| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.7 LAccepted-Finance | L1 | Accepted-Finance Ok | |
| 2 | L2₹5.2 L+₹53,856.45 (11.5%)Accepted-Finance | L2 | Accepted-Finance Ok | |
| 3 | L3₹5.3 L+₹63,816.93 (13.6%)Accepted-Finance | L3 | Accepted-Finance Ok | |
| 4 | L4₹5.8 L+₹1.1 L (23.5%)Accepted-Finance | L4 | Accepted-Finance Ok | |
| 5 | L5₹7.2 L+₹2.5 L (53.5%)Accepted-Finance | L5 | Accepted-Finance Ok |
Tender Value
Refer Docs
EMD Value
₹14,700
Closing Date
24 Jul 2024, 2:30 pmClosed
EE(EnM)HP-II
OFFICE OF THE EXECUTIVE ENGINEER (EnM) HP-II DELHI JAL BOARD GOVT OF NCT OF DELHI HAIDER PUR WATER WORKS, DELHI 110085
Renovation of back pressure line 4 dia. Scour valve and Repair of pump sets with allied works at Filter house (South) HPWW-II
2024_DJB_259634_4
NIT 06(2024-25)HP-II
Open Tender
Miscellaneous Works
Item Rate
60 days
WTP Haiderpur
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
DJB
₹14,700
31 Jul 2024
16 Jul 2024
24 Jul 2024
16 Jul 2024
24 Jul 2024
16 Jul 2024
Dismantling and taking out of nonworkable pump set and damaged pipe line from the ground after digging work upto the depth of 2.5ft down in the ground. The job includes cutting of rusted nut bolts & pipe with the help of gas cutter & other tools tackles by manual labour arrangement and shifting the old material to jank yard as per the direction of engineer in-charge.
Supply of MS Medium Class black pipe of 100mm dia. 4.5mm thick, 98m length
Supply of M.S Bend of size 100mm X 100mm dia.
Supply of M.S Tee of size 100mm X 100mm dia.
Supply of C.I foot valve of 100mm dia. SOR 4.41.4
Supply of C.I Sluice valve of 100mm dia.
Supply of MS Flange of 100mm dia.
Tyre coupling set TC-12 SOR 21.8.13
Supply of Nut bolts & washers.
Supply of rubber packing sheet. SOR 22.6.1
Supply of 4 core, 25mmsq aluminum conductor, PVC insulated armored cable 1.1KV confirming to IS: 1554 (part-I) 1988/7098 Make- Grandlay/Gloster/Universal/ICL/ICC/Havells.
Laying and fixing work of MS pipe of 100mm dia in the ground upto the depth of 2.5ft down i/c digging work of ground upto the depth of 2.5ft down for laying the MS pipe with all jointing carefully.
Digging and laying work or surface laying for PVC insulated power cable by digging of earth by manual labour upto the required depth, sand cushioning and protective covering of power cable in the trench etc & refilling the trenches after completion of laying work as per site requirement.
Making of RCC foundation for fixing of M.S. Base frame of pump set with grouting of foundation bolts for base Frame as per site requirement. Including the charges of labour and civil material.
Making of RCC foundation for fixing of panel as per the height required at site and fixing of nut bolts Including the charges of labour and civil material.
Fabrication and fixing of canopy for electric panel for safety from the rain water. The canopy fabricated by MS angle of size 25x25x3mm and fiber sheet i/c nut bolts and other hardware goods as per site requirement.
Fabrication and fixing of new base frame for pump set of size 17”x45” fabricated by MS channel of size 100x50x50mm i/c cutting, welding, grinding and finishing etc as per job requirement.
SITC of modular/combinable Polycarbonate insulated outdoor type housing shock proof, Weather proof, rust proof, UV resistant, Halogen free, silicone free, protection class: II safe, IP 65 according to IEC 61 439-2, IEC 60 999, DIN EN 50 262, DIN 43 880, IEC 60 529/DIN VDE 0470 Teil I, the DB should have ASTA certification by CPRI and manufacturer routine Test Certificate should be provided, totally insulated, having internal embedded gasket with provision of cable entry through glands. The panel board should have following control panel MCB and accessories etc. complete with connections & interconnections etc. as required. Note 1: for mounting of metering & outgoing MCBs only box with hinged door with triangle lid to be used. Note 2: For mounting of 10HP FASD feeder pillar MS angle frame should be hot dipped galvanized and made out of MS angle of size 35 x 35 x 5 mm at the bottom as per site requirement. Note 3: All indicating lights and measuring instrument shall be protected by suitable MCB. The Panel sould consist of followings:- a) 32 A, FP, 10 KA, MCB (L&T) – 1 No. b) 18 A, TP, Power contactor (L&T) – 3 Nos. c) Side mounting Aux. contact block (L&T) -2 Nos. d) 6 -10 A over load relay (L&T) -1 No. e) Star delta electronic timer (L&T) -1 No. f) Single phasing preventor (L&T) -1 No. g) lluminated push Bottom with element (L&T) -2 Nos. h) LED indicating light R, Y, B (L&T) -3 Nos. i) 6 A, 10 KA, SP MCB (L&T) -4 Nos. j) TP digital VAF + PF CI 1 meter (L&T) -1 No. k) CT 30/ 5 A (AE) -2 Nos.
Renovation of complete pumps by replacing of their bearings, damaged body studs, gland packing , GM sleeve, bearing lock, chucknut for impeller etc and greasing / oiling and making proper alignment for smooth running. i/c Repairing of shaft by making of bearing seats on both side and impeller seat on front side at shaft by remateling and machining with complete finishing for accurate size of bearing and impeller
Fabrication & fixing of Fibre glass sheet shed on the scour pump in order to protect the motor, pump from rain to avoid these equipment getting rust and moisture. This includes supply of M.S. pipe of 25mm dia upto the height of 40” fixing of fibre glass sheet on the roof M.S structure with the help of fasteners.
Installation charges of above all items including foot valve, coupling, packing sheet, sluice valve, welding of flanges with pipe, bend, tee etc. connecting of pipe line with pump set along with above all items as per requirement of site.
Painting & primer charges of complete system with one coat of primer & minimum two coat of enamel paint as per required shade.Make of paint & primer:- Berger / Asian / Nerolac / DJB Approved.
Testing & commissioning charges of complete system on full load.
K R ELECTRICAL
V.K. ENTERPRISES
SUSHMA ENTERPRISES
MK ENGG.CO.
Darshan Engineering Works
KAMLESH ENGINEERING WORKS
NEW INDIA ELECTRICALS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .