CWE KIRKEE
Headquarters CWE Kirkee, Military Engineer Services, Range Hills Road, Kirkee, Pune-411003
REPAIR/SERVICING OF HT VCBs, HT PANELS, OCBs AND MAINT OF UNDERGROUND HT CABLE WITH CONNECTED WORK UNDER AGE EM II IN GE (C) KIRKEE
2021_MES_488050_1
CWE/KKE/TOKEN-26 OF 2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
KIRKEE
As per tender documents
5 documents required · 5 mandatory
₹1,000
Yes
GE CENTRAL KIRKEE
₹1.1 L
Yes
8 Feb 2022
12 Nov 2021
17 Dec 2021
12 Nov 2021
15 Dec 2021
3 Dec 2021
13 Nov 2021 - 26 Nov 2021
Amount
Excavation in trenches n. exc. 1.5 mtr wide and n. exc. 1.5 mtr in depth and n exc 10 sqm on plan for laying of underground cable and getting out in hard / dense soil complete all as specified and directed.
Excavation in trenches n.exc. 1.5 mtr wide and exc. 1.5 mtr but n. exc 3.0 m in depth and n exc 10 sqm on plan and getting out in hard / dense soil complete all as specified and directed.
Returning, filling in excavated soil in trenches including spreading, leveling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and directed
Removing of excavted soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
M&L for sand/fine dust cushioning to under ground cable providing with a layer of and 08 cm thick before laying of cable and 15 cm after laying of cable in trenches, hand punning complete all as specified and directed by Engr-in-charge (Note: Thickness after punning down shall be measured and paid)
Supplying and laying precast concrete HT cable cover, class HV, type flat , size 300mm x 180mm x 40mm complete for protection of underground cable complete all as specified and directed.
Supply, laying in replacement, in trenches /ducts/fixing on pole/STR with suitable size of GI clamps made out of GI strip 32 mm x 6 mm, XLPE insulated, screened, earthed, PVC bedded, galvanised steel strip, electric power cable (heavy duty) of size 3 x 120 sqmm with aluminium conductor suitable for 22 KV (E) grade as per relevent IS including latest amendment for IS testing, commissionong all as specified and directed including taking out of old burnt out cable as directed by Engr-in-Charge at site. Note:- (a) Necessry tests to be conducted at site before and after laying of HT cable and reading shall be recorded jointly and test report to be submitted in triplicate to the Engineer-in-Charge. The cost of the same shall be deemed to be included in the unit rate quoted above.
All as per item No 7 above but cable size 3x300 sqmm- ditto
Supply, installation, commissioning and testing of HT 22 KV, outdoor type, Porcelain Clad Vacum Circuit Breaker (PCVCB), 1250 Amps, 50 Hz, 3 phase, Rated short circuit current 25 KA/3 Sec,110 V DC Shunt tripping and closing coil, spring charging motor rated 230 V AC, spring charge indicator, auxilary contacts: 6NO+6NC, sutomatic safety shutters, mechanical on/off push button, including suitable CT, PTand relays all as per MSETCL specification and as per relevent IS including latest amendment for IS testing including taking down old HT switchgear any type all as specified and as directed at site by Engr-in-Charge. Note: (i) Contractor should visit the site before quoting the rate. (ii) Rates are including all work for installation, commissioning and testing at site with all necessary tools and safety equipments. (iii) Disconnecting existing HT cable from old swithgear and connecting to new PC VCB with necessary tools and equipments at no any extra cost.
M&L for servicing of HT vacuum circuit breaker (HT VCB) and SF6 of capacity 630/800A, 22 KV, 350 MVA for servicing, repairs, replacement of defective/worn out minor parts / components and reassembling complete comprising of the following including testing and commissioning to the entire satisfaction of Engineer-in-Charge:- Make of HTCBs :- Powercare Electrical , ABB as approved by GE Note:- This item continue from 10.01 to 10.13
(a) Dismantling the HTCB from the enclosure consisting of vacuum interrupter assembly, socket contacts , checking the serviceability of the following parts carefully including cleaning, adjustments, replacement of defective/worn out parts and re-assembling the unit complate.
(b) Cleaning the external surface of bushings with CTC or Liquid ammonia to remove the accumulation of dirt or any other deposits. Inspection of bushings and make sure that vibration due to breaker operation have not caused the bushings to move resulting misallignment of contacts.
(c) Checking the vaccum interrupter assembly and contacts. Checking the allignment of contacts and setting the contact surfaces to bare firm and uniform pressure and adjust the gap as per manufacterurs tolerance. Badly potted contacts needs to be replaced. Note: Contacts shall be ordered separately.
(d) Checking the breaker bushing of bus bar and circuit side inspecting the internal surface carefully for any charging/trackings,replacement of bushings.
(e) Dismantling the spring charging mechanism of the HTCB, checking the operations of the closing/tripping through closing/tripping coils electrically as well as manualy charging including cleaning adjustments complete for smoothly functionig
(f) Checking the condition of the spring charging motor along with gear box including servicing to the motor commulator bushes, lubrication of bearing surfaces etc.
(g) Checking the ratchet wheel assembly, driving and charging parts including replacement of defective ratchet wheel and parts.
(h Checking the type and release prop and dash pot assembly making necessary adjustment
(j) Checking the operating mechanism of the breaker and ensure its operation freely through entire stroke.
(k) Checking of operating voltage at mechanism terminals and tripping arrangement for positive tripping. Contacts to be examined for their condition and operation.
(l) Review the adjustment of all pressure switches and lockout devices.
(m) Inspecting all bolts, nuts, pins and coller pins are in place and they are tight and opened properly.
(n) Inspection, cleaning and relubrication of circuit breaker
All as per item No 10.00 here-in-before but HT VCB of capacity 1250 Amps of make HTCB all as -ditto-
M&L for servicing of HT oil circuit breaker (HT OCB) of capacity 800/400A.22 KV, 350 MVA for servicing , repairs, replacement of defective/worn out minor parts / compounents and reassembling complete comprising of the following including testing and commissioning to the entire satisfaction of Engineer-in-Charge:- Make : Kirloskar Electric Note:- This item continue from 12.01 to 12.17
(a) Dismatling the HTCB by separating the upper chamber consisting of contacts and cross bar assembly from the oil tank, checking the serviceability of the following parts carefully including cleaning, adjustment,replacement of dffective/worn out parts (excluding parts) re-assembling the unit complete:-
(b) Drain out the oil from the tank, cleaning the tank by removing the sediments at the bottom, checking the condition of the tank liners and gaskets including replacement of defective gasket/tank liners. Testing of oil, if shows signs of moisture, carbonisation or dirt filtering and testing and replacement if necessary. Ensuring the oil guage indicating properly the actual oil level. Checking the condition of all gaskets to ensure that they are sealed properly and arrest any leakages by replaceing the gaskets or sealing the box outside and inside ,with necessery sealing material etc.,
(c) Checking the operating mechanism of the breaker including cleaning, lubrication to all moving parts of the breaker mechanism like hold on catch assembly, trip bridge, trip lever and assembly, charging motor, belt, latchgear and worm gear assembly clutch shaft etc for proper operation both electrically and manualy. Checking the operating mechanism of the breaker and ensure its operation freely through entire stroke. Parts which shows excessive wear and tear to be replaced or adjusted as per manufacterurs tolerance.
(d) Checking of operating voltage at mechanism terminals and tripping arrangement for positive tripping. Contacts to be examined for their condition and operation. Dress the pitted contactcts and replace if necessary.
(e) Checking the raise /lower mechanism in three position(Draw out,test,service) and lubrication to the moving parts.
(f) Review the adjustment of all pressure switches and lockout devices.
(g) Inspecting all bolts, nuts, pins and coller pins are in place and they are tight and opened properly.
(h) Inspection, cleaning and relubrication of circuit breaker
(j) Checking the auxiliary contact assembly, cleaning/replacement of contacts, adjustment of operating lever and lubrication to moving parts and apply petroleum jelly to the contacts.
NOTEs for item No 10.00 to 12.00:-
(l) Checking of operating voltage at mechanism terminals and tripping arrangement for positive tripping. Contacts to be examined for their condition and operation. Dress the pitted contactcts and replace if necessary.
(m) Review the adjustment of all pressure switches and lockout devices.
(n) Inspecting all bolts, nuts, pins and coller pins are in place and they are tight and opened properly.
(a) Cost of additional hardwares like bolts,nuts , washers, spring washers, prtroleum jelly or any other item not included in the list of supply only spare parts etc, to put the breaker in serviceable condition is deemed to be included in the rate quoted .
(b) The major spare parts requiered to be replced are measured and paid for separatly.
(c) Old unserviceable spare parts removed from the breakers shall be accounted for under schedule of credit
(d) Contractor should visit the sire before quoting the rates.
Repair /Maint/Reconditioning of breaker In-Out trolly, including proper allignment of wheels, wheel moving channel/rail, ramp etc, repairing of stoper pins, locking pins, replacement of dammaged wheels, fixing base etc complete for smooth operation of trolly for in/out and up/down etc complete all as specified and directed . Note: Rates including necessary welding, bending, staightning work if required as per site requirement.
Repair/maint of HT Panel Board duly Decarbonsing/cleaning, HT panels board of 22 KV cubicle type, consists of bus bar chamber, circuit chamber and metering chambers, by opening the spout/bus covers inspecting the bus bar joints, cleaning of bus bars, checking the bus bar spouts and circuit spouts for any flash overs/tracks, applying Becktolred solution to the bus bars and spouts having moderate tracking, replacement of bus bar/circuit spouts in case of spouts subjects to heave tracking, applying HT insulated red compounds/Monoplist compound at the bus bar joints after tightening of joints, cleaning of bus bar insulators and bus bars with CTC and improving megger with inject to ensure proper decarbonisation and re-assembling complete including fixing of new bus bar supporting insulators if required to be replaced all as directed by Engineer-in-Charge Note: Cost of cleaning and insulating material included in the unit rate. Contractor should visit the site before quoting the rates.
M&L for dismentaling of unserviciable power pack unit and S&F new unit in repacement commissioning & testing of power pack rating 110 volt/230volt AC input 30 volt DC output for auxillary supply including necessary conyrol wiring in existing HT panel complete all as specified and directed.
S&F digital type multifunction meter VAF ,PF 3 Phase 4 wire AC 440 Volts 50 Hz of rating 5 Amps with Class 1.0 with Provision for housing the meter & control wiring with 2.5 Sqmm PVC insulated unsheathed multistranded copper conductor including testing & Commissioning complete Make Schneider Cat No EM 6459 or equivalent of HPL make all as specified and as directed by the Engineer-in-Charge. NOTE:- 1. During the replacement of any relay, modification of panel, necessary control wiring , testing, calibration, setting with load requirements etc., are deemed to be included in the unit rates quoted. 2. Contractor should visit site before quoting the rates.
Repair / reconditionong of HT CTs by removing of all dust cleaning of terminals improving of megger value with inject and Checking & testing the 22 kv CTs for its ratio and connecting with new nutbolts complete
Repair / reconditionong of HT PTs by removing of all dust cleaning of terminals improving of meager value with inject and connecting with new nutbolts complete all as specified and directed.
M&L for removing of defective current tranceformer and S&F in old location 22 KV epoxy resin cast HT CT Ratio as per site requirement Dual core Class 5P 10 for protection, metering Class 1.0 as per existing size/shape suitable for optimum perforemance of relays Make: Kappa/CG or equivalent as approved by GE
M&L for removing of defective potantial tranceformer and S&F in old location 22 KV epoxy resin cast HT PT Ratio 22KV/110V Class 1.0 200 VA burden suitable for optimum perforemance of relays Make: Kappa/CG or equivalent as approved by GE
M&L for HT fuse for PT 22 KV 25 KA breaking cap of rating as per existing for the perticular HT panel as per existing shape and size tubeler or box type complete with fuse holder all as specified and directed. Note: Fuses shall be checked at site and order shall be done as per sample
M&L for disconnecting HT/LT XLPE cable of any size from structure/pole/transformer for finding fault, defect rectification HT/LTcable laid in trenches or any location by locating fault with the help of electronic fault locating machine comprising of surge generator pulse, ECHO fault locator with high frequency distance calculator etc.including and additional excavation in normal or any type of strata required for exposing the cable fault. removal of deteriorated portion of cable treating of cable and keeping the same ready for jointing work for cable of any size. The fault locating equipments will be brought to site within the 6 hours of instruction from Engr-in-Charge as specified and as directed. Note: 1. Complaint will be notified to contractor on mobile phone at any time between 0800 hrs to 2200 hrs and will be rectified within 6 hours after notification, failing which Rs 500/- per day per complaint will be recovered. 2. Rates included necessary earth work in any type of strata or Road or Tank road for opening the cable and prepare the cable ready to jointing work and making good to match with existing finishes
M&L in repairs HT heat shrinkable outdoor / indoor type end termination cable jointing kit suitable for 22 KV 3 core 120-/185 sqmm XLPE aluminium conductor cable including disconnecting of cable and removing of old jointing kit complete all as specified and as directed.
All as per Item Ser No 23 above but cable size 300 Sqmm 3 core -ditto-
M&L in repairs HT heat shrinkable strait through cable jointing kit suitable for 22 KV 3 core 120-/185 sqmm XLPE aluminium conductor cable including disconnecting of cable and removing of old jointing kit complete all as specified and as directed.
All as per Item Ser No 25 above but cable size 300 Sqmm 3 core -ditto-
M&L in repairs HT heat shrinkable indoor type end termination cable jointing kit suitable for 11 KV 3 core 95 sqmm XLPE aluminium conductor cable including disconnecting of cable and removing of old jointing kit complete all as specified and as directed.
M&L in repairs HT heat shrinkable strait through cable jointing kit suitable for 11 KV 3 core 95 sqmm XLPE aluminium conductor cable including disconnecting of cable and removing of old jointing kit complete all as specified and as directed.
M&L for rubber insulating mating of HT 22 KV rating 5 mm thick and 1 mtr width, As per IS, all as specified and as directed.
M&L for preparation of steel surfaces of existing MOCB/SFS breaker cubical panel including cleaning/scrapping of old painted surface, removing all the scrapped of paint particals from the panel using the proper vaccum cleaner to the complete satisafication of engr-in-charge, applaying two coats of synthetic enamel paint by using of spray machine to finish the surface glosy of colour or/shade approved by Eng-in-charge commissioning of breaker after completing the job include marking of MES/SM No, incomoming, outgoing to or from etc all as specified and directed. Note :-(a) The quoted rate is deemed to the inclusive of painting details pertaning to respective breaker like - details of CT & PT connected, caliberated and set parameters of protection relay installed details of transformer fed by respective HV breaker, etc all as specified by Eng-in-charge on the inside of the panel door/wall covered with transparent sheet all as specified and as directed.
Dismantling old unserviceable cable ducts from within the panel, S&F PVC cable ducts of size of size 45x30 MM including drawing existing cable through the ducts and commissioning the panel all as directed and specified by Engr-in-Charge.
S&F in repairs 2.5 Sqmm multistranded copper conductor cable, S/C, FRLS wire for control circuit of panel complete in various HT panels all as specified and directed by Engr-in-Charge.
M&L for earthing complete with copper earth plate electrode 60×60cm×3mm thick electrode burried directly in ground (earth pit not less than 2.25 m deep below GL) with top edge of the plate not less than 1.5 m below the normal ground level connected with 20×3mm copper strip as earthing lead by means of bolts, nuts, check nuts and washers of copper including necessary excavation & earth work in any type of soil strata, with and including PCC chamber in PCC (1:2:4), type B1, using 20 mm graded stone aggregate, RCC Cover as specified with watering arrangement with funnel internally secured with wire mesh with 20 mm dia medium grade GI pipe for watering, 40 mm dia light grade Gl pipe for lead protection in and including alternate layer of charcoal dust and common salt complete all as shown in electrical plate No 3 of SSR Part-I (2009) all as specified and indicated including testing on completion including retrieving of old GI earthing as directed by Engineer-in-Charge.
M&L Earth continuity copper conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. of size 20x3mm all as directed by Engineer-in-Charge.
M&L cross arms, bracing, supports, clamps and back plates MS sheet fabricated from structual steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape or size for repair to panels, duct cover and as indicted and inclusive of one primer coat one under coat and two finishing coat of aluminium /oil paint all as specified and as directed.
M&L for taking down old Lightning arresters and s&F new LA expulsion type complete, 22/33 KV capacity with all fittings, transmission class, discharge capacity 65 kilo amp suitable for 22/33 KV supply all as specified and as directed.
M&L for replacement of batterry inter connecting lead / srtip with terminal and nut bolt mabe from lead metal as per sample for connecting of batterries in series all as directed at site.
M&L for taking down burnt jumpers and M&L for jumper connection between GOD and drop out fuses and transformers with Jummpers made with copper strip 20x3mm as a conductor duly insulated 1.5 mtr long with copper nut bolt and washers both ends and PVC sleeves, 22 KV grade, high tension, with colour code all as directed by Engr-in-Charge at site.
M & L for Checking of DC circuit complete from batterry bank to HT panels for proper supply to HT panel cotrols for smooth fuctioning of panels complete all as spcified and directed.
Star Electrical
SHAILENDRA B TULSANI
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .