I. pipe 50 mm Dia 20mtr long from ground upto the water level and it will be connected to the G.S. strip 50X6 mm ( Providing & laying of G.S. strip including cutting, welding, bending etc.) for equipments(L.A,T/F,C.T., VCB.etc). The earth strip will be welded to the G.I. Pipe. The work also includes Cap & Clamps for pouring water, the cost of all material with all labour & T&P etc. Complete in all respect. (All the material will be supplied by the contractor)
Commissioning of 10 MVA T/F and its eqipments installed in switchyards and 11 KV Incoming and Outgoing Pannels complete in all respect upto energising
Construction of cable trench of 200 mm wide and 300 mm deep with MS strip at a distance of 1mtr. With brick work 1:4:8 in foundation 12 mm thick plaster of 1:4 cement coarse sand for finishing along with MS strip. (All the material will be supplied by the contractor)
Construction of trench cover of 600 mm long and 75 mm thick for cable trench Including cost of material, labour and T&P. (All the material will be supplied by the contractor)
Painting of Sub Station Structures (Old+New) with one coat of ready mixed primer and 2 coats of AL.Paint of good quality including cost of material, Labour and T&P complete in all respect.
Hosting of 11 KV Cable on existing/erected support with provision of MS Pipe 150 mm dia 3 mtr long suitable for 3x185 sq mm cable fixing of proper support and its clamping , providing long barral lugs 6 nos and P.G. Clamps & "Y" shape jumpering properly and 02 nos. supporting angle 65X65X6, 2800 mm as per RESSPO Norms. (All material will be supplied by the contractor like MS Pipe , P.G. Clamps, Al. Lug And Supporting Angle 65X65X6, 2800 mm).
Digging and locating the earth mat and outdoor Structures earthing by M.S. G.I Flat. 50X6 mm the job include cutting, bending. (All the material will be supplied by the contractor.)
Fixing and making Bus Bar connection in between I/C and O/G switchgears after cleaning and tapping with H.T. tape, Empire tape and PVC tape properly providing and fixing of 6mm thick bakelite seperators and plugging of all opening and holes with plastic compound. complete work including cost of all material Strictly to the satisfaction of site incharge.
M/S INDIA ELECTRICALS
M/s Shukla Enterprises
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .