Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.9 LAccepted-AOC | L1 | Accepted-AOC AOC | |
| 2 | L2₹31.6 L+₹10.2 L (47.6%)Rejected-Finance KG 115 SABIRA MANZIL HBR 2ND STAGE VENKATESH PURAM BANGALORE 560 045 | BENGALURU URBAN | KARNATAKA | 560045 | L2 | Rejected-Finance Not L1 | |
| 3 | Rejected-Technical | - | Rejected-Technical Due to ban imposed on account of revocation in other works pertains to this office. |
Tender Value
Refer Docs
EMD Value
₹39,200
Closing Date
6 Nov 2023, 6:00 pmClosed
GE(South) Bangalore
GE(South) Bangalore
REPAIR / MAINT OF LT PANELS, MCCBs AND CONNECTED ITEM FOR LT NETWORK UNDER GE(SOUTH) BANGALORE
2023_MES_621628_1
8749/E8
Open Tender
Civil Works
Item Rate
180 days
Bangalore
As per tender document
6 documents required · 6 mandatory
₹500
GE(South) Bangalore
₹39,200
Yes
29 Dec 2023
4 Oct 2023
8 Nov 2023
4 Oct 2023
6 Nov 2023
18 Oct 2023
Amount
Dismanling old unserviceable of MCB/MCCB any type any capacity
S&F of MCCB 3 pole 415 volt fixed type of capacity 400 Amps with breaking capacity 36 KA
S&F of MCCB 3 pole 415 volt fixed type of capacity 250 Amps with breaking capacity 36 KA
S&F of MCCB 3 pole 415 volt fixed type of capacity 200 Amps with breaking capacity 36 KA
S&F of MCCB 3 pole 415 volt fixed type of capacity 160 Amps with breaking capacity 36KA
S&F of MCCB 3 pole 415 volt fixed type of capacity 125 Amps with breaking capacity 16 KA
S&F of MCCB 3 pole 415 volt fixed type of capacity 100 Amps with breaking capacity 16 KA
S&F of MCCB 3 pole 415 volt fixed type of capacity 63 Amps with breaking capacity 16 KA
S&F MCB TPN 40 Amp capacity three phase 415 volt 50 Hz
S&F MCB TPN 63 Amp capacity three phase 415 volt 50 Hz
M&L for repairing of LT Panel by fixing broken hinges welding , greasing , internal MCCB/Bus bar cubicle hinges repairing , tightining of earthing including new hinges , locks welding /brazing , greasing if reqd for complete LT Panel off sizes complete all as dpeciefied and directed by Engr in Charge.
M&L for fixing in repair locking arrangement of external doors of LT Panel by providing proper lock proper lock mechanism , including replacement of lock if reqd complete all as specified and directed by Engr in Charge .
M&L for Preparaton of oldsurfaces for painting of existing LT Panel/feeder pillar size up to 1.7x1.2x0.4mtr by peeling existing paint layer and dust , cleaning of surface , and applying to coats of sytnhetic enamel paint of colour as decided over one coat of red oxide primer on all outdoor sides of LT panel including inner side of gates complete all as specified and directed by Engr in Charge.
Fabricate, Supply, testing, commissioning for Feeder pillar box made of Aluminium bus bar of 400A capacity for one incoming cable and 160 MCCB as incomer and outgoing to bus bar 4 out going cable housing in sheet metal enclosure of MS sheet 3.15mm thick, CRCA sheet, angle iron frame of size 40x40x6mm including locking arrangement & painting with two coats of powder coated paint over a coats of metal primer, suitable foundation & platform etc complete all as specified and directed
Dismantling of old unserviceable LT Panel board from Site .
Supply and fixing of LT Panel board suitable for indoor installation , fabricated out of 3.0mm thick CRCA sheet , CPRI Approved LT Panel board of size not less than 900x900x600mm with cable entry from bottom , dust and vermin proof by providing suitable gaskets , double door type , with locking arrangement , mounted on angle iron frame of size not less than 40x40x6mm at height by 450mm above ground level and 300mm below ground level including grouting in PCC 1:4:8 0.5mtr depth and 300mm width including following accessories:- Location :- Paint Shop
Incoming
(i) MCCB 200 amps,25kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval 25mm size -1set
Outgoing
(i) MCCB 100 Amps 25Ka,415 volt 50Hz, 4P - 03No.
(ii) MCB TPN 32 Amps 415 Volt,50Hz, - 06 Nos.
(iii) MCB SP 20 Amps 230 Volt,50Hz, - 12 Nos.
(iv) Star delta starter 3 phase 415 volt ML 3MF inbuilt single phase preventor for 30 HP Motor - 02 Nos
(v) DOL starter 3 phase 415 volt inbuilt single phase preventor for 05 HP Motor - 02 Nos
All as per Item No -16 but size not less than 600x600x400mm following accessoris Location :- 515 Mil wing OTM pump House
Incoming
(i) MCCB 63 amps,16kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(ii) MCB TPN 32 Amps 415 Volt,50Hz, - 03 Nos.
(ii) MCB SP 20 Amps 230 Volt,50Hz, - 01 Nos.
(iii) DOL starter 3 phase 415 volt inbuilt single phase preventor for 05 HP Motor - 01 Nos
(iv) DOL starter 3 phase 415 volt inbuilt single phase preventor for 02 HP Motor - 01 Nos
All as per Item No -16 but out door canopy type 3.15mm thick sheet size not less than 600x600x400mm following accessoris Location SHO main Gate
Incoming
(i) MCCB 200 amps,16kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(i) MCCB 100 Amps 25KA,415 volt 50Hz, 4P - 03No.
All as per Item No -16 but out door canopy type 3.15mm thick sheete size not less than 600x600x400mm following accessoris Location FAFA accn
Incoming
(i) MCCB 200 amps,16kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(i) MCCB 100 Amps 25KA,415 volt 50Hz, 4P - 04No.
(ii) MCB SP 20 Amps 230 Volt,50Hz, - 01 Nos.
All as per Item No -16 indoor panel board but size not less than 600x600x400mm following accessoris Location:- QAD
Incoming
(i) MCCB 400 amps,25kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(i) MCCB 200 Amps 25KA,415 volt 50Hz, 4P - 03No.
(ii) MCB SP 20 Amps 230 Volt,50Hz, - 01 Nos.
All as per Item No -16 indoor panle board but size not less than 600x600x400mm following accessoris Location :- MED
Incoming
(i) MCCB 400 amps,25kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(i) MCCB 200 Amps 25KA,415 volt 50Hz, 4P - 02No.
(ii) MCCB 100 Amps 25KA,415 volt 50Hz, 4P - 02No.
(iii) MCCB 63 Amps 25KA,415 volt 50Hz, 4P - 02No.
All as per Item No -16 indoor panle board but size not less than 600x600x400mm grouting in wall after complete work cement , putty and paint work done as per exsiting colour with following accessoris Location :- Adm Block
Incoming
(i) MCCB 200 amps,25kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(i) MCB TPN 32 Amps 415 Volt,50Hz, - 03 Nos.
(ii) MCB SP up to 32 Amps - 18No.
All as per Item No -16 indoor panle board but size not less than 600x600x400mm grouting in wall after complete work cement , putty and paint work done as per exsiting colour with following accessoris Location :- SMD Bldg
Incoming
(i) MCCB 200 amps,25kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(i) Onload front handle change over switch 100Amps 415 volt 50 Hz 4P Make- Indoasian/havells/Legrand -01 Nos
(i) MCB TPN 63 Amps 415 Volt,50Hz, - 06 Nos.
(ii) MCB SPN 40 Amps - 02 No.
All as per Item No -16 but out door canopy type 3.15mm thick sheet size not less than 600x600x400mm following accessoris Location:- 515 Mil wing MD accn
Incoming
(i) MCCB 100 amps,25kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(i) MCCB 63 Amps 25KA,415 volt 50Hz, 4P - 03No.
(ii) MCB SP 20 Amps 230 Volt,50Hz, - 01 Nos.
All as per Item No -16 indoor panel board but size not less than 600x600x400mm following accessoris Location:- CED
Incoming
(i) MCCB 630 amps,35kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(i) MCCB 400 Amps 25KA,415 volt 50Hz, 4P - 02No.
(ii) MCB SP 20 Amps 230 Volt,50Hz, - 01 Nos.
All as per Item No -16 in door panel board but size not less than 600x600x300mm following accessoris Location:- P-120 OTM
Incoming
(i) MCCB 100 amps,35kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(ii) MCB SP up to 32 Amps 230 Volt,50Hz, - 24 Nos.
All as per Item No -16 indoor panel board but size not less than 600x600x400mm following accessoris Location:- FAD Bay 1 & 5
Incoming
(i) MCCB 400 amps,25kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(i) MCCB 100 Amps 25KA,415 volt 50Hz, 4P - 03No.
(i) MCCB 63Amps 25KA,415 volt 50Hz, 4P - 03No.
All as per Item No -16 in door panel board but size not less than 600x600x300mm following accessoris Location:- P- 56 ASC FOL Depot
Incoming
(i) MCCB 100 amps,35kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(ii) MCB SP up to 32 Amps 230 Volt,50Hz, - 24 Nos.
All as per Item No -16 but size not less than 600x600x400mm following accessoris Location :- APS pump House
Incoming
(i) MCCB 63 amps,16kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(ii) MCB SPN 32 Amps 415 Volt,50Hz, - 02 Nos.
(ii) MCB SP 20 Amps 230 Volt,50Hz, - 02 Nos.
(iii) DOL starter 3 phase 415 volt inbuilt single phase preventor for 03 HP Motor - 01 Nos
(iv) DOL starter 3 phase 415 volt inbuilt single phase preventor for 03 HP Motor - 01 Nos
All as per Item No -16 indoor panle board but size not less than 600x600x400mm grouting in wall after complete work cement , putty and paint work done as per exsiting colour with following accessoris Location :- Signal Centre
Incoming
(i) MCCB 250 amps,25kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(i) Onload front handle change over switch 200Amps 415 volt 50 Hz 4P -02 Nos
(ii) MCCB 200 Amps 25KA,415 volt 50Hz, 4P - 02No.
(iii) MCCB 100 Amps 25KA,415 volt 50Hz, 4P - 01No.
(iv) MCB SPN 40 Amps - 02 No.
All as per Item No -16 but out door canopy type 3.15mm size not less than 600x600x400mm following accessoris Location:- Baird BK
Incoming
(i) MCCB 400 amps,35kA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(i) MCCB 250 Amps 25KA,415 volt 50Hz, 4P - 01No.
(ii) MCCB 200 Amps 25KA,415 volt 50Hz, 4P - 01No.
(iii) MCCB 100 Amps 25KA,415 volt 50Hz, 4P - 01No.
All as per Item No -16 but out door canopy type 3.15mmsize not less than 600x600x400mm following accessoris Location:- Baird BK
Incoming
(i) MCCB 315 amps, 35KA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(i) MCCB 250 Amps 25KA,415 volt 50Hz, 4P - 01No.
(ii) MCCB 200 Amps 25KA,415 volt 50Hz, 4P - 02No.
(iii) MCCB 100 Amps 25KA,415 volt 50Hz, 4P - 01No.
All as per Item No -16 but out door canopy type 3.15mmt size not less than 600x600x400mm following accessoris Location:- ARMY SCHOOL
Incoming
(i) MCCB 315 amps, 35KA, 415 Volt,50Hz, 4P -1No.
(iv) LED cluster indication lamp(R Y B) set of 3-1set
Busbar : - Aluminium busbar 15/25mm 3 phase 4 wire of 200 to 300 Amps supported with ebonite insulation at 20cm interval -1set
Outgoing
(i) MCCB 250 Amps 25KA,415 volt 50Hz, 4P - 01No.
(ii) MCCB 200 Amps 25KA,415 volt 50Hz, 4P - 02No.
Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the earth plate at a depth of not less than 1.5 mtr below ground level connected to galvanized iron strip 25 x 4 mm as earthing lead by means of bolts, nuts and washers made out of GI/steel earth strip protected by GI light grade pipe of 40 mm dia and connecting to main panel board/switch board/control board all shown in electrical plate No 3 of SSR Pt I incl PCC chambers in 1:2:4 and RCC cover slab with 8mm dia MS bars reinforced at 10 cm center to center both ways incl earth work like excavation, returning filling back disposal etc complete.
Excavation in trenches in soft/loose soil not exceeding 1.5 M wide and not exceeding 1.5 M in depth for laying of UG cables and LT Panel board foundation etc and getting out.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cms in any type of soil.
Removing excavated soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 M above the starting point all as directed.
M&L for sand cushioning in trenches for bricks of u/g cable with coarse sand laid dry in trenches with uniform thickness.
Supply and lay burnt bricks of sub class 'B' laid dry across in trenches for cable protection all as specified and directed.
Supply, laying and testing cable XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium sonductor of size 10 Sqmm x 2 core including taking down unserviceable UG cable complete all as specified and directed.
All as per Item No 40 but of size 16 Sqmm x 4 Core
All as per Item No 40 but of size 50 Sqmm x 3.5 Core
All as per Item No 40 but of size 70 Sqmm x 3.5 Core
GS TRADERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .