| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.9 LAccepted-AOC | L1 | Accepted-AOC being lowest bidder | |
| 2 | L2₹43.0 L+₹6.0 L (16.2%)Rejected-Finance | L2 | Rejected-Finance Being other than lowest bidder | |
| 3 | L3₹43.1 L+₹6.1 L (16.4%)Rejected-Finance FLAT NO 101 2ND FLOOR RAGHAVENDRA RESIDENCY PLOT NO 1 2 3 SURVEY NO 27 PICKET SECUNDERABAD 500026 | HYDERABAD | TELANGANA | 500026 | L3 | Rejected-Finance Being other than lowest bidder | |
| 4 | L4₹45.4 L+₹8.3 L (22.5%)Rejected-Finance HOUSE NO 2 4 136 LINGREDDY MANSION BLOCK NO IV OPP HANUMAN TEMPLE TADBUND SECUNDERABAD 500009 | SECUNDERABAD | HYDERABAD | TELANGANA | 500009 | L4 | Rejected-Finance Being other than lowest bidder | |
| 5 | L5₹47.1 L+₹10.1 L (27.2%)Rejected-Finance | L5 | Rejected-Finance Being other than lowest bidder |
| Sl No | Description | Qty | Unit | L and S ENTERPRISES L3 | Srinivasa Consructions L6 | omsai thermax engineers L4 | MS ENTERPRISES L5 | SUN LIGHT HOUSE L1 | Srinivash Engineers L2 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 500 Amps rating for phase and neutral 4 strips with colour | 4 | Each job | 1,35,000 ₹5,40,000 | 1,75,000 ₹7,00,000 | 1,43,100 ₹5,72,400 | 1,59,323 ₹6,37,292 | 1,10,000 ₹4,40,000 Lowest | 1,35,000 ₹5,40,000 |
| 1.01coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- | |||||||||
| 1.02MCCB 4pole, 315 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) | |||||||||
| 1.03MCCB 4pole, 100 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 06 No (Outgoing) | |||||||||
| 1.04Digital Ammeter 0 to 500Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set | |||||||||
| 1.05Digital Voltmeter 0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set | |||||||||
| 1.06Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set | |||||||||
| 2.00 | Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 400 Amps rating for phase and neutral 4 strips with colour | 3 | Each job | 1,26,000 ₹3,78,000 | 1,61,000 ₹4,83,000 | 1,31,400 ₹3,94,200 | 1,45,323 ₹4,35,969 | 1,00,000 ₹3,00,000 Lowest | 1,29,000 ₹3,87,000 |
| 2.01coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :- | |||||||||
| 2.02MCCB 4pole, 315 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming) | |||||||||
Tender Value
₹47.9 L
EMD Value
₹95,880
Closing Date
24 Dec 2025, 6:00 pmClosed
GE (UTILITY) SECUNDERABAD
GE UTILITY SECUNDERABAD MUDFORT SECUNDERABAD-500003
REPAIRS/ REPLACEMENT AND MAINTENANCE OF LT SWITCH GEAR, PANEL, APFC PANEL, CAPACITOR BANK AND CONNECTED ITEM AT CERTAIN LOCATION OF OR MD/ JCO MD ACCN OF TRISHUL LINE AREA, SANJAY LINE AREA, LAKE LINE AREA AND CERTAIN AREA UNDER AGE EM I OF GE(U) SEC
2025_MES_742714_1
GE (U)/SEC/TOKEN/62 OF 2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
SECUNDERABAD
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE (UTILITY) SECUNDERABAD
₹95,880
Yes
27 Feb 2026
3 Dec 2025
31 Dec 2025
3 Dec 2025
24 Dec 2025
17 Dec 2025
Amount
Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 500 Amps rating for phase and neutral 4 strips with colour
coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :-
MCCB 4pole, 315 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
MCCB 4pole, 100 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 06 No (Outgoing)
Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 400 Amps rating for phase and neutral 4 strips with colour
coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :-
MCCB 4pole, 315 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
MCCB 4pole, 63 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 06 No (Outgoing)
Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 250 Amps rating for phase and neutral 4 strips with colour
coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :-
MCCB 4pole, 200 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415lt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
MCCB 4pole, 40 Amps, with adjustable thermal and magnetic settings, 10KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 06 No (Outgoing)
MCCB 4pole, 125 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 03 No (Outgoing)
Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 630 Amps rating for phase and neutral 4 strips with colour
coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :-
MCCB 4pole, 630 Amps, with adjustable thermal and magnetic settings, 25 KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
MCCB 4pole, 315 Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 04 No (Outgoing)
Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
Supply, Install, testing and commissioning in replacement of old unserviceable LT panel, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 500 Amps rating for phase and neutral 4 strips with colour
coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the following accessories :-
MCCB 4pole, 400 Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415lt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
MCCB 4pole, 63 Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 07 No (Outgoing)
Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
S&F in repairs Weather proof outdoor bus bar chamber made out of 3mm thick MS sheet comprising MCCB 4pole 125 Amps 25KA capacity thernal and magnetic setting as incommer and 4 Nos aluminium strips each of 200 Amps as outgoing , 90cm long duly insulated mounted on insulators with 4 No’s mounting legs made out of 25mm x 25mm x 6mm angle iron grouted in PCC block of size 30cm x 30cm x 90cm (30cm depth below ground level and 60cm above ground level) in cement concrete 1:3:6, type C-2 (using 40mm grade crushed stone aggregate), and connections with suitable size of aluminium thimbles, nuts, bolts & washers, cable glands at entry and outlet points and excavation, earth work, returning filling in and removal of surplus soils including taking out old unserviceable bus bar chamber complete all as specified and directed.
Supply only power factor correction capacitor, 5 KVAR, heavy duty 440 volts 50 Hz complete including taking down old existing capacitor complete all as specified and directed.
All as per item No 11 above but 10 KVAR Capactor.
All as per item No 11 here-in-before but 15 KVAR Capactor.
All as per item No 11 here-in-before but 20 KVAR Capactor.
All as per item No 11 here-in-before but 25 KVAR Capactor. Make for item No 11 to 15- L&T or equivalent make in Schneider/HPL
S&F in repairs APFC relay with auto-set function 6 stage, including taking down old existing relay complete all as specified and directed. Make:- L&T/schneider/siemens
S&F in repairs APFC relay with auto-set function 6 stage, including taking down old existing relay complete all as specified and directed. Make:- L&T/schneider/siemens
S&F in repairs, 3pole 63Amp MCCB, 16KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
S&F in repairs, 3pole 125Amp MCCB, 16KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
S&F in repairs, 4pole 160Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
S&F in repairs, 3pole 200Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
S&F in repairs, 4pole 200Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
S&F in repairs, 3pole 250Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
S&F in repairs, 4pole 250Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
S&F in repairs, 4pole 400Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
S&F in repairs, 4pole 630Amp MCCB, 50KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II complete all as specified.
Supply and fix in repaire, 3 phase street light control DB Box internally prewired comprising of Aestronomical timer swich, power contactor, and MCCB for maximum load of 65 Amps complete all as specified and directed by Engh in charge.Make IndoAsian cat no TL065ASO with astronomical switch TDA45163 OR equivalant in L&T/Scheinde
M&L in repairs, Earthing complete with galvanized steel earth plate electrode of size 600 x 600 x 6mm thick buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of plate not less than 1.5m below normal ground level connected to GI strip 25x4mm as earth lead by means of bolts, nuts, washers and check nuts made out of galvanized iron or steel all as shown on Electrical Plate No. 3 of SSR Part-I including testing on completion complete all as specified and directed by Eng-in-charge.
Note 1: The unit rate shall also include for earth work in any type of soil, PCC 1:3:6 type C1 chamber, 50mm thick RCC 1:2:4 type B-1 using 20mm graded stone aggregate cover slab reinforced with 6 Nos of 8mm dia TMT bars both ways, funnel with watering pipe 20mm dia medium grade, GI protection pipe medium grade 40mm dia and wire mesh complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub-heading earthing, specified on Sl Page No. 422 of SSR Part-II.
Srinivash Engineers (BID ID -3505586)
L and S ENTERPRISES (BID ID -3506345)
omsai thermax engineers (BID ID -3506580)
MS ENTERPRISES (BID ID -3509848)
Srinivasa Consructions (BID ID -3506452)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.27 MB
BOQ_831696.xls
BOQ • 0.34 MB
TENDER.pdf
Tender Documents • 0.55 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .