GE(AF) GORAKHPUR
GE(AF) GORAKHPUR PIN-273008
REPAIR/MAINT OF EXTERNAL ELECTRIC SUPPLY, STREET LIGHT AT GRD KUNRAGHAT AND NCC GORAKHPUR
2022_MES_542462_2
8918/E8
Open Tender
Civil Works
Item Rate
330 days
GE(AF) GORAKHPUR
As per Tender documents
8 documents required · 8 mandatory
₹500
GE(AF) GORAKHPUR
₹40,000
Yes
6 Oct 2022
31 Aug 2022
20 Sept 2022
31 Aug 2022
19 Sept 2022
7 Sept 2022
Amount
Taking proper shut down in writing / disconnecting the LT and HT electric mains from transformer of capacity 630 KVA (33KV/0.433KV) removing the transformer from platforms, shifting to workshop after draining out the transformer oil at site, dismantling and disconnecting damaged HT/LT coils to facilitate necessary repairs, re-assembling the transformer bringing back to the site, refilling new transformer oil and dehydrated old oil connecting with existing electrical system of HT and LT including charging, testing commission complete all as specified and directed. Note:- 1. Winding wire and other items mentioned in sch 'A' will be measured and paid separately. 2. Placing / removing standby transformer in the place of defective transformer under repair will be the responsibility of the contractor, including transportation and man power stand by transformer or diverting the electric supply to other feeders will be provided by the deptt.
S&F in replacement new HV coil for 630 KVA (33KV/0.433KV) transformer complete all as specified and directed.
S&F reconditioned HV coil for 630 KVA (33KV/0.433KV) transformer complete all as specified and directed.
S&F in replacement new LV coil for 630 KVA (33KV/0.433KV) transformer complete all as specified and directed.
S&F in replacement of damaged laminated core for 630 KVA (33KV/0.433KV) transformer complete all as specified and directed.
S&F in replacement insulating material for 630 KVA (33KV/0.433KV) transformer complete all as specified and directed.
S&F in replacement gasket set of synthetic rubberized cork sheet 5mm thickness with suitable holes for any model transformer rating 630 KVA (33KV/0.433KV) complete all as specified and directed.
M&L for spray painting of transformer at site with one coat of weather proof grey synthetic enamel paint after removing all dust rust carbon and oily spots, including well preparation of surfaces and writing /marking SM/MES No as 25mm stencil with white paint complete all as specified including cleaning of temperature gauge and silica gel, oil temperature level etc for transformer rating 630 KVA (33KV/0.433KV) complete all as specified and directed.
S&F in replacement oil level indicating glass with gasket for transformer rating 630 KVA (33KV/0.433KV) complete all as specified and directed.
S&F in replacement cast iron wheel of transformer for transformer rating 630 KVA (33KV/0.433KV) of suitable size including nuts bolts, split pins welding works as required at site complete all as specified and directed.
S&F in replacement breather assembly complete with silica gel suitable for any model of transformer rating for 630 KVA (33KV/0.433KV) complete all as specified and directed.
S&F in replacement silica gel for transformer rating 630 KVA (33KV/0.433KV) transformer complete all as specified and directed.
S&F in replacement HT bush rod of brass 3/8" dia suitable size both ends threaded including nuts, checknuts and washers suitable for transformer rating 630 KVA (33KV/0.433KV) complete all as specified and directed.
S&F in replacement LT bush rod of brass 12 / 16 mm dia and 180/190mm long with 5 nuts washers rubber washers etc suitable for transformer rating 630 KVA (33KV/0.433KV) complete all as specified and directed.
S&F in replacement Tap changing switch complete all as specified and directed.
Supply only transformer oil of approved quality as per IS having dielectric strength of 40-70 kv in 2.5 mm gap for filling in transformer or for toping up complete all as specified and directed. Make : Servo / Castrol/ Power oil (In a sealed container).
Dehydration /filtration of transformer oil by means of centrifugal filtration plant to achieved the specified dielectric strength up to 40 kv at 4 mm gap in existing possession of transformer of any capacity and transformer oil for toping up at various sub station complete all as specified and directed.
S&F in replacement nuts bolts and washers fully threaded of MS size 5/8"x2" or as per requirement complete all as specified and directed.
S&F in replacement Buch Holz Relay complete all as specified and directed.
Excavation in trenches in soft/loose soil n.exc 1.5 mtr wide and n.exc 1.5 mtr depth and getting out for cable trench complete all as specified and directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exc 25 cm thick complete all as specified and directed.
Removing surplus excavated material not exc 50 mtrs and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
Supply and providing sand cushioning with dry clean sand 15 cm below cable and 8 cm above the cable complete all as specified and directed. Note: Punned thickness shall be measured for the purpose of payments.
Supply and laying burnt bricks old size sub class-B laid in trenches for cable protection with length of brick perpendicular to length of cable complete all as specified and directed.
Supply, laying and testing 10 Sqmm, 4.0 Core XLPE insulated, armoured heavy duty electric cable, screened PVC bedded, galvanised steel strip or wire, with aluminium conductor 1100 V grade, laid in trenches/ along poles, ducts or through sleeve including taking out old cable complete all as specified and directed Note: Earth work, sand cushioning and bricks will be measured and paid separately under relevant items.
All as per item No. 25 above but for 16 Sqmm, 4 core XLPE cable.
All as per item No. 25 above but for 25 Sqmm, 4 core XLPE cable.
All as per item No. 25 above but for 35 Sqmm, 3.5 core XLPE cable.
All as per item No. 25 above but for 70 Sqmm, 3.5 core XLPE cable.
All as per item No. 25 above but for 95 Sqmm, 3.5 core XLPE cable.
All as per item No. 25 above but for 120 Sqmm, 3.5 core XLPE cable.
S&F aluminium lugs for fixing armoured cable of size 10 to 16 sqmm 4 core in panel including taking down old one lugs from cable complete all as specified and directed.
All as per item No. 32 above but for 25 to 35 Sqmm, 4 core XLPE cable.
All as per item No. 32 above but for 50 to 70 Sqmm, 3.5 core XLPE cable.
All as per item No. 32 above but for 95 to 120 Sqmm, 3.5 core XLPE cable.
All as per item No. 32 above but for 150 to 185 Sqmm, 3.5 core XLPE cable.
All as per item No. 32 above but for 240 to 300 Sqmm, 3.5 core XLPE cable.
Taking out old LT under ground cable 16 Sqmm, 4 core XLPE cable from trench and relaying cable after repair in trench complete all as specified and directed. Note:-Excavation and other related items will be measured and paid separately.
All as per item No. 38 above but for 25 Sqmm, 4 core XLPE cable.
All as per item No. 38 above but for 70 Sqmm, 3.5 core XLPE cable.
All as per item No. 38 above but for 95 Sqmm, 3.5 core XLPE cable.
All as per item No. 38 above but for 240 Sqmm, 3.5 core XLPE cable.
M&L for straight through LT cable joint kit including cutting of faulty cable, preparation and jointing complete of size 25 sqmm to 50 sqmm 3.5/4 core including taking out old joint complete all as specified and directed.
All as per item No. 43 above but for 70 to 95 Sqmm, 3.5/4 core XLPE cable.
All as per item No. 43 above but for 120 to 150 Sqmm, 3.5/4 core XLPE cable.
All as per item No. 43 above but for 185 to 240 Sqmm, 3.5/4 core XLPE cable.
Labour only for re-stretching/ restringing of existing loosed/ sagged ACSR over head conductor of any type and size including binding wire/aluminum tape of required size, opening from insulators as fixed on pole after taking proper electric shut down from concerned staff including taking down unserviceable conductor from OH line and proper binding with additional conductor and restringing on line, complete all as specified and directed. Note:- Supply only ACSR conductor shall be measured and paid separately under relevant items.)
S&F in replacement MCCB, 63 Amp, 4 Pole, 50 HZ, 415 Volt, with thermal magnetic based release and rupturing capacity 16 KA complete all as specified and directed.
S&F in replacement MCCB, 100 Amp, 4 Pole, 50 HZ, 415 Volt, with thermal magnetic based release and rupturing capacity 16 KA complete all as specified and directed.
S&F in replacement MCCB, 125 Amp, 4 Pole, 50 HZ, 415 Volt, with thermal magnetic based release and rupturing capacity 16 KA complete all as specified and directed.
S&F in replacement MCCB, 200 Amp, 4 Pole, 50 HZ, 415 Volt, with thermal magnetic based release and rupturing capacity 36 KA complete all as specified and directed.
S&F in replacement MCCB, 250 Amp, 4 Pole, 50 HZ, 415 Volt, with thermal magnetic based release and rupturing capacity 36 KA complete all as specified and directed.
S&F in replacement MCCB, 400 Amp, 4 Pole, 50 HZ, 415 Volt, with thermal magnetic based release and rupturing capacity 36 KA complete all as specified and directed.
S&F in replacement of change over switch on load type front handle operated 63 Amp, 415 Volts, 4 pole confirming to IS 13947-3 in sheet steel enclosure complete all as specified and directed.
S&F in replacement of change over switch on load type front handle operated 200 Amp, 415 Volts, 4 pole confirming to IS 13947-3 in sheet steel enclosure complete all as specified and directed.
S&F in replacement of change over switch on load type front handle operated 630 Amp, 415 Volts, 4 pole confirming to IS 13947-3 in sheet steel enclosure complete all as specified and directed.
M&L in replacement earthing with Galvanised iron earth plate electrode 600x600 mm and 6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal GL) with top of earth plate not less than 1.5 mtr below GL connected to GI earth lead wire of size 4 mm dia connected to earth plate electrode by means of GI nuts, bolts and washers of galvanised iron or steel protected with and including 15 mm dia med grade ISI marked GI pipe upto a length of 7.5 mtr long as shown in electrical plate No 5 of MES Sch Part-I with and including PCC 1:3:6, C-1 pit with cover or RCC 1:2:4 B1 reinforced with welded steel wire fabric not less than 4 kg per Sqm watering arrangement within 20mm dia GI med grade pipe ISI marked, GI funnel with GI mesh, filling with mixture of common salt and charcoal necessary excavation and earth work in soft/loose soil including connected to earthing test point, and main switch/DB, testing and commissioning complete all as specified and directed. Note: (i) GI earth wire with GI pipe protection upto 7.5 mtr shall be deemed included in the item.
M&L in replacement earthing with Galvanised iron earth plate electrode 600x600 mm and 6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal GL) with top of earth plate not less than 1.5 mtr below GL connected to GI earth strip of size 32x6mm connected to earth plate electro by means of GI nuts, bolts, and washers earth strip protection with and incl 40mm dia medium grade ISI marked GI pipe as shown in electrical plate No 5 of MES Sch Part-I, with and incl PCC 1:3:6 type C-1 pit with cover of RCC 1:2:4 type B-1 reinforced with welded steel wire fabric not less than 4 Kg per Sqm, watering arrangements with 20mm dia GI medium graded pipe ISI mark, GI funnel with GI mesh, filling with mixture of common salt and charcoal, necessary excavation and earth work in soft/loose soil, incl test point, testing and commissioning complete all as specified and directed. Note: GI earth strip with GI pipe protection upto 7.5 mtr shall be deemed included in the item.
S&F in replacement earth continuity conductor or main earthing lead 4mm dia GI earth lead, laid in trench, fixed on walls or any other position including jointing by tinned GI nuts, bolts and washers in addition to brazing at every joint, complete all as specified and directed.
S&F in replacement earth continuity conductor or main earthing lead 32mmx 6mm GI strip/earth lead, laid in trench, fixed on walls or any other position including jointing by tinned GI nuts, bolts and washers in addition to brazing at every joint, complete all as specified and directed.
S&F in replacement of volt meter (0-600 volts) of size (96x96) mm square type flush mounting complete all as specified and directed. Make:- AE/L&T/HPL
S&F in replacement of Amp meter (0-400 Amps) of size (96x96) mm square type flush mounting complete all as specified and directed. Make:- AE/L&T/HPL
S&F in replacement current transformer Ratio 100/5 A, 240 Volt AC indoor type insulated ring type LT Current Transformer and including connecting wire and connected with panel bus bar complete all as specified and directed.
M&L for cutting and removing wild bushes/ vegetation, surface dressing around the MES installation and depositing surplus spoil/ rubbish exc 100M but n.exc 500 M complete all as specified and directed.
S&F in replacement 80mm bore GI pipe, light grade with all fittings laid in trenches, road crossing and fixed to walls, on poles etc for cable protection complete all as specified and directed.
S&F cable route indicators LT, made of RCC 1:2:4 of size 0.2mx0.1m x0.75 m including necessary excavation in soft/loose soil, embedded in PCC 1:3:6 type C-1 block of size 200x200x150mm and removal of surplus soil and marked as LT cable / joints complete all as specified and as directed.
Labour only for checking the serviceability of the different spares/ components/ parts of security/ street light/ Flood light fittings on pole/ wall any wattage/ capacity of any description and in any position with the help of one Electrician and one helper, replacement of un-serviceable/ damaged/ broken part(s) either in single or in combination, re-assembling the fittings and making the light fittings serviceable, fixing the fittings in new or old position, connecting to electric supply and its testing on installation complete all as specified and directed.
Disconnecting and taking out old existing unserviceable street light fitting of any description and S&F, testing energy saving, die cast aluminium housing IP 65 protection, 45 W LED street light fitting with high power LED as light source complete fixed on pole using 30x5mm FI clamps, nuts, bolts & washers all as per site requirement complete all as specified and directed. Make:-Havells Cat No. ENDURAPEARLNEOSL45WLED757PASY TOPC or equivalent in specified make.
Disconnecting and taking out old existing unserviceable street light fitting of any description and S&F, testing energy saving, die cast aluminium housing IP 65 protection, 60 W LED street light fitting with high power LED as light source complete fixed on pole using 30x5mm FI clamps, nuts, bolts & washers all as per site requirement complete all as specified and directed. Make:-Havells Cat No. ENDURAPEARLNEOSL60WLED757PASY TOPC or equivalent in specified make.
Disconnecting and taking out old existing unserviceable light fitting of any description and S&F light fitting IP-66 powder coated pressure die cast aluminium housing with high power LED as lighting source with heat resistant toughtened glass 60 W LED fitting complete with all accessories of capacity 60 watt complete all as specified and directed. Make:-Havells Cat No. JETA QUANTOPLUSFLP60WLED757 SYMLENS or equivalent in specified make.
S&F in repair of LED power Driver for street light 50 watt complete all as directed.
S&F in repair of LED power Driver for street light 60 watt complete all as directed.
S&F in replacement 2.5 sqmm three core PVC insulated, unsheathed multistranded copper conductor cable 1100 Volt grade draw from junction box to street light fitting complete all as specified and as directed.
Disconnecting and taking out old unserviceable light fitting’s bracket incl FI clamps of any description and in any position and supplying and fixing brackets made out of 32mm dia medium grade GI pipe 1.50 mtr long bent to shape and size fixed on location using new 2 nos 30x5mm FI clamps made to shape incl nuts, bolts & washers complete all as specified and directed .
Disconnecting and taking out old existing unserviceable junction box and S&F in position new sheet moulding compound (SMC) junction boxes of size 300mmX200mmX130mm depth. The box shall provided with and including 4 Nos, 100 Amps aluminum bus bar mounted on porcelain insulators including connecting the bus bars to cables with using suitable GI nut, bolts and washers and aluminum lugs etc fixed on pole using 30x5mm FI clamps, nuts, bolts & washers complete all as specified and directed.
M&L for painting of LT steel tubular pole swaged/steel poles of 8/9 mtr height with and including cross arms, MS clamps nuts, bolts, street light brackets, height from 1.5 mtr from coping to top of pole including preparation of iron surface and applying with single coat of aluminium paint on existing surface and from coping to 1.5 mtr height painting with a coat of synthetic enamel paint in 30 cm wide strips alternatively black and white on existing surface including white washing on PCC coping of poles complete all as specified and directed.
Repair of LED garden Light 9 watt by replacement the defective part i.e. holder/diode/CFL LED including all accessories and repair of UNSV wire any size connected to garden light complete all as specified and directed.
S&F in repair LED Bollard light (Garden Light) 9 watt, single phase, 240 Volts with 9 watt LED lamp opal diffuser & aluminium reflector complete all as specified and directed. Make:- Code No. LTGLC W LED of C&S or equivalent in Bajaj/ Philips/ CG/ WIPRO
S&F in repair Integral LED Post-Top Luminaire 40 W comprises housing with LEDs and driver, glare-free and better uniformity and heat resistant toughened glass with frame suitably gasket for IP-65 class-I protection including all accessories, complete all as specified and directed. Make: CG Model- Maple, Cat part No: LPTO-40-CDL or equivalent in Bajaj/ Philips/Havells/CG/ WIPRO
M&L for servicing of 33 KVA VCB, current transformer, control relay panel, remote ON/OFF of control panel, repair of battery charger of control panel, repair of DC motor of TPMO with including wiring and related other works complete all as specified and directed.
M&L for disconnecting burnt end or portion of 10 sq mm to 185 Sq mm 3.5 core cable, removing the cable from loop including necessary excavation, earthwork, removing brick protection and relaying the same, and reconnecting the cable by removing burnt portion of cable and preparing fresh terminals of LT cable to pole / main switch etc complete all as specified and directed.
S&F in replacement of rubberised gasket set for top cover, Brass spindles, LT and HT bushings etc. complete all as specified and directed.
S&F in replacement factory made epoxy powder coated distribution board double door TP&N 4 ways (VTPN MCCB DB) with metal door (IP-43 protection) fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including 200 Amps copper bus bar, neutral bar, strandard DIN rail, earth bar and cable ties for cable management, top and bottom removable gland plates with knockouts including one FP MCCB/MCB 100/ 63 Amps as incomer and 24 Nos MCBs (or any combination of SP/TP MCBs ) outgoings complete all as specified & directed.
Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) FRLS with aluminium conductor, 33000 volts, grade cross sectional area 70 sqmm 3 core (Earthed) including out existing unsv cable complete all as specified and directed.
Supply and laying in replacement weather proof cable 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed 10 sq.mm 2 core nominal cross section in service connections complete all as specified and directed.
Pioneer Engineering works
His And Her Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .