Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.6 LAccepted-AOC 296 SECTOR 15 PANCHKULA HARYANA | L1 | Accepted-AOC L1 | |
| 2 | L2₹7.6 L+₹64,930 (9.36%)Rejected-AOC 262 1 NEAR MANAV CHOWK NEW GRAIN MARKET AMBALA CITY HARYANA HARYANA 134003 | AMBALA | HARYANA | 134003 | L2 | Rejected-AOC L2 | |
| 3 | L3₹8.5 L+₹1.6 L (22.9%)Rejected-AOC | L3 | Rejected-AOC L3 | |
| 4 | L4₹10.4 L+₹3.5 L (50.2%)Rejected-AOC | L4 | Rejected-AOC L4 | |
| 5 | L5₹10.8 L+₹3.8 L (55.5%)Rejected-AOC | L5 | Rejected-AOC L5 |
Tender Value
Refer Docs
EMD Value
₹21,600
Closing Date
14 Apr 2021, 6:00 pmClosed
SH A P SINGH, IDSE, SE
HQ CWE CHANDIMANDIR
CA NO. CWE/CHM(U)-103/2020-21 REPAIR/MAINT OF AC PLANT 2 x 56 TR IN MANEKSHAW AUDITORIUM ATCHANDIMANDIR CANTT
2021_MES_431670_1
CWE/CHM(U)-103/2020-21
Open Tender
Miscellaneous Works
Item Rate
365 days
HQ CWE CHANDIMANDIR
Class E cat c (i)
9 documents required · 9 mandatory
₹500
Yes
GE (U) CHANDIMANDIR
₹21,600
Yes
29 May 2021
18 Mar 2021
16 Apr 2021
19 Mar 2021
14 Apr 2021
1 Apr 2021
Amount
Comprehensive maintenance of central AC plant of capacity 56 TR x 02 Nos (Chilled water and strip heater type) air cooled type installed at Manekshaw Auditorium comprising Quarterly Inspection and servicing by rep/mechanic of Blue Star Company including servicing, testing of circuit plant, programming of PCB of the plant /AHU and submit its report for serviceability. First such inspection and servicing shall be carried out within 21 days from the date of commencement of work given in work order No 01. (Replacement of parts whenever and wherever required except minor items mentioned in notes below and painting etc shall be measured and paid separately under srl item No 2 to 30). The plant includes the following:- (i) Multi stage reciprocating compressor: Model. XACYS2060R2. Make: Blue Star (Capacity 56 TR each) (Two working and one stand by) -02 Nos (ii) Electrical control panel (LT) 440 volts, 680 Amps -02 Nos.
(iii) Condenser and chiller of shell and tube type -02 Nos (iv) Condenser water pumping set of 3 phase, 44000 ltrs - 02 Nos. (v) Chilled water pumping set of 15HP, 3 phase, 440 volts-02 Nos. Make: Beacon. (vi) Paharpur induced draft cooling tower, 204 Ton, with 15 HP-01 No wheather proof, gear driven electrical motor. (vii) All other connected items of the plants/ equipments/machines mentioned in respects of sub paras (i) to (vi) above. (viii) Air handling unit, blower, evaporating coil and other sections of humidification arrangements, electrical panels etc and all other connected items - 06 Nos. (ix) Water softening unit with monoblock pump 2HP-01 No. (viii) Air handling unit, blower, evaporating coil and other sections of humidification arrangements, electrical panels etc and all other connected items - 06 Nos. (ix) Water softening unit with monoblock pump 2HP-01 No.
Notes :- Following checks and duties shall also be carried out under this item:- (a) Checking the proper functioning of all Air Conditioning plants 2X 56 TR, one stand by and AHU's. make: Blue Star. (b) Checking of the plant machinary equipment and LT panel and maintaining the record quarterly, half yearly and yearly as directed by Engineer-in-Charge/JE on a format to be decided by the Engr-in-Charge. (c) Checking the earth test record for compressor/condensor pump set, Chiller pump set, cooling tower, LT panel and AHU's and maintaining the record half yearly and submit the record there of and filling of the water in earth pit to improve the earth resistance and proper maintenance of earth pits. (d) Materials and labour (s) required for replacement of minor items such as nuts, bolts, washers, lubricants (etc) including fixing charges are deemed to be included in the item rate quoted against item No 1 of BOQ. (e) Cleaning of AHU room and MInor spares such as nuts, bolts washer, aluminium lugs grease or any spare part required for satisfactory operation of AC plant upto 2000/- other than mentioned in this CA here -in-after are deemed to be included in unit rate quoted by the contractor.
Supply and charging of Gas R-407C suitable for 56 TR chiller plant after detecting and rectification of any leakage in system by using CO2 gas and flushing the complete system with Nitrogen gas complete all as specified and directed by Engr-in-Charge. Note :- (a) Gas to be brought by contractor at site from auth dealer in company sealed cylinder of 61 Kgs. (b) The unit rate inserted shall deemed to be included the cost of CO2 and Nitrogen gas to be used for leakage test and flushing and pressure test prior to charging the gas in plant.
S&F in replacement the fan belt of AHU fan suitable for capacity 11 KW blower motor complete all as directed.
M&L for Petty Repair to chiller pump 5.5 KW such as replacement of gland packing , bearing ,seal, coupling, shaft, nut bolts washer, etc all as directed.
M&L for rewinding the chiller pump motor of capacity 5.5 KW with suitable gauge of super enamelled branded copper winding wire including heating, varnishing including taking out un-serviceable winding complete all as directed. Make : Pump/ motor - Kirloskar or equivalent as approved by GE.
S&F and charging in replacement of expansion valve of capacity 30 TR complete all as specified and directed. Cat Part No 067N2188. Make - Danfoss or equivalent as approved by GE.
S&F in replacement dial type pressure gauge of Capacity 7 Kg/sq cm Squirel complete all as specified and directed. Make- Fiebig or equivalent as approved by GE.
S&F in replacement tempreture gauge as per existing model complete all as specified and directed. Make- Fiebig or equivalent as approved by GE.
S&F in replacement MCCB TP 415 V of capacity 250A, 35KA breaking capacity 1cs=1cu=100% with adjustable thermal & adjustable magnetic setting complete all as specified and directed.
S&F in replacement 3 pole power contactor of chiller pump AC1 rating 55A type MNX 40 complete all as specified and directed. Make - L&T cat. No. CS94190 or or equivalent as approved by GE
S&F in replacement 3 way mixing valve (rotary type) 80mm dia cat Part No DR 80 GFLA , VC 6013MC6000T , 6 sec. 6 VA valve actuator , 200-240 V AC 50/60 HZ. Cable 3 Way , ¾ inch lare (W/O ADPR) T 65 TS 110, IP 40 complete all as specified and directed. Make : Honeywell or Equivalent as approved by GE.
S&F in replacement, Actuator suitable for 3 way valve of cat Part No CN7234A2008 , 34Nm, 24 V AC/DC , 50/60 Hz, class 2, 110/95, sec 900 , IP 54 complete all as specified and directed. Make : Honeywell or Equivalent as approved by GE.
S&F in replacement Temperature controller Cat Part No T 2798-1-1000 complete all as specified and directed. Make : Honeywell or Equivalent as approved by GE.
S&F in replacement Fan motor suitable for 56 TR chiller complete all as specified and directed.
S&F in replacement Flow switch cat Part No FSW 1600 complete all as specified and directed. Make: Danfoss or equivalent as approved by GE.
S&F in replacement water temp sensor suitable for 56 TR chiller complete all as specified and directed.
S&F in replacement gun metal gate valve with iron wheel head, screwed both ends for 25mm bore pipe complete all as specified and directed.
M&L for rewinding of AHU blower motor of capacity 11 KW with suitable gauge of super enamelled branded copper wire including heating, varnishing including taking out old unserviceable winding wire complete all as specified and directed.
M&L for Petty repair to AHU blower such as replacement of seal, coupling, shaft , bush, bearing ,nut bolts washer, adjustment of allingment , shaft etc complete all as specified and directed.
S&F in replacement AHU air filter suitable for chiller plant of capacity 56 TR complete all as specified and directed.
S&F in replacement company made sealed (scroll) compressor unit of cap 18 TR of model No SY300A4PBB thermal protected with one year guarantee and commissioning complete all as specified and directed. Make: Danfoss or equivalent suitable for operating volltage 430-460 V, 60Hz as approved by GE.
S&F in replacement eliminator filter drier liquid line complete all as specified and directed. Cat pt No DCL 609S 023Z0037. Make - Danfoss or equivalent as approved by GE.
S&F in replacement 3 pole power contactor Ith =55A, i.e. AC-1=55A complete all as specified and directed. Make-ABB type code A30-30-10 CAT Part No 1SBL281001R10 or equivalent of any make mentioned in Appx 'B'.
S&F in replacement 3 pole power contactor Ith =30A, i.e. AC-1=30A complete all as specified and directed. Make-ABB type code A16-30-10 CAT Part No 1SBL181001R10 or equivalent of any make mentioned in Appx 'B'.
S&F in replacement MCB TP 32 A ,415V , having breaking capacity 10KA , 'C' characterstic all as specified and as directed. Make -ABB/ legrand /Schenider/ IndoAsian/ Havells/standard or any equivalent make mentioned in Appx 'B'.
S&F in replacement MCB TP 100 A ,415V , having breaking capacity 10KA , 'C' characterstic all as specified and as directed. Make -ABB/ legrand /Schenider/ IndoAsian/ Havells/standard or any equivalent make mentioned in Appx 'B'.
S&F in replacement of 6 mm thick nitrile rubber insulation on condensate drain piping of size 50/40 mm dia and fitting like valve flanges union etc complete all as specified and directed. Make:- Accoflex/ Armacell/ K Flex.
Taking out defective insulation over duct and preparing surface applying adhesive and insulating the duct with external thermal insulation 13mm thick nitrile rubber open cell acoustic form including insulating the joint with aluminium type all as specified and directed at site. Make:- Accoflex/ Armacell/ K Flex/Vidoflex.
Gas welding of AC MS pipe for arresting of water leakage complete all as specified and directed.
M&L Painting of cooling tower / Centre AC plant / Motor 56 TR after removing or old paint from surface of cooling tower and base /AC plant unit with synthetic enamelled paint after preparation of surface with spray painting complete all as specified and directed. Note - Colour of Paint as per existing on site approved by GE.
Repair / replacment of GI/MS pipe of AC duct in AC plant including opnening of duct ,refixing of ac complete all as specified and directed by engr-in- charge.
Repair / replacment of AC duct (GI FDF flange 'L' shape hallow prefile duct duly insulated) , in AC plant including opnening of old duct and fixing of new AC duct with all accessirise like nut, bolt, washer, ripiting of duct, complete all as specified and directed by engr-in- charge.
Repair / replacment of butterfly Stop valves, cast copper alloy screwed pressure, with crutch of butterfly handle, screwed both ends for iron pipe for unions and fixed,refixing of ac complete all as specified and directed by Engr-in- charge.
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for foundation etc or for laying pipe lines and cables and getting out as in hard/dense soil complete all as specified and directed.
Returning filling in including spreading leveling, watering and well ramming in layer not exceeding 25 cm in hard/dense soil, complete all as specified and directed.
Removing excavated material to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
Material and labour of XLPE armoured copper cable 1.5 Sqmm 5 core 1100v for AC Plant complete all as specified and directed Enger-in-Charge. Make of wire :- Havells/Grandlay/Finolex/RR Kable/Grandlay.
Material and labour of XLPE armoured copper cable 10 Sqmm 5 core 1100v for AC Plant complete all as specified and directed Enger-in-Charge. Make of wire :- Havells/Grandlay/Finolex/RR Kable
M&L earthing complete with galvanized steel plate electrode 60cmx60cmx6mm surrounded by charcoal & salt buried directly in a pit of depth not less than 1.5m below ground level with top edge of the earth plate at a depth of not less than 1.50m below ground level, connected to and including GI strip 25mmx4mm upto 7.5m length by means of bolts, nuts, check nuts & washers of galvanized iron, earth strip protected by galvanized steel pipe 40 mm bore (light grade) & connected to main control board including necessary excavation & earth work, disposal of surplus soil not exceeding 50m, in any type of soil. (The rate also includes for cost of charcoal & salt in alternate layers of 15 cm thickness, 20 mm bore GI pipe (medium grade) for watering, funnel, wiremesh, PCC chamber in cement concrete (1:3:6) type C-1, 40mm thick RCC(1:2:4) type B-1 cover & frame etc) complete all as indicated in electric plate No 3 of SSR 2009 Part I including testing complete all as specified and as directed.
Note : (i) Earthing result/data sheet will be prepared by the Contractor and submitted to Engineer-in-Charge. Earth resistance shall be to the entire satisfaction of Engineer-in-Charge and contractor will make all arrangements & provisions to get the desired reduction of resistance by artificial treatment/replacement of soil etc at no extra cost to department. (ii) GI protection pipe for earth lead shall be measured & paid for separately .
Supplying & fixing XLPE insulated PVC sheathed armoured heavy duty electrical LT cables with aluminium stranded conductor 1100 Volts earth grade of cross section area 400 sqmm, 3.5 core in trench/wall/pole complete all as specified and directed.
Supplying & fixing XLPE insulated PVC sheathed armoured heavy duty electrical LT cables with aluminium stranded conductor 1100 Volts earth grade of cross section area 120 sqmm, 3.5 core in trench/wall/pole complete all as specified and directed.
M&L for dry river sand in trenches for cable cushioning & protection including spreading, ramming all as specified and directed.
Supply & laying bricks well burnt for cable protection gap between the two adjascent brick shall be not more than 10mm, all as specified and directed..
M&L for PCC (1:4:8) (using 40mm graded aggregate) type D2 for foundation of poles struts & stay assembly etc all as specified & directed.
Repair/ replacment of cable tray for cable ,including welding nut-bolts washer etc screwed both ends and fixed,refixing , complete all as specified and directed by Engr-in- charge.
Supply and fix in replacement 3 pole power contactor MNX-A2 and MNX-A1 complete all as specified and directed. Make-ABB Legrand / Schenider / C&S / IndoAsian / Havells/ Standard or equivalent make specified in Appx 'B'.
Repairing of micro computor contactor model-XACYS2060R2 rated capacity 56 TR, Refrigerant -R-407C, charge qty 43 Kg , 400 V 3 ph-50Hz M/C SR No 53300B-L-12 complete all as specified and directed Enger-in-ChargMake Blue stare or equivalent as approved by GE.
Alpha Engineers and Builders
M/S W R traders
M/S Trilok chand sharma
CHADHA ENGINEERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .