SE EUCC XI
SE EUCC XI
Tapping of Sec-25 Indira Nagar Line Enamating from 132 Khurram Nagar, Badri Saraf Exposure to 33/11 KV S/S Vikas Nagar and assoicated work On Semi turnkey basis Under Business Plan 2024-25.
2024_MVVNL_922705_1
57/EUCC(XI)/LESA(T.G.)/2023-24
Open Tender
Electrical Works
Item Wise
EE EUCD I
AS PER PQR
2 documents required · 2 mandatory
₹3,540
EE EUCD I
₹24,600
7 May 2024
20 Apr 2024
4 May 2024
20 Apr 2024
3 May 2024
20 Apr 2024
Amount
Safe loading & carriage including & proper stacking of following store material from ESC Lucknow /JE store to site of work .
33 KV 3x300 sq mm XLPE Cable
33 KV 3x300 sq mm XLPE St/Th J/Kit
33 KV 3x300 sq mm XLPE O/D J/Kit
Panther Conductor
33 KV VCB 800 Amp 750 MVA
Single Feeder Control Panel
33 KV LINE ISOLATOR 400/800 A
33 KV Lightening Arrestor
33 KV BUS ISOLATOR 400/800 A
33 KV CT 400/200/1 amp
33 KV PT,33KV/110V-1P (outdoor)
ST Pole 11 Mtr Long (Galvanised Bottom)
33 KV Pin Insulator
33 KV Pin with Nut
MS earthing rod 20x2500 mm
LT PVC Cable 1x400 sq mm
Steel Section
33 kv3x300 Sq.mm XLPE cable laying in 150mm GI/MS pipe dia single circuit (All the material shall be provided by the contractor except cable )as per resspo norms.
33 kv 3x300 sq mm XLPE cable laying in RCC Pipe S/C.(All the material shall be provided by the contractor except 33kvcables)as per resspo norms.
Cable laying by drill method Double circuit. (All the material shall be provided by the contractor except 33kvcables)
Hoisting of 33 kv 3x300 sq mm XLPE Cable on D/P with GI Pipe dia 6" its jumpring complete with clamps , nuts and bolts .(All the material shall be provided by the contractor except33kv cables & O/D J/K. )as per RESSPO NORMS
Hoisting of 33 kv 3x300 sq mm XLPE Cable on cable stand its jumpring complete with clamps , nuts and bolts .(All the material shall be provided by the contractor except33kv cables & O/D J/K. )as per RESSPO NORMS
Construction of plinth of size 2.0 mtr x 1.5 mtr x 0.9 mtr suitable for erection of upper structure for 33KV VCB including grouting of anchor bolts in proper alignment and level. Scope of work includes excavation of foundation base concreting in CC 1:6:12 (cement, fine sand & brick ballast ),1 st class brick work in cement mortar of ratio 1:4 CC in ratio 1:4:8 and RCC work in ratio 1:2:4 (cement coarse sand and stone grit of 20mm gauge ) as per RESSPO norms.
Installation of 33KV VCB- complete work including commissioning
Fabrication & erection of LA, CT & PT. structure as per RESSPO Norms.(steel material provided by Contractor )
Assembling and installation/ Mounting of lightning arrestors on the L.A. Structure as per Resspo norms.
Installation of PT/CTs on the PT/CT structure along with PT/C.T. junction box .(junction box provided by contractor).
Shifting carefully & installation of 33KV feeder / transformer control panel in control room including its grouting
Fabrication & erection of Isolator structure as per RESSPO Norms.(steel material provided by deptt.)
Assembling and installation of line / bus isolator on the isolator structure , In case of line isolator proper operator of earth links shall also be insured. The work includes fabrication for proper flexing if required.
Fabrication & erection of 33 KV cable exposure type double pole with the provision of separate bus bar for each cable with fixing of necessary clamps and other accessories like danger board, number plate, barbed wire, 9 no. pin insulators with pins,2 no. channels 100x50 mm (1600mm each),1 no.MS channel 100x50 mm(3200mm in length) and 2 no.MS angle 65x65x6 mm (each 3200mm in length ) for supporting the hoisting of cable etc. Its jumpering by single core PVC aluminium cable with proper size of lug as per RESSPO norms.(All material to be arranged by contractor except STP, MS Channel, MS Angle, 33 KV Pin Insulator, 33 KV Pin with nut &PVC cable).
Fabrication & erection of cable stand with grouting & plinthing as per resspo norms. (steel material provided by department)
Earthing by way of boring and lowering of "B" Class GI pipe 50 mm dia from ground upto the water level(minimum 30 mtr. Deep )as per standard practice (All material shall be provided by the contractor except the supplied items )as per resspo norms.
High pressure testing of 33kv 3x300 sq.mm.XLPE cable .Testing equipment will be arranged by the contractor
Painting of 33 kv feeder Name on the Cable stand as per instruction of site engineer
Earthing of indoor/Outdoor equipments & structures by means of M.S strip 50X6mm & connecting to pipe type earthing as per RESPO norms.joints will be welded with high quality are welding.( All the material shall be provided by the contractor )as per RESPO norms(
Painting of all structures &equipments. (All materials shall be provided by the contractor ).as per RESSPO Norms.
Jumpering of all equipments in switch yard with Panther conductor P.G.clams & proper size aluminium lugs including stringing Busbar.
Providing & fixing of connector for CT ,isolator etc.
Digging of pit of size 3x2x1 mtr. For making straight through joint 33KV work included filling of soil levelling and ramming of the same .( S/Th Providing by department )
Scanning/Tracing of existing underneath power cables, water pipe line, gas pipe line, sewer pipe line on proposed route.(Tracing Equipment shall be arrange by the contractor)
Painting of all structures & equipments. (All materials shall be provided by the contractor ).as per RESSPO Norms.
Grouting & plinthing of STP in depth of 1/6th the length of pole in ratio 1:4:8 in cement sand and brick ballast and construction of pole plinth 300mm x 45mm above ground level in 1:2:4 in cement, coarse sand and stone gritt as per RESSPO norms.
Painting of STP with one coat of red oxide & two coats of best quality top 2 M PO Red paint and remaining al. Paint (ISI mark) as per RESPO norms.
Construction of cable trench of size 300x300 mm with welded frame type control cable trench cover suitable for trench including cost of MS/Torr Bar.(All material Shall be supplied by the contractor)
Providing and Laying of following size copper, control cable through underground/cable trench/trenching SGR interlinking through proper connections to transformer control panel/protection board /Battery and Battery Charger/Relays 33/11 KV Transformer junction box/ 33KV VCB ,CTs etc as per site conditions.
Providing & installation of control cable tray.
GST SHALL BE PAID EXTRA
ARIHANT ELECTRIC COMPANY
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .