Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.3 CrAdmitted-Finance MANIK COLONY OPP RAJA HOTEL AHILYABAI CHOWK KALYAN W 421 301 | KALYAN W | THANE | MAHARASHTRA | 421301 | ₹4.3 Cr | L1 | Admitted-Finance |
| 2 | L2₹4.8 CrAdmitted-Finance | ₹4.8 Cr | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | J D ELECTRIC WORKS L1 | sagarsai Enterprises L2 |
|---|---|---|---|---|---|
| 1.00Sub Estimate No.01 Providing Power Supply Infrastructure at Plot P‑32 in Taloja Industrial Area | |||||
| 2.00 | Item no.01 Hermetically Sealed transformer (SS-TR-HSL) 1.1 Supplying, installing, testing & commissioning 3 phase, 22/0.433 kV, 50 Hz., 630 kVA, Mineral oil immersed and naturally cooled outdoor type, Copper wound, without gas cushioning, hermetically Sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 45 degree by thermometer in oil and 50? by the resistance method in winding at full load rating, using type A winding insulation (kraft paper) with HV tapping (with off load tap changer) off load +5 to -10 in steps of 2.5%,having 7 number of tap positions with standard accessories complete with test certificate with losses below 1953 Watts at 50% load, 5565 Watts at 100% load as per IS:1180 (part 1) : 2014 with necessary permissions of Electrical Inspector, as per specification no SS- TR-HSL. | 4 | each | 14,00,000 ₹56 L | 12,50,680 ₹50.0 L |
| 3.00 | Item No.02Accessories 2.1 Supplying and erecting 22 kV outdoor type gang operated air break, triple pole switch 200 A capacity with 3 post pin type insulator per phase, mounted in horizontal or vertical position with necessary channels on provided cross arm with adequate length of "C" class G.I. pipe for operating handle erected on extended square shaft. The operating handle provided with lock and key at suitable height from ground level with necessary clamp. | 5 | Per Set | 22,000 ₹1.1 L | 24,000 ₹1.2 L |
| 4.00 | 2.2 Supplying and erecting, 22 kV outdoor type drop out fuse with insulator complete with fuse holders, fuse barrel with metal fitting, fuse element mounted on M.S. channel with working current of 15A capacity complete erected on provided cross arm. | 5 | Per Set | 13,000 ₹65,000 | 14,800 ₹74,000 |
| 5.00 | 2.3 Supplying and erecting fencing of section having size at least 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete with provided earthing as per specification no. SS-AS/FSG | 80 | each | 6,857 ₹5.5 L | 5,175 ₹4.1 L |
| 6.00 | 2.4 Supplying and erecting 50 x 50 x 6 mm angle iron as corner support 2.45m long fixed at the middle of the fencing frame and the other side inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminium paint complete. | 16 | each | 1,358 ₹21,728 | 2,000 ₹32,000 |
| 7.00 | 2.5 Supplying and erecting double leaf hinged door each 1500 mm in width x 2450 mm in height using B class GI pipe, hinges and angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation and painted complete as per specification no SS-AS/DLD | 4 | each | 19,632 ₹78,528 | 11,500 ₹46,000 |
| 8.00 | Item No.03 C.C. Foundation 3.1 Making Transformer plinth (1.5 x 1.5 x 1.5)m in size with necessary excavation in ground with 150mm thick M-10 PCC at the bottom and top and 250mm thick, burnt brick wall constructed at periphery and remaining hollow portion shall be filled with 40mm hard broken aggregate. External surface duly plastered by 12mm thick including watering etc. complete. | 4 | each | 14,302 ₹57,208 | 27,100 ₹1.1 L |
| 9.00 | 3.2 Making Cement concrete foundation including excavation (60 x 60)cm x deep 1/6 of pole length in 1:3:6 cement concrete 20 x 25 mm stone metal, 45cm x 45cm x 45cm/ 45cm dia. x 45cm height plinth duly plastered, with necessary curing and finishing complete. (for above 9m poles) | 50 | each | 5,000 ₹2.5 L | 1,850 ₹92,500 |
| 10.00 | Item No.04 Steel Poles (OH-PL) 4.1 Supplying and erecting rolled steel joist (girder) pole 152 x 152 mm (37.1 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ | 50 | Meter | 2,528 ₹1.3 L | 3,330 ₹1.7 L |
Updated dates
Tender Value
₹4.9 Cr
EMD Value
₹2.5 L
Closing Date
23 Mar 2026, 5:00 pmClosed
SE E and M Comm Mumbai
MIDC HQ office Udyog sarathi Andheri Mumbai 93
Taloja Industrial Area...Providing Power Supply Infrastructure, Pure water and effluent Pumping Machineries and allied work at Plot P-32 in Taloja Industrial Area.
2026_MIDC_1282375_1
MIDC/E and M/AMB/38022/79/2025-26
Open Tender
Electrical and Maintenance Works
365 days
Taloja Mahape
Please refer Tender documents.
2 documents required · 2 mandatory
₹30,680
₹2.5 L
24 Mar 2026
27 Feb 2026
24 Mar 2026
27 Feb 2026
23 Mar 2026
6 Mar 2026
27 Feb 2026 - 4 Mar 2026
Sub Estimate No.01 Providing Power Supply Infrastructure at Plot P‑32 in Taloja Industrial Area
Item no.01 Hermetically Sealed transformer (SS-TR-HSL) 1.1 Supplying, installing, testing & commissioning 3 phase, 22/0.433 kV, 50 Hz., 630 kVA, Mineral oil immersed and naturally cooled outdoor type, Copper wound, without gas cushioning, hermetically Sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 45 degree by thermometer in oil and 50? by the resistance method in winding at full load rating, using type A winding insulation (kraft paper) with HV tapping (with off load tap changer) off load +5 to -10 in steps of 2.5%,having 7 number of tap positions with standard accessories complete with test certificate with losses below 1953 Watts at 50% load, 5565 Watts at 100% load as per IS:1180 (part 1) : 2014 with necessary permissions of Electrical Inspector, as per specification no SS- TR-HSL.
Item No.02Accessories 2.1 Supplying and erecting 22 kV outdoor type gang operated air break, triple pole switch 200 A capacity with 3 post pin type insulator per phase, mounted in horizontal or vertical position with necessary channels on provided cross arm with adequate length of "C" class G.I. pipe for operating handle erected on extended square shaft. The operating handle provided with lock and key at suitable height from ground level with necessary clamp.
2.2 Supplying and erecting, 22 kV outdoor type drop out fuse with insulator complete with fuse holders, fuse barrel with metal fitting, fuse element mounted on M.S. channel with working current of 15A capacity complete erected on provided cross arm.
2.3 Supplying and erecting fencing of section having size at least 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete with provided earthing as per specification no. SS-AS/FSG
2.4 Supplying and erecting 50 x 50 x 6 mm angle iron as corner support 2.45m long fixed at the middle of the fencing frame and the other side inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminium paint complete.
2.5 Supplying and erecting double leaf hinged door each 1500 mm in width x 2450 mm in height using B class GI pipe, hinges and angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation and painted complete as per specification no SS-AS/DLD
Item No.03 C.C. Foundation 3.1 Making Transformer plinth (1.5 x 1.5 x 1.5)m in size with necessary excavation in ground with 150mm thick M-10 PCC at the bottom and top and 250mm thick, burnt brick wall constructed at periphery and remaining hollow portion shall be filled with 40mm hard broken aggregate. External surface duly plastered by 12mm thick including watering etc. complete.
3.2 Making Cement concrete foundation including excavation (60 x 60)cm x deep 1/6 of pole length in 1:3:6 cement concrete 20 x 25 mm stone metal, 45cm x 45cm x 45cm/ 45cm dia. x 45cm height plinth duly plastered, with necessary curing and finishing complete. (for above 9m poles)
Item No.04 Steel Poles (OH-PL) 4.1 Supplying and erecting rolled steel joist (girder) pole 152 x 152 mm (37.1 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ
Item No.05 Conductors (OH-CON) 5.1 Supplying and erecting ACSR conductor of size - 6/1-4.72 mm (Dog) complete. (394.00 kg/km) as per specification No. OH-CON/ACSR
Item No.06 Insulators (OH-INS) 6.1 Supplying and erecting porcelain disc type insulator 70KN with necessary hardware suitable for 22kV line, complete as per specification no. OH-INS/DI
6.2 Supplying and erecting porcelain pin type insulator with GI pin suitable for 22kV line , complete as per specification no. OH-INS/PN
6.3 Supplying and erecting distribution class, 22 kV thyrite type lightening arrester with nut bolts, on provided MS channel as per specification no. OH-INS/LA
Item No.07 Accessories 7.1 Supplying and erecting pole clamp made from 50x6mm MS flat for pole or pipe, post erected with 15mm bolts and nuts duly painted with one coat of red oxide and two coats of aluminium paint complete.
7.2 Supplying and erecting D type pole clamps, fabricated from 50x6mm MS flat with 15mm bolts and nuts fixed to steel tubular pole duly painted with one coat of red oxide and two coats of aluminium paint complete.
7.3 Supplying and erecting C type (half) clamps for pole made from 50x10mm flat for fixing cross arms by means of 15mm bolts and nuts painted with one coat of red oxide and two coats of aluminium paint complete.
Item No.08 HT Cables (CB-HT) 8.1 Supplying , erecting & terminating XLPE insulated, galvanised steel formed wire armoured (round) cable 22 kV(E), 3 x 300 sq. mm. aluminium conductor laid in provided trench / pipe as per specification no. CB-HT
Item no.09 Cable Enclosures (CB-CE) 9.1 Supplying & laying (including excavation) reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete.
9.2 Supplying & laying (including excavation) half round reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete.
Item No.10 HT SF6 Load Break Switch /VCB/RMU (SW-HTS) 10.1 Supplying, installing, testing and commissioning SF 6 insulated 22kV, 630A, 16kA/3sec, 4 way outdoor, extensible motorised SCADA compatible RMU, internal arc tested as per electric supply company specification consisting of 2 nos. feeder with 2 LBS and 2 nos. feeder with 2 VCB compliant to IEC 62271-100, 200 and 102 as per specification no. SW-HTS/RMU SCADA.
10.2 Supplying, installing, testing and commissioning SF 6 insulated 22kV, 630A, 16kA/3sec, 6 way outdoor, extensible motorised SCADA compatible RMU, internal arc tested as per electric supply company specification consisting of 2 nos. feeder with 2 LBS and 4 nos. feeder with 4 VCB compliant to IEC 62271-100, 200 and 102 as per specification no. SW-HTS/RMU SCADA.
Item No.11 Excavation for foundation in Hard murum and boulders including removing the excavated material upto a distance of 50 metres, beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift from 1.5 m to 3.0 m.) By Mechanical Means
Item No.12 DTC Metring with Box, single core L.T. XLPE cable ( 300 Sq.mm, 320 mtr. length) and other allied material for 630 KVA
Item No.15 Providing and laying Cast in situ/Ready Mix cement concrete in M15 of trap/ granite/quartzite/gneiss metal for foundation and bedding / steps including steel centering, formwork, laying/pumping, compacting, roughening them if special finish is to be provided, finishing uneven and honeycombed surface and curing etc. complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface, only. Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc. (Wooden centering will not be allowed.),with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Item No.16 Plate, Pipe type Earthing (EA-EP) 16.1 Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recording the results as per specification no. EA-EP
16.2 Supply, installing, and testing of maintenance free earthing comprising of electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity (min. 125kg) complete, and recording the results specification no. EA-MF
Item No.17 Accessories 17.1 Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required as per specification no EA-EP.
Item No.18 LT Cables (Aluminum) (CB-LT/AL) 18.1 Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3½ core 300 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Item No.19 Cable Joints & End Termination Kits (HT Cables) (CB-JT/HT) 19.1 Providing and erecting Heat shrinkable outdoor termination kit for 11 kV (UE)/ 22 kV ( E ) XLPE HT cable 3x240 to 400 sq. mm. with necessary material as per specification no. CB-JT/HT
19.2 Providing and erecting Heat shrinkable straight through joint kit for 11 kV (UE)/22 kV ( E ) XLPE HT cable 3x240 to 300 sq. mm. with necessary material as per specification no. CB-JT/HT
Item No.20 Providing and erecting Heat shrinkable Touch proof indoor termination kit for 11 KV(UE)/22 KV(E) XLPE HT cable 3 X240 to 400 sqmm with necessary materilas .
Item No.21 SITC of 6 way feeder pillar with ACB
Item No.22 Supplying and erecting Galvanizing Iron, work consisting of Various sections of iron, Plates, Chequered Plates, Rods, Bars, GI square / round pipes, etc. for fabrication purposes complete with bending, cutting, drilling and welding complete erected at the position with necessary materials as per directions by the authority.
Sub Estimate No.02 Providing pure water Pumping Machineries at Plot P‑32 in Taloja Industrial Area Item No.01 Submersible pumps for Openwells (WP-OSP) 1.1 Supplying, erecting, testing and commissioning of minimum three & above star rated submersible pump set suitable for erection on open well of 5.625 kW/7.5 HP with 415 V, three phase, 50 Hz, A.C. supply having delivery head from 36 to 14m and discharge from 225 to 1680 lpm & 75 mm suction/65 mm delivery dia. as per specification no. WP-OSP.
Item No.02 Valves (FF-VL) 2.1 Supplying and erecting 150 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV
2.2 Supplying and erecting 150 mm dia cast iron double flange NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV
Item No.03 Supplying, erecting, testing and commissioning of pump starter panel including all required accessories
Item No.05 LT Cables (Aluminum) (CB-LT/AL) 5.1 Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3½ core 50 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
5.2 Supplying, erecting & terminating FR XLPE insulated, galvanised steel wire armoured (round) cable, 1100 V 3 core 10 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Item No.06 Providing and laying Cast in situ/Ready Mix cement concrete in M15 of trap/ granite/quartzite/gneiss metal for foundation and bedding / steps including steel centering, formwork, laying/pumping, compacting, roughening them if special finish is to be provided, finishing uneven and honeycombed surface and curing etc. complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface, only. Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc. (Wooden centering will not be allowed.),with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Item No.07 Accessories 7.1 Supplying and fixing PVC synthetic elastomerelectrically insulatingmat withclassCinsulationconformingto IS:15652–2006testedhaving3mm thickness upto 33 kV
Item No.08 Bunch of Wires (WG-MA/BW) 8.1 Supplying & erecting mains with 3x10 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/bus bars or any other places as per specification no. WG-MA/BW
Item No.09 Wiring Accessories 9.1 Supplying and erecting recess type, 3 pin plug socket 6A with piano switch 6A erected on M.S Box made of 16 SWG sheet duly painted and covered with bakelite hylam sheet of 3mm thickness connected with earth terminals and leads duly concealed
Item No.10 Modular switches and Accessories 10.1 Supplying and erecting modular type switch 6A/10A on provided plate and box with wiring connections complete.
10.2 Supplying and erecting PVC Surface modular switch box with double mounting & front plate for 8 module complete duly connected.
10.3 Supplying and erecting 6 to 32A, 10kA, SPMCB suitable to fix in 1 module of modular switch in provided box complete & duly concealed with necessary material and connected.
Item No.11 Point Wiring (WG-PW) Point wiring for 11.1 independent plug in PVC trunking (casing-capping) with 1.5 sq.mm FRLSH grade copper wire, flush type switch,earthing and required accessories as per specification no. WG-PW/SW
11.2 Point wiring for light/bell/exhaust fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification no. WG-PW/SW
Item No.12 Lamps and Tubes for Indoor & Outdoor (FG-LP) 12.1 Supplying & erecting ready to use Retrofit T8 LED, 18 / 20 watt tube light with polycarbonate body, heat sink, integrated HF electronic driver complete & compatible to T8 / T12 LED luminaire by disconnecting starter & ballast if necessary as per specification No. FG-LP/RET.
Item No.13 Fans (FG-FN) 13.1 Supplying and erecting regular/ standard model ceiling fan of 900 /1050 mm. sweep complete erected in position as per specification no. FG-FN/CF.
13.2 Providing and erecting air circulator 600 mm. sweep oscillating type, wall mounting 1440 RPM without speed regulator, overheat protection unit, totally enclosed, flame proof motor suitable for 230/250 volts single phase, 50 cycles A.C. supply, core lead wire and with moisture proof treatment to winding and with ‘E’ class insulation.
13.3 Supplying and erecting exhaust fan heavy duty 230 V A.C. 50 cycles 450 mm. 900 RPM complete erected in position as per specification no. FG-FN/EXF
Item No.14 Plate, Pipe type Earthing (EA-EP) 14.1 Supply, installing, and testing of maintenance free earthing comprising of electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity (min. 125kg) complete, and recording the results specification no. EA-MF
Item No.15 Accessories 15.1 Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required as per specification no EA-EP.
Item No.16 Providing and Supplying ISI mark C.I. S&S pipes (push on joints pressure pipes of C.I of following class and diameters confirming to the I.S.specification inclusive cost of jointing gasket materials(Rubber Quality) of EPDM excluding GST levied by Gol and GoM in all respect, Third party inspection charges of TPI Agency approved by MJP including Transit insurance, Railway Freight, Unloading from railway wagon, Loading into Truck, Transportation to departmental work, unloading, store/site of as stacking etc. completed directed by Engineer -in-charge (IS 1536/2001 for pipes and IS 158/1969 and IS 12820/1989 or latest edition / revision with amendments for Rubber Gaskets. (Suitable for Tyton / Pig lead joints) Class B pipe dia 300mm.
Item No.17 Lowering laying and jointing with SBR ruber gaskets C.I. S/S pipes of various classes with CI / MS specials of following diameter in proper position, grade and alignment as directed by Engineer-in-charge including conveyance of material from stores to site of work, including cost of jointing materials and rubber rings labour etc. complete. Note: Only SBR Rubber gaskets to be used as per. Only 85 % rate shall be payable till satisfactory Hydraulic testing is given. b) C.I. ‘L.A. Class / Mortar inlined DI K-9/K-7 Without Rubber Rings With Rubber Rings a) 300mm
Item No.18 Excavation for foundation / pipe trenches in earth soils of all types, sand, gravel and soft murum, including removing the excavated material upto a distance of 50 metres and lifts as below, stacking and spreading directed, as normal dewatering, bed for and excluding preparing the foundation backfilling, etc. complete. (Bd-A- 1/259) lift 0 to 1.5 M
Item No.19 Excavation for foundation / pipe trenches in soft rock and old cement and lime masonry foundation asphalt road including removing the excavated material upto a distance of 50 ? beyond the area and lifts as below, stacking as directed Engineer-in- charge, normal dewatering, preparing the bed for foundation and excluding backfilling, etc. complete. (Bd-A-4/259).lift 0 to 1.5 M
Item No.20 Lowering, laying in position to correct line and level including M. S. pipes with / without any outcoating on pedestals or chairs upon prepared formation. The rate to include loading, unloading, hoisting, marginal cutting wherever required, assembling and tack welding, and transportation upto 500 M. etc. completed as specified. 20.1 5 mm to 8 mm thick - i)) Upto 250 mm. dia.
Item No.21 Provding erecting Air valve with isolating sluice valves size 100 mm(PN 1.6)
Item no.22 Providing, erecting and commissioning M.S. Dismantling joint as per requirement and Department‘s approved drawing and specifications, including machining and rubber rings and suitable for 16 kg/cm2 working pressure with required flanges of suitable size with nut bolts etc complete. The joint should have through long bolts so that during normal working pressure there should be no sliding movement of sliding flanges. L.O.F. ( length over flange ) should not be less than 75% of dia. 150 mm
Sub Estimate No.03 Providing Effluent Pumping Machineries at Plot P‑32 in Taloja Industrial Area Item No.01 Providing, installing commissioning and testing of Submersible non clog Pump capable of discharging effluent of specific gravity 1.2 at 100 Cum /Hr at duty point head of 10 Mtr and operating within head range of 8 to 12 Mtr with all s.s parts with SS 316 such as casing ,impeller ,casing wear ring ,pump shaft ,sleeve, nut bolts etc & with Class F insulation motor having 7.5 HP capacity etc complete along with the necessary SS frame, SS Structure with Chain Pulley Block, Stainless Steel Lifting Chain, of adequate capacity, guide pipe etc as per site requirement for lowering and lifting of pump for Maintenance purpose.
Item No.02 Providing, installing, commissioning and testing pump starter panel including all required accessories.
Item No.03 Valves (FF-VL) 3.1 Supplying and erecting 150 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV
3.2 Supplying and erecting 150 mm dia cast iron double flange NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV
Item No.04 Providing, fixing In position and jointing 80 mm Dia. stainless steel Dynamic Air Valve with nipple and with / without isolating thread stop cock conforming to IS: 14848-2000, tested to 200 M head of water (working pressure). [Rates to include cost of gaskets, bolts, nuts and any other material required for jointing and also cost of Valve, its transportation etc. including taxes and duties but excluding GST
Item No.05 Supplying ,erecting and commissioning of Spiral Welded S.S.316 Pipes of size,150 mm, 250 mm , 600 mm dia of 10 mm thick, Flanges 250 mm & 600 mm ,dismantling joints (as manufactured by SAIL or its equivalent). Rates to include cost of all materials and all kind of duties and including loading, transporting, unloading and stacking , fabrication work etc
Item No.06 LT Cables (Aluminum) (CB-LT/AL) 6.1 Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3½ core 50 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Item No.07 Providing and laying Cast in situ/Ready Mix cement concrete in M15 of trap/ granite/quartzite/gneiss metal for foundation and bedding / steps including steel centering, formwork, laying/pumping, compacting, roughening them if special finish is to be provided, finishing uneven and honeycombed surface and curing etc. complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface, only. Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc. (Wooden centering will not be allowed.),with fully With fine aggregate (Crushed sand VSI Grade)
Item No.08 Accessories 8.1 Supplying and fixing PVC synthetic elastomer electrically insulating mat with class C insulation conforming to IS: 15652 – 2006 tested having 3mm thickness upto 33 kV
Item No.09 Bunch of Wires (WG-MA/BW) 9.1 Supplying & erecting mains with 3x10 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/bus bars or any other places as per specification no. WG-MA/BW
Item No.10 Wiring Accessories 10.1 Supplying and erecting recess type, 3 pin plug socket 6A with piano switch 6A erected on M.S Box made of 16 SWG sheet duly painted and covered with bakelite hylam sheet of 3mm thickness connected with earth terminals and leads duly concealed
Item No.11 Modular switches and Accessories 11.1 Supplying and erecting modular type switch 6A/10A on provided plate and box with wiring connections complete.
11.2 Supplying and erecting PVC Surface modular switch box with double mounting & front plate for 8 module complete duly connected.
11.3 Supplying and erecting 6 to 32A, 10kA, SPMCB suitable to fix in 1 module of modular switch in provided box complete & duly concealed with necessary material and connected.
Item No.12 Point Wiring (WG-PW) 12.1 Point wiring for independent plug in PVC trunking (casing-capping) with 1.5 sq.mm FRLSH grade copper wire, flush type switch,earthing and required accessories as per specification no. WG-PW/SW
12.2 Point wiring for light/bell/exhaust fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification no. WG-PW/SW
Item No.13 Lamps and Tubes for Indoor & Outdoor (FG-LP) 13.1 Supplying & erecting ready to use Retrofit T8 LED, 18 / 20 watt tube light with polycarbonate body, heat sink, integrated HF electronic driver complete & compatible to T8 / T12 LED luminaire by disconnecting starter & ballast if necessary as per specification No. FG-LP/RET.
Item No.14 Fans (FG-FN) 14.1 Supplying and erecting regular/ standard model ceiling fan of 900 /1050 mm. sweep complete erected in position as per specification no. FG-FN/CF.
14.2 Providing and erecting air circulator 600 mm. sweep oscillating type, wall mounting 1440 RPM without speed regulator, overheat protection unit, totally enclosed, flame proof motor suitable for 230/250 volts single phase, 50 cycles A.C. supply, core lead wire and with moisture proof treatment to winding and with ‘E’ class insulation.
14.3 Supplying and erecting exhaust fan heavy duty 230 V A.C. 50 cycles 450 mm. 900 RPM complete erected in position as per specification no. FG-FN/EXF
Item No.15 Plate, Pipe type Earthing (EA-EP) 15.1 Supply, installing, and testing of maintenance free earthing comprising of electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity (min. 125kg) complete, and recording the results specification no. EA-MF
Item No.16 Accessories 16.1 Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required as per specification no EA-EP.
Sub Estimate No.04 Providing Street lights on ineternal CC road at Plot P‑32 in Taloja Industrial Area Item No.01 Hot Dipped Galvanized Poles & High-Mast (OH-HM) 1.1 Providing & erecting 7 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 130 mm A/F, top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL
1.2 Providing and erecting galvanised 1000mm single arm sword type bracket with FRP dome and ball as per specification no. OH-PL/BKT
Item No.02 C.C. Foundation 2.1 Making M-20 grade reinforced cement concrete foundation by considering the safe soil bearing capacity at site as 10 T/sq.m at 1.5m depth including supply of steel, concrete, excavation and fixing provided nut bolts with the help of template, duly plastered as per design complete (for 6m to 8m high octagonal/conical GI pole).
Item No.03 Outdoor Fittings (FG-ODF) 3.1 Supplying and erecting integrated LED street light fitting 100-110W IP65 & IK08 class having single piece pressure die-cast aluminium housing, having system lumens output of Min. 11000 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.95, operating range of 140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs at L70B50 including driver complete with minimum 2 Years warranty as per specification No. FG-ODF/SL.
Item No.05 Plate, Pipe type Earthing (EA-EP) 5.1 Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recording the results as per specification no. EA-EP
Item No.06 LT Cables (Aluminum) (CB-LT/AL) 6.1 Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 4 core 16 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
6.2 Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 4 core 25 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Item no.07Cable Enclosures (CB-CE) 7.1 Supplying and laying (including excavation of suitable width & depth up to 90 cm) 50 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, complete.
Item no.08 Bunch of Wires (WG-MA/BW) 8.1 Supplying & erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/bus bars or any other places as per specification no. WG-MA/BW
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.32 MB
BOQ_2205690.xls
BOQ • 0.36 MB
ItemSpecification.pdf
Other Document • 0.14 MB
TenderDocument.pdf
Tender Documents • 0.53 MB
Download all tender documents and submit your bid