Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.6 CrAccepted-AOC 25 A RR SAMY LANE KATTOOR COIMBATORE 641009 | COIMBATORE | COIMBATORE | TAMIL NADU | 641009 | ₹10.6 Cr Quoted ₹11.1 Cr | L1 | Accepted-AOC ACCEPTED AS L1 CONTRACTOR |
| 2 | L2₹11.5 CrRejected-AOC 2 209 1 NANGAVARAM ROAD PERUGAMANI POST SRIRANGAM TALUK TIRUCHIRAPPALLI | TIRUCHIRAPPALLI | TAMIL NADU | 620001 | ₹11.5 Cr | L2 | Rejected-AOC REJECTED SINCE RATE QUOTED ARE HIGHER THAN L1 |
| 3 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Others-DOCUMENT NOT FULFILLED |
| Sl No | Description | Qty | Unit | rv electricals L1 | GANAPATHY ELECTRICALS L2 |
|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing and commissioning of 11kV, 800A, 25KA OUTDOOR TYPE Single Panel Vaccum Circuit Breaker
1) Vaccum Circuit Breaker: (1 no)
a) 11KV, 25kA Horizontal Draw Out type VCB fitted with Manual / Motor Operated spring charged mechanism with 230V AC Motor & Motor Control Switch, Mechanical ON / OFF indicator Operation Counter, Automatic safety shutters & push button.-1no (800A)
b) Shunt trip coil - 110V DC
c) Closing coil - 110V DC
d) Spare auxillary contact - 6 NO + 6 NC
e) Antipumping Feature - 110V DC
f) Power pack - 230VAC/110V DC
2) Potential Transformer: (1 no)
a) Single Phase, Resin cast, Dry type, Fixed type potential transformer with one set of HT and LT HRC fuses and one no. Neutral Link - (11KV/√3) / (110V/√3) - 3 nos
b) Secondary 1: for meter - Cl-0.2, 50VA burden
3) Current Transformer:
a) Single phase, Resin Cast, Dry Type Current Transformer 100-50/5-5Amps dual core
Core 1: for meter - Cl-0.5, 7.5VA burden
Core 2: Accuracy class 5P10,7.5VA Burden for protection | 1 | No | 6,30,000 ₹6.3 L | 6,54,000 ₹6.5 L |
| 1.014) Metering: a) Digital Voltmeter with inbuilt selector switch CI. 0.5, 110V AC - 1 no b) Digital Multifunction meter with Inbuilt Selector Switch CI.0.5 5A,110V AC (PT) & 110V AC Aux c) Digital Trivector meter - 1 no d) Digital powerfactor meter - 1 no e) Digital Frequency meter - 1 no 5) Protection: Numerical Breaker Manager Relay MB 140C with 3O/C+1E/F Protection relay provided with In-Built Master trip relay,Trip Circuit Supervision Relay,AntiPumping Relay,PT fuse failure relay,DC supervision,Auxillary Relay for Transformer protection,Annunciation unit,In-Built Breaker Control Push buttons,Local and Remote Push buttons,In-built LED Indications etc., - 5A/110V DC 6) Indication/Alarm: Buzzer - 1 no 7) Control wiring with appropriate colors: a) Breaker Control Switch (Close-Neutral-Trip) - 110V/25A - 1 no b) Test Terminal block - 1 no 8) Busbar: a) Copper busbar with PVC sleeve - 11 kV,800A, 25kA/3Sec ( 1 set ) b) Earth bus - ( 1 set ) 9) Common for switchgear : Heater ON / OFF switch with filament type 80Watts space heater & thermostat , single phase switch with socket, Lamp for panel illumination with snap type door limit switch, Fuses / MCBs for AC / DC control - 1 set | |||||
| 1.0210) Enclosure : MS Sheet steel enclosure & installation suitable for Indoor - 1 set 11) Termination: a) Incoming (Excluding cable termination kits, lugs and glands) - Bottom b) Outgoing (Excluding cable termination kits, lugs and glands) - Bottom 12) Surge Protection: 9kV,10kA etc., complete complying with standard specification and as directed by the department officers. | |||||
| 2.00 | Supply, installation, testing and commissioning of 11kV, 800A, 25KA OUTDOOR TYPE Three Panel Vaccum Circuit Breaker
1) Vaccum Circuit Breaker: (3Nos) [Incoming -1No & Outgoing-2Nos]
a) 11KV, 25kA Horizontal Draw Out type VCB fitted with Manual / Motor Operated spring charged mechanism with 230V AC Motor & Motor Control Switch, Mechanical ON / OFF indicator Operation Counter, Automatic safety shutters & push button.-1no (800A)
b) Shunt trip coil - 110V DC
c) Closing coil - 110V DC
d) Spare auxillary contact - 6 NO + 6 NC
e) Antipumping Feature - 110V DC
f) Power pack - 230VAC/110V DC
2) Potential Transformer: (3 Nos)
a) Single Phase, Resin cast, Dry type, Fixed type potential transformer with one set of HT and LT HRC fuses and one no. Neutral Link - (11KV/√3) / (110V/√3) - 3 nos
b) Secondary 1: for meter - Cl-0.2, 50VA burden
3) Current Transformer:
a) Single phase, Resin Cast, Dry Type Current Transformer 100-50/5-5Amps dual core - 9 Nos
Core 1: for meter - Cl-0.5, 7.5VA burden
Core 2: Accuracy class 5P10,7.5VA Burden for protection | 1 | No | 15,22,500 ₹15.2 L | 15,80,500 ₹15.8 L |
| 2.014) Metering: a) Digital Voltmeter with inbuilt selector switch CI. 0.5, 110V AC - 1 no b) Digital Multifunction meter with Inbuilt Selector Switch CI.0.5 5A,110V AC (PT) & 110V AC Aux c) Digital Trivector meter - 1 no d) Digital powerfactor meter - 1 no e) Digital Frequency meter - 1 no 5) Protection: Numerical Breaker Manager Relay MB 140C with 3O/C+1E/F Protection relay provided with In-Built Master trip relay,Trip Circuit Supervision Relay,AntiPumping Relay,PT fuse failure relay,DC supervision,Auxillary Relay for Transformer protection,Annunciation unit,In-Built Breaker Control Push buttons,Local and Remote Push buttons,In-built LED Indications etc., - 5A/110V DC 6) Indication/Alarm: Buzzer - 1 no 7) Control wiring with appropriate colors: a) Breaker Control Switch (Close-Neutral-Trip) - 110V/25A - 1 no b) Test Terminal block - 1 no 8) Busbar: a) Copper busbar with PVC sleeve - 11kV,800A, 25kA/3Sec ( 1 set ) b) Earth bus - ( 1 set ) 9) Common for switchgear : Heater ON / OFF switch with filament type 80Watts space heater & thermostat , single phase switch with socket, Lamp for panel illumination with snap type door limit switch, Fuses / MCBs for AC / DC control - 1 set | |||||
| 2.0310) Enclosure : MS Sheet steel enclosure & installation suitable for Indoor - 1 set 11) Termination: a) Incoming (Excluding cable termination kits, lugs and glands) - Bottom b) Outgoing (Excluding cable termination kits, lugs and glands) - Bottom 12) Surge Protection: 9kV,10kA - 3 nos 13) Mechanical Interlock and Key: Castell interlock and key ( 2 Base + 1 Key) - 1 set etc., complete complying with standard specification and as directed by the department officers. | |||||
| 3.00 | Supply and clamping of 11KV 300 sq.mm. 3 core HT XLPE 11KV cable on post or on wall with MS Clamps. | 260 | Mtrs | 2,193 ₹5.7 L | 2,275.92 ₹5.9 L |
| 4.00 | Supply and providing cable Outdoor end termination suitable for 11KV 3 core 240-300 sqmm XLPE HT UG cable with necessary outdoor type heat shrinkable Termination kit and accessories complete. | 7 | Nos | 23,597 ₹1.7 L | 24,495.57 ₹1.7 L |
| 5.00 | Supply and laying of 2C x 2.5 Sq mm XLPE armoured LTUG Cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 mt. Layer of sand and covering the cable completely with bricks and sand and refilling the earth to make good. | 60 | Mtrs | 974 ₹58,440 | 1,011.52 ₹60,691.20 |
| 6.00 | Supply and clamping of 2C x 2.5 Sq mm XLPE LTUG armoured cable on post or on wall with MS clamps. | 80 | Mtrs | 463 ₹37,040 | 480.69 ₹38,455.20 |
Tender Value
Refer Docs
EMD Value
₹5.5 L
Closing Date
17 Sept 2025, 3:00 pmClosed
SUPERINTENDING ENGINEER
O/o THE SUPERINTENDING ENGINEER PWD BUILDINGS CONSTRUCTION AND MAINTENANCE CIRCLE COIMBATORE
Provision for Escalator, Lift, Generator Arrangements and HT Transformer works in the proposed Grand Library and Science Centre in Coimbatore District.
2025_PWD_599212_1
33BCMCBE26082025
Open Tender
Electrical Works
GANDHIPURAM
Please refer Tender documents.
14 documents required · 14 mandatory
₹0
₹5.5 L
21 Nov 2025
2 Sept 2025
17 Sept 2025
2 Sept 2025
17 Sept 2025
2 Sept 2025
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.37 MB
BOQ_716272.xls
BOQ • 0.45 MB
Download all tender documents and submit your bid