Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.0 LAccepted-AOC | L1 | Accepted-AOC Eligible | |
| 2 | L2₹11.5 L+₹1.5 L (15.4%)Rejected-AOC | L2 | Rejected-AOC Eligible | |
| 3 | L3₹11.7 L+₹1.7 L (17.3%)Rejected-AOC 02 SIDDHANT RESIDENCY NEAR AMBAD POLICE STATION SINHASTHA NAGAR CIDCO NASHIK MAHARASHTRA 422009 UDYAM MH 23 0069304 | NASHIK | MAHARASHTRA | 422009 | L3 | Rejected-AOC Eligible | |
| 4 | L4₹12.6 L+₹2.6 L (25.6%)Rejected-AOC MATHOSHREE PLOT NO 55 SR NO 787 A BEHIND ASHWANI HOSPITAL GOVIND NAGAR NASIK 422 009 | NASIK | NASHIK | MAHARASHTRA | 422009 | L4 | Rejected-AOC Eligible | |
| 5 | L5₹13.9 L+₹3.9 L (38.5%)Rejected-AOC | L5 | Rejected-AOC Eligible |
Tender Value
Refer Docs
EMD Value
₹26,000
Closing Date
25 Oct 2021, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE AF NAGPUR
CWE AF VAYUSENA NAGAR NAGPUR
PROVISION OF 02 NOS. SD SETS (15 KVA) FOR SECURITY LIGHTS AT AF STATION BORGAD
2021_MES_474936_1
80477
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF OJHAR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE AF OJHAR
₹26,000
Yes
24 Nov 2021
14 Sept 2021
1 Nov 2021
14 Sept 2021
25 Oct 2021
11 Oct 2021
60 days
Amount
Supply, installation, testing and commissioning of silent diesel engine driven factory assembled, floor mounted generating set with suitable Automatic on Mains failure control panel (AMF) mounted inside canopy suitable for out put, 15 KVA, 415 volts, 3 phase, 4 wire, 50 HZ,1500 RPM Water Cooled complete with safety control and metering equipment mounted on & including common base frame on new PCC foundation as recommended by manufacturer all as specified and comprising of the following :- Prime Mover: Directly coupled diesel engine, radiator (with blower fan, Standard integral set-mounted radiator system, designed and tested for 50° C ambient temperatures) water cooled-Corrosion inhibitor/liquid coolant suitably of matching 12 KW under NTP condition of BS:5514 for driving 15 KVA capacity alternator, electric start, four stroke liquid cool technology confirming to BS : 5514 and IS -10000 suitable for prime duty generating set for continuous running of 12 hours and capable for taking 10% over load for 1 hours in every 12 hours complete with following accessories :- (i) Water Cooled Engine with turbo Charger (ii) Fly wheel to suit coupling with guards. (iii) Air cleaner with filters (Dry type, (iv) Lubricating oil cooler and filter. (v) Fuel and lub filters (vi) Anti- vibration pad as recommended by manufacturers (vii) PT pump with governor of suitable capacity & flywheel housing and flywheel to suit single bearing alternator
(viii) Electric starters-self starter 12 volts DC (ix) 12 volts, 90AH dry maintenance free battery supplied along with the in charged condition along with flexible copper battery lead and connector & Battery charging alternator (x) Standard safety device. (xi) Fuel tank (Not less than 62 litre capacity) ,Tank complete with level indicator, fuel inlet and outlet, air vent , drain plug, including arrangement for direct filling) for full running capacity of DG set for min 08 hours enclosed within the canopy all as per CPCB with level indicator, fuel outlet drain plug. (xii) Exhaust system shall be provided with thermal insulation by using fire retardant/non igniting foam confirming to BS-4735 to prevent excess heat radiation on the engine and sage for operator, Critical grade silencer suitable optimized to meet stringent sound emission standards laid down by MOEF/CPCB, Stainless steel exhaust flexible bellows to meet emission norms & Exhaust system shall not be based on (Exhaust Gas regeneration) i.e. EGR (a) Integrated DG set controller (DG set should have a microprocessor based controller with LCD display for engine and alternator parameter) Integrated Electronic Control Panel (displaying the following Engine parameters): (1) Engine Metering: Oil pressure, Engine temperature, starting battery voltage, Engine running hours. (2) AC Alternator Metering : L-L Voltage and L-N Voltage, (3) Current (phase and total), KVA (phase and total), Frequency, KVAH, KWAH (4) Engine Protection : Low lube oil pressure, Battery Over/under/Weak Volts, Fail to Crank/Start, Sensor failure, cranking lockout MODBUS interface (RS 485 RTU) (5) AC Alternator Protection : Over/Under Voltage, Over/Under Frequency, Loss of AC sensing.
(6) Safety Control (Trip & Indication) (7) High water temperature (hwt) (8). low lube oil pressure (llop) (9) Battery Over/Under/Weak Volts. (10). Failed to start, over crank lockout stop pressed. (b) Alternator: 15KVA/12 KW at 0.8 power factor, self regulated 3 phase with neutral 415 volts ,50 Hz ,1500 RPM with brushless excitation, Band of Voltage regulation + 1% of rated voltage, from no load to full load, Insulation Class "H" The alternator generally confirms to BS:2613 / IS:4722. The silent feature of alternator are as under :- (i) Casing protection : As per IP-23 (ii) Overload capacity : 10% of one hour in any 12 hours of operation (iii) permanently lubricating bearing. (C) Repair/Maint tools to be supplied with DG set are as mentioned in particular specification. (d) ACOUSTIC ENCLOSURE : Floor Mounted Acoustic Enclosure suitable for 15 KVA DG Set as per CPCB Norms of Make: Cummins or Kirloskar KOEL or Equivalent in Mahendra & Mahendra. The DG set shall be guaranteed against faulty workmanship/poor material quality and against failures due to the same, for minimum of two years or 5000 Hrs of operation whichever is earliest, from the date of commissioning complete all as specified and directed. Make Engine : Model No of Cummins C15D5P , Gen Set Engine Model No X1.3TAA-G1 or equivalent in Kirloskar / Greaves Cotton Ltd / Mahindra. Make of Alternator: Stamford (CGT) or equivalent in Kirloskar/ Crompton Greaves.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3½ core Complete all as specified and directed .
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core Complete all as specified and directed .
Material & labour for fixing of DWC pipes it should be flexible & should allow deformation in diameter as well as in joints under external load & soil natural movement , socket & spigot joint with elastometric sealing ring, it should be highly corrosive resistant & it should be impact resistant, chemical resistant, flexible, light weight & it should have hih flow capacity of 63/50 mm outer and inner dia complete with coupler, elbows, joints and necessary joints required for completion of work all as specified & as directed.
Material & labour for fixing of DWC pipes it should be flexible & should allow deformation in diameter as well as in joints under external load & soil natural movement , socket & spigot joint with elastometric sealing ring, it should be highly corrosive resistant & it should be impact resistant, chemical resistant, flexible, light weight & it should have hih flow capacity of 50/38mm outer and inner dia complete with coupler, elbows, joints and necessary joints required for completion of work all as specified & as directed.
Excavation in trenches not exceeding 1.50 mtr wide and not exceeding 1.50 meter in depth for foundation and getting out in hard soil all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the pipes have been laid and tested complete all as specified and directed.
Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point complete all as specified and directed.
Material and labour for earthing in repair including taking out GI plate with pipe and complete with galvanised steel earth plate electrode 600x600x6mm thick,burried directly in ground (earth pit not less than 2.25 Mtr deep below ground level ) with top edge of the plate not less than 1.5 Mtr below normal ground level,connected to galvanised iron strip 25x4 mm as earth lead by means of bolts,nuts ,washer and check nut of galvanized steel, protected by and including GI pipe 50 mm bore (light grade) and connected to main switch / MCB DBs box point / LP test point as directed and including cement concret pit in 1:2:4 type B1 using 12.5mm graded aggregate, with cast iron mild steel frame embedded in the concrete enclouser fineshed flushed & CI cover 10 mm thick of size (300mmx300mm CI) having locking arrengment hinged to CI frame all as shown under electrical plate of SSR Pt - I 2009 and as directed including painting the external surface of chamber & cover with enamel paint in diffrent colour as directed and writing earth results & date of test carried out with white paint on black painted background, wiremesh funnel 20 mm bore GI pipe medium grade for watering adequate quantity of charcol and common salt in alternate layer of 15cm 3ft x 3ft thick all around the electrode including necessery excavation & earth work in any type of soil , rock /strata/ other if any, complete testing on completion all as directed.
Note:- i) Filling the pit with black cotton soil brought at site.from out of defence land. ii) The excavated soil will be removed iii) Earth resistance should be less than 4 ohm. iv)GI strip up to 7.5 RM with GI pipe 40mm dia is included in the quoted rate. (v) If resistance value is found more than 04 ohm, any time after execution upto end of defect liability period contractor has to do needful action within 07 days without any extra cost to bring the value less than 04 Ohm, failing which the cost of the earthing (as quoted by the contractor or prevaling in the market whichever is high will be recovered from the contractor.
Supply and fix LDPE UPVC Pipe 6 Kgf/Cm2 & plain UPVC PIPE fitting in trenches / Surface for water of 15 mm outer dia complete all as specifeid and directed.
Cutting existing steel tubing for alteration or additions and screwing existing steel tubing (or lengthening screw on pipe from connector ) 20mm dia Complete all as specified and directed.
Supply anf fix stop valve, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for fixing with 15 mm iron pipe or for union complete all as specified and directed.
Paras Electricals
SHRI SULAI ELECTRICALS
DURGAI ELECTRICALS
M/s.TIRUPATI BUILDERS
NATIONAL ENGINEERING CORPORATION
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .