Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.5 LAccepted-AOC | ₹4.5 L | L1 | Accepted-AOC L1 |
| 2 | L2₹4.5 L+₹2,011.90 (0.45%)Rejected-Finance | ₹4.5 L+₹2,011.90 (0.45%) | L2 | Rejected-Finance L2 |
| 3 | L3₹4.7 L+₹24,136.90 (5.40%)Rejected-Finance | ₹4.7 L+₹24,136.90 (5.40%) | L3 | Rejected-Finance L3 |
| Sl No | Description | Qty | Unit | Parth Electricals L2 | EXCEL ELECTRICALS L1 | HARBHAJAN ELECTRIC WORKS L3 |
|---|---|---|---|---|---|---|
| 1.00Wiring and Switchboards | ||||||
| 1.01 | Lights (Primary) and Fans point
Supply, installation, testing and commissioning (SITC) of wiring for tube lights, ceiling fans and exhaust fan point from respective switchboards, using 2 x 1.5 sq mm and 1.0 sq mm, 1100 Volts grade PVC insulated single core multistranded unsheathed copper FRLSH wires, including main circuit wiring from the MCB DB box to respective switchboard in suitable dia medium duty MS conduit with required accessories like bends, tees, junction boxes etc., in partly concealed/ partly surface manner (as the case may be) and making good the chases with cement plaster of suitable thickness, merging with adjoining area. The surface shall be finished by skilled persons for getting a smooth and merging surface.
Rate shall include for provision of modular type 10 Amp Switches with 6 Amp Sockets on switchboards (as mentioned above) on factory fabricated GI box (of same Make, as switches plate) and required size mounting plate fixed on respective approved company make boxes concealed in wall. All the fan points need to be terminated on a 3-terminal ceiling rose on a junction box. All tube light points need to be terminated with providing a tee-cover.
Necessary circuit wiring from D.B. upto the switch board for above items rate shall be done with (2 x 2.5 and 1 x 1.5) 1100 Volts grade PVC insulated single core multistranded unsheathed copper FRLSH wires.
Final connections also shall be made with flexible wires (of suitable rating) etc. Load on each circuit shall not be more than 800 Watts. Use blank plates on switchboards wherever required. | 89 | Nos | 1,525 ₹1,60,155.5 Lowest | 1,530 ₹1,60,680.6 | 1,550 ₹1,62,781 |
| 1.02 | Lights (Secondary) Point
Same as Item at S.N. 1.01 above, but looped from primary light point, and controlled through same 10 Amp switch of the switchboard. | 14 | Nos | 760 ₹12,555.2 Lowest | 765 ₹12,637.8 | 785 ₹12,968.2 |
| 1.03 | Set of two 6 Amp Plug-point (Primary)
SITC of (a pair) independent two 3-pin 6 Amp modular socket controlled by two 10 Amp modular switch housed in metal GI box and modular plate (both of same Make) of suitable size and wired using 2 x 2.5 + 1.5 sq. mm 1100 Volts grade PVC insulated single core multistranded unsheathed copper FRLSH wire, from mains MCB DB laid through recessed medium duty MS conduit pipe complete with all accessories or on surface, as per site requirement as directed by Bank's Engineer.
Light & fan switchboard, as per Item 1.01, and Set of two 6 Amp Plug-points, as per Item 1.02, shall be on same main circuit. | 19 | Nos | 1,690 ₹37,889.8 Lowest | 1,695 ₹38,001.9 | 1,720 ₹38,562.4 |
| 1.04 | Set of two 6 Amp Plug-point (Secondary)
SITC of (a pair) independent two 3-pin 6 Amp modular socket controlled by two 10 Amp modular switch housed in metal GI box and modular plate (both of same Make) of suitable size and wired using 2 x 2.5 + 1.5 sq. mm 1100 Volts grade PVC insulated single core multistranded unsheathed copper FRLSH wires, looped from nearest primary point (as per S.N. 1.02) laid through recessed MS medium duty conduit pipe complete with all accessories or on surface, as per site requirement as directed by Bank's Engineer. | 19 | Nos | 1,690 ₹37,889.8 Lowest | 1,695 ₹38,001.9 | 1,720 ₹38,562.4 |
| 1.05 | Power Plug-point 16 Amp (Primary)
SITC of independent 6/16 Amp modular socket controlled by 16 Amp modular switch housed in metal GI box and modular plate (both of same Make) of suitable size and wired using 2 x 2.5 + 1.5 sq. mm 1100 Volts grade PVC insulated single core multistranded unsheathed copper FRLSH wires, from mains MCB DB laid through recessed MS medium duty conduit pipe complete with all accessories or on surface, as per site requirement as directed by Bank's Engineer. | 5 | Nos | 4,240 ₹25,016 Lowest | 4,250 ₹25,075 | 4,350 ₹25,665 |
| 1.06 | Power Plug-point 16 Amp (Secondary)
SITC of independent 6/16 Amp modular socket controlled by 16 Amp modular switch housed in metal GI box and modular plate (both of same Make) of suitable size and wired using 2 x 2.5 + 1.5 sq. mm 1100 Volts grade PVC insulated single core multistranded unsheathed copper FRLSH wires, looped from primary power plug-point laid through recessed MS medium duty conduit pipe complete with all accessories or on surface, as per site requirement as directed by Bank's Engineer. | 4 | Nos | 3,385 ₹15,977.2 | 3,390 ₹16,000.8 | 3,350 ₹15,812 Lowest |
| 1.07 | Plug-point 6 Amp
SITC of one 3-pin 6 Amp modular socket controlled by a 10 Amp modular switch, latter housed in metal GI box (both of same Make) and modular plate of suitable size. The wiring to be done using 2 x 2.5 + 1.5 sq. mm PVC insulated single core multistranded unsheathed copper FRLSH wires, extended through switchboard as per S.N. Item 1.01 above, laid through recessed medium duty MS conduit pipe complete with all accessories, or on surface as per site requirement as directed by Bank's Engineer. The socket to be provided at certain height on the wall, while control switch to be provided in the same switchboard as per S.N. Item 1.01 | 10 | Nos | 1,690 ₹19,942 Lowest | 1,695 ₹20,001 | 1,725 ₹20,355 |
| 1.08 | Regulator
Fan regulator: -Supply and fixing of 2 module 4-step electronic regulators 100 watt for BLDC ceiling fans on the existing switch boards of Item No. 1.01 | 35 | Nos | 630 ₹26,019 Lowest | 636 ₹26,266.8 | 650 ₹26,845 |
| 2.00MCB Distribution System | ||||||
Tender Value
₹5.1 L
Closing Date
27 Aug 2026, 2:00 pmClosed
Regional Director
Reserve Bank of India, Estate Department, New Delhi.
e-tender for Electrical Renovation Work at Basement Area of Main Office Building, New Delhi
2026_RBI_283028_1
DEL.ESTT.ADM.No.S749 2026-2027
Limited
Electrical Works
Works
120 days
6, Sansad Marg, RBI
Please refer tender documents.
2 documents required · 2 mandatory
₹0
Exempted
Reserve Bank of India, 1st Floor, Estate Departmen
4 Sept 2026
6 Jul 2026
28 Aug 2026
6 Jul 2026
27 Aug 2026
3 Aug 2026
3 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Wiring and Switchboards | |||||
| 1.01 | Lights (Primary) and Fans point
Supply, installation, testing and commissioning (SITC) of wiring for tube lights, ceiling fans and exhaust fan point from respective switchboards, using 2 x 1.5 sq mm and 1.0 sq mm, 1100 Volts grade PVC insulated single core multistranded unsheathed copper FRLSH wires, including main circuit wiring from the MCB DB box to respective switchboard in suitable dia medium duty MS conduit with required accessories like bends, tees, junction boxes etc., in partly concealed/ partly surface manner (as the case may be) and making good the chases with cement plaster of suitable thickness, merging with adjoining area. The surface shall be finished by skilled persons for getting a smooth and merging surface.
Rate shall include for provision of modular type 10 Amp Switches with 6 Amp Sockets on switchboards (as mentioned above) on factory fabricated GI box (of same Make, as switches plate) and required size mounting plate fixed on respective approved company make boxes concealed in wall. All the fan points need to be terminated on a 3-terminal ceiling rose on a junction box. All tube light points need to be terminated with providing a tee-cover.
Necessary circuit wiring from D.B. upto the switch board for above items rate shall be done with (2 x 2.5 and 1 x 1.5) 1100 Volts grade PVC insulated single core multistranded unsheathed copper FRLSH wires.
Final connections also shall be made with flexible wires (of suitable rating) etc. Load on each circuit shall not be more than 800 Watts. Use blank plates on switchboards wherever required. | - | Nos | - | - |
| 1.02 | Lights (Secondary) Point
Same as Item at S.N. 1.01 above, but looped from primary light point, and controlled through same 10 Amp switch of the switchboard. | - | Nos | - | - |
| 1.03 | Set of two 6 Amp Plug-point (Primary)
SITC of (a pair) independent two 3-pin 6 Amp modular socket controlled by two 10 Amp modular switch housed in metal GI box and modular plate (both of same Make) of suitable size and wired using 2 x 2.5 + 1.5 sq. mm 1100 Volts grade PVC insulated single core multistranded unsheathed copper FRLSH wire, from mains MCB DB laid through recessed medium duty MS conduit pipe complete with all accessories or on surface, as per site requirement as directed by Bank's Engineer.
Light & fan switchboard, as per Item 1.01, and Set of two 6 Amp Plug-points, as per Item 1.02, shall be on same main circuit. | - | Nos | 100 | - |
| 1.04 | Set of two 6 Amp Plug-point (Secondary)
SITC of (a pair) independent two 3-pin 6 Amp modular socket controlled by two 10 Amp modular switch housed in metal GI box and modular plate (both of same Make) of suitable size and wired using 2 x 2.5 + 1.5 sq. mm 1100 Volts grade PVC insulated single core multistranded unsheathed copper FRLSH wires, looped from nearest primary point (as per S.N. 1.02) laid through recessed MS medium duty conduit pipe complete with all accessories or on surface, as per site requirement as directed by Bank's Engineer. | - | Nos | 53 | - |
| 1.05 | Power Plug-point 16 Amp (Primary)
SITC of independent 6/16 Amp modular socket controlled by 16 Amp modular switch housed in metal GI box and modular plate (both of same Make) of suitable size and wired using 2 x 2.5 + 1.5 sq. mm 1100 Volts grade PVC insulated single core multistranded unsheathed copper FRLSH wires, from mains MCB DB laid through recessed MS medium duty conduit pipe complete with all accessories or on surface, as per site requirement as directed by Bank's Engineer. | - | Nos | 10 | - |
| 1.06 | Power Plug-point 16 Amp (Secondary)
SITC of independent 6/16 Amp modular socket controlled by 16 Amp modular switch housed in metal GI box and modular plate (both of same Make) of suitable size and wired using 2 x 2.5 + 1.5 sq. mm 1100 Volts grade PVC insulated single core multistranded unsheathed copper FRLSH wires, looped from primary power plug-point laid through recessed MS medium duty conduit pipe complete with all accessories or on surface, as per site requirement as directed by Bank's Engineer. | - | Nos | 11 | - |
| 1.07 | Plug-point 6 Amp
SITC of one 3-pin 6 Amp modular socket controlled by a 10 Amp modular switch, latter housed in metal GI box (both of same Make) and modular plate of suitable size. The wiring to be done using 2 x 2.5 + 1.5 sq. mm PVC insulated single core multistranded unsheathed copper FRLSH wires, extended through switchboard as per S.N. Item 1.01 above, laid through recessed medium duty MS conduit pipe complete with all accessories, or on surface as per site requirement as directed by Bank's Engineer. The socket to be provided at certain height on the wall, while control switch to be provided in the same switchboard as per S.N. Item 1.01 | - | Nos | 10 | - |
| 1.08 | Regulator
Fan regulator: -Supply and fixing of 2 module 4-step electronic regulators 100 watt for BLDC ceiling fans on the existing switch boards of Item No. 1.01 | - | Nos | 11 | - |
| 2MCB Distribution System | |||||
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.19 MB
TenderDocument.pdf
Tender Documents • 0.54 MB
BOQ_330192.xls
BOQ • 0.40 MB
tenderextension.pdf
PDF • 0.07 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .