Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹69,999Accepted-AOC 852 EKTA VIHAR 1 C NEAR ANAND NAGAR 9 B PATIALA 147001 | PATIALA | PATIALA | PUNJAB | 147001 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹82,500+₹12,501 (17.9%)Rejected-Finance 0 NGG POWER TECH INDIA PRIVATE LIMITED VILLAGE JHOLAN MAJRA PO POLIAN BEET TEHSIL HAROLI UNA HIMACHAL PRADESH 174503 UDYAM HP 12 0000141 02AAFCN4843C1ZX B M R MII STATUS AS VERIFIED | UNA | HIMACHAL PRADESH | 174503 | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹93,000+₹23,001 (32.9%)Rejected-Finance H NO 597 SEONA ROAD RANJIT NAGAR PATIALA PB 147001 | PATIALA | PATIALA | PUNJAB | 147001 | L3 | Rejected-Finance Being L3 | |
| 4 | L4₹98,500+₹28,501 (40.7%)Rejected-Finance 3 3430 NICHOLSON ROAD KASHMERE GATE DELHI DELHI DELHI 110002 | CENTRAL DELHI | DELHI | 110002 | L4 | Rejected-Finance Being L4 | |
| 5 | L5₹99,000+₹29,001 (41.4%)Rejected-Finance 300 PREM BASTI 10 SANGRUR SANGRUR PUNJAB 148001 | SANGRUR | PUNJAB | 148001 | L5 | Rejected-Finance Being L5 |
Tender Value
Refer Docs
Closing Date
10 Jul 2021, 5:00 pmClosed
CWE PATIALA
HQ CWE PATIALA
Repair of 200 KVA transformer aluminum wound in New Cantt area under GE North Patiala
2021_MES_453722_1
3001/JOB/2021-22/26/E3
Open Tender
Electrical and Maintenance Works
Works
30 days
GE NORTH PATIALA
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
Exempted
20 Jul 2021
23 Jun 2021
12 Jul 2021
23 Jun 2021
10 Jul 2021
25 Jun 2021
23 Jun 2021 - 24 Jun 2021
Amount
Disconnecting and taking down of transformer indoor/outdoor type 11000/415 volts having capacity 200 KVA, transportation to contractor’s workshop for repairs, strip opening of transformer after unscrewing nuts /bolts screws and connected accessories such as breather, conservator tank, temp gauge, taking out the core for replacement of defective parts and transportation back to the site after repairs and installing, connecting up, testing and commissioning at the site complete all as specified and directed. Notes : - (a) Transformer oil shall be drained out by the contractor in suitable capacity MS drums to be arranged by the contractor. The said drained out transformer oil shall be refilled in the transformer duly dehydrated after repair and the cost thereof shall be included in unit rate quoted against the respective item of this schedule. (b) Fixing/Installing HT & LT coils in core shall be measured and paid for separately under respective item of this schedule. (c) Transportation charges for transportation of transformer from site to workshop and after repair, workshop to site shall be borne by the contractor and cost thereof shall be deemed to be included in the unit rate quoted for this item. 1.01 (d) The said transformer shall be repaired in reputed workshop as decided by the GE. (e) Note – Coil to be replaced shall have same number of turns, gauge insulation value matching with manufacturer’s design. 1.02 (e) Testing of transformer after repair shall be carried out with the following test and the cost of testing shall deem to be included in unit rate quoted against this item :- (i) The IR value of the dried winding before inserting the core in the shell shall not be less than 750 mega ohm with 5000 volts megger and record of the same shall be maintained. (f) Painting of transformer with one coat of super enamelled paint after cleaning the oil from transformer body complete all as specified and directed. 2.00 Supply and replcament of HT and LT coils as provided below: 2.01 Supply and replacement of HT coils made out of super enameled, aluminium winding wire of same gauge and same no of turns as per manufacturer design and size of coil.of transformer having capacity 250 KVA all as specified and directed - 72 Kg 2.02 Supply and replacement of LT coils made out of aluminium strip of same gauge and same no of turns as per manufacturer design and size of coil for transformer having capacity 250 KVA all as specified and directed- 48 Kg
NGG Power Tech India Private Limited
Jawandha Enterprises
M/s Anil Kumar and co.
AGGARWAL & CO
Swami Engineers
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .